ED 21 - 301
Split System Air Conditioners SkyAir (Pair and Twin-Triple-Double Twin)
LU Series — Cooling Only —
ED21-301
SkyAir LU Series (Pair) — Cooling Only — ..................................... 1 1. Model Name and Power Supply..............................................................2 1.1 Pair Series................................................................................................2
2. External Appearance...............................................................................4 2.1 External Appearance................................................................................4
3. Functions.................................................................................................5 3.1 Indoor Units + Outdoor Units (35-60G(A), 71-140LU)..............................5
4. Specifications ..........................................................................................8 4.1 50Hz (General).........................................................................................8 4.2 50Hz (Complied with Australian Standard) ............................................19 4.3 60Hz .......................................................................................................21
5. Dimensions and Service Space ............................................................27 5.1 5.2 5.3 5.4
Indoor Unit..............................................................................................27 Remote Controller ..................................................................................42 Outdoor Unit ...........................................................................................45 Installation Service Space for R71LU, 100LU, 125LU, 140LU...............49
6. Piping Diagrams....................................................................................51 6.1 Indoor Unit + Outdoor Unit .....................................................................51
7. Wiring Diagrams....................................................................................54 7.1 Indoor Unit..............................................................................................54 7.2 Outdoor Units .........................................................................................67
8. Capacity Tables ....................................................................................74 8.1 8.2 8.3 8.4
50Hz (General).......................................................................................74 50Hz (Complied with Australian Standard) ............................................79 60Hz .......................................................................................................82 Capacity Correction Factor by The Length of Refrigerant Piping...........87
9. Operation Limits ....................................................................................88 9.1 Operation Limits .....................................................................................88
10.Sound Level ..........................................................................................89 10.1 Overall Sound Level ...............................................................................89 10.2 Octave Band Level .................................................................................90
11.Fan Performance ..................................................................................94 11.1 Fan Performance....................................................................................94
12.Electric Characteristics..........................................................................96 12.1 50Hz .......................................................................................................96 12.2 60Hz .......................................................................................................98
13.Option List .............................................................................................99 13.1 LU Series................................................................................................99
14.Field Piping and Wiring .......................................................................103 14.1 Field piping ...........................................................................................103 14.2 Field Wiring ..........................................................................................106
SkyAir LU Series (Twin, Triple, Double Twin) — Cooling Only — ........................................................... 107 1. Features ..............................................................................................108 1.1 What are Twin, Triple, Double Twin Systems? ....................................108
2. Model Name and Power Supply..........................................................109 2.1 Twin, Triple and Double Twin System..................................................109 Table of Contents
i
ED21-301
3. External Appearance...........................................................................111 3.1 External Appearance............................................................................111
4. Specifications ......................................................................................112 4.1 50Hz .....................................................................................................112 4.2 60Hz .....................................................................................................118
5. Dimensions and Service Space ..........................................................124 5.1 5.2 5.3 5.4 5.5
Indoor Unit............................................................................................124 Remote Controller ................................................................................132 Outdoor Unit .........................................................................................134 Installation Service Space for R71LU, 100LU, 125LU, 140LU.............137 Installation Service Space for R200KU, 250KU ...................................139
6. Piping Diagrams..................................................................................140 6.1 Twin......................................................................................................140 6.2 Triple ....................................................................................................145 6.3 Double Twin .........................................................................................147
7. Wiring Diagrams..................................................................................148 7.1 Indoor Unit............................................................................................148 7.2 Outdoor Unit .........................................................................................150
8. Capacity Tables ..................................................................................155 8.1 50Hz .....................................................................................................155 8.2 60Hz .....................................................................................................158 8.3 Capacity Correction Factor by The Length of Refrigerant Piping.........162
9. Operation Limits ..................................................................................163 9.1 Operation Limits ...................................................................................163
10.Sound Level ........................................................................................164 10.1 Overall Sound Level .............................................................................164 10.2 Octave Band Level ...............................................................................165
11.Electric Characteristics........................................................................167 11.1 50Hz .....................................................................................................167 11.2 60Hz .....................................................................................................168
12.Option List ...........................................................................................170 12.1 LU Series..............................................................................................170
13.Field Piping and Wiring .......................................................................172 13.1 Field Piping...........................................................................................172 13.2 Field Wiring ..........................................................................................175
Detail Information of Options SkyAir LU Series ........................ 177 1. Remote Controller ...............................................................................178 1.1 1.2 1.3 1.4 1.5
Remote Controller, Timer, Adaptor List................................................178 Wired Remote Controller......................................................................178 Wireless Remote Controller .................................................................183 Various Control by Liquid Crystal Remote Controller...........................185 BRC15A61 – Set Back Time Clock ......................................................189
2. Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C] .......................192 2.1 2.2 2.3 2.4 2.5
ii
BYC125K – W1 – Decoration Panel.....................................................192 KDBHJ55K160 – Sealing member of air discharge outlet....................195 KDBJ55K160W – Panel spacer ...........................................................197 KDDP55D160(K) – Fresh Air Intake Kit ...............................................199 KDDJ55X160 – Fresh Air Intake Kit .....................................................202
Table of Contents
ED21-301
2.6 KAFP556D80 · 160 – High Efficiency Filter (Including Filter Chamber) KAFP557D80 · 160 – High Efficiency Filter (Including Filter Chamber)....................................................................204 2.7 KAFJ552K80 · 160 – High Efficiency Filter (Replacement) KAFJ553K80 · 160 – High Efficiency Filter (Replacement)..................204 2.8 KRP1B98 – Installation Box for Adaptor PCB ......................................204 2.9 KDDFP55D160 – High-Efficiency Filter Chamber................................205 2.10 KAFJ551K160 – Long-Life Filter for Decoration Panel (Replacement) ........................207 2.11 KAFP55D160, KAFJ55K160H (Replacement) – Ultra Long-Life Filter (Including Filter Chamber)....................................................................207 2.12 KKSJ55K160 – Chamber Connection Kit.............................................207 2.13 KDJ55K80 · 160 – Branch Duct Chamber............................................208 2.14 Dimensions with Optional Kit................................................................213
3. Ceiling Mounted Cassette Corner Type [FH(Y)K] ...............................217 3.1 3.2 3.3 3.4 3.5 3.6
BYK45FJW1 · 71FJW1 – Decoration panel .........................................217 KPBJ52F56W · 80W – Panel Specer...................................................221 KDBJ52F56W · 80W – Air Discharge Blind Panel ...............................225 KAFJ521F56 · 80 – Replacement Long Life Filter ...............................232 K-HV7AW · 9AW – Discharge Grille.....................................................232 KFDJ52F56 · 80 – Flexible Duct with Shutter ......................................233
4. Ceiling Mounted Built-In Type [FH(Y)B] ..............................................240 4.1 BYBS45DJW1 – Decoration panel BYBS71DJW1 – Decoration panel BYBS125DJW1 – Decoration panel.....................................................240 4.2 KTBJ25K56W · 80W · 160W – Service access panel ..........................244 4.3 KAFJ252L56 · 80 · 160 – High-Efficiency Filter KAFJ253L56 · 80 · 160 – High-Efficiency Filter....................................245 4.4 KAFJ251K56 · 80 · 160 – Replacement long-life filter..........................246 4.5 KAJ25L56D · 80D · 160D – Filter Chamber for Bottom Suction...........246 4.6 KAJ25L56B · 80B · 160B – Filter Chamber for Rear Suction...............247 4.7 KSAJ25K56 · 80 ·160 – Canvas Duct ..................................................250 4.8 K-DG4BW · 5BW · 7BW · 9BW – Air Discharge Unit-Discharge Grille+Discharge Chamber K-DGC4B · 5B · 7B · 9B – Air Discharge Unit-Discharge Grille+Discharge Chamber.................251 4.9 K-DDV20A – Branch Duct ....................................................................253 4.10 K-FDK151B · 152B · 153B · 154B · 155B · 156B – Flexible Duct K-FDK201B · 202B · 203B · 204B · 205B · 206B – Flexible Duct......................................................................................254 4.11 KBBJ25K56 · 80 · 160 – Blind Board ...................................................255 4.12 KDAJ25K56 · 71 · 140 – Adaptor for Discharge...................................255 4.13 KDJ2507K56 · 80 · 160 – Flange for Suction .......................................256 4.14 Optional Kit Installation Drawing ..........................................................257
5. New Ceiling Suspended Cassette Type [FUY] ...................................258 5.1 5.2 5.3 5.4 5.5 Table of Contents
KDBHJ49F80 · 140 – Sealing Member of Air Discharge Outlet ...........258 KDBTJ49F80 · 140 – Decoration Panel for Air Discharge ...................258 KDGJ49F80 · 140 – Vertical Flap Kit ...................................................258 KAFJ495F140 – Replacement Long Life Filter ....................................259 KHFJ49F80 · 140 – L Connection Piping Kit........................................259 iii
ED21-301
5.6 KRP1B97 – Installation Box for Adaptor PCB ......................................259
6. Ceiling Suspended Type [FH(Y)] ........................................................260 6.1 6.2 6.3 6.4
KAFJ501D56 · 80 · 112 · 160 – Replacement Long Life Filter .............260 KDU50B50 · 71 · 125VE – Drain Pump Kit ..........................................260 KHFJ5F50 · 60 · 80 · 160 – L-Type Piping Kit......................................261 KRP1C93 – Installation Box for Adaptor PCB......................................261
7. Floor Standing Type [FVY]..................................................................262 7.1 KAFJ95L160 – Replacement Long Life Filter.......................................262 7.2 KRP4A95 – Installation Box for Adaptor PCB ......................................262
8. Outdoor Unit........................................................................................263 8.1 8.2 8.3 8.4
iv
KIS95 – Drain Piping Kit.......................................................................263 KKPJ5F180 – Central Drain Plug.........................................................263 KRK5F80V1 · 140V1 · 160V1 – Year Round Cooling Kit .....................264 KHR58C21, KHD58C21A, KHD58C23A, KHD58C24A, KHD58D31, KHD58D33, KHRJ5F224F, KHRJ5F280F – Refrigerant Branch Piping .................................................................265
Table of Contents
ED21-301
SkyAir LU Series (Pair) — Cooling Only —
1
Model Series Class Indoor Units
35
45
50
60
71
100
125
140
35K
—
50K
60K
—
—
—
—
—
—
—
—
71K
100K
125K
140K
35F
45F
—
60F
—
—
—
—
—
—
—
—
71FJ
—
—
—
35F
45F
—
60F
—
—
—
—
FHYB
—
—
—
—
71F
100F
125F
—
FUY
—
—
—
—
71FJ
100FJ 125FJ
—
35B
—
50B
60B
—
—
—
—
FHY
—
—
—
—
71B
100B
125B
—
FAY
—
—
—
—
71L
100FA
—
—
FVY
—
—
—
—
71LA
35G
50G
FHC FHYC FHK FHYK FHB
FH
Outdoor R Units
50G(A) 60G(A) 71LU
100LA 125LA
—
100LU 125LU 140LU
Cautions 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
SkyAir LU Series – Cooling Only –
1
Model Name and Power Supply
ED21-301
1. Model Name and Power Supply 1.1
Pair Series
1.1.1
50Hz (General) Indoor Units
Notes:
2
Outdoor Units
FHC35KVE
R35GV1
FHC50KVE
R50GV1
FHC60KVE
R60GV1
FHYC71KVE
R71LUV1∗
FHYC100KVE
R100LUV1∗
FHYC71KVE
R71LUY1∗
FHYC100KVE
R100LUY1∗
FHYC125KVE
R125LUY1∗
FHYC140KVE
R140LUY1∗
FHK35FV1
R35GV1
FHK45FV1
R50GV1
FHK60FV1
R60GV1
FHYK71FJV1∗
R71LUV1∗
FHYK71FJV1∗
R71LUY1∗
FHB35FV1
R35GV1
FHB45FV1
R50GV1
FHB60FV1
R60GV1
FHYB71FV1
R71LUV1∗
FHYB100FV1
R100LUV1∗
FHYB71FV1
R71LUY1∗
FHYB100FV1
R100LUY1∗
FHYB125FV1
R125LUY1∗
FUY71FJV1
R71LUV1∗
FUY100FJV1
R100LUV1∗
FUY71FJV1
R71LUY1∗
FUY100FJV1
R100LUY1∗
FUY125FJV1
R125LUY1∗
FH35BVE
R35GV1
FH50BVE
R50GV1
FH60BVE
R60GV1
FHY71BVE
R71LUV1∗
FHY100BVE
R100LUV1∗
FHY71BVE
R71LUY1∗
FHY100BVE
R100LUY1∗
FHY125BVE
R125LUY1∗
FAY71LVE∗
R71LUV1∗
FAY100FAVE
R100LUV1∗
FAY71LVE∗
R71LUY1∗
FAY100FAVE
R100LUY1∗
FVY71LAVE
R71LUV1∗
FVY100LAVE
R100LUV1∗
FVY71LAVE
R71LUY1∗
FVY100LAVE
R100LUY1∗
FVY125LAVE
R125LUY1∗
Power Supply
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1φ, 220~240V, 50Hz 3φ, 380~415V, 50Hz 1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
1. ∗ : New Model or Changed Model 2. Power Supply Intake : Outdoor Unit
SkyAir LU Series – Cooling Only –
ED21-301
1.1.2
Model Name and Power Supply
50Hz (Complied with Australian Standard) Indoor Units
1.1.3
Outdoor Units
FHC35KVE
R35GV1A
FHC50KVE
R50GAV1A∗
FHC60KVE
R60GAV1A∗
FH50BVE
R50GAV1A
FH60BVE
R60GAV1A
1
Power Supply
1φ, 240V, 50Hz
60Hz Indoor Units FHC50KVE
Notes:
Outdoor Units
Power Supply
R50GVAL
FHC60KVE
R60GVAL
FHYC71KVE
R71LUVAL∗
1φ, 220V, 60Hz
FHYC100KVE
R100LUVAL∗
FHYC125KVE
R125LUTAL∗
3φ, 220V, 60Hz
FHYC125KVE
R125LUYAL∗
3φ, 380V, 60Hz
FHYC140KVE
R140LUTAL∗
3φ, 220V, 60Hz
FHYC140KVE
R140LUYAL∗
3φ, 380V, 60Hz
FH50BVE
R50GVAL
FH60BVE
R60GVAL
FHY71BVE
R71LUVAL∗
1φ, 220V, 60Hz
FHY100BVE
R100LUVAL∗
FHY125BVE
R125LUTAL∗
3φ, 220V, 60Hz
FHY125BVE
R125LUYAL∗
3φ, 380V, 60Hz
FAY71LVE∗
R71LUVAL∗
FAY100FAVE
R100LUVAL∗
FVY71LAVE
R71LUVAL∗
FVY100LAVE
R100LUVAL∗
FVY125LAVE
R125LUTAL∗
3φ, 220V, 60Hz
FVY125LAVE
R125LUYAL∗
3φ, 380V, 60Hz
1φ, 220V, 60Hz 1φ, 220V, 60Hz
1. ∗ : New Model or Changed Model 2. Power Supply Intake : Outdoor Unit
SkyAir LU Series – Cooling Only –
3
External Appearance
ED21-301
2. External Appearance 2.1
External Appearance
Indoor Units
FH(Y)C–K
FH(Y)K–F(J)
FUY–FJ
FH(Y)–B
FAY71L
FAY100FA
FH(Y)B–F
FVY–LA
Remote Controller
Wired Type Wireless Type
Outdoor Units
R35G R50G(A)
4
R60G(A)
R71LU
R100LU
R125LU
R140LU
SkyAir LU Series – Cooling Only –
ED21-301
Functions
3. Functions 3.1
1
Indoor Units + Outdoor Units (R35-60G(A), R71-140LU) Items Model Type Main Improvement
35~60K
71~140K
Indoor Units
Existing
Existing
Outdoor Units
Existing
New
Appearance Improved
{
{
Reduction of Operation Sound
{
{
Auto Restart
{
{
Fan Operation Mode
{
{
Wired Type
{
{
Wireless Type
{
{
Auto Swing Function
{
{
Ceiling Soiling Prevention
{
{
Wired Type
{
{
Wireless Type
—
—
LCD Remote Controller (Option)
For Comfortable Air Conditioning
For Easy Construction and Maintenance
For Flexible Control
Ceiling Mounted Cassette (FH(Y)C)
Improved Points and Functions
Two Select Thermo Sensor Program Dry
{
{
High Fan Speed Mode
—
—
High Ceiling Application
{
{
Low Ambient Temperature Kit (Option)
—
{
Timer Selector
{
{
Fresh Air Intake Directly from The Unit
{
{
Drain Pump
{
{
Long Life Filter
{
{
Ultra-Long Life Filter (Option)
{
{
Mold Resistant Treatment for Filter
{
{
Filter Sign
{
{
Mold Resistant Drain Pan
{
{
Emergency Operation
{
{
Self Diagnoses Function
{
{
Low Gas Pressure Detection (R)
—
{ (71~140)
Set Back Time Clock
{
{
Double Remote Control
{
{
Group Control by 1 Remote Controller
{
{
Control by D-BACS
{
{
Remote/Centralized Control
{
{
z : Improved Points and Functions { : Functions — : No Functions
SkyAir LU Series – Cooling Only –
5
Functions
ED21-301
Items
Model Type
Ceiling Mounted Cassette Corner (FH(Y)K)
Ceiling Mounted Built-In (FH(Y)B)
35~60F
71FJ
35~60F
71~ 125F
71~125FJ
Indoor Units
Existing
New
Existing
Existing
Existing
Outdoor Units
Existing
New
Existing
New
New
{
{
{
{
—
{
{
{
{
—
Auto Restart
{
{
{
{
{
Fan Operation Mode
{
{
{
{
{
LCD Remote Controller (Option)
{
{
{
{
{
Auto Swing Function
{
{
—
—
{
Ceiling Soiling Prevention
{
{
—
—
{
Wired Type
{
{
{
{
{
Wireless Type
Improved Points and Functions
Appearance Improved
Main Improvement Reduction of Operation Sound
For Comfortable Air Conditioning
For Easy Construction and Maintenance
For Flexible Control
Two Select Thermo Sensor
New Ceiling Suspended (FUY)
—
—
—
—
—
Program Dry
{
{
{
{
{
High Fan Speed Mode
—
—
—
—
—
High Ceiling Application
{
{
—
—
{
Low Ambient Temperature Kit (Option)
—
{
—
{
{
Timer Selector
{
{
{
{
{
Fresh Air Intake Directly from The Unit
{
{
{
{
—
Drain Pump
{
{
{
{
{
Long Life Filter
{
{
{
{
{
Ultra-Long Life Filter (Option)
—
—
—
—
—
Mold Resistant Treatment for Filter
{
{
{
{
{
Filter Sign
{
{
{
{
{
Mold Resistant Drain Pan
{
{
{
{
{
Emergency Operation
{
{
{
{
{
Self Diagnoses Function
{
{
{
{
{
{ {(71~125) (71~125)
Low Gas Pressure Detection (R)
—
{(71)
—
Set Back Time Clock
{
{
{
{
{
Double Remote Control
{
{
{
{
{
Group Control by 1 Remote Controller
{
{
{
{
{
Control by D-BACS
{
{
{
{
{
Remote/Centralized Control
{
{
{
{
{
z : Improved Points and Functions { : Functions — : No Functions
6
SkyAir LU Series – Cooling Only –
ED21-301
Functions
Items
Improved Points and Functions
Wall Floor Mounted Standing (FAY) (FVY)
Ceiling Suspended (FH(Y)) 35, 50B
60, 71B
100B, 125B
71L, 100FA
71~125LA
Indoor Units
Existing
Existing
Existing
New(71)
Existing
Outdoor Units
Existing
New(71)
New
New
New
{
{
{
{
{
Main Improvement Reduction of Dimensions or Weight Reduction of Operation Sound
{
{
{
{
{
{
{
{
{
{
Auto Restart Fan Operation Mode
{
{
{
{
{
{
{
{
{
{
LCD Remote Controller (Option) Wired
{
{
{
{
{
LCD Remote Controller (Option) Wirelless
{
{
{
{
—
Model Type
Appearance Improved
For Comfortable Air Conditioning
For Easy Construction and Maintenance
For Flexible Control
Auto Swing Function
{
{
{
{
{
Ceiling Soiling Prevention
—
—
—
—
—
Wired Type
{
{
{
{
{
Wireless Type
—
Two Select Thermo Sensor
—
—
—
—
Program Dry
{
{
{
{
{
High Fan Speed Mode
—
—
—
{
— —
High Ceiling Application
{
{
{
—
Low Ambient Temperature Kit (Option)
—
{
{
{
{
Timer Selector
{
{
{
{
{
Fresh Air Intake Directly from The Unit
—
—
—
—
—
Drain Pump Kit (Option)
{
{
{
—
—
Long Life Filter
{
{
{
—
{
Ultra-Long Life Filter (Option)
—
—
—
—
—
Mold Resistant Treatment For Filter
{
{
{
{
{
Filter Sign
{
{
{
{
{
Mold Resistant Drain Pan
{
{
{
{
—
Emergency Operation
{
{
{
{
{
Self Diagnoses Function
{
{
{
{
{
{ { { (100, 125) (71, 100) (71~125)
Low Gas Pressure Detection (R)
—
{(71)
Set Back Time Clock
{
{
{
{
{
Double Remote Control
{
{
{
{
{
Group Control by 1 Remote Controller
{
{
{
{
{
Control by D-BACS
{
{
{
{
{ — {
Installation Box for Adapter PCB
—
—
—
z (71 only)
Remote/Centralized Control
{
{
{
{
z : Improved Points and Functions { : Functions — : No Functions
SkyAir LU Series – Cooling Only –
7
1
Specifications
ED21-301
4. Specifications 4.1
50Hz (General)
FHC (Ceiling Mounted Cassette Type) <50Hz> Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)
Indoor Units Dimensions Coil
Fan
FHC35KVE R35GV1 3.54/3.5 12,100/11,900 3,040/3,010 FHC35KVE
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Weight Piping Connections
Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)
Wired Wireless
Model Color Dimensions (H×W×D) Air Filter Weight
Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Hz–Volts
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V
2. 3. 4. 5.
8
FHC50KVE FHC60KVE R50GV1 R60GV1 kW 5.34/5.3 6.44/6.4 Btu/h 18,200/18,100 22,000/21,800 kcal/h 4,590/4,560 5,540/5,500 FHC50KVE FHC60KVE mm 230×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 m² 0.331 QTS45B14M Turbo Fan W 45 m³/min. (H) 14 (L) 10 (H) 15 (L) 11 (H) 19 (L) 14 kg 24 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 5) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R35GV1 R50GV1 R60GV1 Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC46AV1TRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.1 1.7 2.2 PZ380 PZ430 Propeller W 27 45 53 m³/min. 28 27 40 kg 37 42 61 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor. Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 25 30 m 15 R22 kg 1.10 (Charged for 10m) 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.50 0.85 1.20 4D006549A
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
1
FHYC (Ceiling Mounted Cassette Type) <50Hz> Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Units Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2
Weight Piping Connections
Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)
Wired Wireless
Model Color Dimensions (H×W×D) Air Filter Weight
Outdoor Units Color Dimensions Coil
Comp.
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate
Weight Piping Connections
∗2 kg
Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHYC71KVE R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FHYC71KVE 230×840×840
FHYC100KVE R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FHYC100KVE
FHYC125KVE FHYC140KVE V1 — — Y1 R125LUY1 R140LUY1 kW 13.0/12.8/12.8 14.5/14.2/14.2 Btu/h 44,500/43,600/43,600 49,400/48,400/48,400 kcal/h 11,200/11,000/11,000 12,500/12,200/12,200 FHYC125KVE FHYC140KVE mm 288×840×840 Cross Fin coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 2×12×1.5 m² 0.331 0.497 QTS45B14M QTS45A17M Turbo Fan W 45 90 m³/min. (H) 19–21 (L) 14–16 (H) 28–31 (L) 21–24 (H) 33–36 (L) 24–27 (H) 35–38 (L) 26–28 kg 24 28 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 5, 6) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 V1 R71LUV1 R100LUV1 — — Y1 R71LUY1 R100LUY1 R125LUY1 R140LUY1 Ivory mm 770×900×320 1,170×900×320 1,345×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 2×60×2.0 m² 0.634 0.983 1.134 V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE JT170BC–YE Hermetically Sealed Scroll Type kW 2.24 3.00 3.75 4.50 P47L11S P47L11SX2 Propeller W 65 90 65+85 65+90 m³/min. 48–51 59–62 92–100 97–109 V1 72 87 — Y1 71 84 98 109 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125·140>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K L 1.2 1.2 1.5 1.6 4D039096 4D039079
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–220V (380V)
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V (415V)
AS 1861
2. 3. 4. 5. 6.
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rafe) and sound pressure level are shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
9
Specifications
ED21-301
FHK (Ceiling Mounted Cassette Corner Type) <50Hz> Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)
Indoor Units Dimensions Coil
Fan
kW Btu/h kcal/h
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Weight Piping Connections
Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)
Wired Wireless
Model Color Dimensions (H×W×D) Air Filter Weight
Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHK45FV1 R50GV1 5.19/5.1 17,700/17,500 4,460/4,400 FHK45FV1
mm
FHK60FV1 R60GV1 6.6/6.5 22,760/22,200 5,690/5,600 FHK60FV1 215×1,310×710
215×1,110×710 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×11×1.75 3×11×1.75 m² 0.180 0.226 3D12H1AH1V1 3D12H1AJ1V1 4D12H1AG1V1 Sirocco Fan W 20 25 45 m³/min. (H) 12 (L) 9 (H) 12 (L) 10 (H) 17 (L) 14 kg 30 31 33 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 6) — BYK45FJW1 BYK71FJW1 White mm 70×1,240×800 70×1,440×800 Resin Net (with Mold Resistant) kg 8.5 9.5 R35GV1 R50GV1 R60GV1 Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC46AV1TRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.1 1.7 2.2 PZ380 PZ430 Propeller W 27 45 53 m³/min. 28 27 40 kg 37 42 61 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35, 50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor.Fuse. % 100–0 Capillary Tube m 25 30 m 15 R22 kg 1.10 (Charged for 10m) 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.50 0.85 1.20 4D006259A
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Hz–Volts
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
2. 3. 4. 5.
10
FHK35FV1 R35GV1 3.54/3.4 12,100/11,600 3,040/2,930 FHK35FV1
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
1
FHYK (Ceiling Mounted Cassette Corner Type) <50Hz> Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Units Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Weight Piping Connections
Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)
Wired Wireless
Model Color Dimensions (H×W×D) Air Filter Weight
Outdoor Units Color Dimensions Coil
Comp.
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate
Weight Piping Connections
kg Liquid Gas Drain
Safety Devices
Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHYK71FJV1 V1 R71LUV1 Y1 R71LUY1 kW 7.8/7.7/7.7 Btu/h 26,600/26,200/26,200 kcal/h 6,700/6,600/6,600 FHYK71FJV1 mm 215×1,310×710 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 3×11×1.75 m² 0.226 4D12H1AG1V1 Sirocco Fan W 45 m³/min. (H) 17–18 (L) 14–15 ∗3 kg 33 mm φ9.5 (Flare) mm φ15.9 (Flare) mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 6) — BYK71FJW1 White mm 70×1,440×800 Resin Net (with Mold Resistant) kg 9.5 V1 R71LUV1 Y1 R71LUY1 Ivory mm 770×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 m² 0.634 V1 ZR36K3–PFJ Y1 ZR36K3–TFD Hermetically Sealed Scroll Type kW 2.24 P47L11S Propeller W 65 m³/min. 48–51 ∗3 V1 72 Y1 71 φ9.5 (Flare) mm mm φ15.9 (Flare) φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor Protector (Compressor). Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) SONTEX 200LT L 1.2 4D039104
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–220V (380V)
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V (415V)
AS 1861
2. 3. 4. 5. 6.
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. ∗3 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
11
Specifications
ED21-301
FHB (Ceiling Mounted Built-In Type) <50Hz> Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)
Indoor Units Dimensions Coil
Fan
kW Btu/h kcal/h
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)
Wired Wireless
Model Color Dimensions (H×W×D) Weight
Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHB45FV1 R50GV1 5.19/5.1 17,700/17,500 4,460/4,400 FHB45FV1
mm
FHB60FV1 R60GV1 6.6/6.5 22,760/22,200 5,690/5,600 FHB60FV1 300×1,000×800
300×700×800 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 3×14×1.75 m² 0.132 0.221 D18H2AH1V1 D18H2AJ1V1 2D18H2AH1V1 Sirocco Fan W 65 85 110 m³/min. (H) 11.5 (L) 9 (H) 14 (L) 10 (H) 17 (L) 13 Resin Net (with Mold Resistant) kg 30 31 41 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 5) — BYBS45DJW1 (∗2 BYBS45D–W2) BYBS71DJW1 (∗2 BYBS71D–W2) White mm 55×880×500 55×1,100×500 kg 3.5 4.5 R35GV1 R50GV1 R60GV1 Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC46AV1TRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.1 1.7 2.2 PZ380 PZ430 Propeller W 27 45 53 m³/min. 28 27 40 kg 37 42 61 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35 · 50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 25 30 m 15 R22 kg 1.10 (Charged for 10m) 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.50 0.85 1.2 4D006258B
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Hz–Volts
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V
2. 3. 4. 5. 6.
12
FHB35FV1 R35GV1 3.54/3.4 12,100/11,600 3,040/2,930 FHB35FV1
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B62 is also available. Wire for remote controller : Field supplied. ∗2 This type can be used.
