Ceiling Cassette (50Hz/R22) TH5CST2-04A ( Replace : TH5CST2-03C)
General Description Thank you very much for your special patronage of LG air conditioners. LG’s "Ceiling Cassette" is a indoor unit which is installed for the significant purpose. The ceiling cassette is used for the commercial purposes. It can be installed in various places such as restaurants, hotels, offices and meeting rooms. This unit has nice outlook and is equipped with many special features. It has four louver for the air circulation in all directions which in turn can maintain even and wide cooling. In other side it has facility for high elevation piping (30m), built in drain pump (drain throw 70cm),high ceiling operation,others for facilitating its working. Noise level of the unit is very low. In installation field unit is installed in fall ceiling. It has wide capacity range from 18 to 48 kBtu/h. A lot of information regarding the design & installation of this system is provided in this publication. This new products series contains data on the same pattern. Please utilize all the information for conducting your business efficiently. Make sure the specification, dimension or others technical data are same as provided in enginering data book before you start the project. We look forward to your continuing support.
LG Electronics lnc. Air Conditioning Division
2
Ceiling Cassette(50Hz, R22)
LG Airconditioners Product Data
Table of contents Table of contents
Page
1. Models List ......................................................................................................................4 2. Model Number Nomenclature..........................................................................................5 3. Feature & Benefits ...........................................................................................................6 4. List of Functions..............................................................................................................11 5. Specifications.................................................................................................................12 6. Dimensional Drawings ...................................................................................................18 7. Wiring Diagrams .............................................................................................................21 8. Refrigerant Cycle Diagrams......................................................................................... 25 9. Selection Procedure ..................................................................................................... 26 10. Perfor mance Data......................................................................................................... 27 11. The Coefficient of Capacity Change ...........................................................................33 12. Operation range.............................................................................................................. 34 13. Air Velocity and Temperature Distributions(Reference Data)................................................. 35 14. Sound Levels ................................................................................................................37 15. Installation .....................................................................................................................38 16. Function of Remote Control.........................................................................................50
2008 Product Data
3
1. Models List
1.1 Cooling Only Nominal Capacity Model Name
kW
kBtu/h
5.3
18
HT-C186HLA0 HT-C186HLA1
7.0
24
HT-C246HLA0 HT-C246HLA1
8.8
30
HT-C306HLA0
10.6
36
HT-C368DLA0 HT-C368DLA1
14.1
48
Power Supply
Model Refrigerant
Ø,V,Hz
1Ø, 220-240V, 50Hz
R22
3Ø, 380-415V, 50Hz
HT-C488DLA0 HT-C488DLA1
Publication history Pub. No.
TH5CST2-04A
Frequency Category
50Hz
CAC
4 Ceiling Cassette(50Hz,R22)
Type Product name
Single Ceiling Cassette
Refrigerant
R22
Model
HT-C368DLA1 HT-C488DLA1
Notes
Addition of new models
Published in
Oct.2008
2. Model Number Nomenclature 2.1 Model Number Nomenclature H T
C 1 8 6 H L A 0 Development Sequence Function A : Basic E : Elevation Grille
C : Plasma Air Purifying F : Elevation Grille + Plasma Air Purifying
Decoration Panel Information L : Basic Panel
Chassis Type H : TH Chassis
D : TD1 Chassis
Electric Standard (Volts / Freq. / Phase) 6 : 220-240V, 50Hz, 1Ă˜
8 : 380-415V, 50Hz, 3Ă˜
Nominal Cooling Capacity Ex) 18-> 18,000 Btu/h
24-> 24,000 Btu/h
Model Type
C : Cooling Only N : Indoor Type , U : Outdoor Type T : Cassette Type H : Development in Thailand
2008 Product Data
5
3. Features & Benefits 840mm
Compact Design and Easy Installation (For TH Chassis)
840mm
Only about 225mm height in the ceiling is sufficient for installation space. 225mm
Low noise with 3-dimensional turbo fan The most advanced low-noise design.The adoption of turbo-fan and round type give the most quiet operation.
Noise output measured in anechoic test room
Hygienic and Easy-to-Clean Filter Washable and anti bacteria filter is adopted. It is easy to open grille and replace clean filter.
Anti Corrosion Gold Fin™ (Option) LG ’s Outdoor Heat Exchanger is coated with a golden anticorrosive epoxy treatment on the aluminum coil to minimized corrosion. This maintains heat transfer properties of the coil for an extended time where as non-Gold Fin coils progressively lose efficiency due to surface corrosion. Standard on every LG air conditioner, this assists in areas suffering from pollution or near the ocean where the unit
Salt Spray Test for 15 Days
After 15 Days
LG Gold Fin™ Anti Corrosion
Gold Coated Aluminum
After 15 Days
Uncoated Aluminum
• Gold Fin is long lasting, durable and makes the Outdoor Unit look prestigious.
6 Ceiling Cassette(50Hz,R22)
Conventional Starting to corrode
3. Features & Benefits Central Control (Optional)
It enables to control 16 x 8 = 128 units with the help of 8 controllers. All units can be put on and off from one central room. For setting the temperature, fan speed and other sub functions, access the sespecture LCD wired remote controller of each unit.
Main PCB
M 1
M 2
M 16
M 17
M 18
M 128
Sub 1
Sub 2
Sub 16
Sub 17
Sub 18
Sub 128
Controller #1
Controller #2
Controller #8
Cooling & Fan Operation(for cooling only) LG Ceiling Cassette air conditioner provides cooling & fan operation. In the cooling mode, it cools the air with an operation range of 18~30°C. In the fan operation mode, only indoor fan at the selected speed will run, outdoor fan and compressor will be off.
AUTO SWING
OPERATION
SET TEMP Room Temp
Wired Remote Control It can control all the functions of the unit. You can check/set temperature, change operation mode, set timer & also diagnose the error of the unit. It also has the option of weekly program.
2ndF Timer
FAN SPEED
SUB FUNCTION
AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door ZONE 1 2 3 4
HI MED LO
Time
Operation unit No Func Program set
On Off Set no. Time 01
03
05
07
Timer
Cancel
2ndF
Program
Week
Holiday
09
11
13
15
17
19
21
23
PLASMA
Set/Clr Hour
Min
RESET
Auto Restart Operation When there is electricity failure the unit shuts off and after resumption of the power, unit will start in the same mode as prior to the power failure. Memorized condition are on / off condition, operating mode (cooling/heating), set temperature and fan speed.The unit will memorize the above conditions and start with same memorized condition.
Two Thermistor Control There may be a significant difference between the temperature taken at the installed product and indoor temperature. Two thermistor control provides option to control temperature by referring any of the two temperatures. With the help of the slide switch at the back of the LCD wired remote controller, selection of the desired thermistor for controlling the unit can be done. One thermistor is in the Indoor unit & the other one is in the LCD wired remote.
2008 Product Data
7
3. Features & Benefits Plasma Air Purifying System (Optional) The PLASMA Air Purifying Function not only removes microscopic contaminants and dust, b ut also removes house mites, pollen, and pet fur helps to prevent allergic diseases like asthma. Dust particles
Dust electrode discharge
Ionizer
Photo-Catalyst Coated Mesh
+4.8KV discharge
+
Polluted Air
+ +
Purified fresh Air
+
Generating plasma
Odour Odour molecule
High Head Drain Pump(700mm) Built-in Drain Pump drains out water automatically. A standard drain-head height of up to 700 mm is possible, creating the ideal solution for perfect water drainage. Pipe fixture
Slope 1/50~1/100
Maximum 700mm Flexible drain hose
Hard Tube(ex.PVC) Drain Pump
Drain Pan
Ceiling Board
High Ceiling Operation According to the height of the installation, it provides variability of indoor fan motor speed. If the height of installation is low then you can adjust low rpm of indoor fan motor. On the other hand if the height of the installation is high you can adjust high speed of indoor fan motor. Selection of speed can be done by slide switch at the back of the LCD wired remote controller. ex: If ceiling height of 2.7-3m(taken as standard for the product) is exceeded, then the slide switch is iperated in the high mode discharging air at a high volume rate and when below 2.7m, the switch is adjusted to discharge at a lower volume rate.
8 Ceiling Cassette(50Hz,R22)
Air velocity distribution
3. Features & Benefits Child Lock Function It prevents the children or others from tampering with the control buttons. Unit can be controlled by the wireless remote controller. This can be easily set by pressing timer key & Min key simultaneously. After child lock is set, pressing any key will display CL on the LCD for 3 seconds and all the keys will be ineffective.
AUTO SWING
OPERATION
SET TEMP Room Temp
Operation unit No Func Program set
On Off Set no. Time 01
Jet Cool
SUB FUNCTION
AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door ZONE 1 2 3 4
HI MED LO
Time
2ndF Timer
FAN SPEED
03
05
07
09
11
13
15
17
19
21
23
Cancel Timer CHILD LOC2ndF K Display
In this mode quick and fast cooling is done. Cold
Program
and high velocity air is supplied to the room till the
Week
Holiday PLASMA
Set/Clr
indoor temperature reaches 18°C.
Hour
RESET
Min
4- Open(Conventional)
Comparison of Floor o Temp. Distri b ution( 20 C)
Swirl Swing
2.4%
Sw irl Sw ing(Ne w )
100% Improved
4.8%
It is the function for comfort cooling/heating operation. The diagonal two louvers are opened the more larger than the other louvers. After one minute, it is opposite.
Comparison of Air Flo w Types 4- Open(Conventional)
Sw irl Sw ing(Ne w )
Vane 1 Open
Vane 1 Close
Vane 2 Open
Vane 2 Open
Vane 3 Open
Vane 3 Close
Vane 4 Open
Vane 4 Open
Close
Time
Group Control
Open
Vane 2 Close
Open
Close
Close
Open
Close
Open
Open
Close
Open
Close
Open 71
Close
Open
Vane 3
Vane 1
Time Vane 4
1
2
16
1) Operation summary - Where several products are linked, one specific control device can control a specific number of products. 2) Specific operation
Remote Controller
- Connecting line is linked to each of the indoor equipments for communication. A specific control device is connected to each of them and this control device can control the same function. - Group control function is enabled by cutting an optional jump wire in the wired remote controller. At this time, the main system will not respond in order to prevent data collision. - While executing group control command, use the random data(0-3minutes) in the main body of indoor equipment for limiting starting current. - Control device can control up to 16 indoor equipments. 2008 Product Data
9
3. Features & Benefits Space Control (Accessory) • Space control Vanes angle can be controlled by pair, considering its installation environment. - For example direct drafts can be annoying, leading to discomfort and reduced productivity, vane control helps to eliminate this problem. - Easily controlled by wired remote control. - Air flow can be controlled easily regarding any space environment.
20°~70°
Time Delay Safety Function It delays restarting of the compressor by three minutes thereby preventing damage to the compressor.
Long Refrigerant Piping It provides flexibility of installation and keep the building in a good outlook.
