Double deflection air grille

Page 1

Grilles & Registers Contents • GV Double Deflection Supply Air Grille ....................2 • GH Double Deflection Supply Air Grille ....................4 • GA Supply Air Linear Bar Grille ................................9 • RA Linear Bar Grille ................................................13 • SLLS Linear Ceiling Diffuser ..................................19 • Accessories ............................................................23

GA Supply Air Linear Bar Grille

GH Double Deflection Supply Air Grille

RA Linear Bar Grille

SLLS Linear Ceiling Diffuser

G1 Opposed Blade Damper

GV Double Deflection Supply Air Grille

G2 Volume Extractor


GV Double Deflection Supply Air Grille • Materials:

GV Double Deflection Supply Air Grille

• GV-T Frame 1.0mm, Blade 0.35mm SPGC Galvanized Steel. • GV-S Frame 0.7mm, Blade 0.3mm Stainless Steel SUS. 304. • GV-A Extruded Aluminium A6063.

• Surface Finish:

• GV-T Baked White Powder Coat as standard. • GV-S Stainless Steel Original Colour. • GV-A Baked White Powder Coat or Natural Anodized.

• Accessories:

• G1 Opposed Blade Damper. • G2 Volume Extractor. • Model GV is made up of two sets of individually adjustable air foil blades with the vertical set in front & the horizontal set behind. • The grille will come in more sections for blade length that is more than 600mm. • Non-standard sizes are available.

Construction Illustration

Physcal Dimension Unit:mm

Materials

GV-T

SPGC Steel

1.0

0.35

GV-S

Stainless Steel 0.7 SUS. 304

0.3

GV-A

2

Thickness Standard Size A B D W X H Duct Size Wall Size Face Size Frame Blade

Model

Extruded Aluminium A6063

1.2

4.0

350 X 150 400 X 150 450 X 150 500 X 150 500 X 200

Order Key GV-T + G1 - 350X150

W+10 H+10

W+20 H+20

W+60 H+60

W

H

Accessories Materials Model


GV Supply Air Grille & Accessories • GV+G1 Opposed Blade Damper.

GV+G1 Opposed Blade Damper

• Materials:

• G1-T SPGC Galvanized Steel.

• Surface Finish:

• G1-T Baked Black as standard.

• The G1 opposed blade damper is gear operated & can be set at fully open, half open & fully close. • G1 maximum dimension is 500mm x 500mm. Damper size bigger than this will come in sections.

• GV & GV+G1 Physical Dimension Model

Depth

GV

48

GV+G1

T A

123

Unit:mm

Neck A B D Size Duct Size Wall Size Face Size WXH

W+10 H+10

W+20 H+20

W+60 H+60

WXH

W+15 H+15

W+20 H+20

W+60 H+60

• GV+G2 Volume Extractor.

GV+G2 Volume Extractor

• G2 volume extractor helps in balancing by guiding a regulated amount of air for supply air grilles from the main duct & enable even air distribution over the entire surface of grille. • Maximum angle for G2 is 35˚ - 40˚. • Materials for G2 is 1.0mm SPGC galvanized steel & surface finish is baked black.

• Uneven air distribution

• Even air distribution with G2

3


GH Double Deflection Supply Air Grille • Materials:

GH Double Deflection Supply Air Grille

• GH-T Frame 1.0mm, Blade 0.35mm SPGC Galvanized Steel. • GH-S Frame 0.7mm, Blade 0.3mm Stainless Steel SUS. 304. • GH-A Extruded Aluminium A6063.

• Surface Finish:

• GH-T Baked White Powder Coat as standard. • GH-S Stainless Steel Original Colour. • GH-A Baked White Powder Coat or Natural Anodized.

• Accessories:

• G1 Opposed Blade Damper. • G2 Volume Extractor. • Model GH is made up of two sets of individually adjustable air foil blades with the horizontal set in front & the vertical set behind. • The grille will come in more sections for blade length that is more than 600mm. • Non-standard sizes are available.

Construction Illustration

Physcal Dimension Unit:mm

Materials

GH-T

SPGC Steel

1.0

0.35

GH-S

Stainless Steel 0.7 SUS. 304

0.3

GH-A

4

Thickness Standard Size A B D W X H Duct Size Wall Size Face Size Frame Blade

Model

Extruded Aluminium A6063

1.2

4.0

350 X 150 400 X 150 450 X 150 500 X 150 500 X 200

Order Key GH-T + G1 - 350X150

W+10 H+10

W+20 H+20

W+60 H+60

W H Accessories Materials Model


GH Supply Air Grille & Accessories • GH+G1 Opposed Blade Damper.

GH+G1 Opposed Blade Damper

• Materials:

• G1-T SPGC Galvanized Steel.

• Surface Finish:

• G1-T Baked Black as standard. • The G1 opposed blade damper is gear operated & can be set at fully open, half open & fully close. • G1 maximum dimension is 500mm x 500mm. Damper size bigger than this will come in sections.

• GH & GH+G1 Physical Dimension Model

Depth

GH

48

GH+G1

T A

123

Unit:mm

Neck A B D Size Duct Size Wall Size Face Size WXH

W+10 H+10

W+20 H+20

W+60 H+60

WXH

W+15 H+15

W+20 H+20

W+60 H+60

• GH+G2 Volume Extractor.

GH+G2 Volume Extractor

• G2 volume extractor helps in balancing by guiding a regulated amount of air for supply air grilles from the main duct & enable even air distribution over the entire surface of grille. • Maximum angle for G2 is 35˚ - 40˚. • Materials for G2 is 1.0mm SPGC galvanized steel & surface finish is baked black.

•Uneven air distribution

• Even air distribution with G2

5


Performance Data for GV & GH (1) Performance Data for GV & GH (1)

Neck Area m2 Effective Area m2

Neck Size mm

Vel. M/S

2

2.5

3

3.5

4

4.5

5

Total

0.8

1.2

1.7

2.2

3.0

3.8

4.6

Press

22˚

0.9

1.4

1.9

2.5

3.5

4.2

5.2

(mmAq) 45˚

1.3

2.1

2.8

3.8

5.0

6.4

7.8

CMH 0.01 0.005

0.015 0.009

0.02 0.012

0.025 0.015

100 X 100

150 X 100

150 X 150 200 X 100

250 X 100

Throw (M)

72

90

108

126

144

162

180

1.8-3.5

2.4-4.2

3.0-4.8

3.7-5.2

3.8-5.7

4.2-6.0

4.5-6.4

22˚

1.5-3.0

1.8-3.2

2.4-3.8

3.0-4.2

3.0-4.4

3.3-4.8

3.6-5.1

45˚

1.0-1.8

1.2-2.0

1.5-2.4

1.8-2.7

2.0-2.6

2.1-3.0

2.2-3.2

NC

-

-

-

-

-

23

25

CMH

108

135

162

189

216

243

270

2.2-3.9

2.5-4.5

3.3-5.2

3.9-5.7

4.5-6.1

4.7-6.6

5.0-6.9

22˚

1.8-3.1

1.9-3.6

2.8-4.2

3.1-4.6

3.6-4.8

3.8-5.3

4.0-5.6

45˚

Throw (M)

