Ministry of Transportation (MOT)

Page 1


1.0 2.0 3.0 4.0 5.0 6.0

Abstract 1 Acknowledgement 2 Introduction to the Ministry of Transport (MOT) 3 Methodology 4 Limitation of Study 5 Fire Protection System 6 6.1 Introduction 6.2 Active Fire Protection System 7 6.2.1 Introduction 6.2.2 Water Based System 8 6.2.3 Non-Water Based System 10 6.2.4 Alarm, Detection System and Device 11 6.2.5 Case Study of Active Fire Protection System in MOT 12 6.2.5.1 External Fire Hydrant 6.2.5.2 Hose Reel System 13 6.2.5.2.1 Hose Reel Pump 6.2.5.2.2 Hose Reel Water Storage Tank 6.2.5.3 Wet Riser System 17 6.2.5.4 Automatic Fire Sprinkler System 18 6.2.5.4.1 Fire Sprinkler Head 6.2.5.4.2 Fire Sprinkler Pump 6.2.5.5 Carbon Dioxide (CO2) Suppression System 21 6.2.5.6 Portable Fire Extinguisher 22 6.2.5.6.1 ABC Multipurpose Dry Powder Extinguisher 6.2.5.6.2 Carbon Dioxide Extinguisher 6.2.5.7 Fire Alarm System 24 6.2.5.7.1 Fire Alarm Bell 6.2.5.7.2 Manual Pull Station 6.2.5.7.3 Fireman’s Switch 6.2.5.7.4 Voice Communication System 6.2.5.7.5 Smoke Detector 6.2.5.7.6 Heat Detector 6.2.5.8 Fire Control Room 31 6.2.5.8.1 Fire Alarm Control Panel 6.2.5.8.2 Intercom Panel 6.3 Passive Fire Protection System 33 6.3.1 Introduction 6.3.2 Means of Escape and Firefighter Access 34 6.3.3 Compartmentation 36 6.3.4 Case Study of Passive Fire Protection in MOT 37 6.3.4.1 Fire Rated Doors 38 6.3.4.2 Emergency Exit Signage 40 6.3.4.3 Fire Escape Staircase 42 6.3.4.4 Fire Rated Walls 45 6.3.4.5 Smoke and Heat Exhaust Ventilation System 47


7.0

8.0

6.3.4.6 Fire Shutter Mechanical Ventilation System 7.1 Introduction 7.2 Basic Ventilation System 7.3 Comparison of Natural and Mechanical Ventilation 7.4 Type of Mechanical Ventilation 7.4.1 Exhaust Ventilation System 7.4.2 Supply Ventilation System 7.4.3 Balanced Ventilation System 7.4.4 Energy Recovery System 7.5 Component in Mechanical Ventilation System 7.5.1 Fan 7.5.1.1 Propeller Fan 7.5.1.2 Axial Fan 7.5.1.3 Centrifugal Fan 7.5.2 Filter 7.5.2.1 Dry Filter 7.5.2.2 Viscous Filter 7.5.2.3 Electrostatic Filter 7.5.2.4 Activated Carbon Filter 7.5.3 Ductwork 7.5.4 Fire Damper 7.5.5 Diffusers 7.6 Case Study of Mechanical Ventilation in MOT 7.6.1 Supply Ventilation System 7.6.1.1 Stairwell Pressurization System 7.6.1.2 Lift Lobby Pressurization System 7.6.1.3 Basement Carpark 7.6.1.4 Ductwork 7.6.2 Exhaust Ventilation System 7.6.2.1 Car Park Exhaust System 7.6.3 Utility Room Exhaust System Air-Conditioning System 8.1 Introduction 8.2 Operating Principles of Air Cooling 8.2.1 Refrigerant Cycle 8.2.2 Air Cycle 8.3 Air Conditioning System 8.3.1 Room Air Conditioning System 8.3.2 Split Air Conditioning System 8.3.3 Packaged Unit Air Conditioning System 8.3.4 Plant Air Conditioning System 8.4 Case Study of Air Conditioning System in MOT 8.4.1 Centralized Air Conditioning System 8.4.1.1 District Cooling System

49 52 53 54 55 55 56 57 58 59

62

65 66 66 67 68

73 75 76 77 78 80 81 81 82 83 84 86 86


9.0

8.4.1.2 Heat Exchanger (HEX) 8.4.1.3 Chill Water Pump 8.4.1.4 Air Handling Unit (AHU) 8.4.1.5 Air Duct and Diffuser 8.4.2 Split Air Conditioning System 93 8.4.2.1 Split Air Conditioning System in Elevator Control Room 8.4.2.2 Split Air Conditioning System as a Backup Mechanical Transportation System 97 9.1 Introduction 97 9.2 Lift 98 9.2.1 Lift Application 98 9.2.2 Types of Lifts (Elevators) 99 9.2.2.1 Electric Lift 9.2.2.2 Hydraulic Lift 9.2.2.3 Pneumatic Lift 9.2.2.4 Climbing Lift 9.2.2.5 Comparison on Cost and Energy Consumption on Different Types of Lifts 9.3 Escalator 104 9.3.1 Components of Escalator 104 9.3.2 Escalator Arrangement 105 9.4 Travelators 106 9.4.1 Component of Travelators 107 9.5 Case Study of Mechanical Transportation in MOT 108 9.5.1 Overview 109 9.5.2 General Traction Lift 110 9.5.3 Components of Geared Traction Lift 111 9.5.4 Machine Room (Lift Motor Room) 112 9.5.4.1 Exhaust Fan 9.5.4.2 Hoisting Motor 9.5.4.3 Control Panel Cabinet 9.5.4.4 Lift Main Control Board 9.5.4.5 Hoisting Sheave 9.5.4.6 Gear Box 9.5.4.7 Overspeed Governor 9.5.5 Lift Shaft 118 9.5.5.1 Guide Rails 9.5.5.2 Suspension Rope 9.5.5.3 Counterweight 9.5.5.4 Landing Door 9.5.5.5 Car Buffer 9.5.5.6 Elevator Pit 9.5.6 Lift Car 123 9.5.6.1 Lift Car Frame 9.5.7 Lift Cabin 124


9.5.7.1 9.5.7.2 9.5.7.3 9.5.7.4 10.0 11.0

Conclusion References

Control System Sensor (Safety Door Edge) Hall Call Panel Floor Request Button Panel 127 128


1.0 Abstract This project requires students to analyze the services in an office building of our choice. Each group is needed to perform an observational study and analysis of the following services, and report them in accordance with the requirement of the UBBL 1984: a. Fire Protection (Active and Passive Fire Protection System) b. Mechanical Ventilation System c. Air-Conditioning System d. Mechanical Transportation System (Lift) With this report, we will be able to focus on the details and gain a better understanding of how services function and are implemented in an office building. The Ministry of Transport (MOT) building is a great example to show case a modern building with services.

1


2.0 Acknowledgement Our group would like to give a very big thank you to the following individuals who have actively assist us in this journey with a fruitful experience. First will be our tutor Ar. Sateerah Hassan who was actively supporting us throughout this report, including providing us with a very informative tutorial session every week. We have indeed gained a lot from our learning process in a very short period of time. At last we would like to thank Ministry of Transport (MOT) and other officers, Mr. Shahriman (from the administrative and assets department) as the person in charge to arrange our technical visit, and Mr. Amirul (Mechanical Engineer from IKSB – Irfan Khairi Sdn. Bhd.) for allowing and assisting us to conduct research activities at MOT building, which also provided us with significant amount of information throughout this research process.

2


3.0 Introduction to the Ministry of Transport (MOT)

The Ministry of Transport (MOT) is located at Jalan Tun Hussein in Putrajaya and this building is the head office of the MOT. It was designed by the architect firm named Arkitek MAA and it was completed in year 2014. This building was a competition towards the architecture in Putrajaya under Putrajaya Holdings and Arkitek MAA won it. This building has a different name which is the 4G5 development. 4G5 is a 10 storey government office building which includes a multipurpose hall, cafeteria and four levels of basement carpark, while the faรงade concept of this building is formal and complies with urban design guidelines to blend in with the surrounding environment. The Ministry of Transport is in cooperate with Irfan Khairi Sdn. Bhd. (IKSB) to work best for the services in the building. By signing a contract with the Ministry of Transportation, the company named IKSB will be handling the building services for 3 years in which this company will be looking over the services everyday in order to increase the efficiency of the services and reduce any incidents to be happened.

3


4.0 Methodology The group embarked on the project with the intention of conducting a thorough study of the building services implemented at an office building in Putra Jaya – Ministry of Transport (MOT). The visit to the MOT was divided into three different occasions, so the first visit was basically to understand their movements and the availability of the services in the building. The second visit was a more thorough research done during the visit. We were assisted by Mr. Amirul and his assistants from IKSB, the Mechanical Engineers on the details or intricacies of the systems in place in the building because it is their job to keep every service in the building are functioning well. The third visit to the Ministry of Transport was the last visit in which we were to get known any further details such as the usage of the systems in the buildings and the efficiency of the services. The group was divided to work on different aspects and topics in the building, in preparation for the site visit. The group visited the site within three occasion with a very thorough research done. After the completion of data collection, the group then compile all the data in google drive for ease of access. The data was then analyzed and shared among group members while the group were drafting out the report.

4


5.0 Limitation of Study The group actually encountered several issues during the research process which slightly delayed the preparation of the whole project. During the initial stage of the process, it was hard to contact to the person in charge as we got a lot of redirected call which lead to some false calls. The problems continued for a few days and the only solution was to make a call to the reception department in Ministry of Transport (MOT) again. After all, when we contacted the person in charge, we were unable to visit the site due to site visit in Ipoh for design studio subject and also public holidays, which postponed the whole project for about a week. One of the biggest challenge would be the lack of published building’s drawing of Ministry of Transport (MOT) such as building’s plans and sections. This issue forced us to manual sketch some of the plan to produce a proper plan. Second, the visit was restricted in some places which resulted the lack of information but through questions we prepared to the assisting people from IKSB, we gathered enough information that could be used to be written in our report.

5


6.0 Fire Protection System 6.1 Introduction Fire protection refers to the safety measures to prevent fire destruction towards the buildings, to reduce the impact, and also to save lives and property. Fire prevention and fire protection are different from their meaning as fire prevention is the process to be done before the fire outbreak. Fire protection by its definition is the use of a combination of different fire safety equipment and procedures that are used to defend the property line in case of any fire happens. Fire protection is the top priority to be designed in the buildings as fire prevention is not an effective way to design in a building. This is because any fire outbreak cannot be prevented, as fire can be happened in any kind of accident such as short circuit in a building. Fire protection system can be divided into two major types, Active Fire Protection and Passive Fire Protection

6


6.2 Active Fire Protection System 6.2.1 Introduction Active Fire Protection (AFP) is the component of the fire detection and prevention which reacts to action and motion. The role of fire protection within the fire containment process is to detect, alert about, seek to eliminate the fire hazard. The active fire protection system can be generated by four main parts: water-based system, non-water-based system, alarm and detection system, as well as smoke control system to prevent and suppress the structural fire spreading as well to allow appropriate firefighting action being taken. A brief explanation shall be given to all the systems before proceeds to the case study towards the MOT in which the MOT consists all the systems listed.

Diagram 6.0: Overview chart of active fire protection

7


6.2.2 Water Based System Water is the most natural element of all extinguishing agents and is usually available in sufficient quantities at a reasonable price. It reduces smoke as well as pollutants in order to extend the time for occupants to escape from the fire incident. Water Based System operates by using water as the most natural fire extinguisher agents. Buildings exceeding ten storeys or 30m in height above ground floor level, whichever is the least, should be provided with one or more wet rising mains to be used exclusively for fire fighting purposes. The riser is always charged with water under pressure, fed by pumping sets from a break tank. There are four types of water based system which include: 1. External fire hydrant 2. Hose reel system 3. Wet riser system 4. Automatic sprinkler system.

8


1. External Fire Hydrant A fire hydrant is a connection point by which fire fighters can tap into a water supply. It is a component of active fire protection.

2. Hose Reel System Fire hose reel systems consist of pumps, pipes, water supply and hose reels located strategically in a building, ensuring proper coverage of water to combat a fire. These appliances are designed to deliver, as a minimum, 0.33L of water per second.

3. Wet Riser System Wet risers are used to supply water within buildings for firefighting purposes. Wet risers are permanently charged with water. This is as opposed to dry risers which do not contain water when they are not being used, but are charged with water by fire service pumping appliances when necessary.

4. Automatic Sprinkler System Automatic sprinkler system that designed to detect and extinguish the fire in the early stage. It usually located at the ceiling of the building and location that specified designed.

9


6.2.3 Non-Water Based System When fire breakout due to electrical equipment, the pouring water will make worse of the situation and may prove fatal. Hence, fire fighting equipment such as non-water based system is safe to use in case of an emergency. The non-water based system consists of carbon dioxide system and dry chemical agents, which include the carbon dioxide suppression system and portable fire extinguishers.

1. Carbon Dioxide Suppression System Carbon dioxide suppression system is a fast, reliable and effective in one of the active fire protection system. It can quickly extinguish the fire to protect the property from causing damage when sense of fire.

2. Portable Fire Extinguisher A fire extinguisher is an active protection device that used to control and extinguish small fire. There are few types of fire extinguisher that can extinguish different fire source such as flammable liquid and electric equipment.

10


6.2.4 Alarm, Detection System and Device

An alarm system consists of multiple devices work together to detect and alert people through either visual or audio information during the occurrence of smoke, fire, carbon monoxide or other emergencies. These devices are the most sensitive active fire protection system as they are the first system to be activated in the case of fire emergency. These alarms can be activated manually through fire alarm activation device such as manual call point or pull station. Furthermore, these alarms can also be activated automatically through the detector of smoke, heat and flame.

