ED43 - 120A
Air Cooled Single Packaged Air Conditioners Roof Top Type (Cooling Only) UAT - KA Series
The contents of minor change of ED43-120A Date
Page
Sep. 2002
47
Mar. 2005
39
Note
Correction of errors. (EDB No. of ED43-120A is not changed)
ED43-120A
Air Cooled Single Packaged Roof Top Type ................................. 1 1. Features ..................................................................................................2 1.1 Features ...................................................................................................2
2. Power Supply ..........................................................................................4 2.1 Power Supply ...........................................................................................4
3. Specifications ..........................................................................................5 3.1 50Hz / 60Hz..............................................................................................5
4. Dimensions .............................................................................................8 4.1 Dimensions/Service Space ......................................................................8
5. Piping Diagrams....................................................................................14 5.1 Piping Diagrams .....................................................................................14
6. Wiring Diagrams....................................................................................16 6.1 Y1, YAL ..................................................................................................16 6.2 TAL.........................................................................................................20 6.3 TO ..........................................................................................................24
7. Capacity Tables ....................................................................................25 7.1 Cooling Capacity [50Hz].........................................................................25 7.2 Cooling Capacity [60Hz].........................................................................29
8. Fan Performance ..................................................................................33 8.1 Fan Performance Data ...........................................................................33 8.2 Fan Motor Specification..........................................................................35
9. Operation Limit......................................................................................36 9.1 Operation Limit .......................................................................................36
10.Sound Level ..........................................................................................37 10.1 Overall Sound Level ...............................................................................37 10.2 Octave Band Level .................................................................................38
11.Electric Characteristics..........................................................................39 11.1 Electric Characteristics...........................................................................39
12.Field Wiring ...........................................................................................41 12.1 Field Wiring ............................................................................................41
13.Center of Gravity ...................................................................................42 13.1 Center of Gravity ....................................................................................42
14.Installation .............................................................................................44 14.1 Installation Manual .................................................................................44
15.Foundation and Service Space of UAT30H ..........................................53 15.1 UAT30H..................................................................................................53 15.2 How to Install Pulley ...............................................................................54
16.Optional Accessories ............................................................................56 16.1 Option List ..............................................................................................56 16.2 Remote Controller ..................................................................................57 16.3 Details of DTA107A55............................................................................61
17.Wiring Modification................................................................................70 17.1 Wiring for operating signal and alarm.....................................................70
Table of Contents
i
ED43-120A
ii
Table of Contents
ED43-120A
Air Cooled Single Packaged Roof Top Type UAT06KA UAT08KA UAT09KA UAT10KA
Packaged Air Conditioners UAT-KA Series
UAT12KA UAT15KA UAT18KA UAT21KA UAT30H
UAT06KA
UAT08KA UAT09KA UAT10KA UAT12KA
UAT15KA UAT18KA UAT21KA
UAT30H
1
Features
ED43-120A
1. Features 1.1
Features
Model Range
UAT06KA~21KA, 30H
Operation Range (Outdoor Temp)
21°CDB~52°CDB Cooling (UAT06~21KA) 20°CDB~52°CDB Cooling (UAT30H)
Capacity Range
17.7kW~107.7kW (50/60Hz) Cooling
Installation
Easy to install on rooftop or veranda, requiring only ducting, power line and drain piping.
Casing
The casing is made of paintable galvanized steel plate and treated against rust. Since the unit is installed outdoors, the casing is completely weather-proof.
Scroll Compressor
Daikin’s innovative scroll compressor is 10% lighter and 30% smaller than equivalent conventional reciprocating compressors. This makes this series among the industry’s most lightweight and compact, than previous models. Also, since the scroll compressor generates less vibration, this series has greatly improved its durability and achieved the industry’s lowest operation sound. Moreover, the installation of the latest scroll compressor has further improved system efficiency. The recycling guard timer prevents frequent ON/OFF switching, and protects the compressor against overloads due to short cycling.
<NEW> Central Remote Control with VRV
By adopting Central Control Adapter Kit (DTA107A55), you can control UAT series using like VRV such as Central Remote Controller (DCS302B61), Scheduled Timer (DST30161) and Unified On/Off Controller (DCS301B61) With these controller the following functions are available: 1. Operation and Monitoring On/Off 2. Setting and Monitoring of Operation mode 3. Temperature setting 4. Forced shut down 5. Group control 6. Indication of alarm 7. Setting of Timer 8. Setting and cleaning sign of air filter 9. On/Off Group control For the detail, refer to “Details of DTA107A55” on page 61
2
Packaged Air Conditioners UAT-KA Series
ED43-120A
