The Mr Slim R32 Power Inverter Range A blend of energy efficiency and sophisticated design
It’s time to enjoy energy savings and great new product features
It’s time to put R32 refrigerant at the heart of your conversations and plans moving forward, with the market leading range of R32 products from Mitsubishi Electric
It’s time for your air conditioning to help meet EU carbon emissions targets
The 2014 F-Gas Regulations have one key objective: to reduce F-Gas emissions by 79% between 2015 and 2030, by cutting the availability of hydrofluorocarbons (HFCs) with a high Global Warming Potential (GWP). It’s time therefore to look at alternative, low GWP refrigerants such as R32. Already making up 50% of the existing R410A refrigerant found in many current air conditioning systems, R32 has a GWP of 675 (one third that of R410A), is highly energy efficient and is easy to recycle. Plus, the volumetric capacity of R32 is around 20% higher than that of R410A, which means system refrigerant volumes are lower.
Benefits of R32
Low GWP of 675 High efficiency refrigerant F-Gas phase down compliant Less refrigerant volume requirement compared to R410A Affordable & readily available A single component refrigerant Easy to handle, reuse and recycle
The Mr Slim R32 Power Inverter Range The Mr Slim R32 Power Inverter range blends a host of outstanding features with a premium quality, sophisticated design. Offering our highest seasonal efficiency levels, advanced control options and extended pipe runs, this range is extremely flexible and available in four different indoor unit types, from 3.5 to 14kW.
Industry Leading Seasonal Energy Efficiency Ratings The R32 Power Inverter is able to achieve high seasonal efficiencies through the optimisation of a newly designed compressor and use of the latest energy-saving technologies. ERP energy efficiency ratings of A++ are common throughout the range, with annual power consumption drastically reduced, resulting in increased run cost savings. Heating / Cooling
Indoor Unit
3.5kW
PLA-ZM 4-Way Blow Ceiling Cassette
5.0kW
6.0kW
7.1kW
10.0kW
12.5kW
14.0kW
A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++
PKA-M Wall Mounted PEAD-M Ceiling Concealed Ducted PCA-M Ceiling Suspended
A+ / A++
A+ / A++
A+ / A++
A+ / A++
A+ / A++
-
-
A / A+
A+ / A++
A+ / A++
A / A+
A+ / A++
A / A+
A+ / A+
-
A+ / A++
A+ / A++
A+ / A++
A+ / A++
A+ / A++
A+ / A++
3-Phase Power Supply The 10.0, 12.5 and 14.0kW models are also available as a 3-phase option. Choosing this option dramatically reduces the running current of the unit and subsequent fuse rating. Power Supply 3-Phase
10.0kW
12.5kW
14.0kW
Max Running Current (A)
8.5
10.0
13.7
Fuse Rating (A)
16
16
16
10.0kW
12.5kW
14.0kW
27.0
27.0
28.7
32
32
40
Power Supply Single Phase
Max Running Current (A) Fuse Rating (A)
Note: Example using a 4-Way Blow Ceiling Cassette
10.0 / 12.5 / 14.0kW PUZ-ZM100-140VKA/YKA 6.0 / 7.1kW PUZ-ZM60/71VHA 3.5 / 5.0kW PUZ-ZM35/50VKA
Increased Pipe Lengths Pipe lengths of up to 100m with a 30m height difference are now available with the R32 Power Inverter, increasing the application possibilities of the range. Outdoor Unit
Max Pipe Length (m)
Max Height Difference (m)
PUZ-ZM35/50VKA
50
30
PUZ-ZM60/71VHA
55 (5m increase over R410A PUHZ-ZRP Power Inverter)
30
100 (25m increase over R410A PUHZ-ZRP Power Inverter)
30
PUZ-ZM100/125/140VKA/YKA
Full Heating Capacity Down to -3ยบC
Height Difference 30m Pipe Length 100m
R32
1.6
Designed to provide powerful heating, even on bitterly cold or snowy days. When compared to the R410A Power Inverter, the rated heating capacity is maintained down to outside temperatures of -3ยบC.
PUZ-ZM
1.4 1.2 1.0 0.8 0.6
Multi-Split Applications
R410A
0.4
The R32 Power Inverter can be used as a Multi-Split, making it an ideal option for open plan spaces in medium sized premises such as shops or offices, where two or three indoor units are required connected to a single outdoor unit. The indoor units can be a mix of ceiling cassettes, wall mounted, ceiling concealed ducted or ceiling suspended types.
PUHZ-ZRP
0.2 -3ยบC
Outside Temperature
Twin Indoor Units
5ยบC
Triple Indoor Units
Outdoor Unit Capacity Twin
Triple
Indoor Unit Combination
7.1kW
10.0kW
12.5kW
14.0kW
14.0kW
PLA-ZM
3.5 x 2
5.0 x 2
6.0 x 2
7.1 x 2
5.0 x 3
PKA-M
3.5 x 2
5.0 x 2
6.0 x 2
7.1 x 2
5.0 x 3
PEAD-M
3.5 x 2
5.0 x 2
6.0 x 2
7.1 x 2
5.0 x 3
-
5.0 x 2
6.0 x 2
7.1 x 2
5.0 x 3
PCA-M
Multi Distributor Pipes
Outdoor Unit
Multi Distributor Pipes
Outdoor Unit
Built using micron-precise calculations, the compressor is the heart of the R32 Power Inverter air conditioning system
Poki-Poki Motor
Dramatically enhanced motor efficiency utilising Mitsubishi Electric’s original dense winding technology.
Heat Caulking
Mitsubishi Electric’s heat caulking method minimises cylinder distortion for even greater efficiency.
30Pa External Static Pressure An external static pressure of 30Pa enables the outdoor unit to be installed on balconies in high-rise buildings or spaces near louvres.* * Optional (requires PAC-SJ71FM-E). Rated noise levels may be higher when equipped with this option.
