Indeed - Design Guidelines

Page 1

Design Guidelines

Version 1.3 / 7.19.2017

Updates on pages 16,18,24,26,102,159


Indeed Design Guidelines Facilitate the design process and assist project teams in making informed decisions about how offices are planned, designed, renovated and constructed. The standards outlined in this document are not intended to rigidly prescribe space standards nor specifications, but instead to offer guidance and options.


Let’s design our offices to fit our needs and culture...

as well as our jobs fit the skillset of each hire.


Table of Contents what: Introduction

5–7

where: Design Guidelines

Introduction Statement of intent Who we are

8–18

Indeed around the world

Design Design drivers

Planning concepts Space types Programming Project process

19–63 Spaces Individual Team Community Support

64–167 Technical

General construction guidelines Architectural Furniture + finishes Graphics / Signage Lighting + acoustics Appliances + equipment Audio visual Network design Security Indeed Guidelines

4


Introduction what: Introduction where: Design Guidelines

In December of 2016, a series of meetings were held with different stakeholder groups to discuss the evolution of Indeed’s workplace and brand during the past ten years; with the intent to clarify a design direction for future office growth and expansion. Indeed’s real estate strategy must continue to anticipate the dynamic needs of Indeed employees, as well as new technological advances that will enhance the way work will be done in the future… while also reinforcing the unique brand and culture that drives Indeed’s success. This document provides an updated Global Design Guideline that synthesizes input from a diverse group of leaders and employees across Indeed’s organization. The goal is to standardize around big ideas, space sizes and ratios so that more energy can be spent in the design of unique workplace elements that reflect Indeed’s local culture. Offices should have a local approach and should be designed to create a workplace experience unique to each office. Be mindful of local regulations and code compliance during the design development process. Simultaneously, offices should reflect the global Indeed brand and values and ensure that our employees thrive in both sales and engineering offices. Passionate workers make the Indeed brand a powerful engine. This is a living document that will be updated as new practices and design concepts develop. These guidelines will continue to be refined over time.

Indeed Guidelines

5


Who We Are

what: Introduction where: Design Guidelines

It is critical that the workplace design reflects Indeed’s unique culture and mission.

As the world’s #1 job site, with over 200 million unique visitors every month from over 60 different countries, Indeed has become the catalyst for putting the world to work. Indeed is intensely passionate about delivering the right fit for every hire. Indeed helps companies of all sizes hire the best talent and offers the best opportunity for job seekers to get hired.

“Culture is strong because we have huge responsibility to help people find jobs: We’re purpose driven.”

We help people get jobs. Indeed Guidelines

6


Around the World what: Introduction where: Design Guidelines

As a global brand, it is important for Indeed’s workplace to be consistent across the globe, while also reflecting the unique local culture of each Indeed office.

“The environment is a recruitment tool. People get hooked by the mission and the energy in the work environment.”

The world needs talented people. Indeed Guidelines

7


Design

what: Design where: Design Guidelines

Indeed’s senior leadership team identified key factors that influence the success of the company, as well as key differentiators of the organization that bring people together. These elements can be expressed and enhanced within the design vocabulary of Indeed’s workplace, to provide a more vibrant environment that is both functional and inspiring. The focus must be on the employee experience and building a strong sense of community; a feeling of being at home. The aesthetic should be one of simplicity and cleanliness, and should reinforce Indeed’s mission to help people get jobs. Other key factors include: Indeed’s culture is not reactive… it is steadily evolving. Indeed wants to be a place where people choose to work based on the physical space, the community and the culture. Indeed wants to foster innovation and faster problem solving. Indeed wants to give employees choices in where they work, while ensuring visual connectivity to colleagues and team members.

“The office experience should propel us to come in everyday. It’s about the space, and the amenities – most importantly, the community.”

DESIGN DRIVERS 1. Connect people The office is a place for connecting people. Amenities should enhance employee wellbeing. Employees will come to our offices because they are inspired by what it has to offer. 2. Be transparent + open We want to see people and celebrate our culture by expressing openness throughout the office space. Reinforce the positive impact of Indeed’s work in other people’s lives. 3. Foster innovation Be supportive, allow for vulnerability. Space should inspire, connect people and provide opportunities for various types of interactions. 4. Live data Be data driven in how we make decisions about space. Celebrate and showcase data that is meaningful to us through digital walls, also showcasing activity across Indeed’s global locations. LOOK + FEEL DRIVERS 1. Human Raw - Warm - True To Materials - Comfortable - Cozy 2. Simple

“We are anti-hype. We are not flashy. We are substance, authentic, and true.”

Modern - Monochromatic - Narrow Palette - Sophisticated 3. Honest Clean - Bold- Proactive - Forward-Thinking - Tech - Relevant

“The space should feel exciting, and full of energy. We want it to be memorable.”

Indeed Guidelines

8


Design Drivers what: Design

``

Brand filters link the organization’s values to the personality and attributes of how Indeed wants to be perceived. They set the foundation for selecting a visual aesthetic and serve as a checks + balance system, ensuring an embedded consistency for the brand across all of its user touch-points.

where: Design Guidelines

FORWARD THINKING

TECHY OPENNESS & INCLUSION

INNOVATION

CORE VALUES RELEVANT

COMFORTABLE

TRANSPARENT

DATA DRIVEN

PUTTING THE JOB SEEKER FIRST

AUTHENTIC

TONE + PERSONALITY

NO NONSENSE

BOLD

DESIGN DRIVERS RSE

. C U LT U R E D . C U R A

TE

HUMAN

D

VE

DI

HONEST

ECLECTIC SIMPLE

Indeed Guidelines

9


Design Drivers what: Design where: Design Guidelines

BRAND

WORK

LIFESTYLE

THE WOW

THE ZONE

THE NODE

HONEST

SIMPLE

HUMAN

DESIGN VISION

ARCHITECTURAL EXPRESSION

RAW WARMTH TACTILE CONSCIOUS

ENTRY EXPERIENCE INTERACTIVE ENGAGING MESSAGING THE RIGHT AMOUNT OF LOCAL

SUBSTANCE BOLD MODERN PALETTE SLEEK

WORK PLACE HIGH ENERGY THE PRODUCT STANDARDS

LOCALIZED REPRESENTATION LIVELY EVOCATIVE COMFORTABLE/COZY

PANTRY COMMUNITY FLEXIBLE THE VIBE

Indeed Guidelines

10


Planning Concepts what: Design where: Design Guidelines

Point of Arrival

Distribute smaller open community spaces in the corners of the floor.

Locate enclosed support spaces in the interior of the plan near the core.

Locate most of the enclosed spaces in the interior of the floor along the core, with open spaces at the perimeter.

ior

Small community space

ior

Locate large community spaces in a central location near the Node.

Small team space

te r

Point of arrival

te r

Distribute small team spaces throughout the floor.

Small team space

Small community space

Ex

Individual workstations

i

il d

In

Locate individual workstations near the perimeter with access to natural light and views.

Small team space

il d

g

Small community space

Bu

ng

Individual workstations

Planning Guidelines •

Bu

in

The Node is a group of spaces that create convergence, and is one of the primary planning concepts within Indeed’s Design Guidelines. The combination of Community, Team and Support spaces form a Node of activity and convergence, which should be immediately accessible from the point of entry into the building/onto the floor.

Individual workstations

Support

Node (large community spaces)

Small community space

Node Path of Travel Indeed Guidelines

11


Planning Case Study - Single Floor what: Design where: Design Guidelines

London • Single level • Odd shape

Individual Team Community Support Core Node Path of Travel

Amsterdam • Single level • Basic shape Indeed Guidelines

12


Planning Case Study - Multi-Floor what: Design where: Design Guidelines

Toronto Floor 12 • Multi-level • Basic shape Individual • Typical floor Team

Toronto Floor 14

• Multi-level • Basic shape • Node floor

Community Support Core Node Path of Travel

Indeed Guidelines

13


Space Types what: Design

Indeed’s space is comprised of four zones.

Individual

Team

where: Design Guidelines

Personal work spaces: phone rooms, workstations, wellness rooms

Community

Spaces for 10+ people gatherings

Spaces for 2-9 people to collaborate: conference rooms, interview rooms, standing communal tables, white boards

Support

Spaces that support day-to-day office functions

Indeed Guidelines

14


Space Types what:

Within the four zones, Indeed’s kit of parts strives to provide variety in work settings to suit a range of activities.

Design where: Design Guidelines

Individual

Team

Community

Board room Phone rooms

7 Person conference room Workstations

5 Person conference room

Wellness room

Pantry

11 Person conference room

2 person Conference room Interview room

12-40 Person training room Game room

Indeed Guidelines

15


Space Types what: Design

Indeed’s approach to planning space is based on a kit of parts. In combination, these parts provide the functionality and variety that enables the Indeed workforce. The graphic below shows what is included in the kit of parts, including the space types, typical square footage, and planning ratio (how many to plan per person). Each of these space types is explained further in the Spaces Section. Note that square footage values for large Community spaces are variable based on the head count.

where: Design Guidelines

*

Space Type INDIVIDUAL Phone Rooms Workstations Wellness Room TEAM 2 Person Conference Room 5 Person Conference Room 7 Person Conference Room Standing Communal Tables Interview Room Whiteboards COMMUNITY Open Collaboration lounge 11 Person Conference Room Board Room 12-40 Person Training Room Medium Pantry Large Pantry Barista / Lounge Area Game Room Fitness Area Presentation Space Amphitheater Space SUPPORT Reception Area IT - IDF IT - MDF IT - Genius Bar IT Helpdesk Storage

Small

Medium

Large

1 1 0

X X X

X X X

X X X

60 : 1 25 : 1 60 : 1 200 : 1 350 : 1 30 : 1

3 5 7 8 4 0

X X X X X X

X X X X X X

X X X X X X

120 270 500 500 700 3000 300 300 1500 800 1500

40 : 1 200 : 1 1,000 : 1 200 : 1 150 : 1 150 : 1 200 : 1 250 : 1 1,000 : 1 800 : 1 800 : 1

6 11 22 25 0 0 0 0 0 0 0

X X

X X X X X X

X X X X X X X X X X X

500 120 1,000 700 270 200

1 per building 1 per floor 1 per building 1 per building 1 per building 1 per floor

12 0 0 24 2-3 0

Unit Net SF*

Planning Ratio

Seats Per Unit

35 30 80

40 : 1 1:1 250 : 1

96 126 156 0 100 0

Regus

<15,000 SF

X X X

15,00040,000 SF

X

X X X

X X X

X X X

X

X X

≥40,000 SF

X X X X X X

*Note: Net SF (NSF) represents the size of each room or workspace only, measured within the walls of each space, not the circulation between the rooms. In order to calculate the usable of the overall floor, a circulation factor will need to be applied of approximately 35%.

Indeed Guidelines

16


Programming where:

Indeed’s approach to planning space sets out a few key metrics that should be referenced in order to ensure that spaces are efficient, functional, and meet Indeed’s goals. Following the planning ratios for each space type should yield results within range of these targets. Note that there are different targets for planning a full site (including amenities and extra support) vs. a typical office floor within a site that already has amenities. Note that all target values are approximate based on current Indeed practices, and will be refined over time.

Design Guidelines

Target Efficiency for typical office floors

what: Design

Approximate Square Footage Per Person of Each Zone

~100 Usable SF / Person* 140

Target Efficiency for an entire site ~130 Usable SF / Person

120

Enclosed Collaboration space

100

Circulation

0.5 seats per person in enclosed rooms (falls within the Team and Community categories) 80

Open Collaboration space 0.4 seats per person in open areas (not including pantry, falls within the Team and Community categories)

60

40

*Note: Usable Square Footage (USF) includes all of the programmable interior space and circulation, but does not include the building core (stairs, mechanical rooms, elevators, shafts). This metric is used instead of Gross or Rentable Square Footage because it is more easily quantifiable by the design team, whereas other metrics are impacted by the landlord or base building. Rentable Square Footage varies by market but will always be higher than the USF.

20

SUPPORT 11

COMMUNITY 30

Circulation

SUPPORT 8 COMMUNITY 15

TEAM 10

TEAM 10

INDIVIDUAL 30

INDIVIDUAL 30

Guidelines NSF/Person for Whole Site

Guidelines NSF/Person for Typical Floor

0

Indeed Guidelines

17


Programming Template what: Design

Indeed has developed a programming template to use at the initiation of each new project. The template is intended to give the team a starting point for developing the primary space requirements. The space types, sizes, and quantities are the same as those that appear in this guidelines document, ensuring that each new project starts from the guidelines. Using the template ensures that Indeed’s goals for efficiency and functionality are met from the beginning.

where: Design Guidelines

Indeed Program Template Draft Input the head count for the project

Quantities and sizes of each space type will be automatically calculated based on the recommended ratios

The estimated total square footage or square meters for the project will be calculated based on the space requirements above

Type of Office: Headcount:

Space Type INDIVIDUAL Phone Rooms Bench Workstations Hex Workstations Wellness Room Subtotal TEAM 2 Person Conference Room 5 Person Conference Room 7 Person Conference Room Standing Communal Tables Interview Room Whiteboards Subtotal COMMUNITY Open Collaboration lounge Standing Communal Tables 11 Person Conference Room Board Room 12-40 Person Training Room Medium Pantry Large Pantry Barista / Lounge Area Game Room Fitness Area Presentation Space Amphitheater Space Subtotal SUPPORT Reception Area IT - IDF IT - MDF IT - Genius Bar IT Helpdesk Storage Subtotal Total NSF Circulation Total Usable SF Usable SF / Person Enclosed Collaboration Open Collaboration Total Collaboration

Tier: Scope:

Engineer (select) 500 (input)

Unit Net SF

Planning Ratio (based on headcount)

35 30 48 80

Tier 4 Entire Site

(automatically calculated) (select)

Quantity

Total SF

Seats Per Unit

Total Seats

40 : 1 1:1 1:1 250 : 1

13 500

455 15,000

1 1

13 500

2 515

160 15,615

0

0 513

96 126 156 120 100 0

60 : 1 25 : 1 60 : 1 200 : 1 350 : 1 30 : 1

8 20 8 3 1 17 57

768 2,520 1,248 360 100 0 4,996

3 5 7 8 4 0

24 100 56 24 4 0 208

Enclosed Enclosed Enclosed Open Enclosed Open

120 120 270 500 500 700 3000 300 300 1500 800 1500

40 : 1 200 : 1 200 : 1 1,000 : 1 200 : 1 150 : 1 500 : 1 200 : 1 250 : 1 1,000 : 1 800 : 1 800 : 1

13 3 3 1 3 3 1 3 2 1 1 1

1,560 360 810 500 1,500 2,100 3,000 900 600 1,500 800 1,500 15,130

8 8 11 22 25

104 24 33 22 75 0 0 0 0 0 0 0 258

Open Open Enclosed Enclosed Enclosed Open Open Open Open Enclosed Open Open

2

1,000 240 1,000 700 270 2,000 5,210 40,951 27,301 68,252 137

12

24

Open Enclosed Enclosed

0

0 24

500 120 1,000 700 270 200

300 : 1 1 per floor 1 per building 1 per building 1 per building 50 : 1

10

40%

0.65 seats per person 0.35 seats per person

0

Open or Enclosed Comments Enclosed Open Open Enclosed

0.42 seats per person Lounge area

0.52 seats per person

Open Enclosed

Open

327 seats 176 seats

Indeed benchmark = 0.6 Indeed benchmark = 0.4

Indeed Guidelines

18


Spaces

Individual Team Community

Best practices

Support

Conference Rooms are enclosed, private spaces for presentations and meetings. These rooms are intended for internal and external attendees. Best Practices •

Distribute small meeting rooms throughout the space. Provide small meeting spaces near heads-down workstation areas for quick unscheduled use, but provide adequate acoustic isolation. Any public-facing conference rooms need to have a visual privacy solution—the specific response (art glass, curtains, blinds, or motorized shades) can vary by location.

Community

12' - 0"

Support

3 4

glass wall w/ sliding door distraction banding fully obscuring view of TV screen

Look + Feel

6' - 0"

Magsafe Macbook charger

5' - 0"

IP phone w/ speaker

see section 1.6

GW

1

video conference speaker

3

2

Lighting provide an average lighting level range of 30-50 fc

4' - 0"

provide dimmable lighting and automated sensors

4' - 0"

carpet tile graphic wallcovering + whiteboard

Equipment dual or single wall display with Google hangouts

Performance Specifications

2

Power / Data

iPad-mini IT connection

Architecture

Community

1

7

4' - 0"

task chairs

Team

12' - 0"

A

8' - 0"

rectangular table with standing option

see section 1.1

4’4'-- 0" 0”

Furniture

Individual

A

6’6'-- 0” 0"

EQ

10’ 0” 10' -- 0"

EQ

Plan

see section 1.1

5 Person conference room

phone system

5 6

A see section 1.1 12' - 0"

7

EQ EQ

6' - 0"

5

6

Mac-Mini wireless keyboard and mouse

EQ

5' - 0"

7

iPad-mini at entry door

1 4' - 0"

Axon 12' - 0"

EQ

12' - 0"

“prosumer” USB camera

4

2

4' - 0"

4' - 0"

• Reception area • IT • Storage • Restrooms

27

Example: Detail Page

4' - 0"

Support

Indeed Guidelines

10' - 0"

• Open collaboration lounge • Standing communal tables • 11 person conference room • Board room • 12-40 person training room • Medium pantry • Large pantry • Barista / lounge area • Game room • Fitness area • Presentation space • Amphitheater space

3

Note : tags can be found in technical section Indeed Guidelines

28

4' - 7"

Indeed Guidelines

19

2' - 6"

• 2 person conference room • 5 person conference room • 7 person conference room • Interview room • White boards

5 Person conference room

7' - 0"

Team

Space description

6' - 0"

• Phone room • Workstation • Wellness room

Example: Intro Page

8' - 0"

Individual

4' - 0"

Design Guidelines

4' - 0"

where:

13' - 0"

Spaces

The following pages contain planning guidelines for each of the space types listed below. Each space is described in two pages: an intro page containing the planning intent and general principles and a detail page showing the specific layout and furniture of each room type. Key tags on the detail pages reference construction details found in the Technical Section. Please note that dimensions and specifications are primarily relevant to US locations. Conversion to metric and compliance with local codes shall be assured by the local architect on a project by project basis.

13' - 0"

what:


Individual

Private work space Personal work spaces

Team Community Support

Indeed Guidelines

20


Phone room Individual Team Community Support

Phone rooms are spaces that support individual work or private phone calls. These rooms are not reservable and are recommended for 30-minute time frame use. Best Practices • • •

Provide acoustic isolation from surrounding spaces. See Lighting + Acoustics Section of IT Design Standards for additional requirements. Locate Phone rooms in visible locations with glass fronts to discourage long-term use and ensure that rooms are made available to the entire office population.

Indeed Guidelines

21


5’ - 0” 5' - 0"

Phone room

A

Furniture

Individual

built-in work surface at table height or standing table 8' - 0"

soft chair

1

1

2

see section 1.6

Support

glass wall w/ hinged door or sliding door distraction banding

3 4

7’ - 0” 7' - 0"

Community

Architecture

A

GW

2

see section 1.1

5

3

Look + Feel carpet tile

5

graphic wallcovering

A

Equipment

see section 1.1

IP phone w/ built-in speakerphone 10' - 0"

Power / Data USB 5v power duplex power above counter

55' - 0"

data outlet above counter

Lighting

1

10' - 0"

recessed ceiling, wall mounted, or task lighting based on design intent

2

provide an average lighting level range of 30-50 fc

3

4

provide dimmable lighting and automated sensors 6' - 0"

Team

see section 1.1

Note : tags can be found in Technical Section Indeed Guidelines

22


Workstation Individual Team Community Support

Individual Workstations are used by all Indeed employees as their primary assigned work space. Workstations feature efficient storage and work surfaces. The placement of workstations should develop into neighborhoods which provide flexibility in heads down or collaborative work styles. Best Practices • • • • •

While it is not a current practice at Indeed, panel screens at the ends of workstation rows could be considered along major traffic aisles. Screen workstations appropriately for sightlines & acoustics adjacent to support. Workstations are located around the perimeter allowing for access to daylight and views. Workstations should be oriented to minimize circulation behind the employee’s back when seated. There should be a minimum of 7-8 feet clearance between desk rows.

Indeed Guidelines

23


Workstation Individual Team

tackable panel pedestal task chair

Community Support

work surface

Architecture Acoustic absorption above workstations in sales offices

Look + Feel carpet tile

Equipment single or dual monitor keyboard

1 2 3 4

Lighting locate workstations in proximity to windows (within 25’) for daylighting provide an average lighting level range of 30-50 fc

2’ 2'- -6” 6"

Furniture

4’4' --7"7”

2

provide ambient overhead lighting plus task lighting

1

to prevent glare, avoid direct light onto workstations

4

provide zoned controls for overhead ambient lighting maintain a recommended height of 9’-6” for all overhead lighting orient workstations to avoid glare from windows provide diffusers on overhead lighting

mouse

WORKSTATIONS & CONF. RM. docking station

2

Power / Data

1

data and power stub up for each workstation cluster, 1.5 cables per workstation (3 for every 2) 4+1 (4 power, 1data) for adjustable height (sit/stand) desks

4

PRESENTAT

3

Note : tags can be found in Technical Section Indeed Guidelines

24


Wellness room Individual Team Community Support

This room should be private, secure, and accommodating for multiple uses including nursing mothers, sick employees or short employee breaks. It should contain comfortable seating, a small table, and convenient power outlets. Best Practices • • • • • •

Refer to local regulations. In the United States it is required to provide a minimum of one per facility. Locate and configure the room for discrete entry and exit. Design with a warm residential look and feel in mind i.e. no white laminate millwork. This room may also be used as a prayer room. Design team to confirm with Indeed HR for Wellness Room requirements on each floor. Provide door access control with privacy indicator (with override access).

