Indoor unit (R410A) 0CVP0-01A
Indoor unit (R410A) 0CVP0-01A General Information
Indoor unit • Introduction • General Information • Indoor Units • Dip Switch & Group Control Setting
Introduction 1. Preface
is the most favored choice when there is a need for precise air conditioning of relatively big projects extending from Multi-Room structure to big commercial places. We have a big line up, that offers wider flexibility of model selection. Equipped with inverter technology and long piping installation, the product matches well if one talk about optimum power consumption in high rise buildings. Add on capacity feature makes it easy to upgrade the existing capacity at any time. With the growing concern about environment preservation, comes with R410A refrigerant which is environment friendly and thus our system is a high technology and environment friendly product.
Unique refrigerant flow and electronic circuit control gives this system an unique capability to work in extreme/abnormal working conditions making our customer feel great about their decision of selecting LG as their first choice. This publication provides a detailed and in depth information about the design and installation of . We hope that with this information you would become an expert of your
system.
Air-Conditioning Company
General Information
R410A Model
General Information
2. Step by Step (1)
(2)
System Selection Process
Calculate or obtain the maximum heat load for the area(s) to be air conditioned
Decide the indoor unit specifications Decide the outdoor unit specifications Capacity coefficient factor Decide the air velocity and temperature distributions
(3)
(4)
Selection of refrigerant pipe joints and headers
Selection of the control system Control wiring method Description of devices
(5)
Electrical wiring Electric characteristics Field wiring
!
Caution
1. Air conditioners should not be installed in areas where corrosive gas such as acid gas or alkaline gas is produced. 2. If the outdoor unit is installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
Indoor unit General Information 1. Model Names 2. External Appearance 3. Nomenclature 4. Indoor Unit Capacity Index
1. Model Names Chassis 5k Name (1.6)
General information Indoor unit
Category
9k (2.8)
12k (3.6)
15k (4.5)
ARNU18G ARNU24G S5*2 S5*2
S5 ARNU07G ARNU09G ARNU12G ARNU15G SE*2 SE*2 SE*2 SE*2
SE Mirror ART COOL
ARNU18G ARNU24G S8*2 S8*2
S8
Gallery
ARNU07G ARNU09G ARNU12G SF*2 SF*2 SF*2 ARNU07G ARNU09G ARNU12G GTU*2 GTU*2 GTU*2
SF TU
1 Way
ARNU18G ARNU24G TT*2 TT*2 ARNU18G ARNU24G TL*2 TL*2
TT 2 Way Ceiling
TL TR
Cassette
ARNU05 ARNU07G ARNU09G ARNU12G GTR*2 TR*2 TR*2 TR*2 ARNU15 ARNU18G GTQ*2 TQ*2
TQ 4 Way
Capacity(Btu/h(kW)) 18k 24k 28k 36k 42k 48k 76k 96k (5.6) (7.1) (8.2) (10.6) (12.3) (14.1) (22.4) (28.0)
ARNU07G ARNU09G ARNU12G ARNU15G SE*2 SE*2 SE*2 SE*2
SE
Wall Mounted (General)
7k (2.2)
ARNU24G ARNU28G TP*2 TP*2
TP
ARNU36G TN*2
TN
ARNU42G ARNU48G TM*2 TM*2
TM BH High Static Ceiling Concealed Duct
ARNU07G ARNU09G ARNU12G ARNU15G ARNU18G ARNU24G BHA2 BHA2 BHA2 BHA2 BHA2 BHA2 ARNU28G ARNU36G ARNU42G BGA2 BGA2 BGA2
BG
ARNU48G BRA2
BR
URNU76G URNU96G B8A2 B8A2
B8 B1 Low Static
ARNU07 GB1G2
ARNU09 GB1G2
ARNU12 GB1G2
ARNU15 GB1G2 ARNU18 GB2G2
B2 B3 Built In
ARNU07G ARNU09G ARNU12G ARNU15G B3G2 B3G2 B3G2 B3G2 ARNU18G ARNU24G B4G2 B4G2
B4 Ceiling & Floor
VE
Ceiling Suspended
VJ CE
With Case
ARNU09G ARNU12G VEA2 VEA2 ARNU18G ARNU24G VJA2 VJA2 ARNU07G ARNU09G ARNU12G ARNU15G CEA2 CEA2 CEA2 CEA2 ARNU18G ARNU24G CFA2 CFA2
CF
Floor Standing
Without Case Console
CE
ARNU07G ARNU09G ARNU12G ARNU15G CEU2 CEU2 CEU2 CEU2 ARNU18G ARNU24G CFU2 CFU2
CF QA BR
Fresh Air Intake Unit
ARNU24 GB2G2
ARNU07G ARNU09G ARNU12G ARNU15G QAA2 QAA2 QAA2 QAA2 ARNU48G BRZ2
B8
❈ *ART COOL- SE/S8( * R:Mirror, V:Silver, B : Blue), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable)) *Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma
1 _ General Information
URNU76 URNU96 GB8Z2 GB8Z2
2. External Appearance Ceiling Concealed Duct - High Static
ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2
ARNU07GBHA2 ARNU09GBHA2 ARNU12GBHA2 ARNU15GBHA2 ARNU18GBHA2 ARNU24GBHA2 ARNU28GBGA2
ARNU18GTT*2 ARNU24GTT*2
* A:Basic, C:Plasma
Ceiling Cassette- 4Way ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2 ARNU15GTQ*2 ARNU18GTQ*2
ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 ARNU42GTM*2 ARNU48GTM*2 * A:Basic, C:Plasma
Ceiling Concealed Duct - Low Static ARNU07GB1G2 ARNU15GB1G2 ARNU09GB1G2 ARNU18GB2G2 ARNU12GB1G2 ARNU24GB2G2
Ceiling Concealed Duct – Built-in ARNU07GB3G2 ARNU09GB3G2 ARNU12GB3G2
ARNU15GB3G2 ARNU18GB4G2 ARNU24GB4G2
ARNU36GBGA2 ARNU42GBGA2 ARNU48GBRA2 URNU76GB8A2 URNU96GB8A2
Wall Mounted ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2
ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2 * A:Basic, L:Plasma
ART COOL Gallery ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2 * E:Red V:Silver G:Gold 1: Kiss (Photo changeable)
Floor Standing With case ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2
ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2
ART COOL Mirror
Without case
ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2
ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2
ARNU15GSE*2 ARNU18GS8*2 ARNU24GS8*2 * R:Mirror, V:Silver, B:Blue
ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2
Ceiling & Floor Console
ARNU09GVEA2 ARNU12GVEA2
Ceiling Suspended ARNU18GVJA2 ARNU24GVJA2
Ceiling Cassette -2Way ARNU18GTL*2 ARNU24GTL*2
ARNU07GQAA2 ARNU09GQAA2 ARNU12GQAA2 ARNU15GQAA2
Fresh Air Intake Unit ARNU48GBRZ2 URNU76GB8Z2 URNU96GB8Z2
* A:Basic, C:Plasma
General Information _ 2
General information Indoor unit
Ceiling Cassette- 1Way
General information Indoor unit
3. Nomenclature ARN
U
07
G
TU
A
2 Serial Number Combinations of functions A:Basic function L:Neo Plasma(Wall Mounted) C:Plasma(Ceiling Cassette) G: Low Static U : Floor Standing without Case ART COOL Type Panel Color SE/S8 - R:Mirror V:Silver B:Blue SF - E:Red V:Silver G:Gold 1: Kiss (Photo changeable) Q : Console Z : Fresh Air Intake Unit Chassis Name Electrical Ratings 2:1Ø, 220V, 60Hz 6:1Ø, 220 - 240V, 50Hz G:1Ø, 220 - 240V, 50Hz / 1Ø, 220V, 60Hz Total Cooling Capacity in Btu/h EX) 5,000 Btu/h Class ➝ '05' 18,000 Btu/h Class ➝ '18' Combination of Inverter Type and Cooling Only or Heat Pump N: AC Inverter and H/P V: AC Inverter and C/O U: DC Inverter and H/P and C/O System with Indoor Unit using R410A ❈ LGETA:U Ex) URN
3 _ General Information
4. Indoor Unit Capacity Index INDOOR UNIT CAPACITY INDEX 5k
7k
9k
12k
15k
18k
24k
28k
36k
42k
48k
76k
96k
Capacity Index
1.6
2.2
2.8
3.6
4.5
5.6
7.1
8.2
10.6
12.3
14.1
22.4
28.0
â?ˆ Capacity Index is same as the capacity(kW).
General Information _ 4
General information Indoor unit
Unit Capacity (Btu/h)
5 _ General Information
General information Indoor unit
Indoor unit Ceiling Cassette 1-Way Ceiling Cassette 2-Way Ceiling Cassette 4-way Ceiling Concealed Duct(High Static) Ceiling Concealed Duct(Low Static) Ceiling Concealed Duct(Built in) Wall Mounted ART COOL Mirror ART COOL Gallery Ceiling & Floor/Ceiling Suspended Floor Standing Console Fresh Air Intake Unit Dip Switch & Group Control Setting
Indoor unit Ceiling Cassette 1-Way 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of functions Category
Air flow
Air purifying
Installation
Convenience
Individual control
Special function kit
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU07GTU*2, ARNU09GTU*2, ARNU12GTU*2 ARNU18GTT*2, ARNU24GTT*2 1 Auto O 4/5/4 X O O X Option O O O X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. * Some functions can be limited by remote controller.
Ceiling Cassette 1-Way _ 1
Indoor Units
Reliability
Function
2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Body Dimensions (WxDxH) Front Panel
Indoor Units
Coil
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
mm inch mm inch m3 W A CMM cfm
Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)
Ø, V, Hz
1Way Ceiling Cassette ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 860 x 450 x 132 860 x 450 x 132 860 x 450 x 132 33.8 x 17.7 x 5.2 33.8 x 17.7 x 5.2 33.8 x 17.7 x 5.2 1100 x 500 x 34 1100 x 500 x 34 1100 x 500 x 34 43.3 x 19.7 x 1.3 43.3 x 19.7 x 1.3 43.3 x 19.7 x 1.3 2 x 12 x 18 2 x 12 x 18 2 x 12 x 18 0.16 0.16 0.16 Cross Flow Fan Cross Flow Fan Cross Flow Fan 30 30 30 0.18 0.18 0.18 8.2 / 7.3 / 6.4 9.2 / 8.6 / 8.2 10 / 9.2 / 8.2 289.5 / 257.7 / 225.9 324.7 / 303.6 / 289.5 353 / 324.8 / 289.5 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 25(1) 14.7(32.4) 14.7(32.4) 14.7(32.4) 32 / 29 / 25 35 / 34 / 32 38 / 35 / 32 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C White White White PT-UUC(Grill), PT-UUD(Panel)
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
2 _ Ceiling Cassette 1-Way
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Body Dimensions (WxDxH) Front Panel Coil
m3 W A CMM cfm
Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)
Ø, V, Hz
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling Cassette 1-Way _ 3
Indoor Units
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
mm inch mm inch
1Way Ceiling Cassette ARNU18GTT*2 ARNU24GTT*2 5.6 7.1 4,800 6,100 19,100 24,200 6.3 7.1 5,400 6,100 21,500 24,200 Galvanized Steel Plate Galvanized Steel Plate 1180 x 450 x 132 1180 x 450 x 132 13.3 x 17.7 x 5.2 46.5 x 17.7 x 5.2 1420 x 500 x 34 1420 x 500 x 34 55.9 x 19.7 x 1.3 55.9 x 19.7 x 1.3 2 x 12 x 18 2 x 12 x 18 0.24 0.24 Cross Flow Fan Cross Flow Fan 30 30 0.30 0.30 13.3 / 12.1 / 10.9 14.6 / 13.3 / 11.5 515.4 / 427.1 / 384.8 575.4 / 469.5 / 406 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) 25(1) 25(1) 18.7(41.23) 18.7(41.23) 40 / 37 / 35 43 / 40 / 36 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C White White PT-UTC(Grill), PT-UTD(Panel)
1,100 881(Air outlet Hole)
1012
861
88
106.8 206.6 275.8 57.4 96.5 168.3
4 _ Ceiling Cassette 1-Way 500 34
27
Air suction grill Air discharge grill
3 4
(unit : mm)
Unit size(7k, 9k, 12k):ø12.7
Unit size(7k, 9k, 12k):ø6.35
Descripition
CHASSIS CODE: TU
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Gas pipe connection
2
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
(Panel Name: PT-UUC)
320.5
453
Liquid pipe connection
Name
ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2
Ceiling Cassette 1-way
1
Number
Indoor Units
3. Dimensions
Ceiling Cassette 1-Way _ 5
109.5
1012
1100
88
109.5
453 320.5
34
500
106.8 206.3 275.8 96.5 168.3 57.4
453 354.3
46.5
861
Air discharge grill
4
Unit size(7k, 9k, 12k):ø12.7
Unit size(7k, 9k, 12k):ø6.35
Descripition
(unit : mm)
CHASSIS CODE: TU
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Air suction grill
3
Gas pipe connection
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
(Panel Name: PT-UUD)
27
Liquid pipe connection
1
Name
ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2
2
Number
Indoor Units
117
Ceiling Cassette 1-way
3. Dimensions
247.5 180.6 65.3
453.8
173.8 96.1 91 20.6 57.4 31.7
6 _ Ceiling Cassette 1-Way
1,201(Air Outlet Hole)
1,420
1332
1176.4 65.1
500 34
453.8
4
CHASSIS CODE: TT
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Air suction grill Air discharge grill
3
Unit size(18k):ø12.7, (24k):ø15.88
Gas pipe connection
2
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
(Panel Name: PT-UTC)
(unit : mm) Descripition
Liquid pipe connection Unit size(18k):ø6.35, (24k):ø9.52
Name
ARNU18GTT*2 ARNU24GTT*2
Ceiling Cassette 1-way
1
Number
Indoor Units
3. Dimensions
Ceiling Cassette 1-Way _ 7
109.5
1332
1420
Ø14 15.2
65.3
453.8 247.5 180.6
173.8 97.1 91
500
57.4 31.7 20.6
46.5
34
65.1
22.3
57 132
1176.4
109.5
335
453.8
Air discharge grill
CHASSIS CODE: TT
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
4
Air suction grill
3
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
(Panel Name: PT-UTD)
96.5
Gas pipe connection
Unit size(18k):ø12.7, (24k):ø15.88
Liquid pipe connection Unit size(18k):ø6.35, (24k):ø9.52
Descripition
(unit : mm)
2
Name
ARNU18GTT*2 ARNU24GTT*2
1
Number
Indoor Units
44
Ceiling Cassette 1-way
3. Dimensions
4. Piping Diagrams
Heat Exchanger
EEV
Filter
:Cooling :Heating
Th2
Th3 C.F.F.
Filter
Indoor Units
Th1
lndoor unit
Refrigerant pipe connection port diameter [Unit: mm(inch)]
Model
Gas
Liquid
Ø12.7(1/2)
Ø6.35(1/4)
Ø15.88(5/8)
Ø9.52(3/8)
ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 ARNU18GTT*2 ARNU24GTT*2
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
8 _ Ceiling Cassette 1-Way
5. Wiring Diagrams TU, TT Chassis
LOCATION POINT Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Option pwb. Communication Step motor
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
FUNCTION Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Communication between main and option Communication between indoor and outdoor Step motor output
Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
Ceiling Cassette 1-Way _ 9
Indoor Units
CONNECTOR NUMBER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-OPTION CN-COM CN-VANE1
6. Capacity Tables 6.1 Cooling Capacity
Capacity Index
Indoor Units
2.2
2.8
3.6
Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
Cooling capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
Notes: TC: Total Capacity(kW)
10 _ Ceiling Cassette 1-Way
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
SHC: Sensible Heat Capacity(kW)
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
30 22 TC SHC kW kW 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
32 24 TC SHC kW kW 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8
1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2
6. Capacity Tables
Capacity Index
5.6
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
Notes: TC: Total Capacity(kW)
20 14 TC SHC kW kW
23 16 TC SHC kW kW
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9
5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1
30 22 TC SHC kW kW 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3
32 24 TC SHC kW kW 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6
4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.9 4.8 4.7 4.7 4.6 4.5 4.4 4.4 4.3
SHC: Sensible Heat Capacity(kW)
Ceiling Cassette 1-Way _ 11
Indoor Units
7.1
Outdoor air temp. (DB, °C)
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor Units
2.2
2.8
3.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
Heating capacity Indoor air temp. (DB, °C)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7 2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3
1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2 2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Notes: TC: Total Capacity(kW)
12 _ Ceiling Cassette 1-Way
6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
5.6
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2 4.8 4.9 5.2 5.5 5.8 6.0 6.1 6.2 6.5 6.7 7.0 7.5 7.9 8.0 8.2 8.2 8.2 8.2 8.2
4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7 4.8 4.9 5.2 5.4 5.8 6.0 6.1 6.2 6.5 6.7 7.0 7.5 7.6 7.6 7.6 7.6 7.6 7.6 7.6
4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3 4.8 4.9 5.2 4.9 5.1 5.4 5.5 5.6 5.8 6.0 6.2 6.6 6.9 7.1 7.1 7.1 7.1 7.1 7.1
4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 4.7 4.9 5.2 5.4 5.7 6.0 6.1 6.2 6.3 6.6 6.8 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9
4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 4.7 4.8 5.2 5.4 5.7 6.0 6.1 6.2 6.3 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7
4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.7 4.8 5.1 5.4 5.7 6.0 6.0 6.1 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2
Notes: TC: Total Capacity(kW)
Ceiling Cassette 1-Way _ 13
Indoor Units
7.1
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Indoor air temp. (DB, °C)
7. Air Velocity and Temperature Distribution(Reference Data) ARNU07GTU*2 Cooling
Heating
Discharge angle: 50°
Discharge angle: 60° Air velocity [m/s]
0.1
2m
2.0
2m
0.5
1
2. 5
0.1
0.5
22
.5
0.5
0. 1
3
0.1
0.1
0.5
1
0.5
1.5
1.0 3.5. 43 .0 5
Air velocity [m/s]
1.0
0.1
1.0
05
0. 5
0.5
1m
1.0
1
0.5
1m
0.1 1.0
1.5
0.5
0.5
0.5
0.5
1 0.
1.5
1.5
5 0.
0.1
0.5
1
0.5 1
4m
0.5
3m
2m
1m
0
5m
Temperature [°C]
4m
0.5 0.5
3m
01
2m
0
1m
0
Temperature [°C] 32 14
30
30
16 20
31
32
33
34
2m
31
36
3 37 8
32
24
22
31
35
34
26
32
2m
36
31
28
28
35
34
30
28
26
24
4327
32
30
41 3 396
32
1m
35
37 36
24
1m 34
28
26
30
33
28
36
24
32
28
30
26
4m
3m
28
26
28
30
5m
2m
31
0 5m
0
1m
35
4m
36
35
34
3m
2m
0
1m
0
ARNU09GTU*2 Cooling
Heating
Discharge angle: 50°
Discharge angle: 60°
Air velocity [m/s]
Air velocity [m/s] 2.5 0.5
3.0
2. 0 0.5
1.0 1.5
0.5
1.0
1.0
0.5
1
1
0.5
0.5
5 0.
1m
1.5
1m
0.5
01
1
0.5
1.5
0.5
0.5
2m
0.1
1
2
1.0
1.5
2m
0.1
0.1
5 0. 0.5
0.1
1.5 1.5
2. 5 3 .5 5 1.
0.5
0.1
1
3
0.1
0.5
1 0.5
4m
0.5
0
3m
2m
1m
0
5m
Temperature [°C]
4m
1.0 0.5
01
3m
2m
0
1m
0
Temperature [°C]
32
31 32
2284 20
32
38
18
30
32
35
30
22
32
43 38326354 9
5m
36
33 37 36 33
30
32
22
2m 36
26 28
26
31
2m
28
24
1m
36
33
34 35 37
34
3231
24
30
28
1m
4m
28
3m
26
26 30 28
2m
1m
32
0 0
33
32
26
30
5m
36
31
24
34
35
28
28
Indoor Units
0.1
0
0.5
0.5
5m
1
5m
4m
36
35
34
3m
2m
0 1m
0
Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m
14 _ Ceiling Cassette 1-Way
7. Air Velocity and Temperature Distribution(Reference Data) ARNU12GTU*2 Cooling
Heating
Discharge angle: 50°
Discharge angle: 60° Air velocity [m/s] 1.0
0.1
2. 5
0.5
1.0
1. 0. 05
2m 1.5
1m
0.5
0.1
0.1
0. 5
0.1
0.1
2
0.5
1.5
0.5
1
5 0.
1.50.5
1.5
1
1
0.5
0. 5
5 1. 0.5
2. 0
0.5
1 0.
2m
05
0.1
1.5
11.5 .0 2. 420.5 .0
2 11 .5
Air velocity [m/s]
1m
1.0
3m
2m
1.0
0
1m
0
01
5m
4m
0
3m
2m
1m
0
Temperature [°C]
32
32
32
32
28
31
32
37 41
30
3 4064
Temperature [°C]
0.5
1
4m
05
1
0.5
5 0.
5m
0.5
1.0
1.0
1.5
0.5
0.5
0.5
30
33
2m
2m
33
37 32
4m
36
35
34 36
31
24
26
34
24
28
3m
36
33
5m
26
30
1m
37
28
28
38
24
28
22
32
30
28
3635
28
31
26
28
30
1m
26
34
39
31
26
0
2m
5m
0
1m
37
35
34
32
4m
3536
3m
2m
0
1m
0
ARNU18GTT*2 Cooling
Heating
Discharge angle: 50°
Discharge angle: 60°
Air velocity [m/s]
Air velocity [m/s] 1
0.53
1
.5
5
01.5 43.5
2
2
2 1.5
1
2. 5
2m
2m
1
0.5
1
0.5 0.5
1
1.5
1.5
0.5
1.5 2
0.5
0.5
5 0.
0.5 0.5
1 0.5
5 0.
2. 5
0.5
.5 1 4
1.5
1m
1.5
1
1m
1
1
0.5
0.5
0.5
0.5
1 .5
0.5
0.5
4m
3m
0 2m
1m
0
0 5m
Temperature [°C]
4m
3m
2m
1m
0
Temperature [°C]
32
32
32
32
3364
30
30 39 40
30
32
26
22
2m 33
31
34
35
24
34
30
28 33
4m
3m
36
33
26
34
24
2826
5m
1m
36
28
36
37
1m
36
32
24
24
31
2628
28
2m
35 33
30
32
32 1 4
38
22
18 28
35
202
8
31
34
5m
31
0
0 2m
1m
0
5m
4m
3m
2m
1m
0
Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m
Ceiling Cassette 1-Way _ 15
Indoor Units
26
7. Air Velocity and Temperature Distribution(Reference Data) ARNU24GTT*2 Cooling
Heating
Discharge angle: 50째
Discharge angle: 60째
Air velocity [m/s]
Air velocity [m/s] 2. 5
1.5
1
2m
2 1.5
1.5
0.5
0.5
0.5
1m
05
0.5
1 1.5
0 .5
1.5 0.5
0.5
0.5
0. 1.55
1 5 0.
2m
1
2
0. 5
2
0.5
32
.5 4.5
5 0.
1 1. 52
0.5
1
1
2
3.5
1m
1
1
0.5
1.5
1
1
1
1.5
1
0.5 1
1
0.5
5m
4m
0.5
3m
2m
1
0
1m
0
0 5m
Temperature [째C]
4m
3m
2m
1m
0
Temperature [째C]
32
32
32 161
36
2
32
40
32333
26 22
30
2m
2m 38
22
31
28
28
4
39
32
20
28
36
36 37
36
33
36
1m
24
35
30
33
34
31
28
28
32
1m
34
26
35
37
24
33
24 4
28
28
26
34
31
30
Indoor Units
31
30
30 24
35
30
28
5m
4m
3m
0
0 2m
1m
0
5m
4m
3m
2m
1m
0
Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m
16 _ Ceiling Cassette 1-Way
8. Electric Characteristics Units
Power Supply
Input(W)
MFA
kW
FLA
1.23
15
0.03
0.18
40
40
1.23
15
0.03
0.18
40
40
1.23
15
0.03
0.18
40
40
1.38
15
0.03
0.30
70
70
TT
1.38
15
0.03
0.30
70
70
ARNU07GTU*2
TU
1.23
15
0.03
0.18
40
40
ARNU09GTU*2
TU
1.23
15
0.03
0.18
40
40
ARNU12GTU*2
TU
1.23
15
0.03
0.18
40
40
ARNU18GTT*2
TT
1.38
15
0.03
0.30
70
70
ARNU24GTT*2
TT
1.38
15
0.03
0.30
70
70
Model
Type
ARNU07GTU*2
TU
ARNU09GTU*2
TU
ARNU12GTU*2
TU
ARNU18GTT*2
TT
ARNU24GTT*2
Hz
50
Volts
220-240
60
220
Voltage Range MCA
IFM
Max:264 Min:198
Max:242 Min:198
Cooling Heating
Indoor Units
Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.
Ceiling Cassette 1-Way _ 17
9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
1.5m Microphone
Sound Levels dB(A) H M L
Model
Indoor Units
ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 ARNU18GTT*2 ARNU24GTT*2
32 35 38 40 43
29 34 35 37 40
25 32 32 35 36
Sound Pressure Level ARNU09GTU*2
ARNU12GTU*2 XP
WP
WP
WP
nc MVU
VP nc MVP nc MUU
UP
nc MUP nc MTU
TP
nc MTP nc MSU
SP
nc MSP
RP
nc MRU
a h @ t
ncMVP ncMUU
UP ncMUP ncMTU
TP ncMTP
nc MQU
QRU
RUP
UPP
QPPP
RPPP
TPPP
XPPP
o @b @c @f @Hh I
18 _ Ceiling Cassette 1-Way
ncMSU
SP
ncMSP
ncMRU
RP
nc MRP
QP VS
ncMVU
VP
QP
a h t VS
o @b @s @p @l @H b@ @RPµp @I
XP
o @b @s @p @l @H b@ @RPµp @I
o @b @s @p @l @H b@ @RPµp @I
ARNU07GTU*2 XP
NC-65
VP NC-60 NC-55
UP NC-50 NC-45
TP NC-40
NC-30
QRU
RUP
UPP
QPPP
RPPP
TPPP
o @b @c @f @Hh I
XPPP
NC-25
RP
ncMRP ncMQU
NC-35
SP
QP
Approximate Hearing Threshold VS
NC-20 NC-15
QRU
RUP
UPP
QPPP
RPPP
TPPP
o @b @c @f @Hh I
XPPP
9. Sound Levels ARNU24GTT*2
80
80
70
70
NC-65 60 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
NC-25
20 Approximate Hearing Threshold
NC-65 60 NC-60
NC-50
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
NC-45
40
NC-40 NC-35
30
NC-30
20
10
NC-25 Approximate Hearing Threshold 63
NC-20
125
250
500
1000
2000
4000
NC-15 8000
Indoor Units
10
NC-55
50
NC-20 NC-15
63
o @b @s @p @l @H b@ @RPµp @I
o @b @s @p @l @H b@ @RPµp @I
ARNU18GTT*2
Octave Band Center Frequency (Hz)
Ceiling Cassette 1-Way _ 19
10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Outlet
TEM P
Remote Controlle
Indoor Units
r
Inlet
Required Parts • Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose
Wired remote controller
Required Tools • Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer
20 _ Ceiling Cassette 1-Way
Ceiling board
500 or more
300 or less
500 or more
Above 2500 3300 or less
Ceiling Ceiling board
1000 or more
• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have the maintenance space.
200 or more
10.1 Selection of the best location
Unit:mm Floor
10. Installation 10.2 Ceiling opening dimensions and hanging bolt location 1,385 1,285
50
50
354 466
1,180
448
306
40
600
400
• The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.
40
Ceiling 250
TT Chassis
Level gauge
1,065 965
50
50
250
354 466
448
860
TU Chassis
• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.
(unit: mm)
Ceiling board
NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam. Air conditioner
Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table
2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.
Ceiling Cassette 1-Way _ 21
Indoor Units
• This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.
40
400
CAUTION
306
40
600
10. Installation Ceiling
Nut (W3/8 or M10)
70mm
Keep the length of the bolt from the bracket to 40mm
Hanging bolt (W3/8 or M10)
Flat washer for M10 (accessory) Ceiling board
Spring washer (M10)
Flat washer for M10 (accessory) Nut (W3/8 or M10)
Air conditioner body
Set screw of paper model (4 pieces)
Paper model for installation
Open the ceiling board along the outer edge of the paper model
Indoor Units
Adjust the same height
• The following parts are local purchasing. ① Hanging bolt - W 3/8 or M10 ② Nut - W 3/8 or M10 ③ Spring washer - M10 ④ Plate washer - M10
Ceiling board
CAUTION • Tighten the nut and bolt to prevent the unit from falling.
10.3 Wiring Connection • Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model] Terminal block of indoor unit 1(L)
2(N)
3
SODU B
SODU A
IDU B
IDU A
INT B
INT A
4
Indoor power input
[Except Multi VIII Heat Pump Model] Terminal block of outdoor unit Terminal block of indoor unit 1(L)
2(N)
3
4
Outdoor unit Indoor unit
SODU SODU IDU IDU INTERNET DRY1 DRY2 GND 12V
Indoor power input
WARNING Make sure that the screws of the terminal are not loose.
22 _ Ceiling Cassette 1-Way
Central controller
10. Installation 10.4 Installation of Decoration Panel (Panel Type) Before installing the decoration panel, always remove the paper template.
The decoration panel has its installation direction. 1. Open the air outlet vane, and extract side covers. 2. Remove the air inlet panel from the decoration panel.
3. Hook decoration panel to indoor unit, using hooks attached at the backside of both side of decoration panel. 4. Arrange wires not to get caught between decoration panel and indoor unit. 5. Screw 7 fixing screws. (7,9,12kBtu : 6 screws) 6. Connect the vane motor connector ,display connector and air inlet panel connector. 7. Install the air inlet panel (including the air filter) and side covers. Air conditioner unit
Indoor Units
Mesh Control box cover
Side cover Robot kit Decorative panel fixing screws (hexagon M6 screws) (tightening about 20mm)
Air inlet panel
Decorative panel Air outlet vane
CAUTION
Install certainly the decoration panel. Cool air leakage causes sweating. ⇨讀 Waterdrops fall.
Good example
Bad example Air conditioner unit Cool air leakage (no good) Ceiling board Decorative panel
Air conditioner unit Ceiling board Decorative panel
Fit the insulator (this part) and be careful for cool air leakage
Ceiling Cassette 1-Way _ 23
10. Installation 10.5 Installation of Decoration Panel(Grille Type) Before installing the decoration panel, always remove the paper template.
The decoration panel has its installation direction. 1. Open the air outlet vane, and extract side covers. 2. Remove the air inlet grille from the decoration panel.
3. Hook decoration panel to indoor unit, using hooks attached at the backside of both side of decoration panel. 4. Arrange wires not to get caught between decoration panel and indoor unit. 5. Screw 7 fixing screws. (7,9,12kBtu : 6 screws) 6. Connect the vane motor connector and display connector. (Plasma connector for plasma model)
Indoor Units
7. Install the air inlet grille (including the air filter) and side covers.
Air conditioner unit
Mesh Control box cover
Side cover Plasma filter (applied only to plasma model) Decorative panel fixing screws (hexagon M6 screws) (tightening about 20mm) Air inlet grille
Decorative panel Air inlet grille
CAUTION
Install certainly the decoration panel. Cool air leakage causes sweating. ⇨讀 Waterdrops fall.
Good example
Bad example Air conditioner unit Cool air leakage (no good) Ceiling board Decorative panel
Fit the insulator (this part) and be careful for cool air leakage
24 _ Ceiling Cassette 1-Way
Air conditioner unit Ceiling board Decorative panel
10. Installation 10.6 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe 25mm and pipe fittings
Upward routing not allowed
Pipe clamp Indoor unit
Maintenance drain port
• Be sure to install heat insulation on the drain piping. 1/50~1/100
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
Max 700mm
Drain test
Feed water
Flexible drain hose (accessory) Main drain pipe
Drain pump
Drain port
Glue the joint
Drain hose connection Use the clip (accessory)
• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Drain pan
CAUTION Max 300mm Metal clamp Flexible drain hose
Hanger bracket 1/50~1/100 slope Max 700mm
The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.
Hanger distance 1~15m
Insulation
Ceiling Cassette 1-Way _ 25
Indoor Units
The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:
10. Installation
Indoor Units
CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.
WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
TEMP
yes
Remote Controller
no
TEMP
Remote Controller
5feet (1.5meters)
TEMP
Controller Remote
no
no
Fig.1 Typical locations for remote controller
26 _ Ceiling Cassette 1-Way
11. Accessories Name
Drain hose
Clamp metal
Quantity
1 EA
2 EA
Washer for hanging bracket 8 EA
Plastic band
Insulation for fitting
4 EA
1 SET
Shape
for gas pipe
for liquid pipe
Paper pattern for installation
Installation and Owner's manual
Quantity
1EA
1EA
Shape
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
Ceiling Cassette 1-Way _ 27
Indoor Units
Name
Indoor unit Ceiling Cassette 2-Way 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of functions Category
Air flow
Air purifying
Installation
Convenience
Individual control
Special function kit
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU18GTL*2, ARNU24GTL*2 2 Auto O 4/5/4 X O O X Option O O O X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Ceiling Cassette 2-way _ 1
Indoor Units
Reliability
Function
2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Body Dimensions (WxDxH) Front Panel
Indoor Units
Coil
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
mm inch mm inch m3 W A CMM cfm
Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)
Ø, V, Hz
2Way Ceiling Cassette ARNU18GTL*2 5.6 4,800 19,100 6.3 5,400 21,500 Galvanized Steel Plate 830 x 550 x 225 32.6 x 21.6 x 8.9 1,050 x 640 x 28.5 41.3 x 25.2 x 1.1 2 x 11 x 20 0.13 Cross Flow Fan 20 x 2 0.18 x 2 13 / 12 / 10 459 / 424 / 353 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 22(48.5) 40 / 36 / 32 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog PT-HL*
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
2 _ Ceiling Cassette 2-way
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Body Dimensions (WxDxH) Front Panel Coil
m3 W A CMM cfm
Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)
Ø, V, Hz
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling Cassette 2-way _ 3
Indoor Units
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
mm inch mm inch
2Way Ceiling Cassette ARNU24GTL*2 7.1 6,100 24,200 8.0 6,900 27,300 Galvanized Steel Plate 830 x 550 x 225 32.6 x 21.6 x 8.9 1,050 x 640 x 28.5 41.3 x 25.2 x 1.1 2 x 11 x 20 0.13 Cross Flow Fan 20 x 2 0.18 x 2 17 / 15 / 13 601 / 530 / 459 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø9.52(3/8) Ø15.88(5/8) 25(1) 22(48.5) 42 / 38 / 34 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog PT-HL*
3
4
144.2
921(Air Outlet Hole) 1,050
893
931.2 830 34 1
4-R15
482 550
2 205.5 69.2
35.6
162.4 640 28.5
4 _ Ceiling Cassette 2-way 177.1 225
6.5
92
206.5 69.2
Air discharge grill
Air suction grill
Gas pipe connection
Liquid pipe connection
Name
(unit : mm)
Unit size(24k):ø15.88
Unit size(18k):ø12.7
Unit size(24k):ø9.52
Unit size(18k):ø6.35
Descripition
ARNU18GTL*2 ARNU24GTL*2
Ceiling Cassette 2-way
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
CHASSIS CODE: TL
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
4
3
2
1
Number
Indoor Units
3. Dimensions
4. Piping Diagrams
Heat Exchanger
EEV
Filter
:Cooling :Heating
Th2
Th3 C.F.F.
Filter Th1
lndoor unit
[Unit: mm(inch)]
Model
Gas
Liquid
ARNU18GTL*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU24GTL*2
Ø15.88(5/8)
Ø9.52(3/8)
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
Ceiling Cassette 2-way _ 5
Indoor Units
Refrigerant pipe connection port diameter
5. Wiring Diagrams
Indoor Units
TL Chassis
CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO
SPEC AC Power supply Fan motor output Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
DESCRIPTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
6 _ Ceiling Cassette 2-way
6. Capacity Tables 6.1 Cooling Capacity
Capacity Index
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
32 24 TC SHC kW kW
10
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.7
4.2
7.4
4.2
12
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.7
4.2
7.3
4.1
14
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.7
4.2
7.2
4.1
16
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.7
4.2
7.1
4.0
18
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.7
4.2
7.0
4.0
20
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.7
4.2
6.9
3.9
21
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.7
4.2
6.8
3.9
23
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.7
4.2
6.7
3.8
25
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.6
4.2
6.6
3.8
27
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.4
4.1
6.6
3.7
29
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.4
4.0
6.5
3.7
31
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.3
3.9
6.4
3.6
33
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.2
3.9
6.3
3.6
35
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
6.0
4.0
6.0
3.8
6.2
3.5
37
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
5.8
3.9
5.9
3.7
6.1
3.5
39
3.8
3.2
4.5
3.6
5.2
3.9
5.6
3.9
5.7
3.9
5.8
3.7
6.0
3.4
Outdoor air temp. (DB, °C)
Notes: TC: Total Capacity(kW)
SHC: Sensible Heat Capacity(kW)
Ceiling Cassette 2-way _ 7
Indoor Units
5.6
Cooling capacity
6. Capacity Tables Cooling capacity
Indoor Units
Capacity Index
7.1
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
32 24 TC SHC kW kW
10
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.5
5.3
9.3
5.3
12
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.5
5.3
9.2
5.2
14
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.5
5.3
9.1
5.2
16
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.5
5.3
9.0
5.1
18
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.5
5.3
8.8
5.0
20
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.5
5.3
8.7
5.0
21
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.5
5.3
8.7
4.9
23
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.5
5.3
8.5
4.9
25
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.4
5.3
8.4
4.8
27
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.2
5.1
8.3
4.7
29
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.1
5.1
8.2
4.7
31
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
8.0
5.0
8.1
4.6
33
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
7.8
4.9
7.9
4.5
35
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.6
5.1
7.7
4.8
7.8
4.4
37
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.4
5.0
7.5
4.7
7.7
4.4
39
4.8
4.1
5.7
4.5
6.6
4.9
7.1
5.0
7.2
4.9
7.4
4.6
7.6
4.3
Outdoor air temp. (DB, °C)
Notes: TC: Total Capacity(kW)
8 _ Ceiling Cassette 2-way
SHC: Sensible Heat Capacity(kW)
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
-19.8 -20.0
kW 4.2
kW 4.2
kW 4.2
kW 4.2
kW 4.2
kW 4.2
-18.8 -19.0
4.3
4.3
4.3
4.3
4.3
4.3
-16.7 -17.0
4.6
4.6
4.6
4.6
4.6
4.5
-14.7 -15.0
4.9
4.8
4.3
4.8
4.8
4.8
-12.6 -13.0
5.1
5.1
4.5
5.0
5.0
5.0
-10.5 -11.0
5.4
5.4
4.8
5.4
5.3
5.3
-9.5 -10.0
5.4
5.4
4.9
5.4
5.4
5.4
-8.5
-9.1
5.5
5.5
5.0
5.5
5.5
5.4
-7.0
-7.6
5.7
5.7
5.1
5.6
5.6
5.5
-5.0
-5.6
6.0
6.0
5.4
5.8
5.8
5.5
-3.0
-3.7
6.2
6.2
5.5
6.1
5.9
5.5
0.0
-0.7
6.6
6.6
5.8
6.1
5.9
5.5
3.0
2.2
7.0
6.7
6.2
6.1
5.9
5.5
5.0
4.1
7.1
6.7
6.3
6.1
5.9
5.5
7.0
6.0
7.2
6.7
6.3
6.1
5.9
5.5
9.0
7.9
7.2
6.7
6.3
6.1
5.9
5.5
11.0
9.8
7.2
6.7
6.3
6.1
5.9
5.5
13.0 11.8
7.2
6.7
6.3
6.1
5.9
5.5
15.0 13.7
7.2
6.7
6.3
6.1
5.9
5.5
Notes: TC: Total Capacity(kW)
Ceiling Cassette 2-way _ 9
Indoor Units
5.6
Heating capacity
6. Capacity Tables Heating capacity
Indoor Units
Outdoor air temp. Capacity Index DB(°C) WB(°C)
7.1
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
-19.8 -20.0
kW 5.4
kW 5.4
kW 5.4
kW 5.3
kW 5.3
kW 5.3
-18.8 -19.0
5.5
5.5
5.5
5.5
5.4
5.4
-16.7 -17.0
5.8
5.8
5.8
5.8
5.8
5.8
-14.7 -15.0
6.2
6.1
5.5
6.1
6.1
6.1
-12.6 -13.0
6.5
6.5
5.8
6.4
6.4
6.4
-10.5 -11.0
6.8
6.8
6.0
6.8
6.7
6.7
-9.5 -10.0
6.9
6.9
6.2
6.9
6.9
6.8
-8.5
-9.1
7.0
7.0
6.3
7.0
7.0
6.8
-7.0
-7.6
7.3
7.3
6.5
7.1
7.1
7.0
-5.0
-5.6
7.6
7.6
6.8
7.4
7.4
7.0
-3.0
-3.7
7.9
7.9
7.0
7.7
7.5
7.0
0.0
-0.7
8.4
8.4
7.4
7.8
7.5
7.0
3.0
2.2
8.9
8.6
7.8
7.8
7.5
7.0
5.0
4.1
9.0
8.6
8.0
7.8
7.5
7.0
7.0
6.0
9.2
8.6
8.0
7.8
7.5
7.0
9.0
7.9
9.2
8.6
8.0
7.8
7.5
7.0
11.0
9.8
9.2
8.6
8.0
7.8
7.5
7.0
13.0 11.8
9.2
8.6
8.0
7.8
7.5
7.0
15.0 13.7
9.2
8.6
8.0
7.8
7.5
7.0
Notes: TC: Total Capacity(kW)
10 _ Ceiling Cassette 2-way
7. Air Velocity and Temperature Distribution(Reference Data) ARNU24GTL*2 Cooling
Heating
Discharge angle: 40째
Discharge angle: 60째
Air velocity [m/s]
Air velocity [m/s] 2.7m
2.0
2.5
3.0
3.0
2.5
2m
2.0
1.5
1.5
1.0
1.0
0.5
4m
2.7m 2.5 2.0 1.5
1m
2m
1m
0m
1m
2m
0m 4m
3m
Temperature [째C]
0.5
4m
3m
2m
20
20
2.7m 21
22
0m
32 31
2m
23
1m
2m
0m 4m
3m
24
1m
28 26
1m
0m
1m
2m
3m
0m 4m
4m
27
3m
2m
1m
29
2.7m
32 31
30
24
2m
0.5
1m
2m
30 27
28
29 28
0m
1m
28 27
1m
26
2m
3m
0m 4m
Ceiling Cassette 2-way _ 11
Indoor Units
21
23
3m
1m
1.0
Temperature [째C]
22
4m
2m
1.5
1.0
0.5
3m
2.5 2.0
8. Electric Characteristics Units Model
Type
ARNU18GTL*2
TL
ARNU24GTL*2
TL
ARNU18GTL*2
TL
ARNU24GTL*2
TL
Power Supply Hz
Volts
50
220-240
60
220
Voltage Range MCA
IFM
Input(W)
MFA
kW
FLA
Cooling Heating
Max:264
0.52
15
0.04
0.41
70
70
Min:198
0.52
15
0.04
0.41
70
70
Max:242
0.52
15
0.04
0.41
70
70
Min:198
0.52
15
0.04
0.41
70
70
Symbols:
Indoor Units
MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.
