R407C
NEW The High-efficiency Air-cooled Chiller "H series" The air-cooled chiller "H series" with improved efficiency and functionality by several advanced technologies. This series with the world's best standard A-type screw compressor and newly designed shell and tube heat exchanger that have powerful cooling ability, low noise, low vibration, high efficiency and high reliability is the perfect answer to all your needs!!
E nhanced Line-up
~up to 400 HP~
H igh-performance A-type Screw Compressor P recise Capacity Control Technology E xcellent Control Function H ighly Reliable Shell and Tube Heat Exchanger
Improved heat-exchange performance by using inverse M type Air Side Heat Exchanger
Protection Net (standard equipment)
Acoustic Chamber (standard equipment)
Product Series RCUG-AHYZ1
RCU-AHYZ1
Nominal Capacity Range (50Hz)
Nominal Capacity Range (50Hz)
110 kW to 1,089 kW
116 kW to 1,146 kW
31 USRT to 310 USRT
33 USRT to 326 USRT
94,600 kcal/h to 936,540 kcal/h
99,760 kcal/h to 985,560 kcal/h
R407C Wide Line-up
To meet the need for air conditioning systems for large facilities and the demand for higher capacity industrial cooling systems.
40
50
60
75
100
120
150
160
180
200
240
270
300
330
350
360
380
400 (HP)
RCUG-AHYZ1
R407C RCU-AHYZ1
40
50
60
75
100
120
150
160
180
200
240
270
300
330
350
360
380
400 (HP)
2
Technical Features
H igh-performance A-type Screw Compressor ~Newly Designed~ Built-in Cyclone Oil Separator
NEW
Low oil carrying-out is realized and reduction of heat transfer efficiency is minimized.
High Technology by Internal Manufacture Because all manufacturing processes, from rotor manufacturing to unit assembly, are done internally, exceptional reliability is achieved.
New Screw Compressor Operation Image
No outside pump is required due to the reliable differential-pressure oil-feeding system.
Discharged Gas
Cyclone Oil Separator
Suctioned Refrigerant Gas Screw Rotor
This oil-feeding system, which does not use any electrical mechanism, prevents the compressor from being damaged and maintains long-term stable operation.
Oil Oil Reservoir Differential Pressure Lubrication Mechanism
Simple Structure with a Small Number of Parts Whereas the number of main parts for the casing, compression mechanism and capacity control mechanism of a reciprocating compressor is 268, that of a screw compressor is only 27, just one tenth of the number ! A structure with so few parts offers high reliability and easy maintenance.
Vibration Comparison
Low Vibration Level No exclusive vibration control equipment is necessary by using low-vibration screw compressor.
Reciprocating
Screw
1,430 / 1,720
2,880 / 3,470
At leg of comp.
20-30
5-8
At base frame
20
Less than 10
At leg of comp.
23.8 / 28.7
48.5 / 57.8
At base frame
23.8 / 28.7
48 / 57.8
Type Comp. speed (rpm) 50/60Hz
Full amplitude
Vib. frequecy
Acceleration energy
3
Screw: 1/5 of reciprocating type
P recise Capacity Control Technology Continuous Capacity Control The temperature of the chilled water outlet can be kept at the set temperature ¹1°C by continuous capacity control, so it is suitable for industrial use. Load-up signal 12sec.
Start
Capacity Controller Structural Outline
When there is a big difference between set temperature and actual temperature.
(HITACHI Patented System)
60sec.
Load-up
Inlet water temperature
Load-up signal
Inlet water temperature
Slide Valve
2sec.
Outlet water temperature
Bypass Gas
Outlet water temperature
60sec.
Load-down Low Pressure Gas
Low Pressure Gas
Slide Valve Bypass Gas
Pd
Ps
Ps
Pd
8 Suction Gas
Neutral zone standard
6 4
Stop
Rotor
Stop temperature standard
Load-down signal 2sec. 60sec.
