/flame-arrester-rmg-9

Page 1

RMG 933-A

Flame arrester RMG 933-A Pipe Protection Protection System

-Tube protection against deflagration -Tube protection against detonation

Approval

EC-type examination certificate based upon Directive 94/9/EG, according to ATEX 95 and EN 12874

Protection

Gas/air or steam/air mixtures of the explosion groups: – I (methane) NSW ≥ 1.14 mm – IIA (D) NSW ≥ 0.90 mm – IIB3 (C) NSW ≥ 0.65 mm – IIC (B) NSW ≥ 0.50 mm

Pipe Sizes

DN25, DN32, DN40, DN50, DN65, DN80 1", 11?4", 11?2", 2", 21?2", 3"

Connection Standards

-DIN 2501 PN10 -ANSI B16.5 – 150 RF

Materials

Strip protection: Stainless steel, special alloys Rust cage: Stainless steel, special alloys Body: Carbon steel, stainless steel, Special alloys

Coating

Optional

Temperature Sensor

Resistance thermometer with ignition protection type - Inherently safe (E Ex i) - Pressure-resistant enclosure (E Ex d) To top

RMG Regel + Messtechnik GmbH | Osterholzstrasse 45 | D-34123 Kassel, Germany | Phone +49 (0)561 5007-0 | rmg@honeywell.com | Imprint / Legal Notice | Privacy Statement