Daikin engineering data sky air (cooling only) LU

Page 1

ED 21 - 301

Split System Air Conditioners SkyAir (Pair and Twin-Triple-Double Twin)

LU Series — Cooling Only —


ED21-301

SkyAir LU Series (Pair) — Cooling Only — ..................................... 1 1. Model Name and Power Supply..............................................................2 1.1 Pair Series................................................................................................2

2. External Appearance...............................................................................4 2.1 External Appearance................................................................................4

3. Functions.................................................................................................5 3.1 Indoor Units + Outdoor Units (35-60G(A), 71-140LU)..............................5

4. Specifications ..........................................................................................8 4.1 50Hz (General).........................................................................................8 4.2 50Hz (Complied with Australian Standard) ............................................19 4.3 60Hz .......................................................................................................21

5. Dimensions and Service Space ............................................................27 5.1 5.2 5.3 5.4

Indoor Unit..............................................................................................27 Remote Controller ..................................................................................42 Outdoor Unit ...........................................................................................45 Installation Service Space for R71LU, 100LU, 125LU, 140LU...............49

6. Piping Diagrams....................................................................................51 6.1 Indoor Unit + Outdoor Unit .....................................................................51

7. Wiring Diagrams....................................................................................54 7.1 Indoor Unit..............................................................................................54 7.2 Outdoor Units .........................................................................................67

8. Capacity Tables ....................................................................................74 8.1 8.2 8.3 8.4

50Hz (General).......................................................................................74 50Hz (Complied with Australian Standard) ............................................79 60Hz .......................................................................................................82 Capacity Correction Factor by The Length of Refrigerant Piping...........87

9. Operation Limits ....................................................................................88 9.1 Operation Limits .....................................................................................88

10.Sound Level ..........................................................................................89 10.1 Overall Sound Level ...............................................................................89 10.2 Octave Band Level .................................................................................90

11.Fan Performance ..................................................................................94 11.1 Fan Performance....................................................................................94

12.Electric Characteristics..........................................................................96 12.1 50Hz .......................................................................................................96 12.2 60Hz .......................................................................................................98

13.Option List .............................................................................................99 13.1 LU Series................................................................................................99

14.Field Piping and Wiring .......................................................................103 14.1 Field piping ...........................................................................................103 14.2 Field Wiring ..........................................................................................106

SkyAir LU Series (Twin, Triple, Double Twin) — Cooling Only — ........................................................... 107 1. Features ..............................................................................................108 1.1 What are Twin, Triple, Double Twin Systems? ....................................108

2. Model Name and Power Supply..........................................................109 2.1 Twin, Triple and Double Twin System..................................................109 Table of Contents

i


ED21-301

3. External Appearance...........................................................................111 3.1 External Appearance............................................................................111

4. Specifications ......................................................................................112 4.1 50Hz .....................................................................................................112 4.2 60Hz .....................................................................................................118

5. Dimensions and Service Space ..........................................................124 5.1 5.2 5.3 5.4 5.5

Indoor Unit............................................................................................124 Remote Controller ................................................................................132 Outdoor Unit .........................................................................................134 Installation Service Space for R71LU, 100LU, 125LU, 140LU.............137 Installation Service Space for R200KU, 250KU ...................................139

6. Piping Diagrams..................................................................................140 6.1 Twin......................................................................................................140 6.2 Triple ....................................................................................................145 6.3 Double Twin .........................................................................................147

7. Wiring Diagrams..................................................................................148 7.1 Indoor Unit............................................................................................148 7.2 Outdoor Unit .........................................................................................150

8. Capacity Tables ..................................................................................155 8.1 50Hz .....................................................................................................155 8.2 60Hz .....................................................................................................158 8.3 Capacity Correction Factor by The Length of Refrigerant Piping.........162

9. Operation Limits ..................................................................................163 9.1 Operation Limits ...................................................................................163

10.Sound Level ........................................................................................164 10.1 Overall Sound Level .............................................................................164 10.2 Octave Band Level ...............................................................................165

11.Electric Characteristics........................................................................167 11.1 50Hz .....................................................................................................167 11.2 60Hz .....................................................................................................168

12.Option List ...........................................................................................170 12.1 LU Series..............................................................................................170

13.Field Piping and Wiring .......................................................................172 13.1 Field Piping...........................................................................................172 13.2 Field Wiring ..........................................................................................175

Detail Information of Options SkyAir LU Series ........................ 177 1. Remote Controller ...............................................................................178 1.1 1.2 1.3 1.4 1.5

Remote Controller, Timer, Adaptor List................................................178 Wired Remote Controller......................................................................178 Wireless Remote Controller .................................................................183 Various Control by Liquid Crystal Remote Controller...........................185 BRC15A61 – Set Back Time Clock ......................................................189

2. Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C] .......................192 2.1 2.2 2.3 2.4 2.5

ii

BYC125K – W1 – Decoration Panel.....................................................192 KDBHJ55K160 – Sealing member of air discharge outlet....................195 KDBJ55K160W – Panel spacer ...........................................................197 KDDP55D160(K) – Fresh Air Intake Kit ...............................................199 KDDJ55X160 – Fresh Air Intake Kit .....................................................202

Table of Contents


ED21-301

2.6 KAFP556D80 · 160 – High Efficiency Filter (Including Filter Chamber) KAFP557D80 · 160 – High Efficiency Filter (Including Filter Chamber)....................................................................204 2.7 KAFJ552K80 · 160 – High Efficiency Filter (Replacement) KAFJ553K80 · 160 – High Efficiency Filter (Replacement)..................204 2.8 KRP1B98 – Installation Box for Adaptor PCB ......................................204 2.9 KDDFP55D160 – High-Efficiency Filter Chamber................................205 2.10 KAFJ551K160 – Long-Life Filter for Decoration Panel (Replacement) ........................207 2.11 KAFP55D160, KAFJ55K160H (Replacement) – Ultra Long-Life Filter (Including Filter Chamber)....................................................................207 2.12 KKSJ55K160 – Chamber Connection Kit.............................................207 2.13 KDJ55K80 · 160 – Branch Duct Chamber............................................208 2.14 Dimensions with Optional Kit................................................................213

3. Ceiling Mounted Cassette Corner Type [FH(Y)K] ...............................217 3.1 3.2 3.3 3.4 3.5 3.6

BYK45FJW1 · 71FJW1 – Decoration panel .........................................217 KPBJ52F56W · 80W – Panel Specer...................................................221 KDBJ52F56W · 80W – Air Discharge Blind Panel ...............................225 KAFJ521F56 · 80 – Replacement Long Life Filter ...............................232 K-HV7AW · 9AW – Discharge Grille.....................................................232 KFDJ52F56 · 80 – Flexible Duct with Shutter ......................................233

4. Ceiling Mounted Built-In Type [FH(Y)B] ..............................................240 4.1 BYBS45DJW1 – Decoration panel BYBS71DJW1 – Decoration panel BYBS125DJW1 – Decoration panel.....................................................240 4.2 KTBJ25K56W · 80W · 160W – Service access panel ..........................244 4.3 KAFJ252L56 · 80 · 160 – High-Efficiency Filter KAFJ253L56 · 80 · 160 – High-Efficiency Filter....................................245 4.4 KAFJ251K56 · 80 · 160 – Replacement long-life filter..........................246 4.5 KAJ25L56D · 80D · 160D – Filter Chamber for Bottom Suction...........246 4.6 KAJ25L56B · 80B · 160B – Filter Chamber for Rear Suction...............247 4.7 KSAJ25K56 · 80 ·160 – Canvas Duct ..................................................250 4.8 K-DG4BW · 5BW · 7BW · 9BW – Air Discharge Unit-Discharge Grille+Discharge Chamber K-DGC4B · 5B · 7B · 9B – Air Discharge Unit-Discharge Grille+Discharge Chamber.................251 4.9 K-DDV20A – Branch Duct ....................................................................253 4.10 K-FDK151B · 152B · 153B · 154B · 155B · 156B – Flexible Duct K-FDK201B · 202B · 203B · 204B · 205B · 206B – Flexible Duct......................................................................................254 4.11 KBBJ25K56 · 80 · 160 – Blind Board ...................................................255 4.12 KDAJ25K56 · 71 · 140 – Adaptor for Discharge...................................255 4.13 KDJ2507K56 · 80 · 160 – Flange for Suction .......................................256 4.14 Optional Kit Installation Drawing ..........................................................257

5. New Ceiling Suspended Cassette Type [FUY] ...................................258 5.1 5.2 5.3 5.4 5.5 Table of Contents

KDBHJ49F80 · 140 – Sealing Member of Air Discharge Outlet ...........258 KDBTJ49F80 · 140 – Decoration Panel for Air Discharge ...................258 KDGJ49F80 · 140 – Vertical Flap Kit ...................................................258 KAFJ495F140 – Replacement Long Life Filter ....................................259 KHFJ49F80 · 140 – L Connection Piping Kit........................................259 iii


ED21-301

5.6 KRP1B97 – Installation Box for Adaptor PCB ......................................259

6. Ceiling Suspended Type [FH(Y)] ........................................................260 6.1 6.2 6.3 6.4

KAFJ501D56 · 80 · 112 · 160 – Replacement Long Life Filter .............260 KDU50B50 · 71 · 125VE – Drain Pump Kit ..........................................260 KHFJ5F50 · 60 · 80 · 160 – L-Type Piping Kit......................................261 KRP1C93 – Installation Box for Adaptor PCB......................................261

7. Floor Standing Type [FVY]..................................................................262 7.1 KAFJ95L160 – Replacement Long Life Filter.......................................262 7.2 KRP4A95 – Installation Box for Adaptor PCB ......................................262

8. Outdoor Unit........................................................................................263 8.1 8.2 8.3 8.4

iv

KIS95 – Drain Piping Kit.......................................................................263 KKPJ5F180 – Central Drain Plug.........................................................263 KRK5F80V1 · 140V1 · 160V1 – Year Round Cooling Kit .....................264 KHR58C21, KHD58C21A, KHD58C23A, KHD58C24A, KHD58D31, KHD58D33, KHRJ5F224F, KHRJ5F280F – Refrigerant Branch Piping .................................................................265

Table of Contents


ED21-301

SkyAir LU Series (Pair) — Cooling Only —

1

Model Series Class Indoor Units

35

45

50

60

71

100

125

140

35K

50K

60K

71K

100K

125K

140K

35F

45F

60F

71FJ

35F

45F

60F

FHYB

71F

100F

125F

FUY

71FJ

100FJ 125FJ

35B

50B

60B

FHY

71B

100B

125B

FAY

71L

100FA

FVY

71LA

35G

50G

FHC FHYC FHK FHYK FHB

FH

Outdoor R Units

50G(A) 60G(A) 71LU

100LA 125LA

100LU 125LU 140LU

Cautions 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.

2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.

SkyAir LU Series – Cooling Only –

1


Model Name and Power Supply

ED21-301

1. Model Name and Power Supply 1.1

Pair Series

1.1.1

50Hz (General) Indoor Units

Notes:

2

Outdoor Units

FHC35KVE

R35GV1

FHC50KVE

R50GV1

FHC60KVE

R60GV1

FHYC71KVE

R71LUV1∗

FHYC100KVE

R100LUV1∗

FHYC71KVE

R71LUY1∗

FHYC100KVE

R100LUY1∗

FHYC125KVE

R125LUY1∗

FHYC140KVE

R140LUY1∗

FHK35FV1

R35GV1

FHK45FV1

R50GV1

FHK60FV1

R60GV1

FHYK71FJV1∗

R71LUV1∗

FHYK71FJV1∗

R71LUY1∗

FHB35FV1

R35GV1

FHB45FV1

R50GV1

FHB60FV1

R60GV1

FHYB71FV1

R71LUV1∗

FHYB100FV1

R100LUV1∗

FHYB71FV1

R71LUY1∗

FHYB100FV1

R100LUY1∗

FHYB125FV1

R125LUY1∗

FUY71FJV1

R71LUV1∗

FUY100FJV1

R100LUV1∗

FUY71FJV1

R71LUY1∗

FUY100FJV1

R100LUY1∗

FUY125FJV1

R125LUY1∗

FH35BVE

R35GV1

FH50BVE

R50GV1

FH60BVE

R60GV1

FHY71BVE

R71LUV1∗

FHY100BVE

R100LUV1∗

FHY71BVE

R71LUY1∗

FHY100BVE

R100LUY1∗

FHY125BVE

R125LUY1∗

FAY71LVE∗

R71LUV1∗

FAY100FAVE

R100LUV1∗

FAY71LVE∗

R71LUY1∗

FAY100FAVE

R100LUY1∗

FVY71LAVE

R71LUV1∗

FVY100LAVE

R100LUV1∗

FVY71LAVE

R71LUY1∗

FVY100LAVE

R100LUY1∗

FVY125LAVE

R125LUY1∗

Power Supply

1φ, 220~240V, 50Hz

3φ, 380~415V, 50Hz

1φ, 220~240V, 50Hz

3φ, 380~415V, 50Hz

1φ, 220~240V, 50Hz

3φ, 380~415V, 50Hz

1φ, 220~240V, 50Hz

3φ, 380~415V, 50Hz

1φ, 220~240V, 50Hz

3φ, 380~415V, 50Hz

1φ, 220~240V, 50Hz 3φ, 380~415V, 50Hz 1φ, 220~240V, 50Hz

3φ, 380~415V, 50Hz

1. ∗ : New Model or Changed Model 2. Power Supply Intake : Outdoor Unit

SkyAir LU Series – Cooling Only –


ED21-301

1.1.2

Model Name and Power Supply

50Hz (Complied with Australian Standard) Indoor Units

1.1.3

Outdoor Units

FHC35KVE

R35GV1A

FHC50KVE

R50GAV1A∗

FHC60KVE

R60GAV1A∗

FH50BVE

R50GAV1A

FH60BVE

R60GAV1A

1

Power Supply

1φ, 240V, 50Hz

60Hz Indoor Units FHC50KVE

Notes:

Outdoor Units

Power Supply

R50GVAL

FHC60KVE

R60GVAL

FHYC71KVE

R71LUVAL∗

1φ, 220V, 60Hz

FHYC100KVE

R100LUVAL∗

FHYC125KVE

R125LUTAL∗

3φ, 220V, 60Hz

FHYC125KVE

R125LUYAL∗

3φ, 380V, 60Hz

FHYC140KVE

R140LUTAL∗

3φ, 220V, 60Hz

FHYC140KVE

R140LUYAL∗

3φ, 380V, 60Hz

FH50BVE

R50GVAL

FH60BVE

R60GVAL

FHY71BVE

R71LUVAL∗

1φ, 220V, 60Hz

FHY100BVE

R100LUVAL∗

FHY125BVE

R125LUTAL∗

3φ, 220V, 60Hz

FHY125BVE

R125LUYAL∗

3φ, 380V, 60Hz

FAY71LVE∗

R71LUVAL∗

FAY100FAVE

R100LUVAL∗

FVY71LAVE

R71LUVAL∗

FVY100LAVE

R100LUVAL∗

FVY125LAVE

R125LUTAL∗

3φ, 220V, 60Hz

FVY125LAVE

R125LUYAL∗

3φ, 380V, 60Hz

1φ, 220V, 60Hz 1φ, 220V, 60Hz

1. ∗ : New Model or Changed Model 2. Power Supply Intake : Outdoor Unit

SkyAir LU Series – Cooling Only –

3


External Appearance

ED21-301

2. External Appearance 2.1

External Appearance

Indoor Units

FH(Y)C–K

FH(Y)K–F(J)

FUY–FJ

FH(Y)–B

FAY71L

FAY100FA

FH(Y)B–F

FVY–LA

Remote Controller

Wired Type Wireless Type

Outdoor Units

R35G R50G(A)

4

R60G(A)

R71LU

R100LU

R125LU

R140LU

SkyAir LU Series – Cooling Only –


ED21-301

Functions

3. Functions 3.1

1

Indoor Units + Outdoor Units (R35-60G(A), R71-140LU) Items Model Type Main Improvement

35~60K

71~140K

Indoor Units

Existing

Existing

Outdoor Units

Existing

New

Appearance Improved

{

{

Reduction of Operation Sound

{

{

Auto Restart

{

{

Fan Operation Mode

{

{

Wired Type

{

{

Wireless Type

{

{

Auto Swing Function

{

{

Ceiling Soiling Prevention

{

{

Wired Type

{

{

Wireless Type

LCD Remote Controller (Option)

For Comfortable Air Conditioning

For Easy Construction and Maintenance

For Flexible Control

Ceiling Mounted Cassette (FH(Y)C)

Improved Points and Functions

Two Select Thermo Sensor Program Dry

{

{

High Fan Speed Mode

High Ceiling Application

{

{

Low Ambient Temperature Kit (Option)

{

Timer Selector

{

{

Fresh Air Intake Directly from The Unit

{

{

Drain Pump

{

{

Long Life Filter

{

{

Ultra-Long Life Filter (Option)

{

{

Mold Resistant Treatment for Filter

{

{

Filter Sign

{

{

Mold Resistant Drain Pan

{

{

Emergency Operation

{

{

Self Diagnoses Function

{

{

Low Gas Pressure Detection (R)

{ (71~140)

Set Back Time Clock

{

{

Double Remote Control

{

{

Group Control by 1 Remote Controller

{

{

Control by D-BACS

{

{

Remote/Centralized Control

{

{

z : Improved Points and Functions { : Functions — : No Functions

SkyAir LU Series – Cooling Only –

5


Functions

ED21-301

Items

Model Type

Ceiling Mounted Cassette Corner (FH(Y)K)

Ceiling Mounted Built-In (FH(Y)B)

35~60F

71FJ

35~60F

71~ 125F

71~125FJ

Indoor Units

Existing

New

Existing

Existing

Existing

Outdoor Units

Existing

New

Existing

New

New

{

{

{

{

{

{

{

{

Auto Restart

{

{

{

{

{

Fan Operation Mode

{

{

{

{

{

LCD Remote Controller (Option)

{

{

{

{

{

Auto Swing Function

{

{

{

Ceiling Soiling Prevention

{

{

{

Wired Type

{

{

{

{

{

Wireless Type

Improved Points and Functions

Appearance Improved

Main Improvement Reduction of Operation Sound

For Comfortable Air Conditioning

For Easy Construction and Maintenance

For Flexible Control

Two Select Thermo Sensor

New Ceiling Suspended (FUY)

Program Dry

{

{

{

{

{

High Fan Speed Mode

High Ceiling Application

{

{

{

Low Ambient Temperature Kit (Option)

{

{

{

Timer Selector

{

{

{

{

{

Fresh Air Intake Directly from The Unit

{

{

{

{

Drain Pump

{

{

{

{

{

Long Life Filter

{

{

{

{

{

Ultra-Long Life Filter (Option)

Mold Resistant Treatment for Filter

{

{

{

{

{

Filter Sign

{

{

{

{

{

Mold Resistant Drain Pan

{

{

{

{

{

Emergency Operation

{

{

{

{

{

Self Diagnoses Function

{

{

{

{

{

{ {(71~125) (71~125)

Low Gas Pressure Detection (R)

{(71)

Set Back Time Clock

{

{

{

{

{

Double Remote Control

{

{

{

{

{

Group Control by 1 Remote Controller

{

{

{

{

{

Control by D-BACS

{

{

{

{

{

Remote/Centralized Control

{

{

{

{

{

z : Improved Points and Functions { : Functions — : No Functions

6

SkyAir LU Series – Cooling Only –


ED21-301

Functions

Items

Improved Points and Functions

Wall Floor Mounted Standing (FAY) (FVY)

Ceiling Suspended (FH(Y)) 35, 50B

60, 71B

100B, 125B

71L, 100FA

71~125LA

Indoor Units

Existing

Existing

Existing

New(71)

Existing

Outdoor Units

Existing

New(71)

New

New

New

{

{

{

{

{

Main Improvement Reduction of Dimensions or Weight Reduction of Operation Sound

{

{

{

{

{

{

{

{

{

{

Auto Restart Fan Operation Mode

{

{

{

{

{

{

{

{

{

{

LCD Remote Controller (Option) Wired

{

{

{

{

{

LCD Remote Controller (Option) Wirelless

{

{

{

{

Model Type

Appearance Improved

For Comfortable Air Conditioning

For Easy Construction and Maintenance

For Flexible Control

Auto Swing Function

{

{

{

{

{

Ceiling Soiling Prevention

Wired Type

{

{

{

{

{

Wireless Type

Two Select Thermo Sensor

Program Dry

{

{

{

{

{

High Fan Speed Mode

{

— —

High Ceiling Application

{

{

{

Low Ambient Temperature Kit (Option)

{

{

{

{

Timer Selector

{

{

{

{

{

Fresh Air Intake Directly from The Unit

Drain Pump Kit (Option)

{

{

{

Long Life Filter

{

{

{

{

Ultra-Long Life Filter (Option)

Mold Resistant Treatment For Filter

{

{

{

{

{

Filter Sign

{

{

{

{

{

Mold Resistant Drain Pan

{

{

{

{

Emergency Operation

{

{

{

{

{

Self Diagnoses Function

{

{

{

{

{

{ { { (100, 125) (71, 100) (71~125)

Low Gas Pressure Detection (R)

{(71)

Set Back Time Clock

{

{

{

{

{

Double Remote Control

{

{

{

{

{

Group Control by 1 Remote Controller

{

{

{

{

{

Control by D-BACS

{

{

{

{

{ — {

Installation Box for Adapter PCB

z (71 only)

Remote/Centralized Control

{

{

{

{

z : Improved Points and Functions { : Functions — : No Functions

SkyAir LU Series – Cooling Only –

7

1


Specifications

ED21-301

4. Specifications 4.1

50Hz (General)

FHC (Ceiling Mounted Cassette Type) <50Hz> Model

Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)

Indoor Units Dimensions Coil

Fan

FHC35KVE R35GV1 3.54/3.5 12,100/11,900 3,040/3,010 FHC35KVE

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Weight Piping Connections

Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)

Wired Wireless

Model Color Dimensions (H×W×D) Air Filter Weight

Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Hz–Volts

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V

2. 3. 4. 5.

8

FHC50KVE FHC60KVE R50GV1 R60GV1 kW 5.34/5.3 6.44/6.4 Btu/h 18,200/18,100 22,000/21,800 kcal/h 4,590/4,560 5,540/5,500 FHC50KVE FHC60KVE mm 230×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 m² 0.331 QTS45B14M Turbo Fan W 45 m³/min. (H) 14 (L) 10 (H) 15 (L) 11 (H) 19 (L) 14 kg 24 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 5) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R35GV1 R50GV1 R60GV1 Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC46AV1TRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.1 1.7 2.2 PZ380 PZ430 Propeller W 27 45 53 m³/min. 28 27 40 kg 37 42 61 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor. Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 25 30 m 15 R22 kg 1.10 (Charged for 10m) 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.50 0.85 1.20 4D006549A

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

Capacities are net, including a deduction for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

1

FHYC (Ceiling Mounted Cassette Type) <50Hz> Model

Indoor Units Outdoor Units

∗1 Cooling Capacity (1)/(2)/(3)

Indoor Units Dimensions Coil

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2

Weight Piping Connections

Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)

Wired Wireless

Model Color Dimensions (H×W×D) Air Filter Weight

Outdoor Units Color Dimensions Coil

Comp.

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate

Weight Piping Connections

∗2 kg

Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FHYC71KVE R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FHYC71KVE 230×840×840

FHYC100KVE R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FHYC100KVE

FHYC125KVE FHYC140KVE V1 — — Y1 R125LUY1 R140LUY1 kW 13.0/12.8/12.8 14.5/14.2/14.2 Btu/h 44,500/43,600/43,600 49,400/48,400/48,400 kcal/h 11,200/11,000/11,000 12,500/12,200/12,200 FHYC125KVE FHYC140KVE mm 288×840×840 Cross Fin coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 2×12×1.5 m² 0.331 0.497 QTS45B14M QTS45A17M Turbo Fan W 45 90 m³/min. (H) 19–21 (L) 14–16 (H) 28–31 (L) 21–24 (H) 33–36 (L) 24–27 (H) 35–38 (L) 26–28 kg 24 28 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 5, 6) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 V1 R71LUV1 R100LUV1 — — Y1 R71LUY1 R100LUY1 R125LUY1 R140LUY1 Ivory mm 770×900×320 1,170×900×320 1,345×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 2×60×2.0 m² 0.634 0.983 1.134 V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE JT170BC–YE Hermetically Sealed Scroll Type kW 2.24 3.00 3.75 4.50 P47L11S P47L11SX2 Propeller W 65 90 65+85 65+90 m³/min. 48–51 59–62 92–100 97–109 V1 72 87 — Y1 71 84 98 109 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125·140>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K L 1.2 1.2 1.5 1.6 4D039096 4D039079

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–220V (380V)

JIS B8616

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V (415V)

AS 1861

2. 3. 4. 5. 6.

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

∗2 AFR (Air flow rafe) and sound pressure level are shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

9


Specifications

ED21-301

FHK (Ceiling Mounted Cassette Corner Type) <50Hz> Model

Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)

Indoor Units Dimensions Coil

Fan

kW Btu/h kcal/h

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Weight Piping Connections

Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)

Wired Wireless

Model Color Dimensions (H×W×D) Air Filter Weight

Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FHK45FV1 R50GV1 5.19/5.1 17,700/17,500 4,460/4,400 FHK45FV1

mm

FHK60FV1 R60GV1 6.6/6.5 22,760/22,200 5,690/5,600 FHK60FV1 215×1,310×710

215×1,110×710 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×11×1.75 3×11×1.75 m² 0.180 0.226 3D12H1AH1V1 3D12H1AJ1V1 4D12H1AG1V1 Sirocco Fan W 20 25 45 m³/min. (H) 12 (L) 9 (H) 12 (L) 10 (H) 17 (L) 14 kg 30 31 33 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 6) — BYK45FJW1 BYK71FJW1 White mm 70×1,240×800 70×1,440×800 Resin Net (with Mold Resistant) kg 8.5 9.5 R35GV1 R50GV1 R60GV1 Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC46AV1TRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.1 1.7 2.2 PZ380 PZ430 Propeller W 27 45 53 m³/min. 28 27 40 kg 37 42 61 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35, 50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor.Fuse. % 100–0 Capillary Tube m 25 30 m 15 R22 kg 1.10 (Charged for 10m) 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.50 0.85 1.20 4D006259A

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Hz–Volts

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

2. 3. 4. 5.

10

FHK35FV1 R35GV1 3.54/3.4 12,100/11,600 3,040/2,930 FHK35FV1

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

1

FHYK (Ceiling Mounted Cassette Corner Type) <50Hz> Model

Indoor Units Outdoor Units

∗1 Cooling Capacity (1)/(2)/(3)

Indoor Units Dimensions Coil

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Weight Piping Connections

Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)

Wired Wireless

Model Color Dimensions (H×W×D) Air Filter Weight

Outdoor Units Color Dimensions Coil

Comp.

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate

Weight Piping Connections

kg Liquid Gas Drain

Safety Devices

Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FHYK71FJV1 V1 R71LUV1 Y1 R71LUY1 kW 7.8/7.7/7.7 Btu/h 26,600/26,200/26,200 kcal/h 6,700/6,600/6,600 FHYK71FJV1 mm 215×1,310×710 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 3×11×1.75 m² 0.226 4D12H1AG1V1 Sirocco Fan W 45 m³/min. (H) 17–18 (L) 14–15 ∗3 kg 33 mm φ9.5 (Flare) mm φ15.9 (Flare) mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 6) — BYK71FJW1 White mm 70×1,440×800 Resin Net (with Mold Resistant) kg 9.5 V1 R71LUV1 Y1 R71LUY1 Ivory mm 770×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 m² 0.634 V1 ZR36K3–PFJ Y1 ZR36K3–TFD Hermetically Sealed Scroll Type kW 2.24 P47L11S Propeller W 65 m³/min. 48–51 ∗3 V1 72 Y1 71 φ9.5 (Flare) mm mm φ15.9 (Flare) φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor Protector (Compressor). Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) SONTEX 200LT L 1.2 4D039104

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–220V (380V)

JIS B8616

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V (415V)

AS 1861

2. 3. 4. 5. 6.

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. ∗3 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

11


Specifications

ED21-301

FHB (Ceiling Mounted Built-In Type) <50Hz> Model

Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)

Indoor Units Dimensions Coil

Fan

kW Btu/h kcal/h

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Air Filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)

Wired Wireless

Model Color Dimensions (H×W×D) Weight

Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FHB45FV1 R50GV1 5.19/5.1 17,700/17,500 4,460/4,400 FHB45FV1

mm

FHB60FV1 R60GV1 6.6/6.5 22,760/22,200 5,690/5,600 FHB60FV1 300×1,000×800

300×700×800 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 3×14×1.75 m² 0.132 0.221 D18H2AH1V1 D18H2AJ1V1 2D18H2AH1V1 Sirocco Fan W 65 85 110 m³/min. (H) 11.5 (L) 9 (H) 14 (L) 10 (H) 17 (L) 13 Resin Net (with Mold Resistant) kg 30 31 41 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 5) — BYBS45DJW1 (∗2 BYBS45D–W2) BYBS71DJW1 (∗2 BYBS71D–W2) White mm 55×880×500 55×1,100×500 kg 3.5 4.5 R35GV1 R50GV1 R60GV1 Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC46AV1TRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.1 1.7 2.2 PZ380 PZ430 Propeller W 27 45 53 m³/min. 28 27 40 kg 37 42 61 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35 · 50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 25 30 m 15 R22 kg 1.10 (Charged for 10m) 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.50 0.85 1.2 4D006258B

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Hz–Volts

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V

2. 3. 4. 5. 6.

12

FHB35FV1 R35GV1 3.54/3.4 12,100/11,600 3,040/2,930 FHB35FV1

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B62 is also available. Wire for remote controller : Field supplied. ∗2 This type can be used.

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

1

FHYB (Ceiling Mounted Built-In Type) <50Hz> Model

Indoor Units Outdoor Units

V1 Y1 kW Btu/h kcal/h

∗1 Cooling Capacity (1)/(2)/(3)

Indoor Units Dimensions Coil

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2

Air Filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)

Wired Wireless

Model Color Dimensions (H×W×D) Weight

Outdoor Units Color Dimensions Coil

Comp.

