ED 21 - 302
Split System Air Conditioners SkyAir [50Hz] (Pair and Twin-Triple-Double Twin)
LU Series — Heat Pump —
ED21-302
SkyAir LU Series (Pair) — Heat Pump — [50Hz] ............................ 1 1. Power Supply ..........................................................................................2 1.1 Pair Series................................................................................................2
2. External Appearance...............................................................................3 2.1 External Appearance................................................................................3
3. Functions.................................................................................................4 3.1 LU Series..................................................................................................4
4. Specifications ..........................................................................................7 4.1 General.....................................................................................................7
5. Dimensions and Service Space ............................................................17 5.1 5.2 5.3 5.4
Indoor Unit..............................................................................................17 Remote Controller ..................................................................................32 Outdoor Unit ...........................................................................................35 Installation Service Space for RY71LU, 100LU, 125LU, 140LU ............39
6. Piping Diagrams....................................................................................41 6.1 Indoor Unit + Outdoor Unit .....................................................................41
7. Wiring Diagrams....................................................................................45 7.1 Indoor Unit..............................................................................................45 7.2 Outdoor Units .........................................................................................54
8. Capacity Tables ....................................................................................57 8.1 Capacity Tables......................................................................................57 8.2 Capacity Correction Factor by The Length of Refrigerant Piping...........62
9. Operation Limits ....................................................................................63 9.1 Operation Limits .....................................................................................63
10.Sound Level ..........................................................................................64 10.1 Overall Sound Level ...............................................................................64 10.2 Octave Band Level .................................................................................65
11.Fan Performance ..................................................................................69 11.1 Ceiling Mounted Built-In Type ................................................................69
12.Air Velocity and Temperature Distribution.............................................71 12.1 Indoor Unit..............................................................................................71
13.Electric Characteristics..........................................................................77 13.1 RY35~60 ................................................................................................77 13.2 RY71 ......................................................................................................78 13.3 RY100~140 ............................................................................................79
14.Option List .............................................................................................80 14.1 Indoor Unit..............................................................................................80 14.2 Outdoor Unit ...........................................................................................83
15.Field Piping and Wiring .........................................................................84 15.1 Field Piping.............................................................................................84 15.2 Field Wiring ............................................................................................86
SkyAir LU Series (Twin, Triple, Double Twin) — Heat Pump — [50Hz] .................................................... 87 1. Features ................................................................................................88 1.1 What are Twin, Triple, Double Twin systems? .......................................88
2. Model Name and Power Supply............................................................89 2.1 Twin Triple and Double Twin System.....................................................89 Table of Contents
i
ED21-302
3. External Appearance.............................................................................90 3.1 External Appearance..............................................................................90
4. Specifications ........................................................................................91 4.1 FHYC......................................................................................................91 4.2 FHY ........................................................................................................94
5. Dimensions and Service Space ............................................................97 5.1 5.2 5.3 5.4 5.5
Indoor Unit..............................................................................................97 Remote Controller ................................................................................105 Outdoor Unit .........................................................................................107 Installation Service Space for RY71LU, 100LU, 125LU, 140LU ..........110 Installation Service Space for RY200KU, 250KU.................................112
6. Piping Diagrams..................................................................................113 6.1 Twin......................................................................................................113 6.2 Triple ....................................................................................................119 6.3 Double Twin .........................................................................................121
7. Wiring Diagrams..................................................................................123 7.1 Indoor Unit............................................................................................123 7.2 Outdoor Units .......................................................................................125
8. Capacity Tables ..................................................................................128 8.1 Capacity Tables....................................................................................128 8.2 Capacity Correction Factor by The Length of Refrigerant Piping.........131
9. Operation Limits ..................................................................................132 9.1 Operation Limits ...................................................................................132
10.Sound Level ........................................................................................133 10.1 Overall Sound Level .............................................................................133 10.2 Octave Band Level ...............................................................................134
11.Electric Characteristics........................................................................136 11.1 RY71~140 ............................................................................................136 11.2 RY200 RY250 ..................................................................................................137
12.Option List ...........................................................................................138 12.1 LU Series..............................................................................................138
13.Field Piping and Wiring .......................................................................140 13.1 Field Piping...........................................................................................140 13.2 Field Wiring ..........................................................................................143
Detail Information of Options SkyAir LU Series ........................ 145 1. Remote Controller ...............................................................................146 1.1 1.2 1.3 1.4 1.5
Remote Controller, Timer, Adaptor List................................................146 Wired Remote Controller......................................................................146 Wireless Remote Controller .................................................................151 Various Control by Liquid Crystal Remote Controller...........................153 BRC15A61 – Set Back Time Clock ......................................................157
2. Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C] .......................160 2.1 2.2 2.3 2.4 2.5
ii
BYC125K – W1 – Decoration Panel.....................................................160 KDBHJ55K160 – Sealing member of air discharge outlet....................163 KDBJ55K160W – Panel spacer ...........................................................165 KDDP55D160(K) – Fresh Air Intake Kit ...............................................167 KDDJ55X160 – Fresh Air Intake Kit .....................................................170
Table of Contents
ED21-302
2.6 KAFP556D80 · 160 – High Efficiency Filter (Including Filter Chamber) KAFP557D80 · 160 – High Efficiency Filter (Including Filter Chamber) ...............................172 2.7 KAFJ552K80 · 160 – High Efficiency Filter (Replacement) KAFJ553K80 · 160 – High Efficiency Filter (Replacement)..................172 2.8 KRP1B98 – Installation Box for Adaptor PCB ......................................172 2.9 KDDFP55D160 – High-Efficiency Filter Chamber................................173 2.10 KAFJ551K160 – Long-Life Filter for Decoration Panel (Replacement) ........................175 2.11 KAFP55D160, KAFJ55K160H (Replacement) – Ultra Long-Life Filter (Including Filter Chamber) ...............................175 2.12 KKSJ55K160 – Chamber Connection Kit.............................................175 2.13 KDJ55K80 · 160 – Branch Duct Chamber............................................176 2.14 Dimensions with Optional Kit................................................................181
3. Ceiling Mounted Cassette Corner Type [FH(Y)K] ...............................185 3.1 3.2 3.3 3.4 3.5 3.6
BYK45FJW1 · 71FJW1 – Decoration panel .........................................185 KPBJ52F56W · 80W – Panel Specer...................................................189 KDBJ52F56W · 80W – Air Discharge Blind Panel ...............................193 KAFJ521F56 · 80 – Replacement Long Life Filter ...............................200 K-HV7AW · 9AW – Discharge Grille.....................................................200 KFDJ52F56 · 80 – Flexible Duct with Shutter ......................................201
4. Ceiling Mounted Built-In Type [FH(Y)B-F]...........................................208 4.1 BYBS45DJW1 – Decoration panel BYBS71DJW1 – Decoration panel BYBS125DJW1 – Decoration panel.....................................................208 4.2 KTBJ25K56W · 80W · 160W – Service access panel ..........................212 4.3 KAFJ252L56 · 80 · 160 – High-Efficiency Filter KAFJ253L56 · 80 · 160 – High-Efficiency Filter....................................213 4.4 KAFJ251K56 · 80 · 160 – Replacement long-life filter..........................214 4.5 KAJ25L56D · 80D · 160D – Filter Chamber for Bottom Suction...........214 4.6 KAJ25L56B · 80B · 160B – Filter Chamber for Rear Suction...............215 4.7 KSAJ25K56 · 80 ·160 – Canvas Duct ..................................................218 4.8 K-DG4BW · 5BW · 7BW · 9BW – Air Discharge Unit-Discharge Grille+Discharge Chamber K-DGC4B · 5B · 7B · 9B – Air Discharge Unit-Discharge Grille+Discharge Chamber.................219 4.9 K-DDV20A – Branch Duct ....................................................................221 4.10 K-FDK151B · 152B · 153B · 154B · 155B · 156B – Flexible Duct K-FDK201B · 202B · 203B · 204B · 205B · 206B – Flexible Duct......................................................................................222 4.11 KBBJ25K56 · 80 · 160 – Blind Board ...................................................223 4.12 KDAJ25K56 · 71 · 140 – Adaptor for Discharge...................................223 4.13 KDJ2507K56 · 80 · 160 – Flange for Suction .......................................224 4.14 Optional Kit Installation Drawing ..........................................................225
5. New Ceiling Suspended Cassette Type..............................................226 5.1 5.2 5.3 5.4 5.5 Table of Contents
KDBHJ49F80 · 140 – Seiling Member of Air Discharge Outlet ............226 KDBTJ49F80 · 140 – Decoration Panel for Air Discharge ...................226 KDGJ49F80 · 140 – Vertical Flap Kit ...................................................226 KAFJ495F140 – Replacement Long Life Filter ....................................227 KHFJ49F80 · 140 – L Connection Piping Kit........................................227 iii
ED21-302
5.6 KRP1B97 – Installation Box for Adaptor PCB ......................................227
6. Ceiling Suspended Type [FH(Y)] ........................................................228 6.1 6.2 6.3 6.4
KAFJ501D56 · 80 · 112 · 160 – Replacement Long Life Filter .............228 KDU50B50 · 71 · 125VE – Drain Pump Kit ..........................................228 KHFJ5F50 · 60 · 80 · 160 – L-Type Piping Kit......................................229 KRP1C93 – Installation Box for Adaptor PCB......................................229
7. Floor Standing Type [FVY]..................................................................230 7.1 KAFJ95L160 – Replacement Long Life Filter.......................................230 7.2 KRP4A95 – Installation Box for Adaptor PCB ......................................230
8. Outdoor Unit........................................................................................231 8.1 KIS95 – Drain Plug Kit..........................................................................231 8.2 KKPJ5F180 – Central Drain Plug.........................................................231 8.3 KHR58C21, KHD58C21A, KHD58C23A, KHD58C24A, KHD58D31, KHD58D33, KHRJ5F224F, KHRJ5F280F – Refrigerant Branch Piping .................................................................232
iv
Table of Contents
ED21-302
SkyAir LU Series (Pair) — Heat Pump — [50Hz]
1
Model Series Class Indoor Units
35
45
50
60
71
100
125
140
FHYC
35K
—
50K
60K
71K
100K
125K
140K
FHYK
35FJ
45FJ
—
60FJ
71FJ
—
—
—
FHYB
35F
45F
—
60F
71F
100F
125F
—
FUY
—
—
—
—
71FJ
100FJ 125FJ
—
FHY
35B
—
50B
60B
71B
100B
125B
—
FAY
—
—
—
—
71L
100FA
—
—
FVY
—
—
—
—
71LA
100LA 125LA
35F
50G
50GA
60GA
71LU
100LU 125LU 140LU
Outdoor RY Units
—
Cautions 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
SkyAir LU Series – Heat Pump –
1
Power Supply
ED21-302
1. Power Supply 1.1
Pair Series
1.1.1
Genaral Indoor Units
Notes:
2
Outdoor Units
FHYC35KVE
RY35FV1A
FHYC50KVE
RY50GAV1A
FHYC60KVE
RY60GAV1A
FHYC71KVE
RY71LUV1∗
FHYC100KVE
RY100LUV1∗
FHYC71KVE
RY71LUY1∗
FHYC100KVE
RY100LUY1∗
FHYC125KVE
RY125LUY1∗
FHYC140KVE
RY140LUY1∗
FHYK35FJV1
RY35FV1A
FHYK45FJV1
RY50GAV1A
FHYK60FJV1
RY60GAV1A
FHYK71FJV1
RY71LUV1∗
FHYK71FJV1
RY71LUY1∗
FHYB35FV1
RY35FV1A
FHYB45FV1
RY50GAV1A
FHYB60FV1
RY60GAV1A
FHYB71FV1
RY71LUV1∗
FHYB100FV1
RY100LUV1∗
FHYB71FV1
RY71LUY1∗
FHYB100FV1
RY100LUY1∗
FHYB125FV1
RY125LUY1∗
FUY71FJV1
RY71LUV1∗
FUY100FJV1
RY100LUV1∗
FUY71FJV1
RY71LUY1∗
FUY100FJV1
RY100LUY1∗
FUY125FJV1
RY125LUY1∗
FHY35BVE
RY35FV1A
FHY50BVE
RY50GAV1A
FHY60BVE
RY60GAV1A
FHY71BVE
RY71LUV1∗
FHY100BVE
RY100LUV1∗
FHY71BVE
RY71LUY1∗
FHY100BVE
RY100LUY1∗
FHY125BVE
RY125LUY1∗
FAY71LVE∗
RY71LUV1∗
FAY100FAVE
RY100LUV1∗
FAY71LVE∗
RY71LUY1∗
FAY100FAVE
RY100LUY1∗
FVY71LAVE
RY71LUV1∗
FVY100LAVE
RY100LUV1∗
FVY71LAVE
RY71LUY1∗
FVY100LAVE
RY100LUY1∗
FVY125LAVE
RY125LUY1∗
Power Supply
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1φ, 220~240V, 50Hz 3φ, 380~415V, 50Hz 1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1. ∗ : New Model or Changed Model 2. Power Supply Intake; Outdoor Unit.
SkyAir LU Series – Heat Pump –
ED21-302
External Appearance
2. External Appearance 2.1
1
External Appearance
Indoor Units
FHYC–K
FHYK–FJ
FUY–FJ
FHY–B
FAY71L
FAY100FA
FHYB–F
FVY–LA
Remote Controller
Wired Type Wireless Type
Outdoor Units
RY35F
RY50GA
SkyAir LU Series – Heat Pump –
RY60GA
RY71LU
RY100LU
RY125LU
RY140LU
3
Functions
ED21-302
3. Functions 3.1
LU Series Ceiling Mounted Super Cassette (FHYC) Items
Model Type Main Improvement
For Comfortable Air Conditioning
For Easy Construction and Maintenance
Improved Points and Functions
Indoor Units Outdoor Units
Wireless Type
35K~140K
35K~140K
Existing
Existing
New (71~140) New (71~140)
35~71FJ Existing New (71)
Appearance Improved
{
{
Reduction of Operation Sound
{
{
{
Auto Restart
{
{
{
Fan Operation Mode
{
{
{
LCD Remote Controller (Option)
{
{
{
Auto Swing Function
{
{
{
Ceiling Soiling Prevention
{
{
{
Program Dry
{
{
{
High Fan Speed Mode
—
—
—
High Ceiling Application
{
{
{
Two Select Thermo Sensor
{
—
—
Hot Start
{
{
{
Timer Selector
{
{
{
Fresh Air Intake Directly from The Unit
{
{
{
Drain Pump
{
{
{
Long Life Filter
{
{
{
Ultra-Long Life Filter (Option)
{
{
—
Mold Resistant Treatment for Filter
{
{
{
Filter Sign
{
{
{
Mold Resistant Drain Pan
{
{
{
Emergency Operation
{
{
{
Self Diagnoses Function
{
{
{
{
{(71~140)
{(71~140)
{(71)
Set Back Time Clock
{
{
{
Double Remote Control
{
{
{
Group Control by 1 Remote Controller
{
{
{
Control by External Command
{
{
{
Remote/Centralized Control
{
{
{
Low Gas Pressure Detection (RY)
For Flexible Control
Wired Type
Ceiling Mounted Cassette Corner (FHYK)
z : Improved Points and Functions { : Functions — : No Functions
4
SkyAir LU Series – Heat Pump –
ED21-302
Functions
Items
Model Type Main Improvement
For Comfortable Air Conditioning
Improved Points and Functions
71~125FJ
Existing
Existing
Existing
New (71~125)
New
New (71~125)
Appearance Improved
{
—
{
Reduction of Operation Sound
{
—
{
Auto Restart
{
{
{
Fan Operation Mode
{
{
{
LCD Remote Controller (Option)
{
{
{
Auto Swing Function
—
{
{
Ceiling Soiling Prevention
—
—
—
Program Dry
{
{
{
High Fan Speed Mode
—
—
—
High Ceiling Application
—
{
{
Wired Type
—
{
{
Wireless Type
Outdoor Units
35~125B
—
—
—
Hot Start
{
{
{
Timer Selector
{
{
{
Fresh Air Intake Directly from The Unit
{
—
—
Drain Pump
{
{
{ (Option)
Long Life Filter
{
{
{
Ultra-Long Life Filter (Option)
—
—
—
Mold Resistant Treatment for Filter
{
{
{
Filter Sign
{
{
{
Mold Resistant Drain Pan
{
{
{
Emergency Operation
{
{
{
Self Diagnoses Function
{
{
{
{(71~125)
{(71~125)
{(71~125)
Low Gas Pressure Detection (RY)
For Flexible Control
1
Ceiling Suspended (FHY)
35~125F Indoor Units
Two Select Thermo Sensor
For Easy Construction and Maintenance
Ceiling New Ceiling Mounted Built- Suspended In (FHYB) (FUY)
Set Back Time Clock
{
{
{
Double Remote Control
{
{
{
Group Control by 1 Remote Controller
{
{
{
Control by External Command
{
{
{
Remote/Centralized Control
{
{
{
z : Improved Points and Functions { : Functions — : No Functions
SkyAir LU Series – Heat Pump –
5
Functions
ED21-302
Items
Model Type Main Improvement
For Comfortable Air Conditioning
71L, 100FA
71~125LA
New (71)
Existing
New
New
Appearance Improved
{
{
Reduction of Dimensions or Weight
{
{
Reduction of Operation Sound
{
{
Auto Restart
{
{
Fan Operation Mode
{
{
LCD Remote Controller (Option)
{
{
Auto Swing Function
{
{
Ceiling Soiling Prevention
—
—
Program Dry
{
{
High Fan Speed Mode
{
—
—
—
Indoor Units Outdoor Units
High Ceiling Application Wired Type
{
{
Wireless Type
—
—
Hot Start
{
{
Timer Selector
{
{
Fresh Air Intake Directly from The Unit
—
—
Drain Pump
—
—
Long Life Filter
—
{
Ultra-Long Life Filter (Option)
—
—
Mold Resistant Treatment For Filter
{
{
Filter Sign
{
{
Mold Resistant Drain Pan
{
—
Emergency Operation
{
{
Self Diagnoses Function
{
{
Two Select Thermo Sensor
For Easy Construction and Maintenance
Wall Mounted (FAY) Floor Standing (FVY)
Improved Points and Functions
{(71, 100)
{(71~125)
Set Back Time Clock
{
{
Double Remote Control
{
{
Group Control by 1 Remote Controller
{
{
Control by D-BACS
{
{
z (71 only)
—
{
{
Low Gas Pressure Detection (RY)
For Flexible Control
Installation Box for Adapter PCB Remote/Centralized Control
z : Improved Points and Functions { : Functions — : No Functions
6
SkyAir LU Series – Heat Pump –
ED21-302
Specifications
4. Specifications 4.1
1
General
FHYC (Ceiling Mounted Cassette Type) Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)
kW Btu/h kcal/h kW Btu/h kcal/h
∗1 Heating Capacity (1)/(2)
Indoor Units Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
mm
m²
W m³/min. kg mm mm mm
Wired Wireless
Decoration Model Panel (Option) Color Dimensions (H×W×D) mm Air Filter Weight kg Outdoor Units Color Dimensions H×W×D mm Coil Type Row×Stages×Fin Pitch Face Area m² Comp. Model Type Motor Output kW Fan Model Type Motor Output W Air Flow Rate (C/H) m³/min. Weight kg Piping Liquid mm Connections Gas mm Drain mm Safety Devices Capacity Step % Refrigerant Control Ref. Piping Max. Length m Max. Height Difference m Refrigerant Model Charge (Factory Charge) kg Ref. Oil Model Charge L Drawing No.
Notes:
FHYC35KVE RY35FV1A 3.79/3.75 12,900/12,800 3,260/3,230 4.18/4.22 14,300/14,400 3,590/3,630 FHYC35KVE
FHYC50KVE FHYC60KVE RY50GAV1A RY60GAV1A 5.27/5.2 6.24/6.15 18,000/17,800 21,300/21,000 4,530/4,470 5,370/5,290 5.79/5.8 6.99/7.0 19,800/19,800 23,900/23,900 4,990/4,990 6,020/6,020 FHYC50KVE FHYC60KVE 230×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 0.331 QTS45B14M Turbo Fan 45 (H) 14 (L) 10 (H) 15 (L) 11 (H) 19 (L) 14 24 φ6.4 (Flare) φ12.7 (Flare) φ15.9 (Flare) I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 5) BRC7C612W BYC125K–W1 White 40×950×950 Resin Net (with Mold Resistant) 5 RY35FV1A RY50GAV1A RY60GAV1A Ivory White 540×750×270 685×800×300 685×880×350 Cross Fin Coil (FL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 0.372 0.46 0.50 RC53V1TNRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type 1.3 1.7 2.2 PZ430 PZ460 Propeller 27 35 53 26/23 35/32 44/40 41 51 75 φ6.4 (Flare) φ12.7 (Flare) φ15.9 (Flare) φ18.0 (Hole) Thermal Protector for Compressor. Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. 100–0 Capillary Tube 20 30 15 R22 1.12 (Charged for 10m) 1.55 (Charged for 10m) 1.75 (Charged for 5m) SUNISO 4GS–DI MS–32 0.85 1.0 1.2 C : 4D006538B
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
2. 3. 4. 5.
Heating
Conversion Formulae
Piping length
Hz–Volts
Standard
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
5m
50Hz–220V
—
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–220V
JIS B8616
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
7
Specifications
ED21-302
FHYC (Ceiling Mounted Cassette Type) Model
Indoor Units Outdoor Units
FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE RY71LUV1 RY100LUV1 — — RY71LUY1 RY100LUY1 RY125LUY1 RY140LUY1 ∗1 Cooling Capacity (1)/(2)/(3) 7.8/7.7/7.7 10.5/10.4/10.4 13.0/12.8/12.8 14.5/14.2/14.2 26,600/26,200/26,200 35,700/35,300/35,300 44,500/43,600/43,600 49,400/48,400/48,400 6,700/6,600/6,600 9,000/8,900/8,900 11,200/11,000/11,000 12,500/12,200/12,200 ∗1 Heating Capacity (1)/(2)/(3) 7.9/7.9/7.9 11.2/11.2/11.2 14.2/14.2/14.2 16.3/16.3/16.3 27,000/27,000/27,000 38,100/38,100/38,100 48,400/48,400/48,400 56,000/56,000/56,000 6,800/6,800/6,800 9,600/9,600/9,600 12,200/12,200/12,200 14,000/14,000/14,000 Indoor Units FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE Dimensions H×W×D mm 230×840×840 288×840×840 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Cross Fin Coil Row×Stages×Fin Pitch 2×8×1.5 2×12×1.5 Face Area m² 0.331 0.497 Fan Model QTS45B14M QTS45A17M Type Turbo Fan Motor Output W 45 90 m³/min. (H) 19–21 (L) 14–16 (H) 28–31 (L) 21–24 (H) 33–36 (L) 24–27 (H) 35–38 (L) 26–28 Air Flow Rate ∗2 Weight kg 24 28 φ9.5 (Flare) Piping Liquid mm Connections Gas φ15.9 (Flare) φ19.1 (Flare) mm Drain mm I. Dφ25×O. Dφ32 Remote Controller Wired BRC1C61 (Note. 5, 6) BRC1C61 (Note. 6) (Option) Wireless BRC7C612W Decoration Model BYC125K–W1 Panel Color White (Option) Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Units V1 RY71LUV1 RY100LUV1 — — Y1 RY71LUY1 RY100LUY1 RY125LUY1 RY140LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 1,345×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 2×60×2.0 Face Area m² 0.634 0.983 1.134 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ — — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE JT170BC–YE Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 3.75 4.50 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 65 90 65+85 65+90 48–51 59–62 92–100 97–109 Air Flow Rate (C/H) ∗2 m³/min. Weight kg V1 73 89 — Y1 72 86 101 112 φ9.5 (Flare) Piping Liquid mm Connections Gas φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) Drain mm Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <RY125·140>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <RY71·100>. Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.6 1.5 Drawing No. 4D039078 4D039079
Notes:
V1 Y1 kW Btu/h kcal/h kW Btu/h kcal/h
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
2. 3. 4. 5. 6.
8
Heating
Conversion Formulae
Piping length
Hz–Volts
Standard
5m
50Hz–220V (380V)
—
7.5m
50Hz–220V (380V)
JIS B8616
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
ED21-302
Specifications
1
FHYK (Ceiling Mounted Cassette Corner Type) Model
Indoor Units Outdoor Units
V1 Y1 kW Btu/h kcal/h kW Btu/h kcal/h
∗1 Cooling Capacity (1)/(2)/(3)
∗1 Heating Capacity (1)/(2)/(3)
Indoor Units Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2
Weight Piping Connections (Note. 7)
Liquid Gas Drain Remote Controller (Option)
Decoration Panel (Option)
—
Model Color Dimensions (H×W×D) Air Filter Weight
H×W×D Type
Comp.
Row×Stages×Fin Pitch Face Area Model
Piping Connections (Note. 7)
W m³/min. kg mm mm mm
BRC1C61(Note. 5, 6)
Color Dimensions Coil
Weight
m²
Wired Wireless
Outdoor Units
Fan
mm
FHYK35FJV1 FHYK45FJV1 FHYK60FJV1 FHYK71FJV1 RY35FV1A RY50GAV1A RY60GAV1A RY71LUV1 — — — RY71LUY1 3.5/3.5/– 5.0/4.85/– 6.3/6.15/– 7.8/7.7/7.7 12,100/11,900/– 16,900/16,600/– 21,400/21,000/– 26,600/26,200/26,200 3,040/3,000/– 4,260/4,200/– 5,390/5,300/– 6,700/6,600/6,600 4.05/4.1/– 5.5/5.5/– 7.1/7.1/– 7.9/7.9/7.9 13,800/14,000/– 18,800/18,800/– 24,000/24,000/– 27,000/27,000/27,000 3,480/3,520/– 4,740/4,740/– 6,080/6,080/– 6,800/6,800/6,800 FHYK35FJV1 FHYK45FJV1 FHYK60FJV1 FHYK71FJV1 215×1,110×710 215×1,310×710 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×11×1.75 3×11×1.75 0.180 0.226 3D12H1AH1V1 3D12H1AJ1V1 4D12H1AG1V1 Sirocco Fan 20 25 45 (H) 12 (L) 9 (H) 12 (L) 10 (H) 17 (L) 14 (H) 17–18 (L) 14–15 30 31 33 φ6.4 (Flare) φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) I. Dφ25×O. Dφ32
BYK71FJW1 White
mm
70×1,240×800
70×1,440×800 Resin Net (with Mold Resistant)
kg V1 Y1
RY35FV1A —
8.5
mm
540×750×270
9.5 RY50GAV1A — Ivory White
RY60GAV1A —
685×800×300
685×880×350
Cross Fin Coil (FL Fins and Hi–XA Tubes)
Type Motor Output Model Type Motor Output Air Flow Rate (C/H) kg
∗2
Liquid Gas Drain
Safety Devices
Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Notes:
BYK45FJW1
2×28×2.0 0.46 0.50 RC70AV1TRT NH41VMDT — Hermetically Sealed Rotary Type kW 1.3 1.7 2.2 PZ380 PZ430 PZ460 Propeller W 27 35 53 m³/min. 26/23 35/32 44/40 V1 41 51 75 Y1 — φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35, 50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. m² V1 Y1
2×22×2.0 0.372 RC53V1TNRT
%
RY71LUV1 RY71LUY1 Ivory 770×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 0.634 ZR36K3–PFJ ZR36K3–TFD Hermetically Sealed Scroll Type
2.24 P47L11S 65 48–51 73 72 φ9.5 (Flare)
φ26.0 (Hole) Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor Protector (Compressor). Reverse Phase Protector (Y1). Fuse.
