Warning

Daikin Industries, Ltd.ʼs products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorised importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.

PCS0316H

Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer.

AIR CONDITIONING SYSTEM COOLING ONLY HE AT PUMP

Cautions on product corrosion 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

JMI-0107

JQA-1452

About ISO 9001 ISO 9001 is a plant certification system defined by the International Organization for Standardization (ISO) relating to quality assurance. ISO 9001 certification covers quality assurance aspects related to the “ design, development, manufacture, installation, and supplementary service” of products manufactured at the plant.

About ISO 14001 ISO 14001 is the standard defined by the International Organization for Standardization (ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the requirements of ISO 14001.

Dealer Head Office: Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan Tokyo Office: JR Shinagawa East Bldg., 2-18-1, Konan, Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global_ac/ c All rights reserved Printed in Japan 05/08/005 SW • HP • SS

Specifications, designs and other content appearing in this brochure are current as of May 2008 but subject to change without notice.

C

r e a t io n o f

C

o m fo r t

[ 50 Hz ] [ 50 Hz ]


Stores often feature the latest in designed decor. This refined beauty attracts people. Meanwhile, offices have a functional beauty. This encourages those within to work hard and apply intelligence and passion to their tasks. In either situation, a certain elegance should fill the space because thinking minds require high quality air conditioning. SkyAir by D aikin realise a comfortable indoor environment. All over the world, stores, offices, and homes prefer the low operating sound, attractive

1

2


Cooling only

Capacity

HP

The values given for 1 HP is for FDGB type, 1.5 HP–6 HP is for FHYC type, 7 HP is for FDMG type, 8 HP–20 HP is for FD type.

kW

1

1.5

2

2.5

3

4

5

6

7

8

10

15

20

2.6

3.5

5.3

6.4

7.7

10.5

12.8

14.2

16.8

24.0

29.2

47.9

58.4

Btu/h

8,900

11,900

18,100

21,800

26,200

35,700

43,600

48,400

57,500

81,800

99,600

163,500

199,400

kcal/h

2,250

3,010

4,560

5,500

6,600

9,000

11,000

12,200

14,400

20,600

25,100

41,200

50,200

FHC35KVE

FHC50KVE

FHC60KVE

FHYC71KVE

FHYC100KVE

FHYC125KVE

FHYC140KVE

R35GV1

R50GV1

R60GV1

R71LUV1 / Y1

R100LUV1 / Y1

R125LUY1

R140LUY1

FH35BVE

FH50BVE

FH60BVE

FHY71BVE

FHY100BVE

FHY125BVE

R35GV1

R50GV1

R60GV1

R71LUV1 / Y1

R100LUV1 / Y1

R125LUY1

CEILING MOUNTED CASSETTE TYPE Page 11– 14 Specifications Dimensions

Indoor unit

Page 39 Page 60

Outdoor unit

CEILING SUSPENDED TYPE Page 15– 16 Specifications Dimensions

Indoor unit

Page 39 Page 60

Outdoor unit

CEILING SUSPENDED CASSETTE TYPE Page 17– 18 Specifications Dimensions

Page 40 Page 61

Indoor unit

FUY71FJV1

FUY100FJV1

FUY125FJV1

Outdoor unit

R71LUV1 / Y1

R100LUV1 / Y1

R125LUY1

CEILING MOUNTED CASSETTE CORNER TYPE Page 19– 20 Specifications Dimensions

Indoor unit

Page 40 Page 61

Outdoor unit

FHK35FV1

FHK45FV1

FHK60FV1

FHYK71FJV1

R35GV1

R50GV1

R60GV1

R71LUV1 / Y1

FHB35FV1

FHB45FV1

FHB60FV1

FHYB71FV1

FHYB100FV1

FHYB125FV1

R35GV1

R50GV1

R60GV1

R71LUV1 / Y1

R100LUV1 / Y1

R125LUY1

CEILING MOUNTED BUILT-IN TYPE Page 21– 22 Specifications Dimensions

Page 41 Page 62

Indoor unit Outdoor unit

WALL MOUNTED TYPE Page 23– 24 Specifications Dimensions

Page 41 Page 62,63

FAY71LVE

FAY100FAVE

R71LUV1 / Y1

R100LUV1 / Y1

Indoor unit

FVY71LAVE

FVY100LAVE

FVY125LAVE

Outdoor unit

R71LUV1 / Y1

R100LUV1 / Y1

R125LUY1

Indoor unit Outdoor unit

FLOOR STANDING TYPE Page 25– 26 Specifications Dimensions

Page 42 Page 63

PACKAGED AIR CONDITIONERS

LOW STATIC PRESSURE TYPE Specifications Page 42 Dimensions Page 64

Indoor unit Outdoor unit

DUCT CONNECTION

FDBG25AVE

FDBG35AVE

FDBG50AVE

FDBG60AVE

FDBG71AVE

R25JV1

R35JV1

R50GV1

R60GV1

R71FUV1 / Y1

MIDDLE STATIC PRESSURE TYPE Specifications Page 43 Dimensions Page 64,65

(FDMG)

(FDMG)

Page 27– 30

(FDYM)

(FDYM)

(FDMG)

(FDMG)

(FDYM)

Indoor unit

FDMG71AV1

FDMG100AV1

FDMG125AV1

FDMG140AV1

FDMG180AV1

Outdoor unit Indoor unit

RG71AV1 / Y1

R100FUV1 / Y1

R125FUY1

RG140AY1

RG180AY1

FDYM03FAV1

FDYM04FAV1

FDYM05FAV1

FDYM06FAV1

Outdoor unit

R71LUV1 / Y1

R100LUV1 / Y1

R125LUY1

R140LUY1

Indoor unit

FD03KY1

FD04KY1

FD05KY1

FD06KY1

FD08KY1

FD10KY1

FD15KY1

FD20KY1

Outdoor unit Outdoor unit

R71FUY1

R100FUY1

R125FUY1

RU06KY1

RU08KUY1 RU08KY1

RU10KUY1 RU10KY1

RU08KUY1 × 2 RU08KY1 × 2

RU10KUY1 × 2 RU10KY1 × 2

RU08KUY1 RU08KY1

RU10KUY1 RU10KY1

RU08KUY1 × 2 RU08KY1 × 2

RU10KUY1 × 2 RU10KY1 × 2

HIGH STATIC PRESSURE TYPE Specifications Page 44,45 Dimensions Page 65– 67

(Type without factory charged refrigerant)

OUTDOOR UNIT Page 33– 34

Dimensions Page 68– 74

R25JV1

3

R35GV1

R35JV1

R50GV1

R60GV1

R71LUV1 R71LUY1

R71FUY1 RG71AV1 R100LUV1 R100FUY1 RG71AY1 R100LUY1 R100FUV1

R125LUY1 R125FUY1

R140LUY1

RU06KY1 RG140AY1

RG180AY1

4


Cooling only Simultaneous operation system HP

Capacity The values given on the right are for the FHYC type.

Page 31– 32

TWIN MULTI OPERATION 3

4

Specifications Page 46– 48

5

6

8

10

kW

7.7

10.5

12.8

14.2

22.2

26.6

Btu/h

26,200

35,700

43,600

48,400

75,800

90,800

kcal/h

6,600

9,000

11,000

12,200

19,100

22,900

FHYC35KVE × 2

FHYC50KVE × 2

FHYC60KVE × 2

FHYC71KVE × 2

FHYC100KVE × 2

FHYC125KVE × 2

R71LUV1 / Y1

R100LUV1 / Y1

R125LUY1

R140LUY1

R200KUY1

R250KUY1

Simultaneously running 2 to 4 units distributes comfort across wide spaces.

CEILING MOUNTED CASSETTE TYPE Indoor unit Outdoor unit

Simultaneous control with 2 units in spacious space

CEILING SUSPENDED TYPE Indoor unit Outdoor unit

FHY35BVE × 2

FHY50BVE × 2

FHY60BVE × 2

FHY71BVE × 2

FHY100BVE × 2

FHY125BVE × 2

R71LUV1 / Y1

R100LUV1 / Y1

R125LUY1

R140LUY1

R200KUY1

R250KUY1

FDYM04FAV1 × 2

FDYM05FAV1 × 2

R200KUY1

R250KUY1

R200KUY1

R250KUY1

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE Indoor unit Outdoor unit

Simultaneous control with 3 units for irregularly shaped space

OUTDOOR UNIT Page 33– 34 R71LUV1 R71LUY1

Simultaneous operation system

Capacity The values given on the right are for the FHYC type.

R100LUV1 R100LUY1

R125LUY1

R140LUY1

Page 31– 32

TRIPLE MULTI OPERATION

Specifications Page 46– 48

Simultaneous operation system

DOUBLE TWIN MULTI OPERATION

Page 31– 32 Specifications Page 46– 48

HP

6

8

8

10

kW

14.2

22.2

22.2

26.6

Btu/h

48,400

75,800

75,800

90,800

kcal/h

12,200

19,100

19,100

22,900

FHYC50KVE × 3

FHYC71KVE × 3

FHYC50KVE × 4

FHYC60KVE × 4

R140LUY1

R200KUY1

R200KUY1

R250KUY1

FHY50BVE × 3

FHY71BVE × 3

FHY50BVE × 4

FHY60BVE × 4

R140LUY1

R200KUY1

R200KUY1

R250KUY1

R200KUY1

R250KUY1

Simultaneous control with 4 units for large space

CEILING MOUNTED CASSETTE TYPE Indoor unit Outdoor unit

CEILING SUSPENDED TYPE Indoor unit Outdoor unit

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

FDYM03FAV1 × 3

Indoor unit Outdoor unit

R200KUY1

OUTDOOR UNIT Page 33– 34 R140LUY1

5

R200KUY1

6


Heat pump 15 43.5

20 53.0

75,700

92,500

148,000

181,000

19,100

23,300

37,400

45,600

23.2

29.5

44.8

56.8

56,000

79,200

100,700

153,000

194,000

12,200

14,000

20,000

25,400

38,500

48,800

2 5.2

2.5 6.15

3 7.7

4 10.4

5 12.8

6 14.2

Btu/h

12,800

17,800

21,000

26,200

35,300

43,600

48,400

kcal/h

3,230

4,470

5,290

6,600

8,900

11,000

12,220

kW

4.22

5.8

7.0

7.9

11.2

14.2

16.3

Btu/h

14,400

19,800

23,900

27,000

38,100

48,400

kcal/h

3,630

4,990

6,020

6,800

9,600

Indoor unit

kW

Cooling

The values given on the right are for the FHYC type. Values for other

Heating

types may differ slightly.

10 27.1

1.5 3.75

HP

Capacity The values given for 8HP to 20HP are for the FDY type.

8 22.2

CEILING MOUNTED CASSETTE TYPE Page 11– 14

Specifications Page 49 Dimensions Page 60

FHYC35KVE

FHYC50KVE

FHYC60KVE

FHYC71KVE

FHYC100KVE

FHYC125KVE

FHYC140KVE

Outdoor unit

RY35FV1A

RY50GAV1A

RY60GAV1A

RY71LUV1 / Y1

RY100LUV1 / Y1

RY125LUY1

RY140LUY1

Indoor unit

FHY35BVE

FHY50BVE

FHY60BVE

FHY71BVE

FHY100BVE

FHY125BVE

Outdoor unit

RY35FV1A

RY50GAV1A

RY60GAV1A

RY71LUV1 / Y1

RY100LUV1 / Y1

RY125LUY1

FUY71FJV1

FUY100FJV1

FUY125FJV1

RY71LUV1 / Y1

RY100LUV1 / Y1

RY125LUY1

CEILING SUSPENDED TYPE Page 15– 16

Specifications Page 49 Dimensions Page 60

CEILING SUSPENDED CASSETTE TYPE Page 17– 18

Specifications Page 50 Dimensions Page 61

Indoor unit Outdoor unit

CEILING MOUNTED CASSETTE CORNER TYPE Page 19– 20

Specifications Page 50 Dimensions Page 61

Indoor unit Outdoor unit

FHYK35FJV1

FHYK45FJV1

FHYK60FJV1

FHYK71FJV1

RY35FV1A

RY50GAV1A

RY60GAV1A

RY71LUV1 / Y1

FHYB35FV1

FHYB45FV1

FHYB60FV1

FHYB71FV1

FHYB100FV1

FHYB125FV1

RY35FV1A

RY50GAV1A

RY60GAV1A

RY71LUV1 / Y1

RY100LUV1 / Y1

RY125LUY1

CEILING MOUNTED BUILT-IN TYPE Page 21– 22

Specifications Page 51 Dimensions Page 62

Indoor unit Outdoor unit

WALL MOUNTED TYPE Page 23– 24

Specifications Page 51 Dimensions Page 62,63

Indoor unit Outdoor unit

FAY71LVE

FAY100FAVE

RY71LUV1 / Y1

RY100LUV1 / Y1

FLOOR STANDING TYPE Page 25– 26

Specifications Page 52 Dimensions Page 63

Indoor unit Outdoor unit

FVY71LAVE

FVY100LAVE

FVY125LAVE

RY71LUV1 / Y1

RY100LUV1 / Y1

RY125LUY1

PACKAGED AIR CONDITIONERS

DUCT CONNECTION

LOW STATIC PRESSURE TYPE Specifications Page 52 Dimensions Page 64

Indoor unit Outdoor unit

FDYB35KAVE

FDYB50KAVE

FDYB60KAVE

FDYB71KAVE

RY35FV1A

RY50GAV1A

RY60GAV1A

RY71LUV1 / Y1

MIDDLE STATIC PRESSURE TYPE Specifications Page 53 Dimensions Page 64,65

Indoor unit

FDYM03FAV1

FDYM04FAV1

FDYM05FAV1

FDYM06FAV1

Outdoor unit

RY71LUV1 / Y1

RY100LUV1 / Y1

RY125LUY1

RY140LUY1

HIGH STATIC PRESSURE TYPE Specifications Page 54 Dimensions Page 65– 67

Page 27– 30

Indoor unit

FDY06KAY1

FDY08KAY1

FDY10KAY1

FDY15KAY1

FDY20KAY1

Outdoor unit

RY140LUY1

RY200KUY1

RY250KUY1

RY200KUY1 × 2

RY250KUY1 × 2

RY140LUY1

RY200KUY1

RY250KUY1

RY200KUY1 × 2

RY250KUY1 × 2

OUTDOOR UNIT Page 33– 34 7

Dimensions

Page 68– 74

RY35FV1A

RY50GAV1A

RY60GAV1A

RY71LUV1 RY71LUY1

RY100LUV1 RY100LUY1

RY125LUY1

8


Heat pump Simultaneous operation system HP

Capacity Cooling / Heating The values given on the right are for the FHYC type.

Page 31– 32

TWIN MULTI OPERATION 3

4

Specifications Page 54– 56

5

6

8

Simultaneously running 2 to 4 units distributes comfort across wide spaces.

10

kW

7.7/7.9

10.4/11.2

12.8/14.2

14.2/16.3

22.2/22.7

26.6/28.4

Btu/h

26,200/27,000

35,300/38,100

43,600/48,400

48,400/56,000

75,800/77,500

90,800/97,000

kcal/h

6,600/6,800

8,900/9,600

11,000/12,200

12,200/14,000

19,100/19,500

22,900/24,400

FHYC35KVE × 2

FHYC50KVE × 2

FHYC60KVE × 2

FHYC71KVE × 2

FHYC100KVE × 2

FHYC125KVE × 2

RY71LUV1 / Y1

RY100LUV1 / Y1

RY125LUY1

RY140LUY1

RY200KUY1

RY250KUY1

CEILING MOUNTED CASSETTE TYPE Indoor unit Outdoor unit

Simultaneous control with 2 units in spacious space

CEILING SUSPENDED TYPE Indoor unit

FHY35BVE × 2

FHY50BVE × 2

FHY60BVE × 2

FHY71BVE × 2

FHY100BVE × 2

FHY125BVE × 2

Outdoor unit

RY71LUV1 / Y1

RY100LUV1 / Y1

RY125LUY1

RY140LUY1

RY200KUY1

RY250KUY1

FDYM04FAV1 × 2

FDYM05FAV1 × 2

RY200KUY1

RY250KUY1

RY200KUY1

RY250KUY1

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE Indoor unit Outdoor unit

Simultaneous control with 3 units for irregularly shaped space

OUTDOOR UNIT Page 33– 34 RY71LUV1 RY71LUY1

Simultaneous operation system HP

Capacity Cooling / Heating The values given on the right are for the FHYC type.

RY100LUV1 RY100LUY1

RY125LUY1

RY140LUY1

Page 31– 32

TRIPLE MULTI OPERATION 6

Specifications Page 54– 56

8

Simultaneous operation system

DOUBLE TWIN MULTI OPERATION

8

Page 31– 32 Specifications Page 54– 56

10

kW

14.2/16.3

22.2/22.7

22.2/22.7

26.6/28.4

Btu/h

48,400/56,000

75,800/77,500

75,800/77,500

90,800/97,000

kcal/h

12,200/14,000

19,100/19,500

19,100/19,500

22,900/24,400

FHYC50KVE × 3

FHYC71KVE × 3

FHYC50KVE × 4

FHYC60KVE × 4

RY140LUY1

RY200KUY1

RY200KUY1

RY250KUY1

FHY50BVE × 3

FHY71BVE × 3

FHY50BVE X 4

FHY60BVE × 4

RY140LUY1

RY200KUY1

RY200KUY1

RY250KUY1

FDYB71KAVE × 3

FDYB50KAVE × 4

FDYB60KAVE × 4

RY200KUY1

RY200KUY1

RY250KUY1

RY200KUY1

RY250KUY1

CEILING MOUNTED CASSETTE TYPE Indoor unit Outdoor unit

Simultaneous control with 4 units for large space

CEILING SUSPENDED TYPE Indoor unit Outdoor unit

DUCT CONNECTION LOW STATIC PRESSURE TYPE Indoor unit Outdoor unit

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

FDYM03FAV1 × 3

Indoor unit Outdoor unit

RY200KUY1

OUTDOOR UNIT Page 33– 34 RY140LUY1

9

RY200KUY1

10


CEILING MOUNTED CASSETTE TYPE Sound level

35/ 30

CEILING MOUNTED CASSETTE TYPE

Unified square panels

dB(A)

High

All models from the 35K to 140K use the same size panel. Multiple unit installations maintain a physical uniformity that is aesthetically pleasing and make it easier to plan ceiling lighting systems and to design interiors.

Low

FHYC71K

FH( Y) C

950 mm

Cooling only FH(Y)C35KVE–140KVE Heat pump FHYC35KVE–140KVE

Quiet, decor-blending form and easy installation in new or old buildings.

Optimal comfort and convenience assured by 3 air discharge modes

Same for all models

Air direction Desired situation

Draft prevention setting When drafts are unwanted

Auto-swing

5-levels air direction setting

Wireless LCD remote controller A s ignal rec eiver mus t be added to the indoor unit.

950 mm

BRC1C61 Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

Signal receiver unit (Installed type) Cooling only

BRC7C613W Heat pump

BRC7C612W

Indoor units use an aerodynamically designed Diffuser Turbo Fan

Wireles s remote c ontroller and s ignal rec eiver unit are s old as a s et.

For gentle drafts (Ceiling is soiled.)

Auto-s wing between 30° and 65°

Settable to 5 different levels between 10° and 40°

Settable to 5 different levels between 10° and 65°

Settable to 5 different levels between 30° and 65°

Draft prevention (In heating mode)

At heating s tartup and thermo OFF*, air direc tion is automatic ally s et to a near horizontal 10˚ to prevent direc t expos ure to c ool

Note: Air direc tion is s et to the s tandard pos ition when the unit is s hipped from the fac tory. The pos ition c an be c hanged from the remote c ontroller. *When the thermos tat turns off.

Multi-Flow System 4-way flow

3-way flow 4 pattern

Draft resistance has been reduced by incorporating, into a single unit, an impeller and a diffuser to control air flow inside the unit. The Diffuser Turbo Fan is both quiet during operation and compact. dB(A)

Indoor unit

High

Low

35K

33 33 35 35 39 42 44

29 29 30 30 34 36 37

60K 71K 100K 125K 140K

Wide air distribution A newly shaped air discharge opening increases flow without increasing wind speed, hence discharged air reaches farther than before. Air discharge distribution comparison •125K

B lade

50K

At heating startup and thermo OFF*, air discharge is automatically set to 30˚ to prevent both direct exposure to cool air drafts and con-

The air direc tion is s et automatic ally to the memoris ed pos ition of the previous air direc tion. (Initial s etting is 65˚ for heating and 30˚ for c ooling.)

1 pattern

Diffus er

When ceilings must be kept spotless

Auto-s wing between 10° and 65°

Auto air direction control

Compact body and quiet operation

Setting to prevent soiling of ceiling

Auto-s wing between 10° and 40°

Accessory required for indoor unit (option) Wired LCD remote controller

Standard setting

2-way flow

4 (m)

" " denotes piping direction. " " denotes sealing member for air discharge outlet (option) . Note: For 3-way or 2-way flow ins tallation, the s ealing member for air dis c harge outlet (option) mus t be us ed to c los e off the unus ed outlet(s ).

Air direction can be selected according to installation. Note: Operation s ound inc reas es when us ing 2-way or 3-way

2.5 m/sec 2 2.0 m/sec 1.5 m/sec 1.0 m/sec 1 0.5 m/sec

0.5 m/sec

3 pattern

3

2

1

0

1

2

Air discharge temperature comparison •125K

3

4 (m)

(In heating)

(m) 3.2 3

Super Cassette

(m) Conventional model 2.7 33˚C 30˚C 2 27˚C 1

3

33˚C 30˚C 27˚C

2

1

2 1

25˚C

25˚C

22˚C 4 (m)

(m) 3.2 3

Super Cassette

(m) Conventional model 2.7 2.5 m/sec 2.0 m/sec 2 1.5 m/sec 1.0 m/sec 1

22˚C 0

1

2

3

4 (m)

Suitable for high ceilings Criteria for ceiling height and number of air discharge outlets Number of air discharge outlets used

35K–71K 4-way flow Standard Ceiling High ceiling height High ceiling

Note : Anec hoic c hamber c onvers ion value, meas ured ac c ording to J IS parameters and

3-way flow

2-way flow

100K–140K 4-way flow

3-way flow

2-way flow

2.7 m 3.0 m 3.5 m 3.2 m 3.6 m 4.2 m 3.0 m 3.3 m 3.8 m 3.6 m 4.0 m 4.2 m 3.5 m 3.5 m 4.2 m 4.2 m -

Note: Initial s ettings are for s tandard c eiling height and 4-way flow. High c eiling s ettings 1 and 2 are s et from the remote

Programme "Dry" Two selectable temperature-sensors Both indoor unit and wired remote controller (option) contain temperaturesensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.

11

Guide Line up P. 3–10

Outdoor units P. 33–34

Remote controllers P. 35–36

Standard specifications P. 39, 46, 49, 54

Options P. 57

Outer dimension drawings P. 60

*Temperature-s ens or on indoor unit mus t be us ed when the air c onditioner is c ontrolled from another room. **Wireles s remote c ontroller does not have a

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Switchable fan speed: High/Low

12


CEILING MOUNTED CASSETTE TYPE Easier to maintain

Dust can be kept from blowing onto ceilings by directly setting flaps by hand or by remote control.

The new long-life filter is 20% more efficient than the previous one. This has enabled further reductions in running costs by extending the heat-exchanger cleaning interval by once every two years to once every three years.

Conventional

Super Cassette

*1 298 mm high with 100K – 140K *2 303 mm high with 100K – 140K

U lt r a lo n g -life filt e r

P a n e l s pa c e r

Even in smoky environments where the air conditioning is on most of the time, the ultra long-life filter only has to be changed once a year.

Use when only minimal space is available between drop ceilings and ceiling slabs.

Smoky atmosphere: annual filter change *For dust concentration of 0.3 mg/m3 (Requires separately sold Air Cleaner.) 1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year

S e a lin g m e m be r fo r a ir d is c h a r g e o u t le t

3 years

Conventional

Super Cassette

H ig h -e ffic ie n c y filt e r

B r a n c h d u c t c h a m be r

Available in two types: 65% and 90% colorimetry.

This chamber lets you connect a round flexible duct to the air discharge opening at any time after the original installation.

F r e s h a ir in t a k e k it

Less cleaning work thanks to "Non-dew Flaps" with non-flocking The use of non-flocking flaps minimises adnerring dart, so less cleaning work is needed.

Installable in any direction

Self-diagnosis function

Using this kit, a duct can be fitted to increase the intake of outdoor air.

Outside Note: *C onnec ting duc ts , ins ec t nets , fire dampers , air filters , and other

parts s hould, as required, be proc ured loc ally. **Outs ide Air fan interloc ked with air c onditioning unit is nec es s ary. Optional PC B (K R P1C 63)is required for interloc king. ***It is rec ommended that the volume of outdoor air introduc ed through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introduc ing higher quantities will inc reas e the operating nois e and may als o influenc e temperature s ending.

Low gas pressure detection Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.

The units can be installed in the following different ways. Chamber type (without T-joint pipe and fan) Kit name: KDDP55D160

Since the orientation of the intake grill can be adjusted after installing, the direction of the intake grill lines can be unified when multiple units are installed.

Chamber type (with T-joint pipe and without fan) Kit name: KDDP55D160K

Flexible duct (procured locally)

Flexible duct

T-joint pipe (procured locally)

T-joint pipe

Direct installation type Kit name: KDDJ55X160

Suction chamber Connection chamber

Figure 1)

Signal receiver unit

Notes : R equires an ins pec tion port for maintenanc e ac c es s . For dual intake duc t ins tallation only. If only a s ingle intake duc t c an be c onnec ted bec aus e of an obs truc tion, etc ., K DDP55D160 s hould be us ed ins tead. It is not pos s ible to us e this kit s imultaneous ly with the wireles s remote c ontroller.

Refrigerant piping

Notes: R equires an inspection port for maintenance access. If intake ducts cannot be connected to both connection chambers due, for example, to an obstruction, single intake duct installation is possible. Figure 1 shows what the installation will look like

750 mm

Note: Us e of options will inc reas e operating s ound.

Cooling only Heat pump DoubleTwin Multi Operation

*1Applic able *2Applic able *3Applic able *4Applic able

*1

*2

*4

*4

*1

*3

*4

*4

Option

Others

PE fin

Auto-res tart

S elf-diagnos is func tion

Control features E mergenc y operation

Low gas pres s ure detec tion

C eiling s oiling prevention

Filter s ign

Long-life filter

Pre c harged for up to 30 m

Work & Servicing Drain pump mec hanis m

Mould res is tant treatment for filter

Year-round c ooling applic able

Hot s tart

Two s elec table temperature-s ens ors

S witc hable fan s peed

Draft prevention func tion

Model

S wing pattern s elec tion

Auto s wing

The high-performance filter and other options are easily clipped into place. There is no need for a screwdriver.

Supports simultaneous running of the twin, triple, and double twin multi operation.

Mould prevention

Comfort High c eiling applic ation

Easy installation for options

(Features are explained on P. 37–38.)

Feature

Programme "Dry"

Features

Triple Multi Operation

Intake duct (procured locally)

Intake duct Connection (procured locally) chamber (duct length: 4 m max.)

Intake duct (procured locally) (duct length: 4 m max.)

Drain pump is equipped as standard accessory with 750 mm lift.

Duct flange (with insulation material)

Suction chamber

Twin / triple / double twin multi operation

All models suspended without lift

2 years

High-effic ienc y filter

Note: If the wireless remote c ontrol option is installed, a light rec eptor unit is housed in one of the adjuster poc k-

Move to 0° 1 Move to des ired angle

Sealing members block air discharge openings not used in 2-way or 3-way blow.

Fres h air intake kit

Each corner of the unit has an Adjuster Pocket that lets you easily adjust the unit's suspended height.

1 2

*For dust concentration of 0.15 mg/m3 4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 4 years

Ultra long-life filter

Easy height adjustment

less ce ilin dirt tha g Move flaps n before direc tly to des ired angle

Heat-exchanger cleaning interval

258 mm

40 mm

Ordinary store or office: filter change every 4 years

30%—40%

Twin Multi Operation

Note: S ome c eiling c ons truc tions may hinder ins tallation. 40 mm C ontac t your DaiPanel spacer Panel spacer kin Dealer before ins talling your unit. For 35K–71K indoor units For 100K–140K indoor units 200 mm

Interloc k c ontrol

245 mm *2

Heat exchanger cleaning required only once every 3 years

Timer s elec tor

240 mm *1

Stepping motor controls flaps to prevent soiled ceilings

C entral remote c ontrol

Just 240 mm high. Installable in tight ceiling spaces (35K–71K)

Options required for specific operating environments

Auto-c ooling/heating c hange-over C ontrol by 2 remote c ontrollers C ontrol by 1 remote c ontroller E xternal c ommand c ontrol

Quick and easy to install

when wired remote c ontroller is us ed to R 71LU– R 140LU outdoor units (for temp. down to – 15°C ) (An option is required.) to R Y71LU– R Y140LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C ) to R (Y)71LU– 140LU outdoor units

See pages 31–32 for details of the Multi Series.

13

14


CEILING SUSPENDED TYPE Sound level

CEILING SUSPENDED TYPE

39/ 35

Spreads comfortable air throughout the room

dB(A)

High

Auto-swing for comfort in all directions

Low

FHY71B

Both indoor unit and wired remote controller (option) contain temperature-sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.

dB(A)

Accessory required for indoor unit (option) Wired LCD remote controller

A s ignal rec eiver mus t be added to the indoor unit.

