Lg multi vrf iii mfl61741606 multi v indoor unit 10

Page 1

Indoor unit (R410A) 0CVP0-01A


Indoor unit (R410A) 0CVP0-01A General Information


Indoor unit • Introduction • General Information • Indoor Units • Dip Switch & Group Control Setting


Introduction 1. Preface

is the most favored choice when there is a need for precise air conditioning of relatively big projects extending from Multi-Room structure to big commercial places. We have a big line up, that offers wider flexibility of model selection. Equipped with inverter technology and long piping installation, the product matches well if one talk about optimum power consumption in high rise buildings. Add on capacity feature makes it easy to upgrade the existing capacity at any time. With the growing concern about environment preservation, comes with R410A refrigerant which is environment friendly and thus our system is a high technology and environment friendly product.

Unique refrigerant flow and electronic circuit control gives this system an unique capability to work in extreme/abnormal working conditions making our customer feel great about their decision of selecting LG as their first choice. This publication provides a detailed and in depth information about the design and installation of . We hope that with this information you would become an expert of your

system.

Air-Conditioning Company

General Information

R410A Model


General Information

2. Step by Step (1)

(2)

System Selection Process

Calculate or obtain the maximum heat load for the area(s) to be air conditioned

Decide the indoor unit specifications Decide the outdoor unit specifications Capacity coefficient factor Decide the air velocity and temperature distributions

(3)

(4)

Selection of refrigerant pipe joints and headers

Selection of the control system Control wiring method Description of devices

(5)

Electrical wiring Electric characteristics Field wiring

!

Caution

1. Air conditioners should not be installed in areas where corrosive gas such as acid gas or alkaline gas is produced. 2. If the outdoor unit is installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.


Indoor unit General Information 1. Model Names 2. External Appearance 3. Nomenclature 4. Indoor Unit Capacity Index


1. Model Names Chassis 5k Name (1.6)

General information Indoor unit

Category

9k (2.8)

12k (3.6)

15k (4.5)

ARNU18G ARNU24G S5*2 S5*2

S5 ARNU07G ARNU09G ARNU12G ARNU15G SE*2 SE*2 SE*2 SE*2

SE Mirror ART COOL

ARNU18G ARNU24G S8*2 S8*2

S8

Gallery

ARNU07G ARNU09G ARNU12G SF*2 SF*2 SF*2 ARNU07G ARNU09G ARNU12G GTU*2 GTU*2 GTU*2

SF TU

1 Way

ARNU18G ARNU24G TT*2 TT*2 ARNU18G ARNU24G TL*2 TL*2

TT 2 Way Ceiling

TL TR

Cassette

ARNU05 ARNU07G ARNU09G ARNU12G GTR*2 TR*2 TR*2 TR*2 ARNU15 ARNU18G GTQ*2 TQ*2

TQ 4 Way

Capacity(Btu/h(kW)) 18k 24k 28k 36k 42k 48k 76k 96k (5.6) (7.1) (8.2) (10.6) (12.3) (14.1) (22.4) (28.0)

ARNU07G ARNU09G ARNU12G ARNU15G SE*2 SE*2 SE*2 SE*2

SE

Wall Mounted (General)

7k (2.2)

ARNU24G ARNU28G TP*2 TP*2

TP

ARNU36G TN*2

TN

ARNU42G ARNU48G TM*2 TM*2

TM BH High Static Ceiling Concealed Duct

ARNU07G ARNU09G ARNU12G ARNU15G ARNU18G ARNU24G BHA2 BHA2 BHA2 BHA2 BHA2 BHA2 ARNU28G ARNU36G ARNU42G BGA2 BGA2 BGA2

BG

ARNU48G BRA2

BR

URNU76G URNU96G B8A2 B8A2

B8 B1 Low Static

ARNU07 GB1G2

ARNU09 GB1G2

ARNU12 GB1G2

ARNU15 GB1G2 ARNU18 GB2G2

B2 B3 Built In

ARNU07G ARNU09G ARNU12G ARNU15G B3G2 B3G2 B3G2 B3G2 ARNU18G ARNU24G B4G2 B4G2

B4 Ceiling & Floor

VE

Ceiling Suspended

VJ CE

With Case

ARNU09G ARNU12G VEA2 VEA2 ARNU18G ARNU24G VJA2 VJA2 ARNU07G ARNU09G ARNU12G ARNU15G CEA2 CEA2 CEA2 CEA2 ARNU18G ARNU24G CFA2 CFA2

CF

Floor Standing

Without Case Console

CE

ARNU07G ARNU09G ARNU12G ARNU15G CEU2 CEU2 CEU2 CEU2 ARNU18G ARNU24G CFU2 CFU2

CF QA BR

Fresh Air Intake Unit

ARNU24 GB2G2

ARNU07G ARNU09G ARNU12G ARNU15G QAA2 QAA2 QAA2 QAA2 ARNU48G BRZ2

B8

❈ *ART COOL- SE/S8( * R:Mirror, V:Silver, B : Blue), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable)) *Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma

1 _ General Information

URNU76 URNU96 GB8Z2 GB8Z2


2. External Appearance Ceiling Concealed Duct - High Static

ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2

ARNU07GBHA2 ARNU09GBHA2 ARNU12GBHA2 ARNU15GBHA2 ARNU18GBHA2 ARNU24GBHA2 ARNU28GBGA2

ARNU18GTT*2 ARNU24GTT*2

* A:Basic, C:Plasma

Ceiling Cassette- 4Way ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2 ARNU15GTQ*2 ARNU18GTQ*2

ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 ARNU42GTM*2 ARNU48GTM*2 * A:Basic, C:Plasma

Ceiling Concealed Duct - Low Static ARNU07GB1G2 ARNU15GB1G2 ARNU09GB1G2 ARNU18GB2G2 ARNU12GB1G2 ARNU24GB2G2

Ceiling Concealed Duct – Built-in ARNU07GB3G2 ARNU09GB3G2 ARNU12GB3G2

ARNU15GB3G2 ARNU18GB4G2 ARNU24GB4G2

ARNU36GBGA2 ARNU42GBGA2 ARNU48GBRA2 URNU76GB8A2 URNU96GB8A2

Wall Mounted ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2

ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2 * A:Basic, L:Plasma

ART COOL Gallery ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2 * E:Red V:Silver G:Gold 1: Kiss (Photo changeable)

Floor Standing With case ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2

ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2

ART COOL Mirror

Without case

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2

ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2

ARNU15GSE*2 ARNU18GS8*2 ARNU24GS8*2 * R:Mirror, V:Silver, B:Blue

ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2

Ceiling & Floor Console

ARNU09GVEA2 ARNU12GVEA2

Ceiling Suspended ARNU18GVJA2 ARNU24GVJA2

Ceiling Cassette -2Way ARNU18GTL*2 ARNU24GTL*2

ARNU07GQAA2 ARNU09GQAA2 ARNU12GQAA2 ARNU15GQAA2

Fresh Air Intake Unit ARNU48GBRZ2 URNU76GB8Z2 URNU96GB8Z2

* A:Basic, C:Plasma

General Information _ 2

General information Indoor unit

Ceiling Cassette- 1Way


General information Indoor unit

3. Nomenclature ARN

U

07

G

TU

A

2 Serial Number Combinations of functions A:Basic function L:Neo Plasma(Wall Mounted) C:Plasma(Ceiling Cassette) G: Low Static U : Floor Standing without Case ART COOL Type Panel Color SE/S8 - R:Mirror V:Silver B:Blue SF - E:Red V:Silver G:Gold 1: Kiss (Photo changeable) Q : Console Z : Fresh Air Intake Unit Chassis Name Electrical Ratings 2:1Ø, 220V, 60Hz 6:1Ø, 220 - 240V, 50Hz G:1Ø, 220 - 240V, 50Hz / 1Ø, 220V, 60Hz Total Cooling Capacity in Btu/h EX) 5,000 Btu/h Class ➝ '05' 18,000 Btu/h Class ➝ '18' Combination of Inverter Type and Cooling Only or Heat Pump N: AC Inverter and H/P V: AC Inverter and C/O U: DC Inverter and H/P and C/O System with Indoor Unit using R410A ❈ LGETA:U Ex) URN

3 _ General Information


4. Indoor Unit Capacity Index INDOOR UNIT CAPACITY INDEX 5k

7k

9k

12k

15k

18k

24k

28k

36k

42k

48k

76k

96k

Capacity Index

1.6

2.2

2.8

3.6

4.5

5.6

7.1

8.2

10.6

12.3

14.1

22.4

28.0

â?ˆ Capacity Index is same as the capacity(kW).

General Information _ 4

General information Indoor unit

Unit Capacity (Btu/h)


5 _ General Information

General information Indoor unit


Indoor unit Ceiling Cassette 1-Way Ceiling Cassette 2-Way Ceiling Cassette 4-way Ceiling Concealed Duct(High Static) Ceiling Concealed Duct(Low Static) Ceiling Concealed Duct(Built in) Wall Mounted ART COOL Mirror ART COOL Gallery Ceiling & Floor/Ceiling Suspended Floor Standing Console Fresh Air Intake Unit Dip Switch & Group Control Setting


Indoor unit Ceiling Cassette 1-Way 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Installation

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GTU*2, ARNU09GTU*2, ARNU12GTU*2 ARNU18GTT*2, ARNU24GTT*2 1 Auto O 4/5/4 X O O X Option O O O X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. * Some functions can be limited by remote controller.

Ceiling Cassette 1-Way _ 1

Indoor Units

Reliability

Function


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions (WxDxH) Front Panel

Indoor Units

Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz

1Way Ceiling Cassette ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 860 x 450 x 132 860 x 450 x 132 860 x 450 x 132 33.8 x 17.7 x 5.2 33.8 x 17.7 x 5.2 33.8 x 17.7 x 5.2 1100 x 500 x 34 1100 x 500 x 34 1100 x 500 x 34 43.3 x 19.7 x 1.3 43.3 x 19.7 x 1.3 43.3 x 19.7 x 1.3 2 x 12 x 18 2 x 12 x 18 2 x 12 x 18 0.16 0.16 0.16 Cross Flow Fan Cross Flow Fan Cross Flow Fan 30 30 30 0.18 0.18 0.18 8.2 / 7.3 / 6.4 9.2 / 8.6 / 8.2 10 / 9.2 / 8.2 289.5 / 257.7 / 225.9 324.7 / 303.6 / 289.5 353 / 324.8 / 289.5 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 25(1) 14.7(32.4) 14.7(32.4) 14.7(32.4) 32 / 29 / 25 35 / 34 / 32 38 / 35 / 32 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C White White White PT-UUC(Grill), PT-UUD(Panel)

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Cassette 1-Way

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions (WxDxH) Front Panel Coil

m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 1-Way _ 3

Indoor Units

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch

1Way Ceiling Cassette ARNU18GTT*2 ARNU24GTT*2 5.6 7.1 4,800 6,100 19,100 24,200 6.3 7.1 5,400 6,100 21,500 24,200 Galvanized Steel Plate Galvanized Steel Plate 1180 x 450 x 132 1180 x 450 x 132 13.3 x 17.7 x 5.2 46.5 x 17.7 x 5.2 1420 x 500 x 34 1420 x 500 x 34 55.9 x 19.7 x 1.3 55.9 x 19.7 x 1.3 2 x 12 x 18 2 x 12 x 18 0.24 0.24 Cross Flow Fan Cross Flow Fan 30 30 0.30 0.30 13.3 / 12.1 / 10.9 14.6 / 13.3 / 11.5 515.4 / 427.1 / 384.8 575.4 / 469.5 / 406 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) 25(1) 25(1) 18.7(41.23) 18.7(41.23) 40 / 37 / 35 43 / 40 / 36 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C White White PT-UTC(Grill), PT-UTD(Panel)


1,100 881(Air outlet Hole)

1012

861

88

106.8 206.6 275.8 57.4 96.5 168.3

4 _ Ceiling Cassette 1-Way 500 34

27

Air suction grill Air discharge grill

3 4

(unit : mm)

Unit size(7k, 9k, 12k):ø12.7

Unit size(7k, 9k, 12k):ø6.35

Descripition

CHASSIS CODE: TU

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Gas pipe connection

2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

(Panel Name: PT-UUC)

320.5

453

Liquid pipe connection

Name

ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2

Ceiling Cassette 1-way

1

Number

Indoor Units

3. Dimensions


Ceiling Cassette 1-Way _ 5

109.5

1012

1100

88

109.5

453 320.5

34

500

106.8 206.3 275.8 96.5 168.3 57.4

453 354.3

46.5

861

Air discharge grill

4

Unit size(7k, 9k, 12k):ø12.7

Unit size(7k, 9k, 12k):ø6.35

Descripition

(unit : mm)

CHASSIS CODE: TU

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air suction grill

3

Gas pipe connection

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

(Panel Name: PT-UUD)

27

Liquid pipe connection

1

Name

ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2

2

Number

Indoor Units

117

Ceiling Cassette 1-way

3. Dimensions


247.5 180.6 65.3

453.8

173.8 96.1 91 20.6 57.4 31.7

6 _ Ceiling Cassette 1-Way

1,201(Air Outlet Hole)

1,420

1332

1176.4 65.1

500 34

453.8

4

CHASSIS CODE: TT

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air suction grill Air discharge grill

3

Unit size(18k):ø12.7, (24k):ø15.88

Gas pipe connection

2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

(Panel Name: PT-UTC)

(unit : mm) Descripition

Liquid pipe connection Unit size(18k):ø6.35, (24k):ø9.52

Name

ARNU18GTT*2 ARNU24GTT*2

Ceiling Cassette 1-way

1

Number

Indoor Units

3. Dimensions


Ceiling Cassette 1-Way _ 7

109.5

1332

1420

Ø14 15.2

65.3

453.8 247.5 180.6

173.8 97.1 91

500

57.4 31.7 20.6

46.5

34

65.1

22.3

57 132

1176.4

109.5

335

453.8

Air discharge grill

CHASSIS CODE: TT

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

4

Air suction grill

3

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

(Panel Name: PT-UTD)

96.5

Gas pipe connection

Unit size(18k):ø12.7, (24k):ø15.88

Liquid pipe connection Unit size(18k):ø6.35, (24k):ø9.52

Descripition

(unit : mm)

2

Name

ARNU18GTT*2 ARNU24GTT*2

1

Number

Indoor Units

44

Ceiling Cassette 1-way

3. Dimensions


4. Piping Diagrams

Heat Exchanger

EEV

Filter

:Cooling :Heating

Th2

Th3 C.F.F.

Filter

Indoor Units

Th1

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

Model

Gas

Liquid

Ø12.7(1/2)

Ø6.35(1/4)

Ø15.88(5/8)

Ø9.52(3/8)

ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 ARNU18GTT*2 ARNU24GTT*2

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

8 _ Ceiling Cassette 1-Way


5. Wiring Diagrams TU, TT Chassis

LOCATION POINT Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Option pwb. Communication Step motor

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Communication between main and option Communication between indoor and outdoor Step motor output

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Cassette 1-Way _ 9

Indoor Units

CONNECTOR NUMBER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-OPTION CN-COM CN-VANE1


6. Capacity Tables 6.1 Cooling Capacity

Capacity Index

Indoor Units

2.2

2.8

3.6

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

Notes: TC: Total Capacity(kW)

10 _ Ceiling Cassette 1-Way

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

SHC: Sensible Heat Capacity(kW)

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

30 22 TC SHC kW kW 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

32 24 TC SHC kW kW 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2


6. Capacity Tables

Capacity Index

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1

30 22 TC SHC kW kW 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3

32 24 TC SHC kW kW 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.9 4.8 4.7 4.7 4.6 4.5 4.4 4.4 4.3

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 1-Way _ 11

Indoor Units

7.1

Outdoor air temp. (DB, °C)

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor Units

2.2

2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Heating capacity Indoor air temp. (DB, °C)

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7 2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2 2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Notes: TC: Total Capacity(kW)

12 _ Ceiling Cassette 1-Way


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

5.6

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2 4.8 4.9 5.2 5.5 5.8 6.0 6.1 6.2 6.5 6.7 7.0 7.5 7.9 8.0 8.2 8.2 8.2 8.2 8.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7 4.8 4.9 5.2 5.4 5.8 6.0 6.1 6.2 6.5 6.7 7.0 7.5 7.6 7.6 7.6 7.6 7.6 7.6 7.6

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3 4.8 4.9 5.2 4.9 5.1 5.4 5.5 5.6 5.8 6.0 6.2 6.6 6.9 7.1 7.1 7.1 7.1 7.1 7.1

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 4.7 4.9 5.2 5.4 5.7 6.0 6.1 6.2 6.3 6.6 6.8 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 4.7 4.8 5.2 5.4 5.7 6.0 6.1 6.2 6.3 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.7 4.8 5.1 5.4 5.7 6.0 6.0 6.1 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2

Notes: TC: Total Capacity(kW)

Ceiling Cassette 1-Way _ 13

Indoor Units

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Indoor air temp. (DB, °C)


7. Air Velocity and Temperature Distribution(Reference Data) ARNU07GTU*2 Cooling

Heating

Discharge angle: 50°

Discharge angle: 60° Air velocity [m/s]

0.1

2m

2.0

2m

0.5

1

2. 5

0.1

0.5

22

.5

0.5

0. 1

3

0.1

0.1

0.5

1

0.5

1.5

1.0 3.5. 43 .0 5

Air velocity [m/s]

1.0

0.1

1.0

05

0. 5

0.5

1m

1.0

1

0.5

1m

0.1 1.0

1.5

0.5

0.5

0.5

0.5

1 0.

1.5

1.5

5 0.

0.1

0.5

1

0.5 1

4m

0.5

3m

2m

1m

0

5m

Temperature [°C]

4m

0.5 0.5

3m

01

2m

0

1m

0

Temperature [°C] 32 14

30

30

16 20

31

32

33

34

2m

31

36

3 37 8

32

24

22

31

35

34

26

32

2m

36

31

28

28

35

34

30

28

26

24

4327

32

30

41 3 396

32

1m

35

37 36

24

1m 34

28

26

30

33

28

36

24

32

28

30

26

4m

3m

28

26

28

30

5m

2m

31

0 5m

0

1m

35

4m

36

35

34

3m

2m

0

1m

0

ARNU09GTU*2 Cooling

Heating

Discharge angle: 50°

Discharge angle: 60°

Air velocity [m/s]

Air velocity [m/s] 2.5 0.5

3.0

2. 0 0.5

1.0 1.5

0.5

1.0

1.0

0.5

1

1

0.5

0.5

5 0.

1m

1.5

1m

0.5

01

1

0.5

1.5

0.5

0.5

2m

0.1

1

2

1.0

1.5

2m

0.1

0.1

5 0. 0.5

0.1

1.5 1.5

2. 5 3 .5 5 1.

0.5

0.1

1

3

0.1

0.5

1 0.5

4m

0.5

0

3m

2m

1m

0

5m

Temperature [°C]

4m

1.0 0.5

01

3m

2m

0

1m

0

Temperature [°C]

32

31 32

2284 20

32

38

18

30

32

35

30

22

32

43 38326354 9

5m

36

33 37 36 33

30

32

22

2m 36

26 28

26

31

2m

28

24

1m

36

33

34 35 37

34

3231

24

30

28

1m

4m

28

3m

26

26 30 28

2m

1m

32

0 0

33

32

26

30

5m

36

31

24

34

35

28

28

Indoor Units

0.1

0

0.5

0.5

5m

1

5m

4m

36

35

34

3m

2m

0 1m

0

Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

14 _ Ceiling Cassette 1-Way


7. Air Velocity and Temperature Distribution(Reference Data) ARNU12GTU*2 Cooling

Heating

Discharge angle: 50°

Discharge angle: 60° Air velocity [m/s] 1.0

0.1

2. 5

0.5

1.0

1. 0. 05

2m 1.5

1m

0.5

0.1

0.1

0. 5

0.1

0.1

2

0.5

1.5

0.5

1

5 0.

1.50.5

1.5

1

1

0.5

0. 5

5 1. 0.5

2. 0

0.5

1 0.

2m

05

0.1

1.5

11.5 .0 2. 420.5 .0

2 11 .5

Air velocity [m/s]

1m

1.0

3m

2m

1.0

0

1m

0

01

5m

4m

0

3m

2m

1m

0

Temperature [°C]

32

32

32

32

28

31

32

37 41

30

3 4064

Temperature [°C]

0.5

1

4m

05

1

0.5

5 0.

5m

0.5

1.0

1.0

1.5

0.5

0.5

0.5

30

33

2m

2m

33

37 32

4m

36

35

34 36

31

24

26

34

24

28

3m

36

33

5m

26

30

1m

37

28

28

38

24

28

22

32

30

28

3635

28

31

26

28

30

1m

26

34

39

31

26

0

2m

5m

0

1m

37

35

34

32

4m

3536

3m

2m

0

1m

0

ARNU18GTT*2 Cooling

Heating

Discharge angle: 50°

Discharge angle: 60°

Air velocity [m/s]

Air velocity [m/s] 1

0.53

1

.5

5

01.5 43.5

2

2

2 1.5

1

2. 5

2m

2m

1

0.5

1

0.5 0.5

1

1.5

1.5

0.5

1.5 2

0.5

0.5

5 0.

0.5 0.5

1 0.5

5 0.

2. 5

0.5

.5 1 4

1.5

1m

1.5

1

1m

1

1

0.5

0.5

0.5

0.5

1 .5

0.5

0.5

4m

3m

0 2m

1m

0

0 5m

Temperature [°C]

4m

3m

2m

1m

0

Temperature [°C]

32

32

32

32

3364

30

30 39 40

30

32

26

22

2m 33

31

34

35

24

34

30

28 33

4m

3m

36

33

26

34

24

2826

5m

1m

36

28

36

37

1m

36

32

24

24

31

2628

28

2m

35 33

30

32

32 1 4

38

22

18 28

35

202

8

31

34

5m

31

0

0 2m

1m

0

5m

4m

3m

2m

1m

0

Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

Ceiling Cassette 1-Way _ 15

Indoor Units

26


7. Air Velocity and Temperature Distribution(Reference Data) ARNU24GTT*2 Cooling

Heating

Discharge angle: 50째

Discharge angle: 60째

Air velocity [m/s]

Air velocity [m/s] 2. 5

1.5

1

2m

2 1.5

1.5

0.5

0.5

0.5

1m

05

0.5

1 1.5

0 .5

1.5 0.5

0.5

0.5

0. 1.55

1 5 0.

2m

1

2

0. 5

2

0.5

32

.5 4.5

5 0.

1 1. 52

0.5

1

1

2

3.5

1m

1

1

0.5

1.5

1

1

1

1.5

1

0.5 1

1

0.5

5m

4m

0.5

3m

2m

1

0

1m

0

0 5m

Temperature [째C]

4m

3m

2m

1m

0

Temperature [째C]

32

32

32 161

36

2

32

40

32333

26 22

30

2m

2m 38

22

31

28

28

4

39

32

20

28

36

36 37

36

33

36

1m

24

35

30

33

34

31

28

28

32

1m

34

26

35

37

24

33

24 4

28

28

26

34

31

30

Indoor Units

31

30

30 24

35

30

28

5m

4m

3m

0

0 2m

1m

0

5m

4m

3m

2m

1m

0

Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

16 _ Ceiling Cassette 1-Way


8. Electric Characteristics Units

Power Supply

Input(W)

MFA

kW

FLA

1.23

15

0.03

0.18

40

40

1.23

15

0.03

0.18

40

40

1.23

15

0.03

0.18

40

40

1.38

15

0.03

0.30

70

70

TT

1.38

15

0.03

0.30

70

70

ARNU07GTU*2

TU

1.23

15

0.03

0.18

40

40

ARNU09GTU*2

TU

1.23

15

0.03

0.18

40

40

ARNU12GTU*2

TU

1.23

15

0.03

0.18

40

40

ARNU18GTT*2

TT

1.38

15

0.03

0.30

70

70

ARNU24GTT*2

TT

1.38

15

0.03

0.30

70

70

Model

Type

ARNU07GTU*2

TU

ARNU09GTU*2

TU

ARNU12GTU*2

TU

ARNU18GTT*2

TT

ARNU24GTT*2

Hz

50

Volts

220-240

60

220

Voltage Range MCA

IFM

Max:264 Min:198

Max:242 Min:198

Cooling Heating

Indoor Units

Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.

Ceiling Cassette 1-Way _ 17


9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1.5m Microphone

Sound Levels dB(A) H M L

Model

Indoor Units

ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 ARNU18GTT*2 ARNU24GTT*2

32 35 38 40 43

29 34 35 37 40

25 32 32 35 36

Sound Pressure Level ARNU09GTU*2

ARNU12GTU*2 XP

WP

WP

WP

nc MVU

VP nc MVP nc MUU

UP

nc MUP nc MTU

TP

nc MTP nc MSU

SP

nc MSP

RP

nc MRU

a h @ t

ncMVP ncMUU

UP ncMUP ncMTU

TP ncMTP

nc MQU

QRU

RUP

UPP

QPPP

RPPP

TPPP

XPPP

o @b @c @f @Hh I

18 _ Ceiling Cassette 1-Way

ncMSU

SP

ncMSP

ncMRU

RP

nc MRP

QP VS

ncMVU

VP

QP

a h t VS

o @b @s @p @l @H b@ @RPµp @I

XP

o @b @s @p @l @H b@ @RPµp @I

o @b @s @p @l @H b@ @RPµp @I

ARNU07GTU*2 XP

NC-65

VP NC-60 NC-55

UP NC-50 NC-45

TP NC-40

NC-30

QRU

RUP

UPP

QPPP

RPPP

TPPP

o @b @c @f @Hh I

XPPP

NC-25

RP

ncMRP ncMQU

NC-35

SP

QP

Approximate Hearing Threshold VS

NC-20 NC-15

QRU

RUP

UPP

QPPP

RPPP

TPPP

o @b @c @f @Hh I

XPPP


9. Sound Levels ARNU24GTT*2

80

80

70

70

NC-65 60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-65 60 NC-60

NC-50

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

NC-45

40

NC-40 NC-35

30

NC-30

20

10

NC-25 Approximate Hearing Threshold 63

NC-20

125

250

500

1000

2000

4000

NC-15 8000

Indoor Units

10

NC-55

50

NC-20 NC-15

63

o @b @s @p @l @H b@ @RPµp @I

o @b @s @p @l @H b@ @RPµp @I

ARNU18GTT*2

Octave Band Center Frequency (Hz)

Ceiling Cassette 1-Way _ 19


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Outlet

TEM P

Remote Controlle

Indoor Units

r

Inlet

Required Parts • Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

Wired remote controller

Required Tools • Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

20 _ Ceiling Cassette 1-Way

Ceiling board

500 or more

300 or less

500 or more

Above 2500 3300 or less

Ceiling Ceiling board

1000 or more

• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have the maintenance space.

200 or more

10.1 Selection of the best location

Unit:mm Floor


10. Installation 10.2 Ceiling opening dimensions and hanging bolt location 1,385 1,285

50

50

354 466

1,180

448

306

40

600

400

• The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.

40

Ceiling 250

TT Chassis

Level gauge

1,065 965

50

50

250

354 466

448

860

TU Chassis

• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.

(unit: mm)

Ceiling board

NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam. Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

Ceiling Cassette 1-Way _ 21

Indoor Units

• This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.

40

400

CAUTION

306

40

600


10. Installation Ceiling

Nut (W3/8 or M10)

70mm

Keep the length of the bolt from the bracket to 40mm

Hanging bolt (W3/8 or M10)

Flat washer for M10 (accessory) Ceiling board

Spring washer (M10)

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Air conditioner body

Set screw of paper model (4 pieces)

Paper model for installation

Open the ceiling board along the outer edge of the paper model

Indoor Units

Adjust the same height

• The following parts are local purchasing. ① Hanging bolt - W 3/8 or M10 ② Nut - W 3/8 or M10 ③ Spring washer - M10 ④ Plate washer - M10

Ceiling board

CAUTION • Tighten the nut and bolt to prevent the unit from falling.

10.3 Wiring Connection • Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model] Terminal block of indoor unit 1(L)

2(N)

3

SODU B

SODU A

IDU B

IDU A

INT B

INT A

4

Indoor power input

[Except Multi VIII Heat Pump Model] Terminal block of outdoor unit Terminal block of indoor unit 1(L)

2(N)

3

4

Outdoor unit Indoor unit

SODU SODU IDU IDU INTERNET DRY1 DRY2 GND 12V

Indoor power input

WARNING Make sure that the screws of the terminal are not loose.

22 _ Ceiling Cassette 1-Way

Central controller


10. Installation 10.4 Installation of Decoration Panel (Panel Type) Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction. 1. Open the air outlet vane, and extract side covers. 2. Remove the air inlet panel from the decoration panel.

3. Hook decoration panel to indoor unit, using hooks attached at the backside of both side of decoration panel. 4. Arrange wires not to get caught between decoration panel and indoor unit. 5. Screw 7 fixing screws. (7,9,12kBtu : 6 screws) 6. Connect the vane motor connector ,display connector and air inlet panel connector. 7. Install the air inlet panel (including the air filter) and side covers. Air conditioner unit

Indoor Units

Mesh Control box cover

Side cover Robot kit Decorative panel fixing screws (hexagon M6 screws) (tightening about 20mm)

Air inlet panel

Decorative panel Air outlet vane

CAUTION

Install certainly the decoration panel. Cool air leakage causes sweating. ⇨讀 Waterdrops fall.

Good example

Bad example Air conditioner unit Cool air leakage (no good) Ceiling board Decorative panel

Air conditioner unit Ceiling board Decorative panel

Fit the insulator (this part) and be careful for cool air leakage

Ceiling Cassette 1-Way _ 23


10. Installation 10.5 Installation of Decoration Panel(Grille Type) Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction. 1. Open the air outlet vane, and extract side covers. 2. Remove the air inlet grille from the decoration panel.

3. Hook decoration panel to indoor unit, using hooks attached at the backside of both side of decoration panel. 4. Arrange wires not to get caught between decoration panel and indoor unit. 5. Screw 7 fixing screws. (7,9,12kBtu : 6 screws) 6. Connect the vane motor connector and display connector. (Plasma connector for plasma model)

Indoor Units

7. Install the air inlet grille (including the air filter) and side covers.

Air conditioner unit

Mesh Control box cover

Side cover Plasma filter (applied only to plasma model) Decorative panel fixing screws (hexagon M6 screws) (tightening about 20mm) Air inlet grille

Decorative panel Air inlet grille

CAUTION

Install certainly the decoration panel. Cool air leakage causes sweating. ⇨讀 Waterdrops fall.

Good example

Bad example Air conditioner unit Cool air leakage (no good) Ceiling board Decorative panel

Fit the insulator (this part) and be careful for cool air leakage

24 _ Ceiling Cassette 1-Way

Air conditioner unit Ceiling board Decorative panel


10. Installation 10.6 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe 25mm and pipe fittings

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

• Be sure to install heat insulation on the drain piping. 1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

Max 700mm

Drain test

Feed water

Flexible drain hose (accessory) Main drain pipe

Drain pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

CAUTION Max 300mm Metal clamp Flexible drain hose

Hanger bracket 1/50~1/100 slope Max 700mm

The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.

Hanger distance 1~15m

Insulation

Ceiling Cassette 1-Way _ 25

Indoor Units

The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:


10. Installation

Indoor Units

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.

WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Remote Controller

5feet (1.5meters)

TEMP

Controller Remote

no

no

Fig.1 Typical locations for remote controller

26 _ Ceiling Cassette 1-Way


11. Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for hanging bracket 8 EA

Plastic band

Insulation for fitting

4 EA

1 SET

Shape

for gas pipe

for liquid pipe

Paper pattern for installation

Installation and Owner's manual

Quantity

1EA

1EA

Shape

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Cassette 1-Way _ 27

Indoor Units

Name


Indoor unit Ceiling Cassette 2-Way 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Installation

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU18GTL*2, ARNU24GTL*2 2 Auto O 4/5/4 X O O X Option O O O X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Ceiling Cassette 2-way _ 1

Indoor Units

Reliability

Function


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions (WxDxH) Front Panel

Indoor Units

Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz

2Way Ceiling Cassette ARNU18GTL*2 5.6 4,800 19,100 6.3 5,400 21,500 Galvanized Steel Plate 830 x 550 x 225 32.6 x 21.6 x 8.9 1,050 x 640 x 28.5 41.3 x 25.2 x 1.1 2 x 11 x 20 0.13 Cross Flow Fan 20 x 2 0.18 x 2 13 / 12 / 10 459 / 424 / 353 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 22(48.5) 40 / 36 / 32 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog PT-HL*

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Cassette 2-way

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions (WxDxH) Front Panel Coil

m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 2-way _ 3

Indoor Units

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch

2Way Ceiling Cassette ARNU24GTL*2 7.1 6,100 24,200 8.0 6,900 27,300 Galvanized Steel Plate 830 x 550 x 225 32.6 x 21.6 x 8.9 1,050 x 640 x 28.5 41.3 x 25.2 x 1.1 2 x 11 x 20 0.13 Cross Flow Fan 20 x 2 0.18 x 2 17 / 15 / 13 601 / 530 / 459 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø9.52(3/8) Ø15.88(5/8) 25(1) 22(48.5) 42 / 38 / 34 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog PT-HL*


3

4

144.2

921(Air Outlet Hole) 1,050

893

931.2 830 34 1

4-R15

482 550

2 205.5 69.2

35.6

162.4 640 28.5

4 _ Ceiling Cassette 2-way 177.1 225

6.5

92

206.5 69.2

Air discharge grill

Air suction grill

Gas pipe connection

Liquid pipe connection

Name

(unit : mm)

Unit size(24k):ø15.88

Unit size(18k):ø12.7

Unit size(24k):ø9.52

Unit size(18k):ø6.35

Descripition

ARNU18GTL*2 ARNU24GTL*2

Ceiling Cassette 2-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: TL

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

4

3

2

1

Number

Indoor Units

3. Dimensions


4. Piping Diagrams

Heat Exchanger

EEV

Filter

:Cooling :Heating

Th2

Th3 C.F.F.

Filter Th1

lndoor unit

[Unit: mm(inch)]

Model

Gas

Liquid

ARNU18GTL*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GTL*2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Cassette 2-way _ 5

Indoor Units

Refrigerant pipe connection port diameter


5. Wiring Diagrams

Indoor Units

TL Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO

SPEC AC Power supply Fan motor output Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

DESCRIPTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

6 _ Ceiling Cassette 2-way


6. Capacity Tables 6.1 Cooling Capacity

Capacity Index

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

10

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.4

4.2

12

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.3

4.1

14

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.2

4.1

16

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.1

4.0

18

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.0

4.0

20

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.9

3.9

21

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.8

3.9

23

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.7

3.8

25

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.6

4.2

6.6

3.8

27

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.4

4.1

6.6

3.7

29

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.4

4.0

6.5

3.7

31

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.3

3.9

6.4

3.6

33

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.2

3.9

6.3

3.6

35

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.0

3.8

6.2

3.5

37

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.8

3.9

5.9

3.7

6.1

3.5

39

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.7

3.9

5.8

3.7

6.0

3.4

Outdoor air temp. (DB, °C)

Notes: TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 2-way _ 7

Indoor Units

5.6

Cooling capacity


6. Capacity Tables Cooling capacity

Indoor Units

Capacity Index

7.1

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

10

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.3

5.3

12

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.2

5.2

14

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.1

5.2

16

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.0

5.1

18

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.8

5.0

20

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.7

5.0

21

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.7

4.9

23

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.5

4.9

25

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.4

5.3

8.4

4.8

27

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.2

5.1

8.3

4.7

29

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.1

5.1

8.2

4.7

31

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.0

5.0

8.1

4.6

33

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

7.8

4.9

7.9

4.5

35

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

7.7

4.8

7.8

4.4

37

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.4

5.0

7.5

4.7

7.7

4.4

39

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.2

4.9

7.4

4.6

7.6

4.3

Outdoor air temp. (DB, °C)

Notes: TC: Total Capacity(kW)

8 _ Ceiling Cassette 2-way

SHC: Sensible Heat Capacity(kW)


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

-19.8 -20.0

kW 4.2

kW 4.2

kW 4.2

kW 4.2

kW 4.2

kW 4.2

-18.8 -19.0

4.3

4.3

4.3

4.3

4.3

4.3

-16.7 -17.0

4.6

4.6

4.6

4.6

4.6

4.5

-14.7 -15.0

4.9

4.8

4.3

4.8

4.8

4.8

-12.6 -13.0

5.1

5.1

4.5

5.0

5.0

5.0

-10.5 -11.0

5.4

5.4

4.8

5.4

5.3

5.3

-9.5 -10.0

5.4

5.4

4.9

5.4

5.4

5.4

-8.5

-9.1

5.5

5.5

5.0

5.5

5.5

5.4

-7.0

-7.6

5.7

5.7

5.1

5.6

5.6

5.5

-5.0

-5.6

6.0

6.0

5.4

5.8

5.8

5.5

-3.0

-3.7

6.2

6.2

5.5

6.1

5.9

5.5

0.0

-0.7

6.6

6.6

5.8

6.1

5.9

5.5

3.0

2.2

7.0

6.7

6.2

6.1

5.9

5.5

5.0

4.1

7.1

6.7

6.3

6.1

5.9

5.5

7.0

6.0

7.2

6.7

6.3

6.1

5.9

5.5

9.0

7.9

7.2

6.7

6.3

6.1

5.9

5.5

11.0

9.8

7.2

6.7

6.3

6.1

5.9

5.5

13.0 11.8

7.2

6.7

6.3

6.1

5.9

5.5

15.0 13.7

7.2

6.7

6.3

6.1

5.9

5.5

Notes: TC: Total Capacity(kW)

Ceiling Cassette 2-way _ 9

Indoor Units

5.6

Heating capacity


6. Capacity Tables Heating capacity

Indoor Units

Outdoor air temp. Capacity Index DB(°C) WB(°C)

7.1

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

-19.8 -20.0

kW 5.4

kW 5.4

kW 5.4

kW 5.3

kW 5.3

kW 5.3

-18.8 -19.0

5.5

5.5

5.5

5.5

5.4

5.4

-16.7 -17.0

5.8

5.8

5.8

5.8

5.8

5.8

-14.7 -15.0

6.2

6.1

5.5

6.1

6.1

6.1

-12.6 -13.0

6.5

6.5

5.8

6.4

6.4

6.4

-10.5 -11.0

6.8

6.8

6.0

6.8

6.7

6.7

-9.5 -10.0

6.9

6.9

6.2

6.9

6.9

6.8

-8.5

-9.1

7.0

7.0

6.3

7.0

7.0

6.8

-7.0

-7.6

7.3

7.3

6.5

7.1

7.1

7.0

-5.0

-5.6

7.6

7.6

6.8

7.4

7.4

7.0

-3.0

-3.7

7.9

7.9

7.0

7.7

7.5

7.0

0.0

-0.7

8.4

8.4

7.4

7.8

7.5

7.0

3.0

2.2

8.9

8.6

7.8

7.8

7.5

7.0

5.0

4.1

9.0

8.6

8.0

7.8

7.5

7.0

7.0

6.0

9.2

8.6

8.0

7.8

7.5

7.0

9.0

7.9

9.2

8.6

8.0

7.8

7.5

7.0

11.0

9.8

9.2

8.6

8.0

7.8

7.5

7.0

13.0 11.8

9.2

8.6

8.0

7.8

7.5

7.0

15.0 13.7

9.2

8.6

8.0

7.8

7.5

7.0

Notes: TC: Total Capacity(kW)

10 _ Ceiling Cassette 2-way


7. Air Velocity and Temperature Distribution(Reference Data) ARNU24GTL*2 Cooling

Heating

Discharge angle: 40째

Discharge angle: 60째

Air velocity [m/s]

Air velocity [m/s] 2.7m

2.0

2.5

3.0

3.0

2.5

2m

2.0

1.5

1.5

1.0

1.0

0.5

4m

2.7m 2.5 2.0 1.5

1m

2m

1m

0m

1m

2m

0m 4m

3m

Temperature [째C]

0.5

4m

3m

2m

20

20

2.7m 21

22

0m

32 31

2m

23

1m

2m

0m 4m

3m

24

1m

28 26

1m

0m

1m

2m

3m

0m 4m

4m

27

3m

2m

1m

29

2.7m

32 31

30

24

2m

0.5

1m

2m

30 27

28

29 28

0m

1m

28 27

1m

26

2m

3m

0m 4m

Ceiling Cassette 2-way _ 11

Indoor Units

21

23

3m

1m

1.0

Temperature [째C]

22

4m

2m

1.5

1.0

0.5

3m

2.5 2.0


8. Electric Characteristics Units Model

Type

ARNU18GTL*2

TL

ARNU24GTL*2

TL

ARNU18GTL*2

TL

ARNU24GTL*2

TL

Power Supply Hz

Volts

50

220-240

60

220

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

Max:264

0.52

15

0.04

0.41

70

70

Min:198

0.52

15

0.04

0.41

70

70

Max:242

0.52

15

0.04

0.41

70

70

Min:198

0.52

15

0.04

0.41

70

70

Symbols:

Indoor Units

MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.