1. Fire Alarm System Fire alarm system is a system that have multiple device work together to detect and warn the occupants through visual and audio when fire is occurred in the building. This system used automatically activated device or manually operated device to activate the system.

2. Fire Control Room Fire control room is required for building that over 25m and this room will be the nerve center of the building when fire is occurred. This room control of the building’s fire protection system, fire pump, secondary water supply, communication and elevator control.

11


6.2.5 Case Study of Active Fire Protection System in MOT 6.2.5.1 External Fire Hydrant The fire hydrant is a source of water which is provided in urban, suburban and rural areas with public water services to enable the firefighters to tap into the water supply easily in attempts of extinguishing a fire. The fire hydrant is usually installed in an open space area for the convenience of firefighters in the case of an emergency. The fire hydrant system consists of a system of pipe works connected directly to the water supply. Firefighters attach a hose to the fire hydrant, the valve is then opened to release high pressured water. The water from the fire hydrant can be further pressurized for longer distance water shooting by the firefighters which they will connect the hose to a fire truck which contains a booster pump to enable an increment in water pressure. External fire hydrant can be separated into two types which are the three-ways fire hydrant and two-ways fire hydrant. In MOT, there are two external fire hydrant and only two-way fire hydrant found outside the building. It is also found that the external fire hydrants, one was located beside Jalan Tun Hussien and one more located beside Lebuh Setia.

Figure 6.1: Two-way fire hydrant located outside MOT

Diagram 6.1: Ground floor plan showing location of external fire hydrant

UBBL 1984 Clause 225 Detecting and extinguishing fire 1. Every building shall be provided with means of detecting and extinguishing fire with fire alarms together with illuminated exit signs in accordance with requirements as specified in the Tenth Schedule to these By-laws. 2. Every building shall be served by at least one fire hydrant located not more than 91.5 metres from the nearest point of fire brigade access. 3. Depending on the size and location of the building and the provision of access for fire appliances, additional fire hydrant shall be provided as may be required by the Fire Authority. 12


6.2.5.2 Hose Reel System The hose reel system is existed for people to use during the early stage of a fire outbreak. Fire hose reel system is set to be located at strategic places inside a building in order to provide a reasonably accessible and serve as an initial firefighting aid to control the fire. The system consists of hose reel pumps, water tanks, hose reels, pipeworks and valves. This system is manually operated and is activated by opening a valve enabling water to flow out of the hose reel. These appliances are designed to deliver a minimum, 0.33L water per seconds. A control nozzle is attached to the end of the hose to enable the operator to control the direction and flow of the water. All fire hose reels come with unique ball valve shut-off device, a plastic or solid brass hose reel nozzle and mounting bracket. In MOT, the hose reels are located at every floor including upper and lower car park level. Some hose reels are kept in the small compartments together with hose cardle, fire extinguisher and landing valve whereas some are placed outside along the corridor as well as the basement.

Diagram 6.2: Overall layout of hose reel system

13

Figure 6.2: Hose reel system placed together with hose cradle and landing valve


Diagram 6.3: Ground floor plan showing highlighted location of hose reel system

14


6.2.5.2.1 Hose Reel Pump The hose reel system that is used in MOT consists of two types of pumps, namely duty pump for duty operation and standby pump for standby operation. Fire hose reel pump is compulsory to have a backup pump to ensure the hose reel pump to operate even the main duty pump fails to operate. Duty pump will be functioned when pressure of the water is low in order to maintain the system and make sure it is running well. There is a pump attached together to the system which is known as the jockey pump. Jockey pump, it is also known as pressure maintenance pump, is a small apparatus that works together with a fire pump as part of a fire protection sprinkler system. It is designed to keep the pressure in the system elevated to a specific level when the system is not used so that the fire pump does not run all the time.

Diagram 6.4 Basement floor plan shows the location of hose reel pump in the sprinkler room

Figure 6.3 Standby pump that is used for the hose reel system

UBBL 1984 Clause 244 (b) Hose reel 1. Hydraulic Hose Reels shall be located at every 45 metres (depending on building form). Besides, fire hose reels should be located at strategic places in buildings, especially near fire-fighting access lobbies in order to provide a reasonably accessible and controlled supply of water for fire-fighting purposes.

15


6.2.5.2.2 Hose Reel Water Storage Tank The hose reel water tank is ensured to be fully stored with water and is prepared to be used in case of any emergency for the hose reel system. The tank must have a minimum volume of water of 1.6 mÂł. The hose reel water storage tank and hose reel pump are placed in the sprinkler pump room because the hose reel pump system also serves as a main water supply at higher pressure for the fire sprinkler system apart from just a hose reel system. The hose reel pump is needed when the external fire hydrant cannot provide sufficient pressure to meet with the hydraulic design requirement of the fire sprinkler system. UBBL 1984 Clause 247 Part VIII: Fire Alarms, Fire Detection, Fire Extinguishment and Fire Fighting Access 1. Water storage capacity and water flow rate for fire fighting systems and installations shall be provided in accordance with the scale as set out in the Tenth Schedule to these By Laws. 2. Main water storage tanks within the building, other than hose reel system, shall be located at ground, first or second basement levels, with fire brigade pumping inlet connections accessible to fire appliances 3. Storage tanks for automatic fire sprinkler installations where full capacity is provided without for replenishment shall be exempted from restrictions in their location

Figure 6.4 Hose Reel water storage tank

16


6.2.5.3 Wet Riser System Wet riser is a network of pipes filled with water for firemen to use for fire-combating purposes. Unlike the dry riser system, whereby water flows through the pipeline when the fire department starts pumping water into the system; wet risers are constantly pressurized to ensure an immediate water supply for fire-suppression purposes. This system allows the fire brigades to confront serious fire hazard without the need of bringing their own distribution system. Wet riser requires regular flow tests and should be regularly checked to ensure the system pressure is working.

Diagram 6.5 Overall layout of the wet riser system

Figure 6.5 Wet riser pump room at basement carpark level

Ministry of Transportation, being higher than 30.5 metres, uses the wet riser system. Wet riser system is installed near to the usable staircase in every floor. In the event of emergency, fire brigade can access the wet riser system easily and work faster to extinguish the fire. UBBL 1984 Clause 231 Wet risers 1. Wet riser system to be provided in buildings with top most floor more than 30.5m. 2. Wet riser to be provided to every staircase which extends to the roof. 3. Each stage of wet riser to be no more than 61.0m except in cases may be permitted to 70.15m.

17


6.2.5.4 Automatic Fire Sprinkler System A fire sprinkler system is an active fire protection system that is connected to a water supply system as the water supply system provides an adequate pressure and flow rate to a water distribution piping system, onto which fire sprinklers are connected. Fire sprinkler systems are triggered by extreme heat and can extinguish a fire effectively in a room when they are started. Fire sprinkler system distributes water to combat fire outbreak by using a series of water pipes whereby smoke or heat detectors detect fire and promptly activates the sprinklers at the affected area. The system consists of sprinkler heads and sprinkler pump which work closely with alarm and smoke detector. Sprinkler installation cover the whole MOT except electrical rooms.

Diagram 6.6 Overall layout of automatic fire sprinkler system

Diagram 6.7 Diagram shows how the sprinkler works when there is a fire

18


6.2.5.4.1 Fire Sprinkler Head Fire sprinkler heads in automatic fire sprinkler system act as the spray nozzles that release water around the detected fire hazard area. In the event of fire, the sprinkler and the smoke detector will be operated immediately to allow the flow of water to distinguish fire. It extinguishes fire quickly, prevents fire from spreading over a large area, and ready to be used after a replacement. Each sprinkler head is designed to have its own temperature that will activated individually when it is heated. Sprinkler will activate when the temperature is more than 68°C in case of fire hazard. In MOT, the type of sprinkler used are recessed pendent sprinkler head. The recessed pendent sprinkler head is placed facing downwards and hanged down from the ceiling. When the water sprays downwards to the ground, curved downwards deflector will direct the sprinkler water into a cone water pattern to increase the water sprinkler range.

Diagram 6.8 Component of fire sprinkler head

Figure 6.6 Recessed pendent sprinkler head used in MOT

UBBL 1984 Clause 228 Sprinkler System 1. Sprinkler valves shall be located in a safe and enclosed position on the exterior wall and shall be readily accessible to the Fire Authority 2. All sprinkler system shall be electricity connected to the nearest fire station to provide immediate and automatic relay of the alarm when activated 19


6.2.5.4.2 Fire Sprinkler Pump In MOT, fire sprinkler pump system consists different type of pump, including duty pump, standby pump and jockey pump with each serving different purposes. These fire sprinkler pump systems draw water from water storage tank to feed the sprinkler network. 1. Duty Pump Duty pump functions when pressure in the pipe goes down, supplying enough pressure of water in order to maintain the system and make sure it is running well. However, if duty pump encounters some issue and fails to run, standby pump will automatically be activated by the system and take over. Duty pump can be manually switched off by using the master control panel. 2. Standby Pump Standby pump has the exact same function as the duty pump. It replaces the duty pump when it is not operated and need to be switched off manually. 3. Jockey Pump The jockey pump is a smaller pump that works along the duty pump to maintain the water pressure of the pipe within a specific range. As pipe leakage often happens and causes water pressure to go down, jockey pump senses this and will fill them back up to normal pressure. Without the presence and contribution of jockey pump in maintaining the pressure, the system will end up with a low pressure and the fire pump will send high pressurized water back to the pipe. This will cause destroy of the whole entire automatic fire sprinkler system.

Figure 6.7 Fire sprinkler pump room at basement carpark

20


6.2.5.5 Carbon Dioxide (CO²) Suppression System Carbon dioxide (CO²) is a colorless, odorless, electrically non-conductive gas that is highly efficient as suppression agent. It extinguishes fire primarily by lowering the level of oxygen that supports combustion in a protected area. Carbon dioxide fire protection system uses the intelligent, reliable and fast acting control panels to quickly sense a fire before it can cause damage to the property. Carbon dioxide may be stored in high pressure spun steel cylinder (HPCO² suppression system) or low-pressured light wall refrigerated tanks (LPCO² suppression system). MOT only consists of high pressure spun steel cylinder (HPCO² suppression system) in the fire control room.

Figure 6.8 HPCO3 suppression system located in

Diagram 6.9 HPCO3 suppression operating system

fire control room

Diagram 6.10 Ground floor plan shows the highlighted location with HPCO3 suppression system

21


6.2.5.6 Portable Fire Extinguisher A portable fire extinguisher is one of the active protection devices and is commonly used for initial outbreak of fire and prevent a full-scale fire escalation. MOT consists two type of portable fire extinguisher that is ABC multipurpose dry powder extinguisher and carbon dioxide extinguisher. Different types of extinguishers serve to extinguish different fire source efficiently.

Diagram 6.11 Type of fire extinguisher

Diagram 6.12 Standard operational procedure of a fire extinguisher

Figure 6.9 Carbon dioxide extinguisher (left) ABC multipurpose fire extinguisher (middle) and some kept in a case beside fire fighting lift (right)

22


6.2.5.6.1 ABC Multipurpose Dry Powder Extinguisher ABC dry powder fire extinguisher is one of the most common fire extinguishers that is being used because it is a multipurpose fire extinguisher that solve fire from class A, B and C (A: common combustibles, B: flammable liquids, C: gaseous fires). Fire requires oxygen, heat and fuel to happen. Dry powder fire extinguishers deal with fire primarily by interrupting the chemical reaction. In MOT, this type of fire extinguisher can be found near the emergency exit of the whole building and some of it are kept in case to prevent accidental discharge.

6.2.5.6.2 Carbon Dioxide Extinguisher Carbon dioxide extinguisher can only be used when the fire involving electricity appliances and class B (flammable liquid) liquid fires. These extinguisher’s horn is designed to easily allow the carbon dioxide to blow at a high speed, so that the snow that is formed does not block the exit smoothly.

UBBL 1984 Clause 227 Portable extinguishers 1. Portable extinguishers shall be provided in accordance with the relevant codes of practice and shall be sited in prominent positions on exit routes to be visible from all directions and similar extinguishers in a building shall be of the same method of operation.

23


6.2.5.7 Fire Alarm System Fire alarm consists of alarm bells, manual pull station, fireman’s switch, voice communication system, smoke and heat detector. Fire alarm system will provide audible and visual alarm signals to the occupants in the building. There are two types of fire alarm signals, which are two stages alarm system and single alarm system. Both of these alarm signals are applied in MOT. In single alarm system, the fire detection system will send out signal to the fire control room when a fire occurs. The security then will investigate the source of the fire. If fire is occurred, the alarm will be activated from the signal given from fire control room. It will notify the people where execution starts from the nearest floor from the fire source. In the second stage alarm system, the alarm will be activated after 5 minutes if the fire detection does not send out any signal. The system will automatically contact the fire fighters once the signal are sent out.

Figure 6.10 Fire alarm control case located at tenth floor along the corridor of the elevator

24

Diagram 6.13 Overall layout of fire alarm system


6.2.5.7.1 Fire Alarm Bell Alarm bell is an audible fire alarm system. Fire alarms may be activated automatically or manually through detection devices or manual call point. Alarms can be either motorized bells or wall mountable sounders or horns. User activates the alarm by breaking down the glass and press the switch, the signal is sent to an alarm and then to the fire alarm control panel. Once activated, fire alarm will keep ringing until the fire department deactivate it. The alarm should have a minimum sound level of 65 db or +5 db above ambient noise level sustainable for a period of minimum of 20 seconds should be produced by sound unit. The alarm bell are mounted on the wall with a minimum height of 2.1m from floor level.