BRC1C61 Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

Cooling only

BRC7EA66 Heat pump

BRC7E63W

Wireles s remote c ontroller and s ignal rec eiver unit are s old as a s et.

37 38 38 39 42 44

32 33 33 35 37 39

125B

Note : Anec hoic c hamber c onvers ion value, meas ured ac c ording to J IS parameters and

Uses quiet stream fan and other quiet technologies.

Sound damper

Installation flexibility for freedom of design

Drain pump kit (option) can be easily incorporated

Uniform height and depth. Compact design for small-capacity models to meet tighter dimensional constraints. Signal receiver unit (Installed type)

35B

71B

Switchable fan speed: High/Low

Wireless LCD remote controller

Low

100B

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Installable on ceilings 3.5 m high

High

60B

Programme "Dry"

100°

Indoor unit

50B

*Temperature-sensor on indoor unit must be used when the air c onditioner is c ontrolled from another room. **Wireless remote controller does not have a temperaturesensor.

Cooling only FH(Y)35BVE–125BVE Heat pump FHY35BVE–125BVE

Upgrade to a quiet and compact system.

Sound operation has been reduced on the exposed ceiling suspended type unit.

Two selectable temperature-sensors

Wide air discharge openings produce a spreading 100° airflow

FH( Y)

Quiet operation

Drain pipe connection can be done inside the unit. Refrigerant and drain pipe outlets are at the same opening.

(mm)

Indoor unit 35B/50B 60B/71B 100B Height Width Depth

125B

195 960

1,160

1,400

Two time settings (2500 hrs and 1250 hrs) are available to match the installation environment. Maintenance time warning is displayed on the remote controller (filter sign).

Non-dew flap without bristles

All wiring and internal servicing done from below the unit

The unit fits more snugly into tight spaces.

Absence of bristles minimises clinging dirt and simplifies cleaning.

Pipes more easily rigged, too

For 71B indoor unit

Non-dew flap

Plastic panels are used to conceal piping holes. Holes can be easily punched out without requiring special tools.

Dimens ions in brac kets are for previous model.

1,160 mm (1,300 mm) 1,220 mm (1,420 mm)

* For dust concentration of 0.15 mg/m3

Drain pump kit (built inside main unit)

Reduced edge space, more flexible installation

(60 mm)

Long-life filter lasts about 1 year * Maintenance not required

600 mm

Weight of all models reduc ed (down 10% c ompared with previous models ). Trans fer and ins tallation work is les s arduous .

30 mm

Easy-clean, flat surfaces It is easy to wipe dirt off the flat side and lower surfaces of the unit.

For all maintenance tasks, access is from bottom surface.

(60 mm)

Low gas pressure detection

*Water used in the test-run can now be drained from the air discharge opening rather than from the side as was formerly the case.

Quiet stream fan

Easier to maintain

1,590

680

30 mm

Turbulent flow Straightening is produced vane

Improved-oil resistant grille Supports simultaneous running of the twin, triple and double twin multi operation. Twin Multi Operation

Triple Multi Operation

Oil-resistant plastic is used for the air discharge grille. This improves durability in restaurants and other similar environments.

DoubleTwin Multi Operation

Note: Intended for use in salons, dining rooms, and ordinary sales floors, this specification is not suitable for kitchens or other harsh environments. See pages 31–32 for details of the Multi Series.

(Features are explained on P. 37–38.)

15

Guide Line up P. 3–10

Outdoor units P. 33–34

Remote controllers P. 35–36

Standard specifications P. 39, 47, 49, 55

Options P. 57

Outer dimension drawings P. 60

*1Ins tallable on max. 3.5 m high c eiling *4Applic able to R Y71LU– R Y140LU outdoor units (for temp. down to – 5°C ) *2Applic able when wired remote c ontroller is us ed and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C ) *3Applic able to R 71LU– R 140LU outdoor units (for temp. down to – 15°C *5Optional ) available 6 * Applic able to R (Y)71LU– 140LU outdoor units (An option is required.)

PE fin

Twin / triple / double twin multi operation

Others

Interloc k c ontrol

C entral remote c ontrol

E xternal c ommand c ontrol

C ontrol by 1 remote c ontroller

C ontrol by 2 remote c ontrollers

Auto-c ooling/heating c hange-over

Auto-res tart

Control features S elf-diagnos is func tion

E mergenc y operation

Low gas pres s ure detec tion

Filter s ign

*6

Long-life filter

*6

*6

Mould-proofing drain pan

Pre c harged for up to 30 m

Mould res is tant treatment for filter

*6

*5

Timer s elec tor

*5

*4

Year-round c ooling applic able *3

*2

Hot s tart

*2

Two s elec table temperature-s ens ors

High c eiling applic ation *1

S witc hable fan s peed

Draft prevention func tion

Work & Servicing Drain pump mec hanis m

Cooling only Heat pump

Auto s wing

Model

Mould prevention

Comfort

Feature

Programme "Dry"

Features

16


CEILING SUSPENDED CASSETTE TYPE Sound level

The auto-swing function increases comfort level

dB(A)

High

Low

Ultra-thin with quiet operation

Auto-swing

5-levels air direction setting

Auto-air direction control

Auto-swing between 0° and 60°

Settable to 5 different levels between 0° and 60°

The air direction is set automatically to the memorised position of the previous air direction. (Initial setting is 60° for heating and 30° for cooling.)

Thinner usually means noisier, but Daikin's exclusive technology has solved this.

FUY71FJ

Heat exchanger

Ultra-thin, quiet design made possible by new Flat Turbo Fan.

At heating startup and thermo OFF*, air direction is automatically set to horizontal

Draft prevention (in heating)

Through use of a high-static-pressure vane and a thorough reduction in flow loss in the path between internal fan suction and air output, we have achieved a thinner fan unit and quiet operation while maintaining airflow.

*When the thermos tat turns off.

Air direction can be selected according to installation Selection patterns for air direction and fan speed ratio Note: Applicable only to the flow configurations shown below.

Wireless LCD remote controller

*R equires sealing member for air discharge outlet (optional ac c es s ory) for oppos ing 2-

Moderate (approx. 70%)

dB(A)

2-way flow BRC1C61 Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

Cooling only

BRC7C529W Heat pump

BRC7C528W

Wireles s remote c ontroller and s ignal rec eiver unit are s old as a s et.

Suitable for high ceilings

Two selectable temperature-sensors

Criteria for ceiling height and number of air discharge outlets

Both indoor unit and wired remote controller (option) contain temperaturesensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.

3.5 m 3.8 m —

Standard

Ceiling High ceiling 1 height High ceiling 2

3-Way 3-wayAirflow Flow 4-Way 4-wayAirflow Flow

3.0 m 3.3 m 3.5 m

2.7 m 3.0 m 3.5 m

Note: Initial s ettings are for s tandard c eiling height and 4-way flow. High c eiling s ettings 1 and 2 are s et from the remote

Simply lock the body in place with suspension bolts to install. Adjustment is smooth and simple, too.

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Since the orientation of the intake grill can be adjusted after installing, the direction of the intake grill lines can be unified when multiple units are installed.

Accessible from below for easy maintenance

(Features are explained on P. 37–38.)

Cooling only Heat pump

17

Outer dimension drawings P. 61

*1

*2

*4

*4

*1

*3

*4

*4

Control features S elf-diagnos is func tion

E mergenc y operation

Low gas pres s ure detec tion

Filter s ign

Long-life filter

Pre c harged for up to 30 m

Work & Servicing Drain pump mec hanis m

Mould-proofing drain pan

Timer s elec tor

Year-round c ooling applic able

Hot s tart

Two s elec table temperature-s ens ors

High c eiling applic ation

S witc hable fan s peed

Draft prevention func tion

S wing pattern s elec tion

Auto-s wing

Mould res is tant treatment for filter

Mould prevention

Comfort

Feature

Model

Note: The panel cannot be turned when the wireless remote controller is in use.

Low gas pressure detection

Programme "Dry"

Features

T-type hexagon wrench

Installable in any direction

Easier to maintain

* For dust concentration of 0.15 mg/m3

Hook

500 mm

Switchable fan speed: High/Low

Long-life filter lasts about 1 year * Maintenance not required

Suspension bolt

Drain pump is equipped as standard accessory with 500 mm lift.

*Temperature-sensor on indoor unit must be used when the air c onditioner is c ontrolled from another room. **Wireless remote controller does not have a

Programme "Dry"

Options P. 57

35 38 39

Simple installation procedure

Number of air discharge outlets used

Standard specifications P. 40 and 50

40 43 44

Quick and easy to install

2-way flow

Remote controllers P. 35–36

71FJ

Note : Anec hoic c hamber c onvers ion value, meas ured ac c ording to J IS parameters and

Note: When 2- or 3-way flow configurations are selected, the unused flow outlets must be blocked off with the optional sealing material. Sound during operation will rise by about 2 dB.

Outdoor units P. 33–34

Low

125FJ

3-way flow 4-way flow

Guide Line up P. 3–4, 7–8

High

100FJ

Piping position

Signal receiver unit (Installed type)

Indoor unit

*1Applic able when wired remote c ontroller is us ed *3Applic able to R Y71LU– 125LU outdoor units (for temp. down to – 5°C ) *2Applic able to R 71LU– 125LU outdoor units (for temp. down to – 15°C*4)Applic able to R (Y)71LU– 125LU outdoor units (An option is required.)

E xternal c ommand c ontrol C entral remote c ontrol

A s ignal rec eiver mus t be added to the indoor unit.

Standard (100%)

C ontrol by 1 remote c ontroller

Wired LCD remote controller

C ontrol by 2 remote c ontrollers

Flexibility in installation location. Installation is also simple.

Accessory required for indoor unit (option)

Auto-c ooling/heating c hange-over

Cooling only FUY71FJV1–125FJV1 Heat pump FUY71FJV1–125FJV1

Auto-res tart

FUY

Sliding shutter Closes to moderate airflow (70%)

Others

PE fin

40/ 35

Interloc k c ontrol

CEILING SUSPENDED CASSETTE TYPE

18


CEILING MOUNTED CASSETTE CORNER TYPE Sound level

41/ 36dB(A)

CEILING MOUNTED CASSETTE CORNER TYPE

High

Multiple airflow variations for stepped or 3.8 m high ceilings

Low

1 Downward flow

FHYK71FJ FHYK71FJ

Quiet operation dB(A)

2 Downward flow + Forward flow

Indoor unit

High

Low

35F(J)

39 39 41 41

33 34 36 36

3 Forward flow

45F(J)

Airflow variation

FH( Y) K

60F(J) 71F(J)

Note : Anec hoic c hamber c onvers ion value, meas ured ac c ording to J IS parameters and

Auto-swing

Cooling only FH(Y)K35FV1–71F(J)V1 Heat pump FHYK35FJV1–71FJV1

Easier to install and service

High ceiling installation

R equires ceiling tap cutting.

R equires ceiling tap cutting.

Required options

Fits in ceiling corners. Equipped for versatile airflow control.

Accessory required for indoor unit (option) Wired LCD remote controller

Air dis c harge grille, flexible duc t

Panel spacers (option) can be installed with all three airflow variations. Decoration panels (option) to hide the downward air discharge opening can be installed with variation 3 above. 500 mm

E x a m ple in s t a lla t io n s In the corner of a room (downward flow)

Comfortable cooling from ceiling to floor (downward flow)

Wind speed profile Heating (65° downward flow ... Standard installation)

BRC1C61 Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

Drain pump is equipped as standard accessory with 500 mm lift.

Not s uited for high c eilings because air currents do not

(m)

3.8 3

2.0 m/s 1.5 m/s 1.0 m/s 0.5 m/s 0.3 m/s

1 1

2

3

4

* For dust concentration of 0.15 mg/m3

Low gas pressure detection Fresh air intake possible

Air c onditioner

2.0 m/s 1.5 m/s 1.0 m/s 0.5 m/s 0.3 m/s

2 1 5

Long-life filter lasts about 1 year * Maintenance not required

Wind speed profile On stepped ceilings, downward flow Heating (65° downward flow from high ceiling) can be blocked and outward flow alone can be used to cool or heat the space.

3 2

On O n sstepped tepped cceiling ei l i n g (outward (Outward + downward downward flow) flow)

6 (m)

1

2

3

4

Dec orative panel (s old s eparately)

5

(Site installation required) A duct can be connected to the rear of the indoor unit to draw in outdoor air.

C over here with dec orative panel.

Decorative panels (option) can be installed on the downward air discharge opening to close gaps without stepped room interiors.

6

K eep duc t no more than 5 m long.

Optimal comfort and convenience assured by three air discharge modes Draft prevention setting

Air direction

When drafts are unwanted

Desired situation

Standard setting

Note: The maximum duc t length for c onnec tion to the fres h air intake kit is 5 m. C onnec ting duc ts , ins ec t nets , fire dampers , air filters , and other parts s hould, as required, be

Setting to prevent soiling of ceiling

For gentle drafts (Ceiling is soiled.)

When ceilings must be kept spotless

P a n e l s pa c e r ( o pt io n ) Auto-swing

5-levels air direction setting

Auto-s wing between 0° and 65°

Auto-s wing between 0° and 65°

Auto-s wing between 0° and 65°

Settable to 5 different levels between 0° and 65°

Settable to 5 different levels between 30° and 65°

Settable to 5 different levels between 40° and 65°

Use when only minimal space is available between drop ceilings and ceiling slabs.

20mm

C eiling

Panel s pac er

Draft prevention (In heating) model

At heating s tartup and thermo OFF*, air dis c harge is automatic ally s et to a near horizontal 10˚ to prevent direc t expos ure to c ool air drafts .

Upgrade options for easy installation on stepped ceilings Air dis c harge grille

The air direc tion is s et automatic ally to the memoris ed pos ition of the previous air direc tion. (Initial s etting is 65° for heating and 30° for c ooling.)

Auto air direction control

Flexible duc t

Note: Air direc tion is s et to the s tandard pos ition when the unit is s hipped from the fac tory. The pos ition c an be c hanged from the remote c ontroller. *When the thermos tat turns off.

Programme "Dry" Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Cooling only Heat pump

19

Guide Line up P. 3–4, 7–8

Outdoor units P. 33–34

Remote controllers P. 35–36

Standard specifications P. 40 and 50

Options P. 58

Outer dimension drawings P. 61

*1

*3

*3

*2

*3

*3

*1Applic able to R 71LU outdoor units (for temp. down to – 15°C ) (An option is required.) *2Applic able to R Y71LU outdoor units (for temp. down to – 5°C ) *3Applic able to R (Y)71LU outdoor units

PE fin

Others

Interloc k c ontrol

C entral remote c ontrol

E xternal c ommand c ontrol

C ontrol by 1 remote c ontroller

Auto-c ooling/heating c hange-over C ontrol by 2 remote c ontrollers

Auto-res tart

S elf-diagnos is func tion

Control features E mergenc y operation

Low gas pres s ure detec tion

C eiling s oiling prevention

Filter s ign

Long-life filter

Pre c harged for up to 30 m

Work & Servicing Drain pump mec hanis m

Timer s elec tor

Year-round c ooling applic able

Hot s tart

High c eiling applic ation

Programme "Dry"

Draft prevention func tion

S wing pattern s elec tion

Mould res is tant treatment for filter

Mould prevention

Comfort

Auto s wing

Model

For outward blow, detach the punch-out panel from the duct-connection port on the front of the unit.

(Features are explained on P. 37–38.)

Feature

S witc hable fan s peed

Features

Switchable fan speed: High/Low

20


CEILING MOUNTED BUILT-IN TYPE Sound level

CEILING MOUNTED BUILT-IN TYPE

41/ 35 High

Meets diverse of installation needs

Flexibly adapts to shop interiors

dB(A)

To cope with the challenges of Lshaped or U-shaped spaces, it is possible to install the air discharge unit away from the main unit. At the same time, different types of architectural space can be kept comfortable.

Low

FHYB71F

FH( Y) B

The indoor unit can be installed in rooms with as little as 350 mm between the drop ceiling and ceiling slab. It also works with both flexible and ordinary ducts. S t a n da r d in s t a lla t io n e x a m ple s In crawl space 6

With canvas bellows and air intake panel (sold separately) 2 Air conditioner

4

2 Air conditioner

350 mm or more

4

6 5

1

Air blow

Cooling only FH(Y)B35FV1–125FV1 Heat pump FHYB35FV1–125FV1

425 mm or more 3

Long-life filter

Air intake Long-life filter

5

1

Air intake

Air blow

45 mm

W it h h ig h -e ffic ie n c y filt e r

C e ilin g r e t u r n

2 Air conditioner

L-shaped space

Clever and compact mini ducted unit provides comfort and flexibility.

Accessory required for indoor unit (option) Wired LCD remote controller

U-shaped space

Long space

4

13

6

2 Air conditioner

540 mm or more

7

450 mm or more

4

6

Air intake

Long-life filter

3 8

5

Programme "Dry"

5

1

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Air blow

Air intake

Air blow

C e iling re turn w ith high-e ffic ie nc y filte r 2 Air conditioner 6

Switchable fan speed: High/Low

4

9

W it h o r d i n a r y d u c t s Ordinary duct (procured locally)

540 mm or more Air intake 7

Ordinary duct (procured locally)

Air conditioner

10

11

460 mm or more

9 8

8

5

Air intake

Air blow

Air blow

Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

Options

Quiet operation

5 1

dB(A)

Indoor unit

High

Low

35F

38 39 41 41 41 44

32 34 35 35 35 38

45F 60F 71F 100F 125F

4

2 3

Decorative panel Air discharge opening adapter Canvas bellows and air intake panel

6 7 8

Flexible duct Air discharge grille Air discharge chamber High-performance filter Inspection panel

Drain pump is equipped as standard accessory with 250 mm lift.

9 10 11 12 13

External static pressure can be set depending on duct length, presence of high-efficiency filter, and other installation conditions.

250 mm

External static pressure pattern

Note : Anec hoic c hamber c onvers ion value, meas ured ac c ording to J IS parameters and

Indoor unit

High

Standard

Low

35F–71F

78 98

39 39

20

100F and 125F

Fresh air intake possible

Easier to maintain

Note: The maximum duct length for connection to the fresh air intake kit is 5 m. C onnecting ducts, insect nets, fire dampers, air filters, and other parts should, as required,

Low gas pressure detection Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.

21

Guide Line up P. 3–4, 7–8

Outdoor units P. 33–34

Remote controllers P. 35–36

Standard specifications P. 41, 51

Options P. 58

Outer dimension drawings P. 62

H ig h -e ffic ie n c y filt e r ( o pt io n ) Available in two types: 65% and 90% colorimetry. This filter easily meets dust collection efficiency regulations specified in building codes.

Options have also been upgraded to make installation even easier. Air discharge opening adapter Air discharge chamber Air Flexible duct Flexible duct discharge (dia. 200 mm) (dia. 150 mm) grille Canvas bellows Decorative panel Branch duct and air Intake panel

(Features are explained on P. 37–38.)

*1

*3

*3

*2

*3

*3

*1Applic able to R 71LU– R 125LU outdoor units (for temp. down to – 15°C ) (An option is required.) *2Applic able to R Y71LU– R Y125LU outdoor units (for temp. down to – 5°C ) *3Applic able to R (Y)71LU– 125LU outdoor units

High-effic ienc y filter

Option Others

Interloc k c ontrol

E xternal c ommand c ontrol C entral remote c ontrol

C ontrol by 1 remote c ontroller

Auto-c ooling/heating c hange-over C ontrol by 2 remote c ontrollers

Auto-res tart

Control features S elf-diagnos is func tion

E mergenc y operation

Low gas pres s ure detec tion

Filter s ign

Long-life filter

Pre c harged for up to 30 m

Work & Servicing Drain pump mec hanis m

Timer s elec tor

Year-round c ooling applic able

Hot s tart

Programme "Dry"

S witc hable fan s peed

Mould res is tant treatment for filter

Mould prevention

Comfort

Feature

Cooling only Heat pump

External static pressure is set to standard when the unit is shipped from the factory.

A duct can be connected to the rear of the indoor unit to draw in outdoor air.

* For dust concentration of 0.15 mg/m3

Model

(Pa)

(Custom installation required with locally procured materials)

Long-life filter lasts about 1 year * Maintenance not required

Features

Rear intake blocking pad Air discharge opening flange Rear intake filter chamber Branch duct Low-draft filter chamber

PE fin

BRC1C61

22


WALL MOUNTED TYPE Sound level

43/ 37dB(A)

WALL MOUNTED TYPE

High

Drastic size reduction

Low

FAY71L

FAY

Sound level

5-level air direction setting

10°

Auto-s wing from 10° to 70°

-70 mm

dB(A)

-200 mm

Low

10°

S ettable to 5 different levels between 10° to 70°

70°

70°

290 mm

FAY100FA

Auto-air direction control

10°

(FAY71FAVE)

45/ 41 High

Auto-swing

Reduced size (by 22% in volume, 32% in installation area)makes installation possible in a very limited Conventional model space.

FAY71LVE

Cooling only FAY71LVE / FAY100FAVE Heat pump FAY71LVE / FAY100FAVE

Improved airflow modes realise comfortable air distribution across the entire room

Below features only apply to FAY71L.

The air direction is set automatically to the memorised position of the previous air direction. (Initial setting is 10° for cooling 70° and 70° for heating.)

Comfort even on the far side of the room To carry air to the far side of long rooms, extrahigh airflow adds 10% more fan speed the "high" setting. Air discharge strength is selected from the remote controller.

1,050 mm

Made more compact, stylish, and quieter

Sophisticated extension design

FAY100FAVE Accessory required for indoor unit (option) Wired LCD remote controller

Wireless LCD remote controller A s ignal rec eiver mus t be added to the indoor unit.

Signal receiver unit (Installed type)

Compact and stylish design that does not detract from the decor of the room.

Two selectable temperature-sensors

Flap is closed when not operating Easier to install and service

Cooling only

Light weight

BRC7E619 Heat pump

BRC7EA618 BRC1C61

FAY71L

Cooling only

BRC7C611W Heat pump Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

BRC7C610W

FAY100F Wireles s remote c ontroller and s ignal rec eiver unit are s old as a s et.

Reduced weight by 8kg greatly facilitates installation. Conventional

New model

(FAY71FAVE)

(FAY71LVE)

21 Kg

13 Kg

Easier to install and service

Both indoor unit and wired remote controller (option) contain temperaturesensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.

Maintenance possible from the front of the unit All maintenance tasks can be carried out via front access. During service work, attachment and detachment of parts is easier.

*Temperature-sensor on indoor unit must be used when the air c onditioner is c ontrolled from another room. **Wireles s remote c ontroller does not have a

Low gas pressure detection Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.

Programme "Dry"

Drain pump kit is available as option.

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Installs onto side of unit. Height of drain up

Switchable fan speed: High/Low

1,000 mm Indoor unit

Drain-pump kit (Available to be installed onto right side.)

Drain enclosure can be used on either left and right side. Drain pan and air filter can be kept clean by mould-proof polystyrene

Removable and washable grille DIII-NET connection is standard specification. Adapter is not required. (Features are explained on P. 37–38.)

Cooling only Heat pump

23

Guide Line up P. 3–4, 7–8

Outdoor units P. 33–34

Remote controllers P. 35–36

Standard specifications P. 41, 51

Options P. 58

Outer dimension drawings P. 62, 63

*1Applic able *2Applic able *3Applic able *4Applic able

*1

*2

*4

*4

*1

*3

*4

*4

PE fin

Others

Interloc k c ontrol

C entral remote c ontrol

E xternal c ommand c ontrol

C ontrol by 2 remote c ontrollers C ontrol by 1 remote c ontroller

Auto-c ooling/heating c hange-over

Auto-res tart

Control features S elf-diagnos is func tion

E mergenc y operation

Low gas pres s ure detec tion

Filter s ign

Pre c harged for up to 30 m

Work & Servicing Drain pump mec hanis m

Mould-proofing drain pan

Mould res is tant treatment for filter

Timer s elec tor

Year-round c ooling applic able

Hot s tart

Upward

Two s elec table temperature-s ens ors

Programme "Dry"

S witc hable fan s peed

Draft prevention func tion

Auto s wing

Model

Mould prevention

Comfort

Feature

High fan s peed mode

Features

when wired remote c ontroller is us ed to R 71LU/R 100LU outdoor units (for temp. down to – 15°C ) (An option is required.) to R Y71LU/R Y100LU outdoor units (for temp. down to – 5°C ) to R (Y)71LU/100LU outdoor units

24


FLOOR STANDING TYPE Sound level

FLOOR STANDING TYPE

41/ 35

Quiet operation

dB(A)

High

Easier to install and service dB(A)

Low

FVY71LA

Indoor unit

High

Low

71LA

41 46 49

35 40 43

100LA

FVY

125LA

Lightweight The unit can be easily transported and installed.

Note : Anec hoic c hamber c onvers ion value, meas ured ac c ording to J IS parameters and

Weight

Auto-swing delivers comfort to every corner of the room

Cooling only FVY71LAVE–125LAVE Heat pump FVY71LAVE–125LAVE

The floor-standing configuration means the FVY is easy to install and maintain. It can also be installed under high ceilings.

Conventional FVY-F

New model

71 class

45 kg 63 kg 67 kg

39 kg 46 kg 47 kg

100 class

FVY units have swinging louver spreads comfortable airflow. Any uncomfortable sensation of sudden change is avoided by a slow cycle of 2 to 3 full swings per minute.

125 class

Manual setting of vertical airflow louvers

Auto-swing

Indoor unit

Long-life filter lasts about 1 year * Maintenance not required *For dust concentration of 0.15 mg/m3

LCD control panel is standard

Filter exchange interval

Vertical airflow adjustment is possible when (changing between cooling and heating or) to match interior spaces and partitions.

Note: This remote controller has a temperaturesensor.

A good choice for spaces with ceilings so high that heating by ceiling-mounted units is inefficient.

Annual Long-life filter

Low gas pressure detection Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.

Programme "Dry" Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Note: For optimal installation, space factors should be accurately calculated.

2 weeks Conventional filter

Switchable fan speed: High/Low

Easy-to-operate, handy LCD control panel The LCD displays text, numbers and graphics to indicate the temperature setting, timer setting, auto-swing, fan speed, and more. Furthermore, the LCD panel can be detached and used as a remote controller, so air conditioning can be controlled from another room or from the cash register. (Remote controller cable not included. Cables must be procured locally.)

Two selectable temperature-sensors Temperature-sensors on both indoor unit and wired remote controller. Temperature sensing can be set closer to the target area to further improve comfort level. *Temperature-sensor on indoor unit must be used when the air c onditioner is c ontrolled from another room. **Wireles s remote c ontroller does not have a temperature-s ens or.

(Features are explained on P. 37–38.)

Cooling only Heat pump

25

Guide Existing Line up models: P.33–4, P. ~ 4 7–8

Outdoor units units: P.25 P. 33–34 ~ 26

Remote controllers controllers: P.27 P. 35–36 ~ 28

Standard specifications specifications: P.34 P. 42, 52

Options Outer dimension drawings Options: drawings: P.38 63~ 45 P.36 P. 58~ 37 P.

*1

*3

*3

*2

*3

*3

PE fin

Others

Interloc k c ontrol

C entral remote c ontrol

E xternal c ommand c ontrol

C ontrol by 1 remote c ontroller

C ontrol by 2 remote c ontrollers

Auto-c ooling/heating c hange-over

Auto-res tart

Control features S elf-diagnos is func tion

E mergenc y operation

Low gas pres s ure detec tion

Filter s ign

Long-life filter

Work & Servicing

Pre c harged for up to 30 m

Mould res is tant treatment for filter

Timer s elec tor

Two s elec table temperature-s ens ors Year-round c ooling applic able

Hot s tart

S witc hable fan s peed

Auto s wing

Model

Mould prevention

Comfort

Feature

Programme "Dry"

Features

*1Applic able to R 71LU– R 125LU outdoor units (for temp. down to – 15°C ) (An option is required.) *2Applic able to R Y71LU– R Y125LU outdoor units (for temp. down to – 5°C ) *3Applic able to R (Y)71LU– 125LU outdoor units

26


DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE Sound level

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

39dB(A)

Freedom of layout

(220V)

High

LOW

FDMG71A

42 44 45 46 47

38 36 37 36 37

FDMG125A FDMG140A

Duct connection is simpler with standard rear intake chambers

FDMG180A FDYM03FA

FDYM03FAV1–06FAV1 FDYM03FAV1–06FAV1

FDYM04FA

Compact, 295 mm high design makes installation possible where the ceiling space is limited (For FDYM)

FDYM05FA FDYM06FA

FDYM03FA

Unit can be mounted in the ceiling and air can be delivered freely by duct.

Indoor unit

FDMG100A

Middle static pressure type is available in a larger than standard space

FDMG100A

Cooling only FDMG71AV1–180AV1 Heat pump

dB(A) (220V)

The duct system allows the efficient location of discharge outlets in accordance with the room layout

High

FDYM03FA

FDMG/FDYM

Quiet operation

Note : Anec hoic c hamber c onvers ion value, meas ured ac c ording to J IS parameters and

Air conditioner 295 mm

Ordinary duct (procured locally)

Ordinary duct (procured locally)

Accessory required for indoor unit (option) For FDYM Wired LCD remote controller

39 39 44 46

Wireless LCD remote controller

Switchable fan speed: High/Low

305 mm or more Air intake

Air blow

Programme "Dry" Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature. BRC1C61 Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

Signal receiver unit (Separate type) Cooling only

BRC4C64 Heat pump

BRC4C62

For FDMG Digital remote controller

Wireles s remote c ontroller and s ignal rec eiver unit are s old as a s et.