12 _ Ceiling Cassette 2-way
9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
1.5m Microphone
Sound Levels dB(A)
Model
H
M
L
ARNU18GTL*2
40
36
32
ARNU24GTL*2
42
38
34
ARNU24GTL*2
80
80
70
70
NC-65 60 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
20
10
NC-25 Approximate Hearing Threshold 63
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
ARNU18GTL*2
NC-65 60 NC-60
NC-15 250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
20
NC-20
125
Indoor Units
Sound Pressure Level
10
NC-25 Approximate Hearing Threshold 63
NC-20 NC-15 125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
Ceiling Cassette 2-way _ 13
10. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
TEMP
Remote Controller
Air Intake Air Outlet
Required Parts • Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose
Required Tools • Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer
14 _ Ceiling Cassette 2-way
50 or more
Ceiling Board
50 or more
30 or less
Ceiling Ceiling Board
Above 200 300 or less
• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have sufficient maintenance space.
20 or more
10.1 Selection of the best location
100 or more
Indoor Units
Anti-bacteria filter
Unit:cm Floor
10. Installation 10.2 Ceiling opening dimensions and hanging bolt location • The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions. Ceiling board
Ceiling Level gauge
CAUTION
NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.
Air conditioner
Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.
Ceiling Cassette 2-way _ 15
Indoor Units
• This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.
• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.
10. Installation Ceiling
Nut (W3/8 or M10)
90mm
Keep the length of the bolt from the bracket to 40mm
Hanging bolt (W3/8 or M10)
Flat washer for M10 False (accessory) ceiling board
Air Conditioner body
Flat washer for M10 (accessory) Nut (W3/8 or M10)
Set screw of paper pattern (4 pieces)
Paper pattern for installation
Open the ceiling board along the outer edge of the paper pattern
Indoor Units
Adjust the same height
• The following parts are locally purchased. ① Hanging Bolt - W 3/8 or M10 ② Nut - W 3/8 or M10 ③ Spring Washer - M10 ④ Plate Washer - M10
False ceiling board
CAUTION • Tighten the nut and bolt to prevent the unit from falling.
10.3 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU B
IDU B
SODU A
IDU A
INT B
INT A
4
INDOOR POWER INPUT
[Except Multi VIII Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU
4
B
A
INDOOR POWER INPUT
WARNING Make sure that the screws of the terminal are not loose.
16 _ Ceiling Cassette 2-way
INTERNET DRY1 DRY2 GND 12V
IDU -
-
B
A
-
-
-
-
Outdoor Unit
10. Installation 10.4 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.
The decoration panel has its installation direction.
1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included in the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter). Air conditioner unit
Indoor Units
Decorative panel fixing screws (hexagon M6 screws) Temporary fitting at 2 poles (Tightening about 10mm)
Piping side
Control box cover Cover
Plasma filter
Louver motor
Key holes
Decorative panel fixing screws (Hexagon M6 screw)
Decorative panel Push
Ratch pull
Inlet Grille
CAUTION Install the decoration panel otherwise cool air leakage causes condensation. ⇨讀 Water drops fall.
Correct method
Wrong method Air conditioner unit Cool air leakage (no good) Ceiling board Decoration panel
Air conditioner unit Ceiling board Decoration panel
Fit the insulator (this part) and be careful for cool air leakage
Ceiling Cassette 2-way _ 17
10. Installation 10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): Make sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.
Upward routing not allowed
Pipe clamp Indoor unit
Maintenance drain port
Piping material: Polyvinyl chloride pipe inner diameter Ø 25mm and pipe fittings 1/50~1/100
• Make sure to install heat insulation on the drain piping.
MAX 700mm
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:
Feed water
Flexible drain hose (accessory) Main drain pipe
Drain Pump
Drain port
Glue the joint
Drain hose connection Use the clip (accessory)
• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Make sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Drain pan
CAUTION The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.
Max 300mm
Hanger distance 1~15m
Metal clamp Flexible drain hose Insulation
18 _ Ceiling Cassette 2-way
Hanger Bracket 1/50~1/100 slope Max 700mm
Indoor Units
Drain test
10. Installation CAUTION
HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)
WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
TEMP
yes
Remote Controller
no
TEMP
Controller Remote
TEMP
Remote Controller
5feet (1.5meters)
no
no
Fig.1 Typical locations for remote controller
Ceiling Cassette 2-way _ 19
Indoor Units
After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.
11. Accessories Standard Accessories Name
Clamp metal
Drain hose
Insulation for fitting
Quantity
2 EA
1 EA
1 set
Washer for hanging bracket 8 EA
Clamp (Tie Wrap) 4 EA
Bolt
(Other)
4 EA • Paper pattern for installation • Owner's manual • Installation manual
Shape
for gas pipe
for liquid pipe
Indoor Units
• Screws for fixing panels are attached to decoration panel.
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
20 _ Ceiling Cassette 2-way
Indoor unit Ceiling Cassette 4-way 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of functions Category
Air flow
Indoor Units
Air purifying
Installation
Reliability
Convenience
Individual control
Special function kit
Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Elevation Grill Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU05GTR*2, ARNU07GTR*2, ARNU09GTR*2, ARNU12GTR*2 ARNU15GTQ*2, ARNU18GTQ*2, ARNU24GTP*2, ARNU28GTP*2 ARNU36GTN*2, ARNU42GTM*2, ARNU48GTM*2 4 Auto O 4/5/4 X O O O X Option O O X X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory (TM,TN,TP only) Accessory Accessory Accessory Accessory X Accessory -
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. * Plasma kit and Elevation Grille are not applicable at the same time
1 _ Ceiling Cassette 4-way
2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Body Dimensions(WxDxH) Front Panel Coil
m3 W A CMM cfm
Drive Motor type Temperature Control
Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Packaged kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)
Ø, V, Hz mm2 mm2
4 Way Ceiling Cassette ARNU07GTR*2 ARNU09GTR*2 2.2 2.8 1,900 2,400 7,500 9,600 2.5 3.2 2,200 2,800 8,500 10,900 Galvanized Steel Plate Galvanized Steel Plate 570 x 570 x 214 570 x 570 x 214 22.4 x 22.4 x 8.4 22.4 x 22.4 x 8.4 700 x 700 x 30 700 x 700 x 30 27.5 x 27.5 x 1.2 27.5 x 27.5 x 1.2 1 x 8 x 18 2 x 8 x 18 0.21 0.21 Turbo Fan Turbo Fan 43 x 1 43 x 1 0.2 0.2 7.5 / 7.0 / 6.6 8.0 / 7.5 / 7.1 265 / 247 / 212 283 / 265 / 251 Direct Direct BLDC BLDC Microprocessor, Microprocessor, Thermostat for cooling Thermostat for cooling and heating and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 13.1(28.9) 14.2(31.3) 15.4(33.9) 16.5(36.3) 29 / 27 / 26 30 / 29 / 27 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog PT-UQC
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling Cassette 4-way _ 2
Indoor Units
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
mm inch mm inch
ARNU05GTR*2 1.6 1,400 5,500 1.8 1,500 6,100 Galvanized Steel Plate 570 x 570 x 214 22.4 x 22.4 x 8.4 700 x 700 x 30 27.5 x 27.5 x 1.2 1 x 8 x 18 0.21 Turbo Fan 43 x 1 0.2 7.5 / 7.0 / 6.6 265 / 247 / 212 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 13.1(28.9) 15.4(33.9) 29 / 27 / 26 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog
2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Body Dimensions(WxDxH) Front Panel
Indoor Units
Coil
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
mm inch mm inch m3 W A CMM cfm
Drive Motor type Temperature Control
Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Packaged kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)
Ø, V, Hz mm2 mm2
ARNU12GTR*2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 570 x 570 x 214 22.4 x 22.4 x 8.4 700 x 700 x 30 27.5 x 27.5 x 1.2 2 x 8 x 18 0.21 Turbo Fan 43 x 1 0.2 8.7 / 8.0 / 7.0 307 / 283 / 247 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 14.2(31.3) 16.5(36.3) 32 / 30 / 27 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog
4 Way Ceiling Cassette ARNU15GTQ*2 ARNU18GTQ*2 4.5 5.6 3,900 4,800 15,400 19,100 5.0 6.3 4,300 5,400 17,100 21,500 Galvanized Steel Plate Galvanized Steel Plate 570 x 570 x 256 570 x 570 x 256 22.4 x 22.4 x 10.1 22.4 x 22.4 x 10.1 700 x 700 x 30 700 x 700 x 30 27.5 x 27.5 x 1.2 27.5 x 27.5 x 1.2 2 x 10 x 18 2 x 10 x 18 0.27 0.27 Turbo Fan Turbo Fan 43 x 1 43 x 1 0.2 0.2 11.0 / 10.0 / 9.3 11.2 / 11.0 / 10.0 388 / 353 / 328 396 / 388 / 353 Direct Direct BLDC BLDC Microprocessor, Microprocessor, Thermostat for cooling Thermostat for cooling and heating and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 15.5(34.2) 15.5(34.2) 18.0(39.7) 18.0(39.7) 36 / 34 / 32 37 / 35 / 34 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog PT-UQC
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
3 _ Ceiling Cassette 4-way
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specifications * Model Name A:Basic, C:Plasma Type Model
4 Way Ceiling Cassette ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 Cooling Capacity 7.1 8.2 10.6 6,100 7,100 9,100 24,200 28,000 36,200 Heating Capacity 8.0 9.2 11.9 6,900 8,000 10,200 27,300 31,500 40,600 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions Body mm 840 x 840 x 204 840 x 840 x 204 840 x 840 x 246 (WxDxH) inch 33.0 x 33.0 x 8.0 33.0 x 33.0 x 8.0 33.0 x 33.0 x 9.7 Front Panel mm 950 x 950 x 25 950 x 950 x 25 950 x 950 x 25 inch 37.4 x 37.4 x 1 37.4 x 37.4 x 1 37.4 x 37.4 x 1 Coil Rows x Columns x FPI 2 x 8 x 19 2 x 8 x 19 2x10x19 Face Area m3 0.40 0.40 0.57 Fan Type Turbo Fan Turbo Fan Turbo Fan Motor Outputx Number W 30 30 135 Running Current A 0.15 0.15 0.56 Air Flow Rate(H / M / L) CMM 17 / 15 / 13 19 / 16 / 14 25 / 21 / 19 cfm 600 / 529 / 459 671 / 565 / 494 883 / 742 / 671 Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Safety Device Fuse Fuse Fuse Pipe Liquid Side mm(inch) Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Connections Gas Side mm(inch) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 25(1) 25(1) 25(1) Net Weight Body kg(lbs) 20.8(45.8) 20.8(45.8) 23.5(51.8) Noise Level (Sound Press, 1.5m, H / M / L) dB(A) 36 / 34 / 31 39 / 35 / 33 43 / 40 / 37 Power Supply 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cord CV2.0 X 3C CV2.0 X 3C CV2.0 X 3C Transmission cable CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C Panel Color Morning fog Morning fog Morning fog Panel Name(Accessory) PT-UMC Elevation Grill(Accessory) PTEGM0 Unit kW kcal/h Btu/h kW kcal/h Btu/h
1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling Cassette 4-way _ 4
Indoor Units
Notes:-
2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity
Heating Capacity
Casing Dimensions (WxDxH)
Body Front Panel
Indoor Units
Coil Fan
Rows x Columns x FPI Face Area Type Motor Outputx Number Running Current Air Flow Rate(H / M / L)
Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch mm inch m3 W A CMM cfm
Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Pipe Liquid Side mm(inch) Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level (Sound Press, 1.5m, H / M / L) dB(A) Power Supply Ø, V, Hz Refrigerant Control Power cord Transmission cable Panel Color Panel Name(Accessory) Elevation Grill(Accessory)
4 Way Ceiling Cassette ARNU42GTM*2 ARNU48GTM*2 12.3 14.1 10,600 12,100 42,000 48,100 13.8 15.9 11,000 13,200 43,800 51,200 Galvanized Steel Plate Galvanized Steel Plate 840 x 840 x 288 840 x 840 x 288 33.0 x 33.0 x 11.3 33.0 x 33.0 x 11.3 950 x 950 x 25 950 x 950 x 25 37.4 x 37.4 x 1 37.4 x 37.4 x 1 2 x 12 x 19 2 x 12 x 19 0.57 0.57 Turbo Fan Turbo Fan 135 135 0.56 0.56 30 / 27 / 24 31 / 29 / 27 1,059 / 954 / 848 1,059 / 1,024 / 954 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø9.52(3/8) Ø9.52(3/8) Ø15.88(5/8) Ø15.88(5/8) 25(1) 25(1) 25.6(56.4) 25.6(56.4) 44 / 41 / 38 46 / 43 / 41 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV2.0 X 3C CV2.0 X 3C CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C Morning fog Morning fog PT-UMC PTEGM0
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
5 _ Ceiling Cassette 4-way
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling Cassette 4-way _ 6
6
A
CEILING OPENING
700
473
380(Air outlet hole)
700 B
376(Inlet Grille)
22.5
5
4
523 59.5 84.5
3
A ARROW VIEW
30 19 142.5
2 1
79 53 48
128 570
165
461 570
517
Power supply connection Air discharge grill Air suction grill
3 4 5 6
(unit : mm)
VP25(Φ32)
Unit size(5k, 7k, 9k, 12k):ø12.7
Unit size(5k, 7k, 9k, 12k):ø6.35
Descripition
B ARROW VIEW
500mm or more*
• REQUIRED SPACE
500mm or more*
CHASSIS CODE: TR
500mm or more*
500mm or more*
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Gas pipe connection Drain pipe connection
2
Liquid pipe connection
Name
1
Number
ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2
Ceiling Cassette 4-way
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
Branch Duct Connection
63
69
517 214 34.5
4R20
5
570
Indoor Units
R3
3. Dimensions
A
CEILING OPENING
700
473
380(Air outlet hole)
B
6
376(Inlet Grille) 22.5
5
4
59.5
523
30 19 142.5
2 1
3
A ARROW VIEW
125 95.5
4R20
79 48 570
165
461 570
517
5
174
R3
517
Power supply connection Air discharge grill Air suction grill
3 4 5 6 Note
Gas pipe connection Drain pipe connection
2
Liquid pipe connection
Name
1
Number
(unit : mm)
VP25(Φ32)
Unit size(15k, 18k):Ø12.7
Unit size(15k, 18k):Ø6.35
Descripition
ARNU15GTQ*2 ARNU18GTQ*2
Ceiling Cassette 4-way
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
500mm or more*
• REQUIRED SPACE
500mm or more*
CHASSIS CODE: TQ
500mm or more*
500mm or more*
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
B ARROW VIEW
Branch Duct Connection
63
68
570
256
7 _ Ceiling Cassette 4-way 76 94
Indoor Units
3. Dimensions
700
Ceiling Cassette 4-way _ 8
31
475
71
B ARROW VIEW
35
Ceiling opening
870-920(CEILING OPENING SPACE) 786(SUSPENSION POSITION)
500(Air outlet Hole) 737 950
614(Inlet Grille) 682(SUSPENSION POSITION)
ø70
OUTDOOR AIR INTAKE (DIRECT CONNECTION)
B
62
669(SUSPENSION POSITION) 420 393
13-ø 3, 3 Hole
26
71
300 OR LESS
420
950
25 870-920(CEILING OPENING SPACE)
6
2
A
65 40
5
671 108 60
1
840
165
350
53.5
60 82 99
4
3 Branch Duct Connection
80
840
787
787
804
204
BRANCH DUCT CONNECTION
684 840 92
VP25(Φ32)
Unit size(24k, 28k):ø15.88
Unit size(24k, 28k):ø9.52
92
10 350
50
92
165
92
500mm or more*
BRANCH DUCT CONNECTION
500mm or more*
CHASSIS CODE: TP
500mm or more*
500mm or more*
• REQUIRED SPACE
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
A ARROW VIEW
165
(unit : mm) Descripition
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Air suction grill
4
Air discharge grill
Drain pipe connection Power supply connection
3
6
Gas pipe connection
2
5
Liquid pipe connection
Name
1
Number
ARNU24GTP*2 ARNU28GTP*2
Ceiling Cassette 4-way
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
13-ø 3, 3 Hole
79
204 154 79 41.5
32 50 50
Indoor Units
4-R20
3. Dimensions
13-ø 3, 3 Hole
35
71
B
ø70
OUTDOOR AIR INTAKE (DIRECT CONNECTION)
B ARROW VIEW
31
475
Ceiling opening
786(SUSPENSION POSITION)
870-920(CEILING OPENING SPACE)
682(SUSPENSION POSITION)
500(Air outlet Hole) 737 950
614(Inlet Grille) 25
2
870-920(CEILING OPENING SPACE)
6
110
1
A
60 840
165
350
103 141
246
3
4
Branch Duct Connection
53.5
80
840
78
5
420
300 OR LESS 80
669(SUSPENSION POSITION) 420 393
44
71
950 40 107
246 195 100 52
BRANCH DUCT CONNECTION 43 60
4-R20
13-ø 3, 3 Hole
100
9 _ Ceiling Cassette 4-way 60
165
10 350
92
165
92 BRANCH DUCT CONNECTION
500mm or more*
500mm or more*
CHASSIS CODE: TN
500mm or more*
500mm or more*
• REQUIRED SPACE
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
A ARROW VIEW
92
VP25(Φ32)
Unit size(36k):ø15.88
Unit size(36k):ø9.52
Descripition
(unit : mm)
1. Unit should be installed in compliance with the installation manual in the product box.
Note
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
92
5
Air suction grill
Air discharge grill
4 6
Drain pipe connection Power supply connection
3
Gas pipe connection
2
Name Liquid pipe connection
ARNU36GTN*2
Ceiling Cassette 4-way
1
Number
Indoor Units
3. Dimensions
Ceiling Cassette 4-way _ 10
6
75
31
475
ø70
B
OUTDOOR AIR INTAKE (DIRECT CONNECTION)
B ARROW VIEW
35
71
Ceiling opening
682(SUSPENSION POSITION) 110
870-920(CEILING OPENING SPACE) 786(SUSPENSION POSITION)
300 OR LESS
420
614(Inlet Grille)
25 870-920(CEILING OPENING SPACE)
500(Air outlet Hole) 737 950
2
A
1 100 84
669(SUSPENSION POSITION) 420 393
13-ø 3, 3 Hole
71
288 165
237 350
53.5
Branch Duct Connection
3
4 76 60
136 13-ø 3, 3 Hole
BRANCH DUCTCONNECTION
60
840
Air suction grill
5 6
(unit : mm)
VP25(Φ32)
Unit size(42k, 48k):ø15.88
Unit size(42k, 48k):ø9.52
Descripition
10 350
92
165
92
500mm or more*
CHASSIS CODE: TM
500mm or more*
500mm or more*
• REQUIRED SPACE
500mm or more*
BRANCH DUCT CONNECTION
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
A ARROW VIEW
165
92
Air discharge grill
4
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
92
Power supply connection
3
Note
Gas pipe connection Drain pipe connection
2
Liquid pipe connection
Name
ARNU42GTM*2 ARNU48GTM*2
Ceiling Cassette 4-way
1
Number
100
5
Indoor Units
4-R20
3. Dimensions
950
4. Piping Diagrams
Heat Exchanger
:Cooling :Heating
EEV Filter
Th3
Th2 Turbo Fan
Filter
lndoor unit
Indoor Units
Th1
Refrigerant pipe connection port diameter [Unit: mm(inch)]
Model
Gas
Liquid
ARNU05GTR*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU07GTR*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU09GTR*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU12GTR*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU15GTQ*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU18GTQ*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU24GTP*2
Ø15.88(5/8)
Ø9.52(3/8)
ARNU28GTP*2
Ø15.88(5/8)
Ø9.52(3/8)
ARNU36GTN*2
Ø15.88(5/8)
Ø9.52(3/8)
ARNU42GTM*2
Ø15.88(5/8)
Ø9.52(3/8)
ARNU48GTM*2
Ø15.88(5/8)
Ø9.52(3/8)
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
11 _ Ceiling Cassette 4-way
5. Wiring Diagrams TR/TQ Chassis
LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
Ceiling Cassette 4-way _ 12
Indoor Units
CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC
5. Wiring Diagrams
Indoor Units
TM/TN/TP Chassis
CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE1 / VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC
LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
13 _ Ceiling Cassette 4-way
6. Capacity Tables 6.1 Cooling Capacity
Capacity Index
1.6
2.8
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
Notes: TC: Total Capacity(kW)
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
32 24 TC SHC kW kW 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0
1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.1 1.1 1.8 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.7
SHC: Sensible Heat Capacity(kW)
Ceiling Cassette 4-way _ 14
Indoor Units
2.2
Outdoor air temp. (DB, °C)
Cooling capacity
6. Capacity Tables Cooling capacity
Capacity Index
Indoor Units
3.6
4.5
5.6
Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
Notes: TC: Total Capacity(kW)
15 _ Ceiling Cassette 4-way
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
SHC: Sensible Heat Capacity(kW)
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
32 24 TC SHC kW kW 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8 5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0
2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.2 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4
6. Capacity Tables Cooling capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
Capacity Index
Outdoor air temp. (DB, °C)
7.1
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1
7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2
5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 5.0
8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4
5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4 5.3 5.2 5.1 5.1 5.0 4.9 4.8
9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6
5.4 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9 4.8 4.7 4.6 4.6 4.5 4.4
8.2
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9
6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7
5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8
8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2
5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9
8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.5 8.4
6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.9 5.8
9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.7 9.4 9.3 9.2 9.0 8.9 8.7 8.5
6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.1 6.1 5.9 5.8 5.7 5.6 5.5
10.8 10.6 10.5 10.4 10.2 10.1 10.0 9.9 9.7 9.6 9.5 9.3 9.2 9.0 8.9 8.8
6.3 6.2 6.1 6.1 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.4 5.3 5.2 5.1
10.6
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2
6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3
8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5
6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9
9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9
7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6
7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.0 10.8
7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.7 7.5
12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.5 12.2 12.1 11.9 11.7 11.4 11.2 11.0
8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.1 7.9 7.8 7.7 7.6 7.4 7.3 7.1
13.9 13.7 13.6 13.4 13.2 13.0 12.9 12.8 12.6 12.4 12.2 12.0 11.8 11.7 11.5 11.3
8.1 8.0 7.9 7.8 7.7 7.6 7.6 7.5 7.3 7.3 7.1 7.0 6.9 6.8 6.7 6.6
SHC: Sensible Heat Capacity(kW)
Ceiling Cassette 4-way _ 16
Indoor Units
Notes: TC: Total Capacity(kW)
32 24 TC SHC kW kW
6. Capacity Tables Cooling capacity
Capacity Index
Indoor Units
12.3
14.1
Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5
9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3
11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2
7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3
Notes: TC: Total Capacity(kW)
17 _ Ceiling Cassette 4-way
8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2
8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1
8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2
SHC: Sensible Heat Capacity(kW)
13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.8 12.5 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 14.7 14.4
9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 8.9 8.7 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.2 10.0
30 22 TC SHC kW kW
32 24 TC SHC kW kW
14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.1 14.0 13.8 13.5 13.3 13.0 12.8 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.6 16.2 16.1 15.8 15.5 15.2 14.9 14.7
16.2 15.9 15.8 15.6 15.3 15.1 15.0 14.8 14.6 14.4 14.2 14.0 13.7 13.5 13.4 13.1 18.5 18.3 18.1 17.8 17.6 17.3 17.2 17.0 16.7 16.5 16.3 16.0 15.8 15.5 15.3 15.1
9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.4 9.2 9.1 8.9 8.8 8.6 8.4 8.3 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.8 10.5 10.4 10.2 10.0 9.9 9.7 9.5
9.4 9.3 9.2 9.1 9.0 8.8 8.8 8.6 8.5 8.4 8.3 8.2 8.0 7.9 7.8 7.7 10.8 10.7 10.6 10.4 10.3 10.1 10.1 9.9 9.8 9.6 9.5 9.4 9.2 9.1 8.9 8.8
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
1.6
2.8
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
1.2 1.2 1.3 1.4 1.5 1.5 1.5 1.6 1.6 1.7 1.8 1.9 2.0 2.0 2.1 2.1 2.1 2.1 2.1 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7
1.2 1.2 1.3 1.4 1.5 1.5 1.5 1.6 1.6 1.7 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
1.2 1.2 1.3 1.2 1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2
1.2 1.2 1.3 1.4 1.4 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
1.2 1.2 1.3 1.4 1.4 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.2 1.2 1.3 1.4 1.4 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
Notes: TC: Total Capacity(kW)
Ceiling Cassette 4-way _ 18
Indoor Units
2.2
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Heating capacity
6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor Units
3.6
4.5
5.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6 3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2
2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7
2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0 3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3
2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Notes: TC: Total Capacity(kW)
19 _ Ceiling Cassette 4-way
6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
7.1
10.6
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2 6.2 6.3 6.7 7.1 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 10.2 10.4 10.6 10.6 10.6 10.6 10.6
5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6 6.2 6.3 6.7 7.0 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 9.8 9.8 9.8 9.8 9.8 9.8 9.8
5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0 6.2 6.3 6.7 6.3 6.6 7.0 7.1 7.3 7.5 7.8 8.1 8.5 9.0 9.2 9.2 9.2 9.2 9.2 9.2
5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 6.1 6.3 6.7 7.0 7.4 7.8 7.9 8.1 8.2 8.5 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9
5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 6.1 6.3 6.7 7.0 7.4 7.7 7.9 8.1 8.2 8.5 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6
5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.1 6.3 6.6 7.0 7.4 7.7 7.8 7.9 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
8.0 8.2 8.7 9.2 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 13.2 13.4 13.7 13.7 13.7 13.7 13.7
8.0 8.2 8.7 9.0 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 12.7 12.7 12.7 12.7 12.7 12.7 12.7
8.0 8.2 8.7 8.2 8.6 9.0 9.2 9.4 9.7 10.1 10.4 11.0 11.6 11.9 11.9 11.9 11.9 11.9 11.9
7.9 8.2 8.7 9.0 9.5 10.1 10.2 10.5 10.6 11.0 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
7.9 8.1 8.7 9.0 9.5 10.0 10.2 10.5 10.6 11.0 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2
7.9 8.1 8.6 9.1 9.5 10.0 10.1 10.2 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4
Notes: TC: Total Capacity(kW)
Ceiling Cassette 4-way _ 20
Indoor Units
8.2
Indoor air temp. (DB, °C)
6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
12.3
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
9.2 9.5 10.1 10.6 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 15.3 15.5 15.9 15.9 15.9 15.9 15.9
9.2 9.5 10.1 10.5 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 14.8 14.8 14.8 14.8 14.8 14.8 14.8
9.2 9.5 10.1 9.5 10.0 10.4 10.7 10.9 11.3 11.7 12.1 12.8 13.5 13.8 13.8 13.8 13.8 13.8 13.8
9.1 9.5 10.1 10.5 11.0 11.7 11.9 12.1 12.2 12.8 13.3 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4
9.1 9.4 10.1 10.5 11.0 11.6 11.9 12.1 12.2 12.8 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
9.1 9.4 9.9 10.5 11.0 11.6 11.7 11.8 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1
14.1
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
10.7 11.0 11.6 12.2 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.7 17.9 18.3 18.3 18.3 18.3 18.3
10.7 11.0 11.6 12.1 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.0 17.0 17.0 17.0 17.0 17.0 17.0
10.7 11.0 11.6 10.9 11.5 12.0 12.3 12.6 13.0 13.5 13.9 14.7 15.5 15.9 15.9 15.9 15.9 15.9 15.9
10.5 11.0 11.6 12.1 12.7 13.5 13.7 14.0 14.1 14.7 15.3 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4
10.5 10.8 11.6 12.1 12.7 13.4 13.7 14.0 14.1 14.7 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9
10.5 10.8 11.4 12.1 12.7 13.4 13.5 13.6 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Notes: TC: Total Capacity(kW)
21 _ Ceiling Cassette 4-way
7. Air Velocity and Temperature Distribution(Reference Data) ARNU05GTR*2, ARNU07GTR*2, ARNU09GTR*2 Cooling
Heating
Discharge angle: 40°
Discharge angle: 50°
Air velocity [m/s]
Air velocity [m/s] 2.7m
2.7m 2.0
2.0
2.0
1.5 1.0
1.5 1.0
2m
2.0 1.5
1.5 1.0
2.5m
1.5m
0m
1.5m
0m 2.5m
1.0 0.5
0.5
1m
0.5
0.5
2.5m
2m
1.5m
1m
0m
1.5m
0m 2.5m
Temperature [°C]
Temperature [°C]
2.7m
2.7m 2m
18
18 20
20
22
21
21 2m 27
18
24
27
18 24
24
1m
22
33
1m
24
2.5m
1.5m
0m
1.5m
0m 2.5m
2.5m
1.5m
0m
1.5m
0m 2.5m
ARNU12GTR*2 Cooling
Heating
Discharge angle: 40°
Discharge angle: 50° Air velocity [m/s]
Air velocity [m/s]
2.7m
2.7m 2.0
2.0 1.5
2.0
2m 1.5
2.0 1.5
1.0 1.0
1.0
0.5
2.5m
2m
1.5 1.0
0.5
1m
1m
0.5
0.5
1.5m
0m
1.5m
0m 2.5m
2.5m
1.5m
0m
0m 2.5m
1.5m
Temperature [°C]
Temperature [°C]
2.7m
2.7m 18
33
18
20
2m
20
22
33
30 24
22
2m
30
27
27
24
21
21
1m
1m 24
2.5m
1.5m
24
0m
1.5m
0m 2.5m
2.5m
1.5m
0m
1.5m
0m 2.5m
Ceiling Cassette 4-way _ 22
Indoor Units
33
7. Air Velocity and Temperature Distribution(Reference Data) ARNU15GTQ*2 Cooling
Heating
Discharge angle: 40°
Discharge angle: 50°
Air velocity [m/s]
Air velocity [m/s]
2.7m
2.7m 2.0
2.0
2.0 1.5
1.0
1m
1m
0m
1m
2m
4m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
2.7m
2.7m 18
18 20
20
33
33
2m
2m 22
22
21
24
24
1m
27
24
24
3m
21
1m 27
4m
0m
Temperature [°C]
Temperature [°C]
Indoor Units
0.5
0.5
3m
1m
1.0
1.0
0.5
2m
1.5
1.5
0.5 3m
2m
2m 1.5
1.0
4m
2.0
2m
1m
0m
1m
2m
3m
4m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
0m
ARNU18GTQ*2 Cooling
Heating
Discharge angle: 40°
Discharge angle: 50°
Air velocity [m/s]
Air velocity [m/s]
2.7m
2.7m 2.0
2.0
2.0
1.5
2m
1.0
4m
3m
2m
1.5
1.5 1m
1.0
0.5 0m
1m
3m
4m
0m
4m
3m
2m
1m
1.0
0.5
2m
2m
1.5
1.0
0.5 1m
2.0
0.5
1m
0m
1m
2m
3m
4m
Temperature [°C]
Temperature [°C]
2.7m
2.7m 18 20
18
22
33
20
2m
2m
2m
30
21
22
24
3m
33
30
1m
4m
0m
21 24
27
27
1m
24
24
1m
0m
1m
2m
23 _ Ceiling Cassette 4-way
3m
4m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
0m
7. Air Velocity and Temperature Distribution(Reference Data) ARNU24GTP*2 Cooling
Heating
Discharge angle: 40°
Discharge angle: 50°
Air velocity [m/s]
Air velocity [m/s]
2.7m
2.7m 2.0
2.0
2m
2m 2.0
1.5
3m
1.0
1.0
1.0 4m
1m
1.5
2m
1m
0m
1m
3m
4m
0m
4m
2m
0.5
1m
0m
1m
2m
3m
4m
0m
Temperature [°C] 2.7m
2.7m
18 20 22
2m
24
2m
1m
0m
1m
2m
3m
4m
0m
4m
2m
3m
1m
24
24
27
23
24
30 22
22
1m 23
33
33 30
2m
1m
27
0m
1m
2m
3m
4m
0m
ARNU28GTP*2 Cooling
Heating
Discharge angle: 40°
Discharge angle: 50°
Air velocity [m/s]
Air velocity [m/s]
2.7m 2.0
2m
2.0
1.0
1.0
1.0
2m
2m 1.5
1m
1.5
1.0 3m
2.7m
3.0 2.0
1.5
1m
1.5
4m
3.0 2.0
2.5
2.5
1m
0m
1m
2m
3m
4m
0m
0.5
4m
3m
2m
0.5
1m
0m
1m
2m
3m
4m
Temperature [°C]
Temperature [°C]
2.7m
2.7m 18
33
18
33
2m
2m 21 22
22 23
4m
3m
2m
0m
23
1m
0m
1m
2m
3m
4m
0m
30
24
1m
30
1m
27
4m
3m
2m
21
24
1m
0m
27 1m
2m
3m
4m
0m
Ceiling Cassette 4-way _ 24
Indoor Units
18 20 22
3m
3m
1m
1.0
0.5
2m
Temperature [°C]
4m
2.0
7. Air Velocity and Temperature Distribution(Reference Data) ARNU36GTN*2 Cooling
Heating
Discharge angle: 40°
Discharge angle: 50°
Air velocity [m/s]
Air velocity [m/s]
3.0 2.5 2.0
2.7m
3.0 2.5 2.0
2m 1.5
1.5 1.0 5m
4m
3m
1m
1m
2m
0m
1m
2m
3m
4m
Indoor Units
1.0
3m
2m
1m
2.7m
0m
1m
2m
3m
4m
0m 5m
22
23
1m
0m
2m
1m
2m
3m
4m
0m 5m
30
24 22
1m 23
2m
33
2m
20
22
2.7m
33
18
20
3m
4m
1m
Temperature [°C]
18
4m
5m
2m
2.0
1.0
0m 5m
2.7m
3.5 3.0 2.5
2.0
1.0
Temperature [°C]
5m
3.5 3.0 2.5
30
27
5m
4m
3m
2m
1m
24 22
1m
4m
0m 5m
27
0m
1m
2m
3m
ARNU42GTM*2 Cooling
Heating
Discharge angle: 40°
Discharge angle: 50°
Air velocity [m/s]
Air velocity [m/s]
3.2m
3.2m 4.0
4.0
4.0 3.0
3.0
3.0
2m
3.0
4.0
2m
1m
5m
4m
3m
1m 2.0
2.0 1.0
2.0 1.0 2m
1m
0m
1m
2m
2.0
1.0
3m
4m
0m 5m
5m
4m
3m
2m
1.0
1m
0m
1m
2m
3m
4m
Temperature [°C]
Temperature [°C] 3.2m
3.2m
2m
20
33
33
18
18
24
20
22
22
4m
3m
2m
1m
0m
1m
2m
25 _ Ceiling Cassette 4-way
3m
22 27
24
24
30
22
1m
4m
0m 5m
5m
4m
2m
24 30
5m
0m 5m
3m
2m
1m
1m
27
0m
1m
2m
3m
4m
0m 5m
7. Air Velocity and Temperature Distribution(Reference Data) ARNU48GTM*2 Cooling
Heating
Discharge angle: 40째
Discharge angle: 50째
Air velocity [m/s]
Air velocity [m/s]
3.2m 4.0
1.0 4m
3m
2m
1m
0m
1m
2m
2m
3.0
3.0
1m
2.0 1.0
2.0
4.0
2m
3.0
3.0
5m
3.2m 4.0
4.0
1m 2.0
2.0
1.0
3m
4m
0m 5m
4m
5m
3m
2m
1m
1.0
0m
1m
2m
3m
4m
0m 5m
Temperature [째C]
Temperature [째C]
3.2m 33
2m
20
20
33
2m 22
24
22
24
1m 22 24
5m
4m
24
3m
2m
1m
1m
0m
1m
2m
3m
30
30 27
22
4m
0m 5m
5m
4m
3m
2m
1m
27
0m
1m
2m
3m
4m
0m 5m
Ceiling Cassette 4-way _ 26
Indoor Units
3.2m 18
18
8. Electric Characteristicss Units
Indoor Units
Model
Type
Power Supply Hz
Volts
Voltage Range MCA
IFM
Input(W)
MFA
kW
FLA
Cooling Heating
ARNU05GTR*2
TR
0.25
15
0.043
0.2
30
30
ARNU07GTR*2
TR
0.25
15
0.043
0.2
30
30
ARNU09GTR*2
TR
0.25
15
0.043
0.2
30
30
ARNU12GTR*2
TR
0.25
15
0.043
0.2
30
30
ARNU15GTQ*2
TQ
0.25
15
0.043
0.2
30
30
ARNU18GTQ*2
TQ
0.25
15
0.043
0.2
30
30
0.22
15
0.03
0.17
33
33
50
220-240
MAX : 264 MIN:198
ARNU24GTP*2
TP
ARNU28GTP*2
TP
0.22
15
0.03
0.17
33
33
ARNU36GTN*2
TN
0.81
15
0.135
0.64
144
144
ARNU42GTM*2
TM
0.81
15
0.135
0.64
144
144
ARNU48GTM*2
TM
0.81
15
0.135
0.64
144
144
ARNU05GTR*2
TR
0.25
15
0.043
0.2
30
30
ARNU07GTR*2
TR
0.25
15
0.043
0.2
30
30
ARNU09GTR*2
TR
0.25
15
0.043
0.2
30
30
ARNU12GTR*2
TR
0.25
15
0.043
0.2
30
30
ARNU15GTQ*2
TQ
0.25
15
0.043
0.2
30
30
ARNU18GTQ*2
TQ
0.25
15
0.043
0.2
30
30
ARNU24GTP*2
TP
0.22
15
0.03
0.17
33
33
ARNU28GTP*2
TP
0.22
15
0.03
0.17
33
33
ARNU36GTN*2
TN
0.81
15
0.135
0.64
144
144
ARNU42GTM*2
TM
0.81
15
0.135
0.64
144
144
ARNU48GTM*2
TM
0.81
15
0.135
0.64
144
144
60
220
MAX : 242 MIN:198
Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.
27 _ Ceiling Cassette 4-way
9. Sound Levels Overall Notes: - Sound measured at 1.5m below the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
Ceiling 1.5m
Model H 29 29 30 32 36 37
Model H 36 39 43 44 46
ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 ARNU42GTM*2 ARNU48GTM*2
Sound Level dB(A) L M 34 31 35 33 40 37 41 38 43 41
Indoor Units
ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2 ARNU15GTQ*2 ARNU18GTQ*2
Sound Level dB(A) L M 26 27 26 27 27 29 27 30 32 34 34 35
Sound Pressure Level ARNU07GTR*2
ARNU09GTR*2 80
70
70
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
10
NC-25 Approximate Hearing Threshold 63
NC-60
125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20 NC-15 8000
NC-65
60
10
NC-25 Approximate Hearing Threshold 63
Octave Band Sound Pressure Level (dB re 20μPa )
80
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
ARNU05GTR*2 80
NC-60
125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20 NC-15 8000
NC-65
60
10
NC-25 Approximate Hearing Threshold 63
NC-20
125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)
NC-15 8000
Ceiling Cassette 4-way _ 28
9. Sound Levels ARNU12GTR*2
80
ARNU15GTQ*2
NC-65 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
Approximate Hearing Threshold
10
63
NC-60 50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
NC-20 NC-15 125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)
NC-55
NC-25
20
NC-25
20
NC-65
60
10
Approximate Hearing Threshold 63
8000
125
ARNU24GTP*2
NC-60 NC-55 NC-50 NC-45 NC-40 NC-35
30
NC-30 20
10
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
NC-65
40
63
250
500
NC-15 1000 2000 4000 8000
4000
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25 Approximate Hearing Threshold 63
NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 Approximate Hearing Threshold 63
Octave Band Sound Pressure Level (dB re 20μPa )
NC-60
20
250
500
63
125
250
500
NC-15 1000 2000 4000 8000
NC-60
NC-15 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
29 _ Ceiling Cassette 4-way
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20
10
Approximate Hearing Threshold 63
125
NC-20
250
500
NC-15 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
125
250
500
1000
2000
4000
NC-15 8000
NC-65 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20
10
Approximate Hearing Threshold 63
125
NC-20
250
500
NC-15 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
NC-65
60
NC-20
60
NC-20
70
NC-20
125
10
NC-25 Approximate Hearing Threshold
ARNU36GTN*2
ARNU48GTM*2
NC-65
30
NC-30
Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)
70
40
NC-35
30
20
NC-15 8000
80
50
NC-40
70
ARNU42GTM*2 Octave Band Sound Pressure Level (dB re 20μPa )
2000
NC-45
40
70
10
80
60
NC-50
80
Octave Band Center Frequency (Hz)
10
1000
NC-55
50
80
NC-20
125
500
20
NC-25 Approximate Hearing Threshold
NC-60
ARNU28GTP*2
70
50
250
NC-65
60
Octave Band Center Frequency (Hz)
80
60
70
NC-20
Octave Band Sound Pressure Level (dB re 20μPa )
60
Octave Band Sound Pressure Level (dB re 20μPa )
80
70
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
70
Indoor Units
ARNU18GTQ*2
80
10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Anti-bacteria filter
Indoor Units
Air Intake
TEM P
Remote Controll
er
Air Outlet Wired Remote Controller(Optional)
Required Parts
Required Tools
• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose
• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer
Ceiling Board
50 or more
30 or less
50 or more
Above 250 360 or less
Ceiling Ceiling Board
100 or more
• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have sufficient maintenance space.
30 or more
10.1 Selection of the best location
Unit:cm Floor
Ceiling Cassette 4-way _ 30
10. Installation 10.2 Ceiling opening dimensions and hanging bolt location • The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions.
Ceiling Ceiling board
Level gauge
TQ/TR Chassis
TM/TN/TP Chassis
585~660(Ceiling opening)
875(Ceiling opening)
461
Unit:mm
CAUTION • This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.
875(Ceiling opening)
684(Hanging bolt)
840 Unit size 840 Unit size
671
517
570
585~660(Ceiling opening)
787(Hanging bolt)
570 319
523
Indoor Units
517
Unit:mm
• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.
NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam. Air conditioner
Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.