Indeed Guidelines

25


see section 1.1

D

Wellness room Individual Team Community Support

Furniture recliner with ottoman* side table storage cabinets dimmable lamp

1 2 3

3 9

Lighting provide an average lighting level range of 30-50 fc

8

A

provide dimmable lighting and automated sensors

throw pillow

2

throw blanket

Architecture solid (non-glass) door with lockable hardware set with occupancy indicator deadbolt and exterior key override

3

see section 1.1

1

4

4

A

1

see section 1.3

see section 1.1

Look + Feel carpet tile graphic wallcovering mirror

Equipment trash receptacle bluetooth speakers for music under counter fridge sink ambient sound machine storage for supplies

5 6 7 8 9

DESIGN GUIDELINES INDEED 4

5

6

7

Power / Data duplex power audio via bluetooth data outlet

*Sofa option also available

Note : tags can be found in Technical Section Indeed Guidelines

26


Individual Team

Spaces for 2-9 people to collaborate

Community Support

Indeed Guidelines

27


2 Person conference room Individual Team

Conference rooms are enclosed, private spaces for presentations and meetings. These rooms are intended for internal and external participants. Best Practices •

Community Support

The configuration of the 2 Person conference room should allow both people to face the TV wall in order to engage in video conferencing but also provide enough space to allow the occupants to face each other. Distribute small meeting rooms throughout the space. Provide small meeting spaces near heads-down workstation areas for quick unscheduled use, and provide adequate acoustic isolation. Any public-facing conference rooms need to have a visual privacy solution—the specific response (art glass, curtains, blinds, or motorized shades) can vary by location. See Lighting + Acoustics Section of IT Design Standards for additional requirements.

Indeed Guidelines

28


6' - 0"

2 Person room - Option A

12’ 12' --0"0”

see section 1.1

Individual

task chairs 10' - 6"

Architecture

Community

3

glass wall w/ hinge door without closer

4

distraction banding fully obscuring view of TV screen 4' - 0"

Support

Magsafe Macbook 2 charger

1

USB-C charger IP phone w/ speaker video conference speaker iPad-mini IT connection

see section 1.6

2

GW

7

data outlet

6

Lighting Look + Feel carpet tile graphic wallcovering + whiteboard 12' - 0"

Equipment EQ

dual or single wall display with Google hangouts

5 6 7

3

provide an average lighting level range of 30-50 fc

A

provide dimmable lighting and automated sensors

see section 1.1

10' - 0"

EQ

phone system “prosumer” USB camera Mac-Mini wireless keyboard and mouse

7

10' - 0"

10' - 0"

iPad-mini at entry door

4' - 0"

5

1 6

2

4

3' - 6"

Team

1 2

bar-type work surface

A

5

A

Power / Data

8’ -8' 0” - 0"

Furniture

see section 1.1

3 Note : tags can be found in Technical Section Indeed Guidelines

29


4' - 0"

12' - 0"

2 Person room - Option B EQ

Team Community Support

1 2

round table task chairs

Architecture

4

distraction banding fully obscuring view of TV screen

4' - 0"

carpet tile

5 6

graphic wallcovering + whiteboard

Equipment dual or single wall display with Google hangouts

5

IP phone w/ speaker video conference speaker iPad-mini IT connection

see section 1.6

GW

2

USB-C charger

3

glass wall w/ hinge door without closer

A

Magsafe Macbook 2 charger

4' - 0"

Look + Feel

N GUIDELINES D

Power / Data

10’ -10'0” - 0"

Individual

Furniture

3

1

7

data outlet 3' - 6"

6' - 0"

A

see section 1.1

10' - 0"

12' - 0"

see section 1.1 10’ 10' -- 0"0”

EQ

6

Lighting provide an average lighting level range of 30-50 fc

A

provide dimmable lighting and automated sensors

see section 1.1

7

phone system “prosumer” USB camera Mac-Mini wireless keyboard and mouse

7

iPad-mini at entry door

6

5 1

2

4

3

WORKSTATIONS & CONF. RM.

Note : tags can be found in Technical Section Indeed Guidelines

30


5 Person conference room Individual Team Community Support

Conference rooms are enclosed, private spaces for presentations and meetings. These rooms are intended for internal and external attendees. Best Practices •

• •

Distribute small meeting rooms throughout the space. Provide small meeting spaces near heads-down workstation areas for quick unscheduled use, and provide adequate acoustic isolation. Any public-facing conference rooms need to have a visual privacy solution—the specific response (art glass, curtains, blinds, or motorized shades) can vary by location. See Lighting + Acoustics Section of IT Design Standards for additional requirements. Coordinate all MEP/FP services with engineer for optimal layout (e.g avoiding air returns adjacent to door).

Indeed Guidelines

31


12' - 0"

see section 1.1

5 Person conference room

task chairs

13' - 0"

3 4

glass wall w/ hinge door without closer distraction banding fully obscuring view of TV screen

Magsafe Macbook 2 charger USB-C charger

4' - 0"

carpet tile

Equipment

5 6

GW

6

3

2

data outlet

5

provide an average lighting level range of 30-50 fc

Look + Feel graphic wallcovering + whiteboard

iPad-mini IT connection

see section 1.6

1

IP phone w/ speaker

Lighting

4' - 0"

provide dimmable lighting and automated sensors

A see section 1.1 12' - 0"

dual or single wall display with Google hangouts phone system

7

EQ

EQ

12' - 0"

6' - 0" “prosumer” USB camera

6

Mac-Mini wireless keyboard and mouse

7 1

5 4' - 0"

4

2 3' - 6"

10' - 0"

iPad-mini at entry door

13' - 0"

3

Note : tags can be found in Technical Section Indeed Guidelines 4' - 0"

Support

Power / Data

video conference speaker

Architecture

Community

2

7

- 0”

Team

1

A

4' -4’ 0"

rectangular table with standing option

see section 1.1

6”

Furniture

Individual

A

EQ

10’- 6"10'

EQ

6’6'-- 0” 0"

32


7 Person conference room Individual Team

Conference rooms are enclosed, private spaces for presentations and meetings. These rooms are intended for internal and external attendees. Best Practices •

Community Support

Distribute small meeting rooms throughout the space. Provide small meeting spaces near heads-down workstation areas for quick unscheduled use, and provide adequate acoustic isolation. Any public-facing conference rooms need to have a visual privacy solution—the specific response (art glass, curtains, blinds, or motorized shades) can vary by location. See Lighting + Acoustics Section of IT Design Standards for additional requirements.

Indeed Guidelines

33


7 Person conference room

Community Support

task chairs

Architecture glass wall w/ hinge door without closer distraction banding fully obscuring view of TV screen

1 2

graphic wallcovering + whiteboard

Equipment dual or single wall display with Google hangouts

7

A

Magsafe Macbook 2 charger USB-C charger IP phone w/ speaker

3 4

iPad-mini IT connection data outlet

GW

6

3

Lighting provide an average lighting level range of 30-50 fc

5 6

see section 1.6

1

video conference speaker

Look + Feel carpet tile

see section 1.1

4’4' --0"0”

Team

rectangular table with standing option

Power / Data

A

6’6' --0"0”

13’13' -- 0"0”

Individual

Furniture

see section 1.1

12’ 12' --0"0”

2 5

provide dimmable lighting and automated sensors

A see section 1.1

7

phone system “prosumer” USB camera

6

Mac-Mini wireless keyboard and mouse

7

iPad-mini at entry door

1

5

4

2 3 DESIGN GUIDELINES INDEED

Note : tags can be found in Technical Section Indeed Guidelines

34


Interview room Interview rooms are small, public meeting spaces for 4-6 people, intended for interviewing candidates.

Individual

Best Practices for Sales Office Interview room

Team

Community

Locate the interview room adjacent to Reception for visitors. 4-5 people at a round table is typical.

Support Best Practices for Engineering Office Interview room • • • •

Locate the Interview room adjacent to Reception for visitors. 4-6 people at a round table is typical. Ensure whiteboard has enough space in front for people to stand. Some engineering offices may require dual screens in the Interview room.

See Lighting + Acoustics Section of IT Design Standards for additional requirements.

Indeed Guidelines

35


10’ 10' - -0"0”

Interview room

see section 1.1 5’ - 5'0”- 0"

5’5' -- 0"0”

A

see section 1.1

Team Community Support

round table soft chairs

Architecture glass wall w/ hinge door without closer distraction banding fully obscuring view of TV screen

1 2

Lighting provide an average lighting level range of 30-50 fc

7

A

provide dimmable lighting and automated sensors

3 4

10’ - 0”

Individual

Furniture

6

5

see section 1.1

1

A 2

Look + Feel carpet tile graphic wallcovering + whiteboard

5 6

4

3

GW

Equipment

see section 1.6

IP phone w/ speaker video conference speaker “prosumer” USB camera wall mounted display* Mac-mini w/ keyboard and mouse

7 6

iPad-mini at entry door

7

Power / Data convenient tabletop duplex power Magsafe Macbook 2 charger USB-C charger convenient USB

3

1 4

2

5

data outlet

*Some engineering offices may require dual screens in the Interview room.

Note : tags can be found in Technical Section Indeed Guidelines

36


Whiteboards Individual Team Community Support

Whiteboards are visual communication tools allowing the user to write and erase content quickly without the use of technology, intended for both short-term brainstorming sessions and long term task management. Best Practices • •

Provide whiteboards in all meeting rooms and throughout the open work area in Sales offices. Develop clear policies for cleaning and erasing the boards to ensure that content is not lost unintentionally and that boards remain available for use.

Furniture soft mobile seating

Architecture pen and eraser storage

Look + Feel wallcovering

Equipment n/a

Power / Data adjacent duplex power convenient USB

Lighting provide indirect lighting in Whiteboard areas to minimize glare.

Indeed Guidelines

37


Individual Team Community

Spaces for 10 + people gatherings

Support

Indeed Guidelines

38


Open collaboration lounge Individual Team Community Support

Open informal collaboration area for small groups located between neighborhoods, near service centers, pantry areas, etc. to encourage casual collisions. This space is not reservable. Best Practices • • • •

Locate within the open plan areas in a balanced mix of Workstations, Phone Rooms, 3-5 Person Conference Rooms, etc. Provide adequate separation and zoning to prevent noise distraction to nearby work areas. Locate near windows for optimum daylight. Provide visual and acoustic separation from open workstations. Do not locate immediately adjacent to workstations.

Standing communal tables Standing Communal Tables are provided as open informal collaboration spaces between Individual work areas. Best Practices •

Confirm usage with local office prior to inclusion in the project.

Indeed Guidelines

39


Open collaboration lounge Individual Team Community Support

Furniture lounge chairs sofa coffee table side chairs

1 2 3 4

Equipment wall mounted display speakers

6

Architecture acoustical treatment open layout built-in storage

5

Look + Feel hard floor + area rugs large feature graphic

Power / Data

6

local cable local audio convenient duplex power convenient USB ports

5

3

data outlet

Lighting

4

1 2

decorative lighting unique lighting differentiates these areas from general workstation zones provide an average lighting level range of 30-50 fc

Indeed Guidelines

40


11 Person conference room Individual Team

11 Person conference rooms are enclosed spaces for team meetings that accommodate over 10 people, typically shared by multiple departments. Best Practices •

Community Support

Locate along primary circulation in the Node; can be located on the core of the building or exterior window wall, but daylight access should be prioritized for open workstation areas. Provide sufficient acoustic performance and presentation technology. See Lighting + Acoustics Section of IT Design Standards for additional requirements.

Indeed Guidelines

41


21' - 6"

11 Person conference room

see section 1.1

9' - 0"

Support

2

glass wall w/ hinge door without closer

3

distraction banding fully obscuring view of TV screen

4

7' - 0"

iPad-mini IT connection data outlet

6

5 6

graphic wallcovering + whiteboard

Equipment dual or single wall display with Google hangouts

7

3

Lighting provide dimming for all fixtures

carpet tile

GW

1

IP phone w/ speaker

task lighting

Look + Feel

36' - 1 1/16"

USB-C charger video conference speaker

Architecture

see section 1.6

Magsafe Macbook 2 charger

2

5’5' --0" 0”

Community

task chairs

1

7

A

5' - 0"

19’19' --0" 0”

Team

5' - 0"

Power / Data

rectangular table with standing option

A

7’7' --0" 0”

4' - 0"

Individual

Furniture

see section 1.1

14’14' -- 0"0”

if video is being considered, required typical average light levels of 40-50 foot candles (430-540 Lux), dimmable to 20-25 foot candles (215-270 Lux) when not in use (horizontal FC at a typical work-plane of 30” (76 cm) A.F.F.).

5 14' - 0"

EQ

EQ

A see section 1.1

phone system “prosumer” USB camera

6

Mac-Mini wireless keyboard and mouse 19' - 0"

iPad-mini at entry door

5' - 0"

5

Zoned lighting, AV, and speaker/microphone systems to be determined on a case by case basis.

CONF. ROOM & GAME ROOM

1 2

5' - 0"

4

5' - 0"

microphones

DESIGN GUIDELINES INDEED

7

3 PRESENTATION

Note : tags can be found in Technical Section Indeed Guidelines

42


Board room The Board room is an enclosed meeting space for large formal group meetings.

Individual

Best Practices

Team

Community Support

• • • •

Locate on the same floor as Reception for easy access by outside visitors. Provide pre-function space for meeting attendees to gather and wait before/after scheduled meetings. Provide refreshments nearby. Accommodate 20-25 seats. Increased acoustical privacy - See Lighting + Acoustics Section of IT Design Standards for additional requirements.

Indeed Guidelines

43


see section 1.1

A

36’

see section 1.1

Board room

side benches

Architecture glass wall w/ hinge door without closer distraction banding

5 6

dual wall display

Look + Feel carpet tile graphic wallcovering + whiteboard

Power / Data

wonkavision monitor if possible

7 8

phone system “prosumer” USB camera Mac-Mini wireless keyboard and mouse iPad-mini at entry door

touch panel

video conference speaker

audio amp

iPad-mini IT connection

speakers

local cable

mini fridge

see section 1.1

5

B

9

6

see section 1.3

3

A

GW

see section 1.6

see section 1.1

4' - 0"

10

10 19' - 0"

tie into IDF room 5' - 0"

5' - 0"

1

2

5' - 0"

7 19' - 0"

6

14' - 0"

14' - 0"

8

9 3

7' - 0"

data outlet

4 EQ

power outlets and AV connection in table

EQ

PRESENTATION

Zoned lighting, AV, and speaker/microphone systems to be determined on a case by case basis.

3

5

21' - 6"

DSP

IP phone w/ speaker

9

1

5' - 0"

microphones

USB-C charger

3

10

5' - 0"

Magsafe Macbook 2 charger

5

1

if video is being considered, required typical average light levels of 40-50 foot candles (430-540 Lux), dimmable to 20-25 foot candles (215-270 Lux) when not in use (horizontal FC at a typical work-plane of 30” (76 cm) A.F.F.).

Equipment

3

4

2

5' - 0"

provide dimming for all fixtures

CONF. ROOM & GAME ROOM

Support

credenza

1 2 3 4

5’ - 0”

7' - 0"

Community

task chairs

Lighting

see section 1.3

9' - 0"

Team

large formal table

4

A

DESIGN GUIDELINES INDEED

Individual

Furniture

D

36' - 1 1/16"

5 Note : tags can be found in Technical Section Indeed Guidelines

44


12-40 Person training room Individual Team Community Support

The 12-40 Person training room functions as a meeting, lecture, and training space. Movable tables and chairs offer a variety of configurations to accommodate many activities. Best Practices • • • •

Provide flexible furniture solutions for multiple room configurations. Provide adequate acoustic and visual separation from heads-down work spaces. Provide pre-function space for meeting attendees to gather and wait before/after scheduled meetings. Provide white boards on all non-glazed walls if possible.

Indeed Guidelines

45


see section 1.1

A

21’ - 6” 21' - 6"

12-40 Person training room

Support

podium 9' - 0"

8

4' - 0"

2

A

wonkavision monitor if possible speakers wireless mics

4’ - 0”

see section 1.1

8

7' - 0"

whiteboards on all available walls glass wall w/ hinge door without closer distraction banding

4 5 6

“prosumer” video camera audio amp touch panel

see section 1.6

Look + Feel

see section 1.1

GW

speakers mixing board

storage

7

1

Mac-mini

Architecture

5' - 0"

19' - 0"

stacking and/or folding chairs

2 presentation monitors or dual projection system

5’ - 0”

5

A

Power / Data

carpet tile

7

graphic wallcovering dimmable lighting

HDMI input plate 2 audio inputs data outlet

Lighting provide dimming for all fixtures if video is being considered, required typical average light levels of 40-50 foot candles (430-540 Lux), dimmable to 20-25 foot candles (215270 Lux) when not in use (horizontal FC at a typical work-plane of 30” (76 cm) A.F.F.)

8

3

DESIGN GUIDELINES INDEED

5

6

1

2

4

19' - 0"

Community

1 2 3

5' - 0"

5' - 0"

Team

Equipment

standing+folding / stacking tables

5’ - 0”

36' - 1 1/16"

Individual

Furniture

3

7

CONF. ROOM & GAME ROOM

Note : tags can be found in Technical Section Indeed Guidelines

46


Medium pantry Individual Team Community Support

The Medium pantry is essential to Indeed’s workplace culture. It provides the refreshments that are considered a critical benefit at Indeed, as well as basic services such as refrigeration, vending, coffee, and sinks. A variety of seating styles and furniture configurations are provided for eating, collaboration or a touchdown space for visitors and staff. Best Practices • • • • • •

Locate the Medium pantry within the floor Node, along with other activity-generating spaces. Provide one Medium pantry per office floor. Provide pull-out drawer bins for snacks with clear glass or plexi fronts. Mix open and closed shelving. Open shelving should be the appropriate height to access commonly used items. Locate lockable storage room with access control adjacent to Medium Pantry.

Indeed Guidelines

47


see section 1.1

Medium pantry Individual Team Community Support

Furniture built in seating loose tables mobile chairs stools at island

A 1 2 3 4

storage for utensils, plates, bowls cups, mugs

local audio wonkavision monitor if possible

A

3

5' - 0"

2

6 DW

4

convenient USB ports

2 double door glass fridges

storage for vending service consult with local vendor

1 double sink

built-in waste, recycling, compost binsDESIGN GUIDELINES INDEED serving counter top island

5 6

1 under counter fridge 1 water system

5

D

6

8

1

convenient duplex power

Equipment

snack storage

pull out drawer bins for snacks

see section 1.1

local cable

1

5’ - 0”

card reader for storage room

Architecture

napkin dispensers

Power / Data

see section 1.1

see section 1.2

2

7

6 5

6 see section 1.1

A

7 8

RECEPTION & PANTRY

PRESENTATION

1 coffee brewer 1 coffee grinder 1 espresso machine 1 ice maker

Look + Feel hard flooring large feature graphic

Lighting provide an average lighting level range of 30-50 fc provide a mix of daylight, ambient lighting, and feature pendant lighting in seating and dining spaces.

1 microwave 1-2 commercial dishwashers 1 single stainless fridge 1 toaster 1 blender

3

2

1 4

8 6

7

provide lower levels of artificial lighting in the dining seating area than in the food preparation area. locate the seating area near windows for daylight.

Note : tags can be found in Technical Section Indeed Guidelines

48


Large pantry Individual Team Community Support

The Large pantry is a larger food service amenity than the Medium pantry. It includes more equipment and provides seating for a larger population than the Medium pantry. The Large pantry is an essential amenity at larger Indeed sites. It provides the refreshments that are considered a critical benefit at Indeed, as well as basic services such as refrigeration, vending, coffee, and sinks. In large sites, one floor may have a Large pantry serving as the primary food service space, while other floors would have Medium pantries. Best Practices •

• • • •

Provide acoustic, visual, and odor separation from heads-down work area - See Lighting + Acoustics Section of IT Design Standards for additional requirements. Locate the Large pantry within the primary site Node, along with other activity-generating spaces. Mix open and closed shelving. Open shelving should be the appropriate height to access commonly used items. Locate lockable storage room with access control adjacent to Large pantry.

Indeed Guidelines

49


Large pantry Individual Team Community Support

Furniture

Power / Data

built in seating

Magsafe Macbook 2 charger

loose tables

USB-C charger

mobile chairs

local cable

stools at island

local audio convenient duplex power

Architecture

convenient USB ports

storage for utensils, plates, bowls cups, mugs

card reader for storage room

snack storage storage for vending service consult with local vendor built-in waste, recycling, compost bins 2-3 serving counter top island napkin dispensers pull out drawers bins for snacks lockable storage closet

Look + Feel hard flooring large feature graphic

Equipment 3 double door glass fridges 1 double sink 2 under counter fridge 1 water system 2 coffee brewer 1 coffee grinder 1 espresso machine 1 ice maker 2 microwave 2-3 commercial dishwashers 2 single stainless fridge

Lighting

1 toaster

provide an average lighting level range of 30-50 fc

1-2 projectors*

Provide feature lighting to match the site’s design concept. provide lower levels of artificial lighting in the dining seating area than in the food preparation area. locate the seating area near windows for daylight.

1 blender wonkavision monitor if possible

*Projector quantity based on pantry size Indeed Guidelines

50


Barista / lounge area Individual Team Community Support

The Barista / lounge area is a coffee bar and lounge space providing coffee service and informal meeting space. Best Practices • • •

Provide acoustic, visual, and odor separation from heads-down work area. Provide touchdown spaces and outlets to encourage coffee-bar style work. Locate lockable storage room with access control adjacent to Barista / lounge area. Furniture

Power / Data

n/a

local cable local audio

Architecture

convenient duplex power

storage

convenient USB

large counter area

card reader for storage room

Look + Feel

Lighting

hard flooring large feature graphic feature lighting

Equipment

provide a mix of lighting types and levels to simulate a lounge environment provide feature lighting to match the site’s design concept

espresso machine dishwasher under counter fridges sink speakers wonkavision monitor if possible

Indeed Guidelines

51


Game room Individual Team Community Support

The Game room is a separate space within the Node that is allocated for games and entertainment. Consider ping-pong, billiards, TV, or video games. Take local culture into consideration. The Game room should help our employees take a complete break from work before refocusing on the task at hand. Best Practices •

Provide acoustic and visual separation from the heads-down Individual work areas to minimize distraction.

