ClimaCheck™ Performance-analyser 8:7
Analysing of Refrigeration, air-conditioning and heat pump system ¾
Performance inspection and energy optimisation
¾
Speed up commissioning and reduce warranty costs
¾
Effective trouble shooting
¾
Documented maintenance with detailed information of all parameters
ClimaCheck Performance-analyser 8:7 is a specialised “intelligent” data collection unit specially developed to facilitate cost effective supervision of refrigeration-, air-conditioning units and heat pumps together with the ClimaCheck software. The unit is a versatile data logger that can be used for performance control of almost any type of compressor based refrigeration process. Performance Analyser is available as DIN mounted unit or as a complete field service system. Communication with the Performance-analyser can be done through direct, modem or internet connection. The unit has an advanced integrated alarm function.
Performance control Performance evaluation and detection of wear or problems with any of the component in the systems can be done with the ClimaCheck software based on the measurement in the refrigeration circuit and calculation with thermodynamic
Subcool in condenser Heat transfer and temperature differences in condenser and evaporator Flow in condenser and evaporator Optimise control and verify COP performance during actual operation
properties. The well proven method allow accurate
Communication
calculations of all relevant performance
ClimaCheck is capable of utilising state of the art
characteristic in the system. Through the measured
technologies to send data through direct
data ClimaCheck is capable of analysing
connection to a computer or different types of
performance of the refrigeration process and
modem such as fixed lines, GSM and GPRS. The
controls including:
logger can save data and send it in batches or
COP cooling and heating
transmit data as it is scanned. The ClimaCheck
Capacity cooling and Heating
Performance-analyser 8:7 can change recording
Compressor efficiency to detect any wear in
interval depending on operation conditions such as
compressor
compressor on or off to optimise storage capacity
Superheat in evaporator
May 2005
and data traffic to for example a web server in real
Sensor placement for a standard system is
time on GPRS.
displayed below.
Advanced Alarm Capability The Performance-analyser can also send SMS
TT_SecW_in [ 6 ]
TT_Rexp_in [ 3 ]
messages via a Web server to desired recipients
TT_SecW_out [ 7 ]
PT_RHP [ AI1 ] TT_RComp_out [ 1 ] EP [AI3 ]
according to a programmed schedule. The messages can be tailored after the occurring event
PT_RLP [ AI2 ]
and it is possible to schedule several numbers
TT_RComp_in [ 2 ]
depending on time of day/week. Temperature, Pressure and Power Input
TT_SecC_out [ 5 ]
TT_SecC_in [ 4 ]
ClimaCheck Performance-analyser 8-7 has eight temperature channels that measure desired temperatures on the refrigeration- and secondary systems and seven analogue input channels for
Sensors used for “standard” ClimaCheck analyses.
sensors with voltage or current signals. It can be
Proven Method
used for almost all relevant measurements in most
The method to calculate performance based on
refrigeration or heat pump systems.
measurements in the refrigeration circuit was
Most common sensors used are pressure-, power-
patented in 1986 and the easy to use and inherent
and humidity transducers. This will be sufficient for
good accuracy compared to alternative methods
a full evaluation of all components in a refrigeration
was verified by several manufacturers, universities
system.
and the Swedish Research and Testing Institute (SP).
ClimaCheck Software ClimaCheck software accurately analyses data collected with the Performance-analyser see special information or visit web site www.climacheck.com .
ΓΙΑ ΠΕΡΙΣΣΟΤΕΡΕΣ ΠΛΗΡΟΦΟΡΙΕΣ ΕΠΙΚΟΙΝΩΝΗΣΤΕ ΜΕ ΤΗΝ ΕΤΑΙΡΕΙΑ ΣΟΛΔΑΤΟΣ
ClimaCheck developed and distributed by:
FOR INFORMATION PLEASE CONTACT SOLDATOS COMPANY
ClimaCheck Sweden AB Nysätravägen 24 S-131 33 Nacka Tel.: +46 (0)8-55 61 55 75 E-mail: info@berglof-kylteknologi.se Web: www.berglof-kylteknologi.se
May 2005
Specifications ClimaCheck™ Performance Analyser 8:7
ClimaCheck Performance Analyser 8:7 to the left DIN rail mounted to the right field inspection unit with built in power transformer.
Analogue Inputs
Temperature inputs
7 analogue inputs with 12 bit resolution
8 PT1000 temperature inputs covering the range of
Each input can be programmed to be either a 4-
-50 to +150 degC.
20mA current input or a 0-2.5V or a 0-5V input. 3
Each input has a discriminator capable of
inputs are software switchable between current and
transforming the analogue value into a digital
voltage input the other 4 require jumpers. The
value. The discriminator can be set to operate as a
switch between 0-2.5V and 0-5V is controlled by
simple switch or a window. The digital value can
software.
be set to be true if the input is above or below the
Each input has a discriminator capable of
switch threshold or within or outside the window.
transforming the analogue value into a digital
Hysteresis is used to prevent spurious switching
value. The discriminator can be set to operate as a
around the thresholds.
simple switch or a window. The digital value can
Programmable delay from 0 to 255 seconds for
be set to be true if the input is above or below the
each input
switch threshold or within or outside the window.
Programmable analogue sampling rate from once
Hysteresis is used to prevent spurious switching
per second to one sample every 18 hours.
around the thresholds.
