ComecoGTS control devices

Page 1




process indicators Low-cost Programmable Display TI08 ♦ ♦ ♦ ♦ ♦ ♦

Lowest cost 5 DIN cases - up to 1/32 DIN 4-digit bright LED indication Universal linear input Up to 2 alarm relays available with pulsed output Fully programmable parameters

TI08 is a cheap programmable process indicator available in 5 DIN cases and designed for wide range of display applications with/without relay alarm. Equipped with a bright 4-digit LED display, this model is especially suitable for measuring and controlling various technological values from -1999 to 9999 with resolution of up to 6000 points. The device may be equipped with up to 2 programmable relays providing ON/OFF control/alarm with or without pulse mode. TI08 accepts various linear input voltage or current signals. The display limits, decimal point position, measurement offset value as well as many other parameters are fully programmable. Thanks to its excellent price-to-performance ratio, TI08 is an exceptionally widely applicable device.

Technical specifications Input Linear voltage 0...10 V Linear voltage 0...5 V (1) Linear current 0(4)...20 mA Custom linear (option) Two-wire external transmitter Decimal point selection

(programmable) -1999...9999, programmable -1999...9999, programmable -1999...9999, programmable -1999...9999, programmable 4...20 mA (2) programmable (up to 2 relay outputs (3))

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Alarms

5A/250V w/ NO/NC (4) contact 1A/250VAC (5) 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF, pulse mode programmable

Accuracy 0.3% from span 0.02% from span for 1 °C

Measurement error Temperature drift

Operating conditions -10...65 °C 0...85 %RH

Operating temperature Operating humidity

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage External mains transformer (6) Consumption

230 VAC (1) or 115 VAC (1) 90…250 VAC/DC (1) 12…24 VAC/DC or 24 VAC (1) 12…24 VAC/DC 9(12) VAC max. 1.5 VA

Indication and controls Digital display LEDs Keyboard

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals)

4 LED indicators 2 LEDs for output state 2 membrane keys, lockable 'B' 'H' 'S' 'L' 'M' 96x96 96x48 48x48 72x36 48x24 panel panel panel panel panel 90x90 90x42 45x45 71x29 46x22 98 56 98 100 42 14 14 20 10 9 250 150 350 200 30 IP54/20 IP54/20 IP54/20 IP54/20 IP54/20 IP65 IP65 IP65 (7) plastic plastic plastic plastic plastic plug-in plug-in screw screw screw

(1)

Not available for case 'M' Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Only one for case 'M' (4) For case 'S' 2nd relay is NO; for case 'L' both relays are NO; for case 'M' relay is 3A/250VAC with NO contact (5) 0.2A/250VAC for cases 'L' and 'M' (6) Ordered separately (see 'Accessories') (7) Ask for availability! (2)

(3)

TI08 - G0.G1.G5G5 - #1.#2

Code Feature or option

(8)

Code values

G0

Case (front size)

B - 96x96 mm, H - 96x48 mm, S - 48x48 mm, L - 72x36 mm, M - 48x24 mm

G1

Power supply

A - 230 VAC (1), B - 115 VAC (1), C - 90…250 V (1), E - 9(12) VAC w/ external transformer (6), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC (1)

G5

Relay output (3)

X - none, C - relay NO/NC (4), D - SSR, J - for external SSR, M - isolated MOS gate

#1

Increased front protection

X - none, P - IP65 front protection (1,8)

#2

Customer specified input signal

X - none, Z - custom linear signal (specify!)

Not available for case 'S'

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

Ordering code


process indicators Programmable Trip-alarm Unit TI08-R ♦ ♦ ♦ ♦ ♦ ♦ ♦

Low cost 11-pin box for DIN-rail mounting 3-digit bright LED indication Universal linear input Up to 2 alarm relays available with pulsed output Auxiliary output for powering external transmitters Fully programmable parameters

TI08-R is a cheap programmable process indicator for DIN-rail mounting designed for trip-alarm applications. Equipped with a bright 3-digit LED display, this model is especially suitable for measuring and controlling various technological values from -199 to 999 with resolution of up to 1000 points. The device can have up to 2 programmable relays providing on/off control/alarm with or without pulse mode. TI08-R accepts various linear input voltage or current signals from 2- and 3-wire transmitters that can be powered internally via the auxiliary power supply output. The display-to-input correspondence, decimal point position, measurement offset value as well as many other parameters are fully programmable. Thanks to its excellent price-to-performance ratio, TI08-R is an exceptionally widely applicable device.

Technical specifications Input Linear voltage 0...10 V Linear voltage 0...5 V Linear current 0(4)...20 mA Two-wire external transmitter Decimal point selection

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Alarms

(programmable) -199...999, programmable -199...999, programmable -199...999, programmable 4...20 mA (1) programmable (up to 2 relay outputs) 5A/250V w/ NO/NC (2) contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF, pulse mode programmable

Accuracy 0.3% from span 0.02% from span for 1 °C

Measurement error Temperature drift

Operating conditions -10...65 °C 0...85 %RH

Operating temperature Operating humidity (1) (2) (3)

Power supply Mains supply voltage Isolated low voltage Non-isolated low voltage External mains transformer (3) Consumption

230 VAC or 115 VAC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC 9(12) VAC max. 1.5 VA

Indication and controls Digital display LEDs Keyboard

3 LED indicators, 10 mm 2 LEDs for output state 3 membrane keys, lockable

Design and materials Case material Mounting Wiring Dimensions Weight Protection, front/terminals

plastic in socket or on 35 mm DIN rail socket UNDECAL (3) 35x78x91 mm 180 g IP44 / IP20

Provides loop supply voltage - 24 VDC (only w/ isolated power supply) NO for the 2nd relay Ordered separately (see 'Accessories')

Ordering code

TI08 - R.G1.G5G5

Code Feature or option

Code values

Power supply

G5

Relay output

X - none, C - relay NO/NC (2), D - SSR, J - for external SSR, M - isolated MOS gate

COMECO reserves the right of changing specifications without prior notice!

G1

A - 230 VAC, B - 115 VAC, E - 9(12) VAC w/ external transformer (3), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,


process indicators Programmable Process Indicator TC660 ♦ ♦ ♦ ♦ ♦ ♦ ♦

20 mm or 32 mm digit height Universal programmable input 2 programmable alarm outputs Programmable digital filter Calibration and self-calibration Isolated current output RS485 serial interface available

TC660 is a multifunctional programmable process indicator with a 4-digit, 20 mm or 32 mm programmable display that provides excellent visibility in many applications. The device has a universal input for the most common thermoresistances, thermocouples, and linear signals. The input has a built-in automatic software compensation of line resistance and cold junction temperature as well as automatic software compensation of temperature drift, and can be calibrated manually. A programmable input filter and various options for access restriction are available. TC660 can also have up to 2 programmable alarm outputs (2 relays or 1 relay and 1 analog output) and can be equipped with an isolated RS485 serial interface. Input Technical

specifications

Pt100 (w=1.385, 1.391); 3-wire Cu100 (w=1.426, 1.428); 3-wire Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Thermocouple "C" Thermocouple "L - GOST" Linear voltage 0...50 mV (1) Linear current 0...20 mA Linear current 4...20 mA Input type selection Decimal point selection Digital filter Input calibration

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Operation modes Control algorithms Auto-tuning Alarms Other control features Analog output (3) Serial interface

(programmable) -100...600 °C -50...200 °C 0...1000 °C 0...1300 °C 0...1700 °C 0...1700 °C 100...1800 °C 0...2300 °C 0...600 °C -1999...9999, programmable -1999...9999, programmable -1999...9999, programmable (2) programmable programmable programmable programmable (up to 2 outputs) 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA manual and automatic ON/OFF, PID-pulse, and PID for motor valves, programmable programmable programmable BUMPLESS and ANTI-WINDUP 4(0)...20 mA or 0...10 V, isolated RS485, isolated

Accuracy 0.3% (4) from span 0.01% from span for 1 °C automatic software automatic software automatic software

Measurement error Temperature drift Self-calibration Cold junction compensation RTD line compensation

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 5 VA

Indication and controls 4 LED indicators 2 LEDs for output state 3 membrane keys

Digital display LEDs Keyboard

Operating conditions Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring

'H' 96x48 panel 90x42 98 20 400 IP54 / IP20 IP65 plastic plug-in terminals

-10...55 °C 0...85 %RH 'D' (5) 144x72 panel 136x66 92 32 600 IP54 / IP20 plastic plug-in terminals

(1)

Other voltage ranges can be obtained by the means of 2 external resistors. Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Instead of 1st relay! If mounted, it can be programmed as control or retransmission! (4) 0.5% for T/Cs "S", "R", "B", and "C" (5) Ask for availability! (3)

Ordering code

TC660 - G0.G1.G5G5.G9'9".G11 - #1

Code Feature or option

(6)

Code values

G0

Case (front size)

H - 96x48 mm, D - 144x72 mm (5)

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G9'

Serial interface

X - none, B - RS485

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

G11

Analog output (3)

X - none, E - 0…20 mA, F - 4…20 mA, K - 0…10 V

#1

Increased front protection

X - none, P - IP65 front protection (6)

Available ONLY for case 'H'

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(2)


process indicators Programmable Process Indicator TC67U ♦ ♦ ♦ ♦ ♦ ♦ ♦

Low cost Large LED display up to 45 mm high Universal input for 4 RTDs, 6 T/Cs, and 3 linear types 2 alarm relay outputs Software input line and 'cold junction' correction Self-testing and self-calibration RS485 serial interface available

TC67U is designed for wide range of control applications. It is equipped with a large LED display and 2 programmable relay alarm outputs. TC67U has a universal input accepting signals from Pt100, Pt1000, PTC, 6 thermocouple types as well as linear current and voltage signals from external transmitters. This device also has a built-in circuit for self-testing and self-calibration, manual measurement offset setting, and automatic software compensation of line resistance and cold junction temperature. The display-to-input correspondence (in case of linear input), decimal point position, temperature measurement unit, and offset value are also programmable through the convenient keyboard. Thanks to its large display, universal input, serial interface, and excellent price-to-performance ratio, TC67U is exceptionally widely applicable device.

Technical specifications (programmable)

Pt100 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire PTC (1k at 25 °C); 3-wire PTC (2k at 25 °C); 3-wire Thermocouple "T" Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Linear voltage 0...10 V Linear current 0(4)...20 mA Custom linear (option) (3) Two-wire external transmitter Manual input offset Input type selection Decimal point selection Temperature measurement unit

Outputs

-100...850 °C -100...600 °C -50...150 °C -50...150 °C -40...400 °C -20...1000 °C -20...1300 °C (1) 0...1700 °C (1) 0...1700 °C (1) 100...1800 °C (1) -1999...9999 (2), programmable -1999...9999 (2), programmable -1999...9999 (2), programmable 4...20 mA (4) programmable programmable programmable °C or °F, programmable (up to 2 relay outputs)

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Alarms Serial interface

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits programmable RS485, isolated

Accuracy Measurement error Temperature drift Cold junction compensation RTD line compensation

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

3 or 4 LED indicators 2 LEDs for output state 3 membrane keys

Digital display LEDs Keyboard

Operating conditions Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digits Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals) (4)

(2)

(5)

Ordering code

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 2 VA

Indication and controls

(1)

Up to 1000 °C for case 'D3' -199...999 for case 'D3' (3) Instead of linear current

0.3% from span 0.02% from span for 1 °C automatic, -10...80 °C automatic, up to 2 х 25 Ω

(6)

'H' 96x48 panel 90x42 98 4 20 400 IP54/20 IP65 (5) plastic plug-in

'D3' 144x72 panel 136x66 92 3 45 600 IP54/20 plastic plug-in

Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Double front panel sealing! Available ONLY for case 'H'

TC67U - G0.G1.G5G5.G9'9" - #1.#2

Code Feature or option

Code values

G0

Case (front size)

H - 96x48 mm, D3 - 144x72 mm w/ 3-digit display, D4 - 144x72 mm w/ 4-digit display

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G9'

Serial interface

X - none, B - RS485

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

#1

Increased front protection

X - none, P - IP65 front protection (6)

#2

Customer specified input signal

X - none, Z - custom linear signal (specify!) (3)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

-10...65 °C 0...85 %RH 'D4' 144x72 panel 136x66 92 4 32 600 IP54/20 plastic plug-in

COMECO reserves the right of changing specifications without prior notice!

Input


process indicators Programmable Process Indicator TC67U ♦ ♦ ♦ ♦ ♦ ♦ ♦

Low cost Large LED display up to 45 mm high Universal input for 4 RTDs, 6 T/Cs, and 3 linear types 2 alarm relay outputs Software input line and 'cold junction' correction Self-testing and self-calibration RS485 serial interface available

TC67U is designed for wide range of control applications. It is equipped with a large LED display and 2 programmable relay alarm outputs. TC67U has a universal input accepting signals from Pt100, Pt1000, PTC, 6 thermocouple types as well as linear current and voltage signals from external transmitters. This device also has a built-in circuit for self-testing and self-calibration, manual measurement offset setting, and automatic software compensation of line resistance and cold junction temperature. The display-to-input correspondence (in case of linear input), decimal point position, temperature measurement unit, and offset value are also programmable through the convenient keyboard. Thanks to its large display, universal input, serial interface, and excellent price-to-performance ratio, TC67U is exceptionally widely applicable device.

Technical specifications (programmable)

Pt100 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire PTC (1k at 25 °C); 3-wire PTC (2k at 25 °C); 3-wire Thermocouple "T" Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Linear voltage 0...10 V Linear current 0(4)...20 mA Custom linear (option) (3) Two-wire external transmitter Manual input offset Input type selection Decimal point selection Temperature measurement unit

Outputs

-100...850 °C -100...600 °C -50...150 °C -50...150 °C -40...400 °C -20...1000 °C -20...1300 °C (1) 0...1700 °C (1) 0...1700 °C (1) 100...1800 °C (1) -1999...9999 (2), programmable -1999...9999 (2), programmable -1999...9999 (2), programmable 4...20 mA (4) programmable programmable programmable °C or °F, programmable (up to 2 relay outputs)

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Alarms Serial interface

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits programmable RS485, isolated

Accuracy Measurement error Temperature drift Cold junction compensation RTD line compensation

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

3 or 4 LED indicators 2 LEDs for output state 3 membrane keys

Digital display LEDs Keyboard

Operating conditions Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digits Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals) (4)

(2)

(5)

Ordering code

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 2 VA

Indication and controls

(1)

Up to 1000 °C for case 'D3' -199...999 for case 'D3' (3) Instead of linear current

0.3% from span 0.02% from span for 1 °C automatic, -10...80 °C automatic, up to 2 х 25 Ω

(6)

'H' 96x48 panel 90x42 98 4 20 400 IP54/20 IP65 (5) plastic plug-in

'D3' 144x72 panel 136x66 92 3 45 600 IP54/20 plastic plug-in

Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Double front panel sealing! Available ONLY for case 'H'

TC67U - G0.G1.G5G5.G9'9" - #1.#2

Code Feature or option

Code values

G0

Case (front size)

H - 96x48 mm, D3 - 144x72 mm w/ 3-digit display, D4 - 144x72 mm w/ 4-digit display

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G9'

Serial interface

X - none, B - RS485

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

#1

Increased front protection

X - none, P - IP65 front protection (6)

#2

Customer specified input signal

X - none, Z - custom linear signal (specify!) (3)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

-10...65 °C 0...85 %RH 'D4' 144x72 panel 136x66 92 4 32 600 IP54/20 plastic plug-in

COMECO reserves the right of changing specifications without prior notice!

Input


process indicators Programmable Process Indicator TC67U ♦ ♦ ♦ ♦ ♦ ♦ ♦

Low cost Large LED display up to 45 mm high Universal input for 4 RTDs, 6 T/Cs, and 3 linear types 2 alarm relay outputs Software input line and 'cold junction' correction Self-testing and self-calibration RS485 serial interface available

TC67U is designed for wide range of control applications. It is equipped with a large LED display and 2 programmable relay alarm outputs. TC67U has a universal input accepting signals from Pt100, Pt1000, PTC, 6 thermocouple types as well as linear current and voltage signals from external transmitters. This device also has a built-in circuit for self-testing and self-calibration, manual measurement offset setting, and automatic software compensation of line resistance and cold junction temperature. The display-to-input correspondence (in case of linear input), decimal point position, temperature measurement unit, and offset value are also programmable through the convenient keyboard. Thanks to its large display, universal input, serial interface, and excellent price-to-performance ratio, TC67U is exceptionally widely applicable device.

Technical specifications (programmable)

Pt100 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire PTC (1k at 25 °C); 3-wire PTC (2k at 25 °C); 3-wire Thermocouple "T" Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Linear voltage 0...10 V Linear current 0(4)...20 mA Custom linear (option) (3) Two-wire external transmitter Manual input offset Input type selection Decimal point selection Temperature measurement unit

Outputs

-100...850 °C -100...600 °C -50...150 °C -50...150 °C -40...400 °C -20...1000 °C -20...1300 °C (1) 0...1700 °C (1) 0...1700 °C (1) 100...1800 °C (1) -1999...9999 (2), programmable -1999...9999 (2), programmable -1999...9999 (2), programmable 4...20 mA (4) programmable programmable programmable °C or °F, programmable (up to 2 relay outputs)

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Alarms Serial interface

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits programmable RS485, isolated

Accuracy Measurement error Temperature drift Cold junction compensation RTD line compensation

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

3 or 4 LED indicators 2 LEDs for output state 3 membrane keys

Digital display LEDs Keyboard

Operating conditions Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digits Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals) (4)

(2)

(5)

Ordering code

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 2 VA

Indication and controls

(1)

Up to 1000 °C for case 'D3' -199...999 for case 'D3' (3) Instead of linear current

0.3% from span 0.02% from span for 1 °C automatic, -10...80 °C automatic, up to 2 х 25 Ω

(6)

'H' 96x48 panel 90x42 98 4 20 400 IP54/20 IP65 (5) plastic plug-in

'D3' 144x72 panel 136x66 92 3 45 600 IP54/20 plastic plug-in

Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Double front panel sealing! Available ONLY for case 'H'

TC67U - G0.G1.G5G5.G9'9" - #1.#2

Code Feature or option

Code values

G0

Case (front size)

H - 96x48 mm, D3 - 144x72 mm w/ 3-digit display, D4 - 144x72 mm w/ 4-digit display

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G9'

Serial interface

X - none, B - RS485

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

#1

Increased front protection

X - none, P - IP65 front protection (6)

#2

Customer specified input signal

X - none, Z - custom linear signal (specify!) (3)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

-10...65 °C 0...85 %RH 'D4' 144x72 panel 136x66 92 4 32 600 IP54/20 plastic plug-in

COMECO reserves the right of changing specifications without prior notice!

Input


process indicators 8-channel Programmable Indicator TC800 ♦ ♦ ♦ ♦ ♦

8 inputs, 8 outputs, and 16 alarms 2 displays ─ for measured value and for channel number Programmable ranges and alarms Self-testing and system-failure alarm RS485 serial interface available

The TC800 indicator is designed for multi-point control of technological variables. With its compact design, 8 inputs and outputs, TC800 successfully performs all the tasks of indicating, monitoring, and signaling the level of several channels. With the proper programming, any of the channels may be turned into a 2-or 3-state ON/OFF controller and even into a multistage controller. Motorized actuators may be controlled by using 2 relay outputs. The device input accepts thermoresistances, thermocouples, or standard current and voltage signals. Additional discrete inputs are available for remote channel switching and tampering protection. TC800 performs digital compensation for RTD sensor line resistance as well as thermocouple cold-junction compensation, and constantly monitors sensor and sensor-lead state. A rich set of parameters allows programming every aspect of controller operation and an RS485 serial interface allows network operation or connection to operator station.

Technical specifications (2...8 inputs) Pt10…1000 (w=1.385, 1.391) -100(-200)...200(850) °C (1) Cu50, Cu100 (w=1.426, 1.428) -50(0)...200 °C (1) (1) Other RTD min. -200...max. 850 °C Thermocouple "J" 0...800 °C Thermocouple "K" 0...1200 °C Thermocouple "S" 0...1600 °C Thermocouple "R" 0...1600 °C Thermocouple "B" 200...1800 °C Thermocouple "L" 0...1200 °C Thermocouple "L - GOST" 0...600 °C Thermocouple "E" 0...1000 °C Thermocouple "T" 0...400 °C Thermocouple "U" 0...600 °C (1) Other thermocouple min. 0...max. 2400 °C Linear voltage 0...1/ 2/ 5/ 10 V -999...9999, programmable Linear current 0(4)...20 mA -999...9999, programmable (1) Custom linear voltage; max. 40 V min. -999...max. 9999, programmable Custom linear current; max. 50 mA (1) min. -999...max. 9999, programmable

Accuracy

Discrete inputs

Ambient temperature Ambient humidity

Input signal type Input 1 function Input 2 function

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Alarms System-failure alarm Serial interface

(up to 2 inputs) contact, TTL, NPN, or PNP remote channel selection ext. programmed parameter protection (up to 9 relay outputs) (2) 3A/250V w/ NO (3) contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA up to 16, programmable activates SPDT EMR output No 9 RS485, isolated (4)

(1)

Measurement error Temperature drift Cold junction compensation RTD line compensation

0.4% from span 0.005% from span for 1 °C ± 1 °C, automatic software software

Power supply Mains supply voltage SMPS voltage Isolated low voltage Consumption

230 VAC or 115 VAC 90…250 V 12…24 V or 24 VAC max. 4 VA

Indication and controls Channel-number display Measured-value display LEDs Keyboard

2 green LED indicators, 14 mm 4 red LED indicators, 14 mm 8 LEDs for output state and 16 LEDs for alarm state 8 membrane keys

Operating conditions

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals Increased front IP (option)

Custom; specify range within the limits stated. Relay No 9 is for system-failure alarm only (G10)! NO/NC for relay No 1 (4) With ASCII protocol, the outputs may be controlled only through the interface, and with binary protocol – only through the hardware! (2) (3)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

-10...65 °C 0...85 %RH plastic in 90x90 mm panel cut-out plug-in terminals 96x96(front)x107 mm 98 mm max. 650 g IP54 / IP20 IP65

COMECO reserves the right of changing specifications without prior notice!

Analog inputs


process indicators

Ordering code

TC800 - G1.G5─G5.G6'6"─G6'6".G7G7.G9'9".G10 - #1

Code Feature or option

Code values

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, A - relay NO (3), D - SSR, J - for external SSR, M - isolated MOS gate

G6'

Input signal

G6"

Sensor

B - thermoresistance, C - thermocouple, D - linear, Z - other on request RTD

B - Pt50, D - Pt100, F - Pt500, G - Pt1000, H - Cu50, K - Cu100, Z - other (1)

T/C

B - "B", E - "E", J - "J", K - "K", L - "L", M - "L-GOST", S - "S", R - "R", T - "T", U - "U", Z - other (1)

linear

B - 0…20 mA, C - 4…20 mA, H - 0…1 V, I - 0…2 V, J - 0…5 V, K - 0…10 V, Z - other (1)

Discrete input

X - none, A - contact, E - NPN, F - PNP, G - TTL

G9'

Serial interface

X - none, B - RS485

G9"

Protocol

A - ASCII, B - binary, C - ASCII for "PolyMonitor", D - binary for "PolyMonitor"

G10

System alarm

X - none, S - system-failure alarm relay

#1

Increased front protection

X - none, P - IP65 front protection

COMECO reserves the right of changing specifications without prior notice!

G7

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,


process indicators Slim-size Bargraph Indicator TC150 ♦ ♦ ♦ ♦ ♦ ♦ ♦

Low-cost Analog design Current and voltage input signals 24x96 mm DIN-sized front panel 30-dot LED bargraph Moving dot / bar modes available Custom-design bargraph and scale available

TC150 is a slim-sized process indicator for panel mounting with 24x96 mm DIN front size. It accepts linear voltage or current signals at its input and is equipped with a 30-dot vertical LED bargraph, indicating the input value as a percentage of the input range and thereby presenting a convenient 'analog' reading. In combination with a level transmitter, TC150 provides a handy level indication. Moving dot and moving bar modes of the bargraph display as well as custom bargraph design are available. Low priced, TC150 with its useful features and slim front design can be widely applicable for a vast range of industrial solutions.