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
1
FHYB (Ceiling Mounted Built-In Type) <50Hz> Model
Indoor Units Outdoor Units
V1 Y1 kW Btu/h kcal/h
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Units Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)
Wired Wireless
Model Color Dimensions (H×W×D) Weight
Outdoor Units Color Dimensions Coil
Comp.
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate
Weight Piping Connections
∗2 kg
Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHYB71FV1 R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FHYB71FV1 300×1,000×800
mm
FHYB100FV1 R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FHYB100FV1 300×1,400×800 Cross Fin Coil 3×14×1.75
m²
0.221 2D18H2AJ1V1
0.338 3D18H2AN1V1 3D18H2AP1V1 Sirocco Fan W 125 135 225 m³/min. (H) 19–21.5 (L) 14–16.5 (H) 27–29 (L) 20–22 (H) 35–40.5 (L) 24–29.5 Resin Net (with Mold Resistant) kg 41 51 52 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 5) — BYBS71DJW1 (∗3 BYBS71D–W2) BYBS125DJW1 (∗3 BYBS125D–W2) White mm 55×1,100×500 55×1,500×500 kg 4.5 6.5 V1 R71LUV1 R100LUV1 — Y1 R71LUY1 R100LUY1 R125LUY1 Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Hermetically Sealed Scroll Type kW 2.24 3.00 3.75 P47L11S P47L11S×2 Propeller W 65 90 65+85 m³/min. 48–51 59–62 92–100 V1 72 87 — Y1 71 84 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K L 1.2 1.5 4D039103
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–220V (380V)
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V (415V)
AS 1861
2. 3. 4. 5. 6.
FHYB125FV1 — R125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 FHYB125FV1
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. BRC1B62 is also available. Wire for remote controller : Field supplied. ∗3 This type can be used.
SkyAir LU Series – Cooling Only –
13
Specifications
ED21-301
FUY (New Ceiling Suspended Cassette Type) <50Hz> Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Unit Color Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Comp.
Fan
mm
165×895×895
m²
W m³/min
Wired Wireless V1 Y1
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate
Weight Piping Connections
FUY71FJV1 R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FUY71FJV1
kg mm mm mm
Outdoor Units Color Dimensions Coil
V1 Y1 kW Btu/h kcal/h
mm
m² V1 Y1 kW
W m³/min V1 Y1 mm mm mm
∗2 kg
Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
m m kg L
FUY125FJV1 — R125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 FUY125FJV1
230×895×895 Cross Fin Coil (Multi Louver Fins and Hi–XA Tubes) 3×6×1.5 3×8×1.5 0.265 0.353 QTS48A QTS50B15M Turbo Fan 45 90 (H)19 (L)14 (H)29 (L)21 (H)32 (L)23 Resin Net (with Mold Resistant) 25 31 φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) I.D φ20×O.D φ26 BRC1C61 (Note. 4, 5) BRC7C529W R71LUV1 R100LUV1 — R71LUY1 R100LUY1 R125LUY1 Ivoly 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 0.634 0.983 ZR36K3–PFJ ZR48K3–PFJ — ZR36K3–TFD ZR48K3–TFD JT160BC–YE Hermetically Sealed Scroll Type 2.24 3.00 3.75 P47L11S P47L11S×2 Propeller 65 90 65+85 48–51 59–62 92–100 72 87 — 71 84 98 φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ26.0 (Hole) Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. 100–0 Electronic Expansion Valve 50 (Equivalent Length 70m) 30 R22 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K 1.2 1.5 4D039105
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–220V (380V)
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V (415V)
AS 1861
2. 3. 4. 5.
14
%
FUY100FJV1 R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FUY100FJV1 White
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
1
FH (Ceiling Suspended Type) <50Hz> Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)
Indoor Units Color Dimensions Coil
Fan
kW Btu/h kcal/h
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Air filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Wired Wireless
Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FH35BVE R35GV1 3.54/3.4 12,100/11,600 3,040/2,930 FH35BVE
FH50BVE R50GV1 5.19/5.1 17,700/17,500 4,460/4,400 FH50BVE White
FH60BVE R60GV1 6.6/6.5 22,760/22,200 5,690/5,600 FH60BVE
mm
195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 2×12×1.75 3×12×1.75 m² 0.182 0.223 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H) 13 (L) 10 (H) 16 (L) 13 Resin Net (with Mold Resistant) kg 23 24 26 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 4) BRC7E66 R35GV1 R50GV1 R60GV1 Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC46AV1TRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.1 1.7 2.2 PZ380 PZ430 Propeller W 27 45 53 m³/min. 28 27 40 kg 37 42 61 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35 · 50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 25 30 m 15 R22 kg 1.10 (Charged for 10m) 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.50 0.85 1.20 4D028432
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Hz–Volts
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for indoor fan motor heat. 3. In case of drain piping for outdoor unit, drain piping kit (option) is needed. 4. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
15
Specifications
ED21-301
FHY (Ceiling Suspended Type) <50Hz> Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Units Color Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Air filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Wired Wireless
Outdoor Units Color Dimensions Coil
Comp.
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate
Weight Piping Connections
∗2 kg
Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHY71BVE R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FHY71BVE
FHY100BVE FHY125BVE R100LUV1 — R100LUY1 R125LUY1 10.6/10.5/10.5 13.0/12.8/12.8 36,100/35,700/35,700 44,500/43,600/43,600 9,100/9,000/9,000 11,200/11,000/11,000 FHY100BVE FHY125BVE White mm 195×1,160×680 195×1,400×680 195×1,590×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.293 0.341 4D12K1AA1 3D12K2AA1 4D12K2AA1 Sirocco Fan W 62 130 m³/min. (H) 17 (L) 14 (H) 24 (L) 20 (H) 30 (L) 25 Resin Net (with Mold Resistant) kg 27 32 35 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 4) BRC7E66 V1 R71LUV1 R100LUV1 — Y1 R71LUY1 R100LUY1 R125LUY1 Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Hermetically Sealed Scroll Type kW 2.24 3.00 3.75 P47L11S P47L11S×2 Propeller W 65 90 65+85 m³/min. 48–51 59–62 92–100 V1 72 87 — Y1 71 84 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K L 1.2 1.5 4D039099 V1 Y1 kW Btu/h kcal/h
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–220V (380V)
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. ∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). 3. Capacities are net, including a deduction for cooling for indoor fan motor heat. 4. Wire for remote controller : Field supplied.
16
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
1
FAY (Wall Mounted Type) <50Hz> Model
Indoor Units Outdoor Units
V1 Y1 kW Btu/h kcal/h
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Units Color Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Wired Wireless
Outdoor Units Color Dimensions Coil
Comp.
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate
Weight Piping Connections
∗2 kg
Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FAY71LVE R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FAY71LVE
FAY100FAVE R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FAY100FAVE
White 290×1,050×230 360×1,570×200 Cross Fin Coil (Multi Louver Fins and Hi–XA Tubes) 2×16×1.4 2×12×1.4 m² 0.289 0.332 QCL9686M QCL1163MA+QCL1163MB Cross Flow Fan W 43 46 m³/min. (H) 19–19 (L) 15–15 (H) 23–23 (L) 19–19 Resin Net (with Mold Resistant) kg 13 26 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm I. Dφ20×O. Dφ26 mm I. Dφ13×O. Dφ18 BRC1C61 (Note. 5, 6) BRC7E619 BRC7C611W V1 R71LUV1 R100LUV1 Y1 R71LUY1 R100LUY1 Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 V1 ZR36K3–PFJ ZR48K3–PFJ Y1 ZR36K3–TFD ZR48K3–TFD Hermetically Sealed Scroll Type kW 2.24 3.00 P47L11S Propeller W 65 90 m³/min. 48–51 59–62 V1 72 87 Y1 71 84 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor Protector (Compressor). Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT L 1.2 4D039583 4D039106 mm
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–220V (380V)
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V (415V)
AS 1861
2. 3. 4. 5. 6.
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
17
Specifications
ED21-301
FVY (Floor Standing Type) <50Hz> Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Units Color Dimensions Coil
Fan
Air Filter Weight Piping Connections
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2
Liquid Gas Drain
Outdoor Units Color Dimensions Coil
Comp.
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate
Weight Piping Connections
∗2 kg
Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
V1 Y1 kW Btu/h kcal/h
FVY71LAVE R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FVY71LAVE
mm
1,850×600×270
FVY100LAVE R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FVY100LAVE White 1,850×600×350 Cross Fin Coil 2×44×1.75 0.44
2×40×1.75 0.40 QS37A1AM
m²
FVY125LAVE — R125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 FVY125LAVE
(3×22×1.75)×2 0.44 (0.22×2)
QS37A2AM Sirroco Fan W 30 60 90 m³/min. (H) 18–20 (L) 14–16 (H) 28–31 (L) 22–25 (H) 32–35 (L) 25–28 Resin Net (with Mold Resistant) kg 39 46 47 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ20×O. Dφ26 V1 R71LUV1 R100LUV1 — Y1 R71LUY1 R100LUY1 R125LUY1 Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Hermetically Sealed Scroll Type kW 2.24 3.00 3.75 P47L11S P47L11S×2 Propeller W 65 90 65+85 m³/min. 48–51 59–62 92–100 V1 72 87 — Y1 71 84 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K L 1.2 1.5 4D039102
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–220V (380V)
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V (415V)
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. ∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). 3. Capacities are net, including a deduction for cooling for indoor fan motor heat.
18
SkyAir LU Series – Cooling Only –
ED21-301
4.2
Specifications
50Hz (Complied with Australian Standard)
1
FHC (Ceiling Mounted Cassette Type) <50Hz> Model
Indoor Units Outdoor Units ∗1 Cooling Capacity
Indoor Units Dimensions Coil
Fan
FHC35KVE R35GV1A 3.43 11,700 2,950 FHC35KVE
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Weight Piping Connections
Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)
Wired Wireless
Model Color Dimensions (H×W×D) Air Filter Weight
Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHC50KVE FHC60KVE R50GAV1A R60GAV1A kW 5.3 6.4 Btu/h 18,100 21,800 kcal/h 4,560 5,500 FHC50KVE FHC60KVE mm 230×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 m² 0.331 QTS45B14M Turbo Fan W 45 m³/min. (H) 16 (L) 12 (H) 17 (L) 13 (H) 21 (L) 16 kg 24 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 5) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R35GV1A R50GAV1A R60GAV1A Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC46AV1TRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.1 1.7 2.2 PZ380 PZ430 Propeller W 27 45 53 m³/min. 29 28 41 kg 37 42 61 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35·50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 25 30 m 15 R22 kg 1.10 (Charged for 10m) 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.50 0.85 1.20 C : 4D010466A
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V
AS 1861
2. 3. 4. 5.
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
19
Specifications
ED21-301
FH (Ceiling Suspended Type) <50Hz> Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)/(3)
Indoor Units Color Dimensions Coil
Fan
kW Btu/h kcal/h
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Wired Wireless
Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FH50BVE R50GAV1A 5.19/5.1/5.1 17,700/17,500/17,500 4,460/4,400/4,400 FH50BVE
FH60BVE R60GAV1A 6.6/6.5/6.5 22,760/22,200/22,200 5,690/5,600/5,600 FH60BVE
White 195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.182 4D12K1AA1 3D12K1AA1 Sirocco Fan W 62 m³/min. (H) 13 (L) 10 (H) 16 (L) 13 Resin Net (with Mold Resistant) kg 24 26 φ6.4 (Flare) mm φ15.9 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 3) BRC7E66 R50GAV1A R60GAV1A Ivory White mm 685×800×300 540×750×270 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.7 2.2 PZ430 PZ380 Propeller W 45 53 m³/min. 28 41 kg 42 61 φ6.4 (Flare) mm φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35·50 Model) Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 30 m 15 R22 kg 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.85 1.2 C : 4D028448 mm
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V
—
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V
AS 1861
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Wire for remote controller : Field supplied.
20
SkyAir LU Series – Cooling Only –
ED21-301
4.3
Specifications
60Hz
1
FHC (Ceiling Mounted Cassette Type) <60Hz> Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)
Indoor Unit Dimensions Coil
Fan
kW Btu/h kcal/h
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate Sound Pressure Level
Weight Piping Connections
Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)
Wired Wireless
Model Color Dimensions (H×W×D) Air Filter Weight
Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHC50KVE R50GVAL 5.64/5.6 19,300/19,100 4,850/4,820 FHC50KVE
FHC60KVE R60GVAL 6.84/6.8 23,400/23,200 5,880/5,850 FHC60KVE
mm
230×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 m² 0.331 QTS45B14M Turbo Fan W 45 m³/min. (H)15 (L)11 (H)19 (L)14 dB(A) — kg 24 φ6.4 (Flare) mm φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 5, 6) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R50GVAL R60GVAL Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (FL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC60VHTNRT RC75VHTR2T Hermetically Sealed Rotary Type kW 1.5 1.8 PZ380 PZ430 Propeller W 45 53 m³/min. 30 44 kg 41 51 φ6.4 (Flare) mm φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 30 m 15 R22 kg 1.15 (Charged for 10m) 1.60 (Charged for 5m) SUNISO 4GS–DI L
0.85
1.00 4D006550B
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
(1)
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
5m
(2)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
5m
2. 3. 4. 5. 6.
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. Each value shows the specification per one unit. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
21
Specifications
ED21-301
FHYC (Ceiling Mounted Cassette Type) <60Hz> Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)
Indoor Unit Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate Sound Pressure Level
Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Decoration Panel (Option)
Wired Wireless
Model Color Dimensions (H×W×D) Air Filter Weight
Outdoor Units
Color Dimensions Coil
Comp.
Fan
Weight Piping Connections
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
SONTEX 200LT 1.2
L
SUNISO 4GSDID–K 1.5 4D039107
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Standard
(1)
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
5m
—
(2)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
7.5m
JIS B8616
2. 3. 4. 5. 6.
22
FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE R71LUVAL R100LUVAL — — — — R125LUTAL R140LUTAL — — R125LUYAL R140LUYAL 8.3/8.1 11.6/11.4 14.5/14.3 16.1/15.8 28,200/27,800 39,700/38,900 49,600/48,800 55,000/53,900 7,100/7,000 10,000/9,800 12,500/12,300 13,800/13,500 FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE mm 230×840×840 288×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Cross Fin Coil 2×8×1.5 2×12×1.5 m² 0.331 0.497 QTS45B14M QTS45A17M Turbo Fan W 45 90 m³/min. (H)19 (L)14 (H)28 (L)21 (H)33 (L)24 (H)35 (L)26 dB(A) — (H)44 (L)37 kg 24 28 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 6) BRC1C61 (Note. 5, 6) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 VAL R71LUVAL R100LUVAL — — TAL — — R125LUTAL R140LUTAL YAL — — R125LUYAL R140LUYAL Ivory mm 770×900×320 1,170×900×320 1,345×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 2×60×2.0 m² 0.634 0.983 1.134 VAL ZR36K3–PFV ZR47K3–PFV — TAL — JT170BC JT170BC YAL — JT170BC–YH JT170BC–YE Hermetically Sealed Scroll Type kW 2.24 2.92 3.75 4.50 P47L11S P47L11S×2 Propeller W 75 100 95+75 65+90 m³/min. 49 59 94 97–109 kg 75 92 98 112 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125·140>. Low Pressure Switch. Over Current Decive. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m) VAL TAL YAL kW Btu/h kcal/h
1.6 4D040213
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. Each value shows the specification per one unit. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
1
FH (Ceiling Suspended Type) <60Hz> Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)/(3)
Indoor Unit Color Dimensions Coil
Fan
kW Btu/h kcal/h
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Wired Wireless
Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FH50BVE R50GVAL 5.3/5.25/4.5 18,240/18,000/15,400 4,560/4,500/3,900 FH50BVE
FH60BVE R60GVAL 6.6/6.5/5.6 22,760/22,200/19,100 5,690/5,600/4,800 FH60BVE
White 195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.182 0.233 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)16 (L)13 Resin Net (with Mold Resistant) kg 24 26 φ6.4 (Flare) mm φ15.9 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 4) BRC7E66 R50GVAL R60GVAL Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (FL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC60VHTNRT RC75VHTR2T Hermetically Sealed Rotary Type kW 1.5 1.8 PZ380 PZ430 Propeller W 45 53 m³/min. 30 44 kg 41 51 φ6.4 (Flare) mm φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100-0 Capillary Tube m 30 m 15 R22 kg 1.15 (Charged for 10m) 1.60 (Charged for 5m) mm
SUNISO 4GS–DI L
0.85
1.00 4D028441
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m (Horizontal)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
5m (Horizontal)
—
(3)
Indoor : 29°CDB, 19.0°CWB Outdoor : 46°CDB, 24°CWB
7.5m (Horizontal)
SASO
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
23
Specifications
ED21-301
FHY (Ceiling Suspended Type) <60Hz> Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)
Indoor Unit Color Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Wired Wireless
Outdoor Units
Color Dimensions Coil
Comp.
Fan
Weight Piping Connections
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHY71BVE R71LUVAL — — 8.3/8.1 28,200/27,800 7,100/7,000 FHY71BVE
FHY100BVE FHY125BVE R100LUVAL — — R125LUTAL — R125LUYAL 11.6/11.4 14.5/14.3 39,700/38,900 49,600/48,800 10,000/9,800 12,500/12,300 FHY100BVE FHY125BVE White mm 195×1,160×680 195×1,400×680 195×1,590×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.293 0.341 4D12K1AA1 3D12K2AA1 4D12K2AA1 Sirocco Fan W 62 130 m³/min. (H)17 (L)14 (H)24 (L)20 (H)30 (L)25 Resin Net (with Mold Resistant) 32 35 kg 27 mm φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 4) BRC7E66 VAL R71LUVAL R100LUVAL — TAL — — R125LUTAL YAL — — R125LUYAL Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 VAL ZR36K3–PFV ZR47K3–PFV — TAL — JT160BC YAL — JT160BC–YH Hermetically Sealed Scroll Type kW 2.24 2.92 3.75 P47L11S P47L11S×2 Propeller W 75 100 95+75 m³/min. 49 59 94 kg 75 92 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse. % 100-0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) VAL TAL YAL kW Btu/h kcal/h
SONTEX 200LT 1.2
L
SUNISO 4GSDID–K 1.5 4D039110
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m (Horizontal)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m (Horizontal)
JIS B8616
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.
24
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
1
FAY (Wall Mounted Type) <60Hz> Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)
Indoor Units Color Dimensions Coil
Fan
kW Btu/h kcal/h
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Wired Wireless
Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FAY71LVE R71LUVAL 8.3/8.1 28,200/27,800 7,100/7,000 FAY71LVE
FAY100FAVE R100LUVAL 11.6/11.4 39,700/38,900 10,000/9,800 FAY100FAVE
White 290×1,050×230 360×1,570×200 Cross Fin Coil (Multi Louver Fins and Hi–XA Tubes) 2×16×1.4 2×12×1.4 m² 0.289 0.332 QCL9686M QCL1163MA+QCL1163MB Cross Flow Fan W 43 46 m³/min. (H) 19–19 (L) 15–15 (H) 23 (L) 19 Resin Net (with Mold Resistant) kg 13 26 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm I. Dφ20×O. Dφ26 mm I. Dφ13×O. Dφ18 BRC1C61 (Note. 4, 5) BRC7E619 BRC7C611W R71LUVAL R100LUVAL Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 ZR36K3–PFV ZR47K3–PFV Hermetically Sealed Scroll Type kW 2.24 2.92 P47L11S Propeller W 75 100 m³/min. 49 59 kg 75 92 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor Protector (Compressor). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT L 1.2 1.2 4D041586 4D039114 mm
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
JIS B8616
2. 3. 4. 5.
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for cooling for indoor fan motor heat. Each value for indoor unit shows the specification per one unit. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
25
Specifications
ED21-301
FVY (Floor Standing Type) <60Hz> Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)
Indoor Units Color Dimensions Coil
Fan
Air Filter Weight Piping Connections
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Liquid Gas Drain
Outdoor Units
Color Dimensions Coil
Comp.
Fan
Weight Piping Connections
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
VAL TAL YAL kW Btu/h kcal/h
FVY71LAVE R71LUVAL — — 8.3/8.1 28,200/27,800 7,100/7,000 FVY71LAVE
mm
1,850×600×270
FVY100LAVE R100LUVAL — — 11.6/11.4 39,700/38,900 10,000/9,800 FVY100LAVE White
FVY125LAVE — R125LUTAL R125LUYAL 14.5/14.3 49,600/48,800 12,500/12,300 FVY125LAVE
1,850×600×350 Cross Fin Coil 2×40×1.75 2×44×1.75 (3×22×1.75)×2 m² 0.40 0.44 0.44 (0.22×2) QS37A1AM QS37A2AM QS37A2AM Sirroco Fan W 30 60 90 m³/min. (H) 18 (L) 14 (H) 28 (L) 22 (H) 32 (L) 25 Resin Net (with Mold Resistant) kg 39 46 47 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ20×O. Dφ26 VAL R71LUVAL R100LUVAL — TAL — — R125LUTAL YAL — — R125LUYAL Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 VAL ZR36K3–PFV ZR47K3–PFV — TAL — — JT160BC YAL — — JT160BC–YH Hermetically Sealed Scroll Type kW 2.24 2.92 3.75 P47L11S P47L11S×2 Propeller W 75 100 95+75 m³/min. 49 59 94 kg 75 92 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K L 1.2 1.5 4D039113
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
JIS B8616
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Each value for indoor unit shows the specification per one unit.
26
SkyAir LU Series – Cooling Only –
ED21-301
Dimensions and Service Space
5. Dimensions and Service Space 5.1
Indoor Unit
5.1.1
FH(Y)C (Ceiling Mounted Cassette Type)
1
FHC35K + BYC125K-W1 C 860~890 Ceiling opening
80
2× 100=200
Unit (mm)
85
300 or less 680 Suspension position
950
(165)
Note3.
420
9
Branch duct connection
350 C
view 60
4-M4 Hole (prepared hole) φ7
80 80
6
40
860~890 Ceiling opening
950
780 Suspension position
10
5
840
55
55
55
80 2× 100=200
12-M4 Hole (prepared hole)
85
5
150
2
1
4
40 350
Branch duct connection
A
∗1500mm or more Required space ∗1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more.
1000 or more Required space
30
8
260 270 315
165
95 110
295
For fresh air intake kit connection (direct installation type)
view
55
840
125 150 240
750 10
B B
200
Adjustable (0~550)
420
3
40
230
view
240
Suspension bolt 4-M8~M10
160
7 A
Description
Name Number 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.
3. In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.
2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
5 6 7 8
φ6.4 flare φ12.7 flare VP25
Remote control code and control wiring connection
Air discharge grille Air suction grille Port for water supply Corner decoration cover
9 10 Drain hose
O.D.32
C : 3D012310B
FHC50K + BYC125K-W1 FHC60K + BYC125K-W1 Unit (mm)
C
950
2× 100=200 85
80
860~890 Ceiling opening 300 or less 680 Suspension position
(165)
Note3.
420
9 10
6
Branch duct connection
C view 60
4-M4 Hole (prepared hole) φ7
80
5
80
950
780 Suspension position 860~890 Ceiling opening
40 350
840
55
12-M4 Hole (prepared hole)
8
5
260 270 315
4
1
2
40 350
Branch duct connection
A
165 1000 or more Required space
125 150 240 240
For fresh air intake kit connection (direct installation type)
55
2×100=200 85
95 110
80
150
750 Adjustable (0~550)
55
840 295
200
230
B view
55
30 Suspension bolt 4-M8~M10
B
3
40
10
420
160
7 A view
∗1500mm or more Required space 1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more. Name Number 1 Liquid pipe connection Gas pipe connection 2 Drain pipe connection 3 Power supply connection 4
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.
3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.
5
Remote control code and control wiring connection
6
2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
9 10
Air discharge grille Air suction grille Port for water supply Corner decoration cover
7 8
Drain hose
Description φ6.4 flare φ15.9 flare VP25
O.D.32
C : 3D012311B
SkyAir LU Series – Cooling Only –
27
Dimensions and Service Space
ED21-301
FHYC71K + BYC125K-W1
1000 or more
Unit (mm)
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
C : 3D012312C
FHYC100K + BYC125K-W1 FHYC125K + BYC125K-W1 FHYC140K + BYC125K-W1 Unit (mm)
C
(195)
950
2× 100=200 85
80
860~890 Ceiling opening 300 or less 680 Suspension position
Note3.
165
6
40 350
Branch duct connection
C view
4-M4 Hole (prepared hole) φ7 5
60 80 80
950
780 Suspension position 860~890 Ceiling opening
10
155
420
9
160
7 A view
420
B
5
260 270 315
4
1
14-M4 Hole (prepared hole)
2× 100=200 85
2
40 350
Branch duct connection
A
28
195
150
125 150 298 240
8
55
840 80
200
30 Suspension bolt 4-M8~M10
55
40 50 155 165
55
840 295
1000 or more Required space
55
40
10
288
750 Adjustable (0~550)
B view
3
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.
3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.
2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
For fresh air intake kit connection (direct installation type)
∗1500mm or more Required space ∗1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required is space 200mm or more. Number Name 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection 5 6 7 8 9 10
Description φ9.5 flare φ19.1 flare VP25
Remote control code and control wiring connection
Air discharge grille Air suction grille Port for water supply Corner decoration cover Drain hose
O.D.32
C : 3D012313C
SkyAir LU Series – Cooling Only –
ED21-301
5.1.2
Dimensions and Service Space
FH(Y)C with High Efficiency Filter
1
KAFP556D80·557D80 for FH(Y)C35~71K
Unit (mm)
290
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975A
KAFP556D160·557D160 for FHYC100~140K
Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032976A
SkyAir LU Series – Cooling Only –
29
Dimensions and Service Space
5.1.3
ED21-301
FH(Y)C with Fresh Air Intake Kit (Without T Joint, Duct Fan)
KDDP55D160 for FH(Y)C35~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
Note 4
View
Service Access Panel : 450×450mm or more Refer to Note 2
290
Installation Service Access Panel
Connection Chamber (Right)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
How to connect Chamber 4 Independently(Refer to Note 5,6)
Applicable Models SkyAir
FH(Y)C35~71K
5 4 3 2 1 Number
Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981A
KDDP55D160 for FHYC100~140K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
View
Service Access Panel : 450×450mm or more Refer to Note 2
Note 4
Installation Service Access Panel
Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
30
Applicable Models SkyAir
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984A
SkyAir LU Series – Cooling Only –
ED21-301
5.1.4
Dimensions and Service Space
FH(Y)C with Fresh Air Intake Kit (With T Joint, Without Duct Fan)
1
KDDP55D160K for FH(Y)C35~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Flexible Duct (Accessory)
Installation Service Access Panel
Service Access Panel : 450×450mm or more Refer to Note 2
Suction Duct (K-KFD9A) Optional (Accessory) T Joint
Plate Band
(Accessory)
290
(Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
Applicable Models SkyAir
FH(Y)C35~71K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032987A
KDDP55D160K for FHYC100~140K Service Access Panel : 450×450mm or more Refer to Note 2
Installation Service Access Panel
Unit (mm) Flexible Duct (Accessory)
Service Access Panel : 450×450mm or more Refer to Note 2 Plate Band (Accessory)
T Joint (Accessory)
Suction Duct (K-KFD9A) Optional (Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
SkyAir LU Series – Cooling Only –
Applicable Models SkyAir
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032990A
31
Dimensions and Service Space
5.1.5
ED21-301
FH(Y)C with Panel Spacer
KDBJ55K160W for FH(Y)C35~71K Unit (mm)
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005390E
KDBJ55K160W for FHYC100~140K Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005391D
32
SkyAir LU Series â&#x20AC;&#x201C; Cooling Only â&#x20AC;&#x201C;
ED21-301
5.1.6
Dimensions and Service Space
FH(Y)K (Ceiling Mounted Cassette Corner Type)
1
FHK35F + BYK45FJW1 FHK45F + BYK45FJW1 Unit (mm) Model
B
FHK35F
FHK45F
6.4
6.4
12.7
15.9
B
3D027409
FHK60F + BYK71FJW1 FHYK71FJ + BYK71FJW1 Unit (mm) Model
FHK60F
FHYK71FJ
6.4
9.5
B
15.9
15.9
B
3D027408
SkyAir LU Series – Cooling Only –
33
Dimensions and Service Space
5.1.7
ED21-301
FH(Y)B (Ceiling Mounted Built-in Type)
FHB35F + BYBS45DJW1 Without Canvas Duct FHB45F + BYBS45DJW1
60
57
485
A
3
5 Model 195 B
2
6
FH(Y)B35F
FH(Y)B45F
12.7
15.9
350 or more (Required space)
67 150 200
300 245 215 150 135 10
3×150=450
440 315
1
D
45
C
Suspension bolt
135 120
50 65
∗ The required ceiling depth varies according to configuration of specific system
2×65=130
460
8
Unit (mm)
800 595 (Air suction panel center)
25 700
4
300 or more 45
Service space
12-φ7
46
460 Suction air intake position when installing the duct
650
150 215 245 150 250 300
500
228
160
462 (Ceiling opening)
628
3×150=450 485
4×150=600
760 (Ceiling opening)
700
14-M5 Hole
800
D View
B View 160 P. C. D φ125 (Knockout hole)
600 Fresh air intake Position
100
630 (Suspension position) 145
6×65=390
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
6-M5 Hole (Circumference liner)
7
1. Liquid pipe connection φ6.4Flare 2. Gas pipe connection Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
C View
750 (Suspension position) A View
JC : DU224-247
FHB35F + BYBS45DJW1 With Canvas Duct FHB45F + BYBS45DJW1 60 50
25
135 120
2×65=130
67 150 200
2
45
46
6
300 or more
4
5
B
FH(Y)B35F
Suction air intake position when instaling the duct.
