ED 45 - 439
Packaged Air Conditioners Floor Standing Type FV(P)G-A Series — Cooling Only (50Hz) —
ED45-439
Packaged Air Conditioners Floor Standing Type FV(P)G-A Series – Cooling Only (50Hz) – Model Series Direct Air Blow Type Duct Connection Type
FVG05AV2 FVG08AV2 FVG10AV2 FVPG10AY1 FVPG15AY1 FVPG20AY1
RG125AUY1 RUG08AUY1 RUG10AUY1 RUG10AUY1 RUG08AUY1×2 RUG10AUY1×2
1. Power Supply and Nomenclature............................................................1 1.1 Power Supply ...........................................................................................1 1.2 Nomenclature ...........................................................................................1
2. External Appearance...............................................................................2 3. Specifications ..........................................................................................3 4. Dimensions .............................................................................................5 4.1 Indoor Unit................................................................................................5 4.2 Outdoor Unit .............................................................................................8
5. Piping Diagrams....................................................................................10 5.1 For Each Unit .........................................................................................10 5.2 Unit Combination....................................................................................12
6. Wiring Diagrams....................................................................................13 6.1 Indoor Unit..............................................................................................13 6.2 Outdoor Unit ...........................................................................................15
7. Electric Characteristics..........................................................................16 7.1 Indoor Unit..............................................................................................16 7.2 Outdoor Unit ...........................................................................................16
8. Capacity Tables (Cooling Capacity)......................................................17 9. Operation Limit......................................................................................20 10.Fan Performance ..................................................................................21 11.Sound Level ..........................................................................................22 11.1 Overall ....................................................................................................22
12.Installation .............................................................................................23 12.1 Indoor Unit·····FVG05AV2, FVG08AV2, FVG10AV2 FVPG10AY1, FVPG15AY1, FVPG20AY1......................23 12.2 Outdoor Unit·····RG125AUY1 .................................................................29 12.3 Outdoor Unit·····RUG08AUY1, RUG10AUY1 .........................................43 Table of Contents
i
ED45-439
Power Supply and Nomenclature
1. Power Supply and Nomenclature 1.1
Power Supply Indoor Unit Direct Air Blow Type
1.2
Outdoor Unit
Power Supply
Duct Connection Type
FVG05AV2
—
RG125AUY1
FVG08AV2
—
RUG08AUY1
FVG10AV2
FVPG10AY1
RUG10AUY1
—
FVPG15AY1
RUG08AUY1×2
—
FVPG20AY1
RUG10AUY1×2
3φ, 380-415V, 50Hz
Nomenclature Indoor Unit
F V (P) G
1 0
A
Y 1 Power Supply Symbol V2 : 1φ, 220~240V, 50Hz Y1 : 3φ, 380~415V, 50Hz Major design category
Rated cooling capacity (Horse power) Floor standing indoor unit FVG : Direct Air Blow Type FVPG : Duct Connection Type Outdoor Unit
R (U) G
1 0
A U
Y 1 Power Supply Symbol Major design category
Rated cooling capacity (Horse power) 125 : (kW×10) Outdoor unit
FV(P)G-A Series (50Hz)
1
External Appearance
ED45-439
2. External Appearance Indoor Unit
FVG05A
FVG08A
FVG10A
FVPG10A
FVPG15A
FVPG20A
Outdoor Unit
RG125AU
2
RUG08AU
RUG10AU
FV(P)G-A Series (50Hz)
ED45-439
Specifications
3. Specifications Direct Air Blow Type Model
Indoor Unit
FVG05AV2
FVG08AV2
FVG10AV2
Outdoor Unit
RG125AUY1
RUG08AUY1
RUG10AUY1
14.3 / 14.1 48,800 / 48,000 12,300 / 12,100
380~415V, 50Hz, 3 Phase, 4 Wires 24.2 / 23.9 82,600 / 81,500 20,800 / 20,600
30.4 / 29.9 104,000 / 102,000 26,100 / 25,700
FVG05AV2
FVG08AV2
FVG10AV2
Power Supply ∗1
Cooling Capacity (1)/(2)
kW Btu/h kcal/h
Indoor Unit Casing Color Air Flow Rate (H) Fan Drive Sound Level (H/L) Dimensions Machine Weight Operation Range
∗2 H×W×D
m³/min cfm
42 1,485
dBA mm kg °CWB
59 / 50 1,870×750×510 90
Outdoor Unit
Refrigerant Oil
Type Motor Output Model Charge
Refrigerant Charge (R22) ∗2 H×W×D
Sound Level Dimensions Machine Weight Operation Range Refrigerant Piping
Indoor Unit Outdoor Unit
Liquid Gas Liquid Gas
Indoor Unit Outdoor Unit Max. Interunit Piping Length Max. Installation Level Difference Heat Insulation Drain Connections
Note:
FV(P)G-A Series (50Hz)
61 / 52 1,870×1,170×510 143
RUG08AUY1
RUG10AUY1
3.75
9 4.0 6.1 (Charged for 5m)
L
1.5
Ivory White Hermetically Sealed Scroll Type 7.5 SUNISO4GSDID-K 4.0
kg
2.8 (Charged for 5m)
5 (Charged for 5m)
kW
80 2,824
RG125AUY1
Casing Color Compressor
Ivory White 63 2,225 Direct Drive 3 Speed 60 / 51 1,870×950×510 107 14 to 25
dBA
57
60
61
mm kg °CDB mm mm mm mm mm mm m m
1,215×880×370 110
1,220×1,280×690 177 21 to 52 φ 12.7 (Brazing) φ 25.4 (Brazing) φ 12.7 (Flare) φ 25.4 (Brazing) FPS1B — 50 (Equivalent Length 70m) 30 Both Liquid and Gas Pipes
1,440×1,280×690 190
φ 9.52 (Brazing) φ 19.1 (Brazing) φ 9.52 (Flare) φ 19.1 (Flare) —
1. ∗1 Nominal cooling capacities are based on the following conditions: (1) Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5m (horizontal). (2) Return air temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5m (horizontal). 2. ∗2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
φ 15.9 (Brazing) φ 31.8 (Brazing) φ 15.9 (Flare) φ 31.8 (Brazing) —
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
3
Specifications
ED45-439
Duct Connection Type Model
Indoor Unit
FVPG10AY1
FVPG15AY1
FVPG20AY1
Outdoor Unit
RUG10AUY1
RUG08AUY1×2
RUG10AUY1×2
30.4 / 29.9 104,000 / 102,000 26,100 / 25,700
380~415V, 50Hz, 3 Phase, 4 Wires 47.6 / 46.9 162,500 / 160,000 40,900 / 40,300
59.5 / 58.6 203,100 / 200,000 51,200 / 50,400
FVPG10AY1
FVPG15AY1
FVPG20AY1
Power Supply ∗1
Cooling Capacity (1)/(2)
kW Btu/h kcal/h
Indoor Unit Casing Color Air Flow Rate (H) Fan
Drive Ext. Static Pressure ∗2 H×W×D
Sound Level Dimensions Machine Weight Operation Range
m³/min cfm
80 2,824
Pa(mmH2O) dBA mm kg °CWB
61 1,740×1,170×510 150
Outdoor Unit
Refrigerant Oil
Type Motor Output Model Charge
Refrigerant Charge (R22) ∗2 H×W×D
Sound Level Dimensions Machine Weight Operation Range Refrigerant Piping
Indoor Unit Outdoor Unit
Liquid Gas Liquid Gas
Indoor Unit Drain Connections Outdoor Unit Max. Interunit Piping Length Max. Installation Level Difference Heat Insulation
Note:
4
63 1,870×1,470×720 240
RUG08AUY1×2
RUG10AUY1×2
9
9.0×2 4.0×2 6.1×2 (Charged for 5m)
L
4.0
Ivory White Hermetically Sealed Scroll Type 7.5×2 SUNISO4GSDID-K 4.0×2
kg
6.1 (Charged for 5m)
5.0×2 (Charged for 5m)
kW
172 6,075
RUG10AUY1
Casing Color Compressor
Ivory White 120 4,240 Belt Drive 150 (15) 62 1,870×1,170×720 180 14 to 25
dBA
61
60 ∗3
61 ∗3
mm kg °CDB mm mm mm mm mm mm m m
1,440×1,280×690 190
(1,220×1,280×690)×2 177×2 21 to 52 φ 12.7 (Brazing)×2 φ 25.4 (Brazing)×2 φ 12.7 (Flare)×2 φ 25.4 (Brazing)×2 FPS1B — 50 (Equivalent Length 70m) 30 Both Liquid and Gas Pipes
(1,440×1,280×690)×2 190×2
φ 15.9 (Brazing) φ 31.8 (Brazing) φ 15.9 (Flare) φ 31.8 (Brazing) —
1. ∗1 Nominal cooling capacities are based on the following conditions: (1) Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5m (horizontal). (2) Return air temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5m (horizontal) 2. ∗2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3. ∗3 Specification for outdoor unit is for a single unit only.
