Mr slim r32 power inverter brochure1

Page 1



The Mr Slim R32 Power Inverter Range A blend of energy efficiency and sophisticated design


It’s time to enjoy energy savings and great new product features

It’s time to put R32 refrigerant at the heart of your conversations and plans moving forward, with the market leading range of R32 products from Mitsubishi Electric

It’s time for your air conditioning to help meet EU carbon emissions targets


The 2014 F-Gas Regulations have one key objective: to reduce F-Gas emissions by 79% between 2015 and 2030, by cutting the availability of hydrofluorocarbons (HFCs) with a high Global Warming Potential (GWP). It’s time therefore to look at alternative, low GWP refrigerants such as R32. Already making up 50% of the existing R410A refrigerant found in many current air conditioning systems, R32 has a GWP of 675 (one third that of R410A), is highly energy efficient and is easy to recycle. Plus, the volumetric capacity of R32 is around 20% higher than that of R410A, which means system refrigerant volumes are lower.

Benefits of R32

Low GWP of 675 High efficiency refrigerant F-Gas phase down compliant Less refrigerant volume requirement compared to R410A Affordable & readily available A single component refrigerant Easy to handle, reuse and recycle


The Mr Slim R32 Power Inverter Range The Mr Slim R32 Power Inverter range blends a host of outstanding features with a premium quality, sophisticated design. Offering our highest seasonal efficiency levels, advanced control options and extended pipe runs, this range is extremely flexible and available in four different indoor unit types, from 3.5 to 14kW.

Industry Leading Seasonal Energy Efficiency Ratings The R32 Power Inverter is able to achieve high seasonal efficiencies through the optimisation of a newly designed compressor and use of the latest energy-saving technologies. ERP energy efficiency ratings of A++ are common throughout the range, with annual power consumption drastically reduced, resulting in increased run cost savings. Heating / Cooling

Indoor Unit

3.5kW

PLA-ZM 4-Way Blow Ceiling Cassette

5.0kW

6.0kW

7.1kW

10.0kW

12.5kW

14.0kW

A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++

PKA-M Wall Mounted PEAD-M Ceiling Concealed Ducted PCA-M Ceiling Suspended

A+ / A++

A+ / A++

A+ / A++

A+ / A++

A+ / A++

-

-

A / A+

A+ / A++

A+ / A++

A / A+

A+ / A++

A / A+

A+ / A+

-

A+ / A++

A+ / A++

A+ / A++

A+ / A++

A+ / A++

A+ / A++

3-Phase Power Supply The 10.0, 12.5 and 14.0kW models are also available as a 3-phase option. Choosing this option dramatically reduces the running current of the unit and subsequent fuse rating. Power Supply 3-Phase

10.0kW

12.5kW

14.0kW

Max Running Current (A)

8.5

10.0

13.7

Fuse Rating (A)

16

16

16

10.0kW

12.5kW

14.0kW

27.0

27.0

28.7

32

32

40

Power Supply Single Phase

Max Running Current (A) Fuse Rating (A)

Note: Example using a 4-Way Blow Ceiling Cassette

10.0 / 12.5 / 14.0kW PUZ-ZM100-140VKA/YKA 6.0 / 7.1kW PUZ-ZM60/71VHA 3.5 / 5.0kW PUZ-ZM35/50VKA


Increased Pipe Lengths Pipe lengths of up to 100m with a 30m height difference are now available with the R32 Power Inverter, increasing the application possibilities of the range. Outdoor Unit

Max Pipe Length (m)

Max Height Difference (m)

PUZ-ZM35/50VKA

50

30

PUZ-ZM60/71VHA

55 (5m increase over R410A PUHZ-ZRP Power Inverter)

30

100 (25m increase over R410A PUHZ-ZRP Power Inverter)

30

PUZ-ZM100/125/140VKA/YKA

Full Heating Capacity Down to -3ยบC

Height Difference 30m Pipe Length 100m

R32

1.6

Designed to provide powerful heating, even on bitterly cold or snowy days. When compared to the R410A Power Inverter, the rated heating capacity is maintained down to outside temperatures of -3ยบC.

PUZ-ZM

1.4 1.2 1.0 0.8 0.6

Multi-Split Applications

R410A

0.4

The R32 Power Inverter can be used as a Multi-Split, making it an ideal option for open plan spaces in medium sized premises such as shops or offices, where two or three indoor units are required connected to a single outdoor unit. The indoor units can be a mix of ceiling cassettes, wall mounted, ceiling concealed ducted or ceiling suspended types.

PUHZ-ZRP

0.2 -3ยบC

Outside Temperature

Twin Indoor Units

5ยบC

Triple Indoor Units

Outdoor Unit Capacity Twin

Triple

Indoor Unit Combination

7.1kW

10.0kW

12.5kW

14.0kW

14.0kW

PLA-ZM

3.5 x 2

5.0 x 2

6.0 x 2

7.1 x 2

5.0 x 3

PKA-M

3.5 x 2

5.0 x 2

6.0 x 2

7.1 x 2

5.0 x 3

PEAD-M

3.5 x 2

5.0 x 2

6.0 x 2

7.1 x 2

5.0 x 3

-

5.0 x 2

6.0 x 2

7.1 x 2

5.0 x 3

PCA-M

Multi Distributor Pipes

Outdoor Unit

Multi Distributor Pipes

Outdoor Unit


Built using micron-precise calculations, the compressor is the heart of the R32 Power Inverter air conditioning system

Poki-Poki Motor

Dramatically enhanced motor efficiency utilising Mitsubishi Electric’s original dense winding technology.

Heat Caulking

Mitsubishi Electric’s heat caulking method minimises cylinder distortion for even greater efficiency.