100–0 Capillary Tube
m m kg L
20
Electronic Expansion Valve 50 (Equivalent Length 70m) 30
30 15
1.12 (Charged for 10m) 1.55 (Charged for 10m) SUNISO 4GS–DI 0.85 1.0 C : 4D006263B
R22 1.75 (Charged for 5m) MS–32 1.2
2.8 (Charged for 30m) SONTEX 200LT 1.2 4D039087
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
(2) (3)
2. 3. 4. 5. 6. 7.
Heating
Conversion Formulae
Piping length
Hz–Volts
Standard
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
5m
50Hz–220V (380V)
—
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–220V (380V)
JIS B8616
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). (In case of FHYK71FJV1) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied. FHYK45 and FHYK60 models are connected by using attached auxiliary piping.
SkyAir LU Series – Heat Pump –
9
Specifications
ED21-302
FHYB (Ceiling Mounted Built-In Type) Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)
kW Btu/h kcal/h kW Btu/h kcal/h
∗1 Heating Capacity (1)/(2)
Indoor Units Dimensions Coil
FHYB35FV1 RY35FV1A 3.5/3.5 12,100/11,900 3,040/3,000 4.05/4.1 13,800/14,000 3,480/3,520 FHYB35FV1
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
FHYB45FV1 RY50GAV1A 5.0/4.85 16,900/16,600 4,260/4,200 5.5/5.5 18,800/18,800 4,750/4,750 FHYB45FV1
FHYB60FV1 RY60GAV1A 6.3/6.15 21,400/21,000 5,390/5,300 7.1/7.1 24,200/24,200 6,100/6,100 FHYB60FV1 300×1,000×800
300×700×800 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 3×14×1.75 m² 0.132 0.221 Fan D18H2AH1V1 D18H2AJ1V1 2D18H2AH1V1 Sirocco Fan W 65 85 110 m³/min. (H) 11.5 (L) 9 (H) 14 (L) 10 (H) 17 (L) 13 Air Filter Resin Net (with Mold Resistant) Weight kg 30 31 41 φ6.4 (Flare) Piping Liquid mm Connections φ12.7 (Flare) φ15.9 (Flare) Gas mm Drain mm I. Dφ25×O. Dφ32 Remote Controller Wired BRC1C61 (Note. 4, 5) (Option) Wireless — Decoration Model BYBS45DJW1 (∗2 BYBS45D–W2) BYBS71DJW1 (∗2 BYBS71D–W2) Panel (Option) Color White Dimensions (H×W×D) mm 55×880×500 55×1,100×500 Weight kg 3.5 4.5 Outdoor Units RY35FV1A RY50GAV1A RY60GAV1A Color Ivory White Dimensions H×W×D mm 540×750×270 685×800×300 685×880×350 Coil Type Cross Fin Coil (FL Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×22×2.0 2×28×2.0 Face Area m² 0.372 0.46 0.50 Comp. Model RC53V1TNRT RC70AV1TRT NH41VMDT Type Hermetically Sealed Rotary Type Motor Output kW 1.3 1.7 2.2 Fan Model PZ380 PZ430 PZ460 Type Propeller Motor Output W 27 35 53 Air Flow Rate (C/H) m³/min. 26/23 35/32 44/40 Weight kg 41 51 75 φ6.4 (Flare) Piping Liquid mm Connections φ12.7 (Flare) φ15.9 (Flare) Gas mm φ18.0 (Hole) Drain mm Safety Devices Thermal Protector for Compressor (35 · 50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. Capacity Step % 100–0 Refrigerant Control Capillary Tube Ref.Piping Max. Length m 20 30 Max. Height Difference m 15 Refrigerant Model R22 Charge (Factory Charge) kg 1.12 (Charged for 10m) 1.55 (Charged for 10m) 1.75 (Charged for 5m) Ref. Oil Model SUNISO 4GS–DI MS–32 Charge L 0.85 1.0 1.2 Drawing No. C : 4D006262C
Notes:
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
2. 3. 4. 5. 6.
10
mm
Heating
Conversion Formulae
Piping length
Hz–Volts
Standard
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
5m
50Hz–220V
—
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–220V
JIS B8616
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B62 is also available. Wire for remote controller : Field supplied. ∗2 This type can be used.
SkyAir LU Series – Heat Pump –
ED21-302
Specifications
1
FHYB (Ceiling Mounted Built-In Type) Model
Indoor Units Outdoor Units
V1 Y1 kW Btu/h kcal/h kW Btu/h kcal/h
∗1 Cooling Capacity (1)/(2)/(3)
∗1 Heating Capacity (1)/(2)/(3)
Indoor Units Dimensions Coil
FHYB71FV1 RY71LUV1 RY71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 7.9/7.9/7.9 27,000/27,000/27,000 6,800/6,800/6,800 FHYB71FV1 300×1,000×800
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2
mm
FHYB100FV1 RY100LUV1 RY100LUY1 10.5/10.4/10.4 35,700/35,300/35,300 9,000/8,900/8,900 11.2/11.2/11.2 38,100/38,100/38,100 9,600/9,600/9,600 FHYB100FV1
FHYB125FV1 — RY125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 14.2/14.2/14.2 48,400/48,400/48,400 12,200/12,200/12,200 FHYB125FV1 300×1,400×800
Cross Fin Coil 3×14×1.75
0.338 3D18H2AN1V1 3D18H2AP1V1 Sirocco Fan W 125 135 225 m³/min. (H) 19–21.5 (L) 14–16.5 (H) 27–29 (L) 20–22 (H) 35–40.5 (L) 24–29.5 Air Filter Resin Net (with Mold Resistant) Weight kg 41 51 52 φ9.5 (Flare) Piping Liquid mm Connections φ15.9 (Flare) φ19.1 (Flare) Gas mm Drain mm I. Dφ25×O. Dφ32 Remote Controller Wired BRC1C61(Note. 5, 6) (Option) Wireless — Decoration Model BYBS71DJW1 (∗3 BYBS71D–W2) BYBS125DJW1 (∗3 BYBS125D–W2) Panel (Option) Color White Dimensions (H×W×D) mm 55×1,100×500 55×1,500×500 Weight kg 4.5 6.5 Outdoor Units V1 RY71LUV1 RY100LUV1 — Y1 RY71LUY1 RY100LUY1 RY125LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 65 90 65+85 Air Flow Rate (C/H) ∗2 m³/min. 48–51 59–62 92–100 Weight kg V1 73 89 — Y1 72 86 101 φ9.5 (Flare) Piping Liquid mm Connections φ15.9 (Flare) φ19.1 (Flare) Gas mm φ26.0 (Hole) Drain mm Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <RY125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <RY71·100>. Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref.Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039086 Fan
Notes:
m²
0.221 2D18H2AJ1V1
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
(2) (3)
2. 3. 4. 5. 6. 7.
Heating
Conversion Formulae
Piping length
Hz–Volts
Standard
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
5m
50Hz–220V (380V)
—
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–220V (380V)
JIS B8616
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B62 is also available. Wire for remote controller : Field supplied. ∗3 This type can be used.
SkyAir LU Series – Heat Pump –
11
Specifications
ED21-302
FUY (New Ceiling Suspended Cassette Type) Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)/(3)
∗1 Heating Capacity (1)/(2)/(3)
Indoor Unit Color Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Comp.
Fan
Weight Piping Connections
FUY71FJV1 RY71LUV1 RY71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 7.9/7.9/7.9 27,000/27,000/27,000 6,800/6,800/6,800 FUY71FJV1
mm
165×895×895
m²
W m³/min kg mm mm mm
Wired Wireless
Outdoor Units Color Dimensions Coil
V1 Y1 kW Btu/h kcal/h kW Btu/h kcal/h
V1 Y1 H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate (C/H) ∗2 kg Liquid Gas Drain
mm
m² V1 Y1 kW
W m³/min V1 Y1 mm mm mm
Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Notes:
m m kg L
FUY125FJV1 — RY125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 14.2/14.2/14.2 48,400/48,400/48,400 12,200/12,200/12,200 FUY125FJV1
230×895×895 Cross Fin Coil (Multi Louver Fins and Hi–XA Tubes) 3×6×1.5 3×8×1.5 0.265 0.353 QTS48A QTS50B15M Turbo Fan 45 90 (H)19 (L)14 (H)29 (L)21 (H)32 (L)23 Resin Net (with Mold Resistant) 25 31 φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) I.D φ20×O.D φ26 BRC1C61 (Note. 5, 6) BRC7C528W RY71LUV1 RY100LUV1 — RY71LUY1 RY100LUY1 RY125LUY1 Ivory 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 0.634 0.983 ZR36K3–PFJ ZR48K3–PFJ — ZR36K3–TFD ZR48K3–TFD JT160BC–YE Hermetically Sealed Scroll Type 2.24 3.00 3.75 P47L11S P47L11S×2 Propeller 65 90 65+85 48–51 59–62 92–100 73 89 — 72 86 101 φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ26.0 (Hole) Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <RY125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <RY71·100>. Reverse Phase Protector (Y1). Fuse. 100–0 Electronic Expansion Valve 50 (Equivalent Length 70m) 30 R22 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K 1.2 1.5 4D039088
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
2. 3. 4. 5. 6.
12
%
FUY100FJV1 RY100LUV1 RY100LUY1 10.5/10.4/10.4 35,700/35,300/35,300 9,000/8,900/8,900 11.2/11.2/11.2 38,100/38,100/38,100 9,600/9,600/9,600 FUY100FJV1 White
Heating
Conversion Formulae
Piping length
Hz–Volts
Standard
5m
50Hz–220V (380V)
—
7.5m
50Hz–220V (380V)
JIS B8616
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
ED21-302
Specifications
1
FHY (Ceiling Suspended Type) Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)/(3)
FHY50BVE FHY60BVE RY50GAV1A RY60GAV1A kW 5.0/4.85/4.85 6.3/6.15/6.15 Btu/h 16,900/16,600/16,600 21,400/21,000/21,000 kcal/h 4,260/4,200/4,200 5,390/5,300/5,300 ∗1 Heating Capacity (1)/(2)/(3) kW 5.5/5.5/5.78 7.1/7.1/7.24 Btu/h 18,800/18,800/19,700 24,200/24,200/24,700 kcal/h 4,750/4,750/4,970 6,100/6,100/6,230 Indoor Units FHY50BVE FHY60BVE Color White Dimensions H×W×D mm 195×960×680 195×960×680 195×1,160×680 Coil Type Cross Fin Coil (Multi Louver Fins and N–hix Tubes) Row×Stages×Fin Pitch 2×12×1.75 3×12×1.75 Face Area m² 0.182 0.233 Fan Model 3D12K1AA1 4D12K1AA1 Type Sirocco Fan Motor Output W 62 Air Flow Rate m³/min. (H) 13 (L) 10 (H) 16 (L) 13 Air filter Resin Net (with Mold Resistant) Weight kg 23 24 26 φ6.4 (Flare) φ9.5 (Flare) Piping Liquid mm Connections φ12.7 (Flare) φ15.9 (Flare) Gas mm Drain mm I. Dφ20×O. Dφ26 Remote Controller Wired BRC1C61 (Note. 4) (Option) Wireless BRC7E63W Outdoor Units RY35FV1A RY50GAV1A RY60GAV1A Color Ivory White Dimensions H×W×D mm 540×750×270 685×800×300 685×880×350 Coil Type Cross Fin Coil (FL Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×22×2.0 2×28×2.0 Face Area m² 0.372 0.46 0.50 Comp. Model RC53V1TNRT RC70AV1TRT NH41VMDT Type Hermetically Sealed Rotary Type Motor Output kW 1.3 1.7 2.2 Fan Model PZ380 PZ430 PZ460 Type Propeller Motor Output W 27 35 53 Air Flow Rate (C/H) m³/min. 27/24 38/35 46/43 Weight kg 41 51 75 φ6.4 (Flare) Piping Liquid mm Connections φ12.7 (Flare) φ15.9 (Flare) Gas mm φ18.0 (Hole) Drain mm Safety Devices Thermal Protector for Compressor (35 · 50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. Capacity Step % 100–0 Refrigerant Control Capillary Tube Ref.Piping Max. Length m 20 30 Max. Height Difference m 15 Refrigerant Model R22 Charge (Factory Charge) kg 1.12 (Charged for 10m) 1.55 (Charged for 10m) 1.75 (Charged for 5m) Ref. Oil Model SUNISO 4GS–DI MS–32 Charge L 0.85 1.00 1.20 Drawing No. C : 4D028434
Notes:
FHY35BVE RY35FV1A 3.5/3.5/– 12,100/11,900/– 3,040/3,000/– 4.05/4.1/– 13,800/14,000/– 3,480/3,520/– FHY35BVE
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
Heating
Conversion Formulae
Piping length
Hz–Volts
Standard
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
5m
50Hz–220V
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–220V
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–240V
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 3. In case of drain piping for outdoor unit, drain piping kit (option) is needed. 4. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
13
Specifications
ED21-302
FHY (Ceiling Suspended Type) Model
Indoor Units Outdoor Units
FHY100BVE FHY125BVE RY100LUV1 — RY100LUY1 RY125LUY1 ∗1 Cooling Capacity (1)/(2)/(3) 10.5/10.4/10.4 13.0/12.8/12.8 35,700/35,300/35,300 44,500/43,600/43,600 9,000/8,900/8,900 11,200/11,000/11,000 ∗1 Heating Capacity (1)/(2)/(3) 11.2/11.2/11.2 14.2/14.2/14.2 38,100/38,100/38,100 48,400/48,400/48,400 9,600/9,600/9,600 12,200/12,200/12,200 Indoor Units FHY100BVE FHY125BVE Color White Dimensions H×W×D mm 195×1,160×680 195×1,400×680 195×1,590×680 Coil Type Cross Fin Coil (Multi Louver Fins and N–hix Tubes) Row×Stages×Fin Pitch 3×12×1.75 Face Area m² 0.233 0.293 0.341 Fan Model 4D12K1AA1 3D12K2AA1 4D12K2AA1 Type Sirocco Fan Motor Output W 62 130 Air Flow Rate ∗2 m³/min. (H) 17 (L) 14 (H) 24 (L) 20 (H) 30 (L) 25 Air filter Resin Net (with Mold Resistant) Weight kg 27 32 35 φ9.5 (Flare) Piping Liquid mm Connections φ15.9 (Flare) φ19.1 (Flare) Gas mm Drain mm I. Dφ20×O. Dφ26 Remote Controller Wired BRC1C61 (Note. 5) (Option) Wireless BRC7E63W Outdoor Units V1 RY71LUV1 RY100LUV1 — Y1 RY71LUY1 RY100LUY1 RY125LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 65 90 65+85 Air Flow Rate (C/H) ∗2 m³/min. 48–51 59–62 92–100 Weight kg V1 73 89 — Y1 72 86 101 φ9.5 (Flare) Piping Liquid mm Connections φ15.9 (Flare) φ19.1 (Flare) Gas mm φ26.0 (Hole) Drain mm Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan motor. High Pressure Switch <RY125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <RY71·100>. Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref.Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039082
Notes:
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
2. 3. 4. 5.
14
FHY71BVE RY71LUV1 RY71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 7.9/7.9/7.9 27,000/27,000/27,000 6,800/6,800/6,800 FHY71BVE
V1 Y1 kW Btu/h kcal/h kW Btu/h kcal/h
Heating
Conversion Formulae
Piping length
Hz–Volts
Standard
5m
50Hz–220V (380V)
—
7.5m
50Hz–220V (380V)
JIS B8616
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
ED21-302
Specifications
1
FAY (Wall Mounted Type) Model
Indoor Units Outdoor Units
V1 Y1 kW Btu/h kcal/h kW Btu/h kcal/h
∗1 Cooling Capacity (1)/(2)/(3)
∗1 Heating Capacity (1)/(2)/(3)
Indoor Units Color Dimensions Coil
FAY71LVE RY71LUV1 RY71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 7.9/7.9/7.9 27,000/27,000/27,000 6,800/6,800/6,800 FAY71LVE
FAY100FAVE RY100LUV1 RY100LUY1 10.5/10.4/10.4 35,700/35,300/35,300 9,000/8,900/8,900 11.2/11.2/11.2 38,100/38,100/38,100 9,600/9,600/9,600 FAY100FAVE
White 290×1,050×230 360×1,570×200 Cross Fin Coil (Multi Louver Fins and Hi–XA Tubes) 2×16×1.4 2×12×1.4 m² 0.289 0.332 Fan QCL9686M QCL1163MA+QCL1163MB Cross Flow Fan W 43 46 m³/min. (H) 19–19 (L) 15–15 (H) 23–23 (L) 19–19 Air Filter Resin Net (with Mold Resistant) Weight kg 13 26 φ9.5 (Flare) Piping Liquid mm Connections Gas φ15.9 (Flare) φ19.1 (Flare) mm I. Dφ20×O. Dφ26 Drain mm I. Dφ13×O. Dφ18 Remote Controller Wired BRC1C61 (Note. 5, 6) (Option) Wireless BRC7E618 BRC7C610W Outdoor Units V1 RY71LUV1 RY100LUV1 Y1 RY71LUY1 RY100LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ Y1 ZR36K3–TFD ZR48K3–TFD Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 Fan Model P47L11S Type Propeller Motor Output W 65 90 Air Flow Rate (C/H) ∗2 m³/min. 48–51 59–62 Weight kg V1 73 89 Y1 72 86 φ9.5 (Flare) Piping Liquid mm Connections Gas φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) Drain mm Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor Protector (Compressor). Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref.Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT Charge L 1.2 Drawing No. 4D039583 4D039271 H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2
Notes:
mm
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
2. 3. 4. 5. 6.
Heating
Conversion Formulae
Piping length
Hz–Volts
Standard
5m
50Hz–220V (380V)
—
7.5m
50Hz–220V (380V)
JIS B8616
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
15
Specifications
ED21-302
FVY (Floor Standing Type) Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)/(3)
∗1 Heating Capacity (1)/(2)/(3)
Indoor Units Color Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2
V1 Y1 kW Btu/h kcal/h kW Btu/h kcal/h
FVY71LAVE RY71LUV1 RY71LUY1 7.8/7.7/9.7 26,600/26,200/26,200 6,700/6,600/6,600 7.9/7.9/7.9 27,000/27,000/27,000 6,800/6,800/6,800 FVY71LAVE
mm
1,850×600×270
FVY125LAVE — RY125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 14.2/14.2/14.2 48,400/48,400/48,400 12,200/12,200/12,200 FVY125LAVE 1,850×600×350
Cross Fin Coil 2×44×1.75 0.44
2×40×1.75 0.40 QS37A1AM
m²
FVY100LAVE RY100LUV1 RY100LUY1 10.5/10.4/10.4 35,700/35,300/35,300 9,000/8,900/8,900 11.2/11.2/11.2 38,100/38,100/38,100 9,600/9,600/9,600 FVY100LAVE White
(3×22×1.75)×2 0.44 (0.22×2)
QS37A2AM Sirroco Fan W 30 60 90 m³/min. (H) 18–20 (L) 14–16 (H) 28–31 (L) 22–25 (H) 32–35 (L) 25–28 Air Filter Resin Net (with Mold Resistant) Weight kg 39 46 47 φ9.5 (Flare) Piping Liquid mm Connections φ15.9 (Flare) φ19.1 (Flare) Gas mm Drain mm I. Dφ20×O. Dφ26 Outdoor Units V1 RY71LUV1 RY100LUV1 — Y1 RY71LUY1 RY100LUY1 RY125LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 65 90 65+85 Air Flow Rate (C/H) ∗2 m³/min. 48–51 59–62 92–100 Weight kg V1 73 89 — Y1 72 86 101 φ9.5 (Flare) Piping Liquid mm Connections φ15.9 (Flare) φ19.1 (Flare) Gas mm φ26.0 (Hole) Drain mm Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <RY125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <RY71·100>. Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref.Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039085
Notes:
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Heating
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
Conversion Formulae
Piping length
Hz–Volts
Standard
5m
50Hz–220V (380V)
—
7.5m
50Hz–220V (380V)
JIS B8616
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. ∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). 3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 4. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
16
SkyAir LU Series – Heat Pump –
ED21-302
Dimensions and Service Space
5. Dimensions and Service Space 5.1
Indoor Unit
5.1.1
FHYC (Ceiling Mounted Cassette Type)
1
FHYC35K + BYC125K-W1 C 860~890 Ceiling opening
80
2× 100=200
Unit (mm)
85
300 or less 680 Suspension position
950
(165)
Note3.
420
9
Branch duct connection
350 C
view 60
4-M4 Hole (prepared hole) φ7
80 80
6
40
860~890 Ceiling opening
950
780 Suspension position
10
5
55
55
840
55
12-M4 Hole (prepared hole)
5
150 40 350
2
1
4
165
95 110
85
Branch duct connection
A
∗1500mm or more Required space ∗1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more.
1000 or more Required space
30
8
260 270 315
For fresh air intake kit connection (direct installation type)
view
55
840 80 2× 100=200
295
125 150 240
750 10
B B
200
Adjustable (0~550)
420
3
40
230
view
240
Suspension bolt 4-M8~M10
160
7 A
Description
Name Number 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.
3. In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.
2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
5 6 7 8
φ6.4 flare φ12.7 flare VP25
Remote control code and control wiring connection
Air discharge grille Air suction grille Port for water supply Corner decoration cover
9 10 Drain hose
O.D.32
C : 3D012310B
FHYC50K + BYC125K-W1 FHYC60K + BYC125K-W1 Unit (mm)
C
950
2× 100=200 85
80
860~890 Ceiling opening 300 or less 680 Suspension position
(165)
Note3.
420
9 10
6
Branch duct connection
C view 60
4-M4 Hole (prepared hole) φ7
80
5
80
950
780 Suspension position 860~890 Ceiling opening
40 350
840
55
12-M4 Hole (prepared hole)
8
5
260 270 315
4
1
2
40 350
Branch duct connection
A
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille. 2. When installing an optional accessory, refer to the installation drawings. z For fresh air intake kit ...... Inspection port is necessary. z For high efficiency filter unit ...... Inspection port is not necessary.
165 1000 or more Required space
125 150 240 240
For fresh air intake kit connection (direct installation type)
55
2×100=200 85
95 110
80
150
750 Adjustable (0~550)
55
840 295
200
230
B view
55
30 Suspension bolt 4-M8~M10
B
3
40
10
420
160
7 A view
∗1500mm or more Required space 1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more. Name Number 1 Liquid pipe connection Gas pipe connection 2 Drain pipe connection 3 Power supply connection 4
3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.
5
Remote control code and control wiring connection
6
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
9 10
Air discharge grille Air suction grille Port for water supply Corner decoration cover
7 8
Drain hose
Description φ6.4 flare φ15.9 flare VP25
O.D.32
C : 3D012311B
SkyAir LU Series – Heat Pump –
17
Dimensions and Service Space
ED21-302
FHYC71K + BYC125K-W1
1000 or more
Unit (mm)
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
C : 3D012312C
FHYC100K + BYC125K-W1 FHYC125K + BYC125K-W1 FHYC140K + BYC125K-W1 Unit (mm)
C
(195)
950
2× 100=200 85
80
860~890 Ceiling opening 300 or less 680 Suspension position
Note3.
165
6
40 350
Branch duct connection
C view
4-M4 Hole (prepared hole) φ7 5
60 80 80
950
780 Suspension position 860~890 Ceiling opening
10
155
420
9
160
7 A view
420
B
8
5
260 270 315
4
1
14-M4 Hole (prepared hole)
2× 100=200 85
2
40 350
Branch duct connection
A
18
195
150
125 150 298 240
55
840 80
200
30 Suspension bolt 4-M8~M10
55
40 50 155 165
55
840 295
1000 or more Required space
55
40
10
288
750 Adjustable (0~550)
B view
3
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.
3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.
2. When installing an optional accessory, refer to the installation drawings. z For fresh air intake kit ...... Inspection port is necessary. z For high efficiency filter unit ...... Inspection port is not necessary.
