CALIFORNIA STATE UNIVERSITY, SACRAMENTO
FOLSOM HALL BLDG 2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 6000 J STREET, SACRAMENTO, CA 95819 CSFM FILE # 18-N-2834-C-NW
12/21/2018 - 100% Construction Documents 04/26/2019 - CALFIRE RESUBMITTAL 05/06/2019 - DSA OTC
Design Build Team CONTRACTOR: XL CONSTRUCTION 1810 13th Street, Suite 110 Sacremento, California 95811 (916) 282-2900
MECHANICAL/ ELECTRICAL
PETERS ENGINEERING 2411 ALHAMBRA BLVD SUITE 100 SACRAMENTO, CA 95817 (916) 447-2841
LIONAKIS ARCHITECT Nineteenth Street /STRUCTURAL 1919 Sacramento, California 95811 /INTERIORS: (916) 558-1900
G-000
2
3
4
5
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 7667 FOLSOM BLVD, SACRAMENTO, CA 95826 D
FOLSOM HALL 2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS MAY 6, 26, 2019 APRIL 2019
DSA APPROVED SET 100% CONSTRUCTION DOCUMENTS
A2 A-303
A2 A-303
SECTION INDICATOR - BUILDING
A4 A-201
ELEVATION INDICATOR - EXTERIOR A1
A-202
A2
A4
A-202
A2
ELEVATION INDICATOR - INTERIOR, SINGLE & MULTIPLE VIEW
A3
MATCH LINE SEE XX / X-XXX
MATCH LINE INDICATOR
1 A
REFERENCE GRID WITH REFERENCE GRID LINES
REVISION INDICATOR & REVISION CLOUD 22
ROOM NAME 101 LEVEL 1 100'-0"
ROOM IDENTIFIER WITH ROOM NAME & NUMBER
TOC 98'-8"
10
22
ELEVATION INDICATOR - LEVEL & SPOT
WINDOW OR LOUVER IDENTIFIER
KEYNOTE INDICATOR
B PLAN NORTH
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
PLAN NORTH & TRUE NORTH INDICATOR
LOCATION MAP
CG CI CJ CL CLG CLR CMU CNTR CO COL CONC CONSTR CONT COTG CP CPT CRS CSK CSWK CT CTR DBL DEPT DET
EIFS EJ EL ELEC ELEV EMER ENCL EPB EQ EQUIP EW EWC EXH EXST EXP EXT FA FB FD FDTN FE FEC FIN FLG FLL FLR FOC FOF FOM FOS FOW FP FRP FT FTG FURG FUT G GA GALV GB GI GLU LAM GYP HB HC HDBD HDW HDWD HM HORIZ HR HT ID INSUL INT JAN KIT L LAB
VICINITY MAP
OFF OGL OPH OPNG OPP PAF PL PLAM PLB PLBG PLYWD PNL PROP PSF PSI PT PTN PV QT R RD REBAR REF REF REINF REQD RESIL RM RO RWD RWL SAD SATC SB SC SCHED SD SDST SHT SHTHG SHV SIM SLNT SM SPEC SQ SS
LAVATORY MATERIAL MAXIMUM MECHANICAL MEMBRANE MANFACTURER MANHOLE MINIMUM MISCELLANEOUS MASONRY OPENING MOISTURE RESISTANT MOUNTED METAL MULLION NOT IN CONTRACT NUMBER NOMINAL NOT TO SCALE OVER ON CENTER OUTSIDE DIAMETER OWNER FURNISHED / CONTRACTOR INSTALLED OFFICE OBSCURE GLASS OPPOSITE HAND OPENING OPPOSITE POWER ACTUATED FASTENER PROPERTY LINE; PLATE PLASTIC LAMINATE PLUMB PLUMBING PLYWOOD PANEL PROPERTY POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH PAINT; PAINT PARTITION PHOTOVOLTAIC QUARRY TILE RADIUS; RISER ROOF DRAIN REINFORCING STEEL BAR REFERENCE REFRIGERATOR REINFORCE / REINFORCING REQUIRED RESILIENT ROOM ROUGH OPENING REDWOOD RAIN WATER LEADER SEE ARCHITECTURAL DRAWINGS SUSPENDED ACOUSTICAL TILE CEILING SPLASH BLOCK SOLID CORE SCHEDULE STORM DRAIN SELF DRIVING, SELF TAPPING SHEET SHEATHING SHELVING SIMILAR SEALANT SHEET METAL SPECIFICATION SQUARE SANITARY SEWER; SERVICE SINK
SST STD STL STOR STRUCT SUSP CLG SV SYMM SYS T T&G TEL THK TMH TMPD TO TOC TOF TOJ TOM TOP TOPO TOS TOW TV TYP UC UNO UON UR VCT VERT VEST VIF VWC VWF W/ W/O WC WD WH WO WP WPM WSCT WT WTR WWR
STAINLESS STEEL STANDARD STEEL STORAGE STRUCTURAL SUSPENDED CEILING SHEET VINYL SYMMETRICAL SYSTEM TREAD TONGUE & GROOVE TELEPHONE THICKNESS TOP OF MANHOLE TEMPERED TOP OF TOP OF CURB TOP OF FRAME TOP OF JOIST TOP OF MASONRY TOP OF PARAPET TOPOGRAPHY TOP OF STEEL TOP OF WALL TELEVISION TYPICAL UNDER COUNTER/CABINET UNLESS NOTED OTHERWISE UNLESS OTHERWISE NOTED URINAL VINYL COMPOSITION TILE VERTICAL VESTIBULE VERIFY IN FIELD VINYL WALL COVERING VINYL WALL FABRIC WITH WITHOUT WATER CLOSET WOOD WATER HEATER WHERE OCCURS WORKING POINT WATERPROOF MEMBRANE WAINSCOT WEIGHT WATER WELDED WIRE REINFORCEMENT
GENERAL G-000 COVER SHEET G-001 GENERAL INFORMATION GA101 CAMPUS SITE GL111 LIFE SAFETY FLOOR PLAN - LEVEL 1 GL112 LIFE SAFETY FLOOR PLAN - LEVEL 2 GL112.2 PARTIAL LIFE SAFETY FLOOR PLAN - LEVEL 2 G-111 ACCESSIBILITY REQUIREMENTS
THE PROVIDED CIVIL, DRAWINGS, SPECIFICATIONS, AND/ OR CALCULATIONS HAVE BEEN PREPARED BY OTHER DESIGN PROFESSIONALS OR CONSULTANTS WHO ARE LICENSED AND/OR AUTHORIZED TO PREPARE SUCH DRAWINGS IN THIS STATE. THESE DOCUMENTS HAVE BEEN EXAMINED BY ME FOR THE DESIGN INTENT AND APPEAR TO MEET THE APPROPRIATE REQUIREMENTS FOR TITLE 24, CALIFORNIA CODE OF REGULATIONS AND THE PROJECT SPECIFICATIONS PREPARED BY ME, AND COORDINATION WITH MY PLANS AND SPECIFICATIONS IS ACCEPTABLE FOR INCORPORATION INTO THE CONSTRUCTION OF THIS PROJECT. THE STATEMENT OF GENERAL CONFORMANCE "SHALL NOT BE CONSTRUED AS RELIEVING ME OF MY RIGHTS, DUTIES, AND RESPONSIBILITIES UNDER SECTIONS 17302 AND 81138 OF THE EDUCATION CODE AND SECTIONS 4-336, 4-341 AND 4-344" OF TITLE 24, PART 1. (TITLE 24, PART 1, SECTION 4-317(b))
ARCHITECTURAL A-112 FLOOR PLAN - LEVEL 2 - OVERALL A-112A PARTIAL FLOOR & CEILING PLAN - LEVEL 2 - AREA A & B AF112A PARTIAL FINISH FLOOR & SIGNAGE PLAN - LEVEL 2 E2.01 (E) LIGHTING (FOR REFERENCE ONLY) FA2.01 (E) FIRE ALARM (FOR REFERENCE ONLY) FP1 (E) FIRE SPRINKLER (FOR REFERENCE ONLY) A-221 ELEVATIONS - INTERIOR A-531 PARTITION TYPES & SCHEDULE A-532 STANDARD METAL STUD DETAILS & SCHEDULES A-533 STANDARD METAL STUD DETAILS A-541 DOOR AND WINDOW SCHEDULE & DETAIL A-551 SUSPENDED CEILING DETAILS - TYPICAL A-561 DETAILS - CASEWORK
05/26/2019 04/25/2019
JONATHAN MCMURTRY | LIONAKIS PRINTED NAME OF ARCHITECT
C23603
G H V B C L S A I Q F P D M E W T R X Z O
PROJECT LOCATION
A
GENERAL HAZARDOUS MATERIALS SURVEY/MAPPING GEOTECHNICAL CIVIL LANDSCAPE STRUCTURAL ARCHITECTURAL INTERIORS EQUIPMENT FIRE PROTECTION PLUMBING PROCESS MECHANICAL ELECTRICAL DISTRIBUTED ENERGY TELECOMMUNICATIONS RESOURCE OTHER DISCIPLINES CONTRACTOR/SHOP DRAWINGS OPERATIONS
D A RCH SE I E N A N McM TE H U T A
C23603 T
R E
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD, SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
MECHANICAL M-001 SYMBOLS, NOTES & SCHEDULE M-112 FLOOR PLAN - LEVEL 2 - OVERALL M-113 PARTIAL FLOOR PLAN - MECHANICAL ELECTRICAL E-001 SYMBOLS, NOTES & SCHEDULE E-002 TITLE 24 E-112 FLOOR PLAN - LEVEL 2 - OVERALL E-113 PARTIAL FLOOR PLANS - POWER E-114 PARTIAL FLOOR PLANS - LIGHTING E-301 ONE LINE DIAGRAM E-401 DETAILS E-402 DETAILS
ISSUED MARK
FIRE ALARM FA-001 SYMBOLS, NOTES & SCHEDULE FA-112 FLOOR PLAN - LEVEL 2 - OVERALL FA-113 PARTIAL FLOOR PLANS - FIRE ALARM FA-301 ONE LINE DIAGRAM & DETAILS
DATE
DESCRIPTION
PROJECT DATA & APPLICABLE CODES CONTRACTOR SHALL VERIFY DIMENSIONS, ELEVATIONS, PROPERTY LINES, ETC PRIOR TO CONSTRUCTION.
2.
CONTRACTOR SHALL NOTIFY THE ARCHITECT WHERE CONFLICT OCCURS ON ANY OF THE CONTRACT DRAWINGS OR DOCUMENTS. CONTRACTOR IS NOT TO ORDER MATERIAL OR CONSTRUCT ANY PORTION OF THE BUILDING THAT IS KNOWN TO BE IN CONFLICT UNTIL THE CONFLICT IS RESOLVED WITH THE AFFECTED PARTIES. 3. CONSTRUCTION SHALL CONFORM TO ALL APLLICABLE CODES AND REGULATIONS AND CURRENT GOVERNING CODES: SEE SHEETS G-001, GL111, GL112, AND GL112.2. BUILDING NO.: SFM FILE NO.:
SFM BUILDING NO. 91/CSUS BUILDING NO.65 #18-N-2834-C-NW
DSA FILE NO.: PRIOR APPLICATIONS: 34-CSUS , CFSM # 18-34-03-0001
SCOPE OF PROJECT
4.
WORK INCLUDES ALL SCOPE WITHIN THESE DOCUMENTS INCLUDING BUT NOT LIMITED TO: 1. FOLSOM HALL TENANT IMPROVEMENT OF 2,430 SQ FT WITHIN THE EXISTING BUILDING FOOTPRINT. THE IMPROVEMENT WILL CONSISTS OF 3 AUDIOLOGY LABS, 1 COMPUTER LAB, AND 1 CLASSROOM WITH MODIFICATION OF EXISTING FIRE ALARM, ADDITIONAL SPRINKLER HEADS, MECHANICAL DIFFUSERS, POWER, LIGHTING, DOORS, SIGNAGE, FINISHES, SUSPENDED CEILING, AND CASEWORKS.
SHEET TYPE DESIGNATORS 0 - GENERAL 1 - PLANS 2 - ELEVATIONS 3 - SECTIONS 4 - LARGE SCALE VIEWS 5 - DETAILS 6 - SCHEDULES & DIAGRAMS 7 - USER DEFINED 8 - USER DEFINED 9 - 3D REPRESENTATIONS
DEFERRED SUBMITTALS NONE
5.
CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE CODES AND REGULATIONS, INCLUDING BUT NOT LIMITED TO: 2016 CBC CH 35 2016 CFC CH 80 TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHALL REGULATIONS TITLE 24 CCR, PART 1 - 2016 BUILDING STANDARDS ADMINISTRATIVE CODE TITLE 24 CCR, PART 2 - 2016 CALIFORNIA BUILDING CODE, VOL.1 & 2 (CBC) TITLE 24 CCR, PART 3 - 2016 CALIFORNIA ELECTRICAL CODE (CEC) TITLE 24 CCR, PART 4 - 2016 CALIFORNIA MECHANICAL CODE (CMC) TITLE 24 CCR, PART 5 - 2016 CALIFORNIA PLUMBING CODE (CPC) TITLE 24 CCR, PART 6 - 2016 CALIFORNIA ENERGY CODE TITLE 24 CCR, PART 9 - 2016 CALIFORNIA FIRE CODE (CFC) TITLE 24 CCR, PART 11 - 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE TITLE 24 CCR, PART 12 - 2016 CALIFORNIA REFERENCED STANDARDS 2016 NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS (CA AMENDED) 2016 NFPA 14, INSTALLATION OF STANDPIPE AND HOSE SYSTEMS 2016 NFPA 17, DRY CHEMICAL EXTINGUISHING SYSTEMS 2013 NFPA 17A, WET CHEMICAL EXTINGUISHING SYSTEMS 2016 NFPA 20, INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION 2013 NFPA 22, WATER TANKS FOR PRIVATE FIRE PROTECTION 2016 NFPA 24, INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES 2013CA NFPA 25, INSPECTION, TESTING, MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS (CA AMENDED) 2016 NFPA 72, NATIONAL FIRE ALARM CODE (CA AMENDED) 2016 ICC 300, BLEACHERS, FOLDING AND TELESCOPIC SEATING, AND GRANDSTANDS
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
PROJECT DIRECTORY
016279.06 ?00.00.00? LIONAKIS 2015
AGENCY
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
A MINIMUM OF 72 HOUR NOTICE IS REQUIRED FOR ANY TESTING AND/OR INSPECTION. AC
FLS
SS
DATE
AUTHORITIES HAVING JURISDICTION TITLE
DISCIPLINE DESIGNATOR - LEVEL 1
CONTRACTOR
ARCHITECT/ STRUCTURAL/ INTERIORS
XL CONSTRUCTION 1810 13TH STREET SACRAMENTO, CA 95811 PHONE: 916.282.2900
LIONAKIS 1919 19TH STREET SACRAMENTO, CA 95811 PHONE: 916.558.1900
DISCIPLINE DESIGNATOR - LEVEL 2 REPLACE DASH WHERE OCCURS
SHEET TYPE DESIGNATOR SHEET TYPE SUBSET DESIGNATOR LEVEL/SEQUENCE DESIGNATOR AREA IDENTIFIER - WHERE OCCURS UNIQUE PORTION IDENTIFIER - WHERE OCCURS
C.A-123AB
EXPIRATION DATE
FIRE PROTECTION FP-100 PARTIAL FLOOR PLAN - FIRE SPRINKLER PIPING IMPROVEMENT
1.
BUILDING IDENTIFIER - WHERE OCCURS
PROJECT LOCATION
08/31/2019
LICENSE NUMBER
SHEET IDENTIFICATION LEGEND DISCIPLINE DESIGNATORS - LEVEL 1
DATE
SIGNATURE OF ARCHITECT
SEAL
IA
LAV MATL MAX MECH MEMB MFR MH MIN MISC MO MR MTD MTL MULL NIC NO NOM NTS O/ OC OD OF/CI
A
SECTION INDICATOR PARTIAL BUILDING/WALL & DETAIL INDICATOR - AREA
D2 A-512
DRINKING FOUNTAIN DETENTION HOLLOW METAL DIAMETER DIMENSION DOWNSPOUT DRY STANDPIPE DRAWING DRAWER EACH EXTERIOR GYPSUM SHEATHING BOARD EXTERIOR INSULATION AND FINISH SYSTEM EXPANSION JOINT ELEVATION ELECTRIC / ELECTRICAL ELEVATOR EMERGENCY ENCLOSURE ELECTRICAL PANEL BOARD EQUAL EQUIPMENT EACH WAY ELECTRIC WATER COOLER EXHAUST EXISTING EXPANSION EXTERIOR FIRE ALARM FLAT BAR FLOOR DRAIN FOUNDATION FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET FINISH FLOORING FLOW LINE FLOOR FACE OF CONCRETE/CURB FACE OF FINISH FACE OF MASONRY FACE OF STUD FACE OF WALL FIREPROOF FIBERGLASS REINFORCED PLASTIC FEET / FOOT FOOTING FURRING FUTURE GROUND; NATURAL GAS GAGE GALVANIZED GRAB BAR GALVANIZED IRON GLUED LAMINATED WOOD GYPSUM HOSE BIB HOLLOW CORE HARDBOARD HARDWARE HARDWOOD HOLLOW METAL HORIZONTAL HOUR HEIGHT INSIDE DIAMETER INSULATION INTERIOR JANITOR KITCHEN ANGLE LABORATORY
ST
B3 A-301
DF DHM DIA DIM DS DSP DWG DWR EA EGSB
N
DETAIL INDICATOR - SECTION & DETAIL INDICATOR - SECTION ITEM
B3 A-501
& @ (E) ' " # ALUM ARCH A/C UNIT A/E AB AC ACC ACS DR ACS PNL ACST AD ADC ADO ADDL ADJ SHV AFF AFG AGGR AHU ASSY BD BKG BLDG BM BM BOT BTWN BUR BW C CAB CB CBC CEM CEM PLAS CFLG CFMF
SEE UNITED STATES NATIONAL CAD STANDARD FOR ANY ABBREVIATIONS NOT LISTED BELOW. AND AT EXISTING FOOT, FEET INCH(ES) NUMBER ALUMINUM ARCHITECTURAL AIR CONDITIONING UNIT ARCHITECT / ENGINEER ANCHOR BOLT ASPHALTIC CONCRETE ACCESSIBLE ACCESS DOOR ACCESS PANEL ACOUSTIC AREA DRAIN AUTOMATIC DOOR CLOSER AUTOMATIC DOOR OPERATOR ADDITIONAL ADJUSTABLE SHELVING ABOVE FINISHED FLOOR ABOVE FINISHED GRADE AGGREGATE AIR HANDLING UNIT ASSEMBLY BOARD BACKING BUILDING BEAM BENCHMARK BOTTOM BETWEEN BUILT-UP ROOFING BOTH WAYS CHANNEL CABINET CATCH BASIN CALIFORNIA BUILDING CODE CEMENT CEM PLASTER COUNTERFLASHING COLD-FORMED METAL FRAMING CORNER GUARD CAST IRON CONSTRUCTION JOINT / CONTROL JOINT CENTER LINE CEILING CLEAR CONCRETE MASONRY UNIT COUNTER CLEANOUT COLUMN CONCRETE CONSTRUCTION CONTINUE / CONTINUOUS CLEANOUT TO GRADE CONTROL PANEL CARPET COLD ROLLED STEEL COUNTER SUNK CASEWORK CERAMIC TILE CENTER DOUBLE DEPARTMENT DETAIL
CT Y R RT
B3 A-501
C
DETAIL INDICATOR - REFERENCE & DETAIL INDICATOR - ITEM
D2 A-512
ARCHITECT'S STATEMENT
SHEET INDEX
9
D2 A-512
LIST OF ARCHITECTURAL ABBREVIATIONS
R
ARCHITECTURAL SYMBOLS LEGEND
4/25/2019 8:48:47 AM
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
LI JO C N
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
MECHANICAL/ELECTRICAL PETERS ENGINEERING 2411 ALHAMBRA BLVD SUITE 100 SACRAMENTO CA 95817 PHONE: 916.447.2841
3RD PARTY PLAN REVIEW BUREAU VERITAS NORTH AMERICA, INC. 180 PROMENADE CIRCLE, SUITE 150 SACRAMENTO CA 95834 PHONE:916.725.4200. FAX:916.725.8242
CAL FIRE OFFICE OF THE STATE FIRE MARSHAL FIRE AND LIFE SAFETY - NORTH 2251 HARVARD ST, SUITE 400 SACRAMENTO. CA 98518 PHONE: 916.568.3800
GENERAL INFORMATION
DSA CALIFORNIA DIVISION OF THE STATE ARCHITECT DSA SACRAMENTO REGIONAL OFFICE 1102 Q ST, SUITE 5200 SACRAMENTO, CA 95811 PHONE: 916.445.8730
SHEET
G-001
FIRE PUMP ROOM STO P
FO
O LS
T LO 14
LANE BIK E
M
L HA
L
KNOX BOX DSA APP# 02-111537 FOR EXISTING PARKING LOT
MANAGEMENT 78'-0"
BUILDING 2 (E) FIRE ALARM CONTROL PANEL, SEE SHEET GL111
FIRE SEPARATION DISTANCE 24'-0"
TYP 174'-0" 51'-0"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
DSA APP# 02-111537 FOR EXISTING PARKING LOT
TITLE A
(E) FIRE DEPARTMENT CONNECTION
PLAN NORTH
SS FLS AC
016279.06 ?00.00.00? LIONAKIS 2015
BUILDING 1
CAMPUS SITE (E) FIRE HYDRANT
(E) FIRE HYDRANT (E) FIRE HYDRANT
210'-0" LA NE
78'-0"
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT: 24'-0"
77'-0" G IN E RK UR PA UCT R IV ST
BE IK
30'-0" LA NE
52'-0" 21'-0" 19'-5" 11'-6" BIE K
LANE
CLEA R KEEP
CLEA R KEEP
CLEA R
C DO MO ALL H
State University Dri ve PA NA LL HA
" '-0 42 T.= .00 . H 39 DG L.= BL FL. E
BE IK
SCALE 1" = 400'-0"
77'-0" 79'-0"
26'-0"
LANE IK BE
SCALE 1" = 40'-0"
" '-0 70 T.= .50 . H 40 DG L.= BL FL. E
AL PIT C CA BLI PU DIO RA
NORTH
DESCRIPTION DATE MARK STOP
" '-0 30 T.= .00 . H 40 DG L.= BL FL. E
ard
2 GA101
(E) 2 HOUR RATED BUILDING SEPARATION FIRE WALL 43'-0"
LANE K BE I
T LO 9
71'-0" Fols om Bou lev
17'-8 131/256"
85'-0"
BUILDING PERIMETER WITH LESS THAN 30'-0" MIN. FRONTING = 166'-0"
R
N
9
IA
LI JO C N
LANE
STOP
STOP
ST OP ST OP STO P
BIK E
LANE
ONL Y ONL Y ONL Y
PLAN NORTH T LO 0 1
STOP
(E) PARKING GARAGE LEVEL 2 3
30'-0"
20'-4"
LANE
BIK E LANE
LANE
AH EAD
BE IK
SIGNAL
d ilr oa Ra
E BIK
KEEP
STOP STOP
T7 LO T H U SO
STOP
NI UM R AL NTE CE
1F
STO P
ONL Y
3F
cif ic Pa
ve College Town Dri
(E) PARKING GARAGE LEVEL 1 " '-0 25 T.= .0 0 . H 39 DG L.= BL L. E F
Callery Pear Way YIELD
D 0" OA 27'-IC BRG. HLT.=.=E3T7.6 0 Y D EL IT BLTLH A F . CIL FA
B
ern uth So
LANE
BE IK
STOP
STOP
STOP
LANE
STOP
K GM
3F
Stadium Drive 3F K GM
2F
B
F 1F 1F 2
ive Dr wn To
A LNE
BE IK
T LO 8
3F
ET RN M HO ADIU ST
e lleg Co
3F
BIK E
State University Drive
1F
3F
1G
3F
ONL Y
CT Y R RT
A
STOP STOP
T7 LO RTH NO
STO P STO P
2F
1G
1G
EL2-8
ST
" T 4R '-0E 2 0 AR TT.=U .0 . HP.= 43 GL L B DU SBCL FL . ELA
IC BL PU FET Y SA " '-0 21 T.= .5 0 . H 39 DG L.= BL L.E F
1A
CG CG CG 1F
ive Dr 3F K GM
STOP
E
H UT SO ER ) T 4 ND ION LO T . (U U CT EX STR N CO
STOP
ium
ve Dri ith Sm ay ar W ry Pe Calle
d Sta
G '-6 " 0 I N.= 53 E RGK. HTLT.=U36R.0 D .C E PA BL FU R L III ST
LOT 12
E TH LL WE
" '-5 51 T.= .2 0 . H 38 DG L.= BL FL.E
1E
IC ET HL GE AT ORA ST
STOP
IK
T4 LO T H U SO
. FL
d Je
E TIC AC K PR RAC T
1E
STOP
B
STOP
B
T I LD EN C H OPM NEX N " L V E R A 5'-0 DE NTE HT.=10.2 0 C E LDG. EL.=4
.E FL
1E
CIA " NI .=L46'-00 LT .0 BE A HG. H .=39 L D BL L. E F
STOP
STOP
BEKI
STOP
B
T ILD EN CH OPM " 0 L E1R 2'VE NT T.= .2 5 DE CLDEG. HL.= 39
1E
1E
WS RO S TH NUE VE
STOP
BIEK
ive Dr ity ers
G IN E RK UR 6'-0 " P A UCTHT.=349.00 R . ST BLDFGL.IEIL.=
T LO 6
E HO TA ALL H
1E
" '-2 38 T.= .5 0 . H 36 DG L.= BL FL.E
1E
1D
3D
3D
College Town Drive
LANE
ET RN ING HO SS O CR
A LNE
iv Un ate St ET RN'-6"ORE HOT.=K5.=8S3T9.0 0 HO L BOFL.E
T LO 5
XFMR
. .R.C A.I
'6" 70 T.= .6 7 . H 28 DG L.= BL L. E F
1D
1D 1D
3D
BIK E
E
PARKING NO
T4 LO RTH NO
LANE
RC
V
O ST
STOP
Y SIT33.5 EFLR.EL.=N I'-V 6" IO UN 44 UN .= HT
II RY 9 RA60 '-T09"H U2 .8 LIBHT.=O S. EL.= FL
FL
L AL
OR20' ADT.= 1.0 0 AMLDG.ALH.=L4L3 B H.E
B SE BA
2D
TU RN STOP
I
C L
F
RY RA T89H'-0 " R.= 9 LIB . O HT 29.8 G L.= IDN BL L. E
2D
1D
EL2-8
LEFT EL2-7
BIK E
EN . 08 - 3 1 - 1 O F OF CAL I
R T
BUS
STO P
ONL Y STOP STOP
R C LE AEE P K R C LE AEE P K R C LE AEE P K
J
ST RE ET CLEA R KEEP
BIEK LANE
BIEK
ON LY
STOP
LANE
LANE BIEK
YIE LD
BUS
STO P
LANE BIEK
BIKE LANE
STOP
STOP
STOP STOP
STOP STOP
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
YIELD ONLY
D OA ILR RA
EL2-10
y 50 ighwa U.S. H oule vard
K I BE
A LNE
Fols om B
BIKE
G I N 6'-E 0" RK U4R P A U.CHTT.= 39.00 R G L.= STBLDFL. E I
K GM
STOP
C23603 3 GA101 C IFI AC
STOP
R
AIL TR
AT
e Driv
1C
EL2-8,10,12
CLIENT Red Buckeye Way
ST OP
E IK
Z-M . 12'-0" HA LDG B . HT.=38 .03 DG L.= BL FL.E
h Smit Jed
F
T OS TP L. "F OU L15'-5 A. HLT.=3E7.3R5 T SM DG L.= BL EEA TH
T UR
EL1-2
LANE
O AN 5 " TR 67'- 8 PIS . HLT.=.=L39.9 L CA BLDHGLA .E
1C T UR
S CO NNI #14
EL1-4
ONL Y
N
B
EL ES DI G IN MP T PU LAN P
& 9'-6" T.= 8 EH . HS 37.3 DG .= BL L.EL F
F
" E '-0 20 SI1D EHRT.=L38L.1 0 .= RBLIDVGL.H .ELA
1C
T UR
1C
A NT LL S A A HA AR CL
T UR
S CO NNI #7
" '-2 15 T.= .4 7 . H 36 DG L.= BL L.E F
S CO NNI #5
TE
T UR
TE
S CO NNI #13
P RN HE UT SO
ST OP
PROJECT (E) PARKING RAMP STOP STOP
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819 ONL Y
STOP
A
A OI QU SE ALL H
" '-6 85 3 T.= .0 . H 37 DG L.= BL L. E F
DT OL MB LL HU HA
" '-0 24 0 T.= .6 . H 37 DG L.= BL L . E F
TE
TE
1C
3C
T UR
3C
S CO NNI #12
TE
1C 3B
ERA TOR GEN
C
SE OU NH EE GR
ER AC PL ALL H
" '-0 86 T.= .5 0 . H 37 DG L.= BL FL.E
T UR
S CO NNI #3
T UR
L MA ER GY K TH NER TAN B T UR E GE S CO NNI #6 RA B
TE
S CO NNI #4
O ST
KA RE EU ALL H
BB T UR
TE
" '-6 51 6 T.= .6 . H 32 DG L.= BL L. E F
N 8" O 2'.= 2 .50 HTT E IGG. H .= 36L BBRLDFL.HELAL ZON GER NA MA
S NNI #2
L5'-0" RA .= 2 0 N.THT.= T37.0 CEDGLEALN BL P . FL
TE
G IN OL R CO OWEURT T CO
E '8" IN.=22 2 LDGP. HT.=L3L6.9 A L BL H .EA FL
B
1C
T UR
TE
S CO NNI #11
3B
3B
EL1-6
R T UR
TE
S CO NNI #10
2B
TE
S CO NNI #9
T UR
TE
S CO NNI #8
3B
1B
2C
TE
3B
2B
EL2-7,9
ONL Y
White Poplar Way
C LEAR KE EP
SEAL TR AIL
E ve m Dri Stadiu
y r Wa Ceda Atlas
ay ar W Ced Atlas
7667 FOLSOM BLVD, SACRAMENTO, CA 95826 EL1-6 EL1-1
rive ity D " '-0 72 T.= .40 . H 38 DG EL.=
D L BL L. E F
S RA VE1L3'-0" LA A T.=L .00 CA GH . H .= 38
3 . DG L.= BL FL. E
A OS RIP L '-0" MA HALHT.=875.3 0
0" NO 95'LA .= .50 SO G.AHLT.=L 37 DH L BL L. E F
1C
K GM
1B
LL BA FT SO
3A
E LEL. 81 TU N N9 F=1 . . 40 C=29
Coulter Pine Wa y EL1-1
E LEL. . 84 TU N N F=1 8 . 39 C=28
L T UNNE ND RGROU UNDE
E LEL. TU N N8. 42 F=1 . 02 C=28 E LEL. 51 TU N N8 F=1 . .23 C=31
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS EL2-12
O IN OC ND LL L. ME HA F BL
FL
MA DE KA HALL " '-0 30 T.= .50 . H 38 DG L.= BL L. E F
ay aW
SS LA29'-9" T.= 8.50 UG . H .=L3L AL DBOLDGH .E
D UN RO USE HO
N SSE LA ALL H
" '-0 54 2 T.= .4 . H 38 DG L.= BL L. E F
rag Mo
S CO NI #1
3A
1A
STOP
I
L TRAI
ers Univ T LO 3
TE OR L N LL DE HA " '-6 48 1 T.= 7.7 .H 3 DG L.= BL FL. E
ER RIVONT R FR NTE CE
" '-0 27 T.= .44 . H 38 DG L.= BL L. E F
D L BL L. E F
TO EN AM 0" CR LL 36'SA HGA. HT.=.=39.46
T LO A
6"
N '21L TE A3L6.20 T.= HB G.DL.= TS DN BLA L. EUR H FC O 1C
L AL
1A
ER CC SO
ive Dr wn To
3A
H '-0 " NO .=E3X6.40 T 6 LA N SO DGA.NHL.= 3 BL L. E F
TE MI SE L " YO HAL G40Y'-00M T.= 37.5 . HH GT L.= DU SBOL FL. E
S PE RO URSE CO
e eg
E LEL. TU N N . 24 F=1 98. 78 C=2
T LO 2 H UT SO
State
TA AS SH ALL H
" '-0 62 T.= .50 . H 34 DG L.= BL L. E F
STOP
ST OP
R
BIKE
STOP
E
St re et
M
STO P
T2 LO RTH NO
J
A
T .2 . H 37 DG EL.= BL
D ON SM L L. DE HAL 38'-0" F 5 .=
ST OP
AR CLE P KEE
T LO B NG MI IM L SW POO OL PO DG. BL
STOP
TRAIL
NS KI JEN ALL H
0" '-1 28 5 T.= 7.7 .H 3 DG L.= BL FL. E
T2 L O ST WE
ST OP
T LO 1
TE MI SE L 0" YO HAL G4Y0'-M H .= .49 RDGT. HLT.= 37 BL FL. E NO
ll Co
E LEL. TU N N0. 12 F=2 9. 77 C=2 E LEL. . 16 TU N N F=2 0 . 73 C=29
E LEL. TU N N . 54 F=1 81 .31 C=3
STO P
RIGHT
AGENCY
FILE NO: 34-CSUS
DATE
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
BIKE
0'
e
Residence Way
e
d na
d na
pla
pla
Es
e riv
Es
N ICA ER R 6'-0" D R AM RIVET.=Y4A .5 0 . HT 39 DGR L.= BL U. E COFL
yD sit er
IC ET 27'-9" HL TE.=R .42 AT LEDGN. HTL.= 38 CB FL. E
& S ITIE CIL EX
E LEL. TU N N . 45 . 02 F=1 9 C=29
RIGHT
d ir Roa Sincla
T ES Y W GE GU RID B
D A RCH SE I E N A N McM TE H U T A E LEL. TU N N9. 29 F=1 . 82 C=28
TU RN
.C. A.R .P. C
iv Un
T LO 1
ES ITI ENT STOP CIL M F A AGE N MA
G IN ILD.45 ES BUEL.=R3A5 D . T FL
" '-0 21 T.= .96 . H 34 DG L.= BL L. E F
ICS PH RA OM OG RO P R IL RE M A
retu
KEEP
E LEL. 14 TU N N9 F=1 . . 64 C=28
ONLY
LANE
STO P TU RN
'-1 ER28 3 A. HPT.=.=L37.7 R DG ELL D BL FL. A H
YIELD
ST OP
ONL Y
Way Pine son Morri CLEA R CLEA R KEEP
BIKE
L IA OD SE ST OU CU REH WA
S ND OU ING GR ILD BU
Arbo
FA NN A NG IVI SE CE OU RE REH ay WA mW
ONLY
F
" '-4
ER.=36 0 TDGT. HLTL.=36.2 SU . EL BL FLA H
BEKI
e at St ALNE
BIEK
STOP
STOP
ad Ro lair c Sin
NG NI N'-S8" DI MHTO.=194.6 5 M. 3 DG L.= CO BL L. E
A RR SIE ALL H
ive Dr
" '-4 36 T.= .5 0 . H 36 DG L.= BL L. E F
on rls Ca
LANE
BUS
STOP
E AG OR . ST LDG B
STOP STOP
STOP
E AG OR . ST LDG B ET E RN US HO EHO R WA
y Wa rel Lau
STOP
. OL GE DG. BL E AG OR . ST LDG B
STOP
DURING CONSTRUCTION, IF POT ITEMS WITHIN THE SCOPE OF THE PROJECT REPRESENTED AS CODE COMPLIANT ARE FOUND TO BE NONCONFORMING BEYOND REASONABLE CONSTRUCTION TOLERANCES, THEY SHALL BE BROUGHT INTO COMPLIANCE WITH THE CBC AS A PART OF THIS PROJECT BY MEANS OF A CONSTRUCTION CHANGE DOCUMENT. SE OU NH EE GR
ONL Y
GA101 SCALE 1" = 40'-0"
EXIT
ve Dri ity ers niv te U Sta
ay rW opla P ite Wh
C
T LO 1 1
STO P
LANE
SHEET
2
CAMPUS SITE PLAN
1 B
BUILDING SITE PLAN
4/25/2019 8:48:57 AM
E FIR ION AT ST
YIE LD
BIKE
BUS
D
y Ba
STOP
y Wa tum ore Arb
STOP
(E) FIRE HYDRANT
FH DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE STATEMENT: THE POT IDENTIFIED IN THESE CONSTRUCTION DOCUMENTS IS COMPLIANT WITH THE CURRENT APPLICABLE CALIFORNIA BUILDING CODE ACCESSIBILITY PROVISIONS FOR PATH OF TRAVEL REQUIREMENTS FOR ALTERATIONS, ADDITIONS AND STRUCTURAL REPAIRS. AS PART OF THE DESIGN OF THIS PROJECT, THE POT WAS EXAMINED AND ANY ELEMENTS, COMPONENTS OR PORTIONS OF THE POT THAT WERE DETERMINED TO BE NONCOMPLIANT 1) HAVE BEEN IDENTIFIED AND 2) THE CORRECTIVE WORK NECESSARY TO BRING THEM INTO COMPLIANCE HAS BEEN INCLUDED WITHIN THE SCOPE OF THIS PROJECT’S WORK THROUGH DETAILS, DRAWINGS AND SPECIFICATIONS INCORPORATED INTO THESE CONSTRUCTION DOCUMENTS. ANY NONCOMPLIANT ELEMENTS, COMPONENTS OR PORTIONS OF THE POT THAT WILL NOT BE CORRECTED BY THIS PROJECT BASED ON VALUATION THRESHOLD LIMITATIONS OR A FINDING OF UNREASONABLE HARDSHIP ARE SO INDICATED IN THESE CONSTRUCTION DOCUMENTS. YIELD
EXISTING BUILDINGS ACCESSIBLE ROUTE Hickok Lane
1"
E BIK LANE
SITE PLAN LEGEND GENERAL NOTES
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
ACCESSIBLE PATH OF TRAVEL Street H
sig n sig n
5 4 3 2 2"
1
ISSUED
STOP
STOP
2"
1
2
BLDG 1 CODE ANALYSIS
3
4
5
BLDG 2 CODE ANALYSIS
LIFE SAFETY LEGEND
GOVERNING CODE:
2016 CALIFORNIA BUILDING CODE
1.
GOVERNING CODE:
2016 CALIFORNIA BUILDING CODE
2.
OCCUPANCY CLASSIFICATION AND USE: (CBC 302)
MIXED-USE PER CBC 508.3 B OCCUPANCY - OFFICES & CLASSROOMS A3 OCCUPANCY - CLASSROOMS
2.
OCCUPANCY CLASSIFICATION AND USE: (CBC 302)
MIXED-USE PER CBC 508.3 B OCCUPANCY - OFFICES & CLASSROOMS A3 OCCUPANCY - CLASSROOMS
3.
BUILDING CONSTRUCTION TYPE: (CBC 601 & 602)
IIIB - BUILDING IS FULLY SPRINKLERED
3.
BUILDING CONSTRUCTION TYPE: (CBC 601 & 602)
IIIB - BUILDING IS FULLY SPRINKLERED
4.
ACTUAL NUMBER OF STORIES:
3 STORIES
4.
ACTUAL NUMBER OF STORIES:
3 STORIES
5.
ACTUAL BUILDING HEIGHT:
45'-0"
5.
ACTUAL BUILDING HEIGHT:
45'-0"
USE NAME XXX SF / XX XX
OCCUPANT LOAD FACTOR OCCUPANT LOAD SQUARE FOOTAGE
6.
