Gas Pressure Regulator RMG 370
RMG 370
Pilot-operated Gas Pressure Regulator According to DIN EN 334 ( operating with auxiliary energy from the inlet pressure range) with Incorporated Direct-acting SSV According to DIN EN 334 / 14382 Application
Device for offtake stations in gas transmission as well as commercial and industrial facilities Excellent for dynamic regulating lines (i.e., gas furnaces) Diaphragm assembly with inlet pressure compensation optionally with Safety Relief Valve (SRV) or safety diaphragm Optionally available with Safety Shut-off Valve (SSV) with in-line flow Noise reduction optional Very easy to maintain due to exchangeable functional units (cartridge assembly) Suitable for non-aggressive gases, other gases on enquiry
Tables outlet pressure ranges, valve specifications, setting range and accuracy class Technical description RMG_370_CN_2009_05 RMG_370_DE_2010_04 RMG_370_EN_2009_05
CE-registration according to PED
RMG_370_PL_2009_05 RMG_370_RU_2010_11
Max. admissible pressure PS
= 20 bar
Max. inlet pressure pu max
up to 20 bar
RMG_370_20_DE_2010_07
Outlet pressure range:
Wd 20 mbar up to 4 bar
RMG_370_20_EN_2010_07
Class of lock-up pressure zone
SZ 2.5
SSV setting range
Wdo 25 mbar up to 5.2 bar
Operation & maintenance, spare parts
RMG_370_20_RU_2010_07
Wdu 5 mbar up to 400 mbar SRV setting range
Wd 15 up to 90 mbar above pds
Connection
DIN flange PN 16 or Class 150 according to ANSI 16.5, DN 25 thru DN 150 Other flange types on enquiry
All mechanical components of this device are without ignition sources. As such, they are not subject to ATEX 95 (94/9/EC). All electrical components used with this device fulfil the ATEX requirements. To top RMG Regel + Messtechnik GmbH | Osterholzstrasse 45 | D-34123 Kassel, Germany | Phone +49 (0)561 5007-0 | rmg@honeywell.com | Imprint / Legal Notice | Privacy Statement