Figure 8.11 Fir alarm bell located on the

Figure 8.12 Fire alarm bell placed on top of

ground floor lobby

the fire alarm control case

UBBL 1984 Clause 237 Fire Alarms 1. Fire alarms shall be provided in accordance with the Tenth Schedule to these By-Laws 2. All premises and buildings with gross floor areas excluding car park and storage areas exceeding 9290 square metres or exceeding 30.5 metres in height shall be provided with a two-stage alarm system with evacuation (continuous signal) to be given immediately in the affected section of the premises while an alert (intermittent signal) be given to adjoining section. 3. Provision shall be made for the general evacuation of the premises by action of a master control.

25


6.2.5.7.2 Manual Pull Station Manual pull station is designed for the purpose of raising an alarm manually once verification of a fire or emergency condition exists, by operating the push button or by breaking the glass, the alarm signal can be raised. Manual alarm call points require a two-action process to prevent unwanted activation - break the cover glass or plastic, followed by activating the switch within. Once activated the alarm can be reset at the fire control room or manually by specific key. Manual alarm call point and alarm bell to be along escape corridors or beside exit and staircase doors, such that no occupant need to travel more than 30 metres to reach a call point.

Figure 6.13 Manual pull station

6.2.5.7.3 Fireman’s Switch

Fireman’s switch is a specialized switch which allows firefighters to disconnect the high voltage current from the electrical supply that may pose a danger in an event of an emergency. The switch is red in color and be fitted with a name plate saying ‘Fireman’s Switch’ in order to get spotted easily. These switches are installed at the stairway at every level of MOT.

Figure 6.14 Fireman’s Switch

UBBL 1984 Clause 240 Electrical Isolating Switch 1. Every floor or zone of any floor with a net area exceeding 929 square meters shall be provided with an electrical isolation switch located with a staircase enclosure to permit the disconnection of electrical power supply to the relevant floor or zone served. 2. The switch shall be of a type similar to the fireman’s switch specified in the Institution of Electrical Engineers Regulations then in force. 26


6.2.5.7.4 Voice Communication System The system is a two-way emergency voice communication between remote telephone handsets inside a phone box and the telephone from intercom panel inside the fire control room in case of an emergency that requires personal assistance. The wall device is installed at the emergency exits for rapid access in MOT. Fire Intercom system is intended to be used in conjunction with fire detection and alarm system to control the safe evacuation of building occupants.

Figure 6.15 Intercom headset station at emergency escape staircase

Diagram 6.14 Ground floor plan showing highlighted location of intercom headset

27


UBBL 1984 Clause 239 There shall be two separate approved continuously electrically supervised voice communication systems, one a fire brigade communication system and the other a public address system between the central control station and followings areas: a.

Lifts, lift lobbies, corridors and staircases;

b.

In every office area exceeding 92.2 sq.metres in area;

c.

In each dwelling unit and hotel guest room where the fire brigade system may be combined with the public address system

28


6.2.5.7.5 Smoke Detector A smoke detector is a device that senses smoke, typically as an indicator for fire. There are currently three types of smoke alarms on the market: ionization, photoelectric and combination ionization/photoelectric. Smoke alarm contains a small amount of radioactive material between two electrically charged plates, which ionizes the air and causes current to flow between the plates. When smoke enters the chamber, it disrupts the flow of ions, thus reducing the flow of current and activating the alarm. There are two types of smoke detector in general such as ionization smoke detector and photoelectric smoke detector. MOT only installed ionization smoke detector in the building. Ionization smoke detectors implement a trace amount of radioactive material that's fitted between two electrically charged plates. The sum of these ingredients creates a steady flow of ionized air within the smoke alarm. The presence of any smoke within the alarm's vicinity will disturb this flow and immediately warn the surrounding area.

Figure 6.16 Ionization smoke detector

Diagram 6.14 Operational system of ionization smoke detector

UBBL 1984 Clause 153 1. All lift lobbies shall be provided with smoke detector 2. Lift not opening into a smoke lobby shall not use door reopening devices controlled by light beam or photodetectors unless incorporated with a force close feature which after thirty seconds of any interruption of the beam cause the door close within a present of time.

29


6.2.5.7.6 Heat Detector

Heat detector is able to minimize the damage of property by reacting to the temperature changed in the building during the fire. It enables the occupants to have more response time. Heat detector usually has a lower false alarm rate, but it is slower than smoke detector in detecting fire. In generally, there are two types of heat detectors which are fixed temperature heat detector and rate of rise heat detector. Fixed temperature heat detector initiates the alarm when detecting element reaches a predetermined fixed temperature. It is usually preferred by most of the office building due to its economical and efficiency in alarm detecting ambient temperature. Rate of rise heat detector activates the alarm from a sudden change of temperature from predetermined value. MOT has both types of heat detectors installed.

Figure 6.17 Fixed temperature heat detector

Figure 6.18 Rate of rise heat indicator

Diagram 6.15 Operational system of fixed temperature and rate of rise detector

UBBL 1984 Clause 225 1. Every building shall be provided with means of detecting and extinguishing fire with fire alarms together with illuminated exit signs in accordance with the requirements as specified in the Tenth Schedule to these By-Laws. 30


6.2.5.8 Fire Control Room Fire control room in MOT is located behind the reception at the ground floor. It is the central of the building in the case of a fire emergency. It is a space where the status of fire detection, alarm system, and a communications and control system are displayed, and from which all systems can be manually controlled. The fire control room in MOT contains necessary controls, telephones, furniture and equipment for fire-fighting operations to be directed. Security guards will take shifts to monitor the systems in the control room. When the control unit receives signals from the alarm system, decisions are made immediately. Besides, the digital alarm communication system will automatically send signals generated by the fire alarm to the nearest fire station if there is an occurrence of fire. Fire detection and extinguishing control panels process results detection by sensors, control alarm devices and set off alarms to permanently manned stations and the fire department. They continuously monitor the extinguishing systems for functionality and trigger them electrically if necessary. In case of a danger, it receives signals, monitors and provides notifications to the occupants in MOT.

Figure 6.19 Fire alarm control panel

Diagram 6.16 Ground floor plan shows the location of fire control room

UBBL 1984 section 238 Fire Command Centre 1. Large or tall buildings over 30.5 metres or exceeding 9,290 sq.metres in gross area required Command and Control Centre to be located at the designated floor with direct telephone connection to Bomba.

31


6.2.5.8.1 Fire Alarm Control Panel

The fire alarm control panel is the main key component in managing the fire alarm of a building. The signal that receives from fire alarm system in the building will be displayed through the control panel in any case of emergency such as contacting the nearest fire brigade immediately or requesting treatment from nearest hospital. It informs the occupant about the exact address and condition of the location of fire through a series of fire mimic diagrams.

Figure 6.20 Fire alarm control panel, digital communicator direct to firefighter (left) water pump alarm control panel (right)

6.2.5.8.2 Intercom Panel

The purpose of intercom panel is to allow an easy communication facility between the fire chief and firefighting. All intercom systems are connected to the master handset panel located at the ground floor. During a fire break out, a call alert lamp will flash with audible signals at the master handset panel whenever there is an incoming call. As the handset is lifted to answer the call, the signal will be silenced.

Figure 6.21 Intercom panel connecting voice communication system at each floor

32


6.3 Passive Fire Protection System 6.3.1 Introduction Passive Fire Protection (PFP) is a form of fire safety provision that remains inert during normal conditions but play an important role during fire event. Passive fire protection is considered during the stage of planning the building’s design. The main purpose of this system is to protect the building itself from fire devastation, minimizing the danger of fire induced collapse or structural distortion and limiting the movement of fire and smoke between different space. The passive fire protection can be separated by 3 main parts, that is means of escape, compartmentation and firefighting access.

The passive fire protection system can be divided into two main branches. The first is to provide a mean of escape and the second is building compartmentalization. The definition of these two systems are stated below Passive fire protection (PFP) is an integral component in the structural fire protection and fire safety in any building. PFP works as a mechanism to slow down the spread of fire in a building, generally done by compartmentation of the building through the use of high fire rated structural components such as walls, floors and doors. The compartment also allows smoke not to overwhelm the building by diverting them out of the building which is vital as estimated death from smoke related injuries during fire account for more than 50%. It also works by allowing a safe escape passage in case of a fire emergency and efficient access route for the firefighters and their equipments. Unlike Active Fire Protection (AFP), it does not take any type of action during any fire event. Therefore, it can be said that both AFP and PFP are meant to work together during a fire, not one in place of another. Careful measures are specially paid attention on passive fire protection through simulation and comprehensive testing to ensure that it is suitable and work as intended should any fire emergency event arises. It is worth noting that these passive fire protections should function in extreme heat condition for a specific amount of time before failing. This is known as fire resistance ratings which are expressed in terms of how many hours it can last (example: 30 minutes, 1 hour, 1.5 hours, 2 hours, 4 hours and others). Both AFP and PFP are heavily regulated and monitored through UBBL 1984 and its compliance are checked thoroughly by the authorities before construction began to ensure its effectiveness as expected by the building codes

33


6.3.2 Means of Escape and Firefighter Access This refers to any route that one can take to go in and out of building safely during the occurrence of fire. Evacuation routes are always clearly defined through the fire escape staircases in every medium to high-rise building and are used to direct to occupants directly towards an exit point without any obstruction in between. Furthermore, there would also be an assembly point whereby people would gather after they escaped from the building. UBBL 1984 Section 166 mentioned that no less than two separate exits shall be provided from each storey together with such additional exits as may be necessary. These exits are required to be accessible at all times without obstructions. Moreover, Section 169 also said to maintain the accessibility of the paths, all fire evacuation routes are required to have a consistent width along its path of travel from the storey exit to the final exit.

34


Fire escape staircase is a fire protected area, usually surrounded by fire walls as the main designated escape route in case of any emergencies.

Figure 6.3.1 example of fire staircase

A fire door is a swing door with a fire-resistance rating that is used as part of a passive fire protection system to reduce the spread of fire and smoke between separate compartments of a structure which enables safe means of escape from a building.

Figure 6.3.2 example of fire rated door

Door Release Mechanism is located at lower ground floor whereby access is only possible through the use of ‘pass’ card. The door is locked with the use of magnetic door lock installed at the top of the door and the door frame. Figure 6.3.3 example of door release mechanism

The emergency exit signage functions as a guide to direct occupants to the nearest fire exit. It signifies the presence of a fire exit and the general direction of the fire exit location. Figure 6.3.4 example of fire escape sign

35


6.3.3 Compartmentation Compartmentation is a tool that is used in a vast majority of buildings, other than simple lowrise developments, this aims for the safety of the people during fire, allowing them to escape as harmlessly as possible. Compartmentation is referred to as in many different ways: fire walls, fire separation, enclosed stairs and others. It is basically the division of the whole building into cells and separating one cell from another through the use of fire rated walls assembled and fire rated doors used. In a large open space, such as in a mall, a fire shutter is employed which it will be operated in case of a fire. Fire dampers are usually used where ductwork passes any fire wall. The importance of compartmentation is exponentially increased when the building is higher and bigger as to escape in such large building takes a longer time. The size of occupancy in a building is also another important factor, as one staircase can only hold a limited amount of people at any given time.

Figure 6.3.5 example of compartmentation through the fire rated walls and fire shutters

36


6.3.4 Case Study of Passive Fire Protection System in MOT 6.3.4.1 Fire rated doors Fire door acts as a protective opening and provide a specific degree of fire protection to the opening. It also compartmentalizes a fire to stop the smoke and flames spreading from one section to another. They are usually located at the emergency exit or staircase.

6.3.4.2 Emergency exit signage Ensuring that emergency exits in the building are clearly marked with Exit signs can reduce confusion and injury in the event of an emergency.

6.3.4.3 Fire escape staircase Different kind of stairway for emergency escape in the event of fire, they shall be protected from exposure to fire risk throughout their descend down the staircase to the final exit at ground level.

6.3.4.4 Fire rated walls It is a wall that subdividing a building to prevent the spread of fire and having a fire resistance rating and structural stability. Firewalls are usually blank, parapeted and are non-load bearing.

6.3.4.5 Smoke and heat exhaust ventilation system Remove smoke from a building allows low level escape routes to be free from smoke and reduces damage to the building.

6.3.4.6 Fire roller shutters Fire shutters serve the same role as firewalls but only move into their operational position in the event of a fire. This is to keep fire from spreading to outside.

37


6.3.4.1 Fire Rated Doors A fire door is a door with a fire-resistance rating used as part of the passive fire protection system to reduce the spread of fire and smoke between separate compartments of a structure and to enable safe egress from a building.

Figure 6.3.6 Escape Door

Figure 6.3.7 Office Door

Fire rated door components: • Fire retardant core with plywood to a total thickness of not less than 43 mm with all edges • Laminated with adhesives conforming to BS 1444 “cold setting casein glue for wood” • Finished with a fire rated Intumescent strip throughout the side During the fire, intumescent seal in door frame groove tend to expand under the sense of heat from surroundings. It fills up the gap between the door frame to its original size. It prevents the smoke from entering to the other side of the door when there’s present of smoke.

38


Figure 6.3.8 Fire Resistance Rating on escape door

A fire-resistance rating typically means the duration for which a passive fire protection system can withstand a standard fire resistance test. This can be quantified as a measure of time, or it may entail a host of other criteria, involving other evidence of functionality or fitness for purpose. UBBL Section 162 (I) and (II): Fire doors in compartment walls and separating walls I. Fire doors in compartment walls and separating walls II. Openings in compartment walls and separating walls shall be protected by a fire door having a FRP in accordance with the requirements for that wall specified in the Ninth Schedule to these By-Laws. UBBL Section 173: Exit doors 1. All exit doors shall be operable from the inside without the use of a key or any special knowledge or effort.

39


6.3.4.2 Emergency Exit Signage The emergency exit signage functions as a guide to direct occupants to the nearest fire exit. It signifies the presence of a fire exit and thus should be clearly visible for the occupants. It is installed on the ceiling above every fire exit. In case of a power outage during fire, the fire exit sign will be illuminated, powered by a battery-backup system.