12 _ Ceiling Cassette 2-way


9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1.5m Microphone

Sound Levels dB(A)

Model

H

M

L

ARNU18GTL*2

40

36

32

ARNU24GTL*2

42

38

34

ARNU24GTL*2

80

80

70

70

NC-65 60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

20

10

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU18GTL*2

NC-65 60 NC-60

NC-15 250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

20

NC-20

125

Indoor Units

Sound Pressure Level

10

NC-25 Approximate Hearing Threshold 63

NC-20 NC-15 125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

Ceiling Cassette 2-way _ 13


10. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

TEMP

Remote Controller

Air Intake Air Outlet

Required Parts • Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

Required Tools • Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

14 _ Ceiling Cassette 2-way

50 or more

Ceiling Board

50 or more

30 or less

Ceiling Ceiling Board

Above 200 300 or less

• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have sufficient maintenance space.

20 or more

10.1 Selection of the best location

100 or more

Indoor Units

Anti-bacteria filter

Unit:cm Floor


10. Installation 10.2 Ceiling opening dimensions and hanging bolt location • The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions. Ceiling board

Ceiling Level gauge

CAUTION

NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.

Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

Ceiling Cassette 2-way _ 15

Indoor Units

• This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.

• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.


10. Installation Ceiling

Nut (W3/8 or M10)

90mm

Keep the length of the bolt from the bracket to 40mm

Hanging bolt (W3/8 or M10)

Flat washer for M10 False (accessory) ceiling board

Air Conditioner body

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Set screw of paper pattern (4 pieces)

Paper pattern for installation

Open the ceiling board along the outer edge of the paper pattern

Indoor Units

Adjust the same height

• The following parts are locally purchased. ① Hanging Bolt - W 3/8 or M10 ② Nut - W 3/8 or M10 ③ Spring Washer - M10 ④ Plate Washer - M10

False ceiling board

CAUTION • Tighten the nut and bolt to prevent the unit from falling.

10.3 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

IDU B

SODU A

IDU A

INT B

INT A

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INDOOR POWER INPUT

WARNING Make sure that the screws of the terminal are not loose.

16 _ Ceiling Cassette 2-way

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit


10. Installation 10.4 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction.

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included in the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter). Air conditioner unit

Indoor Units

Decorative panel fixing screws (hexagon M6 screws) Temporary fitting at 2 poles (Tightening about 10mm)

Piping side

Control box cover Cover

Plasma filter

Louver motor

Key holes

Decorative panel fixing screws (Hexagon M6 screw)

Decorative panel Push

Ratch pull

Inlet Grille

CAUTION Install the decoration panel otherwise cool air leakage causes condensation. ⇨讀 Water drops fall.

Correct method

Wrong method Air conditioner unit Cool air leakage (no good) Ceiling board Decoration panel

Air conditioner unit Ceiling board Decoration panel

Fit the insulator (this part) and be careful for cool air leakage

Ceiling Cassette 2-way _ 17


10. Installation 10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): Make sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

Piping material: Polyvinyl chloride pipe inner diameter Ø 25mm and pipe fittings 1/50~1/100

• Make sure to install heat insulation on the drain piping.

MAX 700mm

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Make sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

CAUTION The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Max 300mm

Hanger distance 1~15m

Metal clamp Flexible drain hose Insulation

18 _ Ceiling Cassette 2-way

Hanger Bracket 1/50~1/100 slope Max 700mm

Indoor Units

Drain test


10. Installation CAUTION

HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)

WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling Cassette 2-way _ 19

Indoor Units

After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.


11. Accessories Standard Accessories Name

Clamp metal

Drain hose

Insulation for fitting

Quantity

2 EA

1 EA

1 set

Washer for hanging bracket 8 EA

Clamp (Tie Wrap) 4 EA

Bolt

(Other)

4 EA • Paper pattern for installation • Owner's manual • Installation manual

Shape

for gas pipe

for liquid pipe

Indoor Units

• Screws for fixing panels are attached to decoration panel.

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

20 _ Ceiling Cassette 2-way


Indoor unit Ceiling Cassette 4-way 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Indoor Units

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Elevation Grill Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU05GTR*2, ARNU07GTR*2, ARNU09GTR*2, ARNU12GTR*2 ARNU15GTQ*2, ARNU18GTQ*2, ARNU24GTP*2, ARNU28GTP*2 ARNU36GTN*2, ARNU42GTM*2, ARNU48GTM*2 4 Auto O 4/5/4 X O O O X Option O O X X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory (TM,TN,TP only) Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. * Plasma kit and Elevation Grille are not applicable at the same time

1 _ Ceiling Cassette 4-way


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions(WxDxH) Front Panel Coil

m3 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Packaged kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz mm2 mm2

4 Way Ceiling Cassette ARNU07GTR*2 ARNU09GTR*2 2.2 2.8 1,900 2,400 7,500 9,600 2.5 3.2 2,200 2,800 8,500 10,900 Galvanized Steel Plate Galvanized Steel Plate 570 x 570 x 214 570 x 570 x 214 22.4 x 22.4 x 8.4 22.4 x 22.4 x 8.4 700 x 700 x 30 700 x 700 x 30 27.5 x 27.5 x 1.2 27.5 x 27.5 x 1.2 1 x 8 x 18 2 x 8 x 18 0.21 0.21 Turbo Fan Turbo Fan 43 x 1 43 x 1 0.2 0.2 7.5 / 7.0 / 6.6 8.0 / 7.5 / 7.1 265 / 247 / 212 283 / 265 / 251 Direct Direct BLDC BLDC Microprocessor, Microprocessor, Thermostat for cooling Thermostat for cooling and heating and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 13.1(28.9) 14.2(31.3) 15.4(33.9) 16.5(36.3) 29 / 27 / 26 30 / 29 / 27 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog PT-UQC

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 4-way _ 2

Indoor Units

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch

ARNU05GTR*2 1.6 1,400 5,500 1.8 1,500 6,100 Galvanized Steel Plate 570 x 570 x 214 22.4 x 22.4 x 8.4 700 x 700 x 30 27.5 x 27.5 x 1.2 1 x 8 x 18 0.21 Turbo Fan 43 x 1 0.2 7.5 / 7.0 / 6.6 265 / 247 / 212 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 13.1(28.9) 15.4(33.9) 29 / 27 / 26 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions(WxDxH) Front Panel

Indoor Units

Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch m3 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Packaged kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz mm2 mm2

ARNU12GTR*2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 570 x 570 x 214 22.4 x 22.4 x 8.4 700 x 700 x 30 27.5 x 27.5 x 1.2 2 x 8 x 18 0.21 Turbo Fan 43 x 1 0.2 8.7 / 8.0 / 7.0 307 / 283 / 247 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 14.2(31.3) 16.5(36.3) 32 / 30 / 27 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog

4 Way Ceiling Cassette ARNU15GTQ*2 ARNU18GTQ*2 4.5 5.6 3,900 4,800 15,400 19,100 5.0 6.3 4,300 5,400 17,100 21,500 Galvanized Steel Plate Galvanized Steel Plate 570 x 570 x 256 570 x 570 x 256 22.4 x 22.4 x 10.1 22.4 x 22.4 x 10.1 700 x 700 x 30 700 x 700 x 30 27.5 x 27.5 x 1.2 27.5 x 27.5 x 1.2 2 x 10 x 18 2 x 10 x 18 0.27 0.27 Turbo Fan Turbo Fan 43 x 1 43 x 1 0.2 0.2 11.0 / 10.0 / 9.3 11.2 / 11.0 / 10.0 388 / 353 / 328 396 / 388 / 353 Direct Direct BLDC BLDC Microprocessor, Microprocessor, Thermostat for cooling Thermostat for cooling and heating and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 15.5(34.2) 15.5(34.2) 18.0(39.7) 18.0(39.7) 36 / 34 / 32 37 / 35 / 34 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog PT-UQC

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

3 _ Ceiling Cassette 4-way

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications * Model Name A:Basic, C:Plasma Type Model

4 Way Ceiling Cassette ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 Cooling Capacity 7.1 8.2 10.6 6,100 7,100 9,100 24,200 28,000 36,200 Heating Capacity 8.0 9.2 11.9 6,900 8,000 10,200 27,300 31,500 40,600 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions Body mm 840 x 840 x 204 840 x 840 x 204 840 x 840 x 246 (WxDxH) inch 33.0 x 33.0 x 8.0 33.0 x 33.0 x 8.0 33.0 x 33.0 x 9.7 Front Panel mm 950 x 950 x 25 950 x 950 x 25 950 x 950 x 25 inch 37.4 x 37.4 x 1 37.4 x 37.4 x 1 37.4 x 37.4 x 1 Coil Rows x Columns x FPI 2 x 8 x 19 2 x 8 x 19 2x10x19 Face Area m3 0.40 0.40 0.57 Fan Type Turbo Fan Turbo Fan Turbo Fan Motor Outputx Number W 30 30 135 Running Current A 0.15 0.15 0.56 Air Flow Rate(H / M / L) CMM 17 / 15 / 13 19 / 16 / 14 25 / 21 / 19 cfm 600 / 529 / 459 671 / 565 / 494 883 / 742 / 671 Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Safety Device Fuse Fuse Fuse Pipe Liquid Side mm(inch) Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Connections Gas Side mm(inch) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 25(1) 25(1) 25(1) Net Weight Body kg(lbs) 20.8(45.8) 20.8(45.8) 23.5(51.8) Noise Level (Sound Press, 1.5m, H / M / L) dB(A) 36 / 34 / 31 39 / 35 / 33 43 / 40 / 37 Power Supply 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cord CV2.0 X 3C CV2.0 X 3C CV2.0 X 3C Transmission cable CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C Panel Color Morning fog Morning fog Morning fog Panel Name(Accessory) PT-UMC Elevation Grill(Accessory) PTEGM0 Unit kW kcal/h Btu/h kW kcal/h Btu/h

1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 4-way _ 4

Indoor Units

Notes:-


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Casing Dimensions (WxDxH)

Body Front Panel

Indoor Units

Coil Fan

Rows x Columns x FPI Face Area Type Motor Outputx Number Running Current Air Flow Rate(H / M / L)

Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch mm inch m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Pipe Liquid Side mm(inch) Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level (Sound Press, 1.5m, H / M / L) dB(A) Power Supply Ø, V, Hz Refrigerant Control Power cord Transmission cable Panel Color Panel Name(Accessory) Elevation Grill(Accessory)

4 Way Ceiling Cassette ARNU42GTM*2 ARNU48GTM*2 12.3 14.1 10,600 12,100 42,000 48,100 13.8 15.9 11,000 13,200 43,800 51,200 Galvanized Steel Plate Galvanized Steel Plate 840 x 840 x 288 840 x 840 x 288 33.0 x 33.0 x 11.3 33.0 x 33.0 x 11.3 950 x 950 x 25 950 x 950 x 25 37.4 x 37.4 x 1 37.4 x 37.4 x 1 2 x 12 x 19 2 x 12 x 19 0.57 0.57 Turbo Fan Turbo Fan 135 135 0.56 0.56 30 / 27 / 24 31 / 29 / 27 1,059 / 954 / 848 1,059 / 1,024 / 954 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø9.52(3/8) Ø9.52(3/8) Ø15.88(5/8) Ø15.88(5/8) 25(1) 25(1) 25.6(56.4) 25.6(56.4) 44 / 41 / 38 46 / 43 / 41 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV2.0 X 3C CV2.0 X 3C CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C Morning fog Morning fog PT-UMC PTEGM0

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

5 _ Ceiling Cassette 4-way

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


Ceiling Cassette 4-way _ 6

6

A

CEILING OPENING

700

473

380(Air outlet hole)

700 B

376(Inlet Grille)

22.5

5

4

523 59.5 84.5

3

A ARROW VIEW

30 19 142.5

2 1

79 53 48

128 570

165

461 570

517

Power supply connection Air discharge grill Air suction grill

3 4 5 6

(unit : mm)

VP25(Φ32)

Unit size(5k, 7k, 9k, 12k):ø12.7

Unit size(5k, 7k, 9k, 12k):ø6.35

Descripition

B ARROW VIEW

500mm or more*

• REQUIRED SPACE

500mm or more*

CHASSIS CODE: TR

500mm or more*

500mm or more*

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

Name

1

Number

ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

Branch Duct Connection

63

69

517 214 34.5

4R20

5

570

Indoor Units

R3

3. Dimensions


A

CEILING OPENING

700

473

380(Air outlet hole)

B

6

376(Inlet Grille) 22.5

5

4

59.5

523

30 19 142.5

2 1

3

A ARROW VIEW

125 95.5

4R20

79 48 570

165

461 570

517

5

174

R3

517

Power supply connection Air discharge grill Air suction grill

3 4 5 6 Note

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

Name

1

Number

(unit : mm)

VP25(Φ32)

Unit size(15k, 18k):Ø12.7

Unit size(15k, 18k):Ø6.35

Descripition

ARNU15GTQ*2 ARNU18GTQ*2

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

500mm or more*

• REQUIRED SPACE

500mm or more*

CHASSIS CODE: TQ

500mm or more*

500mm or more*

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

B ARROW VIEW

Branch Duct Connection

63

68

570

256

7 _ Ceiling Cassette 4-way 76 94

Indoor Units

3. Dimensions

700


Ceiling Cassette 4-way _ 8

31

475

71

B ARROW VIEW

35

Ceiling opening

870-920(CEILING OPENING SPACE) 786(SUSPENSION POSITION)

500(Air outlet Hole) 737 950

614(Inlet Grille) 682(SUSPENSION POSITION)

ø70

OUTDOOR AIR INTAKE (DIRECT CONNECTION)

B

62

669(SUSPENSION POSITION) 420 393

13-ø 3, 3 Hole

26

71

300 OR LESS

420

950

25 870-920(CEILING OPENING SPACE)

6

2

A

65 40

5

671 108 60

1

840

165

350

53.5

60 82 99

4

3 Branch Duct Connection

80

840

787

787

804

204

BRANCH DUCT CONNECTION

684 840 92

VP25(Φ32)

Unit size(24k, 28k):ø15.88

Unit size(24k, 28k):ø9.52

92

10 350

50

92

165

92

500mm or more*

BRANCH DUCT CONNECTION

500mm or more*

CHASSIS CODE: TP

500mm or more*

500mm or more*

• REQUIRED SPACE

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

A ARROW VIEW

165

(unit : mm) Descripition

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air suction grill

4

Air discharge grill

Drain pipe connection Power supply connection

3

6

Gas pipe connection

2

5

Liquid pipe connection

Name

1

Number

ARNU24GTP*2 ARNU28GTP*2

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

13-ø 3, 3 Hole

79

204 154 79 41.5

32 50 50

Indoor Units

4-R20

3. Dimensions


13-ø 3, 3 Hole

35

71

B

ø70

OUTDOOR AIR INTAKE (DIRECT CONNECTION)

B ARROW VIEW

31

475

Ceiling opening

786(SUSPENSION POSITION)

870-920(CEILING OPENING SPACE)

682(SUSPENSION POSITION)

500(Air outlet Hole) 737 950

614(Inlet Grille) 25

2

870-920(CEILING OPENING SPACE)

6

110

1

A

60 840

165

350

103 141

246

3

4

Branch Duct Connection

53.5

80

840

78

5

420

300 OR LESS 80

669(SUSPENSION POSITION) 420 393

44

71

950 40 107

246 195 100 52

BRANCH DUCT CONNECTION 43 60

4-R20

13-ø 3, 3 Hole

100

9 _ Ceiling Cassette 4-way 60

165

10 350

92

165

92 BRANCH DUCT CONNECTION

500mm or more*

500mm or more*

CHASSIS CODE: TN

500mm or more*

500mm or more*

• REQUIRED SPACE

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

A ARROW VIEW

92

VP25(Φ32)

Unit size(36k):ø15.88

Unit size(36k):ø9.52

Descripition

(unit : mm)

1. Unit should be installed in compliance with the installation manual in the product box.

Note

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

92

5

Air suction grill

Air discharge grill

4 6

Drain pipe connection Power supply connection

3

Gas pipe connection

2

Name Liquid pipe connection

ARNU36GTN*2

Ceiling Cassette 4-way

1

Number

Indoor Units

3. Dimensions


Ceiling Cassette 4-way _ 10

6

75

31

475

ø70

B

OUTDOOR AIR INTAKE (DIRECT CONNECTION)

B ARROW VIEW

35

71

Ceiling opening

682(SUSPENSION POSITION) 110

870-920(CEILING OPENING SPACE) 786(SUSPENSION POSITION)

300 OR LESS

420

614(Inlet Grille)

25 870-920(CEILING OPENING SPACE)

500(Air outlet Hole) 737 950

2

A

1 100 84

669(SUSPENSION POSITION) 420 393

13-ø 3, 3 Hole

71

288 165

237 350

53.5

Branch Duct Connection

3

4 76 60

136 13-ø 3, 3 Hole

BRANCH DUCTCONNECTION

60

840

Air suction grill

5 6

(unit : mm)

VP25(Φ32)

Unit size(42k, 48k):ø15.88

Unit size(42k, 48k):ø9.52

Descripition

10 350

92

165

92

500mm or more*

CHASSIS CODE: TM

500mm or more*

500mm or more*

• REQUIRED SPACE

500mm or more*

BRANCH DUCT CONNECTION

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

A ARROW VIEW

165

92

Air discharge grill

4

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

92

Power supply connection

3

Note

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

Name

ARNU42GTM*2 ARNU48GTM*2

Ceiling Cassette 4-way

1

Number

100

5

Indoor Units

4-R20

3. Dimensions

950


4. Piping Diagrams

Heat Exchanger

:Cooling :Heating

EEV Filter

Th3

Th2 Turbo Fan

Filter

lndoor unit

Indoor Units

Th1

Refrigerant pipe connection port diameter [Unit: mm(inch)]

Model

Gas

Liquid

ARNU05GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU07GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GTQ*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GTQ*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GTP*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU28GTP*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU36GTN*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU42GTM*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU48GTM*2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

11 _ Ceiling Cassette 4-way


5. Wiring Diagrams TR/TQ Chassis

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Cassette 4-way _ 12

Indoor Units

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC


5. Wiring Diagrams

Indoor Units

TM/TN/TP Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE1 / VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

13 _ Ceiling Cassette 4-way


6. Capacity Tables 6.1 Cooling Capacity

Capacity Index

1.6

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

32 24 TC SHC kW kW 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0

1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.1 1.1 1.8 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.7

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 4-way _ 14

Indoor Units

2.2

Outdoor air temp. (DB, °C)

Cooling capacity


6. Capacity Tables Cooling capacity

Capacity Index

Indoor Units

3.6

4.5

5.6

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

Notes: TC: Total Capacity(kW)

15 _ Ceiling Cassette 4-way

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

SHC: Sensible Heat Capacity(kW)

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

32 24 TC SHC kW kW 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8 5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0

2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.2 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4


6. Capacity Tables Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, °C)

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 5.0

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4 5.3 5.2 5.1 5.1 5.0 4.9 4.8

9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

5.4 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9 4.8 4.7 4.6 4.6 4.5 4.4

8.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7

5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8

8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2

5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.5 8.4

6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.9 5.8

9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.7 9.4 9.3 9.2 9.0 8.9 8.7 8.5

6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.1 6.1 5.9 5.8 5.7 5.6 5.5

10.8 10.6 10.5 10.4 10.2 10.1 10.0 9.9 9.7 9.6 9.5 9.3 9.2 9.0 8.9 8.8

6.3 6.2 6.1 6.1 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.4 5.3 5.2 5.1

10.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2

6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5

6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9

9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9

7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6

11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.0 10.8

7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.7 7.5

12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.5 12.2 12.1 11.9 11.7 11.4 11.2 11.0

8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.1 7.9 7.8 7.7 7.6 7.4 7.3 7.1

13.9 13.7 13.6 13.4 13.2 13.0 12.9 12.8 12.6 12.4 12.2 12.0 11.8 11.7 11.5 11.3

8.1 8.0 7.9 7.8 7.7 7.6 7.6 7.5 7.3 7.3 7.1 7.0 6.9 6.8 6.7 6.6

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 4-way _ 16

Indoor Units

Notes: TC: Total Capacity(kW)

32 24 TC SHC kW kW


6. Capacity Tables Cooling capacity

Capacity Index

Indoor Units

12.3

14.1

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5

9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3

11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2

7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3

Notes: TC: Total Capacity(kW)

17 _ Ceiling Cassette 4-way

8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1

8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2

SHC: Sensible Heat Capacity(kW)

13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.8 12.5 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 14.7 14.4

9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 8.9 8.7 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.2 10.0

30 22 TC SHC kW kW

32 24 TC SHC kW kW

14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.1 14.0 13.8 13.5 13.3 13.0 12.8 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.6 16.2 16.1 15.8 15.5 15.2 14.9 14.7

16.2 15.9 15.8 15.6 15.3 15.1 15.0 14.8 14.6 14.4 14.2 14.0 13.7 13.5 13.4 13.1 18.5 18.3 18.1 17.8 17.6 17.3 17.2 17.0 16.7 16.5 16.3 16.0 15.8 15.5 15.3 15.1

9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.4 9.2 9.1 8.9 8.8 8.6 8.4 8.3 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.8 10.5 10.4 10.2 10.0 9.9 9.7 9.5

9.4 9.3 9.2 9.1 9.0 8.8 8.8 8.6 8.5 8.4 8.3 8.2 8.0 7.9 7.8 7.7 10.8 10.7 10.6 10.4 10.3 10.1 10.1 9.9 9.8 9.6 9.5 9.4 9.2 9.1 8.9 8.8


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

1.6

2.8

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

1.2 1.2 1.3 1.4 1.5 1.5 1.5 1.6 1.6 1.7 1.8 1.9 2.0 2.0 2.1 2.1 2.1 2.1 2.1 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

1.2 1.2 1.3 1.4 1.5 1.5 1.5 1.6 1.6 1.7 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

1.2 1.2 1.3 1.2 1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

1.2 1.2 1.3 1.4 1.4 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

1.2 1.2 1.3 1.4 1.4 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

1.2 1.2 1.3 1.4 1.4 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

Notes: TC: Total Capacity(kW)

Ceiling Cassette 4-way _ 18

Indoor Units

2.2

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Heating capacity


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor Units

3.6

4.5

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6 3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0 3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

Notes: TC: Total Capacity(kW)

19 _ Ceiling Cassette 4-way


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

7.1

10.6

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2 6.2 6.3 6.7 7.1 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 10.2 10.4 10.6 10.6 10.6 10.6 10.6

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6 6.2 6.3 6.7 7.0 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 9.8 9.8 9.8 9.8 9.8 9.8 9.8

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0 6.2 6.3 6.7 6.3 6.6 7.0 7.1 7.3 7.5 7.8 8.1 8.5 9.0 9.2 9.2 9.2 9.2 9.2 9.2

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 6.1 6.3 6.7 7.0 7.4 7.8 7.9 8.1 8.2 8.5 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 6.1 6.3 6.7 7.0 7.4 7.7 7.9 8.1 8.2 8.5 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.1 6.3 6.6 7.0 7.4 7.7 7.8 7.9 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

8.0 8.2 8.7 9.2 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 13.2 13.4 13.7 13.7 13.7 13.7 13.7

8.0 8.2 8.7 9.0 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 12.7 12.7 12.7 12.7 12.7 12.7 12.7

8.0 8.2 8.7 8.2 8.6 9.0 9.2 9.4 9.7 10.1 10.4 11.0 11.6 11.9 11.9 11.9 11.9 11.9 11.9

7.9 8.2 8.7 9.0 9.5 10.1 10.2 10.5 10.6 11.0 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5

7.9 8.1 8.7 9.0 9.5 10.0 10.2 10.5 10.6 11.0 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2

7.9 8.1 8.6 9.1 9.5 10.0 10.1 10.2 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4

Notes: TC: Total Capacity(kW)

Ceiling Cassette 4-way _ 20

Indoor Units

8.2

Indoor air temp. (DB, °C)


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

12.3

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

9.2 9.5 10.1 10.6 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 15.3 15.5 15.9 15.9 15.9 15.9 15.9

9.2 9.5 10.1 10.5 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 14.8 14.8 14.8 14.8 14.8 14.8 14.8

9.2 9.5 10.1 9.5 10.0 10.4 10.7 10.9 11.3 11.7 12.1 12.8 13.5 13.8 13.8 13.8 13.8 13.8 13.8

9.1 9.5 10.1 10.5 11.0 11.7 11.9 12.1 12.2 12.8 13.3 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4

9.1 9.4 10.1 10.5 11.0 11.6 11.9 12.1 12.2 12.8 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0

9.1 9.4 9.9 10.5 11.0 11.6 11.7 11.8 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1

14.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

10.7 11.0 11.6 12.2 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.7 17.9 18.3 18.3 18.3 18.3 18.3

10.7 11.0 11.6 12.1 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.0 17.0 17.0 17.0 17.0 17.0 17.0

10.7 11.0 11.6 10.9 11.5 12.0 12.3 12.6 13.0 13.5 13.9 14.7 15.5 15.9 15.9 15.9 15.9 15.9 15.9

10.5 11.0 11.6 12.1 12.7 13.5 13.7 14.0 14.1 14.7 15.3 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4

10.5 10.8 11.6 12.1 12.7 13.4 13.7 14.0 14.1 14.7 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9

10.5 10.8 11.4 12.1 12.7 13.4 13.5 13.6 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

21 _ Ceiling Cassette 4-way


7. Air Velocity and Temperature Distribution(Reference Data) ARNU05GTR*2, ARNU07GTR*2, ARNU09GTR*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m 2.0

2.0

2.0

1.5 1.0

1.5 1.0

2m

2.0 1.5

1.5 1.0

2.5m

1.5m

0m

1.5m

0m 2.5m

1.0 0.5

0.5

1m

0.5

0.5

2.5m

2m

1.5m

1m

0m

1.5m

0m 2.5m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 2m

18

18 20

20

22

21

21 2m 27

18

24

27

18 24

24

1m

22

33

1m

24

2.5m

1.5m

0m

1.5m

0m 2.5m

2.5m

1.5m

0m

1.5m

0m 2.5m

ARNU12GTR*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50° Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0 1.5

2.0

2m 1.5

2.0 1.5

1.0 1.0

1.0

0.5

2.5m

2m

1.5 1.0

0.5

1m

1m

0.5

0.5

1.5m

0m

1.5m

0m 2.5m

2.5m

1.5m

0m

0m 2.5m

1.5m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 18

33

18

20

2m

20

22

33

30 24

22

2m

30

27

27

24

21

21

1m

1m 24

2.5m

1.5m

24

0m

1.5m

0m 2.5m

2.5m

1.5m

0m

1.5m

0m 2.5m

Ceiling Cassette 4-way _ 22

Indoor Units

33


7. Air Velocity and Temperature Distribution(Reference Data) ARNU15GTQ*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0

2.0 1.5

1.0

1m

1m

0m

1m

2m

4m

0m

4m

3m

2m

1m

0m

1m

2m

3m

4m

2.7m

2.7m 18

18 20

20

33

33

2m

2m 22

22

21

24

24

1m

27

24

24

3m

21

1m 27

4m

0m

Temperature [°C]

Temperature [°C]

Indoor Units

0.5

0.5

3m

1m

1.0

1.0

0.5

2m

1.5

1.5

0.5 3m

2m

2m 1.5

1.0

4m

2.0

2m

1m

0m

1m

2m

3m

4m

0m

4m

3m

2m

1m

0m

1m

2m

3m

4m

0m

ARNU18GTQ*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0

2.0

1.5

2m

1.0

4m

3m

2m

1.5

1.5 1m

1.0

0.5 0m

1m

3m

4m

0m

4m

3m

2m

1m

1.0

0.5

2m

2m

1.5

1.0

0.5 1m

2.0

0.5

1m

0m

1m

2m

3m

4m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 18 20

18

22

33

20

2m

2m

2m

30

21

22

24

3m

33

30

1m

4m

0m

21 24

27

27

1m

24

24

1m

0m

1m

2m

23 _ Ceiling Cassette 4-way

3m

4m

0m

4m

3m

2m

1m

0m

1m

2m

3m

4m

0m


7. Air Velocity and Temperature Distribution(Reference Data) ARNU24GTP*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0

2m

2m 2.0

1.5

3m

1.0

1.0

1.0 4m

1m

1.5

2m

1m

0m

1m

3m

4m

0m

4m

2m

0.5

1m

0m

1m

2m

3m

4m

0m

Temperature [°C] 2.7m

2.7m

18 20 22

2m

24

2m

1m

0m

1m

2m

3m

4m

0m

4m

2m

3m

1m

24

24

27

23

24

30 22

22

1m 23

33

33 30

2m

1m

27

0m

1m

2m

3m

4m

0m

ARNU28GTP*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m 2.0

2m

2.0

1.0

1.0

1.0

2m

2m 1.5

1m

1.5

1.0 3m

2.7m

3.0 2.0

1.5

1m

1.5

4m

3.0 2.0

2.5

2.5

1m

0m

1m

2m

3m

4m

0m

0.5

4m

3m

2m

0.5

1m

0m

1m

2m

3m

4m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 18

33

18

33

2m

2m 21 22

22 23

4m

3m

2m

0m

23

1m

0m

1m

2m

3m

4m

0m

30

24

1m

30

1m

27

4m

3m

2m

21

24

1m

0m

27 1m

2m

3m

4m

0m

Ceiling Cassette 4-way _ 24

Indoor Units

18 20 22

3m

3m

1m

1.0

0.5

2m

Temperature [°C]

4m

2.0


7. Air Velocity and Temperature Distribution(Reference Data) ARNU36GTN*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

3.0 2.5 2.0

2.7m

3.0 2.5 2.0

2m 1.5

1.5 1.0 5m

4m

3m

1m

1m

2m

0m

1m

2m

3m

4m

Indoor Units

1.0

3m

2m

1m

2.7m

0m

1m

2m

3m

4m

0m 5m

22

23

1m

0m

2m

1m

2m

3m

4m

0m 5m

30

24 22

1m 23

2m

33

2m

20

22

2.7m

33

18

20

3m

4m

1m

Temperature [°C]

18

4m

5m

2m

2.0

1.0

0m 5m

2.7m

3.5 3.0 2.5

2.0

1.0

Temperature [°C]

5m

3.5 3.0 2.5

30

27

5m

4m

3m

2m

1m

24 22

1m

4m

0m 5m

27

0m

1m

2m

3m

ARNU42GTM*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

3.2m

3.2m 4.0

4.0

4.0 3.0

3.0

3.0

2m

3.0

4.0

2m

1m

5m

4m

3m

1m 2.0

2.0 1.0

2.0 1.0 2m

1m

0m

1m

2m

2.0

1.0

3m

4m

0m 5m

5m

4m

3m

2m

1.0

1m

0m

1m

2m

3m

4m

Temperature [°C]

Temperature [°C] 3.2m

3.2m

2m

20

33

33

18

18

24

20

22

22

4m

3m

2m

1m

0m

1m

2m

25 _ Ceiling Cassette 4-way

3m

22 27

24

24

30

22

1m

4m

0m 5m

5m

4m

2m

24 30

5m

0m 5m

3m

2m

1m

1m

27

0m

1m

2m

3m

4m

0m 5m


7. Air Velocity and Temperature Distribution(Reference Data) ARNU48GTM*2 Cooling

Heating

Discharge angle: 40째

Discharge angle: 50째

Air velocity [m/s]

Air velocity [m/s]

3.2m 4.0

1.0 4m

3m

2m

1m

0m

1m

2m

2m

3.0

3.0

1m

2.0 1.0

2.0

4.0

2m

3.0

3.0

5m

3.2m 4.0

4.0

1m 2.0

2.0

1.0

3m

4m

0m 5m

4m

5m

3m

2m

1m

1.0

0m

1m

2m

3m

4m

0m 5m

Temperature [째C]

Temperature [째C]

3.2m 33

2m

20

20

33

2m 22

24

22

24

1m 22 24

5m

4m

24

3m

2m

1m

1m

0m

1m

2m

3m

30

30 27

22

4m

0m 5m

5m

4m

3m

2m

1m

27

0m

1m

2m

3m

4m

0m 5m

Ceiling Cassette 4-way _ 26

Indoor Units

3.2m 18

18


8. Electric Characteristicss Units

Indoor Units

Model

Type

Power Supply Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

ARNU05GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU07GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU09GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU12GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU15GTQ*2

TQ

0.25

15

0.043

0.2

30

30

ARNU18GTQ*2

TQ

0.25

15

0.043

0.2

30

30

0.22

15

0.03

0.17

33

33

50

220-240

MAX : 264 MIN:198

ARNU24GTP*2

TP

ARNU28GTP*2

TP

0.22

15

0.03

0.17

33

33

ARNU36GTN*2

TN

0.81

15

0.135

0.64

144

144

ARNU42GTM*2

TM

0.81

15

0.135

0.64

144

144

ARNU48GTM*2

TM

0.81

15

0.135

0.64

144

144

ARNU05GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU07GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU09GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU12GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU15GTQ*2

TQ

0.25

15

0.043

0.2

30

30

ARNU18GTQ*2

TQ

0.25

15

0.043

0.2

30

30

ARNU24GTP*2

TP

0.22

15

0.03

0.17

33

33

ARNU28GTP*2

TP

0.22

15

0.03

0.17

33

33

ARNU36GTN*2

TN

0.81

15

0.135

0.64

144

144

ARNU42GTM*2

TM

0.81

15

0.135

0.64

144

144

ARNU48GTM*2

TM

0.81

15

0.135

0.64

144

144

60

220

MAX : 242 MIN:198

Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.

27 _ Ceiling Cassette 4-way


9. Sound Levels Overall Notes: - Sound measured at 1.5m below the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Ceiling 1.5m

Model H 29 29 30 32 36 37

Model H 36 39 43 44 46

ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 ARNU42GTM*2 ARNU48GTM*2

Sound Level dB(A) L M 34 31 35 33 40 37 41 38 43 41

Indoor Units

ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2 ARNU15GTQ*2 ARNU18GTQ*2

Sound Level dB(A) L M 26 27 26 27 27 29 27 30 32 34 34 35

Sound Pressure Level ARNU07GTR*2

ARNU09GTR*2 80

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

NC-60

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 8000

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

80

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU05GTR*2 80

NC-60

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 8000

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

NC-20

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-15 8000

Ceiling Cassette 4-way _ 28


9. Sound Levels ARNU12GTR*2

80

ARNU15GTQ*2

NC-65 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

Approximate Hearing Threshold

10

63

NC-60 50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-20 NC-15 125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-55

NC-25

20

NC-25

20

NC-65

60

10

Approximate Hearing Threshold 63

8000

125

ARNU24GTP*2

NC-60 NC-55 NC-50 NC-45 NC-40 NC-35

30

NC-30 20

10

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

NC-65

40

63

250

500

NC-15 1000 2000 4000 8000

4000

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25 Approximate Hearing Threshold 63

NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

NC-60

20

250

500

63

125

250

500

NC-15 1000 2000 4000 8000

NC-60

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

29 _ Ceiling Cassette 4-way

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

125

NC-20

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

125

250

500

1000

2000

4000

NC-15 8000

NC-65 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

125

NC-20

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

NC-65

60

NC-20

60

NC-20

70

NC-20

125

10

NC-25 Approximate Hearing Threshold

ARNU36GTN*2

ARNU48GTM*2

NC-65

30

NC-30

Octave Band Center Frequency (Hz)

Octave Band Center Frequency (Hz)

70

40

NC-35

30

20

NC-15 8000

80

50

NC-40

70

ARNU42GTM*2 Octave Band Sound Pressure Level (dB re 20μPa )

2000

NC-45

40

70

10

80

60

NC-50

80

Octave Band Center Frequency (Hz)

10

1000

NC-55

50

80

NC-20

125

500

20

NC-25 Approximate Hearing Threshold

NC-60

ARNU28GTP*2

70

50

250

NC-65

60

Octave Band Center Frequency (Hz)

80

60

70

NC-20

Octave Band Sound Pressure Level (dB re 20μPa )

60

Octave Band Sound Pressure Level (dB re 20μPa )

80

70

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

70

Indoor Units

ARNU18GTQ*2

80


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Anti-bacteria filter

Indoor Units

Air Intake

TEM P

Remote Controll

er

Air Outlet Wired Remote Controller(Optional)

Required Parts

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

Ceiling Board

50 or more

30 or less

50 or more

Above 250 360 or less

Ceiling Ceiling Board

100 or more

• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have sufficient maintenance space.

30 or more

10.1 Selection of the best location

Unit:cm Floor

Ceiling Cassette 4-way _ 30


10. Installation 10.2 Ceiling opening dimensions and hanging bolt location • The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions.

Ceiling Ceiling board

Level gauge

TQ/TR Chassis

TM/TN/TP Chassis

585~660(Ceiling opening)

875(Ceiling opening)

461

Unit:mm

CAUTION • This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.

875(Ceiling opening)

684(Hanging bolt)

840 Unit size 840 Unit size

671

517

570

585~660(Ceiling opening)

787(Hanging bolt)

570 319

523

Indoor Units

517

Unit:mm

• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.

NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam. Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

31 _ Ceiling Cassette 4-way


10. Installation Ceiling

Nut (W3/8 or M10)

Flat washer for M10 (accessory) Ceiling board

150mm

Keep the length of the bolt from the bracket to 40mm

Hanging bolt (W3/8 or M10)

Air Conditioner body

Ceiling board Keep the length of 15~18mm between the air conditioner bottom surface and the ceiling surface

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Set screw of paper model (4 pieces) Open the ceiling board along the outer edge of the paper model

Paper model for installation

• The following parts are locally purchased. ① Hanging Bolt - W 3/8 or M10 ② Nut - W 3/8 or M10 ③ Spring Washer - M10 ④ Plate Washer - M10

CAUTION

10.3 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

Indoor cord Remote control cord power cord

• TR/TQ Chassis [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

[Except Multi VIII Heat Pump Model] SODU B

SODU A

IDU B

IDU A

INT B

INT A

Terminal Block Indoor

4

1(L)

INDOOR POWER INPUT

2(N)

3

SODU

4

B

A

Outdoor Unit

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

INDOOR POWER INPUT

• TM/TN/TP Chassis [Multi V III Heat Pump Model]

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor

Terminal Block Indoor

1(L) 2(N) 3(L) 4(N)

5(A) 5(B) RD

POWER INPUT

SODU B

SODU A

IDU B

IDU A

INT B

INT A

YL BK

TO AIR FRESH KIT

Terminal Block Indoor

Terminal Block Indoor

SODU

1(L) 2(N) 3(L) 4(N)

5(A) 5(B) RD

B

POWER INPUT

YL BK

A

IDU B

INTERNET DRY1 DRY2 GND 12V A

B

A

-

-

-

-

Outdoor Unit

TO AIR FRESH KIT

WARNING Make sure that the screws of the terminal are not loose.

Ceiling Cassette 4-way _ 32

Indoor Units

• Tighten the nut and bolt to prevent the unit from falling.


10. Installation 10.4 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction.

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included in the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter). Piping side

Indoor Units

Air conditioner unit

Control box cover Decoration panel fixing screws (hexagon M5 screws) Temporally fitting at 2 places (Tightening about 10mm)

Louver motor

Decoration panel

Display Lead wire for louver motor and display

Decoration panel fixing screws (Hexagon M5 screw)

CAUTION Install certainly the decoration panel. Cool air leakage causes sweating.

Inlet Grille

Good example

⇨讀 Water drops fall.

Bad example Air conditioner unit

Ceiling board Decoration panel Fit the insulator (this part) and be careful for cool air leakage

33 _ Ceiling Cassette 4-way

Air conditioner unit Air

Cool air leakage (no good) Ceiling board Decoration panel


10. Installation 10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

• Be sure to install heat insulation on the drain piping.

1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

MAX 700mm

Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Max 300mm

Hanger distance 1~15m

Metal clamp Flexible drain hose

Hanger Bracket 1/50~1/100 slope

Max 700mm

CAUTION

Insulation

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.

HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).

Ceiling Cassette 4-way _ 34

Indoor Units

Feed water


10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:

Indoor Units

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Remote Controller

5feet (1.5meters)

TEMP

Controller Remote

no

no

Fig.1 Typical locations for remote controller

35 _ Ceiling Cassette 4-way


11. Accessories Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Shape

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

4 EA

1 SET

for gas pipe

Bolt

(Other)

4 EA • Paper pattern for installation • Owner's manual • Installation manual

for liquid pipe

Indoor Units

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Cassette 4-way _ 36


Indoor unit Ceiling Concealed Duct (High Static) 1. List of functions 2. Specifications 3. Dimensions & Gravity point 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure(E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2, ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2, ARNU28GBGA2 , ARNU36GBGA2, ARNU42GBGA2, ARNU48GBRA2, URNU76GB8A2, URNU96GB8A2 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O Accessory Accessory Accessory Accessory X Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Ceiling Concealed Duct(High Static) _ 1

Indoor Units

Installation

Function


2. Specifications Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A)

Indoor Units

Coil

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

ARNU07GBHA2 2.2 1,900 7,500 2.5 2,200 8,500 Galvanized Steel Plate 882 x 450 x 260 34.7 x 17.7 x 10.2 2 x 10 x 21 0.15 Sirocco Fan 118 0.92 8.5 / 7.5 / 6.0 300 / 265 / 212 8(78) 8.5 / 8.0 / 7.5 300 / 282 / 265 6(59) Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 26(57.4) 34 / 33 / 32 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C

Ceiling Concealed Duct -High Static ARNU09GBHA2 ARNU12GBHA2 2.8 3.6 2,400 3,100 9,600 12,300 3.2 4.0 2,800 3,400 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate 882 x 450 x 260 882 x 450 x 260 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2 2 x 10 x 21 2 x 10 x 21 0.15 0.15 Sirocco Fan Sirocco Fan 118 118 0.92 0.92 10.0 / 8.5 / 7.5 12.0 / 10.0 / 8.5 353 / 300 / 265 424 / 353 / 300 8(78) 8(78) 8.5 / 8.0 / 7.5 11.0 / 8.5 / 7.5 300 / 282 / 265 388 / 300 / 265 6(59) 6(59) Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 26(57.4) 26(57.4) 35 / 34 / 33 37 / 35 / 34 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Concealed Duct(High Static)

ARNU15GBHA2 4.5 3,900 15,400 5.0 4,300 17,100 Galvanized Steel Plate 882 x 450 x 260 34.7 x 17.7 x 10.2 2 x 10 x 21 0.15 Sirocco Fan 118 0.92 13.5 / 12.0 / 8.5 477 / 424 / 300 8(78) 13.5 / 12.0 / 11.0 477 / 424 / 388 6(59) Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 26(57.4) 39 / 38 / 37 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct(High Static) _ 3

Indoor Units

Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Coil

Ceiling Concealed Duct(High Static) ARNU18GBHA2 ARNU24GBHA2 ARNU28GBGA2 5.6 7.1 8.2 4,800 6,100 7,100 19,100 24,200 28,000 6.3 8.0 9.2 5,400 6,900 8,000 21,500 27,300 31,500 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 882 x 450 x 260 882 x 450 x 260 1,182 x 450 x 298 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2 46.5 x 17.7 x 11.7 3 x 10 x 21 3 x 10 x 21 3 x 12 x 21 0.15 0.15 0.26 Sirocco Fan Sirocco Fan Sirocco Fan 118 118 390 0.92 0.92 2.30 15.5 / 13.5 / 12.4 18.3 / 16.9 / 15.5 25.9 / 24.1 / 21.8 547 / 477 / 438 646 / 597 / 547 915 / 851 / 770 8(78) 8(78) 10(98) 15.3 / 13.6 / 10.3 19.0 / 16.4 / 14.5 25.3 / 21.8 / 17.6 540 / 480 / 364 671 / 579 / 512 893 / 770 / 622 6(59) 6(59) 8(78) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø6.35(1/4) Ø9.52(3/8) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) Ø15.88(5/8) 25(1) 25(1) 25(1) 26.5(58.4) 26.5(58.4) 38.0(83.8) 42.5 / 41 / 37 45 / 43 / 41 44 / 42 / 40 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C


2. Specifications Type Model Cooling Capacity

Heating Capacity

Ceiling Concealed Duct(High Static) Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A)

Indoor Units

Coil

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

ARNU36GBGA2 ARNU42GBGA2 ARNU48GBRA2 10.6 12.3 14.1 9,100 10,600 12,100 36,200 42,000 48,100 11.9 13.8 15.9 10,200 11,000 13,200 40,600 43,800 51,200 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 1,182 x 450 x 298 1,182 x 450 x 298 1,230 x 590 x 380 46.5 x 17.7 x 11.7 46.5 x 17.7 x 11.7 48.4 x 23.2 x 15 3 x 12 x 21 3 x 12 x 21 3 x 13 x 19 0.26 0.26 0.38 Sirocco Fan Sirocco Fan Sirocco Fan 390 390 390 2.30 2.30 2.40 32.3 / 29.0 / 25.3 34.5 / 32.3 / 30.7 44.8 / 40.6 / 33.3 1,141 / 1,024 / 894 1,218 / 1,141 / 1,084 1,582 / 1,434 / 1,176 10(98) 10(98) 14(137) 28.4 / 25.3 / 21.8 32.0 / 28.4 / 27.2 44.4 / 39.5 / 33.5 1,003 / 894 / 770 1,130 / 1,003 / 961 1,568 / 1,395 / 1,183 8(78) 8(78) 10(98) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) 25(1) 25(1) 25(1) 38(83.8) 38(83.8) 53(117) 46 / 44 / 42 48 / 46 / 45 45 / 43 / 41 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

4 _ Ceiling Concealed Duct(High Static)

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications Type Model

Ceiling Concealed Duct(High Static) URNU76GB8A2 URNU96GB8A2 22.4 28 Cooling Capacity 19,300 24,100 76,400 95,900 25.2 31.5 Heating Capacity 21,700 27,100 86,000 107,500 Casing Galvanized Steel Plate Galvanized Steel Plate mm 1,562 x 688 x 460 1,562 x 688 x 460 Dimensions(WxDxH) Body inch 61.5 x 27.1 x 18.1 61.5 x 27.1 x 18.1 Rows x Columns x FPI 3 x 21 x 19 3 x 21 x 19 Coil Face Area m3 0.59 0.59 Type Sirocco Fan Sirocco Fan Motor Output x Number W 375 x 2 375 x 2 Running Current A 4.50 4.50 Air Flow Rate(H / M / L) CMM 60.0 / 50.0 / 50.0 72.0 / 64.0 / 64.0 (High Mode-factory set) cfm 2,119 / 1,766 / 1,766 2542 / 2,260 / 2,260 Fan External Static Pressure mmAq(Pa) 22(216) 22(216) Air Flow Rate(H / M / L) CMM 64.0 / 50.0 / 50.0 76.0 / 64.0 / 64.0 (Standard Mode) cfm 2,260 / 1,766 / 1,766 2,684 / 2,260 / 2,260 External Static Pressure mmAq(Pa) 15(147) 15(147) Drive Direct Direct Motor type BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse Fuse Liquid Side mm(inch) Ø9.52(3/8) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø19.05(3/4) Ø22.2(7/8) Drain Pipe(Internal Dia.) mm(inch) 25(1) 25(1) Net Weight kg(lbs) 87(192) 87(192) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) 50 / 48 / 48 52 / 50 / 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Unit kW kcal/h Btu/h kW kcal/h Btu/h

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct(High Static) _ 5

Indoor Units

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.


5

7.

R3

60

114

450

260

47

355

158

20

175

75

21

49

64

24

243

5

428

6

882

212

882

87 750

932

745

243

119

65

108

30

115

4

450 47

133 127 106

6 _ Ceiling Concealed Duct(High Static)

450

219 119

1 2

100

50

70

260

29

51

3

123 140

48 52 165

31

Air suction

6

Unit size(7k,9k,12k,18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k,9k,12k,18k):ø12.7 Unit size(24k):ø15.88

Descripition

(unit : mm)

Gravity point

CHASSIS CODE: BH

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air discharge

5

Drain pipe connection Power supply connection

3 4

Gas pipe connection

Liquid pipe connection

Name

2

1

Number

ARNU07GBHA2 ARNU09GBHA2 ARNU12GBHA2 ARNU15GBHA2 ARNU18GBHA2 ARNU24GBHA2

Ceiling Concealed Duct (High Static)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

101

Indoor Units

3. Dimensions & Gravity point

355

224


Ceiling Concealed Duct(High Static) _ 7

ø1

00

60

152

224

20

298

220

23

186

450

232

49

565

243

5

6

1,182

232

1,182

87 830

1,230

243

232

115

108

29

75

87

355 450 158 113

219 136

1,043

1

100

50

2 261

165

3

122 140

47 53

32

Note

(unit : mm)

Unit size(28k,36k,42k):ø15.88

Unit size(28k,36k,42k):ø9.52

Descripition

Gravity point

CHASSIS CODE: BG

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Air suction

Air discharge

5 6

Power supply connection

4

Drain pipe connection

Gas pipe connection

2 3

Liquid pipe connection

1

Name

ARNU28GBGA2 ARNU36GBGA2 ARNU42GBGA2

Ceiling Concealed Duct (High Static)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

102 51

Number

Indoor Units

4

3. Dimensions & Gravity point


R6

0

60

198

312

380

50

215

5

621

279

6

1,230

1,004

241

118 1,004

1,284 1,230

279 215

120

114

4

2

90

1

135 190 260

115

101 83

Name

Air discharge Air suction

4 5 6

Unit size(48k):ø15.88

Unit size(48k):ø9.52

Descripition

(unit : mm)

Gravity point

CHASSIS CODE: BR

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Power supply connection

3

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

3

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

1

Number 26

ARNU48GBRA2

Ceiling Concealed Duct (High Static)

72 123 221 122 144

1,092

477 590 56 168

25

303

32

140

590

8 _ Ceiling Concealed Duct(High Static) 185 174

302 293

Indoor Units

3. Dimensions & Gravity point


Ceiling Concealed Duct(High Static) _ 9

460

460

688

293

5

329

819

6 1,622

1,562

320

1,220

1,562

329

115

688 30

222

560 64

290 161

20

440

318

1,396

358

68

18

109

58

122 60 70 64

397

Air suction

(unit : mm)

Unit size(76k):ø19.05 Unit size(96k):ø22.2

Unit size(76k,96k):ø9.52

Descripition

Gravity point

CHASSIS CODE: B8

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

6

5

Air discharge

Drain pipe connection Power supply connection

3 4

Gas pipe connection

2

Name Liquid pipe connection

3

1

Number

70 120

2

URNU76GB8A2 URNU96GB8A2

Ceiling Concealed Duct (High Static)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

1

40 99 1

Indoor Units

4

3. Dimensions & Gravity point


4. Piping Diagrams

Heat Exchanger

:Cooling :Heating

EEV Filter

Th3

Th2 Sirocco Fan

Indoor Units

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GBHA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU28GBGA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU36GBGA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU42GBGA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU48GBRA2

Ø15.88(5/8)

Ø9.52(3/8)

URNU76GB8A2

Ø19.05(3/4)

Ø9.52(3/8)

URNU96GB8A2

Ø22.2(7/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

10 _ Ceiling Concealed Duct(High Static)


5. Wiring Diagrams BH Chassis

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Concealed Duct(High Static) _ 11

Indoor Units

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC


5. Wiring Diagrams

Indoor Units

BG Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC

LOCATION POINT AC Power supply Fan motor output Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

12 _ Ceiling Concealed Duct(High Static)


5. Wiring Diagrams BR Chassis

LOCATION POINT AC Power supply Fan motor output Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Concealed Duct(High Static) _ 13

Indoor Units

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC


5. Wiring Diagrams

Indoor Units

B8 Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1, CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-DISPLAY CN-OPTION CN-ZONE

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact RF Remocon Option PCB Zone controller

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC Output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room thermistor Remote control line Dry contact line RF Remocon receiver Option PCB connector Zone controller line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

14 _ Ceiling Concealed Duct(High Static)


6. Capacity Tables 6.1 Cooling Capacity

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0

2.3 2.3 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

3.0 2.9 2.9 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4

Capacity Index

Outdoor air temp. (DB, °C)

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct(High Static) _ 15

Indoor Units

Notes: TC: Total Capacity(kW)

30 22 TC SHC kW kW


6. Capacity Tables Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

4.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8

3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.1 3.0

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0

6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8

4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0

4.4 4.3 4.3 4.2 4.1 4.1 4.1 4.0 3.9 3.9 3.8 3.8 3.7 3.6 3.6 3.5

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.3 5.2 5.1 5.0 4.9 4.8

9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5

Indoor Units

Capacity Index

Outdoor air temp. (DB, °C)

Notes: TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

16 _ Ceiling Concealed Duct(High Static)

32 24 TC SHC kW kW


6. Capacity Tables Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

8.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0

8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2

6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.5 8.4

6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.1 6.0

9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.7 9.4 9.3 9.2 9.0 8.9 8.7 8.5

6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7

10.8 10.6 10.5 10.4 10.2 10.1 10.0 9.9 9.7 9.6 9.5 9.3 9.2 9.0 8.9 8.8

6.5 6.4 6.3 6.2 6.1 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.3 5.3

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3

6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3

9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5

7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0

10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3

7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1

11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.0 10.8 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.8 12.5

8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.9 7.7 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.2 9.0

12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.5 12.2 12.1 11.9 11.7 11.4 11.2 11.0 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.1 14.0 13.8 13.5 13.3 13.0 12.8

8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.7 9.4 9.3 9.2 9.0 8.8 8.7 8.5

13.9 13.7 13.6 13.4 13.2 13.0 12.9 12.8 12.6 12.4 12.2 12.0 11.8 11.7 11.5 11.3 16.2 15.9 15.8 15.6 15.3 15.1 15.0 14.8 14.6 14.4 14.2 14.0 13.7 13.5 13.4 13.1

8.4 8.2 8.2 8.0 7.9 7.8 7.8 7.7 7.5 7.5 7.3 7.2 7.1 7.0 6.9 6.8 9.7 9.6 9.5 9.3 9.2 9.1 9.0 8.9 8.8 8.6 8.5 8.4 8.3 8.1 8.0 7.9

10.6

12.3

Notes: TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct(High Static) _ 17

Indoor Units

Capacity Index

Outdoor air temp. (DB, °C)


6. Capacity Tables Cooling capacity

Capacity Index

Indoor Units

14.1

22.4

28.0

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9

11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5

13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1

9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8

10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3

14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0

10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6

SHC: Sensible Heat Capacity(kW)

18 _ Ceiling Concealed Duct(High Static)

15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 14.7 14.4 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8

10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.6 10.4 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2

30 22 TC SHC kW kW

32 24 TC SHC kW kW

16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.6 16.2 16.1 15.8 15.5 15.2 14.9 14.7 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5

18.5 18.3 18.1 17.8 17.6 17.3 17.2 17.0 16.7 16.5 16.3 16.0 15.8 15.5 15.3 15.1 29.4 29.0 28.7 28.3 27.9 27.5 27.4 27.0 26.6 26.2 25.8 25.4 25.0 24.6 24.3 23.9 36.8 36.3 35.9 35.4 34.9 34.4 34.2 33.7 33.2 32.8 32.3 31.8 31.3 30.8 30.4 29.9

11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.2 10.9 10.8 10.7 10.5 10.3 10.1 9.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1

11.3 11.1 11.0 10.8 10.7 10.5 10.5 10.3 10.2 10.0 9.9 9.7 9.6 9.4 9.3 9.2 16.7 16.5 16.3 16.1 15.9 15.6 15.5 15.3 15.1 14.9 14.7 14.4 14.2 14.0 13.8 13.6 20.9 20.6 20.4 20.1 19.8 19.5 19.4 19.1 18.9 18.6 18.3 18.1 17.8 17.5 17.3 17.0


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating capacity

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct(High Static) _ 19

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


6. Capacity Tables Heating capacity

Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

4.5

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

20 _ Ceiling Concealed Duct(High Static)


6. Capacity Tables Heating capacity

Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

8.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

6.2 6.3 6.7 7.1 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 10.2 10.4 10.6 10.6 10.6 10.6 10.6

6.2 6.3 6.7 7.0 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 9.8 9.8 9.8 9.8 9.8 9.8 9.8

6.2 6.3 6.7 6.3 6.6 7.0 7.1 7.3 7.5 7.8 8.1 8.5 9.0 9.2 9.2 9.2 9.2 9.2 9.2

6.1 6.3 6.7 7.0 7.4 7.8 7.9 8.1 8.2 8.5 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9

6.1 6.3 6.7 7.0 7.4 7.7 7.9 8.1 8.2 8.5 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6

6.1 6.3 6.6 7.0 7.4 7.7 7.8 7.9 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0

10.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

8.0 8.2 8.7 9.2 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 13.2 13.4 13.7 13.7 13.7 13.7 13.7

8.0 8.2 8.7 9.0 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 12.7 12.7 12.7 12.7 12.7 12.7 12.7

8.0 8.2 8.7 8.2 8.6 9.0 9.2 9.4 9.7 10.1 10.4 11.0 11.6 11.9 11.9 11.9 11.9 11.9 11.9

7.9 8.2 8.7 9.0 9.5 10.1 10.2 10.5 10.6 11.0 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5

7.9 8.1 8.7 9.0 9.5 10.0 10.2 10.5 10.6 11.0 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2

7.9 8.1 8.6 9.1 9.5 10.0 10.1 10.2 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4

12.3

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

9.2 9.5 10.1 10.6 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 15.3 15.5 15.9 15.9 15.9 15.9 15.9

9.2 9.5 10.1 10.5 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 14.8 14.8 14.8 14.8 14.8 14.8 14.8

9.2 9.5 10.1 9.5 10.0 10.4 10.7 10.9 11.3 11.7 12.1 12.8 13.5 13.8 13.8 13.8 13.8 13.8 13.8

9.1 9.5 10.1 10.5 11.0 11.7 11.9 12.1 12.2 12.8 13.3 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4

9.1 9.4 10.1 10.5 11.0 11.6 11.9 12.1 12.2 12.8 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0

9.1 9.4 9.9 10.5 11.0 11.6 11.7 11.8 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct(High Static) _ 21

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


6. Capacity Tables Heating capacity

Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

14.1

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

10.7 11.0 11.6 12.2 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.7 17.9 18.3 18.3 18.3 18.3 18.3

10.7 11.0 11.6 12.1 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.0 17.0 17.0 17.0 17.0 17.0 17.0

10.7 11.0 11.6 10.9 11.5 12.0 12.3 12.6 13.0 13.5 13.9 14.7 15.5 15.9 15.9 15.9 15.9 15.9 15.9

10.5 11.0 11.6 12.1 12.7 13.5 13.7 14.0 14.1 14.7 15.3 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4

10.5 10.8 11.6 12.1 12.7 13.4 13.7 14.0 14.1 14.7 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9

10.5 10.8 11.4 12.1 12.7 13.4 13.5 13.6 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9

22.4

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

16.9 17.4 18.4 19.4 20.4 21.4 21.7 22.2 22.9 23.9 25.0 26.5 28.0 28.4 29.0 29.0 29.0 29.0 29.0

16.9 17.4 18.4 19.2 20.4 21.4 21.7 22.2 22.9 23.9 25.0 26.5 27.0 27.0 27.0 27.0 27.0 27.0 27.0

16.9 17.4 18.4 17.3 18.2 19.1 19.5 19.9 20.6 21.5 22.1 23.4 24.6 25.2 25.2 25.2 25.2 25.2 25.2

16.6 17.4 18.4 19.2 20.2 21.4 21.7 22.2 22.4 23.3 24.3 24.4 24.4 24.4 24.4 24.4 24.4 24.4 24.4

16.6 17.1 18.4 19.2 20.2 21.2 21.7 22.2 22.4 23.3 23.7 23.7 23.7 23.7 23.7 23.7 23.7 23.7 23.7

16.6 17.1 18.1 19.2 20.2 21.2 21.4 21.6 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0

28.0

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

21.1 21.7 23.0 24.3 25.5 26.8 27.1 27.7 28.7 29.9 31.2 33.1 35.0 35.4 36.2 36.2 36.2 36.2 36.2

21.1 21.7 23.0 23.9 25.5 26.8 27.1 27.7 28.7 29.9 31.2 33.1 33.7 33.7 33.7 33.7 33.7 33.7 33.7

21.1 21.7 23.0 21.6 22.7 23.8 24.4 24.9 25.7 26.8 27.6 29.2 30.8 31.5 31.5 31.5 31.5 31.5 31.5

20.8 21.7 23.0 23.9 25.2 26.8 27.1 27.7 28.0 29.1 30.3 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5

20.8 21.4 23.0 23.9 25.2 26.5 27.1 27.7 28.0 29.1 29.6 29.6 29.6 29.6 29.6 29.6 29.6 29.6 29.6

20.8 21.4 22.7 24.0 25.2 26.5 26.8 27.0 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

22 _ Ceiling Concealed Duct(High Static)


7. External Static Pressure (E.S.P) & Air Flow ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2 ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2 Setting Value 70 80 90 100 110 120 130 140 145 150

(Unit: CMM)

Static Pressure(mmAq(Pa)) 3(29)

4(39)

5(49)

6(59)

7(69)

8(78)

9(88)

10(98)

12(118)

4.1 7.6 10.7 13.4 15.9 18.6 19.8 22.3 23.2 24.3

8.1 11.2 13.2 16.2 18.8 21.1 22.2 23.1

6.3 9.6 12.6 15.2 18.0 20.3 21.4 22.3

4.9 7.5 10.3 12.8 15.3 17.7 19.1 21.1

4.0 7.7 11.1 14.2 17.1 18.4 19.8

5.5 9.1 12.4 15.5 16.9 18.3

6.7 10.4 13.7 15.3 16.8

5.3 8.8 12.6 13.8 15.2

5.7 9.7 11.8 13.0

Setting Value 70 80 90 100 110 120 130 140 143 150 160

(Unit: CMM)

Static Pressure(mmAq(Pa)) 5(49)

6(59)

7(69)

8(78)

9(88)

10(98)

12(118)

14(137)

16(157)

4.0 12.1 17.0 21.4 25.8 30.0 36.0 37.5 41.0 42.4

6.9 15.5 19.6 24.0 28.5 32.1 33.9 38.0 41.6

4.13 11.01 17.53 21.8 26.93 30.41 32.1 36.0 38.2

6.2 14.0 19.8 25.3 29.0 30.7 34.5 36.1

4.2 11.6 17.9 23.4 27.4 28.8 32.1 35

6.6 14.6 21.8 25.9 27.2 30.1 34.6

12.1 18.1 21.6 23.0 26.3 31.1

14.6 17.8 20.1 22.4 26.8

11.3 14.5 16.8 18.2 23.3

ARNU48GBRA2 Setting Value 91 96 101 106 111 116 121 126

(Unit: CMM) Static Pressure(mmAq(Pa)) 5(49)

6(59)

8(78)

46.5 49.9 52.1 51.4 53.6 62.3 67.0 68.2

43.7 46.1 50.2 51.2 53.7 61.0 64.8 67.5

38.2 43.0 47.9 50.4 52.9 60.3 64.1 66.2

10(98) 12(118) 14(137) 15(147) 16(157) 17(168) 18(176) 20(196) 31.3 33.5 39.5 44.4 49.9 55.7 58.2 65.1

23.2 31.1 37.4 43.1 48.3 50.8 52.2 64.3

14.0 18.4 27.3 33.3 40.6 44.8 50.8 57.4

9.0 13.7 25.2 32.1 40.2 42.6 50.3 54.4

3.7 9.0 17.8 28.9 32.8 40.1 45.7 51.2

2.6 8.9 21.0 31.5 37.6 44.6 50.4

6.1 17.9 27.2 32.5 38.8 46.0

8.3 17.5 27.6 32.2 43.5

Note: 1. The above table shows the correlation between the air rates and E.S.P.

Ceiling Concealed Duct(High Static) _ 23

Indoor Units

ARNU28GBGA2, ARNU36GBGA2, ARNU42GBGA2


7. External Static Pressure (E.S.P) & Air Flow URNU76GB8A2, URNU96GB8A2 (Unit: CMM)

Indoor Units

Setting Value

Static Pressure(mmAq(Pa)) 6(59)

9(88)

12(118)

15(147)

18(177)

20(196)

22(216)

23(226)

25(245)

60

40.5

-

-

-

-

-

-

-

-

65

52.7

-

-

-

-

-

-

-

-

70

63.7

47.1

-

-

-

-

-

-

-

75

71.1

56.9

44.7

-

-

-

-

-

-

80

76.3

69.7

55.2

-

-

-

-

-

-

85

83.3

78.6

67.4

55.9

-

-

-

-

-

91

89.7

87.1

78.9

67.6

54.2

-

-

-

-

95

93.4

91.4

86.1

77.0

66.4

50.6

30.0

-

-

100

93.4

91.4

88.3

84.9

75.9

69.5

60.8

43.1

-

105

93.2

91.3

88.3

84.9

81.1

77.4

69.2

67.9

51.3

Note: 1. The above table shows the correlation between the air rates and E.S.P.

24 _ Ceiling Concealed Duct(High Static)


7. External Static Pressure (E.S.P) & Air Flow ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2 ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2 Capacity

High (factory set) 7k Standard High (factory set) 9k Standard High (factory set) Standard High (factory set) 15k Standard High (factory set) 18k Standard High (factory set) Standard

Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

120 117 115 110 107 105 125 120 117 110 107 105 130 125 120 115 110 105 135 130 120 123 120 115 140 135 130 130 125 110 150 145 140 145 135 128

8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59)

CMM 8.5 7.5 6 8.5 8 7.5 10 8.5 7.5 8.5 8 7.5 12 10 8.5 11 8.5 7.5 13.5 12 8.5 13.5 12 11 15.5 13.5 12.4 15.3 13.6 10.3 18.3 16.9 15.5 19 16.4 14.5

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

ARNU28GBGA2, ARNU36GBGA2, ARNU42GBGA2 Capacity

28k

High (factory set) Standard

36k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard High (factory set)

42k Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

140 136 130 130 124 116 151 145 139 138 130 124 157 154 151 145 138 134

10(98) 8(78) 10(98) 8(78) 10(98) 8(78)

CMM 25.9 24.1 21.8 25.3 21.8 17.6 32.3 29 25.3 28.4 25.3 21.8 34.5 32.3 30.7 32 28.4 27.2

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

8(78)

16(157)

6(59)

10(98)

8(78)

14(137)

6(59)

10(98)

8(78)

12(118)

6(59)

10(98)

Ceiling Concealed Duct(High Static) _ 25

Indoor Units

12k

24k

Standard Set value ESP(mmAq(Pa))

Mode


7. External Static Pressure (E.S.P) & Air Flow ARNU48GBRA2 Capacity

Standard Set value ESP(mmAq(Pa))

Mode High (factory set)

48k Standard

HI Mid Low HI Mid Low

116 111 106 106 101 96

14(137) 10(98)

CMM 44.8 40.6 33.3 44.4 39.5 33.5

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

10(98)

20(196)

7(67)

14(137)

URNU76GB8A2, URNU96GB8A2

Indoor Units

Capacity

76k

High (factory set) Standard

96k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low

102 98 98 86 83 83 105 102 102 94 89 89

22(216) 15(147) 22(216) 15(147)

26 _ Ceiling Concealed Duct(High Static)

CMM 60 50 50 64 50 50 72 64 64 76 64 64

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

12(118)

25(245)

12(118)

25(245)

12(118)

25(245)

12(118)

25(245)


8. Electric Characteristics Units

Power Supply

Input(W)

kW

FLA

1.32

15

0.118

1.06

150

150

BH

1.32

15

0.118

1.06

150

150

ARNU12GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU15GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU18GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU24GBHA2

BH

Max:264

1.32

15

0.118

1.06

150

150

ARNU28GBGA2

BG

Min:198

3.31

15

0.39

2.65

450

450

ARNU36GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU42GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU48GBRA2

BR

3.45

15

0.39

2.76

450

450

URNU76GB8A2

B8

6.47

15

0.75

5.18

800

800

URNU96GB8A2

B8

6.47

15

0.75

5.18

800

800

ARNU07GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU09GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU12GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU15GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU18GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU24GBHA2

BH

Max:242

1.32

15

0.118

1.06

150

150

ARNU28GBGA2

BG

Min:198

3.31

15

0.39

2.65

450

450

ARNU36GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU42GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU48GBRA2

BR

3.45

15

0.39

2.76

450

450

URNU76GB8A2

B8

6.47

15

0.75

5.18

800

800

URNU96GB8A2

B8

6.47

15

0.75

5.18

800

800

Type

ARNU07GBHA2

BH

ARNU09GBHA2

Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFM : Indoor Fan Motor

Hz

50

60

Volts

220-240

220

Cooling Heating

Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.

Ceiling Concealed Duct(High Static) _ 27

Indoor Units

MFA

Model

Voltage Range MCA

IFM


9. Sound Levels Overall

DISCHARGE

SUCTION

DUCT

DUCT 1.5m

2m

Indoor Units

Model

1m 1m

Sound Level dB(A)

Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Sound Level dB(A)

Model

ARNU07GBHA2

H 34

M 33

L 32

ARNU28GBGA2

H 44

M 42

L 40

ARNU09GBHA2

35

34

33

ARNU36GBGA2

46

44

42

ARNU12GBHA2

37

35

34

ARNU42GBGA2

48

46

45

ARNU15GBHA2

39

38

37

ARNU48GBRA2

45

43

41

ARNU18GBHA2

42.5

41

37

URNU76GB8A2

50

48

48

ARNU24GBHA2

45

43

41

URNU96GB8A2

52

50

50

Sound Pressure Level ARNU09GBHA2

ARNU12GBHA2 80

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

28 _ Ceiling Concealed Duct(High Static)

Octave Band Sound Pressure Level (dB re 20μPa )

80

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU07GBHA2 80

10

NC-25 Approximate Hearing Threshold 63

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)


9. Sound Levels ARNU15GBHA2

ARNU18GBHA2

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold 63

70

250

500

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

125

80

NC-15 1000 2000 4000 8000

10

NC-25 Approximate Hearing Threshold 63

NC-50

NC-40

NC-30 20

10

NC-60 NC-55 NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25 Approximate Hearing Threshold 63

250

500

NC-15 1000 2000 4000 8000

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

NC-60

125

250

500

Octave Band Center Frequency (Hz)

500

NC-15 1000 2000 4000 8000

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

10

NC-25 Approximate Hearing Threshold 63

125

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

125

250

500

Octave Band Center Frequency (Hz)

500

NC-15 1000 2000 4000 8000

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

NC-20 NC-15 1000 2000 4000 8000

250

URNU96GB8A2

80

NC-65

60

NC-20

Octave Band Center Frequency (Hz)

URNU76GB8A2

70

NC-20 NC-15 1000 2000 4000 8000

250

NC-65

60

NC-20

125

80

NC-65

60

NC-15 1000 2000 4000 8000

70

Octave Band Center Frequency (Hz)

ARNU48GBRA2

500

20

NC-25 Approximate Hearing Threshold 63

80

250

ARNU42GBGA2

NC-65

Octave Band Center Frequency (Hz)

70

125

80

60

10

NC-20

Octave Band Center Frequency (Hz)

70

NC-20

125

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

NC-65

50

NC-35

30

Octave Band Sound Pressure Level (dB re 20μPa )

70

60

NC-45

40

ARNU36GBGA2 Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

500

NC-55

50

80

20

Octave Band Sound Pressure Level (dB re 20μPa )

NC-60

Indoor Units

ARNU28GBGA2

10

250

NC-15 1000 2000 4000 8000

NC-65

60

Octave Band Center Frequency (Hz)

80

10

70

NC-20

125

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20μPa )

NC-65

60

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

70

10

ARNU24GBHA2

80

80

10

Approximate Hearing Threshold 63

NC-20

125

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

Ceiling Concealed Duct(High Static) _ 29


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Air outlet vents

Air filters

Air intake vents TEMP

Indoor Units

Wired LCD Remote Control

Remote Controller

Required Parts

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

10.1 Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unitʼs weight. • The place shall be able to inspect the unit as the figure. • The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit. • The servicing inspection hole in the ceiling should be as large as the product • The selection of the servicing hole should be approved by the customer

30 _ Ceiling Concealed Duct(High Static)

[Inspection Hole Standard] Number of Inspection hole

Distance between False ceiling & Actual ceiling

1

More than 100cm

2

20cm to 100cm

Hole size should be more than the size of IDU.

Less than 20cm

Remarks Sufficient space in the ceiling for servicing. Insufficient space. Difficult for servicing Minimum height for motor replacement.


10. Installation 10.2 Ceiling dimension and hanging bolt location

BH/BG/BR Chassis

C E

■ Installation of Unit Install the unit above the ceiling correctly.

A B

CASE 1

D

POSITION OF SUSPENSION BOLT

F

(G)

I

• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. • Refer to the Dimensions. (Unit:mm) Dimension

B

C

D

E

F

(G)

H

I

932

882

355

47

450

30

87

750

158

BG

1232

1182

355

47

450

30

87

830

186

BR

1282 1230

477

56

590

30

H

BH

Drainage hole

Indoor Units

A Chassis

B8 Chassis

120 1006 294

(Unit:mm) Dimension

A

B

C

D

E

F

G

H

I

J

K

L

Chassis

B8

1680 1565 1160 330 460 580 700 1400 1635 390 445 15

• Install the unit leaning to a drainage hole side as a figure for easy water drainage.

CASE 2 POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

Ceiling Concealed Duct(High Static) _ 31


10. Installation NOTE: • Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated. 5. Avoid places near high frequency generators. • Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling.

• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

Indoor Units

Old building

New building

1 Set anchor 2 Plate washer 3 Spring washer

CAUTION

4 Nut 5 Suspension bolts

Tighten the nut and bolt to prevent unit falling.

10.3 Connecting Cables between Indoor Unit and Outdoor Unit Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

IDU B

SODU A

IDU A

INT B

INT A

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING Make sure that the screws of the terminal are not loose.

Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.

32 _ Ceiling Concealed Duct(High Static)


10. Installation THERMAL INSULATION

All thermal insulation must comply with local requirement.

INDOOR UNIT BH/BG/BR Chassis

Union for liquid pipe

Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply)

Refrigerant pipe and thermal insulator(Local supply) Hose clamp for thermal insulator (Local supply)

B8

Thermal insulator for refrigerant pipe (Local supply) Union for gas pipe

Overlap with thermal insulator for piping. Hose clamp for thermal insulator(Local supply) Make sure that there is no clearance here.

Union for gas pipe

Hose crip for thermal insulator (Local supply) Refrigerant pipe and therma insulator(Local supply)

Union for liquid pipe

10.4 Checking the Drainage 1) Checking the Drainage

BH/BG/BR Chassis

1. Remove the Air Filter.

B8

2. Check the drainage. • Spray one or two glasses of water on the evaporator. • Ensure that water flows through drain hose of indoor unit without any leakage.

Ceiling Concealed Duct(High Static) _ 33

Indoor Units

Thermal insulator for refrigerant pipe (Local supply)


10. Installation 10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings • Be sure to install heat insulation on the drain piping.

1/50~1/100 MAX 700mm

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Feed water

Drain Pump

Flexible drain hose (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. Main drain pipe • Feed water to the flexible drain hose and check the piping for leakage. Drain • Be sure to check the drain pump for normal operation and port Glue the joint noise when electrical wiring is complete. Drain hose connection Use the clip (accessory) • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

CAUTION The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Max 300mm

Hanger distance 1~15m

Hanger Bracket 1/50~1/100 slope

Metal clamp Flexible drain hose

Max 700mm

Indoor Units

Drain test

Insulation

Flexible drain hose Flexible drain hose Flexible drain hose

34 _ Ceiling Concealed Duct(High Static)


10. Installation 10.6 Ground drain piping a) It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible.

Face the vent pipe opening facing downward to keep foreign matter from penetrating the system Face piping downward

b) The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.