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate

Weight Piping Connections

∗2 kg

Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FHYB71FV1 R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FHYB71FV1 300×1,000×800

mm

FHYB100FV1 R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FHYB100FV1 300×1,400×800 Cross Fin Coil 3×14×1.75

0.221 2D18H2AJ1V1

0.338 3D18H2AN1V1 3D18H2AP1V1 Sirocco Fan W 125 135 225 m³/min. (H) 19–21.5 (L) 14–16.5 (H) 27–29 (L) 20–22 (H) 35–40.5 (L) 24–29.5 Resin Net (with Mold Resistant) kg 41 51 52 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 5) — BYBS71DJW1 (∗3 BYBS71D–W2) BYBS125DJW1 (∗3 BYBS125D–W2) White mm 55×1,100×500 55×1,500×500 kg 4.5 6.5 V1 R71LUV1 R100LUV1 — Y1 R71LUY1 R100LUY1 R125LUY1 Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Hermetically Sealed Scroll Type kW 2.24 3.00 3.75 P47L11S P47L11S×2 Propeller W 65 90 65+85 m³/min. 48–51 59–62 92–100 V1 72 87 — Y1 71 84 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K L 1.2 1.5 4D039103

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–220V (380V)

JIS B8616

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V (415V)

AS 1861

2. 3. 4. 5. 6.

FHYB125FV1 — R125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 FHYB125FV1

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. BRC1B62 is also available. Wire for remote controller : Field supplied. ∗3 This type can be used.

SkyAir LU Series – Cooling Only –

13


Specifications

ED21-301

FUY (New Ceiling Suspended Cassette Type) <50Hz> Model

Indoor Units Outdoor Units

∗1 Cooling Capacity (1)/(2)/(3)

Indoor Unit Color Dimensions Coil

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Air Filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Comp.

Fan

mm

165×895×895

W m³/min

Wired Wireless V1 Y1

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate

Weight Piping Connections

FUY71FJV1 R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FUY71FJV1

kg mm mm mm

Outdoor Units Color Dimensions Coil

V1 Y1 kW Btu/h kcal/h

mm

m² V1 Y1 kW

W m³/min V1 Y1 mm mm mm

∗2 kg

Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

m m kg L

FUY125FJV1 — R125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 FUY125FJV1

230×895×895 Cross Fin Coil (Multi Louver Fins and Hi–XA Tubes) 3×6×1.5 3×8×1.5 0.265 0.353 QTS48A QTS50B15M Turbo Fan 45 90 (H)19 (L)14 (H)29 (L)21 (H)32 (L)23 Resin Net (with Mold Resistant) 25 31 φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) I.D φ20×O.D φ26 BRC1C61 (Note. 4, 5) BRC7C529W R71LUV1 R100LUV1 — R71LUY1 R100LUY1 R125LUY1 Ivoly 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 0.634 0.983 ZR36K3–PFJ ZR48K3–PFJ — ZR36K3–TFD ZR48K3–TFD JT160BC–YE Hermetically Sealed Scroll Type 2.24 3.00 3.75 P47L11S P47L11S×2 Propeller 65 90 65+85 48–51 59–62 92–100 72 87 — 71 84 98 φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ26.0 (Hole) Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. 100–0 Electronic Expansion Valve 50 (Equivalent Length 70m) 30 R22 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K 1.2 1.5 4D039105

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–220V (380V)

JIS B8616

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V (415V)

AS 1861

2. 3. 4. 5.

14

%

FUY100FJV1 R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FUY100FJV1 White

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

1

FH (Ceiling Suspended Type) <50Hz> Model

Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)

Indoor Units Color Dimensions Coil

Fan

kW Btu/h kcal/h

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Air filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Wired Wireless

Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FH35BVE R35GV1 3.54/3.4 12,100/11,600 3,040/2,930 FH35BVE

FH50BVE R50GV1 5.19/5.1 17,700/17,500 4,460/4,400 FH50BVE White

FH60BVE R60GV1 6.6/6.5 22,760/22,200 5,690/5,600 FH60BVE

mm

195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 2×12×1.75 3×12×1.75 m² 0.182 0.223 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H) 13 (L) 10 (H) 16 (L) 13 Resin Net (with Mold Resistant) kg 23 24 26 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 4) BRC7E66 R35GV1 R50GV1 R60GV1 Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC46AV1TRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.1 1.7 2.2 PZ380 PZ430 Propeller W 27 45 53 m³/min. 28 27 40 kg 37 42 61 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35 · 50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 25 30 m 15 R22 kg 1.10 (Charged for 10m) 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.50 0.85 1.20 4D028432

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Hz–Volts

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for indoor fan motor heat. 3. In case of drain piping for outdoor unit, drain piping kit (option) is needed. 4. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

15


Specifications

ED21-301

FHY (Ceiling Suspended Type) <50Hz> Model

Indoor Units Outdoor Units

∗1 Cooling Capacity (1)/(2)/(3)

Indoor Units Color Dimensions Coil

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Air filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Wired Wireless

Outdoor Units Color Dimensions Coil

Comp.

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate

Weight Piping Connections

∗2 kg

Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FHY71BVE R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FHY71BVE

FHY100BVE FHY125BVE R100LUV1 — R100LUY1 R125LUY1 10.6/10.5/10.5 13.0/12.8/12.8 36,100/35,700/35,700 44,500/43,600/43,600 9,100/9,000/9,000 11,200/11,000/11,000 FHY100BVE FHY125BVE White mm 195×1,160×680 195×1,400×680 195×1,590×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.293 0.341 4D12K1AA1 3D12K2AA1 4D12K2AA1 Sirocco Fan W 62 130 m³/min. (H) 17 (L) 14 (H) 24 (L) 20 (H) 30 (L) 25 Resin Net (with Mold Resistant) kg 27 32 35 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 4) BRC7E66 V1 R71LUV1 R100LUV1 — Y1 R71LUY1 R100LUY1 R125LUY1 Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Hermetically Sealed Scroll Type kW 2.24 3.00 3.75 P47L11S P47L11S×2 Propeller W 65 90 65+85 m³/min. 48–51 59–62 92–100 V1 72 87 — Y1 71 84 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K L 1.2 1.5 4D039099 V1 Y1 kW Btu/h kcal/h

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–220V (380V)

JIS B8616

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V (415V)

AS 1861

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. ∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). 3. Capacities are net, including a deduction for cooling for indoor fan motor heat. 4. Wire for remote controller : Field supplied.

16

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

1

FAY (Wall Mounted Type) <50Hz> Model

Indoor Units Outdoor Units

V1 Y1 kW Btu/h kcal/h

∗1 Cooling Capacity (1)/(2)/(3)

Indoor Units Color Dimensions Coil

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2

Air Filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Wired Wireless

Outdoor Units Color Dimensions Coil

Comp.

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate

Weight Piping Connections

∗2 kg

Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FAY71LVE R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FAY71LVE

FAY100FAVE R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FAY100FAVE

White 290×1,050×230 360×1,570×200 Cross Fin Coil (Multi Louver Fins and Hi–XA Tubes) 2×16×1.4 2×12×1.4 m² 0.289 0.332 QCL9686M QCL1163MA+QCL1163MB Cross Flow Fan W 43 46 m³/min. (H) 19–19 (L) 15–15 (H) 23–23 (L) 19–19 Resin Net (with Mold Resistant) kg 13 26 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm I. Dφ20×O. Dφ26 mm I. Dφ13×O. Dφ18 BRC1C61 (Note. 5, 6) BRC7E619 BRC7C611W V1 R71LUV1 R100LUV1 Y1 R71LUY1 R100LUY1 Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 V1 ZR36K3–PFJ ZR48K3–PFJ Y1 ZR36K3–TFD ZR48K3–TFD Hermetically Sealed Scroll Type kW 2.24 3.00 P47L11S Propeller W 65 90 m³/min. 48–51 59–62 V1 72 87 Y1 71 84 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor Protector (Compressor). Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT L 1.2 4D039583 4D039106 mm

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–220V (380V)

JIS B8616

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V (415V)

AS 1861

2. 3. 4. 5. 6.

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

17


Specifications

ED21-301

FVY (Floor Standing Type) <50Hz> Model

Indoor Units Outdoor Units

∗1 Cooling Capacity (1)/(2)/(3)

Indoor Units Color Dimensions Coil

Fan

Air Filter Weight Piping Connections

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2

Liquid Gas Drain

Outdoor Units Color Dimensions Coil

Comp.

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate

Weight Piping Connections

∗2 kg

Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

V1 Y1 kW Btu/h kcal/h

FVY71LAVE R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FVY71LAVE

mm

1,850×600×270

FVY100LAVE R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FVY100LAVE White 1,850×600×350 Cross Fin Coil 2×44×1.75 0.44

2×40×1.75 0.40 QS37A1AM

FVY125LAVE — R125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 FVY125LAVE

(3×22×1.75)×2 0.44 (0.22×2)

QS37A2AM Sirroco Fan W 30 60 90 m³/min. (H) 18–20 (L) 14–16 (H) 28–31 (L) 22–25 (H) 32–35 (L) 25–28 Resin Net (with Mold Resistant) kg 39 46 47 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ20×O. Dφ26 V1 R71LUV1 R100LUV1 — Y1 R71LUY1 R100LUY1 R125LUY1 Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Hermetically Sealed Scroll Type kW 2.24 3.00 3.75 P47L11S P47L11S×2 Propeller W 65 90 65+85 m³/min. 48–51 59–62 92–100 V1 72 87 — Y1 71 84 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K L 1.2 1.5 4D039102

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–220V (380V)

JIS B8616

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V (415V)

AS 1861

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. ∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). 3. Capacities are net, including a deduction for cooling for indoor fan motor heat.

18

SkyAir LU Series – Cooling Only –


ED21-301

4.2

Specifications

50Hz (Complied with Australian Standard)

1

FHC (Ceiling Mounted Cassette Type) <50Hz> Model

Indoor Units Outdoor Units ∗1 Cooling Capacity

Indoor Units Dimensions Coil

Fan

FHC35KVE R35GV1A 3.43 11,700 2,950 FHC35KVE

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Weight Piping Connections

Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)

Wired Wireless

Model Color Dimensions (H×W×D) Air Filter Weight

Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FHC50KVE FHC60KVE R50GAV1A R60GAV1A kW 5.3 6.4 Btu/h 18,100 21,800 kcal/h 4,560 5,500 FHC50KVE FHC60KVE mm 230×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 m² 0.331 QTS45B14M Turbo Fan W 45 m³/min. (H) 16 (L) 12 (H) 17 (L) 13 (H) 21 (L) 16 kg 24 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 4, 5) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R35GV1A R50GAV1A R60GAV1A Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC46AV1TRT RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.1 1.7 2.2 PZ380 PZ430 Propeller W 27 45 53 m³/min. 29 28 41 kg 37 42 61 φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35·50 Model). Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 25 30 m 15 R22 kg 1.10 (Charged for 10m) 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.50 0.85 1.20 C : 4D010466A

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V

AS 1861

2. 3. 4. 5.

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

19


Specifications

ED21-301

FH (Ceiling Suspended Type) <50Hz> Model

Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)/(3)

Indoor Units Color Dimensions Coil

Fan

kW Btu/h kcal/h

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Air Filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Wired Wireless

Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FH50BVE R50GAV1A 5.19/5.1/5.1 17,700/17,500/17,500 4,460/4,400/4,400 FH50BVE

FH60BVE R60GAV1A 6.6/6.5/6.5 22,760/22,200/22,200 5,690/5,600/5,600 FH60BVE

White 195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.182 4D12K1AA1 3D12K1AA1 Sirocco Fan W 62 m³/min. (H) 13 (L) 10 (H) 16 (L) 13 Resin Net (with Mold Resistant) kg 24 26 φ6.4 (Flare) mm φ15.9 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 3) BRC7E66 R50GAV1A R60GAV1A Ivory White mm 685×800×300 540×750×270 Cross Fin Coil (HL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC70AV1TRT NH41VMDT Hermetically Sealed Rotary Type kW 1.7 2.2 PZ430 PZ380 Propeller W 45 53 m³/min. 28 41 kg 42 61 φ6.4 (Flare) mm φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor (35·50 Model) Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 30 m 15 R22 kg 1.20 (Charged for 10m) 1.50 (Charged for 5m) SUNISO 4GS–DI MS–32 L 0.85 1.2 C : 4D028448 mm

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V

AS 1861

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Wire for remote controller : Field supplied.

20

SkyAir LU Series – Cooling Only –


ED21-301

4.3

Specifications

60Hz

1

FHC (Ceiling Mounted Cassette Type) <60Hz> Model

Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)

Indoor Unit Dimensions Coil

Fan

kW Btu/h kcal/h

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate Sound Pressure Level

Weight Piping Connections

Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)

Wired Wireless

Model Color Dimensions (H×W×D) Air Filter Weight

Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FHC50KVE R50GVAL 5.64/5.6 19,300/19,100 4,850/4,820 FHC50KVE

FHC60KVE R60GVAL 6.84/6.8 23,400/23,200 5,880/5,850 FHC60KVE

mm

230×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 m² 0.331 QTS45B14M Turbo Fan W 45 m³/min. (H)15 (L)11 (H)19 (L)14 dB(A) — kg 24 φ6.4 (Flare) mm φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 5, 6) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R50GVAL R60GVAL Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (FL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC60VHTNRT RC75VHTR2T Hermetically Sealed Rotary Type kW 1.5 1.8 PZ380 PZ430 Propeller W 45 53 m³/min. 30 44 kg 41 51 φ6.4 (Flare) mm φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 30 m 15 R22 kg 1.15 (Charged for 10m) 1.60 (Charged for 5m) SUNISO 4GS–DI L

0.85

1.00 4D006550B

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

(1)

Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB

5m

(2)

Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB

5m

2. 3. 4. 5. 6.

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. Each value shows the specification per one unit. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

21


Specifications

ED21-301

FHYC (Ceiling Mounted Cassette Type) <60Hz> Model

Indoor Units Outdoor Units

∗1 Cooling Capacity (1)/(2)

Indoor Unit Dimensions Coil

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate Sound Pressure Level

Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Decoration Panel (Option)

Wired Wireless

Model Color Dimensions (H×W×D) Air Filter Weight

Outdoor Units

Color Dimensions Coil

Comp.

Fan

Weight Piping Connections

H×W×D Type Row×Stages×Fin Pitch Face Area Model

Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

SONTEX 200LT 1.2

L

SUNISO 4GSDID–K 1.5 4D039107

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Standard

(1)

Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB

5m

(2)

Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB

7.5m

JIS B8616

2. 3. 4. 5. 6.

22

FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE R71LUVAL R100LUVAL — — — — R125LUTAL R140LUTAL — — R125LUYAL R140LUYAL 8.3/8.1 11.6/11.4 14.5/14.3 16.1/15.8 28,200/27,800 39,700/38,900 49,600/48,800 55,000/53,900 7,100/7,000 10,000/9,800 12,500/12,300 13,800/13,500 FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE mm 230×840×840 288×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Cross Fin Coil 2×8×1.5 2×12×1.5 m² 0.331 0.497 QTS45B14M QTS45A17M Turbo Fan W 45 90 m³/min. (H)19 (L)14 (H)28 (L)21 (H)33 (L)24 (H)35 (L)26 dB(A) — (H)44 (L)37 kg 24 28 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 6) BRC1C61 (Note. 5, 6) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 VAL R71LUVAL R100LUVAL — — TAL — — R125LUTAL R140LUTAL YAL — — R125LUYAL R140LUYAL Ivory mm 770×900×320 1,170×900×320 1,345×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 2×60×2.0 m² 0.634 0.983 1.134 VAL ZR36K3–PFV ZR47K3–PFV — TAL — JT170BC JT170BC YAL — JT170BC–YH JT170BC–YE Hermetically Sealed Scroll Type kW 2.24 2.92 3.75 4.50 P47L11S P47L11S×2 Propeller W 75 100 95+75 65+90 m³/min. 49 59 94 97–109 kg 75 92 98 112 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125·140>. Low Pressure Switch. Over Current Decive. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m) VAL TAL YAL kW Btu/h kcal/h

1.6 4D040213

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. Each value shows the specification per one unit. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

1

FH (Ceiling Suspended Type) <60Hz> Model

Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)/(3)

Indoor Unit Color Dimensions Coil

Fan

kW Btu/h kcal/h

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Air Filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Wired Wireless

Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FH50BVE R50GVAL 5.3/5.25/4.5 18,240/18,000/15,400 4,560/4,500/3,900 FH50BVE

FH60BVE R60GVAL 6.6/6.5/5.6 22,760/22,200/19,100 5,690/5,600/4,800 FH60BVE

White 195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.182 0.233 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)16 (L)13 Resin Net (with Mold Resistant) kg 24 26 φ6.4 (Flare) mm φ15.9 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 4) BRC7E66 R50GVAL R60GVAL Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (FL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC60VHTNRT RC75VHTR2T Hermetically Sealed Rotary Type kW 1.5 1.8 PZ380 PZ430 Propeller W 45 53 m³/min. 30 44 kg 41 51 φ6.4 (Flare) mm φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100-0 Capillary Tube m 30 m 15 R22 kg 1.15 (Charged for 10m) 1.60 (Charged for 5m) mm

SUNISO 4GS–DI L

0.85

1.00 4D028441

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m (Horizontal)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

5m (Horizontal)

(3)

Indoor : 29°CDB, 19.0°CWB Outdoor : 46°CDB, 24°CWB

7.5m (Horizontal)

SASO

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

23


Specifications

ED21-301

FHY (Ceiling Suspended Type) <60Hz> Model

Indoor Units Outdoor Units

∗1 Cooling Capacity (1)/(2)

Indoor Unit Color Dimensions Coil

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Air Filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Wired Wireless

Outdoor Units

Color Dimensions Coil

Comp.

Fan

Weight Piping Connections

H×W×D Type Row×Stages×Fin Pitch Face Area Model

Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FHY71BVE R71LUVAL — — 8.3/8.1 28,200/27,800 7,100/7,000 FHY71BVE

FHY100BVE FHY125BVE R100LUVAL — — R125LUTAL — R125LUYAL 11.6/11.4 14.5/14.3 39,700/38,900 49,600/48,800 10,000/9,800 12,500/12,300 FHY100BVE FHY125BVE White mm 195×1,160×680 195×1,400×680 195×1,590×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.293 0.341 4D12K1AA1 3D12K2AA1 4D12K2AA1 Sirocco Fan W 62 130 m³/min. (H)17 (L)14 (H)24 (L)20 (H)30 (L)25 Resin Net (with Mold Resistant) 32 35 kg 27 mm φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 4) BRC7E66 VAL R71LUVAL R100LUVAL — TAL — — R125LUTAL YAL — — R125LUYAL Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 VAL ZR36K3–PFV ZR47K3–PFV — TAL — JT160BC YAL — JT160BC–YH Hermetically Sealed Scroll Type kW 2.24 2.92 3.75 P47L11S P47L11S×2 Propeller W 75 100 95+75 m³/min. 49 59 94 kg 75 92 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse. % 100-0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) VAL TAL YAL kW Btu/h kcal/h

SONTEX 200LT 1.2

L

SUNISO 4GSDID–K 1.5 4D039110

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m (Horizontal)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m (Horizontal)

JIS B8616

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.

24

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

1

FAY (Wall Mounted Type) <60Hz> Model

Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)

Indoor Units Color Dimensions Coil

Fan

kW Btu/h kcal/h

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Air Filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Wired Wireless

Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

FAY71LVE R71LUVAL 8.3/8.1 28,200/27,800 7,100/7,000 FAY71LVE

FAY100FAVE R100LUVAL 11.6/11.4 39,700/38,900 10,000/9,800 FAY100FAVE

White 290×1,050×230 360×1,570×200 Cross Fin Coil (Multi Louver Fins and Hi–XA Tubes) 2×16×1.4 2×12×1.4 m² 0.289 0.332 QCL9686M QCL1163MA+QCL1163MB Cross Flow Fan W 43 46 m³/min. (H) 19–19 (L) 15–15 (H) 23 (L) 19 Resin Net (with Mold Resistant) kg 13 26 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm I. Dφ20×O. Dφ26 mm I. Dφ13×O. Dφ18 BRC1C61 (Note. 4, 5) BRC7E619 BRC7C611W R71LUVAL R100LUVAL Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 ZR36K3–PFV ZR47K3–PFV Hermetically Sealed Scroll Type kW 2.24 2.92 P47L11S Propeller W 75 100 m³/min. 49 59 kg 75 92 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor Protector (Compressor). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT L 1.2 1.2 4D041586 4D039114 mm

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

JIS B8616

2. 3. 4. 5.

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat. Each value for indoor unit shows the specification per one unit. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

25


Specifications

ED21-301

FVY (Floor Standing Type) <60Hz> Model

Indoor Units Outdoor Units

∗1 Cooling Capacity (1)/(2)

Indoor Units Color Dimensions Coil

Fan

Air Filter Weight Piping Connections

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate

Liquid Gas Drain

Outdoor Units

Color Dimensions Coil

Comp.

Fan

Weight Piping Connections

H×W×D Type Row×Stages×Fin Pitch Face Area Model

Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

VAL TAL YAL kW Btu/h kcal/h

FVY71LAVE R71LUVAL — — 8.3/8.1 28,200/27,800 7,100/7,000 FVY71LAVE

mm

1,850×600×270

FVY100LAVE R100LUVAL — — 11.6/11.4 39,700/38,900 10,000/9,800 FVY100LAVE White

FVY125LAVE — R125LUTAL R125LUYAL 14.5/14.3 49,600/48,800 12,500/12,300 FVY125LAVE

1,850×600×350 Cross Fin Coil 2×40×1.75 2×44×1.75 (3×22×1.75)×2 m² 0.40 0.44 0.44 (0.22×2) QS37A1AM QS37A2AM QS37A2AM Sirroco Fan W 30 60 90 m³/min. (H) 18 (L) 14 (H) 28 (L) 22 (H) 32 (L) 25 Resin Net (with Mold Resistant) kg 39 46 47 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ20×O. Dφ26 VAL R71LUVAL R100LUVAL — TAL — — R125LUTAL YAL — — R125LUYAL Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 VAL ZR36K3–PFV ZR47K3–PFV — TAL — — JT160BC YAL — — JT160BC–YH Hermetically Sealed Scroll Type kW 2.24 2.92 3.75 P47L11S P47L11S×2 Propeller W 75 100 95+75 m³/min. 49 59 94 kg 75 92 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT SUNISO 4GSDID–K L 1.2 1.5 4D039113

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

JIS B8616

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Each value for indoor unit shows the specification per one unit.

26

SkyAir LU Series – Cooling Only –


ED21-301

Dimensions and Service Space

5. Dimensions and Service Space 5.1

Indoor Unit

5.1.1

FH(Y)C (Ceiling Mounted Cassette Type)

1

FHC35K + BYC125K-W1 C 860~890 Ceiling opening

80

2× 100=200

Unit (mm)

85

300 or less 680 Suspension position

950

(165)

Note3.

420

9

Branch duct connection

350 C

view 60

4-M4 Hole (prepared hole) φ7

80 80

6

40

860~890 Ceiling opening

950

780 Suspension position

10

5

840

55

55

55

80 2× 100=200

12-M4 Hole (prepared hole)

85

5

150

2

1

4

40 350

Branch duct connection

A

∗1500mm or more Required space ∗1500mm or more

∗1500mm or more

∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more.

1000 or more Required space

30

8

260 270 315

165

95 110

295

For fresh air intake kit connection (direct installation type)

view

55

840

125 150 240

750 10

B B

200

Adjustable (0~550)

420

3

40

230

view

240

Suspension bolt 4-M8~M10

160

7 A

Description

Name Number 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection

Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.

2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

5 6 7 8

φ6.4 flare φ12.7 flare VP25

Remote control code and control wiring connection

Air discharge grille Air suction grille Port for water supply Corner decoration cover

9 10 Drain hose

O.D.32

C : 3D012310B

FHC50K + BYC125K-W1 FHC60K + BYC125K-W1 Unit (mm)

C

950

2× 100=200 85

80

860~890 Ceiling opening 300 or less 680 Suspension position

(165)

Note3.

420

9 10

6

Branch duct connection

C view 60

4-M4 Hole (prepared hole) φ7

80

5

80

950

780 Suspension position 860~890 Ceiling opening

40 350

840

55

12-M4 Hole (prepared hole)

8

5

260 270 315

4

1

2

40 350

Branch duct connection

A

165 1000 or more Required space

125 150 240 240

For fresh air intake kit connection (direct installation type)

55

2×100=200 85

95 110

80

150

750 Adjustable (0~550)

55

840 295

200

230

B view

55

30 Suspension bolt 4-M8~M10

B

3

40

10

420

160

7 A view

∗1500mm or more Required space 1500mm or more

∗1500mm or more

∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more. Name Number 1 Liquid pipe connection Gas pipe connection 2 Drain pipe connection 3 Power supply connection 4

Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.

5

Remote control code and control wiring connection

6

2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

9 10

Air discharge grille Air suction grille Port for water supply Corner decoration cover

7 8

Drain hose

Description φ6.4 flare φ15.9 flare VP25

O.D.32

C : 3D012311B

SkyAir LU Series – Cooling Only –

27


Dimensions and Service Space

ED21-301

FHYC71K + BYC125K-W1

1000 or more

Unit (mm)

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

C : 3D012312C

FHYC100K + BYC125K-W1 FHYC125K + BYC125K-W1 FHYC140K + BYC125K-W1 Unit (mm)

C

(195)

950

2× 100=200 85

80

860~890 Ceiling opening 300 or less 680 Suspension position

Note3.

165

6

40 350

Branch duct connection

C view

4-M4 Hole (prepared hole) φ7 5

60 80 80

950

780 Suspension position 860~890 Ceiling opening

10

155

420

9

160

7 A view

420

B

5

260 270 315

4

1

14-M4 Hole (prepared hole)

2× 100=200 85

2

40 350

Branch duct connection

A

28

195

150

125 150 298 240

8

55

840 80

200

30 Suspension bolt 4-M8~M10

55

40 50 155 165

55

840 295

1000 or more Required space

55

40

10

288

750 Adjustable (0~550)

B view

3

Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.

2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

For fresh air intake kit connection (direct installation type)

∗1500mm or more Required space ∗1500mm or more

∗1500mm or more

∗1500mm or more ∗ When the discharge grill is closeout, the required is space 200mm or more. Number Name 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection 5 6 7 8 9 10

Description φ9.5 flare φ19.1 flare VP25

Remote control code and control wiring connection

Air discharge grille Air suction grille Port for water supply Corner decoration cover Drain hose

O.D.32

C : 3D012313C

SkyAir LU Series – Cooling Only –


ED21-301

5.1.2

Dimensions and Service Space

FH(Y)C with High Efficiency Filter

1

KAFP556D80·557D80 for FH(Y)C35~71K

Unit (mm)

290

Note:When other optional kit is installed, refer to the installation drawing of its optional kit.

6 5 4 3 2 1 Number

Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975A

KAFP556D160·557D160 for FHYC100~140K

Unit (mm)

Note:When other optional kit is installed, refer to the installation drawing of its optional kit.

6 5 4 3 2 1 Number

Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032976A

SkyAir LU Series – Cooling Only –

29


Dimensions and Service Space

5.1.3

ED21-301

FH(Y)C with Fresh Air Intake Kit (Without T Joint, Duct Fan)

KDDP55D160 for FH(Y)C35~71K

Unit (mm)

Service Access Panel : 450×450mm or more Refer to Note 2

Refrigerant Piping

Note 4

View

Service Access Panel : 450×450mm or more Refer to Note 2

290

Installation Service Access Panel

Connection Chamber (Right)

Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.

How to connect Chamber 4 Independently(Refer to Note 5,6)

Applicable Models SkyAir

FH(Y)C35~71K

5 4 3 2 1 Number

Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981A

KDDP55D160 for FHYC100~140K

Unit (mm)

Service Access Panel : 450×450mm or more Refer to Note 2

Refrigerant Piping

View

Service Access Panel : 450×450mm or more Refer to Note 2

Note 4

Installation Service Access Panel

Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6)

Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.

30

Applicable Models SkyAir

FHYC100~140K

5 4 3 2 1 Number

Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984A

SkyAir LU Series – Cooling Only –


ED21-301

5.1.4

Dimensions and Service Space

FH(Y)C with Fresh Air Intake Kit (With T Joint, Without Duct Fan)

1

KDDP55D160K for FH(Y)C35~71K

Unit (mm)

Service Access Panel : 450×450mm or more Refer to Note 2

Flexible Duct (Accessory)

Installation Service Access Panel

Service Access Panel : 450×450mm or more Refer to Note 2

Suction Duct (K-KFD9A) Optional (Accessory) T Joint

Plate Band

(Accessory)

290

(Accessory)

Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)

Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.

Applicable Models SkyAir

FH(Y)C35~71K

5 4 3 2 1 Number

Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032987A

KDDP55D160K for FHYC100~140K Service Access Panel : 450×450mm or more Refer to Note 2

Installation Service Access Panel

Unit (mm) Flexible Duct (Accessory)

Service Access Panel : 450×450mm or more Refer to Note 2 Plate Band (Accessory)

T Joint (Accessory)

Suction Duct (K-KFD9A) Optional (Accessory)

Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)

Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.

SkyAir LU Series – Cooling Only –

Applicable Models SkyAir

FHYC100~140K

5 4 3 2 1 Number

Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032990A

31


Dimensions and Service Space

5.1.5

ED21-301

FH(Y)C with Panel Spacer

KDBJ55K160W for FH(Y)C35~71K Unit (mm)

3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name

Note:When other optional kit is installed, refer to the installation drawing of its optional kit

Thickness of panel spacer

Dimension between the bottom surface of box and the surface of ceiling

View

Description J : 3D005390E

KDBJ55K160W for FHYC100~140K Unit (mm)

Note:When other optional kit is installed, refer to the installation drawing of its optional kit

3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name

Thickness of panel spacer

Dimension between the bottom surface of box and the surface of ceiling

View

Description J : 3D005391D

32

SkyAir LU Series – Cooling Only –


ED21-301

5.1.6

Dimensions and Service Space

FH(Y)K (Ceiling Mounted Cassette Corner Type)

1

FHK35F + BYK45FJW1 FHK45F + BYK45FJW1 Unit (mm) Model

B

FHK35F

FHK45F

6.4

6.4

12.7

15.9

B

3D027409

FHK60F + BYK71FJW1 FHYK71FJ + BYK71FJW1 Unit (mm) Model

FHK60F

FHYK71FJ

6.4

9.5

B

15.9

15.9

B

3D027408

SkyAir LU Series – Cooling Only –

33


Dimensions and Service Space

5.1.7

ED21-301

FH(Y)B (Ceiling Mounted Built-in Type)

FHB35F + BYBS45DJW1 Without Canvas Duct FHB45F + BYBS45DJW1

60

57

485

A

3

5 Model 195 B

2

6

FH(Y)B35F

FH(Y)B45F

12.7

15.9

350 or more (Required space)

67 150 200

300 245 215 150 135 10

3×150=450

440 315

1

D

45

C

Suspension bolt

135 120

50 65

∗ The required ceiling depth varies according to configuration of specific system

2×65=130

460

8

Unit (mm)

800 595 (Air suction panel center)

25 700

4

300 or more 45

Service space

12-φ7

46

460 Suction air intake position when installing the duct

650

150 215 245 150 250 300

500

228

160

462 (Ceiling opening)

628

3×150=450 485

4×150=600

760 (Ceiling opening)

700

14-M5 Hole

800

D View

B View 160 P. C. D φ125 (Knockout hole)

600 Fresh air intake Position

100

630 (Suspension position) 145

6×65=390

Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.