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
For fresh air intake kit connection (direct installation type)
∗1500mm or more Required space ∗1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required is space 200mm or more. Number Name 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection 5 6 7 8 9 10
Description φ9.5 flare φ19.1 flare VP25
Remote control code and control wiring connection
Air discharge grille Air suction grille Port for water supply Corner decoration cover Drain hose
O.D.32
C : 3D012313C
SkyAir LU Series – Heat Pump –
ED21-302
5.1.2
Dimensions and Service Space
FHYC with High Efficiency Filter
1
KAFP556D80·557D80 for FHYC35~71K
Unit (mm)
290
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975A
KAFP556D160·557D160 for FHYC100~140K
Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032976A
SkyAir LU Series – Heat Pump –
19
Dimensions and Service Space
5.1.3
ED21-302
FHYC with Fresh Air Intake Kit (Without T Joint, Duct Fan)
KDDP55D160 for FHYC35~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
Note 4
View
Service Access Panel : 450×450mm or more Refer to Note 2
290
Installation Service Access Panel
Connection Chamber (Right)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
How to connect Chamber 4 Independently(Refer to Note 5,6)
Applicable Models Skyair
FH(Y)C35~71K
5 4 3 2 1 Number
Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981A
KDDP55D160 for FHYC100~140K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
View
Service Access Panel : 450×450mm or more Refer to Note 2
Note 4
Installation Service Access Panel
Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
20
Applicable Models Skyair
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984A
SkyAir LU Series – Heat Pump –
ED21-302
5.1.4
Dimensions and Service Space
FHYC with Fresh Air Intake Kit (With T Joint, Without Duct Fan)
1
KDDP55D160K for FHYC35~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Flexible Duct (Accessory)
Installation Service Access Panel
Service Access Panel : 450×450mm or more Refer to Note 2
Suction Duct (K-KFD9A) Optional (Accessory) T Joint
Plate Band
(Accessory)
290
(Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
Applicable Models SkyAir
FH(Y)C35~71K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032987A
KDDP55D160K for FHYC100~140K Service Access Panel : 450×450mm or more Refer to Note 2
Installation Service Access Panel
Unit (mm) Flexible Duct (Accessory)
Service Access Panel : 450×450mm or more Refer to Note 2 Plate Band (Accessory)
T Joint (Accessory)
Suction Duct (K-KFD9A) Optional (Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
SkyAir LU Series – Heat Pump –
Applicable Models Skyair
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032990A
21
Dimensions and Service Space
5.1.5
ED21-302
FHYC with Panel Spacer
KDBJ55K160W for FHYC35~71K Unit (mm)
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005390E
KDBJ55K160W for FHYC100~140K Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005391D
22
SkyAir LU Series â&#x20AC;&#x201C; Heat Pump â&#x20AC;&#x201C;
ED21-302
5.1.6
Dimensions and Service Space
FHYK (Ceiling Mounted Cassette Corner Type)
1
FHYK35FJ + BYK45FJW1 FHYK45FJ + BYK45FJW1 Unit (mm)
φ12.7 φ6.4 3D027409
FHYK60FJ + BYK71FJW1 FHYK71FJ + BYK71FJW1 Unit (mm)
φ15.9 φ9.5
3D027408
SkyAir LU Series – Heat Pump –
23
Dimensions and Service Space
5.1.7
ED21-302
FHYB (Ceiling Mounted Built-In Type)
FHYB35F + BYBS45DJW1 Without Canvas Duct FHYB45F + BYBS45DJW1 60
57
485
A
3
5 Model 195 B
2
6
350 or more (Required space)
67 150 200
300 245 215 150 135 10
3×150=450
440 315
1
D
45
C
Suspension bolt
135 120
50 65
∗ The required ceiling depth varies according to configuration of specific system
2×65=130
460
8
Unit (mm)
800 595 (Air suction panel center)
25 700
FHYB35F
FHYB45F
12.7
15.9
4
300 or more 45
Service space
12-φ7
46
460 Suction air intake position when installing the duct
650
150 215 245 150 250 300
500
228
160
462 (Ceiling opening)
628
3×150=450 485
4×150=600
760 (Ceiling opening)
700
14-M5 Hole
800
D View
B View 160 P. C. D φ125 (Knockout hole)
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
600 Fresh air intake Position
100
630 (Suspension position) 145
6×65=390
6-M5 Hole (Circumference liner)
7
1. Liquid pipe connection φ6.4Flare 2. Gas pipe connection Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
C View
750 (Suspension position) A View
JC : DU224-247
FHYB35F + BYBS45DJW1 With Canvas Duct FHYB45F + BYBS45DJW1 60 50
25
135 120
2×65=130
67 150 200
2
45
46
6
300 or more
4
∗ The required ceiling depth varies according to configuration of specific system
5
B
FHYB35F
FHYB45F
12.7
15.9 12-φ7
460
Service space
10
Model
650
Suction air intake position when instaling the duct.
150 215 245
A
3
195
440 315
1
465 or more Required installation space
Suspension bolt
57
Unit (mm)
800 595 (Air suction panel center)
D
45 115~255
C
300 245 215 150 135
8
700 485 460 3×150=450 65
3×150=450 485
4×150=600 700
760 (Ceiling opening)
D View
14-M5 hole
800
B View 160 P. C. D
6×65=390
φ125 (Knockout hole)
600 Fresh air intake position
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
100
630 (Suspension position) 145
150 250 300
228
160
500
462 (Ceiling opening)
628
6-M5 hole (Circumference liner)
7 750 (Suspension position)
A
C
View
1. Liquid pipe connection φ6.4 Flare 2. Gas pipe connection Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
View
JC : DU224-248
24
SkyAir LU Series – Heat Pump –
ED21-302
Dimensions and Service Space
1
FHYB60F + BYBS71DJW1 Without Canvas Duct FHYB71F + BYBS71DJW1 Unit (mm)
45
(Reqjired space)
195
FHYB71F
6.4
9.5 16-φ7 760
4
6
2
FHYB60F
46
150 215 245
A
300 or more Survice space
B
350 or more
D
Model
135 120
150 200
57
5
3
Suction air intake position when installing the duct 5×150=750 785
View
150 250 300
D
160
500
462 (Ceiling opening)
950 927
228
10
5×150=750 785
440 315
1 2×65=130
Suspension bolt
45
C
60 50
67
1000 760 65
300 245 215 150 135
8
∗ The required ceiling depth varies according to configuration of specific system
800 595 (Air suction panel center)
25
1060 (Ceiling opening)
6×150=900
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
1000
1100 18-M5 Hole
B
View
160 P. C. D
11×65=715
600 fresh air intake position
1. Liquid pipe connection Flare 2. Gas pipe connection φ15.9 Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
100
630 (Suspension position) 145
φ125 (Knockout hole)
6-M5 Hole (Circumference Liner)
C
7
View
1050 (Suspension position)
A
JC : DU226-256
View
FHYB60F + BYBS71DJW1 With Canvas Duct FHYB71F + BYBS71DJW1 60 50
25
135 120
D
5
Model 195
3
1 2×65=130
150 200
300 245 215 150 135 45 115~255
B 57
45
2
A
46
6
300 or more
4
FHYB60F
FHYB71F
6.4
9.5
16-φ7 760
10
Service space
950
Suction air intake position when instaling the duct.
1000 18-M5 hole
1100
B 160 P. C. D φ125 (Knockout hole)
View
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
1. Liquid pipe connection Flare 2. Gas pipe connection φ15.9Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
6-M5 hole (Circumference liner)
7
SkyAir LU Series – Heat Pump –
View
600 Fresh air intake position
100
630 (Suspension position) 145
11×65=715
View
D
6×150=900
1060 (Ceiling opening)
A
5×150=750 785
150 250 300
160
228
500
462 (Ceiling opening)
927
1050 (Suspension position)
150 215 245
C
315 Suspension bolt
67
65
∗ The required ceiling depth varies according to configuration of specific system
440
760 5×150=750
8
Unit (mm)
800 595 (Air suction panel center)
465 or more Required installation space
1000 785
C
View
JC : DU226-257
25
Dimensions and Service Space
ED21-302
FHYB100F + BYBS125DJW1 Without Canvas Duct FHYB125F + BYBS125DJW1 Unit (mm)
10
7×150=1050 1185
57
5
A
195
135 120 45
B
7×150=1050 1185
4
6
2
300 or more Survice space
20-φ7 1160
150 215 245
3
(Reqjired space)
440 315 2×65=130
150 200
300 245 215 150 135
D
∗ The required ceiling depth varies according to configuration of specific system
800 595 (Air suction panel center)
1
45
C
Suspension bolt 4-M8~M10
67
8
60 50
350 or more
25 1400 1160 65
D
46
View
462 (Ceiling opening)
Suction air intake position when instaling the duct.
150 250 300
228
160
500
1328
1460 (Ceiling opening)
9×150=1350
1500
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
1400 24-M5 hole
B
View
160 P. C. D
16×65=1040
600 fresh air intake
1. Liquid pipe connection φ9.5 Flare 2. Gas pipe connection φ19.1 Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
100
630 (Suspension position) 145
φ125 (Knockout hole)
6-M5 Hole (Circumference Liner)
C
7
View
1450 (Suspension position)
A
View
FHYB100F + BYBS125DJW1 With Canvas Duct FHYB125F + BYBS125DJW1 25
3
1
20-φ7
45 115~255
B 57
2
A
45
46
6
300 or more
4
1160
465 or more Required installation space
D
5 135 120
150 200
300 245 215 150 135
C
315 Suspension bolt 4-M8~M10 67
65
∗ The required ceiling depth varies according to configuration of specific system
440
2×65=130
8
Unit (mm)
800 595 (Air suction panel center)
150 215 245
60 50
1160 7×150=1050
195
1400 1185
7×150=1050 1185
10
Service space Suction air intake position when instaling the duct.
D
View
9×150=1350 1400
1460 (Ceiling opening)
24-M5 hole
1500
B 160 P. C. D φ125 (Knockout hole)
View
1. Liquid pipe connection φ9.5 Flare 2. Gas pipe connection φ19.1 Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
6-M5 hole (Circumference)
7 1450 (Suspension position)
A
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
600 Fresh air intake position
100
630 (Suspension position) 145
16×65=1040
26
150 250 300
160
228
500
462 (Ceiling opening)
1328
C
View
View
SkyAir LU Series – Heat Pump –
ED21-302
5.1.8
Dimensions and Service Space
FUY (New Ceiling Suspended Cassette Type)
1
FUY71FJ Unit (mm)
3D013860A
FUY100FJ FUY125FJ Unit (mm)
3D013859A
SkyAir LU Series – Heat Pump –
27
Dimensions and Service Space
5.1.9
ED21-302
FHY (Ceiling Suspended Type)
FHY35B FHY50B Unit (mm)
A
Model
FHY35B
FHY50B
A
12.7
15.9
3D027536C 3D028600
FHY60B FHY71B Unit (mm)
A
28
Model
FHY60B
FHY71B
A
6.4
9.5
3D027537 3D027538B
SkyAir LU Series – Heat Pump –
ED21-302
Dimensions and Service Space
1
FHY100B Unit (mm)
3D027539B
FHY125B Unit (mm)
3D027540
SkyAir LU Series – Heat Pump –
29
Dimensions and Service Space
ED21-302
5.1.10 FAY (Wall Mounted Type) FAY71L Unit (mm)
3D038540A
FAY100FA Unit (mm)
3D014381A
30
SkyAir LU Series – Heat Pump –
ED21-302
Dimensions and Service Space
5.1.11 Floor Standing Type
1
FVY71LA Unit (mm)
3D031617
FVY100LA FVY125LA Unit (mm)
3D031618
SkyAir LU Series – Heat Pump –
31
Dimensions and Service Space
5.2
ED21-302
Remote Controller
BRC7C612W (Wireless Type for FHYC~K)
BRC7C528W (Wireless Type for FUY~FJ)
32
SkyAir LU Series – Heat Pump –
ED21-302
Dimensions and Service Space
1
BRC7E618 (Wireless Type for FAY71L)
FAY71
C : 3D034905
BRC7C610W (Wireless Type for FAY100FA)
SkyAir LU Series – Heat Pump –
33
Dimensions and Service Space
ED21-302
BRC7E63W (Wireless Type for FHY~B)
3D028963
BRC1C61 (Wired Type)
More comfortable operation by thermo sensor in the Remote Controller Applicable Model FHYK-FJ FH(Y)-B FH(Y)C-K FHYB-F FUY-FJ FV(Y)-LA (Available for 2 remote control use) FAY-FA/L
C : 3D028952
34
SkyAir LU Series – Heat Pump –
ED21-302
5.3
Dimensions and Service Space
Outdoor Unit
1
RY35F
RY50GA Unit (mm)
3D004853B
SkyAir LU Series – Heat Pump –
35
Dimensions and Service Space
ED21-302
RY60GA Unit (mm)
3D004852A
RY71LU Unit (mm)
3D039213
36
SkyAir LU Series – Heat Pump –
ED21-302
Dimensions and Service Space
1
RY100LU Unit (mm)
3D039214
RY125LU Unit (mm)
3D039215
SkyAir LU Series – Heat Pump –
37
Dimensions and Service Space
ED21-302
RY140LU Unit (mm)
3D039216
38
SkyAir LU Series – Heat Pump –
ED21-302
5.4
Dimensions and Service Space
Installation Service Space for RY71LU, 100LU, 125LU, 140LU
1
140 140
3D039172-1
SkyAir LU Series – Heat Pump –
39
Dimensions and Service Space
ED21-302
3D039172-2
40
SkyAir LU Series – Heat Pump –
ED21-302
Piping Diagrams
6. Piping Diagrams 6.1
1
Indoor Unit + Outdoor Unit
RY35FV1A
RY50GAV1A
C : 3D028561
SkyAir LU Series – Heat Pump –
41
Piping Diagrams
ED21-302
RY60GAV1A
C : 3D028562
RY71LU
3D039734
42
SkyAir LU Series – Heat Pump –
ED21-302
Piping Diagrams
1
RY100LU
3D039735
RY125LU
3D039736
SkyAir LU Series – Heat Pump –
43
Piping Diagrams
ED21-302
RY140LU
3D039737
44
SkyAir LU Series – Heat Pump –
ED21-302
Wiring Diagrams
7. Wiring Diagrams 7.1
1
Indoor Unit
FHYC35KVE FHYC50KVE FHYC60KVE FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE
3D005668C
SkyAir LU Series – Heat Pump –
45
Wiring Diagrams
ED21-302
FHYK35FJV1 FHYK45FJV1 FHYK60FJV1 FHYK71FJV1
DU423-5174A
46
SkyAir LU Series – Heat Pump –
ED21-302
Wiring Diagrams
1
FHYB35FV1 FHYB45FV1 FHYB60FV1 FHYB71FV1
DU423-5173C
SkyAir LU Series – Heat Pump –
47
Wiring Diagrams
ED21-302
FHYB100FV1 FHYB125FV1
DU428-5353C
48
SkyAir LU Series – Heat Pump –
ED21-302
Wiring Diagrams
1
FUY71FJV1 FUY100FJV1 FUY125FJV1
3D013404B
SkyAir LU Series – Heat Pump –
49
Wiring Diagrams
ED21-302
FHY35BVE FHY50BVE FHY60BVE FHY71BVE FHY100BVE FHY125BVE
3D027502
50
SkyAir LU Series – Heat Pump –
ED21-302
Wiring Diagrams
1
FAY71LVE
3D037717B
SkyAir LU Series – Heat Pump –
51
Wiring Diagrams
ED21-302
FAY100FAVE
DU427-5410E
52
SkyAir LU Series – Heat Pump –
ED21-302
Wiring Diagrams
1
FVY71LAVE FVY100LAVE FVY125LAVE
3D013540B
SkyAir LU Series – Heat Pump –
53
Wiring Diagrams
7.2
ED21-302
Outdoor Units
RY35FV1A
RY50GAV1A
3D028080
54
SkyAir LU Series – Heat Pump –
ED21-302
Wiring Diagrams
1
RY60GAV1A
3D028081
RY71LUV1 RY100LUV1
3D037639C
SkyAir LU Series – Heat Pump –
55
Wiring Diagrams
ED21-302
RY71LUY1 RY100LUY1
3D037641C
RY125LUY1 RY140LUY1
3D037643C
56
SkyAir LU Series – Heat Pump –
ED21-302
Capacity Tables
8. Capacity Tables 8.1
1
Capacity Tables
FHYC35KVE + RY35FV1A
C : 3D006617
FHYC50KVE + RY50GAV1A
C : 3D006614
SkyAir LU Series – Heat Pump –
57
Capacity Tables
ED21-302
FHYC60KVE + RY60GAV1A
C : 3D006613
FHYK35FJV1 / FHYB35FV1 / FHY35BVE + RY35FV1A
3D006626B
58
SkyAir LU Series – Heat Pump –
ED21-302
Capacity Tables
1
FHYK45FJV1 / FHYB45FV1 / FHY50BVE + RY50GAV1A
C : 3D006623B
FHYK60FJV1 / FHYB60FV1 / FHY60BVE + RY60GAV1A
C : 3D006622B
SkyAir LU Series – Heat Pump –
59
Capacity Tables
ED21-302
FHYC71KVE / FHYK71FJV1 / FHYB71FV1 / FUY71FJV1 / FHY71BVE / FAY71LVE / FVY71LAVE + RY71LUV1 FHYC71KVE / FHYK71FJV1 / FHYB71FV1 / FUY71FJV1 / FHY71BVE / FAY71LVE / FVY71LAVE + RY71LUY1
3D039611A
FHYC100KVE / FHYB100FV1 / FUY100FJV1 / FHY100BVE / FAY100FAVE / FVY100LAVE + RY100LUV1 FHYC100KVE / FHYB100FV1 / FUY100FJV1 / FHY100BVE / FAY100FAVE / FVY100LAVE + RY100LUY1
3D039624
60
SkyAir LU Series – Heat Pump –
ED21-302
Capacity Tables
1
FHYC125KVE / FHYB125FV1 / FUY125FJV1 / FHY125BVE / FVY125LAVE + RY125LUY1
3D039633
FHYC140KVE + RY140LUY1
3D039642
SkyAir LU Series – Heat Pump –
61
Capacity Tables
8.2
ED21-302
Capacity Correction Factor by The Length of Refrigerant Piping
Cooling (Heating) capacity correction factor
The cooling and heating capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit) All Models for Pair System (Reference Valve) 100
60 35·50 35·50
95
71~125
90
85
100 71 125
80 140 75
0
5
10
20 25 30 35 15 Length of refrigerant piping (Total length)
40
45
50 (m) (S0003)
Notes:
62
1.
line: Correction factor for cooling capacity line: Correction factor for heating capacity 2. The correction factor remains the same whether the outdoor unit is to be installed above or below the indoor unit. 3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the range of its limitation.
SkyAir LU Series – Heat Pump –
ED21-302
Operation Limits
9. Operation Limits 9.1
1
Operation Limits
RY35FV1 RY50GAV1A RY60GAV1A
RY71LUV1 / RY71LUY1 RY100LUV1 / RY100LUY1 RY125LUY1 RY140LUY1
3D039656
SkyAir LU Series – Heat Pump –
63
Sound Level
ED21-302
10. Sound Level 10.1
Overall Sound Level dB(A) 50Hz Model
220V
240V
Measuring Location
H
L
H
L
FHYC35K FHYC50K FHYC60K FHYC71K FHYC100K FHYC125K FHYC140K
33 33 35 35 39 42 44
29 29 30 30 34 36 37
35 35 37 37 41 44 46
31 31 32 32 36 38 39
FHYC
FHYK35FJ FHYK45FJ FHYK60FJ FHYK71FJ
39 39 41 41
33 34 36 36
41 41 43 43
35 36 38 38
FHYK
FHYB35F FHYB45F FHYB60F FHYB71F FHYB100F FHYB125F
38 39 41 41 41 44
32 34 35 35 35 38
40 41 43 43 43 46
34 36 37 37 37 40
FHYB
FUY71FJ FUY100FJ FUY125FJ
40 43 44
35 38 39
42 45 46
37 40 41
FUY
FHY35B FHY50B FHY60B FHY71B FHY100B FHY125B
37 38 38 39 42 44
32 33 33 35 37 39
37 38 38 39 42 44
32 33 33 35 37 39
FHY
FAY71L FAY100FA
43 45
37 41
43 45
37 41
FAY
FVY71LA FVY100LA FVY125LA
41 46 49
35 40 43
43 48 51
37 42 45
FVY
Cooling
Heating
Cooling
Heating
47 49 54 48 49
48 51 54 49 52
48 50 56 49 50
49 52 56 50 53
(S0007)
RY35F RY50GA RY60GA RY71LU RY100LU
380V RY71LU RY100LU RY125LU RY140LU
Microphone
4D028280A
RY35~60
RY71~140LU
415V
Cooling
Heating
Cooling
Heating
48 49 49 54
49 52 52 56
49 50 50 55
50 53 53 57
Microphone
4D039806
Note:
64
Operation sound is measured in an anechoic chamber.
SkyAir LU Series – Heat Pump –
ED21-302
10.2
Sound Level
Octave Band Level
1
10.2.1 Indoor Units FHYC35KVE FHYC50KVE
FHYC60KVE FHYC71KVE
FHYC100KVE
FHYC125KVE
FHYC140KVE
FHYK35FJV1
70
NC-60 60
H(240V) NC-50 50
H(220V) NC-40 40 NC-30 30
L(240V) NC-20 20
L(220V)
63
125
250
500
1000
2000
4000
8000
4D013951
FHYK45FJV1
FHYK60FJV1 FHYK71FJV1
FHYB35FV1
FHYB45FV1
FHYB60FV1 FHYB71FV1
FHYB100FV1
SkyAir LU Series – Heat Pump –
65
Sound Level
ED21-302
FHYB125FV1
FUY71FJV1
FUY100FJV1
4D013827A
FUY125FJV1
4D028280A
4D013829A
FHY125BVE
4D028281A
FHY100BVE
FHY71BVE
4D028282
4D028355
4D028283
FAY71LVE
4D028284
66
FHY50BVE
FHY35BVE
FHY60BVE
4D013828A
4D038512A
SkyAir LU Series – Heat Pump –
ED21-302
Sound Level
FAY100FAVE (Cooling)
FAY100FAVE (Heating)
4D014379A
FVY100LAVE
FVY71LAVE
1
4D013840B
4D014380A
FVY125LAVE
4D013841A
4D013842B
10.2.2 Outdoor Units RY35FV1A (Cooling)
RY35FV1A (Heating)
RY50GAV1A (Cooling)
3D028537
RY60GAV1A (Heating)
RY60GAV1A (Cooling)
RY50GAV1A (Heating)
3D028537
SkyAir LU Series – Heat Pump –
3D028538
3D028538
67
Sound Level
ED21-302
RY71LUV1 / RY71LUY1 (Cooling)
RY71LUV1 / RY71LUY1 (Heating)
4D039802
RY100LUV1 / RY100LUY1 (Cooling)
4D039803
RY125LUY1 (Cooling)
RY100LUV1 / RY100LUY1 (Heating)
4D039805
RY140LUY1 (Cooling)
4D039804
RY125LUY1 (Heating)
4D039806
4D039807
RY140LUY1 (Heating)
4D039808
4D039809
240V, 415V, 50Hz 220V, 380V, 50Hz
68
SkyAir LU Series – Heat Pump –
ED21-302
Fan Performance
11. Fan Performance 11.1
1
Ceiling Mounted Built-In Type
FHYB35F
FHYB45F
FHYB60F
FHYB71F
SkyAir LU Series – Heat Pump –
69
Fan Performance
FHYB100F
FHYB125F
Notes:
70
ED21-302
1. The remote controller can be used to switch between “high” and “low”. 2. The air flow is set to “standard” before leaving the factory. It is possible to switch between “standard ESP” and “high ESP” by remote controller. 3. The internal static pressure indicates the characteristics of the fan when a suction panel (optional accessory) and a canvas for the suction panel (optional accessory) are incorporated into the main unit (with a long-life filter).
