Assignment 1, Construction Design - ABPL30041

Page 1

27. POLYSTYRENE LAYER: 100MM THICK 28. POLYETHYLENE MEMBRANE: 0.2MM 29. DEPTH 0.0 - 500MM (FILL) NON DESCRIPTIVE CRUSHED ROCK CAPPED BY 30MM ASPHALT, GRAY, MOIST, SAND, MEDIUM DENSE, CEMENTED STABILISED FROM 0.3 METERS

30. DEPTH 500MM - 1000MM (FILL) CLAY, ORANGE BROWN, MOIST, SILT, TRACES OF GRAVELS, MEDIUM DENSE

31. CONCRETE SUSPENDED SLAB: 150MM WITH SL92 MESH TOP, SL92 MESH BOTTOM PLUS 2N12 TOP EACH WAY OVER EACH PIER CONCRETE GRADE: 32 MPA CONCRETE COVER: 30MM (TOP AND BOTTOM)

32. DEPTH 1000MM - 3000MM (SILTSTONE) EXTREMELY WEATHERED, YELLOW ORANGE/GRAY, VERY SILTY, GRAVELS, VERY LOW ROCK STRENGTH

33. BORED PIER AS AN ALTERNATIVE TO THE USE OF PAD FOOTINGS AND/OR STRIP FOOTINGS END BEARING PRESSURE: 450 KPA

1

LL FA

DETAIL A

34. EDGE BEAM (EB1): 300(W)x600(D)

37

1 : 10

WITH 3-L12-TM TOP AND BOTTOM PROVIDE 2N12 BARS x 1200 LONG TOP TO ALL RE-ENTRANT CORNERS UNDER MESH CONCRETE GRADE: 32 MPA

70 9

RL 41.35

2 38

3

35. BLINDING CONCRETE

4

50MM WEAK MIX CONCRETE BLINDING F'C=15 MPA

36. N12-200 CRS 'Z' BARS VERTICAL 37. PRECAST PANEL (PC5): 180MM THICK PANEL

PC4A

RL 39.00

5

WITH 150 COG AT ENDS CAST INTO FLOOR SLAB/FLOOR BEAM AND N16-400 CRS CAST IN FERRULES FOR FLOOR SLAB/FLOOR BEAM TYPE 'D' PANEL TO PANEL CAST IN PLATES 15MM MAXIMUM REBATE FOR SLAB/EDGE BEAM CONCRETE GRADE: 40 MPA

A 40

PC4B

38. 90x90x8.0 EA

7

WITH 10MM THINK END PLATE, 6MM CFW ALL AROUND

39. APRON FLASHING

39

6

SHOULD BE LAID BETWEEN METAL SHEET FOR PARAPET.AND ABOVE ROOF SHEETING

8 71

40. PARAPET CAPPING

DETAIL B B

1 : 10

41. METAL ROOFING SHEET LL FA

0.6MM BMT COLORBOND COATED STEEL SHEET, PROVIDE DRIP AT THE END OF TO ALLOW WATER TO FLOW TO THE GUTTER

41

42. CP7 WALL 150MM CONCRETE PANEL RAW FINISH

43. PRECAST PANEL (PC4): 200MM THICK PANEL

10

WITH CAST IN FERRULES FOR RA1 CONNECTION AND N16-400 CRS CAST IN FERRULES FOR FLOOR SLAB/FLOOR BEAM TYPE 'A' PANEL TO PANEL CAST IN PLATES CONCRETE GRADE: 40 MPA

12

49

43

44. WEATHER SEAL TO OPENING SASHES

45. CP1 WALL CONCRETE PANEL, MIN 10MM GAP, 64MM NOM STEEL STUD FRAME WITH SARKING, GLASS WOOL INSULATION WITH R2.5, 13MM PLASTERBOARD

46. EQUAL ANGLE (T1) 47. W.F.14: 3630x4050 POWDERCOAT ALUMINIUM FRAME 2x (1815x1050) FIXED GLASSES, 2x (1815x2100) FIXED GLASSES AND 2x (1815x900) AWNING SASH WITH TIME CLOCK SYSTEM FLY WIRE SCREEN 13

48. SF3 WALL

DETAIL C

NOM 46MM O/A ALUMINIUM COMPOSITE CLADDING SYSTEM, 2x16MM FIRE RATED & MOISTURE RESISTANT PLASTERBOARD, 90MM STUD FRAME WITH SARKING