Remote controller

KRC47-2A KRC47-4A

Low gas pressure detection Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.

Supports simultaneous running of the twin and triple multi operations. Twin Multi Operation

Triple Multi Operation

KRC47-1A See pages 31–32 for details of the Multi Series.

Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening) When air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicated ventilation grilles should be installed on the partitioning wall or under the door between the rooms.

27

Guide Line up P. 3–10

Outdoor units P. 33–34

Remote controllers P. 35–36

Standard specifications P. 43, 48, 53, 56

Options P. 59

Outer dimension drawings P. 64, 65

Under-door cutout

Ventilates air through the partitioning wall. (S ee right)

Partitioning wall

Ventilation grille

Ventilation grille

Under-door c utout

Note: The under-door cutout method should be used only when there is a small volume of airflow.

Adjus table external s tatic pres s ure

PE fin

Twin and triple multi operation

Others

Interloc k c ontrol

E xternal c ommand c ontrol C entral remote c ontrol

G roup c ontrol by 1 remote c ontroller

C ontrol by 2 remote c ontrollers

*3

Control features

Auto-res tart

*3

*3

S elf-diagnos is func tion

*3

*2

E mergenc y operation

*1

Timer s elec tor

Low gas pres s ure detec tion

Year-round c ooling applic able

Work & Servicing

Pre c harged for up to 30 m

Heat pump

FDMG FDYM

Programme "Dry"

S witc hable fan s peed

Model

Automatic c ool/heat c hange -over

Comfort

Feature

Cooling only

Wall-installed ventilation grille

(Features are explained on P. 37–38.)

Hot s tart

Features

Door-installed ventilation grille

*1Applic able to R 71LU– R 140LU outdoor units (for temp. down to – 15°C ) (An option is required.) *2Applic able to R Y71LU– R Y140LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C ) *3Applic able to R (Y)71LU– 140LU outdoor units

28


Sound level

DUCT CONNECTION LOW STATIC PRESSURE TYPE

DUCT CONNECTION HIGH STATIC PRESSURE TYPE

Sound level

38

dB(A) LOW

FDBG/FDYB

(220V)

FDYB50KA

Cooling only FDBG25AVE–71AVE Heat pump FDYB35KAVE–71KAVE

Accessory required for indoor unit (option)

dB(A)

High

FD( Y)

FDYB50KA

51

FDY06KA FDY06KA

Cooling only FD03KY1–20KY1 Heat pump FDY06KAY1–20KAY1

Accessory required for indoor unit (option)

Cooling only

Cooling only Digital remote controller

Remote controller

Remote controller

KRC47-2A KRC47-4A

KRC47-1A

KRC47-3A Heat pump

Heat pump

Wired LCD remote controller

Wired LCD remote controller

Signal receiver unit (Separate type)

BRC1C61 Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

BRC4C62

Note : Anechoic chamber conversion value, measured according to J IS parameters and criteria.

Highly durable outdoor unit has PE fins for improved resistance to salt corrosion and atmospheric pollution.

Durable

S uc tion c hamber

29

Adjus table external s tatic pres s ure

PE fin

Triple and double twin multi operation

*2

* Applic able to R Y71LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C ) *2Applic able to R Y71LU outdoor units

Guide Line up P. 3–10

*2

Outdoor units P. 33–34

Remote controllers P. 35–36

Adjus table external s tatic pres s ure

PE fin

Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)

1

*1

Others

*2Applic able to R (Y)140LU outdoor units *3R equired to c hange the pulley *4FDY06-10 only

Others

Interloc k c ontrol

C entral remote c ontrol

G roup c ontrol by 1 remote c ontroller E xternal c ommand c ontrol

C ontrol by 2 remote c ontrollers

Control features

Auto-res tart

S elf-diagnos is func tion

E mergenc y operation

Low gas pres s ure detec tion

Pre c harged for up to 30 m

Timer s elec tor

Work & Servicing Year-round c ooling applic able

Automatic c ool/heat c hange -over

Programme "Dry"

S witc hable fan s peed

Hot s tart

Comfort

Control features

Interloc k c ontrol

Hot s tart

(Features are explained on P. 37–38.)

Feature

Cooling only Heat pump

See pages 31–32 for details of the Multi Series.

Work & Servicing

C entral remote c ontrol

Double twin Multi Operation

Guide Line up P. 3–4, 7–8 Outdoor units P. 33–34 Remote controllers P. 35–36 Standard specifications P. 44, 45, 53 Model Options *3 Cooling only P. 59 *4 *1 *2 *2 *4 *3 Heat pump Outer dimension drawings *1Applic able to R Y140LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. downP. to 65–67 – 0°C )

Comfort

Feature

G roup c ontrol by 1 remote c ontroller E xternal c ommand c ontrol

Triple Multi Operation

(Features are explained on P. 37–38.)

C ontrol by 2 remote c ontrollers

To prevent increased operation sound, avoid installing the air suction grille directly below the suction chamber.

Auto-res tart

[Duc t c onnec tion]

Supports simultaneous running of the triple and double twin multi operations.

Model

Features

Air filter

S elf-diagnos is func tion

To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.

Features

Many options are available for use with large-scale and advanced-function centrally controlled systems

Durable

E mergenc y operation

39

BRC4C62

Wireles s remote c ontroller and s ignal rec eiver unit are s old as a s et.

Central control

Low gas pres s ure detec tion

42

Quiet operation

Pre c harged for up to 30 m

FDBG60AVE

Small, lightweight, and easy-to-install outdoor unit.

Timer s elec tor

Low

Year-round c ooling applic able

High

Automatic c ool/heat c hange -over

Indoor unit

Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

Recommended for spacious and large-volume areas because of its flexible installation Suitable for large stores, factories, and other large areas, and for use with housing ducts in homes

Compact dB(A)

Signal receiver unit (Separate type)

BRC1C61

Wireles s remote c ontroller and s ignal rec eiver unit are s old as a s et.

Ideal for quiet, beautiful living spaces Suitable for condominiums and apartments, houses and hotels

Quiet operation

Wireless LCD remote controller

Wireless LCD remote controller

Standard specifications P. 42, 52, 56

Options P. 59

Outer dimension drawings P. 64

When air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicate ventilation grilles should be installed on the partitioning wall or under the door between the rooms.

Door-installed ventilation grille

Partitioning wall

Wall-installed ventilation grille

Under-door cutout

Ventilates air through the partitioning wall. (S ee right) Ventilation grille

Ventilation grille

Under-door c utout

Note: The under-door cutout method should be used only when there is a small volume of airflow.

30


Simultaneous operation system

MULTI SERIES

Simultaneous operation system

Remote controllers for the Multi Series

MULTI SERIES

INDOOR UNIT

Wired LCD remote controller

Wireless LCD remote controller

(Option)

(Option)

Twin, Triple, and Double Twin Multi-Operation CEILING MOUNTED CASSETTE TYPE

Heat pump

BRC7EA66 BRC7E63W

Heat pump

BRC4C62

Cooling only

BRC4C64 BRC4C62

Cooling only

BRC1C61

DUCT CONNECTION LOW STATIC PRESSURE TYPE DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

In a single-floor restaurant, for example, positioning 4 units at strategic locations realises comfortable airflow that reaches every inch of the room.

In large interior spaces a single indoor unit may not be able to provide uniform comfort. Installation of 2 to 4 units, can provide an effective solution.

Heat pump

CEILING SUSPENDED TYPE

Simultaneously operates 2 to 4 indoor units using a single outdoor unit.

BRC7C613W BRC7C612W

Cooling only

Heat pump

A single remote controller controls simultaneous operation of multiple indoor units.

Connect the wired remote controller to turn an indoor unit into the master unit.

Install the signal receiver unit (part of the optional wireless remote controller) to turn an indoor unit into the master unit.

Supports Two selectable temperature-sensor functions.

Wired remote controller has a temperature-sensor. Depending on the installation conditions, select and set the temperature-sensor of a selected indoor unit or the temperaturesensor of the remote controller.

Because the wireless remote controller does not have a temperature-sensor, select the temperature-sensor of the indoor master unit.

Note: This type of system does not allow individual control or independent operation of indoor units. It is not the best choice for large rooms with partitions.

Installing multiple units is economical and realises comfort Lower cost of installation than for individual pair type Reduced installation space for outdoor units Enhanced comfort from distributed indoor units

Note: Selectable temperature sensing is available with ceiling-mounted cassette and ceilingsuspended models, but not with middle staticpressure models.

Note: An indoor unit's temperature-sensor must be used when the air conditioners are controlled from another room.

Indoor units include ceiling mounted cassette type, ceiling suspended type, and duct connection middle and low static pressure type.

Double Twin Multi operation

4 indoor units can be run simultaneously with a single outdoor unit.

Improved comfort level and space-saving for outdoor unit installation New

5 HP x 2 units

10 HP double twin multi operation

Twin Multi Operation

Triple Multi Operation Sub unit

Dead zone

Dead zone

Before

Piping Guideline

Branch piping kit

L1

Branch piping kit Branch piping kit

Required about 40% less installation space for outdoor unit Before

Sub unit

L2

Branch piping kit

Sub unit Main unit

L3

L3

Outdoor unit

L4

Sub unit

L5

L1 Branch piping kit

Remote controller

Main pipe L

Sub unit

L6

L2

Remote controller

Main pipe L

Outdoor unit

Outdoor unit

300 mm

R(Y)200KU or R(Y)250KU x 1 unit 500 mm

Simultaneous operation system

Max. piping length Max. branch piping length 300 mm 1000 mm

Max. branch pipe length difference

Twin Multi Operation L

Max. (L1, L2) Max. (L1, L2)*1

Max. (L1, L2)

50 m 20 m

Min. (L1, L2)*2

Triple Multi Operation

Double Twin Multi Operation

L

L

Max. (L1, L2, L3) Max. (L1, L2 , L3)

10 m

Max. (L1, L2, L3)

50 m 20 m

Min. (L1, L2, L3)

10 m

Max. (L1, L2)

Max. (L3, L4, L5, L6)

Max. (L1, L2)

Max. (L3, L4, L5, L6)

(L2 L6)

(L1 L3) 10 m L2 L1 10 m L4 L3 10 m L6 L5 10 m

In case of L1

Triple Multi operation

Main unit

New

R(Y)125KU x 2 units

4 indoor units distribute comfortable airflow throughout the room. Simultaneous operation of four indoor units can be controlled from a single remote controller. Requires a single refrigerant piping system.

L1

Remote controller

Main pipe L

Branch piping kit

Sub unit

Main unit

L2

Double Twin Multi Operation

Twin Multi operation

L2, L3

Max. level difference between outdoor unit and indoor units

30 m

30 m

30 m

Max. level difference between indoor units

0.5 m

0.5 m

0.5 m

L4, L5

50 m 20 m

L6

*1 Max. (L1, L2) means maximum length out of L1 and L2. *2 Min. (L1, L2) means minimum length out of L1 and L2.

Refrigerant piping uses terminal branching to facilitate installation. (Branch piping kits are sold separately. Please use the model indicated on page 59) Branch piping kit

Branch piping kit

31

Guide Line up P. 5–6, 9–10

Outdoor units P. 33–34

Remote controllers P. 35–36

Standard specifications P. 46–48, 54–56

Options Outer dimension drawings P. 57–59 P. 60–74

(For Twin Multi)

(For Triple Multi)

(For Double Twin Multi)

32


OUTDOOR UNIT

OUTDOOR UNIT

Compact unit provides quiet operation.

P o w e r fu l

Ins ta lla tion a nd ma intena nc e

Uses "Receiver" to enhance refrigerant control

Pre charged for up to 30 metres

(Applies to R(Y)71LU–140LU)

Instead of the using an accumulator to absorb excess refrigerant, Daikin outdoor units have a receiver in the piping located away from the compressor. By preventing the return of liquid to the compressor, the receiver enhances reliability.

Defrost control delivers powerful heating in extremely cold climates (Applies to RY71LU–140LU) (Heat pump only)

R(Y)125LU

R(Y)140LU

Q u ie t O pe r a t io n Fitted with wide inlet fan

Fitted with Super Aero Grille

(Applies to R(Y)71LU–140LU)

(Applies to R(Y)71LU–140LU)

Fully shaped aerodynamic propellers are designed to push air with a large wing surface, providing both high blow volume and quiet operation with turbulence.

To suppress turbulence and achieve quiet operation, the curved ribs of the grille are optimised to meet the outflow of air.

Equipped with scroll compressor for quiet operation (Applies to R(Y)125LU and 140LU)

Smooth running, minimal vibration, low operating sound.

Integral heating capacity and temperature difference (actual measurement when outdoor temperature is -1.5°C) 25

°C Defrost begins in this area Integral heating capacity

20 15 10 5

Max. point of integral capacity

R(Y)100LU

Defrost and hot start

R(Y)71LU

To optimise heating performance, by monitoring the difference in air temperature in the indoor/outdoor heat exchanger and the intake air temperature, the system accurately adjusts to provide the best operating parameters. This enables defrost mode to be initiated and so minimise indoor declines in temperature caused by frost. For example, if the outdoor airtemperature falls to -1.5°C, the integrated heating capacity is raised about 20%.

0 0

10

20

30

Difference between indoor heat exchange temperature and intake air temperature ( T)

40 50 60 70 80 Elapses operation time (min.)

Defrost operation complete Defrost monitoring start (heating operation restart) (monitors to maximum point)

Suited for year-round cooling applications

Wide inlet fan

Operation sound

(Applies to R(Y)71LU–140LU)

dB(A)

Heat pump Outdoor unit

Sound level (cool/heating)

RY71LU

48/49

Slim and low-profile design outdoor units

RY100LU

49/52

(Applies to R(Y)71LU–140LU)

RY125LU

49/52

RY140LU

54/56

Cooling only Outdoor unit

Sound level

R71LU

48

(Applies to R(Y)71LU-125LU)

R100LU

49

The light weight makes delivery and installation easier.

R125LU

49

R140LU

54

C o m pa c t Compactly designed outdoor unit with interior layout optimised for the smooth airflow.

Reduced weight

conventional

New

108 kg

89 kg

RY100KUV1

RY100LUV1

The design curved Super Aero Grille restricts the spread of exhaust gas and fits in the same space as conventional outdoor units.

50 500 (mm)

33

Note : Anec hoic c hamber c onvers ion value, meas ured ac c ording to J IS parameters and

Cooling is efficient even in winter when indoor temperatures are higher than those outside, such as in underground public spaces or offices with many computers.

If refrigerant piping length does not exceed 30 m, there is no need for onsite gas charging. (Applies to R(Y)71LU–140LU)

Flexible design for large room or multi-use

Allowed refrigerant pipe length and level difference Pre charged *1

Max. length

Max. level difference

R25J

10 m

25 m

15 m

RY35F

10 m

20 m

15 m

R35J RY50GA R50G RY60GA R60G RY71LU R71LU RY100LU R100LU RY125LU R125LU RY140LU R140LU RG71A RA140A RG180A R100FU R125FU

10 m

25 m

15 m

10 m

30 m

15 m

5m

30 m

15 m

30 m

50 m

30 m

50 m

30 m

50 m

30 m

50 m

30 m

50 m

30 m

50 m

30 m

30 m 30 m

(Equivalent length 70 m) (Equivalent length 70 m) (Equivalent length 70 m)

30 m

(Equivalent length 70 m)

5m

(Equivalent length 70 m)

5m

(Equivalent length 70 m)

Piping can be drawn out from three directions - front, left side, or below.

200 and 250 class models can be combined for centralised, horizontal-series installation

1

Note: Additional refrigerant charging is required if the refrigerant pipe is longer than the length.

Common width and depth make series installation easy.

4-direction piping offers greater layout freedom

R(Y)200KU R(Y)200KU R(Y)250KU

(Applies to R(Y)71LU–140LU)

Piping can be run from the front, bottom, right or rear surface according to how the unit is installed.

690 mm 1280 mm

1280 mm

1280 mm

Allowed refrigerant pipe length and level difference

Facilitates pump down (Refrigerant recovery function) A pump-down switch is provided to make it easier to collect refrigerant if the unit is to be moved or layout modified.

Pre charged *1

Max. length

Max. level difference

5m

50 m

30 m

50 m

30 m

R(Y)200KU R(Y)250KU

5m

(Equivalent length 70 m) (Equivalent length 70 m)

Note: 1Additional refrigerant charging is required if the refrigerant pipe is longer than the length.

Also adapts to year-round cooling Low gas level detection function (Applies to R(Y)71LU–140LU)

Effective gas monitoring reduces the labor required for operation, maintenance, and repairs.

RY200 KU a nd 250KU can adapt up to 0°C. (Heat pump only)

RU08/10K models are available in two type depending on installation conditions

• Heat pump/RY71–140LU: possible up to -5°C • Cooling only/R71–140LU: possible up to -15°C • The year-round cooling kit is required as option.

RU08/10KU models are factory shipped with refrigerant charged for 5 m of piping. RU08/10K models are factory shipped with no refrigerant charged.

D u r a bilit y Heat exchange fins provided with anti-corrosion treatment To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.

(Applies to all outdoor units)

Construction Non-treated fin

Aluminium

PE fin

Hydrophilic film Aluminium C orrosion resistant ac rylic resin

34


LCD REMOTE CONTROLLER

Easy-to-read LCD remote controller allows various system control configurations and can control multiple indoor units.

LCD REMOTE CONTROLLERS Necessary optional accessory

Remote controller options are shown on the page introducing each indoor unit model.

For easier operation, louver switches, which are frequently used, have been made larger. Oil-resistant plastic casing. Only 17 mm thick. Can be installed either recessed or exposed.

Indoor units applicable for the remote controller CEILING MOUNTED CASSETTE TYPE CEILING SUSPENDED TYPE CEILING SUSPENDED CASSETTE TYPE CEILING MOUNTED CASSETTE CORNER TYPE WALL MOUNTED TYPE CEILING MOUNTED BUILT-IN TYPE*1 DUCT CONNECTION LOW STATIC PRESSURE TYPE *2 DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE DUCT CONNECTION HIGH STATIC PRESSURE TYPE *2

BRC1C61

*1. When the auto-swing function is not available, the message, THIS FUNCTION IS NOT AVAILABLE is displayed when the wind direction adjustment button is pressed. *2. Applicable to only heat pump type.

Wired LCD remote controller with weekly schedule timer Remote control is equipped with weekly timer function. 24-hour clock function (1-hour backup for power failures) Programming function for each day of week. Scheduling possible of start/stop and temperature limit (5 settings/day) Programming can be enabled or disabled. Copy function for programmed schedules.

Indoor units applicable for the remote controller CEILING MOUNTED CASSETTE TYPE CEILING SUSPENDED TYPE CEILING SUSPENDED CASSETTE TYPE CEILING MOUNTED CASSETTE CORNER TYPE WALL MOUNTED TYPE CEILING MOUNTED BUILT-IN TYPE*1 DUCT CONNECTION LOW STATIC PRESSURE TYPE *2 DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE DUCT CONNECTION HIGH STATIC PRESSURE TYPE *2

BRC1D61

*1. When the auto-swing function is not available, the message, THIS FUNCTION IS NOT AVAILABLE is displayed when the wind direction adjustment button is pressed. *2. Applicable to only heat pump type. •Standard remote controller (BRC1C61) is not required. •If the BRC1D61 is connected to the centralised remote controller, the schedule function is not available.

Wireless LCD remote controller signal receiver mounted type

The wireless remote controller is supplied in a set with a signal receiver. Shape of signal receiver unit differs according to the indoor unit. Note: The signal rec eiver unit shown in the photograph is for mounting inside the dec oration panel of the c eiling mounted assette type. Indoor cunits applicable for the remote controller

Signal receiver unit (For ceiling mounted cassette type)

Wireless remote controller

35

Displays auto-swing operating status and setting position of air discharge angle. (Not available for ceiling mounted built-in type and duct connection type )

Preset temperature / operation mode display Programming time display Self-diagnosis function

W ir e d r e m o t e c o n t r o lle r h a s bu ilt -in t e m pe r a t u r e -s e n s o r (Applies to wired remote controllers)

Easier to read because LCD screen is larger.

BRC1D61

Airflow / swing display

Displays preset room temperature and operating status (fan, dry, cool). Operation start and stop time can be set for individual timers up to 72 hours. The liquid crystal display also shows when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning. Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.

S im ple s y s t e m pr o v id e s a d iv e r s e a s s o r t m e n t o f c o n t r o l m o d e s .

Wired LCD remote controller

BRC1C61

L C D pa n e l s h o w s o pe r a t in g s t a t u s in le t t e r s , n u m be r s , a n d m o t io n .

Enables temperature sensing closer to target area for improved comfort. (When using remote control from another room, temperature-sensor in indoor unit's air inlet must be selected.) Note: The indoor unitʼs temperature-sensor is specified at the time of shipment. Temperature sensing with the wired remote controller is not available with the ceiling mounted cassette corner, ceiling-mounted built-in, and duct connection type.

Control pattern

Control by 1 remote controller

Control by 2 remote controllers

Group control

Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically).

Control by external command

S ignal rec eiver unit ins talled on indoor unit C ontrol by 1 wireles s remote c ontroller and 1 wired remote c ontroller (S ee note 1)

For control from 2 locations such as in room and control room, exits, etc.

S ignal rec eiver unit ins talled on indoor unit

C onnec ts 2 wired remote c ontrollers

For simultaneous control of up to 16 indoor units.

Automatic addres s s etting func tion

Automatic addres s s etting func tion

Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.

(C ommand from outs ide)

(C ommand from outs ide)

Optional wiring adaptor for elec tric al appendic es is nec es s ary

Optional wiring adaptor for elec tric al appendic es is nec es s ary

C entral remote c ontroller (option)

Centralised remote control

Remote controller is equipped with model name and failure display functions. This facilitates service in the unlikely event of a malfunction.

S k y A ir s h a r e s c o m m o n c o n t r o l w it h H R V (h e a t r e c la im v e n t ila t io n ) a n d t h e o t h e r D a ik in a ir -c o n dit io n in g u n it s , t h u s s im plify in g in t e r lo c k in g o pe r a t io n s .

(Basic system)

S ignal rec eiver unit ins talled on 1 indoor unit

F a c ilit a t e s m a in t e n a n c e a n d r e pa ir All initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted units can be remotely set without having to use stepladder access for manual setting.

Wireless remote controller

Non-polar, double-c ore (max. wiring length 500 m)

N o n -po la r , do u ble -c o r e c o n n e c t io n s pe c ific a t io n s s im plify w ir in g Non-polar, double-core remote controller wire prevents wiring mistakes. signal receiver unit (or decoration panel) of wireless type is also easy to connect.

Wired remote controller

C entral remote c ontroller (option)

Centralised control of up to 64 indoor groups from remote location up to 1 kilometer away. Optional S kyAir s eries interfac e adaptor required. *1

Optional S kyAir s eries interfac e adaptor required. *1

HR V

HR V

Link by remote controller group control.

C an be operated s imultaneous ly or independently by remote c ontroller (s et by ventilation mode)

Interlock control with HRV

C an be operated s imultaneous ly by remote c ontroller (s et by ventilation mode)

C entral remote c ontroller (option)

C entral remote c ontroller (option)

Easily adaptable to large-scale, highfunction, centralised remote control systems. Zone link control by centralised control.

Installing and connecting control wiring between SkyAir and other Daikin air-conditioning equipment is easy.

HR V

HR V

HR V for indoor units within a zone are operated by interlocking C an also be operated independently by remote controller. Optional interface adaptor for S kyAir series is necessary *1

Optional adaptor for external commands or remote control of external equipment has been standardised to one type.

HR V for indoor units within a zone are operated by interloc king Optional interfac e adaptor for S kyAir s eries is nec es s ary *1

Note: When a wireless remote c ontroller is used, remote c ontrol by two remote c ontrollers is not possible. *1. DIII-net adaptor function is standard equipment for the FAY71L.

Easily adaptable to large-scale, high-function, centralised remote control system. C e n t r a l r e m o t e c o n t r o lle r DCS302CA61 (Option)

U n ifie d o n /o ff c o n t r o lle r DCS301BA61 (Option)

S c h e d u le t im e r DST301BA61 (Option)

DCS601C51 (Option)

Signal receiver unit is contained inside decoration panel or indoor unit Heat pump

Cooling only

CEILING MOUNTED CASSETTE TYPE

BRC7C612W BRC7C613W

CEILING SUSPENDED TYPE

BRC7E63W

CEILING SUSPENDED CASSETTE TYPE FAY71L WALL MOUNTED TYPE FAY100FA DUCT CONNECTION LOW STATIC PRESSURE TYPE DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE DUCT CONNECTION HIGH STATIC PRESSURE TYPE

BRC7EA66

BRC7C528W BRC7C529W BRC7EA618 BRC7E619 BRC7C610W BRC7C611W

BRC4C62

Centralised control of on/off by group or all at once for up to 256 indoor units.

Unified control of weekly schedule for up to 1,024 indoor units. Schedule timer sets on/off time in 1 minute units to be executed twice a day for a week at a time.

With its high functionality, the full color “all-in-one” graphic controller facilitates management of Skyair System in a variety of ways. *Please refer to the page 59 for the details.

BRC4C62 BRC4C62

Centralised control, with setting as simple as it is with a standard remote controller, of up to 64 groups (1,024 indoor units) is possible.

BRC4C64

Interface adaptor for SkyAir series

Enables centralised control via connection to a high-speed, DIII-NET communication system, adopted for the Daikin VRV system.

Necessary for interface adaptor for SkyAir series with the central remote control units shown at above. Note : DIII-net adaptor function is standard equipment for the FAY71L.

DTA102A52 (Option)

Central control adaptor kit *2 DTA107A55 (Option) (for FD series) *2.The central control adaptor kit for FDB series can be made to order.

36


Abundance of functions that provide comfortable air-conditioning in stores and offices. Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.

C omfort A u t o -s w in g

H ig h fa n s pe e d m o d e

Delivers comfortable air-conditioning to all areas, near to and far from the air-conditioner.

You can increase fan speed approximately 10% higher than the "high" setting. Applicable for wall mounted type

H ig h -c e ilin g a pplic a t io n Air discharge direction angle can be set (fixed setting)

Delivers air-conditioning comfort all the way down to the floor in air-conditioning zones with high ceilings.

S w in g pa t t e r n s e le c t io n

W ork a nd S e rvic ing L o w g a s pr e s s u r e d e t e c t io n

D r a in pu m p m e c h a n is m

Steeper gradient realises more efficient condensate drainage. High-lift is especially useful for long lengths of drain piping. P r e c h a r g e d fo r u p t o 3 0 m e t r e s

If refrigerant piping length does not exceed 30 m, there is no need for on-site gas charging. (Applies to R(Y)71LU–140LU)

Maintenance is not required for one year (two years when a ceiling mounted cassette type is used). C e ilin g s o ilin g pr e v e n t io n fu n c t io n

Applicable for ceiling mounted cassette type and ceiling mounted cassette corner type. Note:When units are installed on high ceilings, depending on the model, various restrictions concerning maximum height, air discharge direction, and choice of options may apply.

(1) Air direction in standard position

T w o s e le c t a ble t e m pe r a t u r e -s e n s o r s

(2) Air direction in draft prevention position

Temperature-sensors are included in the indoor unit and optional wired remote controller. Temperature sensing closer to target area is possible to further

(3) Air direction in ceiling soiling prevention position

D r a ft pr e v e n t io n fu n c t io n

Daikin's innovative air discharge mechanism keeps airflow away from the ceiling. Ceiling cleaning is less frequently required. F ilt e r s ig n

To prevent cold air drafts, automatically adjusts airflow to horizontal vector when heating initially starts or when the thermostat turns off. (Horizontal air dis c harge)

Note: Wireless remote controllers have no temperature-sensor.

H ot s ta rt

(after defrost)

Uncomfortable cold air draft is not discharged when heating operation starts or when switching to heat after defrosting. Y e a r -r o u n d c o o lin g a pplic a ble

S w it c h a ble fa n s pe e d

High setting provides maximum reach while low setting minimises drafts. P rogra m m e " Dry"

Dehumidification is microprocessor controlled to prevent uncomfortable changes in air temperature. Useful for reducing uncomfortable humidity without uncomfortable cooling.

Efficient cooling even in winter when indoor temperatures are higher than those outside, such as in underground public spaces or offices with many computers. • Heat pump/RY71—140LU: possible up to -5°C • Cooling only/R71—140LU: possible up to -15°C • The year-round cooling kit is required as option.

T im e r s e le c t o r

Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.

S e lf d ia g n o s is fu n c t io n

The operating parameters of indoor and outdoor units, and sensor data at critical locations throughout the system, are constantly monitored using a microcomputer. To facilitate quick response in the event of a malfunction, a message appears on the LCD of the remote controller and an LED on the unit illuminates.

The filter sign warns you when it is time to clean the filter. *When using a wired remote controller the sign is displayed in the LCD. When using a wireless remote controller the filter sign lamp illuminates on the signal receiver unit.

C ontrol features

Use the temperature-sensor in the indoor unit when controlling air conditioning from another room.

(heating)

E m e r g e n c y o pe r a t io n

If there is a malfunction elsewhere in the system, the fan or compressor can still be operated.