Model HT-C186HLA0 HT-C186HLA1 HT-C246HLA0 HT-C246HLA1 HT-C306HLA0 HT-C368DLA0 HT-C368DLA1 HT-C488DLA0 HT-C488DLA1
B
Max. Piping length m. (A) Max. Elevation m. (B) 30 30 30 30 30 30 50 30 50
10 Ceiling Cassette(50Hz,R22)
10 10 10 10 10 15 15 15 15
A
4. List of Functions Indoor Unit C a tegory
F unc tion
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down Auto swing(left & right) Auto swing(up & down) Air flow Airflow steps(fan/cool) (wired remote) Chaos wind (auto wind) Vane Control Jet cool(Power wind) Swirl wind Deodorizing filter Air purifying Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Installation Electric heater(operation) High Ceiling Operation Hot start Reliability Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence)
Auto restart operation Child lock Convenience Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Standard wired remote controller Deluxe wired remote controller Individual Simple wired remote controller control Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control General central controller (Non LGAP)
CAC network function
Dry contact Simple central control (LGAP) PDI(power distribution indicator) PI485 Zone control Special CTIE function kit Electro thermostat
Ceiling Cassette Type ( wired remote) 4
Ceiling Cassette Type ( wireless remote)
X
X
Auto
Auto
X
X
O
O
4/5
3/4
X
X
O O O
O O O
× Option
× Option
O O
O O
-
O ×
O O
× ×
O O O O O O O O O O
× × × × Accessory × Option
O
× Accessory × × ×
Remark
4
function for HT-C***HLC*
Accessory × Accessory
O
× ×
O O
Accessory
O Accessory
O O
Accessory Accessory Accessory × × × ×
O
× Option
O × Accessory × × ×
Outdoor Unit Defrost/Deicing High pressure switch Low pressure switch Phase protection Reliability Restart delay(3-minutes) Self diagnosis Soft start Test function Auto operation(Artificial intelligence) Convenience Auto restart operation CAC network Network soluation(LGAP) function PDI(Power Distribution Indicator) PI485 Special Low ambient operation function kit Others Thermistor
-
-
× × ×
× × ×
O O × × -
O Accessory × × -
O
O
× × ×
× × ×
×
×
-
-
Note: O : Applied, X : Not applied, - : No relation * Option : Model name & price are different according to options, and assembled in factory with main unit * Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied separate package.
2008 Product Data
11
5. Specifications Model No : HTNC186HLA0, HTNC186HLA1, HTNC246HLA0 Indoor Unit Power Supply Cooling Capacity Heating Capacity Current
HTNC186HLA0
HTNC186HLA1
HTNC246HLA0
kW
1/220-240/50 5.3
1/220-240/50 5.3
1/220-240/50 7.0
Btu/h
18,000
18,000
24,000
kW
-
-
Btu/h
-
-
-
Ø / V / Hz
0.3
A
Nominal Running Current
Motor Type Fan Type
Turbo Fan 100x1
Motor Output(W) x No. of Unit Fan
Air Flow Rate (SH / H / M / L / SL) External Static Pressure Capacitor Drive
Coil Dimensions (W x H x D) Net Weight
Row × Column × FPI Body Decorative Panel
CMM
17/15/12/10/8 600/530/424/353/283
cfm mmAq
-
µF / Vac
220/450
Direct 2R x 9C x 18 mm(inch) 840x840x225(33.1x33.1x8.9) mm(inch) 950x950x30(37.4x37.4x1.2)
Body
kg (lbs)
Decorative Panel
kg (lbs)
26(57.3) 5(11) Long Life Filter
Air Filter Sound Level (SH / H / M / L / SL) Piping Connections
dB(A)+3
Liquid
mm (inch)
Gas
mm (inch)
Drain(OD/ID)
Dehumidification Rate
mm l/h
Safety Devices Temperature Sensor Referigerant Referigerant Control No.×mm
2
-
220/450 Direct 2R x 9C x 18 840x840x225(33.1x33.1x8.9) 950x950x30(37.4x37.4x1.2) 26(57.3) 5(11) Long Life Filter
35/31/27/24/20 6.35(1/4) 12.7(1/2) 32 / 25 1.2
35/31/27/24/20 6.35(1/4) 12.7(1/2) 32 / 25 1.15
Fuse, Thermal Protector Thermistor R22
Fuse, Thermal Protector Thermistor R22 Capillary HTUC186HLA1 4x0.75
Capillary
Connectable Outdoor Unit Power and Transmission Interunit Cable
0.3 BLDC Turbo fan 100x1 17/15/12/10/8 600/530/424/353/283
BLDC
HTUC186HLA0 4x0.75
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code. 3. The specification may be subject to change without prior notice for purpose of improvement.
12 Ceiling Cassette(50Hz,R22)
0.3 BLDC Turbo fan 100x1 22/17/15/13/12 776/600/530/459/424 -
220/450 Direct 2R x 9C x 18 840x840x225(33.1x33.1x8.9) 950x950x30(37.4x37.4x1.2) 33(72.7) 5(11) Long Life Filter 42/34/32/29/27 6.35(1/4) 15.88(5/8) 32 / 25 2.4 Fuse, Thermal Protector Thermistor R22 Capillary
HTUC246HLA0 4x0.75
Model No : HTNC246HLA,HTN306HLA0,HTNC368DLA0 Indoor Unit Power Supply Cooling Capacity Heating Capacity Current
HTNC246HLA1
HTNC306HLA0
1/220-240/50
kW
1/220-240/50 7.0
Btu/h
24,000
30,000
Ø / V / Hz
kW
-
-
Btu/h
-
-
0.3
A
Nominal Running Current
Motor Type Motor Output(W) x No. of Unit Fan
External Static Pressure Capacitor Drive Coil Dimensions (W x H x D) Net Weight
Row × Column × FPI Body Decorative Panel
CMM cfm mmAq
kg (lbs)
Decorative Panel
kg (lbs) dB(A)+3 mm (inch)
Gas
mm (inch)
Dehumidification Rate
mm l/h
42/34/32/29/27 6.35(1/4) 15.88(5/8) 32 / 25 2.4 Fuse, Thermal Protector Thermistor R22
Safety Devices Temperature Sensor Referigerant Referigerant Control
Capillary
Connectable Outdoor Unit Power and Transmission Interunit Cable
220/450
26(57.3) 5(11) Long Life Filter
Liquid Drain(OD/ID)
23/22/20/18/16 812/777/706/636/565
Direct 2R x 9C x 18 mm(inch) 840x840x225(33.1x33.1x8.9) mm(inch) 950x950x30(37.4x37.4x1.2)
Air Filter
Piping Connections
22/17/15/13/12 778/600/530/459/424 -
µF / Vac
Body
Sound Level (SH / H / M / L / SL)
Turbo Fan 100x1
0.3 BLDC Turbo fan 100x1
BLDC
Fan Type Air Flow Rate (SH / H / M / L / SL)
8.8
No.×mm
2
HTUC246HLA1 4x0.75
HTNC368DLA0
3/380-415/50 10.6 36, 000 -
0.4 BLDC Turbo fan 124x1 37/27/21/20/17 1,307/954/742/706/600
-
680 / 400 220/450 Direct Direct 2R x 12C x 19 2R x 9C x 18 840x840x225(33.1x33.1x8.9) 840x840x288(33.1x33.1x11.3) 950x950x30(37.4x37.4x1.2) 950x950x30(37.4x37.4x1.2) 33(72.7) 26(57.3) 5(11) 5(11) Long Life Filter Long Life Filter 51/44/39/38/35 44/42/40/37/35 6.35(1/4) 6.35(1/4) 15.88(5/8) 15.88(5/8) 32 / 25 32 / 25 3. 8 3.4 Fuse, Thermal Protector Fuse, Thermal Protector Thermistor Thermistor R22 R22 Capillary Capillary HTUC368DLA0 HTUC306HLA0 4x0.75 4x0.75
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code. 3. The specification may be subject to change without prior notice for purpose of improvement.
2008 Product Data
13
Model No : HTNC368DLA1,HTN488DLA0,HTNC488DLA1
Indoor Unit Power Supply Cooling Capacity
kW
Heating Capacity Current
HTNC368DLA1 Ø / V / Hz
Dimensions (W x H x D) Net Weight
Row × Column × FPI Body Decorative Panel Body Decorative Panel
Air Filter Sound Level (SH / H / M / L / SL) Piping Connections
Liquid Gas Drain(OD/ID)
Dehumidification Rate
-
-
-
-
-
A
0.4 BLDC Turbo fan
0.4 BLDC
0.4 BLDC Turbo fan
Turbo fan 124x1 43/36/31/27/23
124x1 43/36/31/27/23
1,519/1,271/1,095/954/812
1,519/1,271/1,095/954/812
124x1
CMM cfm
37/27/21/20/17 1,307/954/742/706/600
mmAq
-
µF / Vac
680 / 400 Direct 2R x 12C x 19
-
680 / 400 Direct
l/h
3. 8 Fuse, Thermal Protector Thermistor R22 Capillary
Temperature Sensor Referigerant Referigerant Control Connectable Outdoor Unit No.×mm
2
HTUC368DLA1 4x0.75
4.6 Fuse, Thermal Protector Thermistor R22 Capillary HTUC488DLA0 4x0.75
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code. 3. The specification may be subject to change without prior notice for purpose of improvement.