Features
Remote Controller (Optional)
Remote Controller encases a sensible thermostat to ensure accurate temperature control.
Evaporator and Condenser
Efficient cross fin coils are used: the unique waffle louver fins*1 maximize heat exchange efficiency, while the Hi-XA copper tube*2, featuring an inner spiral groove, fully exploits refrigerant turbulence to help increase heat exchange efficiency. The result is substantial energy savings. The fin of the heat exchanger is finished with special acrylic coating (PE fin), and highly resistant to corrosion due to acid rain, sea breeze, etc. Hi-XA tube Waffle louver fins
U.S. PAT. *1 : No.4,434,844 *2 : No.4,480,684
Packaged Air Conditioners UAT-KA Series
3
Power Supply
ED43-120A
2. Power Supply 2.1
Power Supply Symbol
Model
Power Supply
UAT06KAY1 UAT08KAY1 UAT09KAY1 UAT10KAY1 Y1 UAT15KAY1
3φ 380~415V 50Hz (4 wires)
UAT18KAY1 UAT21KAY1 UAT30HY1 UAT06KATAL UAT08KATAL UAT09KATAL TAL
UAT12KATAL
3φ 220V 60Hz (3 wires)
UAT15KATAL UAT18KATAL UAT21KATAL UAT06KAYAL UAT08KAYAL UAT09KAYAL YAL
UAT12KAYAL
3φ 380V 60Hz (4 wires)
UAT15KAYAL UAT18KAYAL UAT21KAYAL TO
4
UAT30HTO
3φ 200/200~220V 50/60Hz (3 wires)
Packaged Air Conditioners UAT-KA Series
ED43-120A
Specifications
3. Specifications 3.1
50Hz / 60Hz
Model
Y1
UAT06KAY1
UAT08KAY1
UAT09KAY1
UAT10KAY1
TAL
UAT06KATAL
UAT08KATAL
UAT09KATAL
—
YAL
UAT06KAYAL
UAT08KAYAL
UAT09KAYAL
—
USRT kW Btu/h kcal/h kW Btu/h %
5 17.7 60,300 15,200 (15.5) (52,900) 100-0 FPS3/4B 530×932 270×739
6 7.5 9 22.0 26.4 31.4 ∗1 Cooling Capacity (50/60Hz) 75,000 90,000 107,200 18,900 22,700 27,000 (19.8) (23.8) (28.3) ∗2 Cooling Capacity (50/60Hz) (67,600) (81,200) (96,600) Capacity Steps 100-0 100-0 100-0 Drain Piping FPS3/4B FPS3/4B FPS3/4B Connections Return (H×W) mm 488×917 488×917 576×952 Ducting Supply (H×W) mm 297×878 297×878 297×878 Casing/Color Paintable Galvanized Steel Plate/Ivory White Type Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) Indoor Coil Rows×Stages×Fin Pitch 2×24×2.0 3×22×2.0 3×22×2.0 3×26×2.0 Face Area m² 0.491 0.443 0.443 0.543 Type Sirocco Fan Drive Belt Drive m³/min 52 68 68 83 Indoor Fan Air Flow Rate cfm 1,840 2,400 2,400 2,930 9 10 10 10 Ext. Static Pressure mmH2O Motor Output kW 0.75 1.5 1.5 1.5 Type Hermetically Sealed Scroll Type Y1 JT200B-YE JT212D-P1YE JT300D-P1YE JT335D-P1YE TAL JT190B JT190B JT265D-P1 — Compressor Model YAL JT190B-YH JT190B-YH JT265D-P1YH — 5.5(Y1) Motor Output kW 4.5 7.5 9.0 4.5(TAL,YAL) Model R22 Refrigerant No. of Refrigerant Circuits 1 1 1 1 Charge kg 2.9 4.0 4.1 5.0 Model SUNISO 4GSDID-K Refrigerant Oil Charge L 1.6 2.7 2.7 2.7 Type Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) Outdoor Coil Rows×Stages×Fin Pitch 2×50×2.0 2×40×2.0 2×40×2.0 2×50×2.0 Face Area m² 1.26 1.57 1.57 1.97 Refrigerant Control Capillary Tube Type Propeller Model P52H11S P52H11S P52H11S P52H11S Y1 90 150 150 175 m³/min TAL 95 160 160 — Outdoor Fan Air Flow Rate YAL 95 160 160 — 50/60Hz Y1 3,177 5,295 5,295 6,177 cfm TAL 3,353 5,648 5,648 — YAL 3,353 5,648 5,648 — Motor Output W 280 230+190 230+190 230+190 Thermal Protector for Compressor and Outdoor Fan Motor, High Pressure Switch, Over Current Relay (Compressor and Safety Devices Indoor Fan Motor), Reverse Phase Protector, Fuse Dimensions H×W×D mm 1,490×690×1,750 1,270×1,600×1,280 1,270×1,600×1,280 1,490×1,600×1,280 Y1 218 313 316 330 Weight kg TAL 218 291 315 — YAL 218 291 315 — Y1 4D015477 4D015478 Drawing No. TAL 4D015480 4D015481 — YAL 4D015483 4D015484 —
Notes:
1. The above data marked with ∗1 are rated in accordance with 27°CDB (80°FDB) 19.5°CWB (67°FWB) indoor temp. 380V and 35°CDB (95°FDB) outdoor temp. 2. The above data marked with ∗2 are rated in accordance with 29°CDB (84°FDB) 19°CWB (66°FWB) indoor temp. and 46°CDB (115°FDB) outdoor temp. at HI fan speed. 3. Above cooling capacities do not include indoor fan motor heat 4. The figures of ∗2 are reference value.
Packaged Air Conditioners UAT-KA Series
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
5
Specifications
Model
ED43-120A
Y1
—
UAT15KAY1
UAT18KAY1
UAT21KAY1
TAL
UAT12KATAL
UAT15KATAL
UAT18KATAL
UAT21KATAL
YAL
UAT12KAYAL
UAT15KAYAL
UAT18KAYAL
UAT21KAYAL
USRT kW Btu/h kcal/h kW Btu/h %
10 35.1 120,000 30,200 (31.6) (107,800) 100-0 FPS3/4B 576×952 297×878
12.5 15 17.5 43.9 52.7 61.6 ∗1 Cooling Capacity (50/60Hz) 150,000 180,000 210,400 37,800 45,300 53,000 (39.6) (47.5) (55.5) ∗2 Cooling Capacity (50/60Hz) (135,200) (162,100) (189,400) Capacity Steps 100-50-0 100-50-0 100-50-0 Drain Piping FPS1B FPS1B FPS1B Connections Return (H×W) mm 572×1,372 572×1,372 748×1,372 Ducting Supply (H×W) mm 343×1,042 343×1,042 343×1,042 Casing/Color Paintable Galvanized Steel Plate/Ivory White Type Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) Indoor Coil Rows×Stages×Fin Pitch 3×26×2.0 3×26×2.0 3×26×2.0 3×34×2.0 Face Area m² 0.543 0.784 0.784 1.024 Type Sirocco Fan Drive Belt Drive m³/min 100 136 136 166 Indoor Fan Air Flow Rate cfm 3,530 4,800 4,800 5,860 10 15 15 15 Ext. Static Pressure mmH2O Motor Output kW 1.5 2.2 2.2 3.7 Type Hermetically Sealed Scroll Type Y1 — 2×(JT212D-P1YE) 2×(JT300D-P1YE) 2×(JT335D-P1YE) Model TAL JT335D-P1 2×(JT190B) 2×(JT265D-P1) 2×(JT300D-P1) Compressor YAL JT335D-P1YH 2×(JT190B-YH) 2×(JT265D-P1YH) 2×(JT300D-P1YH) Y1 — 2×5.5 2×7.5 2×9.0 Motor Output kW TAL 9.0 2×4.5 2×7.5 2×7.5 YAL 9.0 2×4.5 2×7.5 2×7.5 Model R22 Refrigerant No. of Refrigerant Circuits 1 2 2 2 Charge kg 5.0 2×4.0 2×4.1 2×5.3 Model SUNISO 4GSDID-K Y1 — 2×2.7 2×2.7 2×2.7 Refrigerant Oil Charge L TAL 2.7 2×1.6 2×2.7 2×2.7 YAL 2.7 2×1.6 2×2.7 2×2.7 Type Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) Outdoor Coil Rows×Stages×Fin Pitch 2×50×2.0 2×(2×40×2.0) 2×(2×40×2.0) 2×(2×50×2.0) Face Area m² 1.97 2×1.57 2×1.57 2×1.97 Refrigerant Control Capillary Tube Type Propeller Model P52H11S P52H11S P52H11S P52H11S Y1 — 2×150 2×150 2×175 m³/min TAL 200 2×160 2×160 2×190 Outdoor Fan YAL 200 2×160 2×160 2×190 Air Flow Rate Y1 — 2×5,295 2×5,295 2×6,177 cfm TAL 7,060 2×5,648 2×5,648 2×6,707 YAL 7,060 2×5,648 2×5,648 2×6,707 Motor Output W 230+280 2×(230+190) 2×(230+190) 2×(230+190) Thermal Protector for Compressor and Outdoor Fan Motor, High Pressure Switch,Over Current Relay (Compressor and Safety Devices Indoor Fan Motor), Reverse Phase Protector, Fuse Dimensions H×W×D mm 1,490×1,600×1,280 1,270×1,980×1,980 1,270×1,980×1,980 1,490×1,980×1,980 Y1 — 626 632 660 Weight kg TAL 330 581 630 660 YAL 330 581 630 660 Y1 — 4D015479 Drawing No. TAL 4D015481 4D015482 YAL 4D015484 4D015485
Notes:
6
1. The above data marked with ∗1 are rated in accordance with 27°CDB (80°FDB) 19.5°CWB (67°FWB) indoor temp. 380V and 35°CDB (95°FDB) outdoor temp. 2. The above data marked with ∗2 are rated in accordance with 29°CDB (84°FDB) 19°CWB (66°FWB) indoor temp. and 46°CDB (115°FDB) outdoor temp. at HI fan speed. 3. Above cooling capacities do not include indoor fan motor heat 4. The figures of ∗2 are reference value.