L o n g -life filt e r

(draft prevention, standard, ceiling soiling prevention)

You can freely set 3 air discharge positions by remote controller.

Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.Reliability is assured and maintenance and inspection can be carried out more quickly.

A u t o -r e s t a r t

C o n t r o l by 1 r e m o t e c o n t r o lle r

If there is a power outage while the equipment is operating, operations will restart in the same mode as before the power cut when electricity is restored. A u t o c o o l/h e a t c h a n g e -o v e r

(Heat pump only)

Detects difference in preset temperature and actual room temperature and automatically switches to cooling or heating accordingly. C o n t r o l by 2 r e m o t e c o n t r o lle r s

You can turn up to 16 indoor units on/off with a single remote controller. (When using connected indoor units, the settings must all be the same and on/off will be simultaneous.) E x te rna l c om m a nd c ontrol Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room. C e ntra l re m ote c ontrol

Using 2 remote controllers you can operate the equipment locally or from a remote location. Note: When a wireless remote controller is used, remote control by two remote controllers is not possible.

Optional central remote controller enables centralised control of up to 1024 indoor units (64 groups) from up to 1 kilometer away. I n t e r lo c k c o n t r o l

Enables interlocking control with external equipment such as heat reclaim ventilation (HRV).

Mould prevention M o u ld -r e s is t a n t t r e a t m e n t fo r filt e r

M o u ld -p r o o fi n g d r a in p a n

Sanitary filter has mould-resistant treatment.

Mould-proofing maintains hygiene by preventing growth in highly humid conditions.

Others T w in / tr iple / do u ble tw in m u lti o pe r a tio n

Simultaneously operates 2–4 indoor units with a single outdoor unit.

37

P E fin

To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit. In high corrosive areas, regular maintenance needs to be carried out.

Options H ig h -e ffic ie n c y filt e r u n it

F r e s h -a ir in t a k e k it

Two types are available: 65% and 90% colorimetry. U lt r a lo n g -life filt e r

Requires no maintenance for about 4 years* (10,000 h) in stores and offices. * For dust concentration of 0.15 mg/m 3

You can provide air-conditioning with fresh air from outside. Convenient for places where a ventilation fan cannot be installed. Note: *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally. **Outside Air fan interlocked with air conditioning unit is necessary. Optional PCB(KRP1C63)is required for interlocking. ***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating noise and may also influence temperature sending.

38


CEILING MOUNTED CASSETTE TYPE Indoor unit

Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

kW Btu/h kcal/h kW

Power consumption 1a/1b Indoor unit

Outdoor unit

Unit Decoration panel m3/min Airflow rate (H) cfm dB(A) Sound level (H/L) 2 mm Dimensions Unit (HX WX D) mm Decoration panel kg Unit Machine weight kg Decoration panel °CWB Certified operation range Colour Compressor Type Motor output kW Colour

Refrigerant charge (R-22) Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Liquid (Flare) Piping connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

kg

CEILING SUSPENDED CASSETTE TYPE

71 100 125 140 FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE R71LUV1 R100LUV1 R50GV1 R60GV1 R125LUY1 R35GV1 R140LUY1 R71LUY1 R100LUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 14.5/14.2 5.34/5.3 6.44/6.4 7.8/7.7 10.6/10.5 13.0/12.8 3.54/3.5 12,100/11,900 18,200/18,100 22,000/21,800 26,600/26,200 36,100/35,700 44,500/43,600 49,400/48,400 4,590/4,560 5,540/5,500 6,700/6,600 9,100/9,000 3,040/3,010 11,200/11,000 12,500/12,200 3.07/3.07 (V1) 4.01/4.01 (V1) 2.02/2.01 2.45/2.44 4.96/4.96 5.02/5.02 1.20/1.20 3.05/3.05 (Y1) 3.96/3.96 (Y1) ---------White 35 15 19 28 14 19 33 1,235 529 670 988 494 670 1,164 44/37 33/29 33/29 35/30 35/30 39/34 42/36 230X 840X 840 230X 840X 840 230X 840X 840 230X 840X 840 288X 840X 840 288X 840X 840 288X 840X 840 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 24 24 24 24 28 28 28 5 5 5 5 5 5 5 14 to 23 14 to 25 Ivory white Hermetically sealed rotary type Hermetically sealed scroll type 3.75 4.50 1.1 1.7 2.2 2.24 3.00 3.7 4.1 1.10 1.20 1.50 2.8 3.7 (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) 35 FHC35KVE

50 FHC50KVE

60 FHC60KVE

dB(A) 49 54 48 49 54 48 49 540X 750X 270 540X 750X 270 685X 800X 300 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 mm kg 37 42 61 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 109 °CDB 19.4 to 46 19.4 to 54 19.4 to 46 21 to 46, -15 to 46 3 (Option installed) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 mm mm I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) mm 25 30 50 (equivalent length 70 m) m 15 30 m Both liquid and gas piping

Indoor unit Outdoor unit

Power supply Cooling capacity 1a/1b

Power consumption 1a/1b Indoor unit

Outdoor unit

Colour Airflow rate (H) Sound level (H/L) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Compressor Type Motor output Refrigerant charge (R-22)

Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

Indoor unit

Sound level (H/L) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Outdoor Compressor Type unit Motor output Refrigerant charge (R-22) Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

48 540X 750X 270 37 19.4 to 46 o/ 6.4 o/ 12.7 I.D o/ 20X O.D o/ 26 o/ 18.0 (Hole) 25

Note : 1 Rated cooling capacities are based on the following conditions: 1a Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.) 2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3 This value is for when year-round cooling kit (option) is installed.

39

Outdoor unit

Power consumption 1a/1b Indoor unit

Outdoor unit

54 685X 800X 300 61 19.4 to 46 o/ 6.4 o/ 15.9 I.Do/ 20X O.D o/ 26 o/ 18.0 (Hole) 30

15

49 48 49 770X 900X 320 1,170X 900X 320 1,170X 900X 320 98 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 21 to 46, -15 to 46 3 (Option installed) o/ 9.5 o/ 9.5 o/ 9.5 o/ 19.1 o/ 15.9 o/ 19.1 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.Do/ 20X O.D o/ 26 o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

kW kg dB(A) mm kg °CDB mm mm mm mm m m

Indoor unit

Power supply Cooling capacity 1a/1b

60 FH60BVE

49 540X 750X 270 42 19.4 to 54 o/ 6.4 o/ 15.9 I.D o/ 20X O.D o/ 26 o/ 18.0 (Hole)

m3/min cfm dB(A) mm kg °CWB

CEILING MOUNTED CASSETTE CORNER TYPE

71 100 125 FHY71BVE FHY100BVE FHY125BVE R71LUV1 R100LUV1 R35GV1 R50GV1 R60GV1 R125LUY1 R71LUY1 R100LUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 3.54/3.4 5.19/5.1 6.6/6.5 7.8/7.7 10.6/10.5 13.0/12.8 kW 12,100/11,600 17,700/17,500 22,760/22,200 26,600/26,200 36,100/35,700 44,500/43,600 Btu/h 3,040/2,930 4,460/4,400 5,690/5,600 6,700/6,600 9,100/9,000 11,200/11,000 kcal/h 3.10/3.10 (V1) 3.90/3.90 (V1) 1.51/1.50 2.16/2.15 2.80/2.78 4.92/4.92 kW 3.08/3.08 (Y1) 3.85/3.85 (Y1) White 30 13 16 13 17 24 m3/min 1,059 cfm 458 458 564 600 847 44/39 dB(A) 37/32 38/33 38/33 39/35 42/37 195X 1,590X 680 195X 960X 680 195X 1,160X 680 195X 960X 680 195X 1,160X 680 195X 1,400X 680 mm 35 kg 23 24 26 27 32 °CWB 14 to 25 14 to 23 Ivory white Hermetically sealed rotary type Hermetically sealed scroll type 3.75 kW 1.1 1.7 2.2 2.24 3.00 3.7 1.10 1.20 1.50 2.8 3.7 kg (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) dB(A) mm kg °CDB mm mm mm mm m m

50 FH50BVE

kW

Colour Airflow rate (H)

Model Name 35 FH35BVE

kW Btu/h kcal/h

Power consumption 1a/1b

CEILING SUSPENDED TYPE Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

100 125 FUY100FJV1 FUY125FJV1 R100LUV1 R125LUY1 R100LUY1 V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 10.6/10.5 13.0/12.8 7.8/7.7 36,100/35,700 44,500/43,600 26,600/26,200 9,100/9,000 11,200/11,000 6,700/6,600 3.08/3.08 (V1) 4.07/4.07 (V1) 4.97/4.97 3.06/3.06 (Y1) 4.02/4.02 (Y1) White 29 32 19 1,023 1,129 670 43/38 44/39 40/35 165X 895X 895 230X 895X 895 230X 895X 895 25 31 31 14 to 25 Ivory white Hermetically sealed scroll type 2.24 3.00 3.75 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m) 48 49 49 770X 900X 320 1,170X 900X 320 1,170X 900X 320 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 21 to 46, -15 to 46 3 (Option installed) o/ 9.5 o/ 9.5 o/ 9.5 o/ 15.9 o/ 19.1 o/ 19.1 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.Do/ 26 o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping 71 FUY71FJV1 R71LUV1 R71LUY1

Indoor unit

Model Name

45 FHK45FV1

60 FHK60FV1

R35GV1

R50GV1

R60GV1

kW Btu/h kcal/h

3.54/3.4 12,100/11,600 3,040/2,930

kW

1.41/1.40

Unit Decoration panel m3/min Airflow rate (H) cfm dB(A) Sound level (H/L) 2 mm Dimensions Unit (HX WX D) mm Decoration panel kg Unit Machine weight kg Decoration panel °CWB Certified operation range Colour Compressor Type Motor output kW kg Refrigerant charge (R-22) dB(A) Sound level 2 mm Dimensions (HX WX D) kg Machine weight

Liquid (Flare) Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

71 FHYK71FJV1 R71LUV1 R71LUY1

V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 5.19/5.1 6.6/6.5 17,700/17,500 22,760/22,200 5,690/5,600 4,460/4,400 2.25/2.24

2.76/2.74

7.8/7.7 26,600/26,200 6,700/6,600 3.07/3.07 (V1) 3.05/3.05 (Y1)

---------White

Colour

Certified operation range Piping connections

35 FHK35FV1

12 423 39/33 215X 1,110X 710 70X 1,240X 800 30 8.5

17 600 41/36 215X 1,310X 710 70X 1,440X 800 33 9.5

12 423 39/34 215X 1,110X 710 70X 1,240X 800 31 8.5 14 to 23

Ivory white Hermetically sealed rotary type 1.7 1.1 2.2 1.20 (Charged for 10 m) 1.10 (Charged for 10 m) 1.50 (Charged for 5 m) 49 48 54 540X 750X 270 540X 750X 270 685X 800X 300 37 42 61

°CDB

19.4 to 46

19.4 to 54

19.4 to 46

mm mm mm mm m m

o/ 6.4 o/ 12.7 I.D o/ 25X O.D o/ 32 o/ 18.0 (Hole) 25

o/ 6.4 o/ 15.9 I.D o/ 25X O.D o/ 32 o/ 18.0 (Hole)

o/ 6.4 o/ 15.9 I.Do/ 25X O.Do/ 32 o/ 18.0 (Hole) 30

15

17 600 41/36 215X 1,310X 710 70X 1,440X 800 33 9.5 14 to 25 Hermetically sealed scroll type 2.24 2.8 (Charged for 30 m) 48 770X 900X 320 72 (V1), 71 (Y1) 21 to 46 -15 to 46 3 (Option installed) o/ 9.5 o/ 15.9 I.Do/ 25X O.Do/ 32 o/ 26.0 (Hole) 50 (equivalent length 70 m) 30

Both liquid and gas piping

Note : Rated cooling capacities are based on the following conditions: 1a Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.) 2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3 This value is for when year-round cooling kit (option) is installed. 1

40


CEILING MOUNTED BUILT-IN TYPE Indoor unit

Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

kW Btu/h kcal/h kW

Power consumption 1a/1b Indoor unit

Outdoor unit

35 FHB35FV1

Unit Decoration panel m3/min Airflow rate (H) cfm dB(A) Sound level (H/L) 2 mm Dimensions Unit (HX WX D) mm Decoration panel kg Unit Machine weight kg Decoration panel °CWB Certified operation range Colour Compressor Type Motor output kW Colour

Refrigerant charge (R-22) Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

kg dB(A) mm kg °CDB mm mm mm mm m m

FLOOR STANDING TYPE 45 FHB45FV1

60 FHB60FV1

71 100 125 FHYB71FV1 FHYB100FV1 FHYB125FV1 R71LUV1 R100LUV1 R35GV1 R50GV1 R60GV1 R125LUY1 R71LUY1 R100LUY1 V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 3.54/3.4 5.19/5.1 6.6/6.5 7.8/7.7 10.6/10.5 13.0/12.8 12,100/11,600 17,700/17,500 22,760/22,200 26,600/26,200 36,100/35,700 44,500/43,600 3,040/2,930 4,460/4,400 5,690/5,600 6,700/6,600 9,100/9,000 11,200/11,000 3.13/3.13 (V1) 4.00/4.00 (V1) 1.47/1.46 2.33/2.32 2.78/2.76 4.74/4.74 3.11/3.11 (Y1) 3.95/3.95 (Y1) ---------White 11.5 14 17 19 27 35 405 494 600 670 953 1,235 38/32 39/34 41/35 41/35 41/35 44/38 300X 700X 800 300X 700X 800 300X 1,000X 800 300X 1,000X 800 300X 1,400X 800 300X 1,400X 800 55X 880X 500 55X 880X 500 55X 1,100X 500 55X 1,100X 500 55X 1,500X 500 55X 1,500X 500 30 31 41 41 51 52 3.5 3.5 4.5 4.5 6.5 6.5 14 to 23 14 to 25 Ivory white Hermetically sealed rotary type Hermetically sealed scroll type 1.1 1.7 2.2 2.24 3.00 3.75 1.10 1.20 1.50 2.8 3.7 3.7 (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) 48 49 54 48 49 49 540X 750X 270 540X 750X 270 685X 800X 300 770X 900X 320 1,170X 900X 320 1,170X 900X 320 37 42 61 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 19.4 to 46 19.4 to 54 19.4 to 46 21 to 46, -15 to 46 3 (Option installed) o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 25 30 50 (equivalent length 70 m) 15 30 Both liquid and gas piping

Indoor unit Outdoor unit

Power supply Cooling capacity 1a/1b

Power consumption 1a/1b Indoor unit

Colour Airflow rate (H)

Sound level (H/L) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Outdoor Compressor Type unit Motor output Refrigerant charge (R-22) Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

kW Btu/h kcal/h kW m3/min cfm dB(A) mm kg °CWB

kW kg dB(A) mm kg °CDB mm mm mm mm m m

71 100 FAY71LVE FAY100FAVE R71LUV1 R100LUV1 R71LUY1 R100LUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 7.8/7.7 10.6/10.5 26,600/26,200 36,100/35,700 6,700/6,600 9,100/9,000 2.98/ 2.98(V1) 3.90/3.90 (V1) 3.85/3.85 (Y1) 2.96/2.96(Y1) White 19 23 670 811 43/37 45/41 290X 1,050X 230 360X 1,570X 200 13 26 14 to 25 Ivory white Hermetically sealed scroll type 2.24 3.00 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 48 49 770X 900X 320 1,170X 900X 320 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 21 to 46, -15 to 46 3 (Option installed) o/ 9.5 o/ 9.5 o/ 19.1 o/ 15.9 I.D o/ 20X O.D o/ 26 I.D o/ 13X O.D o/ 18 o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

Note : 1 Rated cooling capacities are based on the following conditions: (FHB) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.) (FAY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R100LU is 7.5 m.) 2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3 This value is for when year-round cooling kit (option) is installed.

41

Outdoor unit

Power supply Cooling capacity 1a/1b

kW Btu/h kcal/h kW

Power consumption 1a/1b Indoor unit

Colour Airflow rate (H)

Sound level (H/L) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Outdoor Compressor Type unit Motor output Refrigerant charge (R-22) Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

m3/min cfm dB(A) mm kg °CWB

kW kg dB(A) mm kg °CDB mm mm mm mm m m

100 125 71 FVY100LAVE FVY125LAVE FVY71LAVE R100LUV1 R71LUV1 R125LUY1 R100LUY1 R71LUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 10.6/10.5 13.0/12.8 7.8/7.7 36,100/35,700 44,500/43,600 26,600/26,200 9,100/9,000 11,200/11,000 6,700/6,600 3.18/3.18 (V1) 4.03/4.03 (V1) 5.06/5.06 3.16/3.16 (Y1) 3.98/3.98 (Y1) White 28 32 18 988 1,129 635 46/40 49/43 41/35 1,850X 600X 350 1,850X 600X 350 1,850X 600X 270 39 46 47 14 to 25 Ivory white Hermetically sealed scroll type 2.24 3.00 3.75 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m) 48 49 49 770X 900X 320 1,170X 900X 320 1,170X 900X 320 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 21 to 46, -15 to 46 3 (Option installed) o/ 9.5 o/ 9.5 o/ 9.5 o/ 15.9 o/ 19.1 o/ 19.1 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

DUCT CONNECTION LOW STATIC PRESSURE TYPE Outdoor unit

Power supply Cooling capacity 1a/1b, 4

Power consumption 1a/1b Colour Airflow rate (H)

Indoor unit

Outdoor unit

25 FDBG25AVE

Indoor unit

Model Name

WALL MOUNTED TYPE Model Name

Indoor unit

Model Name

Fan Driving system Sound level (H/L) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Compressor Type Motor output Refrigerant charge (R-22)

Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

kW Btu/h kcal/h kW m3/min cfm dB(A) mm kg °CWB

kW kg dB(A) mm kg °CDB mm mm mm mm m m

35 FDBG35AVE

50 FDBG50AVE

60 FDBG60AVE

71 FDBG71AVE R71FUV1 R25JV1 R35JV1 R50GV1 R60GV1 R71FUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 3.54/3.50 5.34/5.30 7.03/6.97 2.64/2.60 7.80/7.70 12,100/11,900 18,200/18,100 24,000/23,800 9,000/8,900 26,600/26,200 3,040/3,010 4,590/4,560 6,050/6,000 2,270/2,250 6,700/6,600 0.88/0.87 1.25/1.24 2.06/2.05 2.76/2.75 2.82/2.80 ---------13 13 13 18 18 458 458 458 635 635 Direct drive (2 speed) 41/38 41/38 41/38 42/39 42/39 260X 900X 580 260X 900X 580 260X 900X 580 260X 1,300X 580 260X 1,300X 580 22 22 23 31 31 14 to 23 14 to 25 Ivory white Hermetically sealed rotary type Hermetically sealed type 1.7 2.2 2.2 0.7 1.1 1.20 1.50 2.10 0.8 1.0 (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 5 m) (Charged for 10 m) 49 54 52 46 48 540X 750X 270 685X 800X 300 816X 880X 370 560X 695X 265 560X 695X 265 27 33 42 61 87 (V1), 84 (Y1) 19.4 to 54 19.4 to 46 21 to 52 19.4 to 46 o/ 6.4 o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5 o/ 12.7 o/ 15.9 o/ 9.5 o/ 15.9 o/ 15.9 3/4B 3/4B 3/4B 3/4B 3/4B o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) 25 30 50 (equivalent length 70 m) 15 30 Both liquid and gas piping

Note : 1 Rated cooling capacities are based on the following conditions: (FVY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.) (FDBG) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3 This value is for when year-round cooling kit (option) is installed. 4 Capacities are gross, with no deduction made for evaporator fan motor heat.

42


DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE Indoor unit

Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

Power consumption 1a/1b Colour Indoor Fan Airflow rate (H) unit Sound level (H) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Outdoor Compressor Type unit Motor output Refrigerant charge (R-22) Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

m3/min cfm dB(A) mm kg °CWB

kW kg dB(A) mm kg °CDB mm mm mm mm m m

Power consumption 1a/1b Colour Fan Airflow rate (H)

External static pressure Sound level (H) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Outdoor Compressor Type unit Motor output Refrigerant charge (R-22) Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

100 125 140 FDYM04FAV1 FDYM05FAV1 FDYM06FAV1 R100LUV1 R125LUY1 R140LUY1 R100LUY1 V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 10.6/10.5 13.0/12.8 14.5/14.2 7.8/7.7 36,100/35,700 44,500/43,600 49,400/48,400 26,600/26,200 9,100/9,000 11,200/11,000 12,500/12,200 6,700/6,600 3.25/3.25 (V1) 4.08/4.08 (V1) 5.06/5.06 5.18/5.18 3.23/3.23 (Y1) 4.03/4.03 (Y1) ---------26 35 37 20 917 1,235 1,306 706 98(10) 98(10) 98(10) 98(10) 39 44 39 46 295X 1,500X 680 295X 1,500X 680 295X 1,100X 680 295X 1,500X 680 42 56 57 57 14 to 25 Ivory white Hermetically sealed scroll type 2.24 3.00 3.75 4.50 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m) 4.1 (Charged for 30 m) 48 49 49 54 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 109 21 to 46, -15 to 46 3 (Option installed) o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 19.1 o/ 19.1 o/ 19.1 o/ 15.9 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping 71 FDYM03FAV1 R71LUV1 R71LUY1

Outdoor unit

Power supply Cooling capacity 1a/1b

Indoor unit

kW Btu/h kcal/h kW

Indoor unit

Model Name

100 125 140 180 FDMG100AV1 FDMG125AV1 FDMG140AV1 FDMG180AV1 R100FUV1 R125FUY1 RG140AY1 RG180AY1 R100FUY1 V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 10.6/10.5 13.1/12.9 14.5/14.2 8.8/8.7 17.2/16.8 36,100/35,700 44,500/43,600 49,400/48,400 30,000/29,600 58,700/57,500 9,100/9,000 11,200/11,000 12,500/12,200 7,600/7,500 14,700/14,400 3.15/3.13 4.08/4.04 4.89/4.85 5.25/5.25 6.45/6.45 ---------34 37 42 23 42 1,200 1,306 1,412 811 1,482 44 45 46 42 47 305X 1,550X 680 305X 1,550X 680 305X 1,550X 680 305X 1,350X 680 305X 1,900X 680 43 51 52 52 58 14 to 25 Ivory white Hermetically sealed type Hermetically sealed scroll type 2.20 3.00 3.75 4.50 4.50 2.4 (Charged for 5 m) 2.4 (Charged for 5 m) 2.8 (Charged for 5 m) 2.9 (Charged for 5 m) 2.8 (Charged for 5 m) 52 56 57 56 55 816X 880X 370 1,215X 880X 370 1,215X 880X 370 1,345X 880X 370 1,345X 880X 370 87 (V1), 84 (Y1) 117 (V1), 109 (Y1) 110 113 114 21 to 52 21 to 50 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 o/ 19.1 3/4B 3/4B 3/4B 3/4B 3/4B o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping 71 FDMG71AV1 RG71AV1 RG71AY1

kW Btu/h kcal/h kW m3/min cfm Pa(mmH2O) dB(A) mm kg °CWB

kW kg dB(A) mm kg °CDB mm mm mm mm m m

Note : 1 Rated cooling capacities are based on the following conditions: 1a Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.) 2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3 This value is for when year-round cooling kit (option) is installed.

43

DUCT CONNECTION HIGH STATIC PRESSURE TYPE Model Name Power supply Cooling capacity 1a/1b

Power consumption 1a/1b Colour Indoor Airflow rate (H) unit External static pressure Driving system Sound level (H) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Compressor Type Motor output

Fan

Outdoor unit

Refrigerant charge (R-22) Sound level Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation 2

Model Name Power supply Cooling capacity 1a/1b

kW Btu/h kcal/h kW

8.1/ 7.9 27,800/27,000 7,000/6,800 2.50/2.48

m3/min cfm Pa(mmH2O)

26 917 69 (7)

dB(A) mm kg °CWB

46 450X 650X 850 51

kW

3.0 2.1 (Charged for 5 m)

kg dB(A) mm kg °CDB mm mm mm mm m m

Power consumption 1a/1b Colour Airflow rate (H) Fan

External static pressure Driving system Sound level (H) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Compressor Type Motor output Refrigerant charge (R-22)

Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Brazing) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

100 125 FD04KY1 FD05KY1 R100FUY1 R125FUY1 Y1: 3 phase, 380–415 V, 50 Hz 11.0/10.8 14.0/13.8 37,700/36,900 47,600/46,800 9,500/9,300 12,000/11,800 3.52/3.48 4.19/4.15 ---------30 46 1,059 1,623 88 (9) Belt drive 49 450X 900X 850 59 72 14 to 25 Ivory white Hermetically sealed type 3.8 4.5 2.4 2.8 (Charged for 5 m) (Charged for 5 m)

52 816X 880X 370 84

56

140 FD06KY1 RU06KY1 17.4/17.2 59,500/58,800 15,000/14,800 5.7/5.7 52 1,835

51 450X 1,130X 850 79

Hermetically sealed scroll type 4.5 3.0 (Charged for 5 m)

57 110

59 1,345X 880X 320 112

o/ 9.5 o/ 19.1

o/ 9.5 o/ 19.1

1,215X 880X 370 109 21 to 52

o/ 9.5 o/ 15.9

o/ 9.5 o/ 19.1

3/4B o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

o/ 26.0 (Hole)

200 FD08KY1 RU08KUY1

Indoor unit Outdoor unit

Indoor unit

Outdoor unit

71 FD03KY1 R71FUY1

Indoor unit Outdoor unit

kW Btu/h kcal/h kW

24.3/24.0 83,000/81,800 20,900/20,600 7.5/7.4

m3/min cfm Pa(mmH2O)

68 2,400

----------

250 400 FD10KY1 FD15KY1 RU10KUY1 RU08KUY1X 2 Y1: 3 phase, 380–415 V, 50 Hz 29.7/29.2 48.6/47.9 101,200/99,600 166,000/163,500 25,500/25,100 41,800/41,200 9.9/9.8 15.0/14.8 ---------83 136 2,929 4,800 98 (10)

500 FD20KY1 RU10KUY1X 2 59.3/58.4 202,400/199,400 51,000/ 50,200 19.8/19.6 166 5,859 147 (15)

Belt drive dB(A) mm kg °CWB

51 500X 1,130X 850 93

kW

7.5 5.0 (Charged for 5 m) 60 1,220X 1,280X 690 185

kg dB(A) mm kg °CDB mm mm mm mm m m

53 500X 1,330X 850 104

58 625X 1,620X 850 161

60 625X 1,980X 850 187

14 to 25 Ivory white Hermetically sealed scroll type 9.0 7.5 X 2 6.1 5.0 (Charged for 5 m) (Charged for 5 m)X 2 61 60 3 (1,220X 1,280X 690) X 2 1,440X 1,280X 690 200 185X 2 21 to 52 o/ 15.9 o/ 12.7 X 2 o/ 31.8 o/ 25.4 X 2

o/ 12.7 o/ 25.4 3/4B

9.0X 2 6.1 (Charged for 5 m)X 2 61 3 (1,440X 1,280X 690) X 2 200X 2 o/ 15.9 X 2 o/ 31.8 X 2 1B

---------50 (equivalent length 70 m) 30 Both liquid and gas piping

Note : Models RU08K(U)Y1 and RU10K(U)Y1 are recommended for commercial facilities. 1 Rated cooling capacities are based on the following conditions: 1a Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3 Specification for outdoor unit is for a single unit only.

44


Simultaneous operation system

DUCT CONNECTION HIGH STATIC PRESSURE TYPE Model Name Power supply Cooling capacity 1a/1b

Indoor unit Outdoor unit

Power consumption Colour Airflow rate (H) 1a/1b

Indoor unit

External static pressure Driving system Sound level (H) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Compressor Type Motor output Fan

Outdoor unit

200 FD08KY1 RU08KY1

Refrigerant charge (R-22) Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Brazing) connections Gas (Brazing) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

kW Btu/h kcal/h kW

24.3/24.0 83,000/81,800 20,900/20,600 7.5/7.4

m3/min cfm Pa(mmH2O)

68 2,400

CEILING MOUNTED CASSETTE TYPE

250 400 FD10KY1 FD15KY1 RU10KY1 RU08KY1X 2 Y1: 3 phase, 380–415 V, 50 Hz 29.7/29.2 48.6/47.9 101,200/99,600 166,000/163,500 25,500/25,100 41,800/41,200 9.9/9.8 15.0/14.8 ---------83 136 2,929 4,800 98 (10)

500 FD20KY1 RU10KY1X 2 59.3/58.4 202,400/199,400 51,000/50,200 19.8/19.6 166 5,859

kW kg dB(A) mm kg °CDB mm mm mm mm m m

51 500X 1,130X 850 93

7.5 5.0

53 500X 1,330X 850 104

(Field charge required for 5 m) 4

58 625X 1,620X 850 161

(Field charge required for 5 m) 4

60 1,220X 1,280X 690 177

61 1,440X 1,280X 690 190

o/ 12.7 o/ 25.4

o/ 15.9 o/ 31.8 3/4B

Note : Models RU08K(U)Y1 and RU10K(U)Y1 are recommended for commercial facilities. 1 Rated cooling capacities are based on the following conditions: 1a Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3 Specification for outdoor unit is for a single unit only. 4 This is the amount of refrigerant required for piping of five meters or less. Since the unit does not contain refrigerant when shipped from the factory, it must be added at the installation site. For details, please refer to the installation manual.