14 Ceiling cassette type (50Hz,R22)
-
680 / 400 Direct
2R x 12C x 19 2R x 12C x 19 mm(inch) 840x840x288(33.1x33.1x11.3) 840x840x288(33.1x33.1x11.3) 840x840x288(33.1x33.1x11.3) 950x950x30(37.4x37.4x1.2) mm(inch) 950x950x30(37.4x37.4x1.2) 950x950x30(37.4x37.4x1.2) 33(72.7) kg (lbs) 33(72.7) 33(72.7) 5(11) 5(11) kg (lbs) 5(11) Long Life Filter Long Life Filter Long Life Filter dB(A)+3 51/44/39/38/35 53/49/46/43/40 53/49/46/43/40 mm (inch) 6.35(1/4) 9.52(3/8) 9.52(3/8) mm (inch) 15.88(5/8) 19.05(3/4) 19.05(3/4) 32 / 25 mm 32 / 25 32 / 25
Safety Devices
Power and Transmission Interunit Cable
-
kW
Drive Coil
14.1 48,000
Btu/h
Motor Output(W) x No. of Unit
Capacitor
3/380-415/50
36, 000
Fan Type
External Static Pressure
HTNC488DLA1
3/380-415/50
Btu/h
Motor Type
Fan
HTNC488DLA0
14.1 48,000
Nominal Running Current
Air Flow Rate (SH / H / M / L / SL)
3/380-415/50 10.6
4.6 Fuse, Thermal Protector Thermistor R22 Capillary HTUC488DLA1 4x0.75
Model No : HTUC186HLA0,HTUC186HLA1,HTUC246HLA0 Outdoor unit Nominal Capacity (Min∼Rating∼Max) Nominal Input (Min∼Rating∼Max) Testing Combination Running Current(Rating) Starting Current Power Supply Power Supply Cable(Outdoor)
Cooling Heating Cooling Heating Cooling Heating Cooling/Heating
kW Btu/h kW Btu/h kW kW
Power and Transmission Cable(BD to Indoor) WxHxD
Net Weight Max. Number of Connectable Indoor Units Type Qty x Model Compressor (#1) Motor type Oil charge volume Oil Type Cycle A Charge (at 7.5m) Cycle B Charge (at 7.5m) Refrigerant Type Control Additional Refrigerant Charge (Rows x Column x FPI) × No. Heat Exchanger Defrosting Method Capacitor Drive Fan Discharge Direction(Side/Top) Air Flow Rate×No. of Fan Sound Level Sound Pressure Liquid(Cycle A) Gas(Cycle A) Piping Connections Liquid(Cycle B) Gas(Cycle B) High Pressure Gas Total Piping Max. Interunit Main Piping Piping Length Total Branch Piping Each Branch Piping Max. Elevation Outdoor Unit~Indoor Unit Difference Indoor Unit~Indoor Unit Cooling Operation Range (Outdoor) Heating
HTUC186HLA1
HTUC246HLA0
5.3
5.3
7.0
18,000
18,000 1.55
24,000 2.28 12.0 1/220~240/50
1.71
A A A Ø / V / Hz
7.75 1/220~240/50
7.75 1/220~240/50
2
3 × 1.5
2
4 × 0.75(Including Earth)
2
-
-
-
mm(inch)
870×655×320(34.2×25.8×12.6)
870×655×320(34.2×25.8×12.6)
870×655×320(34.2×25.8×12.6)
kg(lbs)
57(125)
51(112)
1 Rotary
1 Rotary
62(136) 1 Rotary
1 × QP325PBA
1 x QJ292PBA Induction 450
No.×mm
Power and Transmission Cable(Outdoor to Indoor or Outdoor to BD)
Dimensions
HTUC186HLA0
No.×mm No.×mm
Induction
cc
700 SUNISO 4GSI
g(oz) g(oz)
g/m
1,360 (48) R22 Capillary 25 (2R × 30C × 21FPI) × 1
(2R × 30C × 21FPI) × 1
56
6.35(1/4) 12.7(1/2)
30
30
10
10
C( F)
21 ~ 43 (69.8 ~ 93.2)
21 ~ 43 (69.8 ~ 93.2)
C( F)
-
-
CMM(cfm) dB(A)+3 mm(inch) mm(inch) mm(inch) mm(inch) mm(inch) m m m m m m o
-R22 Capillary 25
6.35(1/4) 12.7(1/2)
Direct Side
o
SUNISO 4GSI 1,100 (39)
6/370 Direct Side 52(1,836) × 1 56
㎌/Vac
6/370
3 × 1.5 4 × 0.75(Including Earth)
o o
52(1,836) × 1
3 × 2.5 4 × 0.75(Including Earth)
1 x QP407PAB Induction 700 NM56 or SUNISO 4GSI 1,440 (51) R22 Capillary 30 (2R x 28C x 18FPI) x 1 6/370 Direct Side 52(1,836) × 1 56 6.35(1/4) 15.88(5/8) 30 10 21 ~ 43 (69.8 ~ 93.2) -
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m '- Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
2008 Product Data
15
Model No: HTUC246HLA1,HTUC3306HLA0,HTUC368DLA0 Outdoor unit Nominal Capacity (Min∼Rating∼Max) Nominal Input (Min∼Rating∼Max) Testing Combination Running Current(Rating) Starting Current Power Supply Power Supply Cable(Outdoor)
Cooling Heating Cooling Heating Cooling Heating Cooling/Heating
A A A Ø / V / Hz No.×mm
Power and Transmission Cable(Outdoor to Indoor or Outdoor to BD)
Power and Transmission Cable(BD to Indoor) Dimensions
kW Btu/h kW Btu/h kW kW
WxHxD
Net Weight Max. Number of Connectable Indoor Units Type Qty x Model Compressor (#1) Motor type Oil charge volume Oil Type Cycle A Charge (at 7.5m) Cycle B Charge (at 7.5m) Refrigerant Type Control Additional Refrigerant Charge (Rows x Column x FPI) × No. Heat Exchanger Defrosting Method Capacitor Drive Fan Discharge Direction(Side/Top) Air Flow Rate×No. of Fan Sound Level Sound Pressure Liquid(Cycle A) Gas(Cycle A) Piping Connections Liquid(Cycle B) Gas(Cycle B) High Pressure Gas Total Piping Max. Interunit Main Piping Piping Length Total Branch Piping Each Branch Piping Max. Elevation Outdoor Unit~Indoor Unit Difference Indoor Unit~Indoor Unit Cooling Operation Range (Outdoor) Heating
No.×mm
2 2 2
HTUC246HLA1
HTUC306HLA0
HTUC368DLA0
7.0
8.8 30,000
10.6 36,000 3.50
24,000 2.33 11.0 1/220~240/50 3 × 2.5 4 × 0.75(Including Earth)
15.0
6.0
1/220~240/50
3/380~415/50
3 × 2.5 4 × 0.75(Including Earth)
4 × 4.0 4 × 0.75(Including Earth)
-
-
-
mm(inch)
870×655×320(34.2×25.8×12.6)
870×800×320(34.2×31.4×12.6)
900×1,160×370(35.4×45.7×14.6)
kg(lbs)
62(136) 1 Rotary
73(160)
81(178) 1
1 x QP407PAB
1 x NHT52VBAT Induction 1,300
No.×mm
cc
Induction 700 NM56 or SUNISO 4GSI
g(oz) g(oz)
g/m
㎌/Vac
CMM(cfm) dB(A)+3 mm(inch) mm(inch) mm(inch) mm(inch) mm(inch) m m m m m m o o
1 Rotary
DIAMOND MS56
1,520 (53.6) R22 Capillary 30
2,000 (70.5)
(2R x 28C x 18FPI) x 1 6/370 Direct Side
(2R x 36C x 18FPI) x 1
52(1,836) × 1 53 6.35(1/4) 15.88(5/8) 30
-R22 Capillary 40 6/370 Direct Side 53(1,873.5) × 1 54 6.35(1/4) 15.88(5/8) 30
10
10
C( F)
21 ~ 43 (69.8 ~ 93.2)
21 ~ 43 (69.8 ~ 93.2)
C( F)
-
-
o o
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m '- Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
16 Ceiling Cassette Type (50Hz,R22)
3.05
Scroll 1 x SQ042YAA Induction 1,300 SUNISO 4GSI 2,000 (70.5) R22 Capillary 40 (1R x 22C x 17FPI) x 2 6/370 Direct Side 53(1,873.5) × 1 58 6.35(1/4) 15.88(5/8) 30 15 21 ~ 43 (69.8 ~ 93.2) -
Model No: HTUC368DLA1,HTUC488DLA0,HTUC488DLA1 Outdoor unit Nominal Capacity (Min∼Rating∼Max) Nominal Input (Min∼Rating∼Max) Testing Combination Running Current(Rating) Starting Current Power Supply Power Supply Cable(Outdoor)
Cooling Heating Cooling Heating Cooling Heating Cooling/Heating
A A A Ø / V / Hz No.×mm
Power and Transmission Cable(Outdoor to Indoor or Outdoor to BD)
Power and Transmission Cable(BD to Indoor) Dimensions
kW Btu/h kW Btu/h kW kW
WxHxD
Net Weight Max. Number of Connectable Indoor Units Type Qty x Model Compressor (#1) Motor type Oil charge volume Oil Type Cycle A Charge (at 7.5m) Cycle B Charge (at 7.5m) Refrigerant Type Control Additional Refrigerant Charge (Rows x Column x FPI) × No. Heat Exchanger Defrosting Method Capacitor Drive Fan Discharge Direction(Side/Top) Air Flow Rate×No. of Fan Sound Level Sound Pressure Liquid(Cycle A) Gas(Cycle A) Piping Connections Liquid(Cycle B) Gas(Cycle B) High Pressure Gas Total Piping Max. Interunit Main Piping Piping Length Total Branch Piping Each Branch Piping Max. Elevation Outdoor Unit~Indoor Unit Difference Indoor Unit~Indoor Unit Cooling Operation Range (Outdoor) Heating
No.×mm No.×mm
2 2 2
HTUC368DLA1
HTUC488DLA0
HTUC488DLA1
10.6 36,000
14.1 48,000