150 250 300
228
500
160
628 462 (Ceiling opening)
15.9
12.7 460
650
3×150=450 485
4×150=600 700
760 (Ceiling opening)
D View
14-M5 hole
800
B View 160 P. C. D
6×65=390
φ125 (Knockout hole)
600 Fresh air intake position
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
100
630 (Suspension position) 145
FH(Y)B45F
12-φ7
Service space
10
Model
150 215 245
A
3
195
440 315
1
∗ The required ceiling depth varies according to configuration of specific system
465 or more Required installation space
Suspension bolt
57
Unit (mm)
800 595 (Air suction panel center)
D
45 115~255
C
300 245 215 150 135
8
700 485 460 3×150=450 65
6-M5 hole (Circumference liner)
7 750 (Suspension position)
A
C
View
1. Liquid pipe connection φ6.4 Flare 2. Gas pipe connection Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
View
JC : DU224-248
34
SkyAir LU Series – Cooling Only –
ED21-301
Dimensions and Service Space
1
FHB60F + BYBS71DJW1 Without Canvas Duct FHYB71F + BYBS71DJW1 Unit (mm)
A
45
(Reqjired space)
195
350 or more
FHYB71F
6.4
9.5 16-φ7 760
4
6
2
B
FH(Y)B60F
46
150 215 245
57
Model
135 120
150 200
D
300 or more Survice space
5
3
Suction air intake position when installing the duct 5×150=750 785
View
150 250 300
D
160
500
462 (Ceiling opening)
950 927
228
10
5×150=750 785
440 315
1 2×65=130
Suspension bolt
45
C
60 50
67
1000 760 65
300 245 215 150 135
8
∗ The required ceiling depth varies according to configuration of specific system
800 595 (Air suction panel center)
25
1060 (Ceiling opening)
6×150=900
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
1000
1100 18-M5 Hole
B
View
160 P. C. D
11×65=715
600 fresh air intake position
1. Liquid pipe connection Flare 2. Gas pipe connection φ15.9 Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
100
630 (Suspension position) 145
φ125 (Knockout hole)
6-M5 Hole (Circumference Liner)
C
7
View
1050 (Suspension position)
A
JC : DU226-256
View
FHB60F + BYBS71DJW1 With Canvas Duct FHYB71F + BYBS71DJW1 60 50
25
135 120
D
5
Model 195
3
1 2×65=130
150 200
300 245 215 150 135 45 115~255
B 57
45
2
A
46
6
300 or more
4
FH(Y)B60F
FHYB71F
6.4
9.5
16-φ7 760
10
Service space
950
Suction air intake position when instaling the duct.
1000 18-M5 hole
1100
B 160 P. C. D φ125 (Knockout hole)
View
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
1. Liquid pipe connection Flare 2. Gas pipe connection φ15.9Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
6-M5 hole (Circumference liner)
7
SkyAir LU Series – Cooling Only –
View
600 Fresh air intake position
100
630 (Suspension position) 145
11×65=715
View
D
6×150=900
1060 (Ceiling opening)
A
5×150=750 785
150 250 300
160
228
500
462 (Ceiling opening)
927
1050 (Suspension position)
150 215 245
C
315 Suspension bolt
67
65
∗ The required ceiling depth varies according to configuration of specific system
440
760 5×150=750
8
Unit (mm)
800 595 (Air suction panel center)
465 or more Required installation space
1000 785
C
View
JC : DU226-257
35
Dimensions and Service Space
ED21-301
FHYB100F + BYBS125DJW1 Without Canvas Duct FHYB125F + BYBS125DJW1 Unit (mm)
57
5
A
45
7×150=1050 1185
4
6
2
300 or more Survice space
B
150 215 245
D
20-φ7 1160
(Reqjired space)
3
195
67
150 200
300 245 215 150 135 10
7×150=1050 1185
440 315
1
45
C
Suspension bolt 4-M8~M10
135 120
60 50
2×65=130
1400 1160 65
8
∗ The required ceiling depth varies according to configuration of specific system
800 595 (Air suction panel center)
350 or more
25
D
46
View
462 (Ceiling opening)
Suction air intake position when instaling the duct.
150 250 300
228
160
500
1328
1460 (Ceiling opening)
9×150=1350
1500
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
1400 24-M5 hole
B
View
160 P. C. D
16×65=1040
600 fresh air intake
1. Liquid pipe connection φ9.5 Flare 2. Gas pipe connection φ19.1 Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
100
630 (Suspension position) 145
φ125 (Knockout hole)
6-M5 Hole (Circumference Liner)
C
7
View
1450 (Suspension position)
A
View
FHYB100F + BYBS125DJW1 With Canvas Duct FHYB125F + BYBS125DJW1 25
3
1
20-φ7
45 115~255
B 57
2
A
45
46
6
300 or more
4
1160
465 or more Required installation space
D
5 135 120
150 200
300 245 215 150 135
C
315 Suspension bolt 4-M8~M10 67
65
∗ The required ceiling depth varies according to configuration of specific system
440
2×65=130
8
Unit (mm)
800 595 (Air suction panel center)
150 215 245
60 50
1160 7×150=1050
195
1400 1185
7×150=1050 1185
10
Service space Suction air intake position when instaling the duct.
D
View
9×150=1350 1400
1460 (Ceiling opening)
24-M5 hole
1500
B 160 P. C. D φ125 (Knockout hole)
View
1. Liquid pipe connection φ9.5 Flare 2. Gas pipe connection φ19.1 Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange
6-M5 hole (Circumference)
7 1450 (Suspension position)
A
Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.
600 Fresh air intake position
100
630 (Suspension position) 145
16×65=1040
36
150 250 300
160
228
500
462 (Ceiling opening)
1328
C
View
View
SkyAir LU Series – Cooling Only –
ED21-301
5.1.8
Dimensions and Service Space
FUY (New Ceiling Suspended Cassette Type)
1
FUY71FJ Unit (mm)
3D013860A
FUY100FJ FUY125FJ Unit (mm)
3D013859A
SkyAir LU Series – Cooling Only –
37
Dimensions and Service Space
5.1.9
ED21-301
FH(Y) (Ceiling Suspended Type)
FH35B FH50B Unit (mm)
A
Model
FH(Y)35B FH(Y)50B
A
12.7
15.9
3D027536C 3D028600
FH60B FHY71B Unit (mm)
A
38
Model
FH(Y)60B
FHY71B
A
6.4
9.5
3D027537 3D027538B
SkyAir LU Series – Cooling Only –
ED21-301
Dimensions and Service Space
1
FHY100B Unit (mm)
3D027539B
FHY125B Unit (mm)
3D027540
SkyAir LU Series – Cooling Only –
39
Dimensions and Service Space
ED21-301
5.1.10 FAY (Wall Mounted Type) FAY71L Unit (mm)
3D038540A
FAY100FA Unit (mm)
3D014381A
40
SkyAir LU Series – Cooling Only –
ED21-301
Dimensions and Service Space
5.1.11 FVY (Floor Standing Type)
1
FVY71LA Unit (mm)
3D031617
FVY100LA FVY125LA Unit (mm)
3D031618
SkyAir LU Series – Cooling Only –
41
Dimensions and Service Space
5.2
ED21-301
Remote Controller
BRC7C613W (Wireless Type for FH(Y)C~K)
3D005912B
BRC7C529W (Wireless Type for FUY~FJ)
3D014035
42
SkyAir LU Series – Cooling Only –
ED21-301
Dimensions and Service Space
1
BRC7E619 (Wireless Type for FAY71L)
FAY71
C : 3D034905
BRC7C611W (Wireless Type for FAY100FA)
3D010766A
SkyAir LU Series – Cooling Only –
43
Dimensions and Service Space
ED21-301
BRC7E66 (Wireless Type for FH(Y)~B)
3D028963
BRC1C61 (Wired Type)
More comfortable operation by thermo sensor in the Remote Controller Applicable Model FH(Y)K-F(J) FH(Y)-B FH(Y)C-K FH(Y)B-F FUY-FJ FV(Y)-LA (Available for 2 remote control use) FAY-FA/L
C : 3D028952
44
SkyAir LU Series – Cooling Only –
ED21-301
5.3
Dimensions and Service Space
Outdoor Unit
1
R35G Unit (mm)
3D006245C
R50G / R50GA Unit (mm)
3D004855D
SkyAir LU Series – Cooling Only –
45
Dimensions and Service Space
ED21-301
R60G / R60GA Unit (mm)
3D004856E
R71LU Unit (mm)
3D039213
46
SkyAir LU Series – Cooling Only –
ED21-301
Dimensions and Service Space
1
R100LU Unit (mm)
3D039214
R125LU Unit (mm)
3D039215
SkyAir LU Series – Cooling Only –
47
Dimensions and Service Space
ED21-301
R140LU Unit (mm)
3D039216
48
SkyAir LU Series – Cooling Only –
ED21-301
5.4
Dimensions and Service Space
Installation Service Space for R71LU, 100LU, 125LU, 140LU
1
140 140
3D039172-1
SkyAir LU Series – Cooling Only –
49
Dimensions and Service Space
ED21-301
3D039172-2
50
SkyAir LU Series – Cooling Only –
ED21-301
Piping Diagrams
6. Piping Diagrams 6.1
1
Indoor Unit + Outdoor Unit
R35G R50G / R50GA R60G / R60GA
R71LU
3D039739
SkyAir LU Series – Cooling Only –
51
Piping Diagrams
ED21-301
R100LU
3D039740
R125LU
3D039741
52
SkyAir LU Series – Cooling Only –
ED21-301
Piping Diagrams
1
R140LU
3D039742
SkyAir LU Series – Cooling Only –
53
Wiring Diagrams
ED21-301
7. Wiring Diagrams 7.1
Indoor Unit
FHC35KVE FHC50KVE FHC60KVE
3D005749B
54
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
1
FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE
3D005668C
SkyAir LU Series – Cooling Only –
55
Wiring Diagrams
ED21-301
FHK35FV1 FHK45FV1 FHK60FV1
DU423-5176B
56
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
1
FHYK71FJV1
DU423-5174A
SkyAir LU Series – Cooling Only –
57
Wiring Diagrams
ED21-301
FHB35FV1 FHB45FV1 FHB60FV1
DU423-5175B
58
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
1
FHYB71FV1
DU423-5173C
SkyAir LU Series – Cooling Only –
59
Wiring Diagrams
ED21-301
FHYB100FV1 FHYB125FV1
DU428-5353C
60
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
1
FUY71FJV1 FUY100FJV1 FUY125FJV1
3D013404B
SkyAir LU Series – Cooling Only –
61
Wiring Diagrams
ED21-301
FH35BVE FH50BVE FH60BVE
3D027501
62
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
1
FHY71BVE FHY100BVE FHY125BVE
3D027502
SkyAir LU Series – Cooling Only –
63
Wiring Diagrams
ED21-301
FAY71LVE
3D037717B
64
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
1
FAY100FAVE
DU427-5410E
SkyAir LU Series – Cooling Only –
65
Wiring Diagrams
ED21-301
FVY71LAVE FVY100LAVE FVY125LAVE
3D013540B
66
SkyAir LU Series – Cooling Only –
ED21-301
7.2
Outdoor Units
7.2.1
50Hz
Wiring Diagrams
1
R35GV1 / R35GV1A
R50GV1 / R50GV1A
3D005285A
SkyAir LU Series – Cooling Only –
67
Wiring Diagrams
ED21-301
R50GAV1A
3D028077
R60GV1 / R60GV1A
3D004030A
68
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
1
R60GAV1A
3D028078
R71LUV1 R100LUV1
3D037640C
SkyAir LU Series – Cooling Only –
69
Wiring Diagrams
ED21-301
R71LUY1 R100LUY1
3D037642C
R125LUY1 R140LUY1
3D037644C
70
SkyAir LU Series – Cooling Only –
ED21-301
7.2.2
Wiring Diagrams
60Hz
1
R50GVAL
3D005285A
R60GVAL
SkyAir LU Series – Cooling Only –
71
Wiring Diagrams
ED21-301
R71LUVAL R100LUVAL
3D037935C
R125LUTAL R140LUTAL
3D037936C
72
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
1
R125LUYAL R140LUYAL
3D037937C
SkyAir LU Series – Cooling Only –
73
Capacity Tables
ED21-301
8. Capacity Tables 8.1
50Hz (General)
FHC35KVE + R35GV1
0.02
C: 3D006618
FHK35FV1 / FHB35FV1 / FH35BVE + R35GV1
3D006627B
74
SkyAir LU Series – Cooling Only –
ED21-301
Capacity Tables
1
FHC50KVE + R50GV1
0.02
C: 3D006616
FHK45FV1 / FHB45FV1 / FH50BVE + R50GV1
3D006621B
SkyAir LU Series – Cooling Only –
75
Capacity Tables
ED21-301
FHC60KVE + R60GV1
0.02
C: 3D006615
FHK60FV1 / FHB60FV1 / FH60BVE + R60GV1
3D006625C
76
SkyAir LU Series – Cooling Only –
ED21-301
Capacity Tables
1
FHYC71KVE / FHYK71FJV1 / FHYB71FV1 / FUY71FJV1 / FHY71BVE / FAY71LVE / FVY71LAVE + R71LUV1 FHYC71KVE / FHYK71FJV1 / FHYB71FV1 / FUY71FJV1 / FHY71BVE / FAY71LVE / FVY71LAVE + R71LUY1
3D039613A
FHYC100KVE / FHYB100FV1 / FUY100FJV1 / FHY100BVE / FAY100FAVE / FVY100LAVE + R100LUV1 FHYC100KVE / FHYB100FV1 / FUY100FJV1 / FHY100BVE / FAY100FAVE / FVY100LAVE + R100LUY1
3D039626A
SkyAir LU Series – Cooling Only –
77
Capacity Tables
ED21-301
FHYC125KVE / FHYB125FV1 / FUY125FJV1 / FHY125BVE / FVY125LAVE + R125LUY1
3D039635
FHYC140KVE + R140LUY1
3D039644
78
SkyAir LU Series – Cooling Only –
ED21-301
8.2
Capacity Tables
50Hz (Complied with Australian Standard)
1
FHC35KVE + R35GV1A
C: 3D006618
220V
240V 14
16
220V : 5m 240V : 7.5m
C:3D011149
FHC50KVE + R50GAV1A
C: 3D006616
220V
240V 15 0.18
17 0.18
220V : 5m 240V : 7.5m
C:3D011150
SkyAir LU Series – Cooling Only –
79
Capacity Tables
ED21-301
FH50BVE + R50GAV1A
3D006621B
3D011053B
FHC60KVE + R60GAV1A
C: 3D006615
220V
240V 19
21
220V : 5m 240V : 7.5m
C:3D011151
80
SkyAir LU Series – Cooling Only –
ED21-301
Capacity Tables
1
FH60BVE + R60GAV1A
3D006625C
3D011054B
SkyAir LU Series – Cooling Only –
81
Capacity Tables
8.3
ED21-301
60Hz
FHC50KVE + R50GVAL
C : 3D006814
FH50BVE + R50GVAL
3D006619B
82
SkyAir LU Series – Cooling Only –
ED21-301
Capacity Tables
1
FHC60KVE + R60GVAL
C : 3D006825
FH60BVE + R60GVAL
3D006620B
SkyAir LU Series – Cooling Only –
83
Capacity Tables
ED21-301
FHYC71KVE / FHY71BVE / FAY71LVE / FVY71LAVE + R71LUVAL
3D039615A
FHYC100KVE / FHY100BVE / FAY100FAVE / FVY100LAVE + R100LUVAL
3D039628
84
SkyAir LU Series – Cooling Only –
ED21-301
Capacity Tables
1
FHYC125KVE / FHY125BVE / FVY125LAVE + R125LUYAL
3D039638
FHYC125KVE / FHY125BVE / FVY125LAVE + R125LUTAL
3D039637
SkyAir LU Series – Cooling Only –
85
Capacity Tables
ED21-301
FHYC140KVE + R140LUTAL
3D039648
FHYC140KVE + R140LUYAL
3D039652
86
SkyAir LU Series – Cooling Only –
ED21-301
8.4
Capacity Tables
Capacity Correction Factor by The Length of Refrigerant Piping The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit) All Models for Pair System (Reference Valve) 1. In case of piping length 5m (35~140)
Cooling capacity correction factor
100
95 35·45·50·60 90
85
100 71 125
80 140 75
0
5
10
15 20 25 30 35 Length of refrigerant piping (Total length)
40
45
50 (m) (S0003)
2. In case of piping length 7.5m (71~140)
Cooling capacity correction factor
100
95
90
85
100 71 125
80
140
75
Note:
0
5
7.5 10
20 25 30 35 15 Length of refrigerant piping (Total length)
40
45
50 (m)
1. line: Correction factor for cooling capacity 2. The correction factor remains the same whether the outdoor unit is to be installed above or below the indoor unit. 3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the range of its limitation.
SkyAir LU Series – Cooling Only –
87
1
Operation Limits
ED21-301
9. Operation Limits 9.1
Operation Limits R50GVAL R60GVAL
R35GV1 / R35GV1A R50GV1 / R50G(A)V1A R60GV1 / R60G(A)V1A
4D006229C
R71LUV1 / R71LUY1 / R71LUVAL R100LUV1 / R100LUY1 / R100LUVAL R125LUY1 / R125LUTAL / R125LUYAL R140LUY1 / R140LUTAL / R140LUYAL
3D039657
Notes:
88
The graphs are based on the following conditions. Equivalent piping length 5m Level difference 0m Air flow rate High
SkyAir LU Series – Cooling Only –
ED21-301
Sound Level
10. Sound Level 10.1
1
Overall Sound Level dB(A) 50Hz Model
60Hz
220V
240V
220V
Measuring Location
H
L
H
L
H
L
FHC35K FHC50K FHC60K FHYC71K FHYC100K FHYC125K FHYC140K
33 33 35 35 39 42 44
29 29 30 30 34 36 37
35 35 37 37 41 44 46
31 31 32 32 36 38 39
— 33 35 35 39 42 44
— 29 30 30 34 36 37
FH(Y)C
FHK35F FHK45F FHK60F FHYK71FJ
39 39 41 41
33 34 36 36
41 41 43 43
35 36 38 38
— — — —
— — — —
FHK
FHB35F FHB45F FHB60F FHYB71F FHYB100F FHYB125F
38 39 41 41 41 44
32 34 35 35 35 38
40 41 43 43 43 46
34 36 37 37 37 40
— — — — — —
— — — — — —
FH(Y)B
FUY71FJ FUY100FJ FUY125FJ
40 43 44
35 38 39
42 45 46
37 40 41
— — —
— — —
FUY
FH35B FH50B FH60B FHY71B FHY100B FHY125B
37 38 38 39 42 44
32 33 33 35 37 39
37 38 38 39 42 44
32 33 33 35 37 39
— 38 38 39 42 42
— 33 33 35 37 39
FH(Y)
FAY71L FAY100FA
43 45
37 41
43 45
37 41
43 45
37 41
FAY
FVY71LA FVY100LA FVY125LA
41 46 49
35 40 43
43 48 51
37 42 45
41 46 49
35 40 43
FVY
(S0007)
R35G R50G(A) R60G(A) R71LU R100LU
48 49 54 48 49
49 50 55 49 50
— 52 55 — —
380V
415V
220V
R71LU R100LU R125LU R140LU R125LUTAL R140LUTAL
48 49 49 54 — —
49 50 50 55 — —
49 51 — — 51 55
R125LUYAL R140LUYAL
— —
— —
Microphone
4D028280A
R35~60
R71~140LU
Microphone
380V
Note:
51 55
4D039806
Operation sound is measured in an anechoic chamber.
SkyAir LU Series – Cooling Only –
89
Sound Level
10.2
ED21-301
Octave Band Level
10.2.1 Indoor Units FHC35KVE FHC50KVE
FHC60KVE FHYC71KVE
FHYC100KVE
FHYC140KVE
FHK35FVE
H H
L L
4D006198A
FHYC125KVE
70
NC-60 60
H(240V) NC-50 50
H(220V) NC-40 40 NC-30 30
L(240V) NC-20 20
L(220V)
63
125
250
500
1000
2000
4000
8000
4D013951
FHK45FVE
FHK60FVE FHYK71FJVE
FHB35FVE
FHB45FV1
FHB60FV1 FHYB71FV1
FHYB100FV1
90
SkyAir LU Series – Cooling Only –
ED21-301
Sound Level
FHYB125FV1
FUY71FJV1
FUY100FJV1
4D013827A
FUY125FJV1
FH60BVE
4D028280A
FHY71BVE
4D028282
FHY125BVE
SkyAir LU Series – Cooling Only –
4D028281A
FHY100BVE
4D028355
FAY71LVE
4D028284
4D013828A
FH50BVE
FH35BVE
4D013829A
1
4D028283
FAY100FAVE
4D038512A
4D014379A
91
Sound Level
ED21-301
FVY71LAVE
FVY100LAVE
4D013840B
FVY125LAVE
4D013841A
4D013842B
10.2.2 Outdoor Units (50Hz) R35GV1 / R35GV1A
R50GV1 / R50G(A)V1A
4D000697B
R71LUV1 / R71LUY1
R60GV1 / R60G(A)V1A
DW525-597E
R100LUV1 / R100LUY1
4D039802
DW527-217E
R125LUY1
4D039804
4D039806
R140LUY1
4D039808
92
SkyAir LU Series – Cooling Only –
ED21-301
Sound Level
10.2.3 Outdoor Unit (60Hz) R50GVAL
1
R71LUVAL
R60GVAL
4D039810
R100LUVAL
R140LUTAL /R140LUYAL
R125LUTAL /R125LUYAL
4D039811
4D039812
4D039813
240V, 415V 220V, 380V Notes:
1. Dotted line shows the case of 50Hz. 2. Continuous line shows the case of 60Hz. 3. Only continuous line shows the case of both 50 and 60Hz.
SkyAir LU Series – Cooling Only –
93
Fan Performance
ED21-301
11. Fan Performance 11.1
Fan Performance
11.1.1 Ceiling Mounted Built-In Type FHB35F
FHB45F
FHB60F
FHYB71F
94
SkyAir LU Series – Cooling Only –
ED21-301
Fan Performance
FHYB100F
FHYB125F
Notes:
1
1. The remote controller can be used to switch between “high” and “low”. 2. The air flow is set to “standard” before leaving the factory. It is possible to switch between “standard ESP” and “high ESP” by remote controller. 3. The internal static pressure indicates the characteristics of the fan when a suction panel (optional accessory) and a canvas for the suction panel (optional accessory) are incorporated into the main unit (with a long-life filter).