SV1
Suction Gas
SV2
SV3 Rotor
SV1
SV2
High Pressure Oil
High Pressure Oil
Lapsed time A given load status is maintained.
SV3
Pd: Discharge pressure, Ps: Suction pressure,
The inlet water temperature is detected at a stop, and it is restarted by a rise in inlet water temperature.
SV1,2,3 : Solenoid valve
: Valve open
: Valve close
E xcellent Control Function Building Management System (BMS) R
Hitachi uses Building Management System through LONWORKS . For chiller air-conditioning, Hitachi provides its own central station system. No complicated work is necessary.
* : "LONWORKS
R
" is a trademark of Echelon Corporation registered in the United States and other countries.
List of Functions
BMS System (Supplied by BMS Maker)
Remote Setting
*
Other Building Equipment
G/W communication adapter (option)
G/W communication adapter (option) can be connected up to 4 units.
ON / OFF Operation Chilled Water Temperature (Inlet or Outlet) Remote Monitor
ON / OFF Status Setting Chilled Water Temperature (Inlet or Outlet) Current Water Temperature of Inlet and Outlet Alarm Code
* In addition, up to 8 units can be connected using the G/W communication adapter for the Hitachi Chiller Unit signal (RS485).
* Equipment below the dotted line is provided by HITACHI
H ighly Reliable Shell and Tube Heat Exchanger ~Newly Designed~ Dry expansion cooler system Low environmental impact: refrigerant quantity reduced by 60% from the current unit Perfect matching with the chiller unit due to our own design - Downsized by redesigned heat-transfer tube - Improved efficiency by optimized refrigerant distribution
4
R407C General Data Model
RCUG40AHYZ1
Power Source Nominal Cooling Capacity*1
RCUG100AHYZ1 272
kW
110
136
170
181
USRT
31
39
48
51
77
kcal/h
94,600
116,960
146,200 Continuous Capacity Control
155,660
233,920
2,170
2,170
2,170
2,170
2,170
1,940
1,940
1,940
1,940
1,940
2,390
2,390
2,390
2,390
4,490
1,790
1,830
1,870 R407C
1,890
3,210
Capacity Control
mm
Width Depth
kg
Net Weight Type Refrigerant
Thermal Expansion Valve
Flow Control
1 Semi-Hermetic Screw Type
Number of Circuits Type Model
Compressor
mm
Width Depth
kg
Shipping Weight
1.1
1.1
2,190
2,190
2,190
2,190
2,600
2,600
2,600
2,600
4,700
2,000
2,040
2,080
2,100
Main Power (square orifice)
500 x 160
mm
φ48; φ64.5; φ102; φ52
RCUG270AHYZ1
RCUG330AHYZ1 RCUG300AHYZ1 RCUG350AHYZ1 Main (AC 3φ) 380, 415V / 50Hz, Control (AC 1φ) 220, 240V / 50Hz
RCUG360AHYZ1 1,020
kW
703
726
873
907
200
206
248
258
290
kcal/h
604,580
624,360
750,780
780,020
877,200
Continuous Capacity Control 100~15(7.5)*2, 0
% mm
Width Depth
kg
Net Weight
2,170
2,170
2,170
1,940
1,940
1,940
1,940
1,940
9,080(min.)
9,080(min.)
11,180(min.)
11,180(min.)
13,280(min.)