6-M5 Hole (Circumference liner)

7

1. Liquid pipe connection φ6.4Flare 2. Gas pipe connection Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange

C View

750 (Suspension position) A View

JC : DU224-247

FHB35F + BYBS45DJW1 With Canvas Duct FHB45F + BYBS45DJW1 60 50

25

135 120

2×65=130

67 150 200

2

45

46

6

300 or more

4

5

B

FH(Y)B35F

Suction air intake position when instaling the duct.

150 250 300

228

500

160

628 462 (Ceiling opening)

15.9

12.7 460

650

3×150=450 485

4×150=600 700

760 (Ceiling opening)

D View

14-M5 hole

800

B View 160 P. C. D

6×65=390

φ125 (Knockout hole)

600 Fresh air intake position

Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.

100

630 (Suspension position) 145

FH(Y)B45F

12-φ7

Service space

10

Model

150 215 245

A

3

195

440 315

1

∗ The required ceiling depth varies according to configuration of specific system

465 or more Required installation space

Suspension bolt

57

Unit (mm)

800 595 (Air suction panel center)

D

45 115~255

C

300 245 215 150 135

8

700 485 460 3×150=450 65

6-M5 hole (Circumference liner)

7 750 (Suspension position)

A

C

View

1. Liquid pipe connection φ6.4 Flare 2. Gas pipe connection Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange

View

JC : DU224-248

34

SkyAir LU Series – Cooling Only –


ED21-301

Dimensions and Service Space

1

FHB60F + BYBS71DJW1 Without Canvas Duct FHYB71F + BYBS71DJW1 Unit (mm)

A

45

(Reqjired space)

195

350 or more

FHYB71F

6.4

9.5 16-φ7 760

4

6

2

B

FH(Y)B60F

46

150 215 245

57

Model

135 120

150 200

D

300 or more Survice space

5

3

Suction air intake position when installing the duct 5×150=750 785

View

150 250 300

D

160

500

462 (Ceiling opening)

950 927

228

10

5×150=750 785

440 315

1 2×65=130

Suspension bolt

45

C

60 50

67

1000 760 65

300 245 215 150 135

8

∗ The required ceiling depth varies according to configuration of specific system

800 595 (Air suction panel center)

25

1060 (Ceiling opening)

6×150=900

Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.

1000

1100 18-M5 Hole

B

View

160 P. C. D

11×65=715

600 fresh air intake position

1. Liquid pipe connection Flare 2. Gas pipe connection φ15.9 Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange

100

630 (Suspension position) 145

φ125 (Knockout hole)

6-M5 Hole (Circumference Liner)

C

7

View

1050 (Suspension position)

A

JC : DU226-256

View

FHB60F + BYBS71DJW1 With Canvas Duct FHYB71F + BYBS71DJW1 60 50

25

135 120

D

5

Model 195

3

1 2×65=130

150 200

300 245 215 150 135 45 115~255

B 57

45

2

A

46

6

300 or more

4

FH(Y)B60F

FHYB71F

6.4

9.5

16-φ7 760

10

Service space

950

Suction air intake position when instaling the duct.

1000 18-M5 hole

1100

B 160 P. C. D φ125 (Knockout hole)

View

Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.

1. Liquid pipe connection Flare 2. Gas pipe connection φ15.9Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange

6-M5 hole (Circumference liner)

7

SkyAir LU Series – Cooling Only –

View

600 Fresh air intake position

100

630 (Suspension position) 145

11×65=715

View

D

6×150=900

1060 (Ceiling opening)

A

5×150=750 785

150 250 300

160

228

500

462 (Ceiling opening)

927

1050 (Suspension position)

150 215 245

C

315 Suspension bolt

67

65

∗ The required ceiling depth varies according to configuration of specific system

440

760 5×150=750

8

Unit (mm)

800 595 (Air suction panel center)

465 or more Required installation space

1000 785

C

View

JC : DU226-257

35


Dimensions and Service Space

ED21-301

FHYB100F + BYBS125DJW1 Without Canvas Duct FHYB125F + BYBS125DJW1 Unit (mm)

57

5

A

45

7×150=1050 1185

4

6

2

300 or more Survice space

B

150 215 245

D

20-φ7 1160

(Reqjired space)

3

195

67

150 200

300 245 215 150 135 10

7×150=1050 1185

440 315

1

45

C

Suspension bolt 4-M8~M10

135 120

60 50

2×65=130

1400 1160 65

8

∗ The required ceiling depth varies according to configuration of specific system

800 595 (Air suction panel center)

350 or more

25

D

46

View

462 (Ceiling opening)

Suction air intake position when instaling the duct.

150 250 300

228

160

500

1328

1460 (Ceiling opening)

9×150=1350

1500

Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.

1400 24-M5 hole

B

View

160 P. C. D

16×65=1040

600 fresh air intake

1. Liquid pipe connection φ9.5 Flare 2. Gas pipe connection φ19.1 Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange

100

630 (Suspension position) 145

φ125 (Knockout hole)

6-M5 Hole (Circumference Liner)

C

7

View

1450 (Suspension position)

A

View

FHYB100F + BYBS125DJW1 With Canvas Duct FHYB125F + BYBS125DJW1 25

3

1

20-φ7

45 115~255

B 57

2

A

45

46

6

300 or more

4

1160

465 or more Required installation space

D

5 135 120

150 200

300 245 215 150 135

C

315 Suspension bolt 4-M8~M10 67

65

∗ The required ceiling depth varies according to configuration of specific system

440

2×65=130

8

Unit (mm)

800 595 (Air suction panel center)

150 215 245

60 50

1160 7×150=1050

195

1400 1185

7×150=1050 1185

10

Service space Suction air intake position when instaling the duct.

D

View

9×150=1350 1400

1460 (Ceiling opening)

24-M5 hole

1500

B 160 P. C. D φ125 (Knockout hole)

View

1. Liquid pipe connection φ9.5 Flare 2. Gas pipe connection φ19.1 Flare 3. Drain pipe connection VP25 4. Wire intake for remote control cord 5. Wire intake 6. Drain hole VP25 7. Air filter 8. Air discharge Flange

6-M5 hole (Circumference)

7 1450 (Suspension position)

A

Note; 1. Location of unit's Name Plate:Fan housing surface inside of filter. 2. When installing an optional accessory, refer to the Option Handbook.

600 Fresh air intake position

100

630 (Suspension position) 145

16×65=1040

36

150 250 300

160

228

500

462 (Ceiling opening)

1328

C

View

View

SkyAir LU Series – Cooling Only –


ED21-301

5.1.8

Dimensions and Service Space

FUY (New Ceiling Suspended Cassette Type)

1

FUY71FJ Unit (mm)

3D013860A

FUY100FJ FUY125FJ Unit (mm)

3D013859A

SkyAir LU Series – Cooling Only –

37


Dimensions and Service Space

5.1.9

ED21-301

FH(Y) (Ceiling Suspended Type)

FH35B FH50B Unit (mm)

A

Model

FH(Y)35B FH(Y)50B

A

12.7

15.9

3D027536C 3D028600

FH60B FHY71B Unit (mm)

A

38

Model

FH(Y)60B

FHY71B

A

6.4

9.5

3D027537 3D027538B

SkyAir LU Series – Cooling Only –


ED21-301

Dimensions and Service Space

1

FHY100B Unit (mm)

3D027539B

FHY125B Unit (mm)

3D027540

SkyAir LU Series – Cooling Only –

39


Dimensions and Service Space

ED21-301

5.1.10 FAY (Wall Mounted Type) FAY71L Unit (mm)

3D038540A

FAY100FA Unit (mm)

3D014381A

40

SkyAir LU Series – Cooling Only –


ED21-301

Dimensions and Service Space

5.1.11 FVY (Floor Standing Type)

1

FVY71LA Unit (mm)

3D031617

FVY100LA FVY125LA Unit (mm)

3D031618

SkyAir LU Series – Cooling Only –

41


Dimensions and Service Space

5.2

ED21-301

Remote Controller

BRC7C613W (Wireless Type for FH(Y)C~K)

3D005912B

BRC7C529W (Wireless Type for FUY~FJ)

3D014035

42

SkyAir LU Series – Cooling Only –


ED21-301

Dimensions and Service Space

1

BRC7E619 (Wireless Type for FAY71L)

FAY71

C : 3D034905

BRC7C611W (Wireless Type for FAY100FA)

3D010766A

SkyAir LU Series – Cooling Only –

43


Dimensions and Service Space

ED21-301

BRC7E66 (Wireless Type for FH(Y)~B)

3D028963

BRC1C61 (Wired Type)

More comfortable operation by thermo sensor in the Remote Controller Applicable Model FH(Y)K-F(J) FH(Y)-B FH(Y)C-K FH(Y)B-F FUY-FJ FV(Y)-LA (Available for 2 remote control use) FAY-FA/L

C : 3D028952

44

SkyAir LU Series – Cooling Only –


ED21-301

5.3

Dimensions and Service Space

Outdoor Unit

1

R35G Unit (mm)

3D006245C

R50G / R50GA Unit (mm)

3D004855D

SkyAir LU Series – Cooling Only –

45


Dimensions and Service Space

ED21-301

R60G / R60GA Unit (mm)

3D004856E

R71LU Unit (mm)

3D039213

46

SkyAir LU Series – Cooling Only –


ED21-301

Dimensions and Service Space

1

R100LU Unit (mm)

3D039214

R125LU Unit (mm)

3D039215

SkyAir LU Series – Cooling Only –

47


Dimensions and Service Space

ED21-301

R140LU Unit (mm)

3D039216

48

SkyAir LU Series – Cooling Only –


ED21-301

5.4

Dimensions and Service Space

Installation Service Space for R71LU, 100LU, 125LU, 140LU

1

140 140

3D039172-1

SkyAir LU Series – Cooling Only –

49


Dimensions and Service Space

ED21-301

3D039172-2

50

SkyAir LU Series – Cooling Only –


ED21-301

Piping Diagrams

6. Piping Diagrams 6.1

1

Indoor Unit + Outdoor Unit

R35G R50G / R50GA R60G / R60GA

R71LU

3D039739

SkyAir LU Series – Cooling Only –

51


Piping Diagrams

ED21-301

R100LU

3D039740

R125LU

3D039741

52

SkyAir LU Series – Cooling Only –


ED21-301

Piping Diagrams

1

R140LU

3D039742

SkyAir LU Series – Cooling Only –

53


Wiring Diagrams

ED21-301

7. Wiring Diagrams 7.1

Indoor Unit

FHC35KVE FHC50KVE FHC60KVE

3D005749B

54

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

1

FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE

3D005668C

SkyAir LU Series – Cooling Only –

55


Wiring Diagrams

ED21-301

FHK35FV1 FHK45FV1 FHK60FV1

DU423-5176B

56

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

1

FHYK71FJV1

DU423-5174A

SkyAir LU Series – Cooling Only –

57


Wiring Diagrams

ED21-301

FHB35FV1 FHB45FV1 FHB60FV1

DU423-5175B

58

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

1

FHYB71FV1

DU423-5173C

SkyAir LU Series – Cooling Only –

59


Wiring Diagrams

ED21-301

FHYB100FV1 FHYB125FV1

DU428-5353C

60

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

1

FUY71FJV1 FUY100FJV1 FUY125FJV1

3D013404B

SkyAir LU Series – Cooling Only –

61


Wiring Diagrams

ED21-301

FH35BVE FH50BVE FH60BVE

3D027501

62

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

1

FHY71BVE FHY100BVE FHY125BVE

3D027502

SkyAir LU Series – Cooling Only –

63


Wiring Diagrams

ED21-301

FAY71LVE

3D037717B

64

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

1

FAY100FAVE

DU427-5410E

SkyAir LU Series – Cooling Only –

65


Wiring Diagrams

ED21-301

FVY71LAVE FVY100LAVE FVY125LAVE

3D013540B

66

SkyAir LU Series – Cooling Only –


ED21-301

7.2

Outdoor Units

7.2.1

50Hz

Wiring Diagrams

1

R35GV1 / R35GV1A

R50GV1 / R50GV1A

3D005285A

SkyAir LU Series – Cooling Only –

67


Wiring Diagrams

ED21-301

R50GAV1A

3D028077

R60GV1 / R60GV1A

3D004030A

68

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

1

R60GAV1A

3D028078

R71LUV1 R100LUV1

3D037640C

SkyAir LU Series – Cooling Only –

69


Wiring Diagrams

ED21-301

R71LUY1 R100LUY1

3D037642C

R125LUY1 R140LUY1

3D037644C

70

SkyAir LU Series – Cooling Only –


ED21-301

7.2.2

Wiring Diagrams

60Hz

1

R50GVAL

3D005285A

R60GVAL

SkyAir LU Series – Cooling Only –

71


Wiring Diagrams

ED21-301

R71LUVAL R100LUVAL

3D037935C

R125LUTAL R140LUTAL

3D037936C

72

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

1

R125LUYAL R140LUYAL

3D037937C

SkyAir LU Series – Cooling Only –

73


Capacity Tables

ED21-301

8. Capacity Tables 8.1

50Hz (General)

FHC35KVE + R35GV1

0.02

C: 3D006618

FHK35FV1 / FHB35FV1 / FH35BVE + R35GV1

3D006627B

74

SkyAir LU Series – Cooling Only –


ED21-301

Capacity Tables

1

FHC50KVE + R50GV1

0.02

C: 3D006616

FHK45FV1 / FHB45FV1 / FH50BVE + R50GV1

3D006621B

SkyAir LU Series – Cooling Only –

75


Capacity Tables

ED21-301

FHC60KVE + R60GV1

0.02

C: 3D006615

FHK60FV1 / FHB60FV1 / FH60BVE + R60GV1

3D006625C

76

SkyAir LU Series – Cooling Only –


ED21-301

Capacity Tables

1

FHYC71KVE / FHYK71FJV1 / FHYB71FV1 / FUY71FJV1 / FHY71BVE / FAY71LVE / FVY71LAVE + R71LUV1 FHYC71KVE / FHYK71FJV1 / FHYB71FV1 / FUY71FJV1 / FHY71BVE / FAY71LVE / FVY71LAVE + R71LUY1

3D039613A

FHYC100KVE / FHYB100FV1 / FUY100FJV1 / FHY100BVE / FAY100FAVE / FVY100LAVE + R100LUV1 FHYC100KVE / FHYB100FV1 / FUY100FJV1 / FHY100BVE / FAY100FAVE / FVY100LAVE + R100LUY1

3D039626A

SkyAir LU Series – Cooling Only –

77


Capacity Tables

ED21-301

FHYC125KVE / FHYB125FV1 / FUY125FJV1 / FHY125BVE / FVY125LAVE + R125LUY1

3D039635

FHYC140KVE + R140LUY1

3D039644

78

SkyAir LU Series – Cooling Only –


ED21-301

8.2

Capacity Tables

50Hz (Complied with Australian Standard)

1

FHC35KVE + R35GV1A

C: 3D006618

220V

240V 14

16

220V : 5m 240V : 7.5m

C:3D011149

FHC50KVE + R50GAV1A

C: 3D006616

220V

240V 15 0.18

17 0.18

220V : 5m 240V : 7.5m

C:3D011150

SkyAir LU Series – Cooling Only –

79


Capacity Tables

ED21-301

FH50BVE + R50GAV1A

3D006621B

3D011053B

FHC60KVE + R60GAV1A

C: 3D006615

220V

240V 19

21

220V : 5m 240V : 7.5m

C:3D011151

80

SkyAir LU Series – Cooling Only –


ED21-301

Capacity Tables

1

FH60BVE + R60GAV1A

3D006625C

3D011054B

SkyAir LU Series – Cooling Only –

81


Capacity Tables

8.3

ED21-301

60Hz

FHC50KVE + R50GVAL

C : 3D006814

FH50BVE + R50GVAL

3D006619B

82

SkyAir LU Series – Cooling Only –


ED21-301

Capacity Tables

1

FHC60KVE + R60GVAL

C : 3D006825

FH60BVE + R60GVAL

3D006620B

SkyAir LU Series – Cooling Only –

83


Capacity Tables

ED21-301

FHYC71KVE / FHY71BVE / FAY71LVE / FVY71LAVE + R71LUVAL

3D039615A

FHYC100KVE / FHY100BVE / FAY100FAVE / FVY100LAVE + R100LUVAL

3D039628

84

SkyAir LU Series – Cooling Only –


ED21-301

Capacity Tables

1

FHYC125KVE / FHY125BVE / FVY125LAVE + R125LUYAL

3D039638

FHYC125KVE / FHY125BVE / FVY125LAVE + R125LUTAL

3D039637

SkyAir LU Series – Cooling Only –

85


Capacity Tables

ED21-301

FHYC140KVE + R140LUTAL

3D039648

FHYC140KVE + R140LUYAL

3D039652

86

SkyAir LU Series – Cooling Only –


ED21-301

8.4

Capacity Tables

Capacity Correction Factor by The Length of Refrigerant Piping The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit) All Models for Pair System (Reference Valve) 1. In case of piping length 5m (35~140)

Cooling capacity correction factor

100

95 35·45·50·60 90

85

100 71 125

80 140 75

0

5

10

15 20 25 30 35 Length of refrigerant piping (Total length)

40

45

50 (m) (S0003)

2. In case of piping length 7.5m (71~140)

Cooling capacity correction factor

100

95

90

85

100 71 125

80

140

75

Note:

0

5

7.5 10

20 25 30 35 15 Length of refrigerant piping (Total length)

40

45

50 (m)

1. line: Correction factor for cooling capacity 2. The correction factor remains the same whether the outdoor unit is to be installed above or below the indoor unit. 3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the range of its limitation.

SkyAir LU Series – Cooling Only –

87

1


Operation Limits

ED21-301

9. Operation Limits 9.1

Operation Limits R50GVAL R60GVAL

R35GV1 / R35GV1A R50GV1 / R50G(A)V1A R60GV1 / R60G(A)V1A

4D006229C

R71LUV1 / R71LUY1 / R71LUVAL R100LUV1 / R100LUY1 / R100LUVAL R125LUY1 / R125LUTAL / R125LUYAL R140LUY1 / R140LUTAL / R140LUYAL

3D039657

Notes:

88

The graphs are based on the following conditions. Equivalent piping length 5m Level difference 0m Air flow rate High

SkyAir LU Series – Cooling Only –


ED21-301

Sound Level

10. Sound Level 10.1

1

Overall Sound Level dB(A) 50Hz Model

60Hz

220V

240V

220V

Measuring Location

H

L

H

L

H

L

FHC35K FHC50K FHC60K FHYC71K FHYC100K FHYC125K FHYC140K

33 33 35 35 39 42 44

29 29 30 30 34 36 37

35 35 37 37 41 44 46

31 31 32 32 36 38 39

— 33 35 35 39 42 44

— 29 30 30 34 36 37

FH(Y)C

FHK35F FHK45F FHK60F FHYK71FJ

39 39 41 41

33 34 36 36

41 41 43 43

35 36 38 38

— — — —

— — — —

FHK

FHB35F FHB45F FHB60F FHYB71F FHYB100F FHYB125F

38 39 41 41 41 44

32 34 35 35 35 38

40 41 43 43 43 46

34 36 37 37 37 40

— — — — — —

— — — — — —

FH(Y)B

FUY71FJ FUY100FJ FUY125FJ

40 43 44

35 38 39

42 45 46

37 40 41

— — —

— — —

FUY

FH35B FH50B FH60B FHY71B FHY100B FHY125B

37 38 38 39 42 44

32 33 33 35 37 39

37 38 38 39 42 44

32 33 33 35 37 39

— 38 38 39 42 42

— 33 33 35 37 39

FH(Y)

FAY71L FAY100FA

43 45

37 41

43 45

37 41

43 45

37 41

FAY

FVY71LA FVY100LA FVY125LA

41 46 49

35 40 43

43 48 51

37 42 45

41 46 49

35 40 43

FVY

(S0007)

R35G R50G(A) R60G(A) R71LU R100LU

48 49 54 48 49

49 50 55 49 50

— 52 55 — —

380V

415V

220V

R71LU R100LU R125LU R140LU R125LUTAL R140LUTAL

48 49 49 54 — —

49 50 50 55 — —

49 51 — — 51 55

R125LUYAL R140LUYAL

— —

— —

Microphone

4D028280A

R35~60

R71~140LU

Microphone

380V

Note:

51 55

4D039806

Operation sound is measured in an anechoic chamber.

SkyAir LU Series – Cooling Only –

89


Sound Level

10.2

ED21-301

Octave Band Level

10.2.1 Indoor Units FHC35KVE FHC50KVE

FHC60KVE FHYC71KVE

FHYC100KVE

FHYC140KVE

FHK35FVE

H H

L L

4D006198A

FHYC125KVE

70

NC-60 60

H(240V) NC-50 50

H(220V) NC-40 40 NC-30 30

L(240V) NC-20 20

L(220V)

63

125

250

500

1000

2000

4000

8000

4D013951

FHK45FVE

FHK60FVE FHYK71FJVE

FHB35FVE

FHB45FV1

FHB60FV1 FHYB71FV1

FHYB100FV1

90

SkyAir LU Series – Cooling Only –


ED21-301

Sound Level

FHYB125FV1

FUY71FJV1

FUY100FJV1

4D013827A

FUY125FJV1

FH60BVE

4D028280A

FHY71BVE

4D028282

FHY125BVE

SkyAir LU Series – Cooling Only –

4D028281A

FHY100BVE

4D028355

FAY71LVE

4D028284

4D013828A

FH50BVE

FH35BVE

4D013829A

1

4D028283

FAY100FAVE

4D038512A

4D014379A

91


Sound Level

ED21-301

FVY71LAVE

FVY100LAVE

4D013840B

FVY125LAVE

4D013841A

4D013842B

10.2.2 Outdoor Units (50Hz) R35GV1 / R35GV1A

R50GV1 / R50G(A)V1A

4D000697B

R71LUV1 / R71LUY1

R60GV1 / R60G(A)V1A

DW525-597E

R100LUV1 / R100LUY1

4D039802

DW527-217E

R125LUY1

4D039804

4D039806

R140LUY1

4D039808

92

SkyAir LU Series – Cooling Only –


ED21-301

Sound Level

10.2.3 Outdoor Unit (60Hz) R50GVAL

1

R71LUVAL

R60GVAL

4D039810

R100LUVAL

R140LUTAL /R140LUYAL

R125LUTAL /R125LUYAL

4D039811

4D039812

4D039813

240V, 415V 220V, 380V Notes:

1. Dotted line shows the case of 50Hz. 2. Continuous line shows the case of 60Hz. 3. Only continuous line shows the case of both 50 and 60Hz.

SkyAir LU Series – Cooling Only –

93


Fan Performance

ED21-301

11. Fan Performance 11.1

Fan Performance

11.1.1 Ceiling Mounted Built-In Type FHB35F

FHB45F

FHB60F

FHYB71F

94

SkyAir LU Series – Cooling Only –


ED21-301

Fan Performance

FHYB100F

FHYB125F

Notes:

1

1. The remote controller can be used to switch between “high” and “low”. 2. The air flow is set to “standard” before leaving the factory. It is possible to switch between “standard ESP” and “high ESP” by remote controller. 3. The internal static pressure indicates the characteristics of the fan when a suction panel (optional accessory) and a canvas for the suction panel (optional accessory) are incorporated into the main unit (with a long-life filter).

SkyAir LU Series – Cooling Only –

95


Electric Characteristics

ED21-301

12. Electric Characteristics 12.1

50Hz Unit combination Indoor

Outdoor

Power supply Hz-Volts

50-220 FHC35KVE R35GV1(A) 50-230 50-240 50-220 50-230 FHK35FV1 R35GV1 50-240 50-220 50-230 FHB35FV1 R35GV1 50-240 50-220 50-230 FH35BVE R35GV1 50-240 50-220 FHC50KVE R50G(A)V1(A) 50-230 50-240 50-220 50-230 FHK45FV1 R50GV1 50-240 50-220 50-230 FHB45FV1 R50GV1 50-240 50-220 50-230 FH50BVE R50GV1 50-240 50-220 FH50BVE R50GAV1A 50-230 50-240 50-220 FHC60KVE R60G(A)V1(A) 50-230 50-240 50-220 50-230 FHK60FV1 R60GV1 50-240 50-220 50-230 FHB60FV1 R60GV1 50-240 50-220 50-230 FH60BVE R60GV1 50-240 50-220 FH60BVE R60GAV1A 50-230 50-240 50-220 50-230 FHYC71KVE R71LUV1 50-240 50-220 50-230 FHY71BVE R71LUV1 50-240 50-220 50-230 FHYB71FV1 R71LUV1 50-240 50-220 50-230 FHYK71FJV1 R71LUV1 50-240 50-220 50-230 FVY71LAVE R71LUV1 50-240 50-220 50-230 R71LUV1 FAY71LVE 50-240 50-220 50-230 FUY71FJV1 R71LUV1 50-240 50-380/220 50-400/230 FHYC71KVE R71LUY1 50-415/240 50-380/220 50-400/230 FHY71BVE R71LUY1 50-415/240 50-380/220 FHYB71FV1 R71LUY1 50-400/230 50-415/240 50-380/220 FHYK71FJV1 R71LUY1 50-400/230 50-415/240 50-380/220 50-400/230 FVY71LAVE R71LUY1 50-415/240 50-380/220 50-400/230 R71LUY1 FAY71LVE 50-415/240 50-380/220 50-400/230 FUY71FJV1 R71LUY1 50-415/240

Voltage range

Max. 50Hz 264V Min. 50Hz 198V

Max. 50Hz 264V Min. 50Hz 198V

Max. 50Hz 264V Min. 50Hz 198V

Max. 50Hz 264V Min. 50Hz 198V

Max. 50Hz 456/264V Min. 50Hz 342/198V

Comp

MCA TOCA MFA 6.9

15

7.6

15

7.9

15

8.0

15

13.5

20

11.9

20

12.4

20

12.3

20

13.5

20

14.5

25

16.3

25

16.4

25

16.3

25

14.5

25

18.3

23.2

30

20.9

23.8

30

19.3

23.5

30

18.6

23.1

30

19.1

23.3

30

18.3

23.0

30

18.5

23.2

30

7.5

8.7

15

7.7

8.7

15

7.9

9.0

15

7.5

8.6

15

7.8

8.8

15

7.3

8.5

15

7.5

8.7

15

LRA 29 30 31 29 30 31 29 30 31 29 30 31 42 44 46 42 44 46 42 44 46 42 44 46 42 44 46 55 58 60 55 58 60 55 58 60 55 58 60 55 58 60 82 78 75 82 78 75 82 78 75 82 78 75 82 78 75 82 78 75 82 78 75 40 38 37 40 38 37 40 38 37 40 38 37 40 38 37 40 38 37 40 38 37

RLA 4.6 4.7 4.7 5.3 5.5 5.6 5.3 5.5 5.6 5.3 5.5 5.6 9.2 9.7 10.1 9.0 9.1 9.1 9.0 9.1 9.1 9.0 9.1 9.1 9.2 9.7 10.1 10.6 10.5 10.3 11.9 12.0 12.1 11.9 12.0 12.1 11.9 12.0 12.1 10.6 10.5 10.3 13.7 13.1 12.6 14.2 13.6 13.0 14.2 13.5 13.0 14.0 13.4 12.9 14.2 13.6 13.0 13.8 13.2 12.6 13.8 13.2 12.7 5.0 4.8 4.6 5.2 4.9 4.7 5.1 4.9 4.7 5.1 4.8 4.7 5.2 4.9 4.7 5.0 4.8 4.6 5.0 4.8 4.6

OFM

IFM

kW

FLA

kW

FLA

0.027

0.4

0.045

0.6

0.027

0.4

0.025

0.2

0.027

0.4

0.065

0.5

0.027

0.4

0.062

0.6

0.045

0.3

0.045

0.6

0.045

0.3

0.025

0.2

0.045

0.3

0.085

0.7

0.045

0.3

0.062

0.6

0.045

0.3

0.062

0.6

0.053

0.6

0.045

0.6

0.053

0.6

0.06

0.6

0.053

0.6

0.11

0.7

0.053

0.6

0.062

0.6

0.053

0.6

0.062

0.6

0.065

0.6

0.045

0.6

0.065

0.6

0.062

0.6

0.065

0.6

0.125

0.9

0.065

0.6

0.045

0.5

0.065

0.6

0.030

0.7

0.065

0.6

0.068

0.4

0.065

0.6

0.045

0.6

0.065

0.6

0.045

0.6

0.065

0.6

0.062

0.6

0.065

0.6

0.125

0.9

0.065

0.6

0.045

0.5

0.065

0.6

0.030

0.7

0.065

0.6

0.068

0.4

0.065

0.6

0.045

0.6

3D006610D 3D006301A 3D039576C

96

SkyAir LU Series – Cooling Only –


ED21-301

Electric Characteristics

Unit combination Indoor

Outdoor

FHYC100KVE R100LUV1 FHY100BVE

R100LUV1

FHYB100FV1 R100LUV1 FVY100LAVE R100LUV1 FAY100FAVE R100LUV1 FUY100FJV1 R100LUV1 FHYC100KVE R100LUY1 FHY100BVE

R100LUY1

FHYB100FV1 R100LUY1 FVY100LAVE R100LUY1 FAY100FAVE R100LUY1 FUY100FJV1 R100LUY1 FHYC125KVE R125LUY1 FHY125BVE

Power supply

R125LUY1

FHYB125FV1 R125LUY1 FVY125LAVE R125LUY1 FUY125FJV1 R125LUY1 FHYC140KVE R140LUY1

Hz-Volts 50-220 50-230 50-240 50-220 50-230 50-240 50-220 50-230 50-240 50-220 50-230 50-240 50-220 50-230 50-240 50-220 50-230 50-240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240