10.7 Use of an auxiliary drain hose(flexible) a) To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be used. auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain. Auxiliary drain hose

Thermal insulation (drain pipe area)

Metal clamp

Metal clamp Thermal insulation(bend area) Drain pan

â?ˆ Important points - The drain pipe should be at least equal in size to that of the indoor unit. - The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe. - The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected some water should be added to the drain pan and the drain pump to check and see if it is functioning correctly. - All connections should be secure. (Special care is needed with PVC pipe) - Insulate auxiliary drain hose with thermal insulation band.

Ceiling Concealed Duct(High Static) _ 35

Indoor Units

Vent pipe


10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:

Indoor Units

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

36 _ Ceiling Concealed Duct(High Static)


11. Accessories Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

1 EA

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

4 EA

1 SET

(Other)

• Owner's manual • Installation manual Shape

for gas pipe

for liquid pipe

Indoor Units

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Concealed Duct(High Static) _ 37


Indoor unit Ceiling Concealed Duct(Low Static) 1. List of functions 2. Specifications 3. Dimensions & Gravity point 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure (E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Installation

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2, ARNU18GB2G2, ARNU24GB2G2 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O Accessory Accessory Accessory Accessory X Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Ceiling Concealed Duct(Low Static) _ 1

Indoor Units

Reliability

Function


2. Specifications Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A)

Indoor Units

Coil

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

Ceiling Concealed Duct (Low Static) ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 2 x 11 x 21 2 x 11 x 21 2 x 11 x 21 0.16 0.16 0.16 Sirocco Fan Sirocco Fan Sirocco Fan 28 28 28 0.15 0.15 0.15 8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 10.5 / 9.5 / 8.5 300 / 265 / 229 335 / 300 / 265 371 / 335 / 300 2(20) 2(20) 2(20) 8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 10.5 / 9.5 / 8.5 300 / 265 / 229 335 / 300 / 265 371 / 335 / 300 0(0) 0(0) 0(0) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuser �Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 25.4(1) 25.4(1) 25.4(1) 21(46.3) 21(46.3) 21(46.3) 33 / 32 / 29 34 / 33 / 32 35 / 34 / 33 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Concealed Duct(Low Static)

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications Type Model

Ceiling Concealed Duct (Low Static) ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2 4.5 5.6 7.1 Cooling Capacity 3,900 4,800 6,100 15,400 19,100 24,200 5.0 6.3 8.0 Heating Capacity 4,300 5,400 6,900 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 1,100 x 575 x 190 1,100 x 575 x 190 Dimensions(WxDxH) Body inch 32.3 x 21.7 x 7.5 43.3 x 21.7 x 7.5 43.3 x 21.7 x 7.5 Rows x Columns x FPI 2 x 11 x 21 3 x 10 x 18 3 x 10 x 18 Coil Face Area m3 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 28 76 76 Running Current A 0.15 0.38 0.38 Air Flow Rate(H / M / L) CMM 11.5 / 10.5 / 9.5 16.0 / 14.0 / 12.0 19.0 / 17.0 / 15.0 (High Mode-factory set) cfm 406 / 371 / 335 565 / 494 / 424 671 / 600 / 530 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H / M / L) CMM 11.5 / 10.5 / 9.5 16.0 / 14.0 / 12.0 19.0 / 17.0 / 15.0 (Standard Mode) cfm 406 / 371 / 335 565 / 494 / 424 671 / 600 / 530 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 26(57.3) 26(57.3) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) 38 / 37 / 36 40 / 37 / 34 43 / 40 / 37 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Unit kW kcal/h Btu/h kW kcal/h Btu/h

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct(Low Static) _ 3

Indoor Units

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.


575

18

154

383

18

B1 : 448 B2 : 573

D

B A

C

6

5 13

161 14 B1 : 186 B2 : 175 B1 : 73 B2 : 81

4 _ Ceiling Concealed Duct(Low Static) 4

3

216 24

65 60

190

Gas pipe connection Drain pipe connection Power supply connection Air discharge Air suction

2 3 4 5 6

1072

794

D

Descripition

(unit : mm)

1131

856

C

Unit size(7k,9k,12k,18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k,9k,12k,18k):ø12.7 Unit size(24k):ø15.88

1008

728

B

(unit: mm)

Gravity point

CHASSIS CODE: B1/B2

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Liquid pipe connection

Name

1100

820

1

Number

ARNU18GB2G2 ARNU24GB2G2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

2

1

A

ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2

Ceiling Concealed Duct (Low Static)

ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2

Indoor Units

3. Dimensions & Gravity point

277

190


4. Piping Diagrams

Heat Exchanger

EEV Filter

Th3

:Cooling :Heating

Th2 Sirocco Fan

Th1

Filter

lndoor unit

[Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GB2G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GB2G2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Concealed Duct(Low Static) _ 5

Indoor Units

Refrigerant pipe connection port diameter


5. Wiring Diagrams

Indoor Units

B1/B2 Chassis

CONNECTOR NUMBER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-D/PUMP CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-ZONE CN-DISPLAY CN-CC

SPEC. Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Drain pump output Option PWB. Communication Drain pump output AC power supply Zone Controller RF Remote controller Dry contact

DESCRIPTION Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV control output AC output for drain pump Communication between main and option Communication between indoor and outdoor AC output for drain pump AC power line input for indoor controller Zone control line RF remote control line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

6 _ Ceiling Concealed Duct(Low Static)


6. Capacity Tables 6.1 Cooling Capacity

Capacity Index

2.2

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6

30 22 TC SHC kW kW 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 1.9 1.9 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.6 2.5 2.5

32 24 TC SHC kW kW 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.3

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct(Low Static) _ 7

Indoor Units

2.8

Outdoor air temp. (DB, °C)

Cooling capacity


6. Capacity Tables Cooling capacity

Capacity Index

Indoor Units

4.5

5.6

7.1

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

SHC: Sensible Heat Capacity(kW)

8 _ Ceiling Concealed Duct(Low Static)

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.9 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.0

30 22 TC SHC kW kW 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 5.2 5.1 5.0 4.9 4.8 4.7

32 24 TC SHC kW kW 5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5 3.5 3.4 5.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5 4.4 4.4


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating capacity Indoor air temp. (DB, °C)

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct(Low Static) _ 9

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor Units

4.5

5.6

7.1

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

10 _ Ceiling Concealed Duct(Low Static)


7. External Static Pressure (E.S.P) & Air Flow ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2 Setting Value

Static Pressure(mmAq(Pa)) 0(0) 6.02 6.95 7.69 8.46 9.5 10.35 10.81 11.57 12.58 13.31 14.2 14.82

1(10) 2.25 3.32 5.16 6.93 7.37 8.72 9.66 10.31 11.22 12.27 13.24 13.92

2(20)

3(29)

4(39)

0.61 0.73 1.19 2.42 3.4 5.33 6.75 8.56 9.75 10.89 12.15 12.64

0.54 0.65 0.77 0.87 1.35 3.15 4.73 7.46 8.64 10.49 11.16

0.48 0.56 0.63 0.72 0.88 0.98 1.03 2.31 5.01 7.7 9.48

ARNU18GB2G2, ARNU24GB2G2 Setting Value 65 70 75 80 85 90 95 100 105 110 115 120 125 130

(Unit: CMM) Static Pressure(mmAq(Pa))

0(0)

1(10)

2(20)

3(29)

4(39)

10.07 11.39 12.01 13.21 14.24 15.04 16.02 17.11 17.99 19.04 19.77 20.94 21.97 22.83

6.9 8.49 9.79 11.03 12.36 13.34 14.63 15.56 16.53 17.71 18.62 19.92 20.56 21.98

0.82 2.2 4.2 5.92 9.41 10.8 12.5 13.66 15.17 16.22 17.1 18.56 19.25 20.75

0.92 2.1 5.29 7.59 11.53 12.35 14.23 15.23 16.98 17.68 19.32

1.01 1.34 5.35 7.67 10.45 13.25 14.66 16.06 17.73

Note : 1. The above table shows the correlation between the air rates and E.S.P.

Ceiling Concealed Duct(Low Static) _ 11

Indoor Units

60 65 70 75 80 85 90 95 100 105 110 115

(Unit: CMM)


7. External Static Pressure (E.S.P) & Air Flow ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2 Capacity

7k

High (factory set) Standard

9k

High (factory set) Standard High (factory set)

12k

Indoor Units

Standard Set value ESP(mmAq(Pa))

Mode

Standard High (factory set) 15k Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

94 92 86 75 69 62 99 94 92 82 75 69 103 99 94 89 80 75 107 105 99 95 89 82

2(20) 0(0) 2(20) 0(0) 2(20) 0(0) 2(20) 0(0)

CMM 8.5 7.5 6.5 8.5 7.5 6.5 9.5 8.5 7.5 9.5 8.5 7.5 10.5 9.5 8.5 10.5 9.5 8.5 11.5 10.5 9.5 11.5 10.5 9.5

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

ARNU18GB2G2, ARNU24GB2G2 Capacity

18k

High (factory set) Standard

24k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low

110 101 93 95 84 75 125 115 105 110 100 90

2(20) 0(0) 2(20) 0(0)

12 _ Ceiling Concealed Duct(Low Static)

CMM 16 14 12 16 14 12 19 17 15 19 17 15

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)


8. Electric Characteristics Units Model

Type

Power Supply Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

B1

0.22

15

0.028

0.17

30

30

ARNU09GB1G2

B1

0.22

15

0.028

0.17

30

30

ARNU12GB1G2

B1

Max:264

0.22

15

0.028

0.17

30

30

ARNU15GB1G2

B1

Min:198

0.22

15

0.028

0.17

30

30

ARNU18GB2G2

B2

0.55

15

0.076

0.44

80

80

ARNU24GB2G2

B2

0.55

15

0.076

0.44

80

80

ARNU07GB1G2

B1

0.22

15

0.028

0.17

30

30

ARNU09GB1G2

B1

0.22

15

0.028

0.17

30

30

ARNU12GB1G2

B1

Max:242

0.22

15

0.028

0.17

30

30

ARNU15GB1G2

B1

Min:198

0.22

15

0.028

0.17

30

30

ARNU18GB2G2

B2

0.55

15

0.076

0.44

80

80

ARNU24GB2G2

B2

0.55

15

0.076

0.44

80

80

50

60

220-240

220

Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFM : Indoor Fan Motor Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.

Ceiling Concealed Duct(Low Static) _ 13

Indoor Units

ARNU07GB1G2


9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1.5m

Ceiling 2.0m Microphone

Sound Levels dB(A) H 33 34 35 38 40 43

ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2

M 32 33 34 37 37 40

L 29 32 33 36 34 37

Sound Pressure Level ARNU09GB1G2

ARNU12GB1G2

80

80

70

70

70

NC-65

60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

20

63

NC-55

50 NC-50 NC-45

40 NC-40

30

NC-30

NC-15

250

500

10

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

ARNU15GB1G2

250

500

NC-55 NC-50 NC-45 NC-40 NC-35

30

NC-30

20

NC-25

Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

NC-60

40

NC-15

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

NC-40 NC-35

30

NC-30

NC-25 NC-20 NC-15

10 63

1000 2000 4000 8000

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

ARNU24GB2G2 80

70

NC-65

60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-20

125

NC-45

40

ARNU18GB2G2

NC-65

50

NC-50

Approximate Hearing Threshold

80

70

10

125

NC-55

50

Octave Band Center Frequency (Hz)

80

60

NC-60

NC-20 NC-15

63

NC-65

60

20

NC-25

Approximate Hearing Threshold

NC-20

125

NC-35

70

NC-65

60 NC-60

NC-15

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

14 _ Ceiling Concealed Duct(Low Static)

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-20

10 63

Octave Band Sound Pressure Level (dB re 20μPa )

10

NC-60

20

NC-25

Approximate Hearing Threshold

NC-65

60

Octave Band Sound Pressure Level (dB re 20μPa )

80

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU07GB1G2

Octave Band Sound Pressure Level (dB re 20μPa )

Indoor Units

Model Name

NC-20 NC-15

10 63

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)


10. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

Indoor Units

Required Parts

10.1 Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unitʼs weight. • The place shall be able to inspect the unit as given in the figure. • The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit. • The servicing inspection hole in the ceiling should be as large as the product. • The selection of the servicing hole should be approved by the customer.

[Inspection Hole Standard] Number of Inspection hole

Distance between False ceiling & Actual ceiling

1

More than 100cm

2

20cm to 100cm

Hole size should be more than the size of IDU.

Less than 20cm

Remarks Sufficient space in the ceiling for servicing. Insufficient space. Difficult for servicing Minimum height for motor replacement.

Inspection hole (600X600) Control box

Top view (unit: mm)

600

600

Front view

H

Ceiling Concealed Duct(Low Static) _ 15


10. Installation 10.2 Ceiling dimension and hanging bolt location ■ Installation of Unit Install the unit above the ceiling correctly.

CASE 1 M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

POSITION OF SUSPENSION BOLT

Indoor Units

• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.

• Install the unit leaning to a drainage hole side as a figure for easy water drainage.

CASE 2 POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

NOTE: • Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated. 5. Avoid places near high frequency generators.

16 _ Ceiling Concealed Duct(Low Static)


10. Installation 10.3 Connecting Cables Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

SODU A

IDU B

IDU A

INT B

INT A

IDU

INTERNET DRY1 DRY2 GND 12V

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

-

-

B

A

-

-

-

-

Outdoor Unit

Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.

10.4 Checking the Drainage • Spray one or two glasses of water on the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.

10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to pro- Pipe clamp vide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the Indoor unit drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings

Upward routing not allowed

Maintenance drain port

• Be sure to install heat insulation on the drain piping. 1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

MAX 700mm

Ceiling Concealed Duct(Low Static) _ 17

Indoor Units

INDOOR POWER INPUT


10. Installation Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Indoor Units

Drain pan Max 300mm

CAUTION

Hanger distance 1~15m

Hanger Bracket 1/50~1/100 slope

Metal clamp

The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Flexible drain hose

Max 700mm

Feed water

Insulation

10.6 Ground drain piping a) It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible.

Flexible drain hose

Flexible drain hose

Face the vent pipe mouth downward to keep foreign matter from penetrating the system Face piping downward Vent pipe

b) The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.

10.7 Use of an auxiliary drain hose(flexible) a) To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be used. auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain.

18 _ Ceiling Concealed Duct(Low Static)


10. Installation Auxiliary drain hose

Thermal insulation (drain pipe area)

Metal clamp

Metal clamp Thermal insulation(bend area) Drain pan

â?ˆ Important points

WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling Concealed Duct(Low Static) _ 19

Indoor Units

- The drain pipe should be at least equal in size to that of the indoor unit. - The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe. - The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected some water should be added to the drain pan and the drain pump to check and see if it is functioning correctly. - All connections should be secure. (Special care is needed with PVC pipe) - Insulate auxiliary drain hose with thermal insulation band.


11. Accessories Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for hanging backet 8 EA

Clamp (Tie Wrap) 4 EA

Insulation for fitting

(Other)

1 SET

• Owner's manual • Installation manual Shape

for gas pipe

Indoor Units

for liquid pipe

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

20 _ Ceiling Concealed Duct(Low Static)


Indoor unit Ceiling Concealed Duct_Built in 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure (E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of Functions Category

Air flow

Indoor Units

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O Accessory Accessory Accessory Accessory X Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

1 _ Ceiling Concealed Duct_Built in


2. Specification Ceiling Concealed Duct (Built-in) PBSGB30/PBSC30 PBSGB30/PBSC30 PBSGB30/PBSC30 Unit ARNU07GB3G2 ARNU09GB3G2 ARNU12GB3G2 kW 2.2 2.8 3.6 Cooling Capacity kcal/h 1,900 2,400 3,100 Btu/h 7,500 9,600 12,300 kW 2.5 3.2 4.0 Heating Capacity kcal/h 2,200 2,800 3,400 Btu/h 8,500 10,900 13,600 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 Dimensions(WxDxH) Body inch 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 Rows x Columns x FPI 2 x 11 x 21 2 x 11 x 21 2 x 11 x 21 Coil Face Area m3 0.16 0.16 0.16 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 30 30 30 Running Current A 0.15 0.15 0.15 Air Flow Rate(H / M / L) CMM 8.0 / 6.5 / 5.5 9.0 / 7.0 / 6.0 10.0 / 8.0 / 6.5 (High Mode-factor set) cfm 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H / M / L) CMM 8.0 / 6.5 / 5.5 9.0 / 7.0 / 6.0 10.0 / 8.0 / 6.5 (Standard Mode) cfm 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Liquid Side mm(inch) �Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Drain Pipe(Internal Dia.) mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 21(46.3) 21(46.3) Noise Level(Sound Press, 1m, H / M / L) dB(A) 33 / 32 / 29 34 / 33 / 32 35 / 34 / 33 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Type Accessory Model

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct_Built in _ 2

Indoor Units

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV: Electronic Expansion Valve 5. To be added for more available Models 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.


2. Specification Ceiling Concealed Duct (Built-in) PBSGB30/PBSC30 PBSGB40/PBSC40 PBSGB40/PBSC40 Unit ARNU15GB3G2 ARNU18GB4G2 ARNU24GB4G2 kW 4.5 5.6 7.1 Cooling Capacity kcal/h 3,900 4,800 6,100 Btu/h 15,400 19,100 24,200 kW 5.0 6.3 8.0 Heating Capacity kcal/h 4,300 5,400 6,900 Btu/h 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 1,100 x 575 x 190 1,100 x 575 x 190 Dimensions(WxDxH) Body inch 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 Rows x Columns x FPI 2 x 11 x 21 3 x 10 x 18 3 x 10 x 18 Coil Face Area m3 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 30 80 80 Running Current A 0.15 0.38 0.38 Air Flow Rate(H / M / L) CMM 11.0 / 10.0 / 8.0 14.0 / 12.0 / 10.0 17.0 / 15.0 / 10.0 (High Mode-factor set) cfm 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H / M / L) CMM 11.0 / 10.0 / 8.0 14.0 / 12.0 / 10.0 17.0 / 15.0 / 10.0 (Standard Mode) cfm 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 26(57.3) 26(57.3) Noise Level(Sound Press, 1m, H / M / L) dB(A) 41 / 40 / 37 43 / 40 / 37 46 / 43 / 37 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C

Indoor Units

Type Accessory Model

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV: Electronic Expansion Valve 5. To be added for more available Models 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

3 _ Ceiling Concealed Duct_Built in

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


Ceiling Concealed Duct_Built in _ 4

E

B

F

575

A

With Suction Grille & Suction Canvas

250

388

PBSC30 PBSC40

PBSGB30 PBSGB40

E 821 1100

B 910 1188

Btu/h A 7,9,12,15k 820 18,24k 1100 D 56 56 F G 274 42~250 274 42~250

C 359 359

With Suction Grille

G

C

6

1

4

5

Drain pipe connection Power supply connection Air suction Air discharge

3 4 5 6

(unit : mm) Unit size(7k,9k,12k,15k,18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k,9k,12k,15k,18k):ø12.7 Unit size(24k):ø15.88

Descripition

CHASSIS CODE: B3/B4

Gas pipe connection

2

Name

2

Liquid pipe connection

60

190

1

Number

3

65

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

277

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

500(Max)

D

190

216 24

With Suction Grille & Suction Canvas

Indoor Units

With Suction Grille

388 190

B3/B4

618

Ceiling Concealed Duct (Built in)

3. Dimensions


4. Piping Diagrams

Heat Exchanger

EEV Filter

Th2

Th3 Sirocco Fan

Th1

Indoor Units

:Cooling :Heating

Filter

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

5 _ Ceiling Concealed Duct_Built in


5. Wiring Diagrams B3/B4 Chassis

CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-D/PUMP CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-ZONE CN-DISPLAY CN-CC

SPEC.

DESCRIPTION

Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Drain pump output Option PWB. Communication Drain pump output AC power supply Zone Controller RF Remote controller Dry contact

Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV control output AC output for drain pump Communication between main and option Communication between indoor and outdoor AC output for drain pump AC power line input for indoor controller Zone control line RF remote control line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Concealed Duct_Built in _ 6

Indoor Units

CONNECTOR NUMBER


6. Capacity Tables 6.1 Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5

2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 1.9 1.9 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.6 2.5 2.5

3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.3

Outdoor air temp. (DB, °C)

2.2 Indoor Units

Capacity Index

2.8

3.6

Cooling capacity

Notes: TC: Total Capacity(kW)

7 _ Ceiling Concealed Duct_Built in

SHC: Sensible Heat Capacity(kW)

30 22 TC SHC kW kW

32 24 TC SHC kW kW


6. Capacity Tables Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, °C)

4.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8

3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.9 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.0

6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 5.2 5.1 5.0 4.9 4.8 4.7

7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5 3.5 3.4 5.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5 4.4 4.4

7.1

Notes: TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct_Built in _ 8

Indoor Units

5.6

32 24 TC SHC kW kW


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating capacity Indoor air temp. (DB, °C)

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

9 _ Ceiling Concealed Duct_Built in


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

4.5

7.1

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct_Built in _ 10

Indoor Units

5.6

Indoor air temp. (DB, °C)


7. External Static Pressure (E.S.P) & Air Flow ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Indoor Units

Setting Value

(Unit: CMM)

Static Pressure(mmAq(Pa)) 0(0)

1(10)

2(20)

3(29)

4(39)

60

6.29

3.03

0.93

-

-

65

6.61

4.84

1.52

-

-

70

7.69

5.64

2.18

0.79

-

75

8.19

6.28

2.81

0.85

-

80

8.91

7.43

4.96

1.58

-

85

9.51

8.14

5.91

2.75

0.95

90

10.21

8.76

6.79

3.41

1.36

95

10.83

9.62

8.11

5.48

2.61

100

11.31

10.55

9.02

6.12

3.31

105

11.84

11.19

9.99

8.28

5.32

110

12.68

11.88

10.38

9.16

6.92

115

13.19

12.22

11.55

10.21

8.23

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) Setting Value

(Unit: CMM)

Static Pressure(mmAq(Pa)) 0(0)

1(10)

2(20)

3(29)

4(39)

75

10.32

7.68

3.55

-

-

80

11.06

8.77

4.71

1.38

-

85

11.84

10.02

6.95

2.16

-

90

12.73

10.74

8.26

4.73

1.25

95

13.47

12.13

9.93

6.74

2.73

100

14.16

13.25

10.51

8.41

3.65

105

15.29

14.11

12.31

9.83

6.21

110

16.09

14.77

13.49

10.39

8.32

115

16.91

15.88

14.48

12.77

9.92

120

17.81

16.88

15.15

13.98

10.85

125

18.55

17.84

16.12

15.13

12.97

130

19.01

18.55

17.33

16.28

14.59

Note : 1. The above table shows the correlation between the air rates and E.S.P. 2. E.S.P. is given after subtracting coil losses motor step factory installed 3. E.S.P. can be higher than the maximum given in the table, but the unit faces the problem of freezing the coil.

11 _ Ceiling Concealed Duct_Built in


7. External Static Pressure (E.S.P) & Air Flow ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) Capacity

7k

High (factory set) Standard

9k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set)

High (factory set) 12k Standard High (factory set) 15k Standard

94 88 83 74 62 56 99 89 85 82 66 58 105 94 88 90 74 62 110 105 94 96 90 74

2(20) 0(0) 2(20) 0(0) 2(20) 0(0) 2(20) 0(0)

8 6.5 5.5 8 6.5 5.5 9 7 6 9 7 6 10 8 6.5 10 8 6.5 11 10 8 11 10 8

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39))

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) Capacity

18k

High (factory set) Standard

24k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low

115 103 93 100 86 74 128 118 93 116 104 74

2(20) 0(0) 2(20) 0(0)

CMM 14 12 10 14 12 10 17 15 10 17 15 10

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)

Ceiling Concealed Duct_Built in _ 12

Indoor Units

Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

CMM


8. Electric Characteristics

Indoor Units

Units

Power Supply

Input(W)

MFA

kW

FLA

0.22

15

0.028

0.17

30

30

0.22

15

0.028

0.17

30

30

Max:264

0.22

15

0.028

0.17

30

30

Min:198

0.22

15

0.028

0.17

30

30

B4

0.55

15

0.076

0.44

80

80

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

B4

0.55

15

0.076

0.44

80

80

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

0.22

15

0.028

0.17

30

30

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

0.22

15

0.028

0.17

30

30

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

Max:242

0.22

15

0.028

0.17

30

30

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

Min:198

0.22

15

0.028

0.17

30

30

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

B4

0.55

15

0.076

0.44

80

80

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

B4

0.55

15

0.076

0.44

80

80

Model

Type

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Hz

50

60

Volts Voltage Range MCA

IFM

220-240

220

Cooling Heating

Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFA : Indoor Fan Motor Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.

13 _ Ceiling Concealed Duct_Built in


9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operation condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1.5m

Ceiling 2.0m Microphone

Sound Levels dB(A) Model Name

M 32 33 34 40 40 43

L 29 32 33 37 37 37

Sound Pressure Level ARNU09GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y) 80

70

70

70

NC-65 60 NC-60 NC-55 NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-50

NC-40

125

250

500

1000

2000

4000

NC-35

30

NC-30 NC-25 Approximate Hearing Threshold

NC-15

63

NC-45

40

NC-20

10

NC-55

50

20

NC-25 Approximate Hearing Threshold

NC-60

NC-15 63

8000

70

70

NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20µPa )

80

40

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

250

500

1000

2000

4000

8000

NC-45 NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold

NC-20 NC-15

10 63

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

ARNU24GB4G2+ PBSGB40(Acc'y), PBSC40(Acc'y) 80

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-65 60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-25

20

NC-25

20

NC-20

125

NC-50

40

ARNU18GB4G2+ PBSGB40(Acc'y), PBSC40(Acc'y)

80

50

125

NC-55

50

Octave Band Center Frequency (Hz)

ARNU15GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y)

60

NC-60

NC-20

10

Octave Band Center Frequency (Hz)

NC-65 60

Octave Band Sound Pressure Level (dB re 20µPa )

50

NC-65 60

Octave Band Sound Pressure Level (dB re 20µPa )

80

20

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU12GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y)

80

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU07GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y)

10

Approximate Hearing Threshold 63

Approximate Hearing Threshold

NC-20

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

NC-15 8000

NC-20 NC-15

10 63

125

250

500

1000 2000

4000

8000

Octave Band Center Frequency (Hz)

Ceiling Concealed Duct_Built in _ 14

Indoor Units

H 33 34 35 41 43 46

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Suction Grille TEMP

Remote Controller

Indoor Units

Suction Grille + Suction Canvas

TEMP

Remote Controller

Required Parts

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose (Inner Dia ....................................25mm)

• Level • Screw driver • Electric drill • Hole core drill (ø70mm) • Flaring Tools set • Torque Wrenches • Hexagonal Wrench (4mm, 5mm) • Gas-leak detector • Ownerʼs Manual • Thermometer

15 _ Ceiling Concealed Duct_Built in


10. Installation 10.1 Selection of the best location Install the air conditioner in the location that satisfies the following conditions.

Top view (unit:mm) Airflow

• The place shall easily bear a load exceeding four times the indoor unitʼs weight.

Inspection hole (600 x 600)

• The place shall be able to inspect the unit as the figure.

Control box

• The place where the unit shall be leveled. • The place shall easily connect with the outdoor unit. 600

• The place where the unit is not affected by an electrical noise.

600

• There should not be any heat source or steam near the unit

Indoor Units

Confirm the positional relationship between the unit and suspension bolts.

270 or more

• The place where air circulation in the room will be good .

(Unit : mm) Chassis

A

B

B3

600

900

B4

600

1100

520 or more

• Installation the ceiling opening to clean the filter or service under the product.

• Refer to Suction grille and Suction canvas installation manual for detail installation of Built-in duct type

A(Min)

B3/B4 Series : Built-in Duct type

B(Min)

Ceiling Service Space

A

B

Ceiling Concealed Duct_Built in _ 16


10. Installation 10.2 Ceiling dimension and hanging bolt location Installation of Unit B A J

Install the unit above the ceiling correctly.

CASE 1

C D

POSITION OF SUSPENSION BOLT

E

• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. G

• Apply a filter Accessory at air return hole. (Unit:mm)

Indoor Units

I F

Dimension

A

D

E

F

850 900 383 575 1130 1180 383 575

93 93

190 190

Chassis

B3 B4

B

C

G

H

I

J

H 21 795 163 820 21 1065 163 1100

Drainage hole

Drain Pump use

M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

CASE 2 • Install the unit leaning to a drainage hole side as a figure for easy water drainage.

POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

17 _ Ceiling Concealed Duct_Built in


10. Installation • Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling.

• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

Old building

New building

1 Set anchor 2 Plate washer 3 Spring washer 4 Nut

Indoor Units

CAUTION

5 Suspension bolts

Tighten the nut and bolt to prevent unit falling.

10.3 Connecting Cables Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

SODU A

IDU B

IDU A

INT B

INT A

IDU

INTERNET DRY1 DRY2 GND 12V

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

-

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING Make sure that the screws of the terminal are not from loose.

Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.

Ceiling Concealed Duct_Built in _ 18


10. Installation 10.4 Part name and functions Air outlet

Air outlet

Suction Grille Suction Grille Suction Canvas

Indoor Units

• Buit-in duct type with Suction Grille

• Buit-in duct type with Suction Grille and Suction Canvas

■ B3/B4 Series : Built-in Duct type Control Box service

19 _ Ceiling Concealed Duct_Built in


10. Installation INSULATION, OTHERS THERMAL INSULATION

Insulate the joint and tubes completely.

All thermal insulation must comply with local requirement.

INDOOR UNIT Union for gas pipe

Refrigerant pipe and thermal insulator(Local supply)

Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply)

Hose clip for thermal insulator (Local supply) Overlap with thermal insulator for piping. Hose clip for thermal insulator(Local supply) Make sure that there is no clearance here.

Thermal insulator for refrigerant pipe (Local supply) Union for liquid pipe

Felt

Cabinet

Rubber

No clearance

TEST AND CHECK

■ After all workings are finished, check the working and operation. • Air distribution ............... Is the air circulation good? • Drain ............................. Is the drainage smoothly and no sweating? • Gas leakage ................. Is the piping connection correctly? • Wiring ........................... Is the wiring connection correctly? • Lock-bolt ....................... Is the lock-bolt of compressor loosened? • Insulation Is the unit fully insulated? • Ground Is the unit safely grounded?

10.5 Checking the Drainage 1. Remove the Air Filter.

2. Check the drainage. • Spray one or two glasses of water upon the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.

Ceiling Concealed Duct_Built in _ 20

Indoor Units

Insulation


10. Installation CAUTION 1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 19mm.

Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation.

Ceiling

Indoor Units

Drainage hole

Drain Pump use

10.6 Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.

Pipe clamp Indoor unit

Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings

Upward routing not allowed

Maintenance drain port

• Be sure to install heat insulation on the drain piping. Heat insulation material: Polyethylene foam with thickness more than 8 mm.

1/50~1/100 MAX 700mm

Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip

Drain pan

21 _ Ceiling Concealed Duct_Built in

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.


10. Installation Max 300mm

Hanger distance 1~15m

Metal clamp Flexible drain hose

Hanger Bracket 1/50~1/100 slope Max 700mm

CAUTION : The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.

Insulation

CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit.

4) Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal function of an overload protection device. • Proper starting power is not given to the compressor.

HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)

Ceiling Concealed Duct_Built in _ 22

Indoor Units

3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out Flexible drain hose of the wires.)


10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:

Indoor Units

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Remote Controller

5feet (1.5meters)

TEMP

Controller Remote

no

no

Fig.1 Typical locations for remote controller

23 _ Ceiling Concealed Duct_Built in


11. Accessories Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

4 EA

1 SET

(Other)

• Owner's manual • Installation manual Shape

for gas pipe

for liquid pipe

Indoor Units

CAUTION • Use only those accessories (Standard or optional) which have designated specilications.

Ceiling Concealed Duct_Built in _ 24


Indoor unit Wall Mounted 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GSE*2, ARNU09GSE*2, ARNU12GSE*2 ARNU15GSE*2, ARNU18GS5*2, ARNU24GS5*2 1 SE Manual / S5 Auto Auto SE Manual / S5 Auto X 3/4/3 O O O X Option O O O O O(Heat recovery) O O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Wall Mounted _ 1

Indoor Units

Installation

Function


2. Specifications * Model Name A:Basic L:Plasma Type Model Cooling Capacity

Heating Capacity Dimensions(WxDxH) Body

Indoor Units

Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color

Ø, V, Hz mm2 mm2

Wall Mounted ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 895 x 165 x 282 895 x 165 x 282 895 x 165 x 282 35.2 x 6.5 x 11.1 35.2 x 6.5 x 11.1 35.2 x 6.5 x 11.1 2 x 15 x 18 2 x 15 x 18 2 x 15 x 18 0.21 0.21 0.21 Cross Flow Fan Cross Flow Fan Cross Flow Fan 20 20 20 0.2 0.2 0.2 5.6 / 5.0 / 4.6 7.0 / 6.5 / 6.0 9.5 / 9.0 / 8.5 198.0 / 177.0 / 162.5 247.0 / 230.0 / 212.0 336.0 / 318.0 / 300.0 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Resin Net(washable) Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 16(5/8) 16(5/8) 16(5/8) 9(19.8) 9(19.8) 9(19.8) 37 / 33 / 23 39 / 35 / 25 41 / 36 / 27 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog Morning fog

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Wall Mounted

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications * Model Name A:Basic L:Plasma Type Model Cooling Capacity

Heating Capacity Dimensions(WxDxH) Body Coil

m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color

Ø, V, Hz mm2 mm2

Wall Mounted ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2 4.5 5.6 7.1 3,900 4,800 6,100 15,400 19,100 24,200 5.0 6.3 8.0 4,300 5,400 6,900 17,100 21,500 27,300 895 x 165 x 282 1,090 x 178 x 300 1,090 x 178 x 300 35.2 x 6.5 x 11.1 42.9 x 7 x 11.8 42.9 x 7 x 11.8 2 x 15 x 18 2 x 15 x 20 2 x 15 x 20 0.21 0.26 0.26 Cross Flow Fan Cross Flow Fan Cross Flow Fan 20 20 20 0.2 0.2 0.2 10.5 / 9.0 / 8.5 12.0 / 10.5 / 9.0 14.0 / 13.0 / 10.0 371.0 / 318.0 / 300.0 424.0 / 371.0 / 318.0 494.0 / 459.0 / 353.0 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Resin Net(washable) Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) 16(5/8) 16(5/8) 16(5/8) 9(19.8) 12(26.5) 12(26.5) 42 / 36 / 27 44 / 40 / 36 46 / 41 / 38 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog Morning fog

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Wall Mounted _ 3

Indoor Units

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch


PIPING/WIRING DIRECTION

4 _ Wall Mounted PIPE AND DRAIN DIMENSION

567

PIPING DIRECTION

PIPING/WIRING DIRECTION

Front panel Air discharge Air suction Liquid pipe Gas pipe Drain pipe Right side piping/wiring connection Left side piping/wiring connection

1 2 3 4 5 6 7 8

Descripition

(unit : mm)

165

Ø6.35 Flare connection Ø12.7 Flare connection External dia. Ø17

282

D

(unit : mm)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

Higher than eye-level

More than 100 mm

※ Required space(unit:mm)

CHASSIS CODE: SE

More than 100 mm

Lower than 2.3m More than 200 mm

Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

Name

895

H

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2

Wall Mounted

Number

W

Model ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2

Indoor Units

3. Dimensions

265


Wall Mounted _ 5

PIPING/WIRING DIRECTION

PIPE AND DRAIN DIMENSION

804

PIPING DIRECTION

PIPING/WIRING DIRECTION

Front panel Air discharge Air suction Liquid pipe Gas pipe Drain pipe Right side piping/wiring connection Left side piping/wiring connection

1 2 3 4 5 6 7 8

Descripition

(unit : mm)

178

Ø6.35 Flare connection Ø12.7 Flare connection External dia. Ø17

300

D

(unit : mm)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

Higher than eye-level

More than 100 mm

※ Required space(unit:mm)

CHASSIS CODE: S5

More than 100 mm

Lower than 2.3m More than 200 mm

Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

Name

1090

ARNU18GS5*2 ARNU24GS5*2

H

ARNU18GS5*2 ARNU24GS5*2

Number

W

Model

Indoor Units

281

Wall Mounted

3. Dimensions


4. Piping Diagrams

Heat Exchanger

EEV Filter

Th3

Th2

C.F.F

Th1

Indoor Units

:Cooling :Heating

Filter

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GS5*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GS5*2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

6 _ Wall Mounted


5. Wiring Diagrams SE Chassis

Indoor Units

S5 Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-COM CN-DISP1 CN-DISP2 CN-EEV CN-U/D, CN-L/R CN-TH1 CN-REMO CN-CC CN-HVB

LOCATION POINT AC Power supply Fan motor output Communication Display Display EEV output Step motor Room/pipe sensor Remote controller Dry contact Air clean

FUNCTION AC Power line input for indoor controller Motor output of BLDC Connection between indoor and outdoor Display of indoor status Display of indoor status EEV control output Step motor output Room and pipe thermistor Remote control line Dry contact line Air clean control

Wall Mounted _ 7


6. Capacity Tables 6.1 Cooling Capacity

Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5 1.5 1.5 1.5

2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.9 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.5 2.5 2.4

3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2

Indoor Units

Capacity Index

Outdoor air temp. (DB, °C)

2.8

3.6

Notes: TC: Total Capacity(kW)

8 _ Wall Mounted

SHC: Sensible Heat Capacity(kW)

32 24 TC SHC kW kW


6. Capacity Tables Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8

3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.9 2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 5.0

6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.8 3.8 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4 5.3 5.2 5.1 5.1 5.0 4.9 4.8

7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

4.3 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 5.4 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9 4.8 4.7 4.6 4.6 4.5 4.4

Capacity Index

Outdoor air temp. (DB, °C)

4.5

7.1

Notes: TC: Total Capacity(kW)

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Wall Mounted _ 9

Indoor Units

5.6

30 22 TC SHC kW kW


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating Capacity Indoor air temp. (DB, °C)

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

10 _ Wall Mounted


6. Capacity Tables Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

4.5

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

Wall Mounted _ 11

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


7. Air Velocity and Temperature Distribution(Reference Data) ARNU07GSE*2 Cooling

Heating Discharge angle:50°

Discharge angle:45° Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m

2m

2m 2.0 1.5

0.5

1.5

1.0

1m

1m

1.0 0.5

5m

4m

3m

2m

0m 0m

1m

Temperature [°C]

5m

4m

3m

2m

0m 0m

1m

Temperature [°C]

Indoor Units

2.7m

2.7m

2m

2m 21

24

18 20

33 30

1m

1m

27 22

24

5m

4m

3m

2m

0m 0m

1m

5m

4m

3m

2m

0m 0m

1m

ARNU09GSE*2 Cooling

Heating Discharge angle:50°

Discharge angle:45°

Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m

2m

2m 2.0 1.5

1.5

1m

1m

1.0 0.5

1.0 0.5

5m

4m

3m

2m

0m 0m

1m

Temperature [°C]

5m

4m

3m

2m

0m 0m

1m

Temperature [°C] 2.7m

2.7m

2m

2m 33

18 21 20

24

30

1m

1m

27 22

24

5m

4m

3m

12 _ Wall Mounted

2m

1m

0m 0m

5m

4m

3m

2m

1m

0m 0m


7. Air Velocity and Temperature Distribution(Reference Data) ARNU12GSE*2 Cooling

Heating Discharge angle:50°

Discharge angle:45°

Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m

2m

2m

2.0

2.0

1m

1m 1.5 0.5

5m

4m

3m

2m

1.0

1.0

0.5

0m 0m

1m

5m

4m

1.5

3m

2m

0m 0m

1m

Temperature [°C]

Temperature [°C]

2.7m

2.7m

Indoor Units

2m

2m 33

18

21 30

1m

20

1m

27 24

5m

4m

24

22

3m

2m

0m 0m

1m

5m

4m

3m

2m

0m 0m

1m

ARNU18GS5*2 Cooling

Heating Discharge angle:50°

Discharge angle:45°

Air velocity [m/s]

Air velocity [m/s]

2.5 0.5

8m

7m

6m

5m

4m

3m

2.7m

2.7m

2m

2m

1m

1.5

1.0

2m

1.0

0.5

0m 0m

1m

1m

2.0

8m

7m

6m

5m

4m

3m

2m

1.5

0m 0m

1m

Temperature [°C]

Temperature [°C]

2.7m

2.7m

2m

2m 33

18 20

7m

6m

5m

4m

30

21

3m

2m

1m

0m 0m

8m

7m

6m

5m

4m

3m

1m

27

24

22

24

8m

1m

2m

1m

0m 0m

Wall Mounted _ 13


8. Electric Characteristics

Indoor Units

Units

Power Supply

Input(W)

MFA

kW

FLA

0.29

15

0.02

0.23

40

40

0.29

15

0.02

0.23

40

40

Max:264

0.29

15

0.02

0.23

40

40

Min:198

0.29

15

0.02

0.23

40

40

S5

0.29

15

0.02

0.23

40

40

ARNU24GS5*2

S5

0.29

15

0.02

0.23

40

40

ARNU07GSE*2

SE

0.29

15

0.02

0.23

40

40

ARNU09GSE*2

SE

0.29

15

0.02

0.23

40

40

ARNU12GSE*2

SE

Max:242

0.29

15

0.02

0.23

40

40

ARNU15GSE*2

SE

Min:198

0.29

15

0.02

0.23

40

40

ARNU18GS5*2

S5

0.29

15

0.02

0.23

40

40

ARNU24GS5*2

S5

0.29

15

0.02

0.23

40

40

Model

Type

ARNU07GSE*2

SE

ARNU09GSE*2

SE

ARNU12GSE*2

SE

ARNU15GSE*2

SE

ARNU18GS5*2

Hz

50

60

Volts

220 - 240

220

Voltage Range MCA

IFM

Cooling Heating

Symbols: MCA :Min, Circuit Amps(A) MFA:Max. Fuse Amps(see note 5) kW:Fan Motor Rated Output(kW) FLA:Full Load Amps(A) IFM:Indoor Fan Motor Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.

