ECN March 2021

Page 38

SPECIAL FEATURE

TEST EQUIPMENT

A HANDY GUIDE TO EICRS Gary Parker, ECA Technical Manager, dives into the rationale behind the different codes that make up an EICR, and what they all mean.

W

ith the second Amendment to the 18th Edition Wiring Regulations just around the corner, it’s as important as ever to stay up to speed with the different codes that make up those all-important electrical installation condition reports (EICRs). To demystify the nuances of which codes apply to which faults, and to help you carry out smoother inspections, read on.

Codes have consequences

Who decides? The inspector is the only person who can make an informed decision about what code is suitable in any given situation. This is because they are on-site and can see defects first-hand and make an informed call on how safe an installation is. As an aside, it is important to note that any item raised should be set against the requirements of the Wiring Regulations (BS 7671:2018), not against the inspector’s personal judgement or preferences.

Decision tree for selecting an appropriate code during an EICR

It is extremely important to understand the consequences of any code raised during an EICR. For instance, both a C1 and C2 result in an ‘unsatisfactory’ outcome. Therefore, overzealous use of these codes can potentially cause unwarranted disruption to the client, their building and possibly their business. For example: if an installation is found to be lacking RCD protection for socket outlets, most guidance would recommend a C3 code. Should a contractor decide to instead raise a C2, then the client could be looking at a significant cost or inconvenience. Of course, BS 7671 does take account of cost, and cost must not dictate decisions concerning electrical safety. But the safety, practical and cost implications of getting a code wrong, whichever way it may be, can be highly significant. An inspector should not reduce a code from a more serious to a lesser code just because the client would like it that way. The inspector has been employed as a technical expert in electrical safety and must not let their professional decisions become compromised by any external influence.

Is it a type of risk assessment? Indeed it is. When considering what code is relevant to any given situation, the inspector needs to consider the environment and the potential risk of damage or injury. So, simply saying that scenario ‘x’ results in outcome ‘y’ is not always suitable. A nuanced decision-making process is required. To do this, we must first look at what the codes actually mean. •  C1 – Danger present: in this scenario, there is an immediate danger of shock or fire to persons, property or livestock. •  C2 – Potentially dangerous: in this scenario, there is a fault that could potentially become dangerous (a hazard), but another fault or foreseeable action must occur in order for danger to arise. •  C3 – Improvement recommended: in this scenario, there is a defect against BS 7671, but it does not present any immediate or potential danger to people or property.

A PERCEIVED DEFECT IS LOCATED

C1 Recommend   urgent action

YES

Does it present an imminent danger, to the persons using the installation, from shock or fire? NO

C2 Although there is no immediate risk, action is taken as a matter of urgency to remedy the defect

Could this defect become dangerous if a fault or other foreseeable defect were to occur? NO C3 Consider upgrading the installation

The decision tree, right, expands this further.

GTC 400 C PROFESSIONAL THERMAL CAMERA Precise. Reliable. Efficient.

YES

It is of course essential that the inspector is well-versed in the requirements of the latest version of the Wiring Regulations. If need be, before raising a coded item, the inspector should always be in a position to reference a BS 7671 Regulation number on the issue in question, particularly if challenged.

Only defects against BS 7671 should be recorded The EICR is aimed specifically at defects against the requirements of BS 7671. The inspector should not raise a code against any defects noticed against other British Standards. They are, however, at liberty to raise comments or make notes about other issues or defects and to inform the client. Take the example of defective emergency light fittings. If they do not present any electrical hazard to the user, they are effectively safe and should not appear as a coded item on an EICR. However, this scenario may show a departure from BS 5266. In this case, it may be useful to inform the client on a separate document.

The last word Guidance material cannot take the place of the skill, knowledge and experience of the inspector. The ultimate decision is down to them. The recognised industry guidance is only a guide. It can be deviated from if the inspector is able to credibly present the reasons for doing so. For more information on EICRs (and any other electrotechnical issue), ECA’s technical assistance helpline is open to ECA Members and can be found at eca. co.uk/myECA.  ECA, eca.co.uk

Make the invisible visible

▶ Measuring range -10°C to +400°C ▶ Big 3.5" colour display to display measurements

▶ Infrared sensor resolution of 160 x120 (19,000 single measurement points)

▶ Visual camera integrated to save real image together with thermal images

It’s in your hands. Bosch Professional.

38  |  March 2021

Test Equipment – ECA.indd 38

electricalcontractingnews.com

@ElecConNews

/electricalcontractingnews

25/02/2021 15:57


Turn static files into dynamic content formats.

Create a flipbook

Articles inside

Company Showcase

17min
pages 44-48

HAL makes light work of safety testing

3min
pages 42-43

A quality first approach to EV charging

4min
page 41

Back to the future – detail on NAPIT’s latest publication dedicated to inspection and testing of electrical installations

4min
page 40

A handy guide to EICRs

5min
pages 38-39

Schaeffler takes standardised electrical design into new markets with EPLAN

3min
page 32

Lighting the way to a fully connected university

4min
page 33

Bosch’s GTC 400 C Professional Thermal Camera offers a variety of great functions

6min
pages 36-37

More ‘eyes’ on the network to stop power cuts before they happen

5min
pages 30-31

Taking energy performance to new heights in Swansea

2min
pages 28-29

Consultation opens on new code for construction product information

2min
pages 26-27

Scolmore looks at the need for suppliers to work collaboratively with wholesalers

4min
pages 24-25

Key Issue

4min
pages 16-17

Advertisement Feature

2min
page 20

Project Focus

2min
pages 18-19

Cover Story

4min
pages 10-11

Training

3min
pages 14-15

Contract News

10min
pages 12-13

Industry News

8min
pages 7-9

How antimicrobial sockets and switches can help to limit the spread of viruses

3min
pages 22-23
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.