Technical specifications Input (1)

Power supply

Linear voltage

0…10, 20, 50, or 100 mV, 0…1, 2, 5, or 10 V 0(4)…20 mA min. 0...max. 40 V DC min. 0...max. 100 mA DC

Linear current (2) Custom linear voltage Custom linear current (2)

Accuracy

SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

90…250 VAC/DC 12…24 VAC/DC 12…24 VAC/DC max. 4 VA

Operating conditions Operating temperature Operating humidity

-10...65 °C 0...85 %RH

Design and materials

Resolution Temperature drift

3.33% from span 0.02% from span for 1 °C

Bargraph display Type Scale Mode Color

30 LED dots, 2 mm wide 0…100% or custom design (2) moving dot or moving bar (2) red, green, or yellow

Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals Increased front IP (option)

plastic in 21x93 mm panel cut-out plug-in terminals 24x96(front)x125 mm 120 mm max. 150 g IP54 / IP20 IP65

(1)

Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Specify when ordering! (3) Ask for availability! (2)

Ordering code

TC150 - G1.G2.G6'6" - #1

Code Feature or option

Code values

Power supply

C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated

G2

Bargraph display

D1 - w/ moving dot, D2 - w/ moving bar, Z - custom design (specify!)

G6'6"

Input (1)

DA - 0...5 mA, DB - 0...20 mA, DC - 4...20 mA, DE - 0...10 mV, DF - 0...20 mV, DG - 0...50 mV, DH - 0...1 V, DI - 0...2 V, DJ - 0...5 V, DK - 0...10 V, DZ - other

#1

Increased front protection

X - none, P - IP65 front protection

COMECO reserves the right of changing specifications without prior notice!

G1

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail:

exp


process indicators Programmable Bargraph Display TI250 ♦ ♦ ♦ ♦ ♦ ♦ ♦

Tri-color fully programmable 30-dot LED bargraph 3-digit bright LED indication Universal linear input Up to 2 alarm relays available with pulsed output 48x96 mm DIN-sized front panel Moving dot / bar programmable modes Custom-design bargraph and scale available

TI250 is a versatile and non-expensive combination of TI08 programmable process indicator in 48x96mm DIN case and a fully programmable Tri-color LED bargraph. It is designed for wide range of display applications with/without relay alarm. Equipped with a bright 3-digit LED display, this model is suitable for measuring and controlling various technological values from -199 to 999 with programmable resolution. The device may be also equipped with up to 2 programmable relays providing ON/OFF control/alarm with or without pulse mode. TI250 bargraph display allows user programming of every LED dot color, dot/bar display mode as well as customized scale. Like TI08 the unit accepts various linear input voltage or current signals. Display limits, decimal point position, measurement offset value as well as many other parameters are fully programmable. Thanks to its rich display features and excellent price-to-performance ratio, TI250 can be a very useful and widely applicable device.

Technical specifications Input Linear voltage 0...10 V Linear voltage 0...5 V Linear current 0(4)...20 mA Custom linear (option) Two-wire external transmitter Decimal point selection

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Alarms

(programmable) -199...999, programmable -199...999, programmable -199...999, programmable -199...999, programmable 4...20 mA (1) programmable (up to 2 relay outputs) 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF, pulse mode programmable

Digital display Design Measurement accuracy Resolution Temperature drift

3 LED indicators, 10 mm 0.3% from span programmable 0.02% from span for 1 °C

Bargraph display Design Scale Mode Color (2) (3)

Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage External mains transformer (2) Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC 9(12) VAC max. 3 VA

Indication and controls LEDs Keyboard

2 LEDs for output state 3 membrane keys, lockable

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals Increased front IP (option)

plastic in 42x90 mm panel cut-out plug-in terminals 48x96(front)x107 mm 98 mm max. 300 g IP54 / IP20 IP65

Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Ordered separately (see 'Accessories') Specify when order!

Ordering code

TI250 - G1.G2.G5G5 - #1.#2

Code Feature or option

Code values

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, E - 9(12) VAC w/ external transformer (2), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G2

Bargraph display scale

D - standard (0...100%), Z - custom design (specify!)

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

#1

Increased front protection

X - none, P - IP65 front protection

#2

Customer specified input signal

X - none, Z - custom linear signal (specify!)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(1)

30 LED dots, 2 mm wide 0…100% or custom design (3) programmable: dot or bar programmable: red, green, or yellow

Power supply


process indicators Bargraph Indicator TC66 ♦ ♦ ♦ ♦ ♦ ♦ ♦

Low-cost 4-digit LED display plus 50-dot bargraph Various input signals Well protected from electromagnetic disturbances Moving dot / bar modes available Auxiliary input for display brightness control Custom-design bargraph and scale available

In addition to the digital display, showing the exact value of the measured variable, the TC66 process indicator is equipped with a LED bargraph, indicating the input value as a percentage of the input range and thereby presenting more convenient 'analog' reading. Two variants of the indicator are available: one with a linear, horizontal bargraph ('D') and one with a bargraph in the shape of a 240-degree arc, which provides a visualization resembling that of a traditional pointer-and-dial gauge ('B'). Moving dot and moving bar modes of the bargraph display as well as custom bargraph design are available. Both TC66 variants feature a customized front-panel tag denoting the range and the measurement unit of the monitored physical quantity. The indicator may also be equipped with an auxiliary DC input for display brightness control. The low-priced, low-maintenance TC66 is widely applicable in boat building, power plants, and other industrial areas.

Technical specifications Input

Power supply

Linear voltage 0…10 mV (1) Linear voltage 0…20 mV (1) Linear voltage 0…50 mV (1) Linear voltage 0…100 mV (1) Linear voltage 0…1 V (1) Linear voltage 0…2 V (1) Linear voltage 0…5 V (1) Linear voltage 0…10 V (1) Linear current 0…5 mA (1) Linear current 0(4)…20 mA (1) Custom linear voltage; max. 40 V (1) Custom linear current; max. 50 mA (1) Decimal point position Display range Brightness control (option) (3)

min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) min. -1999...max. 1999 (2) x1, x0.1, x0.01, x0.001 specified by customer min. 0...max. 24 VDC

Accuracy 0.4% from span 0.02% from span for 1 °C

Measurement error Temperature drift

Indication and controls 4 LED indicators 50 LED dots, 0...100%

Digital display Bargraph display (4)

Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 4 VA

Operating conditions -10...65 °C 0...85 %RH

Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Bargraph shape Maximum weight [g] Protection, front/terminals Case material Wiring

'B'

'D'

96x96 panel 90x90 98 10 240° arc 650 IP54 / IP20 plastic plug-in terminals

144x72 panel 136x66 92 14 horizontal bar 650 IP54 / IP20 plastic plug-in terminals

(1)

Specify lower and upper display limits. Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Specify range within the limits stated. (4) Custom display or/and scale design is also available. Ask!

(2)

Ordering code

TC66 - G0.G1.G2.G3.G6'6" - #1

Code Feature or option

Code values

G0

Case (front size)

B - 96x96 mm, D - 144x72 mm

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G2

Bargraph display

D1 - w/ moving dot, D2 - w/ moving bar, Z - custom design (specify!)

G3

Resolution

B - 1, C - 0.1, D - 0.01, E - 0.001

(1)

G6'6"

Input

#1

Auxiliary input

DA - 0...5 mA, DB - 0...20 mA, DC - 4...20 mA, DE - 0...10 mV, DF - 0...20 mV, DG - 0...50 mV, DH - 0...1 V, DI - 0...2 V, DJ - 0...5 V, DK - 0...10 V, DZ - other X - none, BC - input for brightness control mounted (3)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


process indicators Programmable Bargraph Indicator TC600 ♦ ♦ ♦ ♦ ♦ ♦

4-digit LED display plus 50-dot bargraph Various input signals and nonlinearities Programmable ranges and alarms Programmable relay and linear outputs Serial interface available Self-testing and self-calibration

TC600 is a microprocessor-based programmable process indicator with alarm relay outputs. In addition to the digital display, indicating the measured value, the device features a 50-dot LED bar-graph, showing the input value as a percentage of the input range. A changeable front-panel tag indicates the measurement unit. TC600 accepts standard current or voltage signals as well as signals from various thermoresistances and thermocouples. The device software allows programming display range, alarm value and type, and various nonlinear input-to-display transformations. Besides the relay alarm outputs, the indicator may be equipped with a digital interface and an analog retransmission output. The low price and the rich set of functions make TC600 widely applicable in industry and especially in power plants.

Technical specifications Input

Power supply

Pt50…1000 (w=1.385, 1.391) Cu50, Cu100 (w=1.426, 1.428) Other RTD (1) Thermocouple "J" Thermocouple "K" Thermocouple "S" Other thermocouple (1) Linear voltage 0…10 V Linear current 0(4)…20 mA Custom linear voltage; max. 40 V (1) Custom linear current; max. 50 mA (1) Decimal point selection Digital-display range Bargraph range Nonlinear transformation

-99.9(-200)...199.9(800) °C -50.0...199.9 °C min. -200...max. 1000 °C -100...900 °C 0...1200 °C 0...1600 °C min. -200...max. 2400 °C -1999...9999 (2) -1999...9999 (2) min. -1999...max. 9999 (2) min. -1999...max. 9999 (2) programmable programmable programmable up to 6 conversion modules (up to 2 relay and 1 analog) 5A/250V with NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA programmable 4(0)...20 mA or 0...10 V, isolated RS232 or RS485, isolated

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Alarm set point Analog retransmission output Serial interface (3)

Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

Indication and controls Digital display Bargraph display (4) LEDs Keyboard

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Bargraph shape Maximum weight [g] Protection, front/terminals Case material Wiring

0.4% from span 0.01% from span for 1 °C hardware, ± 1 °C

Custom; specify range within the limits stated Provides loop supply voltage - 24 VDC (only w/ isolated power supply)

Ordering code

-10...65 °C 0...85 %RH

Ambient temperature Ambient humidity

(3) (4)

'B'

'D'

96x96 panel 90x90 98 9 240° arc 650 IP54 / IP20 plastic plug-in terminals

144x72 panel 136x66 92 14 horizontal bar 650 IP54 / IP20 plastic plug-in terminals

Ask for availability! Custom display or/and scale design is also available. Ask!

TC600 - G0.G1.G5G5.G6'6".G9'9".G11 - #1

Code Feature or option

Code values

Case (front size)

B - 96x96 mm, D - 144x72 mm

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G6'

Input signal

B - thermoresistance, C - thermocouple, D - linear, Z - other on request

G0

G6"

Sensor

RTD

B - Pt50, D - Pt100, F - Pt500, G - Pt1000, H - Cu50, K - Cu100, Z - other (1)

T/C

J - "J", K - "K", S - "S", Z - other (1)

linear

B - 0…20 mA, C - 4…20 mA, K - 0…10 V, Z - other (1)

G9'

Serial interface

X - none, A - RS232 (3), B - RS485 (3)

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

G11

Analog retransmission output

X - none, E - 0…20 mA, F - 4…20 mA, K - 0…10 V

#1

Nonlinear trans formation

X - none, HC - horizontal cylinder, LC - lying cylindrical tank, SC - standing cylindrical tank, SN - standing conical tank, SP - spherical tank, QR - square root, Z - other

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(1) (2)

4 LED indicators 50 LED dots 2 LEDs for output state 4 membrane keys

Operating conditions

Accuracy Measurement error Temperature drift Cold junction compensation

230 VAC or 115 VAC 90…250 V 12…24 V or 24 VAC 12…24 V max. 5 VA


process indicators Programmable Bargraph Indicator TC600 ♦ ♦ ♦ ♦ ♦ ♦

4-digit LED display plus 50-dot bargraph Various input signals and nonlinearities Programmable ranges and alarms Programmable relay and linear outputs Serial interface available Self-testing and self-calibration

TC600 is a microprocessor-based programmable process indicator with alarm relay outputs. In addition to the digital display, indicating the measured value, the device features a 50-dot LED bar-graph, showing the input value as a percentage of the input range. A changeable front-panel tag indicates the measurement unit. TC600 accepts standard current or voltage signals as well as signals from various thermoresistances and thermocouples. The device software allows programming display range, alarm value and type, and various nonlinear input-to-display transformations. Besides the relay alarm outputs, the indicator may be equipped with a digital interface and an analog retransmission output. The low price and the rich set of functions make TC600 widely applicable in industry and especially in power plants.

Technical specifications Input

Power supply

Pt50…1000 (w=1.385, 1.391) Cu50, Cu100 (w=1.426, 1.428) Other RTD (1) Thermocouple "J" Thermocouple "K" Thermocouple "S" Other thermocouple (1) Linear voltage 0…10 V Linear current 0(4)…20 mA Custom linear voltage; max. 40 V (1) Custom linear current; max. 50 mA (1) Decimal point selection Digital-display range Bargraph range Nonlinear transformation

-99.9(-200)...199.9(800) °C -50.0...199.9 °C min. -200...max. 1000 °C -100...900 °C 0...1200 °C 0...1600 °C min. -200...max. 2400 °C -1999...9999 (2) -1999...9999 (2) min. -1999...max. 9999 (2) min. -1999...max. 9999 (2) programmable programmable programmable up to 6 conversion modules (up to 2 relay and 1 analog) 5A/250V with NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA programmable 4(0)...20 mA or 0...10 V, isolated RS232 or RS485, isolated

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Alarm set point Analog retransmission output Serial interface (3)

Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

Indication and controls Digital display Bargraph display (4) LEDs Keyboard

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Bargraph shape Maximum weight [g] Protection, front/terminals Case material Wiring

0.4% from span 0.01% from span for 1 °C hardware, ± 1 °C

Custom; specify range within the limits stated Provides loop supply voltage - 24 VDC (only w/ isolated power supply)

Ordering code

-10...65 °C 0...85 %RH

Ambient temperature Ambient humidity

(3) (4)

'B'

'D'

96x96 panel 90x90 98 9 240° arc 650 IP54 / IP20 plastic plug-in terminals

144x72 panel 136x66 92 14 horizontal bar 650 IP54 / IP20 plastic plug-in terminals

Ask for availability! Custom display or/and scale design is also available. Ask!

TC600 - G0.G1.G5G5.G6'6".G9'9".G11 - #1

Code Feature or option

Code values

G0

Case (front size)

B - 96x96 mm, D - 144x72 mm

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G6'

Input signal

G6"

Sensor

B - thermoresistance, C - thermocouple, D - linear, Z - other on request RTD

B - Pt50, D - Pt100, F - Pt500, G - Pt1000, H - Cu50, K - Cu100, Z - other (1)

T/C

J - "J", K - "K", S - "S", Z - other (1)

linear

B - 0…20 mA, C - 4…20 mA, K - 0…10 V, Z - other (1)

G9'

Serial interface

X - none, A - RS232 (3), B - RS485 (3)

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

G11

Analog retransmission output

X - none, E - 0…20 mA, F - 4…20 mA, K - 0…10 V

#1

Nonlinear transformation

X - none, HC - horizontal cylinder, LC - lying cylindrical tank, SC - standing cylindrical tank, SN - standing conical tank, SP - spherical tank, QR - square root, Z - other

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

(1) (2)

4 LED indicators 50 LED dots 2 LEDs for output state 4 membrane keys

Operating conditions

Accuracy Measurement error Temperature drift Cold junction compensation

230 VAC or 115 VAC 90…250 V 12…24 V or 24 VAC 12…24 V max. 5 VA


process indicators Loop-powered Indicator TI200 ♦ ♦ ♦ ♦ ♦ ♦ ♦

Panel, in-head, or free mounting IP65 box and Ex housing available 4-digit LCD or LED display Down to 2 mA operating loop current Programmable display ranges and alarms 2 alarm outputs Built-in temperature transmitter available

TI200 is a microprocessor-based programmable process indicator, designed especially to be powered from the input current loop. TI200 is equipped with a fully programmable -1999...9999 LCD or LED display with programmable point position and digital filter as well as with a 2-key (hidden) keyboard. Two alarm limits with programmable parameters – set point, hysteresis, direction, dead time, etc – control 2 alarm outputs (polarized relay type or open collector type, which can be used to control external relays). Five different housing types are available: − plastic case for panel mounting with 96x96 mm DIN front size; − plastic case for panel mounting with 96x48 mm DIN front size; − plastic box with IP65 protection class and 80x80 mm front size; − housing for mounting into sensor protection head type "DW" or "DHW"; − housing for mounting into sensor protection head type "EGW". The IP65-box housing allows a standard in-head transmitter to be incorporated inside the box so TI200 can be used as a temperature or level transmitter with local programmable display. The low price, alarm features, and flexibility make TI200 widely applicable in industry and especially when loop current transmission is measured.

Technical specifications Input

Indication and controls

Input type Operating range Measurement range Display range Display-to-input correspondence Decimal point selection

Outputs Non-isolated transistor gate Polarized relay Control algorithm Alarms

loop supply DC current 3...22 mA 4...20 mA min. -1999...max. 9999 programmable programmable (set of 2 alarm outputs) open collector, 100mA/40V 5A/250V w/ NO contact ON/OFF programmable

Accuracy ± 0.05% from span ± 1 digit within measurement error 0.025% from span for 1 °C

Measurement error Non-linearity Temperature drift

Power supply 4...36 VDC 2...50 mA

Loop supply voltage Loop supply current

4 LCD (plus backlight), 13 mm or 4 LED indicators, 14 mm 2 (hidden) keys

Digital display Keyboard

Operating conditions -10...65 °C 0...85 %RH (1)

Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals)

'B'

'H'

'Y'

'Z1'

'Z2'

96x96 96x48 80x80 ø63 ø73 panel panel free (2) in head (3) in head 90x90 90x42 98 23 60 98 23 200 60 200 300 60 IP65 IP65 IP54/20 IP54/20 IP68 (4) IP65 IP65 plastic plastic plastic aluminum aluminum spring plug-in plug-in screw spring

(1)

0...95 %RH for case 'Y' Radial, axial, and DIN-rail mounting accessories for 80x80x60 mm box can be ordered separately (see 'Accessories') May be mounted in different, separately ordered Ex housings for field applications (see 'Accessories') (4) Ask for availability! (2)

Ordering code

TI200 - G0.G2.G5 - #1.#2.#3

Code Feature or option

Code values

G0

Case

B - for panel mounting, 96x96 mm, H - for panel mounting, 96x48 mm, Y - box IP65, Z1 - for mounting in head type "DW" or "DHW" (3), Z2 - for mounting in head type "EGW" (3)

G2

Display

A - LCD, B - LED, T - LCD + backlight

G5

Relay outputs (set of 2 alarm outputs)

X - none, A - relays NO, E - open collectors NPN, F - open collectors PNP

#1

Increased front protection

X - none, P - IP65 front protection (5)

#2

Temperature transmitter

X - none, TT - built-in temperature transmitter (6)

#3

Mounting kit

X - none, E - kit for mounting in Ex housing (7)

(5)

Not available for cases 'Y', 'Z1', and 'Z2'. Ask for case 'B'! Available ONLY for case 'Y'! Specify exact transmitter type and specifications separately. (7) Only for cases 'Z1' (for mounting in instrument housing EX) and 'Z2' (for mounting in head type "EGW") (6)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


process indicators Loop-powered Indicator TI200 ♦ ♦ ♦ ♦ ♦ ♦ ♦

Panel, in-head, or free mounting IP65 box and Ex housing available 4-digit LCD or LED display Down to 2 mA operating loop current Programmable display ranges and alarms 2 alarm outputs Built-in temperature transmitter available

TI200 is a microprocessor-based programmable process indicator, designed especially to be powered from the input current loop. TI200 is equipped with a fully programmable -1999...9999 LCD or LED display with programmable point position and digital filter as well as with a 2-key (hidden) keyboard. Two alarm limits with programmable parameters – set point, hysteresis, direction, dead time, etc – control 2 alarm outputs (polarized relay type or open collector type, which can be used to control external relays). Five different housing types are available: − plastic case for panel mounting with 96x96 mm DIN front size; − plastic case for panel mounting with 96x48 mm DIN front size; − plastic box with IP65 protection class and 80x80 mm front size; − housing for mounting into sensor protection head type "DW" or "DHW"; − housing for mounting into sensor protection head type "EGW". The IP65-box housing allows a standard in-head transmitter to be incorporated inside the box so TI200 can be used as a temperature or level transmitter with local programmable display. The low price, alarm features, and flexibility make TI200 widely applicable in industry and especially when loop current transmission is measured.

Technical specifications Input

Indication and controls

Input type Operating range Measurement range Display range Display-to-input correspondence Decimal point selection

Outputs Non-isolated transistor gate Polarized relay Control algorithm Alarms

loop supply DC current 3...22 mA 4...20 mA min. -1999...max. 9999 programmable programmable (set of 2 alarm outputs) open collector, 100mA/40V 5A/250V w/ NO contact ON/OFF programmable

Accuracy ± 0.05% from span ± 1 digit within measurement error 0.025% from span for 1 °C

Measurement error Non-linearity Temperature drift

Power supply 4...36 VDC 2...50 mA

Loop supply voltage Loop supply current

4 LCD (plus backlight), 13 mm or 4 LED indicators, 14 mm 2 (hidden) keys

Digital display Keyboard

Operating conditions -10...65 °C 0...85 %RH (1)

Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals)

'B'

'H'

'Y'

'Z1'

'Z2'

96x96 96x48 80x80 ø63 ø73 panel panel free (2) in head (3) in head 90x90 90x42 98 23 60 98 23 200 60 200 300 60 IP65 IP65 IP54/20 IP54/20 IP68 (4) IP65 IP65 plastic plastic plastic aluminum aluminum spring plug-in plug-in screw spring

(1)

0...95 %RH for case 'Y' Radial, axial, and DIN-rail mounting accessories for 80x80x60 mm box can be ordered separately (see 'Accessories') May be mounted in different, separately ordered Ex housings for field applications (see 'Accessories') (4) Ask for availability! (2)

Ordering code

TI200 - G0.G2.G5 - #1.#2.#3

Code Feature or option

Code values

G0

Case

B - for panel mounting, 96x96 mm, H - for panel mounting, 96x48 mm, Y - box IP65, Z1 - for mounting in head type "DW" or "DHW" (3), Z2 - for mounting in head type "EGW" (3)

G2

Display

A - LCD, B - LED, T - LCD + backlight

G5

Relay outputs (set of 2 alarm outputs)

X - none, A - relays NO, E - open collectors NPN, F - open collectors PNP

#1

Increased front protection

X - none, P - IP65 front protection (5)

#2

Temperature transmitter

X - none, TT - built-in temperature transmitter (6)

#3

Mounting kit

X - none, E - kit for mounting in Ex housing (7)

(5)

Not available for cases 'Y', 'Z1', and 'Z2'. Ask for case 'B'! Available ONLY for case 'Y'! Specify exact transmitter type and specifications separately. (7) Only for cases 'Z1' (for mounting in instrument housing EX) and 'Z2' (for mounting in head type "EGW") (6)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


process indicators Loop-powered Indicator TI200 ♦ ♦ ♦ ♦ ♦ ♦ ♦

Panel, in-head, or free mounting IP65 box and Ex housing available 4-digit LCD or LED display Down to 2 mA operating loop current Programmable display ranges and alarms 2 alarm outputs Built-in temperature transmitter available

TI200 is a microprocessor-based programmable process indicator, designed especially to be powered from the input current loop. TI200 is equipped with a fully programmable -1999...9999 LCD or LED display with programmable point position and digital filter as well as with a 2-key (hidden) keyboard. Two alarm limits with programmable parameters – set point, hysteresis, direction, dead time, etc – control 2 alarm outputs (polarized relay type or open collector type, which can be used to control external relays). Five different housing types are available: − plastic case for panel mounting with 96x96 mm DIN front size; − plastic case for panel mounting with 96x48 mm DIN front size; − plastic box with IP65 protection class and 80x80 mm front size; − housing for mounting into sensor protection head type "DW" or "DHW"; − housing for mounting into sensor protection head type "EGW". The IP65-box housing allows a standard in-head transmitter to be incorporated inside the box so TI200 can be used as a temperature or level transmitter with local programmable display. The low price, alarm features, and flexibility make TI200 widely applicable in industry and especially when loop current transmission is measured.