14 _ Wall Mounted


9. Sound Levels Overall Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1m 1m Microphone Sound Levels dB(A)

Model ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2

M 33 35 36 36 40 41

L 23 25 27 27 36 38

Indoor Units

H 37 39 41 42 44 46

Sound Pressure Level

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

10

Approximate Hearing Threshold 63

NC-60

250

500

1000

2000

4000

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

125

NC-65

60

NC-15 8000

10

NC-25 Approximate Hearing Threshold 63

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20μPa )

80

20

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-15 8000

NC-60

NC-50

NC-40

NC-30 20

10

ARNU18GS5*2

NC-55 NC-50 NC-45 NC-40 NC-35 NC-30

10

NC-25 Approximate Hearing Threshold 63

NC-65 60 NC-60 50

NC-50

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold

NC-20 NC-15 8000

NC-55

10 63

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20μPa )

NC-60

Octave Band Sound Pressure Level (dB re 20μPa )

70

NC-65

NC-20

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-15 8000

ARNU24GS5*2

70

20

NC-25 Approximate Hearing Threshold 63

70

30

NC-35

30

80

40

NC-45

40

80

50

NC-55

50

80

60

NC-65

60

NC-20

ARNU15GSE*2

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU12GSE*2

ARNU09GSE*2 80

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU07GSE*2 80

NC-65 60 NC-60

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold

NC-20 NC-15 8000

NC-55

50

NC-20 NC-15

10 63

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

8000

Wall Mounted _ 15


10. Installation • Please read the instruction sheetss completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Installation Parts Provided

1. Type "A" screw

Indoor Units

2. Installation Plate

Required Parts

Required Tools

❏ Installation plate ❏ Four type "A" screws ❏ Connecting cable

❏ Level gauge ❏ Screw driver ❏ Electric drill ❏ Hole core drill

❏ Pipes: Gas side Liquid side ❏ Insulation materials ❏ Additional drain pipe

❏ Flaring tool set ❏ Specified torque wrenches ❏ Spanner......................................................Half union ❏ A glass of water ❏ Screw driver ❏ Thermometer

16 _ Wall Mounted


10. Installation 10.1 Selection of the best location

Front

• There

should not be any heat source or steam near the unit.

• There should not be any obstacles to prevent air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.

Left Rear left Down right Right

Rear right

More than 100mm

More than 200mm

More than 2300mm

The mounting wall should be strong and solid enough to protect it from vibration.

S5 chassis

1.Mount the installation plate on the wall with four Type "A" screws. (If mounting the unit on the concrete wall, consider using anchor bolts.) • Always mount the Installation plate horizontally by aligning the marking-off line by means of thread and a level.

Installation Plate Chassis Hook

Type “A”

SE chassis Installation Plate

Chassis Hook

Type “A”

Wall Mounted _ 17

Indoor Units

More than 100mm


10. Installation Preparing work for installation ■ Preparing the indoor unit's piping and drain hose for installation through the wall. ■ Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis. ■ Replace the plastic tubing holder in the original position.

3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

Loop

Indoor Units

Tubing holder To remove the holder, press the bottom of chassis near the holder upward and pull the tab out of its hole.

Connecting cable Drain hose

Gas side piping Liquid side piping

2 Pull 1 Press

CAUTION While installing, make sure that the remaining parts must be removed clearly so as not to damage the piping and drain hose, especially power cord and connecting cable.

For left rear piping 1. Route the indoor tubing and the drain hose in the direction of rear left.

NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended. 4. Indoor unit installation ■ Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Connecting cable

Drain hose

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound). Drain hose

2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole. ■ Do not connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.

5. Connecting the pipings to the indoor unit and drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.

Indoor unit tubing

18 _ Wall Mounted

Flare nut

Pipings


10. Installation ■ Tighten the flare nut with a wrench. Spanner (fixed) Flare nut Connection pipe

Torque wrench

■ Wrap the area which accommodates the rear piping housing section with vinyl tape. Indoor unit pipe Wrap with vinyl tape

Connection pipe Vinyl tape (wide)

Connecting cable

Indoor unit tubing

Pipe

■ When extending the drain hose at the indoor unit, install the drain pipe.

Drain pipe

Vinyl tape(narrow)

■ Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section. Wrap with vinyl tape

Pipe

Adhesive

Vinyl tape(wide) Drain hose

6. Wrap the insulation material around the connecting portion. ■ Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.

Plastic bands

For right rear piping 1. Route the indoor tubing and the drain hose to the required piping hole position.

Insulation material

2. Insert the piping, drain hose and the connecting cable into the piping hole. Connecting cable

Drain pipe

Wall Mounted _ 19

Indoor Units

Indoor unit drain hose Vinyl tape(narrow)


10. Installation 3. Insert the connecting cable into the indoor unit. ■ Don't connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.

■ When extending the drain hose at the indoor unit, install the drain pipe.

Drain hose

4. Tape the drain hose and the connecting cable. • Connecting cable

Indoor unit drain hose Vinyl tape(narrow) Adhesive

Indoor Units

7. Wrap the insulation material around the connecting portion. ■ Overlap the connecting pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap. 5. Indoor unit installation ■ Hang the indoor unit from the hooks at the top of the installation plate. ■ Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall. Indoor unit Spacer

6. Connecting the pipings to the indoor unit and the drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.

Flare nut

Pipings

■ Tighten the flare nut with a wrench.

Spanner (fixed)

Indoor unit tubing

20 _ Wall Mounted

■ Wrap the area which accommodates the rear piping housing section with vinyl tape.

Vinyl tape (wide)

80mm (2-3/16 inch)

Torque wrench

Insulation material

Connection pipe

Installation plate

Indoor unit tubing

Plastic bands

Flare nut Connection pipe

Indoor unit piping Wrap with vinyl tape Pipe

Connecting cable

Vinyl tape (narrow)


10. Installation ■ Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.

10. Indoor unit installation ■ Remove the spacer. ■ Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Pipe Drain hose

Vinyl tape (narrow)

Connecting

Wrap with vinyl tape(wide)

8. Reroute the pipings and the drain hose across the back of the chassis.

Drain hose

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

Indoor Units

Piping for passage through piping hole

9. Set the pipings and the drain hose to the back of the chassis with the tubing holder. ■ Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.

Tubing holder 1 Hook

2 Push

Wall Mounted _ 21


10. Installation 10.2 Connection of Pipings

Indoor Units

1. To remove the front panel from the indoor unit, remove the front panel from the indoor unit cabinet. ■ Set the air direction louvers up-and-down to the position(horizontally) by hand. ■ Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off. (2.1/7, 2.6/9, 3.5/12 kW/Btu models: 2EA, 3.5/18 kW/Btu models: 3EA)

2. To check the drainage. ■ Pour a glass of water on the evaporator. ■ Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

Pull the right and the left side.

Screw

10.3 Connect the cable to the indoor unit 1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

Remote control co cord

Connecting cable

22 _ Wall Mounted


10. Installation [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

SODU A

IDU B

IDU A

INT B

INT A

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

Indoor Units

2. Attach the Grille onto the cabinet. • Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis. • Press the Grille toward the chassis until it is back in place.

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Confirm the specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between the cable length and thickness.) 7) In a wet or moist area, always install an earth leakage circuit breaker. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.

Wall Mounted _ 23


10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:

Indoor Units

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

24 _ Wall Mounted


11. Accessories Standard Accessories Name

Installation panel

Type "A" screw

Quantity

1 set

SE: 6 EA S5: 8 EA

(Other) • Owner's manual • Installation manual

SE

Shape S5

Indoor Units

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Wall Mounted _ 25


Indoor unit ART COOL Mirror 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GSE*2, ARNU09GSE*2, ARNU12GSE*2 ARNU15GSE*2, ARNU18GS8*2, ARNU24GS8*2 1 Auto Auto Auto X 3/4/3 O O O X Option O O O O O(Heat recovery) O O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

ART COOL Mirror _ 1

Indoor Units

Installation

Function


2. Specifications

Indoor Units

Type Model

ART COOL Mirror ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 2.2 2.8 3.6 Cooling Capacity 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 Heating Capacity 2,200 2,800 3,400 8,500 10,900 13,600 915 x 169 x 282 915 x 169 x 282 915 x 169 x 282 Dimensions(WxDxH) Body 36.0 x 6.5 x 11.1 36.0 x 6.5 x 11.1 36.0 x 6.5 x 11.1 Rows x Columns x FPI 2 x 15 x 18 2 x 15 x 18 2 x 15 x 18 Coil Face Area m3 0.21 0.21 0.21 Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Motor Output x Number W 20 20 20 Running Current A 0.2 0.2 0.2 Fan Air Flow Rate(H / M / L) CMM 7.0 / 6.0 / 4.0 8.0 / 7.0 / 5.0 10.0 / 8.0 / 6.0 cfm 247 / 212 / 141 282 / 247 / 177 353 / 283 / 212 Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Resin Net(washable) Resin Net(washable) Resin Net(washable) Safety Device Fuse Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Drain Pipe(Internal Dia.) mm(inch) 16(5/8) 16(5/8) 16(5/8) Net Weight kg(lbs) 11.2(24.7) 11.2(24.7) 11.2(24.7) Noise Level(Sound Press, 1m, H / M / L) dB(A) 37 / 33 / 23 39 / 35 / 25 41 / 36 / 27 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Front Panel('*' Position) R:Mirror V:Silver B:Blue Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ ART COOL Mirror

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications Type Model

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

ARNU24GS8*2 7.1 6,100 24,200 8.0 6,900 27,300 1,107 x 200 x 299 43.9 x 7.9 x 11.8 2 x 15 x 20 0.26 Cross Flow Fan 20 0.2 17.9 / 14.4 / 12.0 632 / 508 / 424 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø9.52(3/8) Ø15.88(5/8) 16(5/8) 15(33.1) 43 / 37 / 32 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

ART COOL Mirror _ 3

Indoor Units

ART COOL Mirror ARNU15GSE*2 ARNU18GS8*2 4.5 5.6 Cooling Capacity 3,900 4,800 15,400 19,100 5.0 6.3 Heating Capacity 4,300 5,400 17,100 21,500 915 x 169 x 282 1,107 x 200 x 299 Dimensions(WxDxH) Body 36.0 x 6.5 x 11.1 43.9 x 7.9 x 11.8 Rows x Columns x FPI 2 x 15 x 18 2 x 15 x 20 Coil Face Area m3 0.21 0.26 Type Cross Flow Fan Cross Flow Fan Motor Output x Number W 20 20 Running Current A 0.2 0.2 Fan Air Flow Rate(H / M / L) CMM 10.5 / 8.0 / 6.0 14.4 / 13.0 / 11.0 cfm 371 / 283 / 212 508 / 459 / 388 Drive Direct Direct Motor type BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Air Filter Resin Net(washable) Resin Net(washable) Safety Device Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Drain Pipe(Internal Dia.) mm(inch) 16(5/8) 16(5/8) Net Weight kg(lbs) 11.2(24.7) 15(33.1) Noise Level(Sound Press, 1m, H / M / L) dB(A) 42 / 36 / 27 37 / 34 / 31 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Front Panel('*' Position) R:Mirror V:Silver B:Blue Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch


165

282

4 _ ART COOL Mirror 567

915

H

W

169

1

51

2

282

D

Air suction grill

282

H

Descripition

(unit : mm)

169

D

(unit : mm)

CHASSIS CODE: SE

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

2

Name Air discharge grill

1

915

W

Number

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2

Model

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2

ART COOL Mirror

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

53

Indoor Units

3. Dimensions

265


ART COOL Mirror _ 5

804

1107

1

72 58 122

2

281

93

299

3

200

53

4

Air suction grille Knockout hole Installation plate

4 5

(unit : mm) Remark

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: S8

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

ARNU18GS8*2 ARNU24GS8*2

Display & signal receiver

Front panel

Part Name

3

2

1

No.

Indoor Units

10 63

48

ART COOL Mirror

3. Dimensions


4. Piping Diagrams

Heat Exchanger

:Cooling :Heating

EEV Filter Th2

Th3

C.F.F

Indoor Units

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GSE*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GS8*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GS8*2

Ø15.88(5/8)

Ø9.52(3/8)

*Panel Color (SE/S8 chassis) : R(Mirror),V(Silver), B(Blue)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

6 _ ART COOL Mirror

PCB Connector CN-TH1 CN-TH2


5. Wiring Diagrams SE/S8 Chassis

Indoor Units

CONNECTOR NUMBER

LOCATION POINT

FUNCTION

CN-MOTOR1

Fan motor output

Motor output of BLDC

CN-COM

Communication

Communication between indoor and outdoor

CN-EEV

EEV output

EEV control output

CN-L/R

Step motor

Step motor output for left/right

CN-U/D

Step motor

Step motor output

CN-TH1

Room/pipe sensor

Room & pipe thermistor

CN-TH2

Discharge pipe sensor

Discharge pipe thermistor

CN-SUC

Step motor(front)

Front panel step motor

CN-HVB

Air purifier

Air purifier output

CN-VFD

Display

Display of indoor status

CN-12V

Safety connection

Safety of indoor status

CN-REMO

Remote controller

Remote control line

CN-CC

Dry contact

Dry contact line

CN-HVB

Air clean

Air clean control

ART COOL Mirror _ 7


6. Capacity Tables 6.1 Cooling Capacity

Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5 1.5 1.5 1.5

2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.9

3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0

2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.5 2.5 2.4

4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2

Outdoor air temp. (DB, °C)

Indoor Units

Capacity Index

Notes: TC: Total Capacity(kW)

8 _ ART COOL Mirror

SHC: Sensible Heat Capacity(kW)

30 22 TC SHC kW kW

32 24 TC SHC kW kW


6. Capacity Tables Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, °C)

4.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8

3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.9 2.8

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0

6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.8 3.8

7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0

4.3 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.3 5.2 5.1 5.0 4.9 4.8

9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5

SHC: Sensible Heat Capacity(kW)

ART COOL Mirror _ 9

Indoor Units

Notes: TC: Total Capacity(kW)

32 24 TC SHC kW kW


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating Capacity Indoor air temp. (DB, °C)

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

10 _ ART COOL Mirror


6. Capacity Tables Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

4.5

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

ART COOL Mirror _ 11

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


7. Air Velocity and Temperature Distribution ARNU07GSE*2 Cooling

Heating

Discharge angle:45°

Discharge angle:60° Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m

2m

2m

2.0

2.0

1.5

1m

1m 1.5 1.0

0.5

0.5

5m

4m

3m

2m

0m 0m

1m

5m

4m

1.0

3m

2m

0m 0m

1m

Temperature [°C]

Temperature [°C]

2.7m

Indoor Units

2.7m

2m

2m 33

18 30 20

1m

1m 24

22

21

24

5m

4m

3m

2m

1m

0m 0m

5m

4m

27

3m

2m

0m 0m

1m

ARNU12GSE*2 Cooling

Heating

Discharge angle:45°

Discharge angle:60° Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m

2m

2m 2.0

2.0 1.5

1m

1.5

0.5 0.5

5m

4m

3m

1m

1.0

1.0

2m

1m

0m 0m

5m

4m

3m

2m

0m 0m

1m

Temperature [°C]

Temperature [°C] 2.7m

2.7m

2m

2m 33

18

30

1m

21

1m 20 24

5m

4m

3m

24

27

22

2m

12 _ ART COOL Mirror

1m

0m 0m

5m

4m

3m

2m

1m

0m 0m


8. Electric Characteristics Units Model

Type

Power Supply Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

ARNU07GSE*2

SE

0.29

15

0.02

0.23

40

40

ARNU09GSE*2

SE

0.29

15

0.02

0.23

40

40

ARNU12GSE*2

SE

Max:264

0.29

15

0.02

0.23

40

40

ARNU15GSE*2

SE

Min:198

0.29

15

0.02

0.23

40

40

ARNU18GS8*2

S8

0.29

15

0.02

0.23

35

35

ARNU24GS8*2

S8

0.29

15

0.02

0.23

35

35

ARNU07GSE*2

SE

0.29

15

0.02

0.23

40

40

ARNU09GSE*2

SE

ARNU12GSE*2

SE

ARNU15GSE*2

SE

ARNU18GS8*2 ARNU24GS8*2

50

220 - 240

0.29

15

0.02

0.23

40

40

Max:242

0.29

15

0.02

0.23

40

40

Min:198

0.29

15

0.02

0.23

40

40

S8

0.29

15

0.02

0.23

35

35

S8

0.29

15

0.02

0.23

35

35

60

220

Indoor Units

Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA.

ART COOL Mirror _ 13


9. Sound Levels Overall Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1m 1m Microphone

Sound Levels dB(A) H 37 39 41 42 37 43

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 ARNU18GS8*2 ARNU24GS8*2

M 33 35 36 36 34 37

L 23 25 27 27 31 32

Sound Pressure Level ARNU07GSE*2

80

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

Approximate Hearing Threshold 63

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

NC-25

20

70

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

10

Octave Band Sound Pressure Level (dB re 20µPa )

NC-65

Octave Band Sound Pressure Level (dB re 20µPa )

Approximate Hearing Threshold 63

NC-60

NC-50

NC-40

NC-30

10

ARNU24GS8*2 70

NC-60 NC-55 NC-50 NC-45 NC-40 NC-35

Octave Band Sound Pressure Level (dB re 20µPa )

70

NC-65

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

14 _ ART COOL Mirror

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

ARNU18GS8*2

70

30

NC-25 Approximate Hearing Threshold 63

80

40

NC-35

30

80

50

NC-45

40

80

60

NC-55

50

20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

ARNU15GSE*2

NC-65

60

NC-20

Octave Band Sound Pressure Level (dB re 20µPa )

Octave Band Sound Pressure Level (dB re 20µPa )

ARNU12GSE*2 80

70

60

10

ARNU09GSE*2

80

70

Octave Band Sound Pressure Level (dB re 20µPa )

Indoor Units

Model

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

NC-25

20

10

Approximate Hearing Threshold 63

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Installation Parts Provided

1. Type "A" screw

2. Installation Plate

Indoor Units

Required Parts

Required Tools

❏ Installation plate ❏ Four type "A" screws ❏ Connecting cable

❏ Level gauge ❏ Screw driver ❏ Electric drill ❏ Hole core drill

❏ Pipes: Gas side Liquid side ❏ Insulation materials ❏ Additional drain pipe

❏ Flaring tool set ❏ Specified torque wrenches ❏ Spanner......................................................Half union ❏ A glass of water ❏ Screw driver ❏ Thermometer

ART COOL Mirror _ 15


10. Installation 10.1 Selection of the best location

More than 100mm

• There should not be any heat source or steam near the

unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.

More than 100mm More than 2300mm

S8 chassis Installation Plate

Chassis Hook

The mounting wall should be strong and solid enough to protect it from the vibration. Mount the installation plate on the wall with four Type "A" screws. (If mounting the unit on the concrete wall, consider using anchor bolts.) • Always mount the Installation plate horizontally by aligning the marking-off line by means of the thread and a level.

Type “A”

SE chassis Installation Plate

Chassis Hook

Type “A”

The lower left and the right side of Installation Plate S8 chassis

Ø70mm

Ø70mm

Installation plate 133mm

100mm

Installation plate

Ø70mm

Ø70mm

85mm

Left rear piping

Right rear piping

110mm

SE chassis

110mm

Indoor Units

More than 200mm

Left rear piping

65mm

Right rear piping

CAUTION : In case that the unit is installed near the sea, the installation parts may be corroded by salt. The installation parts (and the unit) should be taken appropriate anti-corrosion measures.

16 _ ART COOL Mirror


10. Installation Preparing work for installation ■ Preparing the indoor unit's piping and drain hose for installation through the wall. ■ Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis. ■ Replace the plastic tubing holder in the original position.

3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

Tape Connecting pipe Drain hose

Connecting cable

For right rear piping

*Foamed polyethylene or equivalent is recommended.

1. Route the indoor tubing and the drain hose in the direction of rear left.

Drain hose

4. Indoor unit installation ■ Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Connecting

Drain hose

2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole. ■ Do not connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

ART COOL Mirror _ 17

Indoor Units

NOTICE : If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.


10. Installation 5. Connecting the pipings to the indoor unit and drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.

■ Wrap the area which accommodates the rear piping housing section with vinyl tape. Indoor unit pipe Wrap with vinyl tape

Connection pipe Vinyl tape (wide)

Connecting cable

Indoor unit tubing

Flare nut

Pipings

Pipe Vinyl tape(narrow)

■ Tighten the flare nut with a wrench.

Indoor Units

Spanner (fixed) Flare nut Connection pipe

Torque wrench

■ Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section. Wrap with vinyl tape

Pipe

Indoor unit tubing

■ Mount the clamp on the boss with a type "B" screw.(optional)

Type "B" screw

Drain hose

Clamp

Vinyl tape(wide) Drain hose

For left rear piping

Boss

1. Route the indoor tubing and the drain hose to the required piping hole position. ■ When extending the drain hose at the indoor unit, install the drain pipe.

Drain pipe

Indoor unit drain hose Vinyl tape(narrow) Adhesive

6. Wrap the insulation material around the connecting portion. ■ Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap. Plastic bands

18 _ ART COOL Mirror

Insulation material

2. Insert the piping, drain hose and the connecting cable into the piping hole.

Connecting cable Drain pipe


10. Installation 3. Insert the connecting cable into the indoor unit. ■ Don't connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.

■ When extending the drain hose at the indoor unit, install the drain pipe.

Drain hose

4. Tape the drain hose and the connecting cable. • Connecting cable

Indoor unit drain hose Vinyl tape(narrow) Adhesive

7. Wrap the insulation material around the connecting portion. ■ Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap. Plastic bands

Insulation material

■ Wrap the area which accommodates the rear piping housing section with vinyl tape.

Indoor unit Spacer Installation plate

Connection pipe Vinyl tape (wide)

80mm

Indoor unit piping Wrap with vinyl tape Pipe

6. Connecting the pipings to the indoor unit and the drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.

Indoor unit tubing

Flare nut

Connecting cable

Vinyl tape (narrow)

Pipings

■ Tighten the flare nut with a wrench. Spanner (fixed)

Torque wrench

Flare nut Connection pipe

Indoor unit tubing

ART COOL Mirror _ 19

Indoor Units

5. Indoor unit installation ■ Hang the indoor unit from the hooks at the top of the installation plate. ■ Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.


10. Installation ■ Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.

9. Set the pipings and the drain hose to the back of the chassis with the tubing holder. ■ Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.

Pipe Drain hose

Vinyl tape (narrow)

Indoor Units

Wrap with vinyl tape(wide)

8. Reroute the pipings and the drain hose across the back of the chassis.

Tubing holder

10. Indoor unit installation ■ Remove the spacer. ■ Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Connecting

Piping for passage through piping hole

Drain hose

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

20 _ ART COOL Mirror


10. Installation 10.2 Connection of Pipings 1. To remove the front panel from the indoor unit, remove the front panel from the indoor unit cabinet. ■ Set the air direction louvers up-and-down to the position(horizontally) by hand. ■ Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.

2. To check the drainage. ■ Pour a glass of water on the evaporator. ■ Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. Connecting area drain hose

Leakage checking Drain pan

Leakage checking

Front panel

■ The drain hose should point downward for easy drain flow. Downward slope

■ Do not make drain piping. Accumulated drain water Air

Do not raise

Water leakage

Water leakage

Waving

Tip of drain hose dipped in water Water leakage

Less than 50mm gap

Ditch

10.3 Connect the cable to the indoor unit 1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

Remote control co cord

Connecting cable

ART COOL Mirror _ 21

Indoor Units

Drain hose


10. Installation [Multi V III Heat Pump Model] Terminal Block Indoor 1(L1) 2(L2)

3

SODU B

SODU A

IDU B

IDU A

INT B

INT A

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model] SODU

Terminal Block Indoor 1(L1) 2(L2)

3

4

B

A

IDU -

-

INTERNET DRY1 DRY2 GND 12V Outdoor unit B A -

Indoor Units

INDOOR POWER INPUT

2. Attach the Grille onto the cabinet. • Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis. • Press the Grille toward the chassis until it is back into its original place.

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness.) 7) Always install an earth leakage circuit breaker in a wet or moist area. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.

22 _ ART COOL Mirror


10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

Indoor Units

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

ART COOL Mirror _ 23


11. Accessories Standard Accessories Name

Installation panel

Type "A" screws and plastic anchors

Quantity

1 set

4 set

(Other)

SE

• Owner's manual • Installation manual S8

Indoor Units

Shape

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

24 _ ART COOL Mirror


Indoor unit ART COOL Gallery 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Electric Characteristics 8. Sound Levels 9. Installation 10. Accessories


1. List of functions Category

Air flow

Indoor Units

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GSF*2, ARNU09GSF*2, ARNU12GSF*2 3 X Auto X O 3/4/3 X O O X Option O O O O O(Heat recovery) O O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

1 _ ART COOL Gallery


2. Specifications Type Model Cooling Capacity

Heating Capacity Dimensions(WxDxH) Body Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch m3

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Front Panel('*' Position)

Ø, V, Hz mm2 mm2

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

• Panel color: E(Red), V(Silver), G(Gold) → Panel type 1: Kiss (Photo changeable) → Gallery type

ART COOL Gallery _ 2

Indoor Units

W A CMM cfm

ART COOL Gallery ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 600x146x600 600x146x600 600x146x600 23.6x5.7x23.6 23.6x5.7x23.6 23.6x5.7x23.6 2x20x21 2x20x21 2x20x21 0.18 0.18 0.18 Turbo Fan Turbo Fan Turbo Fan 30 30 30 0.16 0.16 0.16 8.1 / 6.3 / 4.2 8.1 / 6.3 / 4.2 9.3 / 7.7 / 6.0 286 / 222 / 148 286 / 222 / 148 328 / 272 / 212 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Resin Net(washable) Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 12.2(15/32) 12.2(15/32) 12.2(15/32) 15(33.1) 15(33.1) 15(33.1) 38 / 32 / 27 38 / 32 / 27 44 / 38 / 32 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C E:Red, V:Silver, G:Gold, 1: Kiss (Photo changeable)


1

3 _ ART COOL Gallery

Fix Hole

2

500

Pipe Hole

W

Hanger Hole

1

H

D

1

Air discharge grill Air suction grill

1 2

600

H

Descripition

(unit : mm)

146

D

(unit : mm)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: SF

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Name

600

W

ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2

ART COOL Gallery

Number

ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2

Model

Indoor Units

3. Dimensions

525


4. Piping Diagrams

Heat Exchanger Th3

EEV

Filter

:Cooling :Heating

Th2

Turbo Fan

Th1

Filter

lndoor unit

[Unit: mm(inch)]

Model

Gas

Liquid

ARNU07GSF*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GSF*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GSF*2

Ø12.7(1/2)

Ø6.35(1/4)

*Panel color :E(Red), V(Silver), G(Gold), 1(Kiss (Photo changeable)) LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

PCB Connector CN-TH1 CN-TH1

ART COOL Gallery _ 4

Indoor Units

Refrigerant pipe connection port diameter


5. Wiring Diagrams

Indoor Units

SF Chassis

CONNECTOR NUMBER CN-MOTOR1 CN-COM

LOCATION POINT Fan motor output Communication

FUNCTION Motor output of BLDC Communication between indoor and outdoor

CN-EEV CN-D1 CN-LR1

EEV output Display Step motor

EEV control output Display of indoor status Step motor output for left/right

CN-LR2 CN-UD CN-TH1

Step motor Step motor Room/pipe sensor

Step motor output for left/right Step motor output Room and pipe thermistor

CN-TH2 CN-REMO

Discharge pipe sensor Remote controller

Discharge pipe thermistor Remote control line

CN-CC CN-HVB

Dry contact Air clean

Dry contact line Air clean control

5 _ ART COOL Gallery


6. Capacity Tables 6.1 Cooling Capacity

Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, °C)

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5 1.5 1.5 1.5

2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.9

3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0

2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.5 2.5 2.4

4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2

SHC: Sensible Heat Capacity(kW)

ART COOL Gallery _ 6

Indoor Units

Notes: TC: Total Capacity(kW)

32 24 TC SHC kW kW


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating Capacity

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

7 _ ART COOL Gallery


7. Electric Characteristics Units Model

Type

ARNU07GSF*2

SF

ARNU09GSF*2

SF

ARNU12GSF*2

SF

ARNU07GSF*2

SF

ARNU09GSF*2

SF

ARNU12GSF*2

SF

Power Supply Hz 50

Volts 220 - 240

60

220

Voltage Range MCA Max:264 Min:198

Max:242 Min:198

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

0.23

15

0.024

0.18

35

35

0.23

15

0.024

0.18

35

35

0.23

15

0.024

0.18

35

35

0.23

15

0.024

0.18

35

35

0.23

15

0.024

0.18

35

35

0.23

15

0.024

0.18

35

35

Symbols:

Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA. 5. Instead of fuse, use Circuit Breaker.

ART COOL Gallery _ 8

Indoor Units

MCA: Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor


8. Sound Levels Overall

Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1m 0.8m Microphone

H

Sound Levels dB(A) M L

ARNU07GSF*2

38

32

27

ARNU09GSF*2

38

32

27

ARNU12GSF*2

44

38

32

Sound Pressure Level ARNU07GSF*2 ARNU09GSF*2

ARNU12GSF*2 80

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

Octave Band Sound Pressure Level (dB re 20µPa )

80

Octave Band Sound Pressure Level (dB re 20µPa )

Indoor Units

Model

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-25

20

NC-20

Approximate Hearing Threshold

NC-15

10 63

NC-25

20

Approximate Hearing Threshold 125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

9 _ ART COOL Gallery

NC-20 NC-15

10 63

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)


9. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Installation Parts Provided

1. Installation guide map

2. Type "A" screw and plastic anchors Indoor Units

Required Parts

Required Tools

❏ Four type "A" screws ❏ Connecting cable ❏ Pipes: Gas side Liquid side

❏ Level gauge ❏ Screw driver ❏ Electric drill ❏ Hole core drill ❏ Flaring tool set ❏ Specified torque wrenches ❏ Spanner......................................................Half union ❏ A glass of water ❏ Screw driver ❏ Thermometer

❏ Insulation materials ❏ Additional drain pipe

9.1 Selection of the best location • Do not have any heat or steam near the unit. • Select a place where there are no obstacles in front of the unit. • Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway. • Ensure that the space around the left and right of the unit is more than 500mm. The unit should be installed as high on the wall as possible, allowing a minimum of 200mm from ceiling. • Use a stud finder to locate studs to prevent unnecessary damage to the wall.

More than 200mm More than 500mm

More than 500mm More than 1500mm

ART COOL Gallery _ 10


9. Installation 9.2 Preparing Work for Installation Open panel front 1. Pull the upper part of the front panel. 2. Lift up the panel. 3. To detach the front panel, remove the two screws at the lower part. 4. Detach the front panel from the body.

Indoor Units

5. To detach the panel, disconnect the connector at the upper part.

Panel Front Connector

Cover pipe and cover side remove 1. Please remove the screw of the center tuning cover. 2. Pull up the side cover of desired connecting direction, then cover side is separated. 3. Pick the pipe hole of the side cover.

CAUTION: After removing the pipe hole, cut the burr for safety.

Pipe hole Side cover

NOTICE

When making pipe path through rear wall, you donĘźt need to pick the pipe hole.

Drain hose junction 1. Remove the rubber stopple in the desired drain direction. 2. Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by. Adhesive

Onlythe the Only desired desireddirection direction

Connecting part Drain hose

11 _ ART COOL Gallery

rubber cap


9. Installation 9.3 Fixing Indoor Unit 1. Attach an Installation guide map on the desired surface. INSTALLATION GUIDE MAP

2. Look at suited horizon by horizontal meter on the horizontal setting line, and fix lightly the map by adhesive tape. Horizontality

3. Make a hole with a diameter of 6mm and depth of 30-35mm by piercing a screw point. IN ST AII AT IO N

IN ST AL LA TIO N

GU ID EM AP

4. Drill the pierted part as a diameter of 50mm for connecting piping. (In case of piercing rear surface)

GU ID EM AP

IN ST AL LA TIO N

GU ID EM AP

6. First, Drive the two points of the upper parts by screws. (Leave 10mm for hanging the product) 10

Plastic anchors

7. Hang the hole of product at the upper screws, and remove the map. (Falling attention) INS TAL LAT ION GUID EM AP

mm

IN ST AL LA TIO N

GU

8. Drive the lower parts after facing the hole of product with plastic anchors, and fix completely the upper screws. Plastic anchors

Hanger hole (Rear side of the product)

9. Check the fixed product with light power.

10. In case of nothing wrong, connect the pipe and the wire. (Refer to installation manual)

ART COOL Gallery _ 12

Indoor Units

5. Drive the fore plastic anchors into drilled points.


9. Installation 9.4 Connecting the Piping Preparing the indoor unit's piping and drain hose for installation through the wall. 1. Route the indoor tubing and the drain hose in the direction of rear left or right

3. Connecting the pipings to the in door unit and drain hose to drain pipe ❏ Align the center of the pipings and sufficiently tighten the flare nut by hand.

Indoor unit tubing

Flare nut

Pipings

❏ Tighten the flare nut with a wrench.

Drain hose

Spanner (fixed)

Indoor Units

Flare nut

2. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

Torque wrench

Connection pipe

Indoor unit tubing

❏ When extending the drain hose at the indoor unit, install the drain pipe.

Drain pipe

Loop

Connecting cable

Gas side piping Liquid side piping

Drain hose

CAUTION: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.

13 _ ART COOL Gallery

Indoor unit drain hose Adhesive

Vinyl tape(narrow)

4. Wrap the insulation material around the connecting portion. ❏ Overlap the connecting pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.

Plastic bands Insulation material


9. Installation CAUTION: Installation Information For right piping. Follow the instruction below. Good case • Press on the upper side of clamp and unfold the tubing to downward slowly.

Indoor Units

Bad case • Following bending type from left to right may cause damage to the turbing.

9.5 Drain Piping 1) To check the drainage. • Pour a glass of water on the evaporator. • Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

2) Drain piping • The drain hose should point downward for easy drain flow. Downward slope

• Do not make drain piping. Do not raise

Tip of drain hose dipped in water

Accumulated drain water

Less than 50mm gap

Air

Water leakage

Water leakage

Waving

Water leakage

Ditch

ART COOL Gallery _ 14


9. Installation 9.6 Panel Front Assembly

Indoor Units

1. First, Check the side cover assembly exactly, and fix the power cord in the bottom groove of cover side left.

2. Assemble connecting lead wire with controller, fix the upper part of panel front, and match the lower part of panel front. Panel Front Connector

3. Screw up panel front, and suspend the hook of panel front in the groove.

15 _ ART COOL Gallery


9. Installation 9.7 Connect the cable to the Indoor unit. • Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.) The earth wire should be longer than the common wires. [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

SODU A

IDU B

IDU A

INT B

INT A

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

CAUTION • When installing, refer to the circuit diagram on the Control Box of Indoor Unit. • When installing, refer to the wiring diagram on the Control Cover Inside Outdoor Unit.

CAUTION • The above circuit diagram is subject to change without notice. • Be sure to connect wires according to the wiring diagram. • Connect the wires firmly, so that not to be pulled out easily. • Connect the wires according to color codes by referring the wiring diagram.

After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power circuit specifically for the air conditioner. As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Confirm the specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. 7) Always install an earth leakage circuit breaker in a wet or moist area. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.

