Electrical Engineering and Automation June 2013, Volume2, Issue 2, PP.19-23
Judgment and Treatment of Single-Phase Ground Fault in 35kv System of 330kv Substation Xiaopeng Li, Yanpeng Hou, Zhixiong Chang, Chong Shao Gansu Electric Power Maintenance Company, Jiuquan Gansu, 735000
Abstract Some typical phenomena have been depicted in this paper along with the occurrence of fault in the process of single-phase grounding in 35kV system in two substations of 330kV as example. Then, through the analysis of the principle diagram and fault, the cause of the fault phenomenon has been expounded, and a set of fault finding process and the subsequent processing method that is simple and reliable has been put forward, which can be a reference for the operation and maintenance personnel. Keywords: 330kV Substation; 35kV; Single-Phase Grounding Fault Treatment
330kV 变电站 35kV 系统单相接地故障的诊断及处理 李晓鹏,侯延鹏,畅志雄,邵冲 甘肃省电力公司检修公司酒泉分部,甘肃省 酒泉市 735000 要:本文结合两起 330kV 变电站 35kV 系统的单相接地故障处理过程,叙述了该类型故障发生时伴随的一些典型现象。
摘
然后通过原理图和故障分析,阐明了故障现象出现的原因,并针对性的提出了一套简单可靠的故障查找流程及后续处理 方法,可供运维人员参考。 关键词:330kV 变电站;35kV 侧;单相接地;故障处理
引言 330kV 变电站中的 35kV 系统,为典型不接地系统,具有重要的作用,常连接的有电容器、电抗器、所 用变等设备(如图 1),担负着为系统提供无功补偿、为变电站提供电源等任务。由于是不接地系统,单相 接地故障电流小,并常伴有母线 PT 保险熔断,故障现象比较隐蔽,不易发现和查找,如果该系统发生单相 接地故障,有可能导致 35kV 系统长时间带故障运行,主变低压侧长时间 PT 异常,甚至会发生其他伴生故障。 所以需要在故障发生时快速确定故障点,消除故障,提高设备的运行水平。本文结合两次典型该类型故障的 检查和处理过程,着重探讨并给出了一套简单有效的 35kV 系统单相接地故障的查找步骤和处理方法。
图 1 330kV 变电站 35kV 系统常见接线
- 19 www.ivypub.org/eea