φ 15.9 (Brazing)×2 φ 31.8 (Brazing)×2 φ 15.9 (Flare)×2 φ 31.8 (Brazing)×2 —
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
FV(P)G-A Series (50Hz)
ED45-439
Dimensions
4. Dimensions 4.1
Indoor Unit
Direct Air Blow Type FVG05A 750
LIQUID PIPE CONN. φ9.5 C1220T BRAZING GAS PIPE CONN. φ19.1 C1220T BRAZING DRAIN OUTLET FPS IB FEMALE SCREW POWER SUPPLY & CONTROL WIRE INTAKE DIGITAL REMOTE CONTROLLER
510
1 2 3 4 5
750
330
510
740
1870
1870
35
370
5
150
1
50
100 100
2 4
70
250
325
3
720
474
SDR3150095
FVG08A 950
LIQUID PIPE CONN. φ12.7 C1220T BRAZING GAS PIPE CONN. φ25.4 C1220T BRAZING DRAIN OUTLET FPS IB FEMALE SCREW POWER SUPPLY & CONTROL WIRE INTAKE DIGITAL REMOTE CONTROLLER
510
1 2 3 4 5
950
370
330
510
740
1870
1870
35
5
150
1
50
3
70
250
325
4
100 100
2
FV(P)G-A Series (50Hz)
920
474
SDR3150096
5
Dimensions
ED45-439
FVG10A 1170
LIQUID PIPE CONN. φ15.9 C1220T BRAZING GAS PIPE CONN. φ31.8 C1220T BRAZING DRAIN OUTLET FPS IB FEMALE SCREW POWER SUPPLY & CONTROL WIRE INTAKE DIGITAL REMOTE CONTROLLER
510
1 2 3 4 5
1170
370
330
510
740
1870
1870
35
5
150
50
1 100 100
2 4
70
250
325
3
1140
SDR3150097
Duct Connection Type FVPG10A 1 2 3 4 5
1170 334
140
334
146
LIQUID PIPE CONN. φ15.9 C1220T BRAZING GAS PIPE CONN. φ31.8 C1220T BRAZING DRAIN OUTLET FPS IB FEMALE SCREW POWER SUPPLY & CONTROL WIRE INTAKE DIGITAL REMOTE CONTROLLER
510
510
394
292
177
31
40
216
510
1170
177
571
28
390
5
250
250
50
290
40
177
724
1740
1670
290
1
325
50
70
150
250
100 100
2 4
1140
6
474
3
SDR3150098
FV(P)G-A Series (50Hz)
ED45-439
Dimensions
FVPG15A 1170 398
1 2 3 4 5
295
LIQUID PIPE CONN. φ12.7 C1220T BRAZING GAS PIPE CONN. φ25.4 C1220T BRAZING DRAIN OUTLET FPS IB FEMALE SCREW POWER SUPPLY DIGITAL REMOTE CONTROLLER
720
602
344
52
477
1210
720
1170
510
10
205
915
1870
1800
50
5
1
100
2
325
178 100 100
150
50
70
4
1144
3
682
SDR3150099
FVPG20A 1470 474
438
1 2 3 4 5
LIQUID PIPE CONN. φ15.9 C1220T BRAZING GAS PIPE CONN. φ31.8 C1220T BRAZING DRAIN OUTLET FPS IB FEMALE SCREW POWER SUPPLY DIGITAL REMOTE CONTROLLER
720
602
407
52
558
1510
720
1470
510
10
237
915
1870
1800
50
5
1
100
325
1444
FV(P)G-A Series (50Hz)
70
70
50
4
178 100 100
2 150
682
3
SDR3150100
7
Dimensions
4.2
ED45-439
Outdoor Unit
RG125AU 84
HOLE FOR ANCHOR BOLT 4-M12
30
38
GAS PIPE CONN. φ19.1 FLARE LIQUID PIPE CONN. φ9.5 FLARE SERVICE PORT (IN THE UNIT) GROUNDING TERMINAL. M5(IN SWITCH BOX) REFRIGERANT PIPING INTAKE POWER SUPPLY WIRING INTAKE. ø 34 KNOCK HOLE CONTROL WIRING INTAKE. ø 34 KNOCK HOLE DRAIN OUTLET. ø 26
30
35
395
370
1 2 3 4 5 6 7 8
146
584
150
880
30
4 3 2 1215
1
7
NAME PLATE
84
568
90
6 49 95
49 95
24
60
538
5
14
14
11
275
61
40
11
102
67 115
137
KNOCK HOLE FOR LOWER PIPING
8
391
SDR3150101
RUG08AU
726
4-φ15 FOR ANCHOR BOLTS
700
1000 (PITCH OF ANCHOR BOLTS)
1 2 3 4 5 6
LIQUID PIPE CONN. WITH STOP VALVE φ12.7 C1220T FLARE GAS PIPE CONN.WITH STOP VALVE φ25.4 C1220T BRAZING EARTH TERMINAL M5 IN THE EL. BOX ASS'Y WIRING INTAKE (SIDE) φ62 REFRIGERANT PIPING CONN. (SIDE) KNOCK OUT HOLE REFRIGERANT PIPING CONN. (BOTTOM) KNOCK OUT HOLE
1290
5
220 165
165
52 177 156
2
76
80
70
1
90
1220
4
70
1220
3 4
202 32
20
NAME PLATE 1280
690
80
80 750
97
6 110 54
32
SDR3150102
8
FV(P)G-A Series (50Hz)
ED45-439
Dimensions
RUG10AU
700
4-φ15 FOR ANCHOR BOLTS
726
1000 (PITCH OF ANCHOR BOLTS)
1 2 3 4 5 6
LIQUID PIPE CONN. WITH STOP VALVE φ15.9 C1220T FLARE GAS PIPE CONN.WITH STOP VALVE φ31.8 C1220T BRAZING EARTH TERMINAL M5 IN THE EL. BOX ASS'Y WIRING INTAKE (SIDE) φ62 REFRIGERANT PIPING CONN. (SIDE) KNOCK OUT HOLE REFRIGERANT PIPING CONN. (BOTTOM) KNOCK OUT HOLE
1290
1
5
2
80
76
220 20
165
165
NAME PLATE 202
80
80
1280
6
750 32
97
110
54
690
70
4
52
32
1440
4
177 156
70
90
1440
3
SDR3150103
FV(P)G-A Series (50Hz)
9
Piping Diagrams
ED45-439
5. Piping Diagrams 5.1
For Each Unit
5.1.1
Indoor Unit
FVG05AV2 FVG08AV2 FVG10AV2 FVPG10AY1
SDR3160059
FVPG15AY1 FVPG20AY1
SDR3160060
10
FV(P)G-A Series (50Hz)
ED45-439
5.1.2
Piping Diagrams
Outdoor Unit
RG125AUY1
SDR3160061
RUG08AUY1 RUG10AUY1
SDR3160062
FV(P)G-A Series (50Hz)
11
Piping Diagrams
5.2
ED45-439
Unit Combination
FVG05AV2, RG125AUY1
Refrigerant piping (Liquid, Gas)
Refrigerant Piping RG125AUY1 IndoorLiquid φ9.52 Outdoor Gas φ19.1
FVG08AV2, RUG08AUY1 FVG10AV2, RUG10AUY1
Refrigerant piping (Liquid, Gas)
Refrigerant Piping RUG08AUY1 RUG10AUY1 Liquid φ15.9 φ12.7 IndoorGas φ31.8 φ25.4 Outdoor
FVPG10AY1, RUG10AUY1
Refrigerant piping (Liquid, Gas)
Refrigerant Piping RUG10AUY1 Liquid φ15.9 IndoorGas φ31.8 Outdoor
FVPG15AY1, RUG08AUY1×2 FVPG20AY1, RUG10AUY1×2
Refrigerant piping (Liquid, Gas)
Refrigerant Piping RUG08AUY1 RUG10AUY1 Liquid φ15.9 φ12.7 IndoorGas φ31.8 φ25.4 Outdoor
Refrigerant piping (Liquid, Gas)
12
FV(P)G-A Series (50Hz)
ED45-439