ART COOL Gallery _ 16

Indoor Units

INDOOR POWER INPUT


9. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:

Indoor Units

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

17 _ ART COOL Gallery


10. Accessories Standard Accessories Name

Installation guide map

Quantity

1 EA

Type "A" screws and plastic anchors

(Other)

4 SET • Owner's manual • Installation manual

Shape

Indoor Units

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

ART COOL Gallery _ 18


Indoor unit Ceiling & Floor / Ceiling Suspended 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU09GVEA2, ARNU12GVEA2 ARNU18GVJA2, ARNU24GVJA2 1 Manual Auto X O 3/4/3 X O O X X O X X X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Ceiling & Floor / Ceiling Suspended _ 1

Indoor Units

Installation

Function


2. Specifications Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

Indoor Units

Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color

Ø, V, Hz mm2 mm2

Ceiling & Floor ARNU09GVEA2 ARNU12GVEA2 2.8 3.6 2,400 3,100 9,600 12,300 3.2 4.0 2,800 3,400 10,900 13,600 900 x 200 x 490 900 x 200 x 490 35.4 x 7.9 x 19.3 35.4 x 7.9 x 19.3 2 x 12 x 20 2 x 12 x 20 0.10 0.10 Cross Flow Fan Cross Flow Fan 27 27 0.15 0.15 7.6 / 6.9 / 6.2 9.2 / 7.6 / 6.9 268 / 243 / 219 325 / 268 / 244 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 16(5/8) 16(5/8) 13.7(30.2) 13.7(30.2) 36 / 32 / 28 38 / 36 / 30 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling & Floor / Ceiling Suspended

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body Coil

m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color

Ø, V, Hz mm2 mm2

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling & Floor / Ceiling Suspended _ 3

Indoor Units

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch

Ceiling Suspended ARNU18GVJA2 ARNU24GVJA2 5.6 7.1 4,800 6,100 19,100 24,200 6.3 8.0 5,400 6,900 21,500 27,300 Galvanized Steel Plate+Painting Galvanized Steel Plate+Painting 950 x 220 x 650 950 x 220 x 650 37.4 x 8.7 x 25.6 37.4 x 8.7 x 25.6 3 x 14 x 19 3 x 14 x 19 0.23 0.23 Sirocco Fan Sirocco Fan 60 60 0.30 0.30 16.0 / 14.0 /12.0 18.0 / 16.0 / 14.0 565 / 495 / 424 636 / 565 / 495 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) 16(5/8) 16(5/8) 24.6(54.2) 24.6(54.2) 42 / 40 / 37 43 / 41 / 39 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog


587

273

4 _ Ceiling & Floor / Ceiling Suspended Liquid pipe Gas pipe Suction gille Discharge grille Suspension bracket Right side drain hose hole Left side drain hose hole Wiring connection Piping connection Signal receiver & Operation indicator 1 2 3 4

Slit hole Slit hole

More than 200mm

CHASSIS CODE: VE

More than 50mm

More than 200mm

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

More than 50mm

More than 200mm

※ Required space(unit:mm)

More than 200mm

(unit : mm)

200

D

(unit : mm)

Descripition ø6.35 Flare connection ø12.7 Flare connection

490

H

Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

5 6 7 8 9 10

Name

900

ARNU09GVEA2 ARNU12GVEA2

Number

W

ARNU09GVEA2 ARNU12GVEA2

Ceiling & Floor

Model

Indoor Units

3. Dimensions


(unit : mm)

220

D

(unit : mm)

Slit hole Slit hole Slit hole Slit hole

Descripition ø6.35 Flare connection ø12.7 Flare connection

650

H

Ceiling & Floor / Ceiling Suspended _ 5

Indoor Units

CHASSIS CODE: VJ

More than 300mm

More than 700Um

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

More than 700mm

※ Required space(unit:mm)

Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

5 6 7 8 9 10 11

Name Liquid pipe Gas pipe Suction gille Discharge grille Suspension bracket Right side drain hose hole Left side drain hose hole Wiring connection Piping connection Right side drain pipe connection Left side drain pipe connection

1 2 3 4

950

ARNU18GVJA2 ARNU24GVJA2

Number

W

Model

ARNU18GVJA2 ARNU24GVJA2

Ceiling Suspended

3. Dimensions


4. Piping Diagrams VE Chassis Heat Exchanger Th3

EEV

Filter

Th2 C.F.F.

Th1

Indoor Units

:Cooling :Heating

Filter

lndoor unit

VJ Chassis Heat Exchanger

EEV

:Cooling :Heating

Filter

Th2

Th3 Sirocco Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

Model

Gas

Liquid

ARNU09GVEA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GVEA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GVJA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GVJA2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

6 _ Ceiling & Floor / Ceiling Suspended


5. Wiring Diagrams VE Chassis

CN-POWER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-DISPLAY CN-DOOR CN-CC

SPEC.

DESCRIPTION

AC power supply Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Option pwb. Communication Drain pump output AC power supply Display wire Door lock switch Dry contact

AC power line input for indoor controller Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV Control output Communication between main and option Communication between indoor and outdoor AC Output for drain pump AC Power line input for indoor controller Display wire line Door lock switch line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling & Floor / Ceiling Suspended _ 7

Indoor Units

CONNECTOR NUMBER


5. Wiring Diagrams

Indoor Units

VJ Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-DISPLAY CN-DOOR CN-CC

SPEC.

DESCRIPTION

AC power supply Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Option pwb. Communication Drain pump output AC power supply Display wire Door lock switch Dry contact

AC power line input for indoor controller Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV Control output Communication between main and option Communication between indoor and outdoor AC Output for drain pump AC Power line input for indoor controller Display wire line Door lock switch line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

8 _ Ceiling & Floor / Ceiling Suspended


6. Capacity Tables 6.1 Cooling Capacity

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.9

3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0

2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4

4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0

6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.8 3.8

7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0

4.3 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5

Capacity Index

Outdoor air temp. (DB, °C)

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling & Floor / Ceiling Suspended _ 9

Indoor Units

Notes: TC: Total Capacity(kW)

30 22 TC SHC kW kW


6. Capacity Tables

Indoor Units

Cooling capacity

Capacity Index

Outdoor air temp. (DB, °C)

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1

SHC: Sensible Heat Capacity(kW)

10 _ Ceiling & Floor / Ceiling Suspended

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 5.0

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4 5.3 5.2 5.1 5.1 5.0 4.9 4.8

32 24 TC SHC kW kW 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

5.4 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9 4.8 4.7 4.6 4.6 4.5 4.4


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating capacity Indoor air temp. (DB, °C)

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.8

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

Notes: TC: Total Capacity(kW)

Ceiling & Floor / Ceiling Suspended _ 11

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


6. Capacity Tables Heating capacity

Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor Units

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

12 _ Ceiling & Floor / Ceiling Suspended


7. Air Velocity and Temperature Distribution ARNU09GVEA2 ■ Ceiling Cooling

Heating Discharge angle:60°

Discharge angle:50° Air velocity [m/s]

Air velocity [m/s] 1.5

2.7m 0.5

1.0

2.7m

0.5

0.5

1.0 1.0

0.5

1.0

0.5

1.0

2m

0.5

2m

1.0

0.5 1.0

1.0

0.5

0.5

0.5

0.5

1.0

4m

3m

2m

1m

0.5

1.0

0m 0m

5m

Temperature [°C]

4m

3m

2m

0m 1m

0m

Temperature [°C] 2.7m

32.0 30.0

.0 42

32

44.0 42.0

.5

15.0

30.0

18.0

17.0

28.0

.0

17.0 16.0

32

17.0

2.7m

14.0 13.0 13.0 15.0 17.0 17.0

.0 34

2m

2m

38.0

32.5 18.0 18.0

32.0

17.0

1m

30.0

18.0

18.0

30.0

4m

3m

2m

0m

1m

.0 3434.0

28.0

0m

5m

1m

5m

4m

3m

2m

1m

0m

0m

ARNU09GVEA2 ■ Floor

Cooling

Heating Discharge angle:50°

Discharge angle:45° Air velocity [m/s]

Air velocity [m/s] 2.7m 0.5

2.7m

0.5

1.0

0.5

0 .5

0.5

0.5

2m

2m 1.0

1.0

0.5

0.5

0.5

0.5

0.4

0m 3m

2m

1m

4m

3m

0.5

2m

0m

1m

0m

Temperature [°C] .0

32

.0

36.0

2.7m

0 18.

38.0

35

2m

35.1

35 .1

36.0

0 18.

18.0

34.0

1m

0m

5m

35.1

35.1

0m 2m

1m .0

18.0

1m

40

0 16.

38.0

38.0

14.8

2m

42.0

14.8

3m

2.7m

35.1

14.8

4m

0.5

0.5

1.0

5m

0m

Temperature [°C]

5m

1m

0.4 0. 0.4 5

0.5 4m

1.0 0.4

0.5

1.5

2.0

1m

1.5

0.2

5m

0.5

1.0

0.5

4m

3m

34.0

2m

34.0

0m 1m

0m

Ceiling & Floor / Ceiling Suspended _ 13

Indoor Units

15.0

32.0

5m

1m

0.5

1m


7. Air Velocity and Temperature Distribution ARNU12GVEA2 ■ Ceiling Cooling

Heating Discharge angle:60°

Discharge angle:50°

Air velocity [m/s]

Air velocity [m/s] 1.0

0.5 2.5 1.5

1.5

1.0

1.0

0.5

2.7m

1.0

2.7m

26.0

28.0

1.0

1.0

30.0

30.0

44.0

0.5

0.5

26.0

2m

2m

38.0 30.0

28.0 1.0

1m

1m 0.5

26.0 30.0

1.0 1.0

0.5

1.5

0.5

28.0

24.0

32.0

0m

0m 5m

4m

3m

2m

1m

5m

0m

Indoor Units

3m

2m

1m

0m

Temperature [°C]

Temperature [°C] 14.0

15.0

17.0

4m

16.0

2.7m

14.0 13.0 13.0

15.0

2.7m

26.0

28.0

30.0

30.0

18.0 17.0

17.0

44.0 26.0

2m

17.0

2m

38.0 30.0

28.0

1m

1m

26.0 17.0

17.0

30.0

16.0 18.0

17.0 16.0

28.0

24.0

32.0

0m

0m 5m

4m

3m

2m

0m

1m

5m

4m

3m

2m

0m

1m

ARNU12GVEA2 ■ Floor

Cooling

Heating Discharge angle:60°

Discharge angle:50°

Air velocity [m/s] 2.7m 0.5

0.5

0.5

2m

1.0

1.5

1.0

0.4

1. 0

1.0

2.0

1.0

0.5

0.5

1.0

0.5

1.0

0.5 0.5

1.0

0.5

1m

1.5 1.5

1.0

0.5

1m

0.4 0.5

0.5

2.5

0.5

1.5

1.0 1.5

0.4

2m

1.5

0.5

0.5

0.4

2.7m

1.5

0. 5

1.0

1.5

Air velocity [m/s]

0m 4m

3m

2m

1m

0m

0m 5m

4m

3m

2m

1m

0m

Temperature [°C]

Temperature [°C] 16.0

2.7m

36.0 34.0

16.0

36.0 15.0

18.0

38.0

5m

16.8

38 38 .0

2.7m

.0

35.4

2m

.4

2m

1m

40.0

1m

36 .0

17.0

18.0

3m

35

4m

15.0

.0 42 42.035.4

.0

5m

16.8

36.0 35.4

36.0

1m

16 16.8

.0 20 19.0

35.4

14.0 13.0 16 .0

42.0

38.0

2m

34.0

0m 0m

14 _ Ceiling & Floor / Ceiling Suspended

5m

4m

3m

34.0

35.4

0m 2m

1m

0m


7. Air Velocity and Temperature Distribution ARNU18GVJA2 ■ Ceiling Cooling

Heating Discharge angle:60°

Discharge angle:50° Air velocity [m/s]

Air velocity [m/s] 3.0

3.0

1.5

4.0

2.7m

1.5 4.0 1.5 3.5

1.5

3.0

1.5

3.0

1.5

2.7m

1.0

3.0

3.0 1.5

1.5

1.0

1.5

2m

2m

1.5

1.5

1m

1.5

1m

1.0 1.5

1.5 1.0

1.5

1.5 0m

4m

3m

2m

1m

0m

Temperature [°C]

3m

2m

1m

0m

Temperature [°C] 40.0

34.0

38.0

40.0

42.0

2.7m

42.0 36.0

2m

36.0

2m

.0

17.0

2.7m

13.0 14.0 13.0 14.0 17.0 17.0

32

16

16.0

40.0

14.0

.0

18.0

.0

4m

30.0

16.0

36.0

1m

38.0

18.0

1m

36

.0

36.0

.0

.0 19

17

.0

19

28.0

0m 5m

4m

3m

2m

0m

1m

0m 5m

4m

3m

2m

0m

1m

ARNU24GVJA2 ■ Ceiling

Cooling

Heating Discharge angle:60°

Discharge angle:50° g

Air velocity [m/s]

Air velocity [m/s] 3.0

1.0

2.7m

2.0

2.0 1.0 1.0 4 2.0 .5 5.0 1.0

1.0

1.0

2.7m

1.0 0.5 3.0 3.5 3.0 1.0

2.0

3.0

6.0

g

1.0

2m

1.0

2m 0.5 1.0

2.0

1.0

1m

1m

1.0

1.0

1.0

1.0

2.0

0m

0m 4m

3m

2m

1m

5m

0m

3m

2m

1m

0m

Temperature [°C] 2.7m

34.0

15.0

40.0 38.0

38.0

38.0

14.0 13.0 17.0

18.0

17.0

17.0

40.0 36.0

2.7m

40.0

.0 42.0 42 36.0 38.0

.0

15.0

13.0

Temperature [°C] .0 18

4m

36

5m

34.0

2m

2m

36.0

16.0

18.0

1m

1m

5m

17.0

.0

.0 36 2.0 3

16 19 .0

.0

18

36.0

32.0

0m

0m 4m

3m

2m

1m

0m

5m

4m

3m

2m

1m

0m

Ceiling & Floor / Ceiling Suspended _ 15

Indoor Units

15

0m 5m

34.0

5m


8. Electric Characteristics Units Model

Type

ARNU09GVEA2 ARNU12GVEA2

VE VE

ARNU18GVJA2 ARNU24GVJA2

VJ VJ

ARNU09GVEA2 ARNU12GVEA2 ARNU18GVJA2 ARNU24GVJA2

VE VE VJ VJ

Power Supply Hz

50

Volts

220 - 240

60

220

Voltage Range MCA Max:264 Min:198

Max:242 Min:198

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

0.22 0.22

15 15

0.027 0.027

0.17 0.17

30 30

30 30

0.43 0.43

15 15

0.060 0.060

0.35 0.35

63 63

63 63

0.22 0.22 0.43 0.43

15 15 15 15

0.027 0.027 0.060 0.060

0.17 0.17 0.35 0.35

30 30 63 63

30 30 63 63

Indoor Units

Symbols: MCA: Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA. 5. Instead of fuse, use Circuit Breaker.

16 _ Ceiling & Floor / Ceiling Suspended


9. Sound Levels Overall Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1m

1m Microphone

Sound Levels dB(A)

Model

Sound Levels dB(A)

Model

H

M

L

H

M

L

ARNU09GVEA2

36

32

28

ARNU18GVJA2

42

40

37

ARNU12GVEA2

38

36

30

ARNU24GVJA2

43

41

39

Sound Pressure Level

70

70

70

NC-65 60 NC-60 NC-55

50

NC-50 NC-45 40 NC-40 NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-60

NC-50 NC-45 40 NC-40

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-15 125

NC-55

50

NC-20

10 63

NC-65 60

NC-65 60 NC-60

NC-15 125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

NC-55

50

NC-50 NC-45 40 NC-40 NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-20

10 63

Octave Band Sound Pressure Level (dB re 20μPa )

80

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU18GVJA2

ARNU12GVEA2 80

NC-20 NC-15

10 63

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

ARNU24GVJA2 80

Octave Band Sound Pressure Level (dB re 20μPa )

70

NC-65 60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

20

10

NC-25 Approximate Hearing Threshold 63

NC-20 NC-15 125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

Ceiling & Floor / Ceiling Suspended _ 17

Indoor Units

ARNU09GVEA2 80


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

10.1 Features 10.1.1 VE Chassis

Vertical louver

Horizontal louver

Indoor Units

Air outlet vent

Air filters (behind front panel) Air inlet vent

18 _ Ceiling & Floor / Ceiling Suspended


10. Installation 10.1.2 VJ Chassis

Air Discharge

Right Side Cover

Signal Receptor

Left Side Cover

Inlet Grill

Drain hose

Ceiling & Floor / Ceiling Suspended _ 19

Indoor Units

Air Filter


10. Installation VE Chassis 10.2 Installation Map NOTICE

Installation parts you should purchase.

There should be no gap between the ceiling and the unit.

Indoor Units

Ceiling Mounting

Sleeve Bushing-Sleeve Putty(Gum Type Sealer) More than 200mm (Left and right are identical)

More than 50mm

Bend the pipe as closely on the wall as possible, but be careful that it doesn't break.

Wall Mounting

More than 200mm (Left and right are identical)

Vinyl tape (Wide) • To carry out the drainage test, remove the air filters and pour water into the heat exchanger. • Apply after carrying out a drainage test.

More than 50mm

Saddle

20 _ Ceiling & Floor / Ceiling Suspended


10. Installation 10.3 Select the best Location Indoor unit

More than 200mm

1. Do not have any heat or steam near the unit. 2. Select a place where there are no obstacles in front of the unit.

More than 200mm

3. Make sure that condensation drainage can be conveniently routed away. More than 50mm

4. Do not install near a doorway. 5. Ensure that the interval between a wall and the left (or right) of the unit is more than 200mm. The unit should be installed as low as possible on the wall, allowing a minimum of 500mm from floor.

More than 200mm

More than 50mm

More than 200mm

9.4 Preparing Work for Installation Open panel front 1. Remove the five screws. 2. Release the claws in the 3 places indicated. 3. Pull up the Front Panel.

2 Claw

Cover pipe and cover side remove 1. Pull up the side cover of desired connecting direction, then cover side is separated. 2. Pick the pipe hole of the side cover.

1

3

CAUTION: After removing the pipe hole, cut the burr for safety. NOTICE

When making pipe path through rear wall, you donĘźt need to pick the pipe hole.

Drain hose junction 1. Remove the rubber stopple in the desired drain direction. 2. Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure as shown on the right.

Ceiling & Floor / Ceiling Suspended _ 21

Indoor Units

6. Use a stud finder to locate studs to prevent unnecessary damage to the wall.


10. Installation 10.5 Mounting the installation plate(Wall Mounting) The wall you select should be strong and solid enough to prevent vibration

Indoor Units

1. Mount the installation plate on the wall with type "A" screws. While mounting the unit on a concrete wall, use anchor bolts. • Mount the installation plate horizontally by aligning the centerline using a level.

2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.

Installation Plate

Type "A" screw

70

70 Installation plate

Ă˜70mm

120

Ă˜70mm

more than 2000 Left rear piping

Right rear piping Floor

22 _ Ceiling & Floor / Ceiling Suspended


10. Installation 10.6 Mounting the anchor Nut & Bolt(Ceiling Mounting) • Prepare 4 suspension bolts. (Each bolts length should be same.) • Measure and mark the position for the Suspension bolts and the piping hole. • Drill the hole for anchor nut on the ceiling.

Anchor nut Ceiling Nut

Washer

Suspension bolts

• Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on the ceiling.

40

235 820

Suspension bolt

50 100

• Mount the suspension bolts to the anchor-nuts firmly. • Secure the hangers onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers.

Reference of piping hole (Ø45)

piping hole (Ø45)

• Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts.

: Tighten the nut and bolt to prevent unit falling.

Spring washer Hangen Max. 12mm

Nut

Washer

Hanging bolt (W3/8 or M10) Nut (W3/8 or M10)

Flat washer for M10 (accessory)

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Ceiling & Floor / Ceiling Suspended _ 23

Indoor Units

Suspension bolts

• Adjust a level on the direction of top-bottom by adjusting supension bolts. Then the unit will be inclined to the bottomside so as to drain well.


10. Installation : Installation Information For right piping. Follow the instruction below.

Good case

Bad case

For left piping. Follow the instruction below.

1. Following bending type from right to left could cause problem of pipe damage.

1. Press on the upper side of clamp. (â’ś) 2. Unfold the tubing downward slowly. (â’ˇ)

Indoor Units

3. Bend the tubing to the left side of chassis.

24 _ Ceiling & Floor / Ceiling Suspended


10. Installation 10.7 Checking the Drainage 1. Set the air direction louvers up-and-down to the position(horizontally) by hand.

To check the drainage. 1. Pour a glass of water on the evaporator using a kettle. 2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. ■ Checking the Drainage 1. Remove the Air Filter.

• To remove air filter, take hold of tab and pull slightly upwards.

Indoor Units

2. Check the drainage.

• Spray one or two glasses of water upon the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.

Downward slope

Drain piping 1. The drain hose should point downward for easy drain flow. 2. Do not make drain piping like the following.

Do not raise

Water leakage

Water leakage

Accumulated drain water Air

Waving

Less than 50mm gap

Tip of drain hose dipped in water

Water leakage

Ditch

10.8 Panel Front Assembly 1. Suspend the hook of panel front in the groove. 2. Press the panel front.

1

3. Screw up panel front. 3 2

Ceiling & Floor / Ceiling Suspended _ 25


10. Installation VJ Chassis 10.9 Select the best Location Indoor unit 1. Do not have any heat or steam near the unit.

More than 700mm

2. Select a place where there are no obstacles in front of the unit. 3. Make sure that condensation drainage can be conveniently routed away. 4. Do not install near a doorway.

Indoor Units

5. Ensure that the interval between a wall and the left (or right) of the unit is more than 700mm. 6. Use a stud finder to locate studs to prevent unnecessary damage to the wall.

More than 700mm

More than 300mm

: In case that the unit is installed near the sea, the installation parts may be cor-

roded by salt. The installation parts (and the unit) should be treated with appropriate anti-corrosion measures.

26 _ Ceiling & Floor / Ceiling Suspended


10. Installation 10.10 Preparing Work for Installation Open side cover 1. Remove two screws from side-cover as shown in fig. 2. Unlock side-cover from side panel by slightly pulling the edge of side cover. 3. Tap the side-cover with your palm on the backside.(Inlet grill side.) 4. Hold the side-cover with other hand while tapping to prevent it to fall down.

2 Edge part

1

5. Remove the rubber stopple in the desired drain direction. Indoor Units

6. Knock out the pipe hole from the left side-cover with the help or nipper/plier. 7. Knock hole on right side-cover only if right side is selected for water drain.

Ceiling & Floor / Ceiling Suspended _ 27


10. Installation (Unit: mm)

MOUNTING THE ANCHOR NUT AND BOLT

DIM.

A

B

855

320

MODEL

• Prepare 4 suspension bolts. (Each bolts length should be same.)

VJ

• Measure and mark the position for the Suspension bolts and the piping hole. • Drill the hole for anchor nut on the ceiling. • Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on the ceiling.

B

A

Ceiling

Suspension bolt Nut

Washer

Suspension bolts

• Secure the hangers onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers. • Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts.

Suspension bolts

• Adjust a level on the direction of top-bottom by adjusting supension bolts. Then the unit will be inclined to the bottomside so as to drain well.

: Tighten the nut and bolt to prevent unit falling.

Spring washer Hangen

Nut

Max. 12mm

Washer

Hanging bolt (W3/8 or M10) Nut (W3/8 or M10)

Flat washer for M10 (accessory)

Flat washer for M10 (accessory) Nut (W3/8 or M10)

DRILL A HOLE IN THE WALL.

WALL Indoor

Outdoor

28 _ Ceiling & Floor / Ceiling Suspended

(3/16"~5/16")

• Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.

5-7mm

Indoor Units

• Mount the suspension bolts to the anchor-nuts firmly.

Anchor nut


10. Installation 10.11 Indoor unit installation Hang the Indoor unit on suspension bolt as per following guidelines: 1. Lift the indoor unit to sufficient height. 2. Insert the suspended part of four suspension bolt in the four hangers provided on the side of main body one by one. 3. Lower the indoor unit till the hangers rest on their respective flat washer. 4. Adjust the level in the top down direction by adjusting the suspension bolts. Inclined the indoor unit as per direction provided in the fig

: Installation Information For Declination

1. Inclination of the indoor unit is very important for drain purposes in the convertible type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 10mm.

Front of view • The unit must be horizontal or inclined at angle. • The inclination should be less than or equal to 1° or in between 10 to 20mm inclined in drain direction as shown in fig. Ceiling 10~20mm

Side of view • The unit must be inclined to the bottomside of the unit when finished installation. Ceiling

Ceiling & Floor / Ceiling Suspended _ 29

Indoor Units

3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.


10. Installation 10.12 Checking the Drainage 1. Set the air direction louvers up-and-down to the position(horizontally) by hand.

To check the drainage. 1. Pour a glass of water on the evaporator using a kettle.

Indoor Units

2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

Drain piping Downward slope

1. The drain hose should point downward for easy drain flow.

2. Do not make drain piping like the following. Accumulated drain water Air

Do not raise

Water leakage

Water leakage

Waving

30 _ Ceiling & Floor / Ceiling Suspended

Tip of drain hose dipped in water

Water leakage

Ditch

Less than 50mm gap


10. Installation 10.13 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

IDU B

SODU A

IDU A

INT B

INT A

4

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING : Make sure that the screws of the terminal are free from looseness.

Ceiling & Floor / Ceiling Suspended _ 31

Indoor Units

INDOOR POWER INPUT


10. Installation CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have a separate power circuit specially for the air conditioner. As for the method of wiring, follow the circuit diagram posted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source 5) Confirm that electrical capacity is sufficient.

Indoor Units

6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal function of an overload protection device. • Proper starting power is not given to the compressor.

32 _ Ceiling & Floor / Ceiling Suspended


10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

Indoor Units

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling & Floor / Ceiling Suspended _ 33


11. Accessories Standard Accessories Name

Installation plate

Type "A" screw and plastic anchor

Quantity

1EA

4EA

(Other)

• Owner's manual • Installation manual

Indoor Units

Shape

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

34 _ Ceiling & Floor / Ceiling Suspended


Indoor unit Floor Standing 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Floor Standing _ 1

Indoor Units

Installation

Function

ARNU07GCEA2, ARNU09GCEA2, ARNU12GCEA2 ARNU15GCEA2, ARNU18GCFA2, ARNU24GCFA2 ARNU07GCEU2, ARNU09GCEU2, ARNU12GCEU2 ARNU15GCEU2, ARNU18GCFU2, ARNU24GCFU2 1 3/3/3 X X O X O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O X O O O Accessory Accessory Accessory Accessory X Accessory -


2. Specification Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

Indoor Units

Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch m3 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

Floor Standing ARNU07GCEA2 ARNU09GCEA2 2.2 2.8 1,900 2,400 7,500 9,600 2.5 3.2 2,200 2,800 8,500 10,900 Galvanized Galvanized Steel Plate Steel Plate 1,067 x 203 x 635 1,067 x 203 x 635 42.2 x 8.0 x 25.0 42.2 x 8.0 x 25.0 2 x 12 x 19 2 x 12 x 19 0.16 0.16 Sirocco Fan Sirocco Fan 28 28 0.15 0.15 8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 300 / 265 / 229 335 / 300 / 265 Direct Direct BLDC BLDC Microprocessor, Microprocessor, Thermostat for Thermostat for cooling and heating cooling and heating Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 12(15/32) 12(15/32) 27(59.5) 27(59.5) 35 / 33 / 31 36 / 34 / 32 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Floor Standing

ARNU12GCEA2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 1,067 x 203 x 635 42.2 x 8.0 x 25.0 2 x 12 x 19 0.16 Sirocco Fan 28 0.15 10.5 / 9.5 / 8.5 371 / 335 / 300 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12(15/32) 27(59.5) 37 / 35 / 33 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specification Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body Coil

m3 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

Floor Standing ARNU09GCEU2 2.8 2,400 9,600 3.2 2,800 10,900 Galvanized Steel Plate 978 x 190 x 639 38.5 x 7.5 x 25.2 2 x 12 x 19 0.16 Sirocco Fan 28 0.15 9.5 / 8.5 / 7.5 335 / 300 / 265 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12(15/32) 20(44.1) 36 / 34 / 32 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

ARNU12GCEU2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 978 x 190 x 639 38.5 x 7.5 x 25.2 2 x 12 x 19 0.16 Sirocco Fan 28 0.15 10.5 / 9.5 / 8.5 371 / 335 / 300 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12(15/32) 20(44.1) 37 / 35 / 33 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Floor Standing _ 3

Indoor Units

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch

ARNU07GCEU2 2.2 1,900 7,500 2.5 2,200 8,500 Galvanized Steel Plate 978 x 190 x 639 38.5 x 7.5 x 25.2 2 x 12 x 19 0.16 Sirocco Fan 28 0.15 8.5 / 7.5 / 6.5 300 / 265 / 229 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12(15/32) 20(44.1) 35 / 33 / 31 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C


2. Specification

Indoor Units

Type Model

Floor Standing ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2 4.5 5.6 7.1 Cooling Capacity 3,900 4,800 6,100 15,400 19,100 24,200 5.0 6.3 8.0 Heating Capacity 4,300 5,400 6,900 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 1,067 x 203 x 635 1,345 x 203 x 635 1,345 x 203 x 635 Dimensions(WxDxH) Body inch 42.2 x 8.0 x 25.0 52.9 x 8.0 x 25.0 52.9 x 8.0 x 25.0 Rows x Columns x FPI 2 x 12 x 19 3 x 11 x 19 3 x 11 x 19 Coil Face Area m3 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 28 76 76 Running Current A 0.15 0.38 0.38 Fan Air Flow Rate(H / M / L) CMM 11.5 / 10.0 / 9.5 16.0 / 14.0 / 12.0 18.0 / 16.0 / 14.0 cfm 406 / 353 / 335 565 / 494 / 424 635 / 565 / 494 Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat Microprocessor, Thermostat Microprocessor, Thermostat for cooling and heating for cooling and heating for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Resin Net(washable) Resin Net(washable) Resin Net(washable) Safety Device Fuse Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 12(15/32) 12(15/32) 12(15/32) Net Weight kg(lbs) 27(59.5) 34(75.0) 34(75.0) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) 38 / 37 / 35 40 / 37 / 34 43 / 40 / 37 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Unit kW kcal/h Btu/h kW kcal/h Btu/h

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

4 _ Floor Standing

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specification Type Model

Floor Standing ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2 4.5 5.6 7.1 Cooling Capacity 3,900 4,800 6,100 15,400 19,100 24,200 5.0 6.3 8.0 Heating Capacity 4,300 5,400 6,900 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 978 x 190 x 639 1,256 x 190 x 639 1,256 x 190 x 639 Dimensions(WxDxH) Body inch 38.5 x 7.5 x 25.2 49.5 x 7.5 x 25.2 49.5 x 7.5 x 25.2 Rows x Columns x FPI 2 x 12 x 19 3 x 11 x 19 3 x 11 x 19 Coil Face Area m3 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 28 76 76 Running Current A 0.15 0.38 0.38 Fan Air Flow Rate(H / M / L) CMM 11.5 / 10.0 / 9.5 16.0 / 14.0 / 12.0 18.0 / 16.0 / 14.0 cfm 406 / 353 / 335 565 / 494 / 424 635 / 565 / 494 Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat Microprocessor, Thermostat Microprocessor, Thermostat for cooling and heating for cooling and heating for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Resin Net(washable) Resin Net(washable) Resin Net(washable) Safety Device Fuse Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 12(15/32) 12(15/32) 12(15/32) Net Weight kg(lbs) 20(44.1) 27(59.5) 27(59.5) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) 38 / 37 / 35 40 / 37 / 34 43 / 40 / 37 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Unit kW kcal/h Btu/h kW kcal/h Btu/h

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Floor Standing _ 5

Indoor Units

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.


148.3

<Without Case>

978 794

<With Case> 2

1067

1067

13

148.3

1

635 70 20.4

6 _ Floor Standing 62.8

190 161

203

14

Air discharge grill Air suction grill

1 2

639

635

H

Descripition

(unit : mm)

190

203

D

(unit : mm)

ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: CE

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Name

Number

978

ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2

W 1067

Model

ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2

Floor Standing

ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2

Indoor Units

3. Dimensions

49

639


Floor Standing _ 7

148.3

70

21.4

639

<Without Case>

1256 1098 1072

<With Case>

1048.4

2

203 635 109.8 30

148.3

70 81.4

1345

1

190 161

203

14

Air discharge grill Air suction grill

1 2

639

635

H

Descripition

(unit : mm)

190

203

D

(unit : mm)

ARNU18GCFU2 ARNU24GCFU2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: CF

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Name

Number

1256

1345

ARNU18GCFA2 ARNU24GCFA2 ARNU18GCFU2 ARNU24GCFU2

W

ARNU18GCFA2 ARNU24GCFA2

Model

Indoor Units

145

49.4

Floor Standing

3. Dimensions


4. Piping Diagrams

Heat Exchanger

EEV Th2

Th3 Sirroco Fan

Th1

Indoor Units

Filter

:Cooling :Heating

Filter

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

Model ARNU07GCEA2 ARNU07GCEU2 ARNU09GCEA2 ARNU09GCEU2 ARNU12GCEA2 ARNU12GCEU2 ARNU15GCEA2 ARNU15GCEU2 ARNU18GCFA2 ARNU18GCFU2 ARNU24GCFA2 ARNU24GCFU2

8 _ Floor Standing

Gas

Liquid

Ø12.7(1/2)

Ø6.35(1/4)

Ø12.7(1/2)

Ø6.35(1/4)

Ø12.7(1/2)

Ø6.35(1/4)

Ø12.7(1/2)

Ø6.35(1/4)

Ø12.7(1/2)

Ø6.35(1/4)

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor


5. Wiring Diagrams CE/CF Chassis

CN-POWER CN-MOTOR1 CN-MOTOR2 CN-COMM CN-EEV CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-OPTION CN-ZONE CN-DISPLAY CN-CC

LOCATION POINT

FUNCTION

AC power supply Fan motor output Fan motor output Communication Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Option PCB Zone controller RF Remote controller Dry contact

AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC Communication between indoor and outdoor EEV Control output Pipe in thermistor Pipe out thermistor Room thermistor Remote control line Communication between main and option Zone control line RF Remote control line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Floor Standing _ 9

Indoor Units

CONNECTOR NUMBER


6. Capacity Tables 6.1 Cooling Capacity

Capacity Index

Indoor Units

2.2

2.8

3.6

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

10 _ Floor Standing

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

SHC: Sensible Heat Capacity(kW)

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5 1.5 1.5 1.5 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 1.9 1.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.7 2.7 2.6 2.6 2.5 2.5

32 24 TC SHC kW kW 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3


6. Capacity Tables Cooling capacity

Capacity Index

4.5

7.1

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8

3.6 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.0

6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.8 3.8 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 5.2 5.1 5.0 4.9 4.8 4.7

7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

4.3 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 5.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5 4.4 4.4

Notes: TC: Total Capacity(kW)

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Floor Standing _ 11

Indoor Units

5.6

20 14 TC SHC kW kW

Outdoor air temp. (DB, °C)


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating capacity Indoor air temp. (DB, °C)

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW) Capacity

12 _ Floor Standing


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

4.5

7.1

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2 5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7 5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3 5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

Floor Standing _ 13

Indoor Units

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Indoor air temp. (DB, °C)


7. Air velocity and Temperature Distribution(Reference Data) ARNU07GCEA2 /ARNU07GCEU2 Cooling

Heating

Discharge angle:45°

Discharge angle:60° Air velocity [m/s] 22

2.7m

24

24 3028

26

2.7m

3 0 32

26 32

20

21

2248

23

21 22

21

23

34

Air velocity [m/s]

23 20

2m

30

36 38

22

2m

26

19 19 36 34

22

18

1m

18

1m

28

23

1156

21

26

22

8m

7m

6m

24

23

23

0

5m

4m

3m

2m

1m

0

8m

24

7m

6m

5m

4m

28

26

3m

2m

24

0

Temperature [°C]

Temperature [°C]

1

2m

1.5

2m 5 0.

1

Indoor Units

2.7m

0.5

2.7m

0.5 0.5

5 0 .2 1.5 1

5 0.

1 0.5

1m

3

2

0.5 2

8m

7m

0

1m

6m

5m

4m

3m

2m

1m

0 0

141.5

8m

7m

6m

5m

4m

3m

2m

1m

1m

0

0

ARNU09GCEA2 /ARNU09GCEU2 Cooling

Heating

Discharge angle:45°

Discharge angle:60°

Air velocity [m/s]

Air velocity [m/s] 2.7m

19

2624

2624

83

82

21

2.7m

84

2m

24

86

83

2m

83 80

82

22 21 20

22 21

20 22

20

02 0 8 84

1m 26

22

24

0 8m

7m

6m

5m

4m

3m

2m

1m

0

8m

Temperature [°C]

7m

6m

26

24

5m

1m

83

17 19 21 16

24

8 22 1

18

26

03

22

21

4m

3m

0 2m

1m

0

Temperature [°C] 0.5

2.7m

1

3.5

0.5

2.7m

3.5 1

2m

5 1.

0.5

1.5

2m 1

2

1m

2.5

1m

1

2

7m

6m

5m

14 _ Floor Standing

4m

3m

2m

1m

0

1.5

3.5

8m

3.5

0.5

0 8m

7m

6m

5m

4m

3m

2m

1m

0 0


7. Air velocity and Temperature Distribution(Reference Data) ARNU12GCEA2 /ARNU12GCEU2 Cooling

Heating

Discharge angle:45°

Discharge angle:60°

Air velocity [m/s]

26

83

86

80

2m

84

22

24

82 80

20

18

21

83 26

82

24 24

21

2.7m

19 22

20

26

Air velocity [m/s] 21

22

83

2.7m 2m

21 20 5 22 1 21 16

1m

22

22

6m

5m

4m

3m

2m

1m

0

8m

Temperature [°C]

7m

6m

5m

26

24

4m

0 3m

2m

1m

0

Temperature [°C] 1

2.7m

3.5

2.7m

0.5

2m

2

2m

1

1. 5

1 .5 3

1

1m

0. 5

1m

2.5 1.5

0.5

2.5 1.5 .5 1

1

5 3.

1.5

0 8m

7m

6m

5m

4m

3m

2m

1m

8m

0

7m

6m

5m

4m

3m

2m

1m

0

0

ARNU15GCEA2 /ARNU15GCEU2 Cooling

Heating

Discharge angle:45°

Discharge angle:60°

Air velocity [m/s]

Air velocity [m/s] 20

2.7m

21

3230

28 30

1m 34

28

28

0 5m

4m

3m

2m

1m

32

16

21

6m

2m

34

40

8 15 21 1

18 20

21

7m

2.7m

19

17

38

30

2m

21

8m

32

3436

20

19

30 28

21

1m

0

8m

Temperature [°C]

7m

6m

5m

4m

28

3m

2m

0

1m

0

Temperature [°C] 1

2.7m

0.5 0.5

1.0

0.5

2.7m

0.5

2m

1

1. 5

0.5

0.5 5 0.

2m

1.0

1 2

1. 5

1m

1m

2.0

3. 5

5 2.

2

7m

6m

5m

4m

3m

2m

1m

0 0

1.0

11.5 2

8m

0.5

3

4

0 8m

7m

6m

5m

4m

3m

2m

1m

0

Floor Standing _ 15

Indoor Units

0.5

0.5

3.5

7m

26

24

0 8m

1m

84 02 82

19

03

83

17


7. Air velocity and Temperature Distribution(Reference Data) ARNU18GCFA2 /ARNU18GCFU2 Cooling

Heating

Discharge angle:45°

Discharge angle:60°

Air velocity [m/s]

Air velocity [m/s]

22

20

30

32 34 32

30

32

2m

2m

36

20

38 4 2

22

40

32

16

1m

1m 30

18

30

7m

30

22

22

8m

2.7m

34

38

20

2.7m

22

18

30

20

36

22

20

0

0 6m

5m

4m

3m

2m

1m

8m

0

Temperature [°C]

7m

6m

5m

4m

3m

2m

1m

0

Indoor Units

Temperature [°C] 2.7m

1.0

2.7m

0.5

1.0

0.5

1.0 2.0

0. 5

2m

2m 0 2. 0.5

1.0

1.0

1m

1m 1.0

3. 0

2.

