2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
INC:
REVIEWED FOR
770 DIAMOND AVE RED BLUFF, CA 96080
ACS
✔
✔
07/03/2019
CONSULTANT
TEHAMA CENTER STUDENT SERVICES NEW CONSTRUCTION DSA BACKCHECK
A2 A-303
SECTION INDICATOR - BUILDING
A4 A-201
ELEVATION INDICATOR - EXTERIOR A1
A-202
A2
A4
A-202
A2
ELEVATION INDICATOR - INTERIOR, SINGLE & MULTIPLE VIEW
A3
MATCH LINE SEE XX / X-XXX
MATCH LINE INDICATOR
1 A
REFERENCE GRID WITH REFERENCE GRID LINES
REVISION INDICATOR & REVISION CLOUD
22
ROOM NAME 101 LEVEL 1 100'-0"
ROOM IDENTIFIER WITH ROOM NAME & NUMBER
TOC 98'-8"
10
22
ELEVATION INDICATOR - LEVEL & SPOT
WINDOW OR LOUVER IDENTIFIER
KEYNOTE INDICATOR
B PLAN NORTH PLAN NORTH & TRUE NORTH INDICATOR
LOCATION MAP
CL CLG CLR CMU CNTR CO COL CONC CONSTR CONT COTG CP CPT CRS CSK CSWK CT CTR DBL DEPT DET DF
VICINITY MAP
EJ EL ELEC ELEV EMER ENCL EPB EQ EQUIP EW EWC EXH EXST EXP EXT FA FB FD FDTN FE FEC FIN FLG FLL FLR FOC FOF FOM FOS FOW FP FRP FT FTG FURG FUT G GA GALV GB GI GLU LAM GYP HB HC HDBD HDW HDWD HM HORIZ HR HT ID INSUL INT JAN KIT L LAB LAV
OFF OGL OPH OPNG OPP PAF PL PLAM PLB PLBG PLYWD PNL PROP PSF PSI PT PTN PV QT R RD REBAR REF REF REINF REQD RESIL RM RO RWD RWL SAD SATC SB SC SCHED SD SDST SHT SHTHG SHV SIM SLNT SM SPEC SQ SS SST
STD STL STOR STRUCT SUSP CLG SV SYMM SYS T T&G TEL THK TMH TMPD TO TOC TOF TOJ TOM TOP TOPO TOS TOW TV TYP UC UNO UON UR VCT VERT VEST VIF VWC VWF W/ W/O WC WD WH WO WP WPM WSCT WT WTR WWR
STANDARD STEEL STORAGE STRUCTURAL SUSPENDED CEILING SHEET VINYL SYMMETRICAL SYSTEM TREAD TONGUE & GROOVE TELEPHONE THICKNESS TOP OF MANHOLE TEMPERED TOP OF TOP OF CURB TOP OF FRAME TOP OF JOIST TOP OF MASONRY TOP OF PARAPET TOPOGRAPHY TOP OF STEEL TOP OF WALL TELEVISION TYPICAL UNDER COUNTER/CABINET UNLESS NOTED OTHERWISE UNLESS OTHERWISE NOTED URINAL VINYL COMPOSITION TILE VERTICAL VESTIBULE VERIFY IN FIELD VINYL WALL COVERING VINYL WALL FABRIC WITH WITHOUT WATER CLOSET WOOD WATER HEATER WHERE OCCURS WORKING POINT WATERPROOF MEMBRANE WAINSCOT WEIGHT WATER WELDED WIRE REINFORCEMENT
1.
CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, PROPERTY LINES ETC. PRIOR TO CONSTRUCTION.
2.
FABRICATION AND INSTALLATION OF DEFERRED SUBMITTAL ITEMS SHALL NOT BE STARTED UNTIL CONTRACTOR'S DRAWINGS, SPECIFICATIONS, AND ENGINEERING CALCULATIONS FOR THE ACTUAL SYSTEMS TO BE INSTALLED HAVE BEEN ACCEPTED AND SIGNED BY THE ARCHITECT OR STRUCTURAL ENGINEER AND APPROVED BY THE DSA.
SEAL
3.
CONTRACTOR SHALL NOTIFY ARCHITECT WHERE CONFLICT OCCURS ON ANY OF THE CONTRACT DRAWINGS OR DOCUMENTS. CONTRACTOR IS NOT TO ORDER MATERIAL OR CONSTRUCT ANY PORTION OF THE BUILDING THAT IS IN CONFLICT UNTIL CONFLICT IS RESOLVED WITH THE AFFECTED PARTIES.
4.
WHERE REQUIRED, ROOM OCCUPANCY CAPACITIES SHALL BE POSTED WITH THE REQUIREMENTS OF CALIFORNIA STATE FIRE MARSHAL & CBC 1004.3.
5.
SPECIAL REQUIREMENTS: A. -ASSUMED PROPERTY LINES & FIRE SEPARATION DISTANCE PER SHEETS GL111 B. -ACCESSIBLE PATH OF TRAVEL PER SHEET AS101 C. -EMERGENCY VEHICLE ROAD ACCESS PER G-101 D. -FOR PARKING REQUIREMENTS SEE SHEET AS101 E. -FOR BUILDING SIGNAGE REQUIREMENTS SEE SHEETS A-151
6.
7.
• • • • • • • • • • • • • • • • • • • • • • • •
TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHALL REGULATIONS TITLE 24 CCR, PART 1 - 2016 BUILDING STANDARDS ADMINISTRATIVE CODE TITLE 24 CCR, PART 2 - 2016 CALIFORNIA BUILDING CODE, VOL.1 & 2 (CBC) (2015 INTERNATIONAL BUILDING CODE, VOL. 1-2, AND 2013 CALIFORNIA AMENDMENTS) TITLE 24 CCR, PART 3 - 2016 CALIFORNIA ELECTRICAL CODE (CEC) (2014 NATIONAL ELECTRICAL CODE, AND 2016 CALIFORNIA AMENDMENTS) TITLE 24 CCR, PART 4 - 2016 CALIFORNIA MECHANICAL CODE (CMC) (2015 UNIFORM MECHANICAL CODE, AND 2016 CALIFORNIA AMENDMENTS) TITLE 24 CCR, PART 5 - 2016 CALIFORNIA PLUMBING CODE (CPC) (2015 UNIFORM PLUMBING CODE, AND 2013 CALIFORNIA AMENDMENTS) TITLE 24 CCR, PART 6 - 2016 CALIFORNIA ENERGY CODE TITLE 24 CCR, PART 7 - 2016 CALIFORNIA ELEVATOR SAFETY CONSTRUCTION CODE TITLE 24 CCR, PART 9 - 2016 CALIFORNIA FIRE CODE (CFC) (2015 INTERNATIONAL FIRE CODE, AND 2016 CALIFORNIA AMENDMENTS) TITLE 24 CCR, PART 11 - 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE TITLE 24 CCR, PART 12 - 2016 CALIFORNIA REFERENCED STANDARDS 2013 ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS W/ A17.1A/CSA B44A13 ADDENDA) 2016 NFPA 13, AUTOMATIC SPRINKLER SYSTEMS (CA AMENDED) 2013 NFPA 14, STANDPIPE SYSTEMS 2013 NFPA 17, DRY CHEMICAL EXTINGUISHING SYSTEMS 2013 NFPA 17A, WET CHEMICAL SYSTEMS 2016 NFPA 20, STATIONARY PUMPS 2013 NFPA 22, WATER TANKS FOR PRIVATE FIRE PROTECTION 2016 NFPA 24, PRIVATE FIRE MAINS 2016 NFPA 72, NATIONAL FIRE ALARM CODE (CA AMENDED) 2016 NFPA 80, FIRE DOORS AND OTHER OPENING PROTECTIVES 2015 NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS 2015 NFPA 253, CRITICAL RADIANT FLUX OF FLOOR COVERING SYSTEMS 2015 NFPA 2001, CLEAN AGENT FIRE EXTINGUISHING SYSTEMS 2003 UL 464, AUDIBLE SIGNAL APPLIANCES 1999 UL 521, HEAT DETECTORS FOR FIRE PROTECTIVE SIGNALING SYSTEMS CFC CH 33 - FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
CHANGES TO THE APPROVED DRAWINGS OR SPECIFICATIONS SHALL BE MADE BY ADDENDA OR CONSTRUCTION CHANGE DOCUMENTS (CCD) APPROVED BY DSA, AS REQUIRED BY SECTION 4-338, PART 1, TITLE 24, CCR. A "DSA CERTIFIED" CLASS 1 PROJECT INSPECTOR EMPLOYED BY THE DISTRICT AND APPROVED BY THE DIVISION OF THE STATE ARCHITECT SHALL PROVIDE CONTINUOUS INSPECTION OF THE WORK.THE DUTIES OF THE INSPECTOR ARE DEFINED IN SECTION 4-342, PART 1, TITLE 24, CCR.
10. ALL WORK SHALL CONFORM TO THE 2016 EDITION TITLE 24, CALIFORNIA CODE OF REGULATIONS.
CONSTRUCTION OF A NEW STUDENT SERVICES BUILDING FOR THE TEHAMA CAMPUS OF SHASTA COLLEGE.
OWNER
STRUCTURAL ENGINEER
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT 11555 OLD OREGON TRAIL REDDING, CA 96049-6006 CONTACT: GEORGE ESTRADA PHONE: 530.242.7929 EMAIL: GESTRADA@SHASTACOLLEGE.EDU
LIONAKIS 1919 19TH STREET SACRAMENTO, CA 95811 CONTACT: LUCAS JOLLY PHONE: 916.558.1900 EMAIL: LUCAS.JOLLY@LIONAKIS.COM
SHARRAH DUNLAP SAWYER 6590 LOCKHEED DRIVE REDDING, CA 96002 CONTACT: TONY MAGDALENO PHONE: 530.221.1792 EMAIL: TMAGDALENO@SDSENGINEERING.COM
MECHANICAL/PLUMBING ENGINEER
DEFERRED SUBMITTALS 1. ALL STOREFRONT OPENINGSSYSTEMS CONTAINING GLAZING, INCLUDING DOORS WITH SIDELIGHTS AND TRANSOMS
PROJECT LOCATION
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ARCHITECT'S STATEMENT
ISSUED
MARK DSA APPLICATION NO. 02-117123
FILE NO. 45-C1
DATE 01/04/2019 05/17/2019
PETERS ENGINEERING 2411 ALHAMBRA BLVD, SUITE 100 SACRAMENTO, CA 95817 CONTACT: SEAN TICHENOR PHONE: 916.447.2841 EMAIL: STICHENOR@PETERSENG.COM
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
THE CIVIL, PLUMBING, MECHANICAL, FIRE PROTECTION, ELECTRICAL, OTHER LISTED DRAWINGS IN THE SHEET INDEX AND SPECIFICATIONS HAVE BEEN PREPARED BY OTHER DESIGN PROFESSIONALS OR CONSULTANTS WHO ARE LICENSED AND/OR AUTHORIZED TO PREPARE SUCH DRAWINGS IN THIS STATE. THESE DOCUMENTS HAVE BEEN EXAMINED BY ME FOR THE DESIGN INTENT AND APPEAR TO MEET THE APPROPRIATE REQUIREMENTS OF TITLE 24, CALIFORNIA CODE OF REGULATIONS AND PROJECT SPECIFICATIONS PREPARED BY ME AND COORDINATION WITH MY PLANS AND SPECIFICATIONS IS ACCEPTABLE FOR INCORPORATION INTO THE CONSTRUCTION OF THIS PROJECT. THE STATEMENT OF GENERAL CONFORMANCE "SHALL NOT BE CONSTRUED AS RELIEVING ME OF MY RIGHTS, DUTIES, AND RESPONSIBILITIES UNDER SECTIONS 17302 AND 81138 OF THE EDUCATION CODE AND SECTIONS 4-336, 4-341, AND 4-344" OF TITLE 24, PART 1. (TITLE 24, PART 1, SECTION 4-317 [b])
05/16/19 SIGNATURE OF ARCHITECT
DATE
JONATHAN McMURTRY
MANAGEMENT
PRINTED NAME
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
C23603
08-31-2019
LICENSE NUMBER
EXPIRATION DATE AGENCY
SHEET IDENTIFICATION LEGEND
CIVIL ENGINEER/ LANDSCAPE ARCHITECT
PROJECT LOCATION
EN . 08 - 3 1 - 1 O F OF CAL I
12. A DSA ACCEPTED TESTING LABORATORY DIRECTLY EMPLOYED BY THE DISTRICT (OWNER) SHALL CONDUCT ALL THE REQUIRED TESTS AND INSPECTIONS FOR THE PROJECT.
PROJECT DIRECTORY
A
R E
11. GRADING PLANS, DRAINAGE IMPROVEMENTS, ROAD AND ACCESS REQUIREMENTS AND ENVIRONMENTAL HEALTH CONSIDERATIONS SHALL COMPLY WITH ALL LOCAL ORDINANCES.
SCOPE OF PROJECT RELATED SITE WORK INCLUDING PAVING AREAS, PARKING AREAS, AND LANDSCAPE.
T
PROJECT
CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE CODES AND REGULATIONS, INCLUDING BUT NOT LIMITED TO:
•
9.
C23603
THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS IS THAT THE WORK OF ALTERATION, REHABILITATION OR RECONSTRUCTION IS TO BE IN ACCORDANCE WITH TITLE 24, CCR. SHOULD ANY EXISTING CONDITIONS SUCH AS DETERIORATION OR NON-COMPLYING CONSTRUCTION BE DISCOVERED WHICH IS NOT COVERED BY THE CONTRACT DOCUMENTS WHEREIN THE FINISHED WORK WILL NOT COMPLY WITH TITLE 24, CCR, A CONSTRUCTION CHANGE DOCUMENT (CCD), OR A SEPARATE SET OF PLANS AND SPECIFICATIONS, DETAILING AND SPECIFYING THE REQUIRED WORK SHALL BE SUBMITTED TO AND APPROVED BY DSA BEFORE PROCEEDING WITH THE WORK (SECTION 4-317(C), PART 1, TITLE 24, CCR)
• • •
8.
D A RCH SE I E N A N McM TE H U T A
IA
MATERIAL MAXIMUM MECHANICAL MEMBRANE MANFACTURER MANHOLE MINIMUM MISCELLANEOUS MASONRY OPENING MOISTURE RESISTANT MOUNTED METAL MULLION NOT IN CONTRACT NUMBER NOMINAL NOT TO SCALE OVER ON CENTER OUTSIDE DIAMETER OWNER FURNISHED / CONTRACTOR INSTALLED OFFICE OBSCURE GLASS OPPOSITE HAND OPENING OPPOSITE POWER ACTUATED FASTENER PROPERTY LINE; PLATE PLASTIC LAMINATE PLUMB PLUMBING PLYWOOD PANEL PROPERTY POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH PAINT; PAINT PARTITION PHOTOVOLTAIC QUARRY TILE RADIUS; RISER ROOF DRAIN REINFORCING STEEL BAR REFERENCE REFRIGERATOR REINFORCE / REINFORCING REQUIRED RESILIENT ROOM ROUGH OPENING REDWOOD RAIN WATER LEADER SEE ARCHITECTURAL DRAWINGS SUSPENDED ACOUSTICAL TILE CEILING SPLASH BLOCK SOLID CORE SCHEDULE STORM DRAIN SELF DRIVING, SELF TAPPING SHEET SHEATHING SHELVING SIMILAR SEALANT SHEET METAL SPECIFICATION SQUARE SANITARY SEWER; SERVICE SINK STAINLESS STEEL
N
MATL MAX MECH MEMB MFR MH MIN MISC MO MR MTD MTL MULL NIC NO NOM NTS O/ OC OD OF/CI
9
EIFS
DETENTION HOLLOW METAL DIAMETER DIMENSION DOWNSPOUT DRY STANDPIPE DRAWING DRAWER EACH EXTERIOR GYPSUM SHEATHING BOARD EXTERIOR INSULATION AND FINISH SYSTEM EXPANSION JOINT ELEVATION ELECTRIC / ELECTRICAL ELEVATOR EMERGENCY ENCLOSURE ELECTRICAL PANEL BOARD EQUAL EQUIPMENT EACH WAY ELECTRIC WATER COOLER EXHAUST EXISTING EXPANSION EXTERIOR FIRE ALARM FLAT BAR FLOOR DRAIN FOUNDATION FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET FINISH FLOORING FLOW LINE FLOOR FACE OF CONCRETE/CURB FACE OF FINISH FACE OF MASONRY FACE OF STUD FACE OF WALL FIREPROOF FIBERGLASS REINFORCED PLASTIC FEET / FOOT FOOTING FURRING FUTURE GROUND; NATURAL GAS GAGE GALVANIZED GRAB BAR GALVANIZED IRON GLUED LAMINATED WOOD GYPSUM HOSE BIB HOLLOW CORE HARDBOARD HARDWARE HARDWOOD HOLLOW METAL HORIZONTAL HOUR HEIGHT INSIDE DIAMETER INSULATION INTERIOR JANITOR KITCHEN ANGLE LABORATORY LAVATORY
A
A2 A-303
DHM DIA DIM DS DSP DWG DWR EA EGSB
ST
SECTION INDICATOR - PARTIAL BUILDING/WALL & DETAIL INDICATOR - AREA
D2 A-512
& @ (E) ' " # ALUM ARCH A/C UNIT A/E AB AC ACC ACS DR ACS PNL ACST AD ADC ADO ADDL ADJ SHV AFF AFG AGGR AHU ASSY BD BKG BLDG BM BM BOT BTWN BUR BW C CAB CB CBC CEM CEM PLAS CFLG CFMF CG CI CJ
SEE UNITED STATES NATIONAL CAD STANDARD FOR ANY ABBREVIATIONS NOT LISTED BELOW. AND AT EXISTING FOOT, FEET INCH(ES) NUMBER ALUMINUM ARCHITECTURAL AIR CONDITIONING UNIT ARCHITECT / ENGINEER ANCHOR BOLT ASPHALTIC CONCRETE ACCESSIBLE ACCESS DOOR ACCESS PANEL ACOUSTIC AREA DRAIN AUTOMATIC DOOR CLOSER AUTOMATIC DOOR OPERATOR ADDITIONAL ADJUSTABLE SHELVING ABOVE FINISHED FLOOR ABOVE FINISHED GRADE AGGREGATE AIR HANDLING UNIT ASSEMBLY BOARD BACKING BUILDING BEAM BENCHMARK BOTTOM BETWEEN BUILT-UP ROOFING BOTH WAYS CHANNEL CABINET CATCH BASIN CALIFORNIA BUILDING CODE CEMENT CEM PLASTER COUNTERFLASHING COLD-FORMED METAL FRAMING CORNER GUARD CAST IRON CONSTRUCTION JOINT / CONTROL JOINT CENTER LINE CEILING CLEAR CONCRETE MASONRY UNIT COUNTER CLEANOUT COLUMN CONCRETE CONSTRUCTION CONTINUE / CONTINUOUS CLEANOUT TO GRADE CONTROL PANEL CARPET COLD ROLLED STEEL COUNTER SUNK CASEWORK CERAMIC TILE CENTER DOUBLE DEPARTMENT DETAIL DRINKING FOUNTAIN
GENERAL NOTES
CT Y R RT
DETAIL INDICATOR - SECTION & DETAIL INDICATOR - SECTION ITEM
B3 A-501
B3 A-301
C
DETAIL INDICATOR - REFERENCE & DETAIL INDICATOR - ITEM
D2 A-512
B3 A-501
LIST OF ARCHITECTURAL ABBREVIATIONS
MAY 17, 2019
R
D2 A-512
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
FLS
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
ARCHITECTURAL SYMBOLS LEGEND
5/15/2019 3:48:54 PM
DATE:
LI J ON C
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
SS
✔
DISCIPLINE DESIGNATORS - LEVEL 1 G H V B C L S A I Q F P D M E W T R X Z O
GENERAL HAZARDOUS MATERIALS SURVEY/MAPPING GEOTECHNICAL CIVIL LANDSCAPE STRUCTURAL ARCHITECTURAL INTERIORS EQUIPMENT FIRE PROTECTION PLUMBING PROCESS MECHANICAL ELECTRICAL DISTRIBUTED ENERGY TELECOMMUNICATIONS RESOURCE OTHER DISCIPLINES CONTRACTOR/SHOP DRAWINGS OPERATIONS
SHEET TYPE DESIGNATORS 0 - GENERAL 1 - PLANS 2 - ELEVATIONS 3 - SECTIONS 4 - LARGE SCALE VIEWS 5 - DETAILS 6 - SCHEDULES & DIAGRAMS 7 - USER DEFINED 8 - USER DEFINED 9 - 3D REPRESENTATIONS
TITLE
COVER SHEET BUILDING IDENTIFIER - WHERE OCCURS DISCIPLINE DESIGNATOR - LEVEL 1 DISCIPLINE DESIGNATOR - LEVEL 2 REPLACE DASH WHERE OCCURS
ARCHITECT
ELECTRICAL ENGINEER
SHEET TYPE DESIGNATOR
LIONAKIS 1919 19TH STREET SACRAMENTO, CA 95811 CONTACT: JONATHAN MCMURTRY PHONE: 916.558.1900 EMAIL: JONATHAN.MCMURTRY@LIONAKIS.COM
PETERS ENGINEERING 2411 ALHAMBRA BLVD, SUITE 100 SACRAMENTO, CA 95817 CONTACT: GINO ROMANO PHONE: 916.447.2841 EMAIL: GROMANO@PETERSENG.COM
SHEET TYPE SUBSET DESIGNATOR LEVEL/SEQUENCE DESIGNATOR
C.A-123AB
AREA IDENTIFIER - WHERE OCCURS
SHEET
UNIQUE PORTION IDENTIFIER - WHERE OCCURS
G-001
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
SHEET INDEX IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
DATE:
FLS
ACS
✔
✔
07/03/2019
SEAL D A RCH SE I E N A N McM TE H U T A
CT Y R RT
R E
N
T
IA
C23603
A
ARCHITECTURAL AS101 ARCHITECTURAL SITE PLAN AS501 ARCHITECTURAL SITE DETAILS A-111 FLOOR PLAN A-112 CLERESTORY / LOWER ROOF PLAN A-121 CEILING PLAN A-131 FINISH FLOOR PLAN A-141 ROOF PLAN A-151 SIGNAGE PLAN A-211 ELEVATIONS - EXTERIOR A-221 ELEVATIONS - INTERIOR A-222 ELEVATIONS - INTERIOR A-311 SECTIONS - BUILDING A-312 SECTIONS - BUILDING A-313 SECTIONS - BUILDING A-314 SECTIONS - BUILDING A-411 LARGE SCALE VIEWS A-511 DETAILS - EXTERIOR A-512 DETAILS - EXTERIOR A-514 DETAILS - ROOF A-521 DETAILS - INTERIOR A-522 DETAILS - INTERIOR A-531 PARTITION TYPES & SCHEDULE A-541 DETAILS - DOOR AND WINDOW A-542 DETAILS - DOOR AND WINDOW A-551 DETAILS - CEILING A-561 DETAILS - CASEWORK A-621 SCHEDULES / DIAGRAMS - DOORS & WINDOWS A-641 SCHEDULE - INTERIOR FINISHES
CONSULTANT
EN . 08 - 3 1 - 1 O F OF CAL I 9
STRUCTURAL S-001 GENERAL NOTES S-011 TYPICAL NOTES S-013 TYPICAL NOTES S-014 TYPICAL NOTES S-111 PLAN - FOUNDATION S-132 PLAN - LOW ROOF FRAMING S-133 PLAN - HIGH ROOF FRAMING S-261 ELEVATIONS - SHEARWALL S-262 ELEVATIONS - SHEARWALL S-263 ELEVATIONS - SHEARWALL S-264 ELEVATIONS - SHEARWALL S-311 SECTIONS - BUILDING S-312 SECTIONS - BUILDING S-531 DETAILS - TYPICAL CONCRETE S-532 DETAILS - TYPICAL CONCRETE S-561 DETAILS - TYPICAL WOOD FRAMING S-562 DETAILS - TYPICAL WOOD FRAMING S-563 DETAILS - TYPICAL WOOD SHEAR WALL FRAMING S-564 DETAILS - TYPICAL MANUFACTURED LUMBER FRAMING S-565 DETAILS - TYPICAL WOOD I-JOIST FRAMING S-566 DETAILS - ROOF FRAMING DETAILS S-567 DETAILS - ROOF FRAMING DETAILS
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
ST
C
REVIEWED FOR ✔
COVER SHEET GENERAL NOTES GRADING, DRAINAGE AND PAVING PLAN UTILITY PLAN INTERIM EROSION CONTROL PLAN HORIZONTAL CONTROL PLAN
LANDSCAPE L-1 PLANTING PLAN IRRIGATION PLAN L-2 LANDSCAPE DETAILS
D
INC:
R
CIVIL C001 C002 C011 C012 C013 C060
APP. 02-117123
LI J ON C
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
1"
GENERAL G-001 COVER SHEET G-002 SHEET INDEX G-101 FIRE LIFE SAFETY SITE PLAN G-111 LIFE SAFETY FLOOR PLAN G-511 ACCESSIBILITY REQUIREMENTS G-512 ACCESSIBILITY REQUIREMENTS G-513 ACCESSIBILTY SIGNAGE STANDARDS AND DETAILS
PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
FIRE PROTECTION FP-0.00 FIRE SPRINKLER - SITE PLAN FP-1.00 FIRE SPRINKLER - PIPING PLAN / SECTION FP-2.00 FIRE SPRINKLER - RCP & ROOF PLANS FP-3.00 FIRE PROTECTION RISER / DETAILS PLUMBING P-001 SYMBOLS, NOTES & SCHEDULES P-101 PLUMBING GAS SITE PLAN P-111 FLOOR PLAN - DRAINAGE PLUMBING P-112 FLOOR PLAN - DOMESTIC PLUMBING P-133 ROOF PLAN - PLUMBING P-501 DETAILS
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
B
MARK
DATE 01/04/2019 05/17/2019
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
TITLE
SHEET INDEX
SHEET
5/15/2019 3:48:55 PM
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
MECHANICAL M-001 SYMBOLS, NOTES & SCHEDULES M-002 MECHANICAL SCHEDULES M-003 MECHANICAL TITLE 24 M-004 MECHANICAL TITLE 24 M-111 FLOOR PLAN - MECHANICAL M-112 PIPING AND CONTROLS FLOOR PLAN - MECHANICAL M-133 ROOF PLAN - MECHANICAL M-401 VRF-1 DIAGRAMS AND DETAILS M-501 DETAILS M-502 DETAILS M-601 MECHANICAL CONTROLS ELECTRICAL E-001 SYMBOLS, NOTES & SCHEDULES E-002 TITLE 24 - INDOOR E-003 TITLE 24 - OUTDOOR E-101 ELECTRICAL SITE PLAN E-111 FLOOR PLAN - POWER E-112 FLOOR PLAN - LOW VOLTAGE E-121 FLOOR PLAN - LIGHTING E-133 ROOF PLAN - POWER E-501 DETAILS E-502 DETAILS E-503 DETAILS E-601 ONE LINE DIAGRAM & PANEL SCHEDULES E-602 ONE LINE DIAGRAM FA-001 SYMBOLS NOTES & SCHEDULES FA-101 FIRE ALARM SITE PLAN FA-111 FLOOR PLAN - FIRE ALARM FA-501 DETAILS FA-601 ONE LINE DIAGRAM AND CALCS TOTAL SHEET COUNT: 104
A
ISSUED
G-002
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
FIRE FLOW INFORMATION
5
GENERAL NOTES
(E) FIR
R 40 '-0" R 60 '-0 "
0 1/4" 1/2"
1"
1.
E LAN
APP. 02-117123
(E) POND
SS
✔
DATE:
0'-0 " R4
E
D
ACS
✔
✔
07/03/2019
NE RE LA (E) F I
(E) ELECTRICAL YARD NE RE LA (E) F I
) (E
N LA
FLS
0'-0 "
(E) GAS METER ENCLOSURE
E FIR
INC:
REVIEWED FOR
ALL FIRE LANES AND CURBS IDENTIFIED ON PLAN ARE EXISTING AND PER PRIOR APPROVALS
E R4
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
R4
ER
TY
LIN
E
0'-0 R 60'-0" "
OP
(E) FH
PR
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
2.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
DIMENSIONS GIVEN TO ASSUMED PROPERTY LINE ARE FOR CODE ANALYSIS PURPOSES ONLY AND SHALL NOT BE USED TO LOCATE BUILDINGS FOR STAKING PURPOSES. SEE CIVIL DRAWINGS FOR EXACT BUILDING LOCATIONS.
LEGEND
(E) FH
PROPERTY LINE (E) BUILDING 1 A# 02-109288
ASSUMED IMAGINARY LINE
(E) BUILDING 3 A# 02-109288
(E) BUILDING WITH NO SCOPE IN THIS PROJECT SEAL
PROPOSED NEW BUILDING D A RCH SE I E N A N McM TE H U T A
N O IN G RK PA
N O IN G RK PA
N O IN G RK PA
0'-6"
R 20 '-0"
PA
R +/- 5
NE LA
IA
N
EN . 08 - 3 1 - 1 O F OF CAL I 9
R E
R
A
E FIR ) (E
T
(E) 20' BARRIER-FREE FIRE TRUCK ACCESS ROAD EMERGENCY FIRE TRUCK ACCESS PATH OF TRAVEL, ROUTE WITH A MINIMUM OF 20' WIDE BY 15'-6" VERTICAL CLEARANCE WITH 50' INSIDE TURNING RADIUS AND AN ADDITIONAL 2' OF WIDTH PROVIDED TO ALLOW FOR CLEARANCE OF APPARATUS BUMPER OVERHANG, TYP. VEHICLE BARRIERS SUCH AS GATES PROVIDED WITH A KNOX BOX AT CAMPUS ENTRY POINTS.
S S TEHAMA CENTER STUDENT SERVICES OCCUPANCY TYPE: A-3(S1)& B(S1) TYPE V-B CONSTRUCTION WITH AUTOMATED FIRE SPRINKLER SYSTEM 9,258 SF J
ST
N O IN G RK PA
N O IN G RK
(E) FIRE LANE SIGN
R 2 (E) FH 8'-0 "
FIRELANE " '-0 P TY
(E) FH
E IR )F E (
NE LA
'-0" (E) FH /- 24 +
" 5'-0
20
(E) TRASH ENCLOSURE
(E) PAVEMENT JOINT
"
(E) FIRE HYDRANT
"
" 8'-4
'-0" 10 +/-
'-6 34 +/-
(E) FH
-0" 40'
±3
" 0'-0 R3 R 49'-0"
C23603
' -0 40
±4
±
0"
R
" 8'-5
'-1" ±28
R 20'-
CT Y R RT
±4
C
(E) BUILDING 2 A# 02-109288
LI J ON C
(E) PARKING A# 02-109288
FIRE FLOW REDUCTION (CFC TABLE B105.1)
FIRE FLOW CALCULATION AREA CONSTRUCTION TYPE AREA FIRE FLOW (GALLONS PER MINUTE)
-
-
9,988 SF TYPE V-B 9,401-11,300 SF 2,750 REQ'D
(CFC TABLE B105.2)
REDUCTION FOR FULLY-SPRINKLERED BUILDING (% REQ'D)x(FIRE FLOW) = (75%)x(2750)
=
75% 2,063 REQ'D
(CFC TABLE C102.1)
REQUIRED NUMBER AND SPACING OF FIRE HYDRANTS: FIRE FLOW REQUIREMENTMINIMUM NUMBER OF HYDRANTS AVERAGE DISTANCE BETWEEN HYDRANTS: MAX. DISTANCE FROM ANY POINT ON THE STREET OR ROAD FRONTAGE TO A HYDRANT -
-
-
-
PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
(E) RPP/FDC
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
2,063 3 HYDRANTS 450 FEET 225 FEET
ISSUED
MARK
R PE O PR
IR )F (E
B
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
E LIN Y T
E AN L E
O AM DI
MANAGEMENT
ND U EN AV
(E) SITE ENTRANCE SIGNAGE W/ TOW AWAY WARNING SIGNAGE
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 ?00.00.00? LIONAKIS 2017
E
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
NORTH
1
FIRE LIFE SAFETY PLAN
AGENCY
SCALE 1" = 50'-0"
FIRE HYDRANT TEST DATA
A
TITLE
FIRE LIFE SAFETY SITE PLAN
5/15/2019 3:48:58 PM
SHEET
G-101
2"
1
2
3
4
5
CODE ANALYSIS LEGEND
0 1/4" 1/2"
1"
USE SQUARE FOOTAGE OCCUPANT LOAD OCCUPANT LOAD FACTOR
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
AREA USE
APP. 02-117123
150 SF/20 7
REVIEWED FOR SS
✔
DATE:
OCCUPANT LOAD THROUGH EXIT ACCESS ELEMENT
FLS
ACS
✔
✔
07/03/2019
###
EXIT LOCATION & NUMBER OF OCCUPANTS USING EXIT
101
"EXIT" SIGNS W/ DIRECTIONAL ARROWS WHERE SHOWN
EXIT
NON-RATED PARTITION 17 A-522
FIRE EXTINGUISHER IN CABINET PER SPECIFICATIONS
18 A-522
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
CODE ANALYSIS 1.
GOVERNING CODE:
2016 CALIFORNIA BUILDING CODE
2.
OCCUPANCY TYPE:
GROUP A-3(S1), B(S1). A-3(S1) GOVERNS AS MOST RESTRICTIVE
3.
CONSTRUCTION TYPE: (CBC 506 & TABLE 506.2)
TYPE V-B, WITH AUTOMATED FIRE SPRINKLER SYSTEM ALLOWABLE AREA AND HEIGHT INCREASES NOT UTILIZED
4.
TABULAR ALLOWABLE HEIGHT AND BUILDING AREA: (CBC 504.3, 504.4, 506.2)
OCCUPANCY GROUP
ALLOWABLE BLDG AREA
MAX NO OF STORIES
ALLOWABLE BLDG HT
GROUP A-3(S1)
24,000 SF
1 STORY
60 FT
ACTUAL
OCCUPANCY GROUP
ACTUAL BLDG AREA
MAX NO OF STORIES
ACTUAL BLDG HT
GROUP A-3(S1)
9,988 SF
1 STORY
35 FT
DETAILED ALLOWABLE BUILDING AREA DETERMINATION (CBC 506.2)
ACTUAL AREA
9,988 SF
FIRE RESISTIVE REQUIREMENTS: (CBC TABLE 601)
STRUCTURAL FRAME 0 HR BEARING WALLS - EXTERIOR 0 HR BEARING WALLS - INTERIOR 0 HR NON-BEARING WALLS & PARTITIONS - EXTERIOR 0 HR (BASED ON FIRE SEPARATION DISTANCE OF 10 FT < X = 0 HR) NON-BEARING WALLS & PARTITIONS - INTERIOR 0 HR FLOOR CONSTRUCTION 0 HR ROOF CONSTRUCTION0 HR SHAFT ENCLOSURES (CBC 713) 0 HR PROJECTIONS 0 HR EXTERIOR DOORS AND WINDOWS UNPROTECTED, NO LIMIT (CBC 705.8.1 EX 2, NON-RATED EXTERIOR WALLS AND STRUCTURAL FRAME) CORRIDORS N/A
3
4
5
6
7
18
ENTRY TOWER 42
D PH
42 36 EXIT
CAMPUS SAFETY 94 SF/ 100 1
1
43
93 SF/ 100 1
1
EXIT
1
94 SF/ 100 1
1
HALLWAY
35
PH
EXIT
96 SF/ 100 1
LOBBY
CLASSROOM/LOBBY OVERFLOW
1,044 SF/ 15 70
626 SF/ 15 42
203 SF/ 100 3
3
ADMIN OFFICES 124 SF/ 100 2
COUNSELOR OFFICES
1 93 SF/ 100 1
1
1 92 SF/ 100 1
1
92 SF/ 100 1
OCCUPANT LOADS: (CBC TABLE 1004.1.2)
TOTAL:
214 OCCUPANTS
9.
TOTAL EGRESS WIDTH: (CBC 1005)
LOBBY EXIT: HALLWAY EXITS:
REQ'D: 36 OCCUPANTS x 0.2" = 7.2" REQ'D: 43 OCCUPANTS x 0.2" = 8.6"
T
R E
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
TEHAMA CENTER STUDENT SERVICES
E
CANOPY
COUNSELOR OFFICES
8.
CT Y R RT
F
C23603
A
C
D A RCH SE I E N A N McM TE H U T A
ST
18
7.
SEAL
IA
2
24,000 SF
N
1
<
9
6.
R
5.
LI J ON C
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
INC:
74 SF/ 100 1
91 SF/ 100 1
1
10. COMMON PATH OF EGRESS TRAVEL: (CBC TABLE 1006.2.1)
TWO EXITS OR EXIT ACCESS DOORWAYS FROM A SPACE SHALL BE PROVIDED WHERE THE COMMON PATH OF TRAVEL EXCEEDS 75'-0"
11. FIRE FLOW REDUCTION (CFC TABLE B105.1) -
FIRE FLOW CALCULATION AREA CONSTRUCTION TYPE AREA FIRE FLOW (GALLONS PER MINUTE)
-
-
-
-
-
9,258 SF TYPE V-B 7,701-9,400 SF 2,500 REQ'D
=
75% 1,875 REQ'D
(CFC TABLE B105.2)
-
REDUCTION FOR FULLY-SPRINKLERED BUILDING (% REQ'D)x(FIRE FLOW) = (75%)x(2500)
(CFC TABLE C102.1)
-
REQUIRED NUMBER AND SPACING OF FIRE HYDRANTS: FIRE FLOW REQUIREMENTMINIMUM NUMBER OF HYDRANTS AVERAGE DISTANCE BETWEEN HYDRANTS: MAX. DISTANCE FROM ANY POINT ON THE STREET OR ROAD FRONTAGE TO A HYDRANT -
C.4
STUDENT SERVICES
PROVIDED: 72" PROVIDED: 36"
12. FIRE EXTINGUISHERS (CBC TABLE 906.3(1))
LIGHT (LOW) HAZARD OCCUPANCY MAXIMUM DISTANCE OF TRAVEL TO EXTINGUISHER TOTAL NUMBER PROVIDED -
-
770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
1,875 2 HYDRANTS 450 FEET 225 FEET
ISSUED
MARK
75 FEET 4
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
5 C
HALLWAY WORK CENTER 345 SF/ 100 4
6
IDF 68 SF/ 300 1
B
CONFERENCE
VET CENTER
398 SF/ 15 27
296 SF/ 15 20
VET OFFICE 124 SF/ 100 2
27
20
HALLWAY 1
1
2
1 STORAGE
CUSTODIAL
RESTROOM
120 SF/ 300 1
79 SF/ 300 1
77 SF
84 SF/ 100 1
80 SF/ 100 1
1
1
80 SF/ 100 1
80 SF/ 100 1
1
1
96 SF/ 100 1
1
1
EXIT
PH
EXIT
FIRE RISER
2 97 SF/ 100 1
17
1 FACULTY OFFICE
114 SF/ 100 2
B.6
81 SF/ 100 1
STUDENT SERVICES
80 SF/ 100 1
1
80 SF/ 100 1
1
80 SF/ 100 1
1
80 SF/ 100 1
1
82 SF/ 100 1
FACULTY OFFICES
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
1
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
B 4
CANOPY
FACULTY HALLWAY
5 AGENCY
A
PLAN NORTH
1
A
LIFE SAFETY FLOOR PLAN - LEVEL 1 SCALE 1/8" = 1'-0"
TITLE
LIFE SAFETY FLOOR PLAN
SHEET
5/15/2019 3:49:00 PM
017294 ?00.00.00? LIONAKIS 2017
G-111
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR
FIN. FACE OF WALL WHERE OCCURS 12" MIN 17" MIN 18" MAX
40" MAX 1'-7" MAX 1 '- 5" MIN
33"-36" TO TOP OF GB
5'-0" MIN CLR
D
FLS
ACS
✔
✔
07/03/2019
4'-0" MIN 12" MAX
24" MIN
GB48 STPH OR TPH
SANITARY NAPKIN DISPOSAL, ADJACENT TO TPH - 19" AFF MAX TO OPENING
ACC WC (ACCESSIBLE WATER CLOSET)
7"-9" 54" MIN
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
ACC WC (ACCESSIBLE WATER CLOSET)
19" MAX
FEC (FIRE EXTINGUISHER CABINET)
11" MIN 6" MIN TOE SPACE ACC SINK ELEVATION
ACC LAV ELEVATION
MOP RACK
2'-6"
10" MIN
10" MIN
INSULATE EXPOSED SUPPLY AND DRAIN PIPES WHERE OCCURS
27" MIN
INSULATE ALL SUPPLY AND DRAIN PIPES, TYP
11" MIN 6" MAX TOE SPACE
ACC LAV (ACC SINK SIM.)
8" MIN
27" MIN
SD
SH (SHELF)
19" MIN
8" MIN
29" MIN
34" MAX
PTD
40" MAX TO REFL SURFACE
MI-S
18" MIN
48" MAX
8" X 4'-0" SHELF, UNO
48" MAX TO ALL OPERABLE PARTS OF CABINET AND F.E. HANDLE
CONSULTANT
48" MAX
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
GB42
DATE:
33"-36" TO TOP OF GB
FIN. FACE OF WALL 24" MIN
VALVE BUTTON
FACE OF WALL OR EDGE OF LAV
✔
MR & SSK (MOP RACK & MOP SINK)
ALL OPERATING MECHANISMS SHALL BE NO HIGHER THAN 3'-4" ABOVE FINISHED FLOOR AT ACCESSIBLE TOILET ROOMS
SEAL
MI-S / MI (MIRROR STAINLESS / MIRROR)
19" MIN TO OUTLET
PTD/WR (PAPER TOWEL DISPENSER / WASTE RECEPTACLE)
TPH (TOILET PAPER HOLDER)
TSCD (TOILET SEAT COVER DISPENSER)
IA
N
R E
EN . 08 - 3 1 - 1 O F OF CAL I 9
A
C
PTD (PAPER TOWEL DISPENSER)
T
R
40" MAX
C23603 ST
SD (SOAP DISPENSER)
CT Y R RT
LI J ON C
D A RCH SE I E N A N McM TE H U T A
PROJECT
TEHAMA CENTER STUDENT SERVICES
NOTE: 1. AT ACCESSIBLE TOILET STALLS, OPENING FOR PARTITION DOOR SHALL BE MIN. 34" CLEAR, DOOR SHALL BE SELF CLOSING, AND AN ACCESSIBLE DOOR PULL SHALL BE PLACED ON BOTH SIDES OF THE DOOR NEAR THE LATCH. 2. PROVIDE BACKING FOR ALL WALL HUNG ACCESSORIES, SEE TYPICAL BACKING DETAIL 3. BACKING LOCATIONS SHALL BE COORDINATED W/ ANCHORAGE LOCATIONS, TYP. 4. SEE INTERIOR ELEVATIONS FOR DEFINITIONS OF ACCESSORY ABBREVIATIONS. 5. WHERE WALL MOUNTED EQUIPMENT IS LOCATED ABOVE COUNTER/WORK SURFACE, HEIGHT TO OPERABLE PART SHALL BE 46" MAX. FOR PARALLEL APPROACH. 6. WHERE WALL MOUNTED EQUIPMENT IS LOCATED ABOVE COUNTER/WORK SURFACE, HEIGHT TO OPERABLE PART FOR FORWARD APPROACH IS 48" MAX. WHEN COUNTER/WORK SURFACE IS A MAXIMUM OF 20" DEEP. WHEN REACH DEPTH IS BETWEEN 20" AND THE MAXIMUM ALLOWABLE OF 25", THE HEIGHT TO OPERABLE PARTS SHALL BE 44" MAX. 7. CONTRACTOR IS RESPONSIBLE FOR COORDINATING THAT MAXIMUM DIMENSIONS ARE NOT TO BE EXCEEDED AND MINIMUM CLEARANCES ARE NOT LESS THAN THE MINIMUM DIMENSIONS LISTED.
770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
INTERIOR - ACCESSORIES - MOUNTING HEIGHTS & LOCATIONS
14
0500_0000_ACC MOUNTING HEIGHTS_01 171108
1/4" = 1'-0"
ISSUED
MARK
1 1/2"
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
ABOVE
12" MIN. CLR.
WALL, SEE PLAN FOR TYPE
DATE 01/04/2019 05/17/2019
ESCUTCHEON PLATE 1 1/2" SS TUBING GRAB BAR FOR MOUNTING HEIGHTS SEE 14 G-511
19
WOOD STUD (3) #12 PAN HEAD WOOD SCREWS W/ 1 1/2" MIN EMBED INTO BACKING
25" MAX REACH DEPTH (SEE NOTE)
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
GRAB BARS 0500_1080_ACC GRAB BAR MOUNTING_01 150901. Q2
3" = 1'-0"
FINISH FACE OF WALL WITH ELECTRICAL RECEPTACLES OR SWITCH
5'-0" CLR
6"
TYPICAL TOILET CLEARANCE
17" MIN 19" MAX
2'-6"
11 G-512
30" X 48" CLEAR FLOOR WHEELCHAIR SPACE
REACH OVER OBSTRUCTION 0500_0000_REACH OVER_01 ?YYMMDD?
20
4'-0" CLR
4'-8" CLR (WALL MTD TOILETS)
36" MIN 24" MIN
19" MIN
4'-0"
ALLOWABLE KNEE SPACE REDUCTION AT PLUMBING FIXTURES SEE
4'-0"
1
36" MIN 12" MIN T-SHAPED TURNING SPACE
2'-6"
2'-6"
VARIES
1 1/2" = 1'-0"
12" MIN
5'-0" CLEARANCE CIRCLE
(SEE NOTE)
16
" '-0
4'-0"
28"-34"
NOTE: TOE SPACE MUST BE EQUAL TO, OR GREATER THAN 6 REACH DEPTH
10" MIN
29" MIN AT LAVATORIES
A
ø5
60" MIN
60" MIN
19" MIN TOE SPACE DEPTH
5/15/2019 3:49:01 PM
ANCHOR SCHEDULE METAL STUD (3) #12 SDST SCREWS INTO TYPE 'C' BACKING
CMU / CONCRETE (3) 1/4" DIA 'HILTI' KWIK-CON II W/ 1 3/4" EMBED
27" MIN AT WORK COUNTERS AND SINKS
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
1 1/2" MIN. CLR. BELOW
B
TYPICAL SINK CLEARANCE
TYPICAL LAVATORY CLEARANCE
NOTE: FOR REQUIRED KNEE / TOE CLEARANCES @ ACCESSIBLE SINK / LAVATORY LOCATIONS, SEE 14 G-511
ACCESSIBILITY REQUIREMENTS
SHEET
ACCESSIBILITY CLEARANCES 1/4" = 1'-0"
TITLE
0500_0000_ACC CLEARANCES_01 171108
G-511
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
DATE:
FLS
ACS
✔
✔
07/03/2019
2
MAX
1/4" MAX
1/4" MAX
1/2" MAX
1
'P'
PROTRUDING OBJECT
PROTRUDING OBJECT
MAXIMUM HEIGHTS AT ALL THRESHOLDS
4" MAX IF 'X' > 27"
D
1
2
PROVIDE CANE DETECTABLE ELEMENT IF 'P' > 4" AND 'X' > 27"
80" MIN
1/2" MAX
MAX
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
'X'
'X'
MAXIMUM HEIGHT AT SLOPED LEVEL CHANGE
1/4" MAX
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
CARPET WILL NOT EXCEED 1/2" HIGH PILE WHERE INSTALLED CARPET TO BE PERMANENTLY AND SECURELY AFFIXED TO FLOOR
FINISHED FLOOR
MAXIMUM HEIGHT AT LEVEL CHANGE WITH NO TRANSITION
13
FLOORING TRANSITION 0520_0960_FLOORING TRANSITION_01 170614. Q2
6" = 1'-0"
17
PROTRUDING OBJECTS 0500_0000_PROTRUDING OBJECTS_01
1/2" = 1'-0"
LEVER
SEAL
PUSH
2. LATCHING AND LOCKING DOORS THAT ARE HAND-ACTIVATED AND WHICH ARE IN ACCESSIBLE ROUTE, SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER-TYPE HARDWARE, PANIC BARS OR OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE. LOCKED EXIT DOORS SHALL OPERATE AS ABOVE IN EGRESS DIRECTION.
10
ACCESSIBLE DOOR HARDWARE REQUIREMENTS 1" = 1'-0"
0500_0870_ACCESSIBLE DOOR HARDWARE REQUIREMENTS_01 170614. Q2
14
PUSH SIDE
0500_0850_ACCESSIBLE DOOR SURFACE REQUIREMENTS_01 170614. Q2
18" MIN CLR @ INTERIOR DOOR
SWITCHES
PUSH SIDE
CLEAR OPENING
32" MIN
PULL SIDE
MIN
PROVIDE THIS ADDITIONAL SPACE IF DOOR IS EQUIPED WITH A LATCH AND A CLOSER 1'-0"
24" MIN CLR @ EXTERIOR DOOR
CLEAR SPACE FINISH ELEVATION TO MATCH FINISH FLOOR ELEVATION AT DOOR
FIRE ALARM
ACCESSIBLE PATH OF TRAVEL IS BARRIER FREE
THERMOSTAT
SLIP RESISTANT SURFACE (MEDIUM BROOM FINISH)
48" MIN IF DOOR HAS A LATCH AND CLOSER
PULL SIDE
KICK PLATE
FINISHED FLOOR
36" MIN
11
CLEAR OPENING
32" MIN
PUSH SIDE
54" MIN
0500_0000_ACCESSIBLE MOUNTING HEIGHT REQUIREMENTS_01 170614. Q2
ACCESSIBLE ROUTE WALK 1/4" = 1'-0"
0500_0000_ACCESSIBLE ROUTE WALK_01 170614. Q1
1.
2. 3.
1.
3.
HAND ACTIVATED DOOR OPENING HANDLE AND HARDWARE. PER CBC 11B-404.2.7 & 11B-309.4 90 12°
60" MIN
48" MIN IF DOOR HAS A CLOSER
4. 5.
1.
24" MIN
3. 4.
CLEAR OPENING
NOTE : DOOR CLOSERS, IF PRESENT, MUST BE SET SO THAT IT TAKES DOOR AT 1. LEAST 5 SECONDS TO CLOSE FROM AN OPEN POSITION OF 90 DEGREES TO 12 DEGREES FROM THE LATCH PER 11B-404.2.8.1.
2.
ACCESSIBLE DOOR CLEARANCES 1/2" = 1'-0"
0500_0850_ACCESSIBLE DOOR CLEARANCES_01 170614. Q2
FORCE REQUIRED TO OPERATE DOOR SHALL BE 5 LBS MAXIMUM PRESSURE AT INTERIOR AND EXTERIOR DOORS AND 15 LBS MAXIMUM TO OPERATE AT FIRE DOORS WHERE ALLOWED BY THE AHJ PER CBC 11B-404.2.9.
IA
N
9
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
OBJECTS PROJECTING FROM WALLS WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80 INCHES ABOVE THE FINISHED FLOOR SHALL PROTRUDE NO MORE THAN 4" INTO WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES. OBJECTS MOUNTED WITH THEIR LEADING EDGES AT OR BELOW 27 INCHES ABOVE THE FINISHED FLOOR MAY PROTRUDE ANY AMOUNT. FREE-STANDING OBJECTS MOUNTED ON POSTS / PYLONS MAY OVERHANG 12 INCHES MAXIMUM FROM 27 INCHES TO 80 INCHES ABOVE THE GROUND OR FINISHED FLOOR. PROTRUDING OBJECTS SHALL NOT REDUCE THE REQUIRED CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING SPACE. ANY OBSTRUCTION OVERHANGING A PEDESTRIAN WAY SHALL BE A MINIMUM OF 80 INCHES ABOVE THE WALKING SURFACE AS MEASURED TO THE BOTTOM OF THE OBSTRUCTION.
12
ACCESSIBLE DOOR CLOSER REQUIREMENTS 1/2" = 1'-0"
0500_0850_ACCESSIBLE DOOR CLOSER REQUIREMENTS_01
SURFACE SLOPES OF ACCESSIBLE PARKING SPACES AND ACCESS AISLES SHALL NOT EXCEED 1/4 INCH PER FOOT (2% GRADIENT) IN ANY DIRECTION. ACCESSIBLE PARKING SPACES SHALL BE LOCATED SO AS NOT TO REQUIRE USERS TO TRAVEL OR WALK BEHIND ANY PARKING SPACE OTHER THAN THEIR OWN. IN EACH PARKING AREA, A BUMPER OR CURB SHALL BE PROVIDED AND LOCATED TO PREVENT ENCROACHMENT OF CARS OVER THE REQUIRED WIDTH OF WALKWAYS. PARKING SPACES RESERVED FOR PERSONS WITH DISABILITIES SHALL BE IDENTIFIED BY A REFLECTORIZED SIGN PERMANENTLY POSTED IMMEDIATELY ADJACENT TO AND VISIBLE FROM EACH STALL OR SPACE CONSISTING OF A PROFILE VIEW OF A WHEELCHAIR WITH OCCUPANT, IN WHITE ON DARK BLUE BACKGROUND. THE SIGN SHALL NOT BE SMALLER THAN 70 INCHES IN AREA AND, WHEN IN AN ACCESSIBLE ROUTE, SHALL BE POSTED AT A MINIMUM HEIGHT OF 80 INCHES FROM THE BOTTOM OF THE SIGN TO THE PARKING SPACE FINISHED GRADE. SIGNS MAY ALSO BE MOUNTED ON THE WALL AT THE INTERIOR END OF THE PARKING SPACE AT A MINIMUM HEIGHT OF 60 INCHES FROM THE PARKING SPACE FINISHED GRADE, GROUND, OR WALK.
TITLE
ACCESSIBILITY REQUIREMENTS
DISCREPANCIES 1.
NOTE: AREA MUST NOT EXCEEED A SLOPE OF 2% IN ANY DIRECTION
8
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
PARKING
2.
A
CLIENT
°
HINGE APPROACH DOOR CLEARANCES, TYP 44" MIN
MINIMUM CLEAR FLOOR OR GROUND SPACE REQUIRED TO ACCOMMODATE A SINGLE, STATIONARY WHEELCHAIR AND OCCUPANT IS 30 INCHES BY 48 INCHES. MINIMUM CLEAR FLOOR OR GROUND SPACE FOR WHEELCHAIRS MAY BE POSITIONED FOR FORWARD OR PARALLEL APPROACH TO AN OBJECT, UNLESS RESTRICTED BY CODE. FLOOR OR GROUND SPACE FOR WHEELCHAIRS MAY BE PART OF THE KNEE SPACE REQUIRED UNDER SOME ELEMENTS AS ALLOWED BY CODE. PROVIDE A MINIMUM CLEAR SPACE 60 INCHES WIDE AT ALCOVES GREATER THAN 15 INCHES DEEP AND DESIGNED FOR SIDE APPROACH. PROVIDE A MINIMUM CLEAR SPACE 36 INCHES WIDE AT ALCOVES GREATER THAN 24 INCHES DEEP AND DESIGNED FOR FRONT APPROACH.
770 DIAMOND AVE RED BLUFF, CA 96080
HAZARDOUS AND PROJECTING OBJECTS
PUSH SIDE PULL SIDE LATCH APPROACH DOOR CLEARANCES, TYP 5/15/2019 3:49:02 PM
1/2" = 1'-0"
15
MIN 60" X 60" CLEAR SPACE AND LEVEL 2% MAX SLOPE AREAS AT ENTRANCE OR PASSING SPACE
2.
32" MIN
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
NO LEVEL CHANGE
MIN
IN NEW CONSTRUCTION, ALL PRIMARY ENTRANCES AND EXTERIOR GROUND FLOOR EXIT DOORS TO BUILDINGS AND FACILITIES SHALL BE ACCESSIBLE TO THE DISABLED. 2. IN EXISTING BUILDINGS WHERE NOT ALL ENTRANCES ARE ACCESSIBLE, ALL ACCESSIBLE ENTRANCES SHALL BE IDENTIFIED WITH AT LEAST ONE STANDARD INTERNATIONAL SYMBOL OF ACCESSIBILITY SIGN AND WITH ADDITIONAL DIRECTIONAL SIGNS, AS REQUIRED, VISIBLE FROM APPROACHING PEDESTRIAN WAYS. 3. EVERY REQUIRED ENTRANCE OR PASSAGE DOORWAY SHALL BE OF A SIZE AS TO PERMIT THE INSTALLATION OF A DOOR NOT LESS THAN 36 INCHES IN WIDTH, AND NOT LESS THAN 80 INCHES IN HEIGHT. DOORS SHALL BE CAPABLE OF OPENING AT LEAST 90 DEGREES AND SHALL BE MOUNTED SO THAT THE CLEAR WIDTH THE DOORWAY IS NOT LESS THAN 32 INCHES. 4. LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED AND WHICH ARE PART OF AN ACCESSIBLE ROUTE OR SPACE, SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE HARDWARE, PANIC BARS, PUSH-PULL ACTIVATING BARS. OR OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP THE OPENING HARDWARE. 5. HAND ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED BETWEEN 34 INCHES MINIMIUM AND 44 INCHES MAXIMUM ABOVE THE FLOOR. 6. THE FLOOR OR LANDING LENGTH ON EACH SIDE OF AN ENTRANCE OR A PASSAGE DOOR SHALL BE LEVEL AND CLEAR AT LEAST 60 INCHES IN THE DIRECTION OF THE DOOR SWING AND AT LEAST 48 INCHES OPPOSITE THE DIRECTION OF THE DOOR SWING AS MEASURED AT RIGHT ANGLES TO THE FACE OF THE DOOR IN THE CLOSED POSITION. THE WIDTH OF THE LEVEL AND CLEAR AREA ON THE SIDE WHICH THE DOOR SWINGS SHALL EXTEND A MINIMUM OF 24 INCHES PAST THE STRIKE EDGE OF THE DOOR FOR DOORS WITH LATCH SIDE APPROACH AND 36 INCHES FOR DOORS REQUIRING HINGE SIDE APPROACH. 7. THE FLOOR OR LANDING SHALL NOT BE MORE THAN 1/2 INCH LOWER THAN THE THRESHOLD OF THE DOORWAY. CHANGES IN LEVEL BETWEEN 1/4 INCH AND 1/2 INCH SHALL BE BEVELED WITH A SLOPE NO GREATER THAN 1:2. 8. THE BOTTOM 10 INCHES OF ALL DOORS (EXCEPT AUTOMATIC AND SLIDING) SHALL HAVE A SMOOTH UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION WHERE NARROW FRAME DOORS ARE USED, A 10 INCH HIGH SMOOTH PANEL SHALL BE INSTALLED ON THE PUSH SIDE OF THE DOOR, WHICH WILL ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST. 9. THE MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED 5 LBS. FOR EXTERIOR OR INTERIOR DOORS. SUCH PULL OR PUSH EFFORT BEING APPLIED AT RIGHT ANGLES TO HINGED DOORS AND AT THE CENTER PLANE OF SLIDING OR FOLDING DOORS. COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS MAY BE UTILIZED TO MEET THE ABOVE STANDARDS. WHEN FIRE DOORS ARE REQUIRED, THE MAXIMUM EFFORT TO OPERATE THE DOOR MAY NOT EXCEED 15 LBS. 10. EACH GRADE-LEVEL EXTERIOR EXIT DOOR SHALL BE IDENTIFIED BY A TACTILE SIGN WITH THE WORD "EXIT". EACH EXIT DOOR THAT LEADS DIRECTLY TO GRADE-LEVEL EXTERIOR EXIT BY MEANS OF STAIRWAY OR RAMP IS IDENTIFIED BY A TACTILE SIGN THAT STATES "EXIT STAIR DOWN," "EXIT RAMP DOWN," "EXIT STAIR UP," OR "EXIT RAMP UP" AS APPROPRIATE. EACH EXIT DOOR THAT LEADS DIRECTLY TO GRADE-LEVEL EXTERIOR EXIT BY MEANS OF AN EXIT ENCLOSURE OR EXIT PASSAGEWAY IS IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "EXIT ROUTE." EACH ACCESS DOOR FROM AN INTERIOR ROOM OR AREA TO A CORRIDOR OR HALLWAY THAT IS REQUIRED TO HAVE A VISUAL EXIT SIGN IS IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "EXIT ROUTE". EACH DOOR THROUGH A HORIZONTAL EXIT IS IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "TO EXIT."
CLEAR FLOOR SPACE FOR WHEELCHAIRS
24"
OBJECT WHERE OCCURS
ACCESSIBLE MOUNTING HEIGHT REQUIREMENTS
5% MAX
2% MAX
36" MIN
MIN
4'-0"
CONVENIENC E WALL OUTLET 18" MIN UON
60" MIN
34" MIN
44" MIN
44" MAX
FRONT APPROACH DOOR CLEARANCES, TYP
48" MAX
4'-0"
UNOBSTRUCTED
B 5'-0"
TEHAMA CENTER STUDENT SERVICES
1.
WHERE AN OBSTRUCTION IS MORE THAN 8", PROVIDE THE NOTED CLEAR SPACE
DOOR HANDLE/ PANIC HARDWARE WHERE OCCURS
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
ENTRANCES AND DOORS:
ACCESSIBLE DOOR SURFACE REQUIREMENT 3" = 1'-0"
R E
R
SMOOTH, UNINTERRUPTED SURFACE
10" MIN - FULL WIDTH OF DOOR
34"- 44"
C
T
A
1. HAND-ACTIVATED DOOR OPENING HARDWARE, HANDLES, PULLS, LATCHES. LOCKS AND OTHER OPERATING DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT GRASPING. TIGHT PINCHING OR TWISTING OF THE WRIST TO OPERATE.
C23603 ST
LOOP
DOOR OTHER THAN SLIDING DOOR IN ACCESSIBLE PATH OF TRAVEL
CT Y R RT
LI J ON C
D A RCH SE I E N A N McM TE H U T A
THE INFORMATION DEPICTED ON THIS SHEET REPRESENT BUILDING CODE REQUIREMENTS. NOTIFY THE ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES ON THIS PROJECT THAT WOULD CREATE A CONFLICT WITH THE PLANS OR ACCESS REQUIREMENTS.
20
ACCESSIBLE ROUTE NOTES 1/2" = 1'-0"
0500_0000_ACCESSIBLE PATH OF TRAVEL NOTES_01 ?YYMMDD?. Q1
SHEET
G-512
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR
1. 2. 3.
ALL SYMBOLS TO CONSIST OF A WHITE FIGURE ON A BLUE BACKGROUND BLUE TO APPROXIMATE FS15090 IN FEDERAL STANDARD 595C ALTERNATE COLORS MAY BE USED IF APPROVED BY THE AUTHORITY HAVING JURISDICTION, BUT CONTRAST MUST REMAIN - EITHER DARK ON LIGHT OR LIGHT ON DARK SEE SIGNAGE PLAN AND SPECIFIC SIGN DETAILS FOR SIZES AND APPLICATION
NOTE: 1. MOUNT SIGN CENTERED 60" AFF ON EXTERIOR SIDE OF THE DOOR.
DATE:
FLS
ACS
✔
✔
07/03/2019
1'-0" MIN
2'-0" MIN
1 1/2" HIGH CHARACTERS VOLUME CONTROL TELEPHONE
INTERNATIONAL SYMBOL OF TTY
70" AFF MAX BOT OF HIGHEST LINE OF RAISED CHARACTERS
MAXIMUM OCCUPANT LOAD XXXX BY ORDER OF THE STATE FIRE MARSHAL
FIRE SPRINKLER RISER INSIDE
TAMPERPROOF SCREWS
CONSULTANT
MOUNT ACCORDING TO PROJECT NEEDS WITHIN VISUAL CHARACTER HEIGHT TABLE 11B-703.5.5
INTERNATIONAL SYMBOL OF ACCESS FOR HEARING LOSS
TAMPERPROOF SCREWS
OCCUPANCY LOAD SIGN
9
0570_1014_ STANDARD SYMBOLS_01 170614. Q1
1/2" = 1'-0"
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
40" AFF MIN BOT OF LOWEST LINE OF CHARACTERS
STANDARD SYMBOLS
5
1 1/2" HIGH CHARACTERS 6" MIN
INTERNATIONAL SYMBOL OF ACCESSIBILITY (ISA)
D
16" MIN
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
4.
NOTES: 1. PER CBC 1004.3, EVERY ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL HAVE THE OCCUPANT LOAD OF THE ROOM OR SPACE POSTED... 2. PER CFC 1004.3, EVERY ROOM OR SPACE WHICH IS USED FOR ASSEMBLY, CLASSROOM, DINING, DRINKING, OR SIMILAR PURPOSES HAVING AN OCCUPANT LOAD OF 50 OR MORE SHALL HAVE THE OCCUPANT LOAD OF THE ROOM OR SPACE POSTED... 3. SIGN TO BE POSTED NEAR MAIN EXIT (CBC 1004.3), SEE SIGNAGE PLAN FOR LOCATIONS AND SIGN INFORMATION 4. VERIFY INFORMATION FROM ARCHITECT PRIOR TO SIGN FABRICATION 5. OCCUPANT LOAD DETERMINED FROM THE LIFE SAFETY EXITING PLAN SHEET
✔
AE_G_0570_004 150901. Q2
1 1/2" = 1'-0"
MISCELLANEOUS SIGNS
13
3" = 1'-0"
Q1 NOTES:
PICTOGRAM AND BACKGROUND TO HAVE NON-GLARE FINISH PICTOGRAM TO CONTRAST WITH BACKGROUND, EITHER DARK ON LIGHT OR LIGHT ON DARK
NOTES:
3. 4. 5. 6. 7.
6
3.
5. 6.
NOTES: 1. PERMANENT SIGNAGE TO BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. 2. MOUNTING LOCATION MUST ALLOW A PERSON TO APPROACH WITHIN 3" OF SIGNAGE WITHOUT ENCOUNTERING PROTRUDING OBJECTS OR STANDING WITHIN THE SWING PATH OF THE DOOR. PROVIDE 18" SQUARE CLEAR FLOOR AREA AT TACTILE SIGNS. 3. SIGNS AND IDENTIFICATION SHALL BE FIELD INSPECTED AFTER INSTALLATION AND APPROVED BY THE ENFORCING AGENCY, IN ACCORDANCE WITH SECTION 11B-703.1.1.2 "INSPECTION" AS 9" 9" REQD CLR FLR SPACE REQD CLR FLR SPACE REQD RAISED CHARACTERS (ROOM NAME AND NUMBER) 60" AFF MAX BOT OF HIGHEST LINE OF RAISED CHARACTERS CORRESPONDING BRAILLE CL 48" AFF MIN BOT OF LOWEST SHOW ALL LINES CENTERED LINE OF BRAILLE
7
7. 8. 9.
3" MIN
HEIGHT TO FINISH FLOOR OR GROUND FROM BASELINE OF CHARACTER 40 inches (1016 mm) to less than or equal to 70 inches (1778 mm)
Greater than 70 inches (1778 mm) to less than or equal to 120 inches (3048 mm)
Greater than 120 inches (3048 mm)
AT DOOR
14
11 G-512
MINIMUM CHARACTER HEIGHT
Less than 72 inches (1829 mm)
5/8 inch (15.9 mm)
72 inches (1829 mm) and greater
5/8 inch (15.9mm), plus 1/8 inch (3.2 mm) per foot (305 mm) of viewing distance above 72 inches (1829 mm)
Less than 180 inches (4572 mm)
2 inches (51 mm)
180 inches (4572 mm) and greater
2 inches (51 mm), plus 1/8 inch (3.2 mm) per foot (305 mm) of viewing distance above 180 inches (4572 mm)
Less than 21 feet (6401 mm)
3 inches (76 mm)
21 feet (6401 mm) and greater
3 inches (76 mm), plus 1/8 inch (3.2 mm) per foot (305 mm) of viewing distance above 21 feet (6401 mm)
0570_1014_DIRECTIONAL AND INFORMATIONAL SIGNS_01 170614. Q1
1/2" = 1'-0"
IA
ABC CLIENT
BELOW CEILING
0570_1014_ASSISTIVE LISTENING SIGNAGE_01 170614. Q2
18
PICTOGRAM REQUIREMENTS 0570_1014_PICTOGRAM REQUIREMENTS_01 170614. Q1
1/2" = 1'-0"
ISSUED
MARK 1/32" RAISED TEXT AT WALL SIGN
ILLUMINATED EXIT SIGN, IF REQD BY SFM
EXIT
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
60" AFF MAX BOT OF HIGHEST LINE OF RAISED CHARACTERS
1/8" BACKPLATE AT WALL SIGN
EQ
EQ
20 G-513
CONTRACTED GRADE 2 BRAILLE AT WALL SIGN 48" AFF MIN BOT OF LOWEST LINE OF BRAILLE 1/4" BACKING AT DOOR SIGN FOR EACH CIRCLE AND TRIANGLE
16 G-513
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
SEE
6 G-513
15
017294 ?00.00.00? LIONAKIS 2017
FOR MOUNTING INFO.
CHARACTERS AND BRAILLE PER
DIRECTIONAL AND INFORMATIONAL SIGNS
11
0570_1014_ROOM ID SIGN_01 170614. Q2
N
770 DIAMOND AVE RED BLUFF, CA 96080
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ASSISTIVE LISTENING SIGN 1/4" = 1'-0"
TEHAMA CENTER STUDENT SERVICES
FOR TEXT SIZE AND MOUNTING HEIGHT
AT WINDOW
EN . 08 - 3 1 - 1 O F OF CAL I
CL
HORIZONTAL VIEWING DISTANCE
TYP
PERMANENT ROOM IDENTIFICATION SIGNS 1/4" = 1'-0"
CHARACTERS AND THEIR BACKGROUND MUST HAVE A NON-GLARE FINISH CHARACTERS MAY BE UPPERCASE, LOWERCASE, OR A COMBINATION OF BOTH CHARACTERS MUST BE SANS SERIF; WITHOUT ITALICS, SCRIPT, OR OTHER DECORATIVE OR UNUSUAL FORMS CHARACTERS MUST BE SELECTED FROM FONTS WHERE THE WIDTH OF THE UPPERCASE "O" IS 60-110% OF THE HEIGHT OF THE UPPERCASE "T". FLOOR PLANS PROVIDING EMERGENCY INFORMATION DO NOT NEED TO COMPLY WITH THIS REQUIREMENT CHARACTERS MUST BE SELECTED FROM FONTS WHERE THE STROKE THICKNESS OF THE UPPERCASE "I" IS 10-20% OF THE HEIGHT OF THE LETTER CHARACTER SPACING, MEASURED BETWEEN THE TWO CLOSEST POINTS OF ADJACENT CHARACTERS, MUST BE 10-35% OF THE CHARACTER HEIGHT SPACING BETWEEN BASELINES OF MULTI-LINE TEXT MUST BE 135-170% OF THE CHARACTER HEIGHT TEXT MUST BE IN A HORIZONTAL FORMAT TEXT MUST MEET THE FOLLOWING HEIGHT REQUIREMENTS FOR VIEWING DISTANCE:
SEE
R E
PROJECT
TABLE 11B-703.5.5 VISUAL CHARACTER HEIGHT
NOTES: 1. VERIFY ROOM NAMES W/ ARCHITECT BEFORE FABRICATION 2. MOUNTED TO WALL PER SPECIFICATIONS 3. CENTER CHARACTERS AND BRAILLE 4. IF SIGN TACTILE CHARACTERS ARE NOT CENTERED, CLEAR FLOOR AREAS NEED TO BE ADJUSTED. SEE 20 G-511 8 CHARACTERS AND BRAILLE PER G-513
8 G-513
8 G-513
CHARACTERS AND BRAILLE PER TYP
TACTILE EXIT SIGNAGE
19
1/2" = 1'-0"
AGENCY
TYP
RESTROOM SIGNAGE 0570_1014_RESTROOM SIGNAGE_02 150901. Q2
1/4" = 1'-0"
Q1 PROVIDE SIGNAGE PER: CBC 11B-703
60" AFF MAX
"
BOT OF LOWEST LINE OF BRAILLE EXIT ROUTE
BRAILLE REQUIREMENTS AND LEGEND:
EXIT ROUTE
A RAISED CHARACTER REQUIREMENTS AND LEGEND:
A. CHARACTERS SHALL BE RAISED 1/32" MINIMUM ABOVE THEIR BACKGROUND. B. CHARACTER HEIGHT SHALL BE A MINIMUM OF 5/8" AND A MAXIMUM OF 2" HIGH BASED ON THE UPPERCASE "I". C. CHARACTERS SHALL BE SEPARATED FROM ANY RAISED BORDER OR DECORATIVE ELEMENT BY 3/8" D. CHARACTER FONT PROPORTION WITH THE UPPERCASE 'O' WIDTH BEING 60 PERCENT MINIMUM TO 110 PERCENT MAXIMUM THE HEIGHT OF THE UPPERCASE 'I'. E. CHARACTER STROKE THICKNESS OF THE UPPERCASE 'I' SHALL BE 15 PERCENT MAXIMUM THE HEIGHT OF CHARACTER. F. CHARACTER THAT ARE RECTANGULAR IN CROSS SECTION SHALL BE A 1/8" MINIMUM AND 4 TIMES THE RAISED CHARACTER STROKE WIDTH MAXIMUM. G. RAISED CHARACTERS SHALL HAVE EASED EDGES.
8
BRAILLE SHALL BE PER CBC 11B-703.3 INCLUDING, BUT NOT LIMITED TO THE FOLLOWING: DISTANCES IN INCHES, MIN TO MAX. A. DISTANCE BETWEEN CORRESPONDING DOTS FROM ONE CELL DIRECTLY BELOW: 0.395 TO 0.400 B. DISTANCE BETWEEN TWO DOTS IN THE SAME CELL : 0.100, MEASURED CENTER TO CENTER C. DISTANCE BETWEEN CORRESPONDING DOTS IN ADJACENT CELLS: 0.300 D. SINGLE BRAILLE CELL E. BLANK CELL SPACE BETWEEN WORDS F. BASE DIAMETER: 0.059 TO 0.063 G. NO RAISED DOT, BLANK CELL SPACE BETWEEN WORDS
6" = 1'-0"
TO EXIT TO EXIT
0570_1014_ACC TACTILE SIGN REQUIREMENTS_01 ?YYMMDD?.Q1
TYPE 2 LOCATE AT EACH ACCESS DOOR FROM AN INTERIOR ROOM OR AREA TO A CORRIDOR OR HALLWAY, AND EACH DOOR THAT LEADS TO A GRADE LEVEL EXIT BY MEANS OF EXIT ENCLOSURE OR EXIT PASSAGEWAY.
FINISH FLOOR
15 G-513
TYP
C
8 G-513
TYP
0570_1014_EXIT SIGNAGE_01 170614. Q2
CHARACTERS AND BRAILLE PER
9" MIN.
RESTROOM .. . .. .. .. .. . .. .. ..
EXIT SIGNS 1/2" = 1'-0"
B
9" MIN.
CHARACTERS AND BRAILLE PER
16
A
SECOND SIGN REQUIRED THE SECOND SIGN REQUIRED IS A PERMANENT ROOM IDENTIFICATION SIGN. COORDINATE AND CONFIRM USE & TYPE OF PICTOGRAMS W/OWNER. ISA'S & DIRECTIONAL SIGNS PER SIGN PLANS.
TYPE 3 LOCATE AT EXIT DOOR OF A HORIZONTAL EXIT
LOCATION PER
BRAILLE TO BE CONTRACTED GRADE 2, AND DOT HEIGHT TO BE 0.025 TO 0.037. DOTS MUST BE DOMED OR ROUNDED. DOTS INDICATING UPPERCASE LETTER OR LETTERS MUST ONLY BE USED AT THE FIRST WORD OF SENTENCES, PROPER NOUNS AND NAMES, INDIVIDUAL LETTERS OF THE ALPHABET, INITIALS, AND/OR ACRONYMS.
ACCESSIBLE TACTILE SIGN REQUIREMENTS
12"
48" AFF MIN BOT OF LOWEST LINE OF BRAILLE
TYPE 1 LOCATE AT GRADE LEVEL EXIT DOORS.
60" MAX.
LOCATION VARIES BY TYPE
G
CONTRACTED GRADE 2 BRAILLE AT WALL SIGN
EXIT
58" MIN.
SIGNAGE SIZE AND CHARACTER
SIGN FIELD TO BE CONTRASTING COLORS, EITHER LIGHT ON DARK OR DARK ON LIGHT. COORDINATE WITH ARCHITECT FOR SPECIFIC COLORS.
EXIT
BOT OF HIGHEST LINE OF RAISED CHARACTER S 48" AFF MIN
1/8" BACKPLATE AT WALL SIGN
12
E F
G C
TO MEET THE 2016 CALIFORNIA TITLE 24 CODE AND AMERICANS WITH DISABILITIES ACT, A COMBINATION OF THE TWO FOLLOWING SIGNS ARE REQ'D FOR RESTROOM IDENTIFICATION: FIRST SIGN REQUIRED THE 1/4" THICK 12" CIRCLE DESIGNATES THE WOMEN'S RESTROOM, THE 1/4" THICK 12" EQUILATERAL TRIANGLE DESIGNATES THE MEN'S RESTROOM. A UNISEX RESTROOM IS DESIGNATED BY A 12" CIRCLE WITH A SOLID TRIANGLE SUPERIMPOSED ON IT, BOTH 1/4" THICK. CENTERED SIGN 60" ABOVE THE FLOOR. THE EDGES OF THE SIGN MUST BE EASED OR ROUNDED @ 1/6" MIN OR CHAMFERED AT 1/8" MAX. VERTICES OF THE TRIANGLE MUST BE RADIUSED 1/8" MIN TO 1/4" MAX. C L OF DOOR
1/32" RAISED TEXT AT WALL SIGN
9" MIN.
D
6" MIN.
B
SIGNAGE IS TO BE OF CONTRASTING COLOR FROM THE DOOR
12"
C
3/8"-1/2"
F
NOTES: PROVIDE EXIT SIGNAGE PER: CBC 1011, 11B-216, 11B-703
A
3/8"
EXIT ROUTE
B
C
D
A
E
RAISED CHARACTERS SHALL BE UPPERCASE, SANS-SERIF, HORIZONTAL FORMAT, WITH FONTS PER CBC 11B-703.2
B B
RAISED CHARACTERS AND SIGN FIELD TO HAVE NON-GLARE FINISH. SIGNAGE SIZE AND CHARACTER LOCATION VARIES BY TYPE
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
1. 2.
0570_1014_TACTILE SIGNS AT DOORS_01 170614. Q2
234
5/15/2019 3:49:04 PM
DIRECTIONAL AND INFORMATIONAL SIGNS THAT ARE NOT REQUIRED TO HAVE TACTILE/BRAILLE CHARACTERS SHALL COMPLY WITH THE FOLLOWING:
SIGN LOCATION
234
B
F.F.
4.
1/2" = 1'-0"
CL
NO CHARACTERS OR BRAILLE PERMITTED IN PICTOGRAM FIELD TEXT DESCRIPTORS ARE REQD DIRECTLY BELOW THE FIELD SEE 7 FOR ADDL REQMTS
3/8"-1/2"
2.
WHERE A TACTILE SIGN IS PROVIDED AT DOOR, THE SIGN SHALL BE LOCATED ALONGSIDE THE DOOR AT EACH LATCH WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE DOORS WITH ONE ACTIVE LEAF, THE SIGN SHALL BE LOCATED ON THE INACTIVE LEAF WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE DOORS WITH TWO ACTIVE LEAVES, THEN THE SIGN SHALL BE LOCATED TO THE RIGHT OF THE RIGHT HAND DOOR WHERE THERE IS NO WALL SPACE AT THE LATCH SIDE OF A SINGLE DOOR OR AT THE RIGHT SIDE OF A DOUBLE DOOR, SIGNS SHALL BE LOCATED ON THE NEAREST ADJACENT WALL WHERE PERMANENT IDENTIFICATION SIGNAGE IS PROVIDED FOR ROOMS AND SPACES THEY SHALL BE LOCATED ON THE APPROACH SIDE OF THE DOOR AS ONE ENTERS THE ROOM OR SPACE SIGNS THAT IDENTIFY EXITS SHALL BE LOCATED ON THE APPROACH SIDE OF THE DOOR AS ONE EXITS THE ROOM OR SPACE TACTILE SIGNS TO BE MOUNTED AT 60" ABOVE THE FLOOR TO THE CENTER OF THE SIGN PROVIDED THAT BASED ON THE SIGN CONTENT THE RAISED CHARACTERS ARE 60" MAXIMUM TO THE BASELINE OF THE HIGHEST RAISED CHARACTER AND 48" MINIMUM TO THE BASELINE OF THE LOWEST RAISED CHARACTER OR BRAILLE
6"
1.
40" MIN
C
T
9
13"
C23603
R
DEVICE CALCULATIONS PROVIDED ON SIGNAGE PLAN, ALS REQUIRED AT ALL ASSEMBLY AND CONFERENCE AREAS
D A RCH SE I E N A N McM TE H U T A
LI J ON C
ASSISTIVE LISTENING SYSTEM AVAILABLE _______
6" MIN
PER CHART BELOW
18" MIN
SEAL
A
18" X 18" MIN CLEAR FLOOR SPACE TO BE PROVIDED CENTERED ON SIGNAGE
CC: "IN______________"
ST
18" MIN
DIRECTIONAL AND INFORMATIONAL SIGN
TO BE EDITED TO:
SIGN NOT REQUIRED TO BE PROVIDED AT A DOOR, BUT MUST BE POSTED AT A PROMINENT LOCATION NEAR THE ASSEMBLY AREA / CONFERENCE ROOM ENTRANCE. SEE SIGNAGE PLAN FOR LOCATIONS
CT Y R RT
CL
1.
SIGN SIZE BASED ON TEXT SIZE REQUIREMENTS
8"
NO WALL MOUNTED PROTRUDING OBJECTS MORE THAN 3" BEYOND FACE OF WALL AT SIGN LOCATION
8 G-513
PICTOGRAM REQUIREMENTS PER
TYP.
SHEET
RESTROOM SIGNAGE 3/16" = 1'-0"
ACCESSIBILTY SIGNAGE STANDARDS AND DETAILS
18 G-513
EDGE OF DOOR
20
TITLE
0570_1014_RESTROOM SIGNAGE_01 150901. Q2
G-513
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
INC:
REVIEWED FOR
0 1/4" 1/2"
SS
DATE:
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
FLS
✔
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
S HA R RAH DUN L A P S AW Y E R I N C O RPO RAT E D Civil Engineering • Land Planning • Surveying & Mapping Landscape Architecture • Presentation Graphics 6590 Lockheed Drive, Redding, CA 96002 530.221.1792 voice • 530.221.8369 fax info@sdsengineering.com
SEAL
PROJECT C
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED MARK
DATE 05/17/2019
DESCRIPTION DSA APPROVAL
PY CANO
N ADMI CE OFFI 102
Y ENTR R TOWE
R R
US CAMP TY SAFE 126
BBY M/LO SROOFLOW CLASOVER101
LOBB
COUN132
SELO COUN130
ENT STUD ICES SERV108
K WOR ER CENT
ROOM REST 118
R
WAY
SELO R COUN131
HALL
R
ENT STUD ICES SERV106
100
SELO COUN128
R
N ADMI E ENT OFFIC 104 STUD ICES SERV103
WAY HALL
Y
R SELO
ODIAL CUST119
SELO COUN129 WAY HALL
SELO COUN127
AGE STOR120
IDF
SELO COUN125
LTY FACU E OFFIC
121
VET E OFFIC
LTY FACU CE OFFI
116
LTY FACU E OFFIC
LTY FACU E OFFIC
LTY FACU E OFFIC
ENT STUD ICES SERV 107
LTY FACU E OFFIC
LTY FACU E OFFIC
LTY FACU E OFFIC 105
LTY FACU E OFFIC
LTY FACU CE OFFI 109
110
111
112
113
114
115
LTY FACU WAY HALL150
117
122
FIRE RISER
VET ER CENT 123
151
CE EREN CONF 124
PY CANO
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman.rvt
AGENCY
A
TITLE
COVER SHEET
2/20/2018 3:56:52 PM
SHEET
C001
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
INC:
REVIEWED FOR
0 1/4" 1/2"
SS
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
DATE:
D
FLS
✔
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
S HA R RAH DUN L A P S AW Y E R I N C O RPO RAT E D Civil Engineering • Land Planning • Surveying & Mapping Landscape Architecture • Presentation Graphics 6590 Lockheed Drive, Redding, CA 96002 530.221.1792 voice • 530.221.8369 fax info@sdsengineering.com
SEAL
PROJECT C
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED MARK
DATE 05/17/2019
DESCRIPTION DSA APPROVAL
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 ?00.00.00? LIONAKIS 2017
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman.rvt
AGENCY
A
TITLE
GENERAL NOTES
2/20/2018 3:56:52 PM
SHEET
C002
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
INC:
REVIEWED FOR
0 1/4" 1/2"
SS
DATE:
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
FLS
✔
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
S HA R RAH DUN L A P S AW Y E R I N C O RPO RAT E D Civil Engineering • Land Planning • Surveying & Mapping Landscape Architecture • Presentation Graphics 6590 Lockheed Drive, Redding, CA 96002 530.221.1792 voice • 530.221.8369 fax info@sdsengineering.com
SEAL
PROJECT C
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED MARK
DATE 05/17/2019
DESCRIPTION DSA APPROVAL
ENTRY TOWER
B
CANOPY
CAMPUS SAFETY
COUNSELOR
126
COUNSELOR COUNSELOR
128
130
MANAGEMENT
ADMIN OFFICE
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
102
132
017294 ?00.00.00? LIONAKIS 2017
CLASSROOM/LOBBY OVERFLOW HALLWAY
101
LOBBY
AGENCY
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman.rvt
100
COUNSELOR
COUNSELOR
125
STUDENT ADMIN SERVICES OFFICE
COUNSELOR COUNSELOR
127
129
FIRE RISER
103
WORK CENTER
HALLWAY
151
104
131
HALLWAY
IDF 121
CUSTODIAL
STORAGE
124
CANOPY A
VET CENTER
VET OFFICE
123
122
STUDENT SERVICES
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
118
108
107
106
105
119
120
CONFERENCE
RESTROOM
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
114
113
112
111
110
109
FACULTY HALLWAY 150
TITLE
GRADING, DRAINAGE AND PAVING PLAN
2/20/2018 3:56:52 PM
SHEET
C011
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
INC:
REVIEWED FOR
0 1/4" 1/2"
SS
DATE:
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
FLS
✔
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
S HA R RAH DUN L A P S AW Y E R I N C O RPO RAT E D Civil Engineering • Land Planning • Surveying & Mapping Landscape Architecture • Presentation Graphics 6590 Lockheed Drive, Redding, CA 96002 530.221.1792 voice • 530.221.8369 fax info@sdsengineering.com
SEAL
PROJECT C
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED MARK
DATE 05/17/2019
DESCRIPTION DSA APPROVAL
B
ENTRY TOWER MANAGEMENT
CANOPY
CAMPUS SAFETY
COUNSELOR
126
ADMIN OFFICE
COUNSELOR COUNSELOR
128
130
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
102
132
AGENCY
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman.rvt
CLASSROOM/LOBBY OVERFLOW
HALLWAY
101
LOBBY 100
COUNSELOR
COUNSELOR
125
STUDENT ADMIN SERVICES OFFICE
COUNSELOR COUNSELOR
127
129
FIRE RISER
103
WORK CENTER
HALLWAY
151
104
131
HALLWAY
IDF 121
CUSTODIAL
STORAGE
124
VET CENTER
VET OFFICE
123
122
STUDENT SERVICES
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
118
108
107
106
105
119
120
CONFERENCE
RESTROOM
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
114
113
112
111
110
109
A
CANOPY
FACULTY HALLWAY 150
TITLE
UTILITY PLAN
2/20/2018 3:56:52 PM
SHEET
C012
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
INC:
REVIEWED FOR
0 1/4" 1/2"
SS
DATE:
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
FLS
✔
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
S HA R RAH DUN L A P S AW Y E R I N C O RPO RAT E D Civil Engineering • Land Planning • Surveying & Mapping Landscape Architecture • Presentation Graphics 6590 Lockheed Drive, Redding, CA 96002 530.221.1792 voice • 530.221.8369 fax info@sdsengineering.com
SEAL
PROJECT C
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED MARK
DATE 05/17/2019
DESCRIPTION DSA APPROVAL
ENTRY TOWER
B
CANOPY
CAMPUS SAFETY
COUNSELOR
126
COUNSELOR COUNSELOR
128
130
MANAGEMENT
ADMIN OFFICE
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
102
132
017294 ?00.00.00? LIONAKIS 2017
CLASSROOM/LOBBY OVERFLOW HALLWAY
101
LOBBY
AGENCY
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman.rvt
100
COUNSELOR
COUNSELOR
125
STUDENT ADMIN SERVICES OFFICE
COUNSELOR COUNSELOR
127
129
FIRE RISER
103
WORK CENTER
HALLWAY
151
104
131
HALLWAY
IDF 121
CUSTODIAL
STORAGE
124
CANOPY A
VET CENTER
VET OFFICE
123
122
STUDENT SERVICES
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
118
108
107
106
105
119
120
CONFERENCE
RESTROOM
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
114
113
112
111
110
109
FACULTY HALLWAY 150
TITLE
INTERIM EROSION CONTROL PLAN
2/20/2018 3:56:52 PM
SHEET
C013
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
INC:
REVIEWED FOR
0 1/4" 1/2"
SS
DATE:
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
FLS
✔
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
S HA R RAH DUN L A P S AW Y E R
ENTRY TOWER CANOPY
CAMPUS SAFETY
COUNSELOR
126
ADMIN OFFICE
COUNSELOR COUNSELOR
128
130
102
132
CLASSROOM/LOBBY OVERFLOW HALLWAY
101
LOBBY 100
COUNSELOR
COUNSELOR
COUNSELOR COUNSELOR
127
125
STUDENT ADMIN SERVICES OFFICE
129
FIRE RISER
103
I N C O RPO RAT E D
104
131
WORK CENTER
HALLWAY
151
HALLWAY
IDF 121
CUSTODIAL
STORAGE
CONFERENCE 124
VET OFFICE
123
122
STUDENT SERVICES
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
118
108
107
106
105
119
120
VET CENTER
RESTROOM
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
114
113
112
111
110
109
Civil Engineering • Land Planning • Surveying & Mapping Landscape Architecture • Presentation Graphics
FACULTY HALLWAY
CANOPY
150
6590 Lockheed Drive, Redding, CA 96002 530.221.1792 voice • 530.221.8369 fax info@sdsengineering.com
SEAL
PROJECT C
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED MARK
1
2
3
4
5
6
DATE 05/17/2019
DESCRIPTION DSA APPROVAL
7
B
F E
ENTRY TOWER
MANAGEMENT
CANOPY D
CAMPUS SAFETY
COUNSELOR
126
ADMIN OFFICE
COUNSELOR COUNSELOR
128
130
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
102
132
AGENCY
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman.rvt
CLASSROOM/LOBBY OVERFLOW
HALLWAY
101
LOBBY
C.4
100
COUNSELOR
COUNSELOR
125
STUDENT ADMIN SERVICES OFFICE
COUNSELOR COUNSELOR
127
129
FIRE RISER
103
C
WORK CENTER
HALLWAY
151
104
131
HALLWAY
IDF
B.6
121
CUSTODIAL
STORAGE
124
VET CENTER
VET OFFICE
123
122
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
118
108
107
106
105
119
120
CONFERENCE
RESTROOM
STUDENT SERVICES
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
114
113
112
111
110
109
B A
CANOPY
TITLE
FACULTY HALLWAY 150
A
HORIZONTAL CONTROL PLAN
2/20/2018 3:56:52 PM
SHEET
C060
017294 ?00.00.00? LIONAKIS 2017
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
INC:
REVIEWED FOR SS
✔
DATE:
FLS
✔
07/03/2019
ACS
✔
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
INC:
REVIEWED FOR SS
✔
DATE:
FLS
✔
07/03/2019
ACS
✔
S-_014213_N001A
STRUCTURAL SYMBOLS LEGEND
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
1"
SEE UNITED STATES NATIONAL CAD STANDARD FOR ANY ABBREVIATIONS NOT LISTED BELOW. SEE BUILDING CODE FOR REFERENCED DESIGN AND MATERIALS SYMBOLS, ACRONYMS & NOTATIONS.
D
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
B3 S-501
DETAIL INDICATOR - SECTION & DETAIL INDICATOR - SECTION ITEM
B3 S-501
2. B3 S-301
SECTION INDICATOR PARTIAL BUILDING/WALL DETAIL INDICATOR - AREA
D2 S-512
REFERENCES TO CONSTRUCTION DOCUMENTS ARE TO THE ENFORCEMENT AGENCY APPROVED DRAWINGS AND SPECIFICATIONS FOR THIS PROJECT. SUPPLEMENTAL DOCUMENTS INCLUDING, BUT NOT LIMITED TO, ADDENDA, REVISED DRAWINGS, FIELD INSTRUCTIONS AND MODIFICATIONS PRODUCED FOR THIS PROJECT, SHALL ALSO BE CONSIDERED A CONSTRUCTION DOCUMENT. ALL REQUIREMENTS OF THE INITIALLY APPROVED CONSTRUCTION DOCUMENTS SHALL APPLY TO ANY SUPPLEMENTAL DOCUMENTS.
S-_014100_N003A 170125. Q2
BUILDING CODE: 2016 CBC ENFORCEMENT AGENCY: DIVISION OF THE STATE ARCHITECT (DSA) A. VERTICAL DESIGN CRITERIA (UNLESS OTHERWISE SHOWN OR NOTED) ROOF LIVE LOADS: TYP ROOF AREA 20 PSF (REDUCIBLE) MECHANICAL & ELECTRICAL AREA 50 PSF (NON-REDUCIBLE) FLOOR LIVE LOADS: OFFICE/CLASSROOMS (W/ 15 PSF PARTITION LL) FIRST FLOOR CORRIDORS
50 PSF (REDUCIBLE) 100 PSF (REDUCIBLE)
GROUND SNOW LOAD:
0 PSF
B. LATERAL DESIGN CRITERIA A2 S-303
3.
A2 S-303
SECTION INDICATOR - BUILDING
A4 S-201
ELEVATION INDICATOR - EXTERIOR
4.
CAREFULLY EXAMINE THE CONSTRUCTION DOCUMENTS AND NOTIFY THE STRUCTURAL ENGINEER OF ANY CONFLICTS OR DISCREPANCIES WITHIN THE STRUCTURAL CONSTRUCTION DOCUMENTS AND BETWEEN ALL OTHER CONSTRUCTION DOCUMENTS. DEVIATIONS SHALL NOT BE MADE TO THE REQUIREMENTS INDICATED IN THE STRUCTURAL CONSTRUCTION DOCUMENTS.
5.
PORTIONS OF THESE CONSTRUCTION DOCUMENTS ARE DIAGRAMMATIC ONLY. ITEMS INCLUDING, BUT NOT LIMITED TO, LOCATIONS, SIZES, QUANTITIES, ACCESSORIES AND CONNECTIONS ARE INDICATED IN A REPRESENTATIONAL MANNER AND MAY NOT BE COMPLETELY SHOWN. PROVIDE ALL WORK AND MATERIALS NECESSARY TO COMPLETE THE PROJECT AS REPRESENTED IN THE CONSTRUCTION DOCUMENTS.
A1
S-202
A2
A4
S-202
ELEVATION INDICATOR - INTERIOR, SINGLE & MULTIPLE VIEW
A2
A3
MATCH LINE SEE XX / X-XXX
6.
MATCH LINE INDICATOR
7.
1 A
REFERENCE GRID WITH REFERENCE GRID LINES
8.
9.
REVISION INDICATOR & REVISION CLOUD 22
LEVEL 1 100'-0"
TOC 98'-8"
ELEVATION INDICATOR - LEVEL & SPOT
WHERE THE CONSTRUCTION DOCUMENTS INDICATE TO NOTIFY THE STRUCTURAL ENGINEER, SUCH NOTIFICATION SHALL BE SUBMITTED IN WRITING WITH SUFFICIENT ALLOWANCE FOR A REASONABLE TIME PERIOD FOR REVIEW, DESIGN, ENFORCEMENT AGENCY APPROVAL AS REQUIRED AND WRITTEN RESPONSE SO AS NOT TO AFFECT THE CONSTRUCTION SCHEDULE. OBTAIN WRITTEN RESPONSE BEFORE PROCEEDING WITH THE AFFECTED WORK.
DIMENSIONS AND ELEVATIONS INDICATED ARE FOR STRUCTURAL ELEMENTS ONLY. COORDINATE WITH ALL OTHER CONSTRUCTION DOCUMENTS FOR DIMENSIONS AND ELEVATIONS NOT INDICATED ON THE STRUCTURAL CONSTRUCTION DOCUMENTS. DO NOT SCALE DRAWINGS. CONSTRUCTION SHALL COMPLY WITH ALL BUILDING, HEALTH AND SAFETY STANDARDS, CODES AND REGULATIONS APPLICABLE TO THIS PROJECT. NOTHING IN THE CONSTRUCTION DOCUMENTS SHALL BE CONSTRUED TO PERMIT WORK NOT CONFORMING TO THE STANDARDS, CODES AND REGULATIONS. REFERENCES TO STANDARDS, CODES AND REGULATIONS INCLUDING, BUT NOT LIMITED TO, ICC, IBC, CBC, ACI, ASTM, ASCE, ANSI, AWS, AISI, AITC AND AISC SHALL BE TO THE LATEST EDITION AS ADOPTED BY THE ENFORCEMENT AGENCY. FEATURES OF CONSTRUCTION INDICATED ARE TYPICAL. WHERE FEATURES ARE NOT FULLY OR SPECIFICALLY INDICATED BY THE CONSTRUCTION DOCUMENTS, THEIR CONSTRUCTION SHALL BE AS INDICATED FOR IDENTICAL OR SIMILAR FEATURES ELSEWHERE IN THE CONSTRUCTION DOCUMENTS. IF ANY CONDITIONS REQUIRE CONSTRUCTION DIFFERENT THAN THAT INDICATED ON THE CONSTRUCTION DOCUMENTS, NOTIFY THE STRUCTURAL ENGINEER.
10. STRUCTURAL ELEMENTS SHALL NOT BE REMOVED OR MODIFIED UNLESS INDICATED IN THE STRUCTURAL CONSTRUCTION DOCUMENTS. IF STRUCTURAL ELEMENTS INTERFERE WITH THE WORK INDICATED IN ANY OTHER CONSTRUCTION DOCUMENTS, NOTIFY THE STRUCTURAL ENGINEER. 11. THE CONSTRUCTION DOCUMENTS AND THE DESIGNS INCORPORATED THEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, ARE NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT.
KEYNOTE INDICATOR
22
PLAN NORTH
PLAN NORTH & TRUE NORTH INDICATOR
MATERIAL SYMBOL LEGEND EARTH
EARTH, COMPACT FILL
EARTH, ROCK
GRAVEL, ROCK FILL
SAND, MORTAR, GROUT
CONCRETE, CAST IN PLACE
S-_011000_N006A 170125. Q2
12. STRUCTURAL ELEMENTS REPRESENTED IN THE CONSTRUCTION DOCUMENTS ARE INDICATED IN THEIR COMPLETED CONFIGURATION. THE CONSTRUCTION DOCUMENTS DO NOT INDICATE MEANS, METHODS OR SEQUENCES OF CONSTRUCTION UNLESS SPECIFICALLY NOTED OTHERWISE. PROVIDE ALL MEASURES NECESSARY AS REQUIRED FOR THE PROTECTION OF LIFE AND PROPERTY AND TO ASSURE THE CORRECT AND ACCURATE STRUCTURE GEOMETRY AND STABILITY DURING CONSTRUCTION. MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, PROVIDING ADEQUATE FORMING, SHORING AND BRACING. MEASURES SHALL REMAIN IN PLACE UNTIL THE STRUCTURAL ELEMENTS AND ALL OTHER STRUCTURAL ELEMENTS USED TO SUPPORT THEM HAVE BEEN COMPLETED AND HAVE ATTAINED THEIR REQUIRED DESIGN STRENGTHS. 13. PROTECT ALL ELEMENTS, WHETHER CONCEALED OR NOT, INCLUDING, BUT NOT LIMITED TO, PROPERTIES, STRUCTURES, FINISHES, STREETS, LANDSCAPING AND UTILITIES ADJACENT TO OR ON THIS SITE DURING THE CONSTRUCTION OF THIS PROJECT. SHOULD DAMAGE OCCUR TO ANY ELEMENTS, THEY SHALL BE RESTORED TO THEIR ORIGINAL CONDITION AT NO ADDITIONAL COST TO THE OWNER. CONTROL ITEMS SUCH AS, BUT NOT LIMITED TO, DUST, DIRT, WATER, FUMES, SMOKE, TRASH, NOISE AND VIBRATION CREATED AS A RESULT OF ANY OPERATIONS DURING CONSTRUCTION IN CONFORMANCE WITH APPLICABLE STANDARDS, CODES AND REGULATIONS. 14. STRUCTURAL DESIGN LOADS, STRENGTHS, CAPACITIES AND CRITERIA INDICATED ON THE CONSTRUCTION DOCUMENTS ARE FOR THE COMPLETED STRUCTURE ONLY. THE USE OF ANY PART OR PARTS OF THE INCOMPLETE OR COMPLETED STRUCTURE FOR THE SUPPORT OF CONSTRUCTION ITEMS INCLUDING, BUT NOT LIMITED TO, OTHER PORTIONS OF THE STRUCTURE, PERSONNEL, MATERIALS AND EQUIPMENT IS LIMITED TO THE SAFE CAPACITY OF THE STRUCTURE AT THE TIME IT IS TO BE USED FOR SUCH SUPPORT. PROVIDE ALL MEASURES NECESSARY AS REQUIRED TO PREVENT OVERLOADING, EXCESSIVE MOVEMENT AND DAMAGE TO ANY PART OR PARTS OF THE STRUCTURE. 15. IF SUBSTITUTIONS ARE REQUESTED FOR STRUCTURAL ELEMENTS INDICATED IN THE CONSTRUCTION DOCUMENTS, NOTIFY THE STRUCTURAL ENGINEER. SUBMIT DATA AND DOCUMENTATION INCLUDING, BUT NOT LIMITED TO, COMPARATIVE QUALITY, SUITABILITY, PERFORMANCE, STRUCTURAL CAPACITY, ICC APPROVAL AND ENFORCEMENT AGENCY ACCEPTABILITY SUBSTANTIATING THE COMPLETE COMPLIANCE OF EACH PROPOSED SUBSTITUTION WITH THE CONSTRUCTION DOCUMENTS. ONLY ONE REQUEST FOR SUBSTITUTION WILL BE ALLOWED FOR EACH STRUCTURAL ELEMENT. SUBSTITUTIONS WILL NOT BE CONSIDERED WHEN SUBMITTALS ARE INCOMPLETE OR ACCEPTANCE WOULD REQUIRE REVISIONS TO THE CONSTRUCTION DOCUMENTS. PROVIDE OWNER REIMBURSEMENT FOR SERVICES REQUIRED TO OBTAIN ENFORCEMENT AGENCY APPROVAL OF SUBSTITUTIONS. IF A PROPOSED SUBSTITUTION SUBMITTAL IS NOT COMPLETE, NOT ACCEPTABLE TO THE STRUCTURAL ENGINEER, OR NOT APPROVED BY THE ENFORCEMENT AGENCY PROVIDE THE SPECIFIED ITEM AS INDICATED IN THE CONSTRUCTION DOCUMENTS. THE STRUCTURAL ENGINEER WILL BE THE SOLE JUDGE OF THE ACCEPTABILITY OF THE PROPOSED SUBSTITUTION VERSUS THE SPECIFIED ITEM. ACCEPTANCE OF A SUBSTITUTION SHALL NOT BE CONSTRUED TO PERMIT WORK NOT CONFORMING TO THE REQUIREMENTS OF THE CONSTRUCTION DOCUMENTS.
SEISMIC SITE CRITERIA: SS=0.65, S1 =0.30, SDS=0.55, SD1 =0.36, SITE CLASS: D BUILDING CRITERIA: SEISMIC: • RISK CATEGORY= II • IMPORTANCE FACTOR, I=1.00 • SEISMIC DESIGN CATEGORY = D • SEISMIC FORCE RESISTING SYSTEM: LIGHT FRAMED WOOD WALLS W/ SHEAR PANELS • RESPONSE MODIFICATION FACTOR, R = 6.5 • DESIGN BASE SHEAR: V = 28K • SEISMIC RESPONSE COEFFICIENT, Cs=0.08 • ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE • HORIZONTAL IRREGULARITIES: TYPE 2 (REENTRANT CORNER), TYPE 3 (DIAPHRAGM DISCONTINUITY) • VERTICAL IRREGULARITIES: TYPE 3 (GEOMETRIC) BUILDING DISPLACEMENT (AMPLIFIED): LEVEL INTERSTORY DISPLACEMENT GROUND 0.00 IN ROOF 1.50 IN
TOTAL DISPLACEMENT 0.00 IN 1.50 IN
WIND: ULTIMATE DESIGN WIND SPEED, V(ULT) = 110 MPH NOMINAL DESIGN WIND SPEED, V(ASD) = 85 MPH RISK CATEGORY = II WIND EXPOSURE = C GCPI = +/- 0.18 COMPONENTS AND CLADDING WIND PRESSURES TO BE DETERMINED PER ASCE 7-10
PROJECT DIRECTORY OWNER
STRUCTURAL ENGINEER
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT 11555 OLD OREGON TRAIL REDDING, CA 96049-6006 CONTACT: GEORGE ESTRADA PHONE: 530.242.7929 EMAIL: GESTRADA@SHASTACOLLEGE.EDU
LIONAKIS 1919 19TH STREET SACRAMENTO, CA 95811 CONTACT: DANIELLE SMITH PHONE: 916.558.1900 EMAIL: DANIELLE.SMITH@LIONAKIS.COM
SOIL INFO IS BASED ON GEOTECHNICAL REPORT BY: MID PACIFIC ENGINEERING, INC / REPORT NO 04083-01 DATED: DECEMBER 14, 2018 SPREAD FOUNDATIONS: ALLOWABLE BEARING PRESSURE: DL + LL = 2500PSF DL + LL + LATERAL = 3325 PSF COEFFICIENT OF FRICTION = 0.25 ALLOWABLE PASSIVE PRESSURE = 250 PCF IF FRICTIONAL RESISTANCE AND PASSIVE PRESSURE ARE COMBINED, FRICTION IS REDUCED BY 50%
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
REVIEWED FOR SS
✔
DATE:
FLS
ACS
✔
07/03/2019
MECHANICAL ENGINEER PETERS ENGINEERING 2411 ALHAMBRA BLVD, SUITE 100 SACRAMENTO, CA 95817 CONTACT: SEAN TICHENOR PHONE: 916.447.2841 EMAIL: STICHENOR@PETERSENG.COM
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
ARCHITECT
ELECTRICAL ENGINEER
LIONAKIS 1919 19TH STREET SACRAMENTO, CA 95811 CONTACT: JONATHAN MCMURTRY PHONE: 916.558.1900 EMAIL: JONATHAN.MCMURTRY@LIONAKIS.COM
PETERS ENGINEERING 2411 ALHAMBRA BLVD, SUITE 100 SACRAMENTO, CA 95817 CONTACT: GINO ROMANO PHONE: 916.447.2841 EMAIL: GROMANO@PETERSENG.COM
STRUCTURAL SHEET INDEX S-001 S-011 S-013 S-014 S-111 S-132 S-133 S-261 S-262 S-263 S-264 S-311 S-312 S-531 S-532 S-561 S-562 S-563 S-564 S-565 S-566 S-567
SN011000-001
SHEET NAME GENERAL NOTES TYPICAL NOTES TYPICAL NOTES TYPICAL NOTES PLAN - FOUNDATION PLAN - LOW ROOF FRAMING PLAN - HIGH ROOF FRAMING ELEVATIONS - SHEARWALL ELEVATIONS - SHEARWALL ELEVATIONS - SHEARWALL ELEVATIONS - SHEARWALL SECTIONS - BUILDING SECTIONS - BUILDING DETAILS - TYPICAL CONCRETE DETAILS - TYPICAL CONCRETE DETAILS - TYPICAL WOOD FRAMING DETAILS - TYPICAL WOOD FRAMING DETAILS - TYPICAL WOOD SHEAR WALL FRAMING DETAILS - TYPICAL MANUFACTURED LUMBER FRAMING DETAILS - TYPICAL WOOD I-JOIST FRAMING DETAILS - ROOF FRAMING DETAILS DETAILS - ROOF FRAMING DETAILS
SEAL FESSIONA PRO L ED RRY J. VOLKE E
T
T
E
No. S3737
A RU C T UR O F OF I CAL
05/15/2019 PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
ISSUED
MARK
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
16. SCHEDULES, LEGENDS, ABBREVIATIONS, TYPICAL NOTES AND TYPICAL DETAILS ON THE STRUCTURAL CONSTRUCTION DOCUMENTS MAY REFERENCE STRUCTURAL ELEMENTS OR REQUIREMENTS NOT SPECIFICALLY INDICATED OR REQUIRED ELSEWHERE IN THE CONSTRUCTION DOCUMENTS. 17. THE STRUCTURAL CONSTRUCTION DOCUMENTS ARE NOT COMPLETE AND READY FOR CONSTRUCTION UNTIL THEY ARE APPROVED BY THE ENFORCEMENT AGENCY AND SIGNED BY THE STRUCTURAL ENGINEER.
CONCRETE, PRE-CAST OR TILT UP
MASONRY, CLAY BRICK
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
MASONRY, CONCRETE AGENCY
STEEL
ALUMINUM
WOOD BLOCKING OR SHIM
WOOD FRAMING CONTINUOUS
WOOD
A
✔
SHARRAH DUNLAP SAWYER 6590 LOCKHEED DRIVE REDDING, CA 96002 CONTACT: TONY MAGDALENO PHONE: 530.221.1792 EMAIL: TMAGDALENO@SDSENGINEERING.COM
TITLE
GENERAL NOTES
SHEET
5/15/2019 4:35:19 PM
INC:
CIVIL ENGINEER
SHEET NUMBER C. SOIL DESIGN CRITERIA
S-_014100_N001A 170125. Q2
EER GIN EN R
JOIST HANGER JOINT ANGLE, LONG, LENGTH LIVE LOAD LONG LEG HORIZONTAL LONG LEG VERTICAL LONGITUDINAL LAG SCREW LIGHT WEIGHT CONCRETE MAXIMUM MACHINE BOLT MISCELLANEOUS CHANNEL MASONRY CONTROL JOINT MASONRY DOWEL JOINT MECHANICAL MASONRY EXPANSION JOINT MANUFACTURER MINIMUM MISCELLANEOUS MASONRY KEY JOINT MASONRY RAKE JOINT NOT APPLICABLE NEAR FACE NOT IN CONTRACT NOT TO SCALE NORMAL WEIGHT CONCRETE OVER ON CENTER OUTSIDE DIAMETER OPPOSITE HAND OPENING OPPOSITE OUTSIDE RADIUS POWER ACTUATED FASTENER PRECAST CONCRETE POUNDS PER CUBIC FOOT PARTIAL JOINT PENETRATION PLATE, PROPERTY LINE POUNDS PER LINEAR FOOT PREFABRICATE POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH PRESERVATIVE TREATED WOOD QUANTITY RADIUS, RISER REINFORCING STEEL BAR REINFORCE, REINFORCING REQUIRE, REQUIRED ROUND ROUGH OPENING ROUGH SAWN REDWOOD SPACED, SPACING, SPLICE, STEP SEE ARCHITECTURAL DRAWINGS SCHEDULE SELF-DRILLING SELF-TAPPING STRUCTURAL ENGINEER SECTION SEISMIC FORCE RESISTING SYSTEM SHEATHING SIMILAR SHRINKAGE JOINT SNOW LOAD STRUCTURAL PANEL SPECIFICATION SQUARE STAINLESS STEEL STAGGERED STANDARD STIFFENER STIRRUP STEEL STRUCTURAL SYMMETRICAL TREAD, THICKNESS TOP & BOTTOM TONGUE & GROOVE THICKNESS THROUGH TOOL JOINT TOE NAIL TOP OF BEAM TOP OF CURB/CONCRETE TOP OF FRAMING/FOOTING/FLOOR TOP OF JOIST TOP OF MASONRY TOP OF PARAPET TOP OF STEEL TOP OF STRUCTURAL PANEL TOP OF TRUSS TOP OF WALL TUBE STEEL TYPICAL UNDERCUT UNLESS NOTED OTHERWISE UNLESS OTHERWISE NOTED VERTICAL VERIFY IN FIELD VAPOR RETARDER WIDE, WIDTH, WELD, W-SHAPE WITH WITHOUT WIDE FLANGE WELDED HEADED STUD WIND LOAD WHERE OCCURS WORKING POINT WEIGHT, W TEE-SHAPE WELDED THREADED STUD WELDED WIRE REINFORCEMENT EXTRA STRONG DOUBLE EXTRA STRONG
THE STRUCTURAL NOTES AND TYPICAL DETAILS, WHETHER SPECIFICALLY REFERENCED OR NOT, ARE GENERAL AND APPLY TO ALL CONSTRUCTION DOCUMENTS. PROVIDE ALL STRUCTURAL ELEMENTS INDICATED IN THE STRUCTURAL NOTES AND TYPICAL DETAILS AS REQUIRED TO CONFORM TO THE FINISHED PROJECT AS INDICATED IN OTHER CONSTRUCTION DOCUMENTS. PROVIDE ALL STRUCTURAL ELEMENTS INDICATED IN OTHER CONSTRUCTION DOCUMENTS. STRUCTURAL CONSTRUCTION DOCUMENTS SHALL BE USED IN CONJUNCTION WITH ALL OTHER CONSTRUCTION DOCUMENTS. SEE OTHER CONSTRUCTION DOCUMENTS FOR COMPLETE PROJECT REQUIREMENTS.
STRUCTURAL DESIGN CRITERIA
A
JH JT L LL LLH LLV LONG LS LWC MAX MB MC MCJ MDJ MECH MEJ MFR MIN MISC MKJ MRJ NA NF NIC NTS NWC O/ OC OD OPH OPNG OPP OR PAF PCC PCF PJP PL PLF PREFAB PSF PSI PTW QTY R REBAR REINF REQ RND RO RS RWD S SAD SCHED SDST SE SECT SFRS SHTHG SIM SJ SL SP SPEC SQ SST STAG STD STIF STIR STL STRUCT SYMM T T&B T&G THK THRU TJ TN TOB TOC TOF TOJ TOM TOP TOS TOSP TOT TOW TS TYP UC UNO UON VERT VIF VR W W/ W/O WF WHS WL WO WP WT WTS WWR XS XXS
S-_014100_N004A 170125. Q2
S
B
AND AT EXISTING FOOT, FEET INCH, INCHES NUMBER, POUND ARCHITECT / ENGINEER ANCHOR BOLT ABOVE ADDITIONAL ABOVE FINISHED FLOOR ABOVE FINISHED GRADE ABOVE FINISHED SLAB ALTERNATE ALUMINUM APPROXIMATE ARCHITECT ALL THREAD ROD BELOW FINISH FLOOR BACKING BUILDING BLOCKING BELOW BEAM BRICK MASONRY UNIT BOUNDARY NAIL BOTTOM OF STEEL BOTTOM BETWEEN CAMBER, CHANNEL CARRIAGE BOLT CALIFORNIA BUILDING CODE COLD-FORMED STEEL FRAMING CENTER OF GRAVITY CONSTRUCTION JOINT COMPLETE JOINT PENETRATION CENTER LINE CLEAR CONCRETE MASONRY UNIT COLUMN CONCRETE CONNECT, CONNECTION CONTINUE, CONTINUOUS COLD ROLLED STEEL COUNTER SUNK CENTER PENNY (NAIL), DEEP, DEPTH DOUBLE DEMAND CRITICAL WELD DEGREE DEMOLITION DETAIL DIAMETER DIAGONAL DIMENSION DOWEL JOINT DEAD LOAD DITTO, DO OVER DOUGLAS FIR DRAWING DOWEL EACH EACH END EACH FACE EXPANSION JOINT ELEVATION ELECTRIC, ELECTRICAL ELEVATOR EMBEDMENT EDGE NAIL EDGE OF SLAB EQUAL, EQUALLY EACH SIDE EACH WAY EXTERIOR FACE TO FACE FRAMING ANGLE FLAT BAR FOUNDATION FINISH FLANGE FLOOR FIELD NAIL FACE OF CONCRETE/CURB FACE OF FINISH FACE OF MASONRY FACE OF STUD FACE OF WALL FRAMING FIRE RETARDANT TREATED WOOD FAR SIDE FEET, FOOT FOOTING FURRING GAGE GALVANIZED GLUED LAMINATED BEAM GRADE HIGH, HEIGHT HEADER HANGER HOLDDOWN HORIZONTAL HIGH STRENGTH HIGH STRENGTH BOLT HOLLOW STRUCTURAL SECTION HEIGHT INTERNATIONAL CODE COUNCIL INSIDE DIAMETER ISOLATION JOINT INFORMATION INTERIOR INSIDE RADIUS
1.
DETAIL INDICATOR - REFERENCE & DETAIL INDICATOR - ITEM
D2 S-512
STRUCTURAL GENERAL NOTES
5
ST
C
& @ (E) ' " # A/E AB ABV ADDL AFF AFG AFS ALT ALUM APPROX ARCH ATR BFF BKG BLDG BLKG BLW BM BMU BN BOS BOT BTWN C CB CBC CFSF CG CJ CJP CL CLR CMU COL CONC CONN CONT CRS CSK CTR D DBL DCW DEG DEMO DET DIA DIAG DIM DJ DL DO DOUG FIR DWG DWL EA EE EF EJ EL ELEC ELEV EMBED EN EOS EQ ES EW EXT F/F FA FB FDTN FIN FLG FLR FN FOC FOF FOM FOS FOW FRMG FRTW FS FT FTG FURG GA GALV GLB GR H HDR HGR HLDN HORIZ HS HSB HSS HT ICC ID IJ INFO INT IR
D2 S-512
SN011000-004
4
L N IA
STRUCTURAL ABBREVIATIONS LEGEND
3
R
2
REGIST ER K
2"
1
S-001
017294 ?00.00.00? LIONAKIS 2017
0 1/4" 1/2"
1"
1.
S-_014100_N001A 170125. Q2 SUBMITTALS INCLUDE, BUT ARE NOT LIMITED TO, SHOP DRAWINGS, FABRICATION DRAWINGS, PLACEMENT DRAWINGS, CALCULATIONS, DESIGNS, TEST DATA, PRODUCT DATA, SAMPLES, CERTIFICATIONS AND REPORTS AS REQUIRED BY THE CONSTRUCTION DOCUMENTS.
2.
SUBMITTALS, AS A MINIMUM, SHALL CONSIST OF TWO (2) COPIES OF EACH SHEET.
3.
SUBMITTALS SHALL NOT CONTAIN NOR CONSIST OF REPRODUCTIONS OF THE CONSTRUCTION DOCUMENTS. SUBMITTALS CONTAINING REPRODUCTIONS OF ANY PORTION OF THE CONSTRUCTION DOCUMENTS ARE SUBJECT TO REJECTION.
STRUCTURAL OBSERVATION 1.
S-_014500_N001A 170125. Q2
STRUCTURAL OBSERVATION IS THE VISUAL OBSERVATION OF THE STRUCTURAL SYSTEM BY THE STRUCTURAL OBSERVER (THE STRUCTURAL ENGINEER OR OWNER'S DESIGNATED REPRESENTATIVE) FOR GENERAL CONFORMANCE TO THE ENFORCEMENT AGENCY APPROVED CONSTRUCTION DOCUMENTS AT SIGNIFICANT CONSTRUCTION STAGES AND AT COMPLETION OF THE STRUCTURAL SYSTEM.
FOUNDATION AND EARTHWORK 1.
2.
4.
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
5.
6.
D
7.
8.
9.
EACH SUBMITTAL SHALL HAVE A COVER SHEET IDENTIFYING THE CONTENTS BY SPECIFICATION SECTION AND LISTING EACH ITEM AND SHEET NUMBER. EACH SUBMITTAL SHALL HAVE A UNIQUE IDENTIFICATION NUMBER. PRIOR TO SUBMISSION TO THE STRUCTURAL ENGINEER, STAMP SUBMITTALS INDICATING THEY HAVE BEEN REVIEWED AND APPROVED FOR COMPLETENESS AND CONFORMANCE WITH THE INTENT OF THE CONSTRUCTION DOCUMENTS. SUBMITTALS THAT ARE DETERMINED TO BE INCOMPLETE, IN THE JUDGMENT OF THE STRUCTURAL ENGINEER, WILL BE RETURNED WITHOUT REVIEW SO THEY CAN BE COMPLETED. THE STRUCTURAL ENGINEER SHALL NOT BE REQUIRED TO REVIEW PARTIAL SUBMISSIONS OR THOSE FOR WHICH SUBMISSIONS OF CORRELATED ITEMS HAVE NOT BEEN RECEIVED.
2.
3. 4.
PRIOR TO SUBMISSION TO THE STRUCTURAL ENGINEER, THE OWNER'S TESTING LABORATORY SHALL STAMP THE FOLLOWING MARKED SUBMITTALS INDICATING THEY HAVE BEEN REVIEWED AND APPROVED FOR COMPLETENESS AND CONFORMANCE WITH THE INTENT OF THE CONSTRUCTION DOCUMENTS: ■ CONCRETE MIX DESIGNS AND SUBSTANTIATING TEST DATA □ MASONRY GROUT MIX DESIGNS AND SUBSTANTIATING TEST DATA ■ WELDING PROCEDURE SPECIFICATIONS SUBMITTALS SHALL BE REVIEWED BY THE STRUCTURAL ENGINEER PRIOR TO UTILIZATION, INSTALLATION, FABRICATION OR CONSTRUCTION OF ITEMS CONTAINED WITHIN THE SUBMITTALS. SUBMITTALS SHALL BE DELIVERED TO THE STRUCTURAL ENGINEER TO ALLOW SUFFICIENT TIME, IN THE STRUCTURAL ENGINEER'S JUDGMENT, FOR A REASONABLE PERIOD FOR ADEQUATE REVIEW, ENFORCEMENT AGENCY APPROVAL AS REQUIRED AND RESPONSE SO AS NOT TO AFFECT THE CONSTRUCTION SCHEDULE. ALLOW THE STRUCTURAL ENGINEER THE GREATER SUBMITTAL REVIEW PERIOD OF: TEN (10) WORK DAYS; OR FIVE (5) WORK DAYS FOR EACH 100 SHEETS, OR PORTION THEREOF, FOR EACH SUBMITTAL. SUBMITTAL REVIEW PERIOD COMMENCES THE NEXT WORK DAY AFTER SUBMITTAL RECEIPT BY THE STRUCTURAL ENGINEER. CONCURRENT SUBMITTALS OF MULTIPLE PORTIONS OF THE SAME SUBMITTAL ITEM WILL BE REVIEWED IN THEIR ENTIRETY AS ONE SUBMITTAL SUBJECT TO THE REVIEW PERIOD LIMITATION ABOVE. SCHEDULE SUBMITTAL REVIEWS AND CONSTRUCTION ACCORDINGLY. REVIEW OF SUBMITTALS BY THE STRUCTURAL ENGINEER WILL INCLUDE CHECKING FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE CONSTRUCTION DOCUMENTS. IT WILL NOT INCLUDE REVIEW OF THE ACCURACY OR COMPLETENESS OF ITEMS SUCH AS QUANTITIES, DIMENSIONS, WEIGHTS OR GAUGES, FABRICATION PROCESSES, CONSTRUCTION MEANS OR METHODS, COORDINATION WITH THE WORK OF OTHER TRADES, OR CONSTRUCTION SAFETY PRECAUTIONS. REVIEW OF A SPECIFIC ITEM SHALL NOT INDICATE THAT THE STRUCTURAL ENGINEER HAS REVIEWED THE ENTIRE ASSEMBLY OF WHICH THE ITEM IS A COMPONENT. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS NOT BROUGHT TO THE STRUCTURAL ENGINEER'S ATTENTION IN WRITING.
STRUCTURAL OBSERVATION DOES NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR THE INSPECTIONS REQUIRED BY THE ENFORCEMENT AGENCY OR BY OTHER SECTIONS OF THE BUILDING CODE. REQUIRED INSPECTIONS DO NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR STRUCTURAL OBSERVATION. STRUCTURAL OBSERVATION DOES NOT INCLUDE THE SUPERVISION OF CONSTRUCTION FOR PROPER EXECUTION OF THE WORK SHOWN IN THE CONSTRUCTION DOCUMENTS. THE FOLLOWING COMPLETED CONSTRUCTION STAGES MARKED ARE SUBJECT TO STRUCTURAL OBSERVATION IF DEEMED NECESSARY DURING CONSTRUCTION BY THE STRUCTURAL OBSERVER: ■ FOUNDATION EXCAVATIONS AND REINFORCEMENT PRIOR TO CONCRETE PLACEMENT ■ FORMWORK CONSTRUCTION AND REINFORCEMENT PRIOR TO CONCRETE PLACEMENT □ CONCRETE TILT-UP PANEL INSTALLATION □ CONCRETE PRE-CAST ELEMENT PANEL INSTALLATION □ MASONRY INSTALLATION AND REINFORCEMENT PRIOR TO GROUT PLACEMENT □ STEEL FRAMING ERECTION □ STEEL DECK INSTALLATION AND REINFORCEMENT PRIOR TO CONCRETE FILL PLACEMENT □ STEEL DECK INSTALLATION ON FRAMING ■ WOOD FRAMING ERECTION ■ WOOD STRUCTURAL PANEL INSTALLATION ON FRAMING ■ WOOD HARDWARE AND CONNECTOR INSTALLATION ON STRUCTURAL FRAMING □ COLD-FORMED STEEL FRAMING ERECTION □ PRE-FABRICATED STRUCTURAL ELEMENT INSTALLATION ■ PRIOR TO THE CLOSING OF ANY PHASE ■ STRUCTURAL SYSTEM COMPLETION
5.
NOTIFY THE STRUCTURAL OBSERVER 48 HOURS MINIMUM IN ADVANCE OF THE COMPLETION OF THE ABOVE CONSTRUCTION STAGES TO FACILITATE STRUCTURAL OBSERVATIONS BY THE STRUCTURAL OBSERVER. COORDINATE WITH THE STRUCTURAL OBSERVER SO THAT THE WORK FOR THE CONSTRUCTION STAGES NOTED ABOVE IS ACCESSIBLE AND EXPOSED FOR STRUCTURAL OBSERVATION PURPOSES. REMOVE AND/OR REPLACE MATERIALS AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER TO ALLOW STRUCTURAL OBSERVATION.
6.
DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS NOTED DURING STRUCTURAL OBSERVATIONS SHALL BE CORRECTED AT NO ADDITIONAL COST TO THE OWNER.
7.
PROVIDE OWNER REIMBURSEMENT FOR DESIGN PROFESSIONAL COSTS INCURRED TO CORRECT DEVIATIONS AND TO MAKE REVISIONS TO THE CONSTRUCTION DOCUMENTS, INCLUDING OBTAINMENT OF ENFORCEMENT AGENCY APPROVAL AS REQUIRED.
8.
CORRECTIVE WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE ENFORCEMENT AGENCY APPROVED CONSTRUCTION DOCUMENTS AND THE BUILDING CODE.
9.