30Pa External Static Pressure An external static pressure of 30Pa enables the outdoor unit to be installed on balconies in high-rise buildings or spaces near louvres.* * Optional (requires PAC-SJ71FM-E). Rated noise levels may be higher when equipped with this option.


Solutions that address the ban on R22 refrigerant As of 1st January 2015 it became illegal to use R22 refrigerant*1 to service and maintain air conditioning units, yet there are a large number of systems still in use in the UK that rely on R22. Many of these building operators remain unaware that whilst their air conditioning will not be illegal to run, it may need immediate replacement if it requires maintenance involving any degassing of the system. The continual rise in energy costs also means everyone involved in the built environment is focusing on energy use and consumption and this is where modern equipment can really help to support replacement. The R32 Power Inverter models incorporate our unique ‘Replace Technology’ which allows the upgrade of systems using existing pipe work, without the need to apply any special cleaning machines.

*1 The EC Ozone Regulation (No.1005/2009) was introduced to control and phase out the remaining uses of all Ozone Depleting Substances (ODS) such as R22 refrigerant. This has led to a total ban on its use for service and maintenance by the start of the year 2015. ODS can result in greater UV radiation reaching the earth’s surface which is harmful for humans, animals and plants, leading to increases in skin cancer, cataracts and a reduction in food crop yields. Modern alternatives such as HFC’s, which include R32, do not have the same ozone depleting potential (ODP).


PLA-ZM 4-Way Blow Ceiling Cassette System


The new square grille design of the PLA-ZM beautifully harmonises with any interior, making it ideal for applications such as offices or retail stores. Horizontal Airflow Control New horizontal airflow control helps remove uncomfortable draughts and improve comfort levels.

Optional 3D i-see Sensor Highly accurate 360ยบ motion detection for body temperature and room occupancy, improving efficiency and comfort through automatic selection of energy-saving modes.

Optional Filter Lowering Grille

Controller Options

Allows easy, regular cleaning of the filter, improving efficiency and reducing maintenance.

8 sensors

rotate a full 360ยบ in 3 minute intervals

This feature is particularly useful in rooms that have a high ceiling Detects position and number of people Detects body and floor temperature

1.2m 1.6m 2.0m 2.4m

PAR-33MAA Wired Controller

2.8m 3.2m 3.6m 4.0m max

NEW PAR-SL100A-E Backlit Wireless Controller


PKA-M Wall Mounted System


Flat panel is easy to clean

The PKA-M blends a host of outstanding features with a sophisticated pure white, flat panel, streamlined design. Offering high seasonal efficiency, advanced control options and quiet operation, this range provides extreme flexibility and ease of installation. Improved airflow control, including adjustable louvres for uniform air distribution Internal pipe connection to wall mounted unit for easy and neat installation Compact Indoor Units Indoor unit width has been reduced by as much as 510mm. Units take up much less space, greatly increasing installation possibilities. PKA-M35/50HA

PKA-M60/71KA

Controller Options CN22 connector as standard for connection to PAR-33MAA wired controller

92mm DOWN* *Compared to PKA-RP35/50GA

230mm DOWN* *Compared to PKA-RP60/71FA

PKA-M100KA

510mm DOWN* *Compared to PKA-RP100FA

PAR-33MAA Wired Controller

PAR-FL32MA Wireless Controller


PEAD-M Ceiling Concealed Ducted System


The PEAD-M includes a host of outstanding features with an unobtrusive design for easy installation and maintenance.

Compact Indoor Units

External Static Pressure

The height of all models has been unified to 250mm. Compared to the previous PEAD-RP EA range, this has seen a reduction by as much as 75mm (sizes 100-140), making installation in low ceilings with a minimal clearance space possible.

The external static pressure can be set to five stages, up to a maximum of 150Pa, making units applicable for a wide range of building types. This is now standard on all unit sizes. External static pressure setting Model / Size PEAD-M

35

50

60

71

100

125

35/50/70/100/150Pa

250mm Reduction of

75mm

(models 100-140) compared to PEAD-RP EA

Drain pump is included as standard

140

PAR-33MAA Wired Controller


PCA-M Ceiling Suspended System


The PCA-M incorporates a stylish new indoor unit design with airflow settings for both high and low ceiling applications, expanding the installation possibilities of this unit.

Controller Options

Stylish Indoor Unit Design

PAR-SL94B Wireless Controller and receiver

PAR-33MAA Wired Controller

A new stylish square-like design allows these units to blend in seamlessly with the ceiling.

Automatic Air-speed Adjustment In addition to the conventional 4-speed setting, units are now equipped with an automatic air-speed adjustment mode. This setting automatically adjusts the air speed to conditions that match the room environment. At the start of the heating/cooling operation, the airflow is set to high-speed to quickly heat/cool the room. When the room temperature reaches the desired setting, the airflow speed is decreased automatically creating a stable, comfortable environment.

Units are equipped with high and low ceiling operation modes that make it possible to switch the airflow volume to match room height. The ability to choose the optimum airflow volume makes it possible to reduce draughts. High Ceiling

Standard Ceiling

Gentle

Start of cooling/heating

After room temperature is stabilised

Optional Drain Pump

High / Low Ceiling Modes

Size

Strong

Low Ceiling

50

3.5m

2.7m

2.5m

60

3.5m

2.7m

2.5m

71

3.5m

2.7m

2.5m

100

4.2m

3.0m

2.6m

125

4.2m

3.0m

2.6m

140

4.2m

3.0m

2.6m

The pumping height of the optional drain pump has been increased from 400mm to 600mm, expanding the location possibilities of the unit. Drainage outlet can be 600mm above ceiling surface

Outside air Intake Unts are equipped with a knock-out hole that enables the induction of fresh air. Outside air intake characteristics 50 0 -50 -100

Ceiling surface

-150 -200 -250 -300

0

1

2

Airflow volume (m3/min)

PCA-M100-140

PCA-M60/71

3

PCA-M50

4


Mobile control and monitoring of your Mitsubishi Electric systems MELCloud is a cloud based solution for controlling and monitoring your Mitsubishi Electric air conditioning, ventilation or heating systems either locally or remotely by PC, tablet or smartphone app. It offers the ability to control which units are on/off, temperature settings, the 7 day weekly schedule, frost protection settings, holiday mode and also log and record errors. Ensuring total flexibility from a single device, from any worldwide location, the MELCloud app also provides localised information like weather forecasts and customer service contact details.