1.0-2.1

1.2-2.4

1.5-2.7

2.1-3.0

2.1-3.1

2.3-3.3

2.5-3.4

NC

-

-

-

-

21

25

27

CMH

144

180

216

252

288

324

360

2.8-4.8

3.4-5.5

4.3-6.2

4.5-6.7

4.9-7.0

5.2-7.6

5.5-8.0

22˚

2.2-4.0

2.8-4.3

3.4-4.9

3.7-5.2

4.0-5.5

4.2-6.0

4.5-6.5

45˚

1.3-2.6

1.6-2.8

1.9-3.0

2.2-3.1

2.5-3.4

2.8-3.5

3.0-3.7

NC

-

-

-

21

25

27

29

CMH

180

225

170

315

360

405

450

Throw (M)

Throw (M)

3.2-5.7

3.9-6.4

4.8-6.8

5.0-7.2

5.7-7.8

6.2-8.4

6.4-8.8

22˚

2.6-4.5

3.0-5.2

3.8-5.4

4.2-5.7

4.5-6.3

4.8-6.7

5.1-7.0

45˚

1.5-2.7

2.1-3.0

2.4-3.3

2.7-3.6

2.9-3.9

3.1-4.2

3.3-4.6

-

-

-

22

26

28

30

NC CMH 0.03 0.018

0.035 0.021

0.04 0.025

0.045 0.028

200 X 150 300 X 100

250 X 150 350 X 100

200 X 200 400 X 100

300 X 150 450 X 100

Throw (M)

216

270

324

378

432

486

540

3.5-6.2

4.3-6.9

5.5-7.7

5.8-8.3

6.5-8.9

6.8-9.4

7.1-9.8

22˚

2.8-4.9

3.4-5.4

4.3-6.2

4.6-6.5

5.2-7.1

5.3-7.4

5.5-7.7

45˚

1.8-3.1

2.2-3.3

2.5-3.7

2.8-4.0

3.1-4.3

3.2-4.6

3.4-4.9

NC

-

-

-

22

26

28

30

CMH

252

315

378

441

504

567

630

3.8-6.8

4.8-7.5

5.6-8.3

6.5-8.9

6.8-9.5

7.2-10.0

7.7-10.6

22˚

3.0-5.2

3.8-5.7

4.5-6.5

5.2-7.1

5.3-7.7

5.7-8.1

6.2-8.6

45˚

Throw (M)

1.8-3.2

2.3-3.6

2.8-4.0

3.2-4.3

3.5-4.6

3.7-4.9

3.9-5.2

NC

-

-

-

23

27

29

32

CMH

288

360

432

504

576

648

720

4.0-7.2

5.1-7.9

6.2-8.8

6.7-9.4

7.3-10.1

7.6-10.8

7.9-11.3

22˚

3.2-5.6

4.1-6.3

4.9-7.0

5.4-7.6

5.7-8.2

6.2-8.7

6.4-9.0

45˚

2.0-3.4

2.7-3.9

3.0-4.3

3.4-4.6

3.7-5.0

3.9-5.3

4.1-5.6

NC

-

-

-

24

28

30

33

CMH

324

405

486

567

648

729

810

Throw (M)

Throw (M) NC

4.2-7.7

5.3-8.4

6.8-9.3

7.1-9.9

7.8-10.8

8.1-11.4

8.4-12.0

22˚

3.5-6.2

4.4-6.8

5.4-7.5

5.6-8.0

6.2-8.7

6.5-9.1

6.8-9.5

45˚

2.3-3.7

2.9-4.3

3.3-4.6

3.5-4.9

3.9-5.3

4.1-5.7

4.4-6.2

-

-

21

25

28

31

35

• Throw is based on terminal velocities of 0.5 m/s - 0.25 m/s respectively. • NC value is based on a room absorption of 10 dB, re 10-12 watts. • Dash (-) in space indicates NC value less than 20.

6

• With G1 damper, the pressure loss is 1.136P, and add 2 for NC value. • The performance data is tested based on A.D.C. standard.


Performance Data for GV & GH (2) Neck Area m2 Effective Area m2

Neck Size mm

Vel. M/S

2

2.5

3

3.5

4

4.5

5

Total

0.8

1.2

1.7

2.2

3.0

3.8

4.6

Press

22˚

0.9

1.4

1.9

2.5

3.5

4.2

5.2

(mmAq) 45˚

1.3

2.1

2.8

3.8

5.0

6.4

7.8

CMH 0.05 0.032

0.06 0.039

0.07 0.05

0.08 0.053

250 X 200 350 X 150 500 X 100 550 X 100

250 X 250 300 X 200 400 X 150 600 X 100 650 X 100 300 X 250 350 X 200 450 X 150 500 X 150 700 X 100 750 X 100 350 X 250 400 X 200 550 X 150 800 X 100

Throw (M)

360

450

540

630

720

810

900

4.5-7.9

5.8-8.8

6.9-9.7

7.6-10.6

7.9-11.3

8.5-11.9

9.2-12.5

22˚

3.7-6.4

4.6-7.0

5.5-7.8

6.1-8.6

6.4-9.1

6.8-9.5

7.4-10.1

45˚

2.5-3.9

3.0-4.6

3.4-4.9

3.7-5.2

4.0-5.5

4.3-5.9

4.6-6.5

NC

-

-

21

26

29

32

36

CMH

432

540

648

756

864

972

1080

4.9-8.6

6.3-9.6

7.4-10.5

8.3-11.4

8.9-12.2

9.4-13.1

9.9-14.0

22˚

4.1-6.8

4.9-7.8

5.9-8.4

6.7-9.3

7.1-9.8

7.6-10.4

8.1-11.2

45˚

Throw (M)

2.6-4.2

3.2-4.9

3.8-5.2

4.1-5.8

4.4-6.2

4.7-6.6

5.0-6.9

NC

-

-

21

26

29

32

37

CMH

504

630

756

882

1008

1134

1260

5.4-9.6

6.9-10.7

8.3-11.7

9.1-12.5

9.6-13.5 10.2-14.2 10.8-14.8

22˚

4.5-7.6

5.5-8.6

6.6-9.4

7.3-10.0

7.8-10.8

8.2-11.4

8.5-12.0

45˚

2.8-4.7

3.5-5.2

4.2-5.8

4.4-6.4

4.8-6.8

5.2-7.2

5.4-7.5

NC

-

-

21

26

30

33

38

CMH

576

720

864

1008

1152

1296

1440

Throw (M)

Throw (M)

