ClimaCheck™ Performance-analyser 8:7

Analysing of Refrigeration, air-conditioning and heat pump system ¾

Performance inspection and energy optimisation

¾

Speed up commissioning and reduce warranty costs

¾

Effective trouble shooting

¾

Documented maintenance with detailed information of all parameters

ClimaCheck Performance-analyser 8:7 is a specialised “intelligent” data collection unit specially developed to facilitate cost effective supervision of refrigeration-, air-conditioning units and heat pumps together with the ClimaCheck software. The unit is a versatile data logger that can be used for performance control of almost any type of compressor based refrigeration process. Performance Analyser is available as DIN mounted unit or as a complete field service system. Communication with the Performance-analyser can be done through direct, modem or internet connection. The unit has an advanced integrated alarm function.

Performance control Performance evaluation and detection of wear or problems with any of the component in the systems can be done with the ClimaCheck software based on the measurement in the refrigeration circuit and calculation with thermodynamic

Subcool in condenser Heat transfer and temperature differences in condenser and evaporator Flow in condenser and evaporator Optimise control and verify COP performance during actual operation

properties. The well proven method allow accurate

Communication

calculations of all relevant performance

ClimaCheck is capable of utilising state of the art

characteristic in the system. Through the measured

technologies to send data through direct

data ClimaCheck is capable of analysing

connection to a computer or different types of

performance of the refrigeration process and

modem such as fixed lines, GSM and GPRS. The

controls including:

logger can save data and send it in batches or

COP cooling and heating

transmit data as it is scanned. The ClimaCheck

Capacity cooling and Heating

Performance-analyser 8:7 can change recording

Compressor efficiency to detect any wear in

interval depending on operation conditions such as

compressor

compressor on or off to optimise storage capacity

Superheat in evaporator

May 2005


and data traffic to for example a web server in real

Sensor placement for a standard system is

time on GPRS.

displayed below.

Advanced Alarm Capability The Performance-analyser can also send SMS

TT_SecW_in [ 6 ]

TT_Rexp_in [ 3 ]

messages via a Web server to desired recipients

TT_SecW_out [ 7 ]

PT_RHP [ AI1 ] TT_RComp_out [ 1 ] EP [AI3 ]

according to a programmed schedule. The messages can be tailored after the occurring event

PT_RLP [ AI2 ]

and it is possible to schedule several numbers

TT_RComp_in [ 2 ]

depending on time of day/week. Temperature, Pressure and Power Input

TT_SecC_out [ 5 ]

TT_SecC_in [ 4 ]

ClimaCheck Performance-analyser 8-7 has eight temperature channels that measure desired temperatures on the refrigeration- and secondary systems and seven analogue input channels for

Sensors used for “standard” ClimaCheck analyses.

sensors with voltage or current signals. It can be

Proven Method

used for almost all relevant measurements in most

The method to calculate performance based on

refrigeration or heat pump systems.

measurements in the refrigeration circuit was

Most common sensors used are pressure-, power-

patented in 1986 and the easy to use and inherent

and humidity transducers. This will be sufficient for

good accuracy compared to alternative methods

a full evaluation of all components in a refrigeration

was verified by several manufacturers, universities

system.

and the Swedish Research and Testing Institute (SP).

ClimaCheck Software ClimaCheck software accurately analyses data collected with the Performance-analyser see special information or visit web site www.climacheck.com .

ΓΙΑ ΠΕΡΙΣΣΟΤΕΡΕΣ ΠΛΗΡΟΦΟΡΙΕΣ ΕΠΙΚΟΙΝΩΝΗΣΤΕ ΜΕ ΤΗΝ ΕΤΑΙΡΕΙΑ ΣΟΛΔΑΤΟΣ

ClimaCheck developed and distributed by:

FOR INFORMATION PLEASE CONTACT SOLDATOS COMPANY

ClimaCheck Sweden AB Nysätravägen 24 S-131 33 Nacka Tel.: +46 (0)8-55 61 55 75 E-mail: info@berglof-kylteknologi.se Web: www.berglof-kylteknologi.se

May 2005


Specifications ClimaCheck™ Performance Analyser 8:7

ClimaCheck Performance Analyser 8:7 to the left DIN rail mounted to the right field inspection unit with built in power transformer.

