FIRE PROTECTION NARRATIVE AND REPORT
TOWER CROSSROADS 1801 MAIN STREET KANSAS CITY, MISSOURI
MCCANN, WILLIAM MCCANN FIRE PROTECTION
TABLE OF CONTENTS I.
INTRODUCTION .........................................................................................2
II.
BUILDING DESCRIPTION ........................................................................2
III.
CODES AND STANDARDS ........................................................................2
IV.
FIRE PROTECTION APPROACH ............................................................4 BUILDING OCCUPANCY ............................................................................................ 4 FIRE RESISTIVE CONSTRUCTION ........................................................................... 5 EXISTING REQUIREMENTS....................................................................................... 6 SECONDARY POWER ................................................................................................. 6 FIRE ALARM ................................................................................................................. 7 FIRE SUPPRESSION ................................................................................................... 11 SMOKE CONTROL SYSTEM .................................................................................... 15
V.
APPENDIX A ...............................................................................................17 FIRE MODEL ............................................................................................................... 17 CODE AND STANDARD REFERENCES ................................................................. 17 PERFORMANCE GOALS ........................................................................................... 18 MODEL OUTPUT GRAPHS AND IMAGES ............................................................. 18
VI.
APPENDIX B ...............................................................................................22 MODEL LANGUAGE ................................................................................................. 22
INTRODUCTION
BUILDING DESCRIPTION New construction of a High-Rise Mixed-Use Development named Tower Crossroads to be located at 1801 Main Street Kansas City, Missouri. The project includes 5 levels of subterranean vehicle parking, 1 level featuring a restaurant retail shop and facility support areas, 2 levels including office space, equipment and fabrication areas, 15 levels of open office space. This document describes the general expectations of the Fire Protection systems for this project.
CODES AND STANDARDS 1.
THE FOLLOWING CODES, REGULATIONS AND STANDARDS SHALL BE USED IN THE DESIGN OF THIS PROJECT:
a.) 2012 International Building Code, with Kansas City, Missouri Amendments b.) 2012 International Mechanical Code, with Kansas City, Missouri Amendments c.) 2012 International Plumbing Code, with Kansas City, Missouri Amendments d.) 2012 International Fuel Gas Code, with Kansas City, Missouri Amendments e.) 2012 International Fire Code, with Kansas City, Missouri Amendments f.) 2012 International Energy Conservation Code, with Kansas City, Missouri Amendments g.) 2014 National Electric Code h.) 2012 Kansas City, Missouri Green Ordinance i.) ADA/TAS Americans with Disabilities Act / Missouri Accessibility Standards
j.) Occupational Safety and Health Act (OSHA) k.) National Fire Protection Association (NFPA) l.) American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE)
m.) American National Standards Institute (ANSI) n.) Air Conditioning, Heating and Refrigeration Institute (AHRI) o.) Sheet Metal and Air Conditioning Contractors National Association, Inc. (SMACNA) p.) Underwriters Laboratories (UL) q.) Illuminating Engineering Society (IES) r.) Institute of Electrical and Electronics Engineers (IEEE) s.) National Electrical Manufactures' Association (NEMA) Page 2 of 16 t.) American Society for Testing and Materials (ASTM) u.) American Gas Association (AGA) v.) American Society of Mechanical Engineers (ASME) w.) American Society of Sanitary Engineers (ASSE) x.) American Welding Society (AWS) y.) American Water Works Association (AWWA) z.) National Electrical Manufacturers Association (NEMA) aa.) National Standards Foundation (NSF) bb.) Plumbing and Drainage Institute (PDI) cc.) All other applicable State and Local codes not referenced herein.
FIRE PROTECTION APPROACH BUILDING OCCUPANCY 1. BASIC BUILDING INFORMATION CONSTRUCTION CLASSIFICATION:
Type I-A IBC 2012
OCCUPANCY CLASSIFICATION: Mixed Non-Separated use, consisting of Storage, Mercantile, Assembly, Fabrication, and Business OCCUPANCY BY FLOOR:
Lower Levels: Level 1:
Storage (S-2) Assembly (A-2) Mercantile (M)
Levels 2-3:
Business (B)
Levels 4-17:
Business (B)
2. HEIGHT/AREA LIMITATIONS ANALYSIS ALLOWABLE HEIGHT ANALYSIS ALLOWABLE HEIGHT/STORIES: Unlimited IBC Table 503 ACTUAL HEIGHT:
17 Stories above grade: 204 feet 5 Levels below grade: 50 feet
ALLOWABLE AREA ANALYSIS ALLOWABLE AREA: IBC Table 503 ACTUAL AREA:
Unlimited
Lower Levels: 10,034 SF/Floor Level 1: 19,771 SF Levels 2-3: 6965 SF/Floor Levels: 4-17: 7,000 SF/Floor Total: 181,871 SF
FIRE RESISTIVE CONSTRUCTION 1. PASSIVE FIRE SAFETY FEATURES FIRE RESISTANCE OF SREUCTURAL ELEMENTS IBC TABLE 601 (unless otherwise noted) STRUCTURAL ELEMENT
PRIMARY STRUCTURAL FRAME
FIRE RESISTANCE RATING (IN HOURS) 3
EXTERIOR BEARING WALLS • SUPPORTING MORE THAN ON LEVEL
3
EXTERIOR NONLOAD-BEARING WALLS • FIRE SEPARATION < 5 FEET • FIRE SEPARATION 0 TO 10 FEET • FIRE SEPARATION > 10 FEET • FIRE SEPARATION > 30 FEET FIRE WALL (if required) TABLE 706.4
2 2 1 0 3