3,320 + 3,280
2 x 3,320
4,865 + 3,320
4,900 + 3,320
2 x 4,865
Thermal Expansion Valve 5
4
Number of Circuits Type 60ASCC-Z
Model
60ASCC-Z
Condenser Fan Fan Motor Power Intput Quantity
kW
Safety Devices Height
mm
Depth
kg
Shipping Weight Inlet Outlet
Main Power (square orifice)
60ASCC-Z
60ASCC-Z 6
Cross Fin Type
Evaporator
Width
6
5
Condenser
5
Semi-Hermetic Screw Type 60ASCC-Z
4
Quantity
Circuit
2,170
R407C
Flow Control
Piping Connections for Water Side Heat Exchanger
100~15(7.5)*2, 0
100~15(6)*2, 0
2,170
Type
Connection Hole
2 xφ48; φ64.5; φ102; φ52
USRT
Height
Shipping Dimensions
3,610 With φ142 Inner Diameter Companion Flange
With φ90 Inner Diameter Companion Flange
Capacity Control
Heat Exchanger
1.1
2,190
Inlet Outlet
Model
Compressor
1.1
4
Power Source
Refrigerant
1.1
4
Circuit
Outer Dimensions
2
4 8 4 Shell-and-Tube Type Overcurrent Relay for Compressor, Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor, Thermal Overcurrent Relay for Fan Motor, High-Pressure Switch, Low-Pressure Control, Suction Gas Temperature Control, Freeze Protection Thermistor Control, Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve 2,510 2,510 2,510 2,510 2,510
Height
Nominal Cooling Capacity*1
50ASCC-Z
Direct Drive Propeller Fan kW
Safety Devices
Connection Hole
60ASCC-Z
Cross Fin Type
Condenser Fan Fan Motor Power Intput Quantity Evaporator
Piping Connections for Water Side Heat Exchanger
2
1
Condenser
Shipping Dimensions
60ASCC-Z
50ASCC-Z
40ASCC-Z
Quantity
Heat Exchanger
100~15(7.5)*2, 0
100~15, 0
% Height
Outer Dimensions
RCUG60AHYZ1 RCUG50AHYZ1 RCUG75AHYZ1 Main (AC 3φ) 380, 415V / 50Hz, Control (AC 1φ) 220, 240V / 50Hz
1.1
1.1
Direct Drive Propeller Fan 1.1
1.1
1.1
8+8
2x8
12 + 8
12 + 8
2 x 12
Shell-and-Tube Type Overcurrent Relay for Compressor, Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor, Thermal Overcurrent Relay for Fan Motor, High-Pressure Switch, Low-Pressure Control, Suction Gas Temperature Control, Freeze Protection Thermistor Control, Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve 2,510 2,510 2,510 2,510 2,510 2,190 2,190 2,190 2,190 2,190 2 x 4,700
2 x 4,700
6,800 + 4,700
6,800 + 4,700
2 x 6,800
3,720 + 3,680
2 x 3,720
5,500 + 3,720
5,535 + 3,720
2 x 5,500
With φ142 Inner Diameter Companion Flange 2 x 500 x 160
mm 4 xφ48; 2 xφ64.5; 2 xφ102; 2 xφ52
5 xφ48; 2 xφ64.5; 2 xφ102; 3 xφ52
6 xφ48; 2 xφ64.5; 2 xφ102; 4 xφ52
R407C RCUG180AHYZ1 RCUG200AHYZ1 RCUG160AHYZ1 RCUG150AHYZ1 Main (AC 3φ) 380, 415V / 50Hz, Control (AC 1φ) 220, 240V / 50Hz
RCUG120AHYZ1
RCUG240AHYZ1
340
363
408
510
544
97
103
116
145
155
193
292,400
312,180
467,840
584,800 100~15(7.5)*2, 0 2,170
438,600 350,880 Continuous Capacity Control
680
100~15(5)*2, 0
100~15(7.5)*2, 0 2,170
2,170
2,170
2,170
2,170
1,940
1,940
1,940
1,940
1,940
1,940
4,490
4,490
6,590
6,590
6,590
9,080(min.)