Analogue Inputs

Temperature inputs

7 analogue inputs with 12 bit resolution

8 PT1000 temperature inputs covering the range of

Each input can be programmed to be either a 4-

-50 to +150 degC.

20mA current input or a 0-2.5V or a 0-5V input. 3

Each input has a discriminator capable of

inputs are software switchable between current and

transforming the analogue value into a digital

voltage input the other 4 require jumpers. The

value. The discriminator can be set to operate as a

switch between 0-2.5V and 0-5V is controlled by

simple switch or a window. The digital value can

software.

be set to be true if the input is above or below the

Each input has a discriminator capable of

switch threshold or within or outside the window.

transforming the analogue value into a digital

Hysteresis is used to prevent spurious switching

value. The discriminator can be set to operate as a

around the thresholds.

simple switch or a window. The digital value can

Programmable delay from 0 to 255 seconds for

be set to be true if the input is above or below the

each input

switch threshold or within or outside the window.

Programmable analogue sampling rate from once

Hysteresis is used to prevent spurious switching

per second to one sample every 18 hours.

around the thresholds.

Input averaging. The analogue inputs can be set

Programmable delay from 0 to 255 seconds for

to record either the average value over the logging

each input

period or the instantaneous value when a log is

Programmable analogue sampling rate from once

taken.

per second to one sample every 18 hours. Input averaging. The analogue inputs can be set

Digital Inputs

to record either the average value over the logging

8 digital inputs are fully optically isolated in pairs.

period or the instantaneous value when a log is

Optically isolated inputs can have onboard pullup

taken.

resistors switched in but this negates the isolation. All inputs have led status indication when using internal pullups.

Maj 2005


Input accepts a switch closure to ground with an

Alarm escalation programmable on each alarm.

onboard switchable pullup resistor.

Disabled phone numbers are automatically

32 bit counter associated with each input. The

excluded from the escalation.

counter counts the positive transitions on an input.

Programmable delay time for each alarm.

Counters can be selectively logged.

Alarm inputs can be derived from digital inputs,

Counters can be reset at each logging interval or

digital variables, analogue inputs or timeclocks.

by a signal derived from any digital input, digital

Optional daily alarm limit preventing excessive

variable, analogue input or timeclock.

SMS phone bills.

Counters are scaled using user defined scale

User programmable number of retries.

factors and units.

User programmable time between retries.

Each counter can set a predefined digital variable if the either the input frequency exceeds a user

Logic functions

defined value or if the counts exceed a used

8 logic functions each with 4 inputs and 4 AND/OR

defined count. Each input has it's own digital

arrays.

variable.

Logic function inputs can be derived from digital

Each counter has a second digital variable which

inputs, digital variables, analogue inputs or

will give an early warning of a possible excess

timeclocks. Logic function output can be inverted

frequency or excess count condition.

Digital Outputs

Delay functions

3 open collector MOSFET outputs

4 delay functions each capable of generating one of

Each output can be driven from a signal derived

3 types of output: Delayed turn on, Fixed width

from any digital input, digital variable, analogue

output or Input stretching.

input or timeclock.

Delay function can be programmed to operate from

The switches can handle loads of 100mA with

either the rising or falling edge of the input.

voltages up to 25Volts.

Logic function inputs can be derived from digital

Digital Variables

inputs, digital variables, analogue inputs or

48 digital variables accept outputs from the

Delay times from 1 to 255 seconds.

internal functions.

timeclocks.

All digital variables can be used as inputs to any

Timeclocks

function.

8 separate time/action events during the day.

2 logical OR functions allowing combining of

4 daily schedules.

variables.