Wiring Diagrams
6. Wiring Diagrams 6.1
Indoor Unit
FVG05AV2 FVG08AV2
SDR3010185
FVG10AV2
SDR3010186
FV(P)G-A Series (50Hz)
13
Wiring Diagrams
ED45-439
FVPG10AY1
SDR3010187
FVPG15AY1 FVPG20AY1
SDR3010170A
14
FV(P)G-A Series (50Hz)
ED45-439
6.2
Wiring Diagrams
Outdoor Unit
RG125AUY1
SDR3010189
RUG08AUY1 RUG10AUY1
SDR3010190
FV(P)G-A Series (50Hz)
15
Electric Characteristics
ED45-439
7. Electric Characteristics 7.1
Indoor Unit Unit
Power supply
EFM
Model Type
Volts-Ph-Hz
Voltage range
FVG05A FVG08A V2 FVG10A FVPG10A FVPG15A FVPG20A
Y1
220-1-50 230-1-50 240-1-50
Max. 264V Min. 198V
380-3-50 400-3-50 415-3-50
Max. 456V Min. 342V
Symbols : MCA : Min. Ckt (Circuit) Amps (A) TOCA : Total Overcurrent Amps (A) MFA : Max. Fuse Amps (A) (See note 4) EFM : Evaporator Fan Motor FLA : Full Load Amps (A) kW : Fan Motor Rated Output (kW)
7.2
MCA
TOCA
MFA
kW
FLA
—
—
—
0.375
4.5
—
—
—
0.55
6.2 9
—
—
—
0.375 + 0.375
4.4
3.6
15
1.5
3.5
6.1
5.0
15
2.2
4.9
10.0
8.0
30
3.7
8.0
Note : 1. TOCA means the total value of each OC set. 2. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. 3. Maximum allowable voltage unbalance between phases is 2%. 4. MCA / MFA (FD) MCA = 1.25 × FLA MFA 4 × FLA (Min. 15A) (Next lower standard fuse rating) 5. Select wire size based on the larger value of MCA. 6. Instead of fuse, use Circuit Breaker.
Outdoor Unit Unit
Power supply
Model Volts-Ph-Hz RG125AUY1
Voltage range
380-3-50 400-3-50 415-3-50
RUG08AUY1 380/220-3-50 400/230-3-50 415/240-3-50
Max. 456V Min. 342V
RUG10AUY1
Symbols : MCA : Min. Ckt (Circuit) Amps (A) TOCA : Total Overcurrent Amps (A) MFA : Max. Fuse Amps (A) (See note 5) LRA : Locked Rotor Amps (A) RLA : Rated Load Amps (A) CFM : Condenser Fan Motor : Full Load Amps (A) FLA : Fan Motor Rated Output (kW) kW
16
Comp. (each)
CFM (each)
Starting Method
Direct
MCA
TOCA
MFA
LRA
RLA
kW
FLA
10.4
9.5
15
62
7.2
0.075 + 0.06
0.7 + 0.7
18.6
20.5
30
112 117 122
12.4 12.2 12.9
0.19 + 0.23
1.2 + 1.3
24.4
26.5
40
148 155 161
16.5 15.8 17.5
0.19 + 0.23
1.2 + 1.3
Note : 1. RLA is based on the following conditions. Indoor temp. 27°CDB / 19.5°CWB Outdoor temp. 35°CDB 2. TOCA means the total value of each OC set. 3. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. 4. Maximum allowable voltage unbalance between phases is 2%. 5. MCA / MFA MCA = 1.25 × RLA + ea. FLA MFA 2.25 × RLA + ea. FLA (Next lower standard fuse rating : Min. 15A) 6. Select wire size based on the larger value of MCA or TOCA. 7. Instead of fuse, use Circuit Breaker.
FV(P)G-A Series (50Hz)
ED45-439
Capacity Tables (Cooling Capacity)
8. Capacity Tables (Cooling Capacity) FVG05AV2+RG125AUY1 Indoor AFR 21 EDB EWB (BF) (˚C) (˚C) TC SHC 14.0 16.0 42 18.0 19.0 (0.15) 19.5 22.0 24.0
20 22 25 27 27 30 32
13.4 14.3 15.3 15.9 16.2 17.5 18.7
9.5 9.8 10.1 10.4 10.6 10.8 11.0
Outdoor temperature (˚CDB) 25 PI 3.21 3.32 3.44 3.50 3.53 3.70 3.85
TC SHC 13.0 13.9 14.9 15.4 15.6 16.9 18.0
Symbols : AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity PI : Power input (Comp. + Outdoor fan motor)
9.3 9.6 9.9 10.0 10.4 10.6 10.8
30 PI 3.43 3.55 3.68 3.74 3.78 3.96 4.13
(m3/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
TC SHC 12.4 13.4 14.2 14.8 15.0 16.3 17.4
8.9 9.3 9.6 9.8 10.0 10.2 10.6
35 PI 3.67 3.80 3.94 4.02 4.05 4.26 4.43
TC SHC 11.9 12.7 13.7 14.1 14.3 15.5 16.6
8.7 8.9 9.4 9.5 9.8 9.8 10.2
40 PI 3.86 3.99 4.16 4.24 4.27 4.50 4.70
TC SHC 11.3 12.2 13.0 13.5 13.7 14.9 15.9
8.4 8.7 9.1 9.2 9.5 9.6 10.0
45 PI 3.99 4.15 4.32 4.42 4.45 4.70 4.90
TC SHC 10.8 11.5 12.4 12.8 13.0 14.1 15.1
8.1 8.4 8.7 8.9 9.2 9.4 9.7
50 PI 4.08 4.26 4.44 4.54 4.59 4.84 5.05
TC SHC 10.1 10.9 11.6 12.1 12.3 13.4 14.3
7.8 8.1 8.4 8.6 8.8 9.1 9.3
52 PI 4.12 4.31 4.51 4.61 4.67 4.94 5.11
TC SHC 9.9 10.7 11.4 11.9 12.1 13.0 0.0
7.7 8.0 8.3 8.5 8.7 8.9 0.0
PI 4.12 4.32 4.52 4.63 4.69 4.97 0.0
Notes : 1. Figures in show nominal capacities. 2. The above capacities are gross capacities which do not include a deduction for indoor fan motor heat. 3. SHC is based on each EWB and EDB. SHC* = SHC correction for other dry bulb. (DB*) = 0.02 × AFR × (1 - BF) × (DB* - EDB) Add SHC* to SHC. 4. Direct interpolation is permissible. Do not extrapolate. 5. Capacities are based on the following conditions. Corresponding refrigerant piping length :5m Level difference :0m
FVG08AV2+RUG08AUY1 Indoor AFR 21 EDB EWB (BF) (˚C) (˚C) TC SHC 14.0 16.0 63 18.0 19.0 (0.15) 19.5 22.0 24.0
20 22 25 27 27 30 32
22.5 23.9 25.4 26.2 26.5 28.5 30.1
17.3 17.3 18.4 18.7 18.7 19.1 19.1
Outdoor temperature (˚CDB) 25 PI 5.47 5.57 5.70 5.76 5.77 5.97 6.07
TC SHC 22.0 23.3 24.8 25.5 25.8 27.8 29.4
Symbols : AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity PI : Power input (Comp. + Outdoor fan motor)