MAC-567IF Optional Wi-Fi Interface


PLA-ZM R32 Power Inverter Heat Pump 4-Way Blow Ceiling Cassette System Product Specifications PLA-ZM35EA

PLA-ZM - INDOOR  UNITS CAPACITY (kW)

PLA-ZM50EA

PLA-ZM60EA

PLA-ZM71EA

PLA-ZM100EA

PLA-ZM100EA

PLA-ZM125EA

PLA-ZM125EA

PLA-ZM140EA

PLA-ZM140EA

Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)

7.0 (2.8-8.2) 4.1 (1.6-5.2) 6.0 (2.5-7.3) 8.0 (3.5-10.2) 11.2 (4.5-14.0) 11.2 (4.5-14.0) 14.0 (5.0-16.0) 14.0 (5.0-16.0) 16.0 (5.7-18.0) 16.0 (5.7-18.0) 6.1 (2.7-6.5) 3.6 (1.6-4.5) 5.0 (2.3-5.6) 7.1 (3.3-8.1) 9.5 (4.9-11.4) 9.5 (4.9-11.4) 12.5 (5.5-14.0) 12.5 (5.5-14.0) 13.4 (6.2-15.0) 13.4 (6.2-15.0) 3.5 (1.35-4.4) 5.1 (2.15-6.2) 6.8 (3.0-8.65) 9.5 (3.85-11.9) 9.5 (3.85-11.9) 11.9 (4.25-13.6) 11.9 (4.25-13.6) 13.6 (4.85-15.3) 13.6 (4.85-15.3) 6.0 (2.38-6.97) 3.3 (1.45-4.15) 4.6 (2.1-5.15) 6.55 (3.05-7.45) 9.2 (4.5-10.5) 9.2 (4.5-10.5) 11.5 (5.05-12.9) 11.5 (5.05-12.9) 12.9 (5.7-14.1) 12.9 (5.7-14.1) 5.6 (2.48-5.98) 0.77 0.95 0.85 0.72 0.77 0.77 0.70 0.70 0.70 0.70 SHF (nominal) 4.10 / 4.20 5.00 / 5.10 4.40 / 4.52 4.40 / 4.30 4.30 / 4.60 4.30 / 4.60 3.81 / 3.70 3.81 / 3.70 3.71 / 3.60 3.71 / 3.60 COP / EER (nominal) 4.60 / 7.20 4.70 / 7.50 4.90 / 7.60 4.80 / 7.60 4.80 / 7.70 4.80 / 7.50 4.70 / 7.40 4.70 / 7.20 4.60 / 7.00 4.60 / 6.90 SCOP / SEER (BS EN14825) A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ ERP ENERGY  EFFICIENCY  CLASS Heating/Cooling 183-217-250-267 200-233-267-300 283-317-350-383 317-367-417-467 317-367-417-467 350-400-433-483 350-400-433-483 400-433-483-533 400-433-483-533 200-233-267-300 AIRFLOW (l/s) Lo-Mi-Mi2-Hi 12.7 (1/2”) / 6.35 (1/4”) 12.7 (1/2”) / 6.35 (1/4”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) PIPE SIZE MM (in) Gas/Liquid 27-29-31-32 26-28-29-31 27-29-31-32 28-30-33-36 31-34-37-40 31-34-37-40 33-36-39-41 33-36-39-41 36-39-42-44 36-39-42-44 SOUND  PRESSURE  LEVEL (dBA) Lo-Mi-Mi2-Hi 54 51 54 57 61 61 62 62 65 65 SOUND  POWER  LEVEL (dBA) DIMENSIONS (mm) Width x Depth x Height (Grille) 840 (950) x 840 (950) x 258 (40) 840 (950) x 840 (950) x 258 (40) 840 (950) x 840 (950) x 258 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 21 / 5 21 / 5 21 / 5 24 / 5 26 / 5 26 / 5 26 / 5 26 / 5 26 / 5 26 / 5 WEIGHT (kg) Unit / Grille Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit ELECTRICAL  SUPPLY 6 6 6 6 6 6 6 6 6 6 FUSE RATING (BS88) - HRC (A) 4 4 4 4 4 4 4 4 4 4 INTERCONNECTING CABLE  NO. CORES PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA GRILLE  REFERENCE PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA WIRED  REMOTE  CONTROLLER  REFERENCE PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E WIRELESS  REMOTE  CONTROLLER  REFERENCE

PUZ-ZM -  OUTDOOR UNITS SOUND  PRESSURE  LEVEL (dBA) SOUND  POWER  LEVEL (dBA) WEIGHT (kg) DIMENSIONS (mm) ELECTRICAL  SUPPLY PHASE SYSTEM POWER  INPUT (kW) STARTING  CURRENT (A) SYSTEM RUNNING CURRENT (A) FUSE RATING (BS88) - HRC (A) MAINS CABLE NO. CORES MAX PIPE LENGTH (m) MAX HEIGHT DIFFERENCE (m) CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t) MAX ADDITIONAL REFRIGERANT (kg) / CO2 EQUIVALENT (t)

Heating/Cooling Cooling Width x Depth x Height

Heating/Cooling (nominal) Heating/Cooling (UK) Heating/Cooling [MAX]