ACTUAL BUILDING AREA:
OCCUPANY GROUP
ACTUAL BLDG AREA
NO. BLDG HT OF STORIES
GROUP A-3 GROUP B
21,735 SF 15,304 SF
--
GROUP A-3 GROUP B
1,286 SF 36,432 SF
GROUP B TOTAL
6.
ACTUAL BUILDING AREA:
27
OCCUPANY GROUP
ACTUAL BLDG AREA
NO. OF STORIES
BLDG HT
--
GROUP A-3 GROUP B
6,016 SF 21,310 SF
"
"
--
--
GROUP B
25,952 SF
"
"
36,432 SF
--
--
GROUP B
25,952 SF
"
"
109,903 SF
3
45'
TOTAL
79,230 SF
3
45'
0
EXIT LOCATION & NUMBER OF OCCUPANTS USING EXIT
OCCUPANT LOAD
FIRE EXTINGUISHER (E) FEC (E) CABINET
CEILING MOUNTED "EXIT" SIGNS W/ DIRECTIONAL ARROWS WHERE SHOWN
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
1 HR RATED
(E) 1 HR RATED
NON-RATED PARTITION
EGRESS PATH
D
7.
AREA OF PROJECT:
2,430 SF OF INTERIOR TENANT IMPROVEMENT ON LEVEL 2 (SEE SHEET GL112)
7.
AREA OF PROJECT:
--,--- SF
8.
SEPARATED OR NONSEPARATED USE:
SEPARATED
8.
SEPARATED OR NONSEPARATED USE:
SEPARATED
9.
ALLOWABLE AREA PER (CBC 504.3, 504.4 & 506.2)
OCCUPANY GROUP
ALLOWABLE BLDG AREA
MAX NO. OF STORIES
ALLOWABLE BLDG HT
9.
ALLOWABLE AREA PER (CBC 504.3, 504.4 & 506.2)
OCCUPANY GROUP
ALLOWABLE BLDG AREA
MAX NO. OF STORIES
ALLOWABLE BLDG HT
GROUP B
57,000 SF
5
75'-0"
GROUP B
57,000 SF
5
75'-0"
GROUP A3
28,500 SF
3
55'-0"
GROUP A3
28,500 SF
3
55'-0"
PER CBC 508.4 SEPARATED OCCUPANCIES
10. AREA INCREASE (AREA MODIFICATION PER CBC CHAP 5):
506.3.3 FRONTAGE INCREASE I f = [F/P - 0.25] W/30
I f = 0.59
I f = 0.46
A a= [28500 + (9500 x 0.46)]
A a= 34,105 SF
A a= 32,870 SF
A a= [57000 + (19000 x 0.46)]
A a= 68,210 SF
A a= 65,740 SF
ENTIRE BLDG - ALLOWABLE AREA
21,735 SF 1ST FLR
2ND FLR
34,105 SF 1,286 SF 34,105 SF
3RD FLR
+
R E
EN . 08 - 3 1 - 1 O F OF CAL I
ENTIRE BLDG - ALLOWABLE AREA B ACTUAL B ALLOWABLE
A3 ACTUAL
=
X
=
0.86 < 1
A3 ALLOWABLE
15,304 SF +
T
A
A a= [57000 + (19000 x 0.59)]
A3 ALLOWABLE
C23603
506.2.4 MIXED-OCCUPANCY, MULTISTORY BLDG - B OCC A a= [A t + (NS x I f )]
ST
506.2.4 MIXED-OCCUPANCY, MULTISTORY BLDG - B OCC A a= [A t + (NS x I f )]
D A RCH SE I E N A N McM TE H U T A
CT Y R RT
A a= [28500 + (9500 x 0.59)]
+
SEAL
506.2.4 MIXED-OCCUPANCY, MULTISTORY BLDG - A3 OCC A a= [A t + (NS x I f )]
IA
506.2.4 MIXED-OCCUPANCY, MULTISTORY BLDG - A3 OCC A a= [A t + (NS x I f )]
N
I f = [71+210+18+174+26/701 - 0.25] 30/30
A3 ACTUAL
EXISTING OCCUPANCY - A3
PER CBC 508.4 SEPARATED OCCUPANCIES
I f = [(30+78+52+78+43+24+85+24+20+79+26+77+51)/795 - 0.25] 30/30
C
LIMITS OF ARCHITECTURAL WORK
9
506.3.3 FRONTAGE INCREASE I f = [F/P - 0.25] W/30
EXISTING OCCUPANCY - B
R
10. AREA INCREASE (AREA MODIFICATION PER CBC CHAP 5):
EXISTING - NOT IN SCOPE
LI JO C N
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
1.
68,210 SF 36,432 SF 68,210 SF 36,432 SF 68,210 SF
+
6,016 SF
=
=
1ST FLR
0.57< 1
2ND FLR
0.53 < 1
3RD FLR
TOTAL = 1.96 < 2
32,870 SF
B ACTUAL B ALLOWABLE
PROJECT =
X
=
0.51 < 1
55 OCCS.
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
109 OCCS.
7667 FOLSOM BLVD, SACRAMENTO, CA 95826
21,310 SF +
65,740 SF 25,952 SF
=
65,740 SF 25,952 SF
=
65,740 SF
37 OCCS.
0.4 < 1
0.4 < 1
333 OCCS.
73 OCCS.
CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
TOTAL = 1.31 < 2
11. HEIGHT INCREASE:
NO
11. HEIGHT INCREASE:
NO
12. FIRE SPRINKLERS TYPE:
YES: WET // SEE SFM 18-34-03-0001
12. FIRE SPRINKLERS TYPE:
YES: WET
13. FIRE ALARM TYPE:
YES: AUTOMATIC W/ F-1 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS
13. FIRE ALARM TYPE:
YES: AUTOMATIC W/ F-1 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS
14. OTHER FIRE PROTECTION SYSTEM
FIRE EXTINGUISHER, FIRE HOSE CABINETS
14. OTHER FIRE PROTECTION SYSTEM
FIRE EXTINGUISHER, FIRE HOSE CABINETS
15. SMOKE CONTROL SYSTEM
NO
15. SMOKE CONTROL SYSTEM
NO
36 OCCS. 139 OCCS. 1 OCC.
18 OCCS.
18 OCCS.
54 OCCS.
SEATING AREA
50 OCCS. ISSUED
559 SQ. FT.
MARK
DATE
DESCRIPTION
30 OCCS.
101 OCCS.
1 OCC.
37 OCCS.
452 SQ. FT.
SEATING AREA 16. OCCUPANT LOAD FOR ENTIRE BLDG & FLOORS (EXISTING)
1ST FLOOR =
1,176 OCCUPANTS
2ND FLOOR =
694 OCCUPANTS
3RD FLOOR =
324 OCCUPANTS
16. OCCUPANT LOAD FOR ENTIRE BLDG & FLOORS (EXISTING)
TOTAL BLDG OCCUPANCY = 2,194 OCCUPANTS
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
B
1ST FLOOR =
280 OCCUPANTS
2ND FLOOR =
263 OCCUPANTS
3RD FLOOR =
239 OCCUPANTS
1980
17. YEAR BUILDING WAS CONSTRUCTED
1980
18. IS BLDG LOCATED IN HIGH FIRE HAZARD SEVERITY ZONE:
NO
18. IS BLDG LOCATED IN HIGH FIRE HAZARD SEVERITY ZONE:
NO
19. SEISMIC JOINTS, IF YES, PROVIDE LOCATION:
NO
19. SEISMIC JOINTS, IF YES, PROVIDE LOCATION:
NO
21. RISK CATEGORIES OF BUILDINGS (CBCTABLE 1604.5)
III
1 OCC.
53 OCCS.
NONE
21. RISK CATEGORIES OF BUILDING (CBCTABLE 1604.5)
III
(E) 2 HOUR BUILDING SEPARATION FIRE WALL
50 OCCS.
125 OCCS.
11 OCCS.
1 OCC.
20. EMERGENCY RESPONDER RADIO COVERAGE:
63 OCCS.
53 OCCS.
1 OCC.
1 OCC. 1 OCC.
1 OCC. 1 OCC. 1 OCC.
106 OCCS.
1 OCC.
10 OCCS. 38 OCCS. 3 OCCS.
21 OCCS.
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
50 OCCS.
76 OCCS.
SEATING AREA
35 OCCS.
1 OCC.
74 SQ. FT.
UP
59 OCCS. 38 OCCS.
1 HR RATED WALL
221 OCCS.
(E) FIRE ALARM CONTROL PANEL
SEATING AREA
AGENCY
SEATING AREA
TOTAL 50% 78 OCCS. OL AT 1ST FLOOR: 108
CORRIDOR
016279.06 ?00.00.00? LIONAKIS 2015
5 OCCS.
520 SQ. FT.
B-OCCUPANCY AREA Total: 559 OCCS.
MANAGEMENT
62 OCCS.
25 OCCS. 25 OCCS.
216 OCCS.
11 OCCS. 160 SQ. FT.
25 OCCS. UP
62 OCCS.
PER CSFM FILE # 02-112652 1 HOUR RATED FIRE SEPARATION BETWEEN OCCUPANCIES
110 OCCS.
10 OCCS. 50 OCCS. 125 OCCS.
27 OCCS.
12 OCCS.
13 OCCS.
935 SF
FILE NO: 34-CSUS
50 OCCS.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
21 OCCS.
296 OCCS.
308 SQ. FT.
55 OCCS.
AC
25 OCCS.
11 OCCS.
28 OCCS.
25 OCCS.
FLS
SS
DATE
63 OCCS.
A
TITLE
LIFE SAFETY FLOOR PLAN LEVEL 1
155 OCCS. 20 OCCS. 297 SQ. FT.
SEATING AREA
33 OCCS.
1
LIFE SAFETY FLOOR PLAN - LEVEL 1 SCALE 1/16" = 1'-0"
SEATING AREA
489 SQ. FT.
UP
4/25/2019 2:34:18 PM
25 OCCS.
51 OCCS. 1 OCC.
1 OCC.
NONE
1 OCC.
TOTAL BLDG OCCUPANCY = 782 OCCUPANTS
17. YEAR BUILDING WAS CONSTRUCTED
20. EMERGENCY RESPONDER RADIO COVERAGE:
25 OCCS.
1 HR RATED WALL
A-3 OCCUPANCY AREA Total: 617 OCCS.
DOOR OPENING WIDTH CAPACITY: 72"/0.2 = 360 NOTE: MAX LOBBY EXIT WIDTH - 50% ACCOMODATION - 50% OF OCC. LOAD FOR EXIT DISCHARGE FOR BOTH 1ST AND 2ND FLOOR
PLAN NORTH SHEET
GL111
2"
1
2
3
4
5
1"
LIFE SAFETY LEGEND NAME XXX SF / XX XX
CEILING MOUNTED "EXIT" SIGNS W/ DIRECTIONAL ARROWS WHERE SHOWN
OCCUPANT LOAD SQUARE FOOTAGE
1 GL112.2
STAIR NO. 4 STAIR WIDTH/CAPACITY: 50" / 166 OCCS DOOR OPG WIDTH/CAPACITY: 46" / 230 OCCS
27 STAIR NO. 5 STAIR WIDTH/CAPACITY: 50" / 166 OCCS DOOR OPG WIDTH/CAPACITY: 34" / 170 OCCS
0
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
OCCUPANT LOAD FACTOR
EXIT LOCATION & NUMBER OF OCCUPANTS USING EXIT
OCCUPANT LOAD
1 HR RATED
(E) 1 HR RATED
FIRE EXTINGUISHER (E) FEC (E) CABINET
NON-RATED PARTITION
EGRESS PATH
D
OFFICE = 6 occs.
155 Occs.
43 Occs.
LIMITS OF ARCHITECTURAL WORK
EXISTING OCCUPANCY - A3
138 Occs.
(E) NON-OCCUPIED ROOF TERRACE
BREAK ROOM = 86 OCCS
43 Occs.
(E) 2 HOUR BUILDING SEPARATION FIRE WALL
SEAL D A RCH SE I E N A N McM TE H U T A
CT Y R RT
LI JO C N
48 Occs.
C23603
(E) NON-OCCUPIED ROOF TERRACE
T
A
(E) NON-OCCUPIED ROOF TERRACE
ST
(E) NON-OCCUPIED ROOF TERRACE
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
Occupant Load = 138 Occs. (13,785 sf/100)
96 Occs. 2 Occs. DN DN
STAIR NO. 3 STAIR WIDTH/CAPACITY: 45" / 150 OCCS DOOR OPG WIDTH/CAPACITY: 46" / 230 OCCS
REQUIRED MIN. DOOR WIDTH: (96 x .15 = 14.4") < PROPOSED 36" DOOR WIDTH
7667 FOLSOM BLVD, SACRAMENTO, CA 95826
STAIR NO. 6 STAIR WIDTH/CAPACITY: 50" / 166 OCCS DOOR OPG WIDTH/CAPACITY: 46" / 230 OCCS
CORRIDOR = 7.3 Occs. (726 sf/100)
CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
156 Occs. 125 Occs. UP DN
150 Occs.
82 Occs.
124 Occs.
265 Occs. 183 Occs.
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
NURSING DEPARTMENT
C
R E
IA
41 Occs.
N
(E) NON-OCCUPIED ROOF TERRACE
EXISTING OCCUPANCY - B
9
(E) NON-OCCUPIED ROOF TERRACE
EXISTING - NOT IN SCOPE
R
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
USE
83 Occs.
233 Occs.
28 Occs.
ISSUED
MECH EQUIP AREA
14 Occs.
MARK
DATE
DESCRIPTION
40 Occs.
STAIR NO. 1 STAIR WIDTH/CAPACITY: 72" / 240 OCCS DOOR OPG WIDTH/CAPACITY: N/A, OPEN STAIR
ACADEMIC TALENT SEARCH
DEPARTMENT OF PUBLIC HEALTH Occupant Load = 76 Occs. (7,565 sf/100)
Occupant Load = 28 Occs. (2,799 sf/100)
B STAIR NO. 2 STAIR WIDTH/CAPACITY: 47" / 156 OCCS DOOR OPG WIDTH/CAPACITY: 34" / 170 OCCS
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
NORTH CENTRAL INFO CENTER Occupant Load = 14 Occs. (1,355 sf/100)
EXIT ANALYSIS - OCCUPANT LOAD & EXIT WIDTH Total Occupant Load 2nd Floor: 922 AVAILABLE STAIR CAPACITY Total Existing Stair Width = 319” Total Existing Stair Capacity: 1,044 Total Occupant Load 2nd Floor: 927 (OK under capacity) DIFFERENCE OCC LOAD FOR STAIRS: 64 UNUSABLE CAPACITY, STAIR 5: 32 TOTAL CAPACITY UNDER, FLOOR: 64 occupants AVAILABLE DOOR CAPACITY Total Required Door Width - Enclosed Stairs 2-6 Occ Load at Doors: 922 total - 240 Stair 1 = 682 occupants Door Capacity: 206" / .2" = 1,030 Occupants TOTAL DOOR WIDTH - OK DOOR WIDTH AT EACH STAIR - OK
FOR COMPLIANCE 1. TOTAL OCCUPANT LOAD COUNT IS UNDER 1060. 2. REDISTRIBUTE OCCUPANT LOAD FOR MAXIMUM EXITING OCCUPANT LOAD AT EACH STAIR.
A
1
LIFE SAFETY FLOOR PLAN - LEVEL 2
TOTAL A-OCCUPANCY AT FOLSOM HALL
AGENCY
KEY PLAN
GROUND FLOOR 125 OCC 75 OCC 125 OCC 50 OCC 50 OCC 192 OCC at Seating Areas TOTAL: 617 A-OCCUPANTS
FILE NO: 34-CSUS
SECOND FLOOR 86 OCC TOTAL: 86 A-OCCUPANTS
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
NOTE: THERE ARE NO A-OCCUPANCY AT THE THIRD FLOOR
AC
A
TOTAL A-OCCUPANCY FOR ENTIRE BUILDING = 703 OCCUPANTS < 1000 OCCUPANTS - OK PER IR F-1 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS
FLS
SS
DATE
TITLE
B
SCALE 1/16" = 1'-0" PLAN NORTH
4/25/2019 8:49:15 AM
016279.06 ?00.00.00? LIONAKIS 2015
LIFE SAFETY FLOOR PLAN LEVEL 2 SHEET
GL112
2"
1
2
3
4
5
LIFE SAFETY LEGEND 1"
36 USE NAME
NW ROOF TERRACE 4
NW ROOF TERRACE 5
NON-OCCUPIED ROOF TERRACE. NOT INCLUDED IN OCCUPANCY CALCULATIONS. MAINTENANCE ONLY ACCESS. THESE DOORS TO BE LOCKED. FOR MAINTENANCE PERSONNEL ACCESS ONLY
XXX SF / XX XX
NW ROOF TERRACE 6
NON-OCCUPIED ROOF TERRACE. NOT INCLUDED IN OCCUPANCY CALCULATIONS
CEILING MOUNTED "EXIT" SIGNS W/ DIRECTIONAL ARROWS WHERE SHOWN
OCCUPANT LOAD SQUARE FOOTAGE
NON-OCCUPIED ROOF TERRACE. NOT INCLUDED IN OCCUPANCY CALCULATIONS
27 BREAKROOM
THESE 2 DOORS TO BE LOCKED. FOR MAINTENANCE ONLY ACCESS.
0
1,286 SF/ 15 86
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
OCCUPANT LOAD FACTOR
EXIT LOCATION & NUMBER OF OCCUPANTS USING EXIT
OCCUPANT LOAD
1 HR RATED
(E) 1 HR RATED
98 Occs. FIRE EXTINGUISHER (E) FEC (E) CABINET
NON-RATED PARTITION
EGRESS PATH
D
ASC
FT OFFICE
FT OFFICE
CONF/BREAK
263 SF/ 100 3
173 SF/ 100 2
182 SF/ 100 2
316 SF/ 15 21
3
2
2
(E) PH
2
FT OFFICE
EXIT SEPARATION FOR CLINIC ADMIN. DEPARTMENT ACCEPTABLE PER 2016 CBC 1007.1.1, 1-2 (GREATER THAN (1/3 x 187.5' = 63'))
91 SF/ 100 1
67 SF/ 100 1
PT OFFICE
PT OFFICE
PT OFFICE
124 SF/ 100 2
153 SF/ 100 2
165 SF/ 100 2
2
2
193 SF/ 100 2
CHAIR OFFICE
C
SEAL
CORRIDOR
PT OFFICE
2 OCCUPANTS PER TABLE
FIXED COMPUTER TABLES TO WALL
". -6 ' 7 18
REMOTE LOCATION TO STAIR NO.4 = 145'-0" MAX TRAVEL DISTANCE FOR B OCCUPANCY CBC 1017.1= 300'-0"
113 SF/ 7 16
T
212 SF/ 50 4
EXIT
CORRIDOR LENGTH ACCEPTABLE PER 2016 CBC 1020.4, 2 (LESS THAN 50')
3
2
CORRIDOR
2
2
206 SF/ 20 11
PROJECT
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
EXIT ROUTE SIGN
AUDIO LAB CONSULT 214 SF/ 50 5
AUDIOLOGY LAB 185 SF/ 20 10
UP
2 14
CORRIDOR
39
35 CLINIC COORD.
SUPPLY
THERAPY PREP CLINC SCHEDULER
183 SF/ 100 2
2
2
CLIENT
TELECOM
OBSERVATION 365 SF/ 50 8
GENDER NEUTRAL RESTROOM
ELEC/TELE
JAN.
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
CORRIDOR 2
DN
137 SF/ 50 3
WOMEN'S RESTROOM
MEN'S RESTROOM
EXIT SEPARATION ACCEPTABLE PER 2016 CBC 1007.1.1, 1-2 (GREATER THAN (1/3 x 205' = 69'))
229 SF/ 100 2
AUXILLARY OBSERVATION
7667 FOLSOM BLVD, SACRAMENTO, CA 95826
96
96 Occs. EXIT ROUTE SIGN *(E) FEC
FILE & CONF
CORRIDOR
609 SF/ 300 2
274 SF/ 100 3
NON-OCCUPIED MECHANICAL TERRACE. NOT INCLUDED IN OCCUPANCY CALCULATIONS.
10
23
*(E) FEC
20
11
8'8" .
215 SF/ 100 2
EN . 08 - 3 1 - 1 O F OF CAL I
AUDIOLOGY LAB
180 SF/ 20 9
NET AREA = 784 SF FLOOR AREA = 1074 SF TOTAL OCCUPANTS = 39
R E
AUDIOLOGY LAB
784 SF/ 20 39
276 SF/ 100 3
C23603
CLOS.
AUDIO LAB TEST BOOTH
CLINICIAN COMPUTER CLASSROOM
WAITING AREA
D A RCH SE I E N A N McM TE H U T A
195 SF/ 100 2
CT Y R RT
208 SF/ 100 2
2
A
212 SF/ 100 2
41
ST
FT OFFICE
2
CORRIDOR
10
FT OFFICE
CLASSROOM 739 SF/ 20 41
THESE DOORS TO BE LOCKED. MAINTENANCE ONLY ACCESS.
GRAD COORD.
CORRIDOR SERV CLOS.
44
44 Occs. EXIT ROUTE SIGNAGE
IA
*(E) FEC
100 SF/ 7 12
N
159 SF/ 100 2
NON-OCCUPIED ROOF TERRACE. NOT INCLUDED IN OCCUPANCY CALCULATIONS
MAINTENANCE ONLY ACCESS. DOOR TO BE LOCKED
192 SF/ 100 2
2
NW ROOF TERRACE 3
NON-OCCUPIED ROOF TERRACE. NOT INCLUDED IN OCCUPANCY CALCULATIONS
EXISTING OCCUPANCY - A3
9
NON-OCCUPIED ROOF TERRACE. NOT INCLUDED IN OCCUPANCY CALCULATIONS.
LIMITS OF ARCHITECTURAL WORK
R
NW ROOF TERRACE 2
COPY/MAIL
SERV DESK WAITING
FT OFFICE
NW ROOF TERRACE 1
OPEN OFFICE
LI JO C N
NOTE: FOR EXISTING AREAS NOT IN SCOPE, SEE CSFM #18-34-03-001
EXISTING OCCUPANCY - B
21 11
166 SF/ 100 2
EXISTING - NOT IN SCOPE
35
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
(E) PH
STAIR NO. 2 DN
STORAGE
STORAGE
165 SF/ 100 2
166 SF/ 100 2 ISSUED
156 Occs.
MARK
OBVS. CLOS.
DATE
DESCRIPTION
*(E) FEC 150 Occs.
NW ROOF EQUIP
UP
3
2
37
CORRIDOR
37
82
CORRIDOR
DN
STAIR NO. 3
THERAPY
THERAPY
THERAPY
THERAPY
118 SF/ 100 2
117 SF/ 100 2
116 SF/ 100 2
151 SF/ 100 2
8 Occ.
2
2
2
2
2
2
376 SF/ 7 37
2
*(E) FEC
CORRIDOR 40
143 Occs.
EXIT ROUTE SIGN
CORRIDOR
2
124 Occs.
233 Occs.
With tables & chairs 115 SF / 15 = 8 Occs
WAITING
258 SF/ 100 3
2
265 Occs.
STAIR EXIT SIGN
ELEV NO.1
RECEPTION
3 B
143
EXIT ROUTE SIGN
*(E) FEC 143 Occs.
STAIR EXIT SIGN
2
7 Occ.
2
2
2
2
2
CORRIDOR LENGTH ACCEPTABLE PER 2016 CBC 1020.4, 2 (LESS THAN 50')
STAIR NO.1 LOBBY
17 Occs
2
ELEV NO.2
978 SF/
*(E) FEC MANAGEMENT
CORRIDOR THERAPY
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
121 SF/ 100 2
THERAPY 114 SF/ 100 2
THERAPY
THERAPY
THERAPY
THERAPY
THERAPY
THERAPY
THERAPY
THERAPY
THERAPY
114 SF/ 100 2
121 SF/ 100 2
121 SF/ 100 2
114 SF/ 100 2
113 SF/ 100 2
121 SF/ 100 2
114 SF/ 100 2
113 SF/ 100 2
121 SF/ 100 2
COMPUTER LAB
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
784 SF/ 20 40
CORRIDOR SW ROOF EQUIP NON-OCCUPIED MECHANICAL TERRACE. NOT INCLUDED IN OCCUPANCY CALCULATIONS.
19
AGENCY FLOOR AREA = 1045 SF
GROUP THERAPY
GROUP THERAPY
GROUP THERAPY
GROUP THERAPY
LG THERAPY
LG THERAPY
LG THERAPY
LG THERAPY
LG THERAPY
280 SF/ 15 19
278 SF/ 15 19
278 SF/ 15 19
278 SF/ 15 19
187 SF/ 15 13
187 SF/ 15 13
180 SF/ 15 12
180 SF/ 15 12
188 SF/ 15 13
19 *(E) FEC
34
19 42
44
CORRIDOR
19
NET AREA (NET W/ FIXED COMP TABLES) = 784 SF
2 OCCUPANTS PER FIXED TABLES
KEY PLAN
TOTAL OCCUPANTS WITH PROPOSED FIXED COMPUTER TABLES = 37
13
13
13
13
13
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
CLASSROOM VOICE / ENDOSCOPY 509 SF/ 15 34
CLASSROOM NEUROSERV ALLIANCE 652 SF/ 15 44
CLASSROOM LANGUAGE LITERACY 620 SF/ 15 42
AC
A NOTE: FOR EXISTING AREAS NOT IN SCOPE, SEE CSFM #18-34-03-001
FLS
SS
DATE
A
TITLE
B
PLAN NORTH
4/25/2019 8:49:47 AM
016279.06 ?00.00.00? LIONAKIS 2015
PLAN NORTH
PARTIAL LIFE SAFETY FLOOR PLAN - LEVEL 2 SHEET
1
PARTIAL LIFE SAFETY FLOOR PLAN - LEVEL 2 SCALE 1/8" = 1'-0"
GL112.2
2
3
4
5
F
4. 5. 6. 7.
4
1'-0"
18" MIN CLR @ INTERIOR DOOR
24" MIN CLR @ EXTERIOR DOOR
PUSH SIDE
CLEAR OPENING
32" MIN 44" MIN
48" MIN IF DOOR HAS A LATCH AND CLOSER
PULL SIDE
PUSH SIDE
'X'
80" MIN 'X'
1/2" MAX
LI JO C N
8"
AT DOOR
0520_09_FLOORING TRANSITION_01 170614. Q2
11
CONVENIENC E WALL OUTLET
FINISHED FLOOR
ACCESSIBLE MOUNTING HEIGHT REQUIREMENTS 0500_08_ACCESSIBLE MOUNTING HEIGHT REQUIREMENTS_01 170614. Q2
1/2" = 1'-0"
15
DOOR OTHER THAN SLIDING DOOR IN ACCESSIBLE PATH OF TRAVEL
PUSH SIDE
ACCESSIBLE DOOR SURFACE REQUIREMENT 0500_08_ACCESSIBLE DOOR SURFACE REQUIREMENTS_01 170614. Q2
3" = 1'-0"
IA N
9
R
1/4" MAX
1/4" MAX
6"
CLIENT
FOR TEXT SIZE AND MOUNTING HEIGHT
6" = 1'-0"
THERMOSTAT
KICK PLATE
NOTES: PROVIDE EXIT SIGNAGE PER: CBC 1011, 11B-216, 11B-703
18
BELOW CEILING
AT WINDOW
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
ASSISTIVE LISTENING SIGN 1/4" = 1'-0"
0570_10_ASSISTIVE LISTENING SIGNAGE_01 170614. Q2
ISSUED
IN NEW CONSTRUCTION, ALL PRIMARY ENTRANCES AND EXTERIOR GROUND FLOOR EXIT DOORS TO BUILDINGS AND FACILITIES SHALL BE ACCESSIBLE TO THE DISABLED. 2. IN EXISTING BUILDINGS WHERE NOT ALL ENTRANCES ARE ACCESSIBLE, ALL ACCESSIBLE ENTRANCES SHALL BE IDENTIFIED WITH AT LEAST ONE STANDARD INTERNATIONAL SYMBOL OF ACCESSIBILITY SIGN AND WITH ADDITIONAL DIRECTIONAL SIGNS, AS REQUIRED, VISIBLE FROM APPROACHING PEDESTRIAN WAYS. 3. EVERY REQUIRED ENTRANCE OR PASSAGE DOORWAY SHALL BE OF A SIZE AS TO PERMIT THE INSTALLATION OF A DOOR NOT LESS THAN 36 INCHES IN WIDTH, AND NOT LESS THAN 80 INCHES IN HEIGHT. DOORS SHALL BE CAPABLE OF OPENING AT LEAST 90 DEGREES AND SHALL BE MOUNTED SO THAT THE CLEAR WIDTH THE DOORWAY IS NOT LESS THAN 32 INCHES. 4. LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED AND WHICH ARE PART OF AN ACCESSIBLE ROUTE OR SPACE, SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE HARDWARE, PANIC BARS, PUSH-PULL ACTIVATING BARS. OR OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP THE OPENING HARDWARE. 5. HAND ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED BETWEEN 34 INCHES MINIMIUM AND 44 INCHES MAXIMUM ABOVE THE FLOOR. 6. THE FLOOR OR LANDING LENGTH ON EACH SIDE OF AN ENTRANCE OR A PASSAGE DOOR SHALL BE LEVEL AND CLEAR AT LEAST 60 INCHES IN THE DIRECTION OF THE DOOR SWING AND AT LEAST 48 INCHES OPPOSITE THE DIRECTION OF THE DOOR SWING AS MEASURED AT RIGHT ANGLES TO THE FACE OF THE DOOR IN THE CLOSED POSITION. THE WIDTH OF THE LEVEL AND CLEAR AREA ON THE SIDE WHICH THE DOOR SWINGS SHALL EXTEND A MINIMUM OF 24 INCHES PAST THE STRIKE EDGE OF THE DOOR FOR DOORS WITH LATCH SIDE APPROACH AND 36 INCHES FOR DOORS REQUIRING HINGE SIDE APPROACH. 7. THE FLOOR OR LANDING SHALL NOT BE MORE THAN 1/2 INCH LOWER THAN THE THRESHOLD OF THE DOORWAY. CHANGES IN LEVEL BETWEEN 1/4 INCH AND 1/2 INCH SHALL BE BEVELED WITH A SLOPE NO GREATER THAN 1:2. 8. THE BOTTOM 10 INCHES OF ALL DOORS (EXCEPT AUTOMATIC AND SLIDING) SHALL HAVE A SMOOTH UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION WHERE NARROW FRAME DOORS ARE USED, A 10 INCH HIGH SMOOTH PANEL SHALL BE INSTALLED ON THE PUSH SIDE OF THE DOOR, WHICH WILL ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST. 9. THE MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED 5 LBS. FOR EXTERIOR OR INTERIOR DOORS. SUCH PULL OR PUSH EFFORT BEING APPLIED AT RIGHT ANGLES TO HINGED DOORS AND AT THE CENTER PLANE OF SLIDING OR FOLDING DOORS. COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS MAY BE UTILIZED TO MEET THE ABOVE STANDARDS. WHEN FIRE DOORS ARE REQUIRED, THE MAXIMUM EFFORT TO OPERATE THE DOOR MAY NOT EXCEED 15 LBS. 10. EACH GRADE-LEVEL EXTERIOR EXIT DOOR SHALL BE IDENTIFIED BY A TACTILE SIGN WITH THE WORD "EXIT". EACH EXIT DOOR THAT LEADS DIRECTLY TO GRADE-LEVEL EXTERIOR EXIT BY MEANS OF STAIRWAY OR RAMP IS IDENTIFIED BY A TACTILE SIGN THAT STATES "EXIT STAIR DOWN," "EXIT RAMP DOWN," "EXIT STAIR UP," OR "EXIT RAMP UP" AS APPROPRIATE. EACH EXIT DOOR THAT LEADS DIRECTLY TO GRADE-LEVEL EXTERIOR EXIT BY MEANS OF AN EXIT ENCLOSURE OR EXIT PASSAGEWAY IS IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "EXIT ROUTE." EACH ACCESS DOOR FROM AN INTERIOR ROOM OR AREA TO A CORRIDOR OR HALLWAY THAT IS REQUIRED TO HAVE A VISUAL EXIT SIGN IS IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "EXIT ROUTE". EACH DOOR THROUGH A HORIZONTAL EXIT IS IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "TO EXIT."
MARK
DATE
DESCRIPTION
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
016279.06 ?00.00.00? LIONAKIS 2015
AGENCY
CLEAR FLOOR SPACE FOR WHEELCHAIRS
44" MIN
°
HINGE APPROACH DOOR CLEARANCES, TYP
18" X 18" MIN CLEAR FLOOR SPACE TO BE PROVIDED CENTERED ON SIGNAGE
WHERE A TACTILE SIGN IS PROVIDED AT DOOR, THE SIGN SHALL BE LOCATED ALONGSIDE THE DOOR AT EACH LATCH WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE DOORS WITH ONE ACTIVE LEAF, THE SIGN SHALL BE LOCATED ON THE INACTIVE LEAF WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE DOORS WITH TWO ACTIVE LEAVES, THEN THE SIGN SHALL BE LOCATED TO THE RIGHT OF THE RIGHT HAND DOOR WHERE THERE IS NO WALL SPACE AT THE LATCH SIDE OF A SINGLE DOOR OR AT THE RIGHT SIDE OF A DOUBLE DOOR, SIGNS SHALL BE LOCATED ON THE NEAREST ADJACENT WALL WHERE PERMANENT IDENTIFICATION SIGNAGE IS PROVIDED FOR ROOMS AND SPACES THEY SHALL BE LOCATED ON THE APPROACH SIDE OF THE DOOR AS ONE ENTERS THE ROOM OR SPACE SIGNS THAT IDENTIFY EXITS SHALL BE LOCATED ON THE APPROACH SIDE OF THE DOOR AS ONE EXITS THE ROOM OR SPACE TACTILE SIGNS TO BE MOUNTED AT 60" ABOVE THE FLOOR TO THE CENTER OF THE SIGN PROVIDED THAT BASED ON THE SIGN CONTENT THE RAISED CHARACTERS ARE 60" MAXIMUM TO THE BASELINE OF THE HIGHEST RAISED CHARACTER AND 48" MINIMUM TO THE BASELINE OF THE LOWEST RAISED CHARACTER OR BRAILLE
60" MIN
2. 3.
EXIT ROUTE EXIT ROUTE
NOTE : DOOR CLOSERS, IF PRESENT, MUST BE SET SO THAT IT TAKES DOOR AT 1. LEAST 5 SECONDS TO CLOSE FROM AN OPEN POSITION OF 90 DEGREES TO 12 DEGREES FROM THE LATCH PER 11B-404.2.8.1.
TYPE 2 LOCATE AT EACH ACCESS DOOR FROM AN INTERIOR ROOM OR AREA TO A CORRIDOR OR HALLWAY, AND EACH DOOR THAT LEADS TO A GRADE LEVEL EXIT BY MEANS OF EXIT ENCLOSURE OR EXIT PASSAGEWAY.
1. 2. 3. 4.
2.
FORCE REQUIRED TO OPERATE DOOR SHALL BE 5 LBS MAXIMUM PRESSURE AT INTERIOR AND EXTERIOR DOORS AND 15 LBS MAXIMUM TO OPERATE AT FIRE DOORS WHERE ALLOWED BY THE AHJ PER CBC 11B-404.2.9.
LOCATION PER
4 G-111
PUSH SIDE PULL SIDE LATCH APPROACH DOOR CLEARANCES, TYP NOTE: AREA MUST NOT EXCEEED A SLOPE OF 2% IN ANY DIRECTION
8
ACCESSIBLE DOOR CLEARANCES 1/2" = 1'-0"
0540_08_ACCESSIBLE DOOR CLEARANCES_01 170614. Q2
12
ACCESSIBLE DOOR CLOSER REQUIREMENTS 1/2" = 1'-0"
0540_08_ACCESSIBLE DOOR CLOSER REQUIREMENTS_01
16
TYP
5.
6 G-111
TYP
EXIT SIGNS 1/2" = 1'-0"
MINIMUM CLEAR FLOOR OR GROUND SPACE REQUIRED TO ACCOMMODATE A SINGLE, STATIONARY WHEELCHAIR AND OCCUPANT IS 30 INCHES BY 48 INCHES. MINIMUM CLEAR FLOOR OR GROUND SPACE FOR WHEELCHAIRS MAY BE POSITIONED FOR FORWARD OR PARALLEL APPROACH TO AN OBJECT, UNLESS RESTRICTED BY CODE. FLOOR OR GROUND SPACE FOR WHEELCHAIRS MAY BE PART OF THE KNEE SPACE REQUIRED UNDER SOME ELEMENTS AS ALLOWED BY CODE. PROVIDE A MINIMUM CLEAR SPACE 60 INCHES WIDE AT ALCOVES GREATER THAN 15 INCHES DEEP AND DESIGNED FOR SIDE APPROACH. PROVIDE A MINIMUM CLEAR SPACE 36 INCHES WIDE AT ALCOVES GREATER THAN 24 INCHES DEEP AND DESIGNED FOR FRONT APPROACH.
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
FLS
SS
DATE
HAZARDOUS AND PROJECTING OBJECTS
CHARACTERS AND BRAILLE PER
SIGN LOCATION 0570_10_LOCATION OF TACTILE SIGNS AT DOORS_01 170614. Q2
1.
HAND ACTIVATED DOOR OPENING HANDLE AND HARDWARE. PER CBC 11B-404.2.7 & 11B-309.4
48" MIN IF DOOR HAS A CLOSER
1/2" = 1'-0"
34"- 44"
1/2" MAX
60" MIN
CLEAR OPENING
3.
SEE
FLOORING TRANSITION
FIRE ALARM
DOOR HANDLE/ PANIC HARDWARE WHERE OCCURS
24" MIN
A
14
EN . 08 - 3 1 - 1 O F OF CAL I
7667 FOLSOM BLVD, SACRAMENTO, CA 95826
3 G-111
1.
4'-0"
32" MIN
2.
R E
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
ENTRANCES AND DOORS:
FRONT APPROACH DOOR CLEARANCES, TYP
NOTES: 1.
T
PROJECT
90
18" MIN
D A RCH SE I E N A N McM TE H U T A
C23603
MAX
12°
CL
2
MAXIMUM HEIGHT AT LEVEL CHANGE WITH NO TRANSITION
SWITCHES
5'-0"
0570_10_DIRECTIONAL AND INFORMATIONAL 170614. SIGNS_01 Q1 NO WALL MOUNTED PROTRUDING OBJECTS MORE THAN 3" BEYOND FACE OF WALL AT SIGN LOCATION
1/2" = 1'-0"
1
CLEAR SPACE FINISH ELEVATION TO MATCH FINISH FLOOR ELEVATION AT DOOR PROVIDE THIS ADDITIONAL SPACE IF DOOR IS EQUIPED WITH A LATCH AND A CLOSER
32" MIN
3
ASSISTIVE LISTENING SYSTEM AVAILABLE _______
DEVICE CALCULATIONS PROVIDED ON SIGNAGE PLAN, ALS REQUIRED AT ALL ASSEMBLY AND CONFERENCE AREAS
WHERE AN OBSTRUCTION IS MORE THAN 8", PROVIDE THE NOTED CLEAR SPACE
DIRECTIONAL AND INFORMATIONAL SIGNS
SEAL
13"
SMOOTH, UNINTERRUPTED SURFACE
21 feet (6401 mm) and greater
3 inches (76 mm), plus 1/8 inch (3.2 mm) per foot (305 mm) of viewing distance above 21 feet (6401 mm)
0500_08_ACCESSIBLE DOOR HARDWARE REQUIREMENTS_01 170614. Q2
1" = 1'-0"
18" MIN UON
3 inches (76 mm)
0570_10_SIGNAGE FOR FUNCTIONAL ROOMS AND SPACES_01 170614. Q2
1/4" = 1'-0"
10
ACCESSIBLE DOOR HARDWARE REQUIREMENTS
UNOBSTRUCTED
Less than 21 feet (6401 mm)
PERMANENT ROOM IDENTIFICATION SIGNS
48" MAX
2 inches (51 mm), plus 1/8 inch (3.2 mm) per foot (305 mm) of viewing distance above 180 inches (4572 mm)
TYP
34" MIN
180 inches (4572 mm) and greater
MAX
"AT MAIN LOBBY BEHIND SECURITY DESK"
MAXIMUM HEIGHT AT SLOPED LEVEL CHANGE
2. LATCHING AND LOCKING DOORS THAT ARE HAND-ACTIVATED AND WHICH ARE IN ACCESSIBLE ROUTE, SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER-TYPE HARDWARE, PANIC BARS OR OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE. LOCKED EXIT DOORS SHALL OPERATE AS ABOVE IN EGRESS DIRECTION.