14.1 48,000
-
-
-
3.93
5.0
4.9
-
-
-
7.0
8.5
8.5
-
-
-
3 / 380 ~ 415 / 50 4 × 4.0 4 × 0.75(Including Earth)
-
mm(inch)
870×800×320(34.2×31.4×12.6)
kg(lbs)
79(173) 1
cc g(oz) g(oz)
g/m
CMM(cfm) dB(A)+3 mm(inch) mm(inch) mm(inch) mm(inch) mm(inch) m m m m m m o o
o
C( F) o
C( F)
4 × 4.0
4 × 0.75(Including Earth)
4 × 0.75(Including Earth)
-
-
900×1,160×370(35.4×45.7×14.6) 900×1,160×370(35.4×45.7×14.6)
87(192) 1
Scroll
Scroll 1 x SB061YAA Induction 1,650
SUNISO 4GSI
SUNISO 4GSI
2,100(74)
R22 Capillary 60 (2R x 30C x 17FPI) x 1
3 / 380 ~ 415 / 50
4 × 4.0
1 x SR049YAA Induction 1,800
-
㎌/Vac
3 / 380 ~ 415 / 50
2,600(92)
87(192) 1 Scroll 1 x SB061YAA Induction 1,650 SUNISO 4GSI 2,600(92)
--
R22 Capillary 60 (2R x 26C x 18FPI) x 2
R22 Capillary 50 (2R x 26C x 18FPI) x 2
-
-
6/370 Direct Side 53(1,873.5) × 1 54 6.35(1/4) 15.88(5/8)
6/370 Direct Side 53(1,873.5) × 2
6/370 Direct Side 53(1,873.5) × 2
59 9.52(3/8) 19.05(6/8)
59 9.52(3/8) 19.05(6/8)
-
-
-
50
30
50
15
15
-
-
-
21~ 43 (69.8~93.2)
-
-
-
21~ 43 (69.8~93.2)
15
-
21~ 43 (69.8~93.2)
-
-
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m '- Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
2008
17
6. Dimensional Drawings 6.1 Indoor Units Model No : HTNC186HLA0,HTNC186HLA1,HTNC246HLA0,HTNC246HLA1,HTNC306HLA0, HTNC368DLA0, HTNC368DLA1,HTNC488DLA0,HTNC488DLA1
875 (Ceiling opening) 785(Hanging bolt)
L1 950
840 Unit size 840 Unit size
950 950 5
875 (Ceiling opening)
45
101.5 672 (Hanging bolt) 101.5
45
Unit:mm
840
785
840
950
678
30
6
(unit : mm)
L1
L2
L3
L5
1
140
L4
288
47
90
HTNC368DLA0 HTNC368DLA1 HTNC488DLA0 HTNC488DLA1
84
90
70.4 139.8
3
210.5 152
52
: mm)
Descripition Number
Name
1 2
Liquid pipe connection Gas pipe connection
3 4
Drain pipe connection Power supply connection
5
Air discharge grille
6
Air suction grille
18 Ceiling Cassette (50Hz,R22)
HTNC186HLA0, HTNC246HLA0, HTNC368DLA0 HTNC306HLA0, HTNC186HLA1 HTNC246HLA1 HTNC368DLA1
ø 6.35 ø 12.70 -
ø 6.35 ø 15.88 -
ø 6.35 ø 15.88 -
ø 6.35 ø 15.88
2
110
L2 L5
225
L1
110
HTNC186HLA0 HTNC186HLA1 HTNC246HLA0 HTNC246HLA1 HTNC306HLA0
(unit
L4
30
Model
40
4
-
HTNC488DLA0 HTNC488DLA1
ø 9.52 ø 19.05
-
L3
Dimension
6. Dimensional Drawings 6.2 Outdoor Units Model No : HTUC186HLA0,HTUC186HLA1,HTUC246HLA0,HTUC246HLA1, HTU306HLA0,HTUC368DLA1 W
Air discharge grille
(18k,24k) (30k)
Model Dimensions W mm H mm D mm L1 mm L2 mm L3 mm L4 mm L5 mm L6 mm L7 mm L8 mm L9 mm L10 mm L11 mm 1 mm 2 mm
HTUC186HLA0 HTUC246HLA0 HTUC186HLA1 HTUC246HLA1 870 655 320 370 25 340 775 25 546 162 162 54 74.5 79 Ø6.35 Ø12.70
870 655 320 370 25 340 775 25 546 162 162 54 74.5 79 Ø6.35 Ø15.88
HTUC306HLA0 HTUC368DLA1 870 800 320 370 25 340 775 25 546 162 162 54 74. 5 79 Ø6.35 Ø15.88
2008 Product Data
19
6. Dimensional Drawings Model : HTUC368DLA0, HTUC488DLA0,HTUC488DLA1 4-hole for anchor bolts
L1
L2
D
L3
W
L4
H
Control cover
Liquid side 3-way valve
L5
L10 L11
Gas side 3-way valve
L7
L6
Mdel Dimensions W mm H mm D mm L1 mm L2 mm L3 mm L4 mm L5 mm L6 mm L7 mm L8 mm L9 mm L10 mm L11 mm mm 1 2 mm
20 Ceiling Cassette(50Hz,R22)
L8
L9
HTUC368DLA0
900 1,160 370 460 45 410 1,135 30 550 175 175 112 120 83 Ø6.35 Ø15.88
HTUC488DLA0 HTUC488DLA1
900 1,160 370 460 45 410 1,135 30 550 175 175 112 120 83 Ø9.52 Ø19.05
7. Wiring Diagrams 7.1 Indoor Wiring Diagrams Model No : HTNC186HLA0, HTNC186HLA1, HTNC246HLA0, HTNC246HLA1, HTNC306HLA0
Option
CONNECTOR NUMBER
LOCATION
CN-POWER
AC POWER SUPPLY
CN-MOTOR
BLDC FAN MOTOR OUTPUT
CN-D/PUMP
DRAIN PUMP OUTPUT
CN-DISP
DISPLAY
CN-FLOAT
FLOAT SWITCH INPUT
CN-REMO
REMOTE CONTROL
CN-GRILLE
ELEVATION TWILLE
CN-CC
CENTRAL CONTROL
CN-PIPE1
DISCHARGE PIPE SENSOR
CN-ROOM
ROOM SENSOR
CN-HVB
AIR CLEANER
CN-VANE1
STEP MOTOR
CN-VANE2
STEP MOTOR
2008 Product Data
21
7. Wiring Diagrams Model No : HTNC368DLA0,HTNC368DLA1,HTNC488DLA0,HTNC488DLA1
Option
CONNECTOR NUMBER
LOCATION
CN-POWER
AC POWER SUPPLY
CN-MOTOR
BLDC FAN MOTOR OUTPUT
CN-D/PUMP
DRAIN PUMP OUTPUT
CN-DISP
DISPLAY
CN-FLOAT
FLOAT SWITCH INPUT
CN-REMO
REMOTE CONTROL
CN-GRILLE
ELEVATION TWILLE
CN-CC
CENTRAL CONTROL
CN-PIPE1
DISCHARGE PIPE SENSOR
CN-ROOM
ROOM SENSOR
CN-HVB
AIR CLEANER
CN-VANE1
STEP MOTOR
CN-VANE2
STEP MOTOR
22 Ceiling Cassette(50Hz,R22)
7. Wiring Diagrams 7.2 Outdoor Wiring Diagrams Model No : HTUC186HLA0, HTUC186HLA1, HTUC246HLA0, HTUC246HLA1
Model No : HTUC368DLA1
Model No : HTUC306HLA0
OUTDOOR WIRING DIAGRAM
Notes: CM BR WH
COMPRESSOR BROWN WHITE
BL OR YL
BLUE ORANGE YELLOW
BK RD GN/YL
BLACK RED GREEN/YELLOW
2008 Product Data
23
7. Wiring Diagrams Model No : HTUC368DLA0, HTUC488DLA0
(U)
(V)
Model No : HTUC488DLA1
(W)
3854A20072Z
Notes: CM BR WH
COMPRESSOR BROWN WHITE
24 Ceiling Cassette(50Hz,R22)
BL OR YL
BLUE ORANGE YELLOW
BK RD GN/YL
BLACK RED GREEN/YELLOW
8. Refrigerant Cycle Diagrams Model No: HT-C186HLA0 , HT-C186HLA1, HT-C246HLA0 ,HT-C246HLA1, HT-C306HLA0 , HT-C368DLA0, HT-C368DLA1, HT-C488DLA0, HT-C488DLA1 INDOOR UNIT
OUTDOOR UNIT
CAPILLARY TUBE
INDOOR COIL
LIQUID SIDE CAPILLARY TUBE
OUTDOOR COIL
Th1
Th2
COMPRESSOR
GAS SIDE
COOLING
Th1 : Temp. thermistor Th2 : Pipe in thermistor
Refrigerant pipe connection part diameter
Model
Field Piping
Gas(mm)
Liquid(mm)
HT-C186HLA0,HT-C186HLA1
Ø12.70
Ø6.35
HT-C246HLA0,HT-C246HLA1
Ø15.88
Ø6.35
HT-C306HLA0
Ø15.88
Ø6.35
HT-C368DLA0,HT-C368DLA1
Ø15.88
Ø6.35
HT-C488DLA0,HT-C488DLA1
Ø19.05
Ø9.52
2008 Product Data
25
9. Selection Procedure Step 1. Determine cooling load requirements at design conditions. Required load conditions: Required cooling capacity (TC) .............................. 24,000 Btu/h Sensible capacity (SHC) ........................................ 20,200 Btu/h Temperature air entering Outdoor Unit ................. 95°F Temperature air entering Indoor Unit ..................... 80.6 °F DB/66.2°FWB DB — dry bulb temperature WB — wet bulb temperature Step 2. Select unit based on required cooling capacity. Based on Total Cooling Capacity, choose suitable model from the specification table. The model with net cooling capacity of 24,000 Btu/h is selected. The system is HT-C246HLA0. Verify the unit performance at the given conditions in accordance with step 3. Step 3. Determine if system selected satisfies cooling requirements. Enter cooling capacities table on page 30 at high speed and 95°F outdoor entering air temperature with 80.6°FDB/66.2°FWB indoor entering air temperature. Total cooling capacity = 24,000 Btu/h, Sensible capacity=20,200 Btu/h To find capacity at intermediate conditions not in the table ; Interpolation should be used when design conditions are between two numbers that are in the capacity table. Extra-polation is not recommended. If the interconnecting piping length is more than 7.5 m ; Find the capacity(%) at that particular interconnecting piping length from the coefficient of capacity change graph, on page 33. . Multiply coefficient factor with Total Cooling Capacity & Sensible Capacity. Ex: At 30m interconnecting piping length, from coefficient of capacity change graph, coeffienct factor is 0.915.