12

1 : 20

14

45 44

49. RECTANGULAR HOLLOW SECTION (SB3): 250(V)x150x6.0 HOT DEEP GALVANISED

16

GRADE: 350 MPA WELDED TO SS2 USING 6MM SITE CONTINUOUS FILLET WELD

48

NOTES: 1. WIND BRACING (RB2): 200MM DIAMETER ROD UNIVERSAL WIND BRACING

20

RL 36.00

19

21

50. SHS (OR2): 89x89x6.0 OUTRIGGER C

SUPPORT FROM ROOF PURLINS AT MIDSPAN

17

2. PARALLEL FLANGE CHANNEL (B1): 150 PFC BOLTED TO THE CLEAT PLATE/CAST IN PLATE RJB-EP1 ON PC5 USING 2M16-8.8/S BOLTS

51. PARALLEL FLANGE CHANNEL (SB2): 230x75 HOT DEEP GALVANISED BOLTED TO SS2 USING 2M20-8.8/S BOLTS FULL DEPTH CLEAT 6MM CFW

RL 35.10

3. ROOF OVERLAP

12

47 66

FIXING SHOULD NOT BE ON LOWER SIDE BECAUSE UNDERLAPPED SHEET WOULD LEAK

49

52. PARALLEL FLANGE CHANNEL (SS2): 230x75 HOT DEEP GALVANISED BOLTED TO SB2 USING 2M20-8.8/S BOLTS FULL DEPTH CLEAT 6MM CFW ALL AROUND TYPICAL

4. UNEQUAL ANGLE (RA1): 150(V)x90x10 UA 15

5. RECTANGULAR HOLLOW SECTION (DH2): 250(V)x150x5.0 RHS

53. W.G.17: 3630x2150MM POWDERCOAT ALUMINIUM FRAME

46

GRADE: 350 MPA WELDED TO 10MM CLEAT AND END PLATE, THEN BOLTED TO CAST IN PLATE USING 2M20-8.8/S BOLTS

2x (1815x1250) FIXED GLASSES AND 2x (1815x900) AWNING SASH WITH TIME CLOCK SYSTEM FLY WIRE SCREEN

50

54. GALVANISED MS PLATE: 10MM THK

6. C CHANNEL (BP1): 2/C20024

51

SNUG STRUT AT MID SPAN BOLTED TO THE CLEAT PLATES OF RA1

5 DEGREE FALL AWAY FROM BUILDING

55. PAD FOOTING (F1): 1500x1500 52 22

7. SAFETY MESH GALVANISED WIRE SAFETY MESH

DEPTH 750MM WITH N12-200 CRS AT THE BOTTOM ON BOTH DIRECTIONS CONCRETE GRADE: 25 MPA

56. MORTAR

8. CEILING PRIMARY RAILS

JOINT THICKNESS = 10MM MORTAR QUALITY = M3

23

AT 1200MM CENTRES HUNG ON 5MM GALVANISED ROD, ACCURATELY LEVELLED WITH SUSPENSION CLIP AT 1200MM CENTRES

57. POLYETHYLENE FOAM BACKER ROD 24

9. ROOF SPACER TO BE FIXED ON TOP OF PURLINS BELOW ROOF SHEET

58. SF2 WALL

42

18

90MM THK X 90MM HIGH FACE BLOCK WORK (STRETCHER BOND), 50MM GAP, 92MM NOM STEEL STUD FRAME WITH SARKING, 2x16 FIRE RATED PLASTERBOARD