61 3 (1,440X 1,280X 690) X 2 190 X 2 o/ 15.9 X 2 o/ 31.8 X 2 1B

---------50 (equivalent length 70 m) 30 Both liquid and gas piping

kW

Unit Decoration panel m3/min Airflow rate (H) cfm Sound level (H/L) 2 dB(A) mm Dimensions Unit (HX WX D) Decoration mm panel

Colour

Machine weight

(Field charge required for 5 m) 4 X 2

60 3 (1,220X 1,280X 690) X 2 177 X 2 21 to 52 o/ 12.7 X 2 o/ 25.4 X 2

kW Btu/h kcal/h

Power consumption 1a/1b

9.0X 2 6.1

(Field charge required for 5 m) 4 X 2

Outdoor unit

Power supply Cooling capacity 1a/1b

60 625X 1,980X 850 187

14 to 25 Ivory white Hermetically sealed scroll type 9.0 7.5 X 2 6.1 5.0

Indoor unit

Model Name

Indoor unit 3

147 (15) Belt drive

dB(A) mm kg °CWB

TWIN & TRIPLE & DOUBLE TWIN MULTI

Outdoor unit

Unit Decoration panel

Certified operation range Colour Compressor Type Motor output Refrigerant charge (R-22)

40X 950X 950

40X 950X 950

40X 950X 950

40X 950X 950

40X 950X 950

40X 950X 950

kg

24

24

24

24

28

28

kg

5

5

5

5

5

5

°CWB

kW kg

Sound level 2 dB(A) mm Dimensions (HX WX D) kg Machine weight Certified operation range °CDB mm Piping Liquid (Flare) connections Gas mm mm Drain Indoor unit Outdoor unit mm m Max. interunit piping length m Max. installation level difference Heat insulation

Indoor unit Model Name Outdoor unit Power supply Cooling capacity 1a/1b

Machine weight

2.24 2.8 (Charged for 30 m) 48 770X 900X 320 72 (V1), 71 (Y1) o/ 9.5 o/ 15.9 (Flare) I.D o/ 25X O.D o/ 32 o/ 26.0 (Hole)

14 to 25 Ivory white Hermetically sealed scroll type 3.00 3.75 4.50 3.7 3.7 4.1 (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) 49 49 54 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 109 87 (V1), 84 (Y1) 98 21 to 46, -15 to 46 4 (Option installed) o/ 9.5 o/ 9.5 o/ 9.5 o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

140 FHYC50KVEX 3 R140LUY1 kW Btu/h kcal/h kW

Power consumption 1a/1b Colour Unit Indoor Decoration panel unit 3 m3/min Airflow rate (H) cfm Sound level (H/L) 2 dB(A) mm Dimensions Unit (HX WX D) Decoration mm panel Unit Decoration panel

100 125 71 200 250 140 FHYC100KVEX 2 FHYC50KVEX 2 FHYC60KVEX 2 FHYC125KVEX 2 FHYC35KVEX 2 FHYC71KVEX 2 R71LUV1 R100LUV1 R125LUY1 R200KUY1 R140LUY1 R250KUY1 R71LUY1 R100LUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 14.5/14.2 22.5/22.2 27.1/26.6 7.8/7.7 10.6/10.5 13.0/12.8 49,400/48,400 76,800/75,800 92,500/90,800 26,600/26,200 36,100/35,700 44,500/43,600 12,500/12,200 19,400/19,100 23,300/22,900 6,700/6,600 9,100/9,000 11,200/11,000 3.17/3.17 (V1) 4.06/4.06 (V1) 5.01/5.01 5.02/5.02 7.7/7.6 9.7/9.7 3.15/3.15 (Y1) 4.01/4.01 (Y1) ------------White 19 28 33 14 15 19 494 529 670 670 988 1,164 33/29 33/29 35/30 35/30 39/34 42/36 230X 840X 840 230X 840X 840 230X 840X 840 230X 840X 840 288X 840X 840 288X 840X 840

14.5/14.2 49,400/48,400 12,500/12,200 5.02/5.02

15 529 33/29 230X 840X 840

5.5 9.0 5.3 5.7 (Charged for 5 m) (Charged for 5 m) 60 61 1,220X 1,280X 690 1,440X 1,280X 690 178 202 -5 to 52 o/ 15.9 o/ 12.7 o/ 25.4 (Flange) o/ 28.6 (Flange) I.D o/ 25X O.D o/ 32 I.Do/ 25X O.Do/ 32 -----------------

200 200 FHYC71KVEX 3 FHYC50KVEX 4 R200KUY1 R200KUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz 22.5/22.2 22.5/22.2 76,800/75,800 76,800/75,800 19,400/19,100 19,400/19,100 7.7/7.6 7.7/7.6 ------------White 19 15 670 529 35/30 33/29 33/29 230X 840X 840 230X 840X 840

250 FHYC60KVEX 4 R250KUY1 27.1/26.6 92,500/90,800 23,300/22,900 9.7/9.7

19 670 35/30 230X 840X 840

40X 950X 950

40X 950X 950

40X 950X 950

40X 950X 950

kg

24

24

24

24

kg

5

5

5

5

Certified operation range °CWB Colour Outdoor Compressor Type unit kW 4.50 Motor output kg 4.1 (Charged for 30 m) Refrigerant charge (R-22) 54 Sound level 2 dB(A) 1,345X 900X 320 mm Dimensions (HX WX D) 109 kg Machine weight Certified operation range °CDB 21 to 46, -15 to 46 4 (Option installed) mm Piping Liquid (Flare) o/ 9.5 connections Gas mm o/ 19.1 (Flare) mm Drain Indoor unit I.D o/ 25X O.D o/ 32 Outdoor unit mm o/ 26.0 (Hole) m Max. interunit piping length m Max. installation level difference Heat insulation

14 to 25 Ivory white Hermetically sealed scroll type 5.5 5.5 5.3 (Charged for 5 m) 5.3 (Charged for 5 m) 60 60 1,220X 1,280X 690 1,220X 1,280X 690 178 178 -5 to 52 o/ 12.7 o/ 12.7 o/ 25.4 (Flange) o/ 25.4 (Flange) I.D o/ 25X O.D o/ 32 I.D o/ 25X O.Do/ 32 ----------------50 (equivalent length 70 m) 30 Both liquid and gas piping

9.0 5.7 (Charged for 5 m) 61 1,440X 1,280X 690 202 o/ 15.9 o/ 28.6 (Flange) I.Do/ 25X O.Do/ 32 ---------

Note : Models R200KU and R250KU are recommended for commercial facilities. 1 Rated cooling capacities are based on the following conditions: 1a Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.) 2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3 Values shown are for a single unit only. 4 This value is for when year-round cooling kit (option) is installed.

45

46


Simultaneous operation system

TWIN & TRIPLE & DOUBLE TWIN MULTI

CEILING SUSPENDED TYPE Indoor unit

Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

kW Btu/h kcal/h

Power consumption 1a/1b Indoor unit 3

Outdoor unit

kW

Colour Airflow rate (H)

m3/min cfm dB(A) Sound level (H/L) 2 mm Dimensions (HX WX D) kg Machine weight ° Certified operation range CWB Colour Compressor Type kW Motor output Refrigerant charge (R-22)

kg

dB(A) Sound level mm Dimensions (HX WX D) kg Machine weight Certified operation range °CDB mm Piping Liquid (Flare) connections Gas mm mm Drain Indoor unit Outdoor unit mm m Max. interunit piping length m Max. installation level difference Heat insulation 2

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

200 71 100 125 250 140 FHY100BVE × 2 FHY35BVE × 2 FHY50BVE × 2 FHY60BVE × 2 FHY125BVE × 2 FHY71BVE × 2 R71LUV1 R100LUV1 R200KUY1 R125LUY1 R250KUY1 R140LUY1 R71LUY1 R100LUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 27.1/26.6 7.8/7.7 10.6/10.5 13.0/12.8 14.5/14.2 22.5/22.2 92,500/90,800 26,600/26,200 36,100/35,700 44,500/43,600 49,400/48,400 76,800/75,800 23,300/22,900 6,700/6,600 9,100/9,000 11,200/11,000 12,500/12,200 19,400/19,100 3.20/3.20 (V1) 3.95/3.95 (V1) 4.98/4.98 5.17/5.17 7.7/7.6 9.7/9.7 3.18/3.18 (Y1) 3.90/3.90 (Y1) White 13 13 16 17 24 30 458 458 564 600 847 1,059 37/32 38/33 38/33 39/35 42/37 44/39 195X 960X 680 195X 960X 680 195X 1,160X 680 195X 1,590X 680 195X 1,160X 680 195X 1,400X 680 23 24 26 27 32 35 14 to 25 Ivory white Hermetically sealed scroll type 2.24 3.00 3.75 9.0 4.50 5.5 2.8 3.7 3.7 4.1 5.3 5.7 (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 5 m) (Charged for 5 m) 48 49 49 54 60 61 1,440X 1,280X 690 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 770X 900X 320 1,220X 1,280X 690 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 109 178 202 -5 to 52 21 to 46, -15 to 46 4 (Option installed) o/ 9.5 o/ 9.5 o/ 9.5 o/ 12.7 o/ 9.5 o/ 15.9 o/ 15.9 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 25.4 (Flange) o/ 28.6 (Flange) I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 ----------------o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

140 200 200 FHY50BVE × 3 FHY71BVE × 3 FHY50BVE × 4 R140LUY1 R200KUY1 R200KUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V,50 Hz 22.5/22.2 14.5/14.2 kW 22.5/22.2 76,800/75,800 Btu/h 49,600/48,400 76,800/75,800 19,400/19,100 kcal/h 12,500/12,200 19,400/19,100 kW 5.17/5.17 7.7/7.6 7.7/7.6 Power consumption 1a/1b White Colour Indoor 17 13 m3/min 13 Airflow rate (H) unit 3 458 600 458 cfm 39/35 38/33 dB(A) 38/33 Sound level (H/L) 2 mm 195X 1,160X 680 195X 960X 680 195X 960X 680 Dimensions (HX WX D) kg 24 27 24 Machine weight 14 to 25 Certified operation range °CWB Ivory white Colour Outdoor Hermetically sealed scroll type Compressor Type unit 5.5 4.50 5.5 kW Motor output 4.1 (Charged for 30 m) 5.3 (Charged for 5 m) 5.3 (Charged for 5 m) kg Refrigerant charge (R-22) 60 60 dB(A) 54 Sound level 2 1,220X 1,280X 690 1,345X 900X 320 1,220X 1,280X 690 mm Dimensions (HX WX D) kg 109 178 178 Machine weight -5 to 52 Certified operation range °CDB 21 to 46, -15 to 46 4 (Option installed) mm Piping Liquid (Flare) o/ 9.5 o/ 12.7 o/ 12.7 connections Gas mm o/ 25.4 (Flange) o/ 25.4 (Flange) o/ 19.1 (Flare) mm Drain Indoor unit I.D o/ 20X O.D o/ 26 I.Do/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 ----------------Outdoor unit mm o/ 26.0 (Hole) m 50 (equivalent length 70 m) Max. interunit piping length 30 m Max. installation level difference Both liquid and gas piping Heat insulation

Indoor unit Model Name Outdoor unit Power supply Cooling capacity 1a/1b

250 FHY60BVE × 4 R250KUY1

Model Name Power supply Cooling capacity 1a/1b

Indoor unit Outdoor unit

Power consumption 1a/1b Colour Fan Airflow rate (H)

Indoor unit 3

External static pressure Sound level (H) 2 Dimensions (HX WX D) Machine weight Certified operation range Colour Outdoor Compressor Type unit Motor output Refrigerant charge (R-22) Sound level 2 Dimensions (HX WX D) Machine weight Certified operation range Piping Liquid (Flare) connections Gas (Flange) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

kW Btu/h kcal/h kW m3/min cfm Pa(mmH2O) dB(A) mm kg °CWB

kW kg dB(A) mm kg °CDB mm mm mm mm m m

200 200 250 FDYM03FAV1 × 3 FDYM04FAV1 × 2 FDYM05FAV1 × 2 R200KUY1 R250KUY1 R200KUY1 V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 22.5/22.2 22.5/22.2 27.1/26.6 76,800/75,800 76,800/75,800 92,500/90,800 19,400/19,100 19,400/19,100 23,300/22,900 8.0/7.9 7.7/7.6 9.9/9.9 ---------20 26 35 1,235 706 917 98(10) 98(10) 98(10) 44 39 39 295X 1,500X 680 295X 1,100X 680 295X 1,500X 680 56 57 42 14 to 25 Ivory white Hermetically sealed scroll type 5.5 9.0 5.5 5.3 (Charged for 5 m) 5.7 (Charged for 5 m) 5.3 (Charged for 5 m) 61 60 60 1,220X 1,280X 690 1,440X 1,280X 690 1,220X 1,280X 690 202 178 178 -5 to 52 o/ 15.9 o/ 12.7 o/ 12.7 o/ 25.4 o/ 28.6 o/ 25.4 o/ 25I.D.,o/ 32O.D. o/ 25I.D.,o/ 32O.D. o/ 25I.D.,o/ 32O.D. ------------------------50 (equivalent length 70 m) 30 Both liquid and gas piping

Note : Models R200KU and R250KU are recommended for commercial facilities. 1 Rated cooling capacities are based on the following conditions: 1a Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3 Values shown are for a single unit only.

27.1/26.6 92,500/90,800 23,300/22,900 9.7/9.7 16 564 38/33 195X 1,160X 680 26

9.0 5.7 (Charged for 5 m) 61 1,440X 1,280X 690 202 o/ 15.9 o/ 28.6 (Flange) I.D o/ 20X O.D o/ 26 ---------

Note : Models R200KU and R250KU are recommended for commercial facilities. 1 Rated cooling capacities are based on the following conditions: 1a Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.) 2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 3 Values shown are for a single unit only. 4 This value is for when year-round cooling kit (option) is installed.

47

48


CEILING MOUNTED CASSETTE TYPE Outdoor unit

Power supply Cooling capacity 1a/1b

kW Btu/h kcal/h kW Btu/h kcal/h kW kW

Heating capacity 2

Cooling 1a/1b Heating 2 Unit Colour Decoration panel m3/min Airflow rate (H) cfm dB(A) Sound level (H/L) 3 mm Dimensions Unit (H×W×D) mm Decoration panel kg Machine weight Unit kg Decoration panel °CWB Cooling Certified operation range Heating °CDB Colour Compressor Type Motor output kW

Power consumption Indoor unit

Outdoor unit

35 FHYC35KVE

Indoor unit

Model Name

Refrigerant charge (R-22) Sound level (Cooling/Heating) 3 Dimensions (H×W×D) Machine weight Cooling Certified operation range Heating Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

kg

50 FHYC50KVE

71 125 140 100 FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE RY100LUV1 RY71LUV1 RY35FV1A RY50GAV1A RY60GAV1A RY125LUY1 RY140LUY1 RY71LUY1 RY100LUY1 VE: 1 Phase 220–240/220 V, 50/60 Hz V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 3.79/3.75 7.8/7.7 13.0/12.8 14.5/14.2 10.5/10.4 5.27/5.2 6.24/6.15 12,900/12,800 18,000/17,800 21,300/21,000 26,600/26,200 35,700/35,300 44,500/43,600 49,400/48,400 3,260/3,230 6,700/6,600 9,000/8,900 11,200/11,000 12,500/12,200 4,530/4,470 5,370/5,290 4.22 16.3 7.9 5.8 11.2 7.0 14.2 14,400 56,000 27,000 19,800 38,100 23,900 48,400 3,630 14,000 6,800 4,990 9,600 6,020 12,200 3.01 /3.01 (V1), 2.99/2.99 (Y1) 3.93 /3.93 (V1), 3.88/3.88 (Y1) 1.51/1.50 4.89/4.89 4.95/4.95 1.92/1.91 2.35/2.33 1.37 2.84 (V1), 2.82 (Y1) 3.64 (V1), 3.60 (Y1) 4.68 4.84 1.68 2.26 ---------White 14 15 19 28 19 33 35 494 529 670 988 670 1,164 1,235 33/29 33/29 35/30 35/30 39/34 42/36 44/37 230×840×840 230×840×840 230×840×840 288×840×840 230×840×840 288×840×840 288×840×840 40×950×950 40×950×950 40×950×950 40×950×950 40×950×950 40×950×950 40×950×950 24 24 24 28 24 28 28 5 5 5 5 5 5 5 14 to 23 12 to 25 15 to 28 15 to 27 Ivory white Hermetically sealed rotary type Hermetically sealed scroll type 1.3 1.7 2.2 2.24 3.00 3.75 4.50 1.12 1.55 1.75 2.8 3.7 3.7 4.1 (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)

47/48 dB(A) 540×750×270 mm 41 kg °CDB °CWB o/ 6.4 mm o/ 12.7 mm mm I.Do/ 25×O.Do/ 32 o/ 18.0 (Hole) mm m 20 m

49/51 685×800×300 51 19.4 to 46 -10 to 15.5 o/ 6.4 o/ 15.9 I.Do/ 25×O.Do/ 32 o/ 18.0 (Hole) 15

60 FHYC60KVE

54/54 685×880×350 75

48/49 49/52 49/52 54/56 770×900×320 1,170×900×320 1,170×900×320 1,345×900×320 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) 101 112 -5 to 46 -10 to 15 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 30 50 (equivalent length 70 m) 30 Both liquid and gas piping

CEILING SUSPENDED TYPE Indoor unit

Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

Heating capacity 2

Power consumption Indoor unit

Outdoor unit

Cooling 1a/1b Heating 2

Colour Airflow rate (H) Sound level (H/L) 3 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Colour Compressor Type Motor output Refrigerant charge (R-22)

Sound level (Cooling/Heating) 3 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

71 100 125 FHY71BVE FHY100BVE FHY125BVE RY71LUV1 RY100LUV1 RY50GAV1A RY60GAV1A RY35FV1A RY125LUY1 RY71LUY1 RY100LUY1 VE: 1 Phase 220–240/220 V, 50/60 Hz V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 5.0/4.85 6.3/6.15 kW 10.5/10.4 13.0/12.8 3.5/3.5 7.8/7.7 16,900/16,600 21,400/21,000 12,100/11,900 26,600/26,200 35,700/35,300 44,500/43,600 Btu/h 4,260/4,200 5,390/5,300 3,040/3,000 6,700/6,600 9,000/8,900 11,200/11,000 kcal/h 5.5 7.1 4.1 7.9 11.2 14.2 kW 18,800 24,200 14,000 27,000 38,100 48,400 Btu/h 4,750 6,100 3,520 6,800 9,600 12,200 kcal/h 2.17/2.16 3.14/3.12 kW 3.04/3.04 (V1), 3.02/3.02 (Y1) 3.82/3.82 (V1), 3.77/3.77 (Y1) 1.58/1.57 4.85/4.85 kW 1.96 2.94 2.98 (V1), 2.95 (Y1) 3.69 (V1), 3.64 (Y1) 1.37 4.77 White 13 16 17 24 13 30 m3/min 458 564 600 847 458 cfm 1,059 38/33 38/33 39/35 42/37 37/32 44/39 dB(A) 195X 960X 680 195X 1,160X 680 195X 1,160X 680 195X 1,400X 680 195X 960X 680 195X 1,590X 680 mm kg 23 24 26 27 32 35 °CWB 14 to 23 12 to 25 °CDB 15 to 28 15 to 27 Ivory white Hermetically sealed rotary type Hermetically sealed scroll type 3.00 3.75 kW 1.3 1.7 2.2 2.24 3.7 3.7 1.12 1.55 1.75 2.8 kg (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) 35 FHY35BVE

dB(A) mm kg °CDB °CWB mm mm mm mm m m

47/48 540X 750X 270 41

o/ 6.4 o/ 12.7 I.Do/ 20X O.D o/ 26 o/ 18.0 (Hole) 20

50 FHY50BVE

49/51 685X 800X 300 51 19.4 to 46 -10 to 15.5 o/ 6.4 o/ 15.9 I.D o/ 20X O.D o/ 26 o/ 18.0 (Hole) 15

60 FHY60BVE

54/54 685X 880X 350 75

49/52 49/52 1,170X 900X 320 1,170X 900X 320 101 89 (V1), 86 (Y1) -5 to 46 -10 to 15 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 I.Do/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.Do/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 30 50 (equivalent length 70 m) 30 Both liquid and gas piping

Note : 1 Rated cooling capacities are based on the following conditions: 1a Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) 2 Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) 3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

49

48/49 770X 900X 320 73 (V1), 72 (Y1)

CEILING SUSPENDED CASSETTE TYPE Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

Heating capacity 2

Power consumption Indoor unit

71 FUY71FJV1 RY71LUV1 RY71LUY1

Indoor unit

Cooling 1a/1b Heating 2

Colour Airflow rate (H)

Sound level (H/L) 3 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Colour Outdoor Compressor Type unit Motor output Refrigerant charge (R-22) Sound level (Cooling/Heating) 3 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

kW Btu/h kcal/h kW Btu/h kcal/h kW kW m3/min cfm dB(A) mm kg °CWB °CDB

kW kg dB(A) mm kg °CDB °CWB mm mm mm mm m m

100 125 FUY100FJV1 FUY125FJV1 RY100LUV1 RY125LUY1 RY100LUY1 V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 13.0/12.8 7.8/7.7 10.5/10.4 44,500/43,600 26,600/26,200 35,700/35,300 11,200/11,000 6,700/6,600 9,000/8,900 14.2 7.9 11.2 27,000 38,100 48,400 6,800 12,200 9,600 4.90/4.90 3.02/3.02 (V1), 3.00/3.00 (Y1) 3.99/3.99 (V1), 3.94/3.94 (Y1) 4.61 2.87 (V1), 2.84 (Y1) 3.66 (V1), 3.62 (Y1) White 19 29 32 670 1,023 1,129 43/38 44/39 40/35 230X 895X 895 230X 895X 895 165X 895X 895 25 31 31 12 to 25 15 to 27 Ivory white Hermetically sealed scroll type 2.24 3.00 3.75 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m) 48/49 49/52 49/52 770X 900X 320 1,170X 900X 320 1,170X 900X 320 73 (V1), 72 (Y1) 101 89 (V1), 86 (Y1) -5 to 46 -10 to 15 o/ 9.5 o/ 9.5 o/ 9.5 o/ 15.9 o/ 19.1 o/ 19.1 I.D o/ 20X O.D o/ 26 o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

CEILING MOUNTED CASSETTE CORNER TYPE Model Name Power supply Cooling capacity 1a/1b

Heating capacity 2

Indoor unit Outdoor unit kW Btu/h kcal/h kW Btu/h kcal/h kW kW

Cooling 1a/1b Heating 2 Unit Colour Indoor Decoration panel unit m3/min Airflow rate (H) cfm dB(A) Sound level (H/L) 3 mm Dimensions Unit (HX WX D) mm Decoration panel kg Machine weight Unit kg Decoration panel °CWB Cooling Certified °CDB operation range Heating Colour Outdoor Compressor Type unit Motor output kW kg Refrigerant charge (R-22) dB(A) Sound level (Cooling/Heating) 3 mm Dimensions (HX WX D) kg Machine weight °CDB Cooling Certified °CWB operation range Heating mm Piping Liquid (Flare) connections mm Gas (Flare) mm Drain Indoor unit mm Outdoor unit m Max. interunit piping length m Max. installation level difference Heat insulation Power consumption

35 FHYK35FJV1

45 FHYK45FJV1

60 FHYK60FJV1

RY35FV1A

RY50GAV1A

RY60GAV1A

71 FHYK71FJV1 RY71LUV1 RY71LUY1

V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 7.8/7.7 3.5/3.5 5.0/4.85 6.3/6.15 26,600/26,200 12,100/11,900 16,900/16,600 21,400/21,000 6,700/6,600 3,040/3,000 4,260/4,200 5,390/5,300 7.9 5.5 7.1 4.1 27,000 14,000 18,800 24,000 6,800 3,520 4,740 6,080 1.47/1.46 1.95/1.94 2.87/2.85 3.01/3.01 (V1), 2.99/2.99 (Y1) 1,25 1.72 2.65 2.91 (V1), 2.88 (Y1) ---------White 12 17 12 17 423 600 423 600 39/33 41/36 39/34 41/36 215X 1,110X 710 215X 1,110X 710 215X 1,310X 710 215X 1,310X 710 70X 1,240X 800 70X 1,240X 800 70X 1,440X 800 70X 1,440X 800 30 31 33 33 8.5 8.5 9.5 9.5 14 to 23 12 to 25 15 to 27 15 to 28 Ivory white Hermetically sealed rotary type Hermetically sealed scroll type 1.3 1.7 2.2 2.24 1.55 (Charged for 10 m) 1.75 (Charged for 5 m) 2.8 (Charged for 30 m) 1.12 (Charged for 10 m) 47/48 49/51 54/54 48/49 685×880×350 770×900×320 540×750×270 685×800×300 41 51 75 73 (V1), 72 (Y1) 19.4 to 46 -5 to 46 -10 to 15.5 -10 to 15 o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5 o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9 I.D o/ 25×O.D o/ 32 I.D o/ 25×O.D o/ 32 I.Do/ 25×O.D o/ 32 I.Do/ 25×O.Do/ 32 o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) 20 30 50 (equivalent length 70 m) 15 30 Both liquid and gas piping

Note : 1 Rated cooling capacities are based on the following conditions: 1a Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.) 2 Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.) 3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

50


FLOOR STANDING TYPE

CEILING MOUNTED BUILT-IN TYPE 35 FHYB35FV1

Indoor unit

Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

kW Btu/h kcal/h kW Btu/h kcal/h kW kW

Heating capacity 2

Cooling 1a/1b Heating 2 Unit Colour Decoration panel m3/min Airflow rate (H) cfm dB(A) Sound level (H/L) 3 mm Dimensions Unit (HX WX D) mm Decoration panel kg Machine weight Unit kg Decoration panel °CWB Cooling Certified operation range Heating °CDB Colour Compressor Type Motor output kW

Power consumption Indoor unit

Outdoor unit

kg

Refrigerant charge (R-22) Sound level (Cooling/Heating) Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

3

dB(A) mm kg °CDB °CWB mm mm mm mm m m

71 100 125 FHYB71FV1 FHYB100FV1 FHYB125FV1 RY71LUV1 RY100LUV1 RY35FV1A RY50GAV1A RY60GAV1A RY125LUY1 RY100LUY1 RY71LUY1 V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 3.5/3.5 7.8/7.7 10.5/10.4 13.0/12.8 6.3/6.15 5.0/4.85 12,100/11,900 26,600/26,200 35,700/35,300 44,500/43,600 21,400/21,000 16,900/16,600 3,040/3,000 6,700/6,600 9,000/8,900 11,200/11,000 4,260/4,200 5,390/5,300 4.1 7.9 11.2 14.2 5.5 7.1 14,000 27,000 38,100 48,400 24,200 18,800 3,520 6,800 9,600 12,200 4,750 6,100 3.07/3.07 (V1), 3.05/3.05 (Y1) 3.92/3.92 (V1), 3.87/3.87 (Y1) 1.53/1.52 4.67/4.67 1.97/1.96 2.91/2.89 3.06 (V1), 3.03 (Y1) 3.75 (V1), 3.70 (Y1) 1.34 4.63 1.92 2.71 ---------White 11.5 14 17 19 27 35 405 494 600 670 953 1,235 38/32 39/34 41/35 41/35 41/35 44/38 300X 700X 800 300X 700X 800 300X 1,000X 800 300X 1,000X 800 300X 1,400X 800 300X 1,400X 800 55X 880X 500 55X 880X 500 55X 1,100X 500 55X 1,100X 500 55X 1,500X 500 55X 1,500X 500 30 31 41 41 51 52 3.5 3.5 4.5 4.5 6.5 6.5 14 to 23 12 to 25 15 to 28 15 to 27 Ivory white Hermetically sealed rotary type Hermetically sealed scroll type 1.7 2.2 2.24 1.3 3.00 3.75 1.55 1.75 2.8 1.12 3.7 3.7 (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) 47/48 540X 750X 270 41

o/ 6.4 o/ 12.7 I.D o/ 25X O.Do/ 32 o/ 18.0 (Hole) 20

45 FHYB45FV1

49/51 685X 800X 300 51 19.4 to 46 -10 to 15.5 o/ 6.4 o/ 15.9 I.D o/ 25X O.D o/ 32 o/ 18.0 (Hole) 15

60 FHYB60FV1

54/54 685X 880X 350 75

48/49 770X 900X 320 73 (V1), 72 (Y1)

49/52 49/52 1,170X 900X 320 1,170X 900X 320 101 89 (V1), 86 (Y1) -5 to 46 -10 to 15 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 30 50 (equivalent length 70 m) 30 Both liquid and gas piping

Indoor unit Outdoor unit

Power Supply Cooling capacity 1a/1b

Heating capacity 2

Power consumption Indoor unit

Cooling 1a/1b Heating 2

Colour Airflow rate (H)

Sound level (H/L) 3 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Colour Outdoor Compressor Type unit Motor output Refrigerant charge (R-22) Sound level (Cooling/Heating) 3 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