Indeed Guidelines

52


36' - 1 1/16"

Game room see section 1.1

Community Support

sofa soft mobile stools coffee table side chairs gaming furniture

Architecture built-in storage

1 2 3 4 5 6

1

B

3 see section 1.1

4

8

2

6

7

B

19' - 0"

Team

lounge chairs

5' - 0"

Individual

Furniture

5

7

Look + Feel hard flooring + area rugs

DESIGN GUIDELINES

largeINDEED feature graphic

CONF. ROOM & GAME ROOM

feature lighting

Equipment wall mounted display speakers

Power / Data local cable

8

8 7

4

local audio convenient duplex power: wall outlets and floor boxes adjacent to freestanding furniture convenient USB

5

1 2

6

3

data outlet

Lighting provide an average lighting level range of 30-50 fc

Note : tags can be found in Technical Section Indeed Guidelines

53


Fitness area Individual Team Community Support

The Fitness area is an amenity space that provides employees with a place to exercise on site at the Indeed facility. The space includes exercise equipment and open multi-purpose floor space for a variety of physical activities. If the Indeed location is not large enough to warrant a designated fitness area, accommodate group fitness classes such as yoga in the café node or other areas. Best Practices • • • • • •

The Fitness area should include changing and shower facilities. Lockers should be large enough to hold a backpack and/or gym bag. Locate the Fitness area away from heads-down Individual work spaces and away from public-facing amenity areas. Provide acoustic and visual privacy for spaces on the same floor, as well as those above and below. Ensure that space is monitored in some way to prevent injury. Provide door access control.

Indeed Guidelines

54


Fitness area Individual Team Community Support

Furniture exercise equipment TBD by local office

Architecture resilient surfaces storage

Look + Feel resilient flooring large feature graphic bright lighting

Equipment wonkavision monitor if possible speakers charging station refrigerator card reader

Power / Data local cable to exercise equipment or wonkavision local audio convenient duplex power convenient USB

Lighting indirect up-lighting TBD

Indeed Guidelines

55


Presentation space Individual Team Community Support

The Presentation space is an open multi-purpose area for presenting to large groups. It includes AV for sharing content. It may be included as part of other large Community spaces. Best Practices • • •

Locate the Presentation space in the Node adjacent to other activity-generating spaces. If the project does not have designated presentation space, casual presentations can take place in the pantry areas. The presentation space can be fully open, partially enclosed, or fully enclosed. Enclosure of the presentation space needs to be evaluated on a case by case basis.

Amphitheater space The Amphitheater is an expanded, enlarged version of the Presentation space, including stadium-style seating for larger group presentations. Best Practices •

Accommodate stadium seating with appropriate ceiling height.

See Lighting + Acoustics Section of IT Design Standards for additional requirements. Indeed Guidelines

56


Presentation space Individual Team

Furniture

Lighting

stackable / mobile chairs

provide dimmable specialty lighting, zoned separately for the seating area vs the stage/ presentation area.

podium

Architecture

Community

large open space

Support

storage

elevated stage area

Look + Feel carpet tile large feature graphic dimmable lighting

Equipment branded podium wireless mics speakers high-lumen projectors multiple large screens “prosumer” video camera mixing board audio amp

Power / Data tie to IDF closet HDMI input plate 1 HDMI output plate data outlet

Indeed Guidelines

57


Individual Team Community Support

Spaces that support day-to-day office functions

Indeed Guidelines

58


Reception area Individual Team Community Support

Reception is typically the first point of contact and welcome area for anyone entering the workspace. The design should be an expression of the local culture and typically will have an Indeed logo. Note that not all lobby spaces will be multifunctional. Best Practices • • • •

Locate Reception off of the main elevator lobby, with refreshments and waiting area immediately adjacent. There should be a physical barrier between the elevator lobby and Reception area. There should be 1 staffed Reception per building. Door release button located at Reception desk required for entrance doors.

Indeed Guidelines

59


see section 1.1

Reception area

Team Community Support

Power / Data

assorted lounge furniture depending on space

door release button under reception desk

task chair credenza

Architecture reception desk with view of entry lockable storage behind desk* coat storage

1 2 3 4 5 6 7

Look + Feel hard flooring + area rugs large indeed logo

8

local cable

see section 1.2

see section 1.1

local audio

B

convenient duplex power convenient USB

6 3 5 4 5

8

11

7

data outlet

iPad for sign in wall display

under counter fridge

4

5 1 9

2

Lighting Provide an average lighting level range of 30-50 fc

5' - 0"

Provide feature lighting to match the site’s design concept.

DW

9

6

10

speakers water system

6 10

feature lighting

Equipment

5

6

5' - 0"

Furniture

area rug

6

10' - 0"

5' - 0"

Individual

see section 1.2

B

11

DESIGN GUIDELINES INDEED

*In smaller offices (1-100 people) - lockable storage credenza may take the place of storage room

7

8 11

3

9

5

10

RECEPTION & PANTRY

2

1

4

PRESENTATION

Security: For security protocol reference the Security Section in Technical Section Note : tags can be found in Technical Section Indeed Guidelines

60


IT IT spaces ensure high connectivity and accessibility to in-person IT support for Indeed employees.

Individual Team Community Support

IT Help Desk • Need for IT Help Desk arises when sites reach 150 people • When sites reach 300, IT Help Desk requires separate staging area that includes 8’ bench with power & storage • Walk up desk/counter for 2-3 IT people to sit behind • Lockable with access card • Seating for employees coming for help • Adjacent storage for extra IT parts • Outlets and USB ports for employees when waiting • Indeed to revisit IT Help Desk storage adjacent to help area vs. designated storage elsewhere IT Genius Bar • Need for IT Genius Bar arises when sites reach 600-700 people • Room with 24 workstations and built-in storage cabinets • Open window with counter for people to walk up and get help • Lockable with access card • Lounge area with tall tables and stools, similar to retail environment • Indeed to revisit IT Help Desk storage adjacent to help area vs. designated storage elsewhere • Typically located on an amenities floor IT Storage • 1 storage closet per floor • Lockable with access card • Access control • Movable cart for AV equipment MDF Closet* • 10’x12’ typical, 1 per building • Lockable with access card IDF Closet* • 10’x12’ typical • 1 per floor • Lockable with access card

*MDF/IDF size to be confirmed on a case by case basis

Indeed Guidelines

61


Storage* Individual Team Community Support

HR Storage • Consult with local teams regarding needs • HR can be with Facilities but Marketing to be separate • Access control Office Manager Storage/ Facilities Storage • 1 lockable storage closet per floor preferably in ‘back-of house’ location • Access control Marketing Storage • Consult with local teams regarding needs • Access control Coat Storage • One closet or built-in rack per floor, or multiple based on seating Printing Stations • Locate centrally • Counter for printer - coordinate equipment height • Shredder • Shelving/cabinet storage for office supplies, printer paper, etc. • Waste/recycling bin Office Supply Station • 1 per floor • Ideally paired with printer locations Badge Printing Station • Details TBD

*Storage size and location to be confirmed on a case by case basis. General intention for locating storage is in the core. Indeed Guidelines

62


Restrooms Individual Team Community Support

Restrooms are generally provided in the base-building design to local code. Single-occupant restrooms need to be reviewed on a case by case basis.

Multiple-occupant restroom

Single-occupant restroom • HR directive is one gender neutral bathroom per floor. • In smaller offices, a ratio of 1:200 for single occupant restrooms should be sufficient. • ADA restrooms can double as gender neutral restrooms. • Finishes should comply with base building standards.

Indeed Guidelines

63


Technical what: Technical

Section 0

Construction Guidelines

where:

Section 1

Architectural

Design Guidelines

Section 2

Wall types

1.1

Millwork details

1.2

Door Details

1.3

Ceiling Details

1.4

Acoustical Details

1.5

Demountable partitions

1.6

Furniture + Finishes Furniture

2.1

Finishes

2.2

Section 3

Graphics / Signage

Section 4

Lighting + Acoustics

Section 5

Appliances

Section 6

Audio Visual Guidelines

Section 7

Network Design Guidelines

Section 8

Security Guidelines

Back Indeed Guidelines

64


Construction Guidelines

FACILITY SPACE SPECIFICATIONS The design and construction of each office location must comply with the building codes and supplemental requirements (ie: energy codes, accessibility guidelines, etc.) as applicable within the local jurisdiction. In addition, the Landlord’s requirements for construction methodologies and procedures must be strictly adhered to. Beyond those requirements, the following technical guidelines have been established for new construction projects to ensure uniformity of function and consistency of quality throughout Indeed’s global offices. For renovation projects that may include the expansion of an existing facility, consideration must be given to matching the existing construction standards of adjacent areas to remain. Coordinate also with detailed written construction specifications in compliance with CSI or similar formatting as regionally standardized.

what: Technical where: Design Guidelines

1. DRYWALL CONSTRUCTION • Partitions shall be full height constructed of 3 5/8” metal studs with one layer of 5/8” gypsum board on both sides with batt insulation unless noted otherwise. • Construction shall comply with ASTM C645-83, utilizing twenty (20) gauge, screw type “Cee” studs, maximum spacing shall be sixteen (16) inches on center. Studs for all demising wall partitions shall extend to structure above/slab to slab. • Per code, provide appropriate thickness of gypsum board where required to achieve required fire rating for demising partitions and interior exit corridors. • Provide water resistant type gypsum board in all toilets, pantries, and similar spaces. Provide cement board at all tiled restroom walls. • Stapling of trim or gypsum board shall not be permitted. Plastic edge trim shall not be permitted. • Provide fiberglass insulation in the following wall assemblies for sound acoustics: conference rooms, training rooms, assembly areas, kitchenettes, pantries, copy rooms, print rooms, and other space as deemed necessary. • Exterior walls to be furred and insulated, where required by project scope. 2. PAINTING • Two (2) coats (one coat primer, one coat paint) of latex paint on drywall, plaster, and exposed masonry and concrete surfaces. Provide back filler for masonry. • Two (2) coat application of alkyd enamel on hollow and ferrous metals and solid wood trim.

Back

3. CARPETING • Carpeting shall be carpet tiles: • Installation: a. Trowelable Leveling and Patching Compounds: Latex-modified, hydraulic-cement-based formulation provided or recommended by carpet tile manufacturer. b. Adhesives: Water-resistant, mildew-resistant, nonstaining, pressure-sensitive type to suit products and subfloor conditions indicated, that complies with flammability requirements for installed carpet tile and is recommended by carpet tile manufacturer for releasable installation. Indeed Guidelines

65


Construction Guidelines •

Adhesives shall comply with the testing and product requirements of the California Department of Health Services’ “Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers.” • Adhesives shall have a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). c. Metal Edge/Transition Strips: Extruded aluminum with mill finish of profile and width shown, of height required to protect exposed edge of carpet, and of maximum lengths to minimize running joints.

what: Technical where: Design Guidelines

4. HARD-SURFACE FLOORING • Where used, ceramic floor tile shall be set on latex mortar setting bed. Wall tile shall be installed by thin set on masonry and organic adhesive on drywall. • Grout shall be anti-bacterial and acid resistant, Hydroment Ceramic Tile Grout; grout should not be light in color. 5. HOLLOW METAL DOOR FRAMES • Metal frames shall be cold-rolled steel of commercial grade sixteen (16) gauge minimum. All frames shall be fitted with concealed fasteners, and 5/8” high integral stops. Frames shall be full seam and face welded and ground smooth; no knock down frames shall be acceptable. • Provide UL label frames at fire rated openings. • Provide all necessary hardware reinforcement, twelve (12) gauge except hinge and pivot reinforcements seven (7) gauge; door silencers, anchors, and all other accessories for a complete installation. 7. GLASS DOORS The following specifications apply where doors are visible to public lobbies and corridors. • Doors may be either “frameless” with top and bottom shoes, or of “narrow stile” tubular construction. • Trim and accessories shall be compatible with the size and weight of the selected doors and match color/finish of glass office front system. • Glazing shall be 1/2” minimum tempered glass for frameless doors, and 1/2” minimum tempered or laminated safety glass for narrow stile doors. • For interior glass doors and demountable walls, refer to Section 1.6 for product information and details.

Back

8. FINISHED HARDWARE • Badge readers can be found in the following doors: mother’s room, vestibules, IT Help Desk, Executive Board rooms, MDF/IDF, Facility/Help Desk Storage Closets etc, stairwell entries, and lobby areas. Badge readers are to be installed at the required ADA height of four (4) feet. All badge readers are POE and their relevant cables terminate into that floors Brivo Panel located in either the MDF or IDF. Cabling for these readers is 446100-4 Elemen Comp Cable (white jacket). All other doors are assumed unlocked unless otherwise specified.

Indeed Guidelines

66


Construction Guidelines •

what: Technical

where:

Design Guidelines

Lock cylinders throughout premises shall be by manufacturer as approved by building management, and shall be master keyed as directed by building management. Refer to Section 7 Security Guidelines for additional information and requirements. Door hardware locksets and latch sets shall be combination mortised type units. Trim shall be lever handles to conform to ADA requirements, and local codes. Hinges shall be full mortise type. Ball bearing hinges shall be provided on doors over 3’-6” width, and on doors having closers. Provide 1-1/2 pr. hinges per doors for 7’-0” high doors and 2 pr. hinges for 8’-0” high door.

9. ACOUSTICAL TILE CEILINGS • Mineral Fiber Acoustic Ceiling: Provide mineral fiber acoustic board made by Armstrong or equal. Sizes can vary based on design intent. • Ceiling Suspension Material: Comply with ASTM C635 as applicable. Coordinate with other work supported by or penetrating through ceilings, including light fixtures, HVAC equipment, and partition system, if any. Structural Class: Intermediate duty system. • Trim and Accessories: Provide manufacturer’s printed instructions, governing regulations, fire resistance rating and industry standards. • Install materials in accordance with manufacturer’s printed instructions, governing regulations, fire resistance rating and industry standards. • Fire-resistant ratings to meet local, state and/or country codes. 10. LIGHTING FIXTURES • Specialty lighting may be provided in the following areas: lobby, conference rooms, training rooms, phonebooths, reception, and other rooms. • Lighting shall be controlled by daylight/occupancy sensors, occupancy sensors, and/or local switching as required.

Back

11. HVAC • Provide all labor, materials, engineering, etc. for a complete installation as required for the facility as shown on the drawings. Work will be in strict accordance with all applicable codes and local requirements. • The scope is intended to describe only the principal items required for the heating, ventilation, and air conditioning of the facility. Equipment arrangement, duct distribution, specific operating characteristics, and code requirements shall be determined by the subcontractor and incorporated in the design to satisfy all specified criteria. • Provide ventilation and / or air conditioning as required for the electrical and telephone rooms. • Dedicated air conditioning systems will be required for computer rooms. Sizing of HVAC equipment to be determined by MEP engineer, based on room size and equipment requirements. • The toilet exhaust system shall be sized for a minimum of 2 cfm per square foot with transfers or supply air as required per code. • The work shall be inspected and approved by governing authorities. • The system shall be completely tested and balanced as necessary for proper system operation. Indeed Guidelines

67


Construction Guidelines •

what: Technical where: Design Guidelines

Design Criteria: • In general, refer to local, state, or country standards for design conditions, occupant loads, and ventilation requirements. • Indoor Conditions to meet building and local code requirements. • Cooling Load Design Criteria to meet building and local code requirements. • VAV boxes are to be specified on the basis of one box per 800 square feet for exterior zones and 1600 square feet for interior zones (not more than 1200 square feet per zone average). • Conditions shall be in compliance with all local codes and may vary based upon area of country. The above HVAC specification would typically apply to a new facility. If this were a space being improved in an existing building, the HVAC would be a modification only. Install all terminal units, ductwork, diffusers, returns, controls, etc. for a complete operating system per all applicable codes and standards. System shall be tested and balanced for proper airflows and operation. The quality of the system shall be building standard or better. Air returns not adjacent to door.

12. ELECTRICAL • Electrical installation shall conform to present day practices, electrical code requirements, and industry standards. • Electrical work shall include everything essential for a complete, balanced electrical system in satisfactory operating order. • Electrical Power - 5.0 volt/amps per rentable square foot at 480/277 volts shall be designed for lighting and appliance use and for the installation of supplemental air conditioning. Panels shall be installed within leasehold space, preferably in the telecom / IT closet. • Exit lights shall be installed per code. All exit lights are to be lighted clear lens. • Provisions for emergency power shall be provided via the landlord. • Fire alarm system shall meet building and local code requirements. • Refer also to furniture guidelines for locations and qualities of power/data at workstations. 13. VOICE / DATA CABLING • See Indeed Network Design Guidelines.

Back

14. GENERAL PLUMBING/FIRE PROTECTION • Planned installation of new work and connections shall ensure minimum interference with regular operation of existing facilities. All shut-downs shall be made at such times as will not interfere with regular operation of existing facilities and shall require written approval of the Landlord. To ensure continuous operation, contractor will make necessary temporary connections between new and existing work. • All existing areas and areas scheduled to remain that are damaged during demolition, shall be patched, repaired, and finished. • All piping, fittings, valves, materials, etc. to be the same type and quality as called for in the base building specifications. Indeed Guidelines

68


Construction Guidelines •

what:

Technical where:

Design shall be coordinated with all other trades and existing conditions of the site to maintain required ceiling heights and space conditions. All materials, fixtures, equipment, services, hangers, supports, labor, and tests necessary for complete execution of the work must be in accordance with the Local and State Building Code and Fire Insurance Company.

15 PLUMBING • All plumbing fixtures and model numbers shall be of the water-saving type and approved in accordance with the local Building Codes. • Individual point of use electric water heaters (where required) shall be utilized in kitchenettes/break rooms for dishwashers. • Wet column locations and drain lines shall be a primary design consideration for proposed plumbing locations.

Design Guidelines

16. FIRE / SPRINKLER PROTECTION • Sprinkler heads in finished spaces shall be based on building standard and finish – if not building specified, they should be reliable concealer G1 FM approved. The floors will be served with sprinkler heads at a design of one (1) sprinkler head per 180 rentable square feet, subject to approval by Factory Mutual Standard. Revisions to the sprinkler system may be required due to partition or lighting fixture layout. • All shop drawings and hydraulic calculations must be approved before any installation work is commenced. • Design to provide portable fire extinguishers and cabinets per code. • Fire stopping shall be provided and installed to close concealed draft openings. Fire stopping shall form an effective barrier between rooms and floor levels. 17 MILLWORK • Millwork shall conform to for “Premium Grade” construction. 18. LIFE SAFETY 19. SECURITY EQUIPMENT • See Indeed Security Design Guidelines Section 1.6Exit lights shall be installed per code. All exit lights are to be lighted clear lens. • Provisions for emergency power shall be provided via the landlord. • Fire alarm system shall meet building and local code requirements. • Fire stopping shall be provided and installed to close concealed draft openings. Fire stopping shall form an effective barrier between rooms and floor levels.

Back Indeed Guidelines

69


Wall Types

Section 1.1 - Acoustical Wall Details

what: Technical where: Design Guidelines

SEE SECTION 1.6

PARTITION - FULL HEIGHT A A

PARTITION- FULL HEIGHT B B

PARTITION - FULL HEIGHT

B1 B1

PARTITION - 2-1/2" STUD

PARTITION - FULL HEIGHT

PARTITION - 6" STUD B2 B2

A1 A2 Back

HEADER DETAIL C C

AT GLASS PARTITIONS

PARTITION - 3-5/8" STUD B3 B3 B4

PARTITION - 3-5/8" STUD 2

Indeed Guidelines

70


A

Wall Types Section 1.1

what:

A1 A2

PARTITION - FULL HEIGHT PARTITION - FULL HEIGHT PARTITION - FULL HEIGHT

Technical

B B1 B2 B3

where:

B4

Design Guidelines

PARTITION- FULL HEIGHT PARTITION - 2-1/2" STUD PARTITION - 6" STUD PARTITION - 3-5/8" STUD PARTITION - 3-5/8" STUD

1120 Avenue of the Americas New York, NY 10036

PARTITION- FULL HEIGHT D E CEMENT BOARD

RTITION - WOOD & GLASS Back

PARTITION - FURRING - 7/8" CHANNEL E F

G

PARTITION - LAMINATING E1 MEP ENGINEER: F1

G1

PARTITION - FURRING - 2-1/2" STUD E2 F2

G2

CFS ENGINEERS 228 East 45th Street 5th Floor New York, NY 10017 212.867.0259

EXPEDITOR: PARTITION - FURRING - 3-5/8" STUD EMPIRE CITY CONSULTANTS E3 F3 15 West 36th Street

PARTITION - CHA

PARTITION - CHA

PARTITION - CHA

3rd Floor

F4 F5

New York, NY 10018 PARTITION - FURRING - 3-5/8" STUD 212.228.1131 LIGHTING: CLARITY LIGHTS 228 PARK AVENUE SOUTH, SUITE 71169

PARTITION - FURRING - 3-5/8" STUD

EXISTING CORE WALL/DOOR

Indeed Guidelines

71


Wall Types

Section 1.1 - Raised Floor Details

what: Technical where: Design Guidelines

F

G

PARTITION - FULL HEIGHT

Back Indeed Guidelines

72


Millwork Details Section 1.2

what: Technical

CABINETS, CABINETS, TYP. TYP. 3/4"3/4" MDF MDF W/ W/ P. P. LAM. LAM. AS AS SCHEDULED SCHEDULED ONON ALLALL EXPOSED EXPOSED OUTER OUTER SURFACES, SURFACES, EDGES EDGES & ALL & ALL DOOR, DOOR, DRAWERS, DRAWERS, INCLUDING INCLUDING INSIDE INSIDE FACES FACES OF OF DOORS DOORS , ETC. , ETC.

CABINETS, CABINETS, TYP. TYP. 3/4"3/4" MDF MDF W/ W/ P. LAM. P. LAM. AS AS SCHEDULED SCHEDULED ONON ALLALL EXPOSED EXPOSED OUTER OUTER SURFACES, SURFACES, EDGES EDGES & ALL & ALL DOOR, DOOR, DRAWERS, DRAWERS, INCLUDING INCLUDING INSIDE INSIDE FACES FACES OF OF DOORS DOORS , ETC. , ETC.

Design Guidelines

PROVIDE PROVIDE CONCEALED CONCEALED HINGES HINGES AS AS REQ'D., REQ'D., TYP. TYP.