AT THE COMPLETION OF THE WORK INCLUDED IN THE CONSTRUCTION DOCUMENTS, THE STRUCTURAL OBSERVER SHALL SUBMIT TO THE ENFORCEMENT AGENCY A WRITTEN STATEMENT THAT THE STRUCTURAL OBSERVATIONS HAVE BEEN MADE AND IDENTIFY ANY REPORTED DEFICIENCIES THAT, TO THE BEST OF THE STRUCTURAL OBSERVER'S KNOWLEDGE, HAVE NOT BEEN RESOLVED.
3.
4.
5.
6.
7.
8.
10. SUBMITTALS PROCESSED BY THE STRUCTURAL ENGINEER ARE NOT CHANGE ORDERS.
1.
2.
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
SPECIAL INSPECTION IS DEFINED AS THE INSPECTION OF THE MATERIALS, INSTALLATION, FABRICATION, ERECTION OR PLACEMENT OF COMPONENTS AND CONNECTIONS REQUIRING SPECIAL EXPERTISE TO ENSURE COMPLIANCE WITH APPROVED CONSTRUCTION DOCUMENTS AND REFERENCED STANDARDS. THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL INSPECTORS TO PERFORM INSPECTIONS DURING CONSTRUCTION ON THE TYPES OF WORK MARKED IN THE LIST BELOW IN CONFORMANCE WITH THE ENFORCEMENT AGENCY REGULATORY REQUIREMENTS. THESE INSPECTIONS ARE IN ADDITION TO THE INSPECTIONS REQUIRED BY THE ENFORCEMENT AGENCY. A. TESTING ■ COMPACTED FILL ■ CONCRETE □ MASONRY □ MORTAR & GROUT ■ EXPANSION, EPOXY, SCREW ANCHORS ■ SHOT-IN ANCHORS B. SPECIAL INSPECTIONS ■ EXCAVATION, GRADING & FILLING FOR ALL FOUNDATION WORK □ PILE DRIVING & TESTING ■ PLACEMENT OF CONCRETE & REINFORCEMENT □ PLACEMENT OF MASONRY & REINFORCEMENT & DURING GROUTING OPERATIONS ■ SHOP WELDS NOT DONE IN FABRICATOR'S SHOP REGISTERED & APPROVED BY THE BUILDING OFFICIAL ■ FIELD WELDING □ HIGH-STRENGTH BOLTING ■ EXPANSION, EPOXY, SCREW ANCHORS □ SPRAY-APPLIED FIRE PROOFING □ SHOTCRETE ■ GLU-LAM FABRICATION ■ I-JOIST FABRICATION □ WELDED SHEAR STUDS
B
A
S-_014500_N002A 170125. Q2
3.
THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE, TO THE SATISFACTION OF THE ENFORCEMENT AGENCY AND THE ARCHITECT/STRUCTURAL ENGINEER, FOR THE INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION.
4.
SPECIAL INSPECTORS SHALL KEEP RECORDS OF INSPECTIONS. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE ENFORCEMENT AGENCY, OWNER, CONTRACTOR AND ARCHITECT/STRUCTURAL ENGINEER. REPORTS SHALL INDICATE THAT WORK INSPECTED WAS OR WAS NOT COMPLETED IN CONFORMANCE TO APPROVED CONSTRUCTION DOCUMENTS.
5.
DISCREPANCIES IN THE INSPECTED WORK SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF THEY ARE NOT CORRECTED, THE DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENFORCEMENT AGENCY, OWNER, CONTRACTOR AND ARCHITECT/STRUCTURAL ENGINEER PRIOR TO THE COMPLETION OF THAT PHASE OF THE WORK.
6.
A FINAL REPORT DOCUMENTING REQUIRED SPECIAL INSPECTIONS AND CORRECTION OF ANY DISCREPANCIES NOTED IN THE INSPECTIONS SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY, OWNER, CONTRACTOR AND ARCHITECT/STRUCTURAL ENGINEER AT THE COMPLETION OF THE WORK INCLUDED IN THE CONSTRUCTION DOCUMENTS.
7.
SCHEDULE AND COORDINATE ALL STRUCTURAL TESTS AND SPECIAL INSPECTIONS. NOTIFY THE SPECIAL INSPECTOR 48 HOURS MINIMUM PRIOR TO PERFORMING ANY WORK REQUIRING THE SPECIAL INSPECTOR'S PRESENCE. COORDINATE WITH THE SPECIAL INSPECTOR SO THAT THE WORK REQUIRING THE TESTS AND INSPECTIONS NOTED ABOVE IS ACCESSIBLE AND EXPOSED FOR TESTING AND INSPECTION PURPOSES. REMOVE AND/OR REPLACE MATERIALS AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER TO ALLOW TESTS AND INSPECTIONS.
THE GEOTECHNICAL INFORMATION PROVIDED IS NOT A WARRANTY OF THE SITE OR SUBSURFACE CONDITIONS. PRIOR TO BIDDING AND AT NO COST TO THE OWNER, SITE VISITS TO INVESTIGATE OR TO PERFORM ADDITIONAL SUBSURFACE INVESTIGATIONS MAY BE MADE TO DETERMINE THE EXISTING CONDITIONS. SUCH INVESTIGATIONS MAY BE PERFORMED ONLY UNDER TIME SCHEDULES AND ARRANGEMENTS APPROVED BY THE OWNER IN ADVANCE. AN OWNER-RETAINED SPECIAL INSPECTOR/GEOTECHNICAL ENGINEER SHALL PROVIDE TESTING AND INSPECTION SERVICES DURING ALL FOUNDATION AND EARTHWORK. PRIOR TO REQUESTING AN ENFORCEMENT AGENCY FOUNDATION INSPECTION, OBTAIN WRITTEN DOCUMENTATION FROM THE SPECIAL INSPECTOR/GEOTECHNICAL ENGINEER THAT THE FOUNDATION AND EARTHWORK IS IN CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
FOUNDATIONS BELOW GRADE SHALL BE FORMED UNLESS WRITTEN DOCUMENTATION PERMITTING UNFORMED FOOTINGS IS OBTAINED FROM THE SPECIAL INSPECTOR/GEOTECHNICAL ENGINEER. FORWARD WRITTEN DOCUMENTATION TO THE STRUCTURAL ENGINEER FOR REVIEW PRIOR TO THE START OF FOUNDATION EXCAVATIONS. THE SIDES OF UNFORMED FOUNDATION EXCAVATIONS MUST BE ABLE TO STAND WITHOUT CAVING OR SLOUGHING. PROVIDE FORMS OR PROTECTION AS REQUIRED TO PREVENT SLOUGHING OF SOIL INTO EXCAVATIONS. WHERE UNFORMED FOUNDATIONS ARE USED, COORDINATE AND COMPLY WITH THE CONCRETE PROTECTION REQUIREMENTS FOR REINFORCEMENT PLACED ADJACENT TO EARTH. FOUNDATIONS ABOVE GRADE SHALL BE FORMED. ALL FORMS SHALL BE REMOVED ABOVE OR BELOW GRADE, UNLESS OTHERWISE NOTED. THE TOP SURFACE OF FOUNDATIONS SHALL BE LEVEL. THE BOTTOM SURFACE OF FOUNDATIONS IS PERMITTED TO HAVE A SLOPE NOT EXCEEDING ONE UNIT VERTICAL IN TEN UNITS HORIZONTAL. FOOTINGS SHALL BE STEPPED WHERE IT IS NECESSARY TO CHANGE THE ELEVATION OF THE TOP SURFACE OF THE FOOTING OR WHERE THE SURFACE OF THE GROUND AND/OR BOTTOM SURFACE OF THE FOOTINGS SLOPES MORE THAN ONE UNIT VERTICAL IN TEN UNITS HORIZONTAL. STEP FOOTINGS AS REQUIRED PER TYPICAL DETAILS. THE TOP OF EXTERIOR FOOTINGS SHALL BE LOCATED 4 INCHES MINIMUM BELOW LOWEST ADJACENT EXTERIOR FINISHED GRADE OR SURFACE, UNLESS OTHERWISE NOTED. WHERE ADJACENT EXTERIOR FINISHED GRADE OR SURFACE SLOPES DOWN AND AWAY FROM THE FOUNDATION, THE TOP OF EXTERIOR FOOTINGS SHALL BE NO HIGHER THAN THE ELEVATION OF THE FINISHED GRADE OR SURFACE LOCATED 18 INCHES FROM THE FACE OF SUCH FOOTING, UNLESS OTHERWISE NOTED. STEP FOOTINGS AS REQUIRED PER TYPICAL DETAILS TO OBTAIN THE MINIMUM DIMENSIONS REQUIRED.
10. FOUNDATION DEPTHS SHOWN ON THE CONSTRUCTION DOCUMENTS ARE MINIMUM DEPTHS ONLY AND DO NOT NECESSARILY ACCOUNT FOR ALL PIPES, CONDUITS, UTILITIES AND TRENCHES ADJACENT TO OR CROSSING FOOTINGS AS REQUIRED BY ALL OTHER CONSTRUCTION DOCUMENTS. STEP FOOTINGS TO COMPLY WITH THE REQUIREMENTS OF TYPICAL DETAILS FOR PIPES AND CONDUITS AT FOOTINGS. 11. FOR DAMP-PROOFING, WATER-PROOFING AND DRAINAGE SYSTEMS ADJACENT TO FOUNDATIONS, SEE ALL OTHER CONSTRUCTION DOCUMENTS.
CONCRETE MATERIALS, QUALITY CONTROL AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH ACI 318.
2.
SEE CONCRETE MIX DESIGN TABLE FOR REQUIRED CONCRETE PROPERTIES.
3.
PORTLAND CEMENT SHALL CONFORM TO ASTM C150, TYPE II.
4.
AGGREGATES SHALL CONFORM TO ASTM C33 FOR NORMAL-WEIGHT AND ASTM C330 FOR LIGHTWEIGHT CONCRETE. MAXIMUM AGGREGATE SIZE USED IN MIXES SHALL BE APPROPRIATE FOR FORM AND REBAR CLEARANCES TO BE ENCOUNTERED.
5.
REINFORCING STEEL SHALL CONFORM TO ASTM A706, GRADE 60, OR ASTM A615, GRADE 60.
6.
REINFORCING STEEL TO BE WELDED SHALL CONFORM TO ASTM A706, GRADE 60. WELD FILLER METAL FOR REINFORCING STEEL SHALL COMPLY WITH AWS D1.4, Fu=80 KSI. WELDING SHALL CONFORM WITH AWS D1.4.
7.
WELDED WIRE REINFORCEMENT SHALL BE COMPOSED OF FLAT SHEETS AND CONFORM TO ASTM A185.
8.
9.
DIMENSIONS LOCATING REINFORCING STEEL ARE TO THE FACE OF REINFORCING STEEL AND DENOTE CLEAR COVERAGE. MINIMUM CONCRETE COVER SHALL BE AS FOLLOWS, UNO: A. CONCRETE CAST AGAINST EARTH (EXCEPT SLAB ON GRADE) - 3" - SLAB ON GRADE - CENTER REINF IN SLAB, UNO B. CONCRETE FORMED & EXPOSED TO EARTH OR WEATHER: - #6 THRU #18 BARS - 2" - #5 BAR, W31 OR D31 WIRE, & SMALLER - 1 1/2" C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH THE GROUND: - BEAMS & COLUMNS - 1 1/2" - SLABS & WALLS: #14 & #18 BARS - 1 1/2", #11 BAR & SMALLER - 3/4" SPLICES IN CONTINUOUS REINFORCING SHALL BE LAPPED AS NOTED IN THE TYPICAL DETAIL, UNO. SPLICES IN ADJACENT BARS SHALL BE STAGGERED SO THERE IS NO OVERLAP. LAP SPLICES OF #14 & #18 REBAR IS NOT PERMITTED AND BARS SHALL BE CONTINUOUS ONE PIECE FOR THE FULL LENGTH SHOWN. LAP SPLICES OF REBAR IN A BUNDLE SHALL BE EQUAL TO THE LAP SPLICE LENGTH REQUIRED FOR THE INDIVIDUAL BARS WITHIN THE BUNDLE MULTIPLIED BY 1.33. INDIVIDUAL BAR SPLICES WITHIN A BUNDLE SHALL NOT OVERLAP. ENTIRE BUNDLES SHALL NOT BE LAP SPLICED.
S-_033000_N002B 170906. Q1
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
MIX DESIGN TABLE LOCATION
NOTIFY THE SPECIAL INSPECTOR/GEOTECHNICAL ENGINEER 48 HOURS IN ADVANCE OF THE TIME WHEN THE FOUNDATION EXCAVATIONS AND EARTHWORK WILL BE COMPLETE AND READY FOR FORMS OR REINFORCING PLACEMENT. NO FORMS OR REINFORCING SHALL BE PLACED IN ANY FOUNDATION UNTIL THE EXCAVATION HAS BEEN INSPECTED AND APPROVED BY THE SPECIAL INSPECTOR/GEOTECHNICAL ENGINEER. FOUNDATIONS SHALL EXTEND INTO FIRM BEARING IN UNDISTURBED SOIL, OR WHERE REQUIRED, IN COMPACTED FILL MATERIAL OR CONTROLLED LOW-STRENGTH MATERIAL PER THE CONSTRUCTION DOCUMENTS. FOUNDATION DEPTHS SHOWN ON THE CONSTRUCTION DOCUMENTS ARE MINIMUM DEPTHS ONLY. FOUNDATION EXCAVATIONS MAY BE REQUIRED TO BE OVER-EXCAVATED TO REACH SUITABLE BEARING MATERIAL. WHERE THE SPECIAL INSPECTOR/GEOTECHNICAL ENGINEER HAS DETERMINED OVER-EXCAVATION IS REQUIRED, THE REMOVED MATERIAL MAY BE REPLACED WITH COMPACTED FILL MATERIAL OR CONTROLLED LOW-STRENGTH MATERIAL PER THE CONSTRUCTION DOCUMENTS.
CONCRETE MIX DESIGN
BELOW GRADE CONCRETE (FTGS, PIERS, GRADE BEAMS) & BLDG CURBS & STEM WALLS SLAB ON GRADE
SITE CONCRETE (PAVEMENTS, CURBS AND GUTTERS) UNLESS OTHERWISE SPECIFIED
APP. 02-117123
ACI REQ SCM REQ EARLY REQ 56 DAY AIR MAX MAX (% BY WEIGHT COMPRESSIVE COMPRESSIVE CONTENT W/C AIR-DRY EXPOSURE CLASS OF TOTAL RATIO WEIGHT STRENGH STRENGH CEMENTITIOUS (PSI) (PSI) (LBS/FT3) MATERIALS)
15
2500 PRIOR TO LOADING
15
-
4000
NONE
0.45
145
F1, S0, P0, C1
NONE*
0.45
145
F0, S0, P0, C1
REVIEWED FOR SS
14. FOUNDATION EXCAVATIONS SHALL BE MADE TO THE SIZES AND SHAPES REQUIRED BY THE CONSTRUCTION DOCUMENTS. NO MATERIAL IS TO BE EXCAVATED UNNECESSARILY.
FLS
ACS
✔
✔
07/03/2019
4000
15
-
3500
NONE*
0.50
145
F1, S0, P0, C1
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
* 3 PERCENT MAX AIR AT STEEL TROWELED CONCRETE UNLESS CONCTRACTOR CAN ASSURE THAT DELAMINATION WILL NOT OCCUR. PROTECT SLABS UNTIL SPACE IS CONDITIONED IF AIR CONTENT IS LESS THAN 4.5 PERCENT.
10. UNLESS DETAILED OTHERWISE: REINFORCING IN CONTINUOUS BEAMS AND SPANDRELS SHALL HAVE THE TOP BARS SPLICED AT MID-SPAN AND THE BOTTOM BARS SPLICED AT THE CENTERLINE OF SUPPORTS. REINFORCING IN CONTINUOUS SOIL-BEARING GRADE BEAMS OR FOOTINGS SHALL HAVE THE TOP BARS SPLICED AT CENTERLINE OF COLUMN SUPPORTS AND THE BOTTOM BARS SPLICED AT MID-SPAN. AT DISCONTINUOUS ENDS, THE BARS SHALL BE TERMINATED WITH A STANDARD HOOK EXTENDED TO THE FAR FACE OF THE SUPPORT OR BEAM. 11. PROVIDE FOUNDATION DOWELS TO MATCH GRADE, QUANTITY, SIZE & SPACING OF WALL/COLUMN REINFORCEMENT. EXTEND DOWELS INTO FOOTINGS AND TERMINATE WITH A STANDARD HOOK 3" ABOVE BOTTOM OF FOOTING, UNO. PROVIDE STANDARD LAP AT DOWELS TO EACH WALL/COLUMN REBAR. 12. HOOKS SHALL BE STANDARD HOOKS, UNO. 13. ITEMS TO BE EMBEDDED IN CONCRETE, SUCH AS REINFORCING, DOWELS, BOLTS, ANCHORS, SLEEVES, ETC SHALL BE SECURELY TIED AND SUPPORTED PRIOR TO PLACING CONCRETE.
SEAL
14. THE LOCATION OF SLAB ON GRADE JOINTS SHALL BE AS INDICATED ON THE DRAWINGS. SLAB ON GRADE JOINT SPACINGS ARE NOT TO EXCEED 12'-0" IN EITHER DIRECTION, UNO. SUBMIT LOCATION PLAN FOR ALL PROPOSED JOINTS FOR REVIEW.
FESSIONA PRO L ED RRY J. VOLKE E
15. SURFACE OF CONSTRUCTION JOINTS SHALL BE CLEANED AND LAITANCE REMOVED. IMMEDIATELY BEFORE CONCRETE IS PLACED, CONSTRUCTION JOINTS SHALL BE WETTED AND STANDING WATER REMOVED. CONSTRUCTION JOINT SURFACES SHALL BE ROUGHENED TO A 1/4" MINIMUM AMPLITUDE, UNO.
T
T
E
16. FORM 3/4" CHAMFER AT ALL EXPOSED WALL AND COLUMN EDGES AND CORNERS, UNO.
No. S3737
A RU C T UR O F OF I CAL
05/15/2019 17. EXTERIOR SLABS INCLUDING SIDEWALKS SHALL BE 4" MIN THICKNESS AND HAVE 6x6-W1.4xW1.4 WWR IN CENTER OF SLAB, UNO. 18. NO CONDUIT, PIPE, OR SLEEVES LARGER THAN 1" OD SHALL BE PLACED IN OR THROUGH CONCRETE BEAMS OR SLABS UNLESS SPECIFICALLY DETAILED AND APPROVED BY THE STRUCTURAL ENGINEER. CONDUIT OR PIPES 1" OD AND SMALLER SHALL BE SPACED & POSITIONED SUCH THAT THE EFFECTIVENESS OF THE REBAR IS NOT REDUCED.
PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
15. EXTERIOR FINISHED GRADES OR SURFACES SHALL HAVE POSITIVE DRAINAGE AWAY FROM FOUNDATIONS. GROUND SURFACES WITHIN TEN FEET OF THE BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 5%. PAVED SURFACES WITHIN TEN FEET OF THE BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2%. PLANTERS SHALL HAVE ADEQUATE SURFACE DRAINAGE TO PREVENT STANDING WATER ADJACENT TO THE FOUNDATIONS. 16. WHERE EXCAVATIONS OCCUR ADJACENT TO EXISTING STRUCTURES, PROVIDE ADEQUATE UNDERPINNING, SHORING OR SUPPORT TO PREVENT SETTLEMENT AND LATERAL MOVEMENT OF THE EXISTING FOUNDATIONS. FOUNDATIONS ADJACENT TO EXISTING FOUNDATIONS SHALL PENETRATE A MINIMUM OF THE SAME DEPTH AS EXISTING, UNLESS OTHERWISE NOTED.
ISSUED
MARK
17. FOUNDATION SIZES SHALL BE AS REQUIRED ON THE CONSTRUCTION DOCUMENTS. THE MINIMUM DEPTH NOTED SHALL BE BELOW THE ADJACENT UNDISTURBED GROUND SURFACE. THE MINIMUM DEPTH SHALL ALSO EXTEND BELOW THE FROST LINE OF THE LOCALITY. FOOTINGS SHALL NOT BEAR ON FROZEN SOIL.
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
TITLE
TYPICAL NOTES
SHEET
5/15/2019 4:35:20 PM
✔
DATE:
12. FOUNDATION ELEMENTS SHOWN ARE INDICATED IN THEIR COMPLETED LOCATION AND CONDITION. FILL AROUND FOUNDATION ELEMENTS SHALL BE PLACED IN LIFTS AND COMPACTED IN A MANNER THAT DOES NOT DAMAGE OR MOVE THE FOUNDATION, WATER-PROOFING OR DAMP-PROOFING. SHORE AND ADEQUATELY SUPPORT FOUNDATION ELEMENTS WHILE PLACING FILL UNTIL THE FOUNDATION ELEMENTS AND THEIR SUPPORTING STRUCTURAL ELEMENTS HAVE BEEN COMPLETED AND ATTAINED THEIR REQUIRED DESIGN STRENGTHS. 13. FOUNDATION EXCAVATIONS SHALL BE CLEANED OF DEBRIS, LOOSE SOIL AND STANDING WATER DURING CONSTRUCTION AND IMMEDIATELY PRIOR TO CONCRETE PLACEMENT. PROVIDE FOR DE-WATERING IF WATER IS PRESENT IN THE EXCAVATIONS DUE TO ANY SOURCE.
INC:
A
STRUCTURAL TESTING & INSPECTION
THE GEOTECHNICAL INFORMATION PROVIDED IS BASED UPON A GEOTECHNICAL REPORT PROVIDED BY THE OWNER FOR THIS PROJECT. THE GEOTECHNICAL REPORT WAS USED FOR THE DESIGN INDICATED IN THESE CONSTRUCTION DOCUMENTS. THE GEOTECHNICAL REPORT AND THE RECOMMENDATIONS CONTAINED THEREIN SHALL BE USED IN CONJUNCTION WITH THE CONSTRUCTION DOCUMENTS. COMPLY WITH THE REQUIREMENTS AND RECOMMENDATIONS CONTAINED IN THE GEOTECHNICAL REPORT.
1.
S-_033000_N002A 170907. Q2
S
C
13. THE MINIMUM REQUIRED STRUCTURAL SUBMITTALS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING MARKED ITEMS: □ PILE FABRICATION DRAWINGS AND CALCULATIONS ■ CONCRETE MIX DESIGNS AND SUBSTANTIATING TEST DATA ■ CONCRETE REINFORCING PLACEMENT DRAWINGS ■ CONCRETE PRODUCT CERTIFICATION AND DATA SHEETS ■ CONCRETE SLAB JOINT LAYOUT □ MASONRY REINFORCING PLACEMENT DRAWINGS □ MASONRY GROUT MIX DESIGNS AND SUBSTANTIATING TEST DATA □ MASONRY MORTAR MIX DESIGNS □ MASONRY PRODUCT CERTIFICATION AND DATA SHEETS ■ STRUCTURAL STEEL SHOP DRAWINGS □ STEEL DECK PLACEMENT DRAWINGS AND DATA SHEETS □ WELDING PROCEDURE SPECIFICATIONS □ METAL-PLATE-CONNECTED WOOD TRUSS PLACEMENT DRAWINGS AND CALCULATIONS ■ WOOD I-JOIST PLACEMENT DRAWINGS AND CALCULATIONS □ METAL WEB WOOD JOIST PLACEMENT DRAWINGS AND CALCULATIONS ■ GLUED-LAMINATED TIMBER FABRICATION AND PLACEMENT DRAWINGS AND CERTIFICATIONS ■ PRE-ENGINEERED LUMBER CERTIFICATIONS AND DATASHEETS □ OPEN WEB STEEL JOIST PLACEMENT DRAWINGS AND CALCULATIONS □ PRE-ENGINEERED STEEL STAIR SHOP DRAWINGS AND CALCULATIONS □ COLD-FORMED STEEL FRAMING PRODUCTS, ACCESSORIES, DATA SHEETS AND CALCULATIONS
ALL FOUNDATION AND EARTHWORK INCLUDING, BUT NOT LIMITED TO, EXCAVATION, GRADING, FILLING, SUB-GRADE PREPARATION, SOIL TREATMENT, ASSOCIATED SITE WORK, TRENCHING AND BACKFILLING SHALL BE PERFORMED IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS.
REINFORCED CONCRETE
ST
12. SUBMITTALS THAT HAVE BEEN REVIEWED AND RETURNED BY THE STRUCTURAL ENGINEER, REGARDLESS OF MARKINGS ON THE SUBMITTALS, SHALL NOT BE CONSTRUED TO PERMIT WORK NOT CONFORMING TO THE REQUIREMENTS OF THE CONSTRUCTION DOCUMENTS.
9.
S-_033000_N003A 170125. Q2
5
EER GIN EN R
11. SUBMITTALS THAT WILL REQUIRE ADDITIONAL REVIEW, IN THE STRUCTURAL ENGINEER'S JUDGMENT, WILL BE MARKED "RESUBMIT". THE SUBMITTAL SHALL BE REVISED AND RESUBMITTED FOR RE-REVIEW AND IS SUBJECT TO ALL THE REQUIREMENTS OF THE INITIAL SUBMITTAL. PROVIDE OWNER REIMBURSEMENT FOR STRUCTURAL ENGINEER COSTS INCURRED TO RE-REVIEW SUBMITTALS.
4
L N IA
STRUCTURAL SUBMITTALS
3
R
2
REGIST ER K
2"
1
S-011
017294 ?00.00.00? LIONAKIS 2017
0 1/4" 1/2"
1"
1.
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
2.
3.
D
4.
5.
6.
7.
WOOD STRUCTURAL PANELS PERMANENTLY EXPOSED IN OUTDOOR APPLICATIONS SHALL HAVE AN EXTERIOR ADHESIVE BOND CLASSIFICATION. ROOF SHEATHING PERMANENTLY EXPOSED TO THE OUTDOORS ONLY ON THE UNDERSIDE OF PROTECTED OVERHANGS IS PERMITTED TO HAVE AN EXPOSURE 1 ADHESIVE BOND CLASSIFICATION. WOOD STRUCTURAL PANELS FOR ALL OTHER USES SHALL HAVE AN EXPOSURE 1 ADHESIVE BOND CLASSIFICATION, UNO. PRESERVATIVE-TREATED WOOD PRODUCTS SHALL CONFORM TO THE REQUIREMENTS OF AWPA STANDARD U1. EACH PIECE SHALL BEAR AN AWPA QUALITY MARK OF AN ALSC APPROVED INSPECTION AGENCY. CARE FOR PRODUCTS SHALL CONFORM TO THE REQUIREMENTS OF AWPA STANDARD M4. UNTREATED SURFACES EXPOSED BY DAMAGE OR FIELD FABRICATION SHALL BE FIELD TREATED. PRODUCTS SHALL HAVE A MAXIMUM MOISTURE CONTENT OF 19% WHEN INSTALLED. PRESERVATIVE-TREATED WOOD PRODUCTS SHALL BE USED FOR STRUCTURAL MEMBERS (ALL FRAMING AND STRUCTURAL PANELS) AT THE FOLLOWING LOCATIONS, UNO: • ALL FLOOR FRAMING AND STRUCTURAL PANELS WHEN JOISTS OR PANELS ARE LESS THAN 18", OR GIRDERS ARE LESS THAN 12" TO EXPOSED EARTH IN UNDER-FLOOR SPACES LOCATED WITHIN THE BUILDING FOUNDATION PERIMETER • MEMBERS SUPPORTED BY EXTERIOR FOUNDATIONS AND LESS THAN 8” FROM EXPOSED EARTH • MEMBERS IN CONTACT WITH EXTERIOR OR BELOW GRADE CONCRETE OR MASONRY WALLS • MEMBERS IN CONTACT WITH CONCRETE OR MASONRY SLABS ON GRADE OR FOOTINGS • MEMBERS SUPPORTING EXTERIOR WOOD SIDING THAT IS LESS THAN 6” FROM EXPOSED EARTH OR LESS THAN 2” FROM HORIZONTAL CONCRETE OR MASONRY SURFACES • MEMBERS PERMANENTLY EXPOSED TO WEATHER AND NOT FULLY PROTECTED • MEMBERS IN CONTACT WITH EARTH THE INSTALLATION OF FASTENERS SHALL BE IN ACCORDANCE WITH THE NATIONAL DESIGN SPECIFICATION (NDS) FOR WOOD CONSTRUCTION. THE NUMBER AND SIZE OF FASTENERS CONNECTING WOOD MEMBERS SHALL NOT BE LESS THAN SPECIFIED IN THE BUILDING CODE, UNO. FASTENER MATERIALS SHALL COMPLY WITH THE BENDING YIELD STRENGTHS LISTED IN NDS APPENDIX I. FASTENERS SHALL BE TIGHTENED ON INSTALLATION & RETIGHTENED JUST PRIOR TO CLOSING IN. FASTENERS AND WOOD CONSTRUCTION CONNECTORS (PREMANUFACTURED OR AS INDICATED) THAT ARE: PERMANENTLY EXPOSED TO WEATHER, IN CONTACT WITH PRESERVATIVE-TREATED WOOD OR IN CONTACT WITH FIRE-RETARDANT-TREATED WOOD SHALL BE HOT-DIPPED, ZINCCOATED GALVANIZED STEEL OR STAINLESS STEEL. THE COATING WEIGHTS FOR ZINC-COATED FASTENERS SHALL BE IN ACCORDANCE WITH ASTM A153. FASTENERS OTHER THAN NAILS, WOOD SCREWS AND LAG SCREWS SHALL BE PERMITTED TO BE OF MECHANICALLY DEPOSITED ZINC-COATED STEEL WITH COATING WEIGHTS IN ACCORDANCE WITH ASTM B695, CLASS 55 MINIMUM.
WOOD SCREWS SHALL CONFORM TO ANSI/ASME STANDARD B18.6.1. SCREWS SHALL BE MADE FROM HEAT TREATED CARBON STEEL WIRE WITH HEADS, LENGTHS AND SIZES AS INDICATED. SCREWS SHALL BE SELF DRILLING. INSTALL SCREWS SUCH THAT END DISTANCES, EDGE DISTANCES AND SPACINGS ARE SUFFICIENT TO PREVENT SPLITTING OF THE WOOD.
10. LAG SCREWS SHALL CONFORM TO ANSI/ASME STANDARD B18.2.1. LAG SCREWS SHALL HAVE HEX HEADS AND CONFORM TO THE MATERIAL REQUIREMENTS OF ASTM A307, GRADE A. LAG SCREW SHANK AND THREADS SHALL BE THE SAME FULL BODY DIAMETER SPECIFIED. 11. BOLTS SHALL CONFORM TO ANSI/ASME STANDARD B18.2.1. BOLTS SHALL HAVE HEX HEADS AND CONFORM TO ASTM A307, GRADE A. PROVIDE HEX NUTS AT BOLTS THAT CONFORM TO ASTM A563, GRADE A. BOLT SHANK AND THREADS SHALL BE THE SAME FULL BODY DIAMETER SPECIFIED. 12. BOLTS AND LAG SCREWS SHALL BE PROVIDED WITH A STANDARD CUT WASHER UNDER HEADS AND NUTS WHICH BEAR ON WOOD, UNO. SEE ROUGH CARPENTRY WASHER SCHEDULE FOR SIZE, OF PLATE OR MALLEABLE IRON WASHERS WHERE REQD. WHERE BOLT OR LAG SCREW SPACING CAUSES WASHERS TO OVERLAP, PROVIDE A CONTINUOUS PLATE WASHER (ONE PIECE) THAT MATCHES WIDTH, THICKNESS AND HOLE DIAMETER SHOWN IN WASHER SCHEDULE. 13. PREDRILL HOLES IN WOOD MEMBERS FOR BOLTS AND LAG SCREWS. BOLT HOLES SHALL BE 1/16" LARGER THAN THE BOLT DIAMETER FOR THE FULL DEPTH OF BOLT. LAG SCREW HOLES SHALL BE THE SAME DIAMETER & DEPTH AS THE UNTHREADED LAG SCREW SHANK. PROVIDE HOLES EQUAL TO 50% OF FASTENER DIAMETER FOR THE THREADED PORTION OF LAG SCREWS. HOLES SHALL BE PERPENDICULAR, UNO, TO CONNECTED SURFACES AND ACCURATELY ALIGNED IN MAIN MEMBERS AND SIDEPLATES. FASTENERS SHALL NOT BE FORCIBLY DRIVEN. 14. INSTALL BOLTS AND LAG SCREWS SUCH THAT END DISTANCES, EDGE DISTANCES AND SPACINGS ARE SUFFICIENT TO PREVENT SPLITTING OF THE WOOD. SPACE BOLTS AND LAG SCREWS FOUR DIAMETERS CENTER TO CENTER, FOUR DIAMETERS FROM WOOD EDGES, EIGHT DIAMETERS FROM WOOD ENDS AND TWO DIAMETERS FROM STEEL SIDE PLATE EDGES OR ENDS, UNO. 15. PREFABRICATED WOOD CONSTRUCTION CONNECTORS INDICATED IN THE DRAWINGS ARE PER THE LATEST EDITION OF THE “WOOD CONSTRUCTION CONNECTORS” CATALOG BY THE SIMPSON STRONG-TIE COMPANY INC. CONNECTORS USED MUST BE LISTED IN A CURRENT AND VALID EVALUATION REPORT BY AN EVALUATION AGENCY RECOGNIZED BY THE ENFORCEMENT AGENCY. EACH CONNECTOR SHALL BE IDENTIFIED BY A FACTORY APPLIED MANUFACTURER’S STAMP. INSTALL CONNECTORS AND REQUIRED FASTENERS PER INSTRUCTIONS IN THE CATALOG AND REPORTS BEFORE LOADING THE CONNECTION. USE THE SPECIFIED FASTENER TYPE, SIZE, MATERIAL, FINISH AND QUANTITY, FILLING ALL FASTENER HOLES WITHOUT OVERDRIVING OR UNDERDRIVING THE FASTENER. ONLY BEND CONNECTORS ONCE THAT ARE SPECIFICALLY DESIGNED TO BE BENT. DO NOT BEND OR MODIFY CONNECTORS UNLESS SPECIFICALLY SHOWN.
B
16. HANGERS SHALL BE INSTALLED AT ALL BEAMS, RAFTERS AND JOISTS THAT DO NOT BEAR DIRECTLY ON A SUPPORTING WALL OR BEAM. HANGERS SHALL MATCH THE MEMBER SIZE, SLOPE AND SKEW, UNO. PROVIDE HANGERS WITH STRAIGHT OR CONCEALED FLANGES AS NECESSARY SO THAT FLANGE NAILS ARE PLACED INTO SIDE GRAIN OF CARRYING MEMBER. HANGERS AT 2X AND 3X FRAMING SHALL BE “SIMPSON” LUS AND HANGERS AT 4X AND LARGER FRAMING SHALL BE “SIMPSON” HU-TYPE, UNO. 17. POSTS IN STUD WALLS SHALL HAVE FRAMING ANGLES EACH SIDE AT TOP AND BOTTOM TO PLATES UNO. POSTS SUPPORTING OR SUPPORTED BY BEAMS SHALL HAVE MATCHING SIZE "SIMPSON" PC OR EPC POST CAPS, UNO. POSTS BEARING ON CONCRETE SHALL HAVE MATCHING SIZE "SIMPSON" ABU POST BASE, UNO.
5/15/2019 4:35:22 PM
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
18. FRAMING ANGLES SHALL BE BY "SIMPSON" AND OF THE FOLLOWING MINIMUM SIZES, UNO. INSTALL “A” ANGLES WITH 8D X 1 1/2” NAILS AND “LS” ANGLES WITH 10D X 1 1/2" NAILS. NOMINAL FRAMING DEPTH/WIDTH “SIMPSON” FRAMING ANGLE 4” A34 OR LS30 6” A35 OR LS50 8” LS70 10” AND 12” LS90 19. BEAMS, RAFTERS AND JOISTS SHALL BE BRACED AT ENDS AND AT POINTS OF SUPPORT TO PREVENT ROTATION AND/OR LATERAL DISPLACEMENT. BRACING SHALL BE BY 2X FULL DEPTH SOLID BLOCKING BETWEEN EACH MEMBER, BY CONNECTION TO A CONTINUOUS 2X MINIMUM FULL DEPTH SOLID BAND, RIM OR LEDGER MEMBER, OR BY PREFABRICATED FACE MOUNT HANGERS. 20. RAFTERS AND JOISTS OVER 10 INCH NOMINAL DEPTH SHALL BE BRACED BETWEEN ENDS AND BETWEEN POINTS OF SUPPORT TO PREVENT ROTATION AND/OR LATERAL DISPLACEMENT. BRACING SHALL BE BY 2X FULL DEPTH SOLID BLOCKING BETWEEN EACH MEMBER OR BY PREFABRICATED METAL BRIDGING INSTALLED BETWEEN EACH MEMBER SPACED AT INTERVALS NOT EXCEEDING 8'-0". 21. STUD WALLS SHALL BE BRACED BY MINIMUM 2X STUD DEPTH SOLID BLOCKING BETWEEN EACH STUD SPACED VERTICALLY AS FOLLOWS: AT 8'-0" OC MAXIMUM, AT EACH SP EDGE JOINT, AND AT 6'-0" OC MAXIMUM FOR WALLS WITHOUT SP OR GYPSUM BOARD APPLIED ON AT LEAST ONE FACE OF STUD. 22. HOLES REQUIRED FOR PASSING STRAPS OR HARDWARE THROUGH SP SHALL BE NEATLY DRILLED ROUND HOLES OR NEATLY SLOTTED HOLES. DO NOT OVERCUT. THE DIMENSION OF HOLES OR SLOTS SHALL NOT EXCEED THE STRAP OR HARDWARE DIMENSION BY MORE THAN 1/4 INCH. 23. HOLES OR NOTCHES IN ANY MEMBERS SHALL COMPLY WITH TYPICAL DETAILS UNLESS SPECIFICALLY SHOWN OTHERWISE.
A
FASTENING
2.
(1) 16D
GLUED-LAMINATED TIMBERS SHALL BE MANUFACTURED AND IDENTIFIED IN CONFORMANCE WITH AITC A190.1 & ASTM D3737.
1.
DESIGN IS FOR DRY CONDITIONS OF USE, BUT ADHESIVE USED SHALL BE FOR WET CONDITIONS OF USE PER AITC A190.1.
2.
FACE NAIL
3.
DESIGN IS FOR SERVICE TEMPERATURES LESS THAN 150° F.
4.
APPEARANCE SHALL BE INDUSTRIAL GRADE, UNO. EACH MEMBER SHALL BE IDENTIFIED IN ACCORDANCE WITH AITC A190.1.
TO PERPENDICULAR BEARINGS FOR EACH 2" OF BEARING LENGTH
(2) 8D
TOE NAIL STAG
5.
TO PARALLEL BEARINGS
8D @ 6" OC
TOE NAIL STAG
DOUBLE MEMBERS FOR EACH 4" OF MEMBER DEPTH
(1) 16D @ 16" OC
FACE NAIL
SPECIAL INSPECTION IS NOT REQUIRED MEMBERS OF 5BE 1/8 INCH MAX 6. OVER 5 1/8" WIDE AND 18" DEEP FOR AND NON-CUSTOM WITH A SPAN OVER 32' SHALL CONTINUOUSLY 6. MEMBERS WIDTH ANDBY 18AINCH MAX DEPTH, AND A MAX CLEAR SPAN OF 32 FEET, MANUFACTURED AND INSPECTED QUALIFIED SPECIAL INSPECTOR APPROVED BY THE ENFORCEMENT AGENCY. MARKED IN ACCORDANCE WITH ANSI/AITC A 190/1 SECTION 6.1.1 FOR NON-CUSTOM 7. EACH MEMBER SHALL BE INDIVIDUALLY WRAPPED DURING SHIPPING AND FIELD HANDLING PER MEMBERS AITC 111. 7. EACH MEMBER SHALL BE INDIVIDUALLY WRAPPED DURING SHIPPING AND FIELD HANDLING PER 8. SUBMIT FABRICATION AND INSTALLATION DRAWINGS FOR REVIEW PRIOR TO FABRICATION. AITC 111.
TO RIMS, BANDS, HIPS, OR RIDGES TO 2x - FOR EACH 2" OF MEMBER DEPTH (1) 16D TO 3x OR GREATER - FOR EA 2" OF MEMBER DEPTH (2) 8D
END NAIL TOE NAIL STAG
DOUBLE TOP PLATES UPPER TO LOWER PLATE FOR EACH 2" OF PLATE WIDTH AT EA LAP SPLICE AT INTERSECTIONS - FOR EA 2" OF PLATE WIDTH
(1) 16D @ 16" OC (8) 16D (1) 16D
FACE NAIL FACE NAIL FACE NAIL
STUDS TO TOP PLATES, SILL & SOLE PLATES OR BEAMS TO 2x - FOR EA 2" OF STUD WIDTH
(1) 16D OR (2) 8D
END NAIL TOE NAIL
(2) 8D
TOE NAIL
(1) 16D @ 16" OC
FACE NAIL
TO PERPENDICULAR FRAMING OR BLOCKING FOR EACH 2" OF PLATE WIDTH
(1) 16D
FACE NAIL
TO PARALLEL FRAMING OR BLOCKING
16D @ 6" OC
FACE NAIL
TO SIDES OF JOIST, RAFTERS OR STUDS FOR EACH 4" OF BLOCKING DEPTH/WIDTH
(2) 8D
TOE NAIL STAG
TO PERPENDICULAR BEARINGS FOR EACH 2" OF BEARING LENGTH
(2) 8D
TOE NAIL STAG
8D @ 6" OC ((3) MIN)
TOE NAIL STAG
TO 3x OR GREATER - FOR EACH 2" OF STUD WIDTH DOUBLE STUDS OR STUD LAP TO POST FOR EACH 4" OF STUD WIDTH SILL & SOLE PLATES
BLOCKING
TO PARALLEL BEARINGS LEDGERS TO STUDS - FOR EA 2" OF LEDGER DEPTH
(1) 16D
FACE NAIL
TO PARALLEL BLOCKING OR FRAMING
16D @ 6" OC
FACE NAIL
BEAMS 4x AND LARGER TO KING STUD - FOR EA 2" OF BEAM DEPTH TO BEARINGS - FOR EACH 2" OF BEARING LENGTH
(2) 16D (2) 16D
END NAIL TOE NAIL STAG
POSTS 4x AND LARGER TO TOP PLATES, SILL & SOLE PLATES OR BEAMS TO 2x - FOR EACH 2" OF POST WIDTH TO 3x OR GREATER - FOR EACH 2" OF POST WIDTH
(2) 16D (2) 16D
END NAIL TOE NAIL STAG
NOTES: CONDITIONS SHOWN ARE FOR COMMON NAILS AT 2X FRAMING, UNO. WHERE 3x FRAMING OCCURS USE 40D BOX NAILS INSTEAD OF 16D COMMONS AT NOTED FACE NAIL CONNECTIONS.
SP NAILING SCHEDULE
S-_061100_N001A 170126. Q2
WOOD STRUCTURAL PANEL NAILING SCHEDULE (UNO) - PROVIDE 1/8" SPACE BETWEEN SHEETS FOR ALL SP SHEATHING. - MIN SHEET WIDTH SHALL BE 24" FOR ROOF & FLOOR, 12" FOR WALLS. ROOF - 19/32" STRUCT I SP, APA SPAN RATED 40/20 ARRANGE SHEETS AS SHOWN ON ROOF FRAMING PLAN EN AT PERIMETER OF EA SHEET FN AT INTERIOR CONTACTS OF EA SHEET BN AT PERIMETER OF ROOF
8D @ 6" OC 8D @ 12" OC 8D @ 6" OC
SIDE JOINTS TO BE BLOCKED W/ 2X3 FLAT NAILED W/ (2) 8d EA END TO JOIST OR RAFTER.
WALL - 15/32" STRUCT I SP, APA SPAN RATED 32/16 PLACE SHEETS VERTICALLY ON STUDS EN AT PERIMETER OF EA SHEET FN AT INTERIOR CONTACTS OF EA SHEET
STRUCTURAL STEEL
S-_051200_N001A_ 170125. Q2
THE DESIGN, FABRICATION AND ERECTION OF STEEL SHALL BE IN ACCORDANCE WITH AISC 360 AND AISC 341 INCLUDING ANY ENFORCEMENT AGENCY AMENDMENTS.
8D @ 6" OC 8D @ 12" OC
HORIZONTAL JOINTS TO BE BLOCKED W/ 2X STUD THICKNESS WHERE 2X STUDS ARE INDICATED OR 3X STUD THICKNESS WHERE 3X STUDS ARE INDICATED
9. FROM AND SPECIES & GRADESDRAWINGS OF LUMBERFOR WHICH WILLPRIOR PRODUCE DESIGN VALUES 8. MANUFACTURE SUBMIT FABRICATION INSTALLATION REVIEW TO FABRICATION. EQUAL TO OR EXCEEDING THE FOLLOWING WHEN LOADED PERPENDICULAR TO THE WIDE OF THE LAMINATIONS: 9. FACES MANUFACTURE FROM SPECIES & GRADES OF LUMBER WHICH WILL PRODUCE DESIGN VALUES INTERIOR AND THE EXTERIOR PROTECTED EQUAL TOLOCATIONS OR EXCEEDING FOLLOWING WHEN LOCATIONS LOADED PERPENDICULAR TO THE WIDE •FACES SIMPLE SPAN BEAMS: 24F-V4 DF/DF OF THE LAMINATIONS: BENDING (Fb) = 2400 PSIEXTERIOR (TENSION PROTECTED ZONE) INTERIOR LOCATIONS AND LOCATIONS (Fb) =BEAMS: 1850 PSI (COMPRESSION ZONE) • BENDING SIMPLE SPAN 24F-V4 DF/DF SHEAR PARALLEL TOPSI GRAIN (Fv) = 240 PSI BENDING (Fb) = 2400 (TENSION ZONE) MODULUS OF ELASTICITY (E) = 1,800,000 PSI BENDING (Fb) = 1850 PSI (COMPRESSION ZONE) • CANTILEVERED AND BEAMS SHEAR PARALLEL TOCONTINUOUS GRAIN (Fv) = 240 PSI AND TRUSS TOP AND BOTTOM CHORDS: 24F V8 DF/DF MODULUS OF ELASTICITY (E) = 1,800,000 PSI (Fb) = 2400 (TENSION ZONE) • BENDING CANTILEVERED AND PSI CONTINUOUS BEAMS AND TRUSS TOP AND BOTTOM CHORDS: BENDING (Fb) = 2400 PSI (COMPRESSION ZONE) 24F V8 DF/DF SHEAR PARALLEL TOPSI GRAIN (Fv) = 240 PSI BENDING (Fb) = 2400 (TENSION ZONE) MODULUS OF ELASTICITY (E) = 1,800,000 PSI BENDING (Fb) = 2400 PSI (COMPRESSION ZONE) • POSTS TRUSSTO WEBS: DOUGLAS SHEAR AND PARALLEL GRAIN (Fv) = 240FIR PSICOMBINATION 3 DF COMPRESSION PARALLEL (E) TO =GRAIN (Fc) PSI = 1850 PSI (2 OR MORE LAMINATIONS) MODULUS OF ELASTICITY 1,800,000 PARALLEL GRAIN (Fc) 2300 PSI (4 OR3 MORE LAMINATIONS) • COMPRESSION POSTS AND TRUSS WEBS:TO DOUGLAS FIR =COMBINATION DF TENSION PARALLEL TO GRAIN (Ft) = 1450 COMPRESSION PARALLEL TO GRAIN (Fc) PSI = 1850 PSI (2 OR MORE LAMINATIONS) MODULUS OF ELASTICITY 1,900,000 COMPRESSION PARALLEL(E) TO=GRAIN (Fc)PSI = 2300 PSI (4 OR MORE LAMINATIONS) TENSION PARALLEL TO GRAIN (Ft) = 1450 PSI EXTERIOR EXPOSED LOCATIONS MODULUS OF ELASTICITY (E) = 1,900,000 PSI • SIMPLE SPAN BEAMS: ALASKAN CEDAR 20F-V12 AC/AC BENDING (Fb) = 2000 PSI (TENSION ZONE) EXTERIOR EXPOSED LOCATIONS (Fb) =BEAMS: 1400 PSI (COMPRESSION ZONE) AC/AC • BENDING SIMPLE SPAN ALASKAN CEDAR 20F-V12 SHEAR PARALLEL TOPSI GRAIN (Fv) = 240 PSI BENDING (Fb) = 2000 (TENSION ZONE) MODULUS OF ELASTICITY (E) = 1,500,000 PSI BENDING (Fb) = 1400 PSI (COMPRESSION ZONE) • CANTILEVERED AND BEAMS SHEAR PARALLEL TOCONTINUOUS GRAIN (Fv) = 240 PSI AND TRUSS TOP AND BOTTOM CHORDS: ALASKAN 20F-V13 AC/AC MODULUSCEDAR OF ELASTICITY (E) = 1,500,000 PSI (Fb) = 2000 (TENSION ZONE) • BENDING CANTILEVERED AND PSI CONTINUOUS BEAMS AND TRUSS TOP AND BOTTOM CHORDS: BENDING = 2000 PSI (COMPRESSION ZONE) ALASKAN (Fb) CEDAR 20F-V13 AC/AC SHEAR PARALLEL TOPSI GRAIN (Fv) = 240 PSI BENDING (Fb) = 2000 (TENSION ZONE) MODULUS OF ELASTICITY (E) = 1,500,000 PSI BENDING (Fb) = 2000 PSI (COMPRESSION ZONE) • POSTS TRUSSTO WEBS: ALASKAN CEDAR SHEAR AND PARALLEL GRAIN (Fv) = 240 PSI COMBINATION 70 AC COMPRESSION PARALLEL (E) TO =GRAIN (Fc) PSI = 1450 PSI MODULUS OF ELASTICITY 1,500,000 PARALLEL TO GRAIN (Ft) = 975 PSI COMBINATION 70 AC • TENSION POSTS AND TRUSS WEBS: ALASKAN CEDAR MODULUS OF ELASTICITY 1,300,000 COMPRESSION PARALLEL(E) TO=GRAIN (Fc)PSI = 1450 PSI TENSION PARALLEL TO GRAIN (Ft) = 975 PSI MODULUS OF ELASTICITY (E) = 1,300,000 PSI
3.
4.
EXPOSED EXTERIOR STEEL & FASTENERS SHALL BE HOT DIP GALVANIZED, UNO. PROVIDE FILL AND VENT HOLES AT ENCLOSED SPACES OF HOLLOW PIECES. SEAL HOLES WATER-TIGHT AFTER GALVANIZING. PROVIDE DRAIN HOLES AS REQUIRED AT SOLID PIECES. HOLE SIZES AND LOCATIONS SHALL NOT DETRIMENTALLY AFFECT THE PIECES STRUCTURAL CAPACITY AND ARE SUBJECT TO THE STRUCTURAL ENGINEERS REVIEW.
5.
EXPOSED STRUCTURAL STEEL MEMBERS AND CONNECTIONS VISIBLE TO THE PUBLIC AND BUILDING OCCUPANTS (OTHER THAN MAINTENANCE AREAS) SHALL MEET THE FOLLOWING CRITERIA: A. FABRICATION, HANDLING, AND SHIPPING SHALL EMPLOY SPECIAL CARE TO ENSURE ACCEPTABLE FINISHED APPEARANCE. B. WELDS SHALL BE GROUND SMOOTH. GROOVE WELDS SHALL BE MADE FLUSH (+ 1/16", -0"). OVERSIZE WELDS AS REQUIRED. C. FIELD-WELDING AIDS AND ERECTION AIDS SHALL BE REMOVED AND STEEL SHALL BE REPAIRED AND GROUND SMOOTH. D. SHOP PIECE MARKS AND MILL MARKS SHALL BE LOCATED SUCH THAT THEY ARE FULLY HIDDEN IN THE FINAL STRUCTURE OR ARE MADE WITH SUCH MEDIA TO PERMIT FULL REMOVAL AFTER ERECTION. E. GRIND EDGES OF SHEARED, PUNCHED OR FLAME CUT STEEL IN AREAS WITHIN REACH TO TOUCH BY THE PUBLIC AND BUILDING OCCUPANTS. F. ALIGN AND ORIENT BOLTED CONNECTIONS TO BE UNIFORM AND CONSISTENT.
MANUFACTURED LUMBER MANUFACTURED LUMBER
S-_061700_N001A 170126. Q2 S-_061700_N001A WOOD I-JOISTS SHALL BE MANUFACTURED BY "RED-BUILT", "I-LEVEL" OR ACCEPTED EQUAL, 170126. Q2 MANUFACTURED IN ACCORDANCE WITH APPROVED SHOP DRAWINGS. THE ENTIRE I-JOIST
1.
SHALL CONFORM TO ICC ACCEPTANCE CRITERIA"I-LEVEL" AC14. 1. ASSEMBLY WOOD I-JOISTS SHALL BE MANUFACTURED BY "RED-BUILT", OR ACCEPTED EQUAL, MANUFACTURED IN ACCORDANCE WITH APPROVED SHOP DRAWINGS. THE ENTIRE I-JOIST 2. PROVIDE SHOP AND INSTALLATION TO INDICATE ASSEMBLY SHALL CONFORM TO ICCDRAWINGS ACCEPTANCE CRITERIATYPES, AC14. SIZE, SPACING, BRIDGING, BLOCKING, CONNECTIONS, ANCHORING AND OTHER PERTINENT DETAILS. 2. PROVIDE SHOP AND INSTALLATION DRAWINGS TO INDICATE TYPES, SIZE, SPACING, BRIDGING, 3. SUBSTITUTIONS MUST MEETANCHORING OR EXCEEDAND MOMENT, AND STIFFNESS BLOCKING, CONNECTIONS, OTHERSHEAR PERTINENT DETAILS. OF THOSE MEMBERS SPECIFIED AT THE SAME DEPTH AND SPACING. 3. SUBSTITUTIONS MUST MEET OR EXCEED MOMENT, SHEAR AND STIFFNESS OF THOSE MEMBERS 4. SPRINKLER LINE ATTACHMENTS CONFORM TO NFPA 13 AND "RED-BUILT", "I-LEVEL" SPECIFIED AT THE SAME DEPTH SHALL AND SPACING. PUBLICATION "GUIDELINES FOR SPRINKLER SYSTEM INSTALLATIONS". ATTACHMENT OF LOADS BE APPROVED PRIOR TO INSTALLATION. DOTO NOT NOTCH OR "RED-BUILT", DRILL THROUGH 4. SHALL SPRINKLER LINE ATTACHMENTS SHALL CONFORM NFPA 13 AND "I-LEVEL" MANUFACTURED MEMBERS.FOR SPRINKLER SYSTEM INSTALLATIONS". ATTACHMENT OF LOADS PUBLICATION "GUIDELINES SHALL BE APPROVED PRIOR TO INSTALLATION. DO NOT NOTCH OR DRILL THROUGH 5. PARALLEL STRAND LUMBER (PSL) BEAMS SHALL BE "PARALLAM" MANUFACTURED BY:"I-LEVEL" OR MANUFACTURED MEMBERS. AN ACCEPTED EQUAL WITH THE FOLLOWING MINIMUM PROPERTIES: = 2,000,000 PSI, Fb LUMBER = 2,900 PSI, Fv BEAMS = 290 PSI 5. E PARALLEL STRAND (PSL) SHALL BE "PARALLAM" MANUFACTURED BY:"I-LEVEL" OR AN ACCEPTED EQUAL WITH THE FOLLOWING MINIMUM PROPERTIES: 6. LAMINATED (LSL) E = 2,000,000STRAND PSI, Fb =LUMBER 2,900 PSI, Fv =BEAMS 290 PSISHALL BE "TIMBERSTRAND" MANUFACTURED BY: "I-LEVEL" OR AN ACCEPTED EQUAL WITH THE FOLLOWING MINIMUM PROPERTIES: 600 2425 = 1,550,000 PSI, Fb =LUMBER 2325 PSI,(LSL) Fv = BEAMS 310 PSI SHALL BE "TIMBERSTRAND" MANUFACTURED BY: 545 6. E LAMINATED STRAND "I-LEVEL" OR AN ACCEPTED EQUAL WITH THE FOLLOWING MINIMUM PROPERTIES: 600 VENEER 2425 7. LAMINATED (LVL) E = 1,550,000 PSI, Fb =LUMBER 2325 PSI, Fv =BEAMS 310 PSISHALL BE "MICROLAM" MANUFACTURED BY:"I-LEVEL" 545 OR AN ACCEPTED EQUAL WITH THE FOLLOWING MINIMUM PROPERTIES: = 1,900,000VENEER PSI, Fb =LUMBER 2,600 PSI, Fv =BEAMS 285 PSISHALL BE "MICROLAM" MANUFACTURED BY:"I-LEVEL" 7. E LAMINATED (LVL) OR AN ACCEPTED EQUAL WITH THE FOLLOWING MINIMUM PROPERTIES: 8. SUBSTITUTIONS NOTED SHALL BE SUBMITTED TO DSA FOR REVIEW AND E = 1,900,000 PSI,FOR Fb =THOSE 2,600 PSI, Fv = ON 285 PLANS PSI APPROVAL. 8. SUBSTITUTIONS FOR THOSE NOTED ON PLANS SHALL BE SUBMITTED TO DSA FOR REVIEW AND APPROVAL.
SHEAR WALL SCHEDULE SHEAR WALL SCHEDULE WALL MARK WALL MARK A
SP EDGE SILL PLATE NAILING THICKNESS SP EDGE SILL PLATE NAILING THICKNESS 8D @ 6" OC 2X
S-_061700_N001A 170126. Q2 S-_061700_N001A STRUCTURAL SILL PLATE ANCHORAGE 170126. Q2 STUDS OR PANEL 15/32" BLKG AT TO WOOD STRUCTURAL STRUCT I AB'S TO CONC SILL PLATENAILS ANCHORAGE PANEL EDGES STUDS OR FRAMING PANEL 15/32" BLKG AT NAILS TO WOOD STRUCT AB'S TO CONC PANEL 2XEDGES 5/8" DIA @ 48" OC 16D @ 6" OC ONE SIDEI FRAMING
B A
8D 8D @ @ 4" 6" OC OC
3X 2X
3X 2X
5/8" 5/8" DIA DIA @ @ 40" 48" OC OC
16D @ 6" OC
ONE ONE SIDE SIDE
C B
8D 8D @ @ 3" 4" OC OC
3X 3X
3X 3X
5/8" 5/8" DIA DIA @ @ 32" 40" OC OC
ONE ONE SIDE SIDE
D C
8D 8D @ @ 2" 3" OC OC
3X 3X
3X 3X
5/8" 5/8" DIA DIA @ @ 24" 32" OC OC
E D
8D 8D @ @ 4" 2" OC OC
3X 3X
3X 3X
5/8" 5/8" DIA DIA @ @ 16" 24" OC OC
FE
8D 8D @ @ 3" 4" OC OC
3X 3X
3X 3X
5/8" 5/8" DIA DIA @ @ 8" 16"OC OC
SEE SECTIONS AND SEE DETAILS SECTIONS AND DETAILS
ONE ONE SIDE SIDE
BOTH ONE SIDES SIDE BOTH SIDES
BOTH SIDES 8DNAILING @ 3" OCOCCURS 5/8"FIELD DIA @NAILING 8" OC SHALL BE 8D @ 12" OC. 3X AT EVERY PANEL 3X 1. F EDGE EDGE. 2. BEOCCURS STEEL WIRE COMMON TYPE OF THE SIZES DENOTED. STRUCTURAL PANEL 1. NAILS EDGE SHALL NAILING AT EVERY PANEL EDGE. FIELD NAILING SHALL DRIVE BE 8D @ 12" OC. NAILS SO THAT THE NAIL HEADS ARE FLUSH WITH THE SURFACE OF THE PANEL. DO NOT STAGGER NAILS AT EACH SIDE OFSIZES JOINTS. 2. OVERDRIVE NAILS SHALLNAILS. BE STEEL WIRE COMMON TYPE OF THE DENOTED. DRIVE STRUCTURAL PANEL NAILS SO THAT THE NAIL HEADS ARE FLUSH WITH THE SURFACE OF THE PANEL. DO NOT 3. STRUCTURAL PANELS SHALL HAVE PANEL OF 32/16. OSB OR 5-PLY/5-LAYER OVERDRIVE NAILS. STAGGER NAILSAAT EACHSPAN SIDE RATING OF JOINTS. PLYWOOD. 3. STRUCTURAL PANELS SHALL HAVE A PANEL SPAN RATING OF 32/16. OSB OR 5-PLY/5-LAYER 4. BLOCK PANEL EDGES WITH FULL STUD WIDTH BLOCKING OF THICKNESS SPECIFIED. PLYWOOD. 5. PLATE NAILING IS WITH TO PARALLEL FRAMING (WHETHER BLKG OR CONT). PROVIDE (2) 4. SILL BLOCK PANEL EDGES FULL STUD WIDTH BELOW BLOCKING OF THICKNESS SPECIFIED. ADDITIONAL NAILS OF SIZE SHOWN TO EA PERPENDICULAR FRAMING BELOW. 5. SILL PLATE NAILING IS TO PARALLEL FRAMING BELOW (WHETHER BLKG OR CONT). PROVIDE (2) 6. PREDRILL NAIL HOLES IF SPLITTING OCCURS. STAGGER NAILING TO PREVENT ADDITIONAL NAILS OF SIZE SHOWN TO EA PERPENDICULAR FRAMING BELOW. SPLITTING. 7. STRUCTURAL OCCUR AT BOTH SIDES OFNAILING WALL, STAGGER PANEL JOINTS AT 6. WHERE PREDRILL NAIL HOLESPANELS IF SPLITTING OCCURS. STAGGER TO PREVENT SPLITTING. EACH FACE SO THEY DO NOT FALL ON THE SAME STUD OR BLOCKING. 7. WHERE STRUCTURAL PANELS OCCUR AT BOTH SIDES OF WALL, STAGGER PANEL JOINTS AT 8. PROVIDE STRUCTURAL FULL ANDSTUD HEIGHT ALL EXTERIOR WALLS AND AT EACH FACE SO THEY DOPANELS NOT FALL ONLENGTH THE SAME OR OF BLOCKING. INTERIOR WALLS AS SHOWN ON SECTIONS AND DETAILS. MINIMUM STRUCTURAL PANEL NAILING BE STRUCTURAL TYPE UNO. SEE PLANS HEAVIER NAILINGOF LOCATIONS NOTED BY WALL 8. SHALL PROVIDE PANELS FULL FOR LENGTH AND HEIGHT ALL EXTERIOR WALLS ANDMARKS AT THUS: INTERIOR WALLSAAS SHOWN ON SECTIONS AND DETAILS. MINIMUM STRUCTURAL PANEL NAILING SHALL BE TYPE & DETAILS UNO. SEE PLANS FOR HEAVIER NAILING LOCATIONS MARKS SEE SECTIONS WHERENOTED EXTENTBY ISWALL INDICATED, A THUS: FOR SIDE OF WALL REMAINDER OF WALL LINE
REQUIRING STRUCTURAL SEE SECTIONS & DETAILS PANELS FOR SIDE OF WALL REQUIRING STRUCTURAL PANELS
X WALL X LINE WALL LINE
REQUIRES TYPE IS UNO WHERE EXTENT A INDICATED, REMAINDER OF WALL LINE REQUIRES TYPE A UNO IF NO EXTENT IS INDICATED THE ENTIRE WALL LINE REQUIRES THEISTYPE NOTED IF NO EXTENT INDICATED THE ENTIRE WALL LINE REQUIRES THE TYPE NOTED
STEEL MATERIALS SHALL CONFORM TO THE FOLLOWING, UNO: STEEL PRODUCT ASTM SPECIFICATION, UNO COMMENTS W & WT SHAPES A992, GRADE 50 Fy = 50ksi HP SHAPES A572, GRADE 50 Fy = 50ksi M, MT, S & ST SHAPES A36 Fy = 36ksi CHANNELS (C & MC) A36 Fy = 36ksi ANGLES A36 Fy = 36ksi PLATES & BARS A36,TYP, UNO Fy = 36ksi A572, GRADE 50 Fy = 50ksi RODS, PLAIN & ALL-THREADED A36 Fy = 36ksi RAISED-PATTERN FLOOR PLATE A786, MEETING ASTM A36 Fy = 36ksi PIPES A53, GRADE B Fy = 35ksi ROUND HSS A500, GRADE B Fy = 42ksi RECTANGULAR & SQUARE HSS A500, GRADE B Fy = 46ksi HIGH-STRENGTH BOLTS A325, HEAVY HEX, TYPE I Fy = 92ksi TWIST-OFF-TYPE TENSION-CONTROL BOLTS F1852, TYPE I BOLTS A307, GRADE A, HEX Fy = 60ksi WASHERS F844 PLATE WASHERS A36 Fy = 36ksi HARDENED WASHERS F436, TYPE I DIRECT-TENSION INDICATOR WASHERS F959, TYPE 325 NUTS FOR HS & TENSION CONTROL BOLTS A563, GRADE C, HEAVY HEX GRADE DH IF GALVANIZED NUTS FOR BOLTS & RODS A563, HEAVY HEX, GRADE A TYP, UNO GRADE DH IF GALVANIZED GRADE DH W/ F1554 GRADE 105 BOLTS ANCHOR BOLTS & RODS F1554, CLASS 2A, S3 (HEADED OR THREADED & NUTTED) GRADE 36 TYP, UNO Fy = 36ksi GRADE 55, S1 & S4 Fy = 55ksi GRADE 105, S4 & S5 Fy = 105ksi WELDED HEADED STUDS, SHEAR STUDS, A108, GRADES 1010 - 1020 & WELDED THREADED STUDS DEFORMED BAR ANCHORS A496 Fy = 75ksi WELD FILLER METAL AWS D1.1 Fy = 70ksi TURNBUCKLES F1145 & AISI C-1035 CLEVISES, CLEVIS PINS, COTTER PINS AISI C-1035 EYENUTS & EYEBOLTS AISI C-1030 SLEEVE NUTS AISI C-1018, GRADE 2 RECESSED NUTS & PINS A36 COUPLING NUTS AISI 12L14 CARBON STEEL EXPOSED INTERIOR STEEL SHALL RECEIVE ONE COAT OF PRIMER PAINT, UNO. DO NOT PAINT SURFACES IN DIRECT CONTACT WITH CONCRETE OR MASONRY, WHERE FIELD WELDING IS REQUIRED, WHERE FIRE-PROOFING IS REQUIRED OR CONTACT SURFACES OF STEEL-TO-STEEL, AND DECK-TO-STEEL CONNECTIONS. CONCEALED STEEL DOES NOT REQUIRE PAINT, UNO.
6.
PROVIDE CONCRETE / MASONRY COVER AT STEEL BELOW GRADE. STEEL EMBEDDED IN CONCRETE CAST AGAINST EARTH SHALL HAVE 3" MIN COVER. STEEL EMBEDDED IN FORMED CONCRETE OR MASONRY SHALL HAVE 2" MIN COVER.
7.
WELDING MATERIALS & PROCEDURES SHALL CONFORM WITH AWS D1.1. AND AWS D1.8 WHERE APPLICABLE.
8.
MINIMUM SIZE OF FILLET WELDS: 1/8" FOR MATERIAL 1/8" TO 1/4" THICK, 3/16" FOR MATERIAL OVER 1/4" TO 1/2" THICK, 1/4" FOR MATERIAL OVER 1/2" TO 3/4" THICK, AND 5/16" FOR MATERIAL OVER 3/4" THICK. MATERIAL THICKNESS IS FOR THINNER PART JOINED. SINGLE PASS WELDS MUST BE USED FOR SIZES SHOWN. SIZE OF WELD IS LEG DIMENSION OF FILLET. MINIMUM EFFECTIVE LENGTH OF FILLET WELDS SHALL BE NOT LESS THAN FOUR TIMES THE FILLET SIZE. MINIMUM EFFECTIVE LENGTH OF INTERMITTENT FILLET WELDS SHALL BE 1 1/2".
9.
GROOVE WELDS SHALL BE COMPLETE JOINT PENETRATION WELDS, UNO. GROOVE WELDS SHALL BE TERMINATED AT THE END OF JOINTS IN A MANNER THAT WILL ENSURE SOUND WELDS. USE WELD TABS AND BACKING BARS ALIGNED TO PROVIDE AN EXTENSION OF THE JOINT PREPARATION. REMOVE EXTENSIONS UPON COMPLETION & COOLING OF THE WELD. GRIND ENDS OF THE WELD SMOOTH AND FLUSH WITH THE EDGES OF THE ABUTTING PARTS.
APP. 02-117123
INC:
REVIEWED FOR SS
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
SEAL FESSIONA PRO L ED RRY J. VOLKE E
T
T
E
No. S3737
A RU C T UR O F OF I CAL
05/15/2019 PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
10. WHERE "ALL AROUND" FILLET WELDS ARE INDICATED AT CONCEALED/NON-EXPOSED SQUARE OR RECTANGULAR HSS CONNECTIONS TO PLATES, FILLET WELDS ARE NOT REQUIRED AT RADIUSED CORNERS , UNO. 11. BOLTS FOR STEEL-TO-STEEL CONNECTIONS SHALL BE PLACED IN STANDARD SIZE HOLES, TYP UNO. BOLTS FOR STEEL-TO-CONCRETE/MASONRY CONNECTIONS SHALL BE PLACED IN ANCHOR ROD HOLES, TYP UNO. HOLE DIMENSIONS SHALL BE AS SHOWN IN TABLES BELOW. USE STANDARD AISC PITCH & GAGE FOR BOLTED CONNECTIONS, UNO.
ISSUED
MARK
12. BOLTS AND RODS SHALL BE CUT-THREAD TYPE WITH FULL DIAMETER BODY STYLE MEETING REQUIREMENTS OF ASME B18.2.1. THE BODY DIAMETER SHALL NOT BE LESS THAN THE MINIMUM MAJOR DIAMETER WHEN THREADS ARE CUT. REDUCED DIAMETER BODY STYLE ROLLED THREAD BOLTS OR RODS ARE NOT PERMITTED.
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
13. STEEL-TO-STEEL BOLTED CONNECTIONS SHALL BE ASSEMBLED UTILIZING HIGH-STRENGTH OR TWIST-OFF-TYPE TENSION CONTROL BOLT ASSEMBLIES, UNO. A BOLT ASSEMBLY CONSISTS OF A MINIMUM OF A BOLT, A HARDENED WASHER AND A NUT. THE HARDENED WASHER SHALL BE PLACED UNDER THE TURNED ELEMENT OF THE BOLT ASSEMBLY. ALSO PROVIDE A HARDENED WASHER AT BOLT HEADS OR NUTS BEARING ON SHORT SLOTTED HOLES. ALSO PROVIDE A 5/16" MINIMUM THICKNESS PLATE WASHER OR CONTINUOUS BAR WITH STD HOLES AT BOLT HEADS OR NUTS BEARING ON LONG SLOTTED HOLES. 14. IF DIRECT-TENSION-INDICATOR (DTI) WASHERS ARE USED, A "DTI" BOLT ASSEMBLY CONSISTS OF A MINIMUM OF A HIGH STRENGTH BOLT, A HARDENED WASHER, A "DTI" WASHER AND A NUT. INSTALL THE "DTI" WITH THE BUMPS FACING THE UNDERSIDE OF THE BOLT HEAD OR NUT. THE HARDENED WASHER SHALL BE PLACED UNDER THE TURNED ELEMENT OF THE "DTI" BOLT ASSEMBLY. IF THE "DTI" IS PLACED UNDER THE TURNED ELEMENT OF THE BOLT ASSEMBLY, PLACE THE HARDENED WASHER BETWEEN THE "DTI" AND THE TURNED ELEMENT. ALSO PROVIDE A HARDENED WASHER AT "DTI"s, BOLT HEADS OR NUTS BEARING ON OVERSIZE OR SHORT SLOTTED HOLES. ALSO PROVIDE A 5/16" MINIMUM THICKNESS PLATE WASHER OR CONTINUOUS BAR W/ STD HOLES AT "DTI"s, BOLT HEADS OR NUTS BEARING ON LONG SLOTTED HOLES. 15. BOLT HEADS, NUTS OR "DTI"S OF BOLTED STEEL-TO-STEEL AND STEEL-TO-CONCRETE/ MASONRY CONNECTIONS BEARING ON SLOPING SURFACES SHALL USE A BEVELED HARDENED WASHER IN THE BOLT ASSEMBLY AT THAT SURFACE.
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
16. HIGH-STRENGTH BOLT ASSEMBLIES SHALL BE PRE-TENSIONED. FAYING SURFACES OF HIGHSTRENGTH BOLT ASSEMBLIES SHALL BE PREPARED AS REQUIRED FOR CLASS A OR BETTER SLIP-CRITICAL JOINTS. AGENCY
17. WOOD MEMBERS IN PARALLEL CONTACT WITH STEEL SHALL BE BOLTED WITH 5/8" DIA WELDED THREADED STUDS STAGGERED AT 2'-8" OC MAX, TYP. PROVIDE ADDITIONAL STUDS @ 5" MIN AND 9" MAX FROM ENDS, SPLICES & HOLES OR NOTCHES GREATER THAN 1/3 THE WOOD MEMBER WIDTH.
HOLE DIMENSIONS AT STEEL TO STEEL CONNECTIONS BOLT DIA, D
STANDARD (DIA)
OVERSIZED (DIA)
SHORT SLOT LONG SLOT (WIDTH X LENGTH) (WIDTH X LENGTH)
1/2"
9/16"
5/8"
9/16" x 11/16"
9/16" x 1 1/4"
5/8"
11/16"
13/16"
11/16" x 7/8"
11/16" x 1 9/16"
3/4"
13/16"
15/16"
13/16" x 1"
13/16" x 1 7/8"
7/8"
15/16"
1 1/16"
15/16" x 1 1/8"
15/16" x 2 3/16"
1"
1 1/16"
1 1/4"
1 1/16" x 1 5/16"
1 1/16" x 2 1/2"
1 1/8" & GREATER
D + 1/16"
D + 5/16"
(D + 1/16")x(D + 3/8") (D + 1/16")x(2.5 x D)
HOLE DIMENSIONS AT STEEL TO CONCRETE / MASONRY CONNECTIONS BOLT DIA
ANCHOR ROD HOLE DIA
BOLT DIA
ANCHOR ROD HOLE DIA
1/2"
15/16"
1 1/4"
2 1/16"
24. BLOCKING SHOWN ON THE STRUCTURAL DRAWINGS IS FOR STRUCTURAL PURPOSES ONLY. SEE ALL OTHER DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL BLOCKING REQUIRED FOR FINISHES, FIRE AND DRAFT STOPS, THE ATTACHMENT OF NONSTRUCTURAL ITEMS, OR ANY OTHER REASON.
5/8"
1 1/16"
1 1/2"
2 5/16"
3/4"
1 5/16"
1 3/4"
2 3/4"
7/8"
1 9/16"
2"
3 1/4"
25. FRAMING MEMBERS (INCLUDING BLOCKING) SHALL BE CUT TO PROVIDE TIGHT FIT AND FULL BEARING AT ALL CONTACT SURFACES. CUT MEMBERS TO MATCH SIZE, DEPTH, SLOPE OR ANGLE SHOWN WHERE SHAPED SURFACES OR NOTCHES ARE INDICATED. DO NOT OVERCUT.
1"
1 13/16"
2 1/2"
3 3/4"
PLATE WASHER SCHEDULE (WITH STANDARD HOLE AT CENTER)
WASHER SCHEDULE FOR BOLTS & LAG SCREWS IN WOOD
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
LOCATION
JOISTS, RAFTERS, TIES, STRUTS, BRACES LAPS TO SIDES OF OTHER MEMBERS FOR EACH 2" OF THE DEEPEST MEMBER DEPTH
S-_061800_N001A 170126. Q2
A
NAILS SHALL CONFORM TO THE REQUIREMENTS OF ASTM F1667 INCLUDING THE NAIL BENDING YIELD STRENGTHS OF SUPPLEMENTARY REQUIREMENT S1. NAILS SHALL BE STEEL WIRE COMMON NAILS UNO, OF THE SIZE INDICATED. INSTALL NAILS SUCH THAT END DISTANCES, EDGE DISTANCES AND SPACINGS ARE SUFFICIENT TO PREVENT SPLITTING OF THE WOOD. PREDRILL NAIL HOLES IN WOOD MEMBERS EQUAL TO 75% OF NAIL DIAMETER WHEN NECESSARY TO PREVENT SPLITTING.
1.
NAILING SCHEDULE (UNO) CONNECTION / MEMBERS
GLUED-LAMINATED TIMBER
S
C
WOOD STRUCTURAL PANELS SHALL CONFORM TO THE REQUIREMENTS FOR THEIR TYPE. PLYWOOD PANELS SHALL CONFORM TO THE REQUIREMENTS OF DOC PS-1. WOOD-BASED STRUCTURAL-USE PANELS SHALL CONFORM TO THE REQUIREMENTS OF DOC PS-2. EACH PANEL SHALL BE IDENTIFIED FOR GRADE AND ADHESIVE BOND CLASSIFICATION TYPE BY THE TRADEMARKS OF AN APPROVED TESTING AND GRADING AGENCY. EACH PANEL SHALL BEAR A "SIZED FOR SPACING" MARK. PANEL SPAN INDEX AND THICKNESS SHALL BE AS INDICATED FOR THE INSTALLED LOCATION.
S-_061100_N004A 170126. Q2
ST
9.
SAWN LUMBER FRAMING SHALL BE INDENTIFIED BY THE GRADE MARK OF AN APPROVED LUMBER GRADING OR INSPECTION AGENCY IN CONFORMANCE WITH DOC PS-20. EACH PIECE OF FRAMING SHALL BE IDENTIFIED BY THE GRADE MARK SIGNIFYING CONFORMANCE WITH THE SPECIES, GRADE, SIZE AND SEASONING PROVISIONS. FRAMING LUMBER SHALL HAVE A MAXIMUM MOISTURE CONTENT OF 19% WHEN INSTALLED. FRAMING 4X AND LARGER SHALL BE FREE OF HEART CENTER. SPECIES SHALL BE DOUGLAS FIR-LARCH WITH THE FOLLOWING MINIMUM GRADES: 2X & 3X FRAMING NO. 2 4X FRAMING NO. 1 6X AND LARGER FRAMING SELECT STRUCTURAL
CARPENTRY NAILING SCHEDULE
5
EER GIN EN R
8.
S-_061100_N003A 170125. Q2
4
L N IA
ROUGH CARPENTRY
3
R
2
REGIST ER K
2"
1
BOLT DIA
STEEL PLATE SIZE
BOLT DIA
STEEL PLATE SIZE
BOLT OR LAG DIA
STEEL PLATE WASHER SIZE & HOLE DIA AT CL
MALLEABLE IRON WASHER (ASTM A47)
1/2"
3/16" x 1 1/2" SQ
1 1/4"
1/2" x 3 1/2" SQ
1/2"
.229" x 3" SQ W/ 9/16" DIA HOLE
1/4" x 2 1/2" DIA
5/8"
1 /4" x 1 3/4" SQ
1 1/2"
1/2" x 4" SQ
5/8"
.229" x 3" SQ W/ 11/16" DIA HOLE
5/16" x 2 3/4" DIA
3/4"
1 /4" x 2" SQ
1 3/4"
5/8" x 4 1/2" SQ
3/4"
.229" x 3" SQ W/ 13/16" DIA HOLE
7/16" x 3" DIA
7/8"
5/16" x 2 1/2" SQ
2"
3/4" x 5" SQ
7/8"
5/16" x 3" SQ W/ 15/16" DIA HOLE
7/16" x 3 1/2" DIA
1"
3/8" x 3" SQ
2 1/2"
7/8" x 6" SQ
1"
3/8" x 3 1/2" SQ W/ 1 1/16" DIA HOLE
1/2" x 4" DIA
TITLE
TYPICAL NOTES
SHEET
S-013
017294 ?00.00.00? LIONAKIS 2017
S-_056000_N005A S-_056000_N005A 170127. 170127. Q2 Q2
1"
1. 1. REFERENCES REFERENCES TO TO "EPOXY" "EPOXY" OR OR "CHEMICAL" "CHEMICAL" ANCHORS ANCHORS EMBEDDED EMBEDDED IN IN CONCRETE CONCRETE SHALL SHALL REFER REFER TO TO THESE THESE NOTES. NOTES.
SCREW ANCHORS IN CONCRETE
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
4. 4. EMBEDMENT EMBEDMENT DEPTHS DEPTHS SHALL SHALL BE BE 88 TIMES TIMES THE THE NOMINAL NOMINAL DIAMETER DIAMETER OF OF ANCHOR, ANCHOR, UNO. UNO. 5. 5. CONCRETE CONCRETE SHALL SHALL MEET MEET THE THE SPECIFIED SPECIFIED DESIGN DESIGN STRENGTH STRENGTH PRIOR PRIOR TO TO INSTALLATION, INSTALLATION, AND AND SHALL SHALL HAVE HAVE A A MINIMUM MINIMUM AGE AGE OF OF 21 21 DAYS, DAYS, UNO. UNO. 6. 6. TEST TEST LOADS LOADS SHALL SHALL BE BE AS AS INDICATED INDICATED IN IN DRAWINGS. DRAWINGS. IF IF NO NO TEST TEST LOAD LOAD IS IS SPECIFIED, SPECIFIED, TEST TEST LOAD LOAD SHALL SHALL BE BE 1000 1000 LBS. LBS.
S-_056000_N004A S-_056000_N004A 170127. 170127. Q2 Q2
1. 1. EMBEDMENT EMBEDMENT SHALL SHALL BE BE AS AS INDICATED INDICATED IN IN THE THE TABLE TABLE BELOW, BELOW, TYP TYP UNO. UNO. ALL ALL EMBEDMENTS EMBEDMENTS SPECIFIED SPECIFIED ARE ARE NOMINAL NOMINAL EMBEDMENT EMBEDMENT DEPTHS DEPTHS REQUIRED REQUIRED
2. 2. ACCEPTABLE ACCEPTABLE ADHESIVE ADHESIVE PRODUCTS PRODUCTS ARE: ARE: •• "HILTI" HIT-RE 500 V3 (ICC "HILTI" HIT-RE 500 V3 (ICC ESR-3814) ESR-3814) •• "HILTI" "HILTI" HIT-HY-200 HIT-HY-200 (ICC (ICC ESR-3187) ESR-3187) •• "SIMPSON" "SIMPSON" SET-XP SET-XP (ICC (ICC ESR-2508) ESR-2508) •• "SIMPSON" "SIMPSON" AT-XP AT-XP (IAPMO (IAPMO ER-263) ER-263) •• "DEWALT" "DEWALT" PURE PURE 100+ 100+ (ICC (ICC ESR-3298) ESR-3298) •• "DEWALT" "DEWALT" AC200+ AC200+ GOLD GOLD (ICC (ICC ER-4027) ER-4027) 3. 3. THREADED THREADED ROD ROD AND AND REBAR REBAR USED USED W/ W/ ADHESIVE ADHESIVE ANCHORS ANCHORS SHALL SHALL MEET MEET THE THE REQUIREMENTS REQUIREMENTS OF OF THE THE EVALUATION EVALUATION AGENCY AGENCY REPORT. REPORT.
4
ANCHOR 3/8" 1/2" 1/4" ANCHOR DIA DIA 1/4" 3/8" 1/2" STD STD EMBED, EMBED, 3" 11 5/8" 5/8" 22 1/8" 1/8" 3" Hnom Hnom TYP TYP UNO UNO MIN MIN CONC CONC ** 33 1/4" 44 3/4" 1/4" 4" 3/4" 4" THICKNESS, THICKNESS, TT MAX MAX INSTALLATION INSTALLATION 18 40 45 18 40 45 TORQUE TORQUE (LB-FT) (LB-FT) TORQUE TORQUE TEST TEST 20 99 23 20 23 LOAD LOAD (LB-FT) (LB-FT) **
5/8" 5/8"
3/4" 3/4"
UNDERSIDE OF CONC OVER STEEL DECK LOWER FLUTE UPPER FLUTE 1/4"
3/8"
1/2"
1/4"
3/8"
1/2"
3"
1 5/8"
1 5/8"
2 1/4"
5" 5"
66 1/4" 1/4" 1 5/8"
2 1/2"
7" 7"
88 1/4" 1/4"
SEE DIAGRAM BELOW T = 3 1/4" MIN, C = 1 1/4" MIN
85 85
115 115
18
40
45
18
40
45
43 43
58 58
9
20
23
9
20
23
T= T= 22 1/2" 1/2" AT AT TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK
GENERAL GENERAL CONCRETE CONCRETE & & TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STL STL DECK DECK
ANCHOR ANCHOR DIA DIA STD STD EMBED, EMBED, Hnom Hnom TYP TYP UNO UNO MIN MIN CONC CONC THICKNESS, THICKNESS, TT
MAX MAX INSTALLATION INSTALLATION TORQUE TORQUE (LB-FT) (LB-FT) TORQUE TORQUE TEST TEST LOAD LOAD (LB-FT) (LB-FT)
**
1/4" 1/4"
1/2" 11 5/8" 5/8" 22 1/2"
33 1/4" 1/4"
5/8" 5/8"
3/4" 3/4"
1/4"
33 1/4" 1/4"
4" 4"
55 1/2" 1/2"
1 5/8"
** 4" 4"
5" 5"
6" 6"
3/8"
1/2"
2 1/2" 3 1/2"
1/4"
3/8"
1/2"
1 5/8"
1 7/8"
2"
SEE DIAGRAM BELOW T = 1 1/2" MIN IN LOWER FLUTE T = 3 1/4" MIN IN UPPER FLUTE C = 3/4" MIN
88 3/4" 3/4"
24 24
50 50
65 65
100 100
150 150
24
50
65
24
50
65
12 12
25 25
33 33
50 50
75 75
12
25
33
12
25
33
T= T= 33 1/4" 1/4" AT AT TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK
"DEWALT" "DEWALT" SCREWBOLT+ SCREWBOLT+ INSTALLED INSTALLED IN IN NORMAL NORMAL WEIGHT WEIGHT OR OR LIGHT LIGHT WEIGHT WEIGHT CONCRETE CONCRETE (f'c (f'c == 3000 3000 PSI PSI MIN) MIN) (ICC REPORT ESR 3889) (ICC REPORT ESR 3889) GENERAL GENERAL CONCRETE CONCRETE & & TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STL STL DECK DECK
22 5/16" 5/16" ** ** 33 5/8" 5/8"
5/8" 5/8"
3/4" 3/4"
44 1/2" 1/2"
55 5/8" 5/8"
** 4" 4"
** 6" 6"
6" 6"
8" 8"
25 25
40 40
60 60
110 110
3/8"
1/2"
5/8"
2 3/8" 3 5/8" 2 3/8" SEE DIAGRAM BELOW T = 1 1/2" MIN, C = 5/8" MIN 40
25
60
ANCHOR ANCHOR DIA DIA STD STD EMBED, EMBED, Hnom Hnom TYP TYP UNO UNO MIN MIN CONC CONC THICKNESS, THICKNESS, TT TORQUE TORQUE TEST TEST LOAD LOAD (LB-FT) (LB-FT)
UNDERSIDE OF CONC O/ STEEL DECK
1/4" 1/4"
3/8" 3/8"
1/2" 1/2"
5/8" 5/8"
3/4" 3/4"
3/8"
1/2"
5/8"
11 3/4" 3/4"
11 7/8" 7/8"
**3 **3 7/8" 7/8"
33 3/8" 3/8"
44 1/8" 1/8"
2"
2 3/4"
3 3/8"
33 1/4" 1/4"
33 1/4" 1/4"
** 44 1/2" 1/2"
55 1/2" 1/2"
66 3/4" 3/4"
44
30 30
60 60
90 90
150 150
SEE DIAGRAM BELOW T = 1 1/2" MIN, C = 1/2" MIN
30
UNDERSIDE UNDERSIDE OF OF CONC CONC OVER OVER STEEL STEEL DECK DECK LOWER FLUTE UPPER FLUTE
1/2" 1/2"
5/8" 5/8"
3/4" 3/4"
3/8"
1/2"
5/8"
3/8"
1/2"
11 5/8" 5/8"
2" 2"
3" 3"
4" 4"
44 1/4" 1/4"
2"
3"
4"
2 1/8"
2 1/2"
33 1/4" 1/4" 33 1/2" 1/2" 55 1/4" 1/4"
6" 6"
6" 6"
25 25
45 45
60 60
70 70
25
45
60
25
45
18 18
30 30
75 75
100 100
18
30
75
18
30
SEE DIAGRAM BELOW T = 1 1/2" MIN IN LOWER FLUTE T = 3 1/4" MIN IN UPPER FLUTE C = 3/4" MIN
90
** TT == 33 1/4" 1/4" MIN MIN AT AT TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK ** ** STD STD EMBED EMBED == 22 3/4" 3/4" AT AT TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK
"DEWALT" "DEWALT" POWER-STUD+ POWER-STUD+ SD2 SD2 INSTALLED INSTALLED IN IN NORMAL WEIGHT OR LIGHT WEIGHT CONCRETE (f'c = 3000 NORMAL WEIGHT OR LIGHT WEIGHT CONCRETE (f'c = 3000 PSI PSI MIN) MIN) (ICC (ICC REPORT REPORT ESR ESR 2502) 2502)
ANCHOR ANCHOR DIA DIA STD STD EMBED, EMBED, Hnom Hnom TYP TYP UNO UNO MIN CONC MIN CONC THICKNESS, THICKNESS, TT TORQUE TORQUE TEST TEST LOAD LOAD (LB-FT) (LB-FT)
3/8" 3/8"
1/2" 1/2"
**2 **2 3/8" 3/8" **3 **3 3/4" 3/4"
UNDERSIDE OF CONC O/ STEEL DECK
5/8" 5/8"
3/4" 3/4"
3/8"
1/2"
5/8"
3/4"
44 7/8" 7/8"
55 3/4" 3/4"
2 3/8"
2 1/2"
3 5/8"
4 1/2"
** 4" 4"
*5 *5 3/4" 3/4"
66 1/2" 1/2"
10" 10"
20 20
40 40
60 60
110 110
** TT == 22 1/2" 1/2" MIN MIN AT AT TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK ** ** STD STD EMBED EMBED == 22 1/2" 1/2" AT AT TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK
T= T= 22 1/2" 1/2" AT AT TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK
SEE DIAGRAM BELOW T = 3 1/4" MIN, C = 3/4" MIN
25
40
60
REVIEWED FOR SS
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
2. 2. INSTALLATION INSTALLATION OF OF ADHESIVE ADHESIVE ANCHORS ANCHORS INSTALLED INSTALLED IN IN HORIZONTAL HORIZONTAL OR OR UPWARDLY UPWARDLY INCLINED INCLINED ORIENTATIONS ORIENTATIONS RESISTING RESISTING SUSTAINED SUSTAINED TENSION TENSION LOADS LOADS (AS (AS SPECIFICALLY SPECIFICALLY NOTED NOTED ON ON DETAILS) DETAILS) SHALL SHALL BE BE PERFORMED PERFORMED BY BY PERSONNEL PERSONNEL CERTIFIED CERTIFIED BY BY AN AN APPLICABLE APPLICABLE CERTIFICATION CERTIFICATION PROGRAM. PROGRAM. CERTIFICATION CERTIFICATION SHALL SHALL INCLUDE INCLUDE A A WRITTEN WRITTEN TEST TEST AND AND PERFORMANCE PERFORMANCE TEST TEST IN IN ACCORDANCE ACCORDANCE WITH WITH THE THE ACI/CRSI ACI/CRSI ADHESIVE ADHESIVE ANCHOR ANCHOR INSTALLER INSTALLER CERTIFICATION CERTIFICATION PROGRAM, PROGRAM, OR OR EQUIVALENT. EQUIVALENT. CERTIFICATION CERTIFICATION PROGRAM PROGRAM SHALL SHALL BE BE SUBMITTED SUBMITTED TO TO STRUCTURAL STRUCTURAL ENGINEER ENGINEER FOR FOR REVIEW REVIEW AND AND APPROVAL APPROVAL PRIOR PRIOR TO TO INSTALLATION. INSTALLATION.
110
4. 4. ANCHOR ANCHOR INSTALLATION INSTALLATION & & CURE CURE TEMPERATURES TEMPERATURES SHALL SHALL FOLLOW FOLLOW EVALUATION EVALUATION AGENCY AGENCY REPORT REPORT & & MANUFACTURER'S MANUFACTURER'S PUBLISHED PUBLISHED INSTALLATION INSTALLATION INSTRUCTIONS. INSTRUCTIONS. 5. 5. WHEN WHEN INSTALLING INSTALLING ANCHORS ANCHORS IN IN CONCRETE CONCRETE OR OR MASONRY, MASONRY, DO DO NOT NOT DAMAGE DAMAGE REINFORCING REINFORCING (REBAR (REBAR AND/OR AND/OR PRE/POST PRE/POST TENSIONED TENSIONED STRANDS). STRANDS). LOCATE LOCATE ALL ALL REINFORCING REINFORCING AT AT AFFECTED AFFECTED AREAS AREAS USING USING NON-DESTRUCTIVE NON-DESTRUCTIVE MEANS MEANS PRIOR PRIOR TO TO INSTALLING INSTALLING ANCHORS. ANCHORS. MAINTAIN MAINTAIN A A MINIMUM MINIMUM CLEARANCE CLEARANCE OF OF TWO TWO INCHES INCHES BETWEEN BETWEEN THE THE REINFORCEMENT REINFORCEMENT AND AND THE THE ANCHOR. ANCHOR.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
INSPECTION INSPECTION 1. 1. PROVIDE PROVIDE SPECIAL SPECIAL INSPECTION INSPECTION AS AS REQUIRED REQUIRED BY BY THE THE EVALUATION EVALUATION AGENCY AGENCY REPORT REPORT AND AND ENFORCEMENT ENFORCEMENT AGENCY. AGENCY. WHERE WHERE EVALUATION EVALUATION AGENCY AGENCY REPORT REPORT PERMITS PERMITS EITHER EITHER PERIODIC PERIODIC OR OR CONTINUOUS CONTINUOUS INSPECTION, INSPECTION, USE USE CONTINUOUS. CONTINUOUS. 2. 2. ADHESIVE ADHESIVE ANCHORS ANCHORS INSTALLED INSTALLED IN IN HORIZONTAL HORIZONTAL OR OR UPWARDLY UPWARDLY INCLINED INCLINED ORIENTATIONS ORIENTATIONS RESISTING RESISTING SUSTAINED SUSTAINED TENSION TENSION LOADS LOADS (AS (AS SPECIFICALLY SPECIFICALLY NOTED NOTED ON ON DETAILS) DETAILS) SHALL SHALL BE BE CONTINUOUSLY CONTINUOUSLY INSPECTED INSPECTED BY BY AN AN INSPECTOR INSPECTOR SPECIALLY SPECIALLY APPROVED APPROVED FOR FOR THAT THAT PURPOSE PURPOSE BY BY THE THE ENFORCEMENT ENFORCEMENT AGENCY. AGENCY. TESTING TESTING 1. 1. TEST TEST ANCHORS ANCHORS IN IN ACCORDANCE ACCORDANCE WITH WITH THE THE EVALUATION EVALUATION AGENCY AGENCY REPORT REPORT AND AND ENFORCEMENT AGENCY REQUIREMENTS FOR THE SPECIFIC ANCHOR ENFORCEMENT AGENCY REQUIREMENTS FOR THE SPECIFIC ANCHOR AND AND IN IN ACCORDANCE ACCORDANCE WITH WITH THE THE FREQUENCIES FREQUENCIES AND AND TEST TEST METHODS METHODS LISTED LISTED BELOW. BELOW. 2. 2. TESTS TESTS SHALL SHALL BE BE PERFORMED PERFORMED IN IN THE THE PRESENCE PRESENCE OF OF THE THE PROJECT PROJECT INSPECTOR INSPECTOR AND AND A A REPORT REPORT OF OF THE THE TEST TEST RESULTS RESULTS SHALL SHALL BE BE SUBMITTED SUBMITTED TO TO THE THE ENFORCEMENT ENFORCEMENT AGENCY AGENCY AND AND STRUCTURAL STRUCTURAL ENGINEER. ENGINEER. 3. 3. REACTION REACTION LOADS LOADS FROM FROM TEST TEST FIXTURE(S) FIXTURE(S) MAY MAY BE BE APPLIED APPLIED CLOSE CLOSE TO TO THE THE ANCHOR ANCHOR BEING BEING TESTED, TESTED, PROVIDED PROVIDED THE THE ANCHOR ANCHOR IS IS NOT NOT RESTRAINED RESTRAINED BY BY THE THE FIXTURE(S) FIXTURE(S) FROM FROM WITHDRAWING. WITHDRAWING. 4. 4. TEST TEST METHOD METHOD SHALL SHALL BE BE AS AS NOTED NOTED FOR FOR SPECIFIC SPECIFIC ANCHOR ANCHOR TYPES TYPES AND AND THE THE FOLLOWING FOLLOWING CRITERIA CRITERIA APPLY APPLY FOR FOR THE THE ACCEPTANCE ACCEPTANCE OF OF INSTALLED INSTALLED ANCHORS ANCHORS :: •• HYDRAULIC HYDRAULIC RAM RAM METHOD METHOD (TENSION (TENSION TESTING): TESTING): THE THE ANCHOR ANCHOR SHALL SHALL MAINTAIN MAINTAIN THE THE TEST TEST LOAD LOAD FOR FOR 15 15 SECONDS SECONDS AND AND SHALL SHALL HAVE HAVE NO NO OBSERVABLE OBSERVABLE MOVEMENT MOVEMENT AT AT THE THE APPLICABLE APPLICABLE TEST TEST LOAD. LOAD. A A PRACTICAL PRACTICAL WAY WAY TO TO DETERMINE DETERMINE OBSERVABLE OBSERVABLE MOVEMENT MOVEMENT IS IS THAT THAT THE THE WASHER WASHER UNDER UNDER THE THE NUT NUT BECOMES BECOMES LOOSE. LOOSE. •• TORQUE TORQUE WRENCH WRENCH METHOD METHOD (TORQUE (TORQUE TESTING): TESTING): •• THE THE APPLICABLE APPLICABLE TEST TEST TORQUE TORQUE MUST MUST BE BE REACHED REACHED WITHIN WITHIN THE THE FOLLOWING FOLLOWING LIMITS: LIMITS: •• ONE-HALF ONE-HALF (1/2) (1/2) TURN TURN OF OF THE THE NUT, NUT, TYP TYP UNO. UNO. •• ONE-QUARTER ONE-QUARTER (1/4) (1/4) TURN TURN OF OF THE THE NUT NUT FOR FOR THE THE 3/8" 3/8" SLEEVE SLEEVE ANCHOR ANCHOR ONLY. ONLY. •• ONE-QUARTER ONE-QUARTER (1/4) (1/4) TURN TURN OF OF THE THE SCREW SCREW AFTER AFTER INITIAL INITIAL SEATING SEATING OF OF THE THE SCREW SCREW HEAD HEAD FOR FOR SCREW SCREW ANCHORS. ANCHORS.
TT
6. 6. IF IF ANY ANY ANCHOR ANCHOR FAILS FAILS TESTING, TESTING, ALL ALL ANCHORS ANCHORS OF OF THE THE SAME SAME CATEGORY CATEGORY NOT NOT PREVIOUSLY PREVIOUSLY TESTED TESTED SHALL SHALL BE BE TESTED TESTED UNTIL UNTIL 20 20 CONSECUTIVE CONSECUTIVE ANCHORS ANCHORS PASS, PASS, THEN THEN THE THE INITIAL INITIAL TESTING TESTING FREQUENCY FREQUENCY SHALL SHALL BE BE RESUMED. RESUMED.
SEAL FESSIONA PRO L ED RRY J. VOLKE E
T
APPLICATION APPLICATION
PERCENT PERCENT OF OF ALL ALL ANCHORS ANCHORS
SILL SILL PLATE PLATE BOLTING BOLTING AND AND REBAR REBAR AT AT SLAB SLAB ON ON GRADE, GRADE, UNO UNO
10 10 PERCENT PERCENT
STRUCTURAL STRUCTURAL EXCLUDING EXCLUDING SILL SILL PLATE PLATE BOLTING BOLTING
100 100 PERCENT PERCENT
NON-STRUCTURAL NON-STRUCTURAL INCLUDING INCLUDING EQUIPMENT EQUIPMENT ANCHORAGE ANCHORAGE
50 50 PERCENT PERCENT
T
E
No. S3737
A RU C T UR O F OF I CAL
05/15/2019 PROJECT
TEHAMA CENTER STUDENT SERVICES
TESTING TESTING FREQUENCY FREQUENCY
GENERAL GENERAL CONC CONC
INC:
INSTALLATION INSTALLATION 1. 1. INSTALL INSTALL PER PER REQUIREMENTS REQUIREMENTS OF OF THE THE EVALUATION EVALUATION AGENCY AGENCY REPORT REPORT & & MANUFACTURER'S MANUFACTURER'S PUBLISHED PUBLISHED INSTALLATION INSTALLATION INSTRUCTIONS INSTRUCTIONS FOR FOR THE THE SPECIFIC SPECIFIC ANCHOR. ANCHOR.
5. 5. TESTING TESTING FREQUENCIES FREQUENCIES SHALL SHALL BE BE AS AS INDICATED INDICATED IN IN THE THE TABLE TABLE BELOW. BELOW. WHEN WHEN MULTIPLE MULTIPLE ANCHORS ANCHORS ARE ARE USED USED IN IN A A SINGLE SINGLE GROUP GROUP OR OR CONNECTION, CONNECTION, THE THE PERCENT PERCENT OF OF ANCHORS ANCHORS TESTED TESTED AT AT EACH EACH LOCATION LOCATION SHALL SHALL BE BE AS AS INDICATED INDICATED BELOW. BELOW.
GENERAL GENERAL CONC CONC
APP. 02-117123
EER GIN EN R
3/8" 3/8"
60
THESE THESE NOTES NOTES SHALL SHALL APPLY APPLY TO TO THE THE INSTALLATION, INSTALLATION, INSPECTION, INSPECTION, AND AND TESTING TESTING OF OF EXPANSION, EXPANSION, ADHESIVE, ADHESIVE, AND AND SCREW SCREW ANCHORS. ANCHORS. USE USE SPECIFIC SPECIFIC PRODUCTS PRODUCTS WHERE WHERE INDICATED. INDICATED. IF IF A A SPECIFIC SPECIFIC PRODUCT PRODUCT // MANUFACTURER MANUFACTURER IS IS NOT NOT NOTED, NOTED, SELECT SELECT ANCHOR ANCHOR FROM FROM THE THE PROVIDED PROVIDED TABLES TABLES BASED BASED ON ON ANCHOR ANCHOR TYPE, TYPE, DIAMETER DIAMETER AND AND BASE BASE MATERIAL. MATERIAL. POST-INSTALLED POST-INSTALLED ANCHORS ANCHORS // REINFORCING ARE NOT PERMITTED TO REPLACE CAST-IN ANCHORS/REINFORCING REINFORCING ARE NOT PERMITTED TO REPLACE CAST-IN ANCHORS/REINFORCING UNLESS UNLESS SPECIFICALLY SPECIFICALLY NOTED. NOTED.
3. 3. ANCHOR ANCHOR INSTALLATION INSTALLATION SHALL SHALL MEET MEET THE THE MINIMUM MINIMUM EMBEDMENT, EMBEDMENT, EDGE EDGE DISTANCE, DISTANCE, SPACING, SPACING, AND AND BASE BASE MATERIAL MATERIAL THICKNESS THICKNESS CRITERIA CRITERIA ESTABLISHED ESTABLISHED BY BY THE THE RELEVANT RELEVANT EVALUATION EVALUATION AGENCY AGENCY REPORT REPORT & & MANUFACTURER'S MANUFACTURER'S PUBLISHED PUBLISHED INSTALLATION INSTALLATION INSTRUCTIONS. INSTRUCTIONS.
** TT == 33 1/4" 1/4" MIN MIN AT AT TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK ** STD EMBED = 2 3/8" AT TOPSIDE OF CONC ** STD EMBED = 2 3/8" AT TOPSIDE OF CONC O/ O/ STEEL STEEL DECK DECK
GENERAL GENERAL CONCRETE CONCRETE & & TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
A
C
1/2" 1/2"
S-_056000_N002A S-_056000_N002A 170127. 170127. Q2 Q2
S
**
3/8" 3/8"
GENERAL GENERAL CONCRETE CONCRETE & & TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK
1/4" 1/4"
19 19
ANCHOR ANCHOR DIA DIA STD EMBED, STD EMBED, Hnom Hnom TYP TYP UNO UNO MIN MIN CONC CONC THICKNESS, THICKNESS, TT TORQUE TORQUE TEST TEST LOAD LOAD (LB-FT) (LB-FT)
UNDERSIDE OF CONC O/ STEEL DECK
POST INSTALLED ANCHORS
ST
MAX MAX INSTALLATION INSTALLATION TORQUE TORQUE (LB-FT) (LB-FT) TORQUE TORQUE TEST TEST LOAD LOAD (LB-FT) (LB-FT)
GENERAL GENERAL CONCRETE CONCRETE & & TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STEEL STEEL DECK DECK
TT
ANCHOR ANCHOR DIA DIA STD STD EMBED, EMBED, Hnom Hnom TYP TYP UNO UNO MIN MIN CONC CONC THICKNESS, THICKNESS, TT
"HILTI" "HILTI" KWIK KWIK BOLT-TZ BOLT-TZ INSTALLED INSTALLED IN IN NORMAL NORMAL WEIGHT WEIGHT OR OR LIGHT LIGHT WEIGHT WEIGHT CONCRETE CONCRETE (f'c (f'c == 3000 3000 PSI PSI MIN) MIN) (ICC REPORT ESR 1917) (ICC REPORT ESR 1917)
UNDERSIDE OF CONC OVER STEEL DECK LOWER FLUTE UPPER FLUTE
1/2" 1/2"
3/8" 3/8"
S-_056000_N004A S-_056000_N004A 170127. 170127. Q2 Q2
"SIMPSON" "SIMPSON" STRONG-BOLT STRONG-BOLT 22 INSTALLED INSTALLED IN IN NORMAL NORMAL WEIGHT WEIGHT OR OR LIGHT LIGHT WEIGHT WEIGHT CONCRETE CONCRETE (f'c (f'c == 3000 3000 PSI PSI MIN) MIN) (ICC (ICC REPORT REPORT ESR ESR 3037) 3037)
"SIMPSON" "SIMPSON" TITEN TITEN HD HD INSTALLED INSTALLED IN IN NORMAL NORMAL WEIGHT WEIGHT OR OR LIGHT LIGHT WEIGHT WEIGHT CONCRETE CONCRETE (f'c (f'c == 3000 3000 PSI PSI MIN) MIN) (ICC REPORT ESR 2713) (ICC REPORT ESR 2713)
D
EXPANSION ANCHORS IN CONCRETE
1. 1. EMBEDMENT EMBEDMENT SHALL SHALL BE BE AS AS INDICATED INDICATED IN IN THE THE TABLE TABLE BELOW, BELOW, TYP TYP UNO. UNO. ALL ALL EMBEDMENTS EMBEDMENTS SPECIFIED SPECIFIED ARE ARE NOMINAL NOMINAL EMBEDMENT EMBEDMENT DEPTHS. DEPTHS. REFER REFER TO TO EVALUATION EVALUATION AGENCY AGENCY REPORT REPORT FOR FOR EFFECTIVE EFFECTIVE EMBEDMENTS. EMBEDMENTS.
"HILTI" "HILTI" KWIK KWIK HUS-EZ HUS-EZ (KH-EZ) (KH-EZ) // KWIK KWIK HUS-EZ1 HUS-EZ1 (KH-EZ1) (KH-EZ1) INSTALLED INSTALLED IN IN NORMAL NORMAL WEIGHT WEIGHT OR OR LIGHT LIGHT WEIGHT WEIGHT CONCRETE CONCRETE (f'c (f'c == 3000 3000 PSI PSI MIN) MIN) (ICC REPORT ESR 3027) (ICC REPORT ESR 3027) GENERAL GENERAL CONCRETE CONCRETE & & TOPSIDE TOPSIDE OF OF CONC CONC O/ O/ STL STL DECK DECK
5
L N IA
ADHESIVE ANCHORS IN CONCRETE
3
R
2
REGIST ER K
2"
1
770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
ISSUED
MARK
POWER ACTUATED FASTENERS
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
S-_056000_N001A S-_056000_N001A 180306. 180306. Q2 Q2
1. 1. POWER POWER ACTUATED ACTUATED FASTENERS FASTENERS SHALL SHALL BE BE "HILTI" "HILTI" X-U X-U (ICC (ICC ESR ESR 2269), 2269), "SIMPSON" "SIMPSON" PDPA PDPA (ICC (ICC ESR ESR 2138), 2138), OR OR "DEWALT" "DEWALT" POWER POWER DRIVEN DRIVEN FASTENERS FASTENERS (ICC (ICC ESR ESR 2024), 2024), TYP TYP UNO. UNO.
B
2. 2. INSTALLATION INSTALLATION OF OF FASTENERS FASTENERS SHALL SHALL BE BE IN IN ACCORDANCE ACCORDANCE WITH WITH THE THE EVALUATION EVALUATION AGENCY AGENCY REPORT. REPORT. INSTALL INSTALL FASTENERS FASTENERS WITH WITH SUFFICIENT SUFFICIENT EDGE EDGE DISTANCE DISTANCE AND AND SPACING SPACING TO TO ACHIEVE ACHIEVE FULL FULL CAPACITY, CAPACITY, UNO. UNO. 3. 3. FASTENERS FASTENERS TO TO CONCRETE CONCRETE OR OR MASONRY MASONRY SHALL SHALL HAVE HAVE 1" 1" MIN MIN EMBEDMENT EMBEDMENT (1 (1 1/4" 1/4" MIN MIN FOR FOR "SIMPSON" "SIMPSON" PDPA PDPA IN IN MASONRY), MASONRY), TYP TYP UNO. UNO. 4. 4. FASTENERS FASTENERS TO TO STRUCTURAL STRUCTURAL STEEL STEEL SHALL SHALL HAVE HAVE MIN MIN EMBEDMENT EMBEDMENT TO TO STEEL STEEL PER PER MANUFACTURER, MANUFACTURER, TYP TYP UNO. UNO.
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
5. 5. FASTENERS FASTENERS MAY MAY NOT NOT BE BE USED USED FOR FOR TENSION TENSION LOADS LOADS EXCEPT EXCEPT FOR FOR THE THE FOLLOW FOLLOW CONDITIONS: CONDITIONS: •• VERTICAL VERTICAL SUSPENSION SUSPENSION WIRES WIRES FOR FOR ACOUSTICAL ACOUSTICAL TILE TILE OR OR LAY-IN LAY-IN CEILINGS CEILINGS •• VERTICAL VERTICAL SUPPORTS SUPPORTS OF OF MECH MECH DUCTS, DUCTS, CONDUITS, CONDUITS, ETC ETC WHERE WHERE THE THE SERVICE SERVICE LOAD LOAD ON ON EACH EACH ANCHOR ANCHOR DOES DOES NOT NOT EXCEED EXCEED 90 90 LBS LBS FOR FOR FASTENERS FASTENERS IN IN CONCRETE CONCRETE OR OR 250 250 LBS LBS FOR FOR FASTENERS FASTENERS IN IN STRUCTURAL STRUCTURAL STEEL. STEEL. •• FASTENERS FASTENERS ARE ARE NOT NOT PERMITTED PERMITTED AT AT SEISMIC SEISMIC BRACING BRACING ATTACHMENTS. ATTACHMENTS.
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
6. 6. WHEN WHEN INSTALLING INSTALLING FASTENERS FASTENERS IN IN PRE/POST-TENSIONED PRE/POST-TENSIONED CONCRETE CONCRETE DO DO NOT NOT DAMAGE DAMAGE STRANDS. STRANDS. LOCATE LOCATE STRANDS STRANDS AT AT AFFECTED AFFECTED AREAS AREAS USING USING NON-DESTRUCTIVE NON-DESTRUCTIVE MEANS MEANS PRIOR PRIOR TO TO INSTALLING INSTALLING FASTENERS. FASTENERS. MAINTAIN MAINTAIN A A MINIMUM MINIMUM CLEARANCE CLEARANCE OF OF 2" 2" BETWEEN BETWEEN THE THE STRANDS STRANDS AND AND THE THE FASTENERS. FASTENERS. 7. 7. THE THE OPERATOR, OPERATOR, TOOL, TOOL, & & FASTENER FASTENER SHALL SHALL BE BE PRE-QUALIFIED PRE-QUALIFIED BY BY THE THE PROJECT PROJECT INSPECTOR INSPECTOR WHO WHO SHALL SHALL OBSERVE OBSERVE THE THE TESTING TESTING OF OF THE THE FIRST FIRST 10 10 FASTENER FASTENER INSTALLATIONS. INSTALLATIONS. THEREAFTER, THEREAFTER, RANDOM RANDOM TESTS TESTS UNDER UNDER THE THE PROJECT PROJECT INSPECTOR'S INSPECTOR'S SUPERVISION SUPERVISION SHALL SHALL BE BE MADE MADE TO TO APPROXIMATELY APPROXIMATELY 11 IN IN 10 10 PINS. PINS. IF IF ANY ANY PIN PIN FAILS, FAILS, TEST TEST ALL ALL PINS PINS OF OF THE THE SAME SAME CATEGORY CATEGORY NOT NOT PREVIOUSLY PREVIOUSLY TESTED TESTED UNTIL UNTIL 20 20 CONSECUTIVE CONSECUTIVE PASS, PASS, THEN THEN RESUME RESUME THE THE INITIAL INITIAL TESTING TESTING FREQUENCY. FREQUENCY. 8. 8. TENSION TENSION TEST TEST LOAD LOAD SHALL SHALL BE BE 11 1/4 1/4 TIMES TIMES THE THE TENSION TENSION CAPACITY CAPACITY LISTED LISTED IN IN THE THE EVALUATION EVALUATION AGENCY AGENCY REPORT. REPORT. 9. 9. TEST TEST LOAD LOAD SHALL SHALL BE BE APPLIED APPLIED TO TO THE THE PIN PIN IN IN SUCH SUCH A A MANNER MANNER AS AS NOT NOT TO TO RESIST RESIST THE THE SPALLING SPALLING TENDENCY TENDENCY OF OF THE THE CONCRETE CONCRETE SURROUNDING SURROUNDING THE THE PIN. PIN. 10. 10. TESTING TESTING IS IS NOT NOT REQUIRED REQUIRED FOR FOR FASTENERS FASTENERS USED USED AT AT SILLS SILLS OF OF INTERIOR INTERIOR NON-STRUCTURAL NON-STRUCTURAL WALLS WALLS PROVIDED PROVIDED THERE THERE ARE ARE A A MINIMUM MINIMUM OF OF (3) (3) FASTENERS FASTENERS PER PER SEGMENT SEGMENT OF OF SILL. SILL. 11. 11. A A REPORT REPORT OF OF TEST TEST RESULTS RESULTS SHALL SHALL BE BE SUBMITTED SUBMITTED TO TO THE THE ENFORCEMENT ENFORCEMENT AGENCY AGENCY AND AND STRUCTURAL STRUCTURAL ENGINEER. ENGINEER.
A
TITLE
TYPICAL NOTES
5/15/2019 4:35:23 PM
SHEET
S-014
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
FOUNDATION NOTES 170828. Q2
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
1. SEE S-000 SERIES SHEETS FOR GENERAL NOTES & S-500 SERIES SHEETS FOR TYPICAL DETAILS.
APP. 02-117123
2. SEE S-200 SERIES SHEETS FOR WALL & FRAMING ELEVATIONS.
REVIEWED FOR
3. DIMENSIONS ARE TO FOS OR CENTERLINE OF COLUMNS/POSTS, UNO. SEE SECTIONS & DETAILS FOR FOC LOCATIONS RELATIVE TO FOS.
0 1/4" 1/2"
INC:
SS
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
4. SEE ARCH & OTHER CONSULTANT DWGS FOR DIMENSIONS & LOCATIONS OF WALL OPENINGS. 5. SEE ARCH DWGS FOR DIMENSIONS OF SLAB DEPRESSIONS & SLOPED SLABS. 6. SEE ARCH & OTHER CONSULTANT DWGS FOR FLOOR PENETRATIONS NOT SHOWN. SAWCUT OR CORE DRILL CLEAN HOLES WITH NO OVERCUTTING. COMPLY WITH TYPICAL DETAILS.
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
7. SEE CIVIL DRAWINGS AND SPECIFICATIONS FOR ENGINEERED FILL. 8. EXTERIOR CONCRETE FLATWORK IS NOT SHOWN, SEE CIVIL & ARCH DWGS. 9. CONTINUOUS WALL FOOTINGS TO BE CENTERED UNDER WALLS AND PAD FOOTINGS TO BE CENTERED UNDER COLUMNS, TYP UNO. 10. TOP OF FOOTINGS SHALL BE 1'-0" BELOW FINISHED FLOOR (TOF 99'-0"), TYP UNO. SEE ARCH & OTHER CONSULTANT DRAWINGS FOR UTILITIES THAT WILL AFFECT FOOTINGS AND COMPLY WITH TYPICAL DETAILS.
D
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
11. SEE SCHEDULE FOR CONTINUOUS FOOTING SIZE & REINF, TYP UNO. 12. CONCRETE SLAB OVER SUB BASE SHALL BE AS NOTED IN SCHEDULE O/ VAPOR BARRIER O/ 4" FREE DRAINING CRUSHED ROCK. TOC = 100'-0" TYP UNO.
CONSULTANT
13. EXTERIOR STUDS SHALL BE AS FOLLOWS, TYP UNO: • GRIDLINES B & D: 2X6 1.6E LSL STUDS @ 16" OC, ALIGN STUD W/ I-JOIST, TYP • GRIDLINES 1 & 7: STUDS LESS THAN OR EQUAL TO 18 FEET IN LENGTH SHALL BE 2X8 1.6E LSL STUDS @ 16" OC; STUDS GREATER THAN 18 FEET IN LENGTH SHALL BE 4X8 1.6E LSL STUDS @ 16" OC. 14. INTERIOR STUDS SHALL BE 2X6 @ 16" OC TYP UNO. STUDS LESS THAN OR EQUAL TO 18 FEET IN LENGTH SHALL BE DF-L #1. STUDS GREATER THAN 18 FEET IN LENGTH SHALL BE 2X8 1.6E LSL STUDS @ 16" OC.
SCHEDULES SCHEDULE - SLAB
SCHEDULE - CONTINUOUS FOOTING SCHEDULE - CONTINUOUS FOOTING DEPTH REINFORCEMENT
WIDTH WIDTH 1'-6" 1'-6" 3'-0"
DEPTH 1'-6" 1'-6" 2'-0"
REINFORCEMENT (2) #5 #5 CONT CONTBARS BARST&B AT BOT LONG & #5 @ 16" OC TRANS (2) LONGITUDINAL (2) #5 CONT BARS AT BOT LONG & #5 @ 16" OC TRANS (5) BARS AT BOT LONG & #5 @ TRANS (5) #5 CONT BARS T&B LONG & #5 @16" 24"OC OC TRANS AT BOT
SEAL
SCHEDULE - SPREAD FOOTING WIDTH WIDTH 3'-0" 2'-0" 4'-0" 3'-0"
DEPTH DEPTH 1'-6" 1'-6" 1'-6" 1'-6"
FS4.0
4'-0"
4'-0"
1'-6"
FESSIONA PRO L ED RRY J. VOLKE E
REINFORCEMENT REINFORCEMENT (4) (3) #5 #5 BOTTOM BOTTOM BARS BARS EA EA WAY WAY (5) #5 BOTTOM BARS EA WAY (4) #5 BOTTOM BARS EA WAY
REGIST ER K
LENGTH LENGTH 3'-0" 2'-0" 4'-0" 3'-0"
(5) #5 BOTTOM BARS EA WAY
A
T
20'-3 5/8" 20'-3 5/8"
4'-74'-7 5/8" 5/8"
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
CONC SLAB TYPE
DIAGONAL BRACE ABOVE
SI ZE C O L SI ZE H D
FCX.X CONTINUOUS FOOTING & TAG MANAGEMENT
FSX.X
S
S
STEPPED FOOTING
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 ?00.00.00? LIONAKIS 2017
AGENCY
H H D D U U 4 4
2 H D
U
2 H D
U
2 H D
U
2 H D
U
2 H D
U
2 H D
U
2 H D
U
2 U H D
H D
U
2
S-311
2
SPREAD FOOTING & TAG
18'-2" 18'-2"
3 3 S-311
U
SHEAR WALL TYPE, SEE "SHEAR WALL SCHEDULE"
6x6 6x6 8x8 8x8
FS4.0 FS4.0
HOLDOWN & REQUIRED POST
1 1 S-312
2 2 S-312
3 3 S-312
S-312
S-312
S-312
FS3.0 FS3.0
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
FS3.0 FS3.0
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
FS3.0 FS3.0
8" 8"
C
CL HSS CL HSS
CL HSS CL HSS
8'-58'-5 1/4" 1/4"
1 1 S-263 S-263
A A
7 3/4" 7 3/4"
A
TITLE
PLAN - FOUNDATION
SHEET
5/15/2019 4:35:27 PM
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
COLUMN WITH CALLOUT
A
C C 9'-69'-6 3/4" 3/4"
H H D D U U 4 4
2 2 S-262 S-262
2 2 S-311 S-311
76'-2 5/8" 76'-2 5/8"
H H D D U U 4 4
H H D D U U 5 5
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
FS4.0 FS4.0
DATE 01/04/2019 5/17/2019
DIAGONAL BRACE BELOW
C.4 C.4 10'-6 3/4" 10'-6 3/4"
FUTURE DOOR, FRAME PER FUTURE DOOR, FRAME 11 PER 11 S-561 S-561
H H D D 6X 6X U4 U4 8 8
FS4.0 FS4.0
1 1 S-262
ISSUED
MARK
17'-1" 17'-1"
S-311
B.6 B.6
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4 FC3.0
H DH H UD D 2U U 14 14
2 H D
U
2 H D
U
2 H D
U
2 U H D FS3.0 FS3.0
ELEVATION RELATIVE TO TOC
B B
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
L = 121'-3"
C C
SLAB STEP SYMBOL -2"
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
C FL = 55'-6"
H H D D U U 4 4
1 1 S-311
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
SAD FOR EXTENTS
X SG
S-262
FS4.0 FS4.0
H H D D U U 11 141 FS3.0 FS3.0
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
FS3.0 FS3.0
H H D D U U 14 14
S-263
H D
H H D D U U 11 141 H H SS S 4XS4X 4X 4X 1/ 1/ 4 4 FC3.0
H H D D U U 4 4 H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
FS3.0 FS3.0
2 2 S-263
S-261
S-311
DEPRESSED SLAB AREA
D D
H H D D U U 14 14
HHSHS SSS S 4X8X5X 4X8X5X 1/5/83/ 4 8
FS4.0 FS4.0
L = 105'-3" B B
2 2 S-261
CONCRETE CURB OR PAD
E E
7'-97'-9 1/4" 1/4"
16 16 S-532 S-532 TYP TYP
H H D D U U 4 4
C C
H H D D U U 5 5
H H D D U U 5 5
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
1'-2 5/8"
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
HH SSS 8SX5 8XX5 5X/ 3 8 /8
TOC 100'-0" TOC 100'-0"
H H D D U U 5 5
H HD D U U 1 5 1
L = 76'-3"
L = 21'-6"
FS3.0 FS3.0
FC C
B
H H D D U U 4 4
1 1 S-261 S-261
3 3 S-311
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
H HSH SS SS 4XS8X5X 4X8X5X 1/ 5/38/ 4 8
H H D D U U 4 4
L = 55'-6"
H H D D U U 11 11
FS4.0 FS4.0
FS3.0 FS3.0
CLIENT
F F
FS4.0
1 1 S-264 S-264
770 DIAMOND AVE RED BLUFF, CA 96080
STRUCTURAL WALL
HHS SSS H H 85XX5 D D 8XX3 U U 14 14 5//8 8
H SS
H H D D U U 4 4
FS4.0
TEHAMA CENTER STUDENT SERVICES
NON-STRUCTURAL WALL, SAD
2'-0" TYP
SG4 SLAB TYP
5 U U5 HD HD
2 2 S-311 S-311
3 3 S-312 S-312
FS3.0
4 4 SG SG
B
FS3.0
(E) ELEMENTS SHOWN FADED - LINETYPE AND PATTERN/HATCHING AS NOTED FOR NEW CONSTRUCTION
C
H SS
4X 4X 1/ 4 FS4.0
S-311
FC3.0
FULL HEIGHT 6X6X5/8 HSS5x5x3/8 EA SIDE OF STRONGWALL, TYP
A RU C T UR O F OF I CAL
PROJECT
FOUNDATION LEGEND
20'-6 5/8" 20'-6 5/8"
1'-2 5/8"
2 2 S-312 S-312
E
No. S3737
05/15/2019
170828. Q1 13'-0 1/2"
EXTEND FOUNDATION BELOW COLUMN, TYP LINE F
H HH 58XX5 D DD U U U 8X35 111411 /8
C C
2 2 S-264 S-264 FS3.0
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
L = 10'-0"
HHH SSSS SS 86X5XX 86X5XX 55/3/ / 888
11 1 U U1 H D HD
H H D D U U 4 4
13'-0 1/2"
7 7
19'-8 3/8" 19'-8 3/8"
FC3.0
H H D D U U 11 11
FS3.0 FS3.0
FS3.0
FS4.0 1 1 S-311
40'-7 1/4" 12'-1"
"SIMPSON" STRONGWALL, TYP OF (4) SEE ELEVATION
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
H H SS S 4XS4X 4X 4X 1/ 1/ 4 4
1 1 S-312 S-312
6 6
20'-3 5/8" 20'-3 5/8"
4X 4X 1/ 4
1'-2 5/8"
FS3.0 FS3.0
5 5
H SS
19'-8 3/8" 19'-8 3/8"
4X 4X 1/ 4
20'-6 5/8" 20'-6 5/8"
C
121'-1 1/4" 121'-1 1/4"
4 4
4X 4X 1/ 4
3 3
H SS
2 2
H SS
1 1
T
S
ST
NOTE: CONTINIUOS FOOTING SIZES NOTES SHALL APPLY TO FULL LENGTH OF GRID LINE, TYP, UNO
EER GIN EN R
TYPE TYPE FS3.0 FS2.0 FS4.0 FS3.0
L N IA
TYPE TYPE FC1.5 FC1.5 FC3.0
DESCRIPTION 4" CONC SLAB W/ #4 @ 16" OC EW CENTERED IN SLAB
R
TYPE SG4
Q1
11
PLAN -- FOUNDATION FOUNDATION PLAN SCALE 1/8" = 1'-0" SCALE 1/8" = 1'-0"
NORTH
S-111
2"
1
2
3
4
5
ROOF FRAMING NOTES 1"
1. 2.
S-_010000_N001A 170828. Q2 SEE S-000 SERIES SHEETS FOR GENERAL NOTES & S-500 SERIES SHEETS FOR TYPICAL DETAILS.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
REVIEWED FOR
SEE S-200 SERIES SHEETS FOR WALL & FRAMING ELEVATIONS.
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
SS
D
INC:
3.
DIMENSIONS ARE TO FOS OR CENTERLINE OF COLUMNS/POSTS, UNO. SEE SECTIONS & DETAILS FOR FOC LOCATIONS RELATIVE TO FOS.
4.
SEE ARCH & OTHER CONSULTANT DWGS FOR DIMENSIONS & LOCATIONS OF WALL OPENINGS. SEE TYPICAL DETAILS FOR FRAMING AT OPENINGS.