Solutions that address the ban on R22 refrigerant As of 1st January 2015 it became illegal to use R22 refrigerant*1 to service and maintain air conditioning units, yet there are a large number of systems still in use in the UK that rely on R22. Many of these building operators remain unaware that whilst their air conditioning will not be illegal to run, it may need immediate replacement if it requires maintenance involving any degassing of the system. The continual rise in energy costs also means everyone involved in the built environment is focusing on energy use and consumption and this is where modern equipment can really help to support replacement. The R32 Power Inverter models incorporate our unique ‘Replace Technology’ which allows the upgrade of systems using existing pipe work, without the need to apply any special cleaning machines.
*1 The EC Ozone Regulation (No.1005/2009) was introduced to control and phase out the remaining uses of all Ozone Depleting Substances (ODS) such as R22 refrigerant. This has led to a total ban on its use for service and maintenance by the start of the year 2015. ODS can result in greater UV radiation reaching the earth’s surface which is harmful for humans, animals and plants, leading to increases in skin cancer, cataracts and a reduction in food crop yields. Modern alternatives such as HFC’s, which include R32, do not have the same ozone depleting potential (ODP).
PLA-ZM 4-Way Blow Ceiling Cassette System
The new square grille design of the PLA-ZM beautifully harmonises with any interior, making it ideal for applications such as offices or retail stores. Horizontal Airflow Control New horizontal airflow control helps remove uncomfortable draughts and improve comfort levels.
Optional 3D i-see Sensor Highly accurate 360ยบ motion detection for body temperature and room occupancy, improving efficiency and comfort through automatic selection of energy-saving modes.
Optional Filter Lowering Grille
Controller Options
Allows easy, regular cleaning of the filter, improving efficiency and reducing maintenance.
8 sensors
rotate a full 360ยบ in 3 minute intervals
This feature is particularly useful in rooms that have a high ceiling Detects position and number of people Detects body and floor temperature
1.2m 1.6m 2.0m 2.4m
PAR-33MAA Wired Controller
2.8m 3.2m 3.6m 4.0m max
NEW PAR-SL100A-E Backlit Wireless Controller
PKA-M Wall Mounted System
Flat panel is easy to clean
The PKA-M blends a host of outstanding features with a sophisticated pure white, flat panel, streamlined design. Offering high seasonal efficiency, advanced control options and quiet operation, this range provides extreme flexibility and ease of installation. Improved airflow control, including adjustable louvres for uniform air distribution Internal pipe connection to wall mounted unit for easy and neat installation Compact Indoor Units Indoor unit width has been reduced by as much as 510mm. Units take up much less space, greatly increasing installation possibilities. PKA-M35/50HA
PKA-M60/71KA
Controller Options CN22 connector as standard for connection to PAR-33MAA wired controller
92mm DOWN* *Compared to PKA-RP35/50GA
230mm DOWN* *Compared to PKA-RP60/71FA
PKA-M100KA
510mm DOWN* *Compared to PKA-RP100FA
PAR-33MAA Wired Controller
PAR-FL32MA Wireless Controller
PEAD-M Ceiling Concealed Ducted System
The PEAD-M includes a host of outstanding features with an unobtrusive design for easy installation and maintenance.
Compact Indoor Units
External Static Pressure
The height of all models has been unified to 250mm. Compared to the previous PEAD-RP EA range, this has seen a reduction by as much as 75mm (sizes 100-140), making installation in low ceilings with a minimal clearance space possible.
The external static pressure can be set to five stages, up to a maximum of 150Pa, making units applicable for a wide range of building types. This is now standard on all unit sizes. External static pressure setting Model / Size PEAD-M
35
50
60
71
100
125
35/50/70/100/150Pa
250mm Reduction of
75mm
(models 100-140) compared to PEAD-RP EA
Drain pump is included as standard
140
PAR-33MAA Wired Controller
PCA-M Ceiling Suspended System
The PCA-M incorporates a stylish new indoor unit design with airflow settings for both high and low ceiling applications, expanding the installation possibilities of this unit.
Controller Options
Stylish Indoor Unit Design
PAR-SL94B Wireless Controller and receiver
PAR-33MAA Wired Controller
A new stylish square-like design allows these units to blend in seamlessly with the ceiling.
Automatic Air-speed Adjustment In addition to the conventional 4-speed setting, units are now equipped with an automatic air-speed adjustment mode. This setting automatically adjusts the air speed to conditions that match the room environment. At the start of the heating/cooling operation, the airflow is set to high-speed to quickly heat/cool the room. When the room temperature reaches the desired setting, the airflow speed is decreased automatically creating a stable, comfortable environment.
Units are equipped with high and low ceiling operation modes that make it possible to switch the airflow volume to match room height. The ability to choose the optimum airflow volume makes it possible to reduce draughts. High Ceiling
Standard Ceiling
Gentle
Start of cooling/heating
After room temperature is stabilised
Optional Drain Pump
High / Low Ceiling Modes
Size
Strong
Low Ceiling
50
3.5m
2.7m
2.5m
60
3.5m
2.7m
2.5m
71
3.5m
2.7m
2.5m
100
4.2m
3.0m
2.6m
125
4.2m
3.0m
2.6m
140
4.2m
3.0m
2.6m
The pumping height of the optional drain pump has been increased from 400mm to 600mm, expanding the location possibilities of the unit. Drainage outlet can be 600mm above ceiling surface
Outside air Intake Unts are equipped with a knock-out hole that enables the induction of fresh air. Outside air intake characteristics 50 0 -50 -100
Ceiling surface
-150 -200 -250 -300
0
1
2
Airflow volume (m3/min)
PCA-M100-140
PCA-M60/71
3
PCA-M50
4
Mobile control and monitoring of your Mitsubishi Electric systems MELCloud is a cloud based solution for controlling and monitoring your Mitsubishi Electric air conditioning, ventilation or heating systems either locally or remotely by PC, tablet or smartphone app. It offers the ability to control which units are on/off, temperature settings, the 7 day weekly schedule, frost protection settings, holiday mode and also log and record errors. Ensuring total flexibility from a single device, from any worldwide location, the MELCloud app also provides localised information like weather forecasts and customer service contact details.