Figure 6.3.9 Emergency Exit Signature above escape door

Exit signs must be cleared from decorations or equipments which may impair visibility to means of an Exit. Emergency exit signage also known as ‘KELUAR’ signage can be found above the fire doors at every escape staircase. It is placed at the front and back door in the main lobby. It is used to give direction for the occupants during emergency and at the same time leads them to the outdoor open space or assembly point.

40


Figure 6.3.10 Emergency Exit Signature dimension

UBBL 1984 - SECTION 172: Emergency exit signs I.

Exit sign shall have word ‘KELUAR’ in a plainly legible not less than 15mm height with the principle stroke of the letters not less than 18mm wide

II.

The exits and access to such exit shall be marked by readily visible signs and shall not be obscured by decorations, furnishing or other equipment

III.

The sign with the reading of ‘KELUAR’ should indicating the direction shall be placed in every location where the direction of the travel to reach the nearest exit.

IV.

All exit signs should be illuminated continuously during period of occupancy.

41


6.3.4.3 Fire Escape Staircase

Figure 6.3.11 Level 5 Floor Plan

Emergency staircase

Fire escape staircase is a fire protected area. It connects from the storey exit to the final exit which is located at the ground floor. The most common type of fire escape staircase is an enclosed stairway. The enclosure must be a half-self-closing door that swing in the direction of egress travel. The doors must be swung into the stairway enclosure except at the level of exit discharge, where they must swing out.

42


Figure 6.3.12 Emergency staircase

Pressurization system of Fire escape staircase: • air supply (to supply fresh air into the stairway) • pressure relief (to avoid overpressure when doors are closed) • air release (air and smoke is released from the adjoining fire area). These three components work to create a positive pressure difference which prevents lobbies and staircases from filling up with smoke.

43


Figure 6.3.13 Emergency staircase section

UBBL 1984 section 110: No obstruction in staircases 1. There shall be no obstruction in any staircase between the topmost landing thereof and the exit discharge on the ground floor. 2. There shall be no projection, other than handrail in staircase, in any corridor, passage or staircase at a level lower than 2 metres above the floor or above any stair. 3. UBBL 1984 section 168(i): Staircases Except as provided in by-law 194 every upper floor shall have means of egress via at least two separate staircases.

44


6.3.4.4 Fire Rated Walls Firewall is found and is installed in almost every high-rise building as one of the fire protection system. It is constructed by using fire-resistance materials to allow firewall to withstand at least one hour of fire to reduce the potential of fire spreading. It acts as a barrier which provides an hour of escape period for the occupants to escape through fire staircase and door.

Fire Rated Wall Fire barrier walls are commonly continuous within the buildings or form one fire barrier wall to another fire barrier wall. It provides same fire resistance rating or even greater than the required rating for the application. The use of barrier wall is mostly to prevent fire from spreading from one room to another room or from inside out.

45


Firewall is made up of fire-resistance plasterboard at the external wall. It has steel stud connected to fiberglass insulation and fire blocking Gypsum board at both sides covered by fire- resistance plasterboards.

Figure 6.3.14 Fire Rated Wall Component

UBBL section 148: Special requirements as to compartment walls and compartment floors (6) Any compartment walls or compartment floor which is required by these By- Laws to have FRP of one hour or more shall be constructed wholly of non-combustible materials, and apart from other ceiling, the required FRP of wall or floor shall be obtained without assistance from any non-combustible materials.

46


6.3.4.5 Smoke and Heat Exhaust Ventilation System Smoke and heat exhaust ventilation systems, also known as "SHEVS" are natural or powered systems to remove smoke from a building allowing low level escape routes to be kept clear of smoke and reducing damage to the building.

Figure 6.3.15 Verticle Extract Ventilation

Figure 6.3.16 SSFA

Figure 6.3.17 SSEA

Mechanical smoke extraction units are especially indispensable to the following application areas: 1. High ceiling rooms without windows 2. Subterranean rooms and passages 3. Buildings which are constantly exposed to wind 4. Huge rooms with high fire load 5. Rooms with sprinkler systems 47


Figure 6.3.18 Process of Heat and Smoke Ventilation System

During a fire, smoke and fire gases spread through the entire building, the system is automatically triggered and start to extract smoke out of the building to prevent smoke cover the whole building and become obstruct towards building occupants. As the smoke is extracted, building occupants are safe to evacuate towards fire escape staircase. SSEA extract the smoke while SSFA is giving fresh air into the space.

48


6.3.4.6 Fire Shutter

Fire Shutter

Fire shutters serve the same role as firewalls, but they differ by the fact that fire shutters only move into their operational position in the event of a fire. They are usually wired to the fire control room and would activate autonomously in the event of a fire.

49


Figure 6.3.19 Fire Shutter in Basement Carpark

They are designed to operate in two stages. It is initially lowered to a predetermined safe height (usually right above head height) to act as a smoke barrier while still permitting occupants to escape. It then lowers and shuts completely after a predetermined time to act as a fire-resistant barrier. It is usually constructed out of steel or aluminium with a fireproof coating for an added protection.

50


Figure 6.3.20 Fire Shutter Plan View Component

Figure 6.3.21 Fire Shutter Section View Component

51


7.0 Mechanical Ventilation System 7.1 Introduction Ventilation is an important part of a building design where it helps to provide fresh air, moisture, remove odor and remove other airborne chemicals built inside a building. It requires movement of air to achieve indoor air quality and also to achieve the state of thermal comfort of the users in a building. Ventilation can be divided into 2 categories, Passive Ventilation and Mechanical Ventilation. Passive ventilation (also known as natural ventilation) is applied in a way that a building has some openings to allow the air to naturally ventilate through the building, while this type of ventilation cannot be controlled. Mechanical ventilation is a ventilation that allows the air to ventilate through a mechanical device in a building such as fan. It is a man-made object and it requires installation, electricity to activate it and require maintenance in order to achieve thermal comfort for the occupants in the building, while this type of ventilation can be controlled by the users to maximize the fresh air to be provided in a space or building. Therefore, it is much more efficient than passive ventilation as the air can be filtered to remove dust and airborne disease.

52


7.2 Basic Ventilation System There are 2 types of method for basic ventilation system which are, fan and makeup air supply. Fan element is to extract the moist air out from the wet area in the building, such as kitchen, bathrooms, gym and others. Makeup air supply is used to deliver the air from exterior to the interior of the building, the suction of the exhaust fan creates negative pressure where it allows the air from being pulled into the interior space of the house from the exterior (supply point).

Fan Figure 7.2.1 Fan that pull air out from a moisture space.

Make-up air Supply Figure 7.2.2 Air from exterior being pull through the interior space

53


7.3 Comparison of Natural & Mechanical Ventilation Natural ventilation takes place when an open space or open window or opening in the building allows the wind to move freely into and out of the building. The air movement will not be as consistent and efficient for fresh air to enter the building but it does not require any maintenance. Mechanical ventilation is used to control air movement inlet and outlet of the buildings. It gives sufficient fresh air into the building in which all the air will be filtered but require high maintenance cost. It provides an amount of oxygen into the building while remove excess carbon dioxide. It prevents heat concentration on mechanical appliances, human, lights, and machines.

54


7.4 Type of Mechanical Ventilation

7.4.1 Exhaust Ventilation System

Figure 7.4.1.1 Exhaust Ventilation

Exhaust ventilation is worked by depressurizing the air in the building. It reduces the air pressure inside the building. While the pressure out of the building is high, it causes causes the fresh air from the outside to be continuously forced into the negative pressure inside. The exhaust ventilation kept the room dry. Exhaust ventilation is more suitable in cold climates. If it is put in a warm or summer climate it will cause the moisture in the air from diffusing into the wall cavity and may cause condensation and moisture damage. It is mostly suitable for kitchen or bathrooms. It is a simple and inexpensive installation and a system that composed of only a single fan which is connected to centrally located, single exhaust point of house. This may draw pollutants along with fresh air.

55


7.4.2 Supply Ventilation System

Figure 7.4.2.1 Supply Ventilation

Supply ventilation is work by pressurizing the house. The fans are used to force the air from the outside to go into the building while air leak out through holes. It is a simple and inexpensive installation. The system introduces fan and duct system that welcome fresh air into the building in order to have a better control of air quality. It is preferred that the supply system is installed or located in the occupants’ rooms such as bedroom or living room. Supply ventilation will discourage the entry of pollutants from outside of the building because it allows the air outside to be filtered to remove pollutants and dust. This ventilation works best in hot or humid climate because the pressure will create moisture in the room at cold climate. The moisture in the air will cause mould or mildew and decay to happen.

56


7.4.3 Balanced Ventilation System

Figure 7.4.3.1 Balance Ventilation

Balance ventilation system is a properly designed and installed system. It is neither pressurizing nor depressurizing a house. It introduces equal quality of air outside and the air inside. It will facilitate well if the supply and exhaust vents are in an appropriate place to distribute the fresh and good quality of air into the building. It is more suitable to apply at spaces where it is used often, such as bedrooms. It will not remove the moisture in the room but it will filter to remove dust and pollen from the outside before the air enter the room. Balance system is suitable in all climate because it requires two ducts and fan system and it is expensive to be install.

57


7.4.4 Energy Recovery System

Figure 7.4.4.1 Energy Recovery System

Energy recovery system will cost more than other types of installation. In order to save cost, many systems share the same existing ductwork. It has a higher maintenance and require more power supply to activate. Installation require an expertise and well-experienced contractor because every room requires to have a supply and a return conduct. The duct that is connected to the ventilator must be short and straight and a bigger size of it is needed to improve the performance. Energy ventilation system is needed to clean regularly to prevent deterioration as it may cause the ventilation rates and heat recovery to be ineffective and it is also to prevent mould and bacteria from growing on the heat exchange surface.

58


7.5 Component in Mechanical Ventilation System 7.5.1 Fan Fan is a main device in mechanical ventilation system where it helps to exhaust and supply air circulation in the building. There are 3 types of fan: 1. Propeller Fan 2. Axial Fan 3. Centrifugal Fan

7.5.1.1 Propeller fan Propeller fan is a general ventilation fan where it is cost effective. It produces an air flow through the building by creating different pressure between the outdoor and the indoor area. It has long slender blades. There are fixed or adjustable pitch models which the differences are mainly the wind oriented by the blades. It is normally used in buildings, toilets and kitchen where it does not create lots of sound and acts as an exhaust, cooling tower or air-cooled heat exchanger.

Figure 7.5.1.1.1 Propeller Fan (Fixed)

Figure 7.5.1.1.2 Propeller Fan (Adjustable)

59


7.5.1.2 Axial Fan Axial Fan is similar to the propeller fan but the blades are shorter and rigid that it is assembled in a metal tube to provide thermal control and air flow into the building. Axial fan can be divided into 2 types which are the vane axial and tube axial that is due to the construction requirement. It can be easily found and is normally used in the basement and tunnel.

Figure 7.5.1.2.1 Tube Axial Fan

Figure 7.5.1.2.2 Vane Axial Fan

60


7.5.1.3 Centrifugal Fan Centrifugal fan is mostly used in industry where it can move large or small amount of air. It is often called as a blower. The air pressure can be increased by the fan wheel, which is a series of blade mounted on a circular hub. The air flow created by centrifugal fan will direct through a system of duct and tubes in order to help create a high pressure of airflow.

Figure 7.5.1.3.1 Centrifugal Fan

Figure 7.5.1.3.2 Types of Centrifugal Fan

61


7.5.2 Filter Filter is one of the alternative elements to be used in the mechanical ventilation. It helps to filter the air to prevent carbon dioxide, pollutant and other unwanted elements to flow into the building. This allows good quality of air to flow into the building. There are 4 types of filters: 1. Dry 2. Viscous 3. Electrostatic 4. Activated carbon

62


7.5.2.1. Dry Filter The air from the outside flow through the roll filter to filter the air shown in diagram 7.5.2.1.1. The filter fabric is a disposable element filter shown in diagram 7.5.2.1.2.

Figure 7.5.2.1.1 Roller Filter

Figure 7.5.2.1.2 Disposable Element Filter

Figure 7.5.2.1.3 Dry Filter

63


7.5.2.2 Viscous Filters It filters air that the surface of impinges is covered with a viscous fluid or oil, to attach the dirt particles at there.

Figure 7.5.2.2.1 Viscous Filters

7.5.2.3 Electrostatic Filters It is a safe and naturally occurring phenomenon where the air from the exterior is cleaned by using static electricity before it come into the interior space. The air flows through a maze of static prone fibers causes an electrostatic charge. The static charge holds the airborne particles which are attracted by it. It can be cleaned by washing it.

Figure 7.5.2.3.1 Electrostatic Filters

64


7.5.2.4 Activated Carbon Filter It is a filter that uses a bed of carbon to remove pollutants and airborne particles by using chemical.

Figured 7.5.2.3.1 Example how activated carbon filters are used

7.5.3 Ductwork

Ductwork is an air passenger that is used in heating, ventilation and air conditioning to supply air, return air and exhaust air. There are 3 different shapes for ductwork which are circle, square or rectangular. Circle shaped ductwork are more efficient, and less frictional resistance to air flow. Rectangular shaped ductwork is more easily fitted into the building fabric.

Figure 7.5.3.2 Circular Ductwork

Figure 7.5.4.1 Rectangular Ductwork

65


7.5.4 Fire Damper

A passive fire protection product. It is used to prevent the spread of fire inside the ductwork.

Figure 7.5.4.1 Fire Damper

7.5.5 Diffusers

A device that reduce velocity and increase the static pressure of a fluid passing through a system.