51

Outdoor unit

Cooling capacity 1a/1b

kW Btu/h kcal/h kW Btu/h kcal/h kW kW

71 FAY71LVE RY71LUV1 RY71LUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz 7.8/7.7 26,600/26,200 6,700/6,600 7.9 27,000 6,800 2.92/2.92 (V1), 2.90/2.90 (Y1) 2.85 (V1), 2.82 (Y1)

m3/min cfm dB(A) mm kg °CWB °CDB

19 670 43/37 290X 1,050X 230 13

kW kg dB(A) mm kg °CDB °CWB mm mm mm mm m m

2.24 2.8 (Charged for 30 m) 48/49 770X 900X 320 73 (V1), 72 (Y1)

o/ 9.5 o/ 15.9 I.D o/ 13X O.D o/ 18 o/ 26.0 (Hole)

100 FAY100FAVE RY100LUV1 RY100LUY1 V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 10.5/10.4 35,700/35,300 9,000/8,900 11.2 38,100 9,600 3.82/ 3.82 (V1), 3.77/ 3.77 (Y1) 3.66 (V1), 3.61 (Y1) White 23 811 45/41 360X 1,570X 200 26 12 to 25 15 to 27 Ivory white Hermetically sealed scroll type 3.00 3.7 (Charged for 30 m) 49/52 1,170X 900X 320 89 (V1), 86 (Y1) -5 to 46 -10 to 15 o/ 9.5 o/ 19.1 I.D o/ 20X O.D o/ 26 o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

Note : 1 Rated cooling capacities are based on the following conditions: (FHYB) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.) (FAY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal). 2 Rated heating capacities are based on the following conditions: (FHYB) Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.) (FAY) Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). 3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

kW Btu/h kcal/h kW Btu/h kcal/h kW kW

Heating capacity 2

Power consumption Indoor unit

Cooling 1a/1b Heating 2

Colour Airflow rate (H)

Sound level (H/L) 3 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Colour Outdoor Compressor Type unit Motor output Refrigerant charge (R-22) Sound level (Cooling/Heating) 3 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Liquid (Flare) Piping connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

m3/min cfm dB(A) mm kg °CWB °CDB

kW kg dB(A) mm kg °CDB °CWB mm mm mm mm m m

71 100 FVY71LAVE FVY100LAVE RY71LUV1 RY100LUV1 RY71LUY1 RY100LUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz 7.8/7.7 10.5/10.4 26,600/26,200 35,700/35,300 6,700/6,600 9,000/8,900 7.9 11.2 27,000 38,100 6,800 9,600 3.12/3.12 (V1), 3.10/3.10 (Y1) 3.95/3.95 (V1), 3.90/3.90 (Y1) 3.00 (V1), 2.97 (Y1) 3.75 (V1), 3.70 (Y1) White 18 28 635 988 41/35 46/40 1,850X 600X 270 1,850X 600X 350 39 46 12 to 25 15 to 27 Ivory white Hermetically sealed scroll type 2.24 3.00 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 48/49 49/52 770X 900X 320 1,170X 900X 320 89 (V1), 86 (Y1) 73 (V1), 72 (Y1) -5 to 46 -10 to 15 o/ 9.5 o/ 9.5 o/ 15.9 o/ 19.1 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

125 FVY125LAVE RY125LUY1 Y1: 3 Phase, 380–415 V, 50 Hz 13.0/12.8 44,500/43,600 11,200/11,000 14.2 48,400 12,200 4.99/4.99 4.73 32 1,129 49/43 1,850X 600X 350 47

3.75 3.7 (Charged for 30 m) 49/52 1,170X 900X 320 101

o/ 9.5 o/ 19.1 I.Do/ 20X O.Do/ 26 o/ 26.0 (Hole)

DUCT CONNECTION LOW STATIC PRESSURE TYPE Indoor unit

Model Name

WALL MOUNTED TYPE Model Name

Indoor unit

Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

kW Btu/h kcal/h kW Btu/h kcal/h kW kW

Heating capacity 2

Power consumption Indoor unit

Cooling 1a/1b Heating 2

Colour Airflow rate (H) Fan

Outdoor unit

External static pressure Driving system Sound level (H/L) 3 Dimensions(HX WX D) Machine weight Cooling Certified operation range Heating Colour Compressor Type Motor output

dB(A) mm kg °CWB °CDB

kW kg

Refrigerant charge (R-22) Sound level (Cooling/Heating) Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Piping Liquid (Flare) connections Gas (Flare) Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

m3/min cfm Pa(mmH2O)

3

dB(A) mm kg °CDB °CWB mm mm mm mm m m

35 FDYB35KAVE

50 FDYB50KAVE

60 FDYB60KAVE

71 FDYB71KAVE RY71LUV1 RY35FV1A RY50GAV1A RY60GAV1A RY71LUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 3.79/3.75 5.27/5.20 6.24/6.15 7.8/7.7 12,900/12,800 18,000/17,800 21,300/21,000 26,600/26,200 3,260/3,230 4,530/4,470 5,370/5,290 6,700/6,600 4.22 5.80 7.0 7.9 14,400 23,900 27,000 19,800 3,630 4,990 6,020 6,800 1.51/1.50 2.01/2.00 2.38/2.36 3.08/3.08 (V1), 3.06/3.06 (Y1) 1.33 1.78 2.29 2.91 (V1), 2.88 (Y1) ---------13 18 460 635 20 (2) Direct drive (2 speed) 41/38 43/40 260X 900X 580 260X 1,300X 580 22 23 31 14 to 23 12 to 25 15 to 28 15 to 27 Ivory white Hermetically sealed rotary type Hermetically sealed scroll type 1.3 1.7 2.2 2.24 1.12 1.55 1.75 2.8 (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) 47/48 540X 750X 270 41

49/51 685X 800X 300 51 19.4 to 46 -10 to 15.5 o/ 6.4 o/ 15.9

54/54 685X 880X 350 75

o/ 6.4 o/ 12.7

o/ 6.4 o/ 15.9

48/49 770X 900X 320 73 (V1), 72 (Y1) -5 to 46 -10 to 15 o/ 9.5 o/ 15.9

3/4B o/ 18.0 (Hole) 20

o/ 18.0 (Hole)

Note : 1 Rated cooling capacities are based on the following conditions: (FVY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal). (FDYB) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2 Rated heating capacities are based on the following conditions: (FVY) Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). (FDYB) Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). 3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

o/ 18.0 (Hole) 30

15

o/ 26.0 (Hole) 50 (equivalent length 70 m) 30

Both liquid and gas piping

52


Simultaneous operation system

TWIN & TRIPLE & DOUBLE TWIN MULTI DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

kW Btu/h kcal/h kW Btu/h kcal/h kW kW

Heating capacity 2

Power consumption Indoor unit

71 FDYM03FAV1 RY71LUV1 RY71LUY1

Indoor unit

Cooling 1a/1b Heating 2

Colour Fan Airflow rate (H)

m3/min cfm External static pressure Pa(mmH2O) dB(A) Sound level (H) 3 mm Dimensions (HX WX D) kg Machine weight °CWB Cooling Certified operation range Heating °CDB Colour Outdoor Compressor Type unit Motor output kW kg Refrigerant charge (R-22) dB(A) Sound level (Cooling/Heating) 3 mm Dimensions (HX WX D) kg Machine weight °CDB Cooling Certified operation range Heating °CWB mm Piping Liquid (Flare) connections mm Gas (Flare) mm Drain Indoor unit mm Outdoor unit m Max. interunit piping length m Max. installation level difference Heat insulation

100 125 140 FDYM04FAV1 FDYM05FAV1 FDYM06FAV1 RY100LUV1 RY125LUY1 RY140LUY1 RY100LUY1 V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 7.8/7.7 10.5/10.4 13.0/12.8 14.5/14.2 26,600/26,200 35,700/35,300 44,500/43,600 49,400/48,400 6,700/6,600 9,000/8,900 11,200/11,000 12,500/12,200 7.9 11.2 14.2 16.3 48,400 27,000 38,100 56,000 6,800 9,600 12,200 14,000 3.19/3.19 (V1), 3.17/3.17 (Y1) 4.00/4.00 (V1), 3.95/3.95 (Y1) 4.99/4.99 5.10/5.10 2.95 (V1), 2.92 (Y1) 3.91 (V1), 3.86 (Y1) 4.75 4.96 ---------20 26 35 37 706 917 1,235 1,306 98 (10) 98 (10) 98 (10) 98 (10) 39 39 44 46 295X 1,100X 680 295X 1,500X 680 295X 1,500X 680 295X 1,500X 680 42 56 57 57 12 to 25 15 to 27 Ivory white Hermetically sealed scroll type 2.24 3.00 3.75 4.50 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m) 4.1 (Charged for 30 m) 48/49 49/52 49/52 54/56 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) 101 112 -5 to 46 -10 to 15 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 oI.Do/ 25X O.Do/ 32 o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

DUCT CONNECTION HIGH STATIC PRESSURE TYPE Model Name Power supply Cooling capacity 1a/1b

kW Btu/h kcal/h kW Btu/h kcal/h kW kW

Heating capacity 2

Power consumption Indoor unit

Cooling 1a/1b Heating 2

Colour Airflow rate (H) Fan

Outdoor unit

External static pressure Driving system Sound level (H) 3 Dimensions(HX WX D) 5 Machine weight Cooling Certified operation range Heating Colour Compressor Type Motor output

Sound level (Cooling/Heating) Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Piping Liquid (Flare) connections Gas Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

m3/min cfm Pa(mmH2O) dB(A) mm kg °CWB °CDB

kW kg

Refrigerant charge (R-22) 3

200 250 400 500 FDY08KAY1 FDY10KAY1 FDY15KAY1 FDY20KAY1 RY200KUY1 RY250KUY1 RY200KUY1X 2 RY250KUY1X 2 Y1: 3 phase, 380–415 V (4 wires), 50 Hz 14.5/14.2 22.5/22.2 27.6/27.1 44.0/43.5 53.9/53.0 49,500/48,500 76,800/75,700 94,200/92,500 150,000/148,000 184,000/181,000 12,500/12,220 19,300/19,100 23,700/23,300 37,800/37,400 46,400/45,600 15.3 23.2 29.5 44.8 56.8 52,200 100,700 153,000 194,000 79,200 13,200 20,000 25,400 38,500 48,800 5.14/5.14 7.2/7.1 9.3/9.2 14.4/14.2 18.5/18.3 4.54 6.1 8.8 12.2 17.6 --------52 68 83 136 166 1,835 2,400 2,929 4,800 5,859 118 (12) 147 (15) 108 (11) Belt drive 51 53 58 60 450X 1,130X 850 500X 1,130X 850 500X 1,330X 850 625X 1,620X 850 625X 1,980X 850 80 94 105 161 187 12 to 25 14 to 25 15 to 27 Ivory white Hermetically sealed scroll type 4.5 5.5 9.0 5.5 X 2 9.0 X 2 4.1 4.0 5.5 4.0 5.5 (Charged for 5 m) X 2 (Charged for 5 m) X 2 (Charged for 30 m) (Charged for 5 m) (Charged for 5 m) 54/56 60/62 61/63 60/62 4 61/63 4 1,345X 900X 320 1,220X 1,280X 690 1,440X 1,280X 690 (1,220X 1,280X 690) X 2 (1,440X 1,280X 690) X 2 112 180 206 180 X 2 206 X 2 -5 to 46 0 to 50 0 to 50 -10 to 15 -10 to 15 -10 to 15 o/ 15.9 X 2 o/ 12.7 X 2 o/ 12.7 o/ 15.9 o/ 9.5 o/ 28.6 X 2 (Flange) o/ 25.4 X 2 (Flange) o/ 25.4 (Flange) o/ 28.6 (Flange) o/ 19.1 (Flare) 1B 3/4B --------o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping 140 FDY06KAY1 RY140LUY1

Indoor unit Outdoor unit

dB(A) mm kg °CDB °CWB mm mm mm mm m m

Note : Models RY200KU and RY250KU are recommended for commercial facilities. 1 Rated cooling capacities are based on the following conditions: 1a Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) 2 Rated heating capacities are based on the following conditions: Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) 3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 4 Specification for outdoor unit is for a single unit only. 5 Without control box.

53

CEILING MOUNTED CASSETTE TYPE Indoor unit

Model Name

Outdoor unit

Power supply Cooling capacity 1a/1b

Heating capacity 2

kW Btu/h kcal/h kW Btu/h kcal/h kW kW

Cooling 1a/1b Power consumption Heating 2 Colour Unit Indoor Decoration panel unit 3 m3/min Airflow rate (H) cfm dB(A) Sound level (H/L) 4 mm Dimensions Unit (HX WX D) Decoration panel mm kg Machine Unit weight Decoration panel kg °CWB Cooling Certified operation range Heating °CDB Colour Outdoor Compressor Type unit Motor output kW Refrigerant charge (R-22)

kg

Sound level (Cooling/Heating) 4 dB(A) mm Dimensions (HX WX D) kg Machine weight °CDB Cooling Certified operation range Heating °CWB mm Piping Liquid (Flare) connections Gas mm mm Drain Indoor unit Outdoor unit mm m Max. interunit piping length m Max. installation level difference Heat insulation Indoor unit Model Name Outdoor unit Power supply Cooling capacity 1a/1b

Heating capacity 2

200 250 125 71 100 140 FHYC50KVEX 2 FHYC125KVEX 2 FHYC60KVEX 2 FHYC35KVEX 2 FHYC100KVEX 2 FHYC71KVEX 2 RY100LUV1 RY71LUV1 RY250KUY1 RY125LUY1 RY200KUY1 RY140LUY1 RY100LUY1 RY71LUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 14.5/14.2 7.8/7.7 10.5/10.4 13.0/12.8 27.1/26.6 22.5/22.2 49,400/48,400 26,600/26,200 35,700/35,300 44,500/43,600 92,500/90,800 76,800/75,800 12,500/12,200 6,700/6,600 9,000/8,900 11,200/11,000 23,300/22,900 19,400/19,100 7.9 11.2 14.2 16.3 22.7 28.4 27,000 38,100 48,400 56,000 77,500 97,000 6,800 9,600 12,200 14,000 19,500 24,400 4.94/4.94 4.95/4.95 7.7/7.6 9.7/9.7 3.11/3.11 (V1), 3.09/3.09 (Y1) 3.98/3.98 (V1), 3.93/3.93 (Y1) 4.73 4.84 6.5 9.2 2.94 (V1), 2.92 (Y1) 3.69 (V1), 3.65 (Y1) ------------White 19 14 15 19 33 28 670 494 529 1,164 670 988 35/30 33/29 33/29 39/34 42/36 35/30 230X 840X 840 230X 840X 840 230X 840X 840 230X 840X 840 288X 840X 840 288X 840X 840 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 24 24 24 24 28 28 5 5 5 5 5 5 12 to 25 14 to 25 15 to 27 15 to 27 Ivory white Hermetically sealed scroll type 4.50 5.5 9.0 2.24 3.00 3.75 4.1 4.0 5.5 2.8 3.7 3.7 (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 5 m) (Charged for 5 m) 48/49 770X 900X 320 73 (V1), 72 (Y1)

o/ 9.5 o/ 15.9 (Flare) I.D o/ 25X O.D o/ 32 o/ 26.0 (Hole)

49/52 49/52 54/56 1,345X 900X 320 1,170X 900X 320 1,170X 900X 320 89 (V1), 86 (Y1) 101 112 -5 to 46 -10 to 15 o/ 9.5 o/ 9.5 o/ 9.5 o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

60/62 61/63 1,220X 1,280X 690 1,440X 1,280X 690 180 206 0 to 50 -10 to 15 o/ 12.7 o/ 15.9 o/ 25.4 (Flange) o/ 28.6 (Flange) I.D o/ 25X O.D o/ 32 I.Do/ 25X O.Do/ 32 -----------------

140 FHYC50KVEX 3 RY140LUY1

kW Btu/h kcal/h kW Btu/h kcal/h kW kW

Cooling 1a/1b Power consumption Heating 2 Colour Unit Indoor Decoration panel unit 3 m3/min Airflow rate (H) cfm dB(A) Sound level (H/L) 4 mm Dimensions Unit (HX WX D) Decoration panel mm kg Machine Unit weight Decoration panel kg °CWB Cooling Certified operation range Heating °CDB Colour Outdoor Compressor Type unit Motor output kW Refrigerant charge (R-22) kg Sound level (Cooling/Heating) 4 dB(A) mm Dimensions (HX WX D) kg Machine weight °CDB Cooling Certified operation range Heating °CWB mm Piping Liquid (Flare) connections Gas mm mm Drain Indoor unit Outdoor unit mm m Max. interunit piping length m Max. installation level difference Heat insulation

200 200 250 FHYC71KVEX 3 FHYC50KVEX 4 FHYC60KVEX 4 RY200KUY1 RY200KUY1 RY250KUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz 27.1/26.6 22.5/22.2 22.5/22.2 14.5/14.2 92,500/90,800 76,800/75,800 76,800/75,800 49,400/48,400 23,300/22,900 19,400/19,100 19,400/19,100 12,500/12,200 28.4 22.7 16.3 22.7 97,000 77,500 56,000 77,500 24,400 19,500 14,000 19,500 7.7/7.6 7.7/7.6 9.7/9.7 4.95/4.95 6.5 6.5 9.2 4.84 ------------White 19 19 15 15 670 670 529 529 35/30 35/30 33/29 33/29 230X 840X 840 230X 840X 840 230X 840X 840 230X 840X 840 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 24 24 24 24 5 5 5 5 12 to 25 14 to 25 15 to 27 15 to 27 Ivory white Hermetically sealed scroll type 5.5 5.5 4.50 9.0 4.0 (Charged for 5 m) 4.0 (Charged for 5 m) 4.1 (Charged for 30 m) 5.5 (Charged for 5 m) 60/62 60/62 54/56 61/63 1,220X 1,280X 690 1,220X 1,280X 690 1,345X 900X 320 1,440X 1,280X 690 112 180 180 206 -5 to 46 0 to 50 -10 to 15 -10 to 15 o/ 12.7 o/ 12.7 o/ 15.9 o/ 9.5 o/ 25.4 (Flange) o/ 25.4 (Flange) o/ 28.6 (Flange) o/ 19.1 (Flare) I.D o/ 25X O.D o/ 32 I.D o/ 25X O.Do/ 32 I.D o/ 25X O.D o/ 32 I.Do/ 25X O.D o/ 32 ------------------------o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

Note : Models RY200KU and RY250KU are recommended for commercial facilities. 1 Rated cooling capacities are based on the following conditions: 1a Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) 2 Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) 3 Values shown are for a single unit only. 4 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

54


Simultaneous operation system

TWIN & TRIPLE & DOUBLE TWIN MULTI CEILING SUSPENDED TYPE

DUCT CONNECTION LOW STATIC PRESSURE TYPE

71 100 125 140 200 250 Indoor unit FHY35BVE × 2 FHY50BVE × 2 FHY60BVE × 2 FHY71BVE × 2 FHY100BVE × 2 FHY125BVE × 2 Model RY71LUV1 RY100LUV1 Name Outdoor unit RY125LUY1 RY140LUY1 RY200KUY1 RY250KUY1 RY71LUY1 RY100LUY1 Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 7.8/7.7 10.5/10.4 13.0/12.8 14.5/14.2 27.1/26.6 Cooling capacity 1a/1b kW 22.5/22.2 Btu/h 26,600/26,200 35,700/35,300 44,500/43,600 49,400/48,400 92,500/90,800 76,800/75,800 kcal/h 6,700/6,600 9,000/8,900 11,200/11,000 12,500/12,200 23,300/22,900 19,400/19,100 7.9 11.2 14.2 16.3 22.7 28.4 Heating capacity 2 kW 27,000 38,100 48,400 56,000 77,500 97,000 Btu/h kcal/h 6,800 9,600 12,200 14,000 19,500 24,400 3.14/3.14 (V1) 3.87/3.87 (V1) Power 1a/1b 9.7/9.7 4.91/4.91 7.7/7.6 kW 5.10/5.10 Cooling consumption 3.12/3.12 (Y1) 3.82/3.82 (Y1) 9.2 3.08 (V1), 3.05 (Y1) 3.74 (V1),3.69 (Y1) 4.83 4.99 6.5 kW Heating 2 White Colour Indoor 16 13 17 24 13 30 m3/min Airflow rate (H) unit 3 564 458 458 600 847 1,059 cfm 38/33 37/32 38/33 39/35 42/37 44/39 dB(A) Sound level (H/L) 4 195X 1,160X 680 195X 960X 680 195X 960X 680 195X 1,160X 680 195X 1,400X 680 195X 1,590X 680 mm Dimensions (HX WX D) 23 24 26 27 32 35 kg Machine weight °CWB 12 to 25 14 to 25 Cooling Certified operation range Heating °CDB 15 to 27 15 to 27 Ivory white Colour Outdoor Hermetically sealed scroll type Compressor Type unit 2.24 3.00 3.75 4.50 5.5 9.0 Motor output kW 2.8 3.7 3.7 4.1 4.0 5.5 Refrigerant charge (R-22) kg (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 5 m) (Charged for 5 m) Sound level (Cooling/Heating) 4 dB(A) mm Dimensions (HX WX D) kg Machine weight °CDB Cooling Certified operation range Heating °CWB mm Piping Liquid (Flare) connections Gas mm mm Drain Indoor unit Outdoor unit mm m Max. interunit piping length m Max. installation level difference Heat insulation

48/49 770X 900X 320 73 (V1), 72 (Y1)

o/ 9.5 o/ 15.9 (Flare) I.D o/ 20X O.D o/ 26 o/ 26.0 (Hole)

49/52 49/52 54/56 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 89 (V1), 86 (Y1) 101 112 -5 to 46 -10 to 15 o/ 9.5 o/ 9.5 o/ 9.5 o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

60/62 61/63 1,440X 1,280X 690 1,220X 1,280X 690 180 206 0 to 50 -10 to 15 o/ 12.7 o/ 15.9 o/ 25.4 (Flange) o/ 28.6 (Flange) I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 -----------------

Model Name Power supply Cooling capacity 1a/1b

Indoor unit Outdoor unit

Heating capacity 2

Power consumption Indoor unit 3

Cooling 1a/1b Heating 2

Colour Airflow rate (H)

Fan External static pressure Sound level (H) 4 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Colour Outdoor Compressor Type unit Motor output Refrigerant charge (R-22) Sound level (Cooling/Heating) 4 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Piping Liquid connections Gas Drain Indoor unit Outdoor unit Max. interunit piping length Max. installation level difference Heat insulation

kW Btu/h kcal/h kW Btu/h kcal/h kW kW m3/min cfm Pa(mmH2O) dB(A) mm kg °CWB °CDB

kW kg dB(A) mm kg °CDB °CWB mm mm mm mm m m

200 200 250 FDYB50KAVE × 4 FDYB71KAVE × 3 FDYB60KAVE × 4 RY200KUY1 RY200KUY1 RY250KUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz 22.5/22.2 22.5/22.2 27.1/26.6 76,800/75,800 76,800/75,800 92,500/90,800 19,400/19,100 19,400/19,100 23,300/22,900 22.7 22.7 28.4 77,500 77,500 97,000 19,500 19,500 24,400 7.7/7.6 7.7/7.6 9.7/9.7 6.5 6.5 9.2 ––– 13 18 18 458 635 635 20 (2) 41 43 43 260X 900X 580 260X 1,300X 580 260X 1,300X 580 23 31 31 14 to 25 14 to 25 14 to 25 15 to 27 15 to 27 15 to 27 Ivory white Hermetically sealed scroll type 5.5 5.5 9.0 4.0 (Charged for 5 m) 4.0 (Charged for 5 m) 5.5 (Charged for 5 m) 60/62 60/62 61/63 1,220X 1,280X 690 1,220X 1,280X 690 1,440X 1,280X 690 180 206 180 0 to 50 -10 to 15 12.7 (Flare) 12.7 (Flare) 15.9 (Flare) 25.4 (Flange) 25.4 (Flange) 28.6 (Flange) 3/4B ––– 50 (equivalent length 70 m) 30 Both liquid and gas piping

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE Model Indoor unit Name Outdoor unit Power supply Cooling capacity 1a/1b

Heating capacity 2

Cooling 1a/1b Power consumption Heating 2 Colour Indoor Airflow rate (H) unit 3

140 FHY50BVE × 3 RY140LUY1

kW Btu/h kcal/h kW Btu/h kcal/h kW kW m3/min cfm dB(A) mm kg °CWB °CDB

Sound level (H/L) 4 Dimensions (HX WX D) Machine weight Cooling Certified operation range Heating Colour Outdoor Compressor Type unit Motor output kW Refrigerant charge (R-22) kg Sound level (Cooling/Heating) 4 dB(A) mm Dimensions (HX WX D) kg Machine weight °CDB Cooling Certified operation range Heating °CWB mm Piping Liquid (Flare) connections Gas mm mm Drain Indoor unit Outdoor unit mm m Max. interunit piping length m Max. installation level difference Heat insulation

200 200 250 FHY71BVE × 3 FHY50BVE × 4 FHY60BVE × 4 RY200KUY1 RY200KUY1 RY250KUY1 VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz 22.5/22.2 22.5/22.2 27.1/26.6 14.5/14.2 76,800/75,800 76,800/75,800 92,500/90,800 49,400/48,400 19,400/19,100 19,400/19,100 23,300/22,900 12,500/12,200 22.7 22.7 28.4 16.3 77,500 77,500 97,000 56,000 19,500 19,500 24,400 14,000 7.7/7.6 7.7/7.6 9.7/9.7 5.10/5.10 6.5 6.5 9.2 4.99 White 16 17 13 13 564 600 458 458 39/35 38/33 38/33 38/33 195X 1,160X 680 195X 1,160X 680 195X 960X 680 195X 960X 680 27 26 24 24 12 to 25 14 to 25 15 to 27 15 to 27 Ivory white Hermetically sealed scroll type 9.0 4.50 5.5 5.5 5.5 (Charged for 5 m) 4.1 (Charged for 30 m) 4.0 (Charged for 5 m) 4.0 (Charged for 5 m) 61/63 54/56 60/62 60/62 1,440X 1,280X 690 1,345X 900X 320 1,220X 1,280X 690 1,220X 1,280X 690 112 180 180 206 -5 to 46 0 to 50 -10 to 15 -10 to 15 o/ 12.7 o/ 12.7 o/ 15.9 o/ 9.5 o/ 25.4 (Flange) o/ 25.4 (Flange) o/ 28.6 (Flange) o/ 19.1 (Flare) I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.Do/ 20X O.D o/ 26 I.Do/ 20X O.D o/ 26 ------------------------o/ 26.0 (Hole) 50 (equivalent length 70 m) 30 Both liquid and gas piping

Note : Models RY200KU and RY250KU are recommended for commercial facilities. 1 Rated cooling capacities are based on the following conditions: 1a Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) 2 Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) 3 Values shown are for a single unit only. 4 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

55

Model Indoor unit Name Outdoor unit Power supply Cooling capacity 1a/1b

Heating capacity 2

Power consumption Indoor unit 3

Cooling 1a/1b Heating 2 Colour Fan Airflow rate (H)

kW Btu/h kcal/h kW Btu/h kcal/h kW kW

m3/min cfm External static pressure Pa(mmH2O) dB(A) Sound level (H) 4 mm Dimensions (HX WX D) kg Machine weight °CWB Cooling Certified operation range Heating °CDB Colour Outdoor Compressor Type unit kW Motor output kg Refrigerant charge (R-22) dB(A) Sound level (Cooling/Heating) 4 mm Dimensions (HX WX D) kg Machine weight °CDB Cooling Certified operation range Heating °CWB mm Piping Liquid (Flare) connections mm Gas mm Drain Indoor unit mm Outdoor unit m Max. interunit piping length m Max. installation level difference Heat insulation

200 250 200 FDYM04FAV1 × 2 FDYM05FAV1 × 2 FDYM03FAV1 × 3 RY200KUY1 RY250KUY1 RY200KUY1 V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 22.5/22.2 22.5/22.2 27.1/26.6 76,800/75,800 76,800/75,800 92,500/90,800 19,400/19,100 19,400/19,100 23,300/22,900 22.7 28.4 22.7 77,500 97,000 77,500 19,500 24,400 19,500 7.7/7.6 9.9/9.9 8.0/7.9 6.5 9.2 6.8 ---------20 26 35 706 917 1,235 98 (10) 98 (10) 98 (10) 39 39 44 295X 1,100X 680 295X 1,500X 680 295X 1,500X 680 56 57 42 14 to 25 15 to 27 Ivory white Hermetically sealed scroll type 5.5 5.5 9.0 4.0 (Charged for 5 m) 4.0 (Charged for 5 m) 5.5 (Charged for 5 m) 60/62 61/63 60/62 1,220X 1,280X 690 1,440X 1,280X 690 1,220X 1,280X 690 180 206 180 0 to 50 -10 to 15 o/ 12.7 o/ 12.7 o/ 15.9 o/ 25.4 (Flange) o/ 28.6 (Flange) o/ 25.4 (Flange) I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.Do/ 32 ------------------------50 (equivalent length 70 m) 30 Both liquid and gas piping

Note : Models RY200KU and RY250KU are recommended for commercial facilities. 1 Rated cooling capacities are based on the following conditions: 1a Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1b Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal) 2 Rated heating capacities are based on the following conditions: Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal) 3 Values shown are for a single unit only. 4 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

56


CEILING MOUNTED CASSETTE CORNER TYPE

Indoor unit

Kit name Name of option

CEILING MOUNTED CASSETTE TYPE Name of option

Remark

Decoration panel Sealing member for air discharge outlet Panel spacer Fresh air intake kit1 Chamber Without the T-joint pipe and fan type With the T-joint pipe,without fan Direct installation type Chamber connection kit2 High-efficiency filter (Colorimetric method 65%) (Colorimetric method 90%) Replacement (Colorimetric method 65%) high-efficiency filter (Colorimetric method 90%) High-efficiency filter chamber Replacement long-life filter Ultra long-life filter Replacement ultra long-life filter Branch duct chamber Remote controller Wired type3 Wireless type Wired LCD remote controller with weekly schedule timer Central remote controller4 Unified ON/OFF controller4 Schedule timer4 intelligent Touch Controller4 Adaptor for wiring5 Wiring adaptor for electrical appendices5 Interface adaptor for SkyAir series Installation box for adaptor PCB

Kit name Heat pump Cooling only FHC35K/50K/60K FHYC35K/50K/60K/71K FHYC100K/125K/140K FHYC100K/125K/140K FHYC35K/50K/60K/71K BYC125K-W1 KDBHJ55K160 KDBP55H160WA KDDP55D160 KDDP55D160K KDDJ55X160 KKSJ55K160 KAFP556D80 KAFP556D160 KAFP557D80 KAFP557D160 KAFP552H80 KAFP552H160 KAFP553H80 KAFP553H160 KDDFP55D160 KAFJ551K160 KAFP55D160 KAFJ55K160H KDJ55K80 KDJ55K160 BRC1C61 BRC7C612W BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 KRP1BA57 KRP4AA53 DTA102A52 KRP1B98

BYC125K-W1 KDBHJ55K160 KDBP55H160WA KDDP55D160 KDDP55D160K KDDJ55X160 KKSJ55K160 KAFP556D80 KAFP556D160 KAFP557D80 KAFP557D160 KAFP552H80 KAFP552H160 KAFP553H80 KAFP553H160 KDDFP55D160 KAFJ551K160 KAFP55D160 KAFJ55K160H KDJ55K80 KDJ55K160 BRC1C61 BRC7C613W BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 KRP1BA57 KRP4AA53 DTA102A52 KRP1B98

Note: 1 Refer to page 14 for the details. 2 Required for installing high-efficiency or ultra long-life filter. 3 Wiring for wired remote controller to be procured locally. 4 This optional accessory requires DTA102A52. 5 Installation box for adaptor PCB (KRP1B98) is necessary.