17.0 17.0 17.9 18.4 18.4 18.7 18.7
30 PI 5.86 5.96 6.07 6.16 6.17 6.36 6.46
(m3/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
TC SHC 21.3 22.6 24.0 24.7 25.0 27.0 28.5
16.6 16.6 17.6 18.0 18.0 18.4 18.4
35 PI 6.46 6.56 6.66 6.76 6.76 6.96 7.06
TC SHC 20.5 21.8 23.2 23.9 24.2 26.1 27.6
16.2 16.2 17.1 17.6 17.6 17.9 18.0
40 PI 7.06 7.15 7.36 7.37 7.45 7.56 7.76
TC SHC 19.7 20.9 22.2 22.9 23.3 25.1 26.5
15.2 15.4 16.3 16.8 16.8 17.1 17.1
45 PI 7.75 7.84 8.05 8.05 8.15 8.25 8.45
TC SHC 18.9 20.0 21.4 22.0 22.3 24.1 25.5
15.2 15.4 16.3 16.8 16.8 17.1 17.1
50 PI 8.54 8.64 8.74 8.84 8.85 9.10 9.24
TC SHC 17.9 19.1 20.4 21.1 21.4 23.0 0.0
14.7 14.8 14.8 15.8 16.3 16.6 0.0
52 PI 9.33 9.43 9.64 9.74 9.74 9.94 0.0
TC SHC 17.6 18.7 20.0 20.6 20.9 22.6 0.0
14.6 14.6 15.6 16.1 16.1 16.5 0.0
PI 9.63 9.83 9.94 10.03 10.03 10.24 0.0
Notes : 1. Figures in show nominal capacities. 2. The above capacities are gross capacities which do not include a deduction for indoor fan motor heat. 3. SHC is based on each EWB and EDB. SHC* = SHC correction for other dry bulb. (DB*) = 0.02 × AFR × (1 - BF) × (DB* - EDB) Add SHC* to SHC. 4. Direct interpolation is permissible. Do not extrapolate. 5. Capacities are based on the following conditions. Corresponding refrigerant piping length :5m Level difference :0m
FVG10AV2+RUG10AUY1 Indoor AFR 21 (BF) EWB EDB (˚C) (˚C) TC SHC 14.0 16.0 80 18.0 19.0 (0.14) 19.5 22.0 24.0
20 22 25 27 27 30 32
28.3 29.9 31.7 32.7 33.1 35.6 37.6
21.8 21.8 22.9 23.4 23.4 23.8 23.8
Outdoor temperature (˚CDB) 25 PI 7.47 7.57 7.77 7.86 7.87 8.03 8.23
TC SHC 27.6 29.2 31.0 32.0 32.3 34.8 36.7
Symbols : AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity PI : Power input (Comp. + Outdoor fan motor)
FV(P)G-A Series (50Hz)
21.4 21.4 22.5 23.1 23.1 23.5 23.5
30 PI 7.98 8.19 8.28 8.38 8.38 8.68 8.78
(m3/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
TC SHC 26.7 28.4 30.0 30.9 31.4 33.7 35.6
20.8 21.0 22.0 22.6 22.6 23.1 23.1
35 PI 8.81 8.91 9.11 9.20 9.20 9.40 9.61
TC SHC 25.8 27.4 29.1 29.9 30.4 32.6 34.4
20.4 20.4 21.5 22.1 22.1 22.5 22.5
40 PI 9.64 9.74 9.93 10.02 10.13 10.33 10.53
TC SHC 24.9 26.4 28.0 28.8 19.2 31.4 33.3
19.8 19.9 21.1 21.5 21.5 22.0 22.0
45 PI 10.56 10.77 10.96 11.05 11.06 11.25 11.46
TC SHC 23.8 25.2 26.9 27.7 28.1 30.2 32.0
19.2 19.3 20.5 21.1 21.1 21.4 21.4
50 PI 11.60 11.80 11.99 12.08 12.08 12.33 12.53
TC SHC 22.7 24.1 25.7 26.5 26.9 29.0 0.0
18.6 18.6 19.9 20.5 20.5 21.0 0.0
52 PI 12.74 12.95 13.13 13.22 13.22 13.52 0.0
TC SHC 22.2 23.6 25.2 26.0 26.4 28.4 0.0
18.4 18.4 19.7 20.3 20.3 20.7 0.0
PI 13.26 13.46 13.64 13.73 13.74 14.03 0.0
Notes : 1. Figures in show nominal capacities. 2. The above capacities are gross capacities which do not include a deduction for indoor fan motor heat. 3. SHC is based on each EWB and EDB. SHC* = SHC correction for other dry bulb. (DB*) = 0.02 × AFR × (1 - BF) × (DB* - EDB) Add SHC* to SHC. 4. Direct interpolation is permissible. Do not extrapolate. 5. Capacities are based on the following conditions. Corresponding refrigerant piping length :5m Level difference :0m
17
Capacity Tables (Cooling Capacity)
ED45-439
FVPG10AY1+RUG10AUY1 Indoor AFR 21 EDB EWB (BF) (˚C) (˚C) TC SHC
Outdoor temperature (˚CDB) 25 PI
30
TC SHC
PI
TC SHC
35 PI
TC SHC
40 PI
TC SHC
45 PI
TC SHC
50 PI
TC SHC
52 PI
TC SHC
PI
14.0 16.0 68 18.0 19.0 (0.13) 19.5 22.0 24.0
20 22 25 27 27 30 32
27.7 29.3 31.2 32.1 32.6 35.0 37.0
21.00 21.00 22.00 22.50 22.50 23.00 23.00
7.37 7.58 7.63 7.73 7.73 7.93 8.14
27.1 28.7 30.5 31.4 31.7 34.2 36.2
20.6 20.6 21.8 22.1 22.2 22.5 22.5
7.99 8.09 8.29 8.25 8.38 8.55 8.75
26.3 27.8 29.5 30.5 30.8 33.1 35.1
20.2 20.2 21.2 21.8 21.8 22.0 22.0
8.71 8.92 9.01 9.10 9.11 9.37 9.47
25.4 26.9 28.5 29.4 29.9 32.1 34.0
19.7 19.7 20.7 21.3 21.3 21.6 21.6
9.54 9.74 9.94 10.03 10.03 10.18 10.39
24.4 25.9 27.6 28.4 28.7 30.9 32.7
19.1 19.2 20.3 20.7 20.7 21.0 21.0
10.57 10.67 10.86 10.96 10.96 11.21 11.41
23.4 24.9 26.4 27.2 27.7 29.8 31.4
18.5 18.6 19.7 20.3 20.3 20.5 20.5
11.61 11.71 11.90 11.99 12.09 12.23 12.44
22.3 23.7 25.2 26.2 26.5 28.5 0.0
17.9 17.9 19.1 19.7 19.7 20.1 0.0
12.75 12.85 13.04 13.13 13.23 13.36 0.0
21.9 23.3 24.8 25.6 25.9 28.0 0.0
17.6 17.7 18.9 19.5 19.5 19.8 0.0
13.17 13.37 13.55 13.65 13.75 13.88 0.0
14.0 16.0 80 18.0 19.0 (0.14) 19.5 22.0 24.0
20 22 25 27 27 30 32
28.3 29.9 31.7 32.7 33.1 35.6 37.6
21.80 21.80 22.90 23.40 23.40 23.80 23.80
7.47 7.54 7.77 7.86 7.87 8.03 8.23
27.6 29.2 31.0 32.0 32.3 34.8 36.7
21.4 21.4 22.5 23.1 23.1 23.5 23.5
7.98 8.19 8.28 8.38 8.38 8.68 8.78
26.7 28.4 30.0 30.9 31.4 33.7 35.6
20.8 21.0 22.0 22.6 22.6 23.1 23.1
8.81 8.91 9.11 9.20 9.20 9.40 9.61
25.8 27.4 29.1 29.9 30.4 32.6 34.4
20.4 20.4 21.5 22.1 22.1 22.5 22.5