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Packaged Air Conditioners UAT-KA Series
ED43-120A
Specifications
Model
Y1
UAT30HY1
TO
UAT30HTO
27.5/30 97.1/107.7 331,000/368,000 83,500/92,600 83.1/96.9 ∗2 Cooling Capacity (50/60Hz) 284,000/330,700 Capacity Steps 100-50-0 Drain Piping FPS1 1/4B Connections Return (H×W) mm 1,113×1,640 Ducting Supply (H×W) mm 205×1,640 Casing/Color Paintable Galvanized Steel Plate/Ivory White Type Cross Fin Coil (Waffle Louver Fins and Hi-X Tubes) Indoor Coil Rows×Stages×Fin Pitch 3×44×2.0 Face Area m² 1.83 Type Dual Suction Multi-Blade Drive Belt Drive m³/min 295 Indoor Fan Air Flow Rate cfm 10,410 17 Ext. Static Pressure mmH2O Motor Output kW 5.5 Type Semi-Hermetically Sealed Reciprocating Compressor Model×No. 8HC582LEC×1 Motor Output kW 22 Model R22 Refrigerant No. of Refrigerant Circuits 1 Charge kg 13.5 Model SUNISO 4GSDID-K Refrigerant Oil Charge L 8 Type Cross Fin Coil (Waffle Louver Fins and Hi-X Tubes) Outdoor Coil Rows×Stages×Fin Pitch 2×50×2.0 Face Area m² 4.260 Refrigerant Control Thermal expansion valve Type Propeller (Direct Drive) Model×No. P80F×3 m³/min 750/900 Flow Rate Outdoor Fan Air (50/60Hz) cfm 26,480/31,770 TH4/YH Model kW 2.5×3 Motor Output Y14 Model kW 1.5×3 High Pressure Switch, Low Pressure Switch, Compressor Thermal Protector, Recycling Guard Timer, Overcurrent Safety Devices Relay (Compressor and Evaporator Fan Motor), Condenser Fan Motor Overcurrent Relay, Fuse, Oil Pressure Control Switch. Dimensions H×W×D mm 1,755×2,680×1,340 Weight (Approx.) kg 1,080 Drawing No. ∗1 Cooling Capacity (50/60Hz)
Notes:
USRT kW Btu/h kcal/h kW Btu/h %
1. The above data marked with ∗1 are rated in accordance with 27°CDB (80°FDB) 19.5°CWB (67°FWB) indoor temp. 380V and 35°CDB (95°FDB) outdoor temp. 2. The above data marked with ∗2 are rated in accordance with 29°CDB (84°FDB) 19°CWB (66°FWB) indoor temp. and 46°CDB (115°FDB) outdoor temp. at HI fan speed. 3. Operative up to 52°C for 50Hz. Operative up to 49°C for 60Hz
Packaged Air Conditioners UAT-KA Series
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
7
Dimensions
ED43-120A
4. Dimensions 4.1
Dimensions/Service Space
(Unit:mm)
UAT06KA
8
Packaged Air Conditioners UAT-KA Series
ED43-120A
Dimensions
(Unit:mm)
UAT08KA / UAT09KA
Packaged Air Conditioners UAT-KA Series
9
Dimensions
ED43-120A
(Unit:mm)
UAT10KA / UAT12KA
10
Packaged Air Conditioners UAT-KA Series
ED43-120A
Dimensions
Packaged Air Conditioners UAT-KA Series
3D014563A
(Unit:mm)
UAT15KA / UAT18KA
11
Dimensions
ED43-120A
12
3D014564A
(Unit:mm)
UAT21KA
Packaged Air Conditioners UAT-KA Series
ED43-120A
Dimensions
UAT30H
Packaged Air Conditioners UAT-KA Series
13
Piping Diagrams
ED43-120A
5. Piping Diagrams 5.1
Piping Diagrams
UAT06KA
UAT08KA / UAT09KA / UAT10KA / UAT12KA
14
Packaged Air Conditioners UAT-KA Series
ED43-120A
Piping Diagrams
UAT15KA / UAT18KA / UAT21KA
UAT30H
Packaged Air Conditioners UAT-KA Series
15
Wiring Diagrams
ED43-120A
6. Wiring Diagrams 6.1
Y1, YAL
UAT06KAY1, UAT06KAYAL
16
Packaged Air Conditioners UAT-KA Series
ED43-120A
Wiring Diagrams
UAT08KAY1 / UAT09KAY1 / UAT10KAY1 UAT08KAYAL / UAT09KAYAL / UAT12KAYAL
Packaged Air Conditioners UAT-KA Series
17
Wiring Diagrams
ED43-120A
UAT15KAY1 / UAT18KAY1 / UAT21KAY1 UAT15KAYAL / UAT18KAYAL / UAT21KAYAL
18
Packaged Air Conditioners UAT-KA Series
ED43-120A
Wiring Diagrams
UAT30HY1
Packaged Air Conditioners UAT-KA Series
19
Wiring Diagrams
6.2
ED43-120A
TAL
UAT06KATAL
20
Packaged Air Conditioners UAT-KA Series
ED43-120A
Wiring Diagrams
UAT08KATAL / UAT09KATAL
Packaged Air Conditioners UAT-KA Series
21
Wiring Diagrams
ED43-120A
UAT12KATAL
22
Packaged Air Conditioners UAT-KA Series
ED43-120A
Wiring Diagrams
UAT15KATAL / UAT18KATAL / UAT21KATAL
Packaged Air Conditioners UAT-KA Series
23
Wiring Diagrams
6.3
ED43-120A
TO
UAT30HTO
24
Packaged Air Conditioners UAT-KA Series
ED43-120A
Capacity Tables
7. Capacity Tables 7.1
Cooling Capacity [50Hz]
UAT06KAY1
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020850A
UAT08KAY1
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020852A
Packaged Air Conditioners UAT-KA Series
25
Capacity Tables
ED43-120A
UAT09KAY1
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020854A
UAT10KAY1
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020856A
26
Packaged Air Conditioners UAT-KA Series
ED43-120A
Capacity Tables
UAT15KAY1
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020858A
UAT18KAY1
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020860A
Packaged Air Conditioners UAT-KA Series
27
Capacity Tables
ED43-120A
UAT21KAY1
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020862A
UAT30HY1
28
Packaged Air Conditioners UAT-KA Series
ED43-120A
7.2
Capacity Tables
Cooling Capacity [60Hz]
UAT06KATAL / UAT06KAYAL
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020851A
UAT08KATAL / UAT08KAYAL
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020853A
Packaged Air Conditioners UAT-KA Series
29
Capacity Tables
ED43-120A
UAT09KATAL / UAT09KAYAL
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020855A
UAT12KATAL / UAT12KAYAL
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020857A
30
Packaged Air Conditioners UAT-KA Series
ED43-120A
Capacity Tables
UAT15KATAL / UAT15KAYAL
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020859A
UAT18KATAL / UAT18KAYAL
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020861A
Packaged Air Conditioners UAT-KA Series
31
Capacity Tables
ED43-120A
UAT21KATAL / UAT21KAYAL
Symbols: AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity : Power input PI (Comp.+outdoor fan motor).