PROVIDE PROVIDE CONCEALED CONCEALED HINGES HINGES AS AS REQ'D., REQ'D., TYP. TYP.

SHELVING SHELVING TO TO BE BE 3/4"3/4" WHITE WHITE MELAMINE MELAMINE (ADJUSTABLE (ADJUSTABLE ONON S.S.S.S. PINS) PINS)

SHELVING SHELVING TO TO BE BE 3/4"3/4" WHITE WHITE MELAMINE MELAMINE (ADJUSTABLE (ADJUSTABLE ONON S.S.S.S. PINS) PINS)

INTERIOR INTERIOR SURFACES SURFACES (U.O.N.) (U.O.N.) TO TO BE BE WHITE WHITE MELAMINE, MELAMINE, TYP. TYP.

INTERIOR INTERIOR SURFACES SURFACES (U.O.N.) (U.O.N.) TO TO BE BE WHITE WHITE MELAMINE, MELAMINE, TYP. TYP. UNDER UNDER CABINET CABINET PLUG PLUG MOLD, MOLD, TYP. TYP. WHERE WHERE SHOWN SHOWN ONON POWER POWER TEL. TEL. PLAN PLAN

UNDER UNDER CABINET CABINET PLUG PLUG MOLD, MOLD, TYP. TYP. WHERE WHERE SHOWN SHOWN ONON POWER POWER TEL. TEL. PLAN PLAN

UNDER UNDER CABINET CABINET LIGHT LIGHT FIXT. FIXT. AS AS SCHEDULED, SCHEDULED, TYP. TYP.

UNDER UNDER CABINET CABINET LIGHT LIGHT FIXT. FIXT. AS AS SCHEDULED, SCHEDULED, TYP. TYP.

INTEGRAL INTEGRAL EDGE EDGE PULL PULL

INTEGRAL INTEGRAL EDGE EDGE PULL PULL

CONT. CONT. FULL FULL HEIGHT HEIGHT BACK BACK SPLASH SPLASH NONO SEAMS SEAMS PANEL PANEL TO TO BE BE CUT CUT AS AS 1 PIECE 1 PIECE

CONT. CONT. FULL FULL HEIGHT HEIGHT BACK BACK SPLASH SPLASH NONO SEAMS SEAMS PANEL PANEL TO TO BE BE CUT CUT AS AS 1 PIECE 1 PIECE

3/4"3/4" SOLID SOLID SURFACE SURFACE COUNTER COUNTER AS AS SCHEDULED SCHEDULED SCRIBED SCRIBED TO TO WALL WALL OVER OVER 3/4"3/4" PLYWOOD PLYWOOD SUBTOP SUBTOP SCRIBED SCRIBED TO TO WALL, WALL, TYP. TYP.

3/4"3/4" SOLID SOLID SURFACE SURFACE COUNTER COUNTER AS AS SCHEDULED SCHEDULED SCRIBED SCRIBED TO TO WALL WALL OVER OVER 3/4"3/4" PLYWOOD PLYWOOD SUBTOP SUBTOP SCRIBED SCRIBED TO TO WALL, WALL, TYP. TYP.

SINK SINK & FIXTURES. & FIXTURES. AS AS SCHEDULED SCHEDULED REFER REFER TO TO PLUMBING PLUMBING DRAWINGS DRAWINGS FOR FOR ROUGH-IN ROUGH-IN REQUIREMENT. REQUIREMENT. INSTALL INSTALL PAIR PAIR OF OF MTL. MTL. WALL WALL BRACKETS BRACKETS @ EACH @ EACH SIDE SIDE OF OF SINK SINK W/ W/ BLOCKING BLOCKING AS AS REQ'D. REQ'D.

2 ALUMINUM 2 ALUMINUM TRASH TRASH GROMMETS GROMMETS INTEGRAL INTEGRAL EDGE EDGE PULL, PULL, TYP. TYP.

PLASTIC PLASTIC LAMINATE LAMINATE ONON 3/4"3/4" MDF MDF REMOVABLE REMOVABLE PANEL, PANEL, MTD. MTD. ONON Z-CLIPS Z-CLIPS

P. LAM. P. LAM. AS AS SCHEDULED SCHEDULED ONON 3/4"3/4" MDF MDF @ EXPOSED @ EXPOSED SIDES SIDES & & EDGES EDGES OF OF BASE BASE CABINETS. CABINETS. BASE BASE TRIM TRIM AS AS SCHEDULED, SCHEDULED, TYP. TYP.

11 1

PANTRY PANTRY SINK SINK && UPPER UPPER CABINET CABINET

4" 4"

Back

TRASH TRASH DRAWER DRAWER EQUIP EQUIP AS AS SCHEDULED, SCHEDULED, TYP. TYP. 4" 4"

where:

PULL OUT OUT TRASH TRASH BIN BIN && UPPER UPPER CAB. CAB. 22 2 PULL

33 Indeed Guidelines

73

BAS B


Millwork Details Section 1.2

what: Technical

AM. AS UTER

CES

CABINETS,CABINETS, TYP. 3/4" MDF TYP.W/ 3/4" MDF W/ P. LAM. ASP. SCHEDULED LAM. AS SCHEDULED ON ON ALL EXPOSED ALL EXPOSED OUTER OUTER SURFACES, SURFACES, EDGES & ALL EDGES & ALL DOOR, DRAWERS, DOOR, DRAWERS, INCLUDINGINCLUDING INSIDE FACES INSIDE OF FACES DOORSOF , DOORS , ETC. ETC.

CABINETS,CABINETS, TYP. 3/4" MDF TYP.W/ 3/4" P. MDF W/ P. LAM. AS SCHEDULED LAM. AS SCHEDULED ON ALL ON ALL EXPOSED EXPOSED OUTER SURFACES, OUTER SURFACES, EDGES & ALL EDGES DOOR, & ALL DRAWERS, DOOR, DRAWERS, INCLUDINGINCLUDING INSIDE FACES INSIDE OF FACES OF DOORS , ETC. DOORS , ETC.

where: Design Guidelines

PROVIDE CONCEALED PROVIDE CONCEALED HINGES HINGES AS REQ'D.,AS TYP. REQ'D., TYP.

S

AMINE

SHELVINGSHELVING TO BE 3/4"TO WHITE BE 3/4" WHITE MELAMINEMELAMINE (ADJUSTABLE (ADJUSTABLE ON S.S. PINS) ON S.S. PINS)

BE

INTERIOR INTERIOR SURFACESSURFACES (U.O.N.) TO(U.O.N.) TO BE WHITE BE MELAMINE, WHITE MELAMINE, TYP. TYP.

PROVIDE CONCEALED PROVIDE CONCEALED HINGES HINGES AS REQ'D.,AS TYP. REQ'D., TYP. SHELVINGSHELVING TO BE 3/4"TO WHITE BE 3/4" WHITE MELAMINEMELAMINE (ADJUSTABLE (ADJUSTABLE ON S.S. PINS) ON S.S. PINS) INTERIOR INTERIOR SURFACESSURFACES (U.O.N.) (U.O.N.) TO BE WHITE TO BE MELAMINE, WHITE MELAMINE, TYP. TYP.

UNDER CABINET UNDERPLUG CABINET PLUG MOLD, TYP. MOLD, WHERE TYP. SHOWN WHERE SHOWN ON POWER ON TEL. POWER PLAN TEL. PLAN

UNDER CABINET UNDERPLUG CABINET PLUG MOLD, TYP. MOLD, WHERE TYP. SHOWN WHERE SHOWN ON POWER ON TEL. POWER PLAN TEL. PLAN

UNDER CABINET UNDERLIGHT CABINET LIGHT FIXT. AS SCHEDULED, FIXT. AS SCHEDULED, TYP. TYP.

UNDER CABINET UNDERLIGHT CABINET LIGHT FIXT. AS SCHEDULED, FIXT. AS SCHEDULED, TYP. TYP.

INTEGRAL INTEGRAL EDGE PULL EDGE PULL

INTEGRAL INTEGRAL EDGE PULL EDGE PULL

CONT. FULL CONT. HEIGHT FULL BACK HEIGHT BACK SPLASH NO SPLASH SEAMSNO PANEL SEAMS TO PANEL BE TO BE CUT AS 1 PIECE CUT AS 1 PIECE

BACKSPLASH BACKSPLASH AS AS SPECIFIED. SPECIFIED. IF SOLID IF SOLID SURFACE SURFACE MATERIAL,MATERIAL, MINIMIZE JOINTS. MINIMIZE JOINTS.

3/4" SOLID3/4" SOLID SURFACE SURFACE COUNTER COUNTER AS AS SCHEDULED SCHEDULED SCRIBED TO SCRIBED WALL TO WALL OVER 3/4" OVER 3/4" PLYWOODPLYWOOD SUBTOP SUBTOP SCRIBED TO SCRIBED WALL, TO WALL, TYP. TYP.

ELECTRICAL ELECTRICAL OUTLET OUTLET AS SCHEDULED AS SCHEDULED

New York, NY New 10018 York, NY 10018 212.228.1131212.228.1131

CONTINUOUS CONTINUOUS 2"x2" 2"x2" ALUM. ANGLE ALUM. (3 SIDES) ANGLE (3 SIDES) EQUIPMENT EQUIPMENT AS SCHEDULED AS SCHEDULED

INTEGRAL INTEGRAL EDGE EDGE PULL, TYP.PULL, TYP.

4"

4"

4"

4"

TRASH DRAWER TRASHEQUIP DRAWER AS EQUIP AS SCHEDULED, SCHEDULED, TYP. TYP.

PULL OUT PULL TRASH OUT TRASH BIN & UPPER BIN & UPPER CAB. CAB. 2

33

MEP ENGINEER: MEP ENGINEER: CFS ENGINEERS CFS ENGINEERS 228 East 45th 228 Street East 45th Street 5th Floor 5th Floor New York, NY New 10017 York, NY 10017 212.867.0259212.867.0259

3/4" SOLID3/4" SURFACE SOLID SURFACE COUNTER COUNTER AS SCHEDULED AS SCHEDULED EXPEDITOR:EXPEDITOR: SCRIBED TO SCRIBED WALL OVER TO WALL 3/4" OVER 3/4"EMPIRE CITYEMPIRE CONSULTANTS CITY CONSULTANTS Street West 36th Street PLYWOODPLYWOOD SUBTOP SCRIBED SUBTOP SCRIBED15 West 36th15 3rd Floor 3rd Floor TO WALL, TYP. TO WALL, TYP.

2 ALUMINUM 2 ALUMINUM TRASH GROMMETS TRASH GROMMETS

Back

1120 Avenue 1120 of Avenue the Americas of the Americas New York, New NYYork, 10036 NY 10036

BASE &BASE UPPER & UPPER CAB. CAB. 3 4

ELECTRICAL ELECTRICAL AS REQ'D, AS REQ'D, 1'-6" A.F.F. 1'-6" , TYP. A.F.F. PROVIDE , TYP. PROVIDE ALL OTHER ALL REQ'D. OTHER UTILITY REQ'D. UTILITY WORK PER WORK EQUIP., PER TYP. EQUIP., TYP.

LIGHTING: LIGHTING: CLARITY LIGHTS CLARITY LIGHTS 228 PARK AVENUE 228 PARK SOUTH, AVENUE SUITE SOUTH, 71169SUITE 71169 NEW YORK, NEW NY 10003 YORK, NY 10003 718-517-9286 718-517-9286 STRUCTURAL STRUCTURAL ENGINEER: ENGINEER:

PROVIDE 3/4" PROVIDE THK. 3/4" THK. PLASTIC LAMINATE PLASTIC LAMINATE CLAD SUPPORT CLAD SUPPORT FOR FOR SPANS GREATER SPANS GREATER THAN 5'-0" THAN 5'-0" BASE TRIMBASE AS TRIM AS SCHEDULED, SCHEDULED, TYP. TYP.

EQUIPMENT & UPPER & UPPER CAB. CAB. 44 EQUIPMENT NOTE: NOTE: ALIGN TILEALIGN AND FACE TILE AND OF MIRROR FACE OF MIRROR

Indeed Guidelines

74


3/4" SOLID SURFACE COUNTER AS SCHEDULED & END TURNDOWN RETURN WALL OVER 3/4" PLYWOOD SUBTOP, TYP.

SOLID SURFACE CLAD UNDERSIDE & INSIDE OF END RETURN WALLS, TYP.

CONT. 1"x 2"LLH ALUM. ANGLE (4 SIDES)

what:

CABINETS, TYP. 3/4" MDF W/ P. LAM. AS SCHEDULED ON ALL EXPOSED OUTER SURFACES, EDGES & ALL DOOR, DRAWERS, INCLUDING INSIDE FACES OF DOORS , ETC.

GYPSUM BOARD WALL BEYOND

Millwork Details

GYPSUM BOARD SOFFIT REFER TO RCP FOR ALIGNMENT & EXTENT SOFFITS WILL ALIGN WITH DEEPER CABINETS BEYOND

Section 1.2

PROVIDE CONCEALED HINGES AS REQ'D., TYP.

OLID SURFACE BEYOND

Technical AT ALL EXPOSED

LAM TERIORS

SHELVING TO BE 3/4" WHITE MELAMINE (ADJUSTABLE ON S.S. PINS)

where:

INTERIOR SURFACES (U.O.N.) TO BE WHITE MELAMINE, TYP.

PROVIDE CONCEALED HINGES AS REQ'D., TYP.

REVEAL

SHELVING TO BE 3/4" WHITE MELAMINE (ADJUSTABLE ON S.S. PINS)

MEP ENGINEER: CFS ENGINEERS 228 East 45th Street 5th Floor New York, NY 10017 212.867.0259

INTERIOR SURFACES (U.O.N.) TO BE WHITE MELAMINE, TYP.

EXPEDITOR: EMPIRE CITY CONS 15 West 36th Street 3rd Floor New York, NY 10018 212.228.1131

UNDER CABINET PLUG MOLD, TYP. WHERE SHOWN ON POWER TEL. PLAN

OLID SURFACE COUNTER AS SCHEDULED D TURNDOWN RETURN WALL OVER 3/4" OOD SUBTOP, TYP.

UNDER CABINET LIGHT FIXT. AS SCHEDULED, TYP.

LIGHTING: CLARITY LIGHTS 228 PARK AVENUE NEW YORK, NY 1000 718-517-9286

INTEGRAL EDGE PULL CONT. FULL HEIGHT BACK SPLASH NO SEAMS PANEL TO BE CUT AS 1 PIECE

D SURFACE CLAD RSIDE & INSIDE OF RETURN WALLS, TYP.

. 1"x 2"LLH ALUM. E (4 SIDES)

STRUCTURAL ENGI

P. LAM FILLER STRIP AS/IF REQ'D. PER SCHEDULED EQUIP. TYP.

SURFACE BEYOND

3/4" SOLID SURFACE COUNTER AS SCHEDULED SCRIBED TO WALL OVER 3/4" PLYWOOD SUBTOP SCRIBED TO WALL, TYP.

AT ALL EXPOSED ORS

ASKET DRAWERS AS ULED, TYP.

CONT. 2"x2" ALUM. ANGLE (3 SIDES)

(BACK) FACE PANEL,

3/4" THK. WHITE MELAMINE ADJUSTABLE SHELVING ON S.S. PINS

EAL

KET DRAWERS AS D, TYP.

2

CABINETS, TYP. 3/4" MDF W/ P. LAM. AS SCHEDULED ON ALL EXPOSED OUTER SURFACES, EDGES & ALL DOOR, DRAWERS, INCLUDING INSIDE FACES OF DOORS , ETC.

Design Guidelines

LAM (BACK) FACE PANEL, YP.

1120 Aven New Yo

WHITE MELAMINE DRAWERS, TYP. INTEGRAL EDGE PULL, TYP.

Back P-LAM AT ALL EXPOSED INTERIORS/ EXTERIORS

2

HEAVY DUTY GLIDES, TYP.

55

PANTRY DRAWER & UPPER CABINET

OUTLET

CABINETS, TYP. 3/4" MDF W/ P. LAM. AS SCHEDULED ON ALL

1

66

PANTRY DRAWER & UPPER CABINET Indeed Guidelines

ARCHITECT: HABJAN ARCHITEC 115 W30TH STREET NEW YORK, NEW YO 646-766-1650

75

INDEED


SCRIBED TO WALL, TYP.

PLUMBING DRAWINGS FOR ROUGH-IN REQUIREMENT. INSTALL PAIR OF MTL. WALL BRACKETS @ EACH SIDE OF SINK W/ BLOCKING AS REQ'D.

Section 1.2

what: Technical

1

INTEGRAL EDGE PULL, TYP.

PLASTIC LAMINATE ON 3/4" MDF REMOVABLE PANEL, MTD. ON Z-CLIPS

P. LAM. AS SCHEDULED ON 3/4" MDF @ EXPOSED SIDES & EDGES OF BASE CABINETS.

TRASH DRAWER EQUIP SCHEDULED, TYP.

BASE TRIM AS SCHEDULED, TYP.

PANTRY SINK & UPPER CABINET

4"

Millwork Details

2 ALUMINUM TRASH GROMMETS

2

PULL OUT TRASH BIN & UPPER CAB.

where: Design Guidelines

REFER TO PLAN

3/4" PL. LAM./OR SOLID SURFACE COUNTERTOP SCRIBED TO WALL 3/4" PLYWD. SUB-TOP

3/4" PLYWOOD VENEER HAT SHELF, PAINTED LACQUER FINISH TO MATCH P-1 EQ

EQ 1 2"

8

PROVIDE 3-1/2 x 3-1/2" x STEEL POST IN WALL SLAB TO SLAB WITH WELDED 1-1/2" STEEL OUTRIGGERS EVERY 2'-0" O.C.

1-1/4"D. STAINLESS STEEL ROD WALL TO WALL TYP.

6

TYPI

NOTE: ALIGN TILE

CONTINUOUS 2"x2" ALUM. ANGLE (3 SIDES) SEE PLANS FOR WALL INFO PROVIDE 3-1/2 x 3-1/2" x 21" STEEL POST IN WALL SLAB TO SLAB WITH WELDED 1-1/2" STEEL OUTRIGGERS EVERY 2'-0" O.C.

PROVIDE 1" THK. VERTICAL DIVIDERS FOR SPAN GREATER THAN 5'-0"

FIN. FLOOR

BASE AS SPECIFIED.

77

Back

TYPICAL COAT CLOSET DETAIL

88

TYPICAL P-LAM COUNTER W/ STEEL OUTRIGGERS

7

Note: ADA-compliant detail for shelf to be added Indeed Guidelines

76

TYPI


3

2

8"

8"

REVEAL3 PLASTIC 8" REVEAL LAMINATEPLASTIC LAMINATE

A

what:

10'-11" 10'-11"

ELECTRICAL OUTLET ELECTRICAL OUTLET

EXISTING CONVECTOR EXISTING CONVECTOR ELECTROSTATIC PAINT ELECTROSTATIC PAINT WALL BASE WALL BASE

B

EAST ELEV. - PANTRY 11-38

EAST- ELEV. - PANTRY PANTRY MEDIUM PANTRY 11-38 A MILWORK A

Technical where:

PLASTIC LAMINATE PLASTIC LAMINATE

B

SOLID SURFACE ELECTRICAL OUTLET PANTRY ISLAND SOLID SURFACE WALL BASE SOLID SURFACE ELECTRICAL ELECTRICAL OUTLET PLASTIC LAMINATE OUTLET ELECTRICAL OUTLET PANTRY ISLAND PANTRY ISLAND WALL BASE WALL BASE ELECTRICAL OUTLET PLASTIC LAMINATE ELECTRICAL OUTLET PLASTIC LAMINATE

3'-0"

Section 1.2 EAST ELEV. - PANTRY 11-38

WALL BASE

MILLWORK BANQUET EXISTING MILLWORK CONVECTOR BANQUET ELECTROSTATIC PAINT

REVEAL

1" FINGER PULL 1" FINGER PULL

3'-0" 8'-6 3'-0" 3/4" 6'-9"

3'-10" 1'-6"

Millwork Details

MILLWORK BANQUET UPHOLSTERED BACK UPHOLSTERED BACK WALL WALL ELECTRICAL OUTLET

8"

PAINTED GYP. PAINTED GYP. 1" FINGER PULL

8'-6 3/4" 8'-6 3/4" 6'-9"10'-11" 6'-9"

UPHOLSTERED BACK WALL PAINTED GYP. PAINTED GYP.

10'-11" 3'-10" 3'-10" 1'-6" 1'-6" 8'-6 3/4"

10'-11" 10'-11"

8'-6 3/4" 8'-6 3/4"

2

REVEAL3

PLASTIC LAMINATE

PAINTED GYP. 2

WEST ELEV. - PANTRY 11-38

WEST ELEV. - PANTRY 11-38 WEST ELEV. - PANTRY 11-38 B 3

FACETED WALL PAINTED GYP.

Design Guidelines

3 8"

3 8"

REVEAL

REVEAL 3

FACETED WALL FACETED WALL PAINTED GYP. PAINTED GYP.