Technical specifications Input

Indication and controls

Input type Operating range Measurement range Display range Display-to-input correspondence Decimal point selection

Outputs Non-isolated transistor gate Polarized relay Control algorithm Alarms

loop supply DC current 3...22 mA 4...20 mA min. -1999...max. 9999 programmable programmable (set of 2 alarm outputs) open collector, 100mA/40V 5A/250V w/ NO contact ON/OFF programmable

Accuracy ± 0.05% from span ± 1 digit within measurement error 0.025% from span for 1 °C

Measurement error Non-linearity Temperature drift

Power supply 4...36 VDC 2...50 mA

Loop supply voltage Loop supply current

4 LCD (plus backlight), 13 mm or 4 LED indicators, 14 mm 2 (hidden) keys

Digital display Keyboard

Operating conditions -10...65 °C 0...85 %RH (1)

Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals)

'B'

'H'

'Y'

'Z1'

'Z2'

96x96 96x48 80x80 ø63 ø73 panel panel free (2) in head (3) in head 90x90 90x42 98 23 60 98 23 200 60 200 300 60 IP65 IP65 IP54/20 IP54/20 IP68 (4) IP65 IP65 plastic plastic plastic aluminum aluminum spring plug-in plug-in screw spring

(1)

0...95 %RH for case 'Y' Radial, axial, and DIN-rail mounting accessories for 80x80x60 mm box can be ordered separately (see 'Accessories') May be mounted in different, separately ordered Ex housings for field applications (see 'Accessories') (4) Ask for availability! (2)

Ordering code

TI200 - G0.G2.G5 - #1.#2.#3

Code Feature or option

Code values

G0

Case

B - for panel mounting, 96x96 mm, H - for panel mounting, 96x48 mm, Y - box IP65, Z1 - for mounting in head type "DW" or "DHW" (3), Z2 - for mounting in head type "EGW" (3)

G2

Display

A - LCD, B - LED, T - LCD + backlight

G5

Relay outputs (set of 2 alarm outputs)

X - none, A - relays NO, E - open collectors NPN, F - open collectors PNP

#1

Increased front protection

X - none, P - IP65 front protection (5)

#2

Temperature transmitter

X - none, TT - built-in temperature transmitter (6)

#3

Mounting kit

X - none, E - kit for mounting in Ex housing (7)

(5)

Not available for cases 'Y', 'Z1', and 'Z2'. Ask for case 'B'! Available ONLY for case 'Y'! Specify exact transmitter type and specifications separately. (7) Only for cases 'Z1' (for mounting in instrument housing EX) and 'Z2' (for mounting in head type "EGW") (6)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


process indicators Battery-Powered Thermometer TIB100 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Operates with TSEC temperature probes Direct in-process mounting All stainless steel design 4-digit 18 mm LCD display Captures minimum and maximum readings Powered by 2 AA batteries 20000 hours average battery life Programmable display ranges and alarms User calibration available Selectable temperature units

COMECO's TIB100 is a digital temperature indicator, designed for direct control over temperature processes when coupled with a TSEC or other compatible temperature probe. This model combines the power supply independence of the bimetallic/gas thermometers and the advantages of the digital temperature measuring instruments. TIB100 is a programmable device and allows current, minimum, and maximum temperature readings, alarm settings, unit selection, and user calibration.

Technical specifications Input

Power supply Pt100 (1), Pt500 (1), Pt1000 min. -50.0...max. 600 °C (min. -58.0...max. 1112.0 °F)

Input (sensor) type Measurement range

Accuracy Display measurement error Non-linearity Hysteresis Repeatability Temperature drift

≤ ± 0.3% of span within measurement error within measurement error within measurement error 0.005% from span for 1 °C

Indication and controls 4-digit LCD, 18 mm 0.1 or 1 °C, programmable on/off, °C/°F/K, min/max, auto off 3 membrane keys through the keyboard 2 programmable alarms on display

Digital display Display resolution Display functions Keyboard Device calibration Alarms

Supply voltage Battery life Battery state control Auto-power-off time

3 V from 2 batteries AA 1.5 V up to 20000 h (2) automatic 0...100 min, programmable

Operating conditions -10...50 °C 0...85 %RH

Ambient temperature Ambient humidity

Design and materials Case material Mounting Probe connection Dimensions Weight Protection class

stainless steel on probe top (3) G3/8", 3/8" NPT, G1/2", 1/2" NPT, M16x1.5, M18x1.5, or welding (4) axial: approx. ø100x50 mm; radial: approx. 100x120x35 mm max. 700 g IP65 (NEMA 4X)

(1)

Ask for availability! Depending on battery type, sensor, and operating mode Order separately! Suitable for assembly are temperature probes type TSEC (see 'Temperature Probes'). (4) Available only when an axial mounted probe is ordered. (2)

(3)

TIB100 - G1.G6'6".G12'12"

Code Feature or option

(5)

Code values

G1

Power supply

X - none (5), G - long-life batteries

G6'6"

Input

BD - Pt100 (1), BF - Pt500 (1), BG - Pt1000

G12'

Probe connection

Q0 - M16x1.5, Q1 - M18x1.5, Q3 - G3/8", Q4 - G1/2", Q9 - 3/8" NPT, Q10 - 1/2" NPT, Uxx - female thread (xx - same as for Qxx), W - welding (4), Z - other (specify!)

G12"

Probe position

A - axial, R - radial underneath, RU - radial on top, RL - radial on the left, RR - radial on the right

The device is supplied without batteries.

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

Ordering code


process controllers Temperature Controller TC48 ♦ ♦ ♦ ♦ ♦ ♦

Low price 48x48 DIN-sized front panel Thermocouple or Pt100 RTD input Independent set-point observation Sensor break indication Panel, DIN-rail, and in-socket mounting

The TC48 temperature controller has no temperature value indication and thus is applicable in cases, in which the low price is one of the major requirements, especially in food industry and household applications. With its 48x48 mm DIN-sized front panel, TC48 is best suited for applications, in which small size is important too. The device works with either an RTD temperature sensor or a thermocouple type "J" or "K" and can be used for controlling various temperature processes and driving electrical actuators by the means of a relay control output and through ON/OFF algorithm. A potentiometer and a dial on the front panel enable easy set-point adjustment, and a red LED – a clear sensor break indication. The controller can be mounted on a panel, on a rail, and in a socket. Inexpensive, compact, and easy-to-use, the TC48 temperature controller is one versatile general-purpose control device.

Technical specifications Input

Indication and controls 0...100 °C, 0...200 °C, 0...400 °C (1) 0...100 °C, 0...200 °C, 0...400 °C, 0...800 °C (1) 0...400 °C, 0...800 °C, 0...1000 °C, 0...1200 °C (1)

Pt100 (w=1.385); 3-wire Thermocouple "J" Thermocouple "K"

LEDs Front-panel potentiometer Front-panel trimmer potentiometer

LED for relay state, LED for sensor break for set-point adjustment for hysteresis adjustment

Output Relay electromechanical Solid state relay (2) MOS gate (2) Output for external SSR Control algorithm Set point

5A/250V w/ NO/NC or NO contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits

Accuracy Measurement error Temperature drift Cold junction compensation

0.5% from span 0.007% from span for 1 °C ± 1 °C

Power supply 230 VAC or 115 VAC 24 VAC max. 3 VA

Mains supply voltage Isolated low voltage (2) Consumption (2) (3)

-10...65 °C 0...85 %RH

Operating temperature Operating humidity

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals

plastic in 45x45 mm panel cut-out or on 35 mm DIN rail socket (3) OCTAL or UNDECAL 48x48(front)x95 mm 103 mm (w/ socket) max. 250 g IP40 / IP20

Specify range when ordering. Ask for availability! Ordered separately (see 'Accessories')

Ordering code

TC48 - G1.G5.G6'6"

Code Feature or option

Code values

G1

Power supply

A - 230 VAC, B - 115 VAC, R - 24 VAC (2)

G5

Relay output

X - none, C - relay NO/NC, D - SSR (2), J - for external SSR, M - isolated MOS gate (2)

G6'6"

Input

(1)

BD - Pt100, CJ - thermocouple "J", CK - thermocouple "K"

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(1)

Operating conditions


process controllers All-purpose Analog Controller TC56 ♦ ♦ ♦ ♦

Very good EMI protection User-friendly controls Analog retransmission output 4-digit LED display

TC56 is an electronic analog controller with very good protection against electromagnetic disturbances, used for automatic control of various processes through relay outputs employing ON/OFF control algorithm. The device can operate with a number of input signal types – thermoresistive, thermoelectrical, or standard signals from relative humidity, pressure, flow, etc. transmitters – at that providing supply for input signal transmitters. In addition to the 2 control or alarm relay outputs, the TC56 controller can be equipped with an analog retransmission output that generates standard signal to external chart recorders, controllers, and indicators.

Technical specifications Input

Accuracy

Pt46 (GOST) Pt50 (w=1.385, 1.391) Pt100 (w=1.385, 1.391) Pt500 (w=1.385) Pt1000 (w=1.385) Cu100 (w=1.426, 1.428) Cu50 (w=1.426, 1.428) Cu53 (GOST) Other RTD (1) Thermocouple "J" Thermocouple "K" Linear voltage 0…1/ 2 / 5/ 10 V Linear current 0…5 mA Linear current 0(4)…20 mA Custom linear voltage; max. 10 V Custom linear current; max. 50 mA

-50...199.9(600) °C -50...199.9(600) °C -50...199.9(600) °C -50...199.9(600) °C -50...199.9(600) °C -50...199.9(200) °C -50...199.9(200) °C -50...199.9(200) °C min. -99...max. 600 °C 0...700 °C 0...700(1200) °C -199.9(1999)...199.9(1999) (2,3) -199.9(1999)...199.9(1999) (2,3) -199.9(1999)...199.9(1999) (2,3) min. -1999...max. 1999 (2,3) min. -1999...max. 1999 (2,3) (up to 3 outputs) 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits 2 control or 1 control and 1 alarm 0(4)...20 mA or 0...10 V none

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Relay function Analog retransmission output Isolation

0.5% from span 0.007% from span for 1 °C automatic hardware, ± 1 °C

Measurement error Temperature drift Cold junction compensation

Power supply 230 VAC or 115 VAC 24 VAC max. 4 VA

Mains supply voltage Isolated low voltage Consumption

Indication and controls Digital display LEDs Multi-turn potentiometer Front-panel trimmer Case-side trimmers

4 LED indicators, 14 mm 2 LEDs for relay-output state for set-point adjustment (4) for hysteresis and dead-band adjustment for alarm-limit adjustment

Operating conditions -10...65 °C 0...85 %RH

Operating temperature Operating humidity

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals

plastic on 90x42 mm panel cut-out plug-in terminals 96x48(front)x107 mm 98 mm max. 400 g IP40 / IP20

(1)

Custom; specify range within the limits stated Specify lower and upper display limits Provides loop supply voltage - 24 VDC (4) Displayed while the set-point button is pressed (2) (3)

TC56 - G1.G3.G5G5.G6'6".G10.G11

Code Feature or option

Code values

G1

Power supply

A - 230 VAC, B - 115 VAC, R - 24 VAC

G3

Resolution

B - 1, C - 0.1

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G6'

Input signal

B - thermoresistance, C - thermocouple, D - linear A - Pt46, B - Pt50, C - Pt50, D - Pt100, E - Pt100, F - Pt500, G - Pt1000, H - Cu50, I - Cu50, J - Cu53, K - Cu100, L - Cu100, Z - other (1)

RTD G6"

Sensor

T/C linear

J - "J", K - "K" (2)

A - 0...5 mA, B - 0...20 mA, C - 4...20 mA, H - 0...1 V, I - 0...2 V, J - 0...5 V, K - 0...10 V, Z - other

G10

Alarm

X - none, A - absolute upper, B - absolute lower, C - absolute mixed, D - relative above set point, E - relative below set point

G11

Analog retransmission output

X - none, E - 0…20 mA, F - 4…20 mA, K - 0…10 V, Z - other

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

Ordering code


process controllers Programmable Controller RT28U ♦ ♦ ♦ ♦ ♦ ♦

Low cost 3-digit bright LED display 4 DIN cases Universal input for 4 RTDs, 6 T/Cs, and 4 linear types Keyboard or encoder adjustment controls RS485 serial interface available

RT28U is designed for wide range of applications. It is equipped with a 3-digit LED display, a universal input for Pt100, Pt1000, PTC, 6 thermocouple types as well as for linear current, voltage, and resistive signals from external transmitters and can have up to 2 programmable relay control/alarm outputs. RT28U can be ordered with either keyboard, or unique rotating encoder for set-point adjustment and programming. All modifications have a built-in circuit for self-testing and self-calibration, manual measurement offset setting, and automatic software compensation of line resistance and cold junction temperature. The display-toinput correspondence (in case of linear input), decimal point position, temperature measurement unit, and offset value are also programmable. Thanks to its universal input, the available various enclosures, serial interface, and excellent price-to-performance ratio, RT28U is an exceptionally widely applicable device.

Technical specifications (programmable)

Pt100 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire PTC (1k at 25 °C); 3-wire PTC (2k at 25 °C); 3-wire Thermocouple "T" Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Linear voltage 0...10 V Linear current 0(4)...20 mA Linear resistive 0...1 kΩ Custom linear (option) (1) Two-wire external transmitter Manual input offset Input type selection Decimal point selection Temperature measurement unit

Outputs

-100...850 °C -100...600 °C -50...150 °C -50...150 °C -40...400 °C -20...999 °C -20...999 °C 0...999 °C 0...999 °C 100...999 °C -199...999, programmable -199...999, programmable -199...999, programmable -199...999, programmable 4...20 mA (2) programmable programmable programmable °C or °F, programmable (up to 2 relay outputs)

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Alarms Serial interface

5A/250V w/ NO/NC or NO (3) contact 1A/250VAC (4) 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits programmable RS485, isolated

(1)

Instead of linear current Provides loop supply voltage - 24 VDC (only w/ isolated power supply). (3) For case 'S' w/ SMPS, 1st relay is NO; for case 'L' and case 'S' w/ serial interface, 2nd relay is NO. (4) 0.2A/250VAC for case 'L' (5) 0.5% for T/Cs "S", "R", and "B" (2)

Ordering code

Accuracy 0.3% (5) from span 0.02% from span for 1 °C automatic, -10...80 °C automatic, up to 2 х 25 Ω

Measurement error Temperature drift Cold junction compensation RTD line compensation

Power supply Mains supply voltage (6) SMPS voltage Isolated low voltage Non-isolated low voltage External mains transformer (7) Consumption

230 VAC or 115 VAC 90…250 V 12…24 V or 24 VAC 12…24 V 9(12) VAC max. 1.5 VA

Indication and controls Digital display LEDs Controls

3 LED indicators 2 LEDs for output state keyboard w/ 3 keys or rotary encoder (8)

Operating conditions Ambient temperature Ambient humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals)

'B' 96x96 panel 90x90 98 20 350 IP54/20 IP65 (9) plastic plug-in

'H' / 'V' 96x48 panel 90x42 98 14 300 IP54/20 IP65 plastic plug-in

-10...65 °C 0...85 %RH 'S' 'L' 48x48 72x36 panel panel 45x45 71x29 56 100 14 10 150 200 IP54/20 IP54/20 IP65 plastic plastic screw screw

(6)

Not available for case 'L'. Ordered separately (see 'Accessories') Available ONLY for cases 'H', 'V', and 'B'. (9) Ask for availability! (10) Not available for case 'S'. (7)

(8)

RT28U - G0.G1.G4.G5G5.G9'9" - #1.#2

Code Feature or option

Code values

G0

Case (front size)

B - 96x96 mm, H - 96x48 mm, V - 48x96 mm, S - 48x48 mm, L - 72x36 mm

G1

Power supply

A - 230 VAC (6), B - 115 VAC (6), C - 90…250 V, E - 9(12) VAC w/ external transformer (7), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G4

Adjustment controls

A - keyboard, H - rotary encoder (8)

G5

Relay output

X - none, A - relay NO (3), C - relay NO/NC (3), D - SSR, J - for external SSR, M - isolated MOS gate

G9'

Serial interface

X - none, B - RS485

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

#1

Increased front protection

X - none, P - IP65 front protection (10)

#2

Customer specified input signal

X - none, Z - custom linear signal (specify!) (1)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Input


process controllers Programmable Controller RT28U-R ♦ ♦ ♦ ♦ ♦

Low cost DIN-rail case and 11-pin box for rail mounting 3-digit bright LED display Universal input for 4 RTDs, 6 T/Cs, and 4 linear types RS485 serial interface available

RT28U-R is a modification of RT28U for rail mounting. It is equipped with a 3-digit LED display, a universal input for Pt100, Pt1000, PTC, 6 thermocouple types as well as for linear current, voltage, and resistive signals from external transmitters and can have up to 2 programmable relay control/alarm outputs. The device has a built-in circuit for self-testing and self-calibration, manual measurement offset setting, and automatic software compensation of line resistance and cold junction temperature. The display-to-input correspondence (in case of linear input), decimal point position, temperature measurement unit, and offset value are also programmable. Thanks to its universal input, serial interface, and excellent price-to-performance ratio, RT28U-R is a widely applicable device.

Technical specifications Input Pt100 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire PTC (1k at 25 °C); 3-wire PTC (2k at 25 °C); 3-wire Thermocouple "T" Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Linear voltage 0...10 V Linear current 0(4)...20 mA Linear resistive 0...1 kΩ Custom linear (option) (1) Two-wire external transmitter Manual input offset Input type selection Decimal point selection Temperature measurement unit

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Alarms Serial interface (4)

(programmable) -100...850 °C -100...600 °C -50...150 °C -50...150 °C -40...400 °C -20...999 °C -20...999 °C 0...999 °C 0...999 °C 100...999 °C -199...999, programmable -199...999, programmable -199...999, programmable -199...999, programmable 4...20 mA (2) programmable programmable programmable °C or °F, programmable (up to 2 relay outputs) 5A/250V w/ NO/NC or NO (3) contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits programmable RS485, isolated

Accuracy 0.3% (5) from span 0.02% from span for 1 °C automatic, -10...80 °C automatic, up to 2 х 25 Ω

Measurement error Temperature drift Cold junction compensation RTD line compensation

Power supply Mains supply voltage Isolated low voltage Non-isolated low voltage External mains transformer (6) Consumption

230 VAC or 115 VAC 12…24 V or 24 VAC 12…24 V 9(12) VAC max. 1.5 VA

Indication and controls 3 LED indicators 2 LEDs for output state 3 membrane keys

Digital display LEDs Keyboard

Operating conditions -10...65 °C 0...85 %RH

Ambient temperature Ambient humidity

Design and materials Dimensions [mm] Mounting Display digit height [mm] Maximum weight [g] Protection, front/terminals Case material Wiring

'R1'

'R2'

70x110x58 on rail 14 300 IP20 plastic screw terminals

35x78x91 in socket or on rail 10 200 IP44 / IP20 plastic socket UNDECAL (6)

(1)

Instead of linear current Provides loop supply voltage - 24 VDC (only w/ isolated power supply). NO/NC for case 'R1'; NO for case 'R2' (4) Not available for case 'R2'. (5) 0.5% for T/Cs "S", "R", and "B" (6) Ordered separately (see 'Accessories') (2)

Ordering code

RT28U - G0.G1.G5G5.G9'9" - #1

Code Feature or option

Code values

G0

Case

R1 - for rail mounting, R2 - 11-pin box

G1

Power supply

A - 230 VAC, B - 115 VAC, E - 9(12) VAC w/ external transformer (6), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, A - relay NO (3), C - relay NO/NC (3), D - SSR, J - for external SSR, M - isolated MOS gate (4)

G9'

Serial interface

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

#1

Customer specified input signal

X - none, Z - custom linear signal (specify!) (1)

X - none, B - RS485

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


process controllers Programmable Controller RT28U-R ♦ ♦ ♦ ♦ ♦

Low cost DIN-rail case and 11-pin box for rail mounting 3-digit bright LED display Universal input for 4 RTDs, 6 T/Cs, and 4 linear types RS485 serial interface available

RT28U-R is a modification of RT28U for rail mounting. It is equipped with a 3-digit LED display, a universal input for Pt100, Pt1000, PTC, 6 thermocouple types as well as for linear current, voltage, and resistive signals from external transmitters and can have up to 2 programmable relay control/alarm outputs. The device has a built-in circuit for self-testing and self-calibration, manual measurement offset setting, and automatic software compensation of line resistance and cold junction temperature. The display-to-input correspondence (in case of linear input), decimal point position, temperature measurement unit, and offset value are also programmable. Thanks to its universal input, serial interface, and excellent price-to-performance ratio, RT28U-R is a widely applicable device.

Technical specifications Input Pt100 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire PTC (1k at 25 °C); 3-wire PTC (2k at 25 °C); 3-wire Thermocouple "T" Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Linear voltage 0...10 V Linear current 0(4)...20 mA Linear resistive 0...1 kΩ Custom linear (option) (1) Two-wire external transmitter Manual input offset Input type selection Decimal point selection Temperature measurement unit

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Alarms Serial interface (4)

(programmable) -100...850 °C -100...600 °C -50...150 °C -50...150 °C -40...400 °C -20...999 °C -20...999 °C 0...999 °C 0...999 °C 100...999 °C -199...999, programmable -199...999, programmable -199...999, programmable -199...999, programmable 4...20 mA (2) programmable programmable programmable °C or °F, programmable (up to 2 relay outputs) 5A/250V w/ NO/NC or NO (3) contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits programmable RS485, isolated

Accuracy 0.3% (5) from span 0.02% from span for 1 °C automatic, -10...80 °C automatic, up to 2 х 25 Ω

Measurement error Temperature drift Cold junction compensation RTD line compensation

Power supply Mains supply voltage Isolated low voltage Non-isolated low voltage External mains transformer (6) Consumption

230 VAC or 115 VAC 12…24 V or 24 VAC 12…24 V 9(12) VAC max. 1.5 VA

Indication and controls 3 LED indicators 2 LEDs for output state 3 membrane keys

Digital display LEDs Keyboard

Operating conditions -10...65 °C 0...85 %RH

Ambient temperature Ambient humidity

Design and materials Dimensions [mm] Mounting Display digit height [mm] Maximum weight [g] Protection, front/terminals Case material Wiring

'R1'

'R2'

70x110x58 on rail 14 300 IP20 plastic screw terminals

35x78x91 in socket or on rail 10 200 IP44 / IP20 plastic socket UNDECAL (6)

(1)

Instead of linear current Provides loop supply voltage - 24 VDC (only w/ isolated power supply). NO/NC for case 'R1'; NO for case 'R2' (4) Not available for case 'R2'. (5) 0.5% for T/Cs "S", "R", and "B" (6) Ordered separately (see 'Accessories') (2)

Ordering code

RT28U - G0.G1.G5G5.G9'9" - #1

Code Feature or option

Code values

G0

Case

R1 - for rail mounting, R2 - 11-pin box

G1

Power supply

A - 230 VAC, B - 115 VAC, E - 9(12) VAC w/ external transformer (6), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, A - relay NO (3), C - relay NO/NC (3), D - SSR, J - for external SSR, M - isolated MOS gate (4)

G9'

Serial interface

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

#1

Customer specified input signal

X - none, Z - custom linear signal (specify!) (1)

X - none, B - RS485

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


process controllers Programmable ON/OFF Controller RT38 ♦ ♦ ♦ ♦ ♦ ♦

Low cost 5 DIN cases - up to 1/32 DIN Low power consumption Semi-universal input Various power supplies Fully programmable parameters

The cheap programmable controller RT38 is designed for wide range of ON/OFF control applications. Equipped with a 3-digit LED display, RT38 is especially suitable for measuring and controlling various technological values with resolution of up to 1000 points. It can be ordered in various cases including the smallest 1/32 DIN case, and for different power supplies. The device has 1 programmable relay control/alarm output and is available in 2 universal-input versions: RTD - for 7 selectable Ptx and 4 Cux sensor types, and T/C - for 3 selectable thermocouples as well as versions for linear current and voltage signals. RT38 allows an automatic software compensation of line resistance and cold junction temperature. The display-to-input correspondence (in case of linear input), the decimal point position, the temperature measuring unit as well as the offset value are also programmable. Thanks to its power supply options, semi-universal input, and excellent price-to-performance ratio, RT38 is an exceptionally widely applicable device.