SkyAir LU Series – Heat Pump –
ED21-302
Air Velocity and Temperature Distribution
12. Air Velocity and Temperature Distribution 12.1
1
Indoor Unit
12.1.1 Ceiling Mounted Cassette Type FHYC71K (Heating · Air Velocity Distribution) Air Flow Direction : 65°
(12001)
FHYC71K (Heating · Temperature Distribution) Air Flow Direction : 65°
(12002)
FHYC125K (Heating · Air Velocity Distribution) Air Flow Direction : 65°
(12003)
FHYC125K (Heating · Temperature Distribution) Air Flow Direction : 65°
(12004)
SkyAir LU Series – Heat Pump –
71
Air Velocity and Temperature Distribution
ED21-302
12.1.2 Ceiling Mounted Cassette Corner Type FHYK71FJ (Heating · Air Velocity Distribution) Vertical Air Outlet
(12005)
FHYK71FJ (Heating · Temperature Distribution) Vertical Air Outlet
(12006)
12.1.3 Ceiling Mounted Built-In Type FHYB71F (Heating · Air Velocity Distribution) For 9 m³/min Dischange Grille (Option) use
(12007)
FHYB71F (Heating · Temperature Distribution) For 9 m³/min Dischange Grille (Option) use
(12008)
72
SkyAir LU Series – Heat Pump –
ED21-302
Air Velocity and Temperature Distribution
FHYB125F (Heating · Air Velocity Distribution) For 9 m³/min Dischange Grille (Option) use
1
(12009)
FHYB125F (Heating · Temperature Distribution) For 9 m³/min Dischange Grille (Option) use
(12010)
12.1.4 New Ceiling Suspended Cassette type FUY71FJ (Heating · Air Velocity Distribution) Vertical Air Multi Flow
(12011)
FUY71FJ (Heating · Temperature Distribution) Vertical Air Multi Flow
(12012)
SkyAir LU Series – Heat Pump –
73
Air Velocity and Temperature Distribution
ED21-302
FUY125FJ (Heating · Air Velocity Distribution) Vertical Air Multi Flow
(12013)
FUY125FJ (Heating · Temperature Distribution) Vertical Air Multi Flow
(12014)
12.1.5 Floor Standing Type FVY71LA (Heating · Air Velocity Distribution) Vertical Air Flow : 25° (m)
(Air Distribution)
2.7 2.0
0.5m/s
1.0
1.0m/s 2.0m/s
1.5m/s
0.3 0
1
2
3
4
5
6
7
8 (m) (12015)
FVY71LA (Heating · Temperature Distribution) Vertical Air Flow : 25° (m)
(Temperature)
2.7 22
2.0 25
1.0 31
28
0.3 0
1
2
3
4
5
6
7
8 (m) (12016)
74
SkyAir LU Series – Heat Pump –
ED21-302
Air Velocity and Temperature Distribution
FVY125LA (Heating · Air Velocity Distribution) Vertical Air Flow : 25°
1 (m)
(Air Distribution)
2.7 2.0
0.5m/s
1.0m/s
1.0
1.5m/s 2.0m/s
0.3 0
1
2
3
4
5
6
7
8 (m) (12017)
FVY125LA (Heating · Temperature Distribution) Vertical Air Flow : 25° (m)
(Temperature)
2.7 2.0
22
25
1.0
28 31
0.3 0
1
2
3
4
5
6
7
8 (m) (12018)
12.1.6 Ceiling Suspended Type FHY71B (Heating · Air Velocity Distribution) Intermediate Flow
(12019)
FHY71B (Heating · Temperature Distribution) Intermediate Flow
(12020)
SkyAir LU Series – Heat Pump –
75
Air Velocity and Temperature Distribution
ED21-302
FHY125B (Heating · Air Velocity Distribution) Intermediate Flow
(12021)
FHY125B (Heating · Temperature Distribution) Intermediate Flow
(12022)
76
SkyAir LU Series – Heat Pump –
ED21-302
Electric Characteristics
13. Electric Characteristics 13.1
1
RY35~60 Unit Combination
Indoor
Outdoor
Power Supply Hz - Volts
FHYC35KVE
RY35FV1A
50 - 220 50 - 230 50 - 240
FHYK35FJV1
RY35FV1A
50 - 220 50 - 230 50 - 240
Voltage Range
Compressor
MCA
IFM
MFA
LRA
RLA
kW
FLA
kW
FLA
—
15
33 34 35
7.2 7.3 7.3
0.027
0.3
0.045
0.6
9.0
—
15
33 34 35
6.6 6.7 6.7
0.027
0.3
0.02
0.2
9.3
—
15
33 34 35
6.6 6.7 6.7
0.027
0.3
0.065
0.5
10.0
TOCA
OFM
Max.50Hz 264V Min.50Hz 198V
FHYB35FV1
RY35FV1A
50 - 220 50 - 230 50 - 240
FHY35BVE
RY35FV1A
50 - 220 50 - 230 50 - 240
10.0
—
15
33 34 35
7.2 7.3 7.3
0.027
0.3
0.062
0.6
FHYC50KVE
RY50GAV1A
50 - 220 50 - 230 50 - 240
13.2
—
20
37 38 40
8.7 9.2 9.8
0.035
0.4
0.045
0.6
FHYK45FJV1
RY50GAV1A
50 - 220 50 - 230 50 - 240
11.7
—
20
37 38 40
8.7 8.8 8.8
0.035
0.4
0.025
0.3
12.1
—
20
37 38 40
8.7 8.8 8.8
0.035
0.4
0.085
0.7
Max.50Hz 264V Min.50Hz 198V
FHYB45FV1
RY50GAV1A
50 - 220 50 - 230 50 - 240
FHY50BVE
RY50GAV1A
50 - 220 50 - 230 50 - 240
13.3
—
20
37 38 40
8.7 9.2 9.8
0.035
0.4
0.062
0.6
FHYC60KVE
RY60GAV1A
50 - 220 50 - 230 50 - 240
13.7
—
20
55 58 60
9.9 9.7 9.6
0.053
0.7
0.045
0.6
FHYK60FJV1
RY60GAV1A
50 - 220 50 - 230 50 - 240
17.0
—
25
55 58 60
12.4 12.5 12.6
0.053
0.7
0.045
0.5
17.2
—
25
55 58 60
12.4 12.5 12.6
0.053
0.7
0.11
0.7
13.7
—
20
55 58 60
9.9 9.7 9.6
0.053
0.7
0.062
0.6
FHYB60FV1
RY60GAV1A
50 - 220 50 - 230 50 - 240
FHY60BVE
RY60GAV1A
50 - 220 50 - 230 50 - 240
Max.50Hz 264V Min.50Hz 198V
3D006300 3D006610D
SkyAir LU Series – Heat Pump –
77
Electric Characteristics
13.2
ED21-302
RY71 Unit Combination
Indoor
Power Supply
Outdoor
Hz - Volts
Voltage Range
Compressor
MCA
TOCA
OFM
IFM
MFA
LRA
RLA
kW
FLA
kW
FLA
23.2
30
82 78 75
13.5 12.9 12.3
0.065
0.6
0.045
0.6
FHYC71KVE
RY71LUV1
50 - 220 50 - 230 50 - 240
FHYK71FJV1
RY71LUV1
50 - 220 50 - 230 50 - 240
18.4
23.1
30
82 78 75
13.8 13.2 12.6
0.065
0.6
0.045
0.5
FHYB71FV1
RY71LUV1
50 - 220 50 - 230 50 - 240
18.9
23.5
30
82 78 75
13.9 13.3 12.7
0.065
0.6
0.125
0.9
FUY71FJV1
RY71LUV1
50 - 220 50 - 230 50 - 240
18.1
23.2
30
82 78 75
13.5 13.0 12.4
0.065
0.6
0.045
0.6
FHY71BVE
RY71LUV1
50 - 220 50 - 230 50 - 240
18.6
23.2
30
82 78 75
13.9 13.3 12.8
0.065
0.6
0.062
0.6
FAY71LVE
RY71LUV1
50 - 220 50 - 230 50 - 240
17.9
23.0
30
82 78 75
13.5 12.9 12.4
0.065
0.6
0.068
0.4
FVY71LAVE
RY71LUV1
50 - 220 50 - 230 50 - 240
18.7
23.3
30
82 78 75
13.9 13.3 12.8
0.065
0.6
0.030
0.7
FHYC71KVE
RY71LUY1
50 - 380/220 50 - 400/230 50 - 415/240
7.3
8.7
15
40 38 37
4.9 4.7 4.5
0.065
0.6
0.045
0.6
FHYK71FJV1
RY71LUY1
50 - 380/220 50 - 400/230 50 - 415/240
7.4
8.6
15
40 38 37
5.0 4.8 4.6
0.065
0.6
0.045
0.5
FHYB71FV1
RY71LUY1
50 - 380/220 50 - 400/230 50 - 415/240
7.9
9.0
15
40 38 37
5.1 4.8 4.6
0.065
0.6
0.125
0.9
FUY71FJV1
RY71LUY1
50 - 380/220 50 - 400/230 50 - 415/240
7.5
8.7
15
40 38 37
5.1 4.7 4.5
0.065
0.6
0.045
0.6
FHY71BVE
RY71LUY1
50 - 380/220 50 - 400/230 50 - 415/240
7.6
8.7
15
40 38 37
5.1 4.8 4.6
0.065
0.6
0.062
0.6
FAY71LVE
RY71LUY1
50 - 380/220 50 - 400/230 50 - 415/240
7.3
8.5
15
40 38 37
5.0 4.7 4.5
0.065
0.6
0.068
0.4
FVY71LAVE
RY71LUY1
50 - 380/220 50 - 400/230 50 - 415/240
7.7
8.8
15
40 38 37
5.1 4.8 4.6
0.065
0.6
0.030
0.7
Max.50Hz 264V Min.50Hz 198V
Max.50Hz 456/264V Min.50Hz 342/198V
18.1
3D039576C
Symbols: MCA : Min. Circuit Amps TOCA : Total Over-current Amps MFA : Max. Fuse Amps (See note 7) LRA : Locked Rotor Amps RLA : Rated Load Amps OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps kW : Fan Motor Rated Output Notes: 1. RLA is based on the following conditions: Indoor temp. 27ºCDB/19.0ºCWB Outdoor temp. 35ºCDB 2. TOCA means the total value of each OC set. 3. Votage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. 4. Maximum allowable voltage unbalance between phases is 2%. 5. MCA/MFA MCA=1.25×RLA+ea.FLA MFA≤2.25×RLA+ea.FLA (Next lower standard fuse rating, Min.15A) 6. Select wire size base on the larger value of MCA or TOCA. 7. Instead of fuse, use circuit breaker.
78
SkyAir LU Series – Heat Pump –
ED21-302
13.3
Electric Characteristics
RY100~140 Unit Combination
Indoor
Power Supply
Outdoor
Hz - Volts
Voltage Range
Compressor
MCA
TOCA
OFM
1
IFM
MFA
LRA
RLA
kW
FLA
kW
FLA
27.8
40
114 109 105
17.9 17.2 16.5
0.09
0.8
0.090
1.0
FHYC100KVE
RY100LUV1
50 - 220 50 - 230 50 - 240
FHYB100FV1
RY100LUV1
50 - 220 50 - 230 50 - 240
24.2
27.8
40
114 109 105
17.9 17.1 16.4
0.09
0.8
0.135
1.0
FUY100FJV1
RY100LUV1
50 - 220 50 - 230 50 - 240
24.1
27.8
40
114 109 105
17.8 17.1 16.4
0.09
0.8
0.090
1.0
23.8
27.5
40
114 109 105
17.8 17.0 16.3
0.09
0.8
0.135
0.7
24.2
Max.50Hz 264V Min.50Hz 198V
FHY100BVE
RY100LUV1
50 - 220 50 - 230 50 - 240
FAY100FAVE
RY100LUV1
50 - 220 50 - 230 50 - 240
23.5
27.1
40
114 109 105
17.9 17.1 16.4
0.09
0.8
0.046
0.3
FVY100LAVE
RY100LUV1
50 - 220 50 - 230 50 - 240
24.4
28.1
40
114 109 105
17.8 17.0 16.3
0.09
0.8
0.060
1.3
FHYC100KVE
RY100LUY1
50 - 380/220 50 - 400/230 50 - 415/240
10.1
11.8
15
50 48 46
6.6 6.3 6.1
0.09
0.8
0.090
1.0
FHYB100FV1
RY100LUY1
50 - 380/220 50 - 400/230 50 - 415/240
10.1
11.8
15
50 48 46
6.6 6.3 6.0
0.09
0.8
0.135
1.0
FUY100FJV1
RY100LUY1
50 - 380/220 50 - 400/230 50 - 415/240
10.1
11.8
15
50 48 46
6.6 6.2 6.0
0.09
0.8
0.090
1.0
FHY100BVE
RY100LUY1
50 - 380/220 50 - 400/230 50 - 415/240
9.8
11.5
15
50 48 46
6.6 6.2 6.0
0.09
0.8
0.135
0.7
FAY100FAVE
RY100LUY1
50 - 380/220 50 - 400/230 50 - 415/240
9.4
11.1
15
50 48 46
6.6 6.3 6.0
0.09
0.8
0.046
0.3
FVY100LAVE
RY100LUY1
50 - 380/220 50 - 400/230 50 - 415/240
10.2
12.1
15
50 48 46
6.5 6.2 6.0
0.09
0.8
0.060
1.3
FHYC125KVE
RY125LUY1
50 - 380/220 50 - 400/230 50 - 415/240
12.3
15.3
20
51 53 56
7.9 8.0 8.0
0.065 + 0.085
0.6 + 0.7
0.090
1.0
FHYB125FV1
RY125LUY1
50 - 380/220 50 - 400/230 50 - 415/240
12.3
15.7
20
51 53 56
7.5 7.6 7.7
0.065 + 0.085
0.6 + 0.7
0.225
1.4
FUY125FJV1
RY125LUY1
50 - 380/220 50 - 400/230 50 - 415/240
12.3
15.3
20
51 53 56
7.8 7.9 8.0
0.065 + 0.085
0.6 + 0.7
0.090
1.0
FHY125BVE
RY125LUY1
50 - 380/220 50 - 400/230 50 - 415/240
12.1
15.0
20
51 53 56
8.0 8.0 8.1
0.065 + 0.085
0.6 + 0.7
0.144
0.7
FVY125LAVE
RY125LUY1
50 - 380/220 50 - 400/230 50 - 415/240
12.8
15.8
20
51 53 56
7.9 7.9 8.0
0.065 + 0.085
0.6 + 0.7
0.090
1.5
FHYC140KVE
RY140LUY1
50 - 380/220 50 - 400/230 50 - 415/240
13.0
17.4
25
67 71 74
8.1 8.2 8.5
0.065 + 0.090
0.6 + 0.8
0.090
1.0
Max.50Hz 456/264V Min.50Hz 342/198V
Max.50Hz 456/264V Min.50Hz 342/198V
Max.50Hz 456/264V Min.50Hz 342/198V
3D039577A 3D039578A 3D039579A
SkyAir LU Series – Heat Pump –
79
Option List
ED21-302
14. Option List 14.1
Indoor Unit
FHYC–K Name of Option
Remark
Kit Name 35~71K
100~140K
Decoration Panel
BYC125K-W1
Sealing Member of Air Discharge Outlet
KDBHJ55K160
Panel Spacer
KDBJ55K160W
Fresh Air Intake Kit ∗3
Chamber Type
Without T Joint
KDDP55D160
With T Joint
KDDP55D160K
Direct Installation Type High Efficiency Filter Replacement High Efficiency Filter
KDDJ55X160
(Colorimetric Method 65%)
KAFP556D80
KAFP556D160
(Colorimetric Method 90%)
KAFP557D80
KAFP557D160
(Colorimetric Method 65%)
KAFJ552K80
KAFJ552K160
(Colorimetric Method 90%)
KAFJ553K80
KAFJ553K160
High-Efficiency Filter Chamber
KDDFP55D160
Long-Life Filter
KAFJ551K160
Resin Net (Gravimetric Method 50%)
Ultra–Long Life Filter
KAFP55D160
Ultra–Long Life Replacement Filter
KAFJ55K160H
Chamber Connection Kit ∗4
KKSJ55K160
Branch Duct Chamber Remote Controller
KDJ55K80
KDJ55K160
Wired Type ∗2
BRC1C61 (Note. 2)
Wireless Type
BRC7C612W
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring (Interlock for Fresh Air Intake Fan) ∗1
KRP1B57
Wiring Adaptor for Electrical Appendices ∗1
KRP4A53
Interface Adaptor for SkyAir Series
DTA102A52
Installation Box for Adaptor PCB
KRP1B98 C : 3D006559E
FHYK-FJ Name of Option
Remark
Decoration Panel
Kit Name 35·45FJ
60·71FJ
BYK45FJW1
BYK71FJW1
Panel Spacer
KPBJ52F56W
KPBJ52F80W
Air Discharge Blind Panel
KDBJ52F56W
KDBJ52F80W
Replacement Long-Life Filter Resin Net
KAFJ521F56
KAFJ521F80
Discharge Grille Flexible Duct with Shutter Remote Controller
Wired Type ∗2
K-HV7AW
K-HV9AW
KFDJ52F56
KFDJ52F80
BRC1C61 (Note. 2)
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring (Interlock for Fresh Air Intake Fan)
KRP1B51
Wiring Adaptor for Electrical Appendices
KRP4A51
Interface Adaptor for SkyAir Series
DTA102A52 DU423-9100C
Note:
80
1. 2. 3. 4. 5.
∗1 : Installation box for adaptor PCB(KRP1B98) is necessary. BRC1B61 is also available. ∗2 : Wire for Remote Controller : Field Supplied. ∗3 : Refer to the Option handbook for the detail. ∗4 : When using the filter (High-Efficiency Filter of Ultra-Long Life Filter) and the Fresh Air Intake Kit together, this kit is necessary.
SkyAir LU Series – Heat Pump –
ED21-302
Option List
1
FHYB-F Name of Option
Kit Name
Remark
Decoration Panel
35·45F
60·71F
BYBS45DJW1
BYBS71DJW1
BYBS125DJW1
Service Access Panel
100F
125F
KTBJ25K56W
KTBJ25K80W
KTBJ25K160W
(Colorimetric method 65%)
KAFJ252L56
KAFJ252L80
KAFJ252L160
(Colorimetric method 90%)
KAFJ253L56
KAFJ253L80
KAFJ253L160
Replacement LongResin Net Life Filter
KAFJ251K56
KAFJ251K80
KAFJ251K160
Filter Chamber for Bottom Suction
KAJ25L56D
KAJ25L80D
KAJ25L160D
Filter Chamber for Rear Suction
KAJ25L56B
KAJ25L80B
KAJ25L160B
Canvas Duct
KSAJ25K56
KSAJ25K80
KSAJ25K160
High-Efficiency Filter
Discharge Grille
(φ150)
K-DG4BW
K-DG5BW
K-DG4BW
K-DG5BW
(φ200)
K-DG7BW
K-DG9BW
K-DG7BW
K-DG9BW
Discharge Chamber
(φ150)
K-DGC4B
K-DGC5B
K-DGC4B
K-DGC5B
(φ200)
K-DGC7B
K-DGC9B
K-DGC7B
K-DGC9B
Branch Duct
φ200 → φ150
K-DDV20A
(φ150)
(1m)K-FDK151B, (2m)K-FDK152B, (3m)K-FDK153B, (4m)K-FDK154B, (5m)K-FDK155B, (6m)K-FDK156B
(φ200)
(1m)K-FDK201B, (2m)K-FDK202B, (3m)K-FDK203B, (4m)K-FDK204B, (5m)K-FDK205B, (6m)K-FDK206B
Flexible Duct Blind Board
KBBJ25K56
KBBJ25K80
KBBJ25K160
Adaptor For Discharge
KDAJ25K56
KDAJ25K71
KDAJ25K140
KDJ2507K56
KDJ2507K80
KDJ2507K160
Flange For Suction Remote Controller
Wired Type ∗2
BRC1C61 (Note. 2)
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring (Interlock for Fresh Air Intake Fan)
KRP1B54
Wiring Adaptor for Electrical Appendices
KRP4A51
Interface Adaptor for Skyair Series
DTA102A52 DU423-999B
FUY-FJ Name of Option
Remark
Kit Name 71FJ
100FJ
125FJ
Sealing Member of Air Discharge Outlet ∗3
KDBHJ49F80
KDBHJ49F140
Decoration Panel for Air Discharge
KDBTJ49F80
KDBTJ49F140
Vertical Flap Kit
KDGJ49F80
Replacement Long-Life Filter L Connection Piping Kit Remote Controller
KDGJ49F140 KAFJ495F140
KHFJ49F80
KHFJ49F140
Wired Type ∗2
BRC1C61 (Note. 3)
Wireless Type
BRC7C528W
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified On/Off Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Wiring Adaptor for Electrical Appendices ∗1 Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB
KRP4A53 DTA102A52 KRP1B97 3D013861B
Note:
1. 2. 3. 4. 5.
∗1 : Installation box for adaptor PCB(KRP1B97) is necessary.
BRC1B62 is also available. BRC1B61 is also available. ∗2 : Wire for Remote Controller : Field Supplied. ∗3 : This option is necessary for setting up 2-way (opposing directional) air flow when the air conditioner is installed.
SkyAir LU Series – Heat Pump –
81
Option List
ED21-302
FHY-B Name of Option
Kit Name
Remark
35B
50B
60B
71B
100B
125B
Replacement Long-Life Filter
KAFJ501D56
KAFJ501D80
KAFJ501D112 KAFJ501D160
Drain Pump Kit
KDU50B50VE
KDU50B71VE
KDU50B125VE
L-Type Piping Kit (For Upward Direction)
KHFJ 5F50
Remote Controller
KHFJ5F60
KHFJ 5F80
KHFJ5F160
Wired Type ∗3
BRC1C61
Wireless Type
BRC7E63W
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring
KRP1B54
Wiring Adaptor for Electrical Appendices ∗1
KRP4A52
Interface Adaptor for Skyair Series
DTA102A52
Installation Box for Adaptor PCB
KRP1C93 3D028285A
FAY-L/FA Name of Option
Remark
Drain Pump Kit Remote Controller
Kit Name 71L
100FA
K-KDU572BVE
—
Wired Type ∗3 Wireless Type
BRC1C61 (Note. 5) BRC7E618
Set Back Time Clock
BRC7C610W
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Wiring Adaptor for Electrical Appendices Interface Adaptor for Skyair Series Installation Box for Adaptor PCB
KRP4A51 ∗4
KRP4A51
—
DTA102A52
KRP4A93
— 3D039142C C : DU427-965E
FVY-LA Name of Option
Remark
Replacement Long Life Filter
Kit Name 71~125LA KAFJ95L160
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Remote Controller for 2 Remote Control System
BRC1C61
Adaptor for Wiring ∗2
KRP1B57
Group Control Adaptor ∗2 Interface Adaptor for Skyair Series Installation Box for Adaptor PCB
KRP4A52 DTA102A52 KRP4A95 4D013855A
Note:
82
1. 2. 3. 4. 5.
∗1 : Installation box for adaptor PCB (KRP1C93) is necessary. ∗2 : Installation box for adaptor PCB (KRP4A95) is necessary. ∗3 : Wire for Remote Controller : Field Supplied. ∗4 : Installation box for adaptor PCB (KRP4A93) is necessary.
BRC1B61 is also available.
SkyAir LU Series – Heat Pump –
ED21-302
14.2
Option List
Outdoor Unit
1
14.2.1 RY35~60 Kit Name
Name of Option
RY35F / RY50GA / RY60GA
Drain Piping Kit
KIS95
14.2.2 RY71~140
Name of Option Central Drain Plug
Kit Name RY71LU
RY100LU
RY125LU
RY140LU
KKPJ5F180 3D039655
SkyAir LU Series – Heat Pump –
83
Field Piping and Wiring
ED21-302
15. Field Piping and Wiring 15.1
Field Piping
15.1.1 Maximum Allowable Piping Length and Level Difference RY35F
RY50, 60GA
Max. Allowable Piping Length
20 m
30 m
RY71~140LU 50 m(Equivalent Length 70 m)
Max.Allowable Level Difference
15 m
15 m
30 m
15.1.2 Additional Refrigerant Charge RY35F / RY50GA / RY60GA When the piping length is longer than A m, be sure to follow the instructions below. —Charge the refrigerant additionaly as follows. Additional Charge
A
RY35F
Model
30 g/m
10
RY50GA
30 g/m
10
RY60GA
60 g/m
5
—Evacuate the air in the connecting piping and the indoor unit, and then charge the additional refrigerant. RY71~140LU This unit requires additional charging of refrigerant according to the length of pipe connected at the site. When the entire refrigerant pipe length is within 30 meters, the additional changing is not needed. Take the following steps for proper charging. When Connected to one indoor unit (Pair system)
Main pipe (L1)
Indoor unit One-way length of pipe (L): L1
1. Refrigerant charge amount Additional charging of refrigerant Select the amount of refrigerant which matches a length which exceeds the charge-less length, and add it. Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear surface of the front plate, as this is necessary for after-sales service.
FOR PAIR SYSTEM The maximum allowable pipe length is 50 meters. Pipe excess length over 30 meters Additional Charging Amount
<unit : kg> 10m or less
20m or less
RY71
0.50
1.00
RY100~140
0.75
1.50
2. Recharging refrigerant When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the amount mentioned on the nameplate, and when the pipe length exceeds 30 meters, the charging amount is an addition of the amount stated on the nameplate and the additional charging amount. 1PN05248B
15.1.3 Pump down operation method The outdoor unit is equipped with a low-pressure switch to protect the compressor. Take the following steps to perform the pumping-down operation. Never short-circuit the low-pressure switch in this operation.
84
SkyAir LU Series – Heat Pump –
ED21-302
Field Piping and Wiring
Procedure
Precautions
1. Start the fan operation with the remote controller.
Confirm that stop valves both on the liquid and gas side are open. Take care when the procedure 2 is done first because the indoor unit fan may operate automatically.
2. Push the pumping-down button on the PC board of the outdoor unit.
Compressor and outdoor fan will start operation automatically.
3. Continue operation for 1 min. until operation condition stabilizes. 4. Close the stop valve on the liquid side securely. (Refer to Fig. 13)
— Insecure closing of the valve may result in burning of the compressor.
5. When the low-pressure switch is activated, the unit stops working. At this time, close the stop valve on the gas side.
—
This is the end of pumping-down operation. After pumping-down operation, the remote controller shows “U4” even when ON button on the remote controller is pressed, and it will not operate. Although the remote controller may or may not indicate “U4” according to circumstances at this time, it is normal. When the remote controller indicates “U4”, the indoor unit fan may operate (for about max 30 minutes). Turn off the main power supply switch and turn it on again in need of operation.
Necessity of a trap Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases of deterioration of oil return, it will be necessary to provide a trap at an appropriate place in the riser gas piping. Trap installation spacing Indoor unit Oil trap Gas piping
015m
Liquid piping
0 Marks. Install trap at each difference in height 15m
Outdoor unit
Note:
A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit. Caution to be taken when brazing refrigerant piping “Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”. (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible. (Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g . BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant leakage.
SkyAir LU Series – Heat Pump –
85
1
Field Piping and Wiring
15.2
ED21-302
Field Wiring
V1(A) MODEL
C : DU423-5177C-1
86
SkyAir LU Series – Heat Pump –
ED21-302
SkyAir LU Series (Twin, Triple, Double Twin) — Heat Pump — [50Hz] Model Series Twin
Class
35
50
60
71
100
125
Indoor Units
FHYC
35K×2
50K×2
60K×2
71K×2
100K×2 125K×2
FHY
35B×2
50B×2
60B×2
71B×2
100B×2 125B×2
Outdoor Units
RY
71LU
100LU
125LU
140LU
200KU
Triple
Class
250KU
Double Twin
50
71
50
60
Indoor Units
FHYC
50K×3
71K×3
50K×4
60K×4
FHY
50B×3
71B×3
50B×4
60B×4
Outdoor Units
RY
140LU
200KU
200KU
250KU
Cautions 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
SkyAir LU Series – Heat Pump –
87
2
Features
ED21-302
1. Features SkyAir Series - Twin, Triple, Double Twin Systems (Simultaneous Operation System)
1.1
What are Twin, Triple, Double Twin systems? One large room can be cooled or heated simultaneously by two, three or four indoor units according to the environmental needs. Space saving for outdoor units. Note:
Individual control (Such as room temperature) is not available.
(Ex.)Pair
(Ex.)Pair
(Ex.)Twin
(Ex.)Twin
(Ex.)Triple
(Ex.)Triple
FHYC50K
FHYC50K
FHYC50K
FHYC50K
FHYC50K
FHYC50K
Circuit breaker RY140LU
Even Temperature Distribution Only one Remote Controller Only one Circuit Breaker (S0026-2)
(S0027)
Only one circuit breaker is needed for versatile electric work. Simple refrigerant system due to the branch piping kit specially designed for this system.
88
SkyAir LU Series – Heat Pump –
ED21-302
Model Name and Power Supply
2. Model Name and Power Supply 2.1
Twin Triple and Double Twin System Twin Indoor Units
Outdoor Units
FHYC35KVE+FHYC35KVE
RY71LUV1
FHY35BVE+FHY35BVE
RY71LUV1
FHYC50KVE+FHYC50KVE
RY100LUV1
FHY50BVE+FHY50BVE
RY100LUV1
FHYC35KVE+FHYC35KVE
RY71LUY1
FHY35BVE+FHY35BVE
RY71LUY1
FHYC50KVE+FHYC50KVE
RY100LUY1
FHY50BVE+FHY50BVE
RY100LUY1
FHYC60KVE+FHYC60KVE
RY125LUY1
FHY60BVE+FHY60BVE
RY125LUY1
FHYC71KVE+FHYC71KVE
RY140LUY1
FHY71BVE+FHY71BVE
RY140LUY1
FHYC100KVE+FHYC100KVE
RY200KUY1
FHY100BVE+FHY100BVE
RY200KUY1
FHYC125KVE+FHYC125KVE
RY250KUY1
FHY125BVE+FHY125BVE
RY250KUY1
Power Supply
2 1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
Triple Indoor Units
Outdoor Units
FHYC50KVE+FHYC50KVE+ FHYC50KVE
RY140LUY1
FHY50BVE+FHY50BVE+ FHY50BVE
RY140LUY1
FHYC71KVE+FHYC71KVE+ FHYC71KVE
RY200KUY1
FHY71BVE+FHY71BVE+ FHY71BVE
RY200KUY1
Power Supply
3φ, 380~415V, 50Hz
Double Twin Indoor Units
Notes:
Outdoor Units
FHYC50KVE+FHYC50KVE+ FHYC50KVE+FHYC50KVE
RY200KUY1
FHY50BVE+FHY50BVE+ FHY50BVE+FHY50BVE
RY200KUY1
FHYC60KVE+FHYC60KVE+ FHYC60KVE+FHYC60KVE
RY250KUY1
FHY60BVE+FHY60BVE+ FHY60BVE+FHY60BVE
RY250KUY1
Power Supply
3φ, 380~415V, 50Hz
Power Supply Intake; Outdoor Unit.