INTERIOR BEARING WALLS • SUPPORTING MORE THAN ON LEVEL • SUPPORTING ONE LEVEL • SUPPORTING A ROOF ONLY SMOKE BARRIERS 709.3
3 3 2 N/A
ENCLOSURE OF VERTICAL SHAFTS • 4 STORIES OR MORE 713.4
2
FLOOR CONSTRUCTION
2
ROOF CONSTRUCTION FIRE BARRIER • Fire Areas TABLE 707.3.10 • Atrium 404. • Fire Pump 913.2.1 • Fire Command Center • EXIT STAIRWAYS 1022.2 FIRE PARTITIONS • Corridor serving greater than 30 Occupants TABLE 1018.1 • Elevator Shafts SMOKE PARTITIONS
1 1/2
3 1 2 2 2 1 1 N/A
SEPARATION OF OCCUPANICIES IBC TABLE 508.4 • Non-separated mixed use building – no separation required
EXISTING REQUIREMENTS 1. OCCUPANT LOAD EXAMPLE CALCULATIONS OL = A/OLF A – Area of a space (square feet) OL – Occupant Load (number of persons) OLF – Occupant Load Factor (number of persons/square feet) o IBC (2012) Table 1004.1.2 BREWERY & TAP ROOM LEVEL 1 AREA: Total Area = 1858 SF
Equipment/Bar Area = 1138 SF
Net Area = 720 SF OLF: Assembly without fixed seats – Un-concentrated (tables and chairs) = 15 net OL:
48 persons
BUISNESS AREA LEVELS 2-3 AREA: Total Area – 6965 SF OLF: Industrial Area = 100 gross OL:
70 persons
SECONDARY POWER
FIRE ALARM APPLICABLE CODE AND STANDARD
a)
2012 International Building Code, with Kansas City, Missouri Amendments CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 907 – FIRE ALARM AND DETECTION SYSTEMS This section covers the application, installation, performance and maintenance of fire alarm systems and their components. 907.2.1 Group A 907.2.2 Group B 907.2.4 Group F (Two or more stories) 907.2.13 High-rise buildings 907.2.18 Underground buildings with smoke control systems 907.4.2 Manual fire alarm boxes 907.5 Occupant notification systems SECTION 909 – SMOKE CONTROL SYSTEMS This section applies to mechanical or active smoke control systems when they are required by other provisions of this code. 909.12 Detection and control systems
CHAPTER 4 SPECIAL DETAILED REQUIRMENTS BASED ON USE AND OCCUPANCY SECTION 403 – HIGH-RISE BUILDINGS 403.4 Emergency systems 403.6 Elevators SECTION 404 – ATRIUMS SECTION 405 – UNDERGROUND BUILDINGS
b)
2012 International Fire Code, with Kansas City, Missouri Amendments SECTION 403
c)
NFPA 72 Installation of Fire Alarm Systems
1. SYSTEM AND REPORT •
High-rise buildings shall be provided with an automatic smoke detection system and an emergency voice/alarm communication system
•
Smoke detectors shall be connected to an automatic fire alarm system that will activate the emergency voice/alarm system
•
Emergency voice/alarm communication system shall be designed and installed in accordance with NFPA 72. The operation of any automatic fire detector, sprinkler water flow or manual fire alarm box shall automatically sound an alert tone followed by voice instructions giving approved information and directions for evacuation. Speakers shall be provided throughout the building by paging zones at minimum provided as follows: I. Elevator II. Exit stairways III. Each floor
2. OTHER REQUIRMENTS • • • •
Manual override for emergency voice communication shall be provided on a selective and all-call basis The emergency voice /alarm system shall have the capability to broadcast live voice messages on a selective and all-call basis The emergency voice /alarm system shall be allowed to be used for other announcements, provided the manual fire alarm takes precedence over any other use Visible alarm notification appliances shall be provided in locations specified in notification section
3. INITIATION •
In high-rise buildings, a separate zone by floor shall be provided for each of the following types of alarm-initiating devices: I. Smoke detectors II. Sprinkler water flow devices III. Manual fire alarm boxes IV. Other approved types of automatic fire detection services
Component
Required Location
Design Specifications
Heat Detection
Elevator Machine Room & Shafts
Within 2 feet of sprinkler for Shunt
Manual Pull Stations
At each unless exempted by IBC 907
Monitor Modules
Fire Pump Connections Kitchen Hood Suppression systems Sprinkler Pressure Switches Sprinkler Tamper Switch Sprinkler Water Flow Switch
Monitoring for alarm, trouble, or supervisory adjacent to switch or system Monitoring for alarm, trouble, or supervisory adjacent to switch or system
Smoke Detection
Above Fire Alarm Equipment • Amplifier, fire Alarm Control Panel Remote Power Supply Door Release Elevator Pressurization Systems Elevator Recall Mechanical Unit Shutdown • All units/systems greater than 2,000 CFM • For systems over 15,000 CFM, at each floor level connection to riser Smoke Control System Smoke or Fire/Smoke Dampers Stairwell Pressurization Systems
Beam-Type: • Often a 60- foot spacing • Distances can get up to 400 feet Duct-Type: • At connection to unit (between unit and split) • If for damper, within 5 ft of damper Spot Types: • All portions of a covered area must be within 21 • feet (0.7x30’-0”) of a spot-type smoke detector
4. NOTIFICATION Component
Required Location
Not Required
Design Specifications
Visible Signaling (Strobes)
All public and common areas. • Assembly, Auditoriums, Cafeterias, • Classrooms, Community, Corridors, Exercise, • Exit Stairwells, Lobbies, Locker Room, Loud • Environments (>105 dBA), Gymnasiums, • Kitchens, Open Office, Parking Garages, • Private Offices (wiring only, no strobe), • Restrooms, Sleeping Areas (ADA), Storage • Areas (with working areas), Theatres, • Vestibules, Warehouses All occupiable areas
Private or non-occupied areas. • Coolers, Elevator Shafts, Escalator • Pits, Freezers, Hydrotherapy Pits, • Private Offices, Shafts, Sleeping Areas • (non-ADA), Storage Areas (without working areas)
Room Spacing: • Provide strobe spacing for entire room
Non-occupiable areas.