SkyAir LU Series – Cooling Only –
95
Electric Characteristics
ED21-301
12. Electric Characteristics 12.1
50Hz Unit combination Indoor
Outdoor
Power supply Hz-Volts
50-220 FHC35KVE R35GV1(A) 50-230 50-240 50-220 50-230 FHK35FV1 R35GV1 50-240 50-220 50-230 FHB35FV1 R35GV1 50-240 50-220 50-230 FH35BVE R35GV1 50-240 50-220 FHC50KVE R50G(A)V1(A) 50-230 50-240 50-220 50-230 FHK45FV1 R50GV1 50-240 50-220 50-230 FHB45FV1 R50GV1 50-240 50-220 50-230 FH50BVE R50GV1 50-240 50-220 FH50BVE R50GAV1A 50-230 50-240 50-220 FHC60KVE R60G(A)V1(A) 50-230 50-240 50-220 50-230 FHK60FV1 R60GV1 50-240 50-220 50-230 FHB60FV1 R60GV1 50-240 50-220 50-230 FH60BVE R60GV1 50-240 50-220 FH60BVE R60GAV1A 50-230 50-240 50-220 50-230 FHYC71KVE R71LUV1 50-240 50-220 50-230 FHY71BVE R71LUV1 50-240 50-220 50-230 FHYB71FV1 R71LUV1 50-240 50-220 50-230 FHYK71FJV1 R71LUV1 50-240 50-220 50-230 FVY71LAVE R71LUV1 50-240 50-220 50-230 R71LUV1 FAY71LVE 50-240 50-220 50-230 FUY71FJV1 R71LUV1 50-240 50-380/220 50-400/230 FHYC71KVE R71LUY1 50-415/240 50-380/220 50-400/230 FHY71BVE R71LUY1 50-415/240 50-380/220 FHYB71FV1 R71LUY1 50-400/230 50-415/240 50-380/220 FHYK71FJV1 R71LUY1 50-400/230 50-415/240 50-380/220 50-400/230 FVY71LAVE R71LUY1 50-415/240 50-380/220 50-400/230 R71LUY1 FAY71LVE 50-415/240 50-380/220 50-400/230 FUY71FJV1 R71LUY1 50-415/240
Voltage range
Max. 50Hz 264V Min. 50Hz 198V
Max. 50Hz 264V Min. 50Hz 198V
Max. 50Hz 264V Min. 50Hz 198V
Max. 50Hz 264V Min. 50Hz 198V
Max. 50Hz 456/264V Min. 50Hz 342/198V
Comp
MCA TOCA MFA 6.9
15
7.6
15
7.9
15
8.0
15
13.5
20
11.9
20
12.4
20
12.3
20
13.5
20
14.5
25
16.3
25
16.4
25
16.3
25
14.5
25
18.3
23.2
30
20.9
23.8
30
19.3
23.5
30
18.6
23.1
30
19.1
23.3
30
18.3
23.0
30
18.5
23.2
30
7.5
8.7
15
7.7
8.7
15
7.9
9.0
15
7.5
8.6
15
7.8
8.8
15
7.3
8.5
15
7.5
8.7
15
LRA 29 30 31 29 30 31 29 30 31 29 30 31 42 44 46 42 44 46 42 44 46 42 44 46 42 44 46 55 58 60 55 58 60 55 58 60 55 58 60 55 58 60 82 78 75 82 78 75 82 78 75 82 78 75 82 78 75 82 78 75 82 78 75 40 38 37 40 38 37 40 38 37 40 38 37 40 38 37 40 38 37 40 38 37
RLA 4.6 4.7 4.7 5.3 5.5 5.6 5.3 5.5 5.6 5.3 5.5 5.6 9.2 9.7 10.1 9.0 9.1 9.1 9.0 9.1 9.1 9.0 9.1 9.1 9.2 9.7 10.1 10.6 10.5 10.3 11.9 12.0 12.1 11.9 12.0 12.1 11.9 12.0 12.1 10.6 10.5 10.3 13.7 13.1 12.6 14.2 13.6 13.0 14.2 13.5 13.0 14.0 13.4 12.9 14.2 13.6 13.0 13.8 13.2 12.6 13.8 13.2 12.7 5.0 4.8 4.6 5.2 4.9 4.7 5.1 4.9 4.7 5.1 4.8 4.7 5.2 4.9 4.7 5.0 4.8 4.6 5.0 4.8 4.6
OFM
IFM
kW
FLA
kW
FLA
0.027
0.4
0.045
0.6
0.027
0.4
0.025
0.2
0.027
0.4
0.065
0.5
0.027
0.4
0.062
0.6
0.045
0.3
0.045
0.6
0.045
0.3
0.025
0.2
0.045
0.3
0.085
0.7
0.045
0.3
0.062
0.6
0.045
0.3
0.062
0.6
0.053
0.6
0.045
0.6
0.053
0.6
0.06
0.6
0.053
0.6
0.11
0.7
0.053
0.6
0.062
0.6
0.053
0.6
0.062
0.6
0.065
0.6
0.045
0.6
0.065
0.6
0.062
0.6
0.065
0.6
0.125
0.9
0.065
0.6
0.045
0.5
0.065
0.6
0.030
0.7
0.065
0.6
0.068
0.4
0.065
0.6
0.045
0.6
0.065
0.6
0.045
0.6
0.065
0.6
0.062
0.6
0.065
0.6
0.125
0.9
0.065
0.6
0.045
0.5
0.065
0.6
0.030
0.7
0.065
0.6
0.068
0.4
0.065
0.6
0.045
0.6
3D006610D 3D006301A 3D039576C
96
SkyAir LU Series – Cooling Only –
ED21-301
Electric Characteristics
Unit combination Indoor
Outdoor
FHYC100KVE R100LUV1 FHY100BVE
R100LUV1
FHYB100FV1 R100LUV1 FVY100LAVE R100LUV1 FAY100FAVE R100LUV1 FUY100FJV1 R100LUV1 FHYC100KVE R100LUY1 FHY100BVE
R100LUY1
FHYB100FV1 R100LUY1 FVY100LAVE R100LUY1 FAY100FAVE R100LUY1 FUY100FJV1 R100LUY1 FHYC125KVE R125LUY1 FHY125BVE
Power supply
R125LUY1
FHYB125FV1 R125LUY1 FVY125LAVE R125LUY1 FUY125FJV1 R125LUY1 FHYC140KVE R140LUY1
Hz-Volts 50-220 50-230 50-240 50-220 50-230 50-240 50-220 50-230 50-240 50-220 50-230 50-240 50-220 50-230 50-240 50-220 50-230 50-240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240
Comp
Voltage range MCA TOCA MFA 24.7
27.8
40
24.1
27.5
40
24.6
27.8
40
24.7
28.1
40
23.9
27.1
40
24.6
27.8
40
10.2
11.8
15
9.9
11.5
15
Max. 50Hz 456/264V
10.2
11.8
15
Min. 50Hz 342/198V
10.5
12.1
15
9.5
11.1
15
10.2
11.8
15
12.4
15.3
20
12.3
15.0
20
12.5
15.7
20
12.9
15.8
20
12.3
15.3
20
13.0
17.4
25
Max. 50Hz 264V Min. 50Hz 198V
Max. 50Hz 456/264V Min. 50Hz 342/198V
Max. 50Hz 456/264V Min. 50Hz 342/198V
LRA
RLA
114 109 105 114 109 105 114 109 105 114 109 105 114 109 105 114 109 105 50 48 46 50 48 46 50 48 46 50 48 46 50 48 46 50 48 46 51 53 56 51 53 56 51 53 56 51 53 56 51 53 56 67 71 74
18.3 17.5 16.7 18.1 17.3 16.6 18.2 17.4 16.7 18.1 17.3 16.6 18.2 17.4 16.7 18.2 17.4 16.6 6.7 6.4 6.1 6.7 6.3 6.1 6.7 6.4 6.1 6.7 6.3 6.1 6.7 6.4 6.1 6.7 6.3 6.1 8.0 8.0 8.1 8.1 8.1 8.2 7.6 7.7 7.8 8.0 8.0 8.1 7.9 7.9 8.0 8.2 8.2 8.5
OFM
1
IFM
kW
FLA
kW
FLA
0.09
0.8
0.090
1.0
0.09
0.8
0.135
0.7
0.09
0.8
0.135
1.0
0.09
0.8
0.060
1.3
0.09
0.8
0.046
0.3
0.09
0.8
0.090
1.0
0.09
0.8
0.090
1.0
0.09
0.8
0.135
0.7
0.09
0.8
0.135
1.0
0.09
0.8
0.060
1.3
0.09
0.8
0.046
0.3
0.09
0.8
0.090
1.0
0.065 + 0.085 0.065 + 0.085 0.065 + 0.085 0.065 + 0.085 0.065 + 0.085 0.065 + 0.090
0.6 + 0.7 0.6 + 0.7 0.6 + 0.7 0.6 + 0.7 0.6 + 0.7 0.6 + 0.8
0.090
1.0
0.144
0.7
0.225
1.4
0.090
1.5
0.090
1.0
0.090
1.0
3D039577A 3D039578A 3D039579A
SkyAir LU Series – Cooling Only –
97
Electric Characteristics
12.2
ED21-301
60Hz Unit combination Indoor
Outdoor
Power supply Hz-Volts
FHC50KVE
R50GVAL
60-220
FH50BVE
R50GVAL
60-220
FHC60KVE
R60GVAL
60-220
FH60BVE
R60GVAL
60-220
Comp
Voltage range MCA TOCA MFA Max. 60Hz 242V Min. 60Hz 198V
Max. 60Hz 242V Min. 60Hz 198V
OFM
LRA
RLA
IFM
kW
FLA
kW
FLA
13.0
—
20
42
9.5
0.045
0.4
0.045
0.7
13.0
—
20
42
9.4
0.045
0.4
0.062
0.7
15.8
—
25
47
11.6
0.053
0.6
0.045
0.7
15.8
—
25
47
11.4
0.053
0.6
0.062
0.7
19.5
23.5
30
99
14.4
0.075
0.8
0.045
0.7
22.4
22.0
30
99
15.3
0.075
0.8
0.062
0.7
FHYC71KVE R71LUVAL
60-220
FHY71BVE
R71LUVAL
60-220
FVY71LAVE
R71LUVAL
60-220
20.2
23.6
30
99
14.9
0.075
0.8
0.030
0.8
FAY71LVE
R71LUVAL
60-220
19.5
23.2
30
99
14.6
0.075
0.8
0.068
0.4
FHYC100KVE R100LUVAL
60-220
24.8
27.9
40
143
18.3
0.1
0.9
0.090
1.0
R100LUVAL
60-220
25.5
27.9
40
143
18.9
0.1
0.9
0.135
1.0
FVY100LAVE R100LUVAL
60-220
25.3
28.3
40
143
18.4
0.1
0.9
0.060
1.4
FAY100FAVE R100LUVAL
60-220
24.2
27.3
40
143
18.3
0.1
0.9
0.046
0.4
FHYC125KVE R125LUTAL
60-220
21.6
24.3
30
137
15.1
0.090
1.0
R125LUTAL
60-220
23.2
24.4
30
137
16.3
0.130
1.1
FVY125LAVE R125LUTAL
60-220
22.9
25.0
30
137
15.6
0.090
1.7
FHYC125KVE R125LUYAL
60-380
13.3
15.3
20
66
8.5
0.090
1.0
R125LUYAL
60-380
14.3
15.4
20
66
9.2
0.130
1.1
FVY125LAVE R125LUYAL
60-380
14.4
16.0
20
66
8.8
0.090
1.7
FHYC140KVE R140LUTAL
60-220
Max. 60Hz - 242V 22.5 Min. 60Hz - 198V
30.7
40
146
15.8
0.090
1.0
FHYC140KVE R140LUYAL
60-380
Max. 60Hz 418V Min. 60Hz 342V
17.7
25
75
8.7
0.090
1.0
FHY100BVE
FHY125BVE
FHY125BVE
Max. 60Hz 242V Min. 60Hz 198V
Max. 60Hz 242V Min. 60Hz 198V
Max. 60Hz 242V Min. 60Hz 198V
Max. 60Hz 418V Min. 60Hz 342V
13.6
0.075 + 0.095 0.075 + 0.095 0.075 + 0.095 0.075 + 0.095 0.075 + 0.095 0.075 + 0.095 0.075 + 0.100 0.075 + 0.100
0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9
3D006610D 3D006301A 3D039576C 3D039577A 3D039578A 3D039579A
98
SkyAir LU Series – Cooling Only –
ED21-301
Option List
13. Option List 13.1
1
LU Series
13.1.1 Indoor Unit FH(Y)C–K Name of Option
Remark
Kit Name 35~71K
100~140K
Decoration Panel
BYC125K-W1
Sealing Member of Air Discharge Outlet
KDBHJ55K160
Panel Spacer
KDBJ55K160W
Fresh Air Intake Kit ∗3
Chamber Type
Without T Joint
KDDP55D160
With T Joint
KDDP55D160K
Direct Installation Type High Efficiency Filter Replacement High Efficiency Filter
KDDJ55X160
(Colorimetric Method 65%)
KAFP556D80
KAFP556D160
(Colorimetric Method 90%)
KAFP557D80
KAFP557D160
(Colorimetric Method 65%)
KAFJ552K80
KAFJ552K160
(Colorimetric Method 90%)
KAFJ553K80
KAFJ553K160
High-Efficiency Filter Chamber
KDDFP55D160
Long-Life Filter
KAFJ551K160
Resin Net (Gravimetric Method 50%)
Ultra–Long Life Filter
KAFP55D160
Ultra–Long Life Replacement Filter
KAFJ55K160H
Chamber Connection Kit ∗4
KKSJ55K160
Branch Duct Chamber Remote Controller
KDJ55K80
KDJ55K160
Wired Type ∗2
BRC1C61 (Note. 2)
Wireless Type
BRC7C613W
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring (Interlock for Fresh Air Intake Fan) ∗1
KRP1B57
Wiring Adaptor for Electrical Appendices ∗1
KRP4A53
Interface Adaptor for SkyAir Series
DTA102A52
Installation Box for Adaptor PCB
KRP1B98 C : 3D006559E
FH(Y)K–F(J) Name of Option
Remark
Decoration Panel
Kit Name 35·45F
60F·71FJ
BYK45FJW1
BYK71FJW1
Panel Spacer
KPBJ52F56W
KPBJ52F80W
Air Discharge Blind Panel
KDBJ52F56W
KDBJ52F80W
Replacement Long-Life Filter Resin Net
KAFJ521F56
KAFJ521F80
Discharge Grille
K–HV7AW
K–HV9AW
Flexible Duct with Shutter
KFDJ52F56
KFDJ52F80
Remote Controller
Wired Type ∗2
BRC1C61(Note. 2)
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring (Interlock for Fresh Air Intake Fan)
KRP1B51
Wiring Adaptor for Electrical Appendices
KRP4A51
Interface Adaptor for SkyAir Series
DTA102A52 DU423-9100C
Note:
1. 2. 3. 4. 5.
∗1 : Installation box for adaptor PCB(KRP1B98) is necessary. BRC1B61 is also available. ∗2 : Wire for Remote Controller : Field Supplied. ∗3 : Refer to the Option handbook for the detail. ∗4 : When using the filter (High–Efficiency Filter or Ultra–Long Life Filter) and the Fresh Air Intake Kit together, this kit is necessary.
SkyAir LU Series – Cooling Only –
99
Option List
ED21-301
FH(Y)B–F Name of Option
Remark
Decoration Panel Service Access Panel
Kit Name 35·45F
60·71F
BYBS45DJW1
BYBS71DJW1
100F
BYBS125DJW1
125F
KTBJ25K56W
KTBJ25K80W
KTBJ25K160W
(Colorimetric method 65%)
KAFJ252L56
KAFJ252L80
KAFJ252L160
(Colorimetric method 90%)
KAFJ253L56
KAFJ253L80
KAFJ253L160
Resin Net
KAFJ251K56
KAFJ251K80
KAFJ251K160
Filter Chamber for Bottom Suction
KAJ25L56D
KAJ25L80D
KAJ25L160D
Filter Chamber for Rear Suction
KAJ25L56B
KAJ25L80B
KAJ25L160B
Canvas Duct
KSAJ25K56
KSAJ25K80
KSAJ25K160
(φ150)
K-DG4BW
K-DG5BW
K-DG4BW
K-DG5BW
(φ200)
K-DG7BW
K-DG9BW
K-DG7BW
K-DG9BW
(φ150)
K-DGC4B
K-DGC5B
K-DGC4B
K-DGC5B
(φ200)
K-DGC7B
K-DGC9B
K-DGC7B
K-DGC9B
High-Efficiency Filter Replacement LongLife Filter
Discharge Grille Discharge Chamber Branch Duct
φ200 → φ150
K-DDV20A
(φ150)
(1m)K-FDK151B, (2m)K-FDK152B, (3m)K-FDK153B, (4m)K-FDK154B, (5m)K-FDK155B, (6m)K-FDK156B
(φ200)
(1m)K-FDK201B, (2m)K-FDK202B, (3m)K-FDK203B, (4m)K-FDK204B, (5m)K-FDK205B, (6m)K-FDK206B
Flexible Duct Blind Board
KBBJ25K56
KBBJ25K80
KBBJ25K160
Adaptor For Discharge
KDAJ25K56
KDAJ25K71
KDAJ25K140
Flange For Suction
KDJ2507K56
KDJ2507K80
KDJ2507K160
Remote Controller
Wired Type ∗2
BRC1C61 (Note. 2)
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring (Interlock for Fresh Air Intake Fan)
KRP1B54
Wiring Adaptor for Electrical Appendices ∗1
KRP4A51
Interface Adaptor for SkyAir Series
DTA102A52 DU423-999B
FUY–FJ Name of Option
Remark
Kit Name 71FJ
KDBHJ49F140
Decoration Panel for Air Discharge
KDBTJ49F80
KDBTJ49F140
Vertical Flap Kit
KDGJ49F80
KDGJ49F140
L Connection Piping Kit Remote Controller
KAFJ495F140 KHFJ49F80
KHFJ49F140
Wired Type ∗2
BRC1C61 (Note. 3)
Wireless Type
BRC7C529W
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified On/Off Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Wiring Adaptor for Electrical Appendices ∗1 Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB
100
125FJ
KDBHJ49F80
Replacement Long-Life Filter
Note:
100FJ
Sealing Member of Air Discharge Outlet ∗3
1. 2. 3. 4. 5.
∗1 : Installation box for adaptor PCB(KRP1B97) is necessary.
KRP4A53 DTA102A52 KRP1B97 3D013861B
BRC1B62 is also available. BRC1B61 is also available. ∗2 : Wire for Remote Controller : Field Supplied. ∗3 : This option is necessary for setting up 2-way (opposing directional) air flow when the air conditioner is installed.
SkyAir LU Series – Cooling Only –
ED21-301
Option List
1
FH(Y)–B Name of Option
Kit Name
Remark
35B
50B
60B
71B
100B
125B
Replacement Long-Life Filter
KAFJ501D56
KAFJ501D80
KAFJ501D112 KAFJ501D160
Drain Pump Kit
KDU50B50VE
KDU50B71VE
KDU50B125VE
L-Type Piping Kit (For Upward Direction) Remote Controller
KHFJ5F50
KHFJ5F60
KHFJ5F80
Wired Type ∗3
KHFJ5F160
BRC1C61
Wireless Type
BRC7E66
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring
KRP1B54
Wiring Adaptor for Electrical Appendices ∗1
KRP4A52
Interface Adaptor for SkyAir Series
DTA102A52
Installation Box Adaptor PCB
KRP1C93 3D028285A
FAY–L/FA Name of Option
Remark
Drain Pump Kit Remote Controller
Kit Name 71L
100FA
K-KDU572BVE
—
Wired Type ∗3 Wireless Type
BRC1C61 (Note. 5) BRC7E619
Set Back Time Clock
BRC7C611W
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Wiring Adaptor for Electrical Appendices Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB
KRP4A51 ∗4
KRP4A51
—
DTA102A52
—
KRP4A93
3D039142C C : DU427-965E
FVY–LA Name of Option
Remark
Replacement Long Life Filter
KAFJ95L160
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
Remote Controller for 2 Remote Control System intelligent Touch Controller Adaptor for Wiring ∗2 Group Control Adaptor ∗2 Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB
Note:
Kit Name 71~125LA
1. 2. 3. 4. 5.
∗1 : Installation box for adaptor PCB (KRP1C93) is necessary. ∗2 : Installation box for adaptor PCB (KRP4A95) is necessary. ∗3 : Wire for Remote Controller : Field Supplied. ∗4 : Installation box for adaptor PCB (KRP4A93) is necessary.
BRC1C61 DCS601B51 KRP1B57 KRP4A52 DTA102A52 KRP4A95 4D013855A
BRC1B61 is also available.
SkyAir LU Series – Cooling Only –
101
Option List
ED21-301
13.1.2 Outdoor Unit [R35~60G(A)] Kit Name
Name of Option
R35~60G(A)
Drain Piping Kit
KIS95 C : 3D005955A
13.1.3 Outdoor Unit [R71~140LU] Name of Option
Kit Name R71LU
Central Drain Plug Year-Round Cooling Kit
R100LU
R125LU
R140LU
KKPJ5F180 KRK5F80V1
KRK5F140V1
KRK5F160V1 3D039655
102
SkyAir LU Series – Cooling Only –
ED21-301
Field Piping and Wiring
14. Field Piping and Wiring 14.1
1
Field piping
14.1.1 Maximum Allowable Piping Length and Level Difference
R35G
R50, 60G(A)
Max. Allowable Piping Length
25 m
30 m
R71~140LU 50 m(Equivalent Length 70 m)
Max.Allowable Level Difference
15 m
15 m
30 m
14.1.2 Additional Refrigerant Charge Select the appropriate refrigerant charging amount from Table 1, 2 and charge the refrigerant. Fill out the notice plate attached in the rear of the front plate (2) for future servicing. R35G, 50 · 60G(A) This unit requires additional charging of refrigerant according to the length of pipe connected at the site. <Unit : g>
Table 1 Additional Charge
R35G, 50G(A)
R60G(A)
20 g/m (Exceeding 10 m)
20 g/m (Exceeding 5 m)
R71~140LU This unit requires additional charging of refrigerant according to the length of pipe connected at the site. When the entire refrigerant pipe length is within 30 meters, the additional changing is not needed. Take the following steps for proper charging. When Connected to one Indoor Unit (pair system)
Main pipe (L1)
Indoor unit One-way length of pipe (L): L1
1. Refrigerant charge amount Additional charging of refrigerant Select the amount of refrigerant which matches a length which exceeds the charge-less length, and add it. Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear surface of the front plate, as this is necessary for after-sales service.
FOR PAIR SYSTEM Table 1 The maximum allowable pipe length is 50 meters. Pipe excess length over 30 meters Additional Charging Amount
<unit : kg>
10m or less
20m or less
0.25
0.50
2. Recharging refrigerant When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the amount mentioned on the nameplate, and when the pipe length exceeds 30 meters, the charging amount is an addition of the amount stated on the nameplate and the additional charging amount. 1PN05248B-1
SkyAir LU Series – Cooling Only –
103
Field Piping and Wiring
ED21-301
14.1.3 Pump down operation method The outdoor unit is equipped with a low-pressure switch to protect the compressor. Take the following steps to perform the pumping-down operation. Never short-circuit the low-pressure switch in this operation. Procedure
Precautions
1. Start the fan operation with the remote controller.
Confirm that stop valves both on the liquid and gas side are open. Take care when the procedure 2 is done first because the indoor unit fan may operate automatically.
2. Push the pumping-down button on the PC board of the outdoor unit.
Compressor and outdoor fan will start operation automatically.
3. Continue operation for 1 min. until operation condition stabilizes.
—
4. Close the stop valve on the liquid side securely. (Refer to Fig. 1)
Insecure closing of the valve may result in burning of the compressor.
5. When the low-pressure switch is activated, the unit stops working. At this time, close the stop valve on the gas side.
—
This is the end of pumping-down operation. After pumping-down operation, the remote controller shows “U4” even when ON button on the remote controller is pressed, and it will not operate. Although the remote controller may or may not indicate “U4” according to circumstances at this time, it is normal. When the remote controller indicates “U4”, the indoor unit fan may operate (for about max 30 minutes). Turn off the main power supply switch and turn it on again in need of operation. 1. In case of G(A), KU Type
2. In case of LU Type How to use the stop valve (Refer to Fig. 2) Have a hex wrench ready. (4 mm and 6 mm) 1. Open the valve. a. Place the hex wrench on the valve bar and turn counter-clockwise. b. Stop when the valve bar no longer turns. It is now open. 2. Close the valve. a. Place the hex wrench on the valve bar and turn clockwise. b. Stop when the valve bar no longer turns. It is now closed. (Gas side) Opening direction (Liquid side) Opening direction
Fig. 2
104
1PN05248B-2
SkyAir LU Series – Cooling Only –
ED21-301
Field Piping and Wiring
Necessity of a trap Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases of deterioration of oil return, it will be necessary to provide a trap at an appropriate place in the riser gas piping. Trap installation spacing Indoor unit Oil trap
Gas piping
H 15m
Liquid piping
H Marks. Install trap at each difference in height 15m Outdoor unit
Note:
A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit. Caution to be taken when brazing refrigerant piping “Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”. (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible. (Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g . BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant leakage.
SkyAir LU Series – Cooling Only –
105
1
Field Piping and Wiring
14.2
106
ED21-301
Field Wiring
SkyAir LU Series – Cooling Only –
ED21-301
SkyAir LU Series (Twin, Triple, Double Twin) — Cooling Only — Model Series Twin
Class Indoor Units
35
50
60
FHYC
35K×2
50K×2
60K×2
71K×2 100K×2 125K×2
FHY
35B×2
50B×2
60B×2
71B×2 100B×2 125B×2
71LU
100LU
125LU
140LU
Outdoor R Units
Indoor Units
50
71
50
60
FHYC
50K×3
71K×3
50K×4
60K×4
FHY
50B×3
71B×3
50B×4
60B×4
140LU
200KU
200KU
250KU
Outdoor R Units
100
200KU
125
250KU
Double Twin
Triple
Class
71
Cautions 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
SkyAir LU Series – Cooling Only –
107
2
Features
ED21-301
1. Features SkyAir Series - Twin, Triple, Double Twin Systems (Simultaneous Operation System)
1.1
What are Twin, Triple, Double Twin Systems? One large room can be cooled simultaneously by two, three or four indoor units according to the environmental needs. Space saving for outdoor units. Possible to cool in outdoor temp. down to -15°C by using optional year-round cooling kit (KRK5F80, 140, 160V1) The operation limit has been extended down to an outdoor temp. of -15°C making it possible to operate the unit in the cooling mode whenever you need it all year round. Note:
Individual control (Such as room temperature) is not available.
(Ex.)Pair
(Ex.)Pair
(Ex.)Twin
(Ex.)Twin
(Ex.)Triple
(Ex.)Triple
FHYC50K
FHYC50K
FHYC50K
FHYC50K
FHYC50K
FHYC50K
Circuit breaker R140LU
Even Temperature Distribution Only one Remote Controller Only one Circuit Breaker (S0026-1)
(S0027)
Only one circuit breaker is needed for versatile electric work. Simple refrigerant system due to the branch piping kit specially designed for this system.
108
SkyAir LU Series – Cooling Only –
ED21-301
Model Name and Power Supply
2. Model Name and Power Supply 2.1
Twin, Triple and Double Twin System
2.1.1
50Hz Twin Indoor Units FHYC35KVE+FHYC35KVE
Outdoor Units
2
Power Supply
R71LUV1
FHY35BVE+FHY35BVE
R71LUV1
FHYC50KVE+FHYC50KVE
R100LUV1
FHY50BVE+FHY50BVE
R100LUV1
FHYC35KVE+FHYC35KVE
R71LUY1
FHY35BVE+FHY35BVE
R71LUY1
FHYC50KVE+FHYC50KVE
R100LUY1
FHY50BVE+FHY50BVE
R100LUY1
FHYC60KVE+FHYC60KVE
R125LUY1
FHY60BVE+FHY60BVE
R125LUY1
FHYC71KVE+FHYC71KVE
R140LUY1
FHY71BVE+FHY71BVE
R140LUY1
FHYC100KVE+FHYC100KVE
R200KUY1
FHY100BVE+FHY100BVE
R200KUY1
FHYC125KVE+FHYC125KVE
R250KUY1
FHY125BVE+FHY125BVE
R250KUY1
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
Triple Indoor Units
Outdoor Units
Power Supply
FHYC50KVE+FHYC50KVE+FHYC50KVE R140LUY1 FHY50BVE+FHY50BVE+FHY50BVE
R140LUY1
FHYC71KVE+FHYC71KVE+FHYC71KVE R200KUY1 FHY71BVE+FHY71BVE+FHY71BVE
3φ, 380~415V, 50Hz
R200KUY1
Double Twin Indoor Units
Outdoor Units
FHYC50KVE+FHYC50KVE+ FHYC50KVE+FHYC50KVE
R200KUY1
FHY50BVE+FHY50BVE+ FHY50BVE+FHY50BVE
R200KUY1
FHYC60KVE+FHYC60KVE+ FHYC60KVE+FHYC60KVE
R250KUY1
FHY60BVE+FHY60BVE+ FHY60BVE+FHY60BVE
R250KUY1
SkyAir LU Series – Cooling Only –
Power Supply
3φ, 380~415V, 50Hz
109
Model Name and Power Supply
2.1.2
ED21-301
60Hz Twin Indoor Units FHYC35KVE+FHYC35KVE
Outdoor Units
Power Supply
R71LUVAL
FHY35BVE+FHY35BVE
R71LUVAL
FHYC50KVE+FHYC50KVE
R100LUVAL
FHY50BVE+FHY50BVE
R100LUVAL
FHYC60KVE+FHYC60KVE
R125LUTAL
FHY60BVE+FHY60BVE
R125LUTAL
FHYC71KVE+FHYC71KVE
R140LUTAL
FHY71BVE+FHY71BVE
R140LUTAL
FHYC100KVE+FHYC100KVE
R200KUTAL
FHY100BVE+FHY100BVE
R200KUTAL
FHYC125KVE+FHYC125KVE
R250KUTAL
FHY125BVE+FHY125BVE
R250KUTAL
FHYC60KVE+FHYC60KVE
R125LUYAL
FHY60BVE+FHY60BVE
R125LUYAL
FHYC71KVE+FHYC71KVE
R140LUYAL
FHY71BVE+FHY71BVE
R140LUYAL
FHYC100KVE+FHYC100KVE
R200KUYAL
FHY100BVE+FHY100BVE
R200KUYAL
FHYC125KVE+FHYC125KVE
R250KUYAL
FHY125BVE+FHY125BVE
R250KUYAL
1φ, 220V, 60Hz
3φ, 220V, 60Hz
3φ, 380V, 60Hz
Triple Indoor Units
Outdoor Units
Power Supply
FHYC50KVE+FHYC50KVE+FHYC50KVE R140LUTAL FHY50BVE+FHY50BVE+FHY50BVE
R140LUTAL
FHYC71KVE+FHYC71KVE+FHYC71KVE R200KUTAL FHY71BVE+FHY71BVE+FHY71BVE
3φ, 220V, 60Hz
R200KUTAL
FHYC50KVE+FHYC50KVE+FHYC50KVE R140LUYAL FHY50BVE+FHY50BVE+FHY50BVE
R140LUYAL
FHYC71KVE+FHYC71KVE+FHYC71KVE R200KUYAL FHY71BVE+FHY71BVE+FHY71BVE
3φ, 380V, 60Hz
R200KUYAL
Double Twin Indoor Units
Note:
110
Outdoor Units
FHYC50KVE+FHYC50KVE+ FHYC50KVE+FHYC50KVE
R200KUTAL
FHY50BVE+FHY50BVE+ FHY50BVE+FHY50BVE
R200KUTAL
FHYC60KVE+FHYC60KVE+ FHYC60KVE+FHYC60KVE
R250KUTAL
FHY60BVE+FHY60BVE+ FHY60BVE+FHY60BVE
R250KUTAL
FHYC50KVE+FHYC50KVE+ FHYC50KVE+FHYC50KVE
R200KUYAL
FHY50BVE+FHY50BVE+ FHY50BVE+FHY50BVE
R200KUYAL
FHYC60KVE+FHYC60KVE+ FHYC60KVE+FHYC60KVE
R250KUYAL
FHY60BVE+FHY60BVE+ FHY60BVE+FHY60BVE
R250KUYAL
Power Supply
3φ, 220V, 60Hz
3φ, 380V, 60Hz
Power Supply Intake : Outdoor Unit
SkyAir LU Series – Cooling Only –
ED21-301
External Appearance
3. External Appearance 3.1
External Appearance
Indoor Units
2 FHY–B FHYC–K
Remote Controller
Wired Type
Wireless Type
Outdoor Units
R71LU
R100LU
R200KU
SkyAir LU Series – Cooling Only –
R125LU
R140LU
R250KU
111
Specifications
ED21-301
4. Specifications 4.1
50Hz
FHYC (Ceiling Mounted Cassette Type) <50Hz> - Twin Model
Indoor Unit Outdoor Unit
FHYC50KVE×2 FHYC60KVE×2 R100LUV1 — R100LUY1 R125LUY1 ∗1 Cooling Capacity (1)/(2)/(3) 10.6/10.5/10.5 13.0/12.8/12.8 36,100/35,700/35,700 44,500/43,600/43,600 9,100/9,000/9,000 11,200/11,000/11,000 Indoor Unit ∗3 FHYC50KVE×2 FHYC60KVE×2 Dimensions H×W×D mm 230×840×840 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×8×1.5 Face Area m² 0.331 Fan Model QTS45B14M Type Turbo Fan Motor Output W 45 Air Flow Rate ∗2 m³/min. (H)14–16 (L)10–12 (H)15–17 (L)11–13 (H)19–21 (L)14–16 Weight kg 24 Piping Liquid mm φ6.4 (Flare) Connections Gas mm φ12.7 (Flare) φ15.9 (Flare) Drain mm I.Dφ25×O.Dφ32 Remote Controller Wired BRC1C61 (Note. 6) (Option) Wireless BRC7C613W Decoration Model BYC125K–W1X2 Panel Color White (Option) ∗3 Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Unit V1 R71LUV1 R100LUV1 — Y1 R71LUY1 R100LUY1 R125LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 65 90 65+85 Air Flow Rate ∗2 m³/min. 48–51 59–62 92–100 Weight kg V1 72 87 — Y1 71 84 98 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm φ26.0 (Hole) Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Max. Length m 50 (Equivalent Length 70m) Ref. Piping Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039097
Note:
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–220V (380V)
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V (415V)
AS 1861
2. 3. 4. 5. 6.
112
FHYC35KVE×2 R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FHYC35KVE×2
V1 Y1 kW Btu/h kcal/h
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. ∗3 Each value shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
FHYC (Ceiling Mounted Cassette Type) <50Hz> - Twin Model
Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)
FHYC71KVE×2 R140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 FHYC71KVE×2 230×840×840 Cross Fin Coil 2×8×1.5 0.331 QTS45B14M
kW Btu/h kcal/h
FHYC100KVE×2 R200KUY1 22.5/22.2/22.0 76,800/75,800/75,100 19,400/19,100/18,900 FHYC100KVE×2
FHYC125KVE×2 R250KUY1 27.1/26.6/26.3 92,500/90,800/89,800 23,300/22,900/22,600 FHYC125KVE×2
2
Indoor Unit ∗3 Dimensions H×W×D mm 288×840×840 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×12×1.5 Face Area m² 0.497 Fan Model QTS45A17M Type Turbo Fan Motor Output W 45 90 Air Flow Rate ∗2 m³/min. (H)19–21 (L)14–15 (H)28–31 (L)21–24 (H)33–36 (L)24–27 Sound Pressure Level ∗2 dB(A) (H)35–37 (L)30–32 (H)39–41 (L)34–36 (H)42–44 (L)36–38 Weight kg 24 28 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9(Flare) φ19.1(Flare) Drain mm I.Dφ25×O.Dφ32 Remote Controller Wired BRC1C61 (Note. 5) (Option) Wireless BRC7C613W Decoration Model BYC125K–W1×2 Panel Color White (Option) ∗3 Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Unit R140LUY1 R200KUY1 R250KUY1 Color Ivory Dimensions H×W×D mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×50×2.0 Face Area m² 1.134 1.57 1.97 Comp. Model JT170BC–YE JT236D–P1YE JT335D–P1YE Type Hermetically Sealed Scroll Type Motor Output kW 4.50 5.5 9.0 Fan Model P47L11S×2 P52H11SM Type Propeller Motor Output W 65+90 230+190 Air Flow Rate ∗2 m³/min. 97–109 150–154 175–179 Weight kg 109 178 202 Piping Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) Drain mm φ26.0 (Hole) — Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Capillary Tube Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) Ref. Oil Model SUNISO 4GSDID–K Charge L 1.6 3.0 Drawing No. 4D039098 4D029963 4D029965
Note:
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
Model
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–380V
—
LU, KU
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
—
KU
7.5m
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
2. 3. 4. 5.