SkyAir LU Series – Heat Pump –
89
External Appearance
ED21-302
3. External Appearance 3.1
External Appearance
Indoor Units
FHY–B FHYC-K
Remote Controller
Wired Type Wireless Type
Outdoor Units
RY71LU
RY200KU
90
RY100LU
RY125LU
RY140LU
RY250KU
SkyAir LU Series – Heat Pump –
ED21-302
Specifications
4. Specifications 4.1
FHYC
4.1.1
Twin
FHYC (Ceiling Mounted Cassette Type) Model
Indoor Unit Outdoor Unit
FHYC50KVE×2 FHYC60KVE×2 RY100LUV1 — RY100LUY1 RY125LUY1 ∗1 Cooling Capacity (1)/(2)/(3) 10.5/10.4/10.4 13.0/12.8/12.8 35,700/35,300/35,300 44,500/43,600/43,600 9,000/8,900/8,900 11,200/11,000/11,000 ∗1 Heating Capacity (1)/(2)/(3) 11.2/11.2/11.2 14.2/14.2/14.2 38,100/38,100/38,100 48,400/48,400/48,400 9,600/9,600//9,600 12,200/12,200/12,200 Indoor Unit ∗5 FHYC50KVE×2 FHYC60KVE×2 Dimensions H×W×D mm 230×840×840 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×8×1.5 Face Area m² 0.331 Fan Model QTS45B14M Type Turbo Fan Motor Output W 45 Air Flow Rate ∗2 m³/min. (H)14–16 (L)10–12 (H)15–17 (L)11–13 (H)19–21 (L)14–16 Weight kg 24 Piping Liquid mm φ6.4 (Flare) Connections Gas mm φ12.7 (Flare) φ15.9 (Flare) Drain mm I.Dφ25×O.Dφ32 Remote Controller Wired BRC1C61 (Note. 6) (Option) Wireless BRC7C612W Decoration Model BYC125K–W1×2 Panel Color White (Option) Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Unit V1 RY71LUV1 RY100LUV1 — Y1 RY71LUY1 RY100LUY1 RY125LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 65 90 65+85 Air Flow Rate (C/H) ∗2 m³/min. 48–51 59–62 92–100 Weight kg V1 73 89 — Y1 72 86 101 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm φ26.0 (Hole) Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <RY125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <RY71·100>. Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Max. Length m 50 (Equivalent Length 70m) Ref. Piping Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039080
Notes:
FHYC35KVE×2 RY71LUV1 RY71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 7.9/7.9/7.9 27,000/27,000/27,000 6,800/6,800/6,800 FHYC35KVE×2
V1 Y1 kW Btu/h kcal/h kW Btu/h kcal/h
1.
∗1 The above data based on the conditions shown in the table below.
Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
2. 3. 4. 5. 6.
Heating
Conversion Formulae
Piping length
Hz–Volts
Standard
5m
50Hz–220V (380V)
—
7.5m
50Hz–220V (380V)
JIS B8616
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. ∗5 Each value shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
91
2
Specifications
ED21-302
FHYC (Ceiling Mounted Cassette Type) Model
Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)
FHYC71KVE×2 RY140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 16.3/16.3/16.3 56,000/56,000/56,000 14,000/14,000/14,000 FHYC71KVE×2 230×840×840
kW Btu/h kcal/h kW Btu/h kcal/h
∗1 Heating Capacity (1)/(2)/(3)
Indoor Unit ∗5 Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate ∗2 Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Decoration Model Panel Color (Option) Dimensions (H×W×D) Air Filter Weight Outdoor Unit Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate (C/H) ∗2 Weight Piping Liquid Connections Gas Drain Safety Devices
FHYC125KVE×2 RY250KUY1 27.1/26.6/26.3 92,500/90,800/89,800 23,300/22,900/22,600 28.3/28.4/28.0 96,600/97,000/95,600 24,300/24,400/24,100 FHYC125KVE×2
288×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 2×12×1.5 m² 0.331 0.497 QTS45B14M QTS45A17M Turbo Fan W 45 90 m³/min. (H)19–21 (L)14–15 (H)28–31 (L)21–24 (H)33–36 (L)24–27 kg 24 28 mm φ9.5 (Flare) φ9.5 (Flare) mm φ15.9(Flare) φ19.1 (Flare) mm I.Dφ25×O.Dφ32 BRC1C61 (Note. 6) BRC7C612W BYC125K–W1×2 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 RY140LUY1 RY200KUY1 RY250KUY1 Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 JT170BC–YE JT236D–P1YE JT335D–P1YE Hermetically Sealed Scroll Type kW 4.50 5.5 9.0 P47L11S×2 P52H11SM Propeller W 65+90 230+190 m³/min. 97–109 150/138–154/142 175/161–179/165 kg 112 180 206 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Capillary Tube Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 4.1 (Charged for 30m) 4.0 (Charged for 5m) 5.5 (Charged for 5m) Ref. Oil Model SUNISO 4GSDID–K Charge L 1.6 3.0 Drawing No. 4D039081 4D029812 4D029814
Notes:
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Hz–Volts
Standard
Conversion Formulae
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
5m
50Hz–380V
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–380V
JIS B8616
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–415V
AS 1861
2. 3. 4. 5. 6.
92
mm
FHYC100KVE×2 RY200KUY1 22.5/22.2/22.0 76,800/75,800/75,100 19,400/19,100/18,900 22.6/22.7/22.4 77,200/77,500/76,500 19,400/19,500/19,300 FHYC100KVE×2
Heating
∗2 AFR (Air flow rate) is shown at 380V–415V. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed (For RY140LUY1 only). ∗5 Each value shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
ED21-302
4.1.2
Specifications
Triple / Double Twin
FHYC (Ceiling Mounted Cassette Type) Model
Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)
kW Btu/h kcal/h kW Btu/h kcal/h
FHYC50KVE×3 RY140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 16.3/16.3/16.3 56,000/56,000/56,000 14,000/14,000/14,000 FHYC50KVE×3
FHYC71KVE×3 RY200KUY1
FHYC50KVE×4 RY200KUY1
FHYC60KVE×4 RY250KUY1 27.1/26.6/26.3 92,500/90,800/89,800 23,300/22,900/22,600 28.3/28.4/28.0 96,600/97,000/95,600 24,300/24,400/24,100 FHYC60KVE×4
22.5/22.2/22.0 76,800/75,800/75,100 19,400/19,100/18,900 ∗1 Heating Capacity (1)/(2)/(3) 22.6/22.7/22.4 77,200/77,500/76,500 19,400/19,500/19,300 Indoor Unit ∗5 FHYC71KVE×3 FHYC50KVE×4 Dimensions H×W×D mm 230×840×840 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×8×1.5 Face Area m² 0.331 Fan Model QTS45B14M Type Turbo Fan Motor Output W 45 Air Flow Rate ∗2 m³/min. (H)15–17 (L)11–12 (H)19–21 (L)14–15 (H)15–17 (L)11–12 (H)19–21 (L)14–16 Weight kg 24 Piping Liquid mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) Connections Gas mm φ15.9(Flare) Drain mm I.Dφ25×O.Dφ32 Remote Controller Wired BRC1C61 (Note. 6) (Option) Wireless BRC7C612W Decoration Model BYC125K–W1×3 BYC125K–W1×4 Panel Color White (Option) Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Unit RY140LUY1 RY200KUY1 RY200KUY1 RY250KUY1 Color Ivory Dimensions H×W×D mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×50×2.0 Face Area m² 1.134 1.57 1.97 Comp. Model JT170BC–YE JT236D–P1YE JT335D–P1YE Type Hermetically Sealed Scroll Type Motor Output kW 4.50 5.5 9.0 Fan Model P47L11S×2 P52H11SM Type Propeller Motor Output W 65+90 230+190 Air Flow Rate (C/H) ∗2 m³/min. 97–109 150/138–154/142 175/161–179/165 Weight kg 112 180 206 Piping Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flare) Drain mm φ26.0 (Hole) — Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Capillary Tube Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 4.1 (Charged for 30m) 4.0 (Charged for 5m) 5.5 (Charged for 5m) Ref. Oil Model SUNISO 4GSDID–K Charge L 1.6 3.0 Drawing No. 4D039081 4D029812 4D029814
2
Conversion Formulae
Notes:
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
2. 3. 4. 5. 6.
Heating
Piping length
Hz–Volts
Standard
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
5m
50Hz–380V
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–380V
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–415V
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 380V–415V. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed (For RY140LUY1 only). ∗5 Each value shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
93
Specifications
4.2
FHY
4.2.1
Twin
ED21-302
FHY (Ceiling Suspended Type) Model
Indoor Unit Outdoor Unit
FHY35BVE×2 RY71LUV1 RY71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 7.9/7.9/7.9 27,000/27,000/27,000 6,800/6,800/6,800 FHY35BVE×2
V1 Y1 kW Btu/h kcal/h kW Btu/h kcal/h
∗1 Cooling Capacity (1)/(2)/(3)
∗1 Heating Capacity (1)/(2)/(3)
Indoor Unit ∗5 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit
FHY50BVE×2 RY100LUV1 RY100LUY1 10.5/10.4/10.4 35,700/35,300/35,300 9,000/8,900/8,900 11.2/11.2/11.2 38,100/38,100/38,100 9,600/9,600/9,600 FHY50BVE×2 White
FHY60BVE×2 — RY125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 14.2/14.2/14.2 48,400/48,400/48,400 12,200/12,200/12,200 FHY60BVE×2
195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 2×12×1.75 3×12×1.75 m² 0.182 0.233 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)16 (L)13 Resin Net (with Mold Resistant) kg 23 24 26 mm φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 6) BRC7E63W V1 RY71LUV1 RY100LUV1 — Y1 RY71LUY1 RY100LUY1 RY125LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 65 90 65+85 Air Flow Rate ∗2 m³/min. 48–51 59–62 92–100 Weight kg V1 73 89 — Y1 72 86 101 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm φ26.0 (Hole) Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <RY125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <RY71·100>. Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039083
Notes:
Conversion Formulae
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
2. 3. 4. 5. 6.
94
mm
Heating
Piping length
Hz–Volts
Standard
5m
50Hz–220V (380V)
—
7.5m
50Hz–220V (380V)
JIS B8616
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. ∗5 Each value shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
ED21-302
Specifications
FHY(Ceiling Suspended Type) Model
Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)
FHY100BVE×2 FHY125BVE×2 RY200KUY1 RY250KUY1 kW 22.5/22.2/22.0 27.1/26.6/26.3 Btu/h 76,800/75,800/75,100 92,500/90,800/89,800 kcal/h 19,400/19,100/18,900 23,300/22,900/22,600 ∗1 Heating Capacity (1)/(2)/(3) kW 22.6/22.7/22.4 28,3/28.4/28.0 Btu/h 77,200/77,500/76,500 96,600/97,000/95,600 kcal/h 19,400/19,500/19,300 24,300/24,400/24,100 Indoor Unit ∗5 FHY100BVE×2 FHY125BVE×2 Color White Dimensions H×W×D mm 195×1,160×680 195×1,400×680 195×1,590×680 Coil Type Cross Fin Coil (Multi Louver Fins and N–hix Tubes) Row×Stages×Fin Pitch 3×12×1.75 Face Area m² 0.233 0.293 0.341 Fan Model 4D12K1AA1 3D12K2AA1 4D12K2AA1 Type Sirocco Fan Motor Output W 62 130 Air Flow Rate m³/min. (H)17 (L)14 (H)24 (L)20 (H)30 (L)25 Air Filter Resin Net (with Mold Resistant) Weight kg 27 32 35 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm I.Dφ20×O.Dφ26 Remote Controller Wired BRC1C61 (Note. 6) (Option) Wireless BRC7E63W Outdoor Unit RY140LUY1 RY200KUY1 RY250KUY1 Color Ivory Dimensions H×W×D mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×50×2.0 Face Area m² 1.134 1.57 1.97 Comp. Model JT170BC–YE JT236D–P1YE JT335D–P1YE Type Hermetically Sealed Scroll Type Motor Output kW 4.50 5.5 9.0 Fan Model P47L11S×2 P52H11SM Type Propeller Motor Output W 65+90 230+190 Air Flow Rate (C/H) ∗2 m³/min. 97–109 150/138–154/142 175/161–179/165 Weight kg 112 180 206 Piping Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) Drain mm φ26.0 (Hole) — Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Capillary Tube Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 4.1 (Charged for 30m) 4.0 (Charged for 5m) 5.5 (Charged for 5m) Ref. Oil Model SUNISO 4GSDID–K Charge L 1.6 3.0 3.0 Drawing No. 4D039084 4D028501 4D028500
Notes:
FHY71BVE×2 RY140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 16.3/16.3/16.3 56,000/56,000/56,000 14,000/14,000/14,000 FHY71BVE×2
2
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
5m
50Hz–380V
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–380V
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–415V
AS 1861
2. 3. 4. 5. 6.
Heating
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 380V–415V. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed (For RY140LUY1 only). ∗5 Each value shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
95
Specifications
4.2.2
ED21-302
Triple / Double Twin
FHY(Ceiling Suspended Type) Model
Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)
kW Btu/h kcal/h kW Btu/h kcal/h
FHY50BVE×3 RY140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 16.3/16.3/16.3 56,000/56,000/56,000 14,000/14,000/14,000 FHY50BVE×3
FHY71BVE×3 RY200KUY1
FHY50BVE×4 RY200KUY1
FHY60BVE×4 RY250KUY1 27.1/26.6/26.3 92,500/90,800/89,800 23,300/22,900/22,600 28.3/28.4/28.0 96,600/97,000/95,600 24,300/24,400/24,100 FHY60BVE×4
22.5/22.2/22.0 76,800/75,800/75,100 19,400/19,100/18,900 ∗1 Heating Capacity (1)/(2)/(3) 22.6/22.7/22.4 77,200/77,500/76,500 19,400/19,500/19,300 Indoor Unit ∗5 FHY71BVE×3 FHY50BVE×4 Color White Dimensions H×W×D mm 195×960×680 195×1,160×680 195×960×680 195×1,160×680 Coil Type Cross Fin Coil (Multi Louver Fins and N–hix Tubes) Row×Stages×Fin Pitch 3×12×1.75 Face Area m² 0.182 0.233 0.182 0.233 Fan Model 3D12K1AA1 4D12K1AA1 3D12K1AA1 4D12K1AA1 Type Sirocco Fan Motor Output W 62 Air Flow Rate m³/min. (H)13 (L)10 (H)17 (L)14 (H)13 (L)10 (H)16 (L)13 Air Filter Resin Net (with Mold Resistant) Weight kg 24 27 24 26 Piping Liquid mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) Connections Gas mm φ15.9 (Flare) Drain mm I.Dφ20×O.Dφ26 Remote Controller Wired BRC1C61 (Note. 6) (Option) Wireless BRC7E63W Outdoor Unit RY140LUY1 RY200KUY1 RY200KUY1 RY250KUY1 Color Ivory Dimensions H×W×D mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×50×2.0 Face Area m² 1.134 1.57 1.97 Comp. Model JT170BC–YE JT236D–P1YE JT335D–P1YE Type Hermetically Sealed Scroll Type Motor Output kW 4.50 5.5 9.0 Fan Model P47L11S×2 P52H11SM Type Propeller Motor Output W 65+90 230+190 Air Flow Rate (C/H) ∗2 m³/min. 97–109 150/138–154/142 175/161–179/165 Weight kg 112 180 206 Piping Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) Drain mm φ26.0 (Hole) — Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Capillary Tube Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 4.1 (Charged for 30m) 4.0 (Charged for 5m) 5.5 (Charged for 5m) Ref. Oil Model SUNISO 4GSDID–K Charge L 1.6 3.0 Drawing No. 4D039084 4D028501 4D028500
Conversion Formulae
Notes:
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
(2) (3)
2. 3. 4. 5. 6.
96
Heating
Piping length
Hz–Volts
Standard
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
5m
50Hz–380V
—
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–380V
JIS B8616
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB
7.5m
50Hz–415V
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 380V–415V. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed (For RY140LUY1 only). ∗5 Each value shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Heat Pump –
ED21-302
Dimensions and Service Space
5. Dimensions and Service Space 5.1
Indoor Unit
5.1.1
FHYC (Ceiling Mounted Cassette Type)
FHYC35K + BYC125K-W1 C 860~890 Ceiling opening
2× 100=200
300 or less 680 Suspension position
950
420
9
2
Unit (mm)
85 (165)
Note3.
80
Branch duct connection
350 C
view 60
4-M4 Hole (prepared hole) φ7
80 80
6
40
860~890 Ceiling opening
950
780 Suspension position
10
5
55
55
840
55
12-M4 Hole (prepared hole)
5
150 40 350
2
1
4
165
95 110
85
Branch duct connection
A
∗1500mm or more Required space ∗1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more.
1000 or more Required space
30
8
260 270 315
For fresh air intake kit connection (direct installation type)
view
55
840 80 2× 100=200
295
125 150 240
750 10
B B
200
Adjustable (0~550)
420
3
40
230
view
240
Suspension bolt 4-M8~M10
160
7 A
Description
Name Number 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.
3. In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.
2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
5 6 7 8
φ6.4 flare φ12.7 flare VP25
Remote control code and control wiring connection
Air discharge grille Air suction grille Port for water supply Corner decoration cover
9 10 Drain hose
O.D.32
C : 3D012310B
FHYC50K + BYC125K-W1 FHYC60K + BYC125K-W1 Unit (mm)
C
950
2× 100=200 85
80
860~890 Ceiling opening 300 or less 680 Suspension position
(165)
Note3.
420
9 10
6
Branch duct connection
C view 60
4-M4 Hole (prepared hole) φ7
80
5
80
950
780 Suspension position 860~890 Ceiling opening
40 350
840
55
12-M4 Hole (prepared hole)
8
5
260 270 315
4
1
2
40 350
Branch duct connection
A
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille. 2. When installing an optional accessory, refer to the installation drawings. z For fresh air intake kit ...... Inspection port is necessary. z For high efficiency filter unit ...... Inspection port is not necessary.
165 1000 or more Required space
125 150 240 240
For fresh air intake kit connection (direct installation type)
55
2×100=200 85
95 110
80
150
750 Adjustable (0~550)
55
840 295
200
230
B view
55
30 Suspension bolt 4-M8~M10
B
3
40
10
420
160
7 A view
∗1500mm or more Required space 1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more. Name Number 1 Liquid pipe connection Gas pipe connection 2 Drain pipe connection 3 Power supply connection 4
3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.
5
Remote control code and control wiring connection
6
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
9 10
Air discharge grille Air suction grille Port for water supply Corner decoration cover
7 8
Drain hose
Description φ6.4 flare φ15.9 flare VP25
O.D.32
C : 3D012311B
SkyAir LU Series – Heat Pump –
97
Dimensions and Service Space
ED21-302
FHYC71K + BYC125K-W1
1000 or more
Unit (mm)
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
C : 3D012312C
FHYC100K + BYC125K-W1 FHYC125K + BYC125K-W1 Unit (mm)
C
2× 100=200 85
80
860~890 Ceiling opening
Note3.
(195)
300 or less 680 Suspension position
950
165
6
40 350
Branch duct connection
C view
4-M4 Hole (prepared hole) φ7 5
60 80 80
950
780 Suspension position 860~890 Ceiling opening
10
155
420
9
160
7 A view
420
B
8
5
260 270 315
4
1
14-M4 Hole (prepared hole)
2× 100=200 85
2
40 350
Branch duct connection
A
98
195
150
125 150 298 240
55
840 80
200
30 Suspension bolt 4-M8~M10
55
40 50 155 165
55
840 295
1000 or more Required space
55
40
10
288
750 Adjustable (0~550)
B view
3
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.
3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.
2. When installing an optional accessory, refer to the installation drawings. z For fresh air intake kit ...... Inspection port is necessary. z For high efficiency filter unit ...... Inspection port is not necessary.
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
For fresh air intake kit connection (direct installation type)
∗1500mm or more Required space ∗1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required is space 200mm or more. Number Name 1 Liquid pipe connection Gas pipe connection 2 3 Drain pipe connection 4 Power supply connection 5 6 7 8 9 10
Description φ9.5 flare φ19.1 flare VP25
Remote control code and control wiring connection
Air discharge grille Air suction grille Port for water supply Corner decoration cover Drain hose
O.D.32
C : 3D012313C
SkyAir LU Series – Heat Pump –
ED21-302
5.1.2
Dimensions and Service Space
FHYC with High Efficiency Filter
KAFP556D80 · 557D80 for FHYC35~71K
Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
290
2
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975A
KAFP556D160·557D160 for FHYC100~125K
Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032976A
SkyAir LU Series – Heat Pump –
99
Dimensions and Service Space
5.1.3
ED21-302
FHYC with Fresh Air Intake Kit (Without T Joint, Duct Fan)
KDDP55D160 for FHYC35~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
Note 4
View
Service Access Panel : 450×450mm or more Refer to Note 2
290
Installation Service Access Panel
Connection Chamber (Right)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
How to connect Chamber 4 Independently(Refer to Note 5,6)
Applicable Models Skyair
FH(Y)C35~71K
5 4 3 2 1 Number
Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981A
KDDP55D160 for FHYC100~125K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
View
Service Access Panel : 450×450mm or more Refer to Note 2
Note 4
Installation Service Access Panel
Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
100
Applicable Models Skyair
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984A
SkyAir LU Series – Heat Pump –
ED21-302
5.1.4
Dimensions and Service Space
FHYC with Fresh Air Intake Kit (With T Joint, Without Duct Fan)
KDDP55D160K for FHYC35~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Flexible Duct (Accessory)
2
Installation Service Access Panel
Service Access Panel : 450×450mm or more Refer to Note 2
Suction Duct (K-KFD9A) Optional (Accessory) T Joint
Plate Band
(Accessory)
290
(Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
Applicable Models SkyAir
FH(Y)C35~71K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032987A
KDDP55D160K for FHYC100~125K Service Access Panel : 450×450mm or more Refer to Note 2
Installation Service Access Panel
Unit (mm) Flexible Duct (Accessory)
Service Access Panel : 450×450mm or more Refer to Note 2 Plate Band (Accessory)
T Joint (Accessory)
Suction Duct (K-KFD9A) Optional (Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
SkyAir LU Series – Heat Pump –
Applicable Models Skyair
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032990A
101
Dimensions and Service Space
5.1.5
ED21-302
FHYC with Panel Spacer
KDBJ55K160W for FHYC35~71K Unit (mm)
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005390E
KDBJ55K160W for FHYC100~125K Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005391D
102
SkyAir LU Series â&#x20AC;&#x201C; Heat Pump â&#x20AC;&#x201C;
ED21-302
5.1.6
Dimensions and Service Space
FHY (Ceiling Suspended Type)
FHY35B FHY50B Unit (mm)
2
A
Model
FHY35B
FHY50B
A
12.7
15.9
3D027536C 3D028600
FHY60B FHY71B Unit (mm)
A
SkyAir LU Series – Heat Pump –
Model
FHY60B
FHY71B
A
6.4
9.5
3D027537 3D027538B
103
Dimensions and Service Space
ED21-302
FHY100B Unit (mm)
3D027539B
FHY125B Unit (mm)
3D027540
104
SkyAir LU Series – Heat Pump –
ED21-302
5.2
Dimensions and Service Space
Remote Controller
BRC7C612W (Wireless Type for FHYC~K)
2
BRC7E63W (Wireless Type for FHY~B)
3D028963
SkyAir LU Series – Heat Pump –
105
Dimensions and Service Space
ED21-302
BRC1C61 (Wired Type)
More comfortable operation by thermo sensor in the Remote Controller Applicable Model FHYK-FJ FH(Y)-B FH(Y)C-K FHYB-F FUY-FJ FV(Y)-LA (Available for 2 remote control use) FAY-FA/L
C : 3D028952
106
SkyAir LU Series – Heat Pump –
ED21-302
5.3
Dimensions and Service Space
Outdoor Unit
RY71LU Unit (mm)
2
3D039213
RY100LU Unit (mm)
3D039214
SkyAir LU Series – Heat Pump –
107
Dimensions and Service Space
ED21-302
RY125LU Unit (mm)
3D039215
RY140LU Unit (mm)
3D039216
108
SkyAir LU Series – Heat Pump –
ED21-302
Dimensions and Service Space
RY200KU Unit (mm)
2
3D029265
RY250KU Unit (mm)
3D029264
SkyAir LU Series – Heat Pump –
109
Dimensions and Service Space
5.4
ED21-302
Installation Service Space for RY71LU, 100LU, 125LU, 140LU 140 140
3D039172-1
110
SkyAir LU Series – Heat Pump –
ED21-302
Dimensions and Service Space
2
3D039172-2
SkyAir LU Series – Heat Pump –
111
Dimensions and Service Space
5.5
ED21-302
Installation Service Space for RY200KU, 250KU
3D006578A
112
SkyAir LU Series – Heat Pump –
ED21-302
Piping Diagrams
6. Piping Diagrams 6.1
Twin
3D039761
RY71LU
SkyAir LU Series – Heat Pump –
113
2
Piping Diagrams
ED21-302
3D039762
RY100LU
114
SkyAir LU Series – Heat Pump –
ED21-302
Piping Diagrams
3D039763
RY125LU
2
SkyAir LU Series – Heat Pump –
115
Piping Diagrams
ED21-302
3D039764
RY140LU
116
SkyAir LU Series – Heat Pump –
ED21-302
Piping Diagrams
3D029823
RY200KU
2
SkyAir LU Series – Heat Pump –
117
Piping Diagrams
ED21-302
3D029827
RY250KU
118
SkyAir LU Series – Heat Pump –
ED21-302
6.2
Piping Diagrams
Triple
3D039774
RY140LU
SkyAir LU Series – Heat Pump –
119
2
Piping Diagrams
ED21-302
3D029825
RY200KU
120
SkyAir LU Series – Heat Pump –
ED21-302
6.3
Piping Diagrams
Double Twin
3D029824
RY200KU
SkyAir LU Series – Heat Pump –
121
2
Piping Diagrams
ED21-302
3D029828
RY250KU
122
SkyAir LU Series – Heat Pump –
ED21-302
Wiring Diagrams
7. Wiring Diagrams 7.1
Indoor Unit
FHYC35KVE FHYC50KVE FHYC60KVE FHYC71KVE FHYC100KVE FHYC125KVE
2
3D005668C
SkyAir LU Series – Heat Pump –
123
Wiring Diagrams
ED21-302
FHY35BVE FHY50BVE FHY60BVE FHY71BVE FHY100BVE FHY125BVE
3D027502
124
SkyAir LU Series – Heat Pump –
ED21-302
7.2
Wiring Diagrams
Outdoor Units
RY71LUV1 RY100LUV1
2
3D037639C
RY71LUY1 RY100LUY1
3D037641C
SkyAir LU Series – Heat Pump –
125
Wiring Diagrams
ED21-302
RY125LUY1 RY140LUY1
3D037643C
RY200KUY1
3D028900B
126
SkyAir LU Series – Heat Pump –
ED21-302
Wiring Diagrams
RY250KUY1
2
3D028901B
SkyAir LU Series – Heat Pump –
127
Capacity Tables
ED21-302
8. Capacity Tables 8.1
Capacity Tables
35 × 2 + RY71LUV1 35 × 2 + RY71LUY1
3D039612
50 × 2 + RY100LUV1 50 × 2 + RY100LUY1
3D039625
128
SkyAir LU Series – Heat Pump –
ED21-302
Capacity Tables
60 × 2 + RY125LUY1
2
3D039634
50 × 3 + RY140LUY1 71 × 2 + RY140LUY1
3D039643
SkyAir LU Series – Heat Pump –
129
Capacity Tables
ED21-302
50 × 4 + RY200KUY1 71 × 3 + RY200KUY1 100 × 2 + RY200KUY1
3D029856A
60 × 4 + RY250KUY1 125 × 2 + RY250KUY1
3D029853A
130
SkyAir LU Series – Heat Pump –
ED21-302
8.2
Capacity Tables
Capacity Correction Factor by The Length of Refrigerant Piping
Cooling (Heating) capacity correction factor
The cooling and Heating capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit) Reference Valve 100 71~250 95
90 200 100, 250 71 125
85
80 140 75
0
5
10
20 25 30 35 15 Length of refrigerant piping (Total length)
40
45
50 (m) C : 3D006500B
Notes:
1.
line: Correction factor for cooling capacity line: Correction factor for heating capacity 2. The correction factor remains the same whether the outdoor unit is to be installed above or below the indoor unit. 3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the range of its limitation.