Total Cooling Capacity =
Capacity (%) x Total Cooling Capacity 91.5x24,000 = = 21,960 Btu/h 100 100
91.5x19,300 Sensible Capacity = Capacity (%) x Sensible Capacity = = 18,483 Btu/h 100 100
26 Ceiling Cassette(50Hz,R22)
10. Performance Data Cooling Capacity(SI Unit) Model No : HT-C186HLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
TC 4.3 5.0 5.6 5.8 6.4 6.6
20 SHC 3.5 4.0 4.4 4.5 4.8 4.9
PI 1.12 1.14 1.16 1.17 1.2 1.2
TC 4.2 4.9 5.5 5.7 6.3 6.5
25 SHC 3.5 4.0 4.3 4.5 4.7 4.8
PI 1.3 1.3 1.4 1.4 1.4 1.4
Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 4.0 3.4 1.5 3.9 3.3 1.6 4.7 3.9 1.6 4.5 3.8 1.7 5.2 4.2 1.6 5.0 4.1 1.7 5.4 4.3 1.6 5.3 4.2 1.7 6.0 4.6 1.6 5.8 4.5 1.7 6.2 4.6 1.7 6.0 4.5 1.8
TC 3.7 4.3 4.9 5.1 5.6 5.8
40 SHC 3.3 3.7 4.0 4.1 4.3 4.4
PI 1.7 1.8 1.8 1.8 1.8 1.9
TC 3.6 4.2 4.7 5.0 5.4 5.7
43 SHC 3.2 3.6 3.9 4.0 4.3 4.3
PI 1.8 1.8 1.8 1.9 1.9 1.9
PI 1.2 1.2 1.2 1.3 1.3 1.3
Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 4.0 3.6 1.4 3.9 3.5 1.5 4.7 4.0 1.4 4.5 4.0 1.5 5.2 4.4 1.4 5.0 4.3 1.5 5.4 4.5 1.5 5.3 4.4 1.6 6.0 4.8 1.5 5.8 4.7 1.6 6.2 4.9 1.5 6.0 4.7 1.6
TC 3.7 4.3 4.9 5.1 5.6 5.8
40 SHC 3.4 3.9 4.2 4.3 4.6 4.6
PI 1.6 1.6 1.6 1.6 1.7 1.7
TC 3.6 4.2 4.7 5.0 5.4 5.7
43 SHC 3.4 3.8 4.1 4.2 4.5 4.5
PI 1.6 1.6 1.7 1.7 1.7 1.8
PI 1.8 1.8 1.8 1.9 1.9 1.9
Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 5.3 4.8 2.1 5.2 4.7 2.2 6.2 5.4 2.1 6.0 5.3 2.2 6.9 5.9 2.1 6.7 5.7 2.2 7.3 6.0 2.2 7.0 5.9 2.3 8.0 6.4 2.2 7.7 6.2 2.3 8.3 6.5 2.2 8.0 6.3 2.3
Model No : HT-C186HLA1 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
TC 4.3 5.0 5.6 5.8 6.4 6.6
20 SHC 3.7 4.2 4.6 4.7 5.0 5.1
PI 1.02 1.03 1.05 1.06 1.1 1.1
TC 4.2 4.9 5.5 5.7 6.3 6.5
25 SHC 3.7 4.2 4.5 4.7 5.0 5.0
Model No : HT-C246HLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
TC 5.7 6.7 7.4 7.8 8.5 8.9
20 SHC 4.9 5.6 6.1 6.3 6.7 6.8
PI 1.49 1.52 1.54 1.57 1.6 1.6
TC 5.6 6.5 7.3 7.6 8.3 8.7
25 SHC 4.9 5.6 6.0 6.2 6.6 6.7
TC 5.0 5.8 6.5 6.8 7.4 7.7
40 SHC 4.6 5.2 5.6 5.8 6.1 6.1
PI 2.3 2.3 2.4 2.4 2.5 2.5
TC 4.9 5.7 6.3 6.6 7.3 7.5
43 SHC 4.5 5.1 5.5 5.7 6.0 6.0
PI 2.4 2.4 2.5 2.5 2.5 2.6
43 SHC 4.2 4.8 5.2 5.3 5.6 5.7
PI 2.44 2.48 2.52 2.56 2.59 2.63
Model No : HT-C246HLA1 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
TC 5.7 6.7 7.4 7.8 8.5 8.9
20 SHC 4.7 5.3 5.7 5.9 6.3 6.4
PI 1.53 1.55 1.57 1.60 1.62 1.64
TC 5.6 6.5 7.3 7.6 8.3 8.7
25 SHC 4.6 5.2 5.7 5.9 6.2 6.3
PI 1.81 1.84 1.87 1.90 1.92 1.95
◆Symbol AFR : Air Flow Rate [CMM] DB : Dry Bulb Temperature [°C] WB : Wet Bulb Temperature [°C] TC : Total Capacity [kW] SHC : Sensible Heating Capacity [kW] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)
Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 5.3 4.5 2.11 5.2 4.4 2.22 6.2 5.1 2.14 6.0 5.0 2.26 6.9 5.5 2.17 6.7 5.4 2.29 7.3 5.7 2.21 7.0 5.6 2.33 8.0 6.0 2.24 7.7 5.9 2.36 8.3 6.1 2.27 8.0 5.9 2.39
TC 5.0 5.8 6.5 6.8 7.4 7.7
40 SHC 4.3 4.9 5.2 5.4 5.7 5.8
PI 2.36 2.40 2.44 2.48 2.51 2.55
TC 4.9 5.7 6.3 6.6 7.3 7.5
◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
2008 Product Data
27
10. Performance Data Model No : HT-C306HLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
20 TC SHC 7.1 5.4 8.3 6.2 9.3 6.7 9.7 7.0 10.7 7.4 11.1 7.5
PI 2.00 2.03 2.06 2.10 2.1 2.2
25 TC SHC 7.0 5.4 8.1 6.1 9.1 6.7 9.5 6.9 10.4 7.3 10.8 7.4
PI 2.4 2.4 2.4 2.5 2.5 2.6
Outdoor Air Temperature 32 TC SHC PI TC 6.7 5.3 2.8 6.5 7.8 5.9 2.8 7.5 8.7 6.4 2.8 8.4 9.1 6.7 2.9 8.8 9.9 7.0 2.9 9.6 10.3 7.1 3.0 10.0
(°CDB) 35 SHC PI 5.1 2.9 5.8 3.0 6.3 3.0 6.5 3.1 6.9 3.1 7.0 3.1
40 43 TC SHC PI TC SHC 6.2 5.0 3.1 6.1 5.0 7.2 5.7 3.1 7.1 5.6 8.1 6.1 3.2 7.9 6.0 8.5 6.3 3.2 8.3 6.2 9.3 6.7 3.3 9.1 6.6 9.6 6.8 3.3 9.4 6.6
PI 3.2 3.2 3.3 3.4 3.4 3.4
Model No : HT-C368DLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
TC 8.6 10.0 11.1 11.7 12.8 13.3
20 SHC 7.2 8.2 8.9 9.3 9.8 10.0
PI 2.29 2.33 2.36 2.40 2.4 2.5
TC 8.4 9.8 10.9 11.4 12.5 13.0
25 SHC 7.2 8.1 8.8 9.1 9.7 9.8
PI 2.7 2.8 2.8 2.8 2.9 2.9
Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 8.0 7.0 3.2 7.7 6.8 3.3 9.3 7.9 3.2 9.0 7.7 3.4 10.4 8.6 3.3 10.1 8.4 3.4 10.9 8.9 3.3 10.6 8.7 3.5 11.9 9.4 3.4 11.6 9.1 3.5 12.4 9.5 3.4 12.0 9.3 3.6
TC 7.5 8.7 9.7 10.2 11.1 11.6
40 SHC 6.7 7.6 8.2 8.4 8.9 9.0
PI 3.6 3.6 3.7 3.7 3.8 3.8
TC 7.3 8.5 9.5 9.9 10.9 11.3
43 SHC 6.6 7.4 8.0 8.3 8.7 8.8
PI 3.7 3.7 3.8 3.8 3.9 4.0
Model No : HT-C368DLA1 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
TC 8.6 10.0 11.1 11.7 12.8 13.3
20 SHC 7.5 8.5 9.3 9.6 10.2 10.3
PI 2.57 2.61 2.65 2.70 2.7 2.8
TC 8.4 9.8 10.9 11.4 12.5 13.0
25 SHC 7.4 8.4 9.2 9.5 10.0 10.2
PI 3.0 3.1 3.1 3.2 3.2 3.3
◆Symbol AFR : Air Flow Rate [CMM] DB : Dry Bulb Temperature [°C] WB : Wet Bulb Temperature [°C] TC : Total Capacity [kW] SHC : Sensible Heating Capacity [kW] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)
28 Ceiling Cassette(50Hz, R22)
Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC 8.0 7.2 3.6 7.7 7.1 9.3 8.2 3.6 9.0 8.0 10.4 8.9 3.7 10.1 8.7 10.9 9.2 3.7 10.6 9.0 11.9 9.7 3.8 11.6 9.5 12.4 9.8 3.8 12.0 9.6
PI TC 3.74 7.5 3.80 8.7 3.86 9.7 3.93 10.2 3.98 11.1 4.03 11.6
40 SHC 6.9 7.8 8.5 8.7 9.2 9.3
PI 4.0 4.0 4.1 4.2 4.2 4.3
43 TC SHC PI 7.3 6.8 4.1 8.5 7.7 4.2 9.5 8.3 4.2 9.9 8.6 4.3 10.9 9.0 4.4 11.3 9.2 4.4
◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
10. Performance Data Cooling Capacity(SI Unit) Model No : HT-C488DLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
TC 11.4 13.3 14.9 15.5 17.1 17.7
20 SHC 9.1 10.3 11.2 11.6 12.3 12.5
PI 3.28 3.33 3.38 3.43 3.5 3.5
TC 11.2 13.0 14.5 15.2 16.7 17.3
25 SHC 9.0 10.2 11.1 11.4 12.1 12.3
PI 3.9 3.9 4.0 4.1 4.1 4.2
Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 10.6 8.7 4.5 10.3 8.6 4.8 12.4 9.9 4.6 12.0 9.7 4.8 13.9 10.7 4.7 13.4 10.5 4.9 14.5 11.1 4.7 14.1 10.8 5.0 15.9 11.7 4.8 15.4 11.4 5.1 16.5 11.9 4.9 16.0 11.6 5.1
TC 9.9 11.6 12.9 13.5 14.9 15.4
40 SHC 8.4 9.5 10.2 10.6 11.1 11.3
PI 5.1 5.2 5.2 5.3 5.4 5.5
TC 9.7 11.3 12.6 13.2 14.5 15.1
43 SHC 8.3 9.3 10.1 10.4 10.9 11.1
PI 5.2 5.3 5.4 5.5 5.6 5.6
Model No : HT-C488DLA1 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
TC 11.4 13.3 14.9 15.5 17.1 17.7
20 SHC 9.2 10.4 11.3 11.7 12.4 12.6
PI 3.21 3.26 3.31 3.37 3.4 3.5
TC 11.2 13.0 14.5 15.2 16.7 17.3
25 SHC 9.1 10.3 11.2 11.6 12.3 12.5
PI 3.8 3.9 3.9 4.0 4.0 4.1
Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC 10.6 8.9 4.4 10.3 8.7 12.4 10.0 4.5 12.0 9.8 13.9 10.9 4.6 13.4 10.6 14.5 11.2 4.7 14.1 11.0 15.9 11.9 4.7 15.4 11.6 16.5 12.0 4.8 16.0 11.7
◆Symbol AFR : Air Flow Rate [CMM] DB : Dry Bulb Temperature [°C] WB : Wet Bulb Temperature [°C] TC : Total Capacity [kW] SHC : Sensible Heating Capacity [kW] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)
PI 4.7 4.7 4.8 4.9 5.0 5.0
TC 9.9 11.6 12.9 13.5 14.9 15.4
40 SHC 8.5 9.6 10.4 10.7 11.3 11.4
PI 5.0 5.0 5.1 5.2 5.3 5.4
TC 9.7 11.3 12.6 13.2 14.5 15.1
43 SHC 8.4 9.4 10.2 10.5 11.1 11.2
PI 5.1 5.2 5.3 5.4 5.5 5.5
◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
2008 Product Data
29
10. Performance Data Cooling Capacity(English Units) Model No : HT-C186HLA0 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6
TC 14.6 17.0 19.0 19.9 21.8 22.7
68.0 SHC 12.1 13.7 14.9 15.4 16.3 16.6
PI 1.12 1.14 1.16 1.17 1.2 1.2
TC 14.3 16.7 18.6 19.5 21.4 22.2