CEILING SUSPENDED TYPE Kit name Heat pump Cooling only FH(Y)35B FH(Y)50B FH(Y)60B FHY71B FHY100B FHY125B FHY35B FHY50B FHY60B FHY71B FHY100B FHY125B Replacement long-life filter Resin net KAFJ501D56 KAFJ501D80 KAFJ501D112 KAFJ501D160 KAFJ501D56 KAFJ501D80 KAFJ501D112 KAFJ501D160 Drain-up kit KDU50B50VE KDU50B71VE KDU50B125VE KDU50B125VE KDU50B50VE KDU50B71VE L-type piping kit (for upward direction) KHFJ5F160 KHFJ5F50 KHFJ5F60 KHFJ5F80 KHFJ5F160 KHFJ5F50 KHFJ5F60 KHFJ5F80 Remote controller Wired type1 BRC1C61 BRC1C61 BRC7E63W Wireless type BRC7EA66 Wired LCD remote controller with weekly schedule timer BRC1D61 BRC1D61 Central remote controller2 DCS302CA61 DCS302CA61 2 Unified ON/OFF controller DCS301BA61 DCS301BA61 Schedule timer2 DST301BA61 DST301BA61 intelligent Touch Controller2 DCS601C51 DCS601C51 Adaptor for wiring KRP1BA54 KRP1BA54 Wiring adaptor for electrical appendices3 KRP4AA52 KRP4AA52 Interface adaptor for SkyAir series DTA102A52 DTA102A52 KRP1CA93 KRP1CA93 Installation box for adaptor PCB Name of option

Remark

Note: 1 Wiring for wired remote controller to be procured locally. 2 This optional accessory requires DTA102A52. 3 Installation box for adaptor PCB (KRP1CA93) is necessary.

Kit name Remark

Replacement long-life filter Sealing member for air discharge outlet1 Decoration panel for air discharge Vertical flap kit L-connection piping kit Remote controller Wired type2 Wireless type Wired LCD remote controller with weekly schedule timer Central remote controller3 Unified ON/OFF controller3 Schedule timer3 intelligent Touch Controller3 Wiring adaptor for electrical appendices4 Interface adaptor for SkyAir series Installation box for adaptor PCB Note: 1 Required at time of installation for setting two-way opposing air flow. 2 Wiring for wired remote controller to be procured locally. 3 This optional accessory requires DTA102A52. 4 Installation box for adaptor PCB (KRP1B97) is necessary.

57

Decoration panel Panel spacer Air discharge blind panel Replacement long-life filter Resin net Discharge grille Flexible duct with shutter Wired type1 Remote controller Wired LCD remote controller with weekly schedule timer Central remote controller2 Unified ON/OFF controller2 Schedule timer2 intelligent Touch Controller2 Adaptor for wiring (interlock for fresh air intake fan) Wiring adaptor for electrical appendices Interface adaptor for SkyAir series

Cooling only FUY71FJ FUY100FJ/125FJ KAFJ495F140 KDBHJ49F80 KDBHJ49F140 KDBTJ49F80 KDBTJ49F140 KDGJ49F80 KDGJ49F140 KHFJ49F80 KHFJ49F140 BRC1C61 BRC7C529W BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 KRP4AA53 DTA102A52 KRP1B97

Heat pump FUY100FJ/125FJ KAFJ495F140 KDBHJ49F80 KDBHJ49F140 KDBTJ49F80 KDBTJ49F140 KDGJ49F80 KDGJ49F140 KHFJ49F80 KHFJ49F140 BRC1C61 BRC7C528W BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 KRP4AA53 DTA102A52 KRP1B97 FUY71FJ

FHK35F/45F BYK45FJW1 KPBJ52F56W KDBJ52F56W KAFJ521F56 K-HV7AW KFDJ52F56

Heat pump FHYK60FJ/71FJ BYK71FJW1 KPBJ52F80W KDBJ52F80W KAFJ521F80 K-HV9AW KFDJ52F80 BRC1C61 BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 KRP1B51 KRP4AA51 DTA102A52

Cooling only FHK60F/FHYK71F BYK71FJW1 KPBJ52F80W KDBJ52F80W KAFJ521F80 K-HV9AW KFDJ52F80 BRC1C61 BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 KRP1B51 KRP4AA51 DTA102A52

FHYK35FJ/45FJ BYK45FJW1 KPBJ52F56W KDBJ52F56W KAFJ521F56 K-HV7AW KFDJ52F56

Note: 1Wiring for wired remote controller to be procured locally. 2 This optional accessory requires DTA102A52.

CEILING MOUNTED BUILT-IN TYPE Kit name Heat pump Cooling only FHB35F/45F FHB60F/FHYB71F FHYB100F FHYB125F FHYB35F/45F FHYB60F/71F FHYB100F FHYB125F BYBS125DJW1 BYBS125DJW1 Decoration panel BYBS45DJW1 BYBS71DJW1 BYBS45DJW1 BYBS71DJW1 KTBJ25K160W KTBJ25K160W Service access panel KTBJ25K56W KTBJ25K80W KTBJ25K56W KTBJ25K80W KAFJ252L160 KAFJ252L160 (Colorimetric method 65%) KAFJ252L56 KAFJ252L80 KAFJ252L56 KAFJ252L80 High-efficiency filter KAFJ253L160 KAFJ253L160 (Colorimetric method 90%) KAFJ253L56 KAFJ253L80 KAFJ253L56 KAFJ253L80 KAFJ251K160 KAFJ251K160 Replacement long-life filter Resin net KAFJ251K56 KAFJ251K80 KAFJ251K56 KAFJ251K80 KAJ25L160D KAJ25L160D Filter chamber for bottom suction KAJ25L56D KAJ25L80D KAJ25L56D KAJ25L80D KAJ25L160B KAJ25L160B Filter chamber for rear suction KAJ25L56B KAJ25L80B KAJ25L56B KAJ25L80B KSA-25K160 KSA-25K160 Canvas duct KSA-25K56 KSA-25K80 KSA-25K56 KSA-25K80 (o/ 150) K-DG4DW K-DG4DW K-DG5DW K-DG5DW K-DG5DW K-DG4DW K-DG5DW K-DG4DW Discharge grille (o/ 200) K-DG7DW K-DG9DW K-DG7DW K-DG9DW K-DG7DW K-DG9DW K-DG7DW K-DG9DW K-DGC5D K-DGC4D K-DGC5D (o/ 150) K-DGC4D K-DGC4D K-DGC5D K-DGC4D K-DGC5D Discharge chamber (o/ 200) K-DGC7D K-DGC9D K-DGC7D K-DGC9D K-DGC7D K-DGC9D K-DGC7D K-DGC9D K-DDV20A K-DDV20A o/ 200 o/ 150 Branch duct (o/ 150) K-FDS151D (1 m) K-FDS152D (2 m) K-FDS153D (3 m) K-FDS151D (1 m) K-FDS152D (2 m) K-FDS153D (3 m) Flexible duct K-FDS154D (4 m) K-FDS155D (5 m) K-FDS156D (6 m) K-FDS154D (4 m) K-FDS155D (5 m) K-FDS156D (6 m) (o/ 200) K-FDS201D (1 m) K-FDS202D (2 m) K-FDS203D (3 m) K-FDS201D (1 m) K-FDS202D (2 m) K-FDS203D (3 m) K-FDS204D (4 m) K-FDS205D (5 m) K-FDS206D (6 m) K-FDS204D (4 m) K-FDS205D (5 m) K-FDS206D (6 m) KBBJ25K160 KBBJ25K160 Blind board KBBJ25K56 KBBJ25K80 KBBJ25K56 KBBJ25K80 KDAJ25K140 KDAJ25K140 Adaptor for discharge KDAJ25K56 KDAJ25K71 KDAJ25K56 KDAJ25K71 KDJ2507K160 KDJ2507K160 Flange for suction KDJ2507K56 KDJ2507K80 KDJ2507K56 KDJ2507K80 Remote controller Wired type1 BRC1C61 BRC1C61 Wired LCD remote controller with weekly schedule timer BRC1D61 BRC1D61 Central remote controller2 DCS302CA61 DCS302CA61 2 Unified ON/OFF controller DCS301BA61 DCS301BA61 Schedule timer2 DST301BA61 DST301BA61 intelligent Touch Controller2 DCS601C51 DCS601C51 Adaptor for wiring (interlock for fresh air intake fan) KRP1BA54 KRP1BA54 Wiring adaptor for electrical appendices3 KRP4AA51 KRP4AA51 Interface adaptor for SkyAir series DTA102A52 DTA102A52 Name of option

Remark

Note: 1Wiring for wired remote controller to be procured locally. 2This optional accessory requires DTA102A52. 3 Installation box for adaptor PCB (KRP1B97) is necessary.

WALL MOUNTED TYPE Kit name Name of option

FAY71L K-KDU572CVE

Wired type1 Wireless type Wired LCD remote controller with weekly schedule timer Central remote controller Unified ON/OFF controller Schedule timer intelligent Touch Controller Wiring adaptor for electrical appendices (2) Interface adaptor for SkyAir series3 Installation box for adaptor PCB 1 3

Heat pump

Cooling only

Remark

Drain-up kit Remote controller

CEILING SUSPENDED CASSETTE TYPE Name of option

Remark

FAY100FA

FAY71L K-KDU572CVE

BRC7C611W

BRC7EA618

BRC1C61

BRC1C61 BRC7E619

BRC7C610W BRC1D61

BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 KRP4AA51 3

FAY100FA

DCS302CA61 2 DCS301BA61 2 DST301BA61 2 DCS601C51 2 KRP4AA51 DTA102A52

DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 KRP4AA51 3

KRP4AA93

DCS302CA61 2 DCS301BA61 2 DST301BA61 2 DCS601C51 2 KRP4A51 DTA102A52

KRP4AA93

Wiring for wired remote controller to be procured locally. 2This optional accessory requires DTA102A52. Installation box for adaptor PCB (KRP4AA93) is necessary.

FLOOR STANDING TYPE Kit name Name of option

Remark

Replacement long-life filter Wired LCD remote controller with weekly schedule timer Central remote controller1 Unified ON/OFF controller1 Schedule timer1 intelligent Touch Controller2 Remote controller for 2 remote control system Adaptor for wiring2 Group control adaptor2 Interface adaptor for SkyAir series Installation box for adaptor PCB Note: 1This optional accessory requires DTA102A52. 2 Installation box for adaptor PCB (KRP4A95) is necessary.

Cooling only FVY71LA/100LA/125LA KAFJ95L160 BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 BRC1C61 KRP1BA57 KRP4AA52 DTA102A52 KRP4A95

Heat pump FVY71LA/100LA/125LA KAFJ95L160 BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 BRC1C61 KRP1BA57 KRP4AA52 DTA102A52 KRP4A95

58


DIME N S ION S

(Unit: mm)

Indoor unit CEILING MOUNTED CASSETTE TYPE

Support for centralised control from else where., using a PC with a Web browser (Optional)

Special Function 3

Sending of e-mail alerts to a specified address when malfunctions occur (Optional)

Special Function 4

Built-in Ethernet port for connecting to the Internet or an intranet

55

840

55

295

240

Suspension bolt 4-M8 M10

5

8

260 270 315

840 80 2 100=200 85

4

1

40 350

2

Special Function 5

Simple interlock function

Unification adapter for computerised control [DCS302A52]

Special Function 4

Unified ON/OFF and status monitoring from the central monitoring panel

1500mm or more Required space 1500mm or more

1500mm or more

1500mm or more When the discharge grill is closeout,the required space is 200mm or more.

A

C

FHYC100KVE-140KVE 288 298 195 14-M4 Hole (prepared hole) 40 50 155 165

40 350

B

230 240 165

55

Branch duct connection

A

1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection

195

150

Notes: 1 Location of unit's Name Plate For Main body: Switch Box Cover inside surface of suction grille. For decoration panel: Panel frame inside surface of suction grille. 2 When installing an optional accessory, refer to the installation drawings. For fresh air intake kit Inspection port is necessary. For high efficiency filter unit Inspection port is not necessary. 3 In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.

5 Remote control code and control wiring connection 6 Air discharge grille 7 Air suction grille 8 Port for water supply 9 Corner decoration cover 10 Drain hose

CEILING SUSPENDED TYPE

Special Function 3

1120 1160

FHY100BVE

1360 1400

FHY125BVE

1550 1590

KIS95

RG71A RG140A RG180A

R71LU

R100LU R125LU

R140LU

KIS95 -------

------KKPJ5F180 -------------

------KPW937A4 KKP937A4 1

-------

KHR58C21

KHD58C21A

-------------

RY35F RY50G(A) R60G(A)

KHD58D33 KRK5F80V1 KRK5F140V1 KRK5F160V1

-------

RY71LU

RY100LU RY125LU

RY140LU

------KKPJ5F180 ------------KHD58C21A KHR58C21 ------KHD58D33 -------

Note: 1One set includes 5 pieces for 5units.

A (Hanging position) Hanging bolt 4-M8~M10

1

Position : Hole of wall for taking out in piping back (View from the front)

6

90 155

300 or more

55

(Required space)

13

Kit name Cooling only

For twin multi For triple multi For double twin multi

R200KU KHD58C23A KHR58P322H KHRJ5F224F

R250KU KHD58C24A ------KHRJ5F280F

Heat pump RY250KU RY200KU KHD58C23A KHD58C24A KHR58P322H ------KHRJ5F224F KHRJ5F280F

80

11

40

5

195

680

B

30 or more (Service space)

30 or more (Service space)

4 o/ 45

55

14

The Front

Obstacle Floor side

Brand name plate (Note.2)

Drain pipe connection VP20 (For left piping)

6

80

3

Remark

105

15

225 275

-------

R71FU R100FU R125FU

10

300 275

Heat pump

For height installaion

Touch Controller.

Kit name R35G R50G R60G

65

60

8

Necessary for optional interface adaptor for SkyAir series (DTA112BA51) with the

Cooling only

50

Position slit hole for taking out in piping back (View from the front)

127

HRV

5 (Required space)

D -NET Plus Adapter Indoor Unit (option) [DCS601A52]

145 60 115 60

FHY71BVE

9

12

85 102 160 185 192 36

FH(Y)60BVE 1120 1160

Number of indoor unit expanded from 64 to 128.

R25J R35J

170 105 90 18 17 16 142 58

65

960

135

920

40

FH(Y)50BVE

From the floor side 2500 or more 155

Trouble reports

Outdoor unit

Drain piping kit Central drain plug Air direction adjustment grille Drain plug Refrigerant branch piping For twin multi For triple multi Year-round cooling kit

960

Special Function 1

Mobile Phone

* Limitations apply to some models and functions. For details please contact your local sales office.

Remark

B

920

5 135 (Required space)

D -NET

A FH(Y)35BVE

210

• Connection to power consumption metre when using power proportional distribution function. (Optional)

Forced OFF command from fire alarm monitoring panel

260

Pi Port

Trouble reports

Colour LCD Touch panel Icon display Multilingual (English, French, German, Spanish, Italian, or Chinese)

59

Branch duct connection

840 80 2 100=200 85

(Hanging position)

Forced OFF contact input

Special Function 3

Labor saving Overall energy savings Simplified BMS

Refrigerant branch piping

12-M4 Hole (prepared hole)

Remote monitoring and control

RS-232C

Name of option

55

[FHYC100KVE-140KVE]

DCS601C51

Yearly schedule Power proportional distribution* (option) Auto cool/heat change-over Temperature Limitation

Name of option

For fresh air intake kit connection (direct installation type)

B view Required space

[FH(Y)C35KVE-71KVE]

55

FH(Y)C35KVE-71KVE

PCMCIA Flash Memory

Special Function 2

80

B

1000 or more Required space

Special Function 2

60

160

420

A

New communication functions in the user-friendly icon based multilingual controller simplity centralised control of the system

• CSV output of power proportional distribution results (Optional)

C view 4-4M4 Hole (prepared hole) 75

3

55

Doubling of number of connectable indoor unit by adding a D -NET PLUS adapter (Optional)

Branch duct connection

7 A view

Note: 1 This optional accessory requires DTA102A52. 2 This optional accessory requires DTA107A55. 3 This optional accessory requires KRP1B100. 4 Installation plate for adaptor PCB (KRP4A95) is necessary. 5 In case of using KRC17-2B or field supplied remote controller, 3-Minutes Timer (field supplied) is required.

Special Function 1

C 165 155

6

40 350

80

BRC1C61 ------------BRC4C62 DCS302CA611 DCS301BA611 DST301BA611 DCS601C511 ------------KRP1BA573 KRP4AA533 ------DTA102A52 KRP1B100 -------------

780 Suspension position 860~890 Ceiling opening

10

95 110

BRC1C61 ------------BRC4C62 DCS302CA611 DCS301BA611 DST301BA611 DCS601C511 ------------------KRP4AA514 ------DTA102A52 -------------------

9

BRC1D61 -------

80 2 100=200 85

150

BRC1C61 ------------BRC4C64 DCS302CA611 DCS301BA611 DST301BA611 DCS601C511 ------------------KRP4AA514 ------DTA102A52 -------------------

300 or less

950

------KRC47-2A KRC47-4A -------------------------------------------------------------------------------------

------KRC47-3A KRC47-3A/ KRC17-2B 5 ------KRC47-5 ------------DCS302CA612 DCS301BA612 DST301BA612 DCS601C512 KRCS01-1B DTA107A55 -------------------------------------------

BRC1D61 -------

950

860~890 Ceiling opening 680 Suspension position 420

125 150 B

------BRC1C61 ------KRC47-2A ------KRC47-4A ------BRC4C62 ------DCS302CA611 ------DCS301BA611 ------DST301BA611 DCS601C511 ------------------------------------KRP1BA54 ------KRP4AA52 3 ------KRP1B100 ------DTA102A52 ------------KDGF19A45 KDGF19A71 KDGF19A45 KDGF19A71 KKD19A1 KKD19A1

BRC1D61 -------

750

Wired LCD remote controller Digital remote controller Digital remote controller for duct heater use Wireless remote controller Central remote controller Unified ON/OFF controller Schedule timer intelligent Touch Controller Remote sensor (for indoor temperature) Central control adaptor kit Adaptor for wiring Wiring adaptor for electrical appendices Switch box for adaptor kit Interface adaptor for SkyAir series Installation box for adaptor PCB Suction grille Drain pan cover

------KRC47-1A

BRC1D61 -------

Note3.

06K/08K/ 10K

Adjustable(0~550)

------KRC47-1A

Wired LCD remote controller with weekly schedule timer Remote controller

C

200

Remark

40 A 30 10

Name of option

High static pressure type Heat pump Cooling only FD03K/ FD15K/ FDY06KA/08KA/ 04K/05K/ 20K 10KA/15KA/20KA

Middle static pressure type Heat pump Cooling only FDMG71A/ FDYM03FA/ FDYM03FA/ 100A/125A/ 04FA/05FA/ 04FA/05FA/ 140A/180A 06FA 06FA

Low static pressure type Heat pump Cooling only FDBG25A/ FDBG60A/ FDYB35KA/ FDYB60KA/ 35A/50A 71A 50KA 71KA

1000 or more Required space 165

DUCT CONNECTION TYPE

2

Notes: 1 Location of unit's Name Plate: Bottom of fan housing inside the suction grille. 2 In case of using wireless remote controller, this position will be a signal 3 The remote control code is the standard <about 3 m outside the machine> attached. (0.5 mm2 2 wicks O.D. 5.4) (It is attached to VRV.)

7

5

80 105 170

4

1 Air discharge grille 2 Air suction grille 3 Air filter 4 Gas pipe connection 5 Liquid pipe connection 6 Drain pipe conneciton 7 Earth terminal (inside the electric components box) (M4) 8 Suspension bracket 9 Backward piping and wiring connection opening lid 10 Upward piping and wiring connection opening lid 11 Right side pipe connection 12 Left back drain pipe connection 13 Left side drain pipe connection 14 Right side drain pipe connection 15 Hole of wall for taking out in piping back 16 Upward drain pipe connection 17 Upward gas pipe connection 18 Upward liquid pipe connection

60


DIME N S ION S

(Unit: mm)

CEILING MOUNTED BUILT-IN TYPE

1500mm or more

Suspension bolt

65

895

1500mm or more When closing the discharge grill,the required space is 30mm or more.(Note3)

790 Susension position

A 300 or more

52

1

F

G

H

58

40

165

FUY100FJV1/125FJV1

51

147 177 177 147 125 107 230

6

52

1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Air outlet

132 1000mm or more (Required space)

Notes: 1 Location for manufacture's label: on bell mouth. 2 This is where the signal of wireless remote controller is received. Refer to the drawing of wireless remote controller in detail. 3 When closing the discharge grille (2 or 3 way discharge), direction of pipe connection will be limited, please refer to Installation manual.

5 Air suction grille 6 Corner decoration cover 7 Right pipe/wiring connection

140

170

200mm or more

1500mm or more

8

9

7

65

800

710

290

Dimensions for full open front panel

60

80

230

75

30 or more (Required space)

45

80

3 2

Piping direction

1

Name plate Note)2

50 or more

61

215

50 or more

B

C

D

E

F

G

FH(Y)K35.45F(J)V1

1150 1200 1110

FH(Y)K60.71F(J)V1

1350 1400 1310 2 230=460 720 1440 6-M4 hole

260

Note. 2: Location of unit's Name plate For main body: Bottom part of fan housing inside of Air suction grille. For decoration panel: Service lid face inside of Air suction grille. When installing an optional accessory, refer to the installation drawings. For discharge grille For frexible duct For panel spacer For air discharge blind panel Inspection port is not necessary

520 1240 4-M4 hole

(Requred space) 104

894

2500 or more For installation in high spaces

52

Outside line Notes: Location of unit's of NAME Plate: Right side surface of casing 2 In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail. 80 hole 1

1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Wire intake 5 Wire intake for remote control cord 6 Grounding terminal (M4 in switch box) 7 Air discharge grille 8 Air suction grille 9 Long life air filter 10 Suspension bracket

105

170 10000 or more

20

E

Front discharge duct connection position (Note.2) Suspension bolt 4-M8~M10

Required space

D

140

120 100

G

A 65

14.5

10

B (Ceiling opening) C

7

120 or less

1050

44

5

Piping direction

(Requred space)

45

20

8

4-M4 hole 9

65

150 250 300

160

230 Fresh air intake position

280

125

100 Approx.400

232

F

190

500

Piping direction 200mm or more

20mm or more

250

20

Liquid pipe connection Gas pipe connection Drain pipe connection Wire intake for remote control cord Wire intake Drain hole Air filter

[FAY71LVE]

Required space

4

350 (Suspension position)

C View

H (Suspension position)

215

A (Suspension position)

1 2 3 4 5 6 7

WALL MOUNTED TYPE

3

6

20

Notes: Location of unit's Name Plate: Fan housing surface inside of filter. 2 When installing an optional accessory, refer to the installation drawings. 3 Refer to the separate drawing when installing the duct. 1

7

10 Accessory drain elbow

67

5

600 Fresh air intake position

A View

148

760 (Ceiling opening)

160 P.C.D 125 (Knockout hole)

6 65=390

FH(Y)B35FV1/45FV1

44

2

1

G

B View

6-M5 hole (Circumference)

8 Rear pipe/wiring connection 9 Pipe through cover

CEILING MOUNTED CASSETTE CORNER TYPE 5

L J K H 750 650 628 4 150=600 FH(Y)B60FV1/71FV1 11 65=715 1050 950 927 6 150=900 FHYB100FV1/125FV1 16 65=1040 1450 1328 1328 9 150=1350

18-M5 hole

50 or more (Required space)

E 80

20

D

Height of suspension bracket

4

G

80

F

B

16

E

C

D

A FUY71FJV1

A

G

Suspension bolt

A B C D F E 700 485 460 3 150=450 760 800 FH(Y)B60FV1/71FV1 1000 785 760 5 150=750 1060 1100 FHYB100FV1/125FV1 1400 1185 1160 7 150=1050 1460 1500

L

(Ceiling opening)

630 (Suspension position) 145

3

H

145 185

8

110 110

(Ceiling opening)

80

Sustion air intake position when installing the duct (Note.3)

FH(Y)B35FV1/45FV1

462

30 180

F

C

4

J K

E

7 5

6

83

109

9

46

2

Service space

895

790 Susension position

2

5

B 45

57

10

Drain pipe can be raised up to 350mm from the top surface of the product. Brand name plate (Note)2)

45 115~255

B

A

C

1500mm or more

2 65=130

10

117

3

1

67 150 200

10

300 245 215 150 135

163

1500mm or more

33

83

83

Required space

The required ceiling depth varies according to configration of specific system

195

Drain connection location for rear piping

800 595 (Air suction parelcenter) 440 315

25

228

Drain connection location for upper piping

60 50

465 or more Required installation space

A B C D

135 120

CEILING SUSPENDED CASSETTE TYPE

6 60

5 4

Approx.345 Approx.390 Approx.475

Mounting location

98 80 hole Piping and Wiring intake

1 2 3 4 5 6 7 8 9

Front panel Front grille Air outlet Gas pipe Liquid pipe Drain hose Grounding terminal Right side pipe connection hole Left side pipe connection hole

62


DIME N S ION S

(Unit: mm)

WALL MOUNTED TYPE

DUCT CONNECTION LOW STATIC PRESSURE TYPE

Piping direction

A

580 A

A

A

A

A

4 5

45

142

A

53

A

2 110 170 228

360

A

684 664 D

Direction for air filter draw out 50

123

164 134 107

120

120

Service space

126

C (Suspension bolt pinch)

260

210

(Required space)

120

50 or more

180

100

10 10

50 40 40

50 35

50 30 40 40

Approx. 450 Approx. 580 Approx. 600

6

15

40 50 70

120

1235 120

Ceiling surface 15

60 40 6 6

2

8-5x20 Oval Hole (For wood screw) 5-6x20 Oval Hole (For wood screw)

8

5

13- 5 Hole (For wood screw) 2- 12 Hole (For bolt)

4

60

6

29

7

Mounting location

1 2 3 4 5 6 7 8 9

Front grille Air filter Discharge outlet Gas piping connection Gas piping connection Drain piping connection Earth terminal (M4) (inside cover) Slit hole for right side piping connection Slit hole for left side piping connection

FLOOR STANDING TYPE

1 2 3 4 5 6 7 8

Liquid pipe connection Gas pipe connection Drain pipe connection Ground terminal Switch box Control wiring intake (for outdoor unit) Control wiring intake (for remote controller) Suspension bracket

Note: 1Location of unit's Name Plate: Chamber cap

F G H I J

127

1

16 10 151

L (All around)

Detail A (Mounting hole for installation plate)

Notes: 1 Location of general rated name plate Right side plate outside surface 2 In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.

E

K (All around)

80 Hole Piping and wiring intake

150 219 236

250 or more Service space for air filter

52 16 10

Brand name plate Note 2.

