3 minute read
GENERATORS
HOSPITAL IN THE NORTH OF ENGLAND INSTALLS THREE DIESEL GENERATORS
KoEnrogen has designed, installed, and also commissioned three 600kVA diesel generators, and a switchboard & permanent loadbank unit at a hospital in northern England. The Enrogen generator sets were built with MTU 12V1600G20F engines (400 – 230 V/662 kVA/50 Hz/prime power/ series 1600 – 12V1600) coupled to Leroy Somer
LSA49.3S4 alternators with acoustic attenuation rated at 70dBA @ 1mtr. Also provided were ComAp controls for set-to-set synchronising with n+1 configuration.
The Nidec Leroy-Somer LSA 49.3 alternator has been designed to offer you the best power generation performances, says the manufacturer. With its meticulous design and optimised architecture, the
LSA 49.3 is said to ‘strike the perfect balance between compactness, reliability, performance and longevity’.
Whatever your application, the LSA 49.3 will meet your needs and will adapt to all situations, says the company.
The Nidec Leroy-Somer LSA 49.3 alternator meets all key international standards and regulations, including
IEC 60034, NEMA MG 1.32-33, ISO 8528-3, CSA C22.2 n°100-14 and UL 1446 (UL 1004 on request). Also compliant with IEC 61000-6-2, IEC 61000-6-3, IEC 61000-6-4, VDE 0875G, VDE 0875N and EN 55011, group 1 class A for European zone.
The Nidec Leroy-Somer LSA 49.3 alternator can be integrated in EC marked generator set, and bears EC,
EAC and CMIM markings. It is designed, manufactured and marketed in an ISO 9001 and ISO 14001 quality assurance environment.
The MTU 12V1600G20F engine The engine offers an industry-leading average load factor and low fuel consumption. Emissions optimisations are available and the equipment provides high availability and reliability, outstanding load acceptance and long maintenance intervals. The engine-generator set is designed and manufactured in facilities certified to standards ISO 2008:9001. The Generator set complies with ISO 8528 and fullfills performance level G3. The generator meets BS5000; NEMA MG 1; ISO; DIN EN and IEC standards and comes with a 4P circuit breaker, island operation control panel, integrated fuel tank, industrial silencer (15 dB(A)) and batteries & battery charger. Special features The Enrogen-built switchboard was designed to fit within the plant room with the generators. A temporary switchboard was used during the cable migration so the hospital could continue operations whilst keeping shut-downs to a minimum; this was achieved out of normal working hours. The fuel system was designed and arranged for 72-hr running with a recirculating system from the Enrogen-built underbase 10hr-day tanks back to the bulk tank for fuel polishing. An ASCO (Froment) Permanent Loadbank was supplied so the generators can be tested individually or synchronised together. ASCO loadbanks use market-leading SIGMA Control to provide features and benefits for any load bank application. Formed in 2005, Enrogen specialises in the manufacture of diesel generators for the world market. The company offers a comprehensive range of generator services for end users, OEMs, dealers, and distributors both nationally and internationally.
www.enrogen.com
TRUSTED KNOWLEDGE. TAILORED SOLUTIONS.
If you have concerns about fuel quality, speak to an experienced IPU fuel expert about our industry-leading fuel and environmental managed services.
We can offer everything you need to keep your fuel in peak condition from environmental compliance through OFTEC surveys to subsequent remedial recommendations, installation of polishing systems and scheduled maintenance routines. And, as a leading OEM in fuel systems, we are in a unique position to design and manufacture the solution most tailored to your needs.