44" MAX
2 inches (51 mm)
HAND-ACTIVATED DOOR OPENING 1. HARDWARE, HANDLES, PULLS, LATCHES. LOCKS AND OTHER OPERATING DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT GRASPING. TIGHT PINCHING OR TWISTING OF THE WRIST TO OPERATE.
PUSH
36" MIN
Less than 180 inches (4572 mm)
2 1
SIGN NOT REQUIRED TO BE PROVIDED AT A DOOR, BUT MUST BE POSTED AT A PROMINENT LOCATION NEAR THE ASSEMBLY AREA / CONFERENCE ROOM ENTRANCE. SEE SIGNAGE PLAN FOR LOCATIONS
1/4" MAX
6 CHARACTERS AND BRAILLE PER G-111
PULL SIDE
72 inches (1829 mm) and greater
5/8 inch (15.9mm), plus 1/8 inch (3.2 mm) per foot (305 mm) of viewing distance above 72 inches (1829 mm)
0530_00_PROTRUDING OBJECTS_01
1/2" = 1'-0"
MAXIMUM HEIGHTS AT ALL THRESHOLDS
MIN
PER CHART BELOW
5/8 inch (15.9 mm)
LEVER
NOTES: 1. VERIFY ROOM NAMES W/ ARCHITECT BEFORE FABRICATION 2. MOUNTED TO WALL PER SPECIFICATIONS 3. CENTER CHARACTERS AND BRAILLE 4. IF SIGN TACTILE CHARACTERS ARE NOT CENTERED, CLEAR FLOOR AREAS NEED TO BE ADJUSTED. SEE DETAIL 20
54" MIN
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
Greater than 120 inches (3048 mm)
Less than 72 inches (1829 mm)
CARPET WILL NOT EXCEED 1/2" HIGH PILE WHERE INSTALLED CARPET TO BE PERMANENTLY AND SECURELY AFFIXED TO FLOOR
LOOP
CLEAR OPENING
40" MIN
Greater than 70 inches (1778 mm) to less than or equal to 120 inches (3048 mm)
MINIMUM CHARACTER HEIGHT
1.
SHOW ALL LINES CENTERED
CL
5
PROTRUDING OBJECTS
17
CORRESPONDING BRAILLE
48" AFF MIN BOT OF LOWEST LINE OF BRAILLE
HORIZONTAL VIEWING DISTANCE
FINISHED FLOOR
NOTES:
18" MIN
B
A. DISTANCE BETWEEN CORRESPONDING DOTS FROM ONE CELL DIRECTLY BELOW: 0.395 TO 0.400 B. DISTANCE BETWEEN TWO DOTS IN THE SAME CELL : 0.100, MEASURED CENTER TO CENTER C. DISTANCE BETWEEN CORRESPONDING DOTS IN ADJACENT CELLS: 0.300 D. SINGLE BRAILLE CELL E. BLANK CELL SPACE BETWEEN WORDS F. BASE DIAMETER: 0.059 TO 0.063 G. NO RAISED DOT, BLANK CELL SPACE BETWEEN WORDS
PROVIDE CANE DETECTABLE ELEMENT IF 'P' > 4" AND 'X' > 27"
CT Y R RT
234
BOT OF HIGHEST LINE OF RAISED CHARACTERS
CHARACTERS AND THEIR BACKGROUND MUST HAVE A NON-GLARE FINISH CHARACTERS MAY BE UPPERCASE, LOWERCASE, OR A COMBINATION OF BOTH CHARACTERS MUST BE SANS SERIF; WITHOUT ITALICS, SCRIPT, OR OTHER DECORATIVE OR UNUSUAL FORMS CHARACTERS MUST BE SELECTED FROM FONTS WHERE THE WIDTH OF THE UPPERCASE "O" IS 60-110% OF THE HEIGHT OF THE UPPERCASE "T". FLOOR PLANS PROVIDING EMERGENCY INFORMATION DO NOT NEED TO COMPLY WITH THIS REQUIREMENT CHARACTERS MUST BE SELECTED FROM FONTS WHERE THE STROKE THICKNESS OF THE UPPERCASE "I" IS 10-20% OF THE HEIGHT OF THE LETTER CHARACTER SPACING, MEASURED BETWEEN THE TWO CLOSEST POINTS OF ADJACENT CHARACTERS, MUST BE 10-35% OF THE CHARACTER HEIGHT SPACING BETWEEN BASELINES OF MULTI-LINE TEXT MUST BE 135-170% OF THE CHARACTER HEIGHT TEXT MUST BE IN A HORIZONTAL FORMAT TEXT MUST MEET THE FOLLOWING HEIGHT REQUIREMENTS FOR VIEWING DISTANCE: TABLE 11B-703.5.5 VISUAL CHARACTER HEIGHT
HEIGHT TO FINISH FLOOR OR GROUND FROM BASELINE OF CHARACTER 40 inches (1016 mm) to less than or equal to 70 inches (1778 mm)
4" MAX IF 'X' > 27"
A
8. 9.
BRAILLE SHALL BE PER CBC 11B-703.3 INCLUDING, BUT NOT LIMITED TO THE FOLLOWING: DISTANCES IN INCHES, MIN TO MAX.
ST
7.
A. CHARACTERS SHALL BE RAISED 1/32" MINIMUM ABOVE THEIR BACKGROUND. B. CHARACTER HEIGHT SHALL BE A MINIMUM OF 5/8" AND A MAXIMUM OF 2" HIGH BASED ON THE UPPERCASE "I". C. CHARACTERS SHALL BE SEPARATED FROM ANY RAISED BORDER OR DECORATIVE ELEMENT BY 3/8" D. CHARACTER FONT PROPORTION WITH THE UPPERCASE 'O' WIDTH BEING 60 PERCENT MINIMUM TO 110 PERCENT MAXIMUM THE HEIGHT OF THE UPPERCASE 'I'. E. CHARACTER STROKE THICKNESS OF THE UPPERCASE 'I' SHALL BE 15 PERCENT MAXIMUM THE HEIGHT OF CHARACTER. F. CHARACTER THAT ARE RECTANGULAR IN CROSS SECTION SHALL BE A 1/8" MINIMUM AND 4 TIMES THE RAISED CHARACTER STROKE WIDTH MAXIMUM. G. RAISED CHARACTERS SHALL HAVE EASED EDGES.
NOTES: 1. PERMANENT SIGNAGE TO BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. 2. MOUNTING LOCATION MUST ALLOW A PERSON TO APPROACH WITHIN 3" OF SIGNAGE WITHOUT ENCOUNTERING PROTRUDING OBJECTS OR STANDING WITHIN THE SWING PATH OF THE DOOR. PROVIDE 18" SQUARE CLEAR FLOOR AREA AT TACTILE SIGNS. 3. SIGNS AND IDENTIFICATION SHALL BE FIELD INSPECTED AFTER INSTALLATION AND APPROVED BY THE ENFORCING AGENCY, IN ACCORDANCE WITH SECTION 11B-703.1.1.2 "INSPECTION" AS 9" 9" REQD CLR FLR SPACE REQD CLR FLR SPACE REQD RAISED CHARACTERS (ROOM NAME AND NUMBER) 60" AFF MAX
DIRECTIONAL AND INFORMATIONAL SIGNS THAT ARE NOT REQUIRED TO HAVE TACTILE/BRAILLE CHARACTERS SHALL COMPLY WITH THE FOLLOWING:
6.
BRAILLE REQUIREMENTS AND LEGEND:
PROTRUDING OBJECT
PROTRUDING OBJECT
?DRS TRACKING NUMBER? ?YYMMDD?. Q1
F.F.
5.
'P'
BOT OF LOWEST LINE OF BRAILLE
6" = 1'-0"
234
4.
48" AFF MIN BOT OF LOWEST LINE OF BRAILLE
ACCESSIBLE TACTILE SIGN REQUIREMENTS
6
CL
3.
CONTRACTED GRADE 2 BRAILLE AT WALL SIGN
RAISED CHARACTER REQUIREMENTS AND LEGEND:
3" MIN
0570_10_ STANDARD SYMBOLS_01 170614. Q1
SIGN SIZE BASED ON TEXT SIZE REQUIREMENTS
1. 2.
BOT OF HIGHEST LINE OF RAISED CHARACTER S 48" AFF MIN
1/8" BACKPLATE AT WALL SIGN
BRAILLE TO BE CONTRACTED GRADE 2, AND DOT HEIGHT TO BE 0.025 TO 0.037. DOTS MUST BE DOMED OR ROUNDED. DOTS INDICATING UPPERCASE LETTER OR LETTERS MUST ONLY BE USED AT THE FIRST WORD OF SENTENCES, PROPER NOUNS AND NAMES, INDIVIDUAL LETTERS OF THE ALPHABET, INITIALS, AND/OR ACRONYMS.
STANDARD SYMBOLS
C
G
FONT: DIN-PRO TEXT COLOR: WHITE
MATERIAL: 1/4" NONGLARE PLEX COLOR: BLACK
DIRECTIONAL AND INFORMATIONAL SIGN
60" AFF MAX 3/8"-1/2"
3/8"
G
1/32" RAISED TEXT AT WALL SIGN
A
2201A
C
INTERNATIONAL SYMBOL OF ACCESS FOR HEARING LOSS
1/2" = 1'-0"
D
E
VOLUME CONTROL TELEPHONE
INTERNATIONAL SYMBOL OF TTY
B
F
8"
1
4/25/2019 8:48:51 AM
7/16"
C
3/4"
AUDIOLOGY
C
10" MIN - FULL WIDTH OF DOOR
INTERNATIONAL SYMBOL OF ACCESSIBILITY (ISA)
D
E D A
RAISED CHARACTERS SHALL BE UPPERCASE, SANS-SERIF, HORIZONTAL FORMAT, WITH FONTS PER CBC 11B-703.2
1 1/2".
4.
ALL SYMBOLS TO CONSIST OF A WHITE FIGURE ON A BLUE BACKGROUND BLUE TO APPROXIMATE FS15090 IN FEDERAL STANDARD 595C ALTERNATE COLORS MAY BE USED IF APPROVED BY THE AUTHORITY HAVING JURISDICTION, BUT CONTRAST MUST REMAIN - EITHER DARK ON LIGHT OR LIGHT ON DARK SEE SIGNAGE PLAN AND SPECIFIC SIGN DETAILS FOR SIZES AND APPLICATION
B
1. 2. 3.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
B B
RAISED CHARACTERS AND SIGN FIELD TO HAVE NON-GLARE FINISH.
6 1/2"
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
?DRS TRACKING NUMBER? ?YYMMDD?. Q1
OBJECTS PROJECTING FROM WALLS WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80 INCHES ABOVE THE FINISHED FLOOR SHALL PROTRUDE NO MORE THAN 4" INTO WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES. OBJECTS MOUNTED WITH THEIR LEADING EDGES AT OR BELOW 27 INCHES ABOVE THE FINISHED FLOOR MAY PROTRUDE ANY AMOUNT. FREE-STANDING OBJECTS MOUNTED ON POSTS / PYLONS MAY OVERHANG 12 INCHES MAXIMUM FROM 27 INCHES TO 80 INCHES ABOVE THE GROUND OR FINISHED FLOOR. PROTRUDING OBJECTS SHALL NOT REDUCE THE REQUIRED CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING SPACE. ANY OBSTRUCTION OVERHANGING A PEDESTRIAN WAY SHALL BE A MINIMUM OF 80 INCHES ABOVE THE WALKING SURFACE AS MEASURED TO THE BOTTOM OF THE OBSTRUCTION.
TITLE
ACCESSIBILITY REQUIREMENTS
DISCREPANCIES 1.
THE INFORMATION DEPICTED ON THIS SHEET REPRESENT BUILDING CODE REQUIREMENTS. NOTIFY THE ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES ON THIS PROJECT THAT WOULD CREATE A CONFLICT WITH THE PLANS OR ACCESS REQUIREMENTS.
20
ACCESSIBLE ROUTE NOTES 1/2" = 1'-0" 0500_00_ACCESSIBLE Q1 PATH OF TRAVEL NOTES_01.
SHEET
G-111
2"
1
2
3
4
5
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
FLOOR PLAN LEGEND 1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
EXISTING, NOT IN SCOPE
LIMITS OF ARCHITECTURAL WORK
D
7
4
5
8
6
SEAL
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
2
3
N
EN . 08 - 3 1 - 1 O F OF CAL I
9
A
1
R E
R
ST T
C
IA
C23603
PROJECT
C
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
D
7667 FOLSOM BLVD, SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
AREA A
E
ISSUED
F
MARK
DATE
DESCRIPTION
DN DN
UP DN
G
B
H
AREA B
MANAGEMENT
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
I AGENCY
1 A-112A
J
KEY PLAN
1
FLOOR PLAN - LEVEL 2 - OVERALL IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SCALE 1/16" = 1'-0"
AC
A
FLS
SS
DATE A
TITLE
B
PLAN NORTH
4/25/2019 8:48:09 AM
016279.06 ?00.00.00? LIONAKIS 2015
FLOOR PLAN LEVEL 2 OVERALL SHEET
A-112
2
3
4
GENERAL NOTES - DEMOLITION 7
8
D
SERV DESK WAITING 2401
2400
1. THE INTENT OF THE CONSTRUCTION DOCUMENTS IS THAT THE WORK OF ALTERATION, REHABILITATION OR RECONSTRUCTION SHALL BE IN ACCORDANCE WITH APPLICABLE CODES AND ENFORCEMENT AGENCIES. SHOULD ANY EXISTING CONDITIONS SUCH AS DETERIORATION OR NON-COMPLYING CONSTRUCTION BE DISCOVERED WHICH IS NOT COVERED BY THE CONSTRUCTION DOCUMENTS, WHEREIN THE PROJECT WORK WILL NOT COMPLY WITH APPLICABLE CODES AND/OR ENFORCEMENT AGENCIES, THE CONTRACTOR(S) SHALL IMMEDIATELY NOTIFY THE ARCHITECT AND/OR OWNER’S REPRESENTATIVE IN WRITING UPON DISCOVERY. A CONSTRUCTION CHANGE DOCUMENT (CCD), OR A SEPARATE SET OF PLANS AND SPECIFICATIONS, DETAILING AND SPECIFYING THE REMEDIAL REQUIRED WORK SHALL BE SUBMITTED TO, AND APPROVED BY, THE APPLICABLE ENFORCEMENT AGENCIES PRIOR TO THE CONTRACTOR(S) PROCEEDING WITH THE WORK.
SERV DESK WAITING 2401
CORRIDOR
2400
CORRIDOR
2316
2316
PT OFFICE
PT OFFICE
2306B
2306B
SERV CLOS.
SERV CLOS. MB1
2401A
2604
2401A
0S3A U
CLASSROOM
PT OFFICE
2604
2306A 0S3A V 0S3A
PT OFFICE
CLASSROOM
2306A
2604
0S3A
8'-5"
CLOS. 2308A
E AUDIO LAB TEST BOOTH 2305A
AUDIOLOGY LAB
AUDIOLOGY LAB
2601
2602
0S3A U
CLOS. AUDIO LAB TEST BOOTH
0S3A V 11'-4 3/4"
0S3A V 11'-4"
17'-2"
E
2601
AUDIOLOGY LAB
AUDIOLOGY LAB 2601 8'-5"
7 A-531
0S3A U
2305
2602 8'-5"
8'-5"
2305
3 A-531
CORRIDOR 2309
35/16" 5/16"
2309
F
CORRIDOR
CORRIDOR
2404K
2404K
AUXILLARY OBSERVATION
DN
2320
STAIR NO. 2
STORAGE
STORAGE
2304B
2304
2504 DN
2319
3. WHERE DEMOLITION WORK IS REFERENCED WITHIN THE CONSTRUCTION DOCUMENTS, THIS SHALL MEAN DEMOLITION OF ANY/ALL PARTS OF THE ASSOCIATED ASSEMBLY, IN ITS ENTIRETY, TO BE DEMOLISHED.
2603
CORRIDOR
OBSERVATION
2. THE CONTRACTOR(S) SHALL FIELD VERIFY ALL EXISTING CONDITIONS WHICH ARE INCLUDED AS A PART OF THE WORK, AND WHICH SHALL REMAIN. CONTRACTOR(S) SHALL IDENTIFY ANY EXISTING DAMAGED CONDITIONS OR ASSEMBLIES TO THE ARCHITECT AND/OR OWNER’S REPRESENTATIVE PRIOR TO CONSTRUCTION. CONTRACTOR(S) SHALL PATCH, REPAIR AND RE-FINISH ANY/ALL EXISTING AFFECTED CONDITIONS AND/OR ASSEMBLIES WHICH ARE TO REMAIN AS PART OF THE WORK TO MATCH THE EXISTING CONSTRUCTION AND FINISHED APPEARANCE OF THE EXISTING ADJACENT CONSTRUCTION TO REMAIN, OR ANY/ALL NEW WORK WHICH ABUTS OR IS DIRECTLY ADJACENT TO THE LOCATIONS OR ASSEMBLIES.
2603
J 2602
F
AUDIOLOGY LAB AUDIOLOGY LAB
AUDIO LAB CONSULT
2603
AUDIO LAB CONSULT
2308A
2305A 19'-2 5/8"
D
2'-1" FOF
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
D
OBSERVATION 2319
OBVS. CLOS.
2322
2322
STAIR NO. 2
STORAGE
STORAGE
2504
2304B
2304
4. CONTRACTOR(S) SHALL PROTECT ANY/ALL EXISTING CONSTRUCTION AND/OR EQUIPMENT WHICH IS TO REMAIN IN PLACE DURING THE PERFORMANCE OF THE WORK. 5. THE CONTRACTOR(S) SHALL PROVIDE TEMPORARY BARRICADES OR PARTITIONS AS REQUIRED TO ISOLATE DEMOLITION AND/OR CONSTRUCTION OF THE WORK FROM OCCUPIED SPACES. PROVIDE A SAFE MEANS OF EGRESS THROUGH AND/OR AROUND THE BUILDING AND SITE PER APPLICABLE CODES AT ALL TIMES DURING THE CONSTRUCTION PROCESS. MINIMIZE DISRUPTION TO ADJACENT AREAS TO THE GREATEST EXTENT POSSIBLE. 6. CONTRACTOR(S) SHALL PROVIDE DUST CONTROL BETWEEN CONSTRUCTION AREAS AND OCCUPIED AREAS AT ALL TIMES.
1. ARCHITECTURAL DIMENSIONS ARE TO FACE OF STUDS OR CENTERLINE OF COLUMN GRIDS UNLESS OTHERWISED NOTED. 1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
2. LOCATE DOOR JAMBS 4" AWAY FROM ADJACENT WALL UNLESS OTHERWISED DIMENSIONED. 3. KEY NOTED WALL TYPES SHALL EXTEND FROM CORNER TO CORNER, FULL LENGTH OF WALL UNLESS OTHERWISED NOTED. 4. FOR SYMBOLS LEGEND, SEE SHEET G-001 5. FOR CASEWORK DETAILS, SEE SHEET A-561 6. FOR INTERIOR ELEVATIONS, SEE SHEET A-221 7. FOR WALL TYPES, WALL SCHEDULE, WALL FRAMING AND BLOCKING REQUIREMENTS, SEE SHEETS A-531, A-532, AND A-533 8. FOR DOOR SCHEDULE, SEE SHEET A-541 9. FURNITURE SHOWN ARE FOR REFERENCE ONLY. NOT IN SCOPE 10. A MINIMUM OF 72 HOUR NOTICE IS REQUIRED FOR ANY TESTING AND/OR INSPECTION
FLOOR PLAN LEGEND 1S4A J PARTITION TYPE INDICATOR
KEYNOTE INDICATOR
22
DOOR OPENING IDENTIFIER
101A PLAN NORTH
PLAN NORTH & TRUE NORTH INDICATOR SEAL
ROOM NAME
D A RCH SE I E N A N McM TE H U T A
ROOM NAME AND NUMBER
2001A
CT Y R RT
OBVS. CLOS.
GENERAL NOTES - FLOOR PLAN
8
1"
7
5
LI JO C N
2"
1
2323
G
2323
G
C
ELEV NO.1
0S3A
2204
ELEV NO.1
101
MB2
101
J
STAIR NO.1
STAIR NO.1
LOBBY
2404J
LOBBY
2404J
1000
0S3A U
1000
8. IN AREAS OF DEMOLISHED FLOOR AND WALL FINISHES, CONTRACTOR SHALL BE RESPONSIBLE TO FULLY REMOVE ALL EXISTING CONSTRUCTION MATERIAL, INCLUSIVE OF ADHESIVES AND/OR MECHANICAL FASTENERS AND CERAMIC TILE MORTAR BED. CONTRACTOR SHALL PREP ALL SURFACES TO ACCOMMODATE FINISHES (INCLUDING MECHANICAL ABRADING OF EXISTING SURFACES AND FILLING OF HOLES, WITH APPROPRIATE MATERIALS, AS NECESSARY. 9. ALL EXISTING, TO REMAIN FINISHES, TO BE PROTECTED AS NECESSARY DURING CONSTRUCTION.
CORRIDOR
COMPUTER LAB
2315
2204
H
COMPUTER LAB 2204
H
FLOOR PLAN LEGEND
R E
N
T
EXISTING, NOT IN SCOPE
EN . 08 - 3 1 - 1 O F OF CAL I
9
CORRIDOR
R
3 A-531
A
CORRIDOR
ST
7 A-531
IA
C23603
7. CONTRACTOR(S) SHALL MINIMIZE CONSTRUCTION NOISE TO A LEVEL ACCEPTABLE TO BOTH THE OWNER, AND AS REQUIRED BY ANY LOCAL JURISDICTIONS SURROUNDING THE PROJECT SITE. SCHEDULING OF TASKS CREATING EXCESSIVE NOISE, OR ADJACENT TO NOISESENSITIVE AREAS, SHALL BE CAREFULLY COORDINATED AND SCHEDULED WITH THE OWNER’S REPRESENTATIVE.
PROJECT
MB1
8'-0" W x 4'-0" H WHITE MARKERBOARD, PROVIDE BACKING PER DETAIL
MB2
4'-0" W x 4'-0" H WHITE MARKERBOARD, PROVIDE BACKING PER DETAIL
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
1 A-533
1 A-533
7667 FOLSOM BLVD, SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
GENERAL NOTES - CEILING
10. REFER TO DOOR AND FRAME SCHEDULES FOR REFERENCED FRAMED OPENINGS AND REQUIRED DEMOLITION IN EXISTING WALLS TO ACCOMMODATE FRAMED OPENINGS.
1. ALL CEILING GRID LAYOUTS FROM THE CENTER OF THE ROOM, FULL TILE FROM ROOM CORNER, UNLESS NOTED OTHERWISE.
11. DEMOLITION KEYNOTE ARE FOR REFERENCE AS AN OVERALL LIST. NOT ALL DEMOLITION NOTES LISTED ARE APPLICABLE TO EACH SHEET. REFER TO SPECIFIC DEMOLITION PLANS FOR NOTES THAT APPLY.
CEILING PLAN LEGEND
CORRIDOR 2315
8'-5"
MECHOSHADES, SP1, SEE DETAIL
4 A-551
ISSUED
12. PROVIDE SAFEGUARDS FOR CONSTRUCTION, ALTERATIONS, AND DEMOLITION OPERATIONS TO PROVIDE REASONABLE SAFETY TO LIFE AND PROPERTY FROM FIRE DURING SUCH OPERATIONS PER COMPLIANCE WITH "FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION" IN ACCORDANCE WITH 2016 CALIFORNIA BUILDING CODE, CALIFORNIA FIRE CODE CHAPTER 33, AND CALIFORNIA CODE OF REGULATIONS TITLE 19, DIVISION 1
MARK
DATE
DESCRIPTION
CEILING HEIGHT
8'-5"
(E) 24" X 48" ACT SYSTEM
I
I
DEMO LEGEND
24" X 48" ACT SYSTEM, FOR DETAILS SEE SHEET A-551
B
1
PARTIAL FLOOR PLAN - LEVEL 2 - AREA A & B
2
SCALE 1/8" = 1'-0"
7
SCALE 1/8" = 1'-0"
REMOVE (E) INTERIOR PARTITION
AD02
REMOVE (E) INTERIOR DOOR AND FRAME
AD03
REMOVE (E) 2X2 CEILING GRID
AD04
REMOVE (E) 2X2 LIGHT FIXTURE
(E) CEILING MOUNTED EXIT SIGN MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
016279.06 ?00.00.00? LIONAKIS 2015
24" X 48" RECESSED LIGHT FIXTURE AGENCY
AUDIOLOGY LAB 2603
AUDIO LAB CONSULT
CEILING MOUNTED PROJECTION SCREEN BY OTHERS, NIC. CONTRACTOR TO PROVIDE CEILING BACKING/SUPPORT
AD02
2305
CORRIDOR F
2309
KEY PLAN
CORRIDOR 2404K DN
OBSERVATION
STAIR NO. 2 2504 DN
2319
STORAGE
STORAGE
2304B
2304
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
OBVS. CLOS. 2322
A
G
CORRIDOR
CORRIDOR
2323
2323
2204
AC
A
101
J
B AD03
2404J
AD04
STAIR NO.1 LOBBY
2404J
1000
PLAN NORTH
PARTIAL FLOOR & CEILING PLAN LEVEL 2 - AREA A &B SHEET
3
PARTIAL DEMOLITION FLOOR PLAN - LEVEL 2 - AREA A &B 4 SCALE 1/8" = 1'-0"
PARTIAL DEMOLITION CEILING PLAN - LEVEL 2 - AREA A &B SCALE 1/8" = 1'-0"
SS
TITLE
ELEV NO.1
AD01
FLS
DATE
G
AD02
STAIR NO.1
4/25/2019 8:48:16 AM
AD01
CEILING MOUNTED EXIT SIGN
8
35/16" 5/16"
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
PARTIAL CEILING PLAN - LEVEL 2 - AREA A & B
A-112A
2
3
4
5
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
SEAL
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
N
EN . 08 - 3 1 - 1 O F OF CAL I
9
A
R E
R
ST T
IA
C23603
PROJECT C
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD, SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
ISSUED MARK
DATE
DESCRIPTION
B
MANAGEMENT
4/25/2019 8:48:43 AM
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
016279.06 ?00.00.00? LIONAKIS 2015
AGENCY
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
FLS
SS
DATE A
TITLE
(E) LIGHTING (FOR REFERENCE ONLY) SHEET
E2.01
2
3
4
5
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
SEAL
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
N
EN . 08 - 3 1 - 1 O F OF CAL I
9
A
R E
R
ST T
IA
C23603
PROJECT C
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD, SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
ISSUED MARK
DATE
DESCRIPTION
B
MANAGEMENT
4/25/2019 8:48:45 AM
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
016279.06 ?00.00.00? LIONAKIS 2015
AGENCY
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
FLS
SS
DATE A
TITLE
(E) FIRE ALARM (FOR REFERENCE ONLY) SHEET
FA2.01
2
3
4
5
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
SEAL
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
N
EN . 08 - 3 1 - 1 O F OF CAL I
9
A
R E
R
ST T
IA
C23603
PROJECT C
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD, SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
ISSUED MARK
DATE
DESCRIPTION
B
MANAGEMENT
4/25/2019 8:48:46 AM
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
016279.06 ?00.00.00? LIONAKIS 2015
AGENCY
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
FLS
SS
DATE A
TITLE
(E) FIRE SPRINKLER (FOR REFERENCE ONLY) SHEET
FP1
1
2
EQ
3
4
5
EQ
3'-0"
MB1
VISUAL DISPLAY MONITOR, NOT IN CONTRACT, PROVIDING BACKING PER DETAIL
19 A-532
D
6'-0"
2'-4"
2 EQ WI 302
2'-4" VIF
WI 308
WI 308
5'-4"
2'-10"
2'-8"
2 EQ WI 302
WI 302
WI 302
5'-4"
2'-10"
2'-8"
2'-6"
2'-6"
SF1 COUNTERTOP. SEE SHEET AF112A
PL1, SEE SHEET AF112A
1'-8" 2'-10"
2'-10"
1'-8"
SF1 COUNTERTOP, SEE SHEET AF112A
3'-0"
WI 222 1 A-561
C
EQ
WI 302
5'-4"
EQ
2 (EQ) WI 302
WI 302
3'-0"
3'-0"
2'-4"
PL1, SEE SHEET AF112A
WI 222 7 A-561
OPEN KNEE SPACE
2 EQ WI 222
1 A-561
WI 222 7 A-561
OPEN KNEE SPACE
INFILL WALL, SEE DETAIL 3 A-531
PL1, SEE SHEET AF112A
VISUAL DISPLAY MONITOR, NOT IN SCOPE, PROVIDE BACKING PER DETAIL
7 A-531
2'-6"
19 A-532
2'-10"
1'-8"
SF1 COUNTERTOP, SEE SHEET AF112A
OPEN KNEE SPACE
WI 222
WI 222
7 A-561
1 A-561
VISUAL DISPLAY MONITOR, NOT IN CONTRACT, PROVIDE BACKING PER DETAIL
(E) ALUM STOREFRONT SYSTEM, TYP
19 A-532 EQ
EQ
MB2
MB2
3'-0"
3'-0"
B
EQ
EQ
CL
FILE NO: 34-CSUS FIXED FURNITURE, TYP
A
TITLE
SHEET
3
4
PARTITION CONFIGURATION DIAGRAMS (FOURTH CHARACTER DESIGNATOR)
5
PARTITION TYPE SYMBOL KEY
PARTITION TYPE GENERAL NOTES
FIRE RATING
F
G
H
J
CORE MATERIAL
STRUCT ABOVE TYP
2. THE CONSTRUCTION OF EXTERIOR WALLS ARE SHOWN ON WALL SECTIONS & CORRESPONDING DETAILS. PARTITION SYMBOLS ARE ONLY USED TO SHOW INTERIOR CONDITIONS, INCLUDING INTERIOR FURRING OF EXTERIOR WALLS.
CORE SIZE PARTITION CONFIGURATION
CLG TYP
VARIATION
SEE PLAN
PARTITION TO STRUCTURE
PARTITION TO STRUCTURE
SINGLE GYP BD BOTH SIDES TO STRUCTURE
PARTITION TO STRUCTURE
SINGLE GYP BD ONE SIDE TO STRUCTURE
PARTITION TO BOTTOM SIDE OF CEILING
PARTITION 6" ABOVE CEILING
SINGLE GYP BD BOTH SIDES, 6" ABOVE CEILING
SINGLE GYP BD BOTH SIDES TO BOTTOM SIDE OF CEILING
SINGLE GYP BD BOTH SIDES, 6" ABOVE CEILING
PARTITION TO STRUCTURE
PARTITION - PARTIAL HEIGHT SINGLE GYP BD BOTH SIDES TO TOP OF PARTITION
SINGLE GYP BD ONE SIDE 6" ABOVE CEILING
DOUBLE GYP BD BOTH SIDES TO STRUCTURE
SEE ELEVATIONS
PARTITION TO STRUCTURE
PARTITION TO STRUCTURE
DOUBLE GYP BD ONE SIDE TO STRUCTURE
SINGLE GYP BD BOTH SIDES TO STRUCTURE
SINGLE GYP BD ONE SIDE TO STRUCTURE
K
L
M ADJACENT WALL SEE PLAN
P
ADJACENT WALL SEE PLAN
SEE PLAN
SEE PLAN
N
Q
R
S
T
DESIGNATOR 0 1 2 3 4
SECOND CHARACTER
1S4A J 1
FIRE RATING NON-RATED 1 HR 2 HR 3 HR 4 HR
DESIGNATOR C D E F H M S T W Z ---
SEE PLAN
THIRD CHARACTER PARTITION TO STRUCTURE
PARTITION FURRING TO STRUCTURE
PARTITION FURRING TO STRUCTURE
PARTITION FURRING 6" ABOVE CEILING
PARTITION TO STRUCTURE
PARTITION 6" ABOVE CEILING
DOUBLE GYP BD BOTH SIDES TO STRUCTURE
SINGLE GYP BD ONE SIDE TO STRUCTURE
SINGLE GYP BD ONE SIDE 6" ABOVE CEILING
SINGLE GYP BD ONE SIDE 6" ABOVE CEILING
NO GYP BD
NO GYP BD
PARTITION - PARTIAL HEIGHT NO GYP BD
PARTITION TO STRUCTURE
SHAFT LINER ONE SIDE TO STRUCTURE
DOUBLE GYP BD ONE SIDE TO STRUCTURE
SINGLE GYP BD ONE SIDE TO STRUCTURE
SEE ELEVATIONS
DESIGNATOR 1 2 3 4 6 8 10 12
C
7. IN CASES WHERE TWO DIFFERENT CEILING HEIGHTS ABUT PARTITIONS, THE PARTITION SHALL EXTEND ABOVE THE HIGHEST CEILING INDICATED. 8. GYPSUM BOARD SHALL BE FIRE RESISTANT, TYPE 'X' UNO. FIRE RATED PARTITIONS SHALL BE CONSTRUCTED PER CBC, TABLE 720.1(2).
1S4A S J
CORE MATERIAL CONCRETE DETENTION WALL EXISTING FURRING - WOOD STEEL HAT CHANNELS MASONRY STEEL STUD SHAFTWALL STUD WOOD STUD STEEL ZEE CHANNELS --USER DEFINED---USER DEFINED--
9. PROVIDE MOISTURE RESISTANT GYP BOARD AT PARTITIONS IN WET AREAS (FLOOR TO FINISH CEILING) INCLUDING BUT NOT LIMITED TO THE FOLLOWING ROOMS A. B. C. D. E. F. G.
D
F 3/4" 1 1/2" 2 1/2"
2" 4" 6" 8" 10" 12"
FOURTH CHARACTER
10. PROVIDE ACOUSTICAL TREATMENT AT PARTITIONS WITH ACOUSTIC INSULATION. FILL STUD CAVITIES & RUN INSULATION CONTINUOUS AROUND COLUMNS & OTHER OBSTRUCTIONS TO FORM A CONTINUOUS ACOUSTIC BARRIER.
CORE MATERIAL SIZE H M S T 3/4" 1 5/8" 1 1/2" 2 1/2" 2 1/2" 3 5/8" 2 1/2" 4" 4" 5 5/8" 6" 6" 7 5/8" 8" 9 5/8" 10" 11 12" 5/8"
A. INSTALL ACOUSTIC BATT INSULATION, FULL WIDTH, DEPTH, AND HEIGHT.
W
Z 7/8" 1 1/2"
--
-INSTALL ACOUSTICAL SEALANT AT PARTITION HEAD, SILL & JAMB TRANSITIONS, AS WELL AS AT PENETRATIONS THROUGH THE GYPSUM BOARD MEMBRANE INCLUDING PENETRATIONS AT MOUNTING FASTENERS. FIRE STOPPING REQUIREMENTS SHALL SUPERCEDE ACOUSTIC TREATMENT.
3 1/2" 5 1/2" 7 1/4" 9 1/4" 11 1/4"
GYPSUM BOARD SILL & JAMB EDGES TERMINATING AT DISSIMILAR MATERIAL (CMU, CONCRETE, METAL PANEL , ETC) SHALL ALLOW 1/4" CONTINUOUS GAP AND BE SEALED AIRTIGHT WITH AN ACOUSTIC SEALANT. THE BACK AND SIDES OF DUPLEX ELECTRICAL OUTLETS, TELEPHONE OUTLETS, CABLE TV OUTLETS, FIRE ALARM DEVICES, THERMOSTATS, ETC, SHALL BE SEALED WITH FIRE STOP PUTTY PADS AS SPECIFIED FOR FIRE RATED ASSEMBLIES. ELSEWHERE, BACK-TO-BACK OUTLET BOXES TO BE SEPARATED BY ONE EMPTY STUD SPACE AND A MINIMUM OF 16 INCHES.
1S4A A J
SEE PARTITION CONFIGURATION DIAGRAMS AT LEFT
DECRIPTION
RESILIENT CHANNEL W/ ISOLATION CLIPS W/ SINGLE GYP BD ONE SIDE TO CEILING
RESILIENT CHANNEL W/ ISOLATION CLIPS W/ SINGLE GYP BD ONE SIDE TO CEILING
DECRIPTION
DECRIPTION
DECRIPTION DECRIPTION
DECRIPTION
D EF IN ED
D EF IN ED
D EF IN ED
DECRIPTION
U SE R
U SE R
DECRIPTION
Z
DECRIPTION
DECRIPTION DECRIPTION DECRIPTION
VARIATION MATERIAL MOISTURE RESISTANT GYP BD CEMENTITIOUS BACKER BD GYP BD, ADDITIONAL LAYER REMOVE GYP BD SOUND DAMPENING GYP BD HI-IMPACT GYP BD PLYWOOD LEAD BACKED GYP BD LAMINATED HI-IMPACT GYP BD RIGID INSULATION BULLET RESISTANT COMPOSITE PANELS WITHOUT ACOUSTIC INSULATION PARTITION SMOKE FIRE --USER DEFINED---USER DEFINED---USER DEFINED---USER DEFINED--
12. PENETRATIONS THROUGH RATED PARTITIONS SHALL BE SEALED WITH UL LISTED FIRE/SMOKE STOP ASSEMBLY.
VARIATION
0S3A 0S3A 0S3A 1S3A
UL ASSEMBLY
U V
STC RATING 0 50 50 40
HEAD
SILL
20/A-531 19/A-533 19/A-533 SIM 3/A-531
20/A-531 19/A-533 19/A-533 SIM 4/A-531
T
R E
EN . 08 - 3 1 - 1 O F OF CAL I
13. SEE PARTITION PRIORITY LEGEND FOR PRIORITIZATION OF INTERSECTING PARTITIONS.
PROJECT
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD, SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
PARTITION TYPE SCHEDULE PARTITION TYPE
C23603
A
GYP BD ON ONE SIDE ON STRUCTURE
Y
11. PARTITIONS INDICATED AS FIRE OR SMOKE RATED FORM A SEPARATION THAT SHALL BE CONTINUOUS FROM FLOOR TO STRUCTURE ABOVE WITH NO BREAKS AT CONCEALED SPACES, COLUMNS, TRANSITIONS OR OTHER OBSTRUCTIONS.