77.0 SHC 12.0 13.6 14.7 15.2 16.1 16.4
PI 1.3 1.3 1.4 1.4 1.4 1.4
Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 13.6 11.6 1.5 13.2 11.4 1.6 15.9 13.2 1.6 15.4 12.9 1.7 17.7 14.3 1.6 17.2 14.0 1.7 18.6 14.7 1.6 18.0 14.4 1.7 20.4 15.6 1.6 19.8 15.2 1.7 21.1 15.8 1.7 20.5 15.4 1.8
TC 12.7 14.8 16.6 17.3 19.0 19.7
104.0 SHC 11.1 12.6 13.6 14.0 14.8 15.0
PI 1.7 1.8 1.8 1.8 1.8 1.9
TC 12.4 14.5 16.2 16.9 18.6 19.3
109.4 SHC 11.0 12.4 13.4 13.8 14.5 14.7
PI 1.8 1.8 1.8 1.9 1.9 1.9
PI 1.2 1.2 1.2 1.3 1.3 1.3
Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 13.6 12.2 1.4 13.2 12.0 1.5 15.9 13.8 1.4 15.4 13.5 1.5 17.7 15.0 1.4 17.2 14.7 1.5 18.6 15.5 1.5 18.0 15.1 1.6 20.4 16.4 1.5 19.8 16.0 1.6 21.1 16.6 1.5 20.5 16.2 1.6
TC 12.7 14.8 16.6 17.3 19.0 19.7
104.0 SHC 11.7 13.2 14.3 14.7 15.5 15.7
PI 1.6 1.6 1.6 1.6 1.7 1.7
TC 12.4 14.5 16.2 16.9 18.6 19.3
109.4 SHC 11.5 13.0 14.1 14.5 15.3 15.4
PI 1.6 1.6 1.7 1.7 1.7 1.8
PI 1.8 1.8 1.8 1.9 1.9 1.9
Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 18.2 16.3 2.1 17.6 15.9 2.2 21.2 18.4 2.1 20.6 18.0 2.2 23.6 20.0 2.1 22.9 19.5 2.2 24.7 20.6 2.2 24.0 20.2 2.3 27.1 21.8 2.2 26.3 21.3 2.3 28.2 22.1 2.2 27.3 21.6 2.3
TC 17.0 19.8 22.1 23.1 25.4 26.3
104.0 SHC 15.6 17.6 19.0 19.6 20.7 21.0
PI 2.3 2.3 2.4 2.4 2.5 2.5
TC 16.6 19.3 21.6 22.6 24.8 25.7
109.4 SHC 15.4 17.3 18.7 19.3 20.3 20.6
PI 2.4 2.4 2.5 2.5 2.5 2.6
109.4 SHC 14.5 16.3 17.6 18.2 19.1 19.4
PI 2.44 2.48 2.52 2.56 2.59 2.63
Model No : HT-C186HLA1 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6
TC 14.6 17.0 19.0 19.9 21.8 22.7
68.0 SHC 12.7 14.4 15.6 16.2 17.1 17.4
PI 1.02 1.03 1.05 1.06 1.1 1.1
TC 14.3 16.7 18.6 19.5 21.4 22.2
77.0 SHC 12.5 14.2 15.5 16.0 16.9 17.2
Model No : HT-C246HLA0 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6
TC 19.5 22.7 25.3 26.5 29.1 30.2
68.0 SHC 16.9 19.2 20.8 21.6 22.9 23.2
PI 1.49 1.52 1.54 1.57 1.6 1.6
TC 19.1 22.2 24.8 26.0 28.5 29.6
77.0 SHC 16.7 19.0 20.6 21.3 22.6 22.9
Model No : HT-C246HLA1 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6
TC 19.5 22.7 25.3 26.5 29.1 30.2
68.0 SHC 15.9 18.0 19.6 20.3 21.5 21.9
PI 1.53 1.55 1.57 1.60 1.62 1.64
TC 19.1 22.2 24.8 26.0 28.5 29.6
77.0 SHC 15.7 17.8 19.4 20.0 21.2 21.6
PI 1.81 1.84 1.87 1.90 1.92 1.95
Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 18.2 15.3 2.11 17.6 15.0 2.22 21.2 17.3 2.14 20.6 17.0 2.26 23.6 18.8 2.17 22.9 18.4 2.29 24.7 19.4 2.21 24.0 19.0 2.33 27.1 20.5 2.24 26.3 20.0 2.36 28.2 20.8 2.27 27.3 20.3 2.39
◆Symbol AFR : Air Flow Rate [CFM] DB : Dry Bulb Temperature [°F] WB : Wet Bulb Temperature [°F] TC : Total Capacity [kBtu/h] SHC : Sensible Heating Capacity [kBtu/h] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)
30 Ceiling Cassette (50Hz,R22)
TC 17.0 19.8 22.1 23.1 25.4 26.3
104.0 SHC 14.7 16.6 17.9 18.5 19.5 19.7
PI 2.36 2.40 2.44 2.48 2.51 2.55
TC 16.6 19.3 21.6 22.6 24.8 25.7
◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6ft - Level Difference of Zero.
10. Performance Data Cooling Capacity(English Units)
Model No : HT -C306HLA0 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6
TC 24.3 28.4 31.7 33.2 36.4 37.8
68.0 SHC 18.6 21.1 23.0 23.7 25.2 25.6
PI 2.00 2.03 2.06 2.10 2.12 2.15
TC 23.8 27.8 31.0 32.5 35.6 37.0
77.0 SHC 18.4 20.9 22.7 23.5 24.9 25.2
PI 2.37 2.41 2.44 2.48 2.51 2.55
Outdoor Air 89.6 TC SHC 22.7 17.9 26.5 20.3 29.5 22.0 30.9 22.7 33.9 24.0 35.2 24.4
Temperature (°FDB) 95.0 PI TC SHC PI 2.76 22.0 17.5 2.91 2.80 25.7 19.9 2.95 2.85 28.7 21.5 3.00 2.90 30.0 22.2 3.05 2.93 32.9 23.4 3.09 2.98 34.2 23.8 3.13
TC 21.2 24.7 27.6 28.9 31.7 32.9
104.0 SHC 17.2 19.4 21.0 21.6 22.8 23.1
PI 3.09 3.14 3.19 3.24 3.29 3.33
TC 20.7 24.2 27.0 28.2 31.0 32.1
109.4 SHC 16.9 19.1 20.6 21.3 22.4 22.7
PI 3.20 3.25 3.30 3.35 3.39 3.44
Model No : HT -C368DLA0 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6
TC 29.2 34.1 38.0 39.8 43.7 45.3
68.0 SHC 24.7 28.1 30.5 31.6 33.5 34.0
PI 2.29 2.33 2.36 2.40 2.4 2.5
TC 28.6 33.3 37.2 38.9 42.7 44.4
77.0 SHC 24.5 27.8 30.2 31.2 33.0 33.6
PI 2.7 2.8 2.8 2.8 2.9 2.9
Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 27.2 23.8 3.2 26.4 23.3 3.3 31.8 27.0 3.2 30.8 26.4 3.4 35.5 29.3 3.3 34.4 28.6 3.4 37.1 30.2 3.3 36.0 29.5 3.5 40.7 31.9 3.4 39.5 31.2 3.5 42.3 32.4 3.4 41.0 31.6 3.6
TC 25.4 29.7 33.1 34.7 38.0 39.5
104.0 SHC 22.8 25.8 27.9 28.8 30.3 30.7
PI 3.6 3.6 3.7 3.7 3.8 3.8
TC 24.8 29.0 32.4 33.9 37.2 38.6
109.4 SHC 22.5 25.4 27.4 28.3 29.8 30.1
PI 3.7 3.7 3.8 3.8 3.9 4.0
PI 3.0 3.1 3.1 3.2 3.2 3.3
Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 27.2 24.7 3.6 26.4 24.2 3.7 31.8 28.0 3.6 30.8 27.4 3.8 35.5 30.3 3.7 34.4 29.7 3.9 37.1 31.3 3.7 36.0 30.6 3.9 40.7 33.1 3.8 39.5 32.3 4.0 42.3 33.6 3.8 41.0 32.8 4.0
TC 25.4 29.7 33.1 34.7 38.0 39.5
104.0 SHC 23.7 26.7 28.9 29.8 31.4 31.8
PI 4.0 4.0 4.1 4.2 4.2 4.3
TC 24.8 29.0 32.4 33.9 37.2 38.6
109.4 SHC 23.3 26.3 28.4 29.3 30.9 31.2
PI 4.1 4.2 4.2 4.3 4.4 4.4
Model No : HT -C368DLA1 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6
TC 29.2 34.1 38.0 39.8 43.7 45.3
68.0 SHC 25.6 29.1 31.6 32.7 34.7 35.3
PI 2.57 2.61 2.65 2.70 2.7 2.8
TC 28.6 33.3 37.2 38.9 42.7 44.4
77.0 SHC 25.4 28.8 31.3 32.3 34.3 34.8
◆Symbol AFR : Air Flow Rate [CFM] DB : Dry Bulb Temperature [°F] WB : Wet Bulb Temperature [°F] TC : Total Capacity [kBtu/h] SHC : Sensible Heating Capacity [kBtu/h] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)
◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6ft - Level Difference of Zero.
2008 Product Data
31
10. Performance Data Cooling Capacity(English Units) Model No : HT-C488DLA0 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6
TC 38.9 45.4 50.7 53.0 58.2 60.4
68.0 SHC 31.0 35.1 38.2 39.5 41.9 42.6
PI 3.28 3.33 3.38 3.43 3.5 3.5
TC 38.1 44.5 49.6 51.9 57.0 59.1
77.0 SHC 30.7 34.8 37.8 39.1 41.4 42.0
PI 3.9 3.9 4.0 4.1 4.1 4.2
Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 36.3 29.8 4.5 35.2 29.2 4.8 42.4 33.8 4.6 41.1 33.0 4.8 47.3 36.6 4.7 45.9 35.8 4.9 49.5 37.8 4.7 48.0 37.0 5.0 54.3 40.0 4.8 52.7 39.0 5.1 56.4 40.6 4.9 54.7 39.6 5.1
PI 3.8 3.9 3.9 4.0 4.0 4.1
Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 36.3 30.2 4.4 35.2 29.6 4.7 42.4 34.2 4.5 41.1 33.5 4.7 47.3 37.1 4.6 45.9 36.3 4.8 49.5 38.3 4.7 48.0 37.4 4.9 54.3 40.5 4.7 52.7 39.5 5.0 56.4 41.1 4.8 54.7 40.1 5.0
TC 33.9 39.6 44.2 46.2 50.7 52.6
104.0 SHC 28.6 32.3 34.9 36.0 38.0 38.4
TC 33.9 39.6 44.2 46.2 50.7 52.6
104.0 SHC 28.9 32.7 35.4 36.5 38.4 38.9
PI 5.1 5.2 5.2 5.3 5.4 5.5
TC 33.1 38.7 43.1 45.1 49.5 51.4
109.4 SHC 28.2 31.8 34.4 35.4 37.3 37.7
PI 5.2 5.3 5.4 5.5 5.6 5.6
TC 33.1 38.7 43.1 45.1 49.5 51.4
109.4 SHC 28.5 32.2 34.8 35.9 37.8 38.2
PI 5.1 5.2 5.3 5.4 5.5 5.5
Model No : HT-C488DLA1 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6
TC 38.9 45.4 50.7 53.0 58.2 60.4
68.0 SHC 31.4 35.6 38.7 40.0 42.5 43.2
PI 3.21 3.26 3.31 3.37 3.4 3.5
TC 38.1 44.5 49.6 51.9 57.0 59.1
77.0 SHC 31.1 35.2 38.3 39.6 41.9 42.6
◆Symbol AFR : Air Flow Rate [CFM] DB : Dry Bulb Temperature [°F] WB : Wet Bulb Temperature [°F] TC : Total Capacity [kBtu/h] SHC : Sensible Heating Capacity [kBtu/h] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)
32 Ceiling Cassette (50Hz,R22)
PI 5.0 5.0 5.1 5.2 5.3 5.4
◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6ft - Level Difference of Zero.