Provide with each strobe (unless very small space) Provide where spacing exceeds 50feet
Where designated by designer and approved by AHJ • Typically, all areas where intelligibility can • be reasonably achieved: Auditoriums, • Classrooms, Corridors, Some Lobbies, • Kitchens, Private Offices, small volumes or • areas with carpet and ceilings, Sleeping • Areas, Theatres
Areas designated by designer and approved by AHJ. • Typically, areas where intelligibility • cannot be reasonably achieved: Coolers, • Exit Stairwells, some Lobbies, • Gymnasiums, Large Volumes, Non• Occupied Areas, Parking Garages, • Restrooms
Provide with each strobe Provide more where necessary • Generally, where intelligibility can be • met, a speaker should be within each • space (even where strobes are not • provided)
Audible Notification (Horns/Speakers in nonintelligible spaces)
Intelligible Notification (Speakers)
Corridor Spacing: • Provide 15cd strobe within 15 feet of the end of a corridor • Strobe spacing no greater than 100 feet
FIRE SUPPRESSION CODE AND STANDARD REFERENCES a)
2012 International Building Code, with Kansas City, Missouri Amendments
CHAPTER 4 SPECIAL DETAILED REQUIRMENTS BASED ON USE AND OCCUPANCY SECTION 403 – HIGH-RISE BUILDINGS 403.3 Automatic sprinkler system Buildings and Structures shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and a secondary water supply where required by Section 903.3.5.2. 403.3.1 Number of sprinkler risers and system design Each sprinkler system zone in buildings that are more than 420 feet in building height shall be supplied by no fewer than two risers. 403.3.1.1 Riser location Sprinkler risers shall be placed in interior exit stairways and ramps that are remotely located in accordance with section 1015.2. 403.4.3 Standpipe system A high-rise building shall be equipped with a standpipe system as required by 905.3 SECTION 404 ATRIUMS 406.6 Enclosed Parking Garages CHAPTER 9 FIRE PROTECTION SYSTEMS 901.6.1 Automatic sprinkler systems Automatic sprinkler systems shall be monitored by an approved supervising station. 903.2.1 Group A 902.2.10 Group S-2 enclosed parking garages SECTION 903 – AUTOMATIC SPRINKLER SYSTEMS
SECTION 903.3 â&#x20AC;&#x201C; INSTALLATION REQUIRMENTS 903.2.11.3 Buildings 55 feet or more in height 903.3.1 Standards 903.3.1.1 NFPA sprinkler systems Sprinklers shall be installed in accordance with NFPA 13. 903.4.3 Floor control valves Approved supervised indicating control valves shall be provided at the point of connection to the riser on each floor in high-rise buildings SECTION 905 STANDPIPE SYSTEMS 905.2 Installation standard Standpipe systems shall be installed in accordance with NFPA 13, NFPA 14, and NFPA 20 2010 editions. 905.3.1 Height
1. SYSTEM TYPES Sprinkler system requirements shall be governed by NFPA 13 CHAPTER 7 SYSTEM REQUIRMENTS a)
A wet sprinkler system shall be placed per IBC 2012 and installed with accordance to NFPA 13 on all floors above the finished grade.
b)
A dry sprinkler system shall be placed in the closed parking garage per IBC 2012 and installed in accordance with NFPA 13 on all parking areas located below the finished grade.