5.9-10.1

7.3-11.3

8.9-12.4

9.6-13.5 10.4-14.4 11.0-15.2 11.5-16.0

22˚

4.7-8.0

5.7-9.2

7.0-9.9

7.8-10.7

8.3-11.5

8.7-12.2

9.2-12.8

45˚

3.0-5.0

3.8-5.5

4.4-6.2

4.8-6.8

5.2-7.2

5.6-7.7

5.9-8.0

-

-

22

27

31

34

39

972

1134

1296

1458

1620

NC

0.09 0.061

0.1 0.067

0.12 0.082

0.13 0.087

300 X 300 450 X 200 600 X 150 850 X 100 900 X 100 350 X 300 400 X 250 500 X 200 650 X 150 700 X 150 1000 X 100 400 X 300 450 X 250 550 X 200 600 X 200 750 X 150 800 X 150 450 X 300 500 X 250 550 X 250 650 X 200 850 X 150 900 X 150

CMH Throw (M)

648

810

6.2-10.7

7.8-12.0

9.4-13.2 10.2-14.2 11.0-15.2 11.7-16.2 12.2-17.0

22˚

5.0-8.6

6.1-9.6

7.5-10.5

8.2-11.3

8.8-12.2

9.3-12.9

9.8-13.6

45˚

3.2-5.3

4.0-5.9

4.7-6.6

5.1-7.1

5.5-7.6

5.8-8.0

6.2-8.2

NC

-

-

23

27

32

35

39

CMH

720

900

1080

1260

1440

1620

1800

6.6-11.3

8.3-2.7

9.9-13.9 10.9-14.9 11.5-16.0 12.2-16.9 12.8-17.9

22˚

5.2-9.1

6.5-10.1

8.0-11.2

8.6-12.0

9.2-12.8

9.8-13.6 10.3-14.4

45˚

Throw (M)

3.4-5.6

4.3-6.4

5.0-7.0

5.4-7.5

5.7-8.0

6.1-8.2

6.5-8.7

NC

-

-

23

28

32

35

40

CMH

964

1080

1296

1512

1728

1944

2160

7.1-12.5

9.0-13.9 11.0-15.1 11.8-16.5 12.6-17.5 13.4-18.5 14.1-19.5

22˚

5.6-10.0

7.0-11.2

8.8-12.1

9.4-13.3 10.0-14.0 10.7-14.8 11.3-15.6

45˚

3.6-6.3

4.5-6.9

5.4-7.5

5.9-8.2

6.3-8.6

6.6-9.3

6.9-9.8

NC

-

-

24

29

33

36

40

CMH

936

1170

1404

1638

1872

2106

2640

Throw (M)

Throw (M) NC

7.5-12.9

9.3-14.5 11.5-15.7 12.3-17.2 13.3-18.2 14.0-19.2 14.8-20.5

22˚

6.0-10.5

7.5-11.8

9.3-12.7 10.0-13.9 10.5-14.5 11.0-15.1 11.8-16.0

45˚

3.9-6.7

4.8-7.2

5.8-7.8

6.2-8.5

6.5-9.0

6.7-9.6

7.2-10.2

-

-

24

29

33

36

40

• Throw is based on terminal velocities of 0.5 m/s - 0.25 m/s

respectively. • NC value is based on a room absorption of 10 dB, re 10-12 watts. • Dash (-) in space indicates NC value less than 20.

Performance Data for GV & GH (2)

• With G1 damper, the pressure loss is 1.136P, and add 2 for NC value. • The performance data is tested based on A.D.C. standard.

7


Performance Data for GV & GH (3) Performance Data for GV & GH (3)

Neck Area m2 Effective Area m2

0.15 0.1

0.16 0.11

0.18 0.13

0.2 0.14

Neck Size mm

500 X 300 600 X 250 700 X 200 750 X 200 1000 X 150

550 X 300 650 X 250 800 X 200 850 X 200

600 X 300 700 X 250 750 X 250 900 X 200

650 X 300 700 X 300 800 X 250 1000 X 200

Vel. M/S

2

2.5

3

3.5

4

4.5

5

Total

0.8

1.2

1.7

2.2

3.0

3.8

4.6

Press

22˚

0.9

1.4

1.9

2.5

3.5

4.2

5.2

(mmAq) 45˚

1.3

2.1

2.8

3.8

5.0

6.4

7.8

1350

1620

1890

2160

2430

2700

CMH Throw (M)

1080 0˚

8.0-14.0

9.7-15.5 11.8-16.9 13.0-18.3 14.0-19.5 14.8-20.8 15.5-21.8

22˚

6.5-11.3

7.8-12.4

9.4-13.6 10.2-14.6 11.2-15.5 11.9-16.5 12.4-17.6

45˚

4.0-7.0

4.9-7.5

6.1-8.4

0.16

0.25 0.17

0.27 0.19

0.3 0.21

850 X 300 1000 X 250

900 X 300

1000 X 300

7.8-10.8

-

-

24

29

33

37

40

1152

1440

1728

2016

2304

2592

2880

Throw (M)

8.3-14.5 10.2-16.0 12.4-17.5 13.6-19.0 14.6-20.2 15.4-21.4 16.2-22.7

22˚

6.6-11.5

8.2-12.8

9.7-14.0 10.6-15.1 11.6-16.1 12.3-17.0 13.0-18.1

45˚

4.1-7.2

1.2-2.4

6.4-8.6

6.8-9.4

7.3-10.1

7.7-10.7

8.2-11.2

NC

-

-

24

30

34

37

40

CMH

1296

1620

1944

2268

2592

2916

3240

8.7-15.2 10.9-16.8 12.8-18.5 14.3-19.9 15.4-21.3 16.4-23.0 17.1-24.0

22˚

7.0-12.2

8.7-13.5 10.2-14.7 11.3-15.8 12.3-16.9 13.0-18.5 13.7-19.3

45˚

4.3-7.6

5.4-8.3

6.5-9.3

7.3-9.9

7.6-10.7

8.2-11.5

8.5-11.9

NC

-

21

25

30

35

38

41

CMH

1440

1800

2160

2520

2880

3240

3600

Throw (M)

Throw (M)

Throw (M)

9.2-16.0 11.4-17.9 13.6-19.6 14.9-21.0 16.2-22.6 17.1-24.0 18.0-25.2

22˚

7.5-12.8

9.1-14.3 10.8-15.5 12.0-16.7 13.0-18.0 13.7-19.3 14.3-20.1

45˚

4.5-7.9

5.7-8.7

6.8-9.8

7.5-10.5

8.0-11.3

8.5-11.9

8.9-12.7

-

21

25

30

35

38

41

1620

2025

2430

2835

3240

3645

4050

9.8-16.8 12.0-19.0 14.5-20.7 16.0-22.3 17.1-24.0 18.1-25.5 19.1-26.8

22˚

7.9-13.5

9.6-15.2 11.4-16.4 12.7-17.8 13.8-19.2 14.7-20.3 15.6-21.2

45˚

4.8-8.2

6.0-9.4

7.2-10.3

7.9-11.0

8.4-11.9

9.0-12.9

9.5-13.5

NC

-

22

26

31

36

39

41

CMH

1800

2250

2700

3150

3600

4050

4500

Throw (M)