5m
50Hz–380V 50Hz–415V
JIS B8616
LU
AS 1861
LU, KU
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) and sound pressure level are shown at 380V–415V. Capacities are net, including a deduction for cooling for indoor fan motor heat. ∗3 Each value shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
113
Specifications
ED21-301
FHYC (Ceiling Mounted Cassette Type) <50Hz> - Triple / Double Twin Model
Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)
FHYC71KVE×3 R200KUY1
FHYC50KVE×4 R200KUY1
FHYC60KVE×4 R250KUY1 27.1/26.6/26.3 92,500/90,800/89,800 23,300/22,900/22,600 FHYC60KVE×4
22.5/22.2/22.0 76,800/75,800/75,100 19,400/19,100/18,900 Indoor Unit ∗3 FHYC71KVE×3 FHYC50KVE×4 Dimensions H×W×D mm 230×840×840 Coil Type Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×8×1.5 Face Area m² 0.331 Fan Model QTS45B14M Type Turbo Fan Motor Output W 45 Air Flow Rate ∗2 m³/min. (H)15–17 (L)11–12 (H)19–21 (L)14–15 (H)15–17 (L)11–12 (H)19–21 (L)14–16 Sound Pressure Level ∗2 dB(A) (H)33–35 (L)29–31 (H)35–37 (L)30–32 (H)33–35 (L)29–31 (H)35–37 (L)30–32 Weight kg 24 Piping Liquid mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) Connections Gas mm φ15.9(Flare) Drain mm I.Dφ25×O.Dφ32 Remote Controller Wired BRC1C61 (Note. 5) (Option) Wireless BRC7C613W Decoration Model BYC125K–W1×3 BYC125K–W1×4 Panel Color White (Option) ∗3 Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Unit R140LUY1 R200KUY1 R200KUY1 R250KUY1 Color Ivory Dimensions H×W×D mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×50×2.0 Face Area m² 1.134 1.57 1.97 Comp. Model JT170BC–YE JT236D–P1YE JT335D–P1YE Type Hermetically Sealed Scroll Type Motor Output kW 4.50 5.5 9.0 Fan Model P47L11S×2 P52H11SM Type Propeller Motor Output W 65+90 230+190 Air Flow Rate ∗2 m³/min. 97–109 150–154 175–179 Weight kg 109 178 202 Piping Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) Drain mm φ26.0 (Hole) — Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Capillary Tube Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) Ref. Oil Model SUNISO 4GSDID–K Charge L 1.6 3.0 Drawing No. 4D039098 4D029963 4D029965
Note:
kW Btu/h kcal/h
FHYC50KVE×3 R140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 FHYC50KVE×3
1. ∗1 The above data based on the conditions shown in the table below. Cooling
Piping length
Hz–Volts
Standard
Model
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–380V
—
LU, KU
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
—
KU
7.5m
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
2. 3. 4. 5.
114
Conversion Formulae
Mark
5m
50Hz–380V 50Hz–415V
JIS B8616
LU
AS 1861
LU, KU
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) and sound pressure level are shown at 380V–415V. Capacities are net, including a deduction for cooling for indoor fan motor heat. ∗3 Each value shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
FHY (Ceiling Suspended Type) <50Hz> - Twin Model
Indoor Unit Outdoor Unit
FHY35BVE×2 R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FHY35BVE×2
V1 Y1 kW Btu/h kcal/h
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Unit ∗4 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit
FHY50BVE×2 R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FHY50BVE×2 White
FHY60BVE×2 — R125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 FHY60BVE×2
2
195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 2×12×1.75 3×12×1.75 m² 0.182 0.233 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)16 (L)13 Resin Net (with Mold Resistant) kg 23 24 26 mm φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 5) BRC7E66 V1 R71LUV1 R100LUV1 — Y1 R71LUY1 R100LUY1 R125LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 65 90 65+85 Air Flow Rate ∗2 m³/min. 48–51 59–62 92–100 Weight kg V1 72 87 — Y1 71 84 98 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm φ26.0 (Hole) Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039100
Note:
mm
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–220V (380V)
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V (415V)
AS 1861
2. 3. 4. 5.
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. ∗4 Each value for indoor unit shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
115
Specifications
ED21-301
FHY (Ceiling Suspended Type) <50Hz> - Twin Model
Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)
Indoor Unit ∗4 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate ∗2 Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Notes:
FHY100BVE×2 FHY125BVE×2 R200KUY1 R250KUY1 kW 22.5/22.2/22.0 27.1/26.6/26.3 Btu/h 76,800/75,800/75,100 92,500/90,800/89,800 kcal/h 19,400/19,100/18,900 23,300/22,900/22,600 FHY100BVE×2 FHY125BVE×2 White mm 195×1,160×680 195×1,400×680 195×1,590×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.293 0.341 4D12K1AA1 3D12K2AA1 4D12KAA1 Sirocco Fan W 62 130 m³/min. (H)17 (L)14 (H)24 (L)20 (H)30 (L)25 Resin Net (with Mold Resistant) kg 27 32 35 mm φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 5) BRC7E66 R140LUY1 R200KUY1 R250KUY1 Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 JT170BC–YE JT236D–P1YE JT335D–P1YE Hermetically Sealed Scroll Type kW 4.50 5.5 9.0 P47L11S×2 P52H11SM Propeller W 65+90 230+190 m³/min. 97–109 150–154 175–179 kg 109 178 202 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039101 4D028444 4D028439
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
Model
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–380V
—
LU, KU
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
—
KU
7.5m
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
2. 3. 4. 5.
116
FHY71BVE×2 R140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 FHY71BVE×2
5m
50Hz–380V 50Hz–415V
JIS B8616
LU
AS 1861
LU, KU
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rate) is shown at 380V–415V. Capacities are net, including a deduction for cooling for indoor fan motor heat. ∗4 Each value for indoor unit shows the specification per one unit. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
FHY (Ceiling Suspended Type) <50Hz> - Triple / Double Twin Model
Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)
kW Btu/h kcal/h
Indoor Unit ∗4 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate ∗2 Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Notes:
FHY50BVE×3 R140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 FHY50BVE×3
FHY71BVE×3 R200KUY1
FHY50BVE×4 R200KUY1
FHY60BVE×4 R250KUY1 27.1/26.6/26.3 92,500/90,800/89,800 23,300/22,900/22,600 FHY60BVE×4
22.5/22.2/22.0 76,800/75,800/75,100 19,400/19,100/18,900 FHY71BVE×3 FHY50BVE×4 White mm 195×960×680 195×1,160×680 195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.182 0.233 0.182 0.233 3D12K1AA1 4D12K1AA1 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)17 (L)14 (H)13 (L)10 (H)16 (L)13 Resin Net (with Mold Resistant) kg 24 27 24 26 mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) mm φ15.9 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 5) BRC7E66 R140LUY1 R200KUY1 R200KUY1 R250KUY1 Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 JT170BC–YE JT236D–P1YE JT335D–P1YE Hermetically Sealed Scroll Type kW 4.50 5.5 9.0 P47L11S×2 P52H11SM Propeller W 65+90 230+190 m³/min. 97–109 150–154 175–179 kg 109 178 202 mm φ9.5 (Flare) φ12.7(Flare) φ15.9(Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039101 4D028444 4D028439
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
Model
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–380V
—
LU, KU
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
—
KU
7.5m
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
5m
50Hz–380V 50Hz–415V
JIS B8616
LU
AS 1861
LU, KU
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. ∗2 AFR (Air flow rate) is shown at 380V–415V. 3. Capacities are net, including a deduction for cooling for indoor fan motor heat. 4. ∗4 Each value for indoor unit shows the specification per one unit. 5. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
117
2
Specifications
4.2
ED21-301
60Hz
FHYC (Ceiling Mounted Cassette Type) <60Hz> - Twin Model
Indoor Unit Outdoor Unit
FHYC50KVE×2 FHYC60KVE×2 R100LUVAL — — R125LUTAL — R125LUYAL ∗1 Cooling Capacity (1)/(2) 11.6/11.4 14.5/14.3 39,700/38,900 49,600/48,800 10,000/9,800 12,500/12,300 Indoor Unit ∗2 FHYC50KVE×2 FHYC60KVE×2 Dimensions H×W×D mm 230×840×840 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×8×1.5 Face Area m² 0.331 Fan Model QTS45B14M Type Turbo Fan Motor Output W 45 Air Flow Rate m³/min. (H)14 (L)10 (H)15 (L)11 (H)19 (L)14 Weight kg 24 Piping Liquid mm φ6.4 (Flare) Connections Gas mm φ12.7(Flare) φ15.9(Flare) Drain mm I.Dφ25×O.Dφ32 Remote Controller Wired BRC1C61 (Note. 4) (Option) Wireless BRC7C613W Decoration Model BYC125K–W1×2 Panel (Option) Color White ∗2 Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Unit VAL R71LUVAL R100LUVAL — TAL — — R125LUTAL Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model VAL ZR36K3–PFV ZR47K3–PFV — TAL — — JT160BC YAL — — JT160BC–YH Type Hermetically Sealed Scroll Type Motor Output kW 2.24 2.92 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 75 100 95+75 Air Flow Rate m³/min. 49 59 94 Weight kg 75 92 98 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm φ26.0 (Hole) Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector(TAL·YAL). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039108
Notes:
FHYC35KVE×2 R71LUVAL — — 8.3/8.1 28,200/27,800 7,100/7,000 FHYC35KVE×2
VAL TAL YAL kW Btu/h kcal/h
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
JIS B8616
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.
118
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
FHYC (Ceiling Mounted Cassette Type) <60Hz> - Twin Model
Indoor Unit Outdoor Unit
∗1 Cooling Capacity (1)/(2)/(3)
kW Btu/h kcal/h
Indoor Unit ∗2 Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Sound Pressure Level Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Decoration Model Panel Color (Option) ∗2 Dimensions (H×W×D) Air Filter Weight Outdoor Unit Color Dimensions Coil
Comp.
Fan
Weight Piping Connections
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Notes:
FHYC71KVE×2 R140LUTAL R140LUYAL 16.1/15.8/– 55,000/53,900/– 13,800/13,500/– FHYC71KVE×2 230×840×840 Cross Fin Coil 2×8×1.5 0.331 QTS45B14M
TAL YAL
mm
FHYC100KVE×2 R200KUTAL R200KUYAL 22.5/22.2/20.0 76,800/75,800/68,300 19,400/19,100/17,200 FHYC100KVE×2
FHYC125KVE×2 R250KUTAL R250KUYAL 27.1/26.6/24.1 92,500/90,800/82,300 23,300/22,900/20,700 FHYC125KVE×2
2
288×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×12×1.5 m² 0.497 QTS45A17M Turbo Fan W 45 90 m³/min. (H)19 (L)14 (H)28 (L)21 (H)33 (L)24 dB(A) (H)35 (L)30 (H)39 (L)34 (H)42 (L)36 kg 24 28 mm φ9.5 (Flare) mm φ15.9(Flare) φ19.1(Flare) mm I.Dφ25×O.Dφ32 BRC1C61 (Note. 4) BRC7C613W BYC125K–W1×2 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R140LUTAL R200KUTAL R250KUTAL TAL R140LUYAL R200KUYAL R250KUYAL YAL Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 JT212D–P1 JT300D–P1 JT170BC TAL JT212D–P1YH JT300D–P1YH JT170BC–YH YAL Hermetically Sealed Scroll Type kW 4.50 5.5 7.5 P47L11S×2 P52H11SM Propeller W 100+75 230+190 m³/min. 101 160 190 kg 109 177 200 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039109 4D029964 4D029966
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Standard
Model
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
—
LU, KU
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
5m
—
KU
7.5m
JIS B8616
LU
(3)
Indoor : 29°CDB, 19.0°CWB Outdoor : 46°CDB, 24°CWB
7.5m
SSA 385/386
KU
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
119
Specifications
ED21-301
FHYC (Ceiling Mounted Cassette Type) <60Hz> - Triple / Double Twin Model
Indoor Unit Outdoor Unit
TAL YAL
∗1 Cooling Capacity (1)/(2)/(3)
kW Btu/h kcal/h
Indoor Unit ∗2 Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Sound Pressure Level Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Decoration Model Panel Color (Option) ∗2 Dimensions (H×W×D) Air Filter Weight Outdoor Unit Color Dimensions Coil
Comp.
Fan
Weight Piping Connections
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Notes:
FHYC50KVE×3 R140LUTAL R140LUYAL 16.1/15.8/– 55,000/53,900/– 13,800/13,500/– FHYC50KVE×3
FHYC71KVE×3 R200KUTAL R200KUYAL
FHYC50KVE×4 R200KUTAL R200KUYAL
FHYC60KVE×4 R250KUTAL R250KUYAL 27.1/26.6/24.1 92,500/90,800/82,300 23,300/22,900/20,700 FHYC60KVE×4
22.5/22.2/22.0 76,800/75,800/68,300 19,400/19,100/17,200 FHYC71KVE×3 FHYC50KVE×4 mm 230×840×840 Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 m² 0.331 QTS45B14M Turbo Fan W 45 m³/min. (H)15 (L)11 (H)19 (L)14 (H)15 (L)11 (H)19 (L)14 dB(A) (H)33 (L)29 (H)35 (L)30 (H)33 (L)29 (H)35 (L)30 kg 24 mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) mm φ15.9(Flare) mm I.Dφ25×O.Dφ32 BRC1C61 (Note. 4) BRC7C613W BYC125K–W1×3 BYC125K–W1×4 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R140LUTAL R200KUTAL R200KUTAL R250KUTAL TAL R140LUYAL R200KUYAL R200KUYAL R250KUYAL YAL Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 JT212D–P1 JT300D–P1 JT170BC TAL JT212D–P1YH JT300D–P1YH JT170BC–YH YAL Hermetically Sealed Scroll Type kW 4.50 5.5 7.5 P47L11S×2 P52H11SM Propeller W 100+75 230+190 m³/min. 101 160 190 kg 109 177 200 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039109 4D029964 4D029966
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Standard
Model
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
—
LU, KU
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
5m
—
KU
7.5m
JIS B8616
LU
(3)
Indoor : 29°CDB, 19.0°CWB Outdoor : 46°CDB, 24°CWB
7.5m
SSA 385/386
KU
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.
120
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
FHY (Ceiling Suspended Type) <60Hz> - Twin Model
Indoor Unit Outdoor Unit
FHY35BVE×2 R71LUVAL — — 8.3/8.1 28,200/27,800 7,100/7,000 FHY35BVE×2
VAL TAL YAL kW Btu/h kcal/h
∗1 Cooling Capacity (1)/(2)
Indoor Unit ∗2 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit
FHY50BVE×2 R100LUVAL — — 11.6/11.4 39,700/38,900 10,000/9,800 FHY50BVE×2 White
FHY60BVE×2 — R125LUTAL R125LUYAL 14.5/14.3 49,600/48,800 12,500/12,300 FHY60BVE×2
2
195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 2×12×1.75 3×12×1.75 m² 0.182 0.233 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)16 (L)13 Resin Net (with Mold Resistant) kg 23 24 26 mm φ6.4 (Flare) mm φ12.7 (Flare) φ15.9(Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 4) BRC7E66 VAL R71LUVAL R100LUVAL — TAL — — R125LUTAL YAL — — R125LUYAL Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model VAL ZR36K3–PFV ZR47K3–PFV — TAL — — JT160BC YAL — — JT160BC–YH Type Hermetically Sealed Scroll Type Motor Output kW 2.24 2.92 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 75 100 95+75 Air Flow Rate m³/min. 49 59 94 Weight kg 75 92 98 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm φ26.0 (Hole) Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039111
Notes:
mm
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
JIS B8616
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
121
Specifications
ED21-301
FHY (Ceiling Suspended Type) <60Hz> - Twin Model
Indoor Unit Outdoor Unit
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Unit ∗2 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Sound Pressure Level Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit Color Dimensions Coil
Comp.
Fan
Weight Piping Connections
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Notes:
FHY71BVE×2 R140LUTAL R140LUYAL 16.1/15.8/– 55,000/53,900/– 13,800/13,500/– FHY71BVE×2
FHY100BVE×2 FHY125BVE×2 R200KUTAL R250KUTAL R200KUYAL R250KUYAL 22.5/22.2/20.0 27.1/26.6/24.1 76,800/75,800/68,300 92,500/90,800/82,300 19,400/19,100/17,200 23,300/22,900/20,700 FHY100BVE×2 FHY125BVE×2 White mm 195×1,160×680 195×1,400×680 195×1,590×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.293 0.341 4D12K1AA1 3D12K2AA1 4D12K2AA1 Sirocco Fan W 62 130 m³/min. (H)17 (L)14 (H)24 (L)20 (H)30 (L)25 dB(A) — (H)42 (L)37 (H)44 (L)39 Resin Net (with Mold Resistant) kg 27 32 35 mm φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 4) BRC7E66 TAL R140LUTAL R200KUTAL R250KUTAL YAL R140LUYAL R200KUYAL R250KUYAL Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 TAL JT170BC JT212D–P1 JT300D–P1 YAL JT170BC–YH JT212D–P1YH JT300D–P1YH Hermetically Sealed Scroll Type kW 4.50 5.5 7.5 P47L11S×2 P52H11SM Propeller W 100+75 230+190 m³/min. 101 160 190 kg 109 177 200 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039112 4D028563 4D028564 TAL YAL kW Btu/h kcal/h
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Standard
Model
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
—
LU, KU
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
5m
—
KU
7.5m
JIS B8616
LU
(3)
Indoor : 29°CDB, 19.0°CWB Outdoor : 46°CDB, 24°CWB
7.5m
SSA 385/386
KU
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.
122
SkyAir LU Series – Cooling Only –
ED21-301
Specifications
FHY (Ceiling Suspended Type) <60Hz> - Triple / Double Twin Model
Indoor Unit Outdoor Unit
TAL YAL kW Btu/h kcal/h
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Unit Color Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate Sound Pressure Level
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Wired Wireless
Outdoor Unit Color Dimensions Coil
Comp.
Fan
Weight Piping Connections
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Notes:
FHY50BVE×3 R140LUTAL R140LUYAL 16.1/15.8/– 55,000/53,900/– 13,800/13,500/– FHY50BVE×3
FHY71BVE×3 R200KUTAL R200KUYAL
FHY50BVE×4 R200KUTAL R200KUYAL
FHY60BVE×4 R250KUTAL R250KUYAL 27.1/26.6/24.1 92,500/90,800/82,300 23,300/22,900/20,700 FHY60BVE×4
22.5/22.2/20.0 76,800/75,800/68,300 19,400/19,100/17,200 FHY71BVE×3 FHY50BVE×4 White mm 195×960×680 195×1,160×680 195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.182 0.233 0.182 0.233 3D12K1AA1 4D12K1AA1 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)17 (L)14 (H)13 (L)10 (H)16 (L)13 dB(A) — (H)39 (L)35 (H)38 (L)33 (H)38 (L)33 Resin Net (with Mold Resistant) kg 24 26 23 26 mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) φ6.4 (Flare) mm φ15.9 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 4) BRC7E66 TAL R140LUTAL R200KUTAL R200KUTAL R250KUTAL YAL R140LUYAL R200KUYAL R200KUYAL R250KUYAL Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 TAL JT170BC JT212D–P1 JT300D–P1 YAL JT170BC–YH JT212D–P1YH JT300D–P1YH Hermetically Sealed Scroll Type kW 4.50 5.5 7.5 P47L11S×2 P52H11SM Propeller W 100+75 230+190 m³/min. 101 160 190 kg 109 177 200 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039112 4D028563 4D028564
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Standard
Model
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
—
LU, KU
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
5m
—
KU
7.5m
JIS B8616
LU
(3)
Indoor : 29°CDB, 19.0°CWB Outdoor : 46°CDB, 24°CWB
7.5m
SSA 385/386
KU
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
123
2
Dimensions and Service Space
ED21-301
5. Dimensions and Service Space 5.1
Indoor Unit
5.1.1
FHYC (Ceiling Mounted Cassette Type)
FHYC35K + BYC125K-W1 C 860~890 Ceiling opening
80
2× 100=200
Unit (mm)
85
300 or less 680 Suspension position
950
(165)
Note3.
420
9
Branch duct connection
350 C
view 60
4-M4 Hole (prepared hole) φ7
80 80
6
40
860~890 Ceiling opening
950
780 Suspension position
10
5
840
55
55
55
80 2× 100=200
12-M4 Hole (prepared hole)
85
5
150
2
1
4
40 350
Branch duct connection
A
∗1500mm or more Required space ∗1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more.
1000 or more Required space
30
8
260 270 315
165
95 110
295
For fresh air intake kit connection (direct installation type)
view
55
840
125 150 240
750 10
B B
200
Adjustable (0~550)
420
3
40
230
view
240
Suspension bolt 4-M8~M10
160
7 A
Description
Name Number 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.
3. In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.
2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
5 6 7 8
φ6.4 flare φ12.7 flare VP25
Remote control code and control wiring connection
Air discharge grille Air suction grille Port for water supply Corner decoration cover
9 10 Drain hose
O.D.32
C : 3D012310B
FHYC50K + BYC125K-W1 FHYC60K + BYC125K-W1 Unit (mm)
C
950
2× 100=200 85
80
860~890 Ceiling opening 300 or less 680 Suspension position
(165)
Note3.
420
9 10
6
Branch duct connection
C view 60
4-M4 Hole (prepared hole) φ7
80
5
80
950
780 Suspension position 860~890 Ceiling opening
40 350
840
55
12-M4 Hole (prepared hole)
8
5
260 270 315
4
1
2
40 350
Branch duct connection
A
165 1000 or more Required space
125 150 240 240
For fresh air intake kit connection (direct installation type)
55
2×100=200 85
95 110
80
150
750 Adjustable (0~550)
55
840 295
200
230
B view
55
30 Suspension bolt 4-M8~M10
B
3
40
10
420
160
7 A view
∗1500mm or more Required space 1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more. Name Number 1 Liquid pipe connection Gas pipe connection 2 Drain pipe connection 3 Power supply connection 4
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.
3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.
5
Remote control code and control wiring connection
6
2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
9 10
Air discharge grille Air suction grille Port for water supply Corner decoration cover
7 8
Drain hose
Description φ6.4 flare φ15.9 flare VP25
O.D.32
C : 3D012311B
124
SkyAir LU Series – Cooling Only –
ED21-301
Dimensions and Service Space
FHYC71K + BYC125K-W1 Unit (mm)
1000 or more
2
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
C : 3D012312C
FHYC100K + BYC125K-W1 FHYC125K + BYC125K-W1 Unit (mm)
C
(195)
950
2× 100=200 85
80
860~890 Ceiling opening 300 or less 680 Suspension position
Note3.
165
6
40 350
Branch duct connection
C view
4-M4 Hole (prepared hole) φ7 5
60 80 80
950
780 Suspension position 860~890 Ceiling opening
10
155
420
9
160
7 A view
420
B
5
260 270 315
4
1
14-M4 Hole (prepared hole)
2× 100=200 85
195
150
125 150 298 240
8
55
840 80
200
30 Suspension bolt 4-M8~M10
55
40 50 155 165
55
840 295
2
40 350
Branch duct connection
A
1000 or more Required space
55
40
10
288
750 Adjustable (0~550)
B view
3
Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.
3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.
2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.
4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
SkyAir LU Series – Cooling Only –
For fresh air intake kit connection (direct installation type)
∗1500mm or more Required space ∗1500mm or more
∗1500mm or more
∗1500mm or more ∗ When the discharge grill is closeout, the required is space 200mm or more. Number Name 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection 5 6 7 8 9 10
Description φ9.5 flare φ19.1 flare VP25
Remote control code and control wiring connection
Air discharge grille Air suction grille Port for water supply Corner decoration cover Drain hose
O.D.32
C : 3D012313C
125
Dimensions and Service Space
5.1.2
ED21-301
FHYC with High Efficiency Filter
KAFP556D80·557D80 for FHYC35~71K
Unit (mm)
290
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975A
KAFP556D160·557D160 for FHYC100~125K
Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032976A
126
SkyAir LU Series – Cooling Only –
ED21-301
5.1.3
Dimensions and Service Space
FHYC with Fresh Air Intake Kit (Without T Joint, Duct Fan)
KDDP55D160 for FHYC35~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
2
Refrigerant Piping
Note 4
View
Service Access Panel : 450×450mm or more Refer to Note 2
290
Installation Service Access Panel
Connection Chamber (Right)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
How to connect Chamber 4 Independently(Refer to Note 5,6)
Applicable Models SkyAir
FH(Y)C35~71K
5 4 3 2 1 Number
Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981A
KDDP55D160 for FHYC100~125K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
View
Service Access Panel : 450×450mm or more Refer to Note 2
Note 4
Installation Service Access Panel
Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
SkyAir LU Series – Cooling Only –
Applicable Models SkyAir
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984A
127
Dimensions and Service Space
5.1.4
ED21-301
FHYC with Fresh Air Intake Kit (With T Joint, Without Duct Fan)
KDDP55D160K for FHYC35~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Flexible Duct (Accessory)
Installation Service Access Panel
Service Access Panel : 450×450mm or more Refer to Note 2
Suction Duct (K-KFD9A) Optional (Accessory) T Joint
Plate Band
(Accessory)
290
(Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
Applicable Models SkyAir
FH(Y)C35~71K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032987A
KDDP55D160K for FHYC100~125K Service Access Panel : 450×450mm or more Refer to Note 2
Installation Service Access Panel
Unit (mm) Flexible Duct (Accessory)
Service Access Panel : 450×450mm or more Refer to Note 2 T Joint (Accessory)
Plate Band (Accessory)
Suction Duct (K-KFD9A) Optional (Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
128
Applicable Models SkyAir
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032990A
SkyAir LU Series – Cooling Only –
ED21-301
5.1.5
Dimensions and Service Space
FHYC with Panel Spacer
KDBJ55K160W for FHYC35~71K Unit (mm)
2
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005390E
KDBJ55K160W for FHYC100~125K Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005391D
SkyAir LU Series â&#x20AC;&#x201C; Cooling Only â&#x20AC;&#x201C;
129
Dimensions and Service Space
5.1.6
ED21-301
FHY (Ceiling Suspended Type)
FHY35B FHY50B Unit (mm)
A
Model
FH(Y)35B FH(Y)50B
A
12.7
15.9
3D027536C 3D028600
FHY60B FHY71B Unit (mm)
A
130
Model
FH(Y)60B
FHY71B
A
6.4
9.5
3D027537 3D027538B
SkyAir LU Series – Cooling Only –
ED21-301
Dimensions and Service Space
FHY100B Unit (mm)
2
3D027539B
FHY125B Unit (mm)
3D027540
SkyAir LU Series – Cooling Only –
131
Dimensions and Service Space
5.2
ED21-301
Remote Controller
BRC7C613W (Wireless Type for FHYC~K)
BRC7E66 (Wireless Type for FHY~B)
3D028963
132
SkyAir LU Series – Cooling Only –
ED21-301
Dimensions and Service Space
BRC1C61 (Wired Type)
More comfortable operation by thermo sensor in the Remote Controller Applicable Model FH(Y)K-F(J) FH(Y)-B FH(Y)C-K FH(Y)B-F FUY-FJ FV(Y)-LA (Available for 2 remote control use) FAY-FA/L
2
C : 3D028952
SkyAir LU Series – Cooling Only –
133
Dimensions and Service Space
5.3
ED21-301
Outdoor Unit
R71LU Unit (mm)
3D039213
R100LU Unit (mm)
3D039214
134
SkyAir LU Series – Cooling Only –
ED21-301
Dimensions and Service Space
R125LU Unit (mm)
2
3D039215
R140LU Unit (mm)
3D039216
SkyAir LU Series – Cooling Only –
135
Dimensions and Service Space
ED21-301
R200KU Unit (mm)
3D029265
R250KU Unit (mm)
3D029264
136
SkyAir LU Series – Cooling Only –
ED21-301
5.4
Dimensions and Service Space
Installation Service Space for R71LU, 100LU, 125LU, 140LU
140 140
2
3D039172-1
SkyAir LU Series – Cooling Only –
137
Dimensions and Service Space
ED21-301
3D039172-2
138
SkyAir LU Series – Cooling Only –
ED21-301
5.5
Dimensions and Service Space
Installation Service Space for R200KU, 250KU
2
3D006578A
SkyAir LU Series – Cooling Only –
139
Piping Diagrams
ED21-301
6. Piping Diagrams 6.1
Twin
3D039765
R71LU
140
SkyAir LU Series – Cooling Only –
ED21-301
Piping Diagrams
3D039766
R100LU
2
SkyAir LU Series – Cooling Only –
141
Piping Diagrams
ED21-301
3D039767
R125LU
142
SkyAir LU Series – Cooling Only –
ED21-301
Piping Diagrams
3D039768
R140LU
2
SkyAir LU Series – Cooling Only –
143
Piping Diagrams
ED21-301
3D030194
R200KU R250KU
144
SkyAir LU Series – Cooling Only –
ED21-301
6.2
Piping Diagrams
Triple
3D039769
R140LU
SkyAir LU Series – Cooling Only –
145
2
Piping Diagrams
ED21-301
3D030195
R200KU
146
SkyAir LU Series – Cooling Only –
ED21-301
6.3
Piping Diagrams
Double Twin
3D030196
R200KU R250KU
SkyAir LU Series – Cooling Only –
2
147
Wiring Diagrams
ED21-301
7. Wiring Diagrams 7.1
Indoor Unit
FHYC35KVE FHYC50KVE FHYC60KVE FHYC71KVE FHYC100KVE FHYC125KVE
3D005668C
148
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
FHY35BVE FHY50BVE FHY60BVE FHY71BVE FHY100BVE FHY125BVE
2
3D027502
SkyAir LU Series – Cooling Only –
149
Wiring Diagrams
7.2
Outdoor Unit
7.2.1
50Hz
ED21-301
R71LUV1 R100LUV1
3D037640C
R71LUY1 R100LUY1
3D037642C
150
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
R125LUY1 R140LUY1
2
3D037644C
R200KUY1 R250KUY1
3D029091A
SkyAir LU Series – Cooling Only –
151
Wiring Diagrams
7.2.2
ED21-301
60Hz
R71LUVAL R100LUVAL
3D037935C
R125LUTAL R140LUTAL
3D037936C
152
SkyAir LU Series – Cooling Only –
ED21-301
Wiring Diagrams
R125LUYAL R140LUYAL
2
3D037937C
R200KUTAL R250KUTAL
3D029092A
SkyAir LU Series – Cooling Only –
153
Wiring Diagrams
ED21-301
R200KUYAL R250KUYAL
3D029091A
154
SkyAir LU Series – Cooling Only –
ED21-301
Capacity Tables
8. Capacity Tables 8.1
50Hz
35 × 2 + R71LUV1 35 × 2 + R71LUY1
2
3D039614
50 × 2 + R100LUV1 50 × 2 + R100LUY1
3D039627A
SkyAir LU Series – Cooling Only –
155
Capacity Tables
ED21-301
60 × 2 + R125LUY1
3D039636
50 × 3 + R140LUY1 71 × 2 + R140LUY1
3D039645
156
SkyAir LU Series – Cooling Only –
ED21-301
Capacity Tables
50 × 4 + R200KUY1 71 × 3 + R200KUY1 100 × 2 + R200KUY1
2
3D030166A
60 × 4 + R250KUY1 125 × 2 + R250KUY1
3D030168A
SkyAir LU Series – Cooling Only –
157
Capacity Tables
8.2
ED21-301
60Hz
35 × 2 + R71LUVAL
3D039616
50 × 2 + R100LUVAL
3D039629
158
SkyAir LU Series – Cooling Only –
ED21-301
Capacity Tables
60 × 2 + R125LUTAL
2
3D039639
50 × 3 + R140LUTAL 71 × 2 + R140LUTAL
3D039649
SkyAir LU Series – Cooling Only –
159
Capacity Tables
ED21-301
60 × 2 + R125LUYAL
3D039640
50 × 3 + R140LUYAL 71 × 2 + R140LUYAL
3D039653
160
SkyAir LU Series – Cooling Only –
ED21-301
Capacity Tables
50 × 4 + R200KUTAL / YAL 71 × 3 + R200KUTAL / YAL 100 × 2 + R200KUTAL / YAL
2
3D030167A
60 × 4 + R250KUTAL / YAL 125 × 2 + R250KUTAL / YAL
3D030169A
SkyAir LU Series – Cooling Only –
161
Capacity Tables
8.3
ED21-301
Capacity Correction Factor by The Length of Refrigerant Piping The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit) Reference Data 1. In case of piping length 5m
Cooling capacity correction factor
100
95
90 200 100, 250 71 125
85
80 140 75
0
5
10
30 35 15 20 25 Length of refrigerant piping (Total length)
40
45
50 (m) (S0028)
2. In case of piping length 7.5m
Cooling capacity correction factor
100
95
90
85
200 100, 250 71 125
80
140
75
Note:
162
0
5
7.5 10
30 35 15 20 25 Length of refrigerant piping (Total length)
40
45
50 (m)
1. line: Correction factor for cooling capacity 2. The correction factor remains the same whether the outdoor unit is to be installed above or below the indoor unit. 3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the range of its limitation.