D A RCH SE I E N A N McM TE H U T A
ST
C
(E) GYP BD ON ONE SIDE ON (E) STRUCTURE
X
U SE R
W
U SE R
V
D EF IN ED
U
DESIGNATOR A B C D E F G H J K L M P S W N Q T U
1S4A J
SEAL
CT Y R RT
FIFTH CHARACTER
TOILET ROOMS JANITOR CLOSETS OUTSIDE AIR SHAFTS MECHANICAL ROOMS DRINKING FOUNTAIN ALCOVES KITCHENS LOCKERS
PROVIDE CEMENTITIOUS BACKER BOARD AT WET AREAS SCHEDULED WITH TILE FINISH.
1S4A 4 J
PARTITION TO STRUCTURE
SHAFT LINER ONE SIDE TO STRUCTURE
SEE PLANS FOR STRUCTURE ABOVE NOTED IN PARTITION CONFIGURATION DIAGRAMS.
5. THE PARTITION TYPE ABOVE OR BELOW ANY OPENING IS TO BE THE SAME AS THAT SCHEDULED FOR EITHER SIDE OF THE OPENING, UNO.
PARTITION SYMBOL DESIGNATORS
ADJACENT WALL SEE PLAN
SEE PLAN
4.
6. DIFFERING PARTITION TYPES SHALL ALIGN SO THAT PARTITION FINISH PLANES CONTINUE UNBROKEN WITHIN AND/OR ACROSS SPACES.
FIRST CHARACTER
D
3. PARTITION TYPES AS NOTED BY THE SYMBOL CONTINUE BETWEEN ROOM/SPACE CORNERS OR ANY INTERSECTING PARTITION.
EXAMPLE GIVEN: REFERS TO A PARTITION THAT IS 1 HOUR, STEEL STUD, 4", FULL HEIGHT TO DECK, GYP BD BOTH SIDES WITH LAMINATED HI-IMPACT GYP BD
1S4A J
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
IA
E
N
D
1. REFER TO THE FLOOR PLANS FOR PARTITION TYPE SYMBOLS. A PARTITION TYPE IS INDICATED BY A SYMBOL CONTAINING THE PARTITION IDENTIFICATION WHICH REFERS TO A SPECIFIC ASSEMBLY INDICATED ON THIS SHEET.
9
C
SIZES
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
STANDARD PARTITION CONFIGURATIONS A B
R
2
LI JO C N
2"
1
PARTITION PRIORITY LEGEND REMARKS DOOR FRAME (AS APPLICABLE)
ISSUED MARK
DATE
DESCRIPTION
LOWER PRIORITY PARTITION
SLOTTED TRACK, USE NONSLOTTED TRACK AT SUSPENDED SOFFITS/ CLG SUPPORTS
(E) FLOOR JOIST
PATCH AND REPAIR CEILING WITH 5/8" TYPE 'X' GYP BD AS REQUIRED
PATCH AND REPAIR CEILING WITH 5/8" TYPE 'X' GYP BD AS REQUIRED
EXISTING MTL CHANNEL
5/8" PLYWOOD W/#10 SMS SCREWS @16" OC TO (E) HAT CHANNELS
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
WALL PERPENDICULAR TO RATING NO: 1 HOUR RATED METAL STUD FRAMED WALL ASSEMBLY PER 2016 CBC TABLE 721.1(2) ITEM NO: 13-1.1
HILTI FS-ONE 2- #10 x 1" SCREWS @ 16" OC INTO PLYWOOD
EXISTING MTL CHANNEL
HILTI FS-ONE (BOTH SIDES)
2- #10 x 1" SCREWS @ 16" OC INTO PLYWOOD
3 5/8" MT STUD @ 24" OC W/ 5/8" TYPE "X" GYP BD ON BOTH JOISTS SIDES UNO
(E) FLOOR JOIST
PATCH AND REPAIR CEILING WITH 5/8" TYPE 'X' GYP BD AS REQ'D
5/8" CONT PLYWOOD STRIP, MATCH STUD WITDTH W/ (2) #12 SMS SCREWS @ 16" OC TO (E) HAT CHANNELS
B
3 5/8" MT STUD @ 24" OC W/ 5/8" TYPE "X" GYP BD ON BOTH SIDES UNO
5/8' PLYWOOD W/#10 SMS SCREWS @16" OC TO (E) HAT CHANNELS
SLOTTED TRACK, USE NONSLOTTED TRACK AT SUSPENDED SOFFITS/CLG SUPPORTS 2- #10 x 1" SCREWS @ 16" OC INTO (E) MTL CHANNEL
SLOTTED TRACK, USE NONSLOTTED TRACK AT SUSPENDED SOFFITS/ CLG SUPPORTS
WALL PARALLEL TO JOISTS
SEALANT (BOTH SIDES) 2- #10 x 1" SCREWS @ 16" OC INTO PLYWOOD 3 5/8" MT STUD @ 24" OC W/ 5/8" GYP BD ON BOTH SIDES UNO
HIGHER PRIORITY PARTITION
PATCH AND REPAIR CEILING WITH 5/8" TYPE 'X' GYP BD AS REQ'D
5/8" CONT PLYWOOD STRIP, MATCH STUD WITDTH W/ (2) #12 SMS SCREWS @ 16" OC TO (E) HAT CHANNELS 2- #10 x 1" SCREWS @ 16" OC INTO PLYWOOD 3 5/8" MT STUD @ 24" OC W/ 5/8" GYP BD ON BOTH SIDES UNO
WALL PERPENDICULAR TO JOISTS
NOTE: AT WALL PARALLEL TO JOIST CONDITION, CONTRACTOR OPTION TO OMIT PLYWOOD AND ATTACH TRACK TO (E) HAT CHANNELS
HIGHER PRIORITY PARTITION
HIGHER PRIORITY PARTITION
LOWER PRIORITY PARTITION
SEALANT (BOTH SIDES)
PARTITION PRIORITY LEGEND
SLOTTED TRACK, USE NONSLOTTED TRACK AT SUSPENDED SOFFITS/CLG SUPPORTS 2- #10 x 1" SCREWS @ 16" OC INTO (E) MTL CHANNEL
FOUR HOUR FIRE AND/OR SMOKE PARTITION THREE HOUR FIRE AND/OR SMOKE PARTITION TWO HOUR FIRE AND/OR SMOKE PARTITION TWO HOUR FIRE PARTITION TWO HOUR SHAFTWALL ONE HOUR FIRE AND/OR SMOKE PARTITION ONE HOUR FIRE PARTITION NON-RATED PARTITION
WALL PARALLEL TO JOISTS
PRIORITY 1 (HIGHEST) PRIORITY 2 PRIORITY 3 PRIORITY 4
MANAGEMENT
PRIORITY 5 PRIORITY 6 PRIORITY 7 (LOWEST)
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
NOTE: 1. ALL PARTITIONS MAY NOT BE USED, SEE PLANS. 2. PARTITIONS WITH HIGHER ASSIGNED PRIORITY SHALL BE CONTINUOUS THROUGH INTERSECTIONS.
NOTE: AT WALL PARALLEL TO JOIST CONDITION, CONTRACTOR OPTION TO OMIT PLYWOOD AND ATTACH TRACK TO (E) HAT CHANNELS
AGENCY
RATING NO: 1 HOUR RATED METAL STUD FRAMED WALL ASSEMBLY PER 2016 CBC TABLE 721.1(2) ITEM NO: 13-1.1
3
1-HR RATED MTL STUD WALL @ (E) CEILING 1 1/2" = 1'-0"
Q1
11
UNDERSIDE OF FLOOR
MTL STUD WALL @ (E) CEILING 1 1/2" = 1'-0" Q1
ACOUSTICAL SEALANT , EACH SIDE
SEE
11 A-531
&
12 A-531
5/8" TYPE "X" GYP BD 3 5/8" MT. STUD @ 24" O.C.
3 5/8" MT STUD @ 24" OC
2- #10 x 1 1/2" SCREWS @ 24" O.C. INTO EXISTING SUBFLOOR BASE SEE FINISH SCHEDULE
2- #10 x 1 1/2" SCREWS @ 24" OC INTO EXISTING SUBFLOOR
FOR ATTACHMENT TO STRUCTURE
5/8" TYPE "X" GYP. BD.
HILTI FS-ONE
(E) FLOOR)
LATERAL BRACING
HILTI FS-ONE
5/8" GYP BD
RATING NO: 1 HOUR RATED METAL STUD FRAMED WALL ASSEMBLY PER 2016 CBC TABLE 721.1(2) ITEM NO: 13-1.1
3 5/8" MT. STUD @ 24" O.C.
3 5/8" MT STUD @ 24" OC
2- #10 x 1 1/2" SCREWS @ 24" O.C. INTO EXISTING SUBFLOOR
2- #10 x 1 1/2" SCREWS @ 24" OC INTO EXISTING SUBFLOOR
14
FILE NO: 34-CSUS
A-532
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
5/8" GYP. BD.
(E) FLOOR)
WALL PERPENDICULAR TO JOISTS
A
BASE SEE FINISH SCHEDULE
WALL PARALLEL TO JOISTS
AC SEE REFLECTED CEILING PLAN FOR CEILING TYP AND HEIGHTS
RATING NO: 1 HOUR RATED METAL STUD FRAMED WALL ASSEMBLY PER 2016 CBC TABLE 721.1(2) ITEM NO: 13-1.1
FLS
DATE
TITLE
PARTITION TYPES & SCHEDULE
LATERAL BRACING WALL FINISH SEE SCHEDULE METAL STUDS SEE SCHEDULE BASE SEE FINISH SCHEDULE ACOUSTICAL SEALANT , EACH SIDE
4/25/2019 8:48:23 AM
016279.06 ?00.00.00? LIONAKIS 2015
WALL PERPENDICULAR TO JOISTS
7
1-HR MTL STUD @ (E) FLOOR FRAMING
12
1 1/2" = 1'-0" Q1
WALL PARALLEL TO JOISTS
SHEET
METAL STUD WALL @ (E) FLOOR FRAMING 1 1/2" = 1'-0"
Q1
20
FULL HEIGHT WALL 1:6
AE_A_0550_004 Q1
A-531
SS
2
3
4
5 TYPE 1 BACKING PLATE SHALL BE USED FOR ANCHORAGE OF THE FOLLOWING:
" 1/8 X MA
THREE #10 LOW PROFILE PAN HEAD SMS AT EACH STUD, TYP.
GAS CYLINDER BRACKETS SINKS
WINDOW GLAZING CUT AND BEND TRACK WEB TO FORM 2" RETURN. ATTACH RETURN TO JAMB STUD W/ 3 # 10 SMS TYP. T&B
INTERIOR NON-BEARING PARTITIONS MAXIMUM HEIGHT FOR METAL STUDS BASED ON SSMA NON-COMPOSITE VALUES BASED ON 24" STUD SPACING AND L/240 DEFLECTION DEPTH GAUGE FLANGE WIDTH Fy (KSI): STUD MAX.HEIGHT DESIGNATION 3 5/8" 25 1 1/4" 33 362S125-18 9'-11" (*) 3 5/8" 20 13'-6" 1 1/4" 33 362S125-30 18 15'-3"" 1 1/4" 33 362S125-43 3 5/8" 3 5/8" 16 1 1/4" 50 362S125-54 16'-3" 14 17'-5" 1 1/4" 50 362S125-68 3 5/8" 4" 1 1/4" 33 400S125-18 25 10'-5" (*) 4" 20 1 1/4" 33 400S125-30 14'-7" 4" 18 16'-5" 1 1/4" 33 400S125-43 1 1/4" 50 400S125-54 4" 16 17'-7" 14 1 1/4" 50 400S125-68 18'-10" 4" 6" 20 18'-11" 1 1/4" 33 600S125-30 6" 18 22'-10" 1 1/4" 33 600S125-43 6" 16 1 1/4" 50 600S125-54 24'-5" 6" 14 26'-2" 1 1/4" 50 600S125-68 1 1/4" 33 800S125-43 8" 18 28'-8" 8" 16 1 1/4" 50 800S125-54 30'-9" 8" 14 33'-4" 1 1/4" 50 800S125-68 (*) - REQUIRES WEB STIFFENERS AT EACH END OF STUD 1. STUD SHALL BE DEPTH AS INDICATED ON WALL SCHEDULE AND GAUGE AS DETERMINED BY HEIGHT OF WALL AND THE SCHEDULE ABOVE 3 2. FOR TYPICAL WALL FRAMING CONDITIONS, SEE ELEVATION A-532 20 3. AT CONTRACTOR OPTION WALL STUDS MAY BE REPLACED WITH TRACKLOC STUDS COMPLYING WITH A-532
3/8" = 1'-0"
AE_A_0550_008 Q1
SHOWER SEAT
A-532
A-532
ALUM. CORNER TRIM FINISH TO MATCH WINDOW SYSTEM (BOTH SIDES OF WALL)
1 1/4"
DBL STUD
DBL STUD
14 GAGE X 6" RUNNER TRACK NOTCHED AROUND STUDS AND EXTENDING 3" BEYOND ONE PAIR OF STUDS SPACED 16" O.C. MAX
SEALANT 4 - #10 SMS EA. SIDE BOX HDR
EMSEAL QUIET JOINT.
TYPE 1
PROVIDE EMSEAL QUIET JOINT. ON BOTH SIDES AT RM 2206A LAB - VOICE / ENDOSCOPY
#10 SMS @ 12"CC
STUD AND TRACK TO MATCH SIZE AND GAUGE OF STUD WALL
STUD AND TRACK TO MATCH SIZE #10 SMS @ AND GAUGE OF STUD WALL 12" C.C.
INT. NON-BEARING PARTITION FRAMING SCHEDULE
5
9
AE_A_0550_008 Q1
3" = 1'-0"
CUT AND BEND TRACK WEB TO FORM 2" RETURN. ATTACH RETURN TO JAMB STUD W/ 3 - # 10 SMS TYP. T&B
INT. NON-BEARING PARTITION FRAMING SCHEDULE AE_A_0550_008 Q1
3" = 1'-0"
CUT AND BEND TRACK WEB TO FORM 2" RETURN. ATTACH RETURN TO JAMB STUD W/ 3 - # 10 SMS TYP. T&B
13
3" = 1'-0"
BASE CABINETS 16 GA. METAL STUD FRAMING, TYP.
WALL MOUNTED CABINETS 16 GAGE X 6" RUNNER TRACK NOTCHED AROUND STUDS AND EXTENDING 3" BEYOND ONE PAIR OF STUDS SPACED 16" O.C. MAX
DBL STUD
8'-0"
A-532 15
TRIPLE STUD
12'-0"
A-532
9
3 TRACKS & STUD
A-532 11
3 TRACKS & STUD
CLIP L 18ga x 1 1/2" x 1 1/2" x 0'-3" EA END OF BLK W/ 2-#10 SMS EA LEG
A-532
SEE PLANS AND / OR SECTIONS FOR SIZE AND SPACING OF STUDS
TYPE 2
A-532
TRACK & STUD
CUT AND BEND TRACK WEB TO FORM 2" RETURN. ATTACH RETURN TO JAMB STUD W/ 3 - # 10 SMS TYP. T&B
A-532
CUT AND BEND TRACK WEB TO FORM 2" RETURN. ATTACH RETURN TO JAMB STUD W/ 3 - # 10 SMS TYP. T&B
#10 SMS @ 12" C.C.
INT. NON-BEARING PARTITION FRAMING SCHEDULE AE_A_0550_008 Q1
3/8" = 1'-0"
LIGHT GAUGE STUDS, SEE ELEVATION FOR SIZE AND SPACING
INT. NON-BEARING PARTITION FRAMING SCHEDULE
6
10
AE_A_0550_008 Q1
3" = 1'-0"
ALLOWABLE LOADS ON BACKING
VERTICAL
LATERAL
220 LBS
200 LBS
2 - # 10 SMS
A-532
10
LOCKERS
INT. NON-BEARING PARTITION FRAMING SCHEDULE AE_A_0550_008 Q1
3" = 1'-0"
MTL. STUD TRACK BLKG AT EA. END OF WALL AND 8'-0" C.C. TYP.
SPLICE STRAP AT BLKG AS REQUIRED 4 - #10 SMS AT STRAP TO BLKG AND #10 SMS STRAP TO EA. STUD STRAP BRIDGING FOR ANY SIZE STUD
14
T
SHALL BE USED FOR ANCHORAGE OF THE FOLLOWING:
BUMPER GUARDS DOOR STOPS 20 GA. METAL STUD FRAMING, TYP.
20 GAGE X 6" RUNNER TRACK NOTCHED AROUND STUDS AND EXTENDING 3" BEYOND ONE PAIR OF STUDS SPACED 16" O.C. MAX BACKING
COLD ROLLED CHANNEL BRIDGING FOR 4" OR SMALLER STUDS ONLY
INT. NON-BEARING PARTITION FRAMING SCHEDULE AE_A_0550_008 Q1
TYPE 3
R E
TYPE 3 BACKING PLATE
THREE #10 LOW PROFILE PAN HEAD SMS AT EACH STUD, TYP.
" 1/8 X MA
CLIP L 1 1/2" x 1 1/2" x 18ga FULL WIDTH OF STUD TYP 2 - # 10 SMS TO STUD (CONTRACTOR OPTION TO USE "SIMPSON" SUBH W/ 1-#10 SCREW TO CHANNEL)
3" = 1'-0"
D A RCH SE I E N A N McM TE H U T A
C23603
COLD ROLLED CHANNEL 1 1/2" x 18 ga CONT. BRIDGING
A-532
ELECTRICAL PANELS
6" X 16 GA. PLATE
3"
LIGHT GAUGE STUDS, SEE ELEVATION FOR SIZE AND SPACING
2
BACKING
6 TRACK
TOILET COUNTERTOPS
SEAL
6 TRACK
TOILET PARTITIONS
MTL. STUD
1 1/2" x 20ga STRAP CONT
SILLS
A-532
FULL HEIGHT CABINETS
CT Y R RT
15
TRACK & STUD
SHALL BE USED FOR ANCHORAGE OF THE FOLLOWING:
A
A-532
200 LBS
ST
DBL STUD
4'-0"
220 LBS
GUARDRAILS
AE_A_0550_008 Q1
STUD AND TRACK TO MATCH SIZE AND GAUGE OF STUD WALL
INTERIOR WALL OPENING FRAMING SCHEDULE
C
LATERAL
HANDRAILS
INT. NON-BEARING PARTITION FRAMING SCHEDULE
DBL. STUD
TRACK TO MATCH SIZE AND GAUGE OF STUD WALL
5
VERTICAL
TYPE 2 BACKING PLATE THREE #10 LOW PROFILE PAN HEAD SMS AT EACH STUD, TYP.
" 1/8 X MA
15
DBL. STUD
15
ALLOWABLE LOADS ON BACKING
6" X 14 GA. STUD
3"
CUT AND BEND TRACK WEB TO FORM 2" RETURN. ATTACH RETURN TO JAMB STUD W/ 3 - # 10 SMS TYP.
A-532
HEADERS
20 A-533
(E) WINDOW MULLION
15
JAMBS
NOTE: FOR ANY BACKING TO BE LOCATED ONTO SOUND ISOLATION CLIP WALLS, SEE DETAIL
BACKING
NOTE: 1. BRIDGING FOR 4" AND SMALLER STUDS MAY BE CONSTRUCTED OF COLD ROLLED CHANNEL OR STRAPS AT CONTRACTOR'S OPTION UNLESS OTHERWISE NOTED.
'W' WIDTH MAX
GRAB BARS
DOOR HOLDERS
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD, SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819 ALLOWABLE LOADS ON BACKING
VERTICAL 6" X 20 GA. STUD
IA
1
15
16 GA. METAL STUD FRAMING, TYP.
N
INT. NON-BEARING PARTITION FRAMING SCHEDULE
SEE PLAN FOR WALL TYPE
9
D
URINALS DRESSING BENCH
LIGHT GAUGE STUDS, SEE ELEVATION FOR SIZE AND SPACING
15
LIGHT GAUGE STUDS, SEE ELEVATION FOR SIZE AND SPACING
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
R
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
3"
LI JO C N
2"
1
LATERAL
90 LBS
75 LBS ISSUED
TOP TRACK TO MATCH STUD DEPTH AND GAUGE
BRIDGING @ 4'-0" OC MAX (OMIT WHERE GYP OCCURS BOTH SIDES, 14 SEE A-532
REFER TO 11 / A-531 FOR ATTACHMENT TO STRUCTURE
LIGHT GAUGE STUDS, SEE ELEVATION FOR SIZE AND SPACING
ALTERNATE DOUBLE STUD ATTACHMENT AT INTERIOR STUDS IN LIEU OF WELDING PL 1" x 3" x 18ga @ 30" CC W/ #10 SMS TO EA STUD
15
TYPE 4 BACKING PLATE
20 GAGE X 6" HIGH CONTINUOUS METAL PLATE
A-532 TRIPLE STUD
HEADER
2
5
A-532
A-532
'W' 12'-0" MAX OPENING
CORNER 16
TEE 'W' 12'-0" MAX DOOR OPENING
A-532
B
MAXIMUM HEIGHT SEE SCHEDULE
HEADER, SILL & JAMBS SEE
4 A-532
SPLICE TOP AND BOTTOM TRACK W/ SAME GAUGE TRACK x 2'-0" LONG W/ 6 - #10 SCREWS EA. END TYP. ( CENTER SPLICE PIECE ON SPLICE)
TWO #8 LOW PROFILE PAN HEAD SMS AT EACH STUD, TYP.
4 - #10 SMS EA. SIDE BOX HDR
TOILET AND BATH ACCESSORIES
BULLETIN BOARDS TACK BOARDS
20 GA. METAL STUD FRAMING, TYP.
EXAM LIGHTS DIRECTORIES
1/8"
1-24
CHART RACKS
TYP. EA. SIDE
CHAIR RAIL
FIRE EXTINGUISHER CABINETS
STUD SECTIONS TO BE 600S125-30, #10 SMS @ TRACK TO MATCH SIZE AND GAUGE 12" C.C. OF STUD WALL
NOTE: ALL STUDS AND TRACKS SHALL BE 1 DEPTH AS INDICATED ON WALL SCHEDULE AND GAUGE AS DETERMINED AS BY THE A-532 HEIGHT OF THE WALL AND SCHEDULE
A-532 DBL. STUDS
INT. NON-BEARING PARTITION FRAMING SCHEDULE 1/2" = 1'-0"
11
AE_A_0550_008 Q1
CUT AND BEND TRACK WEB TO FORM 2" RETURN. ATTACH RETURN TO JAMB STUD W/ 3 - # 10 SMS TYP. T&B
INT. NON-BEARING PARTITION FRAMING SCHEDULE AE_A_0550_008 Q1
3" = 1'-0"
TYPE 4 DOUBLE STUD
15
ALLOWABLE LOADS ON BACKING
VERTICAL
LATERAL
6" X 20 GA. PLATE
TRIPLE STUD
15 LBS
AE_A_0550_008 Q1
3" = 1'-0"
19
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
016279.06 ?00.00.00? LIONAKIS 2015
10 LBS AGENCY
INT. NON-BEARING PARTITION FRAMING SCHEDULE
INT. NON-BEARING PARTITION FRAMING SCHEDULE
MANAGEMENT
AE_A_0550_008 Q1
3" = 1'-0"
1/2" GAP
14 ga VERTICAL MOVEMENT TRACK
TRACK
STUD TRACK WALL WIDTH +2" FULL HT. 5/8" MAX DRYWALL WHERE OCCURS
#10 SMS @ 12" C.C. TYP.
#10 SMS @ 12" C.C. TYP. 5/8" MAX DRYWALL WHERE OCCURS
TYP. STUD SEE PLAN STUD ENDS TO BEAR ON TRACK WEB, TYP.
STUD OR TRACK
TYP. TRACK
TYP. TRACK
3"
STANDARD
STUD .
INT. NON-BEARING PARTITION FRAMING SCHEDULE AE_A_0550_008 Q1
8
INT. NON-BEARING PARTITION FRAMING SCHEDULE 1" = 1'-0"
AE_A_0550_008 Q1
12
INT. NON-BEARING PARTITION FRAMING SCHEDULE 6" = 1'-0"
ATTACH FINISHES TO TLA AT CENTER OF SLOT IN TLA
NOTE: SEE PLANS AND SECTIONS FOR STUD AND TRACK SIZES
ATTACHMENT PER ALTERNATE
AE_A_0550_008 Q1
12 A-531
"TLA" TRAKLOC STUD ASSEMBLY SCREW STUD TO TRACK WHERE REQ PER NOTE 2
NOTES: 1. TRAKLOC STUD/TRACK ASSEMBLY SHALL COMPLY W/ ICC ESR-1464. 2. PROVIDE SCREW FROM TRACK TO EA STUD FLANGE AT THESE LOCATIONS: A. FIRST & LAST STUDS OF A WALL SEGMENT B. EA JAMB STUD AT OPENINGS C. STUDS SUPPORTING HUNG CASEWORK OR COUNTERTOP BRACKETS. 3. THIS ASSEMBLY IS NOT TO BE USED AT SOFFITS OR HANGING STUDS.
16
INT. NON-BEARING PARTITION FRAMING SCHEDULE 3" = 1'-0"
AE_A_0550_008 Q1
20
INT. NON-BEARING PARTITION FRAMING SCHEDULE
3" = 1'-0"
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
FLS
SS
DATE
TITLE
STANDARD METAL STUD DETAILS & SCHEDULES
SUPPORTING STRUCTURE
NOTE: SEE OTHER DETAILS ON THIS SHEET FOR ATTACHMENTS OF TRACK TO STRUCTURE NOTE: CONTRACTOR OPTION TO UTILIZE SLOTTED TRACK IN LIEU OF NESTED TRACK. SLOTTED TRACK TO BE 20 GA MIN W/ 2 1/2" LEGS W/ 1/4" x 1 1/2" VERT SLOTS @ 1" OC AT EA LEG
NOTE: SEE PLANS AND SECTIONS FOR STUD AND TRACK SIZES
11 A-531
FINISHES WHERE OCCURS
1 - #10 SMS EA. SIDE, TYP. TOP OR BOTTOM TRACK, HEADER OR SILL
DEEP LEG TRACK
ALTERNATE
3" = 1'-0"
5/8" MAX DRYWALL ATTACHMENT PER WHERE OCCURS
#10 SMS @ 12" C.C. TYP. 3 STUDS TYP.
# 10 SMS Ea. SIDE 3"
4
2"
TRACK STANDARD
A
2"
NO ATTACHMENT OF FINISHES TO TOP TRACK
AGENCY REPORT
#10 SMS @ 12" C.C. TYP.
5/8" MAX DRYWALL WHERE OCCURS
SCREW STUD TO TRACK WHERE REQ PER NOTE
MIN OVERLAP PER EVALUATION
TYP. STUD
SLOT IN TLD, TYP
SUPPORTING STRUCTURE
3/4" CLR
1
TOP OF STUD
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
SHALL BE USED FOR ANCHORAGE OF THE FOLLOWING:
FIRST AID CABINETS/AED DEVICES
15
TRACK
4/25/2019 8:48:27 AM
DESCRIPTION ASI DESCRIPTION
MIRRORS
BACKING
3
DATE MM/DD/YYYY
TELEPHONES
9" MAX @ ENDS FOR FASTENERS
BOTTOM TRACK TO MATCH STUD DEPTH AND GAUGE
MARK ASI-001
AE_A_0550_008 Q1
SHEET
A-532
2
3
4
5
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
SEAL
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
N
EN . 08 - 3 1 - 1 O F OF CAL I
9
A
R E
R
ST T
IA
C23603
PROJECT C
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD, SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
ISSUED
SOUND ISOLATION CLIPS W/ 7/8" HAT CHANNELS
6" MAX
ACOUSTICAL INSULATION
DATE
DESCRIPTION
FROM CEILING
MARK
UNDERSIDE OF (E) FLOOR JOIST (E) 5/8" GYP BD
MIN (2) #10 SDST FASTENERS PER CLIP
14
LATERAL BRACING
ACOUSTICAL SEALANT , EACH SIDE
SEE
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
11 A-531
12 A-531 MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
016279.06 ?00.00.00? LIONAKIS 2015
AGENCY
19
(E) MTL STUD WALL SECTION W/ ISOLATION CLIPS 3" = 1'-0"
?DRS TRACKING NUMBER? ?YYMMDD?. Q1
WALL, SEE FLOOR PLAN FOR TYPE TYPE 4 BACKING, SEE DETAIL
SOUND ISOLATION CLIPS W/ 7/8" HAT CHANNELS
19 A-532
MIN #10 SDST FASTENER AT EACH CLIP
#12 MIN SDST FASTENERS, 24" OC MAX WITH MFR PROVIDED BRACKETS
FILE NO: 34-CSUS
ACOUSTICAL INSULATION
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
(E) 5/8" GYP BD
9"H X 3/4" X 6' 16GA BACKING
AC
MARKERBOARD A
5/8" GYP BD
STANDARD METAL STUD DETAILS
NOTE: WHERE BACKING IS REQUIRED AT SOUND ISOLATION CLIPS, BACKING IS TO BE ONLY ATTACHED INTO THE HAT CHANNEL AND NOT INTO METAL STUD FRAMING
(E) MTL STUD WALL SECTION W/ ISOLATION CLIPS 3" = 1'-0"
SS
TITLE
TRAY
1
FLS
DATE
#12 MIN SDST FASTENERS, 12" OC MAX WITH MFR PROVIDED BRACKETS 4/25/2019 8:48:28 AM
3" MAX
BASE SEE FINISH SCHEDULE FINISH FLOOR, SEE FLOOR SCHED
FOR ATTACHMENT TO STRUCTURE
FROM FINISH FLOOR
5/8" GYP BD B
24" OC MAX
A-532
?DRS TRACKING NUMBER? ?YYMMDD?. Q1
20
(E) MTL STUD WALL W/ ISOLATION CLIPS AND BACKING 3" = 1'-0"
?DRS TRACKING NUMBER? ?YYMMDD?. Q1
SHEET
A-533
2
3
4
5
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
DOOR SCHEDULE DOOR NO
LOCATION
FIRE RATING (MINS)
2204 2601 2602 2603 2604
COMPUTER LAB AUDIOLOGY LAB AUDIOLOGY LAB AUDIOLOGY LAB CLASSROOM
45 0 0 0 45
DOORS HDW GP (none) 7 7 7 (none)
TYPE
WIDTH
DV2 DV2 DV2
3'-0" 3'-0" 3'-0"
LEAF 2 TYPE WIDTH
DOOR SCHEDULE GENERAL NOTES
FRAMES MATL
HEIGHT FINISH
GL
TYPE
MATL
FINISH
GL
HEAD
JAMB
SILL
GL GL GL
FB1 FB1 FB1
HM HM HM
PT PT PT
----
14/A-541 14/A-541 14/A-541
11/A-541 11/A-541 11/A-541
STC
SECURITY
KEYING ACCESS
1. 2.
COMMENTS EXISTING RATED DOOR TO REMAIN
WD WD WD
7'-0" 7'-0" 7'-0"
ST ST ST
15/A-541 15/A-541 15/A-541
3.
45 45 45
4. EXISTING RATED DOOR TO REMAIN
5.
6.
D
7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
GENERAL DOOR SHEET NOTES ARE TYPICAL UNLESS NOTED OTHERWISE. FLOORS OR LANDINGS ON EACH SIDE OF EXIT DOORS SHALL NOT EXCEED ½” FROM THE TOP OF THE DOOR THRESHOLD TO THE FLOOR OR LANDING SURFACE ON EITHER SIDE OF THE DOOR ASSEMBLY. EXITS AND EXIT ACCESS DOORS SHALL BE MARKED BY AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY DIRECTION OF TRAVEL. THE FORCE FOR PUSHING OR PULLING OPEN INTERIOR SWINGING EGRESS DOORS, OTHER THAN FIRE DOORS, SHALL NOT EXCEED 5 POUNDS. FOR OTHER SWINGING DOORS, AS WELL AS SLIDING AND FOLDING DOORS, THE DOOR LATCH SHALL RELEASE WHEN SUBJECTED TO A 15 POUND MAXIMUM FORCE LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED AND WHICH ARE IN THE PATH OF TRAVEL SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE HARDWARE, PANIC BARS, PUSH-PULL ACTIVATING BARS OR OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP, PINCH OR TWIST THE OPENING HARDWARE THE BOTTOM 10” OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING DOORS SHALL HAVE A SMOOTH UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. WHERE NARROW FRAME DOORS ARE USED, A 10” HIGH SMOOTH PANEL SHALL BE INSTALLED ON THE PUSH SIDE OF THE DOOR, WHICH WILL ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. RATED DOORS SHALL BE POSITIVE LATCHING AND SELF CLOSING. FIRE RATED DOORS AND GLASS SHALL HAVE AN APPROVED LABEL OR LISTING MARK INDICATING THE FIRE PROTECTION RATING WHICH IS PERMANENTLY AFFIXED AT THE FACTORY WHERE FABRICATION AND ASSEMBLY OCCUR. DOOR AND FRAME ASSEMBLY DIMENSIONS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION AND INSTALLATION. COORDINATE OVERALL DOOR FRAME DEPTHS WITH WALL TYPES. FOR DOOR HARDWARE GROUPS, SEE PROJECT SPECIFICATIONS. FOR SIGNAGE LOCATIONS, SEE SIGNAGE PLANS. FOR SIGNAGE ON OR ADJACENT TO DOORS, SEE SHEET SERIES G-100. GLASS DOORS, SIDELIGHTS, AND GLAZED OPENINGS WITHIN 18” OF THE FLOOR OR WITHIN 24” HORIZONTALLY OF ANY DOOR OPENING SHALL BE FULLY TEMPERED GLASS APPROVED FOR IMPACT HAZARD. PROVIDE RATED GLASS AT RATED DOORS AND FRAMES WITH LITES. SEE DOOR SCHEDULE AND PROJECT SPECIFICATIONS. COORDINATE THE SIZE AND LOCATION OF RECESSES IN CONCRETE FLOORS FOR RECESSED DOOR HARDWARE. SEE SECURITY DRAWINGS FOR DOORS WITH CARD READERS AND OTHER SECURITY ELECTRONICS, COORDINATE WITH ELECTRICAL. HOLLOW METAL FRAMES IN MASONRY CONSTRUCTION SHALL BE GROUTED FULL.
SEAL
5/8" GYP O/ MTL STUDS SEE WALL TYPES
N
EN . 08 - 3 1 - 1 O F OF CAL I
2"
A
R E
9
ST T
IA
C23603
1/2"
R
DOOR ANCHOR BY MNFR
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
PROJECT
ACOUSTICAL DOOR
FILL FRAME COMPETELY WITH ROCK WOOL INSULATION
C
NEOPRENE SEAL
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
#10 H.W.H. SELF DRILLING SCREW @ 4" OC
SEAL ADJUSTING AREA
7667 FOLSOM BLVD, SACRAMENTO, CA 95826 CLIENT
LEGEND 14
ACOUSTICAL DOOR HEAD 3" = 1'-0"
Q1
(E) = EXISTING ADO = AUTOMATIC DOOR OPERATOR ADC = AUTOMATIC DOOR CLOSER CR = CARD READER EL = ELECTRIC LOCK HDW GP = HARDWARE GROUP HO = HOLD OPEN PH = PANIC HARDWARE V = VINYL STRIPS GLASS LEGEND: GL = GLASS LG = LEADED GLASS RG = RATED GLASS SG = SPANDREL GLASS
MATERIAL ALUM = ALUMINUM DHM = DETENTION HOLLOW METAL HM = HOLLOW METAL SST = STAINLESS STEEL WD = WOOD
FINISH ANOD = ANODIZED FRP = FIBER REINFORCED PLASTIC PLAM = PLASTIC LAMINATE PT = PAINT ST = STAIN
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
ISSUED MARK
DATE
DESCRIPTION
GLASS LEGEND NOTES: 1. SEE SPECS FOR GLASS TYPS NOTED SWING OF DOOR TO OPEN POSITION
5/8" GYP O/ MTL STUDS SEE WALL TYPES
NO. 1/4" - 20 T.H.M.S. ADJUSTING SCREW
1/2"
JAMB OPENING HEIGHT NET DOOR HEIGHT
#10 H.W.H. SELF DRILLING SCREW @ 4" OC
2"
SEAL ADJUSTING AREA
SET THRESHOLD IN GROUT 3"
2
FLOOR/SLA B LINE
FILL FRAME COMPETELY WITH ROCK WOOL INSULATION
Q1
15
MAX
DOOR TYPE D = DOOR S = SLIDER
1/2" x 7 1/2" ANODIZED ALUMINUM THRESHOLD BY SOUND DOOR MFR
DOOR CONFIGURATION F = FLUSH G = GLASS V = VISION L = LOUVER D = DUTCH J = DETENTION S = SLIDER O = OVERHEAD C = COUNTER A = ACCORDION P = STRIP CURTAIN
ACOUSTICAL DOOR SILL 3" = 1'-0"
Q1
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
016279.06 ?00.00.00? LIONAKIS 2015
AGENCY
CONFIGURATION VERSION 1 = VERSION 1 2 = VERSION 2 ETC.
FRAME TYPES
DF1A
VERSION VARIATION A = VARIATION A B = VARIATION B ETC.
FILE NO: 34-CSUS
FRAME TYPE SYMBOL KEY
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
FRAME PROFILE (AT DOOR ONLY) F = DOUBLE RABBET (TYP) R = SINGLE RABBET E = DOUBLE EGRESS C = CASED P = POCKET
A
FRAME CONFIGURATION B = BASIC THREE-SIDED T = TRANSOM G = GLASS LITE V = VISION LITE W = TRANSOM W/ GLASS LITE X = TRANSOM W/ VISION LITE J = DETENTION P = PARTIAL TWO-SIDED Q = FOUR-SIDED CONFIGURATION VERSION 1 = VERSION 1 2 = VERSION 2 ETC.
SEE SCHED SEE SCHED
2"
1'-11"
SEE SCHED
2"
SEE SCHED
2'-1"
SEE SCHED
2"
8"
43" MAX
4/25/2019 8:48:31 AM
ACOUSTICAL DOOR JAMB
DOOR TYPES
SEE SCHED
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
DOOR ANCHOR BY MNFR
3" = 1'-0"
DOOR TYPE SYMBOL KEY
SPONGE NEOPRENE EXTENDS 1/4" BEYOND EDGE OF DOOR ON BOTH SIDES
NEOPRENE SEAL
11
MAX
1/2"
ACOUSTICAL DOOR
MIN
3/4"
1
B
FIN FLR DF1 - WOOD DOOR
DV2 - WOOD DOOR
FIN FLR FB1
FB1M
VERSION VARIATION A = VARIATION A M = VARIATION W/ MULLION R = VARIATION W/ REMOVABLE MULLION ETC.
AC
FLS
SS
DATE
TITLE
DOOR AND WINDOW SCHEDULE & DETAIL SHEET
A-541
2
3
4
5
HANGER WIRE
SLOT END OF TUBE
OPTION 1
1-1/2" x 1-1/2" x 12 GA x 0'-2" CLIP
1-1/2" x 1-1/2" x 12 GA x 0'-2" CLIP
EMT CONDUIT COMPRESSION STRUT, PLACE TIGHT TO CLIP OR STRUCTURE
OPTION 2
EMT COMP STRUT TO (E) WOOD JOISTS
1
AE_A_0550_008 Q1
3" = 1'-0"
5
1 1/2" MAX
15 A-551
COPE FLANGE OR FLATTEN TO ALLOW INSTALLATION OF PANELS
MAIN RUNNER
FIXED SIDE
1 1/2" MAX
CROSS RUNNER
6 MIN
AE_A_0550_010 Q1
3" = 1'-0"
DISTANCE FROM CLG TO STRUCTURE ABOVE
COMPRESSION STRUT SIZE
≤ 8'-0" ≤ 12'-0"
362S125-30 362S162-33
NOTES: 1. DO NOT USE THIS DETAIL WHERE COMPRESSION STRUTS ARE VISIBLE TO BUILDING OCCUPANTS. 2. ALL PRODUCTS SHALL POSSESS DIMENSIONS, SECTION PROPERTIES, AND MATERIALS IN COMPLIANCE WITH THE AISI D100 MANUAL OF COLD-FORMED STEEL DESIGN AND BE MANUFACTURED BY A CURRENT MEMBER OF THE "STEEL STUD MANUFACTURER'S ASSOCIATION" (SSMA). 3. STEEL MEMBERS 18GA OR LIGHTER SHALL BE MANUFACTURED PER ASTM A653 SS, GRADE 33, AND 16 GA OR HEAVIER PER ASTM A653 SS, GRADE 50, CLASS I.