31 _ Ceiling Cassette 4-way
10. Installation Ceiling
Nut (W3/8 or M10)
Flat washer for M10 (accessory) Ceiling board
150mm
Keep the length of the bolt from the bracket to 40mm
Hanging bolt (W3/8 or M10)
Air Conditioner body
Ceiling board Keep the length of 15~18mm between the air conditioner bottom surface and the ceiling surface
Flat washer for M10 (accessory) Nut (W3/8 or M10)
Set screw of paper model (4 pieces) Open the ceiling board along the outer edge of the paper model
Paper model for installation
• The following parts are locally purchased. ① Hanging Bolt - W 3/8 or M10 ② Nut - W 3/8 or M10 ③ Spring Washer - M10 ④ Plate Washer - M10
CAUTION
10.3 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Indoor cord Remote control cord power cord
• TR/TQ Chassis [Multi V III Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
[Except Multi VIII Heat Pump Model] SODU B
SODU A
IDU B
IDU A
INT B
INT A
Terminal Block Indoor
4
1(L)
INDOOR POWER INPUT
2(N)
3
SODU
4
B
A
Outdoor Unit
INTERNET DRY1 DRY2 GND 12V
IDU -
-
B
A
-
-
-
-
INDOOR POWER INPUT
• TM/TN/TP Chassis [Multi V III Heat Pump Model]
[Except Multi VIII Heat Pump Model]
Terminal Block Indoor
Terminal Block Indoor
1(L) 2(N) 3(L) 4(N)
5(A) 5(B) RD
POWER INPUT
SODU B
SODU A
IDU B
IDU A
INT B
INT A
YL BK
TO AIR FRESH KIT
Terminal Block Indoor
Terminal Block Indoor
SODU
1(L) 2(N) 3(L) 4(N)
5(A) 5(B) RD
B
POWER INPUT
YL BK
A
IDU B
INTERNET DRY1 DRY2 GND 12V A
B
A
-
-
-
-
Outdoor Unit
TO AIR FRESH KIT
WARNING Make sure that the screws of the terminal are not loose.
Ceiling Cassette 4-way _ 32
Indoor Units
• Tighten the nut and bolt to prevent the unit from falling.
10. Installation 10.4 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.
The decoration panel has its installation direction.
1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included in the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter). Piping side
Indoor Units
Air conditioner unit
Control box cover Decoration panel fixing screws (hexagon M5 screws) Temporally fitting at 2 places (Tightening about 10mm)
Louver motor
Decoration panel
Display Lead wire for louver motor and display
Decoration panel fixing screws (Hexagon M5 screw)
CAUTION Install certainly the decoration panel. Cool air leakage causes sweating.
Inlet Grille
Good example
⇨讀 Water drops fall.
Bad example Air conditioner unit
Ceiling board Decoration panel Fit the insulator (this part) and be careful for cool air leakage
33 _ Ceiling Cassette 4-way
Air conditioner unit Air
Cool air leakage (no good) Ceiling board Decoration panel
10. Installation 10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings
Upward routing not allowed
Pipe clamp Indoor unit
Maintenance drain port
• Be sure to install heat insulation on the drain piping.
1/50~1/100
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
MAX 700mm
Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Flexible drain hose (accessory) Main drain pipe
Drain Pump
Drain port
Glue the joint
Drain hose connection Use the clip (accessory)
• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Drain pan
The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.
Max 300mm
Hanger distance 1~15m
Metal clamp Flexible drain hose
Hanger Bracket 1/50~1/100 slope
Max 700mm
CAUTION
Insulation
CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.
HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).
Ceiling Cassette 4-way _ 34
Indoor Units
Feed water
10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
Indoor Units
- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
TEMP
yes
Remote Controller
no
TEMP
Remote Controller
5feet (1.5meters)
TEMP
Controller Remote
no
no
Fig.1 Typical locations for remote controller
35 _ Ceiling Cassette 4-way
11. Accessories Standard Accessories Name
Drain hose
Clamp metal
Quantity
1 EA
2 EA
Shape
Washer for hanging backet 8 EA
Clamp (Tie Wrap)
Insulation for fitting
4 EA
1 SET
for gas pipe
Bolt
(Other)
4 EA • Paper pattern for installation • Owner's manual • Installation manual
for liquid pipe
Indoor Units
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
Ceiling Cassette 4-way _ 36
Indoor unit Ceiling Concealed Duct (High Static) 1. List of functions 2. Specifications 3. Dimensions & Gravity point 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure(E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of functions Category
Air flow
Air purifying
Reliability
Convenience
Individual control
Special function kit
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2, ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2, ARNU28GBGA2 , ARNU36GBGA2, ARNU42GBGA2, ARNU48GBRA2, URNU76GB8A2, URNU96GB8A2 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O Accessory Accessory Accessory Accessory X Accessory Accessory -
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Ceiling Concealed Duct(High Static) _ 1
Indoor Units
Installation
Function
2. Specifications Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Dimensions(WxDxH) Body
mm inch
Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A)
Indoor Units
Coil
Power Supply Refrigerant Control Power cable Transmission cable
Ø, V, Hz mm2 mm2
ARNU07GBHA2 2.2 1,900 7,500 2.5 2,200 8,500 Galvanized Steel Plate 882 x 450 x 260 34.7 x 17.7 x 10.2 2 x 10 x 21 0.15 Sirocco Fan 118 0.92 8.5 / 7.5 / 6.0 300 / 265 / 212 8(78) 8.5 / 8.0 / 7.5 300 / 282 / 265 6(59) Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 26(57.4) 34 / 33 / 32 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C
Ceiling Concealed Duct -High Static ARNU09GBHA2 ARNU12GBHA2 2.8 3.6 2,400 3,100 9,600 12,300 3.2 4.0 2,800 3,400 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate 882 x 450 x 260 882 x 450 x 260 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2 2 x 10 x 21 2 x 10 x 21 0.15 0.15 Sirocco Fan Sirocco Fan 118 118 0.92 0.92 10.0 / 8.5 / 7.5 12.0 / 10.0 / 8.5 353 / 300 / 265 424 / 353 / 300 8(78) 8(78) 8.5 / 8.0 / 7.5 11.0 / 8.5 / 7.5 300 / 282 / 265 388 / 300 / 265 6(59) 6(59) Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 26(57.4) 26(57.4) 35 / 34 / 33 37 / 35 / 34 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
2 _ Ceiling Concealed Duct(High Static)
ARNU15GBHA2 4.5 3,900 15,400 5.0 4,300 17,100 Galvanized Steel Plate 882 x 450 x 260 34.7 x 17.7 x 10.2 2 x 10 x 21 0.15 Sirocco Fan 118 0.92 13.5 / 12.0 / 8.5 477 / 424 / 300 8(78) 13.5 / 12.0 / 11.0 477 / 424 / 388 6(59) Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 26(57.4) 39 / 38 / 37 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specifications Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Dimensions(WxDxH) Body
mm inch
Power Supply Refrigerant Control Power cable Transmission cable
Ø, V, Hz mm2 mm2
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling Concealed Duct(High Static) _ 3
Indoor Units
Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Coil
Ceiling Concealed Duct(High Static) ARNU18GBHA2 ARNU24GBHA2 ARNU28GBGA2 5.6 7.1 8.2 4,800 6,100 7,100 19,100 24,200 28,000 6.3 8.0 9.2 5,400 6,900 8,000 21,500 27,300 31,500 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 882 x 450 x 260 882 x 450 x 260 1,182 x 450 x 298 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2 46.5 x 17.7 x 11.7 3 x 10 x 21 3 x 10 x 21 3 x 12 x 21 0.15 0.15 0.26 Sirocco Fan Sirocco Fan Sirocco Fan 118 118 390 0.92 0.92 2.30 15.5 / 13.5 / 12.4 18.3 / 16.9 / 15.5 25.9 / 24.1 / 21.8 547 / 477 / 438 646 / 597 / 547 915 / 851 / 770 8(78) 8(78) 10(98) 15.3 / 13.6 / 10.3 19.0 / 16.4 / 14.5 25.3 / 21.8 / 17.6 540 / 480 / 364 671 / 579 / 512 893 / 770 / 622 6(59) 6(59) 8(78) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø6.35(1/4) Ø9.52(3/8) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) Ø15.88(5/8) 25(1) 25(1) 25(1) 26.5(58.4) 26.5(58.4) 38.0(83.8) 42.5 / 41 / 37 45 / 43 / 41 44 / 42 / 40 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
2. Specifications Type Model Cooling Capacity
Heating Capacity
Ceiling Concealed Duct(High Static) Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Dimensions(WxDxH) Body
mm inch
Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A)
Indoor Units
Coil
Power Supply Refrigerant Control Power cable Transmission cable
Ø, V, Hz mm2 mm2
ARNU36GBGA2 ARNU42GBGA2 ARNU48GBRA2 10.6 12.3 14.1 9,100 10,600 12,100 36,200 42,000 48,100 11.9 13.8 15.9 10,200 11,000 13,200 40,600 43,800 51,200 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 1,182 x 450 x 298 1,182 x 450 x 298 1,230 x 590 x 380 46.5 x 17.7 x 11.7 46.5 x 17.7 x 11.7 48.4 x 23.2 x 15 3 x 12 x 21 3 x 12 x 21 3 x 13 x 19 0.26 0.26 0.38 Sirocco Fan Sirocco Fan Sirocco Fan 390 390 390 2.30 2.30 2.40 32.3 / 29.0 / 25.3 34.5 / 32.3 / 30.7 44.8 / 40.6 / 33.3 1,141 / 1,024 / 894 1,218 / 1,141 / 1,084 1,582 / 1,434 / 1,176 10(98) 10(98) 14(137) 28.4 / 25.3 / 21.8 32.0 / 28.4 / 27.2 44.4 / 39.5 / 33.5 1,003 / 894 / 770 1,130 / 1,003 / 961 1,568 / 1,395 / 1,183 8(78) 8(78) 10(98) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) 25(1) 25(1) 25(1) 38(83.8) 38(83.8) 53(117) 46 / 44 / 42 48 / 46 / 45 45 / 43 / 41 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
4 _ Ceiling Concealed Duct(High Static)
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specifications Type Model
Ceiling Concealed Duct(High Static) URNU76GB8A2 URNU96GB8A2 22.4 28 Cooling Capacity 19,300 24,100 76,400 95,900 25.2 31.5 Heating Capacity 21,700 27,100 86,000 107,500 Casing Galvanized Steel Plate Galvanized Steel Plate mm 1,562 x 688 x 460 1,562 x 688 x 460 Dimensions(WxDxH) Body inch 61.5 x 27.1 x 18.1 61.5 x 27.1 x 18.1 Rows x Columns x FPI 3 x 21 x 19 3 x 21 x 19 Coil Face Area m3 0.59 0.59 Type Sirocco Fan Sirocco Fan Motor Output x Number W 375 x 2 375 x 2 Running Current A 4.50 4.50 Air Flow Rate(H / M / L) CMM 60.0 / 50.0 / 50.0 72.0 / 64.0 / 64.0 (High Mode-factory set) cfm 2,119 / 1,766 / 1,766 2542 / 2,260 / 2,260 Fan External Static Pressure mmAq(Pa) 22(216) 22(216) Air Flow Rate(H / M / L) CMM 64.0 / 50.0 / 50.0 76.0 / 64.0 / 64.0 (Standard Mode) cfm 2,260 / 1,766 / 1,766 2,684 / 2,260 / 2,260 External Static Pressure mmAq(Pa) 15(147) 15(147) Drive Direct Direct Motor type BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse Fuse Liquid Side mm(inch) Ø9.52(3/8) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø19.05(3/4) Ø22.2(7/8) Drain Pipe(Internal Dia.) mm(inch) 25(1) 25(1) Net Weight kg(lbs) 87(192) 87(192) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) 50 / 48 / 48 52 / 50 / 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Unit kW kcal/h Btu/h kW kcal/h Btu/h
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling Concealed Duct(High Static) _ 5
Indoor Units
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
5
7.
R3
60
114
450
260
47
355
158
20
175
75
21
49
64
24
243
5
428
6
882
212
882
87 750
932
745
243
119
65
108
30
115
4
450 47
133 127 106
6 _ Ceiling Concealed Duct(High Static)
450
219 119
1 2
100
50
70
260
29
51
3
123 140
48 52 165
31
Air suction
6
Unit size(7k,9k,12k,18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k,9k,12k,18k):ø12.7 Unit size(24k):ø15.88
Descripition
(unit : mm)
Gravity point
CHASSIS CODE: BH
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Air discharge
5
Drain pipe connection Power supply connection
3 4
Gas pipe connection
Liquid pipe connection
Name
2
1
Number
ARNU07GBHA2 ARNU09GBHA2 ARNU12GBHA2 ARNU15GBHA2 ARNU18GBHA2 ARNU24GBHA2
Ceiling Concealed Duct (High Static)
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
101
Indoor Units
3. Dimensions & Gravity point
355
224
Ceiling Concealed Duct(High Static) _ 7
ø1
00
60
152
224
20
298
220
23
186
450
232
49
565
243
5
6
1,182
232
1,182
87 830
1,230
243
232
115
108
29
75
87
355 450 158 113
219 136
1,043
1
100
50
2 261
165
3
122 140
47 53
32
Note
(unit : mm)
Unit size(28k,36k,42k):ø15.88
Unit size(28k,36k,42k):ø9.52
Descripition
Gravity point
CHASSIS CODE: BG
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Air suction
Air discharge
5 6
Power supply connection
4
Drain pipe connection
Gas pipe connection
2 3
Liquid pipe connection
1
Name
ARNU28GBGA2 ARNU36GBGA2 ARNU42GBGA2
Ceiling Concealed Duct (High Static)
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
102 51
Number
Indoor Units
4
3. Dimensions & Gravity point
R6
0
60
198
312
380
50
215
5
621
279
6
1,230
1,004
241
118 1,004
1,284 1,230
279 215
120
114
4
2
90
1
135 190 260
115
101 83
Name
Air discharge Air suction
4 5 6
Unit size(48k):ø15.88
Unit size(48k):ø9.52
Descripition
(unit : mm)
Gravity point
CHASSIS CODE: BR
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Power supply connection
3
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
3
Gas pipe connection Drain pipe connection
2
Liquid pipe connection
1
Number 26
ARNU48GBRA2
Ceiling Concealed Duct (High Static)
72 123 221 122 144
1,092
477 590 56 168
25
303
32
140
590
8 _ Ceiling Concealed Duct(High Static) 185 174
302 293
Indoor Units
3. Dimensions & Gravity point
Ceiling Concealed Duct(High Static) _ 9
460
460
688
293
5
329
819
6 1,622
1,562
320
1,220
1,562
329
115
688 30
222
560 64
290 161
20
440
318
1,396
358
68
18
109
58
122 60 70 64
397
Air suction
(unit : mm)
Unit size(76k):ø19.05 Unit size(96k):ø22.2
Unit size(76k,96k):ø9.52
Descripition
Gravity point
CHASSIS CODE: B8
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
6
5
Air discharge
Drain pipe connection Power supply connection
3 4
Gas pipe connection
2
Name Liquid pipe connection
3
1
Number
70 120
2
URNU76GB8A2 URNU96GB8A2
Ceiling Concealed Duct (High Static)
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
1
40 99 1
Indoor Units
4
3. Dimensions & Gravity point
4. Piping Diagrams
Heat Exchanger
:Cooling :Heating
EEV Filter
Th3
Th2 Sirocco Fan
Indoor Units
Th1
Filter
lndoor unit
Refrigerant pipe connection port diameter [Unit: mm(inch)]
MODEL
GAS
LIQUID
ARNU07GBHA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU09GBHA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU12GBHA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU15GBHA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU18GBHA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU24GBHA2
Ø15.88(5/8)
Ø9.52(3/8)
ARNU28GBGA2
Ø15.88(5/8)
Ø9.52(3/8)
ARNU36GBGA2
Ø15.88(5/8)
Ø9.52(3/8)
ARNU42GBGA2
Ø15.88(5/8)
Ø9.52(3/8)
ARNU48GBRA2
Ø15.88(5/8)
Ø9.52(3/8)
URNU76GB8A2
Ø19.05(3/4)
Ø9.52(3/8)
URNU96GB8A2
Ø22.2(7/8)
Ø9.52(3/8)
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
10 _ Ceiling Concealed Duct(High Static)
5. Wiring Diagrams BH Chassis
LOCATION POINT AC Power supply Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
Ceiling Concealed Duct(High Static) _ 11
Indoor Units
CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC
5. Wiring Diagrams
Indoor Units
BG Chassis
CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC
LOCATION POINT AC Power supply Fan motor output Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
FUNCTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
12 _ Ceiling Concealed Duct(High Static)
5. Wiring Diagrams BR Chassis
LOCATION POINT AC Power supply Fan motor output Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
FUNCTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
Ceiling Concealed Duct(High Static) _ 13
Indoor Units
CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC
5. Wiring Diagrams
Indoor Units
B8 Chassis
CONNECTOR NUMBER CN-POWER CN-MOTOR1, CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-DISPLAY CN-OPTION CN-ZONE
LOCATION POINT AC Power supply Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact RF Remocon Option PCB Zone controller
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
FUNCTION AC Power line input for indoor controller Motor output of BLDC AC Output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room thermistor Remote control line Dry contact line RF Remocon receiver Option PCB connector Zone controller line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
14 _ Ceiling Concealed Duct(High Static)
6. Capacity Tables 6.1 Cooling Capacity
Cooling capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
2.2
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3
1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5
2.8
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0
2.3 2.3 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9
3.6
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8
3.0 2.9 2.9 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4
Capacity Index
Outdoor air temp. (DB, °C)
32 24 TC SHC kW kW
SHC: Sensible Heat Capacity(kW)
Ceiling Concealed Duct(High Static) _ 15
Indoor Units
Notes: TC: Total Capacity(kW)
30 22 TC SHC kW kW
6. Capacity Tables Cooling capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
4.5
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8
3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.1 3.0
5.6
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0
6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8
4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8
7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0
4.4 4.3 4.3 4.2 4.1 4.1 4.1 4.0 3.9 3.9 3.8 3.8 3.7 3.6 3.6 3.5
7.1
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1
7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2
5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1
8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4
5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.3 5.2 5.1 5.0 4.9 4.8
9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6
5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5
Indoor Units
Capacity Index
Outdoor air temp. (DB, °C)
Notes: TC: Total Capacity(kW)
SHC: Sensible Heat Capacity(kW)
16 _ Ceiling Concealed Duct(High Static)
32 24 TC SHC kW kW
6. Capacity Tables Cooling capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
32 24 TC SHC kW kW
8.2
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7
6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0
8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2
6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.5 8.4
6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.1 6.0
9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.7 9.4 9.3 9.2 9.0 8.9 8.7 8.5
6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7
10.8 10.6 10.5 10.4 10.2 10.1 10.0 9.9 9.7 9.6 9.5 9.3 9.2 9.0 8.9 8.8
6.5 6.4 6.3 6.2 6.1 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.3 5.3
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3
6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9
7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3
9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0
10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3
7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.0 10.8 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.8 12.5
8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.9 7.7 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.2 9.0
12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.5 12.2 12.1 11.9 11.7 11.4 11.2 11.0 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.1 14.0 13.8 13.5 13.3 13.0 12.8
8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.7 9.4 9.3 9.2 9.0 8.8 8.7 8.5
13.9 13.7 13.6 13.4 13.2 13.0 12.9 12.8 12.6 12.4 12.2 12.0 11.8 11.7 11.5 11.3 16.2 15.9 15.8 15.6 15.3 15.1 15.0 14.8 14.6 14.4 14.2 14.0 13.7 13.5 13.4 13.1
8.4 8.2 8.2 8.0 7.9 7.8 7.8 7.7 7.5 7.5 7.3 7.2 7.1 7.0 6.9 6.8 9.7 9.6 9.5 9.3 9.2 9.1 9.0 8.9 8.8 8.6 8.5 8.4 8.3 8.1 8.0 7.9
10.6
12.3
Notes: TC: Total Capacity(kW)
SHC: Sensible Heat Capacity(kW)
Ceiling Concealed Duct(High Static) _ 17
Indoor Units
Capacity Index
Outdoor air temp. (DB, °C)
6. Capacity Tables Cooling capacity
Capacity Index
Indoor Units
14.1
22.4
28.0
Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
Notes: TC: Total Capacity(kW)
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9
11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5
13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2
8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1
9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8
10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3
14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0
10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6
SHC: Sensible Heat Capacity(kW)
18 _ Ceiling Concealed Duct(High Static)
15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 14.7 14.4 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8
10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.6 10.4 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2
30 22 TC SHC kW kW
32 24 TC SHC kW kW
16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.6 16.2 16.1 15.8 15.5 15.2 14.9 14.7 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5
18.5 18.3 18.1 17.8 17.6 17.3 17.2 17.0 16.7 16.5 16.3 16.0 15.8 15.5 15.3 15.1 29.4 29.0 28.7 28.3 27.9 27.5 27.4 27.0 26.6 26.2 25.8 25.4 25.0 24.6 24.3 23.9 36.8 36.3 35.9 35.4 34.9 34.4 34.2 33.7 33.2 32.8 32.3 31.8 31.3 30.8 30.4 29.9
11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.2 10.9 10.8 10.7 10.5 10.3 10.1 9.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1
11.3 11.1 11.0 10.8 10.7 10.5 10.5 10.3 10.2 10.0 9.9 9.7 9.6 9.4 9.3 9.2 16.7 16.5 16.3 16.1 15.9 15.6 15.5 15.3 15.1 14.9 14.7 14.4 14.2 14.0 13.8 13.6 20.9 20.6 20.4 20.1 19.8 19.5 19.4 19.1 18.9 18.6 18.3 18.1 17.8 17.5 17.3 17.0
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Heating capacity
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
2.2
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7
1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
2.8
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
3.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6
2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3
2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0
2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Notes: TC: Total Capacity(kW)
Ceiling Concealed Duct(High Static) _ 19
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
6. Capacity Tables Heating capacity
Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
4.5
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8
3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4
3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0
3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
5.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2
4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7
4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3
4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9
4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
7.1
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2
5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6
5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0
5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Notes: TC: Total Capacity(kW)
20 _ Ceiling Concealed Duct(High Static)
6. Capacity Tables Heating capacity
Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
8.2
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
6.2 6.3 6.7 7.1 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 10.2 10.4 10.6 10.6 10.6 10.6 10.6
6.2 6.3 6.7 7.0 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 9.8 9.8 9.8 9.8 9.8 9.8 9.8
6.2 6.3 6.7 6.3 6.6 7.0 7.1 7.3 7.5 7.8 8.1 8.5 9.0 9.2 9.2 9.2 9.2 9.2 9.2
6.1 6.3 6.7 7.0 7.4 7.8 7.9 8.1 8.2 8.5 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9
6.1 6.3 6.7 7.0 7.4 7.7 7.9 8.1 8.2 8.5 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6
6.1 6.3 6.6 7.0 7.4 7.7 7.8 7.9 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
10.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
8.0 8.2 8.7 9.2 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 13.2 13.4 13.7 13.7 13.7 13.7 13.7
8.0 8.2 8.7 9.0 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 12.7 12.7 12.7 12.7 12.7 12.7 12.7
8.0 8.2 8.7 8.2 8.6 9.0 9.2 9.4 9.7 10.1 10.4 11.0 11.6 11.9 11.9 11.9 11.9 11.9 11.9
7.9 8.2 8.7 9.0 9.5 10.1 10.2 10.5 10.6 11.0 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
7.9 8.1 8.7 9.0 9.5 10.0 10.2 10.5 10.6 11.0 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2
7.9 8.1 8.6 9.1 9.5 10.0 10.1 10.2 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4
12.3
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
9.2 9.5 10.1 10.6 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 15.3 15.5 15.9 15.9 15.9 15.9 15.9
9.2 9.5 10.1 10.5 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 14.8 14.8 14.8 14.8 14.8 14.8 14.8
9.2 9.5 10.1 9.5 10.0 10.4 10.7 10.9 11.3 11.7 12.1 12.8 13.5 13.8 13.8 13.8 13.8 13.8 13.8
9.1 9.5 10.1 10.5 11.0 11.7 11.9 12.1 12.2 12.8 13.3 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4
9.1 9.4 10.1 10.5 11.0 11.6 11.9 12.1 12.2 12.8 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
9.1 9.4 9.9 10.5 11.0 11.6 11.7 11.8 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1
Notes: TC: Total Capacity(kW)
Ceiling Concealed Duct(High Static) _ 21
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
6. Capacity Tables Heating capacity
Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
14.1
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
10.7 11.0 11.6 12.2 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.7 17.9 18.3 18.3 18.3 18.3 18.3
10.7 11.0 11.6 12.1 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.0 17.0 17.0 17.0 17.0 17.0 17.0
10.7 11.0 11.6 10.9 11.5 12.0 12.3 12.6 13.0 13.5 13.9 14.7 15.5 15.9 15.9 15.9 15.9 15.9 15.9
10.5 11.0 11.6 12.1 12.7 13.5 13.7 14.0 14.1 14.7 15.3 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4
10.5 10.8 11.6 12.1 12.7 13.4 13.7 14.0 14.1 14.7 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9
10.5 10.8 11.4 12.1 12.7 13.4 13.5 13.6 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9
22.4
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
16.9 17.4 18.4 19.4 20.4 21.4 21.7 22.2 22.9 23.9 25.0 26.5 28.0 28.4 29.0 29.0 29.0 29.0 29.0
16.9 17.4 18.4 19.2 20.4 21.4 21.7 22.2 22.9 23.9 25.0 26.5 27.0 27.0 27.0 27.0 27.0 27.0 27.0
16.9 17.4 18.4 17.3 18.2 19.1 19.5 19.9 20.6 21.5 22.1 23.4 24.6 25.2 25.2 25.2 25.2 25.2 25.2
16.6 17.4 18.4 19.2 20.2 21.4 21.7 22.2 22.4 23.3 24.3 24.4 24.4 24.4 24.4 24.4 24.4 24.4 24.4
16.6 17.1 18.4 19.2 20.2 21.2 21.7 22.2 22.4 23.3 23.7 23.7 23.7 23.7 23.7 23.7 23.7 23.7 23.7
16.6 17.1 18.1 19.2 20.2 21.2 21.4 21.6 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0
28.0
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
21.1 21.7 23.0 24.3 25.5 26.8 27.1 27.7 28.7 29.9 31.2 33.1 35.0 35.4 36.2 36.2 36.2 36.2 36.2
21.1 21.7 23.0 23.9 25.5 26.8 27.1 27.7 28.7 29.9 31.2 33.1 33.7 33.7 33.7 33.7 33.7 33.7 33.7
21.1 21.7 23.0 21.6 22.7 23.8 24.4 24.9 25.7 26.8 27.6 29.2 30.8 31.5 31.5 31.5 31.5 31.5 31.5
20.8 21.7 23.0 23.9 25.2 26.8 27.1 27.7 28.0 29.1 30.3 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5
20.8 21.4 23.0 23.9 25.2 26.5 27.1 27.7 28.0 29.1 29.6 29.6 29.6 29.6 29.6 29.6 29.6 29.6 29.6
20.8 21.4 22.7 24.0 25.2 26.5 26.8 27.0 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Notes: TC: Total Capacity(kW)
22 _ Ceiling Concealed Duct(High Static)
7. External Static Pressure (E.S.P) & Air Flow ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2 ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2 Setting Value 70 80 90 100 110 120 130 140 145 150
(Unit: CMM)
Static Pressure(mmAq(Pa)) 3(29)
4(39)
5(49)
6(59)
7(69)
8(78)
9(88)
10(98)
12(118)
4.1 7.6 10.7 13.4 15.9 18.6 19.8 22.3 23.2 24.3
8.1 11.2 13.2 16.2 18.8 21.1 22.2 23.1
6.3 9.6 12.6 15.2 18.0 20.3 21.4 22.3
4.9 7.5 10.3 12.8 15.3 17.7 19.1 21.1
4.0 7.7 11.1 14.2 17.1 18.4 19.8
5.5 9.1 12.4 15.5 16.9 18.3
6.7 10.4 13.7 15.3 16.8
5.3 8.8 12.6 13.8 15.2
5.7 9.7 11.8 13.0
Setting Value 70 80 90 100 110 120 130 140 143 150 160
(Unit: CMM)
Static Pressure(mmAq(Pa)) 5(49)
6(59)
7(69)
8(78)
9(88)
10(98)
12(118)
14(137)
16(157)
4.0 12.1 17.0 21.4 25.8 30.0 36.0 37.5 41.0 42.4
6.9 15.5 19.6 24.0 28.5 32.1 33.9 38.0 41.6
4.13 11.01 17.53 21.8 26.93 30.41 32.1 36.0 38.2
6.2 14.0 19.8 25.3 29.0 30.7 34.5 36.1
4.2 11.6 17.9 23.4 27.4 28.8 32.1 35
6.6 14.6 21.8 25.9 27.2 30.1 34.6
12.1 18.1 21.6 23.0 26.3 31.1
14.6 17.8 20.1 22.4 26.8
11.3 14.5 16.8 18.2 23.3
ARNU48GBRA2 Setting Value 91 96 101 106 111 116 121 126
(Unit: CMM) Static Pressure(mmAq(Pa)) 5(49)
6(59)
8(78)
46.5 49.9 52.1 51.4 53.6 62.3 67.0 68.2
43.7 46.1 50.2 51.2 53.7 61.0 64.8 67.5
38.2 43.0 47.9 50.4 52.9 60.3 64.1 66.2
10(98) 12(118) 14(137) 15(147) 16(157) 17(168) 18(176) 20(196) 31.3 33.5 39.5 44.4 49.9 55.7 58.2 65.1
23.2 31.1 37.4 43.1 48.3 50.8 52.2 64.3
14.0 18.4 27.3 33.3 40.6 44.8 50.8 57.4
9.0 13.7 25.2 32.1 40.2 42.6 50.3 54.4
3.7 9.0 17.8 28.9 32.8 40.1 45.7 51.2
2.6 8.9 21.0 31.5 37.6 44.6 50.4
6.1 17.9 27.2 32.5 38.8 46.0
8.3 17.5 27.6 32.2 43.5
Note: 1. The above table shows the correlation between the air rates and E.S.P.
Ceiling Concealed Duct(High Static) _ 23
Indoor Units
ARNU28GBGA2, ARNU36GBGA2, ARNU42GBGA2
7. External Static Pressure (E.S.P) & Air Flow URNU76GB8A2, URNU96GB8A2 (Unit: CMM)
Indoor Units
Setting Value
Static Pressure(mmAq(Pa)) 6(59)
9(88)
12(118)
15(147)
18(177)
20(196)
22(216)
23(226)
25(245)
60
40.5
-
-
-
-
-
-
-
-
65
52.7
-
-
-
-
-
-
-
-
70
63.7
47.1
-
-
-
-
-
-
-
75
71.1
56.9
44.7
-
-
-
-
-
-
80
76.3
69.7
55.2
-
-
-
-
-
-
85
83.3
78.6
67.4
55.9
-
-
-
-
-
91
89.7
87.1
78.9
67.6
54.2
-
-
-
-
95
93.4
91.4
86.1
77.0
66.4
50.6
30.0
-
-
100
93.4
91.4
88.3
84.9
75.9
69.5
60.8
43.1
-
105
93.2
91.3
88.3
84.9
81.1
77.4
69.2
67.9
51.3
Note: 1. The above table shows the correlation between the air rates and E.S.P.
24 _ Ceiling Concealed Duct(High Static)
7. External Static Pressure (E.S.P) & Air Flow ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2 ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2 Capacity
High (factory set) 7k Standard High (factory set) 9k Standard High (factory set) Standard High (factory set) 15k Standard High (factory set) 18k Standard High (factory set) Standard
Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low
120 117 115 110 107 105 125 120 117 110 107 105 130 125 120 115 110 105 135 130 120 123 120 115 140 135 130 130 125 110 150 145 140 145 135 128
8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59)
CMM 8.5 7.5 6 8.5 8 7.5 10 8.5 7.5 8.5 8 7.5 12 10 8.5 11 8.5 7.5 13.5 12 8.5 13.5 12 11 15.5 13.5 12.4 15.3 13.6 10.3 18.3 16.9 15.5 19 16.4 14.5
Lower Limit of External Static Pressure(mmAq(Pa))
Upper Limit of External Static Pressure(mmAq(Pa))
6(59)
12(118)
4(39)
8(78)
6(59)
12(118)
4(39)
8(78)
6(59)
12(118)
4(39)
8(78)
6(59)
12(118)
4(39)
8(78)
6(59)
12(118)
4(39)
8(78)
6(59)
12(118)
4(39)
8(78)
ARNU28GBGA2, ARNU36GBGA2, ARNU42GBGA2 Capacity
28k
High (factory set) Standard
36k
Standard Set value ESP(mmAq(Pa))
Mode
High (factory set) Standard High (factory set)
42k Standard
HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low
140 136 130 130 124 116 151 145 139 138 130 124 157 154 151 145 138 134
10(98) 8(78) 10(98) 8(78) 10(98) 8(78)
CMM 25.9 24.1 21.8 25.3 21.8 17.6 32.3 29 25.3 28.4 25.3 21.8 34.5 32.3 30.7 32 28.4 27.2
Lower Limit of External Static Pressure(mmAq(Pa))
Upper Limit of External Static Pressure(mmAq(Pa))
8(78)
16(157)
6(59)
10(98)
8(78)
14(137)
6(59)
10(98)
8(78)
12(118)
6(59)
10(98)
Ceiling Concealed Duct(High Static) _ 25
Indoor Units
12k
24k
Standard Set value ESP(mmAq(Pa))
Mode
7. External Static Pressure (E.S.P) & Air Flow ARNU48GBRA2 Capacity
Standard Set value ESP(mmAq(Pa))
Mode High (factory set)
48k Standard
HI Mid Low HI Mid Low
116 111 106 106 101 96
14(137) 10(98)
CMM 44.8 40.6 33.3 44.4 39.5 33.5
Lower Limit of External Static Pressure(mmAq(Pa))
Upper Limit of External Static Pressure(mmAq(Pa))
10(98)
20(196)
7(67)
14(137)
URNU76GB8A2, URNU96GB8A2
Indoor Units
Capacity
76k
High (factory set) Standard
96k
Standard Set value ESP(mmAq(Pa))
Mode
High (factory set) Standard
HI Mid Low HI Mid Low HI Mid Low HI Mid Low
102 98 98 86 83 83 105 102 102 94 89 89
22(216) 15(147) 22(216) 15(147)
26 _ Ceiling Concealed Duct(High Static)
CMM 60 50 50 64 50 50 72 64 64 76 64 64
Lower Limit of External Static Pressure(mmAq(Pa))
Upper Limit of External Static Pressure(mmAq(Pa))
12(118)
25(245)
12(118)
25(245)
12(118)
25(245)
12(118)
25(245)
8. Electric Characteristics Units
Power Supply
Input(W)
kW
FLA
1.32
15
0.118
1.06
150
150
BH
1.32
15
0.118
1.06
150
150
ARNU12GBHA2
BH
1.32
15
0.118
1.06
150
150
ARNU15GBHA2
BH
1.32
15
0.118
1.06
150
150
ARNU18GBHA2
BH
1.32
15
0.118
1.06
150
150
ARNU24GBHA2
BH
Max:264
1.32
15
0.118
1.06
150
150
ARNU28GBGA2
BG
Min:198
3.31
15
0.39
2.65
450
450
ARNU36GBGA2
BG
3.31
15
0.39
2.65
450
450
ARNU42GBGA2
BG
3.31
15
0.39
2.65
450
450
ARNU48GBRA2
BR
3.45
15
0.39
2.76
450
450
URNU76GB8A2
B8
6.47
15
0.75
5.18
800
800
URNU96GB8A2
B8
6.47
15
0.75
5.18
800
800
ARNU07GBHA2
BH
1.32
15
0.118
1.06
150
150
ARNU09GBHA2
BH
1.32
15
0.118
1.06
150
150
ARNU12GBHA2
BH
1.32
15
0.118
1.06
150
150
ARNU15GBHA2
BH
1.32
15
0.118
1.06
150
150
ARNU18GBHA2
BH
1.32
15
0.118
1.06
150
150
ARNU24GBHA2
BH
Max:242
1.32
15
0.118
1.06
150
150
ARNU28GBGA2
BG
Min:198
3.31
15
0.39
2.65
450
450
ARNU36GBGA2
BG
3.31
15
0.39
2.65
450
450
ARNU42GBGA2
BG
3.31
15
0.39
2.65
450
450
ARNU48GBRA2
BR
3.45
15
0.39
2.76
450
450
URNU76GB8A2
B8
6.47
15
0.75
5.18
800
800
URNU96GB8A2
B8
6.47
15
0.75
5.18
800
800
Type
ARNU07GBHA2
BH
ARNU09GBHA2
Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFM : Indoor Fan Motor
Hz
50
60
Volts
220-240
220
Cooling Heating
Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.
Ceiling Concealed Duct(High Static) _ 27
Indoor Units
MFA
Model
Voltage Range MCA
IFM
9. Sound Levels Overall
DISCHARGE
SUCTION
DUCT
DUCT 1.5m
2m
Indoor Units
Model
1m 1m
Sound Level dB(A)
Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
Sound Level dB(A)
Model
ARNU07GBHA2
H 34
M 33
L 32
ARNU28GBGA2
H 44
M 42
L 40
ARNU09GBHA2
35
34
33
ARNU36GBGA2
46
44
42
ARNU12GBHA2
37
35
34
ARNU42GBGA2
48
46
45
ARNU15GBHA2
39
38
37
ARNU48GBRA2
45
43
41
ARNU18GBHA2
42.5
41
37
URNU76GB8A2
50
48
48
ARNU24GBHA2
45
43
41
URNU96GB8A2
52
50
50
Sound Pressure Level ARNU09GBHA2
ARNU12GBHA2 80
70
70
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
10
NC-25 Approximate Hearing Threshold 63
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20
NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
NC-65
60
10
NC-25 Approximate Hearing Threshold 63
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20
NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
28 _ Ceiling Concealed Duct(High Static)
Octave Band Sound Pressure Level (dB re 20μPa )
80
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
ARNU07GBHA2 80
10
NC-25 Approximate Hearing Threshold 63
NC-20
NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
9. Sound Levels ARNU15GBHA2
ARNU18GBHA2
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20 Approximate Hearing Threshold 63
70
250
500
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20
125
80
NC-15 1000 2000 4000 8000
10
NC-25 Approximate Hearing Threshold 63
NC-50
NC-40
NC-30 20
10
NC-60 NC-55 NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25 Approximate Hearing Threshold 63
250
500
NC-15 1000 2000 4000 8000
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20 Approximate Hearing Threshold 63
Octave Band Sound Pressure Level (dB re 20μPa )
NC-60
125
250
500
Octave Band Center Frequency (Hz)
500
NC-15 1000 2000 4000 8000
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
10
NC-25 Approximate Hearing Threshold 63
125
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
10
NC-25 Approximate Hearing Threshold 63
125
250
500
Octave Band Center Frequency (Hz)
500
NC-15 1000 2000 4000 8000
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20
NC-20 NC-15 1000 2000 4000 8000
250
URNU96GB8A2
80
NC-65
60
NC-20
Octave Band Center Frequency (Hz)
URNU76GB8A2
70
NC-20 NC-15 1000 2000 4000 8000
250
NC-65
60
NC-20
125
80
NC-65
60
NC-15 1000 2000 4000 8000
70
Octave Band Center Frequency (Hz)
ARNU48GBRA2
500
20
NC-25 Approximate Hearing Threshold 63
80
250
ARNU42GBGA2
NC-65
Octave Band Center Frequency (Hz)
70
125
80
60
10
NC-20
Octave Band Center Frequency (Hz)
70
NC-20
125
NC-25 Approximate Hearing Threshold 63
Octave Band Sound Pressure Level (dB re 20μPa )
NC-65
50
NC-35
30
Octave Band Sound Pressure Level (dB re 20μPa )
70
60
NC-45
40
ARNU36GBGA2 Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
500
NC-55
50
80
20
Octave Band Sound Pressure Level (dB re 20μPa )
NC-60
Indoor Units
ARNU28GBGA2
10
250
NC-15 1000 2000 4000 8000
NC-65
60
Octave Band Center Frequency (Hz)
80
10
70
NC-20
125
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (dB re 20μPa )
NC-65
60
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
70
10
ARNU24GBHA2
80
80
10
Approximate Hearing Threshold 63
NC-20
125
250
500
NC-15 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Ceiling Concealed Duct(High Static) _ 29
10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Air outlet vents
Air filters
Air intake vents TEMP
Indoor Units
Wired LCD Remote Control
Remote Controller
Required Parts
Required Tools
• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose
• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer
10.1 Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unitʼs weight. • The place shall be able to inspect the unit as the figure. • The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit. • The servicing inspection hole in the ceiling should be as large as the product • The selection of the servicing hole should be approved by the customer
30 _ Ceiling Concealed Duct(High Static)
[Inspection Hole Standard] Number of Inspection hole
Distance between False ceiling & Actual ceiling
1
More than 100cm
2
20cm to 100cm
Hole size should be more than the size of IDU.
Less than 20cm
Remarks Sufficient space in the ceiling for servicing. Insufficient space. Difficult for servicing Minimum height for motor replacement.
10. Installation 10.2 Ceiling dimension and hanging bolt location
BH/BG/BR Chassis
C E
■ Installation of Unit Install the unit above the ceiling correctly.
A B
CASE 1
D
POSITION OF SUSPENSION BOLT
F
(G)
I
• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. • Refer to the Dimensions. (Unit:mm) Dimension
B
C
D
E
F
(G)
H
I
932
882
355
47
450
30
87
750
158
BG
1232
1182
355
47
450
30
87
830
186
BR
1282 1230
477
56
590
30
H
BH
Drainage hole
Indoor Units
A Chassis
B8 Chassis
120 1006 294
(Unit:mm) Dimension
A
B
C
D
E
F
G
H
I
J
K
L
Chassis
B8
1680 1565 1160 330 460 580 700 1400 1635 390 445 15
• Install the unit leaning to a drainage hole side as a figure for easy water drainage.
CASE 2 POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.
M10 Nut
X4
M10 washer
X4
M10 washer
X4
M10 Nut
X8
Ceiling Concealed Duct(High Static) _ 31
10. Installation NOTE: • Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated. 5. Avoid places near high frequency generators. • Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling.
• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
Indoor Units
Old building
New building
1 Set anchor 2 Plate washer 3 Spring washer
CAUTION
4 Nut 5 Suspension bolts
Tighten the nut and bolt to prevent unit falling.
10.3 Connecting Cables between Indoor Unit and Outdoor Unit Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively [Multi V III Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU B
IDU B
SODU A
IDU A
INT B
INT A
4
INDOOR POWER INPUT
[Except Multi VIII Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU
4
B
A
INTERNET DRY1 DRY2 GND 12V
IDU -
-
B
A
-
-
-
-
Outdoor Unit
INDOOR POWER INPUT
WARNING Make sure that the screws of the terminal are not loose.
Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.
32 _ Ceiling Concealed Duct(High Static)
10. Installation THERMAL INSULATION
All thermal insulation must comply with local requirement.
INDOOR UNIT BH/BG/BR Chassis
Union for liquid pipe
Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply)
Refrigerant pipe and thermal insulator(Local supply) Hose clamp for thermal insulator (Local supply)
B8
Thermal insulator for refrigerant pipe (Local supply) Union for gas pipe
Overlap with thermal insulator for piping. Hose clamp for thermal insulator(Local supply) Make sure that there is no clearance here.
Union for gas pipe
Hose crip for thermal insulator (Local supply) Refrigerant pipe and therma insulator(Local supply)
Union for liquid pipe
10.4 Checking the Drainage 1) Checking the Drainage
BH/BG/BR Chassis
1. Remove the Air Filter.
B8
2. Check the drainage. • Spray one or two glasses of water on the evaporator. • Ensure that water flows through drain hose of indoor unit without any leakage.