Figure 7.5.5.1 Diffuser

66


7.6 Case Study of Mechanical Ventilation in MOT Ministry of Transport has both features that are the supply and exhaust ventilation system. They allow the building to have a better ventilation in order to achieve thermal comfort for the users, as well as it is safe for emergency exit if there is a fire. Due to their large scale, both systems are installed to ensure the air supply and remove is at a balance rate.

Level M&E N.T.S.

Basement 67

N.T.S.


7.6.1 Supply Ventilation System In MOT, the supply ventilation system is used in the stairwell. It uses an inlet in which the machine will supply the air into the stairwell that forces the unwanted air out of it through another duct. The outside air supply is provided by mechanical means in order to maintain positive pressure by using pressurization method so that it provides smoke free escape route in case of a fire in the building.

7.6.1.1 Stairwell Pressurization System Pressurization creates different pressure between the fire staircase and the elevator space. It will prevent the movement of smoke to enter the stairwell escape route. It keeps the exit routes to be free from smoke during a fire. It allows occupants to have a longer time to escape from the building.

Figure 7.6.1.1.1 Emergency escape staircase with pressurrization system Credit Serene 2018

Figure 7.6.1.1.2 Sketch shows how pressurization works.

68


UBBL- Pressurized system for staircase CLAUSE 202 System is used when height of the building is more than 45.75 meters. •

Air capacity of fan need to be sufficient to maintain an air flow of not less than 60 meters per minute through the doors which are deemed to be open.

The number of doors which are deemed to be opened at the one time shall be 10% of the total number of doors opening into the staircase with a minimal number of 2 doors open.

With all the door closed the air pressure differential between the staircases and the areas served by it shall not exceed 5 mm water gauge.

The mechanical system to prevent smoke from entering the staircase shall be automatically activated by a suitable heat detecting device, manual or automatic alarm or automatic wet pipe sprinkle system.

Which meets the functional requirements as may be agreed with the D.G.F.S.

69


7.6.1.2 Lift Lobby Pressurization System Lobby pressurization system is to ensure smoke-free lift lobby system and it is one of the necessary routes in case of a fire. At figure 7.6.1.2.1, it is to supply air so that it keeps a positive pressure at the escape route. The pressurization system can prevent the smoke from entering the hallway of lift and flows towards the fire staircase escape route. Figure 7.6.1.2.2 is the exhaust that allow the smoke to flow out from the hallway of escape route.

Figure: 7.6.1.2.1 Pressure relief damper found at the lift lobby

Figure: 7.6.1.2.2 Expel smoke if there is a fire happening at the lift lobby

70


7.6.1.3 Basement Carpark Supply Air Carpark System The air from the exterior of the building is being pulled into the carpark to allow the car park to obtain enough fresh air in order to ensure that the basement is constantly ventilated.

7.6.1.4 Ductwork

Figure 7.6.1.3.1 Fresh air is coming into the carpark.

Ductworks are tubes that is part of the ventilation system, they are used to supply fresh air into the car park.

Figure 7.6.1.4.1 Fresh air flowing through the carpark (SSFA)

71


UBBL CLAUSE 197 •

Protected lobbies shall provide to serve staircases in buildings exceeding 18 meters above ground level where the staircase enclosures are not ventilated through external walls.

Building exceeding 45 meters above ground level, such protected lobbies shall be pressurised to meet the requirements of section 7 of the Australian Standard 1668, Part I- 1974 or any other system meeting the functional requirement of the D.G.F.S.

Protected lobbies may be omitted if the staircase enclosures are pressurised to meet the requirement of by-law 200

72


7.6.2 Exhaust Ventilation System In MOT, it is used at the car parks and other utility rooms. It is to prevent accumulation of smoke during the emergency.

7.6.2.1 Car Park Exhaust System The ducts at the basement car parks has the word SSEA printed on it. It is to direct the smoke or fumes from the basement car park towards the duct that is connected to the outside of the building so that there will be new air to flow into the building.

Figure 7.6.2.1.1 Show a space that air being exhaust out from a space

Figure 7.6.2.1.2 Basement duct (SSEA) exhaust

73


Component of Car Park Exhaust System: 1. Ductwork Ductworks are tubes that is part of the ventilation system, used to expel pollutants or smoke out of the building (Figure 7.6.2.1.3 above) 2. Outer griller Use to suck the smoke and fumes from the carpark into the metal duct.

Figure 7.6.2.1.3 Outer griller

UBBL 249. Windowsless buildings, underground structure and large area factories, smoke venting facilities shall provided for the safe use of exit. Third Schedule 7- Mechanical ventilation system in basement areas. 1. Basement and other enclosure below ground level used for working areas or for occupancy of more than 2 hours duration shall be provided with mechanical ventilation having a minimum of six air changes per hour. 2. Basement or underground car parks shall provided with mechanical ventilation such that the air exhausted to the external atmosphere should constitude not less than six air changes per hour. Air extract opening shall be arranged such that it is not less than 0.5 meters above the floor lrvrl period system. 3. Basement and other enclosure below ground level used for working areas or for occupancy of more than 2 hours durations shall be provided with a minimum of one fresh air change per hour, or the minimum of 0.28 cmm per person working in such area.

74


7.6.3 Utility Room Exhaust System The exhaust system in the utility room is to control the air quality and release the smoke when there is a fire emergency. When air is extract out by the exhaust fan, oxygen is reduced within the space and it avoids the fire from spreading. The exhaust vent is activated by the machines (fan).

Figure 7.6.3.1 The exhaust fan connected to the ductwork

Level)

Figure 7.6.3.2 The exhaust fan is connected from the utility room to the top floor (M&E

Figure 7.6.3.3 Sketch shows how air is extracted out and regulated from the utility room

UBBL Clause 250 Natural draught smoke venting 1. Natural draught smoke venting shall utilise roof vents in walls at or near the ceiling level. 2. Such vents shall normally be in open positions of it they are closed they shall be so designed to open automatically by an approved means in the event of a fire.

75


8.0 Air-Conditioning System 8.1 Introduction Air-conditioning (A.C.) system is a system that removes heat and moisture from the interior of an occupied space, improving the thermal comfort of occupants and maintain the air quality of an interior building. Air-conditioning system generally refer to any form of technology that modifies the condition of the air. There are several different kinds of air-conditioning system, while choosing a right airconditioning system for a building depends on the building size and function. So that the airconditioning system can be fully utilize, also to ensure energy efficiency and saving costs. An improper design or installation of air-conditioning system may cause bad consequences, affecting the thermal comfort, lower the air quality and consume more energy in a building which results the waste of energy and might cause air pollution.

76


8.2 Operating Principles of Air Cooling When gas is compressed, it will turn into liquid at a certain point. At the same time, a large amount of latent heat will be released from the gas. In an opposite way, when liquid pressure was lowered, as it will vaporizes back into gas and large amount of latent heat will be absorbed into the liquid. Air conditioning system works by removing heat from a room and releasing the collected heat to outdoor. This process involves two type of cycles to take place which are the refrigeration cycle and air cycle.

Figure 8.2.1 Cycle of air-cooling

77


8.2.1 Refrigerant Cycle The refrigeration cycle is a process to remove heat from one place to another by using a liquid called refrigerant continuously recycling through the process. This process consists of 4 main components which are the Evaporation, Condenser, Compressor, and Expansion valve.

Evaporator

The evaporator is a coil of pipe with low pressure liquid refrigerant inside it. Its function is to absorb heat on the pipe surface, so that the air blown over the surface of this pipe is cooled.

Figure 8.2.2 Evaporator

Compressor

In this component refrigerant was compressed and the vapor from the evaporator is pumped throughout the system. When refrigerant vapour was compressed, the vapor becomes very warm, as high as 200’F and pumps it to the condenser.

Figure 8.2.3 Compressor

Condenser

In this process great deal of heat is expelled and turn the refrigerant vapor into liquid. All those was caused by releasing high pressure refrigerant vapor and dispels heat through the condenser coils.

Figure 8.2.4 Condenser

Expansion Valve A valve that meters liquid refrigerant into the evaporator and restrict the flow of refrigerant from flowing Figure 8.2.5 Expansion Valve

backward.

78


Figure 8.2.6 Refrigerant cycle in air conditioning system

The refrigerant cycle is as follows: 1. Starting from the compressor, the refrigerant comes into the compressor as a low pressured gas, then the refrigerant was compressed, turned into high pressure gas and move to the next component, the condenser. 2. As the gas flows into the condenser, the gas was liquify. Heat was expelled to the external in this process. 3. Then the refrigerant was moved to expansion valve under high pressure and then was lowered the pressure of refrigerant when it leaves to next component, evaporator 4. In evaporator, heat from the air in the room was absorbed and turn liquid refrigerant into low pressure gas. 5. At last, the low-pressure gas was back into the compressor and continuously repeat the cycle again.

79


8.2.2 Air Cycle Air cycle is a process to distribute treated air into the room that needs to be conditioned. Removing the latent heat inside a room by using evaporator to absorb the return air. Water can also involve in this cycle as a medium to absorb the heat. The distribution of air can be either through ducts of chilled water pipes. Thus, heat inside the room is removed and slowly the internal air becomes cooler. There are several components which are required for air cycle to take place. 1. Air handling unit (AHU) - recycling some return air from room 2. Air Filter - dust control 3. Blower fan - to propel the air for distribution 4. Ductwork and diffusers - to distribute air from AHU to room that need to be air-conditioned 5. Clean air intake - to renew the contents of air to be distribute 6. Humidifier/Dehumidifier - used for humidity issue

Figure 8.2.7 Air cycle in air conditioning system

80


8.3 Air Conditioning System Generally, there are four type of air conditioning system, each type of air conditioning system will be used by depending on the building size, type, functionality and their surroundings. The type of air conditioning systems includes room air conditioning system, split air conditioning system, packaged unit air conditioning system and centralized air conditioning system.

8.3.1 Room Air Conditioning System Room air conditioning system is the simplest form among all air conditioning systems. It had a smaller size which are suitable to be adapted in small rooms. It is usually installed at window opening or wall. Room air conditioning systems can be divided into two compartments, which are the room side and outdoor side, separated by an insulated partition

Figure 8.3.1 Indoor unit of room air conditioning system

Figure 8.3.2 Outdoor unit of room air conditioning system

Figure 8.3.3 Cross section and components of room air conditioning system

81


8.3.2 Split Air Conditioning System

Split unit air conditioning is the most popular type of air conditioning system nowadays due to its silent operation, elegant looks, and no need to make a hole in the wall. This air conditioning also consists of two units which are one outdoor unit, the condenser and one or several indoor units, the evaporator or AHU. Two of the unit are connected by a copper tubing.

Figure 8.3.4 Indoor unit of split air conditioning system

Figure 8.3.5 Outdoor unit of split air conditioning system

Figure 8.3.6 Components and function of split air conditioning system

82


8.3.3 Packaged Unit Air Conditioning System

Packaged unit air conditioning system is similar to room air conditioner but in a much larger size with fixed rate capacities. It is normally utilized in medium size building or room, such as halls and restaurants. This air conditioner enclosed all the important components inside a single casing which is considered as difficult for maintenance. There are two types of packed unit air conditioner which are the ducted and ductless.

This air conditioning system can be installed at the rooftop, on the ground, and inside a ceiling or crawl space. Thus, ducting was required for distribution of the conditioned air.

Figure 8.3.7 Cross section, components and function of packaged unit air conditioning system

Packaged unit air conditioning system have two methods of removing the indoor heat in the larger packaged unit. The first method is air-cooled method, which remove indoor heat by outdoor air, where the equipment is located outside of the building adjacent to the room to be air conditioned or on the rooftop for easy flow of air. Second method, water-cooled method which a ducted type, the duct comes from the top of the unit that extends to various rooms that are to be cooled with a continuous supply of water from cooling tower removing the indoor heat. This method consists a basic refrigeration component that built into the compacted indoor unit.

83


8.3.4 Plant Air Conditioning System

Plant air conditioner system is used in large, complex or multiple blocks building, such as hospital, hotels, office towers, airports and shopping mall. Usually this system was installed during the construction of the building and should be integrated with the structure and space planning purpose. The main components of this system are the refrigerant plant, AHU and cooling tower. The refrigerant plant consists of chiller that chill the refrigerant and there are two type of chiller. One is the water-cooled chiller which connect to cooling tower and the second is aircooled chiller which connected to air-cooled condenser. The cooled refrigerant will be distributed to AHU.

Figure 8.3.8 Components and refrigerant flow in plant air conditioning system

84


Figure 8.3.9 Components of AHU in plant air conditioning system

AHU is a large metal box containing a blower, heating or cooling elements, filter rack or chamber, sound attenuators, and dampers. It is connected to ductwork that distribute and return the conditioned air.

Figure 8.3.10 Components of cooling tower in plant air conditioning system

Cooling tower is a heat removal device to transfer heat from the chiller to the atmosphere through evaporation of water. To optimize this function the cooling tower it is usually located on high open space to get optimum ventilation. The cooling water is pumped to the refrigeration machine where it cools the condenser coil. Thus, it needs to be connected to a water tank to replace the water lost by evaporation.

85


8.4 Case Study of Air Conditioning System in MOT

In MOT there are two type of air conditioning systems which are the centralized air conditioning system and split unit air conditioning system. Centralized air conditioning system is the main air conditioning system in MOT, as for the split unit air conditioning system in MOT is only used in the elevator control room and also act as a backup air conditioning system when the main air conditioning system is down.

8.4.1 Centralized Air Conditioning System

MOT is a 15 storeys office building, like most of the large and complex building generally will choose to use this kind of air conditioning system, but what makes MOT different from other buildings is that MOT does not have a refrigerant plant of its own. MOT is located in Putrajaya, an urbanize and due to its location, MOT was introduced to use district cooling plant system, a plant that is located in the center of a city and provides chilled water to the surrounding buildings.