Comp

Voltage range MCA TOCA MFA 24.7

27.8

40

24.1

27.5

40

24.6

27.8

40

24.7

28.1

40

23.9

27.1

40

24.6

27.8

40

10.2

11.8

15

9.9

11.5

15

Max. 50Hz 456/264V

10.2

11.8

15

Min. 50Hz 342/198V

10.5

12.1

15

9.5

11.1

15

10.2

11.8

15

12.4

15.3

20

12.3

15.0

20

12.5

15.7

20

12.9

15.8

20

12.3

15.3

20

13.0

17.4

25

Max. 50Hz 264V Min. 50Hz 198V

Max. 50Hz 456/264V Min. 50Hz 342/198V

Max. 50Hz 456/264V Min. 50Hz 342/198V

LRA

RLA

114 109 105 114 109 105 114 109 105 114 109 105 114 109 105 114 109 105 50 48 46 50 48 46 50 48 46 50 48 46 50 48 46 50 48 46 51 53 56 51 53 56 51 53 56 51 53 56 51 53 56 67 71 74

18.3 17.5 16.7 18.1 17.3 16.6 18.2 17.4 16.7 18.1 17.3 16.6 18.2 17.4 16.7 18.2 17.4 16.6 6.7 6.4 6.1 6.7 6.3 6.1 6.7 6.4 6.1 6.7 6.3 6.1 6.7 6.4 6.1 6.7 6.3 6.1 8.0 8.0 8.1 8.1 8.1 8.2 7.6 7.7 7.8 8.0 8.0 8.1 7.9 7.9 8.0 8.2 8.2 8.5

OFM

1

IFM

kW

FLA

kW

FLA

0.09

0.8

0.090

1.0

0.09

0.8

0.135

0.7

0.09

0.8

0.135

1.0

0.09

0.8

0.060

1.3

0.09

0.8

0.046

0.3

0.09

0.8

0.090

1.0

0.09

0.8

0.090

1.0

0.09

0.8

0.135

0.7

0.09

0.8

0.135

1.0

0.09

0.8

0.060

1.3

0.09

0.8

0.046

0.3

0.09

0.8

0.090

1.0

0.065 + 0.085 0.065 + 0.085 0.065 + 0.085 0.065 + 0.085 0.065 + 0.085 0.065 + 0.090

0.6 + 0.7 0.6 + 0.7 0.6 + 0.7 0.6 + 0.7 0.6 + 0.7 0.6 + 0.8

0.090

1.0

0.144

0.7

0.225

1.4

0.090

1.5

0.090

1.0

0.090

1.0

3D039577A 3D039578A 3D039579A

SkyAir LU Series – Cooling Only –

97


Electric Characteristics

12.2

ED21-301

60Hz Unit combination Indoor

Outdoor

Power supply Hz-Volts

FHC50KVE

R50GVAL

60-220

FH50BVE

R50GVAL

60-220

FHC60KVE

R60GVAL

60-220

FH60BVE

R60GVAL

60-220

Comp

Voltage range MCA TOCA MFA Max. 60Hz 242V Min. 60Hz 198V

Max. 60Hz 242V Min. 60Hz 198V

OFM

LRA

RLA

IFM

kW

FLA

kW

FLA

13.0

20

42

9.5

0.045

0.4

0.045

0.7

13.0

20

42

9.4

0.045

0.4

0.062

0.7

15.8

25

47

11.6

0.053

0.6

0.045

0.7

15.8

25

47

11.4

0.053

0.6

0.062

0.7

19.5

23.5

30

99

14.4

0.075

0.8

0.045

0.7

22.4

22.0

30

99

15.3

0.075

0.8

0.062

0.7

FHYC71KVE R71LUVAL

60-220

FHY71BVE

R71LUVAL

60-220

FVY71LAVE

R71LUVAL

60-220

20.2

23.6

30

99

14.9

0.075

0.8

0.030

0.8

FAY71LVE

R71LUVAL

60-220

19.5

23.2

30

99

14.6

0.075

0.8

0.068

0.4

FHYC100KVE R100LUVAL

60-220

24.8

27.9

40

143

18.3

0.1

0.9

0.090

1.0

R100LUVAL

60-220

25.5

27.9

40

143

18.9

0.1

0.9

0.135

1.0

FVY100LAVE R100LUVAL

60-220

25.3

28.3

40

143

18.4

0.1

0.9

0.060

1.4

FAY100FAVE R100LUVAL

60-220

24.2

27.3

40

143

18.3

0.1

0.9

0.046

0.4

FHYC125KVE R125LUTAL

60-220

21.6

24.3

30

137

15.1

0.090

1.0

R125LUTAL

60-220

23.2

24.4

30

137

16.3

0.130

1.1

FVY125LAVE R125LUTAL

60-220

22.9

25.0

30

137

15.6

0.090

1.7

FHYC125KVE R125LUYAL

60-380

13.3

15.3

20

66

8.5

0.090

1.0

R125LUYAL

60-380

14.3

15.4

20

66

9.2

0.130

1.1

FVY125LAVE R125LUYAL

60-380

14.4

16.0

20

66

8.8

0.090

1.7

FHYC140KVE R140LUTAL

60-220

Max. 60Hz - 242V 22.5 Min. 60Hz - 198V

30.7

40

146

15.8

0.090

1.0

FHYC140KVE R140LUYAL

60-380

Max. 60Hz 418V Min. 60Hz 342V

17.7

25

75

8.7

0.090

1.0

FHY100BVE

FHY125BVE

FHY125BVE

Max. 60Hz 242V Min. 60Hz 198V

Max. 60Hz 242V Min. 60Hz 198V

Max. 60Hz 242V Min. 60Hz 198V

Max. 60Hz 418V Min. 60Hz 342V

13.6

0.075 + 0.095 0.075 + 0.095 0.075 + 0.095 0.075 + 0.095 0.075 + 0.095 0.075 + 0.095 0.075 + 0.100 0.075 + 0.100

0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9

3D006610D 3D006301A 3D039576C 3D039577A 3D039578A 3D039579A

98

SkyAir LU Series – Cooling Only –


ED21-301

Option List

13. Option List 13.1

1

LU Series

13.1.1 Indoor Unit FH(Y)C–K Name of Option

Remark

Kit Name 35~71K

100~140K

Decoration Panel

BYC125K-W1

Sealing Member of Air Discharge Outlet

KDBHJ55K160

Panel Spacer

KDBJ55K160W

Fresh Air Intake Kit ∗3

Chamber Type

Without T Joint

KDDP55D160

With T Joint

KDDP55D160K

Direct Installation Type High Efficiency Filter Replacement High Efficiency Filter

KDDJ55X160

(Colorimetric Method 65%)

KAFP556D80

KAFP556D160

(Colorimetric Method 90%)

KAFP557D80

KAFP557D160

(Colorimetric Method 65%)

KAFJ552K80

KAFJ552K160

(Colorimetric Method 90%)

KAFJ553K80

KAFJ553K160

High-Efficiency Filter Chamber

KDDFP55D160

Long-Life Filter

KAFJ551K160

Resin Net (Gravimetric Method 50%)

Ultra–Long Life Filter

KAFP55D160

Ultra–Long Life Replacement Filter

KAFJ55K160H

Chamber Connection Kit ∗4

KKSJ55K160

Branch Duct Chamber Remote Controller

KDJ55K80

KDJ55K160

Wired Type ∗2

BRC1C61 (Note. 2)

Wireless Type

BRC7C613W

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302B61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601B51

Adaptor for Wiring (Interlock for Fresh Air Intake Fan) ∗1

KRP1B57

Wiring Adaptor for Electrical Appendices ∗1

KRP4A53

Interface Adaptor for SkyAir Series

DTA102A52

Installation Box for Adaptor PCB

KRP1B98 C : 3D006559E

FH(Y)K–F(J) Name of Option

Remark

Decoration Panel

Kit Name 35·45F

60F·71FJ

BYK45FJW1

BYK71FJW1

Panel Spacer

KPBJ52F56W

KPBJ52F80W

Air Discharge Blind Panel

KDBJ52F56W

KDBJ52F80W

Replacement Long-Life Filter Resin Net

KAFJ521F56

KAFJ521F80

Discharge Grille

K–HV7AW

K–HV9AW

Flexible Duct with Shutter

KFDJ52F56

KFDJ52F80

Remote Controller

Wired Type ∗2

BRC1C61(Note. 2)

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302B61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601B51

Adaptor for Wiring (Interlock for Fresh Air Intake Fan)

KRP1B51

Wiring Adaptor for Electrical Appendices

KRP4A51

Interface Adaptor for SkyAir Series

DTA102A52 DU423-9100C

Note:

1. 2. 3. 4. 5.

∗1 : Installation box for adaptor PCB(KRP1B98) is necessary. BRC1B61 is also available. ∗2 : Wire for Remote Controller : Field Supplied. ∗3 : Refer to the Option handbook for the detail. ∗4 : When using the filter (High–Efficiency Filter or Ultra–Long Life Filter) and the Fresh Air Intake Kit together, this kit is necessary.

SkyAir LU Series – Cooling Only –

99


Option List

ED21-301

FH(Y)B–F Name of Option

Remark

Decoration Panel Service Access Panel

Kit Name 35·45F

60·71F

BYBS45DJW1

BYBS71DJW1

100F

BYBS125DJW1

125F

KTBJ25K56W

KTBJ25K80W

KTBJ25K160W

(Colorimetric method 65%)

KAFJ252L56

KAFJ252L80

KAFJ252L160

(Colorimetric method 90%)

KAFJ253L56

KAFJ253L80

KAFJ253L160

Resin Net

KAFJ251K56

KAFJ251K80

KAFJ251K160

Filter Chamber for Bottom Suction

KAJ25L56D

KAJ25L80D

KAJ25L160D

Filter Chamber for Rear Suction

KAJ25L56B

KAJ25L80B

KAJ25L160B

Canvas Duct

KSAJ25K56

KSAJ25K80

KSAJ25K160

(φ150)

K-DG4BW

K-DG5BW

K-DG4BW

K-DG5BW

(φ200)

K-DG7BW

K-DG9BW

K-DG7BW

K-DG9BW

(φ150)

K-DGC4B

K-DGC5B

K-DGC4B

K-DGC5B

(φ200)

K-DGC7B

K-DGC9B

K-DGC7B

K-DGC9B

High-Efficiency Filter Replacement LongLife Filter

Discharge Grille Discharge Chamber Branch Duct

φ200 → φ150

K-DDV20A

(φ150)

(1m)K-FDK151B, (2m)K-FDK152B, (3m)K-FDK153B, (4m)K-FDK154B, (5m)K-FDK155B, (6m)K-FDK156B

(φ200)

(1m)K-FDK201B, (2m)K-FDK202B, (3m)K-FDK203B, (4m)K-FDK204B, (5m)K-FDK205B, (6m)K-FDK206B

Flexible Duct Blind Board

KBBJ25K56

KBBJ25K80

KBBJ25K160

Adaptor For Discharge

KDAJ25K56

KDAJ25K71

KDAJ25K140

Flange For Suction

KDJ2507K56

KDJ2507K80

KDJ2507K160

Remote Controller

Wired Type ∗2

BRC1C61 (Note. 2)

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302B61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601B51

Adaptor for Wiring (Interlock for Fresh Air Intake Fan)

KRP1B54

Wiring Adaptor for Electrical Appendices ∗1

KRP4A51

Interface Adaptor for SkyAir Series

DTA102A52 DU423-999B

FUY–FJ Name of Option

Remark

Kit Name 71FJ

KDBHJ49F140

Decoration Panel for Air Discharge

KDBTJ49F80

KDBTJ49F140

Vertical Flap Kit

KDGJ49F80

KDGJ49F140

L Connection Piping Kit Remote Controller

KAFJ495F140 KHFJ49F80

KHFJ49F140

Wired Type ∗2

BRC1C61 (Note. 3)

Wireless Type

BRC7C529W

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302B61

Unified On/Off Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601B51

Wiring Adaptor for Electrical Appendices ∗1 Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB

100

125FJ

KDBHJ49F80

Replacement Long-Life Filter

Note:

100FJ

Sealing Member of Air Discharge Outlet ∗3

1. 2. 3. 4. 5.

∗1 : Installation box for adaptor PCB(KRP1B97) is necessary.

KRP4A53 DTA102A52 KRP1B97 3D013861B

BRC1B62 is also available. BRC1B61 is also available. ∗2 : Wire for Remote Controller : Field Supplied. ∗3 : This option is necessary for setting up 2-way (opposing directional) air flow when the air conditioner is installed.

SkyAir LU Series – Cooling Only –


ED21-301

Option List

1

FH(Y)–B Name of Option

Kit Name

Remark

35B

50B

60B

71B

100B

125B

Replacement Long-Life Filter

KAFJ501D56

KAFJ501D80

KAFJ501D112 KAFJ501D160

Drain Pump Kit

KDU50B50VE

KDU50B71VE

KDU50B125VE

L-Type Piping Kit (For Upward Direction) Remote Controller

KHFJ5F50

KHFJ5F60

KHFJ5F80

Wired Type ∗3

KHFJ5F160

BRC1C61

Wireless Type

BRC7E66

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302B61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601B51

Adaptor for Wiring

KRP1B54

Wiring Adaptor for Electrical Appendices ∗1

KRP4A52

Interface Adaptor for SkyAir Series

DTA102A52

Installation Box Adaptor PCB

KRP1C93 3D028285A

FAY–L/FA Name of Option

Remark

Drain Pump Kit Remote Controller

Kit Name 71L

100FA

K-KDU572BVE

Wired Type ∗3 Wireless Type

BRC1C61 (Note. 5) BRC7E619

Set Back Time Clock

BRC7C611W

BRC15A61

Central Remote Controller

DCS302B61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601B51

Wiring Adaptor for Electrical Appendices Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB

KRP4A51 ∗4

KRP4A51

DTA102A52

KRP4A93

3D039142C C : DU427-965E

FVY–LA Name of Option

Remark

Replacement Long Life Filter

KAFJ95L160

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302B61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

Remote Controller for 2 Remote Control System intelligent Touch Controller Adaptor for Wiring ∗2 Group Control Adaptor ∗2 Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB

Note:

Kit Name 71~125LA

1. 2. 3. 4. 5.

∗1 : Installation box for adaptor PCB (KRP1C93) is necessary. ∗2 : Installation box for adaptor PCB (KRP4A95) is necessary. ∗3 : Wire for Remote Controller : Field Supplied. ∗4 : Installation box for adaptor PCB (KRP4A93) is necessary.

BRC1C61 DCS601B51 KRP1B57 KRP4A52 DTA102A52 KRP4A95 4D013855A

BRC1B61 is also available.

SkyAir LU Series – Cooling Only –

101


Option List

ED21-301

13.1.2 Outdoor Unit [R35~60G(A)] Kit Name

Name of Option

R35~60G(A)

Drain Piping Kit

KIS95 C : 3D005955A

13.1.3 Outdoor Unit [R71~140LU] Name of Option

Kit Name R71LU

Central Drain Plug Year-Round Cooling Kit

R100LU

R125LU

R140LU

KKPJ5F180 KRK5F80V1

KRK5F140V1

KRK5F160V1 3D039655

102

SkyAir LU Series – Cooling Only –


ED21-301

Field Piping and Wiring

14. Field Piping and Wiring 14.1

1

Field piping

14.1.1 Maximum Allowable Piping Length and Level Difference

R35G

R50, 60G(A)

Max. Allowable Piping Length

25 m

30 m

R71~140LU 50 m(Equivalent Length 70 m)

Max.Allowable Level Difference

15 m

15 m

30 m

14.1.2 Additional Refrigerant Charge Select the appropriate refrigerant charging amount from Table 1, 2 and charge the refrigerant. Fill out the notice plate attached in the rear of the front plate (2) for future servicing. R35G, 50 · 60G(A) This unit requires additional charging of refrigerant according to the length of pipe connected at the site. <Unit : g>

Table 1 Additional Charge

R35G, 50G(A)

R60G(A)

20 g/m (Exceeding 10 m)

20 g/m (Exceeding 5 m)

R71~140LU This unit requires additional charging of refrigerant according to the length of pipe connected at the site. When the entire refrigerant pipe length is within 30 meters, the additional changing is not needed. Take the following steps for proper charging. When Connected to one Indoor Unit (pair system)

Main pipe (L1)

Indoor unit One-way length of pipe (L): L1

1. Refrigerant charge amount Additional charging of refrigerant Select the amount of refrigerant which matches a length which exceeds the charge-less length, and add it. Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear surface of the front plate, as this is necessary for after-sales service.

FOR PAIR SYSTEM Table 1 The maximum allowable pipe length is 50 meters. Pipe excess length over 30 meters Additional Charging Amount

<unit : kg>

10m or less

20m or less

0.25

0.50

2. Recharging refrigerant When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the amount mentioned on the nameplate, and when the pipe length exceeds 30 meters, the charging amount is an addition of the amount stated on the nameplate and the additional charging amount. 1PN05248B-1

SkyAir LU Series – Cooling Only –

103


Field Piping and Wiring

ED21-301

14.1.3 Pump down operation method The outdoor unit is equipped with a low-pressure switch to protect the compressor. Take the following steps to perform the pumping-down operation. Never short-circuit the low-pressure switch in this operation. Procedure

Precautions

1. Start the fan operation with the remote controller.

Confirm that stop valves both on the liquid and gas side are open. Take care when the procedure 2 is done first because the indoor unit fan may operate automatically.

2. Push the pumping-down button on the PC board of the outdoor unit.

Compressor and outdoor fan will start operation automatically.

3. Continue operation for 1 min. until operation condition stabilizes.

4. Close the stop valve on the liquid side securely. (Refer to Fig. 1)

Insecure closing of the valve may result in burning of the compressor.

5. When the low-pressure switch is activated, the unit stops working. At this time, close the stop valve on the gas side.

This is the end of pumping-down operation. After pumping-down operation, the remote controller shows “U4” even when ON button on the remote controller is pressed, and it will not operate. Although the remote controller may or may not indicate “U4” according to circumstances at this time, it is normal. When the remote controller indicates “U4”, the indoor unit fan may operate (for about max 30 minutes). Turn off the main power supply switch and turn it on again in need of operation. 1. In case of G(A), KU Type

2. In case of LU Type How to use the stop valve (Refer to Fig. 2) Have a hex wrench ready. (4 mm and 6 mm) 1. Open the valve. a. Place the hex wrench on the valve bar and turn counter-clockwise. b. Stop when the valve bar no longer turns. It is now open. 2. Close the valve. a. Place the hex wrench on the valve bar and turn clockwise. b. Stop when the valve bar no longer turns. It is now closed. (Gas side) Opening direction (Liquid side) Opening direction

Fig. 2

104

1PN05248B-2

SkyAir LU Series – Cooling Only –


ED21-301

Field Piping and Wiring

Necessity of a trap Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases of deterioration of oil return, it will be necessary to provide a trap at an appropriate place in the riser gas piping. Trap installation spacing Indoor unit Oil trap

Gas piping

H 15m

Liquid piping

H Marks. Install trap at each difference in height 15m Outdoor unit

Note:

A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit. Caution to be taken when brazing refrigerant piping “Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”. (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible. (Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g . BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant leakage.

SkyAir LU Series – Cooling Only –

105

1


Field Piping and Wiring

14.2

106

ED21-301

Field Wiring

SkyAir LU Series – Cooling Only –


ED21-301

SkyAir LU Series (Twin, Triple, Double Twin) — Cooling Only — Model Series Twin

Class Indoor Units

35

50

60

FHYC

35K×2

50K×2

60K×2

71K×2 100K×2 125K×2

FHY

35B×2

50B×2

60B×2

71B×2 100B×2 125B×2

71LU

100LU

125LU

140LU

Outdoor R Units

Indoor Units

50

71

50

60

FHYC

50K×3

71K×3

50K×4

60K×4

FHY

50B×3

71B×3

50B×4

60B×4

140LU

200KU

200KU

250KU

Outdoor R Units

100

200KU

125

250KU

Double Twin

Triple

Class

71

Cautions 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.

2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.

SkyAir LU Series – Cooling Only –

107

2


Features

ED21-301

1. Features SkyAir Series - Twin, Triple, Double Twin Systems (Simultaneous Operation System)

1.1

What are Twin, Triple, Double Twin Systems? One large room can be cooled simultaneously by two, three or four indoor units according to the environmental needs. Space saving for outdoor units. Possible to cool in outdoor temp. down to -15°C by using optional year-round cooling kit (KRK5F80, 140, 160V1) The operation limit has been extended down to an outdoor temp. of -15°C making it possible to operate the unit in the cooling mode whenever you need it all year round. Note:

Individual control (Such as room temperature) is not available.

(Ex.)Pair

(Ex.)Pair

(Ex.)Twin

(Ex.)Twin

(Ex.)Triple

(Ex.)Triple

FHYC50K

FHYC50K

FHYC50K

FHYC50K

FHYC50K

FHYC50K

Circuit breaker R140LU

Even Temperature Distribution Only one Remote Controller Only one Circuit Breaker (S0026-1)

(S0027)

Only one circuit breaker is needed for versatile electric work. Simple refrigerant system due to the branch piping kit specially designed for this system.

108

SkyAir LU Series – Cooling Only –


ED21-301

Model Name and Power Supply

2. Model Name and Power Supply 2.1

Twin, Triple and Double Twin System

2.1.1

50Hz Twin Indoor Units FHYC35KVE+FHYC35KVE

Outdoor Units

2

Power Supply

R71LUV1

FHY35BVE+FHY35BVE

R71LUV1

FHYC50KVE+FHYC50KVE

R100LUV1

FHY50BVE+FHY50BVE

R100LUV1

FHYC35KVE+FHYC35KVE

R71LUY1

FHY35BVE+FHY35BVE

R71LUY1

FHYC50KVE+FHYC50KVE

R100LUY1

FHY50BVE+FHY50BVE

R100LUY1

FHYC60KVE+FHYC60KVE

R125LUY1

FHY60BVE+FHY60BVE

R125LUY1

FHYC71KVE+FHYC71KVE

R140LUY1

FHY71BVE+FHY71BVE

R140LUY1

FHYC100KVE+FHYC100KVE

R200KUY1

FHY100BVE+FHY100BVE

R200KUY1

FHYC125KVE+FHYC125KVE

R250KUY1

FHY125BVE+FHY125BVE

R250KUY1

1φ, 220~240V, 50Hz

3φ, 380~415V, 50Hz

Triple Indoor Units

Outdoor Units

Power Supply

FHYC50KVE+FHYC50KVE+FHYC50KVE R140LUY1 FHY50BVE+FHY50BVE+FHY50BVE

R140LUY1

FHYC71KVE+FHYC71KVE+FHYC71KVE R200KUY1 FHY71BVE+FHY71BVE+FHY71BVE

3φ, 380~415V, 50Hz

R200KUY1

Double Twin Indoor Units

Outdoor Units

FHYC50KVE+FHYC50KVE+ FHYC50KVE+FHYC50KVE

R200KUY1

FHY50BVE+FHY50BVE+ FHY50BVE+FHY50BVE

R200KUY1

FHYC60KVE+FHYC60KVE+ FHYC60KVE+FHYC60KVE

R250KUY1

FHY60BVE+FHY60BVE+ FHY60BVE+FHY60BVE

R250KUY1

SkyAir LU Series – Cooling Only –

Power Supply

3φ, 380~415V, 50Hz

109


Model Name and Power Supply

2.1.2

ED21-301

60Hz Twin Indoor Units FHYC35KVE+FHYC35KVE

Outdoor Units

Power Supply

R71LUVAL

FHY35BVE+FHY35BVE

R71LUVAL

FHYC50KVE+FHYC50KVE

R100LUVAL

FHY50BVE+FHY50BVE

R100LUVAL

FHYC60KVE+FHYC60KVE

R125LUTAL

FHY60BVE+FHY60BVE

R125LUTAL

FHYC71KVE+FHYC71KVE

R140LUTAL

FHY71BVE+FHY71BVE

R140LUTAL

FHYC100KVE+FHYC100KVE

R200KUTAL

FHY100BVE+FHY100BVE

R200KUTAL

FHYC125KVE+FHYC125KVE

R250KUTAL

FHY125BVE+FHY125BVE

R250KUTAL

FHYC60KVE+FHYC60KVE

R125LUYAL

FHY60BVE+FHY60BVE

R125LUYAL

FHYC71KVE+FHYC71KVE

R140LUYAL

FHY71BVE+FHY71BVE

R140LUYAL

FHYC100KVE+FHYC100KVE

R200KUYAL

FHY100BVE+FHY100BVE

R200KUYAL

FHYC125KVE+FHYC125KVE

R250KUYAL

FHY125BVE+FHY125BVE

R250KUYAL

1φ, 220V, 60Hz

3φ, 220V, 60Hz

3φ, 380V, 60Hz

Triple Indoor Units

Outdoor Units

Power Supply

FHYC50KVE+FHYC50KVE+FHYC50KVE R140LUTAL FHY50BVE+FHY50BVE+FHY50BVE

R140LUTAL

FHYC71KVE+FHYC71KVE+FHYC71KVE R200KUTAL FHY71BVE+FHY71BVE+FHY71BVE

3φ, 220V, 60Hz

R200KUTAL

FHYC50KVE+FHYC50KVE+FHYC50KVE R140LUYAL FHY50BVE+FHY50BVE+FHY50BVE

R140LUYAL

FHYC71KVE+FHYC71KVE+FHYC71KVE R200KUYAL FHY71BVE+FHY71BVE+FHY71BVE

3φ, 380V, 60Hz

R200KUYAL

Double Twin Indoor Units

Note:

110

Outdoor Units

FHYC50KVE+FHYC50KVE+ FHYC50KVE+FHYC50KVE

R200KUTAL

FHY50BVE+FHY50BVE+ FHY50BVE+FHY50BVE

R200KUTAL

FHYC60KVE+FHYC60KVE+ FHYC60KVE+FHYC60KVE

R250KUTAL

FHY60BVE+FHY60BVE+ FHY60BVE+FHY60BVE

R250KUTAL

FHYC50KVE+FHYC50KVE+ FHYC50KVE+FHYC50KVE

R200KUYAL

FHY50BVE+FHY50BVE+ FHY50BVE+FHY50BVE

R200KUYAL

FHYC60KVE+FHYC60KVE+ FHYC60KVE+FHYC60KVE

R250KUYAL

FHY60BVE+FHY60BVE+ FHY60BVE+FHY60BVE

R250KUYAL

Power Supply

3φ, 220V, 60Hz

3φ, 380V, 60Hz

Power Supply Intake : Outdoor Unit

SkyAir LU Series – Cooling Only –


ED21-301

External Appearance

3. External Appearance 3.1

External Appearance

Indoor Units

2 FHY–B FHYC–K

Remote Controller

Wired Type

Wireless Type

Outdoor Units

R71LU

R100LU

R200KU

SkyAir LU Series – Cooling Only –

R125LU

R140LU

R250KU

111


Specifications

ED21-301

4. Specifications 4.1

50Hz

FHYC (Ceiling Mounted Cassette Type) <50Hz> - Twin Model

Indoor Unit Outdoor Unit

FHYC50KVE×2 FHYC60KVE×2 R100LUV1 — R100LUY1 R125LUY1 ∗1 Cooling Capacity (1)/(2)/(3) 10.6/10.5/10.5 13.0/12.8/12.8 36,100/35,700/35,700 44,500/43,600/43,600 9,100/9,000/9,000 11,200/11,000/11,000 Indoor Unit ∗3 FHYC50KVE×2 FHYC60KVE×2 Dimensions H×W×D mm 230×840×840 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×8×1.5 Face Area m² 0.331 Fan Model QTS45B14M Type Turbo Fan Motor Output W 45 Air Flow Rate ∗2 m³/min. (H)14–16 (L)10–12 (H)15–17 (L)11–13 (H)19–21 (L)14–16 Weight kg 24 Piping Liquid mm φ6.4 (Flare) Connections Gas mm φ12.7 (Flare) φ15.9 (Flare) Drain mm I.Dφ25×O.Dφ32 Remote Controller Wired BRC1C61 (Note. 6) (Option) Wireless BRC7C613W Decoration Model BYC125K–W1X2 Panel Color White (Option) ∗3 Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Unit V1 R71LUV1 R100LUV1 — Y1 R71LUY1 R100LUY1 R125LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 65 90 65+85 Air Flow Rate ∗2 m³/min. 48–51 59–62 92–100 Weight kg V1 72 87 — Y1 71 84 98 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm φ26.0 (Hole) Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Max. Length m 50 (Equivalent Length 70m) Ref. Piping Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039097

Note:

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–220V (380V)

JIS B8616

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V (415V)

AS 1861

2. 3. 4. 5. 6.

112

FHYC35KVE×2 R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FHYC35KVE×2

V1 Y1 kW Btu/h kcal/h

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. ∗3 Each value shows the specification per one unit. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

FHYC (Ceiling Mounted Cassette Type) <50Hz> - Twin Model

Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)

FHYC71KVE×2 R140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 FHYC71KVE×2 230×840×840 Cross Fin Coil 2×8×1.5 0.331 QTS45B14M

kW Btu/h kcal/h

FHYC100KVE×2 R200KUY1 22.5/22.2/22.0 76,800/75,800/75,100 19,400/19,100/18,900 FHYC100KVE×2

FHYC125KVE×2 R250KUY1 27.1/26.6/26.3 92,500/90,800/89,800 23,300/22,900/22,600 FHYC125KVE×2

2

Indoor Unit ∗3 Dimensions H×W×D mm 288×840×840 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×12×1.5 Face Area m² 0.497 Fan Model QTS45A17M Type Turbo Fan Motor Output W 45 90 Air Flow Rate ∗2 m³/min. (H)19–21 (L)14–15 (H)28–31 (L)21–24 (H)33–36 (L)24–27 Sound Pressure Level ∗2 dB(A) (H)35–37 (L)30–32 (H)39–41 (L)34–36 (H)42–44 (L)36–38 Weight kg 24 28 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9(Flare) φ19.1(Flare) Drain mm I.Dφ25×O.Dφ32 Remote Controller Wired BRC1C61 (Note. 5) (Option) Wireless BRC7C613W Decoration Model BYC125K–W1×2 Panel Color White (Option) ∗3 Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Unit R140LUY1 R200KUY1 R250KUY1 Color Ivory Dimensions H×W×D mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×50×2.0 Face Area m² 1.134 1.57 1.97 Comp. Model JT170BC–YE JT236D–P1YE JT335D–P1YE Type Hermetically Sealed Scroll Type Motor Output kW 4.50 5.5 9.0 Fan Model P47L11S×2 P52H11SM Type Propeller Motor Output W 65+90 230+190 Air Flow Rate ∗2 m³/min. 97–109 150–154 175–179 Weight kg 109 178 202 Piping Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) Drain mm φ26.0 (Hole) — Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Capillary Tube Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) Ref. Oil Model SUNISO 4GSDID–K Charge L 1.6 3.0 Drawing No. 4D039098 4D029963 4D029965

Note:

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

Model

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–380V

LU, KU

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

KU

7.5m

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

2. 3. 4. 5.