R32 (GWP 675) - 30m R32 (GWP 675)

PUZ-ZM60VHA

PUZ-ZM71VHA

PUZ-ZM100VKA PUZ-ZM100YKA

3

Lower View

PUZ-ZM125YKA

52 / 50 70 116 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 3.674 / 3.378 3.27 / 2.87 13.0 15.77 / 14.53 [27.0] 32 3 100 30

52 / 50 52 / 50 70 70 125 118 1050 x 330 + 40 x 1338 1050 x 330 + 40 x 1338 380-415v, 50Hz 220-240v, 50Hz Three Single 3.674 / 3.378 4.312 / 3.772 3.27 / 2.87 3.83 / 3.15 6.0 13.0 5.32 / 4.89 [10.0] 18.41 / 15.88 [28.7] 16 40 5 3 100 100 30 30

46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 0.820 / 0.705 0.73 / 0.59 5.0 3.89 / 3.51 [13.2] 16 3 50 30

46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 1.363 / 1.106 1.21/ 0.94 5.0 6.05 / 5.00 [13.2] 16 3 50 30

2.0 / 1.35

2.00 / 1.35

2.80 / 1.89

2.80 / 1.89

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

0.30 / 0.20

0.30 / 0.20

0.80 / 0.54

0.80 / 0.54

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

49 / 47 49 / 47 67 67 70 70 950 x 330 + 25 x 943 950 x 330 + 25 x 943 220-240v, 50Hz 220-240v, 50Hz Single Single 1.707 / 1.452 1.818 / 1.651 1.43 / 1.15 1.61 / 1.39 6.0 6.0 7.39 / 6.31 [19.2] 7.79 / 7.06 [19.3] 25 25 3 3 55 55 30 30

51 / 49 51 / 49 69 69 116 123 1050 x 330 + 40 x 1338 1050 x 330 + 40 x 1338 220-240v, 50Hz 380-415v, 50Hz Single Three 2.604 / 2.065 2.604 / 2.065 2.09 / 1.77 2.09 / 1.77 13.0 6.0 11.25 / 8.97 [27.0] 3.75 / 2.96 [8.5] 32 16 3 5 100 100 30 30

PLA-ZM35-140EA

Upper View

Front View

Side View

PUZ-ZM140VKA

PUZ-ZM140YKA

PUZ-ZM50VKA

3 Three Phase

Product Dimensions

3

PUZ-ZM125VKA

PUZ-ZM35VKA

3

52 / 50 70 131 1050 x 330 + 40 x 1338 380-415v, 50Hz Three 4.312 / 3.772 3.83 / 3.15 6.0 6.23 / 5.37 [13.7] 16 5 100 30


PKA-M R32 Power Inverter Heat Pump Wall Mounted System Product Specifications PKA-M - INDOOR  UNITS Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)

CAPACITY (kW)

SHF (nominal) COP / EER (nominal) SCOP / SEER (BS EN14825) ERP ENERGY  EFFICIENCY  CLASS AIRFLOW (l/s) PIPE SIZE MM (in)

Heating/Cooling Lo-Mi-Hi Gas Liquid Lo-Mi-Hi

SOUND  PRESSURE  LEVEL (dBA) SOUND  POWER  LEVEL (dBA) DIMENSIONS (mm) Width x Depth x Height WEIGHT (kg) ELECTRICAL  SUPPLY FUSE RATING (BS88) - HRC (A) INTERCONNECTING CABLE  NO. CORES WIRED  REMOTE  CONTROLLER  REFERENCE WIRELESS  REMOTE  CONTROLLER  REFERENCE

PUZ-ZM -  OUTDOOR UNITS SOUND  PRESSURE  LEVEL (dBA) SOUND  POWER  LEVEL (dBA) WEIGHT (kg) DIMENSIONS (mm) ELECTRICAL  SUPPLY PHASE SYSTEM POWER  INPUT (kW) STARTING  CURRENT (A) SYSTEM RUNNING CURRENT (A) FUSE RATING (BS88) - HRC (A) MAINS CABLE NO. CORES MAX PIPE LENGTH (m) MAX HEIGHT DIFFERENCE (m) CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t) MAX ADDITIONAL REFRIGERANT (kg) / CO2 EQUIVALENT (t)

Heating/Cooling Cooling Width x Depth x Height

Heating/Cooling (nominal) Heating/Cooling (UK) Heating/Cooling [MAX]

PKA-M35HA

PKA-M50HA

PKA-M60KA

PKA-M71KA

PKA-M100KA

PKA-M100KA

4.1 (1.6-5.2) 3.6 (1.6-4.5) 3.5 (1.35-4.4) 3.3 (1.45-4.15) 0.81 3.94 / 4.14 4.0 / 6.3 A+ / A++ 150-175-200 12.7 (1/2”) 6.35 (1/4”) 36-40-43 60 898 x 249 x 295 13 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA

5.0 (2.5-7.3) 4.6 (2.3-5.6) 4.25 (2.15-6.2) 4.23 (2.1-5.15) 0.72 3.71 / 3.71 4.1 / 6.4 A+ / A++ 150-175-200 12.7 (1/2”) 6.35 (1/4”) 36-40-43 60 898 x 249 x 295 13 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA

7.0 (2.8-8.2) 6.1 (2.7-6.7) 5.95 (2.4-6.95) 5.5 (2.5-6.15) 0.86 4.04 / 3.91 4.2 / 6.8 A+ / A++ 300-333-367 15.88 (5/8”) 9.52 (3/8”) 39-42-45 64 1170 x 295 x 365 21 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA

8.0 (3.5-10.2) 7.1 (3.3-8.1) 6.8 (3.0-8.65) 6.55 (3.05-7.45) 0.78 3.78 / 3.81 4.3 / 6.8 A+ / A++ 300-333-367 15.88 (5/8”) 9.52 (3/8”) 39-42-45 64 1170 x 295 x 365 21 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA

11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.73 3.61 / 3.95 4.4 / 6.5 A+ / A++ 333-383-433 15.88 (5/8”) 9.52 (3/8”) 41-45-49 65 1170 x 295 x 365 21 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA

11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.73 3.61 / 3.95 4.4 / 6.4 A+ / A++ 333-383-433 15.88 (5/8”) 9.52 (3/8”) 41-45-49 65 1170 x 295 x 365 21 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA

PUZ-ZM35VKA

PUZ-ZM50VKA

PUZ-ZM60VHA

PUZ-ZM71VHA

PUZ-ZM100VKA

PUZ-ZM100YKA

46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 1.040 / 0.869 0.81 / 0.84 5.0 4.97 / 4.31 [13.4] 16 3 50 30

46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 1.347 / 1.239 1.12 / 1.12 5.0 5.98 / 5.57 [13.4] 16 3 50 30

49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 1.732 / 1.560 1.25 / 1.65 6.0 7.41 / 6.65 [19.4] 25 3 55 30

49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 2.116 / 1.863 1.54 / 1.92 6.0 9.10 / 7.96 [19.4] 25 3 55 30

51 / 49 69 116 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 3.102 / 2.405 2.47 / 2.06 13.0 13.46 / 10.45 [27.1] 32 3 100 30

51 / 49 69 123 1050 x 330 + 40 x 1338 380-415v, 50Hz Three 3.102 / 2.405 2.47 / 2.06 6.0 4.49 / 5.45 [8.6] 16 5 100 30

2.0 / 1.35

2.00 / 1.35

2.80 / 1.89

2.80 / 1.89

4.00 / 2.70

4.00 / 2.70

0.30 / 0.20

0.30 / 0.20

0.80 / 0.54

0.80 / 0.54

2.80 / 1.89

2.80 / 1.89

R32 (GWP 675) - 30m R32 (GWP 675)

3

3 Three Phase

Product Dimensions

Product Dimensions

PKA-M35/50HA

Upper View

Front View

Side View

PKA-M60/71/100KA

Upper View

Front View

Side View

192

387

365

431.7

599

55

688

155 898

249

5

11

140.3

197

295

65.2

423.7

74

(855)

241 1170

295

5


PEAD-M R32 Power Inverter Heat Pump Ceiling Concealed Ducted System Product Specifications PEAD-M35JA

PEAD-M50JA

PEAD-M60JA

PEAD-M71JA

PEAD-M100JA

PEAD-M100JA

PEAD-M125JA

PEAD-M125JA

PEAD-M140JA

PEAD-M140JA

4.1 (1.6-5.2) 3.6 (1.6-4.5) 3.5 (1.35-4.4) 3.3 (1.45-4.15) 0.85 4.47 / 4.30 3.9 / 5.8 A / A+ 167-200-233 12.7 (1/2”) 6.35 (1/4”) 35-50-70-100-150 23-27-30 54 900 x 732 x 250 26 Fed by Outdoor Unit 6 4 PAR-33MAA

6.0 (2.5-7.3) 5.0 (2.3-5.6) 5.1 (2.15-6.2) 4.6 (2.1-5.15) 0.84 4.57 / 4.16 4.3 / 6.2 A+ / A++ 200-242-283 12.7 (1/2”) 6.35 (1/4”) 35-50-70-100-150 26-31-35 59 900 x 732 x 250 27 Fed by Outdoor Unit 6 4 PAR-33MAA

7.0 (2.8-8.2) 6.1 (2.7-6.7) 5.95 (2.4-6.95) 5.5 (2.5-6.15) 0.83 4.33 / 4.04 4.0 / 6.1 A+ / A++ 242-300-350 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 25-29-33 55 1100 x 732 x 250 30 Fed by Outdoor Unit 6 4 PAR-33MAA

8.0 (3.5-10.2) 7.1 (3.3-8.1) 6.8 (3.0-8.65) 6.55 (3.05-7.45) 0.83 4.14 / 3.82 3.9 / 5.8 A / A+ 292-350-417 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 26-30-34 58 1100 x 732 x 250 30 Fed by Outdoor Unit 6 4 PAR-33MAA

11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.82 4.31 / 4.18 4.1 / 6.2 A+ / A++ 400-483-567 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 29-34-38 62 1400 x 732 x 250 39 Fed by Outdoor Unit 6 4 PAR-33MAA

11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.82 4.31 / 4.18 4.1 / 6.1 A+ / A++ 400-483-567 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 29-34-38 62 1400 x 732 x 250 39 Fed by Outdoor Unit 6 4 PAR-33MAA

14.0 (5.0-16.0) 12.5 (5.5-14.0) 11.9 (4.25-13.6) 11.5 (5.05-12.9) 0.84 4.18 / 3.75 3.9 / 5.8 A / A+ 492-592-700 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 33-36-40 66 1400 x 732 x 250 40 Fed by Outdoor Unit 6 4 PAR-33MAA

14.0 (5.0-16.0) 12.5 (5.5-14.0) 11.9 (4.25-13.6) 11.5 (5.05-12.9) 0.84 4.18 / 3.75 3.9 / 5.7 A / A+ 492-592-700 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 33-36-40 66 1400 x 732 x 250 40 Fed by Outdoor Unit 6 4 PAR-33MAA

16.0 (5.7-18.0) 13.4 (6.2-15.3) 13.6 (4.85-15.3) 12.9 (5.7-14.1) 0.84 4.03 / 3.69 4.0 / 5.7 A+ / A+ 533-650-767 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 34-38-43 67 1600 x 732 x 250 44 Fed by Outdoor Unit 6 4 PAR-33MAA