MAC-567IF Optional Wi-Fi Interface
PLA-ZM R32 Power Inverter Heat Pump 4-Way Blow Ceiling Cassette System Product Specifications PLA-ZM35EA
PLA-ZM - INDOOR UNITS CAPACITY (kW)
PLA-ZM50EA
PLA-ZM60EA
PLA-ZM71EA
PLA-ZM100EA
PLA-ZM100EA
PLA-ZM125EA
PLA-ZM125EA
PLA-ZM140EA
PLA-ZM140EA
Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)
7.0 (2.8-8.2) 4.1 (1.6-5.2) 6.0 (2.5-7.3) 8.0 (3.5-10.2) 11.2 (4.5-14.0) 11.2 (4.5-14.0) 14.0 (5.0-16.0) 14.0 (5.0-16.0) 16.0 (5.7-18.0) 16.0 (5.7-18.0) 6.1 (2.7-6.5) 3.6 (1.6-4.5) 5.0 (2.3-5.6) 7.1 (3.3-8.1) 9.5 (4.9-11.4) 9.5 (4.9-11.4) 12.5 (5.5-14.0) 12.5 (5.5-14.0) 13.4 (6.2-15.0) 13.4 (6.2-15.0) 3.5 (1.35-4.4) 5.1 (2.15-6.2) 6.8 (3.0-8.65) 9.5 (3.85-11.9) 9.5 (3.85-11.9) 11.9 (4.25-13.6) 11.9 (4.25-13.6) 13.6 (4.85-15.3) 13.6 (4.85-15.3) 6.0 (2.38-6.97) 3.3 (1.45-4.15) 4.6 (2.1-5.15) 6.55 (3.05-7.45) 9.2 (4.5-10.5) 9.2 (4.5-10.5) 11.5 (5.05-12.9) 11.5 (5.05-12.9) 12.9 (5.7-14.1) 12.9 (5.7-14.1) 5.6 (2.48-5.98) 0.77 0.95 0.85 0.72 0.77 0.77 0.70 0.70 0.70 0.70 SHF (nominal) 4.10 / 4.20 5.00 / 5.10 4.40 / 4.52 4.40 / 4.30 4.30 / 4.60 4.30 / 4.60 3.81 / 3.70 3.81 / 3.70 3.71 / 3.60 3.71 / 3.60 COP / EER (nominal) 4.60 / 7.20 4.70 / 7.50 4.90 / 7.60 4.80 / 7.60 4.80 / 7.70 4.80 / 7.50 4.70 / 7.40 4.70 / 7.20 4.60 / 7.00 4.60 / 6.90 SCOP / SEER (BS EN14825) A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ ERP ENERGY EFFICIENCY CLASS Heating/Cooling 183-217-250-267 200-233-267-300 283-317-350-383 317-367-417-467 317-367-417-467 350-400-433-483 350-400-433-483 400-433-483-533 400-433-483-533 200-233-267-300 AIRFLOW (l/s) Lo-Mi-Mi2-Hi 12.7 (1/2”) / 6.35 (1/4”) 12.7 (1/2”) / 6.35 (1/4”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) PIPE SIZE MM (in) Gas/Liquid 27-29-31-32 26-28-29-31 27-29-31-32 28-30-33-36 31-34-37-40 31-34-37-40 33-36-39-41 33-36-39-41 36-39-42-44 36-39-42-44 SOUND PRESSURE LEVEL (dBA) Lo-Mi-Mi2-Hi 54 51 54 57 61 61 62 62 65 65 SOUND POWER LEVEL (dBA) DIMENSIONS (mm) Width x Depth x Height (Grille) 840 (950) x 840 (950) x 258 (40) 840 (950) x 840 (950) x 258 (40) 840 (950) x 840 (950) x 258 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 840 (950) x 840 (950) x 298 (40) 21 / 5 21 / 5 21 / 5 24 / 5 26 / 5 26 / 5 26 / 5 26 / 5 26 / 5 26 / 5 WEIGHT (kg) Unit / Grille Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit ELECTRICAL SUPPLY 6 6 6 6 6 6 6 6 6 6 FUSE RATING (BS88) - HRC (A) 4 4 4 4 4 4 4 4 4 4 INTERCONNECTING CABLE NO. CORES PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA PLP-6EA GRILLE REFERENCE PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA WIRED REMOTE CONTROLLER REFERENCE PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E WIRELESS REMOTE CONTROLLER REFERENCE
PUZ-ZM - OUTDOOR UNITS SOUND PRESSURE LEVEL (dBA) SOUND POWER LEVEL (dBA) WEIGHT (kg) DIMENSIONS (mm) ELECTRICAL SUPPLY PHASE SYSTEM POWER INPUT (kW) STARTING CURRENT (A) SYSTEM RUNNING CURRENT (A) FUSE RATING (BS88) - HRC (A) MAINS CABLE NO. CORES MAX PIPE LENGTH (m) MAX HEIGHT DIFFERENCE (m) CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t) MAX ADDITIONAL REFRIGERANT (kg) / CO2 EQUIVALENT (t)
Heating/Cooling Cooling Width x Depth x Height
Heating/Cooling (nominal) Heating/Cooling (UK) Heating/Cooling [MAX]
R32 (GWP 675) - 30m R32 (GWP 675)
PUZ-ZM60VHA
PUZ-ZM71VHA
PUZ-ZM100VKA PUZ-ZM100YKA
3
Lower View
PUZ-ZM125YKA
52 / 50 70 116 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 3.674 / 3.378 3.27 / 2.87 13.0 15.77 / 14.53 [27.0] 32 3 100 30
52 / 50 52 / 50 70 70 125 118 1050 x 330 + 40 x 1338 1050 x 330 + 40 x 1338 380-415v, 50Hz 220-240v, 50Hz Three Single 3.674 / 3.378 4.312 / 3.772 3.27 / 2.87 3.83 / 3.15 6.0 13.0 5.32 / 4.89 [10.0] 18.41 / 15.88 [28.7] 16 40 5 3 100 100 30 30
46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 0.820 / 0.705 0.73 / 0.59 5.0 3.89 / 3.51 [13.2] 16 3 50 30