10.2-17.8 12.6-19.7 15.0-21.6 17.0-23.5 17.9-25.2 19.0-26.7 20.1-28.2

22˚

8.2-14.3 10.0-15.9 11.8-17.2 13.5-18.7 14.4-20.1 15.3-21.3 16.1-22.4

45˚

5.0-8.7

6.2-9.7

7.4-10.7

8.4-11.6

8.8-12.6

NC

-

22

27

32

36

39

42

CMH

1944

2430

2915

3402

3888

4374

4860

9.5-13.5 10.0-14.2

10.5-18.5 13.1-20.7 15.6-22.7 17.5-24.5 18.7-26.3 19.8-27.8 21.0-29.2

22˚

8.5-14.7 10.5-16.5 12.4-18.0 14.0-19.5 15.0-21.0 15.9-22.2 16.8-23.3

45˚

5.3-9.2

6.5-10.2

7.7-11.3

8.7-12.2

9.3-13.0

NC

-

22

27

32

36

39

42

CMH

2160

2700

3240

3780

4320

4860

5400

Throw (M)

Throw (M) NC

9.9-13.9 10.5-14.6

11.0-19.5 13.7-21.6 16.3-24.1 18.5-26.0 19.6-27.7 20.9-29.3 22.2-31.0

22˚

8.9-15.5 11.0-17.3 13.0-19.2 14.9-20.7 15.8-22.2 16.8-23.4 17.8-24.6

45˚

5.5-9.7

6.7-10.7

8.0-12.0

9.3-12.9

-

23

28

32

• Throw is based on terminal velocities of 0.5 m/s - 0.25 m/s respectively. • NC value is based on a room absorption of 10 dB, re 10-12 watts. • Dash (-) in space indicates NC value less than 20.

8

7.4-10.5

NC

CMH 0.225

6.9-9.7

CMH

NC 750 X 300 800 X 300 850 X 300 900 X 250

6.7-9.1

9.9-13.8 10.5-14.6 11.0-15.4 37

40

43

• With G1 damper, the pressure loss is 1.136P, and add 2 for NC value. • The performance data is tested based on A.D.C. standard.


GA Supply Air Linear Bar Grille • Materials:

GA Supply Air Linear Bar Grille

• GA-A Extruded Aluminium A6063.

• Surface Finish:

• Baked White Powder Coat as standard or Natural Anodized.

• Accessories: •

• • •

• G1 Opposed Blade Damper. • G2 Volume Extractor. Model GA is made up of two sets of air foil blades. The horizontal set is in front & the vertical set is behind. The horizontal set of air blades is fixed & the vertical set is adjustable. The grille will come in more sections for blade length that is more than 600mm. Non-standard sizes are available.

Construction Illustration

Model

GA-A

Materials

Extruded Aluminium A6063

Thickness Standard Size D A B Face Size W X H Duct Size Wall Size Frame Blade

1.2

4.0

400 X 150 450 X 150 500 X 150 500 X 200

Order Key

Physcal Dimension

GA-A+G1-400X150 Unit:mm W+10 H+10

W+15 H+15

W+48 H+48

W H Accessories Materials Model

9


GA Linear Bar Grille & Accessories • GA+G1 Opposed Blade Damper.

GA+G1 Opposed Blade Damper

• Materials:

• G1-T SPGC Galvanized Steel.

• Surface Finish:

• G1-T Baked Black as standard. • The G1 opposed blade damper is gear operated & can be set at fully open, half open & fully close. • G1 maximum dimension is 500mm x 500mm. Damper size bigger than this will come in sections.

• GH & GH+G1 Physical Dimension Model

Depth

GA

52

GA+G1

A

127

WXH

W+10 H+10

W+15 H+15

W+48 H+48

WXH

W+15 H+15

W+15 H+15

W+48 H+48

• GA+G2 Volume Extractor.

GA+G2 Volume Extractor

• G2 volume extractor helps in balancing by guiding a regulated amount of air for supply air grilles from the main duct & enable even air distribution over the entire surface of grille. • Maximum angle for G2 is 35˚ - 40˚. • Materials for G2 is 1.0mm SPGC galvanized steel & surface finish is baked black.

• Uneven air distribution

10

T

Unit:mm

Neck A B D Size Duct Size Wall Size Face Size

• Even air distribution with G2


Performance Data for GA (1) Neck Area m2

0.045

0.06

0.075

0.09

0.1

0.12

0.135

0.15

0.165

Neck Size mm

Vel. M/S

2

2.5

3

3.5

4

4.5

5

Tot. Press (mmAq)

0.9

1.2

1.8

2.3

3.0

4.0

4.8

CMH

324

405

486

567

648

729

810

2.3-4.1

2.9-4.5

3.6-5.0

3.9-5.6

4.2-6.1

4.6-6.6

5.0-7.1

4.3-7.5

5.2-8.3

6.5-8.8

7.0-9.4

7.3-10.6

8.1-11.2

8.3-11.8

NC

-

-

21

25

27

32

37

CMH

432

540

648

756

864

972

1080

2.5-4.6

3.4-5.2

4.1-6.1

4.7-6.7

5.3-7.4

5.7-8.0

6.1-8.3

4.6-8.5

6.3-9.5

7.5-10.6

8.4-11.3

9.0-12.4

9.5-13.0 10.0-13.6

NC

-

-

21

26

29

32

37

CMH

540

675

810

945

1080

1215

1350

2.8-5.3

3.9-6.3

4.9-7.1

5.5-7.7

5.8-8.3

6.3-8.9

6.9-9.5

5.3-9.8

7.1-11.2

8.4-12.0

9.2-12.6

9.7-13.6 10.3-14.4 10.9-15.2

NC

-

-

22

26

31

33

38

CMH

648

810

972

1134

1296

1459

1620

4.6-7.0

5.5-7.8

6.1-8.4

6.5-9.5

7.1-10.3

7.6-11.0

7.6-11.9

9.2-12.7 10.0-13.8 10.6-15.0 11.5-16.0 12.0-16.9

450 X 100 Throw Ceiling 300 X 150 (M) Wall

400 X 150 Throw Ceiling 300 X 200 (M) Wall

500 X 150 Throw Ceiling 300 X 250 (M) Wall

300 X 300 Throw Ceiling 3.5-6.2 450 X 200 (M) Wall 6.1-10.5 NC

-

-

22

27

31

35

38

CMH

720

900

1080

1260

1440

1620

1800

5.1-7.6

6.2-8.6

6.9-9.4

7.6-10.2

8.1-11.1

8.8-12.0

500 X 200 Throw Ceiling 4.0-6.8 400 X 250 (M) Wall 6.8-11.4

8.2-12.5 10.0-14.0 10.8-14.9 11.8-15.8 12.3-16.9 13.0-18.0

NC

-

-

23

28

31

36

39

CMH

864

1080

1296

1512

1728

1944

2160

5.3-8.4

6.5-9.5

7.4-10.4

8.1-11.3

8.8-12.2

9.3-12.9

400 X 300 Throw Ceiling 4.3-7.4 600 X 200 (M) Wall 7.2-12.4

9.0-13.8 10.9-15.1 11.7-16.5 12.6-17.6 13.5-18.6 14.0-19.5

NC

-

-

24

29

33

36

39

CMH

972

1215

1458

1700

1944

2187

2430

5.6-8.9

6.7-10.2

7.7-11.2

8.6-12.2

9.3-13.0

9.8-13.8

450 X 300 Throw Ceiling 4.5-7.9 550 X 250 (M) Wall 7.5-13.2

9.4-14.7 11.3-16.0 12.5-17.4 13.4-18.5 14.2-19.7 14.8-20.7

NC

-

-

24

30

34

36

39

CMH

1080

1350

1620

1890

2160

2430

2700

6.1-9.5

7.3-10.9

8.3-11.6

9.1-12.8

500 X 300 Throw Ceiling 4.8-8.6 600 X 250 (M) Wall 7.7-13.8

Performance Data for GA (1)