3,280
3,320
4,745
4,865
4,900
2 x 3,280
R407C Thermal Expansion Valve 3 Semi-Hermetic Screw Type
2 60ASCC-Z
60ASCC-Z
50ASCC-Z
60ASCC-Z
4 60ASCC-Z
60ASCC-Z
3
2
4
Cross Fin Type Direct Drive Propeller Fan 1.1
1.1
1.1
1.1
1.1
1.1
8
8
12
12
12
2x8
Shell-and-Tube Type Overcurrent Relay for Compressor, Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor, Thermal Overcurrent Relay for Fan Motor, High-Pressure Switch, Low-Pressure Control, Suction Gas Temperature Control, Freeze Protection Thermistor Control, Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve 2,510 2,510 2,510 2,510
2,510
2,510
2,190
2,190
2,190
2,190
2,190
2,190
4,700
4,700
6,800
6,800
6,800
2 x 4,700
3,680
3,720
5,380
5,500
5,535
2 x 3,680
With φ142 Inner Diameter Companion Flange 500 x 160 3 xφ48; φ64.5; φ102; 2 xφ52
2 xφ48; φ64.5; φ102; φ52
RCUG380AHYZ1 RCUG400AHYZ1 Main (AC 3φ) 380, 415V / 50Hz, Control (AC 1φ) 220, 240V / 50Hz 1,055
1,089
300
310
907,300
936,540
Continuous Capacity Control 100~15(7.5)*2, 0 2,170
2,170
1,940
1,940
13,280(min.)
13,280(min.)
2 x 500 x 160 4 xφ48; 2 xφ64.5; 2 xφ102; 2 xφ52
NOTES: 1. The nominal cooling capacities are based on the following conditions. (*1) Chilled Water Inlet / Outlet Temperature: 12˚C / 7˚C Condenser Air Inlet Temperature: 35˚C(DB) 2. The units greater than 240AHYZ1 including 240AHYZ1consist of two modules and are separately shipped. The common chilled water piping (Filed-Supplied) between each water cooler shall be directly connected at site.
2 x 4,900
4,900 + 4,865
R407C Thermal Expansion Valve 6 Semi-Hermetic Screw Type 60ASCC-Z 60ASCC-Z 6 Cross Fin Type Direct Drive Propeller Fan 1.1 1.1 2 x 12
12 + 12
3. Water Flow 1) RCUG240, 300, 360, 400AHYZ1 It is necessary to control the common water flow volume to each cooler. 2) RCUG270, 330, 350, 380AHYZ1 The chilled water flow rate is different between No.1 & No.2 units. It is necessary to control the water flow volume of each unit with adjusting valves (Filed-Supplied). 4. It is required to connect electrical control wires between No.1 & No.2 units for the unit greater than 240AHYZ1 including 240AHYZ1.
Shell-and-Tube Type Overcurrent Relay for Compressor, Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor, Thermal Overcurrent Relay for Fan Motor, High-Pressure Switch, LowPressure Control, Suction Gas Temperature Control, Freeze Protection Thermistor Control, Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve
2,510
5. ( ) marked with *2 is available by selection switch.
2,510
2,190
2,190
2 x 6,800
2 x 6,800
5,535 + 5,500
2 x 5,535
With φ142 Inner Diameter Companion Flange 2 x 500 x 160 6 xφ48; 2 xφ64.5; 2 xφ102; 4 xφ52
Working Range Item
Standard
Chilled Water Outlet Temperature
5~15˚C
Condenser Air Inlet Temperature (DB)
5~43˚C 6
R22
General Data
Model
RCU40AHYZ1
Power Source Nominal Cooling Capacity*1
RCU100AHYZ1 286
kW
116
143
179
191
USRT
33
41
51
54
81
kcal/h
99,760
122,980
153,940 Continuous Capacity Control
164,260
245,960
2,170
2,170
2,170
2,170
2,170
1,940
1,940
1,940
1,940
1,940
2,390
2,390
2,390
2,390
4,490
1,790
1,830
1,870 R22
1,890
3,210
Capacity Control
mm
Width Depth
kg
Net Weight Type Refrigerant
Thermal Expansion Valve
Flow Control Number of Circuits Type
Cross Fin Type Direct Drive Propeller Fan
Condenser Fan Fan Motor Power Intput Quantity Evaporator
kW
Height mm
Width Depth
kg
Shipping Weight
Connection Hole
1.1
1.1
4
2,190
2,190
2,190
2,190
2,190
2,600
2,600
2,600
2,600
4,700
2,000
2,040
2,080
2,100
Inlet Outlet
Main Power (square orifice)
500 x 160
mm
φ48; φ64.5; φ102; φ52
Model
RCU300AHYZ1
RCU270AHYZ1 740
764
919
955
210
217
261
272
305
kcal/h
636,400
657,040
790,340
821,300
923,640
mm
Width
kg
Net Weight
2,170
2,170
2,170
1,940
1,940
1,940
1,940
1,940
9,080(min.)