SkyAir LU Series – Cooling Only –
ED21-301
Operation Limits
9. Operation Limits 9.1
Operation Limits
R71LUV1 / R71LUY1 R100LUV1 / R100LUY1 R125LUY1 R140LUY1 R71LUVAL R100LUVAL R125LUTAL / R125LUYAL R140LUTAL / R140LUYAL
2
3D039657
R200KUY1 R250KUY1
R200KUTAL / R200KUYAL R250KUTAL / R200KUYAL
3D030170
Notes:
The graphs are based on the following conditions. Equivalent piping length 5m Level difference 0m Air flow rate High
SkyAir LU Series – Cooling Only –
163
Sound Level
ED21-301
10. Sound Level 10.1
Overall Sound Level dB(A) Model
50Hz
60Hz
220V
240V
Measuring Location
220V
H
L
H
L
H
L
FHYC35K FHYC50K FHYC60K FHYC71K FHYC100K FHYC125K
33 33 35 35 39 42
29 29 30 30 34 36
35 35 37 37 41 44
31 31 32 32 36 38
33 33 35 35 39 42
29 29 30 30 34 36
FHYC
FHY35B FHY50B FHY60B FHY71B FHY100B FHY125B
37 38 38 39 42 44
32 33 33 35 37 39
37 38 38 39 42 44
32 33 33 35 37 39
37 38 38 39 42 44
32 33 33 35 37 39
FHY
50Hz 380V
50Hz 415V
60Hz 220V
R71LU R100LU R125LU R140LU R125LUTAL R140LUTAL
48 49 49 54 — —
49 50 50 55 — —
49 51 — — 51 55
R125LUYAL R140LUYAL
— —
— —
51 55
50Hz 380V
50Hz 415V
60Hz 220 · 380V
60 61
61 62
60 61
Microphone
4D028280A
R71~140LU
Microphone
60Hz 380V
R200 R250
4D039806
R200KU / R250KU
Microphone
4D030106
Note:
164
Operation sound is measured in an anechoic chamber.
SkyAir LU Series – Cooling Only –
ED21-301
10.2
Sound Level
Octave Band Level
10.2.1 Indoor Units FHYC35KVE FHYC50KVE
FHYC60KVE FHYC71KVE
FHYC100KVE
2 H H
L L
4D006198A
FHYC125KVE
FHY35BVE
FHY50BVE
4D028280A
FHY60BVE
FHY71BVE
4D028282
4D028281A
FHY100BVE
4D028355
4D028283
FHY125BVE
4D028284
SkyAir LU Series – Cooling Only –
165
Sound Level
ED21-301
10.2.2 Outdoor Units R71LUV1 / R71LUY1
R100LUV1 / R100LUY1
4D039802
R140LUY1
4D039804
R71LUVAL
4D039808
R125LUTAL / R125LUYAL
166
4D039806
R100LUVAL
4D039810
R140LUTAL / R140LUYAL
4D039812
R250KUY1
R125LUY1
4D039811
R200KUY1
4D039813
R200KUTAL / R200KUYAL
R250KUTAL / R250KUYAL
SkyAir LU Series – Cooling Only –
ED21-301
Electric Characteristics
11. Electric Characteristics 11.1
50Hz Unit combination Indoor
FHYC35KVE×2 R71LUV1 FHY35BVE×2
R71LUV1
FHYC35KVE×2 R71LUY1 FHY35BVE×2
R71LUY1
FHYC50KVE×2 R100LUV1 FHY50BVE×2
R100LUV1
FHYC50KVE×2 R100LUY1 FHY50BVE×2
R100LUY1
FHYC60KVE×2 R125LUY1 FHY60BVE×2
Power supply
Outdoor
R125LUY1
Hz-Volts 50-220 50-230 50-240 50-220 50-230 50-240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-220 50-230 50-240 50-220 50-230 50-240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240
Comp
Voltage range MCA TOCA MFA 19.6
23.8
30
19.2
23.8
30
Max. 50Hz 456/264V
8.3
9.3
15
Min. 50Hz 342/198V
8.3
9.3
15
24.9
28.0
40
24.9
28.0
40
Max. 50Hz 456/264V
10.4
12.0
15
Min. 50Hz 342/198V
10.4
12.0
15
Max. 50Hz 456/264V
12.8
15.5
20
Min. 50Hz 342/198V
12.8
15.5
20
Max. 50Hz 264V Min. 50Hz 198V
Max. 50Hz 264V Min. 50Hz 198V
LRA
RLA
82 78 75 82 78 75 40 38 37 40 38 37 114 109 105 114 109 105 50 48 46 50 48 46 51 53 56 51 53 56
14.2 13.6 13.0 14.2 13.6 13.0 5.2 4.9 4.7 5.2 4.9 4.7 18.3 17.5 16.7 18.3 17.5 16.7 6.7 6.4 6.1 6.7 6.4 6.1 8.1 8.1 8.2 8.1 8.1 8.2
OFM kW
FLA
IFM kW
FLA
0.065
0.6
0.045×2 0.6×2
0.065
0.6
0.062×2 0.6×2
0.065
0.6
0.045×2 0.6×2
0.065
0.6
0.062×2 0.6×2
0.09
0.8
0.045×2 0.6×2
0.09
0.8
0.062×2 0.6×2
0.09
0.8
0.045×2 0.6×2
0.09
0.8
0.062×2 0.6×2
0.065 + 0.085 0.065 + 0.085
0.6 + 0.7 0.6 + 0.7
2
0.045×2 0.6×2 0.062×2 0.6×2 3D039580
Unit combination Indoor
Outdoor
FHYC50KVE×3 R140LUY1 FHYC71KVE×2 R140LUY1 FHY50BVE×3 FHY71BVE×2
Power supply
R140LUY1 R140LUY1
Hz-Volts 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240
Comp
Voltage range MCA TOCA MFA
Max. 50Hz 456/264V
13.8
18.2
25
13.2
17.6
25
13.8
18.2
25
13.2
17.6
25
Min. 50Hz 342/198V
LRA
RLA
67 71 74 67 71 74 67 71 74 67 71 74
8.2 8.2 8.5 8.2 8.2 8.5 8.2 8.2 8.5 8.2 8.2 8.5
OFM kW 0.065 + 0.090 0.065 + 0.090 0.065 + 0.090 0.065 + 0.090
FLA 0.6 + 0.8 0.6 + 0.8 0.6 + 0.8 0.6 + 0.8
IFM kW
FLA
0.045×3 0.6×3 0.045×2 0.6×2 0.062×3 0.6×3 0.062×2 0.6×2 3D039580
Unit combination Indoor
FHYC100KVE×2 R200KUY1 FHY100BVE×2
R200KUY1
FHYC71KVE×3 R200KUY1 FHY71BVE×3
R200KUY1
FHYC50KVE×4 R200KUY1 FHY50BVE×4
R200KUY1
FHYC125KVE×2 R250KUY1 FHY125BVE×2
R250KUY1
FHYC60KVE×4 R250KUY1 FHY60BVE×4
Power supply
Outdoor
R250KUY1
Hz-Volts 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240
Comp
Voltage range MCA TOCA MFA 20.8
22.5
30
20.2
21.9
30
Max. 50Hz 456/264V
20.6
22.3
30
Min. 50Hz 342/198V
20.6
22.3
30
21.2
22.9
30
21.2
22.9
30
26.0
28.5
40
Max. 50Hz 456/264V
25.4
27.9
40
Min. 50Hz 342/198V
26.4
28.9
40
26.4
28.9
40
LRA
RLA
87 92 95 87 92 95 87 92 95 87 92 95 87 92 95 87 92 95 128 135 140 128 135 140 128 135 140 128 135 140
12.6 12.4 13.0 12.6 12.4 13.0 12.6 12.4 13.0 12.6 12.4 13.0 12.6 12.4 13.0 12.6 12.4 13.0 16.3 15.7 17.2 16.3 15.7 17.2 16.3 15.7 17.2 16.3 15.7 17.2
OFM kW 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19
FLA 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2
IFM kW
FLA
0.090×2 1.0×2 0.130×2 0.7×2 0.045×3 0.6×3 0.062×3 0.6×3 0.045×4 0.6×4 0.062×4 0.6×4 0.090×2 1.0×2 0.130×2 0.7×2 0.045×4 0.6×4 0.062×4 0.7×4 3D029999A 3D030000A
SkyAir LU Series – Cooling Only –
167
Electric Characteristics
11.2
ED21-301
60Hz Unit combination Indoor
Outdoor
Power supply Hz-Volts
Comp
Voltage range MCA TOCA MFA
OFM
LRA
RLA
kW
FLA
IFM kW
FLA
FHYC35KVE×2 R71LUVAL
60-220
21.1
24.0
30
99
15.3
0.075
0.8
0.045×2 0.6×2
FHY35BVE×2
60-220
21.3
24.0
30
99
15.3
0.075
0.8
0.062×2 0.7×2
25.7
28.1
40
143
18.9
0.1
0.9
0.045×2 0.6×2
25.9
28.3
40
143
18.9
0.1
0.9
0.062×2 0.7×2
0.075 + 0.095 0.075 + 0.095 0.075
0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9
R71LUVAL
FHYC50KVE×2 R100LUVAL
60-220
FHY50BVE×2
R100LUVAL
60-220
FHYC60KVE×2 R125LUTAL
60-220
23.3
24.5
30
137
16.3
FHY60BVE×2
R125LUTAL
60-220
23.5
24.7
30
137
16.3
FHYC60KVE×2 R125LUYAL
60-380
14.4
15.5
20
66
9.2
FHY60BVE×2
60-380
14.6
15.7
20
66
9.2
R125LUYAL
Max. 60Hz 242V Min. 60Hz 198V
Max. 60Hz 418V Min. 60Hz 342V
+
0.095 0.075 +
0.095
0.045×2 0.6×2 0.062×2 0.7×2 0.045×2 0.6×2 0.062×2 0.7×2 3D039581
Unit combination Indoor
Outdoor
Power supply Hz-Volts
Comp
Voltage range MCA TOCA MFA
LRA
RLA
OFM
23.6
31.8
40
146
15.8
23.6
31.8
40
146
15.8
22.9
31.1
40
146
15.8
60-220
22.9
31.1
40
146
15.8
FHYC50KVE×3 R140LUYAL
60-380
14.7
18.8
25
75
8.7
FHY50BVE×3
R140LUYAL
60-380
14.7
18.8
25
75
8.7
FHYC71KVE×2 R140LUYAL
60-380
14.0
18.1
25
75
8.7
FHY71BVE×2
60-380
14.0
18.1
25
75
8.7
FHYC50KVE×3 R140LUTAL
60-220
FHY50BVE×3
R140LUTAL
60-220
FHYC71KVE×2 R140LUTAL
60-220
FHY71BVE×2
R140LUTAL
R140LUYAL
Max. 60Hz 242V Min. 60Hz 198V
Max. 60Hz 418V Min. 60Hz 342V
kW 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100
FLA 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9
IFM kW
FLA
0.045×3 0.7×3 0.062×3 0.7×3 0.045×2 0.7×2 0.062×2 0.7×2 0.045×3 0.7×3 0.062×3 0.7×3 0.045×2 0.7×2 0.062×2 0.7×2 3D039581
168
SkyAir LU Series – Cooling Only –
ED21-301
Electric Characteristics
Unit combination Indoor
Power supply
Outdoor
Hz-Volts
Comp
Voltage range MCA TOCA MFA
LRA
RLA
FHYC50KVE×4 R200KUTAL
60-220
35.5
39.2
50
161
23.4
FHY50BVE×4
R200KUTAL
60-220
35.5
39.2
50
161
23.4
FHYC71KVE×3 R200KUTAL
60-220
Max. 60Hz 242V 34.8
38.5
50
161
23.4
Min. 60Hz 198V
R200KUTAL
60-220
34.8
38.5
50
161
23.4
FHYC100KVE×2 R200KUTAL
60-220
34.7
38.4
50
161
23.4
FHY100BVE×2
60-220
34.7
38.4
50
161
23.4
FHYC50KVE×4 R200KUYAL
60-380/220
23.2
24.2
30
81
13.6
FHY50BVE×4
60-380/220
23.2
24.2
30
81
13.6
60-380/220 Max. 60Hz 418/242V
22.5
23.5
30
81
13.6
Min. 60Hz 342/198V
22.5
23.5
30
81
13.6
FHY71BVE×3
R200KUTAL
R200KUYAL
FHYC71KVE×3 R200KUYAL R200KUYAL
60-380/220
FHYC100KVE×2 R200KUYAL
60-380/220
22.4
23.4
30
81
13.6
FHY100BVE×2
60-380/220
22.4
23.4
30
81
13.6
FHYC60KVE×4 R250KUTAL
60-220
41.1
52.2
60
225
27.9
FHY60BVE×4
R250KUTAL
60-220
41.1
52.2
60
225
27.9
FHYC125KVE×2 R250KUTAL
60-220
40.3
51.4
60
225
27.9
FHY125BVE×2
60-220
40.5
51.6
60
225
27.9
FHYC60KVE×4 R250KUYAL
60-380/220
27.8
30.2
40
107
17.3
FHY60BVE×4
60-380/220 Max. 60Hz
27.8
30.2
40
107
17.3
FHY71BVE×3
R200KUYAL
R250KUTAL
R250KUYAL
Max. 60Hz 242V Min. 60Hz 198V
418/242V
FHYC125KVE×2 R250KUYAL
60-380/220 Min. 60Hz 342/198V
27.0
29.4
40
107
17.3
FHY125BVE×2
60-380/220
27.2
29.4
40
107
17.3
R250KUYAL
OFM kW 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19
FLA 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6
IFM kW
FLA
0.045×4 0.7×4
2
0.062×4 0.7×4 0.045×3 0.7×3 0.062×3 0.7×3 0.090×2 1.0×2 0.130×2 1.0×2 0.045×4 0.7×4 0.062×4 0.7×4 0.045×3 0.7×3 0.062×3 0.7×3 0.090×2 1.0×2 0.130×2 1.0×2 0.045×4 0.7×4 0.062×4 0.7×4 0.090×2 1.0×2 0.130×2 1.1×2 0.045×4 0.7×4 0.062×4 0.7×4 0.090×2 1.0×2 0.130×2 1.1×2 3D029999A 3D030000A
Symbols:
Notes:
MCA : Min. Circuit Amps TOCA : Total Over-Current Amps MFA : Max. Fuse Amps (See note 7) LRA : Locked Rotor Amps RLA : Rated Load Amps OFM : Outdoor Fan Motor FLA : Full Load Amps IFM : Indoor Fan Motor kW : Fan Motor Rated Output 1. RLA is based on the following conditions. Indoor temp. 27°CDB/19.0°CWB Outdoor temp. 35°CDB 2. TOCA means the total value of each OC set. 3. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the range listed. 4. Maximum allowable voltage unbalance between phases is 2% 5. MCA/MFA MCA = 1.25 × RLA + ea. FLA MFA ≤ 2.25 × RLA + ea. FLA (Next lower standard fuse rating, Min. 15A) 6. Select wire size based on the larger value of MCA or TOCA. 7. MFA Instead of fuse, use circuit breaker.
SkyAir LU Series – Cooling Only –
169
Option List
ED21-301
12. Option List 12.1
LU Series
12.1.1 Indoor Unit FHYC-K Name of Option
Kit Name
Remark
35~71K
100~125K
Decoration Panel
BYC125K-W1
Sealing Member of Air Discharge Outlet
KDBHJ55K160
Panel Spacer
KDBJ55K160W
Fresh Air Intake Kit ∗4 Chamber Type Without T Joint
KDDP55D160
With T Joint
KDDP55D160K
Direct Installation Type High Efficiency Filter Replacement High Efficiency Filter
KDDJ55X160
(Colorimetric Method 65%)
KAFP556D80
KAFP556D160
(Colorimetric Method 90%)
KAFP557D80
KAFP557D160
(Colorimetric Method 65%)
KAFJ552K80
KAFJ552K160
(Colorimetric Method 90%)
KAFJ553K80
KAFJ553K160
High-Efficiency Filter Chamber
KDDFP55D160
Long-Life Filter
KAFJ551K160
Resin Net (Gravimetric Method 50%)
Ultra-Long Life Filter
KAFP55D160
Ultra-Long Life Replacement Filter
KAFJ55K160H
Chamber Connection Kit ∗5
KKSJ55K160
Branch Duct Chamber Remote Controller
KDJ55K80
KDJ55K160
Wired Type ∗3
BRC1C61 (Note. 6)
Wireless Type
BRC7C613W
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring (Interlock for Fresh Air Intake Fan) ∗1
KRP1B57
Wiring Adaptor for Electrical Appendices ∗1
KRP4A53
Interface Adaptor for SkyAir Series
DTA102A52
Installation Box for Adaptor PCB
KRP1B98 C:3D006559E
FHY-B Name of Option
Remark
Kit Name 35B
50B
60B
71B
100B
125B
Replacement Long-Life Filter
KAFJ501D56
KAFJ501D80
KAFJ501D112 KAFJ501D160
Drain Pump Kit
KDU50B50VE
KDU50B71VE
KDU50B125VE
L-Type Piping Kit (For Upward Direction) KHFJ5F50 Remote Controller
Wired Type ∗3 Wireless Type
Set Back Time Clock
KHFJ5F60
KHFJ5F80 BRC7E66 BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring
KRP1B54
Wiring Adaptor for Electrical Appendices ∗2
KRP4A52
Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB
KHFJ5F160
BRC1C61
DTA102A52 KRP1C93 3D028285A
Note:
170
1. 2. 3. 4. 5. 6.
∗1 : Installation box for adaptor PCB (KRP1B98) is necessary. ∗2 : Installation box for adaptor PCB (KRP1C93) is necessary. ∗3 : Wire for remote controller : Field supplied. ∗4 : Refer to the Option Handbook for the detail. ∗5 : When using the filter (High-Efficiency Filter or Ultra-Long Life Filter) and the Fresh Air Intake Kit together, this kit is necessary. BRC1B61 is also available.
SkyAir LU Series – Cooling Only –
ED21-301
Option List
12.1.2 Outdoor Unit (R71~140LU, R200·250KU) Name of Option
Remark
Kit Name R71LU
R100LU
Central Drain Plug Refrigerant Branch Piping
For Twin Multi
KHR58C21
For Triple Multi
R140LU
R200KU
KHD58D33 —
KRK5F80V1
KRK5F140V1
R250KU —
KHD58C21A —
For DoubleTwin Type Year-round Cooling Kit
R125LU
KKPJ5F180 KHD58C23A
KHD58C24A
KHD58D31
—
KHRJ5F224F KHRJ5F280F KRK5F160V1
— 3D039655 4D029784
SkyAir LU Series – Cooling Only –
171
2
Field Piping and Wiring
ED21-301
13. Field Piping and Wiring 13.1
Field Piping
13.1.1 Maximum Allowable Piping Length and Difference R71~140LU Maximum Allowable Pipe Length [Parenthesized Figure Represents Equivalent Length]
Maximum Allowable Level Difference
50 m (70 m) The total one-way pipe length should be within 60 meters.
30 m The level difference between the indoor units should be 0.5 m.
When connected to two indoor units (simultaneous operation system)
When connected to three indoor units (simultaneous operation system)
Branched pipe (L2)
Branched pipe (L2)
Branched pipe (L3)
Branched pipe (L3) Main pipe (L1) One-way length of pipe (L): L1+L2+L3
Main pipe (L1)
Branched pipe (L4)
One-way length of pipe (L): L1+L2+L3+L4 1PN05248B-1
Allowable Pipe Length The maximum allowable pipe length here means the total length of the main pipe and the branched pipe (the longer one of the two branched pipes). (Refer to the figure above.) R200, 250KU
1PN04787B-1
172
SkyAir LU Series – Cooling Only –
ED21-301
Field Piping and Wiring
2 1PN04787B-2
13.1.2 Additional Refrigerant Charge R71~140LU This unit requires additional charging of refrigerant according to the length of pipe connected at the site. When the entire refrigerant pipe length is within 30 meters, the additional changing is not needed. Take the following steps for proper charging. When connected to two indoor units (simultaneous operation system)
When connected to three indoor units (simultaneous operation system)
Branched pipe (L2)
Branched pipe (L2)
Branched pipe (L3)
Branched pipe (L3) Main pipe (L1)
Main pipe (L1)
One-way length of pipe (L): L1+L2+L3
Branched pipe (L4)
One-way length of pipe (L): L1+L2+L3+L4
1. Refrigerant charge amount Additional charging of refrigerant Select the amount of refrigerant which matches a length which exceeds the charge-less length, and add it. Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear surface of the front plate, as this is necessary for after-sales service.
FOR SIMULTANEOUS OPERATION SYSTEM Find the entire pipe length by totaling that of each pipe in the order of the main pipe (L1), and branched pipes (L2), (L3), (L4), calculate the excess length going over 30 meters, then select from Table 1 the amount of refrigerant corresponding to the excess length. The total value is tha amount required for additional charging. The maximum allowable pipe length is 50 meters. Make the total refrigerant pipe length come within 60 meters. The maximum allowable pipe length here means the total length of the main pipe and the branched pipe (the longer one of the two branched pipes). <unit : kg> Table 1 Pipe excess length over 30 meters
10 m or less Main pipe
Additional charging amount
Liquid pipe
Branched pipe
20 m or less
φ9.5
0.25
0.50
φ9.5
0.25
0.50
φ6.4
0.15
0.30
2. Recharging refrigerant When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the amount mentioned on the nameplate, and when the pipe length exceeds 30 meters, the charging amount is an addition of the amount stated on the nameplate and the additional charging amout. 1PN05248B-2
SkyAir LU Series – Cooling Only –
173
Field Piping and Wiring
ED21-301
R200, 250KU
1PN04788A
Caution to be taken when brazing refrigerant piping “Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”. (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible. (Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g . BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant leakage.
174
SkyAir LU Series – Cooling Only –
ED21-301
13.2
Field Piping and Wiring
Field Wiring
13.2.1 R71LU, 100LU, 125LU, 140LU (V1, Y1, VAL, TAL, YAL)
2
SkyAir LU Series – Cooling Only –
175
Field Piping and Wiring
ED21-301
13.2.2 R200KU, R250KU (Y1, TAL, YAL)
3D029782
176
SkyAir LU Series – Cooling Only –
ED21-301
Detail Information of Options SkyAir LU Series
Note : Refer to VRV Option Handbook (OH02-1) Concerning about the manual for the following Central Control Kits. • Interface Adaptor for SkyAir Series DTA102A52 • Central Remote Controller DCS302B61 • Unified ON/OFF Controller DCS301B61 • Schedule Timer DST301B61
SkyAir LU Series
177
3
Remote Controller
ED21-301
1. Remote Controller 1.1
Remote Controller, Timer, Adaptor List Model Series
Name of Option Wireless Remote Controller
FH(Y)C-K
FH(Y)K-F(J)
FH(Y)B-F
FUY-FJ
FH(Y)-B
FAY71L
FAY100FA
FV(Y)-LA
C/O BRC7C613W
—
—
BRC7C529W
BRC7E66
BRC7E619
BRC7C611W
—
H/P BRC7C612W
—
—
BRC7C528W BRC7E63W
BRC7E618
BRC7C610W
C/O Wired
BRC1C61
H/P
— BRC1C61 (Available for 2 remote control use)
Set Back Time Clock
BRC15A61
Central Remote Controller
DCS302B61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61
intelligent Touch Controller
DCS601B51
Adaptor for Wiring
KRP1B57
KRP1B51
KRP1B54
—
KRP1B54
—
—
KRP1B57
Wiring Adaptor for Electrical Appendicies
KRP4A53∗
KRP4A51
KRP4A51
KRP4A53∗
KRP4A52∗
KRP4A51∗
KRP4A51
KRP4A52∗
Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB
DTA102A52 KRP1B98
—
—
— KRP1B97
KRP1C93
KRP4A93
DTA102A52 —
KRP4A95
∗ Installation Box for Adaptor PCB is necessary.
1.2
Wired Remote Controller
BRC1C61 New BRC1C61 {
BRC1B61 ON / OFF Operation with Air Conditioner Independent operation in intermediate { season Ventilation mode change over (Auto / { HRV / Normal) Air flow change over (Auto / High / Low) { Setting of precooling / preheating Setting of fresh-up operation Filter sign display { { : Initial Setting Only (Field setting by well known service person)
178
SkyAir LU Series
ED21-301
Remote Controller
5 12
4
2
1
3 7
hr
C
6 8
hr
NOT AVAILABLE
TEST
9 11 10 13 21
L H
14
3
20 TEST
16
1 2
3
4
19
15
17
18
ON/OFF BUTTON Press the button and the system will start. Press the button again and the system will stop. OPERATION LAMP (RED) The lamp lights up during operation. DISPLAY “ ” (UNDER CENTRALIZED CONTROL) When this display shows, the system is UNDER CENTRALIZED CONTROL. DISPLAY “ ” “ ”“ ”“ ” (VENTILATION/AIR CLEANING) This display shows that the total heat exchange and the air cleaning unit are in operation (These are optional accessories).
5
DISPLAY “ ” “ ” “ ” “ ” “ ” (OPERATION MODE) This display shows the current OPERATION MODE. For cooling only type, “ ” (Auto) and “ ” (Heating) are not installed.