9.8-13.8 10.5-14.8

9.5-15.4 11.7-17.0 13.0-18.2 13.8-19.3 14.6-20.7 15.3-21.6

NC

-

-

25

30

34

37

39

CMH

1188

1485

1782

2079

2376

2673

2970

550 X 300 Throw Ceiling 5.1-9.1 6.4-10.1 7.7-11.4 8.7-12.4 9.7-13.5 10.4-14.6 11.1-15.7 650 X 250 (M) Wall 8.2-14.6 10.2-16.1 12.4-17.6 13.5-19.0 14.6-20.4 15.1-21.5 16.2-22.8 NC

-

• Throw is based on terminal velocities of 0.5 m/s - 0.25 m/s respectively. • NC value is based on a room absorption of 10 dB, re 10-12 watts. • Dash (-) in space indicates NC value less than 20.

21

25

31

35

37

39

• With G1 damper, the pressure loss is 1.136P, and add 2 for NC value. • The performance data is tested based on A.D.C. standard.

11


Performance Data for GA (2) Performance Data for GA (2)

Neck Area m2

0.18

0.195

0.21

0.225

0.24

0.255

0.27

0.3

0.32

Neck Size mm

Vel. M/S

2

2.5

3

3.5

4

4.5

5

Tot. Press (mmAq)

0.9

1.2

1.8

2.3

3.0

4.0

4.8

CMH

1296

1620

1944

2268

2592

2915

3240

600 X 300 Throw Ceiling 5.3-9.5 6.5-10.8 7.9-12.1 9.0-13.2 10.2-14.3 11.0-15.6 12.0-16.9 700 X 250 (M) Wall 8.5-15.2 10.7-16.9 12.7-18.3 14.2-19.8 15.2-21.3 16.2-22.5 16.9-23.8 NC

-

21

25

31

35

38

40

CMH

1405

1755

2105

2457

2808

3160

3510

650 X 300 Throw Ceiling 5.8-10.1 7.3-11.4 8.7-12.6 9.7-13.9 10.8-15.1 11.7-16.4 12.6-17.6 550 X 350 (M) Wall 9.1-15.8 11.2-17.2 13.2-19.0 14.7-20.7 15.8-22.1 16.8-23.5 17.7-24.9 NC

-

21

25

31

35

38

40

CMH

1512

1890

2268

2646

3024

3402

3780

700 X 300 Throw Ceiling 6.1-10.6 7.8-11.8 9.3-13.1 10.3-14.5 11.3-15.9 12.3-17.2 13.3-18.5 1000 X 200 (M) Wall 9.6-16.5 11.6-18.1 14.0-19.7 15.3-21.5 16.6-23.3 17.5-24.5 18.7-26.0 NC

-

21

26

31

35

38

41

CMH

1620

2025

2430

2835

3240

3645

4050

750 X 300 Throw Ceiling 6.5-11.1 8.3-12.5 9.6-13.8 11.0-15.5 12.2-16.9 13.3-18.2 14.2-19.8 900 X 250 (M) Wall 10.0-17.1 12.1-18.6 14.5-20.5 16.0-22.4 17.2-24.0 18.0-25.6 19.3-26.9

850 X 300

850 X 300

900 X 300

1000 X 300

800 X 400

NC

-

22

26

31

36

39

41

CMH

1728

2160

2592

3024

3456

3888

4320

Throw Ceiling 6.7-11.4 (M)

Wall

10.2-17.5 12.5-19.5 14.8-21.1 16.6-23.1 17.6-24.7 18.6-26.3 19.9-27.7

NC

-

22

26

32

36

39

41

CMH

1836

2295

2754

3213

3672

4130

4590

Throw Ceiling 6.9-11.8 (M)

Wall

8.6-13.4 10.4-15.0 11.6-16.6 12.9-18.2 14.3-20.0 15.1-21.1

10.4-18.0 12.9-20.0 15.2-21.9 17.3-23.8 18.2-25.5 19.3-27.0 20.5-28.5

NC

-

22

27

32

36

39

41

CMH

1944

2430

2915

3402

3888

4374

4860

Throw Ceiling 7.0-12.3 (M)

Wall

8.9-14.0 10.7-15.7 21.1-17.4 13.3-19.1 14.7-20.6 15.5-21.7

10.5-18.4 13.0-20.6 15.6-22.6 17.5-24.5 18.7-26.5 19.6-27.9 21.0-29.3

NC

-

22

27

32

36

39

42

CMH

2160

2700

3240

3780

4320

4860

5400

Throw Ceiling 7.3-12.9 (M)

Wall

9.3-14.8 11.3-16.9 13.0-18.4 14.2-20.2 15.5-21.7 16.6-23.0

11.0-19.5 13.6-21.7 16.4-24.0 18.6-26.0 19.9-27.2 21.0-29.5 22.5-31.1

NC

-

23

28

32

37

40

43

CMH

2304

2880

3456

4032

4608

5184

5760

Throw Ceiling 7.5-13.2 (M)

Wall NC

9.5-15.2 11.5-17.5 13.3-19.4 14.4-21.4 15.8-22.1 17.0-23.7

11.4-19.9 14.1-22.2 16.7-24.7 18.9-26.9 20.2-28.7 21.7-30.5 23.0-32.0 -

• Throw is based on terminal velocities of 0.5 m/s - 0.25 m/s respectively. • NC value is based on a room absorption of 10 dB, re 10-12 watts. • Dash (-) in space indicates NC value less than 20.

12

8.5-13.0 10.2-14.3 11.4-16.0 12.5-17.7 13.6-19.2 14.7-20.4

23

28

32

37

40

43

• With G1 damper, the pressure loss is 1.136P, and add 2 for NC value. • The performance data is tested based on A.D.C. standard.


RA Linear Bar Grille • Materials:

RA Linear Bar Grille

• RA-A Extruded Aluminium A6063.

• Surface Finish: • • • •

• Baked White Powder Coat or Natural Anodized as standard. The bar grille air blades are fixed & not adjustable. Maximum single length is 3m. Above this length, the grille will come in multiple section. The neck sizes (w) are proportional to the number of linear bar blades. Please refer to the following table. Two different types of linear bar face deflection angle are available. The bar grilles that come with plenum boxes are known as RAB.