2. UTILITY INFORMATION a) Per 403.3.1 Number of sprinkler risers and system design Each sprinkler system zone in buildings that are more than 420 feet in building height shall be supplied by no fewer than two risers. The height of our structure is significantly less than the codes requirement therefore there shall be only one incoming utility connection required.
b) The incoming connection shall be one 6-inch line to supply the sprinkler and standpipe system. The fire sprinkler and standpipe utility connections will be shared. 3. HAZARD CLASSIFICATION All public/common areas shall be classified per NFPA 13 CHAPTER 5 CLASSIFICATION OF OCCUPANCIES AND COMMODITIES a) 5.2 Light Hazard Occupancies. Light hazard occupancies shall be defined as occupancies or portions of other occupancies where the quantity and/or combustibility of contents is low and fires with relatively low rates of heat release are expected. (Office spaces, common areas etc.) b) 5.3.1 Ordinary Hazard (Group 1). 5.3.1.1 Ordinary hazard (Group 1) occupancies shall be defined as occupancies or portions of other occupancies where combustibility is low, quantity of combustibles is moderate, stockpiles of combustibles do not exceed 8 ft (2.4 m), and fires with moderate rates of heat release are expected. (Kitchen, mechanical room, etc.) c) 5.3.2.1 Ordinary hazard (Group 2) occupancies shall be defined as occupancies or portions of other occupancies where the quantity and combustibility of contents are moderate to high, stockpiles of contents with moderate rates of heat release do not exceed 12 ft (3.66 m), and stockpiles of contents with high rates of heat release do not exceed 8 ft (2.4 m). (Stores) AREA
HAZARD CLASSIFICATION
Parking OH-1 Garage BREWERY OH1
Storage
OH1
CODE OR STANDARD BASIS
NFPA 13 OH-1: A5.3.1 NFPA 13 Ordinary Hazard Group 1: 11.2.32 & Table 11.2.3.1.2 NFPA 13 Ordinary Hazard Group 1: 11.2.32 & Table 11.2.3.1.2
DENSITY
REMOTE AREA SIZE
HOSE ALLOWANCE
(SQ FT)
(GPM)
0.10/1500 SQ FT 0.15/1500 SQ FT
225
100
130
250
0.15/1500 SQ FT
130
250
Office Areas
LH
Dept. Store
OH2
Elevator Lobbies
LH
Open Office LH Spaces Office Equipment Areas
OH1
NFPA 13 Light Hazard: 11.2.32 & Table 11.2.3.1.2 NFPA 13 Ordinary Hazard Group 2: 11.2.32 & Table 11.2.3.1.2 NFPA 13 Light Hazard: 11.2.32 & Table 11.2.3.1.2 NFPA 13 Light Hazard: 11.2.32 & Table 11.2.3.1.2 NFPA 13 Ordinary Hazard Group 1: 11.2.32 & Table 11.2.3.1.2
0.10/1500 SQ FT
225
100
0.20/1500 SQ FT
130
250
0.10/1500 SQ FT
225
100
0.10/1500 SQ FT
225
100
0.15/1500 SQ FT
130
250
d) 4. Sprinkler Types The use and application of sprinkler types shall be governed by NFPA 13 INSTALLATION REQUIRMENTS. 8.4.1 Standard Upright and Pendent Spray Sprinklers. 8.4.1.1 Upright and pendent spray sprinklers shall be permitted in all occupancy hazard classifications and building construction types. Standard Spray Pendant Sprinklers K5.6 shall be installed wherever a dropped in ceiling occurs within the structure. Standard Spray Upright Sprinklers shall be installed whenever an exposed ceiling exists (lacking a dropped in ceiling). 5. PIPE AND TANK INFORMATION A Fire pump that is capable of handling 171.1 GPM at 57.6 PSI shall be installed in the Fire Pump Room located on the 1st floor. All necessary requirements and installation shall comply with NFPA 20. 6. FIRE STANDPIPE TYPE AND INFORMATION The fire standpipe type shall be an Automatic, Wet standpipe system with type Class I hose connections. All necessary requirements and installation shall comply with NFPA 14.
SMOKE CONTROL SYSTEM CODE AND STANDARD REFERENCES
a) 2012 International Building Code, with Kansas City, Missouri Amendments CHAPTER 4 SPECIAL DETAILED REQUIRMENTS BASED ON USE AND OCCUPANCY SECTION 403 – HIGH-RISE BUILDINGS 403.4.1 Smoke detection. Smoke Detection shall be provided in accordance with Section 907.2.13.1 403.4.7 Smoke removal 403.5.4 Smoke proof enclosures Every required exit stairway serving floors more than 75 feet above the lowest level of the fire department vehicle access shall be a smoke proof enclosure in accordance with Sections 909.20 and 1022.10 SECTION 404 - ATRIUMS 404.5 Smoke control
A smoke control system shall be installed in accordance with Section 909
SECTION 405 – UNDERGROUND BUILDINGS
Exception: - Parking garages provided with an automatic sprinkler system
CHAPTER 9 FIRE PROTECTION SYSTEMS
SECTION 909 â&#x20AC;&#x201C; SMOKE CONTROL SYSTEMS
909.20 Smoke proof enclosures
SECTION 910 SMOKE AND HEAT REMOVAL b) NFPA 101 Life Safety Code 2010 c) NFPA 92 Standard for Smoke Control Systems 2010
APPENDIX A FIRE MODEL CODE AND STANDARD REFERENCES The fire package in the fire model consisted of two couches on two sides of the room. Due to the small dimensions of the space and the fire package a ramped function was used in order to elicit heat release rate. This heat release rate was further broken down into the three types of heat transfer, convection, conduction and radiation, to show minimum evacuation time versus temperature that would allow a person to exit the room safely. This tenability criteria according to SFPE handbook a room becomes untenable when the following occur: -
Temperature exceeds 250°F
-
The heat flux exceeds 2.5 kW/m2
-
Minimum Oxygen level of 19%
PERFORMANCE GOALS An addition temperature thermocouple was added closure to the couch. The chart below displays the resulting temperature of the model over an elapsed time of 200 seconds.