Technical specifications RTD, DIN (w=1.385); 3-wire RTD, GOST (w=1.391); 3-wire RTD measurement range Thermocouple "T" Thermocouple "J" Thermocouple "K" Linear voltage 0...10 V Linear current 0(4)...20 mA Two-wire external transmitter RTD or T/C type selection Decimal point selection Temperature measurement unit

(programmable) Pt50, Pt100, Pt500, Pt1000 Pt46, Pt50, Pt100, Cu50, Cu100 -100...600 °C -40...400 °C -20...999 °C -20...999 °C -199...999, programmable -199...999, programmable 4...20 mA (1) programmable programmable °C or °F, programmable

Output Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Alarms

5A/250V w/ NO/NC (2) contact 1A/250VAC (3) 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits programmable

Accuracy Measurement error Temperature drift Cold junction compensation RTD line compensation

0.3% from span 0.02% from span for 1 °C automatic, -10...80 °C automatic, up to 2 х 25 Ω

Power supply

Indication and controls

Operating conditions Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals) (5)

(2)

(6)

Ordering code

3 LED indicators LED for output state 2 or 3 membrane keys, lockable

Digital display LEDs Keyboard

(1)

Provides loop supply voltage - 24 VDC (only w/ isolated power supply) NO for case 'M' (3) 0.2A/250VAC for case 'M' (4) Not available for case 'M'

230 VAC (4) or 115 VAC (4) 90…250 VAC/DC (5) 12…24 VAC/DC or 24 VAC (4) 12…24 VAC/DC 9(12) VAC max. 1.5 VA

Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage External mains transformer (6) Consumption

'B'

'H' / 'V'

'S'

-10...65 °C 0...85 %RH 'L' 'M'

96x96 96x48 48x48 72x36 48x24 panel panel panel panel panel 90x90 90x42 45x45 71x29 46x22 98 56 98 100 42 14 14 20 10 9 250 150 300 200 30 IP54/20 IP54/20 IP54/20 IP54/20 IP54/20 IP65 IP65 IP65 (7) plastic plastic plastic plastic plastic plug-in plug-in screw screw screw

Not available for cases 'L' and 'M' Ordered separately (see 'Accessories') Ask for availability! (8) Not available for cases 'S' and 'M' (7)

RT38 - G0.G1.G5.G6 - #1

Code Feature or option

Code values

G0

Case (front size)

B - 96x96 mm, H - 96x48 mm, V - 48x96 mm, S - 48x48 mm, L - 72x36 mm, M - 48x24 mm

G1

Power supply

A - 230 VAC (4), B - 115 VAC (4), C - 90…250 V (5), E - 9(12) VAC w/ external transformer (6), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC (4)

G5

Relay output

X - none, C - relay NO/NC (2), D - SSR, J - for external SSR, M - isolated MOS gate

G6

Input

B - RTD (programmable), C - thermocouple (programmable), D - 0(4)…20 mA, DK - 0…10 V

#1

Increased front protection

X - none, P - IP65 front protection (8)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

Input


process controllers Programmable ON/OFF Controller RT38-R ♦ ♦ ♦ ♦ ♦ ♦

Low cost 11-pin box for DIN-rail mounting 3-digit bright LED display Semi-universal input Various power supplies Fully programmable parameters

Technical specifications Input RTD, DIN (w=1.385); 3-wire RTD, GOST (w=1.391); 3-wire RTD measurement range Thermocouple "T" Thermocouple "J" Thermocouple "K" Linear voltage 0...10 V Linear current 0(4)...20 mA Two-wire external transmitter RTD or T/C type selection Decimal point selection Temperature measurement unit

(programmable) Pt50, Pt100, Pt500, Pt1000 Pt46, Pt50, Pt100, Cu50, Cu100 -100...600 °C -40...400 °C -20...999 °C -20...999 °C -199...999, programmable -199...999, programmable 4...20 mA (1) programmable programmable °C or °F, programmable

Output 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits programmable

Accuracy 0.3% from span 0.02% from span for 1 °C

Measurement error Temperature drift (2)

Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage External mains transformer (2) Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC 9(12) VAC max. 1.5 VA

Indication and controls Digital display LEDs Keyboard

3 LED indicators, 10 mm LED for output state 3 membrane keys, lockable

Operating conditions

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Alarms

(1)

Power supply

-10...65 °C 0...85 %RH

Operating temperature Operating humidity

Design and materials Case material Mounting Wiring Dimensions Weight Protection, front/terminals

plastic in socket or on 35 mm DIN rail socket UNDECAL (2) 35x78x91 mm 180 g IP44 / IP20

Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Ordered separately (see 'Accessories')

Ordering code

RT38 - R.G1.G5.G6

Code Feature or option

Code values

Power supply

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G6

Input

B - RTD (programmable), C - thermocouple (programmable), D - 0(4)…20 mA, DK - 0…10 V

COMECO reserves the right of changing specifications without prior notice!

G1

A - 230 VAC, B - 115 VAC, C - 90…250 V, E - 9(12) VAC w/ external transformer (2), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,


process controllers Programmable Controller RT18 ♦ ♦ ♦ ♦ ♦

Self-tuning ON/OFF or PI control algorithm 4 DIN cases - up to 1/16 DIN Fixed input Various power supplies Easy programming

RT18 is a programmable temperature ON/OFF controller with fixed input for various temperature sensors and linear signals. It is equipped with 3-digit LED display and relay control output. For easy mounting in existing cutouts, RT18 is available with 48x48, 96x48, 48x96, and 96x96 mm front sizes. To control its output, the device may utilize either ON/OFF or PI auto-tune control algorithm, the latter being a convenient solution that saves installation time and costs and provides precise control. The reliable operation in noisy industrial environment also extends RT18 application area.

Technical specifications Input

(total number of points for any range: 999)

Pt50 (w=1.385); 3-wire Pt100 (w=1.385); 3-wire Pt500 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire Cu100; 3-wire Cu50; 3-wire Other RTD (1) Thermocouple "J" Thermocouple "K" Thermocouple "L" Thermocouple "L-GOST" Other thermocouple (1) Linear voltage 0...10 V Linear current 0(4)...20 mA Custom linear voltage; max. 40 V Custom linear current; max. 80 mA

-9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(200) °C -9.9(-50)...90.0(200) °C min. -99...max. 500 °C 0...999(600) °C (2) (2) 0...999(850) °C 0...900(600) °C (2) 0...650(550) °C (2) min. -99(0)...max. 900(999) °C (2) -99...900 (0...999) (2,3,4) (2,3,4) -99...900 (0...999) min. -99...max. 999 (2,3,4) min. -99...max. 999 (2,3,4)

Accuracy Measurement error Temperature drift Cold junction compensation RTD line compensation (option)

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

Operating conditions Operating temperature Operating humidity

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Programmable parameters

Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals)

(1)

(4)

(2)

(5)

Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Ask for availability!

Code values

G0

Case (front size)

B - 96x96 mm, H - 96x48 mm, V - 48x96 mm, S - 48x48 mm

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G3

Resolution

B - 1, C - 0.1 (2)

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G6'

Input signal

G6"

(7)

'H' 96x48 panel 90x42 98 14 300 IP54/20 IP65 plastic plug-in

RT18 - G0.G1.G3.G5.G6'6".G8 - #1.#2

Code Feature or option

(6)

'B' 96x96 panel 90x90 98 20 350 IP54/20 (5) IP65 plastic plug-in

-10...65 °C 0...85 %RH 'V' 'S' 48x96 48x48 panel panel 42x90 45x45 98 100 14 10 300 200 IP54/20 IP54/20 IP65 plastic plastic plug-in screw

Sensor

B - thermoresistance, C - thermocouple, D - linear, Z - other on request RTD

B - Pt50, D - Pt100, F - Pt500, G - Pt1000, H - Cu50, K - Cu100, Z - other (1)

T/C

J - "J", K - "K", L - "L" , M - "L-GOST", Z - other (1)

linear

B - 0…20 mA (3), C - 4…20 mA (3), K - 0…10 V (3), Z - other (3) (6)

G8

Control algorithm

A - ON/OFF, C - self-tuning PI

#1

Compensation for 3-wire RTD line

X - none, LC - built-in line resistance compensation

#2

Increased front protection

X - none, P - IP65 front protection (7)

Specify the direction of control action (heating or cooling relay action). Not available for case 'S'!

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Ordering code

3 LED indicators LED for output state 3 membrane keys

Digital display LEDs Keyboard

Design and materials

Custom; specify range within the limits stated. For self-tuning PI algorithm, ONLY the alternative ranges are applicable. (3) Specify lower and upper display limits.

230 VAC or 115 VAC 90...250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 3 VA

Indication and controls

Output 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF, self-tuning PI within input range limits according to control algorithm

0.4% from span 0.005% from span for 1 °C ± 1 °C 0.01% from span for 1 Ω


process controllers Programmable Controller RT28 ♦ ♦ ♦ ♦ ♦ ♦

2 output relays ON/OFF or PD-for-MV control algorithm 3 DIN cases Fixed input Various power supplies Easy programming

The simple-design low-cost microprocessor-based controller RT28 combines the advantages of the microprocessor devices with the high reliability of analog controllers. It is available with 96x48, 48x96, and 96x96 mm DIN-sized front panel and can be equipped with up to 2 control relays. To control its outputs, RT28 may utilize either ON/OFF (heat/cool) duplex or PD control algorithm. The ON/OFF control algorithm allows flexible programming of the action of each relay for solving variety of problems. The PD algorithm results in PI control when used to control motorized valve actuators without position feedback. The reliable operation even in the presence of electromagnetic disturbances and the attractive price also account for the success of the RT28 controller.

Technical specifications (total number of points for any range: 999) -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(200) °C -9.9(-50)...90.0(200) °C min. -99...max. 500 °C 0...999(600) °C 0...999(850) °C 0...900(600) °C 0...650(550) °C min. -99(0)...max. 900(999) °C -99...900 (0...999) (2,3) -99...900 (0...999) (2,3) min. -99...max. 999 (2,3) min. -99...max. 999 (2,3)

Pt50 (w=1.385); 3-wire Pt100 (w=1.385); 3-wire Pt500 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire Cu100; 3-wire Cu50; 3-wire Other RTD (1) Thermocouple "J" Thermocouple "K" Thermocouple "L" Thermocouple "L-GOST" Other thermocouple (1) Linear voltage 0...10 V Linear current 0(4)...20 mA Custom linear voltage; max. 40 V Custom linear current; max. 80 mA

Outputs

(up to 2 relay outputs)

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Programmable parameters

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF, PD within input range limits according to control algorithm

Accuracy

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

3 LED indicators 2 LED for output state 3 membrane keys

Digital display LEDs Keyboard

Operating conditions Ambient temperature Ambient humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals) (4)

(2)

(5)

Ordering code

230 VAC or 115 VAC 90...250 V 12…24 V or 24 VAC 12…24 V max. 3 VA

Indication and controls

(1)

Custom; specify range within the limits stated. Specify lower and upper display limits. (3) Provides loop supply voltage - 24 VDC (only w/ isolated power supply)

0.4% from span 0.005% from span for 1 °C ± 1 °C 0.01% from span for 1 Ω

Measurement error Temperature drift Cold junction compensation RTD line compensation (option)

'B' 'H' 96x96 96x48 panel panel 90x42 90x90 98 98 14 20 300 350 IP54 / IP20 IP54 / IP20 IP65 IP65 (4) plastic plastic plug-in plug-in

-10...65 °C 0...85 %RH 'V' 48x96 panel 42x90 98 14 300 IP54 / IP20 IP65 plastic plug-in

Ask for availability! Ordered separately (see 'Accessories')

RT28 - G0.G1.G3.G5G5.G6'6".G8 - #1.#2

Code Feature or option

Code values

G0

Case (front size)

B - 96x96 mm, H - 96x48 mm, V - 48x96 mm

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G3

Resolution

B - 1, C - 0.1

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G6'

Input signal

G6"

Sensor

B - thermoresistance, C - thermocouple, D - linear, Z - other on request RTD

B - Pt50, D - Pt100, F - Pt500, G - Pt1000, H - Cu50, K - Cu100, Z - other (1)

T/C

J - "J", K - "K", L - "L" , M - "L-GOST", Z - other (1)

linear

B - 0…20 mA (2), C - 4…20 mA (2), K - 0…10 V (2), Z - other (2)

G8

Control algorithm

A - ON/OFF, D - PD

#1

Compensation for 3-wire RTD line

X - none, LC - built-in line resistance compensation

#2

Increased front protection

X - none, P - IP65 front protection

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Input


process controllers Programmable Controller RT284U ♦ ♦ ♦ ♦ ♦ ♦

Low cost 4-digit bright LED display 5 DIN cases Universal input for 4 RTDs, 6 T/Cs, and 4 linear types Keyboard or encoder adjustment controls RS485 serial interface available

RT284U is designed for wide range of applications. It is equipped with a 4-digit LED display, a universal input for Pt100, Pt1000, PTC, 6 thermocouple types as well as for linear current, voltage, and resistive signals from external transmitters and can have up to 2 programmable relay control/alarm outputs. RT284U can be ordered with either keyboard or unique rotating encoder for set-point adjustment and programming. All modifications have a built-in circuit for self-testing and self-calibration, manual measurement offset setting, and automatic software compensation of line resistance and cold junction temperature. The display-to-input correspondence (in case of linear input), decimal point position, temperature measurement unit, and offset value are also programmable. Thanks to its universal input, the available various enclosures and serial interface as well as excellent price-to-performance ratio, RT284U is an exceptionally widely applicable device.

Technical specifications Accuracy

(programmable)

Pt100 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire PTC (1k at 25 °C); 3-wire PTC (2k at 25 °C); 3-wire Thermocouple "T" Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Linear voltage 0...10 V Linear current 0(4)...20 mA Linear resistive 0...1 kΩ Custom linear (option) (1) Two-wire external transmitter Manual input offset Input type selection Decimal point selection Temperature measurement unit

Outputs

Power supply Mains supply voltage (6) SMPS voltage Isolated low voltage Non-isolated low voltage External mains transformer (7) Consumption

Operating conditions Ambient temperature Ambient humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals)

(1)

(6)

(2)

(7)

Ordering code

4 LED indicators 2 LEDs for output state keyboard w/ 3 keys or rotary encoder (8)

Digital display LEDs Controls

5A/250V w/ NO/NC or NO (3) contact 1A/250VAC (4) 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits programmable RS485, isolated

Instead of linear current Provides loop supply voltage - 24 VDC (only w/ isolated power supply). (3) For case 'Q' and case 'S' w/ SMPS, 1st relay is NO; for case 'L', case 'Q' w/ SMPS, and case 'S' w/ serial interface, 2nd relay is NO. (4) 0.2A/250VAC for case 'L' (5) 0.5% for T/Cs "S", "R", and "B"

230 VAC or 115 VAC 90…250 V 12…24 V or 24 VAC 12…24 V 9(12) VAC max. 2 VA

Indication and controls

(up to 2 relay outputs)

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Alarms Serial interface

0.3% (5) from span 0.02% from span for 1 °C automatic, -10...80 °C automatic, up to 2 х 25 Ω

Measurement error Temperature drift Cold junction compensation RTD line compensation

-100...850 °C -100...600 °C -50...150 °C -50...150 °C -40...400 °C -20...1000 °C -20...1300 °C 0...1700 °C 0...1700 °C 100...1800 °C -1999...9999, programmable -1999...9999, programmable -1999...9999, programmable -1999...9999, programmable 4...20 mA (2) programmable programmable programmable °C or °F, programmable

'B' 'H' / 'V' 'Q' 96x96 96x48 72x72 panel panel panel 90x90 90x42 67x67 98 98 66 14 20 14 300 350 300 IP54/20 IP54/20 IP54/20 IP65 IP65 (9) plastic plastic plastic plug-in plug-in screw

-10...65 °C 0...85 %RH 'S' 'L' 48x48 72x36 panel panel 45x45 71x29 100 56 10 9 200 150 IP54/20 IP54/20 IP65 plastic plastic screw screw

Not available for case 'L'. Ordered separately (see 'Accessories') Available ONLY for cases 'H', 'V', and 'B'. (9) Ask for availability! (10) Not available for cases 'Q' and 'S'. (8)

RT284U - G0.G1.G4.G5G5.G9'9" - #1.#2

Code Feature or option

Code values

G0

Case (front size)

B - 96x96 mm, H - 96x48 mm, V - 48x96 mm, Q - 72x72 mm, S - 48x48 mm, L - 72x36 mm

G1

Power supply

A - 230 VAC (6), B - 115 VAC (6), C - 90…250 V, E - 9(12) VAC w/ external transformer (7), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G4

Adjustment controls

A - keyboard, H - rotary encoder (8)

G5

Relay output

X - none, A - relay NO (3), C - relay NO/NC (3), D - SSR, J - for external SSR, M - isolated MOS gate

G9'

Serial interface

X - none, B - RS485

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

#1

Increased front protection

X - none, P - IP65 front protection (10)

#2

Customer specified input signal

X - none, Z - custom linear signal (specify!) (1)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Input


process controllers Programmable Controller RT384 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

5 DIN cases Universal programmable input Various control algorithms including auto-tuning PID-pulse and PID for motor valves Programmable digital filter Manual mode for bumpless switching Calibration and self-calibration RS485 serial interface available

RT384 is a multifunctional programmable controller with universal input for the most common thermoresistances, thermocouples, and linear signals. The input has a built-in automatic software compensation of line resistance and cold junction temperature as well as automatic software compensation of temperature drift, and can be calibrated manually. RT384 is also equipped with a programmable input filter and a 4-digit display with programmable refresh rate. Available are various options for access restriction. The device can have up to 2 outputs (2 relays or 1 relay and 1 analog output), which can control variety of actuators through different programmable control algorithms. RT384 can work in manual or automatic mode, and an RS485 serial interface enables networking.

Technical specifications (programmable)

Pt100 (w=1.385, 1.391); 3-wire Cu100 (w=1.426, 1.428); 3-wire Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Thermocouple "C" Thermocouple "L - GOST" Linear voltage 0...50 mV (1) Linear current 0...20 mA Linear current 4...20 mA Input type selection Decimal point selection Digital filter Input calibration

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Operation modes Control algorithms Auto-tuning Alarms Other control features Analog output (5) Serial interface

-100...600 °C -50...200 °C 0...1000 °C 0...1300 °C 0...1700 °C 0...1700 °C 100...1800 °C 0...2300 °C 0...600 °C -1999...9999, programmable -1999...9999, programmable -1999...9999, programmable (2) programmable programmable programmable programmable (up to 2 outputs) 5A/250V w/ NO/NC or NO (3) contact 1A/250VAC (4) 0.1A/60V, optically isolated 5…24 V, 30 mA manual and automatic ON/OFF, PID-pulse, and PID for motor valves, programmable programmable programmable BUMPLESS and ANTI-WINDUP 4(0)...20 mA or 0...10 V, isolated RS485, isolated

(1)

Other voltage ranges can be obtained by the means of 2 external resistors. Provides loop supply voltage - 24 VDC (only w/ isolated power supply). (3) For case 'Q' and case 'S' w/ serial interface, 1st relay is NO; for cases 'Q' and 'S' w/ SMPS, 2nd relay is NO. (4) 0.2A/250VAC for case 'L' (2)

Ordering code

Accuracy 0.3% (6) from span 0.01% from span for 1 °C automatic software automatic software automatic software

Measurement error Temperature drift Self-calibration Cold junction compensation RTD line compensation

Power supply Mains supply voltage (7) SMPS voltage (7) Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 90…250 V 12…24 V or 24 VAC (7) 12…24 V max. 3 VA

Indication and controls 4 LED indicators 2 LEDs for output state 3 membrane keys

Digital display LEDs Keyboard

Operating conditions Ambient temperature Ambient humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals)

'B' 'H' / 'V' 'Q' 96x96 96x48 72x72 panel panel panel 90x90 90x42 67x67 98 98 66 20 14 / 10 14 300 350 300 IP54/20 IP54/20 IP54/20 IP65 IP65 (8) plastic plastic plastic plug-in plug-in screw

-10...55 °C 0...85 %RH 'S' 'L' 48x48 72x36 panel panel 45x45 71x29 100 56 10 9 200 150 IP54/20 IP54/20 IP65 plastic plastic screw screw

(5)

Instead of 1st relay! If mounted, it can be programmed as control or retransmission! 0.5% for noble thermocouples (7) Not available for case 'L'. (8) Ask for availability! (9) Not available for cases 'Q' and 'S'. (6)

RT384 - G0.G1.G5G5.G9'9".G11 - #1

Code Feature or option

Code values

G0

Case (front size)

B - 96x96 mm, H - 96x48 mm, V - 48x96 mm, Q - 72x72 mm, S - 48x48 mm, L - 72x36 mm

G1

Power supply

A - 230 VAC (7), B - 115 VAC (7), C - 90…250 V (7), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC (7)

G5

Relay output

X - none, A - relay NO (3), C - relay NO/NC (3), D - SSR, J - for external SSR, M - isolated MOS gate

G9'

Serial interface

X - none, B - RS485

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

G11

Analog output (5,8)

X - none, E - 0…20 mA, F - 4…20 mA, K - 0…10 V

#1

Increased front protection

X - none, P - IP65 front protection (9)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Input


process controllers Programmable Controller RT484 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Two 4-digit displays 4 DIN cases Universal programmable input Various control algorithms including auto-tuning PID-pulse and PID for motor valves Programmable digital filter Manual mode for bumpless switching Calibration and self-calibration RS485 serial interface available

RT484 is a multifunctional programmable controller with a universal input for the most common thermoresistances, thermocouples, and linear signals. The input has a built-in automatic software compensation of line resistance and cold junction temperature as well as automatic software compensation of temperature drift, and can be calibrated manually. RT484 is also equipped with a programmable input filter and two 4-digit displays with programmable refresh rate. Available are various options for access restriction. The device can have up to 2 outputs (2 relays or 1 relay and 1 analog output), which can control variety of actuators through different programmable control algorithms. RT484 can work in manual or automatic mode, and an RS485 serial interface enables networking.

Technical specifications (programmable)

Pt100 (w=1.385, 1.391); 3-wire Cu100 (w=1.426, 1.428); 3-wire Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Thermocouple "C" Thermocouple "L - GOST" Linear voltage 0...50 mV (1) Linear current 0...20 mA Linear current 4...20 mA Input type selection Decimal point selection Digital filter Input calibration

Outputs

-100...600 °C -50...200 °C 0...1000 °C 0...1300 °C 0...1700 °C 0...1700 °C 100...1800 °C 0...2300 °C 0...600 °C -1999...9999, programmable -1999...9999, programmable -1999...9999, programmable (2) programmable programmable programmable programmable (up to 2 outputs)

Relay electromechanical Solid state relay MOS gate Output for external SSR Operation modes Control algorithms Auto-tuning Alarms Other control features Analog output (3) Serial interface

5A/250V w/ NO/NC or NO contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA manual and automatic ON/OFF, PID-pulse, and PID for motor valves, programmable programmable programmable BUMPLESS and ANTI-WINDUP 4(0)...20 mA or 0...10 V, isolated RS485, isolated

Accuracy

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

2 x 4 LED indicators 2 LEDs for output state 3 membrane keys

Digital display LEDs Keyboard

Operating conditions Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] PV display digit height [mm] SV display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals) (4)

(2)

(5)

Ordering code

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 5 VA

Indication and controls

(1)

Other voltage ranges can be obtained by the means of two external resistors. Provides loop supply voltage - 24 VDC (only w/ isolated power supply) (3) Instead of 1st relay! If mounted, it can be programmed as control or retransmission!

0.3% (3) from span 0.01% from span for 1 °C automatic software automatic software automatic software

Measurement error Temperature drift Self-calibration Cold junction compensation RTD line compensation

(6)

'B' 'H' / 'V' 96x96 96x48 panel panel 90x42 90x90 98 98 20 14 / 10 10 14 300 350 IP54/20 IP54/20 IP65 IP65 (5) plastic plastic plug-in plug-in

-10...55 °C 0...85 %RH 'Q' 'S' 72x72 48x48 panel panel 45x45 67x67 100 66 10 14 10 10 200 300 IP54/20 IP54/20 plastic plastic screw screw

0.5% for noble thermocouples Ask for availability! Not available for cases 'Q' and 'S'

RT484 - G0.G1.G5G5.G9'9".G11 - #1

Code Feature or option

Code values

G0

Case (front size)

B - 96x96 mm, H - 96x48 mm, V - 48x96 mm, Q - 72x72 mm, S - 48x48 mm

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G9'

Serial interface

X - none, B - RS485

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

G11

Analog output (3,5)

X - none, E - 0…20 mA, F - 4…20 mA, K - 0…10 V

#1

Increased front protection

X - none, P - IP65 front protection (6)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Input


process controllers Universal Programmable Controller RT1800 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

5 DIN sizes Two 4-digit displays plus bargraph Universal programmable input Optional remote set-point input PID-fuzzy auto-tuning with bumpless Auto/Manual Up to 4 relays and analog control output Retransmission analog output available Triple isolation RAMP/SOAK function 2-program-with-up-to-8-point pattern set point available Serial interface available

RT1800 is a microprocessor-based controller with universal input, analog output, and up to 4 relays (control or alarm) that may be controlled through a number of algorithms such as ON/OFF, ON/OFF heating/cooling duplex, motor-valve control, PID, and self-tuning PID. A bumpless auto-manual change-over is built in the PID algorithm. A start-on timer allows one of output relays to be time-controlled. Two displays (for the measured value and for the set point) as well as an output-control bargraph ease operator duties. Carefully protected from electromagnetic disturbances by featuring both input and output optical isolation, RT1800 is well equipped for troublefree operation in harsh industrial conditions.