9.64 9.74 9.93 10.02 10.13 10.33 10.53
24.9 26.4 28.0 28.8 29.2 31.4 33.3
19.8 19.9 21.1 21.5 21.5 22.0 22.0
10.56 10.77 10.96 11.05 11.06 11.25 11.46
23.8 25.2 26.9 27.7 28.1 30.2 32.0
19.2 19.3 20.5 21.1 21.1 21.4 21.4
11.60 11.80 11.99 12.08 12.08 12.33 12.53
22.7 24.1 25.7 26.5 26.9 29.0 0.0
18.6 18.6 19.9 20.5 20.5 21.0 0.0
12.74 12.95 13.13 13.22 13.22 13.52 0.0
22.2 23.6 25.2 26.0 26.4 28.4 0.0
18.4 18.4 19.7 20.3 20.3 20.7 0.0
13.26 13.46 13.64 13.73 13.74 14.03 0.0
14.0 16.0 96 18.0 (0.16) 19.0 19.5 22.0 24.0
20 22 25 27 27 30 32
29.1 30.8 32.7 33.6 34.1 36.6 38.6
23.10 23.20 24.30 25.00 25.50 25.50 25.60
7.56 7.66 7.86 7.86 8.11 8.16 8.39
28.4 30.1 31.9 32.9 33.3 35.7 37.7
22.7 22.7 24.0 24.7 24.7 25.1 25.2
8.07 8.18 8.37 8.47 8.47 8.63 8.87
27.6 29.1 30.9 31.7 32.2 34.5 36.6
22.1 22.1 23.5 24.1 24.1 24.7 24.7
8.79 9.00 9.19 9.19 9.29 9.49 9.69
26.5 28.1 29.9 30.7 31.2 33.4 35.4
21.7 21.7 22.9 23.5 23.5 24.1 24.1
9.72 9.82 10.01 10.11 10.12 10.41 10.62
25.6 27.1 28.7 29.7 30.0 32.2 34.1
21.1 21.1 22.4 23.1 23.1 23.5 23.5
10.65 10.85 10.94 11.03 11.14 11.34 11.54
24.4 25.9 27.6 28.4 28.8 30.9 32.7
20.5 20.6 21.9 22.5 22.5 23.1 23.1
11.68 11.88 12.07 12.17 12.17 12.46 12.67
23.3 24.8 26.4 27.2 27.6 29.7 0.0
19.8 19.9 21.3 21.9 21.9 22.5 0.0
12.82 13.02 13.21 13.30 13.61 13.70 0.0
22.8 24.2 25.8 26.6 27.0 29.1 0.0
19.7 19.7 21.0 21.7 21.7 22.2 0.0
13.4 13.51 13.62 13.71 13.81 14.11 0.0
Symbols : AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity PI : Power input (Comp. + Outdoor fan motor)
(m3/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes : 1. Figures in show nominal capacities. 2. The above capacities are gross capacities which do not include a deduction for indoor fan motor heat. 3. SHC is based on each EWB and EDB. SHC* = SHC correction for other dry bulb. (DB*) = 0.02 × AFR × (1 - BF) × (DB* - EDB) Add SHC* to SHC. 4. Direct interpolation is permissible. Do not extrapolate. 5. Capacities are based on the following conditions. Corresponding refrigerant piping length :5m Level difference :0m
FVPG15AY1+ (RUG08AUY1) ×2 Indoor AFR 21 (BF) EWB EDB (˚C) (˚C) TC SHC
Outdoor temperature (˚CDB) 25 PI
30
TC SHC
PI
TC SHC
35 PI
TC SHC
40 PI
TC SHC
45 PI
TC SHC
50 PI
TC SHC
52 PI
TC SHC
PI
14.0 16.0 102 18.0 19.0 (0.06) 19.5 22.0 24.0
20 22 25 27 27 30 32
43.2 46.0 48.8 50.4 51.1 55.0 58.5
32.7 32.7 34.5 35.5 35.6 36.3 36.3
10.73 10.93 11.14 11.34 11.37 11.57 11.96
42.3 44.8 47.8 49.2 49.9 53.9 57.1
32.3 32.2 34.1 34.8 34.9 35.6 35.6
11.51 11.70 11.92 12.12 12.15 12.35 12.74
40.9 43.4 46.2 47.6 48.3 52.3 55.3
31.5 31.5 33.2 34.1 34.1 34.6 34.6
12.48 12.67 13.08 13.09 13.28 13.52 13.91
39.5 42.0 44.6 46.2 46.7 50.4 53.4
30.6 30.6 32.5 33.2 33.2 34.0 34.0
13.83 14.03 14.24 14.45 14.45 14.89 15.08
37.8 40.4 43.0 44.3 45.0 48.5 51.6
29.7 29.9 31.5 32.5 32.6 33.0 33.0
15.19 15.38 15.60 15.81 15.85 16.25 16.24
36.2 38.5 41.1 42.5 43.2 46.7 49.5
28.7 28.7 30.8 31.5 31.5 32.3 32.3
16.53 16.92 17.15 17.35 17.35 17.81 18.20
34.3 36.7 39.2 40.6 41.3 44.6 0.0
27.7 27.8 29.7 30.6 30.6 31.3 0.0
18.20 18.46 18.69 18.90 19.10 19.30 0.0
33.7 36.0 38.5 39.7 40.4 43.7 0.0
27.2 27.3 29.2 30.4 30.4 31.1 0.0
18.77 19.04 19.46 19.68 19.68 20.08 0.0
14.0 16.0 120 18.0 19.0 (0.08) 19.5 22.0 24.0
20 22 25 27 27 30 32
44.1 46.9 49.9 51.6 52.3 56.2 59.5
34.1 34.1 35.9 36.9 36.9 37.7 37.7
10.74 10.94 11.15 11.35 11.35 11.78 11.97
43.2 45.7 48.8 50.2 50.9 54.8 58.1
33.4 33.4 35.2 36.2 36.2 37.0 37.0
16.52 11.71 11.92 12.13 12.13 12.56 12.75
41.8 44.3 47.1 48.5 49.2 53.2 56.2
32.7 32.7 34.5 35.5 35.5 36.3 36.3
12.68 12.88 13.09 13.30 13.30 13.73 13.93
40.2 42.7 45.5 46.9 47.6 51.3 54.3
31.8 31.8 33.6 34.5 34.5 35.5 35.5
13.85 14.04 14.45 14.46 14.66 14.90 15.29
38.5 41.1 43.7 45.0 45.7 49.5 52.3
29.9 30.1 32.0 32.9 32.9 33.7 33.7
15.19 15.39 15.80 15.81 16.01 16.26 16.65
36.9 39.2 42.0 43.2 43.9 47.4 50.2
29.8 30.1 32.0 32.9 32.9 33.6 33.7
16.69 16.94 17.17 17.37 17.37 17.77 18.22
35.0 37.4 39.9 41.3 42.0 45.3 0.0
28.6 29.0 31.1 32.0 32.0 32.7 0.0
18.22 18.48 18.91 19.12 19.12 19.52 0.0
34.3 36.7 39.2 40.4 41.1 44.3 0.0
28.4 28.5 30.6 31.5 31.5 32.5 0.0
18.80 19.25 19.49 19.69 19.69 20.01 0.0
14.0 16.0 144 18.0 (0.10) 19.0 19.5 22.0 24.0
20 22 25 27 27 30 32
45.5 48.3 51.3 53.0 53.7 57.8 61.3
36.2 36.2 38.3 39.4 39.4 40.2 40.2
10.95 11.15 11.36 11.36 11.56 11.79 12.18
44.3 47.1 50.2 51.8 52.5 56.4 59.7
35.4 35.5 37.8 38.7 38.7 39.7 39.8
11.70 11.93 12.14 12.34 12.34 12.74 12.97
43.0 45.5 48.5 49.9 50.6 54.6 57.8
34.7 34.8 36.9 37.8 37.8 38.7 38.8
12.67 12.90 13.31 13.31 13.59 13.71 14.14
41.3 43.9 46.7 48.3 48.8 52.5 55.7
33.8 33.9 35.9 36.9 36.9 37.8 37.9
14.02 14.26 14.47 14.68 14.68 15.08 15.31
39.7 42.3 45.0 46.4 46.9 50.6 53.7