3 8"

REVEAL3

8"

3 8"

REVEAL

PAINTED GYP. REVEAL3 8" REVEAL

ISLAND

WALL BASE

ISLAND

ELECTRICAL OUTLET ELECTRICAL OUTLET EXISTING CONVECTOR EXISTING CONVECTOR ELECTROSTATIC PAINT ELECTROSTATIC PAINT

WALL BASE WIRE BASKETS WIRE BASKETS WALL BASE

FB-2 FB-2 (4) (4)

11" 1'-9"11"1'-7" 1'-9" 1'-7" 6'-2"

1" FINGER PULL

ELECTRICAL OUTLETS

6'-2"

5'-0 7/8"5'-0 7/8"

1" FINGER PULL

ELECTRICAL 1" FINGER PULL 1" FINGER 1" FINGER PULL OUTLETS ELECTRICAL PULL1" FINGER OUTLETS PULL

WEST ELEV. - PANTRY

WEST ELEV. - PANTRY WEST ELEV. - PANTRY

PLASTIC LAMINATE PLASTIC LAMINATE UNDER CABINET LIGHTING UNDER CABINET LIGHTING FINISH END PANEL PER 1" FINGER PULL DETAIL 1" FINGER PULL SOLID SURFACE

WATER DISPENSER FILTER/ COMPRESSOR/BOILER FINISH END PANEL PER CO2 CYLINDER FINISH END PANEL PER DETAIL COORDINATE W/SPEC DETAIL SOLID SURFACE SOLID SURFACE WATER DISPENSER FILTER/ WATER DISPENSER FILTER/ COMPRESSOR/BOILER COMPRESSOR/BOILER CO2 CYLINDER CO2 W/SPEC CYLINDER COORDINATE COORDINATE W/SPEC

E

4'-10"

10'-11" 10'-11"

E

2

EAST E

EASTEAE E

G

PAINTED GYP

DECOUST

DECOUST

OPEN TO BEYOND

2

4'-10" 2'-10"

Back

WALL BASE WALL BASE

DECOUSTICS PANEL PAINTED GYP DECOUSTICS PANEL PAINTED GYP

4'-10" 10'-0" 4'-10" 2'-10" 8'-6 2'-10" 3/4"

FB-2 (4)

5'-0 7/8"

6'-2"

PLASTIC LAMINATE UNDER CABINET LIGHTING FACETED WALL FACETED WALL PAINTED 1" FINGERGYP. PULL PAINTED GYP.

10'-0"

FD-1FD-1

11" 1'-9" 1'-7"

DECOUSTICS PANEL

FACETED WALL PAINTED GYP.

METAL WALL METAL WALL TILE TILE

8'-610'-11" 3/4" 8'-6 3/4"

FD-1FD-1

FD-1FD-1 FD-1

WEST ELEV. - PANTRY

2

METAL WALL TILE

10'-11" 10'-11"

FD-1

WALL BASE

WEST ELEV. - PANTRY WEST ELEV. - PANTRY

10'-0"

FD FD

FD-1

4'-10" 2'-10"

FD

PLASTIC LAMINATE PLASTIC LAMINATE 1" FINGER PULL 1" FINGER PULL

8'-6 3/4" 6'-9"

10'-11" 10'-11"

8'-6 3/4" 8'-6 3/4" 6'-9"10'-11" 6'-9"

UPHOLSTERED BACK UPHOLSTERED BACK SOLID WALL SURFACE WALL ELECTRICAL OUTLET MILLWORK BANQUET BANQUET EXISTING MILLWORK CONVECTOR ELECTROSTATIC SOLID SURFACE PAINT SOLID SURFACE

EASTEAST ELEV. - PANTRY ELEV. - PANTRY

8'-6 3/4" 8'-6 3/4" 4'-10" 10'-11" 4'-10" 2'-10" 8'-6 2'-10" 3/4"

1FD-1 D

WIRE BASKETS

EAST ELEV. - PANTRY

10'-11" 10'-11"

1

ISLAND

1'-6"

FE

MILLWORK BANQUET

3/4" 3'-0" 3'-0" 8'-6 3'-10" 1'-6" 1'-6" 3'-0"

10'-11" 10'-11"

FB

8'-6 3/4" 8'-6 3/4" 10'-11" 3'-10" 3'-10"

FB

UPHOLSTERED BACK WALL PAINTED GYP. PAINTED GYP.

PAINTED GYP. PAINTED GYP. 1" FINGER PULL

8'-6 3/4" 8'-6 3/4" 4'-10" 10'-11" 4'-10" 2'-10" 8'-6 2'-10" 3/4"

PLASTIC LAMINATE PAINTED GYP.

B FB FB FB FBFE FE

D

FACETED WALL PAINTED GYP. PAINTED GYP.

3

PLASTIC LAMINATE

2

OPEN TO BEYOND OPEN TO BEYOND

2

PANTRY ISLAND: SOLID SURFACE

WALL BASE

NORTH ELEV. - ENTRY TO PANTRY 11-38 PLASTIC LAMINATEPLASTIC LAMINATE

WALL BASE WALL BASE

PANTRY ISLAND:

PANTRY ISLAND: SOLID SURFACE Indeed Guidelines 77 SOLID SURFACE

NORTH ELEV. - ENTRY TO PANTRY 11-38 NORTH ELEV. - ENTRY TO PANTRY 11-38


PLASTIC LAMINATE (PL-1)

WALL BASE - (PL-2) PLASTIC LAMINATE (PL-1)

1" REVEAL SHELVING - PLASTIC LAMINATE (PL-2)

METAL TRIM - (PL-2)

INTERIOR CABINET PLASTIC LAMINATE (PL-1)

2" SOLID SURFACE WATERFALL EDGE

NORTH ELEV. - SERVERY

1" METAL TRIM - (PL-2)

Millwork Details

1" REVEAL

1" METAL TRIM - (PL-2)

Technical

1

PANTRY MILWORK - LARGE ENLARGED FLOOR PLAN: PANTRY 09-15A, TRAY DROP-OFF 09-16

PANTRY

3 8"

FL1" METAL TRIM - (PL-2)

FL

REVEALS

1" METAL TRIM - (PL-2)

PLASTIC LAMINATE

FD

FB

FB

FB

FB

FB

FD

FD

1" REVEAL

METAL TRIM - (PL-2)

FB

NORTH ELEV. - SERVERY

FW

FH

FD

INTERIOR CABINET PLASTIC LAMINATE (PL-1)

SHELVING - PLASTIC LAMINATE (PL-2)

FW

2" SOLID SURFACE WATERFALL EDGE

1" METAL TRIM (PL-2)

FB

FB

FH

1

RUBBER WALL BASE

3 8"

WALL BASE - (PL-2) PLASTIC LAMINATE (PL-1)

REVEAL - TYP. WALL BASE (PL-2) PLASTIC LAMINATE (PL-1)

FW

FB

FB

ARCHITE HABJAN 115 W30T NEW YOR 646-766-1

FB

1" METAL TRIM - (PL-2)

1" REVEAL

SHELVING - PLASTIC LAMINATE (PL-2)

FD 1" METAL TRIM - (PL-2)

SOFFIT - PLASTIC LAMINATE - (PL-1)

FB

FACE - PLASTIC LAMINATE (PL-1)

55" TV

ALIGN

FD

FBPLASTIC LAMINATE (PL-1)

BACKSPLASH - PLASTIC LAMINATE (PL-1)

FW

FB

FW

FW

FB

FB

FB

FB

5'-0" AFF

3 8"

1" METAL TRIM (PL-2)

PLASTIC LAMINATE END PANEL

PLASTIC LAMINATE (PL-1) METAL TRIM (PL-2)

METAL TRIM (PL-2)

SOFFIT: PAINTED GYP.

INDE 1120 9th F New

1" REVEAL

EXPEDITOR: EMPIRE CITY CONSULTANTS 15 West 36th Street 3rd Floor OPEN TO New York, NY 10018 BEYOND 212.228.1131

OPEN TO BEYOND

ELEV

A1

REVEALS

1" METAL TRIM - (PL-2)

PLASTIC LAMINATE (PL-4)

MEP ENGINEER: PLASTIC CFS ENGINEERS SOFFIT: LAMINATE (PL-1) 228 East 45th Street 5th FloorPAINTED SOFFIT: GYP.10017 New York, NY 212.867.0259

PLASTIC LAMINATE - (PL-1)

FB-2

FD

1" METAL TRIM - (PL-2)

WALL BASE

FB-2 EAST ELEV. - SERVERY

1-1/2" SOLID SURFACE TOP PLASTIC LAMINATE (PL-1)

3 8"

WALL BASE (PL-2)

LIGHTING: CLARITY LIGHTS 228 PARK AVENUEWALL SOUTH, SUITE 71169 WALLL BASE (PL-2) BASE (PL-2) DIVIDERS: PLASTIC LAMINATE (PL-2) PLASTIC LAMINATENEW (PL-1) YORK, NY 10003 PLASTIC LAMINATE (PL-1) BACKSPLASH: SOLID 718-517-9286 1" METAL TRIM - (PL-2)

REVEAL - TYP.

SURFACE

B ENLARGED CEILING PLAN: PANTRY 09-15A, TRAY DROP-OFF 09-16

1" METAL TRIM - (PL-2)

SOFFIT - PLASTIC LAMINATE (PL-1)

1" METAL TRIM (PL-2) PLASTIC 3 8" REVEALS LAMINATE (PL-1) COUNTER TOP: PLASTIC LAMINATE (PL-4) SOLID SURFACE

WALL BASE

STRUCTURAL ENGINEER:

WEST ELEV. - SERVERY

1" METAL TRIM - (PL-2) VISION PANEL

FB

9'-2" 8'-6"

FB

8'-3" 7'-3"

FB(4)

FB

1" METAL TRIM - (PL-2)

SOUTH ELEV. - SERVERY

FD

7'-3"

FD

FD

PLASTIC LAMINATE (PL-1)

UC

9'-2"

FD

UC

PLASTIC LAMINATE (PL-1)

8'-0"

FD

WALL BASE - (PL-2)

FH UC

FB

SOFFIT - PLASTIC LAMINATE (PL-1)

VINYL WALLCOVERING

FD

2

LIGHTING CLARITY 228 PARK NEW YOR 718-517-9

REVEAL - TYP.

VISION PANEL

OPEN TO BEYOND

FB

3 8"

WALL BASE (PL-2)

1120 Avenue of the Americas New York, NY 10036

FL

FD

1-1/2" SOLID SURFACE TOP PLASTIC LAMINATE (PL-1)

STRUCTU

SOFFIT - PAINTED GYP.

9'-2" 8'-6"

FD

1" METAL TRIM - (PL-2)

WALL BASE

8'-3" 7'-3"

FD

9'-2"

FH

8'-0"

FD

EXPEDITO EMPIRE C 15 West 3 3rd Floor New York 212.228.1

1" METAL TRIM (PL-2)

EAST ELEV. - SERVERY

FB(4) FL

MEP ENG CFS ENG 228 East 5th Floor New York 212.867.0

PLASTIC LAMINATE (PL-1) PLASTIC LAMINATE - (PL-1)

1" METAL TRIM - (PL-2)

PLASTIC LAMINATE (PL-4)

where:

FD

BACKSPLASH - PLASTIC LAMINATE (PL-1)

ALIGN

55" TV

B

Design Guidelines

SOFFIT - PLASTIC LAMINATE - (PL-1)

FB

5'-0" AFF

what:

SHELVING - PLASTIC LAMINATE (PL-2)

FACE - PLASTIC LAMINATE (PL-1)

Section 1.2

OP-OFF 09-16

UC

LAMINATE

BEYOND

VINYL WALLCOVERING

FB FW FB

FB

1" METAL TRIM (PL-2)

FB FW

FB

FW

FW

SOUTH ELEV. - SERVERY

Back

ARCHITECT: HABJAN BETANCOURT ARCHITECTURE LLP. 115 W30TH STREET, SUITE 1213 NEW YORK, NEW YORK 10001 646-766-1650

FB

FB

SOFFIT: PLASTIC LAMINATE (PL-1)

PLASTIC LAMINATE END PANEL

PLASTIC LAMINATE (PL-1) METAL TRIM (PL-2)

METAL TRIM (PL-2)

9'-2"

FB

'-0"

FB

3"

FB

SOFFIT: PAINTED GYP. 1" REVEAL

SOFFIT: PAINTED GYP.

2 FB

1

FW FB

FW

RUBBER WALL BASE

3 8" REVEAL - TYP. WALL BASE (PL-2) PLASTIC LAMINATE (PL-1)

WALL BASE - (PL-2) PLASTIC LAMINATE (PL-1)

OPEN TO

OPEN TO

INDEED 1120 Avenue of the Americas 9th Floor New York, NY 10036

Indeed Guidelines

78


15 West 36th Street 3rd Floor New York, NY 10018 212.228.1131

12

14

13

15

LIGHTING: CLARITY LIGHTS 228 PARK AVENUE SOU NEW YORK, NY 10003 718-517-9286

17

16

STRUCTURAL ENGINEE

Door Details

1

2

3

Section 1.3

what:

3A

1

Technical where: Design Guidelines

1

38" TYP.

J2

JAMB

H3

11

10 1

1

1 H2A

S2A

HEAD

1

J2A

H1

S1

Back

3A

4

3

2

2

SILL

12

DOOR TYPES

SINGLE GLASS ENTRY DOOR

S3

14

13

15

SILL

INDEED 1120 Avenue 9th Floor New York, NY

3

1

J3

JAMB

3A

4DOOR TYPE

2

JAMB

HEAD

ARCHITECT: HABJAN BETANCOURT 115 W30TH STREET, SU NEW YORK, NEW YORK 646-766-1650

DOUBLE GLASS ENTRY DOOR

1

H2

HEAD

SILL

STANDARD HOLLOW METAL DOOR

5

6 J1

HEAD

JAMB

MOUNTING HEIGHTS

7

8

H2A

HEAD

9

Indeed Guidelines

79


1' - 0"

3

2

SCHE. GYPSUM CEILING

1 JOINT REINFORCEMENT CORNER BEAD 3

8

2 EXISTING GLAZING

SEE RCP

SAG-RESIS GYP. BD WITH METAL STUD FRAMING METAL STUD, SECURED TO STRUCTURE ABOVE, DIAGONALLY BRACE REQUIRED

1

Ceiling Details

SCHEDULE CEILING

SEE RCP

ULE CEILING

1' - 0"

EXISTING METAL DECKING

JOINT REINFORCEMENT

where:

CORNER BEAD

CEILING SUPPORTS AS REQD. SET BACK FROM PANEL EDGE

SCHE. GYPSUM CEILING

GRID 15/16 INTER. DUTY GRID

6" MIN.

1' - 0"

SCHE. GYPSUM CEILING

PARTITION AS SCHEDULED

REINFORCEMENT

ER BEAD

1 1/2" = 1'-0"

Design Guidelines

TECTUM CEILING PANEL CONCEALED GRID TILE TILE THICKNESS 1.5"

EXISTING GLAZING

EXISTING GLAZING

SAG-RESIS GYP. BD WITH METAL STUD FRAMING

TECTUM CEILING PANEL FINISHED EDGE CONDITION MINIMUM 2 PER PANEL END PAN. TO HAVE 3 FIN. ENDS

JOINT REINFORCEMENT

SCHEDULED DOWNLIGHT FIXTURE. COORIDNATE FIXTURE INSTALLATIONBEAM BEYOND WITH SCHEDULED FURNITURE REINFORCEMENT HEADER. SECURE FIXTURE TO SLAB ABOVE AND PROVIDE PATHWAY FOR ULED DOWNLIGHT FIXTURE. FIXTURE CABLES AND SUPPORTS. DNATE FIXTURE INSTALLATION CHANNEL SUPPORTS & HANGERS CHEDULED FURNITURE LINE OF SCHEDULED FURNITURE FOR LED STRIP LIGHT FIXTURE R. SECURE FIXTURE TO SLAB AND PROVIDE PATHWAY FOR ABOVE PERFORATED TILE LINE OF PARTITION BEYOND RE CABLES AND SUPPORTS. SCHEDULED PARTITION CEILING SUPPORT AS REQUIRED F SCHEDULED FURNITURE 5 8"

F PARTITION BEYOND

ING ULED PARTITION

11

2" MTL. O.C.

DETAIL AT TECTUM CEILINGS

1

DETAIL AT TECTUM CEILING

TYP.NO SHADE @ EXTERIOR WINDOW

TYPE X GYPSUM BOARD

11

1 1/2" = 1'-0"

SEE RCP FOR CEILING HEIGHT

F.R. BLOCKING AS REQUIRED FOR FAN COIL TYP.NO SHADE EXTERIOR WINDOWEXISTING TAPED IN LINEAR@ LIGHT FIXTURE UNIT COVER 0' - 8" TO LIGHTING SCHEDULE AND 1 1/2" = 1'-0"REFER

SPECIFICATION

10

0' - 4"

SCHE. A GYPSUM CEILING

ALIGN

IGHTING COVE AT TYPE FG S

24

STONE SADDLE

0' - 6"

0' - 6"

ALIGN

SCHEDULED GYP. CEILING

TAPE AND SPACKLE. ALIGN

SCHEDULED GYP. CEILING

TAPE AND SPACKLE.

SCHEDULED DIFFUSER SCHEDULED ACTMECH CEILING (TYPICAL) SEE CONTROL JOINT DRAWINGS. SEE SPEC.

SCHEDULED DIFFUSER (TYPICAL) SEE MECH DRAWINGS.

CERAMIC TILE AS SCHEDULED LATICRETE BLUE 92 ANTI-FRACTURE MEMBRANE & LATICRETE 125 SOUND & CRACK ADHESIVE THIN SET / FLOOR LEVELING EXISTING SCHEDULED ACT CEILING CONCRETE SLAB

ALIGN

JOINT COMPOUND

GYP. BD CEILING WITH GRID SYSTEM

METAL STUD, SECURED TO STRUCTURE ABOVE, DIAGONALLY BRACE AS REQUIRED

9

ALIGN

6

DETAIL AT CERAMIC TILE & SADDLE ALIGN

TYP. LIGHTING COVE @ COPY / COFFEE 3" = 1'-0"

SHADOWLINE WALL MOLDING (TYP)

C

SEE RCP

VARIES METAL STUD, SECURED TO STRUCTURE ABOVE, DIAGONALLY BRACE REQUIRED

SCHEDULED ACT SUSPENSION SYSTEM GRID AND PANEL METAL STUD, SECURED TO STRUCTURE ABOVE, DIAGONALLY BRACE REQUIRED

GYP. BD CEILING WITH METAL STUD FRAMING

5

PROJECT

TYP. DETAIL @ SOFFIT 3" = 1'-0"

SEE RCP

SCHEDULE CEILING

SCHEDULE CEILING

JOINT REINFORCEMENT CORNER BEAD

JOINT REINFORCEMENT CORNER BEAD

SEE RCP

VARIES

SEE RCP

VARIES

2

2

GYP. BOARD. CEILING WITH GRID SYSTEMS

1

ARCHITECT: HABJAN ARCHITECTURE + INTERIOR DESIGN LLC. 115 W30TH STREET, SUITE 1213 NEW YORK, NEW YORK 10001 3" = 1'-0" 646-766-1650

5

55

TYP. DETAIL @ SOFFIT DETAIL AT SOFFIT

TYP. DETAIL @ SOFFIT

SAG-RESIS GYP. BD WITH METAL STUD FRAMING

SAG-RESIS GYP. BD WITH METAL STUD FRAMING

PANTRY UPPER CABINET (WHERE OCCURS)

JOINT REINFORCEMENT

SCHEDULED PARTITION

PANTRY UPPER CABINET (WHERE OCCURS)

LINE OF PARTITION B BEYOND

SCHEDULED PARTITION

811 LOU HOUSTO

811 LOUISIANA STREET HOUSTON, TEXAS 77002

JOINT REINFORCEMENT METAL STUD BRACING AS REQUIRED.

GYP. BD CEILING WITH METAL STUD FRAMING

SCHEDULED FABRIC WRAPPED PANEL (WHERE OCCURS)

SEE RCP

C

SEE RCP

SHIMMING AS REQUIRED. PAINT TO MATCH ADJ. PARTITION.

GYP. BD. WALL BEYOND

4

METAL STUD, SECURED TO STRUCTURE ABOVE,

SHADOWLINE WALL MOLDING (TYP)

SCHEDULED PARTITION SLIDING DOOR AS SCHEDULED

1 1/2" = 1'-0"

DIAGONALLY BRACE AS 3" = 1'-0" REQUIRED

1 1/2" = 1'-0"

SCHEDULED CEILING GRID SYSTEM

SEE FINISH SCHEDULE FOR DIMENSION REQUIREMENTS

LIGHT COVE AT ACT CE

3

TYP. CEILING TRANSITION-ACT TO GYP STRUCTURAL ENGINEER: BD

SEE RCP

1 1/2" = 1'-0"

SCHEDULED PARTITION

SEE RCP

TYP. CEILING TRANSITION-ACT TO GYP CEILING TRANSITION-ACT TO GYP BD 6 BD 1 TRANSITION-ACT 1/2" = 1'-0" TO GYP 4 TYP. CEILING BD CARPET AS SCHEDULED

6

9

PROVIDE F.T. BLOCKING WITHIN PARTITION TO SUPPORT LIGHTSCHEDULED ACT SUSPENSION SYSTEM GRID AND PANEL

SCHEDULED LIGHT FIXTURE SCHEDULED ACT SUSPENSION SYSTEM GRID AND PANEL SCHEDULED ACT CEILING WITH SYSTEMS GYP. BD GRID CEILING WITH METAL STUD FRAMING

SCHEDULED FINISH SCHEDULED PARTITION

TYP. LIGHTING COVE @ COPY / COFFEE

5

SHADOWLINE WALL MOLDING (TYP) METAL STUD BRACING AS REQUIRED.

3" = 1'-0"

CORNER BEAD

3" = 1'-0"

FIXTURE INSTALLATION SEE RCP

CEILING DIFFUSER DETAIL AT GYP. Back 7 CEILING 1 1/2" = 1'-0" DETAIL AT GYP. CEILING DIFFUSER CEILING 1 1/2" = 1'-0"

DETAIL AT CONTROL JOINT

LIGHTING: CLARITY LIGHTS 228 PARK AVENUE SOUTH, SUITE 71169 NEW YORK, NY 10003 718-517-9286

6

JOINT COMPOUND SAG-RESIS GYP. BD WITH METAL STUD FRAMING

TYP. DETAIL AT CONTROL JOINT

EXPEDITOR: EMPIRE CITY CONSULTANTS ALIGN 15 West 36th Street 3rd Floor New York, NY 10018 212.228.1131

METAL STUD, SECURED TO STRUCTURE ABOVE, DIAGONALLY BRACE AS REQUIRED

1 1/2" = 1'-0"

ALIGN

CORNER BEAD WITH GYP. BD CEILING GRID SYSTEM SCHEDULED FINISH

CEILING DIFFUSER DETAIL AT GYP. CELING

7

TYP. LIGHTING COVE @ COP

9

SCHEDULED LIGHT FIXTURE D (WHERE OCCURS)

SAG-RESIS GYP. BD WITH METAL STUD FRAMING

SEE RCP

1120 Avenue of the Americas New York, NY 10036

EXISTING GLAZING

DETAIL AT FAN COIL UNIT COVER

CEILING

D 7 Dey Street. New York, NY 10007

SEE RCP

SHADE SYSTEM INDICATED

SCHEDULED ACT CEILING

3 CEILING DIFFUSER DETAIL AT GYP.

CLIFFORD DIAS, PE, PC

FT BLOCKING AS REQUIRED

EXISTING GLAZING

SCHEDULED DIFFUSER (TYPICAL) SEE MECH DRAWINGS.