5.
SEE ARCH & OTHER CONSULTANT DWGS FOR ROOF PENETRATIONS NOT SHOWN. PROVIDE FRAMING AROUND OPENINGS PER TYPICAL DETAILS. SAWCUT OR CORE DRILL CLEAN HOLES WITH NO OVERCUTTING. CONFORM WITH TYPICAL DETAILS.
6.
SEE ARCH DWGS FOR DIMENSIONS OF ROOF OVERHANGS, UNO.
7.
EXTERIOR WALLS ARE 2x6 STUDS @ 16" OC, TYP UNO.
8.
PROVIDE STRUCTURAL PANEL EDGE NAILING TO THE FULL LENGTH OF ALL GLB's, AND MANUFACTURED TRUSSES, I-JOISTS, RIM JOISTS AND BLOCKING AT SHEAR WALLS. SEE PLANS FOR LOCATIONS WHERE DOUBLE ROWS OF EDGE NAILING OCCUR.
9.
CAMBER IN GLU-LAM BEAMS SHALL BE 1600' RADIUS, TYP UNO.
✔
DATE:
10. PROVIDE BRIDGING, BLOCKING, ERECTION BRACING, WEB STIFFENERS, FILLERS AND NAILING FOR I-JOIST ROOF PER I-JOIST MANUFACTURER SPECIFICATIONS AND AS SHOWN ON PLANS.
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
11. SEE S-000 SHEETS FOR MANUFACTURED ROOF TRUSS DESIGN CRITERIA.
SEAL
2
3
4
5
6
20'-3 5/8"
20'-3 5/8"
19'-8 3/8"
PROJECT
PLAN LEGEND
20'-6 5/8"
170828. Q1 1 S-312
2 S-312
(E) ELEMENTS SHOWN FADED - LINETYPE AND PATTERN/HATCHING AS NOTED FOR NEW CONSTRUCTION
3 S-312
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
STRUCTURAL WALL
2
TYP AT GLB O/ HSS COL
TOF 113'-9"
S-564
4'-7 5/8"
CO L
SI ZE
7'-9 1/4"
2x12 FASCIA
1 S-311
A
TYP GLB AT WOOD POST, SEE 8 S-567
COLUMN WITH CALLOUT
HOLDOWN & REQUIRED POST
ISSUED
MARK
DATE 01/04/2019 5/17/2019
SHEAR WALL TYPE, SEE "SHEAR WALL SCHEDULE"
BEAM SPLICE
C.4
TOF 113'-9"
TYP AT COL
2 S-262
6 3/4"x21" GLB
6 3/4"x21" GLB
5 1/8"x12" GLB
DBL JOIST
6X12
16" TJI 230 @ 32" OC S-263
5 1/8"x12" GLB 5 1/8"x12" GLB
5 1/8"x12" GLB
DBL JOIST
1
6X12
DBL JOIST
5 1/8"x12" GLB
AGENCY 3 S-311
B
2x10 @ 24" OC
20" TJI 560 @24" OC
18" TJI 360 @ 24" OC
DBL JOIST TYP AT WINDOW JAMB ABOVE
DBL JOIST 2x12 FASCIA
3 S-311
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
B.6
TOF 113'-9"
TOF 113'-9"
CMST12 FILL EVERY OTHER HOLE FULL LENGTH OF LINE B.6
MANAGEMENT
18'-2"
S-262
5 1/8"x12" GLB
5 1/8"x12" GLB
8'-5 1/4"
S-261
S-261
1
S-263
2
2x12 FASCIA
WALL ABV
1
2 S-311
2
9'-6 3/4"
C 2 S-311
A
2x12 FASCIA 1 S-312
2 S-312
3 S-312
A
TITLE
PLAN - LOW ROOF FRAMING
SHEET
5/15/2019 4:35:29 PM
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
S
B
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
E
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
D
10'-6 3/4"
8 3/ 6X 6X V SS B H A 8 3/ 6X 6X BV A
SS H 8
PLYWOOD SPAN DIRECTION
6 3/4"x21" GLB 5 1/8"x21" GLB
6 3/4"x21" GLB
WALL ABV
F
CLIENT
76'-2 5/8"
8
3/
6X
6 3/4"x36" GLB
DBL JOIST
(2) CMSTC16 TYP (4) LOCATIONS SEE DETAIL 14 S-563
6X
SP LAYOUT TYP UNO
SS H
MECH UNIT 2000# MAX 12'-0" TYP
MECH UNIT 3500# MAX
16" TJI/L65 @ 32" OC 16" TJI 230 @32"OC
S-264
DBL I-JOIST
1
18" TJI 360 @ 24" OC DBL I-JOIST
DBL JOIST
MECH UNIT 2000# MAX
DBL JOIST
6 3/4"x36" GLB
TOF 115'-0"
ROOF NAILING AT SHADED REGION EDGE NAIL = 10D @ 2 STAG 4"1/2" OC,OC, STAG FIELD NAIL = 10D @ 12" OC BLOCK ALL PANEL EDGES
2x10 @ 24" OC
4 S-564
5 1/8"x12" GLB
6X12 BLW
S-564
(2)CMST12 FILL
EVERY OTHER HOLE FULL LENGTH OF LINE C.4
4
TYP
5 1/8"x12" GLB
STRUCTURAL WALL BELOW
PO HD S T SIZ E SI ZE
6x12 BLW
2x12 @ 24" OC
ALT
6X12 BLW
5 1/8"x12" GLB
20" TJI 560 @24" OC 18" OC 18" TJI 360 @ 24"
18 S-567
2x12 FASCIA
6x12 BLW
NON-STRUCTURAL WALL, SAD
2x12 FASCIA
2x10 @ 24" OC
5 1/8"x12" GLB
1 S-311
6x12 BLW
2x12 FASCIA
TYP
3'-0"
TYP
3 S-564
16" TJI 230 @ 32" OC
3'-0"
S-264
17'-1"
ROOF NAILING AT SHADED REGION EDGE = 10DAT @SHADED 2 1/2" OC, STAG ROOFNAIL NAILING REGION FIELD NAIL = 10D @ 12" OC EDGE NAIL = 10D @ 2 1/2" OC, STAG BLOCK ALL PANEL EDGES FIELD NAIL = 10D @ 12" OC
L N IA
05/15/2019
121'-1 1/4" 19'-8 3/8"
A RU C T UR O F OF I CAL
7
C 20'-6 5/8"
E
No. S3737
R
REGIST ER K
A
1
T
S
ST
T
EER GIN EN R
FESSIONA PRO L ED RRY J. VOLKE E
NORTH
1
PLAN - LOW ROOF FRAMING SCALE 1/8" = 1'-0"
S-132
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
ROOF ROOF FRAMING FRAMING NOTES NOTES
1"
S-_010000_N001A S-_010000_N001A 170828. 170828.Q2 Q2 1. 1. SEE SEES-000 S-000SERIES SERIESSHEETS SHEETSFOR FORGENERAL GENERALNOTES NOTES&&S-500 S-500SERIES SERIESSHEETS SHEETSFOR FORTYPICAL TYPICAL DETAILS. DETAILS.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
REVIEWED FOR
2. 2. SEE SEES-200 S-200SERIES SERIESSHEETS SHEETSFOR FORWALL WALL&&FRAMING FRAMINGELEVATIONS. ELEVATIONS. SS
0 1/4" 1/2"
INC:
3. 3. DIMENSIONS DIMENSIONSARE ARETO TOFOS FOSOR ORCENTERLINE CENTERLINEOF OFCOLUMNS/POSTS, COLUMNS/POSTS,UNO. UNO. SEE SEESECTIONS SECTIONS&& DETAILS DETAILSFOR FORFOC FOCLOCATIONS LOCATIONSRELATIVE RELATIVETO TOFOS. FOS.
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
4. 4. SEE SEEARCH ARCH&&OTHER OTHERCONSULTANT CONSULTANTDWGS DWGSFOR FORDIMENSIONS DIMENSIONS&&LOCATIONS LOCATIONSOF OFWALL WALLOPENINGS. OPENINGS. SEE SEETYPICAL TYPICALDETAILS DETAILSFOR FORFRAMING FRAMINGAT ATOPENINGS. OPENINGS.
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
5. 5. SEE SEEARCH ARCH&&OTHER OTHERCONSULTANT CONSULTANTDWGS DWGSFOR FORROOF ROOFPENETRATIONS PENETRATIONSNOT NOTSHOWN. SHOWN. PROVIDE PROVIDE FRAMING FRAMINGAROUND AROUNDOPENINGS OPENINGSPER PERTYPICAL TYPICALDETAILS. DETAILS. SAWCUT SAWCUTOR ORCORE COREDRILL DRILLCLEAN CLEANHOLES HOLES WITH WITHNO NOOVERCUTTING. OVERCUTTING. CONFORM CONFORMWITH WITHTYPICAL TYPICALDETAILS. DETAILS. 6. 6. SEE SEEARCH ARCHDWGS DWGSFOR FORDIMENSIONS DIMENSIONSOF OFROOF ROOFOVERHANGS, OVERHANGS,UNO. UNO. 7. 7. EXTERIOR EXTERIORWALLS WALLSARE ARE2x6 2x6STUDS STUDS@ @16" 16"OC, OC,TYP TYPUNO. UNO. 8. 8. PROVIDE PROVIDESTRUCTURAL STRUCTURALPANEL PANELEDGE EDGENAILING NAILINGTO TOTHE THEFULL FULLLENGTH LENGTHOF OFALL ALLGLB's, GLB's,AND AND MANUFACTURED MANUFACTUREDTRUSSES, TRUSSES,I-JOISTS, I-JOISTS,RIM RIMJOISTS JOISTSAND ANDBLOCKING BLOCKINGAT ATSHEAR SHEARWALLS. WALLS. SEE SEEPLANS PLANS FOR FORLOCATIONS LOCATIONSWHERE WHEREDOUBLE DOUBLEROWS ROWSOF OFEDGE EDGENAILING NAILINGOCCUR. OCCUR. 9. 9. CAMBER CAMBERIN INGLU-LAM GLU-LAMBEAMS BEAMSSHALL SHALLBE BE1600' 1600'RADIUS, RADIUS,TYP TYPUNO. UNO.
D
10. 10. PROVIDE PROVIDEBRIDGING, BRIDGING,BLOCKING, BLOCKING,ERECTION ERECTIONBRACING, BRACING,WEB WEBSTIFFENERS, STIFFENERS,FILLERS FILLERSAND ANDNAILING NAILING FOR FORI-JOIST I-JOISTROOF ROOFPER PERI-JOIST I-JOISTMANUFACTURER MANUFACTURERSPECIFICATIONS SPECIFICATIONSAND ANDAS ASSHOWN SHOWNON ONPLANS. PLANS.
11. SEE S-000 SHEETS FOR MANUFACTURED ROOF TRUSS DESIGN CRITERIA.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
SEAL
22
33
44
55
66
20'-3 20'-35/8" 5/8"
20'-3 20'-35/8" 5/8" LOUVER FRAME BLW DBL TOP PLATE, TYP (3) LOCATIONS SEE ELEV
11 S-312 S-312 2'-9" 2'-9" 3'-3" 3'-3"
22
19'-8 19'-83/8" 3/8"
22 S-312 S-312
170828. 170828.Q1 Q1 (E) (E)ELEMENTS ELEMENTSSHOWN SHOWNFADED FADED--LINETYPE LINETYPEAND AND PATTERN/HATCHING PATTERN/HATCHING AS ASNOTED NOTEDFOR FORNEW NEWCONSTRUCTION CONSTRUCTION
6x12 6x12
6x12 6x12
H PPOO HDD SSTT SSIIZZ SSIIZ EE ZEE
44xx6 BBEE LLOO 6 W W
44xx6 BBEE LLOO 6 W W 6x12 6x12
S-263 S-263
6x12 6x12
6x12 6x12
11
S-262 S-262
6x12 6x12
22 S-311 S-311 22
S-262 S-262
6x12 6x12
2'-9" 2'-9"
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
33 S-311 S-311
18'-2" 18'-2"
44xx6 BBEE 6 LLOO W W
SHEAR SHEARWALL WALLTYPE, TYPE,SEE SEE"SHEAR "SHEAR WALL WALLSCHEDULE" SCHEDULE"
BB 8'-5 1/4" 1/4" 8'-5
11
S-263 S-263
AA 11 S-312 S-312
22 S-312 S-312
33 S-312 S-312
A
TITLE
PLAN - HIGH ROOF FRAMING
SHEET
5/15/2019 4:35:31 PM
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
x66 44x W W OO ELL BBE
x66 44x W W OO ELL BBE
x66 44x W W OO ELL BBE
x66 44x W W OO ELL BBE x66 44x W W OO ELL BBE
x66 44x W W OO ELL BBE
x66 44x W W OO ELL BBE
x66 44x W W OO ELL BBE
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
DATE 01/04/2019 5/17/2019
AGENCY
ROOF NAILING AT SHADED REGION EDGE NAIL = 10D @ 2 STAG 4"1/2" OC,OC, STAG FIELD NAIL = 10D @ 12" OC BLOCK ALL PANEL EDGES
33 S-311 S-311
MARK
MANAGEMENT
B.6 B.6
2'-9" 2'-9"
ISSUED
CC
9'-6 3/4" 3/4" 9'-6
22
HOLDOWN HOLDOWN&&REQUIRED REQUIREDPOST POST
C.4 C.4
DBL JOIST JOIST DBL
S-261 S-261
11 TYP TYP S-566 S-566
44xx6 BBEE LLOO 6 W W
2x10 @ @ 24" 24" OC OC 2x10
44xx6 BBEE LLOO 6 W W
DBL JOIST JOIST DBL
S-261 S-261
22
W x66 W 44x OO ELL BBE
11
AA
76'-2 5/8" 5/8" 76'-2
TYP AT COL
CCO OL LS SIIZ ZEE
7'-9 1/4" 1/4" 7'-9 S-564
COLUMN COLUMNWITH WITHCALLOUT CALLOUT
BEAM BEAMSPLICE SPLICE
10'-6 3/4" 3/4" 10'-6
331/8"x9 1/8"x91/2" 1/2"PSL PSL
6x12 6x12
17'-1" 17'-1"
1/8"x9 1/2" 1/2" PSL PSL 33 1/8"x9
44xx6 BBEE LLOO 6 W W
6X
6
BBEE X344/ xx6 LLOO 8 6 W W
S
H SS
6
X BBEE 6X44xx6 LL O 3/86 OW H W S
6x12 6x12BLW
8
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
SS
x66 44x W W OO ELL BBE
2x10 @ @ 24" 24" OC OC 2x10
11 S-311 S-311
B 22 S-311 S-311
EE
16 16 TYP TYPAT AT SPLICE S-566 S-566 SPLICE
x66 44x W W OO ELL BBE
TYP 55 TYP S-566 S-566
6x12 6x12BLW
x66 44x W W OO ELL BBE
SP SPLAYOUT LAYOUT TYP TYPUNO UNO
18 18 S-566 S-566 113/4"x9 3/4"x91/2" 1/2"PSL PSL 3'-3" 2'-9" 2'-9" 3'-3"
HHS SSS 45XX 45XX 13//8 4
44xx6 BBEE LLOO 6 W W 44xx6 BBEE LLOO 6 W W
44xx6 BBEE LLOO 6 W W
W W OO ELL BBE
DBL JOIST JOIST DBL
x66 44x 6x12 6x12
PLYWOOD PLYWOODSPAN SPANDIRECTION DIRECTION
CLIENT
DD
2X10 @ 24" OC MAX TYP
20 20 S-566 S-566
6x12 6x12
1/8"x9 1/2" 1/2" PSL PSL 33 1/8"x9
1/8"x9 1/2" 1/2" PSL PSL 33 1/8"x9
1/8"x9 1/2" 1/2" PSL PSL 33 1/8"x9
S-264 S-264
6'-0" 6'-0"
11 S-311 S-311
STRUCTURAL STRUCTURALWALL WALLBELOW BELOW
FF
4'-7 5/8" 5/8" 4'-7
3'-3" 2'-9" 2'-9" 3'-3"
6'-0" 6'-0"
7'-5" 7'-5" 4'-10" 4'-10"
113/4"x9 3/4"x91/2" 1/2"PSL PSL
11
770 DIAMOND AVE RED BLUFF, CA 96080
NON-STRUCTURAL NON-STRUCTURALWALL, WALL,SAD SAD
331/8"x9 1/8"x91/2" 1/2"PSL PSL
HSS 6X6X3/8 BELOW DBL TOP PLATE, TYP ALL AROUND MECH WELL. SEE ELEC
TEHAMA CENTER STUDENT SERVICES
STRUCTURAL STRUCTURALWALL WALL
17 17 TYP TYPAT AT CORNER CORNER S-566 S-566
S-264 S-264
PROJECT
PLAN PLAN LEGEND LEGEND
20'-6 20'-65/8" 5/8"
33 S-312 S-312
3'-3" 3'-3" 2'-9" 2'-9"
NORTH NORTH
11
PLAN PLAN -- HIGH HIGH ROOF ROOF FRAMING FRAMING SCALE SCALE 1/8" 1/8"==1'-0" 1'-0"
L N IA
05/15/2019
121'-1 121'-11/4" 1/4" 19'-8 19'-83/8" 3/8"
A RU C T UR O F OF I CAL
77
C 20'-6 20'-65/8" 5/8"
E
No. S3737
R
REGIST ER K
A
11
T
S
ST
T
EER GIN EN R
FESSIONA PRO L ED RRY J. VOLKE E
S-133
017294 ?00.00.00? LIONAKIS 2017
2"
11
22
33
44
55
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
DATE:
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
BB
B.6 B.6
CC
C.4 C.4
FLS
ACS
✔
✔
07/03/2019
DD
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
15 15 S-566 CS14, CS14,SEE SEE S-566 TYP AT TYP ATCORNERS CORNERS MSTA30 MST27 TYP EA SIDE
SHEAR WALL EN FULL HEIGHT OF STUD AT GRID LINES B.6 AND C.4
TOP PL TO JOIST
CS16 CS16CONT CONTO/ O/2X 2XBLKG BLKG
POST, SEE PLAN
FESSIONA PRO L ED RRY J. VOLKE E
T
S
ST
A
T
E
No. S3737
L N IA
HOLD HOLDDOWN, DOWN, TYP TYPOF OF(6) (6)THIS THIS WALL WALLLINE, LINE,SEE SEEPLAN PLAN
A RU C T UR O F OF I CAL
R
REGIST ER K
POST, SEE PLAN
POST, SEE PLAN
POST, SEE PLAN
SEAL
EER GIN EN R
POST, SEE PLAN
FOR FORFRAMING FRAMINGAT AT OPENINGS, 11 OPENINGS,SEE SEE 11 TYP S-561 TYP S-561
05/15/2019 13'-4"
11'-6"
11'-1"
PROJECT
C L = 48'-9"
TEHAMA CENTER STUDENT SERVICES
C
B
11
SHEARWALL SHEARWALL ELEVATION ELEVATION LINE LINE 11
770 DIAMOND AVE RED BLUFF, CA 96080
SCALE SCALE 1/4" 1/4"==1'-0" 1'-0"
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
ISSUED
AA
BB
B.6 B.6
CC
C.4 C.4
DD
EE
FF
MARK
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
13 S-566
HSS 6X6X3/8 BTWN HSS FRAME AT HSS ATLOUVERS, LOUVERS, HSSFRAME COL, TYP AT TOP SAD SAD OF MECH WELL WALL
TYP
SEE 2/S-564 FOR HSS HORIZ TO HSS COL ATTACHMENT HSS FRAME AT LOUVERS SAD
B 15 15 S-566 CS14, CS14,SEE SEE S-566 TYP TYPAT ATCORNERS CORNERS MSTA30 MST27 TYP EA SIDE DUCT OPENINGS, TOP PL TO JOIST SEE MECHANICAL
BLW LOUVER. FILL EVERY OTHER HOLE
SHEAR WALL EN FULL HEIGHT OF STUD AT GRID LINES B.6 AND C.4
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
HOLD DOWN, TYP OF (4) THIS WALL LINE, SEE PLAN
HSS, SEE PLAN
HSS BLW GLB
HSS, SEE PLAN
HSS, SEE PLAN
HSS, SEE PLAN
FOR FORFRAMING FRAMINGAT AT OPENINGS, OPENINGS,SEE SEE 11 11 TYP TYP S-561 S-561
HSS4X4X1/4 HSS, SEE PLAN
FOR FORFRAMING FRAMINGAT AT OPENINGS, OPENINGS,SEE SEE 11 11 TYP TYP S-561 S-561
HSS4X4X1/4 HSS, SEE PLAN
CMST12 O/4X BLKG. FILL CMST14 EVERY O/ OTHER HOLE EACH CMST14 O/4X 4XBLKG BLKG SIDE OF WALL
DUCT OPENINGS, SEE MECHANICAL
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
MANAGEMENT
CS16CONT O/2X BLKG SILL CS16 O/ BLKG CS16 CONT O/2X 2XAND BLKG
HOLD DOWN, TYP OF (4) THIS WALL LINE, SEE PLAN 21'-5 1/4"
11'-0 3/8"
L = 76'-3" C F A
22
SHEARWALL SHEARWALL ELEVATION ELEVATION LINE LINE 33 SCALE SCALE 1/4" 1/4"==1'-0" 1'-0"
11'-7 3/8"
C
TITLE
ELEVATIONS SHEARWALL
5/15/2019 4:35:31 PM
SHEET
S-261
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
DATE:
B B
B.6 B.6
C C
C.4 C.4
D D
E E
ACS
✔
✔
07/03/2019
F F
13 S-566
TYP
45°
SEE 2/S-564 FOR HSS HORIZ TO HSS COL ATTACHMENT
HSSFRAME 6X6X3/8 HSS ATBTWN LOUVERS, SAD HSSFRAME COL, TYP AT TOP HSS AT LOUVERS, OF MECH WELL WALL SAD LOUVER FRAME SAD
CS16 CONT O/ 2X BLKG
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
15 S-566
CS14, SEE TYP AT CORNERS
CMST14
15 S-566
CS14, SEE TYP AT CORNERS
SHEAR WALL EN FULL HEIGHT OF STUD AT GRID LINES B.6 AND C.4
CMST14 O/ 4X BLKG CMST12O/O/4X 4XBLKG BLKG EACH CMST14 SIDE OF WALL. FILL EVERY OTHER HOLE
SEAL
10'-9 3/4"
11'-0 3/8"
C
PROJECT
C
TEHAMA CENTER STUDENT SERVICES
F C
1 1
A RU C T UR O F OF I CAL
05/15/2019
11'-10 3/8"
L = 57'-3"
E
L N IA
A
HOLD DOWN, TYP OF (4) THIS WALL LINE, SEE PLAN
T
S
ST
T
No. S3737
R
REGIST ER K
FESSIONA PRO L ED RRY J. VOLKE E
EER GIN EN R
HOLD DOWN, TYP OF (4) THIS WALL LINE, SEE PLAN
HSS, SEE PLAN
6X12 SEE PLAN
HSS, SEE PLAN
HSS BLW GLB
FOR FRAMING AT OPENINGS, SEE FOR FRAMING AT 11 TYP OPENINGS, SEE 11 S-561 TYP S-561
HSS4X4X1/4 HSS, SEE PLAN
6X12 SEE PLAN
CS16 O/2X BLKG AND SILL BLW LOUVER. FILL EVERY OTHER HOLE
HSS, SEE PLAN
MST27 2X10 TO 6X12
HSS, SEE PLAN HSS4X4X1/4
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
A A
FLS
SHEARWALL ELEVATION LINE 5 SHEARWALL ELEVATION LINE 5
770 DIAMOND AVE RED BLUFF, CA 96080
SCALE 1/4" = 1'-0" SCALE 1/4" = 1'-0"
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
A
B
B.6
C
C.4
D ISSUED
MARK
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
15 CS14, SEE S-566 TYP AT CORNERS
B MSTA30 MST27 TYP EA SIDE
TOP PL TO JOIST SHEAR WALL EN FULL HEIGHT OF STUD AT GRID LINES B.6 AND C.4
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
CS16 CONT O/ 2X BLKG AGENCY
FUTURE DOOR LOCATION
POST, SEE PLAN
POST, SEE PLAN
POST, SEE PLAN
FOR FRAMING AT OPENINGS, SEE 11 TYP S-561
POST, SEE PLAN
POST, SEE PLAN
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
FUTURE DOOR LOCATION
HOLDDOWN, TYP OF (6) THIS LINE, SEE PLAN
22'-1"
11'-1 3/4"
L = 56'-0" L = 56'-0"
2 A
12'-7 5/8"
C C
SHEARWALL ELEVATION LINE 7 SCALE 1/4" = 1'-0" TITLE
ELEVATIONS SHEARWALL
5/15/2019 4:35:32 PM
SHEET
S-262
017294 ?00.00.00? LIONAKIS 2017
2"
1
3
4
4
5
5
6
7
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
2
3
APP. 02-117123
0 1/4" 1/2"
1
2
SS
INC:
REVIEWED FOR ✔
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
DATE:
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
10'-2 1/4"
10'-6"
9'-3 3/4"
C 4'-4" L = 121'-3"
4'-4"
L = 121'-3"
1
4'-4"
4'-4"
4'-4"
4'-4"
4'-4"
4'-6 5/8"
C
SHEARWALL ELEVATION LINE B SCALE 1/4" = 1'-0"
SEAL
L N IA
A
E
No. S3737
A RU C T UR O F OF I CAL
R
REGIST ER K
T
S
ST
T
EER GIN EN R
FESSIONA PRO L ED RRY J. VOLKE E
05/15/2019 PROJECT
C
TEHAMA CENTER STUDENT SERVICES 1
2
3
4
5
6
7 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
ISSUED
MARK
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
MECH CHASE PIPE PENETRATION WHERE OCCURS
B
FOR FRAMING AT OPENINGS, SEE 11 TYP S-561
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
HOLD DOWN, TYP OF (6) THIS WALL LINE, SEE PLAN HOLD DOWN, TYP OF (6) THIS WALL LINE, SEE PLAN
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
AGENCY
40'-10 7/8"
L = 105'-6"
B
29'-7 5/8"
25'-1 1/8"
4'-8"
3'-3 7/8"
B
2
A
SHEARWALL ELEVATION LINE C SCALE 1/4" = 1'-0"
TITLE
ELEVATIONS SHEARWALL
5/15/2019 4:35:33 PM
SHEET
S-263
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
DATE:
11
22
33
44
55
66
FLS
ACS
✔
✔
07/03/2019
77 1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
GLB, SEE PLAN
GLB, SEE PLAN CMSTC12 W/W/ (44) 8D16D NAILS (2) CMST12 (54) NAILS TO LSL AND 8DNAILS NAILS TO LSL LEDGER RIM JOIST AND AT 6" OC BTWN GRIDS 4 AND AT 6" OC BTWN GRIDS 4 & 5 5
FORFRAMING FRAMINGAT AT FOR OPENINGS,SEE SEE OPENINGS, 1111 TYP TYP S-561 S-561
DO NOT SPLICE RIM JOIST THIS ZONE
DO NOT SPLICE RIM JOIST THIS ZONE
SEAL
E
L N IA
A
T
No. S3737
A RU C T UR O F OF I CAL
R
REGIST ER K
T
S
ST
HOLDDOWN, DOWN, HOLD TYPOF OF(4) (4)THIS THIS TYP WALLLINE, LINE,SEE SEEPLAN PLAN WALL
EER GIN EN R
FESSIONA PRO L ED RRY J. VOLKE E
05/15/2019 PROJECT
C L = 10'-0" L = 10'-0"
C
L = 21'-6"
C
L = 21'-6"
C C
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
11
SHEARWALL ELEVATION ELEVATION LINE LINE DD SHEARWALL SCALE1/4" 1/4"==1'-0" 1'-0" SCALE
CLIENT
RIM JOIST AND 8D NAILS
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
ISSUED
MARK
55
44
LOUVER FRAME, SAD
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
33
HSS 6X6X3/8 BTWN HSS COLS, TYP AT TOP OF MECH WELL WALL
13 S-566
TYP B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
13 S-563
TOFMECH MECHWELL WELL TOF
6X8 TYP OVER STRONGWALL
SSW24X10
12
"SIMPSON" STRONGWALL, TYP OF (4)
SSW24X10
SSW24X10
SSW24X10 10
TYP
AGENCY
FULL HEIGHT HSS EA SIDE OF STRONGWALL, SEE PLAN
CMSTC16 W/ (25) 0.148X3 1/4" NAILS TO EACH 6X8 OVER STRONG WALL. FILL EVERY OTHER HOLE IN BTWN STRAP WALLS
BEAM, SEE PLAN, TYP
SSW24X10
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
TYP AT HSS AT FLOOR
S-563
S-563
TYP
3'-6"5/8" 3'-5
3'-6" 3'-4"
A
3'-6" 3'-4"
3'-6"5/8" 3'-5 TITLE
22
SHEARWALL ELEVATION ELEVATION LINE LINE FF SHEARWALL
ELEVATIONS SHEARWALL
SCALE1/4" 1/4"==1'-0" 1'-0" SCALE
5/15/2019 4:35:34 PM
SHEET
S-264
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
DATE:
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1
2
3
4
11 S-312 S-312
88 S-566 S-566
14 S-563
4 S-566
6 20 20 S-566 S-566
22 S-312 S-312
SIM
D
5
TOF TOF VARIES VARIES
FLS
ACS
✔
✔
07/03/2019
7
33 S-312 S-312
TYP AT COL
OPH 88 OPH S-566 S-566 TOF TOF VARIES VARIES
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
SEE 4/S-566 LEDGER TO WALL TYP
10 10 S-532 S-532
99 S-532 S-532
OPH OPH 99 S-532 S-532
TYP TYP AT AT INT INT SHEAR SHEAR WALL WALL
TOC TOC 100'-0" 100'-0" TOF TOF 99'-0" 99'-0"
11 S-312 S-312
22 S-312 S-312
33 S-312 S-312
SECTION
1
SCALE SCALE 1/8" 1/8" == 1'-0" 1'-0" SEAL
4
5
6
7
L N IA
T
E
No. S3737
A RU C T UR O F OF I CAL
R
REGIST ER K
3
T
A
2
33 S-312 S-312
S
1
22 S-312 S-312
ST
11 S-312 S-312
EER GIN EN R
FESSIONA PRO L ED RRY J. VOLKE E
05/15/2019 PROJECT
C
88 S-566 S-566
3 S-566
3 S-566
WHERE SHEAR WALL OCCURS
88 OPH OPH S-566 S-566 TOF TOF VARIES VARIES
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
SEE 4/S-566 LEDGER TO WALL TYP
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
TOC TOC 100'-0" 100'-0" TOF TOF 99'-0" 99'-0"
ISSUED
MARK 11 S-312 S-312
22 S-312 S-312
33 S-312 S-312
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
SECTION
2
SCALE SCALE 1/8" 1/8" == 1'-0" 1'-0"
B
1
2
3
4
5
6
7
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 ?00.00.00? LIONAKIS 2017
AGENCY
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
88 S-566 S-566
11 S-312 S-312
99 S-532 S-532
20 20 S-561 S-561
10 10 S-532 S-532
22 S-312 S-312
33 S-312 S-312
88 S-566 S-566
OPH OPH TOF TOF VARIES VARIES
OPH 99 OPH S-532 S-532
77 S-561 S-561
TOC TOC 100'-0" 100'-0" TOF TOF 99'-0" 99'-0" 11 S-312 S-312
A
3
22 S-312 S-312
33 S-312 S-312
SECTION SCALE SCALE 1/8" 1/8" == 1'-0" 1'-0" TITLE
SECTIONS - BUILDING
5/15/2019 4:35:34 PM
SHEET
S-311
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
DATE:
FLS
ACS
✔
✔
07/03/2019
1 1 S-311 S-311
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
AA
BB
B.6 B.6
C C 2 2 S-311 S-311
3 3 S-311 S-311
C.4 C.4
2 2 S-567 S-567
D D
EE
FF
TOF VALLEY TOF VALLEY 121'-9 3/4" 121'-9 3/4"
TOF TOF 123'-2" 123'-2" 1 1 S-566 S-566
6 6 S-566 S-566
D 2 2 S-566 S-566
1 1 S-566 OPH S-566 OPH 6 6 S-567 S-567
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
6 6 S-566 OPH S-566 OPH
6 6 S-567 S-567
2 2 S-566 S-566 OPH OPH TOF TOF 110'-5" 110'-5"
CONSULTANT
10 10 S-532 S-532 TOC TOC 100'-0" 100'-0" TOF TOF 99'-0" 99'-0" 3 3 S-311 S-311
2 2 S-311 S-311
1 1 S-311 S-311
SECTION SECTION
11
SEAL
SCALE 1/8" = 1'-0" SCALE 1/8" = 1'-0"
L N IA
A
E
No. S3737
A RU C T UR O F OF I CAL
R
REGIST ER K
T
S
ST
T
EER GIN EN R
FESSIONA PRO L ED RRY J. VOLKE E
05/15/2019 C
AA
BB
B.6 B.6 3 3 S-311 S-311
2 2 S-566 S-566
C C
TOF VALLEY TOF VALLEY 121'-9 3/4" 121'-9 3/4"
PROJECT
D D
SIM SIM
10 10 S-566 S-566 WALL TO WALL TO I-JOIST I-JOIST
5 5 S-566 S-566
12 10 S-567 S-567
FF
18 OPH 18 S-566 OPH S-566
10 10 S-566 S-566
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
TOF TOF 123'-2" 123'-2"
LOUVER FRAME, SAD
11 11 S-566 S-566
CLIENT 12 12 S-566 S-566 TOF TOF 114'-7" 114'-7"
6 3/4"x36" GLB 6 3/4"x36" GLB
6 3/4"x36" GLB 6 3/4"x36" GLB
FOR TYP FOR TYP HEADERS AT HEADERS AT OPNGS, OPNGS, SEE SEE 11 11 S-561 S-561
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
SIM SIM OPH OPH
12 11 S-566
10 10 S-532 S-532
ISSUED
MARK TOC TOC 100'-0" 100'-0" TOF TOF 99'-0" 99'-0"
3 3 S-311 S-311
22
EE
1 1 S-311 S-311
2 2 S-311 S-311
1 1 S-566 S-566
TOF TOF 110'-7 1/2" 110'-7 1/2"
B
C.4 C.4
18 18 S-566 S-566
2 2 S-311 S-311
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
1 1 S-311 S-311
SECTION SECTION SCALE 1/8" = 1'-0" SCALE 1/8" = 1'-0"
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AA
BB
B.6 B.6
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
3 3 S-311 S-311
TOF VALLEY TOF VALLEY 121'-9 3/4" 121'-9 3/4"
C C 2 2 S-311 S-311
C.4 C.4
D D
EE
FF
1 1 S-311 S-311
AGENCY
5 5 S-566 S-566 TOF TOF 123'-2" 123'-2"
1 1 S-566 S-566
6 6 S-566 S-566
1 1 S-566 S-566
OPH OPH 6 6 S-566 OPH S-566 OPH
6 3/4"x21" GLB 6 3/4"x21" GLB
TOF TOF 110'-7 1/2" 110'-7 1/2"
6 3/4"x21" GLB 6 3/4"x21" GLB
10 10 S-566 S-566
10 10 S-566 S-566 10 10 S-532 S-532
3 3 S-311 S-311
A
2 2 S-311 S-311
2 2 S-566 OPH S-566 OPH TOF TOF 110'-5" 110'-5"
TOC TOC 100'-0" 100'-0" TOF TOF 99'-0" 99'-0" 1 1 S-311 S-311
TITLE
SECTIONS - BUILDING 33
SECTION SECTION SCALE 1/8" = 1'-0" SCALE 1/8" = 1'-0"
SHEET
5/15/2019 4:35:37 PM
017294 ?00.00.00? LIONAKIS 2017
S-312
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123 STD LAP LAP STD
d
0 1/4" 1/2"
STD STD HOOK, HOOK,
REVIEWED FOR
STD LAP LAP STD
SJ SPACING SPACING AS AS REQ REQ (NOT (NOT SHOWN SHOWN ELSEWHERE ELSEWHERE FOR FOR CLARITY) CLARITY) SJ
TYP TYP
SS
DJ SPACING SPACING DJ TYP TYP
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
D
D
11
D
66
INC:
d
3" MIN MIN TYP TYP 3" .
.
.
.
.
BEND
5" (1/2") (1/2") 5"
10" (1") (1") 10"
#6 #6
6xd 6xd
6" (1/2") (1/2") 6"
6" (1/2") (1/2") 6"
12" (1") (1") 12"
.
DJ DJ
DJ DJ
6xd 6xd
8" (1/2") (1/2") 8"
8" (1/2") (1/2") 8"
16" (1") (1") 16"
#9 #9
8xd 8xd
12" (1/2") (1/2") 12"
11" (1/2") (1/2") 11"
20" (1") (1") 20"
#10 #10
8xd 8xd
13" (1/2") (1/2") 13"
12" (1/2") (1/2") 12"
22" (1") (1") 22"
#11 #11
8xd 8xd
14" (1/2") (1/2") 14"
13" (1/2") (1/2") 13"
24" (1") (1") 24"
#14 #14
10xd 10xd
21" (1 (1 1/2") 1/2") 21"
17" (1 (1 1/2") 1/2") 17"
31" (2 (2 1/2") 1/2") 31"
#18 #18
10xd 10xd
27" (2") (2") 27"
23" (2") (2") 23"
41" (3 (3 1/2") 1/2") 41"
DJJ D MAX 11 MAX 66 SJ SJ
DJ DJ SJ SJ DJ
#8 #8
DETAILING DETAILING DIMENSION DIMENSION
SJ SJ DJ DJ
W
TYP REBAR BENDS AND HOOKS S-_032000_T001A S-_032000_T001A 140127 140127
SCALE: NTS NTS SCALE:
DJ DJ
DJ DJ
13
S-_033000_T002A S-_033000_T002A 140127 140127
SCALE: NTS NTS SCALE:
135 DEG DEG HOOK HOOK 135
W (TOL (TOL +/-) +/-) W
(TOL +/-) +/-) LL (TOL
W (TOL (TOL +/-) +/-) W
W (TOL (TOL +/-) +/-) W
(TOL +/-) +/-) LL (TOL
#3 #3
4xd 4xd
1/4" (1/2") (1/2") 22 1/4"
3/4" (1/2") (1/2") 33 3/4"
1/2" (1") (1") 33 1/2"
4" (1/2") (1/2") 4"
3" (1/2") (1/2") 3"
#4 #4
4xd 4xd
3" (1/2") (1/2") 3"
4" (1/2") (1/2") 4"
1/2" (1") (1") 44 1/2"
5" (1/2") (1/2") 5"
3" (1/2") (1/2") 3"
TYP INT SLAB JOINT LAYOUT S-_033000_T024A S-_033000_T024A 170517 170517
SCALE: NTS NTS SCALE:
#6 #6
6xd 6xd
6" (1/2") (1/2") 6"
6" (1/2") (1/2") 6"
12" (1") (1") 12"
9" (1/2") (1/2") 9"
1/4" (1/2") (1/2") 55 1/4"
#7 #7
6xd 6xd
7" (1/2") (1/2") 7"
7" (1/2") (1/2") 7"
14" (1") (1") 14"
10" (1/2") (1/2") 10"
6" (1/2") (1/2") 6"
#8 #8
6xd 6xd
8" (1/2") (1/2") 8"
8" (1/2") (1/2") 8"
16" (1") (1") 16"
11" (1/2") (1/2") 11"
7" (1/2") (1/2") 7"
D
FTG REINF REINF FTG STD HOOK HOOK EA EA STD REBAR, TYP TYP REBAR,
D MIN MIN D
2xS MIN MIN 2xS
TOF TOF
D
D L
STD LAP LAP STD
#4 EF EF FTG FTG #4 AT EA EA STEP STEP AT
S-_032000_T002A S-_032000_T002A 140127 140127
SCALE: NTS NTS SCALE:
3"
T
PLAN
A
FORMED FORMED SURFACE SURFACE
d
A
CONC SLAB SLAB O/ O/ CONC SUB-BASE, SUB-BASE, SEE PLAN PLAN SEE
TOC TOC SEE PLAN PLAN SEE TOF TOF SEE PLAN PLAN SEE
A RU C T UR O F OF I CAL
05/15/2019 PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
TURN DOWN DOWN TURN SLAB EDGE, EDGE, SLAB TYP TYP
6" 6"
11
T
E
No. S3737
2xS MIN MIN 2xS
ADDL SLAB SLAB BAR BAR CONT CONT W/ W/ STD STD HOOK HOOK ADDL EA END END WHERE WHERE DEPRESSION DEPRESSION IS IS EQUAL EQUAL EA TO SLAB SLAB THICKNESS THICKNESS "d" "d" OR OR GREATER GREATER TO
NOTES: NOTES: 1. D D == DEPTH DEPTH FTG, FTG, S S == STEP STEP AT AT FTG FTG (1'-6" (1'-6" MAX). MAX). 1. 2. TWO TWO STEPS STEPS SHOWN. SHOWN. SINGLE SINGLE STEPS STEPS OR OR MULTIPLE MULTIPLE STEPS STEPS SIMILAR. SIMILAR. 2. 3. SEE SEE PLANS PLANS FOR FOR FOOTING FOOTING SIZE SIZE AND AND REINFORCING. REINFORCING. 3. 4. VERT VERT // TIE TIE // DOWEL DOWEL REINF REINF NOT NOT SHOWN SHOWN FOR FOR CLARITY. CLARITY. PROVIDE PROVIDE TYP TYP TO TO BOT BOT OF OF FOOTING FOOTING & & STEP. STEP. 4.
6
FILL BLOCKOUT BLOCKOUT W/ W/ CONC CONC FILL (SAME MIX MIX AS AS SLAB SLAB O/ O/ SUBSUB(SAME BASE) AFTER AFTER ENTIRE ENTIRE BASE) STRUCTURAL SYSTEM SYSTEM IS IS IN IN STRUCTURAL PLACE PLACE
22
STEPPED BOTTOM
TYP REBAR HOOP, STIRRUP, TIE HOOKS & BENDS
4"
d
FTG REINF REINF FTG
TOC TOC SEE PLAN PLAN SEE DEPRESSION, DEPRESSION, SEE PLAN PLAN SEE
4"
S
DETAILING DIMENSION
A
STD HOOK HOOK STD EA REBAR, REBAR, EA TYP TYP
135 DEG HOOK
CONC SLAB SLAB & & SUB-BASE, SUB-BASE, CONC SEE PLAN PLAN SEE SLAB REINF, REINF, SEE SEE PLAN PLAN SLAB
HOOK WHERE WHERE DEPRESSION DEPRESSION HOOK IS 6" 6" OR OR GREATER GREATER IS
S
D
DETAILING DIMENSION
L
4d 2 1/2" MIN
.
.
DETAILING DIMENSION
dd
NOTES: NOTES: 1. D D == MINIMUM MINIMUM FINISHED FINISHED INSIDE INSIDE BEND BEND DIA, DIA, dd == NOMINAL NOMINAL REBAR REBAR DIAMETER DIAMETER 1. 2. TOL TOL == TOLERANCE TOLERANCE (PER (PER ACI ACI 117) 117) 2.
2
R CL 3"
.
90 DEG HOOK
.
180 DEG HOOK
dd
IN M 3"
dd
6d
W W
MATCH MATCH FTG BOT BOT FTG REINF REINF
D D
DJ OR OR SJ, SJ, SEE SEE DJ PLAN & & PLAN TYPICAL TYPICAL DETAILS DETAILS
CONC SLAB SLAB O/ O/ CONC SUB-BASE SUB-BASE
MATCH SLAB SLAB REINF REINF MATCH
W W
FESSIONA PRO L ED RRY J. VOLKE E
A
W W
A
STD LAP LAP STD
PLAN
C
D D
SEAL
S
d
STD LAP LAP STD
CONT FTG FTG TOP TOP REINF REINF CONT
ADDL SLAB SLAB BAR BAR CONT CONT W/ W/ ADDL STD HOOK HOOK EA EA END END STD
DEPRESSED DEPRESSED SLAB SLAB
STEPPED TOP AND BOTTOM
.
BASE PLATE PLATE BASE
ST
2xS MIN MIN 2xS
TYP TYP
BEND .
INDICATES INDICATES OPTIONAL OPTIONAL ROUND ROUND BLOCKOUT BLOCKOUT
COL, SEE SEE PLAN PLAN COL,
STD LAP LAP STD
12d for for #6,7,8 #6,7,8 12d 6d for for #3,4,5 #3,4,5 6d
SECTION AT SLAB EDGE CONDITION
ADDL SLAB SLAB BAR BAR xx 4'-0" 4'-0" AT AT EA EA CORNER CORNER AT AT ADDL MID-DEPTH OF OF SLAB SLAB WHERE WHERE DEPRESSION DEPRESSION MID-DEPTH IS EQUAL EQUAL TO TO SLAB SLAB THICKNESS THICKNESS "d" "d" OR OR GREATER GREATER IS
BEND WHERE WHERE BEND SLAB EDGE EDGE SLAB OCCURS OCCURS
S
4" (1/2") (1/2") 4"
EMBED VERTS VERTS EMBED IN EPOXY EPOXY IN (NO TENSION TENSION (NO TEST) TEST) EDGE OF OF SLAB SLAB WHERE WHERE EDGE OCCURS, SEE SEE PLAN PLAN OCCURS,
S
6" (1/2") (1/2") 6"
S
3/4" (1") (1") 55 3/4"
D
1/2" (1/2") (1/2") 44 1/2"
TOF TOF SEE PLAN PLAN SEE
EER GIN EN R
3/4" (1/2") (1/2") 33 3/4"
CLR 3"
4xd 4xd
FTG REINF REINF FTG
IN DM
#5 #5
MATCH FTG FTG T&B T&B REINF REINF MATCH
3"
TOC TOC SEE PLAN PLAN SEE
TOF TOF
TYP TYP
S
90 DEG DEG HOOK HOOK 90
CONSULTANT
IN M 3" TYP
180 DEG DEG HOOK HOOK 180
DIA DIA D D
PLAN
B
B
STD LAP LAP STD
REBAR REBAR SIZE SIZE
SEE SECTION SECTION AT AT SEE INTERIOR CONDITION CONDITION INTERIOR FOR ADDL ADDL INFO INFO FOR
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
#4 @ @ 16" 16" OC OC EW EW #4 (2) MIN MIN (2)
DJ OR OR CJ CJ AT AT INT INT DJ DOOR DOOR
NOTES: NOTES: 1. DJ DJ SPACING SPACING TO TO BE BE 36'-0" 36'-0" MAX MAX EW. EW. ALIGN ALIGN WITH WITH COLUMN COLUMN SPACING SPACING OR OR MODULE MODULE WHERE WHERE OCCURS. OCCURS. 1. 2. SJ SJ SPACING SPACING TO TO BE BE 12'-0" 12'-0" MAX MAX EW. EW. SPACE SPACE EQUALLY EQUALLY BTWN BTWN DJ'S DJ'S AND AND SLAB SLAB EDGES. EDGES. 2. 3. PROVIDE PROVIDE SJ SJ ALIGNED ALIGNED W/ W/ CENTERLINE CENTERLINE OF OF COLUMNS COLUMNS WHERE WHERE NO NO DJ DJ OCCURS. OCCURS. 3. 4. SEE SEE PLANS PLANS AND AND DETAILS DETAILS FOR FOR CONDITION CONDITION AT AT EDGE EDGE OF OF SLAB. SLAB. 4. 5. LENGTH LENGTH TO TO WIDTH WIDTH RATIO RATIO OF OF ANY ANY INDIVIDUAL INDIVIDUAL ELEMENT ELEMENT NOT NOT TO TO EXCEED EXCEED 11 1/2 1/2 TO TO 1, 1, TYP. TYP. 5. 6. PROVIDE PROVIDE JOINTS JOINTS PARALLEL PARALLEL AND AND PERPENDICULAR PERPENDICULAR TO TO BLDG BLDG COL COL LINES, LINES, TYP TYP UNO. UNO. 6.
TYP CONC FOOTING / WALL REINFORCING AT CORNERS AND INTERSECTIONS
5
SJ SJ
PROVIDE DIAG DIAG JOINTS JOINTS AT AT NONNONPROVIDE RECTANGULAR ELEMENTS ELEMENTS PERPENDICULAR PERPENDICULAR RECTANGULAR TO EDGE EDGE TO
DOUBLE CURTAIN
NOTES: NOTES: 1. D D == MINIMUM MINIMUM FINISHED FINISHED INSIDE INSIDE BEND BEND DIA, DIA, dd == NOMINAL NOMINAL REBAR REBAR DIAMETER DIAMETER 1. 2. TOL TOL == TOLERANCE TOLERANCE (PER (PER ACI ACI 117) 117) 2.
JOINTS AT AT ALL ALL REREJOINTS ENTRANT CORNERS CORNERS ENTRANT IF OFFSET OFFSET IF EXCEEDS 11 IN IN 6, 6, EXCEEDS PLACE JOINTS JOINTS PLACE PARALLEL TO TO TYP TYP PARALLEL JOINT DIRECTION DIRECTION JOINT
DJ DJ
INTERSECTION INTERSECTION
D
CORNER CORNER
90 DEG HOOK
1
.
TYP TYP
180 DEG HOOK
14" (1") (1") 14"
SJ SJ
DJ
7" (1/2") (1/2") 7"
SJ SJ
SJ
7" (1/2") (1/2") 7"
LL
18 "M IN
6xd 6xd
STD LAP LAP STD
.
12d
#7 #7
D
.
L N IA
5" (1/2") (1/2") 5"
DJ OR OR SJ, SJ, SEE SEE DJ PLAN & & PLAN TYPICAL TYPICAL DETAILS DETAILS
R
6xd 6xd
STD STD HOOK, HOOK,
EDGE OF OF SLAB, SLAB, EDGE SEE PLAN PLAN SEE
SJ
#5 #5
4d 4d 1/2" MIN MIN 22 1/2"
DJ
8" (1") (1") 8"
DJ DJ
DJ
1/2" (1/2") (1/2") 44 1/2"
DJ DJ
DJ
4" (1/2") (1/2") 4"
DJ DJ
3"
EJ OR OR DJ DJ AT AT EXT EXT EJ DOOR, SAD SAD DOOR,
DJ
6xd 6xd
DJ
#4 #4
DJ DJ
SINGLE CURTAIN
DJ
6" (1") (1") 6"
DJ
4" (1/2") (1/2") 4"
SJ
3" (1/2") (1/2") 3"
SJ SJ
SJ
6xd 6xd
SJ
#3 #3
.
W (TOL (TOL +/-) +/-) W
.
(TOL +/-) +/-) LL (TOL
CORNER CORNER
CMU OR OR CONC CONC WALL WALL CMU SEE TYP TYP COL COL SEE BLOCKOUT BLOCKOUT
SJ SJ
.
W (TOL (TOL +/-) +/-) W
INTERSECTION INTERSECTION
.
DIA DIA D D
CORNER CORNER
W D
REBAR REBAR SIZE SIZE
DETAILING DETAILING DIMENSION DIMENSION
DJ SPACING TYP
90 DEG DEG HOOK HOOK 90
d
180 DEG DEG HOOK HOOK 180
d
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
3"
REGIST ER K
OFFSET
.
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
6" MIN MIN 6"
SECTION AT INTERIOR CONDITION
TYP STEPPED FOOTING
14
S-_033000_T003A S-_033000_T003A 150630 150630
SCALE: NTS NTS SCALE:
STD LAP LAP STD
TYP DEPRESSION IN CONC SLAB S-_033000_T019A S-_033000_T019A 140127 140127
SCALE: NTS NTS SCALE:
18
TYP COL BLOCKOUT S-_033000_T042A S-_033000_T042A 150807. Q2 Q2 150807.
SCALE: NTS NTS SCALE:
SEALANT SEALANT
75 75
81 108 108 81
93 93
124 105 105 140 140 118 118 157 157 131 131 175 175 124
BOT 22 22 BOT
29 29
29 29
38 38
36 36
48 48
43 43
57 57
63 63
84 84
72 72
95 95
81 108 108 91 91 81
TOP 25 22 TOP
29 33
29 33
39 43
36 41
48 54
44 49
58 65
63 71
84 94
72 81
96 107
81 121 108 102 92 136 122 114 102 151 135 91
BOT 19 17 BOT
23 25
23 25
30 33
28 31
37 42
34 37
45 50
49 54
65 72
56 62
74 83
63 70
83 93
71 79
121 101 101 134 134 121
94 105
BEVELED KEY KEY FORMED FORMED W/ W/ 2x4, 2x4, BEVELED PROVIDE ONE ONE KEY KEY FOR FOR EA EA 12" 12" PROVIDE OF FTG FTG WIDTH WIDTH OF
78 116 104 87
SCALE: NTS NTS SCALE:
S-_032000_T003A S-_032000_T003A 150107. Q2 Q2 150107.
ALL REINF REINF ALL CONT CONT THROUGH JT JT THROUGH
1'-0" 1'-0"
1'-0" 1'-0"
SMOOTH DOWELS DOWELS @ @ 12" 12" OC, OC, SMOOTH PLACE PERPENDICULAR PERPENDICULAR TO TO PLACE JT & & HOLD HOLD IN-PLACE IN-PLACE W/ W/ JT CHAIRS THAT THAT PERMIT PERMIT HORIZ HORIZ CHAIRS MOVEMENT OF OF DOWEL DOWEL MOVEMENT
CONC SLAB SLAB & & REINF, REINF, CONC SEE PLAN PLAN SEE
COAT ONE ONE END END TO TO COAT PREVENT BOND BOND OR OR USE USE PREVENT PLASTIC DOWEL DOWEL SLEEVES SLEEVES PLASTIC
2ND POUR POUR 2ND
#4 @ @ 16" 16" OC OC EW EW #4
TYP CONSTRUCTION JOINT AT GRADE BEAM/CONTINUOUS FOOTING S-_033000_T001A S-_033000_T001A 140127 140127
.
#4 @ @ 16" 16" OC OC #4 AT PERIMETER PERIMETER AT
.
SEALANT PER PER SEALANT SPEC SPEC
2" CLR CLR 2" TYP TYP
AT WALL WALL PROVIDE PROVIDE REBAR REBAR AT W/ STD STD HOOK, HOOK, EXTEND EXTEND W/ TO FAR FAR SIDE SIDE OF OF WALL, WALL, MATCH MATCH TO SIZE & & SPACING SPACING OF OF SLAB SLAB REINF REINF SIZE
CONC SLAB SLAB & & SUB-BASE, SUB-BASE, CONC SEE PLAN PLAN SEE
SLAB REINF REINF CONT CONT THROUGH THROUGH SLAB JT -- DO DO NOT NOT SPLICE SPLICE WITHIN WITHIN JT 2'-0" OF OF JT JT 2'-0"
#4 @ @ 16" 16" OC OC EW EW #4 TOP & & BOTTOM BOTTOM TOP
D/3
S-_033000_T009A S-_033000_T009A 150107. Q2 Q2 150107.
SCALE: NTS NTS SCALE:
CURB WIDTH WIDTH CURB 1/2" 11 1/2" CLR, TYP TYP CLR,
d
#4 CONT CONT AT AT EA EA EDGE EDGE #4 #4 MATCH MATCH TYP TYP SLAB SLAB REINF REINF #4 SPACING (18" (18" OC OC MAX) MAX) SPACING
EMBED (2/3 (2/3 xx d) d) IN IN EPOXY, EPOXY, 5" 5" EMBED MAX, NO NO TENSION TENSION TEST TEST MAX,
(E) REINF REINF (E)
CJ CJ
CURBS WIDER THAN 8" & LESS THAN 24" 12 ANCHOR ANCHOR DIA, DIA, MIN MIN 12
(E) CONC CONC SLAB SLAB & & (E) REINF, SEE SEE PLAN PLAN REINF,
(2/3 xx d) d) EMBED EMBED IN IN EPOXY, EPOXY, 5" 5" MAX MAX (2/3
S-_033000_T025A S-_033000_T025A 150630 150630
2 21/64"
2 21/64"
#4 @ @ 16" 16" OC OC EW EW #4
d
SJ - SHRINKAGE JOINT
CURB WIDTH, WIDTH, 33 1/2" 1/2" MIN MIN CURB
ANCHORAGE, SEE SEE ANCHORAGE, EQUIP DETAIL DETAIL EQUIP
12" MAX 4" MIN
SLAB REINF REINF CONT CONT SLAB THROUGH JOINT JOINT THROUGH
TYP JOINTS AT CONC SLAB
STD LAP, LAP, TYP TYP STD
2" CLR CLR 2"
#4 CONT CONT #4 6"
6"
(E) CONC CONC SLAB SLAB (E) & SUB-BASE, SUB-BASE, & SEE PLAN PLAN SEE
1 1/2" CLR
SAWCUT, USE USE EARLY EARLY ENTRY ENTRY SAWCUT, SAW WITH WITH ANTI-RAVEL ANTI-RAVEL SKID SKID SAW PLATE PLATE
NOTES: NOTES: 1. D D == DEPTH DEPTH SLAB, SLAB, SEE SEE PLANS PLANS 1. 2. SMOOTH SMOOTH DOWELS DOWELS SHALL SHALL HAVE HAVE SAW SAW CUT CUT ENDS ENDS -- DO DO NOT NOT SHEAR. SHEAR. USE USE 1/2" 1/2" DIA DIA FOR FOR D D UP UP TO TO 4", 4", 2. 3/4" DIA DIA FOR FOR D D UP UP TO TO 6", 6", 1" 1" DIA DIA FOR FOR D D UP UP TO TO 8", 8", 11 1/4" 1/4" DIA DIA FOR FOR D D UP UP TO TO 10", 10", & & 11 1/2" 1/2" DIA DIA FOR FOR D D 3/4" OVER 10". 10". OVER 3. SAWCUTTING SAWCUTTING AND AND TOOLING TOOLING SHALL SHALL OCCUR OCCUR AS AS SOON SOON AS AS CONCRETE CONCRETE IS IS HARD HARD ENOUGH ENOUGH SO SO THAT THAT 3. IT WILL WILL NOT NOT BE BE TORN TORN OR OR DAMAGED DAMAGED AND AND BEFORE BEFORE INITIAL INITIAL SHRINKAGE SHRINKAGE HAS HAS STARTED. STARTED. IT
SCALE: NTS NTS SCALE:
AGENCY
TYP CURB AT CONC SLAB
(E) CONC CONC SLAB SLAB (E) & SUB-BASE, SUB-BASE, & SEE PLAN PLAN SEE
ISOLATED PAD
B
SEALANT SEALANT
D/4, 1" MAX
STD HOOK HOOK STD SKEWED, TYP TYP SKEWED,
EXPANSION JOINT JOINT EXPANSION
CJ - CONSTRUCTION JOINT 1/8" to to 1/4" 1/4" 1/8"
NOTES: NOTES: 1. SEE SEE OTHER OTHER CONSTRUCTION CONSTRUCTION DOCUMENTS DOCUMENTS FOR FOR CURB CURB LOCATIONS, LOCATIONS, DIMENSIONS, DIMENSIONS, INSERTS INSERTS 1. & SHAPES. SHAPES. & 2. SEE SEE TYPICAL TYPICAL DETAILS DETAILS FOR FOR CURB CURB DIMENSIONS DIMENSIONS RELATIVE RELATIVE TO TO STUD STUD WALLS. WALLS. 2.
2" CLR CLR 2"
2"
2" CLR CLR -- STOP STOP SLAB SLAB REINF REINF 2" WHERE WALL WALL OCCURS OCCURS WHERE
(2) #4 #4 CONT CONT (2)
ANCHORAGE, SEE SEE ANCHORAGE, EQUIP DETAIL DETAIL EQUIP
12" MAX 4" MIN
CONC SLAB SLAB & & REINF, REINF, CONC SEE PLAN PLAN SEE
D/3
D
12 ANCHOR ANCHOR DIA, DIA, MIN MIN 12
STD LAP LAP STD
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
CURBS 8" WIDE OR LESS
19
#4 @ @ 16" 16" OC OC AT AT PERIMETER PERIMETER #4
5/15/2019 4:35:39 PM
#4 MATCH MATCH TYP TYP SLAB SLAB #4 REINF SPACING SPACING REINF (18" OC OC MAX) MAX) (18"
NOTE: NOTE: PAD MAY MAY BE BE POURED POURED PAD MONOLITHICALLY WITH WITH SLAB SLAB MONOLITHICALLY AT CONTRACTORS CONTRACTORS OPTION OPTION AT
STD LAP LAP STD
12
.
CJ AS AS NEEDED NEEDED CJ
FORM KEY KEY FORM
ADDL SLAB SLAB REBAR REBAR ADDL EA SIDE SIDE OF OF JOINT JOINT EA
CONC SLAB SLAB & & SUBSUBCONC BASE, SEE SEE PLAN PLAN BASE,
CURB WIDTH, WIDTH, 33 1/2" 1/2" MIN MIN CURB .
REINF, SEE SEE PLAN PLAN REINF,
ANCHORAGE, SEE SEE ANCHORAGE, EQUIP DETAIL DETAIL EQUIP
TYP PAD, UNO
A
TOOLED EDGES EDGES AT AT TOOLED EXTERIOR SLABS SLABS EXTERIOR
D/6 D/6
2"
A
CONC SLAB SLAB & & SUB-BASE SUB-BASE CONC SEE PLAN PLAN SEE
CJ CJ
INDICATES CONC CONC OR OR INDICATES MASONRY WALL WALL MASONRY WHERE OCCURS OCCURS WHERE
SCALE: NTS NTS SCALE:
STD LAP, LAP, TYP TYP STD
MATCH WALL WALL MATCH REINF CLEARANCE CLEARANCE REINF
ELEVATION
7
2" CLR CLR 2"
MANAGEMENT
DJ - DOWEL JOINT 1ST POUR POUR 1ST
12" MAX
CURBS WIDER THAN 8" & LESS THAN 24" 12 ANCHOR ANCHOR DIA, DIA, MIN MIN 12
D/3
3
TYP CONCRETE REBAR LAP SPLICE LENGTHS (INCHES)
STD LAP, LAP, TYP TYP STD
D
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
NOTES: NOTES: 1. REINFORCING REINFORCING BEING BEING LAP LAP SPLICED SPLICED MUST MUST MEET MEET ONE ONE OF OF THE THE FOLLOWING FOLLOWING CONDITIONS: CONDITIONS: 1. A. CASE CASE 1: 1: THE THE CLEAR CLEAR SPACING SPACING OF OF THE THE BARS BARS BEING BEING SPLICED SPLICED IS IS NOT NOT LESS LESS THAN THAN ONE ONE BAR BAR A. DIAMETER, CLEAR CLEAR COVER COVER IS IS NOT NOT LESS LESS THAN THAN ONE ONE BAR BAR DIAMETER, DIAMETER, AND AND STIRRUPS STIRRUPS OR OR DIAMETER, TIES THROUGHOUT THROUGHOUT THE THE SPLICE SPLICE LENGTH. LENGTH. TIES B. CASE CASE 2: 2: THE THE CLEAR CLEAR SPACING SPACING OF OF THE THE BARS BARS BEING BEING SPLICED SPLICED IS IS NOT NOT LESS LESS THAN THAN TWO TWO BAR BAR B. DIAMETERS AND AND THE THE CLEAR CLEAR COVER COVER IS IS NOT NOT LESS LESS THAN THAN ONE ONE BAR BAR DIAMETER. DIAMETER. DIAMETERS C. FOR FOR ALL ALL OTHER OTHER CASES, CASES, MULTIPLY MULTIPLY THE THE SPLICES SPLICES SHOWN SHOWN BY BY 1.5. 1.5. C. 2. THE THE ABOVE ABOVE VALUES VALUES ARE ARE FOR: FOR: UNCOATED UNCOATED REINFORCEMENT, REINFORCEMENT, GRADE GRADE 60 60 REBAR, REBAR, CLASS CLASS B. B. 2. 3. TOP TOP BARS BARS ARE ARE HORIZONTAL HORIZONTAL REINFORCEMENT REINFORCEMENT WITH WITH MORE MORE THAN THAN 12" 12" OF OF NEW NEW CONCRETE CONCRETE 3. PLACED BELOW BELOW THE THE BAR. BAR. BOTTOM BOTTOM BARS BARS ARE ARE ALL ALL OTHER OTHER HORIZONTAL HORIZONTAL OR OR VERTICAL VERTICAL PLACED REINFORCEMENT. REINFORCEMENT.
1/2" 11 1/2"
TYP TYP
12" MAX
56 56
12" MAX
62 62
12" MAX
47 47
STD LAP LAP STD
d
50 50
#4, MATCH MATCH TYP TYP #4, SLAB REINF REINF SLAB SPACING SPACING (18" OC OC MAX) MAX) (18"
#4 VERT VERT MATCH MATCH TYP TYP SLAB SLAB #4 REINF SPACING SPACING (18" (18" OC OC REINF MAX) MAX) CJ CJ
d
38 38
STOP SLAB SLAB REINF REINF AT AT STOP JT JT
1 1/2" CLR
38 38
D
NWC LWC LWC NWCLWC NWCLWCNWCLWC NWCLWCNWCLWC NWCLWC NWC NWCLWC LWCNWCLWC NWCLWC NWCLWC NWCLWCNWCLWC NWCLWCNWCLWC NWCLWC NWC TOP 28 28 TOP
CONC SLAB SLAB & & SUB-BASE, SUB-BASE, CONC SEE PLAN PLAN SEE
PLAN
CJ AS AS NEEDED NEEDED CJ
1 1/2" CLR
#11 #11
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
#4 CONT CONT AT AT EA EA EDGE EDGE #4
FORM JOINT JOINT AND AND APPLY APPLY FORM FORM RELEASE RELEASE AGENT AGENT FORM
3" CLR
#10 #10
DATE 01/04/2019 5/17/2019
d
#9 #9
MARK
1/2" 11 1/2" CLR, TYP TYP CLR,
REINF, SEE SEE PLAN PLAN REINF,
D/2 D/2
#8 #8
2" CLR CLR 2" TYP TYP
12" MAX 4" MIN
EQ
#7 #7
EQ
5,000 4,000
#6 #6
EQ
B
#5 #5
CONC SLAB SLAB & & CONC SUB-BASE SEE SEE SUB-BASE PLAN PLAN
AS AN AN ALTERNATE, ALTERNATE, SAW SAW CUT CUT AS OVER DOWEL DOWEL PER PER TYP TYP OVER SHRINKAGE JOINT JOINT (SJ) (SJ) SHRINKAGE DETAIL INSTEAD INSTEAD OF OF DETAIL FORMED JOINT JOINT FORMED
ISSUED
CURB WIDTH WIDTH CURB
(2) #4 #4 CONT CONT (2)
.
.
AT WALL WALL PROVIDE PROVIDE DOWEL DOWEL AT W/ STD STD HOOK, HOOK, EXTEND EXTEND W/ TO FAR FAR SIDE SIDE OF OF WALL WALL TO ADDL SLAB SLAB REBAR REBAR ADDL EA SIDE SIDE OF OF JOINT JOINT EA
EQ
3,000 3,000
#4 #4
FTG DEPTH SEE PLAN
f'c f'c (psi) (psi)
#3 #3
TOOLED EDGES EDGES AT AT TOOLED EXTERIOR SLABS SLABS EXTERIOR
INDICATES CONC CONC OR OR INDICATES MASONRY WALL WALL MASONRY WHERE OCCURS OCCURS WHERE
EQ
FTG WIDTH SEE PLAN
EQ
MATCH WALL WALL MATCH REINF CLEARANCE CLEARANCE REINF
CLEAN, ROUGHEN ROUGHEN SURFACE SURFACE CLEAN, & APPLY APPLY BONDING BONDING AGENT AGENT &
TITLE
DETAILS - TYPICAL CONCRETE
EMBED (2/3 (2/3 xx d) d) IN IN EPOXY, EPOXY, 5" 5" EMBED MAX, NO NO TENSION TENSION TEST TEST MAX,
(E) REINF REINF (E)
CURBS 8" WIDE OR LESS C
PAD AT EXISTING SLAB NOTES: NOTES: 1. SEE SEE CONSTRUCTION CONSTRUCTION DOCUMENTS DOCUMENTS FOR FOR CURB CURB LOCATIONS, LOCATIONS, DIMENSIONS, DIMENSIONS, INSERTS INSERTS & & SHAPES. SHAPES. 1. 2. SEE SEE TYPICAL TYPICAL DETAILS DETAILS FOR FOR CURB CURB DIMENSIONS DIMENSIONS RELATIVE RELATIVE TO TO STUD STUD WALLS. WALLS. 2.
16
TYP HOUSEKEEPING PADS SCALE: NTS NTS SCALE:
S-_033000_T022A S-_033000_T022A 140127 140127
20
TYP CURB AT (E) CONC SLAB SCALE: NTS NTS SCALE:
S-_033000_T007A S-_033000_T007A 150107. Q2 Q2 150107.
SHEET
S-531
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
W
FLS
ACS
✔
✔
07/03/2019
GRADE LINE
. .
EXCAVATE TRENCH & BACKFILL PER SPECS PIPE
BOT OF CONT OR SPREAD FTG
D
2
ABOVE FOOTING
WHERE PIPES INTERSECT REINF AT BOTTOM OF FTG DEPTH D, STEP FTG TO MAINTAIN PIPES IN AREA SHOWN
.
4" MIN
PIPE, TYP
2" 2" MIN MIN CLR CLR TO TO REINF, REINF, TYP TYP
.
4" 4" MIN MIN
.
.
D D
1 2
S S
D MIN
TOC SEE PLAN
SLAB REINF, SEE PLAN
CONSULTANT
CJ #4 VERTS W/ STD HOOK SKEWED MATCH SLAB REINF SPACING
FTG REINF, SEE PLAN
TYP PIPE ADJACENT TO FOOTING
5
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
TOF SEE PLAN
SEE PLAN
NOTES: 1. W = WIDTH FTG, D = DEPTH FTG. 2. TRENCHING LIMITATIONS ARE SAME FOR BOTH FACES OF FOOTING. 3. MAINTAIN LIMITS SHOWN FOR WIDER OR SHALLOWER FTG BEYOND, WHERE OCCURS. 4. PIPE AS NOTED SHALL REFER TO: PIPES, DUCTS, CONDUITS, ETC.
.
.
SLEEVE / WRAP, TYP
CONC SLAB & SUB-BASE, SEE PLAN
SEE SEE PLAN PLAN
FOOTING, SINGLE STEP SHOWN, MULTIPLE STEP SIM
1
FOR DEEPER TRENCHES, SEE TYP DET TO STEP CONT FTG OR DROP PAD FTG TO MAINTAIN LIMITS SHOWN (ALTERNATE: WITH APPROVAL OF GEOTECHNICAL ENGINEER, FILL WITH CONTROLLED LOW STRENGTH MATERIAL PRIOR TO PLACING FTG)
STEP TOP & BOT OF FTG PER TYP DETAIL
PAVEMENT, WHERE OCCURS FIN GR, WHERE OCCURS
6" 6" MIN MIN
1
RECESS CONC CURB PER "TYP GYP BOARD ATTACHMENT AT CURB" DETAIL #4 CONT
AB, SEE SCHED ALIGN
3" 3" CLR CLR
9" 9" MIN MIN
D D S S
NO TRENCHES ADJACENT TO FACE OF FTG BELOW THIS LINE
2
D/2 MIN
WOOD STUD WALL, SEE PLAN
CL STUD, AB & FTG
4" MIN
2" MIN
GRID
SP, SEE PLAN
TOF SEE PLAN D D
2" 2" MIN MIN
D D
. .
FOS
1'-0" 1'-0" MIN MIN
4" 4" MIN MIN
.
.
2" MIN CLR TO REINF, TYP
TOF
2" MIN CLR TO REINF, TYP TOF
✔
DATE:
1'-6" MIN
FACE OF FTG
TOF IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
SS
2xW 3'-0" MIN
FOOTING WALL
2" 2" MIN MIN
BOT OF SLAB
REVIEWED FOR
WHERE PIPES INTERSECT REINF AT TOP OF FTG DEPTH D, STEP FTG TO PASS PIPES ABOVE FTG 2" 2" MIN MIN
0 1/4" 1/2"
SLEEVE / WRAP, TYP PIPE, TYP
INC:
S-_033000_T015A 150623
SCALE: NTS
D MIN
DETAIL
9
S-_033000_C021A 140127. Q2
SCALE: NTS
STEP BOT OF FTG PER TYP DETAIL
PROJECT
TEHAMA CENTER STUDENT SERVICES
2"
3" 3" CLR CLR
SEE SEE PLAN PLAN
CJ
CLIENT
SEE PLAN
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
d
DETAIL 10
LARGEST ADJACENT d d .
d
d
S-_033000_C030A 140127. Q2
SCALE: NTS
ISSUED
1 5/256" 1 5/256"
d
CLR CLR MIN MIN SEE SEE PLANS PLANS TYP TYP
11 1/2" 1/2" CLR CLR TYP TYP
MAKE SAME DEPTH WHEN SPACING IS LESS THAN D, NO STEPS PERMITTED
770 DIAMOND AVE RED BLUFF, CA 96080
#4 VERTS W/ STD HOOK SKEWED, MATCH SLAB REINF SPACING
BELOW SLAB
LARGER ADJACENT d
BELOW FOOTING
MARK
TYP PIPE CROSSING FOOTINGS S-_033000_T016A 150623
L 3x LARGER ADJACENT d
MIN
EQ
EQ E
ANCHOR ROD HOLES
EQ
5/16
E E
REINF
HSS COL, SEE PLAN
SLAB/WALL - SPACING 3d & GREATER LL
GRID
EQ
"D" = SLAB OR WALL THICKNESS "d" = SLEEVE OUTSIDE DIAMETER
.
d
E
CLR MIN, SEE PLANS, TYP EQ EQ
1 5/256" 1 5/256"
MANAGEMENT .
EQ EQ
COL PER PLAN E E
PLAN
SCALE: NTS
GRID
1 1/2"C LR 1 1/2"C LR
BUNDLED PIPE GROUPS
SLAB/WALL - SPACING d to 3d
D/3, 3/4" MIN COVER OR 1 1/2" MIN COVER IF EXPOSED TO EARTH OR WEATHER
NOTES: 1. D = DEPTH FOOTING, W = WIDTH FOOTING, S = STEP AT FOOTING. 2. PIPE AS NOTED SHALL REFER TO: PIPES, DUCTS, CONDUITS, ETC. ELECTRICAL CONDUITS 1" DIA OR LESS NEED NOT BE SLEEVED / WRAPPED. 3. THIS DETAIL SHALL APPLY IN ALL CASES WHERE A PIPE MUST CROSS A CONTINUOUS FOOTING. COORDINATE ELEVATIONS AND LOCATIONS OF ALL PIPES & FOOTINGS ACCORDINGLY. CONTACT STRUCTURAL ENGINEER FOR CONDITIONS NOT COVERED. 4. PIPES SHALL BE SLEEVED OR WRAPPED AS SHOWN. SLEEVE INSIDE DIAMETERS SHALL BE MIN 2" (4" FOR SPRINKLER PIPES 4" & LARGER) LARGER THAN PIPE OUTSIDE DIAMETER. CENTER PIPES WITHIN SLEEVE. PIPES IN PLACE PRIOR TO PLACING CONC MAY BE WRAPPED W/ 1" (2" FOR SPRINKLER PIPES 4" & LARGER) THICK FLEXIBLE INSULATION INSTEAD OF SLEEVE. 5. SLEEVE / WRAP SHALL EXTEND THE FULL WIDTH OF FOOTING. SEAL ENDS OF SLEEVE / WRAP AS REQUIRED TO PREVENT WATER PENETRATION. 6. MULTIPLE PIPES SHALL COMPLY WITH THE HORIZONTAL AND VERTICAL SPACING SHOWN OR BE GROUPED INTO ONE LARGE BUNDLE WITHIN THE LIMITATIONS SHOWN. MULTIPLE BUNDLED PIPE GROUPS SHALL BE SPACED 4xD MIN OC. 7. PIPES AND SLEEVE / WRAP SHALL BE ADEQUATELY SUPPORTED AND SECURED AGAINST DISPLACEMENT BEFORE AND DURING CONCRETE PLACEMENT. 8. COORDINATE PIPE LOCATIONS SO THAT FOOTING REINFORCING IS NOT DISPLACED. MOVE PIPES TO MAINTAIN 2" CLR FROM REINFORCING TO SLEEVE / WRAP. 9. PIPES NEXT TO BUT NOT CROSSING FOOTING SHALL COMPLY WITH TYPICAL DETAIL FOR PIPE ADJACENT TO FOOTINGS. 10. FLEXIBLE INSULATION AS NOTED SHALL REFER TO LOW DENSITY POLYETHYLENE FOAM WITH A DENSITY OF 1.5-3 PCF (PER ASTM D1622) LAYERED TO MEET THICKNESS REQUIREMENTS.
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
12" MAX
11 1/2" 1/2" CLR CLR MIN, MIN, TYP TYP
TYP PIPE CROSSING FOOTING
12" MAX
DATE 01/04/2019 5/17/2019
2 7/32" 2 7/32"
BUNDLE PIPES AS TIGHTLY AS POSSIBLE
1'-6" MIN TYP 12" MIN
.
W W
18" MAX
#5 T&B ADDL REINF, TYP
.
WRAP 1" MIN ALL AROUND
90 DEG WHEN CROSSING THROUGH OR ABOVE FTG, 60 DEG MIN WHEN CROSSING BELOW FTG
2 7/32" 2 7/32"
.
A RU C T UR O F OF I CAL
05/15/2019
2"
6" MIN 6" MIN
THROUGH SLAB
T
E
TOC SEE PLAN
FTG REINF, SEE PLAN
D/4 MIN
BEARING SURFACE AS REQ FOR FOUNDATIONS, TYP
T
NOTES: 1. PIPE AS NOTED SHALL REFER TO: PIPES, DUCTS, CONDUITS, ETC. ELECTRICAL CONDUITS 1" DIA OR LESS NEED NOT BE SLEEVED 2. PIPES SHALL BE INSTALLED SUCH THAT CUTTING, BENDING OR DISPLACEMENT OF REINFORCEMENT FROM ITS PROPER LOCATION WILL NOT BE REQUIRED. 3. PIPES EMBEDDED IN SLABS & WALLS SHALL BE 2" MAX DIA & MIN SCHEDULE 40. 4. FLEXIBLE INSULATION AS NOTED SHALL REFER TO LOW DENSITY POLYETHYLENE FOAM WITH A DENSITY OF 1.5-3 PCF (PER ASTM D1622) LAYERED TO MEET THICKNESS REQUIREMENTS.
7
.
W
A
A
TYP PIPE AT SLABS / WALLS
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
2 1/2" TYP
2 1/2" TYP NOTES: 1. SEE 12/S-532 FOR INFORMATION NOT SHOWN
PLAN
15
GRID
S-_033000_T026A 140127
SCALE: NTS
.
AGENCY
DETAIL SCALE: NTS 150807
ANCHOR ROD & NUT 3" MIN CONC
INCREASE FTG WIDTH BY VERT PIPE DIA + 2" WHERE VERT PIPE OCCURS
AT CONT FOOTING
ADDL TIE ABOVE & BELOW RISER
STL PLATE
T T
TOF OR TOC SEE PLAN
2 1/2" MIN
#5 VERT W/ STD HOOK AT EA CORNER
COL, SEE PLAN COL BLOCKOUT
B
HEADED ANCHOR OR LOCKED DBL HEX NUTS, TYP
SECTION
2'-0" MIN CLR BTWN NOTCHES
PLAN OF CURB
HSS COLUMN BASE PLATE SCHEDULE NO PIPES SHALL BE PLACED WITHIN OR BELOW SPREAD FTGS. DROP PAD FTG BELOW RISER & EXTEND STEEL COL
2" MIN
AT PAD FOOTING
12 S-532
CONC SLAB & SUB-BASE, SEE PLAN
TOC SEE PLAN
TOF DROPPED
BASE PLATE DIMENSIONS T E L
COLUMN SIZE
ANCHOR ROD DIA
HSS4HSS4 OR HSS5
3/4"
3/4" T
1 1/2" E
HSS46HSS4 OR HSS58
3/4"
3/4"
1 1/2"
10" L 14" 10"
WELD SIZE W
1/4"
1/4"
TITLE
TOF SEE PLAN
HOOKS AS REQ, SEE PLAN
6" TYP
S-_033000_T014A 150417. Q1
TYP HSS COL BASE PLATE 12 SCALE: NTS
S-_051200_T001A 180723
DETAILS - TYPICAL CONCRETE
REINF, SEE PLAN
3" CLR, TYP PAD FTG SIZE, SEE PLAN
NOTES: 1. APPLIES TO SQUARE, RECTANGULAR (2 to 1 MAX DEPTH TO WIDTH RATIO), PIPE & ROUND HSS. 2. WELD NOT REQUIRED AT RADIUS CORNERS OF SQUARE OR RECTANGULAR HSS. 3. AT RECTANGULAR HSS, USE LARGER HSS DIMENSION.
TYP PIPE RISERS AT FOOTINGS SCALE: NTS
AB, SEE
SEE TYP DET FOR PILASTER
NOTES: 1. PIPE AS NOTED SHALL REFER TO: DUCTS, CONDUITS, ETC. ELECTRICAL CONDUITS 1" DIA OR LESS NEED NOT BE WRAPPED. 2. PIPES SHALL NOT PENETRATE A SILL PLATE AT SHEAR WALLS 3. FLEXIBLE INSULATION AS NOTED SHALL REFER TO LOW DENSITY POLYETHYLENE FOAM WITH A DENSITY OF 1.5-3 PCF (PER ASTM D1622 LAYERED TO MEET THICKNESS REQUIREMENTS
4
2" 2"
4" TYP 2" MIN
BASE PL NON-SHRINK GROUT
1'-0" 1'-0" MIN MIN UNO UNO
3" MIN
PAD PAD FTG FTG DEPTH DEPTH
. .
WRAP PIPE W/ 1/8" FLEXIBLE INSULATION
SEE SEE PLAN PLAN
WHERE RISER INTERFERES W/ CONT FTG, STEP FTG PER TYP DETAIL & PASS RISER ABOVE FTG
A
STEEL COL, SEE PLAN WRAP VERT PIPE W/ 1/8" FLEXIBLE INSULATION WRAP HORIZ PIPE & ELBOW W/ 1" FLEXIBLE INSULATION #3 TIES @ 12" OC, MAX & 2" FROM TOP
PL WASHER
3" 3" CLR, CLR, TYP TYP
ADDL #4 DOWEL & AB EA SIDE OF PIPE
1 1/2" CLR
12"MAX 12"MAX NOTCH NOTCH
WRAP VERT PIPES WITH 1/8" FLEXIBLE INSULATION. WRAP HORIZ PIPE & ELBOW W/ 1" FLEXIBLE INSULATION 3/4" CLR MAX PIPE SIZE IS AS FOLLOWS: 2 1/4" OD FOR 2x6 WALL 4 1/4" OD FOR 2x8 WALL 6 1/4" OD FOR 2x10 WALL
STD STD LAP LAP TYP TYP
ADDL #4 x4'-0" EA SIDE OF PIPE
1'-9"
SEE TYP DETAIL FOR PIPE AT SLAB TOF STEPPED
ADDL #4 W/ STD LAP EA END
1'-9"
TOF
A
NOTCHED CONT SILL PLATE
3" 3" MAX MAX
PROVIDE 16GA STL PLATE AS SHOWN, ATTACH TO SILL FLEXIBLE INSULATION FLEXIBLE INSULATION
L N IA
. . . .
SLAB REINF, SEE PLAN
2" MIN CLR TO PIPE FROM BOT OF SLAB
4" MIN, TYP
CL PIPE
3
CONC SLAB & SUB-BASE, SEE PLAN
No. S3737
R
1 1/2" 1 1/2"
2" 2" MIN MIN
2" 2" MIN MIN
1/8" MIN FLEXIBLE INSULATION
3 31/32"MIN 3 31/32"MIN
3'-0" 3'-0" MIN MIN
2xW 2xW & & LESS LESS
2" 2" MIN MIN
D D OVER OVER 2xW 2xW
PIPE EXCAVATE & BACKFILL TRENCH PER SPECS
ADDITIONAL #4 CONT
TOF SEE PLAN
CONC SLAB O/ SUB-BASE, SEE PLAN
2" MIN
4" MIN TYP
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
1/3 TOTAL DEPTH OF THICKENED SLAB OR 3" MIN
IN SLAB BELOW REINF
SPACE D MIN
5/15/2019 4:35:41 PM
1
AB, SEE SCHED
A
8" MAX INCLUDING TOTAL DEPTH OF INTERSECTING PIPES
1
8" MIN
C
B
SP, SEE PLAN
1
1/8" MIN FLEXIBLE INSULATION
TOF
WOOD STUD WALL, SEE PLAN
EER GIN EN R
1
CL STUD, AB & FTG
FESSIONA PRO L ED RRY J. VOLKE E
S
FOOTING
1 1/2" MIN CLR TO PIPE
SLEEVE / WRAP, TYP PIPE, TYP
SEAL
ST
IF SPACING IS LESS THAN D, REMOVE SOIL THIS AREA AND FILL W/ SAME MATERIAL AS AT ADJACENT PIPES CONTROLLED LOW-STRENGTH MATERIAL OR CONC PLACED PRIOR TO FTG, TYP (MATCH FTG WIDTH, MIN)
4 1/2" 4 1/2"
THROUGH FOOTING
PROVIDE JOINTS AS SHOWN FOR COVERED CONCRETE. CONTACT ARCH FOR EXPOSED CONDITIONS
REGIST ER K
CONC SLAB O/ SUB-BASE, SEE PLAN SLAB REINF
3 1/2" 3 1/2"
HATCHING INDICATES AREA WITHIN FTG WHERE PIPES ARE ALLOWED TO PASS THROUGH
3" 3" MIN MIN
FOOTING, SINGLE STEP SHOWN, MULTIPLE STEP SIM
SHEET
TYP PAD FOOTING 16 SCALE: NTS
S-532 S-_033000_C014A 140127. Q2
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
INC:
REVIEWED FOR SS
SEE TYP DETAILS FOR STUD WELD
2X STUD EA SIDE, TYP UNO
SHAPE AS SHOWN FOR TIGHT FIT, TYP
STUD WALL, SEE PLAN
EQ EQ
1 7/8
1 7/8
15/16
16d COMMON
0.162
3 1/2
1/8
2
2
1
20d BOX
0.148
4
7/64
1 7/8
1 7/8
15/16
30d BOX
0.148
4 1/2
7/64
1 7/8
1 7/8
15/16
40d BOX
0.162
5
1/8
2
2
1
END
INTERSECTION
SP EN, TYP
INCREASE STUD THICKNESS AS REQ TO MAINTAIN MIN DIM SHOWN, TYP
SPACING PER TABLE
3/32"
1 1/4"
#10
0.190
7/64"
1 1/2"
#12
0.216
1/8"
1 3/4"
#14
0.242
5/32"
2"
C
5" MIN & 9" MAX FROM ENDS, SPLICES & HOLES OR NOTCHES GREATER THAN 1/3 THE STUD WIDTH
NOTES: 1. PREDRILL ALL SCREW HOLES W/ COUNTERSINK BIT. 2. ALL SCREWS TO HAVE FLAT HEAD FOR WOOD TO WOOD CONNECTIONS AND PAN HEAD FOR SP TO WOOD OR METAL TO WOOD CONNECTIONS. 3. ALL SCREWS TO HAVE ROLLED THREADS. 4. WAX SHALL BE USED ON THE WOOD SCREWS OR IN THE LEAD HOLES TO FACILITATE INSERTION AND PREVENT DAMAGE TO THE WOOD SCREW. 5. THE THREADED PORTION OF THE WOOD SCREW SHALL BE INSERTED IN ITS LEAD HOLE BY TURNING WITH A WRENCH, NOT BY DRIVING WITH A HAMMER.
TYP WOOD SCREW INSTALLATION S-_061010_T006A 140127. Q2
SCALE: NTS
3X 3X
1'-4" OC MAX
E
3X
1'-4" OC MAX
F
3X
8" OC MAX
S-_061010_T025A 140127. Q2
SCALE: NTS
CL STUD & AB
15/32" 15/32"
1/2" 1/2"
57/64" 57/64"
1 35/64" 1 35/64"
3" PROJECTION
1/2" DIA AB W/ STEEL WASHER @ 48" OC
2 33/64" 2 33/64"
THREAD LENGTH
1 35/64" 1 35/64"
1/2" 1/2"
1 7/32" 1 7/32"
1 11/32" 1 11/32"
SHANK LENGTH
MINIMUM PENETRATION
BASE WOOD MEMBER
3/8" DIA CONC SCREW W/ STEEL WASHER @ 32" OC
2X PTW PPTWSILL SILL
9/32" 9/32"
'D2' LEAD HOLE FOR THREADED PORTION
B
1/4"
3/8"
1/2"
LAG / SHANK DIA
5/8"
3/4"
7/8"
1" SH AN KLENGTH SH AN KLENGTH
LAG / SHANK DIA
'D2' HOLE SIZE
1/8"
3/8" 1/4"
1/2" 1/4"
MIN PENETRATION 2 1/2" 3 3/4" 4 3/4"
5/8"
3/4"
3/8" 6"
1/2"
7/8" 1/2"
1" 1 41/64" 1 41/64"
1/4"
SHANK LENGTH
5/8"
3" MIN
THREAD LENGTH
AT FLAT SLAB
15/64" 15/64"
'D1' HOLE SIZE
CONC SLAB & SUBBASE, SEE PLAN
7 1/4" 8 1/2" 9 1/2"
DEPRESSED SLAB WHERE OCCURS. IF DEPRESSED 2" OR GREATER, BOLT SILL AS SHOWN AT CURB EDGE OF CONC WHERE OCCURS
8" WALL
10" WALL
4" WALL
6" WALL
8" WALL
10" WALL
4x8
6x6
6x8 FLAT
2x4
2x6
2x8
2x10
8'
4x10
(2) 2x4
(2) 2x6
(2) 2x8
(2) 2x10
10'
4x12
" " 6X12 6x10 " " 6X12 SEE PLAN
6x10 FLAT 6X12 " "
(3) 2x4
(3) 2x6
(3) 2x8
(3) 2x10
TYP LAG SCREW INSTALLATION S-_061010_T004A 160711. Q2
SCALE: NTS
S-_061010_T027A 140127. Q2
SCALE: NTS
STUD WALL, SEE PLAN TYP STUD WELD AT "NELSON" STUDS
1/4
1/2" 1/2"
3/8" DIA CONC SCREW W/ STEEL WASHER @ 32" OC
2X PPTW SILL
1
WALL HT ABOVE FF
WALL HT
(2) 16D EA END, EA 2x
8'-0" OC
12'-0" TO 24'-0"
4'-0" OC
WITHOUT CURB
(E) DEPRESSED SLAB WHERE OCCURS. IF DEPRESSED 2" OR GREATER, BOLT SILL AS SHOWN AT CURB
NOTE: 1. WHERE OPNG IS LESS THAN TYP STUD SPACING, PROVIDE 2X6 ABV & BLW OPNG & ATTACH SIM TO SILL ABV
11
TYP FRAMING AT OPENINGS S-_061010_T031A 140127. Q2
SCALE: NTS
"SIMPSON" CS22 x 1'-4" AT EA BRACE TO STUD W/ (7) 8d TO WALL & (7) 8d TO BRACE
15
S-_061010_T032A 140127. Q2
SCALE: NTS
S-_061010_T039A 140127. Q2
8
TYP INTERIOR NON-STRUCTURAL WALL ANCHORAGE AT (E) SLAB SCALE: NTS
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
ALT CONNECTION PARALLEL TO BEAM 1/4" CLR MAX FROM BLOCK TO JOIST AT CLIP
A
JOIST, SEE PLAN 2X BLKG @ 24" OC
PARALLEL TO JOISTS
TYP INT NON-STRUCTURAL PARTIAL HEIGHT WALL BRACING
MARK
MANAGEMENT
STUD WALL, SEE PLAN
2X STUD WIDTH BLKG EA SIDE
1 1/2"
9"
19
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
WHERE JOISTS ARE 48" OC, PROVIDE DTC EA SIDE OF JOIST
DETAIL A PERPENDICULAR TO JOISTS
AGENCY
TYP INT NON-STRUCTURAL WALL ANCHORAGE AT JOISTS S-_061010_T036A 150107. Q2
SCALE: NTS
CL OF PLATE & DRILLED HOLE
SPLICE 5" MIN & 9" MAX FROM ENDS
4'-0" MAX UNO (SEE SHEAR WALL SCHED & PLANS)
6" 6"
6 1/2" 6 1/2"
5/8" DIA X 1'-0" AB 5/8" DIA X 1'-6" AB WHERE CURB OCCURS ("HEX" HEAD ANCHOR BOLT)
S-_061010_T027B 140127. Q2
WHERE FOUNDATION IS NOT LEVEL, DRY PACK AS REQ TO MAINTAIN FULL BEARING AT CONTACT SURFACES
NOTES: 1. PLATES BORED, CUT OR NOTCHED MORE THAN 1/3 OF WIDTH SHALL HAVE ADDL BOLTS EACH SIDE OF BORE, CUT OR NOTCH (AS FOR SPLICES) 2. TWO BOLTS MIN FOR EACH PIECE OF SILL 3. OUTSIDE DIA OF THREADS MUST EQUAL BOLT SHANK DIA 4. HOLDOWN BOLTS DO NOT REPLACE ANCHOR BOLTS 5. CENTER ALL AB'S ON CENTERLINE OF SILL UNO
12
TYP AB AT WOOD SILL PLATE SCALE: NTS
S-_061010_T035A 140127
BACKER BLKG, TYP WIDTH TO MATCH STUD WALL BACKER BLKG, TYP SP EN SP EN
DBL 2x TOP PL
"SIMPSON" A34 A34 EA EA END END "SIMPSON" "SIMPSON" DTC EA JOIST/BLKG (SLOTTED LEG VERT)LEG INSTALL NAILS (SLOTTED VERT) IN CENTER OF SLOT VERT
"SIMPSON" CS18 EA SIDE OF EA TOP PL W/ (11) 8d EA END
SEE PLAN TOC
WITH CURB
NOTE: 1. PLATES BORED, CUT OR NOTCHED MORE THAN 1/3 OF WIDTH SHALL HAVE ADDL CONNECTOR (PAF OR BOLT AS DENOTED) EACH SIDE OF BORE, CUT OR NOTCH (AS FOR SPLICES) 2. TWO CONNECTORS MIN FOR EACH PIECE OF SILL
TYP WELDED THREADED STUD (WTS)
STUD WALL
"SIMPSON" DTC AT EA JOIST/BLKG (SLOTTED LEG VERT) PLACE NAILS IN SLOT AT 1/2" FROM BOTTOM OF SLOT DRIVE NAILS IN SLOT TO ALLOW 1/16" GAP BETWEEN NAIL HEAD & CLIP
NOTE: 1. FRAMING ABOVE MAY SLOPE, SEE PLANS
AT CURB
SEE PLAN 2 1/2" EMBED
3" MIN
PARALLEL TO BEAM
ISSUED
#10 PAN HD WOOD SCREW EA SIDE - DO NOT DRIVE TIGHT
"SIMPSON" A34 AT EA BRACE
EQ
WOOD NAILER
2X BLKG
ADD 2x4 FLAT W/ 16d @ 12" OC WHEN BRACE LENGTH "x" EXCEEDS 6'-0", (MAX "x" = 14'-0") TYP
BRACE SPACING
7'-6" TO 12'-0"
2x4 BRACES AT MAX SPACING SHOWN PER TABLE, ALTERNATE ES OF WALL WHEN POSSIBLE, PROVIDE ADDL BRACE AT ENDS OF WALL NOT INTERSECTED BY ANOTHER WALL (BRACES PERPENDICULAR TO WALL)
16 GA SLOTTED TRACK W/ WIDTH TO MATCH STUD DEPTH (ICC ESR 1042) W/ # 10 WOOD SCREWS @ 16" OC TO BEAM 1" MIN
1 1/2" MIN
12" LONG 2X BLOCK W/ (2) 16D TO PL
2X STUD WIDTH BLKG
STD CUT WASHER, UNO
SCALE: NTS
BRACE PARALLEL TO FRAMING
1 (MAX) 1/2 (MIN)
BRACE SKEWED OR PERPENDICULAR TO FRAMING
POST WHERE OCCURS, SEE PLAN
A
4
BM
FRAMING, SEE PLAN 2x BLKG AT EA BRACE W/ "SIMPSON" A34 EA END
FRAMING ANCHOR T&B OF EA KING STUD WHERE "L" EXCEEDS 4'-0"
STUD ANCHOR AT BOLT
(E) CONC SLAB & SUBBASE, SEE PLAN
THREADED ROD OR "NELSON" STUD TYPE CPL
SP, SEE PLAN
(3) 16d
STUDS EA SIDE OF OPNG GREATER WHERE "L" EXCEEDS 6'-0"
DOOR OPNG
#4 CONT STEEL MEMBER SEE PLANS
HEADER PER SCHEDULE
"L"
"SIMPSON" HTC AT EA STUD (SLOTTED LEG VERT) PLACE NAILS IN SLOT AT 1/2" FROM BOTTOM OF SLOT DRIVE NAILS IN SLOT TO ALLOW 1/16" GAP BETWEEN NAIL HEAD & CLIP
1/2" 1/2"
1/2" DIA AB W/ STEEL WASHER @ 32" OC - EMBED IN EPOXY INTO (E) CONC SLAB (NO TEST LOAD)
TYP AT THREADED ROD
S-_061010_T029A 140127. Q2
SCALE: NTS
DBL CRIPPLE AND DBL KING EXTERIOR STUDS: (3) 16D EA END STUDS, TYP. TRIPPLE DBL CRIPPLE & DBL KING CRIPPLE AND TRIPPLE KING MIN. TRIPPLE AT DBLFOR CRIPPLE & DBL OPENINGS > KING 6'-0" OPENINGS 6' OR
WINDOW OPNG SHOWN DASHED
3" PROJECTION
D
(1) 16D PER 2" OF HEADER DEPTH EACH (3) 16D EA END END
FRMG ANCHOR
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
(3) 8D EA SIDE OF STUD AT EA PIECE OF BLKG
CL STUD & AB
NOTES: 1. DO NOT COUNTERSINK BOLT TYP UNO 2. D = WOOD NAILER THICKNESS, SEE PLANS 3. d = BOLT DIAMETER (SEE PLANS & DETAILS)
5/15/2019 4:35:44 PM
7
TYP INTERIOR NON-STRUCTURAL WALL ANCHORAGE AT BASE
1/2" ES AT 2x6 & LARGER STUDS, 0" AT 2x4 STUDS
2d, MIN
SEE PLAN
NOTE: WHERE TYPICAL WALL STUDS ARE LSL, CRIPPLE, KINGS AND SILLS, SHALL BE LSL
d
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
3
6X12 " "
SILL PER SCHEDULE
NOTES: 1. PLATES BORED, CUT OR NOTCHED MORE THAN 1/3 OF WIDTH SHALL HAVE ADDL CONNECTOR (PAF OR BOLT AS DENOTED) EACH SIDE OF BORE, CUT OR NOTCH (AS FOR SPLICES) 2. TWO CONNECTORS MIN FOR EACH PIECE OF SILL
770 DIAMOND AVE RED BLUFF, CA 96080
ELEVATION
TYP BEAM / HEADER SUPPORT AT STRUCTURAL WALLS SP EN TO BLKG (3) MIN
6" WALL 6x8
14
SILL SCHEDULE
POST AT HOLDOWN TO BE CONT TO TOP PLS
AT CURB
C
NOTE: 1. MAXIMUM HEADER REACTION OUT OF PLANE IS 1000#.
4" WALL
CONDITION AT HOLDOWN
SECTION
CLIENT
S-_061010_T028A 140127. Q2
HEADER SCHEDULE
FRAMING ANCHOR T&B
B
NON-PERPENDICULAR CORNER
SCALE: NTS
>10'
ELEVATION
A
TYP WOOD STUD WALL FRAMING AT CORNERS & INTERSECTION
TAPERED TIP
NOTES: 1. THE THREADED PORTION OF THE LAG SCREW SHALL BE INSERTED IN ITS LEAD HOLE BY TURNING WITH A WRENCH, NOT BY DRIVING WITH A HAMMER. 2. WAX SHALL BE USED ON THE LAG SCREW OR IN THE LEAD HOLE TO FACILITATE INSERTION AND PREVENT DAMAGE TO THE LAG SCREW. 3. MINIMUM PENETRATION DOES NOT INCLUDE THE LENGTH OF THE TAPERED TIP.
A RU C T UR O F OF I CAL
TEHAMA CENTER STUDENT SERVICES
(2) 2x CRIPPLES BELOW BEAM, TYP UNO AS POST PER PLAN
SP EN
TRIM STUD AS SHOWN & USE FILLER AS REQ
CONC CURB
WOOD TO WOOD
LAG SCREW SCHEDULE
"SIMPSON" LS50 @ 24" OC
SP EN
MAX SPAN "L" 4'
1" CLR
STEEL TO WOOD
10
SEE PLAN
9/32" 9/32"
POST WHERE OCCURS SHOWN DASHED
SP EN TYP
TYP HSS / PIPE COL IN WOOD STUD WALL
2x STUD, UNO
MINIMUM PENETRATION
SP WHERE OCCURS TYP
CORNER
6
T
E
PROJECT
16D @ 12" OC
16D @ 12" OC TYP WHERE POST OCCURS
1/2" ES AT 2X6 & LARGER STUDS, 0" AT 2X4 STUDS
15/32" 15/32"
SP WHERE OCCURS TYP
16D @ 12" OC
2'-0" OC MAX
D
T
No. S3737
05/15/2019
ELEVATION
'D1' LEAD HOLE FOR SHANK
STD HOLE IN STEEL PL
2'-8" OC MAX
FESSIONA PRO L ED RRY J. VOLKE E
INTERSECTIONS
3" PROJECTION AT 2X PL 4" PROJECTION AT 3X PL
0.164
3X
.
#8
B
.
MINIMUM PENETRATION UNO
2'-8" OC MAX
1/8" GAP
221/256" 221/256"
MAXIMUM PREDRILL BIT DIA (IN)
2X
EN 16D @ 12" OC
POST WHERE OCCURS SHOWN DASHED
SEAL
A
SCREW DIAMETER
A
EN, TYP
HEADER OR BEAM, SEE PLAN, TYP
8" 1 / AP G
SCREW SIZE
5/8" DIA WELDED THREADED STUD SPACING
FULL HEIGHT STUDS SEE "TYP FRAMING AT OPENINGS" DETAIL FOR QUANTITY AT THIS CONDITION
S
WOOD SCREW SCHEDULE
STUD THICKNESS EA SIDE OF COLUMN
FRAME ABOVE HEADER PER TYP CORNER DETAIL, TYP
POST WHERE EN OCCURS SHOWN DASHED EN, TYP
16D @ 12" OC, TYP
PLAN
EER GIN EN R
SHEAR WALL MARK
PLAN
ST
BASE WOOD MEMBER
C
16D @ 12" OC TYP
STUD THICKNESS PER TABLE UNO WTS W/ WASHER & NUT, TYP
PLAN
16D @ 12" OC
20 GA BENT PL AT CORNER
"SIMPSON" CS20 W/ ALL HOLES FILLED W/ 8d NAILS
A
S-_061010_T030A 140127. Q2
SCALE: NTS
1" MIN TYP
#8 SDST SCREWS @ 12" OC #8 SDST SCREWS @ 6" OC EA LEG OF BENT PL
ADDITIONAL FULL HEIGHT STUD THIS SIDE IF WALL IS CONT
C
1'-0"
TYP HOLE IN WALL STUD
9
#10 SDST SCREW MIN @ 12" OC
S-_061010_T005A 140127. Q2
"SIMPSON" CS20 W/ ALL HOLES FILLED W/ 8d NAILS
NOTE: 1. NOTCHES IN WALL STUDS ARE NOT ALLOWED. 2. HOLES NOT PERMITTED IN WALL FRAMING 4X AND THICKER. 3. LOCATE HOLES "D" MIN FROM ENDS OF STUDS & ANY CLIPS OR FASTENERS ATTACHED TO FACE OF STUD.
20 GA CONT BENT PL, TYP
MINIMUM PENETRATION
CONSULTANT
CL STUD
TYP NAIL INSTALLATION SCALE: NTS
B
PLAN
WHERE SHEAR WALL MARK IS INDICATED THUS ON PLANS, THE STUD BOLT SPACING SHALL BE AS PER TABLE BELOW
SIDE MEMBER
2
CORNER
5/8" DIA WTS W/ WASHERS & NUTS @ 4'-0" OC MAX EA SIDE, TYP UNO PER TABLE BELOW
WHERE WALL ENDS AT COL, PROVIDE ADDL 2X STUD W/ BORED HOLES FOR WASHERS & NUTS
NOTES: 1. NAIL LENGTHS DENOTED ARE FOR STANDARD NAILS. SHORTER NAILS W/ EQUIVALENT DIA WILL BE PERMITTED IF MINIMUM PENETRATION INTO BASE WOOD MEMBER IS MAINTAINED. 2. PREDRILL TO PREVENT SPLITTING
1
FIELD
L N IA
7/64
R
3
REGIST ER K
0.148
IN "M D 1 1 EN A PE TY
CL OF HOLE AND STRAP (LENGTHWISE)
1" CLR
10d COMMON
A
3/4" CLR
13/16
1 1/4"
1 5/8
1" CLR
1 5/8
2" MAX
3/32
1" CLR
2 1/2
EQ, TYP
EQ
0.131
07/03/2019
FULL HEIGHT STUDS, SEE TYP HEADER DETAIL FOR QUANTITY AT THIS CONDITION
EQ
8d COMMON
D
✔
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
"x "
MINIMUM PENETRATION (IN)
2'-8" MIN
MAXIMUM PREDRILL BIT DIA. (IN)
EQ
LENGTH (IN)
EQ EQ
MINIMUM MINIMUM SPACING EDGE (IN) DISTANCE
SHANK DIA (IN)
HEADER OR BEAM SEE PLAN, TYP
EQ
NAIL SCHEDULE
3/4" MIN TYP
1" CLR
HSS OR PIPE COL, SEE PLAN
2x BLKG FULL LENGTH OF STRAP (3x BLKG W/ EN WHERE SP OCCURS)
8"
BASE WOOD MEMBER
NAIL PENNY WEIGHT
ACS
✔
FULL HEIGHT STUD TYPICAL UNO WITH (4) 16d TO BEAM
1" CLR
2X STUD, TYP UNO, SEE PLAN
BORED HOLE AT CL OF STUD
1'-4" MIN
SP WHERE OCCURS, TYP
D MIN
2" 2"
NAIL
FLS
D/3 MAX
MIN PENETRATION
3/4" MIN TYP
L/3
L
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
TOE NAIL
DATE:
WALL STUDS, SEE PLAN
D
1'-4" MIN
0 1/4" 1/2"
30°
✔
I-JOIST, SEE PLAN
TITLE
TIMBER STRAND BLKG @ 24" OC DEPTH TO MATCH I JOIST 2x BLKG W/ (3) 16D TO PL W/ 1/4" HORIZ GAP FRAMING 2x BLKG W/ TO (3) 16D TO PL EA W/ END 1/4" HORIZ GAP TO FRAMING EA END
NO NAILS THIS AREA PIPE OR CONDUIT OD +3" (6" MIN)
PARALLEL TO JOISTS
PERPENDICULAR TO JOISTS
DETAILS - TYPICAL WOOD FRAMING
NOTES: 1. PROVIDE STRAPS WHERE DIAMETER OF HOLE EXCEEDS 1/3 OF PLATE WIDTH. DIAMETER OF HOLE SHALL NOT EXCEED 2/3 OF PLATE WIDTH. 2. NO NOTCHES PERMITTED AT TOP PLATES. 3. DO NOT LOCATE HOLES WITHIN 4'-0" EA SIDE OF TOP PLATE SPLICES. 4. IF HOLES OCCUR WITHIN A STUD BAY IN WHICH A JOIST OR TRUSS LANDS, ADD A STUD DIRECTLY BELOW THE JOIST OR TRUSS.
16
TYP PLATE REINFORCING AT PIPE OR CONDUIT SCALE: NTS
S-_061010_T033A 140127. Q2
20
TYP INTERIOR NON-STRUCTURAL WALL ANCHORAGE AT I-JOISTS SCALE: NTS
S-_061960_T210A 140127. Q2
SHEET
S-561
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
DATE:
SLOPE, SEE SEE PLAN PLAN SLOPE,
FLS
ACS
✔
✔
07/03/2019
4'-0" MIN MIN LAP LAP 4'-0"
2x CONT CONT LEDGER, LEDGER, 2x MATCH JOIST JOIST DEPTH, DEPTH, TYP TYP MATCH
2x FULL-DEPTH FULL-DEPTH BLKG BLKG 2x @ 4'-0" 4'-0" OC OC AT AT ALL ALL @ JOISTS AT AT FIRST FIRST BAY BAY JOISTS
JOIST PER PER TABLE TABLE JOIST
SPLICE PL PL OVER OVER STUD, STUD, TYP TYP SPLICE
D
JH PER PER "TYP "TYP NOTES" NOTES" JH
2XSTUD, STUD, TYP TYP 2X UNO, SEE SEE PLAN PLAN UNO,
JOIST PER PER TABLE TABLE JOIST
MAX ALLOWED ALLOWED NOTCH NOTCH MAX WHEN BEARING BEARING AT AT WHEN THIS LOCATION LOCATION THIS
CONCRETE OR OR MASONRY MASONRY WALLS WALLS CONCRETE
10 107/256"
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
WIDTH OF OF BEARING BEARING SHALL SHALL WIDTH MATCH STUD STUD WIDTH WIDTH OR OR BEAM BEAM && MATCH SHALL INCLUDE INCLUDE SP SP THICKNESS THICKNESS SHALL WHERE OCCURING, OCCURING, UNO UNO WHERE
CONSULTANT
NAILED SPLICE SPLICE AT AT DOUBLE DOUBLE PLATE PLATE NAILED TYP SPLICE SPLICE UNO UNO (SEE (SEE PLANS) PLANS) TYP
8" MIN MIN 8"
JOIST PER PER TABLE TABLE JOIST
9 JH PER PER "TYP "TYP JH NOTES" NOTES"
DAP BOLTS BOLTS AT AT SHAPED SHAPED DAP PL WHERE WHERE OCCURS, OCCURS, TYP TYP PL
S-_061010_T007A S-_061010_T007A 140127. Q2 Q2 140127.
1"==1'-0" 1'-0" 1"
2XBLKG, BLKG, 2X TYP TYP
STUD WALL, WALL, TYP, TYP, STUD SEE PLAN PLAN SEE
BOLTED SPLICE SPLICE AT AT DOUBLE DOUBLE PLATE PLATE BOLTED
TYP BEARING CUT IN JOIST / RAFTER
BEARING BEARING LENGTH LENGTH
1'-4" 1'-4"
WOOD STUD STUD WALLS WALLS WOOD
JOISTS PERPENDICULAR PERPENDICULAR JOISTS TO WALL WALL TO
L/3 L/3
JOISTS PARALLEL PARALLEL JOISTS TO WALL WALL TO
C
LEDGER NAILING NAILING LEDGER AT EA EA STUD STUD AT
LEDGER BOLTING BOLTING LEDGER AT MASONRY MASONRY OR OR CONC CONC AT
10'-0" 10'-0"
2x4 2x4
(2) 16D 16D (2)
(1) (1)
15'-0" 15'-0"
2x6 2x6
(3) 16D 16D (3)
(1) (1)
20'-0" 20'-0"
2x8 2x8
(4) 16D 16D (4)
(2) (2)
1/4" DIA DIA "HILTI" "HILTI" 1/4" KWIK CON CON IIIIW/ W/ KWIK 3/4" MIN MIN EMBED EMBED 11 3/4" @ 16" 16" OC, OC, TYP TYP @
D/3 D/3 MAX MAX
JOIST JOIST @ 16" 16" OC OC @
NOTCH NOTCH JOIST // RAFTER RAFTER // BEAM BEAM JOIST
MIN DD MIN TYP TYP
ALLOTHER OTHER CEILING CEILING CONFIGURATIONS CONFIGURATIONS ALL
TRIPLE 2X 2X TOP TOP PL PL TRIPLE
SPLICE EA EA PL PL OVER OVER STUD, STUD, TYP TYP SPLICE
BOLTED SPLICE SPLICE AT AT TRIPLE TRIPLE PLATE PLATE BOLTED
2
TYP TOP PLATE SPLICES 3/4"==1'-0" 1'-0" 3/4"
S-_061010_T038A S-_061010_T038A 140127. Q2 Q2 140127.
6
MAXIMUM MAXIMUM SPAN SPAN
JOIST JOIST @ 16" 16" OC OC @
LEDGER NAILING NAILING LEDGER AT EA EA STUD STUD AT
8'-0" 8'-0"
2x4 2x4
(2) 16D 16D (2) (3) 16D 16D (3)
(1) (1)
16'-0" 16'-0"
2x8 2x8
(3) 16D 16D (3)
(1) (1)
20'-0" 20'-0"
2x10 2x10
(4) 16D 16D (4)
(2) (2)
STRAP TO TO EXTEND EXTEND STRAP 2X"S" "S" PAST PAST DOUBLE DOUBLE 2X FRAMING, TYP TYP FRAMING,
NOTE: NOTE: 1. PREDRILL PREDRILL SMALL SMALL DIA DIA HOLE HOLE AT AT ALL ALL CORNERS CORNERS OF OF NOTCHES. NOTCHES. ALL ALL CUTS CUTS SHALL SHALL INTERSECT INTERSECT 1. PREDRILLED HOLE. HOLE. OVERCUTTING OVERCUTTING IS IS NOT NOT PERMITTED. PERMITTED. PREDRILLED 2. NOTCHES NOTCHES IN IN THE THE BOTTOM BOTTOM OF OF JOISTS JOISTS ALLOWED ALLOWED ONLY ONLYWHERE WHERE SPECIFICALLY SPECIFICALLYDETAILED DETAILED ON ON THE THE 2. DRAWINGS. DRAWINGS. 3. IF IF JOIST JOIST // RAFTER RAFTER // BEAM BEAM CANTILEVERS CANTILEVERS OR OR IS IS CONTINUOUS CONTINUOUS OVER OVER MORE MORE THAN THAN ONE ONE SPAN, SPAN, NO NO 3. NOTCHES ARE ARE PERMITTED. PERMITTED. NOTCHES
S-_061010_T002A S-_061010_T002A 140127. Q2 Q2 140127.
10
TYP HOLE OR NOTCH IN JOIST / RAFTER / BEAM 3/4"==1'-0" 1'-0" 3/4"
T
E
No. S3737
A RU C T UR O F OF I CAL
05/15/2019 PROJECT
TEHAMA CENTER STUDENT SERVICES
MIN DD MIN TYP TYP
ELEVATION ELEVATION
T
DOUBLE FRAMING FRAMING DOUBLE EACH SIDE SIDE EACH
DOUBLE FRAMING FRAMING DOUBLE EACH SIDE SIDE EACH
DBL FRAMING FRAMING AT AT DBL EA EDGE, EDGE, TYP TYP EA
1/4" DIA DIA "HILTI" "HILTI" 1/4" KWIK CON CON IIIIW/ W/ KWIK 3/4" MIN MIN EMBED EMBED 11 3/4" @ 16" 16" OC, OC, TYP TYP @
TYP WOOD CEILING FRAMING 3/4"==1'-0" 1'-0" 3/4"
JH TYP TYP JH
MIN 3X4 3X4FLAT FLAT MIN BLKG, TYP TYP BLKG,
(1) (1)
2x6 2x6
3X "S" "S" MAX MAX 3X
DBL JH JH TYP TYP DBL
LEDGER BOLTING BOLTING LEDGER AT MASONRY MASONRY OR OR CONC CONC AT
12'-0" 12'-0"
"S" "S"
A
(4) 5/8" 5/8" DIA DIA BOLTS BOLTS ES ES (4) OF SPLICE SPLICE (8 (8 TOTAL) TOTAL) OF
MAXIMUM MAXIMUM SPAN SPAN
SPACING SPACING PER PLAN PLAN PER
S
CEILING W/ W/ (1) (1) LAYER LAYER OF OF 5/8" 5/8" GYPSUM GYPSUM BOARD BOARD CEILING
FESSIONA PRO L ED RRY J. VOLKE E
1/2" RADIUS RADIUS 1/2" NOTCH AT AT END END NOTCH NOT TO TO EXCEED EXCEED NOT BEARING BEARING LENGTH LENGTH BORED HOLE HOLE BORED
EQ EQ
8" MIN MIN 8"
NO NOTCHES NOTCHES NO WITHIN THIS THIS WITHIN LENGTH UNO UNO LENGTH
EQ EQ
8" MIN MIN 8"
DEPTH DEPTH D D
8" MIN MIN 8"
SEAL L/3 L/3
ST
NO JOISTS JOISTS SHALL SHALL LAND LAND ON ON NO BOLTS WHEN WHEN SHAPED SHAPED PL PL BOLTS DOES NOT NOT OCCUR, OCCUR, TYP TYP DOES
8" MIN MIN 8"
L/3 L/3
EER GIN EN R
D/5 MAX MAX D/5
4'-0" MIN MIN LAP LAP 4'-0" 8" MIN MIN 8"
BEARING BEARING LENGTH LENGTH
SPANLL SPAN NO NOTCHES NOTCHES WITHIN WITHIN THIS THIS LENGTH LENGTH NO AT FRAMING FRAMING 4" 4" WIDE WIDE && LARGER LARGER AT
REGIST ER K
8" MIN MIN 8"
3X 3X "S" "S" MAX MAX
8" MIN MIN 8"
2x FULL-DEPTH FULL-DEPTH BLKG BLKG 2x @ 4'-0" 4'-0" OC OC AT AT ALL ALL @ JOISTS AT AT FIRST FIRST BAY BAY JOISTS JOIST PER PER TABLE TABLE JOIST
D/4 D/4 MAX MAX
8" MIN MIN 8"
2x CONT CONT LEDGER, LEDGER, 2x MATCH JOIST JOIST DEPTH, DEPTH, TYP TYP MATCH
NOTES: NOTES: 1. OVERCUTTING OVERCUTTING IS IS NOT NOT PERMITTED. PERMITTED. ALL ALL CUTS CUTS SHALL SHALL INTERSECT INTERSECT DRILLED DRILLED HOLE HOLE WHEN WHEN USED. USED. 1. 2. BEARING BEARING CUTS CUTS SHALL SHALL OCCUR OCCUR ONLY ONLYWHERE WHERE SPECIFICALLY SPECIFICALLYDETAILED DETAILED ON ON THE THE DRAWINGS. DRAWINGS. 2. 3. CUTS CUTS OR OR DRILLED DRILLED HOLES HOLES SHALL SHALL NOT NOT INTERSECT INTERSECT ANY ANYLOOSE LOOSE KNOTS. KNOTS. 3.
2" 2" MIN MIN
8" MIN MIN 8"
STUD WALL, WALL, TYP, TYP, STUD SEE PLAN PLAN SEE
SLOPED CONDITION CONDITION SLOPED
2" 2" MIN MIN
(4) 5/8" 5/8" DIA DIA BOLTS BOLTS ES ES (4) OF SPLICE SPLICE (8 (8 TOTAL) TOTAL) OF
4'-0" MIN MIN LAP LAP 4'-0"
SP WHERE WHERE OCCURS OCCURS IS IS SP CONT BEHIND BEHIND LEDGER, LEDGER, TYP TYP CONT
D/10 D/10 MAX MAX
NO JOISTS JOISTS SHALL SHALL LAND LAND ON ON NO BOLTS WHEN WHEN SHAPED SHAPED PL PL BOLTS DOES NOT NOT OCCUR, OCCUR, TYP TYP DOES
FLAT CONDITION CONDITION FLAT
L N IA
DOUBLE 2X 2XTOP TOP PL, PL, DOUBLE TYP UNO UNO TYP
10 107/256"
R
(12) 16D 16D EA EA SIDE SIDE OF OF (12) SPLICE, STAGG STAGG (24 (24 TOTAL) TOTAL) SPLICE,
CONC OR OR MASONRY MASONRY WALL WALL CONC
EQ EQ EQ EQ
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
SHAPED PL PL WHERE WHERE OCCURS, OCCURS, TYP TYP SHAPED
CONC OR OR MASONRY MASONRY WALL WALL CONC
D/4 D/4
4'-0" MIN MIN LAP LAP 4'-0"
D D
PREDRILL SMALL SMALL DIA DIA PREDRILL HOLES AS AS REQUIRED REQUIRED HOLES
FRAMING, FRAMING, SEE PLAN PLAN SEE
770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
PROVIDE SHEATHING SHEATHING PROVIDE EN FULL FULL LENGTH LENGTH OF OF EN STRAPS && DOUBLE DOUBLE STRAPS FRAMING, TYP TYP FRAMING,
WHERE SP SP OCCURS OCCURS PROVIDE PROVIDE WHERE "SIMPSON" CS20, CS20, CONT CONT ONE ONE "SIMPSON" PIECE W/ W/ ALL ALL HOLES HOLES FILLED FILLED PIECE W/ 8d 8d NAILS, NAILS, TYP TYP W/
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
OPENINGS CUTTING CUTTING (2 (2 MAX) MAX) FRAMING FRAMING MEMBERS MEMBERS OPENINGS S-_061010_T008A S-_061010_T008A 160211. Q2 Q2 160211.
6'-0" MAX MAXSIZE SIZE 6'-0"
ISSUED "S" "S"
SPACE SINGLE SINGLE OPENINGS OPENINGS SPACE 12" OC OC MIN MIN EA EA WAY WAY 12" 11 227/256"
3 5/128"
3 5/128"
"S" "S" MAX MAX
1'-0"
SINGLE OPENINGS OPENINGS SINGLE UP TO TO 6" 6" MAX MAXMAY MAY UP BE PLACED PLACED WITH WITH NO NO BE ADDL BLKG BLKG REQ REQ ADDL SHEATHING, SHEATHING, SEE PLAN PLAN SEE
2 63/64"
2 63/64"
LOCATE 3" 3" MIN MIN FROM FROM LOCATE SHEATHING EDGES EDGES SHEATHING
USE FOR: FOR: USE SINGLE OPENINGS OPENINGS -- SINGLE GREATER THAN THAN 6" 6" GREATER IN SIZE SIZE IN SINGLE OPENINGS OPENINGS -- SINGLE LOCATED LESS LESS LOCATED THAN 3" 3" FROM FROM THAN SHEATHING EDGES EDGES SHEATHING GROUPS OF OF -- GROUPS SINGLE OPENINGS OPENINGS SINGLE SPACED LESS LESS THAN THAN SPACED 12" 0C 0C 12"
OPENINGS NOT NOT CUTTING CUTTING AA FRAMING FRAMING MEMBER MEMBER OPENINGS
MANAGEMENT
2'-0" MAX MAXSIZE SIZE 2'-0"
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
NOTE: NOTE: 1. SHEATHING SHEATHING REFERS REFERS TO TO GYPSUM GYPSUM BOARD BOARD OR ORSP SP 1.
TYP WOOD ROOF / FLOOR / CEILING FRAMING AT OPENINGS 1/4"==1'-0" 1'-0" 1/4"
S-_061010_T010A S-_061010_T010A 140127. Q2 Q2 140127.