Temperature Thermocouple THCP06 900.00 800.00 700.00
Temperature (°F)
600.00 500.00 400.00 300.00 200.00 100.00 0.00
0.00
50.00
100.00
150.00 Time
FIGURE 1
MODEL OUTPUT GRAPHS AND IMAGES
200.00
250.00
Heat Release Rate 6000.00 5000.00
Heat (kw)
4000.00 3000.00 2000.00 1000.00 0.00
0.00
50.00
100.00
150.00
200.00
250.00
Time
FIGURE 2 HEAT RELEASE RATE
Chart Title 500.00 0.00 -500.00
0.00
50.00
100.00
150.00
200.00
-1000.00 -1500.00 -2000.00 -2500.00 -3000.00 -3500.00 kW Q_RADI
FIGURE 3 TYPES OF HEAT RELEASE
kW Q_CONV
kW Q_COND
250.00
APPENDIX B MODEL LANGUAGE &HEAD CHID='FireModelingIntro'/ &TIME T_END=200.0/ &DUMP RENDER_FILE='RoomFireEx.ge1', COLUMN_DUMP_LIMIT=.TRUE., DT_RESTART=300.0/ &MESH ID='Mesh01', IJK=52,54,24, XB=0.0,5.2,-0.8,4.6,0.0,2.4/ &REAC ID='POLYURETHANE', FYI='NFPA Babrauskas', FUEL='REAC_FUEL', C=6.3, H=7.1, O=2.1, N=1.0, SOOT_YIELD=0.1/ &PROP ID='Cleary Ionization I1', QUANTITY='CHAMBER OBSCURATION', ALPHA_E=2.5, BETA_E=-0.7, ALPHA_C=0.8, BETA_C=-0.9/ &CTRL ID='Smoke detector control', FUNCTION_TYPE='ALL', LATCH=.TRUE., INPUT_ID='Smoke Detector'/ &DEVC ID='Smoke Detector', PROP_ID='Cleary Ionization I1', XYZ=2.5,2.0,2.3/ &DEVC &DEVC &DEVC &DEVC &DEVC &DEVC &DEVC
ID='THCP', QUANTITY='THERMOCOUPLE', XYZ=2.6,2.3,2.1/ ID='THCP01', QUANTITY='THERMOCOUPLE', XYZ=2.6,2.3,1.8/ ID='THCP02', QUANTITY='THERMOCOUPLE', XYZ=2.6,2.3,1.5/ ID='THCP03', QUANTITY='THERMOCOUPLE', XYZ=2.6,2.3,1.2/ ID='THCP04', QUANTITY='THERMOCOUPLE', XYZ=2.6,2.3,0.9/ ID='THCP05', QUANTITY='THERMOCOUPLE', XYZ=2.6,2.3,0.6/ ID='THCP06', QUANTITY='THERMOCOUPLE', XYZ=2.7,2.4,0.7/
&DEVC ID='LAYER->HEIGHT', QUANTITY='LAYER HEIGHT', XB=2.6,2.6,2.3,2.3,0.0,2.4/ &DEVC ID='LAYER->LTEMP', QUANTITY='LOWER TEMPERATURE', XB=2.6,2.6,2.3,2.3,0.0,2.4/ &DEVC ID='LAYER->UTEMP', QUANTITY='UPPER TEMPERATURE', XB=2.6,2.6,2.3,2.3,0.0,2.4/ &MATL ID='Fabric',
SPECIFIC_HEAT=1.0, CONDUCTIVITY=0.1, DENSITY=100.0, HEAT_OF_COMBUSTION=1.5E4, N_REACTIONS=1, HEAT_OF_REACTION=1000.0, SPEC_ID(1,1)='REAC_FUEL', NU_SPEC(1,1)=1.0, REFERENCE_TEMPERATURE=280.0/ &MATL ID='FOAM', FYI='Caution: Reaction Rate Not Validated, remaining data from Jukka Hietaniemi, et al., "FDS simulation of fire spread..."', SPECIFIC_HEAT=1.0, CONDUCTIVITY=0.05, DENSITY=40.0, HEAT_OF_COMBUSTION=3.0E4, N_REACTIONS=1, HEAT_OF_REACTION=800.0, SPEC_ID(1,1)='REAC_FUEL', NU_SPEC(1,1)=1.0, REFERENCE_TEMPERATURE=300.0/ &MATL ID='GYPSUM', FYI='NBSIR 88-3752 - ATF NIST