TYP STUD COMPRESSION STRUT
9
15 A-551
FIXED SIDE
AE_A_0550_012 ?YYMMDD?. Q1
1 1/2" = 1'-0"
FOR CEILING CONNECTION, SEE DETAIL
THESE REQUIREMENTS APPLY TO FLAT AND LEVEL CEILING SYSTEMS WHOSE TOTAL WEIGHT (INCLUDING CEILING-MOUNTED AIR TERMINALS, SERVICES, AND LIGHT FIXTURES) DOES NOT EXCEED FOUR (4) PSF.
MAIN RUNNER
15 A-551
(2) #12 SDST SCREWS
TYP HANGER WIRE TO STUD WALL
12 GA VERTICAL HANGER WIRES @ 48" OC MAX EACH WAY
TYPICAL CEILING BRACING 14 ASSEMBLY, SPACE PER A-551 TABLE BELOW
MAX BRACING ASSEMBLY SPACING SDS ≤ 1.15 12'-0" x 12'-0"
1.15 ≤ SDS ≤ 1.73
8'-0" x 12'-0"
SDS ≥ 1.73
8'-0" x 8'-0"
* SDS SHALL BE PER STRUCTURAL DRAWINGS. IF NO STRUCTURAL DRAWINGS ARE INCLUDED, DETERMINE VALUE PER CURRENT BUILDING CODE.
13
TYPICAL CEILING PLAN
MIN
2"
6" MIN
2" MAX
(2) #10 SDST SCREWS
LC 10 45 DEG M DE G M IN AX
AE_A_0550_011 Q1
3" = 1'-0"
DISTANCE FROM CLG TO STRUCTURE ABOVE
COMPRESSION STRUT SIZE
≤ 4'-0" ≤ 8'-0" ≤ 12'-0"
3/4" DIA 1 1/4" DIA 2" DIA
10
TYP EMT COMPRESSION STRUT
STEEL TRACK CONT OVER (2) STUDS MIN W/ (3) #12 SCREWS TO EA STUD (SCREWS TO WOOD STUDS TO HAVE 1 1/2" MIN EMBED)
#10 x 3" LONG SDST SCREW, TYP EA END
CUT FLANGES AND BEND TYP HANGER WIRE SPACING
OR 1/4 THE LENGTH OF THE END RUNNER, WHICHEVER IS GREATER
362S162-54 BLOCKING BTWN TRAPEZE MEMBERS TO SUPPORT PERP BRACING WIRES (2) #12 SCREWS FROM COMPRESSION STRUT TO TRAPEZE CONT TRACK EA END W/ #12 SCREWS TO EA TRAPEZE FLANGE
7.
EXPANSION JOINTS SHALL BE PROVIDED IN THE CEILING AT INTERSECTIONS OF CORRIDORS AND AT JUNCTIONS OF CORRIDORS AND LOBBIES OR OTHER SIMILAR AREAS.
8.
FOR CEILING AREAS EXCEEDING 2,500 SQUARE FEET, A SEISMIC SEPARATION JOINT SHALL BE PROVIDED TO DIVIDE THE CEILING INTO AREAS NOT EXCEEDING 2,500 SQUARE FEET.
9.
11.
12.
MAIN RUNNER
3/4'' CLR TYP
TIGHTEN SCREW TO WEB OF GRID TO PREVENT MOVEMENT
SIM TO TYP CEILING BRACING ASSEMBLY; OMIT (1) BRACE AT OBSTRUCTION
362S162-54
11
SUSPENDED ACOUSTICAL CEILING
FIXED SIDE
AE_A_0550_007 Q1
3/4" = 1'-0"
TRAPEZE FRAMING PER DETAILS
(2) #12 SST SDST SCREWS @ 12" O.C. (MAX 6" FROM ENDS)
15
17.
ALL CEILING FIXTURES, TERMINALS, AND OTHER DEVICES SHALL BE MOUNTED IN A MANNER THAT WILL NOT COMPROMISE CEILING PERFORMANCE.
ALL LIGHT FIXTURES SHALL BE POSITIVELY ATTACHED TO THE CEILING SUSPENSION SYSTEMS BY SCREWS OR APPROVED FASTENERS. A MINIMUM OF TWO ATTACHMENTS ARE REQUIRED AT EACH LIGHT FIXTURE PER ASTM E580, SECTION 5.3.1.
20.
LIGHT FIXTURES WEIGHING LESS THAN OR EQUAL TO 10 LBS SHALL HAVE A MINIMUM OF ONE (1) #12 GAGE SLACK SAFETY WIRE CONNECTED FROM THE FIXTURE HOUSING TO THE STRUCTURE ABOVE.
21.
LIGHT FIXTURES WEIGHING GREATER THAN 10 LBS BUT LESS THAN OR EQUAL TO 56 LBS MAY BE SUPPORTED DIRECTLY ON THE CEILING RUNNERS, BUT THEY SHALL HAVE A MINIMUM OF TWO (2) #12 GAGE SLACK SAFETY WIRES CONNECTED FROM THE FIXTURE HOUSING AT DIAGONAL CORNERS AND ANCHORED TO THE STRUCTURE ABOVE.
22.
LIGHT FIXTURES WEIGHING GREATER THAN 56 LBS SHALL BE INDEPENDENTLY SUPPORTED BY NOT LESS THAN FOUR (4) TAUT #12 GAGE WIRES ATTACHED TO THE HOUSING AND TO THE STRUCTURE ABOVE.
23.
ALL FOUR FOOT BY FOUR FOOT LIGHT FIXTURES MUST HAVE SLACK SAFETY WIRES AT EACH CORNER UNLESS SUPPORTED AS FOR FIXTURES WEIGHING GREATER THAN 56 LBS.
24.
SURFACE-MOUNTED FIXTURES SHALL BE ATTACHED TO THE MAIN RUNNER WITH AT LEAST TWO POSITIVE CLAMPING DEVICES MADE OF MATERIAL WITH A MINIMUM #14 GAGE. ROTATIONAL SPRING CATCHES DO NOT COMPLY. A #12 GAGE SUSPENSION WIRE SHALL BE ATTACHED FROM EACH CLAMPING DEVICE TO THE STRUCTURE ABOVE. PROVIDE ADDITIONAL SUPPORTS WHEN LIGHT FIXTURES ARE EIGHT (8) FEET OR LONGER. MAXIMUM SPACING BETWEEN SUPPORTS SHALL NOT EXCEED EIGHT (8) FEET.
RIGID CONDUIT SHALL NOT BE USED FOR ATTACHMENT OF THE FIXTURES.
27.
ALL FLEXIBLE SPRINKLER HOSE FITTINGS, CEILING-MOUNTED AIR TERMINALS OR OTHER SERVICES SHALL BE POSITIVELY ATTACHED TO THE CEILING SUSPENSION SYSTEMS BY SCREWS OR APPROVED FASTENERS. A MINIMUM OF TWO ATTACHMENTS ARE REQUIRED AT EACH COMPONENT.
28.
FLEXIBLE SPRINKLER HOSE FITTINGS, CEILING-MOUNTED AIR TERMINALS OR OTHER SERVICES WEIGHING LESS THAN OR EQUAL TO 20 POUNDS SHALL HAVE ONE (1) 12 GAGE SLACK SAFETY WIRE ATTACHED FROM THE TERMINAL OR SERVICE TO THE STRUCTURE ABOVE.
29.
FLEXIBLE SPRINKLER HOSE FITTINGS, CEILING-MOUNTED AIR TERMINALS OR OTHER SERVICES WEIGHING MORE THAN 20 POUNDS BUT LESS THAN OR EQUAL TO 56 POUNDS SHALL HAVE TWO (2) #12 GAGE SLACK SAFETY WIRES ATTACHED FROM THE TERMINAL OR SERVICE TO THE STRUCTURE ABOVE.
1 1/2" MAX
2" 1/ M AX
REMOVABLE CLOSURE (WHITE) BRACING WIRE W/ (4) TIGHT TURNS WITHIN FIRST 1 1/2" AS SHOWN
SHADECLOTH- SIZE TO COVER WINDOW COMPLETELY
33.
ALL LIGHTWEIGHT MISCELLANEOUS DEVICES WEIGHING MORE THAN 20 POUNDS SHALL BE SUPPORTED FROM THE STRUCTURE ABOVE BY NOT LESS THAN FOUR (4) TAUT #12 GAGE WIRES ATTACHED FROM THE DEVICE TO THE STRUCTURE ABOVE.
34.
METAL PANELS AND PANELS WEIGHING MORE THAN ONE-HALF (1/2) PSF, OTHER THAN MINERAL FIBER ACOUSTICAL TILE, ARE TO BE POSITIVELY ATTACHED TO THE CEILING SUSPENSION RUNNERS.
HANGER WIRE
BRACING WIRE
4
3" = 1'-0"
AGENCY
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
FLS
TYP SADDLE TIE 3" = 1'-0"
AE_A_0550_006 Q1
20
SUSPENDED CEILING NOTES 12" = 1'-0"
SS
TITLE
SUSPENDED CEILING DETAILS - TYPICAL SHEET
12
016279.06 ?00.00.00? LIONAKIS 2015
DATE
(E) ALUM STOREFRONT SYSTEM
WINDOW SHADE - WALL MOUNTED
DESCRIPTION
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AC
ALL LIGHTWEIGHT MISCELLANEOUS DEVICES, SUCH AS STROBE LIGHTS, OCCUPANCY SENSORS, SPEAKERS, EXIT SIGNS, AND ETC, SHALL BE ATTACHED TO THE CEILING GRID BY SCREWS OR APPROVED FASTENERS. A MINIMUM OF TWO ATTACHMENTS ARE REQUIRED AT EACH COMPONENT. ALL LIGHTWEIGHT MISCELLANEOUS DEVICES WEIGHING MORE THAN 10 POUNDS SHALL HAVE A #12 GAGE SLACK SAFETY WIRE FROM THE DEVICE TO THE STRUCTURE ABOVE.
DATE
MANAGEMENT
FLEXIBLE SPRINKLER HOSE FITTINGS, CEILING-MOUNTED AIR TERMINALS OR OTHER SERVICES WEIGHING MORE THAN 56 POUNDS SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE BY NOT LESS THAN FOUR (4) TAUT #12 GAGE WIRES ATTACHED FROM THE TERMINAL OR SERVICE TO THE STRUCTURE ABOVE.
32.
DOUBLE LOOP AT SUPPORT, TYP
HEMBAR SEALED INSIDE SHADECLOTH
SUPPORT PENDANT-MOUNTED LIGHT FIXTURES DIRECTLY FROM THE STRUCTURE ABOVE WITH HANGER WIRES OR CABLES PASSING THROUGH EACH PENDANT HANGER AS SHOWN ON ELECTRICAL DWGS. IF THE PENDANT-MOUNTED LIGHT FIXTURE IS DIRECTLY AND INDEPENDENTLY BRACED BELOW THE CEILING, IE, AIRCRAFT CABLES TO WALLS, THEN A BRACE ASSEMBLY IS NOT REQUIRED ABOVE THE CEILING. IF THE PENDANT-MOUNTED LIGHT FIXTURE IS NOT DIRECTLY AND INDEPENDENTLY BRACED BELOW THE CEILING, THEN A TYPICAL BRACING ASSEMBLY IS REQUIRED WHERE THE PENDANT HANGER PENETRATES THE CEILING. WHERE THE WEIGHT OF THE FIXTURE IS LESS THAN 20 POUNDS, A COMPRESSION STRUT IS NOT REQUIRED FOR THE BRACING ASSEMBLY.
26.
31.
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
MARK
19.
SUSPENDED CEILING SYSTEM
CLIENT
ISSUED
CEILING PANELS SHALL NOT SUPPORT ANY LIGHT FIXTURES, AIR TERMINALS, OR DEVICES.
30.
SEE CEILING PLAN
7667 FOLSOM BLVD, SACRAMENTO, CA 95826
18.
1/2" DIA DRILLED HOLE, TYP
EN . 08 - 3 1 - 1 O F OF CAL I
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
HANGER WIRES THAT ARE MORE THAN ONE (HORIZONTAL) IN SIX (VERTICAL) OUT OF PLUMB SHALL HAVE COUNTER-SLOPING WIRES. WHERE PERIMETER HANGER WIRES AT MAIN RUNNERS ARE POSITIVELY ATTACHED TO THE PERIMETER CLOSURE ANGLE, COUNTER-SLOPING IS OPTIONAL. SEE ASTM C636 (FIGURE 1) FOR COUNTER-SLOPING METHODS.
FREE SIDE
R E
PROJECT
16.
ROLLER TUBE AND SHADE BAND ASSEMBLY (MAX 20 LBS)
A
FASTEN HANGER WIRES WITH NOT LESS THAN THREE (3) TIGHT TURNS IN THREE (3) INCHES. HANGER WIRE LOOPS SHALL BE TIGHTLY WRAPPED AND SHARPLY BENT TO PREVENT ANY VERTICAL MOVEMENT OR ROTATION OF THE MEMBER WITHIN THE LOOPS (SEE ASTM E580, SECTION 5.2.7.2). FASTEN BRACING WIRES WITH FOUR (4) TIGHT TURNS. MAKE ALL TIGHT TURNS WITHIN A DISTANCE OF ONE AND ONE-HALF (1 1/2) INCHES.
HANGER WIRES SHALL NOT ATTACH TO OR BEND AROUND INTERFERING MATERIAL OR EQUIPMENT. PROVIDE TRAPEZE OR OTHER SUPPLEMENTARY SUPPORT MEMBERS AT OBSTRUCTIONS TO TYPICAL HANGER SPACING. PROVIDE ADDITIONAL HANGERS, STRUTS, OR BRACES AS REQUIRED AT ALL CEILING BREAKS, SOFFITS, OR DISCONTINUOUS AREAS.
25.
AE_A_0550_004 Q1
T
15.
ACOUSTICAL CEILING EDGE 6" = 1'-0"
C23603
SEPARATE ALL CEILING HANGER AND BRACING WIRES AT LEAST SIX (6) INCHES FROM ALL UNBRACED DUCTS, PIPES, CONDUITS, AND ETC.
AT CURTAIN WALL AND ROLLER SHADE HOUSING CONDITIONS, TYP
TRAPEZE AT COMPRESSION STRUT
D A RCH SE I E N A N McM TE H U T A
14.
INSTALL SCREW SO MOVEMENT IS PERMITTED CEILING GRID 7/8" x 18GA WALL ANGLE WITH CLIP AND #10 x 1 1/2" LONG SDST SCREW TO WALL STUDS @ 24" OC MAX
PENETRATIONS THROUGH THE CEILING FOR SPRINKLER HEADS AND OTHER SIMILAR DEVICES THAT ARE NOT INTEGRALLY TIED TO THE CEILING SYSTEM IN THE LATERAL DIRECTION SHALL HAVE A TWO (2) INCH OVERSIZED RING, SLEEVE, OR ADAPTER THROUGH THE CEILING TILE TO ALLOW FREE MOVEMENT OF ONE (1) INCH IN ALL HORIZONTAL DIRECTIONS. ALTERNATIVELY, PER ASTM E580, SECTION 5.2.8.5, A FLEXIBLE SPRINKLER HOSE FITTING THAT CAN ACCOMMODATE ONE (1) INCH OF CEILING MOVEMENT SHALL BE PERMITTED TO BE USED IN LIEU OF THE OVERSIZED RING, SLEEVE, OR ADAPTER. LATERAL FORCE BRACING MAY BE OMITTED FOR SUSPENDED ACOUSTICAL CEILING SYSTEMS WITH A CEILING AREA OF 144 SQUARE FEET OR LESS.
HANGER OR BRACING WIRE ANCHORED TO THE STRUCTURE SHOULD BE INSTALLED IN SUCH A MANNER THAT THE DIRECTION OF THE ANCHOR ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTION OF THE WIRE.
ACOUSTIC CEILING TILE WHERE OCCURS
ACOUSTICAL CEILING SYSTEM
AE_A_0550_008 Q1
OR 1/4 THE LENGTH OF THE END RUNNER, WHICHEVER IS GREATER
HANGER WIRE, TYP
SEAL
13.
8" MAX
CROSS RUNNER
HANGER WIRE W/ (3) TIGHT TURNS MIN WITHIN FIRST 1 1/2" AS SHOWN
4/25/2019 8:48:35 AM
CEILING GRID MEMBERS SHALL BE ATTACHED TO TWO (2) ADJACENT WALLS PER ASTM E580, SECTION 5.2.3. CEILING GRID MEMBERS SHALL BE AT LEAST 3/4 INCH CLEAR OF OTHER WALLS. IF WALLS RUN DIAGONALLY TO CEILING GRID SYSTEM RUNNERS, ONE END OF MAIN AND CROSS RUNNERS SHOULD BE FREE, AND A MINIMUM OF 3/4 INCH CLEAR OF WALL.
AE_A_0550_003 Q1
3/4" = 1'-0"
SADDLE TIE, TYP
HANGER WIRE TRAPEZE 1 1/2" = 1'-0"
TYP CEILING BRACING ASSEMBLY 8" MAX
DBL HANGER WIRE W/ 4" MIN SEPARATION
1 1/2" MAX TYP
362S125-43 STEEL STUD OR PAIR OF 1 1/2" COLD ROLLED CHANNELS SCREWED BACK-TOBACK W/ #10 SDST SCREWS @ 24" OC MAX HANGER WIRE W/ SADDLE TIE
14
DUCT OR OTHER OBSTRUCTION
TYP WALL STUDS (20GA MIN AT STEEL STUDS & 2x MIN AT WOOD STUDS) W/ (2) LAYERS 5/8" GYP BOARD MAX
TYP CEILING BRACING ASSEMBLY
AE_A_0550_008 Q1
6.
1
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
NOTES: 1. THIS DETAIL DOES NOT APPLY TO CONDITIONS WHERE A COMPRESSION STRUT OCCURS UNDER TRAPEZE. 2. BRACING WIRES CANNOT ATTACH TO CHANNEL ABOVE.
AE_A_0550_009 Q1
1 1/2" = 1'-0"
DUCT OR OTHER OBSTRUCTIO N (3) TIGHT TURNS WITHIN FIRST 1 1/2" AS SHOWN, TYP
(2) #10 SMS SCREWS TO (E) HAT CHANNEL
3" = 1'-0"
MAIN RUNNER
SLOT END OVER MAIN RUNNER OR FLATTEN END
SPAN
EQEQ
7
SUSPENSION SYSTEM INSTALLATION SHALL COMPLY WITH 2016 CBC SECTION 808, ASCE 7-10, ASTM C635, ASTM C636, SECTION 5.2 OF ASTM E580, MANUFACTURER'S EVALUATION AGENCY REPORT, AND THE CONSTRUCTION DOCUMENTS.
CROSS RUNNER
3" MIN TYP
HANGER WIRE TRAPEZE
(4) #12 GA SPLAY WIRE BRACING IN PLANE OF EA RUNNER AT COMPRESSION STRUT. WIRE BRACING TO HAVE (4) TIGHT TURNS WITHIN 1 1/2" AT EACH END
CROSS RUNNER
HANGER WIRE, TYP
3
5.
MAIN RUNNER
2"
1/4" DIA MACHINE BOLT
TYP BRACING WIRE TO STUD WALL
TYP HANGER WIRE SPACING
MAIN RUNNERS, CROSS RUNNERS, SPLICES, EXPANSION DEVICES, AND INTERSECTION CONNECTORS SHALL BE DESIGNED TO CARRY A MEAN ULTIMATE TEST LOAD OF NOT LESS THAN 180 LBS IN COMPRESSION AND TENSION PER ASTM E580 SECTION 5.1.2.
10.
8'-0" MAX
B
4.
10 A-551
3 TIGHT TURNS, TYPICAL
AE_A_0550_008 Q1
OR
1 1/2" MAX
1 1/2" = 1'-0"
9 A-551
EMT GALVANIZED, SIZED TO SLIDE NEATLY OVER COMPRESSION STRUT
NOTES: 1. CEILING BRACING WIRE SHALL NOT BE ATTACHED TO WALL ON "FREE JOINT" SIDE OF CEILING 2. WHERE ONLY (1) LAYER OF 5/8" GYP IS USED, #12 SCREWS MAY BE REPLACED W/ #10 SCREWS 3. SCREWS INTO WOOD STUDS SHALL HAVE 1 1/2" MIN EMBED INTO STUD
6
1'-0" MAX
1/2" MAX
2 HANGER WIRE TRAPEZE
BRACE WIRE, TYP
45° MAX
BRACING WIRES MUST ATTACH TO 1/4" DIA EYE LAG W/ 1 1/2" EMBED INTO (E) WOOD JOIST, LOCATE AT INTERSECTION OF (E) JOIST AND (E) HAT CHANNEL
VERTICAL HANGER WIRE
STUD OR EMT COMPRESSION STRUT
TYP
ATTACH TO (E) HAT CHANNELS W/ 1/4" DIA EYE LAG. ONLY ONE HANGER WIRE PERMITTED PER HAT CHANNEL PER JOIST BAY
CEILING WIRE SHALL BE CLASS 1 ZINC COATED (GALVANIZED) CARBON STEEL CONFORMING TO ASTM A641. WIRE SHALL BE #12 GAGE (0.106" DIAMETER) WITH SOFT TEMPER AND A MINIMUM TENSILE STRENGTH OF 70 ksi.
HANGER WIRE
BRACE WIRE WITH (4) TIGHT TURNS WITHIN FIRST 1 1/2" OF WIRE
12GA x 1" WIDE CLIP WITH 1 1/2" LEGS W/ (2) #12 SDST SCREWS TO STUD OR BACKING
C
3.
A
(E) 7/8" HAT CHANNELS @ 16" OC MAX
THE CEILING GRID SYSTEM MUST BE RATED HEAVY-DUTY AS DEFINED BY ASTM C635.
CT Y R RT
(E) FLOOR JOIST
2.
ST
600S137-54 BACKING; SPAN MIN (2) WALL STUDS & CONNECT W/ (4) #12 SDST SCREWS EA STUD. WHERE CLIP ATTACHES DIRECTLY TO WALL STUDS, ONLY (2) SCREWS ARE REQUIRED
3/4" MIN
(2) LAYERS OF 5/8" GYP BD MAX TYP WALL STUD (18GA MIN STEEL STUD OR 2x MIN WOOD STUD)
SUSPENSION SYSTEM COMPONENTS SHALL COMPLY WITH ASTM C635 AND SECTION 5.1 OF ASTM E580.
AE_A_0550_005 Q1
SCALE: NTS
1 A-551
EMT GALVANIZED COMPRESSION STRUT, SIZE PER TABLE BELOW
1.
IA
(2) #10 SMS
CROSS RUNNER
FREE SIDE
12GA PERIMETER HANGER WIRE WITH (3) TIGHT TURNS WITHIN FIRST 3" OF WIRE
1
PERIMETER WALL ANGLE
N
(2) #10 SMS
BRACE WIRE, TYP
15 A-551
9
D
NOTES: 1. THIS DETAIL APPLIES FOR PERIMETER WIRE ATTACHMENT OR WHERE OBSTRUCTION PREVENTS ATTACHMENT TO STRUCTURE ABOVE 2. HANGER WIRE SHALL HAVE A MINIMUM STRETCH LENGTH OF 12" 3. WHERE ONLY (1) LAYER OF 5/8" GYP IS USED, #12 SCREWS MAY BE REPLACED W/ #10 SCREWS 4. SCREWS INTO WOOD STUDS SHALL HAVE 1 1/2" MIN EMBED INTO STUD
3 77/128"
12 GA PERIMETER HANGER WIRES AT TERMINAL END OF EACH MAIN RUNNER AND CROSS TEE LINE OF PERIMETER WALL
4 205/256"
362S125-30 MIN BACKING; SPAN MIN (2) WALL STUDS & CONNECT W/ (2) #12 SDST SCREWS EA STUD, OMIT WHERE CLIP ATTACHES DIRECTLY TO STUD
12GA x 3/4" WIDE CLIP WITH 1" LEGS W/ (2) #12 SDST SCREWS TO STUD OR BACKING (2) #10 SMS SCREWS TO (E) HAT CHANNEL
1/2 TYP BRACING ASSEMBLY SPACING
FREE SIDE
TYP WALL STUD (18GA MIN STEEL STUD OR 2x MIN WOOD STUD)
(E) FLOOR JOISTS
STEEL STUD COMPRESSION STRUT; SEE TABLE FOR SIZE
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
R
(2) LAYERS OF 5/8" GYP BD MAX
3 A-551
LI JO C N
FOR CEILING CONNECTION SEE DETAIL,
5/8" MIN EDGE DISTANCE, TYP
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
AE_A_0550_002 Q1
A-551
2
3
4
5
CABINET DESIGN SERIES (CDS) COUNTER SEE DETAIL
6 A-561
TRIM EXPOSED END OF ANGLE AT 45° ANGLE AS SHOWN
•
BASE CABINETS W/O DRAWERS
100 SERIES
•
BASE CABINETS W/ DRAWERS
200 SERIES
•
WALL HUNG CABINETS
300 SERIES
•
TALL STORAGE CABINETS
400 SERIES
•
TALL WARDROBE CABINETS
500 SERIES
•
LIBRARY CABINETS
600 SERIES
•
MOVEABLE CABINETS
700 SERIES
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
(3) #12 x 3/4" WOOD SCREWS PER BRACE
D
SEE RCP FOR CEILING LAYOUT AND HEIGHT
REF. CEILING PLAN
CLOSE AND SEAL WALL PENETRATION AT BRACE
SEE
EQ. (3) #12 SCREWS @ 1" OC T&B OF ANGLE TO STUD
LOW PROFILE DUST CAP
LOW PROFILE DUST CAP
SECTION UPPER CABINET DOOR 3 A-561
5" 3/4" ADJUSTABLE SHELF W/ WHITE MELAMINE FINISH
7"
3"
MDF BACKING W/ WHITE MELAMINE FINISH
SCRIBE TO WALL AT BACK AND SIDES. PROVIDE FINISH FACE ON ALL EXPOSED SURFACES
2-0" 3"
IA N
R E
EN . 08 - 3 1 - 1 O F OF CAL I
9
T
CABINET DOOR
DOOR PULL SEE INTERIOR ELEVATIONS
C
PROJECT
(5) 3/4" ADJUSTABLE SHELVES W/ WHITE MELAMINE FINISH
3/4" ADJUSTABLE SHELF W/ WHITE MELAMINE FINISH
ANGLE BRACE AT 24" OC
5 A-561
1" = 1'-0"
7667 FOLSOM BLVD, SACRAMENTO, CA 95826
5 A-561
TYP CASEWORK SECTION ?DRS TRACKING NUMBER? ?YYMMDD?. Q1
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
20 GA MIN STUD AT EA BRACE
BASE CABINET DOOR
1
C23603
R
SEE INTERIOR ELEVATION
SEE INTERIOR ELEVATION
ISOMETRIC
D A RCH SE I E N A N McM TE H U T A
CT Y R RT
DOOR PULL SEE INTERIOR ELEVATIONS
L 1 3/4" x 1 3/4" x 1/4 STEEL ANGLE PAINTED BLACK, TYP
SEAL
A
2' - 1"
TRIM EDGE AT 45° ANGLE (NOT SHOWN FOR CLARITY)
ST
4 A-561
6 COUNTER SEE DETAIL A-561
7" 3"
DOOR PULL SEE INTERIOR ELEVATIONS
FACE OF WALL
1'10 "
LI JO C N
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
2
PLAN
FIN. FLR.
TYP CASEWORK SECTION ?DRS TRACKING NUMBER? ?YYMMDD?. Q1
1" = 1'-0"
7
CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
TYP CONCEALED ANGLE BRACKET 1 1/2" = 1'-0"
?DRS TRACKING NUMBER? ?YYMMDD?. Q1
CONT. BLOCKING ISSUED COUNTER PER FINISH SCHEDULE
4"
3/4" PLYWOOD, TYPICAL
DATE
DESCRIPTION
TYPICAL
SCREWS@ 12" O.C. MAX. (MIN. (2) PER CABINET)
MARK
MTL. BACKING SEE DETAIL CONTINUOUS SILICON SEALANT JOINT
UPPER ANCHOR CABINET BACK
#10 X 34 FLAT HEAD WOOD SCREW 2"
(2) #12-14 TEKS/4 SCREWS
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
016279.06 ?00.00.00? LIONAKIS 2015
24" DEPTH OF CASEWORK, TYPICAL AGENCY
LOWER ANCHOR
3
TYP UPPER CASEWORK ANCHORAGE ?DRS TRACKING NUMBER? ?YYMMDD?. Q1
3" = 1'-0"
6
TYP COUNTERTOP 1" = 1'-0"
?DRS TRACKING NUMBER? ?YYMMDD?. Q1
FINISHED WALL SCRIBE TO WALL
BACK SPLASH
FILE NO: 34-CSUS
BASE CABINET COUNTER PER FINISH SCHEDULE
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
#12x 2 3/4" WOOD SCREWS @ 16" OC MAX CONTINUOUS 2x PRESSURE TREATED WOOD NAILER
AC
FLS
SS
DATE
4" RUBBER BASE
A
TITLE SCREWS @ 12" O.C., TWO (2) SCREWS PER CABINET MIN.
DETAILS CASEWORK
F.F.
MTL. BACKING SEE
2"
4/25/2019 8:48:38 AM
MANAGEMENT
MTL. BACKING PER DETAIL
4"
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
SCRIBE TIGHT TO WALL
33-1/2" ABOVE FINISH FLOOR TYP.
SCREWS @ 12" O.C. MAX. (MIN. (2) PER CABINET)
3/4"
1 1/2"
CONT. BLOCKING B
#10 SCREWS @ 12" OC
SHEET
4
TYP BASE WALL ANCHOR 3" = 1'-0"
?DRS TRACKING NUMBER? ?YYMMDD?. Q1
5
TYP FLOOR BASE ANCHOR 3" = 1'-0"
?DRS TRACKING NUMBER? ?YYMMDD?. Q1
A-561
2"
1
2
3
4
5
GENERAL NOTES
MANUFACTURER
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
FINISH CODE
INTERIOR FINISH LEGEND
CARPET C1 TANDUS
TYPE / STYLE, COLOR, SIZE STYLE: STREET LIFE 03973 COLOR: CURBSIDE 36108
BASE B1 JOHNSONITE CEILING FINISHES CL1 ARMSTRONG
IF AT ANY TIME THE GENERAL CONTRACTOR REQUIRES CLARIFICATION OF FINISH LOCATIONS, CONTACT PROJECT ARCHITECT PRIOR TO FINISH APPLICATION.
3.
CEILING FINISHES SHALL BE IN COMPLIANCE WITH TABLE 803.9
4.
WALL AND CEILING MATERIALS SHALL NOT EXCEED THE ALLOWABLE FLAME SPREAD CLASSIFICATION IN APPLICABLE CODE, CLASS A
5.
INTERIOR WALL AND CEILING FINISHES FOR ALL ROOMS AND ENCLOSED SPACES IN 1-2.1 OCCUPANCY, INCLUDING EXIT ENCLOSURES AND CORRIDORS SHALL BE CLASS B WITH FLAME SPREAD 26 TO 75.
6.
ALL CEILING AND HEADERS TO BE PAINTED P1, UNO.
7.
DOORS FRAMES TO BE LATEX PAINT WITH A GLOSS LEVEL G5 - SEMI-GLOSS FINISH, UNO.
8.
ALL PAINT IN OR ROOMS TO BE A GLOSS LEVEL G5 - SEMI-GLOSS, UNO.
9.
PATCH AND REPAIR ALL AREAS AFFECTED BY DEMOLITION. FINISH TO MATCH ADJACENT SURFACES UNO.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
QUARTER TURN INSTALLATION
PAINT P1 KELLY MOORE COLOR: URBAN BIRD #KM4584 FINISH: SEMI-GLOSS PLASTIC LAMINATE PL1 LAB DESIGNS STYLE: GREY OAK STYLE #: VN707 SM SOLID SURFACE SF1 DUPONT COLOR: CORIAN "LINEN"
D
NOTES
1.
VERTICAL GRAIN INSTALLATION
10. ALL WALL FINISH TEXTURE SHALL MATCH EXISTING CAMPUS STANDARDS. 11. A MINIMUM OF 72 HOUR NOTICE IS REQUIRED FOR ANY TESTING AND/OR INSPECTION
COLOR: THIS ORE THAT
STYLE: ULTIMA 1914 COLOR: WHITE SIZE: 2X4
RESILIENT FLOORING R1 SHAW HARD STYLE NAME: JEOGORI SURFACE STYLE # 012V COLOR NAME: LINEN COLOR #90500 SPECIALITY PRODUCT SP1 MECHOSHADE STYLE NAME: 6000 SERIES TWILL , EUROTWILL WEAVE COLOR: 6009 DOVE GREY
INTERIOR FINISH REMARKS
+/- 3% OPENNESS FACTOR, QUAKER BRONZE FASCIA
1.
SEE REFLECTED CEILING PLAN FOR CLARIFCATION ON CEILING TYPES AND FINISH.
2.
SEE INTERIOR ELEVATIONS FOR FINISH CLARIFICATION AND LOCATION.
3.
FLOORING AND COVED BASE SHALL HAVE WELDED SEAMS TO MATCH DARKEST ADJACENT FLOORING
ROOM FINISH SCHEDULE 2204 2601 2602 2603 2604
CORRIDOR 2316
PT OFFICE 2306B
SERV CLOS. 2401A
CLASSROOM
11
E E E E E
C1 R1 C1 R1 C1
B1 B1 B1 B1 B1
5 5 5 5 E
P1 P1 P1 P1 P1
E 5 5 E E
P1 P1 P1 P1 P1
5 5 5 5 5
P1 P1 P1 P1 P1
E E 5 5 E
P1 P1 P1 P1 P1
CL1 CL1 CL1 CL1 CL1
NONE 1 NONE 1 NONE
-
LEGEND
7
E
PLASTIC LAMINATE DUST CAPS TO MATCH ADJACENT VERTICAL LAMINATE, UNO. D A RCH SE I E N A N McM TE H U T A
COUNTER EDGE BANDING TO BE 3MIL GREENLINE ABS EDGEBANDING, TO MATCH HORIZONTAL SURFACE.
2*
C23603 T
A
C
2.
SEAL
ST
ASSISTIVE LISTENING DEVICE 41 OCC x 4% = 1.64, OR 2 PORTABLE DEVICES
ALL CASEWORK SHELVING SHALL BE ADJUSTABLE, UNO.
5 G-111
FUNCTION ROOM SIGNAGE, SEE DETAIL
C1 P1
1.
4. DRAWER AND DOOR EDGE BANDING TO BE 0.018 3 MIL EDGE BANDING TO MATCH VERTICAL SURFACE.
2
2306A
NOTES
3.
2604
PT OFFICE
CASEWORK LEGEND AND NOTES
2308A
AUDIOLOGY LAB
2305A
2602
2603
R1
C1
R1
P1
P1
2
P1
AUDIO LAB CONSULT
4*
HORIZONTAL: SF1 - COUNTERTOP & BACKSPLASH
5
2305
VERTICAL: PL1
7667 FOLSOM BLVD, SACRAMENTO, CA 95826
REMOVE (E) SIGN WITH MESSAGE "RESTRICTED ACCESS BY ORDER OF THE STATE FIRE MARSHAL"
CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
18 G-111
8
ASSISTIVE LISTENING DEVICE SIGN, SEE DETAIL
C1
FINISH FLOOR TYPE REFER TO ROOM FINISH SCHEDULE AND FINISH LEGEND
2 4*
F
2*
CORRIDOR
AUXILLARY OBSERVATION
TACTILE EXIT SIGNAGE "EXIT ROUTE", SEE DETAIL
16 G-111
BASE: USE BASE SPECIFIED IN ROOM, TYPICAL UNO
7
2
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
(E) TACTILE "EXIT ROUTE" SIGN TYPE 1
5
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
AUDIOLOGY LAB AUDIOLOGY LAB
2601
R E
(E) TACTILE ROOM IDENTIFICATION SIGN
CLOS. AUDIO LAB TEST BOOTH
CT Y R RT
2
COMPUTER LAB AUDIOLOGY LAB AUDIOLOGY LAB AUDIOLOGY LAB CLASSROOM
INTERIOR FINISH REMARKS
IA
2400
ROOM NAME
MATERIAL CODES
2404K
DN
ISSUED
2320
MARK
OBSERVATION STAIR NO. 2
2319
2504 DN
STORAGE
STORAGE
2304B
2304
P1
PAINT TYPE REFER TO ROOM FINISH SCHEDULE AND FINISH LEGEND
OBVS. CLOS. 2322
N
2401
NO
9
WAITING
R
SERV DESK
FLOOR NORTH EAST SOUTH WEST CEILING CASEWORK INTERIOR TYPE ELEVATION MATL FIN BASE MATL FIN MATL FIN MATL FIN MATL FIN MATL FIN
LI JO C N
D
EXISTING, NOT IN SCOPE
C1
CORRIDOR
1 2 3 4 5 6 7 8 E OTS
DATE
DESCRIPTION
CONCRETE PLYWOOD (DECKING) CONCRETE MASONRY UNIT BRICK GYPSUM WALLBOARD GYPSUM WALLBOARD, WATER RESISTANT EXPOSED STRUCTURE CEMENTITIOUS WALLBOARD EXISTING OPEN TO STRUCTURE
2323 7
G
2
ELEV NO.1
B
101
11
C:\Users\jason.luo\Documents\_RevitLocalFiles\016279.06_BIM_A-MASTER_R18_CENTRAL_Jason.Luo.rvt
ASSISTIVE LISTENING DEVICE 40 OCC x 4% = 1.6, OR 2 PORTABLE DEVICES
MANAGEMENT
STAIR NO.1 2404J
LOBBY
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
1000
AGENCY
THERAPY
COMPUTER LAB
2203O
2204
H CORRIDOR 2315
C1 P1
KEY PLAN LG THERAPY 2204B
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
I AC
A
FLS
SS
DATE A
TITLE
B
PLAN NORTH
4 4/25/2019 8:48:41 AM
016279.06 ?00.00.00? LIONAKIS 2015
PARTIAL FINISH FLOOR & SIGNAGE PLAN - LEVEL 2
PARTIAL FINISH FLOOR & SIGNAGE PLAN LEVEL 2
SCALE 1/8" = 1'-0" SHEET
AF112A
FILE NO: 34-CSUS
3
4
5
DUCT SYMBOLS
3.
NOTES: SEE NOTE 1.
1. PEEL BACK JACKET AND SECURE TO PLENUM COLLAR. USE A MIN. OF (3) SHEET METAL SCREWS AND (2) FULL WRAPS OF DUCT TAPE. PULL BACK JACKET AND APPLY (2) FULL WRAPS OF DUCT TAPE. ALTERNATE METHOD: BANDING DEVICE OR PANDUIT STRAP, IN LIEU OF SHEET METAL 3 DIAMETERS SCREWS. SEE NOTE 2.
5.