16.0 (5.7-18.0) 13.4 (6.2-15.3) 13.6 (4.85-15.3) 12.9 (5.7-14.1) 0.84 4.03 / 3.69 4.0 / 5.6 A+ / A+ 533-650-767 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 34-38-43 67 1600 x 732 x 250 44 Fed by Outdoor Unit 6 4 PAR-33MAA

PUZ-ZM35VKA

PUZ-ZM50VKA

PUZ-ZM60VHA

PUZ-ZM71VHA

46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 0.917 / 0.837 0.76 / 0.76 5.0 4.17 / 3.89 [4.1] 16 3 50 30

46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 1.312 / 1.201 1.11 / 1.06 5.0 5.55 / 5.07 [14.4] 16 3 50 30

49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 1.616 / 1.509 1.32 / 1.39 6.0 6.68 / 6.16 [20.5] 25 3 55 30

49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 1.932 / 1.858 1.7 / 1.59 6.0 7.85 / 7.45 [21] 25 3 55 30

2.0 / 1.35

2.00 / 1.35

2.80 / 1.89

2.80 / 1.89

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

0.30 / 0.20

0.30 / 0.20

0.80 / 0.54

0.80 / 0.54

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

PEAD-M - INDOOR  UNITS CAPACITY (kW)

Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)

SHF (nominal) COP / EER (nominal) SCOP / SEER (BS EN14825) ERP ENERGY  EFFICIENCY  CLASS AIRFLOW (l/s) PIPE SIZE MM (in)

Heating/Cooling Lo-Mi-Hi Gas Liquid

EXTERNAL  STATIC  PRESSURE (Pa) SOUND  PRESSURE  LEVEL (dBA) Lo-Mi-Hi SOUND  POWER  LEVEL (dBA) DIMENSIONS (mm) Width x Depth x Height WEIGHT (kg) ELECTRICAL  SUPPLY FUSE RATING (BS88) - HRC (A) INTERCONNECTING CABLE  NO. CORES WIRED REMOTE CONTROLLER REFERENCE

PUZ-ZM -  OUTDOOR UNITS SOUND  PRESSURE  LEVEL (dBA) SOUND  POWER  LEVEL (dBA) WEIGHT (kg) DIMENSIONS (mm) ELECTRICAL  SUPPLY PHASE SYSTEM POWER  INPUT (kW) STARTING  CURRENT (A) SYSTEM RUNNING CURRENT (A) FUSE RATING (BS88) - HRC (A) MAINS CABLE NO. CORES MAX PIPE LENGTH (m) MAX HEIGHT DIFFERENCE (m) CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t) MAX ADDITIONAL REFRIGERANT (kg) / CO2 EQUIVALENT (t)

Heating/Cooling Cooling Width x Depth x Height

Heating/Cooling (nominal) Heating/Cooling (UK) Heating/Cooling [MAX]

R32 (GWP 675) - 30m R32 (GWP 675)

PUZ-ZM100VKA PUZ-ZM100YKA

3 Three Phase

PEAD-M35-140JA Suspension bolt hole 4-14x30 Slot

100

178(Duct)

Terminal block (Remote controller transmission line)

732 700

32 10

238

Drain pipe Drain pump (O.D. 32)

41

Refrigerant piping Flare connection (liquid)

217

Side View

250

Upper View

23 40

Front View

122

15

33

Product Dimensions

2 100 30

PEAD-M60,71JA

643(Suspension bolt pitch)

32)

23

57 20 40

58

32)

PEAD-M35,50JA PEAD-M100,125JA

57

67 356

Drain pipe Terminal block (Spontaneous draining) (Indoor/Outdoor connecting line)

32)

Model

10

136

C

Air inlet

A

Air outlet

B(Suspension bolt pitch)

D (Duct)

100x(E-1)=F

Control box Refrigerant piping Flare connection (gas)

PEAD-M140JA

3

51 / 49 51 / 49 69 69 116 123 1050 x 330 + 40 x 1338 1050 x 330 + 40 x 1338 220-240v, 50Hz 380-415v,50Hz Single Three 2.598 / 2.272 2.598 / 2.272 2.07 / 1.95 2.07 / 1.95 13.0 6.0 10.54 / 9.07 [29.2] 3.51 / 3.01 [10.7] 32 16 3 5 100 100 30 30

A 900 1100 1400 1600

B 954 1154 1454 1654

D C 1000 860 1200 1060 1500 1360 1700 1560

E 9 11 14 16

F 800 1000 1300 1500

PUZ-ZM125VKA PUZ-ZM125YKA 52 / 50 70 116 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 3.349 / 3.333 2.68 / 2.86 13.0 13.21/ 13.10 [29.3] 32 3 100 30

3

PUZ-ZM140VKA PUZ-ZM140YKA

52 / 50 52 / 50 70 70 125 118 1050 x 330 + 40 x 1338 1050 x 330 + 40 x 1338 380-415v,50Hz 220-240v, 50Hz Three Single 3.349 / 3.333 3.970 / 3.631 2.68 / 2.86 3.16 / 3.11 6.0 13.0 4.45 / 4.41 [12.3] 15.74 / 14.21 [30.8] 16 40 5 3 100 100 30 30

3

52 / 50 70 131 1050 x 330 + 40 x 1338 380-415v,50Hz Three 3.970 / 3.631 3.16 / 3.11 6.0 5.58 / 4.87 [15.8] 16 5 100 30


PCA-M R32 Power Inverter Heat Pump Ceiling Suspended System Product Specifications PCA-M60KA

PCA-M50KA

PCA-M - INDOOR  UNITS CAPACITY (kW)

Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)