Ceiling Concealed Duct(High Static) _ 33
Indoor Units
Thermal insulator for refrigerant pipe (Local supply)
10. Installation 10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.
Upward routing not allowed
Pipe clamp Indoor unit
Maintenance drain port
Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings • Be sure to install heat insulation on the drain piping.
1/50~1/100 MAX 700mm
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Feed water
Drain Pump
Flexible drain hose (accessory)
• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. Main drain pipe • Feed water to the flexible drain hose and check the piping for leakage. Drain • Be sure to check the drain pump for normal operation and port Glue the joint noise when electrical wiring is complete. Drain hose connection Use the clip (accessory) • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Drain pan
CAUTION The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.
Max 300mm
Hanger distance 1~15m
Hanger Bracket 1/50~1/100 slope
Metal clamp Flexible drain hose
Max 700mm
Indoor Units
Drain test
Insulation
Flexible drain hose Flexible drain hose Flexible drain hose
34 _ Ceiling Concealed Duct(High Static)
10. Installation 10.6 Ground drain piping a) It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible.
Face the vent pipe opening facing downward to keep foreign matter from penetrating the system Face piping downward
b) The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.
10.7 Use of an auxiliary drain hose(flexible) a) To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be used. auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain. Auxiliary drain hose
Thermal insulation (drain pipe area)
Metal clamp
Metal clamp Thermal insulation(bend area) Drain pan
â?ˆ Important points - The drain pipe should be at least equal in size to that of the indoor unit. - The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe. - The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected some water should be added to the drain pan and the drain pump to check and see if it is functioning correctly. - All connections should be secure. (Special care is needed with PVC pipe) - Insulate auxiliary drain hose with thermal insulation band.
Ceiling Concealed Duct(High Static) _ 35
Indoor Units
Vent pipe
10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
Indoor Units
- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
TEMP
yes
Remote Controller
no
TEMP
Controller Remote
TEMP
Remote Controller
5feet (1.5meters)
no
no
Fig.1 Typical locations for remote controller
36 _ Ceiling Concealed Duct(High Static)
11. Accessories Standard Accessories Name
Drain hose
Clamp metal
Quantity
1 EA
1 EA
Washer for hanging backet 8 EA
Clamp (Tie Wrap)
Insulation for fitting
4 EA
1 SET
(Other)
• Owner's manual • Installation manual Shape
for gas pipe
for liquid pipe
Indoor Units
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
Ceiling Concealed Duct(High Static) _ 37
Indoor unit Ceiling Concealed Duct(Low Static) 1. List of functions 2. Specifications 3. Dimensions & Gravity point 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure (E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of functions Category
Air flow
Air purifying
Installation
Convenience
Individual control
Special function kit
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2, ARNU18GB2G2, ARNU24GB2G2 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O Accessory Accessory Accessory Accessory X Accessory Accessory -
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Ceiling Concealed Duct(Low Static) _ 1
Indoor Units
Reliability
Function
2. Specifications Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Dimensions(WxDxH) Body
mm inch
Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A)
Indoor Units
Coil
Power Supply Refrigerant Control Power cable Transmission cable
Ø, V, Hz mm2 mm2
Ceiling Concealed Duct (Low Static) ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 2 x 11 x 21 2 x 11 x 21 2 x 11 x 21 0.16 0.16 0.16 Sirocco Fan Sirocco Fan Sirocco Fan 28 28 28 0.15 0.15 0.15 8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 10.5 / 9.5 / 8.5 300 / 265 / 229 335 / 300 / 265 371 / 335 / 300 2(20) 2(20) 2(20) 8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 10.5 / 9.5 / 8.5 300 / 265 / 229 335 / 300 / 265 371 / 335 / 300 0(0) 0(0) 0(0) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuser �Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 25.4(1) 25.4(1) 25.4(1) 21(46.3) 21(46.3) 21(46.3) 33 / 32 / 29 34 / 33 / 32 35 / 34 / 33 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
2 _ Ceiling Concealed Duct(Low Static)
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specifications Type Model
Ceiling Concealed Duct (Low Static) ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2 4.5 5.6 7.1 Cooling Capacity 3,900 4,800 6,100 15,400 19,100 24,200 5.0 6.3 8.0 Heating Capacity 4,300 5,400 6,900 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 1,100 x 575 x 190 1,100 x 575 x 190 Dimensions(WxDxH) Body inch 32.3 x 21.7 x 7.5 43.3 x 21.7 x 7.5 43.3 x 21.7 x 7.5 Rows x Columns x FPI 2 x 11 x 21 3 x 10 x 18 3 x 10 x 18 Coil Face Area m3 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 28 76 76 Running Current A 0.15 0.38 0.38 Air Flow Rate(H / M / L) CMM 11.5 / 10.5 / 9.5 16.0 / 14.0 / 12.0 19.0 / 17.0 / 15.0 (High Mode-factory set) cfm 406 / 371 / 335 565 / 494 / 424 671 / 600 / 530 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H / M / L) CMM 11.5 / 10.5 / 9.5 16.0 / 14.0 / 12.0 19.0 / 17.0 / 15.0 (Standard Mode) cfm 406 / 371 / 335 565 / 494 / 424 671 / 600 / 530 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 26(57.3) 26(57.3) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) 38 / 37 / 36 40 / 37 / 34 43 / 40 / 37 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Unit kW kcal/h Btu/h kW kcal/h Btu/h
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling Concealed Duct(Low Static) _ 3
Indoor Units
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
575
18
154
383
18
B1 : 448 B2 : 573
D
B A
C
6
5 13
161 14 B1 : 186 B2 : 175 B1 : 73 B2 : 81
4 _ Ceiling Concealed Duct(Low Static) 4
3
216 24
65 60
190
Gas pipe connection Drain pipe connection Power supply connection Air discharge Air suction
2 3 4 5 6
1072
794
D
Descripition
(unit : mm)
1131
856
C
Unit size(7k,9k,12k,18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k,9k,12k,18k):ø12.7 Unit size(24k):ø15.88
1008
728
B
(unit: mm)
Gravity point
CHASSIS CODE: B1/B2
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Liquid pipe connection
Name
1100
820
1
Number
ARNU18GB2G2 ARNU24GB2G2
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
2
1
A
ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2
Ceiling Concealed Duct (Low Static)
ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2
Indoor Units
3. Dimensions & Gravity point
277
190
4. Piping Diagrams
Heat Exchanger
EEV Filter
Th3
:Cooling :Heating
Th2 Sirocco Fan
Th1
Filter
lndoor unit
[Unit: mm(inch)]
MODEL
GAS
LIQUID
ARNU07GB1G2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU09GB1G2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU12GB1G2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU15GB1G2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU18GB2G2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU24GB2G2
Ø15.88(5/8)
Ø9.52(3/8)
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
Ceiling Concealed Duct(Low Static) _ 5
Indoor Units
Refrigerant pipe connection port diameter
5. Wiring Diagrams
Indoor Units
B1/B2 Chassis
CONNECTOR NUMBER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-D/PUMP CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-ZONE CN-DISPLAY CN-CC
SPEC. Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Drain pump output Option PWB. Communication Drain pump output AC power supply Zone Controller RF Remote controller Dry contact
DESCRIPTION Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV control output AC output for drain pump Communication between main and option Communication between indoor and outdoor AC output for drain pump AC power line input for indoor controller Zone control line RF remote control line Dry contact line
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
6 _ Ceiling Concealed Duct(Low Static)
6. Capacity Tables 6.1 Cooling Capacity
Capacity Index
2.2
3.6
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
Notes: TC: Total Capacity(kW)
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6
30 22 TC SHC kW kW 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 1.9 1.9 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.6 2.5 2.5
32 24 TC SHC kW kW 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8
1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.3
SHC: Sensible Heat Capacity(kW)
Ceiling Concealed Duct(Low Static) _ 7
Indoor Units
2.8
Outdoor air temp. (DB, °C)
Cooling capacity
6. Capacity Tables Cooling capacity
Capacity Index
Indoor Units
4.5
5.6
7.1
Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
Notes: TC: Total Capacity(kW)
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
SHC: Sensible Heat Capacity(kW)
8 _ Ceiling Concealed Duct(Low Static)
4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.9 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.0
30 22 TC SHC kW kW 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4
3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 5.2 5.1 5.0 4.9 4.8 4.7
32 24 TC SHC kW kW 5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6
3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5 3.5 3.4 5.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5 4.4 4.4
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Heating capacity Indoor air temp. (DB, °C)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
2.2
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7
1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
2.8
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
3.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6
2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3
2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0
2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Notes: TC: Total Capacity(kW)
Ceiling Concealed Duct(Low Static) _ 9
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor Units
4.5
5.6
7.1
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2
3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7
3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3
3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9
3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2
5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6
5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0
5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Notes: TC: Total Capacity(kW)
10 _ Ceiling Concealed Duct(Low Static)
7. External Static Pressure (E.S.P) & Air Flow ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2 Setting Value
Static Pressure(mmAq(Pa)) 0(0) 6.02 6.95 7.69 8.46 9.5 10.35 10.81 11.57 12.58 13.31 14.2 14.82
1(10) 2.25 3.32 5.16 6.93 7.37 8.72 9.66 10.31 11.22 12.27 13.24 13.92
2(20)
3(29)
4(39)
0.61 0.73 1.19 2.42 3.4 5.33 6.75 8.56 9.75 10.89 12.15 12.64
0.54 0.65 0.77 0.87 1.35 3.15 4.73 7.46 8.64 10.49 11.16
0.48 0.56 0.63 0.72 0.88 0.98 1.03 2.31 5.01 7.7 9.48
ARNU18GB2G2, ARNU24GB2G2 Setting Value 65 70 75 80 85 90 95 100 105 110 115 120 125 130
(Unit: CMM) Static Pressure(mmAq(Pa))
0(0)
1(10)
2(20)
3(29)
4(39)
10.07 11.39 12.01 13.21 14.24 15.04 16.02 17.11 17.99 19.04 19.77 20.94 21.97 22.83
6.9 8.49 9.79 11.03 12.36 13.34 14.63 15.56 16.53 17.71 18.62 19.92 20.56 21.98
0.82 2.2 4.2 5.92 9.41 10.8 12.5 13.66 15.17 16.22 17.1 18.56 19.25 20.75
0.92 2.1 5.29 7.59 11.53 12.35 14.23 15.23 16.98 17.68 19.32
1.01 1.34 5.35 7.67 10.45 13.25 14.66 16.06 17.73
Note : 1. The above table shows the correlation between the air rates and E.S.P.
Ceiling Concealed Duct(Low Static) _ 11
Indoor Units
60 65 70 75 80 85 90 95 100 105 110 115
(Unit: CMM)
7. External Static Pressure (E.S.P) & Air Flow ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2 Capacity
7k
High (factory set) Standard
9k
High (factory set) Standard High (factory set)
12k
Indoor Units
Standard Set value ESP(mmAq(Pa))
Mode
Standard High (factory set) 15k Standard
HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low
94 92 86 75 69 62 99 94 92 82 75 69 103 99 94 89 80 75 107 105 99 95 89 82
2(20) 0(0) 2(20) 0(0) 2(20) 0(0) 2(20) 0(0)
CMM 8.5 7.5 6.5 8.5 7.5 6.5 9.5 8.5 7.5 9.5 8.5 7.5 10.5 9.5 8.5 10.5 9.5 8.5 11.5 10.5 9.5 11.5 10.5 9.5
Lower Limit of External Static Pressure(mmAq(Pa))
Upper Limit of External Static Pressure(mmAq(Pa))
-
4(39)
-
4(39)
-
4(39)
-
4(39)
-
4(39)
-
4(39)
-
4(39)
-
4(39)
ARNU18GB2G2, ARNU24GB2G2 Capacity
18k
High (factory set) Standard
24k
Standard Set value ESP(mmAq(Pa))
Mode
High (factory set) Standard
HI Mid Low HI Mid Low HI Mid Low HI Mid Low
110 101 93 95 84 75 125 115 105 110 100 90
2(20) 0(0) 2(20) 0(0)
12 _ Ceiling Concealed Duct(Low Static)
CMM 16 14 12 16 14 12 19 17 15 19 17 15
Lower Limit of External Static Pressure(mmAq(Pa))
Upper Limit of External Static Pressure(mmAq(Pa))
-
4(39)
-
4(39)
-
4(39)
-
4(39)
8. Electric Characteristics Units Model
Type
Power Supply Hz
Volts
Voltage Range MCA
IFM
Input(W)
MFA
kW
FLA
Cooling Heating
B1
0.22
15
0.028
0.17
30
30
ARNU09GB1G2
B1
0.22
15
0.028
0.17
30
30
ARNU12GB1G2
B1
Max:264
0.22
15
0.028
0.17
30
30
ARNU15GB1G2
B1
Min:198
0.22
15
0.028
0.17
30
30
ARNU18GB2G2
B2
0.55
15
0.076
0.44
80
80
ARNU24GB2G2
B2
0.55
15
0.076
0.44
80
80
ARNU07GB1G2
B1
0.22
15
0.028
0.17
30
30
ARNU09GB1G2
B1
0.22
15
0.028
0.17
30
30
ARNU12GB1G2
B1
Max:242
0.22
15
0.028
0.17
30
30
ARNU15GB1G2
B1
Min:198
0.22
15
0.028
0.17
30
30
ARNU18GB2G2
B2
0.55
15
0.076
0.44
80
80
ARNU24GB2G2
B2
0.55
15
0.076
0.44
80
80
50
60
220-240
220
Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFM : Indoor Fan Motor Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.
Ceiling Concealed Duct(Low Static) _ 13
Indoor Units
ARNU07GB1G2
9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
1.5m
Ceiling 2.0m Microphone
Sound Levels dB(A) H 33 34 35 38 40 43
ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2
M 32 33 34 37 37 40
L 29 32 33 36 34 37
Sound Pressure Level ARNU09GB1G2
ARNU12GB1G2
80
80
70
70
70
NC-65
60 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
20
63
NC-55
50 NC-50 NC-45
40 NC-40
30
NC-30
NC-15
250
500
10
1000 2000 4000 8000
Octave Band Center Frequency (Hz)
ARNU15GB1G2
250
500
NC-55 NC-50 NC-45 NC-40 NC-35
30
NC-30
20
NC-25
Approximate Hearing Threshold 63
Octave Band Sound Pressure Level (dB re 20μPa )
NC-60
40
NC-15
250
500
1000 2000 4000 8000
Octave Band Center Frequency (Hz)
NC-40 NC-35
30
NC-30
NC-25 NC-20 NC-15
10 63
1000 2000 4000 8000
125
250
500
1000 2000 4000 8000
Octave Band Center Frequency (Hz)
ARNU24GB2G2 80
70
NC-65
60 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
NC-25
20 Approximate Hearing Threshold
NC-20
125
NC-45
40
ARNU18GB2G2
NC-65
50
NC-50
Approximate Hearing Threshold
80
70
10
125
NC-55
50
Octave Band Center Frequency (Hz)
80
60
NC-60
NC-20 NC-15
63
NC-65
60
20
NC-25
Approximate Hearing Threshold
NC-20
125
NC-35
70
NC-65
60 NC-60
NC-15
125
250
500
1000 2000 4000 8000
Octave Band Center Frequency (Hz)
14 _ Ceiling Concealed Duct(Low Static)
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
NC-25
20 Approximate Hearing Threshold
NC-20
10 63
Octave Band Sound Pressure Level (dB re 20μPa )
10
NC-60
20
NC-25
Approximate Hearing Threshold
NC-65
60
Octave Band Sound Pressure Level (dB re 20μPa )
80
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
ARNU07GB1G2
Octave Band Sound Pressure Level (dB re 20μPa )
Indoor Units
Model Name
NC-20 NC-15
10 63
125
250
500
1000 2000 4000 8000
Octave Band Center Frequency (Hz)
10. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Required Tools
• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose
• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer
Indoor Units
Required Parts
10.1 Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unitʼs weight. • The place shall be able to inspect the unit as given in the figure. • The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit. • The servicing inspection hole in the ceiling should be as large as the product. • The selection of the servicing hole should be approved by the customer.
[Inspection Hole Standard] Number of Inspection hole
Distance between False ceiling & Actual ceiling
1
More than 100cm
2
20cm to 100cm
Hole size should be more than the size of IDU.
Less than 20cm
Remarks Sufficient space in the ceiling for servicing. Insufficient space. Difficult for servicing Minimum height for motor replacement.
Inspection hole (600X600) Control box
Top view (unit: mm)
600
600
Front view
H
Ceiling Concealed Duct(Low Static) _ 15
10. Installation 10.2 Ceiling dimension and hanging bolt location ■ Installation of Unit Install the unit above the ceiling correctly.
CASE 1 M10 Nut
X4
M10 washer
X4
M10 washer
X4
M10 Nut
X8
POSITION OF SUSPENSION BOLT
Indoor Units
• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
• Install the unit leaning to a drainage hole side as a figure for easy water drainage.
CASE 2 POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.
NOTE: • Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated. 5. Avoid places near high frequency generators.
16 _ Ceiling Concealed Duct(Low Static)
10. Installation 10.3 Connecting Cables Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively [Multi V III Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU B
SODU A
IDU B
IDU A
INT B
INT A
IDU
INTERNET DRY1 DRY2 GND 12V
4
INDOOR POWER INPUT
[Except Multi VIII Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU
4
B
A
-
-
B
A
-
-
-
-
Outdoor Unit
Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.
10.4 Checking the Drainage • Spray one or two glasses of water on the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.
10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to pro- Pipe clamp vide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the Indoor unit drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings
Upward routing not allowed
Maintenance drain port
• Be sure to install heat insulation on the drain piping. 1/50~1/100
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
MAX 700mm
Ceiling Concealed Duct(Low Static) _ 17
Indoor Units
INDOOR POWER INPUT
10. Installation Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Flexible drain hose (accessory) Main drain pipe
Drain Pump
Drain port
Glue the joint
Drain hose connection Use the clip (accessory)
• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Indoor Units
Drain pan Max 300mm
CAUTION
Hanger distance 1~15m
Hanger Bracket 1/50~1/100 slope
Metal clamp
The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.
Flexible drain hose
Max 700mm
Feed water
Insulation
10.6 Ground drain piping a) It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible.
Flexible drain hose
Flexible drain hose
Face the vent pipe mouth downward to keep foreign matter from penetrating the system Face piping downward Vent pipe
b) The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.
10.7 Use of an auxiliary drain hose(flexible) a) To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be used. auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain.
18 _ Ceiling Concealed Duct(Low Static)
10. Installation Auxiliary drain hose
Thermal insulation (drain pipe area)
Metal clamp
Metal clamp Thermal insulation(bend area) Drain pan
â?ˆ Important points
WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
TEMP
yes
Remote Controller
no
TEMP
Controller Remote
TEMP
Remote Controller
5feet (1.5meters)
no
no
Fig.1 Typical locations for remote controller
Ceiling Concealed Duct(Low Static) _ 19
Indoor Units
- The drain pipe should be at least equal in size to that of the indoor unit. - The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe. - The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected some water should be added to the drain pan and the drain pump to check and see if it is functioning correctly. - All connections should be secure. (Special care is needed with PVC pipe) - Insulate auxiliary drain hose with thermal insulation band.
11. Accessories Standard Accessories Name
Drain hose
Clamp metal
Quantity
1 EA
2 EA
Washer for hanging backet 8 EA
Clamp (Tie Wrap) 4 EA
Insulation for fitting
(Other)
1 SET
• Owner's manual • Installation manual Shape
for gas pipe
Indoor Units
for liquid pipe
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
20 _ Ceiling Concealed Duct(Low Static)
Indoor unit Ceiling Concealed Duct_Built in 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure (E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of Functions Category
Air flow
Indoor Units
Air purifying
Installation
Reliability
Convenience
Individual control
Special function kit
Function
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O Accessory Accessory Accessory Accessory X Accessory Accessory -
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
1 _ Ceiling Concealed Duct_Built in
2. Specification Ceiling Concealed Duct (Built-in) PBSGB30/PBSC30 PBSGB30/PBSC30 PBSGB30/PBSC30 Unit ARNU07GB3G2 ARNU09GB3G2 ARNU12GB3G2 kW 2.2 2.8 3.6 Cooling Capacity kcal/h 1,900 2,400 3,100 Btu/h 7,500 9,600 12,300 kW 2.5 3.2 4.0 Heating Capacity kcal/h 2,200 2,800 3,400 Btu/h 8,500 10,900 13,600 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 Dimensions(WxDxH) Body inch 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 Rows x Columns x FPI 2 x 11 x 21 2 x 11 x 21 2 x 11 x 21 Coil Face Area m3 0.16 0.16 0.16 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 30 30 30 Running Current A 0.15 0.15 0.15 Air Flow Rate(H / M / L) CMM 8.0 / 6.5 / 5.5 9.0 / 7.0 / 6.0 10.0 / 8.0 / 6.5 (High Mode-factor set) cfm 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H / M / L) CMM 8.0 / 6.5 / 5.5 9.0 / 7.0 / 6.0 10.0 / 8.0 / 6.5 (Standard Mode) cfm 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Liquid Side mm(inch) �Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Drain Pipe(Internal Dia.) mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 21(46.3) 21(46.3) Noise Level(Sound Press, 1m, H / M / L) dB(A) 33 / 32 / 29 34 / 33 / 32 35 / 34 / 33 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Type Accessory Model
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling Concealed Duct_Built in _ 2
Indoor Units
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV: Electronic Expansion Valve 5. To be added for more available Models 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
2. Specification Ceiling Concealed Duct (Built-in) PBSGB30/PBSC30 PBSGB40/PBSC40 PBSGB40/PBSC40 Unit ARNU15GB3G2 ARNU18GB4G2 ARNU24GB4G2 kW 4.5 5.6 7.1 Cooling Capacity kcal/h 3,900 4,800 6,100 Btu/h 15,400 19,100 24,200 kW 5.0 6.3 8.0 Heating Capacity kcal/h 4,300 5,400 6,900 Btu/h 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 1,100 x 575 x 190 1,100 x 575 x 190 Dimensions(WxDxH) Body inch 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 Rows x Columns x FPI 2 x 11 x 21 3 x 10 x 18 3 x 10 x 18 Coil Face Area m3 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 30 80 80 Running Current A 0.15 0.38 0.38 Air Flow Rate(H / M / L) CMM 11.0 / 10.0 / 8.0 14.0 / 12.0 / 10.0 17.0 / 15.0 / 10.0 (High Mode-factor set) cfm 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H / M / L) CMM 11.0 / 10.0 / 8.0 14.0 / 12.0 / 10.0 17.0 / 15.0 / 10.0 (Standard Mode) cfm 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 26(57.3) 26(57.3) Noise Level(Sound Press, 1m, H / M / L) dB(A) 41 / 40 / 37 43 / 40 / 37 46 / 43 / 37 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
Indoor Units
Type Accessory Model
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV: Electronic Expansion Valve 5. To be added for more available Models 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
3 _ Ceiling Concealed Duct_Built in
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling Concealed Duct_Built in _ 4
E
B
F
575
A
With Suction Grille & Suction Canvas
250
388
PBSC30 PBSC40
PBSGB30 PBSGB40
E 821 1100
B 910 1188
Btu/h A 7,9,12,15k 820 18,24k 1100 D 56 56 F G 274 42~250 274 42~250
C 359 359
With Suction Grille
G
C
6
1
4
5
Drain pipe connection Power supply connection Air suction Air discharge
3 4 5 6
(unit : mm) Unit size(7k,9k,12k,15k,18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k,9k,12k,15k,18k):ø12.7 Unit size(24k):ø15.88
Descripition
CHASSIS CODE: B3/B4
Gas pipe connection
2
Name
2
Liquid pipe connection
60
190
1
Number
3
65
ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
277
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
500(Max)
D
190
216 24
With Suction Grille & Suction Canvas
Indoor Units
With Suction Grille
388 190
B3/B4
618
Ceiling Concealed Duct (Built in)
3. Dimensions
4. Piping Diagrams
Heat Exchanger
EEV Filter
Th2
Th3 Sirocco Fan
Th1
Indoor Units
:Cooling :Heating
Filter
lndoor unit
Refrigerant pipe connection port diameter [Unit: mm(inch)]
MODEL
GAS
LIQUID
ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
Ø12.7(1/2)
Ø6.35(1/4)
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
Ø12.7(1/2)
Ø6.35(1/4)
ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
Ø12.7(1/2)
Ø6.35(1/4)
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
Ø12.7(1/2)
Ø6.35(1/4)
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
Ø12.7(1/2)
Ø6.35(1/4)
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
Ø15.88(5/8)
Ø9.52(3/8)
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
5 _ Ceiling Concealed Duct_Built in
5. Wiring Diagrams B3/B4 Chassis
CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-D/PUMP CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-ZONE CN-DISPLAY CN-CC
SPEC.
DESCRIPTION
Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Drain pump output Option PWB. Communication Drain pump output AC power supply Zone Controller RF Remote controller Dry contact
Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV control output AC output for drain pump Communication between main and option Communication between indoor and outdoor AC output for drain pump AC power line input for indoor controller Zone control line RF remote control line Dry contact line
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
Ceiling Concealed Duct_Built in _ 6
Indoor Units
CONNECTOR NUMBER
6. Capacity Tables 6.1 Cooling Capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5
2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3
1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 1.9 1.9 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.6 2.5 2.5
3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8
2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.3
Outdoor air temp. (DB, °C)
2.2 Indoor Units
Capacity Index
2.8
3.6
Cooling capacity
Notes: TC: Total Capacity(kW)
7 _ Ceiling Concealed Duct_Built in
SHC: Sensible Heat Capacity(kW)
30 22 TC SHC kW kW
32 24 TC SHC kW kW
6. Capacity Tables Cooling capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
Capacity Index
Outdoor air temp. (DB, °C)
4.5
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8
3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2
4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.9 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.0
6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 5.2 5.1 5.0 4.9 4.8 4.7
7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6
4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5 3.5 3.4 5.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5 4.4 4.4
7.1
Notes: TC: Total Capacity(kW)
SHC: Sensible Heat Capacity(kW)
Ceiling Concealed Duct_Built in _ 8
Indoor Units
5.6
32 24 TC SHC kW kW
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Heating capacity Indoor air temp. (DB, °C)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
2.2
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7
1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
2.8
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
3.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6
2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3
2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0
2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Notes: TC: Total Capacity(kW)
9 _ Ceiling Concealed Duct_Built in
6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
4.5
7.1
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2
3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7
3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3
3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9
3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2
5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6
5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0
5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Notes: TC: Total Capacity(kW)
Ceiling Concealed Duct_Built in _ 10
Indoor Units
5.6
Indoor air temp. (DB, °C)
7. External Static Pressure (E.S.P) & Air Flow ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
Indoor Units
Setting Value
(Unit: CMM)
Static Pressure(mmAq(Pa)) 0(0)
1(10)
2(20)
3(29)
4(39)
60
6.29
3.03
0.93
-
-
65
6.61
4.84
1.52
-
-
70
7.69
5.64
2.18
0.79
-
75
8.19
6.28
2.81
0.85
-
80
8.91
7.43
4.96
1.58
-
85
9.51
8.14
5.91
2.75
0.95
90
10.21
8.76
6.79
3.41
1.36
95
10.83
9.62
8.11
5.48
2.61
100
11.31
10.55
9.02
6.12
3.31
105
11.84
11.19
9.99
8.28
5.32
110
12.68
11.88
10.38
9.16
6.92
115
13.19
12.22
11.55
10.21
8.23
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) Setting Value
(Unit: CMM)
Static Pressure(mmAq(Pa)) 0(0)
1(10)
2(20)
3(29)
4(39)
75
10.32
7.68
3.55
-
-
80
11.06
8.77
4.71
1.38
-
85
11.84
10.02
6.95
2.16
-
90
12.73
10.74
8.26
4.73
1.25
95
13.47
12.13
9.93
6.74
2.73
100
14.16
13.25
10.51
8.41
3.65
105
15.29
14.11
12.31
9.83
6.21
110
16.09
14.77
13.49
10.39
8.32
115
16.91
15.88
14.48
12.77
9.92
120
17.81
16.88
15.15
13.98
10.85
125
18.55
17.84
16.12
15.13
12.97
130
19.01
18.55
17.33
16.28
14.59
Note : 1. The above table shows the correlation between the air rates and E.S.P. 2. E.S.P. is given after subtracting coil losses motor step factory installed 3. E.S.P. can be higher than the maximum given in the table, but the unit faces the problem of freezing the coil.
11 _ Ceiling Concealed Duct_Built in
7. External Static Pressure (E.S.P) & Air Flow ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) Capacity
7k
High (factory set) Standard
9k
Standard Set value ESP(mmAq(Pa))
Mode
High (factory set)
High (factory set) 12k Standard High (factory set) 15k Standard
94 88 83 74 62 56 99 89 85 82 66 58 105 94 88 90 74 62 110 105 94 96 90 74
2(20) 0(0) 2(20) 0(0) 2(20) 0(0) 2(20) 0(0)
8 6.5 5.5 8 6.5 5.5 9 7 6 9 7 6 10 8 6.5 10 8 6.5 11 10 8 11 10 8
Lower Limit of External Static Pressure(mmAq(Pa))
Upper Limit of External Static Pressure(mmAq(Pa))
-
4(39)
-
4(39)
-
4(39)
-
4(39)
-
4(39)
-
4(39)
-
4(39)
-
4(39))
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) Capacity
18k
High (factory set) Standard
24k
Standard Set value ESP(mmAq(Pa))
Mode
High (factory set) Standard
HI Mid Low HI Mid Low HI Mid Low HI Mid Low
115 103 93 100 86 74 128 118 93 116 104 74
2(20) 0(0) 2(20) 0(0)
CMM 14 12 10 14 12 10 17 15 10 17 15 10
Lower Limit of External Static Pressure(mmAq(Pa))
Upper Limit of External Static Pressure(mmAq(Pa))
-
4(39)
-
4(39)
-
4(39)
-
4(39)
Ceiling Concealed Duct_Built in _ 12
Indoor Units
Standard
HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low
CMM
8. Electric Characteristics
Indoor Units
Units
Power Supply
Input(W)
MFA
kW
FLA
0.22
15
0.028
0.17
30
30
0.22
15
0.028
0.17
30
30
Max:264
0.22
15
0.028
0.17
30
30
Min:198
0.22
15
0.028
0.17
30
30
B4
0.55
15
0.076
0.44
80
80
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
B4
0.55
15
0.076
0.44
80
80
ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
B3
0.22
15
0.028
0.17
30
30
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
B3
0.22
15
0.028
0.17
30
30
ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
B3
Max:242
0.22
15
0.028
0.17
30
30
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
B3
Min:198
0.22
15
0.028
0.17
30
30
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
B4
0.55
15
0.076
0.44
80
80
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
B4
0.55
15
0.076
0.44
80
80
Model
Type
ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
B3
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
B3
ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
B3
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
B3
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
Hz
50
60
Volts Voltage Range MCA
IFM
220-240
220
Cooling Heating
Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFA : Indoor Fan Motor Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.
13 _ Ceiling Concealed Duct_Built in
9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operation condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
1.5m
Ceiling 2.0m Microphone
Sound Levels dB(A) Model Name
M 32 33 34 40 40 43
L 29 32 33 37 37 37
Sound Pressure Level ARNU09GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y) 80
70
70
70
NC-65 60 NC-60 NC-55 NC-50 NC-45
40
NC-40 NC-35
30
NC-30
NC-50
NC-40
125
250
500
1000
2000
4000
NC-35
30
NC-30 NC-25 Approximate Hearing Threshold
NC-15
63
NC-45
40
NC-20
10
NC-55
50
20
NC-25 Approximate Hearing Threshold
NC-60
NC-15 63
8000
70
70
NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35
30
NC-30 NC-25
20
10
Approximate Hearing Threshold 63
Octave Band Sound Pressure Level (dB re 20µPa )
80
40
250
500
NC-15 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
250
500
1000
2000
4000
8000
NC-45 NC-40 NC-35
30
NC-30 NC-25
20 Approximate Hearing Threshold
NC-20 NC-15
10 63
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
ARNU24GB4G2+ PBSGB40(Acc'y), PBSC40(Acc'y) 80
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
NC-65 60 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
NC-25
20
NC-25
20
NC-20
125
NC-50
40
ARNU18GB4G2+ PBSGB40(Acc'y), PBSC40(Acc'y)
80
50
125
NC-55
50
Octave Band Center Frequency (Hz)
ARNU15GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y)
60
NC-60
NC-20
10
Octave Band Center Frequency (Hz)
NC-65 60
Octave Band Sound Pressure Level (dB re 20µPa )
50
NC-65 60
Octave Band Sound Pressure Level (dB re 20µPa )
80
20
Octave Band Sound Pressure Level (dB re 20µPa )
ARNU12GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y)
80
Octave Band Sound Pressure Level (dB re 20µPa )
Octave Band Sound Pressure Level (dB re 20µPa )
ARNU07GB3G2+ PBSGB30(Acc'y), PBSC30(Acc'y)
10
Approximate Hearing Threshold 63
Approximate Hearing Threshold
NC-20
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
NC-15 8000
NC-20 NC-15
10 63
125
250
500
1000 2000
4000
8000
Octave Band Center Frequency (Hz)
Ceiling Concealed Duct_Built in _ 14
Indoor Units
H 33 34 35 41 43 46
ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Suction Grille TEMP
Remote Controller
Indoor Units
Suction Grille + Suction Canvas
TEMP
Remote Controller
Required Parts
Required Tools
• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose (Inner Dia ....................................25mm)
• Level • Screw driver • Electric drill • Hole core drill (ø70mm) • Flaring Tools set • Torque Wrenches • Hexagonal Wrench (4mm, 5mm) • Gas-leak detector • Ownerʼs Manual • Thermometer
15 _ Ceiling Concealed Duct_Built in
10. Installation 10.1 Selection of the best location Install the air conditioner in the location that satisfies the following conditions.
Top view (unit:mm) Airflow
• The place shall easily bear a load exceeding four times the indoor unitʼs weight.
Inspection hole (600 x 600)
• The place shall be able to inspect the unit as the figure.
Control box
• The place where the unit shall be leveled. • The place shall easily connect with the outdoor unit. 600
• The place where the unit is not affected by an electrical noise.
600
• There should not be any heat source or steam near the unit
Indoor Units
Confirm the positional relationship between the unit and suspension bolts.
270 or more
• The place where air circulation in the room will be good .
(Unit : mm) Chassis
A
B
B3
600
900
B4
600
1100
520 or more
• Installation the ceiling opening to clean the filter or service under the product.
• Refer to Suction grille and Suction canvas installation manual for detail installation of Built-in duct type
A(Min)
B3/B4 Series : Built-in Duct type
B(Min)
Ceiling Service Space
A
B
Ceiling Concealed Duct_Built in _ 16
10. Installation 10.2 Ceiling dimension and hanging bolt location Installation of Unit B A J
Install the unit above the ceiling correctly.
CASE 1
C D
POSITION OF SUSPENSION BOLT
E
• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. G
• Apply a filter Accessory at air return hole. (Unit:mm)
Indoor Units
I F
Dimension
A
D
E
F
850 900 383 575 1130 1180 383 575
93 93
190 190
Chassis
B3 B4
B
C
G
H
I
J
H 21 795 163 820 21 1065 163 1100
Drainage hole
Drain Pump use
M10 Nut
X4
M10 washer
X4
M10 washer
X4
M10 Nut
X8
CASE 2 • Install the unit leaning to a drainage hole side as a figure for easy water drainage.
POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.
17 _ Ceiling Concealed Duct_Built in
10. Installation • Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling.
• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
Old building
New building
1 Set anchor 2 Plate washer 3 Spring washer 4 Nut
Indoor Units
CAUTION
5 Suspension bolts
Tighten the nut and bolt to prevent unit falling.
10.3 Connecting Cables Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively [Multi V III Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU B
SODU A
IDU B
IDU A
INT B
INT A
IDU
INTERNET DRY1 DRY2 GND 12V
4
INDOOR POWER INPUT
[Except Multi VIII Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU
4
B
A
-
-
B
A
-
-
-
-
Outdoor Unit
INDOOR POWER INPUT
WARNING Make sure that the screws of the terminal are not from loose.
Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.
Ceiling Concealed Duct_Built in _ 18
10. Installation 10.4 Part name and functions Air outlet
Air outlet
Suction Grille Suction Grille Suction Canvas
Indoor Units
• Buit-in duct type with Suction Grille
• Buit-in duct type with Suction Grille and Suction Canvas
■ B3/B4 Series : Built-in Duct type Control Box service
19 _ Ceiling Concealed Duct_Built in
10. Installation INSULATION, OTHERS THERMAL INSULATION
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT Union for gas pipe
Refrigerant pipe and thermal insulator(Local supply)
Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply)
Hose clip for thermal insulator (Local supply) Overlap with thermal insulator for piping. Hose clip for thermal insulator(Local supply) Make sure that there is no clearance here.
Thermal insulator for refrigerant pipe (Local supply) Union for liquid pipe
Felt
Cabinet
Rubber
No clearance
TEST AND CHECK
■ After all workings are finished, check the working and operation. • Air distribution ............... Is the air circulation good? • Drain ............................. Is the drainage smoothly and no sweating? • Gas leakage ................. Is the piping connection correctly? • Wiring ........................... Is the wiring connection correctly? • Lock-bolt ....................... Is the lock-bolt of compressor loosened? • Insulation Is the unit fully insulated? • Ground Is the unit safely grounded?
10.5 Checking the Drainage 1. Remove the Air Filter.
2. Check the drainage. • Spray one or two glasses of water upon the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.
Ceiling Concealed Duct_Built in _ 20
Indoor Units
Insulation
10. Installation CAUTION 1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 19mm.
Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation.
Ceiling
Indoor Units
Drainage hole
Drain Pump use
10.6 Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.
Pipe clamp Indoor unit
Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings
Upward routing not allowed
Maintenance drain port
• Be sure to install heat insulation on the drain piping. Heat insulation material: Polyethylene foam with thickness more than 8 mm.
1/50~1/100 MAX 700mm
Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:
Feed water
Flexible drain hose Main drain pipe
Drain Pump
Drain port
Glue the joint
Drain hose connection Use the clip
Drain pan
21 _ Ceiling Concealed Duct_Built in
• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
10. Installation Max 300mm
Hanger distance 1~15m
Metal clamp Flexible drain hose
Hanger Bracket 1/50~1/100 slope Max 700mm
CAUTION : The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.
Insulation
CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit.
4) Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal function of an overload protection device. • Proper starting power is not given to the compressor.
HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)
Ceiling Concealed Duct_Built in _ 22
Indoor Units
3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out Flexible drain hose of the wires.)
10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
Indoor Units
- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
TEMP
yes
Remote Controller
no
TEMP
Remote Controller
5feet (1.5meters)
TEMP
Controller Remote
no
no
Fig.1 Typical locations for remote controller
23 _ Ceiling Concealed Duct_Built in
11. Accessories Standard Accessories Name
Drain hose
Clamp metal
Quantity
1 EA
2 EA
Washer for hanging backet 8 EA
Clamp (Tie Wrap)
Insulation for fitting
4 EA
1 SET
(Other)
• Owner's manual • Installation manual Shape
for gas pipe
for liquid pipe
Indoor Units
CAUTION • Use only those accessories (Standard or optional) which have designated specilications.