(m³/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes: 1. Direct interpolation is permissible. Do not extrapolate beyond the Operation Limits. 2. shows nominal capacities. 3. SHC is based on each EWB and EDB. SHC*=SHC correction for other dry bulb. (DB*) =0.02×AFR×(1-BF)×(DB*-EDB) Add SHC* to SHC. 4. Above cooling capacities do not include indoor fan motor heat.
3D020863A
UAT30HTO
32
Packaged Air Conditioners UAT-KA Series
ED43-120A
Fan Performance
8. Fan Performance 8.1 8.1.1
Fan Performance Data UAT06 ~ 21KA
3D014926C
Packaged Air Conditioners UAT-KA Series
33
Fan Performance
8.1.2
ED43-120A
UAT30H Performance Data Model
UAT30H
Air flow rate m³/min
ESP
0
5
10
15
20
25
30
40
45
50
250
r.p.m. Kw
670 2.33
730 2.66
780 3.01
840 3.38
890 3.75
940 4.15
990 4.57
265
r.p.m. Kw
710 2.77
760 3.12
820 3.49
870 3.87
920 4.27
970 4.68
1010 1060 1110 1150 1190 5.11 5.56 6.03 6.51 6.98
280
r.p.m. Kw
750 3.27
800 3.64
850 4.03
900 4.42
950 4.84
990 5.26
1040 1080 1130 1170 5.71 6.17 6.65 7.14
295
r.p.m. Kw
790 3.82
840 4.21
890 4.62
930 5.04
980 5.46
1020 1070 1110 1150 5.91 6.36 6.85 7.33
310
r.p.m. Kw
830 4.44
880 4.84
920 5.27
970 5.70
1010 1050 1090 6.15 6.62 7.08
325
r.p.m. Kw
870 5.11
910 5.54
960 5.98
1000 1040 1080 6.44 6.90 7.38
340
r.p.m. Kw
910 5.85
950 6.30
990 6.76
1030 7.23
Symbol:
—
—
1040 1090 1130 1170 5.01 5.46 5.91 6.35
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Note:
r.p.m
: Fan speed
(r.p.m)
kW
: Required motor output
(kW)
ESP
: External static pressure
(mmH2O)
Pulley Specification Model Pulley: Fan side Pulley: Motor side V belt: size × No.
shows the operating range of the standard fan motor. In case the fan motor is used out of range, change motor size.
Operation Range UAT30H
Model
Y1
2B247-35 (fixed dia.)
Air flow rate (m³/min.)
TO
2B291-35 (fixed dia.)
Max. fan speed (r.p.m.)
Y1 TO
34
35
2B171-38 (fixed dia.)
Y1
B64 T 2
TO
B66 T 2
Max. replaceable motor (kW)
UAT30H 250~340 1400 7.5
Packaged Air Conditioners UAT-KA Series
ED43-120A
8.2
Fan Performance
Fan Motor Specification Power supply
Y1 · TAL · YAL Y1 · TAL · YAL Y1 · TAL · YAL Y1 · TAL · YAL
Rated motor output
Y1 · TO
0.75
1.5
2.2
3.7
Shaft outer diameter : φs (mm)
19
24
28
28
38
Shaft length :
Q (mm)
40
50
60
60
80
Keyway width :
W (mm)
6
8
8
8
10
Keyway depth :
U (mm)
3.5
4
4
4
5
B
B
B
B
B 10
Insulation Class :
5.5
Key width :
b (mm)
6
8
8
8
Key Height :
h (mm)
6
7
7
7
8
19
24
28
28
38
Shaft Hole Diameter : φd (mm) Keyway :
B (mm)
6
8
8
8
10
Keyway Height :
H (mm)
21.5
27
31
31
41
Motor : Totally enclosed fan-cooled motor.
Motor Pulley have to be changed when Air Flow Rate and the External Static Pressure are different from factory setting.
How to select Motor Pulley 1. Select the fan revolution speed by air flow rate and external static pressure. 2. Select Motor Pulley by Fan revolution speed. D1 =
D2
N2 N1
D1 D2 N1 N2
: Pitch diameter of Motor Pulley (mm) : Pitch diameter of Fan Pulley (mm) : Revolution speed of Fan Motor (rpm) : Fan Revolution Speed
Relation between outer diameter and pitch diameter of each Pulley are as follows: A type ( Pitch Diameter) = Outer diameter of Pulley - 9mm B type ( Pitch Diameter) = Outer diameter of Pulley - 11mm
How to select V-belt When changing the Motor Pulley, the Standard V- belt may not be used. In that case, select V-belt in accordance with the following formula:
V-belt size ( Length) Lp
Model Name
D2
D1
C
Lp = 2C + 1.57( D1 + D2 ) +
UAT 06KA UAT 08/09/10/12KA UAT 15/18KA UAT 21KA UAT 30H
Wheel Base (C) Y1, TAL, YAL 330 405 500 700 500
( D1 – D2 ) 2 4C
Lp : Effective center periphery length (mm) D1 : Pitch diameter of Motor Pulley (mm) D2 : Pitch diameter of Fan Pulley (mm) C : Wheel base (mm) Note: The unit of V-belt length (Nominal number) is usually shown in “inch”. (P0022)
Packaged Air Conditioners UAT-KA Series
35
Operation Limit
ED43-120A
9. Operation Limit 9.1
Operation Limit
UAT06 ~ 21KA
UAT30H
Note:
36
The graphs are made based on standard air flow rate.
Packaged Air Conditioners UAT-KA Series
ED43-120A
Sound Level
10. Sound Level 10.1
Overall Sound Level dB(A) Model
50/60Hz
UAT06KA
62
Measuring Location in Anechoic Chamber
UAT08KA 63 UAT09KA UAT10KA 64 UAT12KA 2m
UAT15KA
DISCHARGE SIDE
DUCT
66 SUCTION SIDE
UAT18KA
DUCT
A 1m (P0011)
UAT21KA
UAT30H
Note:
67
75
UAT06 ~ 21KA UAT30H
A 0.5m 1.5m
Operation sound differs with operation and ambient conditions.