11. The Coefficient of Capacity Change Model No : HT-C186HLA0, HT-C186HLA1,HT-C246HLA0,HT-C246HLA1,HT-C306HLA0 HT-C368DLA0,HT-C368DLA1,HT-C488DLA0,HT-C488DLA1
Cooling Capacity 100
HT-C368DLA0 HT-C186HLA0(1) HT-C488DLA0 HT-C246HLA0(1)
95
Cap ac i ty (% )
90
+ HT-C306HLA0
85 80
HT-C488DLA1
75
HT-C368DLA1
70 7. 5
10
30
20
50
To t a l Pi p e Leng t h (m )
Models
HT-C186HLA0 HT-C246HLA0 HT-C186HLA1 HT-C246HLA1
HT-C306HLA0 HT-C368DLA0
HT-C488DLA0 HT-C368DLA1
HT-C488DLA1
Additional
Refrigerant
25
30
40
40
60
50
( g/m)
Notes: * Equivalent pipe length = Actual pipe length + number of bend x 0.3 * Refer to the specification for the maximum pipe length of each model.
2008 Product Data
33
12. Operation Range
Cooling 46
Operative Operative
43 Outdoor Unit [ ℃ DB]
Continuous operation
21
Operative -5 18 Indoor Unit [℃ DB]
34
Ceiling Cassette (50Hz,R22)
32
13. Air Velocity and temperature Distributions(Reference Data) Ceiling Cassette 4 -way TH chassis (18kBtu/h) Models Air velocity [m/s]
Discharge angle : 45°
2.7m 2.0
2.0 2m
1.5
1.5
1.0
1.0
0.5
4m
3m
1m
0.5
2m
1m
0m
1m
2m
3m
0m 4m
Ceiling Cassette 4 -way TD1 chassis (36kBtu/h) Models Air velocity [m/s]
Discharge angle : 40°
2.7m 2m 2.0
2.0
1.5 0.5
4m
3m
1.5
1.0
2m
1.0
1m
0m
1m
2m
1m 0.5
3m
0m 4m
2008 Product Data
35
13. Air Velocity and temperature Distribution Ceiling Cassette 4 -way TH chassis
(18kBtu/h) Models
Temperature [ C] Discharge angle:45
2.7m 18
18
20
2m
20
22
22 1m
24 4m
3m
2m
24 1m
0m
Ceiling Cassette 4 -way TD1 chassis
1m
2m
3m
0m 4m
(36kBtu/h) Models
Temperature [ C] Discharge angle:40 2.7m
20
2m
20
22 24 4m
3m
36 Ceiling Cassette (50Hz,R22)
1m
22 24
2m
1m
0m
1m
2m
3m
0m 4m
14. Sound Levels Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operation condition - Reference accoustic pressure OdB = 20 Pa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard.
Overall Ceiling 1.5m
Sound Levels(dBA)
Model HT-C186HLA0(1) HT-C246HLA0(1) HT-C306HLA0 HT-C368DLA0(1) HT-C488DLA0(1)
SH 35 42 44 51 53
M 27 32 40 39 46
H 31 34 42 44 49
L
SL
24 29 37 38 43
20 27 35 35 40
Sound Pressure Level
90
90
90
80
80
80
NC-70 NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
70
70 NC-70 NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-25
NC-25
20
NC-15 125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20
NC-20
NC-15
10 63
8000
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
NC-15
10 63
8000
HT-C368DLA0(1)
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
HT-C488DLA0(1)
90
90
80
80
70
70 NC-70 NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20
NC-70
Sound Pressure Level (dB re 20 Pa )
63
NC-65
NC-20
NC-20 10
NC-70 60
NC-30
NC-30 20
Sound Pressure Level (dB re 20 Pa )
Sound Pressure Level (dB re 20 Pa )
70
Sound Pressure Level (dB re 20 Pa )
Sound Pressure Level (dB re 20 Pa )
HT-C306HLA0
HT-C246HLA0(1)
HT-C186HLA0(1)
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-2510
20
NC-2010
NC-20 NC-15
NC-15 63
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
63
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
2008 Product Data
37
15. Installation 15.1 Select the best location 15.1.1 Indoor Unit There should not be any heat source or steam near the unit. There should not be any obstacles to the air circulation. Taking into account the noise prevention criteria, spot the installation location. Keep proper distance of the unit from ceiling, fence, walls & other obstacles as shown figure. The indoor unit must have the maintenance space around.
20 or more
Ceiling
Ceiling Board
Ceiling Board
1500 or more
There should be easy provision of condensate drain.
1500 or more
In case of the multi flow type, use the high humidity kit. Otherwise the dew drops can be seen on the unit body.
1500 or more H Unit:mm Floor
Refrigerant piping: Increase the piping insulation thickness upto 20mm or more. Refrigerant piping
NOTE
Above figure means minimum value. Please keep these value at least. If H is 2700~3200mm: High ceiling operation control requied Others: Inside the ceiling near th air tight seal places (no escape of the humidity)
If H is ~2700: Normal operation
1500 or more 1500 or more
Grill for ventilation
Indoor unit
Indoor unit Ventilator Lighting
1500 or more
In case of multiple indoor cassette units (recommended)
1500 or more
Above 1500mm
Unit:mm
Above 2000mm Above 3000mm
38 Ceiling Cassette(50Hz, R22)
15. Installation 15.1.2 Outdoor Unit If a roof is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted. Do not place animals and plants in the path of the warm air. Take the air conditioner weight into account and select a place where noise and vibration are minimum. Select a place so that the warm air and noise from the air conditioner do not disturb neighbors. Rooftop Installations : If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
More than 30cm
Fe ob nce sta or cle s
Su
nro of
More than 30cm
M ore than than More 30cm 30cm
More than 60cm
Su
nro
Fe ob nce sta or cle s
More than 70cm
of Mo ore re tthan han 30cm 30cm
More than 50cm (Service space)
More than 60cm More than 70cm
15.2 Settlement of outdoor unit Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.
Bolt
Tubing connection
When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake. In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration rubber.
2008 Product Data
39
15. Installation 15.3 Installation guide at the seaside CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. 3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
15.3.1 Selecting the location(Outdoor Unit) 1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
Sea wind
Sea wind
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Windbreak
the sea wind from the sea. the outdoor unit.
Sea wind
between outdoor unit and the windbreak for easy air flow.
3) Select a well-drained place. 1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment. 2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water.
40
Ceiling Cassette (50Hz, R22)
15. Installation 15.4 Ceiling Opening dimensions and hanging bolt location 870 (Ceiling opening) 785(Hanging bolt)
840 Unit size
840 Unit size
672 (Hanging bolt)
TH,TD1 Chassis
870 (Ceiling opening)
The dimensions of the paper model for installing are the same as those of the ceiling opening dimensions.
Unit:mm
Select and mark the position for fixing bolts and piping hole. Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. Drill the hole for anchor bolt on the wall.
Ceiling board
CA U TI O N This air-conditioner uses a drain pump. Install the unit horizontally using a level gauge. During the installation, care should be taken not to damage electric wires.
Ceiling Level gauge
NOTE:
Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; Make sure that ventilation fan is enough to cover all noxious gases from this place. Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam. 2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.
Air conditioner
Take enough distance
Cooking table
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
2008 Product Data
41
15. Installation 15.5 The Indoor Unit Installation Ceiling
Nut (W3/8 or M10) Spring washer (M10)
Keep the length of the bolt from the bracket to 40mm Flat washer for M10 (accessory) Ceiling board
Flat washer for M10 (accessory) Nut (W3/8 or M10)
Air Conditioner body
Ceiling board
Paper model for installation Adjust the same height
The following parts are local purchasing. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10
150mm
Hanging bolt (W3/8 or M10)
Set screw of paper model (4 pieces) Open the ceiling board along the outer edge of the paper model
Drill the piping hole on the wall slightly tilted to the outdoor side using a Ă˜ 70 hole-core drill.
CA U TI O N
Wall Indoor
Outdoor
5~7mm
Tighten the nut and bolt to prevent unit from falling off.
42 Ceiling Cassette(50Hz, R22)
15. Installation 15.6 Wiring Connection 1. All wiring must comply with LOCAL REGULATIONS. 2. Select a power source that is capable of supplying the current as required by the air conditioner. 3. Feed the power source to the unit via a distribution switch board designed for this purpose. 4. The terminal screws inside the control box may be loose due to vibration during transport. Check the screws for loose connection. (Running the air conditioner with loose connection can overload and damage electrical components.) 5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.
Terminal Block in Indoor 1(L)
2(N)
3
Terminal Block in Indoor 4
1(L)
2(N)
3
Connected to indoor unit
1(L)
2(N)
3(L)
4(N)
5
6
7
Connected to indoor unit 1(R) 2(S)
8
3(T)
4(N )
6(L)
7(N)
8
9
outdoor unit
outdoor unit
Main
Main
3Ă˜,380V ,50HZ
1Ă˜ ,220V , 50Hz
The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA). 18kBtu/h
1 Phase 3 Phase 1.5mm2
24k/30kBtu/h 2.5mm
2
GN
/YL
36k/48kBtu/h 20
CAUTION The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
-
NORMAL CROSS-SECTIO NAL AREA 0.75mm2
4.0 mm 2
7.5mm
Capacity
8.5mm
4
GN /YL
mm
20 m
m
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.
WARNIN G Make sure that the screws of the terminal are free from looseness.
2008 Product Data
43
15. Installation 15.7 Piping Connection 1. Form the piping according to its routing. Avoid bending and bending back the same piping point more than three times. (This will result in hardening the pipe.) 2. After deforming the piping, align centers of the union fitting of the indoor unit and the piping, and tighten them firmly with wrenches. 3. Connect pipe to the service valve or ball valve which is located below the outdoor unit. 4. After completing the piping connection, be sure to check if there is gas leakage in indoor and outdoor connection.
15.8 Vacuum drying After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit. The vacuum drying must be carried out using the service ports of both the liquid and gas side valves.
44
Ceiling Cassette(50Hz,R22)
Liquid side Indoor unit Outdoor unit
Flare connection Gas side Flare connection
Model 18kBtu/h 24kBtu/h
Liquid side piping Gas side piping Ø 12.70mm Ø 6.35mm
30kBtu/h
Ø 6.35mm
Ø15.88mm
36kBtu/h 48kBtu/h
Ø 9.52mm
Ø19.05mm
15. Installation 15.9 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.
The decoration panel has its installation direction.