Ceiling Concealed Duct_Built in _ 24
Indoor unit Wall Mounted 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of functions Category
Air flow
Air purifying
Reliability
Convenience
Individual control
Special function kit
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU07GSE*2, ARNU09GSE*2, ARNU12GSE*2 ARNU15GSE*2, ARNU18GS5*2, ARNU24GS5*2 1 SE Manual / S5 Auto Auto SE Manual / S5 Auto X 3/4/3 O O O X Option O O O O O(Heat recovery) O O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory Accessory Accessory -
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Wall Mounted _ 1
Indoor Units
Installation
Function
2. Specifications * Model Name A:Basic L:Plasma Type Model Cooling Capacity
Heating Capacity Dimensions(WxDxH) Body
Indoor Units
Coil
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch m3 W A CMM cfm
Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color
Ø, V, Hz mm2 mm2
Wall Mounted ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 895 x 165 x 282 895 x 165 x 282 895 x 165 x 282 35.2 x 6.5 x 11.1 35.2 x 6.5 x 11.1 35.2 x 6.5 x 11.1 2 x 15 x 18 2 x 15 x 18 2 x 15 x 18 0.21 0.21 0.21 Cross Flow Fan Cross Flow Fan Cross Flow Fan 20 20 20 0.2 0.2 0.2 5.6 / 5.0 / 4.6 7.0 / 6.5 / 6.0 9.5 / 9.0 / 8.5 198.0 / 177.0 / 162.5 247.0 / 230.0 / 212.0 336.0 / 318.0 / 300.0 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Resin Net(washable) Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 16(5/8) 16(5/8) 16(5/8) 9(19.8) 9(19.8) 9(19.8) 37 / 33 / 23 39 / 35 / 25 41 / 36 / 27 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog Morning fog
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
2 _ Wall Mounted
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specifications * Model Name A:Basic L:Plasma Type Model Cooling Capacity
Heating Capacity Dimensions(WxDxH) Body Coil
m3 W A CMM cfm
Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color
Ø, V, Hz mm2 mm2
Wall Mounted ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2 4.5 5.6 7.1 3,900 4,800 6,100 15,400 19,100 24,200 5.0 6.3 8.0 4,300 5,400 6,900 17,100 21,500 27,300 895 x 165 x 282 1,090 x 178 x 300 1,090 x 178 x 300 35.2 x 6.5 x 11.1 42.9 x 7 x 11.8 42.9 x 7 x 11.8 2 x 15 x 18 2 x 15 x 20 2 x 15 x 20 0.21 0.26 0.26 Cross Flow Fan Cross Flow Fan Cross Flow Fan 20 20 20 0.2 0.2 0.2 10.5 / 9.0 / 8.5 12.0 / 10.5 / 9.0 14.0 / 13.0 / 10.0 371.0 / 318.0 / 300.0 424.0 / 371.0 / 318.0 494.0 / 459.0 / 353.0 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Resin Net(washable) Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) 16(5/8) 16(5/8) 16(5/8) 9(19.8) 12(26.5) 12(26.5) 42 / 36 / 27 44 / 40 / 36 46 / 41 / 38 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog Morning fog
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Wall Mounted _ 3
Indoor Units
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch
PIPING/WIRING DIRECTION
4 _ Wall Mounted PIPE AND DRAIN DIMENSION
567
PIPING DIRECTION
PIPING/WIRING DIRECTION
Front panel Air discharge Air suction Liquid pipe Gas pipe Drain pipe Right side piping/wiring connection Left side piping/wiring connection
1 2 3 4 5 6 7 8
Descripition
(unit : mm)
165
Ø6.35 Flare connection Ø12.7 Flare connection External dia. Ø17
282
D
(unit : mm)
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
Higher than eye-level
More than 100 mm
※ Required space(unit:mm)
CHASSIS CODE: SE
More than 100 mm
Lower than 2.3m More than 200 mm
Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
Name
895
H
ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2
Wall Mounted
Number
W
Model ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2
Indoor Units
3. Dimensions
265
Wall Mounted _ 5
PIPING/WIRING DIRECTION
PIPE AND DRAIN DIMENSION
804
PIPING DIRECTION
PIPING/WIRING DIRECTION
Front panel Air discharge Air suction Liquid pipe Gas pipe Drain pipe Right side piping/wiring connection Left side piping/wiring connection
1 2 3 4 5 6 7 8
Descripition
(unit : mm)
178
Ø6.35 Flare connection Ø12.7 Flare connection External dia. Ø17
300
D
(unit : mm)
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
Higher than eye-level
More than 100 mm
※ Required space(unit:mm)
CHASSIS CODE: S5
More than 100 mm
Lower than 2.3m More than 200 mm
Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
Name
1090
ARNU18GS5*2 ARNU24GS5*2
H
ARNU18GS5*2 ARNU24GS5*2
Number
W
Model
Indoor Units
281
Wall Mounted
3. Dimensions
4. Piping Diagrams
Heat Exchanger
EEV Filter
Th3
Th2
C.F.F
Th1
Indoor Units
:Cooling :Heating
Filter
lndoor unit
Refrigerant pipe connection port diameter [Unit: mm(inch)]
MODEL
GAS
LIQUID
ARNU07GSE*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU09GSE*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU12GSE*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU15GSE*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU18GS5*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU24GS5*2
Ø15.88(5/8)
Ø9.52(3/8)
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
6 _ Wall Mounted
5. Wiring Diagrams SE Chassis
Indoor Units
S5 Chassis
CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-COM CN-DISP1 CN-DISP2 CN-EEV CN-U/D, CN-L/R CN-TH1 CN-REMO CN-CC CN-HVB
LOCATION POINT AC Power supply Fan motor output Communication Display Display EEV output Step motor Room/pipe sensor Remote controller Dry contact Air clean
FUNCTION AC Power line input for indoor controller Motor output of BLDC Connection between indoor and outdoor Display of indoor status Display of indoor status EEV control output Step motor output Room and pipe thermistor Remote control line Dry contact line Air clean control
Wall Mounted _ 7
6. Capacity Tables 6.1 Cooling Capacity
Cooling Capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
2.2
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5 1.5 1.5 1.5
2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3
1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.9 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.5 2.5 2.4
3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8
2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2
Indoor Units
Capacity Index
Outdoor air temp. (DB, °C)
2.8
3.6
Notes: TC: Total Capacity(kW)
8 _ Wall Mounted
SHC: Sensible Heat Capacity(kW)
32 24 TC SHC kW kW
6. Capacity Tables Cooling Capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8
3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.9 2.8
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1
6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 5.0
6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.8 3.8 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4 5.3 5.2 5.1 5.1 5.0 4.9 4.8
7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6
4.3 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 5.4 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9 4.8 4.7 4.6 4.6 4.5 4.4
Capacity Index
Outdoor air temp. (DB, °C)
4.5
7.1
Notes: TC: Total Capacity(kW)
32 24 TC SHC kW kW
SHC: Sensible Heat Capacity(kW)
Wall Mounted _ 9
Indoor Units
5.6
30 22 TC SHC kW kW
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Heating Capacity Indoor air temp. (DB, °C)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
2.2
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7
1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
2.8
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
3.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6
2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3
2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0
2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Notes: TC: Total Capacity(kW)
10 _ Wall Mounted
6. Capacity Tables Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
4.5
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8
3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4
3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0
3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
5.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2
4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7
4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3
4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9
4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
7.1
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2
5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6
5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0
5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Notes: TC: Total Capacity(kW)
Wall Mounted _ 11
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
7. Air Velocity and Temperature Distribution(Reference Data) ARNU07GSE*2 Cooling
Heating Discharge angle:50°
Discharge angle:45° Air velocity [m/s]
Air velocity [m/s] 2.7m
2.7m
2m
2m 2.0 1.5
0.5
1.5
1.0
1m
1m
1.0 0.5
5m
4m
3m
2m
0m 0m
1m
Temperature [°C]
5m
4m
3m
2m
0m 0m
1m
Temperature [°C]
Indoor Units
2.7m
2.7m
2m
2m 21
24
18 20
33 30
1m
1m
27 22
24
5m
4m
3m
2m
0m 0m
1m
5m
4m
3m
2m
0m 0m
1m
ARNU09GSE*2 Cooling
Heating Discharge angle:50°
Discharge angle:45°
Air velocity [m/s]
Air velocity [m/s] 2.7m
2.7m
2m
2m 2.0 1.5
1.5
1m
1m
1.0 0.5
1.0 0.5
5m
4m
3m
2m
0m 0m
1m
Temperature [°C]
5m
4m
3m
2m
0m 0m
1m
Temperature [°C] 2.7m
2.7m
2m
2m 33
18 21 20
24
30
1m
1m
27 22
24
5m
4m
3m
12 _ Wall Mounted
2m
1m
0m 0m
5m
4m
3m
2m
1m
0m 0m
7. Air Velocity and Temperature Distribution(Reference Data) ARNU12GSE*2 Cooling
Heating Discharge angle:50°
Discharge angle:45°
Air velocity [m/s]
Air velocity [m/s] 2.7m
2.7m
2m
2m
2.0
2.0
1m
1m 1.5 0.5
5m
4m
3m
2m
1.0
1.0
0.5
0m 0m
1m
5m
4m
1.5
3m
2m
0m 0m
1m
Temperature [°C]
Temperature [°C]
2.7m
2.7m
Indoor Units
2m
2m 33
18
21 30
1m
20
1m
27 24
5m
4m
24
22
3m
2m
0m 0m
1m
5m
4m
3m
2m
0m 0m
1m
ARNU18GS5*2 Cooling
Heating Discharge angle:50°
Discharge angle:45°
Air velocity [m/s]
Air velocity [m/s]
2.5 0.5
8m
7m
6m
5m
4m
3m
2.7m
2.7m
2m
2m
1m
1.5
1.0
2m
1.0
0.5
0m 0m
1m
1m
2.0
8m
7m
6m
5m
4m
3m
2m
1.5
0m 0m
1m
Temperature [°C]
Temperature [°C]
2.7m
2.7m
2m
2m 33
18 20
7m
6m
5m
4m
30
21
3m
2m
1m
0m 0m
8m
7m
6m
5m
4m
3m
1m
27
24
22
24
8m
1m
2m
1m
0m 0m
Wall Mounted _ 13
8. Electric Characteristics
Indoor Units
Units
Power Supply
Input(W)
MFA
kW
FLA
0.29
15
0.02
0.23
40
40
0.29
15
0.02
0.23
40
40
Max:264
0.29
15
0.02
0.23
40
40
Min:198
0.29
15
0.02
0.23
40
40
S5
0.29
15
0.02
0.23
40
40
ARNU24GS5*2
S5
0.29
15
0.02
0.23
40
40
ARNU07GSE*2
SE
0.29
15
0.02
0.23
40
40
ARNU09GSE*2
SE
0.29
15
0.02
0.23
40
40
ARNU12GSE*2
SE
Max:242
0.29
15
0.02
0.23
40
40
ARNU15GSE*2
SE
Min:198
0.29
15
0.02
0.23
40
40
ARNU18GS5*2
S5
0.29
15
0.02
0.23
40
40
ARNU24GS5*2
S5
0.29
15
0.02
0.23
40
40
Model
Type
ARNU07GSE*2
SE
ARNU09GSE*2
SE
ARNU12GSE*2
SE
ARNU15GSE*2
SE
ARNU18GS5*2
Hz
50
60
Volts
220 - 240
220
Voltage Range MCA
IFM
Cooling Heating
Symbols: MCA :Min, Circuit Amps(A) MFA:Max. Fuse Amps(see note 5) kW:Fan Motor Rated Output(kW) FLA:Full Load Amps(A) IFM:Indoor Fan Motor Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.
14 _ Wall Mounted
9. Sound Levels Overall Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
1m 1m Microphone Sound Levels dB(A)
Model ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2
M 33 35 36 36 40 41
L 23 25 27 27 36 38
Indoor Units
H 37 39 41 42 44 46
Sound Pressure Level
70
70
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
10
Approximate Hearing Threshold 63
NC-60
250
500
1000
2000
4000
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20
125
NC-65
60
NC-15 8000
10
NC-25 Approximate Hearing Threshold 63
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (dB re 20μPa )
80
20
125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)
NC-15 8000
NC-60
NC-50
NC-40
NC-30 20
10
ARNU18GS5*2
NC-55 NC-50 NC-45 NC-40 NC-35 NC-30
10
NC-25 Approximate Hearing Threshold 63
NC-65 60 NC-60 50
NC-50
125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)
NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20 Approximate Hearing Threshold
NC-20 NC-15 8000
NC-55
10 63
125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (dB re 20μPa )
NC-60
Octave Band Sound Pressure Level (dB re 20μPa )
70
NC-65
NC-20
125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)
NC-15 8000
ARNU24GS5*2
70
20
NC-25 Approximate Hearing Threshold 63
70
30
NC-35
30
80
40
NC-45
40
80
50
NC-55
50
80
60
NC-65
60
NC-20
ARNU15GSE*2
Octave Band Sound Pressure Level (dB re 20μPa )
ARNU12GSE*2
ARNU09GSE*2 80
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
ARNU07GSE*2 80
NC-65 60 NC-60
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20 Approximate Hearing Threshold
NC-20 NC-15 8000
NC-55
50
NC-20 NC-15
10 63
125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)
8000
Wall Mounted _ 15
10. Installation • Please read the instruction sheetss completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Installation Parts Provided
1. Type "A" screw
Indoor Units
2. Installation Plate
Required Parts
Required Tools
❏ Installation plate ❏ Four type "A" screws ❏ Connecting cable
❏ Level gauge ❏ Screw driver ❏ Electric drill ❏ Hole core drill
❏ Pipes: Gas side Liquid side ❏ Insulation materials ❏ Additional drain pipe
❏ Flaring tool set ❏ Specified torque wrenches ❏ Spanner......................................................Half union ❏ A glass of water ❏ Screw driver ❏ Thermometer
16 _ Wall Mounted
10. Installation 10.1 Selection of the best location
Front
• There
should not be any heat source or steam near the unit.
• There should not be any obstacles to prevent air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
Left Rear left Down right Right
Rear right
More than 100mm
More than 200mm
More than 2300mm
The mounting wall should be strong and solid enough to protect it from vibration.
S5 chassis
1.Mount the installation plate on the wall with four Type "A" screws. (If mounting the unit on the concrete wall, consider using anchor bolts.) • Always mount the Installation plate horizontally by aligning the marking-off line by means of thread and a level.
Installation Plate Chassis Hook
Type “A”
SE chassis Installation Plate
Chassis Hook
Type “A”
Wall Mounted _ 17
Indoor Units
More than 100mm
10. Installation Preparing work for installation ■ Preparing the indoor unit's piping and drain hose for installation through the wall. ■ Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis. ■ Replace the plastic tubing holder in the original position.
3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
Loop
Indoor Units
Tubing holder To remove the holder, press the bottom of chassis near the holder upward and pull the tab out of its hole.
Connecting cable Drain hose
Gas side piping Liquid side piping
2 Pull 1 Press
CAUTION While installing, make sure that the remaining parts must be removed clearly so as not to damage the piping and drain hose, especially power cord and connecting cable.
For left rear piping 1. Route the indoor tubing and the drain hose in the direction of rear left.
NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended. 4. Indoor unit installation ■ Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.
Connecting cable
Drain hose
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound). Drain hose
2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole. ■ Do not connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.
5. Connecting the pipings to the indoor unit and drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.
Indoor unit tubing
18 _ Wall Mounted
Flare nut
Pipings
10. Installation ■ Tighten the flare nut with a wrench. Spanner (fixed) Flare nut Connection pipe
Torque wrench
■ Wrap the area which accommodates the rear piping housing section with vinyl tape. Indoor unit pipe Wrap with vinyl tape
Connection pipe Vinyl tape (wide)
Connecting cable
Indoor unit tubing
Pipe
■ When extending the drain hose at the indoor unit, install the drain pipe.
Drain pipe
Vinyl tape(narrow)
■ Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section. Wrap with vinyl tape
Pipe
Adhesive
Vinyl tape(wide) Drain hose
6. Wrap the insulation material around the connecting portion. ■ Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Plastic bands
For right rear piping 1. Route the indoor tubing and the drain hose to the required piping hole position.
Insulation material
2. Insert the piping, drain hose and the connecting cable into the piping hole. Connecting cable
Drain pipe
Wall Mounted _ 19
Indoor Units
Indoor unit drain hose Vinyl tape(narrow)
10. Installation 3. Insert the connecting cable into the indoor unit. ■ Don't connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.
■ When extending the drain hose at the indoor unit, install the drain pipe.
Drain hose
4. Tape the drain hose and the connecting cable. • Connecting cable
Indoor unit drain hose Vinyl tape(narrow) Adhesive
Indoor Units
7. Wrap the insulation material around the connecting portion. ■ Overlap the connecting pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap. 5. Indoor unit installation ■ Hang the indoor unit from the hooks at the top of the installation plate. ■ Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall. Indoor unit Spacer
6. Connecting the pipings to the indoor unit and the drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.
Flare nut
Pipings
■ Tighten the flare nut with a wrench.
Spanner (fixed)
Indoor unit tubing
20 _ Wall Mounted
■ Wrap the area which accommodates the rear piping housing section with vinyl tape.
Vinyl tape (wide)
80mm (2-3/16 inch)
Torque wrench
Insulation material
Connection pipe
Installation plate
Indoor unit tubing
Plastic bands
Flare nut Connection pipe
Indoor unit piping Wrap with vinyl tape Pipe
Connecting cable
Vinyl tape (narrow)
10. Installation ■ Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
10. Indoor unit installation ■ Remove the spacer. ■ Ensure that the hooks are properly seated on the installation plate by moving it left and right.
Pipe Drain hose
Vinyl tape (narrow)
Connecting
Wrap with vinyl tape(wide)
8. Reroute the pipings and the drain hose across the back of the chassis.
Drain hose
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Indoor Units
Piping for passage through piping hole
9. Set the pipings and the drain hose to the back of the chassis with the tubing holder. ■ Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.
Tubing holder 1 Hook
2 Push
Wall Mounted _ 21
10. Installation 10.2 Connection of Pipings
Indoor Units
1. To remove the front panel from the indoor unit, remove the front panel from the indoor unit cabinet. ■ Set the air direction louvers up-and-down to the position(horizontally) by hand. ■ Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off. (2.1/7, 2.6/9, 3.5/12 kW/Btu models: 2EA, 3.5/18 kW/Btu models: 3EA)
2. To check the drainage. ■ Pour a glass of water on the evaporator. ■ Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
Pull the right and the left side.
Screw
10.3 Connect the cable to the indoor unit 1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Remote control co cord
Connecting cable
22 _ Wall Mounted
10. Installation [Multi V III Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU B
SODU A
IDU B
IDU A
INT B
INT A
4
INDOOR POWER INPUT
[Except Multi VIII Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU
4
B
A
INTERNET DRY1 DRY2 GND 12V
IDU -
-
B
A
-
-
-
-
Outdoor Unit
INDOOR POWER INPUT
Indoor Units
2. Attach the Grille onto the cabinet. • Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis. • Press the Grille toward the chassis until it is back in place.
CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Confirm the specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between the cable length and thickness.) 7) In a wet or moist area, always install an earth leakage circuit breaker. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.
Wall Mounted _ 23
10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
Indoor Units
- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
TEMP
yes
Remote Controller
no
TEMP
Controller Remote
TEMP
Remote Controller
5feet (1.5meters)
no
no
Fig.1 Typical locations for remote controller
24 _ Wall Mounted
11. Accessories Standard Accessories Name
Installation panel
Type "A" screw
Quantity
1 set
SE: 6 EA S5: 8 EA
(Other) • Owner's manual • Installation manual
SE
Shape S5
Indoor Units
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
Wall Mounted _ 25
Indoor unit ART COOL Mirror 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of functions Category
Air flow
Air purifying
Reliability
Convenience
Individual control
Special function kit
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU07GSE*2, ARNU09GSE*2, ARNU12GSE*2 ARNU15GSE*2, ARNU18GS8*2, ARNU24GS8*2 1 Auto Auto Auto X 3/4/3 O O O X Option O O O O O(Heat recovery) O O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory Accessory -
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
ART COOL Mirror _ 1
Indoor Units
Installation
Function
2. Specifications
Indoor Units
Type Model
ART COOL Mirror ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 2.2 2.8 3.6 Cooling Capacity 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 Heating Capacity 2,200 2,800 3,400 8,500 10,900 13,600 915 x 169 x 282 915 x 169 x 282 915 x 169 x 282 Dimensions(WxDxH) Body 36.0 x 6.5 x 11.1 36.0 x 6.5 x 11.1 36.0 x 6.5 x 11.1 Rows x Columns x FPI 2 x 15 x 18 2 x 15 x 18 2 x 15 x 18 Coil Face Area m3 0.21 0.21 0.21 Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Motor Output x Number W 20 20 20 Running Current A 0.2 0.2 0.2 Fan Air Flow Rate(H / M / L) CMM 7.0 / 6.0 / 4.0 8.0 / 7.0 / 5.0 10.0 / 8.0 / 6.0 cfm 247 / 212 / 141 282 / 247 / 177 353 / 283 / 212 Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Resin Net(washable) Resin Net(washable) Resin Net(washable) Safety Device Fuse Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Drain Pipe(Internal Dia.) mm(inch) 16(5/8) 16(5/8) 16(5/8) Net Weight kg(lbs) 11.2(24.7) 11.2(24.7) 11.2(24.7) Noise Level(Sound Press, 1m, H / M / L) dB(A) 37 / 33 / 23 39 / 35 / 25 41 / 36 / 27 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Front Panel('*' Position) R:Mirror V:Silver B:Blue Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
2 _ ART COOL Mirror
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specifications Type Model
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
ARNU24GS8*2 7.1 6,100 24,200 8.0 6,900 27,300 1,107 x 200 x 299 43.9 x 7.9 x 11.8 2 x 15 x 20 0.26 Cross Flow Fan 20 0.2 17.9 / 14.4 / 12.0 632 / 508 / 424 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø9.52(3/8) Ø15.88(5/8) 16(5/8) 15(33.1) 43 / 37 / 32 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
ART COOL Mirror _ 3
Indoor Units
ART COOL Mirror ARNU15GSE*2 ARNU18GS8*2 4.5 5.6 Cooling Capacity 3,900 4,800 15,400 19,100 5.0 6.3 Heating Capacity 4,300 5,400 17,100 21,500 915 x 169 x 282 1,107 x 200 x 299 Dimensions(WxDxH) Body 36.0 x 6.5 x 11.1 43.9 x 7.9 x 11.8 Rows x Columns x FPI 2 x 15 x 18 2 x 15 x 20 Coil Face Area m3 0.21 0.26 Type Cross Flow Fan Cross Flow Fan Motor Output x Number W 20 20 Running Current A 0.2 0.2 Fan Air Flow Rate(H / M / L) CMM 10.5 / 8.0 / 6.0 14.4 / 13.0 / 11.0 cfm 371 / 283 / 212 508 / 459 / 388 Drive Direct Direct Motor type BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Air Filter Resin Net(washable) Resin Net(washable) Safety Device Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Drain Pipe(Internal Dia.) mm(inch) 16(5/8) 16(5/8) Net Weight kg(lbs) 11.2(24.7) 15(33.1) Noise Level(Sound Press, 1m, H / M / L) dB(A) 42 / 36 / 27 37 / 34 / 31 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Front Panel('*' Position) R:Mirror V:Silver B:Blue Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch
165
282
4 _ ART COOL Mirror 567
915
H
W
169
1
51
2
282
D
Air suction grill
282
H
Descripition
(unit : mm)
169
D
(unit : mm)
CHASSIS CODE: SE
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
2
Name Air discharge grill
1
915
W
Number
ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2
Model
ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2
ART COOL Mirror
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
53
Indoor Units
3. Dimensions
265
ART COOL Mirror _ 5
804
1107
1
72 58 122
2
281
93
299
3
200
53
4
Air suction grille Knockout hole Installation plate
4 5
(unit : mm) Remark
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
CHASSIS CODE: S8
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
ARNU18GS8*2 ARNU24GS8*2
Display & signal receiver
Front panel
Part Name
3
2
1
No.
Indoor Units
10 63
48
ART COOL Mirror
3. Dimensions
4. Piping Diagrams
Heat Exchanger
:Cooling :Heating
EEV Filter Th2
Th3
C.F.F
Indoor Units
Th1
Filter
lndoor unit
Refrigerant pipe connection port diameter [Unit: mm(inch)]
MODEL
GAS
LIQUID
ARNU07GSE*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU09GSE*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU12GSE*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU15GSE*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU18GS8*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU24GS8*2
Ø15.88(5/8)
Ø9.52(3/8)
*Panel Color (SE/S8 chassis) : R(Mirror),V(Silver), B(Blue)
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
6 _ ART COOL Mirror
PCB Connector CN-TH1 CN-TH2
5. Wiring Diagrams SE/S8 Chassis
Indoor Units
CONNECTOR NUMBER
LOCATION POINT
FUNCTION
CN-MOTOR1
Fan motor output
Motor output of BLDC
CN-COM
Communication
Communication between indoor and outdoor
CN-EEV
EEV output
EEV control output
CN-L/R
Step motor
Step motor output for left/right
CN-U/D
Step motor
Step motor output
CN-TH1
Room/pipe sensor
Room & pipe thermistor
CN-TH2
Discharge pipe sensor
Discharge pipe thermistor
CN-SUC
Step motor(front)
Front panel step motor
CN-HVB
Air purifier
Air purifier output
CN-VFD
Display
Display of indoor status
CN-12V
Safety connection
Safety of indoor status
CN-REMO
Remote controller
Remote control line
CN-CC
Dry contact
Dry contact line
CN-HVB
Air clean
Air clean control
ART COOL Mirror _ 7
6. Capacity Tables 6.1 Cooling Capacity
Cooling Capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
2.2
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5 1.5 1.5 1.5
2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3
1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4
2.8
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.9
3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0
2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7
3.6
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.5 2.5 2.4
4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8
2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2
Outdoor air temp. (DB, °C)
Indoor Units
Capacity Index
Notes: TC: Total Capacity(kW)
8 _ ART COOL Mirror
SHC: Sensible Heat Capacity(kW)
30 22 TC SHC kW kW
32 24 TC SHC kW kW
6. Capacity Tables Cooling Capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
Capacity Index
Outdoor air temp. (DB, °C)
4.5
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8
3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.9 2.8
5.6
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0
6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.8 3.8
7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0
4.3 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5
7.1
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1
7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2
5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1
8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4
5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.3 5.2 5.1 5.0 4.9 4.8
9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6
5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5
SHC: Sensible Heat Capacity(kW)
ART COOL Mirror _ 9
Indoor Units
Notes: TC: Total Capacity(kW)
32 24 TC SHC kW kW
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Heating Capacity Indoor air temp. (DB, °C)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
2.2
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7
1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
2.8
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
3.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6
2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3
2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0
2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Notes: TC: Total Capacity(kW)
10 _ ART COOL Mirror
6. Capacity Tables Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
4.5
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8
3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4
3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0
3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
5.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2
4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7
4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3
4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9
4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
7.1
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2
5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6
5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0
5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Notes: TC: Total Capacity(kW)
ART COOL Mirror _ 11
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
7. Air Velocity and Temperature Distribution ARNU07GSE*2 Cooling
Heating
Discharge angle:45°
Discharge angle:60° Air velocity [m/s]
Air velocity [m/s] 2.7m
2.7m
2m
2m
2.0
2.0
1.5
1m
1m 1.5 1.0
0.5
0.5
5m
4m
3m
2m
0m 0m
1m
5m
4m
1.0
3m
2m
0m 0m
1m
Temperature [°C]
Temperature [°C]
2.7m
Indoor Units
2.7m
2m
2m 33
18 30 20
1m
1m 24
22
21
24
5m
4m
3m
2m
1m
0m 0m
5m
4m
27
3m
2m
0m 0m
1m
ARNU12GSE*2 Cooling
Heating
Discharge angle:45°
Discharge angle:60° Air velocity [m/s]
Air velocity [m/s] 2.7m
2.7m
2m
2m 2.0
2.0 1.5
1m
1.5
0.5 0.5
5m
4m
3m
1m
1.0
1.0
2m
1m
0m 0m
5m
4m
3m
2m
0m 0m
1m
Temperature [°C]
Temperature [°C] 2.7m
2.7m
2m
2m 33
18
30
1m
21
1m 20 24
5m
4m
3m
24
27
22
2m
12 _ ART COOL Mirror
1m
0m 0m
5m
4m
3m
2m
1m
0m 0m
8. Electric Characteristics Units Model
Type
Power Supply Hz
Volts
Voltage Range MCA
IFM
Input(W)
MFA
kW
FLA
Cooling Heating
ARNU07GSE*2
SE
0.29
15
0.02
0.23
40
40
ARNU09GSE*2
SE
0.29
15
0.02
0.23
40
40
ARNU12GSE*2
SE
Max:264
0.29
15
0.02
0.23
40
40
ARNU15GSE*2
SE
Min:198
0.29
15
0.02
0.23
40
40
ARNU18GS8*2
S8
0.29
15
0.02
0.23
35
35
ARNU24GS8*2
S8
0.29
15
0.02
0.23
35
35
ARNU07GSE*2
SE
0.29
15
0.02
0.23
40
40
ARNU09GSE*2
SE
ARNU12GSE*2
SE
ARNU15GSE*2
SE
ARNU18GS8*2 ARNU24GS8*2
50
220 - 240
0.29
15
0.02
0.23
40
40
Max:242
0.29
15
0.02
0.23
40
40
Min:198
0.29
15
0.02
0.23
40
40
S8
0.29
15
0.02
0.23
35
35
S8
0.29
15
0.02
0.23
35
35
60
220
Indoor Units
Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA.
ART COOL Mirror _ 13
9. Sound Levels Overall Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
1m 1m Microphone
Sound Levels dB(A) H 37 39 41 42 37 43
ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 ARNU18GS8*2 ARNU24GS8*2
M 33 35 36 36 34 37
L 23 25 27 27 31 32
Sound Pressure Level ARNU07GSE*2
80
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
Approximate Hearing Threshold 63
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20
NC-25
20
70
NC-20
NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
10
Octave Band Sound Pressure Level (dB re 20µPa )
NC-65
Octave Band Sound Pressure Level (dB re 20µPa )
Approximate Hearing Threshold 63
NC-60
NC-50
NC-40
NC-30
10
ARNU24GS8*2 70
NC-60 NC-55 NC-50 NC-45 NC-40 NC-35
Octave Band Sound Pressure Level (dB re 20µPa )
70
NC-65
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20
10
Approximate Hearing Threshold 63
NC-20
NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
14 _ ART COOL Mirror
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
NC-30 NC-25
20
10
Approximate Hearing Threshold 63
NC-20
NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
ARNU18GS8*2
70
30
NC-25 Approximate Hearing Threshold 63
80
40
NC-35
30
80
50
NC-45
40
80
60
NC-55
50
20
NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
ARNU15GSE*2
NC-65
60
NC-20
Octave Band Sound Pressure Level (dB re 20µPa )
Octave Band Sound Pressure Level (dB re 20µPa )
ARNU12GSE*2 80
70
60
10
ARNU09GSE*2
80
70
Octave Band Sound Pressure Level (dB re 20µPa )
Indoor Units
Model
NC-20
NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
NC-25
20
10
Approximate Hearing Threshold 63
NC-20
NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Installation Parts Provided
1. Type "A" screw
2. Installation Plate
Indoor Units
Required Parts
Required Tools
❏ Installation plate ❏ Four type "A" screws ❏ Connecting cable
❏ Level gauge ❏ Screw driver ❏ Electric drill ❏ Hole core drill
❏ Pipes: Gas side Liquid side ❏ Insulation materials ❏ Additional drain pipe
❏ Flaring tool set ❏ Specified torque wrenches ❏ Spanner......................................................Half union ❏ A glass of water ❏ Screw driver ❏ Thermometer
ART COOL Mirror _ 15
10. Installation 10.1 Selection of the best location
More than 100mm
• There should not be any heat source or steam near the
unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
More than 100mm More than 2300mm
S8 chassis Installation Plate
Chassis Hook
The mounting wall should be strong and solid enough to protect it from the vibration. Mount the installation plate on the wall with four Type "A" screws. (If mounting the unit on the concrete wall, consider using anchor bolts.) • Always mount the Installation plate horizontally by aligning the marking-off line by means of the thread and a level.
Type “A”
SE chassis Installation Plate
Chassis Hook
Type “A”
The lower left and the right side of Installation Plate S8 chassis
Ø70mm
Ø70mm
Installation plate 133mm
100mm
Installation plate
Ø70mm
Ø70mm
85mm
Left rear piping
Right rear piping
110mm
SE chassis
110mm
Indoor Units
More than 200mm
Left rear piping
65mm
Right rear piping
CAUTION : In case that the unit is installed near the sea, the installation parts may be corroded by salt. The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
16 _ ART COOL Mirror
10. Installation Preparing work for installation ■ Preparing the indoor unit's piping and drain hose for installation through the wall. ■ Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis. ■ Replace the plastic tubing holder in the original position.
3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
Tape Connecting pipe Drain hose
Connecting cable
For right rear piping
*Foamed polyethylene or equivalent is recommended.
1. Route the indoor tubing and the drain hose in the direction of rear left.
Drain hose
4. Indoor unit installation ■ Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.
Connecting
Drain hose
2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole. ■ Do not connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
ART COOL Mirror _ 17
Indoor Units
NOTICE : If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.
10. Installation 5. Connecting the pipings to the indoor unit and drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.
■ Wrap the area which accommodates the rear piping housing section with vinyl tape. Indoor unit pipe Wrap with vinyl tape
Connection pipe Vinyl tape (wide)
Connecting cable
Indoor unit tubing
Flare nut
Pipings
Pipe Vinyl tape(narrow)
■ Tighten the flare nut with a wrench.
Indoor Units
Spanner (fixed) Flare nut Connection pipe
Torque wrench
■ Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section. Wrap with vinyl tape
Pipe
Indoor unit tubing
■ Mount the clamp on the boss with a type "B" screw.(optional)
Type "B" screw
Drain hose
Clamp
Vinyl tape(wide) Drain hose
For left rear piping
Boss
1. Route the indoor tubing and the drain hose to the required piping hole position. ■ When extending the drain hose at the indoor unit, install the drain pipe.
Drain pipe
Indoor unit drain hose Vinyl tape(narrow) Adhesive
6. Wrap the insulation material around the connecting portion. ■ Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap. Plastic bands
18 _ ART COOL Mirror
Insulation material
2. Insert the piping, drain hose and the connecting cable into the piping hole.
Connecting cable Drain pipe
10. Installation 3. Insert the connecting cable into the indoor unit. ■ Don't connect the cable to the indoor unit. ■ Make a small loop with the cable for easy connection later.
■ When extending the drain hose at the indoor unit, install the drain pipe.
Drain hose
4. Tape the drain hose and the connecting cable. • Connecting cable
Indoor unit drain hose Vinyl tape(narrow) Adhesive
7. Wrap the insulation material around the connecting portion. ■ Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap. Plastic bands
Insulation material
■ Wrap the area which accommodates the rear piping housing section with vinyl tape.
Indoor unit Spacer Installation plate
Connection pipe Vinyl tape (wide)
80mm
Indoor unit piping Wrap with vinyl tape Pipe
6. Connecting the pipings to the indoor unit and the drain hose to drain pipe. ■ Align the center of the pipings and sufficiently tighten the flare nut by hand.
Indoor unit tubing
Flare nut
Connecting cable
Vinyl tape (narrow)
Pipings
■ Tighten the flare nut with a wrench. Spanner (fixed)
Torque wrench
Flare nut Connection pipe
Indoor unit tubing
ART COOL Mirror _ 19
Indoor Units
5. Indoor unit installation ■ Hang the indoor unit from the hooks at the top of the installation plate. ■ Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
10. Installation ■ Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
9. Set the pipings and the drain hose to the back of the chassis with the tubing holder. ■ Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.
Pipe Drain hose
Vinyl tape (narrow)
Indoor Units
Wrap with vinyl tape(wide)
8. Reroute the pipings and the drain hose across the back of the chassis.
Tubing holder
10. Indoor unit installation ■ Remove the spacer. ■ Ensure that the hooks are properly seated on the installation plate by moving it left and right.
Connecting
Piping for passage through piping hole
Drain hose
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
20 _ ART COOL Mirror
10. Installation 10.2 Connection of Pipings 1. To remove the front panel from the indoor unit, remove the front panel from the indoor unit cabinet. ■ Set the air direction louvers up-and-down to the position(horizontally) by hand. ■ Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.
2. To check the drainage. ■ Pour a glass of water on the evaporator. ■ Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. Connecting area drain hose
Leakage checking Drain pan
Leakage checking
Front panel
■ The drain hose should point downward for easy drain flow. Downward slope
■ Do not make drain piping. Accumulated drain water Air
Do not raise
Water leakage
Water leakage
Waving
Tip of drain hose dipped in water Water leakage
Less than 50mm gap
Ditch
10.3 Connect the cable to the indoor unit 1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Remote control co cord
Connecting cable
ART COOL Mirror _ 21
Indoor Units
Drain hose
10. Installation [Multi V III Heat Pump Model] Terminal Block Indoor 1(L1) 2(L2)
3
SODU B
SODU A
IDU B
IDU A
INT B
INT A
4
INDOOR POWER INPUT
[Except Multi VIII Heat Pump Model] SODU
Terminal Block Indoor 1(L1) 2(L2)
3
4
B
A
IDU -
-
INTERNET DRY1 DRY2 GND 12V Outdoor unit B A -
Indoor Units
INDOOR POWER INPUT
2. Attach the Grille onto the cabinet. • Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis. • Press the Grille toward the chassis until it is back into its original place.
CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness.) 7) Always install an earth leakage circuit breaker in a wet or moist area. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.
22 _ ART COOL Mirror
10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
Indoor Units
TEMP
yes
Remote Controller
no
TEMP
Controller Remote
TEMP
Remote Controller
5feet (1.5meters)
no
no
Fig.1 Typical locations for remote controller
ART COOL Mirror _ 23
11. Accessories Standard Accessories Name
Installation panel
Type "A" screws and plastic anchors
Quantity
1 set
4 set
(Other)
SE
• Owner's manual • Installation manual S8
Indoor Units
Shape
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
24 _ ART COOL Mirror
Indoor unit ART COOL Gallery 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Electric Characteristics 8. Sound Levels 9. Installation 10. Accessories
1. List of functions Category
Air flow
Indoor Units
Air purifying
Installation
Reliability
Convenience
Individual control
Special function kit
Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU07GSF*2, ARNU09GSF*2, ARNU12GSF*2 3 X Auto X O 3/4/3 X O O X Option O O O O O(Heat recovery) O O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory Accessory Accessory -
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
1 _ ART COOL Gallery
2. Specifications Type Model Cooling Capacity
Heating Capacity Dimensions(WxDxH) Body Coil
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch m3
Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Front Panel('*' Position)
Ø, V, Hz mm2 mm2
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
• Panel color: E(Red), V(Silver), G(Gold) → Panel type 1: Kiss (Photo changeable) → Gallery type
ART COOL Gallery _ 2
Indoor Units
W A CMM cfm
ART COOL Gallery ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 600x146x600 600x146x600 600x146x600 23.6x5.7x23.6 23.6x5.7x23.6 23.6x5.7x23.6 2x20x21 2x20x21 2x20x21 0.18 0.18 0.18 Turbo Fan Turbo Fan Turbo Fan 30 30 30 0.16 0.16 0.16 8.1 / 6.3 / 4.2 8.1 / 6.3 / 4.2 9.3 / 7.7 / 6.0 286 / 222 / 148 286 / 222 / 148 328 / 272 / 212 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Resin Net(washable) Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 12.2(15/32) 12.2(15/32) 12.2(15/32) 15(33.1) 15(33.1) 15(33.1) 38 / 32 / 27 38 / 32 / 27 44 / 38 / 32 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C E:Red, V:Silver, G:Gold, 1: Kiss (Photo changeable)
1
3 _ ART COOL Gallery
Fix Hole
2
500
Pipe Hole
W
Hanger Hole
1
H
D
1
Air discharge grill Air suction grill
1 2
600
H
Descripition
(unit : mm)
146
D
(unit : mm)
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
CHASSIS CODE: SF
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Name
600
W
ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2
ART COOL Gallery
Number
ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2
Model
Indoor Units
3. Dimensions
525
4. Piping Diagrams
Heat Exchanger Th3
EEV
Filter
:Cooling :Heating
Th2
Turbo Fan
Th1
Filter
lndoor unit
[Unit: mm(inch)]
Model
Gas
Liquid
ARNU07GSF*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU09GSF*2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU12GSF*2
Ø12.7(1/2)
Ø6.35(1/4)
*Panel color :E(Red), V(Silver), G(Gold), 1(Kiss (Photo changeable)) LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
PCB Connector CN-TH1 CN-TH1
ART COOL Gallery _ 4
Indoor Units
Refrigerant pipe connection port diameter
5. Wiring Diagrams
Indoor Units
SF Chassis
CONNECTOR NUMBER CN-MOTOR1 CN-COM
LOCATION POINT Fan motor output Communication
FUNCTION Motor output of BLDC Communication between indoor and outdoor
CN-EEV CN-D1 CN-LR1
EEV output Display Step motor
EEV control output Display of indoor status Step motor output for left/right
CN-LR2 CN-UD CN-TH1
Step motor Step motor Room/pipe sensor
Step motor output for left/right Step motor output Room and pipe thermistor
CN-TH2 CN-REMO
Discharge pipe sensor Remote controller
Discharge pipe thermistor Remote control line
CN-CC CN-HVB
Dry contact Air clean
Dry contact line Air clean control
5 _ ART COOL Gallery
6. Capacity Tables 6.1 Cooling Capacity
Cooling Capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
Capacity Index
Outdoor air temp. (DB, °C)
2.2
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5 1.5 1.5 1.5
2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3
1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4
2.8
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.9
3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0
2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7
3.6
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.5 2.5 2.4
4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8
2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2
SHC: Sensible Heat Capacity(kW)
ART COOL Gallery _ 6
Indoor Units
Notes: TC: Total Capacity(kW)
32 24 TC SHC kW kW
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Heating Capacity
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
2.2
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7
1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
2.8
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
3.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6
2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3
2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0
2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Notes: TC: Total Capacity(kW)
7 _ ART COOL Gallery
7. Electric Characteristics Units Model
Type
ARNU07GSF*2
SF
ARNU09GSF*2
SF
ARNU12GSF*2
SF
ARNU07GSF*2
SF
ARNU09GSF*2
SF
ARNU12GSF*2
SF
Power Supply Hz 50
Volts 220 - 240
60
220
Voltage Range MCA Max:264 Min:198
Max:242 Min:198
IFM
Input(W)
MFA
kW
FLA
Cooling Heating
0.23
15
0.024
0.18
35
35
0.23
15
0.024
0.18
35
35
0.23
15
0.024
0.18
35
35
0.23
15
0.024
0.18
35
35
0.23
15
0.024
0.18
35
35
0.23
15
0.024
0.18
35
35
Symbols:
Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA. 5. Instead of fuse, use Circuit Breaker.
ART COOL Gallery _ 8
Indoor Units
MCA: Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor
8. Sound Levels Overall
Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
1m 0.8m Microphone
H
Sound Levels dB(A) M L
ARNU07GSF*2
38
32
27
ARNU09GSF*2
38
32
27
ARNU12GSF*2
44
38
32
Sound Pressure Level ARNU07GSF*2 ARNU09GSF*2
ARNU12GSF*2 80
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
Octave Band Sound Pressure Level (dB re 20µPa )
80
Octave Band Sound Pressure Level (dB re 20µPa )
Indoor Units
Model
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
NC-25
20
NC-20
Approximate Hearing Threshold
NC-15
10 63
NC-25
20
Approximate Hearing Threshold 125
250
500
1000 2000 4000 8000
Octave Band Center Frequency (Hz)
9 _ ART COOL Gallery
NC-20 NC-15
10 63
125
250
500
1000 2000 4000 8000
Octave Band Center Frequency (Hz)
9. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Installation Parts Provided
1. Installation guide map
2. Type "A" screw and plastic anchors Indoor Units
Required Parts
Required Tools
❏ Four type "A" screws ❏ Connecting cable ❏ Pipes: Gas side Liquid side
❏ Level gauge ❏ Screw driver ❏ Electric drill ❏ Hole core drill ❏ Flaring tool set ❏ Specified torque wrenches ❏ Spanner......................................................Half union ❏ A glass of water ❏ Screw driver ❏ Thermometer
❏ Insulation materials ❏ Additional drain pipe
9.1 Selection of the best location • Do not have any heat or steam near the unit. • Select a place where there are no obstacles in front of the unit. • Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway. • Ensure that the space around the left and right of the unit is more than 500mm. The unit should be installed as high on the wall as possible, allowing a minimum of 200mm from ceiling. • Use a stud finder to locate studs to prevent unnecessary damage to the wall.
More than 200mm More than 500mm
More than 500mm More than 1500mm
ART COOL Gallery _ 10
9. Installation 9.2 Preparing Work for Installation Open panel front 1. Pull the upper part of the front panel. 2. Lift up the panel. 3. To detach the front panel, remove the two screws at the lower part. 4. Detach the front panel from the body.
Indoor Units
5. To detach the panel, disconnect the connector at the upper part.
Panel Front Connector
Cover pipe and cover side remove 1. Please remove the screw of the center tuning cover. 2. Pull up the side cover of desired connecting direction, then cover side is separated. 3. Pick the pipe hole of the side cover.
CAUTION: After removing the pipe hole, cut the burr for safety.
Pipe hole Side cover
NOTICE
When making pipe path through rear wall, you donĘźt need to pick the pipe hole.
Drain hose junction 1. Remove the rubber stopple in the desired drain direction. 2. Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by. Adhesive
Onlythe the Only desired desireddirection direction
Connecting part Drain hose
11 _ ART COOL Gallery
rubber cap
9. Installation 9.3 Fixing Indoor Unit 1. Attach an Installation guide map on the desired surface. INSTALLATION GUIDE MAP
2. Look at suited horizon by horizontal meter on the horizontal setting line, and fix lightly the map by adhesive tape. Horizontality
3. Make a hole with a diameter of 6mm and depth of 30-35mm by piercing a screw point. IN ST AII AT IO N
IN ST AL LA TIO N
GU ID EM AP
4. Drill the pierted part as a diameter of 50mm for connecting piping. (In case of piercing rear surface)
GU ID EM AP
IN ST AL LA TIO N
GU ID EM AP
6. First, Drive the two points of the upper parts by screws. (Leave 10mm for hanging the product) 10
Plastic anchors
7. Hang the hole of product at the upper screws, and remove the map. (Falling attention) INS TAL LAT ION GUID EM AP
mm
IN ST AL LA TIO N
GU
8. Drive the lower parts after facing the hole of product with plastic anchors, and fix completely the upper screws. Plastic anchors
Hanger hole (Rear side of the product)
9. Check the fixed product with light power.
10. In case of nothing wrong, connect the pipe and the wire. (Refer to installation manual)
ART COOL Gallery _ 12
Indoor Units
5. Drive the fore plastic anchors into drilled points.
9. Installation 9.4 Connecting the Piping Preparing the indoor unit's piping and drain hose for installation through the wall. 1. Route the indoor tubing and the drain hose in the direction of rear left or right
3. Connecting the pipings to the in door unit and drain hose to drain pipe ❏ Align the center of the pipings and sufficiently tighten the flare nut by hand.