Figure 8.4.1 Function of district cooling system

86


8.4.1.1 District Cooling System

District Cooling System of MOT was provided by Makhostia SDN BHD. The central plant of this district cooling system is just located beside MOT. This system produces chilled water from the central plant and distributes by using a system of pipes that can run underground. The benefits of using district cooling system is to reduce the space for its own refrigerant plant and the cooling tower on the rooftop. Thus, it can improve the aesthetic of the building. Besides, it aids the environment by increasing energy efficiency and reducing environmental emissions including air pollution, the greenhouse gas, carbon dioxide and ozone-destroying refrigerants.

Figure 8.4.2 Map showing the GDC and the MOT

Firgure 8.4.3 Picture showing the Gas District Cooling (GDC)

Figure 8.4.4 Components and function of district cooling system

87


8.4.1.2 Heat Exchanger (HEX) Inside the MOT the transmission of the underground pipes is connected to a room called HEX room. HEX room is a heat exchange room consists of coils that allow the chilled water from district cooling plant to chill the water in the MOT then distribute to other components. The returned water will flow back to HEX room to be chilled.

Figure 8.4.5 Location of Hex room in basement plan

Figure 8.4.6 Function of heat exchanger

88


8.4.1.3 Chill Water Pump

Then, the chilled water in HEX room is transferred into the chilled water pump room that was located beside it. The pumps pump up the chilled water to all the AHU in the whole building.

Figure 8.4.7 Location of Chill Water Pump room in basement plan

Figure 8.4.8 Water pump in chill water pump room

89


8.4.1.4 Air Handling Unit (AHU)

Every floor in MOT consists of AHU except basements. There are 28 units of AHU in MOT, but half of the numbers will only be used for every week. Generally, AHU in MOT works the same as others, but only the chilling system is different. After the AHU received the chilled water from chill water pump, the chilled water was transfer to cooling coil to produce cool air. Then the cool air will distribute through the ducts and spread out from the diffuser into the room that needs to be conditioned. The returned air will then flow back to AHU to be chilled.

Figure 8.4.9 Location of AHU in highest floor of MOT

Figure 8.4.10 AHU in MOT

90


Components of AHU in MOT

Air filter Before the hot air return to AHU, the air will pass through air filter that consist of a layer of foam and a layer of grill. Both foam and grill are used to ensure the cleanliness of the filtered air and to protect the inner part of AHU components.

Figure 8.4.11 Air filter

Cooling coil Cooling coils is made of copper pipes, it is attached to the chilled water pipe from the HEX room. Cooling coil is coiled up to increase its surface to maximize the area of heat transfer of air so hot air will be cooled down while it contacts with the coil. Figure 8.4.12 Cooling coil

Fan blower Fan blower that is installed inside AHU is to blow the cooling coil and transfer the cooled air through the air duct and then to the diffuser.

Figure 8.4.13 Fan blower

Chill water pipe Chill water pipe is used to transfer chill water. In the diagram, it shows two chill water pipes with a different label, they have different functions. CHWS is the pipe that supply chill water to AHU and CHWR is the return pipe of flows the chill water to HEX room. Figure 8.4.14 Chill water pipe

91


8.4.1.5 Air Duct and Diffuser

Air duct is a connector between AHU and diffuser. It is made of aluminium foil, so that it provides a good insulation that can retain the temperature of cooled air inside it while transferring it into the diffuser. While diffuser is an outlet of cooled air to a certain location. It constantly provides occupant a comfortable environment by removing heat and providing cooled air from AHU to a room that need to be condition.

Figure 8.4.15 Air duct

Figure 8.4.16 Diffuser in most area

Figure 8.4.17 Diffuser in cafeteria

92


8.4.2 Split Air Conditioning System

In MOT split air conditioning system is used only in elevator control room and as a backup air conditioning system while the plant air conditioning system is down.

93


8.4.2.1 Split Air Conditioning System in Elevator Control Room

Indoor unit Split air conditioning system in the elevator room is classified as a ducted type of split air conditioner. There are total of four units inside the room and all of them are attached to the ceiling. The main reason of having this type of air conditioning system is to cool down the temperature of the control room since it is a control room that is always working and produce heat continuously. The reason why the elevator control room has a separated air conditioning system from the whole building is to prevent the elevator from overheating and stop working when the AHU unit is down.

Figure 8.4.18 Location of indoor unit in elevator room

Figure 8.4.19 Indoor unit of elevator control room

94


Outdoor unit The outdoor unit for this air conditioning system is placed at the same level as the control room. Four condensers are facing outward from the building which is shown at the figure below.

Figure 8.4.20 Location of outdoor unit in elevator room

Figure 8.4.21 Outdoor unit of elevator control room

95


8.4.2.2 Split Air Conditioning System as a Backup

Indoor unit It is only installed at 10th floor where the meeting rooms are located. Occupants will not use this type of air conditioning system unless the main air conditioning system is down. All the indoor unit is ceiling mounted/cassette type in the meeting room

Figure 8.4.22 Indoor unit of meeting room

Outdoor unit For the outdoor unit, MOT just simply put the condenser out of the meeting room, which is as shown in the figure below.

Figure 8.4.23 Outdoor unit of meeting room

96


9.0 Mechanical Transportation System 9.1 Introduction Mechanical transportation system is a type of transportation that is used to move goods and people vertically between different levels of floors or horizontally in a modern building. There are 3 common types of transportation include lifts (elevators), escalators and travelators. Generally, it is powered by an electric motor that drives traction cable and counterweight systems like a hoist or a hydraulic pump. According to the clause of 124 within the UBBL 1984, at least a lift shall be provided for nonresidential buildings exceeding 4 storeys above or below main entrance. Besides, lifts should be positioned at locations which provide easy access for all building users such as central entrance lobby of offices, hotels, and apartments with a maximum walking distance of 45mm to the lift lobby. The importance of mechanical transportation system includes: 1. Basic needs - ease burden in lifting the occupants to a higher or lower level in a building 2. Comfort needs - work efficiently for office buildings, or a large organization 3. Fire requirement - provide fire lift in case of an emergency 4. Complying with UBBL 1984 - Buildings with more than 4 storeys must provide a lift system It is required to divide a building into groups of elevators serving floors, called zones, or more categorizing them as low,middle and high zones. The benefits of lifts the users as follows: 1. carry occupants to their destination zone as fast as possible, express zones are provided to run express or shuttle lifts between the lobby and each zone 2. maximise high speed elevator performance, reduce round trip time, increase passenger handling capacity, and reduce the required number of lifts 3. space above the low and middle zone elevator hoist ways in the building is available for use as officers and others purpose 3 common types of mechanical transportation are: 1. Lifts/Elevators 2. Escalators 3. Travelators 97


9.2 Lift Lift (also known as elevator) is a type of vertical transportation with a platform housed within a shaft that moves people or goods between different floors of a building safely and efficiently. It is used in modern offices, government buildings and high-rise buildings. Arrangement of lifts is important to maintain a smooth circulation between the occupants of a building. Factors affecting lift installation: 1. type 2. speed 3. quantity 4. layout

9.2.1 Lift Application

Type of lifts

Car speed (m/s)

Passenger- up to 4 floors

0.3 - 0.8

4 to 9 floors

0.8 - 2.0

9 to 15 floors

2.0 - 5.0

Over 15 floors

5.0 - 7.0

Paternoster

Up to 0.4

Goods,to any height

0.2 - 1.0

Hydraulic,passenger or goods

0.1 - 1.0

98


9.2.2 Types of Lifts (Elevators) There are various types of elevators to fit in different building typologies, whether it is with rope or not, it is depending on the means of moving. There are two main types of elevators that are commonly used, namely electric lift (traction with a machine room and machineroom-less traction) and hydraulic lift. However, there are variation upon each given type.

9.2.2.1 Electric Lift Electric lift, or traction lift is lifted by ropes which passes over a wheel that is connected to a motor, usually an electric motor, that is located in the machine room situated above the elevator shaft. This type of elevator is commonly used in mid and high rise application, as they have higher travel speeds than other types of elevators, for example the hydraulic elevator. In most cases, a counter weight is also used, so that the motor’s load is eased, making the elevators more efficient by offsetting the weight of the car and occupants. Traction elevator can be further divided into geared, gearless, (machine room elevator) or non-machine room elevator and it is depending on its application.

Figure 9.1 Geared Traction Lift

Figure 9.2 Gearless Traction Lift

Figure 9.3 Machine-room-less Lift

Geared traction lifts have a gearbox that is attached to the powered electric motor, which 99


drives the wheel that moves the ropes. They are capable to speed up to 500 feet (152400 mm) per minute. The maximum travel distance for a geared traction elevator is around 250 feet (76200 mm). Gearless traction lifts have the wheel attached directly to the motor. They are capable to speed up to 2,000 feet (60960 mm) per minute. They have a maximum travel distance of around 2,000 feet (60960 mm). Therefore, they are the only choice for high-rise applications. The machine-room-less lifts do not have a dedicated machine room above the elevator shaft. Its control boxes are located in a control room that is adjacent to the electrical shaft on the highest landing and within approximately 150 feet (4572 mm) of the machine. They are capable to speed up to 500 feet (15240 mm) per minute. The maximum travel distance is around 250 feet (7620 mm).

100


9.2.2.2 Hydraulic Lift Hydraulic lift has a slightly slow mechanism. It consists of a piston placed below the lift. It is supported from the bottom by the piston that pushes the lift upward or downward as an electric motor pumps hydraulic fluid into the piston when the specific floor button is pressed. The elevator will descend as the fluid is released. Hydraulic lift is commonly found in low-rise buildings due to a slower speed and maximum travel distance of about 80 feet (24384 mm) or 200 feet (609960mm) / minutes. The electric motor is accommodated in a machine room which is built in the lowest level of the building, unlike the traction lift. This type of lift is used for smaller buildings with are less than 10 floors. Same as the traction lift, there are different types of elevators in hydraulic system as well, namely:

Figure 9.4 Annotated diagrams of conventional hydraulic lift, hole and non-holed hydraulic lift and roped hydraulic lift

101


9.2.2.3 Pneumatic Lift Pneumatic elevators are raised and lowered by controlling air pressure in a chamber where the elevator sits. By applying simple principles of physics, the difference in air pressure above and beneath the vacuum elevator cab literally transports cab by air. It is the vacuum pump or turbine that pull the cab up to the next floor and the slow release of air pressure that floats cab down.

Figure 9.4 Example of Pneumatic Lift

9.2.2.4 Climbing Lift A climbing elevator is a self-ascending elevator with its own propulsion. The propulsion can be done by an electric or a combustion engine. Climbing elevators are used in masts or towers in order to make easy access to parts of these constructions such as flight safety lamps for maintenance.

Figure 9.5 Example of climbing lift

102


9.2.2.5 Comparison on Cost and Energy Consumption on Different Types of Lifts Geared traction

Gearless traction

• Averagely high initial cost

• High initial cost

• Medium ongoing maintenance costs • Medium energy consumption

• Medium ongoing maintenance costs • Less energy consumption than geared traction

Machine-room-less

Hydraulic

• Low initial cost than geared traction

• the lowest initial cost ongoing

• Low ongoing maintenance cost than geared traction

• The lowest maintenance costs

• Less energy consumption than feared traction (require less space, operation and realibility are on par with gearless traction)

103

• Consume the most energy (as it electric motor works against gravity,it forces hydraulic fluid into the piston)


9.3 Escalator

Escalator is the immediate mean of transportation, transports people from a lower level to the next higher level only. It can continuously move large number of live loads, which is the people. It is a quick and efficient mode of transportation as no waiting time required and thus no extra time consumed.

Besides, it is reversible to suit the main flow of traffic during peak periods. In a building, it should be located highly visible to the users. Factors affecting the carrying capacity include: 1. Velocity (normally varies between 0.45m/s to 0.7m/s) 2. Width of the tread (normally varies between 600mm to 1200mm)

9.3.1 Components of Escalator

Figure 9.6 Detailed components of escalator

104


9.3.2 Escalator arrangement

There are various arrangements of escalator constructed to suit the need and spatial typology of each building, these include: 1. Single bank with traffic in one direction (1-way traffic)

2. Single bank with interrupted traffic in one direction (1-way traffic)

3. Double parallel bank with interrupted traffic in two direcion (2-way traffic)

4. Double crisscross and continuous bank in two direction (2-way traffic)

105


9.4 Travelators Travelators are built for horizontal movement that carry people or load horizontal from one place to another place. It can be inclined up to 15°. The material of its moving surface is usually made up of reinforced rubber belt or a series of linked steel plate running on roller. It is widely used at air terminals, railway stations and shopping centers. Factors affecting its carrying capacity include:

1. Velocity (0.6- 1.33m/s) 2. Width of travelators (0.6m to 1.0m)

One application that uses the concept of travelator is the conveyor belt. Conveyor belt is the carrying medium consisting of two or more pulleys, with the endless loop of carrying medium. It is applied to move the baggage and luggage of tourists at the airport.

Figure 9.7 Travelator at air terminal

Figure 9.8 Conveyor belt at airport luggage reclaim area

106


9.4.1 Component of Travelators Diagram below shows the detailed sectional drawings of the components of a travelator.

Figure 9.9 Components of travellator

107


9.5 Case Study of Mechanical Transportation System in MOT In MOT, the main mechanical transportation system, spans the height of the buildings throughout reaching every level of the building. MOT has 15 levels, including 4 levels of basement car park and 1 M&E level at the highest level. UBBL 1984 Part VI: Constructional Requirements Clause 124 For all non-residential buildings exceeding 4 storeys above or below the main access level at least 1 lift shall be provided.