1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter). Piping side
Air conditioner unit
Decoration panel fixing screws (hexagon M5 screws) Temporally fitting at 2 places (Tightening about 10mm)
Control box cover
Louver motor Inlet Grille
Decoration panel Display Key holes Lead wire for louver motor and display
Decoration panel fixing screws (Hexagon M5 screw)
Inlet Grille
CA U TI O N Install certainly the decoration Good example panel. Cool air leakage causes sweating. Water drops fall.
Bad example Air conditioner unit Ceiling board
Decoration panel Fit the insulator (this part) and be careful for cool air leakage
Air conditioner unit Air
Cool air leakage (no good) Ceiling board Decoration panel
2008 Product Data
45
15. Installation 15.11 Drain Pipe Work Drain pipe gradient and support 1) - The drain pipe must be fitted at a gradient of at least 1/100. - The drain pipe should be as short as possible and free from airlocks. Indoor unit Gradient of at least 1 / 100 (1cm/ 1m)
2) Suspension bolts should be used to support long stretches of drain pipe in order to ensure that a gradient of 1/100 is maintained.(PVC pipe should not be bent) Spacing of supports for horizontal piping Class
Nominal diameter
Spacing
Rigid PVC pipe
25~40mm
1.0m or less
3) The length of pipe laid horizontally should be kept a minimum. Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings
Upward routing not allowed
Pipe clamp Indoor unit
Maintenance drain port
Be sure to install heat insulation on the drain piping.
1/50~1/100
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
MAX 700mm
Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:
Feed water
Flexible drain hose (accessory) Main drain pipe
Drain Pump
Drain port
Glue the joint
Drain hose connection Use the clip (accessory)
Drain pan
46
Ceiling Cassette(50Hz, R22)
Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. Feed water to the flexible drain hose and check the piping for leakage. Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. When the test is complete, connect the flexib le drain hose to the drain port on the indoor unit.
15. Installation Grouped drain piping 1) It is standard work practice to make connections to the main pipe from above. The pipe coming down from the combination should be as large as possible.
Face piping downward
Face the vent pipe mouth downward to keep foreign matter from penetrating the system Vent pipe
2) The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.
CAUTION The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.
Flexiblle Flexi ed drain rain h hose ose
1/50~1/100 MAX 700mm
CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual po w er speciali zed for the air conditioner. As for the method of w iring , b e guided b y the circuit diagram pasted on the inside of control b o x cover. 2) Provide a circuit b reaker s w itch b et w een po w er source and the unit. 3) The scre w w hich fasten the w iring in the casing of electrical fittings are lia b le to come loose from vi b rations to w hich the unit is su bj ected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose , it could give rise to b urn -out of the w ires.) 4) Specification of po w er source 5) Confirm that electrical capacity is sufficient. 6) B e sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the ca b le thickness is as specified in the po w er sources specification. (Particularly note the relation b et w een ca b le length and thickness.) 8) Never fail to equip a leakage b reaker w here it is w et or moist. 9) The follo w ing trou b les w ould b e caused b y voltage drop -do w n. Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. Proper starting power is not given to the compressor.
2008 Product Data
47
15. Installation 15.12 Optional Operation (For wire remote) 1) Two Thermistor System (1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows. Position 1: The room temperature is controlled by the thermistor of the main body. Position 2: The room themperature is controlled by the thermistor of the wired remote-controller, control the temperature according to the position of wired remote-controller. Position 3: The room temperature is controlled by lower temperature between the temperature of main body and of remote-controller sensor. (3) Move the slide switch to set position. Room Temp. sensor Slide switch for 2 Thermistor
TH
R14H OP3 SW TH
REMO MAIN 2TH
OP2
REMO MAIN 2TH R17H
R12H
CO1H
OP1 R19H R11H
OP5R16H
OP4 R15H
OP7 R18H OP6
STAND
LO
C070
Position 2 Position 1 Position 3
R13H
R03S
HI
R04S HIGH
R01S
R02S
SW
Slide switch for ceiling height
(4) Close the rear cover and check if it works normally.
CA U TI O N Select the position after counselling with a customer. In case of cooling mode, room temperature is controlled by the main body sensor. To control the room temperature by a wired remote controller, install controller(room temp. sensor) to sense the temperature more accurately. Maunfactured in the position 3.
48 Ceiling Cassette(50Hz,R22)
15. Installation 2) Adjusting air volume to the height of ceiling You can choose the RPM(or air volume) of indoor motor according to the height of ceiling to supply the comfortable atmosphere to consumers. Procedure 1. Choose the selectable position in the table after measuring the height of ceiling. Ceiling height more than 3.3m 2.7~3.3m less than 2.7m
Mode of slide switch High Ceiling Standard Low Ceiling
Change of air volume Increasing Decreasing
Remark Maunfactured in standard mode
2. In the case of changing the height as "high" or "low", open the rear cover of the wired remote-controller. Slide switch for 2 Thermistor
3. Move the slide switch to the set position.
R13H
TH
4. Close the rear cover and check if it works nomally.
Low ceiling Standard (Default) High Ceiling
STAND
Lo
OP2 R14H OP3 SW TH
REMO MAIN 2TH
Hi
R17H
R12H
CO1H
OP1 R19H R11H
OP5R16H
OP4 R15H
OP7 R18H OP6
LO
C070
STAND
R03S
HI
R04S HIGH
R01S
R02S
Slide switch for ceiling height
SW
3) Group Control(Optional Wiring) It operates maximum 16 Units by only one Wired Remote Controller, and each Unit starts sequentially to prevent overcurrent. Main PCB Wiring design Indoor Unit 1
Indoor Unit 2
Terminal(Local Supply) Block Connector
Terminal(Local Supply) Block Connector
RED(12V) YL(SIGNAL) BR(GND)
RED(12V) YL(SIGNAL) BR(GND)
Main PCB #1
YL(SIGNAL) BR(GND)
YL(SIGNAL) BR(GND)
Indoor Unit 16
Terminal(Local Supply) Block Connector
Main PCB #2
....
AUTO SWING
OPERATION
SET TEMP Room Temp
Operation unit 03
FAN SPEED HI MED LO
Time Timer
On Off Set no. Time 01
ZONE
....
YL(SIGNAL) BR(GND)
YL(SIGNAL) BR(GND)
Main PCB #16
Connecting Cable(Local Supply)
SUB FUNCTION
AUTO Heater Preheat JET Defrost Humidify Filter Out door 1 2 3 4
Program set 05
07
09
11
13
15
17
19
21
23
Wired Remote Controller
S/W GR
Single Group
Remote Controller PCB
Using the supplied Wired Remote Controller, wire them like above. Move S/W GR to "Group" position. Check the line color of the wire.
CA U TI O N Be careful not to exchange the color of wires. The maximum length of connecting wire should be below 200m(25â„Ś) on connecting each units. Use a wire more than 0.5mm2
2008 Product Data
49
16. Function of Remote Control 16.1 Wired LCD Remote Control Name and Function of Remote Control
.
AUTO SWING
OPERATION
SET TEMP Room Temp
1
2ndF Timer
FAN SPEED
Cooling Model
SUB FUNCTION
AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door ZONE 1 2 3 4
HI MED LO
Time
Operation unit No Func Program set
On Off Set no. Time 01
03
05
07
09
11
13
15
17
19
21
23
5
14 2 3 4
6 7 Timer
Cancel
2ndF
Program
Week
Holiday
8 9 10 11 12 13
PLASMA
Set/Clr Hour
Min
RESET
1 Operation indication screen
9
2 Swirl button
10
Horizontal/Vertical air flow direction button
11
Room temperature/filtersign release button Used to check the room temperature and release the filter in Second Function Mode.
12
Plasma/Heater button
Displays the operation conditions.
Used to select swirl cool mode.
3 2ndF button 4 Timer set/cancel /Program/Week
Holiday/Hour/Min/SET/Clr/Ventilator
5
Set temperature button
Fan speed button Used to set the disired fan speed.
Used plasma and saved power in Second Function.
Used to set the temperature when required.
6 ON/OFF button
13
Reset Used to set the current time and clear the setting time.
Operation starts when this button is pressed and stops when the button is pressed again.
7
Fan operation Used to circulate room air without cooling or heating.
8
Operation mode selection button Used to select the operation mode.
50
Ceiling Cassette(50Hz,R22)
Time reset button
14
Operation lamp
16. Function of Remote Control 16.2.Wireless Remote Controller Name and Function of Remote Controller
.
This air-conditione r is equipped with wired remote controller basically . Bu t if you want to be availabl e with wireles s remote controller, you pay for it. 1.START/STOP BUTTON Operation starts when this button is pressed and stops when the button is pressed again. The controls will look like the following. 2. OPERATION MODE SELECTION BUTTON Used to select the operation mode. Controls 3. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature. Signal transmitter 4. INDOOR FAN SPEED SELECTOR Used to select fan speed in four steps low, medium, high and CHAOS. 5. JET COOL Used to start or stop the speed cooling.(speed cooling operates super high fan speed in cooling mode.) 6. CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up/down airflow direction. 7. ON/OFF TIMER BUTTONS 5 1 Used to set the time of starting and stopping 6 operation. 8. TIME SETTING BUTTONS 3 Used to adjust the time. 9. TIMER SET/CANCEL BUTTON 4 Used to set the timer when the desired time 10 2 is obtained and to cancel the Timer CANCEL operation. 9 7 SET ON OFF 10. SLEEP MODE AUTO BUTTON AUTO CLEAN 12 11 Used to set Sleep Mode Auto operation. 17 8 11. AIR CIRCULATION BUTTON Used to circulate the room air without 13 14 cooling or heating. 16 15 12. ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature. 13. NEO PLASMA(OPTIONAL) Used to start or stop the plasma-purification function. Flip-up door (opened) 14. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (OPTIONAL) Used to set the desired horizontal airflow direction. 15. RESET BUTTON Used prior to resetting time. 16. 2nd F Button Used prior to using modes printed in blue at the bottom of buttons.
CAUTION:of handling the Remote Controller
17. AUTO CLEAN (OPTIONAL) Used to set Auto Clean mode.
Aim at the signal receiver on the wired remote controller so as to operate. The remote control signal can be received at a distance of up to about 7m. Be sure that there are no obstructions between the remote controller and the signal receptor. Do not drop or throw the remote controller. Do not place the remote controller in a location exposed to direct sunlight, or near the heating unit, or any other heat source. Block a strong light over the signal receptor with a curtain or etc. so as to prevent the abnormal operation. (ex:electronic quick start, ELBA, inverter type fluorescent lamp)
2008 Product Data
51
P/No.:MFL32271301
Rayong Office:
October/2008
The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.