Input averaging. The analogue inputs can be set
Programmable delay from 0 to 255 seconds for
to record either the average value over the logging
each input
period or the instantaneous value when a log is
Programmable analogue sampling rate from once
taken.
per second to one sample every 18 hours. Input averaging. The analogue inputs can be set
Digital Inputs
to record either the average value over the logging
8 digital inputs are fully optically isolated in pairs.
period or the instantaneous value when a log is
Optically isolated inputs can have onboard pullup
taken.
resistors switched in but this negates the isolation. All inputs have led status indication when using internal pullups.
Maj 2005
Input accepts a switch closure to ground with an
Alarm escalation programmable on each alarm.
onboard switchable pullup resistor.
Disabled phone numbers are automatically
32 bit counter associated with each input. The
excluded from the escalation.
counter counts the positive transitions on an input.
Programmable delay time for each alarm.
Counters can be selectively logged.
Alarm inputs can be derived from digital inputs,
Counters can be reset at each logging interval or
digital variables, analogue inputs or timeclocks.
by a signal derived from any digital input, digital
Optional daily alarm limit preventing excessive
variable, analogue input or timeclock.
SMS phone bills.
Counters are scaled using user defined scale
User programmable number of retries.
factors and units.
User programmable time between retries.
Each counter can set a predefined digital variable if the either the input frequency exceeds a user
Logic functions
defined value or if the counts exceed a used
8 logic functions each with 4 inputs and 4 AND/OR
defined count. Each input has it's own digital
arrays.
variable.
Logic function inputs can be derived from digital
Each counter has a second digital variable which
inputs, digital variables, analogue inputs or
will give an early warning of a possible excess
timeclocks. Logic function output can be inverted
frequency or excess count condition.
Digital Outputs
Delay functions
3 open collector MOSFET outputs
4 delay functions each capable of generating one of
Each output can be driven from a signal derived
3 types of output: Delayed turn on, Fixed width
from any digital input, digital variable, analogue
output or Input stretching.
input or timeclock.
Delay function can be programmed to operate from
The switches can handle loads of 100mA with
either the rising or falling edge of the input.
voltages up to 25Volts.
Logic function inputs can be derived from digital
Digital Variables
inputs, digital variables, analogue inputs or
48 digital variables accept outputs from the
Delay times from 1 to 255 seconds.
internal functions.
timeclocks.
All digital variables can be used as inputs to any
Timeclocks
function.
8 separate time/action events during the day.
2 logical OR functions allowing combining of
4 daily schedules.
variables.
6 weekly schedules with public holiday override.
Edge detector
These schedules can be used by other functions.
One edge detector which detects the rising edge of
8 public holidays.
either a digital input, digital variable, analogue
Counter functions
input or timeclock.
2 16 bit counters.
Alarms
Counter inputs can be derived from digital inputs,
Alarms are reported by SMS messages.
Alarm generation capability if count exceeds a user
16 alarms.
defined limit.
8 separate phone numbers.
Counters can be preset to any value.
Phone numbers can be selectively enabled by
Counters can be cleared by any digital input, digital
weekly schedules.
variable, analogue input or timeclock.
Maj 2005
digital variables, analogue inputs or timeclocks.
Logging
GPS location
256kbytes of logging memory. Each analogue input
A GPS receiver can be incorporated into the system
can be selectively logged. Each digital counter can
and location will be stored in the log.
be selectively logged. All log entries are time
SMS command can read out the current device
stamped with a resolution of 1 second. All alarms
location.
are logged. All re-program events are logged. All
Accepts all standard GPS modules which transmit
changes to the input limits are logged together
NMEA sentences at either 4800 or 9600baud.
with the users phone number. Logging intervals selectable from 5 minutes to 1 hour synchronised
Sensor power control
to cardinal times with optional capability to log at
MOSFET switched power supply to external
rates from 5 seconds to 255 seconds interval in 1
sensors. Programmable sensor power on delay
second steps. Logging rate can be controlled by
from 30ms up to 160secs. Programmable analogue
any digital input, digital variable, analogue input or
sample rate from once/sec down to 1 sample every
timeclock. Capability to output logged data as a csv
18 hours.
style frame each time a logged sample is stored.
Communication
Modem power control Capability of powering the modem on/off.
Standard RS232 communications at 9600baud.
Capability of waking the modem up on a regular
SMS commands using a GSM modem. GPRS
schedule to allow for remote access. Capability of
connection supported. Logged data can be output
waking the modem up to send a SMS message.
as it is gathered. Transmission format can be in
Capability of powering the modem on at regular
straight ASCII including units etc or can be
intervals to automatically upload data to remote
compressed to varying degrees.
server via GPRS.
SMS command capability
Physical
Remote interrogation of analogue inputs with the
Dimensions:
values being returned in engineering units.
mounted housing 151 x 82.5 x 12mm (H x W x L)
Remote interrogation of analogue input limits,
Power:
digital inputs and outputs. Remote interrogation of
Current consumption varies depending on the
phone numbers. Can change phone numbers.
configuration from 10µA up to about 50µA.
Can change analogue input limits. Can disable or
Environmental: -20 to +50 degC. 5 to 95%
enable all alarms. Can remotely turn on or off any
humidity non-condensing.
digital output. Can remotely acknowledge an alarm
Power control of analogue sensors:
and cancel escalation. Can change the holiday list.
Switched incoming supply via series MOSFET.
Can be supplied in a DIN rail 12 VDC to 16VDC @ 40µA nominal.
Can read device location if a GPS module is
Maximum load current: 100mA
incorporated into the system. Acknowledgement of
Maximum series resistance: 10ohm
all SMS messages. _________________________________________________________________________________________