Multi-Floor Validation', SPECIFIC_HEAT=1.09, CONDUCTIVITY=0.17, DENSITY=930.0/ &MATL ID='YELLOW PINE', FYI='Quintiere, Fire Behavior - NIST NRC Validation', SPECIFIC_HEAT=2.85, CONDUCTIVITY=0.14, DENSITY=640.0/ &SURF ID='Upholstery', RGB=120.0,116.0,110.0, BURN_AWAY=.TRUE., BACKING='INSULATED', MATL_ID(1,1)='Fabric', MATL_ID(2,1)='FOAM', MATL_MASS_FRACTION(1,1)=1.0, MATL_MASS_FRACTION(2,1)=1.0, THICKNESS(1:2)=0.002,0.1/ &SURF ID='Gypsum', RGB=198.0,225.0,230.0, BACKING='VOID', MATL_ID(1,1)='GYPSUM', MATL_MASS_FRACTION(1,1)=1.0, THICKNESS(1)=0.013/
&SURF ID='Pine', RGB=146.0,202.0,166.0, TEXTURE_MAP='psm_wood2.jpg', TEXTURE_WIDTH=0.6096, TEXTURE_HEIGHT=0.6096, BACKING='VOID', MATL_ID(1,1)='YELLOW PINE', MATL_MASS_FRACTION(1,1)=1.0, THICKNESS(1)=0.01/ &SURF ID='Fire', COLOR='RED', HRRPUA=1000.0/
&VENT ID='Fire Vent', SURF_ID='Fire', XB=-1.0,1.0,-1.5,1.5,0.2,0.2 /
&OBST ID='Seat cushion', XB=1.5,3.1,3.8,4.6,0.2,0.6, SURF_ID='Upholstery'/ &OBST ID='Right armrest', XB=1.3,1.5,3.8,4.6,0.0,0.9, SURF_ID='Upholstery'/ &OBST ID='Left armrest', XB=3.1,3.3,3.8,4.6,0.0,0.9, SURF_ID='Upholstery'/ &OBST ID='Back cushion', XB=1.5,3.1,4.4,4.6,0.6,1.2, SURF_ID='Upholstery'/ &OBST ID='Seat cushion', XB=8.88178E-16,0.8,1.2,2.8,0.2,0.6, SURF_ID='Upholstery'/ &OBST ID='Right armrest', XB=4.44089E-16,0.8,1.0,1.2,0.0,0.9, SURF_ID='Upholstery'/ &OBST ID='Left armrest', XB=8.88178E-16,0.8,2.8,3.0,0.0,0.9, SURF_ID='Upholstery'/ &OBST ID='Back cushion', XB=8.88178E-16,0.2,1.2,2.8,0.6,1.2, SURF_ID='Upholstery'/ &OBST ID='Pad', XB=1.6,3.0,2.4,3.2,0.0,0.2, SURF_ID='Upholstery'/ &OBST ID='Wall', XB=0.0,5.2,-0.2,-1.94289E-16,0.0,2.4, SURF_ID='Gypsum'/ &OBST ID='Fire Obstruction', XB=-1.0,1.0,-1.5,1.5,0.0,0.2, SURF_ID='INERT'/
&HOLE ID='Door', XB=4.0,4.9,-0.3,0.1,-0.01,2.0/ &VENT ID='Mesh Vent: Mesh01 [YMIN]', SURF_ID='OPEN', XB=0.0,5.2,-0.8,0.8,0.0,2.4/ &VENT ID='Mesh Vent: Mesh01 [ZMAX]', SURF_ID='OPEN', XB=0.0,5.2,0.8,0.0,2.4,2.4/ &VENT ID='Floor', SURF_ID='Pine', XB=0.0,5.2,0.0,4.6,0.0,0.0/ &VENT ID='Back Wall', SURF_ID='Gypsum', XB=0.0,5.2,4.6,4.6,0.0,2.4/ &VENT ID='Left Wall', SURF_ID='Gypsum', XB=0.0,0.0,0.0,4.6,0.0,2.4/ &VENT ID='Right Wall', SURF_ID='Gypsum', XB=5.2,5.2,0.0,4.6,0.0,2.4/ &VENT ID='Ceiling', SURF_ID='Gypsum', XB=0.0,5.2,0.0,4.6,2.4,2.4/
&BNDF QUANTITY='WALL TEMPERATURE'/ &SLCF QUANTITY='TEMPERATURE', PBX=2.6/ &SLCF QUANTITY='VELOCITY', VECTOR=.TRUE., PBX=4.45/
&TAIL /
LIFE SAFETY SYMBOLS
F.E.