Technical specifications Pt100 (w=1.385, 1.391); 3-wire Thermocouple "B" Thermocouple "E" Thermocouple "J" Thermocouple "K" Thermocouple "L" Thermocouple "N" Thermocouple "R" Thermocouple "S" Thermocouple "T" Thermocouple "U" Thermocouple "D" Linear voltage -10...50 mV Linear current 0(4)...20 mA Input type/range selection Input isolation Auxiliary input (2) (option) Signal type Function

Control outputs Relay electromechanical (5) Solid state relay MOS gate Output for external SSR Analog output (6) Isolation Control algorithms Auto-tuning Auto/Manual control Pattern set point

Alarm outputs Relay electromechanical Solid state relay (5) MOS gate Output for external SSR

(programmable) (1) -199.9...600.0 °C [6] 0...1820 °C [1] 0...1000 °C [2] 0...400.0(1200) °C [6] 0...400.0(1200) °C [6] 0...800 °C [2] 0...1300 °C [2] 0...1769 °C [2] 0...1769 °C [2] -199.9...400.0 °C [3] -199.9...600.0 °C [3] 0...2320 °C [2] -1999...9999, programmable [4] -1999...9999, programmable [2] programmable optical, 1500 VAC

RS232 or RS485 configuration and networking up to 31 1500 VAC MODEBUS ASCII or RTU

Interface type Function Network devices Isolation Protocol

Accuracy 0.3% from span 0.01% from span for 1 °C 250 ms automatic software automatic software

Measurement error Temperature drift Sample time Cold junction compensation RTD line compensation

Power supply Supply voltage Consumption

85…265 VAC max. 4 VA

Indication and controls 0(4)...20 mA remote set point (3) (up to 2 outputs ) (4) 3A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 24 V, 20 mA 0(4)...20 mA (≤ 600 Ω), 0...10 V (≥ 1 MΩ) optical, 1500 VAC ON/OFF and PID-fuzzy, programmable programmable bumpless, keyboard switched (7) 1(2) programs w/ 16(8) points (up to 2 outputs (3)) (4) 3A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 24 V, 20 mA

Retransmission output (8) (option) Signal type Function Isolation

Serial interface (9)

0(4)...20 mA (≤ 600 Ω), 0...10 V (≥ 1 MΩ) PV or SV transmission optical, 1500 VAC

Digital display (7) Bargraph display LEDs Keyboard

2 x 4 LED indicators st 10-point LED for 1 control output, 0...100% 8 (6 for 'S') control LEDs 5 (4 for 'S') membrane keys

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] PV display digit height [mm] SV display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals)

'B' 96x96 panel 91x91 81 14 10 300 IP56/20 IP65 plastic screw

0...50 °C 20...85 %RH -20...65 °C 0...95 %RH, non-condensing 'H' / 'V' 'Q' 'S' 96x48 panel 91x45 81 8 8 225 IP56/20 IP65 plastic screw

72x72 panel 69x69 81 14 10 225 IP56/20 IP65 plastic screw

48x48 panel 45x45 81 8 8 150 IP56/20 plastic screw

(1)

[n] shows the number of sub-ranges that can be selected via the keyboard. nd For cases 'B', 'H', 'V' – instead of interface; for case 'Q' – instead of 2 alarm output; for case 'S' – instead of interface and retransmission analog output For cases 'B', 'H', 'V' – 2 control + 2 alarm or 1 control + 3 alarm; for case 'Q' – 1 control + 2 alarm or 2 control + 1 alarm; for case 'S' – 2 control + 2 alarm (4) For cases 'B', 'H', 'V' 2nd control (3rd alarm) relay is NO; for case 'Q' 2nd control (1st alarm) relay is NO; for case 'S' all relays are NO. (5) Ask for availability! (6) Instead of control relay! (7) Not available for case 'S'! (8) nd st For cases 'H', 'V' – instead of 2 alarm output; for case 'S' – instead of interface or 1 alarm output. (9) st For cases 'B', 'H', 'V' – instead of auxiliary input; for case 'S' – instead of retransmission or 1 alarm output. (2)

(3)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Main input


process controllers

Ordering code

RT1800 - G0.G5'G5'.G5"G5"G5".G8.G9'9".G11 - #1.#2.#3

Code Feature or option G0

Case (front size)

G5'

Relay control output

G5"

Relay alarm output

G8

Control algorithm

G9'

Serial interface

G9"

Protocol

G11

Analog control output

#1

Auxiliary input

#2

Analog retransmission output

#3

Increased front protection

Code values B - 96x96 mm, H - 96x48 mm, V - 48x96 mm, Q - 72x72 mm, S - 48x48 mm

(3)

(3)

X - none, C - relay NO/NC

(4)

, D - SSR

(5)

, J - for external SSR, M - isolated MOS gate

X - none, C - relay NO/NC

(4)

, D - SSR

(5)

, J - for external SSR, M - isolated MOS gate

F - PID-fuzzy (ON/OFF), H - PID-fuzzy plus pattern control

(9)

X - none, A - RS232, B - RS485 M - MODEBUS (ASCII), N - MODEBUS (RTU) (6)

X - none, E - 0…20 mA, F - 4…20 mA, K - 0…10 V

(2)

X - none, E - 0…20 mA, F - 4…20 mA X - none, E - 0…20 mA, F - 4…20 mA, K - 0…10 V X - none, P - IP65 front protection

(7)

COMECO reserves the right of changing specifications without prior notice!

(8)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org


process controllers Universal Programmable Controller RT1900-R ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

DIN-rail or wall mounting 4-digit display Triple isolation Universal programmable input PID-fuzzy auto-tuning Up to 3 relay and 1 analog outputs RAMP/SOAK pattern control RS485 MODEBUS serial interface USB port for parameter storage

RT1900-R is a DIN-rail mounting microprocessor-based controller with universal input accepting Pt100, 10 thermocouple types and various linear signals. It can have up to 3 relays (control or alarm) and analog output that may be controlled through ON/OFF and self-tuning PID-fuzzy algorithms as well as optional RAMP/SOAK pattern control. A bumpless auto-manual change-over is also built in the PID algorithm. RT1900-R is equipped with 4-digit LED display and 4-button keyboard for programming. A triple input/output/supply isolation protects the controller from electromagnetic disturbances. Communication features include RS485 MODEBUS interface and USB port for program parameter storage. RT1900-R is well equipped for trouble-free operation in harsh industrial conditions.

Technical specifications Pt100 (w=1.385, 1.391); 3-wire Thermocouple "B" Thermocouple "E" Thermocouple "J" Thermocouple "K" Thermocouple "L" Thermocouple "N" Thermocouple "R"("S") Thermocouple "T" Thermocouple "U" Linear DC (mV) Linear DC (V) Linear DC (mA) Linear resistive Linear display Input type/range selection Input isolation

Outputs

(up to 3 outputs) Maximum 2 outputs (2) 5A/250V w/ NO contact 1A/250VAC 0.1A/60V, optically isolated 24 V, 20 mA 0(4)...20 mA (≤ 560 Ω), 0...5(10) V (≤ 20mA) optical, 1500 VAC ON/OFF and PID-fuzzy, programmable programmable 1(2) programs w/ 16(8) points Maximum 3 outputs (2) 5A/250V w/ NO contact

Control outputs - relay electromechanical (3) - solid state relay - MOS gate - output for external SSR (3) - analog output (load) - isolation - control algorithms - auto-tuning - RAMP/SOAK pattern Alarm outputs - relay electromechanical (1) (2)

Communication Serial interface (3) - function - network USB interface - function

isolated RS485, MODEBUS configuration and networking max. 32 devices, max. 1200 m mini-A USB side connector parameter storage

Accuracy Measurement error Temperature drift Sample time Cold junction compensation RTD line compensation

0.3% from span 0.01% from span for 1 °C 250 ms automatic software automatic software

Power supply Supply voltage Consumption

85…265 VAC max. 4 VA

Indication and controls Digital display Status LEDs Keyboard

4 LED indicators, 7 mm 3 LEDs for output and 1 for program 4 tactile keys

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

0...50 °C 20...85 %RH -25...65 °C 0...95 %RH, non-condensing

Design and materials Case material DIN-rail mounting Wall mounting Wiring Dimensions Weight Protection level

plastic on 35 mm DIN rail 4 screws screw terminals 40x107x43 mm approx. 115 g IP10

Some linear ranges may require hardware adjustments (contact COMECO) Maximum total outputs: 2 control + 1 alarm, or 1 control + 2 alarm, or 3 alarm

Ordering code

RT1900 - R.G5'G5'.G5"G5"G5".G8.G9.G11

Code Feature or option G5'

Relay control output

G5"

Relay alarm output

G8

Control algorithm

G9

Serial interface (3)

G11 (3)

(programmable) -199.9...600.0 °C, 6 ranges 0...1820 °C, 1 range 0...900 °C, 2 ranges 0...1200 °C, 6 ranges 0...1200 °C, 6 ranges 0...800 °C, 2 ranges 0...1300 °C, 2 ranges 0...1769 °C, 2 ranges -199.9...400.0 °C, 3 ranges -199.9...600.0 °C, 3 ranges min. -10 mV to max. 50 mV, 4 ranges min. -2 V to max.10 V, 9 ranges 0...20 mA, 4...20 mA 0...5 kΩ -1999...9999, programmable DP programmable (1) optical, 1500 VAC

(2)

(2)

Analog control output

Code values X - none, C - relay NO, D - SSR

(3)

, J - for external SSR, M - isolated MOS gate

X - none, C - relay NO F - PID-fuzzy (ON/OFF), H - PID-fuzzy plus pattern control X - none, B - RS485 (MODEBUS) (3)

X - none, E - 0…20 mA, F - 4…20 mA, I - 0…5 V, K - 0…10 V

Ask for availability!

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Input


process controllers Double Programmable Controller RT218 ♦ ♦ ♦ ♦ ♦

Two RT18 controllers in one housing Self-tuning ON/OFF or PI control algorithm Fixed input Various power supplies Easy programming

RT218 combines two RT18 controllers in one 96x96 mm case. Thanks to its lower cost than the combined cost of 2 separate RT18 controllers, this model is often preferred when 2 technological parameters are controlled in one machine or installation or of separate adjacent processes. Typical applications include control of 2 temperatures, temperature and humidity, pressure and temperature, pH and temperature, and other combinations. Each of the 2 incorporated controllers controls its relay output through an ON/OFF or selftuning PI algorithm, the latter being a convenient solution that saves installation time and costs and provides precise control eliminating temperature cycling and excessive start-up overshoot. The reliable operation even in the presence of electromagnetic disturbances and the attractive price also account for the success of the RT218 controller.

Technical specifications Input

(for each controller) -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(200) °C -9.9(-50)...90.0(200) °C min. -99...max. 500 °C 0...999(600) °C (2) 0...999(850) °C (2) 0...900(600) °C (2) 0...650(550) °C (2) min. -99(0)...max. 900(999) °C (2) -99...900 (0...999) (2,3,4) -99...900 (0...999) (2,3,4) min. -99...max. 999 (2,3,4) min. -99...max. 999 (2,3,4)

Pt50 (w=1.385); 3-wire Pt100 (w=1.385); 3-wire Pt500 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire Cu100; 3-wire Cu50; 3-wire Other RTD (1) Thermocouple "J" Thermocouple "K" Thermocouple "L" Thermocouple "L-GOST" Other thermocouple (1) Linear voltage 0...10 V Linear current 0(4)...20 mA Custom linear voltage; max. 40 V Custom linear current; max. 80 mA

Output

(for each controller)

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Programmable parameters

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF, self-tuning PI within input range limits according to control algorithm

Accuracy Measurement error Temperature drift Cold junction compensation RTD line compensation (option)

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

Indication and controls Digital display LEDs Keyboard

(for each controller) 0.4% from span 0.005% from span for 1 °C ± 1 °C 0.01% from span for 1 Ω (for each controller) 230 VAC or 115 VAC 90...250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 3 VA (for each controller) 3 LED indicators, 14 mm LED for output state 3 membrane keys

Operating conditions -10...65 °C 0...85 %RH

Operating temperature Operating humidity

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals Increased front IP (option) (5)

plastic in 90x90 mm panel cut-out plug-in terminals 96x96(front)x107 mm 98 mm max. 600 g IP54 / IP20 IP65

(1)

Custom; specify range within the limits stated. For self-tuning PI algorithm, ONLY the alternative ranges are applicable. Specify lower and upper display limits. (4) Provides loop supply voltage - 24 VDC (only w/ isolated power supply) (5) Ask for availability! (2)

Ordering code

RT218 - G1(G1).G3(G3).G5(G5).G6'6"(G6'6").G8(G8) - #1(#1).#2 (6)

Code Feature or option Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G3

Resolution

B - 1, C - 0.1 (2)

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G6'

Input signal

G6"

(6) (7)

Code values

G1

Sensor

B - thermoresistance, C - thermocouple, D - linear, Z - other on request RTD

B - Pt50, D - Pt100, F - Pt500, G - Pt1000, H - Cu50, K - Cu100, Z - other (1)

T/C

J - "J", K - "K", L - "L" , M - "L-GOST", Z - other (1)

linear

B - 0…20 mA (3), C - 4…20 mA (3), K - 0…10 V (3), Z - other (3)

G8

Control algorithm

A - ON/OFF, C - self-tuning PI (7)

#1

Compensation for 3-wire RTD line

X - none, LC - built-in line resistance compensation

#2

Increased front protection

X - none, P - IP65 front protection (5)

Second controller values are in brackets. Specify the direction of control action (heating or cooling relay action).

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

(3)


process controllers Double Programmable Controller RT228 ♦ ♦ ♦ ♦ ♦

Two RT28 controllers in one housing ON/OFF or PD-for-MV control algorithm Fixed input Various power supplies Easy programming

RT228 combines two RT28 controllers in one 96x96 mm case. Thanks to its lower cost than the combined cost of 2 separate RT28 controllers, this model is often preferred when 2 technological parameters are controlled in one machine or installation or of separate adjacent processes. Typical applications include control of 2 temperatures, temperature and humidity, pressure and temperature, pH and temperature, and other combinations. Each of the 2 incorporated controllers controls its relay outputs through an ON/OFF or PD algorithm, and thanks to these relay duplex outputs (2 relays per controller, 4 relays per whole device), RT228 is best suited for controlling motorized valve actuators or other actuators with 2-way action. The reliable operation even in the presence of electromagnetic disturbances makes the RT228 controller a widely applicable device.

Technical specifications Input

(for each controller) -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(500) °C -9.9(-50)...90.0(200) °C -9.9(-50)...90.0(200) °C min. -99...max. 500 °C 0...999(600) °C 0...999(850) °C 0...900(600) °C 0...650(550) °C -99(0)...900(999) °C -99...900 (0...999) (2,3) -99...900 (0...999) (2,3) -99...max. 999 (2,3) -99...max. 999 (2,3)

Pt50 (w=1.385); 3-wire Pt100 (w=1.385); 3-wire Pt500 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire Cu100; 3-wire Cu50; 3-wire Other RTD (1) Thermocouple "J" Thermocouple "K" Thermocouple "L" Thermocouple "L-GOST" Other thermocouple (1) Linear voltage 0...10 V Linear current 0(4)...20 mA Custom linear voltage; max. 40 V Custom linear current; max. 80 mA

Outputs

(for each controller, up to 2 relay outputs)

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Programmable parameters

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF, PD within input range limits according to control algorithm

Accuracy Measurement error Temperature drift Cold junction compensation RTD line compensation (option)

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

Indication and controls Digital display LEDs Keyboard

(for each controller) 0.4% from span 0.005% from span for 1 °C ± 1 °C 0.01% from span for 1 Ω (for each controller) 230 VAC or 115 VAC 90...250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 3 VA (for each controller) 3 LED indicators, 14 mm 2 LEDs for output state 3 membrane keys

Operating conditions -10...65 °C 0...85 %RH

Operating temperature Operating humidity

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals Increased front IP (option) (4)

plastic in 90x90 mm panel cut-out plug-in terminals 96x96(front)x107 mm 98 mm max. 600 g IP54 / IP20 IP65

(1)

Custom; specify range within the limits stated. Specify lower and upper display limits. Provides loop supply voltage - 24 VDC (only w/ isolated power supply) (4) Ask for availability! (2)

Ordering code

RT228 - G1(G1).G3(G3).G5G5(G5G5).G6'6"(G6'6").G8(G8) - #1(#1).#2 (5)

Code Feature or option Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G3

Resolution

B - 1, C - 0.1

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G6'

Input signal

G6"

(5)

Code values

G1

Sensor

B - thermoresistance, C - thermocouple, D - linear, Z - other on request RTD

B - Pt50, D - Pt100, F - Pt500, G - Pt1000, H - Cu50, K - Cu100, Z - other (1)

T/C

J - "J", K - "K", L - "L" , M - "L-GOST", Z - other (1)

linear

B - 0…20 mA (2), C - 4…20 mA (2), K - 0…10 V (2), Z - other (2)

G8

Control algorithm

A - ON/OFF, C - PD

#1

Compensation for 3-wire RTD line

X - none, LC - built-in line resistance compensation

#2

Increased front protection

X - none, P - IP65 front protection (4)

Second controller values are in brackets.

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

(3)


process controllers Double Programmable Controller RT228U ♦ ♦ ♦

Two RT28U controllers in one case Universal input for 4 RTDs, 6 T/Cs, and 3 linear types RS485 serial interface available

RT228U combines two RT28U controllers in one 96x96 mm case. Thanks to its lower cost than the combined cost of 2 separate RT28U controllers, this model is often preferred when 2 technological parameters are controlled in one machine or installation or of separate adjacent processes. Typical applications are control of 2 temperatures, temperature and humidity, pressure and temperature, pH and temperature, and other combinations. Each of the 2 incorporated controllers is equipped with universal input and controls its relay outputs by an ON/OFF algorithm. Thanks to its programmable inputs and displays as well as relay duplex outputs (2 relays per controller, 4 relays per whole device), RT228U is a widely applicable device.

Technical specifications Input Pt100 (w=1.385); 3-wire Pt1000 (w=1.385); 3-wire PTC (1k at 25 °C); 3-wire PTC (2k at 25 °C); 3-wire Thermocouple "T" Thermocouple "J" Thermocouple "K" Thermocouple "S" Thermocouple "R" Thermocouple "B" Linear voltage 0...10 V Linear current 0(4)...20 mA Custom linear (option) (1) Two-wire external transmitter Manual input offset Input type selection Decimal point selection Temperature measurement unit

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point Alarms Serial interface (2) (3)

Measurement error Temperature drift Cold junction compensation RTD line compensation

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

Indication and controls Digital display LEDs Keyboard

(for each controller) 0.3% from span 0.02% from span for 1 °C automatic, -10...80 °C automatic, up to 2 х 25 Ω (for each controller) 230 VAC or 115 VAC 90…250 V 12…24 V or 24 VAC 12…24 V max. 1.5 VA (for each controller) 3 LED indicators, 14 mm 2 LEDs for output state 3 membrane keys

Operating conditions -10...65 °C 0...85 %RH

Ambient temperature Ambient humidity

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals Increased front IP (option) (3)

plastic in 90x90 mm panel cut-out plug-in terminals 96x96(front)x107 mm 98 mm max. 600 g IP54 / IP20 IP65

Instead of linear current Provides loop supply voltage - 24 VDC (only w/ isolated power supply) Ask for availability!

Ordering code

RT228U - G1(G1).G5G5(G5G5).G9'9"(G9'9") - #1.#2(#2) (4)

Code Feature or option

(4)

Accuracy

Code values

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G9'

Serial interface

X - none, B - RS485

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

#1

Increased front protection

X - none, P - IP65 front protection (3)

#2

Customer specified input signal

X - none, Z - custom linear signal (specify!) (1)

Second controller values are in brackets.

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(1)

(for each controller, programmable) -100...850 °C -100...600 °C -50...150 °C -50...150 °C -40...400 °C -20...999 °C -20...999 °C 0...999 °C 0...999 °C 100...999 °C -199...999, programmable -199...999, programmable -199...999, programmable 4...20 mA (2) programmable programmable programmable °C or °F, programmable (for each controller, up to 2 relay outputs) 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF within input range limits programmable RS485, isolated


process controllers 2-channel Programmable Controller RT180 ♦ ♦ ♦ ♦ ♦ ♦

2 independent control channels in one device 2 DIN cases – horizontal and vertical Universal input for 4 RTDs, 4 T/Cs, and 3 linear types ON/OFF- pulse-mode control RH, pH, and ∆t variants available RS485 serial interface available

RT180 offers an exceptionally convenient and inexpensive solution for 2 loopcontrol applications within 1 machine or 2 adjacent ones. The universal programmable inputs make sensor change easy and convenient, and allow on-site configuring of variety of inputs and controlled physical values. The controller may be used for measurement and control of temperature difference (variant 'D'), pH and temperature (variant 'P'), relative humidity through the "wet-and-dry-bulb thermometer" method (variant 'R'), and in other cases in which 1 device measures and controls 2 physical values. All of this make RT180 widely applicable for both industry and laboratory use.

Technical specifications Inputs

(1 per channel, programmable)

Pt100 (w=1.385); 3-wire Pt50 (w=1.385); 3-wire Cu100; 3-wire Cu50; 3-wire Other RTD (1) Thermocouple "J" Thermocouple "K" Thermocouple "L" Thermocouple "L- GOST" Other thermocouple (1) Linear voltage 0...50 mV Linear current 0(4)...20 mA Custom linear 0...50 mV/mA (option) (1) Input type selection (3) pH +2000...-2000 mV Manual input offset

Outputs

-19.9(99)...99.9(500) °C -99...500 °C -9.9(50)...99.9(200) °C -99...200 °C min. -99...max. 500 °C min. 0...max. 900 °C min. 0...max. 999 °C min. 0...max. 600 °C min. 0...max. 600 °C min. 0...max. 999 °C -99...999, programmable (2) (2) -99...999, programmable -99...999, programmable (2) programmable 0...14 pH through keyboard (1 per channel)

Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Set point

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF, pulse mode programmable

Serial interface (4) Interface type Protocol

RS485, isolated free ASCII or ASCII for "PolyMonitor"

Accuracy Measurement error Temperature drift Calibration Manual calibration Cold junction compensation RTD line compensation

0.3% from span 0.01% from span for 1 °C automatic software through keyboard automatic software automatic software

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 3 VA

Indication and controls Digital display LEDs Keyboard

2 x 3 LED indicators 2 LEDs for output state 4 membrane keys

Operating conditions Operating temperature Operating humidity

Design and materials Front dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Display digit height [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring

'H' 96x48 panel 90x42 98 9 300 IP54 / IP20 IP65 plastic plug-in terminals

-10...65 °C 0...85 %RH 'V' 48x96 panel 42x90 98 10 300 IP54 / IP20 IP65 plastic plug-in terminals

Instead of a chosen standard input Provides loop supply voltage - 24 VDC (only w/ isolated power supply) pH input is available ONLY for the 1st channel. The 2nd channel must be for temperature correction and/or control (Pt100: -19.9...99.9 °C). (4) Ask for availability! (2) (3)

Ordering code

RT180 - G0.G1.G5G5.G9'9" - #1.#2

Code Feature or option

Code values (5,6)

Variant

N - standard (w/ programmable inputs), D - for temperature difference control , P - for pH control (3,5), R - for relative humidity control (5,6), Z - other on request (4)

G0

Case (front size)

H - 96x48 mm, V - 48x96 mm

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G9'

Serial interface

X - none, B - RS485 (4)

G9"

Protocol

A - ASCII, C - ASCII for "PolyMonitor"

#1

Increased front protection

X - none, P - IP65 front protection

#2

Customer specified input signal

X - none, Z - custom linear signal (specify!)

(5) (6)

(1)

Variants 'P', 'D', and 'R' have FIXED control algorithm that cannot be altered by the user. The default control algorithm is ON/OFF – the same as in the standard variant. The input types of both channels are fixed to Pt100 with fixed input ranges.