SECURE TO STRUCTURE WITH #12 SWG HANGER WIRE (TYPICAL OF 2) @ OPPOSITE CORNERS. SEE STRUCTURAL DETAILS AND 5/M-001
2. IF A MINIMUM 3 DUCT DIAMETERS OF STRAIGHT RUN IS NOT AVAILABLE ABOVE REGISTER USE PLENUM ABOVE REGISTER.
D
4.
FLEXIBLE FIBROUS DUCT. SEE SPEC'S.
3. FLEXIBLE AIR DUCTS AND CONNECTORS SHALL BE NOT MORE THAN 5 FEET IN LENGTH AND SHALL NOT BE USED IN LIEU OF RIGID ELBOWS OR FITTINGS PER CMC 603.4.1.
SHEET METAL SCREWS SEE NOTE 1.
4. FOR CONFINED SPACES, USE PLENUM BOX ABOVE DIFFUSER. FOR CONFINED SPACE DIFFUSER INSTALLATION.
6.
7. SURFACE MOUNTED DIFFUSER SUPPLY AIR DIFFUSER.
T-BAR CEILING
24x12 W
=1
24x12
R
16x12
24x12
16x12
EXHAUST DUCT DROP
PLANS ARE NOT FOR CONSTRUCTION UNTIL APPROVED BY THE AUTHORITY HAVING JURISDICTION. THE CONTRACTOR SHALL NOT ORDER ANY MATERIALS OR INSTALL ANY EQUIPMENT, PIPING, ETC. UNTIL PLANS ARE APPROVED BY THE AUTHORITY HAVING JURISDICTION.
24x12
2
R
ALL WORK SHALL BE IN ACCORDANCE WITH ALL FEDERAL, STATE, CITY AND LOCAL CODES AND ORDINANCES.
W
12x12
THE CONTRACTOR SHALL READ ALL OF THE GENERAL NOTES, SPECIFICATIONS AND PLANS AND SHALL BE SATISFIED TO THEIR TRUE MEANING AND INTENT AND SHALL BE RESPONSIBLE FOR COMPLYING WITH EACH. WHEREVER TWO OR MORE SPECIFICATIONS MAY CONFLICT, THE MORE STRINGENT SPECIFICATION SHALL TAKE PRECEDENCE.
15 10/14
SECTION AT RETURN DUCT RISER
24x12 =1.5
14x10 MVD
TRANSITIONAL TURN
10/14
R=36
12x12
24x12
16x12
RETURN DUCT DROP
3
IT IS INTENDED THAT THESE PLANS AND SPECIFICATIONS REQUIRE ALL LABOR AND MATERIAL NECESSARY AND PROPER FOR THE WORK CONTEMPLATED AND THAT THIS WORK BE COMPLETED IN ACCORDANCE WITH THEIR TRUE INTENT AND PURPOSE. THE CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE IMMEDIATELY REGARDING ANY DISCREPANCIES OR AMBIGUITIES THAT MAY EXIST IN THE PLANS AND/OR SPECIFICATIONS PRIOR TO SUBMITTING BID. THE OWNER'S REPRESENTATIVE AND THE ENGINEER'S INTERPRETATION THEREOF SHALL BE CONCLUSIVE.
TURNING VANES
24x12
16 4/36/8
SECTION AT SUPPLY DUCT RISER
24x12
10x8
38x12
48x12 12x12
CONVERGING OR DIVERGING VANE ANGLE
24x12
17 4/36/8
38x12 TRANSITION
12x12 10x8
36"
CONTRACTOR SHALL INSTALL ALL PIPING AND DUCTWORK SYSTEMS TO BEST SUIT FIELD CONDITIONS, AND COORDINATE WITH THE INSTALLATION WORK OF OTHER TRADES. THE DRAWINGS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION OF PIPING. NOTIFY CONSTRUCTION MANAGER OF ANY DEVIATIONS FROM THESE DRAWINGS PRIOR TO FABRICATION AND/OR INSTALLATION.
5
48x12 VANE ANGLE 20°-29° 30°-50°
12x12
12"∅
TURNING VANES 15° DEFLECTROL AIRTURN
38x12
48x12 12x12 18
12x12
38x12 TRANSITION
12x12 12x12
12x12
NONE
12x12
1 IN 6 MAX.
6
24x12
10.
1"x22 GA HANGER STRAP (TYP 4)
11.
22" MIN
22"X22"
22x18 LINED DUCT
24x7 ABOVE
16x12
ALL WORK SHOWN ANYWHERE ON THE DRAWINGS IS INCLUDED; SHOULD AN ITEM (SUCH AS A VALVE) BE SHOWN ON A DETAIL OR SCHEMATIC BUT NOT ON A PLAN VIEW OR VICE VERSA, IT MUST BE PROVIDED AS THOUGH IT WERE SHOWN IN ALL PLACES ON THE DRAWINGS.
7
CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES, INSERTS, SLEEVES, HANGING DEVICES, MISCELLANEOUS ANGLES, CHANNELS, UNISTRUT ETC. FOR INSTALLATION OF MECHANICAL AND PLUMBING EQUIPMENT, DUCTWORK AND PIPING, ETC. CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ALL BUILDING TRADES TO AVOID CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.
TRANSVERSE SWAY BRACING SERVING AS LONGITUDINAL SWAY BRACING AT END OF DUCT RUN.
SEISMIC BRACING FOR PIPING CARRYING HAZARDOUS OR COMBUSTIBLE MATERIALS (SUCH AS NATURAL LINES) SHALL BE PROVIDED FOR ALL PIPES > 1" DIAMETER IN SIZE. BRACING SHALL BE PER CBC SECTION 1616A.1.26. ACCEPTABLE SEISMIC BRACING DETAILS INCLUDE THOSE SHOWN IN EATON/COOPER B-LINE OPM-0052-13. SEISMIC BRACING FOR PIPING CARRYING HAZARDOUS OR COMBUSTIBLE MATERIALS (SUCH AS WATER LINES) SHALL BE PROVIDED FOR ALL PIPES > 3" DIAMETER IN SIZE. BRACING SHALL BE PER CBC SECTION 1616A.1.26. ACCEPTABLE SEISMIC BRACING DETAILS INCLUDE THOSE SHOWN IN EATON/COOPER B-LINE OPM-0052-13.
12 GA SAFETY WIRE (TYP.OF 4) TRANSVERSE SWAY BRACING SERVING AS LONGITUDINAL SWAY BRACING AT END OF DUCT RUN.
3/8"Ø HANGER ROD 8'-0" O.C. ATTACH TO STRUCTURE PER 5/M-001
BRACKET, 1" WIDEx1/8" WITH (2) 45° BENDS "ELCEN" No. 207P BRIDGE CLEVIS
14x10
UPPER ATTACHMENT DETAIL
21 TRANSITION
14/10
16x12
10"
14/10
14x10
9
24x12
F
TRANSITIONAL RADIUS ELBOW
REMARKS
DEFLECTROL AND BRANCH SAME SIZE 24x12 SIDEWALL REGISTER OR GRILLE
24x12
14x12
24x12
14/10
INCHES UNLESS OTHERWISE NOTED. 10
14x12 10"Ø
12"Ø
10"Ø
12"Ø
23 FLEX DUCT
10"Ø 45ØTEE
24x12 12x6 10'MAX. LENGTH OVER 10' USE NO. 6,7,8 OR 9 FIRE DAMPER
F
10'MAX. LENGTH OVER 10' USE NO. 6,7,8 OR 9
INDICATES ROUND DUCTS IN INCHES, TYPICAL
BRANCH-SEE PLAN FOR SIZE
24x12
CEILING DIFFUSER FLEX. DUCT DIFFUSER
SEAL D A RCH SE I E N A N McM TE H U T A
C23603 T
R E
EN . 08 - 3 1 - 1 O F OF CALI
PROJECT
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD., SACRAMENTO, CA 95826
CEILING DIFFUSER
ELONGATED TEE
CLIENT
TITUS MODEL
BORDER TYPE
OBD
SD-L
MCD
T-BAR LAY-IN
NO
WHITE
MODULAR CORE
AIR FLOW
RG-L
PAR
T-BAR LAY-IN
NO
WHITE
PERFORATED FACE
AIR FLOW
SUPPLY DUCT RISE
11
24 AIR FLOW
RETURN OR EXHAUST AIR RISE
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
SHOE FITTING WITH MVD
SUPPLY DUCT DROP
12
25 AIR FLOW
AIR FLOW
ISSUED MARK
CONICAL FITTING WITH MVD
DATE
DESCRIPTION
26 ACOUSTICALLY LINED SHEET METAL DUCT SIZE SHOWN IS NET INSIDE DIMENSION
24 x 36 AL
24 x 36 AL
CONICAL FITTING
PLAN VIEW NOTE: 1. SUPPORT DUCT WITH TRANSVERSE SUPPORTS EACH END OF DUCT RUN PER OPM-0043-13. TRANSVERSE SUPPORTS EVERY 30'-0" O.C. AND LONGITUDINAL SUPPORTS EVERY 60'-0" O.C. LONGITUDINAL SUPPORT MAY BE OMITTED WHERE TRANSVERSE SUPPORTS ARE WITHIN THE MAXIMUM OFFSET LENGTH AT 90° TURNS. 2. SWAY BRACING MAY BE OMITTED WHEN DUCTWORK IS SECURED WITHIN 12" OF SUPPORT STRUCTURE. 3. CONTRACTOR SHALL PROVIDE A SHOP DRAWING SHOW BRACING LAYOUT COORDINATING WITH ALL DISCIPLINES.
ROUND DUCT SUPPORT NONE
3/8" STRUT HARDWARE (TYP.)
3/8" LAG BOLT 20 GA, 1" WIDE DUCT STRAP
DEFLECTROL AND BRANCH SAME SIZE AS NECK SIZE
SQUARE ELBOW W/ TURNING VANES
10"
I
CAP AT END OF RUN
24x12
TRANSITION 16x12
BLOCKING PER STRUCTURAL DRAWINGS
5" MIN. TYP.
3/8" LAG BOLT
22
14"
OF CA L
L
N I F OR
SECURE STRAP TO CLEVIS WITH 1/4"Øx1" BOLT, WASHER AND NUT
REINFORCEMENT PER STRUCTURAL DRAWINGS
20 GA, 1" WIDE DUCT STRAP 3/8" ALL THREAD
A
24x12
CHAN I CA
4/16/2019 3:44:20 PM
ECCENTRIC
CEILING DIFFUSER
16x12
S.M. STRAP AROUND DUCT
M-001
SECURE 1/8"Lx2x2x6"LONG TO STRUCTURAL MEMBER WITH 1/4"∅ BOLTS & NUTS, TYP.
12x12
CONCENTRIC
ME
TE
MECHANICAL LEGEND
(E) TJI (TYP)
NONE
16x12
13
ROUND DUCT
3
NONE
3/16" MIN. TYP.
12x12
R. T I C HE
AN
M31176 EXP. 12/31/19 TA
DEFLECTROL & BRANCH DUCT SAME SIZE
24x12
-
RECTANGULAR DUCT SUPPORT
SECURE ALL-THREAD TO 1/2" MAX. ANGLE ABOVE WITH TYP. DOUBLE NUTS AND WASHER, TYPI.
20
RETURN OR EXHAUST AIR DROP
SECURE RODS TO BRACKET WITH 3/8"Ø NUTS AND LOCKWASHERS
#10 X 1 1/4" SHT. MTL. SCREWS. TYP. OF (2) PER SIDE (3" PER FROM EA. END)
FINISH
24x12
24x12
1 IN 2 MAX.
24x5 BELOW
14"
PRO F E S S I ONA L
ED
CONTRACTING FLOW
12x6
30x5
24x12
24x12
AIR FLOW
3/32"Ø PRESTRETCHED GALVANIZED AIRCRAFT CABLE 7x19 STRAND CORE @ 45°. 30 FT.
FLOOR ABOVE
M-001
16x12
24x12
14.
MARK
NOTE: 1. SUPPORT DUCT WITH TRANSVERSE SUPPORTS EACH END OF DUCT RUN PER OPM-0043-13. TRANSVERSE SUPPORTS EVERY 30'-0" O.C. AND LONGITUDINAL SUPPORTS EVERY 60'-0" O.C. LONGITUDINAL SUPPORT MAY BE OMITTED WHERE TRANSVERSE SUPPORTS ARE WITHIN THE MAXIMUM OFFSET LENGTH AT 90° TURNS. 2. SWAY BRACING MAY BE OMITTED WHEN DUCTWORK IS SECURED WITHIN 12" OF SUPPORT STRUCTURE. 3. CONTRACTOR SHALL PROVIDE A SHOP DRAWING SHOW BRACING LAYOUT COORDINATING WITH ALL DISCIPLINES.
5
30x5
14/10
NECK SIZE AND DEFLECTION ARE SHOWN ON FLOOR PLANS
PLAN VIEW
M-001
7/5
12"Ø
ATTACH TO STRUCTURE PER 5/M-001
4
SQUARE ELBOW W/ TURNING VANES 16x12
8
EACH MECHANICAL APPLIANCE SHALL BE APPROVED BY THE ADMINISTRATIVE AUTHORITY FOR SAFE USE OR COMPLY WITH APPLICABLE NATIONALLY RECOGNIZED STANDARDS AS EVIDENCED BY THE LISTING AND LABEL OF AN APPROVED AGENCY. THERMOSTAT SETPOINTS SHALL BE PER CALIFORNIA T-24 REQUIREMENT. ANY DEVIATION FROM THESE SETPOINTS BECOMES THE RESPONSIBILITY OF THE USER OR CONTRACTOR.
15.
ATTACH TO STRUCTURE PER 5/M-001
B
24x7 ABOVE
24x12
NONE
1-1/2"x4"x1/4" BENT SWAY BRACE WITH (2) 7/16"ø HOLES
TRANSITIONAL RADIUS ELBOW 30x5
24x12 24x5 BELOW
DIFFUSER, REGISTER AND GILLE SCHEDULE
SECURE SWAY TO SWAY BRACE WITH (2) CABLE CLAMPS. LONGITUDINAL AND TRANSVERSE SWAY BRACING
7/5
30x5
RETURN AIR BOOT DETAIL
20" GA. SHT. MTL. STRAP @ 10'-0" O.C. MIN. 1" WIDE PER SMACNA STDS.
1 IN 2 MAX. ECCENTRIC
A
RETURN DIFFUSER-22x22 RG-L (U.O.N.)
ATTACH TO STRUCTURE PER 5/M-001
24x12
24x12
DIVERGING FLOW
16x12
13.
CEILING, SEE ARCH'L DWGS.
M-001
CONCENTRIC
22x22 NECK(U.O.N.)
C
2
1 IN 2 MAX.
1 IN 2 MAX.
12x12
24x12
12x12
ST
SHEET METAL SCREWS (TYP)
19
7/5 SPLIT TRANSITION
1 IN 6 MAX.
CT Y R RT
12.
24x12
consulting mechanical and electrical engineers
S
ATTACH TO STRUCTURE ABOVE PER 5/M-001
CONTRACTOR SHALL REMOVE RUBBISH WASTE MATERIALS ON DAILY BASIS AND PROTECT AREAS FROM DAMAGE WHICH MAY OCCUR DURING CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE WHICH MAY OCCUR.
SQUARE TO ROUND TRANSITION
PETERS engineering
ER
12"Ø MVD
MVD
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
4/36/8
8"
I NEER
M-001
DIFFUSER DETAIL
LOCATIONS AND DIMENSIONS OF EQUIPMENT, PIPING, AND THEIR SUPPORTS ARE SHOWN DIAGRAMMATICALLY AND SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION OF PIPING OR DUCTWORK. ACTUAL DIMENSIONS AND LOCATIONS ARE DEPENDENT ON MATERIAL SUPPLIED BY CONTRACTORS. CONTRACTORS SHALL PROVIDE OR DETERMINE DIMENSIONS AND PROVIDE LAYOUT DRAWINGS FOR COORDINATION WITH OTHER TRADES IN ACCORDANCE WITH THE SPECIFICATIONS.
SQUARE ELBOW W/ DUCT TURN
4"
10x12
12x12
12x12
4/36/8
8"
TURNING VANES
THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ANY FIELD CHANGES MADE WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE OWNERS REPRESENTATIVE.
TRANSITIONAL RADIUS ELBOW
4"
10x8
36"
SUPPLY DUCT DROP
24x12
MVD 16x12
14"
24x12
48x12
4
14x10 SQUARE ELBOW W/ DUCT TURN
10"
R NO
1
8.
10/14 SPLIT
14"
AIR FLOW
12x12
9.
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
R
24x12
24x12
4/16/2019 3:44:20 PM
TRANSITIONAL RADIUS ELBOW
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
IA
GSM DUCT
W
14x10
10"
14x10
N
2.
ALL PLANS TO BE DESIGNED TO CODES 2016 CBC, CRC, CAL GREEN CODE CMC, CEC, 2016 CPC, (BASED ON THE 2015 IBC, 2015 IRC, 2016 CAL GREEN BUILDING STANDARDS CODE, 2015 UMC, 2015 UPC, 2014 NEC), AND 2016 ENERGY STANDARDS, AS AMENDED BY THE STATE OF CALIFORNIA AND LOCAL JURISDICTIONS.
14 10/14
SECTION AT EXHAUST DUCT RISER
9
1.
LINED DUCT
DESCRIPTION
A
1
SYMBOL
SE
GSM DUCT ELBOW
DESCRIPTION
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
SYMBOL
REG I S T
GENERAL NOTES
R
2
LI JO C N
2"
1
3/8" EYE-BOLT THRU ROOF JOIST WITH NUT & WASHER F
12 GA SAFETY WIRE (TYP.OF 4)
FSD
3/8" ALL THREAD
AC AD AE AFF AL BDD BHP BOD C CD CFM CEF CL DB DL DN. EA EAL EAT EF (E) EG ESP °F FA FAL FC FD FSD FPM FLA FT GA GI GSM H&V HZ HP IF LAT LBS. LRA MBH MAX. MCA MFR
AIR CONDITIONING ACCESS DOOR AIR EXTRACTOR ABOVE FINISHED FLOOR ACOUSTICAL LINING BACKDRAFT DAMPER BRAKE HORSEPOWER BOTTOM OF DUCT CO2 SENSOR CONDENSATE DRAIN CUBIC FEET PER MINUTE CEILING EXHAUST FAN CENTERLINE DRY BULB DOOR LOUVER DOWN EXHAUST AIR EXHAUST AIR LOUVER ENTERING AIR TEMPERATURE EXHAUST FAN EXISTING EXHAUST GRILLE EXTERNAL STATIC PRESSURE DEGREES FAHRENHEIT FRESH AIR FRESH AIR LOUVER FLEXIBLE CONNECTION FIRE DAMPER FIRE/SMOKE DAMPER FEET PER MINUTE FULL LOAD AMPS FOOT OR FEET GAUGE GALVANIZED IRON GALVANIZED SHEET METAL HEATING & VENTILATION HERTZ HORSE POWER INDOOR FAN LEAVING AIR TEMPERATURE POUNDS LOCK ROTOR AMPS THOUSAND BTU PER HOUR MAXIMUM MINIMUM CIRCUIT AMPACITY MANUFACTURER
MIN. MOCP M MVD (N) OBD OC OPNG. OSA OSH φ POC QTY RA RD REF RH RL RPM RR(G) RS S SD SM SA SD(R)(G) SS SW
MINIMUM MAXIMUM OVER CURRENT PROTECTION MOTORIZED DAMPER MANUAL VOLUME DAMPER NEW OPPOSED BLADE DAMPER ON CENTER OPENING OUTSIDE AIR OUTSIDE AIR HOOD PHASE POINT OF CONNECTION QUANTITY RETURN AIR RETURN DIFFUSER ROOF EXHAUST FAN RADIANT HEATER REFRIGERANT LIQUID REVOLUTION PER MINUTE RETURN REGISTER (GRILLE) REFRIGERANT SUCTION TEMPERATURE SENSOR SMOKE DETECTOR SHEET METAL SUPPLY AIR SUPPLY DIFFUSER (REGISTER) (GRILLE) STAINLESS STEEL WALL SWITCH
T TBD TCP TEMP. TD TG TSP TV TYP UCD UTR V VAV VFD
THERMOSTAT TO BE DETERMINED TEMPERATURE CONTROL PANEL TEMPERATURE TRANSFER DUCT TRANSFER GRILLE TOTAL STATIC PRESSURE TURNING VANES TYPICAL UNDERCUT DOORS UP THRU ROOF VOLTS VARIABLE AIR VOLUME VARIABLE FREQUENCY DRIVE
W/ WB WT.
WITH WET BULB WEIGHT
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2015
AGENCY
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
FLS
SS
DATE
TITLE
SYMBOLS, NOTES & SCHEDULES SHEET
M-001
2
3
4
5
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
7
8
D
4
5
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
6
PETERS engineering
R. T I C HE
SE
AN
M31176 EXP. 12/31/19 ME
TE
C
CHAN I CA
OF CA L
L
I
A
S
TA
I NEER
REG I S T
PRO F E S S I ONA L
ED
R NO
ER
consulting mechanical and electrical engineers
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
N I F OR
4/16/2019 3:44:22 PM
1
2
3 SEAL SEE
D
D A RCH SE I E N A N McM TE H U T A
CT Y R RT
LI JO C N
1 M-113
AREA A
E
N
EN . 08 - 3 1 - 1 O F OF CALI 9
A
R E
R
ST T
IA
C23603
PROJECT C
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS F
7667 FOLSOM BLVD., SACRAMENTO, CA 95826
DN
CLIENT
DN
G
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
UP DN
ISSUED MARK
DATE
DESCRIPTION
H
AREA B
I
SEE 1 M-113
B
J
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2015
AGENCY
1 C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
M-112
MECHANICAL FLOOR PLAN - LEVEL 2 - OVERALL 1/16" = 1'-0"
KEY PLAN
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
A
SS
DATE A
TITLE
B
PLAN NORTH
4/16/2019 3:44:22 PM
FLS
FLOOR PLAN LEVEL 2 OVERALL SHEET
M-112
2"
1
2
3
4
5
1. PROVIDE CONICAL FITTINGS FROM ROUND TO RECTANGULAR DUCT CONNECTIONS. 2. PROVIDE SHOE FITTING AT ALL RECTANGULAR TO RECTANGULAR DUCT BRANCHES 3. FLEXIBLE DUCT IS LIMITED TO 5'-0" IN LENGTH. 4. PROVIDE MANUAL VOLUME DAMPER AT EVERY BRANCH DUCT. 5. PROVIDE TURNING VANES AT ALL RECTANGULAR DUCTWORK WITH 90° ELBOWS 6. ALL ACCESS TO BE MAINTAINED. NO DUCTS OR PIPING SHALL BE LOCATED IN THE CLEARANCE AREA. 7. DUCT ROUTING SHOWN IS DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL PROVIDE DETAILED SHOP DRAWINGS THAT COORDINATE WITH TRUSS MANUFACTURER, STRUCTRUAL ELEMENTS, PIPING AND ALL CEILING APPURTENANCES ABOVE CEILING PRIOR TO CONSTRUCTION. 8. DRAWINGS SHOWN ARE BASED ON ASBUILT DRAWINGS. CONTRACTOR IS RESPONSIBLE FOR COORDINATE FIELD CONDITIONS WITH EXISTING EQUIPMENT, DUCTWORK, PIPES, LIGHTING, STRUCTURAL ELEMENTS, ETC. 9. THE RETURN AIR SYSTEM SHALL UTILIZE THE EXISTING RETURN AIR PLENUM.
2400
PT OFFICE 1
2306B
EXISTING RETURN DUCT ABOVE CEILING.
2
CONNECT NEW 16"ø DUCT TO EXISTING.
3
MANUAL VOLUME DAMPER (TYP) AT ALL BRANCH DUCTS.
4
CONNECT NEW 20"ø DUCT TO EXISTING
5
SUPPLY DIFFUSER, SEE DETAIL 1/M-001. TYPICAL.
6
RETURN AIR BOOT. SEE DETAIL 2/M-001. TYPICAL.
7
8"ø ACOUTICALLY LINED DUCT. TERMINATE ABOVE AUDIOLOGY LAB 2603 WITH 1/4" WIRE MESH OVER OPENING.
8
COVER OPENING OF RETURN DUCT WITH 1/4" WIRE MESH
9
ROUTE DUCTWORK TIGHT TO UNDERSIDE OF ROOF FRAMING MEMBERS, FIELD COORDINATE DUCT ROUTING WITH STRUCTURAL MEMBERS, PIPING, SUPPORTS, LIGHT FIXTURES, ETC. SEE DETAIL 3 & 4/M0.1, TYPICAL.
SERV CLOS.
2401A
(E) SENSOR VAV-2-10
CLASSROOM PT OFFICE
2604
S01 315 CFM
2306A AUDIOLOGY LAB
T
8
FSD (E)
S01 315 CFM R01 635 CFM
3
2601
16"x12" AL
14"ø
TA
S
S02 170 CFM
SUPPLY DIFFUSER SCHEDULE
S02 180 CFM
ID# S01 S02 S03
AUDIOLOGY LAB 16"ø
(E) 16"ø
10"ø
2
(E) 52"x24 SA
R02 170 CFM
R02 170 CFM 8"ø AL
2603
8"ø AL
Type SD-L SD-L SD-L
Neck Size 10"x10" 8"x8" 14"x14"
D A RCH SE I E N A N McM TE H U T A
2602
2309
RETURN GRILLE SCHEDULE Neck Size 18"x18" 10"x10" 22"x22"
C23603
Duct Size 16"x16"AL 8"øAL 22"x22"
T
A
CORRIDOR
Type RG-L RG-L RG-L
ST
ID# R01 R02 R03
1
F
AUXILLARY OBSERVATION
LI JO C N
FSD (E)
AUDIOLOGY LAB
CT Y R RT
2305
I
SEAL
7
CORRIDOR
OF CA L
L
N I F OR
4/16/2019 3:44:24 PM
Duct Size 10"ø 8"ø 14"ø
7
AUDIO LAB - CONSULT
CHAN I CA
R E
IA
(E) VAV 2-10 (E) 12"ø
ME
TE
N
2305A
S02 170 CFM
EN . 08 - 3 1 - 1 O F OF CALI 9
8"ø AL
R. T I C HE
AN
M31176 EXP. 12/31/19
7
AUDIO LAB TEST BOOTH
PRO F E S S I ONA L
ED
I NEER
E
consulting mechanical and electrical engineers
R NO
R02 180 CFM
PETERS engineering
REG I S T
9
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
A
2401
1
ER
WAITING
KEYED NOTES:
R
D
SERV DESK
10. A MINIMUM OF 72 HOURS’ NOTICE IS REQUIRED FOR ANY TESTING AND/OR INSPECTION
8
SE
7
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
SHEET NOTES:
2404K
DN
2320
PROJECT
C
OBSERVATION STAIR NO. 2
2319
2504 DN
UNASSIGNED
UNASSIGNED
2304B
2304
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
GENDER NEUTRAL RESTROOM
2321
7667 FOLSOM BLVD., SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
G
(E) SENSOR VAV-2-14
T
VAV (E) 2-14
CORRIDOR
S03 610 CFM
20"ø
2312
ELEV NO.1
ELEV NO.2
101
102
STAIR NO.1
ISSUED
2404J
MARK
4 22"x18" AL
THERAPY
6
2203O
DATE
DESCRIPTION
LOBBY S03 610 CFM
20"ø R03 1220 CFM
1000
H 16"ø
LG THERAPY
9
5
22"x18" AL
2204B B 6
R03 1220 CFM
S03 610 CFM COMPUTER LAB
2204
S03 610 CFM
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2015
I
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
AGENCY
1 M-113
PARTIAL FLOOR PLAN - LEVEL 2 - AREA A & B - MECHANICAL 1/8" = 1'-0"
KEY PLAN
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
A
SS
DATE A
TITLE
B
PLAN NORTH
4/16/2019 3:44:24 PM
FLS
PARTIAL FLOOR PLAN MECHANICAL SHEET
M-113
4
ADEQUATELY STRAP AND SUPPORT ALL CONDUIT WORK PER CEC. IN GENERAL, SUPPORT ALL CONDUIT WITHIN THREE FEET (3') OF OUTLET BOX, CABINET OR PANEL AND MAXIMUM TEN FEET (10') ON CENTER THEREAFTER.
THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT THE ATTACHMENT NEED NOT BE DETAILED ON THE PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING AND CONDUIT.
4.
CORE BORE SHALL BE 1" DIAMETER LARGER THAN EACH CONDUIT. SPACE CONDUIT HOLES 3" APART. SEAL AROUND CONDUIT WITH NON-SHRINK, NON-METALLIC GROUT.
5.
ALL CONDUCTORS INSTALLED IN PANELBOARDS SHALL BE TRAINED, LACED, AND INSTALLED WITH PHASE TAPE ON ALL CONDUCTORS.
A. B.
COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. COMPONENTS WEIGHING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.
6.
7.
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE OR STRUCTURAL ENGINEER DELEGATED RESPONSIBILITY AND THE DSA DISTRICT STRUCTURAL ENGINEER. THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE REQUIREMENTS.
D
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE
LABEL DEVICES (I.E. RECEPTACLES, ETC.) ON EACH COVER PLATE IDENTIFYING CIRCUIT AND PANEL DEVICE IS CONNECTED TO. CLEAN ALL EXTERIOR AND INTERIOR SURFACES OF PANELS AND ALL MATERIAL AND METAL SHAVINGS FROM PANEL AND CABINET INTERIORS. ALL OPENINGS SHALL BE SEALED AND APPLY TOUCH-UP SPRAY PAINT WHERE NEEDED.
8.
FIELD COORDINATE DEVICE LOCATIONS PRIOR TO ROUGH-IN.
9.
INSTALLATION SHALL COMPLY WITH CEC 210.4 - EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH CIRCUIT ORIGINATES. THEREFORE ANY CIRCUIT SHARING A COMMON NEUTRAL SHALL BE CAPABLE OF SIMULTANEOUS DISCONNECT OR DEDICATED NEUTRALS SHALL BE INSTALLED.
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-10 SECTION 13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.5.6, 13.6.7, 13.6.8, AND 2016 CBC, SECTIONS 1616A.1.24, 1616A.1.25 AND 1616A.1.26.
10. SUPPORT ENCLOSURES, BOXES AND CONDUIT INSTALLATIONS PER CEC 314.23 (A) THROUGH (H).
THE METHOD OF SHOWING BRACING AND ATTACHMENTS TO THE STRUCTURE FOR THE IDENTIFIED DISTRIBUTION SYSTEM ARE AS NOTED BELOW. WHEN BRACING AND ATTACHMENTS ARE BASED ON A PREAPPROVED INSTALLATION GUIDE (E.G., SMACNA OR OSHPD OPM), COPIES OF THE BRACING SYSTEM INSTALLATION GUIDE OR MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF AND DURING THE HANGING AND BRACING OF THE DISTRIBUTION SYSTEMS. THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.
11. SEAL CONDUIT OPENINGS THROUGH WALLS AND CEILINGS. INSTALL ESCUTCHEON PLATES AT BUILDING INTERIOR. WHERE EQUIPMENT IS INSTALLED ON THE EXTERIOR WALL, STUB CONDUITS THROUGH WALL AND SEAL CONDUIT OPENINGS, THEN INSTALL EXTERIOR EQUIPMENT. ALSO, SEAL AROUND THE PERIMETER EDGE OF THE EQUIPMENT ENCLOSURE BETWEEN THE ENCLOSURE AND BUILDING.
MECHANICAL PIPING (MP), MECHANICAL DUCTS (MD), PLUMBING PIING (PP), ELECTRICAL DISTRIBUTION SYSTEMS (E):
12. CONDUITS INSTALLED ON ROOF AND BUILDING EXTERIOR SHALL BE RIGID GALV. STEEL (HEAVY WALL) WITH THREADED FITTINGS. CONDUIT AND WALL TO BE PAINTED OUT TO MATCH EXTERIOR FINISH.
MP
PP
E
OPTION 1:
DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND DETAILS
MP MD PP #____________.
E
OPTION 2:
SHALL COMPLY WITH THE APPLICABLE OSHPD PRE-APPROVAL (OPM #)
MP
MD
MD
PP OPTION 3:
13. SPLICES AND TERMINALS SHALL BE COMPRESSION TYPE OF SEAMLESS PURE COPPER, TIN PLATED, LONG BARREL (TERMINALS WITH TWO-HOLE PAD AND INSPECTION WINDOW WITH NEMA DRILLING), AS MANUFACTURED BY BURNDY TYPE YS, YAZ-2N OR EQUAL. CLEAN ALL SURFACES AND INSTALL WITH OXIDE INHIBITING COMPOUND, BURNDY PENETROX-E OR EQUAL. APPLY COMPOUND BETWEEN BUS AND LUG PAD AND BETWEEN CONDUCTOR AND LUG BARREL. INSTALL COMPRESSION CONNECTORS WITH 360° CIRCUMFERENTIAL COMPRESSION DYE, BURNDY HYPRESS OR EQUAL. THE INDENTER OR OTHER TYPE TOOLS WILL NOT BE ACCEPTABLE.
SHALL COMPLY WITH THE SMACNA SEISMIC RESTRAINT MANUAL, OSHPD EDITION (2009), INCLUDING ANY ADDENDA. FASTENERS AND OTHER ATTACHMENTS NOT SPECIFICALLY IDENTIFIED IN THE SMACNA SEISMIC RESTRAINT MANUAL, OSHPD EDITION, ARE DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND DETAILS. THE DETAILS SHALL ACCOUNT FOR THE APPLICABLE SEISMIC HAZARD LEVEL ___ AND CONNECTION LEVEL ___ FOR THE PROJECT AND CONDITIONS.
C 16. FUSES SHALL BE PROVIDED AND INSTALLED AS PER UNIT NAMEPLATE DATA ON THE EQUIPMENT PROVIDED. 17. VERIFY CEILING TYPES PRIOR TO ORDERING LUMINAIRES. CONFIRM THAT FEATURES DESCRIBED IN THE SPECIFICATION OF THE LUMINAIRE IS INCLUDED AS WELL AS PART NUMBERS LISTED ON SCHEDULE IN THE SUBMITTAL PACKAGE. NOTED DISCREPANCIES SHALL BE CLARIFIED WITH ENGINEER PRIOR TO BID.
NL NO, # NTS OC. P PB PFB
18. WIRING DEVICES AND COVER PLATES SHALL BE PROVIDED IN COLOR SELECTED BY ARCHITECT. THE COLOR OF THE WIRING DEVICE AND COVER PLATE SHALL BE THE SAME. 19. REINSTALL EXISTING ELECTRICAL INSTALLATIONS DISTURBED. CERTAIN EXISTING ELECTRICAL INSTALLATIONS MAY BE LOCATED IN WALLS, CEILINGS OR FLOORS THAT ARE TO BE REMOVED AND ARE ESSENTIAL FOR THE OPERATION OF OTHER REMAINING INSTALLATIONS. WHERE THIS CONDITIONS OCCURS, PROVIDE A NEW EXTENSION OF ORIGINAL CIRCUITS, RACEWAYS, EQUIPMENT AND OUTLETS TO RETAIN SERVICE CONTINUITY. INSTALLATIONS SHALL BE CONCEALED IN FINISHED AREAS.
PFCT PH, Ø PLYWD PNL PR PVC (R) REQ'D RM RMC (RR) SPEC STC SQ SW TEL TTB TYP UG UON V WP WT W W/ XFMR &
20. PROVIDE "LOCK-ON" DEVICE FOR ALL CIRCUIT BREAKERS ON EMERGENCY DEDICATED CIRCUITS. 21. DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC. CONTRACTOR SHALL ACCEPT RESPONSIBILITY IN FAMILIARIZING THEMSELVES WITH ARCHITECTURAL AND STRUCTURAL CONDITIONS ALONG WITH INHERENT SPACE LIMITATIONS. WITH THAT UNDERSTANDING SHALL PROVIDE ALL ITEMS OF LABOR, MATERIALS AND TOOLS REQUIRED TO PROVIDE A COMPLETE INSTALLATION. 22. SWITCHED/CONTROLLED RECEPTACLES SHALL BE PERMANENTLY MARKED PER THE CALIFORNIA ENERGY CODE. MARKING SHALL BE AS PROVIDED BY THE MANUFACTURER OF THE RECEPTACLE, STAMPED INTO THE FACE. IE: LEVITON #5362-1PW OR EQUAL. SYMBOL SHALL BE OF CONTRASTING COLOR TO THE DEVICE. 23. DATA SHEETS FOR ALL ELECTRICAL AND LOW VOLTAGE EQUIPMENT TO BE PROVIDED IN THIS PROJECT SHALL BE SUBMITTED AND REVIEWED FOR APPROVAL. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL SUBMITTAL REQUIREMENTS. 24. SHOP DRAWINGS FOR ALL ELECTRICAL AND LOW VOLTAGE SYSTEMS, INCLUDING BUT NOT LIMITED TO LIGHTING CONTROLS, SECURITY, AND COMMUNICATIONS SYSTEMS, SHALL BE SUBMITTED AND REVIEWED FOR APPROVAL. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL SUBMITTAL REQUIREMENTS.
LED, FLUORESCENT FIXTURE - WALL MOUNTED EXIT LIGHT FIXTURE SHADING INDICATES FIXTURE WITH LAMP(S) ON EMERGENCY CIRCUIT "MASTER" FIXTURE "SATELLITE" FIXTURE PRE-WIRED FIXTURE WHIP INCLUDED AS PART OF FIXTURE
J
SINGLE POLE SWITCH
2
TWO POLE SWITCH
3
THREE WAY SWITCH
K
KEYED SWITCH
LV
LOW VOLTAGE SWITCH
M
MANUAL MOTOR CONTROL SWITCH
OS WALL MOUNTED OCCUPANCY AUTO-OFF LIGHT SWITCH OS DIMMER SWITCH WITH OCCUPANCY SENSOR, LINE VOLTAGE DIMMER SWITCH, LOW VOLTAGE OS
CEILING MOUNTED OCCUPANCY AUTO-OFF LIGHT SWITCH. INSTALL PER MANUFACTURER REQUIREMENTS.
DL
CEILING MOUNTED DAY LIGHT SENSOR INSTALL PER MANUFACTURER REQUIREMENTS.
RC
ROOM CONTROLLER INSTALL PER MANUFACTURER REQUIREMENTS.