5m

50Hz–380V 50Hz–415V

JIS B8616

LU

AS 1861

LU, KU

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

∗2 AFR (Air flow rate) and sound pressure level are shown at 380V–415V. Capacities are net, including a deduction for cooling for indoor fan motor heat. ∗3 Each value shows the specification per one unit. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

113


Specifications

ED21-301

FHYC (Ceiling Mounted Cassette Type) <50Hz> - Triple / Double Twin Model

Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)

FHYC71KVE×3 R200KUY1

FHYC50KVE×4 R200KUY1

FHYC60KVE×4 R250KUY1 27.1/26.6/26.3 92,500/90,800/89,800 23,300/22,900/22,600 FHYC60KVE×4

22.5/22.2/22.0 76,800/75,800/75,100 19,400/19,100/18,900 Indoor Unit ∗3 FHYC71KVE×3 FHYC50KVE×4 Dimensions H×W×D mm 230×840×840 Coil Type Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×8×1.5 Face Area m² 0.331 Fan Model QTS45B14M Type Turbo Fan Motor Output W 45 Air Flow Rate ∗2 m³/min. (H)15–17 (L)11–12 (H)19–21 (L)14–15 (H)15–17 (L)11–12 (H)19–21 (L)14–16 Sound Pressure Level ∗2 dB(A) (H)33–35 (L)29–31 (H)35–37 (L)30–32 (H)33–35 (L)29–31 (H)35–37 (L)30–32 Weight kg 24 Piping Liquid mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) Connections Gas mm φ15.9(Flare) Drain mm I.Dφ25×O.Dφ32 Remote Controller Wired BRC1C61 (Note. 5) (Option) Wireless BRC7C613W Decoration Model BYC125K–W1×3 BYC125K–W1×4 Panel Color White (Option) ∗3 Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Unit R140LUY1 R200KUY1 R200KUY1 R250KUY1 Color Ivory Dimensions H×W×D mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×50×2.0 Face Area m² 1.134 1.57 1.97 Comp. Model JT170BC–YE JT236D–P1YE JT335D–P1YE Type Hermetically Sealed Scroll Type Motor Output kW 4.50 5.5 9.0 Fan Model P47L11S×2 P52H11SM Type Propeller Motor Output W 65+90 230+190 Air Flow Rate ∗2 m³/min. 97–109 150–154 175–179 Weight kg 109 178 202 Piping Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) Drain mm φ26.0 (Hole) — Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Capillary Tube Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) Ref. Oil Model SUNISO 4GSDID–K Charge L 1.6 3.0 Drawing No. 4D039098 4D029963 4D029965

Note:

kW Btu/h kcal/h

FHYC50KVE×3 R140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 FHYC50KVE×3

1. ∗1 The above data based on the conditions shown in the table below. Cooling

Piping length

Hz–Volts

Standard

Model

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–380V

LU, KU

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

KU

7.5m

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

2. 3. 4. 5.

114

Conversion Formulae

Mark

5m

50Hz–380V 50Hz–415V

JIS B8616

LU

AS 1861

LU, KU

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

∗2 AFR (Air flow rate) and sound pressure level are shown at 380V–415V. Capacities are net, including a deduction for cooling for indoor fan motor heat. ∗3 Each value shows the specification per one unit. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

FHY (Ceiling Suspended Type) <50Hz> - Twin Model

Indoor Unit Outdoor Unit

FHY35BVE×2 R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FHY35BVE×2

V1 Y1 kW Btu/h kcal/h

∗1 Cooling Capacity (1)/(2)/(3)

Indoor Unit ∗4 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit

FHY50BVE×2 R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FHY50BVE×2 White

FHY60BVE×2 — R125LUY1 13.0/12.8/12.8 44,500/43,600/43,600 11,200/11,000/11,000 FHY60BVE×2

2

195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 2×12×1.75 3×12×1.75 m² 0.182 0.233 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)16 (L)13 Resin Net (with Mold Resistant) kg 23 24 26 mm φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 5) BRC7E66 V1 R71LUV1 R100LUV1 — Y1 R71LUY1 R100LUY1 R125LUY1 Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model V1 ZR36K3–PFJ ZR48K3–PFJ — Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE Type Hermetically Sealed Scroll Type Motor Output kW 2.24 3.00 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 65 90 65+85 Air Flow Rate ∗2 m³/min. 48–51 59–62 92–100 Weight kg V1 72 87 — Y1 71 84 98 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm φ26.0 (Hole) Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039100

Note:

mm

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–220V (380V)

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–220V (380V)

JIS B8616

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

50Hz–240V (415V)

AS 1861

2. 3. 4. 5.

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. ∗4 Each value for indoor unit shows the specification per one unit. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

115


Specifications

ED21-301

FHY (Ceiling Suspended Type) <50Hz> - Twin Model

Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)

Indoor Unit ∗4 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate ∗2 Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Notes:

FHY100BVE×2 FHY125BVE×2 R200KUY1 R250KUY1 kW 22.5/22.2/22.0 27.1/26.6/26.3 Btu/h 76,800/75,800/75,100 92,500/90,800/89,800 kcal/h 19,400/19,100/18,900 23,300/22,900/22,600 FHY100BVE×2 FHY125BVE×2 White mm 195×1,160×680 195×1,400×680 195×1,590×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.293 0.341 4D12K1AA1 3D12K2AA1 4D12KAA1 Sirocco Fan W 62 130 m³/min. (H)17 (L)14 (H)24 (L)20 (H)30 (L)25 Resin Net (with Mold Resistant) kg 27 32 35 mm φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 5) BRC7E66 R140LUY1 R200KUY1 R250KUY1 Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 JT170BC–YE JT236D–P1YE JT335D–P1YE Hermetically Sealed Scroll Type kW 4.50 5.5 9.0 P47L11S×2 P52H11SM Propeller W 65+90 230+190 m³/min. 97–109 150–154 175–179 kg 109 178 202 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039101 4D028444 4D028439

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

Model

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–380V

LU, KU

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

KU

7.5m

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

2. 3. 4. 5.

116

FHY71BVE×2 R140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 FHY71BVE×2

5m

50Hz–380V 50Hz–415V

JIS B8616

LU

AS 1861

LU, KU

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

∗2 AFR (Air flow rate) is shown at 380V–415V. Capacities are net, including a deduction for cooling for indoor fan motor heat. ∗4 Each value for indoor unit shows the specification per one unit. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

FHY (Ceiling Suspended Type) <50Hz> - Triple / Double Twin Model

Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)

kW Btu/h kcal/h

Indoor Unit ∗4 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate ∗2 Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Notes:

FHY50BVE×3 R140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 FHY50BVE×3

FHY71BVE×3 R200KUY1

FHY50BVE×4 R200KUY1

FHY60BVE×4 R250KUY1 27.1/26.6/26.3 92,500/90,800/89,800 23,300/22,900/22,600 FHY60BVE×4

22.5/22.2/22.0 76,800/75,800/75,100 19,400/19,100/18,900 FHY71BVE×3 FHY50BVE×4 White mm 195×960×680 195×1,160×680 195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.182 0.233 0.182 0.233 3D12K1AA1 4D12K1AA1 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)17 (L)14 (H)13 (L)10 (H)16 (L)13 Resin Net (with Mold Resistant) kg 24 27 24 26 mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) mm φ15.9 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 5) BRC7E66 R140LUY1 R200KUY1 R200KUY1 R250KUY1 Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 JT170BC–YE JT236D–P1YE JT335D–P1YE Hermetically Sealed Scroll Type kW 4.50 5.5 9.0 P47L11S×2 P52H11SM Propeller W 65+90 230+190 m³/min. 97–109 150–154 175–179 kg 109 178 202 mm φ9.5 (Flare) φ12.7(Flare) φ15.9(Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039101 4D028444 4D028439

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

Model

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–380V

LU, KU

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

KU

7.5m

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

5m

50Hz–380V 50Hz–415V

JIS B8616

LU

AS 1861

LU, KU

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. ∗2 AFR (Air flow rate) is shown at 380V–415V. 3. Capacities are net, including a deduction for cooling for indoor fan motor heat. 4. ∗4 Each value for indoor unit shows the specification per one unit. 5. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

117

2


Specifications

4.2

ED21-301

60Hz

FHYC (Ceiling Mounted Cassette Type) <60Hz> - Twin Model

Indoor Unit Outdoor Unit

FHYC50KVE×2 FHYC60KVE×2 R100LUVAL — — R125LUTAL — R125LUYAL ∗1 Cooling Capacity (1)/(2) 11.6/11.4 14.5/14.3 39,700/38,900 49,600/48,800 10,000/9,800 12,500/12,300 Indoor Unit ∗2 FHYC50KVE×2 FHYC60KVE×2 Dimensions H×W×D mm 230×840×840 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×8×1.5 Face Area m² 0.331 Fan Model QTS45B14M Type Turbo Fan Motor Output W 45 Air Flow Rate m³/min. (H)14 (L)10 (H)15 (L)11 (H)19 (L)14 Weight kg 24 Piping Liquid mm φ6.4 (Flare) Connections Gas mm φ12.7(Flare) φ15.9(Flare) Drain mm I.Dφ25×O.Dφ32 Remote Controller Wired BRC1C61 (Note. 4) (Option) Wireless BRC7C613W Decoration Model BYC125K–W1×2 Panel (Option) Color White ∗2 Dimensions (H×W×D) mm 40×950×950 Air Filter Resin Net (with Mold Resistant) Weight kg 5 Outdoor Unit VAL R71LUVAL R100LUVAL — TAL — — R125LUTAL Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model VAL ZR36K3–PFV ZR47K3–PFV — TAL — — JT160BC YAL — — JT160BC–YH Type Hermetically Sealed Scroll Type Motor Output kW 2.24 2.92 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 75 100 95+75 Air Flow Rate m³/min. 49 59 94 Weight kg 75 92 98 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm φ26.0 (Hole) Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector(TAL·YAL). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039108

Notes:

FHYC35KVE×2 R71LUVAL — — 8.3/8.1 28,200/27,800 7,100/7,000 FHYC35KVE×2

VAL TAL YAL kW Btu/h kcal/h

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

JIS B8616

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.

118

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

FHYC (Ceiling Mounted Cassette Type) <60Hz> - Twin Model

Indoor Unit Outdoor Unit

∗1 Cooling Capacity (1)/(2)/(3)

kW Btu/h kcal/h

Indoor Unit ∗2 Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Sound Pressure Level Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Decoration Model Panel Color (Option) ∗2 Dimensions (H×W×D) Air Filter Weight Outdoor Unit Color Dimensions Coil

Comp.

Fan

Weight Piping Connections

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Notes:

FHYC71KVE×2 R140LUTAL R140LUYAL 16.1/15.8/– 55,000/53,900/– 13,800/13,500/– FHYC71KVE×2 230×840×840 Cross Fin Coil 2×8×1.5 0.331 QTS45B14M

TAL YAL

mm

FHYC100KVE×2 R200KUTAL R200KUYAL 22.5/22.2/20.0 76,800/75,800/68,300 19,400/19,100/17,200 FHYC100KVE×2

FHYC125KVE×2 R250KUTAL R250KUYAL 27.1/26.6/24.1 92,500/90,800/82,300 23,300/22,900/20,700 FHYC125KVE×2

2

288×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×12×1.5 m² 0.497 QTS45A17M Turbo Fan W 45 90 m³/min. (H)19 (L)14 (H)28 (L)21 (H)33 (L)24 dB(A) (H)35 (L)30 (H)39 (L)34 (H)42 (L)36 kg 24 28 mm φ9.5 (Flare) mm φ15.9(Flare) φ19.1(Flare) mm I.Dφ25×O.Dφ32 BRC1C61 (Note. 4) BRC7C613W BYC125K–W1×2 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R140LUTAL R200KUTAL R250KUTAL TAL R140LUYAL R200KUYAL R250KUYAL YAL Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 JT212D–P1 JT300D–P1 JT170BC TAL JT212D–P1YH JT300D–P1YH JT170BC–YH YAL Hermetically Sealed Scroll Type kW 4.50 5.5 7.5 P47L11S×2 P52H11SM Propeller W 100+75 230+190 m³/min. 101 160 190 kg 109 177 200 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039109 4D029964 4D029966

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Standard

Model

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

LU, KU

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

5m

KU

7.5m

JIS B8616

LU

(3)

Indoor : 29°CDB, 19.0°CWB Outdoor : 46°CDB, 24°CWB

7.5m

SSA 385/386

KU

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

119


Specifications

ED21-301

FHYC (Ceiling Mounted Cassette Type) <60Hz> - Triple / Double Twin Model

Indoor Unit Outdoor Unit

TAL YAL

∗1 Cooling Capacity (1)/(2)/(3)

kW Btu/h kcal/h

Indoor Unit ∗2 Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Sound Pressure Level Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Decoration Model Panel Color (Option) ∗2 Dimensions (H×W×D) Air Filter Weight Outdoor Unit Color Dimensions Coil

Comp.

Fan

Weight Piping Connections

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Notes:

FHYC50KVE×3 R140LUTAL R140LUYAL 16.1/15.8/– 55,000/53,900/– 13,800/13,500/– FHYC50KVE×3

FHYC71KVE×3 R200KUTAL R200KUYAL

FHYC50KVE×4 R200KUTAL R200KUYAL

FHYC60KVE×4 R250KUTAL R250KUYAL 27.1/26.6/24.1 92,500/90,800/82,300 23,300/22,900/20,700 FHYC60KVE×4

22.5/22.2/22.0 76,800/75,800/68,300 19,400/19,100/17,200 FHYC71KVE×3 FHYC50KVE×4 mm 230×840×840 Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 m² 0.331 QTS45B14M Turbo Fan W 45 m³/min. (H)15 (L)11 (H)19 (L)14 (H)15 (L)11 (H)19 (L)14 dB(A) (H)33 (L)29 (H)35 (L)30 (H)33 (L)29 (H)35 (L)30 kg 24 mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) mm φ15.9(Flare) mm I.Dφ25×O.Dφ32 BRC1C61 (Note. 4) BRC7C613W BYC125K–W1×3 BYC125K–W1×4 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R140LUTAL R200KUTAL R200KUTAL R250KUTAL TAL R140LUYAL R200KUYAL R200KUYAL R250KUYAL YAL Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 JT212D–P1 JT300D–P1 JT170BC TAL JT212D–P1YH JT300D–P1YH JT170BC–YH YAL Hermetically Sealed Scroll Type kW 4.50 5.5 7.5 P47L11S×2 P52H11SM Propeller W 100+75 230+190 m³/min. 101 160 190 kg 109 177 200 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039109 4D029964 4D029966

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Standard

Model

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

LU, KU

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

5m

KU

7.5m

JIS B8616

LU

(3)

Indoor : 29°CDB, 19.0°CWB Outdoor : 46°CDB, 24°CWB

7.5m

SSA 385/386

KU

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.

120

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

FHY (Ceiling Suspended Type) <60Hz> - Twin Model

Indoor Unit Outdoor Unit

FHY35BVE×2 R71LUVAL — — 8.3/8.1 28,200/27,800 7,100/7,000 FHY35BVE×2

VAL TAL YAL kW Btu/h kcal/h

∗1 Cooling Capacity (1)/(2)

Indoor Unit ∗2 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit

FHY50BVE×2 R100LUVAL — — 11.6/11.4 39,700/38,900 10,000/9,800 FHY50BVE×2 White

FHY60BVE×2 — R125LUTAL R125LUYAL 14.5/14.3 49,600/48,800 12,500/12,300 FHY60BVE×2

2

195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 2×12×1.75 3×12×1.75 m² 0.182 0.233 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)16 (L)13 Resin Net (with Mold Resistant) kg 23 24 26 mm φ6.4 (Flare) mm φ12.7 (Flare) φ15.9(Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 4) BRC7E66 VAL R71LUVAL R100LUVAL — TAL — — R125LUTAL YAL — — R125LUYAL Color Ivory Dimensions H×W×D mm 770×900×320 1,170×900×320 Coil Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 Face Area m² 0.634 0.983 Comp. Model VAL ZR36K3–PFV ZR47K3–PFV — TAL — — JT160BC YAL — — JT160BC–YH Type Hermetically Sealed Scroll Type Motor Output kW 2.24 2.92 3.75 Fan Model P47L11S P47L11S×2 Type Propeller Motor Output W 75 100 95+75 Air Flow Rate m³/min. 49 59 94 Weight kg 75 92 98 Piping Liquid mm φ9.5 (Flare) Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) Drain mm φ26.0 (Hole) Safety Devices Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse. Capacity Step % 100–0 Refrigerant Control Electronic Expansion Valve Ref. Piping Max. Length m 50 (Equivalent Length 70m) Max. Height Difference m 30 Refrigerant Model R22 Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) Ref. Oil Model SONTEX 200LT SUNISO 4GSDID–K Charge L 1.2 1.5 Drawing No. 4D039111

Notes:

mm

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Standard

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

JIS B8616

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

121


Specifications

ED21-301

FHY (Ceiling Suspended Type) <60Hz> - Twin Model

Indoor Unit Outdoor Unit

∗1 Cooling Capacity (1)/(2)/(3)

Indoor Unit ∗2 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Sound Pressure Level Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit Color Dimensions Coil

Comp.

Fan

Weight Piping Connections

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Notes:

FHY71BVE×2 R140LUTAL R140LUYAL 16.1/15.8/– 55,000/53,900/– 13,800/13,500/– FHY71BVE×2

FHY100BVE×2 FHY125BVE×2 R200KUTAL R250KUTAL R200KUYAL R250KUYAL 22.5/22.2/20.0 27.1/26.6/24.1 76,800/75,800/68,300 92,500/90,800/82,300 19,400/19,100/17,200 23,300/22,900/20,700 FHY100BVE×2 FHY125BVE×2 White mm 195×1,160×680 195×1,400×680 195×1,590×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.293 0.341 4D12K1AA1 3D12K2AA1 4D12K2AA1 Sirocco Fan W 62 130 m³/min. (H)17 (L)14 (H)24 (L)20 (H)30 (L)25 dB(A) — (H)42 (L)37 (H)44 (L)39 Resin Net (with Mold Resistant) kg 27 32 35 mm φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 4) BRC7E66 TAL R140LUTAL R200KUTAL R250KUTAL YAL R140LUYAL R200KUYAL R250KUYAL Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 TAL JT170BC JT212D–P1 JT300D–P1 YAL JT170BC–YH JT212D–P1YH JT300D–P1YH Hermetically Sealed Scroll Type kW 4.50 5.5 7.5 P47L11S×2 P52H11SM Propeller W 100+75 230+190 m³/min. 101 160 190 kg 109 177 200 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039112 4D028563 4D028564 TAL YAL kW Btu/h kcal/h

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Standard

Model

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

LU, KU

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

5m

KU

7.5m

JIS B8616

LU

(3)

Indoor : 29°CDB, 19.0°CWB Outdoor : 46°CDB, 24°CWB

7.5m

SSA 385/386

KU

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.

122

SkyAir LU Series – Cooling Only –


ED21-301

Specifications

FHY (Ceiling Suspended Type) <60Hz> - Triple / Double Twin Model

Indoor Unit Outdoor Unit

TAL YAL kW Btu/h kcal/h

∗1 Cooling Capacity (1)/(2)/(3)

Indoor Unit Color Dimensions Coil

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate Sound Pressure Level

Air Filter Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Wired Wireless

Outdoor Unit Color Dimensions Coil

Comp.

Fan

Weight Piping Connections

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Notes:

FHY50BVE×3 R140LUTAL R140LUYAL 16.1/15.8/– 55,000/53,900/– 13,800/13,500/– FHY50BVE×3

FHY71BVE×3 R200KUTAL R200KUYAL

FHY50BVE×4 R200KUTAL R200KUYAL

FHY60BVE×4 R250KUTAL R250KUYAL 27.1/26.6/24.1 92,500/90,800/82,300 23,300/22,900/20,700 FHY60BVE×4

22.5/22.2/20.0 76,800/75,800/68,300 19,400/19,100/17,200 FHY71BVE×3 FHY50BVE×4 White mm 195×960×680 195×1,160×680 195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.182 0.233 0.182 0.233 3D12K1AA1 4D12K1AA1 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)17 (L)14 (H)13 (L)10 (H)16 (L)13 dB(A) — (H)39 (L)35 (H)38 (L)33 (H)38 (L)33 Resin Net (with Mold Resistant) kg 24 26 23 26 mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) φ6.4 (Flare) mm φ15.9 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 4) BRC7E66 TAL R140LUTAL R200KUTAL R200KUTAL R250KUTAL YAL R140LUYAL R200KUYAL R200KUYAL R250KUYAL Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 TAL JT170BC JT212D–P1 JT300D–P1 YAL JT170BC–YH JT212D–P1YH JT300D–P1YH Hermetically Sealed Scroll Type kW 4.50 5.5 7.5 P47L11S×2 P52H11SM Propeller W 100+75 230+190 m³/min. 101 160 190 kg 109 177 200 mm φ9.5 (Flare) φ12.7 (Flare) φ15.9 (Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039112 4D028563 4D028564

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Standard

Model

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

LU, KU

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

5m

KU

7.5m

JIS B8616

LU

(3)

Indoor : 29°CDB, 19.0°CWB Outdoor : 46°CDB, 24°CWB

7.5m

SSA 385/386

KU

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. ∗2 Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

123

2


Dimensions and Service Space

ED21-301

5. Dimensions and Service Space 5.1

Indoor Unit

5.1.1

FHYC (Ceiling Mounted Cassette Type)

FHYC35K + BYC125K-W1 C 860~890 Ceiling opening

80

2× 100=200

Unit (mm)

85

300 or less 680 Suspension position

950

(165)

Note3.

420

9

Branch duct connection

350 C

view 60

4-M4 Hole (prepared hole) φ7

80 80

6

40

860~890 Ceiling opening

950

780 Suspension position

10

5

840

55

55

55

80 2× 100=200

12-M4 Hole (prepared hole)

85

5

150

2

1

4

40 350

Branch duct connection

A

∗1500mm or more Required space ∗1500mm or more

∗1500mm or more

∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more.

1000 or more Required space

30

8

260 270 315

165

95 110

295

For fresh air intake kit connection (direct installation type)

view

55

840

125 150 240

750 10

B B

200

Adjustable (0~550)

420

3

40

230

view

240

Suspension bolt 4-M8~M10

160

7 A

Description

Name Number 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection

Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.

2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

5 6 7 8

φ6.4 flare φ12.7 flare VP25

Remote control code and control wiring connection

Air discharge grille Air suction grille Port for water supply Corner decoration cover

9 10 Drain hose

O.D.32

C : 3D012310B

FHYC50K + BYC125K-W1 FHYC60K + BYC125K-W1 Unit (mm)

C

950

2× 100=200 85

80

860~890 Ceiling opening 300 or less 680 Suspension position

(165)

Note3.

420

9 10

6

Branch duct connection

C view 60

4-M4 Hole (prepared hole) φ7

80

5

80

950

780 Suspension position 860~890 Ceiling opening

40 350

840

55

12-M4 Hole (prepared hole)

8

5

260 270 315

4

1

2

40 350

Branch duct connection

A

165 1000 or more Required space

125 150 240 240

For fresh air intake kit connection (direct installation type)

55

2×100=200 85

95 110

80

150

750 Adjustable (0~550)

55

840 295

200

230

B view

55

30 Suspension bolt 4-M8~M10

B

3

40

10

420

160

7 A view

∗1500mm or more Required space 1500mm or more

∗1500mm or more

∗1500mm or more ∗ When the discharge grill is closeout, the required space is 200mm or more. Name Number 1 Liquid pipe connection Gas pipe connection 2 Drain pipe connection 3 Power supply connection 4

Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.

5

Remote control code and control wiring connection

6

2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

9 10

Air discharge grille Air suction grille Port for water supply Corner decoration cover

7 8

Drain hose

Description φ6.4 flare φ15.9 flare VP25

O.D.32

C : 3D012311B

124

SkyAir LU Series – Cooling Only –


ED21-301

Dimensions and Service Space

FHYC71K + BYC125K-W1 Unit (mm)

1000 or more

2

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

C : 3D012312C

FHYC100K + BYC125K-W1 FHYC125K + BYC125K-W1 Unit (mm)

C

(195)

950

2× 100=200 85

80

860~890 Ceiling opening 300 or less 680 Suspension position

Note3.

165

6

40 350

Branch duct connection

C view

4-M4 Hole (prepared hole) φ7 5

60 80 80

950

780 Suspension position 860~890 Ceiling opening

10

155

420

9

160

7 A view

420

B

5

260 270 315

4

1

14-M4 Hole (prepared hole)

2× 100=200 85

195

150

125 150 298 240

8

55

840 80

200

30 Suspension bolt 4-M8~M10

55

40 50 155 165

55

840 295

2

40 350

Branch duct connection

A

1000 or more Required space

55

40

10

288

750 Adjustable (0~550)

B view

3

Notes: 1. Location of unit's Name Plate For Main body : Switch Box cover inside surface of suction grille. For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will be signal receiver. Refer to the drawing of wireless remote controller in detail.

2. When installing an optional accessory, refer to the installation drawings. For fresh air intake kit ...... Inspection port is necessary. For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

SkyAir LU Series – Cooling Only –

For fresh air intake kit connection (direct installation type)

∗1500mm or more Required space ∗1500mm or more

∗1500mm or more

∗1500mm or more ∗ When the discharge grill is closeout, the required is space 200mm or more. Number Name 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection 5 6 7 8 9 10

Description φ9.5 flare φ19.1 flare VP25

Remote control code and control wiring connection

Air discharge grille Air suction grille Port for water supply Corner decoration cover Drain hose

O.D.32

C : 3D012313C

125


Dimensions and Service Space

5.1.2

ED21-301

FHYC with High Efficiency Filter

KAFP556D80·557D80 for FHYC35~71K

Unit (mm)

290

Note:When other optional kit is installed, refer to the installation drawing of its optional kit.

6 5 4 3 2 1 Number

Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975A

KAFP556D160·557D160 for FHYC100~125K

Unit (mm)

Note:When other optional kit is installed, refer to the installation drawing of its optional kit.

6 5 4 3 2 1 Number

Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032976A

126

SkyAir LU Series – Cooling Only –


ED21-301

5.1.3

Dimensions and Service Space

FHYC with Fresh Air Intake Kit (Without T Joint, Duct Fan)

KDDP55D160 for FHYC35~71K

Unit (mm)

Service Access Panel : 450×450mm or more Refer to Note 2

2

Refrigerant Piping

Note 4

View

Service Access Panel : 450×450mm or more Refer to Note 2

290

Installation Service Access Panel

Connection Chamber (Right)

Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.

How to connect Chamber 4 Independently(Refer to Note 5,6)

Applicable Models SkyAir

FH(Y)C35~71K

5 4 3 2 1 Number

Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981A

KDDP55D160 for FHYC100~125K

Unit (mm)

Service Access Panel : 450×450mm or more Refer to Note 2

Refrigerant Piping

View

Service Access Panel : 450×450mm or more Refer to Note 2

Note 4

Installation Service Access Panel

Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6)

Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.

SkyAir LU Series – Cooling Only –

Applicable Models SkyAir

FHYC100~140K

5 4 3 2 1 Number

Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984A

127


Dimensions and Service Space

5.1.4

ED21-301

FHYC with Fresh Air Intake Kit (With T Joint, Without Duct Fan)

KDDP55D160K for FHYC35~71K

Unit (mm)

Service Access Panel : 450×450mm or more Refer to Note 2

Flexible Duct (Accessory)

Installation Service Access Panel

Service Access Panel : 450×450mm or more Refer to Note 2

Suction Duct (K-KFD9A) Optional (Accessory) T Joint

Plate Band

(Accessory)

290

(Accessory)

Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)

Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.

Applicable Models SkyAir

FH(Y)C35~71K

5 4 3 2 1 Number

Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032987A

KDDP55D160K for FHYC100~125K Service Access Panel : 450×450mm or more Refer to Note 2

Installation Service Access Panel

Unit (mm) Flexible Duct (Accessory)

Service Access Panel : 450×450mm or more Refer to Note 2 T Joint (Accessory)

Plate Band (Accessory)

Suction Duct (K-KFD9A) Optional (Accessory)

Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)

Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.