46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 1.363 / 1.106 1.21/ 0.94 5.0 6.05 / 5.00 [13.2] 16 3 50 30
2.0 / 1.35
2.00 / 1.35
2.80 / 1.89
2.80 / 1.89
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
0.30 / 0.20
0.30 / 0.20
0.80 / 0.54
0.80 / 0.54
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
49 / 47 49 / 47 67 67 70 70 950 x 330 + 25 x 943 950 x 330 + 25 x 943 220-240v, 50Hz 220-240v, 50Hz Single Single 1.707 / 1.452 1.818 / 1.651 1.43 / 1.15 1.61 / 1.39 6.0 6.0 7.39 / 6.31 [19.2] 7.79 / 7.06 [19.3] 25 25 3 3 55 55 30 30
51 / 49 51 / 49 69 69 116 123 1050 x 330 + 40 x 1338 1050 x 330 + 40 x 1338 220-240v, 50Hz 380-415v, 50Hz Single Three 2.604 / 2.065 2.604 / 2.065 2.09 / 1.77 2.09 / 1.77 13.0 6.0 11.25 / 8.97 [27.0] 3.75 / 2.96 [8.5] 32 16 3 5 100 100 30 30
PLA-ZM35-140EA
Upper View
Front View
Side View
PUZ-ZM140VKA
PUZ-ZM140YKA
PUZ-ZM50VKA
3 Three Phase
Product Dimensions
3
PUZ-ZM125VKA
PUZ-ZM35VKA
3
52 / 50 70 131 1050 x 330 + 40 x 1338 380-415v, 50Hz Three 4.312 / 3.772 3.83 / 3.15 6.0 6.23 / 5.37 [13.7] 16 5 100 30
PKA-M R32 Power Inverter Heat Pump Wall Mounted System Product Specifications PKA-M - INDOOR UNITS Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)
CAPACITY (kW)
SHF (nominal) COP / EER (nominal) SCOP / SEER (BS EN14825) ERP ENERGY EFFICIENCY CLASS AIRFLOW (l/s) PIPE SIZE MM (in)
Heating/Cooling Lo-Mi-Hi Gas Liquid Lo-Mi-Hi
SOUND PRESSURE LEVEL (dBA) SOUND POWER LEVEL (dBA) DIMENSIONS (mm) Width x Depth x Height WEIGHT (kg) ELECTRICAL SUPPLY FUSE RATING (BS88) - HRC (A) INTERCONNECTING CABLE NO. CORES WIRED REMOTE CONTROLLER REFERENCE WIRELESS REMOTE CONTROLLER REFERENCE
PUZ-ZM - OUTDOOR UNITS SOUND PRESSURE LEVEL (dBA) SOUND POWER LEVEL (dBA) WEIGHT (kg) DIMENSIONS (mm) ELECTRICAL SUPPLY PHASE SYSTEM POWER INPUT (kW) STARTING CURRENT (A) SYSTEM RUNNING CURRENT (A) FUSE RATING (BS88) - HRC (A) MAINS CABLE NO. CORES MAX PIPE LENGTH (m) MAX HEIGHT DIFFERENCE (m) CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t) MAX ADDITIONAL REFRIGERANT (kg) / CO2 EQUIVALENT (t)
Heating/Cooling Cooling Width x Depth x Height
Heating/Cooling (nominal) Heating/Cooling (UK) Heating/Cooling [MAX]
PKA-M35HA
PKA-M50HA
PKA-M60KA
PKA-M71KA
PKA-M100KA
PKA-M100KA
4.1 (1.6-5.2) 3.6 (1.6-4.5) 3.5 (1.35-4.4) 3.3 (1.45-4.15) 0.81 3.94 / 4.14 4.0 / 6.3 A+ / A++ 150-175-200 12.7 (1/2”) 6.35 (1/4”) 36-40-43 60 898 x 249 x 295 13 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA
5.0 (2.5-7.3) 4.6 (2.3-5.6) 4.25 (2.15-6.2) 4.23 (2.1-5.15) 0.72 3.71 / 3.71 4.1 / 6.4 A+ / A++ 150-175-200 12.7 (1/2”) 6.35 (1/4”) 36-40-43 60 898 x 249 x 295 13 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA
7.0 (2.8-8.2) 6.1 (2.7-6.7) 5.95 (2.4-6.95) 5.5 (2.5-6.15) 0.86 4.04 / 3.91 4.2 / 6.8 A+ / A++ 300-333-367 15.88 (5/8”) 9.52 (3/8”) 39-42-45 64 1170 x 295 x 365 21 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA
8.0 (3.5-10.2) 7.1 (3.3-8.1) 6.8 (3.0-8.65) 6.55 (3.05-7.45) 0.78 3.78 / 3.81 4.3 / 6.8 A+ / A++ 300-333-367 15.88 (5/8”) 9.52 (3/8”) 39-42-45 64 1170 x 295 x 365 21 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA
11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.73 3.61 / 3.95 4.4 / 6.5 A+ / A++ 333-383-433 15.88 (5/8”) 9.52 (3/8”) 41-45-49 65 1170 x 295 x 365 21 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA
11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.73 3.61 / 3.95 4.4 / 6.4 A+ / A++ 333-383-433 15.88 (5/8”) 9.52 (3/8”) 41-45-49 65 1170 x 295 x 365 21 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-FL32MA
PUZ-ZM35VKA
PUZ-ZM50VKA
PUZ-ZM60VHA
PUZ-ZM71VHA
PUZ-ZM100VKA
PUZ-ZM100YKA
46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 1.040 / 0.869 0.81 / 0.84 5.0 4.97 / 4.31 [13.4] 16 3 50 30
46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 1.347 / 1.239 1.12 / 1.12 5.0 5.98 / 5.57 [13.4] 16 3 50 30