Construction Illustration

• Linear blade Vs width

Unit:mm

No. of Blade

2

3

4

5

6

7

8

10

12

14

16

18

20

Neck Size

45

60

75

90

105

120

135

165

195

225

255

285

315

Model RA-A

RAB

Materials

Extruded Aluminium A6063

Thickness Frame Blade

1.2

4.0

LXW Neck Size L: To suit design Length W: Tosuit No. of Blade

A B D Duct Size Wall Size Face Size

Order Key

Physcal Dimension RA-A-100X3-1 Unit:mm

L+10 W+10

L+15 W+15

L+30 W+30

Materials

No. of blades

Length Model

Type of blade

13


RA Linear Bar Grille • 90˚ mitred corner sections for linear bar grilles are available. • Joining strips are available for continuous installation of the mitred corner section & the linear bar grille.

RA-A Linear Bar Grille

• Maximum length of a single linear bar grille is 3m. Above 3m, the grille will come in multiple section. • Joining strips are available for multiple section

RA-A Linear Bar Grille

14

of linear bar grille.


RAB Linear Bar Grille c/w Plenum Box • Two different linear bar face deflection angles are available. • Deflection for RA-1:0˚ RA-2:15˚

RA-A Bar Deflection Angle

• Model RAB: RA Linear Bar Grille c/w Plenum Box.

RAB Linear Bar Grille c/w Plenum Box

• Plenum box is constructed of 0.5mm SPGC Galvanized Steel. • Two types of insulation are available. • External insulation: 25mm X 24kg/m3 Fiberglass wrapped with fiber-reinforced aluminium foil. • Internal insulation: 10mm thick PE foam.

L Length of Plenum Box

W Width of Plenum Box

H Height of Plenum Box

S Inlet Size

Length of Linear Bar Grille L+5

Width of Linear Bar Grille W+5

195

100ø~300ø above 200mm, inlet diameter is over type

Physcal Dimension Unit:mm

15


Performance Data for RA-1 (0˚) Performance Data for RA-1 (Supply)

Model

2

3

4

5

6

7

8

10

Vel. M/S

2

3

4

5

6

7

Tot. Press (mmAq)

0.4

0.6

0.9

1.6

2.2

3.0

CMH

127

190

254

318

382

445

Throw

Ceiling

0.3-0.3

1.2-1.2

2.1-2.1

2.7-3.0

3.3-3.6

4.2-4.8

(M)

Wall

1.5-2.1

2.4-3.6

3.3-4.8

4.2-6.0

5.1-6.9

5.7-7.8

NC

-

-

-

23

28

32

CMH

182

273

364

455

546

637

Throw

Ceiling

0.4-0.4

1.7-1.7

2.8-2.9

3.5-3.8

4.4-4.7

5.1-5.4

(M)

Wall

1.9-2.6

2.8-4.0

4.0-5.3

4.9-6.5

5.6-7.4

6.6-8.6

NC

-

-

-

22

27

31

CMH

240

360

480

600

720

840

Throw

Ceiling

0.8-0.8

2.3-2.3

3.4-3.5

4.3-4.6

5.3-5.6

6.1-6.6

(M)

Wall

2.1-3.0

3.4-4.6

4.6-5.9

5.6-7.4

6.6-8.2

7.6-9.4

NC

-

-

-

22

27

31

CMH

305

457

609

761

914

1065

Throw

Ceiling

0.9-0.9

2.7-2.7

3.9-3.9

4.8-5.1

6.0-6.3

6.9-7.2

(M)

Wall

2.4-3.3

3.9-5.1

5.1-6.3

6.0-7.5

7.5-9.0

8.4-10.2

NC

-

-

-

23

28

32

CMH

360

540

720

900

1080

1260

Throw

Ceiling

1.1-1.1

3.0-3.0

4.2-4.2

5.2-5.2

6.5-6.8

7.2-7.3

(M)

Wall

2.8-3.7

4.2-5.4

5.5-6.8

6.5-8.0

8.0-9.5

8.9-10.7

NC

-

-

-

23

28

32

CMH

417

625

834

1042

1250

1460

Throw

Ceiling

1.3-1.3

3.0-3.0

4.4-4.4

5.5-5.5

6.8-6.8

7.4-7.4

(M)

Wall

3.2-4.1

4.4-5.6

5.9-7.1

6.8-8.3

8.3-9.8

9.4-11.2

NC

-

-

-

23

28

32

CMH

474

711

948

1185

1423

1660

Throw

Ceiling

1.5-1.5

3.0-3.0

4.5-4.5

5.5-5.5

6.9-6.9

7.5-7.5

(M)

Wall

3.6-4.5

4.8-6.0

6.0-7.2

7.2-8.7

8.7-10.2

9.9-11.7

NC

-

-

-

24

29

33

CMH

580

870

1161

1450

1740

2031

Throw

Ceiling

1.8-1.8

3.3-3.3

4.8-4.8

6.1-6.1

7.5-7.7

8.2-8.2

(M)

Wall

4.2-5.1

5.4-6.6

6.6-7.8

8.0-9.3

9.3-10.8

10.5-12.3

-

-

-

24

29

33

NC

• Throw values are based on an entire section one meter long. • Throw is based on terminal velocities of 0.5 m/s - 0.25 m/s respectively. • NC value is based on a room absorption of 10 dB, re 10-12 watts. • Dash (-) in space indicates NC value less than 20. • For return air application, Negative SP=0.75 x Tot. Press. NC=above plus 5. • The performance data is tested based on A.D.C. standard.

16

• Corrected values for throw and NC value as the length changes

Length (M)

0.5

1

1.5

2

NC

-2

0

+2

+3

Terminal Vel. 0.5m/s

0.8

1

1.1

1.2

Terminal Vel. 0.25m/s 0.9 Eg: When length is 2m, Throw: use a multiple of 1.2 NC: NC plus 3

1

1.15

1.2


Performance Data for RA-2 (15˚) Model

2

3

4

5

6

7

8

10

Vel. M/S

2

3

4

5

6

7

Tot. Press (mmAq)

0.4

0.6

0.9

1.6

2.2

3.0

CMH

130

194

260

324

389

454

Throw

Ceiling

0.3-0.3

1.2-1.2

2.1-2.1

2.7-3.0

3.3-3.6

4.2-4.8

(M)

Wall

1.5-2.1

2.4-3.6

3.3-4.8

4.2-6.0

5.1-6.9

5.4-7.5

NC

-

-

24

30

35

40

CMH

180

270

360

450

540

630

Throw

Ceiling

0.4-0.4

1.6-1.6

2.6-2.8

3.4-3.7

4.5-4.8

5.2-5.7

(M)

Wall

1.8-2.5

2.8-4.0

3.7-5.2

5.0-6.5

5.9-7.7

6.7-8.5

NC

-

-

23

29

34

39

CMH

233

350

467

583

700

816

Throw

Ceiling

0.6-0.6

2.0-2.0

3.4-3.4

4.0-4.3

5.2-5.5

6.1-6.4

(M)