F
consulting mechanical and electrical engineers
FUSED DISCONNECT SWITCH
DOUBLE DUPLEX CONVENIENCE OUTLET
GROUND FAULT CIRCUIT INTERRUPTER DOUBLE DUPLEX OUTLET
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt 4/23/2019 3:19:20 PM
MODEL
LAMP
(E) A1 A1E
1 VA LITHONIA LITHONIA
A2 A2E
LITHONIA LITHONIA
X1
LITHONIA
2BLT4-30L-ADP-EZ1-LP835-N80 2BLT4-30L-ADP-EZ1-LP835-N80E10WLCP 2BLT4-40L-ADP-EZ1-LP835-N80 2BLT4-40L-ADP-EZ1-LP835-N80E10WLCP LQM-S-W-3-R-120/277-ELM-SD
LED LED
30 VA 30 VA
O R. ROMA
EL
TE
EC TR I CA
OF CA L
L
N I F OR
I
4/23/2019 3:19:20 PM
DOUBLE DUPLEX OUTLET WITH: ONE DUPLEX CONVENIENCE OUTLET ONE CONTROLLED DUPLEX OUTLET SPECIAL OUTLET TO MATCH CAP PROVIDED WITH MACHINE FLUSH FLOOR BOX OR "POKE-THRU" UNIT EQUIPPED WITH FLUSH OR PEDESTAL DUPLEX RECEPTACLE AND VOICE/DATA OUTLETS AS NOTED, OR REFER TO SCHEDULE ON DRAWINGS. TRANSFORMER JUNCTION BOX, SIZE AS REQUIRED BY CODE
J J
SEAL D A RCH SE I E N A N McM TE H U T A
C23603
FLEX CONNECTION TO FIXTURE TELEPHONE OUTLET
T
DATA OUTLET
R E
EN . 08 - 3 1 - 1 O F OF CALI
TELEPHONE/DATA OUTLET PANELBOARD, RECESSED MOUNTED
PROJECT
PANELBOARD, SURFACE MOUNTED MAIN SWITCHBOARD TERMINAL CABINET, RECESSED MOUNTED TERMINAL CABINET, SURFACE MOUNTED HOMERUN TO PANELBOARD OR RESPECTIVE TERMINAL CONDUIT RUN CONCEALED IN CEILING OR WALL, SEE NOTE BELOW CONDUIT RUN UNDERGROUND OR UNDER FLOOR INSULATED GREEN GROUND CONDUCTOR EXISTING EQUIPMENT, LIGHTING, DEVICES, CONDUIT, WIRING, ETC., ARE SHOWN LIGHT. NEW OR RELOCATED EQUIPMENT, LIGHTING, DEVICES, CONDUIT, WIRING, ETC., ARE SHOWN DARK. X
X
1
1
AC 1 A E1 (1)1-1/2"C
EXISTING ELECTRICAL EQUIPMENT TO BE REMOVED SYMBOLS REFERRING TO KEYED NOTES ON SAME SHEET
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD., SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
MECHANICAL EQUIPMENT BY OTHERS, CONNECTED BY ELECTRICAL CONTRACTOR DETAIL DESIGNATION, "A" SIGNIFIES DETAIL, "E-1" SIGNIFIES SHEET NUMBER INDICATES SIZE OF CONDUIT = ONE AND ONE HALF INCH CONDUIT NUMBER WITHIN PARENTHESIS INDICATES QUANTITY OF CONDUITS
ISSUED
NOTES:
MARK 1.
MOUNT SWITCH BOXES AT +48" TO TOP OF BOX UNLESS OTHERWISE NOTED.
2.
MOUNT OUTLET BOXES AT +15" TO BOTTOM OF BOX UNLESS OTHERWISE NOTED.
3.
"A" ADJACENT TO OUTLET INDICATES OUTLET BOX TO BE MOUNTED ABOVE COUNTER. COORDINATE WITH COUNTER HEIGHT AND DEPTH PRIOR TO ROUGH IN.
4.
NO CROSSBARS ON CONDUIT RUN INDICATES MINIMUM 3/4" CONDUIT, TWO #12 CU CONDUCTORS PLUS 1#12 CU GND. CROSSBARS INDICATE NUMBER OF #12 CU CONDUCTORS IN CONDUIT. CONDUCTOR SIZES OTHER THAN #12 NOTED ON DRAWINGS. INCREASE CONDUIT SIZE AS REQUIRED TO ACCOMMODATE C.E.C. WIRE FILL REQUIREMENTS. INCLUDE ADDITIONAL BOND WIRE IN ALL PVC AND FLEXIBLE CONDUIT. LONG CROSSBAR INDICATES NEUTRAL CONDUCTOR, SHORT CROSSBARS INDICATE PHASE CONDUCTORS.
5.
MINIMUM 20A BRANCH CIRCUIT CU CONDUCTOR SIZES SHALL BE AS FOLLOWS, AS FIELD MEASURED, BASED UPON MEASURED FIELD ROUTING LENGTHS. MINIMUM CONDUIT SIZE SHALL BE INCREASED TO ACCOMMODATE MAXIMUM 40% CONDUCTOR FILL OF THE BRANCH CIRCUIT CONDUCTORS. WHERE NECESSARY, PROVIDE A JUNCTION BOX AT ACCESSIBLE CEILING SPACE TO CONVERT THE LAST 15 FEET OF CONDUCTOR TO #10 AWG TO ACCOMMODATE TERMINATION OF WIRING DEVICES, LIGHTING FIXTURES, CIRCUIT BREAKER, ETC.
6.
INSTALL CU GROUND CONDUCTOR IN ALL BRANCH CIRCUITS FOR LIGHT FIXTURES AND POWER DEVICES.
DATE
DESCRIPTION
MANAGEMENT
Lighting Fixture Schedule MANUFACTURER
IN
E17247 EXP. 6/30/20 TA
SPLIT DUPLEX OUTLET WITH: ONE CONVENIENCE OUTLET ONE CONTROLLED OUTLET
120V BRANCH CIRCUIT VOLT DROP CONDUCTOR LENGTH CHART
TYPE
PRO F E S S I ONA L
ED
GROUND FAULT CIRCUIT INTERRUPTER DUPLEX OUTLET
B
FIXTURE WATTS
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
PETERS engineering
DUPLEX CONVENIENCE OUTLET
25. WIRING METHODS FOR CONDUCTORS AND CONDUITS LOCATED IN RETURN AIR PLENUM SPACE SHALL COMPLY WITH 2016 CEC ARTICLE 300.22. 26. MATERIALS EXPOSED WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME-SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED RATING OF NOT MORE THAN 50 AND THAT ALL ELECTRICAL, ALARM, TELECOMMUNICATION, COMPUTER, ETC. WIRING WITHIN THE RETURN AIR PLENUMS SHALL BE RATED FOR THE USE IN PLENUMS. 2016 CMC SECTION 602.2 AND 2016 CEC ART. 300.22
a
PAIR OF TANDEM WIRED FLUORESCENT GRID FIXTURES
CT Y R RT
15. COORDINATE EQUIPMENT LOCATIONS, CONTROL AND POWER WIRING REQUIREMENTS AND CONNECT POINTS WITH ALL APPLICABLE DISCIPLINES.
LED, FLUORESCENT FIXTURE - SEE FIXTURE SCHEDULE FOR MOUNTING
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
A
ISO J-BOX KCMIL KVA KW LC LV MCM MECH MDP MH MISC MSB (N) NIC NIES
LED, FLUORESCENT OR HID FIXTURE - CEILING RECESSED
ST
14. INSTALL 'MECHANICALLY FASTENED PHENOLIC NAMEPLATE WITH WHITE LETTERING ON BLACK BACKGROUND ON ALL EQUIPMENT, INCLUDING PULL BOXES, WITH DESCRIPTION INDICATED ON DRAWINGS. NAMEPLATES SHALL READ EXACTLY AS DESCRIBED ON THE DRAWINGS. IN GENERAL NAMEPLATE LETTERING SIZE SHALL BE 3/16" HIGH FOR ALL NAMEPLATES SERVING FEEDER AND BRANCH CIRCUIT BREAKERS. ON MAIN SERVICE PANEL, DISTRIBUTION PANELS AND ALL OTHER NAMEPLATES LETTERING SHALL BE 1/4" HIGH. 14.1. ALL SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, VFD'S, MOTORS, JUNCTION BOXES, PULL BOXES, DISCONNECT SWITCHES, ETC., SHALL BE MARKED TO INDICATE EACH DEVICE OR EQUIPMENT WHERE THE POWER ORIGINATES PER CEC 408.4, FIELD IDENTIFICATION REQUIRED, (B) SOURCE OF SUPPLY.
APPLIES TO ALL FIXTURES
A
3.
3.
CONTROLLED BY SWITCH "a" CONNECTED TO CIRCUIT 2 FIXTURE TYPE A2 LED, FLUORESCENT OR HID FIXTURE - WALL MOUNTED
IA
PROTECT EXISTING EQUIPMENT AND FURNISHINGS FROM ANY DAMAGE DUE TO DUST, MOISTURE OR CONTACT WITH WORK CREW OR MATERIALS.
A2
LED, FLUORESCENT OR HID FIXTURE
ER
2.
2a
G
ALL PERMANENT EQUIPMENT AND COMPONENTS. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G. HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS OR WATER. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS OR HAS A CENTER OF MASS LOCATED 4 FEET OR MORE ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.
AT AMPERE ALTERNATING CURRENT AIR CONDITIONING AMP FRAME ABOVE FINISHED FLOOR AMPERES INTERRUPTING CAPACITY AMP TRIP SETTING AMERICAN WIRE GAUGE BARE COPPER BOARD BELOW FINISHED CEILING BREAKER BUILDING BOOSTER POWER SUPPLY CONDUIT CIRCUIT BREAKER CIRCUIT CEILING CONDUIT ONLY, WITH PULL LINE CONTINUOUS COPPER METALLIC COLD WATER PIPE DEMOLISH DIRECT CURRENT DISCONNECT DISTRIBUTION PANEL EXISTING EACH WITH EACH EVENING LIGHT ELECTRIC EMERGENCY ELECTRICAL METALLIC TUBING END OF LINE DEVICE EQUIPMENT EXISTING RELOCATED ELECTRICAL WATER COOLER ELECTRIC WATER HEATER FUTURE FIRE ALARM CONTROL PANEL FIRE ALARM EXTENDER PANEL FIRE ALARM TERMINAL CABINET FURNISHED BY OTHERS FLUORESCENT FOOT GAUGE GROUND FAULT CIRCUIT INTERRUPT GROUND METALLIC GAS PIPE GYPSUM HIGH INTENSITY DISCHARGE HORSE POWER HEIGHT HERTZ INTERMEDIATE METALLIC CONDUIT INCH SHORT CIRCUIT CURRENT (RMS SYMMETRICAL) ISOLATED JUNCTION BOX THOUSAND CIRCULAR MILLS KILO VOLT AMP KILOWATT LIGHTING CONTROL PANEL LOW VOLTAGE THOUSAND CIRCULAR MILLS MECHANICAL MAIN DISTRIBUTION PANEL METAL HALIDE MISCELLANEOUS MAIN SWITCHBOARD NEW NOT IN CONTRACT NOT IN ELECTRICAL SECTION OF THESE PLANS & SPECS. NIGHT LIGHT NUMBER NOT TO SCALE ON CENTER POLE PULL BOX PROVISION FOR FUTURE BREAKER W/ MOUNTING HARDWARE PROVISION FOR FUTURE CURRENT TRANSFORMER PHASE PLYWOOD PANEL PAIR POLYVINYL CHLORIDE CONDUIT RELOCATE/RELOCATED REQUIRED ROOM RIGID METAL CONDUIT REMOVE AND REPLACE SPECIFICATION SIGNAL TERMINAL CABINET SQUARE SWITCH TELEPHONE TELEPHONE TERMINAL BOARD TYPICAL UNDERGROUND UNLESS OTHERWISE NOTED VOLTS WEATHERPROOF WEIGHT WATT WITH TRANSFORMER AND
N
1. 2.
@ A AC A/C AF AFF AIC AT AWG BC BD BFC BRKR BLDG BPS C C/B CIRC CLG CO CONT CU CWP (D) DC DISC DP (E) E/W EA EL ELEC EM EMT EOL EQUIP (ER) EWC EWH (F) FACP FAEP FATC FBO FLUOR FT GA GFCI GND GP GYP HID HP HT HZ IMC IN ISC
PLANS ARE NOT FOR CONSTRUCTION UNTIL APPROVED BY THE AUTHORITY HAVING JURISDICTION. THE CONTRACTOR SHALL NOT ORDER ANY MATERIALS OR INSTALL ANY EQUIPMENT, PIPING, ETC. UNTIL PLANS ARE APPROVED BY THE AUTHORITY HAVING JURISDICTION.
REG I S T
1.
9
ALL MECHANICAL, PLUMBING AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2016 CBC, SECTIONS 1616A.1.18 THROUGH 1616A.1.26 AND ASCE 7-10 CHAPTER 13, 26 AND 30.
SYMBOLS LIST
I NEER
ABBREVIATION LIST
NO
GENERAL NOTES
S
MEP COMPONENT ANCHORAGE NOTE
5
R
3
LI JO C N
2
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
MOUNTING SURFACE RECESSED RECESSED
LED LED
34 VA 34 VA
RECESSED RECESSED
LED
1 VA
SURFACE
DESCRIPTION LED EXIT LIGHT W/ EMERGENCY BATTERY PACK 2'x4' LED DIMMABLE TROFFER 2'x4' LED DIMMABLE TROFFER W/ EMERGENCY BATTERY PACK 2'x4' LED DIMMABLE TROFFER 2'x4' LED DIMMABLE TROFFER W/ EMERGENCY BATTERY PACK LED EXIT LIGHT W/ EMERGENCY BATTERY PACK
NOTES: A. COLOR TEMPERATURE FOR LED LAMPS SHALL BE 3500K UNLESS OTHERWISE NOTED. B. LUMINAIRES IDENTIFIED WITH "E" SUFFIX SHALL BE EQUIPPED WITH AN EMERGENCY BATTERY AND PROVIDE A MINIMUM OF 1400 LUMENS OUTPUT.
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LENGTH OF CONDUCTOR
LOAD IN VOLT AMPERES
#12
#10
#8
#6
#4
1200VA
74
121
183
284
434
1560VA
57
93
141
218
334
1800VA
49
81
122
189
289
1920VA
46
76
115
178
271
2340VA
X
62
94
146
223
2880VA 3000VA
X
51
76
118
181
X
48
73
114
174
3900VA
X
X
56
87
134
4800VA
X
X
46
71
108
LIONAKIS 2015
WIRE SIZE IN (GAUGE)
AGENCY
NOTES 1. THIS CHART IS FOR COPPER CONDUCTORS ONLY. 2. THIS CHART ASSUMES AN 80% POWER FACTOR AND STEEL RACEWAYS. 3. 2016 CALIFORNIA ENERGY CODE, 130.5(c) ALLOWS A MAXIMUM COMBINED VOLTAGE DROP OF 5%. THIS CHART ASSUMES A MAXIMUM DROP OF 3% FOR FEEDERS. THIS CHART PROVIDES THE MAXIMUM LENGTH OF CONDUCTORS FOR LESS THAN 2% VOLTAGE DROP ON A BRANCH CIRCUIT AT GIVEN VA LOAD. 4. USE WIRE SIZE FROM THIS CHART UNLESS OTHERWISE NOTED ON THE DRAWINGS. 5. FOR VA VALUES NOT SHOWN USE NEXT HIGHEST VALUE FROM THE CHART
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
FLS
SS
DATE A
TITLE
SYMBOLS, NOTES & SCHEDULES SHEET
E-001
2
3
4
5
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
PETERS engineering
G
IN
O R. ROMA
I NEER
REG I S T
PRO F E S S I ONA L
ED
NO
ER
consulting mechanical and electrical engineers
ENG
E17247 EXP. 6/30/20
S
TA
EL
TE
EC TR I CA
OF CA L
L
I
A
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
N I F OR
4/23/2019 3:19:23 PM
SEAL
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
N
EN . 08 - 3 1 - 1 O F OF CALI 9
A
R E
R
ST T
IA
C23603
PROJECT C
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD., SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
ISSUED MARK
DATE
DESCRIPTION
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2015
4/23/2019 3:19:23 PM
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
AGENCY
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
FLS
DATE A
TITLE
TITLE 24
SHEET
E-002
SS
2
3
4
5
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
7
8
D
4
5
6
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
PETERS engineering
G
REG I S T
2
O R. ROMA
E17247 EXP. 6/30/20
3
EL
TE
EC TR I CA
OF CA L
L
I
A
TA
S
1
IN
I NEER
C
PRO F E S S I ONA L
ED
NO
ER
consulting mechanical and electrical engineers
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
N I F OR
4/23/2019 3:19:27 PM
D SEAL
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
AREA A
IA
EN . 08 - 3 1 - 1 O F OF CALI
N
R E
9
A
T
R
ST
E
C23603
PROJECT C
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
F DN DN
TELECOM
7667 FOLSOM BLVD., SACRAMENTO, CA 95826
2211
CLIENT
G
UP DN
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
H
ISSUED
AREA B
MARK
DATE
DESCRIPTION
I
J
B
MANAGEMENT
1 E-112
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
ELECTRICAL FLOOR PLAN - LEVEL 2 - OVERALL
LIONAKIS 2015
1/16" = 1'-0"
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
AGENCY
KEY PLAN
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
A
SS
DATE A
TITLE
B
PLAN NORTH
4/23/2019 3:19:27 PM
FLS
FLOOR PLAN LEVEL 2 OVERALL SHEET
E-112
2"
1
2
3
4
DEMOLITION KEYED NOTES:
8 1
RECEPTACLE OUTLET TO BE DISCONNECTED AND REMOVED. TO BE RELOCATED.
2
RECEPTACLE OUTLET TO BE DISCONNECTED FROM EXISTING CIRCUIT. TO BE CONNECTED TO NEW DEDICATED CIRCUIT.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
GENERAL NOTES ~
1. A MINIMUM OF 72 HOURS’ NOTICE IS REQUIRED FOR ANY TESTING AND/OR INSPECTION
X 1
F
DN
D DN
2
PETERS engineering
F ~
X
X X
IN
O R. ROMA
I NEER
REG I S T
1
PRO F E S S I ONA L
ED
NO
ER
X X
G
G
consulting mechanical and electrical engineers
E17247 EXP. 6/30/20
S
TA
EL
TE
EC TR I CA
OF CA L
L
I
A
~
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
7
5
N I F OR
4/23/2019 3:19:30 PM
SEAL
1/8" = 1'-0"
D A RCH SE I E N A N McM TE H U T A
8 A
SERV DESK
WAITING
2401
2400
KEYED NOTES:
PT OFFICE 2
2306B
2
1
SERV CLOS.
C
EXISTING JUNCTION BOX ABOVE CEILING WITH 1"C.O. TO PANEL 'LF1'. DISCONNECT CONDUIT FROM PANEL 'LF1' AND EXTEND TO PANEL 'LE1'
2
DUPLEX RECEPTACLE OUTLET AND TV OUTLET MOUNTED AT +3'-6" AFF.
8
8
8
8
3
ELECTRICAL PLUGSTRIP WITH OUTLETS AT 24"O.C.. INSTALLED AND RUN ALONG TOP OF COUNTER BACKSPLASH.
4
FLUSH FLOOR DUPLEX RECEPTACLE OUTLET. WIREMOLD #RC7ATCBK POKETHRU, COMPLETE WITH PREWIRED DUPLEX RECEPTACLE AND FOUR BLANK TRACJACK MOUNTING INSERTS FOR UNUSED COMMUNICATION OPENINGS.
5
DUPLEX RECEPTACLE OUTLET RELOCATED TO NEW LOCATION SHOWN AND RECONNECT TO EXISTING CIRCUITRY.
6
NEW RECEPTACLE OUTLET CONNECTED TO EXISTING RECEPTACLE OUTLET USING EXISTING CIRCUITRY.
7
EXISTING RECEPTACLE OUTLET TO BE CONNECTED TO NEW DEDICATED CIRCUIT AS SHOWN.
8
MOUNT OUTLET AT DESK HEIGHT, +42". VERIFY HEIGHT IN FIELD.
9
JUNCTION BOX AT CEILING WITH 1" CONDUIT TO CORRIDOR FOR CAMERA. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH UNIVERSITY.
10
FIRE WRAP ELECTRICAL OUTLET THAT PENETRATES RATED CORRIDOR. SEE DETAIL 5/E-402.
4
CLASSROOM
1"C.O.
12
2604
10
10
PT OFFICE
2306A 10 'LE1'- 8,10 9
10
E
10
10
2
2305A
14
J 12
14
1"C.O.
12
J 6
8
4
8
12 4
14
14 AUDIOLOGY LAB
16 18
3
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
4
2
2 1"C.O.
2603
4
10
AUDIO LAB - CONSULT
4
'LE1'- 16,18
J
12
CORRIDOR
'LD'- 36
2309
F
5 AUDIOLOGY LAB 'LE1'- 2,4,6 2602
(E)
11
CORRIDOR AUXILLARY OBSERVATION
2404K
DN
2320 STAIR NO. 2
(E)PNL 'LF1'
B
(E)PNL 'LE1' (E)PNL 'LC'
GENDER NEUTRAL RESTROOM
2504 DN
'LE1'- 19
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
PENETRATION THROUGH FIRE WALLS WITH "F" OR "T" RATING. SEE DETAIL 4/E-402.
12
PROVIDE PORTABLE ASSISTIVE LISTENING SYSTEM - LISTEN TECHNOLOGIES LKS-4-A1 LISTENTALK PORTABLE ADA KIT. SYSTEM TO INCLUDE: • FOUR (4) LK-1 LISTENTALK TRANSCEIVERS • ONE (1) LA-451 HEADSET 1 (EAR SPEAKER W/BOOM MIC) • THREE (3) LA-401 UNIVERSAL EAR SPEAKER • FOUR (4) LA-445-BK BREAKAWAY LANYARD • TWO (2) LA-166 NECK LOOP • ONE (1) LA-423-01 4-PORT USB CHARGER • ONE (1) LA-436 MICROPHONE INPUT / HEADPHONE OUTPUT CABLE • ONE (1) LA-483 SOFT SHELL CASE 4
UNASSIGNED
UNASSIGNED
2304B
2304
ISSUED MARK
DATE
DESCRIPTION
PROVIDE ASSISTIVE LISTENING NOTIFICATION SIGNAGE KIT - LISTEN TECHNOLOGIES LA-304.
OBSERVATION
2319
11
1
'LE1'- 12,14
3
2305
CLIENT
9
AUDIOLOGY LAB
12
7667 FOLSOM BLVD., SACRAMENTO, CA 95826
10
12
2601
J
J
3
9
14
AUDIO LAB TEST BOOTH
J
4
14
EN . 08 - 3 1 - 1 O F OF CALI
PROJECT
2401A 8
R E
9
ST T
IA
C23603
R
7
CT Y R RT
LI JO C N
E-113
PARTIAL FLOOR PLAN - LEVEL 2 - AREA A - DEMOLITION
N
2
2321 (E)PNL 'LD'
7
(E)PNL 'LE' MANAGEMENT 11
(E)PNL 'LF' 11
(E)PNL 'HB'
~
~
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2015
G 5
6
20 (E)
101
102
AGENCY
1
20 'LE1'- 22,24,26
J
10
CORRIDOR
STAIR NO.1
22
2312
2404J 20
20
LOBBY
KEY PLAN
J
1000 24
THERAPY
2203O J
H
COMPUTER LAB
26
12
2204
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
J
'LE1'- 28,30,32 28
LG THERAPY
20
2204B
AC
J
A
FLS
SS
DATE
30
A
TITLE J
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
'LE1'- 20
PARTIAL FLOOR PLANS - POWER
32 B
I
4/23/2019 3:19:30 PM
ELEV NO.2
2
J
ELEV NO.1
PLAN NORTH
SHEET
1 E-113
PARTIAL FLOOR PLAN - LEVEL 2 - AREA A & B - POWER 1/8" = 1'-0"
E-113
2"
1
2
3
4
5
DEMOLITION KEYED NOTES: EXISTING LIGHT TO BE DISCONNECTED AND REMOVED. 1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
GENERAL NOTES 1. A MINIMUM OF 72 HOURS’ NOTICE IS REQUIRED FOR ANY TESTING AND/OR INSPECTION
7
D
G
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
PETERS engineering 1
X
consulting mechanical and electrical engineers
G
IN
O R. ROMA
I NEER
REG I S T
PRO F E S S I ONA L
ED
NO
ER
E17247 EXP. 6/30/20
S
TA
EL
TE
EC TR I CA
OF CA L
L
I
A
X
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
1
N I F OR
4/23/2019 3:19:34 PM
2 E-114
PARTIAL FLOOR PLAN - LEVEL 2 - AREA B - LIGHTING DEMOLITION 1/8" = 1'-0" SEAL
8
D A RCH SE I E N A N McM TE H U T A
CT Y R RT
LI JO C N
7
WAITING
2401
2400
2306B SERV CLOS.
(E) A1E a
A1
a
A1 J
PT OFFICE
2306A
J OS
A1E b
b
A1
J
A1
J OS
7
b
b
A1
a A1 b
b
a
PRIMARY SIDELIT DAYLIGHT ZONE.
2
SECONDARY SIDELIT DAYLIGHT ZONE.
3
EXISTING JUNCTION BOX WITH 1"C.O. TO PANEL 'HB'.
4
LIGHTING ROOM CONTROLLER, NLIGHT #NPP16D
5
WALL MOUNT DIMMER SWITCH, 2-CHANNEL, NLIGHT #NPODM-2P-DX-WH.
6
WALL MOUNT DIMMER SWITCH WITH OCCUPANCY SENSOR. NLIGHT #NWSXPDT-LV-DX-WH.
7667 FOLSOM BLVD., SACRAMENTO, CA 95826
b
7
CEILING MOUNT OCCUPANCY SENSOR. NLIGHT #NCMR-PDT-10.
CLIENT
8
CEILING MOUNT OCCUPANCY/DAYLIGHT SENSOR, NLIGHT #NCMR-PDT-10-ADCX.
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
5
2
RC
4
7
A1
PROJECT
1
2401A b
N
KEYED NOTES:
PT OFFICE
C
EN . 08 - 3 1 - 1 O F OF CALI 9
A
SERV DESK
R E
R
ST T
IA
C23603
A1
CLASSROOM
2604
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
E AUDIOLOGY LAB AUDIO LAB TEST BOOTH
A1
2305A
2602
A1
AUDIOLOGY LAB J
2601 A1
A1
A1
A1
A1
J
J
J
J
A1 J
AUDIOLOGY LAB
2603 ISSUED MARK
os AUDIO LAB - CONSULT
A1
6
2305
A1 6
os
A1 6
DATE
DESCRIPTION
A1 (E) J os
(E)
3
CORRIDOR
'HB'- 12
2309
F CORRIDOR AUXILLARY OBSERVATION
2404K
2320 OBSERVATION
2319 B
ELEC/TELE
GENDER NEUTRAL RESTROOM
2503
2321
STAIR NO. 2
UNASSIGNED
UNASSIGNED
2504
2304B
2304
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
CORRIDOR
2323
LIONAKIS 2015
G 4
X1 2 a b J (E)
5 C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
3
CORRIDOR
RC A2
101
102
AGENCY
J STAIR NO.1
2312
OS
A2E
2404J 8
KEY PLAN
A2 LOBBY
1000 THERAPY
2203O
A2
H
A2
J
FILE NO: 34-CSUS
J
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
A2
A2
LG THERAPY 2
2204B
OS
COMPUTER LAB
8
AC
A
2204 A2E
FLS
DATE
A J
1
A2
TITLE
J
A2
B
PLAN NORTH
PARTIAL FLOOR PLANS LIGHTING SHEET
1 E-114
PARTIAL FLOOR PLAN - LEVEL 2 - AREA A & B - LIGHTING 1/8" = 1'-0"
SS
A2
I
4/23/2019 3:19:34 PM
ELEV NO.2
A2
J
'HB'- 12
ELEV NO.1
E-114
2"
1
2
3
A.I.C. Rating: Mains Type: Mains Rating: MCB Rating:
Location: ELEC/TELE 2503 Supply From: Mounting: Surface Enclosure: 1
10kA MLO 100 A 100 A
10kA MLO 250 A 250 A
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
Notes:
Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A
Poles 1 1 1 1 1 1 1
(E) CU-1
20 A
2
RECEPT-SERVER [1] SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE
20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
1 1 1 1 1 1 1 1 1 1
20 A
1
A 720
B
C
1200 900
720 100
380
1920 380
900 400
200
900 980
1000 0
1000 0
1000
1000 0
0 0
0
0
0 0
8580 VA 72 A
0
6780 VA 57 A
0 0 6180 VA 52 A
Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
Circuit Description FLR RECEPT 2603 [1] RECEPTS- 2602 [1] PLUGMOLD- 2603 [1] RECEPTS- 2604 [1] RECEPTS- 2604 [1] RECEPTS- 2603 [1] RECEPTS- 2601 [1] PLUGMOLD- 2601 [1] PLUGMOLD- 2601 [1] RECEPTS- 2204 [1] 2204 LAB TABLE 1 [1] 2204 LAB TABLE 2 [1] 2204 LAB TABLE 3 [1] 2204 LAB TABLE 4 [1] 2204 LAB TABLE 5 [1] 2204 LAB TABLE 6 [1] SPARE SPARE SPARE 20 A SPARE 20 A SPARE
CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---
Poles 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ------Total Load: Total Amps:
SPACE SPACE
A 0
B 0
0
0
0
1102
0
3000
0
0
1500 2570
1950 0
0
0
0
0 0
0 0 0 0
C
0
1920
0 0
0 0
0
0
0 1500
0 0
0
0
0 0
3450 VA 12 A
0 0 0 4102 VA 15 A
5990 VA 22 A
Poles 1 1 1 --1 1 1 1 1 1 1 1 1 1 1 ------
Trip 20 A 20 A 20 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ----
Circuit Description (E)LIGHTS- STATE TEACHER (E)LIGHTS- STATE TEACHER EXISTING LOAD SPACE SPACE LIGHTS- COMP LAB / AUDIO [1] EXISTING LOAD (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS SPARE (E) LCC PMO (E) LIGHTS- MAIN ENTRANCE (E) LIGHTS- STATE TEACHER (E) LIGHTS- STATE TEACHER SPACE SPACE SPACE
--
SPACE
--
SPACE
CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
Demand Factor 0.00% 100.00% 97.62% 100.00%
Estimated Demand 0 VA 6000 VA 10250 VA 5040 VA
Panel Totals Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand:
Load Classification Lighting Spare
21540 VA 21290 VA 60 A 59 A
Notes: [1] REVISED OR NEW LOAD [2] PROVIDE UPDATED, TYPE-WRITTEN, PANEL SCHEDULES.
Connected Load 1102 VA 12440 VA
Demand Factor 125.00% 100.00%
Estimated Demand 1377 VA 12440 VA
2
200/3
225/3
3
4
225/3
225/3
5
6
200/3
60/3
7
8
225/3
60/3
9
10
225/3
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
UNDERGROUND PULL SECTION
PETERS engineering 90"
consulting mechanical and electrical engineers
225/3
11
12
225/3
500/3
13
14
225/3
15
16
175/3
17
18
225/3
600/3
Panel Totals
20
19
Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand:
METER & CT'S
PRO F E S S I ONA L
ED
IN
TA
EL
TE
175/3
13542 VA 13817 VA 16 A 17 A
O R. ROMA
E17247 EXP. 6/30/20
S
Connected Load 0 VA 6000 VA 10500 VA 5040 VA
1
M
Legend:
Load Classification Other Power Receptacle Spare
60/3
I NEER
Legend:
Circuit Description (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS (E) LIGHTS- HALLWAY SPACE SPACE
NO
20 A 1 Total Load: Total Amps:
1000
1000 0
0
720
900 0
0
1080
1080 980
180
900
Poles 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
ER
Circuit Description (E) RECEPTS- 2304 (E) RECEPTS- 2204A, CORR. (E) nLIGHT ADR EQUIP. RM2211 (E) PB52 (E) PB53 (E) DDC CONTROL PANEL (E) FIRE SMOKE DAMPER
REG I S T
D
A.I.C. Rating: Mains Type: Mains Rating: MCB Rating:
EC TR I CA
OF CA L
L
N I F OR
I
4/23/2019 3:19:38 PM
3000A MAIN SWITCH 38"
Notes: [1] REVISED OR NEW LOAD [2] PROVIDE UPDATED, TYPE-WRITTEN, PANEL SCHEDULES.
48"
42"
SEAL
36"
D A RCH SE I E N A N McM TE H U T A
MAIN SWITCHBOARD 'MSB' ELEVATION NONE
E-301
CT Y R RT
2
LI JO C N
Notes:
Volts: 480/277 Wye Phases: 3 Wires: 4
A
1"
Volts: 120/208 Wye Phases: 3 Wires: 4
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
Branch Panel: HB
Location: ELEC/TELE 2503 Supply From: Mounting: Surface Enclosure: 1
CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
5
G
Branch Panel: LE1
4
N
EN . 08 - 3 1 - 1 O F OF CALI 9
A
R E
R
ST T
IA
C23603
PROJECT C
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD., SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
KEYED NOTES: (E) UNDERGROUND TERMINATION LANDING LUGS
1
M
EXISTING PANEL USED IN THIS PROJECT.
(E) UTILITY METER
ISSUED MARK
DATE
DESCRIPTION
(E) 3000/3
S
(E) MAIN SWITCHBOARD 'MSB'
GFI
3000A BUS, 277/480VV, 3∅, 4W, 32,900AIC 1
(E) 60/3
2
3
(E) 200/3
4
(E) 225/3
5
(E) 225/3
6
(E) 225/3
7
(E) 200/3
8
(E) 60/3
(E) 225/3
9
10
(E) 60/3
11
(E) 225/3
(E) 225/3
12
(E) 225/3
13 15
(E) 500/3
14
16
(E) 225/3
(E) 175/3
17 19
(E) 600/3
18
20
(E) 225/3
(E) 175/3
N G
(E) T2LM
F
(E) COLD WATER PIPE BOND
(E) PANEL 'HE'
F
(E) PANEL 'HF'
112.5KVA
75KVA
(E) T3LP
30
25
(E) ELEV #2
(E) ELEV #1
75KVA
(E) ELEV FREIGHT
2ND FLR EAST
F
(E) 225/3
(E) PANEL 'HAA'
(E) PANEL 'HA'
(E) PANEL 'HD'
(E) MCC EAST
(E)T2LD (E) PANEL 'HB'
3#350MCM CU
(E) T1LA
(E) (2) 2-1/2"C., EA W/
(E) T1L1
(E) (2) 2"C., EA W/
(E) PAD MOUNTED TRANSFORMER
4#6 CU
(E) 2-1/2"C.,
(E) UNDERGROUND PRIMARY SERVICE
3#4/0 CU
B
(E) MCC WEST
MANAGEMENT (E) T3LG (E) PANEL 'HC'
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2015
112.5KVA
112.5KVA
112.5KVA
3RD FLR EAST
1ST FLR WEST
1ST FLR EAST
ROOF
2ND FLR WEST
AGENCY
3RD FLR WEST 1
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
(E) UFER GROUND (E) 70/3
(E) 225/3
F
(E)T3LW (E) TXHE (E) 225/3
(E)T3LH
(E) T3LF
(E) 400/3
(E) PANEL 'HN'
(E) 225/3
(E) 400/3
(E) 400/3
(E) 400/3
45KVA
75KVA
45KVA
75KVA
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
(E) 150/3 (E) PANEL 'LJ'
A
(E) PANEL 'LK'
(E) PANEL 'LA'
1ST FLR EAST
(E) PANEL 'LB'
1ST FLR WEST
(E) PANEL 'LA1'
(E) PANEL 'LC'
(E) PANEL '3LE' 2ND FLR EAST
(E) PANEL 'T1'
(E) 150/3
(E) 100/3 (E) PANEL 'LP'
(E) 125/3 (E) PANEL '3LF'
(E) 100/3 F
F
AC 1
AC 2
(E) PANEL 'LM'
(E) PANEL 'LN'
(E) PANEL 'LO'
(E) 80KW UPS
2ND FLR EAST
(E) PANEL 'LP'
(E) PANEL 'LZ'
(E) PANEL 'LD'
3RD FLR EAST
(E) 1
(E) 2
(E) 3
(E) PANEL 'LE'
(E) PANEL 'LF'
(N) 2"C., 4#1 THWN CU + 1#8 CU GND
2ST FLR WEST
(E) PANEL 'LF1'
(E) PANEL 'LE1'
(N) PANEL 'T'
(E) PANEL '3LW' 3RD FLR WEST
AC (E) PANEL 'LH'
(E) PANEL 'LG'
(E) PANEL 'LI'
FLS
DATE
TITLE 3RD FLR WEST
ONE LINE DIAGRAM
(E) PANEL '3LWA'
4/23/2019 3:19:38 PM
1
SHEET
1 E-301
ONE LINE DIAGRAM NONE
SHOWN FOR REFERENCE ONLY
E-301
SS
2
3
4
5
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
CEILING SUPPORT WIRES BY CEILING INSTALLER, TYPICAL.
SUPPORT WIRES BY ELECTRICAL CONTRACTOR, TYPICAL.
D
nWSX-PDT-LV-DX-WH
PETERS engineering
DIMMER SWITCH WITH OCCUPANCY SENSOR
consulting mechanical and electrical engineers
RJ45
ER 277/120VAC 0-10V DIMMING
CONDUIT PER PLAN
N
LAY-IN CEILING GRID BY CEILING INSTALLER, TYPICAL.
E-401
LIGHTING CONTROL WIRING DIAGRAM WITH WALL SENSOR NONE
1 E-401
FIXTURE PER PLAN
G
E17247 EXP. 6/30/20 TA
S
4
REG I S T
WHT
BLK/ORN
LIGHTING LOAD
O R. ROMA
I NEER
1
IN
NO
N H
PRO F E S S I ONA L
ED
EL
TE
EC TR I CA
OF CA L
L
I
A
ON/OFF
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
N I F OR
4/23/2019 3:19:41 PM
T-BAR FIXTURE MOUNTING DETAIL NONE
SEAL
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
N
EN . 08 - 3 1 - 1 O F OF CALI 9
A
R E
R
ST T
IA
C23603
PROJECT C SUPPORT WIRES ADDED FOR ELECTRICAL WIRING METHOD 1/4" ALL-THREAD ROD A MINIMUM OF (2) SUPPORT WIRES AT OPPOSITE CORNERS OF EACH LIGHT FIXTURE. ELECTRICAL CONTRACTOR SHALL COORDINATE FIXTURE LOCATIONS WITH THE CONTRACTOR.
CADDY B18 SERIES COMBINATION BOX/ CONDUIT HANGER.
UL APPROVED CADDY CLIPS, TYP.
FLEX CONDUIT WITH ALL NECESSARY FITTINGS TO J-BOX PER PLANS. PROVIDE #12 BRANCH WIRING & #12 GROUND BOND TO LIGHT FIXTURE.
7667 FOLSOM BLVD., SACRAMENTO, CA 95826 CLIENT
GRID SUPPORT BY OTHERS
JUNCTION BOX PER PLANS
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
LIGHT FIXTURE PER PLANS CONNECT SUPPORT WIRES TO SUSPENDED CEILING FOR WIRE STABILITY.
SUSPENDED CEILING SYSTEM PER ARCHITECTURAL PLANS
ISSUED
CEILING SUPPORT WIRES (NO ELECTRICAL SUPPORT PERMITTED)
MARK
NOTES: 1. IN ACCORDANCE WITH CEC 300.11, RACEWAYS, CABLE ASSEMBLIES, BOXES, CABINETS, AND FITTINGS SHALL NOT BE SECURED TO, OR SUPPORTED BY, THE CEILING ASSEMBLY, INCLUDING THE CEILING SUPPORT WIRES. AN INDEPENDENT MEANS OF SECURE SUPPORT SHALL BE PROVIDED AND SHALL BE SECURED AT BOTH ENDS. IN FIRE-RATED ASSEMBLIES THE INDEPENDENT SUPPORT WIRES SHALL BE SHALL BE DISTINGUISHABLE BY COLOR, TAGGING, OR OTHER EFFECTIVE MEANS FROM THOSE THAT ARE PART OF THE FIRE-RATED DESIGN. 2. SUPPORT SHALL NOT EXCEED 5 POUNDS PER LINEAR FOOT.
5 E-401
CONDUIT SUPPORT NONE
LAY-IN LIGHT FIXTURE PER PLAN
MAIN T-BAR RUNNERS, TYPICAL
CROSS T-BAR, TYPICAL
ADJUSTABLE "T-BAR" LOCK CLIP FOR POSITIVE ATTACHMENT OF FIXTURE TO T-BAR. PROVIDE (2) @ EACH END OF FIXTURE.