49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 1.732 / 1.560 1.25 / 1.65 6.0 7.41 / 6.65 [19.4] 25 3 55 30
49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 2.116 / 1.863 1.54 / 1.92 6.0 9.10 / 7.96 [19.4] 25 3 55 30
51 / 49 69 116 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 3.102 / 2.405 2.47 / 2.06 13.0 13.46 / 10.45 [27.1] 32 3 100 30
51 / 49 69 123 1050 x 330 + 40 x 1338 380-415v, 50Hz Three 3.102 / 2.405 2.47 / 2.06 6.0 4.49 / 5.45 [8.6] 16 5 100 30
2.0 / 1.35
2.00 / 1.35
2.80 / 1.89
2.80 / 1.89
4.00 / 2.70
4.00 / 2.70
0.30 / 0.20
0.30 / 0.20
0.80 / 0.54
0.80 / 0.54
2.80 / 1.89
2.80 / 1.89
R32 (GWP 675) - 30m R32 (GWP 675)
3
3 Three Phase
Product Dimensions
Product Dimensions
PKA-M35/50HA
Upper View
Front View
Side View
PKA-M60/71/100KA
Upper View
Front View
Side View
192
387
365
431.7
599
55
688
155 898
249
5
11
140.3
197
295
65.2
423.7
74
(855)
241 1170
295
5
PEAD-M R32 Power Inverter Heat Pump Ceiling Concealed Ducted System Product Specifications PEAD-M35JA
PEAD-M50JA
PEAD-M60JA
PEAD-M71JA
PEAD-M100JA
PEAD-M100JA
PEAD-M125JA
PEAD-M125JA
PEAD-M140JA
PEAD-M140JA
4.1 (1.6-5.2) 3.6 (1.6-4.5) 3.5 (1.35-4.4) 3.3 (1.45-4.15) 0.85 4.47 / 4.30 3.9 / 5.8 A / A+ 167-200-233 12.7 (1/2”) 6.35 (1/4”) 35-50-70-100-150 23-27-30 54 900 x 732 x 250 26 Fed by Outdoor Unit 6 4 PAR-33MAA
6.0 (2.5-7.3) 5.0 (2.3-5.6) 5.1 (2.15-6.2) 4.6 (2.1-5.15) 0.84 4.57 / 4.16 4.3 / 6.2 A+ / A++ 200-242-283 12.7 (1/2”) 6.35 (1/4”) 35-50-70-100-150 26-31-35 59 900 x 732 x 250 27 Fed by Outdoor Unit 6 4 PAR-33MAA
7.0 (2.8-8.2) 6.1 (2.7-6.7) 5.95 (2.4-6.95) 5.5 (2.5-6.15) 0.83 4.33 / 4.04 4.0 / 6.1 A+ / A++ 242-300-350 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 25-29-33 55 1100 x 732 x 250 30 Fed by Outdoor Unit 6 4 PAR-33MAA
8.0 (3.5-10.2) 7.1 (3.3-8.1) 6.8 (3.0-8.65) 6.55 (3.05-7.45) 0.83 4.14 / 3.82 3.9 / 5.8 A / A+ 292-350-417 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 26-30-34 58 1100 x 732 x 250 30 Fed by Outdoor Unit 6 4 PAR-33MAA
11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.82 4.31 / 4.18 4.1 / 6.2 A+ / A++ 400-483-567 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 29-34-38 62 1400 x 732 x 250 39 Fed by Outdoor Unit 6 4 PAR-33MAA
11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.82 4.31 / 4.18 4.1 / 6.1 A+ / A++ 400-483-567 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 29-34-38 62 1400 x 732 x 250 39 Fed by Outdoor Unit 6 4 PAR-33MAA
14.0 (5.0-16.0) 12.5 (5.5-14.0) 11.9 (4.25-13.6) 11.5 (5.05-12.9) 0.84 4.18 / 3.75 3.9 / 5.8 A / A+ 492-592-700 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 33-36-40 66 1400 x 732 x 250 40 Fed by Outdoor Unit 6 4 PAR-33MAA
14.0 (5.0-16.0) 12.5 (5.5-14.0) 11.9 (4.25-13.6) 11.5 (5.05-12.9) 0.84 4.18 / 3.75 3.9 / 5.7 A / A+ 492-592-700 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 33-36-40 66 1400 x 732 x 250 40 Fed by Outdoor Unit 6 4 PAR-33MAA
16.0 (5.7-18.0) 13.4 (6.2-15.3) 13.6 (4.85-15.3) 12.9 (5.7-14.1) 0.84 4.03 / 3.69 4.0 / 5.7 A+ / A+ 533-650-767 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 34-38-43 67 1600 x 732 x 250 44 Fed by Outdoor Unit 6 4 PAR-33MAA
16.0 (5.7-18.0) 13.4 (6.2-15.3) 13.6 (4.85-15.3) 12.9 (5.7-14.1) 0.84 4.03 / 3.69 4.0 / 5.6 A+ / A+ 533-650-767 15.88 (5/8”) 9.52 (3/8”) 35-50-70-100-150 34-38-43 67 1600 x 732 x 250 44 Fed by Outdoor Unit 6 4 PAR-33MAA
PUZ-ZM35VKA
PUZ-ZM50VKA
PUZ-ZM60VHA
PUZ-ZM71VHA
46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 0.917 / 0.837 0.76 / 0.76 5.0 4.17 / 3.89 [4.1] 16 3 50 30
46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 1.312 / 1.201 1.11 / 1.06 5.0 5.55 / 5.07 [14.4] 16 3 50 30
49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 1.616 / 1.509 1.32 / 1.39 6.0 6.68 / 6.16 [20.5] 25 3 55 30
49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 1.932 / 1.858 1.7 / 1.59 6.0 7.85 / 7.45 [21] 25 3 55 30
2.0 / 1.35
2.00 / 1.35