9,080(min.)
11,180(min.)
11,180(min.)
13,280(min.)
3,320 + 3,280
2 x 3,320
4,865 + 3,320
4,900 + 3,320
2 x 4,865
Thermal Expansion Valve 5
4
Number of Circuits Type 60ASCC-Z
Model
60ASCC-Z
Semi-Hermetic Screw Type 60ASCC-Z
4
Quantity Condenser Fan Fan Motor Power Intput Quantity
kW
Height
mm
Depth
kg Inlet Outlet
Main Power (square orifice)
60ASCC-Z 6
1.1
1.1
Direct Drive Propeller Fan 1.1
1.1
1.1
8+8
2x8
12 + 8
12 + 8
2 x 12
Shell-and-Tube Type Overcurrent Relay for Compressor, Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor, Thermal Overcurrent Relay for Fan Motor, High-Pressure Switch, Low-Pressure Control, Suction Gas Temperature Control, Freeze Protection Thermistor Control, Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve 2,510 2,510 2,510 2,510 2,510
Safety Devices
Shipping Weight
60ASCC-Z
Cross Fin Type
Evaporator
Width
6
5
Condenser
Circuit
2,170
R22
Flow Control
Piping Connections for Water Side Heat Exchanger
100~15(7.5)*2, 0
100~15(6)*2, 0
2,170
Type
7
1,074
Continuous Capacity Control 100~15(7.5)*2, 0
%
Depth
Connection Hole
RCU360AHYZ1
kW
Height
Shipping Dimensions
RCU350AHYZ1
RCU330AHYZ1
USRT
Capacity Control
Heat Exchanger
2 xφ48; φ64.5; φ102; φ52
Main (AC 3φ) 380, 415V / 50Hz, Control (AC 1φ) 220, 240V / 50Hz
Nominal Cooling Capacity*1
Compressor
3,610 With φ142 Inner Diameter Companion Flange
With φ90 Inner Diameter Companion Flange
Power Source
Refrigerant
1.1
4
Circuit
Outer Dimensions
1.1
1.1
4 8 4 Shell-and-Tube Type Overcurrent Relay for Compressor, Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor, Thermal Overcurrent Relay for Fan Motor, High-Pressure Switch, Low-Pressure Control, Suction Gas Temperature Control, Freeze Protection Thermistor Control, Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve 2,510 2,510 2,510 2,510 2,510
Safety Devices
Piping Connections for Water Side Heat Exchanger
50ASCC-Z 2
1
Condenser
Shipping Dimensions
60ASCC-Z
60ASCC-Z
50ASCC-Z
40ASCC-Z
Quantity
Heat Exchanger
2
1 Semi-Hermetic Screw Type
Model
Compressor
100~15(7.5)*2, 0
100~15, 0
% Height
Outer Dimensions
RCU60AHYZ1 RCU50AHYZ1 RCU75AHYZ1 Main (AC 3φ) 380, 415V / 50Hz, Control (AC 1φ) 220, 240V / 50Hz
2,190
2,190
2,190
2,190
2,190
2 x 4,700
2 x 4,700
6,800 + 4,700
6,800 + 4,700
2 x 6,800
3,720 + 3,680
2 x 3,720
5,500 + 3,720
5,535 + 3,720
2 x 5,500
With φ142 Inner Diameter Companion Flange 2 x 500 x 160
mm 4 xφ48; 2 xφ64.5; 2 xφ102; 2 xφ52
5 xφ48; 2 xφ64.5; 2 xφ102; 3 xφ52
6 xφ48; 2 xφ64.5; 2 xφ102; 4 xφ52
RCU200AHYZ1 RCU160AHYZ1 RCU180AHYZ1 RCU150AHYZ1 Main (AC 3φ) 380, 415V / 50Hz, Control (AC 1φ) 220, 240V / 50Hz
RCU120AHYZ1
RCU240AHYZ1
358
382
429
537
573
102
109
122
153
163
204
307,880
328,520
492,780
615,760 100~15(7.5)*2, 0 2,170
461,820 368,940 Continuous Capacity Control
100~15(7.5)*2, 0
716
100~15(5)*2, 0
2,170
2,170
2,170
2,170
2,170
1,940
1,940
1,940
1,940
1,940
1,940
4,490
4,490
6,590
6,590
6,590
9,080(min.)