SkyAir LU Series â&#x20AC;&#x201C; Heat Pump â&#x20AC;&#x201C;
131
2
Operation Limits
ED21-302
9. Operation Limits 9.1
Operation Limits
RY71LUV1 / RY71LUY1 RY100LUV1 / RY100LUY1 RY125LUY1 RY140LUY1
3D039656
RY200KUY1 RY250KUY1
C : 3D029783
132
SkyAir LU Series – Heat Pump –
ED21-302
Sound Level
10. Sound Level 10.1
Overall Sound Level dB(A) Model
50Hz
Measuring Location
220V
240V
2
H
L
H
L
FHYC35K FHYC50K FHYC60K FHYC71K FHYC100K FHYC125K
33 33 35 35 39 42
29 29 30 30 34 36
35 35 37 37 41 44
31 31 32 32 36 38
FHYC
FHY35B FHY50B FHY60B FHY71B FHY100B FHY125B
38 39 40 40 42 44
33 34 35 35 37 39
38 39 40 40 42 44
33 34 35 35 37 39
FHY
RY71LU RY100LU
48 49
49 52
49 50
50 53
RY71~140LU
380V
Microphone
415V
Cooling Heating Cooling Heating RY71LU RY100LU RY125LU RY140LU RY200KU RY250KU
48 49 49 54 60 61
4D028280A
49 52 52 56 62 63
49 50 50 55 61 62
50 53 53 57 63 64
Microphone
4D039806
RY200KU/RY250KU
4D027632
Note:
Operation sound is measured in an anechoic chamber.
SkyAir LU Series – Heat Pump –
133
Sound Level
10.2
ED21-302
Octave Band Level
10.2.1 Indoor Units FHYC35KVE FHYC50KVE
FHYC60KVE FHYC71KVE
FHYC100KVE
FHYC125KVE
FHY35BVE
FHY50BVE
4D028280A
FHY60BVE
FHY71BVE
4D028282
4D028281A
FHY100BVE
4D028355
4D028283
FHY125BVE
4D028284
134
SkyAir LU Series – Heat Pump –
ED21-302
Sound Level
10.2.2 Outdoor Units RY71LUV1 / RY71LUY1 (Cooling)
RY71LUV1 / RY71LUY1 (Heating)
RY100LUV1 / RY100LUY1 (Cooling)
2
4D039802
RY100LUV1 / RY100LUY1 (Heating)
4D039803
RY125LUY1 (Cooling)
4D039805
RY140LUY1 (Cooling)
RY125LUY1 (Heating)
4D039806
RY140LUY1 (Heating)
4D039808
RY200KUY1 (Heating)
Notes:
SkyAir LU Series – Heat Pump –
4D039804
4D039807
RY200KUY1 (Cooling)
4D039809
RY250KUY1 (Cooling)
RY250KUY1 (Heating)
V1 : 220V, Y1 : 380V V1 : 240V, Y1 : 415V
135
Electric Characteristics
ED21-302
11. Electric Characteristics 11.1
RY71~140 Unit Combination
Indoor
Outdoor
Power Supply
Compressor
OFM
IFM
Hz - Volts
Voltage Range
MCA
TOCA
MFA
LRA
RLA
kW
FLA
kW
FLA
FHYC35KVE×2
RY71LUV1
50 - 220 50 - 230 50 - 240
Max.50Hz 264V Min.50Hz 198V
19.2
23.8
30
82 78 75
13.9 13.3 12.8
0.065
0.6
0.045 ×2
0.6 ×2
FHY35BVE×2
RY71LUV1
50 - 220 50 - 230 50 - 240
19.2
23.8
30
82 78 75
13.9 13.3 12.8
0.065
0.6
0.062 ×2
0.6 ×2
FHYC35KVE×2
RY71LUY1
50 - 380/220 50 - 400/230 50 - 415/240
8.2
9.3
15
40 38 37
5.1 4.8 4.6
0.065
0.6
0.045 ×2
0.6 ×2
FHY35BVE×2
RY71LUY1
50 - 380/220 50 - 400/230 50 - 415/240
Max.50Hz 456/264V Min.50Hz 342/198V
8.2
9.3
15
40 38 37
5.1 4.8 4.6
0.065
0.6
0.062 ×2
0.6 ×2
FHYC50KVE×2
RY100LUV1
50 - 220 50 - 230 50 - 240
Max.50Hz 264V Min.50Hz 198V
24.4
28.0
40
114 109 105
17.9 17.2 16.5
0.09
0.8
0.045 ×2
0.6 ×2
FHY50BVE×2
RY100LUV1
50 - 220 50 - 230 50 - 240
24.4
28.0
40
114 109 105
17.9 17.2 16.5
0.09
0.8
0.062 ×2
0.6 ×2
FHYC50KVE×2
RY100LUY1
50 - 380/220 50 - 400/230 50 - 415/240
10.3
12.0
15
50 48 46
6.6 6.3 6.1
0.09
0.8
0.045 ×2
0.6 ×2
FHY50BVE×2
RY100LUY1
50 - 380/220 50 - 400/230 50 - 415/240
Max.50Hz 456/264V Min.50Hz 342/198V
10.3
12.0
15
50 48 46
6.6 6.3 6.1
0.09
0.8
0.062 ×2
0.6 ×2
FHYC60KVE×2
RY125LUY1
50 - 380/220 50 - 400/230 50 - 415/240
12.6
15.5
20
51 53 56
8.0 8.0 8.1
0.065 + 0.085
0.6 + 0.7
0.045 ×2
0.6 ×2
FHY60BVE×2
RY125LUY1
50 - 380/220 50 - 400/230 50 - 415/240
Max.50Hz 456/264V Min.50Hz 342/198V
12.6
15.5
20
51 53 56
8.0 8.0 8.1
0.065 + 0.085
0.6 + 0.7
0.062 ×2
0.6 ×2
FHYC50KVE×3
RY140LUY1
13.8
18.2
25
67 71 74
8.1 8.2 8.5
0.065 + 0.090
0.6 + 0.8
0.045 ×3
0.6 ×3
FHYC71KVE×2
RY140LUY1
50 - 380/220 Max.50Hz 50 - 400/230 456/264V 50 - 415/240 Min.50Hz 342/198V 50 - 380/220 50 - 400/230 50 - 415/240
13.2
17.6
25
67 71 74
8.1 8.2 8.5
0.065 + 0.090
0.6 + 0.8
0.045 ×2
0.6 ×2
FHY50BVE×3
RY140LUY1
50 - 380/220 50 - 400/230 50 - 415/240
13.8
18.2
25
67 71 74
8.1 8.2 8.5
0.065 + 0.090
0.6 + 0.8
0.062 ×3
0.6 ×3
FHY71BVE×2
RY140LUY1
50 - 380/220 50 - 400/230 50 - 415/240
13.2
17.6
25
67 71 74
8.1 8.2 8.5
0.065 + 0.090
0.6 + 0.8
0.062 ×2
0.6 ×2 3D039580
136
SkyAir LU Series – Heat Pump –
ED21-302
11.2
Electric Characteristics
RY200 RY250 Unit Combination
Indoor
Power Supply
Outdoor
Compressor
OFM
IFM
Hz - Volts
Voltage Range
MCA
TOCA
MFA
LRA
RLA
kW
FLA
kW
FLA
FHYC100KVE×2 RY200KUY1
50 - 380/220 50 - 400/230 50 - 415/240
20.8
22.5
30
87 92 95
12.6 12.4 13.0
0.23 + 0.19
1.3 + 1.2
0.090 ×2
1.0 ×2
FHY100BVE×2
RY200KUY1
50 - 380/220 50 - 400/230 50 - 415/240
Max.50Hz 456/264V Min.50Hz 342/198V
20.2
21.9
30
87 92 95
12.6 12.4 13.0
0.23 + 0.19
1.3 + 1.2
0.130 ×2
0.7 ×2
FHYC71KVE×3
RY200KUY1
50 - 380/220 50 - 400/230 50 - 415/240
20.6
22.3
30
87 92 95
12.6 12.4 13.0
0.23 + 0.19
1.3 + 1.2
0.045 ×3
0.6 ×3
FHY71BVE×3
RY200KUY1
50 - 380/220 50 - 400/230 50 - 415/240
20.6
22.3
30
87 92 95
12.6 12.4 13.0
0.23 + 0.19
1.3 + 1.2
0.062 ×3
0.6 ×3
FHYC50KVE×4
RY200KUY1
50 - 380/220 50 - 400/230 50 - 415/240
21.2
22.9
30
87 92 95
12.6 12.4 13.0
0.23 + 0.19
1.3 + 1.2
0.045 ×4
0.6 ×4
FHY50BVE×4
RY200KUY1
50 - 380/220 50 - 400/230 50 - 415/240
21.2
22.9
30
87 92 95
12.6 12.4 13.0
0.23 + 0.19
1.3 + 1.2
0.062 ×4
0.6 ×4 3D029820A
Unit Combination Indoor
Power Supply
Outdoor
Compressor
OFM
IFM
Hz - Volts
Voltage Range
MCA
TOCA
MFA
LRA
RLA
kW
FLA
kW
FLA
FHYC125KVE×2 RY250KUY1
50 - 380/220 50 - 400/230 50 - 415/240
26.0
28.5
40
128 135 140
16.3 15.7 17.2
0.23 + 0.19
1.3 + 1.2
0.090 ×2
1.0 ×2
FHY125BVE×2
RY250KUY1
50 - 380/220 50 - 400/230 50 - 415/240
Max.50Hz 456/264V Min.50Hz 342/198V
25.4
27.9
40
128 135 140
16.3 15.7 17.2
0.23 + 0.19
1.3 + 1.2
0.130 ×2
0.7 ×2
FHYC60KVE×4
RY250KUY1
50 - 380/220 50 - 400/230 50 - 415/240
26.4
28.9
40
128 135 140
16.3 15.7 17.2
0.23 + 0.19
1.3 + 1.2
0.045 ×4
0.6 ×4
FHY60BVE×4
RY2500KUY1
50 - 380/220 50 - 400/230 50 - 415/240
26.8
29.3
40
128 135 140
16.3 15.7 17.2
0.23 + 0.19
1.3 + 1.2
0.062 ×4
0.7 ×4 3D029821A
Symbols: MCA : Min. Circuit Amps TOCA : Total Over-current Amps MFA : Max. Fuse Amps (See note 7) LRA : Locked Rotor Amps RLA : Rated Load Amps OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps kW : Fan Motor Rated Output Notes: 1. RLA is based on the following conditions: Indoor temp. 27°CDB/19.0°CWB Outdoor temp. 35°CDB 2. TOCA means the total value of each OC set. 3. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. 4. Maximum allowable voltage unbalance between phases is 2%. 5. MCA/MFA MCA=1.25×RLA+ea.FLA MFA≤2.25×RLA+ea.FLA (Next lower standard fuse rating) 6. Select wire size base on the larger value of MCA or TOCA. 7. Instead of fuse, use circuit breaker.
SkyAir LU Series – Heat Pump –
137
2
Option List
ED21-302
12. Option List 12.1
LU Series
12.1.1 Indoor Unit FHYC-K Name of Option
Kit Name
Remark
35~71K
100~125K
Decoration Panel
BYC125K-W1
Sealing Member of Air Discharge Outlet
KDBHJ55K160
Panel Spacer
KDBJ55K160W
Fresh Air Intake Kit ∗4 Chamber Type Without T Joint
KDDP55D160
With T Joint
KDDP55D160K
Direct Installation Type High Efficiency Filter Replacement High Efficiency Filter
KDDJ55X160
(Colorimetric Method 65%)
KAFP556D80
KAFP556D160
(Colorimetric Method 90%)
KAFP557D80
KAFP557D160
(Colorimetric Method 65%)
KAFJ552K80
KAFJ552K160
(Colorimetric Method 90%)
KAFJ553K80
KAFJ553K160
High-Efficiency Filter Chamber
KDDFP55D160
Long-Life Filter
KAFJ551K160
Resin Net (Gravimetric Method 50%)
Ultra-Long Life Filter
KAFP55D160
Ultra-Long Life Replacement Filter
KAFJ55K160H
Chamber Connection Kit ∗5
KKSJ55K160
Branch Duct Chamber Remote Controller
KDJ55K80
KDJ55K160
Wired Type ∗3
BRC1C61 (Note. 6)
Wireless Type
BRC7C612W
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring (Interlock for Fresh Air Intake Fan) ∗1
KRP1B57
Wiring Adaptor for Electrical Appendices ∗1
KRP4A53
Interface Adaptor for SkyAir Series
DTA102A52
Installation Box for Adaptor PCB
KRP1B98 C:3D006559E
FHY-B Name of Option
Remark
Kit Name 35B
50B
60B
71B
100B
125B
Replacement Long-Life Filter
KAFJ501D56
KAFJ501D80
KAFJ501D112 KAFJ501D160
Drain Pump Kit
KDU50B50VE
KDU50B71VE
KDU50B125VE
L-Type Piping Kit (For Upward Direction) KHFJ5F50 Remote Controller
KHFJ5F60
KHFJ5F80
Wired Type ∗3
BRC1C61
Wireless Type
BRC7E63W
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring
KRP1B54
Wiring Adaptor for Electrical Appendices ∗2
KRP4A52
Interface Adaptor for SkyAir Series
DTA102A52
Installation Box for Adaptor PCB
KHFJ5F160
KRP1C93 3D028285A
Note:
138
1. 2. 3. 4. 5. 6.
∗1 : Installation box for adaptor PCB (KRP1B98) is necessary. ∗2 : Installation box for adaptor PCB (KRP1C93) is necessary. ∗3 : Wire for remote controller : Field supplied. ∗4 : Refer to the Option handbook in detail. ∗5 : When using the filter (High-Efficiency Filter of Ultra-Long Life Filter) and the Fresh Air Intake Kit together, this kit is necessary.
BRC1B61 is also available.
SkyAir LU Series – Heat Pump –
ED21-302
Option List
12.1.2 Outdoor Unit (RY71 ~ 140LU, RY200 · 250KU) Name of Option
Remark
Kit Name RY71LU
RY100LU
Central Drain Plug
RY140LU
RY200KU
KKPJ5F180 For Twin Multi
Refrigerant branch piping Kit
RY125LU
For Triple Multi For DoubleTwin Type
KHR58C21
KHD58C21A —
KHD58D33 —
RY250KU —
KHD58C23A
KHD58C24A
KHD58D31
—
KHRJ5F224F KHRJ5F280F 3D039655 4D029784
SkyAir LU Series – Heat Pump –
139
2
Field Piping and Wiring
ED21-302
13. Field Piping and Wiring 13.1
Field Piping
13.1.1 Maximum Allowable Piping Length and Difference RY71~140LU Maximum Allowable Pipe Length [Parenthesized Figure Represents Equivalent Length]
Maximum Allowable Level Difference
50 m (70 m) The total one-way pipe length should be within 60 meters.
30 m The level difference between the indoor units should be 0.5 m.
When connected to two indoor units (simultaneous operation system)
When connected to three indoor units (simultaneous operation system)
Branched pipe (L2)
Branched pipe (L2)
Branched pipe (L3)
Branched pipe (L3) Main pipe (L1) One-way length of pipe (L): L1+L2+L3
Main pipe (L1)
Branched pipe (L4)
One-way length of pipe (L): L1+L2+L3+L4 1PN05248B-1
Allowable Pipe Length The maximum allowable pipe length here means the total length of the main pipe and the branched pipe (the longer one of the two branched pipes). (Refer to the figure above.) RY200, 250KU
1PN04787B-1
140
SkyAir LU Series – Heat Pump –
ED21-302
Field Piping and Wiring
2 1PN04787B-2
13.1.2 Additional Refrigerant Charge RY71~140LU This unit requires additional charging of refrigerant according to the length of pipe connected at the site. When the entire refrigerant pipe length is within 30 meters, the additional changing is not needed. Take the following steps for proper charging. When connected to two indoor units (simultaneous operation system)
When connected to three indoor units (simultaneous operation system)
Branched pipe (L2)
Branched pipe (L2)
Branched pipe (L3)
Branched pipe (L3) Main pipe (L1)
Main pipe (L1)
One-way length of pipe (L): L1+L2+L3
Branched pipe (L4)
One-way length of pipe (L): L1+L2+L3+L4
1. Refrigerant charge amount Additional charging of refrigerant Select the amount of refrigerant which matches a length which exceeds the charge-less length, and add it. Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear surface of the front plate, as this is necessary for after-sales service.
FOR SIMULTANEOUS OPERATION SYSTEM Find the entire pipe length by totaling that of each pipe in the order of the main pipe (L1), and branched pipes (L2), (L3), (L4), calculate the excess length going over 30 meters, then select from Table 1 the amount of refrigerant corresponding to the excess length. The total vaule is tha amount required for additional charging. The maximum allowable pipe length is 50 meters. Make the total refrigerant pipe length come within 60 meters. The maximum allowable pipe length here means the total length of the main pipe and the branched pipe (the longer one of the two branched pipes). <unit : kg> Table 1 Pipe excess length over 30 meters Main pipe Additional charging amount
Liquid pipe Branched pipe
10 m or less
20 m or less
0.50
1.00
φ9.5
71 type 100·125·140 type
0.75
1.50
φ9.5
71 type
0.50
1.00
100·125·140 type
0.75
1.50
φ6.4
71 type
0.30
0.60
140 type
0.45
0.90
2. Recharging refrigerant When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the amount mentioned on the nameplate, and when the pipe length exceeds 30 meters, the charging amount is an addition of the amount stated on the nameplate and the additional charging amout. 1PN05248B-2
SkyAir LU Series – Heat Pump –
141
Field Piping and Wiring
ED21-302
RY200, 250KU
1PN04788A
Caution to be taken when brazing refrigerant piping “Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”. (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible. (Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g . BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant leakage.
142
SkyAir LU Series – Heat Pump –
ED21-302
13.2
Field Piping and Wiring
Field Wiring
13.2.1 RY71LU, 100LU, 125LU, 140LU (V1, Y1)
2
V1(A) MODEL
C : DU423-5177C-2
SkyAir LU Series – Heat Pump –
143
Field Piping and Wiring
ED21-302
13.2.2 RY200KU, RY250KU (Y1)
C : 3D029782
144
SkyAir LU Series – Heat Pump –
ED21-302
Detail Information of Options SkyAir LU Series
Note : Refer to VRV Option Handbook (OH02-1) Concerning about the manual for the following Central Control Kits. • Interface Adaptor for Skyair Series DTA102A52 • Central Remote Controller DCS302B61 • Unified ON/OFF Controller DCS301B61 • Schedule Timer DST301B61
SkyAir LU Series
145
3
Remote Controller
ED21-302
1. Remote Controller 1.1
Remote Controller, Timer, Adaptor List Name of Option
Model Series FH(Y)C-K
Remote Wireless C/O BRC7C613W Controller H/P BRC7C612W Wired
FH(Y)K-F(J)
FH(Y)B-F
FUY-FJ
FH(Y)-B
FAY71L
FAY100FA
FV(Y)-LA
—
—
BRC7C529W
BRC7E66
BRC7E619
BRC7C611W
—
—
—
BRC7C528W
BRC7E63W
BRC7E618
BRC7C610W
C/O BRC1C61
H/P
— BRC1C61 (Available for 2 remote control use)
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring
KRP1B57
KRP1B51
KRP1B54
—
KRP1B54
—
—
KRP1B57
Wiring Adaptor for Electrical Appendicies
KRP4A53∗
KRP4A51
KRP4A51
KRP4A53∗
KRP4A52∗
KRP4A51∗
KRP4A51
KRP4A52∗
Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB
DTA102A52 KRP1B98
—
—
— KRP1B97
KRP1C93
KRP4A93
DTA102A52 —
KRP4A95
∗ Installation Box for Adaptor PCB is necessary.
1.2
Wired Remote Controller
BRC1C61 New BRC1C61 {
BRC1B61 ON / OFF Operation with Air Conditioner Independent operation in intermediate { season Ventilation mode change over (Auto / { HRV / Normal) Air flow change over (Auto / High / Low) { Setting of precooling / preheating Setting of fresh-up operation Filter sign display { { : Initial Setting Only (Field setting by well known service person)
146
SkyAir LU Series
ED21-302
Remote Controller
5 12
4
2
1
3 7
hr
C
6 8
hr
NOT AVAILABLE
TEST
9 11 10 13 21
L H
14
3
20 TEST
16
1 2
3
4
19
15
17
18
ON/OFF BUTTON Press the button and the system will start. Press the button again and the system will stop. OPERATION LAMP (RED) The lamp lights up during operation. DISPLAY “ ” (UNDER CENTRALIZED CONTROL) When this display shows, the system is UNDER CENTRALIZED CONTROL. DISPLAY “ ” “ ”“ ”“ ” (VENTILATION/AIR CLEANING) This display shows that the total heat exchange and the air cleaning unit are in operation (These are optional accessories).
5
DISPLAY “ ” “ ” “ ” “ ” “ ” (OPERATION MODE) This display shows the current OPERATION MODE. For cooling only type, “ ” (Auto) and “ ” (Heating) are not installed.
6
DISPLAY “ TEST” (INSPECTION/TEST OPERATION) When the INSPECTION/TEST OPERATION BUTTON is pressed, the display shows the system mode is in. hr
DISPLAY “
” (PROGRAMMED TIME)
3PA59583-16Z-1
12
DISPLAY “
” (DEFROST)
NON-FUNCTIONING DISPLAY If that particular function is not available, pressing the button may display the words “NOT AVAILABLE” for a few seconds. When running multiple units simultaneously the 13 “NOT AVAILABLE” message will only be appear if none of the indoor units is equipped with the function. If even one unit is equipped with the function, the display will not appear. 14 15
TIMER MODE START/STOP BUTTON TIMER ON/OFF BUTTON
INSPECTION/TEST OPERATION BUTTON 16 This button is used only by qualified service persons for maintenance purposes. PROGRAMMING TIME BUTTON 17 Use this button for programming “START and/or STOP” time. TEMPERATURE SETTING BUTTON 18 Use this button for SETTING TEMPERATURE. FILTER SIGN RESET BUTTON 19
hr
7
This display shows the PROGRAMMED TIME of the system start or stop. 8
DISPLAY “ ” (SET TEMPERATURE) This display shows the set temperature.
9
DISPLAY “ ” (FAN SPEED) This display shows the set fan speed.
C
DISPLAY “
FAN SPEED CONTROL BUTTON 20 Press this button to select the fan speed, HIGH or LOW, of your choice. OPERATION MODE SELECTOR BUTTON 21 Press this button to select OPERATION MODE. AIR FLOW DIRECTION ADJUST BUTTON 22
” (AIR FLOW FLAP)
10 11
22
NOTE DISPLAY “
”(TIME TO CLEAN AIR FILTER)
• For the sake of explanation, all indications are shown on the display in the above figure contrary to actual running situations. 3PA59583-16Z-2
SkyAir LU Series
147
Remote Controller
ED21-302
Installation
148
SkyAir LU Series
ED21-302
Remote Controller
3
SkyAir LU Series
149
Remote Controller
Mode No. Note) 1
FIRST CODE NO.
0
10(20)
11(21)
13(23)
ED21-302
SECOND CODE No. Note) 2 Description of Setting Filter Contamination - Heavy/Light (Setting for spacing time of display time to clean air filter) (Setting for when filter contamination is heavy, and spacing time to clean air filter is to be halved)
01
02
03
Approx. Heavy 10,000 hours
Approx. 5,000 hours
—
Long-life type
Approx. 2,500 hours
Approx. 1,250 hours
—
Standard type
Approx. 200 hours
Approx. 100 hours
—
Ultra-longlife type
Light
Long-life filter type (Setting of filter sign indication time) (Change setting when Ultra-long-life filter is installed)
Long-life filter
Ultra-long-life filter (1)
—
1
Spacing Time of Display Time to Clean Air Filter Count (Setting for when the filter sign is not to be displayed)
Display
Do Not Display
—
3
Setting Number of Connected Skyair Simultaneous Operation System Indoor Units (Setting for Simultaneous Operation System)
Pair
Twin
—
0
High Ceiling Setting (Setting for when installed in a Ceiling higher than 2.7m)
Normal
High Ceiling 1
High Ceiling 2
0 1
Selection of Air Flow Direction (Setting for when a blocking pad kit has been installed)
F
T
W
Air Flow Direction Adjust Function (To be set when decoration panel for air outlet is installed)
Equipped
No Equipped
—
3 4
Air Flow Direction Range Setting
Upper
Normal
Lower
Setting the External Static Pressure (Setting according to the connected duct resistance) (For FHYK, follow the High Ceiling Setting)
Normal
High Static Pressure
Low Static Pressure
6
(Normal)
(High Ceiling)
—
Note:
1. Setting is carried out in the group mode, however, set the mode number inside the ( ) for individual setting of the each indoor unit or confirmation after setting. 2. The SECOND CODE number is set to “01” when shipped from the factory. However for the following cases it is set to “02” • Air flow direction range setting. 3. Do not make any settings not given in the table above. 4. Not displayed if the indoor unit is not equipped with that function. 5. When returning to the normal mode, “88” may be displayed in the LCD in order for the remote controller to initialize itself. 2P068938-2
150
SkyAir LU Series
ED21-302
1.3
Remote Controller
Wireless Remote Controller
Names and Function Name of Option
Model Series FH(Y)C-K
FH(Y)K-F(J)
FH(Y)B-F
FUY-FJ
FH(Y)-B
FAY71L
FAY100FA
FV(Y)-L(A)
—
—
BRC7C529W
BRC7E66
BRC7E619
BRC7C611W
—
—
—
BRC7C528W
BRC7E63W
BRC7E618
BRC7C610W
—
Remote Wireless C/O BRC7C613W Controller H/P BRC7C612W
1-1 1 ON OFF
3
1-2 H
M L
DOWN
10
C
ON OFF
UP
6
TEMP
FAN
H
M L TIME
4
11
C
hr.
2
3
8
UP
9
hr.
FAN
DOWN
13
RESERVE CANCEL
hr.
5
TIMER
12
MODE
15
hr.