2.80 / 1.89
2.80 / 1.89
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
0.30 / 0.20
0.30 / 0.20
0.80 / 0.54
0.80 / 0.54
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
PEAD-M - INDOOR UNITS CAPACITY (kW)
Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)
SHF (nominal) COP / EER (nominal) SCOP / SEER (BS EN14825) ERP ENERGY EFFICIENCY CLASS AIRFLOW (l/s) PIPE SIZE MM (in)
Heating/Cooling Lo-Mi-Hi Gas Liquid
EXTERNAL STATIC PRESSURE (Pa) SOUND PRESSURE LEVEL (dBA) Lo-Mi-Hi SOUND POWER LEVEL (dBA) DIMENSIONS (mm) Width x Depth x Height WEIGHT (kg) ELECTRICAL SUPPLY FUSE RATING (BS88) - HRC (A) INTERCONNECTING CABLE NO. CORES WIRED REMOTE CONTROLLER REFERENCE
PUZ-ZM - OUTDOOR UNITS SOUND PRESSURE LEVEL (dBA) SOUND POWER LEVEL (dBA) WEIGHT (kg) DIMENSIONS (mm) ELECTRICAL SUPPLY PHASE SYSTEM POWER INPUT (kW) STARTING CURRENT (A) SYSTEM RUNNING CURRENT (A) FUSE RATING (BS88) - HRC (A) MAINS CABLE NO. CORES MAX PIPE LENGTH (m) MAX HEIGHT DIFFERENCE (m) CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t) MAX ADDITIONAL REFRIGERANT (kg) / CO2 EQUIVALENT (t)
Heating/Cooling Cooling Width x Depth x Height
Heating/Cooling (nominal) Heating/Cooling (UK) Heating/Cooling [MAX]
R32 (GWP 675) - 30m R32 (GWP 675)
PUZ-ZM100VKA PUZ-ZM100YKA
3 Three Phase
PEAD-M35-140JA Suspension bolt hole 4-14x30 Slot
100
178(Duct)
Terminal block (Remote controller transmission line)
732 700
32 10
238
Drain pipe Drain pump (O.D. 32)
41
Refrigerant piping Flare connection (liquid)
217
Side View
250
Upper View
23 40
Front View
122
15
33
Product Dimensions
2 100 30
PEAD-M60,71JA
643(Suspension bolt pitch)
32)
23
57 20 40
58
32)
PEAD-M35,50JA PEAD-M100,125JA
57
67 356
Drain pipe Terminal block (Spontaneous draining) (Indoor/Outdoor connecting line)
32)
Model
10
136
C
Air inlet
A
Air outlet
B(Suspension bolt pitch)
D (Duct)
100x(E-1)=F
Control box Refrigerant piping Flare connection (gas)
PEAD-M140JA
3
51 / 49 51 / 49 69 69 116 123 1050 x 330 + 40 x 1338 1050 x 330 + 40 x 1338 220-240v, 50Hz 380-415v,50Hz Single Three 2.598 / 2.272 2.598 / 2.272 2.07 / 1.95 2.07 / 1.95 13.0 6.0 10.54 / 9.07 [29.2] 3.51 / 3.01 [10.7] 32 16 3 5 100 100 30 30
A 900 1100 1400 1600
B 954 1154 1454 1654
D C 1000 860 1200 1060 1500 1360 1700 1560
E 9 11 14 16
F 800 1000 1300 1500
PUZ-ZM125VKA PUZ-ZM125YKA 52 / 50 70 116 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 3.349 / 3.333 2.68 / 2.86 13.0 13.21/ 13.10 [29.3] 32 3 100 30
3
PUZ-ZM140VKA PUZ-ZM140YKA
52 / 50 52 / 50 70 70 125 118 1050 x 330 + 40 x 1338 1050 x 330 + 40 x 1338 380-415v,50Hz 220-240v, 50Hz Three Single 3.349 / 3.333 3.970 / 3.631 2.68 / 2.86 3.16 / 3.11 6.0 13.0 4.45 / 4.41 [12.3] 15.74 / 14.21 [30.8] 16 40 5 3 100 100 30 30
3
52 / 50 70 131 1050 x 330 + 40 x 1338 380-415v,50Hz Three 3.970 / 3.631 3.16 / 3.11 6.0 5.58 / 4.87 [15.8] 16 5 100 30
PCA-M R32 Power Inverter Heat Pump Ceiling Suspended System Product Specifications PCA-M60KA
PCA-M50KA
PCA-M - INDOOR UNITS CAPACITY (kW)
Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)
5.5 (2.5-6.6) 5.0 (2.3-5.6) 4.7 (2.15-5.6) 4.6 (2.1-5.15) SHF (nominal) 0.79 COP / EER (nominal) 4.04 / 4.00 SCOP / SEER (BS EN14825) 4.2 / 6.7 ERP ENERGY EFFICIENCY CLASS Heating/Cooling A+ / A++ AIRFLOW (l/s) Lo-Mi1-Mi2-Hi 167-183-217-250 PIPE SIZE MM (in) Gas/Liquid 12.7 (1/2”) / 6.35 (1/4”) SOUND PRESSURE LEVEL (dBA) Lo-Mi1-Mi2-Hi 32-34-37-40 SOUND POWER LEVEL (dBA) 60 DIMENSIONS (mm) Width x Depth x Height 960 x 680 x 230 WEIGHT (kg) 26 ELECTRICAL SUPPLY Fed by Outdoor Unit FUSE RATING (BS88) - HRC (A) 6 INTERCONNECTING CABLE No. Cores 4 WIRED REMOTE CONTROLLER REFERENCE PAR-33MAA WIRELESS REMOTE CONTROLLER REFERENCE PAR-SL94B
PUZ-ZM - OUTDOOR UNITS SOUND PRESSURE LEVEL (dBA) SOUND POWER LEVEL (dBA) WEIGHT (kg) DIMENSIONS (mm) ELECTRICAL SUPPLY PHASE SYSTEM POWER INPUT (kW)
Heating/Cooling Cooling Width x Depth x Height