32.8 32.9 35.0 36.2 36.2 36.9 37.0
15.37 15.62 15.83 16.04 16.04 16.44 16.88
37.8 40.4 43.0 44.3 45.0 48.5 51.6
31.9 32.0 34.3 35.2 35.2 36.2 36.2
16.70 17.17 17.39 17.60 17.60 18.00 18.39
36.0 38.3 41.1 42.5 43.0 46.4 0.0
30.7 31.0 33.3 34.2 34.3 35.2 0.0
18.45 18.65 18.88 19.04 19.54 19.75 0.0
35.3 37.6 40.2 41.6 42.3 45.5 0.0
30.3 30.5 32.8 33.8 33.8 39.8 0.0
19.03 19.23 19.23 19.66 19.87 20.33 0.0
Symbols : AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity PI : Power input (Comp. + Outdoor fan motor)
18
(m3/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes : 1. Figures in show nominal capacities. 2. The above capacities are gross capacities which do not include a deduction for indoor fan motor heat. 3. SHC is based on each EWB and EDB. SHC* = SHC correction for other dry bulb. (DB*) = 0.02 × AFR × (1 - BF) × (DB* - EDB) Add SHC* to SHC. 4. Direct interpolation is permissible. Do not extrapolate. 5. Capacities are based on the following conditions. Corresponding refrigerant piping length :5m Level difference :0m
FV(P)G-A Series (50Hz)
ED45-439
Capacity Tables (Cooling Capacity)
FVPG20AY1+ (RUG10AUY1) ×2 Indoor AFR 21 EDB EWB (BF) (˚C) (˚C) TC SHC
Outdoor temperature (˚CDB) 25 PI
30
TC SHC
PI
TC SHC
35 PI
TC SHC
40 PI
TC SHC
45 PI
TC SHC
50 PI
TC SHC
52 PI
TC SHC
PI
14.0 16.0 146 18.0 19.0 (0.07) 19.5 22.0 24.0
20 22 25 27 27 30 32
54.2 57.4 61.1 63.0 63.9 68.8 72.8
41.0 41.0 43.4 44.3 44.3 45.2 45.2
14.43 14.83 15.03 15.23 15.23 15.63 16.03
53.0 56.2 59.7 61.6 62.3 67.1 71.0
40.3 40.3 42.7 43.6 43.6 44.2 44.2
15.63 15.83 16.23 16.23 16.43 16.80 17.20
51.4 54.4 57.9 59.7 60.4 65.1 69.0
39.4 39.4 41.5 42.7 42.7 43.4 43.4
17.04 17.44 17.64 17.84 17.84 18.44 18.64
49.5 52.5 55.8 57.6 58.6 63.0 66.7
38.5 38.5 40.6 41.7 41.7 42.4 42.4
18.64 19.04 19.44 19.64 19.64 20.04 20.44
47.6 50.7 53.9 55.5 56.2 60.7 64.2
37.3 37.5 39.6 40.6 40.6 41.3 41.3
20.65 20.85 21.25 21.45 21.45 22.05 22.45
45.5 48.6 51.6 53.2 54.2 58.3 61.6
36.1 36.4 38.5 39.6 39.6 40.3 40.3
22.66 22.86 23.26 23.45 23.65 24.05 24.46
43.5 46.2 49.3 51.1 51.8 55.8 0.0
35.0 35.0 37.3 38.5 38.5 39.4 0.0
24.87 25.07 25.46 25.66 25.86 26.26 0.0
42.5 45.3 48.3 50.0 50.7 54.9 0.0
34.3 34.5 36.8 38.0 38.0 38.9 0.0
25.67 26.07 26.47 26.67 26.87 27.27 0.0
14.0 16.0 172 18.0 19.0 (0.09) 19.5 22.0 24.0
20 22 25 27 27 30 32
55.3 58.6 62.3 64.2 65.1 70.0 73.9
42.7 42.7 45.0 45.9 45.9 46.8 46.8
14.63 14.83 15.23 15.43 15.43 15.83 16.23
53.9 57.2 60.9 62.8 63.5 68.3 72.3
42.0 42.0 44.1 45.2 45.2 46.1 46.1
15.63 16.00 16.23 16.43 16.43 17.03 17.23
52.3 55.5 58.8 60.7 61.6 66.2 70.0
40.8 41.0 43.1 44.3 44.3 45.2 45.2
17.24 17.44 17.84 18.04 18.04 18.44 18.44
50.4 53.7 56.9 58.6 59.5 63.9 67.6
39.9 39.9 42.2 43.4 43.4 44.1 44.1
18.84 19.04 19.44 19.64 19.84 20.24 20.64
48.6 51.6 54.9 56.5 57.2 61.6 65.3
38.7 38.9 41.3 42.2 42.2 43.1 43.1
20.65 21.05 21.45 21.65 21.65 22.05 22.45
46.5 49.3 52.5 54.2 55.1 59.3 62.8
37.5 37.8 40.1 41.3 41.3 42.2 42.2
22.66 23.06 23.45 23.65 23.65 24.25 24.65
44.2 46.9 50.2 51.8 52.5 56.7 0.0
36.4 36.4 38.9 40.1 40.1 41.0 0.0
24.86 25.26 25.66 25.86 25.86 26.46 0.0
43.2 46.0 49.3 50.9 51.6 55.5 0.0
35.9 35.9 38.5 39.6 39.6 40.6 0.0
25.87 26.27 26.66 26.86 26.86 27.46 0.0
14.0 16.0 210 18.0 (0.11) 19.0 19.5 22.0 24.0
20 22 25 27 27 30 32
56.9 60.4 64.2 66.0 66.9 72.1 76.0
45.2 45.4 47.8 49.2 49.2 50.1 50.1
14.83 15.03 15.43 15.43 15.63 16.03 16.43
55.5 59.0 62.5 64.6 65.3 70.2 74.2
44.5 44.5 47.1 48.5 48.5 49.4 49.4
15.83 16.03 16.43 16.63 16.63 17.03 17.43
53.9 56.9 60.7 62.3 63.2 67.9 72.1
43.4 43.4 46.1 47.3 47.3 48.5 48.5
17.23 17.64 18.03 18.03 18.23 18.63 19.03
51.8 55.1 58.6 60.2 61.1 65.5 69.5
42.4 42.4 45.0 46.1 46.1 47.3 47.3
19.04 19.24 19.64 19.84 19.84 20.44 20.84
50.0 53.0 56.2 58.1 58.8 63.2 66.9
41.3 41.3 43.8 45.2 45.2 46.1 46.1
20.85 21.25 21.44 21.64 21.84 22.24 22.64
47.6 50.7 53.9 55.5 56.5 60.7 64.2
40.1 40.3 42.9 44.1 44.1 45.2 45.2
22.85 23.25 23.65 23.85 23.85 24.45 24.85
45.3 48.3 51.6 53.2 53.9 58.1 0.0
38.7 38.9 41.4 42.9 42.9 44.1 0.0
25.06 25.46 25.67 26.06 26.66 26.86 0.0
44.4 47.2 50.4 52.1 52.8 56.9 0.0
38.2 38.2 41.0 42.4 42.4 43.6 0.0
26.06 26.26 26.66 26.86 27.06 27.66 0.0
Symbols : AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. TC : Total cooling capacity SHC : Sensible heat capacity PI : Power input (Comp. + Outdoor fan motor)
(m3/min.) (˚CWB) (˚CDB) (kW) (kW) (kW)
Notes : 1. Figures in show nominal capacities. 2. The above capacities are gross capacities which do not include a deduction for indoor fan motor heat. 3. SHC is based on each EWB and EDB. SHC* = SHC correction for other dry bulb. (DB*) = 0.02 × AFR × (1 - BF) × (DB* - EDB) Add SHC* to SHC. 4. Direct interpolation is permissible. Do not extrapolate. 5. Capacities are based on the following conditions. Corresponding refrigerant piping length :5m Level difference :0m