5

SHADE SYSTEM INDICATED

MEP ENGINEER: CFS ENGINEERS 228 East 45th Street 5th Floor New York, NY 10017 212.867.0259

TAPE AND SPACKLE.

7 De

MEP

SCHEDULED LIGHT FIXTURE (WHERE OCCURS)

1 1/2" = 1'-0"0' - 6"

SCHEDULED GYP. CEILING

PROVIDE F.T. BLOCKING WITHIN PARTITION TO SUPPORT LIGHT FIXTURE CONTROL JOINT INSTALLATION. SEE SPEC. FT BLOCKING AS REQUIRED

1 1/2" = 1'-0"

TYP. PRIVACY SHADE @ EXTERIOR 10 WINDOW 1 1/2" = 1'-0" TYP. PRIVACY SHADE @ EXTERIOR WINDOW

PACK SOUND BARRIER PILLOWS. FILL ALL VOIDS AT PARTITION TERMINATION WHERE APPLICABLE.

PER RCP

TURE

2

TYP. PRIVACY SHADE @ EXTERIOR WINDOW

CONSULTANTS

SCHE. GYPSUM CEILING

1/27/2017 4:28:36 PM

ESIS GYP. BD WITH STUD FRAMING

10 C:\temp\035695.410_Willis_Houston_2016_kimb.rvt

Technical

TYP.NO SHADE @ EXTERIOR WINDOW 0' - 6"

11

0' - 6"

0' - 6"

SCHEDULED PARTITION

1001 McKinney Street Suite 1300 Houston, TX 77002 t 713.366.4000 f 713.528.3339 www.perkinswill.com

PROVIDE F.T. BLOCKING WITHIN PARTITION TO SUPPORT LIGHT FIXTURE INSTALLATION.

LINE OF PARTITION BEYOND

SEE RCP

1 1/2" = 1'-0"

EXISTING EXTERIOR WALL ASSEMBLY

0' - 6"

LINE OF SCHEDULED FURNITURE

what: T DETAIL @ BOOTH

SEE

EXISTING EXTERIOR WALL ASSEMBLY

SCHEDULED DOWNLIGHT FIXTURE. COORIDNATE FIXTURE INSTALLATION EXISTING EXTERIOR WALL WITH SCHEDULED ASSEMBLYFURNITURE HEADER. SECURE FIXTURE TO SLAB ABOVE AND PROVIDE PATHWAY FOR FIXTURE CABLES AND SUPPORTS.

Section 1.4

CEILING DIFFUSER DET CEILING

7

EXISTING GLAZING

3" = 1'-0"

EXISTING EXTERIOR WALL ASSEMBLY

JOINT REINFORCEMENT

1 SHADE SYSTEM INDICATED

ISSUE FOR ADDENDUM #01 2017.01.27

1

TYP. LIGHTING COVE AT TYPE FG LIGHTS

ISSUE FOR ADDENDUM #01 2017.01.27

4

STUD, SECURED TO TURE ABOVE, NALLY BRACE RED

7

SCHE. GYPSUM CEILING

SCHEDULE CEILING

4

B

META TO ST ABOV

LINE OF PARTITION BEYOND

S SEE RCP

SEE RCP

3/4" SHADOW MOLDING SCHEDULED PARTITION

SCHE SUSP SYST

3/4" S

3" = 1'-0"

INDEED 1120 Avenue of the Americas 9, 11, 12, 13, 16 Floors New York, NY 10036

META AS RE

Indeed Guidelines

80

ISSUE CHART

GYP.


Acoustical Details Section 1.5

what:

CEILING SUPPORTS ASAS REQD. CEILING SUPPORTS REQD. SET BACK FROM PANEL EDGE SET BACK FROM PANEL EDGE

Technical

GRID 15/16 INTER. DUTY GRID GRID 15/16 INTER. DUTY GRID

EXISTING METAL EXISTING METAL DECKING DECKING

where: Design Guidelines

6" 6" MIN. MIN.

PARTITION ASAS SCHEDULED PARTITION SCHEDULED

TECTUM CEILING PANEL TECTUM CEILING PANEL FINISHED EDGE CONDITION FINISHED EDGE CONDITION MINIMUM 2 PER PANEL END MINIMUM 2 PER PANEL END PAN. TOTO HAVE 3 FIN. ENDS PAN. HAVE 3 FIN. ENDS

BEAM BEYOND BEAM BEYOND

22 CHANNEL SUPPORTS & HANGERS CHANNEL SUPPORTS & HANGERS FOR LED STRIP LIGHT FIXTURE FOR LED STRIP LIGHT FIXTURE ABOVE PERFORATED TILE ABOVE PERFORATED TILE

TECTUM CEILING PANEL TECTUM CEILING PANEL CONCEALED GRID TILE CONCEALED GRID TILE TILE THICKNESS 1.5" TILE THICKNESS 1.5"

DETAIL DETAILATATTECTUM TECTUMCEILINGS CEILINGS DETAIL AT TECTUM CEILING

2

CEILING SUPPORT ASAS REQUIRED CEILING SUPPORT REQUIRED 120°

120°

5 5 X GYPSUM BOARD 8" TYPE 8" TYPE X GYPSUM BOARD

SEE RCP FOR CEILING HEIGHT SEE RCP FOR CEILING HEIGHT F.R. BLOCKING ASAS REQUIRED FOR F.R. BLOCKING REQUIRED FOR TAPED IN IN LINEAR LIGHT FIXTURE TAPED LINEAR LIGHT FIXTURE REFER TOTO LIGHTING SCHEDULE AND REFER LIGHTING SCHEDULE AND SPECIFICATION SPECIFICATION

B B1 B2 B3 B4

RED QUIRED

HEADER DETAIL 1 C

PARTITION- FULL HEIGHT

AT GLASS PARTITIONS

PARTITION - 2-1/2" STUD PARTITION - 6" STUD

EXISTING FAN COIL EXISTING FAN COIL UNIT COVER UNIT COVER PACK SOUND PACK SOUND BARRIER PILLOWS. BARRIER PILLOWS. FILL ALL VOIDS ATAT FILL ALL VOIDS PARTITION PARTITION TERMINATION WHERE TERMINATION WHERE APPLICABLE. APPLICABLE.

E

PARTITION- FU

DETAIL ATCOIL FAN COIL UNIT COVER DETAIL ATATFAN DETAIL FAN COILUNIT UNITCOVER COVER 5 5 D 3PARTITION - WOOD & GLASS

PARTITION - 3-5/8" STUD Back

PARTITION - 3-5/8" STUD 2

Indeed Guidelines

STONE SADDLE STONE SADDLE

81


Demountable Partitions Section 1.6

what:

Indeed has a preferred relationship with Tecno s.p.a. to provide glazed partitions and interior doors. The following details highlight the recommended products and profiles which are to be considered on each project. Other manufacturers’ products of confirmed equal quality and performance may be considered, if clearly demonstrated to have cost or lead time benefits.

Technical where: Design Guidelines

PLAN SECTION OF GLASS PARTITION

GW

W80 DOUBLE GLAZED GLASS PARTITION

Product Contact :

Back

Tecno Int. NA 20 Exchange Place New York City New York, 10005 Mobile: USA +1.646.331.4193 Mobile: Italy +1.346.88.97.664 Email: info@tecnospa.com

SECTION OF GLASS PARTITION

JOINTS Indeed Guidelines

82


Demountable Partitions Section 1.6

what: Technical where:

Product Contact :

Design Guidelines

Tecno Int. NA 20 Exchange Place New York City New York, 10005 Mobile: USA +1.646.331.4193 Mobile: Italy +1.346.88.97.664 Email: info@tecnospa.com

SECTION OF GLASS DOOR

GD

W80 INTERNAL SLIDING GLASS DOOR

Product Contact :

Back

Tecno Int. NA 20 Exchange Place New York City New York, 10005 Mobile: USA +1.646.331.4193 Mobile: Italy +1.346.88.97.664 Email: info@tecnospa.com

PLAN SECTION OF GLASS DOOR

Indeed Guidelines

83


Demountable Partitions Section 1.6

what: Technical where: Design Guidelines

SECTION OF GLASS DOOR

GD1

W80 HINGED GLASS DOOR

Product Contact :

Back

Tecno Int. NA 20 Exchange Place New York City New York, 10005 Mobile: USA +1.646.331.4193 Mobile: Italy +1.346.88.97.664 Email: info@tecnospa.com

PLAN SECTION OF GLASS DOOR Indeed Guidelines

84


Furniture what:

Section 2.1

Technical

The following images were prepared in coordination with Two Furnish to provide a general reference for various configurations and components. Additional requirements must be coordinated on a project by project basis.

where:

WORKSTATION BENCHING

Design Guidelines

Indeed Guidelines

85


Furniture what: Technical

Section 2.1

HEX WORKSTATIONS

where: Design Guidelines

Indeed Guidelines

86


Furniture what: Technical

Section 2.1

WORKSTATION TASK CHAIR

where: Design Guidelines

+Wk Chr, Aeron, Std-Ht Pneu., Tlt Lim, Adj Arms, Nonuphst Pds/B +Adjustable lumbar support +graphite +2 1/2” hard caster, black yoke, carpet only +black +pellicle-Pr Cat 1 +pellicle classic carbon SIZE B

Size split 70/15/15 for sizes A,B, and C

Indeed Guidelines

87


Furniture what: Technical

Section 2.1

WORKSTATION PEDESTAL

where: Design Guidelines

Indeed Guidelines

88


Furniture what: Technical

Section 2.1

WORKSTATION FINISHES

where: Design Guidelines

Indeed Guidelines

89


Furniture what: Technical where: Design Guidelines

Section 2.1

CONFERENCE ROOMS Watson Miro Conference Table Over 9’ 2 piece top ea top has power box in center D-top rounded end condition Power+AV: Power: ECA Power Box (Finishes based on table top finish; black or silver) Per Box = 3 Power, 2 USB, 2 Data, 1 HDMI Tables that are made into 2-piece tops will get (1) power box centered in each top. See below. Example 1: Gets 2 power boxes

Example 2: Gets 1 Power Box

Finishes: Varies NYC Finishes: Asian Night Top w/ Charcoal Base Phoenix Finishes: Bianco Kos Top w/ Frosty White Base Indeed Guidelines

90


Furniture what: Technical where:

Section 2.1

CONFERENCE ROOMS Custom Podium

Custom Mobile Credenza

Design Guidelines

Indeed Guidelines

91


Furniture what: Technical where:

Section 2.1

CONFERENCE ROOMS Conference Room Chairs

Design Guidelines

CIRCO CHAIR CR2 Frame: BLACK Base: BLACK 5 STAR STANDARD BLACK GAS LIFT HARD CASTERS Mesh: BLACK Fabric: GRADE 3, CAMIRA AQUARIUS Color: PITCH JA002

Indeed Guidelines

92


Furniture what: Technical

Section 2.1

INTERVIEW ROOM - 3 TYPES

where: Design Guidelines Type 1: D- top Conference Table Conference Chair

Type 2: Lounge Furniture to fill space and face video monitor (nothing too deep or that has a slanted seat)

Type 3: Lounge Furniture to fill space and face video monitor (nothing too deep or that has a slanted seat)

Indeed Guidelines

93


Furniture what: Technical

Section 2.1

TRAINING ROOM

where: Design Guidelines

Fliptop Tables with Power/AV at the top of table

Allermuir Circo Chair

Indeed Guidelines

94


Furniture what: Technical

Section 2.1

OPEN COLLABORATION SPACE

where: Design Guidelines

Laptop Tables Allermuir Host Accessories (decorative accessories, books, plants, games, puzzles, coloring books)

Indeed Guidelines

95


Furniture what: Technical where: Design Guidelines

Section 2.1

MEDIUM PANTRY Furniture benches to fit architecture- (the ROI is higher for Indeed)

High Density Stacking Chairs with solid backs, Indeed to decide on a case by case basis if additional chairs and carts should be ordered for All Hands

*Serving counters shall not have stools. Indeed Guidelines

96


Furniture what: Technical

Section 2.1

GAME ROOM

where: Design Guidelines

Indeed Guidelines

97


Finishes what: Technical where: Design Guidelines

Section 2.2

This section will specify the performance and quality standards to be included in Indeed workplaces. GENERAL • Paint (P-1, P-2, P-3) FLOORING OPTIONS • Carpet (CPT-1 : Main, CPT-2: Accent 1, CPT-3 Accent2) • Concrete (CON-1- stain, CON2- existing to polish)

WALL TREATMENT • Wallcovering ( WC-1, WC-2, etc) • Acoustical Panels (AWP-1, AWP-2, etc) • Film- (FM-1, FM-2) • Writable Dry Erase Paint (MB-1) • Vinyl (VIN-1, VIN-2)

• Wood (WD-1: Main, WD-2: Accent)

• Rubber Base (RB-1, RB-2, etc)

• Glazed Porcelain Tile (GPT1: Main, GPT-2: Accent)

• Glass (G-1)

RESTROOMS AND BREAKROOMS • Solid Surface (SS-1, SS-2) • Plastic Laminate (PL-1, PL-2, PL-3)

• Fabric Tack Panel (FTP-1, etc) CEILING • Acoustic Ceiling Tile (APC-1, APC-2)

• Glass Backsplash(GWT-1,GWL-2) • Tile Backsplash (WTI-1, WT-2) • Grout (GRT-1, etc)

Indeed Guidelines

98


Graphics / Signage

what:

Indeed Brand Colors:

Technical where: Design Guidelines

PMS 285 CMYK 100/40/0/0 RGB 33/100/243 HEX #2164f3

PMS 7579 CMYK 0/70/100/0 RGB 255/102/0 HEX #ff6600

White CMYK 0/0/0/0 RGB 255/255/255 HEX #ffffff

PMS 424 CMYK 59/50/50/20 RGB 102/102/102 HEX #666666

Black CMYK 0/0/0/100 RGB 0/0/0 HEX #000000

Indeed Brand Fonts:

Helvetica Neue Bold

Helvetica Neue Regular

Helvetica Neue Light

ABCDEFGHIJKLM NOPQRSTUVWXYZ abcdefghijklm nopqrstuvwxyz 1234567890!@#$%&?

ABCDEFGHIJKLM NOPQRSTUVWXYZ abcdefghijklm nopqrstuvwxyz 1234567890!@#$%&?

ABCDEFGHIJKLM NOPQRSTUVWXYZ abcdefghijklm nopqrstuvwxyz 1234567890!@#$%&?

Indeed Guidelines

99


Graphics / Signage what: Technical where: Design Guidelines

Graphic Icons:

Custom graphic icons have been created for Indeed to be used to identify space types in environmental graphics, signage and wayfinding. In large offices, these icons should be added to the directory for easy wayfinding. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19.

Restrooms (W / M) Elevator Stairs You Are Here Pantry Typical Meeting Room Typical Phone Room Training Room Game Room Cafe Mother’s Room Shower Room Back of House: Mecha Room, IDF, etc. Storage Fitness Room Quiet Room Coat Storage Copy Room Interview Room

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19. Indeed Guidelines

100


Graphics / Signage what: Technical where: Design Guidelines

Application of Graphic Icons

Flat edge to be flush with adjacent door frame or opening

Graphic icons are to be used to identify space types and in wayfinding. Style Line weights of icons should be consistent throughout each project. Use round cap for all exposed edges of linework and round join for all corners.

Round cap

30” top to bottom

Icon Color Indeed Orange (recommended) Wall Application Icon to always be resting on a horizontal datum. If horizontal datum does not exist in the design use the icon to include a horizontal graphic element. Location For room types, icon should be positioned adjacent to open-side of door.Provide a margin between door frame or opening and the icon.

Meeting room signage. Icon only to sit on top of glass film.

Phone room signage. No architectural horizontal datum line. Graphic to include horizontal line.

Wayfinding graphics

Horizontal datum in which the icon is positioned above to be consistent throughout each project. Floor application of wayfinding graphics

Code compliant signage Indeed Guidelines

101


Graphics / Signage what: Technical where: Design Guidelines

Room Signage

Text Helvetica Neue Medium, All caps, Tracking 25, Leading pt size equal to font pt size. Font size to be consistent throughout the project. Text Placement Should be center justified on the door. Minimum 4” margin on all sides of door. Font not to extend to edge of door. Height of room name to be near eyelevel. NO room names below 48” A.F.F. due to lack of visibility.

30” top to bottom 4” Clear all sides

Single line of text

Text Color High contrast between text color and door finish is recommended for legibility. • Light wood door: black text • Dark wood door: white text • Glass door - black, white or frosted text. White text is more legible if interior of the room is dark finishes. Black text is recommended if the room interior is light finishes. Writable Wall Surface Writable wall surface should be 30” top to bottom.

4” Margin

Two lines of text Indeed Guidelines

102


Graphics / Signage

what: Technical where: Design Guidelines

1. Indeed Logo Refer to Indeed Brand Guidelines for specifications on use of logo.

2. Indeed Search Bar Search boxes, “what:”, “where:” and “Find Jobs” button to remain consistent. Text within the what and where search boxes may vary per project location/design. 3. Indeed Dot Map One color/material to be used across entire dot map.

1.

2.

Solid wall application: Light gray 5–7% tint of black recommended

3.

Glazing application: Dusted crystal PVC-free film / frosted glass appearance. Never try to recreate any Dot Map. New maps may only be created by a member of the corporate marketing team. 4. “We help people get jobs.” Tagline used as graphic or signage element. 5. Blue Brand Wall “We help people get jobs.” Custom wallcovering.

4.

Background color: Indeed brand blue printed as 4-process (CMYK) or PMS. Text: White 6. Jobby Incorporated into the design of one custom graphic (recommended). Recommended location: Node or Entry

6. 5. Indeed Guidelines

103


Graphics / Signage what: Technical where: Design Guidelines

Local Flare

Each office should include a local element that varies per project and coordinates with interior aesthetic per location. Three ways to reflect the local environment within each office space: 1. Graphics 2. Materiality 3. Art Installation

1. Custom graphic of local landscape (Phoenix)

The following are examples only.

2. Materials to reflect local environment (Toronto)

3. Street art gong wall installation (London)

Indeed Guidelines

104


Graphics / Signage what: Technical where: Design Guidelines

Sales Office Gong

Sales office floors ring a gong and play music to acknowledge/celebrate completed sales. 1. The gong is typically 36” diameter. 2. The gong is mounted with Crestron touchpanel and iPad Pro.

Note: Dimensions in mm Indeed Guidelines

105


Lighting what: Technical where: Design Guidelines

Overall Goals for Lighting • • •

Provide access to daylight Provide adequate light for tasks Prevent glare from daylight and from interior electric light

Lighting Strategies 1. Place workstations in proximity to windows. 75% of workstations should be within 25 ft of an atrium or window; 95% of workstations within 41 ft of an atrium or window. 2. Provide task lighting when appropriate. If ambient lighting is below 300 lux, specify task lights that provide 300 to 500 lux at the work surface. 3. Use strategies at the windows to reduce solar glare. For glazing below 7’, either employ interior shades/blinds that are operable or automatic, an external shading system, or electrotonic glass that reduces transmissivity by 90% or more. For glazing above 7’, employ a strategy listed above, or use interior light shelves or a film of micro-mirrors to reflect sunlight toward the ceiling. 4. Orient workstations to avoid glare on computer screens. All computer screens at desks located within 15 ft of windows should be oriented within a 20º angle perpendicular to the plane of the window. 5. Shield electric lights to reduce glare, and do not aim them directly at computer screens. 6. Select light colored finishes to reflect light and create an overall brighter interior as opposed to dark-colored finishes that absorb light. 7. Lighting should automatically dim in response to daylight. 8. Lighting should automatically dim when space is unoccupied. 9. Walls should have the appropriate amount of window area, and those windows should transmit the appropriate amount of sunlight. Window-wall ratio should be between 20% and 60%. All glazing higher than 7’ from the floor should have a visible transmittance (VT) of 60% or greater. All glazing below 7’ from the floor should have a visible transmittance (VT) of 50% or greater. 10. Ensure electric lighting contributes to accurate portrayal of colors. Specify that all electric lights have a Color Rendering Index Ra (Avg. R1 through R8) of 80 or higher and Color Rendering Index R9 of 50 or higher.

Indeed Guidelines

106


Lighting what: Technical where: Design Guidelines

Lighting in the Open Workstation Area Visual comfort plays a major role in individuals’ ability to complete job tasks. This means that lighting should be considered when designing a work are according to ergonomic principles. The goal is to prevent or reduce glare. There are two types of glare – direct glare is caused by intensely bright light sources, such as the sun shining in windows and bright light fixtures shining down from the ceiling; reflected glare includes bright spots that are caused when light reflects on a computer monitor or work surface. Avoid using bright overhead lighting, which can cause shadows along with direct and reflected glare. To improve visual comfort and reduce glare, use any of these effective measures: • • • • •

Provide indirect lighting Place good diffusers on overhead lights Lower the general level of light in the work area, and provide task lighting Add shades to windows Tilt or move the monitor to avoid glare; adjust the monitor controls for brightness and contrast

Lighting Fixtures • •

Specialty lighting may be provided in the following areas: lobby, meeting rooms, training rooms, and other rooms as approved. Lighting shall be controlled by time clocks, occupancy sensors, and/or local switching as required.