Heating/Cooling (nominal) Heating/Cooling (UK)
STARTING CURRENT (A) SYSTEM RUNNING CURRENT (A) Heating/Cooling [MAX] FUSE RATING (BS88) - HRC (A) MAINS CABLE NO. CORES MAX PIPE LENGTH (m) MAX HEIGHT DIFFERENCE (m) CHARGE REFRIGERANT (kg) / R32 (GWP 675) - 30m CO2 EQUIVALENT (t) MAX ADDITIONAL REFRIGERANT (kg) / R32 (GWP 675) CO2 EQUIVALENT (t)
PCA-M71KA
7.0 (2.8-8.2) 8.0 (3.5-10.2) 6.1 (2.7-6.7) 7.1 (3.3-8.1) 5.95 (2.4-6.95) 6.8 (3.0-8.65) 5.5 (2.5-6.15) 6.55 (3.05-7.45) 0.81 0.76 4.01 / 4.01 3.71 / 3.88 4.1 / 6.5 4.2 / 6.7 A+ / A++ A+ / A++ 250-267-283-317 267-283-300-333 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 33-35-37-40 35-37-39-41 60 62 1280 x 680 x 230 1280 x 680 x 230 32 32 Fed by Outdoor Unit Fed by Outdoor Unit 6 6 4 4 PAR-33MAA PAR-33MAA PAR-SL94B PAR-SL94B
PCA-M100KA
PCA-M100KA
PCA-M125KA
PCA-M125KA
PCA-M140KA
PCA-M140KA
11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.77 3.71 / 4.10 4.3 / 6.4 A+ / A++ 367-400-433-467 15.88 (5/8”) / 9.52 (3/8”) 37-39-41-43 63 1600 x 680 x 230 37 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B
11.2 (4.5-14.0) 9.5 (4.9-11.4) 9.5 (3.85-11.9) 9.2 (4.5-10.5) 0.77 3.71 / 4.10 4.3 / 6.3 A+/ A++ 367-400-433-467 15.88 (5/8”) / 9.52 (3/8”) 37-39-41-43 63 1600 x 680 x 230 37 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B
14.0 (5.0-16.0) 12.5 (5.5-14.0) 11.9 (4.25-13.6) 11.5 (5.05-12.9) 0.72 3.54 / 3.25 4.3 / 6.2 A+ / A++ 383-417-450-483 15.88 (5/8”) / 9.52 (3/8”) 39-41-43-45 65 1600 x 680 x 230 38 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B
14.0 (5.0-16.0) 12.5 (5.5-14.0) 11.9 (4.25-13.6) 11.5 (5.05-12.9) 0.72 3.54 / 3.25 4.3 / 6.1 A+ / A++ 383-417-450-483 15.88 (5/8”) / 9.52 (3/8”) 39-41-43-45 65 1600 x 680 x 230 38 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B
16.0 (5.7-18.0) 13.4 (6.2-15.0) 13.6 (4.85-15.3) 12.9 (5.7-13.8) 0.72 3.61 / 3.40 4.4 / 6.2 A+ / A++ 400-433-483-533 15.88 (5/8”) / 9.52 (3/8”) 41-43-45-48 68 1600 x 680 x 230 40 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B
16.0 (5.7-18.0) 13.4 (6.2-15.0) 13.6 (4.85-15.3) 12.9 (5.7-13.8) 0.72 3.61 / 3.40 4.4 / 6.1 A+/ A++ 400-433-483-533 15.88 (5/8”) / 9.52 (3/8”) 41-43-45-48 68 1600 x 680 x 230 40 Fed by Outdoor Unit 6 4 PAR-33MAA PAR-SL94B
PUZ-ZM50VKA
PUZ-ZM60VHA
PUZ-ZM71VHA
PUZ-ZM100VKA
PUZ-ZM100YKA
3
PUZ-ZM125VKA
PUZ-ZM125YKA
46 / 44 65 46 809 x 300 x 630 220-240v, 50Hz Single 1.361 / 1.25 1.21 / 1.06 5.0 5.95 / 5.37 [13.4] 16 3 50 30
49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 1.745 / 1.521 1.55 / 1.29 6.0 7.43 / 6.48 [19.4] 25 3 55 30
49 / 47 67 70 950 x 330 + 25 x 943 220-240v, 50Hz Single 2.156 / 1.829 1.92 / 1.55 6.0 9.23 / 7.81 [19.4] 25 3 55 30
51 / 49 69 116 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 3.018 / 2.317 2.41 / 1.99 13.0 12.97 / 9.97 [27.2] 32 3 100 30
51 / 49 69 123 1050 x 330 + 40 x 1338 380-415v,50Hz Three 3.018 / 2.317 2.41 / 1.99 6.0 4.34 / 3.31 [8.7] 16 5 100 30
52 / 50 70 116 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 3.954 / 3.846 3.51 / 3.26 13.0 16.87 / 16.46 [27.3] 32 3 100 30
52 / 50 70 125 1050 x 330 + 40 x 1338 380-415v,50Hz Three 3.954 / 3.846 3.51 / 3.26 6.0 5.69 / 5.54 [10.3] 16 5 100 30
3
3
PUZ-ZM140VKA
PUZ-ZM140YKA
52 / 50 70 118 1050 x 330 + 40 x 1338 220-240v, 50Hz Single 4.432 / 3.941 3.94 / 3.35 13.0 18.76 / 16.66 [28.9] 40 3 100 30
52 / 50 70 131 1050 x 330 + 40 x 1338 380-415v,50Hz Three 4.432 / 3.941 3.94 / 3.35 6.0 6.42 / 5.71 [13.9] 16 5 100 30
2.00 / 1.35
2.80 / 1.89
2.80 / 1.89
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
4.00 / 2.70
0.30 / 0.20
0.80 / 0.54
0.80 / 0.54
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
2.80 / 1.89
3 Three Phase
Product Dimensions Front View
Product Dimensions
PCA-M50KA
Upper View
Front View
Side View
PCA-M60/71KA
Upper View
A
Side View
Product Dimensions Front View
PCA-M100/125/140KA