TEST
7 14
SWING
16
TEST TEST
17
3PA63363-21T-1
Explanation of Receiver FH(Y)C-K
FAY71L
FAY-FA
20
21
19
18
23
22
3P091240-1
FUY-FJ
FH(Y)-B
22
19
21 20
23
18
3PA63363-21T-2
SkyAir LU Series
151
Remote Controller
ED21-302
DISPLAY “ ” (SIGNAL TRANSMISSION) 1 This lights up when a signal is being transmitted. DISPLAY “ ” “ ” “ ”“ “ ” (OPERATION MODE)
3
4
H
M L
C
” (SET TEMPERATURE)
6
7
8
9
10
11
12
AIR FLOW DIRECTION ADJUST 14 BUTTON
15
16
This display shows the set temperature. hr. DISPLAY “ hr. ” (PROGRAMMED TIME)
This display shows PROGRAMMED TIME of the system start or stop. 5
DISPLAY “
TIMER RESERVE/CANCEL BUTTON
”
2 This display shows the current OPERATION MODE. For straight cooling type, “ ” (Auto) and “ ” (Heating) are not installed. DISPLAY “
13
17
18
” (AIR FLOW FLAP)
DISPLAY “ ”“ ” (FAN SPEED) The display shows the set fan speed. TEST ” DISPLAY “ (INSPECTION/ TEST OPERATION) When the INSPECTION/TEST OPERATION BUTTON is pressed, the display shows the system mode is in. ON/OFF BUTTON Press the button and the system will start. Press the button again and the system will stop. FAN SPEED CONTROL BUTTON Press this button to select the fan speed, HIGH or LOW, of your choice. TEMPERATURE SETTING BUTTON Use this button for SETTING TEMPERATURE. (Operates with the front cover of the remote controller closed.) PROGRAMMING TIMER BUTTON Use this button for programming “START and/or STOP” time. (Operates with the front cover of the remote controller opened.) TIMER MODE START/STOP BUTTON
19
20
21
22
23
OPERATION MODE SELECTOR BUTTON Press this button to select OPERATION MODE. FILTER SIGN RESET BUTTON Refer to the section of MAINTENANCE in the operation manual attached to the indoor unit. INSPECTION/TEST OPERATION BUTTON This button is used only by qualified service persons for maintenance purposes. EMERGENCY OPERATION SWITCH This switch is readily used if the remote controller does not work. RECEIVER This receives the signals from the remote controller. OPERATING INDICATOR LAMP (Red) This lamp stays lit while the air conditioner runs. It flashes when the unit is in trouble. TIMER INDICATOR LAMP (Green) This lamp stays lit while the timer is set . AIR FILTER CLEANING TIME INDICATOR LAMP (Red) Lights up when it is time to clean the air filter. DEFROST LAMP (Orange) Lights up when the defrosting operation has started. (For straight cooling type this lamp does not turn on.)
3PA63363-21T-3
152
SkyAir LU Series
SkyAir LU Series
Control by Remote Controller.
For the control of plural indoor units on a floor at the same time
For above control from distant place.
Operation of other equipment combined with the operation of indoor unit
Group control
Group control by 2 remote controllers
Combining control by remote controller
Note 1
BRC1C61
Unit Name and Model Outline of System
Operates HRV in accordance with indoor unit operation.
Operational functions Start/Stop (ON/OFF) Temperature setting Timer setting (Settings in units of 1 hour up to a maximum of 72 hours) Air flow setting Air flow direction adjustment (Swing flap) Indication function Operating display Program dry function display Defrost/Hot start display Filter sign Temperature setting display Timer display Air flow display Abnormal operation display ∗ In case of group control all the indoor units in the system are set to the same value and each unit is controlled individually by its internal thermostat. (Not by the thermostat equipped in remote controller) ∗ In command by double remote controls, the most recent one takes priority. (Selection between master and slave controller is essential) ∗ According to indoor unit’s model, some models cannot be set.
Function
Same as the number of units controlled by remote controller
2 remote controllers control up to 16 indoor units from 2 different places simultaneously
1 remote controller controls up to 16 indoor units simultaneously
2 remote controllers control 1 indoor unit
1 remote controller controls 1 indoor unit
Standard Number of Units
(S1015)
Note: 1. These figures above show the system using wired remote controllers. Wireless remote controller replaced for wired remote controller can be used for same control. 2. In control by two remote controllers, one of two remote controllers must be a wired remote controller. Two wireless remote controllers must not be used. 3. Wiring from a wireless remote controller to the receiver can be lengthened to 200m in maximum.
For control from 2 places (distant or local)
For control from distant place
Remote operation of remote controller
2 remote control Note 2
Example of typical use
Objective / Use
1.4
Local operation of remote controller
Control Method
ED21-302 Remote Controller
Various Control by Liquid Crystal Remote Controller For more effective localized environmental control Daikin offers various control systems such as single or double remote control or centralized control. This enables the construction of a variety of operational control systems which can be adapted for various uses from remote control.
3
153
Set-back Time Clock
Desired Weekly Scheduled Operation of ON/ OFF and Temperature's Set-back
BRC15A61
154 Set-back time clock
Set-back time clock
Remote controller
Remote controller
∗ Be sure to provide a master remote controller. This scheduled operation cannot be used in both cases at control by two remote controllers and at the connection of a group remote control adapter.
Display function Effective/ineffective control on the program The present time and the week day Daylight-saving time setting Setting holidays in a week Display of operation mode(heating/cooling) Usual setting temperature (Cooling/Heating is linked to a remote controller) ON/OFF time setting for a day Set-back time setting for a day
Control function Effective/ineffective control on the program Daylight-saving time The present time adjustment Weekly operation time program (two times a day in max. frequency by a unit of 30 min.) Weekly set-back operation time program (two times a day in max. frequency by a unit of 30 min.) Program of setting temperature for normal/set-back control (each one kind for cooling and heating . The operation mode is linked to the remotecontroller). Elimination of the time in an operation of a day and a setback operation.
Max. 16 groups under simultaneous control by one set-back time clock
One indoor unit control by one set-back time clock
(S1018)
Remote Controller ED21-302
SkyAir LU Series
Scheduled Control
SkyAir LU Series
Adaptor for connection with optional controllers for centralized control
Schedule timer Central remote controller Unified ON/ OFF controller
Unified ON/OFF controller
Central remote controller
Schedule timer
For controlling all indoor units from one place
For carrying out weekly schedule operation by 1-minute units
Interface adaptor for SkyAir series DTA102A52
DCS301B61
DCS302B61
DST301B61
DCS301B61
DCS302B61
DST301B61
Controls up to 64 groups of indoor units with one central remote controller.
Controls up to 16 groups of indoor units with one unified ON/ OFF controller.
Controls up to128 groups (Max. 128 indoor units) with one schedule timer, two central remote controller and eight unified ON/OFF controllers.
Double central control function Function of liquid crystal remote controller can be controlled individually for each zone of the indoor unit. Individual/unified operation Up to 8 patterns can be set for operation controlled by programmed time when used in combination with schedule timer. Temperature setting for each zone Control operation for each room during centralized control Remote controller operation rejected command Sequential start function Double central control function Indoor unit ON/OFF control Individual/unified operation Remote controller operation rejected command (Central remote controller given priority when used in combination with central remote controller.) Sequential start function
Respective functions of schedule timer, central remote controller and unified ON/OFF controller are possible. (Control mode of central remote controller is given priority for operation of remote controller for indoor unit.)
Unification adaptor for computerized control allows you to simultaneously turn indoor units connected to the central remote controller on or off or display at the central monitor panel, etc. Interface adaptor for SkyAir series is for connection of optional controllers for centralized control.
Simultaneously controls 128 groups with one schedule timer.
ON/OFF time can be set by units of day, hour and minute; ON/OFF pattern can be set by time zone of twice per day in accordance with application.
(S1016)
ED21-302 Remote Controller
3
155
Central Control
For control by operation command from building control room
Wiring adaptor for electrical appendices
Adaptor for wiring
When controlling operation with optional accessories added inside indoor units, the status is displayed outside.
Objective / Use
Remote Control
Wiring Modification
156
Control Method
Built into indoor unit KRP1B51·54· 57
KRP4A51·52· 53·54 Built into indoor unit
With remote temperature setting
Unit Name and Model
Group Unified Control (Controls group controlled indoor units all at once and simultaneously.)
Individual Control (Controls Indoor Units Individually.)
Outline of System
Operation display signal and compressor operation signal are supplied.
For group unified control, the setting becomes the same for all connected indoor units, and each indoor unit is controlled individually by built-in thermostat.
1 adaptor controls the electric heater.
1 PC board simultaneously controls 16 group of indoor units.
1 PC board controls 1 indoor unit.
Normally open or momentary open type contactor DC12~24V or no-voltage Various control methods available by mode select switch Voltage, no-voltage selector switch Alarm and operation display signal (no-voltage) Selector switch of zone/individual of alarm display Remote temperature setting (resistance input of 0~135Ω) Selector switch for remote controller temperature setting enable/inhibit ∗
Standard Number of Units
Function
(S1017)
Remote Controller ED21-302
SkyAir LU Series
ED21-302
1.5
Remote Controller
BRC15A61 â&#x20AC;&#x201C; Set Back Time Clock
Installation
Â&#x201E; Connected to a wired remote controller, this timer can set 2 sets of ON/OFF times in an increment of 30 minutes within a day. For each ON/OFF setting a temperature setting is also possible.
3
SkyAir LU Series
157
Remote Controller
ED21-302
SPECIFICATIONS Display of time
12-hour digital display
Clock cycle type
Quartz clock type
Clock accuracy
Within ± 30 sec./month (environmental temperature from 15°C to 35°C)
Timer programming
Two pairs of programmed time for both system start and system off can be set in units of 30 minutes.
Power failure compensation time
Approximately 1 hour for a single occurrence of power failure (clock with No. of programmed time)
Size
120(W)×120(H)×17(D) mm (Width/Height/Depth)
OUTLINE DRAWINGS
120
MON TUE WED THU FRI SAT SUN
PROGRAM OFF OFF OFF OFF OFF OFF OFF
SUMMER TIME
AM PM
MON TUE WED THU FRI SAT SUN CLOCK
0 2 4 6 8 10 12 14 16 18 20 22 24
ON/OFF
˚C ˚C 0 2 4 6 8 10 12 14 16 18 20 22 24
PROGRAM
ON/OFF SET BACK
OK
DAY OF THE WEEK
CLOCK
DAY OFF
SUMMER TIME
120
SET BACK
CLEAR
Specifications and appearance subject to change without notice. About the remote controller which can connect set back time clock (BRC15A61) Wired Remote Controller
Set Back Time Clock
Indoor Unit
Although Set Back Time Clock is connected with Wired Remote Controller in parallel with Series Method, it does not applied to remote control of those other than the following. Model
Remarks
BRC1A51 BRC1A52 BRC1A61 BRC1A62 BRC8A61 ARC11A52 ARC11A54
Only EC9721 the printed Circuit Board currently used for these remote control. (Refer to Note 1)
BRC1B51 BRC1B52 BRC1B61 BRC1B62
Applied for all printed circuit boards.
BRC1C61 BRC1C51
Applied for all printed circuit boards.
Note 1) The check method of printed circuit boards' model No. The rear face of the remote control after removing a back cover Printed Circuit Board
EC9721
158
Printed circuit boards' model No. is indicated at the lower left of the PC board which can be looked at when the back cover of remote controller is removed.
Printed Circuit Boards' The product start of EC9721 was carried out after Model No. 1997.
SkyAir LU Series
ED21-302
Remote Controller
Names and Functions
Fig. 1 12
5
Fig. 2 4
2
1
15
20
PROGRAM
17
DAY OF THE WEEK
CLOCK
DAY OFF
SUMMER TIME
13
14 PROGRAM
6
MON TUE WED THU FRI SAT SUN
SUMMER TIME AM MON TUE WED THU FRI SAT SUN CLOCK PM 0 2 4 6 8 10 12 14 16 18 20 22 24 ON/OFF OFF OFF OFF OFF OFF OFF OFF
7
3 10 11
˚C
SET BACK
8
˚C 0 2 4 6 8 10 12 14 16 18 20 22 24
ON/OFF SET BACK
OK
21
19 CLEAR
3
23
9 PROGRAM
ON/OFF SET BACK
OK
DAY OF THE WEEK
CLOCK
DAY OFF
SUMMER TIME
16
22
18
CLEAR
NAMES AND FUNCTIONS OF OPERATING SECTION (Fig.1,2) ON/OFF BUTTON
1
DISPLAY “
Press this button to make the program start/stop and the set back time schedule active. Press the button again to make them inactive.
11
The lamp turns on when the schedule function becomes active.
DISPLAY “
MON TUE WED THU FRI SAT SUN AM PM
CLOCK
3
12
13
4
SUMMER TIME
PROGRAMMING START BUTTON
” (SUMMER
14
This display shows the clock indicates summer time.
5
DISPLAY “ PROGRAM ” (PROGRAMMING START)
6
OFF
” (DAY OFF SETTING)
Lights above the day of the week set as day off. The operation controlled by timer is not available on that day.
8
17 18
This display shows the set temperature at normal operation time.
19
DISPLAY “ SET BACK ˚C ” (SET TEMPERATURE SET BACK OPERATION TIME)
20
SUMMER TIME SET BUTTON
10
This display shows the programmed normal operation time.
SkyAir LU Series
Press this button to change clock to summer time. Press it again to return to standard time.
TEMPERATURE SET BUTTON
ON/OFF OR SET BACK MODE SELECT BUTTON
21
This display shows the current SELECT MODE (Cool/Heat) when setting temperature.
DISPLAY “ (OPERATION TIME SCHEDULE)
DAYS OFF SET BUTTON
Press this button to adjust the temperature.
” (SELECT MODE)
0 2 4 6 8 10 12 14 16 18 20 22 24
DAYS OF A WEEK SELECT BUTTON
Press this button to set days off.
This display shows the set temperature at set back operation time.
9
Press this button to finish setting the present time and the programmed time.
Press this button to select the day of the week.
DISPLAY “ ˚C ” (SET TEMPERATURE NORMAL OPERATION TIME)
DISPLAY “
Press this button to adjust the present time and the programmed time.
SETTING FINISH BUTTON
16
ON/OFF
7
Press this button to set the programmed time. Press it again after you are through with the program.
TIME ADJUST BUTTON
15
The light turns on when the timer is programmed.
DISPLAY “
CLOCK ADJUST BUTTON Press this button to set the present time.
Displays the present day of the week and time.
DISPLAY “ TIME)
DISPLAY “ ” (UNDER CENTRALIZED CONTROL) When this display shows, the system is UNDER CENTRALIZED CONTROL.
” (PRESENT
TIME)
”
This display shows the programmed set back operation time.
OPERATION LAMP (RED)
2
0 2 4 6 8 10 12 14 16 18 20 22 24
(SET BACK TIME SCHEDULE)
”
Press this button to select ON/OFF or SET BACK mode when setting the programmed time and temperature.
COOL/HEAT SELECT BUTTON
22
23
Press this button to select COOLING or HEATING when setting temperature at set back.
PROGRAM CLEAR BUTTON Press this button to clear the programmed time.
159
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-302
2. Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C] 2.1
BYC125K – W1 – Decoration Panel
BEFORE INSTALLATION PRECAUTIONS • Refer also to the installation manual attached to the indoor unit. ACCESSORIES • Installation manual. NOTE TO INSTALLER Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.
PREPARATION OF DECORATION PANEL
<<For this unit, you are able to select air flow directions. To discharge air in 2 or 3 directions, it is necessary to purchase optional blocking pad kit.>> HANDLING OF DECORATION PANELS • Never place the panel facing down nor lean it against a wall nor leave it on a projecting object. • Never touch or put pressure on the swing flap. (The swing flap may malfunction.) (1) Remove the suction grille from the decoration panel. 1) Push the suction grille lever inward and lift up the lever side. (Refer to Fig. 1.)
2) Detach the suction grille from the decoration panel by lifting the grille up approximately 45 degrees. (Refer to Fig. 2.)
45˚ Lever
Fig. 1 (2) Remove the service cover on the corner. Slide the service cover outward to remove. (Refer to Fig. 3.)
Fig. 2
Fig. 3
160
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
INSTALLATION OF THE DECORATION PANEL TO THE INDOOR UNIT BODY <<Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.>> (1) Set the decoration panel to the indoor unit body by matching the position of the swing flap motor of the decoration panel to the piping position of the indoor unit as shown in Fig. 4. (2) Install the decoration panel. 1) Temporarily install the decoration panel to the indoor unit by hanging the latch on the opposite side of the swing flap motor of the decoration panel to the hook of the indoor unit body. (2 positions) 2) Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit. (Be careful not to let the swing motor lead wire get caught in the sealing material.) 3) Screw all 4 hexagon head screws located right beneath the latches in approximately 5 mm. (Panel will rise.) 4) Adjust the decoration panel by turning it to the arrowed direction in Fig. 4 so that the ceiling opening is completely covered. 5) Tighten the screws until the thickness of the sealing material between the decoration panel and the indoor unit body reduces to 5â&#x20AC;&#x201C;8 mm. Sealing material Indoor unit
3
Ceiling material 5 ~ 8 mm
Decoration panel
Air outlet
Hook
1)
Latch
2) Piping position
2)
Swing flap motor 3)
4)
Fig. 4 PRECAUTIONS â&#x20AC;˘ Improper screwing of the screws may cause the troubles shown in Fig. 5. Screw properly.
Air leak
Air leak from ceiling
Contamination
Dew formation, dew dripping Fig. 5
SkyAir LU Series
161
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-302
• If gap is still left between the ceiling and the decoration panel after screwing the screws, readjust the indoor unit body height. (Refer to Fig. 6.)
Adjustment of the indoor unit body height from the holes in the corner of the decoration panel is possible if the indoor unit is kept leveled and the drain piping, etc. is unaffected.
No gaps is allowed Fig. 6 (3) Wiring of the decoration panel (Refer to Fig. 7.) 6) Connect the connectors for swing flap motor lead wire installed on the decoration panel. If connectors are not connected, the malfunction display (A7) appears on the remote controller. Connect the connectors properly. Make sure that the swing flap motor lead wire is not caught between the indoor unit and the decoration panel.
6) Indoor unit side
Decoration panel side
áWiring
Fig. 7
Instruction Diagramñ (It differs from the actual state.)
INSTALLATION OF SUCTION GRILLE AND SERVICE COVER (1) Install the suction grille. Install by reversing the procedure shown in “PREPARATION OF DECORATION PANEL”. It is possible to install the suction grille in 4 directions by turning the suction grille. Change the direction when adjusting the direction of the suction grille of multiple units or in meeting customers’ demands. NOTE) Be careful not to get swing flap motor lead wire get caught when installing the suction grille. (2) Install the service cover on the corner. 1) Attach the string of the service cover to the pin of the decoration panel as in Fig. 8.
2) Install the service cover over the decoration panel.
Pin
Install the service cover by sliding 4 latches to fit into the holes on the decoration panel.
Fig. 8
162
SkyAir LU Series
ED21-302
2.2
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
KDBHJ55K160 â&#x20AC;&#x201C; Sealing member of air discharge outlet
Caution zRefer to the installation manual for both indoor unit and the decoration panel. zWhen you install other optional kit, it may not be possible to select the 3-way or 2-way air discharge. For details, refer to the manual for the optional kit or the catalogue. zContents of Kit Prior to installation make sure you have the complete kit of parts. Name
Sealing material(A)
Sealing material(B)
Sealing material(C)
Sealing material(D)
Quantity
1 piece
1 piece
1 piece
1 piece
Shape and marking
Name Quantity
3 Insulation for top plate 1 piece
1 piece
Insulation for side plate 1 piece
2 pieces
1 piece
Moisture absorber for bell-mouth
2 pieces
1 piece
Moisture absorber for horizontal vane
5 kinds
Shape and marking
SkyAir LU Series
163
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
3
ED21-302
Installation of the insulation
(1) Installation to the side plate Adhere insulation for side plate
to the side of indoor unit. 140 class
71 class
Put the wire through the slit of the insulation.
(2) Installation to the top plate Adhere insulation for top plate
When adhering insulation, align its edge with the bottom line of casing.
When adhering insulation, align its edge with the bottom line of casing.
,
to the top of the indoor unit.
(3) Adhere the moisture absorber for horizontal vane to the edge of the horizontal vane of air outlet (Fig. 2). (Choose the same color as panel.) Horizontal vane Moisture absorber for horizontal vane Fig. 2
Align it with the upper edge of horizontal vane. Horizontal vane Moisture absorber for horizontal vane
Fig. 1
(4) Adhere the moisture absorber in accordance with the reference surface without wrinkles. (Fig. 4) Adhere the moisture absorber in accordance with the reference line . (Fig. 5) Reference surface Swing connector Swing motor
(Fig. 3)
Sticking reference
Adhere it from the edge of switch box. Switch box
Bellmouth
Sticking reference Fig. 4
Fig. 5 J : 1P012222B
164
SkyAir LU Series
ED21-302
2.3
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
KDBJ55K160W â&#x20AC;&#x201C; Panel spacer
3
SkyAir LU Series
165
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
166
ED21-302
SkyAir LU Series
ED21-302
2.4
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
KDDP55D160(K) â&#x20AC;&#x201C; Fresh Air Intake Kit
SkyAir
FHYC35~140K
3
71
290
C : 3K011144-1-1
SkyAir LU Series
167
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-302
C : 3K011144-1-2
168
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
3
SkyAir LU Series
169
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
2.5
ED21-302
KDDJ55X160 â&#x20AC;&#x201C; Fresh Air Intake Kit
The fresh air is taken into the unit by the indoor unit fan or duct fan, which is field supplied. The location of fresh air intake port will be changeable by installing the duct fan.
KDDJ55X160
1
2P066796B-1
170
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
3
2
2P066796B-2
SkyAir LU Series
171
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
2.6
ED21-302
KAFP556D80 · 160 – High Efficiency Filter (Including Filter Chamber) KAFP557D80 · 160 – High Efficiency Filter (Including Filter Chamber) Combination table
2.7
High Efficiency Filter (Set)
High Efficiency Filter
KAFP556D80 KAFP557D80
KAFJ552K80 KAFJ553K80
KAFP556D160 KAFP557D160
KAFJ552K160 KAFJ553K160
Filter Chamber KDDFP55D160
KAFJ552K80 · 160 – High Efficiency Filter (Replacement) KAFJ553K80 · 160 – High Efficiency Filter (Replacement) Specifications High Efficiency Filter (Replacement) KAFJ552K80
KAFJ552K160
Filter Chamber
KAFJ553K80
KAFJ553K160
KDDFP55D160
Collecting Efficiency (%)
65% (NBS Calorimetric method)
Initial Pressure Loss (Pa)
34
44
Final Pressure Loss (Pa)
78
98
Filter
90% (NBS Calorimetric method)
Non-woven Fabric of Synthetic Fiber Non-woven Fabric of Synthetic Fiber 2,500 (Dust Concentration 0.15 mg / m3)
Life (h) Models to be Applied
35~71K Model
1,800 (Dust Concentration 0.15 mg / m3)
100~140K Model 35~71K Model
100~140K Model
Precaution at use 1. The high efficiency filter, and the other filter can not be installed together. 2. The unit should be operated with 4-way dischange when the high efficiency filter is installed. It can not be applied to the high ceiling room. 3. Field setting by remote controller is necessary when the high efficiency filter is installed.
Dimension
2.8
Model
A
KAFJ552K80, 553K80
25
KAFJ552K160, 553K160
45
KRP1B98 – Installation Box for Adaptor PCB
Dimension
Model No. Item Applicable Model Adaptor for Wiring
172
KRP1B98 FH(Y)C35~140K KRP1B57 KRP4A53
SkyAir LU Series
ED21-302
2.9
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
KDDFP55D160 â&#x20AC;&#x201C; High-Efficiency Filter Chamber
3
SkyAir LU Series
173
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
174
ED21-302
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
2.10
KAFJ551K160 – Long-Life Filter for Decoration Panel (Replacement)
2.11
KAFP55D160, KAFJ55K160H (Replacement) – Ultra Long-Life Filter (Including Filter Chamber)
3
Installation Iocation Filter Cleaning Period Dirty Area
Every 5,000 hrs
Not Dirty Area
Every 10,000 hrs
KKSJ55K160 – Chamber Connection Kit
CAUTION Confirm a combination of chamber connection kit with option (chamber type) by the right table. Fresh air intake kit (chamber type) must be set up side surely.
Option (Chamber Type) Down Side
2.12
Up Side Fresh Air Intake Unit
High Efficiency Filter Unit Ultra-Long Life Filter Unit
Don't adopt any combinations except the Table because they may cause functional disorder.
Dimension
Concerning installation of the indoor unit, the option (chamber type) and the decoration panel, refer to installation (operation) manual attached to these parts.