TITLE
DETAILS - TYPICAL WOOD FRAMING
SHEET
5/15/2019 4:35:45 PM
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
FC, TYP TYP FC,
FRAMING, SEE SEE PLAN PLAN FRAMING,
A
DATE 01/04/2019 5/17/2019
BLKG SAME SAME SIZE SIZE BLKG AS FRAMING, FRAMING, TYP TYP AS
B
15
MARK
11 227/256"
1'-0"
SPACING SPACING PER PLAN PLAN PER
S-562
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
1"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
HSS POST, SEE PLAN
APP. 02-117123
2x8 LSL EA SIDE OF POST
SS
INC:
REVIEWED FOR
FOR FOR FLOORS FLOORS AND AND ROOFS ROOFS W/ W/ SLOPES SLOPES 2:12 2:12 OR OR FLATTER FLATTER PROVIDE PROVIDE T&G T&G SP SP AT AT ALL ALL EDGES EDGES NOT SUPPORTED BY NOT SUPPORTED BY BLKG BLKG
PROVIDE PROVIDE (2) (2) ROWS ROWS SP SP EN EN AT AT ALL ALL 4X 4X && WIDER WIDER FRAMING FRAMING && BLKG BLKG
FRAMING, FRAMING, SEE SEE PLAN PLAN
24" 24" MIN MIN STAGGER STAGGER AT AT END END JOINTS JOINTS
EQ
EQ
EQ
EQ
EQ
WHERE WHERE MULTIPLE MULTIPLE FRAMING FRAMING MEMBERS MEMBERS OCCUR, OCCUR, CENTER CENTER SP SP JOINT JOINT ON ON ONE ONE COMMON COMMON MEMBER MEMBER
EDGE EDGE NAILING, NAILING, TYP TYP AT AT EA EA SUPPORTED SUPPORTED EDGE EDGE EN EN AT AT FIELD FIELD BLKG BLKG WHERE WHERE OCCURS, SEE OCCURS, SEE PLANS PLANS
FRAMING FRAMING OR OR BLKG, BLKG, SEE SEE PLANS PLANS (2X (2X MIN) MIN)
SECTION SECTION
TYP NAILING AT STRUCTURAL PANEL JOINTS S-_061010_T024A S-_061010_T024A 140127. 140127. Q2 Q2
3" 3" ==1'-0" 1'-0"
SP SP EN EN FULL FULL HT HT OF OF POST POST
1"CLR CLR 1" 4"CLR CLR 4"
3" 3" CLR CLR
HOLDOWN HOLDOWN && POST POST WHERE WHERE OCCURS, OCCURS, SEE SEE PLAN PLAN FOR FOR SIZE SIZE && LOCATION LOCATION
SEE SEE PLAN PLAN TOF TOF
ADDITIONAL ADDITIONAL VERT VERT BAR BAR TO TO MATCH TYP FTG VERT MATCH TYP FTG VERT REINF REINF INCREASE FTG WIDTH AS REQ TO MAINTAIN CLR
3" CLR MIN
DETAIL
9
13
1" = 1'-0"
DETAIL 1 1/2" = 1'-0"
Q2
Q1
LEDGER, SEE PLAN
SP, SP, SEE SEE SHEARWALL SHEARWALL SCHEDULE SCHEDULE FOR FOR TYPE TYPE && NAILING NAILING NO NO PANEL PANEL LESS LESS THAN THAN 12" 12" IN IN ANY ANY DIMENSION DIMENSION SHALL SHALL BE BE USED, USED, ADJUST ADJUST LAYOUT LAYOUT AS AS NEEDED NEEDED
2'-01/2"
HSS EA SIDE, SEE PLAN
FESSIONA PRO L ED RRY J. VOLKE E
T
TEHAMA CENTER STUDENT SERVICES
3/4" DIA ATR HSS POST, SEE PLAN
2X NAILER W/ BOLTS PER 6/S-561,TYP
770 DIAMOND AVE RED BLUFF, CA 96080
STUD WALL, SEE PLAN
"SIMPSON" STRONGWALL, SEE ELEVATION
3'-6" 3'-4"
SILL SILL PLATE PLATE
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
PLAN PLAN
TYP SP LAYOUT - SHEAR WALL
SP SP AT AT TWO TWO SIDED SIDED SHEARWALL SHEARWALL WHERE OCCURS, WHERE OCCURS, SEE SEE PLAN PLAN && SCHEDULE SCHEDULE
S-_061010_T023A S-_061010_T023A 140127. 140127. Q2 Q2
1/4" 1/4" ==1'-0" 1'-0"
DETAIL
10
14
1" = 1'-0"
AB AB W/ W/ NUT NUT PER PER PLANS PLANS && SHEAR SHEAR WALL WALL SCHEDULE SCHEDULE STD STD CUT CUT WASHER WASHER WHERE WHERE "SIMPSON" "SIMPSON" BP/BPS BP/BPS OCCURS OCCURS
SP SP 1/2" 1/2" MAX MAX
PLAN PLAN AT AT INTERSECTION INTERSECTION AB AB DIA DIA
POST POST FASTENERS FASTENERS
HDU2 HDU2
5/8" 5/8"
(6) (6) SDS SDS 1/4"x2 1/4"x2 1/2" 1/2"
POST POST WIDTH WIDTH UNO UNO (2) (2) 2X 2X
HDU4 HDU4
5/8" 5/8"
(10) (10) SDS SDS 1/4"x2 1/4"x2 1/2" 1/2"
4X 4X
HDU5 HDU5
5/8" 5/8"
(14) (14) SDS SDS 1/4"x2 1/4"x2 1/2" 1/2"
4X 4X
HDU8 HDU8
7/8" 7/8"
(20) (20) SDS SDS 1/4"x2 1/4"x2 1/2" 1/2"
8X 8X
HDU11 HDU11
1" 1"
(30) (30) SDS SDS 1/4"x2 1/4"x2 1/2" 1/2"
8X 8X
HDU14 HDU14
1" 1" W/ W/ HEAVY HEAVY HEX HEX NUT NUT
(36) (36) SDS SDS 1/4"x2 1/4"x2 1/2" 1/2"
8X 8X
EN EN
0.229" 0.229" xx 3" 3" SQ SQ MIN MIN PLATE PLATE WASHER. WASHER. CONTRACTOR CONTRACTOR OPTION OPTION TO TO PROVIDE PROVIDE "SIMPSON" "SIMPSON" BP/BPS BP/BPS WASHER WASHER && STD STD CUT CUT WASHER WASHER TO TO REPLACE REPLACE TYP TYP PLATE PLATE WASHER WASHER SILL PLATE SILL PLATE
"SIMPSON" A35 T&B EA END OPNG
2X8 LSL EA SIDE OF HSS,TYP
OPNG
MANAGEMENT
10 S-563
HSS EA SIDE, SEE PLAN
TYP SHEAR WALL SILL BOLT 3" 3" ==1'-0" 1'-0"
S-_061010_T056A S-_061010_T056A 151005. 151005. Q1 Q1
017294 ?00.00.00? LIONAKIS 2017
AGENCY
ELEVATION
DETAIL
11
1" = 1'-0"
Q2 SAD
HSS EA SIDE, SEE PLAN
"SIMPSON" STRONGWALL, SEE ELEVATION
OPNG
2X8 LSL EA SIDE OF HSS,TYP #3 HAIRPIN TIE @ 3" OC MAX & 1 1/2" FROM TOP ((3) TIES MIN)
CURB
6"
CL STRONGWALL & FTG
HSS BEYOND, SEE PLAN "SIMPSON" STRONGWALL, SEE ELEVATION #3 HAIRPIN TIE
TOC SEE PLAN 1" DIA ANCHOR ROD, TYP OF (2) W/ HEAVY HEX NUTS EA STRONG WALL. de = 18" MIN
TOF SEE PLAN
de
(2) #4 CLOSED TIES ES OF STRONGWALL ANCHOR, TYP
12
DETAIL
10" TYP
A
ELEVATION
TITLE
DETAILS - TYPICAL WOOD SHEAR WALL FRAMING
SEE PLAN
A
3" CLR
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt 5/15/2019 4:35:46 PM
S-_061010_T017A S-_061010_T017A 151002. 151002. Q2 Q2
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
"SIMPSON" STRONGWALL, SEE ELEVATION
NOTES: NOTES: 1. 1. MULTIPLE MULTIPLE MEMBERS MEMBERS AT AT POSTS POSTS SHALL SHALL BE BE INTERCONNECTED INTERCONNECTED WITH WITH 16D 16D @ @ 6" 6" OC OC MAX, MAX, STAGGERED, STAGGERED, FULL FULL HEIGHT. HEIGHT. 2. 2. WHEN WHEN HOLDOWN HOLDOWN && POST POST ARE ARE INDICATED INDICATED PER PER PLAN PLAN AT AT OPENING OPENING JAMBS, JAMBS, THE THE POST POST SHALL SHALL REPLACE THE KING STUDS REQ IN "TYP FRAMING AT OPENINGS" DETAIL. REPLACE THE KING STUDS REQ IN "TYP FRAMING AT OPENINGS" DETAIL.
7
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
BEAM, SEE PLAN
CONC CONC
TYP HDU HOLDOWN
DATE 01/04/2019 5/17/2019
ATTACH 2X TO HSS EACH SIDE PER 6/561, TYP OVER OPENING
BEAM, SEE PLAN
1/8"TYP TYP 1/8"
"SIMPSON" "SIMPSON" DESIGNATION DESIGNATION
3/4" 3/4" ==1'-0" 1'-0"
MARK
WOOD WOOD STUD STUD
SP SP EN EN FULL FULL HT OF HT OF POST, POST, TYP TYP
3
Q1
ISSUED
HDR, SEE PLAN
POST POST TO TO MATCH MATCH STUD WIDTH STUD WIDTH EA EA DIRECTION, DIRECTION, SEE SEE PLAN PLAN
B
1 1/2" = 1'-0"
9 S-563
2X 2X STUD STUD FULL FULL HT HT W/ W/ 16D 16D @ @ SP SP EN EN SPACING SPACING (STAG) (STAG) ((2) ((2) ROWS ROWS AT AT TWO-SIDED TWO-SIDED SHEARWALLS) SHEARWALLS) TYP TYP EA EA FACE FACE OF OF POST POST NOTCH NOTCH STUD STUD FOR FOR HOLDOWN HOLDOWN
PLAN PLAN AT AT CORNER CORNER
DETAIL
Q2
SP SP TYP, TYP, SEE SEE PLAN PLAN
A RU C T UR O F OF I CAL
PROJECT
16D @ 6" OC,TYP
2'-0"
T
E
No. S3737
05/15/2019
2X8 LSL EA SIDE OF HSS,TYP
SP SP EN EN FULL FULL HT HT OF STUD OF STUD AT AT END END OF OF WALL WALL && FIRST FIRST FULL FULL HT HT STUD ADJACENT STUD ADJACENT TO TO OPNG OPNG
SECTION SECTION
6
SEAL
4X BLKG W/ CMSTC16, EXTEND 12'-0" INTO MECH WELL ROOF
2'-01/2"
SILL SILL BOLTS, BOLTS, SEE SEE PLAN PLAN && SHEARWALL SHEARWALL SCHEDULE SCHEDULE FOR FOR SIZE SIZE && SPACING SPACING
JOIST & HANGER SEE PLAN
(25) 16D SINKERS FROM STRAP TO FIRST BLOCK. 16D @ 6" OC TYP BEYOND
BOT BOT OF OF FTG FTG
ELEVATION ELEVATION
EQ
A
C
DOOR DOOR OR OR WINDOW WINDOW OPNG, OPNG, SEE SEE PLAN PLAN && TYP TYP DETAIL DETAIL
EQ
DBL DBL TOP TOP PL, PL, TYP, TYP, UNO UNO
SEE SEE TYP TYP DETAIL DETAIL FOR FOR SP SP JOINTS JOINTS
SP SP EN EN FULL FULL HT HT OF OF HOLDOWN HOLDOWN POSTS POSTS
EN FULL LENGTH OF EACH JOIST
S
"SIMPSON" "SIMPSON" HOLDOWN HOLDOWN PER PER PLAN PLAN
(4) 1/4" x 4 1/2" SDS EQ SPACED
PLAN S-_061010_T022A S-_061010_T022A 140127. 140127. Q2 Q2
1/4" 1/4" ==1'-0" 1'-0"
STUD STUD DEPTH DEPTH BLKG BLKG @ @ ALL ALL HORIZ HORIZ EDGES, EDGES, SEE SEE SHEAR SHEAR WALL WALL SCHEDULE SCHEDULE FOR FOR THICKNESS THICKNESS
POST POST FASTENERS FASTENERS
TYP TYP AB, AB, HEX HEX HEADED HEADED BOLT BOLT -OR-ORTHREADED THREADED ROD ROD W/ W/ DBL DBL HEX HEX NUTS NUTS AT AT BOT BOT
5
1'-4"
5 1/2"
6X10 BLK W/ A35 ES EACH END
CONSULTANT
ST
TRIMMER TRIMMER STUD(S) STUD(S) WHERE WHERE OCCURS OCCURS AT AT OPENINGS OPENINGS POST POST DEPTH DEPTH PER PER TABLE TABLE ABOVE, ABOVE, WIDTH TO MATCH STUD WIDTH TO MATCH STUD WIDTH, WIDTH, UNO UNO ON ON PLANS PLANS
5 1/2"
TYP STRUCTURAL PANEL LAYOUT ROOF / FLOOR
(2) ROWS OF 1/4" x 3 1/2" SDS @ 3" OC MAX VERT, ((8) TOTAL)
JOIST & HANGER SEE PLAN
NOTES: NOTES: 1. 1. SEE SEE PLANS PLANS FOR FOR DIAPHRAGM DIAPHRAGM NAILING NAILING SCHEDULE, SCHEDULE, NAIL NAIL SIZE, SIZE, SPACING SPACING && SP. SP. 2. 2. NO NO PANEL PANEL LESS LESS THAN THAN 24" 24" IN IN ANY ANY DIMENSION DIMENSION SHALL SHALL BE BE USED, USED, ADJUST ADJUST LAYOUT LAYOUT AS AS NEEDED. NEEDED. 3. WHERE PLAN CALLS FOR EDGE BLOCKING, USE THE FOLLOWING: 3. WHERE PLAN CALLS FOR EDGE BLOCKING, USE THE FOLLOWING: FOR FOR 8d 8d SP SP NAILING, NAILING, USE USE 2X4 2X4 FLAT FLAT W/ W/ "SIMPSON" "SIMPSON" Z28 Z28 EA EA END END W/ W/ (2) (2) 10DX1 10DX1 1/2" 1/2" FOR FOR 10d 10d SP SP NAILING, NAILING, USE USE 3X4 3X4 FLAT FLAT W/ W/ "SIMPSON" "SIMPSON" Z38 Z38 EA EA END END W/ W/ (2) (2) 10DX1 10DX1 1/2" 1/2" OR OR FASTEN FASTEN BLOCKING BLOCKING NOTED NOTED TO TO FRAMING FRAMING PER PER NAILING NAILING SCHEDULE. SCHEDULE.
2X 2X STUDS STUDS UNO, UNO, SEE SEE PLANS PLANS && SHEARWALL SHEARWALL SCHEDULE SCHEDULE
EQ EQ
"SIMPSON" STRONGWALL, SEE ELEVATION
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
EER GIN EN R
11 1/4" 1/4"
3/4" DIA ATR
4'X8' 4'X8' SHEETS, SHEETS, TYP, TYP, UNO UNO
1'-4"
1
JOIST & HANGER SEE PLAN
(14) 1/4" DIA X 3 1/2" SDS SCREWS
L N IA
EQ
EQ
2x12 TYP
R
2 1/256" EQ
3/8" 3/8" @ @ 2X 2X FRAMING FRAMING (4) (4) EQ EQ SPACES: SPACES: 5/8" 5/8" @ @ 3X 3X FRAMING FRAMING
LEDGER, SEE PLAN
EDGE EDGE BLKG BLKG WHERE WHERE REQ, REQ, SEE SEE PLANS PLANS
2 1/256" 2"
SP SP PER PER PLANS PLANS
07/03/2019
HEADER, SEE PLAN
PLAN PLAN D
✔
FIELD FIELD NAILING, NAILING, TYP TYP AT AT SUPPORTS SUPPORTS NOT NOT AT AT EDGES EDGES
SEE SEE TYP TYP DETAIL DETAIL FOR FOR SP SP JOINTS, JOINTS, CENTER CENTER SP SP JOINTS JOINTS ON FRAMING ON FRAMING && BLKG, BLKG, TYP TYP
NAIL NAIL SPACING SPACING PER PER PLANS PLANS
ACS
✔
STUDS O/ HEADER @ 16" OC MAX
NAIL NAIL SPACING SPACING PER PER PLANS PLANS
2"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1/8" 1/8" GAP GAP TYP TYP
DATE:
FLS
REGIST ER K
STAGGER STAGGER NAILS NAILS EA EA SIDE SIDE OF OF JT JT
✔
1" CLR
0 1/4" 1/2"
CL CL FRAMING FRAMING CL CL SP SP JOINT JOINT
10" MAX
#4 CLOSED TIES @ 8" OC TYP DBL HEAVY HEX NUT W/ PL WASHER BTWN
SEE PLAN
A
INNER TIES ONLY REQUIRED WHERE ADDL TIES ARE NOTED ON ELEVATION
SECTION
SHEET
S-563
1" = 1'-0"
Q2
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
1/8DEPTH DEPTH PLUS PLUS ONE ONE LAMINATION LAMINATION 1/8
TENSION ZONE ZONE == BOTTOM BOTTOM FULL FULL LENGTH LENGTH TENSION
✔
07/03/2019
"SIMPSON" DTC DTC AT AT EA EA "SIMPSON" TRUSS CHORD/BLKG CHORD/BLKG TRUSS (SLOTTED LEG LEG VERTICAL) VERTICAL) (SLOTTED
1/8 DEPTH DEPTH PLUS PLUS ONE ONE LAMINATION LAMINATION 1/8
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
1/2" 1/2" CLR CLR
D
1/2" 1/2" CLR CLR
SIMPLE BEAM BEAM SIMPLE
DEPTH DEPTH
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
ACS
✔
DEPTH DEPTH
DATE:
FLS
BOTTOM CHORD CHORD BOTTOM
CONSULTANT
2x4 BLKG BLKG @ @ 48" 48" OC OC W/ W/ 2x4 "SIMPSON" Z28 Z28EA EA END END W/ W/ "SIMPSON" (2) 8d 8dTO TO TRUSS TRUSS && BLKG BLKG (2)
TENSION ZONE ZONE == TOP TOP && BOTTOM BOTTOM FULL FULL LENGTH LENGTH TENSION
PARALLEL TO TO JOISTS JOISTS PARALLEL
CONTINUOUS OR OR CANTILEVER CANTILEVER BEAM BEAM CONTINUOUS
PERPENDICULAR TO TO JOISTS JOISTS PERPENDICULAR
NOTE: NOTE: 1. HATCHED HATCHED AREA AREA INDICATES INDICATES ZONE ZONE OF OF REQUIRED REQUIRED 6" 6" MIN MIN END END JOINT JOINT SPACING SPACING IN IN ADJACENT ADJACENT 1. LAMINATIONS PER PER ANS1/AITC ANS1/AITC STANDARD STANDARD A190.1 A190.1 LAMINATIONS
TYP GLU-LAM BEAM END JOINT SPACING
1
S-_061800_T103A S-_061800_T103A 140127. Q2 Q2 140127.
1"==1'-0" 1'-0" 1"
TYP INTERIOR NON-STRUCTURAL WALL ANCHORAGE AT OPEN WEB JOISTS
5
S-_061970_T250A S-_061970_T250A 140127. Q2 140127. Q2 Q2 140127.
1"==1'-0" 1'-0" 1"
2
3/16 3/16
3/16 3/16 L4X4X1/4 X 4" LONG
C.4 3/8" BENT PLATE W/ 3" VERT LEG X 6" WIDE TYP EACH CORNER OF LOUVER
3" MIN
HSS HORIZ, SEE ELEV
FOR ADDL INFORMATION, SEE
18 S-566
SEAL
T
S
ST
A
T
HSS COL, SEE PLAN
E
No. S3737
L N IA
TYP T&B
A RU C T UR O F OF I CAL
R
3/16 3/16
TYP T&B
REGIST ER K
3/16 3/16
1" MAX
EER GIN EN R
FESSIONA PRO L ED RRY J. VOLKE E
05/15/2019
LOUVER FRAME SEE PLAN
HSS, SEE PLAN C
PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
TYP LOUVER FRAME CONNECTION
TYP COL TO HORIZ GIRT
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
DETAIL
2
13 S-563
GLB WIDTH WIDTH GLB
COL CAP CAP COL AT SPLICE SPLICE AT
COLCAP CAP COL AT END END AT
1/8" 33 1/8"
CC0Q4 CC0Q4
ECC0Q4 ECC0Q4
1/8" 55 1/8"
CC0Q6 CC0Q6
ECC0Q6 ECC0Q6
3/4" 66 3/4"
CC0Q7 CC0Q7
ECC0Q7 ECC0Q7
3/4" 88 3/4"
CC0Q9 CC0Q9
ECC0Q9 ECC0Q9
ISSUED
MARK
HDR BTWN COLS, SEE PLAN
SPLICE GLB GLB AT AT CL CLOF OF COL COL SPLICE WHERE SHOWN SHOWN ON ON PLANS PLANS WHERE
END OF OF END CANTILEVER CANTILEVER GLB,WHERE WHERE GLB, OCCURS OCCURS
B
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
JOIST, SEE PLAN
1/2"CLR CLR AT ATSPLICE SPLICE 1/2" SEE PLAN PLAN SEE
DATE 01/04/2019 5/17/2019
B 6X6 SILL W/ A35 EACH SIDE, EACH END, TYP
BOLT DBL JAMB TO POST PER S-566 ATTACH HDR TO DBL JAMB W/ HU612
AA
HSS COL, SEE PLAN
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
COL CAP, CAP, SEE SEE COL SCHED SCHED
GLB, SEE SEE PLAN PLAN GLB,
AA
TYP GLB OVER COLUMN
3
B S-_061800_T101A S-_061800_T101A 140127. Q2 Q2 140127.
1"==1'-0" 1'-0" 1"
13 S-563
DETAIL
A 2
1/4" x 4" "SIMPSON" SDS SCREW
COL CL GLB WIDTH + 11/8" MAX 2"
6" 8"
PL 3/8
GLB
2" MIN
1/2"
A
1/2"
1/2"
(2) 3/4" DIA BOLTS
1/2"
PERP BEAM AT ALT COND
1 1/2"
SHIM PL ES (1/2" MAX), SHIM PL ES WHERE OCCURS OF GLB
3" 2"
3/8" SEAT PL
BEARING SEAT BELOW
2" 3" 2"
GLB PER PLAN
6"
5 3/8"
GLB WIDTH + 1/8" (1/8)
GLB BLW
COL WIDER THAN BEAM
4"
1/4" PL ES OF COL 3 SIDES
1/4
A
A
GLB WIDTH - 7/8" MIN 1/2"
DETAIL
1/2"
TITLE
SEAT PL TO SIDE PL
1/4
GLB WIDTH + 1/8"
SEAT PL TO COL
1/4
3/16
3
6"
7 1/8"
GLB, SEE PLAN
4 SIDES EA SHIM PL
HSS COL PER PLAN
TYP GLB TO HSS COLUMN 1" = 1'-0"
DETAILS - TYPICAL MANUFACTURED LUMBER FRAMING
BEAM WIDER THAN COL
NOTE: WHERE COLUMN IS WIDER THAN GLULAM BEAM, WELD SIDE PLATES TO COLUMN FACE WITH 1/4" FILLET EACH SIDE, TYP
4
JOIST, SEE PLAN
3/16
SHIM PL ES OF HSS
5/15/2019 4:35:47 PM
SIM
EQ
1"
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
AGENCY
1/4 1/4
STEEL COL, COL, STEEL SEE PLAN PLAN SEE
S-_061800_T100A 140127. Q2
SHEET
8
DETAIL 1" = 1'-0"
S-564
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
INC:
REVIEWED FOR
0 1/4" 1/2"
TOP FLANGE OR FACE MOUNT JOIST OR BEAM HANGER, SEE PLAN
SS
TYP
WALL ABOVE
A
"S"
SPACING PER PLAN
✔
DATE:
3X "S" MAX
FLS
ACS
✔
✔
07/03/2019
HANGER, TYP DBL FRAMING EA SIDE
1 35/64" 1 35/64"
SNUG FIT
1 1/2" MIN EA SIDE
STIFFENERS AT CONCENTRATED LOADS
SP EN TO BLKG (2 ROWS AT INTERIOR WALLS)
TYP
B
GAP, UNO 1/8" MIN 2 3/4" MAX
A35 EA SIDE EA END
1 1/2" MAX
OPENINGS CUTTING (2) FRAMING MEMBERS 6'-0" MAX SIZE
SPACING PER PLAN
SNUG FIT
"S"
2X "S" MAX
DBL FRAMING EACH SIDE
SECTION
JH TYP BEAM, WALL OR HANGER, SEE PLANS
DETAIL
STRAP TO EXTEND 1X "S" PAST DBL FRAMING, TYP
MIN 3X4 FLAT BLKG, TYP
STIFFENERS AT BEARINGS
TYP I-JOIST BLOCKING DETAIL
HANGER TYP S-_061960_T200A 140127. Q2
WEB STIFFENER SIZE AND MATERIAL FLANGE WIDTH WEB STIFFENER SIZE, UNO 1 3/4" 5/8" x 2 5/16" 2 1/2"
1"x 2 5/16"
3 1/2"
2x4
3 1/2" PSL, SAME DEPTH AS JOISTS
SHEATHING (WITH FACE GRAIN VERTICAL) THAT MEETS THE REQUIREMENTS OF PS1 OR PS2
CONSTRUCTION GRADE OR BETTER CONSTRUCTION GRADE OR BETTER RED-I90HS JOISTS REQUIRE LVL / LSL
WHERE SP OCCURS PROVIDE "SIMPSON" CS20, CONT ONE PIECE W/ ALL HOLES FILLED W/ 8d NAILS, OPENINGS TYP
RED-I45 TJI 230 JOISTS
BEAM WHERE OCCURS
RED-I90 & REDI90H JOISTS
SPACING PER PLAN
RED-I90HS JOISTS
CUTTING (1) FRAMING MEMBER
"S"
SPACE SINGLE OPENINGS 12" OC MIN EA WAY
11 7/8"
3
3
3
3
4
14"
3
5
3
3
6
16"
3
6
4
4
6
18"
3
7
4
4
8
SINGLE OPENINGS UP TO 6" MAX MAY BE PLACED WITH NO ADDL BLKG REQ SHEATHING, SEE PLAN
"S" "S" MAX MAX
N/A
1'-0" 1'-0"
N/A
END OR INTERMEDIATE N/A
END
3 5/128" 3 5/128"
INTERMEDIATE
16D NAILS
2 63/64" 2 63/64"
"SIMPSON" TB TENSION BRIDGING W/ (2) 10D X 1 1/2" EA END NAIL BOT ENDS ONLY AFTER ALL ROOF OR FLOOR LOADS ARE APPLIED
AT WALL W/ LEDGER
TYP I-JOIST BRIDGING 3/4" = 1'-0"
26"
N/A
11
7
14
14
28"
N/A
12
8
15
14
OPENINGS NOT CUTTING A FRAMING MEMBER
30"
N/A
13
8
17
16
2'-0" MAX SIZE
32"
N/A
N/A
9
18
18
NOTES: 1. WEB STIFFENERS REQUIRED EA SIDE OF I-JOISTS AT ALL BEARING POINTS AND CONCENTRATED POINT LOADS. 2. WEB STIFFENERS SHALL REMAIN VERTICAL AT SLOPED I-JOISTS (CONDITION NOT SHOWN).
NOTE: 1. ALL I-JOISTS REQUIRE BRIDGING PER MFR REQUIREMENTS
2
3 8 5 5 10 NOTES:20" 1. WEB STIFFENERS REQUIRED EA SIDE OF I-JOISTS AT ALL BEARING POINTS AND 22" N/A 9 6 11 10 CONCENTRATED POINT LOADS. 2. WEB AT SLOPED I-JOISTS SHOWN). 24"STIFFENERS SHALL N/A REMAIN VERTICAL 10 6 13 (CONDITION NOT 12
S-_061960_T202A 140127. Q2
6
LOCATE 3" MIN FROM SHEATHING EDGES
TYP I-JOIST WEB STIFFENERS 3/4" = 1'-0"
S-_061960_T211A 140127. Q2
USE FOR: - SINGLE OPENINGS GREATER THAN 6" IN SIZE - SINGLE OPENINGS LOCATED LESS THAN 3" FROM SHEATHING EDGES - GROUPS OF SINGLE OPENINGS SPACED LESS THAN 12" OC LSL BLKG SAME DEPTH AS FRAMING, TYP FRAMING, SEE PLAN
T
A
END OR INTERMEDIATE N/A
16D NAILS
T
S
END OR INTERMEDIATE 3
8D NAILS
ST
C
AT WALL W/ DBL TOP PL
FESSIONA PRO L ED RRY J. VOLKE E
11 227/256"
8D NAILS
I-JOIST DEPTH
9 1/2"
2X BLKG
SEAL
4'-0" MAX SIZE
11 227/256"
15/16"15/16"
0"
RED-I65 TJI 360 JOISTS
PROVIDE SHEATHING EN FULL LENGTH OF STRAPS & DBL FRAMING, TYP
E
EER GIN EN R
STUD, MASONRY OR CONCRETE WALL
FRAMING, SEE PLAN
WEB STIFFENER MATERIAL
NAILING QUANTITIES FOR WEB STIFFENER ATTACHMENT STAGGER ADJACENT STRAPS TO PROVIDE 1/2" CLEAR
CONSULTANT
No. S3737
L N IA
B
1" = 1'-0"
PROVIDE SHEATHING EN FULL LENGTH OF STRAPS & DBL FRAMING, TYP
A RU C T UR O F OF I CAL
R
10d @ " OC STAG A SIDE OF WEB
A
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
1 1/2"1 1/2"
1 1/2" LSL TO MATCH I-JOIST DEPTH,
WHERE SP OCCURS PROVIDE "SIMPSON" CS20, CONT ONE PIECE W/ ALL HOLES FILLED W/ 8d NAILS, TYP
FRAMING, SEE PLAN
REGIST ER K
6 S-565
SPACE NAILS EQUALLY STAG IN (2) ROWS
10 7/64" 10 7/64"
STIF PER DETAIL
1 33/64" 1 33/64"
1 1/2" MAX
11 1/2" 1/2"
2 1/8"2 1/8"
B
I-JOIST BLK PANEL W/ (4) 10d TN EA END BTWN EA I-JOIST W/ FACTORY INSTALLED MICROLAM LVL END BLOCKS
1
WALL ABOVE WHERE WALL ABOVE OCCURS, SNUG FIT T&B
3 1/2" PSL, SAME DEPTH AS JOISTS
2X 2X "S" "S" MAX MAX
GAP 1/8" MIN, 2 3/4" MAX
HANGER TYP
SECTION
A
SILL PL NAILING TO BLKG STAG
D
1 1/2" 1 1/2"
3x "S" MAX
2 1/8"2 1/8"
GAP, UNO 1/8" MIN 2 3/4" MAX
1 1/2" MAX
A
STRAP TO EXTEND 2X "S" PAST TRIPLE FRAMING, TYP
MIN 3x4 FLAT BLKG, TYP
1 33/64" 1 33/64"
DETAIL
8 1/16" 8 1/16"
SPACE NAILS EQUALLY STAG IN (2) ROWS
3/4"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
1 1/2" MAX
B
DBL FRAMING EA SIDE
05/15/2019 PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
FC, TYP CLIENT
NOTE: 1. SHEATHING REFERS TO GYPSUM BOARD OR SP
9
TYP I-JOIST ROOF / FLOOR / CEILING FRAMING AT OPENINGS 1/4" = 1'-0"
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
S-_061960_T203A 140127. Q2 ISSUED
MARK
B
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
(2) ROWS OF 10D NAILS @ 12" OC, EA JOIST TO FILLER BLOCK. USE RED-I90 JOISTS. 16D NAILS AT TJI 360 JOISTS. CLINCH NAILS WHEN POSSIBLE
CONT FILLER BLOCKING BY MFR
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 ?00.00.00? LIONAKIS 2017
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
AGENCY
3
A
TYP MULTIPLE I-JOISTS 1" = 1'-0"
S-_061960_T207A 160711. Q2
TITLE
DETAILS - TYPICAL WOOD I-JOIST FRAMING
5/15/2019 4:35:48 PM
SHEET
S-565
2
3
4
GRID
5
1"
1" MIN AFTER DAP
DAP TOP PL IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
SEEPLAN PLAN SEE
4XSHAPED SHAPEDBLKG BLKG 4X
1/2" DIA STUD BOLT @ 24" OC
"SIMPSON" LSTA AT PLATE SPLICE
MSTA24EVERY EVERYOTHER OTHER MSTA24 JOIST,FILL FILLALL ALLHOLES HOLES JOIST,
GRID GRID
2XJOISTS JOISTS 2X
3/8" 113/8"
TOF TOF SEEPLAN PLAN SEE
1/2"DIA DIASTUD STUD 1/2" BOLT@@24" 24"OC OC BOLT
GRID GRID
2XSTUD STUDWALL WALL 2X
MSTA12EVERY EVERY MSTA12 OTHERJOIST JOIST OTHER
2XW/ W/16d 16d@@6"6"OC OC 2X
2'-0" 2'-0"
2X6BELOW BELOW 2X6 STUDWALL STUDWALL
7/8" 117/8"
55
TYPICALTOP TOPPLATE PLATE TYPICAL AT TOP OF LOUVER
TYPICALJAMBS JAMBS TYPICAL
1/2X91/2" 1/2"2.0E 2.0EPARALLAM PARALLAMPSL PSL 331/2X9
4X6BLKG BLKGWHERE WHERE 4X6 STRAP OCCURS STRAP OCCURS
DBL STRAP WHERE OCCURS, SEE PLAN
EN EN
1'-0" 1"1"= =1'-0"
PLANVIEW VIEW PLAN
TYPHSS HSSMEMBER MEMBERCONNECTIONS CONNECTIONS TYP 13 13
TYPCORNER CORNERCONSTRUCTION CONSTRUCTION TYP 17 17
1/2"= =1'-0" 1'-0" 1 11/2"
1/2"= =1'-0" 1'-0" 1/2"
Q1 Q1
4XBLKG BLKG 4X 2XWEB WEBSTIFFENER STIFFENER 2X
GRID GRID
MSTA24@@8"8"OC OCEN EN MSTA24 TOI-JOIST I-JOISTWHERE WHERE TO STRAPOCCURS OCCURS STRAP
(10)16D 16DEA EABLK BLKWHERE WHERE (10) STRAPOCCURS OCCURS STRAP
Q1 Q1
GRID
GRID (t-1/8) (t-1/8)
1/2"LSL LSLLEDGER LEDGERW/ W/ 111/2" (5)16D 16DEA EASTUD STUDCONTACT CONTACT (5)
EN EN
ROOFSP SP ROOF
2020 S-566 S-566
CMST12STRAP, STRAP,FILL FILLEVERY EVERY CMST12 OTHERHOLE HOLEO/O/4X 4XBLKG BLKG OTHER
GRID GRID
2'-0" 2'-0"
"SIMPSON" "SIMPSON" LUS210EA EAEND END LUS210
16D@@6"6"OC OCLSL LSLLEDGER LEDGERTO TOBLKG BLKG 16D
DETAIL DETAIL
CONSULTANT 2'-0" 2'-0"
3/4X91/2" 1/2"2.0E 2.0E 113/4X9 PARALLAM PSL PARALLAM PSL
PLATE ABOVE SILLHEIGHT HEIGHT SILL SAD SAD
PJPTOP TOP&& PJP BOTFLANGE FLANGE BOT
PJP PJP SEE PLAN SEE PLAN
CAPPL PLTO TOMATCH MATCHHSS HSS CAP WALLTHICKNESS THICKNESS(GRIND (GRINDTO TO WALL MATCH HSS PROFILE) MATCH HSS PROFILE)
(t-1/8) (t-1/8)
SEE PLAN SEE PLAN
PJP PJP
(t-1/8) (t-1/8)
2XBLKG BLKGW/ W/A35 A35 2X
C
"SIMPSON"H2.5A H2.5A "SIMPSON" EASIDE SIDE EA CMST12AT ATLSL LSL CMST12 SPLICE W/ (44) 16D SPLICE W/ (44) 16D EASIDE SIDEOF OFSPLICE SPLICE EA
2X12FASCIA FASCIA 2X12 BEAMPER PERPLAN PLAN BEAM
EN EN POSTBEYOND BEYOND POST SHAPED PL, 1 1/2" MIN THK
66 S-565 S-565
11
66 WEBSTIFF, STIFF,SEE SEE WEB S-565 S-565
2X6BRACE BRACE@@5'-4" 5'-4"OC OCW/ W/(3) (3)16 16EA EAEND END 2X6
"SIMPSON"L90 L90TYP TYPAT AT "SIMPSON" EAJOIST. JOIST.AT ATEND END EA JOISTOF OFEA EAROOF ROOF JOIST SECTION,PROVIDE PROVIDE(3) (3) SECTION, A35,ALT ALTSIDES SIDESOF OF A35, JOIST&&STAG STAG JOIST
STRAP AT SIM COND B, SEE PLAN
1/2"CONT CONTLSL LSL 111/2" RIM JOIST RIM JOIST
NON-EXPOSED NON-EXPOSED
SP,SEE SEEPLAN PLAN SP,
11
DETAIL DETAIL
66
NAILPL PLTO TOBEAM BEAMW/ NAIL W/ @ 16D 6"OFFSET OC 16D 6"@ OC NAIL OM STRAP
1'-0" 1"1"= =1'-0"
TOF TOF
T
PARALLAM PARALLAM PER PLAN PER PLAN 2XJOISTS JOISTS@@24" 24"OC OC 2X W/"SIMPSON" "SIMPSON"A35 A35 W/ EAEND END EA
FASCIA,SAD SAD 2x2xFASCIA,
"SIMPSON" H8 EA JOIST "SIMPSON" H8 EA JOIST EA SIDE WALL SP, SIDE VARIES, SEE PLAN
HSS, SEE PLAN HSS FRAME WHERE OCCURS, SEE SP, SEE PLAN
GRID
TEHAMA CENTER STUDENT SERVICES
PARALLAM PARALLAM PERPLAN PLAN PER
EN
GRID
SP, SEE PLAN
STUD WALL, SEE PLAN NOTES: NOTES: SEESTRUCTURAL STRUCTURALSTEEL STEELNOTES NOTESFOR FORCRITERIA CRITERIAWHERE WHERECONNECTIONS CONNECTIONSARE AREEXPOSED EXPOSEDAND AND 1.1. SEE VISIBLETO TOTHE THEPUBLIC PUBLICAND ANDBUILDING BUILDINGOCCUPANTS OCCUPANTS(OTHER (OTHERTHAN THANMAINTENANCE MAINTENANCEAREAS). AREAS). VISIBLE THEHSS HSSWALL WALLTHICKNESS THICKNESS 2.2. "t""t"ISISTHE
TYP HSS CORNER & SPLICE 14 TYP HSS CORNER & SPLICE 14
I-JOIST, SEE PLAN
LSL CONT RIM BOARD TOF SEE PLAN
DETAIL 18 DETAIL 18 1'-0" 1"1"= =1'-0"
B
4'-0" 4'-0"
1 1/2" LSL BLKG @ 2'-0" W/ FC EA END
SP EN TO BLKG LSL CONT RIM BOARD
SP, SEE PLAN
1 1/2" LSL BLKG @ 2'-0" W/ FC EA END
WOOD STUD WALL, SEE PLAN
SPEN ENTO TOGLB GLB SP SP,SEE SEEPLAN PLAN SP,
2x FASCIA, SAD 2X BLKG W/ A35
SP, SEE PLAN
JOIST,SEE SEEPLAN PLAN JOIST,
BEAM, SEE PLAN BEAM, SEE PLAN SP, SEE PLAN
STRAP,SEE SEEPLAN PLAN STRAP,
4XFLAT FLATBLKG BLKGAS ASREQ REQFOR FORSTRAP STRAP 4X W/A34 A34EA EAEND, END,T&B T&B W/
H2.5 EA STUD, EA SIDE
ALIGN THE STUD ON THIS SIDE
DETAIL DETAIL 11 11
DETAIL
1'-0" 1"1"= =1'-0"
1" = 1'-0"
MANAGEMENT
FOR CONNECTION, HSS FRAME WHERE SEE 13 OCCURS, SAD S-566
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
STUD WALL WALL SP, SIDE VARIES, SEE PLAN
AGENCY
SP,SEE SEEPLAN PLAN SP,
DETAIL DETAIL 15 15
DETAIL DETAIL 19 19
1'-0" 1"1"= =1'-0"
1'-0" 1"1"= =1'-0"
Q1 Q1
GRID GRID STUDWALL, WALL,SEE SEEPLAN PLAN STUD
GRID
SP,WHERE WHERE SP, OCCURS, SEEPLAN PLAN OCCURS, SEE
SEEPLAN PLAN SEE 3'-0" MAX 3'-0" MAX
MAY OCCUR ON BOTH SIDES
EN EN 16D @ 3"OC TYP
2X12 16D PER STUD 2X8 W/W/ (3)(5) 16D PER STUD TYP 16D@@6"6"OC OC 16D TYP
4X BLKG TYP
BLKG 2x2xBLKG "SIMPSON"H3 H3AT AT "SIMPSON" EAOUTRIGGER OUTRIGGER EA
2'-0"MIN MIN 2'-0" 2'-8" MAX 2'-8" MAX EDGENAIL NAILPER PERPLAN PLAN EDGE
EN EN
SP,SEE SEEPLAN PLAN SP,
SP JOINT TO OCCUR AT RIM JOIST, NAIL SP2X4 BRACE @ 48" OC ABOVE PER FLOOR ABOVE & NAIL SP BELOW PER FLOOR BELOW. SEE PLAN FOR SP NAILING
SEE PLAN
A35 @ 16" OC
CONT 2X8. SPLICE AT DOUBLE STUD WHERE BRACE OCCURS
JOIST HGR,SEE SEEPLAN PLAN I-JOIST,
2X8 BEAM LEDGER W/ (3) 16D WHERE TO EA STUD SEE PLAN OCCURS, STOREFRONT, SAD WOOD STUD WALL, SEE PLAN
44
1'-0" 1"1"= =1'-0"
88
1'-0" 1"1"= =1'-0"
S-_061960_C224A S-_061960_C224A 140127.Q2 Q2 140127.
PARALLAM PARALLAM PERPLAN PLAN PER 2XJOISTS JOISTS@@24" 24"OC OCW/ W/ 2X "SIMPSON"A35 A35EA EAEND END "SIMPSON"
SAD
WOODSTUD STUDWALL, WALL,SEE SEEPLAN PLAN WOOD
TYPFLAT FLATI-JOIST I-JOISTPARALLEL PARALLELTO TOWALL WALLW/ W/ TYP OUTRIGGER OUTRIGGER
PARALLAMPSL, PSL,SEE SEEPLAN PLAN PARALLAM
(4) 10D EA JOIST ((2) EA SIDE)
TOW
I-JOIST,SEE SEE I-JOIST, PLAN PLAN
2X8 JOIST @ 24" OC
(4)1"1"DIA DIACARRIAGE CARRIAGE (4) BOLTSEA EASIDE SIDE BOLTS
(3) 16D NAILS
JOISTHANGER HANGER JOIST
"SIMPSON"H8 H8 "SIMPSON" EAJOIST JOISTEA SIDE EA
BACKER BLOCK, SEE "TYP IJOIST BACKER BLOCK" DETAIL
FORCONNECTION, CONNECTION, FOR SEE SEE 1313 S-566 S-566
" 1 1/2 " 1 1/2 1//44"" 1
SPEN ENTO TOBLKG BLKG SP
BACKER BACKER BLOCKTIGHT TIGHT BLOCK TOTOP TOPAT ATEA EA TO OUTRIGGER OUTRIGGER LOCATION LOCATION
ROOFSP SP ROOF
FASCIA 2x2xFASCIA
6"" 6
DBL2x2xTOP TOPPLATE PLATE DBL
EN EN
2XBLKG BLKGW/ W/ 2X "SIMPSON" A35 "SIMPSON" A35
2X8 STUDS @ 24" OC
FASCIA,SAD SAD FASCIA,
2x6 2x6 OUTRIGGER@@ OUTRIGGER 24"OC OC 24"
TYPLEDGER LEDGERPARALLEL PARALLELTO TOJOIST JOIST TYP
SEEPLAN PLAN SEE
SP, SEE PLAN
FC@@2'-0" 2'-0"OC OC FC
TOW TOW SEEPLAN PLAN SEE
A
SEEPLAN PLAN SEE
STRAP, SEE SHEAR WALL ELEVATION
2XBLKG BLKG 2X MSTA12 TO 4X4 BLOCK AT 24" OC, TYP
GRID GRID
WOOD STUD WALL, SEE PLAN
4X CONT
SP,WHERE WHERE SP, OCCURS, SEEPLAN PLAN OCCURS, SEE
SP,SEE SEEPLAN PLAN SP,
5/15/2019 4:35:51 PM
1 1/4"
2X8 STUDS @ 24" OC
7
1" = 1'-0" 1" = 1'-0"
A35 EA JOIST PARALLAM PER PLAN SHAPED 2X PL "SIMPSON" H8 EA JOIST
FOR CONNECTION, HSS FRAME WHERE SEE OCCURS, SAD 13 S-566 WALL SP, SIDE PLAN SP, SEE SEE PLAN STUD VARIES, WALL
" 1 1/2 " 1 1/2" 1//44" 1
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
DETAIL DETAIL
"SIMPSON" H8 SHAPED PL EA 2X JOIST EA SIDE
SPNOT NOTSHOWN SHOWN SP FORCLARITY CLARITY FOR
STRAP, SEE ELEV
33
PARALLAM PER PLAN 2x FASCIA, SAD 2X JOISTS @ 24" OC W/ "SIMPSON" A35 EA END
PARALLAM PER PLAN
"SIMPSON" H3 EA BLKG
2x FASCIA, SAD
2X BLKG W/ A35
2X JOISTS @ 24" OC 2x FASCIA, SADW/ "SIMPSON" A35 EA END
"SIMPSON" H3 EA BLKG
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
ROOF SP
AA PARALLAM PER PLAN
JOISTHANGER HANGEREA EASIDE SIDE JOIST
DATE 01/04/2019 5/17/2019
ROOF SP
TOFVARIES VARIES TOF SEEPLAN PLAN SEE
I-JOIST, SEE PLAN
WOOD STUD WALL, SEE PLAN
EN EN
A35 @ 32" OC, WHEN SP JOINT OCCURS AT RIM BOARD, WHEN SP DOES NOT OCCUR AT RIM BOARD USE FC PER SHEAR WALL SCHEDULE I-JOIST BACKER BLOCK AT BLKG LOCATION
SEE PLAN SEE PLAN
STRAP,SEE SEEEL EL STRAP,
SLOPEWHERE WHERE SLOPE OCCURS,SEE SEEPLAN PLAN OCCURS,
TOF SEE PLAN
EN I-JOIST BACKER BLOCK AT BLKG LOCATION
SEE PLAN SEE PLAN
DIRECTIONOF OFSLOPE SLOPE DIRECTION VARIES,SEE SEEEL EL VARIES,
(2) ROWS
SP, SEE PLAN
A35 @ 32" OC, WHEN SP JOINT OCCURS AT RIM BOARD, WHEN JOISTS, SP DOES NOT OCCUR SEE PLAN AT RIM BOARD USE FC PER SHEAR WALL SCHEDULE
SHEAR WALL, SEE PLAN
2'-0" 2'-0"
EN
EN
ISSUED
MARK
TOF SEE PLAN
SP JOINT TO OCCUR AT RIM JOIST, NAIL SP ABOVE PER FLOOR ABOVE & NAIL SP BELOW PER FLOOR BELOW. SP,NAILING SEE PLAN SEE PLAN FOR SP
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
S-_051200_T045A S-_051200_T045A 160107 160107
SCALE:NTS NTS SCALE:
1'-4"
WOOD STUD WALL, SEE PLAN SILL PLATE ATTACHMENT, SEE SCHEDULE
SP EN TO BLKG
EN
770 DIAMOND AVE RED BLUFF, CA 96080
PLANAT ATSPLICE SPLICE PLAN
1'-0" 1"1"= =1'-0"
2'-0"
A RU C T UR O F OF I CAL
PROJECT
GRID GRID 16D @ 6" OC WHEN SP JOINT OCCURS AT RIM BOARD, WHEN SP JOINT DOES NOT OCCUR AT RIM BOARD USE SILL PLATE ATTACHMENT PER SHEAR WALL SCHEDULE
T
E
No. S3737
05/15/2019
STUD WALL, SEE PLAN
DETAIL 10 DETAIL 10
1'-0" 1"1"= =1'-0"
PJP PJP
(t-1/8) (t-1/8)
HSSFASCIA FASCIASEE SEEPLAN PLAN HSS
BEAM,SEE SEEPLAN PLAN BEAM,
DETAIL DETAIL
EXPOSED EXPOSED
PLANAT ATCORNER CORNER PLAN
DO NOT HORIZ SPLICE PLYWOOD WITHIN TOP 36 INCHES
22
2x2xFASCIA, FASCIA, SAD SAD
A
2XSTUD STUDWALL, WALL,SEE SEEPLAN PLAN 2X WEBSTIFF, STIFF,SEE SEE WEB
HSSFASCIA, FASCIA, HSS SEE PLAN SEE PLAN
1/4 1/4
S
H8 TYP EACH JOIST
A35 EA JOIST 2X BLKG W/ A35
ST
JOIST,SEE SEE JOIST, PLAN PLAN
PJP PJP
EER GIN EN R
2XJOIST JOIST 2X
FESSIONA PRO L ED RRY J. VOLKE E
ROOF SP 2X BLKG W/ A35
MITER MITER CORNER CORNER
HANGER HANGER
SEAL
EN EN ROOF SP
I-JOIST,SEE SEEPLAN PLAN I-JOIST, HU316HANGER HANGER HU316
EN EN
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
"SIMPSON"A35 A35 "SIMPSON"
17/8" 7/8" 1CENTER IN TOP
STRAP AT SIM COND A SEE PLAN
1/2X91/2" 1/2"2.0E 2.0E 331/2X9 PARALLAM PSL PARALLAM PSL 2X10@@24" 24"OC OC 2X10
"SIMPSON"LSTA LSTA "SIMPSON" ATPLATE PLATESPLICE SPLICE AT
H8EA EASIDE SIDEOF OF H8 BEAM, EA JOIST BEAM, EA JOIST BEAM,PER PERPLAN PLAN BEAM,
3/8" 113/8"
8"8"
CJP CJP
4"4"
STUDWALL WALL STUD
1/2" 111/2"
1 1/4"
TITLE
PARALLAM PARALLAM PERPLAN PLAN PER
HSS OUT BOARD OF HSSFRAME FRAMEWHERE WHERE HSS WALL AT LOUVER ELEV OCCURS, SEE OCCURS, SEE FRAME. ALIGN WITH FINISHES
DETAIL DETAIL 12 12
DETAILS - ROOF FRAMING DETAILS
SP, SEE PLAN WALL SP WALL SP
1/2"CONNECTION CONNECTIONPL PL 1/2" (LOCATEON ONINSIDE INSIDEFACE) FACE) (LOCATE SHEET
NOTE: 1. SEE "TYP LSL RIM BOARD" DETAIL FOR ADDL INFORMATION
1'-0" 1"1"= =1'-0"
L N IA
SP SP
SEEPLAN PLAN SEE
07/03/2019
"SIMPSON"LSTA24 LSTA24 "SIMPSON" TYPAT ATEA EACORNER CORNER TYP
2'-0" 2'-0"
"SIMPSON" "SIMPSON" H2AEA EASIDE SIDE H2A
1'-0" 1"1"= =1'-0"
✔
"SIMPSON"A35 A35 "SIMPSON"
1" MIN 1" MIN AFTER DAP AFTER DAP
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
TYPICAL TOP PLATE AT TOP OF MECH WELL DAPTOP TOPPL PL DAP
2XJOISTS JOISTS 2X
11
ACS
✔
STUD WALL, SEE PLAN
2XBLKG BLKGW/ W/A35 A35 2X
DETAIL DETAIL
FLS
"SIMPSON"LUS410 LUS410 "SIMPSON" INVERTED INVERTED
OPH 1919 OPH S-566 S-566 EN EN
SS
✔
DATE:
1818 S-566 S-566
2XFASCIA FASCIA 2X
D
REVIEWED FOR
1/2X91/2" 1/2"2.0E 2.0E 331/2X9 PARALLAMPSL PSL PARALLAM
REGIST ER K
0 1/4" 1/2"
GRID GRID
INC:
R
2"
1
S-_061960_C206A Q2 140127. Q2
DETAIL DETAIL 16 16
S-566
DETAIL DETAIL 20 20
1'-0" 1"1"= =1'-0"
1'-0" 1"1"= =1'-0"
Q1 Q1
Q1 Q1
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
DATE:
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
GRID GRID
ACS
✔
✔
07/03/2019
FOR ADDL ADDLINFORMATION, INFORMATION, FOR SEE SEE 55 S-566 S-566
4XBLKG BLKG 4X
16D@ 4" 4" OC OC EA EA SIDE SIDE TO TO 16D@ BLOCK BLOCK
D
FLS
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
MSTA12 EVERY OTHER JOIST. STAGGER EACH STRAPS EACH SIDE OF LINE C. SLOT PLYWOOD AS REQUIRED FOR STRAP
CONSULTANT
1/2" LSL LSL LEDGER LEDGER W/ W/ 11 1/2" (6) 4 1/2" SDSCONTACT SCREWS (5)1/4"X 16D EA EA STUD CONTACT (5) 16D STUD TO EACH STUD CONTACT
ROOF JOISTS, JOISTS, ROOF SEE PLAN PLAN SEE
HU316HANGER HANGERW/ (20) #10x 1 1/2 HU316 HANGER HU316 CONNECTOR SCREWS TO LEDGER AND (12) 0.148X 1 1/2" NAILS TO JOIST, TYP
SP SP
22 S-566 S-566
2x FASCIA, FASCIA, 2x SEE PLAN PLAN SEE
GRID
L90AT AT CORNER CORNER L90 SP, SEE PLAN SP, NAIL SEE PLAN PER TYPE C WALL, TYP
SEAL
(10) 16D EA BLK WHERE 16D @4" OC LEDGER STRAP OCCURS TO BLCK
SHAPE BOT BOT PLATE PLATE SHAPE
MSTA12 EVERY OTHER JOIST
EN
A
4X BLKG
4X6 BLKG BLKG 4X6
T
66 S-566 S-566
1/2" CONT CONT LSL LSL RIM RIM 11 1/2" JOIST DO NOT JOIST SPLICE RIM JOIST WITHIN 6''-0" OF WALL CORNER
2X12 LEDGER W/ (4) 16D EA STUD CONTACT
C
ROOF JOISTS, JOISTS, ROOF SEE PLAN PLAN SEE
BEAM, SEE PLAN CLIENT
6
1"==1'-0" 1'-0" 1"
DETAIL
10
1"==1'-0" 1'-0" 1"
DETAIL
18
SCALE: NTS
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT SCHEMATIC PACKAGE
DBL I-JOIST, I-JOIST, SEE SEE PLAN PLAN DBL
PLAN VIEW VIEW PLAN
DETAIL
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
88 S-566 S-566
2
A RU C T UR O F OF I CAL
PROJECT
2x6 OUTRIGGER OUTRIGGER 2x6 @ 24" 24" OC OC @
TYP HANGER
E
No. S3737
05/15/2019
A35 EACH SIDE, STAGD
JOIST, SEE PLAN
T
S
ST
EDGE NAILING NAILING EDGE
GLB, SEE SEE PLAN PLAN GLB,
2X STUD WALL, SEE PLAN
1 1 1/2" 1/2"
SP, SEE SEE PLAN PLAN SP,
L N IA
1/4"X5" SDS 16D@ @4" 6"OC OC 16D @ 6" SCREW
FESSIONA PRO L ED RRY J. VOLKE E
SP, SEE PLAN
EER GIN EN R
CONT STRAP O/4X BLKG, SEE PLAN STUDS, SEE PLAN STUDS, SEE PLAN
REGIST ER K
ADDITIONAL STRAP WHERE OCCURS
R
2XSTUD STUD WALL, WALL, SEE SEE PLAN PLAN 2X
1/2"==1'-0" 1'-0" 1/2"
ISSUED
MARK
DATE 01/04/2019 5/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
2"
POST, SEE PLAN
VARIES, SEE PLAN
1 S-566
VARIES, SEE PLAN
3/16
1 1/2" TYP
JOIST, SEE PLAN ROOF SP, SEE PLAN
(4) 1/2" DIA BOLTS
JOIST, SEE PLAN
B 1 S-566
NO WELD AT RADIUS CORNERS
ROOF SP, SEE PLAN
7 1/4"
MANAGEMENT
A
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
GRID "SIMPSON" A35 EA SIDE 6X6 SILL PLATE W/ A35 T&B EACH END
AC44 EA SIDE, T&B OF POST
HD WHERE OCCURS, SEE PLAN
16D @ 3" OC TO GLB, EA SIDE 2x STUDS ES OF GLB
A
(10) 16D EA BLK WHERE STRAP OCCURS
TYP
ANGLE, SEE PLAN
MSTA12 EVERY OTHER JOIST
16D @ 3" OC TO GLB, EA SIDE
3/16 3/16"
2X STUD WALL, SEE PLAN
STUD ABOVE HEADER, TYP
2x STUD HSS TO HSS TYP
HD WHERE OCCURS, SEE PLAN
SP, SEE PLAN
BREAK BOT PL AT AC44
TOS SEE PLAN
STUD ABOVE HEADER, TYP
EN
ROOF PANEL, SAD
4X BLKG GAP, SAD
A
WHERE POST NOT NOTED ON PLAN, PROVIDE BUILT-UP POST OR STUDS 2X STUDS TO MATCH SEE PLAN BEAM WIDTH
GLB, SEE PLAN
GLB WHERE OCCURS, SEE PLAN
ELEVATION ELEVATION
4
DETAIL 1"==1'-0" 1'-0" 1"
8
L2X2X3/8 TYP ALL AROUND
DETAIL 1"==1'-0" 1'-0" 1"
AA
DETAIL DETAIL
WHERE POST NOT STUD WALL, SEE PLAN NOTED ON PLAN, PROVIDE BUILT-UP 2X STUDS TO MATCH BEAM WIDTH
TYP JOIST, SEE PLAN
PL1/4X2 1/2"SQ
2X12 LEDGER W/ (4) 16D EA STUD CONTACT
POST OR STUDS SEE PLAN
GLB, SEE PLAN
GLB WHERE OCCURS, SEE PLAN
5/15/2019 4:35:52 PM
OPENING, SAD
2x STUDS ES OF GLB
A
BREAK BOT PLAN PL AT POST, SEE AC44 AC44 EA SIDE, T&B OF POST
POST, SEE PLAN
POST WHERE OCCURS, SEE PLAN
CLR
CENTER SPLICE BTWN POSTS
AGENCY
5"
HDR, SEE CENTER SPLICE PLAN, POSTS CONT BTWN O/ (2) SPANS MIN
CS14 STRAP AT SPLICE, 2'-0" EA SIDE OF SPLICE, FILL ALL HOLES, EXTEND AS NEEDED FOR MISSED CONNECTORS AT UPLIFT TIES AT CS14 STRAP SPLICE, 2'-0" EA SIDE OF SPLICE, FILL ALL HOLES, EXTEND AS NEEDED FOR MISSED CONNECTORS AT UPLIFT TIES POST, SEE PLAN
3'-0"
C:\Users\Patty.Braun\Documents\_RevitLocalFiles\017294_BIM_S-MASTER_R18_CENTRAL_patty.braun.rvt
HDR, SEE PLAN, CONT O/ (2) SPANS MIN
OUTRIGGER, FOR ADDL INFO SEE
DECK, SAD TYP 3/16
GAP, SAD
FC EA SIDE WHERE HOLDOWN DOES NOT OCCUR
SLOPE
1/8
HSS, SEE PLAN
3/16
TYP HANGER 1/2
BEAM, SEE PLAN 4'-6" SAD FOR LOCATIONS
2-12
L TO HSS TYP
TITLE
DETAILS - ROOF FRAMING DETAILS
TYP
HSS8X2X1/4 TYP UNO SHEET
STUD WALL, SEE PLAN
12 12
DETAIL PLAN PARTIAL
20
SCALE: NTS 1" = 1'-0"
Q1
S-567
DETAIL 1" = 1'-0"
Q1
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
GENERAL NOTES 1"
1.
0 1/4" 1/2"
2.
E E LAN (E) FIR 09288 -1 A#02
(E) GAS METER ENCLOSURE
(E) ELECTRICAL YARD
D NE LA 8 E 8 FIR 1092 ) (E 02A#
E E LAN (E) FIR 09288 -1 A#02
(E) POND
APP. 02-117123
3.
SEE CIVIL AND LANDSCAPE DRAWINGS FOR ASPHALTIC AND PORTLAND CEMENT CONCRETE PAVING TYPES AND SECTIONS.
4.
SEE CIVIL DRAWINGS FOR LOCATION OF ALL UNDERGROUND UTILITIES.
5.
SEE PLUMBING SHEETS FOR ALL ROUTING OF ALL UNDERGROUND GAS LINES AND ROOF DRAINAGE CONNECTION POINTS TO STORM DRAINAGE SYSTEM, WATER, AND SEWER LINES SHOWN ON CIVIL DRAWINGS.
6.
SEE ELECTRICAL DRAWINGS FOR LOCATION AND TYPES OF VARIOUS POWER AND SIGNAL PULL BOXES AND LIGHT FIXTURES.
7.
EXPANSION JOINT SHALL BE LOCATED AT THE OUTSIDE CORNERS OF THE BUILDING.
8.
SEE CIVIL DRAWINGS FOR TYPICAL PAVEMENT STRIPING, SYMBOLS, ETC., UNO.
9.
SEE SHEET AS101 FOR ACCESSIBLE PATH OF TRAVEL.
10. SEE SHEET GL101 FOR EMERGENCY VEHICLE ACCESS & HYDRANTS.
INC:
REVIEWED FOR
SEE HORIZONTAL CONTROL PLAN, CIVIL DRAWINGS FOR DIMENSIONS NOT OTHERWISE SHOWN ON THIS DRAWING.
11. SEE LANDSCAPE DWGS FOR MISC SITE FEATURES NOT LIMITED TO BUT INCLUDING CONC SEAT WALLS, CONC PLANTERS, SHADE STRUCTURES, PAVING PATTERNS, AND TREE GRATES.
SS
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
12. SEE CIVIL DRAWINGS FOR TOPS OF SITE WALLS.
(E) AC PAVING, UNLOADING AREA
LEGEND
ER
TY
LIN
E
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
(E) F I R A#02 E LANE -1092 88
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SEE CIVIL AND ELECTRICAL DRAWINGS FOR MORE INFORMATION PERTAINING TO SCOPE OF PROJECT.
OP
(E) FH
PR
PROPERTY LINE ASSUMED IMAGINARY LINE
(E) BUILDING WITH NO SCOPE IN THIS PROJECT
SEAL
(E) FH
(E) BUILDING 1 A# 02-109288
M
(E) FH
(E) BUILDING 3 A# 02-109288
W
10
8
(E) PARKING A# 02-109288
SEE CIVIL FOR EXTENT OF NEW CONCRETE
6
(E) BUILDING 2 A# 02-109288
'-6" 69 / +
6 NO ING RK PA
6
S S TEHAMA CENTER STUDENT SERVICES BUILDING 4 U
NO ING RK PA NO ING RK PA
7
(E) FH A# 02-109288
7
J
16
(E) FH
"DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE STATEMENT: THE POT IDENTIFIED IN THESE CONSTRUCTION DOCUMENTS IS COMPLIANT WITH THE CURRENT APPLICATBLE CALIFORNIA BUILDING CODE ACCESSIBILITY PROVISIONS FOR PATH OF TRAVEL REQUIREMENTS FOR ALTERATIONS, ADDITIONS AND STRUCTURAL REPAIRS. AS PART OF THE DESIGN OF THIS PROJECT, THE POT WAS WAS EXAMINED AND ANY ELEMENTS, COMPONENTS OR PORTIONS OF THE POT THAT WERE DETERMINED TO BE NONCOMPLIANT 1) HAS BEEN IDENTIFIED AND 2) THE DETAILS, DRAWINGS AND SPECIFICATIONS INCORPORATED INTO THESE CONSTRUCTION DOCUMENTS. ANY NONCOMPLIANT ELEMENTS, COMPONENTS OR PORTIONS OF THE POT THAT WILL NOT BE CORRECTED BY THIS PROJECT BASED ON VALUATION THRESHOLD LIMITATIONS OR A FINDING OF UNREASONABLE HARDSHIP ARE SO INDICATED IN THESE CONSTRUCTION DOCUMENTS. DURING CONSTRUCTION, IF POT ITEMS WITHIN THE SCOPE OF THE PROJECT REPRESENTED AS CODE COMPLIANT ARE FOUND TO BE NONCONFORMING BEYOND RESONABLE CONSTRUCTION TOLERANCES, TEHY SHALL BE BOUGHT INTO COMPLIANCE WITH THE CBC AS A PART OF THIS PROJECT BY MEANS OF OF CONSTRUCTION CHANGE DOCUMENT."
(E) FH A# 02-109288
NO ING RK PA
7
IA
N
9
PATH OF TRAVEL :
NO ING RK PA
8
NE LA 8 E 28 FIR 109 ) (E 02A#
SEE LANDSCAPE DWGS
E AN L 8 IRE 28 ) F 09 (E 02-1 A#
(E) PASSENGER LOADING ZONE (A# 02-109288) 5 AS501 6 AS501
770 DIAMOND AVE RED BLUFF, CA 96080
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
(E) PATH OF TRAVEL PER A# 02-109285
7
FUTURE PARKING A# 02-109288
(E) 20' BARRIER-FREE FIRE TRUCK ACCESS ROAD PER A# 02-109285
CLIENT
6
8
TEHAMA CENTER STUDENT SERVICES
"
9
HI-LO DRINKING FOUNTAIN WITH BOTTLE FILLING STATION
EMERGENCY FIRE TRUCK ACCESS PATH OF TRAVEL, ROUTE WITH A MINIMUM OF 20' WIDE BY 15'-6" VERTICAL CLEARANCE WITH 50' INSIDE TURNING RADIUS AND AN ADDITIONAL 2' OF WIDTH PROVIDED TO ALLOW FOR CLEARANCE OF APPARATUS BUMPER OVERHANG, TYP. VEHICLE BARRIERS SUCH AS GATES PROVIDED WITH A KNOX BOX AT CAMPUS ENTRY POINTS.
-9 96'
7
PROJECT
DF
FIRELANE
+/-
9
B
*
A# 02-114844 (E) PV PANELS O/ PARKING
8
(E) TRASH ENCLOSURE A# 02-109288
M
6
6
EN . 08 - 3 1 - 1 O F OF CAL I
(E) FIRE HYDRANT
6
10
R E
R
W
10
C
T
A
U
C23603 SAFE DISPERSAL AREA: 5 SF/PERSON MIN 50'-0" FROM ANY BUILDING
ST
6
CT Y R RT
PROPOSED NEW BUILDING
11
10
D A RCH SE I E N A N McM TE H U T A
LI J ON C
11
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
(E) CONCRETE PAVING REVISED ACCESSIBLE PARKING AND WALK
CONCRETE PAVING PER CIVIL DRAWINGS SEE LANDSCAPE DWGS
LANDSCAPE PER LANDSCAPE DRAWINGS
MEN'S ACCESSIBLE RESTROOM
W
WOMEN'S ACCESSIBLE RESTROOM
U
R PE O PR
E LIN Y T
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 ?00.00.00? LIONAKIS 2017
UNISEX ACCESSIBLE STUDENT/STAFF RESTROOM
PARKING COUNT EXISTING PARKING SUMMARY
IR )F (E
E AN L E
STANDARD STANDARD NON ACCESSIBLE ACCESSIBLE ACCESSIBLE REQUIRED PROVIDED SPACES
OVERALL
203
7
5
VAN SPACES PROVIDED
VAN SPACES REQUIRED
TOTAL
1
2
211
ND U EN AV
(E) SITE ENTRANCE 19 SIGNAGE W/ TOW AWAY AS501 WARNING SIGNAGE
E
A
TITLE
ARCHITECTURAL SITE PLAN
NORTH
5/15/2019 3:48:42 PM
M
AGENCY
O AM DI
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
MANAGEMENT
1
ARCHITECTURAL SITE PLAN SCALE 1" = 40'-0"
SHEET
AS101
2"
1
2
3
4
5
0 1/4" 1/2"
1"
A# 02-109288 (E) CURB RAMP A# 02-109288 (E) TRUNCATED DOMES (TYP.)
REMOVE (E) STRIPING, ISA SYMBOL, AND CONCRETE WHEEL STOP, EXTENTS AS SHOWN BY SHADING.
A# 02-109288 (E) ACCESS AISLE (TYP.)
(E) STRIPING TO REMAIN
A# 02-109288 (E) 36" SQ. ISA SYMBOL, TYP.
A# 02-109288 (E) "NO PARKING", TYP.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
A# 02-109288 (E) ACCESSIBLE ROUTE (E) ACCESS AISLE 5'-0" TYP.
(E) ACCESSIBLE SPACE 9'-0" TYP.
INC:
REVIEWED FOR SS
(E) VAN ACCESS AISLE 9'-0"
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
MIN. CLR.
(E) 18'-0"
PARKING STALL DEPTH
(E) 19'-0"
48" MIN .
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
REMOVE
(E) 1'-0" MAX.
D (E) 5'-6"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
A# 02-109288 (E) CONCRETE WHEEL STOP, TYP.
REMOVE (E) SLOPING WALK, SIDEWALK, CURB, AND TRUNCATED DOMES, EXTENTS AS SHOWN BY SHADING
A# 02-109288 (E) 6" RAISED CURB (TYP.)
A# 02-114844 (E) OVERHEAD PHOTOVOLTAIC PANEL COLUMN
A# 02-109288 (E) ACCESSIBLE STALL (TYP.)
RELOCATE (E) ACCESSIBLE PARKING SIGN
A# 02-114844 (E) OVERHEAD PHOTOVOLTAIC PANEL ROOF EXTENTS A# 02-109288 (E) ACCESSIBLE PARKING SIGN, TYP.
A# 02-109288 (E) FLUSH TRANSITION AT TRUNCATED DOMES, TYP.
REMOVE (E) ACCESSIBLE PARKING SIGN
CONSULTANT
A# 02-109288 (E) TRAFFIC SIGNAGE
ACCESSIBLE PARKING PLAN-DEMO
5
SCALE 1/8" = 1'-0"
(N) WHITE PERIMETER AND WHITE DIAGONAL STRIPING (N) 36" SQ. ISA SYMBOL EXISTING PARKING
RELOCATED ACCESSIBLE PARKING SPACE
AS REQ'D
9'-0"
(N) 12" HIGH "NO PARKING"
9'-0"
SEAL
(N) VAN ACCESS AISLE
SPACE
D A RCH SE I E N A N McM TE H U T A
CT Y R RT
LI J ON C
(N) VAN PARKING SPACE
9'-0"
9'-0"
5'-0"
18'-0"
5'-0"
18'-0"
5'-0"
9'-0"
9'-0"
N
EN . 08 - 3 1 - 1 O F OF CAL I 9
A
14'-2"
R E
R
ST
T
IA
C23603
9'-3"
PROJECT
C
TEHAMA CENTER STUDENT SERVICES
10'-0" 1'-0"
770 DIAMOND AVE RED BLUFF, CA 96080
DN
(N)
(N) VAN ACCESSIBLE PARKING SIGNAGE
RELOCATED CONCRETE WHEEL STOP
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
(N) FLUSH TRANSITION AT TRUNCATED DOMES
(N) SIDEWALK SLOPE AND CURB RELOCATED ACCESSIBLE PARKING SIGNAGE
(N) CURB AND SIDEWALK
ACCESSIBLE PARKING PLAN-NEW
6
SCALE 1/8" = 1'-0" SEE PLAN
SLOPING CURB FLUSH TRANSITION
DETECTABLE WARNING
15
1/4" = 1'-0"
Q1
ACCESSIBLE PARKING PERPENDICULAR 1/8" = 1'-0"
Q1
(E) PAINT TOP & FACE OF CURB RED
NO PARKING FIRE LANE
1:12 MAX
1:12 MAX
B
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
C
D
E
AT SITE ENTRY FREE STANDING
ACCESSIBLE WALL MOUNTED
VAN ACCESSIBLE WALL MOUNTED
PAINT WITH TRAFFIC PAINT: SYMBOL: WHITE BACKGROUND: BLUE EQUAL TO FED SPEC 595A COLOR # 15090
AGENCY
1/2" = 1'-0" Q1
1" CROWN AT PAVING EXP JOINT, TYP AT PERIMETER
CONCRETE OR PAVING
SIGN
SIDES OF ISA PARALLEL TO STALL
12" DIA CONCRETE FOOTING
MEDIUM BROOM FINISH ON FACE OF SLOPED SURFACE
FACE OF CURB
TITLE
ARCHITECTURAL SITE DETAILS
(E) SITE PAVING 12 VIEW AT RAMP
LOWER EDGE OF ISA ALIGNED WITH END OF PARKING STALL
1 MAX
5/15/2019 3:48:45 PM
7 AS501 TRUNCATED DOMES PER
4
(E) FIRE LANE MARKING
8
1" = 1'-0" Q1
CONCRETE WHEEL STOP
12
3/4" = 1'-0" Q1
3"
SECTION
017294 ?00.00.00? LIONAKIS 2017
ACCESSIBLE PARKING SIGNAGE
1 1/2" DIA GALV STD PIPE
GRADE BREAKS ARE NOT PERMITTED ON THE SURFACE OF RAMP RUNS OR TURNING SPACES / LANDINGS. TRANSITIONS TO ADJACENT SURFACES MUST BE LEVEL
PLAN
VAN ACCESSIBL E MINIMUM FINE $250
CL
DN
SLOPE OF TOP LANDING AND TURNING SPACE AT BOTTOM TO BE 2% MAX IN ALL DIRECTIONS. CROSS SLOPE OF RAMP RUN TO BE 2% MAX
2'-0"
TO FACE OF CURB OR FACE OF STUD
A
2'-0"
WHERE PARALLEL RAMP LEADS TO A STREET OR CROSSING, ENSURE THAT COUNTER SLOPES OF ADJOINING GUTTERS AND ROADS WITHIN 24" ARE 5% (1:20) MAX AND DO NOT ACCUMULATE WATER
ELEVATIO N
A
DN
PARKING ONLY
MANAGEMENT
3'-0"
3'-0"
(E) 4" HIGH PAINTED WHITE LETTERS SPACE MESSAGE @ 30' OC MAX
48" MIN
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
PARKING ONLY
MINIMUM FINE $250
SEE PLAN FOR SPECIFIC SIGN TYPE, FOR SPECIFIC SIGNAGE INFORMATION, SEE DETAIL
2'-0"
AC PAVING
VAN ACCESSIBL E MINIMUM FINE $250
UNAUTHORIZED VEHICLES PARKED IN DESIGNATED ACCESSIBLE SPACES NOT DISPLAYING DISTINGUISHING PLACARDS OR SPECIAL LICENSE PLATES ISSUED FOR PERSONS WITH DISABILITIES WILL BE TOWED AWAY AT OWNER'S EXPENSE. TOWED VEHICLES MAY BE RECLAIMED AT (ADDRESS) OR BY TELEPHONING (TELEPHONE NUMBER) C.V.C. 22507.8
Q1
TOP LANDING 48" MIN
6"
48" MIN WIDTH OF SIDEWALK
4'-0"
MINIMUM FINE $250
19
#6 STEEL REINF BAR 16" MIN LONG PARKING STRIPE OR CURB, WHERE OCCURS
PARKING ONLY
1'-10" MIN
36" x 36" INTERNATIONAL SYMBOL OF ACCESSIBILITY. CL OF NO ISA 6" MAX FROM CL OF STALL, SIDES OF ISA PARKING PARALLEL TO STALL AND LOWER SIDE 9'-0" MIN 9'-0" MIN 9'-0" MIN ALIGNED WITH END OF PARKING SPACE VAN ACCESSIBLE REGULAR LENGTH. TYP FOR ALL PARKING STALL ACCESSIBLE PARKING PARKING STALL 16 NOTE: AS501 • 2% MAX SLOPE IN ANY DIRECTION FOR ACCESSIBLE STALLS AND ACCESS AISLES. • VAN ACCESSIBLE STALL MAY BE 12'-0" IN WIDTH IF ADJACENT ACCESS AISLE ON PASSENGER SIDE IS 5'-0" IN WIDTH.
2'-6"
WHITE TEXT
PARKING ONLY
ACCESSIBLE VAN ACCESSIBLE FREE STANDING FREE STANDING
ACCESSIBLE FLARED CURB RAMP
11
3" = 1'-0"
COUNTERSLOPE 1:20 MAX FOR 24" OUT FROM THE CURB RAMP
4" WHITE LINE
DATE 01/04/2019 05/17/2019
CONFIRM INFORMATION PRIOR TO FABRICATION AND INSTALLATION
7" MIN
4" BLUE LINE BORDER
60" MIN AT PLANTERS
GRADE BREAKS ARE NOT PERMITTED ON THE SURFACE OF RAMP RUNS OR TURNING SPACES / LANDINGS. TRANSITIONS TO ADJACENT SURFACES MUST BE LEVEL
AX
80" MIN AT ACCESSIBLE ROUTE
APPLY BAND OF TRUNCATED DOMES FULL WIDTH OF RAMP, SEE DETAIL. 2" MAX GAP ALLOWED BETWEEN EDGE OF TRUNCATED DOMES AND RAMP
M
UNAUTHORIZED VEHICLES PARKED IN DESIGNATED ACCESSIBLE SPACES NOT DISPLAYING DISTINGUISHING PLACARDS OR SPECIAL LICENSE PLATES ISSUED FOR PERSONS WITH DISABILITIES WILL BE TOWED AWAY AT OWNER'S EXPENSE. TOWED VEHICLES MAY BE RECLAIMED AT (ADDRESS) OR BY TELEPHONING (TELEPHONE NUMBER) C.V.C. 22507.8.
2'-9" MIN
0.90" NOTES: 1. THE MATERIAL USED TO PROVIDE VISUAL CONTRAST SHALL BE AN INTEGRAL PART OF THE SURFACE. 2. DETECTABLE WARNING SURFACES SHALL BE YELLOW AND APPROXIMATE FS 33538 OF FEDERAL STANDARD 595C. 3. DETECTABLE WARNING SURFACES SHALL PROVIDE A 70% MIN VISUAL CONTRAST WITH ADJACENT WALKING SURFACES. IF VISUAL CONTRAST IS NOT AVAILABLE SEE 11B-705.1.1.3.2 4. WHERE INSTALLED IN A RADIAL PATTERN, DOMES SHALL HAVE A CENTER TO CENTER SPACING OF 1.6-2.4 INCHES. 5. DETECTABLE WARNING SURFACES MUST DIFFER FROM ADJOINING SURFACES IN RESILIENCY OR SOUND-ON-CANE CONTACT.
FRONT EDGE OF SIDEWALK
1:20 MAX
FACE OF CURB
"
MARK
TO BE DISPLAYED:
60" MIN
0.45-0.47"
-0 3'
10" MIN
18'-0" MIN
6" CLR
1:10 MAX AT CURB
6"
4'-0" CONCRETE WHEELSTOP, TYP SEE DETAIL 8 AS501
ISSUED
60" MIN AT PLANTERS
1:12 MAX 3'-0"
0.65" MIN
1:10 MAX AT CURB
6"
2'-0" MIN UNOBSTRUCTED AREA
MIN
19 AS501
1'-6"
ACCESSIBLE PARKING SIGN, FOR VAN SIGN, SEE DETAIL B
ACCESSIBLE PARKING SIGN, FOR STANDARD STALL SIGN, SEE DETAIL A 19 AS501
80" MIN CLR
BACK EDGE OF SIDEWALK
2% MAX
2.3" -2.4"
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
CONCRETE SIDEWALK
SECTION VIEW
B
7
4'-0" CLR
0.20" HT
IN DIRECTION OF TRAVEL
3'-0" MIN
MIN
EXTENT OF STALL, SEE SITE PLAN FOR ADDITIONAL INFORMATION
12" MIN
4'-0"
NOT TO EXCEED 2% SLOPE IN ANY DIRECTION
NOTES: 1. SIGNS SHALL HAVE A MINIMUM AREA OF 70 SQ INCHES 2. SIGNAGE TO BE INSTALLED CENTERED AT INTERIOR END OF EACH PARKING SPACE 3. GALV/ THEFT PROOF BRACKETS, STL BOLTS, NUTS & WASHERS THROUGH SIGN AND POST 4. SIGN PANEL OF 0.08" MIN ALUM SHEET, ENAMEL PAINTED AFTER SMOOTHING WITH WHITE LETTERS, NUMBERS AND BORDER STRIPE 5. CHARACTERS TO BE WHITE ON A BLUE BACKGROUND 6. ALL SIGNS TO HAVE 1/2" RADIUS AT THE CORNERS 7. LETTERS SHALL BE 1" MINIMUM IN HEIGHT 1'-5" MIN 1'-0"
CENTERLINE OF ISA & STALL, 6" MAX OFFSET ALLOWED
PARALLEL CURB RAMP
16
1/8" = 1'-0" Q1
ACCESSIBLE PARKING SYMBOL
20
1" = 1'-0" Q1
TYP SIGN POLE & BASE FOR EXT MOUNTED SIGNS
SHEET
AS501
1/2" = 1'-0" Q1
2"
1
2
3
4
5
GENERAL NOTES 1"
1.
SS
3.
LOCATE DOOR JAMBS 4" AWAY FROM ADJACENT WALL UNLESS OTHERWISE DIMENSIONED.
DATE:
4.
KEY NOTED WALL TYPES SHALL EXTEND FROM CORNER TO CORNER, FULL LENGTH OF WALL UNLESS OTHERWISE NOTED.
5.
FOR SYMBOLS LEGEND SEE SHEET G-001.
6.
SEE SHEET A-131 FOR FINISH FLOOR PLAN AND A-641 FOR FINISH SCHEDULE.
7.
SEE SHEET A-561 FOR CASEWORK DETAILS.
8.
SEE SHEET A-151 FOR SIGNAGE PLANS.
9.
SEE SHEET A-221 AND A-222 FOR INTERIOR ELEVATIONS.
✔
FLS
ACS
✔
✔
07/03/2019
10. SEE SHEET A-411 FOR RESTROOM PLANS AND ELEVATIONS.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
11. FOR BLOCKING REQUIREMENTS SEE TYPICAL FRAMING DETAILS FOR REQUIRED CONSTRUCTION.
D
12. UNLESS OTHERWISE NOTED ALL INTERIOR FLOOR DRAINS ARE SET 3/4" BELOW TOP OF FLOOR SLAB.
CONSULTANT
13. SEE SHEET A-621 FOR DOOR AND WINDOW TYPES. 14. FOR ASSISTIVE LISTENING SYSTEM, INCLUDING NUMBER OF REQUIRED DEVICES, SEE ELEC TELECOM SHEETS. RECEIVERS MUST BE READILY AVAILABLE
FLOOR PLAN LEGEND
A-311
3
4
5
6
121'-1 1/4" 20'-6 5/8"
19'-8 3/8"
7
1 A-221
20'-3 5/8"
20'-3 5/8"
19'-8 3/8"
20'-6 5/8"
5'-6"
4'-6"
150B
CANOPY
8"
3'-6 1/8"
8" 1'-4"
1'-4"
1'-4"
4'-8 7/8"
DS
4'-7 5/8" 7'-9 1/4"
8"
8"
FIRE EXTINGUISHER IN CABINET PER SPECIFICATIONS
107
106
105
0W6A
FACULTY OFFICE
FACULTY OFFICE
117
116
115
114
113
112
111
110
109
5'-3 5/8"
10'-0"
5'-0"
12'-8"
E
E
3'-0"
3'-0"
8"
11 5/8"
A-311
5'-0"
8"
8'-10"
8'-10"
10'-0"
12'-8"
FACULTY HALLWAY 150
5'-3 5/8"
DS
8'-10"
4'-8 3/8"
E
E
3'-0"
3'-0"
11 5/8"
10'-0"
12'-8"
8'-10"
8'-10" 5'-0"
E
E
3'-0"
3'-0"
8" 8"
4 3/8"
9'-1 7/8"
10'-5 3/4"
770 DIAMOND AVE RED BLUFF, CA 96080
10'-0"
150A
5'-6 5/8"
3'-0"
76'-2 5/8"
10'-6 3/4" 9'-6 3/4"
3'-4 1/4" 6'-2 1/2"
MARK 1 A-313
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
B.6
1 A-312
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
A
E 12'-8"
ISSUED
C
B
0W6A 5'-0"
TEHAMA CENTER STUDENT SERVICES
C.4
109
FACULTY OFFICE
110
FACULTY OFFICE
8'-10"
17'-2"
0W6A
FACULTY OFFICE
8'-10"
18 A-522
A-314
18'-2"
108
0W6A
EN . 08 - 3 1 - 1 O F OF CAL I
7'-5 1/2"
118
0W6A
5'-10 7/8"
11 3/4"
FACULTY OFFICE
FACULTY OFFICE
9'-10 3/8"
17 A-522
102 106
STUDENT SERVICES
0W6A
R E
PROJECT
17'-1"
100A
0W6A
T
PLAN NORTH & TRUE NORTH INDICATOR
E
101B
0W6A
0W12A 0W8A
FACULTY OFFICE
1
1
0W6A
6'-3"
FACULTY OFFICE
3'-0" 4 3/8"
11'-10 3/4"
STUDENT SERVICES
0W6A
PH 2'-4 7/8"
100B 9'-9 1/4"
FACULTY OFFICE
E
DS
HALLWAY
9'-11 1/8"
8'-0"
STUDENT SERVICES
0W6A
PLAN NORTH
8'-5 1/4"
10'-0 5/8"
0W8A
4'-2 3/4"
111
124B
4'-2"
0W6A
104
RESTROOM
0W6A
116
0W6A
122
117
F
B
119
0W6A
0W6A
1'-4"
123
VET OFFICE
122B
124
13'-5 3/4"
A-312
122A
123B
CONFERENCE
VET CENTER
CUSTODIAL
STORAGE
103
3'-6 1/8"
121 120
1
0W6A
19'-8 3/8"
0W6A
C23603
DOOR OPENING IDENTIFIER
1
DS
112
IDF
1 A-411
8'-0 1/4" 5 1/2"3'-8"
115
11'-6"
0W10A 0W8A
3'-2 3/4"
120
0W6A
2 A-411
ADMIN OFFICE
107
0W6A 5'-10 7/8"
WORK CENTER
119
ALIGN
HALLWAY
4'-8 1/4"
1'-10"
0W6A
5'-6"
0W8A 4'-8"
121
F
124A
123A
0W8A
19'-8 3/8"
D A RCH SE I E N A N McM TE H U T A
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
STUDENT SERVICES 0W8A
7'-1 1/4"
131
0W6A
108
129
0W8A
113
127
SIGNAGE INDICATOR
SEAL
CLIENT
100
5'-6 1/4"
125
F
LOBBY
0W6A
11
0W6A
101
ALIGN 3'-4 1/4"
COUNSELOR
151
CLASSROOM/LOBBY OVERFLOW
114
COUNSELOR
3'-4 1/4" 5'-10 7/8"
COUNSELOR
0W6A
0W6A
101A
131
127
125 151
102
0W6A
0W6A
COUNSELOR DS
ADMIN OFFICE
104
0W6A
HALLWAY
FURNITURE, FIXTURE & EQUIPMENT INDICATOR
D
105
9'-5 5/8"
118
100D
10'-2 3/4"
3'-6 5/8"
D
103
10'-2 3/4"
3/4" 88 3/4"
0W12A 0W8A
0W8A 0W10A
6'-1 1/2"
7'-3"
129
3'-0 7/8"
0W6A
A-313
1'-4"
11'-3"
132
PH
0W10A 0W8A
FIRE RISER
8"
4 TYP. A-512
CANOPY 5/8" 2'-32'-3 5/8"
132
COUNSELOR
130 130
COUNSELOR
128 126
COUNSELOR
126
10'-11 1/2"
0W6A
CAMPUS SAFETY
2'-3 5/8"
ALIGN
0W6A
4'-8 7/8"
D
128
10'-11 1/2"
0W6A
PH
1
8"
8"
8"
8" 8"
8"
8" 7'-9 1/4"
5'-0 1/2" 4'-11 1/2"
D
DS
B
C 5'-6"
1'-1 1/4"
A-314
ENTRY TOWER
BB
234
CT Y R RT
1
8"
KEYNOTE INDICATOR
A
DS
8"
22
ST
1 A-222
1'-4"
WINDOW OR LOUVER IDENTIFIER
101A
A
C
10
IA
A-311
N
2
PARTITION TYPE INDICATOR
9
2
1
J
LI J ON C
1
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
INC:
REVIEWED FOR
SEE ARCH WALL SECTIONS AND STRUCTURAL PLANS FOR EXTERIOR WALL CONSTRUCTION. WALL CONSTRUCTION SHALL COMPLY W/ CBC TABLE 601.
1S4A
DS AGENCY 1'-2 5/8"
2 A-311
KEY PLAN
FLOOR PLAN SCALE 1/8" = 1'-0"
PLAN NORTH
A
TITLE
FLOOR PLAN
PLAN NORTH
5/15/2019 3:48:02 PM
APP. 02-117123
R
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
2.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
ARCHITECTURAL DIMENSIONS ARE TO FACE OF STUDS OR CENTERLINE OF COLUMN GRIDS UNLESS OTHERWISE NOTED.
SHEET
A-111
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
GENERAL NOTES
0 1/4" 1/2"
1"
1.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SHEET MEMBRANE WATERPROOFING TYP AT ALL BUILDING ROOFS. LOCATIONS SHOWN NOT LIMITED TO EDGE OF ROOF, RIDGES, RAKES, EAVES, VALLEYS, & ANY ROOF PENETRATIONS.
2.
PROVIDE ROOFING FELT PAPER TYP FOR FULL ROOF COVERAGE AT ALL SHINGLE ROOFING.
3.
ATTIC VENTILATION PROVIDED AT 1/300 PER 1203.2 EXCEPTION.
4.
ATTIC VENTILATION CALCULATIONS SHOWN AS FOLLOWS: A. LOWER ROOF: A-112 B. UPPER ROOF: A-141
APP. 02-117123
REVIEWED FOR SS
✔
DATE:
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
INC:
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
LEGEND SINGLE PLY ROOF ASSEMBLY PER SPECIFICATIONS UL CLASS A
SEAL D A RCH SE I E N A N McM TE H U T A
2
3
4
5
6
7
C23603
121'-1 1/4" 20'-3 5/8"
15 18 A-542 A-542
18 A-542
4'-0"
TYP
19'-8 3/8"
18 A-512
20'-6 5/8"
GUTTER, TYP
14 A-542
4'-0"
REV
2'-0"2'-0"
G
2'-8 3/4"2'-8 3/4"
G
G
3'-0"
G
16'-0"
OPEN TO BELOW
A-313
TYP
76'-2 5/8"
11 A-541
10'-6 3/4"
OPEN TO BELOW
1'-2 3/4"
OPEN TO BELOW
15 A-514
ISSUED
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
C 1
OPEN TO BELOW
16'-0"
1'-2 3/4"
5 A-514
MARK
9'-6 3/4"
1
OPEN TO BELOW
16'-0"
LOCATION OF VENTED SOFFIT BOARD, 12" PANEL WIDTH PROVIDING 5 SQ.IN. NET FREE AREA PER LINEAL FOOT
770 DIAMOND AVE RED BLUFF, CA 96080
G
1'-2 3/4"
1'-2 3/4"
OPEN TO BELOW
13 A-511
A-314
C.4 TOP OF GYP. BD.SHELF
LOCATION OF EAVE SOFFIT TRIM, FCP-PCS375V300 BY FRY REGLET OR APPROVED EQUIVALENT, 5.00 SQ.IN. NET FREE ARE PER LINEAL FOOT.
1
ROOF ACCESS VIA LOUVERED DOOR. REFER TO ELEVATION
G
TEHAMA CENTER STUDENT SERVICES
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT 17'-1"
A-314
EN . 08 - 3 1 - 1 O F OF CAL I
CLIENT
H 3" / 12"
1
D
1/2" / 12"
3" / 12"
H
E
7'-9 1/4"
1/4" / 12"
R E
PROJECT
ROOF DRAIN AND OVERFLOW DRAIN, CONNECT TO CIVIL BELOW GRADE, SEE CIVIL DRAWINGS AND DETAIL SHEET
F
4'-7 5/8"
3'-0"
13 A-514 1/4" / 12"
T
SLOPE TO DRAIN
9 A-512
5 A-514
J 3'-0"
C
20'-3 5/8"
A
19'-8 3/8"
SHINGLE ROOFING PER SPECIFICATIONS UL CLASS A
ST
20'-6 5/8"
CT Y R RT
1
LI J ON C
CRICKET PER DETAILS AND SPECIFICATIONS
IA
A-311
N
A-311
9
2
R
1
OPEN TO BELOW
A-313
B.6 1'-3 1/4"
G
1'-8 3/4"
G
2'-8 3/4"
G
2'-8 3/4"
G
G
1'-8"
4"
G 19 A-541
B
3 A-514
SIM 1
18'-2"
1
A-312 MANAGEMENT
3" / 12"
3" / 12"
A-312
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
4 A-514
8'-5 1/4"
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
B
AGENCY
A
TYP EXTERIOR WALL OF BUILDING BELOW
5 A-514 1
2
A-311
A-311
KEY PLAN PLAN NORTH
1
A
CLERESTORY / LOWER ROOF PLAN SCALE 1/8" = 1'-0"
TITLE
CLERESTORY / LOWER ROOF PLAN
SHEET
5/15/2019 3:48:03 PM
017294 ?00.00.00? LIONAKIS 2017
A-112
2"
1
2
3
4
5
GENERAL NOTES 1"
1.
0 1/4" 1/2"
2. 3.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
ALL CEILING GRID LAYOUTS FROM THE CENTER OF THE ROOM, FULL TILE FROM ROOM CORNER, UNLESS NOTED OTHERWISE.
APP. 02-117123
REVIEWED FOR
FOR FINISHES, SEE FINISH SCHEDULE SHEET A-641. SS
FOR SMOKE DETECTOR LOCATIONS, SEE ELECTRICAL DWGS.
✔
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
DATE:
CEILING PLAN LEGEND
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D 8'-0"
INC:
CEILING HEIGHT ELEVATION
CONSULTANT
CL2 - 2' x 2' SUSPENDED ACOUSTICAL CEILING, SEE
1 A-551
GYPSUM BOARD CEILING, SEE FINISH LEGEND AND SCHEDULE ON SHEET A-641.
FIBER CEMENT TEXTURED SOFFIT
4
5
6
7
90 FT 450 SQ.IN.
SEAL
CEILING ACCESS PANEL: AT GYP. BD. CLG.
19'-8 3/8"
20'-6 5/8"
UNDERSIDE OF HIGH ROOF
TYP.
COUNSELOR
126
128
130
132
101
10'-0"
10'-0"
10'-0"
10'-0"
11'-0"
CLASSROOM/LOBBY OVERFLOW
COUNSELOR COUNSELOR
13 13 A-511 A-511 SIM. SIM.
3" / 12"
C
13 A-511
CAMPUS SAFETY
LF OF LOWER VENT: PROVIDED VENT AREA:
40 FT 200 SQ.IN.
LF OF UPPER VENT: PROVIDED UPPER VENT AREA: TOTAL PROVIDED VENT AREA:
40 FT 200 SQ.IN. 400 SQ.IN.
F
4'-7 5/8"
40 FT 200 SQ.IN. 400 SQ.IN.
20'-3 5/8"
10'-0"
AT FIBER CEMENT CLG.
LOCATION OF EAVE SOFFIT TRIM, FCP-PCS375V300 BY FRY REGLET OR APPROVED EQUIVALENT, 5.00 SQ.IN. NET FREE ARE PER LINEAL FOOT.
13 A-511
LOCATION OF VENTED SOFFIT BOARD, 12" PANEL WIDTH PROVIDING 5 SQ.IN. NET FREE AREA PER LINEAL FOOT
5 A-514
COUNSELOR 129
LOBBY
ADMIN OFFICE
TEHAMA CENTER STUDENT SERVICES
CLIENT
100
102
12'-0"
11'-0"
1 A-314
10'-0"
10'-0"
100D
11'-0"
127
13 A-551
IDF
UNDERSIDE OF HIGH ROOF
HALLWAY
BOTTOM OF SOFFIT
9'-0"
BOTTOM OF SOFFIT
12'-0"
100B
103 10'-0"
11'-0"
11'-0"
STORAGE
CUSTODIAL
RESTROOM
120
119
118
10'-0"
10'-0"
10'-0"
B
UNDERSIDE OF HIGH ROOF
105
B.6
STUDENT SERVICES
121 10'-0"
FACULTY OFFICE
11'-0"
11'-0"
11'-0"
11'-0"
C
1 A-313
11'-0"
11'-0"
STUDENT SERVICES
106
1
STUDENT SERVICES
1
A-312
107
A-312
STUDENT SERVICES
TYP. METAL CANOPY CENTER ABOVE WINDOW OPENING
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
108
17 A-514
B
150
8'-5 1/4"
3" / 12"
3" / 12"
FACULTY HALLWAY
AGENCY
CANOPY A SOFFIT AREA: REQ'D. VENT AREA (1/150):
749 SF 5.00 SF 720 SQ.IN.
LF OF LOWER VENT: PROVIDED VENT AREA:
121 FT 605 SQ.IN.
LF OF UPPER VENT: PROVIDED UPPER VENT AREA: TOTAL PROVIDED VENT AREA:
40 FT 200 SQ.IN. 800 SQ.IN.
CONFERENCE
VET CENTER
VET OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
124
123
122
117
116
115
114
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
FACULTY FACULTY OFFICE OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
113
112
111
110
109
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
1
2
A-311
A-311
KEY PLAN PLAN NORTH
1
A
CEILING PLAN SCALE 1/8" = 1'-0"
TITLE
CEILING PLAN
SHEET
5/15/2019 5:09:07 PM
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
9'-6 3/4"
10'-0"
WORK CENTER
13 A-551
12'-0"
DATE 01/04/2019 05/17/2019
18'-2"
10'-0"
100C
BOTTOM OF SOFFIT
3" / 12"
HALLWAY
EQ.
151
EQ.
FIRE RISER
13 A-551
3" / 12" 3" / 12"
10'-0"
104
76'-2 5/8"
125
3" / 12"
3" / 12"
COUNSELOR
MARK 10'-6 3/4"
11'-0"
12'-0"
ISSUED
C.4
ADMIN OFFICE 3" / 12"
10'-0"
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
PROJECT
HALLWAY
10'-0"
A-313
EN . 08 - 3 1 - 1 O F OF CAL I
17'-1"
10'-0"
1
15 A-514
R E
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
131
COUNSELOR
T
770 DIAMOND AVE RED BLUFF, CA 96080
COUNSELOR A-314
C23603
E
D
1
16 A-551
7'-9 1/4"
LF OF UPPER VENT: PROVIDED UPPER VENT AREA: TOTAL PROVIDED VENT AREA:
20'-3 5/8"
3" / 12"
40 FT 200 SQ.IN.
19'-8 3/8"
462 SF 1.54 SF 222 SQ.IN.
A
LF OF LOWER VENT: PROVIDED VENT AREA:
20'-6 5/8"
SOFFIT AREA: REQ'D. VENT AREA (1/300):
ST
462 SF 1.54 SF 222 SQ.IN.
D A RCH SE I E N A N McM TE H U T A
CT Y R RT
121'-1 1/4"
SOFFIT AREA: REQ'D. VENT AREA (1/300):
15 A-551
IA
3
LF OF SOFFIT VENT: PROVIDED VENT AREA:
N
A-311
9
A-311
FIBER CEMENT SMOOTH SOFFIT
R
2
2
457 SF 3.05 SF 439 SQ.IN.
LI J ON C
1
1
SOFFIT AREA: REQ'D. VENT AREA (1/150):
A-121
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
0 1/4" 1/2"
1"
GENERAL NOTES 1.
REFER TO FINISH LEGEND/FINISH SCHEDULE ON SHEET I-641 FOR FINISH CLARIFICATION.
2.
CHANGE IN INTERIOR FLOOR MATERIAL SHALL OCCUR AT CENTERLINE OF DOOR UNO.
3.
REFER TO SHEET I-511 FOR ALL FLOOR FINISH TRANSITIONS.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
INC:
REVIEWED FOR SS
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
FLOOR FINISH LEGEND C1 - CARPET TILE: SHAW, FOCUS 59455, "MEDITATE 54761"
C2 - CARPET TILE: SHAW, BON JOUR II 57032, "TOBACCO 31150"
SF1 - LINOLEUM: FORBO, MARMOLEUM CONCRETE, 3728/372835, "KAOLIN"
D SP5 - SEALED CONCRETE
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
RT1 - VPI, STATMATE STATIC CONTROL TILE, 16, "CLOUD"
1
2
A-311
A-311
SEAL
5
6
7
C23603 ST
A
T
R E
IA
4
N
3
EN . 08 - 3 1 - 1 O F OF CAL I 9
2
R
1
CT Y R RT
LI J ON C
D A RCH SE I E N A N McM TE H U T A
PROJECT
C
TEHAMA CENTER STUDENT SERVICES
F
E ENTRY TOWER
770 DIAMOND AVE RED BLUFF, CA 96080
100E
6'-0"
D
1
CAMPUS SAFETY
COUNSELOR
COUNSELOR
COUNSELOR
A-314
126
128
130
132
7'-0"
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ADMIN OFFICE
1
102
A-314
CLASSROOM/LOBBY OVERFLOW
HALLWAY 100D
101
LOBBY
COUNSELOR
COUNSELOR
COUNSELOR
COUNSELOR
125
127
129
131
ISSUED
C.4
100
MARK
STUDENT SERVICES
ADMIN OFFICE
103
104
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
C
1
FIRE RISER
A-313
HALLWAY
151
100C
6'-0"
HALLWAY WORK CENTER
1 A-313
100B
100A
IDF
B.6 STORAGE
CUSTODIAL
RESTROOM
STUDENT SERVICES
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
120
119
118
108
107
106
105
121
B
CONFERENCE
VET CENTER
124
123
1 A-312
VET OFFICE
1 A-312
4'-0"
4'-0"
4'-0"
122
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
114
113
112
111
110
109
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
B FACULTY HALLWAY 4'-0"
AGENCY 6'-0"
150
A
1
2
A-311
A-311
PLAN NORTH
1
A
FINISH FLOOR PLAN SCALE 1/8" = 1'-0"
TITLE
FINISH FLOOR PLAN
SHEET
5/15/2019 3:48:05 PM
017294 ?00.00.00? LIONAKIS 2017
A-131
2"
1
2
3
4
5
GENERAL NOTES
0 1/4" 1/2"
1"
1.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SHEET MEMBRANE WATERPROOFING TYP AT ALL BUILDING ROOFS. LOCATIONS SHOWN NOT LIMITED TO EDGE OF ROOF, RIDGES, RAKES, EAVES, VALLEYS, & ANY ROOF PENETRATIONS.
2.
PROVIDE ROOFING FELT PAPER TYP FOR FULL ROOF COVERAGE AT ALL SHINGLE ROOFING.
3.
ATTIC VENTILATION PROVIDED AT 1/300 PER 1203.2 EXCEPTION.
4.
ATTIC VENTILATION CALCULATIONS SHOWN AS FOLLOWS: A. LOWER ROOF: A-112 B. UPPER ROOF: A-141
APP. 02-117123
REVIEWED FOR SS
✔
DATE:
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
INC:
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
LEGEND 5
A-311
6
SINGLE PLY ROOF ASSEMBLY PER SPECIFICATIONS UL CLASS A
7
LF OF VENTED SOFFIT: PROVIDED VENT AREA:
150 FT 750 SQ.IN.
D A RCH SE I E N A N McM TE H U T A
CRICKET PER DETAILS AND SPECIFICATIONS
C23603 SHINGLE ROOFING PER SPECIFICATIONS UL CLASS A
T
A
7 A-514
EAVE SOFFIT AREA: REQ'D. VENT AREA (1/150):
125 SF 0.83 SF 120 SQ.IN.
SLOPE TO DRAIN
LF OF VENTED SOFFIT: PROVIDED VENT AREA:
40 FT 200 F SQ.IN.
ROOF DRAIN AND OVERFLOW DRAIN, CONNECT TO CIVIL BELOW GRADE, SEE CIVIL DRAWINGS AND DETAIL SHEET
3" / 12"
3" / 12"
C
E
REFER TO CLERESTORY / LOWER ROOF PLAN
CT Y R RT
431 SF 2.87 SF 413 SQ.IN.
ST
TOWER EAVE SOFFIT AREA: REQ'D. VENT AREA (1/150):
SEAL
REFER TO CLERESTORY / LOWER ROOF PLAN
D
R E
IA
A-211 A-511
4
N
A-311
EN . 08 - 3 1 - 1 O F OF CAL I 9
3
R
2
LI J ON C
1
2
31
1
PROJECT
TEHAMA CENTER STUDENT SERVICES
LOCATION OF EAVE SOFFIT TRIM, FCP-PCS375V300 BY FRY REGLET OR APPROVED EQUIVALENT, 5.00 SQ.IN. NET FREE ARE PER LINEAL FOOT.
13 A-511
LOCATION OF VENTED SOFFIT BOARD, 12" PANEL WIDTH PROVIDING 5 SQ.IN. NET FREE AREA PER LINEAL FOOT
5 A-514
770 DIAMOND AVE RED BLUFF, CA 96080 15 A-514 CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT 1
1
LF OF VENTED SOFFIT: PROVIDED VENT AREA:
40 FT 200 SQ.IN.
REFER TO CLERESTORY / LOWER ROOF PLAN
MARK 19 A-512 1/2" / 12"
4
1/2" / 12"
1/2" / 12"
1/2" / 12"
1/2" / 12"
1/2" / 12"
A-211
TYP EXTERIOR WALL OF CLERESTORY BELOW
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
C 1 A-313
3" / 12"
3" / 12"
A-313
13 A-512 3
A-211
1
ISSUED
C.4 3" / 12"
125 SF 0.83 SF 120 SQ.IN.
3" / 12"
EAVE SOFFIT AREA: REQ'D. VENT AREA (1/150):
A-314
6 A-514
3" / 12"
3" / 12"
A-314
B.6
B 1
1
A-312
A-312 MANAGEMENT
REFER TO CLERESTORY / LOWER ROOF PLAN
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
VENTS TYP, SEE MECH
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
B
AGENCY
A
TYP EXTERIOR WALL OF BUILDING BELOW
1
2
2
A-311
A-211
A-311
EAVE SOFFIT AREA: REQ'D. VENT AREA (1/150): LF OF VENTED SOFFIT: PROVIDED VENT AREA:
381 SF 2.54 SF 366 SQ.IN. 121 FT 605 SQ.IN.
KEY PLAN PLAN NORTH
1
A
UPPER ROOF PLAN SCALE 1/8" = 1'-0"
TITLE
ROOF PLAN
5/15/2019 3:48:07 PM
SHEET
A-141
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
GENERAL NOTES
0 1/4" 1/2"
1"
1.
2.
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
3.
APP. 02-117123
INC:
REVIEWED FOR SS
PROVIDE ASSISTIVE LISTENING SYSTEM IN ROOMS INDICATED BY SIGN TYPE 8. SEE DETAIL 14 / G-513
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
ALL SIGNAGE MUST BE FIELD INSPECTED, VERIFY AFTER INSTALLATION PER 11B-703.1.1.2.
SIGNAGE LEGEND D
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
ROOM NAMES AND NUMBERS SHOWN ON FLOOR PLANS ARE FOR CONSTRUCTION DOCUMENT REFERENCE ONLY. CONTRACTOR TO PROVIDE COMPLETE CHART OF ACTUAL BUILDING ROOM USE SIGNAGE DESIGNATION. ARCHITECT TO FORWARD TO THE DISTRICT FOR REVIEW AND APPROVAL.
#
1
FUNCTIONAL ROOM SIGNAGE, SEE DETAIL 7 / G-513
2
TACTILE EXIT SIGNAGE "EXIT", SEE DETAIL 15 / G-513
3
TACTILE EXIT SIGNAGE "EXIT ROUTE", SEE DETAIL 15 / G-513
4
ACCESSIBLE RESTROOM DOOR AND WALL SIGNAGE, SEE DETAIL 19 / G-513 AND 20 / G-513
5
OCCUPANCY LOAD SIGNAGE, SEE DETAIL 9 / G-513
6
ELECTRICAL PANEL SIGNAGE LOCATION
7
FIRE SPRINKLER RISER INSIDE SIGNAGE, SEE DETAIL 13 / G-513
8
ASSISTIVE LISTENING DEVICE SIGN, SEE DETAIL 14 / G-513
*
MOUNT SIGN ON GLASS, WHERE POSSIBLE MOUNT SIGNS BACK TO BACK AND MAKE EQUAL SIZE. WHERE NO SECOND SIGN IS PRESENT, PROVIDE A BLANK SIGN TO COVER O/ ADHESIVE
**
PROVIDE 90 DEGREE LIMITER ON PULL SIDE RIGHT HAND DOOR AT PAIRS OF DOORS, TYP.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
SEAL
CT Y R RT
LI J ON C
D A RCH SE I E N A N McM TE H U T A
C
N
EN . 08 - 3 1 - 1 O F OF CAL I 9
A
ASSISTIVE LISTENING SYSTEM (ALS) REQUIRED PER CBC 11B-219 OCCUPANTS = 42 42 X 4% = 1.68 (2 MIN) TOTAL # TO BE PROVIDED: 2 SEE GENERAL NOTES FOR ADDITIONAL INFORMATION
R E
R
ST
T
IA
C23603
PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
1
1
*
*
CLIENT 2
2
*
CAMPUS SAFETY
COUNSELOR
COUNSELOR
COUNSELOR
126
128
130
132
*
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ADMIN OFFICE 102 2
5 1
* 2
1
1
1
1
1
1
1
3
8
CLASSROOM/LOBBY OVERFLOW
1
*
1
101
LOBBY
ISSUED
100
COUNSELOR
COUNSELOR
COUNSELOR
COUNSELOR
125
127
129
131
STUDENT SERVICES
ADMIN OFFICE
103
104
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
3
*
FIRE RISER
1
7
1
6
8
151
*
1
2
*
1
*
1
1
*
1
*
1
1
* 1
1
4
IDF
STORAGE
CUSTODIAL
RESTROOM
STUDENT SERVICES
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
120
119
118
108
107
106
105
121
B
CONFERENCE
VET CENTER
124
123 1
1
VET OFFICE 122
2
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
1
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
114
113
112
111
110
109
1
1
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
*
* 1
1
*
FACULTY OFFICE
2
2
*
FACULTY OFFICE
*
1
*
1
* 1
2
*
*
1
*
*
FACULTY HALLWAY 150
1
*
*
1
*
1
*
1
*
*
AGENCY 2
1
*
*
ASSISTIVE LISTENING SYSTEM (ALS) REQUIRED PER CBC 11B-219 OCCUPANTS = 27 27 X 4% = 1.08 (2 MIN) TOTAL # TO BE PROVIDED: 2 SEE GENERAL NOTES FOR ADDITIONAL INFORMATION
PLAN NORTH
1
A
SIGNAGE PLAN SCALE 1/8" = 1'-0"
TITLE
SIGNAGE PLAN
5/15/2019 3:48:09 PM
SHEET
A-151
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
0 1/4" 1/2"
1"
GENERAL NOTES
3 3 BUILDING SIGNAGE BUILDING SIGNAGE A-511 A-511
11 A-311 A-311
RF-1
19 19 SCREED TYPTYP SCREED A-511 A-511
RF-1
18 A-511
CP-1
HORIZ REVEAL TYP
SEE DOOR AND FRAME SCHEDULE SHEET A-621 FOR EXTERIOR DOOR FINISHES.
2.
SEE WINDOW SCHEDULE SHEET A-621 FOR WINDOW FRAME FINISHES.
3.
ALL EXTERIOR PMF DOORS AND FRAMES TO BE PAINTED UNO.
SS
4.
ADD DOUBLE BUILDING PAPER AND TAPE AT ALL EXTERIOR WINDOWS, DOORS, AND OTHER OPENINGS, SEE SHEETS A-541 & A-542.
DATE:
5.
ALL ALUMINUM DOOR AND WINDOW FRAMES TO BE CLEAR ANODIZED
6.
ALL EXTERIOR EXPOSED STEEL TO BE GALVANIZED FINSH, INCLUDING BUT NOT LIMITED TO HANDRAILS, GUARDRAILS, AND STAIRS U.O.N.
7.
UNLESS NOTED OTHERWISE, PROVIDE VERTICAL CONTROL JOINTS IN CEMENT PLASTER SYSTEM AT WINDOW AND DOOR OPENING CORNERS, TYP
8.
FOR TYPICAL FIBER CEMENT SIDING PANEL INSTALLATION, SEE SHEET A-511
9.
FOR EXTERIOR WALL PENETRATIONS, SEE SHEET A-512.
APP. 02-117123
INC:
REVIEWED FOR ✔
FLS
ACS
✔
✔
07/03/2019
RF-1 10. ALL EXPOSED PIPE PENETRATIONS THROUGH ROOF, PAINT COLOR P8 1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
11. CEMENT COLOR ABOVE IS INTEGRAL BASED ON OMEGA AKROFLEX FINE. CLERESTORY SILL 119'-0"
D
12. ROOFING COLOR BASED ON MANUFACTURER'S COLORS.
RF-2
EXTERIOR FINISH SCHEDULE MAT #
LEVEL 1 100'-0"
CP-1 CP-1 2 A-311
FCP-1 CP-1
1 A-511
11 A-311 A-311
AS-1
4 A-512
17 A-511
FCS-1
9 A-511
NORTH EXTERIOR ELEVATION SCALE 1/8" = 1'-0"
FIBER CEMENT SIDING PANEL BASIS OF DESIGN: PER SPECIFICATIONS MATCH EXISTING CAMPUS FOR COLOR AND FINISH METAL LOUVERS BASIS OF DESIGN: PER SPECIFICATIONS MATCH EXISTING CAMPUS FOR COLOR AND FINISH
AS-1
ALUMINUM STOREFRONT BASIS OF DESIGN: PER SPECIFICATIONS MATCH EXISTING CAMPUS FOR COLOR AND FINISH
GL-1
WINDOW GLAZING BASIS OF DESIGN: PER SPECIFICATIONS MATCH EXISTING CAMPUS FOR COLOR
GL-2
WINDOW GLAZING BASIS OF DESIGN: PER SPECIFICATIONS MATCH EXISTING CAMPUS FOR COLOR SINGLE PLY ROOFING BASIS OF DESIGN: PER SPECIFICATIONS
C23603
SHINGLE ROOFING BASIS OF DESIGN: PER SPECIFICATIONS MATCH EXISTING CAMPUS FOR COLOR AND PATTERN
A-311
CP-1
R E
EXTERIOR DOWNSPOUT BASIS OF DESIGN: PAINT TO MATCH EXISTING CAMPUS FOR COLOR AND FINISH
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
RF-1
1
T
A
DS-1
D A RCH SE I E N A N McM TE H U T A
ST
RF-2
SEAL
CT Y R RT
RF-1
C
CEMENT PLASTER BASIS OF DESIGN: PER SPECIFICATIONS MATCH EXISTING CAMPUS FOR COLOR AND FINISH
ML-1
GL-2 GL-1
1
CP-1
IA
TYP TYP
FCP-1
DESCRIPTION
N
CP-1
9
FCP-1
R
TOP PLATE 112'-0"
CP-1
CONSULTANT
LI J ON C
RF-2
3'-0" 3'-0"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
2 A-311
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1.
TEHAMA CENTER STUDENT SERVICES
2 A-311
AS-1
RF-1
GL-1
770 DIAMOND AVE RED BLUFF, CA 96080
CP-1
CLERESTORY SILL 119'-0"
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
RF-2
TOP PLATE 112'-0"
CP-1 ISSUED
MARK LEVEL 1 100'-0"
CP-1 2 A-511
2
FCP-1
1
2
A-311
A-311
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
SOUTH EXTERIOR ELEVATION SCALE 1/8" = 1'-0"
B
MANAGEMENT
1 A-314
1 A-314
1 A-313
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
1 A-312
14 A-512
AGENCY
5 A-511
RF-1
RF-1
RF-1
RF-1
14 A-512
CP-1
EXT LIGHT FIXTURE, SEE ELEC
METAL CANOPY CENTER ABOVE WINDOW OPENING
DS-1 FCP-1 FCP-1
DS-1
FCP-1
2 A-511
11 A-511
1 A-312
1 A-313
EAST EXTERIOR ELEVATION SCALE 1/8" = 1'-0"
SCREED REVEAL
5'-6"
1 A-211
TOP PLATE 112'-0"
FCP-1 CP-1
DS-1
LEVEL 1 100'-0"
A
KEY PLAN RF-2
2'-10"
2 A-511
DS-1 DS-1
DS-1
17 A-514
7'-2"
CP-1
SCREED REVEAL
TOP PLATE 112'-0"
FCP-1
SCREED TYP TYP HORIZ REVEAL
CLERESTORY SILL 119'-0"
RF-2
RF-2
19 18 A-511
CP-1
SCREED REVEAL
13 A-511
CLERESTORY SILL 119'-0"
5'-6"
CP-1
RF-2
3 5/15/2019 3:48:13 PM
1 A-313
10'-0"
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
1 A-312
LEVEL 1 100'-0"
GL-1 GL-1
GL-1
GL-2
GL-2
AS-1 AS-1
AS-1
1 A-314
EXT LIGHT FIXTURE, SEE ELEC
1 A-314
4
WEST EXTERIOR ELEVATION SCALE 1/8" = 1'-0"
1 A-313
DS-1
GL-1
GL-1
CP-1
AS-1
AS-1
4 A-211
3 A-211
TITLE
ELEVATIONS EXTERIOR
1 A-312
2 A-211
PLAN NORTH
SHEET
A-211
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
GENERAL NOTES 1
3
4
5
1"
A-311
0 1/4" 1/2"
---
3"
3'-4" 2'-5 1/4" 3'-6"
2.
CONTRACTOR TO PROVIDE BACKING AS REQUIRED, SEE 18 / A-521 FOR TYPICAL BACKING DETAILS
3.
SEE FINISH SCHEDULE AND LEGEND FOR CASEWORK TYPES
4.
SEE SHEET A-561 FOR TYPICAL CASEWORK ANCHORAGE
5.
ALL CASEWORK SHELVING SHALL BE ADJUSTABLE, UNO
6.
PROVIDE LOCKS ON ALL CASEWORK
7.
WHERE WI NUMBERS ARE INDICATED CONTRACTOR SHALL REFER TO CUSTOM FABRICATED CASEWORK DESCRIBED IN DRAWINGS AND SPECIFICATIONS
8.
FOR TYPICAL MARKERBOARD MOUNTING HEIGHT SEE 14 / A-522
9.
FOR ACCESSIBLE MOUNTING HEIGHTS, SEE SHEET G-511
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
EXIT
E
INC:
REVIEWED FOR SS
✔
DATE:
PLASTER
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
ENTRY TOWER
D
REFER TO FINISH LEGEND AND SCHEDULE ON SHEET A-641 FOR ADDITIONAL INFORMATION
SIDING
F
2'-5 1/4"
4'-4 5/8"
2'-5 1/4" 2'-6" 4'-6 4'-91/2" 7/8" 4'-4
2'-1 5/8"
2'-6" 2'-5 1/4"
2'-5 1/4"
4'-4 5/8"
4'-67/8" 1/2" 4'-9 4'-4
3'-4" 2'-5 1/4" 3'-6"
3"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
4 A-512
3'-6" 3'-4" 2'-5 1/4"
3'-4" 2'-5 3'-6" 1/4"
1.
NORTH
CONSULTANT
D
1
1 100N
A-314
100W
A-221
A-314 100E
LIGHT FIXTURE, SEE ELEC TYP 100S
OPEN TO BEYOND
OPEN TO BEYOND
LOBBY
SEAL
100
C.4
CT Y R RT
LI J ON C
D A RCH SE I E N A N McM TE H U T A
N
9
EN . 08 - 3 1 - 1 O F OF CAL I
2'-6"
A
R E
R
ST
T
IA
C23603 OPEN TO BEYOND
100.
PROJECT 3'-10 1/2"
C A-221 11'-9 1/4"
3'-0"
3'-0"
11'-9 1/4"
TEHAMA CENTER STUDENT SERVICES
SOUTH
1
770 DIAMOND AVE RED BLUFF, CA 96080
2'-9 1/4"
2'-9 1/4"
C 1
100A
A-313
A-313
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
A-221
WORK CENTER 100A
B.6 1 A-311
MARK
ENLARGED PLAN - LOBBY
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
SCALE 1/4" = 1'-0"
2'-10"
1
ISSUED
PLAN NORTH
B
2'-0"
3'-6"
2'-0"
4'-0"
3'-7 3/4"
4'-0"
2'-0"
3'-6"
2'-0"
WI 101
OPEN
WI 101
WI 102
OPEN
WI 102
WI 101
OPEN
WI 101
16 G-511
16 A-561
16 G-511
16 G-511
EAST MANAGEMENT
LOWER CABINETS ONLY
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
100. LOBBY DESK CASEWORK ELEVATION
AGENCY
LIGHT FIXTURE, SEE ELEC TYP
OPEN TO BEYOND
OPEN TO BEYOND
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
WI 301 WI 301 WI 301 WI 301 WI 301
A
1'-8"
OPEN TO BEYOND
OPEN TO BEYOND
TITLE
ELEVATIONS - INTERIOR BASE PER SCHEDULE
2'-0"
3'-0"
4'-0"
4'-0"
2'-6 1/4"
4'-0"
4'-0"
3'-0"
2'-0"
WI 101
OPEN
WI 102
WI 102
OPEN
WI 102
WI 102
OPEN
WI 101
16 G-511
5/15/2019 3:48:15 PM
2'-0"
2'-6"
WI 301 WI 301 WI 301 WI 301 WI 301
2'-0"
2'-10"
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
SCALE 1/4" = 1'-0"
017294 ?00.00.00? LIONAKIS 2017
100A WORKSTATION ELEVATION SCALE 1/4" = 1'-0"
16 G-511
16 A-561
WEST
16 G-511
100
LOBBY ELEVATIONS SCALE 1/4" = 1'-0"
SHEET
A-221
2"
1
2
3
4
5
0 1/4" 1/2"
1"
GENERAL NOTES
2
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
5
6
A-311
1.
REFER TO FINISH LEGEND AND SCHEDULE ON SHEET A-641 FOR ADDITIONAL INFORMATION
2.
CONTRACTOR TO PROVIDE BACKING AS REQUIRED, SEE 18 / A-521 FOR TYPICAL BACKING DETAILS
3.
SEE FINISH SCHEDULE AND LEGEND FOR CASEWORK TYPES
4.
SEE SHEET A-561 FOR TYPICAL CASEWORK ANCHORAGE
5.
ALL CASEWORK SHELVING SHALL BE ADJUSTABLE, UNO
6.
PROVIDE LOCKS ON ALL CASEWORK
7.
WHERE WI NUMBERS ARE INDICATED CONTRACTOR SHALL REFER TO CUSTOM FABRICATED CASEWORK DESCRIBED IN DRAWINGS AND SPECIFICATIONS
8.
FOR TYPICAL MARKERBOARD MOUNTING HEIGHT SEE 14 / A-522
9.
FOR ACCESSIBLE MOUNTING HEIGHTS, SEE SHEET G-511
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
INC:
REVIEWED FOR SS
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
D 1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
BASE PER SCHEDULE
D
NORTH
SOUTH
101 N
CONSULTANT
1
1 101W
A-314
A-222
101E
A-314
101S
CLASSROOM/LOBBY OVERFLOW LIGHT FIXTURE, SEE ELEC, TYP
101
SOFFIT
C.4
SEAL
CT Y R RT
LI J ON C
D A RCH SE I E N A N McM TE H U T A
N
R E
EN . 08 - 3 1 - 1 O F OF CAL I 9
A
T
R
ST
C
IA
C23603
PROJECT
C
2
TEHAMA CENTER STUDENT SERVICES
A-311
EAST PLAN NORTH
1
ENLARGED PLAN - CLASSROOM
770 DIAMOND AVE RED BLUFF, CA 96080
CLASSROOM/LOBBY OVERFLOW - ELEVATIONS
101
SCALE 1/4" = 1'-0"
WEST
SCALE 1/4" = 1'-0" CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK 1
1
A-312
A-312
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
SOFFIT 13 A-522
TYP TACKABLE WALL PANEL
9'-6"
9'-6"
B
TACKABLE WALL PANEL
MANAGEMENT
EQ
EAST
SOUTH
EQ
EQ
BASE PER SCHEDULE
WEST
NORTH
EAST
SOUTH
WEST
EQ
EQ
BASE PER SCHEDULE
109
TYP FACULTY OFFICE 1
1
A-312
A-312
108
SCALE 1/4" = 1'-0"
STUDENT SERVICES (ROOMS 103, 106, & 107 SIM) SCALE 1/4" = 1'-0"
TACKABLE WALL PANEL
9'-6"
TACKABLE WALL PANEL
A
TITLE EQ
NORTH
125
EAST
SOUTH
WEST
COUNSELOR OFFICE (ROOMS 127, 129, & 131 SIM) SCALE 1/4" = 1'-0"
EQ
EQ
3'-4"
BASE PER SCHEDULE
NORTH
132
EAST
EQ
EQ
BASE PER SCHEDULE
SOUTH
ELEVATIONS - INTERIOR
WEST
COUNSELOR OFFICE (ROOMS 126, 128, &130 SIM) SCALE 1/4" = 1'-0" SHEET
5/15/2019 3:48:19 PM
017294 ?00.00.00? LIONAKIS 2017
AGENCY
9'-6"
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
NORTH
EQ
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
A-222
2"
1
2
3
4
5
GENERAL NOTES 1"
1.
0 1/4" 1/2"
1
1
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
A-314
F
E
A-313
D
C.4
A-312
C
8 A-514
2.
1
3.
B.6
B
10 A-511
SS
UNO FIRE SPRINKLER MAIN AND BRANCH LINES ARE TO BE CONCEALED; RUN UNDER BOTTOM CHORD OF TJI AND ABOVE SUSPENDED CEILING (RUN IN PLENUM) AND/OR WALL CAVITY BETWEEN FRAMING, UON. SPRINKLER MAIN AND BRANCH LINES SHALL NOT BE EXPOSED IN CLASSROOMS, ADMINISTRATION AREAS, OFFICES, RESTROOMS, OR OCCUPIED SPACES UNO. PROVIDE DRAWINGS AS REQUIRED PER SPECS (FIRE PROTECTION SECTION), TYP FOR ALL BUILDINGS.
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
A
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
14 A-514
SIM
INC:
REVIEWED FOR
6 A-514 3 A-514
APP. 02-117123
FOR CEILING HEIGHTS, SEE CEILING PLANS.
8 A-514
D
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
BUILDING SECTIONS INTENDED TO INDICATE MAJOR BUILDING SYSTEMS. SEE FLOOR PLAN AND INTERIOR ELEVATIONS FOR INDIVIDUAL ROOM ELEMENTS AND ACCESSORIES.
CONSULTANT
CLERESTORY TOP PLATE 123'-0"
MECH UNIT 3 A-514
MECH UNIT
SIM CLERESTORY SILL 119'-0"
13 10 A-514 A-511 13 A-551
8 A-521
13 A-511
TOP PLATE 112'-0"
LIGHT FIXTURES, SEE ELEC
SEAL
116
150
LI J ON C
C23603
6'-0"
A
T
11 A-521
16 A-541
TEHAMA CENTER STUDENT SERVICES
16 A-512
SIM
16 A-521
TYP
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
LEVEL 1 100'-0"
C
R E
IA
FACULTY HALLWAY
ST
FACULTY OFFICE
N
120
9
STORAGE
100A
R
WORK CENTER
100
D A RCH SE I E N A N McM TE H U T A
45°
LOBBY
9 TYPA-512 TYP
CT Y R RT
9 A-512
770 DIAMOND AVE RED BLUFF, CA 96080
10 A-521
1
1
1
A-314
A-313
A-312 CLIENT
1
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
SECTION THROUGH LOBBY SCALE 1/4" = 1'-0"
ISSUED
MARK
F
E
1
1
1
A-314
A-313
A-312
D
C.4
C
B.6
B
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
A
B
14 A-514
6 A-514
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 ?00.00.00? LIONAKIS 2017
AGENCY
3 SIM A-514 8 A-521
15 A-514
5 A-514
KEY PLAN
13 A-551 TOP PLATE 112'-0"
1 A-311
LIGHT FIXTURES, SEE ELEC
159
101
HALLWAY 100B
STUDENT SERVICES 108
A
FACULTY OFFICE
FACULTY HALLWAY
112
150
6'-0"
CANOPY
CLASSROOM/LOBBY OVERFLOW
2 A-311
9 A-512
TITLE
SECTIONS - BUILDING
LEVEL 1 100'-0"
16 A-512
SIM
5/15/2019 3:48:20 PM
CLERESTORY SILL 119'-0"
45°
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
CLERESTORY TOP PLATE 123'-0"
2
SECTION THROUGH CLASSROOM SCALE 1/4" = 1'-0"
16 A-521
TYP
10 A-521
1
1
1
A-314
A-313
A-312
1 A-311
2 A-311 PLAN NORTH
SHEET
A-311
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
DATE:
1
2
1
2
A-311
A-311
3
4
5
6
7
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
13 A-512 CLERESTORY TOP PLATE 123'-0"
8 A-521
CLERESTORY SILL 119'-0" 2 A-514
TYP
SEAL D A RCH SE I E N A N McM TE H U T A
CT Y R RT
EXTERIOR LIGHTING PER ELECTRICAL
C
CONFERENCE 124 12 A-511
VET CENTER
VET OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
123
122
117
116
115
114
113
112
111
110
109
109
IA
R E
N
A
T
EN . 08 - 3 1 - 1 O F OF CAL I 9
ST
19 A-514
C23603
R
TOP PLATE 112'-0"
LI J ON C
2 A-514
PROJECT
12 A-511
TEHAMA CENTER STUDENT SERVICES
12 A-511 LEVEL 1 100'-0"
770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
12 A-521
1
AT SHEAR WALL
10 A-521
1
2
A-311
A-311
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
TYP
EAST WEST SECTION
ISSUED
SCALE 1/4" = 1'-0"
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
GENERAL NOTES
B
1.
BUILDING SECTIONS INTENDED TO INDICATE MAJOR BUILDING SYSTEMS. SEE FLOOR PLAN AND INTERIOR ELEVATIONS FOR INDIVIDUAL ROOM ELEMENTS AND ACCESSORIES.
2.
FOR CEILING HEIGHTS, SEE CEILING PLANS.
3.