Indoor unit tubing
Flare nut
Pipings
❏ Tighten the flare nut with a wrench.
Drain hose
Spanner (fixed)
Indoor Units
Flare nut
2. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
Torque wrench
Connection pipe
Indoor unit tubing
❏ When extending the drain hose at the indoor unit, install the drain pipe.
Drain pipe
Loop
Connecting cable
Gas side piping Liquid side piping
Drain hose
CAUTION: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.
13 _ ART COOL Gallery
Indoor unit drain hose Adhesive
Vinyl tape(narrow)
4. Wrap the insulation material around the connecting portion. ❏ Overlap the connecting pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Plastic bands Insulation material
9. Installation CAUTION: Installation Information For right piping. Follow the instruction below. Good case • Press on the upper side of clamp and unfold the tubing to downward slowly.
Indoor Units
Bad case • Following bending type from left to right may cause damage to the turbing.
9.5 Drain Piping 1) To check the drainage. • Pour a glass of water on the evaporator. • Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
2) Drain piping • The drain hose should point downward for easy drain flow. Downward slope
• Do not make drain piping. Do not raise
Tip of drain hose dipped in water
Accumulated drain water
Less than 50mm gap
Air
Water leakage
Water leakage
Waving
Water leakage
Ditch
ART COOL Gallery _ 14
9. Installation 9.6 Panel Front Assembly
Indoor Units
1. First, Check the side cover assembly exactly, and fix the power cord in the bottom groove of cover side left.
2. Assemble connecting lead wire with controller, fix the upper part of panel front, and match the lower part of panel front. Panel Front Connector
3. Screw up panel front, and suspend the hook of panel front in the groove.
15 _ ART COOL Gallery
9. Installation 9.7 Connect the cable to the Indoor unit. • Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.) The earth wire should be longer than the common wires. [Multi V III Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU B
SODU A
IDU B
IDU A
INT B
INT A
4
INDOOR POWER INPUT
[Except Multi VIII Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU
4
B
A
INTERNET DRY1 DRY2 GND 12V
IDU -
-
B
A
-
-
-
-
Outdoor Unit
CAUTION • When installing, refer to the circuit diagram on the Control Box of Indoor Unit. • When installing, refer to the wiring diagram on the Control Cover Inside Outdoor Unit.
CAUTION • The above circuit diagram is subject to change without notice. • Be sure to connect wires according to the wiring diagram. • Connect the wires firmly, so that not to be pulled out easily. • Connect the wires according to color codes by referring the wiring diagram.
After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power circuit specifically for the air conditioner. As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Confirm the specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. 7) Always install an earth leakage circuit breaker in a wet or moist area. 8) The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.
ART COOL Gallery _ 16
Indoor Units
INDOOR POWER INPUT
9. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
Indoor Units
- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
TEMP
yes
Remote Controller
no
TEMP
Controller Remote
TEMP
Remote Controller
5feet (1.5meters)
no
no
Fig.1 Typical locations for remote controller
17 _ ART COOL Gallery
10. Accessories Standard Accessories Name
Installation guide map
Quantity
1 EA
Type "A" screws and plastic anchors
(Other)
4 SET • Owner's manual • Installation manual
Shape
Indoor Units
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
ART COOL Gallery _ 18
Indoor unit Ceiling & Floor / Ceiling Suspended 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of functions Category
Air flow
Air purifying
Reliability
Convenience
Individual control
Special function kit
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU09GVEA2, ARNU12GVEA2 ARNU18GVJA2, ARNU24GVJA2 1 Manual Auto X O 3/4/3 X O O X X O X X X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Ceiling & Floor / Ceiling Suspended _ 1
Indoor Units
Installation
Function
2. Specifications Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Dimensions(WxDxH) Body
Indoor Units
Coil
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
mm inch m3 W A CMM cfm
Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color
Ø, V, Hz mm2 mm2
Ceiling & Floor ARNU09GVEA2 ARNU12GVEA2 2.8 3.6 2,400 3,100 9,600 12,300 3.2 4.0 2,800 3,400 10,900 13,600 900 x 200 x 490 900 x 200 x 490 35.4 x 7.9 x 19.3 35.4 x 7.9 x 19.3 2 x 12 x 20 2 x 12 x 20 0.10 0.10 Cross Flow Fan Cross Flow Fan 27 27 0.15 0.15 7.6 / 6.9 / 6.2 9.2 / 7.6 / 6.9 268 / 243 / 219 325 / 268 / 244 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 16(5/8) 16(5/8) 13.7(30.2) 13.7(30.2) 36 / 32 / 28 38 / 36 / 30 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
2 _ Ceiling & Floor / Ceiling Suspended
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specifications Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Dimensions(WxDxH) Body Coil
m3 W A CMM cfm
Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Color
Ø, V, Hz mm2 mm2
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Ceiling & Floor / Ceiling Suspended _ 3
Indoor Units
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
mm inch
Ceiling Suspended ARNU18GVJA2 ARNU24GVJA2 5.6 7.1 4,800 6,100 19,100 24,200 6.3 8.0 5,400 6,900 21,500 27,300 Galvanized Steel Plate+Painting Galvanized Steel Plate+Painting 950 x 220 x 650 950 x 220 x 650 37.4 x 8.7 x 25.6 37.4 x 8.7 x 25.6 3 x 14 x 19 3 x 14 x 19 0.23 0.23 Sirocco Fan Sirocco Fan 60 60 0.30 0.30 16.0 / 14.0 /12.0 18.0 / 16.0 / 14.0 565 / 495 / 424 636 / 565 / 495 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) 16(5/8) 16(5/8) 24.6(54.2) 24.6(54.2) 42 / 40 / 37 43 / 41 / 39 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog
587
273
4 _ Ceiling & Floor / Ceiling Suspended Liquid pipe Gas pipe Suction gille Discharge grille Suspension bracket Right side drain hose hole Left side drain hose hole Wiring connection Piping connection Signal receiver & Operation indicator 1 2 3 4
Slit hole Slit hole
More than 200mm
CHASSIS CODE: VE
More than 50mm
More than 200mm
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
More than 50mm
More than 200mm
※ Required space(unit:mm)
More than 200mm
(unit : mm)
200
D
(unit : mm)
Descripition ø6.35 Flare connection ø12.7 Flare connection
490
H
Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
5 6 7 8 9 10
Name
900
ARNU09GVEA2 ARNU12GVEA2
Number
W
ARNU09GVEA2 ARNU12GVEA2
Ceiling & Floor
Model
Indoor Units
3. Dimensions
(unit : mm)
220
D
(unit : mm)
Slit hole Slit hole Slit hole Slit hole
Descripition ø6.35 Flare connection ø12.7 Flare connection
650
H
Ceiling & Floor / Ceiling Suspended _ 5
Indoor Units
CHASSIS CODE: VJ
More than 300mm
More than 700Um
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
More than 700mm
※ Required space(unit:mm)
Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
5 6 7 8 9 10 11
Name Liquid pipe Gas pipe Suction gille Discharge grille Suspension bracket Right side drain hose hole Left side drain hose hole Wiring connection Piping connection Right side drain pipe connection Left side drain pipe connection
1 2 3 4
950
ARNU18GVJA2 ARNU24GVJA2
Number
W
Model
ARNU18GVJA2 ARNU24GVJA2
Ceiling Suspended
3. Dimensions
4. Piping Diagrams VE Chassis Heat Exchanger Th3
EEV
Filter
Th2 C.F.F.
Th1
Indoor Units
:Cooling :Heating
Filter
lndoor unit
VJ Chassis Heat Exchanger
EEV
:Cooling :Heating
Filter
Th2
Th3 Sirocco Fan
Th1
Filter
lndoor unit
Refrigerant pipe connection port diameter [Unit: mm(inch)]
Model
Gas
Liquid
ARNU09GVEA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU12GVEA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU18GVJA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU24GVJA2
Ø15.88(5/8)
Ø9.52(3/8)
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
6 _ Ceiling & Floor / Ceiling Suspended
5. Wiring Diagrams VE Chassis
CN-POWER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-DISPLAY CN-DOOR CN-CC
SPEC.
DESCRIPTION
AC power supply Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Option pwb. Communication Drain pump output AC power supply Display wire Door lock switch Dry contact
AC power line input for indoor controller Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV Control output Communication between main and option Communication between indoor and outdoor AC Output for drain pump AC Power line input for indoor controller Display wire line Door lock switch line Dry contact line
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
Ceiling & Floor / Ceiling Suspended _ 7
Indoor Units
CONNECTOR NUMBER
5. Wiring Diagrams
Indoor Units
VJ Chassis
CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-DISPLAY CN-DOOR CN-CC
SPEC.
DESCRIPTION
AC power supply Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Option pwb. Communication Drain pump output AC power supply Display wire Door lock switch Dry contact
AC power line input for indoor controller Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV Control output Communication between main and option Communication between indoor and outdoor AC Output for drain pump AC Power line input for indoor controller Display wire line Door lock switch line Dry contact line
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
8 _ Ceiling & Floor / Ceiling Suspended
6. Capacity Tables 6.1 Cooling Capacity
Cooling capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
2.8
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.9
3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0
2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7
3.6
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7
2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4
4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8
2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2
5.6
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0
6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.8 3.8
7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0
4.3 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5
Capacity Index
Outdoor air temp. (DB, °C)
32 24 TC SHC kW kW
SHC: Sensible Heat Capacity(kW)
Ceiling & Floor / Ceiling Suspended _ 9
Indoor Units
Notes: TC: Total Capacity(kW)
30 22 TC SHC kW kW
6. Capacity Tables
Indoor Units
Cooling capacity
Capacity Index
Outdoor air temp. (DB, °C)
7.1
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
Notes: TC: Total Capacity(kW)
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1
SHC: Sensible Heat Capacity(kW)
10 _ Ceiling & Floor / Ceiling Suspended
7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2
5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 5.0
5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4 5.3 5.2 5.1 5.1 5.0 4.9 4.8
32 24 TC SHC kW kW 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6
5.4 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9 4.8 4.7 4.6 4.6 4.5 4.4
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Heating capacity Indoor air temp. (DB, °C)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
2.8
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
3.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6
2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3
2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0
2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
5.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2
4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7
4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3
4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9
4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Notes: TC: Total Capacity(kW)
Ceiling & Floor / Ceiling Suspended _ 11
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
6. Capacity Tables Heating capacity
Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor Units
7.1
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2
5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6
5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0
5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Notes: TC: Total Capacity(kW)
12 _ Ceiling & Floor / Ceiling Suspended
7. Air Velocity and Temperature Distribution ARNU09GVEA2 ■ Ceiling Cooling
Heating Discharge angle:60°
Discharge angle:50° Air velocity [m/s]
Air velocity [m/s] 1.5
2.7m 0.5
1.0
2.7m
0.5
0.5
1.0 1.0
0.5
1.0
0.5
1.0
2m
0.5
2m
1.0
0.5 1.0
1.0
0.5
0.5
0.5
0.5
1.0
4m
3m
2m
1m
0.5
1.0
0m 0m
5m
Temperature [°C]
4m
3m
2m
0m 1m
0m
Temperature [°C] 2.7m
32.0 30.0
.0 42
32
44.0 42.0
.5
15.0
30.0
18.0
17.0
28.0
.0
17.0 16.0
32
17.0
2.7m
14.0 13.0 13.0 15.0 17.0 17.0
.0 34
2m
2m
38.0
32.5 18.0 18.0
32.0
17.0
1m
30.0
18.0
18.0
30.0
4m
3m
2m
0m
1m
.0 3434.0
28.0
0m
5m
1m
5m
4m
3m
2m
1m
0m
0m
ARNU09GVEA2 ■ Floor
Cooling
Heating Discharge angle:50°
Discharge angle:45° Air velocity [m/s]
Air velocity [m/s] 2.7m 0.5
2.7m
0.5
1.0
0.5
0 .5
0.5
0.5
2m
2m 1.0
1.0
0.5
0.5
0.5
0.5
0.4
0m 3m
2m
1m
4m
3m
0.5
2m
0m
1m
0m
Temperature [°C] .0
32
.0
36.0
2.7m
0 18.
38.0
35
2m
35.1
35 .1
36.0
0 18.
18.0
34.0
1m
0m
5m
35.1
35.1
0m 2m
1m .0
18.0
1m
40
0 16.
38.0
38.0
14.8
2m
42.0
14.8
3m
2.7m
35.1
14.8
4m
0.5
0.5
1.0
5m
0m
Temperature [°C]
5m
1m
0.4 0. 0.4 5
0.5 4m
1.0 0.4
0.5
1.5
2.0
1m
1.5
0.2
5m
0.5
1.0
0.5
4m
3m
34.0
2m
34.0
0m 1m
0m
Ceiling & Floor / Ceiling Suspended _ 13
Indoor Units
15.0
32.0
5m
1m
0.5
1m
7. Air Velocity and Temperature Distribution ARNU12GVEA2 ■ Ceiling Cooling
Heating Discharge angle:60°
Discharge angle:50°
Air velocity [m/s]
Air velocity [m/s] 1.0
0.5 2.5 1.5
1.5
1.0
1.0
0.5
2.7m
1.0
2.7m
26.0
28.0
1.0
1.0
30.0
30.0
44.0
0.5
0.5
26.0
2m
2m
38.0 30.0
28.0 1.0
1m
1m 0.5
26.0 30.0
1.0 1.0
0.5
1.5
0.5
28.0
24.0
32.0
0m
0m 5m
4m
3m
2m
1m
5m
0m
Indoor Units
3m
2m
1m
0m
Temperature [°C]
Temperature [°C] 14.0
15.0
17.0
4m
16.0
2.7m
14.0 13.0 13.0
15.0
2.7m
26.0
28.0
30.0
30.0
18.0 17.0
17.0
44.0 26.0
2m
17.0
2m
38.0 30.0
28.0
1m
1m
26.0 17.0
17.0
30.0
16.0 18.0
17.0 16.0
28.0
24.0
32.0
0m
0m 5m
4m
3m
2m
0m
1m
5m
4m
3m
2m
0m
1m
ARNU12GVEA2 ■ Floor
Cooling
Heating Discharge angle:60°
Discharge angle:50°
Air velocity [m/s] 2.7m 0.5
0.5
0.5
2m
1.0
1.5
1.0
0.4
1. 0
1.0
2.0
1.0
0.5
0.5
1.0
0.5
1.0
0.5 0.5
1.0
0.5
1m
1.5 1.5
1.0
0.5
1m
0.4 0.5
0.5
2.5
0.5
1.5
1.0 1.5
0.4
2m
1.5
0.5
0.5
0.4
2.7m
1.5
0. 5
1.0
1.5
Air velocity [m/s]
0m 4m
3m
2m
1m
0m
0m 5m
4m
3m
2m
1m
0m
Temperature [°C]
Temperature [°C] 16.0
2.7m
36.0 34.0
16.0
36.0 15.0
18.0
38.0
5m
16.8
38 38 .0
2.7m
.0
35.4
2m
.4
2m
1m
40.0
1m
36 .0
17.0
18.0
3m
35
4m
15.0
.0 42 42.035.4
.0
5m
16.8
36.0 35.4
36.0
1m
16 16.8
.0 20 19.0
35.4
14.0 13.0 16 .0
42.0
38.0
2m
34.0
0m 0m
14 _ Ceiling & Floor / Ceiling Suspended
5m
4m
3m
34.0
35.4
0m 2m
1m
0m
7. Air Velocity and Temperature Distribution ARNU18GVJA2 ■ Ceiling Cooling
Heating Discharge angle:60°
Discharge angle:50° Air velocity [m/s]
Air velocity [m/s] 3.0
3.0
1.5
4.0
2.7m
1.5 4.0 1.5 3.5
1.5
3.0
1.5
3.0
1.5
2.7m
1.0
3.0
3.0 1.5
1.5
1.0
1.5
2m
2m
1.5
1.5
1m
1.5
1m
1.0 1.5
1.5 1.0
1.5
1.5 0m
4m
3m
2m
1m
0m
Temperature [°C]
3m
2m
1m
0m
Temperature [°C] 40.0
34.0
38.0
40.0
42.0
2.7m
42.0 36.0
2m
36.0
2m
.0
17.0
2.7m
13.0 14.0 13.0 14.0 17.0 17.0
32
16
16.0
40.0
14.0
.0
18.0
.0
4m
30.0
16.0
36.0
1m
38.0
18.0
1m
36
.0
36.0
.0
.0 19
17
.0
19
28.0
0m 5m
4m
3m
2m
0m
1m
0m 5m
4m
3m
2m
0m
1m
ARNU24GVJA2 ■ Ceiling
Cooling
Heating Discharge angle:60°
Discharge angle:50° g
Air velocity [m/s]
Air velocity [m/s] 3.0
1.0
2.7m
2.0
2.0 1.0 1.0 4 2.0 .5 5.0 1.0
1.0
1.0
2.7m
1.0 0.5 3.0 3.5 3.0 1.0
2.0
3.0
6.0
g
1.0
2m
1.0
2m 0.5 1.0
2.0
1.0
1m
1m
1.0
1.0
1.0
1.0
2.0
0m
0m 4m
3m
2m
1m
5m
0m
3m
2m
1m
0m
Temperature [°C] 2.7m
34.0
15.0
40.0 38.0
38.0
38.0
14.0 13.0 17.0
18.0
17.0
17.0
40.0 36.0
2.7m
40.0
.0 42.0 42 36.0 38.0
.0
15.0
13.0
Temperature [°C] .0 18
4m
36
5m
34.0
2m
2m
36.0
16.0
18.0
1m
1m
5m
17.0
.0
.0 36 2.0 3
16 19 .0
.0
18
36.0
32.0
0m
0m 4m
3m
2m
1m
0m
5m
4m
3m
2m
1m
0m
Ceiling & Floor / Ceiling Suspended _ 15
Indoor Units
15
0m 5m
34.0
5m
8. Electric Characteristics Units Model
Type
ARNU09GVEA2 ARNU12GVEA2
VE VE
ARNU18GVJA2 ARNU24GVJA2
VJ VJ
ARNU09GVEA2 ARNU12GVEA2 ARNU18GVJA2 ARNU24GVJA2
VE VE VJ VJ
Power Supply Hz
50
Volts
220 - 240
60
220
Voltage Range MCA Max:264 Min:198
Max:242 Min:198
IFM
Input(W)
MFA
kW
FLA
Cooling Heating
0.22 0.22
15 15
0.027 0.027
0.17 0.17
30 30
30 30
0.43 0.43
15 15
0.060 0.060
0.35 0.35
63 63
63 63
0.22 0.22 0.43 0.43
15 15 15 15
0.027 0.027 0.060 0.060
0.17 0.17 0.35 0.35
30 30 63 63
30 30 63 63
Indoor Units
Symbols: MCA: Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA. 5. Instead of fuse, use Circuit Breaker.
16 _ Ceiling & Floor / Ceiling Suspended
9. Sound Levels Overall Notes: - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
1m
1m Microphone
Sound Levels dB(A)
Model
Sound Levels dB(A)
Model
H
M
L
H
M
L
ARNU09GVEA2
36
32
28
ARNU18GVJA2
42
40
37
ARNU12GVEA2
38
36
30
ARNU24GVJA2
43
41
39
Sound Pressure Level
70
70
70
NC-65 60 NC-60 NC-55
50
NC-50 NC-45 40 NC-40 NC-35
30
NC-30
NC-25
20 Approximate Hearing Threshold
NC-60
NC-50 NC-45 40 NC-40
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
NC-35
30
NC-30
NC-25
20 Approximate Hearing Threshold
NC-15 125
NC-55
50
NC-20
10 63
NC-65 60
NC-65 60 NC-60
NC-15 125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
NC-55
50
NC-50 NC-45 40 NC-40 NC-35
30
NC-30
NC-25
20 Approximate Hearing Threshold
NC-20
10 63
Octave Band Sound Pressure Level (dB re 20μPa )
80
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
ARNU18GVJA2
ARNU12GVEA2 80
NC-20 NC-15
10 63
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
ARNU24GVJA2 80
Octave Band Sound Pressure Level (dB re 20μPa )
70
NC-65 60 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
20
10
NC-25 Approximate Hearing Threshold 63
NC-20 NC-15 125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
Ceiling & Floor / Ceiling Suspended _ 17
Indoor Units
ARNU09GVEA2 80
10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
10.1 Features 10.1.1 VE Chassis
Vertical louver
Horizontal louver
Indoor Units
Air outlet vent
Air filters (behind front panel) Air inlet vent
18 _ Ceiling & Floor / Ceiling Suspended
10. Installation 10.1.2 VJ Chassis
Air Discharge
Right Side Cover
Signal Receptor
Left Side Cover
Inlet Grill
Drain hose
Ceiling & Floor / Ceiling Suspended _ 19
Indoor Units
Air Filter
10. Installation VE Chassis 10.2 Installation Map NOTICE
Installation parts you should purchase.
There should be no gap between the ceiling and the unit.
Indoor Units
Ceiling Mounting
Sleeve Bushing-Sleeve Putty(Gum Type Sealer) More than 200mm (Left and right are identical)
More than 50mm
Bend the pipe as closely on the wall as possible, but be careful that it doesn't break.
Wall Mounting
More than 200mm (Left and right are identical)
Vinyl tape (Wide) • To carry out the drainage test, remove the air filters and pour water into the heat exchanger. • Apply after carrying out a drainage test.
More than 50mm
Saddle
20 _ Ceiling & Floor / Ceiling Suspended
10. Installation 10.3 Select the best Location Indoor unit
More than 200mm
1. Do not have any heat or steam near the unit. 2. Select a place where there are no obstacles in front of the unit.
More than 200mm
3. Make sure that condensation drainage can be conveniently routed away. More than 50mm
4. Do not install near a doorway. 5. Ensure that the interval between a wall and the left (or right) of the unit is more than 200mm. The unit should be installed as low as possible on the wall, allowing a minimum of 500mm from floor.
More than 200mm
More than 50mm
More than 200mm
9.4 Preparing Work for Installation Open panel front 1. Remove the five screws. 2. Release the claws in the 3 places indicated. 3. Pull up the Front Panel.
2 Claw
Cover pipe and cover side remove 1. Pull up the side cover of desired connecting direction, then cover side is separated. 2. Pick the pipe hole of the side cover.
1
3
CAUTION: After removing the pipe hole, cut the burr for safety. NOTICE
When making pipe path through rear wall, you donĘźt need to pick the pipe hole.
Drain hose junction 1. Remove the rubber stopple in the desired drain direction. 2. Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure as shown on the right.
Ceiling & Floor / Ceiling Suspended _ 21
Indoor Units
6. Use a stud finder to locate studs to prevent unnecessary damage to the wall.
10. Installation 10.5 Mounting the installation plate(Wall Mounting) The wall you select should be strong and solid enough to prevent vibration
Indoor Units
1. Mount the installation plate on the wall with type "A" screws. While mounting the unit on a concrete wall, use anchor bolts. • Mount the installation plate horizontally by aligning the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
Installation Plate
Type "A" screw
70
70 Installation plate
Ă˜70mm
120
Ă˜70mm
more than 2000 Left rear piping
Right rear piping Floor
22 _ Ceiling & Floor / Ceiling Suspended
10. Installation 10.6 Mounting the anchor Nut & Bolt(Ceiling Mounting) • Prepare 4 suspension bolts. (Each bolts length should be same.) • Measure and mark the position for the Suspension bolts and the piping hole. • Drill the hole for anchor nut on the ceiling.
Anchor nut Ceiling Nut
Washer
Suspension bolts
• Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
40
235 820
Suspension bolt
50 100
• Mount the suspension bolts to the anchor-nuts firmly. • Secure the hangers onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers.
Reference of piping hole (Ø45)
piping hole (Ø45)
• Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts.
: Tighten the nut and bolt to prevent unit falling.
Spring washer Hangen Max. 12mm
Nut
Washer
Hanging bolt (W3/8 or M10) Nut (W3/8 or M10)
Flat washer for M10 (accessory)
Flat washer for M10 (accessory) Nut (W3/8 or M10)
Ceiling & Floor / Ceiling Suspended _ 23
Indoor Units
Suspension bolts
• Adjust a level on the direction of top-bottom by adjusting supension bolts. Then the unit will be inclined to the bottomside so as to drain well.
10. Installation : Installation Information For right piping. Follow the instruction below.
Good case
Bad case
For left piping. Follow the instruction below.
1. Following bending type from right to left could cause problem of pipe damage.
1. Press on the upper side of clamp. (â’ś) 2. Unfold the tubing downward slowly. (â’ˇ)
Indoor Units
3. Bend the tubing to the left side of chassis.
24 _ Ceiling & Floor / Ceiling Suspended
10. Installation 10.7 Checking the Drainage 1. Set the air direction louvers up-and-down to the position(horizontally) by hand.
To check the drainage. 1. Pour a glass of water on the evaporator using a kettle. 2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. ■ Checking the Drainage 1. Remove the Air Filter.
• To remove air filter, take hold of tab and pull slightly upwards.
Indoor Units
2. Check the drainage.
• Spray one or two glasses of water upon the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.
Downward slope
Drain piping 1. The drain hose should point downward for easy drain flow. 2. Do not make drain piping like the following.
Do not raise
Water leakage
Water leakage
Accumulated drain water Air
Waving
Less than 50mm gap
Tip of drain hose dipped in water
Water leakage
Ditch
10.8 Panel Front Assembly 1. Suspend the hook of panel front in the groove. 2. Press the panel front.
1
3. Screw up panel front. 3 2
Ceiling & Floor / Ceiling Suspended _ 25
10. Installation VJ Chassis 10.9 Select the best Location Indoor unit 1. Do not have any heat or steam near the unit.
More than 700mm
2. Select a place where there are no obstacles in front of the unit. 3. Make sure that condensation drainage can be conveniently routed away. 4. Do not install near a doorway.
Indoor Units
5. Ensure that the interval between a wall and the left (or right) of the unit is more than 700mm. 6. Use a stud finder to locate studs to prevent unnecessary damage to the wall.
More than 700mm
More than 300mm
: In case that the unit is installed near the sea, the installation parts may be cor-
roded by salt. The installation parts (and the unit) should be treated with appropriate anti-corrosion measures.
26 _ Ceiling & Floor / Ceiling Suspended
10. Installation 10.10 Preparing Work for Installation Open side cover 1. Remove two screws from side-cover as shown in fig. 2. Unlock side-cover from side panel by slightly pulling the edge of side cover. 3. Tap the side-cover with your palm on the backside.(Inlet grill side.) 4. Hold the side-cover with other hand while tapping to prevent it to fall down.
2 Edge part
1
5. Remove the rubber stopple in the desired drain direction. Indoor Units
6. Knock out the pipe hole from the left side-cover with the help or nipper/plier. 7. Knock hole on right side-cover only if right side is selected for water drain.
Ceiling & Floor / Ceiling Suspended _ 27
10. Installation (Unit: mm)
MOUNTING THE ANCHOR NUT AND BOLT
DIM.
A
B
855
320
MODEL
• Prepare 4 suspension bolts. (Each bolts length should be same.)
VJ
• Measure and mark the position for the Suspension bolts and the piping hole. • Drill the hole for anchor nut on the ceiling. • Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
B
A
Ceiling
Suspension bolt Nut
Washer
Suspension bolts
• Secure the hangers onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers. • Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts.
Suspension bolts
• Adjust a level on the direction of top-bottom by adjusting supension bolts. Then the unit will be inclined to the bottomside so as to drain well.
: Tighten the nut and bolt to prevent unit falling.
Spring washer Hangen
Nut
Max. 12mm
Washer
Hanging bolt (W3/8 or M10) Nut (W3/8 or M10)
Flat washer for M10 (accessory)
Flat washer for M10 (accessory) Nut (W3/8 or M10)
DRILL A HOLE IN THE WALL.
WALL Indoor
Outdoor
28 _ Ceiling & Floor / Ceiling Suspended
(3/16"~5/16")
• Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
5-7mm
Indoor Units
• Mount the suspension bolts to the anchor-nuts firmly.
Anchor nut
10. Installation 10.11 Indoor unit installation Hang the Indoor unit on suspension bolt as per following guidelines: 1. Lift the indoor unit to sufficient height. 2. Insert the suspended part of four suspension bolt in the four hangers provided on the side of main body one by one. 3. Lower the indoor unit till the hangers rest on their respective flat washer. 4. Adjust the level in the top down direction by adjusting the suspension bolts. Inclined the indoor unit as per direction provided in the fig
: Installation Information For Declination
1. Inclination of the indoor unit is very important for drain purposes in the convertible type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 10mm.
Front of view • The unit must be horizontal or inclined at angle. • The inclination should be less than or equal to 1° or in between 10 to 20mm inclined in drain direction as shown in fig. Ceiling 10~20mm
Side of view • The unit must be inclined to the bottomside of the unit when finished installation. Ceiling
Ceiling & Floor / Ceiling Suspended _ 29
Indoor Units
3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.
10. Installation 10.12 Checking the Drainage 1. Set the air direction louvers up-and-down to the position(horizontally) by hand.
To check the drainage. 1. Pour a glass of water on the evaporator using a kettle.
Indoor Units
2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
Drain piping Downward slope
1. The drain hose should point downward for easy drain flow.
2. Do not make drain piping like the following. Accumulated drain water Air
Do not raise
Water leakage
Water leakage
Waving
30 _ Ceiling & Floor / Ceiling Suspended
Tip of drain hose dipped in water
Water leakage
Ditch
Less than 50mm gap
10. Installation 10.13 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU B
IDU B
SODU A
IDU A
INT B
INT A
4
[Except Multi VIII Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU
4
B
A
INTERNET DRY1 DRY2 GND 12V
IDU -
-
B
A
-
-
-
-
Outdoor Unit
INDOOR POWER INPUT
WARNING : Make sure that the screws of the terminal are free from looseness.
Ceiling & Floor / Ceiling Suspended _ 31
Indoor Units
INDOOR POWER INPUT
10. Installation CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have a separate power circuit specially for the air conditioner. As for the method of wiring, follow the circuit diagram posted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source 5) Confirm that electrical capacity is sufficient.
Indoor Units
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal function of an overload protection device. • Proper starting power is not given to the compressor.
32 _ Ceiling & Floor / Ceiling Suspended
10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
Indoor Units
TEMP
yes
Remote Controller
no
TEMP
Controller Remote
TEMP
Remote Controller
5feet (1.5meters)
no
no
Fig.1 Typical locations for remote controller
Ceiling & Floor / Ceiling Suspended _ 33
11. Accessories Standard Accessories Name
Installation plate
Type "A" screw and plastic anchor
Quantity
1EA
4EA
(Other)
• Owner's manual • Installation manual
Indoor Units
Shape
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
34 _ Ceiling & Floor / Ceiling Suspended
Indoor unit Floor Standing 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of functions Category
Air flow
Air purifying
Reliability
Convenience
Individual control
Special function kit
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Floor Standing _ 1
Indoor Units
Installation
Function
ARNU07GCEA2, ARNU09GCEA2, ARNU12GCEA2 ARNU15GCEA2, ARNU18GCFA2, ARNU24GCFA2 ARNU07GCEU2, ARNU09GCEU2, ARNU12GCEU2 ARNU15GCEU2, ARNU18GCFU2, ARNU24GCFU2 1 3/3/3 X X O X O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O X O O O Accessory Accessory Accessory Accessory X Accessory -
2. Specification Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Dimensions(WxDxH) Body
Indoor Units
Coil
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
mm inch m3 W A CMM cfm
Drive Motor type Temperature Control
Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable
Ø, V, Hz mm2 mm2
Floor Standing ARNU07GCEA2 ARNU09GCEA2 2.2 2.8 1,900 2,400 7,500 9,600 2.5 3.2 2,200 2,800 8,500 10,900 Galvanized Galvanized Steel Plate Steel Plate 1,067 x 203 x 635 1,067 x 203 x 635 42.2 x 8.0 x 25.0 42.2 x 8.0 x 25.0 2 x 12 x 19 2 x 12 x 19 0.16 0.16 Sirocco Fan Sirocco Fan 28 28 0.15 0.15 8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 300 / 265 / 229 335 / 300 / 265 Direct Direct BLDC BLDC Microprocessor, Microprocessor, Thermostat for Thermostat for cooling and heating cooling and heating Foamed polystrene Foamed polystrene Resin Net(washable) Resin Net(washable) Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 12(15/32) 12(15/32) 27(59.5) 27(59.5) 35 / 33 / 31 36 / 34 / 32 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
2 _ Floor Standing
ARNU12GCEA2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 1,067 x 203 x 635 42.2 x 8.0 x 25.0 2 x 12 x 19 0.16 Sirocco Fan 28 0.15 10.5 / 9.5 / 8.5 371 / 335 / 300 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12(15/32) 27(59.5) 37 / 35 / 33 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specification Type Model Cooling Capacity
Heating Capacity
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Casing Dimensions(WxDxH) Body Coil
m3 W A CMM cfm
Drive Motor type Temperature Control
Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable
Ø, V, Hz mm2 mm2
Floor Standing ARNU09GCEU2 2.8 2,400 9,600 3.2 2,800 10,900 Galvanized Steel Plate 978 x 190 x 639 38.5 x 7.5 x 25.2 2 x 12 x 19 0.16 Sirocco Fan 28 0.15 9.5 / 8.5 / 7.5 335 / 300 / 265 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12(15/32) 20(44.1) 36 / 34 / 32 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
ARNU12GCEU2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 978 x 190 x 639 38.5 x 7.5 x 25.2 2 x 12 x 19 0.16 Sirocco Fan 28 0.15 10.5 / 9.5 / 8.5 371 / 335 / 300 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12(15/32) 20(44.1) 37 / 35 / 33 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Floor Standing _ 3
Indoor Units
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)
mm inch
ARNU07GCEU2 2.2 1,900 7,500 2.5 2,200 8,500 Galvanized Steel Plate 978 x 190 x 639 38.5 x 7.5 x 25.2 2 x 12 x 19 0.16 Sirocco Fan 28 0.15 8.5 / 7.5 / 6.5 300 / 265 / 229 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Resin Net(washable) Fuse Ø6.35(1/4) Ø12.7(1/2) 12(15/32) 20(44.1) 35 / 33 / 31 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C
2. Specification
Indoor Units
Type Model
Floor Standing ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2 4.5 5.6 7.1 Cooling Capacity 3,900 4,800 6,100 15,400 19,100 24,200 5.0 6.3 8.0 Heating Capacity 4,300 5,400 6,900 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 1,067 x 203 x 635 1,345 x 203 x 635 1,345 x 203 x 635 Dimensions(WxDxH) Body inch 42.2 x 8.0 x 25.0 52.9 x 8.0 x 25.0 52.9 x 8.0 x 25.0 Rows x Columns x FPI 2 x 12 x 19 3 x 11 x 19 3 x 11 x 19 Coil Face Area m3 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 28 76 76 Running Current A 0.15 0.38 0.38 Fan Air Flow Rate(H / M / L) CMM 11.5 / 10.0 / 9.5 16.0 / 14.0 / 12.0 18.0 / 16.0 / 14.0 cfm 406 / 353 / 335 565 / 494 / 424 635 / 565 / 494 Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat Microprocessor, Thermostat Microprocessor, Thermostat for cooling and heating for cooling and heating for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Resin Net(washable) Resin Net(washable) Resin Net(washable) Safety Device Fuse Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 12(15/32) 12(15/32) 12(15/32) Net Weight kg(lbs) 27(59.5) 34(75.0) 34(75.0) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) 38 / 37 / 35 40 / 37 / 34 43 / 40 / 37 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Unit kW kcal/h Btu/h kW kcal/h Btu/h
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
4 _ Floor Standing
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specification Type Model
Floor Standing ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2 4.5 5.6 7.1 Cooling Capacity 3,900 4,800 6,100 15,400 19,100 24,200 5.0 6.3 8.0 Heating Capacity 4,300 5,400 6,900 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 978 x 190 x 639 1,256 x 190 x 639 1,256 x 190 x 639 Dimensions(WxDxH) Body inch 38.5 x 7.5 x 25.2 49.5 x 7.5 x 25.2 49.5 x 7.5 x 25.2 Rows x Columns x FPI 2 x 12 x 19 3 x 11 x 19 3 x 11 x 19 Coil Face Area m3 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 28 76 76 Running Current A 0.15 0.38 0.38 Fan Air Flow Rate(H / M / L) CMM 11.5 / 10.0 / 9.5 16.0 / 14.0 / 12.0 18.0 / 16.0 / 14.0 cfm 406 / 353 / 335 565 / 494 / 424 635 / 565 / 494 Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat Microprocessor, Thermostat Microprocessor, Thermostat for cooling and heating for cooling and heating for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Resin Net(washable) Resin Net(washable) Resin Net(washable) Safety Device Fuse Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 12(15/32) 12(15/32) 12(15/32) Net Weight kg(lbs) 20(44.1) 27(59.5) 27(59.5) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) 38 / 37 / 35 40 / 37 / 34 43 / 40 / 37 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Unit kW kcal/h Btu/h kW kcal/h Btu/h
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Floor Standing _ 5
Indoor Units
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
148.3
<Without Case>
978 794
<With Case> 2
1067
1067
13
148.3
1
635 70 20.4
6 _ Floor Standing 62.8
190 161
203
14
Air discharge grill Air suction grill
1 2
639
635
H
Descripition
(unit : mm)
190
203
D
(unit : mm)
ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
CHASSIS CODE: CE
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Name
Number
978
ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2
W 1067
Model
ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2
Floor Standing
ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2
Indoor Units
3. Dimensions
49
639
Floor Standing _ 7
148.3
70
21.4
639
<Without Case>
1256 1098 1072
<With Case>
1048.4
2
203 635 109.8 30
148.3
70 81.4
1345
1
190 161
203
14
Air discharge grill Air suction grill
1 2
639
635
H
Descripition
(unit : mm)
190
203
D
(unit : mm)
ARNU18GCFU2 ARNU24GCFU2
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
CHASSIS CODE: CF
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Name
Number
1256
1345
ARNU18GCFA2 ARNU24GCFA2 ARNU18GCFU2 ARNU24GCFU2
W
ARNU18GCFA2 ARNU24GCFA2
Model
Indoor Units
145
49.4
Floor Standing
3. Dimensions
4. Piping Diagrams
Heat Exchanger
EEV Th2
Th3 Sirroco Fan
Th1
Indoor Units
Filter
:Cooling :Heating
Filter
lndoor unit
Refrigerant pipe connection port diameter [Unit: mm(inch)]
Model ARNU07GCEA2 ARNU07GCEU2 ARNU09GCEA2 ARNU09GCEU2 ARNU12GCEA2 ARNU12GCEU2 ARNU15GCEA2 ARNU15GCEU2 ARNU18GCFA2 ARNU18GCFU2 ARNU24GCFA2 ARNU24GCFU2
8 _ Floor Standing
Gas
Liquid
Ø12.7(1/2)
Ø6.35(1/4)
Ø12.7(1/2)
Ø6.35(1/4)
Ø12.7(1/2)
Ø6.35(1/4)
Ø12.7(1/2)
Ø6.35(1/4)
Ø12.7(1/2)
Ø6.35(1/4)
Ø15.88(5/8)
Ø9.52(3/8)
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
5. Wiring Diagrams CE/CF Chassis
CN-POWER CN-MOTOR1 CN-MOTOR2 CN-COMM CN-EEV CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-OPTION CN-ZONE CN-DISPLAY CN-CC
LOCATION POINT
FUNCTION
AC power supply Fan motor output Fan motor output Communication Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Option PCB Zone controller RF Remote controller Dry contact
AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC Communication between indoor and outdoor EEV Control output Pipe in thermistor Pipe out thermistor Room thermistor Remote control line Communication between main and option Zone control line RF Remote control line Dry contact line
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory â&#x2020;&#x2019; Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
Floor Standing _ 9
Indoor Units
CONNECTOR NUMBER
6. Capacity Tables 6.1 Cooling Capacity
Capacity Index
Indoor Units
2.2
2.8
3.6
Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
Notes: TC: Total Capacity(kW)
10 _ Floor Standing
Cooling capacity
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
SHC: Sensible Heat Capacity(kW)
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5 1.5 1.5 1.5 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 1.9 1.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.7 2.7 2.6 2.6 2.5 2.5
32 24 TC SHC kW kW 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8
1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3
6. Capacity Tables Cooling capacity
Capacity Index
4.5
7.1
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
30 22 TC SHC kW kW
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8
3.6 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2
4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.0
6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4
4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.8 3.8 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 5.2 5.1 5.0 4.9 4.8 4.7
7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6
4.3 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 5.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5 4.4 4.4
Notes: TC: Total Capacity(kW)
32 24 TC SHC kW kW
SHC: Sensible Heat Capacity(kW)
Floor Standing _ 11
Indoor Units
5.6
20 14 TC SHC kW kW
Outdoor air temp. (DB, °C)
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Heating capacity Indoor air temp. (DB, °C)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
2.2
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7
1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
2.8
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
3.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6
2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3
2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0
2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Indoor Units
kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Notes: TC: Total Capacity(kW) Capacity
12 _ Floor Standing
6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
4.5
7.1
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2 5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2
3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7 5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6
3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3 5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0
3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Notes: TC: Total Capacity(kW)
Floor Standing _ 13
Indoor Units
5.6
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Indoor air temp. (DB, °C)
7. Air velocity and Temperature Distribution(Reference Data) ARNU07GCEA2 /ARNU07GCEU2 Cooling
Heating
Discharge angle:45°
Discharge angle:60° Air velocity [m/s] 22
2.7m
24
24 3028
26
2.7m
3 0 32
26 32
20
21
2248
23
21 22
21
23
34
Air velocity [m/s]
23 20
2m
30
36 38
22
2m
26
19 19 36 34
22
18
1m
18
1m
28
23
1156
21
26
22
8m
7m
6m
24
23
23
0
5m
4m
3m
2m
1m
0
8m
24
7m
6m
5m
4m
28
26
3m
2m
24
0
Temperature [°C]
Temperature [°C]
1
2m
1.5
2m 5 0.
1
Indoor Units
2.7m
0.5
2.7m
0.5 0.5
5 0 .2 1.5 1
5 0.
1 0.5
1m
3
2
0.5 2
8m
7m
0
1m
6m
5m
4m
3m
2m
1m
0 0
141.5
8m
7m
6m
5m
4m
3m
2m
1m
1m
0
0
ARNU09GCEA2 /ARNU09GCEU2 Cooling
Heating
Discharge angle:45°
Discharge angle:60°
Air velocity [m/s]
Air velocity [m/s] 2.7m
19
2624
2624
83
82
21
2.7m
84
2m
24
86
83
2m
83 80
82
22 21 20
22 21
20 22
20
02 0 8 84
1m 26
22
24
0 8m
7m
6m
5m
4m
3m
2m
1m
0
8m
Temperature [°C]
7m
6m
26
24
5m
1m
83
17 19 21 16
24
8 22 1
18
26
03
22
21
4m
3m
0 2m
1m
0
Temperature [°C] 0.5
2.7m
1
3.5
0.5
2.7m
3.5 1
2m
5 1.