Figure 9.10 Ground floor plan shows the highlighted location are the 7 elevators

MOT meets the UBBL requirement by providing 7 elevators with a total building height of 15 storeys. (10 floors, 4 floors of basement car park, 1 M&E floor)

108


9.5.1 Overview Traction lifts are adopted in MOT in which there is a mechanical and electrical (M&E) room located above the lift shaft.

Figure 9.11 shows the capacity of each lift in MOT and its instructions

Type of elevator: Geared Traction Lift (with machine room) Brand: Toshiba Rated capacity: 1635 kg Rated speed: 1.0- 1.5m/s Max no of person: 24

109


9.5.2 Geared Traction Lift The type of lift used in MOT is geared traction lift with machine room. The machine room is driven by Alternating Current (A.C) or Direct Current (D.C) electric motors. The design of electric motor drives a worm-and-gear-type reduction unit, which turns the hoisting sheave.

The advantages of adopting geared traction lift include: 1. Less expensive installation than gearless traction lift 2. Smoother ride quality than hydraulic lift 3. Faster speeds than other product lines 4. Accommodate front/rear openings 5. Overhead or basement machine rooms 6. Non-proprietary equipment

While the lift rates are slower than a typical gearless elevator, the gear reduction offers the advantage of requiring a less powerful motor to turn the sheave. An electrically controlled brake between the motor and the reduction unit stops the elevator, holding the car at the desired floor level.

110


9.5.3 Components of Geared Traction Lift

Figure 9.12 Components of geared traction lift

111


9.5.4 Machine Room (Lift Motor Room) A lift machine room houses machinery and electrical controls. In MOT, the machine room is located at the 15th floor, which is the highest level of the building. It sits at the top of the lift shaft which minimizes the length of the rope and optimizes the efficiency. It is made up of solid concrete ceiling, walls, and floor. An elevator motor room contains the hoisting motor, hoisting sheave control panel, inspection board, gear box, safety gear and the overspeed governor.

Figure 9.13 Level 15 floor plan highlighted the location of the lift machine room

Figure 9.14 Panoramic view of level 15 elevator motor room

112


9.5.4.1 Exhaust Fan

For every machinery, it is crucial to allow the cooling of their counterparts to prevent them from overheating, combusting and damage of lift components which could pose danger to the lives of the occupants in the building.

Figure 9.15 Exhaust fans prevent overheating of machineries

9.5.4.2 Hoisting Motor A hoisting motor is a device to lift or lower a load with the help of a drum or lift-wheel around which rope or chain wraps. It can be manually operated, electrically or pneumatically driven and may use chain, fibre or wire rope as its lifting medium. The type of motor is used in the hoisting motor consists of the wound field DC motor to aid in providing specific torque speed as required by the application of the lift.

Figure 9.16 Wound Field DC motor used

113


9.5.4.3 Control Panel Cabinet The control panels in the cabinet receive the signals from the operating panels and send buttons, then the electric motor is controlled. The cabinet houses the necessary panel components and power supply to provide sufficient power to the lifts. There are 7 control panels in the machine room. Every lift has its own controller. The lifts in MOT are automatically controlled whereby the controllers are electromechanical relay based. They are big in size and thus consume more operational power.

Figure 9.17 The control panel cabinet at M&E level

114


9.5.4.4 Lift Main Control Board The inspection board of the lift is powered by the Parallel Elevator Main Control Board. It is an all-parallel mode, with the commands and outbound calls connected through wiring. It supports 15 floors for its maximum limit, fitting the needs of vertical transportation within MOT.

Figure 9.18 Parallel Elevator Main Control Board

115


9.5.4.5 Hoisting Sheave A sheave facilitates smooth and safe operation of overhead elevator hoists. The sheave consists of just a pulley with grooves around the circumference. The sheave grips and rotates the hoisting ropes to move. As the traction sheave is connected to an electric motor, the sheave raises the lift and lowers it when the sheave turns another way.

Figure 6.19 Hoisting sheave machine

Figure 6.20 Traction sheave component in the hoisting sheave machine

116


9.5.4.6 Gear Box The hoisting sheave is connected to the gear box. The gear box is a machine in a power transmission system. It consists of the components of gears, gear trains within a box to provide speed and torque in controlling the movement level of the lift through the hoisting motor.

Figure 6.21 Level 15 gear box

9.5.4.7 Overspeed Governor The overspeed governor is mounted on the floor in the machine motor room. It activates the safety system in case the lift car moves too quickly, usually regarding a rapid descent. This type of system is constructed around a governor sheave with another weighted one at the shaft’s bottom. The rope connects to the car, moving upward and downward. When the speed of the car increases, the speed of governor increases. The speed increases proportionally with each other.

117


9.5.5 Lift Shaft The elevator shaft, or hoistway is a vertical passageway in a building which allows the movement of an elevator from one floor to another floor. It consists of several components namely guide rails, safe break, suspension ropes and counterweight. It is constructed with reinforced concrete to accommodate the loading and fire resistance. The size of the elevator shaft space is determined by the number of users.

Figure 6.22 Structure of lift shaft

9.5.5.1 Guide Rails They are parts of the inner workings of the elevator and lift shafts, functioning as the vertical, internal track, keeping the elevator car into a balanced position and directing it in a single direction. These rails operate both as stabilization within the shaft during routine use and as a safety system in case of emergency stops. Traction lifts use two sets of guide rails.

1. Main rails: guide the elevator car 2. Counterweight rails: guide the counterweight

Figure 6.23 Structure of guide rails

118


9.5.5.2 Suspension Rope Suspension rope is attached to the crosshead and extending up into the machine room looping over the sheave on the motor and then down to the counterweight.

Figure 6.24 and Figure 6.25

119


9.5.5.3 Counterweight In traction elevator, a heavy counterweight counterbalances the load of the elevator car, thus, the motor lifts much less the car’s weight. By exerting an opposite force, it provides balance and stability of the mechanical transport system. A counterweight is made up of steel plates stacked on top of each other attached to the opposite ends of the cables to which the car is locked. Composed of a steel frame that can be filled with cast iron fillers above one another, the counterweight weighs about the weight of the car filled to 40 % capacity. When the car is 40% full, the counterweight and the car are perfectly in balance. It travels up and down the shaft, guided by the guide rails bolted in the back wall of the shaft. It functions as a grip to lift’s car, reducing the power of the generator and reducing the brake to stop the car lifts.

Figure 6.26 Indication of guide rails and counterweight

9.5.5.4 Landing Door Landing door is a set of doors that prevent passengers from falling down an open shaft. They can be seen from each floor of the office building of MOT. The lifts have landing doors at every landing the lift stops at. The hoist way door is dependent, (powered by a door operator in the cabin) they are operated to open and close by the electric motors, or manually during emergency situations. The elevator car doors travel along with the hoist way together with the elevator car, but hoist doors are fixed doors in each landing floors.

120


9.5.5.5 Car Buffer Located in the elevator pit, car buffer is a shock absorber system located at the bottom of the lift shaft. It uses a combination of oil and springs to cushion a descending car or counterweight. When the lifts cannot be stopped and hits the bottom of the pit, the bottom car buffer is the last line of defense, prolongs the impact time, dissipates the kinetic energy of the car, reduces the force and the damage to the car and passengers. Overall, it has a quick lead time, small footprints, lightweight, and a wide variety of speed, load capacities and sizes.

9.5.5.6 Elevator Pit A lift pit is the area at the bottom of the hoist way underneath the car. Some of the items that must be included are the buffer springs to catch the car if it falls or overtravel. Traction elevators will have a set of springs under the counterweights as well. An elevator oil buffer is always situated at the middle of the elevation pit.

Figure 6.27 Car buffer within the elevator pit

121


UBBL 1984 Part VII: Fire Requirements Clause 151 Where openings to lift shafts are not connected to protected lobbies, such lift shafts shall be provided with vents of not less than 0.09 square metre lift located at the top of the shaft. Where the vent does not discharge directly to the open air the lift shafts shall be vented to the exterior through a duct of the required FRP as for the lifts shafts. Clause 152 Every openings in a lift shafts are not connected to protected lobbies unless other means of suitable protection to the opening to the satisfaction of the local authority is provided. These requirements shall not be applied to the open type industrial and other special buildings as may be approved by the D.G.F.S. Landing doors should have a FRP of not less than half the FRP of the hoistway structure with a minimum FRP of half hour. No glass shall be used for in landing doors except for vision in which case any vision panel shall be glazed with wired safety glass and shall not be more than 0.0161 square metre and the total area of one of more vision panels in any landing door shall be not more than 0.0156 square metre. Each clear panel opening shall reject a sphere 150 milimetres in diameter. Provision shall be made for the opening of all landing doors by means of an emergency key in respective of the position of the lift car.

In conclusion, MOT meets the UBBL 1984 requirement by installing landing doors in every floor level of the office building for safety purpose. These stainless steel doors implementation caters the requirement whereby no glass material shall be used for landing doors as lift car doors.

122


9.5.6 Lift Car Elevator car is essentially either pulled or pushed up by mechanical means. It is mounted on a platform within an enclosed space called shaft or hoistway. It is known as the compartment which carries people from floor to another floor via a vertical shaft.

Figure 9.28 Structure of lift car

9.5.6.1 Lift Car Frame The frame is used to support the lift car’s cabin located at different positions. Car frame is made up of steel that acquire sufficient strength to withstand the operation of safety gear when fully loaded without permanent deformation.

Figure 9.29 Structure of lift car frame

123


9.5.7 Lift Cabin Elevator cabinets are entirely enclosed by ceiling, walls and floors. The only permissible opening being are the car door, emergency trap door and ventilation apertures.

9.5.7.1 Control System The control system determines the movement of the elevators/lifts. The lifts act as the control system have several components. These can be classified into: 1. INPUT 2. OUTPUT 3. CONTROLLER

9.5.7.2 Sensor (Safety Door Edge) This sensor is a manual trigger sensitive door edges to detect occupants or objects during door closing. This lift door sensor must come in contact of an occupant or an obstruction of any kind to function.

Figure 9.30 Indication of elevator door sensor

124


9.5.7.3 Hall call panel Hall call panels are control panels which call for the elevator car to the level occupants are at. There are 2 hall buttons on each floor, that is, one for up, another for down, except on the highest floor where there is only down button and on the lowest floor where there is only up button. The controller interacts with these buttons by receiving press and release signals signifying the requested direction and floor numbers. It also sends light on/off signals to indicate the status of the buttons

Figure 9.31 Level 2 hall call panel

125


9.5.7.4 Floor request button panel Each lift has the floor request button labelled with the levels of floors in the form of numbers and alphabet buttons, along with the open and close buttons so that occupants in MOT can use it to direct the lift car to the desired floor level. Red light signal is shown later to indicate the pressed button to desired floor level. Emergency bell button: It is located above the floor selection buttons. In case of emergency, a press of this button will produce a sound (bell) to alert people outside the lift shaft that someone is trapped inside the elevator cab due to the malfunction of the lift. Intercom: It is placed next to the alarm. In the lift, it is used to communicate with outside.

Figure 9.32 Floor request button panel inside the lift

In conclusion, the lifts/elevators in Ministry of Transportation (MOT) has an organized arrangement according to the plans in terms of the user accessibility (user friendly). It also fulfils the requirement of UBBL 1984 regulations. Furthermore, every aspects of the lifts are taken into serious considerations in creating a safe, welcome lifts to the users to visit or work in the building. However, the lifts are not disabled-friendly. Besides, closed-circuit television (CCTV) is not installed inside the elevator cabins that may further cause negative impacts. (physical harassment, robbery)

126


10.0 Conclusion

The report is done within a limited time while this report allowed us to communicate among teammates. We can say that everything was done properly by everyone in the group and all of us were giving a very great teamwork towards the project.

We were able to learn every individual topic given in the brief as stated and we were able to understand the use of building services in a building that are needed to be designed in any building. We appreciate what were given to be done in the report because those are the important things to be understood by an Architect and also, the building services are very important elements that allow a building to be functioned properly especially the high-rise buildings. This project has helped us to obtain the first hand look at the application of the theories in the real building.

By stepping out from the classroom towards the real-life project, we learned the things that should be done in the future. The project is not only emphasizing on real-time case study but also providing us the challenge to learn the real-life situations and real-life applications of building services to avoid services failure.