6
DISPLAY “ TEST” (INSPECTION/TEST OPERATION) When the INSPECTION/TEST OPERATION BUTTON is pressed, the display shows the system mode is in. hr
DISPLAY “
” (PROGRAMMED TIME)
22
3PA59583-16Z-1
12
DISPLAY “
” (DEFROST)
NON-FUNCTIONING DISPLAY If that particular function is not available, pressing the button may display the words “NOT AVAILABLE” for a few seconds. When running multiple units simultaneously the 13 “NOT AVAILABLE” message will only be appear if none of the indoor units is equipped with the function. If even one unit is equipped with the function, the display will not appear. 14 15
TIMER MODE START/STOP BUTTON TIMER ON/OFF BUTTON
INSPECTION/TEST OPERATION BUTTON 16 This button is used only by qualified service persons for maintenance purposes. PROGRAMMING TIME BUTTON 17 Use this button for programming “START and/or STOP” time. TEMPERATURE SETTING BUTTON 18 Use this button for SETTING TEMPERATURE. FILTER SIGN RESET BUTTON 19
hr
7
This display shows the PROGRAMMED TIME of the system start or stop. 8
DISPLAY “ ” (SET TEMPERATURE) This display shows the set temperature.
9
DISPLAY “ ” (FAN SPEED) This display shows the set fan speed.
C
DISPLAY “
FAN SPEED CONTROL BUTTON 20 Press this button to select the fan speed, HIGH or LOW, of your choice. OPERATION MODE SELECTOR BUTTON 21 Press this button to select OPERATION MODE. AIR FLOW DIRECTION ADJUST BUTTON 22
” (AIR FLOW FLAP)
10
NOTE
11
• For the sake of explanation, all indications are shown on the display in the above figure contrary to actual running situations.
DISPLAY “
”(TIME TO CLEAN AIR FILTER)
3PA59583-16Z-2
SkyAir LU Series
179
Remote Controller
ED21-301
Installation
180
SkyAir LU Series
ED21-301
Remote Controller
3
SkyAir LU Series
181
Remote Controller
Mode No. Note) 1
FIRST CODE NO.
0
10(20)
1
2
ED21-301
SECOND CODE No. Note) 2 Description of Setting Filter Contamination - Heavy/Light (Setting for spacing time of display time to clean air filter) (Setting for when filter contamination is heavy, and spacing time to clean air filter is to be halved)
01
03
Approx. 5,000 hours
—
Approx. 1,250 hours
—
Approx. 100 hours
—
Long-life filter
Ultra-long-life filter (1)
—
Use
Not Use
—
Display
Do Not Display
—
Pair
Twin
—
Unified
Individual
Ultra-longlife type Long-life type Standard type
Long-life filter type (Setting of filter sign indication time) (Change setting when Ultra-long-life filter is installed) Remote control thermostat (Set when remote control thermostat sensor is used )
3
Spacing Time of Display Time to Clean Air Filter Count (Setting for when the filter sign is not to be displayed)
0
Setting Number of Connected SkyAir Simultaneous Operation System Indoor Units (Setting for Simultaneous Operation System)
1
Simultaneous operation multi-unit individual setting
11(21)
02
Approx. 10,000 hours Light
Approx. 2,500 hours Approx. 200 hours
Heavy
—
2
Indoor unit fan OFF when cooling/heating is OFF
—
Fan OFF
—
0
High Ceiling Setting (Setting for when installed in a Ceiling higher than 2.7m)
Normal
High Ceiling 1
High Ceiling 2
1
Selection of Air Flow Direction (Setting for when a blocking pad kit has been installed)
F
T
W
Upper
Normal
Lower
13(23) 4
Air Flow Direction Range Setting
Note:
1. Setting is carried out in the group mode, however, set the mode number inside the ( ) for individual setting of the each indoor unit or confirmation after setting. 2. The SECOND CODE number is set to “01” when shipped from the factory. However for the following cases it is set to “02” • Air flow direction range setting. 3. Do not make any settings not given in the table above. 4. Not displayed if the indoor unit is not equipped with that function. 5. When returning to the normal mode, “88” may be displayed in the LCD in order for the remote controller to initialize itself. 2P068938-2
182
SkyAir LU Series
ED21-301
1.3
Remote Controller
Wireless Remote Controller
Names and Function Name of Option
Model Series FH(Y)C-K
FH(Y)K-F(J)
FH(Y)B-F
FUY-FJ
FH(Y)-B
FAY71L
FAY100FA
FV(Y)-LA
—
—
BRC7C529W
BRC7E66
BRC7E619
BRC7C611W
—
—
—
BRC7C528W BRC7E63W
BRC7E618
BRC7C610W
—
C/O BRC7C613W Remote Wireless Controller H/P BRC7C612W
1-1 1 ON OFF
3
1-2 H
M L
DOWN
10
C
ON OFF
UP
6
TEMP
FAN
H
M L TIME
4
11
C
hr.
2
3
8
UP
9
hr.
FAN
DOWN
13
RESERVE CANCEL
hr.
5
TIMER
12
MODE
15
hr.
TEST
7 14
SWING
16
TEST TEST
17
3PA63363-21T-1
Explanation of Receiver FH(Y)C-K
FAY-FA
FAY71L
20
21
19
18
23
22
3P091240-1
FUY-FJ
FH(Y)-B
22
19
21 20
23
18
3PA63363-21T-2
SkyAir LU Series
183
Remote Controller
ED21-301
DISPLAY “ ” (SIGNAL TRANSMISSION) 1 This lights up when a signal is being transmitted. DISPLAY “ ” “ ” “ ”“ “ ” (OPERATION MODE)
3
4
H
M L
C
” (SET TEMPERATURE)
6
7
8
9
10
11
12
AIR FLOW DIRECTION ADJUST 14 BUTTON
15
16
This display shows the set temperature. hr. DISPLAY “ hr. ” (PROGRAMMED TIME)
This display shows PROGRAMMED TIME of the system start or stop. 5
DISPLAY “
TIMER RESERVE/CANCEL BUTTON
”
2 This display shows the current OPERATION MODE. For straight cooling type, “ ” (Auto) and “ ” (Heating) are not installed. DISPLAY “
13
17
18
” (AIR FLOW FLAP)
DISPLAY “ ”“ ” (FAN SPEED) The display shows the set fan speed. TEST ” DISPLAY “ (INSPECTION/ TEST OPERATION) When the INSPECTION/TEST OPERATION BUTTON is pressed, the display shows the system mode is in. ON/OFF BUTTON Press the button and the system will start. Press the button again and the system will stop. FAN SPEED CONTROL BUTTON Press this button to select the fan speed, HIGH or LOW, of your choice. TEMPERATURE SETTING BUTTON Use this button for SETTING TEMPERATURE. (Operates with the front cover of the remote controller closed.) PROGRAMMING TIMER BUTTON Use this button for programming “START and/or STOP” time. (Operates with the front cover of the remote controller opened.) TIMER MODE START/STOP BUTTON
19
20
21
22
23
OPERATION MODE SELECTOR BUTTON Press this button to select OPERATION MODE. FILTER SIGN RESET BUTTON Refer to the section of MAINTENANCE in the operation manual attached to the indoor unit. INSPECTION/TEST OPERATION BUTTON This button is used only by qualified service persons for maintenance purposes. EMERGENCY OPERATION SWITCH This switch is readily used if the remote controller does not work. RECEIVER This receives the signals from the remote controller. OPERATING INDICATOR LAMP (Red) This lamp stays lit while the air conditioner runs. It flashes when the unit is in trouble. TIMER INDICATOR LAMP (Green) This lamp stays lit while the timer is set . AIR FILTER CLEANING TIME INDICATOR LAMP (Red) Lights up when it is time to clean the air filter. DEFROST LAMP (Orange) Lights up when the defrosting operation has started. (For straight cooling type this lamp does not turn on.)
3PA63363-21T-3
184
SkyAir LU Series
SkyAir LU Series
Control by Remote Controller.
For the control of plural indoor units on a floor at the same time
For above control from distant place.
Operation of other equipment combined with the operation of indoor unit
Group control
Group control by 2 remote controllers
Combining control by remote controller
Note 1
BRC1C61
Unit Name and Model Outline of System
Operates HRV in accordance with indoor unit operation.
Operational functions Start/Stop (ON/OFF) Temperature setting Timer setting (Settings in units of 1 hour up to a maximum of 72 hours) Air flow setting Air flow direction adjustment (Swing flap) Indication function Operating display Program dry function display Defrost/Hot start display Filter sign Temperature setting display Timer display Air flow display Abnormal operation display ∗ In case of group control all the indoor units in the system are set to the same value and each unit is controlled individually by its internal thermostat. (Not by the thermostat equipped in remote controller) ∗ In command by double remote controls, the most recent one takes priority. (Selection between master and slave controller is essential) ∗ According to indoor unit’s model, some models cannot be set.
Function
Same as the number of units controlled by remote controller
2 remote controllers control up to 16 indoor units from 2 different places simultaneously
1 remote controller controls up to 16 indoor units simultaneously
2 remote controllers control 1 indoor unit
1 remote controller controls 1 indoor unit
Standard Number of Units
(S1015)
Note: 1. These figures above show the system using wired remote controllers. Wireless remote controller replaced for wired remote controller can be used for same control. 2. In control by two remote controllers, one of two remote controllers must be a wired remote controller. Two wireless remote controllers must not be used. 3. Wiring from a wireless remote controller to the receiver can be lengthened to 200m in maximum.
For control from 2 places (distant or local)
For control from distant place
Remote operation of remote controller
2 remote control Note 2
Example of typical use
Objective / Use
1.4
Local operation of remote controller
Control Method
ED21-301 Remote Controller
Various Control by Liquid Crystal Remote Controller For more effective localized environmental control Daikin offers various control systems such as single or double remote control or centralized control. This enables the construction of a variety of operational control systems which can be adapted for various uses from remote control.
3
185
Set-back Time Clock
Desired Weekly Scheduled Operation of ON/ OFF and Temperature's Set-back
BRC15A61
186 Set-back time clock
Set-back time clock
Remote controller
Remote controller
∗ Be sure to provide a master remote controller. This scheduled operation cannot be used in both cases at control by two remote controllers and at the connection of a group remote control adapter.
Display function Effective/ineffective control on the program The present time and the week day Daylight-saving time setting Setting holidays in a week Display of operation mode(heating/cooling) Usual setting temperature (Cooling/Heating is linked to a remote controller) ON/OFF time setting for a day Set-back time setting for a day
Control function Effective/ineffective control on the program Daylight-saving time The present time adjustment Weekly operation time program (two times a day in max. frequency by a unit of 30 min.) Weekly set-back operation time program (two times a day in max. frequency by a unit of 30 min.) Program of setting temperature for normal/set-back control (each one kind for cooling and heating . The operation mode is linked to the remotecontroller). Elimination of the time in an operation of a day and a setback operation.
Max. 16 groups under simultaneous control by one set-back time clock
One indoor unit control by one set-back time clock
(S1018)
Remote Controller ED21-301
SkyAir LU Series
Scheduled Control
SkyAir LU Series
Adaptor for connection with optional controllers for centralized control
Schedule timer Central remote controller Unified ON/ OFF controller
Unified ON/OFF controller
Central remote controller
Schedule timer
For controlling all indoor units from one place
For carrying out weekly schedule operation by 1-minute units
Interface adaptor for SkyAir series DTA102A52
DCS301B61
DCS302B61
DST301B61
DCS301B61
DCS302B61
DST301B61
Controls up to 64 groups of indoor units with one central remote controller.
Controls up to 16 groups of indoor units with one unified ON/ OFF controller.
Controls up to128 groups (Max. 128 indoor units) with one schedule timer, two central remote controller and eight unified ON/OFF controllers.
Double central control function Function of liquid crystal remote controller can be controlled individually for each zone of the indoor unit. Individual/unified operation Up to 8 patterns can be set for operation controlled by programmed time when used in combination with schedule timer. Temperature setting for each zone Control operation for each room during centralized control Remote controller operation rejected command Sequential start function Double central control function Indoor unit ON/OFF control Individual/unified operation Remote controller operation rejected command (Central remote controller given priority when used in combination with central remote controller.) Sequential start function
Respective functions of schedule timer, central remote controller and unified ON/OFF controller are possible. (Control mode of central remote controller is given priority for operation of remote controller for indoor unit.)
Unification adaptor for computerized control allows you to simultaneously turn indoor units connected to the central remote controller on or off or display at the central monitor panel, etc. Interface adaptor for SkyAir series is for connection of optional controllers for centralized control.
Simultaneously controls 128 groups with one schedule timer.
ON/OFF time can be set by units of day, hour and minute; ON/OFF pattern can be set by time zone of twice per day in accordance with application.
(S1016)
ED21-301 Remote Controller
3
187
Central Control
For control by operation command from building control room
Wiring adaptor for electrical appendices
Adaptor for wiring
When controlling operation with optional accessories added inside indoor units, the status is displayed outside.
Objective / Use
Remote Control
Wiring Modification
188
Control Method
Built into indoor unit KRP1B51·54· 57
KRP4A51·52· 53·54 Built into indoor unit
With remote temperature setting
Unit Name and Model
Group Unified Control (Controls group controlled indoor units all at once and simultaneously.)
Individual Control (Controls Indoor Units Individually.)
Outline of System
Operation display signal and compressor operation signal are supplied.
For group unified control, the setting becomes the same for all connected indoor units, and each indoor unit is controlled individually by built-in thermostat.
1 adaptor controls the electric heater.
1 PC board simultaneously controls 16 group of indoor units.
1 PC board controls 1 indoor unit.
Normally open or momentary open type contactor DC12~24V or no-voltage Various control methods available by mode select switch Voltage, no-voltage selector switch Alarm and operation display signal (no-voltage) Selector switch of zone/individual of alarm display Remote temperature setting (resistance input of 0~135Ω) Selector switch for remote controller temperature setting enable/inhibit ∗
Standard Number of Units
Function
(S1017)
Remote Controller ED21-301
SkyAir LU Series
ED21-301
1.5
Remote Controller
BRC15A61 â&#x20AC;&#x201C; Set Back Time Clock
Installation
Â&#x201E; Connected to a wired remote controller, this timer can set 2 sets of ON/OFF times in an increment of 30 minutes within a day. For each ON/OFF setting a temperature setting is also possible.
3
SkyAir LU Series
189
Remote Controller
ED21-301
SPECIFICATIONS Display of time
12-hour digital display
Clock cycle type
Quartz clock type
Clock accuracy
Within ± 30 sec./month (environmental temperature from 15°C to 35°C)
Timer programming
Two pairs of programmed time for both system start and system off can be set in units of 30 minutes.
Power failure compensation time
Approximately 1 hour for a single occurrence of power failure (clock with No. of programmed time)
Size
120(W)×120(H)×17(D) mm (Width/Height/Depth)
OUTLINE DRAWINGS
120
MON TUE WED THU FRI SAT SUN
PROGRAM OFF OFF OFF OFF OFF OFF OFF
SUMMER TIME
AM PM
MON TUE WED THU FRI SAT SUN CLOCK
0 2 4 6 8 10 12 14 16 18 20 22 24
ON/OFF
˚C ˚C 0 2 4 6 8 10 12 14 16 18 20 22 24
PROGRAM
ON/OFF SET BACK
OK
DAY OF THE WEEK
CLOCK
DAY OFF
SUMMER TIME
120
SET BACK
CLEAR
Specifications and appearance subject to change without notice. About the remote controller which can connect set back time clock (BRC15A61) Wired Remote Controller
Set Back Time Clock
Indoor Unit
Although Set Back Time Clock is connected with Wired Remote Controller in parallel with Series Method, it does not applied to remote control of those other than the following. Model
Remarks
BRC1A51 BRC1A52 BRC1A61 BRC1A62 BRC8A61 ARC11A52 ARC11A54
Only EC9721 the printed Circuit Board currently used for these remote control. (Refer to Note 1)
BRC1B51 BRC1B52 BRC1B61 BRC1B62
Applied for all printed circuit boards.
BRC1C61 BRC1C51
Applied for all printed circuit boards.
Note 1) The check method of printed circuit boards' model No. The rear face of the remote control after removing a back cover Printed Circuit Board
EC9721
190
Printed circuit boards' model No. is indicated at the lower left of the PC board which can be looked at when the back cover of remote controller is removed.
Printed Circuit Boards' The product start of EC9721 was carried out after Model No. 1997.
SkyAir LU Series
ED21-301
Remote Controller
Names and Functions
Fig. 1 12
5
Fig. 2 4
2
1
15
20
PROGRAM
17
DAY OF THE WEEK
CLOCK
DAY OFF
SUMMER TIME
13
14 MON TUE WED THU FRI SAT SUN
PROGRAM
6
OFF OFF OFF OFF OFF OFF OFF
SUMMER TIME
MON TUE WED THU FRI SAT SUN CLOCK
7
ON/OFF
8
SET BACK
3
AM PM
ON/OFF SET BACK
OK
21
19
0 2 4 6 8 10 12 14 16 18 20 22 24
10 11
˚C ˚C 0 2 4 6 8 10 12 14 16 18 20 22 24
CLEAR
3
23
9 PROGRAM
ON/OFF SET BACK
OK
DAY OF THE WEEK
CLOCK
DAY OFF
SUMMER TIME
16
22
18
CLEAR
NAMES AND FUNCTIONS OF OPERATING SECTION (Fig.1,2)
1
ON/OFF BUTTON
DISPLAY “
Press this button to make the program start/stop and the set back time schedule active. Press the button again to make them inactive.
(SET BACK TIME SCHEDULE)
11
The lamp turns on when the schedule function becomes active.
DISPLAY “
MON TUE WED THU FRI SAT SUN CLOCK
3
AM PM
12
13
4
SUMMER TIME
PROGRAMMING START BUTTON
” (SUMMER
14
This display shows the clock indicates summer time.
5
DISPLAY “ PROGRAM ” (PROGRAMMING START)
6
7
8
OFF
” (DAY OFF SETTING)
Lights above the day of the week set as day off. The operation controlled by timer is not available on that day.
17 18
This display shows the set temperature at normal operation time.
19
DISPLAY “ SET BACK ˚C ” (SET TEMPERATURE SET BACK OPERATION TIME)
20
10
This display shows the programmed normal operation time.
SkyAir LU Series
DAYS OFF SET BUTTON
SUMMER TIME SET BUTTON Press this button to change clock to summer time. Press it again to return to standard time.
TEMPERATURE SET BUTTON Press this button to adjust the temperature.
ON/OFF OR SET BACK MODE SELECT BUTTON
21
This display shows the current SELECT MODE (Cool/Heat) when setting temperature.
DISPLAY “ (OPERATION TIME SCHEDULE)
DAYS OF A WEEK SELECT BUTTON
Press this button to set days off.
” (SELECT MODE)
0 2 4 6 8 10 12 14 16 18 20 22 24
Press this button to finish setting the present time and the programmed time.
Press this button to select the day of the week.
This display shows the set temperature at set back operation time.
9
Press this button to adjust the present time and the programmed time.
SETTING FINISH BUTTON
16
DISPLAY “ ON/OFF ˚C ” (SET TEMPERATURE NORMAL OPERATION TIME)
DISPLAY “
Press this button to set the programmed time. Press it again after you are through with the program.
TIME ADJUST BUTTON
15
The light turns on when the timer is programmed.
DISPLAY “
CLOCK ADJUST BUTTON Press this button to set the present time.
Displays the present day of the week and time.
DISPLAY “ TIME)
DISPLAY “ ” (UNDER CENTRALIZED CONTROL) When this display shows, the system is UNDER CENTRALIZED CONTROL.
” (PRESENT
TIME)
”
This display shows the programmed set back operation time.
OPERATION LAMP (RED)
2
0 2 4 6 8 10 12 14 16 18 20 22 24
”
Press this button to select ON/OFF or SET BACK mode when setting the programmed time and temperature.
COOL/HEAT SELECT BUTTON
22
23
Press this button to select COOLING or HEATING when setting temperature at set back.
PROGRAM CLEAR BUTTON Press this button to clear the programmed time.
191
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-301
2. Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C] 2.1
BYC125K – W1 – Decoration Panel
BEFORE INSTALLATION PRECAUTIONS • Refer also to the installation manual attached to the indoor unit. ACCESSORIES • Installation manual. NOTE TO INSTALLER Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.
PREPARATION OF DECORATION PANEL <<For this unit, you are able to select air flow directions. To discharge air in 2 or 3 directions, it is necessary to purchase optional blocking pad kit.>> HANDLING OF DECORATION PANELS • Never place the panel facing down nor lean it against a wall nor leave it on a projecting object. • Never touch or put pressure on the swing flap. (The swing flap may malfunction.) (1) Remove the suction grille from the decoration panel. 1) Push the suction grille lever inward and lift up the lever side. (Refer to Fig. 1.)
2) Detach the suction grille from the decoration panel by lifting the grille up approximately 45 degrees. (Refer to Fig. 2.)
45˚ Lever
Fig. 1 (2) Remove the service cover on the corner. Slide the service cover outward to remove. (Refer to Fig. 3.)
Fig. 2
Fig. 3
192
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
INSTALLATION OF THE DECORATION PANEL TO THE INDOOR UNIT BODY <<Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.>> (1) Set the decoration panel to the indoor unit body by matching the position of the swing flap motor of the decoration panel to the piping position of the indoor unit as shown in Fig. 4. (2) Install the decoration panel. 1) Temporarily install the decoration panel to the indoor unit by hanging the latch on the opposite side of the swing flap motor of the decoration panel to the hook of the indoor unit body. (2 positions) 2) Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit. (Be careful not to let the swing motor lead wire get caught in the sealing material.) 3) Screw all 4 hexagon head screws located right beneath the latches in approximately 5 mm. (Panel will rise.) 4) Adjust the decoration panel by turning it to the arrowed direction in Fig. 4 so that the ceiling opening is completely covered. 5) Tighten the screws until the thickness of the sealing material between the decoration panel and the indoor unit body reduces to 5â&#x20AC;&#x201C;8 mm. Sealing material Indoor unit
3
Ceiling material 5 ~ 8 mm
Decoration panel
Air outlet
Hook
1)
Latch
2) Piping position
2)
Swing flap motor 3)
4)
Fig. 4 PRECAUTIONS â&#x20AC;˘ Improper screwing of the screws may cause the troubles shown in Fig. 5. Screw properly.
Air leak
Air leak from ceiling
Contamination
Dew formation, dew dripping Fig. 5
SkyAir LU Series
193
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-301
• If gap is still left between the ceiling and the decoration panel after screwing the screws, readjust the indoor unit body height. (Refer to Fig. 6.)
Adjustment of the indoor unit body height from the holes in the corner of the decoration panel is possible if the indoor unit is kept leveled and the drain piping, etc. is unaffected.
No gaps is allowed Fig. 6 (3) Wiring of the decoration panel (Refer to Fig. 7.) 6) Connect the connectors for swing flap motor lead wire installed on the decoration panel. If connectors are not connected, the malfunction display (A7) appears on the remote controller. Connect the connectors properly. Make sure that the swing flap motor lead wire is not caught between the indoor unit and the decoration panel.
6) Indoor unit side
Decoration panel side
áWiring
Fig. 7
Instruction Diagramñ (It differs from the actual state.)
INSTALLATION OF SUCTION GRILLE AND SERVICE COVER (1) Install the suction grille. Install by reversing the procedure shown in “PREPARATION OF DECORATION PANEL”. It is possible to install the suction grille in 4 directions by turning the suction grille. Change the direction when adjusting the direction of the suction grille of multiple units or in meeting customers’ demands. NOTE) Be careful not to get swing flap motor lead wire get caught when installing the suction grille. (2) Install the service cover on the corner. 1) Attach the string of the service cover to the pin of the decoration panel as in Fig. 8.
2) Install the service cover over the decoration panel.
Pin
Install the service cover by sliding 4 latches to fit into the holes on the decoration panel.
Fig. 8
194
SkyAir LU Series
ED21-301
2.2
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
KDBHJ55K160 â&#x20AC;&#x201C; Sealing member of air discharge outlet
Caution zRefer to the installation manual for both indoor unit and the decoration panel. zWhen you install other optional kit, it may not be possible to select the 3-way or 2-way air discharge. For details, refer to the manual for the optional kit or the catalogue. zContents of Kit Prior to installation make sure you have the complete kit of parts. Name
Sealing material(A)
Sealing material(B)
Sealing material(C)
Sealing material(D)
Quantity
1 piece
1 piece
1 piece
1 piece
Shape and marking
Name Quantity
3 Insulation for top plate 1 piece
1 piece
Insulation for side plate 1 piece
2 pieces
1 piece
Moisture absorber for bell-mouth
2 pieces
1 piece
Moisture absorber for horizontal vane
5 kinds
Shape and marking
SkyAir LU Series
195
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
3
ED21-301
Installation of the insulation
(1) Installation to the side plate Adhere insulation for side plate
to the side of indoor unit. 140 class
71 class
Put the wire through the slit of the insulation.
(2) Installation to the top plate Adhere insulation for top plate
When adhering insulation, align its edge with the bottom line of casing.
When adhering insulation, align its edge with the bottom line of casing.
,
to the top of the indoor unit.
(3) Adhere the moisture absorber for horizontal vane to the edge of the horizontal vane of air outlet (Fig. 2). (Choose the same color as panel.) Horizontal vane Moisture absorber for horizontal vane Fig. 2
Align it with the upper edge of horizontal vane. Horizontal vane Moisture absorber for horizontal vane
Fig. 1
(4) Adhere the moisture absorber in accordance with the reference surface without wrinkles. (Fig. 4) Adhere the moisture absorber in accordance with the reference line . (Fig. 5) Reference surface Swing connector Swing motor
(Fig. 3)
Sticking reference
Adhere it from the edge of switch box. Switch box
Bellmouth
Sticking reference Fig. 4
Fig. 5 J : 1P012222B
196
SkyAir LU Series
ED21-301
2.3
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
KDBJ55K160W â&#x20AC;&#x201C; Panel spacer
3
SkyAir LU Series
197
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
198
ED21-301
SkyAir LU Series
ED21-301
2.4
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
KDDP55D160(K) â&#x20AC;&#x201C; Fresh Air Intake Kit
SkyAir
FH(Y)C35~140K
3
71
290
C : 3K011144-1-1
SkyAir LU Series
199
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-301
C : 3K011144-1-2
200
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
3
SkyAir LU Series
201
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
2.5
ED21-301
KDDJ55X160 â&#x20AC;&#x201C; Fresh Air Intake Kit
The fresh air is taken into the unit by the indoor unit fan or duct fan, which is field supplied. The location of fresh air intake port will be changeable by installing the duct fan.
KDDJ55X160
1
2P066796B-1
202
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
3
2
2P066796B-2
SkyAir LU Series
203
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
2.6
ED21-301
KAFP556D80 · 160 – High Efficiency Filter (Including Filter Chamber) KAFP557D80 · 160 – High Efficiency Filter (Including Filter Chamber) Combination table
2.7
High Efficiency Filter (Set)
High Efficiency Filter
KAFP556D80 KAFP557D80
KAFJ552K80 KAFJ553K80
KAFP556D160 KAFP557D160
KAFJ552K160 KAFJ553K160
Filter Chamber KDDFP55D160
KAFJ552K80 · 160 – High Efficiency Filter (Replacement) KAFJ553K80 · 160 – High Efficiency Filter (Replacement) Specifications High Efficiency Filter (Replacement) KAFJ552K80
KAFJ552K160
Filter Chamber
KAFJ553K80
KAFJ553K160
KDDFP55D160
Collecting Efficiency (%)
65% (NBS Calorimetric method)
90% (NBS Calorimetric method)
Initial Pressure Loss (Pa)
34
44
Final Pressure Loss (Pa)
78
98
Filter
Non-woven Fabric of Synthetic Fiber Non-woven Fabric of Synthetic Fiber 2,500 (Dust Concentration 0.15 mg / m3)
Life (h) Models to be Applied
35~71K Model
1,800 (Dust Concentration 0.15 mg / m3)
100~140K Model 35~71K Model
100~140K Model
Precaution at use 1. The high efficiency filter, and the other filter can not be installed together. 2. The unit should be operated with 4-way dischange when the high efficiency filter is installed. It can not be applied to the high ceiling room. 3. Field setting by remote controller is necessary when the high efficiency filter is installed.
Dimension
2.8
Model
A
KAFJ552K80, 553K80
25
KAFJ552K160, 553K160
45
KRP1B98 – Installation Box for Adaptor PCB
Dimension
Model No. Item Applicable Model Adaptor for Wiring
204
KRP1B98 FH(Y)C35~140K KRP1B57 KRP4A53
SkyAir LU Series
ED21-301
2.9
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
KDDFP55D160 â&#x20AC;&#x201C; High-Efficiency Filter Chamber
3
SkyAir LU Series
205
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
206
ED21-301
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
2.10
KAFJ551K160 – Long-Life Filter for Decoration Panel (Replacement)
2.11
KAFP55D160, KAFJ55K160H (Replacement) – Ultra Long-Life Filter (Including Filter Chamber)
3
Installation Iocation Filter Cleaning Period Dirty Area
Every 5,000 hrs
Not Dirty Area
Every 10,000 hrs
KKSJ55K160 – Chamber Connection Kit
CAUTION Confirm a combination of chamber connection kit with option (chamber type) by the right table. Fresh air intake kit (chamber type) must be set up side surely.
Option (Chamber Type) Down Side
2.12
Up Side Fresh Air Intake Unit
High Efficiency Filter Unit Ultra-Long Life Filter Unit
Don't adopt any combinations except the Table because they may cause functional disorder.
Dimension
Concerning installation of the indoor unit, the option (chamber type) and the decoration panel, refer to installation (operation) manual attached to these parts.