Packaged Air Conditioners UAT-KA Series
37
Sound Level
10.2
ED43-120A
Octave Band Level
UAT06KA
UAT08KA / UAT09KA
UAT10KA / UAT12KA
UAT15KA / UAT18KA
UAT21KA
UAT30H
38
Packaged Air Conditioners UAT-KA Series
ED43-120A
Electric Characteristics
11. Electric Characteristics 11.1
Electric Characteristics 11.1.1 UAT06 ~ 21KA
3D014570B(1)
See next page for Symbol and Notes.
Packaged Air Conditioners UAT-KA Series
39
Electric Characteristics
ED43-120A
3D014570B(2)
UAT30H Cooling
Unit Model
Type
Starting method Volts-Ph-Hz
∗1 Power supply MCA TOCA
MFA
380–3–50 Y1
400–3–50 415–3–50
UAT30H
200–3–50 T0
84.5
84.2
125
Star/Delta
200–3–60
192
196
300
220–3–60 Symbols: MCA TOCA MFA LRA RLA OFM IFM kW FLA
Comp.(each)
OFM (each)
LRA
RLA
kW
FLA
kW
FLA
91
47.8 1.5
3.6
5.5
12.2
2.5
11
5.5
23.2
98
46.5
101
48.5
195
92.6
168
109
190
99.7
IFM
Notes: : Min. Circuit Amps. (A) : Total Overcurrent Amps. (A) : Max. Fuse Amps. (A) : Locked Rotor Amps. (A) : Rated Load Amps. (A) : Outdoor Fan Motor : Indoor Fan Motor : Fan Motor Rated Output (kW) : Full Load Amps. (A)
1. Cooling: Comp, CFM, IFM are in operation. 2. ∗1 shows the power current of cooling operation. 3. RLA is based on the following 27°CDB/19.5°CWB Indoor temp. 35°CDB Outdoor temp. 4. TOCA means the total value of each OC settings. 5. Voltage range Units are suitable for use on electrical systems where voltage supplied to its terminals is not below or above listed range limits. 6. Maximum allowable voltage unbalance between phases is 2 %. 7. MCA/MFA (a) Cooling operation MCA =1.25 × RLA + ea. FLA MFA = 2.25 × RLA + ea. FLA ∗ MFA – Next lower standard fuse ratings ∗ Values with parentheses show that on cooling condition. 8. Select wire size based on the value of MCA. 9. Voltage range is as follows. Type TO
40
Hz
Max. V
50
220
60
242
Min.V 180
Packaged Air Conditioners UAT-KA Series
ED43-120A
Field Wiring
12. Field Wiring 12.1
Field Wiring
Packaged Air Conditioners UAT-KA Series
41
Center of Gravity
ED43-120A
13. Center of Gravity 13.1
Center of Gravity
UAT06KA
UAT08KA UAT09KA UAT10KA UAT12KA
42
Packaged Air Conditioners UAT-KA Series
ED43-120A
Center of Gravity
UAT15KA UAT18KA UAT21KA
Packaged Air Conditioners UAT-KA Series
43
Installation
ED43-120A
14. Installation 14.1
Installation Manual SAFETY CONSIDERATIONS
Please read these “SAFETY CONSIDERATIONS” carefully before installing air conditioning equipment and be sure to install it correctly . After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained.
Meaning of warning and caution symbols WARNING .............Failure to observe a warning may result in death. CAUTION ..............Failure to observe a caution may result in injury or damage to the equipment.
WARNING • Ask your dealer or qualified personnel to carry out installation work. Do not try to install the machine yourself. Improper installation may result in water leakage, electric shocks or fire.
• Perform installation work in accordance with this installation manual. Improper installation may result in water leakage, electric shocks or fire.
• Be sure to use only the specified accessories and parts for installation work. Failure to use the specified parts may result in water leakage, electric shocks, fire or the unit falling.
• Install the air conditioner on a foundation strong enough to withstand the weight of the unit. A foundation of insufficient strength may result in the equipment falling and causing injuries.
• Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes. Improper installation work may result in the equipment falling and causing accidents.
• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by
•
•
• •
•
qualified personnel according to local laws and regulations and this installation manual. An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire. Make sure that all wiring is secured, the specified wires are used, and no external forces act on the terminal connections or wires. Improper connections or installation may result in fire. When wiring the power supply and connecting the wiring between the units and remote controller, position the wires so that the switch box cover can be securely fastened. Improper positioning of the switch box cover may result in electric shocks, fire or the terminals overheating. If the refrigerant gas leaks during installation, ventilate the area immediately . Toxic gas may be produced if the refrigerant gas comes into contact with fire. After completing the installation work, check that the refrigerant gas does not leak. Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker . Before touching electrical parts, turn off the unit. 1PN02530D(1)
44
Packaged Air Conditioners UAT-KA Series
ED43-120A
Installation
CAUTION • Ground the air conditioner .
• •
•
•
Do not connect the ground wire to gas or water pipes, a lightning conductor or a telephone ground wire. Incomplete grounding may result in electric shocks. • Gas pipe — Ignition or an explosion may occur if the gas leaks. • Water pipe — Hard vinyl tubes are not effective grounds. • Lighting conductor or telephone ground wire — Electric potential may rise abnormally if struck by a lightning bolt. Be sure to install an earth leakage breaker . Failure to install an earth leakage breaker may result in electric shocks. While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation. Improper drain piping may result in water leakage and property damage. Install the units, power cord and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise. (Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate noise.) Do not install the air conditioner in the following locations: (a) where a mineral oil mist or an oil spray or vapor is produced, for example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage. (b) where corrosive gas, such as sulfurous acid gas, is produced Corroding copper pipes or soldered parts may result in refrigerant leakage. (c) near machinery emitting electromagnetic waves Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the equipment. (d) where flammable gases may leak, where there are carbon fiber or ignitable dust suspensions in the air, or where volatile flammables such as thinner or gasoline are handled Operating the unit in such conditions may result in fire.
ACCESSORIES Check if the following are included with this unit.
OPTIONS
Name
Installation manual
Screw (M5)
Clamp
Quantity
1 pc.
4 pcs.
4 pcs.
The following optional remote controller is available for this unit. KRC17-2B Remote controller
KRC47-3* KRC47-5
NOTE) • A commercially available remote controller can be used if its specifications are compatible with those shownin the wiring diagram and technical materials. • For UATY_Y19 (in compliance with CE), use KRC17-2B only. * • KRC47-3 is used only for UAT model.
Shape
TAKE SPECIAL CARE DURING INSTALLATION AND CHECK THE FOLLOWING ITEMS AFTER INSTALLATION IS FINISHED. Items to be checked
Result of improper installation
Is the unit securely installed?
The unit may drop, vibrate or make noise.
Is the unit properly insulated?
Condensate may drip.
Is the drain flow smooth?
Condensate may drip.
Does the power supply voltage correspond to that shown on the name plate?
The unit may malfunction or components may burn out.
Is the wiring correct?
