KAISER PERMANENTE - MORENO VALLEY
CENTRAL UTILITY PLAN - FIRE RATED GAS LINE ENCLOSURE
The gas line was installed in the incorrect location inside of the generator yard. This was a fire hazard and a code issue. A solution was coordinated with the contractor and consultants to provide a rated enclosure with an entrance entirely separate from the generator yard was. This solution was reviewed with HCAi field staff prior to finaliing the design and then integrated into the approved construction documents through a amended construction document (ACD).
Advertisement
3A 1/2" = 1'-0" 2 ENLARGED PLAN -STAFF TOILET & SHOWER • LOCKER TYPE 2T = TWO-TIER LOCKER UNIT • LOCKER TYPE 3T = THREE-TIER LOCKER UNIT
1
C1 CORRIDOR
CORRIDOR (UNCOVERED)
W/ MIN ONE FULL CMU
C1
FIRE PROOF SEALANT TYP. ALL AROUND
FIRE PROOF SEALANT TYP. ALL AROUND
3/8” Φ HILTI KBTZ-2 W/ 2.5” EFFECTIVE EMBED @ 16” (ESR-4561).
3/8” Φ HILTI KBTZ-2 W/ 2.5” EFFECTIVE EMBED @ 16” (ESR-4561).
FLUID-APPLIED AIR WATER BARRIER OVER EACH SIDE OF EXTERIOR SHEATHING
FLUID-APPLIED AIR WATER BARRIER OVER EACH SIDE OF EXTERIOR SHEATHING
1/4" 1 -0" GENERATOR
GENERATOR YARD (UNCOVERED)
SEALANT MTL FLASHING V.I.F. TO NEAREST COURSE 7'4"
SEALANT MTL FLASHING
1/4" / 1 -0"
4" METAL STUD FRAMING
5/8" GLASS-MAT GYPSUM EXTERIOR SHEATHING BOARD ON BOTH SIDES OF THE STUD FRAME
YARD (UNCOVERED) 07 4213 METAL PANEL CLADDING OVER EXTERIOR SURFACES
07 4213 METAL PANEL CLADDING OVER EXTERIOR SURFACES
5/8" GLASS-MAT GYPSUM EXTERIOR SHEATHING BOARD ON BOTH SIDES OF THE STUD FRAMING
5/8" GLASS-MAT GYPSUM EXTERIOR SHEATHING BOARD ON BOTH SIDES OF THE STUD FRAMING
4" METAL STUD FRAMING
4" METAL STUD FRAMING
32" WIDE OPENING (E) GAS LINE PIPING
(E) GAS LINE PIPING
32" WIDE OPENING
PREFABRICATED 1" THRESHOLD
PREFABRICATED 1" THRESHOLD
FIRESTOPPING
4" OPENING, 2 ENLARGED PLAN -STAFF TOILET & SHOWER • SEE SHEET A2.30 FOR SCHEDULED FINISHES • SEE SHEET A9.01 FOR ACCESSIBILITY CLEARANCE AND DIMENSIONS • LOCKER TYPE 2T = TWO-TIER LOCKER UNIT • LOCKER TYPE 3T = THREE-TIER LOCKER UNIT 1/2" = 1'-0" 4B
4"HIGH CONC. CURB PER DET 5/A9.11
FIRESTOPPING 4"HIGH CONC. CURB PER DET 5/A9.11
ENLARGED SECTION -ENCLOSURE AT GAS LINE -LOOKING EAST
EAST 1/2" = 1'-0" 4A 1 WALL DESIGN PER US U465 LL V.I.F. 2' - 8" V.I.F. 1' - 4" V.I.F. 2' - 0" 7' - 6" 4'9 3/4" GAS LINE