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

(1)


process controllers Programmable Controller RT390 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Extremely flexible – unlimited range of applications User-programmable structure by ready-made blocks Powerful self-testing capabilities May be used as pH and RH controller Wide range of control algorithms and alarm types Bumpless Auto/Manual change-over Up to 5 inputs and 5 outputs Digital interface for network operation

RT390 is a compact microprocessor-based controller with user programmable internal structure and very wide range of application. It can be equipped with up to 3 analog and 2 discrete inputs and up to 3 relays and 2 analog outputs and can accept a whole variety of input signals including temperature, relative humidity, flow, pressure, pH, etc. Electromechanical relays, solidstate relays, or current or voltage analog outputs may be installed as control, alarm, or limit comparators. Each relay output may be programmed as time or frequency proportional or as a simple ON/OFF. The 3 analog inputs available allow special applications like positioning control, cascade controllers, pH control (with temperature compensation), etc. The internal structure consists of up to 15 functional blocks. Each functional block may calculate one of the 24 standard functions. Custom defined functions may be added. Bumpless auto/manual changeover is another feature. Network functions and hierarchical control are available with serial interface installed. Keyboard locking is possible by connection of a switch to one of the digital inputs.

Technical specifications Pt100; 3-wire Pt500; 3-wire Pt1000; 3-wire Cu53; 3-wire Cu100; 3-wire Ni100; 3-wire Other RTD Thermocouple "B" Thermocouple "D" Thermocouple "E" Thermocouple "J" Thermocouple "K" Thermocouple "L" Thermocouple "L - GOST " Thermocouple "N" Thermocouple "R" Thermocouple "S" Thermocouple "T" Thermocouple "U" Other thermocouple Linear voltage (Rin ≥ 1 GΩ) (1,2) Custom linear voltage (1,2) Linear current (Rin ≤ 10 Ω) (1,2) Custom linear current (1,2) Linear resistive (1) Linear potentiometer (1) pH input (Rin ≥ 10 TΩ) ORP input (Rin ≥ 10 TΩ) Sub-range selection

Digital inputs Input signal type Limitations Functions

Relay outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Output function Control algorithms and alarm limits Set point (1) (2) (3)

(up to 3 inputs) -200...200 (850) °C -200...200 (850) °C -200...200 (850) °C 0...180 °C -200...200 °C -60...200 °C min. -200...max. 850 °C 200...1820 °C 400...2300 °C -270...1000 °C -210...1200 °C -270...1370 °C -200...900 °C -200...900 °C -270...1300 °C -50...1700 °C -50...1700 °C -270...400 °C -200...600 °C up to 2000 °C 0...2 V, 0...5 V, or 0...10 V 0...max. 10 V 0(4)...20 mA 0...max. 50 mA 0...Rp ≥ 50 Ω 0...Rp ≥ 5 kΩ 0.00...14.00 pH -1000...+1000 mV programmable (up to 2 inputs) contact, TTL, NPN, or PNP Uin. max. ≤ 40 VDC programmable, in combination with certain blocks (up to 3 outputs) 5A/250V w/ NO contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF, time-proportional, or frequency-proportional (3) programmable, according to selected block types within input range limits

Analog outputs

(up to 2 outputs)

Current output Voltage output Other on request Output function Output range

0(4)...20 mA DC (RLOAD ≤ 400 Ω) 0...2/ 5/ 10 VDC (RLOAD ≥ 2/ 5/ 10 kΩ) max. 20 mA or 10 V retransmission / control user-programmable

Digital interface Output type Output function

RS232 or RS485 network, operator station, or hierarchical control

Accuracy Measurement error Temperature drift Calibration Cold junction compensation

0.4% from span 0.005% from span for 1 °C automatic software automatic hardware

Power supply Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 3 VA

Indication and controls Digital display LEDs Keyboard

4 LCD or LED indicators, 13 mm with programmable decimal point 3 LEDs for relay output state, LED for auto/manual mode 4 membrane keys

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals

plastic in 93x45 mm panel cut-out screw terminals 96x48(front)x125 mm 120 mm max. 350 g IP54 / IP20

The correspondence (mapping) of the input signal with displayed value ranges is user programmable. Provides 12...24 VDC / 30 mA supply for external transmitter on one of the linear voltage or current outputs Three types of frequency proportional outputs are available (user programmable). Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Analog inputs


process controllers

Programmable structure blocks PID ON/OFF controller ON/OFF duplex controller Positioning control Control error calculation Constant Adder Gain Attenuator Multiplier Divider Linear transformation (mapping) Low pass filter Saturation Dead band "Window" type alarm Inverted "window" type alarm High limit alarm Low limit alarm Timer Generator Time controlled multiplexer Discrete input controlled multiplexer Very long period PWM output Selectable constant (set-point unit) RH measurement by "wet" and "dry" bulb method PID with 2 inputs

Ordering code

industrial PID with anti-windup integration (4 parameters) ON/OFF control (1 parameter) ON/OFF duplex (heating/cooling) control (3 parameters) 2-speed positioning control for motorized valves (4 parameters) compares set point and measured value (1 parameter) constant value (1 parameter) adds 2 signals multiplies input signal by a constant (1 parameter) divides input signal by a constant (1 parameter) multiplies the values of the 2 input signals divides the values of the 2 input signals translates input signal range X1…X2 into output range Y1…Y2 (4 parameters) 3rd order Butterworth low pass filter (no ripple step response) (4 parameters) limits output signal between lower and upper limits (2 parameters) output signal is zero when input is within the dead band (1 parameter) output is active while input is within alarm limits (2 parameters) output is active while input is outside alarm limits (2 parameters) output is active while input above alarm limit (1 parameter) output is active while input below alarm limit (1 parameter) generates a pulse depending on input signal (2 parameters) controlled pulse generator (4 parameters) switches 1 of the 2 input signals to the output at time intervals (2 parameters) switches 1 of the 2 input signals to the output controlled by a discrete input forms PWM signal with time period of up to 9999 s (3 parameters) outputs one of 4 selected constants; controlled by the state of 2 discrete inputs forms signal proportional to RH value from 2 temperature inputs PID module with 2 inputs (input #1 - PV, input #2 - SP)

RT390 - G1.G2.G5G5G5.G6'6"G6'6"G6'6".G7G7.G9'9".G11G11

Code Feature or option

Code values A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G1

Power supply

G2

Display

A - LCD, C - LED

G5

Relay output

X - none, A - relay NO, J - for external SSR, M - isolated MOS gate

G6'

Input signal

X - none, B - thermoresistance, C - thermocouple, D - linear, Z - other on request

G6"

Sensor

RTD

D - Pt100, F - Pt500, G - Pt1000, H - Cu53, K - Cu100, M - Ni100, Z - other

T/C

B - "B", D - "D", E - "E", J - "J", K - "K", L - "L" , M - "L-GOST", N - "N", R - "R", S - "S", T - "T", U - "U", Z - other

linear

B - 0...20 mA, C - 4...20 mA, H - 0...2 V, I - 0...5 V, K - 0...10 V, L - resistive, 0...Rp, M - potentiometer, 0...Rp, N - pH, O - ORP, Z - other

Discrete input

X - none, A - contact, E - NPN, F - PNP, G - TTL

G9'

Serial interface

X - none, A - RS232, B - RS485

G9"

Protocol

B - RT390, D - RT390 for "PolyMonitor"

G11

Analog output

X - none, E - 0…20 mA, F - 4…20 mA, H - 0…2 V, I - 0...5 V, K - 0...10 V, Z - other on request

COMECO reserves the right of changing specifications without prior notice!

G7

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org


level control equipment Level Controller LC05 ♦ ♦ ♦ ♦ ♦ ♦ ♦

Operates with conductive or non-conductive liquids Contact or resistive input Panel mounting Controls level between 2 electrodes with 1 relay output Tank supply or drainage control State indication Low cost

LC05 is a low-cost level controller for supply or drainage level control. Through its relay output, this device directly controls electrical pumps, valves, etc. and may be used either for tank emptying (drainage) or tank filling (supply). Two versions are available employing different methods for level measurement: - LC05 with resistive input., i.e. measuring electrical conductivity of the liquid between electrodes or between electrode and metal tank body, applicable for liquids with relatively high conductivity that are normally used in chemical, paper, food, wine, biotechnological industries, etc; - LC05 with electrical contact input, monitoring float state using magnetic or electromechanical float switches and applicable for various non-conductive liquids or cases of heavy condensation, vaporization, or foaming, such as in heating and water supply installations, etc. LC05 level controller is based on high-tech specialized electronic circuits that guarantee accuracy and stability, prevent electrolytic polarization, and ensure stable operation.

Technical specifications Input

Power supply passive electrical contact ≤ 50 Ω ≥ 500 kΩ conductive electrodes ≤ 50 kΩ ≥ 1…10 MΩ 18 VAC as requested

Contact - ON resistance - OFF resistance Resistive (1) - activation threshold (2) - release threshold (3) - probe voltage Input type

Output Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF

Indication LED for power ON, LED for output state

LEDs

Mains supply voltage SMPS voltage (4) Isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC (4) or 24 VAC max. 2 VA

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals Increased front IP (option)

plastic in 42x90 mm panel cut-out plug-in terminals 48x96(front)x107 mm 98 mm max. 400 g IP54 / IP20 IP65

(1)

Measures liquid resistance between measuring electrode and reference electrode (tank body) Maximum threshold resistance of activation at reaching (exceeding) the level Minimum threshold resistance of release at falling below the level (4) Ask for availability! (2) (3)

LC05 - G1.G5.G7 - #1

Code Feature or option

Code values

Variant

F - for supply control, E - for drainage control

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V (4), Q - 12…24 V, isolated (4), R - 24 VAC

G5

Relay output

C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G7

Input

A - contact (float), B - resistive (conductivity cell)

#1

Increased front protection

X - none, P - IP65 front protection

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

Ordering code


level control equipment Programmable Level Controller LC1x ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

With up to 3 relay outputs, for up to 3 levels (independent) May control 2 dependent levels plus alarm Threshold adjustment option Tank supply and drainage control Input from conductivity-cell level electrodes Indication for reached level Panel or DIN-rail mounting Low cost

LC1x is a low-cost electronic level controller available for DIN-rail and panel mounting. It employs measurement of the electrical conductivity of the liquid between electrodes or between electrode and metal vessel case and is applicable for liquids with relatively high conductivity that are normally used in chemical, paper, food, wine, biotechnological industries, etc. The LC10 variant allows monitoring 1 or 2 fixed levels, and LC11 can monitor 1, 2, or 3 fixed levels, and a corresponding relay is activated or deactivated when each level is reached (drainage / supply control). Besides signaling reached level, the output relays may also be used for controlling electrical actuators. The direction of relay action at reached level as well as the connection (dependence) between levels is user-selectable. The device can also be configured as a drainage or supply level controller with alarm relay. A high-tech microprocessor circuit guarantees accuracy and stability, prevents electrolytic polarization, and ensures stable operation. A possibility to adjust output activation threshold as well as an LED indication makes the LC1x level controller a solution for a wide range of level related problems.

Technical specifications Input

Power supply

Input type (1)

resistive, from conductivity cell electrodes 10…1000 kΩ 10…2000 kΩ max. 5000 pF by trimmers on front panel jumper selectable (3) each level controls a relay 1 relay, controlled by 2 levels (up to 3 relay outputs) 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF jumper selectable (3)

- activation threshold - release threshold Input wiring capacitance Threshold adjustment Operation modes: - independent levels - dependent levels

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Drainage/supply control

Indication LED for power ON (2), 3 LEDs for output state (4), 3 LEDs for reached levels

LEDs

Mains supply voltage SMPS voltage (5) Isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC (5) or 24 VAC max. 2 VA

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

Design and materials Dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) (6) Case material Wiring

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing 'V' 48x96(front)x107 panel 42x90 98 500 IP44 / IP20 IP65 plastic plug-in terminals

'R' 70x110x58 DIN-rail 53 500 IP20 plastic plug-in terminals

(1)

Measures liquid resistance between measuring electrode and reference electrode (tank body) Available ONLY for case 'V' Factory settings: 3 independent levels with drainage action; different factory settings are available on request. (4) Available ONLY for case 'R' (5) Ask for availability! (6) Not available when threshold-adjustment trimmers are mounted! (2)

Ordering code

LC1 - G0.G1.G5G5G5.G7G7G7 - #1.#2 (7)

Code Feature or option

0 - for up to 2 levels, with 2 relay outputs, 1 - for up to 3 levels, with 3 relay outputs

G0

Case

V - for panel mounting, R - for DIN-rail mounting

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V (5), Q - 12…24 V, isolated (5), R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G7

Input

X - none, B - resistive (conductivity cell)

#1

Threshold adjustment

#2 (7)

Code values

Variant

Increased front protection

X - none, A - threshold-adjustment trimmers mounted (6)

X - none, P - IP65 front protection

G5G5.G7G7 for variant '0'

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


level control equipment Programmable Level Controller LC1x ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

With up to 3 relay outputs, for up to 3 levels (independent) May control 2 dependent levels plus alarm Threshold adjustment option Tank supply and drainage control Input from conductivity-cell level electrodes Indication for reached level Panel or DIN-rail mounting Low cost

LC1x is a low-cost electronic level controller available for DIN-rail and panel mounting. It employs measurement of the electrical conductivity of the liquid between electrodes or between electrode and metal vessel case and is applicable for liquids with relatively high conductivity that are normally used in chemical, paper, food, wine, biotechnological industries, etc. The LC10 variant allows monitoring 1 or 2 fixed levels, and LC11 can monitor 1, 2, or 3 fixed levels, and a corresponding relay is activated or deactivated when each level is reached (drainage / supply control). Besides signaling reached level, the output relays may also be used for controlling electrical actuators. The direction of relay action at reached level as well as the connection (dependence) between levels is user-selectable. The device can also be configured as a drainage or supply level controller with alarm relay. A high-tech microprocessor circuit guarantees accuracy and stability, prevents electrolytic polarization, and ensures stable operation. A possibility to adjust output activation threshold as well as an LED indication makes the LC1x level controller a solution for a wide range of level related problems.

Technical specifications Input

Power supply

Input type (1)

resistive, from conductivity cell electrodes 10…1000 kΩ 10…2000 kΩ max. 5000 pF by trimmers on front panel jumper selectable (3) each level controls a relay 1 relay, controlled by 2 levels (up to 3 relay outputs) 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF jumper selectable (3)

- activation threshold - release threshold Input wiring capacitance Threshold adjustment Operation modes: - independent levels - dependent levels

Outputs Relay electromechanical Solid state relay MOS gate Output for external SSR Control algorithm Drainage/supply control

Indication LED for power ON (2), 3 LEDs for output state (4), 3 LEDs for reached levels

LEDs

Mains supply voltage SMPS voltage (5) Isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC (5) or 24 VAC max. 2 VA

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

Design and materials Dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) (6) Case material Wiring

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing 'V' 48x96(front)x107 panel 42x90 98 500 IP44 / IP20 IP65 plastic plug-in terminals

'R' 70x110x58 DIN-rail 53 500 IP20 plastic plug-in terminals

(1)

Measures liquid resistance between measuring electrode and reference electrode (tank body) Available ONLY for case 'V' Factory settings: 3 independent levels with drainage action; different factory settings are available on request. (4) Available ONLY for case 'R' (5) Ask for availability! (6) Not available when threshold-adjustment trimmers are mounted! (2)

Ordering code

LC1 - G0.G1.G5G5G5.G7G7G7 - #1.#2 (7)

Code Feature or option

0 - for up to 2 levels, with 2 relay outputs, 1 - for up to 3 levels, with 3 relay outputs

G0

Case

V - for panel mounting, R - for DIN-rail mounting

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V (5), Q - 12…24 V, isolated (5), R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR, J - for external SSR, M - isolated MOS gate

G7

Input

X - none, B - resistive (conductivity cell)

#1

Threshold adjustment

#2 (7)

Code values

Variant

Increased front protection

X - none, A - threshold-adjustment trimmers mounted (6)

X - none, P - IP65 front protection

G5G5.G7G7 for variant '0'

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


level control equipment Level Controller LC20 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Operates with conductive or non-conductive liquids Contact or resistive input Rail mounting Optional threshold adjustment Controls level between 2 electrodes with 1 relay output Tank supply or drainage control State indication Low cost

LC20 is a low-cost electronic level controller/indicator for rail mounting. Through its relay output, this device directly controls electrical pumps, valves, etc. and may be used either for tank emptying (drainage) or tank filling (supply). Two versions are available employing different methods for level measurement: - LC20 with resistive input., i.e. measuring electrical conductivity of the liquid between electrodes or between electrode and metal tank body, applicable for liquids with relatively high conductivity that are normally used in chemical, paper, food, wine, biotechnological industries, etc; - LC20 with contact input, accepting signals from contact level switches (float, optical, etc.), applicable for various non-conductive liquids or cases of heavy condensation, vaporization, or foaming, such as in heating and water supply installations, etc. An optional output activation threshold adjustment via potentiometer on the front panel provides better adaptation to liquids with different conductivity for both versions.

Technical specifications Input

Power supply

Contact (1) - ON resistance - OFF resistance Resistive (2) - activation threshold (3) - release threshold (4) - probe voltage Input type Threshold adjustment (option)

passive electrical contact ≤ 50 Ω ≥ 500 kΩ conductivite electrodes ≤ 50 kΩ ≥ 1…10 MΩ 18 VAC as requested via front-panel potentiometer, 10...50 kΩ

Output Relay electromechanical Solid state relay (1) MOS gate (1) Output for external SSR Control algorithm

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF

Indication LED

LED for output state

Mains supply voltage SMPS voltage (1) Isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC (1) or 24 VAC max. 2 VA

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

-10...65 °C 0...85 %RH -20...65 °C non-condensing, 0...95 %RH

Design and materials Case material Mounting Wiring Dimensions Weight Protection, front/terminals

plastic on 35 mm DIN rail screw terminals 45x78x124 mm max. 400 g IP40 / IP20

(1)

Ask for availability! (2) Measures liquid resistance between measuring electrode and reference electrode (tank body) (3) Maximum threshold resistance of activation at reaching (exceeding) the level (4) Minimum threshold resistance of release at falling below the level

LC20 - G1.G5.G7 - #1

Code Feature or option

Code values

Variant

F - for supply control, E - for drainage control

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V (1), Q - 12…24 V, isolated (1), R - 24 VAC

G5

Relay output

C - relay NO/NC, D - SSR (1), J - for external SSR, M - isolated MOS gate (1)

G7

Input

A - contact (float) (1), B - resistive (conductivity cell)

#1

Threshold adjustment

X - none, A - potentiometer for threshold adjustment

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

Ordering code


level control equipment Level-Switch Isolating Unit LCI2x ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Isolating amplifier with up to 2 channels Operates with ATEX level switches series LCSFT Provides 2.5 V sensor voltage Isolated AC/DC power supply Output and power state indication 750 V isolation Rail mounting Low cost

The LCI2x isolating amplifier is a low-cost isolating unit with robust plastic case for rail mounting, especially designed to be used with COMECO’s ATEX-approved float level switches series LCSFT. The isolator operates with a wide range of power supply voltages and provides an isolated sensor voltage of only 2.5 V. The internal optical isolator and pulse transformer ensure an isolation level of 750 V. LCI2x can be ordered either with 1 input and 1 relay output, or, when the application requires controlling high and low level points, with 2 inputs and 2 corresponding output relays. Up to 3 LEDs provide convenient indication of the output and power state. The excellent price-toperformance ratio makes the remote isolating unit LCI2x a very useful device for low-cost Ex applications in liquid level control.

Technical specifications Inputs

(1 per channel) OFF/ON, resistive: 20/10 kΩ ± 10% 2.5 VDC ≤ 63 µA 750 VAC for 1 min

Input signal Input (sensor) voltage Input (sensor) current Isolation from output

Outputs

(1 per channel)

Relay electromechanical Solid state relay (1) MOS gate (1) Output for external SSR Switching hysteresis

5A/250V w/ NO contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ≤ 0.01% of span

Indication up to 2 red LEDs for output state, green LED for power ON

LEDs (1)

Isolated low voltage SMPS voltage (1) Isolation from input Consumption

8...28 VAC/DC 90…250 VAC/DC 750 VAC for 1 min max. 2 VA

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

-10...65 °C 0...85 %RH -20...65 °C non-condensing, 0...95 %RH

Design and materials Case material Mounting Wiring Dimensions Weight Protection, front/terminals

plastic on 35 mm DIN rail plug-in terminals 35x110x58 mm max. 250 g IP54 / IP20

Ask for availability!

Ordering code

LCI2 - G1.G5 (2)

Code Feature or option

Code values

Variant

0 - single-channel, 2 - double-channel

G1

Power supply

C - 90…250 V (1), Q - 8…28 V, isolated

G5

Relay output

A - relay NO, D - SSR (1), J - for external SSR, M - isolated MOS gate (1)

G5G5 for variant '2'

COMECO reserves the right of changing specifications without prior notice!

(2)

Power supply

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,


process controllers Field Mounting ON/OFF Controller RT38-Y ♦ ♦ ♦ ♦ ♦ ♦ ♦

Ready to incorporate temperature or other sensor Direct in-process mounting Relay control output switching power supply Semi-universal input Mains or low-voltage power supply Fully programmable parameters IP66 protection class

RT38-Y is a programmable ON/OFF controller, designed for direct control over temperature or other processes when coupled with a TSEC temperature probe or other sensor. The device is equipped with a 3-digit LED display and a control relay. Available are 2 universal-input versions – RTD (for 7 selectable Ptx and 4 Cux sensor types) and T/C (for 3 selectable thermocouples) – as well as versions for linear current and voltage signals. The controller can be ordered either for mains or for low-voltage power supply and allows an automatic software compensation of line resistance and cold junction temperature. The display-to-input correspondence (in case of linear input), decimal point position, temperature measurement unit, and offset value are also programmable. RT38-Y is enclosed in a robust plastic box with IP66 connector and enables easy and firm sensor assembly. Thanks to its design, RT38-Y is widely applicable in cases, in which direct control of electrical actuators is required.

Technical specifications Input

Power supply

RTD, DIN (w=1.385); 3-wire RTD, GOST (w=1.391); 3-wire RTD measurement range Thermocouple "T" Thermocouple "J" Thermocouple "K" Linear voltage 0...10 V Linear current 0(4)...20 mA Two-wire external transmitter RTD or T/C type selection Decimal point selection Temperature measurement unit

Pt50, Pt100, Pt500, Pt1000 Pt46, Pt50, Pt100, Cu50, Cu100 -100...600 °C -40...400 °C -20...999 °C -20...999 °C -199...999, programmable -199...999, programmable 4...20 mA (1) programmable programmable °C or °F, programmable

Output

Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage External mains transformer (2) Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC 9(12) VAC max. 1.5 VA

Indication and controls 3 LED indicators, 14 mm LED for output state 3 membrane keys

Digital display LEDs Keyboard

Operating conditions

Relay electromechanical Solid state relay MOS gate Output for external SSR Direct power supply switching Control algorithm Set point Alarms

5A/250V w/ NO contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA OFF - open circuit; ON - supply voltage ON/OFF within input range limits programmable

Accuracy Measurement error Temperature drift Cold junction compensation

0.3% from span 0.02% from span for 1 °C automatic, -10...80 °C

Ambient temperature Ambient humidity

-10...65 °C 0...85 %RH

Design and materials Case material Controller mounting Probe mounting Power wiring Probe wiring Dimensions Protection, enclosure/terminals

ABS plastic on probe top or free (3) axial (box bottom) or radial (connector opposite) 4-pin М12 connector, always on top 4-pin М12 connector or direct (4) 92x92x60 mm IP66 / IP65

Provides loop supply voltage - 24 VDC (only w/ isolated power supply). Ordered separately (see 'Accessories'). (3) May be mounted on plate or rail by special accessories, which are ordered separately (see 'Accessories'). (4) Order separately! Suitable for assembly are temperature probes type TSEC w/ head connection M12x1.5 (see 'Temperature Probes'). (2)

Ordering code

RT38 - Y.G1.G5.G6.G12'12"

Code Feature or option

Code values

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, E - 9(12) VAC w/ external transformer (2), P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Output

X - none, A - relay NO, D - SSR, J - for external SSR, M - isolated MOS gate, Y - power supply

G6

Input

B - RTD (programmable), C - thermocouple (programmable), D - 0(4)…20 mA, DK - 0…10 V

G12'

Probe connection

I - direct (4), E - via connector

G12"

Probe position

A - axial, R - radial

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(1)


level control equipment Float Level Probe with Controller LCF ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

2-level control with 1 relay output User-selectable filling or drainage control Various float types 135 °C maximum liquid temperature Mains or low-voltage power supply Vertical adjustment option ATEX certified Ex version available Cost saving solutions

COMECO's level controller LCF combines a 2-point float-type level probe LCSFC and a standard LC05 controller installed inside an ABS protective enclosure with IP66. Large variety of versions based on different plastic and stainless steel floats is available. Floats with different dimensions and specific gravity are available for liquid density down to 0.5 g/cm3, temperature up to 135 °C, and pressure up to 50 bar. Various process connections as well as an option for vertical adjustment are available. LCF can be used for liquid filling or emptying control by switching on and off vessel supply or drainage devices such as pumps and magnet valves. The controller allows the operator to select relevant output relay action for either supply or drainage control. Thanks to the compact combination of probe and in-head controller, LCF can be very useful for building cost-saving level control applications.