Indeed Guidelines

107


Acoustics what: Technical where: Design Guidelines

Overall Goals for Acoustics • • • •

Consider exterior noise intrusion Consider interior noise from mechanical systems Shorten reverberation time so that interior-generated noise dissipates quickly, lowering levels of ambient interior noise Reduce sound transmission between spaces separated by walls/doors

Acoustic Strategies 1. Consider exterior noise intrusion: Research shows that loud or repetitive exterior noises can be a source of stress and detrimental to health. When choosing a site to build on, or more commonly, lease, leaders should be hesitant to choose a location in which the average interior sound pressure level from outside noise exceeds 50 dBA. 2. Consider the sound level of mechanical systems in the building: Meet the noise criteria (NC) limits of each space type: • Open workspaces - NC maximum of 40 • Enclosed offices - NC maximum of 35 • Conference rooms - NC maximum of 30 (25 recommended) 3. Plan for acoustic zones: Use an acoustic plan to identify loud and quiet zones, separating heads down areas from high traffic areas. 4. Incorporate mobile technology: headsets and wireless technology enable quick relocation between loud and quiet zones. 5. Employ change management: encourage the use of the right space for the right function. 6. Use sound masking: 45-48 dBA for open workspaces and 40-42 dBA for enclosed offices. 7. Specify acoustic coverings for ceilings and walls using appropriate Noise Reduction Coefficients: • Open workspace ceilings - NRC minimum of 0.9 • Conference room ceilings - NRC minimum of 0.8 on at least 50% of surfaces • Open workspace walls - NRC minimum of 0.8 on at least 25% of surfaces • Enclosed office/conference room walls - NRC minimum of 0.8 on at least 25% 8. Interior partition walls should be full height and meet Noise Isolation Class (NIC) minimums: • Enclosed offices - NIC minimum of 35 when a sound masking system is present; NIC minimum of 40 when no sound masking system is present • Conference rooms - NIC minimum of 53 on walls 9. Interior wall construction should reduce air gaps by properly sealing all acoustically rated partitions at the top and bottom tracks, staggering all gypsum board seams, and packing and sealing all penetrations through the wall. 10. Doors of private offices and conference rooms should be constructed with gaskets, sweeps, and/or non-hollow cores to reduce sound transmission. Indeed Guidelines

108


Appliances what: Technical

Lead times, dimensions, and pricing must be reconfirmed on a project by project basis. For outside of US use appliance standards as guideline, approval by Indeed required.

where:

Item

Brand

Model

Commercial Dishwasher Double Door glass front Refrigerator - Option #1 Double Door glass front Refrigerator - Option #2 Double Door Metal front Refrigerator Single Door metal front Refrigerator Single Door metal front Freezer Countertop water/ice machine ADA Microwave Coffee Brewer (single) Coffee Brewer (double) Coffee Grinder Large office Espresso Machine (over 300) Small office Espresso Machine (less than 100) Under counter Mini-fridge

Fagor Everest TRUE Everest TRUE Everest Scotsman Panasonic Fetco Fetco Fetco Jura Jura Summit

COP-504W EBGR2 GDM-47-LD EBRF2 T-23-HC EBF1 HID312A‐1 NE-1064 2131XTS 2132XTS GR2.2 Giga X7 Giga 5 SCR600BLBIHVADA

Design Guidelines

Indeed Guidelines

109


Audio Visual Guidelines what: Technical

The following Audio Visual content was compiled from the AV Design Standards V.1 2016, to provide detailed requirements for products and functional components within the Indeed workplace.

where:

1. AUDIO / VIDEO STANDARDS INTRODUCTION

Design Guidelines

This document presents the overall indeed Audio/Visual Design Standards Document. The purpose of this document is to acquaint design teams and construction professionals with the basic elements of indeed’s preferred Audio/Visual systems, and to guide the design teams toward a consistent Audio/Visual deployment throughout all indeed Campuses. This will result in easy to use, high quality, reliable A/V throughout all renovation and new building projects. Audio/Visual deployments require a well-coordinated, cohesive effort between the architects, electrical engineers, cabling contractors, network professionals, and A/V integrators, as each is dependent on others to deliver a fully functional room. This is to detail the elements, and provide installation and design guidelines. 2. ROOM DEFINITION The purpose of this section is to define specific room type naming and descriptions for use by the Architect, Real Estate, IT, and AV Integrator. This will establish a common nomenclature for use by the project team for all room referencing.

Indeed Guidelines

110


Audio Visual Guidelines what: Technical where:

2.1 Phone Booth/Room Phone Booths are defined as a small collaboration space with a door, typically for 1-2 people to collaborate for a limited time. The Phone room will have a work surface sufficient for up to 1-2 people, USB 5v power, and an IP phone with builtin speakerphone, and a duplex power outlet with USB receptacles. These spaces are open access, no room reservation required. User can use laptop for video conference.

Design Guidelines

Indeed Guidelines

111


Audio Visual Guidelines what: Technical where: Design Guidelines

2.2 Video Conference Rooms Conference Rooms are defined as a video conference meeting space for 4 to 12 people. The room is expected to be used only for the duration of a meeting and should be scheduled via the IT room reservation system. The Conference Room will have either a couch and/or stationary chairs, a table sufficiently sized for room occupants with a cut-in table box for Magsafe Macbook charger and IT connectivity. The room will have an IP Phone with built-in speakerphone, a separate speaker phone for video conference audio, a “prosumer” USB camera, dual or single Wall-mounted displays (depending on room size), Whiteboard, and a Mac-Mini with wireless keyboard and mouse for collaboration applications (Google Hangouts). These spaces are reservable and there shall be a iPad-mini mounted outside of the room connected to the IT room reservation system. Rooms must have acoustic treatment - ceiling tiles, wall panels, carpeting Must be inventory tagged, logged in Oomnitza along with the associated PO: • Mac Mini • Camera • TVs • Audio units (Phoenix, ClearOne, BiAmp, etc) • Anything over $500 Physically secured under the desk: • Magsafe charger block (so it can’t be easily removed from the room) iPad mount requirements: • Surface mount only (recessed mounts may cause heat issues) Post-install tasks: • Each conference room Mac Mini should be enabled with Nagios monitoring • Each conference room Mac Mini should have the audio settings script installed and tested

Indeed Guidelines

112


Audio Visual Guidelines what: Technical where: Design Guidelines

2.3 Training Rooms Training Rooms are defined as a conference meeting space that can accommodate 12 to 40 people with chairs and table workspaces. These spaces are primarily used for training purposes and may also serve as backfill for the Presentation Spaces. Sites that are designed with multiple Training Rooms, the First room should have dual projectors, locate the rooms adjacent to each other and have a retractable partition wall to join the Training Rooms together for larger audience use. Each room will be fitted with a movable podium at the front of the room. The podium should be functional from both the left and right side of the room. The AV equipment for each room typically consists of one single motorized large screen and one high-lumen projector, Mac-mini, Whiteboard, wireless mics, “prosumer” video cameras, mixing boards, audio amplification, wall mounted touch panel and speakers. Wall mounted AV box to include HDMI input plate (If First room, or primary Room add one HDMI output plate at same location) will route video signal route back to IDF for local source. Also to include 2 audio inputs. Where possible limit the amount of equipment in the room and the footprint of the wall mounted cabinet needed to secure the equipment, vertical mounting of equipment in a wall mounted secure cabinet is preferred. These spaces will also tie into the AV switching gear in the IDF that serves this space. These rooms are reserved via the Office Management team. Crestron programming to broadcast to Wonkavisions outside the room, site dependent. See Crestron programming document. Include acoustic treatments - ceiling, walls, floors

Indeed Guidelines

113


Audio Visual Guidelines what: Technical where: Design Guidelines

2.4 Interview Rooms Interview Rooms are defined as a video conference meeting space for 1 to 4 people. The room is expected to be used only for the duration of a meeting and should be scheduled via the IT room reservation system. The Interview Room will have a table sufficiently sized for room occupants and be located in the middle or up against the wall of the room. The room will have an IP Phone with built-in speakerphone, a separate speaker phone for video conference audio, a “prosumer” USB camera, single Wall-mounted display, a Whiteboard, and a Mac-Mini with wireless keyboard and mouse for collaboration applications (Google Hangouts). These spaces are reservable and there shall be an iPad-mini mounted outside of the room connected to the IT room reservation system.

Indeed Guidelines

114


Audio Visual Guidelines what: Technical where: Design Guidelines

2.5 Presentation Spaces Presentation Spaces are defined as the large gathering spaces for quarterly meetings and large presentations. These spaces are typically in the large kitchen areas or large commons areas in some campuses. The AV equipment typically consists of multiple large screens (Dual 80” or Drop Down Projectors) (motorized) and high-lumen projectors. Wireless mics, “Vaddio/Logitech PTZ” video cameras, mixing boards, audio amplification and speakers. These spaces will also tie into the AV switching gear in the IDF that serves this space. Wall mounted Crestron Panels along with HDMI input plates and one HDMI output plate at same location will route video signal route back to IDF for local source. In the front of the room where a podium is located there will be a wall plate along with an HDMI input which routes back the audio/video mixer in the back of the room. The podium will have a 25FT umbilical which allows the HDMI and other cables to be secured from the wall plate to inside the podium. These rooms will usually utilize Google Hangouts along with handheld mics/lapels but should also accommodate Rental equipment for global video conferences. These rooms are reserved via the Office Management team.

Note: Provide movable rolling cart to secure microphones, mixers, cameras, amplifiers, etc. Indeed Guidelines

115


Audio Visual Guidelines what: Technical where: Design Guidelines

2.6 Executive Conference Room Executive Conference Rooms are defined as the large meeting rooms for private meetings and presentations. The AV equipment typically consists of one large CUSTOM table, (coordinate with Architect and Real Estate group), Table or ceiling mics, mac mini, “prosumer” video cameras, DSP, touch panel, (optional Cable TV), local table source, audio amplification and ceiling speakers. The DSP will function as the room IP Phone and room mixer. This space may require control & integration with lighting and window shade systems. A credenza should be utilized in the room for the Local equipment rack, adequate cooling & space is required. These spaces will also tie into the AV switching gear in the IDF that serves this space. These rooms will usually utilize Google Hangouts for global video conferences. These rooms are reserved via the Office Management team. 2.7 Fitness Center (Gym / Yoga) Fitness Centers contain exercise equipment (gym) and Yoga rooms. Gym should have displays, room amplification, speakers, local Cable TV, local cable tv should be able to be distributed to wonkavision TVs. The Yoga room should not have video, but does require a local audio input and touch panel for control. There should be some sort of shelf/dock for audio device to rest and charge. Include a 5VDC USB socket within 1 foot of shelf.

Indeed Guidelines

116


Audio Visual Guidelines what: Technical where: Design Guidelines

2.8 Barista The Barista bar should have displays, room amplification, speakers, local Cable TV. Local Audio input plate should be provided in the space. The space be used for spill over and receiving Wonka or presentations. 2.9 Mothers Room The mother’s room should have data and local audio input via Bluetooth. The room should have a device that provides ambient noise (sound spa). No local devices provided by IT.

Indeed Guidelines

117


Audio Visual Guidelines what: Technical where: Design Guidelines

2.10 Reception The Receptionist desks is to have a counter suitable for an iPad/LobbyConnect device. The iPad will allow visitors/guests to check-in and have the Indeed Employee notified. A seating area next to the receptionist desk for guests to wait will be needed. In this area there should be a 55”-60” TV displaying Indeed Digital Signage. Music can also be playing overhead provided by an integrated Crestron system. A crestron touch panel will be behind the receptionist desk allowing them to control the music feed, sound levels and what’s displayed on the receptionist TV. Include CATV in the reception lobby with Crestron panel control. Include separate MacMini for Lobby “Welcome” message content and streming function. 2.11 Gaming Room A Gaming space should be designated near the IT Support space/lounge. This area will normally consist of a wall mounted 55-65” TV which will have HDMI input/outputs. The HDMI will feed the back of the TV to a wall plate 3 feet under the TV into a real estate supplied credenza. The credenza will house the gaming system used by the local Indeeders. 2.12 IT Support Help Desk Kiosk In sites which are larger than 200 people there will be a need for a dedicated IT Support Help Desk, Kiosk. A walk up counter along with seating for 2 or more technicians will be needed. Inside the IT Support Help Desk area there should be a centered table with several chairs. On the table a minimum of four or more power/data ports are required. On an adjacent wall an 80” TV or smaller should be mounted for video conference capabilities. Surrounding the centered table should also be cabinets which can support heavy equipment storage. The cabinets should be apple-store esk and have a glossy appearance. Designs will change based off of site size and location. 2.13 IT Support Staging/Storage Area Storage of onsite IT equipment will be needed for all sites. Shelving should be heavy duty and designed to hold over 100 lbs worth of equipment. Cabinets should also be considered. Dependent on site size and location designs will change. Storage areas may also contain a staging zone for IT Support. Staging includes a countertop/shelf which has power/data for technicians to image machines. Chairs will also be needed for each imaging station. Optional video equipment for hangouts can be added if space allows it. 2.14 Break Area Break area should have 50” display for CATV and WonkaVision content.

Indeed Guidelines

118


Audio Visual Guidelines what:

3. DIGITAL SIGNAGE

Technical

The purpose of this section is to define specific digital signage type names and equipment that will be used at the Indeed sites, this naming should also be used by the Architect, Real Estate, IT and AV Integrator. This will establish a common nomenclature for use by the project team for IT Digital Signage referencing.

where: Design Guidelines

3.1 WonkaVision WonkaVision displays are set in all common areas and open office spaces. The content is driven by the Indeed marketing department and physically connected via Mac minis. There should be one Mac mini configured per floor for this purpose, provided Crestron is being used to manage. These are typically 48-75-inch displays (specific sizes specified per site). The displays are wall mounted or pole mounted. All WonkaVision displays are centrally managed per floor via Crestron touchpanel controllers for content as well as function control such as on/off, volume/mute.

Wonkavision mounting standards • Dual back-to-back display ceiling mount directly above the center of desk space (avoid head clearance issues) • Ceiling mount around the perimeter of the office space • In-wall mount around the inside walls of office space • CATV output - Crestron controlled, single source control box in AV rack

Indeed Guidelines

119


Audio Visual Guidelines what: Technical where: Design Guidelines

3.2 Sales Floors & Sales Gongs Sales Floors & Sales Gongs displays (typically 50-inch wall-mounted or ceiling pole) are part of WonkaVision for content and control. Remote Desktop or local keyboard/touch screen should be used to connect to the Mac Mini behind the designated display for content changes. The location of the virtual gong should be location near physical Gong (Architect coordinated). The content includes a photo of each sales person in that area. When they close a sale, they can select their picture and a ten second clip of their chosen song plays across the sales floor via display speakers. Floor ceiling speaker zoning or grouping is also needed with each Sales Gong.

Indeed Guidelines

120


Audio Visual Guidelines what: Technical where: Design Guidelines

4. RESPONSIBILITY ASSIGNMENT The purpose of this section is to define the teams and responsibilities for the AV turnkey implementation. 4.1 AV integrator Responsibilities: 4.1.1 Pre-Construction • Coordination with Indeed IT teams to define AV requirements prior to starting design. • Conducting design review sessions with Indeed IT teams prior to final design document submittals to Architect • Providing Indeed IT team with construction drawings, parts list, and unit pricing for parts and labor for all AV equipment for the implementation. • Coordination with Architect, MEP and Real Estate teams for integrating all AV requirements (power, conduit, pathways, spaces, environmental, etc) into the construction documents. 4.1.2 Implementation • Mounting the display(s) to the wall or cart. • Connecting the Mac Mini system to the display(s). • Connecting the camera, mic(s), keypads and trackpad. • Placing and Connecting IP Phone. • Placing and Connecting conference speaker Phone. • Mounting and Connecting iPad mini 2. • Professional concealment/dressing of associated cables. • Proper activation and configuration of network connection(s). • Connecting and fishing cables through hollow walls/floors/ceilings or existing conduit. • Velcro remote control (TV and Camera) to back of display) • Creating project implementation schedule that is coordinated with the GC/CM construction schedule and Real Estate furniture schedule. • Daily clean-up of related installation area. • Turnkey AV System implementation/operation including, installation, configuration, and testing of the audio-video system for operation. • Documenting all change requests and submitting to Indeed IT (and GC where applicable) for approval. • Use Indeed check off list for final room verification. 4.1.3 Post-Construction • End user training. • As-Built documentation booklet - including drawings, parts list, and serial numbers. • Owner’s manuals. • System warranty. Indeed Guidelines

121


Audio Visual Guidelines what: Technical where: Design Guidelines

4.2 Indeed IT team responsibilities: 4.2.1 All project phases • Single point of contact for Client sign-off of design and change orders • Networks access and IP addressing schemes • Mac Mini and iPad imaging and application setup • Including imaging of Mac Minis for WonkaVisions and Sales Gongs • Room sign off upon the completion of the installation and testing • Project sign off after receipt of working systems and related documentation. 4.3 The GC/CM and Indeed Real Estate team responsibilities include: 4.3.1 Construction phase • Providing furniture • Give access to the meeting rooms, network IDFs and common areas requiring service, for the duration of installation and testing. • AC power for all equipment. • Any physical modifications to the facility (electrical wiring, reinforced wall for mounting, cable runs and drops, and lighting changes or sound abatement). • Conduit for all structured cabling runs • Digital pictures of typical conduit and termination points

Indeed Guidelines

122


Audio Visual Guidelines what:

5. ROOM PREPARATION

Technical

5.1 Meeting room prerequisites The following meeting room prerequisites have been identified

where: Design Guidelines

Indeed Guidelines

123


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

124


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

125


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

126


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

127


Audio Visual Guidelines what:

5.2 Standard Conference Room Line Diagrams

Design Standards - 2016

Technical where: Design Guidelines

Indeed Guidelines

128


Audio Visual Guidelines what:

5.3 Standard Conference Room Line Diagrams

Technical where: Design Guidelines

Figure 3: diagram of a typical conference room setup

A minimum of 1,2 m (4 ft) is required between the wall that will support the TV screen and the room table. If the meeting room is large, keep a larger space between the wall that will support the TV and the room table to allow a good pathway.

Indeed Guidelines

129


Audio Visual GuidelinesDesign Standards - 2016 what: Technical

5.4 Elevation Views (and details)

5.4 Elevation Views (and details)

where: Design Guidelines

See attached drawing at end of document Elevation detail of conduits

Elevation of display wall

Detail of backbox with

Indeed Guidelines

130


Design Standards - 2016

Audio Visual Guidelines what: Technical where: Design Guidelines

See attached drawing at end of document

Indeed Guidelines

131


Audio Visual Guidelines what:

6. INSTALLING EQUIPMENT

Technical where: Design Guidelines

Indeed Guidelines

132


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

133


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

134


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

135


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

136


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

137


Audio Visual Guidelines what:

6.1 Other meeting room equipment or applications

Technical where: Design Guidelines

Indeed Guidelines

138


Audio Visual Guidelines what: Technical where: Design Guidelines

7. ADDITIONAL SECTIONS 7.1. Summary Chart of digital signage types - table format with checklist, include connectivity and extra equipment Digital Signage Displays Pole Mount Display 48-50” Crestron DM-RMC-4K-100 Interior Wall Mount Display 70-75” Display Crestron DM-RMC-4K-100 Column mount displays NOT preferred. 7.2. Summary Chart/Visual of meeting room space types and differences - table format with checklist, include connectivity

Indeed Guidelines

139


Audio Visual Guidelines what:

7.3

Technical where: Design Guidelines

Indeed Guidelines

140


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

141


Audio Visual Guidelines what:

7.4

Technical where: Design Guidelines

Indeed Guidelines

142


Design Standards - 2016

Audio Visual Guidelines

7.5.

See “Design Standards IT Spaces, Cabling and Infrastructure” PDF

7.6.

See “Design Standards IT Spaces, Cabling and Infrastructure” PDF local matrix, touch panels, Crestron AV7.5.design - equipment drawing with head end, 7.6. Crestron AV design - equipment remote PC panel, cabinets, etc. drawing with head end, local matrix, touch panels, remote PC panel, cabinets,

what:

Technical where:

etc.

Design Guidelines

F & IDF Power and data cabinet requirements

Indeed Guidelines

143


Audio Visual Guidelines what: Technical where: Design Guidelines

7.7. MDF & IDF Power and data cabinet requirements One AV cabinet will be provided per floor, located in the MDF or IDF. Power required will be a dedicated 20A circuit. Black Box to provide drawing or photo. 7.8. Remote access requirements for Crestron TeamViewer app on local PC in IDF on Crestron network https://www.teamviewer.com/en/ 7.9. Parts list summary page conference room and digital signage 7.10. Warranty expectations and service maintenance expectations for all equipment

Indeed Guidelines

144


Audio Visual Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

145


Network Design Guidelines what: Technical where: Design Guidelines

The following Network Design content was compiled from the Network Design Standards V.1 2016, to provide detailed requirements for products and functional components within the Indeed workplace. INTRODUCTION This section presents the overall Indeed Facilities Design Standards Document. The purpose of this section is to acquaint design teams and construction professionals with the basic elements of Indeed’s room, construction, and cabling requirements, and to guide the design teams toward a consistent deployment throughout all Indeed Campuses. This will result in easy to use, high quality, reliable communication throughout all renovation and new building projects. Technology deployments require a well-coordinated, cohesive effort between the architects, electrical engineers, cabling contractors, network professionals, and integrators, as each is dependent on others to deliver a fully functional facility. This is to detail the elements, and provide installation and design guidelines. This standard provides guidelines for Indeed sites, room layouts, parts, equipment specifications, for the room types listed below. Any deviation from this standard must be approved and coordinated with the Indeed IT-Sys teams. 1. MDF REQUIREMENTS Larger buildings that are designated as an IT distribution point (this will be determined by the IT-Sys team per project) and new campuses will require a separate Main Distribution Frame to house local servers, controllers for digital signage, and telecommunications equipment. The construction must conform to the current ANSI/TIA 569 Standard for Commercial Building Telecommunications Pathways and Spaces. • • • • • •

The MDF should be at least 120 sq. ft. (10x12) in size, as geometrically square as possible, and located toward the center or core of the building structure. The room should be placed on the ground floor whenever possible due to equipment access and floor loading considerations. Avoid placing the Main Distribution Frame next to outside walls, elevator shafts, and/or internal fixed building walls. All perimeter walls shall be full height (deck-to-deck), 1-hour rated construction, fire sealed, and sealed to prevent chemical fire suppression leaks. The ceiling height should be at least 9 feet - 6 inches from finished floor surface. A primary 6 feet - 0 inches wide double door will be required for access to the hallway closest to the loading dock. All other door entrances should be at least 4 feet - 0 inches wide. There should be no water or plumbing distribution piping routed through the ceiling, room, walls, or plenum. There should not be any water related areas (coffee/break rooms, restrooms, etc.) above or adjacent to the MDF footprint.