5.5 (2.5-6.6) 5.0 (2.3-5.6) 4.7 (2.15-5.6) 4.6 (2.1-5.15) SHF (nominal) 0.79 COP / EER (nominal) 4.04 / 4.00 SCOP / SEER (BS EN14825) 4.2 / 6.7 ERP ENERGY  EFFICIENCY  CLASS Heating/Cooling A+ / A++ AIRFLOW (l/s) Lo-Mi1-Mi2-Hi 167-183-217-250 PIPE  SIZE MM (in) Gas/Liquid 12.7 (1/2”) / 6.35 (1/4”) SOUND  PRESSURE  LEVEL (dBA) Lo-Mi1-Mi2-Hi 32-34-37-40 SOUND  POWER  LEVEL (dBA) 60 DIMENSIONS (mm) Width x Depth x Height 960 x 680 x 230 WEIGHT (kg) 26 ELECTRICAL SUPPLY Fed by Outdoor Unit FUSE  RATING (BS88) - HRC (A) 6 INTERCONNECTING  CABLE  No. Cores 4 WIRED REMOTE CONTROLLER REFERENCE PAR-33MAA WIRELESS REMOTE CONTROLLER REFERENCE PAR-SL94B

PUZ-ZM -  OUTDOOR UNITS SOUND  PRESSURE  LEVEL (dBA) SOUND  POWER  LEVEL (dBA) WEIGHT (kg) DIMENSIONS (mm) ELECTRICAL  SUPPLY PHASE SYSTEM POWER  INPUT (kW)

Heating/Cooling Cooling Width x Depth x Height

Heating/Cooling (nominal) Heating/Cooling (UK)

STARTING  CURRENT (A) SYSTEM RUNNING CURRENT (A) Heating/Cooling [MAX] FUSE RATING (BS88) - HRC (A) MAINS CABLE NO. CORES MAX PIPE LENGTH (m) MAX HEIGHT DIFFERENCE (m) CHARGE REFRIGERANT (kg) / R32 (GWP 675) - 30m CO2 EQUIVALENT (t) MAX ADDITIONAL REFRIGERANT (kg) / R32 (GWP 675) CO2 EQUIVALENT (t)

PCA-M71KA

7.0 (2.8-8.2) 8.0 (3.5-10.2) 6.1 (2.7-6.7) 7.1 (3.3-8.1) 5.95 (2.4-6.95) 6.8 (3.0-8.65) 5.5 (2.5-6.15) 6.55 (3.05-7.45) 0.81 0.76 4.01 / 4.01 3.71 / 3.88 4.1 / 6.5 4.2 / 6.7 A+ / A++ A+ / A++ 250-267-283-317 267-283-300-333 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 33-35-37-40 35-37-39-41 60 62 1280 x 680 x 230 1280 x 680 x 230 32 32 Fed by Outdoor Unit Fed by Outdoor Unit 6 6 4 4 PAR-33MAA PAR-33MAA PAR-SL94B PAR-SL94B

PCA-M100KA

PCA-M100KA

PCA-M125KA

PCA-M125KA

PCA-M140KA

PCA-M140KA

11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.77 3.71 / 4.10 4.3 / 6.4 A+ / A++ 367-400-433-467 15.88 (5/8”) / 9.52 (3/8”) 37-39-41-43 63 1600 x 680 x 230 37 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B

11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.77 3.71 / 4.10 4.3 / 6.3 A+/ A++ 367-400-433-467 15.88 (5/8”) / 9.52 (3/8”) 37-39-41-43 63 1600 x 680 x 230 37 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B

14.0 (5.0-16.0) 12.5 (5.5-14.0) 11.9 (4.25-13.6) 11.5 (5.05-12.9) 0.72 3.54 / 3.25 4.3 / 6.2 A+ / A++ 383-417-450-483 15.88 (5/8”) / 9.52 (3/8”) 39-41-43-45 65 1600 x 680 x 230 38 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B

14.0 (5.0-16.0) 12.5 (5.5-14.0) 11.9 (4.25-13.6) 11.5 (5.05-12.9) 0.72 3.54 / 3.25 4.3 / 6.1 A+ / A++ 383-417-450-483 15.88 (5/8”) / 9.52 (3/8”) 39-41-43-45 65 1600 x 680 x 230 38 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B

16.0 (5.7-18.0) 13.4 (6.2-15.0) 13.6 (4.85-15.3) 12.9 (5.7-13.8) 0.72 3.61 / 3.40 4.4 / 6.2 A+ / A++ 400-433-483-533 15.88 (5/8”) / 9.52 (3/8”) 41-43-45-48 68 1600 x 680 x 230 40 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B

16.0 (5.7-18.0) 13.4 (6.2-15.0) 13.6 (4.85-15.3) 12.9 (5.7-13.8) 0.72 3.61 / 3.40 4.4 / 6.1 A+/ A++ 400-433-483-533 15.88 (5/8”) / 9.52 (3/8”) 41-43-45-48 68 1600 x 680 x 230 40 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B

PUZ-ZM50VKA

PUZ-ZM60VHA

PUZ-ZM71VHA

PUZ-ZM100VKA

PUZ-ZM100YKA

3

PUZ-ZM125VKA

PUZ-ZM125YKA

46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 1.361 / 1.25 1.21 / 1.06 5.0 5.95 / 5.37 [13.4] 16 3 50 30

49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 1.745 / 1.521 1.55 / 1.29 6.0 7.43 / 6.48 [19.4] 25 3 55 30

49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 2.156 / 1.829 1.92 / 1.55 6.0 9.23 / 7.81 [19.4] 25 3 55 30

51 / 49 69 116 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 3.018 / 2.317 2.41 / 1.99 13.0 12.97 / 9.97 [27.2] 32 3 100 30