UNO FIRE SPRINKLER MAIN AND BRANCH LINES ARE TO BE CONCEALED; RUN UNDER BOTTOM CHORD OF TJI AND ABOVE SUSPENDED CEILING (RUN IN PLENUM) AND/OR WALL CAVITY BETWEEN FRAMING, UON. SPRINKLER MAIN AND BRANCH LINES SHALL NOT BE EXPOSED IN CLASSROOMS, ADMINISTRATION AREAS, OFFICES, RESTROOMS, OR OCCUPIED SPACES UNO. PROVIDE DRAWINGS AS REQUIRED PER SPECS (FIRE PROTECTION SECTION), TYP FOR ALL BUILDINGS. MANAGEMENT
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
KEY PLAN
A
TITLE
1 A-312
1 A-312
PLAN NORTH
5/15/2019 3:48:21 PM
017294 ?00.00.00? LIONAKIS 2017
SECTIONS - BUILDING
SHEET
A-312
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
DATE:
11
2
A-311 A-311
A-311
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
1
2
3
4
5
8 A-514
6
CONSULTANT
7
3 A-514
10 A-521
2 A-521
CLERESTORY TOP PLATE 123'-0"
CLERESTORY SILL 119'-0" 13 A-512 13
6X10 HEADER PER 11/S-561
SEAL
A-512
2X6 SHELF FRAMING @ 16" O.C. W/ 5/8" GYB. BD.
A
T
R E
16'-0" SHELF
6X10 HEADER PER 11/S-561
FIRE RISER
CONFERENCE
HALLWAY
124
100C
9'-0" SOFFIT
C
WORK CENTER 100A
151
2
A-311 A-311
A-311
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT 13 A-511
2X4 SOFFIT FRAMING @ 16" O.C. W/ 5/8" GYP. BD.
13 A-511
TEHAMA CENTER STUDENT SERVICES
HALLWAY
770 DIAMOND AVE RED BLUFF, CA 96080
100B
LEVEL 1 100'-0"
11
N
ST
TOP PLATE 112'-0"
IA
C23603
2X6 WALL FRAMING @ 16" O.C. W/ 5/8" GYB. BD. FULLY LINE WITH ACOUSTIC INSULATION
9
13 A-551
R
13 A-551
LI J ON C
18 A-514
CT Y R RT
MECHANICAL / ELECTRICAL / PLUMBING OCCURS PER PLANS
D A RCH SE I E N A N McM TE H U T A
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
1
SECTION THROUGH HALLWAY
DATE 05/17/2019
DESCRIPTION DSA BACKCHECK
SCALE 1/4" = 1'-0"
GENERAL NOTES
B
1.
BUILDING SECTIONS INTENDED TO INDICATE MAJOR BUILDING SYSTEMS. SEE FLOOR PLAN AND INTERIOR ELEVATIONS FOR INDIVIDUAL ROOM ELEMENTS AND ACCESSORIES.
2.
FOR CEILING HEIGHTS, SEE CEILING PLANS.
3.
UNO FIRE SPRINKLER MAIN AND BRANCH LINES ARE TO BE CONCEALED; RUN UNDER BOTTOM CHORD OF TJI AND ABOVE SUSPENDED CEILING (RUN IN PLENUM) AND/OR WALL CAVITY BETWEEN FRAMING, UON. SPRINKLER MAIN AND BRANCH LINES SHALL NOT BE EXPOSED IN CLASSROOMS, ADMINISTRATION AREAS, OFFICES, RESTROOMS, OR OCCUPIED SPACES UNO. PROVIDE DRAWINGS AS REQUIRED PER SPECS (FIRE PROTECTION SECTION), TYP FOR ALL BUILDINGS. MANAGEMENT
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
KEY PLAN
A
1 A-313
1 A-313
TITLE
SECTIONS - BUILDING
PLAN NORTH
5/15/2019 3:48:22 PM
017294 ?00.00.00? LIONAKIS 2017
SHEET
A-313
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR ✔
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
DATE:
11
2
A-311 A-311
A-311
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
1
2
3
4
5
6
7 A-514
SIM
17 A-542
CLERESTORY TOP PLATE 123'-0"
20 A-542
MECH UNIT
SHEAR WALL
10 A-521
13 A-514
MECH UNIT
CLERESTORY SILL 119'-0"
3 A-514
TYP.
10 A-521
2 A-514
TYP.
2 A-514
SEAL D A RCH SE I E N A N McM TE H U T A
CT Y R RT
LI J ON C
2 A-521
CONSULTANT
7
N
R E
EN . 08 - 3 1 - 1 O F OF CAL I 9
A
T
R
ST
TOP PLATE 112'-0"
IA
C23603
PROJECT
C
CAMPUS SAFETY 126
12 A-511
COUNSELOR
COUNSELOR
COUNSELOR
LOBBY
128
130
132
100
CLASSROOM/LOBBY OVERFLOW
ADMIN OFFICE
101
102
12 A-511
TEHAMA CENTER STUDENT SERVICES 12 A-511
12 A-511 LEVEL 1 100'-0"
1
11
2
A-311 A-311
A-311
770 DIAMOND AVE RED BLUFF, CA 96080
SECTION THROUGH MECH WELL
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
SCALE 1/4" = 1'-0"
DATE 05/17/2019
DESCRIPTION DSA BACKCHECK
GENERAL NOTES
B
1.
BUILDING SECTIONS INTENDED TO INDICATE MAJOR BUILDING SYSTEMS. SEE FLOOR PLAN AND INTERIOR ELEVATIONS FOR INDIVIDUAL ROOM ELEMENTS AND ACCESSORIES.
2.
FOR CEILING HEIGHTS, SEE CEILING PLANS.
3.
UNO FIRE SPRINKLER MAIN AND BRANCH LINES ARE TO BE CONCEALED; RUN UNDER BOTTOM CHORD OF TJI AND ABOVE SUSPENDED CEILING (RUN IN PLENUM) AND/OR WALL CAVITY BETWEEN FRAMING, UON. SPRINKLER MAIN AND BRANCH LINES SHALL NOT BE EXPOSED IN CLASSROOMS, ADMINISTRATION AREAS, OFFICES, RESTROOMS, OR OCCUPIED SPACES UNO. PROVIDE DRAWINGS AS REQUIRED PER SPECS (FIRE PROTECTION SECTION), TYP FOR ALL BUILDINGS. MANAGEMENT
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
KEY PLAN
1 A-314
1 A-314
A
TITLE
SECTIONS - BUILDING
PLAN NORTH
5/15/2019 3:48:23 PM
017294 ?00.00.00? LIONAKIS 2017
SHEET
A-314
2"
1
2
3
4
5
GENERAL NOTES 1"
1.
5
E
0 1/4" 1/2"
A
B
C
G F
D
2.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SEE FINISH LEGEND ON SHEET A-641 FOR WALL TILE PATTERN AND ADDITIONAL FINISH CLARIFICATION.
APP. 02-117123
REVIEWED FOR
REFER TO PLUMBING DRAWINGS FOR FIXTURE TYPES.
H
3.
CONTRACTOR TO PROVIDE BACKING AS REQUIRED; SEE TYPICAL BACKING DETAIL 18/A-521
4.
FOR ACCESSIBLE CLEARANCES AND FIXTURE MOUNTING HEIGHTS SEE SHEETS G-511 & G-512.
5.
SEE SHEET G-513 FOR TYPICAL ACCESSIBLE SIGNAGE DETAILS.
6.
STAFF TOILET ROOM WALLS TO BE FINISHED WITH PL4, UNO.
7.
FLOOR DRAINS SHALL HAVE 1/4" MAXIMUM GRATE OPENINGS IN ALL DIRECTIONS.
8.
AREAS WITH FLOOR DRAINS SHALL BE SLOPED TO DRAIN AT 2% MAXIMUM IN ALL DIRECTIONS.
9.
ALL DIMENSIONS INDICATED FOR ACCESS COMPLIANCE ARE TO FACE OF FINISH, UNO.
SS
✔
" -0 5'
118W
A-411
RESTROOM
118E
118S
ACS
✔
✔
07/03/2019
10. WHERE MIRROR STRADDLES GYPSUM BOARD WALL AND WAINSCOT, PROVIDE BACKING AT GYP BD TO MAKE A LEVEL, VERTICAL INSTALLATION, TYPICAL. 1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D PLAN NORTH
1
FLS
118 17"-18"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
ø
118
MIN
30" x 48" MIN CLR
18"
DATE:
B.6
INC:
LARGE SCALE VIEW - RESTROOM
NORTH
118
SCALE 1/4" = 1'-0"
EAST
SOUTH
WEST
RESTROOM 118
CONSULTANT
TOILET ACCESSORY SCHEDULE
SCALE 1/4" = 1'-0"
TYPE MARK DESCRIPTION A RECESSED TOWEL DISP./WASTE RECEPTACLE B GLASS MIRROR WITH STAINLESS STEEL ANGLE FRAME C SURFACE-MOUNTED SOAP DISPENSER D 42" GRAB BAR E 48" GRAB BAR F SURFACE-MOUNTED SANITARY NAPKIN DISPOSAL G RECESSED MULTI-ROLL TOILET TISSUE DISPENSER H SURFACE-MOUNTED SEAT-COVER DISPENSER
4
MANUFACTURER MODEL BOBRICK B-369 BOBRICK
B-290 1830
BOBRICK
B-2111
BOBRICK BOBRICK BOBRICK
B-6806x42 B-6806x48 B-270
BOBRICK
B-4388
BOBRICK
B-221 SEAL
NOTE:
A-411
119S
IA
N
R E
EN . 08 - 3 1 - 1 O F OF CAL I 9
T
119E 4'-0"
119W
C23603
A
119
FLOOR DRAIN COVERS TO HAVE 1/4" SQUARE OPENINGS MAX. CONTRACTOR SHALL SUBMIT TESTING PROTOCOL TO DSA FOR REVIEW AND APPROVAL OF GRAB BAR CONNECTION TO TOILET PARTITIONS, TYP.
R
CUSTODIAL
2.
D A RCH SE I E N A N McM TE H U T A
ST
119
HOT WATER HEATER
"OFCI" - OWNER FURNISHED CONTRACTOR INSTALLED. CONTRACTOR SHALL BE RESPONSIBLE FOR BLOCKING REQUIREMENTS, SEE BACKING DETAIL 18 / A-521 . ALL ACCESSORIES SHALL BE ADA COMPLIANT AT ADA REQUIRED LOCATIONS.
LI J ON C
B.6
1.
CT Y R RT
MOP RACK, PROVIDE BLOCKING PER STRUCT
MOP SINK PROJECT
C
TEHAMA CENTER STUDENT SERVICES PLAN NORTH
2
LARGE SCALE VIEW - CUSTODIAL SCALE 1/4" = 1'-0"
NORTH
119
EAST
SOUTH
WEST
770 DIAMOND AVE RED BLUFF, CA 96080
CUSTODIAL 119 SCALE 1/4" = 1'-0" CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
B
MANAGEMENT
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
A
TITLE
LARGE SCALE VIEWS
SHEET
5/15/2019 3:48:26 PM
017294 ?00.00.00? LIONAKIS 2017
A-411
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123 EXTERIOR INSULATION SHALL OCCUR WHERE SOFFIT VENTILATION IS NOT REQUIRED. WOOD STUD WALL W/ INSUL AND EXT NOTE: ATTACHMENT OF FIBER SHEATHING PER CEMENT SOFFIT BOARD PER ESRWOOD STUD WALL W/ PLAN ESR-2273, MIN. 11ROOFING GA. ROOFING 2273, MIN. 11 GA. NAILS W/ AND EXT SHEATHING NAILS W/ MIN. 1-1/2" PENETRATION MIN. 1-1/2" PENETRATION INTO PER PLAN. INTO FRAMING @ 6" AT EDGES FRAMING @ 6" OC ATOC EDGES AND 6" AND 6" INTERMEDIATE OC AT INTERMEDIATE OC AT FRAMING FRAMING PER MEMBER PER MEMBER SPECIFICATIONS OR SPECIFICATIONS OR APPROVED APPROVED EQUIVALENT. FIBER CEMENT 9 SIDING A-511
WOOD STUD WALL W/ INSUL AND EXT SHEATHING PER PLAN EXTEND 6" STRIP BLDG WRAP O/ ALUM MOLDING FLANGES, TYP EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
WEEP SCREED CL REVEAL DIM. POINT
22 GA MTL EDGE FLASHING AND SOFFIT CORNER TRIM
4" LEG
D
1/2"
1'-0"
1"
22 GA 'Z' DRIP EDGE
1
1/2"
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
7/8"
1 1/2"
PLASTER TO SIDING HORIZONTAL
BLIND ATTACHMENT, SIZE AND SPACING PER ESR-2290, 6D ROOFING NAILS @ 16" OC HORIZONTALLY INTO PER FRAMING PER SPECIFICATIONS OR SPECIFICATIONS OR APPROVED APPROVED EQUIVALENT. DO EQUIVALENT. DO NOT NOT OVERDRIVE OR OVERDRIVE OR COUNTERSINK COUNTERSINK FASTENER FASTENER
1"
3/8"
1" MIN.
(2) LAYERS BLDG WRAP
FIBER CEMENT SOFFIT "J" TRIM, FCP-J CHANNEL BY FRY REGLET OR APPROVED EQUIVALENT
FULL-DEPTH INSULATION TO OCCUR AT ALL EXTERIOR WALLS
EXT PLYWOOD SHEATHING PER STRUCTURAL
FIBER CEMENT VENTED SOFFIT TRIM, FCPFIBER CEMENTPCS375V300 VENTED SOFFIT TRIM, BY FRY FCP-PCS375V300 BY FRY OR REGLET ORREGLET APPROVED APPROVED EQUIVALENT WHERE SOFFIT EQUIVALENT VENTILATION IS REQUIRED PER PLAN
1'-0"
7/8"
3" = 1'-0"
Q2
13
6" = 1'-0"
07/03/2019
1 1/8"
1"
TYP.
CONSULTANT
EXT PLYWOOD SHEATHING PER STRUCTURAL
FIBER CEMENT SOFFIT "J" TRIM, FCP-J CHANNEL BY FRY REGLET OR APPROVED EQUIVALENT
3/8"
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
1" MIN.
3"
FULL-DEPTH INSULATION TO OCCUR AT ALL EXTERIOR WALLS WOOD FRAMING PER STRUCTURAL INTERIOR FINISH PER SCHEDULE
PLASTER TO SOFFIT BOARD
17
3" = 1'-0"
Q2
Q2
✔
MIN #8 WOOD SCREW W/ 7/16 DIA PAN WAFER HEAD @ 16" HORIZONTAL AT EA STUD AND AT EA RIB (7" OC MAX). MAINTAIN 1/4" GAP BETWEEN LATH AND SUBSTRATE, MIN
FIBER CEMENT VENTED SOFFIT TRIM, FIBER CEMENT VENTED FCP-PCS375V300 BYTRIM, FRY REGLET OR SOFFIT FCPAPPROVED PCS375V300 EQUIVALENTBY WHERE FRY SOFFIT VENTILATION IS REQUIRED REGLET OR APPROVED PER PLAN EQUIVALENT
FIBER CEMENT SIDING, TYP
ACS
✔
SELF FURRING MTL LATH FURRED OUT FROM 1/4" FROM SHEATHING
FIBER CEMENT SOFFIT BOARD, SIZE AND SPACING OF ATTACHMENT PER ESR-2273
INTERIOR FINISH PER SCHEDULE
9
DATE:
FLS
(2) LAYERS BLDG WRAP
1 1/2"
WOOD FRAMING PER STRUCTURAL
✔
EXTERIOR CEMENT PLASTER
TYP.
3"
FIBER CEMENT SOFFIT BOARD, SIZE AND SPACING OF ATTACHMENT PER ESR-2273
SS
EXTEND 6" STRIP BLDG WRAP O/ FLASHING & SCREED FLANGES, TYP
WEEP SCREED AND SOFFIT CORNER TRIM
SIDING TO SOFFIT BOARD
5
6" = 1'-0"
1 1/8"
3"
4"
1 1/2" 1 1/8"
9 A-511
FIBER CEMENT SIDING, LAP PER MANUF
EXTEND 6" STRIP BLDG WRAP O/ FLASHING & SCREED FLANGES, TYP
CONT SEALANT
1/2"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
17 A-511
REVIEWED FOR
EXTERIOR INSULATION SHALL OCCUR WHERE SOFFIT VENTILATION IS NOT REQUIRED. WOOD STUD WALL W/ INSUL ANDWALL EXT WOOD STUD NOTE: ATTACHMENT OF FIBER SHEATHING PER AND EXT SHEATHING CEMENT SOFFIT BOARD PER ESRPLANPLAN PER ESR-2273, MIN. 11ROOFING GA. ROOFING 2273, MIN. 11 GA. NAILS W/ NAILS1-1/2" W/ MIN. 1-1/2" PENETRATION MIN. PENETRATION INTO INTO FRAMING @ 6" AT EDGES FRAMING @ 6" OC ATOC EDGES AND 6" EXTERIOR AND 6" OC AT INTERMEDIATE OC AT INTERMEDIATE FRAMING CEMENT PLASTER FRAMING PER MEMBER PER MEMBER SPECIFICATIONS OR O/ SELF-FURRING SPECIFICATIONS OR APPROVED APPROVED EQUIVALENT. MTL LATH O/ (2) LAYERS BLDG 17 WRAP A-511
3"
0 1/4" 1/2"
INTERIOR FINISH PER SCHEDULE
INC:
PLASTER, TYP 6" = 1'-0"
Q2
Q2 INTERIOR FINISH PER SCHEDULE WOOD STUD WALL W/ INSUL AND EXT SHEATHING PER PLAN SEAL
WOOD STUD WALL W/ INSUL AND EXT SHEATHING PER PLAN FIBER CEMENT SIDING O/ (2) LAYERS 9 BLDG WRAP A-511
CONT SEALANT
CL OF REVEAL DIM. POINT
17 A-511
APPLY 6" WIDE STRIP OF BLDG. WRAP BEHIND TRIM, TYP. EXTEND 6" STRIP BLDG WRAP O/ ALUM REVEAL FLANGES, TYP
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
CL OF REVEAL DIM. POINT
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
17 A-511
PLASTER TO SIDING - VERTICAL 6" = 1'-0"
Q2
LI J ON C
IA
N
R
9
EN . 08 - 3 1 - 1 O F OF CAL I
TEHAMA CENTER STUDENT SERVICES
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
1" MIN.
770 DIAMOND AVE RED BLUFF, CA 96080
CP-1 VERTICAL CONTROL JOINT. TERMINATE EA SIDE OF HORIZONTAL REVEAL CLIENT
9 A-511
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
SIDING TRIM - INSIDE CORNER
6
R E
PROJECT
ALUMINUM T-MOLD
2
T
TYP.
SIDING END ATTACHMENT TO OCCUR OUTSIDE OF TRIM FLANGE
EXTERIOR CEMENT 17 PLASTER O/ SELFFURRING MTL LATH O/ A-511 (2) LAYERS BLDG WRAP
PLASTER HORIZONTAL REVEAL
C23603
1" REVEAL
CL
1/4" DIA WOOD SCREW TO 2X TYPE "A" WOOD BACKING, (2) MIN PER LETTER; PROVIDE SELF-ADHERED FLASHING BEHIND CEMENT PLASTER SYSTEM AT LETTERS
1" MIN.
FCP-INTISCNR750 INTEGRAL INSIDE LAP CORNER BY FRY REGLET OR APPROVED EQUIVALENT
C
4" MAX
1" REVEAL
4" MAX.
1/8" TYP.
CONT. SEALANT EA SIDE
18 A-511
A
9 A-511
3 A-511
ALUM REVEAL, DCS-625-100 BY FRY REGLET OR APPROVED EQUIVALENT O/ (2) LAYERS BLDG WRAP, CUT METAL LATH AT HORIZ REVEAL. DO NOT RUN CONT BEHIND.
ST
1/8" TYP
CAST MTL LETTERS, COLOR TBD - SEE FOR SIZE AND FINISH, VERIFY NAMES W/ ARCHITECT BEFORE FABRICATION
D A RCH SE I E N A N McM TE H U T A
CT Y R RT
VERTICAL CONTROL JOINT. TERMINATE EA SIDE OF HORIZONTAL REVEAL
EXT PLYWOOD SHEATHING PER STRUCTURAL
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
EXTEND 6" STRIP BLDG WRAP O/ ALUM REVEAL FLANGES, TYP.
10
6" = 1'-0"
SIGNAGE AT CEMENT PLASTER 1 1/2" = 1'-0"
Q1
Q2
14
VERTICAL CONTROL JOINT AT HORIZONTAL REVEAL
18
6" = 1'-0"
PLASTER HORIZONTAL REVEAL 6" = 1'-0"
Q2
Q2
ISSUED
INTERIOR FINISH PER SCHEDULE
MARK
WOOD STUD WALL W/ INSUL AND EXT SHEATHING PER PLAN
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
RUN CONT BLDG WRAP UNDER CONTROL JOINT
24"
9 A-511
EXTEND 6" STRIP BLDG WRAP O/ CONTROL JOINT FLANGES, TYP.
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
CONTROL JOINT, XJ15 BY CLARK-DIETRICH OR APPROVED EQUIVALENT.
EXT PLYWOOD SHEATHING PER STRUCTURAL
11"
FCP-PXM7575 X CORNER LAP TRIM BY FRY REGLET OR APPROVED EQUIVALENT
1/8" TYP
CONT. SEALANT EA SIDE
B 9 A-511
EXTEND 6" STRIP BLDG WRAP O/ CORNER BEAD FLANGES, TYP
CL OF CONTROL JOINT DIM. POINT
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
17 A-511
CORNER BEAD, CBXA BY CLARK-DIETRICH OR APPROVED EQUIVALENT 11"
WOOD STUD WALL W/ INSUL AND EXT SHEATHING PER PLAN
9 A-511
1/4"
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
17 A-511
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
017294 ?00.00.00? LIONAKIS 2017
AGENCY
SIDING TRIM - OUTSIDE CORNER
11
6" = 1'-0"
SIDING TRIM - VERTICAL 6" = 1'-0"
Q2
Q2
INTERIOR FINISH PER SCHEDULE
WOOD STUD WALL W/ INSUL AND EXT SHEATHING PER PLAN
EXTERIOR CEMENT PLASTER O/ SELF-FURRING MTL LATH O/ (2) LAYERS BLDG WRAP
EXTEND 6" STRIP BLDG WRAP O/ FLASHING & SCREED FLANGES TYP
CONC WALK OR MOW STRIP PER PLAN
TOC SEE PLAN
SLOPE
FRAMING CLIP, SEE TYP DETAILS EXTEND 6" STRIP BLDG WRAP O/ FLASHING & SCREED FLANGES TYP
3"
WEEP SCREED 1 1/8"
EXT. SURFACE MOUNTED LIGHT FIXTURE, SEE ELECTRICAL
22 GA ALUM FLASHING SACK AND PATCH EXPOSED CONC CURB
1 1/2"
CONC WALK OR MOW STRIP PER PLAN
TOC SEE PLAN
SLOPE
TITLE
DETAILS - EXTERIOR
EXTEND 6" STRIP BLDG WRAP O/ FLASHING, TYP
NOTE: CONT SEALANT @ SIDES OF CEMENTITIOUS TRIM
SLAB/CURB REINF PER PLAN
NOTE: CONT SEALANT @ SIDES OF CEMENTITIOUS TRIM
VAPOR BARRIER- INSTALL PER MANUFACTURER'S REQUIREMENTS
8
17 A-511
1 X WOOD TRIM
6" MIN-EARTH
1 1/2"
POLYETHYLENE STRIP CAPILLARY BREAK UNDER P.T. FRAMING
FLASHING W/ HEMMED EDGE 2", TYP
4"
SACK AND PATCH EXPOSED CONC CURB
1/2"
EXT. SURFACE MOUNTED LIGHT FIXTURE SEE ELECTRICAL
22 GA ALUM FLASHING
P.T. SILL ANCHORAGE PER STRUCT
WEEP SCREED
FIBER CEMENT STARTER SHIM 1 1/8"
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
WOOD STUD WALL W/ INSUL AND EXT SHEATHING PER PLAN
FRAMING CLIP, SEE TYP DETAILS
1 X WOOD TRIM A
INTERIOR FINISH PER SCHEDULE
POLYETHYLENE STRIP CAPILLARY BREAK UNDER P.T. FRAMING
FIBER CEMENT STARTER SHIM 22 GA MTL FLASHING W/ HEMMED EDGE
Q2
WOOD STUD WALL W/ INSUL AND EXT SHEATHING PER PLAN
P.T. SILL ANCHORAGE PER STRUCT 9 A-511
6" = 1'-0"
Q2 INTERIOR FINISH PER SCHEDULE
2" MIN-PAVING
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
19
3" = 1'-0"
PLASTER CONTROL JOINT
INTERIOR FINISH PER SCHEDULE
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
WOOD STUD WALL W/ INSUL AND EXT SHEATHING PER PLAN
15
PLASTER OUTSIDE CORNER
6" MIN-EARTH
7
2", TYP
Q1
2" MIN-PAVING
1/4" = 1'-0"
4"
ENLARGED SIGNAGE ELEVATION
1/2"
3
1/8" TYP
EXTEND 6" STRIP BLDG WRAP O/ FLASHING, TYP
5/15/2019 3:48:28 PM
MANAGEMENT
ALUMINUM T-MOLD
3"
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
CONT SEALANT EA SIDE
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
12 SIDING TO CURB
SIDING EXT. MOUNTED FIXTURE
16
3" = 1'-0"
3" = 1'-0"
Q2
Q2
SLAB/CURB REINF PER PLAN
SHEET
EXT. MOUNTED FIXTURE @ PLASTER
VAPOR BARRIER- INSTALL PER MANUFACTURER'S REQUIREMENTS
20
3" = 1'-0"
Q2
A-511
PLASTER TO CURB 3" = 1'-0"
Q2
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
REVIEWED FOR
HOT AIR WELD & SEAM CAULK
EXT BLDG WALL LINE 3" MITERED AND SEALED ALBOW WRIVETS, PREFIN TO MATCH GUTTER
TJI OR WD FRAMING SEE STRUCT
STRUCTURAL BLKG W/HANGER & LAG BOLT PER MECH DWGS
DS BRACKET SEE
NOTE: SEE
1
VENT PIPE BOOT FLASHING
5
1 1/2" = 1'-0"
MECHANICAL UNIT CURB
DIM POINT
1'-0"
GALV STL CONDUCTOR HEAD
11 A-512
FOR ADDITIONAL INFO
COUNTER FLASHING
EXT BUILDING WALL LINE
GALV STL SCUPPER
3" DIA GALV STL PIPE PAINT TO MATCH GUTTER
GALV STL CONDUCTOR HEAD PRE-FIN PAINT
BATT INSULATION COMPLETELY FILL CAVITY FRMG SPACE TYP AT CLERESTORY
CONT 30# FELT PER ROOF PLAN
1 3/4" 4" 2"
CONT BACKER ROD & SEALANT
BATT INSULATION
STORM DRAIN PIPE SEE CIVIL
FOR ADDL INFO
6
1 1/2" = 1'-0"
DUCT THRU ROOF
10
3" = 1'-0"
Q2
14
1 1/2" = 1'-0"
Q2
SINGLE PLY ROOFING O/GYP COVER BD
SINGLE PLY ROOFING UP PARAPET O/PLYWD
2" MIN TAPERED RIGID INSULATION
VENT PIPE SEE PLUMB
DOWNSPOUT AT GRADE
CEM PLAS SYST O/CONT BLDG WRAP O/PLYWD
SHEET MEMB WATERPROOFING AROUND OPENING
SHINGLE ROOFING O/ROOF FELT PAPER O/SMW O/PLY WD DECK
STORM COLLAR 6"
MTL ROOF PANEL SYS O/CONT ROOF FELT PAPER
T
R E
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
TEHAMA CENTER STUDENT SERVICES OVERFLOW DRAIN PIPE W/RAISED 2" COLLAR DRAIN PIPE. SEE PLUMB DWGS
TJI FRMG BEYOND PER STRUCT
770 DIAMOND AVE RED BLUFF, CA 96080
ROOF DRAIN PIPE PER PLUMB DWGS CLIENT
13 A-512
FOR ADDIT INFO
TYPICAL WALL SCUPPER
18
1 1/2" = 1'-0"
Q2
NOTE: FLAT 2X6 BLKG AT 8'0" OR VERTICAL SPACING MAX SEE FOR MAX SPACING TO BRACKET ABOVE CONC SIDEWALK
C23603
MECH WELL ROOF DRAIN AND OVERFLOW 1 1/2" = 1'-0"
Q2
18 A-521
A
SHINGLE ROOFING O/ ROOF FELT PAPER O/ SHEET MEMBRANE WATERPROOFING O/ PLY WD DECK
TYPICAL BRACKETS SHALL BE 3/16" (THICK) X 1 1/2" (WIDE) GALV BENT STEEL @ 8'-0" O.C. VERT SPACING MAX. ALIGN LOCATIONS THROUGHOUT ENTIRE BLDG. PAINT TO MATCH DS. ANCHOR BRACKETS PAINT TO MATCH DS W/ -1/4" DIA X 2 1/2" LAG BOLT AT BLDF WD FRMG -0.145" DIA X 1" PAF W/ WASHER AT STL COLUMN -#14X2" SST WD SCREW AT EXT COLUMN WD TRIM
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
Q2
MARK CLAMP RING TYP
SINGLE-PLY MEMBRANE
RIGID INSUL BELOW ROOF DRAIN PAN 5 1/2"
ISSUED
STRAINER TYP
2 LAYERS SINGLE-PLY MEMBRANE DRAIN FLASHING WELDED SOLID TOGETHER
CL
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
SHEET MEMBRANE WATERPROOFING
CL 5 1/2"
1'-5 1/2"
2"
VENT PIPE FLASHING - STEP 1
SINGLE-PLY MEMBRANE
9 A-512
NOTE: SEE
2
7"
CEM PLAS SYS O/BLDG WRAP
NOTE: SEE
STRAINER TYP 1'-5 1/2"
FIBER CEMENT SOFFIT SMOOTH FIN
DOWNSPOUT SEE
3 A-512
CLAMP RING TYP
SHAPED 2X12 EXT TRIM RAKE PAINT TO MATCH GUTTER
2" 1'-0"
CONC SIDEWALK, MOW STRIP OR PAVING SEE CIVIL
4X4 BLKG W/"SIMPSON" A34 EA SIDE EA END
FIELD CUT HOLE IN PLY WD DECK 1" MIN LARGER THAN PIPE
DS CLEANOUT BOOT SEE PLUMB
ROOF SHTHG & FRAMING
D A RCH SE I E N A N McM TE H U T A
1X8 TRIM PAINT TO MATCH FASCIA
9"
SEAL
A
3/8" LAG BOLT W/2" EMBED MIN 2 PER SIDE
2 LAYERS SINGLE-PLY MEMBRANE DRAIN FLASHING WELDED SOLID TOGETHER
2" RIGID INSULATION TAPERED AROUND DRAIN
1'-0"
DIM POINT
C
GYP COVER BD
ST
11 A-512
Q2
SHEET MEMBRANE WATERPROOFING
1"
DS BRACKET SEE
1" = 1'-0"
Q2
SINGLE PLY ROOFING O/GYP BD O/2" MIN RIGID INSUL
SEE MECH
SST HOSE CLAMP
SINGLY PLY UP CURB
ROOF DRAIN PLAN
CT Y R RT
PREFABRICATED ROOF CURB, SEE MECH
VENT PIPE SEE PLUMB
17
1 1/2" = 1'-0"
Q2 SINGLE PLY ROOFING O/ TAPERED RIGID INSUL CRICKET SEE ROOF PLAN
DUCTWORK SEE MECH
1'-0"
3'-6"
13 SCUPPER DETAIL
1 1/2" = 1'-0"
1'-6"
NOTE: RAKE TRIM CUT BACK FOR CLARITY; RAKE TO BE CONTINUOUS TO END OF ROOF EDGE
GALV STL PIPE DOWNSPOUT 10 SEE A-512
Q2
ASPHALT SHINGLES ON SHEET MEMBRANE WATERPROOFING TYP AROUND OPENINGS O/ROOF FELT PAPER O/PLY WD DECK
PRE-FITTED PIPE FLASHING RIVET TO TO MTL ROOF PANEL
2X12 EXT RAKE TRIM PAINT TO MATCH GUTTER
DOWNSPOUT DETAIL
9
1 1/2" = 1'-0"
Q2
10 A-512
18 A-512
CONSULTANT
CIRCULAR TRANSITION BOOT PAINT TO MATCH GUTTER
ROOF FRAMING SEE STRUCT FOR BLOCK FRMG AT OPENINGS
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
IA
D
TAPERED RIGID INSUL GALV STL SCUPPER W/ COATED METAL EDGE
N
SINGLE PLY ROOFING O/GYP COVER BD O/2" MIN RIGID INSUL
2"LAYERS RIGID INSUL 2 5/8" GYP BD INSIDE CURB 2 LAYERS 5/8" GYP BD 2" RIGIDCURB INSUL INSIDE
OVERFLOW W/ LEAD FLASHING GUARD PLATE
1'-0"
SINGLE PLY ROOFING O/GYP COVER BD O/2" MIN RIGID INSUL
07/03/2019
1X8 TRIM PAINT TO MATCH RAKE
POP RIVET TO LEADER
8"
FASTENER WITH DISC MIN. OF 4 AROUND VENT PIPE
✔
1X4 NAILER
GUTTER STRAINER AND LEADER
9
CONTINUOUS MEMBRANE WELD
ACS
✔
R
MIN. 4X PRESSURE TREATED CONT WOOD LEVELING BLOCKING W/LAG BOLTS PER MECH DWGS
LI J ON C
MECH VIBRATION SPRING MOUNT & ATTACHMENT SEE MECH
MIN. 2" ABV. ADJ. ROOF
MEMBRANE BOOT WITH MIN 1" TURN-UP
FLS
ROOF DRAIN PER PLUMBING DWGS
PLY WD SHTHG PER STRUCT
2 1/4"
POLYURETHANE CAULKING APPLIED BEHIND TURN-UP AND TOP OF THE DRAW BAND
✔
DATE:
1'-0"
DRAWBAND
CONTINUOUS PREFIN MTL. GUTTER
SS
14 A-512
2 1/8"
VENT PIPE
NOTE: SINGLE PLY ROOFING NOT SHOWN FOR CLARITY SEE FOR ADDT'L INFO
5 7/8"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
ROOFING SYSTEM, SEE ROOF PLAN MECH UNIT, FLASHING & MOUNTING, SEE MECH
INC:
PRE-FITTED PIPE FLASHING RIVET TO MTL ROOF PANEL
" 1'-2
PLYWD SHTHG
ROOF FRAMING SEE STRL S1.6 FOR BLOCK FRMG @ OPENINGS
3" DIA GALV STL PIPE SEE & MECH DWGS
PLASTER CASING JBEAD MOLDING
7
1 1/2" = 1'-0"
5 A-511
WALL ALIGNS WITH INT FACE OF COLUMN BEYOND
11
3" = 1'-0"
Q2
Q2
WALL ALIGNS WITH INT FACE OF COLUMN BEYOND 6 A-511
SIDING
12
EQ
CORNER BEAD, CBXA BY CLARKDIETRICH OR APPROVED EQUIVALENT
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
SHADED AREA INDICATES EXTENTS OF 6X10 HEADER AND FRAMING PER 11/S-561
20 A-511
12 A-511
OMIT INTERIOR FINISH
15 A-511
SIDING INSIDE CORNER BEYOND
2
INTERIOR
LEVEL 1 100'-0"
+0"
OVERFLOW DOWN SPOUT SEE PLUMBING DWGS
6"
6"
CL
PLASTER & SEALANT TIGHT AROUND PIPE
GALV STL PIPE SCHEDULE 40 W/ CAST IRON FITTING UP TO 18" HIGH TRANSITION TO NO HUB FITTINGS
CAST IRON OVERFLOW SCUPPER W/THREADED CONNECTION
NO HUB CONNECTION @ OVERFLOW DOWN PIPE TO ELBOW FITTING
12" ABOVE GRADE TYP
EXTERIOR
7 A-511
-10"
FLASHING TAPE AT PIPE PENETRATION
12 A-511
INTERIOR FINISH OF WALL BEYOND
1 1/2" = 1'-0"
CONT BLDG WRAP
WALL ALIGNS WITH EXT FACE OF COLUMN BEYOND
SLOPING SOFFIT
AGENCY
ROOF DRAIN AND OVERFLOW ABOVE CLERESTORY
CEMENT PLASTER SYS O/BLDG WRAP
9 A-511
2X4 @ 16" OC W/ (2) 8D TOE NAILS EACH SIDE, EACH END
+0" LEVEL 1 100'-0"
TITLE
2X BLKG FOR ELBOW & RWL STL PIPE STRAP SUPPORT
CONT BACKER ROD & SEALANT AROUND PIPE
5/8" GYP BD
EXTEND 6" STRIP BLDG WRAP O/ FLASHING & SCREED FLANGES, TYP
WD SILL & STUD FRMG SEE STRUCT
SEALANT O/FIBRE EXP MATERIAL
METAL GYP BD CLIP PER STRUCT
DETAILS - EXTERIOR
CONC PAVING
5/15/2019 3:48:30 PM
PER PLAN
4
CANOPY COLUMN W/ PLASTER COLUMN
12
3" = 1'-0"
Q2
Q2
INTERIOR WALL ELEVATION SOUTH WALL
16
1/4" = 1'-0"
Q2
017294 ?00.00.00? LIONAKIS 2017
CONT BLDG WRAP TO CONC CURB
A-211
SLOPING CEILING
16 A-512
EQ
OMIT INTERIOR FINISH EXTEND 6" STRIP BLDG WRAP O/ CORNER BEAD FLANGES, TYP
9 A-511
ROOF DRAIN RUN IN WALL FRMG
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
Q2
MIN (3) 2X6 SILL PER 11/S-561
6X10 HEADER PER 11/S-561
PER PLAN
17 A-511
PER PLAN
A
17 A-511
PER PLAN
EXTERIOR CEMENT PLASTER O/ SELF-FURRING MTL LATH O/ (2) LAYERS BLDG WRAP
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
STEEL HSS COLUMN AND FRAMING PER STRUCT
19
+6'-0" SILL
PER PLAN
STEEL HSS COLUMN, SEE STRUCT
ROOF OVERFLOW DRAIN RUN IN FURRED WALL. DAYLITE AT BLDG EXT WALKWAY SOFFIT PER RCP
15 A-541
DOWNSPOUT BRACKET
A-512 STEEL HSS COLUMN, SEE STRUCT
MANAGEMENT
13 A-541
1 1/2" = 1'-0"
EQ
BATT INSUL
5/8" GYP BD TYPE 'X'
+9'-0" SOFFIT
19 A-511
45°
EQ CEMENT PLASTER
CL
10 A-512
CEM PLAS CONTROL JOINT. FOR ADDITIONAL INFO, SEE LOCATE 1" AWAY FROM LAG.
COVERED WALKWAY AT MECH WELL
Q2
WALL ALIGNS WITH EXT FACE OF COLUMN BEYOND
6X10 HEADER PER 11/S-561
CEM PLAS SYST O/CONT BLDG WRAP O/PLYWD
VENT PIPE FLASHING - STEP 2
VENTED SOFFIT BOARD
4X12 HEADER PER 11/S-561
FIBER CEMENT SOFFIT
" 1'-0
3
GLB PER STRUCTURAL
12".
GLB SEE STRUCT
FASTENER WITH DISC MIN OF 4 AROUND VENT PIPE
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
16 GAUGE X 1 1/2" WIDE GALV STL STRAPS TYP ANCHOR TO BRACKETS W/ # 10 RHSTS EA SIDE PAINT TO MATCH DS
2"
B
EXTERIOR WALL SECTION SOUTH WALL
20
1 1/2" = 1'-0"
Q2
SHEET
OVERFLOW DRAIN TERMINATE ABOVE GRADE
A-512
1 1/2" = 1'-0"
Q2
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
GUTTER HANGER BRACKETS @ 36" OC
4"
2x4 SOFFIT NAILER @ 12" OC
18 A-514
WD STUD FRMG SEE STRUCT
2" MIN TAPERED RIGID INSUL
4"
PLATE FRMG PER STRUCT
2"
EQ
RIM BD PER STRUCT
EQ
WINDOW, SEE SCHED DS, WHERE OCCURS, RUN BACK TO FACE OF COLUMN SEE
1 1/2" = 1'-0"
Q2
SHINGLE ROOFING O/ ROOF FELT PAPER O/ PLY WD DECK
5
CONT BACKER ROD & SEALANT
BEAM PER STRUCT
CEMENT PLASTER SYS O/ BLDG WRAP
HSS COLUMN PER STRUCT
3" = 1'-0"
Q2
4"
SNAP ON CLIP
NOTE: SEE STRUCTURAL FOR WELDING REQUIREMENTS OF HSS MEMBERS AND ANGLES TYPE 2 METAL ROOF PANEL SYSTEM
1'-8", TYP.
SINGLE PLY ROOFING EXTEND 4" OVER EDGE TYP. 6"
PREFIN MTL FLASHING 1x8 TRIM PAINT TO MATCH FASCIA
C23603
SINGLE PLY O/ SLOPED RIGID INSUL (MIN INSUL 4") PER ROOF PLAN
2x OUTRIGGER PER STRUCT
VARIES (MIN. 2'-6")
10
1 1/2" = 1'-0"
Q2 6 A-514
CEMENT PLASTER SYS O/ BLDG WRAP
RAKE FLASHING AT CLERESTORY 1 1/2" = 1'-0"
6" SELF ADHERE FLASHING O/ GALV MTL DRIP FLANGE
14
RAFTERS PER STRUCT
SEE WINDOW SCHED
VALLEY RAFTER PER STRUCT
HSS BEAM, SEE STRUCT PAINT COLOR TO MATCH CEMENT PLASTER FINISH 2
SINGLE-PLY VALLEY FLASHING
18
1 1/2" = 1'-0"
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
WINDOW CANOPY SECTION AT CEMENT PLASTER 1 1/2" = 1'-0"
Q2
Q2
Q2 NOTE: SEE STRUCTURAL FOR WELDING REQUIREMENTS OF HSS MEMBERS AND ANGLES
SHINGLE ROOFING O/ ROOF FELT PAPER O/ SHEET MEMBRANE WATERPROOFING O/ PLY WD DECK
FRAMING, SEE STRUCT
ISSUED
MARK
17 A-514
TYPE 2 METAL ROOF PANEL SYSTEM
1'-8", TYP.
SINGLE PLY COATED METAL FLASHING
WEEP SCREED
770 DIAMOND AVE RED BLUFF, CA 96080
ANGLE PER STRUCT PAINT TO MATCH BEAM
BATT INSULATION COMPLETELY FILL CAVITY FRMG SPACE TYP AT CLERESTORY
1x8 TRIM PAINT TO MATCH FASCIA
SINGLE PLY ROOFING O/ SHEET MEMBRANE WATERPROOFING O/ PLY WD DECK
TEHAMA CENTER STUDENT SERVICES
ALIGN BOTTOM OF BEAM W/ BOTTOM OF WINDOW HEADER CONCEALED PLATE TO RECEIVE RUST RESISTANT PAINT
SNAP ON CLIP
CEM PLAST SYS O/ CONT BLDG WRAP
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
Q2
FOR TYPICAL NOTES, SEE DETAIL
R E
2x4 SOFFIT NAILER
CONT BACKER ROD & SEALANT
HIGH EAVE FASCIA FLASHING AT CLERESTORY
T
2'-0"
2x12 EXT TRIM FASCIA PAINT TO MATCH GUTTER
FIBER CEMENT SOFFIT
D A RCH SE I E N A N McM TE H U T A
4" TO HDR
FIBER CEM SIDING O/ BLDG WRAP
3" = 1'-0"
SEAL 17 A-541
4"
FOR TYPICAL NOTES SEE DETAIL 2 A-514
6
17 A-514
CT Y R RT
CEM PLASTER SYSTEM O/ CONT BLDG WRAP
RAKE AT GABLE
Q2
A
FIBER CEMENT SOFFIT
FIBER CEM SOFFIT
2
1 1/2" = 1'-0"
Q2
ST
4"
3" = 1'-0"
WINDOW CANOPY SECTION
SHEET MEMBRANE WATERPROOFING
SHAPED 2x12 EXT TRIM FASCIA PAINT TO MATCH GUTTER
2x12 EXT TRIM FASCIA PAINT TO MATCH GUTTER
17
SINGLE PLY ROOFING O/ PLY WD DECK
1x4 NAILER
1x8 TRIM
2x8 EXT TRIM PAINT TO MATCH GUTTER
PARAPET WALL TO ROOF DECK
SINGLE PLY ROOFING O/ PLY WD DECK
PREFIN MTL FLASHING
SMW EXTEND OVER EDGE
C
SINGLE PLY ROOFING EXTEND 4" OVER EDGE
13
BATT INSULATION COMPLETELY FILL CAVITY FRMG SPACE TYP AT CLERESTORY
1x4 NAILER
BATT INSULATION COMPLETELY FILL CAVITY FRMG SPACE TYP AT CLERESTORY
GALV PREFIN MTL FLASHING
SHEET MEMBRANE WATERPROOFING
SNAP ON CLIP
SINGLE PLY ROOFING O/ PLY WD DECK
RUN 6" STRIP OF SMW OVER GALV MTL FLASHING O/ 2'-0" SMW PER ROOF PLAN
NOTE: SEE STRUCTURAL FOR WELDING REQUIREMENTS OF HSS MEMBERS AND ANGLES, DIM, PLATES
EAVE AT COVERED BLDG WALKWAY
SHEET MEMBRANE WATERPROOFING
SHEET MEMBRANE WATER PROOFING PER ROOF PLAN
CONSULTANT
IA
9 A-512
6"
1
19 AT FIBER A-514 CEM SIDING
4'-6", TYP.
FIBER CEM SOFFIT BOARD VENTED PER REFLECTED CEILING PLAN
SINGLE FASCIA FLASHING
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
N
3x4 SHAPED SOFFIT NAILER
TYPE 2 MTL ROOF PANEL SYS
19 A-514
1"
FIBER CEMENT SOFFIT 2x4 SOFFT NAILER @ 12" OC
07/03/2019
16 A-514
9
SHAPED 2x12 EXT TRIM FASCIA PAINT TO MATCH GUTTER
D
✔
ANGLE, SEE STRUCT
AT FIBER AT CEM PLAS CEM SIDING
CEMENT PLASTER SYS O/ BLDG WRAP
SINGLE PLY ROOFING O/ GYP COVER BD
GALV MTL DRIP EDGE FLASHING O/ 2'-0" SMW PER ROOF PLANS 2x12 EXT TRIM FASCIA PAINT TO MATCH GUTTER 2"
ACS
✔
R
4 7/8"
1x8 TRIM PAINT TO MATCH FASCIA
PREFINISHED GUTTER, MATCH ROOFING FINISH
SINGLE PLY ROOFING UP PARAPET O/ PLY WD
4"
RUN 6" STRIP OF SMW O/ GALV MTL DRIP FLASHING O/ 2'-0" SMW
FLS
HSS BEAM, SEE STRUCT
2" 1 1/2"
GALV PREFIN MTL FLASHING O/ FELT PAPER O/ SMW
✔
DATE:
2x RAFTER SEE STRUCT 2x BLKG PER STRUCT
SMW EXTEND OVER EDGE IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
REVIEWED FOR
SHINGLE ROOFING O/ ROOF FELT PAPER O/ SHEET MEMBRANE WATERPROOFING O/ PLY WD DECK
LI J ON C
SHINGLE ROOFING O/ ROOF FELT PAPER O/ SMW O/ PLY WD DECK
INC:
4"
0 1/4" 1/2"
1"
APP. 02-117123
13 A-541
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
4" TO HDR
GALV MTL DRIP FLASHING AND COUNTER FLASHING PAINT TO MATCH CEM PLAST COLOR
2x SHAPED NAILER
LAP ROOF FELT PAPER O/ SMW O/ BLDG WRAP BEHIND FLASHING
FRAMING, SEE STRUCT GALV PREFIN WALL FLASHING VENTED FIBER CEMENT SOFFIT
2x4 SOFFIT NAILER @ 12" OC
HSS PER A-542
FIBER CEM SOFFIT SIDING
ANGLE PER STRUCT PAINT TO MATCH BEAM
4x8 RESTORED MILL TIMBER BEYOND
SEE WINDOW SCHED
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
HSS BEAM, SEE STRUCT PAINT COLOR TO MATCH CEMENT PLASTER FINISH 2
AGENCY
SHINGLE ROOFING AT MECH WELL WALL 3" = 1'-0"
Q2
7
CEM PLAS SYS O/ CONT BLDG WRAP
MECH LOUVER
MECHANICAL TOWER PARAPET CAP
15
1 1/2" = 1'-0"
COVERED WALKWAY AT CLASSROOM
19
1 1/2" = 1'-0"
Q2
SINGLE PLY ROOFING O/ SHEET MEMBRANE WATERPROOFING O/ PLY WD DECK
PREFIN MTL FLASHING
3/4"
SNAP ON CLIP
CEM PLAST SYS O/ BLDG WRAP O/ PLY WD
1x8 TRIM PAINT TO MATCH FASCIA
1'-0"
WEEP SCREED
FRAMING, SEE STRUCT
2x8 TRIM 2x12 EXT TRIM RAKE PAINT TO MATCH GUTTER
FRAMING, SEE STRUCT
1'-0"
TYP GALV MTL FLASHING
1'-0"
1/4"
FIBER CEM SIDING SHEET MEMBRANE WATERPROOFING O/ BLDG WRAP LAP O/ SHT MEMB FROM BELOW (DASHED)
6"
RAKE FRMG BEYOND MECH WELL SEE DETAIL
3/4"
TYP GALV MTL FLASHING
CEMENT PLASTER SIDING
SHEET MEMBRANE WATERPROOFING O/ RIGID INSUL O/ PLY WD DECK SINGLE PLY ROOFING
SINGLE PLY COATED METAL FLASHING
Q2
1/4"
GALV MTL DRIP AND COUNTER FLASHING PAINT TO MATCH CEM PLAS COLOR
2x SHAPED NAILER
1 1/2" = 1'-0"
1'-0"
SHEET MEMBRANE WATERPROOFING O/ BLDG WRAP LAP O/ SHT MEMB FROM BELOW (DASHED)
GALV MTL FLASHING WELD CORNERS PAINT TO MATCH BEAM
7 1/2" MAX.
SMW AND FELT PAPER UNDERLAYMENT EXTEND OVER EDGE
6 A-514
WINDOW CANOPY SECTION SECTION AT FIBER CEM SIDING
Q2
3/4"
FOR TYPICAL NOTES, SEE DETAIL
SHINGLE ROOFING O/ SHEET MEMBRANE WATER PROOFING O/ ROOF FELT PAPER O/ PLY WD DECK
4"
GALV MTL FLASHING WELD CORNERS PAINT TO MATCH BEAM
HSS BEAM SEE STRUCT
HSS BEAM SEE STRUCT FIBER CEM SOFFIT SIDING
VENTED FIBER CEMENT SOFFIT
LOWER BEAM PER STUCT
SHAPED 2x12 EXT TRIM FASCIA PAINT TO MATCH GUTTER
FOR TYPICAL NOTE SEE DETAIL
5 A-514
SINGLE PLY ROOFING UP PARAPET O/ PLY WD
PLASTER WRAPPED COLUMN
CONT SEALANT AND BACKEROD ALL AROUND
SINGLE PLY ROOFING UP PARAPET O/ PLY WD
1/2"
BATT INSULATION COMPLETELY FILL CAVITY FRMG SPACE TYP AT CLERESTORY
SNAP ON CLIP
DETAILS - ROOF
ALIGN BOT OF BEAM W/ BOT OF WIND HEADER
CEM PLAS SYS TO CONT/ BLDG WRAP
1"
TITLE
CONT SEALANT AND BACKEROD ALL AROUND
ALIGN BOT OF BEAM W/ BOT OF WIND HEADER
SHEET MEMBRANE WATERPROOFING O/ BLDG WRAP LAP UNDER SHT MEMB FROM ABOVE
6"
A
6"
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
SNAP ON CLIP PREFIN MTL FLASHING
MANAGEMENT
CEM PLAS SYS TO CONT/ BLDG WRAP
3/4"
1 3/8"
SINGLE PLY ROOFING UP PARAPET O/ PLY WD
SINGLE-PLY ROOFING UP PARAPET O/ PLY WOOD
3
ALIGN BOTTOM OF BEAM W/ BOTTOM OF WINDOW HEADER CONCEALED PLATE TO RECEIVE RUST RESISTANT PAINT
SHAPED 2x12 EXT TRIM FASCIA PAINT TO MATCH GUTTER
6"
SHINGLE ROOFING O/ SHEET MEMBRANE WATER PROOFING O/ ROOF FELT PAPER O/ PLY WD DECK
6"
B
1/2"
5/8" GYP BD TYPE 'X'
PREFIN MTL FLASHING
1"
SHEET MEMBRANE WATERPROOFING O/ BLDG WRAP LAP UNDER SHT MEMB FROM ABOVE
5/15/2019 3:48:32 PM
BATT INSUL
4
RAKE AT COVERED BLDG WALKWAY
8
1 1/2" = 1'-0"
Q2
MECHANICAL TOWER PARAPET CAP
12 RAKE FLASHING AT CLERESTORY
1 1/2" = 1'-0"
1 1/2" = 1'-0"
Q2
Q2
16
WATERPROOFING AT CANOPY BEAM AT CEMENT PLASTER
20
1 1/2" = 1'-0"
Q2
SHEET
WATERPROOFING AT CANOPY BEAM AT FIBER CEM SIDING
A-514
1 1/2" = 1'-0"
Q2
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
8 A-521
NOTE: FOR TYP WALL HEAD TJI INTERSECTION, SEE
8 A-521
DATE:
(2) 16D END NAILS OR (3) 8D TOE NAILS EA END AT EA BLKG, TYP
8 A-521
BATT INSULATION
WEB STIFFENER STIFFENER/ PER STRUCT BLK'G PER STRUCT
WEB STIFFENER PER STRUCT
TJI, SEE STRUCT
TJI, SEE FRAMING STRUCT PER STRUCT
TJI, SEE STRUCT
6" C
PER STRUCT TOP PLATE PER STRUCT
1 A-551 1 A-551 RC @ WALL TYPE 2C THIS SIDE
1 LAYER 5/8" GYP. BOARD EACH SIDE OF STUDS TO PLYWOOD DECK ABOVE
WOOD STUD FRAMING SEE STRUCT DWGS FOR SIZE AND SPACING
PLYWOOD SHEATHING SEE STRUCT DWGS
1 LAYER 5/8" GYP BOARD EACH SIDE OF STUDS
2x WOOD STUD FRAMING WOOD STUD FRAMING SEE STRUCT DWGS FOR SIZE AND SPACING
1" CLR
NOTE: AT STORAGE & FIRE RISER ROOM RUN GYP BD ONLY ONE SIDE TO CONT UNDERSIDE OF ROOF DECK ABOVE
SUSPENDED ACOUSTICAL CEILING SYSTEM
1 A-551
2x6 WOOD STUD FRAMING @ 16" OC
FOR ALL OTHER ROOMS REQUIRING SOUND CONTROL SEE 8 A-521
4X6 FLAT BLKG
B
(2) 16D TOE NAILS EA END OF BLKG OPPOSITE FRAMING CLIP, TYP "SIMPSON" A34 EA END OF BLKG ALT TOP & BOTTOM, TYP
B
ELEVATION
WOOD STUDS @ 16" OC, SEE PLAN
1 A-551
PLAN
2x6 WOOD STUD FRAMING @ 16" OC
1 LAYER 5/8" GYP BOARD EACH SIDE OF STUDS TO PLYWOOD DECK ABOVE
ATTACH ACCESSORIES TO BACKING WITH #12 WOOD SCREWS, MIN
1 LAYER 5/8" GYP BOARD EACH SIDE OF STUDS TO PLYWOOD DECK ABOVE
USE FOR: TOILET & BATH ACCESSORIES UNO, DOOR STOPS, DOOR HOLDERS, CABINETS, DISPLAY CABINETS, TOILET PARTITIONS UNO
2x WOOD STUD FRAMING @ 16" OC
CONC SLAB
CONC CURB (DASHED) WHERE OCCURS PER PLANS
CONC CURB
CONC CURB
D A RCH SE I E N A N McM TE H U T A
C23603
ELEVATION 3
C
WOOD STUDS @ 16" OC, SEE PLAN
PARTITION WALL
T
A
11 A-521
ACOUSTICAL SEALANT @ WALLS WITH ACOUSTIC INSULATION
SEAL
ST
ACOUSTICAL SEALANT @ WALLS WITH ACOUSTIC INSULATION
ACOUSTICAL SEALANT @ WALLS WITH ACOUSTIC INSULATION
4X6 FLAT BLKG
C
PROVIDE ADDL STUD (SAME SIZE AS WALL STUDS) AT EA END OF BACKING "SIMPSON" A34 TOP & BOTTOM AT EA END, TYP
CT Y R RT
ACOUSTIC BATT INSULATION
RUBBER BASE SEE FIN SCHED
FASTENER SEE STRUCT DWGS
FOR ALL OTHER ROOMS REQUIRING SOUND CONTROL SEE 8 A-521
2x4 BLKG W/ 2-16d BOTH ENDS TO TIMBER STRAND BLKG. SEE STRUCT FOR TJI TYP BLOCKING
2x BLKG W/ FRMG CLIP PER STRUCT
TYPE B PLYWOOD SHEATHING SEE STRUCT DWGS
RUBBER BASE BASE PER SPECIFICATIONS
NOTE: AT STORAGE & FIRE RISER ROOM RUN GYP BD ONLY ONE SIDE TO CONT UNDERSIDE ABOVE OF ROOF DECK FRAMING ABOVE
SUSPENDED ACOUSTICAL CEILING SYSTEM
RC @ WALL TYPE 1C THIS SIDE ACOUSTIC BATT INSULATION
2x4 BLKG W/ 2-16d BOTH ENDS TO TIMBER STRAND BLKG. SEE STRUCT FOR TJI TYP BLOCKING
2x BLKG W/ FRMG CLIP PER STRUCT
R E
IA
5/8" GYP. CEILING, CEILING WHERE PER CLGOCCURS PLAN
CONSULTANT
TIMBER STRAND BLKG SEE STRUCT
6"
SLOPED SUSPENDED SUSPENDED CEILING SYSTEM CEILING SYSTEM PER CLG. PLAN
JOIST FRAMING PER STRUCT
TYPE A
LI J ON C
1 A-5511 A-551
NOTE: SEE STRUCT DWGS FOR SHEAR TRANSFER TO PLYWOOD SHEATHING AT ROOF DECK
LR
5/8" GYP. CLG PER CLG. PLAN TOP PLATE
TIMBER STRAND BLKG SEE STRUCT
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
USE FOR: MIRRORS, FLAT SIGNS, TACK BOARDS, DRY ERASE BOARDS. CHALKBOARDS, BULLETIN BOARDS, MARKER BOARDS, FRAMED ARTWORK
6"
AT FIRE RATED WALL 1 LAYER OF 5/8" TYPE 'X' GYP BOARD BATT INSULATION WRAP AROUND TJI BOTH SIDES TYPE 4B
6"
NOTE: SEE STRUCT DWGS FOR SHEAR TRANSFER TO PLYWOOD SHEATHING AT ROOF DECK
NOTE: SEE STRUCT DWGS FOR SHEAR TRANSFER TO PLYWOOD SHEATHING AT ROOF DECK
✔
PLAN ATTACH ACCESSORIES TO BACKING WITH #10 WOOD SCREWS, MIN
1" CLR
TJI, SEE ROOF STRUCT PER FRAMING STRUCT (TJI ILLUSTRATED)
SUSPENDED ACOUSTICAL CEILING SYSTEM PER CLG. PLAN
BATT INSULATION
ROOF FRAMING PER STRUCT
BATT INSULATION
D
BATT INSULATION
ACS
✔
A
ELEVATION
WOOD STUDS AT 16" OC, SEE PLAN
FLS
N
8 A-521
NOTE: FOR TYP WALL HEAD TJI INTERSECTION, SEE
EN . 08 - 3 1 - 1 O F OF CAL I 9
NOTE: FOR TYP WALL HEAD TJI INTERSECTION, SEE
SS
✔
R
0 1/4" 1/2" IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
NOTE: FOR TYP WALL HEAD TJI INTERSECTION, SEE
REVIEWED FOR
2X6 FLAT BLKG
A
INC:
STC 34
11 A-521
C
1
CONC CURB (DASHED) WHERE OCCURS PER PLANS
3A
STC 34
PARTITION / SHEAR WALL
PARTITION / SHEAR WALL
2
STC 36
1B
11 A-521
USE 2x6 WOOD STUDS @ 16" OC
3B
2B
3C
CONC CURB (DASHED) WHERE OCCURS PER PLANS
USE 2x8 WOOD STUDS @ 16" OC
USE 1/2" DBL LEG RC CHANNEL RUN HORIZONTALLY, SPACE VERT @ 24" OC MAX
STC 44
TEHAMA CENTER STUDENT SERVICES
PLAN
USE FOR: HANDRAILS, GRAB BARS, SHOWER SEATS, SHELF BRACKETS, COUNTERTOP BRACKETS, URINAL SCREENS, WATER HEATER STRAPS, SINK BRACKETS
STC 34
4A
PROJECT
ATTACH ACCESSORIES TO BACKING WITH #14 OR 1/4" DIA WOOD SCREWS, MIN
PARTITION WALL
STC 34
USE TILE BACKER BOARD AT RESTROOM SIDE, WALL WITH CURB
STC 36
11 A-521
4
USE TILE BACKER BOARD AT RESTROOM SIDE, WALL WITH CURB
STC 44
USE TILE BACKER BOARD AT RESTROOM SIDE, WALL WITH CURB
CONC CURB (DASHED) WHERE OCCURS PER PLANS
770 DIAMOND AVE RED BLUFF, CA 96080
TYPE C
STC 34 STC 34
1C
2C
PARTITION / SHEAR WALL WITH 1/2" DBL LEG RC CHANNEL RUN HORIZONTALLY, SPACE VERT. @ 24" OC MAX
PARTITION / SHEAR WALL WITH 1/2" DBL LEG RC CHANNEL RUN HORIZONTALLY, SPACE VERT. @ 24" OC MAX
3D
4B
USE 2x8 TILE BACKER BOARD AT RESTROOM SIDE, WALL WITH CURB
USE TILE BACKER BOARD AT RESTROOM SIDE, OPP SIDE WITH 1/2" DBL LEG RC CHANNEL RUN HORIZONTALLY, SPACE VERT @ 24" OC MAX WITH CURB
NOTES: 1. DO NOT CUT OR NOTCH STUDS TO INSTALL BACKING 2. VERIFY LENGTH, HEIGHT, QUANTITY & LOCATION OF BACKING WITH ARCHITECTURAL DETAILS AND ACCESSORY MANUFACTURER 3. EXTEND BACKING TO FIRST STUD PAST END OF ACCESSORY
STC 34 STC 36
2
STC 50
SHEAR WALL - HEAD PARALLEL SHEAR WALL TO ROOF FRMG
6
1 1/2" = 1'-0"
STC 34
SHEAR WALL - HEAD SHEAR WALL PERPENDICULAR TO ROOF FRMG 1 1/2" = 1'-0"
Q2
10
PARTITION WALL FRMG AT TJI ROOF ROOF FRMG FRMG
14
1 1/2" = 1'-0"
Q2
PARTITION WALL FRMG AT TJI ROOF FRMG
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
18 TYP WOOD STUD WALL BACKING
1 1/2" = 1'-0"
3/4" = 1'-0"
Q2
Q2
ISSUED
PLYWD SHTHG WO
BATT INSULATION
4" WALL
6" WALL
8" WALL
10" WALL
4" WALL
6" WALL
8" WALL
10" WALL
4x8
6x6
6x8 FLAT
6x10 FLAT
2x4
2x6
2x8
2x10
8'
4x10
6x8
"
"
"
"
(2) 2x4
(2) 2x6
(2) 2x8
(2) 2x10
10'
4x12
6x10
"
"
"
"
(3) 2x4
(3) 2x6
(3) 2x8
(3) 2x10
ACOUSTICAL INSULATION
HEADER SCHEDULE
>10'
STUD WALL FRAMING SEE STRUCT
SILL SCHEDULE
SEE PLAN
SEE STRUCT
BATT INSULATION
MAX SPAN "L" 4'
ROOF JOIST 5/8" GYP BOARD
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
SEE PLAN "SIMPSON" A34 CLIPS
.
5/8" GYP BD TYPE 'X'
MARK
1" CLR
BASE PER FIN SCHED
TJI SEE STRUCT
CONC CURB PER PLAN
DEPRESSED CONCRETE SLAB WHERE OCCURS 6"
2x4 CONT W/ 2-16d BOTH ENDS TO TIMBER STRAND BLKG. SEE STRUCT FOR TJI TYP BLKG
SEE STRUCT FOR FRMG CLIP & FASTENERS
ACOUSTIC INSULATION
5 CONT GALV ANGLE BOTH SIDES A-522
FLOOR FIN PER SCHED
POST AT HOLDOWN TO BE CONT TO TOP PLS FRAMING ANCHOR T&B
2x BLKG
5/8" GYP BD TYPE 'X' EACH SIDE (OR) TILE BACKER BD PER FIN SCHED
2x DBL TOP PLATE
DBL CRIPPLE & KING STUDS EA SIDE OF OPNG WHERE "L" EXCEEDS 6'-0"
"L"
WINDOW OPNG SHOWN DASHED
POST WHERE OCCURS, SEE PLAN
DOOR OPNG
2x WD STUDS @ 24" OC
(2) 16D EA END, EA 2x
SILL PER SCHEDULE
FRAMING ANCHOR T&B OF EA KING STUD WHERE "L" EXCEEDS 4'-0"
TJI SEE STRUCT
6" CLR
BASE PER FINISH SCHED
CONC CURB SEE STRUCT
1/2" TYP.
6"
2x TOP PLATE PER STRUCT
DEPRESSED CONC SLAB WHERE OCCURS
CHASE WALL WITH CURB STC 44
2x WD SILL PLATE SEE STRUCT BASE AT NONSTRUCT WALL TYP
5/8" GYP BD
CONT GALV 5 ANGLE A-522 BOTH SIDES
FLR FIN PER SCHED
PARALLEL TO BEAM
STUD WALL
"SIMPSON" DTC AT EA JOIST/BLKG (SLOTTED LEG VERT) PLACE NAILS IN SLOT AT 1/2" FROM BOTTOM OF SLOT DRIVE NAILS IN SLOT TO ALLOW 1/16" GAP BETWEEN NAIL HEAD & CLIP
CONCRETE SLAB
ALT CONNECTION PARALLEL TO BEAM TITLE 1/4" CLR MAX FROM BLOCK TO JOIST AT CLIP
A
DETAILS - INTERIOR
CHASE WALL NO CURB 1" CLR.
SUSPENDED ACOUSTICAL CEILING SYSTEM
STC 44
1 A-551
4
#10 PAN HD WOOD SCREW EA SIDE - DO NOT DRIVE TIGHT
1 1/2" MIN
2X BLKG
RUBBER BASE, SEE FINISH SCHEDULE ACOUSTIC SEALANT AT WALLS W/ ACOUSTIC INSULATION
16 GA SLOTTED TRACK W/ WIDTH TO MATCH STUD DEPTH (ICC ESR 1042) W/ # 10 WOOD SCREWS @ 16" OC TO BEAM 1" MIN
CHASE WALL
8
1 1/2" = 1'-0"
Q2
(E)JOIST 2X BLKG @ 24" OC 12" LONG 2X BLOCK W/ (2) 16D TO PL
TYP WALL HEAD FRMG TO TJI @ CLASSROOMS & OFFICES
12
1 1/2" = 1'-0"
Q2
PLUMBED FURRED WALL CONC CURB
16
3" = 1'-0"
Q2
BASE WALL FRMG AT NON-BEARING WALL
PARALLEL TO JOISTS
20
3" = 1'-0"
Q2
1" CLR
5
WALL FINISH PER SCHED
COVED CERAMIC TILE BASE, SLOPE TO DRAIN
"SIMPSON" DTC AT EA STUD (SLOTTED LEG VERT) PLACE NAILS IN SLOT AT 1/2" FROM BOTTOM OF SLOT DRIVE NAILS IN SLOT TO ALLOW 1/16" GAP BETWEEN NAIL HEAD & CLIP
BM
WALL TYPE PER PLANS
S-_061010_T031A 140127. Q2
1/2" = 1'-0"
ACOUSTICAL INSULATION SHEAR WALL PER STRUCT
5/8" GYP BD
19
3/4" CL CLR
5/8" GYP BD TYPE 'X' EACH SIDE OR TILE BACKER BOARD (SEE FINISH SCHEDULE PLUMBED FURRED WALL
SEE STRUCT
A
Q2
ACOUSTIC INSULATION WHERE OCCURS
WEB STIFFENER PER STRUCT
CONC CURB & SLAB SEE STRUCT
3" = 1'-0"
2 A-521
SIM BATT INSULATION
COVED CERAMIC TILE BASE, SLOPE TO DRAIN
017294 ?00.00.00? LIONAKIS 2017
TYP FRAMING AT OPENINGS
1 1/4"
NOTE: FOR TYP WALL HEAD TJI INTERSECTION SEE
CERAMIC TILE
HEAD WALL FRMG AT NON-BEARING WALL
1" CLR CL
11 A-521
15
3" = 1'-0"
TILE BACKER BOARD
1'-6" TYP UNO
DOUBLE WD STUD PLUMBING WALL
WD STUD WALL FRMG AT CONC CURB Q2
ACOUSTIC BATT INSULATION
TILE BACKER BOARD
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AT CURB
2" MAX.
11
1 A-551
5/8" GYP BOARD CEILING
MANAGEMENT
AGENCY
SUSPENDED ACOUSTICAL CEILING SYSTEM
JOIST FRAMING PER STRUCT
5C
5/15/2019 3:48:34 PM
HEADER PER SCHEDULE
CONDITION AT HOLDOWN
STUD WALL
(3) 16D EA END
2x TOP PLATE W/ BLKG & FRMG CLIP PER STRUCT
6"
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
2x BLKG W/ FRMG CLIP PER STRUCT
5/8" GYP BD
1/2" TYP.
CLR
TJI BLOCKING, SEE STRUCT
B
1" CLR
TJI, SEE STRUCT
1/2" GAP @ NON BEARING WALLS
WEB STIFFENER PER STRUCT
TIMBER STRAND BLKG SEE STRUCT
WHERE JOISTS ARE 48" OC, PROVIDE DTC EA SIDE OF JOIST
A
DETAIL
PERPENDICULAR TO JOISTS
NON STRUCT WALL ANCHORAGE 3/4" = 1'-0"
SHEET
A-521
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR
ACOUSTICAL INSULATION PLYWD SHEATHING PER STRUCT
DATE:
5/8" GYP BD 5/8" GYP BD GYP BOARD WHERE OCCURS
DIM POINT
PAF @ 32" OC & 8" FROM ENDS
CONCRETE CURB AS OCCURS
1 9/16"
HANDLE SEE
18 A-522
ACS
✔
✔
07/03/2019
18 A-522
STUD FRMG/BLKG AS REQUIRED
DIM POINT
WINDOW TREATMENT PER DOOR SCHED 1" 1 9/16"
1 15/16"
FLS
DIM POINT
2"
D
SEMI-RECESSED FIRE EXTINGUISHER CABINET
2"
HOLLOW METAL FRAME
1/2"
1/2"
STUD FRMG PER STRUCT
HANDLE SEE
HOLLOW METAL FRAME
5/8"
1/2"
1/2"
PLYWOOD SHEATHING, WHERE OCCURS
5/8"
1 15/16"
ALUM CAP MOLDING
GLAZING STOP PAINT TO MATCH DOOR FRAME
.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
PLY WD SHEATHING PER STRUCT
FABRIC COVERED TACKABLE WALL PANEL SYSTEM PER INT FIN SCHED
GLAZING SET IN CONT SEALANT BED SEE SCHED
1/2" CLR WHERE GYP BOARD OCCURS (0" AT STUD WIDTHS 4" OR LESS)
ACOUSTICAL INSULATION 5/8" GYP BD
WIDTH TO FIT WALL TYPE WIDTH TO FIT WALL TYPE
SEE FLOOR PLANS AND A-521
SEE FLOOR PLANS & A-521
INTERIOR DOOR HEAD
5
3" = 1'-0"
TYP GYP BOARD ATTACHMENT AT CURB S-_092216_T008A 150807. Q2
1 1/2" = 1'-0"
Q2
INTERIOR WINDOW HEAD
13
3" = 1'-0"
17
6" = 1'-0"
Q2
1 1/2" = 1'-0"
Q2
Q2
FOR BLOCKING SEE STRUCT
SEAL D A RCH SE I E N A N McM TE H U T A
PRESSED METAL FRAME
48" AFF TO HANDLE
DIM POINT HOLLOW METAL FRAME
JAMB FRAME ANCHORS BEYOND. MIN. (2) ANCHORS EA SIDE, ANCHORED TO JAMB STUD(S) W/ MIN (4) #10 WOOD SCREWS, (2) EA SIDE OF EA ANCHOR, MIN 11/2" EMBED INTO JAMB STUD(S) PER SPECIFICATIONS
JAMB FRAME ANCHORS BEYOND
DOOR SEE SCHED
DOOR - SEE SCHED
WD STUD FRMG & BLKG GLAZING STOP PAINT TO MATCH DOOR FRAME
WIDTH TO FIT WALL TYPE
WIDTH TO FIT WALL TYPE
SEE FLOOR PLANS & A-521
SEE FLOOR PLANS & A-521
SEE FLOOR PLANS & A-521
3" = 1'-0"
Q2
6
INTERIOR WINDOW DOOR SIDELITE JAMB
10
3" = 1'-0"
LI J ON C
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
ACOUSTICAL INSULATION 5/8" GYP BD
3'-0" AFF
CLIENT
GYP BD WALL FINISH
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
INT WINDOW JAMB (SILL SIM)
14
3" = 1'-0"
Q2
MARKERBOARD
18
6" = 1'-0"
Q2
FLAT BLKG TYPE "A"
PER FLOOR PLAN & A-521
VERT HANGER PER
18 A-521
FASTEN BRACKETS TO BLKG W/ #10 FHWS SCREWS T&B @ 24" O.C. AND MAX 3" FROM EA. END (MIN EMBED 1 1/2")
5/8" GYP BD
GLAZING SET IN CONT SEALANT BED, SEE SCHED
1 A-551
SECTION AT SEMI-RECESSED CABINET - SECTION 1 1/2" = 1'-0"
Q2
WIDTH TO FIT WALL TYPE
Q2 INTERIOR/ EXTERIOR PER PLAN
16d T&B @ 12" OC
5/8"
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
WALL MOUNT BRACKET PER MANUF. MOUNT TIGHT TO WINDOW/ STOREFRONT HEAD.
PROJECTION SCREEN CASING
GLAZING STOP, PAINT TO MATCH FRAME
INTERIOR
(2) #12 SST FHWS SCREWS @ 12" OC (MAX 6" FROM ENDS) - 1" MIN EMBED INTO STRUCTURE
HOLLOW METAL FRAME
SUSPENDED ACST CLG RUNNER
6"
R E
PLY WD SHEATHING PER STRUCT
GLAZING SET IN CONT SEALANT BED SEE SCHED
WIDTH TO FIT WALL TYPE
INTERIOR DOOR JAMB
T
A
HOLLOW METAL FRAME
C23603
SEMI-RECESSED FIRE EXTINGUISHER CABINET
MARKERBOARD
IA
GLAZING STOP PAINT TO MATCH DOOR FRAME
ST
C
STUD FRMG PER STRUCT
BLOCKING AS REQUIRED
JAMB FRAME ANCHORS BEYOND. MIN. (2) ANCHORS EA SIDE, ANCHORED TO JAMB STUD(S) W/ MIN (4) #10 WOOD SCREWS, (2) EA SIDE OF EA ANCHOR, MIN 1-1/2" EMBED INTO JAMB STUD(S) PER SPECIFICATIONS
HOLLOW METAL FRAME
5/8" GYP BD
5/8" GYP BD JAMB STUDS PER STRUCT
PLYWD SHEATHING PER STRUCT
JAMB STUDS PER STRUCT
5/8" GYP BD
CT Y R RT
5/8" GYP BD
#10 FHWS W/ 1 1/2" MIN EMBED @ 16" OC W/ (OR) #12x2" SDST SCREW @ 16" OC TOP & BOT
N
5/8" GYP BD
ACOUSTICAL INSULATION
9
GLAZING SET IN CONT. SEALANT BED SEE SCHED
PLYWD SHEATHING PER STRUCT
R
ACOUSTICAL INSULATION SEE WALL TYPES A-521
2
9
SECTION AT SEMI-RECESSED CABINET - PLAN
CABINET MFR
1
GYP BD TO TACKABLE WALL PANEL TRANSITION
VERIFY PER
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
HEADER PER STRUCT CONT L3/4X1 1/2X22 GA (LLV) GALV SHEET METAL
HEADER PER STRUCT
WOOD STUD WALL, SEE PLANS
5/8" GYP BD
CABINET MFR
5/8" GYP BD 5/8" GYP BD
5/8" GYP BD PER WALL TYPE SEE FLOOR PLANS
VERIFY PER
ACOUSTICAL INSULATION
PLYWD SHEATHING PER STRUCT
✔
DIM POINT SEE RCP
WALL ANGLE PER
10"
B 3 A-551
ROLLER TUBE AND SHADE BAND ASSEMBLY (MAX 20 LBS)
5/8" GYP BD TYPE 'X" SOFFIT
DIM POINT
8'-0" AFF
CONTINOUS SELEANT BED
BOX HEADER PER STRUCT
ALUM BRACKETS PROVIDED BY MNFR
DP
BLKG TYPE "A" PAINT TO MATCH WALL FIN 1/4" "HILTI" KWIK BOLT "TZ" POST INSTALLED ANCHOR W/ 2" MIN EMBED 12" OC & 6" FROM ENDS PER ESR-1917
7
WALL FINISH @ SUSP. CLG.NG
11
3" = 1'-0"
INTERIOR HMF GLAZING SILL 0540_XXXX_DOOR & WINDOW_04
3" = 1'-0"
15
PROJECTION SCREEN WALL MOUNT
19
6" = 1'-0"
AGENCY
0520_1224_WINDOW COVERING_05
3" = 1'-0"
INTERIOR
(2) #12 SST FHWS SCREWS @ 12" OC (MAX 6" FROM ENDS) - 1" MIN EMBED INTO STRUCTURE WALL MOUNT BRACKET PER MANUF. MOUNT ABV SUSPENDED CLG
ACOUSTICAL INSULATION STUD WALL FRAMING SEE STRUCT CARPET, SEE FINISH SCHEDULE
CARPET SEE FIN SCHED
CONC FLOOR SLAB
2
VCT OR SHEET VINYL
P-LAM PER FIN SCHED O/ 3/4" MDF BD SUBSTRATE
5/8" GYP BD TYPE 'X'
CONC CURB PER STRUCT 2 1 MAX
BASE PER FINISH SCHED
1/2" TYP.
CONT GALV ANGLE BOTH SIDES
TITLE
DETAILS - INTERIOR
CLOSURE FASCIA - COLOR TO MATCH WALL / SUSPENDED CEILING
5 A-522
SHADECLOTH - SIZE TO COVER WINDOW COMPLETELY; BLOCK OUT AROUND DOORS
FLR FIN PER SCHED CL
CL
SEE CLG PLANS
ROLLER TUBE AND SHADE BAND ASSEMBLY (MAX 20 LBS) 6"
1/2" MAX
1/2".
CONCRETE
MAX
1 MAX
VCT, OR SHEET VINYL SEE FIN SCHED
BLACK RUBBER TRANSITION STRIP
OPENING HEIGHT
DOOR SEE SCHED
HEMBAR SEALED INSIDE SHADECLOTH
5/15/2019 3:48:35 PM
WINDOW/STOREFRONT PER PLAN
4
017294 ?00.00.00? LIONAKIS 2017
Q2
DOOR SEE SCHED
1 MAX
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
ROLLER SHADE - WALL MOUNTED
DOOR (WHERE OCCURS), SEE SCHEDULE
2
SHADECLOTH - SIZE TO COVER WINDOW COMPLETELY; BLOCK OUT AROUND DOORS
WINDOW/STOREFRONT PER PLAN
INTERIOR/ EXTERIOR PER PLAN
A
MANAGEMENT
HEMBAR SEALED INSIDE SHADECLOTH
PICTURE SURFACE
Q2
1/2" MAX
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
WINDOW PER SCHED
CLOSURE FASCIA - COLOR TO MATCH WALL / SUSPENDED CEILING
VCT TRANSITION
8
6" = 1'-0"
Q2
CARPET/VCT TRANSITION
12
6" = 1'-0"
Q2
TRANSITION- CARPET/CONCRETE 6" = 1'-0"
0520_0960_TRANSITION_05 Q1
16
P-LAM BASE DETAIL
20
3" = 1'-0"
Q2
ROLLER SHADE - WALL MOUNTED SUSPENDED CLG 3" = 1'-0"
0520_1224_WINDOW COVERING_05
SHEET
A-522
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
0 1/4" 1/2"
PARTITION CONFIGURATION DIAGRAMS (FOURTH CHARACTER DESIGNATOR)
PARTITION TYPE SYMBOL KEY
PARTITION TYPE GENERAL NOTES
REVIEWED FOR SS
✔
DATE:
FIRE RATING
D
E
F
G
H
J
CORE MATERIAL
PARTITION CONFIGURATION CLG TYP
VARIATION
SEE PLAN
1S4A
SINGLE GYP BD BOTH SIDES TO STRUCTURE
SINGLE GYP BD ONE SIDE TO STRUCTURE
PARTITION TO STRUCTURE SINGLE GYP BD BOTH SIDES, 6" ABOVE CEILING
PARTITION 6" ABOVE CEILING
PARTITION TO BOTTOM SIDE OF CEILING
SINGLE GYP BD BOTH SIDES, 6" ABOVE CEILING
SINGLE GYP BD BOTH SIDES TO BOTTOM SIDE OF CEILING
SINGLE GYP BD ONE SIDE 6" ABOVE CEILING
PARTITION - PARTIAL HEIGHT SINGLE GYP BD BOTH SIDES TO TOP OF PARTITION
PARTITION TO STRUCTURE DOUBLE GYP BD BOTH SIDES TO STRUCTURE
PARTITION TO STRUCTURE DOUBLE GYP BD ONE SIDE TO STRUCTURE
J
L
M ADJACENT WALL SEE PLAN
ADJACENT WALL SEE PLAN
SEE PLAN
SEE PLAN
N
P
Q
R
S
SINGLE GYP BD BOTH SIDES TO STRUCTURE
T
DESIGNATOR 0 1 2 3 4
SECOND CHARACTER
J
DESIGNATOR C D E F H M S T W Z
PARTITION FURRING TO STRUCTURE
PARTITION FURRING TO STRUCTURE
PARTITION FURRING 6" ABOVE CEILING
SINGLE GYP BD ONE SIDE TO STRUCTURE
SINGLE GYP BD ONE SIDE 6" ABOVE CEILING
SINGLE GYP BD ONE SIDE 6" ABOVE CEILING
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
1S4A S
8. GYPSUM BOARD SHALL BE FIRE RESISTANT, TYPE 'X' UNO. FIRE RATED PARTITIONS SHALL BE CONSTRUCTED PER CBC, TABLE 720.1(2).
J
CORE MATERIAL CONCRETE DETENTION WALL EXISTING FURRING - WOOD STEEL HAT CHANNELS MASONRY STEEL STUD SHAFTWALL STUD WOOD STUD STEEL ZEE CHANNELS
9. PROVIDE MOISTURE RESISTANT GYP BOARD AT PARTITIONS IN WET AREAS (FLOOR TO FINISH CEILING) INCLUDING BUT NOT LIMITED TO THE FOLLOWING ROOMS A. B. C. D. E. F. G.
TOILET ROOMS JANITOR CLOSETS OUTSIDE AIR SHAFTS MECHANICAL ROOMS DRINKING FOUNTAIN ALCOVES KITCHENS LOCKERS
PROVIDE CEMENTITIOUS BACKER BOARD AT WET AREAS SCHEDULED WITH TILE FINISH. 10. PROVIDE ACOUSTICAL TREATMENT AT PARTITIONS WITH ACOUSTIC INSULATION.
PARTITION TO STRUCTURE NO GYP BD
PARTITION 6" ABOVE CEILING NO GYP BD
PARTITION - PARTIAL HEIGHT NO GYP BD
PARTITION TO STRUCTURE
FILL STUD CAVITIES & RUN INSULATION CONTINUOUS AROUND COLUMNS & OTHER OBSTRUCTIONS TO FORM A CONTINUOUS ACOUSTIC BARRIER.
1S4A 4
J
D
F 3/4" 1 1/2" 2 1/2"
PARTITION TO STRUCTURE
SHAFT LINER ONE SIDE TO STRUCTURE
SHAFT LINER ONE SIDE TO STRUCTURE
DOUBLE GYP BD ONE SIDE TO STRUCTURE
SINGLE GYP BD ONE SIDE TO STRUCTURE
SEE ELEVATIONS
C
2"
H 3/4" 1 1/2" 2 1/2"
4" 6" 8" 10" 12" 1S4A A
CORE MATERIAL SIZE M S T 1 5/8" 2 1/2" 3 5/8" 2 1/2" 4" 4" 5 5/8" 6" 6" 7 5/8" 8" 9 5/8" 10" 12" 11 5/8"
J
DESIGNATOR A B C D E F G H J K L M P S W
1S4A
J
VARIATION MATERIAL MOISTURE RESISTANT GYP BD CEMENTITIOUS BACKER BD GYP BD, ADDITIONAL LAYER REMOVE GYP BD SOUND DAMPENING GYP BD HI-IMPACT GYP BD PLYWOOD LEAD BACKED GYP BD LAMINATED HI-IMPACT GYP BD RIGID INSULATION BULLET RESISTANT COMPOSITE PANELS WITHOUT ACOUSTIC INSULATION PARTITION SMOKE FIRE
--
-INSTALL ACOUSTICAL SEALANT AT PARTITION HEAD, SILL & JAMB TRANSITIONS, AS WELL AS AT PENETRATIONS THROUGH THE GYPSUM BOARD MEMBRANE INCLUDING PENETRATIONS AT MOUNTING FASTENERS. FIRE STOPPING REQUIREMENTS SHALL SUPERCEDE ACOUSTIC TREATMENT. GYPSUM BOARD SILL & JAMB EDGES TERMINATING AT DISSIMILAR MATERIAL (CMU, CONCRETE, METAL PANEL , ETC) SHALL ALLOW 1/4" CONTINUOUS GAP AND BE SEALED AIRTIGHT WITH AN ACOUSTIC SEALANT. THE BACK AND SIDES OF DUPLEX ELECTRICAL OUTLETS, TELEPHONE OUTLETS, CABLE TV OUTLETS, FIRE ALARM DEVICES, THERMOSTATS, ETC, SHALL BE SEALED WITH FIRE STOP PUTTY PADS AS SPECIFIED FOR FIRE RATED ASSEMBLIES. ELSEWHERE, BACK-TO-BACK OUTLET BOXES TO BE SEPARATED BY ONE EMPTY STUD SPACE AND A MINIMUM OF 16 INCHES.
SEAL D A RCH SE I E N A N McM TE H U T A
C23603 T
A
FIFTH CHARACTER
3 1/2" 5 1/2" 7 1/4" 9 1/4" 11 1/4"
Z 7/8" 1 1/2"
ST
SEE PARTITION CONFIGURATION DIAGRAMS AT LEFT
A. INSTALL ACOUSTIC BATT INSULATION, FULL WIDTH, DEPTH, AND HEIGHT. W
R E
11. PARTITIONS INDICATED AS FIRE OR SMOKE RATED FORM A SEPARATION THAT SHALL BE CONTINUOUS FROM FLOOR TO STRUCTURE ABOVE WITH NO BREAKS AT CONCEALED SPACES, COLUMNS, TRANSITIONS OR OTHER OBSTRUCTIONS. 12. PENETRATIONS THROUGH RATED PARTITIONS SHALL BE SEALED WITH UL LISTED FIRE/SMOKE STOP ASSEMBLY. 13. SEE PARTITION PRIORITY LEGEND FOR PRIORITIZATION OF INTERSECTING PARTITIONS.
CT Y R RT
DESIGNATOR 1 2 3 4 6 8 10 12
FOURTH CHARACTER
C
7. IN CASES WHERE TWO DIFFERENT CEILING HEIGHTS ABUT PARTITIONS, THE PARTITION SHALL EXTEND ABOVE THE HIGHEST CEILING INDICATED.
SEE PLAN
SIZES
DOUBLE GYP BD BOTH SIDES TO STRUCTURE
11S4A
FIRE RATING NON-RATED 1 HR 2 HR 3 HR 4 HR
THIRD CHARACTER PARTITION TO STRUCTURE
SEE PLANS FOR STRUCTURE ABOVE NOTED IN PARTITION CONFIGURATION DIAGRAMS.
5. THE PARTITION TYPE ABOVE OR BELOW ANY OPENING IS TO BE THE SAME AS THAT SCHEDULED FOR EITHER SIDE OF THE OPENING, UNO.
PARTITION SYMBOL DESIGNATORS
ADJACENT WALL SEE PLAN
SEE PLAN
4.
6. DIFFERING PARTITION TYPES SHALL ALIGN SO THAT PARTITION FINISH PLANES CONTINUE UNBROKEN WITHIN AND/OR ACROSS SPACES.
FIRST CHARACTER
K
EXAMPLE GIVEN: REFERS TO A PARTITION THAT IS 1 HOUR, STEEL STUD, 4", FULL HEIGHT TO DECK, GYP BD BOTH SIDES WITH LAMINATED HI-IMPACT GYP BD
PARTITION TO STRUCTURE
SINGLE GYP BD ONE SIDE TO STRUCTURE
SEE ELEVATIONS
3. PARTITION TYPES AS NOTED BY THE SYMBOL CONTINUE BETWEEN ROOM/SPACE CORNERS OR ANY INTERSECTING PARTITION.
IA
D
PARTITION TO STRUCTURE
07/03/2019
N
PARTITION TO STRUCTURE
✔
2. THE CONSTRUCTION OF EXTERIOR WALLS ARE SHOWN ON WALL SECTIONS & CORRESPONDING DETAILS. PARTITION SYMBOLS ARE ONLY USED TO SHOW INTERIOR CONDITIONS, INCLUDING INTERIOR FURRING OF EXTERIOR WALLS.
CORE SIZE
EN . 08 - 3 1 - 1 O F OF CAL I 9
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
STRUCT ABOVE TYP
ACS
✔
R
C
FLS
1. REFER TO THE FLOOR PLANS FOR PARTITION TYPE SYMBOLS. A PARTITION TYPE IS INDICATED BY A SYMBOL CONTAINING THE PARTITION IDENTIFICATION WHICH REFERS TO A SPECIFIC ASSEMBLY INDICATED ON THIS SHEET.
LI J ON C
STANDARD PARTITION CONFIGURATIONS A B
INC:
PROJECT
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
PARTITION TYPE SHEET NOTES
ISSUED
MARK 2.
SHAFT WALL STUDS ARE 20 GAUGE SPACED AT 24" OC, UNO.
3.
WOOD STUDS ARE 2X SPACED @ 16" OC, UNO.
4.
PARTITIONS NOT IDENTIFIED WITH A SYMBOL ON PLANS SHALL BE:
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
0W4A A
5. TYPICAL PARTITIONS AROUND INTERIOR COLUMNS, UNO. 0W2L
B
MANAGEMENT
5/15/2019 3:48:36 PM
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 ?00.00.00? LIONAKIS 2017
AGENCY
PARTITION PRIORITY LEGEND DOOR FRAME (AS APPLICABLE)
LOWER PRIORITY PARTITION HIGHER PRIORITY PARTITION
HIGHER PRIORITY PARTITION
A
HIGHER PRIORITY PARTITION TITLE
LOWER PRIORITY PARTITION
PARTITION TYPES & SCHEDULE
PARTITION PRIORITY LEGEND FOUR HOUR FIRE AND/OR SMOKE PARTITION THREE HOUR FIRE AND/OR SMOKE PARTITION TWO HOUR FIRE AND/OR SMOKE PARTITION TWO HOUR FIRE PARTITION TWO HOUR SHAFTWALL ONE HOUR FIRE AND/OR SMOKE PARTITION ONE HOUR FIRE PARTITION NON-RATED PARTITION
PRIORITY 1 (HIGHEST) PRIORITY 2 PRIORITY 3 PRIORITY 4 PRIORITY 5 PRIORITY 6 PRIORITY 7 (LOWEST)
NOTE: 1. ALL PARTITIONS MAY NOT BE USED, SEE PLANS. 2. PARTITIONS WITH HIGHER ASSIGNED PRIORITY SHALL BE CONTINUOUS THROUGH INTERSECTIONS.
SHEET
A-531
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
INC:
1 1/2"
WINDOW TREATMENT PER WIND SCHED SEE A-621
SHIM AS REQ W/SEALANT BACKER ROD
4 1/2"
4 1/2"
INSULATED GLASS
INT
ALUMINUM FRAMED SYSTEM
EXT.
ALUMINUM FRAMED SYSTEM
5
3" = 1'-0"
STOREFRONT DOOR TRANSOM
Q1
5/8" GYP BD TYPE 'X'
5/8" GYP BD TYPE 'X'
LINE OF GYP BD WALL BELOW
WD STUD FRMG PER STRUCT
1 FOR ADDL INFO A-542
EXT.
STOREFRONT WINDOW HEADER SIDING 3" = 1'-0"
Q1
JAMB POSTS PER STRUCT
INSULATED GLASS ALUMINUM FRAMED SYSTEM
17
INT.
SEE DTL
2 FOR ADDL INFO A-542
STOREFRONT WINDOW HEADER PLASTER 3" = 1'-0"
Q1
Q1
5/8" TYPE 'X' GYP BD
5/8" GYP BD
5/8" GYP BD
5/8" GYP BD
JAMB STUDS PER STRUCT
CORNER BEAD TYP
CORNER BEAD TYP
CORNER BEAD TYP
ALUMINUM FRAMED SYSTEM
JAMB STUDS PER STRUCT
JAMB STUDS PER STRUCT
ATTACHMENTPER PER ATTACHMENT STOREFRONTMANUF. MANUF.MIN STOREFRONT 1-1/2" EDGE DISTANCE, TYP.
ATTACHMENTPER PER ATTACHMENT STOREFRONTMANUF. STOREFRONT MANUF. MIN 1-1/2" EDGE DISTANCE, TYP.
ATTACHMENT ATTACHMENT PER PER STOREFRONT STOREFRONT MANUF. MIN 1-1/2" EDGE MANUF. DISTANCE, TYP.
4 1/2"
1" INSULATED CLEAR ANODIZED INFILL PNL
EXTEND BUILDING WRAP AROUND OPENING
JAMB STUDS PER STRUCT
C23603 ATTACHMENT ATTACHMENTPER PER STOREFRONT STOREFRONTMANUF. MANUF. MIN 1-1/2" EDGE DISTANCE, TYP.
INSULATED GLAZING
INSULATED GLAZING
ALUM BRAKESHAPE FIN TO MATCH ADJACENT ALUM FRAMED SYSTEM
2
SHIM AS REQ. W/ SEALANT BACKER ROD 17 A-511
9 A-511
SHIM AS REQ. W/SEALANT BACKER ROD
SEE DTL
PLASTER CASING J-BEAD MOLDING
SHIM AS REQ. SEALANT BACKER ROD
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
2"
ALUMINUM J-MOLDING
1 A-542
3/16"
FIBER CEMENT SIDING O/ (2) LAYERS BLDG 9 WRAP A-511
6
3" = 1'-0"
STOREFRONT DOOR JAMB PLASTER
ALUMINUM J-MOLDING
SEE DTL
14
3" = 1'-0"
Q1
5/8" GYP BD
4 1/2"
4 1/2"
CL
SHIM AS REQ. W/SEALANT BACKER ROD
LINE OF SILL BELOW
ALUMINUM FRAMED SYSTEM
WINDOW TREATMENT PER WIND SCHED SEE A-621
SST #14 WD SCREWS ATTACHMENT PER @ 12" OC & 6" FROM STOREFRONT MANUF. ENDS TYPEDGE MIN 1-1/2" DISTANCE, TYP.
SST #14 WD SCREWS @12" OC MAX & 6" FROM ENDS TYP
COMPRESSED NEOPRENE PAD W/ ACOUSTICAL SEALANT EACH SIDE
DOOR STOP
2 PIECE ALUM METAL EDGE TRIM PAINT TO MATCH ADJACENT WALL FINISH
INSULATED GLAZING ALUMINUM FRAMED SYSTEM
DOOR - SEE SCHEDULE
2"
9 A-511
SHIM AS REQ, SEALANT BACKER ROD
ALUM BRAKESHAPE TO MATCH ADJACENT ALUM FRAMED SYSTEM
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
GALV DRIP SILL PAN FLASHING PAINT TO MATCH ADJACENT FRAME
5/8" GYP TYPE 'X' FIN PER INT ELEV
SHIM AS REQ. W/ SEALANT BACKER ROD
ALUM J-MOLDING
3" = 1'-0"
3" = 1'-0"
ALUMINUM FRAMED SYSTEM
2x3 FRMG FILLER
INSULATED GLAZING
ALUMINUM FRAMED GLAZING SYSTEM
2"
WD STUD FRMG PER STRUCT JAMB POSTS PER STRUCT
4
THERMAL INSUL MANAGEMENT
PLY WD SHEATHING PER STRL
STOREFRONT SILL - SIDING
19
3" = 1'-0"
STOREFRONT SILL - PLASTER 3" = 1'-0"
Q1
4 1/2"
CONCRETE SIDEWALK SLOPE PER CIVIL
ANOD. ALUMINUM FLASHING, SET IN CONT BED OF MASTIC ON SLAB, TYP.
TYP EDGE OF BLDG SLAB
TYP EDGE OF BLDG SLAB
1/4"
CONCRETE SIDEWALK SLOPE PER CIVIL
FLR FIN PER SCHED
SHIM AS REQ W/SEALANT BACKER ROD
4 1/2"
ATTACHMENT ATTACHMENT PER PER STOREFRONT STOREFRONT MANUF. MANUF. MIN 2" EDGE DISTANCE, TYP.
ALUMINUM FRAMED SYSTEM W/ SILL PAN
ATTACHMENTPER PER ATTACHMENT STOREFRONT STOREFRONT MANUF.MIN 2" EDGE MANUF. DISTANCE, TYP.
1 7/8" 2"
TITLE
FLR FIN PER SCHED
SHIM AS REQ W/SEALANT BACKER ROD
TYP EDGE OF SLAB AT STOREFRONT
CONT BACKER ROD & SEALANT
DETAILS - DOOR AND WINDOW
TYP EDGE OF SLAB AT STOREFRONT
SHIM AS REQ SEALANT BACKER ROD
CLERESTORY STOREFRONT JAMB TO MULLION
8
3" = 1'-0"
Q1
STOREFRONT DOOR JAMB @ GLAZING
12
3" = 1'-0"
Q1
017294 ?00.00.00? LIONAKIS 2017
AGENCY
Q1
ANOD. ALUMINUM FLASHING
1" INSULATED CLEAR ANODIZED INFILL PNL (OR) INSUL GLAZ W.O.
ALUMINUM FRAMED GLAZING SYSTEM
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
SEE FLOOR PLANS
1 7/8" 2"
ALUM BRAKESHAPE FIN TO MATCH ADJACENT ALUM FRAMED SYSTEM
5/8" GYP BD TYPE 'X'
PLASTER CASING JBEAD MOLDING
SEE FLOOR PLANS
ALUMINUM FRAMED SYSTEM W/ SILL PAN
4 1/2"
ALUMINUM FRAMED SYSTEM
GALV DRIP SILL PAN FLASHING PAINT TO MATCH ADJACENT FRAME
1" INSULATED CLEAR ANODIZED INFILL PNL
2"
2"
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
SILL FRMG PER STRUCT
4 1/2"
A
ALUMINUM DOOR SEE SCHEDULE
DIM POINT
9 A-511
INSULATED GLAZING ALUM FRAMED OPERABLE GLAZING SYSTEM
DATE 01/04/2019 05/17/2019
CONT BACKER ROD & SEALANT
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG 17 WRAP A-511
ALUM FRAMED OPERABLE GLAZING SYSTEM
MARK
CORNER BEAD TYP
THERMAL INSUL
Q1
INTEGRAL DOOR STOP WITH ALUMINUM FRAMED SYSTEM
5/8" GYP BD TYPE 'X'
LINE OF GYP BD SILL BELOW
15
Q1
5/8" GYP BD TYPE 'X'
SHIM AS REQ. W/SEALANT BACKER ROD
2"
Q1
CONT BACKER ROD & SEALANT
ISSUED
ATTACHMENT PER PER ATTACHMENT STOREFRONT MANUF. STOREFRONT MANUF. MIN 1-1/2" EDGE DISTANCE, TYP.
4 1/2"
1/2"
3" = 1'-0"
WALL PERP TO STOREFRONT MULLION
11
ALUMINUM FRAMED SYSTEM W/SILL PAN
2"
7
STOREFRONT DOOR JAMB SIDING
2"
CLERESTORY JAMB FRAMING @ MULLION
3" = 1'-0"
ATTACHMENT PER PER ATTACHMENT STOREFRONT MANUF. STOREFRONT MANUF. MIN 1-1/2" EDGE DISTANCE, TYP.
5/8" GYP BD TYPE 'X'
PLASTER CASING JBEAD MOLDING
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
FOR ADDL INFO
Q1
SILL FRMG PER STRUCT
PLY WD SHEATHING PER STRL
2"
5/15/2019 3:48:37 PM
DIM POINT
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
4 1/2"
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
SEE STRUCT FOR WALL SUPPORT
2 A-542
STOREFRONT JAMB - PLASTER
CORNER BEAD TYP
GLAZING
2x6 WD STUD FRMG
PLUMBED FURRED WALL
CLIENT
Q1
ALUMINUM FRAMED SYSTEM W/SILL PAN
JAMB STUDS PER SRUCT.
18
3" = 1'-0"
Q1
5/8" TYPE 'X' GYP BD
JAMB POST PER STRUCT
3
FOR ADDL INFO
STOREFRONT JAMB - SIDING
CORNER BEAD TYP
SELF ADHERED FLASHING WRAP AROUND OPENING O/BLDG WRAP
1 A-542
770 DIAMOND AVE RED BLUFF, CA 96080
SHIM AS REQ'D W/ SEALANT BACKER ROD
17 A-511
SELF ADHERED FLASHING WRAP AROUND OPENING O/BLDG WRAP
FOR ADDL INFO
ANODIZED PANEL STOREFRONT JAMB - SIDING
10
3" = 1'-0"
Q1
2"
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
SHIM AS REQ. W/SEALANT BACKER ROD
EN . 08 - 3 1 - 1 O F OF CAL I
TEHAMA CENTER STUDENT SERVICES
ALUMINUM FRAMED SYSTEM
2"
2"
SEE DTL
CLERESTORY WINDOW JAMB TO MULLION
B
ALUMINUM FRAMED SYSTEM
1/2"
2"
SELF ADHERED FLASHING WRAP AROUND OPENING O/BLDG WRAP
DIM POINT
2"
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
ALUMINUM FRAMED SYSTEM
3/16"
DIM POINT
DOOR - SEE SCHEDULE
2X3 FRMG FILLER
ALUMINUM FRAMED SYSTEM
R E
PROJECT
C SELF ADHERED FLASHING WRAP AROUND OPENING O/BLDG WRAP
T
A
EXTEND BUILDING WRAP AROUND OPENING
D A RCH SE I E N A N McM TE H U T A
ST
DOOR STOP
SEAL
CT Y R RT
2 LAYERS OF PLY WD FILLER
13
3" = 1'-0"
SEE DTL
INT.
4 1/2"
CLERESTORY STOREFRONT HEADER
4"
CONSULTANT
IA
EXT
WINDOW TREATMENT PER WIND SCHED SEE A-621
SHIM AS REQ W/SEALANT BACKER ROD
INSULATED GLASS
4 1/2"
SHIM AS REQ W/SEALANT BACKER ROD
ALUMINUM DOOR SEE SCHEDULE
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
CORNER BEAD TYP.
GALV METAL DRIP FLASHING PAINT TO MATCH ADJACENT FRAME
4 1/2"
GALV METAL DRIP FLASHING PAINT TO MATCH ADJACENT FRAME
ATTACHMENT ATTACHMENT PER PER STOREFRONT STOREFRONT MANUF. MANUF. MIN 1-1/2" EDGE DISTANCE, TYP.
WEEP SCREED TYP AT ALL HEADERS
CORNER BEAD TYP.
GALV METAL DRIP FLASHING PAINT TO MATCH ADJACENT FRAME
07/03/2019
N
WINDOW TREATMENT PER WIND SCHED SEE A-621
✔
TYP GALV MTL DRIP FLASHING
2"
WEEP SCREED TYP AT ALL HEADERS
DIM POINT
BOX HEADER PER STRUCT
6" SELF ADHERED FLASHING O/GALV MTL DRIP FLANGE
ATTACHMENT ATTACHMENT PER PER STOREFRONT STOREFRONT MANUF. MANUF. MIN 1-1/2" EDGE DISTANCE, TYP.
ALUMINUM FRAMED SYSTEM
SELF ADHERED FLASHING WRAP AROUND OPENING O/ BLDG WRAP
9
6" SELF ADHERED FLASHING O/GALV MTL DRIP FLANGE
ATTACHMENT ATTACHMENT PER PER STOREFRONT STOREFRONT MANUF. MIN 1-1/2" EDGE MANUF. DISTANCE, TYP. CORNER BEAD TYP
5/8" GYP BD
ACS
✔
1 1/2"
TYP GALV MTL DRIP FLASHING
BOX HEADER PER STRUCT
17 A-511
1 1/8"
FLS
R
SELF ADHERED FLASHING WRAP AROUND OPENING O/ BLDG WRAP
INSULATED GLAZING
DIM POINT
1
5/8" GYP BD
DATE:
THERMAL INSULATION
LI J ON C
4 1/2"
BOX HEADER PER STRUCT
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
SS
✔
1/2"
5/8" GYP BD
6" SELF ADHERED FLASHING O/GALV MTL DRIP FLANGE
D
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
1 1/8"
1/2"
EXTERIOR CEMENT PLASTER O/ SELF-FURRING MTL LATH O/ (2) LAYERS BLDG 17 WRAP A-511 SELF ADHERED FLASHING WRAP AROUND OPENING O/ BLDG WRAP
THERMAL INSULATION
4"
THERMAL INSULATION
EXTENDED BUILDING WRAP AROUND OPENING
2"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
EXTENDED BUILDING WRAP AROUND OPENING
2"
0 1/4" 1/2"
REVIEWED FOR
EXTENDED BUILDING WRAP AROUND OPENING
STOREFRONT VERT & HORIZ MULLION
16
3" = 1'-0"
Q1
SHEET
STOREFRONT SILL @ INSULATED INFILL PNL
20
3" = 1'-0"
Q1
A-541
STOREFRONT SILL AT SLAB 3" = 1'-0"
Q1
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR
PLYWD SHEATHING PER STRUCT SEE FLOOR PLANS
SEE FLOOR PLANS
CEMENT PLASTER SYSTEM O/ BLDG WRAP
BACKER ROD W/ CONT BEAD SEALANT
GALV DRIP FLASHING PAINT TO MATCH ADJACENT FRAME
ALUM J-MOLDING D
GALV DRIP FLASHING PAINT TO MATCH ADJACENT FRAME
HEADER FRMG PER STRUCT
DOOR FRAME ANCHOR
DIM POINT
MECH WELL SIDE
GALV MTL DRIP FLASHING PAINT TO MATCH ADJACENT FRAME
FIBER CEMENT SOFFIT
DIM POINT
HEADER FRMG PER STRUCT
SINGLE PLY CLADDING HMF FRAME MULLION TYP PAINT P8
DOOR FRAME ANCHOR
DIM POINT
BACKER ROD W/ CONT SEAL BEAD
1"x1" GALV FLASHING CLIP
FIBER CEM SIDING DOOR DRIP GUARD
DOOR PER SCHED
DOOR PER SCHED HMF PER
HSS 6x6x1/2 PAINT TO MATCH LOUVER AND FRAME
3 A-542
HMF PER
HMF LOUVER AND FRAME TYP PAINT P8
3 A-542
SST #14 SDST SCREW @ 12" OC & 6" FROM ENDS TYP
3"
CL EXT.
1
TYP FLASHING AT WINDOW/DOOR HEAD
5
3" = 1'-0"
INT.
HM DOOR - HEAD AT PLASTER
9
3" = 1'-0"
Q1
LOUVER MULLION
13
3" = 1'-0"
Q1
EQ
CL
EQ
HMF PER
EQ
2"
4"
DOOR PER SCHED
HSS 6x6x1/2 PAINT TO MATCH LOUVER
EQ
TYP GALV MTL DRIP FLASHING
3" = 1'-0"
HM DOOR - JAMB AT SIDING
10
3" = 1'-0"
Q1
PROJECT
HSS 6x6x1/2 PAINT TO MATCH LOUVER
TEHAMA CENTER STUDENT SERVICES
SST #14 SDST SCREW @ 12" OC & 6" FROM ENDS TYP
770 DIAMOND AVE RED BLUFF, CA 96080
HM DOOR - JAMB AT PLASTER
14
3" = 1'-0"
Q1
LOUVER TO LOUVER JAMB AT CORNER AT MECH WELL
18
3" = 1'-0"
Q1
HMF LOUVER AND FRAME TYP. PAINT P8
EQ
CLIENT
PLAN VIEW
PLAN VIEW
6
EN . 08 - 3 1 - 1 O F OF CAL I
2"
1/2"
2
R E
DIM POINT
3 A-542
1 1/2"
TYP FLASHING AT WINDOW/DOOR HEAD
T
SINGLE PLY CLADDING
EQ
3 A-542
D A RCH SE I E N A N McM TE H U T A
A
HMF PER
1 1/8"
CONT SEALANT & BACKER ROD
1"x1" GALV FLASHING CLIP
BACKER ROD W/ CONT BEAD SEALANT
SEAL
C23603
CONT CAULKING DOOR FRAME ANCHOR
DOOR PER SCHED
SINGLE PLY ROOFING O/ PLY WD SHEATHING
EXTERIOR CEMENT PLASTER O/ SELFFURRING MTL LATH O/ (2) LAYERS BLDG WRAP
MECH WELL SIDE
JAMB FRMG PER STRUCT
DIM POINT
SEALANT & BACKER ROD
THERMAL INSULATION
ST
DOOR FRAME ANCHOR
DIM. POINT
WINDOW FRAME
17 A-511
MECH WELL SIDE
ALUM J MOLDING
CEMENT PLASTER SYS O/BLDG WRAP
PLYWD SHTHG PER STRUCT
SST #14 SDST SCREW @ 12" OC & 6" FROM ENDS TYP
5/8" GYP BD TYPE 'X'
PLASTER CASING J-BEAD MOLDING
CONT CAULKING
SELF ADHERED FLASHING WRAP AROUND OPENING O/BLDG WRAP
CEM PLAS ALUM REVEAL SEE EXT ELEV
C
JAMB FRMG PER STRUCT
CEMENT PLASTER SYSTEM O/ BLDG WRAP
2"
4"
EXTEND BLDG WRAP AROUND OPENING
HMF LOUVER AND FRAME, TYP PAINT P8
THERMAL INSULATION
PLYWD SHEATHING PER STRUCT
CT Y R RT
1"
Q1
SST #14 SDST SCREW @ 12" OC & 6" FROM ENDS TYP
FIBER CEMENT SIDING
5/8" GYP BD TYPE 'X'
3" = 1'-0"
Q1
SEE FLOOR PLANS
WOOD STUD WALL W/ INSUL AND EXT SHEATHING PER PLAN
LOUVER FRAME - HEAD
17
3" = 1'-0"
Q1
CEM PLAS CONTROL JOINT SEE EXT ELEV
GALV METAL DRIP FLASHING PAINT TO MATCH ADJACENT FRAME (AT DR/WIND HEAD)
HMF LOUVER AND FRAME TYP. PAINT P8
4"
HM DOOR - HEAD AT SIDING
CONSULTANT
2"
WINDOW FRAME
DOOR DRIP GUARD
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
IA
BACKER ROD W/ CONT BEAD SEALANT
CL
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
LOUVER FRAME - JAMB 3" = 1'-0"
Q1
Q1
MECH WELL SIDE
ISSUED
MARK SINGLE PLY ROOFING O/ PLY WD SHTHG
THREADED STUDS & HEADER PER STRUCT
HMF LOUVER AND FRAME TYP. PAINT P8
JAMB STUDS PER STRUCT SINGLE PLY ROOFING O/ PLYWD SHEATHING HMF LOUVER AND FRAME TYP PAINT P8
DOOR FRAME ANCHOR
MECH WELL SIDE
2"
1 9/16"
MIN. (2) JAMB FRAME ANCHORS EA SIDE, ANCHORED TO JAMB STUD(S) W/ MIN (4) #10 WOOD SCREWS, (2) EA SIDE OF EA ANCHOR, MIN 1-1/2" EMBED INTO JAMB STUD(S) PER SPECIFICATIONS.
7
3" = 1'-0"
2"
2"
PLAN VIEW LOUVER ACCESS DOOR FRAME HSS 5x2x1/8 PAINT P8
HMF LOUVER AND FRAME TYP. PAINT P8
4"
TYP EXT HOLLOW MTL FRAME
1/4" x 4" FULL HEIGHT ASTRAGAL, WELD TO LOUVER ACCESS DOOR FRAME
2"
2"
LOUVER ACCESS DOOR FRAME HSS 5x2x1/8 PAINT P8
INTERIOR
ACCESS DOOR AT MECH WELL HEAD
11
3" = 1'-0"
Q1
ACCESS DOOR AT MECH WELL JAMB AT STRIKE
HSS 6x6x1/2 PAINT TO MATCH LOUVER
HSS 6x6x1/2 PAINT TO MATCH LOUVER
EXTERIOR CEMENT PLASTER O/ SELF-FURRING MTL LATH O/ (2) LAYERS 17 BLDG WRAP A-511
EQ
LOUVER FRAME JAMB CORNER AT CEM PLAS AT MECH WELL
19
3" = 1'-0"
LOUVER TO LOUVER JAMB AT MECH WELL 3" = 1'-0"
Q1
Q1
(3) HEAVY DUTY HINGES (3) HEAVY DUTY HINGES HSS 6x6x1/2 PAINT TO MATCH LOUVER HSS 6x6x1/2 PAINT 1"x1" TO GALV FLASHING MATCH LOUVER CLIP
8
DIM POINT
1
DIM POINT CONT SEALANT & BACKER ROD SST #14 SDST SCREW @ 12" OC & 6" FROM ENDS TYP EXTERIOR CEMENT
1/2" JOINT SEALANT W/FIBRE EXPANSION MATERIAL
EXT DOOR THRESHOLD 3" = 1'-0"
Q1
EQ
CL
MECH WELL SIDE
EQ
EQ
CL
EQ
SST #14 SDST SCREW @ 12" OC & 6" FROM ENDS TYP
GALV SILL PAN PAINT TO MATCH ADJACENT FRAME
DIM POINT
2"
HSS 6x6x1/2. PAINT TO MATCH LOUVER HSS 6x6x1/2 PAINT TO MATCH LOUVER
CONT SEALANT & BACKER ROD
1"x1" GALV FLASHING CLIP
GALV SILL PAN PAINT TO MATCH ADJACENT FRAME
SINGLE PLY ROOFING O/ PLYWD SHTHG
PLYWD SHTHG SINGLE PLY ROOFING O/ PLY WD SHEATHING
PLYWD SHTHG PER STRUCT
THERMAL INSULATION
ACCESS ACCESS DOOR DOOR AT AT MECH MECH WELL WELL -JAMB JAMB AT AT HINGE HINGE 3"3"==1'-0" 1'-0"
Q1 Q1
THERMAL INSULATION
PLYWD SHTHG
EXTERIOR CEMENT PLASTER O/ SELF-FURRING MTL LATH O/ (2) LAYERS BLDG 17 WRAP A-511
16
DIM POINT
1"x1" GALV FLASHING CLIP SINGLE PLY ROOFING O/ PLYWD SHTHG
TITLE
DETAILS - DOOR AND WINDOW
THREADED STUDS & SILL STUDS PER STRUCT
THREADED STUDS & SILL STUDS PER STRUCT
PLASTER O/ SELF17 FURRING MTL LATH HMF LOUVER AND FRAME O/TYP (2) LAYERS BLDG A-511 PAINT P8 WRAP
12 12
CONT SEALANT & BACKER ROD
SINGLE PLY CLADDING 2"
A
2
HMF LOUVER AND FRAME TYP. PAINT P8
MECH WELL SIDE
LOUVER ACCESS DOOR FRAME HSS 5x2x1/8 PAINT P8
MECH WELL SIDE
INTERIOR FLOOR FINISH SLOPE SEE . CIVIL
HMF LOUVER AND FRAME TYP. PAINT P8
ALIGN
HILTI KH-EZ P 1/4" CONC SCREW MIN. 2" EMBED @ 18" OC (MIN 3) PER ESR-3027 OR APPROVED EQUIVALENT
PLAN VIEW
4"
2"
THRESHOLD PER HDW ON CONT. BED OF MASTIC
MECH WELL SIDE
017294 ?00.00.00? LIONAKIS 2017
AGENCY
1/2" GAP
PLAN VIEW
DOOR SEE SCHEDULE
EQ
PLASTER CASING J-BEAD MOLDING
4"
DOOR BOTTOM & SHOE
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
CL
Q1
LOUVER ACCESS DOOR FRAME HSS 5x2x1/8 PAINTACCESS P8 LOUVER DOOR FRAME HSS 5x2x1/8 PAINT P8
MANAGEMENT
HMF LOUVER AND FRAME TYP PAINT P8
PLYWD SHTHG PER STRUCT
15
3" = 1'-0"
Q1
1/2" MAX @ 1:2 SLOPE
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
HSS 6x6x1/2 PAINT TO MATCH LOUVER AND FRAME
ALIGN
1/2" GAP
VARIES
SST #14 SDST SCREW @ 12" OC & 6" FROM ENDS TYP
HSS 6x6x1/2 PAINT TO MATCH LOUVER
2"
5/8"
1"x1" GALV FLASHING CLIP
PER FRAME DEPTH SEE FLOOR PLAN FOR WALL TYPE
5/15/2019 3:48:38 PM
SST #14 SDST SCREW @ 12" OC & 6" FROM ENDS TYP
DIM POINT
1/2" GAP
2"
BACKER ROD W/ CONT SEAL BEAD
TYP HOLLOW METAL FRAME
3
EQ
SINGLE PLY CLADDING
B
EXTERIOR
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
HMF LOUVER AND FRAME TYP PAINT P8
SST #14 SDST SCREW @ 12" OC & 6" FROM ENDS TYP
DIM POINT
2"
EQ
2"
7/8"
2" CONT FLANGE AROUND FRAME JAMBS AND HEAD
EQ
CL
CL
DATE 01/04/2019 05/17/2019
MECH WELL SIDE
GALV MTL DRIP FLASHING PAINT TO MATCH ADJACENT FRAME
1/2" TYP.
EQ
THERMAL INSULATION
INTERIOR FINISH PER SCHED
PLYWD SHEATHING PER STRUCT
07/03/2019
N
1"
✔
FIBER CEMENT SOFFIT
5/8" GYP BD TYPE 'X'
9
5/8" GYP BD TYPE 'X'
ACS
✔
SINGLE PLY ROOFING O/ PLYWD SHEATHING
HMF LOUVER AND FRAME TYP PAINT P8
2"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
FIBER CEMENT SIDING O/ (2) LAYERS BLDG WRAP
THERMAL INSULATION
PLYWD SHEATHING PER STRUCT
FLS
R
THERMAL INSULATION
DATE:
THREADED STUDS & HEADER PER STRUCT
LI J ON C
GALV METAL DRIP FLASHING PAINT TO MATCH ADJACENT FRAME @ DR/WIND HEAD
✔
THERMAL INSULATION
EXTERIOR CEMENT PLASTER O/ SELF-FURRING MTL LATH O/ (2) LAYERS BLDG 17 WRAP A-511 SHEET
ACCESS DOOR AT MECH WELL SILL
20
3" = 1'-0"
Q1
A-542
LOUVER FRAME - SILL 3" = 1'-0"
Q1
4
5
Z/H ≤ 0.5
Z/H > 0.5 a.b
SDS ≤ 1.15
12 X 12
12 X 12
1.15 ≤ SDS ≤ 1.73
12 X 12
8 X 12
SDS ≥ 1.73
8 X 12
8X8
DISTANCE FROM CLG TO STRUCTURE ABOVE
COMPRESSION STRUT SIZE
≤ 5'-0" ≤ 6'-10" ≤ 8'-0" ≤ 8'-10" ≤ 10'-10"
250S125-33 250S137-33 362S137-33 250S137-43 400S137-43
* SDS SHALL BE PER STRUCTURAL DRAWINGS. IF NO STRUCTURAL DRAWINGS ARE INCLUDED, DETERMINE VALUE PER CURRENT BUILDING CODE.
TYPICAL CEILING PLAN AE_A_0550_005 Q1
1" = 1'-0"
5
1" MIN
NOTES: 1. DO NOT USE THIS DETAIL WHERE COMPRESSION STRUTS ARE VISIBLE TO BUILDING OCCUPANTS. 2. ALL PRODUCTS SHALL POSSESS DIMENSIONS, SECTION PROPERTIES, AND MATERIALS IN COMPLIANCE WITH THE AISI D100 MANUAL OF COLD-FORMED STEEL DESIGN AND BE MANUFACTURED BY A CURRENT MEMBER OF THE "STEEL STUD MANUFACTURER'S ASSOCIATION" (SSMA). 3. STEEL MEMBERS 18GA OR LIGHTER SHALL BE MANUFACTURED PER ASTM A653 SS, GRADE 33, AND 16 GA OR HEAVIER PER ASTM A653 SS, GRADE 50, CLASS I.
HANGER WIRE W/ LOOP
9
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
BASIS OF DESIGN: ESR1308
3" MAX MIN MIN
1"
1 1/2" MIN PENETRATION
1 1/2" 2"
MIN
BRACING WIRE TO TJI
10
0550_XXXX_WIRE_01
3" = 1'-0"
UNIVERSAL LCD HOLDER VECTOR MOUNT PER DATA/TELE/COMM
2.01
CEILING WIRE SHALL BE CLASS 1 ZINC COATED (GALVANIZED) CARBON STEEL CONFORMING TO ASTM A641-09A. WIRE SHALL BE #12 GAGE (0.106” DIAMETER) WITH SOFT TEMPER AND MINIMUM TENSILE STRENGTH = 70 KSI.
2.02
GALVANIZED SHEET STEEL (INCLUDING THAT USED FOR METAL STUD AND TRACK COMPRESSION STRUTS/POST) SHALL CONFORM TO ASTM A653-11, OR OTHER EQUIVALENT SHEET STEEL LISTED IN SECTION A2.1 OF THE NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS 2007, INCLUDING SUPPLEMENT 2 DATED 2010 (AISI S100-07/S2-10). MATERIAL 43 MIL (18 GAGE) AND LIGHTER SHALL HAVE MINIMUM YIELD STRENGTH OF 33 KSI. MATERIAL 54 MIL (16 GAGE) AND HEAVIER SHALL HAVE A MINIMUM YIELD STRENGTH OF 50 KSI.
2.03
ELECTRICAL METALLIC TUBE (EMT) SHALL BE ANSI C80.3/UL 797 CARBON STEEL WITH G90 GALVANIZING. EMT SHALL HAVE MINIMUM YIELD STRENGTH (FY) OF 30 KSI AND MINIMUM ULTIMATE STRENGTH (FU) OF 48 KSI.
3.
ATTACHMENT OF HANGER AND BRACING WIRES
3.01
SEPARATE ALL CEILING HANGER AND BRACING WIRES AT LEAST SIX (6) INCHES FROM ALL UNBRACED DUCTS, PIPES, CONDUIT, ETC.
3.02
HANGER AND BRACING WIRES SHALL NOT ATTACH TO OR BEND AROUND OBSTRUCTIONS INCLUDING BUT NOT LIMITED TO: PIPING, DUCTWORK, CONDUIT AND EQUIPMENT.
MIN
1 1/2" MAX
STEP 2
STEP 3
0T O4 5° TYP
2" MAX
(4) TIGHT TURNS
(2) #10 SDST SCREWS
STEP 4
HANGER WIRES THAT ARE MORE THAN ONE (HORIZONTAL) IN SIX (VERTICAL) OUT OF PLUMB SHALL HAVE COUNTER-SLOPING WIRES.
3.04
SLACK SAFETY WIRES SHALL BE CONSIDERED HANGER WIRES FOR INSTALLATION AND TESTING REQUIREMENTS.
3.05
HANGER AND BRACING WIRE ANCHORAGE TO THE STRUCTURE SHALL BE INSTALLED IN SUCH A MANNER THAT THE DIRECTION OF THE ANCHORAGE ALIGNS CLOSELY WITH THE DIRECTION OF THE WIRE. (E.G. BRACING WIRE CEILING CLIPS MUST BE BENT AS SHOWN IN THE DETAILS AND ROTATED AS REQUIRED TO ALIGN CLOSELY WITH THE DIRECTION OF THE WIRE, SCREW EYES IN WOOD MUST BE INSTALLED SO THEY ALIGN CLOSELY WITH THE DIRECTION OF THE WIRE, ETC.)
4.
FASTENERS AND WELDING:
4.01
SHEET METAL SCREWS SHALL COMPLY WITH ASTM C1513-10, ASME B18.6.4-89 (R2005). PENETRATION OF SCREWS THROUGH JOINED MATERIAL SHALL NOT BE LESS THAN THREE EXPOSED THREADS.
EXTENSION COLUMN SLEEVE COVER PLATE
4.02
NOT USED
8'-0" CENTERLINE OF LENS
4.03
NOT USED
4.04
IF NOT OTHERWISE SPECIFIED IN THE EVALUATION REPORT, POWER-ACTUATED FASTENERS INSTALLED IN STEEL SHALL BE INSTALLED SO THE ENTIRE POINTED END OF THE FASTENER IS DRIVEN THROUGH THE STEEL MEMBER.
SUSP ACTS RUNNER
CL
14
PROJECTOR MOUNT
4.05
POWER-ACTUATED FASTENERS IN CONCRETE ARE NOT PERMITTED FOR BRACING WIRES.
4.06
CONCRETE REINFORCEMENT AND PRESTRESSING TENDONS SHALL BE LOCATED BY NON-DESTRUCTIVE MEANS PRIOR TO INSTALLING POST - INSTALLED ANCHOR.
4.07
WELDING SHALL BE IN ACCORDANCE WITH AWS D1.3 USING E60XX SERIES ELECTRODES.
5.
TESTING: ALL FIELD TESTING MUST BE PERFORMED IN THE PRESENCE OF THE PROJECT INSPECTOR.