20

31

10. SUSPENDED CEILING

59. CAVITY: 50MM

54

TO BE FILLED WITH 20 MPA WATERPROOF CONCRETE TO FINISHED GROUND LEVEL

11. C CHANNEL (P2): C20024 - 120 MAX. CRS

60. FIXING PLATE

NO LAP REQUIRED, 1 ROW OF BRIDGING PER BAY BOLTED TO THE CLEAT PLATE OF B1

53

12. CARPET - TILES (C2B)

4M10-4.6/S BOLTS, 8MM THICK CAP PLATE, 6MM CFW ALL AROUND

57

RC&D_ (RUGS CARPET BY DESIGN) HL 630/ MOD 750

13. PARALLEL FLANGE CHANNEL (WH2): 200 PFC BOLTED TO CAP PLATE OF C1 USING 2M20-8.8/S BOLTS

GRADE 350 MPa TEMPORARY BRACING IS REQUIRED BEFORE AT LEAST UNTIL PERMANENT BRACING OR BRICKLAYER IS ERECTED

58

27

RL 31.80

61. SHS 89x89x6.0 (SC4)

56

28

62. CONCRETE INFILL

14. PLASTERBOARD FOR CEILING 10 MM CD FLUSH PLASTERBOARD

TO BE PLACED AFTER PANEL IS ERECTED F'C=32 MPa

29

15. THERMAL INSULATION UNDER FIRST FLOOR SLAB 30

16. CONDEK: 1.0MM SACRIFACIAL FORMWORK FOR FIRST FLOOR CONCRETE SLAB

17. LIVE END TOP STRESING PAN, GROUT TUBE

63. STRIP FOOTING (SF2): 400(W)x600(D)

60

KINGSPAN 'KOOLTHERM' K10 FM SOFFIT BOARD', 50MM THICK, CFC/HCFC FREE RIGID INSULATION

4-L12-TM AT THE TOP AND BOTTOM CONCRETE GRADE: 25 MPA

68

33

62

RL 31.30

63

25 61

RL 30.80

4N12 DEFORMED BARS, 150MM LONG x 50MM COG, FSBW TO CAST IN PLATE TYPICAL

65. PAD FOOTING (F2): 1200x1200

67

18. LIVE END ANCHORAGE

64. CAST IN PLATE: 12MM THICK

DEPTH 750MM WITH SL81 AT THE BOTTOM CONCRETE GRADE: 25 MPA

GROUT TUBE

19. DEAD END

64

ONION END WITH SPACER BAR

65

32

20. POST TENSIONING TENDON

66. N16-400 CRS CAST IN FERRULES FOR FLOOR SLAB 67. THERMAL INSULATION FOR WALL

69

59

CSR BRADFORD 'GOLD' WALL BATTS, R2.5 90MM THICK

21. POST TENSIONED CONCRETE SUSPENDED SLAB: 450MM AND 220MM

68. SARKING

73

CSR BRADFORD 'BREATHERFOIL ANTIGLARE' VAPOUR PERMEABLE SARKING

69. BLOCKWORK: 90x90x390

CONCRETE GRADE: 40 MPA CONCRETE COVER: 30MM (TOP AND BOTTOM)

WEEP HOLES, ARTICULATION JOINT, WALL TIES, FLASHING

36

70. RA1: STANDARD PANEL CLIPS TO PANEL MANUFACTURER'S DETAIL

22. SF6 13MM PLASTERBOARD ON MOISTURE RESISTANT, 90MM STUD FRAME, 13MM PLASTERBOARD ON MOISTURE RESISTANT

34

DETAIL AT 1500 MAX CTS.

23. ALUCOBOND ALUMINIUM COMPOSITE 46MM THICK, SOLID LIGHT GRAY 104 SURF TOP HAT, 10MM JOINT

71. PURLIN BRIDGING 72. LINE OF INFLUENCE 73. GEOTHERMAL TRENCH

35

24. CONCRETE BEAM (1BB4): 2400(W) x 450(D)

72

CONCRETE GRADE: 40 MPA CONCRETE COVER: 30MM (TOP AND BOTTOM)

25. FLOOR VINYL (V1B) SILVER COLOUR, ARMSTRONG 'CONTOUR', 2.0 MM THICK, COVED 100MM UP WALLS

26. INTERNAL BEAM (IB1): 300(W)x600(D) WITH 3-L12-TM TOP AND BOTTOM CONCRETE GRADE: 32 MPA

TIMBER STUD FRAMING 90x35 MGP10 GENERALLY 90x45 MGP10 PLATE STUDS AT CORNER AND OPENING 90x45 MGP10 TWO ROWS NOGGING 90x35 MGP10, 3 ROWS FOR WALL ABOVE 2700

DESIGN LIVE LOAD 4 kN/m2 FOR STAIR AND LANDINGS ALL OTHER AREAS HAVE BEEN DESIGNED FOR A MAXIMUM FLOOR LIVE LOAD OF 3kN/m2 AND 1kN/m2

CONCRETE WITHOUT REINFORCEMENT

SITE CLASSIFICATION 'M'

CARPET TILES (C2B)

ALL EDGE EAMS, PAD FOOTINGS AND STRIP FOOTING TO HAVE FOLLOWING ALLOWABLE BEARING PRESSURE: ISOLATED PADS: 350 kPa CONTINUOUS STRIPS: 300 kPa

FLOOR VINYL (V1B)

GROUNDWORKS - BOREHOLE #4 FILL - NON DESCRIPTIVE CRUSHED ROCK FILL - CLAY

SILTSTONE

CONSTRUCTION DESIGN ABPL30041 SEMESTER 1, 2018

ARCHITECT: CLARKE HOPKINS CLARKE

DRAWN BY: NESIA CAHYONO, 813807 SCALE 1:20

PROJECT: BIO21 SCIENCE SUB SCHOOL UNIVERSITY OF MELBOURNE PARKVILLE CAMPUS

@A0