3

55

8

200 74

317

7

360

9

10 or more

3

1

300 or more

260

1570

3

271

50 or more (Required space)

137 167

50 or more (Required space)

595

500 (Suspension bolt pinch)

B

[FAY100FAVE]

A

B

C

D

E

F

G

H

I

J

FDBG25AVE/35AVE/50AVE

900

704

755

3XP150=450

500

3XP150=450

674

688

704

900

K

L

FDYB25KVE/35KAVE/50KAVE FDBG60AVE/71AVE

900 704 755 3XP150=450 1300 1104 1155 6XP150=900

500 700

3XP150=450 674 688 704 900 6XP150=900 1074 1088 1104 1300

10-M4 12-M4

FDYB60KAVE/71KAVE

1300 1104 1155 6XP150=900

700

6XP150=900 1074 1088 1104 1300

16-M4 18-M4

10-M4 12-M4 Holes Holes

Holes Holes

16-M4 18-M4 Holes Holes

Holes Holes

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE A 3

DETAIL OF CONTROL PANEL IN CASE OF FIXING IT AT THE REAR NORMAL INSTALLATION

1850

2-7X15 OBLONG HOLE (FOR WOOD SCREW)

2 50

OR

50 OR

63

6

50

95 75

F G H

3 THROUGH HOLE FOR SIDE PIPING 4 THROUGH HOLE FOR SIDE PIPING 5 THROUGH HOLE FOR SIDE WIRING 6 THROUGH HOLE FOR REAR PIPING/WIRING 7 THROUGH HOLE FOR BOTTOM PIPING/WIRING 8 LIQUID PIPE CONNECTION

5

4

REQUIRED SPACE

1 SUCTION GRILL 2 AIR FILTER

D

100

95 598

6

E

0O

0

15

3

6

541 616

825 34

200 223 253

O RM

FULL OPEN POSITION OF SUCTION B GRILL C

2

184

184

9 GAS PIPE CONNECTION 10 DRAIN PIPE CONNECTION

NOTES: 1STICKING LOCATION FOR MANUFACTURE'S LABEL : ON THE SURFACE OF COVER OF SWITCH BOX INSIDE THE SUCTION GRILL.

151 8 16

4

51

1350 1153 1137 1121 7XP150=1050

5

H

29

6

1

7 20-M4 Holes

(All around) MO RE

RE

APPROX. 36

10

[FDMG71AV1]

D E F

G (All around)

MO RE

1

9

126

305 206 175 123

740 OR MORE

8

TAKE OUT DIMENSION OF AIR-FILTER

677

FIXTURE (ACCESSARY)

C (Suspension bolt pinch)

305

314

TAKE OUT DIRECTION OF AIR-FILTER

Service space

150 263 280

A

8

1 2 3 4 5 6 7 8

[FDMG100AV1/125AV1/140AV1/180AV1]

Liquid pipe connection Gas pipe connection Drain pipe connection Ground terminal Switch box Control wiring intake (for remote controller) Control wiring intake (for outdoor unit) Suspension bracket

I 151 8 16

J K L 51

M

150 263 280

18

330

74 16 10

IN CASE VIBRATION RESISTANCE IS REQUIRED, FIX IT AT BOTH THE BOTTOM AND THE REAR.

7

4- 14HOLE (FOR BOLT) 68

3

300 or more

Note: 1Location of unit's Name Plate: Chamber cap N

D E F FDMG71AV1 1350 1153 1203 1134 1114 7XP150=1050 FDMG100AV1/125AV1/140AV1 1550 1353 1403 1334 1314 7XP150=1050 FDMG180AV1 1900 1703 1753 1684 1664 9XP150=1350 A

B

C

G

H

18-M4

727

18-M4

827 827

Holes Holes

22-M4 Holes

74 16 10

126

THIS MODEL TO BE FIXED WITH FIXTURE AS SHOWN BELOW. IN CASE OF FIXING IT AT THE BOTTOM

305

215

130

J

130

K

FVY100LAVE/125LAVE 350 44 49 130 190 260 266 322 79 202 229

VIEW

381

260

270 45 50 50 110 180 186 242 57 144 149

600

151

B

L

146

K

116

J

600

H

(Suspension bolt pinch)

G

55

F

152 212 274

E

427

D

50

C

L

FVY71LAVE

B

680

A

(All around)

L I J K M FDMG100AV1/125AV1/140AV1 1550 1353 1337 1321 7XP150=1050 FDMG180AV1 1900 1703 1687 1671 9XP150=1350

N 20-M4 Holes

24-M4 Holes

64


DIME N S ION S

(Unit: mm)

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

DUCT CONNECTION HIGH STATIC PRESSURE TYPE 236 220 (OPENING)

680

9

[FD08KY1]

[FD10KY1]

1200 or more P

72

3

7

FDYM03FA FDYM04FA-06FA

N P 5xP150=750 16- 7 HOLE 8xP150=1200 22- 7 HOLE

5

K 14- 7 HOLE 20- 7 HOLE

L 1079 1479

M 1064 1464

DUCT CONNECTION HIGH STATIC PRESSURE TYPE

Q 46 V U

3

FD06KY1 FD08KY1 FD10KY1

A

B

756 732 732

35 39 39

C

D

E

F

G

967 5XP.180=900 1130 1180 1230 876 4XP.180=720 1130 1180 1230 1076 5XP.180=900 1330 1380 1430

1

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

6-M4 Burring holes 5-M4 Burring holes 6-M4 Burring holes

9 10 10

50 58 58

58 67 67

266 294 294

150 160 160

261 311 311

75 100 100

148 155 155

58 67 67

418 468 468

450 500 500

9 10 10

90 79 79

85 47 47

DUCT CONNECTION HIGH STATIC PRESSURE TYPE

B 850

35

3

756

3 3

3 9

Service Space

C

9

9

B

10

850 A

300 or more

6

9

35

E D

D E

Air inlet

9

FD03KY1 FD04KY1

552

3XP150=450

FD05KY1

735

4XP150=600

C 650 900 900

D E 700 750 950 1000 950 1000

58 9

[FDY08KAY1]

800 or more

Service Space

325

[FDY10KAY1]

1200 or more 63

2-M4 Burring holes (Both sides)

4 9

2

4

50

50 85

O L K K L M N J

418

J 90

450

150 9

46

B 2XP120=240

10

58

75 261 9

3

A 302

58 9

[FDY06KAY1]

58 266 150 2-M4 Burring holes (Both sides)

3

3

4

266

63

148

5

50

2

9

3

1200 or more

9

2-M4 Burring holes (Both sides)

Arrow View

1

1 2 3 4 5 6

Liquid pipe connection Gas pipe connection Drain pipe connection Earth terminal Power supply Suspension bracket

I

50

[FD05KY1]

196

3

50

50

800 or more

[FD04KY1]

Service Space

S (Both sides)

S (Both sides)

9

9

D E

B A C

B

A

Air outlet

[FD03KY1]

J

2-M4 Burring holes (Both sides)

H

287

J 850 1250

T

F G

118

FDYM03FA FDYM04FA-06FA

H 834 1234

T

Liquid pipe connection Gas pipe connection Drain pipe connection Earth terminal Power supply Suspension bracket

130

130 295

130

SUCTION SIDE (NOTE.1)

2-M4 Burring holes (Both sides)

R S

F G E 38- 4.7 HOLE 30- 4.7 HOLE 4xP150=600 50- 4.7 HOLE 44- 4.7 HOLE 7xP150=1050

1 2 3 4 5 6

4 50

5

2

L M

FDYM03FA FDYM04FA-06FA

4

(SERVICE SPACE)

G

9

[FD06KY1]

3

Service Space

N

D A B C 1100 11xP65=715 15xP65=975 1140 1500 18xP65=1170 21xP65=1365 1540

E F

D C I

L M

FDYM03FA FDYM04FA-06FA

INSPECTION HOLE 450 OR MORE

1

31

I

K

136

H (Both sides)

63

E (ALL ROUND)

145 95

DISCHARGE SIDE

3

H (Both sides)

NOTES: 1 MOUNT THE AIR FILTER AT THE SUCTION SIDE. SELECT ITS COLORIMETHOD (GRAVITY METHOD) 50% OR MORE.

58

750 OR MORE

(SERVICE SPACE)

25

680 OR MORE

2

B

O

P (ALL ROUND)

K (ALL ROUND)

125

6

850 A

C D

1 LIQUID PIPE CONNECTION [ 9.5(FLARE CONNECTION)] 2 GAS PIPE CONNECTION [03F: 15.9(FLARE CONNECTION)] [04~06F: 19.1(FLARE CONNECTION)] 3 DRAIN PIPE CONNECTION[VP25] 4 EARTH TERMINAL (INSIDE SWITCH BOX) 5 POWER SUPPLY 6 SUSPENSION BRACKET [FOR M10 or M8 BOLT] 7 MANUFACTURER'S LABEL

N

M

L

D

(SUSPENSION POSITION)

C

A

B

100

6

B

H

G

115

100

J

F (ALL ROUND)

800 or more

600 (SUSPENSION POSITION)

50

210 194 (OPENING)

I

46 P Q

2-M4 Burring holes (Both sides)

A FDY06KAY1 756 FDY08KAY1 732

B 35 39

C 9 10

D 967 876

E F G H 5XP180=900 1130 1180 1230 4XP180=720 1130 1180 1230

I 9 10

J 58 67

K 150 160

L 266 294

M 418 468

N 450 500

O 261 311

P 90 79

Q 85 47

FDY10KAY1 732

39

10

1076 5XP180=900 1330 1380 1430

10

67

160

294

468

500

311

79

47

8 1 6 5 7

1 2 3 4 5 6 7 8 9 10 11

Liquid pipe connection Gas pipe connection Drain pipe connection Earth terminal Hole for power supply Hole for motor wiring Hole for wiring from outdoor unit Hole for remote controller wiring Control box Auxiliary pipe Suspension bracket

Note: 1Location of unit's Name Plate: Lid of control box.

65

66


DIME N S ION S

(Unit: mm)

DUCT CONNECTION HIGH STATIC PRESSURE TYPE

OUTDOOR UNIT // R25JV1, R35JV1

50 or more

12

33

7

Service Space

10

265

4

3

6

5

10

100 50

Service Space

12

190

*1 7- o/ 3.1 holes (Upward and downward)

Air inlet

306

290 95

48

237

60

170

213

*1 10- o/ 3.1 holes (Upward and downward)

Air outlet B

520

DRAIN OUTLETS

10

1045

700

HOLES FOR ANCHOR BOLTS (M8 OR M10)

5

B C D E F G

100 or more

50

Supprting plate

(Commercially available) 800 or more

100 or more

50

OUTDOOR UNIT // R35GV1, RY35FV1A, R50GV1

DUCT CONNECTION HIGH STATIC PRESSURE TYPE

(Commercially available)

150

Evaporator air outlet connection Evaporator air inlet connection Liquid pipe connection (No.1) Gas pipe connection (No.1) Liquid pipe connection (No.2) Gas pipe connection (No.2) Drain pipe connection Earth terminal Power supply intake The holes for anchor bolts

300

544 625

3XP150=450

45 61

763 805

Notes: 1Prepared holes for M4 tapping screw.

38

349

22.5 2XP150=300

257

1 2 3 4 5 6 7 8 9 10

1

10

72

100

530 +4

0

+4

FDY15KAY1

A B C D E F G 500 9XP150=1350 1042 1620 1710 1750 1770

H 24

FDY20KAY1

800 or more

54

11XP150=1650 1762 1980 2070 2110 2220

10

27

SERVICE PORT

MINIMUM SPACE FOR AIR PASSAGE

50

50 100

763 805

Liquid pipe connection (No.1) Gas pipe connection (No.1) Liquid pipe connection (No.2) Gas pipe connection (No.2) Drain pipe connection Earth terminal Hole for power supply Hole for motor wiring Hole for wiring from outdoor unit (No.1) Hole for wiring from outdoor unit (No.2) Hole for remote controller wiring Control box The holes for anchor bolts

150

8 38

7

Arrow view (detail)

1 2 3 4 5 6 7 8 9 10 11 12 13

58

300

6

LIQUID STOP VALVE 105

34

150

*1 4- o/ 3.1 holes (Both sides)

12

GAS STOP VALVE

35

100

600 850

3XP150=450

2XP150=300 22.5

257 349

11

10

POWER INTAKE NAME PLATE

544 625

100

10

Arrow view

3

500 or more 35

*1 3- o/ 3.1 holes (Both sides)

4

5

[FDY20KAY1]

9

1

540

2

Service Space

14

[FDY15KAY1]

0

EARTH TERMINAL (M4)

A

485

12580 80 80

270

H 172

20

45 61

12580 80 80

+4

15

0

71.5

55 193

55

477.5

6

72.5 200 168

750

6

LIQUID STOP VALVE (o/ 6.4CuT)

WALL HEIGHT ON AIR OUTLET SIDE =LESS THAN 1200

*1 4- o/ 3.1 holes (Both sides)

2

21

178

GAS STOP VALVE (o/ A CuT)

MINIMUM SPACE FOR AIR PASSAGE

35

*1 3- o/ 3.1 holes (Both sides)

Supprting plate

12.7

150

600 850

100

100

H 24 54

118

SERVICE PORT

35

50 or more

R35JV1

74

7 500 or more

50 or more

TERMINAL STRIP WITH EARTH TERMINAL

78

Service Space

[FD20KY1]

A B C D E F G FD15KY1 10- o/ 3.1 holes 9XP.150=1350 1042 1620 1710 1750 1770 FD20KY1 12- o/ 3.1 holes 11XP.150=1650 1762 1980 2070 2110 2220

WIRING INLET

50

[FD15KY1]

8

B C D E F G

800 or more

55

55

125 80 80 80

70

10 10

125 80 80 80

695

9.5

50

9

NAME PLATE 19

*1 7- o/ 3.1 holes (Upward and downward)

R25JV1

560

9

115

470

H 172

1045

8

A

*1 A (Upward and downward)

477.5 72.5

8

6XP.150=900

288

100 or more

800 or more

Supprting plate

(Commercially available)

4 –HOLES FOR ANCHOR BOLTS (M8 OR M10)

420

304

DRAIN OUTLET (I. D o/ 15.9 HOSE FOR CONNECTION)

100 or more

50 or more

20

Supprting plate

(Commercially available)

50

Notes: 1Prepared holes for M4 tapping screw.

67

68


(Unit: mm)

OUTDOOR UNIT // R71FUY1, RG71AV1/AY1

OUTDOOR UNIT // RY50GAV1A, R60GV1

269

2-DRAIN OUTLET

Hole for anchor bolt 4-M12

98

37

370

84 44

396

330 350

31

HOLES FOR ANCHOR BOLTS (M8 OR M10)

30

DIME N S ION S

130 146

800

OUTDOOR AIR THERMOSTAT

300

15

584

30

540

150

880

30

4

EARTH TERMINAL (M4)

3 2

POWER INTAKE

816

6 5

5

60

LIQUID PIPE

100

GAS PIPE

84

95

14

49

90

95 195 221

75

49

24

GAS STOP VALVE

84

95

70

60

SERVICE PORT

UNIT NAME PLATE

7 6

1

UNIT NAME PLATE

LIQUID STOP VALVE

645

685

7

137

14

Name plate

67 115

102

11

61 11

40

A

Knock hole for lower piping

1 Gas pipe connection 2 Liquid pipe connection

100

50

150

H

275

MINIMUM SPACE FOR AIR PASSAGE

A

50

3 Service port (in the unit) 4 Grounding terminal

50

H H

H 1000 1000

A 300 600

391

5 Refrigerant piping intake 6 Power supply wiring intake

8

7 Control wiring intake 8 Drain outlet

OUTDOOR UNIT // R(Y)71LUV1/Y1

OUTDOOR UNIT // RY60GAV1A HOLES FOR ANCHOR BOLTS (M8 OR M10)

177 120

500

40

TERMINAL COVER

190

OUTDOOR AIR THERMOSTAT

3-DRAIN OUTLET 881

55

15

140

96 140

620 900

30

3 4 2 1 7 9 6 5

350 EARTH TERMINAL (M4)

686

770

POWER INTAKE

7 6 5

SERVICE PORT

71

8

100

70 102

A

352

19

80

52

145

13

67

16 58

110 117

120

30

223 53 95

143

54 95 19

16

40

MINIMUM SPACE FOR AIR PASSAGE

100

89 142

UNIT NAME PLATE

100

89

28

145

60

GAS STOP VALVE

329

55

55

LIQUID STOP VALVE

54 95 84 55

40

30

48 55

320

350 (345~355)

410

128

40

370

90

30

Hole for anchor bolt 4-M12

5 45

376

191

100

69

100

A

1000

350

H

1000

600

H

A H

1 2 3 4 5 6 7 8 9

Gas pipe connection Liquid pipe connection Service port Grounding terminal Refrigerant piping outlet Power supply wiring outlet Control wiring outlet Drain outlet Supplied piping

Note: In some circumstances, with certain machine types, it may not be possible to attach the supplied piping.

70


DIME N S ION S

(Unit: mm)

OUTDOOR UNIT // R100FUV1/Y1, 125FUY1 30

OUTDOOR UNIT // R(Y)125LUY1, 140LUY1 Hole for anchor bolt 4-M12

B

C

D

R(Y)125LUY1 1170

54

113

579

R(Y)140LUY1 1345

55

—

—

A 30

Hole for anchor bolt 4-M12

584

30

48 61 320

350 (345~355)

370

150

41

880

140

96 140

620 900

30

4

30

146

30

35

396

84 38

3

3

2

4

1 7

1

6

2 7

5

6

14

89

24

14

67 115

C

89 19 D

102

8

71

223

80

52

145

13

5 Refrigerant piping intake 6 Power supply wiring intake

OUTDOOR UNIT // R(Y)100LUV1/Y1

3 Service port (in the unit) 4 Grounding terminal M5 (in switch box) 5 Refrigerant piping intake

5 45

7 Control wiring intake 8 Drain outlet

8

1 Gas pipe connection 2 Liquid pipe connection

58

3 Service port(in the unit) 4 Grounding terminal

376

67

16 16

1 Gas pipe connection 2 Liquid pipe connection

Knock hole for lower piping

391

19

142

70 102 117

11

61 11

137

275

40

90

148

95 54

55

410 435 95 54

60

60 95 49

84

95 49

84

24

Name plate

5

B

5

5

568

538

6

60

7

6

A

7

84

1215

5

6 Power supply wiring intake 7 Control wiring intake

191

8 Drain pipe connection

OUTDOOR UNIT // RU06KY1

620

880

140

320

30

3

900

30

36

30

41 620

320

345

80 34

96 140

130 30

130

30

Hole for anchor bolt 4-M12

320

61

48

350 (345~355)

30

Hole for anchor bolt 4-M12

4

4

2 3

1

2

7 7

5 54

5

71

376

191

55

406

84

95

95

51

28

53 15

67

15

36

145

58

100

200

Gas pipe connection Liquid pipe connection Service port Grounding terminal Refrigerant piping outlet Power supply wiring outlet Control wiring outlet Drain outlet Supplied piping

285

1 2 3 4 5 6 7 8 9

12

12

54 58

117 70 102 45

Note: In some circumstances, with certain machine types, it may not be possible to attach the supplied piping.

14

137

67

16

5

89

53

name plate

88

13

28

52

145

16

71

376

60

223

80

70.5

8

5

54

95

84 55

6

19

19

142

6

7

435

410 95

157.5

60 89 24

89

5

6

120

6 5

7 7

55

6

1345

7

5

1

148

1170

6

223

9

Knock hole for lower pipng 41 377

8 644

1 Gas pipe connection 2 Liquid pipe connection 3 Service port (in the unit) 4 Grounding terminal M5 (in switch box) 5 Refrigerant piping intake 6 Power supply wiring intake 7 Control wiring intake 8 Drain pipe connection

72


DIME N S ION S

(Unit: mm)

OUTDOOR UNIT // RU08KY1/10KY1 A

30

Hole for anchor bolt 4-M12

1000

RU08KY1 1220

4- 15 Holls For anchor bolts

370

RU10KY1 1440

584

30

146

700

35

395

84 38

( Pitch of anchor bolts )

150

880 30

726 ( Pitch of anchor bolts )

OUTDOOR UNIT // RG140AY1/180AY1

1290

4 3 2 1 7 1345

6 5

3 A

7 6 4

76 61 11

1440

( for side-roted pipes )

95

A

4- 15mm-dia.holes ( Foundation bolt holes )

220 1000

B

R(Y)200KUY1

228 1220

R(Y)250KUY1

224 1440

( Pitch of anchor bolts )

Notes: 1. The dimensions marked by an asterisk( ) are those with the installation of the provided pipes. 2.Refer to the installation instructions when the pipes are routed through the bottom of the unit.

4- 15 Holls For anchor bolts

1290

95

726

229

1 Liquid pipe conn. 2 Gas pipe conn. 3 Earth terminal (M5) (in the el.compo. box assy) 4 Wiring intake ( side ) 5 Refrigerant piping conn. ( side ) 6 Refrigerant piping conn. ( Bottom )

( Pitch of anchor bolts )

71

97

700

RU10KUY1

1000 ( Pitch of foundation bolt holes )

( Pitch of foundation bolt holes )

C 1220

80 750

OUTDOOR UNIT // R(Y)200KUY1/250KUY1

700

B 225

54

8 Drain outlet

726

A 76

6 32

name plate

110

6 Power supply wiring intake 7 Control wiring intake

OUTDOOR UNIT // RU08KUY1/10KUY1

RU08KUY1

1280

3 Service port(in the unit) 4 Grounding terminal M5(in switch box) 5 Refrigerant piping intake

8

80

20

5

1 Gas pipe connection 2 Liquid pipe connection

5

391

202

32

690

275

40

137

165

90

165

14

90

14 67 115

2

156

144

60 49

14

102 11

70

1

52 177

90

84

95 49

84

24

name plate

4

5

95

60

538

568

70

5

Notes The dimension ( with marked ) are attached accessory pipe.

1290

( In case of side conn. )

3 C

3 70

1280

6

5

110

65

55

13

62

97

165

750

name plate

(Knock-out hole)

73

90

80

80

220

155 265

A

(for frontroted pipes)

70

150 80

2

750 1280

690

1 Liquid pipe connection port. 2 Gas pipe connection port. 3 Earth terminal (M5) (inside of control box) 4 Power cord routing hole ( side ) 5 Pipe routing hole ( side ) 6 Pipe routing hole ( Bottom )

265

1

34

54

690

1

2

110

A

135

170

(Knock-out hole)

70

4

60

123 150 230

29

32

165

150 90

B

52 177

220

156

70

5 76

4

4

4

B

70

13

97

6

name plate

( In case of front conn. )

1 Liquid pipe conn. 2 Gas pipe conn. 3 Earth terminal (M5) (in the el.compo. box assy) 4 Wiring intake ( side ) 5 Refrigerant piping conn. ( side ) 6 Refrigerant piping conn. ( Bottom )

74


DIME N S ION S

(Unit: mm)

[Space required for outdoor unit installation] (Unit: mm)

REMOTE CONTROLLER

Dimensions inside brackets [ ] indicate case where air direction adjustment guide is adjusted downward.

The values represent the case for the R(Y)71 type through R(Y)140 type. The dimensions in ( ) are for the R(Y)100 and R(Y)140 type (The unit values is mm. )

For R(Y)71LU-140LU

RECEIVER

When there is an obstruction in the overhead space

When the overhead space is open

157

1. For single unit installation

• RECEIVER DETAIL

When there is an obs truc tion on the inlet s ide

REFRIGERANT PIPING SIDE

REMOTE CONTROLLER HOLDER INSTALLATION PROCEDURE <INSTALLATION TO WALL SURFACE>

When there are obs truc tions on both s ides

•RECEIVER INSTALLATION PROCEDURE RECEIVER FAY100FA

DECORATION PANEL

1. For single unit installation

s r les

An obs truc tion in the overhead s pac e

re mo or ) 50 (100

100

When there are obs truc tions on the inlet s ide and ss or le both lateral s ides 500

• RECEIVER DETAIL LIQUID CRYSTAL REMOTE CONTROLLER (WIRELESS)

100

or m

ore 100

REMOTE CONTROLLER HOLDER

RECEIVER DETAIL 2-5x9 Slot

70

18

15 0

re

150

or

mo

100

0o 100

ore or m

rm

500

H

500

ore

or le

ore or m

or e or m 50 (100)

2. For series installation (more than two units)

ss

1. For single unit installation

2. For series installation (more than two units) When there are obs truc tions on the inlet s ide and both lateral s ides

0o

r les

100

or m

ore rm 0o ) 20 (300

ore

0o

rm

An obs truc tion in the overhead s pac e

L

s

An obs truc tion in the overhead s pac e rm ore

49

500

2. For series installation (more than two units)

H

ore or m

100

ore rm 0o

or e or m 200 (300)

ss

50 0

or le

An obs truc tion in the overhead s pac e

ore 2 00

• RECEIVER DETAIL

(Ceiling opening)

150

re

o 500

Switch box

L

When there is an obstruction in the overhead space mo

1. For single unit installation

L

or

5 00

ore or m

ore or m

An obs truc tion in the overhead s pac e

ore

1

ore

20 0

0.5 35

rm

2. For series installation (more than two units) When there are obs truc tions on both s ides

RECEIVER

(Ceiling opening)

120

72 83.5 106

The Front

o 00

When the overhead space is open 2. For series installation (more than two units)

1000 or more

• RECEIVER DETAIL

CEILING SUSPENDED TYPE •RECEIVER INSTALLATION PROCEDURE

or m

When the obstruction on the outlet side is higher than the unit itself (There is no limit to the height of the obstruction on the outlet side.)

H

17.5

o 500

Pattern 1

When the overhead space is open

1. For single unit installation

When there is an obs truc tion only on the inlet s ide

When there are obstructions on both the inlet and outlet sides

H

DRAIN PIPING SIDE

62

When there is an obstruction on the outlet side

When there is an obstruction on the inlet side

L

TRANSMITTING PART

WALL MOUNTED TYPE •RECEIVER INSTALLATION PROCEDURE FAY71L RECEIVER

1000 or more

CEILING MOUNTED CASSETTE TYPE •RECEIVER INSTALLATION PROCEDURE

1000 or more

REMOTE CONTROLLER DIMENSIONS

1000 or more

1000 or more

Wireless type

or

mo

ore rm 0o ) 20 (300

re

(field Supplied parts)

100

0o

ore rm

More than 90 (Srevice space)

Service space for ceiling installation Note : Do not install more than 3 receivers in the vicinity of one another. With 4 or more units, there is always the possibility of malfunction

For R(Y)200KU / 250KU In case of single installation

In case of parallel installation

In case of set installation

Wired type •REMOTE CONTROLLER DIMENSIONS

Pattern 1

•REMOTE CONTROLLER INSTALLATION PROCEDURE A EXPOSED BODY, EXPOSED CORD B EXPOSED BODY, EMBEDDED CORD 17

CONDUIT

84

120

10 or more

117

38

Pattern 1 300 or more

42

STAPLE

Pattern 1

300 or more

10 or more

FRONT SIDE 500 or more

10 or more

20 or more

FRONT SIDE 500 or more

300 or more

10 or more 20 or more

10 or more

20 or more

FRONT SIDE

FRONT SIDE

10 or more 10 or more

600 or more

0~5

500 or more

10 or more 20 or more 900 or more

17

18

CORD OUTLET HOLE

23 28

Pattern 2 17

CONTROL BOX

C EXPOSED BODY, EMBEDDED CODE 46

100 or more

NOTE) 1. REMOTE CONTROLLER CORD AND STAPLE ARE NOT ATTACHED. THEY ARE FIELD SUPPLIED PARTS. 50 or more

THROUGH HOLE (fl12~fl16)

( DISTANCE BETWEEN REMOTE CONTROLLER AND CONTROL BOX )

SIZE

0.75~1.25 mm2

TOTAL LENGTH

500 m

50 or more

100 or more

FRONT SIDE 500 or more

The height of obstacle is free

Pattern 3

10 or more

Pattern 2

300 or more

200 or more

124

FRONT SIDE

500 or more

The height of obstacle is free 50 or more

400 or more

FRONT SIDE

100 or more

FRONT SIDE 500 or more

400 or more

KRC47-3A 136

18

FRONT SIDE

10 or more

FRONT SIDE 500 or more

20 or more

100 or more

100 or more

Pattern 3 300 or more

110

FRONT SIDE 500 or more

50 or more

* Countries requiring EMC: Shield wire (insulated thickness: 1 mm or more)

KRC47-1A

25

FRONT SIDE 500 or more

50 or more

(INSULATED THICKNESS: 1 mm OR MORE)

•REMOTE CONTROLLER

KRC47-2A/ KRC47-4A

20 or more

VINYL CORD WITH SHEATH OR CABLE

TYPE 17

10 or more

100 or more

10 or more

10 or more

SPECIFICATIONS OF CORD

•DIGITAL REMOTE CONTROLLER

Pattern 2

50 or more

100 or more

FRONT SIDE 500 or more

50 or more 50 or more

50 or more

100 or more

50 or more

100 or more

600 or more

50 or more 50 or more

FRONT SIDE 500 or more

136 32

124

32

Front side 1500 mm Suction side 500 mm Side No (imitation)

81

81

58

19

Notes: 1 Obstacies height of (Pattern 1) and (Pattern 2) shall be as follows: h2

120

14

61

75

If the number of units is more than that shown in this manual. take short circuit into account.

35.50

36

92

85

4

For the service space for front side. take the service space required for field piping into account.

SUCTION SIDE

h1

FRONT SIDE

500 mm

For the service space. if the obstacle of height exceeds the above mentioned dimensions. half of the exceeded dimensions shall be added to the standard service space. When installing a unit. choose the most suitable one from this manual depending on actual conditions such as walking passage and ventilation.

3

1500 mm

2

85

76


MEMO

77

78