1 1/2" = 1'-0"
HANGER WIRE SPLICE KNOT APPLICATION STEP 1
3.03
PROJECTOR BY OWNER MAX. 15 LBS
CREATE AN APPROXIMATELY 5 INCH BEND IN THE END OF EACH HANGER WIRE WITH THE SHORT ENDS OPPOSED, BRING THE RIGHT-HAND END OVER THE LEFT-HAND AND LOOP THE SHORT END UNDER AND AROUND THE LEFT-HAND END
2"x2"x15 GA ANGLE ALL FOUR SIDES OF OPENING
LOOP THE LEFT-HAND SHORT END BACK UP AND AROUND THE RIGHTHAND LOOP, WITH THE LEFT-HAND END OVER THE RIGHT-HAND END AND BRING THE LEFT-HAND END UNDER THE LOOP OF THE RIGHT HAND END
1/2" MIN TO BOLT
AT CURTAIN WALL AND ROLLER SHADE HOUSING CONDITIONS, TYP
ACOUSTICAL CEILING EDGE 6" = 1'-0"
AE_A_0550_004 Q1
CROSS RUNNER
MAX
SLOT END OVER MAIN RUNNER OR FLATTEN END DISTANCE FROM CLG TO STRUCTURE ABOVE
COMPRESSION STRUT SIZE
≤ 4'-0" ≤ 8'-0" ≤ 12'-0"
3/4" DIA 1 1/4" DIA 2" DIA
7
MAIN RUNNER
2"
1/4" DIA MACHINE BOLT
FREE SIDE
STEP 5
(4) TIGHT TURNS
TYP EMT COMPRESSION STRUT 0550_XXXX_COMPRESSION STRUT TYP_02
1 1/2" = 1'-0"
11
1" = 1'-0"
0550_XXXX_HANGER WIRE SPLICE_02
6.04
6.05
6.05
15
ACCESS PANEL AT GYP. BD. 3" = 1'-0"
Q2 6.06
6.06
SLOT END OF TUBE
7
2"x2"x15 GA ANGLE ALL FOUR SIDES OF OPENING
1/4" DIA LAG SCREW IN CENTER OF JOIST/ BLK'G, 1-1/2" MIN PENETRATION, TYP
7 7.01 7.01
1-1/2" x 1-1/2" x 12 GA x 0'-2" CLIP. VERT LEG OF CLIPI TO FALL WITHIN WIDTH OF WOOD MEMBER
7.02
(2) #10 SMS
7.03
7.02
7.03 A
EMT CONDUIT COMPRESSION STRUT, PLACE TIGHT TO CLIP
2X10 BLOCKING. ATTACHMENT OF SUSPENDED CLG. ELEMENTS PER DETAILS THIS SHEET.
7.04 RELEASE LATCH
7.04
ACCESS DOOR W/ STEEL FRAME
BACKER BLKG, THICKNESS RIPPED TO ALIGN W/ BOTTOM CHORD OF TJI, DEPTH TO ALIGN W/ TOP OF BLKG, MIN. 18" LENGTH, TYP. ATTACH TO TJI W/ (2) ROWS OF 10D NAILS @ 12" OC
4
8. 8.01 8.01
OPTION 1
TJI BLOCKING AT CEILING ATTACHMENTS 3" = 1'-0"
8.
FIBER CEMENT SOFFIT BOARD PER ESR-2273 O/ EXT. SHEATHING
AE_A_0550_045 Q1
8
OPTION 2
EMT COMPRESSION STRUT TO WOOD JOISTS/BLOCKING 3" = 1'-0"
0550_XXXX_COMPRESSION STRUT TO WOOD_10
16
ACCESS PANEL AT FIBER CEMENT
20
3" = 1'-0"
Q2
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
ALL LIGHT FIXTURES SHALL BE POSITIVELY ATTACHED TO THE CEILING SUSPENSION SYSTEMS BY MECHANICAL MEANS TO RESIST A HORIZONTAL FORCE EQUAL TO THE WEIGHT OF THE FIXTURE. A MINIMUM OF TWO SCREWS OR APPROVED FASTENERS ARE REQUIRED AT EACH LIGHT FIXTURE, PER ASTM E580, SECTION 5.3.1. MIN. (2) HILTI #8-18S PER ESR-2196 OR APPROVED EQUIVALENT. SIZE AND NUMBER SHALL CORRESPOND TO SURFACE-MOUNTED WEIGHT OF FIXTURE.LIGHT FIXTURES SHALL BE ATTACHED TO THE MAIN RUNNER WITH AT LEAST TWO POSITIVE CLAMPING DEVICES. THE CLAMPING DEVICE SHALL SURFACE-MOUNTED LIGHTTHE FIXTURES SHALL CEILING BE ATTACHED TO THE RUNNER WITH COMPLETELY SURROUND SUPPORTING RUNNER AND MAIN BE MADE OF STEEL AT LEAST TWO POSITIVE CLAMPING DEVICES. THE CLAMPING DEVICE SHALL WITH A MINIMUM THICKNESS OF #14 GAGE. ROTATIONAL SPRING CATCHES DO NOT COMPLETELY THE SUPPORTING CEILING RUNNER ANDFROM BE MADE OF STEEL COMPLY. A #12SURROUND GAGE SLACK SAFETY WIRE SHALL BE CONNECTED EACH WITH A MINIMUM THICKNESS OF #14 GAGE. ROTATIONAL SPRING CATCHES DO NOT CLAMPING DEVICE TO THE STRUCTURE ABOVE. PROVIDE ADDITIONAL SUPPORTS WHEN COMPLY. A #12 GAGE SLACK(8) SAFETY WIRE SHALL OR BE EXCEED CONNECTED FROM EACHSPACING LIGHT FIXTURES ARE EIGHT FEET OR LONGER 56 LB. MAXIMUM CLAMPING DEVICE TOSHALL THE STRUCTURE ABOVE. BETWEEN SUPPORTS NOT EXCEED EIGHTPROVIDE (8) FEET ADDITIONAL SUPPORTS WHEN LIGHT FIXTURES ARE EIGHT (8) FEET OR LONGER OR EXCEED 56 LB. MAXIMUM SPACING BETWEEN SUPPORTS SHALLLESS NOT THAN EXCEED LIGHT FIXTURES WEIGHING OR EIGHT EQUAL(8) TOFEET 10 LB. SHALL HAVE A MINIMUM OF
6.04
HANGER WIRE SPLICE, ACOUSTICAL CEILING SYSTEM
CLIENT
6.01
6.03
EN . 08 - 3 1 - 1 O F OF CAL I
770 DIAMOND AVE RED BLUFF, CA 96080
LIGHT FIXTURES:
6.03
R E
TEHAMA CENTER STUDENT SERVICES
6.
ACCESS DOOR W/ DRYWALL FLANGES
T
PROJECT
POST-INSTALLED ANCHORS IN CONCRETE USED TO ATTACH BRACING WIRES SHALL BE TESTED AT A FREQUENCY OF 50 PERCENT IN ACCORDANCE WITH CBC SECTION 1913A.7.
RELEASE LATCH
APPLICATION NOTES: FOR USE WHERE INSTALLED CEILING DROP FROM THE OVERHEAD STRUCTURE TO THE CEILING GRID EXCEEDS THE AVAILABLE LENGTH OF THE WIRE IN VERTICAL AND SEISMIC BRACING WIRES
C23603
5.02
6.02
5x8" GYP BD TYPE 'X' CLG
D A RCH SE I E N A N McM TE H U T A
POST-INSTALLED ANCHORS IN CONCRETE USED TO SUPPORT HANGER WIRES SHALL BE TESTED AT A FREQUENCY OF 10 PERCENT. POWER ACTUATED FASTENERS IN CONCRETE SHALL BE FIELD TESTED FOR 200 LBS. IN TENSION. ALL OTHER POST-INSTALLED ANCHORS IN CONCRETE SHALL BE TESTED IN ACCORDANCE WITH CBC SECTION 1913A.7.
DRAW THE KNOT TIGHT
WRAP THE HANGER WIRE ENDS SECURELY AROUND ITSELF WITH FOUR COMPLETE TIGHT TURNS WITH 11/2 INCHES MAXIMUM
SEAL
5.01 5x8" GYP BD TYPE 'X'
"SIMPSON" A34 EA END
5/15/2019 3:48:38 PM
CONSULTANT
6.02
NOTES: PROVIDE #12 GAGE HANGER WIRES AT THE ENDS OF ALL MAIN AND CROSS RUNNERS WITHIN EIGHT (8) INCHES OF THE SUPPORT OR WITHIN ONE FOURTH (1/4) OF THE LENGTH OF THE END TEE, WHICHEVER IS LESS, FOR THE PERIMETER OF THE CEILING AREA. PERIMETER WIRES ARE NOT REQUIRED WHEN THE LENGTHS OF THE END TEE IS EIGHT (8) INCHES OR LESS
3
BRACING WIRE W/ EYE-LAG
BRACING WIRE CONNECTION TO WOOD JOISTS/BEAMS/BLOCKING
1 1/2" MAX
FIXED SIDE
HANGER WIRE, 3 TIGHT TURNS IN 3" TYP BRACE WIRE, 4 TIGHT TURNS IN 1-1/2" TYP
INSTALL SCREW SO MOVEMENT IS PERMITTED CEILING GRID 7/8" x 18GA WALL ANGLE WITH CLIP AND #10 x 1 1/2" LONG SDST SCREW TO EA WALL STUDS @ 16" OC MAX BERC-2 CLIP SHOWN
MATERIALS:
"LUCASEY" #CMASTA STABILIZER KIT
BALL & SOCKET UNIT LOAD CAPACITY 50 LBS
1/4" DIA CLOSED SCREW EYE LAG W/ 1-1/4" 1-1/2" MIN PENETRATION, INSTALL IN DIRECTION OF WIRE
EMT GALVANIZED COMPRESSION STRUT, SIZE PER TABLE BELOW
3/4" MIN 2"
3/4" MIN. CLR.
CROSS RUNNER ACOUSTIC CEILING TILE WHERE OCCURS TIGHTEN SCREW TO WEB OF GRID TO PREVENT MOVEMENT
B
2.
12 GA SPLAY WIRE ANGLE 45° MAX TYP OF 4 W/ 4 TIGHT TURNS WITHIN 1 1/2" OF END, TYP AT EACH END
Q2
1'-0" MAX
3 TIGHT TURNS, TYPICAL
1 1/2" MAX
MAIN OR CROSS RUNNER
0550_XXXX_COMPRESSION STRUT TO WOOD_02
3" = 1'-0"
EMT NO MORE THAN ONE SIZE LARGER THAN EMT STRUT SELECTED
NOTE 1
NOTE 1
6
LCD PROJECTOR MOUNTING BRACKET
BERC-2 _____________ __ .
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
LCD PROJECT MOUNTING BRACKET
1" MIN CLR
NOTES: 1. CONDITION AT JOISTS SHOWN, COND AT BLKG SIM. ATTACH BLKG TO JOISTS W/ 1-1/2" X 1-1/2" X 18GA CLIP AND (4) 8DX1-1/2" NAILS EA SIDE AND EA END 2. ALL FRMG TO BE 2x (1-1/2" ACTUAL) MIN
STUD COMPRESSION STRUT TO WOOD JOISTS/ BLOCKING
1"
SEISMIC BRACING PER 2 A-551
2X4 MIN FLAT W/ 1-10D OR 1-#10X3" SCREW TO EA OF 3 TRUSS BOTTOM FLANGES
BRACING WIRE W/ LOOP
4 A-551
(E) 1/4" DIA LAG BOLT W/ STL WASHER (2" MIN. EMBED)
BRIDGING OR FULL-DEPTH BLOCKING WITHIN 24" OF BRACING WIRE CONNECTION
CUT FLANGES AND BEND
OPTION 2
SEE TYPICAL DETAILS FOR CONNECTION
8" MAX
MIN 4x BLKG. ATTACHMENT PER
ADJUSTABLE LENGTH EXTENSION COLUMN MODEL: ADJ SERIES VERIFY LENGTH PER MOUNTING HEIGHT AND BEAM LOCATION
1/4" DIA LAG SCREW IN CENTER OF JOIST/ BLOCKING, TYP
WEB OF CHANNEL TO BEAR WITHIN WIDTH OF WOOD MEMBER
6" MIN
8" MAX
1/4" DIA CLOSED SCREW EYE LAG W/ 1-1/2" 1-1/4" MIN PENETRATION, INSTALL IN DIRECTION OF WIRE
07/03/2019
FOR CEILING INSTALLATIONS UTILIZING ACOUSTICAL TILE PANELS OF MINERAL OR GLASS FIBER, IT IS NOT MANDATORY TO PROVIDE ¾” CLEARANCE BETWEEN THE ACOUSTICAL TILE PANELS AND THE WALL ON THE SIDES OF THE CEILING WHICH ARE FREE TO SLIP. FOR ALL OTHER CEILING PANEL TYPES, PROVIDE ¾” CLEARANCE BETWEEN THE CEILING PANEL AND THE WALL ON THE SIDES OF THE CEILING FREE TO SLIP.
3" = 1'-0"
✔
CT Y R RT
45° MAX
TYP
HANGER WIRE, TYP
13
GYP SOFFIT AT ADMIN TRANSITION
SEISMIC WALL CLIP: MANUFACTURER’S MODEL
A
1 3/8" MIN
CROSS RUNNER
AE_A_0550_003 Q1
0550_XXXX_WIRE_01
3" = 1'-0"
(4) TIGHT TURNS IN FIRST 1-1/2"
MAIN RUNNER
3/4" = 1'-0"
5/8" GYP BD TYPE 'X" SOFFIT
ACS
✔
CEILING SYSTEMS. THE FOLLOWING CEILING SYSTEM(S) IS/ARE PART OF THE SCOPE OF THIS PROJECT: MANUFACTURER'S NAME ARMSTRONG WORLD INDUSTRIES PRODUCT EVALUATION REPORT TYPE AND NUMBER ICC ESR-1308 MANUFACTURER'S MODEL NUMBER - MAIN RUNNER __ PRELUDE XL 7301 MANUFACTURER'S CATALOG NUMBER - CROSS RUNNER _XL7342/XL7328
ST
(4) 1/4" DIA LAG SCREWS
OPTION 1
2
HANGER WIRE W/ SADDLE TIE
HANGER WIRE CONNECTION TO WOOD JOISTS/BEAMS/BLOCKING (3) 1-1/2" x 9 GA STAPLES AT EA LOOP
2"
TYP CEILING BRACING ASSEMBLY
HANGER WIRE W/ EYE-LAG
DATE:
FLS
1.06
Q2
(4) #12 GA BRACING WIRE BRACING IN PLANE OF EA RUNNER @ COMPRESSION STRUT. WIRE BRACING TO HAVE (4) TIGHT TURNS WITHIN 1 1/2" @ EA END
C
HANGER WIRE W/ EYE-LAG
3 A-551
WALL ANGLE PER
SS
THE CEILING GRID SYSTEM MUST BE RATED HEAVY DUTY AS DEFINED BY ASTM C635-08.
CEILING PANELS SHALL NOT SUPPORT ANY LIGHT FIXTURES, AIR TERMINALS OR DEVICES.
NOTES: 1. CONDITION AT JOISTS SHOWN, COND AT BLKG SIM. ATTACH 2X BLKG TO TJI W/ (2) 16D COMMON END NAILS OR (3) 10D TOE NAILS EA END 2. ALL FRMG TO BE 2x (1-1/2" ACTUAL) MIN
0550_XXXX_COMPRESSION STRUT TYP_01
1 1/2" = 1'-0"
GYP BD WALL FRMG BEYOND
INC:
REVIEWED FOR ✔
1.05
WD FRMG PER STUCT
(3) TIGHT TURNS IN FIRST 3"
TYP STUD COMPRESSION STRUT
VERTICAL HANGER WIRE, 12 GA @ 4'-0" OC EA WAY AT MAIN RUNNER WITH MIN 3 TIGHT TUNS IN 3" @ EA END
7 A-551
5 A-551
SUSPENDED ACST CLG RUNNER
DIM POINT SEE RCP
EQEQ
STUD OR EMT COMPRESSION STRUT PER
TYP SADDLE TIE
(3) 1-1/2" x 9 GA STAPLES AT EA LOOP
1.04
5/8" GYP BD TYPE 'X' O/ PLY WD
COPE FLANGE OR FLATTEN TO ALLOW INSTALLATION OF PANELS
(2) 1/4" DIA MACHINE BOLT
BRACE ASSAMBLY SPACING (FT.)
1
1 1/2" MAX
4 TIGHT TURNS IN 1-1/2" TYP FOR BRACE WIRE
CROSS RUNNER
DESIGN SPECTRAL ACCELRATION PARAMETER, SDS
1 A-551
APP. 02-117123
IA
3 A-551
VERT HANGER PER ACST INSUL
MAIN RUNNER
MAIN RUNNERS. TYP
FREE SIDE
EQ
6".
3 A-551
1 1/2" MAX
EQ
2"
2 A-551
1.02
2" MIN
FIXED SIDE
FREE SIDE
TYP. BRACING ASSEMBLY PER
CEILING SYSTEM COMPONENTS SHALL COMPLY WITH ASTM C635-07 AND SECTION 5.1 OF ASTM E580-10A.
N
3/4" MIN TYP.
CROSS RUNNERS TYP.
1.01
9
1" MAX
MIN
FIXED SIDE
BRACE WIRE, 4 TIGHT TURNS IN 1-1/2" TYP
1"
PERIMETER WALL ANGLE
5°
D
3 A-551
1/4" DIA DRILLED HOLE
CEILING SYSTEM GENERAL NOTES
1.03
STEEL STUD COMPRESSION STRUT SLOTTED AND CENTERED OVER CROSS RUNNER; SEE TABLE FOR SIZE
LINE OF PERIMETER WALL
O4 0T
3 A-551
MAX
. TYP
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
8'-0" MAX 4'-0" MAX
8'-0" MAX 4'-0" MAX
HANGER WIRE, 3 TIGHT TURNS IN 3" TYP
1/4" DIA CLOSED SCREW EYE LAG W/ 1-1/2" 1-1/4" MIN PENETRATION, INSTALL IN DIRECTION OF WIRE
SEE TYP CONNECTION DETAILS
4'-0" OC
3/4" MIN EDGE DISTANCE TO BOLT TYP
0 1/4" 1/2"
12 GA PERIMETER HANGER WIRES AT TERMINAL END OF EACH MAIN RUNNER AND CROSS TEE
1.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
R
3
LI J ON C
2
1"
2"
1
ONE (1) #12 GAGE SLACK SAFETY WIRE CONNECTED FROM THE FIXTURE HOUSING TO LIGHT FIXTURES WEIGHING THE STRUCTURE ABOVE. LESS THAN OR EQUAL TO 10 LB. SHALL HAVE A MINIMUM OF ONE (1) #12 GAGE SLACK SAFETY WIRE CONNECTED FROM THE FIXTURE HOUSING TO THE STRUCTURE ABOVE. LESS THAN OR EQUAL TO 10 LB. SHALL HAVE A MINIMUM OF LIGHT FIXTURES WEIGHING ONE (1) #12 GAGE SLACK SAFETY WIRE CONNECTED FROM THE FIXTURE HOUSING TO LIGHT FIXTURES WEIGHING THE STRUCTURE ABOVE. LESS THAN OR EQUAL TO 10 LB. SHALL HAVE A MINIMUM OF ONE (1) #12 GAGE SLACK SAFETY WIRE CONNECTED FROM THE FIXTURE HOUSING TO THE STRUCTURE ABOVE. GREATER THAN 10 LB. BUT LESS THAN OR EQUAL TO 56 LBS. LIGHT FIXTURES WEIGHING MAY BE SUPPORTED DIRECTLY ON THE CEILING RUNNERS, BUT THEY SHALL HAVE A LIGHT FIXTURES GREATER 10 LB. BUTCONNECTED LESS THAN OR EQUAL 56 LBS. MINIMUM OF TWOWEIGHING (2) #12 GAGE SLACKTHAN SAFETY WIRES FROM THETO FIXTURE MAY BE SUPPORTED DIRECTLY ONTO THE CEILING RUNNERS, BUT THEY SHALL HAVE A HOUSING AT DIAGONAL CORNERS THE STRUCTURE ABOVE. MINIMUM OF TWO (2) #12ALL GAGE SLACK SAFETY WIRES CONNECTED FROM THE FIXTURE EXCEPTION: LIGHT FIXTURES GREATER THAN TWO BY FOUR FEET HOUSING AT DIAGONAL CORNERS TO THE STRUCTURE ABOVE. WEIGHING LESS THAN 56 LBS. SHALL HAVE A #12 GAGE SLACK SAFETY WIRE EXCEPTION: ALL LIGHT FIXTURES GREATER THAN TWO BY FOUR FEET AT EACH CORNER. WEIGHING LESS THAN 56 LBS. SHALL HAVE A #12 GAGE SLACK SAFETY WIRE AT EACH CORNER. ALL LIGHT FIXTURES WEIGHING GREATER THAN 56 LB. SHALL BE INDEPENDENTLY
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
SUPPORTED BY NOT LESS THAN FOUR (4) TAUT #12 GAGE HANGER WIRES (ONE AT EACH ALL LIGHTATTACHED FIXTURES WEIGHING THAN 56 LB. BE INDEPENDENTLY CORNER) FROM THEGREATER FIXTURE HOUSING TO SHALL THE STRUCTURE ABOVE OR SUPPORTED BY NOT LESS THAN FOUR (4)(4) TAUT #12 GAGE HANGER (ONE AT EACH OTHER APPROVED HANGERS. THE FOUR TAUT #12 GAGE WIRES WIRES OR OTHER CORNER) ATTACHED FROM THE FIXTURE HOUSING TO THE STRUCTURE ABOVE OR APPROVED HANGERS, INCLUDING THEIR ATTACHMENT TO THE STRUCTURE ABOVE, OTHER APPROVED HANGERS. THE FOUR (4) TAUT #12 GAGE WIRES OR OTHER SHALL BE CAPABLE OF SUPPORTING FOUR (4) TIMES THE WEIGHT OF THE FIXTURE. APPROVED HANGERS, INCLUDING THEIR ATTACHMENT TO THE STRUCTURE ABOVE, SHALL BE CAPABLE OF SUPPORTING FOUR (4) TIMES THE WEIGHT OF THE FIXTURE. SERVICES WITHIN THE CEILING: SERVICES WITHIN THE CEILING: ALL FLEXIBLE SPRINKLER HOSE FITTING MOUNTING BRACKETS, CEILING-MOUNTED AIR TERMINALS OR OTHER SERVICES SHALL BE POSITIVELY ATTACHED TO THE CEILING ALL FLEXIBLE SYSTEMS SPRINKLER FITTING MOUNTING BRACKETS, CEILING-MOUNTED AIR SUSPENSION BYHOSE MECHANICAL MEANS. SCREWS OR APPROVED FASTENERS TERMINALS OR OTHER SERVICES SHALL BE POSITIVELY CEILING ARE REQUIRED. A MINIMUM OF TWO ATTACHMENTS AREATTACHED REQUIREDTO ATTHE EACH SUSPENSION COMPONENT SYSTEMS BY MECHANICAL MEANS. SCREWS OR APPROVED FASTENERS ARE REQUIRED. A MINIMUM OF TWO ATTACHMENTS ARE REQUIRED AT EACH COMPONENT CEILING-MOUNTED AIR TERMINALS OR OTHER SERVICES WEIGHING LESS THAN OR EQUAL TO 20 LB. SHALL HAVE ONE (1) #12 GAGE SLACK SAFETY WIRE ATTACHED FROM CEILING-MOUNTED AIR TERMINALS OTHER SERVICES THE TERMINAL OR SERVICE TO THEOR STRUCTURE ABOVE. WEIGHING LESS THAN OR EQUAL TO 20 LB. SHALL HAVE ONE (1) #12 GAGE SLACK SAFETY WIRE ATTACHED FROM THE TERMINAL OR SERVICE TO THE STRUCTURE ABOVE. AIR TERMINALS OR OTHER FLEXIBLE SPRINKLER HOSE FITTINGS, CEILING-MOUNTED SERVICES WEIGHING MORE THAN 20 LB. BUT LESS THAN OR EQUAL TO 56 LB. SHALL FLEXIBLE HOSE FITTINGS, CEILING-MOUNTED AIR TERMINALS OR OTHER HAVE TWOSPRINKLER (2) #12 GAGE SLACK SAFETY WIRES (AT DIAGONAL CORNERS) CONNECTED SERVICES WEIGHING MORE THAN 20 LB. BUT LESS THAN OR EQUAL TO 56 LB. SHALL FROM THE TERMINAL OR SERVICE TO THE STRUCTURE ABOVE. HAVE TWO (2) #12 GAGE SLACK SAFETY WIRES (AT DIAGONAL CORNERS) CONNECTED FROM THESPRINKLER TERMINAL HOSE OR SERVICE TO THE STRUCTURE ABOVE. FLEXIBLE FITTINGS, CEILING-MOUNTED AIR TERMINALS OR OTHER SERVICES WEIGHING MORE THAN 56 LB. SHALL BE SUPPORTED DIRECTLY FROM THE FLEXIBLE SPRINKLER HOSE CEILING-MOUNTED AIR TERMINALS OTHER STRUCTURE ABOVE BY NOTFITTINGS, LESS THAN FOUR (4) TAUT #12 GAGE HANGEROR WIRES SERVICES WEIGHING MORE THAN 56 LB. SHALL BE SUPPORTED DIRECTLY FROM THE ATTACHED FROM THE TERMINAL OR SERVICE TO THE STRUCTURE ABOVE OR OTHER STRUCTURE ABOVE BY NOT LESS THAN FOUR (4) TAUT #12 GAGE HANGER WIRES APPROVED HANGERS. ATTACHED FROM THE TERMINAL OR SERVICE TO THE STRUCTURE ABOVE OR OTHER APPROVED HANGERS. OTHER DEVICES WITHIN THE CEILING:
TITLE
DETAILS - CEILING
OTHER DEVICES WITHIN THE CEILING: ALL LIGHTWEIGHT MISCELLANEOUS DEVICES, SUCH AS STROBE LIGHTS, OCCUPANCY SENSORS, SPEAKERS, EXIT SIGNS, ETC., SHALL BE ATTACHED TO THE CEILING GRID. IN ALL LIGHTWEIGHT AS STROBE LIGHTS, OCCUPANCY ADDITION, DEVICESMISCELLANEOUS WEIGHING MOREDEVICES, THAN 10 SUCH LBS. SHALL HAVE A #12 GAGE SLACK SENSORS, SPEAKERS, EXIT SIGNS, ETC., SHALL BE ATTACHED TO THE CEILING GRID. IN SAFETY WIRE ANCHORED TO THE STRUCTURE ABOVE. DEVICES WEIGHING MORE THAN ADDITION, DEVICES WEIGHING MORE THAN 10 LBS. SHALL HAVE A #12 GAGE SLACK 20 LB. SHALL BE SUPPORTED INDEPENDENTLY FROM THE STRUCTURE ABOVE. SAFETY WIRE ANCHORED TO THE STRUCTURE ABOVE. DEVICES WEIGHING MORE THAN 20 LB. SHALL BE SUPPORTED INDEPENDENTLY FROM THE STRUCTURE ABOVE.
A-551
SUSPENDED CEILING NOTES 1/8" = 1'-0"
SHEET
Q1
017294 ?00.00.00? LIONAKIS 2017
2"
1
2
3
4
5
CASEWORK GENERAL NOTES 100 OR 200 SERIES CABINETS MAY BE CONVERTED INTO MOVEABLE CABINETS BY PREFIXING A "7" TO THE NUMBER. (EXAMPLE: 7-102-36" X 30" X 18").
2.
MOVEABLE CABINETS SHALL BE EQUIPPED WITH ADEQUATE APPROVED CASTERS FOR THE INTENDED LOAD CAPACITY.
0 1/4" 1/2"
1"
1.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
REVIEWED FOR SS
✔
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
DATE:
PARTITION STRUCTURE
TYPICAL CASEWORK FASTENER AND BACKING
WOOD STUD
#14 ROUND WASHER HEAD WOOD SCREW W/ 2 1/2" MIN EMBED INTO TYPE 'B' BACKING, SCREW SPACING: • W/ (1) LAYER OF 5/8" GYP: 16" OC - (2) MIN PER CABINET • W/ (2) LAYERS OF 5/8" GYP: 12" OC - (2) MIN PER CABINET
INC:
FLS
ACS
✔
✔
07/03/2019
CASEWORK LEGEND DIM POINT
WIDTH WI 302
THE CASEWORK IS LABELED PER THE NORTH AMERICAN ARCHITECTURAL WOODWORK STANDARDS MANUAL (NAAWS 3.0) SPONSORED BY THE WOODWORK INSTITUTE. THE MANUAL CONTAINS AN APPENDIX WITH THE CABINET DESIGN SERIES (CDS) WHERE EACH STYLE HAS A UNIQUE IDENTIFYING NUMBER WITH AN ILLUSTRATION OF THE CABINET CONFIGURATION.
D
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
CABINET DIMENSIONS ARE SHOWN ON THE CONSTRUCTION DRAWINGS. ADDITIONAL CONSTRUCTION INFORMATION IS LOCATED IN THE SPECIFICATIONS.
CABINET
TYP CASEWORK FASTENER PER
BACKING, SEE
CASEWORK CONSTRUCTION SHALL BE PER APPLICABLE WI NAAWS 3.0 CONSTRUCTION STANDARDS. ANCHORAGE TO SUPPORTING STRUCTURE SHALL BE PER CONSTRUCTION DOCUMENTATION.
13 A-561
18 A-521
FLOOR STRUCTURE
ATTACH TO CONC SLAB W/ 0.145" DIA PAF @ 24" OC W/ 1" MIN EMBED INTO CONC
CONCRETE
UPPER CASEWORK
9
TYP CASEWORK FASTENERS
13
3" = 1'-0"
FASTENER
WIDTH
AE_A_0560_109 ?YYMMDD?. Q1
SCALE: NTS
Q1
WI 222
WI 302
WI 222
SEAL 9 A-561
84" AFF D A RCH SE I E N A N McM TE H U T A
C
34" AFF
BACKING, SEE
13 A-561
12 A-561
18 A-521
IA R
TEHAMA CENTER STUDENT SERVICES
EQ
TYP FULL HEIGHT CAB, UON
770 DIAMOND AVE RED BLUFF, CA 96080
NOTES:
2. 3.
UPPER CASEWORK - TYP
14
3" = 1'-0"
CLIENT
SEE INTERIOR ELEVATIONS FOR CASEWORK PROFILES. SEE ENLARGED PLANS FOR DIMENSIONS AND SIZES. ALL DIMENSIONS HERE TYP UON.
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
TYP CASEWORK ANCHORAGE AE_A_0560_108 ?YYMMDD?. Q1
SCALE: NTS
Q1
ISSUED
COUNTERTOP DEPTH
MARK
CABINET DEPTH - 2'-0" UON
1"
9
EN . 08 - 3 1 - 1 O F OF CAL I
12 A-561
1.
10
R E
PROJECT
TYP BASE CAB, UON
TYP CASEWORK FASTENER PER
T
A
11 A-561
10 A-561
C23603 ST
10 A-561
CENTER ANCHORAGE NOT REQUIRED FOR CABINET LESS THAN 6' HIGH
EQ
CABINET
TYP UPPER CAB, UON
CT Y R RT
LI J ON C
84" AFF
N
9 A-561
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
1"
SCRIBE TO WALL
9 A-561
2 1/8"
4"
COUNTER TOP, SEE PLANS
5MM BORED HOLES @ 32 MM CENTERS TYP 13 A-561
ADJUSTABLE SHELVES THROUGHOUT. SHELVES SHALL BE 3/4" MELAMINE COVERED MDF BOARD VARIES
CABINET FRAME
CABINET BACK
18 A-521
COUNTERTOP ANCHORAGE - TYP
TYP. TOPS & BACKSPLASH SHALL BE HIGH PRESSURE LAMINATE COVERED 3/4" MDF BOARD
10 A-561
3" = 1'-0"
Q1
NOTE: ALL WOOD MEMBERS IN CONTACT WITH CONCRETE SHALL BE PRESERVATIVE TREATED. FASTENERS INTO PRESERVATIVE TREATED WOOD SHALL BE HOT DIPPED GALVANIZED STEEL OR STAINLESS STEEL
24" MAX.
2 1/8"
4"
11 A-561
#10 x 2 1/2" @ 16" O.C. MAX
TYPICAL DOORS, DRAWERS, EXPOSED PANELS, ETC SHALL BE HIGH PRESSURE LAMINATE COVERED 3/4" MDF BOARD W/ MATCHING PVC EDGE BANDING TYPICAL THROUGHOUT TYPICAL CABINET INTERIORS SHALL BE MELAMINE (LOW PRESSURE LAMINATE) COVERED 3/4" MDF BOARD W/ PVC EDGE BANDING TO MATCH EXPOSED LAMINATE COLOR. SHELF PVC EDGE BANDING TO MATCH MELAMINE
TYPICAL CASEWORK FASTENER TO 13 CONCRETE PER A-561
OF ROOM BASE
A
3"
1/4" PREFINISHED MELAMINE BACKS
TITLE
DETAILS - CASEWORK
12 A-561
CL
SAME BASE FINISH AS ROOM
5/15/2019 3:48:38 PM
SHEET
12
017294 ?00.00.00? LIONAKIS 2017
AGENCY
2'-10"
11
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
2 1/8"
BACKING, SEE
MATCH HEIGHT
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
TYPICAL PULLS UNO
MANAGEMENT
MAX.
TYP CASEWORK FASTENER PER
B
1/2" PREFIN MELAMINE BACKS SEE INTERIOR ELEVATION
CL 1 1/2"
DIM POINT
LOWER CASEWORK ANCHORAGE
16
3" = 1'-0"
Q1
A-561
TYPICAL CASEWORK SECTION 1 1/2" = 1'-0"
Q1
2
3
4
5
--
FLOORS OR LANDINGS ON EACH SIDE OF EXIT DOORS SHALL NOT EXCEED ½” FROM THE TOP OF THE DOOR THRESHOLD TO THE FLOOR OR LANDING SURFACE ON EITHER SIDE OF THE DOOR ASSEMBLY.
REFER TO ELEVATION TYPE C FOR DIMENSIONAL INFORMATION AND APPLICABLE DETAILS. FINISH PER SPECIFICATIONS TO MATCH STOREFRONT FRAMING
HM HM
7'-0" 7'-0"
---
GL GL
FW1 FW1
HM HM
---
GL GL
13/A-542 13/A-542
10/A-542 6/A-542
8/A-542 8/A-542
3.
EXITS AND EXIT ACCESS DOORS SHALL BE MARKED BY AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY DIRECTION OF TRAVEL.
DG1 DV2 DV2 DG2 DG2 DV2 DV2 DV2 DV2 DV2 DV2 DV2 DV2 DV2 DV2 DV2 DV2 DF1 DF1 DF1 DF1 DV2 DV2 DG2 DV2 DG2 DV2 DV2 DV2 DV2 DV2 DV2 DV2 DV2 DV2 DG1 DG1 DF1
3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"
HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM
7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0" 7'-0"
---------------------------------------
GL GL GL GL GL GL GL GL GL GL GL GL GL GL GL GL GL ----GL GL GL GL GL GL GL GL GL GL GL GL GL GL GL GL --
FW1 FB1 FB1 FG1 FG1 FB1 FB1 FB1 FG1 FG1 FG1 FG1 FG1 FG1 FG1 FG1 FG1 FB1 FB1 FB1 FB1 FB1 FG1 FG1 FG1 FG1 FG1 FB1 FB1 FB1 FB1 FB1 FB1 FB1 FB1 FW1 FW1 FB1
HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM
---------------------------------------
GL --GL GL --GL GL GL GL GL GL GL GL GL GL -----GL GL GL GL GL --------GL GL --
9/A-542 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 9/A-542 1/A-522 9/A-542 1/A-522 9/A-542 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 1/A-522 5/A-542 5/A-542 9/A-542
6,10/A-542 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 6,10/A-542 2/A-522 6,10/A-542 2/A-522 6,10/A-542 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 2/A-522 6/A-542 6/A-542 10/A-542
8/A-542
4.
THE FORCE FOR PUSHING OR PULLING OPEN INTERIOR SWINGING EGRESS DOORS, OTHER THAN FIRE DOORS, SHALL NOT EXCEED 5 POUNDS. FOR OTHER SWINGING DOORS, AS WELL AS SLIDING AND FOLDING DOORS, THE DOOR LATCH SHALL RELEASE WHEN SUBJECTED TO A 15 POUND MAXIMUM FORCE
5.
LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED AND WHICH ARE IN THE PATH OF TRAVEL SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE HARDWARE, PANIC BARS, PUSH-PULL ACTIVATING BARS OR OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP, PINCH OR TWIST THE OPENING HARDWARE
6.
THE BOTTOM 10” OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING DOORS SHALL HAVE A SMOOTH UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. WHERE NARROW FRAME DOORS ARE USED, A 10” HIGH SMOOTH PANEL SHALL BE INSTALLED ON THE PUSH SIDE OF THE DOOR, WHICH WILL ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION.
7. 8.
COORDINATE OVERALL DOOR FRAME DEPTHS WITH WALL TYPES.
9.
FOR DOOR HARDWARE GROUPS, SEE PROJECT SPECIFICATIONS.
8/A-542
11. FOR SIGNAGE ON OR ADJACENT TO DOORS, SEE SHEET SERIES G-100.
8/A-542
12. GLASS DOORS, SIDELIGHTS, AND GLAZED OPENINGS WITHIN 18” OF THE FLOOR OR WITHIN 24” HORIZONTALLY OF ANY DOOR OPENING SHALL BE FULLY TEMPERED GLASS APPROVED FOR IMPACT HAZARD.
2'-5 1/2"
T
T
CL C 2'-0" L
6'-1 1/4"
T
3'-10 3/4"
CL
CL 2'-6" 5'-0" 2'-6"
CL 2'-0"
4'-0"
CL CL 2'-6" 5'-0" 2'-6"
T
CL
T
T
T
T
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
T
T
T
T
T
T
T
T
T
T
T
T
1.
NOT USED
2.
INSULATED PANELS @ SPECIFIC LOCATIONS AS INDICATED (SHADED) ON EXTERIOR BUILDING ELEVATIONS.
3.
DIMENSIONS SHOWN FOR HOLLOW METAL FRAME TYPES ARE ROUGH OPENING DIMENSIONS. FIELD VERIFY ACTUAL SIZE OF FRAMED CONSTRUCTION PRIOR TO ASSEMBLY OF FRAMES.
4.
LOUVER SIZES TO BE COORDINATED W/ MECH DWG REQUIREMENTS.
5.
PROVIDE WINDOW TREATMENT (MECHO SHADES) TO COVER FULL WIDTH OF GLAZED OPENING. SEE A-641 FOR LOCATIONS.
6.
ALL INTERIOR HM DOORS & INTERIOR FACES OF EXTERIOR HMF DOORS SHALL BE PAINTED P5 UNO.
7.
ALL EXTERIOR HM DOOR FACES SHALL BE PAINTED P8 UNO.
8.
ALL INTERIOR HMF DOOR AND WINDOW FRAMES TO BE PAINTED P7 UNO.
9.
ALL EXTERIOR HMF DOOR FRAMES TO BE PAINTED P8 AT THE EXTERIOR AND P7 AT THE INTERIOR UNO.
SEAL D A RCH SE I E N A N McM TE H U T A
C23603 T
R E
EN . 08 - 3 1 - 1 O F OF CAL I
PROJECT
TEHAMA CENTER STUDENT SERVICES
LEVEL 1 100'-0" 17 A-541
12 A-541
16 A-541
HEAD
MULLION
SILL
17 A-541
18 A-541
12 A-541
HEAD MULLION
JAMB (PLASTER)
16 A-541
18 A-541
SILL
JAMB (PLASTER)
12 A-541
11 G-513
8 A-542
5 A-541
12 A-541
12 A-541
12 A-541
16 A-541
17 A-541
10 A-541
SIGNAGE
THRESHOLD
DOOR HEAD
DOOR JAMB, SIM.
VERT MULLION
HORIZ MULLION
SILL
HEAD
JAMB (SIDING)
12 A-541
16 A-541
VERT HORIZ MULLION MULLION
SILL
17 A-541
10 A-541
HEAD
JAMB (SIDING)
18 A-541
JAMB (PLASTER)
JAMB HORIZ MULLION
12 A-541
13 A-541
15 A-541
14 A-541
VERT HEAD MULLION
SILL
JAMB
2'-6"
14 A-541
20 A-541
20 A-541 12 A-541
JAMB
SILL
CL
4'-0"
4'-0"
VERT MULLION
14 A-541
12 A-541
SILL
13 A-541
15 A-541
WALL PERP TO MULLION 14 PER PLAN 20 A-541 A-541
VERT HEAD MULLION
SILL
JAMB
12 A-541
JAMB HORIZ MULLION
STOREFRONT WINDOW SYSTEM
3" / 1
EQ
CL
TYP.
2"
EQ
7 A-542
CL
17 3" / A-542 12"
18 A-542
13 A-542
13 A-542
H
5'-1"
5'-1"
CL CL MECHANICAL LOUVER SYSTEM
4'-9"
CL
CL
EQ
EQ
TYP.
STOREFRONT WINDOW SYSTEM
1 A-541
18 A-541
SILL
HEAD
JAMB 14 A-541
VERT MULLION
20 A-541 12 A-541
2'-6" 5'-1" 2'-8"
5'-1"
CL 16 MECHANICAL LOUVER SYSTEM A-542 H
STOREFRONT WINDOW SYSTEM
CL J
F
17 EQ A-542
EQ
G
18 A-542
17 A-542
12 A-542
19 A-542
19 A-542
20 A-542
20 A-542
2'-8"
CL J
3" / 1
18 A-542
13 A-542
2'-7 1/2" 2'-6" 16 CL CL CL CL A-542 20 MECHANICAL LOUVER A-542SYSTEM
CL 15 A-542
11 A-542
2'-7 1/2"
2" 3 " / 12 "
EQ TYP.
CL
17 A-542
EQ
CL 2 3" / 1
TYP. 2" 3" / 1
DG1
"
18 A-542 13 A-542 19 A-542
4'-8"
H
MECHANICAL LOUVER SYSTEM
5'-1" 4'-9"
5'-1"
5'-1"
CL CL LOUVER SYSTEM MECHANICAL MECHANICAL LOUVER SYSTEM REV. HREV.
18 A-541
SILL
HEAD
JAMB
CL
DOOR CONFIGURATION F = FLUSH G = GLASS V = VISION L = LOUVER D = DUTCH J = DETENTION S = SLIDER O = OVERHEAD C = COUNTER A = ACCORDION P = STRIP CURTAIN
17 A-542 18 A-542 13 A-542 19 A-542 CLERESTORY 119'-0"
5'-1"
CL
20 A-542
20 A-542
2"
SEE SCHED
1'-8"
DF1A
SEE SCHED
2"
DG2
FB1
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
FG1
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 ?00.00.00? LIONAKIS 2017
AGENCY
VERSION VARIATION A = VARIATION A B = VARIATION B ETC.
FRAME PROFILE (AT DOOR ONLY) F = DOUBLE RABBET (TYP) R = SINGLE RABBET E = DOUBLE EGRESS C = CASED P = POCKET
2"
FRAME CONFIGURATION B = BASIC THREE-SIDED T = TRANSOM G = GLASS LITE V = VISION LITE W = TRANSOM W/ GLASS LITE X = TRANSOM W/ VISION LITE J = DETENTION P = PARTIAL TWO-SIDED Q = FOUR-SIDED CONFIGURATION VERSION 1 = VERSION 1 2 = VERSION 2 ETC.
SEE SCHED 2"
2"
SEE SCHED
SEE SCHED
BOT GLAZ
+ 43" MAX
SEE SCHED.
FIN FLR
DATE 01/04/2019 05/17/2019
FRAME TYPE SYMBOL KEY
2"
SEE SCHED
CLERESTORY 119'-0"
2'-8"
2"
8"
MARK
CONFIGURATION VERSION 1 = VERSION 1 2 = VERSION 2 ETC.
8"
8"
ISSUED
DOOR TYPE SYMBOL KEY
2"
2"
2" 1'-0" 2"
2"
SEE SCHED.
8" 8" 1'-0"
SEE SCHED.
8" SEE SCHED.
DF1
1 A-541
FRAME TYPES
SEE SCHED. 8"
WALL PERP TO MULLION PER PLAN
19 A-541
STOREFRONT WINDOW SYSTEM
15'-3" 24'-8"
A 8"
11 A-541
DOOR TYPE D = DOOR S = SLIDER
STOREFRONT WINDOW SYSTEM
EQ
FINISH ANOD = ANODIZED FRP = FIBER REINFORCED PLASTIC PLAM = PLASTIC LAMINATE PT = PAINT ST = STAIN
SILL
8'-10" 8'-8"
CL
MATERIAL ALUM = ALUMINUM DHM = DETENTION HOLLOW METAL HM = HOLLOW METAL SST = STAINLESS STEEL WD = WOOD
3'-0"
10'-0"
CL
12 A-541
2" 1'-0" 2"
8"
4'-0"
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
CLERESTORY 119'-0"
LEVEL 1 100'-0"
JAMB
"
14 A-542
5'-1" 20 A-542
SEE SCHED.
CL
4'-0"
CLIENT
GLASS LEGEND NOTES: 1. SEE SPECS FOR GLASS TYPS NOTED
DOOR TYPES
SEE SCHED.
CL
CL T
19 A-541
SILL
7 A-542
TYP.
12 A-542
4'-8"
G
15'-7" 17 CL A-542
EQ
CL
2 3" / 1
14 A-542
11 A-542
CL
1'-0"
5/15/2019 3:48:39 PM
CL
TYP.
18 A-542
5'-1"
E
15'-3"
2" 3" / 1
SEE SCHED.
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
24'-8"
CL
4'-0"
HORIZ MULLION
STOREFRONT WINDOW SYSTEM
F
4'-1"
CLERESTORY 119'-0"
HORIZ MULLION E
CL
4'-0"
3'-0"
T 11 A-541
12 A-541
STOREFRONT WINDOW SYSTEM
WINDOW CANOPY AT SIDING
2'-11"
CL
4'-0"
(E) = EXISTING ADO = AUTOMATIC DOOR OPERATOR ADC = AUTOMATIC DOOR CLOSER CR = CARD READER EL = ELECTRIC LOCK HDW GP = HARDWARE GROUP HO = HOLD OPEN PH = PANIC HARDWARE V = VINYL STRIPS GLASS LEGEND: GL = GLASS LG = LEADED GLASS RG = RATED GLASS SG = SPANDREL GLASS
WINDOW CANOPY AT PLASTER
19 A-514
CL
3'-0"
T
B 14 A-541
2'-0"
CL
9'-0"
T
LEVEL 1 100'-0" 12 A-541
CL
4'-0"
4'-1"
CL CL T
2'-4"
CL
2'-0" 4'-0" 3'-0"
T
2'-0" 2'-4" 9'-0" WINDOW CANOPY AT SIDING C C C 2'-3" L 2'-3" L 2'-3" L 2'-3"
2'-11"
C C C 2'-3" L 2'-3" L 2'-3" L 2'-3"
19 A-514
3'-0"
2'-6"
18 A-514
9'-0"
2'-0"
D
CL
2'-4"
WINDOW CANOPY AT PLASTER
4'-0"
9'-0"
18 A-514
3'-0"
2'-4"
STOREFRONT AND WINDOW SYSTEM
C
10'-0"
2'-0"
STOREFRONT WINDOW SYSTEM
B
2'-0"
B
STOREFRONT WINDOW SYSTEM
770 DIAMOND AVE RED BLUFF, CA 96080
LEGEND
18 A-541
JAMB (PLASTER) A
07/03/2019
DOOR SCHEDULE SHEET NOTES
8/A-542 8/A-542
10'-0"
10'-0"
T
✔
14. COORDINATE THE SIZE AND LOCATION OF RECESSES IN CONCRETE FLOORS FOR RECESSED DOOR HARDWARE.
CL T
3'-0"
CL
T
ACS
✔
13. PROVIDE RATED GLASS AT RATED DOORS AND FRAMES WITH LITES. SEE DOOR SCHEDULE AND PROJECT SPECIFICATIONS.
T
T
DATE:
FLS
8/A-542
CL
10'-0"
4'-6 1/2"
CL
T
SS
10. FOR SIGNAGE LOCATIONS, SEE SIGNAGE PLANS.
10'-0"
CL
6'-1 1/4"
REVIEWED FOR ✔
IA
CL C 2'-0" L
3'-10 3/4"
INC:
N
CL
4'-0"
APP. 02-117123
9
C 2'-0" L
CL C EQ 2'-6" L 2'-0"
DOOR AND FRAME ASSEMBLY DIMENSIONS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION AND INSTALLATION.
8/A-522 12/A-522 12/A-522 8/A-522
36'-0"
2'-5 1/2" 4'-6 1/2" 3'-0"
2.
CT Y R RT
T
COMMENTS
A
T
THRESHOLD
3'-0" 3'-0"
CL C EQ L 2'-6" 2'-0"
CL C 2'-6" EQL 2'-2"
JAMB
R
HEAD
GENERAL DOOR SHEET NOTES ARE TYPICAL UNLESS NOTED OTHERWISE.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
ST
T
GL
GL
7'-9" 9'-0"
C
T
FINISH
1.
DG1 DG1
8'-10" 9'-4" 8'-6"
CL 2'-2" EQ 2'-6"
MATL
CL
02 02 101 03 105 103 104 103 103 103 103 103 103 103 103 103 103 103 103 103 108 106 107 106 102 05 104 04 104 03 102 102 102 102 102 102 102 102 03 03 06
--
TYPE
10'-0"
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
ALUM
GL
CL
D
HALLWAY HALLWAY CLASSROOM/LOBBY OVERFLOW CANOPY ADMIN OFFICE STUDENT SERVICES ADMIN OFFICE FACULTY OFFICE STUDENT SERVICES STUDENT SERVICES STUDENT SERVICES FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE WORK CENTER CUSTODIAL STORAGE IDF VET OFFICE VET OFFICE VET CENTER VET CENTER CONFERENCE CONFERENCE COUNSELOR CAMPUS SAFETY COUNSELOR COUNSELOR COUNSELOR COUNSELOR COUNSELOR COUNSELOR FACULTY HALLWAY FACULTY HALLWAY FIRE RISER
HEIGHT FINISH
4'-6 1/2"
100B 100D 101A 101B 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122A 122B 123A 123B 124A 124B 125 126 127 128 129 130 131 132 150A 150B 151
01
MATL
CL
0
TYPE
2'-5 1/2"
LOBBY
LEAF 2 WIDTH TYPE WIDTH
4'-6 1/2"
100A
HDW GP
FRAMES
3'-0"
LOCATION
DOORS
2'-5 1/2"
DOOR NO
FIRE RATING (MINS)
DOOR SCHEDULE GENERAL NOTES
3'-0"
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
1"
DOOR AND FRAME SCHEDULE
LI J ON C
2"
1
FIN FLR
FW1
DV2
FB1M
VERSION VARIATION A = VARIATION A M = VARIATION W/ MULLION R = VARIATION W/ REMOVABLE MULLION ETC.
TITLE
SCHEDULES / DIAGRAMS - DOORS & WINDOWS SHEET
A-621
2"
1
2
3
ROOM FINISH SCHEDULE
D
100 100A 100B 100C 100D 100E 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 150 151
ROOM NAME LOBBY WORK CENTER HALLWAY HALLWAY HALLWAY ENTRY TOWER CLASSROOM/LOBBY OVERFLOW ADMIN OFFICE STUDENT SERVICES ADMIN OFFICE FACULTY OFFICE STUDENT SERVICES STUDENT SERVICES STUDENT SERVICES FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE RESTROOM CUSTODIAL STORAGE IDF VET OFFICE VET CENTER CONFERENCE COUNSELOR CAMPUS SAFETY COUNSELOR COUNSELOR COUNSELOR COUNSELOR COUNSELOR COUNSELOR FACULTY HALLWAY FIRE RISER
F1 C1 F1 F1 F1 SP5 F1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 SF1 SP5 SP5 RT1 F1 F1 F1 C1 C1 C1 C1 C1 C1 C1 C1 F1 SP5
B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B2 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 PL4 P2 P2 PL4 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P1
5 5 5 5 5 5 5 W1 5 5 W1 W1 5 5 5 5 5 5 5 5 5 5 6 6 5 5 5 5 5 5 5 W1 W1 5 5 W1 W1 5 5
P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 PL4 P2 P2 PL4 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P1
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 PL4 P2 P2 PL4 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P1
5 5 5 5 5 5 5 5 5 W1 5 5 W1 W1 W1 W1 W1 W1 W1 W1 W1 W1 6 6 5 5 5 5 5 W1 W1 5 5 W1 W1 5 5 5 5
P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 PL4 P2 P2 PL4 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P1
CC1 5 5 CL1 CL1 6 CC1 CL1 5 5 CC1 CC1 CC1 CC1 CC1 CL1 CC1 CL1 CL1 CL1 CL1 CL1 CL1 5 5 5 5 CL1 CL1 CL1 CL1 CL1 CL1 CL1 CL1 CL1 CL1 CL1 SP7 6
P1 P1 P1 P1 P1 CL2 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 CL2 CL2 CL2 CL2 CL2 CL2 CL2 CL2 CL2 CL2 CL2 CL2 P1
GENERAL NOTES
INTERIOR FINISH LEGEND
FLOOR NORTH EAST SOUTH WEST CEILING CASEWORK WINDOW INTERIOR TYPE COVERING ELEVATION MATL FIN BASE MATL FIN MATL FIN MATL FIN MATL FIN MATL FIN 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
5
2 1
SP8 SP9 SP9
SP8,SP9 SP8 SP89 SP8,SP9 SP8,SP9 SP9 SP9 SP9 SP8 SP8 SP8 SP8 SP8 SP8 SP8 SP8 SP8
FINISH CODE
MANUFACTURER
TYPE / STYLE, COLOR, SIZE
NOTES
1.
A-221 CARPET C1 C2
A-222
2. CARPET TILE: SHAW CARPET TILE: SHAW
RESILIENT TILE RT1 VPI
FOCUS 59455, 'MEDITATE 54761" BON JOUR II 57032, "TOBACCO 31150"
24" TILES, 1/4 TURN INSTALLATION 24" TILES, 1/4 TURN INSTALLATION
SHEET FLOORING SF1 LINOLEUM: FORBO
MARMOLEUM CONCRETE, 3728/372835, "KAOLIN"
PAINT P1 P2 P3 P4 P5 P6 P7 P8
SHERWIN-WILLIAMS SHERWIN-WILLIAMS SHERWIN-WILLIAMS SHERWIN-WILLIAMS SHERWIN-WILLIAMS SHERWIN-WILLIAMS SHERWIN-WILLIAMS SHERWIN-WILLIAMS
0050 - CLASSIC LIGHT BUFF 9180 - AGED WHITE 6122 - CAMELBACK 7705 - WHEAT PENNY 0077 - CLASSIC FRENCH GRAY 7066 - GRAY MATTERS 6994 - GREENBLACK 0015 - GALLERY GREEN (MATCH EXISTING CAMPUS)
108/A-222 109/A-222
BASE B1 B2
BURKE SELF-COVING BASE SF1
TS-CP, "BLACK", 4" 6"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
IF AT ANY TIME THE GENERAL CONTRACTOR REQUIRES CLARIFICATION OF FINISH LOCATIONS, CONTACT PROJECT ARCHITECT PRIOR TO FINISH APPLICATION.
APP. 02-117123
CEILING FINISHES SHALL BE IN COMPLIANCE WITH TABLE 803.9 (HC REFERENCE CEILING F FINISHES SHALL BE IN COMPLIANCE WITH TABLE 1224.4.11)
4.
WALL AND CEILING MATERIALS SHALL NOT EXCEED THE ALLOWABLE FLAME SPREAD CLASSIFICATION IN APPLICABLE CODE, CLASS A
5.
INTERIOR WALL AND CEILING FINISHES FOR ALL ROOMS AND ENCLOSED SPACES IN 1-2.1 OCCUPANCY, INCLUDING EXIT ENCLOSURES AND CORRIDORS SHALL BE CLASS B WITH FLAME SPREAD 26 TO 75.
INC:
REVIEWED FOR
ALL INTERIOR FINISHES SHALL COMPLY WITH CBC SECTION 803 (INTERIOR FINISHES) (HC REFERENCE CBC SECTION 1224.4.11); FLOOR FINISH SHALL BE SMOOTH, WASHABLE AND DURABLE IN ALL PROCEDURE TYPE AREAS
3. STATMATE STATIC CONTROL TILE, 16, "CLOUD"
A-222
A-411 A-411
SP8 SP8 SP8 SP8 SP8 SP8 SP8 SP8 SP8 SP8 SP8 SP8
INTERIOR FINISH REMARKS
SS
✔
DATE:
FLS
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com MANUFACTURED INSIDE AND OUTSIDE CORNERS
CEILING FINISHES CL1 ARMSTRONG CL2
2'x2' SUSPENDED ACOUSTICAL LAY-IN CEILING TILE, ULTIMA HIGH NRC 1910 2'x2'x3/4" SQUARE EDGE PAINTED GYPSUM BOARD
CEILING COMBINATION CC1 CC2 CC3
CL1 AND GYP WITH P1 CL1 AND GYP SOFFITS CL1, CL3, AND GYP SOFFITS
PLASTIC LAMINATE PL1 WILSONART PL2 WILSONART PL3 WILSONART PL4 WILSONART
4667-60, "GREEN TIGRIS" 7909-60, "FUSION MAPLE" 1695-60, "BLACK" 4823-60, "ANTIQUE BRUSH"
SPECIALTY PRODUCTS AND FINISHES SP1 SOLID SURFACING: CORIAN SP2 FRP: MARLITE FRP SP3 SP4 SP5 SP6 CARNEGIE XOREL FABRIC SP7 HARDI-SOFFIT
"NIGHT SKY" P118, "NATURAL ALMOND", PEBBLED SURFACE PLYWOOD PAINTED P1 PLYWOOD PAINTED P7 CONCRETE SEALER #6619 QUARRY, COLOR "F94" PAINT TO MATCH EXTERIOR SOFFIT
CONSULTANT
SEAL D A RCH SE I E N A N McM TE H U T A
CT Y R RT
LI J ON C
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
1"
NO
4
N
EN . 08 - 3 1 - 1 O F OF CAL I 9
A
R E
R
ST
T
IA
C23603
PROJECT
C
TEHAMA CENTER STUDENT SERVICES 770 DIAMOND AVE RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
FLOOR PATTERNS AND COMBINATIONS
WALL PATTERNS AND COMBINATIONS
INTERIOR FINISH REMARKS
ISSUED
MARK NOTES
NOTES
1.
1.
SEE FLOOR FINISH SHEET A-131 FOR FINISH CLARIFICATION.
F1 CARPET: COMBINATION OF C1 AND C2
SEE ELEVATIONS A-221 THROUGH A-222 WHEN WALL COMBINATIONS ARE USED IN SCHEDULE FOR CLARIFICATION.
W1 SP6 OVER TACKABLE WALL PANEL TO 9'-6" WITH P1 ABOVE
1.
SEE REFLECTED CEILING PLAN FOR CLARIFICATION ON CEILING TYPES AND FINISH.
2.
SEE INTERIOR ELEVATIONS FOR FINISH CLARIFICATION AND LOCATION.
3.
COLUMNS SHALL BE PAINTED P1 ON ALL SIDES UNO.
4.
WRAP ALL EXPOSED SURFACES OF SOFFIT WITH ACCENT PAINT.
5.
WRAP ALL SIDES OF WALL WITH ACCENT PAINT.
6.
PAINT ELECTRICAL PANEL DOORS AND FIRE EXTINGUISHER CABINETS TO MATCH ADJACENT WALL UNO.
7.
PROVIDE 3/4" FIRE-TREATED PLYWOOD ON ALL WALLS. INSTALL THE PLYWOODS STARTING AT 6" AFF TO 8'-6" AFF. (IDF ROOM)
8.
FLOORING AND COVED BASE SHALL HAVE WELDED SEAMS TO MATCH DARKEST ADJACENT FLOORING.
9.
NOT USED.
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
B 10. NOT USED. 11. PAINT ALL EXPOSED DUCTS, PIPING, CONDUIT, STEEL, FRAMING, METAL DECK, ETC P1, UNO.
MANAGEMENT
C:\Users\dan.eitman\Documents\_RevitLocalFiles\017294_A_BIM_A-MASTER_R18_CENTRAL_dan.eitman@lionakis.com.rvt
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
A
CASEWORK LEGEND AND NOTES
WINDOW COVERING LEGEND & NOTES
MATERIAL CODES
NOTES
NOTES
1.
CASEWORK TO BE TYPE 1, UNO.
1.
2.
PROVIDE CASEWORK LOCKS AS NOTED ON THE INTERIOR ELEVATIONS. (COORDINATE CASEWORK LOCKS, QUANTITY AND LOCATION WITH OWNER)
PROVIDE WINDOW TREATMENTS IN LOCATIONS NOTED ON INTERIOR ELEVATIONS AND FINISH SCHEDULE. 19 20 A-522 A-522
3.
PROVIDE GROMMETS @ ALL KNEE SPACES. COLOR TO MATCH ADJACENT COUNTER SURFACE, LOCATIONS TBD WITH ARCHITECT IN FIELD.
1.
ROLLER SHADE, SP8, MANUAL OPERATION
4.
ALL CASEWORK SHELVING SHALL BE ADJUSTABLE, UNO.
2.
ROLLER SHADE, SP9, MOTORIZED OPERATION AT CLERESTORY
5.
PLASTIC LAMINATE DUST CAPS TO MATCH ADJACENT VERTICAL LAMINATE, UNO.
1 2 3 4 5 6 7 8 E OTS
6.
COUNTER EDGE BANDING TO BE 3MIL GREENLINE ABS EDGEBANDING, TO MATCH HORIZONTAL SURFACE.
7.
DRAWER AND DOOR EDGE BANDING TO BE 0.018 3 MIL EDGE BANDING TO MATCH VERTICAL SURFACE.
CONCRETE PLYWOOD (DECKING) CONCRETE MASONRY UNIT BRICK GYPSUM WALLBOARD GYPSUM WALLBOARD, WATER RESISTANT EXPOSED STRUCTURE CEMENTITIOUS WALLBOARD EXISTING OPEN TO STRUCTURE
TITLE
TYPE 1 VERTICAL SURFACE: PL2 HORIZONTAL SURFACE: PL4 BASE: PL3
SCHEDULE - INTERIOR FINISHES
TYPE 2 VERTICAL SURFACE: PL4 HORIZONTAL SURFACE: SP1 BASE: PL3
5/15/2019 3:48:39 PM
017294 ?00.00.00? LIONAKIS 2017
SHEET
A-641
CODE ANALYSIS
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1.
GOVERNING CODE:
2016 CALIFORNIA BUILDING CODE
2.
OCCUPANCY TYPE:
GROUP A-3(S1), B(S1). A-3(S1) GOVERNS AS MOST RESTRICTIVE
3.
CONSTRUCTION TYPE: (CBC 506 & TABLE 506.2)
TYPE V-B, WITH AUTOMATED FIRE SPRINKLER SYSTEM ALLOWABLE AREA AND HEIGHT INCREASES NOT UTILIZED
TABULAR ALLOWABLE HEIGHT AND BUILDING AREA: (CBC 504.3, 504.4, 506.2)
OCCUPANCY GROUP
ALLOWABLE BLDG AREA
MAX NO OF STORIES
ALLOWABLE BLDG HT
GROUP A-3(S1)
24,000 SF
1 STORY
60 FT
ACTUAL
OCCUPANCY GROUP
ACTUAL BLDG AREA
MAX NO OF STORIES
ACTUAL BLDG HT
GROUP A-3B(S1)
8,964 SF
1 STORY
35 FT
8,964 SF
4.
5.
6.
DETAILED ALLOWABLE BUILDING AREA DETERMINATION (CBC 506.2)
ACTUAL AREA
7.
FIRE RESISTIVE REQUIREMENTS: (CBC TABLE 601)
STRUCTURAL FRAME 0 HR BEARING WALLS - EXTERIOR 0 HR BEARING WALLS - INTERIOR 0 HR NON-BEARING WALLS & PARTITIONS - EXTERIOR 0 HR (BASED ON FIRE SEPARATION DISTANCE OF 10 FT < X = 0 HR) NON-BEARING WALLS & PARTITIONS - INTERIOR 0 HR FLOOR CONSTRUCTION 0 HR ROOF CONSTRUCTION0 HR SHAFT ENCLOSURES (CBC 713) 0 HR PROJECTIONS 0 HR EXTERIOR DOORS AND WINDOWS UNPROTECTED, NO LIMIT (CBC 705.8.1 EX 2, NON-RATED EXTERIOR WALLS AND STRUCTURAL FRAME) CORRIDORS N/A
8.
OCCUPANT LOADS: (CBC TABLE 1004.1.2)
TOTAL:
214 OCCUPANTS
9.
TOTAL EGRESS WIDTH: (CBC 1005)
LOBBY EXIT: HALLWAY EXITS:
REQ'D: 49 OCCUPANTS x 0.2" = 9.8" REQ'D: 30 OCCUPANTS x 0.2" = 6"
AREA OF FIRE SPRINKLER PROTECTION SYSTEM
<
24,000 SF
PROVIDED: 72" PROVIDED: 36"
10. COMMON PATH OF EGRESS TRAVEL: (CBC TABLE 1006.2.1)
TWO EXITS OR EXIT ACCESS DOORWAYS FROM A SPACE SHALL BE PROVIDED WHERE THE COMMON PATH OF TRAVEL EXCEEDS 75'-0"
11. FIRE FLOW REDUCTION (CFC TABLE B105.1) -
FIRE FLOW CALCULATION AREA: CONSTRUCTION TYPE AREA FIRE FLOW (GALLONS PER MINUTE)
-
-
-
-
-
TYPE V-B 7,701-9,400 SF 2,500 REQ'D
=
75% 1,875 REQ'D
(CFC TABLE B105.2)
-
REDUCTION FOR FULLY-SPRINKLERED BUILDING (% REQ'D)x(FIRE FLOW) = (75%)x(2500)
(CFC TABLE C102.1)
-
REQUIRED NUMBER AND SPACING OF FIRE HYDRANTS: FIRE FLOW REQUIREMENTMINIMUM NUMBER OF HYDRANTS AVERAGE DISTANCE BETWEEN HYDRANTS: MAX. DISTANCE FROM ANY POINT ON THE STREET OR ROAD FRONTAGE TO A HYDRANT -
1,875 2 HYDRANTS 450 FEET 225 FEET
APP. 02-117123
INC:
REVIEWED FOR SS
✔
DATE:
FLS
✔
07/03/2019
ACS
✔
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
INC:
REVIEWED FOR SS
✔
DATE:
FLS
✔
07/03/2019
ACS
✔
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
INC:
REVIEWED FOR SS
✔
DATE:
FLS
✔
07/03/2019
ACS
✔
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
Model 1000
TESTan DRAIN
®
300 PSI Bronze Ball Valve
Model 1000 - Plan View
Front View - Horizontal Install E
A
F
B
S21 (typ)
TO DRAIN
Joist MFR
TO DRAIN D
H
G
C
Dimensions
Materials
Orifice Size Available: Wood joist or beam. Attachment to I-Joist per MFR Detail S26
3⁄8", 7⁄16", 1⁄2", 17⁄32",
ELO
(5⁄8")*,
ESFR
(3⁄4")*,
FROM BRANCH E
& K25**
SIZE
A
B
C
D
¾"
51⁄16" (128 mm)
11⁄2" (37.5 mm)
23⁄16" (57 mm)
35⁄8" (93 mm)
33⁄8"SYSTEM 113⁄16 " 49PORT ⁄16" ACCESS (86 mm) (46 mm) (117 mm)
63⁄8" (162.5 mm)
1"
51⁄16" (128 mm)
11⁄2" (37.5 mm)
23⁄16" (57 mm)
35⁄8" (93 mm)
33⁄8" (86 mm)
113⁄16"
49⁄16" (117 mm)
63⁄8" (162.5 mm)
11⁄4"
57⁄16" (163 mm)
111⁄16" (43 mm)
29⁄16" (65 mm)
41⁄4" (108 mm)
35⁄16" (83 mm)
115⁄16" (51 mm)
59⁄16" (141 mm)
51⁄2" (192 mm)
1½"
67⁄16"
113⁄16" (45 mm)
31⁄4"
(81.5 mm)
51⁄16"
(127 mm)
37⁄8"
(99 mm)
25⁄8"
(67 mm)
81⁄4"
(207 mm)
107⁄8"
(274 mm)
67⁄16" (163 mm)
113⁄16" (45 mm)
31⁄4" (81.5 mm)
51⁄16" (127 mm)
37⁄8" (99 mm)
25⁄8" (67 mm)
81⁄4" (207 mm)
107⁄8" (274 mm)
2"
1/2” NPT SYSTEM ACCESS PORT
(163 mm)
STREET EL
F
G
(46 mm)
STREET EL * Available on 11⁄4" to 2" size units only OR PIPE ** Available on 11⁄2" and 2" size units only
H
Handle: Steel Stem: Rod Brass Ball: C.P. Brass Body: Bronze Valve Seat: Impregnated Teflon® Indicator Plate: Steel Handle Stop: Steel
Approvals UL and ULC Listed (EX4019) FM Approved NYC-BSA No. 720-87-SM
TO DRAIN
TO DRAIN … The Model 1000 provides all of the following
From the 2007 Edition of NFPA 13 Chapter 8.16.2.4.1* Provisions shall be made to properly drain all parts of the system. Chapter 8.16.2.4.2 Drain connections, interior sectional or floor control valve(s) – shall be provided with a drain connection having a minimum size as shown in Table 8.16.2.4.2. & 8.16.2.4.3 Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling the flow of the drain. Chapter A.8.17.4.2 (Wet Pipe System) test connection is permitted to terminate into a drain capable of accepting full flow… using an approved sight test connection containing a smooth bore corrosion-resistant orifice giving a flow equivalent to one sprinkler… Chapter 8.17.4.2.2 The test connection valve shall be readily accessible. Chapter 8.17.4.2.4 shall be permitted to be installed in any location… downstream of the waterflow alarm. Chapter 8.17.4.3.1 (Dry Pipe System) a trip test connection not less than 1" in diameter, terminating in a smooth bore corrosion-resistant orifice, to provide a flow equivalent to one sprinkler… Chapter 8.17.4.3.2 The trip test connection… with a shutoff valve and plug not less than 1", at least one of which shall be brass.
USA Patent # 4741361 and Other Patents Pending AGF Manufacturing Inc.
100 Quaker Lane, Malvern, PA 19355 Phone: 610-240-4900 Fax: 610-240-4906 www.testandrain.com
IMAGE DENOTES PLAN VIEW OF 4-WAY BRACE ATDENOTES TOP OF RISER ASSEMBLE. USE (2X) IMAGE PLAN VIEW OF 4-WAY BRACE AT TOP OF RISER ASSEMBLY. (2X) LATERAL SWAY BRACE LATERAL SWAYUSE BRACE ASSEMBLIES (SEE ASSEMBLIES (SEE BELOW). ATTACH TO BLOCKING BELOW). ATTACH TO BLOCKING W/ 1/2" W/ DIA 1/2" DIA THRU BOLT. BLOCKING TO BE 4X6 MIN W/ A35 THRU BOLT. BLOCKING TO BE 4X6 MIN W/ A35 EACH SIDE, TOP AND BOTTOM EACH SIDE, TOP AND BOTTOM
SWAY BRACE BOLTING TO JOIST FOR LOADS PARALLEL AND PERPENDICULAR
Job Name:__________________________________ Architect:____________________________________ Engineer:____________________________________ Contractor:__________________________________
APP. 02-117123
INC:
REVIEWED FOR SS
✔
DATE:
FLS
✔
07/03/2019
ACS
✔
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
PLUMBING FIXTURE SCHEDULE
PLUMBING LEGEND
G MG HP OF RWL SD
D
T TR WSP
R
8" SQUARE X 6" DEEP FLOOR SINK WITH WHITE ACID RESISTANT PORCELAIN ENAMEL COATED INTERIOR, LOOSE SET PORCELAIN ENAMEL COATED CAST IRON GRATE, ALUMINUM DOME, BOTTOM STRAINER, AND NO HUB OUTLET.
1.
ALL FIXTURES WHITE UNLESS OTHERWISE NOTED.
2.
PROVIDE FLOW CONTROL DEVICES ON LAVS AND SINKS PER T-24, PART 5, CCR.
3.
ALL FIXTURES SHALL BE FURNISHED WITH STOP VALVES. VALVES MAY BE IN SUPPLY PIPES OR INTEGRAL WITH SUPPLY FITTINGS.
4.
PLUMBING CONTRACTOR SHALL COORDINATE ALL PLUMBING LINE LOCATIONS WITH OTHER TRADES.
5.
REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF FIXTURES AND MOUNTING HEIGHTS.
6.
PLUMBING CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND PAY ALL COSTS INVOLVED.
7.
INSULATE HOT & COLD WATER SUPPLY PIPES, STOPS, P-TRAP AND DRAIN LINE AT EACH ADA LAVATORY AND SINK WITH ANTI-MICROBIAL, SEAMLESS, VANDAL RESISTANT PROTECTIVE PIPE COVER "PROWRAP" OR EQUAL.
REVIEWED FOR SS
CAST IRON BODY WITH NICKEL-BRONZE STRAINER
WATTS
FS-710
HB-1
ACORN
8151-SSLF
HOSE BIBB WITH INTEGRAL VACUUM BREAKER,STAINLESS STEEL RECESSED BOX WITH KEY
WALL
STAINLESS STEEL
HB-2
ACORN
8125CR-LF
HOSE BIBB WITH VACUUM BREAKER AND REMOVABLE HANDLE.
ROOF
CHROME PLATED
L-1
AMERICAN STANDARD
0355.012 LUCERNE
LAVATORY, 20-1/2" x 18-1/4", FAUCET HOLES ON 4" CENTERS, AMERICAN STANDARD 1340.105 (0.5 GPM) METERING MIXING FAUCET WITH 605P400 4" BRASS DECK PLATE. SET FAUCET CYCLE TIME AT 24 SECONDS MAXIMUM (0.2 GALLONS PER CYCLE). PROVIDE P-TRAP, SUPPLIES, STOPS AND FLOOR-MOUNTED UPRIGHTS WITH CONCEALED ARM SUPPORTS. ACCESSIBLE.
WALL
INC:
FLS
✔
ACS
✔
✔
07/03/2019
DATE:
VIT. CHINA 1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
MS-1
24" x 24" x 12" HIGH TERRAZZO MOP SINK WITH INTEGRAL SB-900 SERVICEPTOR STAINLESS STEEL CAP (ALL SIDES), INTEGRAL FLOOR
WILLIAMS
FLOOR
TERRAZZO
DRAIN. FURNISH: T-15 VB WALL MOUNTED H & CW FAUCET WITH VACUUM BREAKER, ADJ. WALL BRACE, SPOUT WITH HOSE THREAD, T-35 HOSE & HOSE BRACKET, T-40 MOP HANGER, P-TRAP, SUPPLIES AND STOPS.
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
consulting mechanical and electrical engineers
RD/OFD-1
TP-1
ZURN
Z165
P.P.P
COMBINATION ROOF AND OVERFLOW DRAINS WITH UNDERDECK CLAMP, SUMP RECEIVER AND CAST IRON DOME
P2-500
ROOF
CAST IRON
---
ADJUSTABLE TRAP PRIMER VALVE WITH UNION AND BALL VALVE
---
ED
AMERICAN STANDARD
2467.100 CADET
FLUSH TANK WATER CLOSET, 16-1/2" HIGH, 1.1 GPF, BENEKE 523SS OPEN FRONT WHITE SEAT, SUPPLY AND STOP, FLUSH TANK LEVER HANDLE ON OPEN SIDE OF STALL. ACCESSIBLE.
FLOOR MOUNT
R . T I CH E
AN
M31176 EXP. 12/31/19 TA
WC-1
PROF E SS I ONA L
ME
TE
CH AN I C A
OF C
I NEER
PLUMBING GENERAL NOTES
FLOOR
MATERIAL
FS-1
L
I RN A L I FO
VIT. CHINA
SEAL
EQUIPMENT SCHEDULE SYMBOL
MAKE
NUMBER
A.O. SMITH
DSE-5A
CHRONOMITE
CM-20L/208
DESCRIPTION/TRIM
EWH 1
C
SUPPORT
R NO
ABOVE CEILING AMERICAN DISABILITIES ACT ABOVE FINISH FLOOR ABOVE FINISH GRADE BELOW FINISH FLOOR (GRADE) BALL VALVE CONDENSATE DRAIN CONDENSATE DRAIN DROP CIVIL ENGINEER CAST IRON CLEAN OUT CLEAN OUT TO GRADE COLD WATER COLD WATER DROP/RISER DRY STAND PIPE DRY STAND PIPE RISER EXISTING ELECTRIC WATER HEATER FROM ABOVE FROM BELOW FLOOR CLEANOUT FINISHED FLOOR ELEVATION
DESCRIPTION/TRIM
S
ABC ADA AFF AFG BFF(G) BV CD CD,D CE CI CO COTG CW CW,D/R DSP DSP,R (E) EWH FA FB FCO FFE
NUMBER
A
F
MAKE
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
D
SYMBOL
ER
AV AW
FIRE HOSE CABINET FLOOR MOUNT FIRE SPRINKLER RISER GAS GAS RISER/DROP GRADE CLEANOUT GAS PRESSURE REGULATOR GATE VALVE GAS WATER HEATER HOT WATER HOT WATER DROP/RISER INVERT ELEVATION MIXING VALVE NEW NOT IN PLUMBING CONTRACT OVER FLOW LEADER PRESSURE & TEMP RELIEF VALVE PLUMBING CONTRACTOR PRESSURE REGULATING VALVE POUNDS PER SQUARE INCH ROOF DRAIN RAIN WATER LEADER RAIN WATER LEADER DROP SHUT OFF COCK SHUT OFF VALVE TRAP PRIMER (CONNECTION) TEMPERED WATER TEMPERED WATER DROP/RISER TYPICAL UNDER FLOOR UNDER SLAB VALVE BOX VENT VENT RISER VENT THRU ROOF WALL CLEANOUT SANITARY SEWER SANITARY SEWER DROP WATER HAMMER ARRESTOR WALL MOUNT WET STAND PIPE WET STAND PIPE RISER
SE
A
FHC FM FSR G G,R/D GCO GPR GV GWH HW HW,D/R IE MV (N) NIPC OFL P&TRV PC PRV PSI RD RWL RWL,D SOC SOV TP(C) TW TW,D/R TYP UF US VB V V,R VTR WCO SS SS,D WHA WM WSP WSP,R
REG I ST
0 1/4" 1/2"
1"
APP. 02-117123
SANITARY SEWER (SS) SANITARY VENT (V) COLD WATER (CW) HOT WATER (140° F) (HW) HOT WATER RETURN (140° F) (HWR) COMPRESSED AIR ACID VENT (AV) ACID WASTE (AW) CONDENSATE DRAIN DRAIN LINE FIRE PROTECTION GAS (G) GAS - MEDIUM PRESSURE GAS - HIGH PRESSURE RAIN WATER LEADER OVERFLOW (OF) RAIN WATER LEADER (RWL) STORM DRAIN (SD) TEMPERED WATER (110° F) (TW) TEMPERED WATER RETURN (110° F) (TWR) WET STAND PIPE (WSP) SHUT OFF VALVE IN VALVE BOX GAS PRESSURE REGULATOR POINT OF CONNECTION
IEWH 1
SUPPORT
NOTES
TANK TYPE ELECTRIC WATER HEATER. 5 GALLON CAPACITY; 3 kW ELECTRIC HEATER. 80°F TEMPERATURE RISE WITH 15 GPH RECOVERY, 208 VOLT, 1 PHASE, 14.4 AMPS (125 LBS. OPERATING WEIGHT FILLED)
WALL
-----
INSTANTANEOUS ELECTRIC WATER HEATER WITH 81° F. TEMPERATURE RISE AT 0.35GPM FLOW RATE, DIGITAL MICROPROCESSOR, SET AT 115 DEGREES FAHRENHEIT, 4160 WATTS, 208 VOLT, 1 PHASE, 20 AMPS (5 LBS.)
WALL
----PROJECT
TEHAMA CENTER STUDENT SERVICE
MEP COMPONENT ANCHORAGE NOTE
770 DIAMOND AVE. RED BLUFF, CA 96080
ALL MECHANICAL, PLUMBING AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2016 CBC, SECTIONS 1616A.1.18 THROUGH 1616A.1.26 AND ASCE 7-10 CHAPTER 13, 26 AND 30.
CLIENT
ALL PIPE PENETRATIONS THROUGH ROOF SHALL BE FLASHED SIMILAR TO VTR'S.
9.
ALL SANITARY SEWER VENT PIPE PENETRATIONS THROUGH ROOF SHALL TERMINATE AT A MINIMUM DISTANCE OF 10' FROM ANY FRESH AIR INTAKE.
THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT THE ATTACHMENT NEED NOT BE DETAILED ON THE PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING AND CONDUIT.
10.
MINIMUM LOCAL CONNECTION SIZES SHALL BE MADE IN ACCORDANCE WITH THE SCHEDULE OF CONNECTIONS.
A.
11.
ALL WATER PIPING SIZED IN ACCORDANCE WITH 2016 C.P.C.
12.
GAS PIPING SIZED IN ACCORDANCE WITH TABLE 1216.2, 2016 C.P.C.
13.
ALL WASTE, WATER, FIRE AND STORM DRAIN PIPING SHALL BE STUBBED OUTSIDE BUILDING TO CONNECTION POINT SHOWN. SEE CIVIL DRAWINGS FOR CONTINUATION. PLUMBING CONTRACTOR SHALL MAKE FINAL CONNECTIONS TO SITE PIPING.
14.
COORDINATE ALL TRENCHING WITH GENERAL CONTRACTOR.
15.
ALL HOSE BIBBS SHALL BE 3/4" AND MOUNTED AT 12" ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED. ALL HOSE BIBBS SHALL HAVE A NON-REMOVABLE VACUUM BREAKER.
16.
PLUMBING CONTRACTOR SHALL VERIFY LOCATION AND ADEQUACY OF SIZE AND DEPTH OF EXISTING PLUMBING UTILITIES PRIOR TO COMMENCEMENT OF ANY WORK OR ORDERING ANY MATERIALS.
17.
PROVIDE MATERIALS AND INSTALL IN ACCORDANCE WITH 2016 CALIFORNIA PLUMBING CODE AND STATE CODE REGULATIONS.
18.
SEISMIC SUPPORTS AND BRACING FOR ALL PIPING SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH CBC SECTION 1613A, ASCE7 SECTION 13.6.1 AND NFPA 13 STANDARDS FOR SUPPORT AND ANCHORAGE. METHODS AND MATERIALS PUBLISHED BY SMACNA AND APPROVED BY STATE AGENCIES SHALL BE USED.
19.
THE CONDENSATE DRAIN RECEPTACLE (CDR) AND ASSOCIATED WASTE AND VENT PIPING IS NOT REQUIRED AT SITES WHERE THE ROOF DRAINS CONNECT TO A STORM DRAIN SYSTEM. CD LINES FROM ROOFTOP MECHANICAL EQUIPMENT MAY SPILL OVER ROOF DRAINS WITH A TURNED-DOWN ELBOW.
20.
21.
C:\Users\rmoyher\Documents\18.003 Tehama SSB MEP- R18_rmoyher@peterseng.com.rvt
3.
ALL PERMANENT EQUIPMENT AND COMPONENTS. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G. HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS OR WATER. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS OR HAS A CENTER OF MASS LOCATED 4 FEET OR MORE ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.
8.
B
5/15/2019 10:16:07 AM
1. 2.
THE WATER CLOSET CONTROLS (FLUSH HANDLE) MUST BE LOCATED ON THE CLEAR/ WIDE SIDE OF THE ACCESSIBLE WATER CLOSETS. HAZARDOUS AND COMBUSTIBLE MATERIAL LINES (E.G. GAS LINES) GREATER THAN 1" IN DIAMETER AND NON-HAZARDOUS LINES (E.G. WATER LINES) GREATER THAN 3" IN DIAMETER REQUIRE SEISMIC BRACING PER 2016 CBC SECTION 1616A.1.26. ACCEPTABLE SEISMIC BRACING DETAILS INCLUDE THOSE SHOWN IN THE EATON/COOPER B-LINE OPM-0052-13 WITH 2016 REVISIONS. GENERAL CONTRACTOR TO CONFIRM BRACING DETAILS WITH DESIGN TEAM PRIOR TO INSTALLATION. GAS LINES TO COMPLY WITH DSA BULLETIN 11-03.
B.
COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. COMPONENTS WEIGHING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE OR STRUCTURAL ENGINEER DELEGATED RESPONSIBILITY AND THE DSA DISTRICT STRUCTURAL ENGINEER. THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE REQUIREMENTS.
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-10 SECTION 13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.5.6, 13.6.7, 13.6.8, AND 2016 CBC, SECTIONS 1616A.1.24, 1616A.1.25 AND 1616A.1.26. THE METHOD OF SHOWING BRACING AND ATTACHMENTS TO THE STRUCTURE FOR THE IDENTIFIED DISTRIBUTION SYSTEM ARE AS NOTED BELOW. WHEN BRACING AND ATTACHMENTS ARE BASED ON A PREAPPROVED INSTALLATION GUIDE (E.G., SMACNA OR OSHPD OPM), COPIES OF THE BRACING SYSTEM INSTALLATION GUIDE OR MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF AND DURING THE HANGING AND BRACING OF THE DISTRIBUTION SYSTEMS. THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS. MECHANICAL PIPING (MP), MECHANICAL DUCTS (MD), PLUMBING PIPING (PP), ELECTRICAL DISTRIBUTION SYSTEMS (E): MP MD PP E OPTION 1: DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND DETAILS MP
MD
PP
MP
MD
PP
E
OPTION 2: SHALL COMPLY WITH THE APPLICABLE OSHPD PRE-APPROVAL (OPM #) #____________. OPTION 3: SHALL COMPLY WITH THE SMACNA SEISMIC RESTRAINT MANUAL, OSHPD EDITION (2009), INCLUDING ANY ADDENDA. FASTENERS AND OTHER ATTACHMENTS NOT SPECIFICALLY IDENTIFIED IN THE SMACNA SEISMIC RESTRAINT MANUAL, OSHPD EDITION, ARE DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND DETAILS. THE DETAILS SHALL ACCOUNT FOR THE APPLICABLE SEISMIC HAZARD LEVEL ___ AND CONNECTION LEVEL ___ FOR THE PROJECT AND CONDITIONS.
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 LIONAKIS 2017
AGENCY
PLUMBING SHEET LIST SHEET NUMBER P-001 P-101 P-111 P-112 P-133 P-501
A
SHEET NAME SYMBOLS, NOTES & SCHEDULES PLUMBING GAS SITE PLAN FLOOR PLAN - DRAINAGE PLUMBING FLOOR PLAN - DOMESTIC PLUMBING ROOF PLAN - PLUMBING DETAILS
TITLE
SYMBOLS, NOTES & SCHEDULES
SHEET
P-001
2"
1
2
3
4
5
SHEET NOTES:
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
1. ALL PIPING SHOWN SHALL BE RUN UNDER GRADE BEFORE RISING AT WALL TO ENTER BUILDING WITH SHUTOFF VALVE PER DETAIL 2/P-501 2. GAS TO ROUTE ON SITE AND ABOVE CEILING IN BUILDING BEFORE ENTERING REGULATOR ON BUILDING ROOF.
APP. 02-117123
REVIEWED FOR SS
0 1/4" 1/2"
INC:
FLS
✔
ACS
✔
✔
07/03/2019
DATE:
1
SEE SHEET P112 FOR GAS RISER INTO BUILDING.
2
CONNECT NEW 1"ø SITE GAS PIPING AT EXISTING TRAFFIC GRAD VAULT AND LID. PROVIDE NEW TRAFFIC GRADE LID AND VAULT FOR FUTURE CONNECTION WITH NEW SHUT OFF VALVE.
3
EXISTING TRAFFIC GRADE VAULT AND LID WITH SHUT OFF VALVE.
4
NEW TRAFFIC GRADE VAULT AND LID WITH SHUT OFF VALVE.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
GAS SUPPLY SCHEDULE
D LOCATION
PRESSURE
LEGNTH (FEET)
GAS REQUIREMENT CONSULTANT
15 FEET
IN BUILDING
5 PSI
90 FEET
5 PSI
POC TO (E) METER
5 PSI
engineering
110 FEET
consulting mechanical and electrical engineers
SE
PROF E SS I ONA L R . T I CH E
AN
M31176 EXP. 12/31/19 ME
TE
CH AN I C A
OF C
L
I RN A L I FO
A
TA
I NEER
REG I ST
ED
R NO
ER
465 FEET
S
(E)
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
280 MBH
ON SITE TO POC
EXISTING GAS LOAD = 2,380 MBH NEW GAS LOAD = 280 MBH TOTAL GAS LOAD = 2,660 MBH
GM
(E)
11 IN. W.C.
TOTAL NEW GAS LOAD = 280 MBH TOTAL DEVELOPED 11 IN. W.C. LENGTH = 15 FT TOTAL DEVELOPED 5 PSI LENGTH = 200 FEET
(E) GAS METER
G1
ON ROOF
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
KEYED NOTES:
C. EL E
25 SD
SEAL
(E
SD 18" (E)
)
18 "
SD P
P
12 SS
CH REN T T
06 SD
JOIN (E)
SS14
C
PROJECT
W " D 3 /4 (E)
TEHAMA CENTER STUDENT SERVICE
SS13
11 SS
770 DIAMOND AVE. RED BLUFF, CA 96080
) (E 4" SS P 0. S= 0 03
CLIENT
4
P SD
05 SD 05 SD
" ) 6 (E
P SD
" ) 8 (E
F W1
" ) 8 (E
P SD
05 SD
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ING ILD BU 7.80 9 =2 FF
1
" ) 8 (E
(E)
P SD
23 SD
ISSUED P SD
MARK
DW 2"
(E) BUILDING 1 GAS LOAD = 800 MBH 05 SD
(E)
W 6" (E)
" 12
2 S S0
) (E
) (E
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
" 18
P SD 18" (E)
05 SD
P SD
SS
05 SD
06
SD05
) (E
G2
A E M
(E) BUILDING 3 GAS LOAD = 980 MBH
4"
P SS
IN)
6" (E)
15 SD
C OR P (F SS 3" (E)
24 SD
3 ING ILD 0 BU 98.0 ) (E F=2 F
FW
01
05 SD
W
P SD 5 SS0
(E) 6" FW
6"
04 SS
) (E
W01
. EC EL ULT VA 05 SD
S S0
1
) (E
. &T AT ULT ) VA (E
05 SD
(E) LIGHTING BOX
18 SD
(E) FIRE WATER BOX
) (E
4"
P SS ) (E
8"
P SD
) (E
6"
P SS
(E) ELEC. BOX
7 SS0
P SS
) (E
WV
3"
4"
) (E
P SD
B
(F C OR ) IN MA
(E) 2"ø MPG
E
2 G IN 4 ILD BU 97.8 ) 2 (E F= F
) (E
) (E
. EC EL OX B
4" P SS
(E) BUILDING 2 GAS LOAD = 600 MBH
G2
1"
MANAGEMENT
R
" ) 2
PIP E
FW
4"
DW
) (E
" ) 6
TE WA
(E (E
05 SD
8"
P SD
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
W
05 SD
P SS
) (E
8"
05 SD
) (E
" 18
2" P SS
10 SD
ILL
AR
3
)P
1
P2 SD
(E) UTILITY VAULT
NO ING RK PA F W1
3
NO ING RK PA
F W08
(297.6)
(297.7)
(E) ICV
(E)ICV
1
NO ING RK PA
" 24
(300)
F W1
) (E S D P
P8 SD
12 FW
(E) FH
2
POC
SS01
S
SD
01
(297.4)
4 (E
(2
(297.4)
)
" 24
P SD
P9 SD
98 )
W
ED OS G OP PR IL DIN 8 .5 9 BU = 2 FF
(297.5)
02 SD
(299.2)
D
H
(E) WATER BOX 1 F W0
(E) FH
W12
P7 SD
F W14
(E) RPP
W0
(297.4)
P6 SD
(E) WATER STRUCTURE
W
H
8
W
8"
FW
(299.3)
8"
(297.6)
0 P1 SD
3 F W0
F W10
W0
(E) ICV
3 W0
W0 1
4
(E) WATER METER (E) ICV
4 P1 SD
) (E
" 15
(E) WATER BOX (E) IRRI. CONTROL PANEL
3 P1 SD 2 P1 SD
C:\Users\rmoyher\Documents\18.003 Tehama SSB MEP- R18_rmoyher@peterseng.com.rvt
) (E
5/15/2019 10:16:08 AM
(29 9)
P5 SD
(297.5) (297.7)
(297.7)
)
6"
3 E BL TA (E)
(299.4)
SD28
(E
(297.6)
(E) FLAG POLE
(299.6)
) (E
F W14
(E) MAILBOX
2
AGENCY 09 SD
P4 SD
F W1
P SD
(297.8)
(298)
H
(299.5)
8"
1/2"ø MPG (280 MBH)
SDP
(299.1) (E
) (E
05 SD
DW 2"
DW
)
LIONAKIS 2017
SDP1 4"
(E
FW
017294
P SD
6"
) (E
33 SD
(E)ICV
(E) 9"∅ SEWER LID
W
) (E
) (E
6"
(E) FIRE ALARM BOX
1 P1 SD
P SD
A
TITLE
1 P-101
PLUMBING GAS SITE PLAN
PLUMBING GAS SITE PLAN
1" = 30'-0"
SHEET NORTH
P-101
3
4
0 1/4" 1/2"
KEYED NOTES:
SHEET NOTES:
1
2" WD, 2" VR, 4" VTR TO LAVATORY.
1. ALL CONDENSATE BRANCH LINES TO INDIVIDUAL FAN COILS ARE 3/4"ø UNLESS NOTED OTHERWISE.
2
4" WD, 3" VR TO WATER CLOSET.
3
2" WD, 2" VR TO MOP SINK.
SS
4
3" RAIN WATER LEADER AND 3" OVER FLOW LEADER FROM ABOVE. ROUTE DOWN COLUMN.
DATE:
5
OVER FLOW LEADER TO DISDCHARG 12" ABOVE GRADE ON SIDE OF ARCHITECTURAL COLUMN.
6
SEE DETAIL 3/P-501 FOR AREA DRAIN UP NEARBY WALL.
7
SUPPORT PIPING PER DETAILS ANDRESTRAIEND 7/P-501FOR 8/P-501. DETAIL 7/P-501 AND DETIAL 8/P-501 FOR UNRESTRAINED. SEISMIC SUPPORTS AND BRACING FOR ALL PIPING SHALL BE 3/4" CONDENSATE DROP FROM ROOF RECEPTOR ABOVE. FURNISHED AND INSTALLED IN ACCORDANCE WITH CBC SECTION 1613A, ASCE 7 SECTION 13.6.1 AND NFPA 13 STANDARDS FOR SUPPORT AND ANCHORAGE.
8
3" RWL, I.E. = -2'-2" B.F.F. SEE CIVIL PLANS FOR CONTINUATION.
4
5
6
5' - 0"
PROVIDE CLEANOUT AT BASE, TYP.
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
7
engineering
consulting mechanical and electrical engineers
OFFSET ABOVE CONT. STRUCTRURAL FOOTING. SEE SHEET S-111
ER
SE
REG I ST
S
CO
CO
4
R . T I CH E
AN
M31176 EXP. 12/31/19
5 TA
4
PROF E SS I ONA L
ME
TE
CH AN I C A
OF C
I NEER
CO
ED
R NO
CO
✔
07/03/2019
PROVIDE CLEANOUT AT BASE, TYP.
5
ACS
✔
CONSULTANT
5' - 0"
3
FLS
✔
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
2
INC:
REVIEWED FOR
TO DO: WHERE IS ROOF ACCESS? ANY EXTERIOR HOSE BIBS?
1
APP. 02-117123
3/4" CONDENSATE DROP FROM ROOF RECEPTOR ABOVE.
8
3" RWL, I.E. = -2'-2" B.F.F. SEE CIVIL PLANS FOR CONTINUATION.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
5
L
I RN A L I FO
A
2
1"
2"
1
E 4" SS, I.E. = -2'-4" B.F.F. SEE CIVIL PLANS FOR CONTINUATION
2-WAY COTG 5' - 0"
SEAL
D
CAMPUS SAFETY
FC-Z11
CO
CO
FC-Z12
COUNSELOR 128
126
C
COUNSELOR
FC-Z13
CO
CO
COUNSELOR
FC-Z14
130
3"ø RWL
132
FC-Z01
TEHAMA CENTER STUDENT SERVICE
101
4"ø SS U.G.
3/4"ø CD
PROJECT
102
CLASSROOM/LOBBY OVERFLOW
CO
3/4"ø CD
ADMIN OFFICE
CO
3"ø RWL
CO
770 DIAMOND AVE. RED BLUFF, CA 96080
FC-Z03 CO
CLEANOUT (CO), TYP. 3/4"ø CD
3/4"ø CD
HALLWAY
FC-Z02
8
CLIENT
100D
CO
CO
LOBBY CO
CO
100
CO
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
3/4"ø CD
CO
C.4 ADMIN OFFICE
CO
CO
FC-Z15
CO
FC-Z16
104
CO
FC-Z17
PIPES HIDDEN IN ARCHITECTURAL CHASE
FC-Z18
STUDENT SERVICES
ISSUED
103
MARK
FF-0'-0" CO
COUNSELOR
4" SS TO DISCHARGE IN LANDSCAPE
COUNSELOR
COUNSELOR 3/4"ø CD 127
125
COUNSELOR 3/4"ø CD
129
131
3" RWL FROM ABOVE
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
3" RWL FROM ABOVE
CO CO
C FS-1 FIRE RISER
3" VTR 3" V U.G.
3/4"ø CD 6
HALLWAY
HALLWAY 3/4"ø CD
100C
151
3" OFL FROM ABOVE
CONFERENCE B
100B
3" OFL FROM ABOVE WORK CENTER
PIPE HIDDEN IN ARCHITECTURAL CHASE
100A
124
FC-1
3" OFL DAYLIGHT THRU HIGH WALL 1"ø CD WALL AND CONNECT TO TAILPIECE OF LAV. 3/4"ø CD
3" OFL DAYLIGHT THRU HIGH WALL
CO
STUDENT SERVICES
FACULTY OFFICE
108
105
B.6 CO 3/4"ø CD
121
3/4"ø CD STORAGE
FC-Z10
RESTROOM
119
120
VET CENTER
WCO
3
123
MS-1
118
2"ø SS U.G.
7
3"ø V A.B.C.
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
CO 4"ø SS U.G.
2"ø SS U.G.
4"ø SS U.G.
FCO CUSTODIAL
4" VTR
L-1
1
IDF
MANAGEMENT
3/4"ø CD
CO
3/4"ø CD
STUDENT SERVICES
STUDENT SERVICES
107
106
2
WC-1
LIONAKIS 2017
FC-Z04 AGENCY
FCO 4"ø SS U.G.
017294
FC-Z05 CO
CO
FC-Z09
2"ø V U.G.
FC-Z07
VET OFFICE
5/15/2019 10:16:11 AM
C:\Users\rmoyher\Documents\18.003 Tehama SSB MEP- R18_rmoyher@peterseng.com.rvt
122
CO
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
FACULTY OFFICE
CO
114
FACULTY OFFICE
FC-Z06
112 FACULTY OFFICE
113
FACULTY OFFICE
111
FC-Z08 CO
CO FACULTY OFFICE
FACULTY OFFICE
109
110
B
A
TITLE
FLOOR PLAN DRAINAGE PLUMBING
A
SHEET
1 P-111
FLOOR PLAN - DRAINAGE PLUMBING 1/4" = 1'-0"
PLAN NORTH
P-111
2"
1
2
3
4
APP. 02-117123
INC:
REVIEWED FOR
3
3/4" CWD TO HOSE BIBB.
DATE:
4
1/2" CWD TO WC.
5
1/2" CWD TO LAVATORY, 1/2" HW FROM IEWH-1.
6
1/2" CWD, 1/2" HWD FROM EWH-1 TO MOP SINK.
7
3/4" CWD TO ROOM HOSE BIBB.
8
GAS RISER TO ROOF.
9
1/2" CW TO INSTANTANEOUS ELECTRIC WATER HEATER. 1/2" HW OUT OF ELECTRIC WATER HEATER.
10
DETAILS7/P-501 ANDRESTRAIEND 7/P-501FOR 8/P-501. SUPPORT PIPING PER DETAIL AND DETIAL 8/P-501 FOR UNRESTRAINED. SEISMIC SUPPORTS AND BRACING FOR ALL PIPING SHALL BE SUPPORT ELECTRIC WATER IN HEATER ON SHELF PERCBC DETAIL MOUNT WATER 10/P-501. FURNISHED AND INSTALLED ACCORDANCE WITH SECTION 1613A, ASCE7 SECTION 13.6.1 AND 13 STANDARDS FOR SUPPORT AND ANCHORAGE. HEATER ONNFPA SHELF. BOTTOM OF SHELF TO BE 6'-0" ABOVE FINISHED FLOOR.
FLS
✔
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
TRAP PRIMER TP-1 INWATER ACCESSIBLE WALL PANEL.PER DETAIL 10/P-501. MOUNT WATER SUPPORT ELECTRIC HEATER ON SHELF HEATER ON SHELF. BOTTOM OF SHELF TO BE 6'-0" ABOVE FINISHED FLOOR.
CONSULTANT
TRAP PRIMER TP-1 IN ACCESSIBLE WALL PANEL.
12
4
1. SEE GENERAL NOTES ON SHEET P-001
SS
12 11
3
GAS SHUTOFF VALVE, SEISMIC SHUT OFF VALVE AND ENTRY TO BUILDING PER DETAIL 2/P-501. GAS SHUT OFF VALVE SHALL BE EQUAL TO PACIFIC SEISMIC PRODUCTS MODEL VB-301 VERTICAL BOTTOM IN FLOW VALVE (CA-DSA NO. 13-42).
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
2" COLD WATER RISER INTO BUILDING.
D
2
SHEET NOTES:
2
11
1
KEYED NOTES:
5
6
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
7
engineering
SE
PROF E SS I ONA L R . T I CH E
AN
M31176 EXP. 12/31/19 ME
TE
CH AN I C A
OF C
L
I RN A L I FO
A
S
TA
I NEER
REG I ST
ED
R NO
ER
consulting mechanical and electrical engineers
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
1"
1
5
E 1 1/2" CW, SEE CIVIL PLANS FOR CONTINUATION
5' - 0"
SEAL
CWD
GV IN VB OFFSET OVER CONT. FOOOTING. SEE SHEET S-111
HB-2
8
D 2
3/4"ø CW
ADMIN OFFICE
CAMPUS SAFETY
COUNSELOR
COUNSELOR
COUNSELOR
126
128
130
132
PROJECT
102
C
TEHAMA CENTER STUDENT SERVICE
SEE P101 FOR CONT.
10
1"ø G
770 DIAMOND AVE. RED BLUFF, CA 96080
1"ø G 3/4"ø CW
1
CLASSROOM/LOBBY OVERFLOW
7
HALLWAY 100D
GAS S.O.V. AND SEISMIC VALVE IN CABINET
CLIENT
101
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT C.4
LOBBY
ADMIN OFFICE
100
104
STUDENT SERVICES
FF-0'-0" COUNSELOR
COUNSELOR
COUNSELOR
COUNSELOR
125
127
129
131
CWD
ISSUED
MARK
103
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
3/4"ø CW
HB-2
C FS-1
HALLWAY
1/2"ø CW U.G.
FIRE RISER
CONFERENCE
151
124
TP-1
HALLWAY
1 1/2"ø CW A.B.C.
100C
100B
WORK CENTER
B
100A 12
CWD
B.6
MANAGEMENT
RESTROOM IDF
5
118
IEWH 9 2 (UNDER LAV) 3/4" CW DOWN WALL
121 STORAGE
CUSTODIAL
120
119
3/4"ø CW
3/4"ø CW WALL MOUNTED: EWH BOTTOM OF SHELF 11 1 @ 6'-0" AFF
VET CENTER 123
3
HB-1
6
MS-1
STUDENT SERVICES
1 1/2"ø CW 4
WC-1
STUDENT SERVICES
FACULTY OFFICE
107
106
105
LIONAKIS 2017
AGENCY
FACULTY OFFICE
122
C:\Users\rmoyher\Documents\18.003 Tehama SSB MEP- R18_rmoyher@peterseng.com.rvt
STUDENT SERVICES
017294
108
3/4" CW DOWN WALL
VET OFFICE
5/15/2019 10:16:13 AM
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
L-1
112 FACULTY OFFICE
117
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
115
114
113
111
110
109
116
B
FACULTY HALLWAY
150
A
TITLE
FLOOR PLAN DOMESTIC PLUMBING
A
SHEET
1 P-112
FLOOR PLAN - DOMESTIC PLUMBING 1/4" = 1'-0"
PLAN NORTH
P-112
2"
1
2
3
4
1"
1 2
5
KEYED NOTES:
SHEET NOTES:
GAS PRESSURE REGULATOR (GPR) ON ROOF. 5 PSI TO 11" W.C. PROVIDE LINE SIZE ISOALTION VALVES ON EACH SIDE WITH UNIONS.
1. CONDENSATE ON ROOF SHALL BE UV PROTECTED PAINTED PVC PIPING.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
REVIEWED FOR
GAS RISER FROM CEILING BELOW.
3
PROVIDE GAS SHUTOFF VALVE TO GAS FIRED ROOFTOP EQUIPMENT.
4
3/4"ø CONDENSATE DOWN THROUGH ROOF. INDIRECT CONNECTION VIA ROOF RECEPTOR. SEE DETAIL 3/P-501.
5
ROOF DRAIN UNDER ARCHITECTURAL OVERHANG. TYPICAL OF 2.
6
3/4"ø COLD WATER RISER THRU ROOF TO ROOFTOP HOSE BIBB.
7
3" RAIN WATER LEADER AND 3" OVERFLOW LEADER DOWN THRU HIGH ROOF. SEE SHEET P-111 FOR RAIN WATER LEADER CONTINUATION. SEE DETAIL 5/P-501, TYPICAL.
8
DRAIN TO ARCHITECTURAL SCUPPER ON EXTERIOR OF BUILDING.
9
3" RAIN WATER LEADER AND 3" OVERFLOW LEADER DOWN THRU MECHANICAL WELL. SEE CONTINUATION ON SHEET P-111. SEE DETAIL 5/P-501, TYPICAL.
10
OVER FLOW LEADER TO DAYLIGHT ON SOUTH WALL ABOVE LOW ROOF.
11
TYPICAL GAS CONNECTION TO ROOFTOP EQUIPMENT. SEE DETIAL 6/P-501.
12
SEE DETAIL 9/P-501 FOR VENT THRU ROOF DETAIL.
FLS
✔
ACS
✔
✔
07/03/2019
DATE:
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
consulting mechanical and electrical engineers
3
4
5
6
7
9
SE
3"RD/OFD-1 845 SQ FT
ME
TE
CH AN I C A
OF C
I NEER
S
9
R . T I CH E
AN
M31176 EXP. 12/31/19 TA
3"RD/OFD-1 845 SQ FT
PROF E SS I ONA L R NO
REG I ST
ED
L
I RN A L I FO
A
2
ER
1
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
SS
D
INC:
5
E SEAL
GPR TOTAL LOAD: 280 MBH 15' TO FARTHEST FIXTURE
1 2
D 1"ø G
11
PROJECT
C
TEHAMA CENTER STUDENT SERVICE
3 DOAS-1 3/4"ø G 80 MBH 7' DEVELOPED LENGTH
CD
CD
3/4"ø CD
CD
AC-1 200 MBH 15' DEVELOPED LENGTH
770 DIAMOND AVE. RED BLUFF, CA 96080
3/4"ø G
3/4"ø CD ACCU-1
4
11
3
CLIENT 6
HB-2
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
VRF-1
C.4 ISSUED
MARK
3"RD/OFD-1 925 SQ FT
7
7
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
3"RD/OFD-1 925 SQ FT
C 8
8
3" VTR
12
B
3"ø OFL BELOW ROOF
3"ø OFL BELOW ROOF MANAGEMENT
B.6
C:\Users\rmoyher\Documents\18.003 Tehama SSB MEP- R18_rmoyher@peterseng.com.rvt
10
10
4" VTR (UNDER OVERHANG)
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
LIONAKIS 2017
12 AGENCY
B
A
TITLE
ROOF PLAN - PLUMBING A
5/15/2019 10:16:14 AM
017294
SHEET PLAN NORTH
1 P-133
ROOF PLAN - PLUMBING 1/4" = 1'-0"
P-133
2
3
4
5
1"
ELMDOR/STONEMAN #11004-6LB-8SK FLASHING TURNED IN ON CAST IRON VENTS 3" & LARGER ONLY
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
0 1/4" 1/2"
SS
9"MIN.EXTEND AS REQ'D.
"ELMDOR/STONEMAN" CAULK TYPE COUNTER FLASHING SLEEVE FOR CAST IRON VENTS AND THREADED OR CAULK TYPE FOR ALL STEEL VENTS.
4"
FLS
✔
OVER FLOW DRAIN
ROOF DRAIN
✔
WATER DAM COLLAR
MAX. DEPTH 2"
2" HEAVY DUTY SOLID COVER
PERMASEAL WATERPROOFING COMPOUND
D
FINISHED GRADE
ROOF DECK & FLASHING.
FLASHING CLAMP & UNDERDECK CLAMP, TYPICAL
CAST IRON DRAIN BODY.
AREA DRAIN
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
3" VENT
CONSULTANT
ROOFING
OVER FLOW PIPING. SEE FLOOR PLAN FOR SIZE, TYPICAL.
RAIN WATER LEADER PIPING. PLAN FOR SIZE, TYPICAL.
4" WASTE PIPE
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
NOTES: 1. REFER TO CIVIL PLANS FOR CONTINUATION.
consulting mechanical and electrical engineers
NONE
P-501
NONE
SE
AREA DRAIN W/ NEARBY WALL
REG I ST
P-501
1
M31176 EXP. 12/31/19
S
TA
BALL VALVE HW SUPPLY (SIZED PER PLANS)
VACUUM RELIEF VALVE, WATTS MODEL N36 OR APPROVED EQUAL.
CW SUPPLY (SIZED PER PLANS)
PROVIDE A 18x18 LOCKABLE CABINET WITH S.O.V. AND SEISMIC VALVE
1
UNION
2"WIDE 16 GAUGE STEEL STRAP SECURE TO WALL W/(2) 3/8" DIA. x 3" LONG LAG BOLTS TO TYPE C BACKING, SEE STRUCTURAL
D
C
PROJECT
TEHAMA CENTER STUDENT SERVICE
TIGHT TO WALL
EQUIPMENT SITE GAS PIPE
3/4" COPPER RELIEF DISCHARGE TO MOP SINK BELOW SHELF.
DIELECTRIC UNION, TYP.
SEAL
8" WIDE X 4" HIGH MINIMUM DIMENSIONS, RED PHENOLIC PLATE WITH 3/4" HIGH WHITE LETTERS
LISTED ANODELESS SERVICE RISER, ELSTER, R.W. LYALL OR EQUAL
FLEXIBLE CONNECTION
OF C
L
I RN A L I FO
GAS SHUT-OFF AND SEISMIC SHUT OFF VALVES
G
EWH
REDUCER
CH AN I C A
SIGN ON WALL
SEAL AROUND PIPE AND ESCUTCHEON UNION
ANCHOR TO WALL @ 12" O.C. W/ MIDDLE ANCHOR CENTERED ON CENTER OF WATER HEATER. MIN 1-1/2" FROM TOP AND BOTTOM OF ANCHOR POINT.
MAX WEIGHT = 125 LBS
GAS RISER IN WALL. GAS RISER IN WALL.
S.O.V. SEISMIC GAS VALVE EQUAL TO PACIFIC SEISMIC PRODUCTS VB-301 VERTICAL BOTTOM IN (CA-DSA NO. 13-42)
WATTS 40XL RELIEF VALVE
ME
TE
NOX BOX WITH VALVE CABINET KEY
EXTERIOR WALL
THERM-X-TROL ST-5 EXPANSION TANK
R . T I CH E
AN
I NEER
NONE
ROOF DRAIN DETAIL
PROF E SS I ONA L R NO
5
ED
ENG
VENT THRU ROOF
ER
ROOF STRUCTURE
P-501
ACS
✔
07/03/2019
DATE:
CAST IRON DOMES TYPICAL
ELMDOR/STONEMAN SEAMLESS LEAD FLASHING #1100-4-SPS6LB-8SK OR #1100-4-SWCI6LB-8SK W/ 8" SKIRT
9
INC:
REVIEWED FOR
EXTEND WHERE REQ'D TO CLEAR FRESH AIR INTAKES, ETC.
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
APP. 02-117123
3" VTR TO ROOF
A
2"
1
770 DIAMOND AVE. RED BLUFF, CA 96080
DIRT LEG
SOC
HOSE BIBB DRAIN CLIENT
10 GAUGE GALVANIZED IRON WALL BRACKET W/ BOTTOM PLATE. MOUNT ON WALL W/(6) 3/8" x 3" LONG LAG BOLTS. SECURE LAG BOLTS TO 4x4 BLOCKING IN WALL.(SIMPSON A35 CLIPS. TOP AND BOTTOM EACH END)
10 P-501
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT APPROVED TRANSITION FITTING BETWEEN METALLIC AND PLASTIC PIPING.
ELECTRIC WATER HEATER ON SHELF
6
NONE
P-501
1/2"x1-1/2" x 13 1/2"x1-1/2" x 13 UNC LOCKING UNC LOCKING BOLT TORQUED TO 10 FT-LBS BOLT TORQUED TO 10 FT-LBS
2" MAX (TOP AND BOTTOM)
1/2" LAG BOLT ANCHORS W/ 3" EMBED 2x6 STUD
6x FULL DEPTH 1/2" MIN BLOCKING FROM STUD TO STUD. HANG FROM 2x6 STUD WITH SIMPSON A35, TOP AND BOTTOM, EACH END. (TYP)
1-1/4"
2x6 STUD
C:\Users\rmoyher\Documents\18.003 Tehama SSB MEP- R18_rmoyher@peterseng.com.rvt
TYPE UCC UCC WITH WITH STEEL STEEL STRUT STRUT ASSEMBLY ASSEMBLY RATINGS RATINGS (ASD) (ASD) TYPE
11 P-501
ROD STIFFENER DETAIL NONE
1/4" DIA. x 3" LAG BOLT, ATTACH TO BLOCKING
U-BOLTS
1 1/2"x3/16" BENT CLIP, 6" LONG 1/2" HEX HEAD SCREW AND CHANNEL
1/2" THROUGH BOLT W/NUT & WASHERS. NUT & WASHERS
ROD ROD SIZE SIZE (INCHES) (INCHES)
MAXIMUM MAXIMUM STRUT STRUT STIFFENER STIFFENER LENGTH LENGTH (INCHES) (INCHES)
MAX MAX UCC UCC SPACING SPACING (INCHES) (INCHES)
MAXIMUM MAXIMUM UNBRACED UNBRACED LENGTH LENGTH (INCHES) (INCHES)
3/8" 3/8" 1/2" 1/2"
156 156 156 156
18 28 25 38
18 18 25 25
TYP. COND. PIPE
LEAD FLASHING
1-1/2" MAX PIPE SIZE
ROOFING
3"MIN 1/2" MIN
1/2" ROD 8'-0" OC MAX
1/2"ø THREADED HANGER ROD
SPACING SHALL BE MIN 6'-0" ON MAXCENTER 6'-0" ON CENTER WOOD BEAM NOTE 1. SEE DETAIL 8/P-501 FOR MULTIPLE PIPES SUPPORTED FROM ABOVE. NOTE SEE DETAIL FOR SHALL SINGLEBE PIPES SUPPORTED FROM ABOVE. 1. SEISMIC SUPPORTS AND BRACING FOR6/M-502 ALL PIPING 1/2"° ROD 2. THIS DETAIL SHALL BE USED FOR FURNISHED AND INSTALLED IN ACCORDANCE WITH CBC 1613A. PIPING SYSTEM THAT ARE EXEMPT FROM DESIGN OF SEISMIC FORCES. U-BOLTS STANDARDS FOR SUPPORT AND ANCHORAGE. ( LONGITUDINAL SEISMIC BRACING SHALL BE PROVIDED AT A MAXIMUM SPACING OF 80'-0" AND LATERAL SEISMIC BRACING SHALL BE PROVIDED AT A MAXIMUM SPACING OF 40'-0". )
TURNBUCKLE
MANAGEMENT
INCREASE TO 3" PIPE THRU ROOF
STEEL STRAP
3/4"VR
3/4"P-TRAP
45°
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
3/4"WD AGENCY
UNISTRUT P1001 2. PROVIDE ROD STIFFENER PER 11/P-501 FOR HANGER RODS.
7 P-501
3' MAX
8'-0" ON CENTER MAXIMUM
TYP PIPE SUPPORT ON RESTRAINED PIPES SUPPORTED WALL
3
NONE
4x4 BLOCKING W/ SIMPSON A34 EACH SIDE, EACH END, TYYP.
P-501
CONDENSATE DRAIN RECEPTACLE NONE
FLOOR ABOVE/ROOF REFER TO STRUCTURAL FOR BLOCKING AND FILLER ATTACHMENT
2" MAX SCHEDULE 40 BLACK STEEL PIPING OR COPPER TYPE "M"
SEE DETAIL 6/M-502 FOR SINGLE PIPE SUPPORT
PIPE CLAMP, LOOSE FIT
4" MAX
A TRAFFIC PAD. EXTEND 8" MINIMUM ALL AROUND SLEEPER. SECURE TO ROOF WITH ROOFING CEMENT
PIPE CLAMP
TYP PIPE SUPPORT UNRESTRAINED NONE
TITLE
DETAILS ROOFING
WASHER & NUT - BOTH SIDES
HORIZONTAL PIPE SUPPORT NOTES: 4x BLOCKING & B-LINE SUPPORT. 1. NOTES: SUPPORT AT ALL CHANGES IN DIRECTION. 1 5/8" B-LINE FRAMING CHANNEL 2. 1.HORIZONTAL PIPE BE SPACED MAX. 8'-0" O.C. SUPPORT AT ALLSUPPORT CHANGESSHALL IN DIRECTION. 3. THIS DETAIL SHALL BE USED FOR PIPING SYSTEMS THAT ARE EXEMPT FROM DESIGN OF SEISMIC FORCES AS NOTED IN 2016 CBC 2. HORIZONTAL PIPE SUPPORT SHALL BE SPACED MAX. 8'-0" O.C. 1616A.1.26, ASCE 7, SEC 16.6.8.3. ONE OF THE BELOW REQUIREMENTS MUST BE IN PLACE FOR THIS DETAIL TO BE USED: PIPING ROD 3" DIAISAND SHALL BE TO FURNISHED WITHUNISTRUT SEISMIC SUPPORTS BRACINGS. A. 3.HANGER LESSLARGER THAN OR EQUAL 12" BETWEEN AND WOODAND FRAMING MEMBERS ABOVE OR B. PIPES ON TRAPEZE ARE NON-HAZARDOUS SYSTEMS AND LESS THAN OR EQUAL TO 3" DIA AND/OR PIPES ON TRAPEZE ARE HAZARDOUS SYSTEMS AND LESS THAN OR EQUAL TO 1" DIA. FOR RESTRAINED PIPING REQUIRING SEISMIC SUPPORTS, SEE DETAIL 7/P-501. P-501
"B-LINE" DURA-BLOK SUPPORT, 6" HIGH MINIMUM, WITH INTEGRATED 1/2" - 13 ELECTRO ZINC ALL THREADED ROD RISERS AND GALVANIZED SLOTTED CHANNEL - 1" HIGH
FLOOR/ROOF JOIST
HWS R PIPING WITH HWS &&R,R,CHWS CHWS& & R PIPING WITH INSULATION INSULATIONSPACER SPACER
8
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
3/4"VTR
L 3"X3"X3/16" BRACE, CRIMP AND BEND FLANGE AT ENDS, TO OCCUR @ CHANGES IN PIPE DIRECTION
UNISTRUT P1000 WALL BRACKET
DATE 01/04/2019 05/17/2019
COUNTERFLASHING SLEEVE
1/2" MIN
HORIZONTAL PIPE SUPPORT
5/15/2019 10:16:14 AM
MARK
UNISTRUT P1000 WALL BRACKET
1 1/2x1 1/2x1/4" ANGLE 1/2" LAG BOLT ANCHORS (3" LONG) W/ 3" EMBED
MASON IND. IND. N.Y. N.Y. UCC UCC SEISMIC SEISMIC ROD ROD CLAMP CLAMP MASON
NONE
ISSUED
U-BOLTS
1-1/4"
1-5/16"
BLDG GAS SHUT-OFF VALVE
4x4 BLOCKING SECURED BETWEEN TJI'S OR TJW'S WITH 3-10d NAILS AT EACH END. REFER TO STRUCTURAL FOR 1/2" MIN ATTACHMENT TO TJI'S OR TJW'S.
1-3/16"
B 1-5/16"
P-501
1-1/2" MAX PIPE SIZE
1" MIN
1-3/16"
2
NONE
6x FULL DEPTH BLOCKING FROM STUD TO STUD. HANG FROM 2x6 STUD WITH SIMPSON A35, TOP AND BOTTOM, EACH END. (TYP)
THREADED ROD ROD THREADED 1-5/8"x1-5/8"x12 GA GA 1-5/8"x1-5/8"x12 SINGLE STRUT STRUT SINGLE STIFFENER STIFFENER
TYP GAS CONNECTION TO EQUIP
1/2" THREADED ROD W/ DBL NUT TO
NOTE: SUPPORTS TO BE PLACED AT A MAXIMUM SPACING OF 8'-0" ON CENTERS. SHEATHING
SHEET
4 P-501
PIPE SUPPORT ON ROOF NONE
P-501
017294 LIONAKIS 2017
1.
2.
PLANS ARE NOT FOR CONSTRUCTION UNTIL APPROVED BY THE AUTHORITY HAVING JURISDICTION. THE CONTRACTOR SHALL NOT ORDER ANY MATERIALS OR INSTALL ANY EQUIPMENT, PIPING, ETC. UNTIL PLANS ARE APPROVED BY THE AUTHORITY HAVING JURISDICTION.
SYMBOL
DESCRIPTION
1
LINED DUCT
ALL WORK SHALL BE IN ACCORDANCE WITH ALL FEDERAL, STATE, CITY AND LOCAL CODES AND ORDINANCES.
4.
5.
THE CONTRACTOR SHALL READ ALL OF THE GENERAL NOTES, SPECIFICATIONS AND PLANS AND SHALL BE SATISFIED TO THEIR TRUE MEANING AND INTENT AND SHALL BE RESPONSIBLE FOR COMPLYING WITH EACH. WHEREVER TWO OR MORE SPECIFICATIONS MAY CONFLICT, THE MORE STRINGENT SPECIFICATION SHALL TAKE PRECEDENCE.
W
=1
24x12
R
24x12
2
SECTION AT RETURN DUCT RISER
24x12
W
12x12
=1.5
6.
24x12
6.
7.
3
TURNING VANES
24x12
SECTION AT SUPPLY DUCT RISER
24x12
11.
12.
13.
24x12
5
12x12
12"∅
TURNING VANES 15° DEFLECTROL AIRTURN
6
7/5 SPLIT TRANSITION
24x7 ABOVE
B
T TBD TCP TEMP. TD TG TSP TV TYP UCD UTR V VAV VFD
THERMOSTAT TO BE DETERMINED TEMPERATURE CONTROL PANEL TEMPERATURE TRANSFER DUCT TRANSFER GRILLE TOTAL STATIC PRESSURE TURNING VANES TYPICAL UNDERCUT DOORS UP THRU ROOF VOLTS VARIABLE AIR VOLUME VARIABLE FREQUENCY DRIVE
W/ WB WT.
WITH WET BULB WEIGHT
19
7/5
30x5
TRANSITIONAL RADIUS ELBOW 30x5
24x12 24x5 BELOW
7
24x7 ABOVE
SQUARE ELBOW W/ TURNING VANES 16x12
7/5
24x12
30x5
16x12
PETERS
24x12
consulting mechanical and electrical engineers
1 IN 6 MAX.
24x12
CONCENTRIC
24x12
1 IN 2 MAX. ECCENTRIC
24x12
DIVERGING FLOW
24x12
16x12
14/10
20
TRANSITION
24x12
14x10
14/10
16x12
10"
14/10
14x10
TA
14/10
INCHES UNLESS OTHERWISE NOTED. 10
24x12
10"Ø
12"Ø
12"Ø
10"Ø
10'MAX. LENGTH OVER 10' USE NO. 6,7,8 OR 9
45ØTEE
SEAL
FIRE DAMPER
F
10'MAX. LENGTH OVER 10' USE NO. 6,7,8 OR 9
DEFLECTROL AND BRANCH SAME SIZE AS NECK SIZE
23
24x12
CEILING DIFFUSER
BRANCH-SEE PLAN FOR SIZE
FLEX DUCT
PROJECT
TEHAMA CENTER STUDENT SERVICE
FLEX. DUCT DIFFUSER
770 DIAMOND AVE. RED BLUFF, CA 96080
CEILING DIFFUSER
ELONGATED TEE
INDICATES ROUND DUCTS IN INCHES, TYPICAL
I
CAP AT END OF RUN
SQUARE ELBOW W/ TURNING VANES
14x12
O F CA L
L
N I F OR
12x6
24x12
10"Ø
12"Ø
DEFLECTROL AND BRANCH SAME SIZE 24x12 SIDEWALL REGISTER OR GRILLE
F
TRANSITIONAL RADIUS ELBOW
TRANSITION
10"
CH AN I CA
24x12
CEILING DIFFUSER
16x12
14x12
ME
TE
ECCENTRIC
DEFLECTROL & BRANCH DUCT SAME SIZE
24x12
22
14"
M31176 EXP. 12/31/19
12x12
CONCENTRIC
16x12
24x12
R. T I C HE
AN
CONTRACTING FLOW
21
14"
ED
24x12
1 IN 2 MAX.
24x5 BELOW
8
PRO F E S S I ONA L
12x12
12x12
24x12
12x6
30x5
24x12
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
engineering
12x12
1 IN 2 MAX.
12x12
CLIENT SUPPLY DUCT RISE
11
24 AIR FLOW
AIR FLOW AIR FLOW SUPPLY DUCT DROP
12
RETURN OR EXHAUST AIR RISE
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
SHOE FITTING WITH MVD
25 AIR FLOW
AIR FLOW
ISSUED
AIR FLOW
MARK
CONICAL FITTING WITH MVD
RETURN OR EXHAUST AIR DROP
26
13
ACOUSTICALLY LINED SHEET METAL DUCT SIZE SHOWN IS NET INSIDE DIMENSION
-
F
FSD
38x12 TRANSITION
16x12
24x12
MINIMUM MAXIMUM OVER CURRENT PROTECTION MOTORIZED DAMPER MANUAL VOLUME DAMPER NEW OPPOSED BLADE DAMPER ON CENTER OPENING OUTSIDE AIR OUTSIDE AIR HOOD PHASE POINT OF CONNECTION QUANTITY RETURN AIR RETURN DIFFUSER ROOF EXHAUST FAN RADIANT HEATER REFRIGERANT LIQUID REVOLUTION PER MINUTE RETURN REGISTER (GRILLE) REFRIGERANT SUCTION TEMPERATURE SENSOR SMOKE DETECTOR SHEET METAL SUPPLY AIR SUPPLY DIFFUSER (REGISTER) (GRILLE) STAINLESS STEEL WALL SWITCH
1 IN 2 MAX.
CONSULTANT
4/36/8
12x12
1 IN 6 MAX.
24x12
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
8"
12x12
SQUARE TO ROUND TRANSITION
16x12
24x12
24x12
MIN. MOCP M MVD (N) OBD OC OPNG. OSA OSH φ POC QTY RA RD REF RH RL RPM RR(G) RS S SD SM SA SD(R)(G) SS SW
38x12
48x12 12x12 18
12x12
MVD
SQUARE ELBOW W/ DUCT TURN
4" 36"
12x12
C
AIR CONDITIONING ACCESS DOOR AIR EXTRACTOR ABOVE FINISHED FLOOR ACOUSTICAL LINING BACKDRAFT DAMPER BRAKE HORSEPOWER BOTTOM OF DUCT CO2 SENSOR CONDENSATE DRAIN CUBIC FEET PER MINUTE CEILING EXHAUST FAN CENTERLINE DRY BULB DOOR LOUVER DOWN DEDICATED OUTSIDE AIR SYSTEM EXHAUST AIR EXHAUST AIR LOUVER ENTERING AIR TEMPERATURE EXHAUST FAN EXISTING EXHAUST GRILLE EXTERNAL STATIC PRESSURE DEGREES FAHRENHEIT FRESH AIR FRESH AIR LOUVER FLEXIBLE CONNECTION FIRE DAMPER FIRE/SMOKE DAMPER FEET PER MINUTE FULL LOAD AMPS FOOT OR FEET GAUGE GALVANIZED IRON GALVANIZED SHEET METAL HEATING & VENTILATION HERTZ HORSE POWER INDOOR FAN LEAVING AIR TEMPERATURE POUNDS LOCK ROTOR AMPS THOUSAND BTU PER HOUR MAXIMUM MINIMUM CIRCUIT AMPACITY MANUFACTURER
10x8
10x12 48x12
VANE ANGLE 20°-29° 30°-50°
12"Ø MVD
9
AC AD AE AFF AL BDD BHP BOD C CD CFM CEF CL DB DL DN. DOAS EA EAL EAT EF (E) EG ESP °F FA FAL FC FD FSD FPM FLA FT GA GI GSM H&V HZ HP IF LAT LBS. LRA MBH MAX. MCA MFR
38x12 TRANSITION
12x12
12x12
SEISMIC BRACING FOR PIPING CARRYING HAZARDOUS OR COMBUSTIBLE MATERIALS (SUCH AS WATER LINES) SHALL BE PROVIDED FOR ALL PIPES > 3" DIAMETER IN SIZE. BRACING SHALL BE PER CBC SECTION 1616A.1.26. ACCEPTABLE SEISMIC BRACING DETAILS INCLUDE THOSE SHOWN IN EATON/COOPER B-LINE OPM-0052-13.