8m

7m

6m

5m

4m

3m

2m

1m

0

0 8m

0

7m

6m

5m

4m

3m

2m

1m

0

ARNU24GCFA2/ARNU24GCFU2 Cooling

Heating

Discharge angle:45°

Discharge angle:60°

Air velocity [m/s]

Air velocity [m/s] 20

20

30

34

32

30

32

38

2.7m

36

2.7m 18

2m

34

30

2m

36

20

32

32

34

40

20 20

18

32

30

1m 20

7m

6m

5m

4m

3m

2m

1m

0

30

30

0 8m

1m

0 8m

Temperature [°C]

7m

6m

5m

4m

3m

2m

1m

0

Temperature [°C] 2.7m

1.0

0.5

1.0

2.7m

0.5

1.0

0.5 2. 0

2m

2m

0 3.

1m

1.0

1m

2. 0

2.0

3.0

1.0

5 0.

0 1.

1.0

2.0

0 2.

0.

0 8m

7m

6m

5m

16 _ Floor Standing

4m

3m

2m

1m

0

8m

7m

6m

5m

4m

3m

2m

1m

40

0

0


8. Electric Characteristics Units Model

Hz

Volts Voltage Range MCA

CE CE CE

MAX.264 50

220-240

60

220

MIN.198

CE CF CF CE CE CE

MAX.242 MIN.198

CE CF CF

0.22 0.22 0.22 0.22 0.22 0.22 0.22 0.22 0.55 0.55 0.55 0.55 0.22 0.22 0.22 0.22 0.22 0.22 0.22 0.22 0.55 0.55 0.55 0.55

IFM

Input(W)

MFA

kW

FLA

15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.076 0.076 0.076 0.076 0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.076 0.076 0.076 0.076

0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.44 0.44 0.44 0.44 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.44 0.44 0.44 0.44

Cooling Heating 30 30 30 30 30 30 30 30 80 80 80 80 30 30 30 30 30 30 30 30 80 80 80 80

30 30 30 30 30 30 30 30 80 80 80 80 30 30 30 30 30 30 30 30 80 80 80 80

Symbols: MCA: Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA. 5. Instead of fuse, use Circuit Breaker.

Floor Standing _ 17

Indoor Units

ARNU07GCEA2 ARNU07GCEU2 ARNU09GCEA2 ARNU09GCEU2 ARNU12GCEA2 ARNU12GCEU2 ARNU15GCEA2 ARNU15GCEU2 ARNU18GCFA2 ARNU18GCFU2 ARNU24GCFA2 ARNU24GCFU2 ARNU07GCEA2 ARNU07GCEU2 ARNU09GCEA2 ARNU09GCEU2 ARNU12GCEA2 ARNU12GCEU2 ARNU15GCEA2 ARNU15GCEU2 ARNU18GCFA2 ARNU18GCFU2 ARNU24GCFA2 ARNU24GCFU2

Type

Power Supply


9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Microphone

With Case

1.5m

E

Du

1.5m Model ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2

Sound Levels dB(A) H L M 35 33 31 36 34 32 37 35 33 38 37 35 40 37 34 43 40 37

Sound Pressure Level ARNU07GCEA2 ARNU07GCEU2

ARNU09GCEA2 ARNU09GCEU2 70

NC-65 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

20

10

NC-25 Approximate Hearing Threshold 63

125

250

500

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 1000 2000 4000 8000

10

63

NC-60

250

500

NC-50

NC-40

NC-30

NC-15 1000 2000 4000 8000

10

NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25

63

NC-60

125

250

500

Octave Band Center Frequency (Hz)

18 _ Floor Standing

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 1000 2000 4000 8000

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

70

Octave Band Sound Pressure Level (dB re 20μPa )

70

10

125

250

500

1000

2000

4000

500

1000 2000

NC-15 4000 8000

NC-15 8000

Octave Band Center Frequency (Hz)

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

125

250

ARNU24GCFA2 ARNU24GCFU2

ARNU18GCFA2 ARNU18GCFU2

70

Approximate Hearing Threshold

NC-20

Octave Band Center Frequency (Hz)

80

20

NC-25 Approximate Hearing Threshold 63

80

30

NC-35

30

80

40

NC-45

40

Octave Band Center Frequency (Hz)

ARNU15GCEA2 ARNU15GCEU2

50

NC-55

50

NC-20

125

NC-65

60

20

NC-25 Approximate Hearing Threshold

Octave Band Center Frequency (Hz)

60

ARNU12GCEA2 ARNU12GCEU2

80

Octave Band Sound Pressure Level (dB re 20μPa )

70

Octave Band Sound Pressure Level (dB re 20μPa )

80

Octave Band Sound Pressure Level (dB re 20μPa )

80

60

Octave Band Sound Pressure Level (dB re 20μPa )

Indoor Units

ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2

(Fie

10

NC-25 Approximate Hearing Threshold 63

NC-20

125

250

500

1000

2000

4000

NC-15 8000

Octave Band Center Frequency (Hz)


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

10.1 Features

[CEA/CFA Type]

Control panel

Air Outlet Remote Controller Control panel TEMP

Remote Controller

Indoor Units

Air Filter Air Inlet

[CEU/CFU Type]

Air Inlet Air filter (At Air Inlet)

Floor Standing _ 19


10. Installation 10.2 Selection of the best location Indoor unit Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unitʼs weight. • Sufficient space should be available to inspect the unit as in the figure shown on the right.

Window

• The place where the unit is installed shall be leveled. • The place shall be suitable for easy connection of the indoor unit with the outdoor unit.

• The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit

Service space Select an installation site where the following conditions are satisfied and that meets your customer's approval. • Where the floor is strong enough to bear the indoor unit weight. • Where the floor is not significantly inclined. • Where nothing blocks the air passage.

20 or more

Air flow direction Front side

100 or more

175 or more

100 or more

1000 or more

Air inlet direction

• Where condensate can be properly drained. Base

• Where sufficient clearance for installation and maintenance can be ensured. • Where there is no possibility of flammable gas leakage. • Where optimum air distribution can be ensured. • Where piping between indoor and outdoor units is possible within the allowable limit (Refer to the installation manual of the outdoor unit.) 80 or more

• Keep the indoor and outdoor unit, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static.(Depending on the type and source of the electrical waves, static may be heard even when more than 1 m away.)

Window

654

Indoor Units

• The place where the unit is installed should not be affected by electrical noise.

Ma

Ao

(Unit: mm) Type

A

B

CEU Type

788

1080

CFU Type

1066

1358

20 _ Floor Standing

inte

[IMPORTANT] Leave sufficient clearance for air inlet and maintenance.

nan

ce

are

rm ore Bo rm ore

a


10. Installation Bolt pitch A

• Positioning of holes for fastening to the wall

A

CEA, CEU CFA, CFU

858 1136

Indoor Units

1. Use the Installation mount for installation. Check whether the wall is strong enough to bear the weight of the unit or not. if there is a risk, reinforce the wall before installing the unit. 2. The unit requires a minimum 100 mm clearance below the unit for air intake. Also, ensure the unit is leveled when installed so that drainage flows smoothly. If inclined, water can leak. 3. Depending upon the shape and nature of the wall surface, operating sound may become bigger.

270

Type

198

(Unit:mm)

How to open/close front panel

(1)

• How to open/close the front panel

(2)

(1) Open the lid of control panel(Both left and right) (2) Remove screws(Both left and right) (3) Lift the front panel of the unit • To close, perform the procedure in opposite order.

(3)

(2)

(1)

Floor Standing _ 21


10. Installation 10.3 Drain piping work • Drain piping must have downward slope(1/50 to 1/100): be sure not to provide up-and-down slope to prevent reverse flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection to the indoor unit is 21mm. Piping material: Polyvinyl chloride pipe 25mm and pipe fittings • Be sure to install heat insulation on the drain piping

Indoor Units

Heat insulation material: Polyethylene foam with thickness more than 10 mm. • If converging multiple drain pipes, install according to the procedure shown below.

Slope downwards at a gradient of at least 1/100 • After piping work is finished, check for drainage. • Be sure to insulate all indoor units.

10.4 How to connect wirings Remove the electric parts Box cover and connect the wiring

Fasten with clamp

Fasten with accessory clamp

Power Supply wiring ground wiring (Field wiring)

22 _ Floor Standing

Power supply wiring ground wiring Transmission wiring (Field wiring)

Transmission wiring


10. Installation 10.5 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

SODU A

IDU B

IDU A

INT B

INT A

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model]

1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING : Make sure that the screws of the terminal are free from looseness. CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have a separate power circuit specifically for the air conditioner. As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness.) 7) In a wet or moist area, always install an earth leakage circuit breaker. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.

Floor Standing _ 23

Indoor Units

Terminal Block Indoor


10. Installations WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys.

Indoor Units

- Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

24 _ Floor Standing


11. Accessories Standard Accessories Name

Dran hose

Level adjustment screw

Insulation for fitting

Clamp (Tie Wrap)

Quantity

1 EA

4

1 each.

8 pcs.

(1) For gas pipe Shape

[Other]

• Operation manual • Installation manual

(2) For liquid pipe

Indoor Units

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Floor Standing _ 25


Indoor unit Console 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Ion Generator Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GQAA2, ARNU09GQAA2, ARNU12GQAA2 ARNU15GQAA2 2 Manual Auto X O 4/5/4 X O O X X O O X X X X O O O O X O O O O O O O O O Accessory X X X X Accessory X X X

Indoor Units

Installation

Function

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Console _ 1


2. Specification Type Model Cooling Capacity

Heating Capacity

Casing Dimensions (W x D x H)

Body Front Panel

Coil

Indoor Units

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

Console Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch mm inch m3 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Safety Device Pipe Liquid Side mm(inch) Connections Gas Side mm(inch) Drain(OD/ID) mm Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Ø, V, Hz Refrigerant Control Power cable mm2(CV) Transmission Cable mm2(VCTF-SB)

ARNU07GQAA2 2.2 1,900 7,500 2.5 2,200 8,500 Galvanized Steel Plate 600 x 700 x 210 23.62 x 27.56 x 8.27 19 x 2 x 19 Turbo fan 48 x 1 0.3 6.7 / 5.9 / 4.8 236 / 209 / 170 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 17/12.2 14.0(30.9) 37 / 34 / 28 1, 220 - 240, 50 EEV 1.5 x 3C 1.0 ~ 1.5 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Console

ARNU09GQAA2 2.8 2,400 9,600 3.2 2,800 10,900 Galvanized Steel Plate 600 x 700 x 210 23.62 x 27.56 x 8.27 19 x 2 x 19 Turbo fan 48 x 1 0.3 6.7 / 5.9 / 4.8 236 / 209 / 170 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 17/12.2 14.0(30.9) 37 / 34 / 28 1, 220 - 240, 50 EEV 1.5 x 3C 1.0 ~ 1.5 x 2C Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specification Type Model Cooling Capacity

Heating Capacity

Casing Dimensions (W x D x H)

Body Front Panel

Coil Fan

mm inch mm inch m3 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Safety Device Pipe Liquid Side mm(inch) Connections Gas Side mm(inch) Drain(OD/ID) mm Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Ø, V, Hz Refrigerant Control Power cable mm2(CV) Transmission Cable mm2(VCTF-SB)

ARNU12GQAA2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 600 x 700 x 210 23.62 x 27.56 x 8.27 19 x 2 x 19 Turbo fan 48 x 1 0.3 7.5 / 5.9 / 4.8 265 / 209 / 170 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 17/12.2 14.0(30.9) 39 / 34 / 28 1, 220 - 240, 50 EEV 1.5 x 3C 1.0 ~ 1.5 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

ARNU15GQAA2 4.5 3,900 15,400 5.0 4,300 17,100 Galvanized Steel Plate 600 x 700 x 210 23.62 x 27.56 x 8.37 19 x 2 x 19 Turbo fan 48 x 1 0.3 8.7 / 6.7 / 5.9 307 / 236 / 209 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 17/12.2 14.0(30.9) 42 / 37 / 31 1, 220 - 240, 50 EEV 1.5 x 3C 1.0 ~ 1.5 x 2C Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Console _ 3

Indoor Units

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)

Console Unit kW kcal/h Btu/h kW kcal/h Btu/h


82.5

18

95

6

160

4 _ Console 600 80 37 100

639

700

666

3

68.5 37

1

6

5

4

150

2

No. 1 2 3 4 5 6

Indoor Units

Part Name Liquid pipe connection Gas pipe connection Drain pipe connection Display & signal receiver Air discharge grill Air suction grill

CHASSIS CODE: QA

Remark Ø6.35 Ø12.7

ARNU07GQAA2 ARNU09GQAA2 ARNU12GQAA2 ARNU15GQAA2

Console

3. Dimensions

140 120

45

210

80

90

125

584


4. Piping Diagrams

Heat Exchanger

:Cooling :Heating

EEV Filter

Th3

Th2 Turbo Fan

Filter

lndoor unit

Th1

[Unit: mm(inch)]

Model

Gas

Liquid

ARNU07GQAA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GQAA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GQAA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GQAA2

Ø12.7(1/2)

Ø6.35(1/4)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Console _ 5

Indoor Units

Refrigerant pipe connection port diameter


5. Wiring Diagrams

Indoor Units

QA Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

6 _ Console


6. Capacity Tables 6.1 Cooling Capacity

Capacity Index

2.8

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

10

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.8

1.6

12

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.8

1.6

14

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.8

1.6

16

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.7

1.6

18

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.7

1.6

20

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.7

1.6

21

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.7

1.6

23

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.5

1.5

2.6

1.5

25

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.5

1.5

2.6

1.5

27

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.5

1.5

2.6

1.5

29

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.5

1.4

2.5

1.5

31

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.4

2.5

1.4

33

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.4

2.4

1.4

35

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.4

2.4

1.4

37

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.2

1.6

2.3

1.4

2.4

1.4

39

1.5

1.3

1.8

1.4

2.1

1.6

2.1

1.5

2.2

1.5

2.3

1.3

2.3

1.4

42

1.5

1.3

1.8

1.4

2.1

1.6

2.1

1.5

2.2

1.5

2.2

1.3

2.3

1.3

44

1.5

1.3

1.8

1.4

2.0

1.5

2.1

1.5

2.1

1.5

2.2

1.3

2.2

1.3

46

1.5

1.3

1.8

1.4

1.9

1.5

2.0

1.4

2.0

1.4

2.0

1.2

2.0

1.2

10

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.6

2.1

12

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.6

2.0

14

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.5

2.0

16

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.5

2.0

18

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.5

2.0

20

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.4

2.0

21

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.4

2.0

23

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.2

1.9

3.3

1.9

25

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.2

1.8

3.3

1.9

27

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.2

1.8

3.3

1.9

29

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.1

1.8

3.2

1.8

31

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

2.9

2.0

3.1

1.8

3.2

1.8

33

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

2.9

2.0

3.0

1.8

3.1

1.8

35

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

2.9

2.0

3.0

1.7

3.1

1.8

37

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

2.8

2.0

2.9

1.7

3.0

1.7

39

1.9

1.6

2.3

1.8

2.6

2.0

2.7

1.9

2.8

1.9

2.9

1.7

3.0

1.7

42

1.9

1.6

2.3

1.8

2.6

2.0

2.7

1.9

2.8

1.9

2.8

1.6

2.9

1.7

44

1.9

1.6

2.3

1.8

2.6

1.9

2.7

1.9

2.7

1.9

2.8

1.6

2.9

1.6

46

1.9

1.6

2.3

1.8

2.5

1.8

2.5

1.8

2.5

1.7

2.6

1.5

2.6

1.5

Outdoor air temp. (DB, °C)

Notes: TC: Total Capacity(kW)

30 22 TC SHC kW kW

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Console _ 7

Indoor Units

2.2

Cooling capacity


6. Capacity Tables Cooling capacity

Indoor Units

Capacity Index

3.6

4.5

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

10

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.3

2.5

4.6

2.7

12

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.3

2.5

4.6

2.7

14

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.3

2.5

4.5

2.6

16

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.3

2.5

4.5

2.6

18

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.3

2.5

4.4

2.6

20

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.2

2.5

4.4

2.6

21

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.2

2.4

4.4

2.5

23

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.1

2.4

4.3

2.5

25

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.1

2.4

4.2

2.5

27

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.1

2.4

4.2

2.4

29

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.0

2.3

4.1

2.4

31

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.6

4.0

2.3

4.1

2.4

33

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.7

2.6

3.9

2.3

4.0

2.3

35

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.7

2.6

3.9

2.2

3.9

2.3

37

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.7

2.5

3.8

2.2

3.9

2.3

39

2.4

2.1

2.9

2.4

3.4

2.6

3.5

2.5

3.6

2.5

3.7

2.2

3.8

2.2

42

2.4

2.1

2.9

2.4

3.4

2.5

3.5

2.5

3.5

2.5

3.6

2.1

3.7

2.2

44

2.4

2.1

2.9

2.4

3.3

2.5

3.4

2.5

3.5

2.4

3.6

2.1

3.7

2.1

46

2.4

2.1

2.9

2.4

3.2

2.4

3.2

2.3

3.3

2.3

3.3

1.9

3.3

1.9

10

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.4

3.1

5.8

3.4

12

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.4

3.1

5.7

3.3

14

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.4

3.1

5.7

3.3

16

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.4

3.1

5.6

3.3

18

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.3

3.1

5.6

3.2

20

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.3

3.1

5.5

3.2

21

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.2

3.1

5.5

3.2

23

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.2

3.0

5.4

3.1

25

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.1

3.0

5.3

3.1

27

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.1

3.0

5.2

3.1

29

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.0

2.9

5.2

3.0

31

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.7

3.3

5.0

2.9

5.1

3.0

33

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.7

3.3

4.9

2.9

5.0

2.9

35

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.6

3.2

4.8

2.8

4.9

2.9

37

3.0

2.7

3.6

2.9

4.2

3.2

4.4

3.2

4.6

3.2

4.7

2.8

4.8

2.8

39

3.0

2.7

3.6

2.9

4.2

3.2

4.4

3.2

4.5

3.1

4.7

2.7

4.8

2.8

42

3.0

2.7

3.6

2.9

4.2

3.2

4.3

3.1

4.4

3.1

4.5

2.7

4.7

2.7

44

3.0

2.7

3.6

2.9

4.1

3.1

4.3

3.1

4.4

3.0

4.5

2.6

4.6

2.7

46

3.0

2.7

3.6

2.9

4.0

3.0

4.0

2.9

4.1

2.8

4.1

2.4

4.2

2.4

Outdoor air temp. (DB, °C)

Notes: TC: Total Capacity(kW)

8 _ Console

SHC: Sensible Heat Capacity(kW)

30 22 TC SHC kW kW

32 24 TC SHC kW kW


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

2.2

3.6

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.5 2.5 2.6 2.7 2.8 2.8 2.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.3 3.4 3.5 3.6 3.6 3.6 2.4 2.5 2.6 2.8 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.1 4.2 4.3 4.5 4.5 4.5

1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.5 2.5 2.6 2.7 2.7 2.7 2.7 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.3 3.4 3.4 3.4 3.4 3.4 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.1 4.2 4.3 4.3 4.3 4.3

1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9

1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.4 2.4 2.6 2.7 2.9 3.0 3.1 3.1 3.3 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Notes: TC: Total Capacity(kW)

Console _ 9

Indoor Units

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Heating capacity


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor Units

4.5

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Notes: TC: Total Capacity(kW)

10 _ Console

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

3.0 3.1 3.3 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.7 4.9 5.1 5.3 5.4 5.6 5.6 5.6

3.0 3.1 3.3 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.7 4.9 5.1 5.2 5.3 5.3 5.3 5.3

3.0 3.1 3.3 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0

3.0 3.1 3.2 3.4 3.6 3.8 3.9 3.9 4.1 4.3 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.0 3.1 3.2 3.4 3.6 3.8 3.9 3.9 4.1 4.2 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7

3.0 3.1 3.2 3.4 3.6 3.8 3.8 3.9 4.1 4.2 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4


7. Air Velocity and Temperature Distribution(Reference Data) ARNU07GQAA2 Cooling

Heating

Discharge angle:40°

Discharge angle:50°

Air velocity [m/s]

2.7m

Air velocity [m/s]

0.3

0.5

2 0.

0.4

2.7m

0.2

1.0

0.2

0.4

0.1

0.5

0.3

1.0

0.2

0.1

2m 0.3

0.4

2m 0.2

1.0

0.1

0.1

0.3

0. 3

0.5 0.2 0.2 1.0

0.1

1m

3

5m

0.2

0.3

4m

3m

2m

0.2

0.2

0.2

0.3

0.4

0.2

0.2

0.5

1.5

0.2

0

1m

0

Temperature [°C]

5m

2.7m

0.2 0.5

0.

0.1

0.2

0.1

0.3

0.1

1m

1.0

0.1

0.4

0.2

1.5

4m

3m

2m

2.0

0.2

0

1m

0

Temperature [°C]

2.7m

36.7

36.6

36.7

.7

13.4

36

13.4

13.8

13.4

36.7 36.6 36.7

13.8

36.6

13.8

36

.6

36.6

12.2

13

36.7

11.5

13.9

13.8

13.8

36

.4

.7

36

.6

13 .8 11.3

4m

3m

2m

39.0

0 5m

0

1m

36.7

.6

5m

13.4

.8

36

13

13.4

1m

39.0 39.0 6.6 36.6 3

.8

36.6

36.6

1m 13

13.9

4m

3m

2m

0

1m

0

ARNU09GQAA2 Cooling

Heating

Discharge angle:40°

Discharge angle:50°

Air velocity [m/s] 0.3

2.7m

Air velocity [m/s]

2.7m

0.3

0.2

0.3

0. 2

0.3

0.2

0.5 0.5

0.3

0.3

0.2

03 0.3

0.2

0.3

0.2

2 0.

0.3

2.5

0.3

0.2

0.2

0.5

1m

2 0. 0.2

5m

4m

1.5

0.3

0.2

3m

2m

0.2

1m

0

.5 14

0.3

02

5m

2.7m

13.5

13.5

0.2

0

Temperature [°C] 13.9

0.2

0. 2

0.2

0. 2

0.3

0.2

0.2

0.2

0.2

0.2

0.2

4m

3m

2m

0.5

1m

.2

39.2

2.7m

39.9

40.6

40.6

13.5

13.9

0 0

Temperature [°C] 39

1m

0.2 0.2

0.2

0.3

2 0.

2 0.

0.3

0.2

0.2

0.2

2m

0.2

0.3

0.2

0.3

0.3

2m

0.5

0.3

0.2

0.3

0.2

0.2

40.6

2m

4

0.0

39.2 40.6

39.9

13.9

40.0

14.5

2m 14.5

39.9 13.9

14

13

.0

12.0

4m

3m

2m

1m

39.9

13.9

13.9

13.5

.5 13.5

40

40.6

40.0

.6

39.2

0 0

5m

4m

1m

39.9 43.0

9 9.

3m

.9

3

40

13

5m

39.9

39

14.5

43.0

1m

13.912.0

.9

.5

13.9

12.0

13.9

2m

43.0

1m

40.0

0 0

Console _ 11

Indoor Units

13.4

2m

2m


7. Air Velocity and Temperature Distribution(Reference Data) ARNU12GQAA2 Cooling

Heating

Discharge angle:40°

Discharge angle:50°

Air velocity [m/s] 0.2

2.7m

0.5

Air velocity [m/s]

0. 2

2.7m 0.4

2 0.

0.4

0.5

0.5

0.4

0.4

0.5

0.2

0.3

0.2

2m

0.4

0.4

0.2

0.4

0.2 0.2

0.3

0.5

0.5

0.2

0.2

0.2

1.3 0.3

2.2

0. 2

0.2

4m

3m

2m

1m

12.1

5m

2.7m

4m

3m

2m

0.2

0.2

0.2

0.4

0 0

0.4

0

Temperature [°C] 42.6

42.5

2.7m

43.3

13

42.5

13.5

13.5

13

42

.8

2m

42.8

42

42.5

.8

.5

43.3

2m

42.5

13

43.3

.5

11.5

13.5

42.5

1m

11.5

42.6

46.3

1m

46.3

42.5

.6

.5 13

.5

43.3

13.5

13.6

4m

3m

2m

42.5

43.3

.6

.5

13

13

5m

11.5

13

13

13.5

13.6

42.6

Indoor Units

42.5

43.3

13.6

0

1m

.5

13.5

13.6

0.2 0.2 0.4

1.3

Temperature [°C] 13.6

0.2

0.2

0.2 0.2

0.2

5m

0.2

0.2

0.2

0.5

1m

0.4

0.2

2 0.

2 0.

0.2

1m

0.3 0.5

0.4

0.5

0.2

2m 0.2

0.3

0.2

0.3

0.2

0.2

42.5

0 5m

0

1m

42.8

4m

3m

2m

43

.3

0

1m

0

ARNU15GQAA2 Cooling

Heating Discharge angle:50°

Air velocity [m/s]

2.7m

0.2

0.4

Air velocity [m/s] 0.2

0.3

0. 2 0.3

0.4

0.2

0.2

0.6

2.7m

1.0

0.4

0.4

1.0

Discharge angle:40°

0.6

0.2

0.2

0.2

3.6

1.9

2 0.

0.3 2 0. 0.3

0.3

0.3

0.3

1m

0

2.7m

3m

2m

0.2

0.6

03

0

1m

0

Temperature [°C] 41.0

41.0

2.7m

14.3

40

.8

41.0

.0

14.1

4m

0.2

0.6

41

14.3

14.1

5m

0.2

0.3

0.3

0.6

0

Temperature [°C] 14.3

0.3

1.9

2 0.

2m

1m

0.3

0.3

0.2 0 0.2 .2

3m

1.0

1.0

0.3

0.2

0.4

0.2 0.2

0.2

0.6

0.2 0.2 1.9

4m

0.3 0.2

1m

0.4

0.4

5m

0.6

0.3

0.4

0.3

0.2

0.2

2m 1.0

0.4

0.3

0.4

0.4

1.0

0.2 0.2

0.6

0.2

2m

41.0

41.0

2m

2m

14.1

41.0

14.1

14.3

.8

1m

41

.1 14

14.3

12 _ Console

3m

2m

1m

40.9

14.3

12.4

0

40

.8

.8

4m

40.8

41.0

40

5m

40.8 43.8

14.3

14.1

1m

41.0

40.8 41.0

.0

14.3

40.8

12.4 .3 14

14.2

40

.0

.8

41 40.9

12.4

43

14.3

.9

14.2

.2

.3

41.0

14 14

40

.1

14.1

14

41.0

0

0 5m

4m

3m

2m

1m

0


8. Electric Characteristicss Units Model

Type

ARNU07GQAA2

QA

ARNU09GQAA2

QA

Power Supply Hz

50

Volts

220-240

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

0.13

15

0.048

0.10

30

30

Min.:198,

0.13

15

0.048

0.10

30

30

Max.:264

0.13

15

0.048

0.10

30

30

ARNU12GQAA2

QA

ARNU15GQAA2

QA

0.13

15

0.048

0.10

30

30

ARNU07GQAA2

QA

0.13

15

0.048

0.10

30

30

ARNU09GQAA2

QA

Min.:198,

0.13

15

0.048

0.10

30

30

ARNU12GQAA2

QA

Max.:264

0.13

15

0.048

0.10

30

30

ARNU15GQAA2

QA

0.13

15

0.048

0.10

30

30

60

220

Symbols:

Indoor Units

MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.

Console _ 13


9. Sound Levels Overall Notes: - Data is valid at nominal operation condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard.

1m 1m

Microphone

Sound Pressure Level Sound Levels dB(A) H

M

L

ARNU07GQAA2

37

34

28

ARNU09GQAA2

37

34

28

ARNU12GQAA2

39

34

28

ARNU15GQAA2

42

37

31

ARNU09GQAA2

ARNU12GQAA2

80

80

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

63

NC-60 50

NC-50

250

500

1000

2000

4000

NC-45

40

NC-40 NC-35

30

NC-30

NC-20

125

NC-55

20

NC-25 Approximate Hearing Threshold

NC-65

60

NC-15 8000

10

NC-25 Approximate Hearing Threshold 63

125

250

500

1000

2000

4000

NC-15 8000

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

125

250

500

1000

2000

4000

NC-15 8000

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

Octave Band Center Frequency (Hz)

14 _ Console

Octave Band Sound Pressure Level (dB re 20μPa )

80

10

NC-25 Approximate Hearing Threshold 63

NC-60

NC-20

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

NC-20

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

ARNU15GQAA2 80

NC-65

60

NC-20

Octave Band Center Frequency (Hz)

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20μPa )

80

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU07GQAA2

Octave Band Sound Pressure Level (dB re 20μPa )

Indoor Units

Model

NC-15 8000

NC-15 8000


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

10.1 Selection of the Best Location

More than 300 More than 300

More than 300

250 or below from the Floor

(Unit : mm)

In case that the unit is installed near the sea, the installation parts may be corroded by salt. The installation parts (and the unit) should be taken appropriate anti-corrosion measures.

Console _ 15

Indoor Units

• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have the maintenance space.


10. Installation 10.2 Indoor unit installation 1. Preparation / Removing front panel 1. Open the front grille by pulling forward

2. Then pull out the link of grille from groove in front panel. 3. Then pull out 2 hinges of grille from grooves in front panel.

Indoor Units

4. Then remove 4 screws, dismount the front panel while pulling it forward.

2. Preparation / For Moldings , Side Piping, and Concealed Installation 2-1 For Moldings 1. Remove the slit portions on the Rear Panel.

Remove

Upper Deco cover

Side Deco cover

2-2 For Concealed Installation 1. Remove the 6 screws. 2. Remove the Upper Deco cover. 3. Remove the Side Deco covers.

2-3 For Side Piping (Reference 2-2.) 1. Remove the Deco Covers. 2. Remove the slit portions 3. Assemble the Deco Covers.

16 _ Console


10. Installation 3. Refrigerant Piping 1. The location of hole is different depending on which side of the pipe is taken out. 2. Drill a hole(Ă˜70mm) in the point indicated by

symbol in the illustration as below

Left bottom piping

60

45

Wall

90

75

Right bottom piping

40 Right back piping

Right back piping

Indoor Units

50

75

45

90

45

Left back piping

Left/right piping

(Unit : mm)

NOTICE - The suggested shortest pipe length is 5m,in order to avoid noise from the outdoor unit and vibration.

4. Installing Indoor unit 4-1 Installation on the Floor. 1. Fix up using 6 screws for floor installation. (700)

26

64

180

159

(600)

140 170

574

140

647

0

170

21

30.5 0

6 screw (M4*25L)

16

30.5

(Unit : mm)

Console _ 17


10. Installation 4-2 Installation on the Wall 1. Fix up the installation plate using 5 screws and the indoor unit using 4 screws. 2. The installation plate should be fixed on a wall which can support the weight of the indoor unit.

Indoor Units

Installation Plate

Molding

4 screw (M4*25L)

4-3 Half concealed installation. 1. Make a wall hole of the size shown Fig-1. 45

Wall

670

Supplemental plate (Field supply)

95

Supplemental plate (Field supply)

Hole

200

200

150

150

585

(Unit : mm)

<Fig - 1>

18 _ Console

1) Normal concealed

2) Deep concealed


10. Installation 2. Installation of supplemental plate for attaching main unit • The rear of the unit can be fixed with screws at the points shown in the Fig-2.Be sure to install the supplemental plate in accordance with the depth of the inner wall.

647

140

140

170

170 (Unit : mm)

Indoor Units

<Fig - 2>

3.Piping Hole Wall

Right bottom Piping 35

50

Left bottom Piping

Left Piping 45

Wall

75

75

50

(Unit : mm)

4. Remove the Deco Covers and Fixing Indoor Unit 1) Remove the Deco Covers. 2) Insert the Indoor Unit to the Wall hole. 3) Secure using 6 screws. (shown in the illustration)

Console _ 19


10. Installation NOTICE - Check the horizon of Indoor unit with the wall. Please use the Leveler on the drain pan guide.

Leveler

Drain pan

Indoor Units

Less than 5mm

Less than 5mm

20 _ Console

Less than 5mm


10. Installation 10.3 Connecting the Piping When you connect the refrigerant pipe, it is easier that you connect the gas pipe first. 1. Hold up the Sensor Link. 2. Separate the Pipe Bracket (2 screws) 3. Connect the refrigerant pipe. (Refer to next page) 4. Assemble the Pipe Bracket (2 screws) 5. Put down the Sensor Link 2

4

5

3

Indoor Units

1

6. After connecting, check the pipe arrangement as per illustration. 7. The piping can be arranged in six ways as shown in the illustration below. 6

7

Pipe Guide

8

3 Connecting Pipe

2 1 Pipe Guide Connecting Pipe must be placed inner than the pipe guide.

4

6 5

In case of âž‚ ~ âž… , The pipe bending can be used in hand-operated bending machine. Make a pipe of the shape shown pic 8.

Console _ 21


10. Installation If the drain hose is routed inside the room insulate the hose with an insulation material* so that dripping from sweating (condensation) will not damage furniture or floors. * Foamed polyethylene or equivalent is recommended.

Tape Connecting cable Drain hose Connecting pipe

Connecting the installation pipe and drain hose to the indoor unit.

Indoor Units

1. Align the center of the pipes and sufficiently tighten the flare nut by hand.

Indoor unit tubing

Flare nut

Pipes

2. Tighten the flare nut with a wrench Outside diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Ø19.05 3/4

Torque kgf.m 1.8~2.5 3.4~4.2 5.5~6.5 6.3~8.2 9.9~12.1

3. When needed to extend the drain hose of indoor unit, assembly the drain pipe as shown on the drawing

Open-end wrench (fixed) Flare nut Wrench

Connection pipe

Indoor unit tubing

Drain pipe

Indoor unit drain hose Adhesive

Wrap the insulation material around the connecting portion. 1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap. 2. Wrap the area which accommodates the rear piping housing section with vinyl tape.

Vinyl tape(narrow)

Insulation material

Indoor unit pipe

Connection pipe

Wrap with vinyl tape Vinyl tape (wide) Connecting cable Pipe

3. Bundle the piping and drain hose together by wrapping them with vinyl tape sufficient enough to cover where they fit into the rear piping housing section.

Vinyl tape(narrow) Wrap with vinyl tape Pipe

Vinyl tape(wide) Drain hose

22 _ Console


10. Installation 10.4 Wiring Connection • Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model] Terminal block of indoor unit 1(L)

2(N)

3(A)

SODU B

SODU A

IDU B

IDU A

INT B

INT A

4(B)

Indoor power input 220V 60Hz

[Except Multi VIII Heat Pump Model] Terminal block of outdoor unit

1(L)

2(N)

3(A)

4(B)

Outdoor unit Indoor unit

Central controller

Indoor Units

Terminal block of indoor unit

SODU SODU IDU IDU INTERNET DRY1 DRY2 GND 12V

Indoor power input 220V 60Hz

Make sure that the screws of the terminal are free from looseness.

After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.

Console _ 23


10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys.

Indoor Units

- Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

24 _ Console


11. Accessories Standard Accessories Name

Drain Hose

Install Plate

Clamp (Tie wrap)

Quantity

1 EA

1 EA

4 EA

Shape

Other

- Allergy Filter - Fixing screw for installation Plate 4*25 mm-5EA - Wood screw for indoor fixation -6EA - Owner's Manual - Installation Manual

Indoor Units

Console _ 25


Indoor unit Fresh Air Intake Unit 1. List of functions 2. Specifications 3. Dimensions & Gravity point 4. Piping Diagrams 5. Wiring Diagrams 6. Outlet temperature, expected capacity and air flow 7. External Static Pressure(E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Operation range 11. Installation 12. Accessories


1. List of functions Category

Air flow

Air purifying

Indoor Units

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Standard wired remote controller Wide Character wired remote controller Picto wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU48GBRZ2, URNU76GB8Z2,URNU96GB8Z2 1 2/2/2 X X O O O X O O O X O(only heat pump or cooling only) O O O X O O X Accessory Accessory Accessory Accessory Accessory X Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

1 _ Fresh Air Intake Unit


2. Specifications Type Model

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Notes:1. Capacities are based on the following conditions: Cooling • Outdoor temp. 33°C[91.4°F]DB/ 28°C[82.4°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Outdoor temp. 0°C[32°F]DB/ -2.9°C[26.78°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. Indoor Unit Connection No 1 2

Connection Condition Fresh Air Intake Units only are connected with outdoor units Mixture connection with general Indoor unit and Fresh Intake Unit

URNU96GB8Z2 28 24,100 95,900 26.7 23,000 91,360 Galvanized Steel Plate 1562 x 688 x 460 61.5 x 27.1 x 18.1 3 x 20 x 19 0.59 Sirocco Fan 375 x 1 2.15 35.7/23.7/23.7 1261/837/837 22 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Long Life Filter Fuse Ø9.52(3/8) Ø22.2(7/8) 25 73(161) 50/48/48 1, 220 - 240, 50 1, 220, 60 EEV CV1.5 x 3C VCTF-SB 1.0 ~ 1.5 x 2C

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Combination 1) The total capacity of Fresh Air Intake Unit should be 50~100% of outdoor unit. 2) The max quantity of Fresh Air Intake unit is 2 Units. 1) The total capacity of indoor units (standard Indoor Unit + Fresh Air Intake Unit) should be 50~100% of outdoor unit. 2) The total capacity of Fresh Air Intake Unit should be less than 30% of the total capacity of indoor units.