127


11.0 References

Active Fire Protection System Hall, F., & Greeno, R. (2013). Building Services Handbook. Hall, F. (2016). Building services and equipment. Taylor & Francis. Sprinklers - Chief Fire Officers Association. (2018). Retrieved from http://www.cfoa.org.uk/11543 Technical Information | The Fire Protection Company | L. Pugh & Associates. (2018). Retrieved from http://lpugh.com/technical-info/ Fire Control Room - Hendry. (2018). Retrieved from https://www.hendry.com.au/fire-control-room/ Fire Control Room | City of San Diego Official Website. (2018). Retrieved from https://www.sandiego.gov/fire/services/highrise/tour/controlroom Krantz, D. (2018). What is a Fire Alarm System?. Retrieved from https://www.douglaskrantz.com/Blogbasicfirealarm.html Fire Alarm Systems: Firesafe.org.uk. (2018). Retrieved from https://www.firesafe.org.uk/fire-alarms/ CO2 Fire Suppression System | Fire Suppression | Fike. (2018). Retrieved from https://www.fike.com/products/co2-fire-suppression-system/ Automatic Sprinkler Systems. (2018). Retrieved from https://www.protec.co.uk/productpage/sprinklers-and-water-mist/product/product/automatic-sprinkler-systems/ Wet riser - Designing Buildings Wiki. (2018). Retrieved from https://www.designingbuildings.co.uk/wiki/Wet_riser Fire hose reel system. (2018). Retrieved from https://www.grundfos.com/servicesupport/encyclopedia-search/fire-hose-reel-systems.html User, S. (2018). Fire Hose Reel System. Retrieved from https://www.spectrumfire.com/products/firehose-reel-system Ionization Smoke Alarms - AlertAndProtected.com. (2018). Retrieved from http://alertandprotected.com/best-smoke-detectors/ionization-smoke-alarms/

128


Passive Fire Protection System

Green, R. Addressing Passive Fire Protection. Presentation, http://www.fmanz.org/site/facilitiesnz/files/2016%20Summit/Adressing%20Passive%20Fire%20Prote ction_RGreen.pdf Minneapolis Fire Department. (2001). Safety Program and Emergency Procedures for High-Rise Buildings. Minneapolis: Minneapolis Fire Department. Retrieved 11 October 2017 from http://www.ci.minneapolis.mn.us/www/groups/public/@fire/documens Murfitt, D. Compartmentation of buildings – What does it mean? - Fire Safety Services. Fire Safety Services. Retrieved 11 October 2017, from http://www.firesafetyservices.co.uk/compartmentation-of-buildings-what-does-it-mean/ Allyn, J., & Stephen, H. (2013). Integration: HVAC fans and smoke control | Consulting-Specifying Engineer. Csemag.com. Retrieved 11 October 2017, from http://www.csemag.com/single-article/integration-hvac-fans-and-smokecontrol/bb3da27c2bc951c536cd1cae8f38f3b1.html Basement Smoke Ventilation | Lawrence Webster Forrest. Lwf.co.uk. Retrieved 11 October 2017, from http://www.lwf.co.uk/bulletin/basement-smoke-ventilation/ Car Park Ventilation Experts - Fire Design Solutions. Fire Design Solutions. Retrieved 11 October 2017, from http://www.firedesignsolutions.com/fire-safety-systems/car-park-ventilation/ Design and Construction of Firewalls | Fire Protection Engineering Services. (2017). Johnivison.com. Retrieved 11 October 2017, from http://www.johnivison.com/design-and-construction-of-firewalls/

129


Mechanical Ventilation System Platinumac.com.au. (2018). [online] Available at: https://platinumac.com.au/wpcontent/uploads/2015/11/ventilation-2.jpg [Accessed 11 Oct. 2018]. Store.ventilationdirect.com. (2018). [online] Available at: https://store.ventilationdirect.com/content/images/thumbs/0000605_10-wall-canopy-hood-fan-directfired-heated-makeup-air-unit-system.jpeg [Accessed 12 Oct. 2018]. DeTorres, D. (2018). Natural Ventilation vs Mechanical Ventilation. [online] Info.zehnderamerica.com. Available at: http://info.zehnderamerica.com/blog/natural-ventilation-vs-mechanical-ventilation [Accessed 12 Oct. 2018]. Hometips.com. (2018). [online] Available at: https://www.hometips.com/wpcontent/uploads/2012/06/exhaust_ventilation.gif [Accessed 12 Oct. 2018]. Store.ventilationdirect.com. (2018). [online] Available at: https://store.ventilationdirect.com/content/images/thumbs/0000605_10-wall-canopy-hood-fan-directfired-heated-makeup-air-unit-system.jpeg [Accessed 12 Oct. 2018]. Hartzell Propeller. (2018). What’s the Difference Between a Fixed Pitch and Variable Pitch Propeller? Hartzell Propeller. [online] Available at: http://hartzellprop.com/whats-the-difference-between-afixed-pitch-and-variable-pitch-propeller/ [Accessed 12 Oct. 2018]. Twin City Fan and Blower. (2018). Propeller Wall Fans by Twin City Fan and Blower | Heavy Duty | Medium Duty | Light Duty. [online] Available at: https://www.tcf.com/products/propeller-wall-fans/ [Accessed 12 Oct. 2018]. Google.com. (2018). vane axial vs tube axial fan - Google Search. [online] Available at: https://www.google.com/search?biw=1022&bih=885&tbm=isch&sa=1&ei=WSSwWnUIMje9QPN1aqYDA&q=vane+axial+vs+tube+axial+fan&oq=vane+axial+vs+tube+axial+fan&gs_l=i mg.3..0i8i30k1.20756.32310.0.33649.16.15.1.0.0.0.118.692.14j1.15.0....0...1c.1.64.img..1.15.647...0i 8i7i30k1.0.wdaT8xlWX1I#imgrc=JIbZltFhpPGJgM [Accessed 12 Oct. 2018]. Pelonis Technologies, I. (2018). Axial Vs. Centrifugal Fans. [online] Pelonistechnologies.com. Available at: https://www.pelonistechnologies.com/blog/axial-vs.-centrifugal-fans [Accessed 12 Oct. 2018]. Slideshare.net. (2018). Mechanical Ventilation. [online] Available at: https://www.slideshare.net/arkam_slideshare/mechanical-ventilation [Accessed 12 Oct. 2018]. TheFreeDictionary.com. (2018). viscous filter. [online] Available at: https://encyclopedia2.thefreedictionary.com/viscous+filter [Accessed 12 Oct. 2018]. Air Commander. (2018). What Is A Electrostatic Air Filter? How it Works, & How to Clean One • Air Commander. [online] Available at: https://acfilter.com/what-is-electrostatic-air-filter/ [Accessed 12 Oct. 2018]. Google.com. (2018). what is ductwork - Google Search. [online] Available at: https://www.google.com/search?q=what+is+ductwork&source=lnms&tbm=isch&sa=X&ved=0ahUKE wiL8bii5OHdAhWKPo8KHYFtB_UQ_AUIDigB&biw=1022&bih=885#imgdii=sEg_sXG3iJZ32M:&imgrc=o _2osnn_tLLHAM: [Accessed 12 Oct. 2018].

130


Google.com. (2018). what is ductwork - Google Search. [online] Available at: https://www.google.com/search?q=what+is+ductwork&source=lnms&tbm=isch&sa=X&ved=0ahUKE wiL8bii5OHdAhWKPo8KHYFtB_UQ_AUIDigB&biw=1022&bih=885#imgrc=o_2osnn_tLLHAM [Accessed 12 Oct. 2018]. Google.com. (2018). fire damper - Google Search. [online] Available at: https://www.google.com/search?q=fire+damper&source=lnms&tbm=isch&sa=X&ved=0ahUKEwinsv ODmeLdAhUJP48KHdJ4BY0Q_AUIDigB&biw=1022&bih=951#imgrc=ie6y1-TY974pXM [Accessed 12 Oct. 2018]. Google.com. (2018). what is diffuser in hvac - Google Search. [online] Available at: https://www.google.com/search?q=what+is+diffuser+in+hvac&source=lnms&tbm=isch&sa=X&ved= 0ahUKEwig39CQnOLdAhUCNY8KHQyBDWcQ_AUIDigB&biw=1022&bih=885#imgrc=42M_LLjZ1KaxM M: [Accessed 12 Oct. 2018].

131


Air Conditioning System

R. M. (n.d.). AIR CONDITIONING SYSTEMS in Building Services (BLD60903). Retrieved October 08, 2018. Lecture slide and notes R. M. (n.d.). AIR CONDITIONING: Packaged and Plant system in Building Services (BLD60903). Retrieved October 08, 2018. Lecture slide and notes Air conditioner condenser. (n.d.). Retrieved October 10, 2018, from https://www.indiamart.com/proddetail/air-conditioner-condenser-14791407588.html Classic Auto Air Air Conditioner Expansion Valve. (n.d.). Retrieved from https://www.cjponyparts.com/air-conditioner-expansionvalve-1967-1968/p/CAA15102/ Evaporator Coil. (n.d.). Retrieved October 10, 2018, from https://originalair.com/67-68-mustangevaporator-coil-new Function and components of room air conditioner system. (n.d.). Retrieved October 10, 2018, from http://www.daviddarling.info/encyclopedia/A/AE_air_conditioner.html How Air Conditioner Refrigerant Cycle work? (n.d.). Retrieved October 10, 2018, from https://www.greenbuildingadvisor.com/article/air-conditioner-basics How an air conditioner compressor work? (n.d.). Retrieved October 10, 2018, from http://smwac.net/hvac-knowledge/how-an-air-conditioner-compressor-works/ How heat exchangers work. (n.d.). Retrieved October 10, 2018, from https://www.explainthatstuff.com/how-heat-exchangers-work.html Room air conditioner. (n.d.). Retrieved October 10, 2018, from https://www.consumerreports.org/cro/air-conditioners/buying-guide/index.htm Room air conditioner outdoor unit. (n.d.). Retrieved October 10, 2018, from https://appliancestandards.org/product/room-air-conditioners Understanding air conditioning system. (n.d.). Retrieved October 10, 2018, from https://www.slideshare.net/NooruleInieOsman/air-conditioning-system Understanding cooling tower components. (n.d.). Retrieved October 10, 2018, from http://www.worldaircond.com/cooling-tower.html

132


Mechanical Transportation System

Abdullahi, O. (2018). Report on mechanical transportation in Building and Electrical services in Fianl Sub-Circult in Building.docx. [online] Academia.edu. Available at: https://www.academia.edu/31045430/Report_on_mechanical_transportation_in_Building_and_Electri cal_services_in_Fianl_Sub-Circult_in_Building.docx [Accessed 13 Oct. 2018]. Anon, (2018). [online] Available at: https://www.researchgate.net/figure/Basic-components-of-tractionelevators_fig3_270575653 [Accessed 13 Oct. 2018]. Campbell, J. (2018). A Review of 3 Popular Lift Tables: Pneumatic, Hydraulic and Ball Screw. [online] The Material Handling Blog. Available at: https://www.bastiansolutions.com/blog/index.php/2014/07/02/review-3-popular-lift-tables-pneumatichydraulic-ball-screw/ [Accessed 13 Oct. 2018]. Cpgroup.com.au. (2018). Escalators and Travelators: What Are Their Advantages in the Modern World?. [online] Available at: http://www.cpgroup.com.au/escalators-and-travelators-what-are-theiradvantages-in-the-modern-world.php [Accessed 13 Oct. 2018]. Elevator Wiki. (2018). Inside the Elevator Motor Room - 2005 Schindler Traction Elevators. [online] Available at: http://elevation.wikia.com/wiki/File:Inside_the_Elevator_Motor_Room__2005_Schindler_Traction_Elevators [Accessed 11 Oct. 2018]. Emsd.gov.hk. (2018). [online] Available at: https://www.emsd.gov.hk/filemanager/en/content_826/Gdlns_LiftShaftWorks_V3.pdf [Accessed 13 Oct. 2018]. Google.com. (2018). elevator pit - Google Search. [online] Available at: https://www.google.com/search?q=elevator+pit&oq=elevator+pit&aqs=chrome.0.69i59j0l5.5212j0j8&s ourceid=chrome&ie=UTF-8 [Accessed 13 Oct. 2018]. Google.com. (2018). guide rail - Google Search. [online] Available at: https://www.google.com/search?q=guide+rail&source=lnms&tbm=isch&sa=X&ved=0ahUKEwiZzaWN -YPeAhURaI8KHRokAHsQ_AUIDigB&biw=1920&bih=918#imgrc=yGl6VHBXzksNIM: [Accessed 13 Oct. 2018]. Google.com. (2018). lift shaft - Google Search. [online] Available at: https://www.google.com/search?q=lift+shaft&source=lnms&tbm=isch&sa=X&ved=0ahUKEwil0JjeIPeAhUXbo8KHa_LAIUQ_AUIDigB&biw=1920&bih=918#imgrc=ZLHmssQlhmTBQM: [Accessed 13 Oct. 2018]. indiamart.com. (2018). Lift Gearbox. [online] Available at: https://www.indiamart.com/proddetail/liftgearbox-8332297148.html [Accessed 13 Oct. 2018]. Mindat.org. (2018). Definition of hoisting sheave - mindat.org glossary. [online] Available at: https://www.mindat.org/glossary/hoisting_sheave [Accessed 13 Oct. 2018]. New Edge Safety & Security Door. (2018). Security Door | Safety Door Manufacturer - About New Edge Safety Door. [online] Available at: https://www.newedge.com.my/about/ [Accessed 13 Oct. 2018]. Patents.google.com. (2018). US8136636B2 - Elevator hall call system including a programmable adaptable touch screen - Google Patents. [online] Available at: https://patents.google.com/patent/US8136636B2/en [Accessed 13 Oct. 2018]. Platinumac.com.au. (2018). [online] Available at: https://platinumac.com.au/wpcontent/uploads/2015/11/ventilation-2.jpg [Accessed 11 Oct. 2018].

133


Systems, M., Circulation, V., Indicators, E., Indicators, <., Architect Credential Info State: CEU, R., Exam, H., Factors, C., Cuts, W. and Actual, D. (2018). Elevator Controls and Indicators archtoolbox.com. [online] archtoolbox.com. Available at: https://www.archtoolbox.com/materialssystems/vertical-circulation/elevcontrols.html [Accessed 2018]. Systems, M., Circulation, V., Types, E., Types, <., Architect Credential Info State: CEU, R., Exam, H., Factors, C., Cuts, W. and Actual, D. (2018). Elevator Types - archtoolbox.com. [online] archtoolbox.com. Available at: https://www.archtoolbox.com/materials-systems/verticalcirculation/elevatortypes.html [Accessed 10 Oct. 2018]. Twin City Fan and Blower. (2018). Elevator Shaft Exhaust | Twin City Fan and Blower. [online] Available at: https://www.tcf.com/applications/elevator-shaft-exhaust/ [Accessed 13 Oct. 2018].

Other References

Mot.gov.my. (2018). About MOT. [online] Available at: http://www.mot.gov.my/en/about-mot [Accessed 10 Sep. 2018]. Arkitekmaa.com. (2018). Arkitek MAA - Ministry of Transport Head Office. [online] Available at: http://www.arkitekmaa.com/works/architecture/office/ministry-of-transport-head-office [Accessed 10 Sep. 2018].

134


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.