128

Applicable Models SkyAir

FHYC100~140K

5 4 3 2 1 Number

Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032990A

SkyAir LU Series – Cooling Only –


ED21-301

5.1.5

Dimensions and Service Space

FHYC with Panel Spacer

KDBJ55K160W for FHYC35~71K Unit (mm)

2

3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name

Note:When other optional kit is installed, refer to the installation drawing of its optional kit

Thickness of panel spacer

Dimension between the bottom surface of box and the surface of ceiling

View

Description J : 3D005390E

KDBJ55K160W for FHYC100~125K Unit (mm)

Note:When other optional kit is installed, refer to the installation drawing of its optional kit

3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name

Thickness of panel spacer

Dimension between the bottom surface of box and the surface of ceiling

View

Description J : 3D005391D

SkyAir LU Series – Cooling Only –

129


Dimensions and Service Space

5.1.6

ED21-301

FHY (Ceiling Suspended Type)

FHY35B FHY50B Unit (mm)

A

Model

FH(Y)35B FH(Y)50B

A

12.7

15.9

3D027536C 3D028600

FHY60B FHY71B Unit (mm)

A

130

Model

FH(Y)60B

FHY71B

A

6.4

9.5

3D027537 3D027538B

SkyAir LU Series – Cooling Only –


ED21-301

Dimensions and Service Space

FHY100B Unit (mm)

2

3D027539B

FHY125B Unit (mm)

3D027540

SkyAir LU Series – Cooling Only –

131


Dimensions and Service Space

5.2

ED21-301

Remote Controller

BRC7C613W (Wireless Type for FHYC~K)

BRC7E66 (Wireless Type for FHY~B)

3D028963

132

SkyAir LU Series – Cooling Only –


ED21-301

Dimensions and Service Space

BRC1C61 (Wired Type)

More comfortable operation by thermo sensor in the Remote Controller Applicable Model FH(Y)K-F(J) FH(Y)-B FH(Y)C-K FH(Y)B-F FUY-FJ FV(Y)-LA (Available for 2 remote control use) FAY-FA/L

2

C : 3D028952

SkyAir LU Series – Cooling Only –

133


Dimensions and Service Space

5.3

ED21-301

Outdoor Unit

R71LU Unit (mm)

3D039213

R100LU Unit (mm)

3D039214

134

SkyAir LU Series – Cooling Only –


ED21-301

Dimensions and Service Space

R125LU Unit (mm)

2

3D039215

R140LU Unit (mm)

3D039216

SkyAir LU Series – Cooling Only –

135


Dimensions and Service Space

ED21-301

R200KU Unit (mm)

3D029265

R250KU Unit (mm)

3D029264

136

SkyAir LU Series – Cooling Only –


ED21-301

5.4

Dimensions and Service Space

Installation Service Space for R71LU, 100LU, 125LU, 140LU

140 140

2

3D039172-1

SkyAir LU Series – Cooling Only –

137


Dimensions and Service Space

ED21-301

3D039172-2

138

SkyAir LU Series – Cooling Only –


ED21-301

5.5

Dimensions and Service Space

Installation Service Space for R200KU, 250KU

2

3D006578A

SkyAir LU Series – Cooling Only –

139


Piping Diagrams

ED21-301

6. Piping Diagrams 6.1

Twin

3D039765

R71LU

140

SkyAir LU Series – Cooling Only –


ED21-301

Piping Diagrams

3D039766

R100LU

2

SkyAir LU Series – Cooling Only –

141


Piping Diagrams

ED21-301

3D039767

R125LU

142

SkyAir LU Series – Cooling Only –


ED21-301

Piping Diagrams

3D039768

R140LU

2

SkyAir LU Series – Cooling Only –

143


Piping Diagrams

ED21-301

3D030194

R200KU R250KU

144

SkyAir LU Series – Cooling Only –


ED21-301

6.2

Piping Diagrams

Triple

3D039769

R140LU

SkyAir LU Series – Cooling Only –

145

2


Piping Diagrams

ED21-301

3D030195

R200KU

146

SkyAir LU Series – Cooling Only –


ED21-301

6.3

Piping Diagrams

Double Twin

3D030196

R200KU R250KU

SkyAir LU Series – Cooling Only –

2

147


Wiring Diagrams

ED21-301

7. Wiring Diagrams 7.1

Indoor Unit

FHYC35KVE FHYC50KVE FHYC60KVE FHYC71KVE FHYC100KVE FHYC125KVE

3D005668C

148

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

FHY35BVE FHY50BVE FHY60BVE FHY71BVE FHY100BVE FHY125BVE

2

3D027502

SkyAir LU Series – Cooling Only –

149


Wiring Diagrams

7.2

Outdoor Unit

7.2.1

50Hz

ED21-301

R71LUV1 R100LUV1

3D037640C

R71LUY1 R100LUY1

3D037642C

150

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

R125LUY1 R140LUY1

2

3D037644C

R200KUY1 R250KUY1

3D029091A

SkyAir LU Series – Cooling Only –

151


Wiring Diagrams

7.2.2

ED21-301

60Hz

R71LUVAL R100LUVAL

3D037935C

R125LUTAL R140LUTAL

3D037936C

152

SkyAir LU Series – Cooling Only –


ED21-301

Wiring Diagrams

R125LUYAL R140LUYAL

2

3D037937C

R200KUTAL R250KUTAL

3D029092A

SkyAir LU Series – Cooling Only –

153


Wiring Diagrams

ED21-301

R200KUYAL R250KUYAL

3D029091A

154

SkyAir LU Series – Cooling Only –


ED21-301

Capacity Tables

8. Capacity Tables 8.1

50Hz

35 × 2 + R71LUV1 35 × 2 + R71LUY1

2

3D039614

50 × 2 + R100LUV1 50 × 2 + R100LUY1

3D039627A

SkyAir LU Series – Cooling Only –

155


Capacity Tables

ED21-301

60 × 2 + R125LUY1

3D039636

50 × 3 + R140LUY1 71 × 2 + R140LUY1

3D039645

156

SkyAir LU Series – Cooling Only –


ED21-301

Capacity Tables

50 × 4 + R200KUY1 71 × 3 + R200KUY1 100 × 2 + R200KUY1

2

3D030166A

60 × 4 + R250KUY1 125 × 2 + R250KUY1

3D030168A

SkyAir LU Series – Cooling Only –

157


Capacity Tables

8.2

ED21-301

60Hz

35 × 2 + R71LUVAL

3D039616

50 × 2 + R100LUVAL

3D039629

158

SkyAir LU Series – Cooling Only –


ED21-301

Capacity Tables

60 × 2 + R125LUTAL

2

3D039639

50 × 3 + R140LUTAL 71 × 2 + R140LUTAL

3D039649

SkyAir LU Series – Cooling Only –

159


Capacity Tables

ED21-301

60 × 2 + R125LUYAL

3D039640

50 × 3 + R140LUYAL 71 × 2 + R140LUYAL

3D039653

160

SkyAir LU Series – Cooling Only –


ED21-301

Capacity Tables

50 × 4 + R200KUTAL / YAL 71 × 3 + R200KUTAL / YAL 100 × 2 + R200KUTAL / YAL

2

3D030167A

60 × 4 + R250KUTAL / YAL 125 × 2 + R250KUTAL / YAL

3D030169A

SkyAir LU Series – Cooling Only –

161


Capacity Tables

8.3

ED21-301

Capacity Correction Factor by The Length of Refrigerant Piping The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit) Reference Data 1. In case of piping length 5m

Cooling capacity correction factor

100

95

90 200 100, 250 71 125

85

80 140 75

0

5

10

30 35 15 20 25 Length of refrigerant piping (Total length)

40

45

50 (m) (S0028)

2. In case of piping length 7.5m

Cooling capacity correction factor

100

95

90

85

200 100, 250 71 125

80

140

75

Note:

162

0

5

7.5 10

30 35 15 20 25 Length of refrigerant piping (Total length)

40

45

50 (m)

1. line: Correction factor for cooling capacity 2. The correction factor remains the same whether the outdoor unit is to be installed above or below the indoor unit. 3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the range of its limitation.

SkyAir LU Series – Cooling Only –


ED21-301

Operation Limits

9. Operation Limits 9.1

Operation Limits

R71LUV1 / R71LUY1 R100LUV1 / R100LUY1 R125LUY1 R140LUY1 R71LUVAL R100LUVAL R125LUTAL / R125LUYAL R140LUTAL / R140LUYAL

2

3D039657

R200KUY1 R250KUY1

R200KUTAL / R200KUYAL R250KUTAL / R200KUYAL

3D030170

Notes:

The graphs are based on the following conditions. Equivalent piping length 5m Level difference 0m Air flow rate High

SkyAir LU Series – Cooling Only –

163


Sound Level

ED21-301

10. Sound Level 10.1

Overall Sound Level dB(A) Model

50Hz

60Hz

220V

240V

Measuring Location

220V

H

L

H

L

H

L

FHYC35K FHYC50K FHYC60K FHYC71K FHYC100K FHYC125K

33 33 35 35 39 42

29 29 30 30 34 36

35 35 37 37 41 44

31 31 32 32 36 38

33 33 35 35 39 42

29 29 30 30 34 36

FHYC

FHY35B FHY50B FHY60B FHY71B FHY100B FHY125B

37 38 38 39 42 44

32 33 33 35 37 39

37 38 38 39 42 44

32 33 33 35 37 39

37 38 38 39 42 44

32 33 33 35 37 39

FHY

50Hz 380V

50Hz 415V

60Hz 220V

R71LU R100LU R125LU R140LU R125LUTAL R140LUTAL

48 49 49 54 — —

49 50 50 55 — —

49 51 — — 51 55

R125LUYAL R140LUYAL

— —

— —

51 55

50Hz 380V

50Hz 415V

60Hz 220 · 380V

60 61

61 62

60 61

Microphone

4D028280A

R71~140LU

Microphone

60Hz 380V

R200 R250

4D039806

R200KU / R250KU

Microphone

4D030106

Note:

164

Operation sound is measured in an anechoic chamber.

SkyAir LU Series – Cooling Only –


ED21-301

10.2

Sound Level

Octave Band Level

10.2.1 Indoor Units FHYC35KVE FHYC50KVE

FHYC60KVE FHYC71KVE

FHYC100KVE

2 H H

L L

4D006198A

FHYC125KVE

FHY35BVE

FHY50BVE

4D028280A

FHY60BVE

FHY71BVE

4D028282

4D028281A

FHY100BVE

4D028355

4D028283

FHY125BVE

4D028284

SkyAir LU Series – Cooling Only –

165


Sound Level

ED21-301

10.2.2 Outdoor Units R71LUV1 / R71LUY1

R100LUV1 / R100LUY1

4D039802

R140LUY1

4D039804

R71LUVAL

4D039808

R125LUTAL / R125LUYAL

166

4D039806

R100LUVAL

4D039810

R140LUTAL / R140LUYAL

4D039812

R250KUY1

R125LUY1

4D039811

R200KUY1

4D039813

R200KUTAL / R200KUYAL

R250KUTAL / R250KUYAL

SkyAir LU Series – Cooling Only –


ED21-301

Electric Characteristics

11. Electric Characteristics 11.1

50Hz Unit combination Indoor

FHYC35KVE×2 R71LUV1 FHY35BVE×2

R71LUV1

FHYC35KVE×2 R71LUY1 FHY35BVE×2

R71LUY1

FHYC50KVE×2 R100LUV1 FHY50BVE×2

R100LUV1

FHYC50KVE×2 R100LUY1 FHY50BVE×2

R100LUY1

FHYC60KVE×2 R125LUY1 FHY60BVE×2

Power supply

Outdoor

R125LUY1

Hz-Volts 50-220 50-230 50-240 50-220 50-230 50-240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-220 50-230 50-240 50-220 50-230 50-240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240

Comp

Voltage range MCA TOCA MFA 19.6

23.8

30

19.2

23.8

30

Max. 50Hz 456/264V

8.3

9.3

15

Min. 50Hz 342/198V

8.3

9.3

15

24.9

28.0

40

24.9

28.0

40

Max. 50Hz 456/264V

10.4

12.0

15

Min. 50Hz 342/198V

10.4

12.0

15

Max. 50Hz 456/264V

12.8

15.5

20

Min. 50Hz 342/198V

12.8

15.5

20

Max. 50Hz 264V Min. 50Hz 198V

Max. 50Hz 264V Min. 50Hz 198V

LRA

RLA

82 78 75 82 78 75 40 38 37 40 38 37 114 109 105 114 109 105 50 48 46 50 48 46 51 53 56 51 53 56

14.2 13.6 13.0 14.2 13.6 13.0 5.2 4.9 4.7 5.2 4.9 4.7 18.3 17.5 16.7 18.3 17.5 16.7 6.7 6.4 6.1 6.7 6.4 6.1 8.1 8.1 8.2 8.1 8.1 8.2

OFM kW

FLA

IFM kW

FLA

0.065

0.6

0.045×2 0.6×2

0.065

0.6

0.062×2 0.6×2

0.065

0.6

0.045×2 0.6×2

0.065

0.6

0.062×2 0.6×2

0.09

0.8

0.045×2 0.6×2

0.09

0.8

0.062×2 0.6×2

0.09

0.8

0.045×2 0.6×2

0.09

0.8

0.062×2 0.6×2

0.065 + 0.085 0.065 + 0.085

0.6 + 0.7 0.6 + 0.7

2

0.045×2 0.6×2 0.062×2 0.6×2 3D039580

Unit combination Indoor

Outdoor

FHYC50KVE×3 R140LUY1 FHYC71KVE×2 R140LUY1 FHY50BVE×3 FHY71BVE×2

Power supply

R140LUY1 R140LUY1

Hz-Volts 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240

Comp

Voltage range MCA TOCA MFA

Max. 50Hz 456/264V

13.8

18.2

25

13.2

17.6

25

13.8

18.2

25

13.2

17.6

25

Min. 50Hz 342/198V

LRA

RLA

67 71 74 67 71 74 67 71 74 67 71 74

8.2 8.2 8.5 8.2 8.2 8.5 8.2 8.2 8.5 8.2 8.2 8.5

OFM kW 0.065 + 0.090 0.065 + 0.090 0.065 + 0.090 0.065 + 0.090

FLA 0.6 + 0.8 0.6 + 0.8 0.6 + 0.8 0.6 + 0.8

IFM kW

FLA

0.045×3 0.6×3 0.045×2 0.6×2 0.062×3 0.6×3 0.062×2 0.6×2 3D039580

Unit combination Indoor

FHYC100KVE×2 R200KUY1 FHY100BVE×2

R200KUY1

FHYC71KVE×3 R200KUY1 FHY71BVE×3

R200KUY1

FHYC50KVE×4 R200KUY1 FHY50BVE×4

R200KUY1

FHYC125KVE×2 R250KUY1 FHY125BVE×2

R250KUY1

FHYC60KVE×4 R250KUY1 FHY60BVE×4

Power supply

Outdoor

R250KUY1

Hz-Volts 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240 50-380/220 50-400/230 50-415/240

Comp

Voltage range MCA TOCA MFA 20.8

22.5

30

20.2

21.9

30

Max. 50Hz 456/264V

20.6

22.3

30

Min. 50Hz 342/198V

20.6

22.3

30

21.2

22.9

30

21.2

22.9

30

26.0

28.5

40

Max. 50Hz 456/264V

25.4

27.9

40

Min. 50Hz 342/198V

26.4

28.9

40

26.4

28.9

40

LRA

RLA

87 92 95 87 92 95 87 92 95 87 92 95 87 92 95 87 92 95 128 135 140 128 135 140 128 135 140 128 135 140

12.6 12.4 13.0 12.6 12.4 13.0 12.6 12.4 13.0 12.6 12.4 13.0 12.6 12.4 13.0 12.6 12.4 13.0 16.3 15.7 17.2 16.3 15.7 17.2 16.3 15.7 17.2 16.3 15.7 17.2

OFM kW 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19

FLA 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2 1.3 + 1.2

IFM kW

FLA

0.090×2 1.0×2 0.130×2 0.7×2 0.045×3 0.6×3 0.062×3 0.6×3 0.045×4 0.6×4 0.062×4 0.6×4 0.090×2 1.0×2 0.130×2 0.7×2 0.045×4 0.6×4 0.062×4 0.7×4 3D029999A 3D030000A

SkyAir LU Series – Cooling Only –

167


Electric Characteristics

11.2

ED21-301

60Hz Unit combination Indoor

Outdoor

Power supply Hz-Volts

Comp

Voltage range MCA TOCA MFA

OFM

LRA

RLA

kW

FLA

IFM kW

FLA

FHYC35KVE×2 R71LUVAL

60-220

21.1

24.0

30

99

15.3

0.075

0.8

0.045×2 0.6×2

FHY35BVE×2

60-220

21.3

24.0

30

99

15.3

0.075

0.8

0.062×2 0.7×2

25.7

28.1

40

143

18.9

0.1

0.9

0.045×2 0.6×2

25.9

28.3

40

143

18.9

0.1

0.9

0.062×2 0.7×2

0.075 + 0.095 0.075 + 0.095 0.075

0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9

R71LUVAL

FHYC50KVE×2 R100LUVAL

60-220

FHY50BVE×2

R100LUVAL

60-220

FHYC60KVE×2 R125LUTAL

60-220

23.3

24.5

30

137

16.3

FHY60BVE×2

R125LUTAL

60-220

23.5

24.7

30

137

16.3

FHYC60KVE×2 R125LUYAL

60-380

14.4

15.5

20

66

9.2

FHY60BVE×2

60-380

14.6

15.7

20

66

9.2

R125LUYAL

Max. 60Hz 242V Min. 60Hz 198V

Max. 60Hz 418V Min. 60Hz 342V

+

0.095 0.075 +

0.095

0.045×2 0.6×2 0.062×2 0.7×2 0.045×2 0.6×2 0.062×2 0.7×2 3D039581

Unit combination Indoor

Outdoor

Power supply Hz-Volts

Comp

Voltage range MCA TOCA MFA

LRA

RLA

OFM

23.6

31.8

40

146

15.8

23.6

31.8

40

146

15.8

22.9

31.1

40

146

15.8

60-220

22.9

31.1

40

146

15.8

FHYC50KVE×3 R140LUYAL

60-380

14.7

18.8

25

75

8.7

FHY50BVE×3

R140LUYAL

60-380

14.7

18.8

25

75

8.7

FHYC71KVE×2 R140LUYAL

60-380

14.0

18.1

25

75

8.7

FHY71BVE×2

60-380

14.0

18.1

25

75

8.7

FHYC50KVE×3 R140LUTAL

60-220

FHY50BVE×3

R140LUTAL

60-220

FHYC71KVE×2 R140LUTAL

60-220

FHY71BVE×2

R140LUTAL

R140LUYAL

Max. 60Hz 242V Min. 60Hz 198V

Max. 60Hz 418V Min. 60Hz 342V

kW 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100 0.075 + 0.100

FLA 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9 0.8 + 0.9

IFM kW

FLA

0.045×3 0.7×3 0.062×3 0.7×3 0.045×2 0.7×2 0.062×2 0.7×2 0.045×3 0.7×3 0.062×3 0.7×3 0.045×2 0.7×2 0.062×2 0.7×2 3D039581

168

SkyAir LU Series – Cooling Only –


ED21-301

Electric Characteristics

Unit combination Indoor

Power supply

Outdoor

Hz-Volts

Comp

Voltage range MCA TOCA MFA

LRA

RLA

FHYC50KVE×4 R200KUTAL

60-220

35.5

39.2

50

161

23.4

FHY50BVE×4

R200KUTAL

60-220

35.5

39.2

50

161

23.4

FHYC71KVE×3 R200KUTAL

60-220

Max. 60Hz 242V 34.8

38.5

50

161

23.4

Min. 60Hz 198V

R200KUTAL

60-220

34.8

38.5

50

161

23.4

FHYC100KVE×2 R200KUTAL

60-220

34.7

38.4

50

161

23.4

FHY100BVE×2

60-220

34.7

38.4

50

161

23.4

FHYC50KVE×4 R200KUYAL

60-380/220

23.2

24.2

30

81

13.6

FHY50BVE×4

60-380/220

23.2

24.2

30

81

13.6

60-380/220 Max. 60Hz 418/242V

22.5

23.5

30

81

13.6

Min. 60Hz 342/198V

22.5

23.5

30

81

13.6

FHY71BVE×3

R200KUTAL

R200KUYAL

FHYC71KVE×3 R200KUYAL R200KUYAL

60-380/220

FHYC100KVE×2 R200KUYAL

60-380/220

22.4

23.4

30

81

13.6

FHY100BVE×2

60-380/220

22.4

23.4

30

81

13.6

FHYC60KVE×4 R250KUTAL

60-220

41.1

52.2

60

225

27.9

FHY60BVE×4

R250KUTAL

60-220

41.1

52.2

60

225

27.9

FHYC125KVE×2 R250KUTAL

60-220

40.3

51.4

60

225

27.9

FHY125BVE×2

60-220

40.5

51.6

60

225

27.9

FHYC60KVE×4 R250KUYAL

60-380/220

27.8

30.2

40

107

17.3

FHY60BVE×4

60-380/220 Max. 60Hz

27.8

30.2

40

107

17.3

FHY71BVE×3

R200KUYAL

R250KUTAL

R250KUYAL

Max. 60Hz 242V Min. 60Hz 198V

418/242V

FHYC125KVE×2 R250KUYAL

60-380/220 Min. 60Hz 342/198V

27.0

29.4

40

107

17.3

FHY125BVE×2

60-380/220

27.2

29.4

40

107

17.3

R250KUYAL

OFM kW 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19 0.23 + 0.19

FLA 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6 1.8 + 1.6

IFM kW

FLA

0.045×4 0.7×4

2

0.062×4 0.7×4 0.045×3 0.7×3 0.062×3 0.7×3 0.090×2 1.0×2 0.130×2 1.0×2 0.045×4 0.7×4 0.062×4 0.7×4 0.045×3 0.7×3 0.062×3 0.7×3 0.090×2 1.0×2 0.130×2 1.0×2 0.045×4 0.7×4 0.062×4 0.7×4 0.090×2 1.0×2 0.130×2 1.1×2 0.045×4 0.7×4 0.062×4 0.7×4 0.090×2 1.0×2 0.130×2 1.1×2 3D029999A 3D030000A

Symbols:

Notes:

MCA : Min. Circuit Amps TOCA : Total Over-Current Amps MFA : Max. Fuse Amps (See note 7) LRA : Locked Rotor Amps RLA : Rated Load Amps OFM : Outdoor Fan Motor FLA : Full Load Amps IFM : Indoor Fan Motor kW : Fan Motor Rated Output 1. RLA is based on the following conditions. Indoor temp. 27°CDB/19.0°CWB Outdoor temp. 35°CDB 2. TOCA means the total value of each OC set. 3. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the range listed. 4. Maximum allowable voltage unbalance between phases is 2% 5. MCA/MFA MCA = 1.25 × RLA + ea. FLA MFA ≤ 2.25 × RLA + ea. FLA (Next lower standard fuse rating, Min. 15A) 6. Select wire size based on the larger value of MCA or TOCA. 7. MFA Instead of fuse, use circuit breaker.

SkyAir LU Series – Cooling Only –

169


Option List

ED21-301

12. Option List 12.1

LU Series

12.1.1 Indoor Unit FHYC-K Name of Option

Kit Name

Remark

35~71K

100~125K

Decoration Panel

BYC125K-W1

Sealing Member of Air Discharge Outlet

KDBHJ55K160

Panel Spacer

KDBJ55K160W

Fresh Air Intake Kit ∗4 Chamber Type Without T Joint

KDDP55D160

With T Joint

KDDP55D160K

Direct Installation Type High Efficiency Filter Replacement High Efficiency Filter

KDDJ55X160

(Colorimetric Method 65%)

KAFP556D80

KAFP556D160

(Colorimetric Method 90%)

KAFP557D80

KAFP557D160

(Colorimetric Method 65%)

KAFJ552K80

KAFJ552K160

(Colorimetric Method 90%)

KAFJ553K80

KAFJ553K160

High-Efficiency Filter Chamber

KDDFP55D160

Long-Life Filter

KAFJ551K160

Resin Net (Gravimetric Method 50%)

Ultra-Long Life Filter

KAFP55D160

Ultra-Long Life Replacement Filter

KAFJ55K160H

Chamber Connection Kit ∗5

KKSJ55K160

Branch Duct Chamber Remote Controller

KDJ55K80

KDJ55K160

Wired Type ∗3

BRC1C61 (Note. 6)

Wireless Type

BRC7C613W

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302B61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601B51

Adaptor for Wiring (Interlock for Fresh Air Intake Fan) ∗1

KRP1B57

Wiring Adaptor for Electrical Appendices ∗1

KRP4A53

Interface Adaptor for SkyAir Series

DTA102A52

Installation Box for Adaptor PCB

KRP1B98 C:3D006559E

FHY-B Name of Option

Remark

Kit Name 35B

50B

60B

71B

100B

125B

Replacement Long-Life Filter

KAFJ501D56

KAFJ501D80

KAFJ501D112 KAFJ501D160

Drain Pump Kit

KDU50B50VE

KDU50B71VE

KDU50B125VE

L-Type Piping Kit (For Upward Direction) KHFJ5F50 Remote Controller

Wired Type ∗3 Wireless Type

Set Back Time Clock

KHFJ5F60

KHFJ5F80 BRC7E66 BRC15A61

Central Remote Controller

DCS302B61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601B51

Adaptor for Wiring

KRP1B54

Wiring Adaptor for Electrical Appendices ∗2

KRP4A52

Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB

KHFJ5F160

BRC1C61

DTA102A52 KRP1C93 3D028285A

Note:

170

1. 2. 3. 4. 5. 6.

∗1 : Installation box for adaptor PCB (KRP1B98) is necessary. ∗2 : Installation box for adaptor PCB (KRP1C93) is necessary. ∗3 : Wire for remote controller : Field supplied. ∗4 : Refer to the Option Handbook for the detail. ∗5 : When using the filter (High-Efficiency Filter or Ultra-Long Life Filter) and the Fresh Air Intake Kit together, this kit is necessary. BRC1B61 is also available.

SkyAir LU Series – Cooling Only –


ED21-301

Option List

12.1.2 Outdoor Unit (R71~140LU, R200·250KU) Name of Option

Remark

Kit Name R71LU

R100LU

Central Drain Plug Refrigerant Branch Piping

For Twin Multi

KHR58C21

For Triple Multi

R140LU

R200KU

KHD58D33 —

KRK5F80V1

KRK5F140V1

R250KU —

KHD58C21A —

For DoubleTwin Type Year-round Cooling Kit

R125LU

KKPJ5F180 KHD58C23A

KHD58C24A

KHD58D31

KHRJ5F224F KHRJ5F280F KRK5F160V1

— 3D039655 4D029784

SkyAir LU Series – Cooling Only –

171

2


Field Piping and Wiring

ED21-301

13. Field Piping and Wiring 13.1

Field Piping

13.1.1 Maximum Allowable Piping Length and Difference R71~140LU Maximum Allowable Pipe Length [Parenthesized Figure Represents Equivalent Length]

Maximum Allowable Level Difference

50 m (70 m) The total one-way pipe length should be within 60 meters.

30 m The level difference between the indoor units should be 0.5 m.

When connected to two indoor units (simultaneous operation system)

When connected to three indoor units (simultaneous operation system)

Branched pipe (L2)

Branched pipe (L2)

Branched pipe (L3)

Branched pipe (L3) Main pipe (L1) One-way length of pipe (L): L1+L2+L3

Main pipe (L1)

Branched pipe (L4)

One-way length of pipe (L): L1+L2+L3+L4 1PN05248B-1

Allowable Pipe Length The maximum allowable pipe length here means the total length of the main pipe and the branched pipe (the longer one of the two branched pipes). (Refer to the figure above.) R200, 250KU

1PN04787B-1

172

SkyAir LU Series – Cooling Only –


ED21-301

Field Piping and Wiring

2 1PN04787B-2

13.1.2 Additional Refrigerant Charge R71~140LU This unit requires additional charging of refrigerant according to the length of pipe connected at the site. When the entire refrigerant pipe length is within 30 meters, the additional changing is not needed. Take the following steps for proper charging. When connected to two indoor units (simultaneous operation system)

When connected to three indoor units (simultaneous operation system)

Branched pipe (L2)

Branched pipe (L2)

Branched pipe (L3)

Branched pipe (L3) Main pipe (L1)

Main pipe (L1)

One-way length of pipe (L): L1+L2+L3

Branched pipe (L4)

One-way length of pipe (L): L1+L2+L3+L4

1. Refrigerant charge amount Additional charging of refrigerant Select the amount of refrigerant which matches a length which exceeds the charge-less length, and add it. Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear surface of the front plate, as this is necessary for after-sales service.

FOR SIMULTANEOUS OPERATION SYSTEM Find the entire pipe length by totaling that of each pipe in the order of the main pipe (L1), and branched pipes (L2), (L3), (L4), calculate the excess length going over 30 meters, then select from Table 1 the amount of refrigerant corresponding to the excess length. The total value is tha amount required for additional charging. The maximum allowable pipe length is 50 meters. Make the total refrigerant pipe length come within 60 meters. The maximum allowable pipe length here means the total length of the main pipe and the branched pipe (the longer one of the two branched pipes). <unit : kg> Table 1 Pipe excess length over 30 meters

10 m or less Main pipe

Additional charging amount

Liquid pipe

Branched pipe

20 m or less

φ9.5

0.25

0.50

φ9.5

0.25

0.50

φ6.4

0.15

0.30

2. Recharging refrigerant When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the amount mentioned on the nameplate, and when the pipe length exceeds 30 meters, the charging amount is an addition of the amount stated on the nameplate and the additional charging amout. 1PN05248B-2

SkyAir LU Series – Cooling Only –

173


Field Piping and Wiring

ED21-301

R200, 250KU

1PN04788A

Caution to be taken when brazing refrigerant piping “Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”. (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible. (Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g . BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant leakage.

174

SkyAir LU Series – Cooling Only –


ED21-301

13.2

Field Piping and Wiring

Field Wiring

13.2.1 R71LU, 100LU, 125LU, 140LU (V1, Y1, VAL, TAL, YAL)

2

SkyAir LU Series – Cooling Only –

175


Field Piping and Wiring

ED21-301

13.2.2 R200KU, R250KU (Y1, TAL, YAL)

3D029782

176

SkyAir LU Series – Cooling Only –


ED21-301

Detail Information of Options SkyAir LU Series

Note : Refer to VRV Option Handbook (OH02-1) Concerning about the manual for the following Central Control Kits. • Interface Adaptor for SkyAir Series DTA102A52 • Central Remote Controller DCS302B61 • Unified ON/OFF Controller DCS301B61 • Schedule Timer DST301B61

SkyAir LU Series

177

3


Remote Controller

ED21-301

1. Remote Controller 1.1

Remote Controller, Timer, Adaptor List Model Series

Name of Option Wireless Remote Controller

FH(Y)C-K

FH(Y)K-F(J)

FH(Y)B-F

FUY-FJ

FH(Y)-B

FAY71L

FAY100FA

FV(Y)-LA

C/O BRC7C613W

BRC7C529W

BRC7E66

BRC7E619

BRC7C611W

H/P BRC7C612W

BRC7C528W BRC7E63W

BRC7E618

BRC7C610W

C/O Wired

BRC1C61

H/P

— BRC1C61 (Available for 2 remote control use)

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302B61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601B51

Adaptor for Wiring

KRP1B57

KRP1B51

KRP1B54

KRP1B54

KRP1B57

Wiring Adaptor for Electrical Appendicies

KRP4A53∗

KRP4A51

KRP4A51

KRP4A53∗

KRP4A52∗

KRP4A51∗

KRP4A51

KRP4A52∗

Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB

DTA102A52 KRP1B98

— KRP1B97

KRP1C93

KRP4A93

DTA102A52 —

KRP4A95

∗ Installation Box for Adaptor PCB is necessary.