6. EEV : Electronic Expansion Valve 7. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dBA)

Fresh Air Intake Unit _ 2

Indoor Units

ARNU48GBRZ2 14.1 Cooling Capacity 12,100 48,100 13.5 Heating Capacity 11,620 46,115 Casing Galvanized Steel Plate mm 1230 x 590 x 380 Dimensions(WxDxH) Body inch 48.4 x 23.2 x 15 Rows x Columns x FPI 3 x 13 x 19 Coil Face Area m3 0.38 Type Sirocco Fan Motor Output x Number W 195 x 1 Running Current A 0.38 Air Flow Rate(H/M/L) CMM 18.8/14.7/14.7 Fan (High Mode-factory set) cfm 664/519/519 External Static Pressure mmAq(Pa) 18 Drive Direct Motor type BLDC Microprocessor, Temperature Control Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Air Filter Long Life Filter Safety Device Fuse Liquid Side mm(inch) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm 25 Net Weight kg(lbs) 45(99) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) 44/42/42 1, 220 - 240, 50 Power Supply Ø, V, Hz 1, 220, 60 Refrigerant Control EEV Power cable mm2 CV1.5 x 3C Transmission cable mm2 VCTF-SB1.0 ~ 1.5 x 2C

Fresh Air Intake Unit URNU76GB8Z2 22.4 19,300 76,400 21.4 18,410 73,080 Galvanized Steel Plate 1562 x 688 x 460 61.5 x 27.1 x 18.1 3 x 20 x 19 0.59 Sirocco Fan 375 x 1 1.36 23.7/13.2/13.2 837/446/446 22 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Long Life Filter Fuse Ø9.52(3/8) Ø19.05(3/4) 25 73(161) 49/47/47 1, 220 - 240, 50 1, 220, 60 EEV CV1.5 x 3C VCTF-SB 1.0 ~ 1.5 x 2C


R6

0

60

198

312

380

25

303

32

140

590

50

185

168

241

5

621

6

279

1,230

118 1,004

1,284 1,230

1,092

120

114

4

477 590

2

90

1

135 190 260

115

101 83

Name

Air discharge Air suction

4 5 6

Unit size(48k):ø25

Unit size(48k):ø15.88

Unit size(48k):ø9.52

Descripition

(unit : mm)

Gravity point

CHASSIS CODE: BR

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Power supply connection

3

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

3

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

1

Number 26

ARNU48GBRZ2

Fresh Air Intake Unit

72 123 221 122 144

3 _ Fresh Air Intake Unit 56

Indoor Units

3. Dimensions & Gravity point

302


Fresh Air Intake Unit _ 4

460

460

688

293

5

329

819

6

1,562

1,220

1,562

688 30

1,622

115

560 64

290 161

20

440

318

1,396

358

68

18

109

58

122 60 70 64

397

Air discharge Air suction

6

Gravity point

CHASSIS CODE: B8

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Unit size(76k):ø19.05 Unit size(96k):ø22.2

Unit size(76k, 96k):ø19.05

Descripition

(unit : mm)

Drain pipe connection Unit size(76k, 96k): ø22.2 Power supply connection 5

4

3

Gas pipe connection

Name

2

3

Liquid pipe connection

0

1

Number

99 14

70 120

2

URNU76GB8Z2 URNU96GB8Z2

Fresh Air Intake Unit

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

1

Indoor Units

4

3. Dimensions & Gravity point


4. Piping Diagrams

Th4

EEV

Th3

Filter

Th2 Heat Exchanger Distributor

Th1

Filter

Filter

S

Capillary Tube

Solenoid Valve

Check Valve

Indoor Units

Fresh Air Intake Unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU48GBRZ2

Ø15.88(5/8)

Ø9.52(3/8)

URNU76GB8Z2

Ø19.05(6/8)

Ø9.52(3/8)

URNU96GB8Z2

Ø22.2(7/8)

Ø9.52(3/8)

LOC.

Description

Th1

Inlet Air Thermistor

Th2

Pipe In Thermistor

Th3

Pipe Out Thermistor

Th4

Outlet Air Thermistor

5 _ Fresh Air Intake Unit

Cooling Heating


5. Wiring Diagrams BR Chassis

Indoor Units

Accessory

B8 Chassis

Accessory

Fresh Air Intake Unit _ 6


6. Outlet temperature, expected capacity and air flow 6.1 Outlet Air Temperature ARNU48GBRZ2 Cooling DB 21 23 25 27 29 31 33 35 37 40

59 WB 15 WB CA SHC 4.7 3.5 4.6 4.1 4.6 4.5 -

63 WB 17 WB CA SHC 5.2 3.1 5.0 3.7 4.9 4.3 4.9 4.9 -

69 WB 20 WB CA SHC 7.8 3.6 7.7 4.2 6.9 4.8 6.6 5.4 6.3 6.1 -

73 WB 23 WB CA SHC 10.4 4.6 9.9 5.2 9.0 5.7 8.8 6.3 8.6 6.9 -

79 WB 26 WB CA SHC 12.9 4.6 12.5 5.2 12.2 5.8 11.8 6.4 11.0 6.9 10.6 7.9

82 WB 28 WB CA SHC 14.2 5.1 13.6 5.5 13.1 5.9 12.7 6.5 12.4 7.5

86 WB 30 WB CA SHC 15.2 4.7 14.9 5.3 14.3 5.9 13.9 6.8

90 WB 32.0 CA SHC 16.2 5.4 15.9 6.4

17.4

DB 21 23 25 27 29 31 33 35 37 40

59 WB 15 WB DB WB 11.8 9.9 11.9 10.0 12.0 10.1 -

63 WB 17 WB DB WB 12.7 11.8 13.0 12.0 13.3 12.0 13.8 12.0 -

69 WB 20 WB DB WB 13.5 12.7 13.7 12.8 14.0 13.5 14.2 13.8 14.3 14.0 -

73 WB 23 WB DB WB 14.7 14.0 14.8 14.4 15.5 15.2 15.7 15.3 15.8 15.5 -

79 WB 26 WB DB WB 16.7 15.7 16.9 16.0 17.2 16.2 17.5 16.5 17.7 17.2 17.9 17.5

82 WB 28 WB DB WB 17.5 17.4 18.2 17.9 18.9 18.2 19.2 18.5 19.5 18.7

86 WB 30 WB WB DB 20.5 19.5 20.7 19.7 20.9 20.1 21.2 20.3

90 WB 32.0 DB WB 22.5 21.6 22.5 21.7

95 WB 35 WB DB WB 25.2 25.1

Outdoor air tempreture DB 70 73 77 81 84 88 91 96 99 104

Indoor Units

Outdoor air tempreture DB 70 73 77 81 84 88 91 96 99 104

95 WB 35 WB CA SHC -

Heating Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68

DB -9 -3 0 3 7 11 15 18 20

Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68

DB -9 -3 0 3 7 11 15 18 20

23 WB

27 WB

32 WB

36 WB

39 WB

43 WB

50 WB

57 WB

-5 WB SHC 14.9 -

-2.9 WB SHC 14.0 -

0 WB SHC 13.8 -

2 WB SHC 14.0 12.5 -

4 WB SHC 12.7 -

6 WB SHC 12.6 11.2 -

10 WB SHC 11.3 9.9 8.9 -

14 WB SHC 10.1 9.0 8.1

23 WB

27 WB

32 WB

36 WB

39 WB

43 WB

50 WB

57 WB

-5 WB DB 38.7 -

-2.9 WB DB 39.2 -

0 WB DB 42.1 -

2 WB DB 42.7 42.6 -

4 WB DB 43.2 -

6 WB DB 43.3 42.8 -

10 WB DB 43.0 43.2 43.2 -

14 WB DB 43.7 43.5 43.1

Note) CA: Total Capacity (kW), SHC: Sensible Heat Capacity (kW) WB: Wet Bulb(℃), DB: Dry Bulb(℃) 1. The data shown in the graph illustrates the supported operating ranges underthe following conditions: - Indoor and Outdoor Unit - Effective piping length: 7.5 m - Height differential: 0 m 2. The actual temperature may not match the temperature setting under some circumstances due to the outdoor-air processing load or mechanical protection controls. 3. The system will not operate in fan mode when the outdoor air temperature is -5°C or below.

7 _ Fresh Air Intake Unit

5.5


6. Outlet temperature, expected capacity and air flow URNU76GB8Z2 Cooling 59 WB

63 WB

69 WB

73 WB

79 WB

82 WB

86 WB

90 WB

95 WB

17 WB CA SHC 8.6 5.0 8.1 5.8 8.2 6.7 8.3 7.5 -

20 WB CA SHC 11.9 5.5 11.4 6.4 11.1 7.2 10.8 7.9 10.7 8.8 -

23 WB CA SHC 14.8 6.6 14.4 7.3 14.1 8.1 13.7 8.9 13.4 9.7 -

26 WB CA SHC 18.2 6.9 17.9 7.7 17.6 8.5 17.3 9.3 15.1 14.8 16.2 11.1

28 WB CA SHC 20.7 7.3 20.3 8.0 19.9 8.8 19.3 9.4 19.1 10.6

30 WB CA SHC 22.2 7.3 21.5 7.9 21.2 8.7 20.7 9.8

32.0

DB 21 23 25 27 29 31 33 35 37 40

15 WB CA SHC 7.7 5.0 7.5 5.8 7.4 6.7 -

35 WB CA SHC 28.6 8.8

59 WB

63 WB

69 WB

73 WB

79 WB

82 WB

86 WB

90 WB

DB 21 23 25 27 29 31 33 35 37 40

15 WB DB WB 10.6 8.3 10.7 8.4 10.8 8.5 -

17 WB DB WB 10.6 10.0 10.8 10.4 10.9 10.2 11.0 10.1 -

20 WB WB DB 11.5 11.0 11.6 11.3 11.8 11.5 12.0 11.7 12.0 11.7 -

23 WB WB DB 13.1 12.5 13.4 12.8 13.6 13.0 13.7 13.2 13.8 13.4 -

26 WB DB WB 14.4 14.2 14.5 14.3 14.7 14.5 14.9 14.6 15.1 14.8 15.5 15.3

28 WB DB WB 15.5 15.3 15.9 15.5 16.1 15.7 16.5 16.1 16.6 16.1

30 WB DB WB 17.6 17.4 18.1 17.8 18.3 17.9 18.5 18.1

32.0 DB WB 19.4 18.9 19.5 19.0

Outdoor air tempreture DB 70 73 77 81 84 88 91 96 99 104 Outdoor air tempreture

SHC 8.2 9.4

95 WB 35 WB DB WB 21.1

21.1

Heating Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68 Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68

DB -9 -3 0 3 7 11 15 18 20

23 WB -5 WB SHC 20.5 -

27 WB -2.9 WB SHC 19.1 -

32 WB 0 WB SHC 18.3 -

36 WB 2 WB SHC 18.2 16.8 -

39 WB 4 WB SHC 16.6 -

43 WB 6 WB SHC 16.7 15.0 -

50 WB 10 WB SHC 14.9 13.2 11.8 -

57 WB 14 WB SHC 13.2 11.8 11.1

27 WB -2.9 WB DB 43.1 -

32 WB 0 WB DB 44.3 -

36 WB 2 WB DB 44.2 45.2 -

39 WB 4 WB DB 44.5 -

43 WB 6 WB DB 44.8 45.1 -

50 10

57 14

DB -9 -3 0 3 7 11 15 18 20

23 WB -5 WB DB 43.2 -

WB WB DB 44.9 44.8 44.7 -

WB WB DB 45.0 44.8 45.2

Note) CA: Total Capacity (kW), SHC: Sensible Heat Capacity (kW) WB: Wet Bulb(℃), DB: Dry Bulb(℃) 1. The data shown in the graph illustrates the supported operating ranges underthe following conditions: - Indoor and Outdoor Unit - Effective piping length: 7.5 m - Height differential: 0 m 2. The actual temperature may not match the temperature setting under some circumstances due to the outdoor-air processing load or mechanical protection controls. 3. The system will not operate in fan mode when the outdoor air temperature is -5°C or below.

Fresh Air Intake Unit _ 8

Indoor Units

DB 70 73 77 81 84 88 91 96 99 104

CA 24.4 24.0


6. Outlet temperature, expected capacity and air flow URNU96GB8Z2 Cooling 59 WB

63 WB

69 WB

73 WB

79 WB

82 WB

86 WB

90 WB

95 WB

17 WB CA SHC 11.1 6.7 10.3 7.9 10.6 9.2 10.6 10.5 -

20 WB CA SHC 16.0 7.5 15.3 8.8 14.8 10.0 14.3 11.2 14.2 12.5 -

23 WB CA SHC 20.5 9.2 19.7 10.3 19.2 11.4 18.7 12.7 18.2 13.9 -

26 WB CA SHC 25.4 9.6 25.0 10.9 24.4 12.0 24.0 13.2 23.5 14.3 22.2 15.9

28 WB CA SHC 29.0 10.3 28.5 11.3 27.9 12.4 26.9 13.4 26.5 15.2

30 WB CA SHC 31.1 10.2 30.0 11.1 29.6 12.3 28.8 14.0

32.0

DB 21 23 25 27 29 31 33 35 37 40

15 WB CA SHC 5.4 3.7 5.2 4.3 5.1 5.0 -

35 WB CA SHC 12.5 40.0

59 WB

63 WB

69 WB

73 WB

79 WB

82 WB

86 WB

90 WB

95 WB

DB 21 23 25 27 29 31 33 35 37 40

15 WB WB DB 11.7 9.4 11.8 9.5 11.9 9.6 -

17 WB DB WB 11.7 11.1 11.9 11.5 12.0 11.3 12.1 11.2 -

20 WB DB WB 12.6 12.1 12.7 12.4 12.9 12.6 13.1 12.8 13.1 12.8 -

23 WB DB WB 14.2 13.6 14.5 13.9 14.7 14.1 14.8 14.3 14.9 14.5 -

26 WB DB WB 15.5 15.3 15.6 15.4 15.8 15.6 16.0 15.7 16.2 15.9 16.6 16.4

28 WB DB WB 16.6 16.4 17.0 16.6 17.2 16.8 17.6 17.2 17.7 17.2

30 WB DB WB 18.7 18.5 19.2 18.9 19.4 19.0 19.6 19.2

32.0 DB WB 20.5 20.0 20.6 20.1

35 WB DB WB 22.2 22.2

Outdoor air tempreture DB 70 73 77 81 84 88 91 96 99 104

Indoor Units

Outdoor air tempreture DB 70 73 77 81 84 88 91 96 99 104

CA 34.4 33.8

SHC 11.6 13.4

Heating Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68

DB -9 -3 0 3 7 11 15 18 20

WB

27

WB

-2.9

SHC 30.8 WB

27 -2.9

-5 DB -9 -3 0 3 7 11 15 18 20

WB WB

32

WB

36

WB

39

WB

43

WB

50

0

WB

2

WB

4

WB

6

WB

10 WB SHC 22.5 19.8 17.6 -

SHC 28.7 -

WB DB 43.1 -

23

Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68

23 -5

WB

WB DB 43.0 -

SHC 28.0 32 0

SHC 27.7 25.3 -

WB

36

WB DB 45.3 -

2

SHC 25.0 -

WB

39

WB DB 44.7 45.2 -

4

SHC 24.4 22.1 -

WB

43

WB DB 44.6 -

6

WB

50

WB DB 43.6 44.2 -

10

Note) CA: Total Capacity (kW), SHC: Sensible Heat Capacity (kW) WB: Wet Bulb(℃), DB: Dry Bulb(℃) 1. The data shown in the graph illustrates the supported operating ranges underthe following conditions: - Indoor and Outdoor Unit - Effective piping length: 7.5 m - Height differential: 0 m 2. The actual temperature may not match the temperature setting under some circumstances due to the outdoor-air processing load or mechanical protection controls. 3. The system will not operate in fan mode when the outdoor air temperature is -5°C or below.

9 _ Fresh Air Intake Unit

WB

57

WB

14 WB SHC 19.6 17.9 16.4

WB

57

WB DB 44.9 44.8 44.5 -

14

WB

WB DB 44.5 45.0 44.7


6. Outlet temperature, expected capacity and air flow 6.2 Air flow ARNU48GBRZ2 Setting Value

6 16 19.9 23.4 24.1 25.5 27 27 28.5 29.8 31.8 32.7 -

8 13.6 17.8 19.6 21.9 22.8 24 25 26.5 28 29.17 30.9 -

12 10.6 13.8 15.8 17.4 20.5 22 24.6 28.3 30.7 -

ESP (mmAq) 14 10.7 16 16.5 19.9 24.2 27.6 30.4 -

15 26.57 42.67 46.44 48.82 50.91 50.9 -

ESP (mmAq) 18 20.9 33.72 40.09 44.3 46.73 49.84 49.66 -

10 15.9 18.2 19.8 22.5 22.8 24.2 25.9 28.2 30.8 -

15 11.8 15.2 20.7 25.2 29.7 -

16 11.9 17.7 24.2 27.2 28.6 -

17 15.8 22.4 26.3 27.6 -

18 14.7 18.8 25.6 27.4 -

20 13.4 18.7 25.9 26.5 -

URNU76GB8Z2,URNU96GB8Z2 Setting Value 55 60 65 70 75 80 85 88 90 92 94 96 98 100 102 105

6 25.39 33.65 40.01 46.43 50.93 55.77 -

9 30.29 35.81 45.35 51.91 54.22 -

12 17.31 35.57 42.86 49.74 52.72 52.54 -

20 23.07 23.46 39.65 44.04 48.09 48.23 -

22 13.87 24.17 39.72 42.56 46.41 -

23 23.63 25.28 40.34 45.92 46.51

25 14.49 15.47 38.6 45.44

Note) Setting Value : ESP value The above table shows the correlation between the air rates and E.S.P.

Fresh Air Intake Unit _ 10

Indoor Units

70 75 80 85 87 90 92 94 96 98 101 103 106 111 116 121 126 130 135 140

5 15.8 18.7 22.2 24.2 25.2 26.8 28.1 29 30.3 -


7. External Static Pressure (E.S.P) & Air Flow ARNU48GBRZ2 Capacity (Btu/h)

Mode

Set value

High High (factory set) Mid

1,160

48k

1,110

Standard ESP(mmAq(Pa)) 18

CMM 18.8 14.7

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

10(98)

20(196)

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

12(118)

25(245)

12(118)

25(245)

URNU76GB8Z2,URNU96GB8Z2 Capacity (Btu/h)

Mode

Set value 950

Mid

930

96k

High (factory set)

High

970

Mid

950

Indoor Units

High (factory set)

High

76k

11 _ Fresh Air Intake Unit

Standard ESP(mmAq(Pa)) 22 22

CMM 23.7 13.2 35.7 23.7


8. Electric Characteristics Units Model

Type

ARNU48GBRZ2

BR

URNU76GB8Z2

B8

URNU96GB8Z2

B8

ARNU48GBRZ2

BR

URNU76GB8Z2

B8

URNU96GB8Z2

B8

Power Supply

Hz 50

volts 220-240

Max: 264 Min: 198 60

Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(see note 5)

IFM : Indoor Fan Motor

220

Input(W)

MCA

MFA

kW

FLA

Cooling Heating

1.5

15

0.39

0.38

169

169

2.7

15

0.38

1.36

230

230

3.7

15

0.38

2.15

360

360

1.5

15

0.39

0.38

169

169

2.7

15

0.38

1.36

230

230

3.7

15

0.38

2.15

360

360

Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.

Fresh Air Intake Unit _ 12

Indoor Units

kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A)

Voltage Range

IFM


9. Sound Levels Overall DISCHARGE

Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

SUCTION

DUCT

DUCT 1.5m

2m

1m 1m

[dB(A)] Sound Level

ARNU48GBRZ2

H 44

M 42

L 42

URNU76GB8Z2

49

47

47

URNU96GB8Z2

50

48

48

Sound Pressure Level ARNU48GBRZ2

URNU76GB8Z2

URNU96GB8Z2

80

80

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

NC-60

125

250

500

Octave Band Center Frequency (Hz)

13 _ Fresh Air Intake Unit

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 1000 2000 4000 8000

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

80

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

Indoor Units

Model

NC-60

125

250

500

Octave Band Center Frequency (Hz)

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 1000 2000 4000 8000

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

NC-20

125

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)


10. Operation Details Operation range FAU will operate in the below range. Hot outdoor temperature (over 43℃) or cold outdoor temperature (under 5℃) will make customer feel uncomfortable because FAU outlet discharge temperature might be not enough controlled in that region. * FAU : Fresh Air Intake Unit -5°C Cooling mode

5°C

15°C

Outdoor Air Temperature (Toa) ℃ 43℃ (1)

19°C

Fan operation (thermo off)

Cooling Cooling

Fan operation Fan stop

Heating mode

6°C

18°C

Heating

Fan operation (thermo off) Fan operation

Heating 16°C

Indoor Units

Automatic mode

Cooling

Heating

Cooling Heating

18°C 16°C (1)Normal model : 43°C Tropical model : 48°C

Usage Limitations

-5°C

15°C

19°C

(33.5°)

43℃ (2)

(2)Normal model : 43°C Tropical model : 48°C

Fresh Air Intake Unit _ 14


11. Installation

Air outlet vents

Air filters

Air intake vents

Indoor Units

Wired Remote Controller

Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

4 EA

1 SET

Others

• Owner's manual • Installation manual Shape

for gas pipe

for liquid pipe

15 _ Fresh Air Intake Unit


11. Installation 11.1 Installation Limit Read completely, then follow step by step.

1. Fresh Air Intake Unit Combination No 1

Connection Condition Only Fresh Air Intake Unit installation

2 Mixture Installation with standard indoor units and Fresh Intake Units

Combination 1) The total capacity of Fresh Air Intake Unit should be 50~100% of outdoor unit. 2) The max quantity of Fresh Air Intake unit is 2 Units. 1) The total capacity of indoor units (standard Indoor Unit + Fresh Air Intake Unit) should be 50~100% of outdoor unit. 2) The total capacity of Fresh Air Intake Units should be less than 30% the total capacity of indoor units.

Failure to comply with the above connection conditions for installation, it can cause cooling & heating capacity down.

Indoor Units

2. Connection of the Outdoor Unit It is possible to connect Heat Pump Models. It is not possible to connect Heat Recovery Models. <Only Fresh Air Intake Unit install>

<Mixture Install>

Outdoor : 10HP

Outdoor : 20HP

FAU

FAU

FAU

Standard

Standard

Standard

5HP

5HP

5HP

5HP

5HP

5HP

<Wrong Install> Outdoor : 20HP

FAU

Standard

Standard

Standard

Standard

5HP

5HP

5HP

5HP

5HP * FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit

ᜀ The total capacity of indoor units exceed 100% of outdoor unit

Fresh Air Intake Unit _ 16


11. Installation 3. Installation of intake air duct Min. 2m

Inlet Hood Intake Air Duct Fresh Air Intake Unit Exhaust Fan Door

1/30 Slope Outlet Air

Indoor Units

Exhaust air

Inlet Hood Inlet Hood should be installed such that no water enter inside the unit Intake Air Duct The Intake Air Duct must have down-slope about 1/30. The length of Intake Air Duct should be longer than 2m. Fresh Air Intake Unit If wired remote controller is not connected, it will display strange value to the room temperature Exhaust Fan Fresh Air Intake Unit will make room the positive pressure. Exhaust fan should be installed to maintain the room pressure. Door It would be possible to raise in the room air pressure because of Fresh Air Intake Unit. In that case, the door could hurt someone in front of door. So be careful of the positive pressure to design the door.

17 _ Fresh Air Intake Unit


11. Installation 4. The Control System 1) In case of connecting with Standard indoor units, Standard indoor unit should be a master unit. Separate Fresh Air Intake Unit with Standard indoor units .Set only one Standard indoor units to Master,

Standard

FAU

Standard

Standard

Slave

* FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit

Set one of the IDU to Master

FAU

FAU

Standard

Standard

FAU

FAU

Standard

Standard

48 kBtu/h

48 kBtu/h

48 kBtu/h

48 kBtu/h

48 kBtu/h

48 kBtu/h

48 kBtu/h

48 kBtu/h

ZONE 1

ZONE 2

ZONE 1

ZONE 2

5. Cycle check and SVC For Fresh Intake Unit cycle check and SVC, LG MV 5.8 or later version should be used.

Fresh Air Intake Unit _ 18

Indoor Units

2) In case of using central remote controller, mixture of indoor units and Fresh Air Intake Unit in same zone is not possible. Separate Fresh Air Intake Unit zone with Standard indoor units zone.


11. Installation 11.2 Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unitʼs weight. • The place shall be able to inspect the unit as the figure. • The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit.

Top view

Inspection hole (600X600)

(unit: mm)

600

1000

Indoor Units

Control box

600

Front

Front view

H

CAUTION : In case that the unit is installed near the sea, the installation parts may be corroded by salt, The installation parts (and the unit) should be taken appropriate anti-corrosion measures.

[Inspection Hole Standard] Number of Inspection hole

Distance between False ceiling & Actual ceiling

1

More than 1000mm

Sufficient space in the ceiling for servicing.

200mm to 1000mm

Insufficient space. Difficult for servicing

Less than 200mm

Minimum height for motor replacement.

2 Hole size should be more than the size of IDU.

19 _ Fresh Air Intake Unit

Remarks


11. Installation 11.3 Ceiling dimension and hanging bolt location Installation of Unit Install the unit above the ceiling correctly.

BR Chassis (48k)

A B

CASE 1 C E

POSITION OF SUSPENSION BOLT

D

• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.

F

(G)

(Unit:mm) Dimension

B

C

D

E

F

(G)

H

I

477

56

590

30

120 1006 294

I

A Capacity(Btu/h)

BR Chassis 1282 1230 (48k)

H

(Unit:mm)

Indoor Units

Drainage hole

B8 Chassis (76/96k)

Dimension

A

B

C

D

E

F

G

H

I

J

K

L

Capacity(Btu/h)

B8 Chassis (76/96k) 1680 1565 1160 330 460 580 700 1400 1635 390 445 15

CASE 2 • Install the unit leaning to a drainage hole side as a figure for easy water drainage. POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

Fresh Air Intake Unit _ 20


11. Installation NOTICE • Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated.

Indoor Units

5. Avoid places near high frequency generators.

11.4 Indoor Unit Installation • Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling.

• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

Old building

1 Set anchor 2 Plate washer 3 Spring washer 4 Nut

CAUTION : Tighten the nut and bolt to prevent unit falling.

21 _ Fresh Air Intake Unit

5 Suspension bolts

New building


11. Installation 11.5 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. • BR Chassis (48k) [Multi V III Heat Pump Model]

1(L)

2(N)

3(A)

[Except Multi VIII Heat Pump Model] SODU B

Terminal Block Indoor

SODU A

IDU B

IDU A

INT B

INT A

Terminal Block Indoor 1(L)

4(B)

2(N)

3(A)

Outdoor unit Indoor unit

4(B)

SODU SODU

IDU

Central controller

Outdoor unit

IDU INTERNET DRY1 DRY2 GND 12V

INDOOR POWER INPUT

INDOOR POWER INPUT

• B8 Chassis (76/96k) [Except Multi VIII Heat Pump Model]

[Multi V III Heat Pump Model] Terminal Block Indoor 1(L)

2(N)

3(A)

Terminal Block

SODU B

SODU A

IDU B

IDU A

INT B

INT A

Terminal Block Indoor 1(L)

4(B)

2(N)

3(A)

Terminal Block 4(B)

Outdoor unit Indoor unit SODU SODU

IDU

Central controller

IDU INTERNET DRY1 DRY2 GND 12V

Outdoor unit

Indoor Power Input

Indoor Power Input

Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.

INSULATION, OTHERS THERMAL INSULATION

Insulate the joint and tubes completely.

All thermal insulation must comply with local requirement.

Union for liquid pipe Refrigerant pipe and thermal insulator(Local supply) Hose crip for thermal insulator (Local supply) Thermal insulator for refrigerant pipe (Local supply) Union for gas pipe

Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply)

Overlap with thermal insulator for piping. Hose crip for thermal insulator(Local supply) Make sure that there is no clearance here.

Fresh Air Intake Unit _ 22

Indoor Units

WARNING : Make sure that the screws of the terminal are free from looseness.


11. Installation 11.6 Check the Drainage

Indoor Units

2. Check the drainage. • Spray one or two glasses of water upon the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.

CAUTION 1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.

Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation.

1~3mm

Ceiling

Drain Pump unuse

Drainage hole

23 _ Fresh Air Intake Unit

Drain Pump use

Drainage hole


11. Installation 11.7 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe inner diameter Ø 25mm and pipe fittings

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

• Be sure to install heat insulation on the drain piping.

1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

MAX 700mm

Drain test

Feed water

Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operation and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Hanger distance 1~15m

Hanger Bracket 1/50~1/100 slope

Metal clamp Flexible drain hose

Max 700mm

Max 300mm

Insulation

Flexible drain hose Flexible drain hose

Flexible drain hose

Fresh Air Intake Unit _ 24

Indoor Units

The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:


11. Installation CAUTION:

Indoor Units

After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal function of an overload protection device. • Proper starting power is not given to the compressor.

HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)

25 _ Fresh Air Intake Unit


12. Accessories Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

4 EA

1 SET

(Other)

• Owner's manual • Installation manual Shape

for gas pipe

for liquid pipe

Indoor Units

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Fresh Air Intake Unit _ 26


Indoor unit Dip Switch & Group Control Setting 1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 1.1 Dip Switch Setting 1.2 Group Control Setting 1.3 2 Remote Control 1.4 Accessories for group control setting

2. Wall Mounted, ART COOL Gallery, ART COOL Mirror 2.1 Master/Slave Setting 2.2 Group Control Setting 2.3 2 Remote Control 2.4 Accessories for group control setting


1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 1.1 Dip Switch Setting Dip Switch Setting of Indoor unit PCB

SW1

Function Communication

Description N/A (Default)

Setting Off -

Setting On -

Default Off

SW2

Cycle

N/A (Default)

-

-

Off

SW3

Group Control

Selection of Master or Slave

Master

Slave

Off

Dry Contact Mode

Selection of Dry Contact Mode

Wired/Wireless remote controller selection of Manual or Auto operation Mode

Auto

Off

SW5

Installation

Fan continuous operation

Continuous operation Removal

-

Off

SW6

Heater linkage

N/A

-

-

Off

Ventilator linkage

Selection of Ventilator linkage

Linkage Removal

Working

Vane selection (Console)

Selection of up/down side Vane

Up side + Down side Vane

Up side Vane Only

Region selection

Selection tropical region

General model

Tropical model

Etc.

Spare

-

-

SW4

SW7

SW8

Off

Off

For Multi V Models, Dip switch 1, 2, 6, 8 must be set OFF.

Dip Switch & Group Control Setting _ 1

Dip Switch & Group Control Setting

CAUTION


1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 1.2 Group Control 1 (1) Group Control 1 Wired remote controller 1 + Standard Indoor Units LGAP Network System

or

Master

Slave

Slave

Slave

Display Error Message Only connect serial signal and GND lines between slave indoor unit

Dip Switch & Group Control Setting

Master

Dip Switch in PCB (Cassette and Duct Type indoor units) - No. 3 Off

- No. 3 On

1. It is possible to 16 indoor units(Max) by one wired remote controller. Set only one indoor unit to Master, set the others to Slave. 2. It is possible to connect with every type of indoor units. 3. It is possible to use wireless remote controller at the same time. 4. It is possible to connect with Dry Contact and Central controller at the same time. - The Master indoor unit is possible to recognize Dry Contact and Central Controller only. - In case of Central controller and Group controller at the same time, it is possible to connect standard 2series indoor units or later since Feb. 2009. - In case of Central controller setting, the Central controller can control indoor units after setting only the address of master indoor unit. - Slave indoor unit will be operated like master indoor unit. - Slave indoor unit can not be individually controlled by Central controller. - Some remote controller can’t perform with Dry Contact and Central controller at the same time. So contact us further information about it.

2 _ Dip Switch & Group Control Setting

GND Signal 12 V


1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 5. In case of any error occurs at indoor unit, display on the wired remote controller. Exception of the error indoor unit, an individual indoor unit control possibility. 6. In case of Group Control, it is possible to use following functions. - Selection of operation options (operation/stop/mode/set temperature) - Control of flow rate (High/Middle/Low) - It is not possible at some functions. Master/Slave setting of indoor units be set possible using a PCB Dip Switch. It is possible to connect indoor units since Feb. 2009. In the other cases, please contact LGE. It can be the cause of malfuctions when there is no setting of master and slave.

(2) Group Control 2 Wired remote controllers + Standard Indoor Units LGAP Network System

or

Slave

Slave

GND Signal 12 V

DonĘźt connect serial 12V line

Display Error Message Master

Slave

It is possible to control N indoor units by wired remote controller M units. (M+N≤17 Units) Set only one indoor unit to Master, set the others to Slave. Set only one wired remote controller to Master, set the others to Slave. Other than those, it is same with the Group Control 1.

Dip Switch & Group Control Setting _ 3

Dip Switch & Group Control Setting

Slave

Master


1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit (3) Group Control 3 Mixture connection with indoor units and Fresh Air Intake Unit LGAP Network System

or

FAU Master

FAU Slave

Master

Slave

GND Signal 12 V

Display Error Message

Master

Master

Dip Switch & Group Control Setting

In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air Intake Unit with standard units. (Because setting temperature are different.) Other than those, it is same with Group Control 1.

FAU

FAU

Standard

Standard

FAU

FAU

Standard

Standard

* FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit

4 _ Dip Switch & Group Control Setting


1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 1.3 2 Remote Control Wired remote controller 2 + Indoor unit 1 LGAP Network System

or

Master

Display Error Message Master

Slave

1. It is possible to connect two wired remote controllers with one indoor unit. 3. It is possible to use wireless remote controller at the same time. 4. It is possible to connect with Dry Contact and Central controller at the same time. 5. In case of any error occurs at indoor unit, display on the wired remote controller. 6. There isnĘźt limits of indoor unit function. â?ˆ Maximum 2wired remote controllers can be connected with 1 indoor unit.

Dip Switch & Group Control Setting _ 5

Dip Switch & Group Control Setting

2. Every types of indoor unit is possible to connect two remote controller.


1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 1.4 Accessories for group control setting It is possible to set group control by using below accessories. Indoor unit 2 EA +Wired remote controller â?ˆ PZCWRCG3 cable used for connection

Indoor unit 1 EA +Wired remote controller 2EA â?ˆ PZCWRC2 cable used for connection

S lave

Mas te r

PZC WRC 2 PZC WRC G3

Dip Switch & Group Control Setting

Maste r

6 _ Dip Switch & Group Control Setting

Maste r

S lave


2. Wall Mounted, ART COOL Gallery, ART COOL Mirror 2.1 Master/Slave Setting

1

With the FAN SPEED button pressed, press the RESET button.

2

By using the TEMPERATURE SETTING button, set function code and setting value. (Please refer the Installer Setting Code Table.) Function Code

Setting Code

4

Reset the remote controller to use the general operation mode.

Installer Setting Code Table No.

Function

Function Code

Setting Value

Remote Controller LCD

0 : Set to Master 1

Group Control

2

1 : Set to Slave 2 : Check Master/Slave

Dip Switch & Group Control Setting _ 7

Dip Switch & Group Control Setting

3

Press the ON/OFF button toward the indoor unit 1 time.


2. Wall Mounted, ART COOL Gallery, ART COOL Mirror Group Control Setting - This function is only for group control. - Please don’t set this function in case of non-group control. - This function is the Master or Slave setting function of indoor unit - Set only one indoor unit to Master, set the others to slave. - After setting Group Control of the product, turn off the power then turn it back on after 1 minute. - Master checking whether the buzzer sounds, such as indoor rings below. ▶ Master: “Beep” (Buzzer sound 1 time) ▶ Slave: “Beep, Beep, Beep, Beep, Beep ” (Buzzer sounds 5 times)

2.2 Group Control 1 (1) Group Control 1 Wired remote controller 1 + Standard Indoor Units LGAP Network System

Dip Switch & Group Control Setting

or

Master

Slave

Slave

Slave

Display Error Message Only connect serial signal and GND lines between slave indoor unit Master

1. It is possible to 16 indoor units(Max) by one wired remote controller. Set only one indoor unit to Master, set the others to Slave. 2. It is possible to connect with every type of indoor units. 3. It is possible to use wireless remote controller at the same time.

8 _ Dip Switch & Group Control Setting

GND Signal 12 V


2. Wall Mounted, ART COOL Gallery, ART COOL Mirror 4. It is possible to connect with Dry Contact and Central controller at the same time. - The Master indoor unit is possible to recognize Dry Contact and Central Controller only. - In case of Central controller and Group controller at the same time, it is possible to connect standard 2series indoor units or later since Feb. 2009. - In case of Central controller setting, the Central controller can control indoor units after setting only the address of master indoor unit. - Slave indoor unit will be operated like master indoor unit. - Slave indoor unit can not be individually controlled by Central controller. - Some remote controller can’t perform with Dry Contact and Central controller at the same time. So contact us further information about it. 5. In case of any error occurs at indoor unit, display on the wired remote controller. Exception of the error indoor unit, an individual indoor unit control possibility. 6. In case of Group Control, it is possible to use following functions. - Selection of operation options (operation/stop/mode/set temperature) - Control of flow rate (High/Middle/Low) - It is not possible at some functions. Indoor units be set possible using a wireless remote controller. This indoor unit be set possible using a wireless remote controller for setting group control. (type : Wall Mounted, ART COOL Gallery, ART COOL Mirror) It is possible to connect indoor units since Feb. 2009. In the other cases, please contact LGE. It can be the cause of malfuctions when there is no setting of master and slave.

Dip Switch & Group Control Setting

Dip Switch & Group Control Setting _ 9


2. Wall Mounted, ART COOL Gallery, ART COOL Mirror (2) Group Control 2 Wired remote controllers + Standard Indoor Units LGAP Network System

or

Slave

Master

Slave

Slave

DonĘźt connect serial 12V line

Display Error Message

Dip Switch & Group Control Setting

Master

Slave

It is possible to control N indoor units by wired remote controller M units. (M+N≤17 Units) Set only one indoor unit to Master, set the others to Slave. Set only one wired remote controller to Master, set the others to Slave. Other than those, it is same with the Group Control 1.

10 _ Dip Switch & Group Control Setting

GND Signal 12 V


2. Wall Mounted, ART COOL Gallery, ART COOL Mirror (3) Group Control 3 Mixture connection with indoor units and Fresh Air Intake Unit LGAP Network System

or

FAU Master

FAU Slave

Master

Slave

GND Signal 12 V

Display Error Message

Master

Master

Other than those, it is same with Group Control 1.

FAU

FAU

Standard

Standard

FAU

FAU

Standard

Standard

* FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit

Dip Switch & Group Control Setting _ 11

Dip Switch & Group Control Setting

In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air Intake Unit with standard units. (Because setting temperature are different.)


2. Wall Mounted, ART COOL Gallery, ART COOL Mirror 2.3 2 Remote Control Wired remote controller 2 + Indoor unit 1 LGAP Network System

or

Master

Display Error Message Master

Slave

Dip Switch & Group Control Setting

1. It is possible to connect two wired remote controllers with one indoor unit. 2. Every types of indoor unit is possible to connect two remote controller. 3. It is possible to use wireless remote controller at the same time. 4. It is possible to connect with Dry Contact and Central controller at the same time. 5. In case of any error occurs at indoor unit, display on the wired remote controller. 6. There isnĘźt limits of indoor unit function. â?ˆ Maximum 2wired remote controllers can be connected with 1 indoor unit.

12 _ Dip Switch & Group Control Setting


2. Wall Mounted, ART COOL Gallery, ART COOL Mirror 2.4 Accessories for group control setting It is possible to set group control by using below accessories. Indoor unit 2 EA +Wired remote controller ❈ PZCWRCG3 cable used for connection

Indoor unit 1 EA +Wired remote controller 2EA ❈ PZCWRC2 cable used for connection

S lave

Mas te r

PZC WRC 2 PZC WRC G3

Maste r

Maste r

S lave

Dip Switch & Group Control Setting

Dip Switch & Group Control Setting _ 13


P/No.: MFL61741606

Air Conditioner 20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com

All rights reserved Printed in Korea March/2010 The specifications, designs, and information in this brochure are subject to change without notice.

The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.