Wall

2.0-2.9

3.2-4.4

4.4-5.8

5.3-6.9

6.4-8.1

7.5-9.3

NC

-

-

22

28

33

38

CMH

292

437

583

729

875

1020

Throw

Ceiling

0.9-0.9

2.4-2.7

3.9-3.9

4.5-4.8

5.7-6.0

6.6-6.9

(M)

Wall

2.4-3.3

3.6-4.8

5.1-6.3

5.7-7.2

7.2-8.7

8.1-9.9

NC

-

-

23

29

34

39

CMH

346

520

692

866

1039

1212

Throw

Ceiling

1.1-1.1

2.6-2.7

4.2-4.2

5.0-5.1

6.2-6.5

7.1-7.2

(M)

Wall

2.8-3.7

4.0-5.2

5.5-6.8

6.2-7.7

7.5-9.2

8.6-10.5

NC

-

-

23

29

34

39

CMH

402

603

804

1004

1250

1406

Throw

Ceiling

1.3-1.3

2.8-2.8

4.3-4.3

5.3-5.3

6.6-6.7

7.4-7.4

(M)

Wall

3.1-4.0

4.4-5.6

5.8-7.1

6.6-8.1

7.7-9.5

8.8-10.7

NC

-

-

23

29

34

39

CMH

455

682

910

1137

1365

1592

Throw

Ceiling

1.5-1.5

3.0-3.0

4.5-4.5

5.4-5.4

6.9-6.9

7.5-7.5

(M)

Wall

3.3-4.2

4.8-6.0

6.0-7.2

7.2-8.4

8.1-9.6

9.0-10.8

NC

-

-

23

29

34

39

CMH

562

842

1123

1404

1685

1965

Throw

Ceiling

1.8-1.8

3.3-3.3

4.8-4.8

6.0-6.0

7.5-7.7

8.1-8.1

(M)

Wall

3.6-4.5

5.4-6.6

6.6-7.8

7.9-9.0

8.5-10.1

9.6-11.4

-

-

23

29

34

39

NC

• Throw values are based on an entire section one meter long. • Throw is based on terminal velocities of 0.5 m/s - 0.25 m/s respectively. • NC value is based on a room absorption of 10 dB, re 10-12 watts. • Dash (-) in space indicates NC value less than 20. • For return air application, Negative SP=0.75 x Tot. Press. NC=above plus 5. • The performance data is tested based on A.D.C. standard.

Performance Data for RA-2 (Supply)

• Corrected values for throw and NC value as the length changes

Length (M)

0.5

1

1.5

2

NC

-2

0

+2

+3

Terminal Vel. 0.5m/s

0.8

1

1.1

1.2

Terminal Vel. 0.25m/s 0.9 Eg: When length is 2m, Throw: use a multiple of 1.2 NC: NC plus 3

1

1.15

1.2

17


Performance Data for RA Performance Data for RA (Return)

Model

2 3 4 5 6 7 8 10

Vel. M/S

2

3

4

5

6

7

Vel. Press (mmAq)

0.25

0.55

1.0

1.55

2.2

3.0

Neg. SP. (mmAq)

0.3

0.5

0.7

1.2

1.7

2.3

CMH/M

127

190

254

318

382

445

NC

-

-

22

28

33

37

CMH/M

182

273

364

455

546

637

NC

-

-

21

27

32

36

CMH/M

240

360

480

600

720

840

NC

-

-

21

27

32

36

CMH/M

305

457

609

761

914

1065

NC

-

-

22

28

33

37

CMH/M

360

540

720

900

1080

1260

NC

-

-

22

28

33

37

CMH/M

417

625

834

1042

1250

1460

NC

-

-

22

28

33

37

CMH/M

474

711

948

1185

1423

1660

NC

-

-

23

29

34

38

CMH/M

580

870

1161

1450

1740

2031

NC

-

-

23

29

34

38

• Throw values are based on an entire section one meter long. • Throw is based on terminal velocities of 0.5 m/s - 0.25 m/s respectively. • NC value is based on a room absorption of 10 dB, re 10-12 watts. • Dash (-) in space indicates NC value less than 20.

18

• Corrected values for throw and NC value as the length changes

Length (M) Correction

0.5 -2

1 0

1.5

2

+2

+3

• The performance data is tested based on A.D.C. standard.


SLLS Linear Ceiling Diffuser • Materials:

SLLS Linear Ceiling Diffuser

• SLLS Extruded Aluminium A6063.

• Surface Finish: • • • • •

• Baked White Powder Coat as standard. Pattern controller vane is Black anodised. SLLS linear ceiling diffuser can be used in T-bar ceiling suspension system & other ceiling types as well. The diffuser incorporates curved blade pattern controller for adjustable of air distribution. Available with 1 slot to 4 slots. Linear diffusers that come with plenum boxes are known as SLLSB. Model GLL-1 has a 90˚ mitred corner connection & model SLLS-2 is 45˚ .

• Standard sizes: • 600(2'), 1200(4').

Construction Illustration

Model

Materials

Thickness Frame Blade

1 Slot 2 Slot 3 Slot 4 Slot

W Neck Size

A B D Duct Size Ceiling Size Face Size

50 Extruded Aluminium A6063

1.2

1.0

94 138 182

Order Key SLL-1-2-100

L+10 W+10

L+15 W+15

L+50 W+25

90˚ Model

Physcal Dimension Unit:mm

Length

No. of Slot

19


SLLB Linear Ceiling Diffuser c/w Plenum Box SLLS Frame Details

SLLS Air Distribution Adjustment

• Model SLLSB: SLLS Linear Diffuser c/w Plenum Box.

SLLSB Linear Diffuser c/w Plenum Box

Physcal Dimension Unit:mm

20

• Plenum box is constructed of 0.5mm SPGC Galvanized Steel. • Two types of insulation are available. • External insulation: 25mm X 24kg/m3 Fiberglass wrapped with fiber-reinforced aluminium foil. • Internal insulation: 5mm thick PE foam.

L Length of Plenum Box

W Width of Plenum Box

H Height of Plenum Box

S Inlet Size

Length of slots diffuser L+5

Width of slots diffuser W+15

195

100ø~300ø above 200mm, inlet diameter is over type


Performance Data for SLLS • Model SLL & Plenum Box Installation.

SLL & Plenum Box Installation

• SLL linear supply air diffusers have a U-type fastening hook & an adjustable screws for installing the diffuser onto the plenum box. • For installation, one can install the diffuser together with the plenum box. However for some application, one can fix the box onto the ceiling, then use the U-type fastening hook to fasten the diffuser to the plenum box. Use the screw to adjust the face flush with the ceiling.