SkyAir LU Series
207
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
2.13
208
ED21-301
KDJ55K80 · 160 – Branch Duct Chamber
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
3
SkyAir LU Series
209
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-301
2.13.1 Fan Performance and Discharge Pattern in case of using Branch Duct Single Branch â&#x20AC;&#x201D; 3 Way Discharge
Sealing
Branch
R
S
Sealing
T
S
Branch
T
Q
S
Sealing Branch
T R
R
Q
S
R
T
Sealing
Q
Q
Branch (V0690)
35~71 Single branch ( ) 50/60Hz Common use
55 50
External static pressure (Pa)
55 50
71
45
50
50
50
40
35
35
35
35
30
30
30
25
25
25
20
20
20
15
15
15
10
10
10
5
5
5
0
0 1
2
60 50
35
35
0
71
45
60
40
Single branch ( ) 50/60Hz Common use
55
71
45
60
40
Single branch ( or ) 50/60Hz Common use
3
4
0 0
1
Air volume (m3/min)
2
3
4
0
1
Air volume (m3/min)
2
3
4
Air volume (m3/min)
100~140 Single branch sealing ( 50/60Hz Common use
130 120
)
or
)
Single branch sealing ( 50/60Hz Common use
130 120
140
110
125
125
110
125
100
100
100
100
100
External static pressure (Pa)
140
90
90
90
80
80
80
70
70
70
60
60
60
50
50
50
40
40
40
20
20
20
20
20
20
10
10
10
0
0 0
1
2
3
4
5
6
7
8
Air volume (m3/min)
210
Single branch sealing ( 50/60Hz Common use
130
9 10
)
140
0 0
1
2
3
4
5
6
7
8
Air volume (m3/min)
9 10
0
1
2
3
4
5
6
7
8
9 10
Air volume (m3/min)
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
Single Branch â&#x20AC;&#x201D; 2 Way Discharge
S
S
T
R Q
Sealing
Sealing
T R
R Branch Q or T
Sealing
S
Branch
S or T
Sealing Sealing
T
Sealing
Q
Branch
R or T
Q
(V0693)
3
35~71
90
Single branch - 2 way discharge ( 50/60Hz Common use
,
sealing) 90
Single branch - 2 way discharge ( 50/60Hz Common use
71
80
71
80
60
60
50
50
70
35
External static pressure (Pa)
External static pressure (Pa)
70
sealing)
60 50 40 30 20 10
35
60 50 40 30 20 10
0
0 0
1
2
3
4
5
0
1
Air volume (m3/min)
2
3
4
5
Air volume (m3/min)
100~140
160
Single branch - 2 way discharge (100~140. 50Hz)
160
150
150
140
140 Sealing
120
Sealing
110 Sealing
100 90 80 70 60 50 40
120
Sealing
110 Sealing
100 90 80 70 60 50 40
30
30
20
20
10
10
0
Sealing
130
External static pressure (Pa)
External static pressure (Pa)
130
0 0
1
2
3
4
5
6
7
8 3
9 10 11 12
Air volume (m /min)
SkyAir LU Series
Single branch - 2 way discharge (100~140. 60Hz)
0
1
2
3
4
5
6
7
8
9 10 11 12
Air volume (m3/min)
211
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-301
2 Branches â&#x20AC;&#x201D; 2 Way Discharge
S
Sealing Sealing
S
T
R
Branch
Q
Sealing
R
T
R
Sealing
S
Branch Sealing
T
Sealing
Q
Q
Branch (V0696)
35~71
90
2 Branch - 2 way discharge ( 50/60Hz Common use
90
71 60
80 70
External static pressure (Pa)
sealing) 2 Branch - 2 way discharge ( 50/60Hz Common use
sealing) 2 Branch - 2 way discharge ( 50/60Hz Common use
71
71
60
80
50
50
35
35
70
50
60
50
50
50
40
40
40
30
30
30
20
20
20
10
10
10 0
0 1
2
3
4
5
6
7
0
8
35
70
60
0
60
80
60
0
sealing)
Air volume (m3/min)
1
2
3
4
5
6
7
Air volume (m3/min)
8
0
1
2
3
4
5
6
7
8
Air volume (m3/min)
100~140
150
2 Branch - 2 way discharge (100~140. 50Hz)
150
External static pressure (Pa)
140
140
130
Branch
130
Branch
120
Branch
120
Branch
110
Branch
110
Branch
100
100
90
90
80
80
70
70
60
60
50
50
40
40
30 20
Operation limit less than 12m3/min
10
30 20
Operation limit less than 12m3/min
10
0
0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Air volume (m3/min)
212
2 Branch - 2 way discharge (100~140. 50Hz)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Air volume (m3/min)
SkyAir LU Series
ED21-301
2.14
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
Dimensions with Optional Kit
2.14.1 KDBJ55K160W â&#x20AC;&#x201C; Panel Spacer FH(Y)C35~71K Unit (mm)
3
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005390E
FHYC100~140K Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name
Thickness of panel spacer
Dimension between the bottom surface of box and the surface of ceiling
View
Description J : 3D005391D
SkyAir LU Series
213
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-301
2.14.2 KDDP55D160 – Fresh Air Intake Kit (Without T Joint, Duct Fan) FH(Y)C35~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
Note 4
View
Service Access Panel : 450×450mm or more Refer to Note 2
290
Installation Service Access Panel
Connection Chamber (Right)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
How to connect Chamber 4 Independently(Refer to Note 5,6)
Applicable Models SkyAir
FH(Y)C35~71K
5 4 3 2 1 Number
Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981A
FHYC100~140K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Refrigerant Piping
View
Service Access Panel : 450×450mm or more Refer to Note 2
Note 4
Installation Service Access Panel
Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6)
Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
214
Applicable Models SkyAir
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984A
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
2.14.3 KDDP55D160K – Fresh Air Intake Kit (With T Joint, Without Duct Fan) FH(Y)C35~71K
Unit (mm)
Service Access Panel : 450×450mm or more Refer to Note 2
Flexible Duct (Accessory)
3 Installation Service Access Panel
Service Access Panel : 450×450mm or more Refer to Note 2
Suction Duct (K-KFD9A) Optional (Accessory) T Joint
Plate Band
(Accessory)
Connecting Chamber (Right)
290
(Accessory)
How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
Applicable Models SkyAir
FH(Y)C35~71K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032987A
FHYC100~140K Service Access Panel : 450×450mm or more Refer to Note 2
Installation Service Access Panel
Unit (mm) Flexible Duct (Accessory)
Service Access Panel : 450×450mm or more Refer to Note 2 Plate Band (Accessory)
T Joint (Accessory)
Suction Duct (K-KFD9A) Optional (Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.
SkyAir LU Series
Applicable Models SkyAir
FHYC100~140K
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032990A
215
Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]
ED21-301
2.14.4 KAFP â&#x20AC;&#x201C; High Efficiency Filter FH(Y)C35~71K
Unit (mm)
290
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975A
FHYC100~140K
Unit (mm)
Note:When other optional kit is installed, refer to the installation drawing of its optional kit.
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032976A
216
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3. Ceiling Mounted Cassette Corner Type [FH(Y)K] 3.1
BYK45FJW1 · 71FJW1 – Decoration panel
BEFORE INSTALLATION PRECAUTIONS • Refer also to the installation manual attached to the indoor unit. ACCESSORIES • The box contains this manual and the parts listed below. Item
Description
Quantity BYK45FJ BYK71FJ
3
Decoration panel
Panel fixing screw
Washer
M5 × 35
1 set
1 set
5 pcs.
5 pcs.
5 pcs.
5 pcs.
NOTE TO INSTALLER Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.
PREPARATION OF DECORATION PANEL • Handle the decoration panel with care. 〈 Never lean the panel against a wall, etc. nor leave it on a projecting object. (For prevention of dents and damages to the panel surface) Never grab the discharge grille during the installation work. (For prevention of damage to the discharge grille) 〉 (1) Remove the suction grille from the decoration panel. (See figure below.) 1) Slide the suction grille lever and lift it up to one side.
SkyAir LU Series
217
Ceiling Mounted Cassette Corner Type [FH(Y)K]
ED21-301
2) Unhook the suction grille off from the decoration panel.
(2) Remove the air filter. Pull up the air filter knob to remove the air filter.
INSTALLATION OF THE DECORATION PANEL TO THE INDOOR UNIT BODY <<Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.>> 1. Installing the panel (1) Install the decoration panel to the indoor unit body temporarily.
Portions to hook the panel's temporary installation hooks
Portion at which the panel is fixed. (5 locations)
218
Temporary installation hooks
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Corner Type [FH(Y)K]
(2) Tighten the panel fixing screws temporarily. 1) Open the air outlet decorative covers.
Air outlet decorative covers
3
2) Put the panel fixing screws (5 pcs.) through the washers and tighten the screws temporarily. 3) Move the panel as indicated by the arrow in the above figure for adjustment so as to make no gap between the panel and the ceiling. 2. Wiring between the indoor unit and the panel ¡ With the decoration panel temporarily installed to the indoor unit, wire between the indoor unit and the decoration panel. (See figure below.) (1) Connect the connectors for swing motor and the limit switch on the decoration panel to those on the indoor unit body respectively. (2) Check that the connectors are of the same color. Panel side
Indoor unit side
(Motor power cable) Color of connector: red
Note: No connection of connectors or connection of connectors of different colors causes the unit to stop operating with the Operation lamp on the remote control blinking and the trouble code display "A7" on the remote controller.
Panel side
Indoor unit side
(Limit switch) Color of connector: black
SkyAir LU Series
219
Ceiling Mounted Cassette Corner Type [FH(Y)K]
ED21-301
3. Fixing the decoration panel (1) In order to prevent air leakage, a sealing material is provided at the spot where the indoor unit body is joined with the decoration panel. Fix the decoration panel in the following method. (Shoulder bolts are used as the fixing screws. Tighten the bolts until their shoulders.) Indoor unit body Indoor unit
Sealing material Standard tightening length: 20 mm Shoulder bolts are used to protect the indoor unit. The bolts can be tightened to the allowance of up to 15 mm.
Decoration panel
Decoration panel body
(2) When tightening the bolts, be sure to make no gap between the panel and the ceiling and set the panel in parallel to the ceiling and the ceiling joint. á
Improper installation of the panel to the cassette body causes air leakage. ñ
Note: In case there remains a gap between the panel and the ceiling when the fixing bolts have been tightened fully to their shoulders, adjust the height of the indoor unit.
Make no gap here.
Note: The decoration panel can be adjusted back and forth to 10 mm, respectively.
(3) Finally, make sure that the decoration panel is securely fixed to the indoor unit. Improper installation (tightening) causes the troubles as shown below; be sure to double-check the completion of the installation work. ñ á
No gap
Air leakage
Air leakage from the ceiling Dust deposit Dew buildup and dew dripping
INSTALLATION OF SUCTION GRILLE AND AIR FILTER For their installation, take the reverse steps mentioned in "PREPARATION OF DECORATION PANEL".
220
SkyAir LU Series
ED21-301
3.2
Ceiling Mounted Cassette Corner Type [FH(Y)K]
KPBJ52F56W · 80W – Panel Specer
3
SkyAir LU Series
221
Ceiling Mounted Cassette Corner Type [FH(Y)K]
222
ED21-301
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
223
Ceiling Mounted Cassette Corner Type [FH(Y)K]
224
ED21-301
SkyAir LU Series
ED21-301
3.3
Ceiling Mounted Cassette Corner Type [FH(Y)K]
KDBJ52F56W · 80W – Air Discharge Blind Panel
3
SkyAir LU Series
225
Ceiling Mounted Cassette Corner Type [FH(Y)K]
226
ED21-301
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
227
Ceiling Mounted Cassette Corner Type [FH(Y)K]
228
ED21-301
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
229
Ceiling Mounted Cassette Corner Type [FH(Y)K]
230
ED21-301
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
231
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3.4
ED21-301
KAFJ521F56 · 80 – Replacement Long Life Filter Washable Model Items Average Efficiency Initial Pressure Loss Final Pressure Loss Life Time Materials Number Required Per Model Weight (kg)
KAFJ521F56
KAFJ521F80
45 (gravity Method) Less Than 9.8 Pa 49 Pa 2,500 hours (Dust Particle Concentration at 0.15 mg/m3) Mildew Proof Resin Net Two pieces 0.4 0.6
Dimension
3.5
Model
A
KAFJ521F56
403
KAFJ521F80
503
K-HV7AW · 9AW – Discharge Grille This optional kit is used when the unit is installed with front air discharge. The direction of air can be adjusted flexibly. This discharge grille should be installed with the following flexible duct. Specifications Model Items Air Flow Rate (m³/min) Type
K-HV7AW
K-HV9AW
9~13
12~19
HV type (Horizontal blade and vertical blade movable)
External Color Materials
White
White
Steel plate (A cryptomeria only at the tip of the outlet + nylon flocking)
Structural Parts
Discharge grille, Screws, Blade control tool KFDJ52F56
KFDJ52F80
Applicable Models
35 · 45F(J)
60 · 71F(J)
Pressure Drop
Applicable Flexible Duct
m/s : Discharge Velocity
Air Flow Rate
Model
232
A
B
C
D
K-HV7AW
523
466
488
500
K-HV9AW
723
666
688
700
SkyAir LU Series
ED21-301
3.6
Ceiling Mounted Cassette Corner Type [FH(Y)K]
KFDJ52F56 · 80 – Flexible Duct with Shutter
3
SkyAir LU Series
233
Ceiling Mounted Cassette Corner Type [FH(Y)K]
234
ED21-301
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
235
Ceiling Mounted Cassette Corner Type [FH(Y)K]
236
ED21-301
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
237
Ceiling Mounted Cassette Corner Type [FH(Y)K]
238
ED21-301
SkyAir LU Series
ED21-301
Ceiling Mounted Cassette Corner Type [FH(Y)K]
3
SkyAir LU Series
239
Ceiling Mounted Built-In Type [FH(Y)B]
ED21-301
4. Ceiling Mounted Built-In Type [FH(Y)B] 4.1
240
BYBS45DJW1 – Decoration panel BYBS71DJW1 – Decoration panel BYBS125DJW1 – Decoration panel
SkyAir LU Series
ED21-301
Ceiling Mounted Built-In Type [FH(Y)B]
3
SkyAir LU Series
241
Ceiling Mounted Built-In Type [FH(Y)B]
242
ED21-301
SkyAir LU Series
ED21-301
Ceiling Mounted Built-In Type [FH(Y)B]
3
SkyAir LU Series
243
Ceiling Mounted Built-In Type [FH(Y)B]
4.2
244
ED21-301
KTBJ25K56W · 80W · 160W – Service access panel
SkyAir LU Series
ED21-301
4.3
Ceiling Mounted Built-In Type [FH(Y)B]
KAFJ252L56 · 80 · 160 – High-Efficiency Filter KAFJ253L56 · 80 · 160 – High-Efficiency Filter
Specifications Model
KAFJ252L56
Item Average Efficiency
KAFJ253L56
KAFJ253L80
KAFJ253L160
90% (NBS Colorimetric Method)
Less Than 5
Less Than 5
10
10
Ultimate Pressure Loss (mmH2O) Effective Life (h)
KAFJ252L160
65% (NBS Colorimetric Method)
Initial Pressure Loss (mmH2O)
Filter Materials
KAFJ252L80
Synthetic Fiber non-woven Fabric 2,500 (Dust Particle Concentration at 0.15 mg/m3)
Filter Chamber for Bottom Suction
KAJ25L56D
Dimensions (mm) (H×W×D)
55×650×360
Applicable Model
35 · 45F
KAJ25L80D
KAJ25L160D
(55×475×360)×2 (55×700×360)×1 (55×650×360)×1 60 · 71F
100 · 125F
Synthetic Fiber non-woven Fabric
3
1,800 (Dust Particle Concentration at 0.15 mg/m3) KAJ25L56D 55×650×360 35 · 45F
KAJ25L80D
KAJ25L160D
(55×475×360)×2 (55×700×360)×1 (55×650×360)×1 60 · 71F
100 · 125F
Installation
Characteristics of Filter
SkyAir LU Series
245
Ceiling Mounted Built-In Type [FH(Y)B]
4.4
ED21-301
KAFJ251K56 · 80 · 160 – Replacement long-life filter
Specifications Model Item Dimensions (mm) (H×W×D) Average Efficiency Pressure Loss Initial (pa) Ultimate Filter Materials Number of Filters Effective Life (h) Applicable Model
4.5
Characteristics of Filter KAFJ251K56
KAFJ251K80
KAFJ251K160
20×506×377 20×701×377 20×451×377 20×656×377 50% (by weight method) 9.8 (1mmH2O) 49 (5mmH2O) Mold Prevention resin net 1 2 (each one) 2 (each one) 2,500 (at Dust Particle Concentration of 0.15 mg/m3) For indoor unit For indoor unit For indoor unit 35~45F 60~71F 100~125F 20×656×377
KAJ25L56D · 80D · 160D – Filter Chamber for Bottom Suction
Applicable Model Model
Installation Applicable Model
Dimension
246
SkyAir LU Series
ED21-301
4.6
Ceiling Mounted Built-In Type [FH(Y)B]
KAJ25L56B · 80B · 160B – Filter Chamber for Rear Suction Contents of kit Name Rear-Intake Filter Chamber Blind Board Screws For Blind Board (M5×12) For Filter Chamber Washer for Suspension Bracket Suspension Bracket Screws for Suspension Bracket (M6×12) Filter Guide Screws for Filter Guide (M5×12) Applicable Model
Quantity KAJ25L56B 1 1 4 11 4 2 2 – – 35 · 45F
KAJ25L80B 1 1 6 13 4 2 2 1 2 60 · 71F
KAJ25L160B 1 1 6 15 4 2 2 1 2 100 · 125F
3
Preparation before installation
SkyAir LU Series
247
Ceiling Mounted Built-In Type [FH(Y)B]
248
ED21-301
SkyAir LU Series
ED21-301
Ceiling Mounted Built-In Type [FH(Y)B]
3
SkyAir LU Series
249
Ceiling Mounted Built-In Type [FH(Y)B]
4.7
250
ED21-301
KSAJ25K56 · 80 ·160 – Canvas Duct
SkyAir LU Series
ED21-301
4.8
Ceiling Mounted Built-In Type [FH(Y)B]
K-DG4BW · 5BW · 7BW · 9BW – Air Discharge Unit-Discharge Grille+Discharge Chamber K-DGC4B · 5B · 7B · 9B – Air Discharge Unit-Discharge Grille+Discharge Chamber
3
SkyAir LU Series
251
Ceiling Mounted Built-In Type [FH(Y)B]
252
ED21-301
SkyAir LU Series
ED21-301
4.9
Ceiling Mounted Built-In Type [FH(Y)B]
K-DDV20A â&#x20AC;&#x201C; Branch Duct
Specification
Dimension Model
Item Inlet Duct Size Outlet Duct Size Outside Insulation Inside Insulation
-
Polyurethane Foam Foam Polysthyrene
Pressure loss of Branch Duct
3
Model
SkyAir LU Series
Weight (kg)
253
Ceiling Mounted Built-In Type [FH(Y)B]
4.10
ED21-301
K-FDK151B · 152B · 153B · 154B · 155B · 156B – Flexible Duct K-FDK201B · 202B · 203B · 204B · 205B · 206B – Flexible Duct Specification Model Item Maximam Outer Dimension Fitting Port Size Operating Temperature Range Applicable Model Structure
(Inner Dimension)
(Inner Dimension)
-10~+70˚C 35~125F Pressure loss of Flexible Duct Air ty oci Vel c.) / se (m t Duc eter Diam m) (m
m H20/100m
254
SkyAir LU Series
ED21-301
4.11
Ceiling Mounted Built-In Type [FH(Y)B]
KBBJ25K56 · 80 · 160 – Blind Board
3
4.12
KDAJ25K56 · 71 · 140 – Adaptor for Discharge
SkyAir LU Series
255
Ceiling Mounted Built-In Type [FH(Y)B]
4.13
256
ED21-301
KDJ2507K56 · 80 · 160 – Flange for Suction
SkyAir LU Series
ED21-301
4.14
Ceiling Mounted Built-In Type [FH(Y)B]
Optional Kit Installation Drawing
Discharge Chamber+Discharge Grille <Ï&#x2020;150> K-DGC4~7B, K-DG4~7BW
3
K-DGC9B, K-DG9BW
SkyAir LU Series
257
New Ceiling Suspended Cassette Type [FUY]
ED21-301
5. New Ceiling Suspended Cassette Type [FUY] 5.1
KDBHJ49F80 · 140 – Sealing Member of Air Discharge Outlet
Dimension
Model KDBHJ49F80 KDBHJ49F140
Material Galvanized Steel Plate (with Flocking)
Model KDBTJ49F80 KDBTJ49F140
Material Galvanized Steel Plate (with Flocking)
Model KDBHJ49F80 KDBHJ49F140
5.2
KDBTJ49F80 · 140 – Decoration Panel for Air Discharge
Dimension
Model KDBTJ49F80 KDBTJ49F140
5.3
KDGJ49F80 · 140 – Vertical Flap Kit
Dimension
Model KDGJ49F80 KDGJ49F140
258
Packing Quantity 4(each 2×2)
SkyAir LU Series
ED21-301
5.4
New Ceiling Suspended Cassette Type [FUY]
KAFJ495F140 – Replacement Long Life Filter
Dimension
Model Item Initial Pressure Loss (Pa) Final Pressure Loss (Pa) Average Efficiency (%) Life Time (h)
KAFJ495F140 Less Than 7 Less Than 49 50 (Gravity Method) 2,500 (Dust Particle Concentration at 0.15 mg/m3)
Filter Pass Air Flow Rate Materials Number Required Per Model Weight (kg)
3
18.5 m /min Mildew Proof Resin Net 1 0.4
3
5.5
KHFJ49F80 · 140 – L Connection Piping Kit Model KHFJ49F80 KHFJ49F140
Dimension
5.6
Liquid Side
Gas Side
KRP1B97 – Installation Box for Adaptor PCB
Dimension
SkyAir LU Series
Model No. Item Applicable Model Adaptor for Wiring
KRP1B97 FUY71~125FJ KRP4A53
259
Ceiling Suspended Type [FH(Y)]
ED21-301
6. Ceiling Suspended Type [FH(Y)] 6.1
KAFJ501D56 · 80 · 112 · 160 – Replacement Long Life Filter
Specifications Model
KAFJ501D56
Item
KAFJ501D80
KAFJ501D112
KAFJ501D160
3
Effective Life, Average Efficiency 2,500 hours (at Dust Particle Concentration of 0.15 mg/m ), 45% (by Weight Method) Filter Materials
Mold Prevention Resin Net
Mold Prevention Resin Net
Nos. Required
2 pieces
3 pieces
Applicable Model
For Indoor unit 35~50
6.2
For Indoor unit 60~71
For Indoor unit 100
For Indoor unit 125
KDU50B50 · 71 · 125VE – Drain Pump Kit
Specifications Model Item
KDU50B50VE
Drain-up Lift (mm)
600
Power Supply
Single Phase 220-240V/220V 50/60Hz (from Indoor Unit PC Board)
Power Consumption (W)
Applicable Model
KDU50B125VE
VP20 (Ex. dia. φ26, Int. dia. φ20)
Drain Con, Diameter Pump
KDU50B71VE
13.5/12 (50/60Hz) 35~50B
60~71B
100~125B
Precaution at use 1. Don’t turn off the power within 5 minutes after cooling operation stops. 2. The liquid crystal display blinks to inform us that safety device actuated. 3. When cooling operation’s seaaon is over, extract drain water. Installation guide of the drain pump kit <Change in drain pump kit> Exit drain pipe has been changed from VP25 to VP20 (to meet the drain diameter of main frame). Attached drain pipe (450 mm chloride vinyl straight pipe bellow, elbow) Æ only bellow hose for VP20 All units of drain up height was unified to 600 mm (from the bottom of the ceiling).
Wiring diagram
260
SkyAir LU Series
ED21-301
6.3
Ceiling Suspended Type [FH(Y)]
KHFJ5F50 · 60 · 80 · 160 – L-Type Piping Kit Application purpose This kit must be bent inside the unit as shown below, when the refrigerant piping is carried out in a ceiling space. This L shape kit is an optional accessory which has been developed for improving the work of the processing on site. Model Item
KHFJ5F50
KHFJ5F60
KHFJ5F80
KHFJ5F160
Applicable Model
For Indoor Unit 35B
For Indoor Unit 45B~60B
For Indoor Unit 71B
For Indoor Unit 100B~125B
Installation KHFJ5F50~160
6.4
3
Installation
KRP1C93 – Installation Box for Adaptor PCB
KRP1C93
Model No. Item Applicable Model Adaptor for Wiring Fixing Place Dimensions (mm)
SkyAir LU Series
W H D
KRP1C93 FH(Y)35~125B KRP1B54 KRP4A52 In the Unit 109 124 38
261
Floor Standing Type [FVY]
ED21-301
7. Floor Standing Type [FVY] 7.1
KAFJ95L160 – Replacement Long Life Filter Model Item Applied Model Average Efficiency (%) Initial Pressure Loss (Pa) Final Pressure Loss (Pa)
Dimension
Life Time (h) Materials Number Required Per Model Weight (kg)
7.2
KRP4A95 – Installation Box for Adaptor PCB
KRP4A95
Model No. Item Applicable Model Adaptor for Wiring Fixing Place Dimensions (mm)
262
KAFJ95L160 FVY71~125L(A) 60 (Gravity Method) Less Than 8 Less Than 49 2,500 (Dust Particle Concentration at 0.15 mg/m3) Mildew Proot Resin Net 1 0.4
W H D
KRP4A95 FVY71~125L(A) KRP4A52 KRP1B57 In the Unit 180 117 64
SkyAir LU Series
ED21-301
Outdoor Unit
8. Outdoor Unit 8.1
KIS95 – Drain Piping Kit Use this plug to connect a drain hose to an outdoor unit. Outlook KIS95
Drain hose connection dia φ16ID. Notes:
8.2
3
KIS95 Drain piping (With Y joint) plug (3 pcs.)
1. This is the joint for attaching a vinyl hose (field supplied). This is used between the drain hole which is on the bottom plate of outdoor unit and vinyl hose. 2. Drain water accumulate to the bottom of outdoor unit it depends on the situation of operation. But it is necessary to connect drain hose not to be spread the drain water over the neighbors, when it is installed on the wall. 3. The position of holes are unfit to connect with outdoor units in some models. In this case, use it without Y joint.
KKPJ5F180 – Central Drain Plug
SkyAir LU Series
263
Outdoor Unit
8.3
ED21-301
KRK5F80V1 · 140V1 · 160V1 – Year Round Cooling Kit
R71LUY1, R71LUVAL R100LUY1, R100LUVAL, R125LUY1, R125LUTAL, R125LUYAL R140LUY1, R140LUYAL, R140LUTAL
C : 3PA60339B
264
SkyAir LU Series
ED21-301
8.4
Outdoor Unit
KHR58C21, KHD58C21A, KHD58C23A, KHD58C24A, KHD58D31, KHD58D33, KHRJ5F224F, KHRJ5F280F – Refrigerant Branch Piping <Caution> This is the branch kit for refrigerant piping to connect indoor and outdoor units of TWIN/TRIPLE/ DOUBLE Twin simultaneous ON/OFF system.
How to use 1. Uses as branch joints of refrigerant piping. Note) It is necessary because it is not attached to the air conditioner. 2. Pipes of the joint parts are widened. → Enables easy connection and Brazing. 3. Insulation materials are equipped as standard.
Type Model
Item
Reducer
Type Model
Applicable Model
Triple Multi KHD58D33
R(Y)71LU
R(Y)100~140LU
R(Y)200KU
R(Y)250KU
R(Y)140LU
2 — — —
2 — — —
— — 2 1
— — 2 —
— — — —
— — — —
2 — 1 —
— 1 — —
— — — 1
— — — —
Double Twin Multi
Triple Multi KHD58D31 R(Y)200KU
KHRJ5F224F R(Y)200KU
KHRJ5F280F R(Y)250KU
Branch Pipe
Reducer
(2 sets)
1 — — 1
— — — —
— — — —
1 — 1 —
— — — —
— — — —
(2 sets)
— — — —
— — — —
— — — —
— — — —
Branch Pipe
(2 sets)
Reducer
Liquid Side Joint
KHD58C24A
Branch Pipe
Item
Gas Side Joint
Twin Multi KHD58C21A KHD58C23A
Branch Pipe
Reducer
Gas Side Joint
Liquid Side Joint
Applicable Model
KHR58C21
SkyAir LU Series
(2 sets)
265
3
Outdoor Unit
Dimension Twin/Double Twin Multi
ED21-301
Triple Multi
Model
(Horizontal)
266
SkyAir LU Series
The air conditioners manufactured by Daikin Industries have received ISO 9000 series certification for quality assurance.
The airconditioning factories of Daikin Industries have received environmental management system standard ISO 14001 certification.
Certificate Number.
Shiga Plant
(ISO9001) JMI-0107 JQA-0495
(ISO9002) JQA-1452
Certificate Number. EC99J2044
Sakai Plant Certificate Number. JQA-E80009
Yodogawa Plant Certificate Number. EC99J2057
Dealer Head Office: Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome, Kita-ku, Osaka 530-8323, Japan Tokyo Office: Shinjuku Sumitomo Bldg., 6-1, Nishi-Shinjuku 2-chome, Shinjuku-ku, Tokyo 163-0235, Japan
http://www.daikin.com/global/ c All rights reserved
The specifications, designs, and information in this brochure are subject to change without notice.
This book is made of recycled paper.
ED 21-301 Printed in Japan 07/2003 FS