The unit may malfunction or components may burn out.
Is the unit safely grounded?
Dangerous electric leakage may result.
Are the wire sizes according to specifications?
The unit may malfunction or components may burn out.
Are the air outlets and inlets of the units free of blockage?
Insufficient cooling may result.
Checked
1PN02530D(2)
Packaged Air Conditioners UAT-KA Series
45
Installation
ED43-120A
1
TRANSPORTING TO INSTALLATION SITE <Do not throw away any of the parts or contents packaged with this unit until installation is completed.> BEFORE INSTALLATION • Decide upon a line of transport. • Leave the unit inside its packaging while transporting, until reaching the installation site. When unpacking is unavoidable, lift the unit using a sling of soft material or protective plates tied together with wire cables to avoid damaging or scratching the unit. • Inspection On receiving the unit, thoroughly check its condition. The unit left the factory in perfect condition, so any damage should be reported without. delay
INSTALLING • Use care not to handle the rear fins or to allow other objects to come in contact with them. • Insert cloth or other soft material between the case of the unit and wire cables to prevent scratches or other damage. • Use protectors to prevent the slings or cables from causing damage. • For safe and accurate installation, the units are designed to be suspended from a hanger as shown UAT15~21K(A), UATY15~21K Wire cables in the illustrations. In addition,this channel base makes it possible to equalize weight of the unit on to the surface of the foundation.Then,fix the unit firmly with anchor bolts.
UAT06K(A) UATY06K Wire cables
Cushioning
UAT08~12K(A), UATY08~12K Wire cables Usetwo wire cables.
Fan cover Handle with care so that it is not damaged.
Wire Cushioning Prepare at the cables installation site. Cushioning
Cushioning Wire cables
2
3
Cushioning
SELECTION OF INSTALLATION SITE • Be certain that sufficient space is left all around the air conditioner as shown in the figure below. If there are any obstacles near the air conditioner, the cooling capacity is reduced and after-sales servicing becomes difficult. • Be certain that the air conditioner has been installed on a flat surface that is strong enough to support the weight of the air conditioner. If the location is not suitable, excessive noise and vibration may occur. • Be certain that the air conditioner has been installed at a location where there is no danger of fire due to leakage of inflammable gas. • Although the unit is waterproof, be sure that there is no water runoff from higher levels or overhangs. • The unit can be set directly on the base. If necessary, use a rubber antivibration cushion (commercially available). • Do not install the unit indoors. Do not position air inlets near exhaust vents or other sources of contaminated . air
INSTALLATION SPACE SERVICE SPACE • Service spacing should be provided as shown in the figure. If there are any obstacles around the unit, air cannot circulate causing the unit to stop frequently, and inspections and after-sales servicing becomes difficult.
UAT06K(A) UATY06K
(Unit : mm) 200 or more 300 or more
600 or more 600 or more
UAT15~21K(A), UATY15~21K
UAT08~12K(A), UATY08~12K 200 or more
300 or more
200 or more
300 or more 500 or more
300 or more
600 or more
600 or more 600 or more 1PN02530D(3)
46
Packaged Air Conditioners UAT-KA Series
ED43-120A
Installation
4
INSTALLATION (1) • Before starting the installation, confirm that the foundation is strong enough so that the unit will not make noise or vibrations. • Secure the unit to the foundation with foundation bolts. 20mm (Prepare 4 sets of M12 foundation bolts with the proper nuts and washers.) • The foundation bolts should extend 20 mm from the surface of the base. (See right Fig.) • Place more than three antivibration pads under a unit per one side. Model
A
B
650
1460
1230
1200
1930
1080
UAT06K(A) UATY06K UAT08~12K(A) UATY08~12K UAT15~21K(A) UATY15~21K
Return air filter • Filters must be installed in duct work in the field. Do not operate the unit without a return air filter installed. • The air filter must be installed so that there is enough space for maintenance.
Filter (commercially available)
Compressor
CAUTION (2) • Remove the yellow packing brace from the compressor as shown in the figure at the right. • Retighten the installation bolts for the compressor. • Two packing braces are attached to the front of each compressor.
Packing brace (Yellow)
Bolt
CAUTION • Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes. Improper installation work may result in the equipment falling and causing an accident. • Make sure that the drainage of the unit will not inconvenience neighbors or harm the environment. Construct a drainage ditch if necessary. • If the unit is to be installed on a rooftop, make certain that it will be capable of withstanding the weight of the unit and that measures have been taken to ensure watertightness. 1PN02530D(4)
Packaged Air Conditioners UAT-KA Series
47
Installation
ED43-120A
UAT06 ~ 21KA
3VA08895
UAT30H
3VA08896
48
Packaged Air Conditioners UAT-KA Series
ED43-120A
Installation
5
DRAIN PIPING • Provide a trap of over 50 mm in the drain piping as a water seal. • A drain plug is installed on the left side of the unit. Depending on your installation setup, install the plug on the opposite side of the drain piping (except on the UAT(Y)06K). • After finishing the drain piping, use insulation material to wrap the drain socket that is located on the opposite side of the drain piping.
UAT06K(A) UATY06K
UAT08~12K(A), UATY08~12K
UAT15~21K(A), UATY15~21K
Drain trap 50(Unit : mm) or more Drain trap
Drain trap
50(Unit : mm) or more
50(Unit : mm) or more
Drain plug
Drain plug
6
Drain plug
ELECTRICAL WIRING CAUTION • All wiring components and materials that are purchased commercially must comply with the applicable local and national codes. • Use copper conductors only. • For details, see the wiring diagram. • Install circuit breakers for safety. • All field wiring and components must be provided by a licensed electrician. • The unit must be grounded in compliance with applicable local and national codes. • Use a ground wire of 100Ω or less • Electrical wiring must be carried out by qualified personnel. • Do not connect the earth wire to gas pipes, water pipes, lighting conductors or telephone earth wires. • Gas pipe — Ignition or an explosion may occur if the gas leaks. • Water pipe — Hard vinyl tubes are not effective grounds. • Lighting conductor or telephone ground wire —
Electric potential may rise abnormally if struck by a lightning bolt. WARNING Use ring type crimp style terminal for connection to power supply terminal block. If is not used, satisfy the following conditions: • Do not connect wires of different gauge to the same power supply terminal. (Looseness in the connection may cause overheating.) • When connecting wires of the same gauge, connect them according to the righthand figure.
Ring type crimp style terminal Wire Connect wires of the same gauge to both sides
Do not connect wires of the same gauge to one side
Do not connect wires of different gauges
1PN02530D(5)
Packaged Air Conditioners UAT-KA Series
49
Installation
ED43-120A
Electrical connections • After the unit has been positioned, the necessary electrical connections must be made between the unit and the power supply. • A quick visual inspection must be made to check that the circuits have not been damaged while transporting. 1) Check that all wires are securely screwed into their terminals. 2) Check that the voltage and frequency of the power supply corresponds to that specified on the unit itself.