Probe specifications LCF

Model B

A

L2

L0

L1

LX

Vertical Adjustment 10% of L0

Specifications Float type

N1

P1

P10

P2

P3

P4

S0/S1/S7/S10

S2

S3

S4

S5

S6

Float material Liquid density [g/cm3]

NBR > 0.80

PP > 0.60

PP > 0.72

PP > 0.60

PP > 0.50

PVDF > 0.70

SS > 0.80

SS > 0.70

SS > 0.65

SS > 0.55

SS > 0.55

SS > 0.50

Ext. tube diameter ('d')

8 mm

8 mm

10 mm

12 mm

16 mm

16 mm

10 mm

14 mm

14 mm

100...1500 100...2500

Min. end-to-float distance ('A') [mm]

23

21

15

37

47

47

22/25/25/29

34

40

39

50

70

Min. float running distance ('B') [mm]

27

24

17

52

62

62

25/30/30/34

40

57

54

75

110

12 bar

30 bar

30 bar

10 bar

min. 2"

min. 2"

-20…100 °C

Max. process pressure Wetted parts

0 bar

5 bar

5 bar

3 bar

min. ½" (M20)

min. 1" (M33)

min. 1" (M33)

min. 1" (M33)

Process connection

-20…80 °C

100...1000

16/18 mm 16/18 mm

100...1000

Process temperature

200...4000

8 mm

Probe length ('L0') [mm]

100...2000 200...3000 200...3000 300...4000 300...5000

-30…125 °C 3 bar

-20…135 °C

2 bar 8/10/30/50 bar 30 bar stainless steel or plastic

min. 1 ¼"

min. 1" (M33)

min. 1½"

min. 3" or flange

Controller specifications Input Input type

Power supply float position – low or high

Output Relay electromechanical Solid state relay (1) MOS gate (1) Output for external SSR Control algorithm Operation mode

8A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated 5…24 V, 30 mA ON/OFF, filling or emptying, user-selectable

Indication LEDs (1)

red LED for output state

Ask for availability!

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

Mains supply voltage SMPS voltage (1) Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC (1) or 24 VAC 24 VDC max. 2 VA

Operating conditions Ambient temperature Ambient humidity

-10...65 °C 0...85 %RH

Design and materials Case material Wiring Dimensions Protection class

ABS plastic screw terminals via PG9 cable glands 80x80x60 mm (w/o glands) IP66

COMECO reserves the right of changing specifications without prior notice!

A


level control equipment

Ordering code

LCF - G0.G1.G5.G6.G9.G10 - #1

Code Feature or option Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V (1), D - 24 VDC, non-isolated, Q - 12…24 V, isolated (1), R - 24 VAC

G1

Float

N1 - NBR, ø15x25, P1 - PP, ø24x22, P2 - PP, ø29x50, P3 - PP, ø38x60, P4 - PVDF, ø38x60, P10 - PP, ø29x11, S0 - stainless steel, ø25x25, S1 - stainless steel, ø28x28, S2 - stainless steel, ø41x38, S3 - stainless steel, ø45x55, S4 - stainless steel, ø52x52, S5 - stainless steel, ø73x73, S6 - stainless steel, ø75x108, S7 - stainless steel, ø30x28, S10 - stainless steel, ø30x32, S20 - stainless steel, ø22x40

G5

Relay output

G0

C - relay NO/NC, D - SSR (1), J - for external SSR, M - isolated MOS gate (1) (2)

G6

Operating lengths [mm]

L0/L1/L2

G9

Process connection

X - none, Q2 - M20x1.5, Q4 - G1/2", Q5 - M27x2, Q6 - G3/4", Q10 - 1/2" NPT, Q11 - 3/4" NPT, Q12 - G1", Q13 - G1½", Q14 - G2", Q15 - 1" NPT, Q16 - 1½" NPT, Q17 - 2" NPT, Q21 - G3", Q22 - 3" NPT, Q25 - M33x2, Q27 - G1¼", Q28 - 1¼" NPT, F - flange (specify!), Z - other (specify!)

G10

Sheath material

M1 - 1.4301, M2 - 1.4541, M3 - 1.4571, M9 - 1.4404, M15 - 1.4362

#1

Vertical adjustment

X - none, A - vertical adjustment via stainless steel ferrule installed

Specify the exact length (step 50 mm) from the thread, flange, or box bottom to the respective contact according to the limits given in the specification table, strictly observing 'A' and 'B' minimum distances! 1st contact → 'L1'; e.g.: LCF - A.S1.C.500/50/200.Q12.M1

COMECO reserves the right of changing specifications without prior notice!

(2)

Code values

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,


pressure and flow control equipment Flow Controller PSF21x ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Excellent price-to-performance ratio Unique ultra-light-rotor technology Exceptional accuracy and reliability Operates with liquids with viscosity from 1 to 1000 CST Pulse output with 6000 pulses per liter of water Alarm/Control output with 2 programmable limits Local programmable LED display Chemically resistant variant available

PSF21x is a programmable flow controller designed for use with low-viscose clear or translucent liquids, transmitting IR light. The operating principle is based on the liquid volume measurement through light-weight rotor, IR sensor, and sophisticated electronics for measurement and control. The material types used (PVDF, Vectra®, Viton®, EPDM, etc.) have a good thermal (up to 90 °C) resistance. A special variant with increased chemical resistance also extends the controller application. Other ranges except the standard 0.5…20 l/min are available on request. PSF21x is equipped with a local 3-digit LED display and a hidden key for easy programming and flow monitoring. Output capabilities include TTL pulse output as well as PNP or NPN alarm output that activates when either of the programmable alarm limits is reached. PSF21x can be used as a flow meter, flow transmitter with pulse output, ON/OFF flow controller, or alarm unit suitable for water treatment and other applications.

Technical specifications Input

Local indicator

Liquid type

clear or translucent liquid transmitting IR light (1) 1...1000 CST 0.5...20 l/min (2)

Liquid viscosity Flow range

Measurement accuracy ± 1.00% 1.00% max. ± 0.30%

Accuracy Interchangeability Reproducibility

Outputs Pulse output Sensitivity Alarm output Alarm type Alarm function

TTL, 100...2000 Hz, max. 0.5 mA 6000 pulses per liter of water PNP/NPN, max. 100mA/40V, NO 'window' ON/OFF

Power supply 18...30 VDC 2 Vp-p at 50 Hz max. 200 mA

Supply voltage Admissible variations Consumption (2)

Operating conditions Process temperature Ambient temperature Process pressure

Design and materials Wetted parts Seals Case material Mounting Process connection Wiring Dimensions Weight Protection class (housing)

PSF210 POM, PVDF, Viton®, Vectra®, EPDM NBR POM free 2 x G1/2”, male 3(4)-wire PVC cable 105x60x45 mm max. 200 g IP67

-20...90 °C -10...65 °C max. 12 bar PSF211 SS, PVDF, Viton®, Vectra®, EPDM PTFE POM free 2 x G1/2”, male 3(4)-wire PVC cable 105x60x45 mm max. 250 g IP67

Liquid medium must be compatible with wetted part and seal materials! Other ranges are available on request.

Ordering code

PSF21 - G5.G9.G12

Code Feature or option

Code values

Variant

0 - standard, 1 - chemically resistant (3)

G5

Relay output

E - NPN, F - PNP

G9

Pulse output

X - none, P - 6000 TTL pulses/l

G12

Cable length [m] and type

1PV…10PV - PVC

(3)

3 LED indicators, 10 mm 0.1 l/min 1s 0.01% from span for 1 °C for alarm event 1 hidden key

Limited with wetted part and seal material resistance!

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(1)

Digital display Display resolution Display refresh Temperature drift LED indicator Keyboard


timers and counters Dial-type Analog Timer CT02 ♦ ♦ ♦ ♦ ♦ ♦

Very low cost Wide time range 48x48 mm or 96x48 mm DIN-sized front panel 8 operating modes Main and auxiliary relays Panel or rail mounting

The CT02 timer is designed for time sequence control of electrical actuators. The time setting adjustment is done by rotating a dial on the front panel and the timing is started at power-on or by external 'start/stop' contact. Various modes of operation – on-delay, off-delay, pulse output, and cyclical output – are available. The operating modes as well as the time range (for variant 'S') can be selected via micro switches. The timer may be equipped with up to 2 relays – main timing relay and auxiliary relay, which is activated at power-on or simultaneously with the main relay. CT02 has no indication, is very easy to set and operate, and yet has all the main functions of a modern electronic timer.

Technical specifications Input

(1)

Indication and controls

Input type Input function

Times and modes Ranges (3) Dial multiplication coefficient Delay Output pulse Cyclic mode

Outputs Relay electromechanical Solid state relay (4) MOS gate Transistor gate (5) Output for external SSR Main (timer) relay Auxiliary relay

passive contact (NO) external 'Start/Stop' or front-panel 'Start/Stop' button (2) 'N' 'S' 1...10 s, 10...100 s, 0...1, 0...3, 0...6 1...10 min, 10...100 min - x1 s, x10 s, x1 min ON or OFF ON or OFF no yes no yes (up to 2 - main and auxiliary) 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated open collector, 40mA/40V 12/24 V, 30 mA time operated activates at power-on (6)

Accuracy 1% (2% for 'N') from span 0.007% from span for 1 °C

Measurement error Temperature drift

LEDs Rotating dial Micro switches

LED for the time operated relay for time adjustment for mode selection and multiplication coefficient setting (7)

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

Design and materials Case material Mounting

230 VAC or 115 VAC 24…230 VAC/DC 24 VDC 24 VDC max. 2 VA

plastic 'H': in 93x45 mm panel cut-out; 'S': in 45x45 mm panel cut-out or on 35 mm DIN rail

Wiring: - for variant 'N' - for variant 'S' Dimensions: - for variant 'N'

Power supply Mains supply voltage (1) SMPS voltage (7) Isolated low voltage (1) Non-isolated low voltage Consumption

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing

- for variant 'S' Mounting depth Weight Protection, front/terminals

'H': screw terminals; 'S': socket UNDECAL (8) socket OCTAL (8) 'H': 96x48(front)x136 mm; 'S': 48x48(front)x102 mm 48x48(front)x95 mm 'H': 120 mm; 'S': max. 105 mm (w/ socket) max. 250 g IP40 / IP20

(1)

Only for variant 'N' Only for case 'H' For variant 'S', ranges are user selectable; for variant 'N', they are fixed and should be specified in customer order. (4) Ask for availability! (5) ONLY with isolated power supply! (6) For variant 'S', a mode may be selected when auxiliary relay operates TOGETHER WITH the main time operated relay. (7) Only for variant 'S' (8) Ordered separately (see 'Accessories') (2)

Ordering code

CT02 - G0.G1.G4.G5G5.G8

Code Feature or option

(9)

Code values

Variant

N - normal, S - simplified

G0

Case (front panel) (1)

S - 48x48 mm, H - 96x48 mm

G1

Power supply

A - 230 VAC (1), B - 115 VAC (1), D - 24 VDC, non-isolated, K - 24…230 V (7), Q - 24 VDC, isolated (1)

G4

Start/Stop

A - at power-on, C - from front-panel button (2), D - from input (1)

G5

Relay output

X - none (9), C - relay NO/NC, D - SSR (4), E - open collector NPN (5), J - for external SSR, M - isolated MOS gate

G8

Operating mode (1)

B - selectable, D - delay ON, E - delay OFF, F - output pulse, G - cyclic

A main relay MUST be installed!

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


timers and counters Dial-type Analog Timer CT02 ♦ ♦ ♦ ♦ ♦ ♦

Very low cost Wide time range 48x48 mm or 96x48 mm DIN-sized front panel 8 operating modes Main and auxiliary relays Panel or rail mounting

The CT02 timer is designed for time sequence control of electrical actuators. The time setting adjustment is done by rotating a dial on the front panel and the timing is started at power-on or by external 'start/stop' contact. Various modes of operation – on-delay, off-delay, pulse output, and cyclical output – are available. The operating modes as well as the time range (for variant 'S') can be selected via micro switches. The timer may be equipped with up to 2 relays – main timing relay and auxiliary relay, which is activated at power-on or simultaneously with the main relay. CT02 has no indication, is very easy to set and operate, and yet has all the main functions of a modern electronic timer.

Technical specifications Input

(1)

Indication and controls

Input type Input function

Times and modes Ranges (3) Dial multiplication coefficient Delay Output pulse Cyclic mode

Outputs Relay electromechanical Solid state relay (4) MOS gate Transistor gate (5) Output for external SSR Main (timer) relay Auxiliary relay

passive contact (NO) external 'Start/Stop' or front-panel 'Start/Stop' button (2) 'N' 'S' 1...10 s, 10...100 s, 0...1, 0...3, 0...6 1...10 min, 10...100 min - x1 s, x10 s, x1 min ON or OFF ON or OFF no yes no yes (up to 2 - main and auxiliary) 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated open collector, 40mA/40V 12/24 V, 30 mA time operated activates at power-on (6)

Accuracy 1% (2% for 'N') from span 0.007% from span for 1 °C

Measurement error Temperature drift

LEDs Rotating dial Micro switches

LED for the time operated relay for time adjustment for mode selection and multiplication coefficient setting (7)

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

Design and materials Case material Mounting

230 VAC or 115 VAC 24…230 VAC/DC 24 VDC 24 VDC max. 2 VA

plastic 'H': in 93x45 mm panel cut-out; 'S': in 45x45 mm panel cut-out or on 35 mm DIN rail

Wiring: - for variant 'N' - for variant 'S' Dimensions: - for variant 'N'

Power supply Mains supply voltage (1) SMPS voltage (7) Isolated low voltage (1) Non-isolated low voltage Consumption

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing

- for variant 'S' Mounting depth Weight Protection, front/terminals

'H': screw terminals; 'S': socket UNDECAL (8) socket OCTAL (8) 'H': 96x48(front)x136 mm; 'S': 48x48(front)x102 mm 48x48(front)x95 mm 'H': 120 mm; 'S': max. 105 mm (w/ socket) max. 250 g IP40 / IP20

(1)

Only for variant 'N' Only for case 'H' For variant 'S', ranges are user selectable; for variant 'N', they are fixed and should be specified in customer order. (4) Ask for availability! (5) ONLY with isolated power supply! (6) For variant 'S', a mode may be selected when auxiliary relay operates TOGETHER WITH the main time operated relay. (7) Only for variant 'S' (8) Ordered separately (see 'Accessories') (2)

Ordering code

CT02 - G0.G1.G4.G5G5.G8

Code Feature or option

(9)

Code values

Variant

N - normal, S - simplified

G0

Case (front panel) (1)

S - 48x48 mm, H - 96x48 mm

G1

Power supply

A - 230 VAC (1), B - 115 VAC (1), D - 24 VDC, non-isolated, K - 24…230 V (7), Q - 24 VDC, isolated (1)

G4

Start/Stop

A - at power-on, C - from front-panel button (2), D - from input (1)

G5

Relay output

X - none (9), C - relay NO/NC, D - SSR (4), E - open collector NPN (5), J - for external SSR, M - isolated MOS gate

G8

Operating mode (1)

B - selectable, D - delay ON, E - delay OFF, F - output pulse, G - cyclic

A main relay MUST be installed!

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


timers and counters 2-period Multifunctional Timer CT03 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Fully programmable 2 time periods with 2 relay outputs Easy-to-set push-wheel switch External or power-on starting modes HOLD input Maximum time delay up to 999 min 4 operating modes 48x48 mm DIN-sized front panel

The CT03 timer is a low-cost microprocessor-based device for time sequence control with 2 adjustable time periods forming a time cycle, 3 sub-ranges, and 4 different timing modes. The push-wheel switch (BCD) on the front panel enables easy setting of the period duration and the 3-digit display indicates the current time, the parameters, or the operating mode. All modes of operation and parameters are user-programmable via front-panel keyboard. CT03 is also equipped with 2 contact inputs for external start and hold and 2 output relays with programmable action for timing control of processes through switching electrical actuators on and off. The extended features of CT03 simplify programming and process monitoring and make the timer a convenient solution to a wide range of timing related problems.

Technical specifications Inputs

Indication and controls

Input type Input START Input HOLD Input programming

NO contacts external closing contacts external closing contacts through keyboard

Times and modes

Digital display LEDs Keyboard Push-wheel switch

3 LED indicators, 10 mm 2 LEDs for relay state 2 membrane keys for easy value programming

Power supply

Ranges First period (t1) Second period (t2) Modes of operation Range selection Time selection Parameter programming Value adjustment

Outputs Relay electromechanical Solid state relay (3) MOS gate Transistor gate (4) Output for ext. SSR Relay K1 action Relay K2 action

0...99.9 s, 999 s, or 999 min after start depends on the operation mode up to 4 modes (1) programmable programmable through keyboard (2) by push-wheel switch (up to 2 relay outputs) 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated open collector, 40mA/40V 5...24 V, 30 mA activates alternatively with t1 and t2 activates for total cycle time (t1+t2)

Accuracy 0.02% from span negligible

Measurement error Temperature drift

Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 2 VA

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

-10...65 °C 0...85 %RH -10...70 °C 0...95 %RH, non-condensing

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals

plastic in 45x45 mm panel cut-out or on 35 mm DIN rail socket UNDECAL (5) 48x48(front)x95 mm 103 mm (w/ socket) max. 250 g IP54 / IP20

(1)

One-shut cycle mode; cyclic mode (repeated cycle); one-shut cycle mode (t2 - total cycle time); cyclic mode (t2 - total cycle time) Relay K1 action after start; relay K2 action in active period; inactive state of K1 and K2; specifies period adjusted by BCD; restart during action; automatic start at power-on Ask for availability! (4) ONLY with isolated power supply! (5) Ordered separately (see 'Accessories') (2)

Ordering code

CT03 - G1.G5G5

Code Feature or option

(6)

Code values

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none (6), C - relay NO/NC, D - SSR (3), E - open collector NPN (4), J - for external SSR, M - isolated MOS gate

At least one relay must be ordered!

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


timers and counters Analog Timer with Display CT04 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Low cost 4-digit LED display Time setting via push-wheel switch Improved precision ON and OFF delay Controls main and auxiliary relay 48x48 mm DIN-sized front panel Panel or rail mounting

With its 48x48 mm DIN-sized front panel, the CT04 timer is especially suitable for building in machines and installations where compact size is important. A 4-digit LED display indicates the current time, and the delay is set by push-on wheels (BCD coders), which greatly simplifies the setting and improves accuracy. Equipped with 2 relay outputs – main and auxiliary relay – CT04 can be used for timing control (switching on and off) of various electrical actuators. The main relay is time operated, and the auxiliary relay is activated at power-on or simultaneously with the main relay. In spite of its simple design and low price, CT04 has all main functions of a modern electronic timer and can be widely used in industry and consumer goods.

Technical specifications Times and modes

Power supply

Range Time unit Mode of operation Timing start

Outputs Relay electromechanical Solid state relay (1) MOS gate Transistor gate (2) Output for external SSR Main (timer) relay Auxiliary relay

0.0...99.9 or 0...999 seconds or minutes on-delay or off-delay at power-on (up to 2 - main and auxiliary) 5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated open collector, 40mA/40V 12/24 V, 30 mA time operated activates at power-on or copies main relay

Accuracy 0.05% from span insignificant

Measurement error Temperature drift

Indication and controls 4 LED indicators, 9 mm 2 LEDs for relay state and time unit for easy time setting

Digital display LEDs Push-wheel switch

Mains supply voltage Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 24 VDC 24 VAC or 24 VDC max. 2 VA

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals

plastic in 45x45 mm panel cut-out or on 35 mm DIN rail socket (3) OCTAL or UNDECAL (4) 48x48(front)x95 mm max. 103 mm (w/ socket) max. 250 g IP40 / IP20

(1)

Ask for availability! ONLY with isolated power supply! Ordered separately (see 'Accessories') (4) ONLY with auxiliary relay (2)

(3)

CT04 - G1.G5G5.G6.G8

Code Feature or option

(5)

Code values

Power supply

A - 230 VAC, B - 115 VAC, D - 24 VDC, E - 24 VAC, Q - 24 VDC, isolated

G5

Relay output

X - none (5), C - relay NO/NC, D - SSR (1), E - open collector NPN (2), J - for external SSR, M - isolated MOS gate

G6

Time range

LS - 0...99.9 s, HS - 0...999 s, LM - 0...99.9 min, HM - 0...999 min

G8

Operating mode

D - delay ON, E - delay OFF

G1

A main relay MUST be installed!

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

Ordering code


timers and counters Budget DIN-rail Digital Timer CT05 ♦ ♦ ♦ ♦ ♦ ♦

For low-cost applications Slim size 3 operating modes Up to 100 hour time delay Long relay life Easy setup and programming

CT05 is a DIN-rail mountable programmable time-delay relay designed for time sequence control of electrical actuators. The time delay can be adjusted from 0.1 s up to 100 h via a rotary switch and a trimming potentiometer on the front panel and the timing starts at power-on. Different modes of operation – on-delay, off-delay, and cyclical output – can be selected with the rotary micro switch. The timer is equipped with 1 relay output as well as a multi-function LED indicating power supply, relay, and failure status, timing and program modes. CT05 is very easy to set, program, and operate, and yet has all the main functions of a modern programmable timer.

Technical specifications Times and modes

Power supply

Ranges

0.1...1 s, 1...10 s, 0.1...1 min, 1...10 min, 0.1...1 h, 1...10 h, 10...100 h programmable (see table below)

Modes of operation

Output

Non-isolated SMPS voltage Non-isolated low voltage Consumption

24…230 VAC/DC 24 VAC/DC ± 10% max. 2 VA

Operating conditions

Output type Contact form and ratings Contact life cycles Initiate time Reset time

electromechanical relay NO/NC (SPDT), max. 5 A, max. 250 V 106 ≤ 350 ms ≤ 350 ms

Accuracy

Operating temperature Operating humidity Storage temperature Storage humidity

-20...65 °C 0...85 %RH -30...80 °C 0...95 %RH, non-condensing

Design and materials

Time accuracy Time repeatability

better than 0.5% of span better than 0.1% of span

Indication and controls LEDs Trimming potentiometer Rotary switch

LED for power ON, mode, and state for time adjustment and mode selection for range and mode selection

Mode

Case material Mounting Wiring Dimensions Weight Protection class

plastic on 35 mm DIN rail screw terminals 18x90x58 mm max. 70 g IP20

Delay ON

Cyclic delay ON

Pulsed delay ON

Delay OFF

Cyclic delay OFF

Pulsed delay OFF

U - power supply voltage R - relay output T - time delay

Ordering code

CT05 - G1

Code Feature or option G1

Power supply

Code values K - 24…230 V, non-isolated, P - 24 VAC/DC, non-isolated

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

LEGEND:


timers and counters 2-channel Programmable Timer CT12 ♦ ♦ ♦ ♦ ♦ ♦ ♦

2 programmable timers in one case Up to 2 freely programmable relay outputs Up to 10 programmable periods per channel 2 programs or 1 longer one 4-digit LED display Start from external input or from keyboard Maximum time per period 9999 minutes

CT12 is a programmable device for timing control incorporating 2 independent timers in one case. Two relay outputs (one per channel) control electrical actuators by switching them on and off. A time sequence that may consist of up to 10 ON or OFF periods, each with different duration, may be programmed for each output (channel). The device may be used as a single channel timer with up to 20 period time sequence. After a start command from the featured external input or the front-panel keyboard, the time sequence may be run once or repeated endlessly. A 4-digit digital display indicates current time and – during programming – parameter values, and the keyboard enables setting of all modes and parameters of time sequence. The CT12 timer is easy to program and – with its rich set of features – widely applicable.