3,280
3,320
4,745
4,865
4,900
2 x 3,280
R22 Thermal Expansion Valve 2
3 Semi-Hermetic Screw Type
60ASCC-Z
60ASCC-Z
60ASCC-Z
50ASCC-Z
2
4 60ASCC-Z
60ASCC-Z
3
4
Cross Fin Type Direct Drive Propeller Fan 1.1
1.1
1.1
1.1
1.1
1.1
8
8
12
12
12
2x8
Shell-and-Tube Type Overcurrent Relay for Compressor, Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor, Thermal Overcurrent Relay for Fan Motor, High-Pressure Switch, Low-Pressure Control, Suction Gas Temperature Control, Freeze Protection Thermistor Control, Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve 2,510 2,510 2,510 2,510
2,510
2,510
2,190
2,190
2,190
2,190
2,190
2,190
4,700
4,700
6,800
6,800
6,800
2 x 4,700
3,680
3,720
5,380
5,500
5,535
2 x 3,680
With φ142 Inner Diameter Companion Flange 500 x 160 3 xφ48;φ64.5;φ102; 2 xφ52
2 xφ48; φ64.5; φ102; φ52
RCU400AHYZ1
RCU380AHYZ1
Main (AC 3φ) 380, 415V / 50Hz, Control (AC 1φ) 220, 240V / 50Hz 1,110
1,146
316
326
954,600
985,560
Continuous Capacity Control 100~15(7.5)*2, 0 2,170
2,170
1,940
1,940
13,280(min.)
13,280(min.)
4,900 + 4,865
2 x 500 x 160 4 xφ48; 2 xφ64.5; 2 xφ102; 2 xφ52
NOTES: 1. The nominal cooling capacities are based on the following conditions. (*1) Chilled Water Inlet / Outlet Temperature: 12˚C / 7˚C Condenser Air Inlet Temperature: 35˚C(DB) 2. The units greater than 240AHYZ1 including 240AHYZ1consist of two modules and are separately shipped. The common chilled water piping (Filed-Supplied) between each water cooler shall be directly connected at site.
2 x 4,900 R22
Thermal Expansion Valve 6 Semi-Hermetic Screw Type 60ASCC-Z 60ASCC-Z 6 Cross Fin Type Direct Drive Propeller Fan 1.1 1.1 12 + 12
2 x 12
3. Water Flow 1) RCU240, 300, 360, 400AHYZ1 It is necessary to control the common water flow volume to each cooler. 2) RCU270, 330, 350, 380AHYZ1 The chilled water flow rate is different between No.1 & No.2 units. It is necessary to control the water flow volume of each unit with adjusting valves (Filed-Supplied). 4. It is required to connect electrical control wires between No.1 & No.2 units for the unit greater than 240AHYZ1 including 240AHYZ1.