Upper View
Side View
51 10
51 51
5
2
182 1198
Air intake
85
57 680
230
195
84 88
Air outlet A
(Drainage)
1600 1493
B
A
60
71
B
179 203
180 200
246
233
(liquid) (gas)
drain socket (isWhen ( installed
182
(Drainage)
1518
Air intake
85
2
10 5
Air outlet
236
(liquid ( (gas (
drain socket ( ( When is installed
878
Air intake
10
57 476
680
230
184 203 246
254
Air outlet
195
84 88
57 680 476 254 85
2
1173
233 182
1280
2
84 88 195 230
5
476
2
853
254
960
236
2
180 200 233 246
(liquid) (gas)
drain socket (When ( is installed (Drainage)
PUZ-ZM R32 Power Inverter Heat Pump Outdoor Unit Product Specifications
PUHZ-ZRP50VKA
O
Product Dimensions
Product Dimensions
PUZ-ZM35/50VKA
Upper View
Front View
Side View
PUZ-ZM60/71VHA
Upper View
Front View
Side View
404.5
Rear air intake
154.5 310
Service port
Front View
2-U shaped notched holes (foundation bolt M10) 600 Installation Feet
225
Handle for moving
(19)
225
19
362
Air discharge
Side View
1050 Earth terminal Terminal connection Left...Power supply wiring Right..Indoor/Outdoor wiring
61 42 2-12 36 Oval holes (foundation bolt M10)
56 40 0 53
1 2 Refrigerant GAS pipe Refrigerant LIQUID pipe connection connection
Service panel Handle for moving
1338 632
1
Air Intake
ø15.88 (5/8F)
ø9.52 (3/8F)
A
Air Discharge
75
28
40
330
370 417
Side Air Intake
MODEL 2
2
B
C
26
369
2
A
B
C
PUZ-ZM100-140VKA
1067
442
450
PUZ-ZM100-140YKA
919
442
450
Front piping cover Rear piping cover
Telephone: 01707 282880 email: air.conditioning@meuk.mee.com web: airconditioning.mitsubishielectric.co.uk microsite: timeforR32.co.uk UNITED KINGDOM Mitsubishi Electric Europe Living Environment Systems Division, Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, England. General Enquiries Telephone: 01707 282880 Fax: 01707 278881 IRELAND Mitsubishi Electric Europe, Westgate Business Park, Ballymount, Dublin 24, Ireland. Telephone: Dublin (01) 419 8800 Fax: Dublin (01) 419 8890 International code: (003531) Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi Electric Europe 2017. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation in technical specification to the equipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to the Company’s General Conditions of Sale, a copy of which is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners. Note: The fuse rating is for guidance only. Please refer to the relevant databook for detailed specification. It is the responsibility of a qualified electrician/electrical engineer to select the correct cable size and fuse rating based on current regulation and site specific conditions. Mitsubishi Electric’s air conditioning equipment and heat pump systems contain a fluorinated greenhouse gas, R410A (GWP:2088), R32 (GWP:675), R407C (GWP:1774) or R134a (GWP:1430). *These GWP values are based on Regulation (EU) No 517/2014 from IPCC 4th edition. In case of Regulation (EU) No.626/2011 from IPCC 3rd edition, these are as follows. R410A (GWP:1975), R32 (GWP: 550), R407C (GWP:1650) or R134a (GWP:1300).
Effective as of October 2017
SAP No. 317318
447
41
673
943
417
40 54 57
2-12 36 oval holes (foundation bolt M10)
PUZ-ZM100/125/140VKA, PUZ-ZM100/125/140YKA
Upper View Rear Air Intake
Handle for moving
Front piping cover Rear piping cover
1
R
Service panel
62
809
Product Dimensions
Earth terminal
23
Installation bolt pitch 500
322
431
Connection for gas pipe FLARE 12.7 (1/2F)
Handle for moving
473
Connection for liquid pipe FLARE 6.35 (1/4F)
8.5
4-10×21 oval hole
175
Installation Feet
330
630
Service panel 320
32.5
40
600
950 2 U-shaped notched holes (Foundation Bolt M10)
28
Air intake Air discharge
175
Side air intake
Earth terminal
30
300 330
360
Service panel for charge plug
53
22.3
370
Handle for moving
42 drain hole
48
Air intake
1...Indication of Terminal connection location. 2...Indication of STOP VALVE connection location.
timeforR32.co.uk