No. of Tot. Press H Slot (mmAq) V CMH H 1 Slot Throw (M) V NC CMH H 2 Slot Throw (M) V NC CMH H 3 Slot Throw (M) V NC CMH H 4 Slot Throw (M) V NC

0.1 0.05 55 0.3-0.9 0.6 105 0.6-1.8 1.5 165 0.9-3.0 2.0 215 0.9-3.3 2.4 -

0.4 0.3 105 0.9-3.2 2.4 215 1.8-4.5 3.3 325 3.0-5.6 3.8 435 3.3-6.5 4.5 -

1.0 0.6 165 2.4-3.9 3.6 325 3.5-5.6 4.8 485 4.8-6.8 6.0 650 5.0-8.0 6.8 -

1.6 1.0 215 3.2-4.5 4.2 435 4.5-6.5 5.6 21 650 5.6-8.0 7.2 24 870 6.5-9.2 8.4 26

2.5 1.5 275 3.5-5.0 1.5 23 545 5.0-7.2 6.5 28 815 6.2-9.0 8.0 31 1085 7.2-10.2 9.2 33

3.6 2.2 325 3.8-5.6 5.1 28 650 5.6-8.0 7.2 33 980 6.8-9.5 8.6 36 1305 8.0-11.0 10.2 38

5.0 3.0 385 4.2-6.0 5.4 33 760 7.5-8.4 7.8 38 1140 7.5-10.5 9.5 41 1520 8.6-12.0 10.8 43

6.4 3.8 435 4.5-6.5 5.7 37 870 6.5-9.2 8.4 42 1305 8.0-11.0 10.2 45 1740 9.2-12.8 11.6 47

No. of Slots Neg. SP (mmAq)

0.5 135 270 405 545 -

1.0 200 405 610 815 -

1.8 270 545 815 21 1085 21

2.8 340 21 680 24 1020 26 1360 27

4.1 405 26 815 29 1225 31 1630 32

5.5 475 30 950 33 1425 35 1905 36

7.2 545 34 1085 37 1630 39 2175 40

11.5 680 40 1360 43 2040 45 2720 46

1 Slot 2 Slot 3 Slot 4 Slot

CMH NC CMH NC CMH NC CMH NC

• Throw values are based on an entire section 1.2 meter long. • Throw is based on terminal velocities of 0.5m/s - 0.25m/s respectively. • NC value is based on a room absorption of 10 dB, re 10-12 watts. • Dash (-) in space indicates NC value less than 20. • The performance data is tested based on A.D.C. standard.

Performance Data for SLLS (Supply)

Performance Data for SLLS (Return)

• NC Correction for Various Diffuser Lengths

Length (M)

0.6

1.2

2.4

Supply NC

-5

0

+3

Return

-3

0

+2

21


Performance Data for SLLSB CMH

30

SLLSB-1 Tot. Press (mmAq) 0.3 1 Slot 100mm Throw (M) 0.6-1.2 24" Long Inlet

105

120

135

0.6

1.0

1.5

2.2

3.0

4.0

5.0

0.9-1.8

1.2-2.4

1.5-3.0

1.8-3.8

2.0-4.5

2.4-5.0

2.6-5.4

20

25

29

33

36

40

CMH

25

55

85

115

140

170

195

225

0.1

0.4

0.9

1.6

2.5

3.6

5.0

6.5

Throw (M)

0.6-1.2

1.2-2.4

1.8-3.5

2.4-4.8

3.0-5.4

3.5-6.0

4.2-6.5

4.8-6.8

NC

-

-

-

20

25

30

33

37

CMH

65

95

130

160

195

225

255

290

0.6

1.1

1.7

2.4

3.3

4.2

5.4

1.5-3.0

1.8-3.8

2.4-5.0

3.0-6.0

3.2-6.8

3.8-7.5

4.5-7.8

NC

-

-

20

25

29

33

36

39

CMH

50

100

150

200

255

305

355

405

0.1

0.4

0.9

1.6

2.4

3.5

4.7

6.2

0.6-1.5

1.5-3.0

2.4-4.8

3.0-6.2

3.8-7.2

4.8-8.0

5.4-8.6

6.2-9.2

-

-

-

20

25

30

33

37

65

95

130

160

195

225

255

290

0.6

1.1

1.7

2.4

3.3

4.2

5.4

1.5-3.0

1.8-3.8

2.4-5.0

3.0-6.0

3.2-6.8

3.8-7.5

4.5-7.8

Throw (M) NC

CMH

SLLSB-2 Tot. Press (mmAq) 0.3 2 Slot 150mm Throw (M) 0.8-1.8 24" Long Inlet NC

-

-

20

25

29

33

36

39

CMH

50

100

150

200

255

305

355

405

0.1

0.4

0.9

1.6

2.4

3.5

4.7

6.2

Throw (M)

0.6-1.5

1.5-3.0

2.4-4.8

3.0-6.2

3.8-7.2

4.8-8.0

5.4-8.6

6.2-9.2

NC

-

-

-

20

25

30

33

37

CMH

100

150

200

255

305

355

405

460

0.5

0.9

1.4

2.0

2.7

3.6

4.5

1.5-3.2

2.0-4.5

2.7-5.4

3.2-6.5

3.8-7.8

4.5-9.0

5.0-9.8

200mm Tot. Press (mmAq)

SLLSB-2 Tot. Press (mmAq) 0.3 2 Slot 150mm Throw (M) 0.8-2.0 48" Long Inlet NC

-

-

20

25

29

33

36

39

CMH

70

135

205

275

345

415

485

555

0.1

0.3

0.6

1.2

1.8

2.6

3.5

4.5

Throw (M)

0.6-1.5

1.5-3.0

2.0-4.5

3.0-6.0

3.6-7.5

4.5-9.2

5.4-10.2

6.0-10.8

NC

-

-

-

20

25

30

33

37

200mm Tot. Press (mmAq) Inlet

90

-

200mm Tot. Press (mmAq)

Inlet

75

-

SLLSB-1 Tot. Press (mmAq) 0.3 1 Slot 150mm Throw (M) 0.8-1.8 48" Long Inlet

Inlet

60

NC

150mm Tot. Press (mmAq) Inlet

45

• Throw is based on terminal velocities of 0.5 m/s - 0.25 m/s respectively. • NC value is based on a room absorption of 10 dB, re 10-12 watts.

22

• Dash (-) in space indicates NC value less than 20. • The performance data is tested based on A.D.C. standard.


Accessories • G1 - Opposed Blade Damper. • Materials:

• G1-T Frame 0.6mm SPGC Galvanized Steel. Blade 0.5mm SPGC Galvanized Steel.

G1 Opposed Blade Damper

• Surface Finishing:

• G1-T Baked Black as standard. • Maximum dimension is 500mm x 500mm. damper size bigger than this will come in sections. • Gear operated, can be set at fully open, half open & fully close.

• G2 Volume Extractor. • Materials:

• G2-T 1.0mm SPGC Galvanized Steel. • G2-S 0.5mm Stainless Steel SUS. 304.

G2 Volume Extractor

• Surface Finishing:

• G2-T Baked Black as standard. • G2-S Stainless Steel Original Colour. • Maximum dimension is 800mm x 500mm. • Suitable for model GV & GH wall grille as guide vanes. • Maximum angle of opening 35˚ - 40˚.

23


Turn static files into dynamic content formats.

Create a flipbook