0.5
1.5
2m 1
2
1m
2.5
1m
1
2
7m
6m
5m
14 _ Floor Standing
4m
3m
2m
1m
0
1.5
3.5
8m
3.5
0.5
0 8m
7m
6m
5m
4m
3m
2m
1m
0 0
7. Air velocity and Temperature Distribution(Reference Data) ARNU12GCEA2 /ARNU12GCEU2 Cooling
Heating
Discharge angle:45°
Discharge angle:60°
Air velocity [m/s]
26
83
86
80
2m
84
22
24
82 80
20
18
21
83 26
82
24 24
21
2.7m
19 22
20
26
Air velocity [m/s] 21
22
83
2.7m 2m
21 20 5 22 1 21 16
1m
22
22
6m
5m
4m
3m
2m
1m
0
8m
Temperature [°C]
7m
6m
5m
26
24
4m
0 3m
2m
1m
0
Temperature [°C] 1
2.7m
3.5
2.7m
0.5
2m
2
2m
1
1. 5
1 .5 3
1
1m
0. 5
1m
2.5 1.5
0.5
2.5 1.5 .5 1
1
5 3.
1.5
0 8m
7m
6m
5m
4m
3m
2m
1m
8m
0
7m
6m
5m
4m
3m
2m
1m
0
0
ARNU15GCEA2 /ARNU15GCEU2 Cooling
Heating
Discharge angle:45°
Discharge angle:60°
Air velocity [m/s]
Air velocity [m/s] 20
2.7m
21
3230
28 30
1m 34
28
28
0 5m
4m
3m
2m
1m
32
16
21
6m
2m
34
40
8 15 21 1
18 20
21
7m
2.7m
19
17
38
30
2m
21
8m
32
3436
20
19
30 28
21
1m
0
8m
Temperature [°C]
7m
6m
5m
4m
28
3m
2m
0
1m
0
Temperature [°C] 1
2.7m
0.5 0.5
1.0
0.5
2.7m
0.5
2m
1
1. 5
0.5
0.5 5 0.
2m
1.0
1 2
1. 5
1m
1m
2.0
3. 5
5 2.
2
7m
6m
5m
4m
3m
2m
1m
0 0
1.0
11.5 2
8m
0.5
3
4
0 8m
7m
6m
5m
4m
3m
2m
1m
0
Floor Standing _ 15
Indoor Units
0.5
0.5
3.5
7m
26
24
0 8m
1m
84 02 82
19
03
83
17
7. Air velocity and Temperature Distribution(Reference Data) ARNU18GCFA2 /ARNU18GCFU2 Cooling
Heating
Discharge angle:45°
Discharge angle:60°
Air velocity [m/s]
Air velocity [m/s]
22
20
30
32 34 32
30
32
2m
2m
36
20
38 4 2
22
40
32
16
1m
1m 30
18
30
7m
30
22
22
8m
2.7m
34
38
20
2.7m
22
18
30
20
36
22
20
0
0 6m
5m
4m
3m
2m
1m
8m
0
Temperature [°C]
7m
6m
5m
4m
3m
2m
1m
0
Indoor Units
Temperature [°C] 2.7m
1.0
2.7m
0.5
1.0
0.5
1.0 2.0
0. 5
2m
2m 0 2. 0.5
1.0
1.0
1m
1m 1.0
3. 0
2.
8m
7m
6m
5m
4m
3m
2m
1m
0
0 8m
0
7m
6m
5m
4m
3m
2m
1m
0
ARNU24GCFA2/ARNU24GCFU2 Cooling
Heating
Discharge angle:45°
Discharge angle:60°
Air velocity [m/s]
Air velocity [m/s] 20
20
30
34
32
30
32
38
2.7m
36
2.7m 18
2m
34
30
2m
36
20
32
32
34
40
20 20
18
32
30
1m 20
7m
6m
5m
4m
3m
2m
1m
0
30
30
0 8m
1m
0 8m
Temperature [°C]
7m
6m
5m
4m
3m
2m
1m
0
Temperature [°C] 2.7m
1.0
0.5
1.0
2.7m
0.5
1.0
0.5 2. 0
2m
2m
0 3.
1m
1.0
1m
2. 0
2.0
3.0
1.0
5 0.
0 1.
1.0
2.0
0 2.
0.
0 8m
7m
6m
5m
16 _ Floor Standing
4m
3m
2m
1m
0
8m
7m
6m
5m
4m
3m
2m
1m
40
0
0
8. Electric Characteristics Units Model
Hz
Volts Voltage Range MCA
CE CE CE
MAX.264 50
220-240
60
220
MIN.198
CE CF CF CE CE CE
MAX.242 MIN.198
CE CF CF
0.22 0.22 0.22 0.22 0.22 0.22 0.22 0.22 0.55 0.55 0.55 0.55 0.22 0.22 0.22 0.22 0.22 0.22 0.22 0.22 0.55 0.55 0.55 0.55
IFM
Input(W)
MFA
kW
FLA
15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.076 0.076 0.076 0.076 0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.028 0.076 0.076 0.076 0.076
0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.44 0.44 0.44 0.44 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.44 0.44 0.44 0.44
Cooling Heating 30 30 30 30 30 30 30 30 80 80 80 80 30 30 30 30 30 30 30 30 80 80 80 80
30 30 30 30 30 30 30 30 80 80 80 80 30 30 30 30 30 30 30 30 80 80 80 80
Symbols: MCA: Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA â&#x2030;¤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the MCA. 5. Instead of fuse, use Circuit Breaker.
Floor Standing _ 17
Indoor Units
ARNU07GCEA2 ARNU07GCEU2 ARNU09GCEA2 ARNU09GCEU2 ARNU12GCEA2 ARNU12GCEU2 ARNU15GCEA2 ARNU15GCEU2 ARNU18GCFA2 ARNU18GCFU2 ARNU24GCFA2 ARNU24GCFU2 ARNU07GCEA2 ARNU07GCEU2 ARNU09GCEA2 ARNU09GCEU2 ARNU12GCEA2 ARNU12GCEU2 ARNU15GCEA2 ARNU15GCEU2 ARNU18GCFA2 ARNU18GCFU2 ARNU24GCFA2 ARNU24GCFU2
Type
Power Supply
9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
Microphone
With Case
1.5m
E
Du
1.5m Model ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2
Sound Levels dB(A) H L M 35 33 31 36 34 32 37 35 33 38 37 35 40 37 34 43 40 37
Sound Pressure Level ARNU07GCEA2 ARNU07GCEU2
ARNU09GCEA2 ARNU09GCEU2 70
NC-65 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30
20
10
NC-25 Approximate Hearing Threshold 63
125
250
500
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20 NC-15 1000 2000 4000 8000
10
63
NC-60
250
500
NC-50
NC-40
NC-30
NC-15 1000 2000 4000 8000
10
NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25
63
NC-60
125
250
500
Octave Band Center Frequency (Hz)
18 _ Floor Standing
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20 NC-15 1000 2000 4000 8000
NC-65
60
10
NC-25 Approximate Hearing Threshold 63
Octave Band Sound Pressure Level (dB re 20μPa )
70
Octave Band Sound Pressure Level (dB re 20μPa )
70
10
125
250
500
1000
2000
4000
500
1000 2000
NC-15 4000 8000
NC-15 8000
Octave Band Center Frequency (Hz)
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20
125
250
ARNU24GCFA2 ARNU24GCFU2
ARNU18GCFA2 ARNU18GCFU2
70
Approximate Hearing Threshold
NC-20
Octave Band Center Frequency (Hz)
80
20
NC-25 Approximate Hearing Threshold 63
80
30
NC-35
30
80
40
NC-45
40
Octave Band Center Frequency (Hz)
ARNU15GCEA2 ARNU15GCEU2
50
NC-55
50
NC-20
125
NC-65
60
20
NC-25 Approximate Hearing Threshold
Octave Band Center Frequency (Hz)
60
ARNU12GCEA2 ARNU12GCEU2
80
Octave Band Sound Pressure Level (dB re 20μPa )
70
Octave Band Sound Pressure Level (dB re 20μPa )
80
Octave Band Sound Pressure Level (dB re 20μPa )
80
60
Octave Band Sound Pressure Level (dB re 20μPa )
Indoor Units
ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2
(Fie
10
NC-25 Approximate Hearing Threshold 63
NC-20
125
250
500
1000
2000
4000
NC-15 8000
Octave Band Center Frequency (Hz)
10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
10.1 Features
[CEA/CFA Type]
Control panel
Air Outlet Remote Controller Control panel TEMP
Remote Controller
Indoor Units
Air Filter Air Inlet
[CEU/CFU Type]
Air Inlet Air filter (At Air Inlet)
Floor Standing _ 19
10. Installation 10.2 Selection of the best location Indoor unit Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unitʼs weight. • Sufficient space should be available to inspect the unit as in the figure shown on the right.
Window
• The place where the unit is installed shall be leveled. • The place shall be suitable for easy connection of the indoor unit with the outdoor unit.
• The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit
Service space Select an installation site where the following conditions are satisfied and that meets your customer's approval. • Where the floor is strong enough to bear the indoor unit weight. • Where the floor is not significantly inclined. • Where nothing blocks the air passage.
20 or more
Air flow direction Front side
100 or more
175 or more
100 or more
1000 or more
Air inlet direction
• Where condensate can be properly drained. Base
• Where sufficient clearance for installation and maintenance can be ensured. • Where there is no possibility of flammable gas leakage. • Where optimum air distribution can be ensured. • Where piping between indoor and outdoor units is possible within the allowable limit (Refer to the installation manual of the outdoor unit.) 80 or more
• Keep the indoor and outdoor unit, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static.(Depending on the type and source of the electrical waves, static may be heard even when more than 1 m away.)
Window
654
Indoor Units
• The place where the unit is installed should not be affected by electrical noise.
Ma
Ao
(Unit: mm) Type
A
B
CEU Type
788
1080
CFU Type
1066
1358
20 _ Floor Standing
inte
[IMPORTANT] Leave sufficient clearance for air inlet and maintenance.
nan
ce
are
rm ore Bo rm ore
a
10. Installation Bolt pitch A
• Positioning of holes for fastening to the wall
A
CEA, CEU CFA, CFU
858 1136
Indoor Units
1. Use the Installation mount for installation. Check whether the wall is strong enough to bear the weight of the unit or not. if there is a risk, reinforce the wall before installing the unit. 2. The unit requires a minimum 100 mm clearance below the unit for air intake. Also, ensure the unit is leveled when installed so that drainage flows smoothly. If inclined, water can leak. 3. Depending upon the shape and nature of the wall surface, operating sound may become bigger.
270
Type
198
(Unit:mm)
How to open/close front panel
(1)
• How to open/close the front panel
(2)
(1) Open the lid of control panel(Both left and right) (2) Remove screws(Both left and right) (3) Lift the front panel of the unit • To close, perform the procedure in opposite order.
(3)
(2)
(1)
Floor Standing _ 21
10. Installation 10.3 Drain piping work • Drain piping must have downward slope(1/50 to 1/100): be sure not to provide up-and-down slope to prevent reverse flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection to the indoor unit is 21mm. Piping material: Polyvinyl chloride pipe 25mm and pipe fittings • Be sure to install heat insulation on the drain piping
Indoor Units
Heat insulation material: Polyethylene foam with thickness more than 10 mm. • If converging multiple drain pipes, install according to the procedure shown below.
Slope downwards at a gradient of at least 1/100 • After piping work is finished, check for drainage. • Be sure to insulate all indoor units.
10.4 How to connect wirings Remove the electric parts Box cover and connect the wiring
Fasten with clamp
Fasten with accessory clamp
Power Supply wiring ground wiring (Field wiring)
22 _ Floor Standing
Power supply wiring ground wiring Transmission wiring (Field wiring)
Transmission wiring
10. Installation 10.5 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. â&#x20AC;˘ Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model]
Terminal Block Indoor 1(L)
2(N)
3
SODU B
SODU A
IDU B
IDU A
INT B
INT A
4
INDOOR POWER INPUT
[Except Multi VIII Heat Pump Model]
1(L)
2(N)
3
SODU
4
B
A
INTERNET DRY1 DRY2 GND 12V
IDU -
-
B
A
-
-
-
-
Outdoor Unit
INDOOR POWER INPUT
WARNING : Make sure that the screws of the terminal are free from looseness. CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have a separate power circuit specifically for the air conditioner. As for the method of wiring, follow the circuit diagram posted on the inside of control cover. 2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3) Specification of power source. 4) Confirm that electrical capacity is sufficient. 5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness.) 7) In a wet or moist area, always install an earth leakage circuit breaker. 8) The following would be caused by voltage drop. â&#x20AC;˘ Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductor.
Floor Standing _ 23
Indoor Units
Terminal Block Indoor
10. Installations WIRED REMOTE CONTROLLER INSTALLATION â&#x20AC;˘ Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys.
Indoor Units
- Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
TEMP
yes
Remote Controller
no
TEMP
Controller Remote
TEMP
Remote Controller
5feet (1.5meters)
no
no
Fig.1 Typical locations for remote controller
24 _ Floor Standing
11. Accessories Standard Accessories Name
Dran hose
Level adjustment screw
Insulation for fitting
Clamp (Tie Wrap)
Quantity
1 EA
4
1 each.
8 pcs.
(1) For gas pipe Shape
[Other]
• Operation manual • Installation manual
(2) For liquid pipe
Indoor Units
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
Floor Standing _ 25
Indoor unit Console 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories
1. List of functions Category
Air flow
Air purifying
Reliability
Convenience
Individual control
Special function kit
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Ion Generator Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU07GQAA2, ARNU09GQAA2, ARNU12GQAA2 ARNU15GQAA2 2 Manual Auto X O 4/5/4 X O O X X O O X X X X O O O O X O O O O O O O O O Accessory X X X X Accessory X X X
Indoor Units
Installation
Function
O : Applied X : Not applied â&#x20AC;&#x201C; : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Console _ 1
2. Specification Type Model Cooling Capacity
Heating Capacity
Casing Dimensions (W x D x H)
Body Front Panel
Coil
Indoor Units
Fan
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)
Console Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch mm inch m3 W A CMM cfm
Drive Motor type Temperature Control
Sound Absorbing Thermal Insulation Material Safety Device Pipe Liquid Side mm(inch) Connections Gas Side mm(inch) Drain(OD/ID) mm Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Ø, V, Hz Refrigerant Control Power cable mm2(CV) Transmission Cable mm2(VCTF-SB)
ARNU07GQAA2 2.2 1,900 7,500 2.5 2,200 8,500 Galvanized Steel Plate 600 x 700 x 210 23.62 x 27.56 x 8.27 19 x 2 x 19 Turbo fan 48 x 1 0.3 6.7 / 5.9 / 4.8 236 / 209 / 170 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 17/12.2 14.0(30.9) 37 / 34 / 28 1, 220 - 240, 50 EEV 1.5 x 3C 1.0 ~ 1.5 x 2C
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
2 _ Console
ARNU09GQAA2 2.8 2,400 9,600 3.2 2,800 10,900 Galvanized Steel Plate 600 x 700 x 210 23.62 x 27.56 x 8.27 19 x 2 x 19 Turbo fan 48 x 1 0.3 6.7 / 5.9 / 4.8 236 / 209 / 170 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 17/12.2 14.0(30.9) 37 / 34 / 28 1, 220 - 240, 50 EEV 1.5 x 3C 1.0 ~ 1.5 x 2C Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
2. Specification Type Model Cooling Capacity
Heating Capacity
Casing Dimensions (W x D x H)
Body Front Panel
Coil Fan
mm inch mm inch m3 W A CMM cfm
Drive Motor type Temperature Control
Sound Absorbing Thermal Insulation Material Safety Device Pipe Liquid Side mm(inch) Connections Gas Side mm(inch) Drain(OD/ID) mm Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) Power Supply Ø, V, Hz Refrigerant Control Power cable mm2(CV) Transmission Cable mm2(VCTF-SB)
ARNU12GQAA2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 600 x 700 x 210 23.62 x 27.56 x 8.27 19 x 2 x 19 Turbo fan 48 x 1 0.3 7.5 / 5.9 / 4.8 265 / 209 / 170 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 17/12.2 14.0(30.9) 39 / 34 / 28 1, 220 - 240, 50 EEV 1.5 x 3C 1.0 ~ 1.5 x 2C
Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.
ARNU15GQAA2 4.5 3,900 15,400 5.0 4,300 17,100 Galvanized Steel Plate 600 x 700 x 210 23.62 x 27.56 x 8.37 19 x 2 x 19 Turbo fan 48 x 1 0.3 8.7 / 6.7 / 5.9 307 / 236 / 209 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 17/12.2 14.0(30.9) 42 / 37 / 31 1, 220 - 240, 50 EEV 1.5 x 3C 1.0 ~ 1.5 x 2C Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Console _ 3
Indoor Units
Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H/M/L)
Console Unit kW kcal/h Btu/h kW kcal/h Btu/h
82.5
18
95
6
160
4 _ Console 600 80 37 100
639
700
666
3
68.5 37
1
6
5
4
150
2
No. 1 2 3 4 5 6
Indoor Units
Part Name Liquid pipe connection Gas pipe connection Drain pipe connection Display & signal receiver Air discharge grill Air suction grill
CHASSIS CODE: QA
Remark Ø6.35 Ø12.7
ARNU07GQAA2 ARNU09GQAA2 ARNU12GQAA2 ARNU15GQAA2
Console
3. Dimensions
140 120
45
210
80
90
125
584
4. Piping Diagrams
Heat Exchanger
:Cooling :Heating
EEV Filter
Th3
Th2 Turbo Fan
Filter
lndoor unit
Th1
[Unit: mm(inch)]
Model
Gas
Liquid
ARNU07GQAA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU09GQAA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU12GQAA2
Ø12.7(1/2)
Ø6.35(1/4)
ARNU15GQAA2
Ø12.7(1/2)
Ø6.35(1/4)
LOC.
Description
Th1
Room thermistor
Th2
Pipe in thermistor
Th3
Pipe out thermistor
Console _ 5
Indoor Units
Refrigerant pipe connection port diameter
5. Wiring Diagrams
Indoor Units
QA Chassis
CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC
LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean
Dip Switch Setting SW3 GROUP
Off Master
On Slave
SW4
DRY CONTACT
Variable
Auto
SW5
EXTRA 1
Off
On
FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory â&#x2020;&#x2019; Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor
CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.
6 _ Console
6. Capacity Tables 6.1 Cooling Capacity
Capacity Index
2.8
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
10
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.6
1.5
2.8
1.6
12
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.6
1.5
2.8
1.6
14
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.6
1.5
2.8
1.6
16
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.6
1.5
2.7
1.6
18
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.6
1.5
2.7
1.6
20
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.6
1.5
2.7
1.6
21
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.6
1.5
2.7
1.6
23
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.5
1.5
2.6
1.5
25
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.5
1.5
2.6
1.5
27
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.5
1.5
2.6
1.5
29
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.5
1.4
2.5
1.5
31
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.4
1.4
2.5
1.4
33
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.4
1.4
2.4
1.4
35
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.3
1.6
2.4
1.4
2.4
1.4
37
1.5
1.3
1.8
1.4
2.1
1.6
2.2
1.6
2.2
1.6
2.3
1.4
2.4
1.4
39
1.5
1.3
1.8
1.4
2.1
1.6
2.1
1.5
2.2
1.5
2.3
1.3
2.3
1.4
42
1.5
1.3
1.8
1.4
2.1
1.6
2.1
1.5
2.2
1.5
2.2
1.3
2.3
1.3
44
1.5
1.3
1.8
1.4
2.0
1.5
2.1
1.5
2.1
1.5
2.2
1.3
2.2
1.3
46
1.5
1.3
1.8
1.4
1.9
1.5
2.0
1.4
2.0
1.4
2.0
1.2
2.0
1.2
10
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.3
1.9
3.6
2.1
12
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.3
1.9
3.6
2.0
14
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.3
1.9
3.5
2.0
16
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.3
1.9
3.5
2.0
18
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.3
1.9
3.5
2.0
20
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.3
1.9
3.4
2.0
21
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.3
1.9
3.4
2.0
23
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.2
1.9
3.3
1.9
25
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.2
1.8
3.3
1.9
27
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.2
1.8
3.3
1.9
29
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
3.0
2.0
3.1
1.8
3.2
1.8
31
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
2.9
2.0
3.1
1.8
3.2
1.8
33
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
2.9
2.0
3.0
1.8
3.1
1.8
35
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
2.9
2.0
3.0
1.7
3.1
1.8
37
1.9
1.6
2.3
1.8
2.6
2.0
2.8
2.0
2.8
2.0
2.9
1.7
3.0
1.7
39
1.9
1.6
2.3
1.8
2.6
2.0
2.7
1.9
2.8
1.9
2.9
1.7
3.0
1.7
42
1.9
1.6
2.3
1.8
2.6
2.0
2.7
1.9
2.8
1.9
2.8
1.6
2.9
1.7
44
1.9
1.6
2.3
1.8
2.6
1.9
2.7
1.9
2.7
1.9
2.8
1.6
2.9
1.6
46
1.9
1.6
2.3
1.8
2.5
1.8
2.5
1.8
2.5
1.7
2.6
1.5
2.6
1.5
Outdoor air temp. (DB, °C)
Notes: TC: Total Capacity(kW)
30 22 TC SHC kW kW
32 24 TC SHC kW kW
SHC: Sensible Heat Capacity(kW)
Console _ 7
Indoor Units
2.2
Cooling capacity
6. Capacity Tables Cooling capacity
Indoor Units
Capacity Index
3.6
4.5
20 14 TC SHC kW kW
23 16 TC SHC kW kW
Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW
10
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.3
2.5
4.6
2.7
12
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.3
2.5
4.6
2.7
14
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.3
2.5
4.5
2.6
16
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.3
2.5
4.5
2.6
18
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.3
2.5
4.4
2.6
20
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.2
2.5
4.4
2.6
21
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.2
2.4
4.4
2.5
23
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.1
2.4
4.3
2.5
25
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.1
2.4
4.2
2.5
27
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.1
2.4
4.2
2.4
29
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.7
4.0
2.3
4.1
2.4
31
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.8
2.6
4.0
2.3
4.1
2.4
33
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.7
2.6
3.9
2.3
4.0
2.3
35
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.7
2.6
3.9
2.2
3.9
2.3
37
2.4
2.1
2.9
2.4
3.4
2.6
3.6
2.6
3.7
2.5
3.8
2.2
3.9
2.3
39
2.4
2.1
2.9
2.4
3.4
2.6
3.5
2.5
3.6
2.5
3.7
2.2
3.8
2.2
42
2.4
2.1
2.9
2.4
3.4
2.5
3.5
2.5
3.5
2.5
3.6
2.1
3.7
2.2
44
2.4
2.1
2.9
2.4
3.3
2.5
3.4
2.5
3.5
2.4
3.6
2.1
3.7
2.1
46
2.4
2.1
2.9
2.4
3.2
2.4
3.2
2.3
3.3
2.3
3.3
1.9
3.3
1.9
10
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.4
3.1
5.8
3.4
12
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.4
3.1
5.7
3.3
14
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.4
3.1
5.7
3.3
16
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.4
3.1
5.6
3.3
18
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.3
3.1
5.6
3.2
20
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.3
3.1
5.5
3.2
21
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.2
3.1
5.5
3.2
23
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.2
3.0
5.4
3.1
25
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.1
3.0
5.3
3.1
27
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.1
3.0
5.2
3.1
29
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.8
3.3
5.0
2.9
5.2
3.0
31
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.7
3.3
5.0
2.9
5.1
3.0
33
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.7
3.3
4.9
2.9
5.0
2.9
35
3.0
2.7
3.6
2.9
4.2
3.2
4.5
3.2
4.6
3.2
4.8
2.8
4.9
2.9
37
3.0
2.7
3.6
2.9
4.2
3.2
4.4
3.2
4.6
3.2
4.7
2.8
4.8
2.8
39
3.0
2.7
3.6
2.9
4.2
3.2
4.4
3.2
4.5
3.1
4.7
2.7
4.8
2.8
42
3.0
2.7
3.6
2.9
4.2
3.2
4.3
3.1
4.4
3.1
4.5
2.7
4.7
2.7
44
3.0
2.7
3.6
2.9
4.1
3.1
4.3
3.1
4.4
3.0
4.5
2.6
4.6
2.7
46
3.0
2.7
3.6
2.9
4.0
3.0
4.0
2.9
4.1
2.8
4.1
2.4
4.2
2.4
Outdoor air temp. (DB, °C)
Notes: TC: Total Capacity(kW)
8 _ Console
SHC: Sensible Heat Capacity(kW)
30 22 TC SHC kW kW
32 24 TC SHC kW kW
6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
2.2
3.6
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.5 2.5 2.6 2.7 2.8 2.8 2.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.3 3.4 3.5 3.6 3.6 3.6 2.4 2.5 2.6 2.8 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.1 4.2 4.3 4.5 4.5 4.5
1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.5 2.5 2.6 2.7 2.7 2.7 2.7 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.3 3.4 3.4 3.4 3.4 3.4 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.1 4.2 4.3 4.3 4.3 4.3
1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0
1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9
1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.4 2.4 2.6 2.7 2.9 3.0 3.1 3.1 3.3 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Notes: TC: Total Capacity(kW)
Console _ 9
Indoor Units
2.8
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
Heating capacity
6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)
Indoor Units
4.5
-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0
-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7
Notes: TC: Total Capacity(kW)
10 _ Console
Indoor air temp. (DB, °C) 16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
kW
kW
kW
kW
kW
kW
3.0 3.1 3.3 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.7 4.9 5.1 5.3 5.4 5.6 5.6 5.6
3.0 3.1 3.3 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.7 4.9 5.1 5.2 5.3 5.3 5.3 5.3
3.0 3.1 3.3 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0
3.0 3.1 3.2 3.4 3.6 3.8 3.9 3.9 4.1 4.3 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8
3.0 3.1 3.2 3.4 3.6 3.8 3.9 3.9 4.1 4.2 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7
3.0 3.1 3.2 3.4 3.6 3.8 3.8 3.9 4.1 4.2 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
7. Air Velocity and Temperature Distribution(Reference Data) ARNU07GQAA2 Cooling
Heating
Discharge angle:40°
Discharge angle:50°
Air velocity [m/s]
2.7m
Air velocity [m/s]
0.3
0.5
2 0.
0.4
2.7m
0.2
1.0
0.2
0.4
0.1
0.5
0.3
1.0
0.2
0.1
2m 0.3
0.4
2m 0.2
1.0
0.1
0.1
0.3
0. 3
0.5 0.2 0.2 1.0
0.1
1m
3
5m
0.2
0.3
4m
3m
2m
0.2
0.2
0.2
0.3
0.4
0.2
0.2
0.5
1.5
0.2
0
1m
0
Temperature [°C]
5m
2.7m
0.2 0.5
0.
0.1
0.2
0.1
0.3
0.1
1m
1.0
0.1
0.4
0.2
1.5
4m
3m
2m
2.0
0.2
0
1m
0
Temperature [°C]
2.7m
36.7
36.6
36.7
.7
13.4
36
13.4
13.8
13.4
36.7 36.6 36.7
13.8
36.6
13.8
36
.6
36.6
12.2
13
36.7
11.5
13.9
13.8
13.8
36
.4
.7
36
.6
13 .8 11.3
4m
3m
2m
39.0
0 5m
0
1m
36.7
.6
5m
13.4
.8
36
13
13.4
1m
39.0 39.0 6.6 36.6 3
.8
36.6
36.6
1m 13
13.9
4m
3m
2m
0
1m
0
ARNU09GQAA2 Cooling
Heating
Discharge angle:40°
Discharge angle:50°
Air velocity [m/s] 0.3
2.7m
Air velocity [m/s]
2.7m
0.3
0.2
0.3
0. 2
0.3
0.2
0.5 0.5
0.3
0.3
0.2
03 0.3
0.2
0.3
0.2
2 0.
0.3
2.5
0.3
0.2
0.2
0.5
1m
2 0. 0.2
5m
4m
1.5
0.3
0.2
3m
2m
0.2
1m
0
.5 14
0.3
02
5m
2.7m
13.5
13.5
0.2
0
Temperature [°C] 13.9
0.2
0. 2
0.2
0. 2
0.3
0.2
0.2
0.2
0.2
0.2
0.2
4m
3m
2m
0.5
1m
.2
39.2
2.7m
39.9
40.6
40.6
13.5
13.9
0 0
Temperature [°C] 39
1m
0.2 0.2
0.2
0.3
2 0.
2 0.
0.3
0.2
0.2
0.2
2m
0.2
0.3
0.2
0.3
0.3
2m
0.5
0.3
0.2
0.3
0.2
0.2
40.6
2m
4
0.0
39.2 40.6
39.9
13.9
40.0
14.5
2m 14.5
39.9 13.9
14
13
.0
12.0
4m
3m
2m
1m
39.9
13.9
13.9
13.5
.5 13.5
40
40.6
40.0
.6
39.2
0 0
5m
4m
1m
39.9 43.0
9 9.
3m
.9
3
40
13
5m
39.9
39
14.5
43.0
1m
13.912.0
.9
.5
13.9
12.0
13.9
2m
43.0
1m
40.0
0 0
Console _ 11
Indoor Units
13.4
2m
2m
7. Air Velocity and Temperature Distribution(Reference Data) ARNU12GQAA2 Cooling
Heating
Discharge angle:40°
Discharge angle:50°
Air velocity [m/s] 0.2
2.7m
0.5
Air velocity [m/s]
0. 2
2.7m 0.4
2 0.
0.4
0.5
0.5
0.4
0.4
0.5
0.2
0.3
0.2
2m
0.4
0.4
0.2
0.4
0.2 0.2
0.3
0.5
0.5
0.2
0.2
0.2
1.3 0.3
2.2
0. 2
0.2
4m
3m
2m
1m
12.1
5m
2.7m
4m
3m
2m
0.2
0.2
0.2
0.4
0 0
0.4
0
Temperature [°C] 42.6
42.5
2.7m
43.3
13
42.5
13.5
13.5
13
42
.8
2m
42.8
42
42.5
.8
.5
43.3
2m
42.5
13
43.3
.5
11.5
13.5
42.5
1m
11.5
42.6
46.3
1m
46.3
42.5
.6
.5 13
.5
43.3
13.5
13.6
4m
3m
2m
42.5
43.3
.6
.5
13
13
5m
11.5
13
13
13.5
13.6
42.6
Indoor Units
42.5
43.3
13.6
0
1m
.5
13.5
13.6
0.2 0.2 0.4
1.3
Temperature [°C] 13.6
0.2
0.2
0.2 0.2
0.2
5m
0.2
0.2
0.2
0.5
1m
0.4
0.2
2 0.
2 0.
0.2
1m
0.3 0.5
0.4
0.5
0.2
2m 0.2
0.3
0.2
0.3
0.2
0.2
42.5
0 5m
0
1m
42.8
4m
3m
2m
43
.3
0
1m
0
ARNU15GQAA2 Cooling
Heating Discharge angle:50°
Air velocity [m/s]
2.7m
0.2
0.4
Air velocity [m/s] 0.2
0.3
0. 2 0.3
0.4
0.2
0.2
0.6
2.7m
1.0
0.4
0.4
1.0
Discharge angle:40°
0.6
0.2
0.2
0.2
3.6
1.9
2 0.
0.3 2 0. 0.3
0.3
0.3
0.3
1m
0
2.7m
3m
2m
0.2
0.6
03
0
1m
0
Temperature [°C] 41.0
41.0
2.7m
14.3
40
.8
41.0
.0
14.1
4m
0.2
0.6
41
14.3
14.1
5m
0.2
0.3
0.3
0.6
0
Temperature [°C] 14.3
0.3
1.9
2 0.
2m
1m
0.3
0.3
0.2 0 0.2 .2
3m
1.0
1.0
0.3
0.2
0.4
0.2 0.2
0.2
0.6
0.2 0.2 1.9
4m
0.3 0.2
1m
0.4
0.4
5m
0.6
0.3
0.4
0.3
0.2
0.2
2m 1.0
0.4
0.3
0.4
0.4
1.0
0.2 0.2
0.6
0.2
2m
41.0
41.0
2m
2m
14.1
41.0
14.1
14.3
.8
1m
41
.1 14
14.3
12 _ Console
3m
2m
1m
40.9
14.3
12.4
0
40
.8
.8
4m
40.8
41.0
40
5m
40.8 43.8
14.3
14.1
1m
41.0
40.8 41.0
.0
14.3
40.8
12.4 .3 14
14.2
40
.0
.8
41 40.9
12.4
43
14.3
.9
14.2
.2
.3
41.0
14 14
40
.1
14.1
14
41.0
0
0 5m
4m
3m
2m
1m
0
8. Electric Characteristicss Units Model
Type
ARNU07GQAA2
QA
ARNU09GQAA2
QA
Power Supply Hz
50
Volts
220-240
Voltage Range MCA
IFM
Input(W)
MFA
kW
FLA
Cooling Heating
0.13
15
0.048
0.10
30
30
Min.:198,
0.13
15
0.048
0.10
30
30
Max.:264
0.13
15
0.048
0.10
30
30
ARNU12GQAA2
QA
ARNU15GQAA2
QA
0.13
15
0.048
0.10
30
30
ARNU07GQAA2
QA
0.13
15
0.048
0.10
30
30
ARNU09GQAA2
QA
Min.:198,
0.13
15
0.048
0.10
30
30
ARNU12GQAA2
QA
Max.:264
0.13
15
0.048
0.10
30
30
ARNU15GQAA2
QA
0.13
15
0.048
0.10
30
30
60
220
Symbols:
Indoor Units
MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA â&#x2030;¤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.
Console _ 13
9. Sound Levels Overall Notes: - Data is valid at nominal operation condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard.
1m 1m
Microphone
Sound Pressure Level Sound Levels dB(A) H
M
L
ARNU07GQAA2
37
34
28
ARNU09GQAA2
37
34
28
ARNU12GQAA2
39
34
28
ARNU15GQAA2
42
37
31
ARNU09GQAA2
ARNU12GQAA2
80
80
70
70
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
10
63
NC-60 50
NC-50
250
500
1000
2000
4000
NC-45
40
NC-40 NC-35
30
NC-30
NC-20
125
NC-55
20
NC-25 Approximate Hearing Threshold
NC-65
60
NC-15 8000
10
NC-25 Approximate Hearing Threshold 63
125
250
500
1000
2000
4000
NC-15 8000
70
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
10
NC-25 Approximate Hearing Threshold 63
125
250
500
1000
2000
4000
NC-15 8000
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20
Octave Band Center Frequency (Hz)
14 _ Console
Octave Band Sound Pressure Level (dB re 20μPa )
80
10
NC-25 Approximate Hearing Threshold 63
NC-60
NC-20
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
10
NC-25 Approximate Hearing Threshold 63
NC-20
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
ARNU15GQAA2 80
NC-65
60
NC-20
Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (dB re 20μPa )
80
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
ARNU07GQAA2
Octave Band Sound Pressure Level (dB re 20μPa )
Indoor Units
Model
NC-15 8000
NC-15 8000
10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
10.1 Selection of the Best Location
More than 300 More than 300
More than 300
250 or below from the Floor
(Unit : mm)
In case that the unit is installed near the sea, the installation parts may be corroded by salt. The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
Console _ 15
Indoor Units
• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have the maintenance space.
10. Installation 10.2 Indoor unit installation 1. Preparation / Removing front panel 1. Open the front grille by pulling forward
2. Then pull out the link of grille from groove in front panel. 3. Then pull out 2 hinges of grille from grooves in front panel.
Indoor Units
4. Then remove 4 screws, dismount the front panel while pulling it forward.
2. Preparation / For Moldings , Side Piping, and Concealed Installation 2-1 For Moldings 1. Remove the slit portions on the Rear Panel.
Remove
Upper Deco cover
Side Deco cover
2-2 For Concealed Installation 1. Remove the 6 screws. 2. Remove the Upper Deco cover. 3. Remove the Side Deco covers.
2-3 For Side Piping (Reference 2-2.) 1. Remove the Deco Covers. 2. Remove the slit portions 3. Assemble the Deco Covers.
16 _ Console
10. Installation 3. Refrigerant Piping 1. The location of hole is different depending on which side of the pipe is taken out. 2. Drill a hole(Ă&#x2DC;70mm) in the point indicated by
symbol in the illustration as below
Left bottom piping
60
45
Wall
90
75
Right bottom piping
40 Right back piping
Right back piping
Indoor Units
50
75
45
90
45
Left back piping
Left/right piping
(Unit : mm)
NOTICE - The suggested shortest pipe length is 5m,in order to avoid noise from the outdoor unit and vibration.
4. Installing Indoor unit 4-1 Installation on the Floor. 1. Fix up using 6 screws for floor installation. (700)
26
64
180
159
(600)
140 170
574
140
647
0
170
21
30.5 0
6 screw (M4*25L)
16
30.5
(Unit : mm)
Console _ 17
10. Installation 4-2 Installation on the Wall 1. Fix up the installation plate using 5 screws and the indoor unit using 4 screws. 2. The installation plate should be fixed on a wall which can support the weight of the indoor unit.
Indoor Units
Installation Plate
Molding
4 screw (M4*25L)
4-3 Half concealed installation. 1. Make a wall hole of the size shown Fig-1. 45
Wall
670
Supplemental plate (Field supply)
95
Supplemental plate (Field supply)
Hole
200
200
150
150
585
(Unit : mm)
<Fig - 1>
18 _ Console
1) Normal concealed
2) Deep concealed
10. Installation 2. Installation of supplemental plate for attaching main unit â&#x20AC;˘ The rear of the unit can be fixed with screws at the points shown in the Fig-2.Be sure to install the supplemental plate in accordance with the depth of the inner wall.
647
140
140
170
170 (Unit : mm)
Indoor Units
<Fig - 2>
3.Piping Hole Wall
Right bottom Piping 35
50
Left bottom Piping
Left Piping 45
Wall
75
75
50
(Unit : mm)
4. Remove the Deco Covers and Fixing Indoor Unit 1) Remove the Deco Covers. 2) Insert the Indoor Unit to the Wall hole. 3) Secure using 6 screws. (shown in the illustration)
Console _ 19
10. Installation NOTICE - Check the horizon of Indoor unit with the wall. Please use the Leveler on the drain pan guide.
Leveler
Drain pan
Indoor Units
Less than 5mm
Less than 5mm
20 _ Console
Less than 5mm
10. Installation 10.3 Connecting the Piping When you connect the refrigerant pipe, it is easier that you connect the gas pipe first. 1. Hold up the Sensor Link. 2. Separate the Pipe Bracket (2 screws) 3. Connect the refrigerant pipe. (Refer to next page) 4. Assemble the Pipe Bracket (2 screws) 5. Put down the Sensor Link 2
4
5
3
Indoor Units
1
6. After connecting, check the pipe arrangement as per illustration. 7. The piping can be arranged in six ways as shown in the illustration below. 6
7
Pipe Guide
8
3 Connecting Pipe
2 1 Pipe Guide Connecting Pipe must be placed inner than the pipe guide.
4
6 5
In case of â&#x17E;&#x201A; ~ â&#x17E;&#x2026; , The pipe bending can be used in hand-operated bending machine. Make a pipe of the shape shown pic 8.
Console _ 21
10. Installation If the drain hose is routed inside the room insulate the hose with an insulation material* so that dripping from sweating (condensation) will not damage furniture or floors. * Foamed polyethylene or equivalent is recommended.
Tape Connecting cable Drain hose Connecting pipe
Connecting the installation pipe and drain hose to the indoor unit.
Indoor Units
1. Align the center of the pipes and sufficiently tighten the flare nut by hand.
Indoor unit tubing
Flare nut
Pipes
2. Tighten the flare nut with a wrench Outside diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Ø19.05 3/4
Torque kgf.m 1.8~2.5 3.4~4.2 5.5~6.5 6.3~8.2 9.9~12.1
3. When needed to extend the drain hose of indoor unit, assembly the drain pipe as shown on the drawing
Open-end wrench (fixed) Flare nut Wrench
Connection pipe
Indoor unit tubing
Drain pipe
Indoor unit drain hose Adhesive
Wrap the insulation material around the connecting portion. 1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap. 2. Wrap the area which accommodates the rear piping housing section with vinyl tape.
Vinyl tape(narrow)
Insulation material
Indoor unit pipe
Connection pipe
Wrap with vinyl tape Vinyl tape (wide) Connecting cable Pipe
3. Bundle the piping and drain hose together by wrapping them with vinyl tape sufficient enough to cover where they fit into the rear piping housing section.
Vinyl tape(narrow) Wrap with vinyl tape Pipe
Vinyl tape(wide) Drain hose
22 _ Console
10. Installation 10.4 Wiring Connection • Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model] Terminal block of indoor unit 1(L)
2(N)
3(A)
SODU B
SODU A
IDU B
IDU A
INT B
INT A
4(B)
Indoor power input 220V 60Hz
[Except Multi VIII Heat Pump Model] Terminal block of outdoor unit
1(L)
2(N)
3(A)
4(B)
Outdoor unit Indoor unit
Central controller
Indoor Units
Terminal block of indoor unit
SODU SODU IDU IDU INTERNET DRY1 DRY2 GND 12V
Indoor power input 220V 60Hz
Make sure that the screws of the terminal are free from looseness.
After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.
Console _ 23
10. Installation WIRED REMOTE CONTROLLER INSTALLATION â&#x20AC;˘ Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys.
Indoor Units
- Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
TEMP
yes
Remote Controller
no
TEMP
Controller Remote
TEMP
Remote Controller
5feet (1.5meters)
no
no
Fig.1 Typical locations for remote controller
24 _ Console
11. Accessories Standard Accessories Name
Drain Hose
Install Plate
Clamp (Tie wrap)
Quantity
1 EA
1 EA
4 EA
Shape
Other
- Allergy Filter - Fixing screw for installation Plate 4*25 mm-5EA - Wood screw for indoor fixation -6EA - Owner's Manual - Installation Manual
Indoor Units
Console _ 25
Indoor unit Fresh Air Intake Unit 1. List of functions 2. Specifications 3. Dimensions & Gravity point 4. Piping Diagrams 5. Wiring Diagrams 6. Outlet temperature, expected capacity and air flow 7. External Static Pressure(E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Operation range 11. Installation 12. Accessories
1. List of functions Category
Air flow
Air purifying
Indoor Units
Installation
Reliability
Convenience
Individual control
Special function kit
Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Standard wired remote controller Wide Character wired remote controller Picto wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat
ARNU48GBRZ2, URNU76GB8Z2,URNU96GB8Z2 1 2/2/2 X X O O O X O O O X O(only heat pump or cooling only) O O O X O O X Accessory Accessory Accessory Accessory Accessory X Accessory Accessory -
O : Applied X : Not applied â&#x20AC;&#x201C; : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
1 _ Fresh Air Intake Unit
2. Specifications Type Model
Unit kW kcal/h Btu/h kW kcal/h Btu/h
Notes:1. Capacities are based on the following conditions: Cooling • Outdoor temp. 33°C[91.4°F]DB/ 28°C[82.4°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Outdoor temp. 0°C[32°F]DB/ -2.9°C[26.78°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. Indoor Unit Connection No 1 2
Connection Condition Fresh Air Intake Units only are connected with outdoor units Mixture connection with general Indoor unit and Fresh Intake Unit
URNU96GB8Z2 28 24,100 95,900 26.7 23,000 91,360 Galvanized Steel Plate 1562 x 688 x 460 61.5 x 27.1 x 18.1 3 x 20 x 19 0.59 Sirocco Fan 375 x 1 2.15 35.7/23.7/23.7 1261/837/837 22 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Long Life Filter Fuse Ø9.52(3/8) Ø22.2(7/8) 25 73(161) 50/48/48 1, 220 - 240, 50 1, 220, 60 EEV CV1.5 x 3C VCTF-SB 1.0 ~ 1.5 x 2C
Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60
Combination 1) The total capacity of Fresh Air Intake Unit should be 50~100% of outdoor unit. 2) The max quantity of Fresh Air Intake unit is 2 Units. 1) The total capacity of indoor units (standard Indoor Unit + Fresh Air Intake Unit) should be 50~100% of outdoor unit. 2) The total capacity of Fresh Air Intake Unit should be less than 30% of the total capacity of indoor units.
