1 minute read
Adding external ZGP-Sensors
Purpose
To control a group or a zone with one sensor. external ZGP-sensors can be commissioned to a group or to a zone, consisting of lights with wireless drivers or lights with SNS410.
How to do?
See screenshots. When the sensor is added, you can choose to finish the process or assign lights to a daylight area, see page 28 for more explanation.
Remarks:
• You can add more than one sensor to a group or zone. • With ZGP-sensor the group size must not exceed 25 lights. • During commissioning of ZGP sensors (in test setups) the devices should not be too close to the lights (between 2m and 5m distance) to avoid commissioning failures. • In case ZGP-sensors are used for a group, and at the same time for zones of that group, the sensor(s) of the group must be added first.
Removing am external ZGP-sensor
A sensor can be removed by following the next steps:
When you remove a sensor, you must remove all sensors and switches in the group/zone. Additionally, you must reset the sensor if you want to reuse it.
Resetting an external ZGP-sensor
A sensor can be reset as indicated in the sensor manual. Usually there is a reset button that must be pressed for several seconds. This action is useful if, for instance, a sensor is still assigned to a group, but the group cannot be assessed.