Capacity Correction Ratio
FV(P)G-A Series (50Hz)
19
Operation Limit
ED45-439
9. Operation Limit
20
FV(P)G-A Series (50Hz)
ED45-439
Fan Performance
10. Fan Performance Fan speed Model Air flow (Power absorb) 3 Indoor unit (m /min ) Motor output RPM FVG05AV2 42 kW RPM 63 FVG08AV2 kW RPM 80 FVG10AV2 kW RPM ( kW ) 68 kW RPM ( kW ) 80 FVPG10AY1 kW RPM ( kW ) 96 kW RPM ( kW ) 102 kW RPM ( kW ) FVPG15AY1 120 kW RPM ( kW ) 144 kW RPM ( kW ) 146 kW RPM ( kW ) FVPG20AY1 172 kW RPM ( kW ) 210 kW ESP : External static pressure
FV(P)G-A Series (50Hz)
ESP( mmH2O / Pa ) 0 / 0 5/50 10/100 15/150 20/200 25/250 30/300 35/350 40/400 45/450 50/500
Standard point ( Factory setting ) Air flow = 42 m3/ min, ESP = 0 / 0 ( mmH2O / Pa ) Fan speed = 1000 / 950 / 850 RPM Air flow = 63 m3/ min, ESP = 0 / 0 ( mmH2O / Pa ) Fan speed = 1300 / 1250 / 1150 RPM Air flow = 80 m3/ min, ESP = 0 / 0 ( mmH2O / Pa ) Fan speed = ( 1000 / 950 / 850 ) x 2 RPM
600 0.24 0.75 613 0.32 0.75 642 0.45 0.75 645 0.74 1.5 713 1.11 1.5 813 1.8 3.7 632 1.26 2.2 724 1.99 3.7 857 3.49 5.5
727 0.33 0.75 733 0.41 0.75 748 0.56 0.75 706 0.84 1.5 763 1.22 2.2 853 1.92 3.7 657 1.31 2.2 746 2.06 3.7 881 3.61 5.5
856 0.45 0.75 838 0.53 0.75 848 0.68 1.5 770 0.94 1.5 814 1.33 2.2 894 2.03 3.7 682 1.36 2.2 768 2.13 3.7 899 3.7 5.5
986 0.59 1.5 946 0.64 1.5 940 0.81 1.5 837 1.06 1.5 867 1.44 2.2 937 2.16 3.7 724 1.48 2.2 789 2.19 3.7 917 3.78 5.5
1101 0.74 1.5 1058 0.81 1.5 1028 0.94 1.5 903 1.19 1.5 923 1.57 2.2 980 2.3 3.7 781 1.65 2.2 809 2.24 3.7 934 3.86 5.5
1202 0.9 1.5 1169 0.98 1.5 1116 1.06 1.5 965 1.31 2.2 981 1.72 2.2 1023 2.43 3.7 836 1.82 3.7 849 2.41 3.7 952 3.94 5.5
1290 1.06 1.5 1268 1.15 1.5 1211 1.27 2.2 1024 1.44 2.2 1037 1.86 3.7
1365 1.2 2.2 1356 1.34 2.2 1303 1.47 2.2 1080 1.57 2.2 1091 2 3.7
1436 1.34 2.2 1439 1.53 2.2 1395 1.67 2.2 1132 1.71 2.2 1143 2.16 3.7
1182 1.82 3.7 1194 2.31 3.7
1242 1.99 3.7 1242 2.45 3.7
887 1.99 3.7 896 2.61 5.5 969 4.02 5.5
935 2.14 3.7 944 2.8 5.5 986 4.08 5.5
982 2.33 3.7 991 3.01 5.5 1015 4.25 5.5
1029 2.49 5.5 1035 3.2 5.5 1050 4.46 5.5
1073 2.7 5.5 1075 3.4 5.5
Air flow = 80 m3/ min ESP = 15 / 150 ( mmH2O / Pa ) Fan speed = 946 RPM Motor output = 1.5 kW Fan pulley = PD 160 - 1A - 25 Motor pulley = PD 100 - 1A - 24 V-Belt = A - 44
Air flow = 120 m3/ min ESP = 15 / 150 ( mmH2O / Pa ) Fan speed = 867 RPM Motor output = 2.2 kW Fan pulley = PD 180 - 1A - 25 Motor pulley = PD 112 - 1A - 28 V-Belt = A - 35
Air flow = 172 m3/ min ESP = 15 / 150 ( mmH2O / Pa ) Fan speed = 789 RPM Motor output = 3.7 kW Fan pulley = PD 250 - 1B - 25 Motor pulley = PD 132 - 1B - 28 V-Belt = B - 41
21
Sound Level
ED45-439
11. Sound Level 11.1
Overall
11.1.1 Indoor Unit Direct Air Blow Type Model
FVG05AV2
FVG08AV2
FVG10AV2
Fan Speed
dBA
H
59
M
54
L
50
H
60
M
56
L
51
H
61
M
57
L
52
Measuring Location
Duct Connection Type Model
dBA
FVPG10AY1
61
FVPG15AY1
62
FVPG20AY1
63
Model
dBA
RG125AUY1
57
RUG08AUY1
60
RUG10AUY1
61
Measuring Location
11.1.2 Outdoor Unit Measuring Location
Note : Operation noise differes with operation and ambient conditions.
22
FV(P)G-A Series (50Hz)
ED45-439
Installation
12. Installation 12.1
Indoor Unit·····FVG05AV2, FVG08AV2, FVG10AV2 FVPG10AY1, FVPG15AY1, FVPG20AY1 1. BEFORE INSTALLATION <Do not throw away any of the parts or contents packaged with this unit until installation is completed.> Plan a convenient path for transporting the unit prior to unpacking or installing it. Unpack the unit at the site of installation. In the event that the unit is unpacked away from the installation site, use a tarp, sheet or some other device when lifting or transporting it to avoid scratches or other damage. 2. SELECTING AN INSTALLATION SITE The installation site should be chosen considering the specifications of Figs. 1 and 2, along with the individual preferences of the user. Optimum air distribution is ensured. The air passage is not blocked. Condensate can drain properly. Sufficient clearance for maintenance and servicing is ensured. Piping between the indoor and outdoor units is within the allowable limits. (Refer to the installation manual for the outdoor unit.) The indoor unit, outdoor unit, power supply wiring and transmission wiring is at least 1 meter away from televisions and radios. This prevents image interference and noise in electrical appliances. (Noise may be generated depending on the conditions under which the electric wave is generated, even if a one-meter allowance is maintained.) Required space for installation Fig. 1
FVG-AV2
FVPG-AY1
FV(P)G-A Series (50Hz)
23
Installation
ED45-439
3.