Field power supply • When installing the unit, install a disconnect switch in accordance with the national and local electrical codes. • All field wiring must comply with national and local electrical requirements.
UAT06K(A) UATY06K
Field control wiring • Use a DAIKIN optional accessory thermostat. • Install the thermostat on a solid wall within the air-conditioned area so that it can detect the average room temperature. • Use a 0.75 mm2 wire when connecting the remote controller to the unit.
Fix the power supply and control wire to the unit with the enclosed clamp to prevent them from contacting the discharge pipe.
Power supply and control wire connection port
Power supply and control wire
UAT08~12K(A), UATY08~12K Switch box
Power supply and control wire Discharge pipe Compressor
UAT15~21K(A), UATY15~21K
Power supply and control wire connection port
Rear view of UAT15~21K(A), UATY15~21K
Power supply and connection port (UATY models only)
Control wire connection port (UAT models only)
Power supply and control wire
Power supply connection port (UAT models only)
Power supply Control wire
Fix the power supply and control wire to the unit with the enclosed clamp. 1PN02530D(6)
50
Packaged Air Conditioners UAT-KA Series
ED43-120A
Installation
Model
Straight Cooling Type
Heat Pump Type
Field Fuse
UAT06KAY1
UATY06KY1
UAT08KAY1
UATY08KY1
UAT08KY1
UAT09KAY1
UATY09KY1
35
—
UAT10KAY1
UATY10KY1
40
UAT10KY1
—
—
45
—
UAT15KAY1
UATY15KY1
50
UAT06KY1
—
—
60
—
UAT18KAY1
UATY18KY1
70
UAT20KY1
UAT21KAY1
UATY21KY1
80
UAT06KTAL
UAT06KATAL UATY06KTAL
45
—
UAT08KATAL UATY08KTAL
50
UAT08KTAL
UAT09KATAL UATY09KTAL
60
—
—
UAT12KATAL UATY12KTAL
80
—
UAT15KATAL UATY15KTAL
90
—
—
All electrical wiring components which are purchased commercially must meet or exceed the applicable standards for the country or region in which the unit is being installed.
H05VV-U4G
110
UAT18KATAL UATY18KTAL UAT20KTAL
UAT21KATAL UATY21KTAL
125
UAT06KYAL
UAT06KAYAL UATY06KYAL
25
—
UAT08KAYAL UATY08KYAL
30
UAT08KYAL
UAT09KAYAL UATY09KYAL
35
—
UAT10KYAL
—
UAT12KAYAL UATY12KYAL
45
—
UAT15KAYAL UATY15KYAL
50
—
UL1015AWG18 or equivalent
0.75 mm2
40
—
UAT15KYAL
Size
Wire Type
H05VV-U5G
70
—
UAT15KTAL
Size
Wire Type
25
UAT15KY1
UAT10KTAL
Wiring Between Unit and the Remote Controller
Power Supply
—
H05VV-U5G
60
—
UAT18KAYAL UATY18KYAL
70
UAT20KYAL
UAT21KAYAL UATY21KYAL
80
• Use the enclosed clamps to attach the wiring to the mounted clamps shown in the following illustrations.
UAT06~12K(A), UATY06~12K <Y1 Model> Power supply 50 Hz 3N 380 - 415 V
<TAL Model> Power supply 60 Hz 3 220 V
NOTE) ** Enclosed clamp Mounted clamp
Main switch fuse
Main switch fuse
Main switch fuse
** *
**
** *
**
<YAL Model> Power supply 60Hz 3N 380 V
NOTE) * In case of UAT_K
* **
In case of UAT_KA P2 P11 P6 P1
**
Remote controller
Unit Remote controller
Unit Remote controller
In case of UATY_K P2 P17 P6 P10 P13 P11 P1
Unit
1PN02530D(7)
Packaged Air Conditioners UAT-KA Series
51
Installation
ED43-120A
UAT15~21K(A), UATY15~21K <TAL Model> Power supply 3 60 Hz 220 V
<Y1 Model> Power supply 3N 50 Hz 380 - 415 V
Main switch fuse
Main switch fuse
Main switch fuse
** *
**
** *
**
<YAL Model> Power supply 3N 60 Hz 380 V
NOTE) * In case of UAT_K
* **
In case of UAT_KA P2 P11 P8 P6 P1
**
Remote controller
Remote controller
In case of UATY_K P2 P17 P6 P7 P13 P11 P15 P8 P1
Remote controller
Unit
Unit
Unit
CAUTION (Y1 Model Only) • Make sure that the phase reversal protector’s terminal connection is converted when switching to a 400-volt or 415-volt connection.
380-volt connection (factory setting)
Convert 400-volt and 415-volt connection
7
• Failing to convert to the proper voltage will cause serious damage to the unit.
OPERATION TEST • Make sure that all installation procedures have been completed according to the unit’s specifications and the remote controller’s installation manuals. • Connect the power at least 6 hours before starting.( UATY models only) • Select the lowest temperature setting on the remote controller. (For the cooling function) • Turn on the remote controller to check the air flow and cooling functions. • After completing the operation test, set the remote controller to the desired temperature. • Give the installation and operation manual of the remote controller to the customer and explain how to operate the unit.
NOTE) The three-minute timer delays the restart operation. 1PN02530D(8)
52
Packaged Air Conditioners UAT-KA Series
ED43-120A
Foundation and Service Space of UAT30H
15. Foundation and Service Space of UAT30H 15.1
UAT30H
Foundation
Notes:
Model
A
B
C
D
E
F
UAT30H
1580
2860
1380
2Ă&#x2014;1200=2400
100
Max.40
1. Provide a concrete flat and level base. 2. Provide a ditch around the unit. 3. In case of roof-top installation, check the strength and water-proof of the roof.
Service Space
Packaged Air Conditioners UAT-KA Series
53
Foundation and Service Space of UAT30H
15.2
ED43-120A
How to Install Pulley
UAT06KA UAT08KA UAT09KA UAT10KA UAT12KA
UAT06KA
L = 5mm
UAT08KA UAT09KA UAT10KA
L = 6mm
UAT12KA
UAT15KA UAT18KA UAT21KA
UAT15KA UAT18KA UAT21KA
54
L = 4mm L = 8mm
Packaged Air Conditioners UAT-KA Series
ED43-120A
Foundation and Service Space of UAT30H
UAT30H L = 8mm, W = 22.6N [ 2.3kgf ] V-BELT TEMSION
V-BELT
0±1.5
REFERENCE PLANE OF PULLEY
FAN PULLEY
FAN MOTOR PULLEY
L
z
Packaged Air Conditioners UAT-KA Series
W = 22.6N (2.3kgf)
55
Optional Accessories
ED43-120A
16. Optional Accessories 16.1
Option List Applicable Model
Option
Remark
Mechanical Type
With 3 minutes timer wired type
Remote Controller Digital Type
Central Control Adapter Kit
Y1 Y1 Y1 Y1 Y1 Y1 Y1 UAT06KATAL UAT08KATAL UAT09KATAL UAT10KAY1 UAT12KATAL UAT15KATAL UAT18KATAL UAT21KATAL UAT30H YAL YAL YAL YAL YAL YAL YAL TO
With 3 minutes timer wired type
KRC47-3
KRC17-2B
KRC17-2B ∗
KRC47-5
KRC47-5 ∗
KRC17-2B
DTA107A55 C : 3D020623
Note:
56
In case of using KRC17-2B or field supplied remote controller, Three-Minutes Timer (KTA19A1) is required for to avoid frequent ON/OFF operation of compressor. ∗ Capacity steps is available for 100-50-0% operation.