1.2

Wired Remote Controller

BRC1C61 New BRC1C61 {

BRC1B61 ON / OFF Operation with Air Conditioner Independent operation in intermediate { season Ventilation mode change over (Auto / { HRV / Normal) Air flow change over (Auto / High / Low) { Setting of precooling / preheating Setting of fresh-up operation Filter sign display { { : Initial Setting Only (Field setting by well known service person)

178

SkyAir LU Series


ED21-301

Remote Controller

5 12

4

2

1

3 7

hr

C

6 8

hr

NOT AVAILABLE

TEST

9 11 10 13 21

L H

14

3

20 TEST

16

1 2

3

4

19

15

17

18

ON/OFF BUTTON Press the button and the system will start. Press the button again and the system will stop. OPERATION LAMP (RED) The lamp lights up during operation. DISPLAY “ ” (UNDER CENTRALIZED CONTROL) When this display shows, the system is UNDER CENTRALIZED CONTROL. DISPLAY “ ” “ ”“ ”“ ” (VENTILATION/AIR CLEANING) This display shows that the total heat exchange and the air cleaning unit are in operation (These are optional accessories).

5

DISPLAY “ ” “ ” “ ” “ ” “ ” (OPERATION MODE) This display shows the current OPERATION MODE. For cooling only type, “ ” (Auto) and “ ” (Heating) are not installed.

6

DISPLAY “ TEST” (INSPECTION/TEST OPERATION) When the INSPECTION/TEST OPERATION BUTTON is pressed, the display shows the system mode is in. hr

DISPLAY “

” (PROGRAMMED TIME)

22

3PA59583-16Z-1

12

DISPLAY “

” (DEFROST)

NON-FUNCTIONING DISPLAY If that particular function is not available, pressing the button may display the words “NOT AVAILABLE” for a few seconds. When running multiple units simultaneously the 13 “NOT AVAILABLE” message will only be appear if none of the indoor units is equipped with the function. If even one unit is equipped with the function, the display will not appear. 14 15

TIMER MODE START/STOP BUTTON TIMER ON/OFF BUTTON

INSPECTION/TEST OPERATION BUTTON 16 This button is used only by qualified service persons for maintenance purposes. PROGRAMMING TIME BUTTON 17 Use this button for programming “START and/or STOP” time. TEMPERATURE SETTING BUTTON 18 Use this button for SETTING TEMPERATURE. FILTER SIGN RESET BUTTON 19

hr

7

This display shows the PROGRAMMED TIME of the system start or stop. 8

DISPLAY “ ” (SET TEMPERATURE) This display shows the set temperature.

9

DISPLAY “ ” (FAN SPEED) This display shows the set fan speed.

C

DISPLAY “

FAN SPEED CONTROL BUTTON 20 Press this button to select the fan speed, HIGH or LOW, of your choice. OPERATION MODE SELECTOR BUTTON 21 Press this button to select OPERATION MODE. AIR FLOW DIRECTION ADJUST BUTTON 22

” (AIR FLOW FLAP)

10

NOTE

11

• For the sake of explanation, all indications are shown on the display in the above figure contrary to actual running situations.

DISPLAY “

”(TIME TO CLEAN AIR FILTER)

3PA59583-16Z-2

SkyAir LU Series

179


Remote Controller

ED21-301

Installation

180

SkyAir LU Series


ED21-301

Remote Controller

3

SkyAir LU Series

181


Remote Controller

Mode No. Note) 1

FIRST CODE NO.

0

10(20)

1

2

ED21-301

SECOND CODE No. Note) 2 Description of Setting Filter Contamination - Heavy/Light (Setting for spacing time of display time to clean air filter) (Setting for when filter contamination is heavy, and spacing time to clean air filter is to be halved)

01

03

Approx. 5,000 hours

Approx. 1,250 hours

Approx. 100 hours

Long-life filter

Ultra-long-life filter (1)

Use

Not Use

Display

Do Not Display

Pair

Twin

Unified

Individual

Ultra-longlife type Long-life type Standard type

Long-life filter type (Setting of filter sign indication time) (Change setting when Ultra-long-life filter is installed) Remote control thermostat (Set when remote control thermostat sensor is used )

3

Spacing Time of Display Time to Clean Air Filter Count (Setting for when the filter sign is not to be displayed)

0

Setting Number of Connected SkyAir Simultaneous Operation System Indoor Units (Setting for Simultaneous Operation System)

1

Simultaneous operation multi-unit individual setting

11(21)

02

Approx. 10,000 hours Light

Approx. 2,500 hours Approx. 200 hours

Heavy

2

Indoor unit fan OFF when cooling/heating is OFF

Fan OFF

0

High Ceiling Setting (Setting for when installed in a Ceiling higher than 2.7m)

Normal

High Ceiling 1

High Ceiling 2

1

Selection of Air Flow Direction (Setting for when a blocking pad kit has been installed)

F

T

W

Upper

Normal

Lower

13(23) 4

Air Flow Direction Range Setting

Note:

1. Setting is carried out in the group mode, however, set the mode number inside the ( ) for individual setting of the each indoor unit or confirmation after setting. 2. The SECOND CODE number is set to “01” when shipped from the factory. However for the following cases it is set to “02” • Air flow direction range setting. 3. Do not make any settings not given in the table above. 4. Not displayed if the indoor unit is not equipped with that function. 5. When returning to the normal mode, “88” may be displayed in the LCD in order for the remote controller to initialize itself. 2P068938-2

182

SkyAir LU Series


ED21-301

1.3

Remote Controller

Wireless Remote Controller

Names and Function Name of Option

Model Series FH(Y)C-K

FH(Y)K-F(J)

FH(Y)B-F

FUY-FJ

FH(Y)-B

FAY71L

FAY100FA

FV(Y)-LA

BRC7C529W

BRC7E66

BRC7E619

BRC7C611W

BRC7C528W BRC7E63W

BRC7E618

BRC7C610W

C/O BRC7C613W Remote Wireless Controller H/P BRC7C612W

1-1 1 ON OFF

3

1-2 H

M L

DOWN

10

C

ON OFF

UP

6

TEMP

FAN

H

M L TIME

4

11

C

hr.

2

3

8

UP

9

hr.

FAN

DOWN

13

RESERVE CANCEL

hr.

5

TIMER

12

MODE

15

hr.

TEST

7 14

SWING

16

TEST TEST

17

3PA63363-21T-1

Explanation of Receiver FH(Y)C-K

FAY-FA

FAY71L

20

21

19

18

23

22

3P091240-1

FUY-FJ

FH(Y)-B

22

19

21 20

23

18

3PA63363-21T-2

SkyAir LU Series

183


Remote Controller

ED21-301

DISPLAY “ ” (SIGNAL TRANSMISSION) 1 This lights up when a signal is being transmitted. DISPLAY “ ” “ ” “ ”“ “ ” (OPERATION MODE)

3

4

H

M L

C

” (SET TEMPERATURE)

6

7

8

9

10

11

12

AIR FLOW DIRECTION ADJUST 14 BUTTON

15

16

This display shows the set temperature. hr. DISPLAY “ hr. ” (PROGRAMMED TIME)

This display shows PROGRAMMED TIME of the system start or stop. 5

DISPLAY “

TIMER RESERVE/CANCEL BUTTON

2 This display shows the current OPERATION MODE. For straight cooling type, “ ” (Auto) and “ ” (Heating) are not installed. DISPLAY “

13

17

18

” (AIR FLOW FLAP)

DISPLAY “ ”“ ” (FAN SPEED) The display shows the set fan speed. TEST ” DISPLAY “ (INSPECTION/ TEST OPERATION) When the INSPECTION/TEST OPERATION BUTTON is pressed, the display shows the system mode is in. ON/OFF BUTTON Press the button and the system will start. Press the button again and the system will stop. FAN SPEED CONTROL BUTTON Press this button to select the fan speed, HIGH or LOW, of your choice. TEMPERATURE SETTING BUTTON Use this button for SETTING TEMPERATURE. (Operates with the front cover of the remote controller closed.) PROGRAMMING TIMER BUTTON Use this button for programming “START and/or STOP” time. (Operates with the front cover of the remote controller opened.) TIMER MODE START/STOP BUTTON

19

20

21

22

23

OPERATION MODE SELECTOR BUTTON Press this button to select OPERATION MODE. FILTER SIGN RESET BUTTON Refer to the section of MAINTENANCE in the operation manual attached to the indoor unit. INSPECTION/TEST OPERATION BUTTON This button is used only by qualified service persons for maintenance purposes. EMERGENCY OPERATION SWITCH This switch is readily used if the remote controller does not work. RECEIVER This receives the signals from the remote controller. OPERATING INDICATOR LAMP (Red) This lamp stays lit while the air conditioner runs. It flashes when the unit is in trouble. TIMER INDICATOR LAMP (Green) This lamp stays lit while the timer is set . AIR FILTER CLEANING TIME INDICATOR LAMP (Red) Lights up when it is time to clean the air filter. DEFROST LAMP (Orange) Lights up when the defrosting operation has started. (For straight cooling type this lamp does not turn on.)

3PA63363-21T-3

184

SkyAir LU Series


SkyAir LU Series

Control by Remote Controller.

For the control of plural indoor units on a floor at the same time

For above control from distant place.

Operation of other equipment combined with the operation of indoor unit

Group control

Group control by 2 remote controllers

Combining control by remote controller

Note 1

BRC1C61

Unit Name and Model Outline of System

Operates HRV in accordance with indoor unit operation.

Operational functions Start/Stop (ON/OFF) Temperature setting Timer setting (Settings in units of 1 hour up to a maximum of 72 hours) Air flow setting Air flow direction adjustment (Swing flap) Indication function Operating display Program dry function display Defrost/Hot start display Filter sign Temperature setting display Timer display Air flow display Abnormal operation display ∗ In case of group control all the indoor units in the system are set to the same value and each unit is controlled individually by its internal thermostat. (Not by the thermostat equipped in remote controller) ∗ In command by double remote controls, the most recent one takes priority. (Selection between master and slave controller is essential) ∗ According to indoor unit’s model, some models cannot be set.

Function

Same as the number of units controlled by remote controller

2 remote controllers control up to 16 indoor units from 2 different places simultaneously

1 remote controller controls up to 16 indoor units simultaneously

2 remote controllers control 1 indoor unit

1 remote controller controls 1 indoor unit

Standard Number of Units

(S1015)

Note: 1. These figures above show the system using wired remote controllers. Wireless remote controller replaced for wired remote controller can be used for same control. 2. In control by two remote controllers, one of two remote controllers must be a wired remote controller. Two wireless remote controllers must not be used. 3. Wiring from a wireless remote controller to the receiver can be lengthened to 200m in maximum.

For control from 2 places (distant or local)

For control from distant place

Remote operation of remote controller

2 remote control Note 2

Example of typical use

Objective / Use

1.4

Local operation of remote controller

Control Method

ED21-301 Remote Controller

Various Control by Liquid Crystal Remote Controller For more effective localized environmental control Daikin offers various control systems such as single or double remote control or centralized control. This enables the construction of a variety of operational control systems which can be adapted for various uses from remote control.

3

185


Set-back Time Clock

Desired Weekly Scheduled Operation of ON/ OFF and Temperature's Set-back

BRC15A61

186 Set-back time clock

Set-back time clock

Remote controller

Remote controller

∗ Be sure to provide a master remote controller. This scheduled operation cannot be used in both cases at control by two remote controllers and at the connection of a group remote control adapter.

Display function Effective/ineffective control on the program The present time and the week day Daylight-saving time setting Setting holidays in a week Display of operation mode(heating/cooling) Usual setting temperature (Cooling/Heating is linked to a remote controller) ON/OFF time setting for a day Set-back time setting for a day

Control function Effective/ineffective control on the program Daylight-saving time The present time adjustment Weekly operation time program (two times a day in max. frequency by a unit of 30 min.) Weekly set-back operation time program (two times a day in max. frequency by a unit of 30 min.) Program of setting temperature for normal/set-back control (each one kind for cooling and heating . The operation mode is linked to the remotecontroller). Elimination of the time in an operation of a day and a setback operation.

Max. 16 groups under simultaneous control by one set-back time clock

One indoor unit control by one set-back time clock

(S1018)

Remote Controller ED21-301

SkyAir LU Series

Scheduled Control


SkyAir LU Series

Adaptor for connection with optional controllers for centralized control

Schedule timer Central remote controller Unified ON/ OFF controller

Unified ON/OFF controller

Central remote controller

Schedule timer

For controlling all indoor units from one place

For carrying out weekly schedule operation by 1-minute units

Interface adaptor for SkyAir series DTA102A52

DCS301B61

DCS302B61

DST301B61

DCS301B61

DCS302B61

DST301B61

Controls up to 64 groups of indoor units with one central remote controller.

Controls up to 16 groups of indoor units with one unified ON/ OFF controller.

Controls up to128 groups (Max. 128 indoor units) with one schedule timer, two central remote controller and eight unified ON/OFF controllers.

Double central control function Function of liquid crystal remote controller can be controlled individually for each zone of the indoor unit. Individual/unified operation Up to 8 patterns can be set for operation controlled by programmed time when used in combination with schedule timer. Temperature setting for each zone Control operation for each room during centralized control Remote controller operation rejected command Sequential start function Double central control function Indoor unit ON/OFF control Individual/unified operation Remote controller operation rejected command (Central remote controller given priority when used in combination with central remote controller.) Sequential start function

Respective functions of schedule timer, central remote controller and unified ON/OFF controller are possible. (Control mode of central remote controller is given priority for operation of remote controller for indoor unit.)

Unification adaptor for computerized control allows you to simultaneously turn indoor units connected to the central remote controller on or off or display at the central monitor panel, etc. Interface adaptor for SkyAir series is for connection of optional controllers for centralized control.

Simultaneously controls 128 groups with one schedule timer.

ON/OFF time can be set by units of day, hour and minute; ON/OFF pattern can be set by time zone of twice per day in accordance with application.

(S1016)

ED21-301 Remote Controller

3

187

Central Control


For control by operation command from building control room

Wiring adaptor for electrical appendices

Adaptor for wiring

When controlling operation with optional accessories added inside indoor units, the status is displayed outside.

Objective / Use

Remote Control

Wiring Modification

188

Control Method

Built into indoor unit KRP1B51·54· 57

KRP4A51·52· 53·54 Built into indoor unit

With remote temperature setting

Unit Name and Model

Group Unified Control (Controls group controlled indoor units all at once and simultaneously.)

Individual Control (Controls Indoor Units Individually.)

Outline of System

Operation display signal and compressor operation signal are supplied.

For group unified control, the setting becomes the same for all connected indoor units, and each indoor unit is controlled individually by built-in thermostat.

1 adaptor controls the electric heater.

1 PC board simultaneously controls 16 group of indoor units.

1 PC board controls 1 indoor unit.

Normally open or momentary open type contactor DC12~24V or no-voltage Various control methods available by mode select switch Voltage, no-voltage selector switch Alarm and operation display signal (no-voltage) Selector switch of zone/individual of alarm display Remote temperature setting (resistance input of 0~135Ω) Selector switch for remote controller temperature setting enable/inhibit ∗

Standard Number of Units

Function

(S1017)

Remote Controller ED21-301

SkyAir LU Series


ED21-301

1.5

Remote Controller

BRC15A61 – Set Back Time Clock

Installation

„ Connected to a wired remote controller, this timer can set 2 sets of ON/OFF times in an increment of 30 minutes within a day. For each ON/OFF setting a temperature setting is also possible.

3

SkyAir LU Series

189


Remote Controller

ED21-301

SPECIFICATIONS Display of time

12-hour digital display

Clock cycle type

Quartz clock type

Clock accuracy

Within ± 30 sec./month (environmental temperature from 15°C to 35°C)

Timer programming

Two pairs of programmed time for both system start and system off can be set in units of 30 minutes.

Power failure compensation time

Approximately 1 hour for a single occurrence of power failure (clock with No. of programmed time)

Size

120(W)×120(H)×17(D) mm (Width/Height/Depth)

OUTLINE DRAWINGS

120

MON TUE WED THU FRI SAT SUN

PROGRAM OFF OFF OFF OFF OFF OFF OFF

SUMMER TIME

AM PM

MON TUE WED THU FRI SAT SUN CLOCK

0 2 4 6 8 10 12 14 16 18 20 22 24

ON/OFF

˚C ˚C 0 2 4 6 8 10 12 14 16 18 20 22 24

PROGRAM

ON/OFF SET BACK

OK

DAY OF THE WEEK

CLOCK

DAY OFF

SUMMER TIME

120

SET BACK

CLEAR

Specifications and appearance subject to change without notice. About the remote controller which can connect set back time clock (BRC15A61) Wired Remote Controller

Set Back Time Clock

Indoor Unit

Although Set Back Time Clock is connected with Wired Remote Controller in parallel with Series Method, it does not applied to remote control of those other than the following. Model

Remarks

BRC1A51 BRC1A52 BRC1A61 BRC1A62 BRC8A61 ARC11A52 ARC11A54

Only EC9721 the printed Circuit Board currently used for these remote control. (Refer to Note 1)

BRC1B51 BRC1B52 BRC1B61 BRC1B62

Applied for all printed circuit boards.

BRC1C61 BRC1C51

Applied for all printed circuit boards.

Note 1) The check method of printed circuit boards' model No. The rear face of the remote control after removing a back cover Printed Circuit Board

EC9721

190

Printed circuit boards' model No. is indicated at the lower left of the PC board which can be looked at when the back cover of remote controller is removed.

Printed Circuit Boards' The product start of EC9721 was carried out after Model No. 1997.

SkyAir LU Series


ED21-301

Remote Controller

Names and Functions

Fig. 1 12

5

Fig. 2 4

2

1

15

20

PROGRAM

17

DAY OF THE WEEK

CLOCK

DAY OFF

SUMMER TIME

13

14 MON TUE WED THU FRI SAT SUN

PROGRAM

6

OFF OFF OFF OFF OFF OFF OFF

SUMMER TIME

MON TUE WED THU FRI SAT SUN CLOCK

7

ON/OFF

8

SET BACK

3

AM PM

ON/OFF SET BACK

OK

21

19

0 2 4 6 8 10 12 14 16 18 20 22 24

10 11

˚C ˚C 0 2 4 6 8 10 12 14 16 18 20 22 24

CLEAR

3

23

9 PROGRAM

ON/OFF SET BACK

OK

DAY OF THE WEEK

CLOCK

DAY OFF

SUMMER TIME

16

22

18

CLEAR

NAMES AND FUNCTIONS OF OPERATING SECTION (Fig.1,2)

1

ON/OFF BUTTON

DISPLAY “

Press this button to make the program start/stop and the set back time schedule active. Press the button again to make them inactive.

(SET BACK TIME SCHEDULE)

11

The lamp turns on when the schedule function becomes active.

DISPLAY “

MON TUE WED THU FRI SAT SUN CLOCK

3

AM PM

12

13

4

SUMMER TIME

PROGRAMMING START BUTTON

” (SUMMER

14

This display shows the clock indicates summer time.

5

DISPLAY “ PROGRAM ” (PROGRAMMING START)

6

7

8

OFF

” (DAY OFF SETTING)

Lights above the day of the week set as day off. The operation controlled by timer is not available on that day.

17 18

This display shows the set temperature at normal operation time.

19

DISPLAY “ SET BACK ˚C ” (SET TEMPERATURE SET BACK OPERATION TIME)

20

10

This display shows the programmed normal operation time.

SkyAir LU Series

DAYS OFF SET BUTTON

SUMMER TIME SET BUTTON Press this button to change clock to summer time. Press it again to return to standard time.

TEMPERATURE SET BUTTON Press this button to adjust the temperature.

ON/OFF OR SET BACK MODE SELECT BUTTON

21

This display shows the current SELECT MODE (Cool/Heat) when setting temperature.

DISPLAY “ (OPERATION TIME SCHEDULE)

DAYS OF A WEEK SELECT BUTTON

Press this button to set days off.

” (SELECT MODE)

0 2 4 6 8 10 12 14 16 18 20 22 24

Press this button to finish setting the present time and the programmed time.

Press this button to select the day of the week.

This display shows the set temperature at set back operation time.

9

Press this button to adjust the present time and the programmed time.

SETTING FINISH BUTTON

16

DISPLAY “ ON/OFF ˚C ” (SET TEMPERATURE NORMAL OPERATION TIME)

DISPLAY “

Press this button to set the programmed time. Press it again after you are through with the program.

TIME ADJUST BUTTON

15

The light turns on when the timer is programmed.

DISPLAY “

CLOCK ADJUST BUTTON Press this button to set the present time.

Displays the present day of the week and time.

DISPLAY “ TIME)

DISPLAY “ ” (UNDER CENTRALIZED CONTROL) When this display shows, the system is UNDER CENTRALIZED CONTROL.

” (PRESENT

TIME)

This display shows the programmed set back operation time.

OPERATION LAMP (RED)

2

0 2 4 6 8 10 12 14 16 18 20 22 24

Press this button to select ON/OFF or SET BACK mode when setting the programmed time and temperature.

COOL/HEAT SELECT BUTTON

22

23

Press this button to select COOLING or HEATING when setting temperature at set back.

PROGRAM CLEAR BUTTON Press this button to clear the programmed time.

191


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301

2. Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C] 2.1

BYC125K – W1 – Decoration Panel

BEFORE INSTALLATION PRECAUTIONS • Refer also to the installation manual attached to the indoor unit. ACCESSORIES • Installation manual. NOTE TO INSTALLER Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.

PREPARATION OF DECORATION PANEL <<For this unit, you are able to select air flow directions. To discharge air in 2 or 3 directions, it is necessary to purchase optional blocking pad kit.>> HANDLING OF DECORATION PANELS • Never place the panel facing down nor lean it against a wall nor leave it on a projecting object. • Never touch or put pressure on the swing flap. (The swing flap may malfunction.) (1) Remove the suction grille from the decoration panel. 1) Push the suction grille lever inward and lift up the lever side. (Refer to Fig. 1.)

2) Detach the suction grille from the decoration panel by lifting the grille up approximately 45 degrees. (Refer to Fig. 2.)

45˚ Lever

Fig. 1 (2) Remove the service cover on the corner. Slide the service cover outward to remove. (Refer to Fig. 3.)

Fig. 2

Fig. 3

192

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

INSTALLATION OF THE DECORATION PANEL TO THE INDOOR UNIT BODY <<Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.>> (1) Set the decoration panel to the indoor unit body by matching the position of the swing flap motor of the decoration panel to the piping position of the indoor unit as shown in Fig. 4. (2) Install the decoration panel. 1) Temporarily install the decoration panel to the indoor unit by hanging the latch on the opposite side of the swing flap motor of the decoration panel to the hook of the indoor unit body. (2 positions) 2) Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit. (Be careful not to let the swing motor lead wire get caught in the sealing material.) 3) Screw all 4 hexagon head screws located right beneath the latches in approximately 5 mm. (Panel will rise.) 4) Adjust the decoration panel by turning it to the arrowed direction in Fig. 4 so that the ceiling opening is completely covered. 5) Tighten the screws until the thickness of the sealing material between the decoration panel and the indoor unit body reduces to 5–8 mm. Sealing material Indoor unit

3

Ceiling material 5 ~ 8 mm

Decoration panel

Air outlet

Hook

1)

Latch

2) Piping position

2)

Swing flap motor 3)

4)

Fig. 4 PRECAUTIONS • Improper screwing of the screws may cause the troubles shown in Fig. 5. Screw properly.

Air leak

Air leak from ceiling

Contamination

Dew formation, dew dripping Fig. 5

SkyAir LU Series

193


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301

• If gap is still left between the ceiling and the decoration panel after screwing the screws, readjust the indoor unit body height. (Refer to Fig. 6.)

Adjustment of the indoor unit body height from the holes in the corner of the decoration panel is possible if the indoor unit is kept leveled and the drain piping, etc. is unaffected.

No gaps is allowed Fig. 6 (3) Wiring of the decoration panel (Refer to Fig. 7.) 6) Connect the connectors for swing flap motor lead wire installed on the decoration panel. If connectors are not connected, the malfunction display (A7) appears on the remote controller. Connect the connectors properly. Make sure that the swing flap motor lead wire is not caught between the indoor unit and the decoration panel.

6) Indoor unit side

Decoration panel side

áWiring

Fig. 7

Instruction Diagramñ (It differs from the actual state.)

INSTALLATION OF SUCTION GRILLE AND SERVICE COVER (1) Install the suction grille. Install by reversing the procedure shown in “PREPARATION OF DECORATION PANEL”. It is possible to install the suction grille in 4 directions by turning the suction grille. Change the direction when adjusting the direction of the suction grille of multiple units or in meeting customers’ demands. NOTE) Be careful not to get swing flap motor lead wire get caught when installing the suction grille. (2) Install the service cover on the corner. 1) Attach the string of the service cover to the pin of the decoration panel as in Fig. 8.

2) Install the service cover over the decoration panel.

Pin

Install the service cover by sliding 4 latches to fit into the holes on the decoration panel.

Fig. 8

194

SkyAir LU Series


ED21-301

2.2

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

KDBHJ55K160 – Sealing member of air discharge outlet

Caution zRefer to the installation manual for both indoor unit and the decoration panel. zWhen you install other optional kit, it may not be possible to select the 3-way or 2-way air discharge. For details, refer to the manual for the optional kit or the catalogue. zContents of Kit Prior to installation make sure you have the complete kit of parts. Name

Sealing material(A)

Sealing material(B)

Sealing material(C)

Sealing material(D)

Quantity

1 piece

1 piece

1 piece

1 piece

Shape and marking

Name Quantity

3 Insulation for top plate 1 piece

1 piece

Insulation for side plate 1 piece

2 pieces

1 piece

Moisture absorber for bell-mouth

2 pieces

1 piece

Moisture absorber for horizontal vane

5 kinds

Shape and marking

SkyAir LU Series

195


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

3

ED21-301

Installation of the insulation

(1) Installation to the side plate Adhere insulation for side plate

to the side of indoor unit. 140 class

71 class

Put the wire through the slit of the insulation.

(2) Installation to the top plate Adhere insulation for top plate

When adhering insulation, align its edge with the bottom line of casing.

When adhering insulation, align its edge with the bottom line of casing.

,

to the top of the indoor unit.

(3) Adhere the moisture absorber for horizontal vane to the edge of the horizontal vane of air outlet (Fig. 2). (Choose the same color as panel.) Horizontal vane Moisture absorber for horizontal vane Fig. 2

Align it with the upper edge of horizontal vane. Horizontal vane Moisture absorber for horizontal vane

Fig. 1

(4) Adhere the moisture absorber in accordance with the reference surface without wrinkles. (Fig. 4) Adhere the moisture absorber in accordance with the reference line . (Fig. 5) Reference surface Swing connector Swing motor

(Fig. 3)

Sticking reference

Adhere it from the edge of switch box. Switch box

Bellmouth

Sticking reference Fig. 4

Fig. 5 J : 1P012222B

196

SkyAir LU Series


ED21-301

2.3

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

KDBJ55K160W – Panel spacer

3

SkyAir LU Series

197


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

198

ED21-301

SkyAir LU Series


ED21-301

2.4

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

KDDP55D160(K) – Fresh Air Intake Kit

SkyAir

FH(Y)C35~140K

3

71

290

C : 3K011144-1-1

SkyAir LU Series

199


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301

C : 3K011144-1-2

200

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

3

SkyAir LU Series

201


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.5

ED21-301

KDDJ55X160 – Fresh Air Intake Kit

The fresh air is taken into the unit by the indoor unit fan or duct fan, which is field supplied. The location of fresh air intake port will be changeable by installing the duct fan.

KDDJ55X160

1

2P066796B-1

202

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

3

2

2P066796B-2

SkyAir LU Series

203


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.6

ED21-301

KAFP556D80 · 160 – High Efficiency Filter (Including Filter Chamber) KAFP557D80 · 160 – High Efficiency Filter (Including Filter Chamber) Combination table

2.7

High Efficiency Filter (Set)

High Efficiency Filter

KAFP556D80 KAFP557D80

KAFJ552K80 KAFJ553K80

KAFP556D160 KAFP557D160

KAFJ552K160 KAFJ553K160

Filter Chamber KDDFP55D160

KAFJ552K80 · 160 – High Efficiency Filter (Replacement) KAFJ553K80 · 160 – High Efficiency Filter (Replacement) Specifications High Efficiency Filter (Replacement) KAFJ552K80

KAFJ552K160

Filter Chamber

KAFJ553K80

KAFJ553K160

KDDFP55D160

Collecting Efficiency (%)

65% (NBS Calorimetric method)

90% (NBS Calorimetric method)

Initial Pressure Loss (Pa)

34

44

Final Pressure Loss (Pa)

78

98

Filter

Non-woven Fabric of Synthetic Fiber Non-woven Fabric of Synthetic Fiber 2,500 (Dust Concentration 0.15 mg / m3)

Life (h) Models to be Applied

35~71K Model

1,800 (Dust Concentration 0.15 mg / m3)

100~140K Model 35~71K Model

100~140K Model

Precaution at use 1. The high efficiency filter, and the other filter can not be installed together. 2. The unit should be operated with 4-way dischange when the high efficiency filter is installed. It can not be applied to the high ceiling room. 3. Field setting by remote controller is necessary when the high efficiency filter is installed.

Dimension

2.8

Model

A

KAFJ552K80, 553K80

25

KAFJ552K160, 553K160

45

KRP1B98 – Installation Box for Adaptor PCB

Dimension

Model No. Item Applicable Model Adaptor for Wiring

204

KRP1B98 FH(Y)C35~140K KRP1B57 KRP4A53

SkyAir LU Series


ED21-301

2.9

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

KDDFP55D160 – High-Efficiency Filter Chamber

3

SkyAir LU Series

205


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

206

ED21-301

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.10

KAFJ551K160 – Long-Life Filter for Decoration Panel (Replacement)

2.11

KAFP55D160, KAFJ55K160H (Replacement) – Ultra Long-Life Filter (Including Filter Chamber)

3

Installation Iocation Filter Cleaning Period Dirty Area

Every 5,000 hrs

Not Dirty Area

Every 10,000 hrs

KKSJ55K160 – Chamber Connection Kit

CAUTION Confirm a combination of chamber connection kit with option (chamber type) by the right table. Fresh air intake kit (chamber type) must be set up side surely.

Option (Chamber Type) Down Side

2.12

Up Side Fresh Air Intake Unit

High Efficiency Filter Unit Ultra-Long Life Filter Unit

Don't adopt any combinations except the Table because they may cause functional disorder.

Dimension

Concerning installation of the indoor unit, the option (chamber type) and the decoration panel, refer to installation (operation) manual attached to these parts.

