THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
525 COCHRANE DRIVE MARKHAM ON
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
COVER SHEET
PROJECT NO:
CONSTRUCTION DRAWINGS DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 N.T.S. DRAWING NO:
A0.00
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
COVER SHEET
PROJECT NO:
CONSTRUCTION DRAWINGS DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 N.T.S. DRAWING NO:
A0.01
NORTH
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
LEGEND
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
SITE PLAN
PROJECT NO:
CONSTRUCTION DRAWINGS
SUSTAINABILITY A
GREEN ROOF
E
RAIN WATER HARVESTING
DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 1:250 B C
D
SOLAR PANEL PERVIOUS PAVER AND CONCRETE WITH HIGH SRI LOW-E GLASS
F
G
TOILETS WITH GRAY WATER SYSTEM XERISCAPING AND DECIDUOUS TREES FACING EAST-WEST
DRAWING NO:
A1.01
NORTH
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
GROUND FLOOR
PROJECT NO:
CONSTRUCTION DRAWINGS
SUSTAINABILITY A
GREEN ROOF
E
RAIN WATER HARVESTING
B
SOLAR PANEL
F
TOILETS WITH GRAY WATER SYSTEM
C
PERVIOUS PAVER AND CONCRETE WITH HIGH SRI
G
XERISCAPING AND DECIDUOUS TREES FACING EAST-WEST
D
LOW-E GLASS
DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 1:150 DRAWING NO:
A2.01
NORTH
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
SECOND FLOOR
PROJECT NO:
CONSTRUCTION DRAWINGS
SUSTAINABILITY A
GREEN ROOF
E
RAIN WATER HARVESTING
B
SOLAR PANEL
F
TOILETS WITH GRAY WATER SYSTEM
C
PERVIOUS PAVER AND CONCRETE WITH HIGH SRI
G
XERISCAPING AND DECIDUOUS TREES FACING EAST-WEST
D
LOW-E GLASS
DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 1:150 DRAWING NO:
A2.02
NORTH
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
ROOF PLAN
PROJECT NO:
CONSTRUCTION DRAWINGS DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
SUSTAINABILITY A
GREEN ROOF
E
RAIN WATER HARVESTING
B
SOLAR PANEL
F
TOILETS WITH GRAY WATER SYSTEM
C
PERVIOUS PAVER AND CONCRETE WITH HIGH SRI
G
XERISCAPING AND DECIDUOUS TREES FACING EAST-WEST
D
LOW-E GLASS
August 15th, 2019 1:150 DRAWING NO:
A2.03
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
ELEVATIONS
PROJECT NO:
CONSTRUCTION DRAWINGS
SUSTAINABILITY A
GREEN ROOF
E
DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
RAIN WATER HARVESTING
August 15th, 2019 1:150 B C
D
SOLAR PANEL PERVIOUS PAVER AND CONCRETE WITH HIGH SRI LOW-E GLASS
F
G
TOILETS WITH GRAY WATER SYSTEM XERISCAPING AND DECIDUOUS TREES FACING EAST-WEST
DRAWING NO:
A3.01
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
ELEVATIONS
PROJECT NO:
CONSTRUCTION DRAWINGS
SUSTAINABILITY A
GREEN ROOF
E
RAIN WATER HARVESTING
B
SOLAR PANEL
F
TOILETS WITH GRAY WATER SYSTEM
C
PERVIOUS PAVER AND CONCRETE WITH HIGH SRI
G
XERISCAPING AND DECIDUOUS TREES FACING EAST-WEST
D
LOW-E GLASS
DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 1:150 DRAWING NO:
A3.02
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
BUILDING SECTIONS
PROJECT NO:
CONSTRUCTION DRAWINGS
SUSTAINABILITY A
GREEN ROOF
E
RAIN WATER HARVESTING
B
SOLAR PANEL
F
TOILETS WITH GRAY WATER SYSTEM
C
PERVIOUS PAVER AND CONCRETE WITH HIGH SRI
G
XERISCAPING AND DECIDUOUS TREES FACING EAST-WEST
D
LOW-E GLASS
DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 1:150 DRAWING NO:
A4.01
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
WALL SECTIONS
PROJECT NO:
CONSTRUCTION DRAWINGS DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 1:25 DRAWING NO:
A4.02
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
DETAILS
PROJECT NO:
CONSTRUCTION DRAWINGS DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 AS SHOWN DRAWING NO:
A5.01
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
MILLWORK
PROJECT NO:
CONSTRUCTION DRAWINGS DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 AS SHOWN DRAWING NO:
A6.01
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
SCHEDULES AND LEGENDS
PROJECT NO:
CONSTRUCTION DRAWINGS DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 1:50 DRAWING NO:
A7.01
THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL INFORMATION SHOWN HEREIN AND SHALL REPORT ERRORS AND OMISSIONS TO THE DESIGNER. THIS DRAWING IS THE PROPERTY OF CENTENNIAL COLLEGE AND SHALL NOT BE REPRODUCED WITHOUT WRITTEN AUTHORIZATION. THIS DRAWING MUST NOT BE SCALED.
PA ARCHITECTS (647) 814 - 6182 17 DUNDONALD ST. TORONTO, ON M4Y 1K3, CANADA
NOTES
DRAWINGS ISSUED ISSUED
DATE
PROJECT NAME:
COOM./ INDUSTRIAL BUILDING 525 COCHRANE DR. MARKHAM, ON DRAWING NAME:
SCHEDULES AND NOTES
PROJECT NO:
CONSTRUCTION DRAWINGS DRAWN BY:
CHECKED BY:
PEDRO A.
HENRY LEVY
DATE:
SCALE:
August 15th, 2019 1:50 DRAWING NO:
A7.02