Indeed Guidelines

146


Network Design Guidelines what: Technical where: Design Guidelines

1.1. MDF Power Requirements • Estimated power load should be 100KVA/80KW for the entire room. (This figure is based on about 100 watts per square foot to support high density computing.) • The power shall be overhead mounted to the ladder rack above the cabinets and racks. • All equipment outlets require “N+1” UPS backup (at least 15 minutes of battery backup) in the room • All UPS systems shall connect to the emergency generator system (if applicable) • Grounding and Bonding is required in accordance to the current ANSI/TIA 569 Standard for Commercial Building 1.2. MDF Telecommunications Pathways and Spaces • This will require a ground bus connection to the main Telecommunications Ground Bus. • An eight-lug grounding bar, attached to the main ground bus via a 6-awg copper cable, provided by the General Contractor. 1.3. MDF HVAC Requirements • 24-hour HVAC at an estimated 25-ton load, delivered via two 15-ton systems at either end of the room. • HVAC and power loads should be at least 100 watts per square foot to support high density computing. • HVAC must be connected to the room UPS and Emergency Generator System (if available). 1.4. MDF Room Safety • The Main Distribution Frame should be finished with static dissipative vinyl composition tile (VCT) or sealed concrete. • Electronic access control systems shall be employed via access card technology at each entry door for security purposes. • Surveillance cameras are required at the entry points of the interior of the room. • MDF Distribution Frame should have at least a pre-action fire suppression system. • An Emergency Power Off (EPO) switch should be installed in the MDF (only if required by code). • If required, the EPO should be mounted to the far left of the exit door and shielded by a plastic cover to prevent inadvertent activation. 1.5. MDF Cabling Access and Pathways • Each MDF will require four (4) four-inch sleeves with collars where needed for horizontal cable distribution. (To be specified per project) • Each MDF will require at least three (3) four-inch floor cores, with sleeves, for vertical backbone cable distribution. To be specified per project. • Cable tray shall be provided for at least 20 feet leaving the MDF. • A single four-inch core should also be provided in the mechanical or electrical room on each floor for a secondary fiber route from the Main Distribution Frame. Indeed Guidelines

147


Network Design Guidelines what: Technical

1.6. MDF Lighting • Required lighting to provide 50 foot candles measured 3 feet from the finished floor surface. • Lighting should be backed by an emergency generator.

where:

1.7. MDF Layout and Elevation Examples

Design Guidelines

2. IDF REQUIREMENTS Critical cabling, IP network, and A/V components will be housed in IDF situated throughout the space. These IDFs will house equipment for voice and data networks, as well as, security, audio/visual systems, overhead paging, and building automation systems. The construction must conform to the current ANSI/TIA 569 Standards for Commercial Building Telecommunications Pathways and Spaces. 2.1. IDF Dimensions and Locations • Every floor in each campus facility should have at least one IDF per 20,000 square feet of useable space. • All rooms should stack vertically within the building. • Each IDF should be centrally located, square in shape. Indeed Guidelines

148


Network Design Guidelines what: Technical where: Design Guidelines

• • • • • • •

Each IDF should be at least 110 sq. ft. in size (10 feet x 11 feet). No closet should be more than 260 feet from the most distant cable run assuming corridor cable routing. The doors should be a minimum of 30 inches in width. There should be no water or plumbing distribution piping routed through the ceiling, room, walls, or plenum. There shall not be any plumbing areas (coffee/break rooms, restrooms, etc.) above or adjacent to the IDF footprint. All walls should be covered with 1-inch plywood and painted with flame retardant paint. Lay in ceiling is neither required, nor recommended in the IDF.

2.2. IDF Power Requirements • An estimated power load of 7kVA/5.6kW per room will be required, however the design teams should carefully monitor systems selected and amend this projection as needed. • The power will be divided into circuits that are supported by the UPS/generator, and generator only. When the UPS is under maintenance, equipment will be supported in the IDF with no interruption. • Each IDF will require multiple 208vac circuits above the equipment racks and at least (4) 120vac 20amp ISO circuits on the walls. • Grounding and Bonding is required in accordance to the current ANSI/TIA 569 Standard for Commercial Building Telecommunications Pathways and Spaces. • This will require a ground bus connection to the main Telecommunications Ground Bus. • An eight-lug grounding bar, attached to the main ground bus via a 6-awg copper cable, provided by the General Contractor. 2.3. IDF HVAC Requirements • Each IDF will require a 24x7 HVAC capable of dissipating approximately 24,000 BTU/hour or 2 tons. • The HVAC systems in the IDF should be on the emergency generator. 2.4. IDF Room Safety • The IDF should be finished with static dissipative vinyl composition tile (VCT) or sealed concrete. • f code requires fire suppression, the water heads should be high temperature heads, and no water head or pipe should be positioned above the equipment racks. • At a minimum, each IDF should be secured with a key. • Electronic access control systems are recommended via access card technology at each entry door for security purposes. • A surveillance camera is required at each entry door. • All walls should be painted with flame retardant paint (White).

Indeed Guidelines

149


Network Design Guidelines what: Technical where: Design Guidelines

2.5. IDF Cabling Access and Pathways • Each IDF will require four (4) four-inch sleeves with collars above the door for horizontal cable distribution. • Each IDF will require three (3) four-inch floor cores, with sleeves, for vertical backbone cable distribution. • Cable tray shall be provided for at least 20 feet leaving the IDF. • A single four-inch core should also be provided in the mechanical or electrical room on each floor for a secondary fiber route to the Main Distribution Frame. 2.6. IDF Lighting • Required lighting to provide 50 foot candles measured 3 feet from the finished floor surface. • If required, lighting should be backed by an emergency generator.

3. TELCO DEMARCATION ROOMS (IF REQUIRED IN NEW CONSTRUCTION) This room provides for the distribution of networking and telecommunication services throughout each campus. These rooms have similar amenities as a typical IDF. Sometimes the D-Marc end room is an adjunct to the MDF or an IDF, where a separate room is generally not required. Each D-Marc room should be designed based upon the following criterion: 3.1. Dimensions and Locations • Room should be located as close to the Main Distribution Frame as possible. • Each D-Marc should be at least 200 sq. ft. in size. • A primary 6 feet - 0-inch double door will be required for access to the hallway closest to the loading dock. • There should be no water or plumbing distribution piping routed through the ceiling, room, walls, or plenum. • There should not be any water related areas (coffee/break rooms, restrooms, etc.) above or adjacent to the Main Distribution Frame footprint. • All walls should be covered with 3/4-inch plywood and painted with flame retardant paint. • Lay in ceiling is neither required, nor recommended. All walls should go deck-to-deck. 3.2. D-Marc Power Requirements • An estimated power load of 20kVA/16KW per room will be required, however the design teams should carefully monitor systems selected and amend this projection as needed. • The power will be supported by the Central UPS system, backed by the Emergency Generator system. • Each Technology Room will require multiple 208vac circuits above the equipment racks and at least (4) four 120vac 20amp ISO circuits on the walls. Indeed Guidelines

150


Network Design Guidelines what:

Technical where: Design Guidelines

Grounding and bonding is required in accordance to the current ANSI/TIA 569 Standard for Commercial Building Telecommunications Pathways and Spaces. (This will require a ground bus connection to the main Telecommunications Ground Bus.) An eight-lug grounding bar, attached to the main ground bus via a 6-awg copper cable, provided by the General Contractor.

3.3. D-Marc HVAC Requirements • The D-Marc will require a 7x24 HVAC capable of dissipating approximately 36,000 BTU/hour or 3 tons. • The HVAC systems in the D-Marc should be on the emergency generator. 3.4. D-Marc Room Safety • The D-Marc should be finished with static dissipative vinyl composition tile (VCT) or sealed concrete. • If code requires fire suppression, the water heads should be high temperature heads, and no water head or pipe should be positioned above the equipment racks. • At a minimum, each D-Marc should be secured with a key. • Electronic access control systems are recommended via access card technology at each entry door for security purposes. • A surveillance camera is recommended at each entry door. • All walls should be painted with flame retardant paint. 3.5. D-Marc Cabling Access and Pathways • Each D-Marc will require four (4) four-inch sleeves with collars above the door for horizontal cable distribution. • Each D-Marc will require three (3) four-inch floor cores, with sleeves, for vertical backbone cable distribution. • Cable tray shall be provided for at least 20 feet leaving the D-Marc. • A single four-inch core should also be provided in the mechanical or electrical room on each floor for a secondary fiber route to the D-Marc. 3.6. D-Marc Lighting • Required lighting to provide 50 foot candles measured 3 feet from the finished floor surface. • If required, lighting should be backed by an emergency generator.

Indeed Guidelines

151


Network Design Guidelines what: Technical where: Design Guidelines

4. BUILDING PATHWAYS AND ACCESS FOR CABLING Building pathways are defined as clear and un-obstructed conduits or cable trays for routing cabling into and within a facility. 4.1. Conduit Requirements (Main Distribution Frame) • Indeed recommends that each facility have at least two sets of four (4) four-inch conduits routed from the Main Distribution Frame to manholes in the utility easements. • Each set of conduits should have at least one 4-inch conduit clear for routing large pair counts of copper cable, and the other conduits should have three – 1 ¼-inch inter-ducts installed in them for fiber and CATV coaxial cable paths. • Each set of conduits should exit the facility at least 100 feet in separation and preferably on opposite sides of the facility. • These conduits are primarily for routing telecommunications services into the facility from the Telecommunications providers. 4.2. Conduit Requirements (Future Expansion) • Additional four inch conduits be stubbed out of each campus facility for future buildings and wireless connectivity in open areas of the campus such as parking lots. 4.3. Conduit Requirements (IDFs) • Each IDF should have two clear paths to the Main Distribution Frame to route redundant fiber risers to each IDF. 4.4. Conduit Requirements (Wall and Floor Outlets) • Each wall outlet that is accessible by an open ceiling will only require a “ring and string” single-gang opening. • All wall outlets that are not accessible by an open ceiling to include all wall phone outlets require at least a 1-1/2-inch conduit to accessible ceiling with a double-gang back box and a single-gang reducer. • All Presentation Areas should have a 1-1/2-inch conduit from the Podium to the overhead projector and/or to the plenum for A/V switch connections in the IDF. Verify routing per A/V designs. • Floor outlet locations should be capable of supporting at least four cables. • A one-inch conduit from the floor outlet location should be routed to the closest wall then to the plenum space for overhead routing. • The most common in-floor outlets used with high-end cable systems are the Walker RC4 Flush Quad poke-thru and the Hubbell PT4XBRS poke-thru.

Indeed Guidelines

152


Network Design Guidelines what:

5. CABLING (NETWORK)

Technical

5.1. Standard Network Data Cabling Standard Network Data Cabling shall terminate to the nearest IDF. These terminations will reside on the “Network Switching Rack” in each IDF.

where: Design Guidelines

a) Category 5e - Panduit family of products (unless otherwise specified). b) Universal Structured cabling – no distinction between voice or data. c) Horizontal cables per work outlet: • Administrative – 2 • Wall Phone – 1 • Typical Desk – 2 (Cables should be 6 ft to max 15 ft depending on the sit/stand capacity) • Presentation Podium – 2 • Wireless Access Points – 2 (Cat 6A) • Projectors – 1 • Security Camera - 1 • Conference Table cubby (Phone) – 1 • Conference Room A/V back box (for Mac-Mini) - 1 d) Patch Cord Colors: • Data - Blue • AV - Black • Security - White • Fire - Red • Wireless Access Point’s - Blue • Voice- Green e) Data Outlets: • White faceplates with White RJ-45 inserts 5.2. Cabling (AV Systems) AV Systems Cabling shall terminate to the nearest IDF. These terminations will reside on the “A/V Equipment Rack” in each specified MDF/IDF. a) Category 5e - Panduit family of products (unless otherwise specified). b) Cabling must terminate to the “A/V Equipment Rack” in each IDF. c) Horizontal cables per work outlet: • EventBoard iPad – (One) Category5e “POE switch only” Indeed Guidelines

153


Network Design Guidelines what: Technical where: Design Guidelines

• • • •

Crestron Display Touch Pad – (One) Category5e Wonka Vision Crestron DMRoom Controller: (One) 5e for RS232 control and (One) “Crestron Cat7” for HDMI signal Projector (One) “Crestron Cat7” for HDMI signal WattBox controller – (One) Category5e

5.3. Vertical Riser Cable (or MDF to IDF) • Two 24-strand multimode 50 Micron fiber optic cables to each IDF from the MDF, routed through separate pathways. • Cable must be armored or run through inner-duct. • Six Cat5e (or Cat 6) UTP or one 25 (or 50) pair UTP cable for analog lines 5.4. Inter-Building Connectivity • Two 48-strand Single-Mode (or 50 micron if within distance limits) fiber optic cables between each required building on a campus to the MDF, routed through separate pathways. • One 50 pair UPT Cat 3 rated • Cable is to be armored, OSP and Plenum rated. • Fiber to be terminated with LC connections. 6. WIRELESS COMMUNICATIONS 6.1. 802.11x Wireless • Initial estimate - One access point should be placed every 1,000 square feet. • Paper survey is required as part of wireless design - refer to Networking team • Two Category 6a cables will be pulled to each Wireless Access Point (WAP) location. • Each Wireless Access Point (WAP) location shall have two data cables installed and terminated to a single-port, surface mount box for each cable. • Leave a 20 foot ‘figure-8’ service loop in the plenum for each cable. 7. EQUIPMENT DESCRIPTIONS AND SPECIFICATIONS Based on the current Indeed standards, the following products should be used to provide for technology support in the MDF, IDFs, and D-Marc room (note that these products may change as the manufacturer updates their products. This is a guideline for selection). 7.1. MDF Infrastructure Products

Indeed Guidelines

154


Network Design Guidelines what:

7.2. IDF Infrastructure Products

Technical where: Design Guidelines

7.3. WAN Infrastructure Products Indeed Guidelines

155


Network Design Guidelines what:

7.4. Data Systems Products

Technical where: Design Guidelines

7.5 Voice Communications Products

7.6 Wireless Products

7.7. Uninterrupted Power Supply Products

Indeed Guidelines

156


Security Guidelines what: Technical where: Design Guidelines

The following Security content was compiled from the Physical Security Standards V.1 2016, to provide detailed requirements for products and functional components within the Indeed workplace. 1. INTRODUCTION The goal of this document is to advise the specifications of Indeed’s security standards. This document is meant to be given to architects, general contractors, integrators, and Indeed IT employees to understand the roles, responsibilities, and hardware standards of each build. 2. Responsibilities The Indeed Physical Security Team’s responsibilities for each site are as listed: • Floor plan markup • Building management requirements • Integrator management • Programming & testing • Employee access • Lobby intercom system The integrator installation responsibilities for each site are as listed: • Low voltage permitting (where applicable) • CAD drawings • Order and deliver all hardware to site • Subcontracting of low voltage work and cabling • Installation and hardware programming of Brivo & camera systems • Any applicable hardware tie-ins • Prep for building inspection • Communication with GC on timelines, progress 3. Office Requirements Indeed’s Physical Security team will install and manage a Brivo system in all offices with over 50 employees. For offices under 50 employees and Regus office spaces regardless of size, the building security system will be used. For subleased spaces over 50 employees, the site will be evaluated for Brivo and determined on a case-by-case basis.

Indeed Guidelines

157


Security Guidelines what: Technical where: Design Guidelines

4. MDF/IDF REQUIREMENTS Depending on the site size there will be at least one box enclosure which contains the Brivo panels and batteries. Each Brivo panel is the location where that current floors badge readers terminates into. This enclosure needs to be mounted on a 4x4 sheet of plywood.Security Standards - 2017 Depending on the site size there will be at least one box enclosure which contains the Brivo panels and batteries. Each Brivo panel is the location where that current floors badge readers terminates into. This enclosure needs to be mounted on a 4x4 sheet of plywood.

[NYC 13th Floor Example: Two 3-panel Brivo enclosures mounted on plywood]

[NYC 13th Floor Example: Two 3-panel Brivo enclosures mounted on plywood]

4.1. MDF/IDF Power Requirements a) For each box enclosure, the general contractor’s electrical contractor should provide (1) dedicated 20 AMP 120VAC Grounded Circuit as well as (1) Quad Outlet. (US Standard) 4.2. Brivo Panel/Cabling Requirements

Indeed Guidelines

158


Security Guidelines what: Technical where: Design Guidelines

4.1. MDF/IDF Power Requirements • For each box enclosure, the general contractor’s electrical contractor should provide (1) dedicated 20 AMP 120VAC Grounded Circuit as well as (1) Quad Outlet. (US Standard) 4.2. Brivo Panel/Cabling Requirements • Floor badge readers that terminate into the Brivo box utilize the following cable type: 446100-4 ELEM COMP CABLE WHITE JACKET • Cables should be protected in a conduit and only exposed at point of entry to the enclosure box (or as local code requires). • Single 18 Gauge 4 Conductor wire needs to be pulled from access control system to the closest Fire Alarm Relay. Fire alarm vendor will need to land these wires in the appropriate location in their relay and disclose if the relay should be programed as normally open or normally closed. 4.3. Port Requirements • Each Brivo box, regardless of size, needs one port. Each Exacqvision system needs two ports, plus one per camera. 5. BADGE READER REQUIREMENTS Badge readers can be found in the following doors: vestibules, IT Help Desk, Executive Board rooms, MDF/IDF, Facility/ Help Desk Storage Closets etc, stairwell entries, and lobby areas. Badge readers are to be installed at the required ADA height of four (4) feet. All badge readers are POE and their relevant cables terminate into that floors Brivo Panel located in either the MDF or IDF. Cabling for these readers is 446100-4 Elemen Comp Cable (white jacket).

[HID multiCLASS SE readers]

Indeed Guidelines

159


Security Guidelines what: Technical where: Design Guidelines

6. DOOR LOCKING HARDWARE Depending on door hardware there are 3 options for locking hardware (in order of preference): 1. Electrified Handset 2. Electric Strike 3. Magnetic Locks This hardware is to be specified by the architect and provided/installed by the general contractor. See diagrams and plans in below 3 drawings: Electrified Handset, Electrified Strike, Magnetic Locks. For Mother’s Rooms, we require both a privacy function latchset as well as a electrified door handle/strike. The intent is so the door is locked via a badge reader at all times, and when a user enters the room the deadbolt/latchset will lock from the inside to ensure no interruptions from a badge read.

Indeed Guidelines

160


Security Guidelines what: Technical

Electrified Handset:

Electrified Handset:

where: Design Guidelines

Security Standards - Version 5

Indeed Guidelines

161


Security Guidelines what: Technical

Electric Strike:

Electric Strike:

where: Design Guidelines

Indeed Guidelines

162


Security Guidelines what: Technical

Magnetic Locks:

Magnetic Locks

where: Design Guidelines

7. Exiting Door Hardware When anyone is walking towards a locked door from inside the office it can unlock in three different ways: Indeed Guidelines 1. Push-bar 2. Exit push-button

163


Security Guidelines what: Technical where: Design Guidelines

7. EXITING DOOR HARDWARE When anyone is walking towards a locked door from inside the office it can unlock in three different ways: 1. Push-bar 2. Exit push-button 3. Motion sensor unlock This door hardware is defined and supplied by the architect and general contractor. The exit buttons and motion sensors are supplied by the security integrator. 8. DURESS BUTTON A single ½ inch EMT conduit run with pull string from nearest IDF to underneath reception desk for duress button. This is to be supplied by general contractor. 9. DOOR RELEASE BUTTON BUTTON Each reception desk requires a door release button to unlock the reception door. 10. CAMERAS Cameras can be found covering the following locations: MDF/IDF door from the inside of the room, stairwell doors from the inside of Indeed space (not inside the stairwell), lobby doors inside the Indeed space, facing the interior side of the IT Help Desk, and Reception (over desk/facing main door). Cameras are cabled utilizing cat6a cabling which feeds back into that floors MDF/IDF. 10.1. Camera Hardware Exacqvision systems can be found in the MDF/IDF of each floor. All Samsung 2mp SNV-6013 cameras on that floor terminate into this box. Exacqvision is a server-based local recording VMS system.

[Samsung 2mp SNV-6013]

[Exacqvision video surveillance system] Indeed Guidelines

164


Security Guidelines what:

11. KEY CONTROL

Technical

All keyways must be small format interchangeable core SCHLAGE Everest R124 Keyways. All offices must be rekeyed before Indeed moves into the space. If building management allows. Indeed security will provide the cores and keys required for the office and provide building management with an appropriate number of keys for access. Offices of less than 100 people should have a single keyway that controls all doors. An appropriate number of keys should be created and and maintained by the office manager.

where: Design Guidelines

12. Security Timeline and Key Milestones In order for the security installation to be successful there are some key milestones that need to be communicated from the project management team. (Milestones in BOLD) 1. Security needs to mark site plans as soon as door locations and construction is mostly finalized. Any changes to door locations or hardware later in the project need to be communicated to the security team as soon as possible in case changes need to be made to security permit drawings. 2. When do we get access to the building? Security integrators will need to walk the space to quote the project and security will need to make sure appropriate security devices are being installed. (Should allow 4-6 weeks for quoting, procurement and delivery of equipment) 3. When are the walls closing? Security vendor needs to have cables pulled or verified pathways exist to reach each device. This is also when they check to make sure doors have been prepared correctly and all equipment has arrived for installation. 4. When are the doors hung? Nothing can be tested until the final doors are installed in place. 5. Security will work with IT on determining when the network is operational. Brivo access control will not function until the panel is able to reach the network. Cameras cannot be aimed, focused or verified in the system until the network is operational. 6. “Go live date” Security team needs to know when to book travel for each location so we can have team members available on move weekend and for the first day or 2 for support.

Indeed Guidelines

165


Security Guidelines what:

13. SAMPLE RESOURCE LIST

Technical where: Design Guidelines

Indeed Guidelines

166


Security Guidelines what: Technical where: Design Guidelines

Indeed Guidelines

167