Packaged Air Conditioners UAT-KA Series
ED43-120A
16.2
Optional Accessories
Remote Controller
KRC47-3
KRC47-3 contains the following parts, and they are packed in one carton. 1. Remote Controller
2. Holder
220
150
80
15
3. Control Board (Box)
4-Ø6HOLE 200
60
240
4. Wire Cable ······ Cable length : 4m (8m or 15m will be available on request) Connecting cable between 1 and 3
Packaged Air Conditioners UAT-KA Series
57
Optional Accessories
KRC47-5
ED43-120A
1. Digital Remote Controller
325
165
80
15
2. Control Board (Box)
4-Ã&#x2DC;6HOLE 310
70
345
(P0007)
3. Wire Cable......Cable length : 4m Connecting cable between 1 and 2.
KRC17-2B
58
Remote Controller (Mechanical Type) : CE Applied Model
Packaged Air Conditioners UAT-KA Series
ED43-120A
Optional Accessories
16.2.1 Internal Wiring Diagrams KRC47-3
(UAT15~21KA)
P11 P8
P6
P2
P1
(UAT06~12KA)
P11
P6
P2
P1
P1
P3
P5
P6
CAUTION
ON
ELECTRONIC CONTROL
TEMPERATURE CONTROL
OFF
Check each identification labels before connecting wires.
KRC47-5
Packaged Air Conditioners UAT-KA Series
59
Optional Accessories
ED43-120A
KRC17-2B
A
B
P2
P6
P2
P6
A
J
E
C
G
H
(UAT30H)
P11
B ON
J OFF COOL
C
D
E
HEAT
F
G
H
P11
(UAT06~12KA)
P8
(UAT15~21KA)
I
H
E-F E-G E-H E-I L H TEMPERATURE Note:
60
For UAT30H, Connect the wiring to meet the terminal symbol.
Packaged Air Conditioners UAT-KA Series
ED43-120A
16.3
Optional Accessories
Details of DTA107A55
16.3.1 Features
Packaged Air Conditioners UAT-KA Series
61
Optional Accessories
ED43-120A
16.3.2 Combination of Remote controllers with DTA107A55.
Kit
Unified
(P0020)
16.3.3 Functions available by each combination
Functions
(P0021)
62
Packaged Air Conditioners UAT-KA Series
ED43-120A
Optional Accessories
16.3.4 Dimension
6 5 4 3 2 1 ITEM
FIXING HOLE EARTH TERMINAL (FOR SHIELD CODE) EARTH TERMINAL (FOR EL. COMPO. BOX ASSY) WIRING INTAKE (FOR THERMISTOR) WIRING INTAKE (FOR CONTROLLER) WIRING INTAKE (FOR AIR CONDITIONER) PARTS NAME
Packaged Air Conditioners UAT-KA Series
4-φ7 (USING M5 BOLTS) M4 (IN THE EL. COMPO. BOX ASSY) M4 (IN THE EL. COMPO. BOX ASSY) (φ8) (φ15) (φ20) REMARK
63
Optional Accessories
ED43-120A
16.3.5 Wiring Diagram With Optional Central Control Adapter UAT06KAY1,YAL + DTA107A55
64
Packaged Air Conditioners UAT-KA Series
ED43-120A
Optional Accessories
UAT06KATAL + DTA107A55
Packaged Air Conditioners UAT-KA Series
65
Optional Accessories
ED43-120A
UAT08KAY1, YAL + DTA107A55 UAT09KAY1, YAL + DTA107A55 UAT10KAY1, YAL + DTA107A55
66
Packaged Air Conditioners UAT-KA Series
ED43-120A
Optional Accessories
UAT08KATAL + DTA107A55 UAT09KATAL + DTA107A55 UAT12KATAL + DTA107A55
Packaged Air Conditioners UAT-KA Series
67
Optional Accessories
ED43-120A
UAT15KATAL + DTA107A55 UAT18KATAL + DTA107A55 UAT21KATAL + DTA107A55
68
Packaged Air Conditioners UAT-KA Series
ED43-120A
Optional Accessories
UAT15KAY1, YAL + DTA107A55 UAT18KAY1, YAL + DTA107A55 UAT21KAY1, YAL + DTA107A55
Packaged Air Conditioners UAT-KA Series
69
Wiring Modification
ED43-120A
17. Wiring Modification 17.1
Wiring for operating signal and alarm
UAT06KAY1 UAT06KAYAL
70
Packaged Air Conditioners UAT-KA Series
ED43-120A
Wiring Modification
UAT08KAY1 / UAT08KAYAL UAT09KAY1 / UAT09KAYAL UAT10KAY1 / UAT12KAYAL
Packaged Air Conditioners UAT-KA Series
71
Wiring Modification
ED43-120A
UAT15KAY1 / UAT15KAYAL UAT18KAY1 / UAT18KAYAL UAT21KAY1 / UAT21KAYAL
72
Packaged Air Conditioners UAT-KA Series
ED43-120A
Wiring Modification
UAT30HY1
Packaged Air Conditioners UAT-KA Series
73
Wiring Modification
ED43-120A
UAT06KATAL
74
Packaged Air Conditioners UAT-KA Series
ED43-120A
Wiring Modification
UAT08KATAL UAT09KATAL
Packaged Air Conditioners UAT-KA Series
75
Wiring Modification
ED43-120A
UAT12KATAL
76
Packaged Air Conditioners UAT-KA Series
ED43-120A
Wiring Modification
UAT15KATAL UAT18KATAL UAT21KATAL
Packaged Air Conditioners UAT-KA Series
77
Wiring Modification
ED43-120A
UAT30HTO
78
Packaged Air Conditioners UAT-KA Series
The air conditioners manufactured by Daikin Industries have received ISO 9001 certification for quality assurance. Certificate Number. JMI-0107 JQA-0495 JQA-1452
All Daikin Industries locations and subsidiaries in Japan have received environmental management system standard ISO 14001 certification. Daikin Industries, Ltd. Domestic Group Certificate Number. EC99J2044
About ISO 14001 ISO 14001 is the standard defined by the International Organization for Standardization (ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the requirements of ISO 14001.
Dealer Head Office: Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome, Kita-ku, Osaka, 530-8323 Japan Tokyo Office: JR Shinagawa East Bldg., 18-1, Konan 2-chome, Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/ c All rights reserved
The specifications, designs, and information in this brochure are subject to change without notice.
This book is made of recycled paper.
ED 43-120A Printed in Japan 03/2005 FS