APPENDIX A: GROUP SIMULTANEOUS PULSE FEATURE

13.1

GROUP SIMULTANEOUS PULSE FEATURE

In some Industrial Installations it may be preferable to provide the ability to link multiple Energisers into a group. When linked the individual Z-Series devices become a “Group”. Members of a group have simultaneous high voltage output pulses and act as is they are one energiser with multiple outputs. This is designed so that no possible combination of individual outputs can be dangerous.

Appendix A: Group Simultaneous Pulse Feature

13.2

GROUP MODE PROGRAMMING (OPTION 26)

A group MUST have only 1 master. The other Energisers in the group are slaves. For the Z25 Energisers, if there is no Master, a Slave will display Error 4 on the Status LED when Armed and it will not electrify the fence. This is a requirement for Australian Standards. For every other Z-Series device, if there is no Master, each Slave will electrify the fence (pulses) when Armed. However, the simultaneous pulse feature will NOT be operating. NOTE:

1. Do not interconnect the energisers via the keypad bus until after they are programmed. 2. If more than one keypad is used, they will need different addresses (see “10.3.6 Changing the Keypad Messages and Address” on page 60. 3. If Perimeter Patrol is used any keypad in the system should not have address 2, (see “10.3.6 Changing the Keypad Messages and Address” on page 60). For all Energisers that will be part of a group, the procedure is as follows: 1. Make sure the key switch is turned off and IN1 isn’t shorted. 2. Connect the battery. 3. On the keypad, enter [Installer’s code] *, 0, #. 4. Enter 2, 6 followed by the required value (e.g. 1 for master) then #. 5. Enter *, # to exit programming.

Page 88