PREPARATIONS BEFORE INSTALLATION Preparation floor strong enough for weight of M/C Lay out point for put insert nut at the floor on Table 1-1, Table 1-2. Checked M/C level not incline by water level (Fig. 2-1, Fig. 2-2) Setting M/C to the position as table and tightening with bolt of insert nut.
Table 1-1 Model
A
FVG05AV2
780
FVG08AV2
960
FVG10AV2
1180
Fig. 2-1
Table 1-2 Model
A
B
FVPG10AY1
1210
394
FVPG15AY1
1210
602
FVPG20AY1
1510
602
Fig. 2-2
4. REFRIGERANT PIPING WORK WARNING Do not mix gas other than the specified refrigerant into the refrigerant cycle. Ventilate the area should any refrigerant leak during installation. Cut the end of the plug before heating the pipe to remove the plug Fig.3 Piping should be brazed onto the indoor unit. Check the size of the refrigerant piping with Table 2, and Fig. 4 Use seamless copper piping only. After brazing the pipes use the insulation to secure the pipe inside of the unit (Fig. 5-1, Fig. 5-2). Install the insulation as close to the body as possible to absorb leaking condensation. Table 2 Refrigerant Piping Size
24
Gas Pipe
Liquid Pipe
FVG05AV2
19.1×1.0t, L=10
9.5×0.8t, L=7
FVG08AV2
25.4×1.2t, L=12
12.7×0.9t, L=8 15.9×0.9t, L=8
FVG10AV2
31.8×1.2t, L=12
FVPG10AY1
31.8×1.2t, L=12
15.9×0.9t, L=8
FVPG15AY1
25.4×1.15t, L=12
12.7×0.9t, L=8
FVPG20AY1
31.8×1.2t, L=12
15.9×0.9t, L=8
FV(P)G-A Series (50Hz)
ED45-439
Installation
Fig. 3
Fig. 4
Fig. 5-1
Fig. 5-2
5. DRAIN PIPING WORK WARNING The drain pipe must be installed to avoid water damage caused by leaks and condensation. Assemble the unit as shown in Fig. 6-1, Fig. 6-2. The drain pipe outlet can be installed on either the left or right side. The drain plug can be removed and placed on either the left or right side as well. For best results, try to keep the piping as short as possible. Slant the piping at an angle to improve airflow (the drain pipe provided with the indoor unit is PT 1 internal thread). Securely insulate the drain pipe. It is necessary to provide a drain trap in the drain outlet to relieve negative pressure that exists withing the unit compared to the outside atmospheric pressure when the unit is operating. Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris. After closing the drain pipe on the opposite side of the unit, completely wrap the drain pipes with insulation (Fig. 6-1, Fig. 6-2). Pour water in the drain pan to test for smooth drainage.
FV(P)G-A Series (50Hz)
25
Installation
ED45-439
Fig. 6-1
6.
Fig. 6-2
ELECTRIC WIRING All commercially available supplies, materials and electrical parts must conform to local codes. Use copper wire only. For electric wiring work, refer to the "WIRING DIAGRAM" Fig. 7-1, Fig. 7-2. For remote controller wiring, refer to the remote controller’s installation manual. All wiring must be performed by an authorized electrician. A circuit breaker capable of controlling the power supply to the entire system must be installed. Refer to the installation manual attached to the outdoor unit for the size of the power supply electrical wire to be used to connect with the outdoor unit, the capacity of the circuit breaker/switch, and wiring instructions.
FVG-AV2 Fig. 7-1
26
FV(P)G-A Series (50Hz)
ED45-439
Installation
FVPG10AY1
FVPG15, 20AY1 Fig. 7-2
WARNING Observe the notes mentioned below while connecting wire to the power supply terminal board. Â&#x201E; Do not connect wires of different size to the same power supply terminal. (Looseness in the connection may cause overheating.). Â&#x201E; When connecting wires of the same gauge, connect them according to the figure below. Connect wires of the same size on Do not connect wires of the same Do not connect wires of different both sides. sizes size to only one side.
CAUTION Busier to use 3 minute delay timer when starting the compressor may not start. WARNING Do not install the switch box on the air outlet side of coil or under any of the surrounding piping to avoid electric fire or shock caused by leaking condensation. Fig. 8-1, Fig. 8-2.
FV(P)G-A Series (50Hz)
27
Installation
ED45-439
FVG-AV2 Fig. 8-1
FVPG10AY1
FVPG15, 20AY1 Fig. 8-2
28
FV(P)G-A Series (50Hz)
ED45-439
12.2
Installation
Outdoor Unit·····RG125AUY1
FV(P)G-A Series (50Hz)
29
Installation
30
ED45-439
FV(P)G-A Series (50Hz)
ED45-439
FV(P)G-A Series (50Hz)
Installation
31
Installation
32
ED45-439
FV(P)G-A Series (50Hz)
ED45-439
FV(P)G-A Series (50Hz)
Installation
33
Installation
34
ED45-439
FV(P)G-A Series (50Hz)
ED45-439
FV(P)G-A Series (50Hz)
Installation
35
Installation
36
ED45-439
FV(P)G-A Series (50Hz)
ED45-439
FV(P)G-A Series (50Hz)
Installation
37
Installation
38
ED45-439
FV(P)G-A Series (50Hz)
ED45-439
FV(P)G-A Series (50Hz)
Installation
39
Installation
40
ED45-439
FV(P)G-A Series (50Hz)
ED45-439
FV(P)G-A Series (50Hz)
Installation
41
Installation
ED45-439
SDR3040989
42
FV(P)G-A Series (50Hz)
ED45-439
12.3
Installation
Outdoor Unit·····RUG08AUY1, RUG10AUY1
FV(P)G-A Series (50Hz)
43
Installation
44
ED45-439
FV(P)G-A Series (50Hz)
ED45-439
FV(P)G-A Series (50Hz)
Installation
45
Installation
46
ED45-439
FV(P)G-A Series (50Hz)
ED45-439
FV(P)G-A Series (50Hz)
Installation
47
Installation
48
ED45-439
FV(P)G-A Series (50Hz)
ED45-439
Installation
SDR3041000
FV(P)G-A Series (50Hz)
49
Cautions on product corrosion 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
The air conditioners manufactured by Daikin Airconditioning (Thailand) LTD. have received ISO 9000 series certification for quality assurance. Certificate Number.
The airconditioning factories of Daikin Airconditioning (Thailand) LTD. have received environmental management system standard ISO 14001 certification. Certificate Number.
(ISO9001) JQA-QM8166
(ISO14001) JQA-EM3701
Dealer 700/444 Moo. 7 Amata Nakorn Industrial Estate Bangna-Trad Road, km. 57, Tambol Donhualor, Amphur Muangchonburi, Chonburi 20000 Thailand Tel: (038)717-066-70 Fax: (038)454-184
Head Office: Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome, Kita-ku, Osaka, 530-8323 Japan Tokyo Office: JR Shinagawa East Bldg., 18-1, Konan 2-chome, Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/ c All rights reserved
The specifications, designs, and information in this brochure are subject to change without notice.
This book is made of recycled paper.
ED 45-439 Printed in Japan 09/2004 FS