SkyAir LU Series
175
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
2.13
176
ED21-302
KDJ55K80 · 160 – Branch Duct Chamber
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
3
SkyAir LU Series
177
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-302
2.13.1 Fan Performance and Discharge Pattern in case of using Branch Duct Single Branch â&#x20AC;&#x201D; 3 Way Discharge
Sealing
Branch
R
S
Sealing
T
S
Branch
T
Q
S
Sealing Branch
T R
R
Q
S
R
T
Sealing
Q
Q
Branch (V0690)
35~71 Single branch ( ) 50/60Hz Common use
55 50
External static pressure (Pa)
50
71
45
50
50
50
40
35
35
30
30
30
25
25
25
20
20
20
15
15
15
10
10
10
5
5
5
0
0 2
50
40
35
1
60
35
35
0
71
45
60
35
Single branch ( ) 50/60Hz Common use
55
71
45
60
40
Single branch ( or ) 50/60Hz Common use
55
3
4
0 0
1
Air volume (m3/min)
2
3
4
0
1
Air volume (m3/min)
2
3
4
Air volume (m3/min)
100~140 Single branch sealing ( 50/60Hz Common use
130 120
)
or
)
Single branch sealing ( 50/60Hz Common use
130 120
140
125
125
110
125
100
100
100
100
100
External static pressure (Pa)
140
110
90
90
90
80
80
80
70
70
70
60
60
60
50
50
50
40
40
40
20
20
20
20
20
20
10
10
10
0
0 0
1
2
3
4
5
6
7
8
Air volume (m3/min)
178
Single branch sealing ( 50/60Hz Common use
130
9 10
)
140
0 0
1
2
3
4
5
6
7
8
Air volume (m3/min)
9 10
0
1
2
3
4
5
6
7
8
9 10
Air volume (m3/min)
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
Single Branch â&#x20AC;&#x201D; 2 Way Discharge
S
S
T
R Q
Sealing
Sealing
T R
R Branch Q or T
Sealing
S
Branch
S or T
Sealing Sealing
T
Sealing
Q
Branch
R or T
Q
(V0693)
3
35~71
90
Single branch - 2 way discharge ( 50/60Hz Common use
,
sealing) 90
Single branch - 2 way discharge ( 50/60Hz Common use
71
80
71
80
60
60
50
50
70
35
External static pressure (Pa)
External static pressure (Pa)
70
sealing)
60 50 40 30 20 10
35
60 50 40 30 20 10
0
0 0
1
2
3
4
5
0
1
Air volume (m3/min)
2
3
4
5
Air volume (m3/min)
100~140
160
Single branch - 2 way discharge (100~140. 50Hz)
160
150
150
140
140 Sealing
120
Sealing
110 Sealing
100 90 80 70 60 50 40
120
Sealing
110 Sealing
100 90 80 70 60 50 40
30
30
20
20
10
10
0
Sealing
130
External static pressure (Pa)
External static pressure (Pa)
130
0 0
1
2
3
4
5
6
7
8 3
9 10 11 12
Air volume (m /min)
SkyAir LU Series
Single branch - 2 way discharge (100~140. 60Hz)
0
1
2
3
4
5
6
7
8
9 10 11 12
Air volume (m3/min)
179
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-302
2 Branches — 2 Way Discharge
S
Sealing Sealing
S
T
R
Branch
Q
Sealing
R
T
R
Sealing
S
Branch Sealing
T
Sealing
Q
Q
Branch (V0696)
35~71
90
2 Branch - 2 way discharge ( 50/60Hz Common use
90
71 60
80 70
External static pressure (Pa)
sealing) 2 Branch - 2 way discharge ( 50/60Hz Common use
sealing) 2 Branch - 2 way discharge ( 50/60Hz Common use
71
71
60
80
50
50
35
35
70
50
60
50
50
50
40
40
40
30
30
30
20
20
20
10
10
10 0
0 1
2
3
4
5
6
7
0
8
35
70
60
0
60
80
60
0
sealing)
Air volume (m3/min)
1
2
3
4
5
6
7
8
Air volume (m3/min)
0
1
2
3
4
5
6
7
8
Air volume (m3/min)
100~140
150
2 Branch - 2 way discharge (100~140. 50Hz)
150
140
External static pressure (Pa)
2 Branch - 2 way discharge (100~140. 50Hz)
140
130
Branch
130
Branch
120
Branch
120
Branch
Branch
110
Branch
110 100
100
90
90
80
80
70
70
60
60
50
50
40
40
30 20
Operation limit less than 12m3/min
10
30
Operation limit less than 12m3/min
20 10
0
0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Air volume (m3/min)
Air volume (m3/min)
As for the installation procedures, refer to the “8.7.1 Filter Chamber”
180
SkyAir LU Series
ED21-302
2.14
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
Dimensions with Optional Kit
2.14.1 KDBJ55K160W â&#x20AC;&#x201C; Panel Spacer FH(Y)C35~71K Unit (mm)
3
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005390E
FHYC100K~140K Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005391D
SkyAir LU Series
181
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-302
2.14.2 KDDP55D160 – Fresh Air Intake Kit (Without T Joint, Duct Fan) FH(Y)C35K~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
Note 4
View
Service Access Panel : 450×450mm or more Refer to Note 2
290
Installation Service Access Panel
Connection Chamber (Right)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
How to connect Chamber 4 Independently(Refer to Note 5,6)
Applicable Models Skyair
FH(Y)C35~71K
5 4 3 2 1 Number
Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981A
FHYC100K~140K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
View
Service Access Panel : 450×450mm or more Refer to Note 2
Note 4
Installation Service Access Panel
Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
182
Applicable Models Skyair
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984A
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
2.14.3 KDDP55D160K – Fresh Air Intake Kit (With T Joint, Without Duct Fan) FH(Y)C35K~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Flexible Duct (Accessory)
3 Installation Service Access Panel
Service Access Panel : 450×450mm or more Refer to Note 2
Suction Duct (K-KFD9A) Optional (Accessory) T Joint
Plate Band
(Accessory)
Connecting Chamber (Right)
290
(Accessory)
How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
Applicable Models SkyAir
FH(Y)C35~71K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032987A
FHYC100K~140K Service Access Panel : 450×450mm or more Refer to Note 2
Installation Service Access Panel
Unit (mm) Flexible Duct (Accessory)
Service Access Panel : 450×450mm or more Refer to Note 2 Plate Band (Accessory)
T Joint (Accessory)
Suction Duct (K-KFD9A) Optional (Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
SkyAir LU Series
Applicable Models Skyair
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032990A
183
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-302
2.14.4 KAFP â&#x20AC;&#x201C; High Efficiency Filter FH(Y)C35~71K
Unit (mm)
290
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975A
FHYC100~140K
Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032976A
184
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3. Ceiling Mounted Cassette Corner Type [FH(Y)K] 3.1
BYK45FJW1 · 71FJW1 – Decoration panel
BEFORE INSTALLATION PRECAUTIONS • Refer also to the installation manual attached to the indoor unit. ACCESSORIES • The box contains this manual and the parts listed below. Item
Description
Quantity BYK45FJ BYK71FJ
3
Decoration panel
Panel fixing screw
Washer
M5 × 35
1 set
1 set
5 pcs.
5 pcs.
5 pcs.
5 pcs.
NOTE TO INSTALLER Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.
PREPARATION OF DECORATION PANEL • Handle the decoration panel with care. 〈 Never lean the panel against a wall, etc. nor leave it on a projecting object. (For prevention of dents and damages to the panel surface) Never grab the discharge grille during the installation work. (For prevention of damage to the discharge grille) 〉 (1) Remove the suction grille from the decoration panel. (See figure below.) 1) Slide the suction grille lever and lift it up to one side.
SkyAir LU Series
185
Ceiling Mounted Cassette Corner Type [FH(Y)K]
ED21-302
2) Unhook the suction grille off from the decoration panel.
(2) Remove the air filter. Pull up the air filter knob to remove the air filter.
INSTALLATION OF THE DECORATION PANEL TO THE INDOOR UNIT BODY <<Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.>> 1. Installing the panel (1) Install the decoration panel to the indoor unit body temporarily.
Portions to hook the panel's temporary installation hooks
Portion at which the panel is fixed. (5 locations)
186
Temporary installation hooks
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Corner Type [FH(Y)K]
(2) Tighten the panel fixing screws temporarily. 1) Open the air outlet decorative covers.
Air outlet decorative covers
3
2) Put the panel fixing screws (5 pcs.) through the washers and tighten the screws temporarily. 3) Move the panel as indicated by the arrow in the above figure for adjustment so as to make no gap between the panel and the ceiling. 2. Wiring between the indoor unit and the panel ¡ With the decoration panel temporarily installed to the indoor unit, wire between the indoor unit and the decoration panel. (See figure below.) (1) Connect the connectors for swing motor and the limit switch on the decoration panel to those on the indoor unit body respectively. (2) Check that the connectors are of the same color. Panel side
Indoor unit side
(Motor power cable) Color of connector: red
Note: No connection of connectors or connection of connectors of different colors causes the unit to stop operating with the Operation lamp on the remote control blinking and the trouble code display "A7" on the remote controller.
Panel side
Indoor unit side
(Limit switch) Color of connector: black
SkyAir LU Series
187
Ceiling Mounted Cassette Corner Type [FH(Y)K]
ED21-302
3. Fixing the decoration panel (1) In order to prevent air leakage, a sealing material is provided at the spot where the indoor unit body is joined with the decoration panel. Fix the decoration panel in the following method. (Shoulder bolts are used as the fixing screws. Tighten the bolts until their shoulders.) Indoor unit body Indoor unit
Sealing material Standard tightening length: 20 mm Shoulder bolts are used to protect the indoor unit. The bolts can be tightened to the allowance of up to 15 mm.
Decoration panel
Decoration panel body
(2) When tightening the bolts, be sure to make no gap between the panel and the ceiling and set the panel in parallel to the ceiling and the ceiling joint. á
Improper installation of the panel to the cassette body causes air leakage. ñ
Note: In case there remains a gap between the panel and the ceiling when the fixing bolts have been tightened fully to their shoulders, adjust the height of the indoor unit.
Make no gap here.
Note: The decoration panel can be adjusted back and forth to 10 mm, respectively.
(3) Finally, make sure that the decoration panel is securely fixed to the indoor unit. Improper installation (tightening) causes the troubles as shown below; be sure to double-check the completion of the installation work. ñ á
No gap
Air leakage
Air leakage from the ceiling Dust deposit Dew buildup and dew dripping
INSTALLATION OF SUCTION GRILLE AND AIR FILTER For their installation, take the reverse steps mentioned in "PREPARATION OF DECORATION PANEL".
188
SkyAir LU Series
ED21-302
3.2
Ceiling Mounted Cassette Corner Type [FH(Y)K]
KPBJ52F56W · 80W – Panel Specer
3
SkyAir LU Series
189
Ceiling Mounted Cassette Corner Type [FH(Y)K]
190
ED21-302
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
191
Ceiling Mounted Cassette Corner Type [FH(Y)K]
192
ED21-302
SkyAir LU Series
ED21-302
3.3
Ceiling Mounted Cassette Corner Type [FH(Y)K]
KDBJ52F56W · 80W – Air Discharge Blind Panel
3
SkyAir LU Series
193
Ceiling Mounted Cassette Corner Type [FH(Y)K]
194
ED21-302
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
195
Ceiling Mounted Cassette Corner Type [FH(Y)K]
196
ED21-302
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
197
Ceiling Mounted Cassette Corner Type [FH(Y)K]
198
ED21-302
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
199
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3.4
ED21-302
KAFJ521F56 · 80 – Replacement Long Life Filter Washable Model Items Average Efficiency Initial Pressure Loss Final Pressure Loss Life Time Materials Number Required Per Model Weight (kg)
KAFJ521F56
KAFJ521F80
45 (gravity Method) Less Than 9.8 Pa 49 Pa 2,500 hours (Dust Particle Concentration at 0.15 mg/m3) Mildew Proof Resin Net Two pieces 0.4 0.6
Dimension
3.5
Model
A
KAFJ521F56
403
KAFJ521F80
503
K-HV7AW · 9AW – Discharge Grille This optional kit is used when the unit is installed with front air discharge. The direction of air can be adjusted flexibly. This discharge grille should be installed with the following flexible duct. Specifications Model Items Air Flow Rate (m³/min) Type
K-HV7AW
K-HV9AW
9~13
12~19
HV type (Horizontal blade and vertical blade movable)
External Color Materials
White
White
Steel plate (A cryptomeria only at the tip of the outlet + nylon flocking)
Structural Parts
Discharge grille, Screws, Blade control tool
Applicable Flexible Duct
KFDJ52F56
KFDJ52F80
35 · 45F
60 · 71F
Pressure Drop
Applicable Models
m/s : Discharge Velocity
Air Flow Rate
Model
200
A
B
C
D
K-HV7AW
523
466
488
500
K-HV9AW
723
666
688
700
SkyAir LU Series
ED21-302
3.6
Ceiling Mounted Cassette Corner Type [FH(Y)K]
KFDJ52F56 · 80 – Flexible Duct with Shutter
3
SkyAir LU Series
201
Ceiling Mounted Cassette Corner Type [FH(Y)K]
202
ED21-302
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
203
Ceiling Mounted Cassette Corner Type [FH(Y)K]
204
ED21-302
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
205
Ceiling Mounted Cassette Corner Type [FH(Y)K]
206
ED21-302
SkyAir LU Series
ED21-302
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
207
Ceiling Mounted Built-In Type [FH(Y)B-F]
ED21-302
4. Ceiling Mounted Built-In Type [FH(Y)B-F] 4.1
208
BYBS45DJW1 – Decoration panel BYBS71DJW1 – Decoration panel BYBS125DJW1 – Decoration panel
SkyAir LU Series
ED21-302
Ceiling Mounted Built-In Type [FH(Y)B-F]
3
SkyAir LU Series
209
Ceiling Mounted Built-In Type [FH(Y)B-F]
210
ED21-302
SkyAir LU Series
ED21-302
Ceiling Mounted Built-In Type [FH(Y)B-F]
3
SkyAir LU Series
211
Ceiling Mounted Built-In Type [FH(Y)B-F]
4.2
212
ED21-302
KTBJ25K56W · 80W · 160W – Service access panel
SkyAir LU Series
ED21-302
4.3
Ceiling Mounted Built-In Type [FH(Y)B-F]
KAFJ252L56 · 80 · 160 – High-Efficiency Filter KAFJ253L56 · 80 · 160 – High-Efficiency Filter
Specifications Model
KAFJ252L56
Item Average Efficiency
KAFJ253L80
KAFJ253L160
Less Than 5
Less Than 5
10
10
Synthetic Fiber non-woven Fabric 2,500 (Dust Particle Concentration at 0.15 mg/m3)
Filter Chamber for Bottom Suction
KAFJ253L56
90% (NBS Colorimetric Method)
Ultimate Pressure Loss (mmH2O) Effective Life (h)
KAFJ252L160
65% (NBS Colorimetric Method)
Initial Pressure Loss (mmH2O)
Filter Materials
KAFJ252L80
KAJ25L56D
Dimensions (mm) (H×W×D)
55×650×360
Applicable Model
35 · 45F
KAJ25L80D
KAJ25L160D
(55×475×360)×2 (55×700×360)×1 (55×650×360)×1 60 · 71F
100 · 125F
Synthetic Fiber non-woven Fabric
3
1,800 (Dust Particle Concentration at 0.15 mg/m3) KAJ25L56D 55×650×360 35 · 45F
KAJ25L80D
KAJ25L160D
(55×475×360)×2 (55×700×360)×1 (55×650×360)×1 60 · 71F
100 · 125F
Installation
Characteristics of Filter
SkyAir LU Series
213
Ceiling Mounted Built-In Type [FH(Y)B-F]
4.4
ED21-302
KAFJ251K56 · 80 · 160 – Replacement long-life filter
Specifications Model Item Dimensions (mm) (H×W×D) Average Efficiency Pressure Loss Initial (pa) Ultimate Filter Materials Number of Filters Effective Life (h) Applicable Model
4.5
Characteristics of Filter KAFJ251K56
KAFJ251K80
KAFJ251K160
20×506×377 20×701×377 20×451×377 20×656×377 50% (by weight method) 9.8 (1mmH2O) 49 (5mmH2O) Mold Prevention resin net 1 2 (each one) 2 (each one) 2,500 (at Dust Particle Concentration of 0.15 mg/m3) For indoor unit For indoor unit For indoor unit 35~45F 60~71F 100~125F 20×656×377
KAJ25L56D · 80D · 160D – Filter Chamber for Bottom Suction
Applicable Model Model
Installation Applicable Model
Dimension
214
SkyAir LU Series
ED21-302
4.6
Ceiling Mounted Built-In Type [FH(Y)B-F]
KAJ25L56B · 80B · 160B – Filter Chamber for Rear Suction Contents of kit Name Rear-Intake Filter Chamber Blind Board Screws For Blind Board (M5×12) For Filter Chamber Washer for Suspension Bracket Suspension Bracket Screws for Suspension Bracket (M6×12) Filter Guide Screws for Filter Guide (M5×12) Applicable Model
Quantity KAJ25L56B
KAJ25L80B
KAJ25L160B
1 1 4 11
1 1 6 13
1 1 6 15
4 2 2
4 2 2
4 2 2
– – 35 · 45F
1 2 60 · 71F
1 2 100 · 125F
3
Preparation before installation
SkyAir LU Series
215
Ceiling Mounted Built-In Type [FH(Y)B-F]
216
ED21-302
SkyAir LU Series
ED21-302
Ceiling Mounted Built-In Type [FH(Y)B-F]
3
SkyAir LU Series
217
Ceiling Mounted Built-In Type [FH(Y)B-F]
4.7
218
ED21-302
KSAJ25K56 · 80 ·160 – Canvas Duct
SkyAir LU Series
ED21-302
4.8
Ceiling Mounted Built-In Type [FH(Y)B-F]
K-DG4BW · 5BW · 7BW · 9BW – Air Discharge Unit-Discharge Grille+Discharge Chamber K-DGC4B · 5B · 7B · 9B – Air Discharge Unit-Discharge Grille+Discharge Chamber
3
SkyAir LU Series
219
Ceiling Mounted Built-In Type [FH(Y)B-F]
220
ED21-302
SkyAir LU Series
ED21-302
4.9
Ceiling Mounted Built-In Type [FH(Y)B-F]
K-DDV20A â&#x20AC;&#x201C; Branch Duct
Specification
Dimension Model
Item Inlet Duct Size Outlet Duct Size Outside Insulation Inside Insulation
Polyurethane Foam Foam Polysthyrene
Pressure loss of Branch Duct
3
Model
SkyAir LU Series
Weight (kg)
221
Ceiling Mounted Built-In Type [FH(Y)B-F]
4.10
ED21-302
K-FDK151B · 152B · 153B · 154B · 155B · 156B – Flexible Duct K-FDK201B · 202B · 203B · 204B · 205B · 206B – Flexible Duct Specification Model Item Maximam Outer Dimension Fitting Port Size Operating Temperature Range Applicable Model Structure
(Inner Dimension)
(Inner Dimension)
-10~+70˚C 35~125F Pressure loss of Flexible Duct Air ty oci Vel c.) / se (m t Duc eter Diam m) (m
m H20/100m
222
SkyAir LU Series
ED21-302
4.11
Ceiling Mounted Built-In Type [FH(Y)B-F]
KBBJ25K56 · 80 · 160 – Blind Board
3
4.12
KDAJ25K56 · 71 · 140 – Adaptor for Discharge
SkyAir LU Series
223
Ceiling Mounted Built-In Type [FH(Y)B-F]
4.13
224
ED21-302
KDJ2507K56 · 80 · 160 – Flange for Suction
SkyAir LU Series
ED21-302
4.14
Ceiling Mounted Built-In Type [FH(Y)B-F]
Optional Kit Installation Drawing
Discharge Chamber+Discharge Grille <Ï&#x2020;150> K-DGC4~7B, K-DG4~7BW
3
K-DGC9B, K-DG9BW
SkyAir LU Series
225
New Ceiling Suspended Cassette Type
ED21-302
5. New Ceiling Suspended Cassette Type 5.1
KDBHJ49F80 · 140 – Seiling Member of Air Discharge Outlet
Dimension
Model KDBHJ49F80 KDBHJ49F140
Material Galvanized Steel Plate (with Flocking)
Model KDBTJ49F80 KDBTJ49F140
Material Galvanized Steel Plate (with Flocking)
Model KDBHJ49F80 KDBHJ49F140
5.2
KDBTJ49F80 · 140 – Decoration Panel for Air Discharge
Dimension
Model KDBTJ49F80 KDBTJ49F140
5.3
KDGJ49F80 · 140 – Vertical Flap Kit
Dimension
Model KDGJ49F80 KDGJ49F140
226
Packing Quantity 4(each 2×2)
SkyAir LU Series
ED21-302
5.4
New Ceiling Suspended Cassette Type
KAFJ495F140 – Replacement Long Life Filter
Dimension
Model Item Initial Pressure Loss (Pa) Final Pressure Loss (Pa) Average Efficiency (%) Life Time (h)
KAFJ495F140 Less Than 7 Less Than 49 50 (Gravity Method) 2,500 (Dust Particle Concentration at 0.15 mg/m3)
Filter Pass Air Flow Rate Materials Number Required Per Model Weight (kg)
3
18.5 m /min Mildew Proof Resin Net 1 0.4
3
5.5
KHFJ49F80 · 140 – L Connection Piping Kit Model KHFJ49F80 KHFJ49F140
Dimension
5.6
Liquid Side
Gas Side
KRP1B97 – Installation Box for Adaptor PCB
Dimension
SkyAir LU Series
Model No. Item Applicable Model Adaptor for Wiring
KRP1B97 FUY71~125FJ KRP4A53
227
Ceiling Suspended Type [FH(Y)]
ED21-302
6. Ceiling Suspended Type [FH(Y)] 6.1
KAFJ501D56 · 80 · 112 · 160 – Replacement Long Life Filter
Specifications Model
KAFJ501D56
Item
KAFJ501D80
KAFJ501D112
KAFJ501D160
3
Effective Life, Average Efficiency 2,500 hours (at Dust Particle Concentration of 0.15 mg/m ), 45% (by Weight Method) Filter Materials
Mold Prevention Resin Net
Mold Prevention Resin Net
Nos. Required
2 pieces
3 pieces
Applicable Model
For Indoor unit 35~50
6.2
For Indoor unit 60~71
For Indoor unit 100
For Indoor unit 125
KDU50B50 · 71 · 125VE – Drain Pump Kit
Specifications Model Item
KDU50B50VE
Drain-up Lift (mm)
600
Power Supply
Single Phase 220-240V/220V 50/60Hz (from Indoor Unit PC Board)
Power Consumption (W)
Applicable Model
KDU50B125VE
VP20 (Ex. dia. φ26, Int. dia. φ20)
Drain Con, Diameter Pump
KDU50B71VE
13.5/12 (50/60Hz) 35~50B
60~71B
100~125B
Precaution at use 1. Don’t turn off the power within 5 minutes after cooling operation stops. 2. The liquid crystal display blinks to inform us that safety device actuated. 3. When cooling operation’s seaaon is over, extract drain water. Installation guide of the drain pump kit <Change in drain pump kit> Exit drain pipe has been changed from VP25 to VP20 (to meet the drain diameter of main frame). Attached drain pipe (450 mm chloride vinyl straight pipe bellow, elbow) Æ only bellow hose for VP20 All units of drain up height was unified to 600 mm (from the bottom of the ceiling).
Wiring diagram
228
SkyAir LU Series
ED21-302
6.3
Ceiling Suspended Type [FH(Y)]
KHFJ5F50 · 60 · 80 · 160 – L-Type Piping Kit Application purpose This kit must be bent inside the unit as shown below, when the refrigerant piping is carried out in a ceiling space. This L shape kit is an optional accessory which has been developed for improving the work of the processing on site. Model Item
KHFJ5F50
KHFJ5F60
KHFJ5F80
KHFJ5F160
Applicable Model
For Indoor Unit 35F
For Indoor Unit 45F~60F
For Indoor Unit 71F
For Indoor Unit 100F~125F
Installation KHFJ5F50~160
6.4
3
Installation
KRP1C93 – Installation Box for Adaptor PCB
KRP1C93
Model No. Item Applicable Model Adaptor for Wiring Fixing Place Dimensions (mm)
SkyAir LU Series
W H D
KRP1C93 FH(Y)35~125B KRP1B54 KRP4A52 In the Unit 109 124 38
229
Floor Standing Type [FVY]
ED21-302
7. Floor Standing Type [FVY] 7.1
KAFJ95L160 – Replacement Long Life Filter Model Item Applied Model Average Efficiency (%) Initial Pressure Loss (Pa) Final Pressure Loss (Pa)
Dimension
Life Time (h) Materials Number Required Per Model Weight (kg)
7.2
KRP4A95 – Installation Box for Adaptor PCB
KRP4A93
Model No. Item Applicable Model Adaptor for Wiring Fixing Place Dimensions (mm)
230
KAFJ95L160 FVYJ71~125L(A) 60 (Gravity Method) Less Than 8 Less Than 49 2,500 (Dust Particle Concentration at 0.15 mg/m3) Mildew Proot Resin Net 1 0.4
W H D
KRP4A95 FVY71~125L(A) KRP4A52 KRP1B57 In the Unit 180 117 64
SkyAir LU Series
ED21-302
Outdoor Unit
8. Outdoor Unit 8.1
KIS95 – Drain Plug Kit Use this plug to connect a drain hose to an outdoor unit. Outlook KIS95
Drain hose connection dia φ16ID. Notes:
8.2
3
KIS95 Drain plug (With Y joint) plug (3 pcs.)
1. This is the joint for attaching a vinyl hose (field supplied). This is used between the drain hole which is on the bottom plate of outdoor unit and vinyl hose. 2. Drain water accumulate to the bottom of outdoor unit it depends on the situation of operation. But it is necessary to connect drain hose not to be spread the drain water over the neighbors, when it is installed on the wall. 3. The position of holes are unfit to connect with outdoor units in some models. In this case, use it without Y joint.
KKPJ5F180 – Central Drain Plug
SkyAir LU Series
231
Outdoor Unit
8.3
ED21-302
KHR58C21, KHD58C21A, KHD58C23A, KHD58C24A, KHD58D31, KHD58D33, KHRJ5F224F, KHRJ5F280F – Refrigerant Branch Piping <Caution> This is the branch kit for refrigerant piping to connect indoor and outdoor units of TWIN/TRIPLE/ DOUBLE Twin simultaneous ON/OFF system.
How to use 1. Uses as branch joints of refrigerant piping. Note) It is necessary because it is not attached to the air conditioner. 2. Pipes of the joint parts are widened. → Enables easy connection and Brazing. 3. Insulation materials are equipped as standard.
Type Model
Item
Reducer
Type Model
Triple Multi KHD58D33
R(Y)71LU
R(Y)100~140LU
R(Y)200KU
R(Y)250KU
R(Y)140LU
2 — — —
2 — — —
— — 2 1
— — 2 —
— — — —
— — — —
2 — 1 —
— 1 — —
— — — 1
— — — —
Double Twin Multi
Triple Multi KHD58D31 R(Y)200KU
KHRJ5F224F R(Y)200KU
KHRJ5F280F R(Y)250KU
Branch Pipe
Reducer
(2 sets)
1 — — 1
— — — —
— — — —
1 — 1 —
— — — —
— — — —
(2 sets)
— — — —
— — — —
— — — —
— — — —
Branch Pipe
(2 sets)
Reducer
Liquid Side Joint
Applicable Model
Gas Side Joint
KHD58C24A
Branch Pipe
Item
232
Twin Multi KHD58C21A KHD58C23A
Branch Pipe
Reducer
Gas Side Joint
Liquid Side Joint
Applicable Model
KHR58C21
(2 sets)
SkyAir LU Series
ED21-302
Dimension Twin/Double Twin Multi
Outdoor Unit
Triple Multi
3 Model
(Horizontal)
SkyAir LU Series
233
The air conditioners manufactured by Daikin Industries have received ISO 9000 series certification for quality assurance.
The airconditioning factories of Daikin Industries have received environmental management system standard ISO 14001 certification.
Certificate Number.
Shiga Plant
(ISO9001) JMI-0107 JQA-0495
(ISO9002) JQA-1452
Certificate Number. EC99J2044
Sakai Plant Certificate Number. JQA-E80009
Yodogawa Plant Certificate Number. EC99J2057
Dealer Head Office: Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome, Kita-ku, Osaka 530-8323, Japan Tokyo Office: Shinjuku Sumitomo Bldg., 6-1, Nishi-Shinjuku 2-chome, Shinjuku-ku, Tokyo 163-0235, Japan
http://www.daikin.com/global/ c All rights reserved
The specifications, designs, and information in this brochure are subject to change without notice.
This book is made of recycled paper.
ED 21-302 Printed in Japan 07/2003 FS