Technical specifications Inputs

Indication and controls

Passive contact input Active signal input External 'Start/Stop' Input setting (2)

NO contacts voltage, max. 40 VDC starts and stops time sequence (1) programmable

Times and modes

Keyboard

4 LED indicators, 10 mm 2 LEDs for output state, 2 LEDs for indicated channel 4 membrane keys

Power supply

Time sequences Time periods Period duration range Time setting Output state setting Mode selection Measurement unit selection

Outputs

Digital display LEDs

(3)

Relay electromechanical Solid state relay MOS gate Transistor gate (4) Output for external SSR Relay function

1 per channel up to 10 per channel or 20 in single-channel mode 0.01 s...9999 min programmable for each period programmable for each period programmable programmable (up to 2 relay outputs) 5A/250V w/ NO/NC contact 1A/250 VAC 0.1A/60V, optically isolated open collector, 40mA/40V 12/24 V, 30 mA ON and OFF, acc. to time sequence

Accuracy 0.7% insignificant

Measurement error Temperature drift

Mains supply voltage (5) SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC (5) 12…24 VAC/DC max. 3 VA

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals Increased front IP (option) (5)

plastic in 93x45 mm panel cut-out screw terminals 96x48(front)x125 mm 120 mm max. 350 g IP54 / IP20 IP65

(1)

Time sequence start and stop may be initiated through external input or keyboard. Select the active front of external signal When only the single-channel mode will be used (20-period time sequence), only one (the first) relay may be ordered. (4) ONLY with isolated power supply! (5) Ask for availability! (2)

Ordering code

CT12 - G1.G5G5 - #1

Code Feature or option

Code values

G1

Power supply

A - 230 VAC (5), B - 115 VAC (5), C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC (5)

G5

Relay output (3)

X - none, C - relay NO/NC, D - SSR, E - open collector NPN (4), J - for external SSR, M - isolated MOS gate

#1

Increased front protection

X - none, P - IP65 front protection (5)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


timers and counters Universal Programmable Counter CT34 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Available as totalizer, R.P.M. meter, and combined One or two 6-digit LED displays Pulse- and analog-input versions Programmable divider and multiplier Pulse counting and batch counting Additional inputs CLEAR, GATE, and DIRECTION 6 user-selectable operating modes plus dosing mode Up to 2 programmable relay outputs Optional optical input isolation up to 1500 VAC RS485 serial interface available

CT34 is a sophisticated new-generation counter equipped with a 6-digit display, which can hold up to 999999 count units or batches, and may have up to 2 programmable relay outputs and an analog output for alarm signaling or process controlling. СТ34 is available as a counter, as an R.P.M. meter, and as a combination of both. As a counter, this model allows programming of 7 different counting and output-relay-action modes (including dosing mode) as well as counting pulses or pulse batches. The R.P.M.-meter variant has 6 operating modes. Besides its counting input, CT34 has 3 additional inputs – CLEAR, GATE, and DIRECTION – and a user-programmable software input filter. Other useful features include fraction number coefficient prescaler and programmable actual and displayed counting directions. With its various features and flexible programmable internal structure, the CT34 counter is a widely applicable device.

Technical specifications Counting input: - pulse, w/ programmable active front - analog, programmable (1,2) Input CLEAR Input GATE Input DIRECTION (3) Maximum input frequency Input filter Prescaler coefficients Input isolation (option)

Indication and controls mechanical contact (NO) or electronic (from PNP / NPN sensor) 0(4)...20 mA or 0...5(10) V resets counter to '0' (4 functions) enables pulse counting changes counting direction 5 kHz for suppression of contact bouncing 1...9999, multiplying and dividing optical, 1500 VAC

Modes Operating modes Counting modes Counting range Programming

Outputs Relay electromechanical (5) Solid state relay MOS gate Transistor gate (6) Output for external SSR Relay action Output pulse duration (8) Analog output Serial interface (1)

7 (incl. dosing mode) pulse counting and batch counting 0...2147483647 through keyboard (up to 2 outputs) 5A/250V w/ NO/NC (4) contact 1A/250VAC 0.1A/60V, optically isolated open collector, 40mA/40V 5…24 V, 30 mA according to the mode (7) 0.1...99.9 s, programmable 0(4)…20 mA or 0…10 V, isolated RS485, isolated

PV display (1) SP display LEDs Keyboard

6 LED indicators, 9 mm 6 LED indicators, 9 mm 2 LEDs for output state 4 membrane keys

Power supply Mains supply voltage (1) SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC (5) or 24 VAC (1) 12…24 VAC/DC max. 6 VA

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

Design and materials Dimensions [mm] Mounting Panel cutout [mm] Mounting depth [mm] Maximum weight [g] Protection, front/terminals Increased front IP (option) Case material Wiring (terminals)

'L'

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing 'S' 'H'

76x35x62 panel 71x29 56 180 IP54/20 IP65 plastic screw

48x48x110 panel 45x45 100 200 IP54/20 plastic screw

96x48x107 panel 90x42 98 280 IP54/20 IP65 plastic plug-in

(1)

Not available for case 'L' Available ONLY for variant 'CR'! Only with pulse input type! (4) NO for case 'L' (5) Ask for availability! (6) ONLY with isolated power supply! (7) st nd In case of variant 'CR' with pulse input, if not additionally specified, 1 relay is linked to counter and 2 – to R.P.M. meter. st nd With analog input, 1 relay is firmly linked to counter and 2 relay is user programmable. (8) nd Instead of 2 relay (_G5)! (9) Not available for case 'S' (2)

(3)

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Inputs


timers and counters Ordering code

CT34 - G0.G1.G3.G5G5.G9'9".G11 - #1.#2

Code Feature or option

Code values

Variant

C - totalizing counter, R - R.P.M. meter, CR - combined

G0

Case (front size)

H - 96x48 mm, S - 48x48 mm, L - 72x36 mm

G1

Power supply

A - 230 VAC , B - 115 VAC , C - 90…250 V, (5) (1) P - 12…24 V, non-isolated, Q - 12…24 V, isolated , R - 24 VAC

G3

Counting input

P - pulse, A - analog

G5

Relay output

G9' G9"

(1)

(1)

(1,2)

, D - SSR

(5)

Serial interface

X - none, B - RS485

Protocol

A - ASCII, C - ASCII for " PolyMonitor"

(5)

(7)

(8)

X - none, C - relay NO/NC M - isolated MOS gate

(4)

, E - open collector NPN

(6)

, J - for external SSR,

(1)

Analog output

X - none, E - 0…20 mA, F - 4…20 mA, K - 0…10 V

#1

Input isolation

X - none, I - input isolation

#2

Increased front protection

X - none, P - IP65 front protection (9)

COMECO reserves the right of changing specifications without prior notice!

G11

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org


timers and counters 2-channel Flow-rate Counter CT34SB ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Accepts pulse signals from 2 flow-meters Fully-programmable math block Two 6-digit LED displays Indicates current flows, math result, total counts Programmable relay output Sensor supply voltage 5...24 VDC Programmable input filtering 96x48 front size panel mounting

CT34SB is a specialized 2-channel fully programmable flow-rate totalizing counter. The instrument is especially designed to measure pulse signals from 2 different flow-meters according to the functional block-diagram below:

Counter software allows a convenient programmable scaling of both measured flow signals and applying various calculations on both flow rates. CT34SB is equipped with two 6-digit LED displays indicating current flow-rates, mathematically calculated values as well as accumulated total counts. The counter has also an optional relay output for generating impulse when certain total value is reached (dosing function).

Technical specifications Power supply

Counting inputs Input type Active front Maximum input frequency Input filter Scaling coefficients Totalizer range Math functions

2 pulse inputs (A and B) contact (NO) or PNP/NPN sensor programmable 5 kHz programmable low-pass filter scale factor and time-base up to 5000000 counts A-B, A+B, A*B, A/B, A/(A+B)

Indication and controls Digital displays Display function (link) LEDs Keyboard

2 x 6 LED indicators, 9 mm Rate A(B), Math result, Total 2 LEDs for output state 3 membrane keys

Output Relay electromechanical Solid state relay (1) MOS gate Transistor gate (2) Output for external SSR Relay action Output pulse duration (1) (2)

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated open collector, 40mA/40V 5…24 V, 30 mA totalizer set-point (dosing function) 0.02...1.2 s, programmable

Mains supply voltage SMPS voltage Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 90…250 VAC/DC 12…24 VAC/DC or 24 VAC 12…24 VAC/DC max. 6 VA

Operating conditions Operating temperature Operating humidity Storage temperature Storage humidity

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing

Design and materials Dimensions Mounting Mounting depth Maximum weight Protection, front/terminals Increased front IP (option) Case material Wiring

96x48x107 mm panel cutout 90x42 mm 98 mm 280 g IP54/20 IP65 plastic plug-in terminals

Ask for availability! ONLY with isolated power supply!

Ordering code

CT34SB - G1.G5 - #1

Code Feature or option

Code values

G1

Power supply

A - 230 VAC, B - 115 VAC, C - 90…250 V, P - 12…24 V, non-isolated, Q - 12…24 V, isolated, R - 24 VAC

G5

Relay output

X - none, C - relay NO/NC, D - SSR (1), E - open collector NPN (2), J - for external SSR, M - isolated MOS gate

#1

Increased front protection

X - none, P - IP65 front protection

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646524, fax: +359 32 634089, e-mail: export@comeco.org

COMECO reserves the right of changing specifications without prior notice!

Inputs


timers and counters Programmable Counter CT38 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Low cost 4-digit LED display for up to 9999 units Easy programming Universal optically isolated counting input Additional RESET input available 6 modes of operation of the counter and the relay output Programmable input multiplying coefficient 48x48 mm DIN-sized front panel

CT38 is a single-channel programmable counter with simplified programming. The device has a 4-digit display and can count up to 9999 input pulses. CT38 may work as up or down counter and has a relay output for switching on and off electrical actuators. Relay output action at reaching the preset counter value is user programmable. CT38 offers 4 counting modes and 2 output action modes. It features optical input isolation, and, optionally, an additional RESET input. The universal input allows connection of both mechanical contacts and electronic sensors. A software preliminary multiplying coefficient enables counting several units at each pulse. With its compact size, easy programming, and attractive price, the CT38 counter is widely used in machine manufacturing and various other areas.

Technical specifications Inputs

Indication and controls

Counting input - type selection Input RESET Maximum input frequency Input filter (fixed) Prescaling multiplying coefficient Input isolation

mechanical contact (NO) or electronic (from PNP / NPN sensor) not needed (automatic) NO contact; resets counter to 0 500 Hz for input contact bouncing 1...999, programmable optical, 750 VAC

Modes

Digital display LEDs Keyboard

4 LED indicators, 10 mm 3 LEDs for output and modes 6 membrane keys

Power supply Mains supply voltage Isolated low voltage Non-isolated low voltage Consumption

230 VAC or 115 VAC 12 VDC 12 VDC or 12 VAC max. 2 VA

Operating conditions 4 (1) 2 (2) 0...9999 through keyboard (up to 2 relay outputs)

Counting modes Output action modes Counting range Programming

Outputs Relay electromechanical Solid state relay (3) MOS gate Transistor gate (4) Output for external SSR Relay action Output pulse duration

5A/250V w/ NO/NC contact 1A/250VAC 0.1A/60V, optically isolated open collector, 40mA/40V 12 V, 30 mA according to the mode 0.1...9.9 s, programmable

Operating temperature Operating humidity Storage temperature Storage humidity

-10...65 °C 0...85 %RH -20...65 °C 0...95 %RH, non-condensing

Design and materials Case material Mounting Wiring Dimensions Mounting depth Weight Protection, front/terminals

plastic in 45x45 mm panel cut-out or on 35 mm DIN rail socket (5) OCTAL or UNDECAL (6) 48x48(front)x92 mm max. 103 mm (w/ socket) max. 250 g IP40 / IP20

(1)

Counting up or down; counting with or without automatic reset at reaching preset counter value Output activates and retains the new state with counter reaching preset value; output activates for a short time with counter reaching preset value Ask for availability! (4) ONLY with isolated power supply! (5) Ordered separately (see 'Accessories') (6) ONLY with RESET input (G7="A") (2)

Ordering code

CT38 - G1.G5.G7

Code Feature or option

Code values

G1

Power supply

A - 230 VAC, B - 115 VAC, D - 12 VDC, E - 12 VAC, Q - 12 VDC, isolated

G5

Relay output

C - relay NO/NC, D - SSR (3), E - open collector NPN (4), J - for external SSR, M - isolated MOS gate

G7

RESET input

X - none, A - contact

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

COMECO reserves the right of changing specifications without prior notice!

(3)


timers and counters Battery-powered Counter CT36 ♦ ♦ ♦ ♦ ♦ ♦

Low cost 8-digit totalizing LCD display 7-year lifetime without battery replacement 1 to 1000 cps selectable counting speed Front and rear-panel RESET 48x24 mm DIN-sized front panel

CT36 is a simple and low-cost battery-powered electronic counter, enclosed in a small plastic box with 48x24 mm front size. Equipped with a 8-digit LCD display, CT36 can count up to 99999999 units. It has 2 inputs counting input with counting speed up to 1000 cps and a RESET input. Both inputs can accept input signals from mechanical or electronic switches. A RESET button on the front panel is also available. The device may be equipped with micros-witches allowing front frequency selection as well as front reset key enabling. CT36 is powered by an incorporated lithium battery that has approximately 7 years of life cycle. Thanks to its small size and longlife battery operation, CT36 can be very useful for many applications requiring independent supply and small mounting dimensions such as integration in water meters, gas meters, etc.

Technical specifications Power supply

Inputs Counting input - active front - residual voltage Input RESET - function - reset pulse Maximum input frequency ON-sense OFF-sense

mechanical contact (NO) or electronic (NPN/PNP/MOS-gate sensor) rising ≤ 0.5 VDC NO contact or electronic sensor resets counter to 0 min. 20 ms 1 Hz, 30 Hz, 1000 Hz, fixed or selectable < 10 kΩ > 750 kΩ

Mode

Indication and controls 8 LCD indicators, 9 mm RESET left: select input frequency, right: front reset enable/disable

Digital display Front push button Side micro-switches

Ordering code

Operating conditions Ambient temperature Ambient humidity Storage temperature Vibration (malfunction) Shock (malfunction) Dielectric strength Insulation resistance

-10...55 °C, non-freezing 35...85 %RH -25...65 °C, non-freezing 0.3 mm at 10…55 Hz for 10 min 3 x 100 m/s2 (≈ 10 G) 2000 VAC for 1 min > 100 MΩ at 500 VDC

Case material Mounting Wiring Dimensions Mounting depth Weight Protection class

plastic in 45x22 mm panel cut-out screw terminals 48x24(front)x58 mm 54 mm max. 60 g IP20

CT36 - G4

Code Feature or option

Code values

Variant

U - w/ selectable input frequency, A - w/ 1 Hz input, B - w/ 30 Hz input, C - w/ 1 kHz input

Reset

D - from input RESET, C - from front-panel button, DC - from both sources

COMECO reserves the right of changing specifications without prior notice!

G4

3 V from lithium battery CR2477 ≈ 7 years (at 20 °C)

Design and materials up counting 0...99999999

Counting mode Counting range

Supply voltage Battery life

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,


handheld devices 2-channel Programmable Thermometer H5700 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Good accuracy at low consumption Operates with Pt1000 and 3 types of thermocouples Universal input available Measures temperature from up to 2 sensors 4-digit LCD display with mode indication Programmable auto power-off function Battery voltage management Readings in Celsius or Fahrenheit Sensor failure control

H5700 is a handheld 2-channel microprocessor-based device for measurement of temperature in 1 or 2 points by the means of Pt1000 sensors or thermocouples type "J", "K", or "S". The device has a 4-digit display providing a resolution of 0.1 °C within the -99.9...999.9 °C range. Two modes of operation – measurement of 1 temperature and measurement of 2 temperatures and temperature difference – are available. H5700 is programmed and controlled through a folio-type keyboard providing high degree of environmental protection. The device is offered with 2 alkaline or rechargeable 1.5 V AA batteries and features a special automatic-battery-control function. The numerous features of H5700, its high accuracy, and low consumption make it a widely applicable measurement instrument.

Technical specifications Inputs

(up to 2 inputs) -100.0...660.0 °C -100.0...1200 (999.9) °C -100.0...1300 (999.9) °C 0.0...1700 (999.9) °C

Pt1000 (w=1.385) Thermocouple "J" Thermocouple "K" Thermocouple "S"

Indication and controls 4-digit LCD, 13 mm 3 membrane keys

Digital display Keyboard

Accuracy

Power supply Supply voltage Operating consumption Stand-by consumption Auto-power-off time

3 V from 2 batteries AA 1.5 V (1) less than 3 mA less than 5 µA 0...30 min, programmable

0.1% (0.3% for T/C input) from span negligible ± 1 °C 0.01% from span for 1 °C 0.05% from span for 1 V

Case material Probe connection Dimensions Weight Protection, case/socket

plastic 4-pin snap-in connector ø8, type 'C3' 65x118x22 mm max. 110 g (w/ batteries) IP44 / IP20

H5700 - G1.G6'6"G6'6"

Code Feature or option

Code values

G1

Power supply

X - none (2), G - long-life batteries, H - rechargeable batteries

G6'6"

Input

X - none (3), A - programmable, BG - Pt1000, CJ - thermocouple "J", CK - thermocouple "K", CS - thermocouple "S"

The device is supplied without batteries. Only the second input can be cancelled.

COMECO reserves the right of changing specifications without prior notice!

(3)

-10...65 °C 0...85 %RH

Battery charger can be ordered separately (see 'Accessories').

Ordering code

(2)

Operating temperature Operating humidity

Design and materials

Measurement error Non-linearity Cold junction compensation Temperature drift Supply-voltage variation influence (1)

Operating conditions

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,


handheld devices Programmable Hygro-/Thermometer H5800 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦

Good accuracy at low consumption Operates with COMECO humidity handheld probes Humidity and temperature measurement Automatic temperature compensation of the RH probe 4-digit LCD display with mode indication Programmable auto power-off function Battery voltage management Readings in percentage, degrees Celsius or Fahrenheit

H5800 is a handheld microprocessor-based device for relative-humidity measurement in air and non-aggressive gases, designed to operate with COMECO’s RH probes. With the help of a Pt1000 sensor build in the RH probe, H5800 compensates probe temperature drift and indicates medium temperature. The device is equipped with a 4-digit display providing a resolution of 0.1. Two modes of operation – measurement of relative humidity and measurement of medium temperature in degrees Celsius or Fahrenheit – are available. Dew-point, absolute humidity, mixing ratio, and enthalpy can also be measured through calculation. H5800 is programmed and controlled through a folio-type keyboard providing high degree of environmental protection. The device is offered with 2 alkaline or rechargeable 1.5 V AA batteries and features a special automatic-battery-control function. The numerous features of H5800, along with its high accuracy and low consumption, make it a widely applicable measurement instrument.

Technical specifications Inputs

Operating conditions

RH input - range Temperature input - range

0…100 mV 0…100 %RH Pt1000 (w=1.385) -20...150 °C (-4...302 °F)

Indication and controls 4-digit LCD, 13 mm 3 membrane keys

Digital display Keyboard

Accuracy

Power supply Supply voltage Operating consumption Stand-by consumption Auto-power-off time

3 V from 2 batteries AA 1.5 V (1) less than 8 mA less than 1 µA 0...30 min, programmable

0.1% from span 0.1% from span negligible 0.01% from span for 1 °C 0.2% from span for 1 V 0.1% from span for 1 V

Case material Probe connection Dimensions Weight Protection, case/socket

plastic 4-pin snap-in connector ø8, type 'C3' 65x118x22 mm max. 110 g (w/ batteries) IP44 / IP40

Battery charger can be ordered separately (see 'Accessories').

Ordering code

H5800 - G1

Code Feature or option G1

Power supply

Code values X - none (2), G - long-life batteries, H - rechargeable batteries

The device is supplied without batteries.

COMECO reserves the right of changing specifications without prior notice!

(2)

-10...65 °C 0...85 %RH

Design and materials

RH measurement error Temperature measurement error Non-linearity Temperature drift Supply-voltage influence for RH Supply-voltage influence for T (1)

Operating temperature Operating humidity

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,


handheld devices Hygro-/Thermometer for Solids H5850 ♦ ♦ ♦ ♦ ♦ ♦ ♦

Good accuracy at low consumption Operates with RHP humidity probes Moisture and temperature measurement 4-digit LCD display with mode indication Programmable auto power-off function Battery voltage management Readings in percentage, degrees Celsius or Fahrenheit

H5850 is a handheld microprocessor-based device for humidity measurement of solids and bulk materials, designed to operate with COMECO’s RH probe model RHP. With the help of a Pt1000 sensor build in the RH probe, H5850 indicates the medium temperature too. The device is equipped with a 4-digit display providing a resolution of 0.1. Three modes of operation – measurement of moisture content, measurement of relative humidity, and measurement of medium temperature in degrees Celsius or Fahrenheit – are available. H5850 can be programmed and controlled through a folio-type keyboard providing high degree of environmental protection. The device is offered with 2 alkaline or rechargeable 1.5 V AA batteries and features a special automatic-batterycontrol function. The numerous features of H5850, along with its high accuracy and low consumption, make it a useful instrument for bulk-material moisture measurement.

Technical specifications Inputs

Operating conditions

Humidity input - moisture-content range - relative-humidity range Temperature input - range

from RHP probe 0…300 % 0…75 % Pt1000 (w=1.385) -20...150 °C (-4...302 °F)

Indication and controls 4-digit LCD, 13 mm 3 membrane keys

Digital display Keyboard

Accuracy

Power supply Supply voltage Operating consumption Stand-by consumption Auto-power-off time

3 V from 2 batteries AA 1.5 V (1) less than 8 mA less than 1 µA 0...30 min, programmable

0.2% from span 0.1% from span negligible 0.01% from span for 1 °C 0.2% from span for 1 V 0.1% from span for 1 V

Case material Probe connection Dimensions Weight Protection, case/socket

plastic 4-pin snap-in connector ø8, type 'C3' 65x118x22 mm max. 110 g (w/ batteries) IP44 / IP20

Battery charger can be ordered separately (see 'Accessories').

Ordering code

H5850 - G1

Code Feature or option G1

Power supply

Code values X - none (2), G - long-life batteries, H - rechargeable batteries

The device is supplied without batteries.

COMECO reserves the right of changing specifications without prior notice!

(2)

-10...65 °C 0...85 %RH

Design and materials

Humidity measurement error Temperature measurement error Non-linearity Temperature drift Supply-voltage influence for humidity Supply-voltage influence for T (1)

Operating temperature Operating humidity

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,


handheld devices Handheld Moisture-content Meter H6300 ♦ ♦ ♦ ♦ ♦ ♦ ♦

Non-contact measurement of wood and concrete samples Modern electromagnetic measurement principle Measurement depth 1...7 cm Entirely eliminates temperature influence Integral moisture-content value measurement Very fast measurement Low price

H6300 by COMECO is designed to measure moisture content of wood or concrete samples, employing an electromagnetic measurement principle. With the help of a sensor detecting variations of electromagnetic field within sample, the device measures moisture content even without an electrical contact with the sample. To perform a measurement, simply place the moisture detector on even sample surface. MOISTURE DETECTOR

A correction table for measurement correction for various types of wood and concrete is supplied with the moisture meter. H6300 may be used for other similar materials if their specific weight when completely dry is known. The moisture detector is equipped with a 16-dot LED display for exact reading of moisture in 1% steps. H6300 is offered with an alkaline or rechargeable 9 V battery. Battery charger is available as accessory. An exceptionally lightweight and compact device, H6300 is especially suited for measurement of thin samples as well as for fast and frequent measurements.

Technical specifications Input

Indication and controls

Input type Measurement range Temperature range Sample material type Temperature influence Surface-moisture interference Static-charge interference

electromagnetic 4...22% moisture content -20...100 °C up to 100 different types none insignificant insignificant

Accuracy ± 1% 0.05% from span for 1 °C 0.05% from span for 1 V fixed manual, via correction table

Material Dimensions Weight Protection class

Operating temperature Operating humidity

Battery charger can be ordered separately (see 'Accessories').

H6300 - G1

Code Feature or option G1 (3)

Supply voltage Consumption Battery state control

9 V from battery 6F22 (1) less than 3 mA automatic

plastic 65x112x22 mm max. 120 g IP44

Operating conditions 2 x 7 cm 13 mm 1s

Minimum sample area Minimum sample thickness Measurement time

(2)

Power supply

Code values

Variant

W - for wood, C - for concrete (2)

Power supply

X - none (3), G - long-life battery, H - rechargeable battery

Ask for availability! The device is supplied without battery.

Comeco Inc., P.O.Box 378, Plovdiv 4000, BULGARIA,

-10...65 °C 0...85 %RH

COMECO reserves the right of changing specifications without prior notice!

Measurement requirements

Ordering code

16 LED dots 1 membrane key

Design and materials

Measurement error Temperature drift Supply-voltage variation influence Factory calibration Correction for other material

(1)

Bargraph display Keyboard





Turn static files into dynamic content formats.