FIRE ALARM SYMBOLS MB
FIRE ALARM MASTER BOX
DH
MAGNETIC DOOR HOLD OPEN DEVICE
KS
GLOBAL HVAC SHUTDOWN SWITCH/BUTTON
PS
PRESSURE DETECTOR/SWITCH
WF
WATERFLOW DETECTOR/SWITCH
TS
TAMPER SWITCH
AOM
ADDRESSABLE OUTPUT CONTROL MODULE
AIM
ADDRESSABLE INPUT MONITOR MODULE
SS
SINGLE STATION SMOKE ALARM
S
SMOKE DETECTOR
S
ID
FIRE ALARM CONTROL PANEL
FACP
HEAT DETECTOR
LOCAL OPERATING CONSOLE WITH MICROPHONE
LOC
RECESSED FIRE ALARM CONTROL PANEL
FACP
FIRE ALARM ANNUNCIATOR PANEL
FAA
F
BELL
F
PULL STATION/FIRE ALARM BOX
M CD
RECESSED FIRE ALARM ANNUNCIATOR PANEL
FAA
M CD
FIRE ALARM TRANSPONDER, # INDICATES UNIT NUMBER
TPR#
SMOKE DETECTOR/SENSOR - IN DUCT
MASS NOTIFICATION COMBINATION VISIBLE WHITE/AMBER (STROBE) - CEILING MOUNT MASS NOTIFICATION COMBINATION VISIBLE WHITE/AMBER (STROBE) - WALL MOUNT
RI
REMOTE TEST STATION WITH INDICATING LIGHT
CD
VISIBLE ONLY (STROBE) - WALL MOUNT
AMPLIFIER PANEL
AMP NAC#
# INDICATES UNIT NUMBER NOTIFICATION CIRCUIT POWER BOOSTER EXTENDER PANEL
S
SPEAKER ONLY - CEILING MOUNT
S
SPEAKER ONLY - WALL MOUNT FIRE SERVICE OR EMERGENCY PHONE STATION JACK
ANNOTATION 1
1 M1
FIRE PROTECTION PLAN CALLOUT
CO
COMBINATION SPEAKER, VISIBLE CEILING MOUNT
CONNECTION POINT OF NEW WORK TO EXISTING DETAIL REFERENCE UPPER NUMBER INDICATES DETAIL NUMBER LOWER NUMBER INDICATES SHEET NUMBER
COMBINATION SPEAKER, VISIBLE WALL MOUNT RTS
1 M1
SECTION CUT DESIGNATION
ETR FHC FP GC GPM JB MAX MIN N/A
ABOVE FINISHED FLOOR ABOVE FINISHED GRADE CANDELA DUCTILE IRON EARLY SUPPRESSION FAST RESPONSE EXISTING TO REMAIN FIRE HOSE CABINET FIRE PROTECTION CONTRACTOR GALLONS PER MINUTE JUNCTION BOX MAXIMUM MINIMUM NOT APPLICABLE
A
REMOTE TEST STATION WITH INDICATING LIGHT ABORT SWITCH VISIBLE ONLY (STROBE) - CEILING MOUNT
ABBREVIATIONS AFF AFG CD DI ESFR
GAS DETECTOR/SENSOR CO INDICATES CARBON MONOXIDE
NIC NOT IN CONTRACT OC ON CENTER PIV POST INDICATOR VALVE PROVIDE FURNISH AND INSTALL PRV PRESSURE REDUCING VALVE RD RETURN DUCT REV REVISION SD SUPPLY DUCT SF SQUARE FEET TYP TYPICAL UL UNDERWRITERS LABORATORIES, INC. UNO UNLESS NOTED OTHERWISE V VOLT(S) WP WEATHERPROOF
STANDARD MOUNTING HEIGHTS (AFF, AFG, UNLESS NOTED OTHERWISE) FIRE ALARM AUDIBLE APPLIANCES (CENTERLINE) FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) FIRE ALARM BELL (EXTERIOR) FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) PULL STATIONS (HANDLE) VISIBLE APPLIANCES (CENTERLINE)
84" 60" 120" 60" 48" 84"
FIRE SUPPRESSION SYMBOLS
S S S
S S
S
S
S
ROOF LEVEL
FF LEVEL SEVENTEEN
FF LEVEL SIXTEEN
FF LEVEL FIFTEEN
FF LEVEL FOURTEEN
FF LEVEL THIRTEEN
FF LEVEL TWELVE
FF LEVEL ELEVEN
FF LEVEL TEN
FF LEVEL NINE
ROOF LEVEL
FF LEVEL EIGHT
FF LEVEL SEVEN
FF LEVEL SIX
FF LEVEL FIVE
FF LEVEL FOUR
FF LEVEL THREE
FF LEVEL TWO
FF LEVEL ONE
FF LEVEL SEVENTEEN
FF LEVEL B1
FF LEVEL B2
FF LEVEL B3
FF LEVEL B4
FF LEVEL B5
FF LEVEL SIXTEEN
FF LEVEL FIFTEEN
FF LEVEL FOURTEEN
FF LEVEL THIRTEEN
FF LEVEL TWELVE
FF LEVEL ELEVEN
FF LEVEL TEN
FF LEVEL NINE
FF LEVEL EIGHT
FF LEVEL SEVEN
FF LEVEL SIX
FF LEVEL FIVE
FF LEVEL FOUR
FF LEVEL THREE
FF LEVEL TWO
FF LEVEL ONE
FF LEVEL B1
FF LEVEL B2
FF LEVEL B3
FF LEVEL B4
FF LEVEL B5
S DH S
S DH
DH
1.
2.
PROVIDE EQUIPMENT AND CONNECTION(S) REQUIRED FOR ELEVATOR RECALL. HEAT DETECTION SHALL BE INSTALLED IN ELEVATOR MACHINE ROOM & SHAFTS WITHIN 2 FEET OF SPRINKLER FOR SHUNT.
AMP S
2 S
1
S DH
S
S
S
MB AMP S
FACP KS
S
2
1.
PROVIDE EQUIPMENT AND CONNECTION(S) REQUIRED FOR ELEVATOR RECALL.
2.
HEAT DETECTION SHALL BE INSTALLED IN ELEVATOR MACHINE ROOM & SHAFTS WITHIN 2 FEET OF SPRINKLER FOR SHUNT.
1
S DH
S
2 1.
PROVIDE EQUIPMENT AND CONNECTION(S) REQUIRED FOR ELEVATOR RECALL.
2.
HEAT DETECTION SHALL BE INSTALLED IN ELEVATOR MACHINE ROOM & SHAFTS WITHIN 2 FEET OF SPRINKLER FOR SHUNT.
1
S DH
S
2 1.