SkyAir LU Series

207


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.13

208

ED21-301

KDJ55K80 · 160 – Branch Duct Chamber

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

3

SkyAir LU Series

209


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301

2.13.1 Fan Performance and Discharge Pattern in case of using Branch Duct Single Branch — 3 Way Discharge

Sealing

Branch

R

S

Sealing

T

S

Branch

T

Q

S

Sealing Branch

T R

R

Q

S

R

T

Sealing

Q

Q

Branch (V0690)

35~71 Single branch ( ) 50/60Hz Common use

55 50

External static pressure (Pa)

55 50

71

45

50

50

50

40

35

35

35

35

30

30

30

25

25

25

20

20

20

15

15

15

10

10

10

5

5

5

0

0 1

2

60 50

35

35

0

71

45

60

40

Single branch ( ) 50/60Hz Common use

55

71

45

60

40

Single branch ( or ) 50/60Hz Common use

3

4

0 0

1

Air volume (m3/min)

2

3

4

0

1

Air volume (m3/min)

2

3

4

Air volume (m3/min)

100~140 Single branch sealing ( 50/60Hz Common use

130 120

)

or

)

Single branch sealing ( 50/60Hz Common use

130 120

140

110

125

125

110

125

100

100

100

100

100

External static pressure (Pa)

140

90

90

90

80

80

80

70

70

70

60

60

60

50

50

50

40

40

40

20

20

20

20

20

20

10

10

10

0

0 0

1

2

3

4

5

6

7

8

Air volume (m3/min)

210

Single branch sealing ( 50/60Hz Common use

130

9 10

)

140

0 0

1

2

3

4

5

6

7

8

Air volume (m3/min)

9 10

0

1

2

3

4

5

6

7

8

9 10

Air volume (m3/min)

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

Single Branch — 2 Way Discharge

S

S

T

R Q

Sealing

Sealing

T R

R Branch Q or T

Sealing

S

Branch

S or T

Sealing Sealing

T

Sealing

Q

Branch

R or T

Q

(V0693)

3

35~71

90

Single branch - 2 way discharge ( 50/60Hz Common use

,

sealing) 90

Single branch - 2 way discharge ( 50/60Hz Common use

71

80

71

80

60

60

50

50

70

35

External static pressure (Pa)

External static pressure (Pa)

70

sealing)

60 50 40 30 20 10

35

60 50 40 30 20 10

0

0 0

1

2

3

4

5

0

1

Air volume (m3/min)

2

3

4

5

Air volume (m3/min)

100~140

160

Single branch - 2 way discharge (100~140. 50Hz)

160

150

150

140

140 Sealing

120

Sealing

110 Sealing

100 90 80 70 60 50 40

120

Sealing

110 Sealing

100 90 80 70 60 50 40

30

30

20

20

10

10

0

Sealing

130

External static pressure (Pa)

External static pressure (Pa)

130

0 0

1

2

3

4

5

6

7

8 3

9 10 11 12

Air volume (m /min)

SkyAir LU Series

Single branch - 2 way discharge (100~140. 60Hz)

0

1

2

3

4

5

6

7

8

9 10 11 12

Air volume (m3/min)

211


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301

2 Branches — 2 Way Discharge

S

Sealing Sealing

S

T

R

Branch

Q

Sealing

R

T

R

Sealing

S

Branch Sealing

T

Sealing

Q

Q

Branch (V0696)

35~71

90

2 Branch - 2 way discharge ( 50/60Hz Common use

90

71 60

80 70

External static pressure (Pa)

sealing) 2 Branch - 2 way discharge ( 50/60Hz Common use

sealing) 2 Branch - 2 way discharge ( 50/60Hz Common use

71

71

60

80

50

50

35

35

70

50

60

50

50

50

40

40

40

30

30

30

20

20

20

10

10

10 0

0 1

2

3

4

5

6

7

0

8

35

70

60

0

60

80

60

0

sealing)

Air volume (m3/min)

1

2

3

4

5

6

7

Air volume (m3/min)

8

0

1

2

3

4

5

6

7

8

Air volume (m3/min)

100~140

150

2 Branch - 2 way discharge (100~140. 50Hz)

150

External static pressure (Pa)

140

140

130

Branch

130

Branch

120

Branch

120

Branch

110

Branch

110

Branch

100

100

90

90

80

80

70

70

60

60

50

50

40

40

30 20

Operation limit less than 12m3/min

10

30 20

Operation limit less than 12m3/min

10

0

0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Air volume (m3/min)

212

2 Branch - 2 way discharge (100~140. 50Hz)

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Air volume (m3/min)

SkyAir LU Series


ED21-301

2.14

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

Dimensions with Optional Kit

2.14.1 KDBJ55K160W – Panel Spacer FH(Y)C35~71K Unit (mm)

3

3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name

Note:When other optional kit is installed, refer to the installation drawing of its optional kit

Thickness of panel spacer

Dimension between the bottom surface of box and the surface of ceiling

View

Description J : 3D005390E

FHYC100~140K Unit (mm)

Note:When other optional kit is installed, refer to the installation drawing of its optional kit

3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name

Thickness of panel spacer

Dimension between the bottom surface of box and the surface of ceiling

View

Description J : 3D005391D

SkyAir LU Series

213


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301

2.14.2 KDDP55D160 – Fresh Air Intake Kit (Without T Joint, Duct Fan) FH(Y)C35~71K

Unit (mm)

Service Access Panel : 450×450mm or more Refer to Note 2

Refrigerant Piping

Note 4

View

Service Access Panel : 450×450mm or more Refer to Note 2

290

Installation Service Access Panel

Connection Chamber (Right)

Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.

How to connect Chamber 4 Independently(Refer to Note 5,6)

Applicable Models SkyAir

FH(Y)C35~71K

5 4 3 2 1 Number

Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981A

FHYC100~140K

Unit (mm)

Service Access Panel : 450×450mm or more Refer to Note 2

Refrigerant Piping

View

Service Access Panel : 450×450mm or more Refer to Note 2

Note 4

Installation Service Access Panel

Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6)

Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.

214

Applicable Models SkyAir

FHYC100~140K

5 4 3 2 1 Number

Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984A

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.14.3 KDDP55D160K – Fresh Air Intake Kit (With T Joint, Without Duct Fan) FH(Y)C35~71K

Unit (mm)

Service Access Panel : 450×450mm or more Refer to Note 2

Flexible Duct (Accessory)

3 Installation Service Access Panel

Service Access Panel : 450×450mm or more Refer to Note 2

Suction Duct (K-KFD9A) Optional (Accessory) T Joint

Plate Band

(Accessory)

Connecting Chamber (Right)

290

(Accessory)

How to connect Chamber 4 Independently(Refer to Note 5)

Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.

Applicable Models SkyAir

FH(Y)C35~71K

5 4 3 2 1 Number

Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032987A

FHYC100~140K Service Access Panel : 450×450mm or more Refer to Note 2

Installation Service Access Panel

Unit (mm) Flexible Duct (Accessory)

Service Access Panel : 450×450mm or more Refer to Note 2 Plate Band (Accessory)

T Joint (Accessory)

Suction Duct (K-KFD9A) Optional (Accessory)

Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)

Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable.

SkyAir LU Series

Applicable Models SkyAir

FHYC100~140K

5 4 3 2 1 Number

Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032990A

215


Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301

2.14.4 KAFP – High Efficiency Filter FH(Y)C35~71K

Unit (mm)

290

Note:When other optional kit is installed, refer to the installation drawing of its optional kit.

6 5 4 3 2 1 Number

Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975A

FHYC100~140K

Unit (mm)

Note:When other optional kit is installed, refer to the installation drawing of its optional kit.

6 5 4 3 2 1 Number

Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032976A

216

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Corner Type [FH(Y)K]

3. Ceiling Mounted Cassette Corner Type [FH(Y)K] 3.1

BYK45FJW1 · 71FJW1 – Decoration panel

BEFORE INSTALLATION PRECAUTIONS • Refer also to the installation manual attached to the indoor unit. ACCESSORIES • The box contains this manual and the parts listed below. Item

Description

Quantity BYK45FJ BYK71FJ

3

Decoration panel

Panel fixing screw

Washer

M5 × 35

1 set

1 set

5 pcs.

5 pcs.

5 pcs.

5 pcs.

NOTE TO INSTALLER Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.

PREPARATION OF DECORATION PANEL • Handle the decoration panel with care. 〈 Never lean the panel against a wall, etc. nor leave it on a projecting object. (For prevention of dents and damages to the panel surface) Never grab the discharge grille during the installation work. (For prevention of damage to the discharge grille) 〉 (1) Remove the suction grille from the decoration panel. (See figure below.) 1) Slide the suction grille lever and lift it up to one side.

SkyAir LU Series

217


Ceiling Mounted Cassette Corner Type [FH(Y)K]

ED21-301

2) Unhook the suction grille off from the decoration panel.

(2) Remove the air filter. Pull up the air filter knob to remove the air filter.

INSTALLATION OF THE DECORATION PANEL TO THE INDOOR UNIT BODY <<Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.>> 1. Installing the panel (1) Install the decoration panel to the indoor unit body temporarily.

Portions to hook the panel's temporary installation hooks

Portion at which the panel is fixed. (5 locations)

218

Temporary installation hooks

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Corner Type [FH(Y)K]

(2) Tighten the panel fixing screws temporarily. 1) Open the air outlet decorative covers.

Air outlet decorative covers

3

2) Put the panel fixing screws (5 pcs.) through the washers and tighten the screws temporarily. 3) Move the panel as indicated by the arrow in the above figure for adjustment so as to make no gap between the panel and the ceiling. 2. Wiring between the indoor unit and the panel ¡ With the decoration panel temporarily installed to the indoor unit, wire between the indoor unit and the decoration panel. (See figure below.) (1) Connect the connectors for swing motor and the limit switch on the decoration panel to those on the indoor unit body respectively. (2) Check that the connectors are of the same color. Panel side

Indoor unit side

(Motor power cable) Color of connector: red

Note: No connection of connectors or connection of connectors of different colors causes the unit to stop operating with the Operation lamp on the remote control blinking and the trouble code display "A7" on the remote controller.

Panel side

Indoor unit side

(Limit switch) Color of connector: black

SkyAir LU Series

219


Ceiling Mounted Cassette Corner Type [FH(Y)K]

ED21-301

3. Fixing the decoration panel (1) In order to prevent air leakage, a sealing material is provided at the spot where the indoor unit body is joined with the decoration panel. Fix the decoration panel in the following method. (Shoulder bolts are used as the fixing screws. Tighten the bolts until their shoulders.) Indoor unit body Indoor unit

Sealing material Standard tightening length: 20 mm Shoulder bolts are used to protect the indoor unit. The bolts can be tightened to the allowance of up to 15 mm.

Decoration panel

Decoration panel body

(2) When tightening the bolts, be sure to make no gap between the panel and the ceiling and set the panel in parallel to the ceiling and the ceiling joint. á

Improper installation of the panel to the cassette body causes air leakage. ñ

Note: In case there remains a gap between the panel and the ceiling when the fixing bolts have been tightened fully to their shoulders, adjust the height of the indoor unit.

Make no gap here.

Note: The decoration panel can be adjusted back and forth to 10 mm, respectively.

(3) Finally, make sure that the decoration panel is securely fixed to the indoor unit. Improper installation (tightening) causes the troubles as shown below; be sure to double-check the completion of the installation work. ñ á

No gap

Air leakage

Air leakage from the ceiling Dust deposit Dew buildup and dew dripping

INSTALLATION OF SUCTION GRILLE AND AIR FILTER For their installation, take the reverse steps mentioned in "PREPARATION OF DECORATION PANEL".

220

SkyAir LU Series


ED21-301

3.2

Ceiling Mounted Cassette Corner Type [FH(Y)K]

KPBJ52F56W · 80W – Panel Specer

3

SkyAir LU Series

221


Ceiling Mounted Cassette Corner Type [FH(Y)K]

222

ED21-301

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Corner Type [FH(Y)K]

3

SkyAir LU Series

223


Ceiling Mounted Cassette Corner Type [FH(Y)K]

224

ED21-301

SkyAir LU Series


ED21-301

3.3

Ceiling Mounted Cassette Corner Type [FH(Y)K]

KDBJ52F56W · 80W – Air Discharge Blind Panel

3

SkyAir LU Series

225


Ceiling Mounted Cassette Corner Type [FH(Y)K]

226

ED21-301

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Corner Type [FH(Y)K]

3

SkyAir LU Series

227


Ceiling Mounted Cassette Corner Type [FH(Y)K]

228

ED21-301

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Corner Type [FH(Y)K]

3

SkyAir LU Series

229


Ceiling Mounted Cassette Corner Type [FH(Y)K]

230

ED21-301

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Corner Type [FH(Y)K]

3

SkyAir LU Series

231


Ceiling Mounted Cassette Corner Type [FH(Y)K]

3.4

ED21-301

KAFJ521F56 · 80 – Replacement Long Life Filter Washable Model Items Average Efficiency Initial Pressure Loss Final Pressure Loss Life Time Materials Number Required Per Model Weight (kg)

KAFJ521F56

KAFJ521F80

45 (gravity Method) Less Than 9.8 Pa 49 Pa 2,500 hours (Dust Particle Concentration at 0.15 mg/m3) Mildew Proof Resin Net Two pieces 0.4 0.6

Dimension

3.5

Model

A

KAFJ521F56

403

KAFJ521F80

503

K-HV7AW · 9AW – Discharge Grille This optional kit is used when the unit is installed with front air discharge. The direction of air can be adjusted flexibly. This discharge grille should be installed with the following flexible duct. Specifications Model Items Air Flow Rate (m³/min) Type

K-HV7AW

K-HV9AW

9~13

12~19

HV type (Horizontal blade and vertical blade movable)

External Color Materials

White

White

Steel plate (A cryptomeria only at the tip of the outlet + nylon flocking)

Structural Parts

Discharge grille, Screws, Blade control tool KFDJ52F56

KFDJ52F80

Applicable Models

35 · 45F(J)

60 · 71F(J)

Pressure Drop

Applicable Flexible Duct

m/s : Discharge Velocity

Air Flow Rate

Model

232

A

B

C

D

K-HV7AW

523

466

488

500

K-HV9AW

723

666

688

700

SkyAir LU Series


ED21-301

3.6

Ceiling Mounted Cassette Corner Type [FH(Y)K]

KFDJ52F56 · 80 – Flexible Duct with Shutter

3

SkyAir LU Series

233


Ceiling Mounted Cassette Corner Type [FH(Y)K]

234

ED21-301

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Corner Type [FH(Y)K]

3

SkyAir LU Series

235


Ceiling Mounted Cassette Corner Type [FH(Y)K]

236

ED21-301

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Corner Type [FH(Y)K]

3

SkyAir LU Series

237


Ceiling Mounted Cassette Corner Type [FH(Y)K]

238

ED21-301

SkyAir LU Series


ED21-301

Ceiling Mounted Cassette Corner Type [FH(Y)K]

3

SkyAir LU Series

239


Ceiling Mounted Built-In Type [FH(Y)B]

ED21-301

4. Ceiling Mounted Built-In Type [FH(Y)B] 4.1

240

BYBS45DJW1 – Decoration panel BYBS71DJW1 – Decoration panel BYBS125DJW1 – Decoration panel

SkyAir LU Series


ED21-301

Ceiling Mounted Built-In Type [FH(Y)B]

3

SkyAir LU Series

241


Ceiling Mounted Built-In Type [FH(Y)B]

242

ED21-301

SkyAir LU Series


ED21-301

Ceiling Mounted Built-In Type [FH(Y)B]

3

SkyAir LU Series

243


Ceiling Mounted Built-In Type [FH(Y)B]

4.2

244

ED21-301

KTBJ25K56W · 80W · 160W – Service access panel

SkyAir LU Series


ED21-301

4.3

Ceiling Mounted Built-In Type [FH(Y)B]

KAFJ252L56 · 80 · 160 – High-Efficiency Filter KAFJ253L56 · 80 · 160 – High-Efficiency Filter

Specifications Model

KAFJ252L56

Item Average Efficiency

KAFJ253L56

KAFJ253L80

KAFJ253L160

90% (NBS Colorimetric Method)

Less Than 5

Less Than 5

10

10

Ultimate Pressure Loss (mmH2O) Effective Life (h)

KAFJ252L160

65% (NBS Colorimetric Method)

Initial Pressure Loss (mmH2O)

Filter Materials

KAFJ252L80

Synthetic Fiber non-woven Fabric 2,500 (Dust Particle Concentration at 0.15 mg/m3)

Filter Chamber for Bottom Suction

KAJ25L56D

Dimensions (mm) (H×W×D)

55×650×360

Applicable Model

35 · 45F

KAJ25L80D

KAJ25L160D

(55×475×360)×2 (55×700×360)×1 (55×650×360)×1 60 · 71F

100 · 125F

Synthetic Fiber non-woven Fabric

3

1,800 (Dust Particle Concentration at 0.15 mg/m3) KAJ25L56D 55×650×360 35 · 45F

KAJ25L80D

KAJ25L160D

(55×475×360)×2 (55×700×360)×1 (55×650×360)×1 60 · 71F

100 · 125F

Installation

Characteristics of Filter

SkyAir LU Series

245


Ceiling Mounted Built-In Type [FH(Y)B]

4.4

ED21-301

KAFJ251K56 · 80 · 160 – Replacement long-life filter

Specifications Model Item Dimensions (mm) (H×W×D) Average Efficiency Pressure Loss Initial (pa) Ultimate Filter Materials Number of Filters Effective Life (h) Applicable Model

4.5

Characteristics of Filter KAFJ251K56

KAFJ251K80

KAFJ251K160

20×506×377 20×701×377 20×451×377 20×656×377 50% (by weight method) 9.8 (1mmH2O) 49 (5mmH2O) Mold Prevention resin net 1 2 (each one) 2 (each one) 2,500 (at Dust Particle Concentration of 0.15 mg/m3) For indoor unit For indoor unit For indoor unit 35~45F 60~71F 100~125F 20×656×377

KAJ25L56D · 80D · 160D – Filter Chamber for Bottom Suction

Applicable Model Model

Installation Applicable Model

Dimension

246

SkyAir LU Series


ED21-301

4.6

Ceiling Mounted Built-In Type [FH(Y)B]

KAJ25L56B · 80B · 160B – Filter Chamber for Rear Suction Contents of kit Name Rear-Intake Filter Chamber Blind Board Screws For Blind Board (M5×12) For Filter Chamber Washer for Suspension Bracket Suspension Bracket Screws for Suspension Bracket (M6×12) Filter Guide Screws for Filter Guide (M5×12) Applicable Model

Quantity KAJ25L56B 1 1 4 11 4 2 2 – – 35 · 45F

KAJ25L80B 1 1 6 13 4 2 2 1 2 60 · 71F

KAJ25L160B 1 1 6 15 4 2 2 1 2 100 · 125F

3

Preparation before installation

SkyAir LU Series

247


Ceiling Mounted Built-In Type [FH(Y)B]

248

ED21-301

SkyAir LU Series


ED21-301

Ceiling Mounted Built-In Type [FH(Y)B]

3

SkyAir LU Series

249


Ceiling Mounted Built-In Type [FH(Y)B]

4.7

250

ED21-301

KSAJ25K56 · 80 ·160 – Canvas Duct

SkyAir LU Series


ED21-301

4.8

Ceiling Mounted Built-In Type [FH(Y)B]

K-DG4BW · 5BW · 7BW · 9BW – Air Discharge Unit-Discharge Grille+Discharge Chamber K-DGC4B · 5B · 7B · 9B – Air Discharge Unit-Discharge Grille+Discharge Chamber

3

SkyAir LU Series

251


Ceiling Mounted Built-In Type [FH(Y)B]

252

ED21-301

SkyAir LU Series


ED21-301

4.9

Ceiling Mounted Built-In Type [FH(Y)B]

K-DDV20A – Branch Duct

Specification

Dimension Model

Item Inlet Duct Size Outlet Duct Size Outside Insulation Inside Insulation

-

Polyurethane Foam Foam Polysthyrene

Pressure loss of Branch Duct

3

Model

SkyAir LU Series

Weight (kg)

253


Ceiling Mounted Built-In Type [FH(Y)B]

4.10

ED21-301

K-FDK151B · 152B · 153B · 154B · 155B · 156B – Flexible Duct K-FDK201B · 202B · 203B · 204B · 205B · 206B – Flexible Duct Specification Model Item Maximam Outer Dimension Fitting Port Size Operating Temperature Range Applicable Model Structure

(Inner Dimension)

(Inner Dimension)

-10~+70˚C 35~125F Pressure loss of Flexible Duct Air ty oci Vel c.) / se (m t Duc eter Diam m) (m

m H20/100m

254

SkyAir LU Series


ED21-301

4.11

Ceiling Mounted Built-In Type [FH(Y)B]

KBBJ25K56 · 80 · 160 – Blind Board

3

4.12

KDAJ25K56 · 71 · 140 – Adaptor for Discharge

SkyAir LU Series

255


Ceiling Mounted Built-In Type [FH(Y)B]

4.13

256

ED21-301

KDJ2507K56 · 80 · 160 – Flange for Suction

SkyAir LU Series


ED21-301

4.14

Ceiling Mounted Built-In Type [FH(Y)B]

Optional Kit Installation Drawing

Discharge Chamber+Discharge Grille <φ150> K-DGC4~7B, K-DG4~7BW

3

K-DGC9B, K-DG9BW

SkyAir LU Series

257


New Ceiling Suspended Cassette Type [FUY]

ED21-301

5. New Ceiling Suspended Cassette Type [FUY] 5.1

KDBHJ49F80 · 140 – Sealing Member of Air Discharge Outlet

Dimension

Model KDBHJ49F80 KDBHJ49F140

Material Galvanized Steel Plate (with Flocking)

Model KDBTJ49F80 KDBTJ49F140

Material Galvanized Steel Plate (with Flocking)

Model KDBHJ49F80 KDBHJ49F140

5.2

KDBTJ49F80 · 140 – Decoration Panel for Air Discharge

Dimension

Model KDBTJ49F80 KDBTJ49F140

5.3

KDGJ49F80 · 140 – Vertical Flap Kit

Dimension

Model KDGJ49F80 KDGJ49F140

258

Packing Quantity 4(each 2×2)

SkyAir LU Series


ED21-301

5.4

New Ceiling Suspended Cassette Type [FUY]

KAFJ495F140 – Replacement Long Life Filter

Dimension

Model Item Initial Pressure Loss (Pa) Final Pressure Loss (Pa) Average Efficiency (%) Life Time (h)

KAFJ495F140 Less Than 7 Less Than 49 50 (Gravity Method) 2,500 (Dust Particle Concentration at 0.15 mg/m3)

Filter Pass Air Flow Rate Materials Number Required Per Model Weight (kg)

3

18.5 m /min Mildew Proof Resin Net 1 0.4

3

5.5

KHFJ49F80 · 140 – L Connection Piping Kit Model KHFJ49F80 KHFJ49F140

Dimension

5.6

Liquid Side

Gas Side

KRP1B97 – Installation Box for Adaptor PCB

Dimension

SkyAir LU Series

Model No. Item Applicable Model Adaptor for Wiring

KRP1B97 FUY71~125FJ KRP4A53

259


Ceiling Suspended Type [FH(Y)]

ED21-301

6. Ceiling Suspended Type [FH(Y)] 6.1

KAFJ501D56 · 80 · 112 · 160 – Replacement Long Life Filter

Specifications Model

KAFJ501D56

Item

KAFJ501D80

KAFJ501D112

KAFJ501D160

3

Effective Life, Average Efficiency 2,500 hours (at Dust Particle Concentration of 0.15 mg/m ), 45% (by Weight Method) Filter Materials

Mold Prevention Resin Net

Mold Prevention Resin Net

Nos. Required

2 pieces

3 pieces

Applicable Model

For Indoor unit 35~50

6.2

For Indoor unit 60~71

For Indoor unit 100

For Indoor unit 125

KDU50B50 · 71 · 125VE – Drain Pump Kit

Specifications Model Item

KDU50B50VE

Drain-up Lift (mm)

600

Power Supply

Single Phase 220-240V/220V 50/60Hz (from Indoor Unit PC Board)

Power Consumption (W)

Applicable Model

KDU50B125VE

VP20 (Ex. dia. φ26, Int. dia. φ20)

Drain Con, Diameter Pump

KDU50B71VE

13.5/12 (50/60Hz) 35~50B

60~71B

100~125B

Precaution at use 1. Don’t turn off the power within 5 minutes after cooling operation stops. 2. The liquid crystal display blinks to inform us that safety device actuated. 3. When cooling operation’s seaaon is over, extract drain water. Installation guide of the drain pump kit <Change in drain pump kit> Exit drain pipe has been changed from VP25 to VP20 (to meet the drain diameter of main frame). Attached drain pipe (450 mm chloride vinyl straight pipe bellow, elbow) Æ only bellow hose for VP20 All units of drain up height was unified to 600 mm (from the bottom of the ceiling).

Wiring diagram

260

SkyAir LU Series


ED21-301

6.3

Ceiling Suspended Type [FH(Y)]

KHFJ5F50 · 60 · 80 · 160 – L-Type Piping Kit Application purpose This kit must be bent inside the unit as shown below, when the refrigerant piping is carried out in a ceiling space. This L shape kit is an optional accessory which has been developed for improving the work of the processing on site. Model Item

KHFJ5F50

KHFJ5F60

KHFJ5F80

KHFJ5F160

Applicable Model

For Indoor Unit 35B

For Indoor Unit 45B~60B

For Indoor Unit 71B

For Indoor Unit 100B~125B

Installation KHFJ5F50~160

6.4

3

Installation

KRP1C93 – Installation Box for Adaptor PCB

KRP1C93

Model No. Item Applicable Model Adaptor for Wiring Fixing Place Dimensions (mm)

SkyAir LU Series

W H D

KRP1C93 FH(Y)35~125B KRP1B54 KRP4A52 In the Unit 109 124 38

261


Floor Standing Type [FVY]

ED21-301

7. Floor Standing Type [FVY] 7.1

KAFJ95L160 – Replacement Long Life Filter Model Item Applied Model Average Efficiency (%) Initial Pressure Loss (Pa) Final Pressure Loss (Pa)

Dimension

Life Time (h) Materials Number Required Per Model Weight (kg)

7.2

KRP4A95 – Installation Box for Adaptor PCB

KRP4A95

Model No. Item Applicable Model Adaptor for Wiring Fixing Place Dimensions (mm)

262

KAFJ95L160 FVY71~125L(A) 60 (Gravity Method) Less Than 8 Less Than 49 2,500 (Dust Particle Concentration at 0.15 mg/m3) Mildew Proot Resin Net 1 0.4

W H D

KRP4A95 FVY71~125L(A) KRP4A52 KRP1B57 In the Unit 180 117 64

SkyAir LU Series


ED21-301

Outdoor Unit

8. Outdoor Unit 8.1

KIS95 – Drain Piping Kit Use this plug to connect a drain hose to an outdoor unit. Outlook KIS95

Drain hose connection dia φ16ID. Notes:

8.2

3

KIS95 Drain piping (With Y joint) plug (3 pcs.)

1. This is the joint for attaching a vinyl hose (field supplied). This is used between the drain hole which is on the bottom plate of outdoor unit and vinyl hose. 2. Drain water accumulate to the bottom of outdoor unit it depends on the situation of operation. But it is necessary to connect drain hose not to be spread the drain water over the neighbors, when it is installed on the wall. 3. The position of holes are unfit to connect with outdoor units in some models. In this case, use it without Y joint.

KKPJ5F180 – Central Drain Plug

SkyAir LU Series

263


Outdoor Unit

8.3

ED21-301

KRK5F80V1 · 140V1 · 160V1 – Year Round Cooling Kit

R71LUY1, R71LUVAL R100LUY1, R100LUVAL, R125LUY1, R125LUTAL, R125LUYAL R140LUY1, R140LUYAL, R140LUTAL

C : 3PA60339B

264

SkyAir LU Series


ED21-301

8.4

Outdoor Unit

KHR58C21, KHD58C21A, KHD58C23A, KHD58C24A, KHD58D31, KHD58D33, KHRJ5F224F, KHRJ5F280F – Refrigerant Branch Piping <Caution> This is the branch kit for refrigerant piping to connect indoor and outdoor units of TWIN/TRIPLE/ DOUBLE Twin simultaneous ON/OFF system.

How to use 1. Uses as branch joints of refrigerant piping. Note) It is necessary because it is not attached to the air conditioner. 2. Pipes of the joint parts are widened. → Enables easy connection and Brazing. 3. Insulation materials are equipped as standard.

Type Model

Item

Reducer

Type Model

Applicable Model

Triple Multi KHD58D33

R(Y)71LU

R(Y)100~140LU

R(Y)200KU

R(Y)250KU

R(Y)140LU

2 — — —

2 — — —

— — 2 1

— — 2 —

— — — —

— — — —

2 — 1 —

— 1 — —

— — — 1

— — — —

Double Twin Multi

Triple Multi KHD58D31 R(Y)200KU

KHRJ5F224F R(Y)200KU

KHRJ5F280F R(Y)250KU

Branch Pipe

Reducer

(2 sets)

1 — — 1

— — — —

— — — —

1 — 1 —

— — — —

— — — —

(2 sets)

— — — —

— — — —

— — — —

— — — —

Branch Pipe

(2 sets)

Reducer

Liquid Side Joint

KHD58C24A

Branch Pipe

Item

Gas Side Joint

Twin Multi KHD58C21A KHD58C23A

Branch Pipe

Reducer

Gas Side Joint

Liquid Side Joint

Applicable Model

KHR58C21

SkyAir LU Series

(2 sets)

265

3


Outdoor Unit

Dimension Twin/Double Twin Multi

ED21-301

Triple Multi

Model

(Horizontal)

266

SkyAir LU Series


The air conditioners manufactured by Daikin Industries have received ISO 9000 series certification for quality assurance.

The airconditioning factories of Daikin Industries have received environmental management system standard ISO 14001 certification.

Certificate Number.

Shiga Plant

(ISO9001) JMI-0107 JQA-0495

(ISO9002) JQA-1452

Certificate Number. EC99J2044

Sakai Plant Certificate Number. JQA-E80009

Yodogawa Plant Certificate Number. EC99J2057

Dealer Head Office: Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome, Kita-ku, Osaka 530-8323, Japan Tokyo Office: Shinjuku Sumitomo Bldg., 6-1, Nishi-Shinjuku 2-chome, Shinjuku-ku, Tokyo 163-0235, Japan

http://www.daikin.com/global/ c All rights reserved

The specifications, designs, and information in this brochure are subject to change without notice.

This book is made of recycled paper.

ED 21-301 Printed in Japan 07/2003 FS