6. EEV : Electronic Expansion Valve 7. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dBA)
Fresh Air Intake Unit _ 2
Indoor Units
ARNU48GBRZ2 14.1 Cooling Capacity 12,100 48,100 13.5 Heating Capacity 11,620 46,115 Casing Galvanized Steel Plate mm 1230 x 590 x 380 Dimensions(WxDxH) Body inch 48.4 x 23.2 x 15 Rows x Columns x FPI 3 x 13 x 19 Coil Face Area m3 0.38 Type Sirocco Fan Motor Output x Number W 195 x 1 Running Current A 0.38 Air Flow Rate(H/M/L) CMM 18.8/14.7/14.7 Fan (High Mode-factory set) cfm 664/519/519 External Static Pressure mmAq(Pa) 18 Drive Direct Motor type BLDC Microprocessor, Temperature Control Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Air Filter Long Life Filter Safety Device Fuse Liquid Side mm(inch) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm 25 Net Weight kg(lbs) 45(99) Noise Level(Sound Press, 1.5m, H/M/L) dB(A) 44/42/42 1, 220 - 240, 50 Power Supply Ø, V, Hz 1, 220, 60 Refrigerant Control EEV Power cable mm2 CV1.5 x 3C Transmission cable mm2 VCTF-SB1.0 ~ 1.5 x 2C
Fresh Air Intake Unit URNU76GB8Z2 22.4 19,300 76,400 21.4 18,410 73,080 Galvanized Steel Plate 1562 x 688 x 460 61.5 x 27.1 x 18.1 3 x 20 x 19 0.59 Sirocco Fan 375 x 1 1.36 23.7/13.2/13.2 837/446/446 22 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Long Life Filter Fuse Ø9.52(3/8) Ø19.05(3/4) 25 73(161) 49/47/47 1, 220 - 240, 50 1, 220, 60 EEV CV1.5 x 3C VCTF-SB 1.0 ~ 1.5 x 2C
R6
0
60
198
312
380
25
303
32
140
590
50
185
168
241
5
621
6
279
1,230
118 1,004
1,284 1,230
1,092
120
114
4
477 590
2
90
1
135 190 260
115
101 83
Name
Air discharge Air suction
4 5 6
Unit size(48k):ø25
Unit size(48k):ø15.88
Unit size(48k):ø9.52
Descripition
(unit : mm)
Gravity point
CHASSIS CODE: BR
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Power supply connection
3
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
3
Gas pipe connection Drain pipe connection
2
Liquid pipe connection
1
Number 26
ARNU48GBRZ2
Fresh Air Intake Unit
72 123 221 122 144
3 _ Fresh Air Intake Unit 56
Indoor Units
3. Dimensions & Gravity point
302
Fresh Air Intake Unit _ 4
460
460
688
293
5
329
819
6
1,562
1,220
1,562
688 30
1,622
115
560 64
290 161
20
440
318
1,396
358
68
18
109
58
122 60 70 64
397
Air discharge Air suction
6
Gravity point
CHASSIS CODE: B8
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Unit size(76k):ø19.05 Unit size(96k):ø22.2
Unit size(76k, 96k):ø19.05
Descripition
(unit : mm)
Drain pipe connection Unit size(76k, 96k): ø22.2 Power supply connection 5
4
3
Gas pipe connection
Name
2
3
Liquid pipe connection
0
1
Number
99 14
70 120
2
URNU76GB8Z2 URNU96GB8Z2
Fresh Air Intake Unit
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea
1
Indoor Units
4
3. Dimensions & Gravity point
4. Piping Diagrams
Th4
EEV
Th3
Filter
Th2 Heat Exchanger Distributor
Th1
Filter
Filter
S
Capillary Tube
Solenoid Valve
Check Valve
Indoor Units
Fresh Air Intake Unit
Refrigerant pipe connection port diameter [Unit: mm(inch)]
MODEL
GAS
LIQUID
ARNU48GBRZ2
Ø15.88(5/8)
Ø9.52(3/8)
URNU76GB8Z2
Ø19.05(6/8)
Ø9.52(3/8)
URNU96GB8Z2
Ø22.2(7/8)
Ø9.52(3/8)
LOC.
Description
Th1
Inlet Air Thermistor
Th2
Pipe In Thermistor
Th3
Pipe Out Thermistor
Th4
Outlet Air Thermistor
5 _ Fresh Air Intake Unit
Cooling Heating
5. Wiring Diagrams BR Chassis
Indoor Units
Accessory
B8 Chassis
Accessory
Fresh Air Intake Unit _ 6
6. Outlet temperature, expected capacity and air flow 6.1 Outlet Air Temperature ARNU48GBRZ2 Cooling DB 21 23 25 27 29 31 33 35 37 40
59 WB 15 WB CA SHC 4.7 3.5 4.6 4.1 4.6 4.5 -
63 WB 17 WB CA SHC 5.2 3.1 5.0 3.7 4.9 4.3 4.9 4.9 -
69 WB 20 WB CA SHC 7.8 3.6 7.7 4.2 6.9 4.8 6.6 5.4 6.3 6.1 -
73 WB 23 WB CA SHC 10.4 4.6 9.9 5.2 9.0 5.7 8.8 6.3 8.6 6.9 -
79 WB 26 WB CA SHC 12.9 4.6 12.5 5.2 12.2 5.8 11.8 6.4 11.0 6.9 10.6 7.9
82 WB 28 WB CA SHC 14.2 5.1 13.6 5.5 13.1 5.9 12.7 6.5 12.4 7.5
86 WB 30 WB CA SHC 15.2 4.7 14.9 5.3 14.3 5.9 13.9 6.8
90 WB 32.0 CA SHC 16.2 5.4 15.9 6.4
17.4
DB 21 23 25 27 29 31 33 35 37 40
59 WB 15 WB DB WB 11.8 9.9 11.9 10.0 12.0 10.1 -
63 WB 17 WB DB WB 12.7 11.8 13.0 12.0 13.3 12.0 13.8 12.0 -
69 WB 20 WB DB WB 13.5 12.7 13.7 12.8 14.0 13.5 14.2 13.8 14.3 14.0 -
73 WB 23 WB DB WB 14.7 14.0 14.8 14.4 15.5 15.2 15.7 15.3 15.8 15.5 -
79 WB 26 WB DB WB 16.7 15.7 16.9 16.0 17.2 16.2 17.5 16.5 17.7 17.2 17.9 17.5
82 WB 28 WB DB WB 17.5 17.4 18.2 17.9 18.9 18.2 19.2 18.5 19.5 18.7
86 WB 30 WB WB DB 20.5 19.5 20.7 19.7 20.9 20.1 21.2 20.3
90 WB 32.0 DB WB 22.5 21.6 22.5 21.7
95 WB 35 WB DB WB 25.2 25.1
Outdoor air tempreture DB 70 73 77 81 84 88 91 96 99 104
Indoor Units
Outdoor air tempreture DB 70 73 77 81 84 88 91 96 99 104
95 WB 35 WB CA SHC -
Heating Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68
DB -9 -3 0 3 7 11 15 18 20
Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68
DB -9 -3 0 3 7 11 15 18 20
23 WB
27 WB
32 WB
36 WB
39 WB
43 WB
50 WB
57 WB
-5 WB SHC 14.9 -
-2.9 WB SHC 14.0 -
0 WB SHC 13.8 -
2 WB SHC 14.0 12.5 -
4 WB SHC 12.7 -
6 WB SHC 12.6 11.2 -
10 WB SHC 11.3 9.9 8.9 -
14 WB SHC 10.1 9.0 8.1
23 WB
27 WB
32 WB
36 WB
39 WB
43 WB
50 WB
57 WB
-5 WB DB 38.7 -
-2.9 WB DB 39.2 -
0 WB DB 42.1 -
2 WB DB 42.7 42.6 -
4 WB DB 43.2 -
6 WB DB 43.3 42.8 -
10 WB DB 43.0 43.2 43.2 -
14 WB DB 43.7 43.5 43.1
Note) CA: Total Capacity (kW), SHC: Sensible Heat Capacity (kW) WB: Wet Bulb(℃), DB: Dry Bulb(℃) 1. The data shown in the graph illustrates the supported operating ranges underthe following conditions: - Indoor and Outdoor Unit - Effective piping length: 7.5 m - Height differential: 0 m 2. The actual temperature may not match the temperature setting under some circumstances due to the outdoor-air processing load or mechanical protection controls. 3. The system will not operate in fan mode when the outdoor air temperature is -5°C or below.
7 _ Fresh Air Intake Unit
5.5
6. Outlet temperature, expected capacity and air flow URNU76GB8Z2 Cooling 59 WB
63 WB
69 WB
73 WB
79 WB
82 WB
86 WB
90 WB
95 WB
17 WB CA SHC 8.6 5.0 8.1 5.8 8.2 6.7 8.3 7.5 -
20 WB CA SHC 11.9 5.5 11.4 6.4 11.1 7.2 10.8 7.9 10.7 8.8 -
23 WB CA SHC 14.8 6.6 14.4 7.3 14.1 8.1 13.7 8.9 13.4 9.7 -
26 WB CA SHC 18.2 6.9 17.9 7.7 17.6 8.5 17.3 9.3 15.1 14.8 16.2 11.1
28 WB CA SHC 20.7 7.3 20.3 8.0 19.9 8.8 19.3 9.4 19.1 10.6
30 WB CA SHC 22.2 7.3 21.5 7.9 21.2 8.7 20.7 9.8
32.0
DB 21 23 25 27 29 31 33 35 37 40
15 WB CA SHC 7.7 5.0 7.5 5.8 7.4 6.7 -
35 WB CA SHC 28.6 8.8
59 WB
63 WB
69 WB
73 WB
79 WB
82 WB
86 WB
90 WB
DB 21 23 25 27 29 31 33 35 37 40
15 WB DB WB 10.6 8.3 10.7 8.4 10.8 8.5 -
17 WB DB WB 10.6 10.0 10.8 10.4 10.9 10.2 11.0 10.1 -
20 WB WB DB 11.5 11.0 11.6 11.3 11.8 11.5 12.0 11.7 12.0 11.7 -
23 WB WB DB 13.1 12.5 13.4 12.8 13.6 13.0 13.7 13.2 13.8 13.4 -
26 WB DB WB 14.4 14.2 14.5 14.3 14.7 14.5 14.9 14.6 15.1 14.8 15.5 15.3
28 WB DB WB 15.5 15.3 15.9 15.5 16.1 15.7 16.5 16.1 16.6 16.1
30 WB DB WB 17.6 17.4 18.1 17.8 18.3 17.9 18.5 18.1
32.0 DB WB 19.4 18.9 19.5 19.0
Outdoor air tempreture DB 70 73 77 81 84 88 91 96 99 104 Outdoor air tempreture
SHC 8.2 9.4
95 WB 35 WB DB WB 21.1
21.1
Heating Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68 Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68
DB -9 -3 0 3 7 11 15 18 20
23 WB -5 WB SHC 20.5 -
27 WB -2.9 WB SHC 19.1 -
32 WB 0 WB SHC 18.3 -
36 WB 2 WB SHC 18.2 16.8 -
39 WB 4 WB SHC 16.6 -
43 WB 6 WB SHC 16.7 15.0 -
50 WB 10 WB SHC 14.9 13.2 11.8 -
57 WB 14 WB SHC 13.2 11.8 11.1
27 WB -2.9 WB DB 43.1 -
32 WB 0 WB DB 44.3 -
36 WB 2 WB DB 44.2 45.2 -
39 WB 4 WB DB 44.5 -
43 WB 6 WB DB 44.8 45.1 -
50 10
57 14
DB -9 -3 0 3 7 11 15 18 20
23 WB -5 WB DB 43.2 -
WB WB DB 44.9 44.8 44.7 -
WB WB DB 45.0 44.8 45.2
Note) CA: Total Capacity (kW), SHC: Sensible Heat Capacity (kW) WB: Wet Bulb(℃), DB: Dry Bulb(℃) 1. The data shown in the graph illustrates the supported operating ranges underthe following conditions: - Indoor and Outdoor Unit - Effective piping length: 7.5 m - Height differential: 0 m 2. The actual temperature may not match the temperature setting under some circumstances due to the outdoor-air processing load or mechanical protection controls. 3. The system will not operate in fan mode when the outdoor air temperature is -5°C or below.
Fresh Air Intake Unit _ 8
Indoor Units
DB 70 73 77 81 84 88 91 96 99 104
CA 24.4 24.0
6. Outlet temperature, expected capacity and air flow URNU96GB8Z2 Cooling 59 WB
63 WB
69 WB
73 WB
79 WB
82 WB
86 WB
90 WB
95 WB
17 WB CA SHC 11.1 6.7 10.3 7.9 10.6 9.2 10.6 10.5 -
20 WB CA SHC 16.0 7.5 15.3 8.8 14.8 10.0 14.3 11.2 14.2 12.5 -
23 WB CA SHC 20.5 9.2 19.7 10.3 19.2 11.4 18.7 12.7 18.2 13.9 -
26 WB CA SHC 25.4 9.6 25.0 10.9 24.4 12.0 24.0 13.2 23.5 14.3 22.2 15.9
28 WB CA SHC 29.0 10.3 28.5 11.3 27.9 12.4 26.9 13.4 26.5 15.2
30 WB CA SHC 31.1 10.2 30.0 11.1 29.6 12.3 28.8 14.0
32.0
DB 21 23 25 27 29 31 33 35 37 40
15 WB CA SHC 5.4 3.7 5.2 4.3 5.1 5.0 -
35 WB CA SHC 12.5 40.0
59 WB
63 WB
69 WB
73 WB
79 WB
82 WB
86 WB
90 WB
95 WB
DB 21 23 25 27 29 31 33 35 37 40
15 WB WB DB 11.7 9.4 11.8 9.5 11.9 9.6 -
17 WB DB WB 11.7 11.1 11.9 11.5 12.0 11.3 12.1 11.2 -
20 WB DB WB 12.6 12.1 12.7 12.4 12.9 12.6 13.1 12.8 13.1 12.8 -
23 WB DB WB 14.2 13.6 14.5 13.9 14.7 14.1 14.8 14.3 14.9 14.5 -
26 WB DB WB 15.5 15.3 15.6 15.4 15.8 15.6 16.0 15.7 16.2 15.9 16.6 16.4
28 WB DB WB 16.6 16.4 17.0 16.6 17.2 16.8 17.6 17.2 17.7 17.2
30 WB DB WB 18.7 18.5 19.2 18.9 19.4 19.0 19.6 19.2
32.0 DB WB 20.5 20.0 20.6 20.1
35 WB DB WB 22.2 22.2
Outdoor air tempreture DB 70 73 77 81 84 88 91 96 99 104
Indoor Units
Outdoor air tempreture DB 70 73 77 81 84 88 91 96 99 104
CA 34.4 33.8
SHC 11.6 13.4
Heating Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68
DB -9 -3 0 3 7 11 15 18 20
WB
27
WB
-2.9
SHC 30.8 WB
27 -2.9
-5 DB -9 -3 0 3 7 11 15 18 20
WB WB
32
WB
36
WB
39
WB
43
WB
50
0
WB
2
WB
4
WB
6
WB
10 WB SHC 22.5 19.8 17.6 -
SHC 28.7 -
WB DB 43.1 -
23
Outdoor air tempreture DB 18 27 32 37 45 52 59 64 68
23 -5
WB
WB DB 43.0 -
SHC 28.0 32 0
SHC 27.7 25.3 -
WB
36
WB DB 45.3 -
2
SHC 25.0 -
WB
39
WB DB 44.7 45.2 -
4
SHC 24.4 22.1 -
WB
43
WB DB 44.6 -
6
WB
50
WB DB 43.6 44.2 -
10
Note) CA: Total Capacity (kW), SHC: Sensible Heat Capacity (kW) WB: Wet Bulb(℃), DB: Dry Bulb(℃) 1. The data shown in the graph illustrates the supported operating ranges underthe following conditions: - Indoor and Outdoor Unit - Effective piping length: 7.5 m - Height differential: 0 m 2. The actual temperature may not match the temperature setting under some circumstances due to the outdoor-air processing load or mechanical protection controls. 3. The system will not operate in fan mode when the outdoor air temperature is -5°C or below.
9 _ Fresh Air Intake Unit
WB
57
WB
14 WB SHC 19.6 17.9 16.4
WB
57
WB DB 44.9 44.8 44.5 -
14
WB
WB DB 44.5 45.0 44.7
6. Outlet temperature, expected capacity and air flow 6.2 Air flow ARNU48GBRZ2 Setting Value
6 16 19.9 23.4 24.1 25.5 27 27 28.5 29.8 31.8 32.7 -
8 13.6 17.8 19.6 21.9 22.8 24 25 26.5 28 29.17 30.9 -
12 10.6 13.8 15.8 17.4 20.5 22 24.6 28.3 30.7 -
ESP (mmAq) 14 10.7 16 16.5 19.9 24.2 27.6 30.4 -
15 26.57 42.67 46.44 48.82 50.91 50.9 -
ESP (mmAq) 18 20.9 33.72 40.09 44.3 46.73 49.84 49.66 -
10 15.9 18.2 19.8 22.5 22.8 24.2 25.9 28.2 30.8 -
15 11.8 15.2 20.7 25.2 29.7 -
16 11.9 17.7 24.2 27.2 28.6 -
17 15.8 22.4 26.3 27.6 -
18 14.7 18.8 25.6 27.4 -
20 13.4 18.7 25.9 26.5 -
URNU76GB8Z2,URNU96GB8Z2 Setting Value 55 60 65 70 75 80 85 88 90 92 94 96 98 100 102 105
6 25.39 33.65 40.01 46.43 50.93 55.77 -
9 30.29 35.81 45.35 51.91 54.22 -
12 17.31 35.57 42.86 49.74 52.72 52.54 -
20 23.07 23.46 39.65 44.04 48.09 48.23 -
22 13.87 24.17 39.72 42.56 46.41 -
23 23.63 25.28 40.34 45.92 46.51
25 14.49 15.47 38.6 45.44
Note) Setting Value : ESP value The above table shows the correlation between the air rates and E.S.P.
Fresh Air Intake Unit _ 10
Indoor Units
70 75 80 85 87 90 92 94 96 98 101 103 106 111 116 121 126 130 135 140
5 15.8 18.7 22.2 24.2 25.2 26.8 28.1 29 30.3 -
7. External Static Pressure (E.S.P) & Air Flow ARNU48GBRZ2 Capacity (Btu/h)
Mode
Set value
High High (factory set) Mid
1,160
48k
1,110
Standard ESP(mmAq(Pa)) 18
CMM 18.8 14.7
Lower Limit of External Static Pressure(mmAq(Pa))
Upper Limit of External Static Pressure(mmAq(Pa))
10(98)
20(196)
Lower Limit of External Static Pressure(mmAq(Pa))
Upper Limit of External Static Pressure(mmAq(Pa))
12(118)
25(245)
12(118)
25(245)
URNU76GB8Z2,URNU96GB8Z2 Capacity (Btu/h)
Mode
Set value 950
Mid
930
96k
High (factory set)
High
970
Mid
950
Indoor Units
High (factory set)
High
76k
11 _ Fresh Air Intake Unit
Standard ESP(mmAq(Pa)) 22 22
CMM 23.7 13.2 35.7 23.7
8. Electric Characteristics Units Model
Type
ARNU48GBRZ2
BR
URNU76GB8Z2
B8
URNU96GB8Z2
B8
ARNU48GBRZ2
BR
URNU76GB8Z2
B8
URNU96GB8Z2
B8
Power Supply
Hz 50
volts 220-240
Max: 264 Min: 198 60
Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(see note 5)
IFM : Indoor Fan Motor
220
Input(W)
MCA
MFA
kW
FLA
Cooling Heating
1.5
15
0.39
0.38
169
169
2.7
15
0.38
1.36
230
230
3.7
15
0.38
2.15
360
360
1.5
15
0.39
0.38
169
169
2.7
15
0.38
1.36
230
230
3.7
15
0.38
2.15
360
360
Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFAâ&#x2030;¤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.
Fresh Air Intake Unit _ 12
Indoor Units
kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A)
Voltage Range
IFM
9. Sound Levels Overall DISCHARGE
Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
SUCTION
DUCT
DUCT 1.5m
2m
1m 1m
[dB(A)] Sound Level
ARNU48GBRZ2
H 44
M 42
L 42
URNU76GB8Z2
49
47
47
URNU96GB8Z2
50
48
48
Sound Pressure Level ARNU48GBRZ2
URNU76GB8Z2
URNU96GB8Z2
80
80
70
70
70
NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20
10
Approximate Hearing Threshold 63
NC-60
125
250
500
Octave Band Center Frequency (Hz)
13 _ Fresh Air Intake Unit
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20 NC-15 1000 2000 4000 8000
NC-65
60
10
NC-25 Approximate Hearing Threshold 63
Octave Band Sound Pressure Level (dB re 20μPa )
80
Octave Band Sound Pressure Level (dB re 20μPa )
Octave Band Sound Pressure Level (dB re 20μPa )
Indoor Units
Model
NC-60
125
250
500
Octave Band Center Frequency (Hz)
NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 20
NC-20 NC-15 1000 2000 4000 8000
NC-65
60
10
NC-25 Approximate Hearing Threshold 63
NC-20
125
250
500
NC-15 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
10. Operation Details Operation range FAU will operate in the below range. Hot outdoor temperature (over 43℃) or cold outdoor temperature (under 5℃) will make customer feel uncomfortable because FAU outlet discharge temperature might be not enough controlled in that region. * FAU : Fresh Air Intake Unit -5°C Cooling mode
5°C
15°C
Outdoor Air Temperature (Toa) ℃ 43℃ (1)
19°C
Fan operation (thermo off)
Cooling Cooling
Fan operation Fan stop
Heating mode
6°C
18°C
Heating
Fan operation (thermo off) Fan operation
Heating 16°C
Indoor Units
Automatic mode
Cooling
Heating
Cooling Heating
18°C 16°C (1)Normal model : 43°C Tropical model : 48°C
Usage Limitations
-5°C
15°C
19°C
(33.5°)
43℃ (2)
(2)Normal model : 43°C Tropical model : 48°C
Fresh Air Intake Unit _ 14
11. Installation
Air outlet vents
Air filters
Air intake vents
Indoor Units
Wired Remote Controller
Standard Accessories Name
Drain hose
Clamp metal
Quantity
1 EA
2 EA
Washer for hanging backet 8 EA
Clamp (Tie Wrap)
Insulation for fitting
4 EA
1 SET
Others
â&#x20AC;˘ Owner's manual â&#x20AC;˘ Installation manual Shape
for gas pipe
for liquid pipe
15 _ Fresh Air Intake Unit
11. Installation 11.1 Installation Limit Read completely, then follow step by step.
1. Fresh Air Intake Unit Combination No 1
Connection Condition Only Fresh Air Intake Unit installation
2 Mixture Installation with standard indoor units and Fresh Intake Units
Combination 1) The total capacity of Fresh Air Intake Unit should be 50~100% of outdoor unit. 2) The max quantity of Fresh Air Intake unit is 2 Units. 1) The total capacity of indoor units (standard Indoor Unit + Fresh Air Intake Unit) should be 50~100% of outdoor unit. 2) The total capacity of Fresh Air Intake Units should be less than 30% the total capacity of indoor units.
Failure to comply with the above connection conditions for installation, it can cause cooling & heating capacity down.
Indoor Units
2. Connection of the Outdoor Unit It is possible to connect Heat Pump Models. It is not possible to connect Heat Recovery Models. <Only Fresh Air Intake Unit install>
<Mixture Install>
Outdoor : 10HP
Outdoor : 20HP
FAU
FAU
FAU
Standard
Standard
Standard
5HP
5HP
5HP
5HP
5HP
5HP
<Wrong Install> Outdoor : 20HP
FAU
Standard
Standard
Standard
Standard
5HP
5HP
5HP
5HP
5HP * FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit
áś&#x20AC; The total capacity of indoor units exceed 100% of outdoor unit
Fresh Air Intake Unit _ 16
11. Installation 3. Installation of intake air duct Min. 2m
Inlet Hood Intake Air Duct Fresh Air Intake Unit Exhaust Fan Door
1/30 Slope Outlet Air
Indoor Units
Exhaust air
Inlet Hood Inlet Hood should be installed such that no water enter inside the unit Intake Air Duct The Intake Air Duct must have down-slope about 1/30. The length of Intake Air Duct should be longer than 2m. Fresh Air Intake Unit If wired remote controller is not connected, it will display strange value to the room temperature Exhaust Fan Fresh Air Intake Unit will make room the positive pressure. Exhaust fan should be installed to maintain the room pressure. Door It would be possible to raise in the room air pressure because of Fresh Air Intake Unit. In that case, the door could hurt someone in front of door. So be careful of the positive pressure to design the door.
17 _ Fresh Air Intake Unit
11. Installation 4. The Control System 1) In case of connecting with Standard indoor units, Standard indoor unit should be a master unit. Separate Fresh Air Intake Unit with Standard indoor units .Set only one Standard indoor units to Master,
Standard
FAU
Standard
Standard
Slave
* FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit
Set one of the IDU to Master
FAU
FAU
Standard
Standard
FAU
FAU
Standard
Standard
48 kBtu/h
48 kBtu/h
48 kBtu/h
48 kBtu/h
48 kBtu/h
48 kBtu/h
48 kBtu/h
48 kBtu/h
ZONE 1
ZONE 2
ZONE 1
ZONE 2
5. Cycle check and SVC For Fresh Intake Unit cycle check and SVC, LG MV 5.8 or later version should be used.
Fresh Air Intake Unit _ 18
Indoor Units
2) In case of using central remote controller, mixture of indoor units and Fresh Air Intake Unit in same zone is not possible. Separate Fresh Air Intake Unit zone with Standard indoor units zone.
11. Installation 11.2 Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unitʼs weight. • The place shall be able to inspect the unit as the figure. • The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit.
Top view
Inspection hole (600X600)
(unit: mm)
600
1000
Indoor Units
Control box
600
Front
Front view
H
CAUTION : In case that the unit is installed near the sea, the installation parts may be corroded by salt, The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
[Inspection Hole Standard] Number of Inspection hole
Distance between False ceiling & Actual ceiling
1
More than 1000mm
Sufficient space in the ceiling for servicing.
200mm to 1000mm
Insufficient space. Difficult for servicing
Less than 200mm
Minimum height for motor replacement.
2 Hole size should be more than the size of IDU.
19 _ Fresh Air Intake Unit
Remarks
11. Installation 11.3 Ceiling dimension and hanging bolt location Installation of Unit Install the unit above the ceiling correctly.
BR Chassis (48k)
A B
CASE 1 C E
POSITION OF SUSPENSION BOLT
D
• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
F
(G)
(Unit:mm) Dimension
B
C
D
E
F
(G)
H
I
477
56
590
30
120 1006 294
I
A Capacity(Btu/h)
BR Chassis 1282 1230 (48k)
H
(Unit:mm)
Indoor Units
Drainage hole
B8 Chassis (76/96k)
Dimension
A
B
C
D
E
F
G
H
I
J
K
L
Capacity(Btu/h)
B8 Chassis (76/96k) 1680 1565 1160 330 460 580 700 1400 1635 390 445 15
CASE 2 • Install the unit leaning to a drainage hole side as a figure for easy water drainage. POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.
M10 Nut
X4
M10 washer
X4
M10 washer
X4
M10 Nut
X8
Fresh Air Intake Unit _ 20
11. Installation NOTICE • Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated.
Indoor Units
5. Avoid places near high frequency generators.
11.4 Indoor Unit Installation • Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling.
• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
Old building
1 Set anchor 2 Plate washer 3 Spring washer 4 Nut
CAUTION : Tighten the nut and bolt to prevent unit falling.
21 _ Fresh Air Intake Unit
5 Suspension bolts
New building
11. Installation 11.5 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. • BR Chassis (48k) [Multi V III Heat Pump Model]
1(L)
2(N)
3(A)
[Except Multi VIII Heat Pump Model] SODU B
Terminal Block Indoor
SODU A
IDU B
IDU A
INT B
INT A
Terminal Block Indoor 1(L)
4(B)
2(N)
3(A)
Outdoor unit Indoor unit
4(B)
SODU SODU
IDU
Central controller
Outdoor unit
IDU INTERNET DRY1 DRY2 GND 12V
INDOOR POWER INPUT
INDOOR POWER INPUT
• B8 Chassis (76/96k) [Except Multi VIII Heat Pump Model]
[Multi V III Heat Pump Model] Terminal Block Indoor 1(L)
2(N)
3(A)
Terminal Block
SODU B
SODU A
IDU B
IDU A
INT B
INT A
Terminal Block Indoor 1(L)
4(B)
2(N)
3(A)
Terminal Block 4(B)
Outdoor unit Indoor unit SODU SODU
IDU
Central controller
IDU INTERNET DRY1 DRY2 GND 12V
Outdoor unit
Indoor Power Input
Indoor Power Input
Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.
INSULATION, OTHERS THERMAL INSULATION
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
Union for liquid pipe Refrigerant pipe and thermal insulator(Local supply) Hose crip for thermal insulator (Local supply) Thermal insulator for refrigerant pipe (Local supply) Union for gas pipe
Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply)
Overlap with thermal insulator for piping. Hose crip for thermal insulator(Local supply) Make sure that there is no clearance here.
Fresh Air Intake Unit _ 22
Indoor Units
WARNING : Make sure that the screws of the terminal are free from looseness.
11. Installation 11.6 Check the Drainage
Indoor Units
2. Check the drainage. • Spray one or two glasses of water upon the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.
CAUTION 1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.
Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation.
1~3mm
Ceiling
Drain Pump unuse
Drainage hole
23 _ Fresh Air Intake Unit
Drain Pump use
Drainage hole
11. Installation 11.7 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe inner diameter Ø 25mm and pipe fittings
Upward routing not allowed
Pipe clamp Indoor unit
Maintenance drain port
• Be sure to install heat insulation on the drain piping.
1/50~1/100
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
MAX 700mm
Drain test
Feed water
Flexible drain hose (accessory) Main drain pipe
Drain Pump
Drain port
Glue the joint
Drain hose connection Use the clip (accessory)
• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operation and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Drain pan
The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.
Hanger distance 1~15m
Hanger Bracket 1/50~1/100 slope
Metal clamp Flexible drain hose
Max 700mm
Max 300mm
Insulation
Flexible drain hose Flexible drain hose
Flexible drain hose
Fresh Air Intake Unit _ 24
Indoor Units
The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:
11. Installation CAUTION:
Indoor Units
After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. â&#x20AC;˘ Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal function of an overload protection device. â&#x20AC;˘ Proper starting power is not given to the compressor.
HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)
25 _ Fresh Air Intake Unit
12. Accessories Standard Accessories Name
Drain hose
Clamp metal
Quantity
1 EA
2 EA
Washer for hanging backet 8 EA
Clamp (Tie Wrap)
Insulation for fitting
4 EA
1 SET
(Other)
• Owner's manual • Installation manual Shape
for gas pipe
for liquid pipe
Indoor Units
CAUTION • Use only those accessories (Standard or optional) which have designated specifications.
Fresh Air Intake Unit _ 26
Indoor unit Dip Switch & Group Control Setting 1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 1.1 Dip Switch Setting 1.2 Group Control Setting 1.3 2 Remote Control 1.4 Accessories for group control setting
2. Wall Mounted, ART COOL Gallery, ART COOL Mirror 2.1 Master/Slave Setting 2.2 Group Control Setting 2.3 2 Remote Control 2.4 Accessories for group control setting
1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 1.1 Dip Switch Setting Dip Switch Setting of Indoor unit PCB
SW1
Function Communication
Description N/A (Default)
Setting Off -
Setting On -
Default Off
SW2
Cycle
N/A (Default)
-
-
Off
SW3
Group Control
Selection of Master or Slave
Master
Slave
Off
Dry Contact Mode
Selection of Dry Contact Mode
Wired/Wireless remote controller selection of Manual or Auto operation Mode
Auto
Off
SW5
Installation
Fan continuous operation
Continuous operation Removal
-
Off
SW6
Heater linkage
N/A
-
-
Off
Ventilator linkage
Selection of Ventilator linkage
Linkage Removal
Working
Vane selection (Console)
Selection of up/down side Vane
Up side + Down side Vane
Up side Vane Only
Region selection
Selection tropical region
General model
Tropical model
Etc.
Spare
-
-
SW4
SW7
SW8
Off
Off
For Multi V Models, Dip switch 1, 2, 6, 8 must be set OFF.
Dip Switch & Group Control Setting _ 1
Dip Switch & Group Control Setting
CAUTION
1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 1.2 Group Control 1 (1) Group Control 1 Wired remote controller 1 + Standard Indoor Units LGAP Network System
or
Master
Slave
Slave
Slave
Display Error Message Only connect serial signal and GND lines between slave indoor unit
Dip Switch & Group Control Setting
Master
Dip Switch in PCB (Cassette and Duct Type indoor units) - No. 3 Off
- No. 3 On
1. It is possible to 16 indoor units(Max) by one wired remote controller. Set only one indoor unit to Master, set the others to Slave. 2. It is possible to connect with every type of indoor units. 3. It is possible to use wireless remote controller at the same time. 4. It is possible to connect with Dry Contact and Central controller at the same time. - The Master indoor unit is possible to recognize Dry Contact and Central Controller only. - In case of Central controller and Group controller at the same time, it is possible to connect standard 2series indoor units or later since Feb. 2009. - In case of Central controller setting, the Central controller can control indoor units after setting only the address of master indoor unit. - Slave indoor unit will be operated like master indoor unit. - Slave indoor unit can not be individually controlled by Central controller. - Some remote controller canâ&#x20AC;&#x2122;t perform with Dry Contact and Central controller at the same time. So contact us further information about it.
2 _ Dip Switch & Group Control Setting
GND Signal 12 V
1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 5. In case of any error occurs at indoor unit, display on the wired remote controller. Exception of the error indoor unit, an individual indoor unit control possibility. 6. In case of Group Control, it is possible to use following functions. - Selection of operation options (operation/stop/mode/set temperature) - Control of flow rate (High/Middle/Low) - It is not possible at some functions. Master/Slave setting of indoor units be set possible using a PCB Dip Switch. It is possible to connect indoor units since Feb. 2009. In the other cases, please contact LGE. It can be the cause of malfuctions when there is no setting of master and slave.
(2) Group Control 2 Wired remote controllers + Standard Indoor Units LGAP Network System
or
Slave
Slave
GND Signal 12 V
DonĘźt connect serial 12V line
Display Error Message Master
Slave
It is possible to control N indoor units by wired remote controller M units. (M+Nâ&#x2030;¤17 Units) Set only one indoor unit to Master, set the others to Slave. Set only one wired remote controller to Master, set the others to Slave. Other than those, it is same with the Group Control 1.
Dip Switch & Group Control Setting _ 3
Dip Switch & Group Control Setting
Slave
Master
1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit (3) Group Control 3 Mixture connection with indoor units and Fresh Air Intake Unit LGAP Network System
or
FAU Master
FAU Slave
Master
Slave
GND Signal 12 V
Display Error Message
Master
Master
Dip Switch & Group Control Setting
In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air Intake Unit with standard units. (Because setting temperature are different.) Other than those, it is same with Group Control 1.
FAU
FAU
Standard
Standard
FAU
FAU
Standard
Standard
* FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit
4 _ Dip Switch & Group Control Setting
1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 1.3 2 Remote Control Wired remote controller 2 + Indoor unit 1 LGAP Network System
or
Master
Display Error Message Master
Slave
1. It is possible to connect two wired remote controllers with one indoor unit. 3. It is possible to use wireless remote controller at the same time. 4. It is possible to connect with Dry Contact and Central controller at the same time. 5. In case of any error occurs at indoor unit, display on the wired remote controller. 6. There isnĘźt limits of indoor unit function. â?&#x2C6; Maximum 2wired remote controllers can be connected with 1 indoor unit.
Dip Switch & Group Control Setting _ 5
Dip Switch & Group Control Setting
2. Every types of indoor unit is possible to connect two remote controller.
1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit 1.4 Accessories for group control setting It is possible to set group control by using below accessories. Indoor unit 2 EA +Wired remote controller â?&#x2C6; PZCWRCG3 cable used for connection
Indoor unit 1 EA +Wired remote controller 2EA â?&#x2C6; PZCWRC2 cable used for connection
S lave
Mas te r
PZC WRC 2 PZC WRC G3
Dip Switch & Group Control Setting
Maste r
6 _ Dip Switch & Group Control Setting
Maste r
S lave
2. Wall Mounted, ART COOL Gallery, ART COOL Mirror 2.1 Master/Slave Setting
1
With the FAN SPEED button pressed, press the RESET button.
2
By using the TEMPERATURE SETTING button, set function code and setting value. (Please refer the Installer Setting Code Table.) Function Code
Setting Code
4
Reset the remote controller to use the general operation mode.
Installer Setting Code Table No.
Function
Function Code
Setting Value
Remote Controller LCD
0 : Set to Master 1
Group Control
2
1 : Set to Slave 2 : Check Master/Slave
Dip Switch & Group Control Setting _ 7
Dip Switch & Group Control Setting
3
Press the ON/OFF button toward the indoor unit 1 time.
2. Wall Mounted, ART COOL Gallery, ART COOL Mirror Group Control Setting - This function is only for group control. - Please don’t set this function in case of non-group control. - This function is the Master or Slave setting function of indoor unit - Set only one indoor unit to Master, set the others to slave. - After setting Group Control of the product, turn off the power then turn it back on after 1 minute. - Master checking whether the buzzer sounds, such as indoor rings below. ▶ Master: “Beep” (Buzzer sound 1 time) ▶ Slave: “Beep, Beep, Beep, Beep, Beep ” (Buzzer sounds 5 times)
2.2 Group Control 1 (1) Group Control 1 Wired remote controller 1 + Standard Indoor Units LGAP Network System
Dip Switch & Group Control Setting
or
Master
Slave
Slave
Slave
Display Error Message Only connect serial signal and GND lines between slave indoor unit Master
1. It is possible to 16 indoor units(Max) by one wired remote controller. Set only one indoor unit to Master, set the others to Slave. 2. It is possible to connect with every type of indoor units. 3. It is possible to use wireless remote controller at the same time.
8 _ Dip Switch & Group Control Setting
GND Signal 12 V
2. Wall Mounted, ART COOL Gallery, ART COOL Mirror 4. It is possible to connect with Dry Contact and Central controller at the same time. - The Master indoor unit is possible to recognize Dry Contact and Central Controller only. - In case of Central controller and Group controller at the same time, it is possible to connect standard 2series indoor units or later since Feb. 2009. - In case of Central controller setting, the Central controller can control indoor units after setting only the address of master indoor unit. - Slave indoor unit will be operated like master indoor unit. - Slave indoor unit can not be individually controlled by Central controller. - Some remote controller canâ&#x20AC;&#x2122;t perform with Dry Contact and Central controller at the same time. So contact us further information about it. 5. In case of any error occurs at indoor unit, display on the wired remote controller. Exception of the error indoor unit, an individual indoor unit control possibility. 6. In case of Group Control, it is possible to use following functions. - Selection of operation options (operation/stop/mode/set temperature) - Control of flow rate (High/Middle/Low) - It is not possible at some functions. Indoor units be set possible using a wireless remote controller. This indoor unit be set possible using a wireless remote controller for setting group control. (type : Wall Mounted, ART COOL Gallery, ART COOL Mirror) It is possible to connect indoor units since Feb. 2009. In the other cases, please contact LGE. It can be the cause of malfuctions when there is no setting of master and slave.
Dip Switch & Group Control Setting
Dip Switch & Group Control Setting _ 9
2. Wall Mounted, ART COOL Gallery, ART COOL Mirror (2) Group Control 2 Wired remote controllers + Standard Indoor Units LGAP Network System
or
Slave
Master
Slave
Slave
DonĘźt connect serial 12V line
Display Error Message
Dip Switch & Group Control Setting
Master
Slave
It is possible to control N indoor units by wired remote controller M units. (M+Nâ&#x2030;¤17 Units) Set only one indoor unit to Master, set the others to Slave. Set only one wired remote controller to Master, set the others to Slave. Other than those, it is same with the Group Control 1.
10 _ Dip Switch & Group Control Setting
GND Signal 12 V
2. Wall Mounted, ART COOL Gallery, ART COOL Mirror (3) Group Control 3 Mixture connection with indoor units and Fresh Air Intake Unit LGAP Network System
or
FAU Master
FAU Slave
Master
Slave
GND Signal 12 V
Display Error Message
Master
Master
Other than those, it is same with Group Control 1.
FAU
FAU
Standard
Standard
FAU
FAU
Standard
Standard
* FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit
Dip Switch & Group Control Setting _ 11
Dip Switch & Group Control Setting
In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air Intake Unit with standard units. (Because setting temperature are different.)
2. Wall Mounted, ART COOL Gallery, ART COOL Mirror 2.3 2 Remote Control Wired remote controller 2 + Indoor unit 1 LGAP Network System
or
Master
Display Error Message Master
Slave
Dip Switch & Group Control Setting
1. It is possible to connect two wired remote controllers with one indoor unit. 2. Every types of indoor unit is possible to connect two remote controller. 3. It is possible to use wireless remote controller at the same time. 4. It is possible to connect with Dry Contact and Central controller at the same time. 5. In case of any error occurs at indoor unit, display on the wired remote controller. 6. There isnĘźt limits of indoor unit function. â?&#x2C6; Maximum 2wired remote controllers can be connected with 1 indoor unit.
12 _ Dip Switch & Group Control Setting
2. Wall Mounted, ART COOL Gallery, ART COOL Mirror 2.4 Accessories for group control setting It is possible to set group control by using below accessories. Indoor unit 2 EA +Wired remote controller ❈ PZCWRCG3 cable used for connection
Indoor unit 1 EA +Wired remote controller 2EA ❈ PZCWRC2 cable used for connection
S lave
Mas te r
PZC WRC 2 PZC WRC G3
Maste r
Maste r
S lave
Dip Switch & Group Control Setting
Dip Switch & Group Control Setting _ 13
P/No.: MFL61741606
Air Conditioner 20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com
All rights reserved Printed in Korea March/2010 The specifications, designs, and information in this brochure are subject to change without notice.
The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.