51 / 49 69 123 1050 x 330 + 40 x 1338 380-415v,50Hz Three 3.018 / 2.317 2.41 / 1.99 6.0 4.34 / 3.31 [8.7] 16 5 100 30

52 / 50 70 116 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 3.954 / 3.846 3.51 / 3.26 13.0 16.87 / 16.46 [27.3] 32 3 100 30

52 / 50 70 125 1050 x 330 + 40 x 1338 380-415v,50Hz Three 3.954 / 3.846 3.51 / 3.26 6.0 5.69 / 5.54 [10.3] 16 5 100 30

3

3

PUZ-ZM140VKA

PUZ-ZM140YKA

52 / 50 70 118 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 4.432 / 3.941 3.94 / 3.35 13.0 18.76 / 16.66 [28.9] 40 3 100 30

52 / 50 70 131 1050 x 330 + 40 x 1338 380-415v,50Hz Three 4.432 / 3.941 3.94 / 3.35 6.0 6.42 / 5.71 [13.9] 16 5 100 30

2.00 / 1.35

2.80 / 1.89

2.80 / 1.89

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

4.00 / 2.70

0.30 / 0.20

0.80 / 0.54

0.80 / 0.54

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

2.80 / 1.89

3 Three Phase

Product Dimensions Front View

Product Dimensions

PCA-M50KA

Upper View

Front View

Side View

PCA-M60/71KA

Upper View

A

Side View

Product Dimensions Front View

PCA-M100/125/140KA

Upper View

Side View

51 10

51 51

5

2

182 1198

Air intake

85

57 680

230

195

84 88

Air outlet A

(Drainage)

1600 1493

B

A

60

71

B

179 203

180 200

246

233

(liquid) (gas)

drain socket (isWhen ( installed

182

(Drainage)

1518

Air intake

85

2

10 5

Air outlet

236

(liquid ( (gas (

drain socket ( ( When is installed

878

Air intake

10

57 476

680

230

184 203 246

254

Air outlet

195

84 88

57 680 476 254 85

2

1173

233 182

1280

2

84 88 195 230

5

476

2

853

254

960

236

2

180 200 233 246

(liquid) (gas)

drain socket (When ( is installed (Drainage)


PUZ-ZM R32 Power Inverter Heat Pump Outdoor Unit Product Specifications

PUHZ-ZRP50VKA

O

Product Dimensions

Product Dimensions

PUZ-ZM35/50VKA

Upper View

Front View

Side View

PUZ-ZM60/71VHA

Upper View

Front View

Side View

404.5

Rear air intake

154.5 310

Service port

Front View

2-U shaped notched holes (foundation bolt M10) 600 Installation Feet

225

Handle for moving

(19)

225

19

362

Air discharge

Side View

1050 Earth terminal Terminal connection Left...Power supply wiring Right..Indoor/Outdoor wiring

61 42 2-12 36 Oval holes (foundation bolt M10)

56 40 0 53

1 2 Refrigerant GAS pipe Refrigerant LIQUID pipe connection connection

Service panel Handle for moving

1338 632

1

Air Intake

ø15.88 (5/8F)

ø9.52 (3/8F)

A

Air Discharge

75

28

40

330

370 417

Side Air Intake

MODEL 2

2

B

C

26

369

2

A

B

C

PUZ-ZM100-140VKA

1067

442

450

PUZ-ZM100-140YKA

919

442

450

Front piping cover Rear piping cover

Telephone: 01707 282880 email: air.conditioning@meuk.mee.com web: airconditioning.mitsubishielectric.co.uk microsite: timeforR32.co.uk UNITED KINGDOM Mitsubishi Electric Europe Living Environment Systems Division, Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, England. General Enquiries Telephone: 01707 282880 Fax: 01707 278881 IRELAND Mitsubishi Electric Europe, Westgate Business Park, Ballymount, Dublin 24, Ireland. Telephone: Dublin (01) 419 8800 Fax: Dublin (01) 419 8890 International code: (003531) Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi Electric Europe 2017. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation in technical specification to the equipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to the Company’s General Conditions of Sale, a copy of which is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners. Note: The fuse rating is for guidance only. Please refer to the relevant databook for detailed specification. It is the responsibility of a qualified electrician/electrical engineer to select the correct cable size and fuse rating based on current regulation and site specific conditions. Mitsubishi Electric’s air conditioning equipment and heat pump systems contain a fluorinated greenhouse gas, R410A (GWP:2088), R32 (GWP:675), R407C (GWP:1774) or R134a (GWP:1430). *These GWP values are based on Regulation (EU) No 517/2014 from IPCC 4th edition. In case of Regulation (EU) No.626/2011 from IPCC 3rd edition, these are as follows. R410A (GWP:1975), R32 (GWP: 550), R407C (GWP:1650) or R134a (GWP:1300).

Effective as of October 2017

SAP No. 317318

447

41

673

943

417

40 54 57

2-12 36 oval holes (foundation bolt M10)

PUZ-ZM100/125/140VKA, PUZ-ZM100/125/140YKA

Upper View Rear Air Intake

Handle for moving

Front piping cover Rear piping cover

1

R

Service panel

62

809

Product Dimensions

Earth terminal

23

Installation bolt pitch 500

322

431

Connection for gas pipe FLARE 12.7 (1/2F)

Handle for moving

473

Connection for liquid pipe FLARE 6.35 (1/4F)

8.5

4-10×21 oval hole

175

Installation Feet

330

630

Service panel 320

32.5

40

600

950 2 U-shaped notched holes (Foundation Bolt M10)

28

Air intake Air discharge

175

Side air intake

Earth terminal

30

300 330

360

Service panel for charge plug

53

22.3

370

Handle for moving

42 drain hole

48

Air intake

1...Indication of Terminal connection location. 2...Indication of STOP VALVE connection location.


timeforR32.co.uk


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.