DATE
DESCRIPTION
CEILING TILE, TYPICAL
2 E-401
T-BAR MOUNTED FIXTURE DETAIL NONE
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2015
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
AGENCY
EXTRA #12 HANGER WIRE @ EA. CORNER OF FIXTURE, ATTACHED TO FIXTURE BODY W/(2) 1/8" POP RIVITS & BRACKET OR TAB PROVIDED WITH FIXTURE. SECURE TO STRUCTURE SIMILAR TO CEILING SYSTEM.
FILE NO: 34-CSUS GRID SUPPORT WIRES, N.I.E.S.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
T-BAR SAFETY CLIPS SNAP-ON HOLD-DOWN CLIP TO SECURE TROFFER TO "T-BAR". PROVIDE (2) @ EA. END OF FIXTURE.
AC
FLS
DATE A CEILING & "T-BAR" SUSPENSION (SEE ARCHITECTURAL DRAWINGS.)
TITLE
DETAILS
4/23/2019 3:19:41 PM
FIXTURE BODY & DOOR.
3 E-401
LAY-IN FIXTURE MOUNTING DETAIL NONE
SHEET
E-401
SS
2
3
4
5
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
ER
ELECTRICAL MOUNTING HEIGHTS
IN
O R. ROMA
E17247 EXP. 6/30/20 TA
EL
TE
EC TR I CA
OF CA L
L
I
A
F.F.
G
15" MIN. TO BOTTOM
PRO F E S S I ONA L
ED
S
OVER OBSTRUCTION
consulting mechanical and electrical engineers
OUTLETS
REG I S T
48" MAX. TOP OF SWITCHES & THERMOSTATS
34" MAX.
F.F.
PETERS engineering
I NEER
46" MAX. (SIDE APPROACH) TOP OF SWITCHES, OUTLETS & THERMOSTATS
24" MAX.
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
NO
44" MAX. (FRONT APPROACH)
D
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
N I F OR
4/23/2019 3:19:42 PM
1 E-402
DEVICE MOUNTING HEIGHT NONE SEAL
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
N
EN . 08 - 3 1 - 1 O F OF CALI 9
A
R E
R
ST T
IA
C23603
PROJECT C
4 E-402
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
CONDUIT PENETRATION NONE
7667 FOLSOM BLVD., SACRAMENTO, CA 95826 CLIENT
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
WIREMOLD RC7ATCBK FLUSH POKE THRU COMPLETE WITH PREWIRED 20A DUPLEX RECEPTACLE AND FOUR BLANK TRACJACK MOUNTING INSERTS FOR UNUSED COMMUNICATION OPENINGS.
FINISH FLOOR CONCRETE FLOOR SLAB
ISSUED MARK
DATE
DESCRIPTION
METAL DECKING NOTE: 1. ASSEMBLED WITH SCRUB WATER GASKET. FOR USE ON TILE OR CARPET FLOORS. 2. POKE-THRU ELECTRICAL INSERTS SHALL MEET THE F AND T RATINGS ACCEPTANCE CRITERIA OF ANSI/UL 1479.
2 E-402
POKE THRU WITH RISER DETAIL NONE
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2015
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
AGENCY
CLEAR THERMAL TRANSFER LAMINATED ADHESIVE TAPE WITH 1/8"H BLACK LETTERS.
FILE NO: 34-CSUS 20-20
AC
FLS
DATE COVER PLATE A
TITLE DUPLEX RECEPTACLE
5 4/23/2019 3:19:42 PM
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
2A-20
E-402
FIRESTOP PUTTY PAD NONE
3 E-402
DETAILS
OUTLET DESIGNATION DETAIL NONE
SHEET
E-402
SS
3
4
5
FIRE ALARM SYSTEM COMPONENTS
THE FOLLOWING IS A BRIEF DESCRIPTION OF THE SCOPE OF WORK FOR THIS PROJECT. IT IS GENERAL IN NATURE AND DOES NOT CONSTITUTE ALL THAT IS TO BE DONE NOR DOES IT INDICATE THE SEQUENCE OF INSTALLATION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FULLY COMPLETE THE WORK IDENTIFIED IN THE PLAN DOCUMENTS. THE CONTRACTOR SHALL FURNISH A MOP OUTLINING A SEQUENCE OF WORK . 1. RELOCATE EXISTING NOTIFICATION APPLIANCES AS REQUIRED BY REMODEL. 2. ADD NEW NOTIFICATION APPLIANCES AS REQUIRED BY REMODEL. 3. EXTEND EXISTING NEW NOTIFICATION APPLIANCE CIRCUITS TO RELOCATED AND NEW DEVICES.
EXISTING DEVICES SYM
(E)
NOTIFIER
NFS640
EXISTING EQUIPMENT
N/A
EXISTING NOTIFICATION EXTENDER POWER SUPPLY
(E)
NOTIFIER
FCPS-24S6
EXISTING EQUIPMENT
EXISTING SMOKE DETECTOR EXISTING DETECTOR BASE
(E)
NOTIFIER
FSP-851
EXISTING EQUIPMENT
EXISTING MANUAL PULL STATION
(E)
NOTIFIER
NBG-12LX
EXISTING EQUIPMENT
XX
EXISTING CEILING MOUNTED HORN STROBE (XX = CANDELA)
(E)
SYSTEM SENSOR
PC2R
EXISTING EQUIPMENT
XX
EXISTING CEILING MOUNTED STROBE ONLY (XX = CANDELA)
(E)
SYSTEM SENSOR
SCR
EXISTING EQUIPMENT
XX
EXISTING WALL MOUNTED STROBE ONLY (XX = CANDELA)
(E)
SYSTEM SENSOR
SR
EXISTING EQUIPMENT
F
NEW DEVICES
XX XX
FIRE ALARM PACKAGE SHALL INCLUDE DETAILED SHOP DRAWINGS, CUT SHEETS, AND COPIES OF THE APPROVED CSFM (CALIFORNIA STATE FIRE MARSHAL) LISTINGS FOR DEVICES, PROGRAMING, COMMISSIONING, STARTUP, AND ONE YEAR OF MAINTENANCE AFTER THE INSTALLATION IS ACCEPTED AND SIGNED OFF BY THE INSPECTOR OF RECORD.
2
SYSTEM SENSOR
PC2RL
7320-1653:0503
CEILING MOUNTED STROBE ONLY (XX = CANDELA)
3
SYSTEM SENSOR
SCRL
7135-1653:0504
PETERS engineering
consulting mechanical and electrical engineers
ER
THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL. IF THE EXISTING SYSTEM IS NOT OPERATIONAL THE CONTRACTOR SHALL PROVIDE A CONTINUOUS FIRE WATCH UNTIL THE SYSTEM IS FULLY RESTORED. THE SYSTEM SHALL BE FULLY COMPATIBLE WITH EXISTING SYSTEM OR PROVIDE METHOD OF RELAY/OPERATION OF NEW SYSTEM.
7.
A STAMPED SET OF APPROVED FIRE ALARM DESIGN DOCUMENTS SHALL BE KEPT ON THE JOB SITE AND USED FOR INSTALLATION. ANY DEVIATION FROM THE APPROVED DESIGN DOCUMENTS, INCLUDING SUBSTITUTION OF DEVICES, SHALL BE APPROVED BY THE AUTHORITY HAVING JURISDICTION. ALL DEVIATIONS SHALL BE MARKED-UP ON THE JOB SITE SET OF THE APPROVED DOCUMENTS. THE APPROVED DOCUMENTS SHALL BE KEPT UP-TO-DATE WITH ALL DEVIATIONS (INCLUDING CONDUIT/CABLE ROUTING CHANGES, WIRING CHANGES AND DEVICE ADDRESS CHANGES) AND SHALL BE USED AS REDLINES FOR THE FINAL AS AS-BUILT SET OF DRAWINGS.
EXISTING FIRE ALARM SYSTEM OPERATIONAL MATRIX
I
G
C23603 T
R E
OPEN CIRCUIT GROUND FAULT NOTIFICATION APPLIANCE CIRCUIT SHORT
EN . 08 - 3 1 - 1 O F OF CALI
PROJECT
AC POWER LOSS SYSTEM LOW BATTERY COMMUNICATION LOSS/TROUBLE SIGNAL SILENCE RESET FIRE ALARM PANEL NOTES: 1. 2.
OF CA L
L
N I F OR
CT Y R RT
13. VISUAL DEVICES SHALL NOT EXCEED 2 FLASHES PER SECOND AND SHALL NOT BE SLOWER THAN 1 FLASH EVERY SECOND. THE DEVICE SHALL HAVE A PULSING LIGHT SOURCE NOT LESS THAN .0375 LUMENS PER SQUARE FEET AND MEET ADA COMPLIANCE. WHEN THERE IS MORE THAN TWO VISUAL APPLIANCES OR GROUPS OF SYNCHRONIZED VISUAL APPLIANCES WITHIN THE FIELD OF VIEW ALL APPLIANCES SHALL BE SYNCHRONIZED.
EC TR I CA
D A RCH SE I E N A N McM TE H U T A
A
12. THE ALARM AUDIBLE SIGNAL PATTERN USED TO NOTIFY OCCUPANTS OF THE NEED TO EVACUATE (LEAVE THE BUILDING) OR RELOCATE (FROM ONE AREA TO ANOTHER) SHALL BE THE STANDARD ALARM EVACUATION SIGNAL CONSISTING OF A THREE-PULSE TEMPORAL PATTERN (NFPA 72, 2016 EDITION SECTION 18.4.2.1) .
EL
TE
SEAL
ST
11. TO ENSURE THAT AUDIBLE PUBLIC MODE SIGNALS ARE CLEARLY HEARD THEY SHALL HAVE A SOUND LEVEL AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 dB ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS, WHICHEVER IS GREATER, MEASURED 5 FT ABOVE THE FLOOR IN THE AREA REQUIRED TO BE SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (dBA) (NFPA 72, 2016 EDITION SECTION 18.4.3.1) .
O R. ROMA
4/23/2019 3:21:26 PM
NOTES
MANUAL PULL STATION SMOKE DETECTOR DUCT DETECTORS FIRE SPRINKLER WATERFLOW FIRE SPRINKLER TAMPER SWITCH
IN
E17247 EXP. 6/30/20 TA
CAUSE
PRO F E S S I ONA L
ED
IA
6.
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
FIRE ALARM CONTROL PANEL IS EXISTING. NO CHANGES TO CONTROL PANEL OR PANEL FUNCTIONALITY ARE PART OF THIS PROJECT.
7667 FOLSOM BLVD., SACRAMENTO, CA 95826
.
15. THE FLASH RATE SHALL NOT EXCEED TWO FLASHES PER SECOND (2 Hz) NOR BE LESS THAN ONE FLASH EVERY SECOND (1 Hz) THROUGHOUT THE LISTED VOLTAGE RANGE OF THE APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.5.3.1) .
CLIENT
WIRE SCHEDULE
16. WHERE MORE THAN TWO VISIBLE NOTIFICATION APPLIANCES OR GROUPS OF SYNCHRONIZED APPLIANCES ARE IN THE SAME ROOM OR ADJACENT SPACE IN THE FIELD OF VIEW ALL APPLIANCES ARE REQUIRED SYNCHRONIZE TOGETHER (NFPA 72, 2016 EDITION SECTION 18.5.5.4.2) .
MANUFACTURER 17. SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN 1'-0" OF OR WITHIN THE SAME LAY-IN TILE AS A FIRE SPRINKLER HEAD
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
N
INFORMATION SHOWN ON THESE PLANS RELATING TO THE EXISTING FIRE ALARM SYSTEM HAS BEEN OBTAINED FROM THE ORIGINAL AND "AS BUILT/RECORD" DRAWINGS AND FROM FIELD OBSERVATIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL EXISTING WIRING AND RELATED CONDITIONS BEFORE PROCEEDING WITH THE EXECUTION OF WORK. MODIFICATIONS TO THE EXISTING WIRING SYSTEMS SHALL ENSURE CIRCUIT CONTINUITY TO ALL REMAINING EXISTING DEVICES OR EQUIPMENT ASSOCIATED WITH THE EXISTING REMAINING WIRING SYSTEM.
14. AN AVERAGE AMBIENT SOUND LEVEL GREATER THAN 105 dBA SHALL REQUIRE THE USE OF A VISIBLE NOTIFICATION APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.4.1.1)
CEILING MOUNTED HORN STROBE (XX = CANDELA)
I NEER
5.
UPON ACTIVATION OF A MANUAL FIRE ALARM BOX, THE RESPECTIVE DEVICE SHALL CAUSE AN INDICATION OF ALARM TO BE RECEIVED BY THE FIRE ALARM CONTROL PANEL. THE PANEL SHALL CAUSE ALL NOTIFICATION APPLIANCES TO ACTIVATE. THE RESPECTIVE DEVICE ADDRESS OR ZONE SHALL BE IDENTIFIED AT THE ANNUNCIATOR AND/OR FACP.
CSFM #
NO
ANY DISCREPANCIES IN THE DRAWING SET WITH APPLICABLE CODES OR RECOGNIZED STANDARDS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER PRIOR TO ORDERING AND INSTALLING EQUIPMENT.
9.
MODEL #
S
4.
UPON ACTIVATION OF INITIATION DEVICES THE FIRE ALARM SYSTEM SHALL TRANSMIT ALARM, SUPERVISORY, AND/OR TROUBLE SIGNALS TO THE MONITORING STATION OF THE OWNER'S CHOICE.
MANUFACTURER
NOTE: THERE ARE NO HARDWARE MODIFICATIONS TO THE EXISTING FIRE ALARM CONTROL PANEL.
PRIOR TO ORDERING AND INSTALLATION THE FIRE ALARM SYSTEM AND ASSOCIATED EQUIPMENT PREPARE AND SUBMIT A COMPLETE SUBMITTAL PACKAGE COMPLETE WITH DETAILED SHOP DRAWINGS (INCLUSIVE OF CALCULATIONS AND POINT BY POINT WIRING DIAGRAMS), CUT SHEETS AND COPIES OF THE APPROVED CALIFORNIA STATE FIRE MARSHAL LISTINGS FOR EACH COMPONENT OF THE SYSTEM TO BE INSTALLED.
8.
QTY
DESCRIPTION
A
SYM
10. THE TOTAL SOUND PRESSURE LEVEL PRODUCED BY COMBINING THE AMBIENT SOUND PRESSURE LEVEL WITH ALL AUDIBLE NOTIFICATION APPLIANCES OPERATING SHALL NOT EXCEED 110 dBA AT THE MINIMUM HEARING DISTANCE (NFPA 72, 2016 EDITION SECTION 18.4.1.2).
C
P
REG I S T
3.
CSFM #
9
2.
MODEL #
AL AR EF TR M S FE OU IG NA CT B SU L L PE E S A T I AL RV GN FA AR ISO AL CP TR M S RY AT OU IG SIG FAC N SU BL AL NA P PE E S A T L A AL RV IGN AN T FA A R I SO A L N U C P TR M S RY AT NCI OU IG SIG AN AT N N O SU BL AL NA UN R E L PE S T O A C I A RV IGN C T A TO I S A L SU N N R OR T S U AC Y O C D IS N C S TI IG SU PAT IAT V NA S C O DE AT L T DI H R AC E A S O PA AC T I V U D CS T TI AT IBL US CH VA E E/ CL T AU VI DI SP OS E W D SU I AT HV E F AT BLE AL A CH A C I R E ER / VI PP SH SM FLO SUA LIA UT O W L NC DO KE BE AP ES AC W D A L L PL I TI AN N MP VA CE SY T E RS S ST E B EM A T N O T ER RM Y AL BAC KU P
D
MANUFACTURER
EXISTING FIRE ALARM PANEL
FIRE ALARM SYSTEM NOTES THE INSTALLATION OF THE FIRE ALARM SYSTEM SHALL CONFORM TO THE FOLLOWING CODES AND STANDARDS: a. 2016 CA BUILDING STANDARDS ADMINISTRATIVE CODE b. 2016 CALIFORNIA BUILDING CODE c. 2016 CALIFORNIA ELECTRICAL CODE d. 2016 CALIFORNIA MECHANICAL CODE e. 2016 CALIFORNIA PLUMBING CODE f. 2016 CALIFORNIA ENERGY CODE g. 2016 CALIFORNIA FIRE CODE h. 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE i. CCR TITLE 19. PUBLIC SAFETY: DIVISION 1. STATE FIRE MARSHAL j. 2016 NFPA 13 - INSTALLATION OF FIRE SPRINKLERS* k. 2013 NFPA 14 - INSTALLATION OF STANDPIPE AND HOSE SYSTEM* l. 2016 NFPA 20 - INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION m. 2016 NPFA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE* * AS AMENDED BY CALIFORNIA
QTY
N/A
S
1.
DESCRIPTION
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
SCOPE OF WORK
R
2
LI JO C N
2"
1
DESCRIPTION
USAGE
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
.
18. DETECTORS SHOULD NOT BE LOCATED IN A DIRECT AIRFLOW OR CLOSER THAN 36 IN. FROM AN AIR SUPPLY DIFFUSER OR RETURN AIR OPENING. SUPPLY OR RETURN SOURCES LARGER THAN THOSE COMMONLY FOUND IN RESIDENTIAL AND SMALL COMMERCIAL ESTABLISHMENTS CAN REQUIRE GREATER CLEARANCE TO SMOKE DETECTORS. SIMILARLY, SMOKE DETECTORS SHOULD BE LOCATED FARTHER AWAY FROM HIGH VELOCITY AIR SUPPLIES (NFPA 72, 2016 EDITION SECTION A.17.7.4.1) .
WEST PENN
N
#998 2#12, FPLP
NOTIFICATION APPLIANCE CIRCUIT
19. ADJUST AND INSTALL DEVICES TO MAXIMIZE PERFORMANCE AND MINIMIZE FALSE ALARMS.
ISSUED
20. T-TAP ONLY WHERE SHOWN ON THE DRAWINGS AND APPROVED BY THE MANUFACTURER'S DOCUMENTATION.
MARK
DATE Date 1
21. INSTALL FIRE ALARM WIRING IN 3/4"C., MINIMUM. 22. WHERE CONDUIT IS SPECIFIED OR REQUIRED BY CODE OR APPLICABLE STANDARDS FIRE ALARM CIRCUITS SHALL BE INSTALLED IN A MINIMUM OF 3/4" CONDUITS. CONDUIT FILL SHALL BE MAINTAINED PER THE APPLICABLE CEC. 23. PENETRATIONS THROUGH RATED ASSEMBLIES AND WALLS SHALL BE SEALED WITH A LISTED SYSTEM THAT IS EQUAL TO OR EXCEEDS THE RATING OF THE ASSEMBLY. 24. WIRING SHALL BE UL APPROVED AS DESIGNATED IN THE FIRE ALARM SYSTEM WIRING SCHEDULE OR THE MANUFACTURER'S INSTALLATION MANUAL. FIRE ALARM CABLES SHALL BE LISTED BY THE CALIFORNIA STATE FIRE MARSHAL (CSFM) AND BE PROVIDED WITH RED PVC JACKET. WIRING INSTALLED UNDERGROUND SHALL BE LISTED FOR WET LOCATION.
DESCRIPTION Revision 1
PATHWAY DESIGNATIONS: 1. 2. 3. 4. 5. 6.
BUILDING IS STATE OWNED. BUILDING IS USED FOR HIGHER EDUCATION AND OFFICES. BUILDING IS NOT SPRINKLED. ALL FIRE ALARM WIRING SHALL BE INSTALLED IN CONDUIT. FIRE ALARM PATHWAYS SHALL BE RUN CLASS B. FIRE ALARM PATHWAY SURVIVABILITY IS LEVEL 1.
25. WIRING PULLED THROUGH A JUNCTION BOX OR BACK BOX SHALL TERMINATE AT A DEVICE, SYSTEM PANEL OR TERMINAL CABINET WITH NO SPLICES. SIZE BOXES PER WIRE FILL AS DEFINED IN THE CEC. PROVIDE A MINIMUM OF 6” OF LEAD WIRE FROM THE BOX TO CONNECT EACH DEVICE. 26. FIRE ALARM CABLES/CONDUCTORS SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
B
27. UPON COMPLETION OF INSTALLATION CONDUCT A TEST OF THE SYSTEMS OPERATION IN ACCORDANCE WITH NFPA 72, 2016 EDITION CHAPTER 14 IN THE PRESENCE OF THE AUTHORITY HAVING JURISDICTION, THE ARCHITECT AND THE INSPECTOR OF RECORD. COMPLETE REQUIRED DOCUMENTATION IN ACCORDANCE WITH NFPA 72, 2016 EDITION CHAPTER 7. PROVIDE ORIGINAL TO INSPECTOR OF RECORD AND COPIES TO OWNER'S REPRESENTATIVE AND AUTHORITY HAVING JURISDICTION. 28. THE AUTHORITY HAVING JURISDICTION, THE INSPECTOR OF RECORD, AND THE OWNER'S REPRESENTATIVE SHALL RECEIVE FORTY EIGHT (48) HOURS NOTICE PRIOR TO THE DATE OF A FUNCTIONAL TEST AND FINAL INSPECTION. 29. THE INSPECTOR OF RECORD AND THE ARCHITECT SHALL RECEIVE ONE (1) WEEKS NOTICE FOR A FINAL PUNCH LIST WALK.
4/23/2019 3:21:26 PM
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
30. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE SYSTEM ACCESS REQUIREMENTS WITH OTHER TRADES, SPECIFICALLY SERVICE ACCESS TO ALL DEVICE LOCATIONS. INITIATING DEVICES SHALL BE INSTALLED IN A MANNER THAT PROVIDES ACCESSIBILITY FOR PERIODIC INSPECTION TESTING AND MAINTENANCE (NFPA 72, 2016 EDITION SECTION 17.4.5). 31. THE FOLLOWING SHALL BE COMPLETED AND SUBMITTED TO THE ENGINEER FOR A FINAL TO BE GRANTED: a. AS-BUILT DRAWINGS, PROGRAMMING DOCUMENTS, SCHEMATICS (DEVICE & EQUIPMENT CUTSHEETS), AND MANUALS PER SPECIFICATIONS. PROVIDE SUCH DOCUMENTS IN PAPER FORM AND ON CD. b. A ½ SIZE LAMINATED POSTING OF THE AS-BUILT PRINTS AT THE FIRE ALARM CONTROL PANEL. c. TYPED RECORD OF COMPLETION PER NFPA 72. d. ITEMS ON A PUNCH LIST SHALL BE COMPLETE AND SIGNED OFF BY THE INSPECTOR OF RECORD. e. ACCEPTANCE OF THE FUNCTIONAL TEST SIGNED OFF BY THE CALIFORNIA STATE FIRE MARSHAL AND THE INSPECTOR OF RECORD.
FIRE ALARM INSTALLATION NOTE: THE FIRE ALARM SYSTEM IS NOT A DEFERRED APPROVAL ITEM. THE FIRE ALARM PLANS ARE COMPLETE AND ARE APPROVED BY THE CALIFORNIA STATE FIRE MARSHAL'S OFFICE. THESE SHEETS, ALTHOUGH APPROVED BY THE FIRE MARSHAL, ARE NOT APPROVED FOR THE INSTALLATION OR MODIFICATION OF ANY FIRE ALARM SYSTEM(S). A SEPARATE SUBMITTAL BY THE INSTALLING C-10 LICENSED FIRE ALARM CONTRACTOR IS TO BE SUBMITTED TO THE FIRE ALARM SYSTEM DESIGN ENGINEER FOR REVIEW AND APPROVAL PRIOR TO THE START OF INSTALLATION OR MODIFICATION OF ANY FIRE ALARM COMPONENTS.
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2015
AGENCY
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
FLS
SS
DATE A
TITLE
SYMBOLS, NOTES & SCHEDULES SHEET
FA-001
2"
1
2
3
4
5
FIRE ALARM LEGEND 1"
EXISTING DEVICES
EXISTING FIRE ALARM PANEL
N/A
EXISTING NOTIFICATION EXTENDER POWER SUPPLY
7
EXISTING SMOKE DETECTOR EXISTING DETECTOR BASE
P
EXISTING MANUAL PULL STATION
F
8
XX
EXISTING CEILING MOUNTED HORN STROBE (XX = CANDELA)
XX
EXISTING CEILING MOUNTED STROBE ONLY (XX = CANDELA)
XX
EXISTING WALL MOUNTED STROBE ONLY (XX = CANDELA)
NEW DEVICES
D
4
5
6
SYM
DESCRIPTION
XX
CEILING MOUNTED HORN STROBE (XX = CANDELA)
XX
CEILING MOUNTED STROBE ONLY (XX = CANDELA)
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
PETERS engineering
G
REG I S T
2
O R. ROMA
E17247 EXP. 6/30/20
3
EL
TE
EC TR I CA
OF CA L
L
I
A
TA
S
1
IN
I NEER
C
PRO F E S S I ONA L
ED
NO
ER
consulting mechanical and electrical engineers
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
N/A
S
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
DESCRIPTION
SYM
N I F OR
4/23/2019 3:21:29 PM
D SEAL
CT Y R RT
LI JO C N
D A RCH SE I E N A N McM TE H U T A
AREA A
IA
EN . 08 - 3 1 - 1 O F OF CALI
N
R E
9
A
T
R
ST
E
C23603
PROJECT C
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
(E) NOTIFICATION EXTENDER PANEL 'BPS2'
F S
DN
P
(E)
DN
7667 FOLSOM BLVD., SACRAMENTO, CA 95826 CLIENT
G
UP DN
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
H
ISSUED
AREA B
MARK
DATE
DESCRIPTION
I
J
B
MANAGEMENT
1 FA-112
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
FIRE ALARM FLOOR PLAN - LEVEL 2 - OVERALL
LIONAKIS 2015
1/16" = 1'-0"
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
AGENCY
0'
8'
16'
32'
64'
KEY PLAN
FILE NO: 34-CSUS IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AC
A
SS
DATE A
TITLE
B
PLAN NORTH
4/23/2019 3:21:29 PM
FLS
FLOOR PLAN LEVEL 2 OVERALL SHEET
FA-112
2"
1
2
3
4
7
5
8
FIRE ALARM LEGEND 1"
EXISTING DEVICES
~ (E) 75
C
DESCRIPTION
N/A
EXISTING FIRE ALARM PANEL
N/A
EXISTING NOTIFICATION EXTENDER POWER SUPPLY
S
1
EXISTING SMOKE DETECTOR EXISTING DETECTOR BASE
P
EXISTING MANUAL PULL STATION
F
~
(E) 15
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
XX
EXISTING CEILING MOUNTED HORN STROBE (XX = CANDELA)
XX
EXISTING CEILING MOUNTED STROBE ONLY (XX = CANDELA)
XX
EXISTING WALL MOUNTED STROBE ONLY (XX = CANDELA)
F
NEW DEVICES
2
D
SYM DN
DESCRIPTION
XX
CEILING MOUNTED HORN STROBE (XX = CANDELA)
XX
CEILING MOUNTED STROBE ONLY (XX = CANDELA)
DN
PETERS engineering
GENERAL NOTES
~
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
consulting mechanical and electrical engineers 1. A MINIMUM OF 72 HOURS’ NOTICE IS REQUIRED FOR ANY TESTING AND/OR INSPECTION
F
REMOVE EXISTING CEILING MOUNTED HORN / STROBE AND PROTECT FOR REUSE. REMOVE EXISTING CONDUIT AND CABLES BACK TO LAST REMAINING DEVICES.
2
REMOVE EXISTING DEVICE. PROTECT EXISTING OUTLET BOX AND CABLES FOR RE-USE.
3
EXISTING DEVICE TO REMAIN.
TA
EL
TE
EC TR I CA
OF CA L
L
I
A
1
O R. ROMA
E17247 EXP. 6/30/20
S
~
IN
I NEER
DEMOLITION KEYED NOTES:
G
G
3
C
PRO F E S S I ONA L
ED
NO
ER
15
REG I S T
(E)
(E)
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
SYM
N I F OR
4/23/2019 3:21:33 PM
SEAL
PARTIAL FLOOR PLAN - LEVEL 2 - AREA A & B - FIRE ALARM DEMOLITION
KEYED NOTES: 2
(E) ~
8'-5"
C
1
EXISTING DEVICE IN NEW LOCATION.
2
CONNECT NEW CABLES INTO EXISTING NOTIFICATION CIRCUIT AT EXISTING DEVICE.
15 N2-9
(E)
EN . 08 - 3 1 - 1 O F OF CALI
PROJECT
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS
CLASSROOM
2604
R E
N
A
T
9
8
ST
7
IA
C23603
R
1/8" = 1'-0"
CT Y R RT
2 FA-113
LI JO C N
D A RCH SE I E N A N McM TE H U T A
N 75
7667 FOLSOM BLVD., SACRAMENTO, CA 95826
1
N2-8
CLIENT
N
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
8'-5"
E AUDIO LAB TEST BOOTH
2305A (N)
AUDIOLOGY LAB
AUDIOLOGY LAB
2602
2603
15
AUDIOLOGY LAB N2-7
2601
N
15 (N)
8'-5"
15
N2-6
(N)
N
ISSUED
N2-5
MARK
DATE
DESCRIPTION
AUDIO LAB - CONSULT
8'-5"
2305
8'-5"
8'-5" N (E)
2
CORRIDOR
15
~
8'-5"
2309
C
N2-4
F
S
P
AUXILLARY OBSERVATION
DN
2320 OBSERVATION
B
10'-0"
8'-5"
2319
8'-5"
8'-5"
DN
STAIR NO. 2
GENDER NEUTRAL RESTROOM OBVS. CLOS. 2321
2504
~
2322
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
F (E)
(E)
15
2
C
N3-3 N
AGENCY
15 (N) N3-4
LOBBY
1000
COMPUTER LAB
2204
0' STAIR NO.1
2404J
4'
8'
16'
32'
KEY PLAN
8'-5"
FILE NO: 34-CSUS
H
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
CORRIDOR
(E) C
95 N3-5
2315
AC
A
FLS
A
TITLE 8'-5" B (E) C
15 N3-6
PLAN NORTH
PARTIAL FLOOR PLANS - FIRE ALARM
I
4/23/2019 3:21:33 PM
SS
DATE
~
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
G
LIONAKIS 2015
8'-5"
SHEET
1 FA-113
PARTIAL FLOOR PLAN - LEVEL 2 - AREA A & B - FIRE ALARM 1/8" = 1'-0"
FA-113
2
3
4
5
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
(E) BPS2
1N, TYP TO (E) NOTIFICATION APPLIANCES
(E)
D
(E) 30
N3-18
(E) 30
N3-17
30 N3-16
(E)
(E) 15
15
75
(E)
(E)
(E) 30
15
15
N2-15
N2-14
N2-13
N2-12
N2-11
N2-10
(E)
(E)
(E)
(E)
(E)
(E)
15
N3-15
15
N3-14
15
N3-13
15 N3-12
15
N3-11
15
N3-10
(E)
(N)
(E)
75
15
N2-9
(N)
N2-8 15
N3-9
(E)
N3-8
(N)
15 N2-7
15
15
N2-6
N3-6
N3-7
(E) 15
15
30
N2-4
(E) 15
15
(N)
N2-5
(E)
(E)
(N)
N3-5
N3-4
N3-3
1N, TYP 15
15
CKT#2 N2-1
(E) 15
15
(E)
N2-2
(E)
(N)
95
N2-3
(E)
(E)
30 N3-2
1N, TYP 15
CKT#3
N3-1
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.058
CKT#4
PETERS engineering
consulting mechanical and electrical engineers
NOTE: NO NEW INITIATION DEVICES ARE BEING ADDED IN THIS PROJECT.
ER
G
IN
O R. ROMA
I NEER
NONE
PRO F E S S I ONA L
ED
NO
FA-301
FIRE ALARM ONE LINE DIAGRAM REG I S T
1
E17247 EXP. 6/30/20
S
TA
EL
TE
EC TR I CA
OF CA L
L
I
A
(E)
CKT#1
ENG
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1"
2"
1
N I F OR
4/23/2019 3:21:35 PM
SEAL D A RCH SE I E N A N McM TE H U T A
FACP
-
BLUE
BROWN
BLUE
BROWN
+ -
TO NEXT APPLIANCE OR EOL RESISTOR FIRE
96"
ALARM
PU L L D OWN
80" MIN. 2
THE TOTAL SOUND PRESSURE LEVEL PRODUCED BY COMBINING THE AMBIENT SOUND PRESSURE LEVEL WITH ALL AUDIBLE NOTIFICATION APPLIANCES OPERATING SHALL NOT EXCEED 110 dBA AT THE MINIMUM HEARING DISTANCE (NFPA 72, 2016 EDITION SECTION 18.4.1.2)
3.
THE ALARM AUDIBLE SIGNAL PATTERN USED TO NOTIFY OCCUPANTS OF THE NEED TO EVACUATE (LEAVE THE BUILDING) OR RELOCATE (FROM ONE AREA TO ANOTHER) SHALL BE THE STANDARD ALARM EVACUATION SIGNAL CONSISTING OF A THREE-PULSE TEMPORAL PATTERN (NFPA 72, 2016 EDITION SECTION 18.4.2.1).
+48" 3
4
5.
THE FLASH RATE SHALL NOT EXCEED TWO FLASHES PER SECOND (2 Hz) NOR BE LESS THAN ONE FLASH EVERY SECOND (1 Hz) THROUGHOUT THE LISTED VOLTAGE RANGE OF THE APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.5.3.1).
2
NFPA 18.5.4.1 VISUAL APPLIANCES SHALL HAVE ENTIRE LENS AT HEIGHTS ABOVE FINISHED FLOOR OF NOT LESS THAN 80" AND NO GREATER THAN 96" OR 6" BELOW CEILING, WHICHEVER IS LOWER.
IA N
9
ISSUED MARK
WHERE MORE THAN TWO VISIBLE NOTIFICATION APPLIANCES OR GROUPS OF SYNCHRONIZED APPLIANCES ARE IN THE SAME ROOM OR ADJACENT SPACE IN THE FIELD OF VIEW ALL APPLIANCES ARE REQUIRED SYNCHRONIZE TOGETHER (NFPA 72, 2016 EDITION SECTION 18.5.5.4.2). WIRING SHALL NOT BE LOOPED THROUGH DEVICE TERMINALS. INPUT AND OUTPUT WIRING DEVICE CONNECTIONS SHALL BE MADE ON SEPARATE TERMINALS OR SHALL BE SEPARATE WIRE LEADS MOUNTED UNDER A COMMON TERMINAL. THE MONITORING OF CIRCUIT INTEGRITY RELIES ON THE INTERRUPTION OF THE WIRING CONTINUITY WHEN THE CONNECTION TO THE INITIATING DEVICE IS LOST (NFPA 72, 2016 EDITION SECTION A.17.4.6). FIRE ALARM WIRING SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
NONE
CALIFORNIA STATE UNIVERSITY, SACRAMENTO 6000 J STREET, SACRAMENTO, CA 95819
DETAIL NOTES: NFPA 18.4.8.1 *WHERE CEILING HEIGHTS ALLOW, AUDIBLE APPLIANCES SHALL HAVE THEIR TOPS AT HEIGHTS ABOVE FINISH FLOOR OF NOT LESS THAN 90" AND BELOW FINISHED CEILING OF NOT LESS THAN 6".
FIRE ALARM HORN STROBE DETAIL
R
CLIENT FINISHED FLOOR
1
8.
4
+42"
TO ENSURE THAT AUDIBLE PUBLIC MODE SIGNALS ARE CLEARLY HEARD THEY SHALL HAVE A SOUND LEVEL AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 dB ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS, WHICHEVER IS GREATER, MEASURED 5 FT ABOVE THE FLOOR IN THE AREA REQUIRED TO BE SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (dBA) (NFPA 72, 2016 EDITION SECTION 18.4.3.1).
7.
2ND FLOOR SPEECH PATHOLOGY & AUDIOLOGY IMPROVEMENTS - SHELLED CLASSROOMS 7667 FOLSOM BLVD., SACRAMENTO, CA 95826
4.
6.
FA-301
AN AVERAGE AMBIENT SOUND LEVEL GREATER THAN 105 dBA SHALL REQUIRE THE USE OF A VISIBLE NOTIFICATION APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.4.1.1)
2.
EN . 08 - 3 1 - 1 O F OF CALI
72"
NOTES: 1.
R E
PROJECT
96" MAX. 2
90" 1
CT Y R RT
BOTTOM OF DEVICE 6" TOP OF PANEL
C
+
B F
SYNCHRONIZATION MODULE
FINISHED CEILING DSM
FROM PANEL OR PREVIOUS APPLIANCE
T
A
FIRE ALARM HORN STROBE
C23603 F.S.R. BELL
ST
F.A. SPEAKER/STROBE F.A. STROBE OR COMBINATION F.A. STROBE/HORN, TYPICAL
FA SPEAKER OR FA HORN, MOUNT AT 90" MIN.
LI JO C N
F.A. ABOVE CEILING HEAT DETECTOR, 5 MOUNT TO UNDERSIDE OF BEAM.
2 FA-301
3
NFPA 17.14.4 THE OPERABLE PART OF EACH MANUAL FIRE ALARM BOX SHALL NOT BE LESS THAN 42" AND NOT MORE THAN 48" ABOVE THE FLOOR.
4
MAINTAIN CONSISTENT HEIGHTS THROUGH OUT PROJECT.
5
INSTALL CEILING ACCESS PANEL AT ALL NON-LAYIN TYPE CEILINGS, WHERE HEAT DETECTOR ABOVE CEILING IS INDICATED.
DATE
DESCRIPTION
FIRE ALARM DEVICE MOUNTING DETAIL NONE
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2015
C:\Users\jmoberly\Documents\18.058 CSUS Folsom Hall Ph3 Mech-Elec R18_jmoberly.rvt
AGENCY
FIRE ALARM STROBE
FROM PANEL OR PREVIOUS APPLIANCE
-
BLUE
BROWN
BLUE
BROWN
+ -
FILE NO: 34-CSUS
TO NEXT APPLIANCE OR EOL RESISTOR
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
NOTES: 1.
AN AVERAGE AMBIENT SOUND LEVEL GREATER THAN 105 dBA SHALL REQUIRE THE USE OF A VISIBLE NOTIFICATION APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.4.1.1)
2.
THE FLASH RATE SHALL NOT EXCEED TWO FLASHES PER SECOND (2 Hz) NOR BE LESS THAN ONE FLASH EVERY SECOND (1 Hz) THROUGHOUT THE LISTED VOLTAGE RANGE OF THE APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.5.3.1).
3.
WHERE MORE THAN TWO VISIBLE NOTIFICATION APPLIANCES OR GROUPS OF SYNCHRONIZED APPLIANCES ARE IN THE SAME ROOM OR ADJACENT SPACE IN THE FIELD OF VIEW ALL APPLIANCES ARE REQUIRED SYNCHRONIZE TOGETHER (NFPA 72, 2016 EDITION SECTION 18.5.5.4.2).
4.
WIRING SHALL NOT BE LOOPED THROUGH DEVICE TERMINALS. INPUT AND OUTPUT WIRING DEVICE CONNECTIONS SHALL BE MADE ON SEPARATE TERMINALS OR SHALL BE SEPARATE WIRE LEADS MOUNTED UNDER A COMMON TERMINAL. THE MONITORING OF CIRCUIT INTEGRITY RELIES ON THE INTERRUPTION OF THE WIRING CONTINUITY WHEN THE CONNECTION TO THE INITIATING DEVICE IS LOST (NFPA 72, 2016 EDITION SECTION A.17.4.6).
5.
FIRE ALARM WIRING SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
AC
FLS
DATE A
TITLE
3 FA-301 4/23/2019 3:21:35 PM
+
ONE LINE DIAGRAM & DETAILS
FIRE ALARM STROBE DETAIL NONE SHEET
FA-301
SS