PROVIDE EQUIPMENT AND CONNECTION(S) REQUIRED FOR ELEVATOR RECALL.
2.
HEAT DETECTION SHALL BE INSTALLED IN ELEVATOR MACHINE ROOM & SHAFTS WITHIN 2 FEET OF SPRINKLER FOR SHUNT.
1
1.
APPROVED SUPERVISED INDICATING CONTROL VALVES SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE RISER ON EACH FLOOR.
1
1.
APPROVED SUPERVISED INDICATING CONTROL VALVES SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE RISER ON EACH FLOOR.
1
1.
APPROVED SUPERVISED INDICATING CONTROL VALVES SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE RISER ON EACH FLOOR.
10'AFF 1
1.
APPROVED SUPERVISED INDICATING CONTROL VALVES SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE RISER ON EACH FLOOR.
SECTION 16C FIRE ALARM SYSTEM: 16C GENERAL 16C GENERAL REQUIRMENTS
APPLIANCE CIRCUIT; SEMI-FLUSH MOUNTING; FOUR INCH CONE; HIGH IMPACT, FLAME RETARDANT PC/ABS THERMOPLASTIC; 25 OR 70 VRMS; MULTI-TAPPED
THE WORK COVERED BY THIS SECTION OF THE SPECIFICATIONS INCLDUES THE FURNISHING OF ALL
OUTPUT POWER RATED ¼ TO 2 WATTS AND PRODUCE 79 TO 88 DB AT 10 FEET.
LABOR, EQUIPMENT AND MATERIAL AS HEREIN SPECIFIED.
VISIBLE ALARM NOTIFICATON APPLIANCES (STROBES): STROBES SHALL BE XENON OR EQUIVALENT,
16C SCOPE OF WORK
UNFILTERED OR CLEAR FILTERED WHITE LIGHT, A
THE SCOPE OF WORK IN THIS SECTION INCLUDES:
MINIMUM INTENSITY OF 15/75 CANDELA AND AS
AUTOMATIC SMOKE DETECTORS; FIRE ALARM
INDICATED ON DRAWINGS, FLASH RATE CHANGE
NOTIFICATION APPLIANCES; BATTERY STAND POWER.
FROM 1 TO 3 HZ, A MAXIMUM PULSE DURATION OF 0.2
16C EQUIPMENT
SEC WITH A MAXIMUM DUTY CYCLE OF 40%. STROBE
THE FIRE ALARM SYSTEM SHALL BE A MICROPROCESSORBASED SYSTEM DESIGNED SPECIFICALLY DESIGNED FOR
SHALL MEET ALL REQUIRMENTS OF THE AMERICANS WITH DISABILITES ACT.
FIRE APLLICATIONS. THE SYSTEM SHALL BE UL LISTED
AUDIBLE/VISBLE ALARM NOTIFICATIONS APPLIANCES
UNDER STANDARDS 864 (CONTROL UNITS FOR
(SPEAKER/STROBES): COMBINATION UNITS SHALL
FIRE-PROTECTIVE SIGNALING SYSTEMS).
PROVIDE A COMMON ENCLOSURE FOR THE FIRE ALARM
THE CONTROL PANEL AND REMOTE ANNOUNCER PANEL SHALL HAVE DEDICATED ALARM, SUPERVISORY AND TROUBLE LED'S AND DEDICATED ALARM, SUPERVISORY AND TROUBLE ACKNOWLEDGEMENT SWITCHES. 16C INITIATING DEVICES SMOKE DETECTOR (PHOTOELECTRIC TYPE): DEVICE SHALL HAVE VISIBLE INDICATION OF DETECTOR
AUDIBLE SYSTEM AND VISIBLE ALARM APPLIANCES AND BE UL LISTED FOR ITS PURPOSE. MINIMUM AUDIBLE LEVEL AND STROBE INTENSITY SHALL MEET ALL REQUIREMENTS FOR SEPARATE APPLIANCES. PROVIDE FLUSH OR RECESSED DEVICES UNLESS OTHERWISE NOTED. 16C INSTALLATION INSTALL CEILING MOUNTED INITIATING DEVICES IN
ACTUATION, SELF-RESTORING, PLUG-IN WITH AN
AREAS WITH EXPOSED STRUCTURE TIGHT TO
INTEGRAL ADDRESSABLE MODULE INDICATING THE
UNDERSIDE OF FLOOR/ROOF DECK.
DETECTOR STATUS. PHOTOELECTRIC DETECTORS
INSTALL CEILING MOUNTED VISIBLE AND AUDIO/VISIBLE
SHALL HAVE SENSITIVITY BETWEEN 0.5 AND 3.5
NOTIFICATION APPLIANCES IN AREAS WITH EXPOSED
PERCENT/FOOR SMOKE OBSCURATION.
STRUCTURE TO BOTTOM OF FLOOR/ROOF STRUCTURE
16C NOTIFICATION APPLIANCES
OR AT 30 FT AFF, WHICHEVER IS LOWER.
ALARM SPEAKERS: UL 1480 LISTED; HIGH QUALITY TONE
PROVIDE STROBE SYCHRONIZATION AS REQUIRED PER
AND VOICE REPRODUCTION; CAPACITOR CONNECTED
NFPA 72.
FOR CONNECTION TO SUPERVISED NOTIFICATION