6 weekly schedules with public holiday override.

Edge detector

These schedules can be used by other functions.

One edge detector which detects the rising edge of

8 public holidays.

either a digital input, digital variable, analogue

Counter functions

input or timeclock.

2 16 bit counters.

Alarms

Counter inputs can be derived from digital inputs,

Alarms are reported by SMS messages.

Alarm generation capability if count exceeds a user

16 alarms.

defined limit.

8 separate phone numbers.

Counters can be preset to any value.

Phone numbers can be selectively enabled by

Counters can be cleared by any digital input, digital

weekly schedules.

variable, analogue input or timeclock.

Maj 2005

digital variables, analogue inputs or timeclocks.


Logging

GPS location

256kbytes of logging memory. Each analogue input

A GPS receiver can be incorporated into the system

can be selectively logged. Each digital counter can

and location will be stored in the log.

be selectively logged. All log entries are time

SMS command can read out the current device

stamped with a resolution of 1 second. All alarms

location.

are logged. All re-program events are logged. All

Accepts all standard GPS modules which transmit

changes to the input limits are logged together

NMEA sentences at either 4800 or 9600baud.

with the users phone number. Logging intervals selectable from 5 minutes to 1 hour synchronised

Sensor power control

to cardinal times with optional capability to log at

MOSFET switched power supply to external

rates from 5 seconds to 255 seconds interval in 1

sensors. Programmable sensor power on delay

second steps. Logging rate can be controlled by

from 30ms up to 160secs. Programmable analogue

any digital input, digital variable, analogue input or

sample rate from once/sec down to 1 sample every

timeclock. Capability to output logged data as a csv

18 hours.

style frame each time a logged sample is stored.

Communication

Modem power control Capability of powering the modem on/off.

Standard RS232 communications at 9600baud.

Capability of waking the modem up on a regular

SMS commands using a GSM modem. GPRS

schedule to allow for remote access. Capability of

connection supported. Logged data can be output

waking the modem up to send a SMS message.

as it is gathered. Transmission format can be in

Capability of powering the modem on at regular

straight ASCII including units etc or can be

intervals to automatically upload data to remote

compressed to varying degrees.

server via GPRS.

SMS command capability

Physical

Remote interrogation of analogue inputs with the

Dimensions:

values being returned in engineering units.

mounted housing 151 x 82.5 x 12mm (H x W x L)

Remote interrogation of analogue input limits,

Power:

digital inputs and outputs. Remote interrogation of

Current consumption varies depending on the

phone numbers. Can change phone numbers.

configuration from 10µA up to about 50µA.

Can change analogue input limits. Can disable or

Environmental: -20 to +50 degC. 5 to 95%

enable all alarms. Can remotely turn on or off any

humidity non-condensing.

digital output. Can remotely acknowledge an alarm

Power control of analogue sensors:

and cancel escalation. Can change the holiday list.

Switched incoming supply via series MOSFET.

Can be supplied in a DIN rail 12 VDC to 16VDC @ 40µA nominal.

Can read device location if a GPS module is

Maximum load current: 100mA

incorporated into the system. Acknowledgement of

Maximum series resistance: 10ohm

all SMS messages. _________________________________________________________________________________________

ΓΙΑ ΠΕΡΙΣΣΟΤΕΡΕΣ ΠΛΗΡΟΦΟΡΙΕΣ ΕΠΙΚΟΙΝΩΝΗΣΤΕ ΜΕ ΤΗΝ ΕΤΑΙΡΕΙΑ ΣΟΛΔΑΤΟΣ

ClimaCheck is developed FOR INFORMATION COP-Analyser PLEASE CONTACT SOLDATOS COMPANY

ClimaCheck Sweden AB Nysätravägen 24 S-131 33 Nacka, Sweden Tel.: +46 (0)8-55 61 55 75 E-mail: info@climacheck.com, Web: www.climacheck.com

Maj 2005