Shell-and-Tube Type Overcurrent Relay for Compressor, Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor, Thermal Overcurrent Relay for Fan Motor, High-Pressure Switch, LowPressure Control, Suction Gas Temperature Control, Freeze Protection Thermistor Control, Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve
2,510
5. ( ) marked with *2 is available by selection switch.
2,510
2,190
2,190
2 x 6,800
2 x 6,800
5,535 + 5,500
2 x 5,535
With φ142 Inner Diameter Companion Flange 2 x 500 x 160 6 xφ48; 2 xφ64.5; 2 xφ102; 4 xφ52
Working Range Item
Standard
Chilled Water Outlet Temperature
5~15˚C
Condenser Air Inlet Temperature (DB)
5~43˚C 8
Dimensional Data R407C RCUG40, 50, 60 and 75AHYZ1
RCU40, 50, 60 and 75AHYZ1
R22
2,390 2,100
290
1,900
Air Side Heat Exchanger
Air Discharge
Air Inlet
2,170
Air Inlet Electric Control Box
Rigging Holes (4-φ50)
300
485
Screw Type Compressor Water Inlet Temperature (With 90mm Inner Diameter Frange)
350
Water Outlet Temperature (With 90mm Inner Diameter Frange)
Mounting Holes (4-φ26)
Earth Connection Terminal M10 1,900
100
52.5
(1,945)
52.5
71
1,110
160
500
100
2,050 700
Fan NOTE: It should be surpport the water pipings properly to avoid its weight press on the unit directly.
Wiring Hole for Power Supply
R407C RCUG100, 120 and 150AHYZ1
RCU100, 120 and 150AHYZ1
R22
4,490 4,200
290
1,900 Air Discharge
Air Side Heat Exchanger
2,170
Air Inlet
Air Inlet
Water Outlet Temperature (With 142mm Inner Diameter Frange) 350
Mounting Holes (6-φ26)
Screw Type Compressor
Earth Connection Terminal M10 150
Rigging Holes (4-φ50)
300
485
Water Inlet Temperature (With 142mm Inner Diameter Frange)
Electric Control Box
1,950
1,950
52.5
(1,945)
52.5
1,140 71
2,090
160
500
100
2,050
NOTE: It should be surpport the water pipings properly to avoid its weight press on the unit directly.
Fan Wiring Hole for Power Supply
R407C RCUG160, 180 and 200AHYZ1
RCU160, 180 and 200AHYZ1
R22
6,590 6,300
290
1,900 Air Side Heat Exchanger
Air Discharge
2,170
Air Inlet
Earth Connection Terminal M10 1,950
2,100 3,125
71
430
Electric Control Box
Rigging Holes (4-φ50)
264
485
Water Inlet Temperature (With 142mm Inner Diameter Frange) 150
100
Air Inlet
Water Outlet Temperature (With 142mm Inner Diameter Frange)
Mounting Holes (8-φ26)
Screw Type Compressor 1,950
52.5
2,150
(1,945)
52.5
2,050
160
500
Fan
Wiring Hole for Power Supply
9
NOTES: 1. It should be surpport the water pipings properly to avoid its weight press on the unit directly. 2. Water connection flange (142mm) are supplied by factory with the unit.
R407C RCUG240, 270 and 300AHYZ1
RCU240, 270 and 300AHYZ1
R22
9,080(min.) 100(min.)