MECHANICAL LEGEND
17 4/36/8
12x12
12x12
THERMOSTAT SETPOINTS SHALL BE 78°f (SUMMER) AND 68°F (WINTER) - ADJUSTABLE. ANY DEVIATION FROM THESE SETPOINTS BECOMES THE RESPONSIBILITY OF THE USER OR CONTRACTOR. SEISMIC BRACING FOR PIPING CARRYING HAZARDOUS OR COMBUSTIBLE MATERIALS (SUCH AS NATURAL LINES) SHALL BE PROVIDED FOR ALL PIPES > 1" DIAMETER IN SIZE. BRACING SHALL BE PER CBC SECTION 1616A.1.26. ACCEPTABLE SEISMIC BRACING DETAILS INCLUDE THOSE SHOWN IN EATON/COOPER B-LINE OPM-0052-13.
VANE ANGLE
24x12
4/36/8
8"
TURNING VANES
CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES, INSERTS, SLEEVES, HANGING DEVICES, MISCELLANEOUS ANGLES, CHANNELS, UNISTRUT ETC. FOR INSTALLATION OF MECHANICAL AND PLUMBING EQUIPMENT, DUCTWORK AND PIPING, ETC. CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ALL BUILDING TRADES TO AVOID CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY. EACH MECHANICAL APPLIANCE SHALL BE APPROVED BY THE ADMINISTRATIVE AUTHORITY FOR SAFE USE OR COMPLY WITH APPLICABLE NATIONALLY RECOGNIZED STANDARDS AS EVIDENCED BY THE LISTING AND LABEL OF AN APPROVED AGENCY.
36"
I N E ER
10.
CONVERGING OR DIVERGING
4
TRANSITIONAL RADIUS ELBOW
4"
S
9.
10x8
38x12
07/03/2019
DATE:
MVD 16x12
14"
24x12
10x8
48x12 12x12
✔
14x10 SQUARE ELBOW W/ DUCT TURN
10"
48x12
CONTRACTOR SHALL REMOVE RUBBISH WASTE MATERIALS ON DAILY BASIS AND PROTECT AREAS FROM DAMAGE WHICH MAY OCCUR DURING CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE WHICH MAY OCCUR. ALL WORK SHOWN ANYWHERE ON THE DRAWINGS IS INCLUDED; SHOULD AN ITEM (SUCH AS A VALVE) BE SHOWN ON A DETAIL OR SCHEMATIC BUT NOT ON A PLAN VIEW OR VICE VERSA, IT MUST BE PROVIDED AS THOUGH IT WERE SHOWN IN ALL PLACES ON THE DRAWINGS.
16 4/36/8
ACS
✔
R NO
8.
LOCATIONS AND DIMENSIONS OF EQUIPMENT, PIPING, AND THEIR SUPPORTS ARE SHOWN DIAGRAMMATICALLY AND SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION OF PIPING OR DUCTWORK. ACTUAL DIMENSIONS AND LOCATIONS ARE DEPENDENT ON MATERIAL SUPPLIED BY CONTRACTORS. CONTRACTORS SHALL PROVIDE OR DETERMINE DIMENSIONS AND PROVIDE LAYOUT DRAWINGS FOR COORDINATION WITH OTHER TRADES IN ACCORDANCE WITH THE SPECIFICATIONS.
16x12
FLS
16x12
10/14
R=36
12x12
SS
✔
10/14 SPLIT
14"
AIR FLOW
INC:
REVIEWED FOR
TRANSITIONAL RADIUS ELBOW
14x10 MVD
RETURN DUCT DROP
THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ANY FIELD CHANGES MADE WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE OWNERS REPRESENTATIVE. CONTRACTOR SHALL INSTALL ALL PIPING AND DUCTWORK SYSTEMS TO BEST SUIT FIELD CONDITIONS, AND COORDINATE WITH THE INSTALLATION WORK OF OTHER TRADES. THE DRAWINGS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION OF PIPING. NOTIFY CONSTRUCTION MANAGER OF ANY DEVIATIONS FROM THESE DRAWINGS PRIOR TO FABRICATION AND/OR INSTALLATION.
15 10/14
TRANSITIONAL TURN
SUPPLY DUCT DROP
D
16x12
24x12
APP. 02-117123
14x10
10"
14x10
EXHAUST DUCT DROP
R
IT IS INTENDED THAT THESE PLANS AND SPECIFICATIONS REQUIRE ALL LABOR AND MATERIAL NECESSARY AND PROPER FOR THE WORK CONTEMPLATED AND THAT THIS WORK BE COMPLETED IN ACCORDANCE WITH THEIR TRUE INTENT AND PURPOSE. THE CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE IMMEDIATELY REGARDING ANY DISCREPANCIES OR AMBIGUITIES THAT MAY EXIST IN THE PLANS AND/OR SPECIFICATIONS PRIOR TO SUBMITTING BID. THE OWNER'S REPRESENTATIVE AND THE ENGINEER'S INTERPRETATION THEREOF SHALL BE CONCLUSIVE.
14 10/14
DESCRIPTION
24x12 R
24x12 3.
SYMBOL
SECTION AT EXHAUST DUCT RISER
W
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
ER
1" 0 1/4" 1/2"
SHEET NAME SYMBOLS, NOTES & SCHEDULES MECHANICAL SCHEDULES MECHANICAL TITLE 24 MECHANICAL TITLE 24 FLOOR PLAN - MECHANICAL PIPING AND CONTROLS FLOOR PLAN - MECHANICAL ROOF PLAN - MECHANICAL VRF-1 DIAGRAMS AND DETAILS DETAILS DETAILS MECHANICAL CONTROLS
DUCT SYMBOLS
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
5
GENERAL NOTES
MECHANICAL SHEET LIST SHEET NUMBER M-001 M-002 M-003 M-004 M-111 M-112 M-133 M-401 M-501 M-502 M-601
4
A
3
SE
2
REG I S T
2"
1
CONICAL FITTING
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
24 x 36 AL
24 x 36 AL
MEP COMPONENT ANCHORAGE NOTE ALL MECHANICAL, PLUMBING AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2016 CBC, SECTIONS 1616A.1.18 THROUGH 1616A.1.26 AND ASCE 7-10 CHAPTER 13, 26 AND 30. 1. 2. 3.
ALL PERMANENT EQUIPMENT AND COMPONENTS. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G. HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS OR WATER. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS OR HAS A CENTER OF MASS LOCATED 4 FEET OR MORE ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.
THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT THE ATTACHMENT NEED NOT BE DETAILED ON THE PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING AND CONDUIT. A. B.
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 LIONAKIS 2017
AGENCY
COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. COMPONENTS WEIGHING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE OR STRUCTURAL ENGINEER DELEGATED RESPONSIBILITY AND THE DSA DISTRICT STRUCTURAL ENGINEER. THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE REQUIREMENTS.
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-10 SECTION 13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.5.6, 13.6.7, 13.6.8, AND 2016 CBC, SECTIONS 1616A.1.24, 1616A.1.25 AND 1616A.1.26. THE METHOD OF SHOWING BRACING AND ATTACHMENTS TO THE STRUCTURE FOR THE IDENTIFIED DISTRIBUTION SYSTEM ARE AS NOTED BELOW. WHEN BRACING AND ATTACHMENTS ARE BASED ON A PREAPPROVED INSTALLATION GUIDE (E.G., SMACNA OR OSHPD OPM), COPIES OF THE BRACING SYSTEM INSTALLATION GUIDE OR MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF AND DURING THE HANGING AND BRACING OF THE DISTRIBUTION SYSTEMS. THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS. MECHANICAL PIPING (MP), MECHANICAL DUCTS (MD), PLUMBING PIING (PP), ELECTRICAL DISTRIBUTION SYSTEMS (E): MP MD PP E OPTION 1: DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND DETAILS
A MP
MD
PP
MP
MD
PP
REYQ168TAYDU
E
OPTION 2: SHALL COMPLY WITH THE APPLICABLE OSHPD PRE-APPROVAL (OPM #) #____________. OPTION 3: SHALL COMPLY WITH THE SMACNA SEISMIC RESTRAINT MANUAL, OSHPD EDITION (2009), INCLUDING ANY ADDENDA. FASTENERS AND OTHER ATTACHMENTS NOT SPECIFICALLY IDENTIFIED IN THE SMACNA SEISMIC RESTRAINT MANUAL, OSHPD EDITION, ARE DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND DETAILS. THE DETAILS SHALL ACCOUNT FOR THE APPLICABLE SEISMIC HAZARD LEVEL ___ AND CONNECTION LEVEL ___ FOR THE PROJECT AND CONDITIONS.
TITLE
SYMBOLS, NOTES & SCHEDULES
5/15/2019 9:20:06 AM
SHEET
M-001
2"
1
2
3
4
5
ROOFTOP GAS-ELECTRIC (AC) UNIT SCHEDULE 1"
SUPPLY FAN DAIKIN MODEL NO.
0 1/4" 1/2"
MARK
3000
MBH
RPM
0.5
BHP
1102
HP
0.47
EAT °F
SENSIBLE TOTAL
4
96.1
DB
102.3
LAT °F WB
82
DB
64
WB
52
52
200
160
2
4.5 / 7.9
2
1.8
ELECT. SERVICE V/φ/HZ
MIN CIR AMPS
UNIT FLA
208/3/60
50.5
ARI EER
54.9
ARI IEER
12.1
MOCP
18.8
FILTERS
APPROX. OPER. WT. LBS.
70
UNIT SIZE (L"xW"xH")
3270
QTY
SIZE (IN) 18x24x2 18x24x2
6 6
91x97x57+20" CURB
DESIGN/ (MIN) OSA MERV (CFM)
APP. 02-117123
REMARKS
REVIEWED FOR SS
8 13
SEE NOTES 1-14
770 / (300)
INC:
FLS
✔
✔
07/03/2019
DATE:
NOTES: 1. PROVIDE UNIT WITH 20" SPRING CURB EQUAL TO MASON WEST RSC - 3" DEFLECTION SPRING. SPRING OPA-0207. CURB 2. SELECTED WITH 109°F DB/73°F WB SUMMER AND 31°F DB WINTER TEMPERATURES 3. WEIGHTS SHOWN INCLUDE UNIT CURB, POWER EXHAUST/ECONOMIZER AND ALL ACCESSORIES. 4. PROVIDE DIRECT-DRIVE PLENUM FANS WITH ECM MOTOR FOR VARIABLE SPEED FAN CONTROL 5. PROVIDE 2" MERV 8 PRE-FILTER AND 2" PLEATED MERV 13 FINAL FILTERS INTO INTEGRAL FILTER HOUSING. 6. PROVIDE POWER MODULATING VFD POWER EXHAUST & DRY BULB ECONOMIZER (MPEE) 7. PROVIDE HINGED ACCESS PANELS WITH LEVER HANDLES. 8. PROVIDE CONDENSER COIL GUARDS. 9. PROVIDE AUTOMATIC FAN SHUTDOWN PER CMC SECTION 608.1 USING AN INLINE DUCT SMOKE DETECTOR. FIRE ALARM TO PROVIDE DUCT SMOKE DETECTOR. TO BE INSTALLED BY MECHANICAL IN SUPPLY DUCTWORK. 10. PROVIDE SEPARATE 120V CONVENIENCE OUTLET. 11. COORDINATE WITH ELECTRICAL TO PROVIDE DISCONNECT 12. HEATING LEAVING AIR TEMPERATURE SHALL BE 85°F MINIMUM. 13. PROVIDE WITH (1) INVERTER SCROLL COMPRESSOR AND (1) FIXED SCROLL COMPRESSOR 14. PROVIDE WITH DEMAND CONTROLLED VENTILATION.
ACS
✔
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
ROOFTOP GAS-ELECTRIC DIRECT OUTSIDE AIR SYSTEM (DOAS) UNIT SCHEDULE
CONSULTANT
DOAS-1
DAIKIN MODEL NO.
CFM
REBEL DPS004A
1120
ESP (IN.)
RPM
0.9
1651
MBH BHP
HP
0.27
1.3
EAT °F
SENSIBLE TOTAL 51.6
51.6
GAS HEATING MBH
LAT °F
DB
WB
DB
WB
105
73
63
58
COMPRESSORS CONDENSER FAN QTY.
RLA
QTY.
FLA (EA)
1
4.5
1
0.4
INPUT OUTPUT 80
64
ELECT. SERVICE V/φ/HZ 208/3/60
UNIT FLA
MIN CIR AMPS
ARI EER
ARI SEER
18.6
12.1
17
16.1
MOCP
FILTERS
APPROX. OPER. WT. LBS.
UNIT SIZE (L"xW"xH")
1625
67x87x41+21" CURB
25
QTY 4 4
SIZE (IN) 16x16x2 16x16x2
MINIMUM OUTSIDE MERV AIR(CFM) 8 13
PETERS
1120 (100% OSA)
engineering
SEE NOTES 1-11
consulting mechanical and electrical engineers
REFRIGERANT
MARK
NO.
RLA
MCA
MOCP
LIQUID
ACCU-1
PUZ-A18NKA7
208/1/60
1
7
11
15
1/4
ME
TE
CH AN I CA
O F CA L
ER REG I S T
I N E ER
S
COMPRESSOR ELECTRICAL SERVICE V/φ/HZ.
R. T I C HE
AN
M31176 EXP. 12/31/19 TA
AIR COOLED CONDENSING UNIT SCHEDULE
PRO F E S S I ONA L
ED
R NO
NOTES: 1. PROVIDE UNIT WITH 21" SPRING CURB EQUAL TO MASON WEST ISC - 2" DEFLECTION SPRING. SPRING OPA-0468. CURB 2. SELECTED WITH 105°F DB/73°F WB SUMMER AND 31°F DB WINTER TEMPERATURES 3. WEIGHTS SHOWN INCLUDE SPRING CURB AND ALL ACCESSORIES. 4. PROVIDE DIRECT-DRIVE PLENUM FANS WITH ECM MOTOR. 5. PROVIDE 2" MERV 8 PRE-FILTER AND 2" PLEATED MERV 13 FINAL FILTERS INTO INTEGRAL FILTER HOUSING. 6. PROVIDE HINGED ACCESS PANELS WITH LEVER HANDLES. 7. PROVIDE CONDENSER COIL GUARDS. 8. PROVIDE SEPARATE 120V CONVENIENCE OUTLET. 9. PROVIDE WITH (1) INVERTER SCROLL COMPRESSOR 10. PROVIDE AUTOMATIC FAN SHUTDOWN PER CMC SECTION 608.1 USING AN INLINE DUCT SMOKE DETECTOR. FIRE ALARM TO PROVIDE DUCT SMOKE DETECTOR. TO BE INSTALLED BY MECHANICAL IN SUPPLY DUCTWORK 11. VARY MOTORIZED DAMPERS IN HIGH DENSITY SPACES TO ACHIEVE DEMAND CONTROLLED VENTILATION.
MITSUBISHI ELECTRIC MODEL NO.
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
REMARKS
L
I
A
MARK
DX COOLING COIL
SE
SUPPLY FAN
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
CFM
REBEL DPS010A
AC-1
ESP (IN.)
GAS HEATING COMPRESSORS CONDENSER FAN MBH FLA RLA QTY. QTY. (EA) (EA) INPUT OUTPUT
DX COOLING COIL
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
N I F OR
COOLING ONLY FAN COIL UNIT SCHEDULE
SUCTION
AHRI EER/ (SEER)
UNIT SERVED
WEIGHT (LBS)
1/2
9.9/(18.5)
FC-1
100
REMARKS
1,2,3,4,5
SUPPLY FAN
MARK
MITSUBISHI ELECTRIC MODEL NO.
CFM
QTY
FLA
FC-1
PKA-A18HA7
320
1
0.33
DX COOLING COIL EAT MBH DB °F SENS/TOT WB °F 80 18/18 67
SEAL
ELECTRICAL SERVICE V/φ/HZ
MCA
208/1/60
1
NOTES: 1. REFRIGERANT TYPE R410A 2. WIRED REMOTE CONTROLLER. 3. SELF CHECK FUNCTION 4. DRAIN PIPE CONNECTION SIZE 5/8" 5. INDOOR UNIT POWERED BY OUTDOOR UNIT.
NOTES: 1. REFRIGERANT TYPE R410A 2. DC INVERTER-DRIVEN TWIN ROTARY COMPRESSOR. 3. REFRIGERANT PIPE SIZES PER SCHEDULE. 4. INDOOR UNIT POWERED BY THE OUTDOOR UNIT. PROVIDE WIRING IN CONDUIT. 5. LOCK HEATING SECTION OUT - SHALL BE USED AS COOLING ONLY.
6. 7. 8.
MOCP
WEIGHT (LBS)
ROOM SERVED FLOOR
15
30
IDF 130
REMARKS
SEE NOTES 1-8
PROVIDE UNIT WITH CONDENSATE PUMP. PROVIDE UNIT WITH MOUNTING BOARD. PROVIDE UNIT WITH MERV 8 FILTERS.
PROJECT
C
TEHAMA CENTER STUDENT SERVICE
EXHAUST FAN SCHEDULE FAN
VRF AIR COOLED CONDENSING UNIT SCHEDULE
MOTOR
MARK
GREENHECK MODEL NO.
CFM
E.S.P.
RPM
EF-1
SQ-080-VG
295
0.375
1610
INPUT
DRIVE TYPE
SERVICE V/φ/HZ
1/10 HP
DIRECT
115/1/60
NOTES: 1. COORDINATE WITH ELECTRICAL FOR POWER AND DISCONNECT AS REQUIRED. 2. PROVIDE NEMA PREMIUM EFFICIENCY MOTOR. 3. PROVIDE WITH HANGER KIT.
4. 5. 6.
MOTOR ENCLOSURE ODP
SONES
ROOMS SERVED
WEIGHT
REMARKS
MARK
DAIKIN MODEL NO.
NOMINAL TONS
DESIGN COOLING (MBH)
7.8
RESTROOM, CUSTODIAL
50
SEE NOTES: 1-6
VRF-1
REYQ168TAYDU
14
146
DESIGN HEATING (MBH) 143
CONNECTION RATIO
FACTORY CHARGE (LBS)
ELECTRICAL SERVICE V/φ/HZ
RLA
MCA
MOCP
ARI EER
ARI IEER
COP
DIMENSIONS (LxWxH)
WEIGHT (LBS)
106%
25.8
208/3/60
41.8
61.9
70
11.6
22.0
3.7
49"x30"x67"
800
REMARKS
SEE NOTES
NOTES: 1. REFRIGERANT TYPE R410A 2. SELECTED WITH 109°F DB/73°F WB SUMMER AND 31°F DB WINTER TEMPERATURES
PROVIDE THERMAL OVERLOAD PROVIDE VARI-GREEN EC MOTOR INTERLOCK WITH AC-1
770 DIAMOND AVE. RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
VRF FAN COIL UNIT SCHEDULE
DIFFUSER, REGISTER AND GRILLE SCHEDULE SUPPLY FAN MARK
BORDER TYPE
OBD
TITUS MCD
T-BAR LAY-IN
NO
SD-S
TITUS MCD
SURFACE
NO
WHITE
MODULAR CORE 4-WAY SUPPLY DIFFUSER
SG-1
TITUS 300RL
SURFACE
NO
WHITE
STEEL DOUBLE DEFLECTION SUPPLY GRILLE - 3/4" BLADE SPACING
TITUS 50F
T-BAR LAY-IN
NO
RF-L
PRICE 80FF / TB
T-BAR LAY-IN
NO
WHITE
RF-S
PRICE 730FF / SM
SURFACE
NO
WHITE
TITUS 50F
T-BAR LAY-IN
NO
TITUS 50F
SURFACE
NO
SD-L
RG-L B
EG-L
EG-S
MFR / MODEL
FINISH
DESCRIPTION
WHITE
MARK
NOMINAL TONS
CFM
QTY
FXSQ09TAVJI
0.8
DUCTED
320
1
FC-Z02
FXSQ24TAVJI
2.0
DUCTED
740
1
FC-Z03
FXSQ12TAVJI
1.0
DUCTED
335
1
FC-Z04
FXSQ05TAVJI
0.5
DUCTED
280
1
FC-Z05
FXSQ15TAVJI
1.3
DUCTED
525
1
1/2x1/2x1/2 CORE FILTER RETURN GRILLE. PROVIDE WITH 20"x20"x2" MERV 8 FILTER TO FIT LAY-IN 2" FILTER HOUSING
FC-Z06
FXSQ05TAVJI
0.5
DUCTED
280
1
3/4" BLADE SPACING AT 45° - FILTER RETURN HORIZONTAL VANES. PROVIDE WITH DEEP MERV FILTER TO FIT SURFACE MOUNTED 2" FILTER HOUSING. SEE RETURN GRILLE SCHEDULE ON SHEET M-111 FOR 2" FILTER FACE DIMENSIONS.
FC-Z07
FXSQ05TAVJI
0.5
DUCTED
280
1
FC-Z08
FXSQ24TAVJI
2.0
DUCTED
750
1
FC-Z09
FXSQ12TAVJI
1.0
DUCTED
335
1
FC-Z10
FXSQ18TAVJI
1.5
DUCTED
600
1
FC-Z11
FXZQ05TAVJU
0.5
CASSETTE 2'x2'
300
1
FC-Z12
FXZQ05TAVJU
0.5
CASSETTE 2'x2'
300
1
FC-Z13
FXZQ05TAVJU
0.5
CASSETTE 2'x2'
300
1
FC-Z14
FXZQ05TAVJU
0.5
CASSETTE 2'x2'
300
1
FC-Z15
FXZQ05TAVJU
0.5
CASSETTE 2'x2'
300
1
REMARKS
FC-Z16
FXZQ05TAVJU
0.5
CASSETTE 2'x2'
300
1
ALUMINUM EGGCRATE RETURN - 1/2"x1/2"x1/2" CORE
WHITE
ALUMINUM EGGCRATE EXHAUST - 1/2"x1/2"x1/2" CORE
WHITE
ALUMINUM EGGCRATE EXHAUST - 1/2"x1/2"x1/2" CORE
ROOFTOP RELIEF HOOD SCHEDULE
COOLING EAT MBH SENS/TOT DB °F WB °F 75 6.1/8.5 63 75 15.2/21.1 63 75 8.4/10.5 63 75 4.3/5.2 63 75 10.0/13.1 63 75 4.3/5.3 63 75 4.3/5.3 63 75 15.2/21.1 63 75 8.4/10.5 63 75 12.0/15.7 63 75 4.3/5.0 63 75 4.3/5.0 63 75 4.3/5.0 63 75 4.3/5.0 63 75 4.3/5.0 63 75 4.3/5.0 63 75 4.3/5.0 63 75 4.3/5.0 63
HEATING
ELECTRICAL SERVICE V/φ/HZ SUCTION
MCA
MOCP
OSA (CFM)
WEIGHT (LBS)
208/1/60
0.8
15
150
55
SEE NOTES 1-3
5/8"
208/1/60
1.8
15
390
85
SEE NOTES 1-3
1/4"
1/2
208/1/60
0.8
15
50
55
SEE NOTES 1-3
70
1/4"
1/2
208/1/60
0.8
15
30
55
SEE NOTES 1-3
17.1
70
1/4"
1/2
208/1/60
1.4
15
45
60
SEE NOTES 1-3
6.5
70
1/4"
1/2
208/1/60
0.8
15
50
55
SEE NOTES 1-3
6.5
70
1/4"
1/2
208/1/60
0.8
15
50
55
SEE NOTES 1-3
27.0
70
3/8"
5/8"
208/1/60
1.8
15
45
85
SEE NOTES 1-3
13.6
70
1/4"
1/2
208/1/60
0.8
15
65
55
SEE NOTES 1-3
20.1
70
1/4"
1/2
208/1/60
1.6
15
150
80
SEE NOTES 1-3
6.5
70
1/4"
1/2
208/1/60
0.3
15
15
35
SEE NOTES 1-3
6.5
70
1/4"
1/2
208/1/60
0.3
15
15
35
SEE NOTES 1-3
6.5
70
1/4"
1/2
208/1/60
0.3
15
15
35
SEE NOTES 1-3
6.5
70
1/4"
1/2
208/1/60
0.3
15
15
35
SEE NOTES 1-3
6.5
70
1/4"
1/2
208/1/60
0.3
15
15
35
SEE NOTES 1-3
6.5
70
1/4"
1/2
208/1/60
0.3
15
15
35
SEE NOTES 1-3
6.5
70
1/4"
1/2
208/1/60
0.3
15
15
35
SEE NOTES 1-3
6.5
70
1/4"
1/2
208/1/60
0.3
15
15
35
SEE NOTES 1-3
EAT
10.6
70
1/4"
1/2
27.0
70
3/8"
13.6
70
6.5
LIQUID
DATE 01/04/2019 05/17/2019
CFM
FPM
SP (IN W.G.)
THROAT SIZE
HOOD SIZE
CURB SIZE
RH-1
FGR-10x10
295
425
0.04
10"x10"
20"x24"
16"x16"
14"
50
SEE NOTES 1-3
FC-Z17
FXZQ05TAVJU
0.5
CASSETTE 2'x2'
300
1
RH-2
FGR-8x8
150
340
0.03
8"x8"
18"x24"
14"x14"
14"
50
SEE NOTES 1-3
FC-Z18
FXZQ05TAVJU
0.5
CASSETTE 2'x2'
300
1
RH-3
FGR-8x8
215
485
0.04
8"x8"
18"x24"
14"x14"
14"
50
SEE NOTES 1,2
RH-4
FGR-10x10
250
360
0.04
10"x10"
20"x24"
16"x16"
14"
50
SEE NOTES 1-3
NOTES: 1. REFRIGERANT TYPE R410A 2. SEE MANUFACTURER'S SUBMITTAL FOR FULL PIPING LAYOUT AND REFRIGERANT LINES SIZES 3. MFR INTEGRAL CONDENSATE PUMP AND INTEGRAL FLOAT SWITCH FOR AUTOMATIC SHUT-OFF
RH-5
FGR-10x16
540
485
0.06
10'x16"
20"x36"
16"x22"
14"
60
SEE NOTES 1-3
REMARKS
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
NOTES: 1. FACTORY PROVIDED GALVANIZED BIRDSCREEN 2. FACTORY PROVIDED 12" STANDARD ROOF CURB - SLOPED TO MATCH ROOF PITCH. 3. PROVIDE BACKDRAFT DAMPER. A
BRANCH SELECTOR BOX SCHEDULE SERVICE
ELECTRICAL SERVICE V/φ/HZ
MCA
BS10Q54TVJ
VRF-1
208/1/60
1.0
15
54
32"x12"x19"
100
SEE NOTES: 1
BS8Q54TVJ
VRF-1
208/1/60
0.8
15
54
22"x12"x19"
75
SEE NOTES: 1
MARK
DAIKIN MODEL NO.
BSB-1 BSB-2
MAX DIMENSIONS MOCP CAPACITY (LxWxH) (MBH)
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
MANAGEMENT
GREENHECK MODEL NO.
HOOD WEIGHT HEIGHT (LBS.)
REFRIGERANT BRANCH SIZE
MBH
MARK
NOTES: 1. NO DRAIN PIPING NEEDED 5/15/2019 9:20:06 AM
TYPE
FC-Z01
NOTES: 1. PROVIDE STEEL GRILLES IN ALL CUSTODIAL AND RESTROOM AREAS 2. COORDINATE FINAL FINISH COLOR WITH ARCHITECT.
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
DAIKIN MODEL NO.
MODULAR CORE 4-WAY SUPPLY DIFFUSER
WHITE
MARK
WEIGHT (LBS)
REMARKS
TITLE
MECHANICAL SCHEDULES
SHEET
M-002
017294 LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR FLS
✔
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
SE
R. T I C HE
AN
M31176 EXP. 12/31/19 ME
TE
CH AN I CA
O F CA L
L
I
A
S
TA
I N E ER
REG I S T
PRO F E S S I ONA L
ED
R NO
ER
consulting mechanical and electrical engineers
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
✔
07/03/2019
DATE:
D
ACS
✔
N I F OR
SEAL
PROJECT
C
TEHAMA CENTER STUDENT SERVICE 770 DIAMOND AVE. RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 LIONAKIS 2017
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
AGENCY
A
TITLE
MECHANICAL TITLE 24
5/15/2019 9:20:08 AM
SHEET
M-003
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR FLS
✔
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
SE
R. T I C HE
AN
M31176 EXP. 12/31/19 ME
TE
CH AN I CA
O F CA L
L
I
A
S
TA
I N E ER
REG I S T
PRO F E S S I ONA L
ED
R NO
ER
consulting mechanical and electrical engineers
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
✔
07/03/2019
DATE:
D
ACS
✔
N I F OR
SEAL
PROJECT
C
TEHAMA CENTER STUDENT SERVICE 770 DIAMOND AVE. RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 LIONAKIS 2017
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
AGENCY
A
TITLE
MECHANICAL TITLE 24
5/15/2019 9:20:09 AM
SHEET
M-004
2"
1
2
3
4
5
KEYED NOTES: 1"
SUPPLY DIFFUSER SCHEDULE Type SD-L SD-L SG-1 SG-1 SD-L SG-1 SD-S SD-L
Neck Size 6"x6" 10"x10" 12"x6" 18"x6" 8"x8" 14"x6" 6"x6" 14"x14"
Duct Size 6"ø 10"ø 12"x6" 18"x6" 8"ø 14"x6" 6"ø 12"ø
ID#
Type
R01 R02 R03 R04 R05 R06
Neck Size
RF-L RF-L RF-S RF-L RF-S RG-L
EXHAUST GRILLE SCHEDULE 2" FILTER SIZE 20"x20" 20"x20" 20"x10" 20"x20' 24"x12" NONE
Duct Size
22"x22" 22"x22" 20"x10" 22"x22" 24"x12" 22"x22"
8"ø 12"ø 20"x10" 10"ø 24"x12" 14"ø
ID# E01 E02 E03 E04
Type EG-S EG-L EG-S EG-S
Neck Size 8"x8" 8"x8" 10"x10" 10"x16"
Duct Size 8"x8" 8"x8" 10"x10" 10"x16"
1
DASHED LINES IN FRONT OF COILS REPRESENT CLEARANCE LINES, TYPICAL.
9
SUPPORT INLINE EXHAUST FAN TO ROOF FRAMING ABOVE PER DETAIL 1/M-502.
2
LINED SUPPLY AIR DUCT FROM AC UNIT ABOVE. TRANSITION WITHIN ROOF CURB AND/OR UNDERSIDE OF ROOF STRUCTURE TO DUCT SIZE AS INDICATED. CONNECT DUCT TO UNIT COMPLETE WITH FLEXIBLE CONNECTION, TYPICAL.
10
SUPPORT BRANCH SELECTOR BOX TO ROOF FRAMING ABOVE CEILING PER DETAIL 1/M-502. TYPICAL OF 2.
LINED RETURN AIR DUCT FROM AC UNIT ABOVE. TRANSITION WITHIN ROOF CURB AND/OR UNDERSIDE OF ROOF STRUCTURE TO DUCT SIZE AS INDICATED. CONNECT DUCT TO UNIT COMPLETE WITH FLEXIBLE CONNECTION, TYPICAL.
3
4
ROUTE DUCTWORK TIGHT TO UNDERSIDE OF ROOF FRAMING MEMBERS, FIELD COORDINATE DUCT ROUTING WITH STRUCTURAL MEMBERS, PIPING, SUPPORTS, LIGHT FIXTURES, ETC. SEE DETAILS 3 & 4/M-502, TYPICAL.
5
FURNISH AND INSTALL MANUAL VOLUME DAMPERS (MVD) IN INDIVIDUAL BRANCH DUCT. BALANCE TO AIR VOLUME SHOWN, TYPICAL.
6
DUCT UP TO GRAVITY VENTILATOR. SEE SHEET M-133 FOR CONTINUATION.
7
SECURE FAN COIL UNIT TO HIGH WALL FRAMING MEMBERS ABOVE DOOR. FIELD VERIFY LOCATION WITH STRUCTURAL MEMBERS. OFFSET AND ROUTE REFRIGERANT LINES ABOVE FINISHED CEILING. SEE DETAIL 6/M-501.
D
DUCT SMOKE DETECTOR DEVICE IN SUPPLY DUCT PER CMC 2016, CHAPTER 6, SECTION 608. CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR FOR POWER AND FIRE ALARM. ELECTRICAL TO PROVIDE, MECHANICAL TO INSTALL, TYPICAL.
8
SHEET NOTES:
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1. PROVIDE CONICAL FITTINGS FROM ROUND TO RECTANGULAR DUCT CONNECTIONS. 2. PROVIDE SHOE FITTING AT ALL RECTANGULAR TO RECTANGULAR DUCT BRANCHES 3. FLEXIBLE DUCT IS LIMITED TO 5'-0" IN LENGTH. 4. PROVIDE MANUAL VOLUME DAMPER AT EVERY BRANCH DUCT. 5. PROVIDE TURNING VANES AT ALL RECTANGULAR DUCTWORK WITH 90° ELBOWS 6. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR ACCESS PANEL LOCATIONS SERVICING MANUAL VOLUME DAMPERS AND EQUIPMENT ABOVE HARD LID CEILINGS. 7. ALL ACCESS TO BE MAINTAINED. NO DUCTS OR PIPING LOCATIONS SHALL IMPEDE MAINTENANCE REQUIREMENTS. 8. UNDERCUTS NOTED ON PLANS ARE 3/4" MIN. REFER TO ARCHITECTURAL DRAWINGS. 9. PROVIDE MANUAL VOLUME DAMPERS AT ALL OUTSIDE AIR BRANCH DUCTS TO RETURN PLENUM OF FAN COILS. MANUAL VOLUME DAMPERS SHALL BE BALANCED TO PROVIDE OSA CFM LISTED ON SHEET M-002. 10. PROVIDE FLEXIBLE CONNECTIONS TO BETWEEN DUCTWORK AND ALL PIECES OF MECHANICAL EQUIPMENT, UNLESS OTHERWISE NOTED.
APP. 02-117123
REVIEWED FOR SS
FLS
✔
11
SUPPORT VRF DUCTED INDOOR FAN COIL TO ROOF FRAMING ABOVE CEILING PER DETAIL 1/M-502, TYPICAL OF 10.
12
SUPPORT VRF CASSETTE TYE INDOOR FAN COIL PER DETAIL 8/M-502, TYPICAL OF 8.
13
DIFFUSER INSTALLATION PER DETAIL 7/M-502. USE UNCONFINED CONFIGURATION WHERE POSSIBLE AND CONFINED CONFIGURATION WHEN CEILING SPACE IS LIMITED. FLEXIBLE AIR DUCTS AND CONNECTORS SHALL NOT BE MORE THAN 5 FEET IN LENGTH AND SHALL NOT BE USED IN LIEU OF RIGID ELBOWS OR FITTINGS PER 2016 CMC 603.4.1.
14
CENTER OF AIR TERMINAL AT 13'-6" ABOVE FINISHED FLOOR.
15
CENTER OF AIR TERMINAL AT 10'-10" ABOVE FINISHED FLOOR.
16
MOTORIZED DAMPER FOR DEMAND CONTROLLED VENTILATION IN SPACE
17
DIFFUSER MOUNTED ON WALL OF DUCT CHASE. SEE ARCHITECTURAL DRAWINGS.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
18
DUCTWORK IN DUCT CHASE. SEE ARCHITECTURAL DRAWINGS.
CONSULTANT
19
CENTER OF AIR TERMINAL AT 13'-0" ABOVE FINISHED FLOOR.
20
CENTER OF AIR TERMINAL AT 13'-9" ABOVE FINISHED FLOOR.
2
3
4
5
6
✔
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
engineering
7
ACS
✔
07/03/2019
DATE:
PETERS
1
INC:
SE
R. T I C HE
AN
M31176 EXP. 12/31/19 ME
TE
CH AN I CA
O F CA L
L
I
A
S
TA
I N E ER
REG I S T
PRO F E S S I ONA L
ED
R NO
ER
consulting mechanical and electrical engineers
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
ID# S01 S02 S03 S04 S05 S06 S07 S08
RETURN GRILLE SCHEDULE
N I F OR
E
SEAL
D COUNSELOR
COUNSELOR
128
130
132
FC Z11
FC Z12
12
FC Z13
12
FC Z14
12
R06 900 CFM
12
26"x8" AL
SD
2
8
4
20"x20" AL
4"ø
4"ø
4"ø
3
FC Z01
R06 900 CFM
R06 900 CFM
S08 530 CFM
C
SD
10"ø
2
UCD
UCD 10"ø
4"ø
S01 70 CFM
HALLWAY
14"ø
6"ø
100D
8"ø 12"ø
18"ø
38"x12"
UCD
UCD 4"ø
4"ø
UCD FC Z02
BSB 2
14"x8"
11
12
1 32"x12"
10"ø
12
12
CLIENT
LOBBY
S03 225 CFM
14"ø
8"ø
S03 225 CFM
100 19
19
S04 315 CFM
12"x6"
FACE OF SOFFIT (SEE ARCHITECTURAL DRAWINGS)
FC Z16
14
14
18
FC Z18
12
COUNSELOR
COUNSELOR
125
127
129
131
R03 95 CFM
14
E04 N/A
S03 145 CFM
14
151
6
101
MARK
103
FACE OF SOFFIT (SEE ARCHITECTURAL DRAWINGS)
100C
S01 50 CFM
STUDENT SERVICES
WORK CENTER
B
FC 1
7
UCD
STUDENT SERVICES
STUDENT SERVICES
107
106
E03 N/A
6
UCD
8"ø
FC Z10
11
16
M
IDF
STORAGE
121
120
19
S07 65 CFM
38"x14"
BDD 8"x8"
6
8"x8"
E01 120 CFM
14"ø
BDD
UCD E02 N/A
S02 240 CFM
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
S02 300 CFM
14"x12"
FC Z09
S01 95 CFM
123
B.6
E01 75 CFM
11
14"x8"
10"x10"
EF 1
10"x10"
S05 175 CFM
6"ø
R01 155 CFM
S05 160 CFM
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
FACE OF SOFFIT (SEE ARCHITECTURAL DRAWINGS)
AGENCY 11
FC Z05
10"ø
26"x10"
6
S05 175 CFM
MANAGEMENT
FC Z04
6"ø 20"x8"
FC Z07
VET OFFICE 8"ø
122 10"ø
S01 70 CFM
R01 55 CFM
20"x10" 10"ø
R01 55 CFM
S01 70 CFM
8"ø
10"ø
10"ø
R01 55 CFM
S01 70 CFM
20"x12"
R01 55 CFM
FC Z06
38"x14"
R01 55 CFM
R01 55 CFM S01 70 CFM
10"ø
S01 70 CFM
11
S01 70 CFM
10"ø
R01 75 CFM
11
6"ø
10"ø
R01 55 CFM
R01 55 CFM
R02 450 CFM R04 205 CFM
R01 160 CFM
S05 175 CFM
R01 160 CFM 12"ø
118
11
S01 70 CFM VET CENTER
PROVIDE MVD E01 100 CFM
14"ø
PROVIDE MVD E02 N/A
10"ø
105
6"ø
S07 90 CFM
CUSTODIAL 119
10"ø
R03 145 CFM
20
RESTROOM
12"ø
FACULTY OFFICE
UCD
S03 225 CFM
S07 110 CFM
6"ø
100B
UCD
6"ø
S02 300 CFM
C
UCD
HALLWAY
108
19
S03 225 CFM
10"ø
FC Z08
8"ø
11
S01 70 CFM
FACULTY OFFICE
14"ø
12"ø
32"x14"
12"ø
R01 105 CFM
S01 120 CFM
109
10"ø
FACULTY OFFICE
117
UCD
FACULTY OFFICE
116
UCD
FACULTY OFFICE
115
S06 250 CFM
B UCD
FACULTY OFFICE
114
UCD
FACULTY OFFICE
113
S06 250 CFM
UCD 6
E01 N/A
FACULTY OFFICE
112
UCD
S06 250 CFM
UCD
FACULTY OFFICE
111
UCD FACULTY OFFICE
R05 700 CFM
UCD
15
110
FACULTY HALLWAY
150
A
TITLE
A
FLOOR PLAN MECHANICAL
5/15/2019 9:20:14 AM
SHEET PLAN NORTH
1 M-111
FLOOR PLAN - MECHANICAL 1/4" = 1'-0"
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
104
17
100A 8"ø
DATE 01/04/2019 05/17/2019
ADMIN OFFICE
S03 125 CFM
HALLWAY
124
ISSUED
STUDENT SERVICES
UCD CONFERENCE
FACE OF SOFFIT (SEE ARCHITECTURAL DRAWINGS)
14
8"ø
10"ø
COUNSELOR
S03 110 CFM
S04 315 CFM
CLASSROOM/LOBBY OVERFLOW
COUNSELOR
FIRE RISER
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
R01 125 CFM
C.4
UCD
4"ø
FC Z15
8"ø 10"ø
8"ø
4"ø
FC Z17
770 DIAMOND AVE. RED BLUFF, CA 96080
M
16
8"ø
UCD
11
FC Z03
10"ø
14"ø
10
10"ø
10"ø
14"ø
10
BSB 1
10"x10"
6"ø
32"x20" AL
TEHAMA CENTER STUDENT SERVICE
R01 160 CFM
28"x32" AL
UCD
102
PROJECT
M
16
8
S05 190 CFM
S05 160 CFM
10"x10"
8"ø
UCD
11
S05 160 CFM
16"x24" AL
S08 530 CFM
S08 530 CFM
ADMIN OFFICE R04 255 CFM
20"x12"
126
R01 170 CFM
20"x12"
COUNSELOR
24"x16" AL
CAMPUS SAFETY
M-111
017294 LIONAKIS 2017
2"
1
2
3
4
5
KEYED NOTES: FURNISH AND INSTALL THERMOSTAT AND SENSOR ON WALL AT +48” TO TOP OF THERMOSTAT AT LOCATION SHOWN. COORDINATE LOCATION WITH ARCHITECT PRIOR TO ROUGH IN. TYPICAL.
2
REFRIGERANT PIPING UP THROUGH ROOF USING ROOF JACK PER DETAIL 7/M-502
3
SECURE REFRIGERANT LINE SET TO STRUCTURE ABOVE PER DETAIL 6/M-502. TYPICAL.
4
PIPEWORK IN ARCHITECTURAL CHASE. SEE ARCHITECTURAL DRAWINGS.
5
PROVIDE TEMPERATURE CONTROLS ROUTER PER SHEET M-601. COORDINATE WITH ELECTRICAL TO PROVIDE 120V/1Ø AND DATA DROP. COORDINATE LOCATION WITH OTHER ELECTRICAL PANELS.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1. REFER TO SHEET M-401 AND EQUIPMENT SUBMITTAL FOR VRF REFRIGERANT PIPING SIZING. 2. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR ACCESS PANEL LOCATIONS SERVICING EQUIPMENT ABOVE HARD LID CEILINGS. 3. ALL ACCESS TO BE MAINTAINED. NO DUCTS OR PIPING LOCATIONS SHALL IMPEDE MAINTENANCE REQUIREMENTS.
APP. 02-117123
INC:
REVIEWED FOR SS
FLS
✔
ACS
✔
✔
07/03/2019
DATE:
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
1
2
3
4
5
6
engineering
7
SE
R. T I C HE
AN
M31176 EXP. 12/31/19 ME
TE
CH AN I CA
O F CA L
L
I
A
S
TA
I N E ER
REG I S T
PRO F E S S I ONA L
ED
R NO
ER
consulting mechanical and electrical engineers
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
1"
1
SHEET NOTES: CO2
N I F OR
E
SEAL
D
C
CAMPUS SAFETY
COUNSELOR
COUNSELOR
COUNSELOR
126
128
130
132
FC Z11
FC Z12
FC Z13
ADMIN OFFICE
PROJECT
TEHAMA CENTER STUDENT SERVICE
102
FC Z14
FC Z01
LOBBY FC-Z11 T
T FC-Z12
FC-Z13 T
100
T FC-Z14
CLASSROOM/LOBBY OVERFLOW
3
770 DIAMOND AVE. RED BLUFF, CA 96080
FC-Z03 T
FC Z03
101
2
FC Z02
BSB 2
ACCU-1
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
BSB 1
HALLWAY 100D
C.4 FC-Z15 T
T FC-Z16
FC Z15
FC-Z17 T
FC Z17
FC Z16
VRF-1
T FC-Z18
T FC-Z01 C T FC-Z02 C
2
ADMIN OFFICE 104 STUDENT SERVICES
FC Z18
ISSUED
MARK
103 COUNSELOR
COUNSELOR
COUNSELOR
COUNSELOR
125
127
129
131
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
C AC-1 T C
4
FIRE RISER 151 CONFERENCE
HALLWAY
HALLWAY
100C
100B
124 B
WORK CENTER
FC-Z10 T C
100A FC 1
T FC-Z04
FC-Z05 T
T FC-1 S BMS STUDENT SERVICES
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
108
107
106
105
IDF
B.6
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
121
FC Z10
STORAGE
CUSTODIAL
RESTROOM
120
119
118
VET CENTER 123
5
LIONAKIS 2017
AGENCY
FC Z07
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
FACULTY OFFICE
FACULTY OFFICE
114
113
FACULTY OFFICE
FC Z06
112 FACULTY OFFICE
FC Z08
FACULTY OFFICE
111
109 FACULTY OFFICE
122
110 T FC-Z06
T FC-Z07 FC-Z08
B
T
FACULTY HALLWAY
150 A
TITLE
A
PIPING AND CONTROLS FLOOR PLAN MECHANICAL SHEET
5/15/2019 9:20:17 AM
017294
FC Z05
FC-Z09 T
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
FC Z04
TCP
FC Z09
VET OFFICE
MANAGEMENT
PLAN NORTH
1 M-112
PIPING AND CONTROLS - MECHANICAL 1/4" = 1'-0"
M-112
2"
1
2
3
4
0 1/4" 1/2"
1"
1
KEYED NOTES:
SHEET NOTES:
SECURE ROOFTOP AC UNIT TO ROOF FRAMING MEMBERS AS REQUIRED. FIELD VERIFY FINAL UNIT LOCATION AND DUCT DROPS THROUGH ROOF WITH STRUCTURAL MEMBERS. REFER TO DETAIL 1/M-501 FOR MOUNTING, TYPICAL.
1. SEE SHEET M-501 FOR TYPICAL ROOF MOUNTING EQUIPMENT DETAILS 2. ALL ACCESS TO BE MAINTAINED. NO PIPING LOCATION SHALL IMPEDE MAINTENANCE REQUIREMENTS.
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
3
SECURE AIR-COOLED CONDENSING VRF UNIT TO ROOF FRAMING AT LOCATION SHOWN. FIELD VERIFY FINAL UNIT LOCATION. SEE DETAIL 3/M-501 FOR MOUNTING. ROUTE REFERIGERANT LINES THRU ROOF AT LOCATION SHOWN. SEAL ROOF PENETRATION WEATHER-TIGHT. WRAP REFRIGERANT SUCTION LINE WITH INSULATION. SEE DETAIL 7/M-501 FOR REFRIGERANT PIPE THROUGH ROOF.
4
SECURE AIR-COOLED CONDENSING UNIT TO ROOF FRAMING AT LOCATION SHOWN. FIELD VERIFY FINAL UNIT LOCATION. SEE DETAIL 4/M-501 FOR MOUNTING.
5
ROUTE REFERIGERANT LINES THRU ROOF AT LOCATION SHOWN. SEAL ROOF PENETRATION WEATHER-TIGHT. WRAP REFRIGERANT SUCTION LINE WITH INSULATION. SEE DETAIL 7/M-501 FOR REFRIGERANT PIPE THROUGH ROOF.
6
INSTALL ROOFTOP GRAVITY RELIEF/INTAKE HOOD PER DETAIL 5/M-501, TYPICAL.
7
SUPPORT REFRIGERNAT PIPING ON ROOF PER DETAIL 9/M-501, TYPICAL.
8
ROOFTOP EQUIPMENT CLEARANCE LINE, TYPICAL.
D
INC:
REVIEWED FOR
SECURE ROOFTOP DOAS TO ROOF FRAMING MEMBERS AS REQUIRED. FIELD VERIFY FINAL UNIT LOCATION AND DUCT DROPS THROUGH ROOF WITH STRUCTURAL MEMBERS. REFER TO DETAIL 2/M-501 FOR MOUNTING, TYPICAL.
2
SS
FLS
✔
ACS
✔
✔
07/03/2019
DATE:
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
consulting mechanical and electrical engineers
3
4
5
6
7
M31176 EXP. 12/31/19
S
TA
ME
TE
CH AN I CA
O F CA L
I N E ER
SE
R. T I C HE
AN
R NO
REG I S T
PRO F E S S I ONA L
ED
L
I
A
2
ER
1
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
5
N I F OR
E SEAL
D 2
DOAS 1
OSA
8 PROJECT
C
EA AC 1
OSA
TEHAMA CENTER STUDENT SERVICE
1
770 DIAMOND AVE. RED BLUFF, CA 96080 8
VRF 1
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
3
5
ACCU 1
4
C.4 ISSUED
MARK
6
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
RH 5
C RH 4
3" VTR
6
B
MANAGEMENT
B.6
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
4" VTR AGENCY
RH 1
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
6
6
RH 3
B
RH 2
A
6 TITLE
A
ROOF PLAN MECHANICAL
5/15/2019 9:20:18 AM
SHEET PLAN NORTH
1 M-133
ROOF PLAN - MECHANICAL 1/4" = 1'-0"
M-133
017294 LIONAKIS 2017
2"
1
2
3
4
5
TO CENTRALIZED CONTROLLER IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
L1, L2, L3 36.1A 3ph
L1, L2 0.3A 1ph
OUT F1,F2
REYQ168TAYDU
P1,P2 VRF-1 REYQ168TAYDU
0 1/4" 1/2"
APP. 02-117123
IN F1,F2
F1,F2
FC-Z11 FXZQ05TAVJU
BRC1E73 (1)
INC:
REVIEWED FOR SS
VRF 1
FLS
✔
ACS
✔
✔
07/03/2019
DATE:
L1, L2 0.3A 1ph P1,P2
5/8x1-1/8x7/8"
3/8x7/8x3/4" KHRP25M72TU9
L1, L2 0.3A 1ph
BSB 1
BS10Q54TVJ
1/4x1/2"
A
FC Z11
FXZQ05TAVJU
3/8x7/8x3/4"
P1,P2 BRC1E73 (1)
BSB- 2 BS8Q54TVJ
L1, L2 0.3A 1ph
B
P1,P2
FXSQ09TAVJU 1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
FC Z12
FXZQ05TAVJU BRC1E73 (1) B
3/8x5/8"
P1,P2 F1,F2
1/4x1/2"
C BRC1E73 (1)
FC Z13
PETERS
FXZQ05TAVJU
consulting mechanical and electrical engineers
C
1/4x1/2"
FC Z03
FXSQ12TAVJU 1/4x1/2"
D
FC Z14
FXZQ05TAVJU
M31176 EXP. 12/31/19
S
TA
L1, L2 0.3A 1ph P1,P2 F1,F2
FC-Z17 FXZQ05TAVJU
D
1/4x1/2"
BRC1E73 (1) 1/4x1/2"
L1, L2 0.3A 1ph
CH AN I CA
O F CA L
L
N I F OR
I
FC Z15
FXZQ05TAVJU
SEAL
P1,P2 F1,F2
FC Z04
ME
TE
FXSQ05TAVJU E
FC-Z18 FXZQ05TAVJU
R. T I C HE
AN
I N E ER
BRC1E73 (1)
PRO F E S S I ONA L
ED
R NO
P1,P2 F1,F2
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
engineering
L1, L2 0.3A 1ph FC-Z16 FXZQ05TAVJU
CONSULTANT
FXSQ24TAVJU
L1, L2 0.3A 1ph FC-Z15 FXZQ05TAVJU
FC Z02
ER
F1,F2
FC-Z14 FXZQ05TAVJU
1/4x1/2"
SE
D
1/4x1/2"
A
FC Z01
REG I S T
F1,F2
FC-Z13 FXZQ05TAVJU
A
BRC1E73 (1)
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
F1,F2
FC-Z12 FXZQ05TAVJU
BRC1E73 (1) E
1/4x1/2"
FC Z05
FXSQ15TAVJU L1, L2 1.6A 1ph
1/4x1/2"
F
P1,P2 F1,F2
FC-Z10 FXSQ18TAVJU
FC Z16
FXZQ05TAVJU BRC1E73 (1)
F
1/4x1/2"
L1, L2 0.8A 1ph C
FXSQ05TAVJU
P1,P2 F1,F2
FC-Z09 FXSQ12TAVJU
1/4x1/2"
G
BRC1E73 (1)
FXZQ05TAVJU
G
P1,P2 FC-Z01 FXSQ09TAVJU
1/4x1/2"
FC Z07
1/4x1/2"
H
FC Z18 CLIENT
FXZQ05TAVJU L1, L2 1.8A 1ph P1,P2 F1,F2
770 DIAMOND AVE. RED BLUFF, CA 96080
FXSQ05TAVJU BRC1E73 (1)
FC-Z02 FXSQ24TAVJU
PROJECT
TEHAMA CENTER STUDENT SERVICE
FC Z17
L1, L2 0.8A 1ph
F1,F2
FC Z06
H
BRC1E73 (1) 1/4x1/2"
I
L1, L2 0.8A 1ph
3/8x5/8"
FC Z08
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
FXSQ24TAVJU
FC Z10
FXSQ18TAVJU
P1,P2 F1,F2
FC-Z03 FXSQ12TAVJU
BRC1E73 (1) ISSUED
MARK L1, L2 0.8A 1ph
F1,F2
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
FXSQ12TAVJU
FC-Z04 FXSQ05TAVJU
BRC1E73 (1)
1
L1, L2 1.4A 1ph
M-401
P1,P2 F1,F2
1/4x1/2"
J
P1,P2
FC Z09
FC-Z05 FXSQ15TAVJU
VRF PIPING DIAGRAM 1/8" = 1'-0"
BRC1E73 (1)
L1, L2 0.8A 1ph P1,P2
B F1,F2
FC-Z06 FXSQ05TAVJU
BRC1E73 (1) VRF-1 (18) REYQ168TAYDU
L1, L2 0.8A 1ph
MANAGEMENT
P1,P2 F1,F2
FC-Z07 FXSQ05TAVJU
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
BRC1E73 (1) L,N ETHERNET 100BASE-TX
L1, L2 1.8A 1ph
F1,F2
3
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
M-401
A
VRF WIRING DIAGRAM 1/8" = 1'-0"
AGENCY
BRC1E73 (1)
BMS SYSTEM TO MONITOR THE VRF SYSTEM VIA BACNET INTERFACE. OWNER TO DETERMINE WHICH BACNET POINTS SHALL BE MONITORED FROM AVAILABLE POINTS.
2 M-401
VRF CONTROLLER WIRING 1/8" = 1'-0"
TITLE
VRF-1 DIAGRAMS AND DETAILS
SHEET
5/15/2019 9:20:19 AM
LIONAKIS 2017
ITOUCH MANAGER DCM601A71
P1,P2 FC-Z08 FXSQ24TAVJU
017294
M-401
3
4
APPLIES TO UNITS: VRF-1
5 APPLIES TO UNITS: AC-1 IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
CONDENSING UNIT
VRF UNIT
SPRING ISOLATOR EQUAL TO MASON WEST SLR - 2" (ONE EACH CORNER)
REFRIGERANT LINE
MIN.6"
18COUNTER GA. COUNTER 18 GA. FLASHING FLASHING CAP CAP
ROOFING MATERIAL
3/8"Øx3" EMBED 3/8"Øx3" EMBED LAG LAG SCREWS PER SIDE) SCREWS (MIN.(MIN. 2 PER2 SIDE)
4x4 BLOCKING WITH SIMPSON A34 EACH SIDE, END, TYP.
SUPPORT SIMILAR TO ACCU ON ROOF
12" 12"
AT JOINTS WELDWELD AT JOINTS PER SINGLE-PLY PER SINGLE-PLY MANUFACTURER MANUFACTURER REQUIREMENTS REQUIREMENTS
D
1/4" DIA. 12 HOLES
3" 3/4" TYP.
7/8" TYP.
CONSULTANT ANCHORING CLIP PLYWOOD SHEATHING PLYWOOD SHEATHING OVEROVER STRUCTURAL STRUCTURAL TJIs TJIs
CURB TO EXTEND 6" BEYOND PIPE EACH SIDE
5-1/2" 1/2"
consulting mechanical and electrical engineers
6"
NONE 26GA. G.I. COUNTERFLASHING. SECURE ROOFING MATERIAL AND COUNTERFLASHING TO CURB WITH #10 WOOD SCREWS
NEOPRENE GASKET ALL AROUND
R. T I C HE
AN
M31176 EXP. 12/31/19 TA
S
AC UNIT
APPLIES TO UNITS: ACCU-1
PRO F E S S I ONA L
ED
ME
TE
CH AN I CA
O F CA L
I N E ER
M-501 xM-501 M-501
NONE
VRF-1 MOUNTING (NEOPRENE) VRF MOUNTING ON ROOF
PETERS
engineering
R NO
M-501
SPONGE AIR SEAL (4) #12 SMS TOP AND BOTTOM (8 TOTAL PER LOCATION) THRU 16 GA SHEET METAL STRAP
1-1/2" TYP.
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
AC-A1
1/2"
4x4 BLOCKING SIMPSON 4x4 BLOCKING WITHWITH SIMPSON A34 A34 EACHEACH SIDE,SIDE, END,END, TYP. TYP.
2 33
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
1-1/2" TYP.
SEE STRUCTURAL DETAILS FOR TJI STIFFENERS
REFRIGERANT PIPE ON ROOF
3/4" DIA. 3 HOLES
3"
SEE STRUCTURAL DETAILS SEE STRUCTURAL DETAILS FOR FOR TJI STIFFENERS. TJI STIFFENERS.
7
9-3/8"
1-1/2" TYP.
THYBAR EQUIPMENT MOUNTING THYBAR EQUIPMENT MOUNTING SUPPORT #TEMS2, 12" HIGH, SUPPORT #TEMS2, 12" HIGH, 18 18 GAUGE STEEL SHELL, GAUGE GALV.GALV. STEEL SHELL, BASEBASE PLATE AND COUNTERFLASHING, PLATE AND COUNTERFLASHING, NAILER, ALL WELDED WITHWITH NAILER, ALL WELDED CONSTRUCTION. CONSTRUCTION.
NOTES: 1. ROOF PENETRATION AND FRAMING BY THE GENERAL CONTRACTOR. 2. ROOFING REPAIR AND WATERPROOFING BY THE GENERAL CONTRACTOR. 3. ROOF PENETRATION ONLY TO BE USED BY REFRIGERANT PIPING.
4.
9-3/8"
✔
LAG SCREW WASHER LAG SCREW WITHWITH WASHER 2x WOOD NAILER 2x WOOD NAILER
SINGLE-PLY ROOFING SINGLE-PLY ROOFING UP UP UNDER CURBCURB AND AND UNDER FLASHING FLASHING CAP CAP PLYWOOD SHEATHING OVER STRUCTURAL TJIs
1-1/8"
ACS
✔
07/03/2019
DATE:
1/2"Øx3" MIN. EMBED S.S.LAG SCREW AT EACH 3/8"Øx1-1/2" MIN.MOUNTING EMBED HOLE (TYPSCREW AT EACH S.S.LAG ATCORNER EACH OF VRF UNIT)HOLE (TYP OF 4 AT MOUNTING EACH SPRING ISOLATOR) NEOPRENE PAD
WOOD CURB BY GENERAL CONTRACTOR
FLS
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
SEAL TIGHT ALL-AROUND PIPE WITH FOAM
SS
1-1/2"
3/8"Ø BOLT AND NUTS (2) AT EACH ISOLATOR (8 TOTAL)
PIPE INSULATION
INC:
REVIEWED FOR ✔
ER
0 1/4" 1/2"
PIPE CLAMP
PIPE SUPPORT, 8" HIGH, 18 GAUGE THYBAR TEMS-2 OR EQUAL WALKPAD BY GENERAL CONTRACTOR
APP. 02-117123
21"
ROOF JACK W/ITH REMOVABLE TOP
REG I S T
1"
COVER WITH SHEET METAL FRONT. SEAL WATER TIGHT SIMILAR
L
I
A
2
SE
2"
1
N I F OR
2" THICK RIGID INSULATION
ROUTE 1/4" CLEAR TUBING UP ALONG WALL TO HIGH CEILING LEVEL. RIGHT HAND, BOTTOM END OF FAN COIL UNIT HOUSING
18 GA. COUNTER FLASHING CAP FAN COIL UNIT HOUSING
ROUTE DISCHARGE TUBING AND POWER BACK UP THRU FAN COIL UNIT HOUSING.
FAN COIL UNIT HOUSING
2" FRONT VIEW
12"
M-501
CONDENSATE PUMP DETAIL
METAL FLASHING, PVC COATED
CANT STRIP
RIGID INSULATION/STIFFENER FINISHED ROOFING
CANT STRIP
PREFAB CURB W/ NAILER - FURNISHED BY UNIT MFR.
4" 1-1/2" MIN.
PROJECT
TEHAMA CENTER STUDENT SERVICE
SECURE LEVELING RAIL TO STRUCTURAL BLOCKING BELOW W/ 3/8"ø LAG SCREWS W/ 3" EMBED AT 32" O.C.
770 DIAMOND AVE. RED BLUFF, CA 96080
1/2" THRU BOLT @ 32" O.C. (MIN 3 PER SIDE) - NUT WASHERS 4 TOP AND BOTTOM , CENTERED ON BLOCKING
WOOD BLOCKING AROUND UNIT TO LEVEL UNIT
NOTES: 4x6 BLOCKING WITH A35 EACH 1. CURB EQUAL MASON WEST RSC 3" SPRING DEFLECTION - SPRING OPA #0207 SIDE, EACH END. CENTER 2. 3 SPRING WINDOWS PER SIDE. APPROXIMATE BLOCKING ON BOLT FORCURB CURBWEIGHT = 750 LBS NOTES: 3. ENTIRE SPRING CURB RAIL SYSTEM & A.C. CURB TO BE INSTALLED PER MFRS. 1. (3) HOLD DOWNS PER LONG SIDE - (6) TOTAL ATTACHMENT RECOMMENDATIONS.
SEE STRUCTURAL DETAIL FOR TJI STIFFENERS
M-501
FINISHED ROOFING
WOOD BLOC 2" THICK RIGID 2-LAYERS OF 5-8" GYP. INSULATION BD. WITHINAROUND CURB UN UNIT. WOOD BLOCKING 2" THICK RIGID 2-LAYERS OF 5-8" GYP. INSULATION BD. WITHIN AROUND CURB UNIT TO LEVEL UNIT.
4x6 BLOCKING W/ A35 EACH SIDE, EACH END. CENTER BLOCKING ON BOLT FOR CURB ATTACHMENT
4x4 BLOCKING WITH SIMPSON A34 EACH SIDE, END, TYP.
4
NONE
ATTACH HOLD DOWN TO CURB W/ (4) #10x1/2" TEK SCREWS
PLYWOOD SHEATHING OVER STRUCTURAL TJIs
NOTES: 1. INSTALL PUMP PER INSTALLATION INSTRUCTIONS. 2. PUMP CAN BE INSTALLED LEFT OR RIGHT HAND SIDE OF FAN COIL UNIT. 3. FEED BOTH POWER CABLE AND DISCHARGE UP THRU FAN COIL OUTLET HOLE. 4. 1/4" CLEAR TUBING SHALL BE USED FOR ENTIRE RUN OF CONDENSATE DRAIN PIPING. DO NOT INSTALL 3/8" TUBING. 5. SLIDE COVER OVER PUMP AFTER INSTALLATION COMPLETE.
10
SEAL
MICROHOLD
2-LAYERS OF 5-8" GYP. 24 GA. GSM WITHIN CURB COUNTER BD. FLASHING
THYBAR EQUIPMENT MOUNTING SUPPORT #TEMS2, 12" HIGH, 18 GAUGE GALV. STEEL SHELL, BASE PLATE AND COUNTERFLASHING, WITH NAILER, ALL WELDED CONSTRUCTION (2 PER UNIT).
SECURE PUMP TO WALL WITH (3)#10 WOOD SCREWS
11.3"
PROFILE VIEW
SECURE CURB TO STRUCTURAL BLOCKING W/ 1/2"ø BOLT AT 32" O.C. 14 GA, 6" WIDEMAX, MANUFACTURED MIN (1) PER BLOCK BELOW
ROOF
WELD AT JOINTS PER SINGLE-PLY MANUFACTURER REQUIREMENTS
PUMP FILTER INLET
14 GA HOLD DOWN
2x WOOD NAILER
3/8"Øx3" EMBED LAG SCREWS (MIN. 2 PER SIDE)
PUMP COLLECTION TRAY
2.4"
ANCHORING CLIP
EQUIPMENT LEG LAG SCREW WITH WASHER
SINGLE-PLY ROOFING UP CURB AND UNDER FLASHING CAP
FAN COIL UNIT DRAIN
PUMP
C
LOCATION 15/16", TYP. (12) TOTAL PER
ATTACH TO UNIT W/ 2" THICK RIGID (4) #10 x 1/2" SM INSULATION TEK SCREWS
3/8"Øx1-1/2" MIN. EMBED S.S.LAG SCREW AT EACH MOUNTING HOLE (TYP OF 4 PLACES)
5/16"ISOLATOR PAD (ONE EACH LEG)
1-3/8", TYP.(4) PER ANCHORING #12 SMS
NEOPRENE GASKET AC UNIT BASE RAIL16 GA STRAP DETAIL
SEAL WEATHER RIGHT W/ A UV RESISTANT SEALANT
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
AC-1MOUNTING DETAIL (RIGID CURB) AC-1 DETAIL xM-501 NONE 1 3 1 M-501
ACCU ON ROOF NONE
M-501
APPLIES TO UNITS: RH-1 THRU RH-5
NONE
APPLIES TO UNITS: DOAS-1
ISSUED
MARK 1/4" NEOPRENE RUBBER PAD
2" MAX SCHEDULE 40 BLACK STEEL PIPING OR COPPER TYPE "M"
SECURE FAN TO WOOD NAILER W/ 1/4"ø LAG BOLTS 12" O.C. MIN. 2 PER SIDE
PIPE CLAMP, LOOSE FIT
4" MAX
B
TRAFFIC PAD. EXTEND 8" MINIMUM ALL AROUND SLEEPER. SECURE TO ROOF WITH ROOFING CEMENT
1/2"
20 GA. G.I. FLASHING (OVERLAP ROOFING MIN 4")
1-1/2" TYP.
CANT STRIP
CURB FLANGE TO BLOCKING W/ 3/8"ø LAG SCREWS (3" EMBED) INTO BLOCKING TYP. (4) SCREWS PER SIDE.
FLASHING 4x4 BLOCKING W/ "SIMPSON" A34 EACH SIDE, EACH END
ROOF
METAL STRAP DETAIL DOAS-1
ROOFING
MANAGEMENT 3/8"x1" PVC GASKET
4D MIN NOTE: SUPPORTS TO BE PLACED AT A MAXIMUM SPACING OF 8'-0" ON CENTERS.
16 GA
4D MIN NOTE: FOR ALL FLASHING AND ROOFING SEE ARCHITECTURAL PLANS
SHEATHING DUCT
SPRING EQUAL TO MASON
DOAS UNIT 2" DEFLECTION WEST AC UNIT SPRING OPA-0468
NEOPRENE GASKET ALL AROUND
14 GA
9
TYPICAL PIPE SUPPORT ON ROOF NONE
5 M-501
RELIEF HOOD ON ROOF
2" THICK RIGID ATTACH TO UNIT W/ INSULATION
(4) #10 x 1/2" SM TEK SCREWS 2-LAYERS OF 5-8" GYP.
NONE
16 GA 2" THICK RIGID INSULATION
BD. WITHIN CURB
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
ATTACHMENT OF UNIT 6" TO ISOLATED SPRING CURB (4) #10 SELF TAPPING SMS, TOP & BOTTOM AT EACH CORNER (SEE SHEET METAL STRAP DETAIL ABOVE) CORNER SNUBBER
AGENCY
15/16", TYP. NEOPRENE WEATHER SEAL 14 GA HOLD DOWN SECURE CURB TO STRUCTURAL BLOCKING W/ 1/2"ø BOLT AT 32" O.C. 14 GA, 6" WIDE MANUFACTURED MAX, MIN (1) PER BLOCK BELOW
MICROHOLD
24 GA. GSM COUNTER FLASHING
APPLIES TO UNITS: FC-1
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
REMOVABLE SHEET METAL COVER 1-3/8", TYP.
NEOPRENE GASKET DOAS UNIT BASE RAIL AC UNIT BASE RAIL
M-501
CANT STRIP ATTACH HOLD DOWN TO CURB W/ (4) #10x1/2" TEK SCREWS FINISHED ROOFING
METAL FLASHING, PVC COATED
RIGID INSULATION/STIFFENER
CANT STRIP
PREFAB CURB W/ NAILER - FURNISHED BY UNIT MFR.
CEILING ROOF
WOOD BLOC 2-LAYERS OF 5-8" GYP. 2" THICK RIGID AROUND BD. WITHIN CURB UN WOODINSULATION BLOCKINGUNIT. AROUND UNIT TO LEVEL 2" THICK RIGID OF 5-8" GYP. UNIT. 2-LAYERS INSULATION BD. WITHIN CURB
10" MINIMUM
4x6 BLOCKING W/ A35 EACH SIDE, EACH END. CENTER BLOCKING ON BOLT FOR CURB ATTACHMENT
4"
1-1/2" MIN, TYP
A
MOUNTING BRACKET (BY UNIT MFR.)
(2) 4" x 4" BLOCKING w/ SIMPSON A35 TOP & BOTTOM EA. END.
1-1/2" MIN.
SECURE LEVELING RAIL TO STRUCTURAL BLOCKING BELOW W/ 3/8"ø LAG SCREWS W/ 3" EMBED AT 32" O.C.
TITLE 1/2" THRU BOLT @ 32" O.C. (MIN 3 PER SIDE) - NUT WASHERS TOP AND BOTTOM , CENTERED WOOD BLOCKING AROUND UNIT ON BLOCKING NOTES: TO LEVEL UNIT 1. CURB EQUAL MASON WEST ISC 2" SPRING - SPRING OPA #0468 4x6DEFLECTION BLOCKING WITH A35 EACH 2. 2 SPRING WINDOWS PER SIDE. APPROXIMATE CURB WEIGHT = 320 SIDE, EACH END. CENTER LBS 3. ENTIRE SPRING CURB RAIL SYSTEM & A.C. CURB TOON BEBOLT INSTALLED PER MFRS. BLOCKING FOR CURB NOTES: 1. (3) HOLDRECOMMENDATIONS. DOWNS PER LONG SIDE - (6) TOTAL ATTACHMENT
(4) 3/8"ø x 3" LAG SCREW, INTO MFR MOUNTING BOARD (1 PER CORNER IN MFR PROVIDED HOLES) FC
DETAILS
1
+6'-8" AFF MIN. WOOD STUD WALL 5/15/2019 9:20:19 AM
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
5-1/2"
SLOPED PREFAB METAL CURB WITH WOOD NAILER & INSULATION "B-LINE" DURA-BLOK SUPPORT, 6" HIGH MINIMUM, WITH INTEGRATED 1/2" - 13 ELECTRO ZINC ALL THREADED ROD RISERS AND GALVANIZED SLOTTED CHANNEL - 1" HIGH
DATE 01/04/2019 05/17/2019
6 M-501
WALL MOUNTED FAN COIL NONE
SHEET
2 M-501
DOAS-1 MOUNTING DETAIL NONE
M-501
017294 LIONAKIS 2017
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123 SEE UPPER SUPPORT DETAIL 2/M-502 FOR ATTACHMENT INFORMATION
2" MIN.
1 5/8" FRAMING CHANNEL
PIPES SHALL BE < 1" DIA (HAZARDOUS PIPING) OR < 3" DIA (NON HAZARDOUS PIPING) TO OMIT SEISMIC BRACING OR PIPES SUPPORT LENGTH SHALL BE LESS SHALL BE < 1" DIAMETER TO THAN < 12" FROM BRACING STRUCTURE ABOVE. OMIT SEISMIC AS SHOWN
1-1/2"
1-1/2" 5"
3/8"Ø THREADED ROD. PROVIDE WITH ROD STIFFENERS FOR LENGTHS GREATER THAN 24"
MULTIPLE PIPING SUPPORT 1 5/8" FRAMING INSULATION NOTES: CHANNEL 1. PROVIDE PIPE SUPPORT AT ALL CHANGES IN DIRECTION. 2. HORIZONTAL PIPE SUPPORT SHALL BE SPACED MAX. 8'-0" O.C. 3. MAXIMUM UNIFORM LOAD: <10 LBS./FT. MULTIPLE/SEISMIC SUPPORT SINGLE PIPE NOTES: 4. PROVIDE SUPPORT PER CPC TABLE 313.6 1. PROVIDE AT SYSTEMS ALL CHANGES DIRECTION. 5. THIS DETAIL SHALL BEPIPE USEDSUPPORT FOR PIPING THAT IN ARE EXEMPT FROM DESIGN OF SEISMIC FORCES AS NOTED IN 2016NOTES: NOTES: 2. HORIZONTAL PIPE SUPPORT SPACED MAX. 8'-0" O.C. CBC 1616A.1.26, ASCE 7, SEC 16.6.8.3. ONE SHALL OF THEBE BELOW REQUIREMENTS MUST BE IN PLACE FOR THIS DETAIL TO BE USED:1. PROVIDE SUPPORT PER 2016 CPC TABLE 313.6 1. PROVIDE SUPPORT PER 2016 CPC TABLE 313.6 3. ROD MAXIMUM UNIFORM LOAD:TO 30 12" LBS./FT. A. HANGER IS LESS THAN OR EQUAL BETWEEN UNISTRUT AND SUPPORT ABOVE OR 2. MAXIMUM SPACING ON PIPE 6'-0" 2. MAXIMUM SPACING ON PIPE 6'-0" 4. TRAPEZE IF TRAPEZE CONTAINS GAS PIPING & TOTAL SUPPORTED EXCEEDS LBS./FT, THEN B. PIPES ON ARE NON-HAZARDOUS SYSTEMS AND LESS THAN ORLOAD EQUAL TO 3" DIA10 AND/OR PIPES ON TRAPEZE ARE 3. THE PIPES SHALL BE AT LEAST 6" CLEAR OF ANY OTHER STRUCTURAL NON-STRUCTURAL COMPONENTS. 3. THE PIPES SHALL BE AT LEASTOR 6" CLEAR OF ANY OTHER CBC 1616A.1.26. HAZARDOUSTRAPEZE SYSTEMSREQUIRES AND LESS SEISMIC THAN OR SUPPORT EQUAL TO PER 1" DIA. 4. CBC 2016 SECTION 1616.10.19 ASCE 7, SECTION 13.6.8.3OR ALLOWS AN EXCEPTION WHICH STATES PIPING SIZES 1 INCH OR STRUCTURAL NON-STRUCTURAL COMPONENTS. 5. PROVIDE SUPPORT PER CPC TABLE 313.6 LESS ARE EXEMPT FROM SEISMIC REQUIREMENTS.
(2) 1/2"Ø x 4 1/2"Ø LONG THRU BOLT
2"x2"x3/16" ANGLE 6" LONG CLIP 8"
FRONT VIEW
CONSULTANT 4x6 BLOCKING SECURED BETWEEN STRUCTURAL MEMBERS WITH SIMPSON A35 EACH SIDE, EACH END.
ROOF
PETERS
engineering
1 1/8"
3" MIN
ER
DOUBLE NUT WITH LOCK WASHER
TJI, SEE STRUCTURAL DRAWINGS
(4)-3/8"Ø HANGER ROD
NONE SEE 9/M-502 FOR HANGER ROD STIFFENER REQUIREMENTS
MASON IND. N.Y. SCB-1
1 MOUNTING BRACKET (TYP.)
EXHAUST FAN / FAN COIL
M-502
770 DIAMOND AVE. RED BLUFF, CA 96080
CLIENT FLEXIBLE FIBROUS DUCT. SEE SPECS
3 DIAMETERS SEE NOTE 2.
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
APPLIES TO UNITS: FC-Z01 THRU FC-Z10, BSB-1, BSB-2, AND EF-1
EXHAUST FAN / FAN COIL DETAIL
1 12 GA SAFETY WIRE. SEE DETAIL 2/M-502
3. FLEXIBLE AIR DUCTS AND CONNECTORS SHALL BE NOT MORE THAN 5 FEET IN LENGTH AND SHALL NOT BE USED IN LIEU OF RIGID ELBOWS OR FITTINGS PER CMC 603.4.1.
NONE
TEHAMA CENTER STUDENT SERVICE
PLAN VIEW
SHEET METAL SCREWS, TYP.
2. IF A MINIMUM 3 DUCT DIAMETERS OF STRAIGHT RUN IS NOT AVAILABLE ABOVE REGISTER USE PLENUM ABOVE REGISTER.
MECHANICAL ROD STIFFENER
PROJECT
NOTES: 1. SUPPORT BRANCH SELECTOR BOX SIMILAR TO EXHAUST FAN/ FAN COIL AS SHOWN. SPRING ISOLATORS MAY BE OMITTED FOR BRANCH SELECTOR BOX.
1. PEEL BACK JACKET AND SECURE TO PLENUM COLLAR. USE A MIN. OF (3) SHEET METAL SCREWS AND (2) FULL WRAPS OF DUCT TAPE. PULL BACK JACKET AND APPLY (2) FULL WRAPS OF DUCT TAPE. ALTERNATE METHOD: BANDING DEVICE OR PANDUIT STRAP, IN LIEU OF SHEET METAL SCREWS.
1818 2525
F.C.
REFRIGERANT GAS / LIQUID LINES (FAN COILS ONLY)
NOTES:
TYPEUCC UCCWITH WITHSTEEL STEELSTRUT STRUTASSEMBLY ASSEMBLYRATINGS RATINGS(ASD) (ASD) TYPE MAXIMUM MAXIMUM STRUT MAX MAXIMUM ROD STRUT MAX MAXIMUM ROD STIFFENER UCC UNBRACED STIFFENER UCC UNBRACED SIZE SIZE LENGTH SPACING LENGTH SPACING LENGTH (INCHES) LENGTH (INCHES) (INCHES) (INCHES) (INCHES) (INCHES) (INCHES) (INCHES)
9
I
3/32"ø PRESTRETCHED GALVANIZED AIRCRAFT CABLE 7x19 STRAND CORE.
CONDENSATE DRAIN CONNECTION. (FAN COILS ONLY)
GSM DUCT ELBOW
1-1/4"
MASONIND. IND.N.Y. N.Y.UCC UCCSEISMIC SEISMICROD RODCLAMP CLAMP MASON
2818 3825
O F CA L
L
N I F OR
1
GSM DUCT ELBOW
156 156 156 156
CH AN I CA
1±0.1
F.C.
3/8" 3/8" 1/2" 1/2"
ME
TE
SEAL
1-3/16" 1-3/16"
1-5/16" 1-5/16"
TA
(2) 5/8"ø BOLTS AND NUTS EACH SIDE
EQUIPMENT
1-1/4"
M31176 EXP. 12/31/19
(2) 5/8"ø BOLTS AND NUTS EACH SIDE
1" MIN
C
R. T I C HE
AN
3/32"ø PRESTRETCHED GALVANIZED AIRCRAFT CABLE 7x19 STRAND CORE. ( 1 PER CORNER)
1±0.1
2" MAX (TOP AND BOTTOM)
PRO F E S S I ONA L
ED
S
SPRING HANGER VIBRATION ISOLATOR (TYP.4) - EQUAL TO MASON RW30N
THREADEDROD ROD THREADED
1/2"x1-1/2" x 13 x 13 UNC LOCKING 1/2"x1-1/2" UNCBOLT LOCKING TORQUED TO 10 FT-LBS BOLT TORQUED TO 10 FT-LBS
consulting mechanical and electrical engineers
SECURE WITH 3/8"ø LAG SCREW, 3" EMBED (TYPICAL OF ALL SEISMIC BRACING ON AIRCRAFT CABLE)
3" MIN
PIPE HANGER DETAIL
1-5/8"x1-5/8"x12GA GA 1-5/8"x1-5/8"x12 SINGLESTRUT STRUT SINGLE STIFFENER STIFFENER
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
I N E ER
M-502
4x8 BLOCKING SECURED TO I-JOIST W/ WEB STIFFENER WITH SIMPSON A35, EACH SIDE, EACH END. SEE STRUCTURAL DRAWINGS FOR WEB STIFFENER, TYPICAL.
R NO
6
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
REG I S T
HHS/R PIPING WITH INSULATION SPACER
07/03/2019
DATE:
1-1/8"
D
✔
12" MAX
3/8"Ø THREADED ROD. PROVIDE WITH ROD STIFFENERS FOR LENGTHS GREATER THAN 24"
PIPE CLAMP
ACS
✔
3/8"ø HANGER ROD WITH (2) NUTS AT BOTTOM ENDS. LENGTH LESS THAN 12".
SEE DETAIL 2/M-502 FOR UPPER ATTACHMENT CONDITIONS. (TYP)
REFRIGERANT PIPING WITH INSULATION SPACER
FLS
A
2" MIN. SEE DETAIL 2/M-502 FOR UPPER ATTACHMENT CONDITIONS. (TYP)
SS
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
3/32"Ø 12 GA PRESTRETCHED GALVANIZED AIRCRAFT CABLE 7x19 STRAND CORE @ 45°. 20 FT MAX LENGTH PIPE CLAMP
REVIEWED FOR ✔
SE
0 1/4" 1/2"
SEE DETAIL 2/M-502 FOR UPPER ATTACHMENT CONDITIONS. (TYP)
INC:
M-502
NONE
ISSUED
4. FOR CONFINED SPACES, USE PLENUM BOX ABOVE DIFFUSER. SEE DETAIL B BELOW. T-BAR CEILING
A
20" GA. SHT. MTL. STRAP @ 10'-0" O.C. MIN. 1-1/2" WIDE PER SMACNA STDS. SEE DETAIL 2/M-502
UNCONFINED SPACE
FLEX DUCT SAME SIZE AS HARD DUCT AND DIFFUSER NECK SIZE UNLESS NOTED OTHERWISE. FLEX DUCT, MAX. LENGTH: 5 FEET. SEAL AIR-TIGHT AT PLENUM COLLAR AND AT SPIN-IN PER SPEC'S AND 1/2" MIN. WIDTH DRAW BANDS ON COMPRESSION ENDS.
MARK
SURFACE MOUNTED DIFFUSER SUPPLY AIR DIFFUSER.
TRANSERSE BRACING SERVING AS LONGITDINAL BRACING AT END OF DUCT RUN.
1-1/2" WIDE DUCT STRAP (EACH CORNER, 4 TOTAL). SEE DETAIL 2/M-502 FOR UPPER ATTACHMENT PLENUM COLLAR
ATTACH TO STRUCTURE PER 1/M-502
5" MIN. TYP, ALL ATTACHMENTS
SECURE STRAP TO STIFFENERS WITH (2) 1/4"ø x 3" SIMPSON SDS SCREW
1" TYP.
PLAN VIEW
B
V.D. SQUARE INSULATED DIFFUSER PLENUM 2" LARGER THAN DIFFUSER COLLAR & DUCT COLLAR
SECURE AIRCRAFT CABLE TO BENT PLATE W/ (2) 5/8" BOLTS AND NUTS, EACH SIDE
B
7
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
M-502
CONFINED SPACE
FINISHED CEILING
DIFFUSER INSTALLATION DETAIL
5" MIN. TYP ALL ATTACHMENTS
3/8" CLOSED EYE-BOLT THRU ROOF JOIST WITH (TYP. OF NUT & WASHER (TYP. 4) OF 4) TYPICAL 12 GA SAFETY WIRE WIRE @ 45° @ (4 45° TIGHT TURNS IN 1.5") STRUCTURAL FRAMING MEMBER
NOTE: 1. SUPPORT DUCT WITH TRANSVERSE SUPPORTS EACH END OF DUCT RUN PER OPM-0043-13. TRANSVERSE SUPPORTS EVERY 30'-0" O.C. AND LONGITUDINAL SUPPORTS EVERY 60'-0" O.C. LONGITUDINAL SUPPORT MAY BE OMITTED WHERE TRANSVERSE SUPPORTS ARE WITHIN THE MAXIMUM OFFSET LENGTH AT 90° TURNS. 2. AIRCRAFT CABLE BRACING MAY BE OMITTED WHEN DUCTWORK IS SECURED WITHIN 12" OF SUPPORT STRUCTURE. 3. CONTRACTOR SHALL PROVIDE A SHOP DRAWING SHOW BRACING LAYOUT COORDINATING WITH ALL DISCIPLINES.
4
NONE
1-1/2"x4"x1/4" BENT PLATE WITH (2) 7/16"ø HOLES, TYP
3/32"ø PRESTRETCHED 1± 0.1 GALVANIZED 1 AIRCRAFT CABLE 7x19 STARND CORE, TYP. #10 X 1 1/4" SHT. MTL. SCREWS. TYP. OF (2) PER SIDE (3" PER FROM EA. END)
M-502
RECTANGULAR DUCT SUPPORT NONE
SECURE ALL-THREAD TO ANGLE ABOVE WITH DOUBLE NUTS AND WASHER (NUT ALSO AT BOTTOM), TYPICAL.
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
TYPICAL 3/8"ø HANGER ROD
M-502
AGENCY
UPPER ATTACHMENT DETAIL NONE
SEE DETAIL 2/M-502 FOR UPPER ATTACHMENT CONDITIONS. (TYP) 3/8"Ø HANGER ROD 8'-0" O.C. ATTACH PER 2/M-502.
SUPPORT @ 8'-0" O.C. WOOD STUD WALL N-205 ANGLE SPRING HANGER VIBRATION ISOLATOR (TYP.4) - EQUAL TO MASON RW30N
SEE 9/M-502 FOR HANGER ROD STIFFENER REQUIREMENTS
1± 0.1 1
MOUNTING BRACKET (TYP)
A
FC Z##
3/32"ø PRESTRETCHED GALVANIZED AIRCRAFT CABLE 7x19 STRAND CORE. SEE 2/M-502 1/M-502 FOR UPPER ATTACHMENT
#10 SMS THRU ANGLE INTO DUCT AT 8" O.C.
2x2x1/4" ANGLE IRON C749, TYP W/ BOLT & NUT A100
SECURE RODS TO BRACKET WITH 3/8"Ø NUTS AND LOCKWASHERS
MASON IND. N.Y. SCH-1 W/ (2) 5/8 BOLT AND NUTS, EACH CORNER (4 TOTAL)
CEILING CASSETTE FAN COIL
CEILING WHERE NOTED ON ARCH DRAWINGS
1±0.1 1 EQUIPMENT
APPLIES TO: FC-Z11 THRU FC-Z18 MAX WEIGHT = 35 LBS
8 M-502
FAN COIL CASSETTE SUPPORT NONE
3/32"ø PRESTRETCHED GALVANIZED AIRCRAFT CABLE 7x19 STRAND CORE @ 45°, TYP. SEE 1/M-502 2/M-502
TRANSVERSE BRACING SERVING AS LONGITDINAL BRACING AT END OF DUCT RUN.
3/32"Ø 12GA PRESTRETCHED GALVANIZED AIRCRAFT CABLE 7x19 STRAND CORE @ 45°. SEE 1/M-502, TYP.
ROUND DUCT
NOTE: MODEL NUMBER DESIGNATIONS ARE SUPERSTRUT.
5/15/2019 9:20:20 AM
TYPICAL 1-1/2" WIDE DUCT STRAP
NOTES: 1. SEE MORE INFORMATION IN SPECIFICATION 23 05 30 (INCLUDING DUCT STRAP GAUGE SIZE) 2. SEE DETAIL 1/M-502 2/M-502 FOR AIRCRAFT CABLE UPPER ATTACHMENT
2
3/8"Øx3" LAG SCREW THRU WOOD FRAMING MEMBER
BRACKET, 1" WIDEx1/8" WITH (2) 45° BENDS "ELCEN" No. 207P BRIDGE CLEVIS SECURE STRAP TO CLEVIS WITH 1/4"Øx1" BOLT, WASHER AND NUT
TITLE
DETAILS PLAN VIEW
S.M. STRAP AROUND DUCT
NOTE: 1. SUPPORT DUCT WITH TRANSVERSE SUPPORTS EACH END OF DUCT RUN PER OPM-0043-13. TRANSVERSE SUPPORTS EVERY 30'-0" O.C. AND LONGITUDINAL SUPPORTS EVERY 60'-0" O.C. LONGITUDINAL SUPPORT MAY BE OMITTED WHERE TRANSVERSE SUPPORTS ARE WITHIN THE MAXIMUM OFFSET LENGTH AT 90° TURNS. 2. AIRCRAFT CABLE BRACING MAY BE OMITTED WHEN DUCTWORK IS SECURED WITHIN 12" OF SUPPORT STRUCTURE.
SUPERSTRUT A120 CHANNEL BRACE AB-227 BENT STEEL FITTING
SHEET
PLAN VIEW
5 M-502
DUCT SUPPORT ON WALL NONE
3 M-502
ROUND DUCT SUPPORT NONE
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
SECURE 1/8"Lx2x2x6"LONG TO WEB STIFFENERS WITH 3" SIMPSON (2) 1/4"ø xTHRU BOLTS &SDS NUTS, SCREW BOLTS & NUTS, TYP. TYP.
FINISHED ROOF
SUSPEND FROM ABOVE #12 SMS EACH CORNER 12 GA SLACK SAFETY WIRE (TYP. OF 2) MOUNT DIAGONALLY. SEE 2/M-502 FOR SPLAY DETAIL
DATE 01/04/2019 05/17/2019
M-502
017294 LIONAKIS 2017
2"
1
2
3
4
5
AI
AI
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
POWER TO UNIT BY DIVISION 26
APP. 02-117123
1"
AI
INC:
REVIEWED FOR
0 1/4" 1/2"
OUTSIDE CONDENSING UNIT
SS
D
G OSA
X
H
FILTERS
EF
ACS
✔
✔
07/03/2019
DATE:
SA
PWR BY DIV 26
FLS
✔
PWR BY DIV 26
DSD
SF
EMS STAINLESS STEEL TEMP SENSOR
T
SET TO MAINTAIN 80°F (ADJ)
BAC
UNIT FAULT
BACNET INTERFACE
DDC CONTROLLER
NOTES: 1. AN ALARM SHALL BE GENERATED ON THE EMS WHEN THE THE TEMPERATURE RISES ABOVE 85 DEGREES.
TEMP
NAC
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com AI
CONSULTANT
TEMP SET POINT AI
120VAC TO 24VAC TRANSFORMER
OVER RIDE DI
120 VAC
S
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
ROOM TEMP
BACnet MS/TP
PETERS
engineering
CO2 LEVEL AI
consulting mechanical and electrical engineers
M-601
NONE
SE
AC-1 CONTROLS
REG I S T
NONE
1
M31176 EXP. 12/31/19
S
TA
AI
ME
TE
CH AN I CA
O F CA L
L
N I F OR
I
AI POWER TO UNIT BY DIVISION 26
SCHEDULING THE ROOF TOP PACKAGE AC UNIT, DOAS UNIT, AND ASSOCIATED EF’S SHALL OPERATE IN ACCORDANCE WITH A PRE-PROGRAMMED OPERATIONAL SCHEDULE. THE BMS, VIA THE INTERNAL TIME CLOCK OR OPTIMUM START PROGRAM, SHALL ENABLE SYSTEMS IN THE WARM UP, PRE-COOL, AND OCCUPIED MODES. ACCESS TO THE SYSTEM SHALL BE VIA THE EXISTING JOHNSON CONTROLS FACILITY MANAGERS WORK STATION. THE OWNER SHALL PROVIDE AN ETHERNET TCP/IP CONNECTION TO THE NAE CONTROL PANEL.
AI
SEAL
D
G
SA
OSA X
H
SAFETY CONTROLS THE SUPPLY AIR FANS SHALL SHUT DOWN IF SMOKE IS SENSED BY THE SUPPLY AIR DUCT SMOKE DETECTOR FOR UNITS WITH CFM GREATER THAN 2,000.
FILTERS
DSD SF
120VAC TO 24VAC TRANSFORMER
EXHAUST FANS EF-1 SHALL ENERGIZE WITH PROGRAMMED SCHEDULE TO MATCH THEIR PERSPECTIVE HEATING AND COOLING UNITS.
PROJECT
770 DIAMOND AVE. RED BLUFF, CA 96080
CLIENT BACnet MS/TP
M-601
TEHAMA CENTER STUDENT SERVICE
FEC
120 VAC
2
PWR BY DIV 26
BAC BACNET INTERFACE
DDC CONTROLLER
DI UNIT FAULT
DO DO FIRST STAGE COOL
DOAS - 1 THE DOAS UNIT SHALL ACTIVATE WHEN FC-Z01 THROUGH FC-Z18 ACTIVATE, AND OUTSIDE AIR IS REQUIRED. THE SUPPLY FAN SHALL TRACK FAN SPEED BASED ON THE CO2 SENSORS IN HIGH DENSITY SPACES (CONF ROOMS, LOBBIES, ETC.). ON CALL FOR COOLING, THE DOAS PACKAGED COOLING CONTROLS WILL BE ENABLED TO MAINTAIN THE SUMMER TIME SUPPLY AIR TEMPERATURE OF 78°F (ADJ). ON CALL FOR HEATING, THE DDC CONTROLLER SHALL CYCLE STAGES OF GAS HEATING TO MAINTAIN A WINTER SUPPLY AIR TEMPERATURE OF 70° (ADJ.)
DI
STAGE 1 HEAT
DO
SF CURRENT
AC - 1 ON FIRST CALL FOR COOLING THE JOHNSON CONTROLLER SHALL ENABLE THE AC UNITS PACKAGED FREE COOLING ECONOMIZER CONTROLS TO MAINTAIN ROOM TEMPERATURE AS SET. ON FURTHER CALL FOR COOLING THE DDC CONTROLLER ENABLE COOLING STAGES 2 AND 3 TO ENABLE THE AC UNIT’S VARIABLE AND CONSTANT SPEED COMPRESSORS MAINTAIN ROOM TEMPERATURE AS SET. ON CALL FOR HEATING THE DDC CONTROLLER SHALL CYCLE STAGES OF GAS HEATING TO MAINTAIN ROOM TEMPERATURE AS SET (SUMMER 78°F, WINTER 68°F, ADJUSTABLE).
START/STOP
C
R. T I C HE
AN
I N E ER
M-601
SPLIT SYSTEM CONTROLS
PRO F E S S I ONA L
ED
R NO
5
ER
CARBON DIOXIDE
A
MFR'S WIRED T-STAT
DI
SECOND STAGE COOL
D
DO DO FIRST STAGE COOL
X
DO DO ECONOMIZER ENABLE
OUTLET
DO
STAGE 2 HEAT
INLET
DI
STAGE 1 HEAT
D
DO
SF CURRENT
RA
START/STOP
FAN COIL
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
EA
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
DOAS-1 CONTROLS NONE
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
EF
CURRENT SW DI DO
B
START/STOP DO DI
MANAGEMENT
INTERLOCK EF-1 WITH PACKAGED ROOFTOP UNIT AC-1.
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
120 VAC
AGENCY
3
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
M-601
EF-1 CONTROLS NONE
120V POWER TO PANEL BY DIVISION 26
TX
ETHERNET TCP/IP INTERNET CABLE BY OWNER COMMUNICATION IS VIA THE EXISTING JOHNSON CONTROLS HOST. LOCATE ROUTER IN STORAGE ROOM 120 WITH DATA DROP. CALL KENT FLOWERS AT SHASTA CONTROLS AT 530-510-5341 FOR PRICING.
NAC
FEC
A
FEC
BACNET
VRF BAC NET INTERFACE
VRF PNL
TITLE
TO OTHER FEC'S AS REQUIRED BACnet MS/TP
MECHANICAL CONTROLS
5/15/2019 9:20:20 AM
SHEET
4 M-601
SYSTEM ARCHITECTURE LAYOUT NONE
M-601
017294 LIONAKIS 2017
2.
A METHOD OF PROCEDURE (MOP) IS MANDATORY AND SHALL BE PROVIDED FOR THIS JOB. WORK SHALL NOT BE STARTED WITHOUT AN APPROVED/SIGNED MOP.
3.
ALL WORK SHALL BE DONE AT SUCH TIME AND IN SUCH MANNER AS PRESCRIBED BY DISTRICT.
4.
PROTECT EXISTING EQUIPMENT AND FURNISHINGS FROM ANY DAMAGE DUE TO DUST, MOISTURE OR CONTACT WITH WORK CREW OR MATERIALS.
ALL PERMANENT EQUIPMENT AND COMPONENTS. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G. HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS OR WATER. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS OR HAS A CENTER OF MASS LOCATED 4 FEET OR MORE ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
A. B.
5.
COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. COMPONENTS WEIGHING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.
6.
7.
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE OR STRUCTURAL ENGINEER DELEGATED RESPONSIBILITY AND THE DSA DISTRICT STRUCTURAL ENGINEER. THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE REQUIREMENTS.
8.
D
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE
9.
MP
MP
MD
MD
PP
E
14. SEAL CONDUIT OPENINGS THROUGH WALLS AND CEILINGS. INSTALL ESCUTCHEON PLATES AT BUILDING INTERIOR. WHERE EQUIPMENT IS INSTALLED ON THE EXTERIOR WALL, STUB CONDUITS THROUGH WALL AND SEAL CONDUIT OPENINGS, THEN INSTALL EXTERIOR EQUIPMENT. ALSO, SEAL AROUND THE PERIMETER EDGE OF THE EQUIPMENT ENCLOSURE BETWEEN THE ENCLOSURE AND BUILDING.
OPTION 2: SHALL COMPLY WITH THE APPLICABLE OSHPD PRE-APPROVAL (OPM #) #____________.
PP
OPTION 3: SHALL COMPLY WITH THE SMACNA SEISMIC RESTRAINT MANUAL, OSHPD EDITION (2009), INCLUDING ANY ADDENDA. FASTENERS AND OTHER ATTACHMENTS NOT SPECIFICALLY IDENTIFIED IN THE SMACNA SEISMIC RESTRAINT MANUAL, OSHPD EDITION, ARE DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND DETAILS. THE DETAILS SHALL ACCOUNT FOR THE APPLICABLE SEISMIC HAZARD LEVEL ___ AND CONNECTION LEVEL ___ FOR THE PROJECT AND CONDITIONS.
15. CONDUITS INSTALLED ON ROOF AND BUILDING EXTERIOR SHALL BE RIGID GALV. STEEL (HEAVY WALL) WITH THREADED FITTINGS. CONDUIT AND WALL TO BE PAINTED OUT TO MATCH EXTERIOR FINISH. 16. SPLICES AND TERMINALS SHALL BE COMPRESSION TYPE OF SEAMLESS PURE COPPER, TIN PLATED, LONG BARREL (TERMINALS WITH TWO-HOLE PAD AND INSPECTION WINDOW WITH NEMA DRILLING), AS MANUFACTURED BY BURNDY TYPE YS, YAZ-2N OR EQUAL. CLEAN ALL SURFACES AND INSTALL WITH OXIDE INHIBITING COMPOUND, BURNDY PENETROX-E OR EQUAL. APPLY COMPOUND BETWEEN BUS AND LUG PAD AND BETWEEN CONDUCTOR AND LUG BARREL. INSTALL COMPRESSION CONNECTORS WITH 360° CIRCUMFERENTIAL COMPRESSION DYE, BURNDY HYPRESS OR EQUAL. THE INDENTER OR OTHER TYPE TOOLS WILL NOT BE ACCEPTABLE.
LIGHTING FIXTURE SCHEDULE
C
MODEL
FIXTURE LAMP WATTS MOUNTING
A AE
LITHONIA LITHONIA
2AVL4-40L-MDR-MVOLT-EZ1-LP840-N80 2AVL4-40L-MDR-MVOLT-EZ1-LP840-N80-E10WLCP
LED LED
48 VA 48 VA
B BE
LITHONIA LITHONIA
2AVL2-20L-MDR-MVOLT-EZ1-LP840-N80 2AVL2-20L-MDR-MVOLT-EZ1-LP840-N80-E10WLCP
LED LED
24 VA 24 VA
C D E E5 E8 EE F FE G H X X1
LITHONIA LBL4-4000LM-80CRI-40K-MIN10-GZT-MVOLT LITHONIA WL4-30L-MVOLT-EZ1-LP840-N80 PEERLESS BRM9L-LLP-4FT-MSL4-80CRI-40K-1D800LMF-10/90-D ARK-ZT-120-SCT PEERLESS BRM9L-LLP-20FT-MSL8-80CRI-40K-1D800LMF-10/90DARK-ZT-120-SCT PEERLESS BRM9L-LLP-32FT-MSL8-80CRI-40K-1D800LMF-10/90DARK-ZT-120-SCT PEERLESS BRM9L-LLP-4FT-MSL4-80CRI-40K-1D800LMF-10/90-D ARK-ZT-120-SCT-E10WLCP LIGMAN UTA-95351-30W-M-W4-120-01-F-RPS-24"-DIM-A90421 LIGMAN UTA-95351-30W-M-W4-120-01-F-RPS-24"-DIM-A90421 -EMG LIGMAN UMV-30052-2X20WLED-M-M-W40-01-120/277V LUMINAIRE SWP610-15W-4000K-120/277-OP-BLK LITHONIA TLE-1-R-120-ELN LITHONIA TLE-1-R-120-ELN
LED LED LED
32 VA 28 VA 29 VA
LED
144 VA
LED
230 VA
LED LED LED LED LED LED LED
29 VA 30 VA 30 VA 40 VA 15 VA 5 VA 5 VA
T-BAR T-BAR
CLEAN ALL EXTERIOR AND INTERIOR SURFACES OF PANELS AND ALL MATERIAL AND METAL SHAVINGS FROM PANEL AND CABINET INTERIORS. ALL OPENINGS SHALL BE SEALED AND APPLY TOUCH-UP SPRAY PAINT WHERE NEEDED.
13. SUPPORT ENCLOSURES, BOXES AND CONDUIT INSTALLATIONS PER CEC 314.23 (A) THROUGH (H).
OPTION 1: DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND DETAILS
E
LABEL DEVICES (I.E. RECEPTACLES, ETC.) ON EACH COVER PLATE IDENTIFYING CIRCUIT AND PANEL DEVICE IS CONNECTED TO.
12. INSTALLATION SHALL COMPLY WITH CEC 210.4 - EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH CIRCUIT ORIGINATES. THEREFORE ANY CIRCUIT SHARING A COMMON NEUTRAL SHALL BE CAPABLE OF SIMULTANEOUS DISCONNECT OR DEDICATED NEUTRALS SHALL BE INSTALLED.
MECHANICAL PIPING (MP), MECHANICAL DUCTS (MD), PLUMBING PIING (PP), ELECTRICAL DISTRIBUTION SYSTEMS (E): PP
ALL CONDUCTORS INSTALLED IN PANELBOARDS SHALL BE TRAINED, LACED, AND INSTALLED WITH PHASE TAPE ON ALL CONDUCTORS.
11. CONTRACTOR WILL PROVIDE ARC FLASH LABELS FOR ELECTRICAL POWER PANELS INCLUDED IN THE PROJECT SCOPE IN ACCORDANCE WITH NFPA 70E AND SPECIFICATION SECTION 26 05 73 'OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY'. THE ARC-FLASH LABELS MESSAGE OR CONTENT SHALL BE PROVIDED BY THE CONTRACTOR.
THE METHOD OF SHOWING BRACING AND ATTACHMENTS TO THE STRUCTURE FOR THE IDENTIFIED DISTRIBUTION SYSTEM ARE AS NOTED BELOW. WHEN BRACING AND ATTACHMENTS ARE BASED ON A PREAPPROVED INSTALLATION GUIDE (E.G., SMACNA OR OSHPD OPM), COPIES OF THE BRACING SYSTEM INSTALLATION GUIDE OR MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF AND DURING THE HANGING AND BRACING OF THE DISTRIBUTION SYSTEMS. THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.
MD
CORE BORE SHALL BE 1" DIAMETER LARGER THAN EACH CONDUIT. SPACE CONDUIT HOLES 3" APART. SEAL AROUND CONDUIT WITH NON-SHRINK, NON-METALLIC GROUT.
10. FIELD COORDINATE DEVICE LOCATIONS PRIOR TO ROUGH-IN.
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-10 SECTION 13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.5.6, 13.6.7, 13.6.8, AND 2016 CBC, SECTIONS 1616A.1.24, 1616A.1.25 AND 1616A.1.26.
MP
ADEQUATELY STRAP AND SUPPORT ALL CONDUIT WORK PER CEC. IN GENERAL, SUPPORT ALL CONDUIT WITHIN THREE FEET (3') OF OUTLET BOX, CABINET OR PANEL AND MAXIMUM TEN FEET (10') ON CENTER THEREAFTER.
DESCRIPTION
2'x4' LED DIMMABLE TROFFER 2'x4' LED DIMMABLE TROFFER W/ EM BATTERY T-BAR 2'x2' LED DIMMABLE TROFFER T-BAR 2'x2' LED DIMMABLE TROFFER W/ EM BATTERY SURFACE 4' LED DIMMABLE WRAPAROUND WALL +7'-6" 4' LED DIMMABLE WALL MOUNT LUMINAIRE PENDANT 4' LED DIMMABLE PENDANT +10'-0" AFF PENDANT 20' LED DIMMABLE PENDANT +12'-0" AFF PENDANT 32' LED DIMMABLE PENDANT +12'-0" AFF PENDANT 4' LED DIMMABLE PENDANT W/ EM +10'-0" AFF BATTERY PENDANT 8" DIA BY 18" HIGH LED CYLINDER PENDANT 8" DIA BY 18" HIGH LED CYLINDER W/ EM BATTERY WALL +7'-6" 5" DIA CYLINDER LED UP/DOWN LIGHT WALL +7'-6" LED WALL MOUNT CEILING LED EXIT LIGHT W/ EM BATTERY WALL LED EXIT LIGHT W/ EM BATTERY
WEIGHT (LBS)
DETAIL
35 35
5&6/E-502 5&6/E-502
20 20
5&6/E-502 5&6/E-502
10 10 19
2/E-502 1/E-502 3&4/E-502
77
3&4/E-502
122
3&4/E-502
19 8 8 10 6 3 3
3&4/E-502 3/E-502 3/E-502 1/E-502 1/E-502 1/E-502 1/E-502
17. INSTALL 'MECHANICALLY FASTENED PHENOLIC NAMEPLATE WITH WHITE LETTERING ON BLACK BACKGROUND ON ALL EQUIPMENT, INCLUDING PULL BOXES, WITH DESCRIPTION INDICATED ON DRAWINGS. NAMEPLATES SHALL READ EXACTLY AS DESCRIBED ON THE DRAWINGS. IN GENERAL NAMEPLATE LETTERING SIZE SHALL BE 3/16" HIGH FOR ALL NAMEPLATES SERVING FEEDER AND BRANCH CIRCUIT BREAKERS. ON MAIN SERVICE PANEL, DISTRIBUTION PANELS AND ALL OTHER NAMEPLATES LETTERING SHALL BE 1/4" HIGH. 17.1. ALL SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, VFD'S, MOTORS, JUNCTION BOXES, PULL BOXES, DISCONNECT SWITCHES, ETC., SHALL BE MARKED TO INDICATE EACH DEVICE OR EQUIPMENT WHERE THE POWER ORIGINATES PER CEC 408.4, FIELD IDENTIFICATION REQUIRED, (B) SOURCE OF SUPPLY.
NL NO, # NTS OC. P PB PFB
18. COORDINATE EQUIPMENT LOCATIONS, CONTROL AND POWER WIRING REQUIREMENTS AND CONNECT POINTS WITH ALL APPLICABLE DISCIPLINES. 19. PROVIDE AND INSTALL FUSES PER UNIT NAMEPLATE DATA ON THE EQUIPMENT PROVIDED.
PFCT PH, Ø PLYWD PNL PR PVC (R) REQ'D RM RMC (RR) SPEC STC SQ SW TEL TTB TYP UG UON V WP WT W W/ XFMR &
20. VERIFY CEILING TYPES PRIOR TO ORDERING LUMINAIRES. CONFIRM THAT FEATURES DESCRIBED IN THE SPECIFICATION OF THE LUMINAIRE ARE INCLUDED AS WELL AS PART NUMBERS LISTED ON SCHEDULE IN THE SUBMITTAL PACKAGE. CLARIFY NOTED DISCREPANCIES WITH ENGINEER PRIOR TO BID. 21. A LAMINATED COPY OF THE FINAL RECORD ONE LINE DIAGRAM SHALL BE PLACED IN ELEC ROOM. 22. PROVIDE WIRING DEVICES AND COVER PLATES IN COLOR(S) SELECTED BY ARCHITECT. THE COLOR OF THE WIRING DEVICE AND COVER PLATE SHALL BE THE SAME UNLESS SPECIFICALLY NOTED OTHERWISE. 23. REINSTALL EXISTING ELECTRICAL INSTALLATIONS DISTURBED. CERTAIN EXISTING ELECTRICAL INSTALLATIONS MAY BE LOCATED IN WALLS, CEILINGS OR FLOORS THAT ARE TO BE REMOVED AND ARE ESSENTIAL FOR THE OPERATION OF OTHER REMAINING INSTALLATIONS. WHERE THIS CONDITIONS OCCURS, PROVIDE A NEW EXTENSION OF ORIGINAL CIRCUITS, RACEWAYS, EQUIPMENT AND OUTLETS TO RETAIN SERVICE CONTINUITY. INSTALLATIONS SHALL BE CONCEALED IN FINISHED AREAS. 24. FOR ROOF PENETRATIONS, REFER TO ARCHITECTURAL PLANS FOR INSTALLATION REQUIREMENTS. 25. FOR WALL PENETRATION INSTALLATIONS, REFER TO ARCHITECTURAL PLANS FOR REQUIREMENTS. 26. PROVIDE "LOCK-ON" DEVICE FOR ALL CIRCUIT BREAKERS ON EMERGENCY DEDICATED CIRCUITS.
B
A2
LED, FLUORESCENT OR HID FIXTURE
CONTROLLED BY SWITCH "a" CONNECTED TO CIRCUIT 2 FIXTURE TYPE A2 LED, FLUORESCENT OR HID FIXTURE - WALL MOUNTED
APPLIES TO ALL FIXTURES
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
APP. 02-117123
LED, FLUORESCENT OR HID FIXTURE - CEILING RECESSED
INC:
REVIEWED FOR
LED, FLUORESCENT FIXTURE - SEE FIXTURE SCHEDULE FOR MOUNTING
SS
LED, FLUORESCENT FIXTURE - WALL MOUNTED
DATE:
FLS
✔
ACS
✔
✔
07/03/2019
EXIT LIGHT FIXTURE SHADING INDICATES FIXTURE WITH LAMP(S) ON EMERGENCY CIRCUIT "MASTER" FIXTURE "SATELLITE" FIXTURE PRE-WIRED FIXTURE WHIP INCLUDED AS PART OF FIXTURE
J
PAIR OF TANDEM WIRED FLUORESCENT GRID FIXTURES
SITE LIGHTING FIXTURE AND POLE BOLLARD AND/OR POLE TOP LIGHT FIXTURE GROUND MOUNTED FLOODLIGHT FIXTURE a
SINGLE POLE SWITCH
2
TWO POLE SWITCH
3
THREE WAY SWITCH
4
FOUR WAY SWITCH
K
KEYED SWITCH
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
LV
LOW VOLTAGE SWITCH
CONSULTANT
M
MANUAL MOTOR CONTROL SWITCH
F
FAN / LIGHT / NIGHT LIGHT SWITCH, PER MECHANICAL
OS WALL MOUNTED OCCUPANCY AUTO-OFF LIGHT SWITCH OS DIMMER SWITCH WITH OCCUPANCY SENSOR, LINE VOLTAGE
OS
CEILING MOUNTED OCCUPANCY AUTO-OFF LIGHT SWITCH. INSTALL PER MANUFACTURER REQUIREMENTS.
DL
CEILING MOUNTED DAY LIGHT SENSOR INSTALL PER MANUFACTURER REQUIREMENTS.
RC
ROOM CONTROLLER INSTALL PER MANUFACTURER REQUIREMENTS.
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
DIMMER SWITCH, LOW VOLTAGE
consulting mechanical and electrical engineers
PRO F E S S I ONA ED NO R. ROMA L I E17247 EXP. 6/30/18 TA
LOW VOLTAGE PUSH BUTTON DOOR BELL T
LOW VOLTAGE TRANSFORMER FOR DOOR BELL
B
DOOR BELL. COORDINATE WITH ARCHITECT
F
FUSED DISCONNECT SWITCH
EL
TE
EC TR I CA
O F CA L
L
N I F OR
I
DUPLEX CONVENIENCE OUTLET DOUBLE DUPLEX CONVENIENCE OUTLET
SEAL
GROUND FAULT CIRCUIT INTERRUPTER DUPLEX OUTLET GROUND FAULT CIRCUIT INTERRUPTER DOUBLE DUPLEX OUTLET SPLIT DUPLEX OUTLET WITH: ONE CONVENIENCE OUTLET ONE CONTROLLED OUTLET DOUBLE DUPLEX OUTLET WITH: ONE DUPLEX CONVENIENCE OUTLET ONE CONTROLLED DUPLEX OUTLET ISOLATED GROUNDING DUPLEX OUTLET DOUBLE DUPLEX ISOLATED GROUNDING OUTLET EMERGENCY DUPLEX OUTLET EMERGENCY DOUBLE DUPLEX OUTLET SPECIAL OUTLET TO MATCH CAP PROVIDED WITH MACHINE
PROJECT
TEHAMA CENTER STUDENT SERVICE
FLUSH FLOOR BOX OR "POKE-THRU" UNIT EQUIPPED WITH FLUSH OR PEDESTAL DUPLEX RECEPTACLE AND VOICE/DATA OUTLETS AS NOTED, OR REFER TO SCHEDULE ON DRAWINGS.
770 DIAMOND AVE. RED BLUFF, CA 96080
PLUGMOLD/WIREMOLD RECEPTACLE SYSTEM TRANSFORMER JUNCTION BOX, SIZE AS REQUIRED BY CODE
J J
FLEX CONNECTION TO FIXTURE TELEPHONE OUTLET DATA OUTLET
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
WALL MOUNTED TELEPHONE OUTLET, +48" AFF WALL MOUNTED TEL/DATA OUTLET, 3-PORT, +18" AFF 2
WALL MOUNTED TEL/DATA OUTLET, 2-PORT, +18" AFF
4
WALL MOUNTED TEL/DATA OUTLET, 4-PORT, +18" AFF
4
FLOOR MOUNTED TEL/DATA OUTLET, 4-PORT
ISSUED KP
SYSTEM KEYPAD, +60" AFF
IA
CEILING MOUNTED MOTION DETECTOR
MARK
DOOR CONTACT, FLUSH IN FRAME GB
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
CEILING MOUNTED GLASS BREAK SENSOR
B
SYSTEM ALARM BELL, +8'-0" AFG WALL MOUNTED BATTERY OPERATED ATOMIC CLOCK, +7'-0" AFF INTERIOR INTERCOM / PUBLIC ADDRESS SPEAKER, +7'-0" AFF EXTERIOR INTERCOM / PUBLIC ADDRESS SPEAKER, +8'-0" AFG PANELBOARD, RECESSED MOUNTED PANELBOARD, SURFACE MOUNTED MAIN SWITCHBOARD
28. PROVIDE SWITCHED/CONTROLLED RECEPTACLES WITH PERMANENT MARKINGS PER THE CALIFORNIA ENERGY CODE. MARKING SHALL BE AS PROVIDED BY THE MANUFACTURER OF THE RECEPTACLE, STAMPED INTO THE FACE (IE, LEVITON #5362-1PW OR EQUAL.) SYMBOL SHALL BE OF CONTRASTING COLOR TO THE DEVICE COLOR.
CONDUIT RUN CONCEALED IN CEILING OR WALL, SEE NOTE BELOW
30. SUBMIT SHOP DRAWINGS FOR ALL ELECTRICAL AND LOW VOLTAGE SYSTEMS (INCLUDING BUT NOT LIMITED TO LIGHTING CONTROLS, FIRE ALARM, INTRUSION ALARM, CCTV, ACCESS CONTROL, INTERCOM, DATA/TELECOMMUNICATIONS AND SOUND REINFORCEMENT SYSTEMS) FOR REVIEW AND APPROVAL PRIOR TO THE INSTALLATION OF ANY EQUIPMENT, DEVICES, RACEWAY OR WIRING. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL SUBMITTAL REQUIREMENTS.
TERMINAL CABINET, RECESSED MOUNTED TERMINAL CABINET, SURFACE MOUNTED HOMERUN TO PANELBOARD OR RESPECTIVE TERMINAL
CONDUIT RUN UNDERGROUND OR UNDER FLOOR EM
INSULATED GREEN GROUND CONDUCTOR INSULATED ISOLATED GROUND CONDUCTOR, GREEN WITH TRACER STRIPE
2.
MOUNT OUTLET BOXES AT +15" TO BOTTOM OF BOX UNLESS OTHERWISE NOTED.
3.
"A" ADJACENT TO OUTLET INDICATES OUTLET BOX TO BE MOUNTED ABOVE COUNTER. COORDINATE WITH COUNTER HEIGHT AND DEPTH PRIOR TO ROUGH IN.
4.
6.
NO CROSSBARS ON CONDUIT RUN INDICATES MINIMUM 3/4" CONDUIT, TWO #12 CU CONDUCTORS PLUS 1#12 CU GND. CROSSBARS INDICATE NUMBER OF #12 CU CONDUCTORS IN CONDUIT. CONDUCTOR SIZES OTHER THAN #12 NOTED ON DRAWINGS. INCREASE CONDUIT SIZE AS REQUIRED TO ACCOMMODATE C.E.C. WIRE FILL REQUIREMENTS. INCLUDE ADDITIONAL BOND WIRE IN ALL PVC AND FLEXIBLE CONDUIT. LONG CROSSBAR INDICATES NEUTRAL CONDUCTOR, SHORT CROSSBARS INDICATE PHASE CONDUCTORS. INCREASE BRANCH CIRCUIT CU CONDUCTOR SIZES AS REQUIRED BY THE 120V BRANCH CIRCUIT VOLT DROP CONDUCTOR LENGTH CHART BELOW. USE CONDUCTOR LENGTHS AS FIELD MEASURED, BASED UPON MEASURED FIELD ROUTING LENGTHS. INCREASE MINIMUM CONDUIT SIZE AS REQUIRED TO ACCOMMODATE A MAXIMUM 40% CONDUCTOR FILL OF THE BRANCH CIRCUIT CONDUCTORS. WHERE NECESSARY, PROVIDE A JUNCTION BOX AT ACCESSIBLE CEILING SPACE TO CONVERT THE LAST 15 FEET OF CONDUCTORS TO #10 AWG TO ACCOMMODATE TERMINATION OF CONDUCTORS AT WIRING DEVICES, LIGHTING FIXTURES, CIRCUIT BREAKER, ETC.
MANAGEMENT
EMERGENCY SYSTEM CONDUIT AND WIRES
NOTES: 1. MOUNT SWITCH BOXES AT +48" TO TOP OF BOX UNLESS OTHERWISE NOTED.
5.
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
2a
27. DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC. CONTRACTOR SHALL ACCEPT RESPONSIBILITY IN FAMILIARIZING THEMSELVES WITH ARCHITECTURAL AND STRUCTURAL CONDITIONS ALONG WITH INHERENT SPACE LIMITATIONS. WITH THAT UNDERSTANDING SHALL PROVIDE ALL ITEMS OF LABOR, MATERIALS AND TOOLS REQUIRED TO PROVIDE A COMPLETE INSTALLATION.
29. PROVIDE DATA SHEETS FOR ALL ELECTRICAL AND LOW VOLTAGE EQUIPMENT (INCLUDING BUT NOT LIMITED TO LIGHTING CONTROLS, FIRE ALARM, INTRUSION ALARM, CCTV, ACCESS CONTROL, INTERCOM, DATA/TELECOMMUNICATIONS AND SOUND REINFORCEMENT SYSTEMS) INCLUDED IN THIS PROJECT FOR REVIEW AND APPROVAL PRIOR TO ORDERING ANY EQUIPMENT OR DEVICES. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL SUBMITTAL REQUIREMENTS.
5/15/2019 9:16:32 AM
AT AMPERE ALTERNATING CURRENT AIR CONDITIONING AMP FRAME ABOVE FINISHED FLOOR AMPERES INTERRUPTING CAPACITY AMP TRIP SETTING AMERICAN WIRE GAUGE BARE COPPER BOARD BELOW FINISHED CEILING BREAKER BUILDING BOOSTER POWER SUPPLY CONDUIT CIRCUIT BREAKER CIRCUIT CEILING CONDUIT ONLY, WITH PULL LINE CONTINUOUS COPPER METALLIC COLD WATER PIPE DEMOLISH DIRECT CURRENT DISCONNECT DISTRIBUTION PANEL EXISTING EACH WITH EACH EVENING LIGHT ELECTRIC EMERGENCY ELECTRICAL METALLIC TUBING END OF LINE DEVICE EQUIPMENT EXISTING RELOCATED ELECTRICAL WATER COOLER ELECTRIC WATER HEATER FUTURE FIRE ALARM CONTROL PANEL FIRE ALARM EXTENDER PANEL FIRE ALARM TERMINAL CABINET FURNISHED BY OTHERS FLUORESCENT FOOT GAUGE GROUND FAULT CIRCUIT INTERRUPT GROUND METALLIC GAS PIPE GYPSUM HIGH INTENSITY DISCHARGE HORSE POWER HEIGHT HERTZ INTERMEDIATE METALLIC CONDUIT INCH ISOLATED JUNCTION BOX THOUSAND CIRCULAR MILLS KILO VOLT AMP KILOWATT LIGHTING CONTROL PANEL LOW VOLTAGE THOUSAND CIRCULAR MILLS MECHANICAL MAIN DISTRIBUTION PANEL METAL HALIDE MISCELLANEOUS MAIN SWITCHBOARD NEW NOT IN CONTRACT NOT IN ELECTRICAL SECTION OF THESE PLANS & SPECS. NIGHT LIGHT NUMBER NOT TO SCALE ON CENTER POLE PULL BOX PROVISION FOR FUTURE BREAKER W/ MOUNTING HARDWARE PROVISION FOR FUTURE CURRENT TRANSFORMER PHASE PLYWOOD PANEL PAIR POLYVINYL CHLORIDE CONDUIT RELOCATE/RELOCATED REQUIRED ROOM RIGID METAL CONDUIT REMOVE AND REPLACE SPECIFICATION SIGNAL TERMINAL CABINET SQUARE SWITCH TELEPHONE TELEPHONE TERMINAL BOARD TYPICAL UNDERGROUND UNLESS OTHERWISE NOTED VOLTS WEATHERPROOF WEIGHT WATT WITH TRANSFORMER AND
A
1. 2.
@ A AC A/C AF AFF AIC AT AWG BC BD BFC BRKR BLDG BPS C C/B CIRC CLG CO CONT CU CWP (D) DC DISC DP (E) E/W EA EL ELEC EM EMT EOL EQUIP (ER) EWC EWH (F) FACP FAEP FATC FBO FLUOR FT GA GFCI GND GP GYP HID HP HT HZ IMC IN ISO J-BOX KCMIL KVA KW LC LV MCM MECH MDP MH MISC MSB (N) NIC NIES
PLANS ARE NOT FOR CONSTRUCTION UNTIL APPROVED BY THE AUTHORITY HAVING JURISDICTION. THE CONTRACTOR SHALL NOT ORDER ANY MATERIALS OR INSTALL ANY EQUIPMENT, PIPING, ETC. UNTIL PLANS ARE APPROVED BY THE AUTHORITY HAVING JURISDICTION.
I N E ER
1.
NO
ALL MECHANICAL, PLUMBING AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2016 CBC, SECTIONS 1616A.1.18 THROUGH 1616A.1.26 AND ASCE 7-10 CHAPTER 13, 26 AND 30.
SYMBOLS LIST
ENG
ABBREVIATION LIST
S
GENERAL NOTES
THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT THE ATTACHMENT NEED NOT BE DETAILED ON THE PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING AND CONDUIT.
MFGR
5
MEP COMPONENT ANCHORAGE NOTE
3.