4,490
1,900 4,490
4,200
290
4,200
290 Air Discharge
Air Side Heat Exchanger
Air Side Heat Exchanger
2,170
Air Inlet
Air Inlet Electric Control Box
Water Outlet Temperature (With 142mm Inner Diameter Frange) 264 430
485
Screw Type Compressor 1,950
Earth Connection Terminal M10 1,950 4,200
150
No.1 Water Outlet 1,140
100
Rigging Holes (8-φ50) Mounting Holes (12-φ26)
71
Earth Connection Terminal M10 1,950 4,200
150
No.1 Water Inlet
2,090
No.2 Water Outlet
2,210
Water Inlet Temperature (With 142mm Inner Diameter Frange) 52.5
1,950
No.2 Water Inlet
2,090
500
160
Fan Wiring Hole for Power Supply
52.5
(1,945) 2,050
NOTES: 1. It should be surpport the water pipings properly to avoid its weight press on the unit directly. 2. These chillers consist of unit No.1 & No.2 and they are supplied separately when dispatched. 3. Water Flow For RCU(G)240,300AHYZ1: It is necessary to control the same water quantity to each cooler. For RCU(G)270AHYZ1: The chilled water flow rate is different between No.1 & No.2 unit... It is necessary to control the water quantity of each unit with adjusting valves (Field-Supplied). 4. It needs to field connect the control wiring between the No.1 & No.2.
R407C RCUG330 and 350AHYZ1
RCU330 and 350AHYZ1
R22
11,180(min.)
1,900
6,690 290
4,490 100(min.)
6,300 Air Side Heat Exchanger
4,200 Air Side Heat Exchanger
290 Air Discharge
P Earth Connection Terminal M10 1,950
150
Screw Type Compressor 1,950
2,100
No.1 Water Outlet 100
3,125
150
Earth Connection Terminal M10 1,950
No.1 Water Inlet
2,150
2,120
No.2 Water Inlet
2,090
160
500
71
Rigging Holes (8-φ50) Mounting Holes (14-φ26)
Water Inlet Temperature (With 142mm Inner 52.5 Diameter Frange)
1,950
No.2 Water Outlet
Air Inlet Electric Control Box
264 430
485
2,170
Air Inlet Water Outlet Temperature (With 142mm Inner Diameter Frange)
Fan
Wiring Hole for Power Supply
(1,945) 2,050
52.5
NOTES: 1. It should be surpport the water pipings properly to avoid its weight press on the unit directly. 2. These chillers consist of unit No.1 & No.2 and they are supplied separately when dispatched. 3. Water Flow For RCU(G)330,350AHYZ1: The chilled water flow rate is different between No.1 & No.2 unit. It is necessary to control the water quantity of each unit with adjusting valves (Field-Supplied). 4. It needs to field connect the control wiring between the No.1 & No.2. 5. In the No.2 unit, the data with the P mark is 300mm.
R407C RCUG360, 380 and 400AHYZ1
RCU360, 380 and 400AHYZ1
R22
13,280(min.)
1,900
6,590 290
6,590 100(min.)
6,300
290
6,300 Air Side Heat Exchanger
Air Side Heat Exchanger
Air Discharge
485 150
Earth Connection Terminal M10 1,950
Screw Type Compressor 1,950
2,100
2,150
150
Earth Connection Terminal M10 1,950
No.1 Water Inlet
2,100
No.2 Water Outlet 4,105
Water Inlet Temperature (With 142mm Inner Diameter Frange) 52.5
1,950
No.2 Water Inlet
2,150
160
500
100
No.1 Water Outlet 3,125 71
Air Inlet Electric Control Box Rigging Holes (8-φ50)
264 430
2,170
Air Inlet Water Outlet Temperature (With 142mm Inner Diameter Frange)
Wiring Hole for Power Supply
Fan
(1,945) 2,050
Mounting Holes (16-φ26) 52.5
NOTES: 1. It should be surpport the water pipings properly to avoid its weight press on the unit directly. 2. These chillers consist of unit No.1 & No.2 and they are supplied separately when dispatched. 3. Water Flow For RCU(G)360,400AHYZ1: It is necessary to control the same water quantity to each cooler. For RCU(G)380AHYZ1: The chilled water flow rate is different between No.1 & No.2 unit. It is necessary to control the water quantity of each unit with adjusting valves (Field-Supplied). 4. It needs to field connect the control wiring between the No.1 & No.2.
10