TYPE
4
ER
3
G
2
REG I S T
0 1/4" 1/2"
1"
2"
1
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 LIONAKIS 2017
CONDUIT RISER EXISTING EQUIPMENT, LIGHTING, DEVICES, CONDUIT, WIRING, ETC., ARE SHOWN LIGHT. NEW OR RELOCATED EQUIPMENT, LIGHTING, DEVICES, CONDUIT, WIRING, ETC., ARE SHOWN DARK. X
X
AGENCY
EXISTING ELECTRICAL EQUIPMENT TO BE REMOVED WIREMOLD SURFACE RACEWAY(S) WITH OUTLETS AS SHOWN OR NOTED, SEE SURFACE RACEWAY SCHEDULE
1
1 AC 1 A E1
(1)1-1/2"C
SYMBOLS REFERRING TO KEYED NOTES ON SAME SHEET MECHANICAL EQUIPMENT BY OTHERS, CONNECTED BY ELECTRICAL CONTRACTOR DETAIL DESIGNATION, "A" SIGNIFIES DETAIL, "E-1" SIGNIFIES SHEET NUMBER INDICATES SIZE OF CONDUIT = ONE AND ONE HALF INCH CONDUIT NUMBER WITHIN PARENTHESIS INDICATES QUANTITY OF CONDUITS
INSTALL CU GROUND CONDUCTOR IN ALL BRANCH CIRCUITS FOR LIGHT FIXTURES AND POWER DEVICES.
120V BRANCH CIRCUIT VOLT DROP CONDUCTOR LENGTH CHART
A
LENGTH OF CONDUCTOR
LOAD IN VOLT AMPERES
#12
#10
1200VA
74
121
183
284
434
1560VA
57
93
141
218
334
1800VA
49
81
122
189
289
1920VA
46
76
115
178
271
2340VA
X
62
94
146
223
2880VA 3000VA
X
51
76
118
181
X
48
73
114
174
3900VA
X
X
56
87
134
4800VA
X
X
46
71
108
WIRE SIZE IN (GAUGE) #8
#6
#4
NOTES 1. THIS CHART IS FOR COPPER CONDUCTORS ONLY. 2. THIS CHART ASSUMES AN 80% POWER FACTOR AND STEEL RACEWAYS. 3. 2016 CALIFORNIA ENERGY CODE, 130.5(c) ALLOWS A MAXIMUM COMBINED VOLTAGE DROP OF 5%. THIS CHART ASSUMES A MAXIMUM DROP OF 3% FOR FEEDERS. THIS CHART PROVIDES THE MAXIMUM LENGTH OF CONDUCTORS FOR LESS THAN 2% VOLTAGE DROP ON A BRANCH CIRCUIT AT GIVEN VA LOAD. 4. USE WIRE SIZE FROM THIS CHART UNLESS LARGER CONDUCTOR SIZES ARE NOTED ON THE DRAWINGS. 5. FOR VA VALUES NOT SHOWN USE NEXT HIGHEST VALUE FROM THE CHART
TITLE
SYMBOLS, NOTES & SCHEDULES
SHEET
E-001
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR FLS
✔
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
I N E ER
G
E17247 EXP. 6/30/18
S
TA
EL
TE
EC TR I CA
O F CA L
L
I
A
REG I S T
PRO F E S S I ONA ED NO R. ROMA L I
NO
ER
consulting mechanical and electrical engineers
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
✔
07/03/2019
DATE:
D
ACS
✔
N I F OR
SEAL
PROJECT
C
TEHAMA CENTER STUDENT SERVICE 770 DIAMOND AVE. RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
AGENCY
A
TITLE
TITLE 24 - INDOOR
5/15/2019 9:16:34 AM
SHEET
E-002
017294 LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR FLS
✔
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
I N E ER
G
E17247 EXP. 6/30/18
S
TA
EL
TE
EC TR I CA
O F CA L
L
I
A
REG I S T
PRO F E S S I ONA ED NO R. ROMA L I
NO
ER
consulting mechanical and electrical engineers
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
✔
07/03/2019
DATE:
D
ACS
✔
N I F OR
SEAL
PROJECT
C
TEHAMA CENTER STUDENT SERVICE 770 DIAMOND AVE. RED BLUFF, CA 96080
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 LIONAKIS 2017
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
AGENCY
A
TITLE
TITLE 24 - OUTDOOR
5/15/2019 9:16:34 AM
SHEET
E-003
3
4
5
1"
1
KEYED NOTES:
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
EXTEND 2"C. TO SIGNAL TERMINAL CABINET 'STC-4' AS SHOWN. REFER TO INTERCOM/CLOCK AND INTRUSION ALARM ONE LINE DIAGRAMS FOR CABLE REQUIREMENTS.
APP. 02-117123
REVIEWED FOR
0 1/4" 1/2"
SS
G1
GM (E)
(E) ELECTRICAL SERVICE MAIN SWITCHBOARD 'MSB'. FOR INFOMATION SEE ONE LINE DIAGRAM 1/E-601. (E)
C ELE
.
INSTALL NEW INTERCOM AND SECURITY CABLES IN EXISTING EMPTY 2" INTERCOM/ SECURITY CONDUIT. REFER TO ONE LINE DIAGRAMS FOR CABLE REQUIREMENTS.
3
INSTALL NEW FIBER OPTIC CABLES IN EXISTING EMPTY 4" DATA CONDUIT. REFER TO ONE LINE DIAGRAM - DATA, FOR CABLE REQUIREMENTS.
4
(2) 4" DATA CONDUITS WITH FIBER OPTIC CABLES. REFER TO ONE LINE DIAGRAM - DATA, FOR CABLE REQUIREMENTS.
5
EXISTING ELECTRICAL POWER CONDUIT. SEE ONE LINE DIAGRAM, 1/E-601 FOR MORE INFORMATION. VERIFY ROUTING OF CONDUIT AND LOCATION OF UNDERGROUND PULL BOXES IN FIELD.
6
NEW 4" CONDUIT FROM EXISTING UNDERGROUND PULL BOX TO NEW PANEL '1D'. SEE ONE LINE DIAGRAM 1/E-601 FOR MORE INFORMATION.
5
5 SD2
(E)
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D (E )
FLS
✔
DATE:
18 "
SD P
CONSULTANT
P SD 18"
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
consulting mechanical and electrical engineers
12 SS
ER
SS14
REG I S T
I N E ER
T JOIN (E)
NO
PRO F E S S I ONA ED NO R. ROMA L I
ENG
NCH TRE
6 SD0
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
T
2
INC:
E17247 EXP. 6/30/18
W " D 3/4 (E)
S
TA
EL
TE
EC TR I CA
O F CA L
L
I
A
2
G
2"
1
N I F OR
S S13
5
SEAL 11 SS
) (E 4" SS P S= 0 03 0.
P
05
PROJECT
FW14
SD 8" (E)
SD 8" (E)
SD
C
P
3
TEHAMA CENTER STUDENT SERVICE
2
SD
P 05
05
SD SD
SD 6" (E)
770 DIAMOND AVE. RED BLUFF, CA 96080
(E) BUILDING 4
23
SD 8" (E)
P
(E) CONDUIT STUBS IN 1 ING ILD BU 7.80 (E) IT ROOM. 9 2 (E) SERVER = FF
5
CLIENT
DW 2" ( E)
W 6"
SD 05 SD 05
24
3"
SD05
P SS
ISSUED G2
(E)
) AIN E M RC (FO SSP
" ) 4 (E
MARK
15 SD
SDP
05
(E)
SD
(E)
SD
3 ING ILD 0 BU 98.0 ) E 2 ( = FF
06 SS
18" (E)
02
5
(E) BUILDING 3
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
SS
2" ) 1 (E
P SD
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
FW 01
SD
05
W 6"
DATE 01/04/2019 05/17/2019
6"
P SD 05
(E)
6"
FW
SS
04 SS
(E)
W 01
. EC EL ULT VA SD
05
1 S S0
) (E
) (E
T. & AT ULT VA
(E) LIGHTING BOX
SD
18 SD " ) 4 (E
(E) FIRE WATER BOX
05
P SS
) (E
2
SS
) (E
WV
07
B ) (E
P SD
P SD
3
8"
4"
" ) 6 (E
P SS
(E) ELEC. BOX
2 ING ILD 84 BU 7. ) =29 E ( FF
. EC EL OX B
(E) BUILDING 2
G2
1"
FW
E PIP
6"
4"
DW 2"
R TE WA
(E)
(E)
) (E
(E) (2)4"C., VERIFY 5 LOCATION IN FIELD
05
) (E
W
SD
05
P SS
SD
6"
(E)
FW
DW
05
DW
P SS
SD
R LA PIL (E)
(298)
NO ING RK PA
SD
(299.5)
(E)
3 F W1
NO ING RK PA
FW08
F W11
(297.6)
P SD
(299.4)
B TA (E)
1
NO ING RK PA
" 24
(300)
AGENCY
(E) FH
6"
FW
5
4
(E) FLAG POLE
(E) UNDERGROUND PULL BOX, TYPICAL.
FW14
4
(297.6)
(297.7)
(E) ICV
(E)ICV
P SD
09
(E) UTILITY VAULT
P SD
(E) MAILBOX
) (E
P8 SD
FW12
(297.5) (297.7)
(29 9)
P5 SD
(299.6)
(297.4)
LE
(2) 4"C., SEE ONE LINE DIAGRAM FOR CONDUCTOR SIZE.
6
PANEL '1D' ) (E
(299.3)
8"
ED OS OP G PR ILDIN 8.5 U 29 B = FF
(297.4)
P9 SD
(2 98 )
W
(297.5)
(297.7)
SD28
(299.2)
D (E) WATER BOX 01 FW
(E) FH
W12
P7 SD
14 FW
(E) RPP
W08
A
) (E
8"
(297.4)
P6 SD
W
(E) WATER STRUCTURE
W
(297.6)
3 FW0 10 FW W03
(E) ICV W04
W0 1
(E) WATER METER (E) ICV
P1 SD
) (E
1 E-101
" 15
SD
P
ELECTRICAL SITE PLAN 1" = 20'-0"
4
(E) WATER BOX (E) IRRI. CONTROL PANEL
3 P1 SD 2 P1 SD
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
10
8"
(297.8)
P2 SD
F W12
5/15/2019 9:16:35 AM
) (E
3 SDP
(299.1)
LIONAKIS 2017
SD
SDP1
2" (E)
017294
) (E
2
2"
33
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
3 4"
SD
W
MANAGEMENT
05
8"
P SD
SD
(E)
6"
(E) FIRE ALARM BOX (E)ICV
(E) 9"∅ SEWER LID
8"
1 P1 SD
0 SIGNAL TERMINAL P1 SD CABINET 'STC-4'
STUB CONDUITS IN IDF ROOM 121. REFER TO FLOOR PLAN - LOW VOLTAGE, 1 / E-112
TITLE
ELECTRICAL SITE PLAN
SHEET
E-101
2"
1
2
3
4
5
KEYED NOTES:
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1
FED FROM ACCU-1 ON ROOF.
APP. 02-117123
2
FLUSH, 3-GANG FLOOR BOX WITH CONNECTIONS FOR OWER, DATA, AND FUTURE USE. LEGRAND TOP GUARD (3) #880MP AND (3) #880MPA WITH: #837 PCC-BLK; THREE NON-METALLIC FLANGE #828 PR-BLK; DUPLEX COVER PLATE #829 PFL-BLK; COMMUNICATION COVER PLATE #829 PCK-BLK; BLACK COVER PLATE
SHEET NOTES:
3
LOCATE AT +84" AFF FOR TV. COORDINATE EXACT LOCATION WITH TV BRACKET PRIOR TO ROUGH-IN.
4
LOCATE AT +132" AFF FOR PROJECTOR. COORDINATE EXACT LOCATION IN FIELD PRIOR TO ROUGH-IN.
5
LOCATE AT +108" AFF FOR DIGITAL SIGNAGE TV. COORDINATE EXACT LOCATION WITH TV BRACKET IN FIELD PRIOR TO ROUGH-IN.
6
LOCATE AT +108" AFF FOR SARS WAIT LIST TV. COORDINATE EXACT LOCATION WITH TV BRACKET IN FIELD PRIOR TO ROUGH-IN.
7
LOCATE AT +84" AFF FOR TV'S AND CONFERENCING CAMERA. COORDINATE EXACT LOCATION IN FIELD PRIOR TO ROUGH-IN.
INC:
REVIEWED FOR SS
FLS
✔
ACS
✔
✔
07/03/2019
DATE:
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
1
2
3
4
5
6
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
7
I N E ER
G
E17247 EXP. 6/30/18
S
TA
EL
TE
EC TR I CA
O F CA L
L
I
A
REG I S T
PRO F E S S I ONA ED NO R. ROMA L I
NO
ER
consulting mechanical and electrical engineers
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
1"
1. REFER TO DETAIL 2/E-501 FOR PANEL MOUNTING DETAILS.
N I F OR
E
SEAL
D +36"
30
CAMPUS SAFETY
COUNSELOR
126
128
32
+36"
+36"
C FC Z11
130
132
34
+36"
32
36
+36"
2
47
14
47
2
FC Z12
M
+36"
34
'3D'- 43
43
FC Z13
M
4
5 2
47
M
47
'3D'- 30,32
32
20 PROJECT
+36"
'3D'- 41
M
6
45
102
M
36 CLASSROOM/LOBBY OVERFLOW
34 HALLWAY
M FC Z02
BSB 2
'2D'- 10,12
F
FC Z03
101
'2D'- 14,16
100D
COUNSELOR
125
24
20
18
FC Z16
M
28
26
M 26
131
C.4 12
M
8
22
F
28
'3D'- 26,28
+36"
26
8
24
8
8
16
12
12
+36"
STUDENT SERVICES
12
+36"
22
+36" '3D'- 22,24
ISSUED
ADMIN OFFICE
16
18 +36"
MARK
104
103
'3D'- 8
24
+36"
+36"
M
22
+36"
18
'3D'- 12,14
+36"
+36"
+36"
16 22
FC Z18
24
18
LOBBY
129
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
+36"
20
COUNSELOR
FC Z17
CLIENT
+36" '3D'- 16,18,20
BSB 1
COUNSELOR
127
FC Z15
28
26
770 DIAMOND AVE. RED BLUFF, CA 96080
M
100 28 COUNSELOR
TEHAMA CENTER STUDENT SERVICE
ADMIN OFFICE
FC Z01
'3D'- 45,47
'3D'- 34,36
34
43 14
2
36
FC Z14
14
8 30
20 +36"
20
14
45
36
+36"
32 30
COUNSELOR
3
30 +36"
COUNSELOR
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
16
12
C 28
2
22
4
2
6
2
HALLWAY
'3D'- 44
HALLWAY '3D'- 2,4,6
100C WORK CENTER
FC 1
B
100B 5
100A '3D'- 1
M 42
~
IDF
1
1
33
'3D'- 37,39
IDF
IDF
1
1
38 38
38
35
37
PNL 'NAC'
FC Z10
VET CENTER
PNL '1D'
120
'3D'- 46 29
123
M
CUSTODIAL #8
119
'3D'- 48
RESTROOM
STUDENT SERVICES
118
3
5
107
+36" 3
5
STUDENT SERVICES
5
FC Z04
+36"
7
FC Z09
'3D'- 40,42
124
'3D'- 27,29
27
29 VET OFFICE
40
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
40
38
+36"
122
23
+36" 27
FC Z07
+36" 23
+36"
+36"
21
19
+36" 21
M
25
+36"
+36"
FACULTY OFFICE
FACULTY OFFICE
117
116
19
FACULTY OFFICE
115 23
25
FACULTY OFFICE
+36"
112
114
113
19
+36"
17
15 15
FC Z08
AGENCY
+36" 9
+36"
13 +36"
+36"
'3D'- 9,11,13
11 +36"
FC Z06
13
M
17
15
+36"
13
11 11
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
111
110
109
13
11
B 15
23
FACULTY HALLWAY
CANOPY 158
'3D'- 31
150
A
TITLE
A
FLOOR PLAN - POWER
SHEET
5/15/2019 9:16:40 AM
LIONAKIS 2017
M
17
FACULTY OFFICE
21
15
+36" FACULTY OFFICE
19 21
23
'3D'- 15,17,19 17
+36"
+36"
25
27
40
'3D'- 21,23,25
+36"
27
+36" 29
25
+36"
017294
9 +36"
M
+36"
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
9
M CONFERENCE
B.6
7
106
7 +36"
FC Z05
EWH 1
J
STUDENT SERVICES
108 M
+36"
EF 1
M
FACULTY OFFICE
105
3
A '2D'- 2,4
9
IEWH 2
1
'2D'- 18
STORAGE
42
M
'2D'- 6,8
PNL '2D'
7
5 '3D'- 3,5,7
#8
PNL '3D' M
3
1
'3D'- 33,35
121 39
1
PLAN NORTH
1 E-111
FLOOR PLAN - POWER 1/4" = 1'-0"
E-111
2"
1
2
3
4
5
KEYED NOTES: 1"
1
0 1/4" 1/2"
2
SHEET NOTES:
LINE ALL WALLS WITH 3/4" THICK FSR AND AC RATED, VOID-FREE PLYWOOD BACKBOARD. PAINT WITH MINIMUM (2) COATS WHITE PAINT. REFER TO SPECIFICATIONS.
8
PROVIDE 12"x4" CABLE TRAY FROM WALL-TO-WALL MOUNTED AT +7'-6" AFF. COORDINATE EXACT LOCATION WITH DATA RACKS. 9
4
PROVIDE 12"x4" CABLE TRAY MOUNTED IN ACCESSIBLE CEILING SPACE AT +11'-0" AFF. REFER TO CABLE TRAY HANGING DETAIL 6/E-501
5
PROVIDE (3) STI EZ-PATH SERIES 44+ WALL PENETRATIONS. INSTALL PENETRATIONS THROUGH WALL TO CORRESPOND WITH CABLE TRAY HEIGHT IN ACCESSIBLE CEILING SPACE.
6
7
D
10" x 2" x 1/4" SOLID COPPER GROUND BUS BAR WITH ISOLATORS AT + 8'-0" AFF, CHATSWORTH #13622-010, OR EQUAL. PROVIDE #3/0 GROUND CONDUCTOR TO MAIN BUILDING GROUND. PROVIDE 2-HOLE LUGS PER GENERAL NOTES ON SHEET E-001. LABEL GROUND CONDUCTORS PER UNIVERSITY STANDARDS. VERIFY EXACT LOCATION WITH UNIVERSITY PRIOR TO ROUGH IN.
PROVIDE 1-1/4"C FROM DATA OUTLET BOX TO NEAREST CABLE TRAY IN ACCESSIBLE CEILING SPACE. TYPICAL FROM EACH TEL/DATA OUTLET BOX LOCATION UNLESS OTHERWISE NOTED.
2
APP. 02-117123 2. REFER TO INTRUSION ALARM ONE-LINE DIAGRAM FOR INTRUSION ALARM DEVICE CABLING REQUIREMENTS. SS
18
PROVIDE OUTLET BOX WITH 1-GANG RING AND BLANK COVER PLATE. STUB 1"C. FROM OUTLET BOX INTO NEAREST ACCESSIBLE CEILING SPACE.
DATE:
19
LOCATE AT +108" AFF FOR DIGITAL SIGNAGE TV. COORDINATE EXACT LOCATION WITH TV BRACKET IN FIELD PRIOR TO ROUGH-IN.
20
LOCATE AT +108" AFF FOR SARS WAIT LIST TV. COORDINATE EXACT LOCATION WITH TV BRACKET IN FIELD PRIOR TO ROUGH-IN.
12
(2) 4"C UNDERGROUND STUBS FOR DATA FIBER OPTIC CABLES.
21
LOCATE IN CEILING FOR OWNER SUPPLIED WIRELESS ACCESS POINT.
13
PROVIDE (1) CAT 6A DATA CABLE FROM EACH DATA/TELEPHONE JACK IN TEL/DATA OUTLET TO CABLE TRAY VIA CONDUIT. RUN CABLES FROM CONDUIT TO IDF RACK VIA CABLE TRAYS. TYPICAL FROM EACH DATA OUTLET LOCATION UNLESS OTHERWISE NOTED.
22
LOCATE AT +84" AFF FOR TV'S AND CONFERENCING CAMERA. COORDINATE EXACT LOCATION IN FIELD PRIOR TO ROUGH-IN.
23
PROVIDE OUTLET BOX WITH 1-GANG RING AND BLANK COVER MOUNTED AT +84" AFF FOR CONFERENCING MICROPHONE CABLE.
24
THREE-GANG FLOOR BOX WITH POWER, DATA AND EMPTY GANG FOR MICROPHONE CABLE.
25
LOCATE FOR TEMPERATURE CONTROL PANEL. COORDINATE EXACT LOCATION IN FIELD PRIOR TO ROUGH-IN.
PROVIDE 18" X 18" X 6" DEEP SCREW COVER JUNCTION BOX IN ACCESSIBLE CEILING SPACE ADJACENT TO CABLE TRAY. MOUNT BOX WITH COVER DOWN 6" ABOVE TOP EDGE OF CABLE TRAY. STUB CONDUIT INTO IDF ROOM. PROVIDE INSULATED BUSHING ON CONDUIT STUB.
4
FLS
LOCATE AT +9'-0" AFF FOR OWNER SUPPLIED WIRELESS ACCESS POINT.
DATA OUTLET LOCATED IN POWER/DATA FLUSH FLOOR BOX.
5
INC:
REVIEWED FOR
17
11
14
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1. REFER TO INTERCOM ONE-LINE DIAGRAM FOR SPEAKER CABLING REQUIREMENTS.
LOCATE DATA OUTLET IN CASEWORK. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH CASEWORK MANUFACTURER IN FIELD PRIOR TO ROUGH-IN.
LOCATE AT +84" AFF FOR TV. COORDINATE EXACT LOCATION WITH TV BRACKET PRIOR TO ROUGH-IN.
3
PROVIDE 1"C FROM OUTLET BOX TO NEAREST CABLE TRAY IN ACCESSIBLE CEILING SPACE. RUN DATA CABLE FROM TEL JACK IN OUTLET TO CABLE TRAY VIA CONDUIT. RUN CABLE FROM CONDUIT TO TTB VIA CABLE TRAYS.
LOCATE FOR LECTERN. PROVIDE DATA WALLPLATE WITH (4) DATA JACKS AND (2) SHIELDED CAT6A RJ45 KEYSTONE/JACKS WITH CAT 6A F/UTP WITH DRAIN WIRE (OUTER FOIL SHIELD, UNSHIELDED TWISTED PAIR) TO PROJECTOR LOCATION AS SHOWN.
10
15
1
16
✔
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
6
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
7
PETERS
engineering
G
E17247 EXP. 6/30/18
S
TA
EL
TE
EC TR I CA
O F CA L
L
I
A
REG I S T
I N E ER
E
PRO F E S S I ONA ED NO R. ROMA L I
NO
ER
consulting mechanical and electrical engineers
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
3
PROVIDE DATA WALLPLATE WITH (2) DATA JACKS AND (2) SHIELDED CAT6A RJ45 KEYSTONE/JACKS WITH CAT 6A F/UTP WITH DRAIN WIRE (OUTER FOIL SHIELD, UNSHIELDED TWISTED PAIR) TO LECTERN LOCATION AS SHOWN. MOUNT AT +132" AFF FOR PROJECTOR. COORDINATE EXACT LOCATION IN FIELD PRIOR TO ROUGH-IN.
N I F OR
SEAL
D
IA IA
IA
GB
GB
GB
IA
COUNSELOR
126
2
IA
GB
GB 1-1/4"C, WITH (4) CAT 6 CABLES
2
130
C
GB
11
2
11
1-1/4"C, WITH (4) CAT 6 CABLES
CLASSROOM/LOBBY OVERFLOW
19
PROJECT
ADMIN OFFICE
101
TEHAMA CENTER STUDENT SERVICE
102
4
6
13
J
HALLWAY
14
6
2"C.O.
100D
770 DIAMOND AVE. RED BLUFF, CA 96080
13
J
J 2"C.O.
14
6
6
13
CLIENT
14
4
13
2
2 7
20
COUNSELOR
128
11
COUNSELOR 132
CAMPUS SAFETY
11
8
IA GB
16
2
GB
IA
2
LOBBY
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
C.4
100
ADMIN OFFICE
10
10
10
104 1-1/4"C, WITH (3) CAT 6 CABLES
STUDENT SERVICES
103 ISSUED
COUNSELOR
COUNSELOR
COUNSELOR
COUNSELOR
125
127
129
131
MARK
1-1/4"C, WITH (3) CAT 6 CABLES
1-1/4"C, WITH (3) CAT 6 CABLES
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
IA
C KP
21
FIRE RISER
2 4
HALLWAY
151
HALLWAY
100C
100B
2"C.O. 1-1/4"C, WITH (3) CAT 6 CABLES
5
WORK CENTER
1-1/4"C, WITH (3) CAT 6 CABLES
1-1/4"C, WITH (3) CAT 6 CABLES
2
17
100A 3' - 0"
124
121 15
IDF
2 2
13
B
CONFERENCE
13
GB
1-1/4"C, WITH (3) CAT 6 CABLES
1-1/4"C, WITH (3) CAT 6 CABLES
TELEPHONE TERMINAL BACKBOARD 'TTB'
B.6 DATA RACKS
MANAGEMENT
15 2
STORAGE
4 3
2"C.O.
STUDENT SERVICES
FACULTY OFFICE
118
108
107
106
105
2"C.O.
25
1-1/4"C.O.
STUDENT SERVICES
119
SIGNAL TERMINAL CABINET 'STC-4'
5
STUDENT SERVICES
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
2"C.O.
AGENCY 14
123
J
J
23
VET CENTER
12
24
22
CUSTODIAL
120
RESTROOM
14
5
1
6
4
6
J
J
4
J
13
4
14
GB
4
VET OFFICE 122
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
114
6
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
112
111
110
109
5/15/2019 9:16:43 AM
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
FACULTY OFFICE
113
IA
B
FACULTY HALLWAY
150 IA 18
A
J
+18"
+18" 18
IA
J
A
TITLE
FLOOR PLAN - LOW VOLTAGE
1 E-112
FLOOR PLAN - LOW VOLTAGE 1/4" = 1'-0"
SHEET PLAN NORTH
E-112
017294 LIONAKIS 2017
2
3
4
1"
2"
1
5
SHEET NOTES:
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1. REFER TO SHEET E-502 FOR LIGHTING FIXTURE DETAILS.
APP. 02-117123
INC:
REVIEWED FOR
0 1/4" 1/2"
SS
FLS
✔
✔
07/03/2019
DATE:
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
consulting mechanical and electrical engineers
6
7
S
TA
E
F F
FE
I N E ER
E17247 EXP. 6/30/18 EL
TE
EC TR I CA
O F CA L
L
I
A
5
ER
4
G
3
REG I S T
2
NO
1
PRO F E S S I ONA ED NO R. ROMA L I
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
ACS
✔
N I F OR
SEAL
F
F
F
F
D CAMPUS SAFETY
C
COUNSELOR
COUNSELOR
128
126
COUNSELOR
130
A
A
X1
132
A
PROJECT
CLASSROOM/LOBBY OVERFLOW
ADMIN OFFICE
101
102
TEHAMA CENTER STUDENT SERVICE
A AE
J
J 5
J 5
J
A
5
A
A
A
A
A
AE
770 DIAMOND AVE. RED BLUFF, CA 96080
A
A
5 OS
OS
J CLIENT
12'-0"
G
os
os
os
J
os
J
J
J
J
J
J
J
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
J os
OS
HALLWAY 100D OS X
AE
AE A
X AE
AE
A J
A
J
os
A
A
A
A
A
G
J
J
J
os
A
5
J
os
A
J
C.4
ISSUED
LOBBY
os
MARK
100 '1D'- 7 5
5
J
5
J
A
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
5
J
A
DATE 01/04/2019 05/17/2019
J
A
E8
A
COUNSELOR
COUNSELOR
COUNSELOR
COUNSELOR
125
127
129
131
E
E5
E
STUDENT SERVICES
ADMIN OFFICE
103
104
'1D'- 5
os
os
C WORK CENTER
FIRE RISER B
151
B
BE
H
OS
B
J
B
EE
100A
HALLWAY
J
J
A
os
os
J
J
C A
A
IDF
os
'1D'- 1
J 124
PNL '1D'
121
C
B
A
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
VET OFFICE J
A
A
A
A
120
C
C
J 3
J 3
J 3
LIONAKIS 2017
AGENCY
3
CUSTODIAL
D
D
119
C
RESTROOM
C
118
A
A
A
A
STUDENT SERVICES
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
108
107
106
105
116
FACULTY OFFICE
'1D'- 3
FACULTY OFFICE
115
114
FACULTY OFFICE
113
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
112
111
110
109
G
3 A
A
A
A
os
J
os
A
3
J
os
3
os
A
J
3
os
A
J
3
os
A
J
3
os
A
J
3
A
J
os
3
os
A
J
A
3
J
os
3
os
B
A
TITLE
F
FE
FE
FE
FE
FE
FLOOR PLAN - LIGHTING A
SHEET
5/15/2019 9:16:45 AM
017294
B.6
PNL '2D'
FACULTY OFFICE
117
3
J
B
1
FACULTY OFFICE
J
J
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
os
122
3 J
os
J
1
STORAGE
VET CENTER
OS
os
os
1
123
MANAGEMENT
PNL '3D'
C
G A
100B
'1D'- 9 VIA 'LCC'
1 CONFERENCE
HALLWAY
E8
os B
X1
X1
100C J
EE
E
PLAN NORTH
1 E-121
FLOOR PLAN - LIGHTING 1/4" = 1'-0"
E-121
2"
1
2
3
4
5
KEYED NOTES:
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
FEED TO FC/1 BELOW.
APP. 02-117123
0 1/4" 1/2"
1
SS
INC:
REVIEWED FOR FLS
✔
✔
07/03/2019
DATE:
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D
CONSULTANT
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
consulting mechanical and electrical engineers
4
5
6
7
I N E ER
REG I S T
NO
PRO F E S S I ONA ED NO R. ROMA L I E17247 EXP. 6/30/18
S
TA
EL
TE
EC TR I CA
O F CA L
L
I
A
3
ER
2
G
1
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
ACS
✔
N I F OR
E SEAL
D
PROJECT
C
TEHAMA CENTER STUDENT SERVICE
DOAS 1 AC 1
F
770 DIAMOND AVE. RED BLUFF, CA 96080
WP
WP #10
~
'2D'- 1,3,5
1
F
WP
F
#10
WP
F
'2D'- 19,21
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
WP '2D'- 7,9,11 3-#10, 1-#10
ACCU 1
WP
CLIENT
VRF 1
'2D'- 13,15,17 3-#4, 1-#8
'2D'- 20
C.4 ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
C
B
PANEL '1D' (BELOW) MANAGEMENT
PANEL '2D' (BELOW)
B.6
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 LIONAKIS 2017
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
AGENCY
B
A
TITLE
ROOF PLAN - POWER A
5/15/2019 9:16:46 AM
SHEET
1 E-133
ROOF PLAN - POWER 1/4" = 1'-0"
PLAN NORTH
E-133
2"
1
2
3
4
5
SPACE AS REQUIRED FOR WIRE MANAGEMENT
COPPER PATCH PANEL
1" 0 1/4" 1/2"
FIBER OPTIC PATCH PANEL 40
PROVIDE (1) DUPLEX RECEPTACLE, NEMA 5-20R LEVITON OR EQUAL
WIRE MGMNT
WIRE MGMNT
COPPER PATCH PANEL 30
WIRE MGMNT
30
COPPER PATCH PANEL WIRE MGMNT
SPACE FOR FUTURE SWITCH
25 WIRE MGMNT
PROVIDE COVERPLATES SHOWN (BRASS)
D
07/03/2019
DATE:
35
SPACE FOR FUTURE SWITCH
2-POST RACK, TYPICAL
✔
COPPER PATCH PANEL 35
WIRE MGMNT
FLUSH FLOOR MOUNTING PLATE (BRASS)
ACS
✔
WIRE MGMNT
WIRE MGMNT
SPACE FOR FUTURE SWITCH
40
FLS
✔
25 COPPER PATCH PANEL WIRE MGMNT
7'-0"
20
20
15
15
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
DATA & TELEPHONE OUTLET STANDARD CONDUIT TAPPING UP TO 3/4"
10
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
10
PETERS
engineering
MAXIMUM CONDUIT TAPPING w/ BUSHING UP TO 1"
5
MAXIMUM CONDUIT TAPPING w/o BUSHING UP TO 1 1/4"
consulting mechanical and electrical engineers
5
TOP VIEW
4 E-501
1
NONE
E-501
DATA RACK ELEVATION
PANEL ENCLOSURE PER PLAN
CONTROLLED RECEPTACLE PANEL
TEHAMA CENTER STUDENT SERVICE
BLK/WHT BLK
BLK RECEPTACLE CIRCUIT (PHASE A)
WHT RED/WHT
RED
Ø 120V
RED RECEPTACLE CIRCUIT (PHASE B)
WHT
N
WHT BLU/WHT
BLU
Ø 120V
BLU RECEPTACLE CIRCUIT (PHASE C)
WHT
N
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
WHT
TYPICAL 2x6 WALL STRUCTURAL MEMBERS
TO CONTROLLED RECEPTACLES TO UNCONTROLLED RECEPTACLES
ISSUED
NEUTRAL MAXIMUM 6'-6" AFF TO TOP OF ENCLOSURE
NEUTRAL
N
SECURE ENCLOSURE TO BLOCKING WITH 1/4" LAG BOLTS, 1-1/4" LENGTH - (2) AT EACH BLOCKING
20A SPDT RELAY, TYPICAL
120V
WHT
770 DIAMOND AVE. RED BLUFF, CA 96080
2x6 BLOCKING - SECURE WITH (3) 16d NAILS AT EACH END OF BLOCKING, TYPICAL INPUT CARD
120V
I
PROJECT
TO BYPASS TIMER
Ø
O F CA L
L
N I F OR
SEAL
FINISHED CEILING - MINIMUM 6'-3" AFF HEAD CLEARENCE
N
EC TR I CA
NONE
C
120V
EL
TE
A
ER
TA
NOTE: 1. VERTICAL WIRE MANAGEMENT IS NOT SHOWN. PROVIDE VERTICAL WIRE MANAGEMENT BETWEEN RACKS ON OUTSIDE OF EACH RACK. REFER TO SPECIFICATIONS FOR VERTICAL WIRE MANAGEMENT REQUIREMENTS. 2. PROVIDE EQUIPMENT TYPES AND QUANTITIES SHOWN AS A MINIMUM. REFER TO SPECIFICATIONS FOR ADDITIONAL EQUIPMENT REQUIREMENTS.
SIDE VIEW
FLUSH FLOOR BOX DETAIL
Ø
E17247 EXP. 6/30/18
S
MULTIPLE GANG FLOOR BOX. BOX SHALL BE OF CAST IRON, WATERTIGHT CONSTRUCTION. PROVIDE CONCRETE POUR CAP
I N E ER
ANCHOR TO FLOOR WITH 3/8" X 3-1/2" HILTI KWIK BOLT KB-TZ ANCHOR WITH NUT, FLAT WASHER AND LOCK WASHER, TYPICAL OF (4) PER RACK
EXTERIOR LEVELING SCREWS (TYP. 4)
G
0
FLUSH FLOOR MOUNTING PLATE w/ INTERIOR LEVELING SCREWS
PRO F E S S I ONA ED NO R. ROMA L I
NO
0
REG I S T
FLOOR
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
PROVIDE COMPARTMENT BARRIERS, TYP.
SS
COPPER PATCH PANEL
INC:
REVIEWED FOR
WIRE MGMNT
SPACE FOR FUTURE SWITCH
MAX LOAD CAPACITY, 1000 LBS
APP. 02-117123
45
45
WIRE MGMNT
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
TO CONTROLLED RECEPTACLES TO UNCONTROLLED RECEPTACLES NEUTRAL TO CONTROLLED RECEPTACLES TO UNCONTROLLED RECEPTACLES
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
PANEL WEIGHTS PANEL AMPS 100 225 400
WEIGHT 125 LBS 250 LBS 410 LBS
NEUTRAL
NOTES: B
1.
ALL RELAYS ARE SHOWN IN THEIR NORMAL "DE-ENERGIZED" STATE.
2.
CIRCUITS SERVING CONTROLLED RECEPTACLES SHALL HAVE TIME BASED CONTROLS IN ACCORDANCE WITH CA TITLE
3.
BY PASS TIMER SHALL BE A NORMALLY OPEN CONTACT DEVICE. TIMER SHALL HAVE A MAXIMUM BYPASS TIME OF 2
4.
ONLY (3) CONTROLLED CIRCUITS ARE SHOWN. ADDITIONAL CIRCUITS MAY BE SPECIFIED TO BE PROVIDED ON FLOOR
3X BLKG MIN
24, 130.5 (d)1. HOURS PER TITLE 24, 130.5 (d)1.
MANAGEMENT
PLANS. ADDITIONAL CIRCUITS SHALL BE WIRED SIMILARLY. 5.
5 E-501
PANEL SHALL BE ACUITY CONTROLS BLUE BOX, LEVITON EZ-MAX, WATT STOPPER LP SERIES OR EQUAL.
CONTROLLED RECEPTACLE WIRING DIAGRAM NONE
2 E-501
SURFACE MOUNTED PANEL ENCLOSURE ANCHORAGE DETAIL NONE
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
FINISHED ROOF
DISCONNECT SWITCH
ROOF JOIST, TYP.
WEATHERPROOF GFI RECEPTACLE, SECURE TO UNIT.
3/8" NUT WITH FENDER 1", TYPICAL WASHER AND LOCK WASHER.
5" MIN.
STRUCTURAL FRAMING 3/8"-20 ROD MEMBER, TYPICAL. LENGTH AS REQUIED.
A
SECURE ALL-THREAD TO ANGLE ABOVE WITH DOUBLE NUTS AND WASHER (NUT ALSO AT BOTTOM), TYPICAL. TYPICAL 3/8"ø HANGER ROD, 2X4 WOOD BLOCKING LENGTH AS REQUIRED.
FINISHED ROOF
CABLE TRAY
TITLE
TRAY TO SECURECABLE ALL-THREAD SUPPORT BRACKET WITH DOUBLE NUTS AND LOCK 3/8" DOUBLE NUT WASHER
PENETRATE THRU CURB OF HVAC UNIT, TYPICAL.
CABLE TRAY CENTER BRAKET, SPACED SUPPORT BRACKET, 4'-0" ON CENTER, MAX. MAX. SPACED 4'-0" CENTER,
SADDLE & STRAP AS REQUIRED BRANCH CIRCUIT PER PLANS
2. MAXIMUM WEIGHT OF CABLE TRAY IS 100 LB/FT.
6 E-501
CABLE TRAY HANGING DETAIL NONE
DETAILS
J-BOX, SECURE TO STRUCTURE
NOTES: 1. PROVIDE PROVIDE ROD STIFFENERS ONAS ALLREQUIRED RODS OVERPER ROD STIFFINERS 4'-0" IN LENGTH. DETAIL 9/M-502STIFFENERS SHALL BE NO MORE THAN 6" FROM BLOCKING AND 6" FROM TRAY.
5/15/2019 9:16:46 AM
AGENCY
MECHANICAL UNIT
SECURE 1/8"Lx2x2x6"LONG TO WEB STIFFENERS WITH (2) 1/4"ø THRU BOLTS, NUTS & WASHERS.
5" MIN.
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
3 E-501
ROOF RECEPTACLE TO MECH UNIT W/ DISCONNECT AND J-BOXES NONE
SHEET
E-501
017294 LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR
TYPICAL - (2)16d NAILS @ EACH END OF BLOCKING CONDUIT PER PLAN CONDUIT TO FLEX ADAPTER FLEXIBLE CONDUIT 2X4 WOOD BLOCKING
ACS
✔
✔
07/03/2019
DATE:
#12 HANGER WIRE @WIRE EA. CORNER OF FIXTURE, EXTRA #12 HANGER @ EA. CORNER OF ATTACHED TO FIXTURE W/ BODY (2) 1/8"W/(2) x 3/4"1/8" FIXTURE, ATTACHED TO BODY FIXTURE BOLTE, NUTS, LOCK WASHERS BRACKETWITH OR POP RIVITS & BRACKET OR TAB &PROVIDED TAB PROVIDED WITH SECURE TO TO FIXTURE. SECURE TO FIXTURE. STRUCTURE SIMILAR STRUCTURE SIMILAR TO CEILING SYSTEM. CEILING SYSTEM.
CEILING TYP. STRUCTURAL FRAMING (4)#10x1 1/4" WOOD SCREWS
J-BOX AT FEED END ONLY
FASTEN TO BLOCKING IN CEILING WALL. FASTEN TO OR (E) WALL STUD USING IDENTICAL USE IDENTICAL MEANS MEANS AS INDICATED AS INDICATED IN THISIN THIS DETAIL. DETAIL.
SCREW PROVIDED WITH CLAMP. CEILING & "T-BAR" SUSPENSION (SEE ARCHITECTURAL DRAWINGS.)
1/4"x3/4" WITH 1/4" x 3/4" LAGSCREWS SCREWS WITH 1" LAG WOOD SCREWS W/ WASHERS. 3/4" MIN. PENETRATION. SECURE FIXTUREBOX WITHWITH MIN.MIN. OF (6) OUTLET OF SCREWS. (4) SCREWS.
CONSULTANT
TYP. STRUCTURAL FRAMING
PETERS
1/4"x1 LAG SCREWS WITH (2) #8 x1/2" 1" MACHINE SCREWS WASHERS. 1 1/2" MIN. THROUGH FIXTURE MOUNTING PENETRATION. SECURE PLATE INTO OUTLET BOX RING FIXTURE WITH MIN. MOUNTING HOLES. OF (6) SCREWS TO WALL STUDS
FURNISH & INSTALL 4X6 WOOD BLOCKING BETWEEN WALL STUDS (4) #10 WOOD SCREWS AT EACH END LENGTH AS REQUIRED
engineering
consulting mechanical and electrical engineers
4x OUTLET BOX FIXTURE PER PLAN
BOX EXTENSION RING
SUSPENDED LINEAR FIXTURE MTG. DETAIL
1
NONE
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
E-502
WALL MOUNTED FIXTURE DETAIL
PRO F E S S I ONA ED NO R. ROMA L I
I N E ER
E-502
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
NO
NONE
4
FINISH WALL
BLOCKING BETWEEN STUDS PROVIDE 2 x 6 BLOCKING w/ SIMPSON U24 @ EA. END
E17247 EXP. 6/30/18 TA
S
E-502
LAY-IN FIXTURE MOUNTING DETAIL
1/8" AIRCRAFT CABLE - LENGTH AS REQUIRED - SECURE AT "EYE" WITH CABLE COMPRESSION CLAMPS (2) CRIMPS MINIMUM CLOSED LAG "EYE" SCREW - 5/16" DIA. 2" LENGTH IN 2X4 BLOCKING
CONDUIT PER PLANS
LIGHTING FIXTURE
PENDANT PENDANT LIGHT LIGHT FIXTURE FIXTURE NOTES: NOTES: 1. 1. PENDANT PENDANT LIGHTING LIGHTING FIXTURES FIXTURES SHALL SHALL BE BE FREE FREE TO TO SWING SWING AA MINIMUM MINIMUM OF OF 45° 45° FROM FROM THE THE VERTICAL VERTICAL IN IN ALL ALL DIRECTIONS DIRECTIONS WITHOUT WITHOUT CONTACTING CONTACTING OBSTRUCTIONS. OBSTRUCTIONS. 2. IN TRANSVERSE DIRECTIONS 2. PROVIDE PROVIDE CABLES SWAY ARRESTORS AT PENDANT AT PENDANTATSUPPORTS ALL LIGHT FIXTURES SUPPORTS ALL LIGHTAT FIXTURES NOT NOT SATISFYING NOTE 1 ABOVE. SATISFYING NOTE 1 ABOVE.
FIXTURE BODY & DOOR.
7
AIRCRAFT CABLE
OR FASTEN (E) WALLIN FASTEN TO TO BLOCKING STUD USING IDENTICAL CEILING OR WALL. USE MEANS AS INDICATED IDENTICAL MEANS AS IN THIS DETAIL.IN THIS INDICATED DETAIL.
NONE
EL
TE
EC TR I CA
O F CA L
L
I
A
D
AIRCRAFT CABLE
CANOPY MOUNTING PLATE W/1/4"-20 ROD CABLE RETAINER LEVELING FITTING
ER
T-BAR SAFETY CLIPS SNAP-ON SEISMIC FIXTURE CLAMPS FOR HOLD-DOWN TO SECURE MECHANICAL CLIP ATTACHMENT TO TROFFER TO "T-BAR". PROVIDE (2) @ T-BAR. CADDY #SFCLT, OR EQUAL. EA. END OF FIXTURE.
CONDUIT PER PLANS
G
CANOPY MOUNTING PLATE W/1/4"-20 ROD CABLE RETAINER
REG I S T
GRID SUPPORT WIRES, N.I.E.S.
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
FLS
✔
N I F OR
SEAL
PROJECT
C
TEHAMA CENTER STUDENT SERVICE FIXTURE SUPPORT BY GENERAL CONTRACTOR. PROVIDE 2x6 WOOD BLOCKING BETWEEN STRUCTURAL MEMBERS AND SECURE WITH MINIMUM OF (2) 16d NAILS EACH END.
CEILING SUPPORT WIRES BY CEILING INSTALLER, TYPICAL.
CONDUIT PER PLANS
770 DIAMOND AVE. RED BLUFF, CA 96080
CEILING FRAMING PER STRUCTURAL PLANS BLOCKING BETWEEN CEILING FRAMING. PROVIDE 2x4 WITH SIMPSON #U24 AT EACH. MOUNT WITH NAILS OR SCREWS SIZED PER MANUFACTURER'S REQUIREMENTS. PROVIDE AT FIXTURE MOUNTING HOLE.
SUPPORT WIRES BY ELECTRICAL CONTRACTOR, TYPICAL.
ROOF
CONDUIT PER PLAN
PROVIDE BAR HANGER W/ 1-1/4" WOOD SCREWS & RETAINER CLIPS
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
JUNCTION BOX. SECURE TO BLOCKING WITH MINIMUM OF (4) #10 WOOD SCREWS. ROOF WOOD STRUCTURAL MEMBER
ISSUED
MARK TYPICAL FIXTURE TYP 'F' & 'FE'. 3/8" DIA. RIGID STEM AND CANOPY WITH 45° SWIVEL.
CONDUIT PER PLAN LAY-IN CEILING GRID BY CEILING INSTALLER, TYPICAL.
8 E-502
WALKWAY CANOPY PENDANT NONE
1/4" ɸ x 3" LAG SCREW WITH FLAT WASHER, (1) @ EACH END OF 4' FIXTURE. FOR 8' FIXTURE, SECURE AT EACH END AND CENTER.
5 E-502
FINISHED CEILING LIGHTING FIXTURE PER PLAN
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
OUTLET BOX & EXTENSION RING, AS REQUIRED.
FIXTURE PER PLAN
T-BAR MOUNTED FIXTURE DETAIL
2
NONE
E-502
SURFACE MOUNTED FIXTURE DETAIL NONE
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
WRAP SAFETY CABLE AROUND 2 x 4 BLOCKING AND SECURE WITH CABLE COMPRESSION CLAMP
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
SIMPSON H1 TIE. CONNECT TO BLOCKING WITH #9 x 1-1/2" SIMPSON SD SCREWS. ALL HOLES TO BE FILLED, TYP.
A MINIMUM OF (2) SUPPORT WIRES AT OPPOSITE CORNERS OF EACH LIGHT FIXTURE. ELECTRICAL CONTRACTOR SHALL COORDINATE FIXTURE LOCATIONS WITH THE CONTRACTOR.
FLEX CONDUIT WITH ALL NECESSARY FITTINGS TO J-BOX PER PLANS. PROVIDE #12 BRANCH WIRING & #12 GROUND BOND TO LIGHT FIXTURE. 1" #6 WOOD SCREWS (TYP. FOR 4)
2"x4" BLOCKING
(3) 16d NAILS AT EA. END
BRANCH CCT. PER PLANS
CEILING
REFER TO SUSPENDED LINEAR FIXTURE MTG. DETAIL 4/E-502 FOR BLOCKING, FIXTURE SUPPORT AND POWER FEED INFORMATION. TYPICAL FOR POWER AND NONPOWER FEED ENDS OF FIXTURE.
3/16" AIRCRAFT CABLE - LENGTH AS REQUIRED. PROVIDE AT BOTH ENDS OF FIXTURE.
SCREW PROVIDED WITH CLAMP
A
LAY-IN LIGHT FIXTURE PER PLAN
MAIN T-BAR RUNNERS, TYPICAL
CROSS T-BAR, TYPICAL
SEISMIC FIXTURE CLAMPS ADJUSTABLE "T-BAR" LOCKFOR CLIP FOR MECHANICAL ATTACHMENT OF POSITIVE ATTACHMENT OF FIXTURE FIXTURE T-BAR. CADDY TO T-BAR.TOPROVIDE (2) @ EACH END #SFCLT, OR EQUAL. OF FIXTURE.
6 E-502
T-BAR FIXTURE MOUNTING DETAIL NONE
CEILING JOIST
2"x10" CEILING JOIST @ 24"O.C.
4" J-BOX AT FEED
GRID SUPPORT BY OTHERS
CEILING FIXTURE MOUNTING STEM 14 GA. STL. MT'G. STRAP (STRAP SHALL NOT BE VISABLE) FIXTURE HOUSING 45° MIN. SWAY, ALL DIRECTIONS
CANOPY ATTACH SAFETY CABLE TO FIXTURE. WRAP CABLE THROUGH 3/16" AIRCRAFT MOUNTING HOLES CABLE IN FIXTURE ATTACH TO BODY. HOUSING AND FIXTURE SECURE WITH CABLE COMPRESSION CLAMP FIXTURE MOUNTING STEM
TITLE
DETAILS
FEED POINT
CEILING TILE, TYPICAL
5/15/2019 9:16:46 AM
2 x 4 BLOCKING
3 E-502
SUSPENSON WITH 2X4 BLOCKING FEED POINT SUSPENDED FIXTURE SAFETY CABLE DETAIL DETAIL NONE
SHEET
E-502
017294 LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR FLS
✔
ACS
✔
✔
07/03/2019
DATE:
LED LIGHTING FIXTURE(S)
NEUTRAL
DW-311 OCCUPANCY SENSOR DIMMING WALL SWITCH GRY VIO
VIO
RED
RED
WHT
WHT
BLK
BLK
YEL
BLK
CONSULTANT
REMOTE SWITCH (WHERE SHOWN ON PLANS)
MAIN SWITCH
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
EARTH GROUND
PETERS
engineering
NOTES: 1. DESIGN AND PART NUMBERS ARE BASED ON WATTSTOPPER PRODUCTS U.O.N. SUBSTITUTIONS OF PRODUCTS OF EQUAL QUALITY AND PERFORMANCE MAY BE SUBMITTED. 2. PROGRAM VACANCY SENSORS IN ROOMS TO BE MANUAL-ON/AUTO-OFF 3. PROVIDE SWITCH COLOR(S) AS SELECTED BY ARCHITECT. 4. ALL WIRING SHALL BE INSTALLED IN CONDUIT.
ER REG I S T
I N E ER
E-503
DIMMING OCC SENSOR WALL SWITCH WIRING
PRO F E S S I ONA ED NO R. ROMA L I
NO
1
consulting mechanical and electrical engineers
E17247 EXP. 6/30/18
NONE S
TA
EL
TE
EC TR I CA
O F CA L
L
I
A
EARTH GROUND
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
G
D
DW-311 OCCUPANCY SENSOR DIMMING WALL SWITCH GRY
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
HOT
N I F OR
SEAL
LED 0-10V LIGHTING FIXTURE(S)
PROJECT
C LMDC-100 LMDC-100 OCCUPANCY SENSOR NEUTRAL
WHT
HOT
BLK GRN
LMDM-101 DIMMER WALL SWITCH
LMRC-211 1 LOAD DIMMING ROOM CONTROLLER
TEHAMA CENTER STUDENT SERVICE 770 DIAMOND AVE. RED BLUFF, CA 96080
RED
3 GRY VIO
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
EARTH GROUND
TO ADDITIONAL LIGHTING ROOM CONTROLLER (WHERE REQUIRED) NETWORK CABLE FROM LIGHTING CONTROL PANEL OR PREVIOUS LIGHTING ROOM CONTROLLER
LMRJ SERIES PRE-TERMINATED CABLES OR CAT5e. FREE TOPOLOGY & SPLITTER ACCEPTABLE
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
NOTES: 1. ALL ROOM CONTROLLERS SHALL BE NETWORKED TO BUILDING CONTROL PANEL. 2. DESIGN AND PART NUMBERS ARE BASED ON WATTSTOPPER PRODUCTS U.O.N. 3. PROGRAM VACANCY SENSORS IN ROOMS TO BE MANUAL ON/AUTO OFF 4. PROVIDE SWITCH COLOR(S) AS SELECTED BY ARCHITECT. 5. ALL WIRING, EXCEPT CAT5E CABLES, SHALL BE INSTALLED IN CONDUIT.
2 E-503
TYP. 1-ZONE LIGHTING WIRING DIAGRAM NONE
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
LED 0-10V LIGHTING FIXTURE(S)
0-10V DIMMER INPUTS TO REMAIN UNCONNECTED. FIXTURE WILL OPERATE AT FULL BRIGHTNESS.
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
LMDC-100 OCCUPANCY SENSOR NEUTRAL
WHT
HOT
BLK
LMSW-101 WALL SWITCH
LMRC-211 1 LOAD DIMMING ROOM CONTROLLER RED
GRN
GRY VIO
EARTH GROUND
OUTPUTS TO REMAIN UNCONNECTED.
TO ADDITIONAL LIGHTING ROOM CONTROLLER (WHERE REQUIRED)
A
LMRJ SERIES PRE-TERMINATED CABLES OR CAT5e. FREE TOPOLOGY & SPLITTER ACCEPTABLE
NETWORK CABLE FROM LIGHTING CONTROL PANEL OR PREVIOUS LIGHTING ROOM CONTROLLER
TITLE
DETAILS
5/15/2019 9:16:47 AM
NOTES: 1. ALL ROOM CONTROLLERS SHALL BE NETWORKED TO BUILDING CONTROL PANEL. 2. DESIGN AND PART NUMBERS ARE BASED ON WATTSTOPPER PRODUCTS U.O.N. 3. PROGRAM VACANCY SENSORS IN ROOMS TO BE MANUAL ON/AUTO OFF 4. PROVIDE SWITCH COLOR(S) AS SELECTED BY ARCHITECT. 5. ALL WIRING, EXCEPT CAT5E CABLES, SHALL BE INSTALLED IN CONDUIT.
3 E-503
NON-DIMMING LIGHTING WIRING DIAGRAM NONE
SHEET
E-503
017294 LIONAKIS 2017
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR
M
ACS
✔
✔
07/03/2019
DATE:
(E)UTILITY METER
(E) UNDERGROUND PULL SECTION
PROVIDE PLACARD AT THE MAIN DEVICE LISTING THE AVAILABLE FAULT CURRENT FROM THE UTILITY. INCLUDE THE DATE PROVIDED PER CEC 110.24.
(E) 1600/3
(E) MAIN SWITCHBOARD 'MSB' 1600A BUS, 120/208V, 3∅, 4W
(E) 125/2
(E) 125/2
/3 1200AF 400AT
PANEL '2D'
Total Load: Total Amps:
29955 VA 251 A
27177 VA 226 A
0
0
0
0
0
0
0
3
150 A PANEL '3D'
11597 15820 27993 VA 234 A
SPARE
(E)(2)4"C., PULL 8#350KCMIL CU
THWN CU + 1#1 THWN CU GND
(E)(2)4"C., E/W 4#400MCM
THWN CU + 1#1 THWN CU GND
consulting mechanical and electrical engineers
+ 1#2/0 CU GND IN EACH
(2)4"C., 8#350KCMIL CU
THWN CU + 1#1 THWN CU GND
(E)(2)4"C., E/W 4#400MCM
THWN CU + 1#1 THWN CU GND
(E)(2)4"C., E/W 4#400MCM
(E) PANEL '1B' BLDG 2
(E) PANEL '1C' BLDG 3
PRO F E S S I ONA ED NO R. ROMA L I E17247 EXP. 6/30/18 TA
EL
TE
EC TR I CA
O F CA L
L
N I F OR
I
SEAL
PANEL '1D'
#3/0 CU GND
(E) #3/0 UFER GND
(E) PANEL '2A' BLDG 1
(E) PANEL '2B' BLDG 2
PROJECT
(E) PANEL '2C' BLDG 3
PANEL '3D'
TEHAMA CENTER STUDENT SERVICE
+ 1#4 CU GND
0
SCIENCE BLDG
(E) PANEL '1A' BLDG 1
3"C., 4#350KCMIL CU
0
SPARE SPARE SPARE SPARE SPARE SPARE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE
(E) PANEL
CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
+ 1#4 CU GND
0
Circuit Description
3"C., 4#350KCMIL CU
0
Trip 20 A 20 A 20 A 20 A 20 A 20 A -------------
+ 1#4 THWN CU GND
576
Poles 1 1 1 1 1 1 -------------
(E) 3"C., 4#350MCM THWN CU
C
+ 1#4 THWN CU GND
Poles A B 1 278 0 1 1361 0 1 1 1688 0 1 548 0 1 -0 0 -0 0 --0 0 -0 0 --0 0 -0 0 --0 0 -0 0 -13514 14500 11675 13600 150 A 3
(E) 3"C., 4#350MCM THWN CU
Trip 20 A 20 A 20 A 20 A 20 A 20 A -------------
+ 1#4 THWN CU GND
C
Circuit Description LIGHTS-118,119,120,121 LIGHTS- SOUTH LIGHTS- NORTH WEST LIGHTS- NORTH EAST LIGHTS- EXTERIOR SPARE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE
CU + 1#2 THWN CU GND
(E) 4"C., 4#600MCM THWN
A.I.C. Rating: 22kA Mains Type: MLO Mains Rating: 400 A MCB Rating:
Notes:
CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
PETERS
EXISTING UNDERGROUND PULL BOX
(E) 3"C., 4#350MCM THWN CU
Volts: 120/208 Wye Phases: 3 Wires: 4
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
S
Location: CUSTODIAL 119 Supply From: Mounting: Surface Enclosure: 1
CONSULTANT
1
engineering
(E) #3/0 COPPER BOND TO BLDG STEEL
Branch Panel: 1D
(E) PFB/3
I N E ER
(E) #3/0 COPPER BOND TO GAS PIPE
M
(E) PFB/3
NO
(E) #3/0 COPPER BOND TO COLD WATER PIPE
(E)(2)4"C., E/W 4#400MCM
(E) PG&E PAD MOUNTED TRANSFORMER
(E) 4"C., 4#600MCM THWN
(E) UFER GND. 20' OF #3/0 BARE COPPER ENCASED IN 3" OF CONCRETE.
(E) PG&E PRIMARY SERVICE
CU + 1#2 THWN CU GND
G
SPARE
SPARE
N
(E) PFB/3
A
(E) 150/2
ER
(E) 400/3
G
(E) 400/3
REG I S T
(E) 400/3
(E) 800/3
+ 1#2/0 CU GND IN EACH
D
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
FLS
✔
770 DIAMOND AVE. RED BLUFF, CA 96080
3
PANEL '2D'
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ONE LINE DIAGRAM
1 E-601
NONE
Legend:
Load Classification HVAC Lighting Lighting - Dwelling Unit Other Power Receptacle
Connected Load 26042 VA 3390 VA 917 VA 520 VA 10523 VA 43780 VA
Demand Factor 100.00% 125.00% 125.00% 125.00% 100.00% 61.42%
Estimated Demand 26042 VA 4238 VA 1146 VA 650 VA 10523 VA 26890 VA
Panel Totals ISSUED
Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand:
85124 VA 69430 VA 236 A 193 A
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
KEYED NOTES: 1
Notes:
PROVIDE METERING TO RECORD AND MONITOR REAL TIME AND PEAK POWER DEMAND IN KW AND ENERGY USE IN KWH.
Branch Panel: 3D Location: Supply From: Mounting: Enclosure:
B
Branch Panel: 2D Location: Supply From: Mounting: Enclosure:
Volts: 120/208 Wye Phases: 3 Wires: 4
CUSTODIAL 119 1D Surface 1
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
Trip
Poles
A 876
DOAS-1
15 A
B
A.I.C. Rating: 22kA Mains Type: MLO Mains Rating: 250 A MCB Rating:
C
3
876 2664
AC-1
30 A
1500
2664 5016
70 A
601
5016
1018 5016
20 A
2
SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPACE
20 A 20 A 20 A 20 A 20 A 20 A 20 A --
1 1 1 1 1 1 1 --
SPACE
--
--
SPACE
--Total Load: Total Amps:
0
0 0 0 0
0
0 0
0 0
0
0
0 0
0
360
360 0
0
601
1018
3
ACCU-1
2080
2080
3
2664 VRF-1
Poles
1500 876
A
Load Classification HVAC Other Power Receptacle
A.I.C. Rating: 22kA Mains Type: MLO Mains Rating: 400 A MCB Rating:
MANAGEMENT
0
0 0
13514 VA 113 A
0
11675 VA 97 A
0 0 11597 VA 97 A
Trip
Circuit Description
2
20 A EWH-1
2
30 A IEWH-2
2
20 A BSB-1 + FC-Z09-Z17
2
20 A BSB-2 + FC-Z01-Z08
1 1 1 1 1 1 1 1 1 1 --
20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A --
--
--
SPACE
--
--
SPACE
EF-1 RECEPTS- ROOF SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPACE
Connected Load 26042 VA 360 VA 10023 VA 360 VA
Demand Factor 100.00% 125.00% 100.00% 100.00%
Estimated Demand 26042 VA 450 VA 10023 VA 360 VA
CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53
Circuit Description RECEPTS-100A, 120, 119, 118 RECEPTS- 108 RECEPTS-107 RECEPTS-106 RECEPTS-105 RECEPTS-109 RECEPTS-110 RECEPTS-111 RECEPTS-112 RECEPTS-113 RECEPTS-114 RECEPTS-115 RECEPTS-116 RECEPTS-117 RECEPTS-122 RECEPTS-150 RECEPT-IDF 121 EAST RECEPT-IDF RACK RECEPT-IDF 121 SOUTH RECEPT-IDF 121 WEST SIGNAGE TV, SARS TV, 100 PROJECTOR 101, TV 102 100 EAST WALL PCs CENTER 100 SPARE SPARE SPARE
Trip Poles 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 Total Load: Total Amps:
A 1080
B 540 1080
1080
1260
1260
1080
900
1080
360
1080
1000
540
1440
500
1260
1260
1260
720
0 720
0
1080
1080
900 360
1000
900
1080 360
360
1080
0
1080 1080
720
1000
1440 1080
1080
1260
900 1260
1080
1000
1080 1080
1080
C
0
0 0
14500 VA 122 A
0
13600 VA 113 A
0 0 15820 VA 133 A
Poles 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
Circuit Description COUNTER PCS-100A COPIER-100A COPIER-100A COMPUTERS-100 SPARE RECEPTS-101 SOUTH RECEPTS-101 NORTH RECEPTS-103 RECEPTS-104 RECEPTS-102 RECEPTS-131 RECEPTS-129 RECEPTS-127 RECEPTS-125 RECEPTS-126 RECEPTS-128 RECEPTS-130 RECEPTS-132 RECEPTS-124 RECEPTS-123 SOUTH RECEPTS-123 NORTH FIRE SPRINKLER BELL * FIRE ALARM POWER SUPPLY * TEMP CONTROL PANEL SPARE SPARE SPARE
Legend:
Legend:
Notes: 5/15/2019 9:16:47 AM
Circuit Description
Volts: 120/208 Wye Phases: 3 Wires: 4
Notes:
Notes:
CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
CUSTODIAL 119 1D Surface 1
Panel Totals Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand:
36785 VA 36875 VA 102 A 102 A
Load Classification Other Power Receptacle
CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 LIONAKIS 2017
AGENCY
TITLE
Connected Load 0 VA 500 VA 43420 VA
Notes: * PROVIDE BREAKER WITH RED HANDLE AND LOCK-ON DEVICE.
Demand Factor 0.00% 100.00% 61.52%
Estimated Demand 0 VA 500 VA 26710 VA
Panel Totals Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand:
43920 VA 27210 VA 122 A 76 A
ONE LINE DIAGRAM & PANEL SCHEDULES
SHEET
E-601
2"
1
2
3
4
5
1"
APP. 02-117123
0 1/4" 1/2"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
SS
INC:
REVIEWED FOR FLS
✔
ACS
✔
✔
07/03/2019
DATE:
WEST PENN #244
D
(E) MDF IN BUILDING 1
EXISTING EMPTY 2" INT/SEC CONDUIT.
IDF 121 EXISTING UNDERGROUND PULL BOX, TYPICAL. REFER TO SITE PLAN FOR EXACT QUANTITIES
EXISTING EMPTY 2" INT/SEC CONDUIT.
EXISTING 2" CONDUIT STUB SIGNAL TERMINAL CABINET 'STC-4' 2" INT/SEC CONDUIT.
IA
IA
IA
IA
IA
IA
IA
IA
IA
IA
IA
WEST PENN #224, TYPICAL
150
124
126
128
130
132
100
100
101
102
150
WEST PENN #244, TYPICAL
150
122
123
124
151
100D
100
101
100B
150
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
GB
GB
GB
GB
GB
GB
GB
GB
GB
GB
CONSULTANT
124
124
126
128
130
132
100
100
100
102
WEST PENN #226
EXISTING INTRUSION ALARM PANEL
WEST PENN #226
PS 120
PETERS
engineering
B EXISTING 4" DATA CONDUITS.
consulting mechanical and electrical engineers
(2) 4" DATA CONDUITS.
NOTES: 1. PROVIDE (1) WEST PENN AQ #244 (KEYPAD), & (1) WEST PENN AQ #244 (DATA) BETWEEN EXISTING INTRUSION ALARM PANEL AND SIGNAL TERMINAL CABINET 'STC-4'. 2. DO NOT SPLICE CABLES. CABLES SHALL BE RUN CONTINUOUS FROM ALARM PANEL TO TERMINAL BLOCKS, TERMINAL BLOCKS TO DEVICES AND BETWEEN DEVICES. 3. CONNECT NEW CABLES TO EXISTING ALARM PANEL AND PROGRAM EXISTING ALARM PANEL AS REQUIRED FOR NEW DEVICE OPERATIONS. 4. REFER TO SPECIFICATIONS FOR EQUIPMENT REQUIREMENTS..
3
ONE LINE DIAGRAM - DATA NONE
1 E-602
E17247 EXP. 6/30/18 TA
S
NOTES: 1. PROVIDE (1) 24-FIBER SINGLEMODE OPR CABLE AND (1) 12-FIBER MULTIMODE OPR CABLE. FROM FIBER PATCH PANEL IN EXISTING MDF TO FIBER PATCH PANEL IN IDF 121. INSTALL CABLES IN 1" INNERDUCT THROUGH 4" CONDUITS. 2. REFER TO SPECIFICATIONS FOR EQUIPMENT REQUIREMENTS.
E-602
REG I S T
36-PORT FIBER OPTIC PATCH PANEL IN DATA RACK
I N E ER
NEW 36-PORT FIBER OPTIC PATCH PANEL. MOUNT IN EXISTING DATA RACK.
PRO F E S S I ONA ED NO R. ROMA L I
NO
ER
EXISTING 4" DATA CONDUITS.
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
G
EXISTING UNDERGROUND PULL BOX, TYPICAL. REFER TO SITE PLAN FOR EXACT QUANTITIES
EL
TE
EC TR I CA
O F CA L
L
I
A
WEST PENN #244, TYPICAL
(E) BUILDING 1 WORK ROOM
KP 100B
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
STORAGE 120
N I F OR
ONE LINE DIAGRAM - INTRUSION NONE
SEAL
PROJECT
C
TEHAMA CENTER STUDENT SERVICE 770 DIAMOND AVE. RED BLUFF, CA 96080 3 CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
STORAGE 120 WEST PENN #25290B, TYPICAL TO EACH SPEAKER 100
100A
100B
B 100D (E) BUILDING 1 WORK ROOM EXISTING UNDERGROUND PULL BOX, TYPICAL. REFER TO SITE PLAN FOR EXACT QUANTITIES
EXISTING EMPTY 2" INT/SEC CONDUIT.
EXISTING EMPTY 2" INT/SEC CONDUIT.
101
EXISTING 2" CONDUIT STUB SIGNAL TERMINAL CABINET 'STC-4' 2" INT/SEC CONDUIT.
EXISTING SIGNAL TERMINAL CABINET 'STC-1'
123
124
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 LIONAKIS 2017
AGENCY
150
SOUTH
WEST
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
NORTH
EAST
NOTES: 1. PROVIDE (1) 25-PAIR #22AWG OUTSIDE PLANT TELEPHONE CABLE BETWEEN EXISTING SIGNAL TERMINAL CABINET 'STC-1' AND SIGNAL TERMINAL CABINET 'STC-4'. 2. DO NOT SPLICE CABLES. CABLES SHALL BE RUN CONTINUOUS BETWEEN TERMINAL BLOCKS IN SIGNAL TERMINAL CABINETS AND FROM TERMINAL BLOCKS TO DEVICES. 3. TERMINATE ALL CABLE PAIRS ON PUNCHDOWN TERMINAL BLOCKS, INCLUDING SPARES. PROVIDE NEW PUNCHDOWN TERMINAL BLOCKS AS REQUIRED FOR CABLE TERMINATIONS. 4. CROSS-CONNECT NEW CABLE PAIRS TO EXISTING SPARE PAIRS IN 'STC-1' AS REQUIRED TO OPERATE NEW DEVICES. 5. CONNECT CABLES AND PROGRAM EXISTING INTERCOM SYSTEM AS FOLLOWS: 5.1. EACH INTERIOR SPEAKER TO BE ON AN INDEPENDENT ZONE. 5.2. EXTERIOR SPEAKERS TO BE GROUPED AS A ZONE. 5.3. ADD NEW SPEAKERS INTO EXISTING ALL CALL, ZONE PAGING AND TIME BASED PROGRAMS AS DIRECTED BY DISTRICT. 6. REFER TO SPECIFICATIONS FOR EQUIPMENT REQUIREMENTS.
A
2 E-602
TITLE
ONE LINE DIAGRAM
ONE LINE DIAGRAM - INTERCOM NONE
5/15/2019 9:16:48 AM
SHEET
E-602
2"
1
2
3
4
5
NL NO, # NTS OC. P PB PFB PFCT
THE FOLLOWING IS A BRIEF DESCRIPTION OF THE SCOPE OF WORK FOR THIS PROJECT. IT IS GENERAL IN NATURE AND DOES NOT CONSTITUTE ALL THAT IS TO BE DONE NOR DOES IT INDICATE THE SEQUENCE OF INSTALLATION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FULLY COMPLETE THE WORK IDENTIFIED IN THE PLAN DOCUMENTS. 1.
2. 3. 4.
EXTEND EXISTING FIRE ALARM SYSTEM TO NEW BUILDING WITH CIRCUITS AS FOLLOWS: 1.1. SIGNALING LINE CIRCUITS SHALL BE CLASS B, LEVEL 1 1.2. INITIATING DEVICE CIRCUITS SHALL BE CLASS B, LEVEL 1 1.3. NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLASS B, LEVEL 1. PROVIDE AUTOMATIC INITIATION DEVICES THROUGHOUT THE BUILDING. PROVIDE FIRE SPRINKLER WATER FLOW AND TAMPER SWITCH MONITORING. PROVIDE NOTIFICATION CIRCUIT EXTENDER PANEL TO POWER AUDIBLE/VISUAL CIRCUITS THROUGHOUT THE BUILDING.
EXISTING FIRE ALARM CONTROL PANEL
FACP
P
FIRE ALARM SYSTEM NOTES
PRIOR TO ORDERING AND INSTALLATION THE FIRE ALARM SYSTEM AND ASSOCIATED EQUIPMENT PREPARE AND SUBMIT A COMPLETE SUBMITTAL PACKAGE COMPLETE WITH DETAILED SHOP DRAWINGS (INCLUSIVE OF CALCULATIONS AND POINT BY POINT WIRING DIAGRAMS), CUT SHEETS AND COPIES OF THE APPROVED CALIFORNIA STATE FIRE MARSHAL LISTINGS FOR EACH COMPONENT OF THE SYSTEM TO BE INSTALLED.
5.
6.
R
CO
F
S
AIM
2
NOTIFIER
NFS2-640
7165-0028:0243
ADDRESSABLE NOTIFICATION CIRCUIT EXTENDER PANEL PANEL CABINET 12V, 7AH BATTERIES
NOTIFIER NOTIFIER VARIES
ACPS-610 CAB-PS1 VARIES
7315-0028:0248 N/A N/A
ADDRESSABLE SMOKE DETECTOR DETECTOR BASE
NOTIFIER SYSTEM SENSOR
FSP-851 B210LP
7272-0028:0206 7300-1653:0109
ADDRESSABLE MULTI-CRITERIA FIRE/CO DETECTOR DETECTOR SOUNDER BASE
NOTIFIER SYSTEM SENSOR
FCO-851 B200S
7275-0028:0264 7300-1653:0213
ADDRESSABLE DUAL ACTION MANUAL PULL STATION METAL SURFACE BACKBOX
NOTIFIER NOTIFIER
NBG-12LX SB-10
7150-0028:0199 N/A
ADDRESSABLE DUCT DETECTOR HOUSING ADDRESSABLE SMOKE DETECTOR ADDRESSABLE OUTPUT RELAY MODULE
NOTIFIER NOTIFIER NOTIFIER
DNR FSP-851 FRM-1
3242-1653:0209 7272-0028:0206 7300-0028:0219
ADDRESSABLE DUAL INPUT MODULE
NOTIFIER
FDM-1
7300-0028:0219
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
AOM
ADDRESSABLE OUTPUT RELAY MODULE
NOTIFIER
FRM-1
7300-0028:0219
IM
ADDRESSABLE ISOLATION MODULE
NOTIFIER
ISO-X
7300-0028:0261
WALL MOUNTED MULTI-CANDELA HORN/STROBE (X = CANDELA SETTING)
WHEELOCK
HSR
7125-0785:0168
WALL MOUNTED MULTI-CANDELA STROBE ONLY (X = CANDELA SETTING)
WHEELOCK
STR
7125-0785:0168
WALL MOUNTED EXTERIOR HORN WEATHERPROOF BACKBOX
WHEELOCK WHEELOCK
AH-24WP-R WBB-R
7125-0785:0131 N/A
FIRE SPRINKLER RISER
FURNISHED BY FIRE SPRINKLER CONTRACTOR
FURNISHED BY FIRE SPRINKLER CONTRACTOR
FURNISHED BY FIRE SPRINKLER CONTRACTOR
WF
FIRE SPRINKLER RISER WATERFLOW SWITCH
FURNISHED BY FIRE SPRINKLER CONTRACTOR
FURNISHED BY FIRE SPRINKLER CONTRACTOR
FURNISHED BY FIRE SPRINKLER CONTRACTOR
VS
FIRE SPRINKLER RISER TAMPER SWITCH
FURNISHED BY FIRE SPRINKLER CONTRACTOR
FURNISHED BY FIRE SPRINKLER CONTRACTOR
FURNISHED BY FIRE SPRINKLER CONTRACTOR
FIRE SPRINKLER RISER WATERFLOW BELL
FURNISHED BY FIRE SPRINKLER CONTRACTOR
FURNISHED BY FIRE SPRINKLER CONTRACTOR
FURNISHED BY FIRE SPRINKLER CONTRACTOR
X
ANY DISCREPANCIES IN THE DRAWING SET WITH APPLICABLE CODES OR RECOGNIZED STANDARDS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER PRIOR TO ORDERING AND INSTALLING EQUIPMENT.
X
INFORMATION SHOWN ON THESE PLANS RELATING TO THE EXISTING FIRE ALARM SYSTEM HAS BEEN OBTAINED FROM THE ORIGINAL AND "AS BUILT/RECORD" DRAWINGS AND FROM FIELD OBSERVATIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL EXISTING WIRING AND RELATED CONDITIONS BEFORE PROCEEDING WITH THE EXECUTION OF WORK. MODIFICATIONS TO THE EXISTING WIRING SYSTEMS SHALL ENSURE CIRCUIT CONTINUITY TO ALL REMAINING EXISTING DEVICES OR EQUIPMENT ASSOCIATED WITH THE EXISTING REMAINING WIRING SYSTEM. A STAMPED SET OF APPROVED FIRE ALARM SHOP DRAWINGS SHALL BE KEPT ON THE JOB SITE AND USED FOR INSTALLATION. ANY DEVIATION FROM THE APPROVED DOCUMENTS, INCLUDING SUBSTITUTION OF DEVICES, SHALL BE APPROVED BY THE INSPECTOR OF RECORD. ALL DEVIATIONS SHALL BE MARKED-UP ON THE JOB SITE SET OF THE APPROVED DOCUMENTS. THE APPROVED DOCUMENTS SHALL BE KEPT UP-TO-DATE WITH ALL DEVIATIONS (INCLUDING CONDUIT/CABLE ROUTING CHANGES, WIRING CHANGES AND DEVICE ADDRESS CHANGES) AND SHALL BE USED AS REDLINES FOR THE FINAL AS AS-BUILT SET OF DRAWINGS.
WP H
7.
UPON ACTIVATION OF ANY INITIATION DEVICE THE FIRE ALARM SYSTEM SHALL TRANSMIT AN ALARM OR SUPERVISORY SIGNAL TO THE MONITORING STATION OF THE OWNER'S CHOICE.
8.
UPON RECEIPT OF ANY TROUBLE CONDITION THE FIRE ALARM SYSTEM SHALL TRANSMIT A TROUBLE SIGNAL TO THE MONITORING STATION OF THE OWNER'S CHOICE.
F
9.
UNLESS SPECIFICALLY NOTED OTHERWISE, DUCT SMOKE DETECTORS SHALL BE PROVIDED BY THE FIRE ALARM CONTRACTOR AND INSTALLED BY THE MECHANICAL CONTRACTOR. DUCT DETECTORS SHALL BE INSTALLED IN COMPLIANCE WITH NFPA 72, 2016 EDITION SECTION 17.7.5.5.
FATC
FIRE ALARM TERMINAL CABINET
SPACE AGE
TCX - SIZE AS REQUIRED
7300-0553:0110
FAD
FIRE ALARM DOCUMENTS BOX
SPACE AGE
SSU00685 (ACE-11)
7300-0553:0110
11. TO ENSURE THAT AUDIBLE PUBLIC MODE SIGNALS ARE CLEARLY HEARD THEY SHALL HAVE A SOUND LEVEL AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 dB ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS, WHICHEVER IS GREATER, MEASURED 5 FT ABOVE THE FLOOR IN THE AREA REQUIRED TO BE SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (dBA) (NFPA 72, 2016 EDITION SECTION 18.4.3.1) .
consulting mechanical and electrical engineers
PRO F E S S I ONA ED NO R. ROMA L I E17247 EXP. 6/30/18 TA
EL
TE
EC TR I CA
O F CA L
L
N I F OR
I
SEAL
PROJECT
TEHAMA CENTER STUDENT SERVICE
12. THE ALARM AUDIBLE SIGNAL PATTERN USED TO NOTIFY OCCUPANTS OF THE NEED TO EVACUATE (LEAVE THE BUILDING) OR RELOCATE (FROM ONE AREA TO ANOTHER) SHALL BE THE STANDARD ALARM EVACUATION SIGNAL CONSISTING OF A THREE-PULSE TEMPORAL PATTERN (NFPA 72, 2016 EDITION SECTION 18.4.2.1) . 13. VISUAL DEVICES SHALL NOT EXCEED 2 FLASHES PER SECOND AND SHALL NOT BE SLOWER THAN 1 FLASH EVERY SECOND. THE DEVICE SHALL HAVE A PULSING LIGHT SOURCE NOT LESS THAN .0375 LUMENS PER SQUARE FEET AND MEET ADA COMPLIANCE. WHEN THERE IS MORE THAN TWO VISUAL APPLIANCES OR GROUPS OF SYNCHRONIZED VISUAL APPLIANCES WITHIN THE FIELD OF VIEW ALL APPLIANCES SHALL BE SYNCHRONIZED. 14. AN AVERAGE AMBIENT SOUND LEVEL GREATER THAN 105 dBA SHALL REQUIRE THE USE OF A VISIBLE NOTIFICATION APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.4.1.1)
FLS
I N E ER
3.
4.
S
THE INSTALLATION OF THE FIRE ALARM SYSTEM SHALL CONFORM TO THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS: a. CODE OF FEDERAL REGULATIONS (CFR) b. AMERICAN NATIONAL DISABILITY ACT (ADA) c. ENVIRONMENTAL PROTECTION AGENCY (EPA) d. FEDERAL COMMUNICATIONS COMMISSION (FCC) e. OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) f. UNDERWRITERS LABORATORIES INC. (UL) g. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) h. NATIONAL FIRE PROTECTION ASSOCIATION 72 (NFPA 72) WITH CALIFORNIA AMENDMENTS. i. CALIFORNIA ELECTRICAL CODE (CEC) j. CALIFORNIA BUILDING CODE (CBC) k. CALIFORNIA FIRE CODE (CFC) FIRE ALARM PACKAGE SHALL INCLUDE DETAILED SHOP DRAWINGS, CUT SHEETS, AND COPIES OF THE APPROVED CSFM (CALIFORNIA STATE FIRE MARSHAL) LISTINGS FOR DEVICES, PROGRAMING, COMMISSIONING, STARTUP, AND ONE YEAR OF MAINTENANCE AFTER THE INSTALLATION IS ACCEPTED AND SIGNED OFF BY THE INSPECTOR OF RECORD.
SS
CSFM #
NEW DEVICES
S
2.
MODEL #
DATE:
NAC
1.
MANUFACTURER
EXISTING DEVICES
10. THE TOTAL SOUND PRESSURE LEVEL PRODUCED BY COMBINING THE AMBIENT SOUND PRESSURE LEVEL WITH ALL AUDIBLE NOTIFICATION APPLIANCES OPERATING SHALL NOT EXCEED 110 dBA AT THE MINIMUM HEARING DISTANCE (NFPA 72, 2016 EDITION SECTION 18.4.1.2).
C
DESCRIPTION
REVIEWED FOR ✔
NO
PH, Ø PLYWD PNL PR PVC (R) REQ'D RM RMC (RR) SPEC STC SQ SW TEL TTB TYP UG UON V WP WT W W/ XFMR &
FIRE ALARM SYSTEM COMPONENTS
INC:
A
ISO J-BOX KCMIL KVA KW LC LV MCM MECH MDP MH MISC MSB (N) NIC NIES
SHORT CIRCUIT CURRENT (RMS SYMMETRICAL) ISOLATED JUNCTION BOX THOUSAND CIRCULAR MILLS KILO VOLT AMP KILOWATT LIGHTING CONTROL PANEL LOW VOLTAGE THOUSAND CIRCULAR MILLS MECHANICAL MAIN DISTRIBUTION PANEL METAL HALIDE MISCELLANEOUS MAIN SWITCHBOARD NEW NOT IN CONTRACT NOT IN ELECTRICAL SECTION OF THESE PLANS & SPECS. NIGHT LIGHT NUMBER NOT TO SCALE ON CENTER POLE PULL BOX PROVISION FOR FUTURE BREAKER W/ MOUNTING HARDWARE PROVISION FOR FUTURE CURRENT TRANSFORMER PHASE PLYWOOD PANEL PAIR POLYVINYL CHLORIDE CONDUIT RELOCATE/RELOCATED REQUIRED ROOM RIGID METAL CONDUIT REMOVE AND REPLACE SPECIFICATION SIGNAL TERMINAL CABINET SQUARE SWITCH TELEPHONE TELEPHONE TERMINAL BOARD TYPICAL UNDERGROUND UNLESS OTHERWISE NOTED VOLTS WEATHERPROOF WEIGHT WATT WITH TRANSFORMER AND
ER
ISC
S
AT AMPERE ALTERNATING CURRENT AIR CONDITIONING AMP FRAME ABOVE FINISHED FLOOR AMPERES INTERRUPTING CAPACITY AMP TRIP SETTING AMERICAN WIRE GAUGE BARE COPPER BOARD BELOW FINISHED CEILING BREAKER BUILDING BOOSTER POWER SUPPLY CONDUIT CIRCUIT BREAKER CIRCUIT CEILING CONDUIT ONLY, WITH PULL LINE CONTINUOUS COPPER METALLIC COLD WATER PIPE DEMOLISH DIRECT CURRENT DISCONNECT DISTRIBUTION PANEL EXISTING EACH EVENING LIGHT ELECTRIC EMERGENCY ELECTRICAL METALLIC TUBING END OF LINE DEVICE EQUIPMENT EXISTING RELOCATED ELECTRICAL WATER COOLER ELECTRIC WATER HEATER FUTURE FIRE ALARM CONTROL PANEL FIRE ALARM EXTENDER PANEL FIRE ALARM TERMINAL CABINET FLUORESCENT FOOT GAUGE GROUND FAULT CIRCUIT INTERRUPT GROUND METALLIC GAS PIPE GYPSUM HIGH INTENSITY DISCHARGE HORSE POWER HEIGHT HERTZ INTERMEDIATE METALLIC CONDUIT INCH
G
D
@ A AC A/C AF AFF AIC AT AWG BC BD BFC BRKR BLDG BPS C C/B CIRC CLG CO CONT CU CWP (D) DC DISC DP (E) EA EL ELEC EM EMT EOL EQUIP (ER) EWC EWH (F) FACP FAEP FTC FLUOR FT GA GFCI GND GP GYP HID HP HT HZ IMC IN
APP. 02-117123
SCOPE OF WORK
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
ABBREVIATIONS LIST
REG I S T
1"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
FIRE ALARM SYMBOLS LIST
770 DIAMOND AVE. RED BLUFF, CA 96080
HOMERUN TO PANELBOARD OR RESPECTIVE TERMINAL
3
.
CONCEALED CONDUIT RUN, SIZE AS REQUIRED EXISTING WORK SHOWN THE SAME AS NEW EXCEPT LIGHT & DASHED, UNLESS OTHERWISE NOTED
15. THE FLASH RATE SHALL NOT EXCEED TWO FLASHES PER SECOND (2 Hz) NOR BE LESS THAN ONE FLASH EVERY SECOND (1 Hz) THROUGHOUT THE LISTED VOLTAGE RANGE OF THE APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.5.3.1) . X 16. WHERE MORE THAN TWO VISIBLE NOTIFICATION APPLIANCES OR GROUPS OF SYNCHRONIZED APPLIANCES ARE IN THE SAME ROOM OR ADJACENT SPACE IN THE FIELD OF VIEW ALL APPLIANCES ARE REQUIRED SYNCHRONIZE TOGETHER (NFPA 72, 2016 EDITION SECTION 18.5.5.4.2) .
X 1
EXISTING ELECTRICAL EQUIPMENT TO BE REMOVED SYMBOL REFERING TO KEYED NOTE ON SAME SHEET
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
17. ADJUST AND INSTALL DEVICES TO MAXIMIZE PERFORMANCE AND MINIMIZE FALSE ALARMS. 18. T-TAP ONLY WHERE SHOWN ON THE DRAWINGS AND APPROVED BY THE MANUFACTURER'S DOCUMENTATION. 19. WHERE CONDUIT IS SPECIFIED OR REQUIRED BY CODE OR APPLICABLE STANDARDS FIRE ALARM CIRCUITS SHALL BE INSTALLED IN A MINIMUM OF 3/4" CONDUITS. CONDUIT FILL SHALL BE MAINTAINED PER THE APPLICABLE CEC.
CABLE SCHEDULE
20. PENETRATIONS THROUGH RATED ASSEMBLIES AND WALLS SHALL BE SEALED WITH A LISTED SYSTEM THAT IS EQUAL TO OR EXCEEDS THE RATING OF THE ASSEMBLY.
MARK
21. WIRING SHALL BE UL APPROVED AS DESIGNATED IN THE FIRE ALARM SYSTEM WIRING SCHEDULE OR THE MANUFACTURER'S INSTALLATION MANUAL. FIRE ALARM CABLES SHALL BE PROVIDED WITH RED PVC JACKET. WIRING INSTALLED UNDERGROUND SHALL BE LISTED FOR WET LOCATION. 22. WIRING PULLED THROUGH A JUNCTION BOX OR BACK BOX SHALL TERMINATE AT A DEVICE, SYSTEM PANEL OR TERMINAL CABINET WITH NO SPLICES. SIZE BOXES PER WIRE FILL AS DEFINED IN THE CEC. PROVIDE A MINIMUM OF 6” OF LEAD WIRE FROM THE BOX TO CONNECT EACH DEVICE. 23. FIRE ALARM CABLES/CONDUCTORS SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS. 24. FIRE ALARM DEVICES SHALL BE CLEARLY LABELED DESIGNATING THE DEVICE ADDRESS OR CIRCUIT AND DEVICE NUMBER. ADDRESSABLE DEVICE LABELS SHALL BE AFFIXED DIRECTLY TO THE DEVICE THAT CARRIES THE ADDRESS. LABELS SHALL BE LOCATED ON THE DEVICES SUCH THAT THEY ARE VISIBLE FROM THE FLOOR LEVEL. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS. 25. UPON COMPLETION OF INSTALLATION CONDUCT A TEST OF THE SYSTEMS OPERATION IN ACCORDANCE WITH NFPA 72, 2016 EDITION CHAPTER 14 IN THE PRESENCE OF THE ARCHITECT AND THE INSPECTOR OF RECORD. COMPLETE REQUIRED DOCUMENTATION IN ACCORDANCE WITH NFPA 72, 2016 EDITION CHAPTER 7. PROVIDE ORIGINAL TO INSPECTOR OF RECORD AND COPIES TO OWNER'S REPRESENTATIVE AND INSPECTOR OF RECORD.
B
26. THE INSPECTOR OF RECORD, AND THE OWNER'S REPRESENTATIVE SHALL RECEIVE FORTY EIGHT (48) HOURS NOTICE PRIOR TO THE DATE OF A FUNCTIONAL TEST AND FINAL INSPECTION. 27. THE INSPECTOR OF RECORD AND THE ARCHITECT SHALL RECEIVE ONE (1) WEEKS NOTICE FOR A FINAL PUNCH LIST WALK. 28. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE SYSTEM ACCESS REQUIREMENTS WITH OTHER TRADES, SPECIFICALLY SERVICE ACCESS TO ALL DEVICE LOCATIONS. INITIATING DEVICES SHALL BE INSTALLED IN A MANNER THAT PROVIDES ACCESSIBILITY FOR PERIODIC INSPECTION TESTING AND MAINTENANCE (NFPA 72, 2016 EDITION SECTION 17.4.5). 29. THE FOLLOWING SHALL BE COMPLETED AND SUBMITTED TO THE ENGINEER FOR A FINAL TO BE GRANTED: a. AS-BUILT DRAWINGS, PROGRAMMING DOCUMENTS, SCHEMATICS (DEVICE & EQUIPMENT CUTSHEETS), AND MANUALS PER SPECIFICATIONS. PROVIDE SUCH DOCUMENTS IN PAPER FORM AND ON CD. b. A ½ SIZE LAMINATED POSTING OF THE AS-BUILT PRINTS AT THE FIRE ALARM CONTROL PANEL. c. TYPED RECORD OF COMPLETION PER NFPA 72. d. ITEMS ON A PUNCH LIST SHALL BE COMPLETE AND SIGNED OFF BY THE INSPECTOR OF RECORD. e. ACCEPTANCE OF THE FUNCTIONAL TEST SIGNED OFF BY THE INSPECTOR OF RECORD.
ISSUED
MANUFACTURER
DESCRIPTION
USAGE
I
N/A
2#14 THWN
INITIATION DEVICE CIRCUIT
N
N/A
2#14 THWN
NOTIFICATION APPLIANCE CIRCUIT
P
N/A
2#14 THWN
24V POWER
S
WEST PENN WIRE, OR EQUAL
#60980B, FPLP 18/2 UNSHIELDED
SIGNALING LINE CIRCUIT
SU
WEST PENN WIRE, OR EQUAL
#AQC224, FPL 18/2 UNSHIELDED
SIGNALING LINE CIRUIT UNDERGROUND
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
NOTES: 1. ALL CABLES SHALL BE RUN IN CONDUIT. 2. ALL CABLES & WIRES SHALL TERMINATE AT TERMINALS. NO SPLICES. 3. ENDS OF STRANDED CABLES SHALL BE TWISTED AND SOLDERED.
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
30. ALL VALVES CONTROLLING THE WATER SUPPLY FOR AUTOMATIC SPRINKLER SYSTEMS AND WATERFLOW SWITCHES ON ALL SPRINKLER SYSTEMS SHALL BE ELECTRICALLY MONITORED VIA SUPERVISORY OR TAMPER SWITCHES WHERE THE NUMBER OF SPRINKLERS IS TWENTY OR MORE. 31. FINAL ACCEPTANCE TEST TO INCLUDE TESTING THE CONNECTION BETWEEN THE FIRE ALARM PANEL AND MONITORING STATION. 32. INSPECTION AND TESTING TO COMPLY WITH NFPA 72, CHAPTER 14 REQUIREMENTS, AND DOCUMENTED ON THE SYSTEM RECORD OF COMPLETION FORMS, FIGURES 7.8.2(a) THROUGH 7.8.2(f) AS APPLICABLE.
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
33. FIRE ALARM MANUAL PULL STATIONS SHALL MEET THE CALIFORNIA ACCESSIBILITY REQUIREMENTS OUTLINED IN THE CBC ("CONTROLS AND OPERATING MECHANISMS SHALL BE OPERABLE WITH ONE HAND AND NOT REQUIRED TIGHT-GRASPING, PINCHING OR TWISTING OF THE WRIST. THE FORCE TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 POUNDS OF FORCE"). 34. CBC 907.6.6.3 (SFM AMMENDMENT) REQUIRES FIRE ALARMS TO "TRANSMIT THE ALARM, SUPERVISORY AND TROUBLE SIGNALS TO AN APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. THE SUPERVISING STATION SHALL BE LISTED AS EITHER UUFX (CENTRAL STATION) OR UUJS (REMOTE & PROPRIETARY) BY THE UNDERWRITES LABORATORY INC. (UL) OR OTHER APPROVED LISTING AND TESTING LABORATORY OR SHALL COMPLY WITH THE REQUIREMENTS OF FM 3011". 35. DUCT SMOKE DETECTORS TO BE PROVIDED BY FIRE ALARM CONTRACTOR AND INSTALLED BY MECHANICAL CONTRACTOR. FIRE ALARM CONTRACTOR TO WIRE DETECTORS INTO FIRE ALARM SYSTEM. WIRING FROM DUCT DETECTOR CONTACTS TO MECHANICAL UNITS FOR UNIT SHUTDOWN TO BE PROVIDED BY MECHANICAL.
A
TITLE
SYMBOLS NOTES & SCHEDULES
5/15/2019 9:18:18 AM
SHEET
FA-001
017294 LIONAKIS 2017
2
3
4
5
1"
1
KEYED NOTES:
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
LOCATE EXISTING 1-1/4"C., STUB AND EXTEND TO FIRE ALARM TERMINAL CABINET 'FATC' AS SHOWN. REFER TO ONE LINE DIAGRAM 1/FA-601 FOR CABLE REQUIREMENTS.
APP. 02-117123
REVIEWED FOR
INSTALL NEW CABL IN EXISTING FIRE ALARM CONDUIT. PULL PAST EXISTING CABLES WHERE POSSIBLE. REMOVE EXISTING CABLES AND REPLACE WITH NEW TO MATCH EXISTING REMOVED WHERE REQUIRED TO ADD NEW CABLE IN EXISTING CONDUIT. REFER TO ONE LINE DIAGRAM 1/FA-601 FOR CABLE REQUIREMENT.
3
CONNECT NEW CABLE TO EXISTING SIGNALING LINE CIRCUIT IN EXISTING PANEL.
(E)
ACS
✔
✔
07/03/2019
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
D (E )
FLS
✔
DATE:
18 "
SD P
CONSULTANT
P SD 18"
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
consulting mechanical and electrical engineers
ER
SS14
REG I S T
I N E ER
T JOIN (E)
NO
ENG
PRO F E S S I ONA ED NO R. ROMA L I G
12 SS
NCH TRE
6 SD0
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
0 1/4" 1/2"
SS
2
INC:
E17247 EXP. 6/30/18
W " D 3/4 (E)
S
TA
EL
TE
EC TR I CA
O F CA L
L
I
A
2"
1
N I F OR
S S13
SEAL 11 SS
) (E 4" SS P S= 0 03 0.
P
05
PROJECT
FW14
SD 8" (E)
P
TEHAMA CENTER STUDENT SERVICE
P 05
05
SD
770 DIAMOND AVE. RED BLUFF, CA 96080
SD
2 SD
SD 6" (E)
SD 8" (E)
SD
C
23
SD 8" (E)
(E) FIRE ALARM CONTROL PANEL IN RECORDS / ADMISSIONS OFFICE (A# = 02-109288)
2
( E)
W
1
2" ) 1 (E
3
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
SD
05
24
3"
SD05
P SS
ISSUED G2
(E)
) AIN E M RC (FO SSP
" ) 4 (E
MARK
15 SD
(E)
SD
3 ING ILD 0 BU 98.0 ) E 2 ( = FF
06 SS
18" (E)
SDP
SD
05
SD
(E)
CLIENT P SD
02
6"
ING ILD BU 7.80 9 =2 FF
SS
DW 2"
(E)
05
2
P
3
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
FW 01
SD
05
W 6"
DATE 01/04/2019 05/17/2019
6"
P SD 05
(E)
6"
FW
SS
04 SS
(E)
. EC EL ULT VA
SD
05
1 S S0
2
W 01
) (E
) (E
T. & AT ULT VA
(E) LIGHTING BOX
SD
18 SD " ) 4 (E
(E) FIRE WATER BOX
05
P SS
) (E
8"
P SD
4"
P SD
" ) 6 (E
P SS
(E) ELEC. BOX
SS
) (E
WV
07
B ) (E
2 ING ILD 84 BU 7. ) =29 E ( FF
~
. EC EL OX B
G2
1" E PIP
FW
4"
DW 2"
6"
) (E
R TE WA
(E)
(E)
2 05
) (E
SD
05
P SS
SD
6"
(E)
W
DW
DW
P SS
SD
10
NO ING RK PA
SD
WP H
(299.5)
8"
P SD
AGENCY
(297.8)
P2 SD
(E) UTILITY VAULT
09
(E)
6"
FW
NO ING RK PA
FW08
(297.6)
(297.7)
(E) ICV
(E)ICV
FW14
4
3 F W1
P SD
(E) MAILBOX
F W12
(297.6)
(E) FH
(E) FLAG POLE
F W11
) (E
NO ING RK PA
" 24
B TA (E)
(299.4)
P SD
LE
P8 SD
FW12
(297.5)
P5 SD
(299.6)
) (E
(297.7)
(297.4)
(299.3)
8"
(297.4)
P9 SD
ED OS OP G PR ILDIN 8.5 U 29 B = FF
W
(297.5)
(297.7)
SD28
(299.2)
D 01 FW
(E) FH
H
WP (E) WATER BOX W12
W08
) (E
8"
(E) WATER STRUCTURE
W
(297.4)
P6 SD
W
A
H WP
P7 SD
14 FW
(E) RPP
(297.6)
10 FW W03
(E) ICV W04
W0 1
(E) WATER METER
P1 SD
) (E
1 FA-101
" 15
SD
P
FIRE ALARM SITE PLAN 1" = 20'-0"
4
3 P1 SD 2 P1 SD
(E) ICV
(E) WATER BOX (E) IRRI. CONTROL PANEL
10 DP
S FIRE ALARM TERMINAL CABINET 'FATC'.
3 FW0
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
) (E
3 SDP
(299.1) R LA PIL (E)
5/15/2019 9:18:19 AM
LIONAKIS 2017
SD
05
6"
SDP1
2" (E)
2"
33
017294
1
FW
4"
SD
W
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
05
8"
MANAGEMENT
SD
(E)
(E)ICV
(E) 9"∅ SEWER LID
(E) UNDERGROUND FIRE ALARM PULL BOX, TYPICAL.
P SD
) (E
(E) FIRE ALARM BOX
8"
TITLE
FIRE ALARM SITE PLAN
1 P1 SD
SHEET
FA-101
2"
1
2
3
4
5
SHEET NOTES: IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
APP. 02-117123
0 1/4" 1/2"
1. ADDRESSES FOR ADDRESSABLE DEVICES TO BE DETERMINED IN FIELD BASED ON AVAILABLE ADDRESSES IN EXISTING PANEL PROGRAM.
SS
INC:
REVIEWED FOR FLS
✔
ACS
✔
✔
07/03/2019
DATE:
1
D
2
3
4
5
6
7
1
MOUNT WITHIN 3'-0" OF PEAK.
2
MOUNT TO MULLION.
3
MOUNT FIRE ALARM DOCUMENTS BOX 'FAD' ON WALL BELOW 'NAC'
4
MOUNT AT TOP OF LIGHT WELL.
5
NOTIFICATION CIRCUIT EXTENDER PANEL 'NAC'.
6
FIRE ALARM TERMINAL CABINET 'FATC'. PROVIDE ISOLATION MODULE MOUNTED INSIDE CABINET.
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com CONSULTANT
E
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
10'-0"
consulting mechanical and electrical engineers
126
128
130
132
101
10'-0"
11'-0"
10'-0"
10'-0"
102
11'-0"
E17247 EXP. 6/30/18 TA
S
10'-0"
ADMIN OFFICE
12'-0"
EL
TE
EC TR I CA
O F CA L
L
I
A
CLASSROOM/LOBBY OVERFLOW
ER
COUNSELOR
REG I S T
COUNSELOR
I N E ER
COUNSELOR
NO
CAMPUS SAFETY
PRO F E S S I ONA ED NO R. ROMA L I G
D
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
KEYED NOTES:
N I F OR
HALLWAY 100D
LOBBY
10'-0"
11'-0"
100
C.4 10'-0"
10'-0"
10'-0"
10'-0"
SEAL
STUDENT SERVICES
COUNSELOR
COUNSELOR
COUNSELOR
COUNSELOR
125
127
129
131
ADMIN OFFICE 104
103
12'-0"
C
FIRE RISER 10'-0"
HALLWAY
151
HALLWAY
WORK CENTER
10'-0"
100C
100B
9'-0"
100A IDF CONFERENCE C
12'-0"
121
124
10'-0"
10'-0"
VET CENTER 10'-0"
STORAGE
10'-0" CUSTODIAL
10'-0" RESTROOM
120
119
118
10'-0"
123
VET OFFICE
STUDENT SERVICES
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
108
107
106
105
11'-0"
11'-0"
11'-0"
B.6
PROJECT
TEHAMA CENTER STUDENT SERVICE
11'-0"
122 10'-0" 10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
117
116
115
114
113
112
10'-0" FACULTY OFFICE
10'-0" FACULTY OFFICE
111
770 DIAMOND AVE. RED BLUFF, CA 96080
10'-0" FACULTY OFFICE
110
3
109
CLIENT
B
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
A
2 FA-111
ISSUED
FLOOR PLAN - CEILING HEIGHTS
MARK
1/8" = 1'-0"
1
2
3
4
5
6
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
7
N2-4 WP H
E
B
N
COUNSELOR
CAMPUS SAFETY
126
S
P
S
COUNSELOR
128 S
130 P S
S
P
132
S
S
N
N
(DOAS-1) S
P
S
P
P
15
S COUNSELOR
H
N2-1 N
COUNSELOR
S P
S
P
S
COUNSELOR S 129
127
P
S
100 S
S
P S
S
1
S
P
1
1
CO
S
R
S
1
P
N
131
N2-5
AGENCY
N S
COUNSELOR
P
S
15
P
N
75
75 N2-6
P
P N2-8 15
P
S
C.4
P 1
S STUDENT SERVICES
N ADMIN OFFICE
103
104
N
C
I AIM
WF
S
S I VS FIRE RISER P
75
N
N1-2
S
P
N HALLWAY
15 N1-1
100C
NAC
S
CONFERENCE
151
P S
P
S
N
P
121
S
15
S
P
P N
S
S
P
5
PNL 'NAC' S
6
PNL 'FATC' P
P
N1-6
S
VET CENTER
VET OFFICE
123
122
120
119
P S FATC
S
S
CUSTODIAL S
N P
S
1
S S
4
P
15 N1-7 P S RESTROOM
STUDENT SERVICES
S
S 4
P
S
108
118
N
S
1
N2-7
100B
15
S
P S
S
4
P
S
S
4
P
P
STUDENT SERVICES
STUDENT SERVICES
FACULTY OFFICE
107
106
105
N
B.6
S S
P
S
N1-4
75
P
STORAGE P
P
S
A
S
3
S N1-3
1
IDF
15 N1-8
N
100A
S
124
S
HALLWAY
WORK CENTER
F
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
2
S
125 NAC
F
WP
P
S
S
R
LOBBY
N2-3 1
S N2-9
CO
LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
102 S
101
P
S
S (AC-1)
S
HALLWAY 100D
P
P
P P
S
P
S
S
S
S
P
S S
CLASSROOM/LOBBY OVERFLOW
S
S 15 N2-2
MANAGEMENT
ADMIN OFFICE
COUNSELOR
P
P
D
F
2
S S
P
FACULTY OFFICE
FACULTY OFFICE
S FACULTY OFFICE
117
116
115
15
1
S
S
P
FACULTY OFFICE
S S
P
S
P
S
S
P
S
FACULTY OFFICE
FACULTY OFFICE
FACULTY OFFICE
113
112
111
FACULTY HALLWAY
N
S S
114
P
P
1
S
S
S
P
S FACULTY OFFICE
FACULTY OFFICE
110
109
TITLE
FLOOR PLAN - FIRE ALARM
B
P N1-9
15
150
H
A
N1-5 WP
5/15/2019 9:18:22 AM
SHEET PLAN NORTH
1 FA-111
FLOOR PLAN - FIRE ALARM 1/8" = 1'-0"
FA-111
017294 LIONAKIS 2017
2"
1
2
3
4
5
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
1"
F.A. ABOVE CEILING HEAT DETECTOR, 5 MOUNT TO UNDERSIDE OF BEAM.
APP. 02-117123
INC:
REVIEWED FOR
0 1/4" 1/2"
SS
F.A. SPEAKER/STROBE F.A. STROBE OR COMBINATION F.A. STROBE/HORN, TYPICAL
FA SPEAKER OR FA HORN, MOUNT AT 90" MIN.
✔
07/03/2019
DATE:
F.S.R. BELL
ACS
✔
B F
SYNCHRONIZATION MODULE
FINISHED CEILING DSM
BOTTOM OF DEVICE 6" TOP OF PANEL
FACP TO INTERFACE DEVICE(S) 96" MAX. 2
90" 1 NO
C
FIRE
96"
ALARM
PU L L D OWN
80" MIN. 2
NC
72"
+42"
+48" 3
4 FINISHED FLOOR
FIRE ALARM ADDRESSABLE DUAL MONITOR MODULE
+ -
RED
RED
BLACK
BLACK
+ -
DETAIL NOTES:
TO NEXT SLC DEVICE WHERE APPLICABLE
1
PETERS
NFPA 18.4.8.1 *WHERE CEILING HEIGHTS ALLOW, AUDIBLE APPLIANCES SHALL HAVE THEIR TOPS AT HEIGHTS ABOVE FINISH FLOOR OF NOT LESS THAN 90" AND BELOW FINISHED CEILING OF NOT LESS THAN 6".
engineering
consulting mechanical and electrical engineers
TO NEXT SLC DEVICE WHERE APPLICABLE
CONNECT INTERFACE DEVICE(S) TO NORMALLY OPEN (NO) OR NORMALLY CLOSED (NC) CONTACTS AS REQUIRED.
2.
EMERGENCY CONTROL FUNCTION INTERFACE DEVICES SHALL BE LOCATED WITHIN 3 FT OF THE COMPONENT CONTROLLING THE EMERGENCY CONTROL FUNCTION (NFPA 72, 2016 EDITION SECTION 21.2.3).
WIRING SHALL NOT BE LOOPED THROUGH DEVICE TERMINALS. INPUT AND OUTPUT WIRING DEVICE CONNECTIONS SHALL BE MADE ON SEPARATE TERMINALS OR SHALL BE SEPARATE WIRE LEADS MOUNTED UNDER A COMMON TERMINAL. THE MONITORING OF CIRCUIT INTEGRITY RELIES ON THE INTERRUPTION OF THE WIRING CONTINUITY WHEN THE CONNECTION TO THE INITIATING DEVICE IS LOST (NFPA 72, 2016 EDITION SECTION A.17.4.6).
3.
FIRE ALARM WIRING SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
4.
ADDRESSABLE DUAL INPUT MODULE
4
NONE
FA-501
WIRING SHALL NOT BE LOOPED THROUGH DEVICE TERMINALS. INPUT AND OUTPUT WIRING DEVICE CONNECTIONS SHALL BE MADE ON SEPARATE TERMINALS OR SHALL BE SEPARATE WIRE LEADS MOUNTED UNDER A COMMON TERMINAL. THE MONITORING OF CIRCUIT INTEGRITY RELIES ON THE INTERRUPTION OF THE WIRING CONTINUITY WHEN THE CONNECTION TO THE INITIATING DEVICE IS LOST (NFPA 72, 2016 EDITION SECTION A.17.4.6).
2
NFPA 18.5.4.1 VISUAL APPLIANCES SHALL HAVE ENTIRE LENS AT HEIGHTS ABOVE FINISHED FLOOR OF NOT LESS THAN 80" AND NO GREATER THAN 96" OR 6" BELOW CEILING, WHICHEVER IS LOWER.
3
NFPA 17.14.4 THE OPERABLE PART OF EACH MANUAL FIRE ALARM BOX SHALL NOT BE LESS THAN 42" AND NOT MORE THAN 48" ABOVE THE FLOOR.
4
MAINTAIN CONSISTENT HEIGHTS THROUGH OUT PROJECT.
5
FIRE ALARM WIRING SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
ADDRESSABLE OUTPUT MODULE
1
NONE
FA-501
PRO F E S S I ONA ED NO R. ROMA L I
I N E ER
1.
NO
FA-501
BLACK
-
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
E17247 EXP. 6/30/18 TA
S
7
BLACK
+
NOTES:
NOTES:
2.
RED
ER
FROM PANEL OR PREVIOUS SLC DEVICE
+ FROM PANEL OR PREVIOUS SLC DEVICE -
NORMALLY OPEN CONTACT DEVICE
RED
REG I S T
NORMALLY OPEN CONTACT DEVICE
1.
CONSULTANT
EOL
G
EOL
INSTALL CEILING ACCESS PANEL AT ALL NON-LAYIN TYPE CEILINGS, WHERE HEAT DETECTOR ABOVE CEILING IS INDICATED.
EL
TE
EC TR I CA
O F CA L
L
I
A
FIRE ALARM ADDRESSABLE RELAY MODULE
D
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
FLS
✔
N I F OR
DEVICE MOUNTING DETAIL NONE SEAL
24VDC FROM PANEL OR + POWER SUPPLY -
RED
RED
BLACK
+
BLACK
-
TO NEXT DEVICE WHERE APPLICABLE
FIRE ALARM HORN STROBE
C
PROJECT +
FROM PANEL OR PREVIOUS APPLIANCE
+ -
BLUE
BLUE
BROWN
BROWN
+ -
FIRE ALARM ADDRESSABLE FIRE/CO DETECTOR W/ SOUNDER BASE TO NEXT APPLIANCE OR EOL RESISTOR
2.
3.
+
FIRE ALARM ADDRESSABLE MANUAL PULL STATION
NOTES: 1.
+ FROM PANEL OR PREVIOUS SLC DEVICE -
AN AVERAGE AMBIENT SOUND LEVEL GREATER THAN 105 dBA SHALL REQUIRE THE USE OF A VISIBLE NOTIFICATION APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.4.1.1) THE TOTAL SOUND PRESSURE LEVEL PRODUCED BY COMBINING THE AMBIENT SOUND PRESSURE LEVEL WITH ALL AUDIBLE NOTIFICATION APPLIANCES OPERATING SHALL NOT EXCEED 110 dBA AT THE MINIMUM HEARING DISTANCE (NFPA 72, 2016 EDITION SECTION 18.4.1.2)
+ FROM PANEL OR PREVIOUS SLC DEVICE -
THE ALARM AUDIBLE SIGNAL PATTERN USED TO NOTIFY OCCUPANTS OF THE NEED TO EVACUATE (LEAVE THE BUILDING) OR RELOCATE (FROM ONE AREA TO ANOTHER) SHALL BE THE STANDARD ALARM EVACUATION SIGNAL CONSISTING OF A THREE-PULSE TEMPORAL PATTERN (NFPA 72, 2016 EDITION SECTION 18.4.2.1).
RED
RED
BLACK
BLACK
+ -
FA-501
1.
2.
WHERE MANUAL FIRE ALARM BOXES ARE INSTALLED, ADDITIONAL MANUAL FIRE ALARM BOXES SHALL BE PROVIDED SO THAT THE TRAVEL DISTANCE TO THE NEAREST MANUAL FIRE ALARM BOX WILL NOT EXCEED 200 FT, MEASURED HORIZONTAL ON THE SAME FLOOR (NFPA 72, 2016 EDITION SECTION 17.14.8.5).
6.
WHERE MORE THAN TWO VISIBLE NOTIFICATION APPLIANCES OR GROUPS OF SYNCHRONIZED APPLIANCES ARE IN THE SAME ROOM OR ADJACENT SPACE IN THE FIELD OF VIEW ALL APPLIANCES ARE REQUIRED SYNCHRONIZE TOGETHER (NFPA 72, 2016 EDITION SECTION 18.5.5.4.2).
3.
WHERE SHOWN ON DRAWINGS, MANUAL FIRE ALARM BOXES SHALL BE MOUNTED ON BOTH SIDES OF GROUPED OPENINGS OVER 40FT IN WIDTH, AND WITHIN 5 FT OF EACH SIDE OF THE GROUPED OPENING (NFPA 72, 2016 EDITION SECTION 17.14.8.6).
7.
WIRING SHALL NOT BE LOOPED THROUGH DEVICE TERMINALS. INPUT AND OUTPUT WIRING DEVICE CONNECTIONS SHALL BE MADE ON SEPARATE TERMINALS OR SHALL BE SEPARATE WIRE LEADS MOUNTED UNDER A COMMON TERMINAL. THE MONITORING OF CIRCUIT INTEGRITY RELIES ON THE INTERRUPTION OF THE WIRING CONTINUITY WHEN THE CONNECTION TO THE INITIATING DEVICE IS LOST (NFPA 72, 2016 EDITION SECTION A.17.4.6).
4.
FIRE ALARM WIRING SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
5.
5
NONE
FA-501
RED
BLACK
+
BLACK
-
TO NEXT SLC DEVICE WHERE APPLICABLE
1.
SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN 1'-0" OF A FIRE SPRINKLER HEAD.
2.
DETECTORS SHOULD NOT BE LOCATED IN A DIRECT AIRFLOW OR CLOSER THAN 36 IN. FROM AN AIR SUPPLY DIFFUSER OR RETURN AIR OPENING. SUPPLY OR RETURN SOURCES LARGER THAN THOSE COMMONLY FOUND IN RESIDENTIAL AND SMALL COMMERCIAL ESTABLISHMENTS CAN REQUIRE GREATER CLEARANCE TO SMOKE DETECTORS. SIMILARLY, SMOKE DETECTORS SHOULD BE LOCATED FARTHER AWAY FROM HIGH VELOCITY AIR SUPPLIES (NFPA 72, 2016 EDITION SECTION A.17.7.4.1).
3.
WIRING SHALL NOT BE LOOPED THROUGH DEVICE TERMINALS. INPUT AND OUTPUT WIRING DEVICE CONNECTIONS SHALL BE MADE ON SEPARATE TERMINALS OR SHALL BE SEPARATE WIRE LEADS MOUNTED UNDER A COMMON TERMINAL. THE MONITORING OF CIRCUIT INTEGRITY RELIES ON THE INTERRUPTION OF THE WIRING CONTINUITY WHEN THE CONNECTION TO THE INITIATING DEVICE IS LOST (NFPA 72, 2016 EDITION SECTION A.17.4.6).
WHERE SHOWN ON DRAWINGS, MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN 5 FT OF EACH EXIT DOORWAY ON EACH FLOOR (NFPA 72, 2016 EDITION SECTION 17.14.8.4).
THE FLASH RATE SHALL NOT EXCEED TWO FLASHES PER SECOND (2 Hz) NOR BE LESS THAN ONE FLASH EVERY SECOND (1 Hz) THROUGHOUT THE LISTED VOLTAGE RANGE OF THE APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.5.3.1).
HORN STROBE DETAIL
RED
CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
NOTES: TO NEXT SLC DEVICE WHERE APPLICABLE
5.
8.
8
TO ENSURE THAT AUDIBLE PUBLIC MODE SIGNALS ARE CLEARLY HEARD THEY SHALL HAVE A SOUND LEVEL AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 dB ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS, WHICHEVER IS GREATER, MEASURED 5 FT ABOVE THE FLOOR IN THE AREA REQUIRED TO BE SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (dBA) (NFPA 72, 2016 EDITION SECTION 18.4.3.1).
770 DIAMOND AVE. RED BLUFF, CA 96080
-
3
NOTES: 4.
TEHAMA CENTER STUDENT SERVICE
-
4.
WHERE DETECTORS ARE INSTALLED BUT NOT OPERATIONAL DURING CONSTRUCTION, THEY SHALL BE PROTECTED FROM CONSTRUCTION DEBRIS, DIRT, AND DAMAGE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND VERIFIED TO BE OPERATING IN ACCORDANCE WITH THE LISTED SENSITIVITY, OR THEY SHALL BE REPLACED PRIOR TO THE FINAL COMMISSIONING OF THE SYSTEM (NFPA 72, 2016 EDITION SECTION 17.7.1.11.2).
WIRING SHALL NOT BE LOOPED THROUGH DEVICE TERMINALS. INPUT AND OUTPUT WIRING DEVICE CONNECTIONS SHALL BE MADE ON SEPARATE TERMINALS OR SHALL BE SEPARATE WIRE LEADS MOUNTED UNDER A COMMON TERMINAL. THE MONITORING OF CIRCUIT INTEGRITY RELIES ON THE INTERRUPTION OF THE WIRING CONTINUITY WHEN THE CONNECTION TO THE INITIATING DEVICE IS LOST (NFPA 72, 2016 EDITION SECTION A.17.4.6).
5.
WHERE DETECTION IS NOT REQUIRED DURING CONSTRUCTION, DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER ALL OTHER CONSTRUCTION TRADES HAVE COMPLETED CLEANUP (NFPA 72, 2016 EDITION SECTION 17.7.1.11.3).
FIRE ALARM WIRING SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
6.
FIRE ALARM WIRING SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
ADDRESSABLE PULL STATION
2
NONE
FA-501
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
ADDRESSABLE FIRE-CO NONE
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
AGENCY
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
FIRE ALARM ADDRESSABLE SMOKE DETECTOR
FIRE ALARM STROBE + FROM PANEL OR PREVIOUS SLC DEVICE -
FROM PANEL OR PREVIOUS APPLIANCE
+ -
BLUE
BROWN
BLUE
BROWN
+ -
AN AVERAGE AMBIENT SOUND LEVEL GREATER THAN 105 dBA SHALL REQUIRE THE USE OF A VISIBLE NOTIFICATION APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.4.1.1)
2.
THE FLASH RATE SHALL NOT EXCEED TWO FLASHES PER SECOND (2 Hz) NOR BE LESS THAN ONE FLASH EVERY SECOND (1 Hz) THROUGHOUT THE LISTED VOLTAGE RANGE OF THE APPLIANCE (NFPA 72, 2016 EDITION SECTION 18.5.3.1).
5.
9 FA-501
-
TO NEXT SLC DEVICE WHERE APPLICABLE
1.
SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN 1'-0" OF A FIRE SPRINKLER HEAD.
2.
DETECTORS SHOULD NOT BE LOCATED IN A DIRECT AIRFLOW OR CLOSER THAN 36 IN. FROM AN AIR SUPPLY DIFFUSER OR RETURN AIR OPENING. SUPPLY OR RETURN SOURCES LARGER THAN THOSE COMMONLY FOUND IN RESIDENTIAL AND SMALL COMMERCIAL ESTABLISHMENTS CAN REQUIRE GREATER CLEARANCE TO SMOKE DETECTORS. SIMILARLY, SMOKE DETECTORS SHOULD BE LOCATED FARTHER AWAY FROM HIGH VELOCITY AIR SUPPLIES (NFPA 72, 2016 EDITION SECTION A.17.7.4.1).
3.
4.
BLACK
+
EOL
TO NEXT APPLIANCE OR EOL RESISTOR
1.
3.
BLACK
RED
NOTES:
NOTES:
A
RED
4.
WHERE MORE THAN TWO VISIBLE NOTIFICATION APPLIANCES OR GROUPS OF SYNCHRONIZED APPLIANCES ARE IN THE SAME ROOM OR ADJACENT SPACE IN THE FIELD OF VIEW ALL APPLIANCES ARE REQUIRED SYNCHRONIZE TOGETHER (NFPA 72, 2016 EDITION SECTION 18.5.5.4.2).
WHERE DETECTION IS NOT REQUIRED DURING CONSTRUCTION, DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER ALL OTHER CONSTRUCTION TRADES HAVE COMPLETED CLEANUP (NFPA 72, 2016 EDITION SECTION 17.7.1.11.3).
FIRE ALARM WIRING SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
6.
FIRE ALARM WIRING SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
NONE
FA-501
+ FROM PANEL OR PREVIOUS SLC DEVICE -
WHERE DETECTORS ARE INSTALLED BUT NOT OPERATIONAL DURING CONSTRUCTION, THEY SHALL BE PROTECTED FROM CONSTRUCTION DEBRIS, DIRT, AND DAMAGE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND VERIFIED TO BE OPERATING IN ACCORDANCE WITH THE LISTED SENSITIVITY, OR THEY SHALL BE REPLACED PRIOR TO THE FINAL COMMISSIONING OF THE SYSTEM (NFPA 72, 2016 EDITION SECTION 17.7.1.11.2).
5.
6
NORMALLY OPEN CONTACT DEVICE
WIRING SHALL NOT BE LOOPED THROUGH DEVICE TERMINALS. INPUT AND OUTPUT WIRING DEVICE CONNECTIONS SHALL BE MADE ON SEPARATE TERMINALS OR SHALL BE SEPARATE WIRE LEADS MOUNTED UNDER A COMMON TERMINAL. THE MONITORING OF CIRCUIT INTEGRITY RELIES ON THE INTERRUPTION OF THE WIRING CONTINUITY WHEN THE CONNECTION TO THE INITIATING DEVICE IS LOST (NFPA 72, 2016 EDITION SECTION A.17.4.6).
WIRING SHALL NOT BE LOOPED THROUGH DEVICE TERMINALS. INPUT AND OUTPUT WIRING DEVICE CONNECTIONS SHALL BE MADE ON SEPARATE TERMINALS OR SHALL BE SEPARATE WIRE LEADS MOUNTED UNDER A COMMON TERMINAL. THE MONITORING OF CIRCUIT INTEGRITY RELIES ON THE INTERRUPTION OF THE WIRING CONTINUITY WHEN THE CONNECTION TO THE INITIATING DEVICE IS LOST (NFPA 72, 2016 EDITION SECTION A.17.4.6).
STROBE DETAIL
FIRE ALARM ADDRESSABLE INPUT MODULE
ADDRESSABLE SMOKE DETECTOR NONE
RED
BLACK
RED
BLACK
+ -
TO NEXT SLC DEVICE WHERE APPLICABLE
NOTES:
3 FA-501
1.
WIRING SHALL NOT BE LOOPED THROUGH DEVICE TERMINALS. INPUT AND OUTPUT WIRING DEVICE CONNECTIONS SHALL BE MADE ON SEPARATE TERMINALS OR SHALL BE SEPARATE WIRE LEADS MOUNTED UNDER A COMMON TERMINAL. THE MONITORING OF CIRCUIT INTEGRITY RELIES ON THE INTERRUPTION OF THE WIRING CONTINUITY WHEN THE CONNECTION TO THE INITIATING DEVICE IS LOST (NFPA 72, 2016 EDITION SECTION A.17.4.6).
2.
FIRE ALARM WIRING SHALL BE LABELED AT BOTH ENDS. REFER TO SPECIFICATIONS FOR LABELING REQUIREMENTS.
TITLE
DETAILS
ADDRESSABLE INPUT MODULE NONE
5/15/2019 9:18:22 AM
SHEET
FA-501
017294 LIONAKIS 2017
2"
1
2
3
4
5
S
1"
IDENTIFICATION STAMP DIV. OF THE STATE ARCHITECT
P
APP. 02-117123
0 1/4" 1/2"
100 P
S
125 P
S
131
P
129
P
S 127
P
S
S
100D
P
S
128
130
P
S
15
15 N1-9
D
N1-8
N1-7 15
15 N2-9
15
N2-8
75
N1-5
N1-6 15
WP
15
15
H
75
N1-4
N1-3
H N2-7
N2-6
N2-5
N2-4
N2-3
15 N2-2
121
CKT#1
P
P
S 124
123
P
S 151
S 100 P
S
100
WF
S
SS
F
S
100
S
S
DOAS-1
AC-1
1N, TYP WP H
P
S
122
CKT#2
AIM
2
IM
S 120
CKT#3 1P CKT#4
119
100A
P
S 117
P
S
P
P
S
S
P
P
S
100A
116
115
S 150
24V
P
P
S
114
S 118
P
S 102
P
S 103
P
S
P
104
100B
151 P
S
102
P
✔
P
S
VS
108
P
S 107
S
P
106
S
1919 Nineteenth Street Sacramento CA 95811 P 916.558.1900 F 916.558.1919 www.lionakis.com
P
105
1S, TYP. UON.
1S
N2-1
P
S
S
ACS
✔
07/03/2019
DATE:
R CO 101 1S,1P R CO 101
FLS
✔
1I
N1-1
N1-2 15
WP
75
75
P
S
FATC
NAC
P
S
132
100C
1N, TYP 15
REVIEWED FOR
100
P
1I
P
S
126
P
S
S 113
P
S
P
P
S
112
111
S
S 110
P
S
P
CONSULTANT
109
P
2411 Alhambra Blvd, Ste. 100 Sacramento, CA 95817 Tel (916) 447-2841 www.peterseng.com Job no. 18.003
PETERS
engineering
150
consulting mechanical and electrical engineers
I N E ER
E17247 EXP. 6/30/18
S
TA
EL
TE
EC TR I CA
O F CA L
L
I
A
ER REG I S T
NO
PRO F E S S I ONA ED NO R. ROMA L I G
1SU
ENG
IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLY
S
P
S
INC:
N I F OR
(E) FACP
SEAL
1 FA-601
FIRE ALARM ONE LINE DIAGRAM NONE
PROJECT
C
TEHAMA CENTER STUDENT SERVICE 770 DIAMOND AVE. RED BLUFF, CA 96080 3 CLIENT
SHASTA-TEHAMA-TRINITY JOINT COMMUNITY COLLEGE DISTRICT
ISSUED
MARK
DATE 01/04/2019 05/17/2019
DESCRIPTION DSA SUBMITTAL DSA BACKCHECK
B
MANAGEMENT LIONAKIS PROJECT NO: CLIENT PROJECT NO: COPYRIGHT:
017294 LIONAKIS 2017
C:\Users\jmoberly\Documents\18.003 Tehama SSB MEP- R18_jmoberly.rvt
AGENCY
A
TITLE
ONE LINE DIAGRAM AND CALCS
5/15/2019 9:18:23 AM
SHEET
FA-601